Trane THD210G3R0B1KMC Voyager™ 17.5 Tons 230V Three Phase Commercial Packaged Gas/Electric Unit Specification

Add to My manuals
162 Pages

advertisement

Trane THD210G3R0B1KMC Voyagerâ„¢ 17.5 Tons 230V Three Phase Commercial Packaged Gas/Electric Unit Specification | Manualzz

Product Catalog

Packaged Rooftop Air Conditioners

Voyager™ Light Commercial – Cooling, Gas/Electric

12.5 to 25 Tons, 60 Hz

March 2017

RT-PRC028AC-EN

Introduction

Packaged Rooftop Air Conditioners

Through the years, Trane has designed and developed the most complete line of Packaged

Rooftop products available in the market today. Trane was the first to introduce the Micro— microelectronic unit controls—and has continued to improve and revolutionize this design concept.

The ReliaTel™control platform offers the same great features and functionality as the original

Micro, with additional benefits for greater application flexibility.

Voyager™ continues to provide the highest standards in quality and reliability, comfort, ease of service, and the performance of Trane light commercial products.

Trane customers demand products that provide exceptional reliability, meet stringent performance requirements, and are competitively priced. Trane delivers with Voyager.

Voyager features cutting edge technologies: reliable compressors, Trane engineered ReliaTel controls, computer-aided run testing, and Integrated Comfort™ Systems. So, whether you’re the contractor, the engineer, or the owner, you can be certain Voyager products are built to meet your needs.

Copyright

This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks

Trane and the Trane logo, CompleteCoat, Frostat, Integrated Comfort Systems, ReliaTel, Tracer,

Voyager, are trademarks of Trane in the United States and other countries. All trademarks referenced in this document are the trademarks of their respective owners.

Revision Summary

• Added New 17½ & 25 Tons Standard Efficiency models.

• Updated Features & Benefits, Model Number Description, General Data, Electrical Data,

Dimensional Data, Weight, Mechanical Specifications sections.

© 2017 Ingersoll Rand RT-PRC028AC-EN

Table of Contents

Features and Benefits

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Standard Features and Available Options

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Standard Features

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Variety of Options

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Factory or Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Other Benefits

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Application Considerations

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Selection Procedure

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Cooling Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Air Delivery Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Model Number Description

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Model Number Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

General Data

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Performance Data

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Controls

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125

Economizer Controls

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125

Zone Sensors

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125

Communication Interfaces

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128

Electrical Data

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129

Jobsite Connections

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141

Dimensional Data

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142

Weights

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151

Mechanical Specifications

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154

Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156

Factory or Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158

Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160

RT-PRC028AC-EN 3

4

Features and Benefits

Note: Packaged Rooftop units cooling, heating capacities, and efficiencies are AHRI certified within scope of AHRI Standard 340-360 (I-P) and ANSIZ21.47 and 10 CFR Part 431 pertaining to Commercial Warm Air Furnaces (gas heating units).

Standard Features and Available Options

Table 1.

Voyager™ Light Commercial control options — standard and optional

BACnet® Communications Interface (BCI)

Discharge Line Thermostat

Humidity Sensor

LonTalk® Communications Interface (LCI)

ReliaTel™ Microprocessor Controls

ReliaTel™ Options Module

Thermostat

Trane® Air-Fi™ Wireless Communication Interface

Trane® Communications Interface (TCI)

Wireless Zone Sensor

Zone Sensors and Remote Zone Sensors

(a)Refer to model number description for option availability

Standard

Features

Factory

Installed

X

X

X

Options (a)

Factory or

Field

Installed

X

Field

Installed

X

X

X

X

X

X

X

Table 2.

Voyager™ Light Commercial features - standard and optional

1-year Limited Parts Warranty

5-year Limited Compressor Warranty

5-year Limited Heat Exchanger Warranty (12½–17½ Tons); 1 Year on 20 and

25 Tons

2” MERV 8 Filters or 2” MERV 13 Filters with Filter Removal Tool

2” throwaway filters

3 Stages of Cooling Capability on 12½–20 Tons, 4 Stages of Cooling Capability on 25 Tons (High Efficiency Units Only)

Anti-Short Cycle Timer

Barometric Relief

Belt Drive Motors

Clogged Filter/Fan Failure Switch

CO

2

Sensor

CO

2

Sensor Wiring (Wiring Only)

Colored and Numbered Wiring

Complete Coat™ Microchannel Condenser Coil

Condensate Overflow Switch

Crankcase Heaters

Dedicated Airflow

Standard

Features

X

X

X

X

X

X

X

X

X

X

Factory

Installed

X

X

X

X

Options (a)

Factory or

Field

Installed

Field

Installed

X

X

X

RT-PRC028AC-EN

Features and Benefits

Table 2.

Voyager™ Light Commercial features - standard and optional

Dehumidification (Hot Gas Reheat)

Digital Display Zone Sensor

Discharge Air Temperature Sensing Kit

Easy Access Low Voltage Terminal Board (LTB)

Economizer - Standard, Downflow

Economizer - Standard, Horizontal

Electric Heaters

Fault Detection & Diagnostics (FDD)

Foil-Faced and Edge Captured Insulation

Frostat™

High and Low Static Drive Kits

High Efficiency Drum and Tube Heat Exchanger

High Efficiency Gas Heat with Hot Surface Ignition

High Efficiency Motors

High Pressure Cutout

High Short Circuit Current Rated (SCCR) Electrical Subsystem

Hinged Access Doors

Human Interface - 5 inch Color Touchscreen

IAQ Sloped Condensate Drain Pan

Indoor Fan Motor Shaft Grounding Ring

Liquid Line Refrigerant Drier

Low Ambient Cooling to 0°F

Low Leak Economizer - Downflow

Low Leak Economizer - Downflow and Horizontal

LP Conversion Kit

Manual Outside Air Dampers

Microchannel Type Condenser Coils

Microchannel Type Evaporator Coils (Standard Efficiency Only)

Modulating Gas Heat Furnace with a 2.5:1 Turndown Ratio

Motorized Outside Air Dampers

Multi-Speed Indoor Fans

Multiple Zone Variable Air Volume (MZVAV)

Operating Charge of R-410A

Oversized Motors

Phase Monitor

Powered Exhaust

Powered or Unpowered Convenience Outlet

Provisions for Through-the-Base Gas Connections

Quick Access Panels

Quick Adjust Idler Arm Pulley

Reference or Comparative Enthalpy

Remote Potentiometer

Roof Curb (Downflow Only)

RT-PRC028AC-EN

Standard

Features

Factory

Installed

X

X

Options (a)

Factory or

Field

Installed

Field

Installed

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

5

Features and Benefits

6

Table 2.

Voyager™ Light Commercial features - standard and optional

Single Point Power

Single Side Service

Single Zone Variable Air Volume (SZ VAV)

Stainless Steel Drain Pan

Stainless Steel Heat Exchanger with 10 Year Warranty

Standardized Components

Supply and/or Return Air Smoke Detector

Thermal Expansion Valve

Through the Base Electrical Access

Through the Base Electrical with Circuit Breaker

Through the Base Electrical with Disconnect Switch

Through the Base Gas Piping

Tool-less Hail Guards

U-shaped Airflow Pattern

Variable Frequency Drive (Multispeed Indoor Fan, VAV, and Single Zone VAV)

Ventilation Override Accessory

(a)Refer to model number description for option availability.

Standard

Features

X

X

X

X

X

X

Factory

Installed

X

X

X

X

X

X

X

X

Options (a)

Factory or

Field

Installed

Field

Installed

X

X

Note: Most Factory Installed Options (FIOPS) available for Downflow Air Discharge units only.

Please verify with ordering system for availability.

Standard Features

Anti-Short Cycle Timer

Provides a 3 minute minimum “ON” time and 3 minute “OFF” time for compressors to enhance compressor reliability by assuring proper oil return.

Colored and Numbered Wiring

Save time and money tracing wires and diagnosing the unit.

Compressors

Voyager contains the best compressor technology available to achieve the highest possible performance. Dual compressors are outstanding for humidity control, light load cooling conditions and system back-up applications. Dual compressors are available on all models and allow for efficient cooling utilizing three stages of compressor operation (high efficiency 12½–20 Tons models only). 25 tons high efficiency units have 4 stages of cooling with a single compressor and tandem set (similar to variable speed).

Controls—ReliaTel™

ReliaTel microprocessor controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure indoor and outdoor temperature and other zone sensors. ReliaTel

RT-PRC028AC-EN

Features and Benefits also provides outputs for building automation systems and expanded diagnostics. For a complete list of ReliaTel offerings, refer to

“Other Benefits,” p. 16

.

Conversionless Units

The dedicated design units (either downflow or horizontal) require no panel removal or alteration time to convert in the field — a major cost savings during installation. Horizontal units come complete with duct flanges so the contractor doesn’t have to field fabricate them. These duct flanges are a time and cost saver.

Crankcase Heaters

These band or insertion heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or low ambient conditions. These are standard on all Voyager models.

Discharge Line Thermostat

A bi-metal element discharge line thermostats installed as a standard feature on the discharge line of each system. This standard feature provides extra protection to the compressors against high discharge temperatures in case of loss of charge, extremely high ambient and other conditions which could drive the discharge temperature higher.

Efficiencies

Standard or High Efficiency Cooling available.

Easy Access Low Voltage Terminal Board

Foil Faced Insulation

RT-PRC028AC-EN

Voyager’s Low Voltage Terminal Board is external to the electrical control cabinet. It is extremely easy to locate and attach the thermostat wire and test operation of all unit functions. This is another cost and time saving installation feature.

All panels in the evaporator section of the unit have cleanable foil-faced insulation. All edges are either captured or sealed to ensure no insulation fibers get into the airstream.

Fork Pocket Access

Voyager™ has the ability to be forked from 3 sides.

Heat Exchanger—Drum and Tube

The cabinet features a drum and tube heat exchanger (pictured right) that is manufactured using aluminized steel with stainless steel components for maximum durability.

The requirement for cycle testing of heat exchangers is 10,000 cycles by ANSI Z21.47.

This is the standard required by both UL and

AGA for cycle test requirements.

For c ed Com b ust i on Blower

Ne ga t i ve Pressure Ga s V a lve

Hot Surf ac e I g n i tor

7

Features and Benefits

Trane requires the design to be tested to 2½ times this current standard. The drum and tube design has been tested and passed over 150,000 cycles, which is over 15 times the current ANSI cycling requirements. The negative pressure gas valve is used in the standard furnaces. This is one of our unique safety features. Modulating heaters use a pressure switch to ensure that the blower motor is operating before the gas valve is allowed to open.

The forced combustion blower supplies pre-mixed fuel through a single stainless steel burner screen into a sealed drum where ignition takes place. It is more reliable to operate and maintain than a multiple burner system. Modulating furnaces contain a metal fiber material to ensure proper flame distribution at low fire. The hot surface ignitor is a gas ignition device which doubles as a safety device utilizing a continuous test to prove the flame. The design is cycle tested at the factory for quality and reliability. Our gas/electric rooftops exceed all California seasonal efficiency requirements and perform even better than the California NO x

emission requirements.

Low Ambient Cooling

All Voyager microprocessor units have cooling capabilities down to 0°F as standard.

Low Voltage Connections

The wiring of the low voltage connections to the unit and the zone sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to wire.

8

Microchannel Coils

Air Inlet

Slit Fins and Braze Contact for Improved Heat Transfer and Strength

Microchannels for Refrigerant

Air Outlet

Microchannel coils are all-aluminum coils with fullybrazed construction. This design reduces risk of leaks and provides increased coil rigidity — making them more rugged on the jobsite. Their flat streamlined tubes with small ports and metallurgical tube-to-fin bond allow for exceptional heat transfer.

Microchannel all-aluminum construction provides several additional benefits:

• Light weight (simplifies coil handling)

• Easy to recycle

• Minimize galvanic corrosion

Motors

All indoor fan motors are belt drive as standard.

Pressure Cutouts

Low and high pressure cutouts are standard on all Voyager models.

Phase Monitor

Voyager features a three-phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating input voltage range of 190–600 Vac, and LED indicators for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition.

RT-PRC028AC-EN

Features and Benefits

Quick-Access Panels

Remove three or more screws for access to the standardized internal components and wiring.

Quick-Adjust Slider Plate

With the Quick-Adjust Slider Plate (pictured right), the belt and sheaves can be quickly adjusted without moving the mounted fan motor. The result is a major savings in time and money.

Single Point Power

A single electrical connection powers the unit.

Single Side Service

Single side service is standard on all units.

Sloped Drain Pans

Every Voyager unit has a non-corrosive, sloped drain pan made of pre-painted steel and standard on all units.

Standardized Components

Components are placed in the same location on all Voyager units. Familiarize yourself with one

Voyager and you are familiar with every Voyager. Due to standardized components throughout the

Voyager line, contractors/owners can stock fewer parts.

U-Shaped Airflow Pattern

The U-shaped airflow allows for improved static capabilities.

Variable Frequency Drives - VFD (Multispeed Indoor Fan, VAV, and SZ VAV

Only)

Variable Frequency Drives are factory installed and tested to provide supply fan motor speed modulation. VFDs on the supply fan, as compared to inlet guide vanes or discharge dampers, are quieter, more efficient, and are eligible for utility rebates. All VFDs are designed to allow bypass if required. Bypass control will simply provide full nominal airflow in the event of drive failure.

Bypass mode is indicated in the unit wiring manual. Modulating gas heat models with SZVAV allow tighter space temperature control with less temperature swing.

Variety of Options 1

Factory Installed Options

Trane® Air-Fi™ Wireless

Trane® Air-Fi™ wireless communication is a reliable, flexible solution that frees you from the hassles associated with wired components for your building controls system. With Air-Fi wireless, you get easy problem solving, efficient performance, and cost savings over the life of the equipment.

CO

2

Sensor Wiring

This is the unit wiring for field installed C0

2

sensors. Factory-installed C0

2

sensor wiring saves time and ensures proper unit connections for the field installed C0

2

sensor kits.

1 Refer to

“Model Number Description,” p. 23 for option availability.

RT-PRC028AC-EN 9

Features and Benefits

10

Complete Coat™ Condenser Coil

The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number of different types of heat exchangers. The coating is selected to provide excellent resistance and durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salt air, and corrosive environments. This coating is available for microchannel coils only.

Circuit Breaker (Required with Through-the-Base Electrical)

This option is a factory installed thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. Available on all models.

Condensate Overflow Switch

A condensate overflow switch is available to shut the unit down in the event that the condensate drain line becomes clogged. This option protects the unit from water overflowing from the drain pan and entering the base of the units.

Dehumidification (Hot Gas Reheat)

This option allows for increased outdoor air ventilation. It reduces humidity levels while increasing comfort level in the air space. Cooling can operate without a demand for dehumidification. The hot gas reheat coil is designed to deliver maximum reheat temperature.

Disconnect Switch (Required with Through-the-Base Electrical)

Factory installed 3-pole, molded case, disconnect switch with provisions for through the base electrical connections are available.

Available on all models.

Codes require a method of assured unit shutdown for servicing. Field-installed disconnects sometimes interfere with service access. Factory installation of unit disconnects reduces costs, assures proper mounting and provides the opportunity to upgrade to unit circuit breaker protection.

Fault Detection & Diagnostics (FDD)

This offering meets the mandatory requirement of CA Title 24 of fully configurable diagnostics allowing fault history and reading fault codes at the unit.This option provides detection of the following faults: Air temperature sensor failure/fault and notification of acceptable economizer mode.The FDD system shall be certified by the Energy Commission as meeting the requirements.

High Efficiency Filtration

Voyager units offer a variety of high efficiency filtration options. MERV 8 and MERV 13 filters provide additional filtration beyond the capabilities of typical 2” throwaway filters. Also, when

MERV 8 or MERV 13 filters are ordered, units come equipped with a filter removal tool.

High Efficiency Motors

High efficiency motors are available with efficiency ratings from 86.5 up to 91.0. It is not available for all models.

High Short Circuit Current Rating (SCCR)

Voyager rooftop units now have an optional high short circuit current rated electrical subsystem for units with an MOP above 60A. This option is a perfect fit for applications that need protection against high potential fault currents. This option also includes individual over current protection for each compressor and the indoor fan, as well as a dedicated over current protection to the

RT-PRC028AC-EN

Features and Benefits condenser fan motor(s). When the high SCCR is ordered, the control box will have components separated into two sections - high and low voltage components.

Hinged Access Doors

These doors permit easy access to the filter, fan/ heat, and compressor/control sections. They reduce the potential roof damage from screws or sharp access door corners.

RT-PRC028AC-EN

Human Interface

The 5 inch Color Touchscreen Human Interface provides an intuitive user interface to the rooftop unit that speeds up unit commissioning, shortens unit troubleshooting times, and enhances preventative maintenance measures. The human interface includes several features such as:

• Data trending capabilities by means of time series graphs

• Historical alarm messages

• Real-time sensor measurements

• On board system setpoints

• USB port that enables the downloading of component runtime information as well as trended historical sensor data

• Customizable reports

Modulating Gas Heat with a 2.5:1 Turndown Ratio

Upon receiving a call for heat, modulating gas heat units with a 2.5:1 turndown ratio light their burner at full fire (100%). After the burner is lit, the unit controls will monitor the discharge air temperature and modulate the input rate down to match the load.

Note: Modulating gas heat units are equipped with a stainless steel heat exchanger as standard.

Multi-Speed Indoor Fan System

Multi-speed indoor fan system is designed for use in applications for meeting the minimum requirement of CA Title 24. This system incorporates a multi-speed fan control to change the speed of the fan to 67% of full airflow based off compressor stages.

Multiple-Zone VAV Control

A multiple-zone VAV (MZVAV) system consists of a packaged rooftop unit that serves several individually controlled zones. Each zone is equipped with a VAV terminal unit that varies the quantity of air delivered to maintain the desired temperature in that zone. The rooftop unit controller varies the speed of the indoor fan to maintain the static pressure in the supply ductwork at a setpoint, ensuring that all zones receive the necessary quantity of air. In addition, cooling capacity is cycled to maintain the supply air temperature at the desired setpoint.

For decades, Trane has been an industry leader in rooftop VAV systems. Now, multiple-zone VAV control is available in Trane’s light commercial rooftop platform (3-25 tons).

11

Features and Benefits

Novar Unit Controls

Novar 3051 and 2024 are available for Voyager Cooling and Gas/Electric models.

Powered or Unpowered Convenience Outlet

This option is a GFCI, 120V/15amp, 2-plug, convenience outlet, either powered or unpowered. This option can only be ordered when Through the Base Electrical with either the Disconnect Switch or

Circuit Breaker option is ordered. This option is available on all models.

Single Zone VAV - One Zone Variable Air Volume Mode

Note: Single Zone VAV is designed to be used with a zone sensor. If a unit is configured for Single

Zone VAV operation but is connected to a thermostat, the control will revert to multi-speed

(2-Speed) indoor fan control. (See "Multi-Speed Indoor Fan System" above.)

Single zone VAV is designed for use in single zone applications like gymnasiums, auditoriums, manufacturing facilities, retail box stores, and any large open spaces, where there is a lot of diversity in the load profile. Single Zone VAV (SZ VAV) is an ideal replacement to "yesterday's" constant volume (CV) systems, by reducing operating costs while improving occupant comfort.

SZ VAV systems combine Trane application, control and system integration knowledge to exactly match fan speed with cooling and heating loads, regardless of the operating condition. Trane algorithms meet/exceed ASHRAE 90.1- 2010, SZ VAV energy-saving recommendations, and those of CA Title 24. The result is an optimized balance between zone temperature control and system energy savings. Depending on your specific application, energy savings can be as much as 20%.

Note: Building system modeling in energy simulation software like TRACE is recommended to evaluate performance improvements for your application.

SZ VAV is fully integrated into the ReliaTel Control system and is available today. It provides the simplest and fastest commissioning in the industry through proven factory-installed, wired, and tested system controllers. All control modules, logic and sensors are factory installed, and tested to assure the highest quality and most reliable system available. This means no special programming of algorithms, or hunting at the jobsite for sensors, boards, etc. that need to be installed in the field. Single zone VAV is a quick and simple solution for many applications and is available from your most trusted rooftop VAV system solution provider- Trane.

Stainless Steel Drain Pan

For excellent corrosion and oxidation resistance, the optional stainless steel drain pan provides a cleanable surface that complement other IAQ solutions such as high efficiency filtration (MERV 8 or 13), demand control ventilation (CO

2

), and hot gas reheat.

Stainless Steel Heat Exchanger

The optional stainless steel heat exchanger is constructed of 304 stainless steel. It is resistant to corrosion and oxidation and easy to clean. The high strength to weight ratio allows for high ventilation rates with gas units and comes standard with a modulating gas heat option. With this option, a 10-year stainless steel heat exchanger warranty is standard.

Supply, Return, and Plenum Air Smoke Detector

With this option (pictured right) installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models.

Supply and/or Return Smoke Detectors may not be used with the Plenum Smoke Detector.

12 RT-PRC028AC-EN

Features and Benefits

Through-the-Base Electrical Utility Access

An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of the unit. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch.

Factory provided through the base openings simplify wiring and piping. Because these utility openings frequently minimize the number of roof penetrations, the integrity of roofing materials is enhanced.

Through-the-Base Gas Piping (Gas/Electric Only)

This option (pictured right) shall have all piping necessary including, black steel, manual gas shut-off valve, elbows, and union. This assembly will require minor field labor to install.

Factory or Field Installed Options 1

BACnet™ Communications Interface

The BACnet communications interface allows the unit to communicate directly with a generic open protocol BACnet MS/TP Network Building Automation System Controls.

Barometric Relief

Designed to be used on downflow units, barometric relief is an unpowered means of relieving excess building pressure.

Clogged Filter/Fan Failure Switch

A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication. These sensors allow a zone sensor service light or Integrated Comfort

System to indicate a dirty filter or a fan that’s not working. The field installation charges for these valuable feedback devices often eliminate them from consideration. Factory installation can make such features a good investment.

Discharge Air Temperature Sensing Kit

Provides true discharge air temperature sensing in heating models. The kit is functional only with the ReliaTel Options Module.

Economizer - Standard, Downflow

Economizers are equipped with either dry bulb, reference, or comparative enthalpy sensing. These economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly installed, they offer a valuable energy savings. Factory-installed economizers save time and ensure proper installation.

Note: Factory-installed economizers require some field set-up.

Economizer - Low Leak, Downflow

This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3 cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air). This option allows 100% outdoor air supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired with powered exhaust for additional building pressure relief. This option can be paired with or without Fault Detection & Diagnostics (FDD) to meet current mandatory CA Title 24 requirements.

1 Refer to

“Model Number Description,” p. 23 for option availability.

RT-PRC028AC-EN 13

Features and Benefits

Available on downflow units only. The economizers come with three control options, dry bulb and reference or comparative enthalpy (optional).

Electric Heaters

Electric heat modules are available within the basic unit. If ordering the Through the Base Electrical option with an Electrical Heater, the heater must be factory installed.

Frostat™

A capillary bulb embedded in the face of the evaporator coil or a thermostat on the suction line monitors coil temperature to prevent evaporator icing and protect the compressor. Recommended for applications with low leaving air temperatures, low airflow and/or high latent load applications.

Note: Frostat is standard on all Single-Zone VAV, Multiple-Zone VAV, and high efficiency units.

Indoor Fan Motor Shaft Grounding Ring

Shaft grounding rings are used on all VFD driven motors to provide a conductive discharge path away from the motor bearings to ground. Bearing Protection Rings shall be maintenance free circumferential rings of conductive micro fibers that discharge voltages to ground.

LonTalk ® Communications Interface

The LonTalk communications interface allows the unit to communicate as a Tracer™LCI-V device or directly with generic LonTalk Network Building Automation System Controls.

Oversized Motors

Factory or field installed oversized motors are available for high static applications.

Reference or Comparative Enthalpy

Measures and communicates humidity while maximizing comfort control.

ReliaTel Options Module (RTOM)

The RTOM monitors the supply fan proving, clogged filter, supply air temperature, exhaust fan setpoint, dehumidification setpoint, supply air tempering, Frostat™ and smoke detector.

Note: The RTOM is standard on high efficiency units.

Tool-less Hail Guards

Tool-less, hail protection quality coil guards (pictured right) shall be either factory or field-installed for condenser coil protection. This option protects the condenser coil from vandalism and/or hail damage.

Trane Communication Interface (TCI)

Available factory or field installed. This module when applied with the

ReliaTel™ easily interfaces with Trane’s Integrated Comfort™ System.

Field Installed Options

1

CO

2

Sensor - Demand Control Ventilation (DCV)

Demand-controlled ventilation (DCV) is a control strategy that responds to the actual demand

(need) for ventilation by regulating the rate at which the HVAC system brings outdoor air into the building. A CO

2

sensor measures the concentration (parts per million, ppm) of CO

2

(Carbon

Dioxide) in the air. As the CO

2

concentration changes, the outside air damper modulates to meet the current ventilation needs of the zone. The CO

2

sensor kit is available as a field installed

1 Refer to

“Model Number Description,” p. 23 for option availability.

14 RT-PRC028AC-EN

Features and Benefits

RT-PRC028AC-EN accessory. Two field installed kits are offered; C0

2

sensor and wiring or C0

2

sensor only. The C0

2 sensor only kit should be ordered with factory installed C0

2

sensor wiring. Factory installed C0

2 sensor wiring saves set-up time and ensures proper unit connections for the C0

2

sensor.

Dampers

0–25 percent manual or 0–50 percent motorized outside air dampers are available.

Digital Display Zone Sensor

The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors.

Economizer - Standard, Horizontal

Economizers are equipped with either dry bulb or reference or comparative enthalpy sensing.

These economizers provide free cooling as the outdoor temperature and/or humidity decreases.

Correctly installed, they offer a valuable energy savings.

Economizer - Low Leak, Downflow & Horizontal

This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3 cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air). This option allows 100% outdoor air supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired with powered exhaust for additional building pressure relief.

Humidity Sensor/Humidistat

Used in conjunction with our Dehumidification (Hot Gas Reheat) units to provide outstanding humidity control and comfort. Humidity sensors can be wall or duct mounted and set for levels between 40% and 60%.

LP Conversion Kit

Provided for field conversion of gas/electric units from natural gas to propane.

Powered Exhaust

This option is available on downflow units and provides exhaust of the return air, when using a downflow economizer, to maintain proper building pressurization. Great for relieving most building overpressurization problems.

Remote Potentiometer

When properly installed in the economizer control circuitry, this accessory provides a remote variable resistance to enable the operator to adjust the minimum damper position.

Roof Curbs

Available for downflow units. Only two roof curbs for the entire Voyager line simplifies curb selection.

Static Drive Accessories

Available on many models, this high and low static drive accessories extend the capability of the standard motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory.

Ventilation Override Accessory

With the Ventilation Override Accessory installed, the unit can be set to transition to up to 3 different pre-programmed sequences for Smoke Purge, Pressurization and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector or fire control panel. The ventilation override kit is available as a field installed accessory.

15

Features and Benefits

Wireless Zone Sensor

LCD display that provides heat, cool, auto, or off. Includes two temperature setpoints and a lockable setting with °F or °C indicators.

Zone Sensors/Thermostats

Available in programmable, automatic and manual styles.

Note: Zone sensors required for units configured for Single Zone VAV indoor fan system control to enable Single Zone VAV functionality.

Other Benefits

Cabinet Integrity

For added water integrity, Voyager has a raised 1-1/8” lip around the supply and return of the downflow units to prevent water from blowing into the ductwork.

Easy to Install, Service and Maintain

Because today’s owners are very cost-conscious when it comes to service and maintenance,

Voyager was designed with direct input from service contractors. This valuable information helped to design a product that would get the serviceman off the job quicker and save the owner money.

Voyager does this by offering outstanding standard features enhanced by a variety of factory and field installed options, multiple control options, rigorously tested proven designs and superior product and technical support.

Outstanding Airflow Distribution

Airflow is outstanding. The Voyager can replace an older machine with old ductwork and, in many cases, improve the comfort through better air distribution.

ReliaTel™ Controls Benefits

ReliaTel controls provide unit control for heating, cooling and ventilating by utilizing input from sensors that measure outdoor and indoor temperature.

Quality and Reliability are enhanced through ReliaTel control and logic:

– Prevents the unit from short cycling, considerably improving compressor life.

– Ensures the compressor will run for a specific amount of time which allows oil to return for better lubrication, enhancing the reliability of the compressor.

Voyager with ReliaTel reduces the number of components required to operate the unit, thereby reducing possibilities for component failure.

ReliaTel Makes Installing and Servicing Easy

ReliaTel eliminates the need for field installed anti-shortcycle timer and time delay relays.

ReliaTel controls provide these functions as an integral part of the unit. The contractor no longer has to purchase these controls as options and pay to install them. The wiring of the low voltage connections to the unit and the zone sensors is as easy as 1-1, 2-2, and 3-3. This simplified system makes wiring easier for the installer.

16 RT-PRC028AC-EN

RT-PRC028AC-EN

Features and Benefits

ReliaTel Makes Testing Easy

ReliaTel requires no special tools to run Voyager unit through its paces. Simply place a jumper between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk through its operational steps automatically.

The unit automatically returns control to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit.

As long as the unit has power and the “system on” LED is lit, ReliaTel is operational. The light indicates that the controls are functioning properly.

ReliaTel features expanded diagnostic capabilities when utilized with Trane Integrated Comfort™

Systems.

Some zone sensor options have central control panel lights which indicate the mode the unit is in and possible diagnostic information (dirty filters for example).

Other ReliaTel Benefits

The ReliaTel built-in anti-shortcycle timer, time delay relay and minimum “on” time control functions are factory tested to assure proper operation. ReliaTel softens electrical “spikes” by staging on fans, compressors and heaters. Intelligent Fallback is a benefit to the building occupant.

If a component goes astray, the unit will continue to operate at predetermined temperature setpoint.

Intelligent Anticipation is a standard ReliaTel feature. It functions continuously as ReliaTel and zone sensor(s) work together in harmony to provide much tighter comfort control than conventional electro-mechanical thermostats.

The same ReliaTel Board fits all Packaged Gas/Electric, Cooling, and Heat Pump models. This provides standardization of parts for contractors. Less money is tied up in inventory with ReliaTel.

Rigorous Testing

All of Voyager’s designs were rigorously rain tested at the factory to ensure water integrity. Voyager units incorporate either a one piece top or the Trane-Tite-Top (T3). Each part of the top (either two or three pieces) overlaps in such a way that water cannot leak into the unit. These overlapped edges are gasketed and sealed to ensure superior water integrity.

Actual shipping tests were performed to determine packaging requirements. Units were test shipped around the country to determine the best packaging. Factory shake and drop tests were used as part of the package design process to help assure that the unit arrives at the job site in top condition.

Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress. For the microchannel coils, the supplier will perform the leak check at 450 psig. The completely assembled refrigerant system is leak tested at a minimum of

225 psig with a refrigerant and nitrogen mixture.

All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately. Every unit receives a 100% unit run test before leaving the production line to make sure it lives up to rigorous Trane requirements.

Unmatched Support

Trane Sales Representatives are a Support Group that can assist you with:

• Product

• Application

• Service

• Training

• Special Applications

• Specifications

• Computer Programs and much more

17

Features and Benefits

VariTrac® – Changeover-Bypass System

A changeover-bypass system consists of a packaged rooftop unit that serves several individually controlled zones. Each zone is equipped with a damper that varies the quantity of air delivered to maintain the desired temperature in that zone. However, unlike a conventional multiple-zone VAV system, the fan inside the rooftop unit operates at a constant speed. Any unneeded air is diverted to the return air stream through a bypass damper.

The term “changeover” refers to how this system handles the cooling and heating requirements of the building. The central rooftop unit can provide either cooled or heated air, and it makes this decision by periodically “polling” the zones.

Note: VariTrac is for Voyager units with constant-speed indoor fan control. It is not recommended for use with Multiple-Speed Indoor Fan Control, Single-Zone VAV Control, or Multiple-Zone

VAV Control.

18 RT-PRC028AC-EN

Application Considerations

Application of this product should be within the cataloged airflow and cooling considerations.

Air-Fi™ Wireless

Please refer to Air-Fi Network Design Installation, Operation, and Maintenance manual BAS-

SVX55*-EN for additional details on applications with factory installed wireless.

Barometric Relief

This product line offers an optional barometric relief damper for use in conjunction with economizer option. This accessory consists of gravity dampers which open with increased pressure. As the building air pressure increases, the pressure in the unit return air section also increases, opening the dampers and relieving the conditioned space.

Note: The effectiveness of barometric relief damper during economizing operation is limited, depending on the pressure drop of the return-air path. For some applications, powered exhaust may be better suited for preventing over-pressurization when economizing.

Clearance Requirements

The recommended clearances identified with unit dimensions should be maintained to ensure adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with local Trane sales personnel.

Complete Coat™ Microchannel Condenser Coil

The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number of different types of heat exchangers. The coating is selected to provide excellent resistance and durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salt air, and corrosive environments. This coating shall be available on microchannel condenser coils.

Condensate Trap

The evaporator is a draw-through configuration. A trap must be field provided prior to start-up on the cooling cycle.

Dual Compressors — 3 Stages of Cooling (12½–20 Tons)

Using the ReliaTel™ microprocessor controls, the Voyager™ high efficiency line can provide three stages of cooling, allowing for a more efficient and comfortable cooling operation.

Important: All high efficiency products will have intertwined evaporator coils as standard. No face split coils are allowed with 3 or 4 stages of cooling.

Note: Standard efficiency models do not have 3 stages of cooling operation.

4 Stages of Cooling (25 Tons)

25 tons high efficiency units have 4 stages of cooling with a single compressor and tandem set

(similar to variable speed).

Heating Operation

The heat exchanger is manufactured with aluminized steel. To prevent condensation within the heat exchanger, do not exceed 50 percent outside air or a minimum mixed air temperature of 40°F.

Optional Stainless Steel Heat Exchanger

The optional stainless steel heat exchanger is manufactured with 304 stainless steel. To prevent corrosion and prolong heat exchanger reliability, the minimum mixed air temperature allowed across the heat exchanger is 20°F. The stainless steel heat exchanger option is an excellent option that compliments the dehumidification package and is used in conjunction with the modulating heat option. Whenever high outside air or outside applications exist, these options should be utilized.

RT-PRC028AC-EN 19

Application Considerations

Low Ambient Cooling

The Voyager line features, with ReliaTel™ microprocessor controls, low ambient cooling down to

0°F. The following options need to be included/considered when low ambient applications are required: continuous fan operation, crankcase heaters (standard), thermal expansion valves, frostat. Contact your local Trane Representative for more assistance with low ambient cooling applications.

Unit Pitch

These units have sloped condensate drain pans. Units must be installed level. Any unit slope must be toward access side of the unit.

Low Airflow

Unit applications designed for airflow below 320 cfm/ton are available on cooling only units and gas heat units equipped with modulating gas heat. Units must be high efficiency units with dehumidification (hot gas reheat) or TXV with Frostat and Crankcase heaters. Electric heat is restricted below 320 cfm/ton. Standard efficiency units are restricted below 250 cfm/ton. Multispeed or single zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

VariTrac®

VariTrac is for Voyager units with constant-speed indoor fan control. It is not recommended for use with Multiple-Speed Indoor Fan Control, Single-Zone VAV Control, or Multiple-Zone VAV Control.

20 RT-PRC028AC-EN

Selection Procedure

Cooling Capacity

Note: Cooling Capacity Procedure is the same for cooling (T*) and gas/electric (Y*).

Step 1.

Calculate the building’s total and sensible cooling loads at design conditions. Use the following calculation methods or any other standard accepted method. Factors used in unit selection:

Total Cooling Load: 180 MBh

Sensible Cooling Load: 126 MBh

Airflow: 6000 cfm

Electrical Characteristics: 460/60/3

Summer Design Conditions: Entering Evaporator Coil: 80 DB, 67 WB Outdoor Ambient: 95 DB

External Static Pressure: 0.39 in. wg

Rooftop—downflow configuration

Accessories

• Roof curb

• Economizer

• Electric Heat

Step 2.

As a starting point, a rough determination must be made of the size of the unit. The final selection will be made after examining the performance at the given conditions. Divide the total cooling load by nominal Btu/h per ton (12 MBh per ton); then round up to the nearest unit size.

180 MBh / 12 MBh = 15.0 tons

Step 3.

Table 18, p. 42

shows that a TSD180F4 has a gross cooling capacity of 186.1 MBh and 139.1 MBh sensible capacity at 6000 cfm and 95 DB outdoor ambient with 80 DB, 67 WB air entering the evaporator.

To Find Capacity at Intermediate Conditions Not in the Table.

When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity.

Note: Extrapolation outside of the table conditions is not recommended.

Step 4.

In order to select the correct unit which meets the building’s requirements, the fan motor heat must be deducted from the gross cooling capacity. The amount of heat that the fan motor generates is dependent on the effort by the motor—cfm and static pressure. To determine the total unit static pressure you add the external static pressure to the additional static related by the added features:

External Static Duct System

Standard Filter 2 in. from

Table 89, p. 120

0.39 wg

0.06 wg

Economizer from

Table 89, p. 120

(100% Return Air)

Electric Heater Size 36 kW from

Table 89, p. 120

0.04 wg

0.07 wg

(Reference

“Heating Capacity,” p. 22

for determination of heater size.) No additional static add for gas/heat exchanger.

Total Static Pressure 0.56 wg

Note: The Evaporator Fan Performance

Table 49, p. 83

has already accounted for the pressure drop for standard filters and wet coils (see note below

Table 49

).

Therefore, the actual total static pressure is 0.56 - 0.06 (from

Table 89, p. 120

= 0.50 wg).

RT-PRC028AC-EN 21

Selection Procedure

With 6000 cfm and 0.50 wg.

Table 49, p. 83 shows 1.95 bhp for this unit. Note below the table gives a formula to calculate Fan

Motor Heat,

3.15 x bhp = MBh.

3.15 x 1.95 = 6.14 MBh.

Now subtract the fan motor heat from the gross cooling capacity of the unit:

Net Total Cooling Capacity = 186.1 MBh - 6.14 = 179.96 MBh.

Net Sensible Cooling Capacity = 139.1 MBh - 6.14 = 132.96 MBh.

Step 5.

If the performance will not meet the required load of the building—total or sensible cooling load, try a selection at the next higher size unit.

Heating Capacity

Note: Heating capacity procedures DIFFER for cooling (T*) and gas/electric (Y*) units.

Step 1.

Calculate the building heating load.

Step 2.

Size the system heating capacity to match the calculated building heating load. The following are building heating requirements:

T* cooling units:

460 volt/3 phase Power Supply

Total heating load of 115.0 MBh

6000 cfm

The electric heat accessory capacities are listed in Table 91, p. 122 . From the table, a 36 kW heater

will deliver 122.94 MBh at 480 volts. In order to determine capacity at 460 volts, the heater voltage

correction factor from Table 92, p. 123

must be used. Therefore, 122.94 MBh x .94 (voltage correction factor) = 115.6 MBh.

Y* gas/electric: Fuel natural gas total heating load of 195 MBh. Table Table 90, p. 122

shows

250 MBh and 350 MBh input models. The output capacities of these furnaces are 203 MBh and

284 MBh respectively. The low heat model with 203 MBh output best matches the building requirements.

Air Delivery Selection

Note: Air Delivery procedures is the same for cooling (T*) and gas/electric (Y*) units.

External static pressure drop through the air distribution system has been calculated to be

0.50 inches of water. From Table 89, p. 120

static pressure drop through the economizer is 0.04 and the 36 kW heater is 0.07 inches of water (0.39 + 0.04 + 0.07). Enter

Table 49, p. 83

for a TSD180F4 at 6000 cfm and 0.50 static pressure. The standard motor at 533 rpm will give the desired airflow at a rated bhp of 1.92.

22 RT-PRC028AC-EN

Y

1

S

2

D

3

1

4

5

5

Digit 1 — Unit Type

T = Packaged Cooling, Electric Heat

Y = Packaged Cooling, Gas Heat

Digit 2 — Efficiency

S = Standard Efficiency

H = High Efficiency

Digit 3 — Airflow Configuration

D = Downflow

H = Horizontal

Digit 4, 5, 6 — Nominal Gross

Cooling Capacity (MBh)

150 = 12½ Tons

180 = 15 Tons

210 = 17½ Tons, 60Hz DOE 2018

211 = 17½ Tons, 60Hz

240 = 20 Tons

300 = 25 Tons, 60Hz DOE 2018

301 = 25 Tons, 60Hz

Digit 7 — Major Design

Sequence

G = ASHRAE 90.1-2013 (Fan/

Compressor Staging)

13

or

Microchannel Type Evaporator &

Condenser Coils

Digit 8 — Voltage Selection

3 = 208-230/60/3

4 = 460/60/3

W = 575/60/3

K = 380/60/3

Digit 9 — Unit Controls

R = Reliatel

Digit 10 — Heating Capacity

Note: (Applicable to Digit 1 T models only)

0 = No Heat

G = 18 kW Electric Heat

K = 27 kW Electric Heat

N = 36 kW Electric Heat

P = 54 kW Electric Heat

R = 72 kW Electric Heat

Note: (Applicable to Digit 1 Y models only)

H = Gas Heat - High

L = Gas Heat - Low

V = Gas Heat - SS Ht Ex - Modulating

X = Gas Heat - SS Ht Ex - Low

Z = Gas Heat - SS Ht Ex - High

Digit 11 — Minor Design

Sequence

RT-PRC028AC-EN

0

6

G

7

3

8

R

9

Digit 12, 13 — Service Sequence

00 = None

01 = 18mm Microchannel Condenser

Coil

Note: ‘01’ only available on select models.

Digit 14 — Fresh Air Selection

0 = No Fresh Air

D = Econ Dry Bulb w/ Barometric

Relief

1

F = Econ Reference Enthaply w/

Barometric Relief

1

H = Econ Comparative Enthaply w/

Barometric Relief

1

K = Low Leak Econ w/ Barometric

Relief

1

M = Low Leak Econ Reference

Enthalpy w/ Barometric Relief

1

P = Low Leak Econ Comparative

Enthalpy w/ Barometric Relief

1

Digit 15 — Supply Fan/Drive

Type/Motor

0 = Standard Motor

1 =

Oversized Motor 6

3 =

High Efficiency Motor 6

6 = Single Zone Variable Air Volume

Standard Motor

7 = Multi-Speed Standard Motor

8 = Single Zone Variable Air Volume

Oversized Motor

9 = Multi-Speed Oversized Motor

A = Single Zone Variable Air Volume

Standard Motor w/ Shaft

Grounding Ring

B = Multi-Speed Standard Motor w/

Shaft Grounding Ring

C = Single Zone Variable Air Volume

Oversized Motor w/ Shaft

Grounding Ring

D = Multi-Speed Oversized Motor w/

Shaft Grounding Ring

E = VAV Supply Air Temperature

Control - Standard Motor

F = VAV Supply Air Temperature

Control - Oversized Motor

G = VAV Supply Air Temperature

Control - Standard Motor w/ Shaft

Grounding Ring

H = VAV Supply Air Temperature

Control - Oversized Motor w/

Shaft Grounding Ring

Digit 16 — Hinged Service

Access / Filters

0 = Standard Panels/Standard

Filters

22

A = Hinged Access/Standard Filters

22

B =

Standard Panels/MERV 8 Filters 6

C =

Hinged Access/MERV 8 Filters 6

D = Standard Panels/MERV 13 Filters

6

E = Hinged Access/MERV 13 Filters

6

Z B 0

10 11 12

Digit 17 — Condenser Coil

Protection

0

13

0 = Standard Coil

1 = Standard Coil With Hail Guard

4 = CompleteCoat™Condenser Coil

5 = CompleteCoat™Condenser Coil with Hail Guard

Digit 18 — Through The Base

Provisions

Note: Applicable to Digit 1, T or Y models.

0 = No Through The Base Provisions

A = Through The Base Electric

12

Note: Applicable to Digit1, Y models only.

B = Through The Base Gas

C = Through The Base Electric/Gas

12

D = Through The Base Access

Digit 19 — Disconnect Switch/

Circuit Breaker 11

0 = No Disconnect/circuit break

1 = Unit Mounted Non-Fused

Disconnect Switch

2 = Unit Mounted Circuit Breaker

Digit 20 — Convenience Outlet

Option

0 = Without Convenience Outlet

A = Unpowered Convenience Outlet

5

B =

Powered Convenience Outlet 5

Digit 21 — Communications

Options

0 = Without Communications Options

1 = Trane Communications Interface

6

,

15

2 = Lontalk Communications

Interface 6

6 = Building Automation Control

Network Communications

Interface

7 =

Air-Fi™ Wireless Communications 24

Digit 22 — Refrigeration System

Option

0 = Standard refrigeration system

B = Dehumidification (Hot Gas

Reheat) 4 , 13

Digit 23 — Refrigeration Controls

0 = Without Refrigeration Controls

1 =

Frostat 9

,

18

Digit 24 — Smoke Detector

2 , 10

0 = Without Smoke Detector

A = Return Air Smoke Detector

B = Supply Air Smoke Detector

C = Return/Supply Air Smoke

Detector

D = Plenum Smoke Detector

19

Digit 25 — System Monitoring

Controls

0 = No Monitoring Controls

23

Model Number Description

1 = Clogged Filter Switch

9

2 = Fan Failure Switch

9

3 =

Discharge Air Sensing 9

4 = Clogged Filter Switch and Fan

Failure switch 9

5 = Clogged Filter Switch and

Discharge Air Sensing 9

6 = Fan Failure Switch and Discharge

Air Sensing 9

7 = Clogged Filter Switch, Fan Failure

Switch and Discharge Air

Sensing 9

A = Condensate Drain Pan Overflow

Switch

B = Clogged Filter Switch and

Condensate Drain Pan Overflow

Switch 9

C = Fan Failure Switch and

Condensate Drain Pan Overflow

Switch 9

D = Discharge Air Sensing and

Condensate Drain Pan Overflow

Switch 9

E = Clogged Filter Switch, Fan Failure

Switch and Condensate Drain Pan

Overflow Switch

9

F = Clogged Filter Switch, Discharge

Air Sensing Tube and Condensate

Drain Pan Overflow Switch

9

G = Fan Failure Switch, Discharge Air

Sensing Tube and Condensate

Drain Pan Overflow Switch

9

H = Clogged Filter Switch, Fan Failure

Switch, Discharge Air Sensing and Condensate Drain Pan

Overflow Switch

9

Digit 26 - System Monitoring

Controls

0 = No Monitoring Controls

A = Demand Control Ventilation

(CO

2

)

17

B = FDD (Fault Detection and

Diagnostics)

C = FDD (Fault Detection Diagnostics)

& Demand Control Ventilation

(CO

2

)

17

Digit 27 - Unit Hardware

Enhancements

0 = No Enhancements

1 = Stainless Steel Drain Pan

Digit 28 - Short Circuit Current

Rating

0 = Standard SCCR

A = 65kA SCCR Option

20

,

21

Digit 31 - Advanced Unit

Controls

0 = Standard Unit Controls

1 =

Human Interface 23

Note: Most Factory Installed Options available for Downflow Air

Discharge units only. Please verify with ordering system for availability.

Model Number Notes

1.

Some field set up required.

2. Requires ReliaTel Options Module.

3. Requires Economizer.

4. All 22 nd digit model numbers for reheat coil (B) require additional factory installed options: Frostat, and 2” pleated filters.

5. Must be ordered with Throughthe-Base Electrical option or

Horizontal-Side Access and either

Unit Mounted Disconnect or

Circuit Breaker.

6. Available factory installed on downflow AND horizontal units.

Verify with ordering system.

7.

Cannot be fused.

8. Must be factory installed when using Through-the-Base Options.

9. ReliaTel Options Module is required when ordering the following accessories: 4 Stage

Cooling, Clogged Filter Switch,

Fan Fail Switch, Condensate

Overflow Switch, Discharge Air

Sensing Kit, Frostat, Ventilation

Override, Smoke Detector,

Dehumidification and Modulating

Gas Heat Furnace.

10. Option cannot be ordered in conjunction with field installed economizer on downflow units.

Must be factory installed. The return air smoke detector may not fit up or work properly on the

Voyager units when used in conjunction with 3 rd party accessories (such as bolt on heat wheels, economizers, and power exhaust). Do not order the return air smoke detectors when using this type of accessory.

11. Unit mounted disconnect and circuit breakers are mutually exclusive of each other.

12. Through-the-base electrical option or Horizontal-Side Access must be ordered with either unit mounted disconnect or circuit breaker. When adding heat, you must order Trane Electric Heat.

13. Available on high efficiency units only.

14. All Factory Installed Options are

Built-to-Order. Check order services for estimated production cycle.

15. TCI is for use with non-VariTrac systems and VariTrac systems.

16. For use with multi-speed and

SZVAV units only.

17. Demand Control Ventilation

Option includes wiring only. The

C0

2

sensor is a field-installed only option.

18. Frostat is standard on VAV and high efficiency units.

19. Supply and/or return smoke detector may not be used with the plenum smoke detector.

20. Only available where MOP is above 60A.

21. 575 VAC option is 25kA.

22. Standard filters are not available with Low Leak Economizers.

23. Human Interface is standard with

FDD (Fault Detection Diagnostics).

24. Must be used with BACnet™ open protocol.

24 RT-PRC028AC-EN

General Data

Table 3.

General data—cooling 12½–15 tons standard efficiency

Cooling Performance (a)

Gross Cooling Capacity

EER (Downflow/Horizontal) (b)

Nominal Airflow CFM / ARI Rated CFM

ARI Net Cooling Capacity

Integrated Energy Efficiency Ratio (IEER) (One

Speed Fan / Multi or Variable Speed Fan) (c)

Percent Capacity @ part load

(Stage 1/Stage 2)

System Power (kW)

Compressor

Number/Type

Sound

Outdoor Sound Rating (BELS) (d)

Outdoor Coil

Type

Coil Width (in.)

Face Area (sq. ft.)

Rows/FPI (DF/HZ)

Indoor Coil

Type

Coil Width (in.)

Face Area (sq. ft.)

Rows/FPI

Refrigerant Control

Drain Connection Number/Size (in.)

Outdoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds cfm

Number Motors/hp

12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units

TS*150G3,4,W,K YS*150G3,4,W,K TS*180G3,4,W,K YS*180G3,4,W,K

150,000

11

5,000 / 4,000

140,000

12.4/13.5

66/100

12.73

2 / Scrolls

9.2

Microchannel

0.71

25.9

1/23

Microchannel

1.00

17.30

2/16

TXV

1/1.00 NPT

150,000

11

5,000 / 4,000

140,000

12.2/13.5

66/100

12.73

2 / Scrolls

9.2

Microchannel

0.71

25.9

1/23

Microchannel

1.00

17.30

2/16

TXV

1/1.00 NPT

186,000

11

6,000 / 5,400

176,000

12.4/13.2

67/100

16.00

2 / Scrolls

9.2

Microchannel

0.71

35.2

1/23

Microchannel

0.81

23.00

2/16

TXV

1/1.00 NPT

186,000

11

6,000 / 5,400

176,000

12.2/13.2

67/100

16.00

2 / Scrolls

9.2

Microchannel

0.71

35.2

1/23

Microchannel

0.81

23.00

2/16

TXV

1/1.00 NPT

Propeller

2 / 26

Propeller

2 / 26

Propeller

2 / 26

Propeller

2 / 26

Direct / 1 Direct / 1 Direct / 1 Direct / 1

11,000 11,000 11,000 11,000

2 / 0.50

2 / 0.50

2 / 0.50

2 / 0.50

1,100 1,100 1,100 1,100

Indoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds

Number Motors

Motor hp (Standard/Oversized) (e)

Motor rpm (Standard/Oversized)

Motor Frame Size (Standard/Oversized)

FC Centrifugal

1 / 15x15

Belt / 1

1

3.0 / 5.0

1,740 / 3,450

56HZ / 56HZ

FC Centrifugal

1 / 15x15

Belt / 1

1

3.0 / 5.0

1,740 / 3,450

56HZ / 56HZ

FC Centrifugal

1 / 18x18

Belt / 1

1

3.0 / 5.0 or 7.5

(f)

1,740 / 3,450

FC Centrifugal

1 / 18x18

Belt / 1

1

3.0 / 5.0 or 7.5

1,740 / 3,450

(f)

184TZ / 56HZ/184TZ 56HZ / 56HZ/184TZ

RT-PRC028AC-EN 25

General Data

Table 3.

General data—cooling 12½–15 tons standard efficiency

12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units

TS*150G3,4,W,K YS*150G3,4,W,K TS*180G3,4,W,K YS*180G3,4,W,K

Filters

Type Furnished (g)

Number Size Recommended

Throwaway Throwaway Throwaway Throwaway

Downflow

Horizontal

(2)20x20x2

(4)20x25x2

(2)20x20x2

(4)20x25x2

(2)20x20x2

(4)20x25x2

(2)20x20x2

(4)20x25x2

(4)20x20x2

(4)20x25x2

(8)20x25x2

(4)20x20x2

(4)20x25x2

(8)20x25x2

Refrigerant Charge

(Pounds of R-410A) (h)

Cir#1 / Cir#2 (DF)

Cir#1 / Cir#2 (HZ)

8.1/5.1

8.1/5.2

8.1/5.1

8.1/5.2

9.0/5.0

9.2/5.1

9.0/5.0

9.2/5.1

(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360.

(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.

(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.

(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.

(e)For 380V/60Hz units, the oversized motor (Indoor Fan) is used as the standard motor. Refer to oversized motor data.

(f) Offered only as a field installed accessory.

(g)An optional 2-inch pleated filter is also available.

(h)Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

* Indicates both downflow and horizontal units.

Table 4.

General data—heating—12½–15 tons standard efficiency

Heating Models

Heating Input (Btu/h)

1st Stage (Btu)

Heating Output (Btu/h)

1st Stage (Btu)

Steady State Efficiency%

No. Burners

No. Stages

Gas Supply Line Pressure (in. wc)

Natural or LP (minimum/maximum)

Gas Connection Pipe Size (in.)

12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units

Heating Performance (a) (Gas/Electric Only)

Low High

Modulating

Turn Down

= 2.5:1 Low High

Modulating

Turn Down

= 2.5:1

150,000

100,000

120,000

80,000

80

1

250,000

175,000

200,000

140,000

80

1

2

2.5/14.0

2

2.5/14.0

Natural or LP Natural or LP

1/2 1/2

350,000

140,000

280,000

112,000

80

1

N/A

2.5/14.0

Natural Only

3/4

250,000

175,000

200,000

140,000

80

1

350,000

250,000

280,000

200,000

80

1

2

2.5/14.0

2

2.5/14.0

Natural or LP Natural or LP

1/2 3/4

350,000

140,000

280,000

112,000

80

1

N/A

2.5/14.0

Natural Only

3/4

(a) Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards

Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.

26 RT-PRC028AC-EN

General Data

Table 5.

General data—17½–20 tons standard efficiency

Cooling Performance (a)

Gross Cooling Capacity

EER (Downflow/Horizontal) (b)

Nominal Airflow CFM / ARI Rated CFM

ARI Net Cooling Capacity

Integrated Energy Efficiency Ratio (IEER) (One

Speed Fan / Multi or Variable Speed Fan) (c)

Percent Capacity @ part load

(Stage 1/Stage 2)

System Power (kW)

Compressor

Number/Type

Sound

Outdoor Sound Rating (BELS) (d)

Outdoor Coil

Type

Coil Width (in.)

Face Area (sq. ft.)

Rows/FPI (DF/HZ)

Indoor Coil

Type

Tube Size (in.) ID

Face Area (sq. ft.)

Rows/FPI

Refrigerant Control

Drain Connection Number/Size (in.)

Outdoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds cfm

Number Motors/hp

Motor rpm

Indoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds

Number Motors

Motor hp (Standard/Oversized) (e)

Motor rpm (Standard/Oversized)

Motor Frame Size (Standard/Oversized)

17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units

TS*210G3,4,W,K YS*210G3,4,W,K TS*240G3,4,W,K YS*240G3,4,W,K

210,000

11

7,000 / 6,125

196,000

12.4/13.2

67/100

17.82

2 / Scrolls

9.4

Microchannel

1.00

35.2

1/20

Microchannel

1.00

23.00

2 / 16

TXV

1/1.00 NPT

Propeller

2 / 26

Direct / 1

14,500

2 / 1.0

1125

FC Centrifugal

1 / 18x18

Belt / 1

1

5.0 / 7.5

3,450 / 3,470

56HZ / 184T

210,000

11

7,000 / 6,125

196,000

12.2/13.2

67/100

17.82

2 / Scrolls

9.4

Microchannel

1.00

35.2

1/20

Microchannel

1.00

23.00

2 / 16

TXV

1/1.00 NPT

Propeller

2 / 26

Direct / 1

14,500

2 / 1.0

1125

FC Centrifugal

1 / 18x18

Belt / 1

1

5.0 / 7.5

3,450 / 3,470

56HZ / 184T

259,000

10

8,000 / 6,400

240,000

11.6/12.4

67/100

24.00

2 / Scrolls

9.4

Microchannel

1.0

35.2

1/23 / 1/20

Microchannel

1.00

23.00

2 / 16

TXV

1/1.00 NPT

Propeller

2 / 26

Direct / 1

15,500

2 / 1.0

1125

FC Centrifugal

1 / 18x18

Belt / 1

1

5.0 / 7.5

3,450 / 3,470

56HZ / 184T

259,000

10

8,000 / 6,400

240,000

11.4/12.4

67/100

24.00

2 / Scrolls

9.4

Microchannel

1.0

35.2

1/23 / 1/20

Microchannel

1.00

23.00

2 / 16

TXV

1/1.00 NPT

Propeller

2 / 26

Direct / 1

15,500

2 / 1.0

1125

FC Centrifugal

1 / 18x18

Belt / 1

1

5.0 / 7.5

3,450 / 3,470

56HZ / 184T

RT-PRC028AC-EN 27

General Data

Table 5.

General data—17½–20 tons standard efficiency

17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units

TS*210G3,4,W,K YS*210G3,4,W,K TS*240G3,4,W,K YS*240G3,4,W,K

Filters

Type Furnished (f)

Number Size Recommended

Throwaway Throwaway Throwaway Throwaway

Downflow

Horizontal

Refrigerant Charge

(Pounds of R-410A)

Cir#1/Cir#2 (DF)

Cir#1/Cir#2 (HZ)

(4)20x20x2

(4)20x25x2

(8)20x25x2

12.6/6.8

12.0/6.8

(4)20x20x2

(4)20x25x2

(8)20x25x2

12.6/6.8

12.0/6.8

(4)20x20x2

(4)20x25x2

(8)20x25x2

12.4/7.2

11.7/6.8

(4)20x20x2

(4)20x25x2

(8)20x25x2

12.4/7.2

11.7/6.8

(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360.

(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.

(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.

(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.

(e)For 380V/60Hz units, the oversized motor (Indoor Fan) is used as the standard motor. Refer to oversized motor data.

(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

* Indicates both downflow and horizontal units.

Table 6.

General data—17½ standard efficiency

Cooling Performance (a)

Gross Cooling Capacity

EER (Downflow/Horizontal) (b)

Nominal Airflow CFM / ARI Rated CFM

ARI Net Cooling Capacity

Integrated Energy Efficiency Ratio (IEER) (One

Speed Fan / Multi or Variable Speed Fan) (c)

Percent Capacity @ part load

(Stage 1/Stage 2)

System Power (kW)

Compressor

Number/Type

Sound

Outdoor Sound Rating (BELS) (d)

Outdoor Coil

17½ Tons Downflow & Horizontal Units

TS*211G3,4,W YS*211G3,4,W

210,000

11

7,000 / 6,125

196,000

11.8/12.9

73/100

17.82

2 / Scrolls

9.4

210,000

11

7,000 / 6,125

196,000

11.8/12.9

73/100

17.82

2 / Scrolls

9.4

Type

Coil Width (in.)

Face Area (sq. ft.)

Rows/FPI (DF/HZ)

Indoor Coil

Type

Tube Size (in.) ID

Face Area (sq. ft.)

Rows/FPI

Refrigerant Control

Drain Connection Number/Size (in.)

Microchannel

1.00

35.2

1/20

Microchannel

1.00

23.00

2 / 16

TXV

1/1.00 NPT

Microchannel

1.00

35.2

1/20

Microchannel

1.00

23.00

2 / 16

TXV

1/1.00 NPT

28 RT-PRC028AC-EN

RT-PRC028AC-EN

Table 6.

General data—17½ standard efficiency

17½ Tons Downflow & Horizontal Units

TS*211G3,4,W YS*211G3,4,W

Outdoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds cfm

Number Motors/hp

Motor rpm

Indoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds

Number Motors

Motor hp (Standard/Oversized) (e)

Motor rpm (Standard/Oversized)

Motor Frame Size (Standard/Oversized)

Filters

Type Furnished (f)

Number Size Recommended

Propeller

2 / 26

Direct / 1

14,500

2 / 1.0

1125

FC Centrifugal

1 / 18x18

Belt / 1

1

5.0 / 7.5

3,450 / 3,470

145T / 184T

Throwaway

Propeller

2 / 26

Direct / 1

14,500

2 / 1.0

1125

FC Centrifugal

1 / 18x18

Belt / 1

1

5.0 / 7.5

3,450 / 3,470

145T / 184T

Throwaway

Downflow

Horizontal

Refrigerant Charge

(Pounds of R-410A)

Cir#1/Cir#2 (DF)

Cir#1/Cir#2 (HZ)

(4)20x20x2

(4)20x25x2

(8)20x25x2

14.4/7.4

14.4/7.4

(4)20x20x2

(4)20x25x2

(8)20x25x2

14.4/7.4

14.4/7.4

(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb.

Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard

340/360.

(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.

(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or

340/360.

(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.

(e)For 380V/60Hz units, the oversized motor (Indoor Fan) is used as the standard motor. Refer to oversized motor data.

(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

* Indicates both downflow and horizontal units.

General Data

29

General Data

Table 7.

General data—heating—17½–20 tons standard efficiency

17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units

Heating Performance (a) (Gas/Electric Only)

Low High

Modulating

Turn

Down = 2.5:1 Low High

Modulating

Turn

Down =

2.5:1 Heating Models

Heating Input (Btu/h)

1st Stage (Btu)

Heating Output (Btu/h)

1st Stage (Btu)

Steady State Efficiency%

No. Burners

250,000

175,000

200,000

140,000

80

1

2

350,000

250,000

280,000

200,000

80

1

2

350,000

140,000

280,000

112,000

80

1

N/A

250,000

175,000

200,000

140,000

80

1

2

400,000

300,000

320,000

240,000

80

1

2

350,000

140,000

280,000

112,000

80

1

N/A No. Stages

Gas Supply Line Pressure (in. wc)

Natural or LP (minimum/maximum)

2.5/14.0

Natural or LP

1/2

2.5/14.0

Natural or LP

3/4

2.5/14.0

Natural Only

3/4

2.5/14.0

2.5/14.0

2.5/14.0

Natural or LP Natural or LP Natural Only

1/2 3/4 3/4 Gas Connection Pipe Size (in.)

(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards

Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.

30 RT-PRC028AC-EN

RT-PRC028AC-EN

General Data

Table 8.

General data—25 ton standard efficiency

25 Tons Downflow & Horizontal Units

TS*300G3,4,W,K YS*300G3,4,W,K

Cooling Performance (a)

Gross Cooling Capacity

EER (Downflow/Horizontal) (b)

Nominal Airflow CFM / ARI Rated CFM

ARI Net Cooling Capacity

Integrated Energy Efficiency Ratio (IEER) (One

Speed Fan / Multi or Variable Speed Fan) (c)

Percent Capacity @ part load

(Stage 1/Stage 2)

System Power (kW)

Compressor

Number/Type

Sound

Outdoor Sound Rating (BELS) (d)

Outdoor Coil

Type

Coil Width (in.)

Face Area (sq. ft.)

Rows/FPI (DF/HZ)

Indoor Coil

Type

Tube Size (in.) ID

Face Area (sq. ft.)

Rows/FPI

Refrigerant Control

Drain Connection Number/Size (in.)

Outdoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds cfm

Number Motors/hp

Motor rpm

Indoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds

Number Motors

Motor hp (Standard/Oversized)

Motor rpm (Standard/Oversized)

Motor Frame Size (Standard/Oversized)

296,400

10

10,000 / 7,750

270,000

11.6/12.4

66/100

27

2 / Scrolls

9.4

Microchannel

1.0

35.2

1/23 / 1/20

Microchannel

1.00

23.00

2 / 16

TXV

1/1.00 NPT

Propeller

2 / 28

Direct / 1

16,100

2 / 1.0

1125

FC Centrifugal

1 / 18x18

Belt / 1

1

7.5 / N/A

3,470 / N/A

184T / N/A

296,400

10

10,000 / 7,750

270,000

11.4/12.4

66/100

27

2 / Scrolls

9.4

Microchannel

1.0

35.2

1/23 / 1/20

Microchannel

1.00

23.00

2 / 16

TXV

1/1.00 NPT

Propeller

2 / 28

Direct / 1

16,100

2 / 1.0

1125

FC Centrifugal

1 / 18x18

Belt / 1

1

7.5 / N/A

3,470 / N/A

184T / N/A

31

General Data

Table 8.

General data—25 ton standard efficiency

25 Tons Downflow & Horizontal Units

TS*300G3,4,W,K YS*300G3,4,W,K

Filters

Type Furnished (e)

Number Size Recommended

Downflow

Horizontal

Refrigerant Charge

(Pounds of R-410A) (f)

Cir#1/Cir#2 (DF)

Cir#1/Cir#2 (HZ)

Throwaway

(4)20x20x2 (4)20x25x2

(8)20x25x2

Throwaway

(4)20x20x2 (4)20x25x2

(8)20x25x2

12.5/6.7

11.7/6.7

12.5/6.7

11.7/6.7

(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment

Certification Program, which is based on ARI Standard 340/360.

(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.

(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.

(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.

(e)An optional 2-inch pleated filter is also available.

(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

* Indicates both downflow and horizontal units.

Table 9.

General data—25 tons standard efficiency

25 Tons Downflow & Horizontal Units

TS*301G3,4,W YS*301G3,4,W

Cooling Performance (a)

Gross Cooling Capacity

EER (Downflow/Horizontal) (b)

Nominal Airflow CFM / ARI Rated CFM

ARI Net Cooling Capacity

Integrated Energy Efficiency Ratio (IEER) (One

Speed Fan / Multi or Variable Speed Fan) (c)

Percent Capacity @ part load

(Stage 1/Stage 2)

System Power (kW)

Compressor

Number/Type

Sound

Outdoor Sound Rating (BELS) (d)

Outdoor Coil

Type

Coil Width (in.)

Face Area (sq. ft.)

Rows/FPI (DF/HZ)

Indoor Coil

Type

Tube Size (in.) ID

Face Area (sq. ft.)

Rows/FPI

Refrigerant Control

Drain Connection Number/Size (in.)

296,400

10

10,000 / 8,000

272,000

10.4/12.0

50/100

27.20

2 / Scrolls

9.4

Microchannel

1.0

35.2

1/23 / 1/20

Microchannel

1.00

23.00

2 / 16

TXV

1/1.00 NPT

296,400

10

10,000 / 8,000

272,000

10.4/12.0

50/100

27.20

2 / Scrolls

9.4

Microchannel

1.0

35.2

1/23 / 1/20

Microchannel

1.00

23.00

2 / 16

TXV

1/1.00 NPT

32 RT-PRC028AC-EN

RT-PRC028AC-EN

General Data

Table 9.

General data—25 tons standard efficiency

25 Tons Downflow & Horizontal Units

TS*301G3,4,W YS*301G3,4,W

Outdoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds cfm

Number Motors/hp

Motor rpm

Indoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds

Number Motors

Motor hp (Standard/Oversized)

Motor rpm (Standard/Oversized)

Motor Frame Size (Standard/Oversized)

Filters

Type Furnished (e)

Number Size Recommended

Downflow

Horizontal

Refrigerant Charge

(Pounds of R-410A) (f)

Cir#1/Cir#2 (DF)

Cir#1/Cir#2 (HZ)

Propeller

2 / 28

Direct / 1

16,100

2 / 1.0

1125

FC Centrifugal

1 / 18x18

Belt / 1

1

7.5 / N/A

3,470 / N/A

184T / N/A

Throwaway

(4)20x20x2 (4)20x25x2

(8)20x25x2

Propeller

2 / 28

Direct / 1

16,100

2 / 1.0

1125

FC Centrifugal

1 / 18x18

Belt / 1

1

7.5 / N/A

3,470 / N/A

184T / N/A

Throwaway

(4)20x20x2 (4)20x25x2

(8)20x25x2

10.5

10.5

10.5

10.5

(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment

Certification Program, which is based on ARI Standard 340/360.

(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.

(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.

(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.

(e)An optional 2-inch pleated filter is also available.

(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

* Indicates both downflow and horizontal units.

33

General Data

Table 10. General data—heating—25 tons

25 Tons Downflow & Horizontal Units

Heating Performance (a) (Gas/Electric Only)

Low High

Modulating Turn

Down = 2.5:1 Heating Models

Heating Input (Btu/h)

1st Stage (Btu)

Heating Output (Btu/h)

250,000

175,000

200,000

400,000

300,000

320,000

350,000

140,000

280,000

1st Stage (Btu)

Steady State Efficiency%

No. Burners

No. Stages

Gas Supply Line Pressure (in. wc)

Natural or LP (minimum/maximum)

Gas Connection Pipe Size (in.)

140,000

80

1

2

2.5 / 14.0

Natural or LP

½

240,000

80

1

2

2.5 / 14.0

Natural or LP

¾

112,000

80

1

N/A

2.5 / 14.0

Natural Only

¾

(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.

34 RT-PRC028AC-EN

General Data

Table 11. General data—12½–15 ton high efficiency

Cooling Performance (a)

Gross Cooling Capacity

EER (b)

Nominal CFM / ARI Rated CFM

ARI Net Cooling Capacity

Integrated Energy Efficiency Ratio (IEER) (One

Speed Fan / Multi or Variable Speed Fan) (c)

Percent Capacity @ part load

(Stage 1/Stage 2/Stage 3) (d)

System Power (kW)

Compressor

Number/Type

Sound

Outdoor Sound Rating (BELS) (e)

Outdoor Coil

Type

Coil Width (in.)

Face Area (sq. ft.)

Rows/FPI

Indoor Coil

Type

Tube Size (in.) ID

Face Area (sq. ft.)

Rows/FPI

Refrigerant Control

Drain Connection Number/Size (in.)

Outdoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds cfm

Number Motors/hp

Motor rpm

Indoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds

Number Motors

Motor hp (Standard/Oversized)

Motor rpm (Standard/Oversized)

Motor Frame Size (Standard/Oversized)

12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units

TH*150G3,4,W YH*150G3,4,W TH*180G3,4,W YH*180G3,4,W

152,400

12.1

5,000 / 4,000

144,000

13.5/15.0

30/70/100

11.90

2 / Scrolls

9.2

Microchannel

1.0

35.2

1 / 20

Hi-Performance

0.3125

26.00

4 / 15

TXV

1/1.00 NPT

Propeller

2 / 26

Direct / 1

2 / 0.50

1,100

FC Centrifugal

1 / 18x18

Belt / 1

1

3.0 / 5.0

1,740 / 3,450

145T / 145T

152,400

12.1

5,000 / 4,000

144,000

13.5/15.0

30/70/100

11.90

2 / Scrolls

9.2

Microchannel

1.0

35.2

1 / 20

Hi-Performance

0.3125

26.00

4 / 15

TXV

1/1.00 NPT

Propeller

2 / 26

Direct / 1

2 / 0.50

1,100

FC Centrifugal

1 / 18x18

Belt / 1

1

3.0 / 5.0

1,740 / 3,450

145T / 145T

180,500

12.1

6,000 / 5,250

174,000

14.0/15.0

32/68/100

14.38

2 / Scrolls

9.2

Microchannel

1.0

42.6

1 / 20

Hi-Performance

0.3125

31.42

4 / 15

TXV

1/1.00 NPT

Propeller

2 / 26

Direct / 1

2 / 0.50

1,100

FC Centrifugal

1 / 18x18

Belt / 1

1

3.0 / 5.0

1,740 / 3,450

145T / 145T

180,500

12.1

6,000 / 5,250

174,000

14.0/15.0

32/68/100

14.38

2 / Scrolls

9.2

Microchannel

1.0

42.6

1 / 20

Hi-Performance

0.3125

31.42

4 / 15

TXV

1/1.00 NPT

Propeller

2 / 26

Direct / 1

2 / 0.50

1,100

FC Centrifugal

1 / 18x18

Belt / 1

1

3.0 / 5.0

1,740 / 3,450

145T / 145T

RT-PRC028AC-EN 35

General Data

Table 11. General data—12½–15 ton high efficiency

12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units

TH*150G3,4,W YH*150G3,4,W TH*180G3,4,W YH*180G3,4,W

Filters

Type Furnished (f)

Number Size Recommended

Throwaway Throwaway Throwaway Throwaway

Downflow

Horizontal

Refrigerant Charge (Pounds of

R-410A) (g)

Downflow & Horizontal (Cir#1/Cir#2)

Optional Hot Gas Reheat Coil (Cir#1/Cir#2)

(4)20x20x2 (4)20x25x2 (4)20x20x2 (4)20x25x2

(8)20x25x2

12.5/7.1

9.2 / 6.9

(8)20x25x2

12.5/7.1

9.2 / 6.9

(8)20x20x2

(4)20x16x2

(12)20x20x2

13.0/8.5

10.9 / 8.9

(8)20x20x2

(4)20x16x2

(12)20x20x2

13.0/8.5

10.9 / 8.9

(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360.

(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.

(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.

(d)3 stages not available with Reheat models.

(e)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.

(f) An optional 2 inch pleated filter is also available.

(g)Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

* Indicates both downflow and horizontal units.

Table 12. General data—heating—12½-15 ton high efficiency

12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units

Heating Performance (a) (Gas/Electric Only)

Low High

Modulating

Turn Down

= 2.5:1 Low High

Modulating

Turn Down

= 2.5:1 Heating Models

Heating Input (Btu/h)

1st Stage (Btu)

Heating Output (Btu/h)

1st Stage (Btu)

Steady State Efficiency%

No. Burners

No. Stages

150,000 250,000 350,000

100,000 175,000 140,000

120,000 200,000 280,000

80,000 140,000 112,000

80 80 80

1 1 1

Gas Supply Line Pressure (in. wc) 2.5 / 14.0

Natural or LP (minimum/maximum)

Gas Connection Pipe Size (in.) ½

2.5 / 14.0

½

2.5 / 14.0

Natural Only

¾

250,000 350,000 350,000

175,000 250,000 140,000

200,000 280,000 280,000

140,000 200,000 112,000

80 80 80

1 1 1

2 2 N/A

2.5 / 14.0

2.5 / 14.0

2.5 / 14.0

½ ¾

Natural Only

¾

(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards

Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.

36 RT-PRC028AC-EN

General Data

Table 13. General data—17½–20 ton high efficiency

17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units

TH*210G3,4,W YH*210G3,4,W TH*240G3,4,W YH*240G3,4,W

Cooling Performance (a)

Gross Cooling Capacity

EER (b)

Nominal CFM / ARI Rated CFM

ARI Net Cooling Capacity

Integrated Energy Efficiency Ratio (IEER) (One

Speed Fan / Multi or Variable Speed Fan) (c)

Percent Capacity @ part load

(Stage 1/Stage 2/Stage 3) (d)

System Power (kW)

Compressor

Number/Type

Sound

Outdoor Sound Rating (BELS) (e)

Outdoor Coil

Type

Coil Width (in.)

Face Area (sq. ft.)

Rows/FPI

Indoor Coil

Type

Tube Size (in.) ID

Face Area (sq. ft.)

Rows/FPI

Refrigerant Control

Drain Connection Number/Size (in.)

Outdoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds cfm

Number Motors/hp

Motor rpm

Indoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds

Number Motors

Motor hp (Standard/Oversized)

Motor rpm (Standard/Oversized)

Motor Frame Size (Standard/Oversized)

214,800

11.8

7,000 / 5,600

204,000

13.0/14.0

31/69/100

17.29

2 / Scrolls

9.2

Microchannel

1.0

42.6

1 / 20

Hi-Performance

0.3125

31.42

4 / 15

TXV

1/1.00 NPT

214,800

11.8

7,000 / 5,600

204,000

13.0/14.0

31/69/100

17.29

248,500

11.0

8,000 / 6,400

234,000

12.4/14.0

30/70/100

21.27

248,500

11.0

8,000 / 6,400

234,000

12.4/14.0

30/70/100

21.27

Propeller

2 / 26

Direct / 1

Propeller

2 / 26

Direct / 1

Propeller

2 / 28

Direct / 1

Propeller

2 / 28

Direct / 1

15,800 15,800 16,500 16,500

2 / 1.0

1,125

2 / 1.0

1,125

2 / 1.0

1,125

2 / 1.0

1,125

FC Centrifugal

1 / 18x18

Belt / 1

1

5.0 / 7.5

3,450 / 3,470

145T / 184T

2 / Scrolls

9.2

Microchannel

1.0

42.6

1 / 20

Hi-Performance

0.3125

31.42

4 / 15

TXV

1/1.00 NPT

FC Centrifugal

1 / 18x18

Belt / 1

1

5.0 / 7.5

3,450 / 3,470

145T / 184T

2 / Scrolls

9.4

Microchannel

1.0

42.6

1 / 20

Hi-Performance

0.3125

31.42

4 / 15

TXV

1/1.00 NPT

FC Centrifugal

1 / 18x18

Belt / 1

1

5.0 / 7.5

3,450 / 3,470

145T / 184T

2 / Scrolls

9.4

Microchannel

1.0

42.6

1 / 20

Hi-Performance

0.3125

31.42

4 / 15

TXV

1/1.00 NPT

FC Centrifugal

1 / 18x18

Belt / 1

1

5.0 / 7.5

3,450 / 3,470

145T / 184T

RT-PRC028AC-EN 37

General Data

Table 13. General data—17½–20 ton high efficiency

17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units

TH*210G3,4,W YH*210G3,4,W TH*240G3,4,W YH*240G3,4,W

Filters

Type Furnished (f)

Number Size Recommended

Throwaway Throwaway Throwaway Throwaway

Downflow

Horizontal

Refrigerant Charge

(Pounds of R-410A) (g)

Downflow & Horizontal (Cir#1/Cir#2)

Optional Hot Gas Reheat Coil (Cir#1/Cir#2)

(8)20x20x2

(4)20x16x2

(12)20x20x2

14.0 / 7.3

12.2/8.9

(8)20x20x2

(4)20x16x2

(12)20x20x2

14.0 / 7.3

12.2/8.9

(8)20x20x2

(4)20x16x2

(12)20x20x2

15.5 / 7.5

11.9 / 9.6

(8)20x20x2

(4)20x16x2

(12)20x20x2

15.5 / 7.5

11.9 / 9.6

(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360.

(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.

(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.

(d)3 stages not available with Reheat models.

(e)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.

(f) An optional 2 inch pleated filter is also available.

(g)Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

* Indicates both downflow and horizontal units.

Table 14. General data—heating—17½–20 ton high efficiency

Heating Models

Heating Input (Btu/h)

17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units

Heating Performance (a) (Gas/Electric Only)

Low High

Modulating

Turn

Down = 2.5:1

250,000 350,000 350,000

175,000 250,000 140,000

Heating Output (Btu/h) 200,000 280,000 280,000

140,000 200,000 112,000

Steady State Efficiency%

No. Burners

No. Stages

80 80 80

1 1 1

Gas Supply Line Pressure (in. wc)

Natural or LP (minimum/maximum)

Gas Connection Pipe Size (in.)

2 2 N/A

2.5 / 14.0

½

2.5 / 14.0

¾

2.5/14.0

Natural Only

¾

Low High

Modulating

Turn

Down = 2.5:1

250,000 400,000 350,000

175,000 300,000 140,000

200,000 320,000 280,000

140,000 240,000 112,000

80 80 80

1 1 1

2 2 N/A

2.5 / 14.0

2.5 / 14.0

2.5/14.0

½ ¾

Natural Only

¾

(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards

Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.

38 RT-PRC028AC-EN

RT-PRC028AC-EN

General Data

Table 15. General data—25 ton high efficiency

25 Tons Downflow & Horizontal Units

TH*300G3,4,W YH*300G3,4,W

Cooling Performance (a)

Gross Cooling Capacity

EER (b)

Nominal CFM / ARI Rated CFM

ARI Net Cooling Capacity

Integrated Energy Efficiency Ratio (IEER) (One

Speed Fan / Multi or Variable Speed Fan) (c)

Percent Capacity @ part load

(Stage 1/Stage 2/Stage 3/Stage 4) (d)

System Power (kW)

Compressor

Number/Type

Sound

Outdoor Sound Rating (BELS) (e)

Outdoor Coil

Type

Coil Width (in.)

Face Area (sq. ft.)

Rows/FPI

Indoor Coil

Type

Tube Size (in.) ID

Face Area (sq. ft.)

Rows/FPI

Refrigerant Control

Drain Connection Number/Size (in.)

Outdoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds cfm

Number Motors/hp

Motor rpm

Indoor Fan

Type

Number Used/Diameter (in.)

Drive Type/No. Speeds

Number Motors

Motor hp (Standard)

Motor rpm (Standard)

Motor Frame Size (Standard)

292,300

10.6

10,000 / 8,000

274,000

12.4/15.0

25/50/75/100

25.85

3 / Scrolls

9.4

Microchannel

1.0

42.58

1 / 20

Hi-Performance

0.3125

31.42

4 / 15

TXV

1/1.00 NPT

292,300

10.6

10,000 / 8,000

274,000

12.4/15.0

25/50/75/100

25.85

Propeller

2 / 28

Direct / 1

Propeller

2 / 28

Direct / 1

16,500 16,500

2 / 1.0

1,125

2 / 1.0

1,125

FC Centrifugal

1 / 18x18

Belt / 1

1

7.5

3,470

184T

3 / Scrolls

9.4

Microchannel

1.0

42.58

1 / 20

Hi-Performance

0.3125

31.42

4 / 15

TXV

1/1.00 NPT

FC Centrifugal

1 / 18x18

Belt / 1

1

7.5

3,470

184T

39

General Data

Table 15. General data—25 ton high efficiency

25 Tons Downflow & Horizontal Units

TH*300G3,4,W YH*300G3,4,W

Filters

Type Furnished (f)

Number Size Recommended

Downflow

Horizontal

Refrigerant Charge

(Pounds of R-410A) (g)

Downflow & Horizontal (Cir#1/Cir#2)

Optional Hot Gas Reheat Coil (Cir#1/Cir#2)

Throwaway

(8)20x20x2 (4)20x16x2

(12)20x20x2

Throwaway

(8)20x20x2 (4)20x16x2

(12)20x20x2

11.8 / 10.6

13.2 / 11.4

11.8 / 10.6

13.2 / 11.4

(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360.

(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.

(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.

(d)3 and 4 stages not available with Reheat models.

(e)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.

(f) An optional 2-inch pleated filter is also available.

(g)Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

* Indicates both downflow and horizontal units.

Table 16. General data—heating—25 ton high efficiency

Heating Models

Heating Input (Btu/h)

1st Stage (Btu)

Heating Output (Btu/h)

1st Stage (Btu)

Steady State Efficiency%

No. Burners

No. Stages

Gas Supply Line Pressure (in. wc)

Natural or LP (minimum/maximum)

Gas Connection Pipe Size (in.)

25 Tons Downflow & Horizontal Units

Heating Performance (a) (Gas/Electric Only)

Low High

Modulating Turn

Down = 2.5:1

250,000 400,000 350,000

175,000 300,000 140,000

200,000 320,000 280,000

140,000 240,000 112,000

80 80 80

1 1 1

2.5 / 14.0

2.5 / 14.0

2.5/14.0

Natural Only

¾ ½ ¾

(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.

40 RT-PRC028AC-EN

Performance Data

Table 17. Gross cooling capacities 12½ tons three phase standard efficiency T/YS*150G3,4,W,K

Air

Flow cfm

4000

4500

5000

5500

6000

Air

Flow cfm

4000

Ent

DB

(°F)

75

80

85

90

75

75

80

85

90

85

90

75

80

85

80

85

90

75

80

90

Ent

DB

(°F)

61

153

161

142

147

156

164

157

161

159

159

158

164

85

67

157

161

105

138

158

164

173

172

173

174

174

173

73

124

154

63

97

130

163

61

Ambient Temperature

95

Entering Wet Bulb

67 73 61

105

67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

135

135

140

148

137

138

145

153

139

141

149

157

141

144

153

161

142

147

156

164

113

134

140

148

121

137

145

153

129

141

149

157

137

144

152

152

151

151

154

154

154

154

156

156

156

157

158

158

115

87

109

131

151

92

117

141

154

96

124

151

157

101

131

166

166

166

166

168

169

169

169

170

171

171

171

172

172

59

81

104

126

60

85

110

135

61

89

117

144

62

93

128

128

134

142

131

131

139

147

132

135

143

151

133

138

110

128

134

142

118

131

139

147

126

144

144

144

144

146

146

146

147

148

135 148

143 148

151 151

133 150

138 149

84

106

128

144

89

113

138

147

93

121

147

151

97

128

157

158

158

158

160

160

160

160

161

162

162

162

162

163

56

78

101 128.7 128.7 136.1 124.8 148.9 97.4

123 136.0 136.0 136.2 136.1 148.8 119.4

57

82

58

121.3 107.0 136.2 81.0 148.3 52.7

121.5 121.4 136.2 103.0 148.6 75.1

123.3 114.8 138.2 85.4 150.0 53.7

125.1 125.1 138.1 110.2 150.4 78.9

107 133.0 133.0 137.8 134.5 150.7 104.0

132 140.3 140.3 140.5 140.5 150.5 128.7

124.7 122.3 139.7 89.7 151.4 54.7

86 128.6 128.6 139.6 117.2 151.9 82.7

114 136.5 136.5 139.2 138.9 152.1 110.5

141 143.7 143.7 143.9 143.9 151.9 137.9

59 125.8 125.6 140.9 94.1 152.4 55.7

90 131.5 131.5 140.8 124.2 153.1 86.5

146

154

135

141

149

146 149

154 154

134 151

141 150

149 150

149

154

102

135

150

163

163

163

164

164

121 139.4 139.4 140.3 140.1 153.6 117.0

151 146.4 146.4 146.5 146.5 152.8 147.1

60 126.8 126.5 141.9 98.4 153.3 56.6

94 134.0 134.0 141.6 131.2 154.2 90.3

127 141.9 141.9 142.0 142.0 153.9 123.8

157

61

157 157 157 164

Ambient Temperature

120

Entering Wet Bulb

67 73

160 148.9 148.9 149.0 149.0 153.3 152.9

61

125

67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 114.1 103.8 127.9 77.7 138.5 49.3 110.4 102.1 123.6 76.0 133.4 47.5 106.5 100.4 119.0 74.1 127.9 45.6

80 115.3 115.3 127.9 99.7 138.9 71.7 112.3 112.3 123.6 98.0 133.7 69.9 109.1 109.1 119.1 96.2 128.3 68.1

85 122.6 122.6 127.8 121.5 139.2 94.0 119.3 119.3 123.3 119.7 134.1 92.3 115.7 115.7 118.7 117.8 128.8 90.4

90 129.4 129.4 129.5 129.5 139.2 116.0 125.8 125.8 125.9 125.9 134.1 114.3 121.9 121.9 122.0 122.0 128.7 112.4

4500

5000

75 115.8 111.5 129.6 82.0 140.0 50.3 111.8 109.7 125.1 80.3 134.6 48.4 107.8 107.6 120.4 78.5 128.9 46.5

80 119.0 119.0 129.5 106.8 140.4 75.5 115.8 115.8 125.0 105.0 135.1 73.7 112.3 112.3 120.3 103.2 129.5 71.8

85 126.4 126.4 129.2 129.0 140.7 100.6 122.8 122.8 124.7 124.5 135.3 98.7 119.0 119.0 120.0 119.8 129.7 96.8

90 133.1 133.1 133.2 133.2 140.5 125.2 129.1 129.1 129.3 129.3 135.2 123.4 124.9 124.9 125.0 125.0 129.5 121.5

75 116.9 116.7 130.9 86.4 141.0 51.2 113.0 112.8 126.3 84.6 135.5 49.4 108.9 108.7 121.4 82.8 129.7 47.5

80 122.1 122.1 130.8 113.8 141.7 79.3 118.7 118.7 126.1 112.0 136.3 77.5 114.9 114.9 121.3 110.2 130.6 75.6

85 129.5 129.5 130.4 130.2 141.8 107.0 125.7 125.7 125.9 125.8 136.3 105.2 121.6 121.6 121.7 121.7 130.5 103.3

90 135.9 135.9 136.0 136.0 141.5 134.4 131.6 131.6 131.7 131.7 135.9 132.4 127.0 127.0 127.1 127.1 130.0 129.5

75 118.0 117.8 131.9 90.7 141.8 52.1 114.0 113.8 127.2 88.9 136.2 50.3 109.9 109.8 122.2 87.1 130.3 48.4

80 124.7 124.7 131.7 120.8 142.7 83.0 121.0 121.0 127.0 119.0 137.3 81.2 117.1 117.1 121.9 117.1 131.5 79.4

5500

6000

85 132.0 132.0 132.1 132.1 142.6 113.5 127.9 127.9 128.0 128.0 137.0 111.6 123.6 123.6 123.7 123.7 131.1 109.7

90 138.2 138.2 138.3 138.3 142.0 141.6 133.7 133.7 133.8 133.8 136.3 135.9 128.8 128.8 128.9 128.9 130.3 130.0

75 118.9 118.8 132.7 94.9 142.5 53.1 115.3 115.3 127.8 93.1 136.8 51.2 111.6 111.6 122.8 91.3 130.8 49.3

80 126.8 126.8 132.4 127.7 143.7 86.9 123.0 123.0 127.4 125.8 138.0 85.1 118.9 118.9 122.2 121.9 132.0 83.1

85 134.0 134.0 134.1 134.1 143.2 119.9 129.7 129.7 129.8 129.8 137.5 118.1 125.2 125.2 125.3 125.3 131.5 116.2

90 140.3 140.3 140.3 140.3 142.4 142.0 135.5 135.5 135.6 135.6 136.7 136.4 130.4 130.4 130.4 130.4 130.8 130.5

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

* Stands for both downflow and horizontal unit.

RT-PRC028AC-EN 41

Performance Data

Table 18. Gross cooling capacities 15 tons three phase standard efficiency T/YS*180G3,4,W,K

Air

Flow cfm

4800

5400

6000

Ambient Temperature

Ent

DB

(°F)

85 95

Entering Wet Bulb

105

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 163.2 138.4 185.0 107.5 206.8 74.7 155.6 134.9 176.1 103.9 195.7

70.7

147.4 131.1 166.3

99.8

183.0

66.1

80 162.9 162.6 185.1 134.2 206.9 101.8 155.4 155.2 176.2 130.5 195.8

97.7

147.3 147.0 166.3 126.5 183.1

93.1

85 164.5 164.4 185.0 160.7 206.9 128.7 157.8 157.7 176.0 157.1 195.9 124.6 151.2 151.2 166.2 152.9 183.2 120.0

90 173.3 173.3 184.6 184.2 207.0 155.3 167.1 167.1 175.7 175.4 195.9 151.3 160.1 160.1 166.1 165.8 183.2 146.7

75 167.9 148.7 190.1 113.9 211.1 76.6 159.8 145.1 180.5 110.0 198.9

72.2

150.9 141.1 170.0 105.8 185.0

67.4

80 167.5 167.2 190.1 143.8 211.2 107.0 159.6 159.3 180.5 140.0 199.0 102.7 151.0 150.7 170.0 135.8 185.2

97.8

85 170.5 170.5 189.9 173.5 211.3 137.2 164.2 164.2 180.3 169.6 199.1 132.9 157.1 157.1 169.8 165.4 185.3 128.0

90 180.7 180.7 189.4 189.1 211.3 167.2 174.0 174.0 180.0 179.7 199.2 162.9 166.3 166.3 169.8 169.5 185.4 158.0

75 171.7 158.9 194.2 120.0 214.3 78.2 163.1 155.1 184.1 115.9 201.1

73.6

153.9 151.0 173.0 111.6 186.5

68.6

80 171.3 171.0 194.2 153.2 214.4 112.0 162.8 162.6 184.1 149.2 201.3 107.4 154.0 153.9 173.0 144.9 186.6 102.3

85 176.6 176.6 193.8 186.2 214.4 145.5 169.8 169.8 183.6 181.7 201.4 141.0 162.2 162.2 172.5 172.1 186.7 135.9

6600

7200

Air

Flow cfm

4800

90 187.2 187.2 193.3 192.9 214.5 178.8 179.9 179.9 183.4 183.2 201.4 174.3 171.6 171.6 172.9 172.8 186.6 169.2

75 174.9 168.9 197.5 125.9 216.5 79.6 165.9 164.6 187.0 121.7 202.5

74.8

156.2 155.8 175.3 117.2 188.2

70.0

80 174.4 174.2 197.5 162.5 216.7 116.8 165.8 165.7 186.9 158.3 202.6 112.0 156.7 156.6 175.2 153.8 188.3 107.1

85 181.9 181.9 196.9 196.4 216.8 153.7 174.7 174.7 186.3 185.8 202.7 148.9 166.5 166.5 174.7 174.3 188.4 144.0

90 192.8 192.8 196.4 196.1 216.8 190.3 184.9 184.9 186.5 186.3 202.9 185.5 176.0 176.0 176.1 176.1 188.3 180.6

75 177.6 177.1 200.3 131.7 218.1 80.9 168.3 167.8 189.3 127.4 204.3

76.2

158.2 157.8 177.1 122.8 189.5

71.3

80 177.2 177.0 200.3 171.5 218.3 121.4 168.5 168.3 189.2 167.3 204.4 116.8 160.2 160.2 177.0 162.6 189.7 111.8

85 186.6 186.6 199.4 198.9 218.4 161.7 178.9 178.9 188.4 187.9 204.5 157.0 170.3 170.3 176.4 175.9 189.8 152.1

90 197.7 197.7 199.4 199.2 218.4 201.7 189.3 189.3 189.4 189.2 204.2 196.9 179.6 179.6 179.6 179.6 189.5 188.8

Ambient Temperature

Ent

DB

(°F)

115 120

Entering Wet Bulb

125

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 138.6 127.2 155.7 95.6 168.4 61.0 134.2 125.2 150.1 93.3 160.9

58.4

144.2

91.0

153.4

55.8

80 138.8 138.5 155.7 122.2 168.6 88.0 134.5 134.3 150.1 120.0 161.0

85.4

144.3 117.7 153.5

82.8

85 144.0 144.0 155.6 148.6 168.7 114.9 140.2 140.2 150.0 146.4 161.1 112.3 136.3 136.3 144.2 143.7 153.6 109.7

90 152.4 152.4 155.7 155.5 168.8 141.6 148.2 148.2 150.3 150.0 161.1 138.9 143.8 143.8 144.8 144.7 153.7 136.4

75 141.6 137.0 158.7 101.3 170.1 62.3 136.9 134.9 152.6 99.0 162.5

59.7

132.1 131.8 146.3

96.6

154.4

57.0

80 142.0 141.9 158.7 131.3 170.2 92.7 137.6 137.4 152.7 128.9 162.6

90.1

133.1 132.9 146.4 126.5 154.6

87.4

5400

6000

6600

85 149.3 149.3 158.4 158.0 170.3 122.8 145.2 145.2 152.5 152.1 162.7 120.3 140.8 140.8 146.3 145.9 154.7 117.6

90 157.8 157.8 159.0 158.8 170.4 152.8 153.1 153.1 153.3 153.1 162.8 150.3 147.9 147.9 148.0 148.0 154.8 147.6

75 144.0 143.6 160.9 106.9 171.6 63.5 139.0 138.6 154.5 104.5 163.5

60.9

134.0 133.6 147.8 102.0 155.0

58.1

80 144.8 144.8 160.9 140.2 171.7 97.3 140.7 140.7 154.5 137.7 163.7

94.6

136.5 136.5 147.8 135.2 155.2

91.8

85 153.8 153.8 160.6 160.3 171.8 130.9 149.2 149.2 154.4 154.0 163.8 128.2 144.4 144.4 147.9 147.5 155.4 125.4

90 162.2 162.2 162.3 162.3 171.8 164.2 156.8 156.8 156.9 156.9 163.8 161.5 150.8 150.8 150.8 150.8 155.6 154.8

75 146.0 145.6 162.6 112.4 172.5 64.8 140.8 140.4 155.9 109.9 164.1

62.0

135.4 135.1 148.9 107.3 155.2

59.1

80 148.4 148.4 162.6 149.0 172.7 101.9 144.1 144.1 155.9 146.5 164.3

99.2

139.6 139.6 148.9 143.9 155.5

96.3

85 157.5 157.5 162.3 161.9 172.9 138.8 152.6 152.6 155.6 155.2 164.5 136.1 147.2 147.2 148.8 148.5 155.8 133.2

90 165.5 165.5 165.6 165.6 172.9 172.2 159.3 159.3 159.4 159.4 164.7 164.0 152.2 152.2 152.2 152.2 156.1 155.5

7200

75 147.6 147.2 163.9 117.8 173.2 66.0 142.2 141.8 156.9 115.2 164.5

63.2

136.6 136.2 149.6 112.5 155.3

60.2

80 151.6 151.6 163.8 157.7 173.4 106.5 147.0 147.0 156.9 155.1 164.7 103.6 142.1 142.1 149.6 149.0 155.5 100.7

85 160.6 160.6 163.3 163.0 173.6 146.7 155.2 155.2 156.6 156.4 165.0 143.9 149.4 149.4 149.7 149.4 156.0 141.1

90 167.9 167.9 167.9 167.9 173.7 173.0 160.7 160.7 160.8 160.8 165.2 164.6 153.9 153.9 154.0 154.0 156.4 155.7

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Stands for both downflow and horizontal unit.

42 RT-PRC028AC-EN

Performance Data

Table 19. Gross cooling capacities 17½ tons three phase standard efficiency T/YS*210G3,4,W,K

Air

Flow cfm

5600

6300

7000

Ambient Temperature

Ent

DB

(°F)

85 95

Entering Wet Bulb

105

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 186.0 161.1 210.2 124.5 233.8 85.5 176.4 156.7 199.5 120.1 221.1 80.9 166.4 152.2 188.0 115.4 207.2 76.0

80 185.1 184.9 209.9 155.7 233.8 117.2 175.8 175.6 199.3 151.4 221.1 112.6 166.2 166.1 187.8 146.7 207.3 107.7

85 191.8 191.8 209.4 186.6 233.7 148.7 184.3 184.3 198.6 182.2 221.0 144.1 176.1 176.1 187.1 177.5 207.2 139.2

90 203.1 203.1 208.5 208.2 233.5 180.1 195.2 195.2 198.0 197.7 220.9 175.5 186.5 186.5 187.0 186.9 207.0 170.5

75 189.9 172.8 214.5 131.5 237.5 87.3 179.9 168.3 203.2 126.9 224.3 82.7 169.5 163.7 191.1 122.1 209.7 77.6

80 189.1 188.9 214.2 166.6 237.5 123.0 179.8 179.7 203.0 162.1 224.3 118.4 171.3 171.3 190.9 157.3 209.8 113.3

85 199.0 199.0 213.3 201.1 237.4 158.5 191.0 191.0 202.1 196.4 224.2 153.8 182.3 182.3 190.0 189.1 209.8 148.9

90 210.7 210.7 212.4 212.2 237.1 193.7 202.2 202.2 202.4 202.4 223.9 189.0 192.8 192.8 193.0 193.0 209.5 183.9

75 193.1 184.2 218.0 138.3 240.3 89.1 182.8 179.0 206.3 133.6 226.6 84.4 171.9 171.4 193.7 128.7 211.5 79.2

80 193.0 193.0 217.6 177.2 240.4 128.8 185.0 185.0 205.9 172.6 226.7 124.0 176.3 176.3 193.3 167.7 211.7 118.9

85 205.2 205.2 216.5 213.8 240.3 168.2 196.7 196.7 204.5 204.1 226.7 163.5 187.4 187.4 191.9 191.6 211.8 158.4

7700

8400

Air

Flow cfm

5600

90 217.3 217.3 217.5 217.5 239.8 207.1 208.2 208.2 208.4 208.4 226.2 202.4 198.2 198.2 198.3 198.3 211.4 197.3

75 195.7 193.8 220.8 144.9 242.6 90.8 184.9 184.5 208.7 140.2 228.4 86.0 173.6 173.2 195.7 135.3 212.8 80.7

80 198.1 198.1 220.4 187.8 242.7 134.4 189.7 189.7 208.3 183.1 228.6 129.6 180.5 180.5 195.3 178.1 213.2 124.4

85 210.5 210.5 218.6 218.1 242.7 177.8 201.6 201.6 206.5 206.2 228.6 173.0 191.7 191.7 193.7 193.4 213.2 167.8

90 222.9 222.9 223.1 223.1 242.0 220.6 213.4 213.4 213.5 213.5 228.1 215.8 202.6 202.6 202.7 202.7 212.8 208.8

75 197.6 197.1 223.2 151.5 244.3 92.4 186.5 186.0 210.7 146.8 229.8 87.6 175.1 174.8 197.6 141.9 213.8 82.3

80 202.5 202.5 222.6 198.2 244.5 140.0 193.8 193.8 210.2 193.5 230.1 135.2 184.2 184.2 196.9 188.5 214.3 129.9

85 215.2 215.2 220.4 220.0 244.5 187.3 205.9 205.9 208.2 207.8 230.1 182.5 195.6 195.6 195.7 195.7 214.3 177.2

90 227.8 227.8 228.0 228.0 243.9 234.0 217.7 217.7 217.8 217.8 229.5 226.5 206.2 206.2 206.3 206.3 213.4 212.7

Ambient Temperature

Ent

DB

(°F)

115 120

Entering Wet Bulb

125

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 156.8 147.9 176.0 110.7 192.2 70.7 152.4 145.9 170.0 108.3 184.3 68.0

164.1 106.0 176.1 65.2

80 157.8 157.8 175.8 141.9 192.3 102.5 154.1 154.1 169.9 139.6 184.5 99.8

164.0 137.3 176.5 97.0

85 167.6 167.6 175.3 171.8 192.4 134.1 163.4 163.4 169.2 167.8 184.7 131.4 159.1 159.1 163.2 162.9 176.8 128.7

90 177.1 177.1 177.2 177.2 192.2 165.3 172.1 172.1 172.2 172.2 184.5 162.6 166.9 166.9 167.0 167.0 176.5 159.9

75 159.4 157.6 178.6 117.2 193.9 72.2 154.5 154.1 172.3 114.8 185.6 69.4 150.2 149.9 166.1 112.5 177.1 66.6

80 163.0 163.0 178.4 152.4 194.2 108.0 158.9 158.9 172.1 149.9 186.0 105.2 154.9 154.9 165.9 147.6 177.7 102.4

6300

7000

7700

85 173.0 173.0 177.3 177.0 194.3 143.5 168.3 168.3 171.1 170.8 186.2 140.8 163.4 163.4 164.9 164.6 177.9 138.0

90 182.5 182.5 182.7 182.7 194.1 178.6 177.0 177.0 177.2 177.2 186.0 175.9 171.1 171.1 171.2 171.2 177.7 172.5

75 161.1 160.8 180.6 123.7 195.1 73.7 156.2 155.9 174.2 121.3 186.5 70.8 151.7 151.4 167.8 118.9 177.7 67.9

80 167.4 167.4 180.3 162.7 195.6 113.5 162.9 162.9 173.8 160.2 187.2 110.7 158.5 158.5 167.3 157.8 178.6 107.8

85 177.4 177.4 179.1 178.7 195.7 152.9 172.2 172.2 172.7 172.5 187.3 150.1 166.8 166.8 166.9 166.9 178.6 147.2

90 187.0 187.0 187.1 187.1 195.4 190.8 180.9 180.9 181.0 181.0 187.0 185.9 174.4 174.4 174.5 174.5 178.1 177.5

75 162.7 162.4 182.3 130.3 195.9 75.2 157.6 157.3 175.7 127.8 187.1 72.3 153.1 152.9 169.2 125.3 178.1 69.3

80 171.1 171.1 181.8 173.0 196.6 118.9 166.3 166.3 175.1 170.3 188.1 116.1 161.5 161.5 168.5 166.3 179.4 113.3

85 181.2 181.2 181.3 181.3 196.6 162.3 175.6 175.6 175.7 175.7 188.0 159.4 169.7 169.7 169.8 169.8 179.1 156.8

90 190.5 190.5 190.6 190.6 196.0 195.3 183.8 183.8 183.9 183.9 187.2 186.7 176.6 176.6 176.7 176.7 178.2 177.7

8400

75 164.1 163.9 183.9 136.8 196.5 76.6 159.1 159.1 177.0 134.2 187.5 73.7 154.9 154.9 170.1 131.7

80 174.2 174.2 183.2 181.5 197.6 124.4 169.1 169.1 176.0 175.3 188.9 121.6 164.0 164.0 169.0 168.5

85 184.4 184.4 184.5 184.5 197.3 171.6 178.5 178.5 178.6 178.6 188.5 169.2 172.2 172.2 172.2 172.2

90 193.2 193.2 193.3 193.3 196.3 195.8 185.9 185.9 186.0 186.0 187.3 186.8 177.9 177.9 177.9 177.9

-

-

-

-

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Stands for both downflow and horizontal unit.

-

-

-

-

RT-PRC028AC-EN 43

Performance Data

Table 20. Gross cooling capacities 17½ tons three phase standard efficiency T/YS*211G3,4,W

Air

Flow cfm

5600

6300

7000

Ambient Temperature

Ent

DB

(°F)

85 95

Entering Wet Bulb

105

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 186.0 161.1 210.2 124.5 233.8 85.5 176.4 156.7 199.5 120.1 221.1 80.9 166.4 152.2 188.0 115.4 207.2 76.0

80 185.1 184.9 209.9 155.7 233.8 117.2 175.8 175.6 199.3 151.4 221.1 112.6 166.2 166.1 187.8 146.7 207.3 107.7

85 191.8 191.8 209.4 186.6 233.7 148.7 184.3 184.3 198.6 182.2 221.0 144.1 176.1 176.1 187.1 177.5 207.2 139.2

90 203.1 203.1 208.5 208.2 233.5 180.1 195.2 195.2 198.0 197.7 220.9 175.5 186.5 186.5 187.0 186.9 207.0 170.5

75 189.9 172.8 214.5 131.5 237.5 87.3 179.9 168.3 203.2 126.9 224.3 82.7 169.5 163.7 191.1 122.1 209.7 77.6

80 189.1 188.9 214.2 166.6 237.5 123.0 179.8 179.7 203.0 162.1 224.3 118.4 171.3 171.3 190.9 157.3 209.8 113.3

85 199.0 199.0 213.3 201.1 237.4 158.5 191.0 191.0 202.1 196.4 224.2 153.8 182.3 182.3 190.0 189.1 209.8 148.9

90 210.7 210.7 212.4 212.2 237.1 193.7 202.2 202.2 202.4 202.4 223.9 189.0 192.8 192.8 193.0 193.0 209.5 183.9

75 193.1 184.2 218.0 138.3 240.3 89.1 182.8 179.0 206.3 133.6 226.6 84.4 171.9 171.4 193.7 128.7 211.5 79.2

80 193.0 193.0 217.6 177.2 240.4 128.8 185.0 185.0 205.9 172.6 226.7 124.0 176.3 176.3 193.3 167.7 211.7 118.9

85 205.2 205.2 216.5 213.8 240.3 168.2 196.7 196.7 204.5 204.1 226.7 163.5 187.4 187.4 191.9 191.6 211.8 158.4

7700

8400

Air

Flow cfm

5600

90 217.3 217.3 217.5 217.5 239.8 207.1 208.2 208.2 208.4 208.4 226.2 202.4 198.2 198.2 198.3 198.3 211.4 197.3

75 195.7 193.8 220.8 144.9 242.6 90.8 184.9 184.5 208.7 140.2 228.4 86.0 173.6 173.2 195.7 135.3 212.8 80.7

80 198.1 198.1 220.4 187.8 242.7 134.4 189.7 189.7 208.3 183.1 228.6 129.6 180.5 180.5 195.3 178.1 213.2 124.4

85 210.5 210.5 218.6 218.1 242.7 177.8 201.6 201.6 206.5 206.2 228.6 173.0 191.7 191.7 193.7 193.4 213.2 167.8

90 222.9 222.9 223.1 223.1 242.0 220.6 213.4 213.4 213.5 213.5 228.1 215.8 202.6 202.6 202.7 202.7 212.8 208.8

75 197.6 197.1 223.2 151.5 244.3 92.4 186.5 186.0 210.7 146.8 229.8 87.6 175.1 174.8 197.6 141.9 213.8 82.3

80 202.5 202.5 222.6 198.2 244.5 140.0 193.8 193.8 210.2 193.5 230.1 135.2 184.2 184.2 196.9 188.5 214.3 129.9

85 215.2 215.2 220.4 220.0 244.5 187.3 205.9 205.9 208.2 207.8 230.1 182.5 195.6 195.6 195.7 195.7 214.3 177.2

90 227.8 227.8 228.0 228.0 243.9 234.0 217.7 217.7 217.8 217.8 229.5 226.5 206.2 206.2 206.3 206.3 213.4 212.7

Ambient Temperature

Ent

DB

(°F)

115 120

Entering Wet Bulb

125

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 156.8 147.9 176.0 110.7 192.2 70.7 152.4 145.9 170.0 108.3 184.3 68.0

164.1 106.0 176.1 65.2

80 157.8 157.8 175.8 141.9 192.3 102.5 154.1 154.1 169.9 139.6 184.5 99.8

164.0 137.3 176.5 97.0

85 167.6 167.6 175.3 171.8 192.4 134.1 163.4 163.4 169.2 167.8 184.7 131.4 159.1 159.1 163.2 162.9 176.8 128.7

90 177.1 177.1 177.2 177.2 192.2 165.3 172.1 172.1 172.2 172.2 184.5 162.6 166.9 166.9 167.0 167.0 176.5 159.9

75 159.4 157.6 178.6 117.2 193.9 72.2 154.5 154.1 172.3 114.8 185.6 69.4 150.2 149.9 166.1 112.5 177.1 66.6

80 163.0 163.0 178.4 152.4 194.2 108.0 158.9 158.9 172.1 149.9 186.0 105.2 154.9 154.9 165.9 147.6 177.7 102.4

6300

7000

7700

85 173.0 173.0 177.3 177.0 194.3 143.5 168.3 168.3 171.1 170.8 186.2 140.8 163.4 163.4 164.9 164.6 177.9 138.0

90 182.5 182.5 182.7 182.7 194.1 178.6 177.0 177.0 177.2 177.2 186.0 175.9 171.1 171.1 171.2 171.2 177.7 172.5

75 161.1 160.8 180.6 123.7 195.1 73.7 156.2 155.9 174.2 121.3 186.5 70.8 151.7 151.4 167.8 118.9 177.7 67.9

80 167.4 167.4 180.3 162.7 195.6 113.5 162.9 162.9 173.8 160.2 187.2 110.7 158.5 158.5 167.3 157.8 178.6 107.8

85 177.4 177.4 179.1 178.7 195.7 152.9 172.2 172.2 172.7 172.5 187.3 150.1 166.8 166.8 166.9 166.9 178.6 147.2

90 187.0 187.0 187.1 187.1 195.4 190.8 180.9 180.9 181.0 181.0 187.0 185.9 174.4 174.4 174.5 174.5 178.1 177.5

75 162.7 162.4 182.3 130.3 195.9 75.2 157.6 157.3 175.7 127.8 187.1 72.3 153.1 152.9 169.2 125.3 178.1 69.3

80 171.1 171.1 181.8 173.0 196.6 118.9 166.3 166.3 175.1 170.3 188.1 116.1 161.5 161.5 168.5 166.3 179.4 113.3

85 181.2 181.2 181.3 181.3 196.6 162.3 175.6 175.6 175.7 175.7 188.0 159.4 169.7 169.7 169.8 169.8 179.1 156.8

90 190.5 190.5 190.6 190.6 196.0 195.3 183.8 183.8 183.9 183.9 187.2 186.7 176.6 176.6 176.7 176.7 178.2 177.7

8400

75 164.1 163.9 183.9 136.8 196.5 76.6 159.1 159.1 177.0 134.2 187.5 73.7 154.9 154.9 170.1 131.7

80 174.2 174.2 183.2 181.5 197.6 124.4 169.1 169.1 176.0 175.3 188.9 121.6 164.0 164.0 169.0 168.5

85 184.4 184.4 184.5 184.5 197.3 171.6 178.5 178.5 178.6 178.6 188.5 169.2 172.2 172.2 172.2 172.2

90 193.2 193.2 193.3 193.3 196.3 195.8 185.9 185.9 186.0 186.0 187.3 186.8 177.9 177.9 177.9 177.9

-

-

-

-

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Stands for both downflow and horizontal unit.

-

-

-

-

44 RT-PRC028AC-EN

Performance Data

Table 21. Gross cooling capacities 20 tons three phase standard efficiency T/YS*240G3,4,W,K

Air

Flow cfm

6400

7200

8000

Ambient Temperature

Ent

DB

(°F)

85 95

Entering Wet Bulb

105

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 230.4 187.9 260.3 147.4 287.7 103.3 219.7 182.8 247.5 142.0 271.7 97.5 208.2 177.5 233.5 136.2 253.6 91.0

80 229.9 221.9 260.2 182.1 287.8 138.7 219.2 216.9 247.4 176.7 271.9 132.8 207.8 207.5 233.4 170.9 253.9 126.3

85 231.6 231.5 260.0 216.6 287.9 173.7 222.2 222.2 247.2 211.2 272.0 167.9 213.1 213.1 233.1 205.4 254.1 161.4

90 244.0 244.0 259.2 250.6 287.9 208.5 235.1 235.1 246.5 245.2 272.1 202.7 225.2 225.2 232.8 232.5 254.4 196.3

75 236.0 200.9 265.9 154.9 292.1 105.1 224.6 195.6 252.3 149.4 275.0 99.0 212.2 190.0 237.4 143.4 255.9 92.3

80 235.3 234.9 265.7 193.9 292.3 144.8 224.0 223.7 252.1 188.4 275.2 138.7 211.9 211.7 237.3 182.4 256.1 132.0

85 239.6 239.6 265.4 232.7 292.4 184.2 230.6 230.6 251.7 227.1 275.5 178.2 220.6 220.6 236.9 221.1 256.5 171.5

90 253.6 253.6 264.7 264.3 292.5 223.4 244.0 244.0 251.2 250.9 275.7 217.4 233.1 233.1 236.8 236.5 256.6 211.2

75 240.4 213.5 270.2 162.2 295.3 106.7 228.3 208.1 256.0 156.5 277.2 100.4 215.3 202.4 240.4 150.4 258.3 93.9

80 239.6 239.3 270.0 205.6 295.5 150.8 227.9 227.6 255.7 199.9 277.6 144.5 215.6 215.4 240.3 193.8 258.6 138.0

85 247.4 247.4 269.5 248.5 295.8 194.6 237.8 237.8 255.2 242.8 278.0 188.4 227.0 227.0 239.7 236.7 258.8 181.7

8800

9600

Air

Flow cfm

6400

90 261.8 261.8 268.9 268.5 295.9 238.2 251.4 251.4 255.0 254.7 278.1 232.0 239.5 239.5 240.4 240.2 258.4 225.6

75 243.8 225.9 273.8 169.4 297.6 108.2 231.2 220.4 258.9 163.6 279.5 101.9 217.8 214.6 242.7 157.3 260.1 95.4

80 243.2 242.9 273.5 217.1 298.0 156.7 231.5 231.3 258.8 211.5 279.5 150.4 219.1 219.1 242.7 205.1 260.4 143.9

85 254.2 254.2 272.7 264.2 298.3 204.9 243.9 243.9 258.0 257.1 279.9 198.5 232.4 232.4 242.1 241.6 260.5 192.0

90 268.8 268.8 272.5 272.3 298.4 252.8 257.6 257.6 258.7 258.4 279.8 246.5 244.7 244.7 244.9 244.9 260.4 239.8

75 246.6 238.2 276.6 176.5 299.5 109.6 233.8 232.7 261.3 170.6 281.4 103.5 219.9 219.4 244.6 164.2 261.5 96.9

80 246.7 246.5 276.5 228.6 299.8 162.5 234.7 234.7 261.3 222.7 281.7 156.4 223.6 223.6 244.5 216.3 261.9 149.8

85 260.1 260.1 275.5 274.8 300.3 215.2 249.2 249.2 260.3 259.7 281.7 209.0 237.0 237.0 243.7 243.3 262.2 202.4

90 274.9 274.9 276.0 275.8 300.2 267.3 262.9 262.9 263.1 263.1 281.3 260.9 249.0 249.0 249.2 249.2 261.8 254.3

Ambient Temperature

Ent

DB

(°F)

115 120

Entering Wet Bulb

125

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 196.3 172.1 218.4 130.1 234.3 84.1 190.2 169.3 210.4 126.9 224.3 80.6

202.2 123.7 214.0 77.1

80 196.0 195.8 218.4 164.8 234.5 119.4 190.1 189.9 210.5 161.7 224.6 116.0

85 203.1 203.1 218.1 199.3 234.6 154.4 198.0 198.0 210.2 196.1 224.9 151.0

-

-

-

-

202.4 158.5 214.4 112.4

202.2 192.9 214.8 147.5

90 214.2 214.2 218.0 217.8 234.7 189.3 208.2 208.2 210.3 210.1 225.0 185.9

202.5 202.3 214.9 182.4

75 199.5 184.4 221.4 137.1 236.4 85.5 193.1 181.5 213.0 133.8 226.0 82.0 186.8 178.8 204.4 130.4 215.2 78.4

80 199.6 199.5 221.4 176.2 236.7 125.3 193.6 193.5 213.1 172.9 226.4 121.7 187.8 187.8 204.6 169.6 215.7 118.1

7200

8000

8800

85 209.8 209.8 221.0 214.8 237.0 164.7 203.9 203.9 212.8 210.3 226.8 161.2 197.8 197.8 204.4 203.4 216.3 157.6

90 220.8 220.8 221.5 221.3 237.0 203.9 214.0 214.0 214.1 214.1 226.7 200.3 206.6 206.6 206.7 206.7 216.2 196.8

75 202.1 196.5 223.6 143.9 237.9 87.0 195.4 193.3 214.9 140.6 227.0 83.3 188.8 187.8 205.9 137.2 215.8 79.6

80 203.3 203.3 223.7 187.4 238.3 131.1 197.8 197.8 215.0 184.0 227.6 127.5 192.1 192.1 206.0 180.6 216.6 123.8

85 215.2 215.2 223.3 222.8 238.5 174.9 208.8 208.8 214.6 214.3 228.2 171.5 202.0 202.0 205.8 205.4 217.2 167.8

90 225.9 225.9 226.1 226.1 238.6 218.3 218.3 218.3 218.4 218.4 228.0 214.8 209.9 209.9 210.0 210.0 217.0 210.6

75 204.1 203.6 225.4 150.7 239.0 88.4 197.3 196.8 216.3 147.3 227.7 84.7 190.4 189.9 207.1 143.8

-

80 207.8 207.8 225.4 198.5 239.5 136.9 201.8 201.8 216.3 195.1 228.5 133.3 195.7 195.7 207.1 191.6

85 219.7 219.7 224.9 224.5 240.0 185.2 212.7 212.7 215.9 215.5 229.0 181.6 205.2 205.2 206.8 206.4

90 229.8 229.8 229.9 229.9 239.7 232.8 221.2 221.2 221.3 221.3 228.9 224.7 212.2 212.2 212.3 212.3

-

-

-

-

-

-

9600

75 205.8 205.3 226.7 157.5 239.7 89.8 198.5 198.1 217.4 154.0 228.2 86.0 191.4 191.0

80 211.6 211.6 226.6 209.5 240.4 142.7 205.2 205.2 217.3 206.0 229.1 139.1 198.5 198.5

85 223.3 223.3 226.1 225.7 240.9 195.4 215.8 215.8 216.9 216.5 229.6 191.7 207.7 207.7

90 232.6 232.6 232.7 232.7 240.7 239.0 223.6 223.6 223.7 223.7 229.5 228.8 214.5 214.5

-

-

-

-

-

-

-

-

-

-

-

-

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Stands for both downflow and horizontal unit.

-

-

-

-

RT-PRC028AC-EN 45

Performance Data

Table 22. Gross cooling capacities 25 tons three phase standard efficiency T/YS*300G3,4,W,K

Air

Flow cfm

7000

8000

9000

Ambient Temperature

Ent

DB

(°F)

85 95

Entering Wet Bulb

105

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 257.6 212.0 289.0 165.3 317.0 114.6 245.8 206.5 274.9 159.4 299.4 108.2 233.1 200.6 259.5 153.1 279.6 101.1

80 257.0 250.5 288.9 204.5 317.1 154.5 245.3 244.2 274.8 198.7 299.5 148.1 232.7 232.3 259.5 192.4 279.8 141.0

85 259.2 259.1 288.8 243.6 317.2 194.2 249.7 249.7 274.6 237.7 299.7 187.7 239.4 239.4 259.2 231.3 280.1 180.7

90 273.4 273.4 287.9 282.0 317.2 233.5 263.5 263.5 274.1 273.6 299.8 227.1 252.3 252.3 258.7 258.4 280.4 220.2

75 264.4 228.7 295.5 175.0 321.8 116.8 251.7 223.0 280.5 168.9 302.9 110.1 238.0 216.8 264.2 162.4 281.8 102.7

80 263.5 263.0 295.4 219.8 322.0 162.4 250.9 250.6 280.4 213.7 303.1 155.7 237.6 237.4 264.1 207.3 282.0 148.3

85 270.1 270.1 295.0 264.3 322.1 207.6 259.9 259.9 279.9 258.2 303.4 201.0 248.6 248.6 263.6 251.6 282.5 193.7

90 285.1 285.1 294.2 293.7 322.2 252.7 274.1 274.1 279.3 279.0 303.6 246.1 261.6 261.6 263.6 263.4 282.7 238.7

75 269.4 245.0 300.5 184.4 325.2 118.8 256.0 239.1 284.8 178.2 305.1 111.8 241.7 232.8 267.6 171.5 284.3 104.8

80 268.4 268.1 300.4 234.8 325.4 170.0 255.7 255.5 284.7 228.6 305.4 163.1 242.3 242.1 267.6 222.1 284.5 156.0

85 279.4 279.4 299.7 284.7 325.7 221.0 268.4 268.4 283.9 278.5 305.9 214.1 256.1 256.1 267.0 266.2 284.7 206.9

10000

11000

Air

Flow cfm

7000

90 294.7 294.7 299.1 298.8 325.8 271.6 282.6 282.6 284.2 284.0 306.1 264.8 268.8 268.8 269.0 269.0 284.4 257.6

75 273.3 261.1 304.4 193.6 327.7 120.8 259.5 255.0 288.0 187.3 307.8 114.0 244.7 244.0 270.1 180.4 286.4 106.9

80 273.1 272.9 304.3 249.8 328.0 177.7 260.3 260.3 288.1 243.4 307.8 170.8 248.3 248.3 270.2 236.5 286.7 163.8

85 287.3 287.3 303.3 302.5 328.3 234.3 275.4 275.4 287.0 286.2 307.9 227.3 262.1 262.1 269.1 268.5 286.9 220.4

90 302.6 302.6 303.8 303.5 328.2 290.4 289.5 289.5 289.7 289.7 307.7 283.6 274.4 274.4 274.5 274.5 286.4 276.4

75 276.5 275.7 307.6 202.8 330.2 122.9 262.3 261.6 290.6 196.3 310.1 116.2 247.0 246.2 272.1 189.3 288.1 109.0

80 277.6 277.6 307.6 264.5 330.3 185.5 266.1 266.1 290.6 258.0 310.3 178.8 253.4 253.4 272.0 251.0 288.4 171.5

85 293.9 293.9 306.1 305.3 331.2 247.7 281.3 281.3 289.1 288.4 310.4 241.0 267.1 267.1 270.8 270.4 288.6 233.8

90 309.2 309.2 309.4 309.4 330.3 309.3 295.0 295.0 295.2 295.2 309.5 302.3 278.5 278.5 278.7 278.7 288.1 286.9

Ambient Temperature

Ent

DB

(°F)

115 120

Entering Wet Bulb

125

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 219.7 194.5 243.0 146.4 258.2 93.6 212.8 191.4 234.3 143.0 247.2 89.8

236.0 85.9

80 219.4 219.2 243.0 185.7 258.2 133.4 212.8 212.5 234.3 182.3 247.5 129.7

85 228.2 228.2 242.7 224.7 258.5 173.0 222.2 222.2 234.1 221.2 247.8 169.3

90 239.8 239.8 242.5 242.2 258.7 212.5 233.0 233.0 234.1 233.9 247.9 208.7

75 223.7 210.5 246.5 155.4 260.3 95.4 216.5 207.3 237.3 151.9 248.8 91.5

80 224.1 224.0 246.6 200.4 260.5 140.9 217.8 217.8 237.4 196.8 249.1 137.1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

236.2 125.8

236.6 165.5

236.8 204.9

227.8 148.2 236.9 87.5

228.0 193.2 237.3 133.1

8000

9000

10000

85 236.1 236.1 246.2 243.9 260.9 186.2 229.4 229.4 237.1 236.4 249.6 182.4

90 247.4 247.4 247.6 247.6 260.9 231.2 239.5 239.5 239.7 239.7 249.6 227.3

75 226.8 224.9 249.1 164.3 261.8 97.2 219.3 218.6 239.4 160.7 249.9 93.3

80 230.0 230.0 249.1 214.9 262.2 148.5 223.5 223.5 239.5 211.2 250.3 144.6

85 242.4 242.4 248.5 248.1 262.5 199.5 234.9 234.9 238.9 238.5 250.7 195.6

-

-

-

-

-

-

-

-

-

-

227.6 227.1 238.0 178.6

231.1 231.1 238.0 223.4

229.5 156.9

229.6 207.4

229.1 228.7

-

-

-

-

-

-

90 252.9 252.9 253.0 253.0 262.4 249.9 243.8 243.8 243.9 243.9 251.0 246.1

233.9 233.9

75 229.3 228.7 251.0 173.2 263.2 99.2 221.2 220.7 241.0 169.4 250.7 95.1 213.2 212.8 230.8 165.7

80 235.2 235.2 250.9 229.2 263.6 156.2 228.2 228.2 240.9 225.5 251.4 152.2 220.9 220.9 230.7 221.7

85 247.3 247.3 250.1 249.6 263.9 212.8 239.1 239.1 240.3 240.0 251.7 208.8 230.3 230.3 230.4 230.4

90 256.6 256.6 256.7 256.7 263.7 262.7 246.2 246.2 246.3 246.3 251.6 250.6 236.1 236.1 236.2 236.2

-

-

-

-

-

-

-

-

-

-

11000

75 230.8 230.4 252.4 182.0 264.0 101.1 222.7 222.3 242.1 178.2 251.2 97.0 214.6 214.1

80 239.4 239.4 252.2 243.6 264.7 163.8 232.0 232.0 242.0 238.9 252.1 159.8 224.1 224.1

85 251.0 251.0 251.7 251.3 264.9 226.1 242.1 242.1 242.2 242.2 252.4 222.0 232.5 232.5

90 258.7 258.7 258.8 258.8 264.6 263.8 248.7 248.7 248.8 248.8 252.1 251.4 237.7 237.7

-

-

-

-

-

-

-

-

-

-

-

-

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Stands for both downflow and horizontal unit.

-

-

-

-

46 RT-PRC028AC-EN

Performance Data

Table 23. Gross cooling capacities 25 tons three phase standard efficiency T/YS*301G3,4,W

Air

Flow cfm

7000

8000

9000

Ambient Temperature

Ent

DB

(°F)

85 95

Entering Wet Bulb

105

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 257.6 212.0 289.0 165.3 317.0 114.6 245.8 206.5 274.9 159.4 299.4 108.2 233.1 200.6 259.5 153.1 279.6 101.1

80 257.0 250.5 288.9 204.5 317.1 154.5 245.3 244.2 274.8 198.7 299.5 148.1 232.7 232.3 259.5 192.4 279.8 141.0

85 259.2 259.1 288.8 243.6 317.2 194.2 249.7 249.7 274.6 237.7 299.7 187.7 239.4 239.4 259.2 231.3 280.1 180.7

90 273.4 273.4 287.9 282.0 317.2 233.5 263.5 263.5 274.1 273.6 299.8 227.1 252.3 252.3 258.7 258.4 280.4 220.2

75 264.4 228.7 295.5 175.0 321.8 116.8 251.7 223.0 280.5 168.9 302.9 110.1 238.0 216.8 264.2 162.4 281.8 102.7

80 263.5 263.0 295.4 219.8 322.0 162.4 250.9 250.6 280.4 213.7 303.1 155.7 237.6 237.4 264.1 207.3 282.0 148.3

85 270.1 270.1 295.0 264.3 322.1 207.6 259.9 259.9 279.9 258.2 303.4 201.0 248.6 248.6 263.6 251.6 282.5 193.7

90 285.1 285.1 294.2 293.7 322.2 252.7 274.1 274.1 279.3 279.0 303.6 246.1 261.6 261.6 263.6 263.4 282.7 238.7

75 269.4 245.0 300.5 184.4 325.2 118.8 256.0 239.1 284.8 178.2 305.1 111.8 241.7 232.8 267.6 171.5 284.3 104.8

80 268.4 268.1 300.4 234.8 325.4 170.0 255.7 255.5 284.7 228.6 305.4 163.1 242.3 242.1 267.6 222.1 284.5 156.0

85 279.4 279.4 299.7 284.7 325.7 221.0 268.4 268.4 283.9 278.5 305.9 214.1 256.1 256.1 267.0 266.2 284.7 206.9

10000

11000

Air

Flow cfm

7000

90 294.7 294.7 299.1 298.8 325.8 271.6 282.6 282.6 284.2 284.0 306.1 264.8 268.8 268.8 269.0 269.0 284.4 257.6

75 273.3 261.1 304.4 193.6 327.7 120.8 259.5 255.0 288.0 187.3 307.8 114.0 244.7 244.0 270.1 180.4 286.4 106.9

80 273.1 272.9 304.3 249.8 328.0 177.7 260.3 260.3 288.1 243.4 307.8 170.8 248.3 248.3 270.2 236.5 286.7 163.8

85 287.3 287.3 303.3 302.5 328.3 234.3 275.4 275.4 287.0 286.2 307.9 227.3 262.1 262.1 269.1 268.5 286.9 220.4

90 302.6 302.6 303.8 303.5 328.2 290.4 289.5 289.5 289.7 289.7 307.7 283.6 274.4 274.4 274.5 274.5 286.4 276.4

75 276.5 275.7 307.6 202.8 330.2 122.9 262.3 261.6 290.6 196.3 310.1 116.2 247.0 246.2 272.1 189.3 288.1 109.0

80 277.6 277.6 307.6 264.5 330.3 185.5 266.1 266.1 290.6 258.0 310.3 178.8 253.4 253.4 272.0 251.0 288.4 171.5

85 293.9 293.9 306.1 305.3 331.2 247.7 281.3 281.3 289.1 288.4 310.4 241.0 267.1 267.1 270.8 270.4 288.6 233.8

90 309.2 309.2 309.4 309.4 330.3 309.3 295.0 295.0 295.2 295.2 309.5 302.3 278.5 278.5 278.7 278.7 288.1 286.9

Ambient Temperature

Ent

DB

(°F)

115 120

Entering Wet Bulb

125

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 219.7 194.5 243.0 146.4 258.2 93.6 212.8 191.4 234.3 143.0 247.2 89.8

236.0 85.9

80 219.4 219.2 243.0 185.7 258.2 133.4 212.8 212.5 234.3 182.3 247.5 129.7

85 228.2 228.2 242.7 224.7 258.5 173.0 222.2 222.2 234.1 221.2 247.8 169.3

90 239.8 239.8 242.5 242.2 258.7 212.5 233.0 233.0 234.1 233.9 247.9 208.7

75 223.7 210.5 246.5 155.4 260.3 95.4 216.5 207.3 237.3 151.9 248.8 91.5

80 224.1 224.0 246.6 200.4 260.5 140.9 217.8 217.8 237.4 196.8 249.1 137.1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

236.2 125.8

236.6 165.5

236.8 204.9

227.8 148.2 236.9 87.5

228.0 193.2 237.3 133.1

8000

9000

10000

85 236.1 236.1 246.2 243.9 260.9 186.2 229.4 229.4 237.1 236.4 249.6 182.4

90 247.4 247.4 247.6 247.6 260.9 231.2 239.5 239.5 239.7 239.7 249.6 227.3

75 226.8 224.9 249.1 164.3 261.8 97.2 219.3 218.6 239.4 160.7 249.9 93.3

80 230.0 230.0 249.1 214.9 262.2 148.5 223.5 223.5 239.5 211.2 250.3 144.6

85 242.4 242.4 248.5 248.1 262.5 199.5 234.9 234.9 238.9 238.5 250.7 195.6

-

-

-

-

-

-

-

-

-

-

227.6 227.1 238.0 178.6

231.1 231.1 238.0 223.4

229.5 156.9

229.6 207.4

229.1 228.7

-

-

-

-

-

-

90 252.9 252.9 253.0 253.0 262.4 249.9 243.8 243.8 243.9 243.9 251.0 246.1

233.9 233.9

75 229.3 228.7 251.0 173.2 263.2 99.2 221.2 220.7 241.0 169.4 250.7 95.1 213.2 212.8 230.8 165.7

80 235.2 235.2 250.9 229.2 263.6 156.2 228.2 228.2 240.9 225.5 251.4 152.2 220.9 220.9 230.7 221.7

85 247.3 247.3 250.1 249.6 263.9 212.8 239.1 239.1 240.3 240.0 251.7 208.8 230.3 230.3 230.4 230.4

90 256.6 256.6 256.7 256.7 263.7 262.7 246.2 246.2 246.3 246.3 251.6 250.6 236.1 236.1 236.2 236.2

-

-

-

-

-

-

-

-

-

-

11000

75 230.8 230.4 252.4 182.0 264.0 101.1 222.7 222.3 242.1 178.2 251.2 97.0 214.6 214.1

80 239.4 239.4 252.2 243.6 264.7 163.8 232.0 232.0 242.0 238.9 252.1 159.8 224.1 224.1

85 251.0 251.0 251.7 251.3 264.9 226.1 242.1 242.1 242.2 242.2 252.4 222.0 232.5 232.5

90 258.7 258.7 258.8 258.8 264.6 263.8 248.7 248.7 248.8 248.8 252.1 251.4 237.7 237.7

-

-

-

-

-

-

-

-

-

-

-

-

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Stands for both downflow and horizontal unit.

-

-

-

-

RT-PRC028AC-EN 47

Performance Data

Table 24. Gross cooling capacities 12½ tons three phase high efficiency T/YH*150G3,4,W (stage 1)

Air

Flow cfm

Ent

DB

(°F)

Ambient Temperature

85 95

Entering Wet Bulb

61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

2000

2500

3000

3500

4000

85

90

75

80

85

90

75

80

85

90

75

80

85

90

75

80

85

90

75

80

42.0 39.3 45.3 31.2 49.8 15.0 39.2 37.2 42.3 29.4 46.7 13.6

44.2 43.5 46.2 39.1 50.3 29.0 41.5 41.2 43.3 37.1 47.2 27.2

46.9 46.6 48.0 44.3 50.7 38.0 44.1 44.1 45.1 42.1 47.6 36.1

49.6 49.3 50.4 48.1 52.2 44.1 46.9 46.8 47.5 45.8 49.1 42.1

43.3 41.5 46.2 33.6 50.4 17.5 40.4 39.2 43.1 31.6 47.1 15.9

45.7 45.7 47.4 41.6 51.1 31.5 42.8 42.8 44.3 39.3 47.9 29.6

48.5 48.5 49.5 46.9 51.8 40.7 45.6 45.6 46.4 44.6 48.6 38.6

51.5 51.5 52.0 50.9 53.5 47.0 48.5 48.5 48.9 48.4 50.3 44.7

44.4 43.3 46.9 35.5 50.8 19.5 41.3 40.8 43.7 33.3 47.3 17.7

47.0 47.0 48.4 43.6 51.7 33.6 44.0 44.0 45.1 41.2 48.3 31.6

50.0 50.0 50.6 49.1 52.7 42.9 46.9 46.9 47.4 46.5 49.3 40.6

53.0 53.0 53.3 53.2 54.6 49.3 49.9 49.9 50.1 50.1 51.2 46.9

45.2 44.7 47.4 37.0 50.9 21.1 42.0 42.0 44.0 34.6 47.7 19.1

48.1 48.1 49.1 45.2 52.1 35.3 44.8 44.8 45.7 42.6 48.5 33.0

51.2 51.2 51.6 50.8 53.3 44.7 48.1 47.9 48.2 48.0 49.8 42.2

54.3 54.3 54.4 54.4 55.4 51.3 50.6 50.6 51.0 51.0 51.9 48.6

45.8 45.6 47.6 38.0 51.3 22.3 42.4 42.4 44.3 35.4 48.4 20.0

48.9 48.9 49.6 46.3 52.2 36.6 45.5 45.5 46.0 43.5 48.7 34.1

52.1 52.1 52.3 52.1 53.7 46.1 48.6 48.6 48.7 48.7 50.0 43.4

54.8 54.8 55.2 55.2 56.0 52.8 51.2 51.2 51.7 51.7 52.3 49.9

4375

75

80

85

90

46.1 46.0 47.6 38.5 51.9 22.8 42.6 42.6 44.6 35.8 48.7 20.5

49.3 49.3 49.8 46.9 52.4 37.2 45.8 45.8 46.1 43.9 48.9 34.6

52.3 52.3 52.6 52.6 53.9 46.8 48.8 48.8 49.0 49.0 50.3 44.0

55.2 55.2 55.7 55.7 56.3 53.6 52.0 52.0 52.1 52.1 52.5 50.6

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

48 RT-PRC028AC-EN

Performance Data

Table 25. Gross cooling capacities 12½ tons three phase high efficiency T/YH*150G3,4,W (stage 2)

Air

Flow cfm

Ent

DB

(°F)

Ambient Temperature

85 95

Entering Wet Bulb

61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

2000

2500

3000

3500

4000

75

80

85

90

87.1 69.1 97.7 56.8 108.4 33.8 83.2 66.7 92.6 54.8 102.7 32.4

88.4 76.3 98.3 68.1 110.1 52.4 84.5 73.5 93.8 65.7 104.8 50.5

91.0 81.9 99.1 76.1 110.6 65.0 87.1 78.9 94.7 73.5 105.5 62.7

94.6 86.6 101.5 82.3 111.0 73.9 90.6 83.5 97.0 79.4 106.0 71.4

75

80

92.4 75.4 101.4 62.0 112.8 37.9 88.1 72.7 96.9 59.7 105.9 36.2

94.3 83.2 103.5 74.1 114.0 57.5 90.1 80.3 98.7 71.6 109.8 55.3

85 97.5 89.5 105.0 83.0 115.8 71.0 93.3 86.3 100.2 80.1 110.4 68.5

90 101.5 94.7 107.9 89.7 116.8 80.7 97.3 91.3 103.2 86.6 111.5 77.9

75

80

96.8 80.9 107.7 66.4 114.3 41.2 92.3 78.0 102.4 64.0 113.2 39.3

99.4 89.5 107.8 79.5 118.5 61.9 94.9 86.3 102.7 76.7 114.1 59.5

85 103.1 96.3 110.0 89.1 120.1 76.2 98.6 92.9 105.0 86.0 114.4 73.5

90 107.6 102.0 113.5 96.4 121.8 86.7 103.1 98.4 108.5 93.1 116.2 83.7

75 100.3 85.7 110.4 70.2 120.2 43.8 95.6 82.5 104.8 67.5 115.7 41.7

80 103.6 95.0 111.4 84.2 123.3 65.5 98.9 91.6 106.0 81.1 117.2 62.9

85 107.9 102.4 114.2 94.5 123.6 80.8 103.2 98.8 108.9 91.1 117.7 77.8

90 112.9 108.7 118.3 102.4 126.0 92.0 108.1 104.9 112.9 98.9 120.1 88.7

75 103.1 89.8 112.3 73.3 121.4 45.7 98.0 86.4 106.5 70.4 116.8 43.3

80 107.0 99.8 114.1 88.1 125.2 68.5 102.0 96.2 108.4 84.9 118.8 65.7

85 111.9 107.9 117.5 99.1 126.3 84.6 106.9 104.0 112.0 95.6 120.0 81.5

90 117.4 114.6 122.2 107.7 129.3 96.5 112.3 110.6 116.6 103.9 123.2 93.1

4375

75 104.6 92.4 113.2 75.1 122.6 46.7 99.3 88.8 107.1 72.0 117.4 44.1

80 109.0 103.0 115.5 90.6 126.1 70.3 103.8 99.1 109.7 87.2 119.4 67.3

85 114.3 111.5 119.5 102.2 127.7 87.1 109.1 107.4 113.7 98.5 121.3 83.7

90 120.1 118.6 124.6 111.2 131.3 99.5 114.8 114.4 118.8 107.3 124.9 95.9

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

RT-PRC028AC-EN 49

Performance Data

Table 26. Gross cooling capacities 12½ tons three phase high efficiency T/YH*150G3,4,W (full load)

Air

Flow cfm

2500

3000

3500

4000

4500

5000

5500

6000

Ent

DB

(°F)

85

Ambient Temperature

95 105

Entering Wet Bulb

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 125.0 96.9 138.0 75.5 153.6 38.3 118.3 92.7 130.4 72.3 145.1 36.2 111.1 88.1 122.3 68.7 136.2 33.8

80 127.7 109.0 139.6 94.4 154.2 68.6 121.0 104.1 132.0 90.4 145.7 65.6 113.8 98.9 123.9 86.0 136.7 62.2

85 132.0 118.4 141.2 108.0 154.7 89.5 125.1 113.0 133.5 103.4 146.2 85.7 117.8 107.3 125.5 98.4 137.2 81.5

90 137.2 126.3 144.6 118.4 155.2 104.6 130.0 120.5 136.8 113.3 146.7 100.1 122.5 114.3 128.6 107.7 137.8 95.3

75 131.2 104.5 143.4 82.5 158.2 44.6 124.1 99.9 135.4 78.9 149.3 42.1 116.5 94.9 126.9 74.9 140.0 39.3

80 134.4 117.1 145.5 102.0 159.3 75.6 127.3 111.8 137.5 97.6 150.4 72.2 119.7 106.2 129.0 92.9 141.0 68.4

85 139.1 127.0 147.6 116.2 160.4 97.2 131.8 121.2 139.6 111.1 151.4 93.0 124.1 115.1 131.1 105.7 142.1 88.4

90 144.6 135.3 151.5 127.1 161.4 112.8 137.1 129.1 143.3 121.5 152.5 107.9 129.1 122.5 134.6 115.6 143.1 102.7

75 136.7 111.4 148.1 88.8 162.1 50.2 129.2 106.4 142.1 84.8 152.8 47.4 121.2 101.0 133.1 80.4 143.1 44.2

80 140.5 124.5 150.7 108.9 163.7 82.0 132.9 118.8 142.3 104.1 154.4 78.2 124.9 112.8 133.4 99.0 144.6 74.0

85 145.6 134.9 153.4 123.6 165.3 104.2 137.8 128.7 144.9 118.2 156.0 99.5 129.7 122.2 136.0 112.4 146.2 94.6

90 151.4 143.6 157.6 135.0 166.9 120.3 143.4 137.0 149.0 129.0 157.6 115.1 135.0 130.0 140.0 122.7 147.8 109.5

75 141.5 117.6 154.6 94.4 165.3 55.2 133.5 112.2 145.6 90.0 155.6 51.9 125.1 106.4 136.1 85.3 145.4 48.3

80 145.8 131.3 155.2 115.2 167.4 87.7 137.8 125.2 146.4 110.0 157.7 83.4 129.4 118.8 137.0 104.5 147.5 78.9

85 151.3 142.1 158.4 130.4 169.6 110.5 143.2 135.5 149.5 124.6 159.8 105.5 134.6 128.6 140.2 118.4 149.6 100.1

90 157.4 151.2 163.1 142.3 171.7 127.2 149.1 144.2 154.0 135.9 161.9 121.5 140.2 136.9 144.6 129.2 151.7 115.5

75 145.6 123.2 157.7 99.4 173.0 59.4 137.2 117.4 148.3 94.6 162.6 55.8 128.4 111.2 138.4 89.4 151.7 51.8

80 150.4 137.3 159.0 120.8 173.0 92.7 142.0 130.9 149.7 115.2 162.7 88.1 133.2 124.1 140.0 109.3 152.0 83.1

85 156.3 148.7 162.7 136.6 173.1 116.1 147.8 141.7 153.4 130.3 162.9 110.7 138.8 134.4 143.7 123.7 152.3 105.0

90 162.8 158.2 167.8 148.9 175.8 133.4 154.0 150.8 158.4 142.1 165.6 127.3 144.7 143.1 148.5 135.0 155.0 120.9

75 149.0 128.0 160.1 103.7 174.5 63.1 140.2 121.8 150.2 98.5 163.6 59.0 130.9 115.3 139.9 92.9 152.3 54.6

80 154.3 142.8 162.1 125.7 175.2 97.0 145.5 135.9 152.4 119.7 164.5 92.0 136.2 128.7 142.2 113.4 153.3 86.7

85 160.6 154.5 166.3 142.0 175.9 121.1 151.6 147.2 156.6 135.4 165.3 115.3 142.2 139.5 146.5 128.4 154.3 109.1

90 167.4 164.5 171.8 154.8 179.1 138.9 158.2 156.7 162.0 147.6 168.5 132.4 148.5 148.5 151.7 140.1 157.5 125.6

75 151.6 132.3 161.8 107.3 175.2 66.0 142.4 125.7 151.5 101.7 164.0 61.5 132.7 118.7 140.8 95.8 152.8 56.8

80 157.5 147.5 164.5 129.9 176.6 100.7 148.2 140.3 154.3 123.6 165.5 95.3 138.6 132.7 143.8 116.8 153.9 89.5

85 164.2 159.7 169.2 146.8 178.0 125.4 154.8 152.0 159.1 139.8 167.0 119.2 145.0 143.9 148.5 132.4 155.6 112.6

90 171.3 170.1 175.1 160.0 181.8 143.7 161.7 161.7 164.9 152.5 170.7 136.9 151.6 151.6 154.2 144.6 159.3 129.7

75 153.6 135.8 162.8 110.2 175.3 68.2 143.9 128.8 152.1 104.2 164.5 63.4 133.8 121.5 140.9 97.9 153.2 58.2

80 160.0 151.6 166.1 133.5 177.4 103.7 150.3 144.0 155.6 126.7 165.8 97.9 140.2 136.0 144.6 119.6 154.5 91.7

85 167.1 164.3 171.4 150.9 179.4 129.0 157.3 156.1 160.9 143.5 168.0 122.4 147.0 147.0 149.9 135.7 156.2 115.5

90 174.5 174.5 177.7 164.6 183.7 147.9 164.4 164.4 167.1 156.7 172.3 140.6 154.0 154.0 155.9 148.4 160.4 133.1

50 RT-PRC028AC-EN

Performance Data

Table 26. Gross cooling capacities 12½ tons three phase high efficiency T/YH*150G3,4,W (full load)

Air

Flow cfm

2500

Ent

DB

(°F)

115

Ambient Temperature

120 125

61 67 73 61

Entering Wet Bulb

67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 103.5 83.2 113.8 64.9 126.9 31.1 99.5 80.7 109.4 62.8 122.0 29.6 95.5 78.0 104.9 60.6 117.0 28.0

80 106.2 93.3 115.4 81.4 127.4 58.5 102.2 90.4 110.9 78.9 122.5 56.5 98.1 87.5 106.4 76.4 117.5 54.4

85 110.0 101.2 116.9 93.0 127.9 77.0 105.9 98.1 112.5 90.3 123.0 74.7 101.8 94.8 107.9 87.4 118.0 72.2

90 114.5 107.9 119.9 101.9 128.4 90.2 110.3 104.5 115.4 98.8 123.5 87.5 106.0 101.1 110.8 95.7 118.5 84.7

75 108.5 89.6 118.0 70.6 130.2 36.2 104.3 86.8 113.3 68.4 125.1 34.5 100.0 84.0 108.6 66.0 120.0 32.7

3000

3500

4000

4500

5000

80 111.7 100.3 120.0 87.8 131.2 64.3 107.5 97.2 115.4 85.1 126.2 62.1 103.2 94.0 110.7 82.4 121.0 59.9

85 115.9 108.6 122.1 100.0 132.3 83.5 111.6 105.3 117.5 97.0 127.2 80.9 107.3 101.8 112.7 94.0 122.0 78.3

90 120.7 115.7 125.5 109.3 133.3 97.2 116.3 112.1 120.8 106.1 128.2 94.3 111.8 108.5 116.0 102.7 123.1 91.3

75 112.7 95.3 123.6 75.8 132.9 40.6 108.3 92.4 118.7 73.3 127.6 38.7 103.8 89.3 113.7 70.8 122.2 36.8

80 116.4 106.5 124.0 93.5 134.4 69.5 112.0 103.2 119.2 90.7 129.1 67.1 107.5 99.8 114.2 87.7 123.8 64.7

85 121.1 115.3 126.6 106.3 136.0 89.3 116.6 111.8 121.8 103.1 130.7 86.5 112.0 108.2 116.8 99.8 125.3 83.7

90 126.2 122.8 130.5 116.1 137.6 103.5 121.6 119.0 125.5 112.6 132.3 100.4 116.9 115.2 120.5 109.1 126.9 97.3

75 116.3 100.4 126.2 80.2 134.8 44.4 111.7 97.2 121.0 77.5 129.3 42.3 107.0 94.0 115.8 74.8 123.7 40.1

80 120.5 112.1 127.3 98.6 136.9 74.0 115.9 108.6 122.2 95.5 131.4 71.4 111.2 105.0 117.1 92.4 125.8 68.8

85 125.6 121.4 130.4 111.9 139.0 94.4 120.9 117.6 125.4 108.5 133.5 91.5 116.1 113.8 120.2 105.1 127.9 88.4

90 131.0 129.2 134.7 122.1 141.1 109.2 126.2 125.3 129.5 118.5 135.6 105.9 121.3 121.2 124.3 114.8 130.0 102.5

75 119.1 104.7 128.0 84.0 140.3 47.5 114.3 101.4 122.7 81.1 134.5 45.2 109.4 97.9 117.3 78.2 128.6 42.8

80 123.9 117.0 129.8 103.0 140.8 77.8 119.0 113.3 124.5 99.7 135.0 75.1 114.1 109.6 119.2 96.4 129.2 72.2

85 129.3 126.7 133.5 116.8 141.3 98.9 124.4 122.8 128.2 113.3 135.6 95.7 119.4 118.8 122.8 109.6 129.8 92.5

90 135.1 135.0 138.1 127.6 143.9 114.2 130.0 130.0 132.8 123.7 138.2 110.7 124.9 124.9 127.4 119.8 132.4 107.1

75 121.2 108.4 129.2 87.1 140.6 49.9 116.2 104.9 123.6 84.0 134.5 47.4 111.1 101.2 118.0 80.9 129.0 44.9

80 126.5 121.2 131.6 106.7 141.7 81.0 121.5 117.4 126.2 103.3 135.7 78.0 116.4 113.4 120.6 99.7 129.6 75.0

85 132.4 131.4 135.8 121.1 142.8 102.7 127.3 127.3 130.4 117.3 136.9 99.3 122.1 122.1 124.8 113.5 130.9 95.9

90 138.4 138.4 140.9 132.3 146.0 118.5 133.2 133.2 135.4 128.3 140.1 114.8 127.9 127.9 129.7 124.1 134.1 111.1

75 122.6 111.5 129.6 89.5 141.0 51.7 117.4 107.7 123.9 86.3 134.8 49.0 112.1 103.9 118.0 82.9 130.0 46.2

5500

80 128.4 124.8 132.7 109.8 141.9 83.5 123.2 120.7 127.1 106.1 136.2 80.3 117.9 116.6 121.3 102.4 130.7 77.1

85 134.7 134.7 137.5 124.7 143.7 105.8 129.4 129.4 131.8 120.7 137.6 102.2 124.0 124.0 126.0 116.7 131.4 98.6

90 141.1 141.1 143.0 136.4 147.4 122.2 135.7 135.7 137.2 132.1 141.3 118.3 130.1 130.1 131.4 127.8 135.1 114.3

75 123.3 113.8 130.0 91.3 142.0 52.7 117.9 109.9 125.0 87.8 135.3 49.9 112.3 105.8 119.0 84.3 130.2 46.9

6000

80 129.7 127.7 133.2 112.2 143.0 85.3 124.2 123.4 127.3 108.3 137.0 81.9 118.7 118.7 124.0 104.4 131.6 78.5

85 136.4 136.4 138.4 127.6 143.8 108.2 130.8 130.8 132.5 123.5 139.0 104.5 125.2 125.2 126.5 119.2 133.0 100.6

90 143.0 143.0 144.3 139.8 148.1 125.2 137.4 137.4 138.4 135.3 141.8 121.1 131.6 131.6 132.3 130.8 135.3 116.9

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

RT-PRC028AC-EN 51

Performance Data

Table 27. Gross cooling capacities 12½ tons three phase dehumidification (hot gas reheat) option high efficiency

T/YHD150G3,4,W (Digit 22 = B)

Air

Flow cfm

2500 (a)

3250

(a)

4000

4500

5000

5500

6000

Ent

DB

(°F)

85

Ambient Temperature

95 105

61 67 73 61

Entering Wet Bulb

67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 119.6 86.9 135.0 60.0 154.5 54.1 112.4 82.4 127.1 56.5 145.9 51.1 104.7 77.6 118.6 52.7 136.8 47.9

80 121.1 102.6 134.0 82.6 151.3 52.9 114.0 97.4 126.2 78.4 142.8 50.0 106.3 92.0 117.9 74.0 133.7 46.8

85 123.7 114.7 134.3 101.6 149.2 75.1 116.7 108.9 126.6 96.8 140.8 71.4 109.2 102.8 118.4 91.7 131.9 67.4

90 127.5 123.2 135.8 116.9 148.3 97.4 120.6 116.7 128.2 111.5 140.0 93.0 113.2 110.0 120.1 105.8 131.2 88.4

75 129.1 96.7 143.2 68.4 161.5 56.5 121.5 91.9 134.9 64.6 152.5 53.4 113.3 86.8 126.0 60.5 142.9 50.0

80 131.4 113.6 143.2 92.1 159.1 57.4 123.9 108.1 134.9 87.7 150.2 54.0 115.8 102.4 126.1 83.0 140.7 50.4

85 134.9 126.9 144.3 112.3 157.9 84.4 127.5 120.8 136.2 107.2 149.1 80.4 119.5 114.4 127.5 101.9 139.7 76.2

90 139.7 136.5 146.7 128.8 157.9 107.9 132.3 129.8 138.6 123.1 149.2 103.2 124.4 122.8 130.0 117.2 139.9 98.3

75 137.1 105.6 149.9 75.8 167.0 58.4 129.0 100.4 141.1 71.7 157.4 55.1 120.3 95.0 131.7 67.4 147.4 51.6

80 140.2 123.6 150.7 100.7 165.4 64.5 132.2 117.8 142.0 96.0 156.0 60.9 123.7 111.8 132.7 91.0 146.1 57.0

85 144.6 138.0 152.7 122.0 165.1 92.7 136.7 131.6 144.1 116.7 155.8 88.5 128.3 124.9 135.0 111.1 145.9 83.9

90 150.2 148.8 156.0 139.7 166.0 117.4 142.4 141.8 147.5 133.7 156.8 112.4 134.0 134.0 138.4 127.5 147.0 107.2

75 141.5 110.9 153.5 80.1 169.7 59.4 133.1 105.5 144.3 75.9 159.9 56.0 124.1 100.0 134.7 71.3 149.5 52.3

80 145.2 129.7 154.9 105.8 168.8 68.7 136.9 123.7 145.8 100.9 159.0 64.9 128.1 117.5 136.3 95.8 148.8 60.8

85 150.2 144.9 157.5 127.9 169.0 97.7 142.0 138.3 148.6 122.4 159.4 93.2 133.2 131.4 139.1 116.6 149.2 88.5

90 156.3 156.3 161.3 146.4 170.5 123.1 148.2 148.2 152.5 140.3 161.0 118.0 139.6 139.6 143.1 133.8 150.9 112.6

75 145.2 115.7 156.3 84.0 171.8 60.1 136.5 110.2 146.9 79.6 161.6 56.6 127.2 104.5 137.0 74.9 151.0 52.8

80 149.5 135.3 158.3 110.5 171.4 72.5 140.9 129.2 149.0 105.4 161.4 68.4 131.7 122.8 139.1 100.1 150.8 64.2

85 155.0 151.3 161.5 133.4 172.2 102.3 146.5 144.5 152.3 127.7 162.3 97.6 137.5 137.5 142.5 121.7 151.8 92.7

90 161.8 161.8 165.9 152.7 174.3 128.4 153.4 153.4 156.8 146.3 164.4 123.1 144.4 144.4 147.1 139.7 154.1 117.6

75 148.2 120.1 158.5 87.5 173.1 60.6 139.2 114.4 148.8 82.9 162.7 56.9 129.6 108.5 138.5 78.0 151.7 53.1

80 153.1 140.5 161.1 114.8 173.3 75.8 144.2 134.2 151.4 109.5 163.0 71.6 134.7 127.6 141.3 104.0 152.1 67.1

85 159.2 157.2 164.8 138.4 174.7 106.3 150.4 150.3 155.3 132.5 164.5 101.5 141.0 141.0 145.3 126.3 153.7 96.4

90 166.5 166.5 169.8 158.5 177.3 133.3 157.8 157.8 160.4 151.9 167.2 127.8 148.6 148.6 150.4 145.1 156.6 122.0

75 150.5 124.1 160.0 90.5 173.7 60.8 141.2 118.2 150.0 85.7 163.0 57.1 131.3 112.1 139.4 80.6 151.7 53.1

80 156.0 145.2 163.1 118.6 174.5 78.6 146.8 138.7 153.2 113.1 163.9 74.2 137.0 131.9 142.7 107.4 152.7 69.6

85 162.7 162.7 167.5 143.0 176.5 110.0 153.6 153.6 157.6 136.9 166.0 104.9 143.9 143.9 147.3 130.5 154.9 99.6

90 170.6 170.6 173.0 163.8 179.7 137.7 161.5 161.5 163.3 157.1 169.3 132.0 152.0 152.0 153.0 150.1 158.3 126.1

52 RT-PRC028AC-EN

Performance Data

Table 27. Gross cooling capacities 12½ tons three phase dehumidification (hot gas reheat) option high efficiency

T/YHD150G3,4,W (Digit 22 = B)

Air

Flow cfm

Ent

DB

(°F)

115

Ambient Temperature

120 125

61 67 73 61

Entering Wet Bulb

67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 96.4 72.5 109.7 48.7 127.1 44.5 92.1 69.8 105.0 46.6 122.1 42.7 87.7 67.2 100.2 44.4 116.9 40.9

2500

3250

(a)

(a)

4000

4500

80 98.2 86.3 109.0 69.4 124.1 43.5 93.9 83.3 104.4 66.9 119.2 41.7 89.5 80.3 99.6 64.4 114.0 39.9

85 101.1 96.4 109.6 86.4 122.4 63.2 96.9 93.2 105.0 83.7 117.5 60.9 92.5 89.8 100.3 80.9 112.4 58.7

90 105.3 103.0 111.4 99.9 121.8 83.5 101.1 99.4 106.9 96.9 116.9 81.0 96.8 95.8 102.2 93.7 111.9 78.4

75 104.6 81.4 116.5 56.2 132.7 46.5 100.0 78.7 111.6 54.0 127.5 44.6 95.3 75.8 106.6 51.7 122.1 42.7

80 107.2 96.4 116.8 78.1 130.7 46.5 102.7 93.3 111.9 75.5 125.4 44.5 98.0 90.2 106.9 72.9 120.1 42.3

85 111.0 107.7 118.3 96.3 129.8 71.6 106.5 104.3 113.4 93.4 124.6 69.3 101.9 100.9 108.5 90.5 119.3 66.9

90 116.0 115.5 120.9 111.0 130.1 93.2 111.6 111.6 116.2 107.8 125.0 90.5 107.1 107.1 111.3 104.5 119.7 87.8

75 111.1 89.4 121.8 62.8 136.8 47.9 106.3 86.5 116.7 60.4 131.3 46.0 101.4 83.5 111.4 57.9 125.7 44.0

80 114.6 105.5 123.0 85.8 135.6 52.8 109.9 102.3 117.9 83.1 130.1 50.6 105.0 99.0 112.7 80.3 124.6 48.4

85 119.3 118.0 125.3 105.2 135.6 79.1 114.6 114.5 120.3 102.2 130.2 76.6 109.8 109.8 115.1 99.1 124.7 74.0

90 125.2 125.2 128.8 121.0 136.7 101.8 120.5 120.5 123.8 117.7 131.4 99.0 115.8 115.8 118.7 114.3 125.9 96.1

75 114.6 94.1 124.5 66.6 138.6 48.5 109.7 91.1 119.2 64.1 133.0 46.5 104.6 88.1 113.8 61.5 127.2 44.5

80 118.7 111.0 126.2 90.4 138.0 56.4 113.8 107.7 121.0 87.6 132.4 54.2 108.8 104.3 115.6 84.7 126.7 51.8

85 123.9 123.9 129.1 110.6 138.6 83.5 119.1 119.1 123.9 107.4 133.0 80.9 114.1 114.1 118.6 104.3 127.3 78.3

90 130.4 130.4 133.2 127.1 140.3 107.0 125.6 125.6 128.1 123.7 134.8 104.1 120.7 120.7 122.8 120.2 129.2 101.1

75 117.4 98.4 126.5 69.9 139.8 48.9 112.3 95.3 121.0 67.4 134.0 46.9 107.1 92.2 115.4 64.7 128.0 44.8

5000

5500

80 122.1 116.1 128.8 94.5 139.7 59.6 117.0 112.7 123.4 91.6 134.0 57.2 111.8 109.2 117.8 88.6 128.1 54.8

85 127.9 127.9 132.2 115.5 140.8 87.5 122.9 122.9 126.9 112.3 135.1 84.8 117.8 117.8 121.4 109.0 129.3 82.0

90 134.9 134.9 136.9 132.8 143.2 111.7 130.0 130.0 131.6 129.3 137.5 108.7 125.0 125.0 126.2 125.7 131.8 105.7

75 119.5 102.3 127.7 72.8 140.2 49.1 114.3 99.1 122.1 70.2 134.2 47.0 108.9 95.8 116.4 67.4 128.2 44.9

80 124.7 120.7 130.6 98.2 140.7 62.3 119.5 117.2 125.0 95.2 134.8 59.9 114.2 113.6 119.4 92.1 128.8 57.4

85 131.1 131.1 134.7 119.9 142.4 91.0 126.0 126.0 129.2 116.6 136.6 88.2 120.7 120.7 123.5 113.2 130.6 85.4

90 138.5 138.5 139.9 138.1 145.4 116.0 133.1 133.1 134.5 134.4 139.6 112.9 128.9 128.9 128.9 128.9 133.6 109.8

75 120.9 105.7 128.3 75.3 139.9 49.0 115.5 102.4 122.5 72.5 133.8 46.8 110.0 99.0 116.7 69.7 127.6 44.7

6000

80 126.7 124.9 131.7 101.4 141.0 64.6 121.4 121.3 126.0 98.3 135.0 62.1 115.9 115.9 120.2 95.2 128.8 59.5

85 133.7 133.7 136.4 123.9 143.3 94.1 128.4 128.4 130.7 120.5 137.3 91.2 123.0 123.0 125.0 117.1 131.2 88.2

90 142.2 142.2 142.2 142.2 146.8 119.9 136.6 136.6 136.6 136.6 140.9 116.7 130.9 130.9 130.9 130.9 134.8 113.4

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

(a)For 2500 and 3250 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Dehumidification (Hot Gas Reheat) with Frostat and Crankcage heaters are required on applications below 320 cfm/ton.

- Multi-speed or single zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

RT-PRC028AC-EN 53

Performance Data

Table 28. Gross cooling capacities 15 tons three phase high efficiency T/YH*180G3,4,W (stage 1)

Air

Flow cfm

Ent

DB

(°F)

Ambient Temperature

85 95

Entering Wet Bulb

61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

2400

3000

3600

4200

4800

85

90

75

80

85

90

75

80

85

90

75

80

85

90

75

80

85

90

75

80

54.8 51.5 59.2 40.6 65.3 18.6 51.8 49.1 56.0 38.5 60.9 17.0

57.4 56.8 60.0 50.8 65.5 37.2 54.3 54.2 56.8 48.5 62.1 35.2

60.3 60.3 61.9 57.4 65.5 48.8 57.1 57.1 58.6 54.8 62.1 46.6

63.3 63.3 64.3 61.8 66.8 56.5 60.1 60.1 61.0 59.1 63.3 54.1

56.6 54.6 60.5 44.0 66.3 22.4 53.4 52.0 57.1 41.7 61.6 20.5

59.5 59.5 61.7 54.3 66.7 40.9 56.2 56.2 58.2 51.8 63.1 38.7

62.6 62.6 63.8 60.9 67.1 52.6 59.3 59.3 60.4 58.2 63.4 50.2

65.7 65.7 66.4 65.5 68.6 60.4 62.3 62.3 62.9 62.6 64.9 57.7

58.1 57.2 61.5 46.8 66.9 25.5 54.7 54.3 57.9 44.3 62.0 23.4

61.2 61.2 63.0 57.2 67.5 44.0 57.8 57.8 59.4 54.4 63.8 41.6

64.5 64.5 65.4 63.9 68.2 55.8 61.0 61.0 61.8 60.9 64.4 53.1

67.9 67.9 68.3 68.3 70.0 63.7 64.3 64.3 64.6 64.6 66.2 60.7

59.3 59.1 62.2 49.1 67.0 28.1 55.7 55.7 58.4 46.3 62.1 25.7

62.6 62.6 64.0 59.5 68.1 46.6 59.0 59.0 60.2 56.4 64.1 43.9

66.2 66.2 66.7 66.3 69.1 58.4 62.5 62.5 62.9 62.9 65.1 55.5

69.7 69.7 69.7 69.7 71.2 66.3 64.6 64.6 65.9 65.9 67.2 63.2

60.1 60.1 62.5 50.7 67.1 30.0 56.4 56.4 58.6 47.7 62.7 27.4

63.7 63.7 64.7 61.1 68.3 48.5 59.9 59.9 60.7 57.9 64.1 45.6

67.5 67.5 67.6 67.6 69.6 60.4 63.6 63.6 63.6 63.6 65.5 57.3

69.8 69.8 70.9 70.9 72.0 68.5 65.9 65.9 66.8 66.8 67.8 65.1

5250

75

80

85

90

60.5 60.5 62.5 51.6 67.2 31.1 56.6 56.6 58.8 48.4 63.0 28.4

64.3 64.3 65.0 62.0 68.5 49.6 60.4 60.4 60.9 58.6 64.1 46.5

67.8 67.8 68.1 68.1 69.8 61.6 63.8 63.8 64.0 64.0 65.5 58.2

70.7 70.7 71.5 71.5 72.4 69.6 66.7 66.7 67.4 67.4 68.0 66.1

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

54 RT-PRC028AC-EN

Performance Data

Table 29. Gross cooling capacities 15 tons three phase high efficiency T/YH*180G3,4,W (stage 2)

Air

Flow cfm (a)

Ambient Temperature

85 95

Ent Entering Wet Bulb

DB 61 67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

2400

3000

3600

4200

4800

75 102.0 81.9 111.7 65.6 123.0 36.1 96.8 78.4 105.8 62.6 116.0 33.6

80 104.0 90.7 113.0 79.9 123.8 59.7 98.9 86.9 107.3 76.5 117.7 56.7

85 107.1 97.4 114.3 89.8 124.6 75.5 102.0 93.4 108.8 86.1 118.5 72.1

90 111.0 102.8 117.0 97.1 125.4 86.5 105.8 98.6 111.5 93.2 119.3 82.9

75 107.2 88.8 117.9 71.7 126.6 41.1 101.7 85.0 111.7 68.3 120.0 38.3

80 109.8 98.2 118.0 86.6 128.0 65.6 104.4 94.1 112.0 82.9 121.5 62.3

85 113.4 105.4 120.0 97.2 129.4 82.2 108.0 101.1 114.1 93.2 123.0 78.5

90 117.8 111.3 123.2 105.1 130.8 93.9 112.3 106.7 117.3 100.8 124.5 89.9

75 111.5 94.8 121.2 76.7 133.1 45.2 105.7 90.6 114.7 73.0 125.9 42.1

80 114.7 104.8 122.0 92.5 133.2 70.6 109.0 100.4 115.7 88.4 126.2 67.0

85 118.9 112.5 124.7 103.7 133.3 87.9 113.2 107.9 118.5 99.3 126.5 84.0

90 123.7 118.9 128.4 112.1 135.3 100.3 117.8 114.0 122.2 107.5 128.7 96.0

75 114.9 99.8 123.6 80.9 134.5 48.4 108.8 95.3 116.8 76.9 127.0 44.9

80 118.8 110.4 125.2 97.4 135.4 74.7 112.7 105.7 118.6 93.0 128.1 70.7

85 123.5 118.7 128.5 109.2 136.3 92.8 117.4 113.7 122.0 104.6 129.2 88.5

90 128.6 125.5 132.8 118.2 139.0 105.7 122.5 120.3 126.3 113.2 132.0 101.1

75 117.4 103.9 125.1 84.1 135.0 50.6 111.0 99.1 117.9 79.7 128.0 46.8

80 121.9 115.2 127.5 101.4 136.7 77.8 115.6 110.1 120.6 96.7 129.1 73.5

85 127.1 123.9 131.5 113.9 138.4 96.7 120.8 118.6 124.6 108.8 131.0 92.0

90 132.7 131.1 136.3 123.3 141.8 110.3 126.3 125.6 129.4 118.1 134.5 105.3

5250

75 118.7 106.3 125.6 85.9 135.5 51.7 112.0 101.3 118.2 81.3 129.0 47.6

80 123.7 118.1 128.7 103.7 137.1 79.5 117.1 112.7 121.5 98.8 129.3 75.0

85 129.3 127.3 133.1 116.7 139.4 99.0 122.7 121.7 126.0 111.4 131.8 94.1

90 135.2 134.8 138.3 126.6 143.3 113.0 128.5 128.5 131.2 121.1 135.7 107.9

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

(a)For 2400, 3000, 3600, and 4200 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and

YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

RT-PRC028AC-EN 55

Performance Data

Table 30. Gross cooling capacities 15 tons three phase high efficiency T/YH*180G3,4,W (full load)

Air

Flow cfm (a)

3000

3600

4200

4800

5400

6000

6600

7200

Ent

DB

(°F)

85

Ambient Temperature

95 105

Entering Wet Bulb

61 67 73 61 67 73 61 67 73

MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 149.8 116.6 163.9 91.6 180.9 48.7 142.5 112.1 155.7 88.3 172.0 46.6 134.3 106.9 146.7 84.2 162.1 43.8

80 153.0 130.6 165.9 113.6 181.8 83.7 145.7 125.4 157.8 109.4 172.9 80.6 137.5 119.5 148.7 104.5 163.1 76.8

85 157.9 141.6 167.9 129.4 182.8 108.0 150.5 135.8 159.8 124.5 173.8 104.0 142.2 129.4 150.8 118.9 164.0 99.3

90 163.8 150.7 171.9 141.5 183.7 125.5 156.2 144.5 163.7 136.0 174.7 120.8 147.7 137.7 154.6 129.9 164.9 115.5

75 156.6 125.2 169.8 99.5 186.1 55.7 148.9 120.2 161.3 95.7 176.7 53.2 140.3 114.6 151.8 91.2 166.5 50.1

80 160.4 139.8 172.4 122.2 187.5 91.6 152.7 134.2 163.9 117.5 178.2 88.1 144.1 127.9 154.4 112.2 168.0 83.9

85 165.7 151.3 175.0 138.6 189.0 116.6 157.9 145.1 166.5 133.2 179.7 112.2 149.2 138.3 157.0 127.2 169.4 107.1

90 172.0 160.9 179.5 151.2 190.5 134.7 163.9 154.2 170.8 145.3 181.2 129.6 155.0 147.0 161.3 138.7 170.9 123.8

75 162.6 133.0 177.9 106.6 190.4 62.0 154.5 127.6 168.8 102.4 180.7 59.1 145.5 121.6 158.9 97.5 170.0 55.5

80 166.9 148.2 178.1 129.9 192.5 98.7 158.8 142.1 169.2 124.9 182.7 94.8 149.8 135.4 159.4 119.1 172.1 90.1

85 172.7 160.2 181.3 147.0 194.5 124.4 164.5 153.6 172.3 141.2 184.8 119.5 155.4 146.3 162.5 134.8 174.1 114.1

90 179.3 170.2 186.2 160.1 196.6 143.1 170.9 163.1 177.2 153.8 186.8 137.6 161.6 155.5 167.2 146.8 176.2 131.4

75 167.9 139.9 182.2 112.8 194.0 67.4 159.3 134.2 172.7 108.2 183.8 64.1 149.9 127.7 162.3 102.9 172.8 60.2

80 172.7 155.7 183.1 136.9 196.6 105.0 164.2 149.3 173.7 131.4 186.5 100.6 154.8 142.2 163.5 125.3 175.4 95.6

85 179.0 168.2 186.8 154.5 199.2 131.4 170.3 161.2 177.5 148.4 189.1 126.1 160.8 153.6 167.2 141.5 178.0 120.2

90 185.9 178.7 192.2 168.2 201.9 150.7 177.1 171.3 182.7 161.4 191.7 144.7 167.3 163.2 172.4 154.0 180.7 138.2

75 172.3 146.1 185.6 118.3 202.7 72.1 163.4 139.9 175.7 113.3 191.8 68.4 153.6 133.1 164.9 107.6 180.1 64.0

80 177.8 162.5 187.3 143.1 202.9 110.5 168.8 155.6 177.5 137.2 192.2 105.7 159.0 148.1 166.9 130.6 180.6 100.3

85 184.4 175.5 191.6 161.3 203.2 137.6 175.4 168.1 181.8 154.7 192.6 131.9 165.5 160.0 171.2 147.5 181.2 125.6

90 191.7 186.4 197.4 175.5 206.4 157.5 182.5 178.6 187.5 168.3 195.8 151.1 172.3 170.1 176.8 160.5 184.4 144.1

75 176.0 151.5 188.3 123.0 204.4 76.0 166.7 144.9 178.0 117.5 193.1 71.9 156.5 137.6 166.8 111.4 181.0 67.1

80 182.0 168.5 190.7 148.5 205.4 115.2 172.7 161.2 180.5 142.2 194.3 110.0 162.5 153.3 169.5 135.2 182.3 104.1

85 189.1 182.0 195.5 167.3 206.3 143.0 179.7 174.2 185.4 160.3 195.4 136.9 169.3 165.7 174.3 152.6 183.5 130.2

90 196.8 193.3 201.8 181.9 210.1 163.5 187.1 185.1 191.5 174.4 199.1 156.7 176.6 176.2 180.4 166.2 187.3 149.3

75 178.9 156.1 190.2 126.9 205.4 79.1 169.2 149.1 179.5 121.0 193.7 74.5 158.6 141.4 167.9 114.5 181.2 69.3

80 185.5 173.7 193.3 153.1 207.0 119.1 175.7 166.0 182.7 146.3 195.5 113.5 165.1 157.6 171.3 139.0 183.1 107.2

85 193.0 187.7 198.7 172.5 208.7 147.6 183.2 179.5 188.2 165.1 197.3 141.1 172.4 170.6 176.7 157.0 185.1 134.0

90 201.0 199.5 205.5 187.6 213.0 168.7 190.9 190.8 194.8 179.7 201.7 161.5 180.0 180.0 183.2 171.1 189.4 153.7

75 181.0 159.9 191.4 130.0 205.6 81.4 170.9 152.5 180.3 123.7 194.3 76.4 159.9 144.4 168.3 116.8 181.3 70.8

80 188.2 178.1 195.2 156.8 207.9 122.2 178.0 170.0 184.2 149.7 196.0 116.2 167.0 161.2 172.3 141.9 183.2 109.5

85 196.1 192.6 201.1 176.9 210.3 151.4 185.9 184.0 190.2 169.0 198.5 144.5 174.7 174.6 178.3 160.6 185.9 137.0

90 204.5 204.5 208.3 192.5 215.2 173.1 194.0 194.0 197.2 184.2 203.4 165.5 182.7 182.7 185.3 175.1 190.8 157.3

56 RT-PRC028AC-EN

Performance Data

Table 30. Gross cooling capacities 15 tons three phase high efficiency T/YH*180G3,4,W (full load)

Air

Flow cfm

(a)

3000

115

Ambient Temperature

120 125

Ent

DB 61 67 73 61

Entering Wet Bulb

67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 125.3 101.0 136.8 79.5 151.4 40.4 120.4 97.8 131.5 76.9 145.7 38.5 115.3 94.5 126.0 74.1 139.8 36.4

80 128.5 113.0 138.8 98.9 152.4 72.3 123.6 109.5 133.6 95.9 146.7 69.9 118.5 105.8 128.1 92.7 140.8 67.2

85 133.0 122.3 140.9 112.6 153.3 94.0 128.1 118.5 135.6 109.3 147.6 91.1 122.9 114.6 130.1 105.7 141.7 88.1

90 138.3 130.2 144.6 123.1 154.2 109.5 133.3 126.2 139.2 119.4 148.5 106.2 128.0 122.0 133.7 115.6 142.6 102.8

75 130.9 108.3 141.5 86.1 155.4 46.3 125.8 105.0 138.6 83.3 149.5 44.1 120.5 101.4 132.9 80.4 143.4 41.8

3600

4200

4800

5400

6000

80 134.6 120.9 144.1 106.2 156.8 79.0 129.5 117.2 138.7 103.0 151.0 76.3 124.3 113.3 133.0 99.6 144.9 73.5

85 139.6 130.8 146.7 120.6 158.3 101.4 134.5 126.8 141.3 117.0 152.5 98.3 129.1 122.6 135.6 113.3 146.4 95.0

90 145.2 139.0 150.9 131.5 159.8 117.4 140.0 134.8 145.3 127.7 153.9 113.9 134.5 130.5 139.6 123.6 147.9 110.3

75 135.7 114.9 148.0 92.0 158.5 51.3 130.4 111.3 142.2 88.9 152.4 48.9 124.9 107.5 136.3 85.8 146.1 46.4

80 140.0 128.0 148.7 112.7 160.6 84.8 134.7 124.1 143.0 109.3 154.5 82.0 129.2 120.0 137.1 105.7 148.2 78.9

85 145.4 138.4 151.8 127.7 162.6 107.9 140.1 134.2 146.1 123.9 156.5 104.6 134.5 129.8 140.2 120.0 150.2 101.1

90 151.4 147.1 156.4 139.2 164.7 124.6 145.9 142.7 150.7 135.1 158.6 120.9 140.3 138.1 144.7 130.9 152.3 117.1

75 139.7 120.6 151.0 97.0 160.9 55.5 134.2 116.8 145.1 93.8 159.7 53.0 128.5 112.9 138.9 90.4 153.1 50.2

80 144.6 134.4 152.4 118.5 163.5 89.9 139.1 130.2 146.5 114.8 159.8 86.8 133.4 125.9 140.4 111.0 153.2 83.5

85 150.4 145.3 156.1 134.0 166.1 113.7 144.9 140.8 150.2 130.0 159.8 110.2 139.1 136.3 144.1 125.9 153.3 106.5

90 156.7 154.4 161.2 146.0 168.7 130.9 151.1 149.8 155.2 141.7 162.5 127.0 145.2 145.0 149.1 137.3 156.0 123.0

75 142.9 125.6 153.3 101.2 167.5 59.0 137.3 121.6 147.1 97.8 160.8 56.2 131.4 117.4 140.7 94.2 154.0 53.2

80 148.4 139.9 155.4 123.4 168.2 94.2 142.7 135.6 149.3 119.6 161.6 90.9 136.8 131.1 143.0 115.6 154.8 87.4

85 154.7 151.3 159.7 139.6 168.8 118.6 148.9 146.7 153.6 135.4 162.4 114.9 143.0 141.9 147.3 131.0 155.6 111.0

90 161.3 160.9 165.1 152.1 172.0 136.5 155.5 155.5 159.0 147.6 165.6 132.4 149.4 149.4 152.6 142.9 158.8 128.2

75 145.4 129.7 154.8 104.7 168.0 61.6 139.5 125.5 148.4 101.0 161.2 58.6 133.4 121.1 141.8 97.3 154.1 55.5

80 151.4 144.7 157.6 127.6 169.4 97.6 145.5 140.1 151.3 123.5 162.6 94.1 139.4 135.4 144.8 119.3 155.6 90.5

85 158.1 156.6 162.4 144.3 170.8 122.8 152.2 151.7 156.1 139.9 164.1 118.9 146.0 146.0 149.6 135.4 157.2 114.8

90 165.1 165.1 168.4 157.3 174.6 141.2 159.1 159.1 162.0 152.6 167.9 137.0 152.8 152.8 155.4 147.8 161.0 132.5

75 147.1 133.1 155.5 107.3 168.5 63.4 141.0 128.7 148.9 103.5 161.5 60.3 134.7 124.1 142.1 99.5 154.2 56.9

6600

80 153.6 148.6 159.0 130.9 169.9 100.3 147.6 143.9 152.5 126.7 162.9 96.6 141.3 138.9 145.8 122.2 155.7 92.7

85 160.8 160.8 164.4 148.3 172.0 126.2 154.7 154.7 157.9 143.7 165.1 122.0 148.3 148.3 151.2 138.9 158.0 117.7

90 168.2 168.2 170.8 161.8 176.3 145.2 161.9 161.9 164.2 156.9 169.4 140.7 155.5 155.5 157.5 151.8 162.3 136.1

75 148.0 135.6 156.1 109.2 169.1 64.5 141.7 131.0 149.4 105.1 161.8 61.1 135.2 126.2 142.4 100.9 154.4 57.5

7200

80 155.1 151.8 159.6 133.5 170.3 102.2 148.8 146.8 152.9 129.0 163.2 98.3 142.3 141.7 146.0 124.4 155.8 94.2

85 162.7 162.7 165.6 151.4 172.4 128.8 156.4 156.4 158.9 146.6 165.3 124.4 149.8 149.8 152.0 141.6 158.7 119.9

90 170.4 170.4 172.4 165.4 177.3 148.4 164.0 164.0 165.7 160.4 170.2 143.7 157.3 157.3 158.7 155.1 162.8 138.8

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

(a)For 3000, 3600, and 4200 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Dehumidification (Hot Gas Reheat) with Frostat and Crankcage heaters are required on applications below 320 cfm/ton.

- Multi-speed or single zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

RT-PRC028AC-EN 57

Performance Data

Table 31. Gross cooling capacities 15 tons three phase dehumidification (hot gas reheat) option high efficiency

T/YHD180G3,4,W (Digit 22 = B)

Air

Flow cfm (a)

3000

3900

4800

5400

6000

6600

7200

85

61

Ambient Temperature

95

Entering Wet Bulb

67 73

105

Ent

DB 61 67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 149.8 108.9 167.7 71.3 190.8 66.8 141.5 104.7 158.6 68.7 180.8 63.3 132.6 99.7 148.8 65.2 170.1 59.5

80 151.5 129.2 166.7 101.1 187.0 65.5 143.4 124.3 157.7 97.7 177.1 62.0 134.7 118.5 148.1 93.4 166.7 58.3

85 154.6 144.8 167.0 126.0 184.5 89.1 146.7 139.2 158.2 121.9 174.9 86.5 138.1 132.6 148.8 116.9 164.6 83.0

90 159.1 155.7 168.7 146.3 183.5 118.7 151.3 149.2 160.1 141.4 174.0 115.3 143.0 141.9 150.9 135.6 163.9 111.1

75 160.4 120.9 176.9 82.0 198.6 69.5 151.6 116.3 167.3 79.0 188.1 65.8 142.3 110.9 157.1 75.1 177.0 61.9

80 163.1 142.6 176.9 113.1 195.8 68.5 154.6 137.2 167.5 109.3 185.5 64.9 145.4 131.0 157.4 104.6 174.5 61.1

85 167.2 159.5 178.2 139.4 194.4 101.1 158.8 153.4 169.0 134.8 184.2 98.1 149.8 146.4 159.1 129.4 173.5 94.2

90 172.7 171.6 180.9 160.9 194.3 132.0 164.5 164.5 171.9 155.6 184.3 128.2 155.7 155.7 162.2 149.4 173.8 123.5

75 169.3 131.7 184.4 91.5 204.6 71.6 160.0 126.7 174.3 88.0 193.7 67.8 150.2 120.8 163.6 83.7 182.1 63.7

80 173.0 154.7 185.4 123.8 202.8 74.8 164.0 148.9 175.5 119.6 192.1 72.1 154.3 142.3 164.9 114.5 180.7 68.6

85 178.1 172.9 187.7 151.4 202.4 111.8 169.3 166.4 178.0 146.5 191.8 108.4 159.8 159.0 167.7 140.6 180.6 104.0

90 184.6 184.6 191.4 174.3 203.4 144.0 176.0 176.0 181.9 168.5 192.9 139.8 166.7 166.7 171.7 161.9 181.9 134.7

75 174.2 138.2 188.4 97.1 207.7 72.7 164.7 132.9 178.0 93.4 196.4 68.7 154.6 126.8 167.0 88.8 184.5 64.6

80 178.6 162.0 190.0 130.3 206.6 80.4 169.3 156.0 179.8 125.8 195.5 77.4 159.3 149.1 169.0 120.4 183.8 73.6

85 184.4 181.1 193.1 158.8 206.8 118.2 175.3 174.3 183.0 153.5 195.9 114.5 165.5 165.5 172.4 147.4 184.4 109.9

90 191.6 191.6 197.4 182.5 208.4 151.4 182.6 182.6 187.6 176.5 197.7 146.9 173.0 173.0 177.2 169.5 186.4 141.5

75 178.4 144.1 191.6 102.1 210.0 73.5 168.5 138.6 180.9 98.1 198.4 69.4 158.1 132.1 169.6 93.2 186.2 65.2

80 183.5 168.8 193.9 136.2 209.5 85.4 173.8 162.5 183.4 131.4 198.1 82.2 163.6 155.3 172.3 125.8 186.1 78.1

85 189.9 188.8 197.6 165.5 210.4 124.1 180.5 180.5 187.3 160.0 199.2 120.1 170.4 170.4 176.4 153.6 187.4 115.3

90 197.8 197.8 202.7 190.1 212.7 158.1 188.5 188.5 192.6 183.8 201.7 153.4 178.6 178.6 181.8 176.6 190.1 147.7

75 181.8 149.5 194.1 106.6 211.5 74.0 171.6 143.7 183.0 102.3 199.6 69.9 160.9 137.0 171.4 97.1 187.1 65.5

80 187.5 175.0 197.1 141.5 211.7 89.9 177.6 168.5 186.2 136.5 200.0 86.4 167.0 161.0 174.8 130.6 187.7 82.0

85 194.7 194.7 201.4 171.8 213.3 129.5 184.9 184.9 190.8 166.0 201.8 125.2 174.5 174.5 179.5 159.2 189.7 120.0

90 203.2 203.2 207.2 197.2 216.3 164.3 193.6 193.6 196.7 190.6 204.9 159.3 183.4 183.4 185.6 183.2 193.0 153.3

75 184.4 154.3 195.7 110.5 212.2 74.3 173.9 148.2 184.4 105.9 200.0 70.0 162.9 141.2 172.5 100.5 187.2 65.5

80 190.8 180.7 199.4 146.3 213.1 93.8 180.6 173.9 188.3 141.0 201.1 90.0 169.7 166.1 176.5 134.8 188.5 85.3

85 198.7 198.7 204.5 177.4 215.4 134.2 188.6 188.6 193.5 171.3 203.6 129.7 177.9 177.9 181.9 164.3 191.1 124.2

90 207.8 207.8 210.9 203.8 219.0 170.0 198.0 198.0 200.1 196.9 207.4 164.6 188.7 188.7 188.7 188.7 195.1 158.4

58 RT-PRC028AC-EN

Performance Data

Table 31. Gross cooling capacities 15 tons three phase dehumidification (hot gas reheat) option high efficiency

T/YHD180G3,4,W (Digit 22 = B)

Air

Flow

cfm (a)

Ent

DB 61

115

67 73 61

Ambient Temperature

120

Entering Wet Bulb

67 73 61

125

67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

3000

3900

4800

5400

75 123.1 93.8 138.4 60.9 158.9 55.6 118.1 90.5 133.0 58.3 153.0 53.5 112.9 87.0 127.4 55.6 147.0 51.4

80 125.3 111.8 137.9 88.3 155.6 54.5 120.4 108.1 132.6 85.4 149.8 52.4 115.4 104.2 127.1 82.2 143.9 50.4

85 129.0 125.1 138.8 111.0 153.7 78.6 124.2 121.1 133.5 107.7 148.0 76.1 119.2 116.8 128.1 104.1 142.2 73.3

90 134.0 133.7 141.0 128.9 153.1 105.9 129.3 129.2 135.9 125.2 147.6 103.0 124.4 124.4 130.6 121.3 141.8 99.9

75 132.3 104.6 146.2 70.3 165.3 57.8 127.1 101.1 140.6 67.6 159.2 55.7 121.7 97.3 134.7 64.6 152.9 53.5

80 135.6 123.9 146.7 99.0 163.0 57.1 130.5 120.0 141.2 95.9 157.0 54.9 125.2 115.9 135.4 92.6 150.8 52.8

85 140.2 138.5 148.6 123.0 162.1 89.3 135.2 134.2 143.1 119.5 156.2 86.6 130.0 129.7 137.5 115.8 150.1 83.6

90 146.3 146.3 151.9 142.3 162.6 118.0 141.3 141.3 146.5 138.4 156.8 114.8 136.2 136.2 140.9 134.2 150.8 111.5

75 139.8 114.1 152.3 78.5 169.9 59.5 134.3 110.4 146.4 75.5 163.6 57.3 128.7 106.4 140.4 72.4 157.1 55.0

80 144.1 134.7 153.8 108.5 168.7 64.1 138.7 130.6 148.0 105.2 162.4 61.6 133.2 126.3 142.1 101.6 156.0 58.8

85 149.8 149.8 156.7 133.8 168.8 98.8 144.5 144.5 151.0 130.1 162.6 95.9 139.1 139.1 145.1 126.2 156.4 92.7

90 156.8 156.8 161.0 154.4 170.3 128.7 151.6 151.6 155.4 150.3 164.2 125.4 146.3 146.3 149.6 145.9 158.0 121.8

75 143.8 119.7 155.4 83.3 172.0 60.2 138.2 115.9 149.3 80.2 165.6 57.9 132.4 111.8 143.1 76.9 158.9 55.6

80 148.8 141.3 157.6 114.2 171.5 68.9 143.3 137.0 151.6 110.7 165.1 66.2 137.6 132.6 145.5 107.0 158.5 63.3

85 155.1 155.1 161.1 140.3 172.3 104.4 149.7 149.7 155.3 136.5 166.0 101.3 144.1 144.1 149.3 132.4 159.5 98.0

90 162.8 162.8 166.1 161.7 174.4 135.2 157.5 157.5 160.3 157.5 168.2 131.7 152.9 152.0 154.4 153.0 161.9 128.0

6000

6600

75 147.1 124.8 157.7 87.5 173.4 60.7 141.3 120.8 151.5 84.2 166.8 58.4 135.4 116.6 145.1 80.8 160.0 56.0

80 152.7 147.2 160.5 119.2 173.5 73.1 147.0 142.8 154.4 115.6 167.0 70.2 141.2 138.2 148.2 111.8 160.3 67.2

85 159.7 159.7 164.8 146.3 175.0 109.5 154.2 154.2 158.8 142.3 168.5 106.2 148.4 148.4 152.6 138.0 161.9 102.8

90 168.7 168.1 170.4 168.5 177.8 141.1 162.8 162.8 164.5 164.2 171.5 137.5 158.4 158.4 158.4 158.4 165.0 133.7

75 149.5 129.4 159.2 91.1 174.0 60.9 143.6 125.2 152.8 87.7 167.2 58.5 137.6 120.9 146.3 84.1 160.3 56.1

80 155.9 152.6 162.7 123.7 174.8 76.7 150.0 148.1 156.5 120.0 168.1 73.7 144.1 143.4 150.1 116.0 161.2 70.5

85 163.6 163.6 167.7 151.6 176.9 114.0 157.8 157.8 161.5 147.5 170.3 110.6 151.9 151.9 155.2 143.1 163.6 107.0

90 174.0 174.0 174.0 174.0 180.4 146.5 167.9 167.9 167.9 167.9 173.9 142.7 161.7 161.7 161.7 161.7 167.3 138.8

7200

75 151.2 133.3 159.9 94.2 173.8 60.8 145.2 129.0 153.4 90.7 166.9 58.4 138.9 124.6 146.8 86.9 159.8 55.9

80 158.2 157.5 164.2 127.7 175.2 79.7 152.3 152.3 157.8 123.8 168.4 76.6 146.1 146.1 151.2 119.7 161.4 73.3

85 166.6 166.6 169.8 156.5 178.1 117.9 160.7 160.7 163.5 152.2 171.3 114.4 154.7 154.7 157.0 147.7 164.4 110.7

90 176.7 176.7 176.7 176.7 182.3 151.3 170.5 170.5 170.5 170.5 175.6 147.4 164.1 164.1 164.1 164.1 168.8 143.3

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

(a)For 3000 and 3900 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Dehumidification (Hot Gas Reheat) with Frostat and Crankcage heaters are required on applications below 320 cfm/ton.

- Multi-speed or single zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

RT-PRC028AC-EN 59

Performance Data

Table 32. Gross cooling capacities 17½ tons three phase high efficiency T/YH*210G3,4,W (stage 1)

Air

Flow cfm (a)

Ambient Temperature

85 95

Ent Entering Wet Bulb

DB 61 67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

2800

3500

4200

4900

5600

85

90

75

80

85

90

75

80

85

90

75

80

85

90

75

80

85

90

75

80

63.9 60.0 68.3 47.4 74.6 22.7 59.8 56.7 64.0 44.6 70.2 20.3

67.5 66.8 70.0 59.7 75.7 44.0 63.4 63.4 65.8 56.6 71.3 41.4

71.6 71.6 73.0 68.1 76.7 58.1 67.5 67.5 68.8 64.8 72.4 55.2

75.8 75.8 76.7 74.3 79.2 67.9 71.7 71.7 72.5 70.9 74.8 64.8

65.8 63.2 69.7 50.8 75.5 26.3 61.5 59.7 65.2 47.7 70.8 23.7

69.8 69.8 71.9 63.3 77.0 47.8 65.5 65.5 67.4 59.9 72.3 44.9

74.1 74.1 75.2 71.9 78.4 62.1 69.8 69.8 70.8 68.3 73.8 58.9

78.6 78.6 79.1 78.4 81.2 72.1 74.2 74.2 74.7 74.7 76.7 68.7

67.3 65.7 70.6 53.5 76.0 29.2 62.8 61.9 65.9 50.1 71.1 26.3

71.6 71.6 73.2 66.2 77.8 50.9 67.0 67.0 68.5 62.5 73.0 47.7

76.2 76.2 76.9 75.0 79.7 65.4 71.6 71.6 72.2 71.2 74.9 61.9

80.9 80.9 81.1 81.1 82.8 75.6 76.3 76.3 76.4 76.4 78.0 71.9

68.4 67.6 71.1 55.5 76.8 31.5 63.6 63.5 66.2 51.9 71.5 28.2

72.9 72.9 74.1 68.4 77.9 53.3 68.2 68.2 69.2 64.5 73.1 49.7

77.8 77.8 78.1 77.4 80.5 67.9 73.0 73.0 73.2 73.2 75.5 64.1

81.0 81.0 82.6 82.6 84.0 78.3 76.5 75.0 77.7 77.7 79.0 74.4

68.9 68.7 71.2 56.9 77.0 33.0 63.7 63.7 67.0 52.9 72.2 29.5

73.9 73.9 74.6 69.9 78.2 55.0 68.9 68.9 69.5 65.7 73.9 51.1

78.0 78.0 78.9 78.9 80.9 69.8 73.2 71.0 73.8 73.8 75.6 65.7

82.1 82.1 83.7 83.7 84.7 80.4 77.0 77.0 78.6 78.6 79.4 76.1

6125

75

80

85

90

69.1 69.1 71.6 57.4 77.4 33.7 63.9 63.9 68.0 53.2 73.0 30.0

74.3 74.3 74.7 70.5 78.4 55.8 69.1 69.1 71.0 66.1 74.4 51.7

78.6 78.6 79.3 79.3 81.8 70.7 73.5 73.5 74.0 74.0 77.0 66.4

83.5 83.5 84.2 84.2 84.9 81.5 77.2 77.2 78.9 78.9 79.5 77.0

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

(a)For 2800, 3500, 4200, and 4900 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and

YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

60 RT-PRC028AC-EN

Performance Data

Table 33. Gross cooling capacities 17½ tons three phase high efficiency T/YH*210G3,4,W (stage 2)

Air

Flow cfm (a)

Ambient Temperature

85 95

Ent Entering Wet Bulb

DB 61 67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

2800

3500

4200

4900

5600

75 123.5 100.2 134.4 80.1 147.8 44.0 117.3 96.3 127.4 77.0 139.9 41.8

80 126.3 111.0 136.4 97.8 148.9 73.2 120.1 106.7 129.4 94.1 141.1 70.2

85 130.4 119.4 138.3 110.3 150.0 92.9 124.2 114.7 131.3 106.1 142.3 89.4

90 135.4 126.3 141.8 119.6 151.1 106.9 129.0 121.3 134.8 115.0 143.4 102.8

75 129.9 108.5 142.2 87.5 152.2 50.4 123.2 104.2 134.6 84.0 143.9 47.6

80 133.3 120.2 142.4 106.1 154.0 80.6 126.7 115.4 135.0 102.0 145.8 77.2

85 138.0 129.2 145.1 119.4 155.8 101.2 131.3 124.0 137.7 114.7 147.7 97.2

90 143.5 136.7 149.2 129.3 157.7 115.9 136.7 131.2 141.7 124.3 149.6 111.4

75 135.1 115.8 146.3 93.8 160.5 55.6 128.0 111.0 138.3 89.8 151.6 52.4

80 139.3 128.2 147.4 113.3 160.5 86.9 132.2 122.9 139.6 108.7 151.8 83.0

85 144.5 137.8 150.7 127.3 160.6 108.4 137.4 132.2 142.9 122.2 152.0 103.9

90 150.5 145.9 155.4 137.9 163.1 123.8 143.2 139.9 147.6 132.5 154.6 118.9

75 139.2 121.9 149.3 99.0 162.4 59.6 131.7 116.7 140.9 94.5 153.0 56.0

80 144.1 135.1 151.3 119.4 163.3 92.0 136.6 129.4 143.0 114.3 154.1 87.7

85 149.9 145.4 155.3 134.1 164.2 114.4 142.4 139.3 147.1 128.6 155.2 109.5

90 156.3 153.9 160.6 145.4 167.5 130.6 148.6 147.5 152.3 139.5 158.5 125.3

75 142.3 126.9 151.2 103.0 163.2 62.6 134.3 121.2 142.3 98.1 153.4 58.5

80 147.8 140.8 154.1 124.3 165.0 96.0 139.9 134.7 145.3 118.8 155.4 91.2

85 154.2 151.7 158.8 139.8 166.8 119.3 146.3 145.2 150.1 133.8 157.4 114.0

90 161.1 160.8 164.6 151.7 170.7 136.3 152.9 152.9 155.9 145.4 161.4 130.5

6125

75 143.8 129.9 151.9 105.3 164.1 64.0 135.5 123.9 142.7 100.0 154.0 59.6

80 149.9 144.4 155.4 127.3 165.5 98.3 141.7 137.9 146.4 121.4 155.6 93.2

85 156.7 155.8 160.7 143.3 168.0 122.3 148.4 148.4 151.7 137.0 158.2 116.6

90 163.9 163.9 167.0 155.7 172.5 139.8 155.4 155.4 157.9 149.0 162.8 133.6

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

(a)For 2800, 3500, 4200, and 4900 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and

YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

RT-PRC028AC-EN 61

Performance Data

Table 34. Gross cooling capacities 17½ tons three phase high efficiency T/YH*210G3,4,W (full load)

Air

Flow cfm (a)

3500

4200

4900

5600

6300

7000

7700

8400

85

Ambient Temperature

95 105

Ent Entering Wet Bulb

DB 61 67 73 61 67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 178.2 140.1 193.8 111.1 207.3 60.7 169.5 134.8 186.6 107.2 204.8 58.4 159.9 128.9 174.5 102.7 183.6 55.5

80 182.3 156.6 197.4 136.9 211.8 102.1 173.6 150.4 187.6 132.0 205.4 98.5 164.0 143.7 177.0 126.4 187.8 94.3

85 188.5 169.5 200.2 155.6 217.6 130.7 179.6 162.7 190.4 149.7 206.7 126.0 169.9 155.2 179.7 143.3 195.0 120.8

90 195.9 180.3 205.3 169.8 219.0 151.3 186.7 172.9 195.3 163.3 208.1 145.8 176.7 164.9 184.5 156.2 196.4 139.7

75 186.2 150.2 194.6 120.2 212.8 68.8 177.0 144.4 193.2 115.8 211.6 66.0 166.9 138.0 183.6 110.8 196.3 62.6

80 191.0 167.4 205.2 147.0 223.4 111.3 181.8 160.8 194.9 141.5 212.2 107.2 171.7 153.5 183.7 135.5 198.7 102.5

85 197.7 181.0 208.6 166.4 225.1 140.8 188.3 173.7 198.3 160.1 213.7 135.6 178.1 165.7 187.1 153.2 201.5 129.9

90 205.5 192.4 214.2 181.3 227.2 162.2 195.9 184.5 203.8 174.3 215.8 156.2 185.3 176.0 192.4 166.7 203.5 149.6

75 193.4 159.4 211.5 128.5 229.7 76.0 183.6 153.0 200.5 123.6 217.5 72.7 173.0 146.1 188.6 118.0 204.6 68.8

80 198.8 177.4 212.0 156.2 230.6 119.6 189.1 170.2 201.2 150.2 218.2 114.9 178.5 162.4 189.5 143.6 205.4 109.7

85 206.0 191.6 216.1 176.3 231.7 150.0 196.1 183.7 205.2 169.5 219.8 144.3 185.4 175.3 193.6 162.1 207.0 138.0

90 214.3 203.5 222.3 191.9 234.4 172.2 204.1 195.1 211.3 184.4 222.5 165.6 193.0 186.1 199.4 176.3 209.8 158.5

75 199.6 167.6 216.7 135.8 236.2 82.3 189.4 160.8 205.1 130.4 223.6 78.5 178.3 153.3 192.7 124.3 206.4 74.0

80 205.7 186.4 218.0 164.4 237.1 126.9 195.5 178.7 206.6 157.9 224.2 121.8 184.4 170.4 194.4 150.8 211.7 116.0

85 213.5 201.3 222.7 185.3 237.4 158.2 203.1 192.9 211.4 178.0 225.0 152.0 191.8 183.9 199.1 170.0 211.7 145.2

90 222.1 213.8 229.4 201.6 240.8 181.2 211.4 204.9 217.9 193.6 228.4 174.2 199.8 195.3 205.5 184.9 215.1 166.5

75 205.0 174.9 220.9 142.2 240.8 87.7 194.2 167.6 208.8 136.2 227.7 83.3 182.6 159.6 195.9 129.7 208.9 78.4

80 211.7 194.5 223.1 171.7 241.7 133.3 201.0 186.3 211.2 164.7 228.6 127.7 189.4 177.4 198.5 157.1 214.6 121.4

85 220.0 210.0 228.4 193.4 242.2 165.6 209.1 201.1 216.6 185.6 229.3 158.8 197.3 191.6 203.8 177.1 215.5 151.5

90 229.1 223.1 235.7 210.4 246.2 189.3 217.8 213.7 223.6 201.8 233.3 181.8 205.7 203.6 210.8 192.6 219.5 173.6

75 209.4 181.3 224.2 147.7 243.2 92.1 198.2 173.4 211.7 141.2 230.3 87.2 186.0 165.0 198.2 134.1 210.2 81.8

80 216.9 201.6 227.2 178.1 244.8 138.8 205.6 192.9 214.8 170.5 231.2 132.7 193.4 183.6 201.6 162.4 216.7 125.9

85 225.6 217.8 233.3 200.6 246.1 172.0 214.2 208.4 220.9 192.2 232.7 164.7 201.9 198.4 207.6 183.2 218.4 156.9

90 235.1 231.5 241.0 218.2 250.8 196.5 223.4 221.5 228.5 209.1 237.4 188.4 210.8 210.8 215.1 199.4 223.1 179.7

75 213.0 186.8 226.7 152.2 245.6 95.6 201.2 178.4 213.6 145.2 231.9 90.2 188.6 169.4 199.6 137.6 210.6 84.2

80 221.1 207.9 230.5 183.5 247.0 143.4 209.3 198.6 217.6 175.5 232.8 136.7 196.6 188.8 203.8 166.8 217.9 129.4

85 230.4 224.7 237.2 206.8 249.1 177.5 218.4 214.8 224.3 197.9 235.2 169.7 205.6 204.3 210.5 188.4 220.4 161.4

90 240.3 238.9 245.5 225.1 254.5 202.8 228.0 228.0 232.4 215.5 240.5 194.2 214.9 214.9 218.5 205.3 225.7 185.0

75 215.7 191.3 228.2 155.8 246.8 98.2 203.4 182.4 214.6 148.3 232.7 92.3 190.2 172.9 200.2 140.2 220.4 85.8

80 224.4 213.2 232.9 188.1 248.3 147.1 212.1 203.4 219.5 179.5 233.6 139.9 199.0 193.1 205.2 170.3 220.8 132.1

85 234.2 230.7 240.2 212.1 251.3 182.0 221.8 220.3 226.8 202.7 236.8 173.8 208.4 208.4 212.6 192.7 221.5 164.9

90 244.5 244.5 249.1 231.1 257.3 208.1 231.8 231.8 235.5 221.0 242.8 199.0 218.1 218.1 221.1 210.2 227.5 189.3

62 RT-PRC028AC-EN

Performance Data

Table 34. Gross cooling capacities 17½ tons three phase high efficiency T/YH*210G3,4,W (full load)

Air

Flow cfm

(a)

3500

115

Ambient Temperature

120 125

Ent

DB 61 67 73 61

Entering Wet Bulb

67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 149.5 122.4 158.0 97.6 172.5 52.1 144.0 119.0 155.8 94.8 165.9 50.1 138.2 115.3 148.3 91.9 160.8 48.0

80 153.6 136.3 165.4 120.3 176.7 89.5 148.1 132.4 159.3 117.0 169.4 86.9 142.3 128.4 153.0 113.5 163.4 84.1

85 159.3 147.2 168.2 136.3 182.4 114.9 153.7 143.0 162.1 132.6 175.8 111.8 147.8 138.6 155.8 128.7 169.0 108.4

90 165.8 156.4 172.8 148.5 183.8 133.0 160.1 151.8 166.7 144.4 177.2 129.4 154.1 147.2 160.3 140.2 170.4 125.7

75 156.0 131.0 171.4 105.2 184.6 58.6 150.2 127.2 164.9 102.2 174.8 56.4 144.2 123.3 158.3 99.0 162.4 54.0

4200

4900

5600

6300

7000

80 160.8 145.6 171.6 128.8 186.8 97.2 155.0 141.5 165.3 125.2 175.3 94.3 149.0 137.2 158.7 121.5 168.6 91.2

85 167.0 157.2 175.0 145.6 188.4 123.5 161.1 152.7 168.7 141.6 181.5 120.1 155.0 148.0 162.1 137.5 174.4 116.5

90 173.9 166.9 180.2 158.5 190.4 142.3 167.9 162.1 173.8 154.1 183.6 138.5 161.6 157.2 167.1 149.6 176.5 134.5

75 161.6 138.6 175.9 111.9 190.2 64.3 155.5 134.6 169.2 108.6 180.7 61.8 149.3 130.4 162.3 105.2 175.1 59.2

80 167.0 154.0 176.9 136.4 192.8 103.9 161.0 149.6 170.3 132.6 181.3 100.7 154.7 145.0 163.5 128.6 176.4 97.4

85 173.7 166.2 181.0 154.0 193.4 131.1 167.6 161.4 174.4 149.8 186.3 127.4 161.3 156.5 167.6 145.3 178.9 123.6

90 181.1 176.5 186.7 167.5 196.1 150.7 174.8 171.5 180.0 162.9 189.0 146.6 168.3 166.3 173.1 158.2 181.7 142.4

75 166.3 145.3 179.4 117.7 192.5 69.0 160.0 141.0 172.5 114.1 184.5 66.3 153.5 136.6 165.3 110.4 176.9 63.4

80 172.4 161.5 181.4 143.1 197.4 109.7 166.1 156.8 174.5 139.0 189.9 106.3 159.6 152.0 167.4 134.8 182.2 102.7

85 179.6 174.3 186.1 161.5 197.6 137.8 173.2 169.3 179.2 157.0 190.2 133.9 166.6 164.1 172.1 152.3 182.6 129.8

90 187.4 185.2 192.3 175.7 201.0 158.2 180.9 179.9 185.4 170.8 193.6 153.9 174.1 174.1 178.2 165.8 186.0 149.3

75 170.1 151.0 182.1 122.5 194.1 72.8 163.6 146.5 174.9 118.7 185.6 69.8 156.8 141.9 167.5 114.8 178.3 66.7

80 176.9 168.0 184.9 148.8 199.8 114.6 170.3 163.1 177.8 144.5 192.1 110.9 163.5 158.0 170.4 140.0 184.1 107.1

85 184.6 181.5 190.2 168.0 200.8 143.6 178.0 176.2 183.1 163.2 193.2 139.4 171.1 170.8 175.8 158.3 185.3 135.1

90 192.8 192.8 197.0 182.9 204.9 164.8 186.0 186.0 189.8 177.7 197.2 160.2 179.0 179.0 182.4 172.5 189.4 155.4

75 173.0 155.9 183.9 126.5 194.4 75.7 166.2 151.1 176.5 122.4 186.5 72.4 159.2 146.2 168.8 118.2 178.8 69.0

80 180.4 173.6 187.5 153.7 201.3 118.5 173.6 168.4 180.1 149.1 193.3 114.6 166.6 163.1 172.5 144.3 185.1 110.5

85 188.7 187.8 193.5 173.6 203.2 148.5 181.8 181.8 186.2 168.6 195.3 144.0 174.7 174.7 178.6 163.4 187.2 139.4

90 197.3 197.3 200.8 189.1 207.9 170.4 190.2 190.2 193.4 183.8 200.0 165.5 183.0 183.0 185.7 178.2 191.9 160.5

75 175.1 159.8 184.8 129.4 195.2 77.6 168.0 154.8 177.1 125.1 187.2 74.1 160.7 149.6 169.2 120.7 179.2 70.5

7700

80 183.1 178.3 189.2 157.6 202.0 121.5 176.0 172.9 181.6 152.7 193.7 117.4 168.7 167.3 173.8 147.7 185.3 113.0

85 191.9 191.9 195.9 178.3 204.7 152.4 184.8 184.8 188.3 173.0 196.5 147.7 177.4 177.4 180.4 167.6 188.1 142.8

90 200.9 200.9 203.8 194.5 210.1 175.1 193.6 193.6 196.0 188.8 201.9 170.0 186.1 186.1 188.1 183.1 193.5 164.7

75 176.2 162.8 184.8 131.5 195.6 78.7 168.9 157.5 177.8 126.9 187.9 74.9 161.3 152.0 170.0 122.2 180.3 71.0

8400

80 184.9 182.1 190.1 160.6 202.4 123.6 177.6 176.4 182.2 155.4 194.3 119.2 170.0 170.0 174.1 150.2 184.4 114.6

85 194.2 194.2 197.4 182.1 205.3 155.4 186.8 186.8 189.5 176.5 196.8 150.4 179.2 179.2 181.4 170.8 188.2 145.3

90 203.6 203.6 205.8 198.9 211.3 178.9 196.1 196.1 197.8 193.0 202.9 173.5 188.3 188.3 189.6 187.0 194.2 168.0

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

(a)For 3500, 4200, and 4900 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

RT-PRC028AC-EN 63

Performance Data

Table 35. Gross cooling capacities 17½ tons three phase dehumidification (hot gas reheat) option high efficiency T/

YHD210G3,4,W (Digit 22 = B)

Air

Flow cfm (a)

3500

4550

5600

6300

7000

7700

8400

85

Ambient Temperature

95 105

Ent

DB 61 67 73 61

Entering Wet Bulb

67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 157.6 122.6 174.5 95.9 196.1 56.8 151.2 119.5 166.8 93.6 187.2 55.2 143.7 115.7 158.2 90.5 177.3 53.0

80 160.6 140.5 174.2 120.6 192.5 88.1 154.0 136.7 166.5 117.6 183.6 85.9 146.5 132.2 157.8 113.8 173.6 83.0

85 165.2 154.7 175.6 141.4 190.7 115.7 158.6 150.2 167.8 137.7 181.7 112.8 151.0 145.0 159.0 133.3 171.6 109.2

90 171.5 165.0 178.7 158.5 190.5 139.5 164.8 159.9 170.8 154.1 181.4 135.9 157.2 154.0 161.9 149.1 171.3 131.6

75 167.1 138.7 182.4 110.5 202.3 69.8 160.1 134.8 174.2 107.4 192.8 67.5 152.2 130.2 164.9 103.5 182.4 64.4

80 171.1 158.1 183.1 136.6 199.7 102.6 164.0 153.5 174.8 132.7 190.2 99.5 156.0 148.2 165.5 128.2 179.7 95.8

85 176.7 173.6 185.5 158.8 198.9 131.5 169.6 168.3 177.1 154.3 189.3 127.8 161.4 161.4 167.7 149.1 178.7 123.4

90 184.0 184.0 189.5 177.3 199.7 156.7 176.8 176.8 181.1 172.1 190.0 152.3 168.6 168.6 171.6 166.2 179.4 147.2

75 174.9 145.5 188.5 116.5 206.7 75.0 167.3 141.2 179.7 113.0 196.7 72.3 158.8 136.2 169.9 108.7 185.7 68.8

80 179.8 165.5 190.1 143.2 205.1 108.5 172.2 160.6 181.3 139.0 195.1 105.0 163.6 154.9 171.5 134.1 184.0 100.9

85 186.4 181.8 193.5 166.2 205.3 138.1 178.7 176.1 184.6 161.3 195.1 134.0 170.0 169.7 174.7 155.7 184.0 129.2

90 194.7 194.2 198.5 185.3 207.0 164.0 186.9 186.9 189.5 179.8 196.8 159.2 178.1 178.1 179.6 173.5 185.7 153.7

75 179.1 151.4 191.5 121.6 208.6 79.4 171.1 146.7 182.4 117.7 198.3 76.2 162.2 141.3 172.3 113.1 187.0 72.4

80 184.6 172.1 193.9 149.1 207.7 113.5 176.6 166.8 184.7 144.5 197.3 109.7 167.7 160.7 174.5 139.1 185.9 105.1

85 191.9 189.1 197.9 172.7 208.5 143.9 183.8 183.0 188.6 167.4 198.0 139.3 174.8 174.8 178.3 161.4 186.5 134.1

90 200.8 200.8 203.5 192.6 210.9 170.4 192.6 192.6 194.2 186.6 200.4 165.2 183.5 183.5 183.9 179.9 188.8 159.3

75 182.4 156.5 193.8 125.9 209.8 82.9 174.2 151.4 184.3 121.6 199.1 79.3 164.9 145.6 173.8 116.6 187.4 75.1

80 188.6 177.9 196.8 154.0 209.5 117.7 180.3 172.1 187.2 149.0 198.8 113.5 171.0 165.6 176.7 143.3 187.0 108.5

85 196.5 195.5 201.4 178.4 211.0 148.7 188.1 188.1 191.8 172.7 200.1 143.8 178.7 178.7 181.2 166.3 188.3 138.2

90 206.1 206.1 207.7 198.9 214.1 176.0 197.6 197.6 198.0 192.5 203.1 170.4 185.5 185.5 187.3 185.5 191.2 164.1

75 185.0 160.6 195.3 129.3 210.2 85.5 176.4 155.2 185.4 124.6 199.1 81.5 166.7 149.0 174.6 119.2 187.0 76.9

80 191.9 182.8 198.9 158.1 210.6 121.0 183.2 176.6 189.0 152.7 199.4 116.4 173.5 169.7 178.0 146.6 187.3 111.0

85 200.4 200.4 204.2 183.1 212.6 152.7 191.6 191.6 194.2 177.1 201.4 147.4 181.9 181.9 183.2 170.3 189.2 141.4

90 210.6 210.6 211.2 204.4 216.4 180.7 201.8 201.8 201.1 197.6 205.1 174.7 190.0 190.0 190.0 190.0 192.8 168.0

75 186.8 164.0 195.9 131.8 209.7 87.2 177.8 158.1 185.7 126.7 198.3 82.9 167.8 151.5 174.5 120.9 185.9 77.8

80 194.3 186.8 200.2 161.3 210.8 123.5 185.2 180.2 189.9 155.6 199.3 118.4 175.2 172.9 178.6 149.0 186.8 112.7

85 203.5 203.5 206.2 187.1 213.5 155.9 194.4 194.4 195.8 180.6 201.9 150.2 184.2 184.2 184.5 173.4 189.3 143.8

90 214.4 214.4 213.8 209.0 217.9 184.5 201.3 201.3 203.4 201.8 206.2 178.1 191.9 191.9 191.9 191.9 193.6 171.1

64 RT-PRC028AC-EN

Performance Data

Table 35. Gross cooling capacities 17½ tons three phase dehumidification (hot gas reheat) option high efficiency T/

YHD210G3,4,W (Digit 22 = B)

115

Ambient Temperature

120 125

Air

Flow

cfm (a)

Ent

DB 61 67 73 61

Entering Wet Bulb

67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

3500

4550

5600

6300

75 135.3 111.1 148.5 86.8 166.4 50.0 130.7 108.6 143.3 84.7 160.6 48.2 125.9 105.9 137.9 82.4 154.5 46.3

80 138.0 127.0 148.0 109.4 162.7 79.3 133.4 124.2 142.8 106.9 156.8 77.2 128.5 121.1 137.3 104.3 150.8 75.0

85 142.4 139.2 149.2 128.2 160.6 104.8 137.8 136.0 143.9 125.4 154.8 102.4 132.9 132.6 138.4 122.4 148.6 99.8

90 148.5 147.5 152.1 143.3 160.3 126.6 143.8 143.8 146.8 140.1 154.3 123.8 138.9 138.9 141.2 136.8 148.2 120.9

75 143.2 124.9 154.8 99.0 171.0 60.6 138.3 119.0 149.3 93.8 164.9 56.2 133.2 118.9 143.6 93.8 158.6 56.2

80 146.9 142.2 155.2 123.0 168.2 91.3 142.0 135.6 149.7 117.2 162.1 86.3 136.9 135.5 144.0 117.1 155.8 86.2

85 152.3 152.3 157.4 143.2 167.2 118.3 147.4 147.4 151.9 136.7 161.0 112.5 142.2 142.2 146.1 136.6 154.6 112.4

90 159.6 159.6 161.2 159.6 167.8 141.4 154.4 154.4 155.7 152.4 161.6 134.9 149.8 149.8 149.8 149.8 155.1 134.9

75 149.3 130.5 159.2 103.8 173.8 64.6 144.2 127.4 153.5 101.1 167.4 62.3 138.8 124.1 147.5 98.2 160.8 59.8

80 154.0 148.5 160.7 128.5 172.0 96.1 148.8 145.0 154.9 125.4 165.6 93.4 143.4 141.4 148.9 122.2 159.0 90.5

85 160.4 160.4 163.8 149.4 171.9 123.7 155.2 155.2 158.0 146.0 165.5 120.6 149.7 149.7 151.9 142.4 158.8 117.4

90 168.4 168.4 168.6 166.5 173.5 147.5 162.8 162.8 162.8 162.8 167.0 144.1 156.7 156.7 156.7 156.7 160.3 140.6

75 152.4 135.2 161.2 107.7 174.6 67.8 147.0 131.9 155.2 104.8 168.1 65.3 141.5 128.4 149.1 101.7 161.3 62.5

80 157.7 153.9 163.3 133.1 173.5 99.9 152.4 150.2 157.3 129.9 166.9 97.0 146.8 146.4 151.1 126.4 160.1 94.0

85 164.7 164.7 167.1 154.7 174.1 128.2 159.4 159.4 161.1 151.1 167.5 125.0 153.7 153.7 154.8 147.3 160.6 121.6

90 172.5 172.5 172.5 172.5 176.3 152.7 166.5 166.5 166.5 166.5 169.7 149.2 160.2 160.2 160.2 160.2 162.8 145.4

7000

7700

75 154.6 139.1 162.3 110.8 174.7 70.1 149.1 135.5 156.2 107.7 168.0 67.4 143.4 131.9 149.9 104.4 161.0 64.4

80 160.6 158.4 165.1 136.9 174.2 102.9 155.1 154.6 159.0 133.4 167.5 99.8 149.3 149.3 152.6 129.8 160.5 96.6

85 168.3 168.3 169.6 159.2 175.4 131.9 162.8 162.8 163.4 155.4 168.7 128.5 156.9 156.9 157.0 151.4 161.6 124.9

90 175.7 175.7 175.7 175.7 178.3 157.1 169.4 169.4 169.4 169.4 171.5 153.3 163.0 163.0 163.0 163.0 164.4 149.4

75 156.1 142.0 162.7 113.0 174.0 71.5 150.5 138.3 156.4 109.7 167.1 68.6 144.5 134.4 149.9 106.2 159.9 65.5

80 162.8 162.1 166.1 139.8 174.2 105.0 157.1 157.1 159.8 136.1 167.2 101.7 151.1 151.1 153.3 132.3 160.0 98.3

85 171.1 171.1 171.2 162.8 176.0 134.7 165.4 165.4 164.9 158.8 169.0 131.1 159.4 159.4 158.3 154.6 161.8 127.3

90 178.0 178.0 178.0 178.0 179.5 160.6 171.6 171.6 171.6 171.6 172.5 156.7 165.0 165.0 165.0 165.0 165.3 152.5

8400

75 156.8 144.2 162.3 114.4 172.5 72.1 151.0 140.3 155.8 110.8 165.4 69.0 144.9 136.2 149.1 107.1 158.0 65.6

80 164.1 164.1 166.4 141.8 173.3 106.3 158.2 158.2 159.9 138.0 166.2 102.8 152.1 152.1 153.1 133.9 158.8 99.1

85 173.1 173.1 172.1 165.5 175.8 136.7 167.2 167.2 165.6 161.3 168.6 132.8 157.2 157.2 158.8 156.9 161.2 128.8

90 179.5 179.5 179.5 179.5 180.0 163.3 173.0 173.0 173.0 173.0 172.8 159.1 166.1 166.1 166.1 166.1 165.3 154.8

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

(a)For 3500, and 4550 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

RT-PRC028AC-EN 65

Performance Data

Table 36. Gross cooling capacities 20 tons three phase high efficiency T/YH*240G3,4,W (stage 1)

Air

Flow cfm (a)

Ambient Temperature

85 95

Ent Entering Wet Bulb

DB 61 67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

3200

4000

4800

5600

6400

85

90

75

80

85

90

75

80

85

90

75

80

85

90

75

80

85

90

75

80

71.7 67.2 76.0 52.7 82.4 24.7 66.8 63.4 70.9 49.4 77.0 21.9

76.1 75.4 78.6 67.1 84.3 49.4 71.3 71.3 73.5 63.4 78.9 46.1

81.1 81.1 82.5 77.1 86.2 65.8 76.3 76.3 77.4 73.1 80.9 62.2

86.3 86.3 87.1 84.6 89.5 77.4 81.4 81.4 82.0 80.5 84.3 73.6

73.6 70.6 77.4 56.5 83.2 28.8 68.4 66.4 71.9 52.7 79.9 25.6

78.5 78.5 80.4 71.0 85.6 53.6 73.3 73.3 75.0 66.9 79.9 50.0

83.8 83.8 84.8 81.2 88.0 70.2 78.6 78.6 79.4 76.9 82.3 66.3

89.3 89.3 89.8 89.1 91.8 82.0 84.1 84.1 84.4 84.4 86.2 77.9

75.0 73.3 78.2 59.4 85.9 32.1 69.5 68.6 72.5 55.2 80.0 28.5

80.3 80.3 81.8 74.2 86.4 57.1 74.8 74.8 76.1 69.7 80.4 53.0

86.0 86.0 86.6 84.7 89.3 73.9 80.5 80.5 80.9 79.9 83.4 69.6

91.8 91.8 91.9 91.9 93.6 86.0 85.0 85.0 86.2 86.2 87.6 81.4

76.0 75.2 78.6 61.6 86.0 34.7 70.2 70.1 72.5 57.1 80.2 30.7

81.7 81.7 82.7 76.6 86.8 59.8 75.9 75.9 76.7 71.7 80.5 55.4

87.8 87.8 87.9 87.3 90.2 76.8 81.0 81.0 81.9 81.9 83.9 72.1

92.0 92.0 93.6 93.6 94.9 89.2 87.0 88.0 87.6 87.6 88.6 84.2

76.5 76.3 79.0 63.1 87.0 36.5 70.3 70.3 73.0 58.1 81.0 32.1

82.6 82.6 83.2 78.3 88.0 61.8 76.5 76.5 76.8 73.0 82.5 56.9

88.2 88.2 88.8 88.8 90.6 79.0 82.0 82.0 82.4 82.4 84.0 73.9

93.5 93.5 94.8 94.8 95.7 91.6 88.2 88.2 88.5 88.5 89.1 86.2

7000

75

80

85

90

76.5 76.5 81.0 63.7 88.0 37.4 70.2 70.2 75.0 58.4 82.0 32.7

83.0 83.0 83.2 79.0 91.0 62.7 76.6 76.6 78.0 73.4 84.0 57.6

89.0 89.0 89.1 89.1 94.0 80.1 82.2 82.2 82.5 82.5 86.0 74.7

95.0 95.0 95.4 95.4 96.0 92.9 88.4 89.0 88.8 88.8 89.1 87.3

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

(a)For 3200, 4000, 4800, and 5600 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and

YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

66 RT-PRC028AC-EN

Performance Data

Table 37. Gross cooling capacities 20 tons three phase high efficiency T/YH*240G3,4,W (stage 2)

Air

Flow cfm (a)

Ambient Temperature

85 95

Ent Entering Wet Bulb

DB 61 67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

3200

4000

4800

5600

6400

75 147.4 116.5 161.9 94.0 179.6 54.5 139.3 111.3 153.0 89.7 169.9 51.2

80 150.8 130.2 164.3 114.7 181.0 87.0 142.8 124.5 155.5 109.7 171.4 82.9

85 155.8 141.5 166.7 130.2 182.4 110.0 147.8 135.4 158.0 124.7 172.9 105.2

90 161.9 151.4 170.9 142.5 183.7 127.2 153.7 144.9 162.2 136.6 174.4 121.9

75 155.6 127.1 171.7 103.0 185.5 61.7 147.0 121.3 162.1 98.1 175.3 57.9

80 160.1 142.0 172.3 125.2 187.9 96.0 151.5 135.8 163.0 119.7 177.7 91.4

85 165.9 154.4 175.7 141.9 190.2 120.5 157.3 147.7 166.4 135.9 180.2 115.2

90 172.5 165.2 180.7 155.4 192.5 138.9 163.9 158.2 171.5 148.9 182.6 133.1

75 162.5 136.3 177.1 110.6 195.7 67.6 153.4 130.0 167.0 105.3 184.6 63.2

80 167.9 152.5 178.9 134.3 196.1 103.6 158.8 145.7 169.0 128.3 185.3 98.5

85 174.5 166.0 183.2 152.3 196.6 129.6 165.4 158.8 173.5 145.8 186.0 123.8

90 181.8 177.7 189.1 166.9 199.9 149.3 172.6 170.2 179.3 159.9 189.4 143.0

75 168.0 144.2 181.2 116.9 198.4 72.1 158.3 137.4 170.5 111.0 186.8 67.2

80 174.3 161.7 184.1 142.1 200.0 109.9 164.7 154.3 173.7 135.6 188.6 104.2

85 181.7 176.2 189.4 161.4 201.6 137.4 172.0 168.4 179.1 154.3 190.5 131.1

90 189.6 188.8 196.1 177.1 205.9 158.4 179.9 179.9 185.7 169.6 194.9 151.5

75 172.1 150.7 183.8 121.9 199.6 75.3 161.8 143.4 172.6 115.5 187.5 69.9

80 179.3 169.5 187.9 148.6 202.4 114.9 169.2 161.6 177.0 141.5 190.5 108.7

85 187.5 185.1 194.2 169.2 205.2 143.9 177.3 176.8 183.3 161.6 193.5 137.0

90 196.0 196.0 201.6 185.9 210.4 166.2 185.8 185.8 190.7 177.9 198.9 158.8

7000

75 174.2 154.7 184.8 124.8 199.6 76.8 163.5 147.0 173.2 117.9 190.8 71.0

80 182.2 174.4 189.9 152.6 203.3 117.8 171.6 166.2 178.5 145.1 191.0 111.1

85 190.9 190.8 196.8 174.1 207.0 147.9 180.3 180.3 185.5 166.1 194.9 140.6

90 199.9 199.9 204.9 191.6 212.9 171.1 189.3 189.3 193.6 183.2 201.0 163.3

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

(a)For 3200, 4000, 4800, and 5600 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and

YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

RT-PRC028AC-EN 67

Performance Data

Table 38. Gross cooling capacities 20 tons three phase high efficiency T/YH*240G3,4,W (full load)

Air

Flow cfm (a)

4000

4800

5600

6400

7200

8000

8800

9600

85

Ambient Temperature

95 105

Ent Entering Wet Bulb

DB 61 67 73 61 67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 204.7 159.8 224.3 126.6 248.0 69.4 194.8 153.5 213.3 121.7 235.9 66.2 184.1 146.6 201.4 116.3 223.0 62.4

80 209.6 179.2 227.5 156.5 249.7 116.6 199.7 172.0 216.5 150.5 237.6 112.1 189.0 164.2 204.7 143.9 224.8 106.9

85 217.0 194.6 230.8 178.3 251.4 149.6 206.9 186.7 219.8 171.4 239.4 143.9 195.9 178.1 208.0 163.9 226.5 137.7

90 225.7 207.7 236.9 195.3 253.2 173.8 215.3 199.2 225.7 187.6 241.1 167.2 204.1 190.1 213.7 179.4 228.2 160.0

75 214.2 171.5 232.6 137.1 255.1 78.6 203.7 164.6 225.1 131.7 242.5 74.8 192.4 157.1 212.5 125.6 229.0 70.4

80 220.0 191.9 236.7 168.2 257.7 127.2 209.5 184.0 225.1 161.6 245.1 122.0 198.1 175.6 212.7 154.4 231.6 116.3

85 228.0 208.1 240.9 191.0 260.3 161.4 217.3 199.6 229.2 183.5 247.7 155.1 205.7 190.4 216.8 175.4 234.2 148.2

90 237.3 221.9 247.6 208.8 262.9 186.5 226.3 212.8 235.9 200.6 250.2 179.3 214.5 203.1 223.2 191.7 236.7 171.5

75 222.7 182.1 243.9 146.6 261.2 86.7 211.5 174.6 231.5 140.5 248.0 82.3 199.6 166.5 218.3 133.9 233.9 77.4

80 229.3 203.5 244.8 178.8 264.7 136.7 218.1 195.0 232.6 171.6 251.4 130.9 206.2 186.0 219.5 163.8 237.3 124.6

85 237.9 220.6 249.8 202.6 268.1 172.0 226.6 211.4 237.6 194.5 254.8 165.1 214.5 201.7 224.5 185.8 240.7 157.6

90 247.8 235.1 257.3 221.2 271.6 198.1 236.2 225.3 244.9 212.4 258.3 190.3 223.7 215.0 231.6 203.0 244.2 181.9

75 230.0 191.6 249.9 154.9 274.8 93.8 218.3 183.5 236.8 148.3 260.5 88.8 205.7 174.8 223.0 141.0 245.5 83.2

80 237.5 214.0 251.8 188.3 274.8 145.1 225.7 204.9 239.0 180.5 260.7 138.7 213.1 195.3 225.3 172.1 245.9 131.8

85 246.8 231.9 257.6 213.1 274.8 181.6 234.9 222.1 244.8 204.4 260.9 174.1 222.1 211.8 231.1 195.1 246.2 166.0

90 257.2 247.1 265.8 232.6 279.1 208.6 245.0 236.8 252.8 223.1 265.2 200.2 231.9 225.9 239.0 213.1 250.5 191.2

75 236.2 200.1 254.7 162.2 278.3 99.8 223.9 191.4 241.1 155.0 263.4 94.2 210.7 182.0 226.6 147.1 247.8 88.0

80 244.5 223.4 257.7 196.7 279.4 152.5 232.2 213.7 244.3 188.3 264.7 145.5 219.0 203.5 230.0 179.4 249.2 137.9

85 254.6 242.2 264.4 222.5 280.4 190.0 242.0 231.8 250.9 213.2 265.9 181.9 228.7 220.8 236.7 203.3 250.6 173.3

90 265.5 258.1 273.2 242.8 285.6 218.1 252.6 247.2 259.6 232.8 271.1 209.1 239.0 235.6 245.2 222.2 255.8 199.5

75 241.4 207.5 258.4 168.5 280.7 104.7 228.4 198.1 244.2 160.6 265.2 98.5 214.6 188.2 229.1 152.1 249.0 91.7

80 250.5 231.7 262.5 204.1 282.8 158.7 237.6 221.5 248.5 195.1 267.5 151.1 223.8 210.7 233.6 185.5 251.4 143.0

85 261.2 251.3 270.1 230.8 284.9 197.4 248.1 240.4 256.0 220.9 269.8 188.7 234.1 228.8 241.1 210.5 253.9 179.4

90 272.7 268.0 279.6 252.0 291.0 226.5 259.2 256.5 265.4 241.4 275.8 216.9 245.0 244.3 250.3 230.2 259.9 206.7

75 245.4 213.8 261.1 173.6 282.0 108.5 231.9 203.8 246.2 165.1 265.9 101.7 217.5 193.3 230.6 156.1 249.1 94.3

80 255.4 239.0 266.2 210.4 285.2 163.9 241.8 228.2 251.6 200.8 269.3 155.7 227.4 216.7 236.1 190.6 252.6 146.9

85 266.8 259.4 274.6 238.1 288.4 203.8 253.0 247.9 259.9 227.6 272.6 194.4 238.5 235.7 244.4 216.5 256.1 184.6

90 278.8 276.8 284.8 260.1 295.2 233.8 264.7 264.7 270.0 248.9 279.5 223.6 249.9 249.9 254.3 237.1 263.0 212.8

75 248.4 219.0 262.6 177.6 282.2 111.2 234.2 208.4 247.2 168.6 265.5 103.8 219.2 197.3 230.9 158.9 248.1 95.8

80 259.2 245.2 268.8 215.6 286.4 168.0 245.0 233.7 253.6 205.4 270.0 159.2 230.0 221.7 237.5 194.6 252.6 149.8

85 271.3 266.5 278.1 244.3 290.7 209.0 256.9 254.3 262.8 233.2 274.4 199.1 241.7 241.5 246.7 221.5 257.2 188.6

90 283.8 283.8 289.0 267.2 298.4 240.0 269.1 269.1 273.5 255.3 282.1 229.2 253.7 253.7 257.3 242.9 264.9 217.8

68 RT-PRC028AC-EN

Performance Data

Table 38. Gross cooling capacities 20 tons three phase high efficiency T/YH*240G3,4,W (full load)

Air

Flow cfm

(a)

4000

115

Ambient Temperature

120 125

Ent

DB 61 67 73 61

Entering Wet Bulb

67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 172.5 139.1 188.8 110.3 209.3 58.1 166.4 135.1 182.1 107.1 202.2 55.7 160.1 131.0 175.3 103.7 194.8 53.1

80 177.4 155.8 192.0 136.8 211.0 101.2 171.3 151.4 185.4 133.0 203.9 98.1 164.9 146.8 178.5 129.1 196.5 94.9

85 184.2 169.0 195.3 155.9 212.8 130.8 178.0 164.3 188.6 151.7 205.6 127.2 171.6 159.4 181.8 147.3 198.2 123.4

90 192.0 180.4 200.9 170.7 214.5 152.2 185.7 175.3 194.2 166.1 207.3 148.1 179.1 170.1 187.2 161.3 199.9 143.9

75 180.2 149.0 199.0 119.0 214.7 65.5 173.8 144.7 192.0 115.5 207.2 62.8 167.2 140.3 184.7 111.8 199.6 60.0

4800

5600

6400

7200

8000

80 185.9 166.6 199.4 146.7 217.3 110.0 179.5 161.9 192.4 142.6 209.8 106.6 172.9 157.1 185.3 138.4 202.1 103.1

85 193.4 180.7 203.5 166.8 219.8 140.7 186.9 175.7 196.5 162.2 212.3 136.8 180.2 170.5 189.4 157.5 204.7 132.7

90 201.8 192.8 209.8 182.4 222.4 163.1 195.2 187.4 202.7 177.5 214.9 158.7 188.3 181.9 195.5 172.4 207.2 154.2

75 186.8 157.8 204.2 126.7 219.0 71.8 180.1 153.2 196.9 122.8 211.2 68.8 173.2 148.5 189.3 118.9 203.2 65.7

80 193.4 176.4 205.6 155.5 222.4 117.6 186.6 171.4 198.4 151.1 214.6 114.0 179.7 166.2 190.9 146.5 206.6 110.1

85 201.5 191.3 210.6 176.5 225.8 149.6 194.7 186.0 203.3 171.7 218.0 145.3 187.7 180.5 195.9 166.7 210.0 141.0

90 210.5 204.1 217.6 193.0 229.2 172.9 203.5 198.5 210.2 187.8 221.4 168.3 196.4 192.7 202.7 182.4 213.4 163.4

75 192.3 165.5 208.3 133.2 229.6 77.1 185.3 160.6 200.7 129.1 221.3 73.8 178.1 155.6 192.8 124.8 212.9 70.3

80 199.7 185.1 210.8 163.2 230.1 124.3 192.7 179.8 203.3 158.5 222.0 120.3 185.5 174.3 195.5 153.7 213.6 116.1

85 208.5 200.9 216.6 185.2 230.7 157.3 201.4 195.2 209.1 180.1 222.6 152.8 194.1 189.4 201.3 174.8 214.3 148.1

90 218.0 214.4 224.3 202.5 235.0 181.7 210.8 208.4 216.7 197.0 226.9 176.7 203.3 202.3 208.8 191.4 218.6 171.5

75 196.7 172.1 211.3 138.7 231.3 81.2 189.4 167.0 203.4 134.3 222.7 77.7 181.9 161.7 195.2 129.7 213.9 73.9

80 205.0 192.7 214.9 169.8 232.9 129.8 197.7 187.1 207.0 164.8 224.4 125.5 190.1 181.4 199.0 159.7 215.7 121.1

85 214.5 209.3 221.6 192.9 234.5 164.0 207.1 203.4 213.7 187.4 226.1 159.2 199.4 197.2 205.6 181.8 217.5 154.2

90 224.5 223.5 229.9 211.0 239.6 189.3 216.9 216.9 222.0 205.2 231.2 184.0 209.2 209.2 213.8 199.2 222.6 178.6

75 200.0 177.7 213.3 143.1 231.9 84.3 192.4 172.2 205.0 138.4 223.0 80.4 184.6 166.6 196.5 133.5 213.9 76.4

80 209.1 199.3 217.9 175.4 234.5 134.2 201.5 193.4 209.7 170.1 225.7 129.6 193.7 187.3 201.3 164.7 216.7 124.9

85 219.3 216.7 225.4 199.4 237.1 169.6 211.6 210.4 217.2 193.6 228.5 164.4 203.7 203.7 208.8 187.8 219.6 159.2

90 229.9 229.9 234.4 218.4 243.1 195.9 222.0 222.0 226.2 212.3 234.4 190.3 214.0 214.0 217.7 206.0 225.5 184.6

75 202.2 182.2 214.1 146.4 231.3 86.3 194.3 176.4 205.5 141.4 222.2 82.2 186.2 170.5 196.7 136.2 213.5 77.8

8800

80 212.2 204.7 219.7 179.9 235.0 137.6 204.3 198.5 211.3 174.3 226.0 132.7 196.1 192.1 202.6 168.5 217.0 127.7

85 223.1 223.0 228.1 204.8 238.7 174.1 215.0 215.0 219.6 198.8 229.7 168.7 206.8 206.8 211.0 192.6 220.5 163.1

90 234.2 234.2 237.8 224.7 245.6 201.4 226.0 226.0 229.3 218.3 236.6 195.5 217.6 217.6 220.5 211.7 227.4 189.5

75 203.4 185.6 216.0 148.7 233.2 87.3 195.1 179.5 207.0 143.3 224.1 82.8 186.7 173.3 198.0 137.9 213.0 78.1

9600

80 214.2 209.1 220.5 183.2 236.2 139.9 205.9 202.6 211.8 177.4 227.0 134.7 197.5 195.9 202.8 171.3 218.0 129.4

85 225.7 225.7 229.8 209.2 239.2 177.5 217.4 217.4 221.0 202.9 229.9 171.8 208.9 208.9 212.0 196.4 223.0 165.9

90 237.4 237.4 240.2 229.9 246.9 205.8 228.9 228.9 231.3 223.2 237.6 199.6 220.2 220.2 222.3 216.3 228.1 193.3

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

(a)For 4000, 4800, and 5600 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

RT-PRC028AC-EN 69

Performance Data

Table 39. Gross cooling capacities 20 tons three phase dehumidification (hot gas reheat) option high efficiency

T/YHD240G3,4,W (Digit 22 = B)

Air

Flow cfm (a)

4000

5200

6400

7200

8000

8800

9600

85

61

Ambient Temperature

95

Entering Wet Bulb

67 73

105

Ent

DB 61 67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 203.7 145.0 228.5 96.2 259.7 90.9 193.4 139.5 217.0 92.5 247.0 86.4 182.4 133.4 204.8 88.3 233.5 81.7

80 206.0 171.4 227.3 134.7 254.8 89.2 195.8 164.9 215.8 130.0 242.1 84.7 184.8 157.8 203.6 124.6 228.6 80.0

85 210.1 191.8 227.8 167.0 251.7 118.8 199.9 184.2 216.3 161.3 239.0 114.9 189.0 176.0 204.1 154.9 225.5 110.4

90 216.1 206.0 230.1 193.2 250.4 157.1 205.9 197.4 218.6 186.5 237.7 152.1 194.9 188.2 206.4 179.1 224.2 146.5

75 218.6 159.9 241.6 108.8 271.0 94.8 207.5 153.9 229.3 104.6 257.4 90.1 195.7 147.3 216.2 99.8 243.0 85.1

80 222.2 188.3 241.6 149.2 267.3 93.6 211.1 181.3 229.3 144.0 253.7 88.8 199.3 173.6 216.2 138.2 239.4 83.8

85 227.6 210.6 243.4 183.5 265.5 133.0 216.5 202.5 231.1 177.3 251.9 128.6 204.7 193.8 218.0 170.4 237.6 123.5

90 234.8 226.8 247.0 211.7 265.4 173.2 223.7 217.7 234.6 204.4 251.9 167.7 211.9 207.9 221.6 196.5 237.5 161.6

75 231.3 173.2 252.5 119.7 280.0 98.0 219.3 166.7 239.3 115.1 265.5 92.9 206.6 159.6 225.3 109.8 250.3 87.6

80 236.2 203.6 253.7 162.1 277.6 97.2 224.2 196.0 240.5 156.4 263.2 93.4 211.5 187.9 226.6 150.1 248.0 88.8

85 242.8 227.8 256.8 198.4 277.0 145.5 230.9 219.3 243.6 191.6 262.6 140.6 218.2 210.0 229.7 184.2 247.4 135.0

90 251.2 245.9 261.6 228.5 278.2 187.7 239.3 236.3 248.4 220.7 263.8 181.7 226.7 226.1 234.5 212.3 248.6 175.1

75 238.5 181.2 258.5 126.2 284.8 99.7 226.0 174.4 244.7 121.2 269.7 94.4 212.7 166.9 230.2 115.5 253.9 88.9

80 244.2 212.9 260.6 169.9 283.2 103.4 231.7 205.0 246.8 163.8 268.2 99.2 218.5 196.5 232.3 157.1 252.4 94.3

85 251.7 238.4 264.4 207.4 283.5 153.0 239.2 229.5 250.7 200.3 268.4 147.7 226.0 220.0 236.2 192.6 252.7 141.8

90 261.0 257.9 270.1 238.9 285.5 196.5 248.5 247.9 256.3 230.7 270.5 190.2 235.3 235.3 241.9 222.0 254.7 183.2

75 244.8 188.5 263.5 131.9 288.6 101.0 231.7 181.3 249.2 126.5 272.9 95.5 217.8 173.5 234.1 120.5 256.6 89.8

80 251.3 221.5 266.4 176.9 287.8 108.9 238.2 213.2 252.1 170.5 272.2 104.3 224.4 204.4 237.0 163.5 255.9 99.1

85 259.6 248.3 271.1 215.8 288.9 159.8 246.5 239.1 256.8 208.3 273.3 154.2 232.7 229.2 241.7 200.2 257.0 147.9

90 269.7 269.0 277.6 248.5 291.8 204.5 256.7 256.7 263.3 240.0 276.2 197.9 242.9 242.9 248.2 230.9 259.9 190.6

75 250.0 195.1 267.5 136.9 291.3 102.0 236.3 187.5 252.6 131.2 275.2 96.3 221.9 179.4 236.9 124.9 258.2 90.4

80 257.4 229.3 271.3 183.2 291.5 113.6 243.7 220.8 256.4 176.5 275.3 108.7 229.3 211.6 240.7 169.1 258.4 103.2

85 266.5 257.5 276.8 223.4 293.4 165.8 252.9 247.9 261.9 215.6 277.2 159.9 238.5 237.7 246.3 207.2 260.3 153.3

90 277.5 277.5 284.1 257.4 297.1 211.9 263.8 263.8 269.2 248.6 280.9 204.9 249.5 249.5 253.6 239.2 264.0 197.3

75 254.3 200.9 270.6 141.2 293.1 102.6 240.0 193.1 255.1 135.2 276.4 96.7 225.0 184.6 238.8 128.5 258.9 90.6

80 262.5 236.5 275.1 188.8 294.1 117.7 248.2 227.6 259.7 181.7 277.4 112.4 233.3 218.1 243.4 174.0 259.9 106.5

85 272.4 266.0 281.5 230.3 296.8 171.2 258.2 256.0 266.0 222.2 280.1 164.9 243.3 243.3 249.8 213.4 262.6 157.9

90 284.2 284.2 289.6 265.7 301.4 218.6 270.0 270.0 274.2 256.5 284.7 211.2 255.1 255.1 258.0 246.7 267.2 203.2

70 RT-PRC028AC-EN

Performance Data

Table 39. Gross cooling capacities 20 tons three phase dehumidification (hot gas reheat) option high efficiency

T/YHD240G3,4,W (Digit 22 = B)

Air

Flow cfm (b)

Ent

DB 61

115

67 73 61

Ambient Temperature

120

Entering Wet Bulb

67 73 61

125

67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

4000

5200

6400

7200

75 170.7 126.7 191.8 83.3 219.2 76.7 164.5 123.1 185.0 80.6 211.8 74.1 158.2 119.3 178.1 77.8 204.2 71.5

80 173.1 150.0 190.6 118.7 214.4 75.0 166.9 145.9 183.8 115.5 207.0 72.4 160.6 141.6 176.8 112.1 199.4 69.8

85 177.3 167.2 191.1 147.9 211.3 105.2 171.1 162.6 184.4 144.2 203.9 102.4 164.8 157.7 177.4 140.3 196.3 99.4

90 183.2 178.3 193.5 171.0 210.0 140.3 177.1 173.1 186.7 166.8 202.6 137.0 170.8 167.8 179.8 162.3 195.1 133.5

75 183.1 140.0 202.3 94.4 227.9 79.8 176.5 136.2 195.1 91.4 220.1 77.0 169.7 132.1 187.7 88.3 212.0 74.2

80 186.7 165.3 202.4 131.7 224.3 78.5 180.1 160.9 195.2 128.2 216.5 75.8 173.4 156.4 187.8 124.6 208.4 73.0

85 192.1 184.5 204.2 162.9 222.5 117.8 185.6 179.6 197.0 158.9 214.7 114.7 178.8 174.5 189.6 154.7 206.7 111.5

90 199.4 197.5 207.8 187.9 222.5 154.9 192.8 192.1 200.6 183.4 214.6 151.3 186.1 186.1 193.2 178.7 206.6 147.5

75 193.2 151.8 210.6 103.8 234.3 82.0 186.2 147.7 203.0 100.6 226.1 79.1 179.0 143.4 195.2 97.2 217.6 76.2

80 198.1 179.1 211.9 143.1 232.0 83.6 191.1 174.4 204.3 139.3 223.7 80.8 183.9 169.6 196.5 135.4 215.3 77.8

85 204.8 200.2 215.0 176.2 231.4 128.8 197.8 195.0 207.4 172.0 223.2 125.5 190.6 189.7 199.5 167.5 214.8 122.0

90 213.3 213.3 219.8 203.2 232.7 167.8 206.3 206.3 212.2 198.5 224.4 164.0 199.1 199.1 204.4 193.5 216.0 160.0

75 198.7 158.8 214.9 109.2 237.4 83.1 191.4 154.5 207.0 105.8 228.9 80.1 183.9 150.0 198.9 102.3 220.1 77.0

80 204.4 187.3 217.0 149.8 235.9 88.8 197.2 182.5 209.1 145.9 227.4 85.8 189.7 177.5 201.0 141.8 218.6 82.6

85 212.0 209.8 220.9 184.2 236.2 135.3 204.7 204.4 213.0 179.8 227.6 131.7 197.2 197.2 204.9 175.2 218.9 128.1

90 221.3 221.3 226.6 212.5 238.2 175.6 214.0 214.0 218.7 207.6 229.7 171.6 206.6 206.6 210.6 202.5 221.0 167.4

8000

8800

75 203.2 165.0 218.2 113.9 239.5 83.8 195.7 160.6 210.0 110.3 230.6 80.7 187.9 155.9 201.6 106.6 221.6 77.6

80 209.8 194.9 221.2 155.8 238.8 93.2 202.2 189.9 213.0 151.7 230.0 90.1 194.5 184.7 204.6 147.5 221.0 86.7

85 218.2 218.2 225.9 191.5 239.9 141.0 210.6 210.6 217.7 186.9 231.1 137.3 202.9 202.9 209.3 182.2 222.1 133.5

90 228.3 228.3 232.4 221.2 242.8 182.7 220.8 220.8 224.2 216.0 234.0 178.4 213.0 213.0 215.9 210.8 225.0 174.1

75 206.8 170.6 220.5 117.9 240.6 84.2 198.9 165.9 212.0 114.2 231.4 81.0 190.9 161.1 203.3 110.3 222.1 77.7

80 214.2 201.7 224.3 161.1 240.7 97.0 206.3 196.6 215.8 156.8 231.6 93.6 198.3 191.2 207.1 152.4 222.3 90.1

85 223.4 223.4 229.9 198.1 242.7 146.0 215.5 215.5 221.4 193.3 233.6 142.2 207.5 207.5 212.7 188.4 224.3 138.1

90 234.3 234.3 237.2 229.1 246.4 189.0 226.5 226.5 228.8 223.8 237.3 184.6 217.9 217.9 220.1 218.3 228.0 180.1

9600

75 209.3 175.4 221.8 121.2 240.6 84.2 201.2 170.6 213.0 117.3 231.2 80.9 192.8 165.6 204.1 113.2 221.6 77.6

80 217.5 207.9 226.4 165.6 241.6 100.0 209.4 202.5 217.7 161.2 232.2 96.5 201.1 197.0 208.7 156.6 222.6 92.8

85 227.6 227.6 232.8 204.0 244.4 150.4 219.4 219.4 224.1 199.1 235.0 146.3 211.1 211.1 215.1 194.0 225.4 142.1

90 239.4 239.4 241.0 236.2 249.0 194.6 230.0 230.0 232.3 230.8 239.6 190.1 223.3 223.3 223.3 223.3 230.0 185.3

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity (a)

(a)For 4000, and 5200 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

(b)For 4000, and 5200 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

RT-PRC028AC-EN 71

Performance Data

Table 40. Gross cooling capacities 25 tons three phase high efficiency T/YH*300G3,4,W (stage 1)

Air

Flow cfm (a)

Ambient Temperature

85 95

Ent Entering Wet Bulb

DB 61 67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

4000

5000

6000

7000

8000

75

80

85

90

75

80

85

90

75

80

80.5 78.0 85.7 62.9 93.7 32.5 75.1 73.7 80.0 59.3 87.7 29.5

85.2 85.2 87.8 78.2 94.6 59.2 79.7 79.7 82.1 74.1 88.6 55.8

90.1 90.1 91.3 88.2 95.4 76.5 84.6 84.6 85.6 83.8 89.4 72.6

94.9 94.9 95.3 95.3 97.8 88.2 89.3 89.3 89.5 89.5 91.8 83.9

83.0 82.1 87.6 67.4 95.0 37.4 77.3 77.3 81.6 63.4 88.7 34.1

88.1 88.1 90.2 82.7 96.3 64.2 82.3 82.3 84.2 78.3 90.0 60.3

93.3 93.3 94.0 92.9 97.6 81.6 87.5 87.5 88.0 88.0 91.3 77.2

98.3 98.3 98.3 98.3 100.3 93.3 92.0 92.0 92.2 92.2 94.0 88.7

85.1 85.1 89.0 71.1 95.7 41.5 79.1 79.1 82.7 66.7 89.2 37.8

90.5 90.5 92.0 86.5 97.5 68.3 84.5 84.5 85.8 81.6 90.9 64.1

85

90

75

80

96.0 96.0 96.2 96.2 99.2 85.8 89.9 89.9 89.9 89.9 92.7 81.1

99.8 99.8 100.8 100.8 102.3 97.7 94.0 94.0 94.4 94.4 95.8 92.6

86.6 86.6 89.8 74.0 96.0 44.9 80.3 80.3 83.3 69.2 89.5 40.7

92.4 92.4 93.4 89.5 98.2 71.7 86.1 86.1 86.8 84.2 91.3 67.0

85 96.0 96.0 97.9 97.9 100.4 89.2 91.0 91.0 91.3 91.3 93.6 84.1

90 101.0 101.0 102.8 102.8 103.8 101.2 95.8 95.8 96.1 96.1 97.0 95.8

75

80

87.7 87.7 90.2 76.1 98.2 47.4 81.1 81.1 83.3 70.9 91.0 42.9

93.8 93.8 94.2 91.6 98.4 74.2 87.2 87.2 87.3 86.0 92.0 69.1

85 98.4 98.4 99.1 99.1 101.0 91.8 92.0 92.0 92.2 92.2 93.9 86.3

90 103.7 103.7 104.2 104.2 104.8 104.0 96.0 96.0 97.3 97.3 97.7 97.7

8750

75

80

88.1 88.1 91.0 77.1 98.5 48.8 81.3 81.3 84.0 71.6 92.0 43.9

94.0 94.0 94.5 92.7 99.0 75.6 87.3 87.3 87.4 86.7 93.5 70.2

85 99.0 99.0 99.7 99.7 101.2 93.2 92.4 92.4 92.6 92.6 95.0 87.4

90 104.0 104.0 105.0 105.0 105.2 105.2 97.0 97.0 97.8 97.8 97.9 97.9

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

(a)For 4000, 5000, 6000, and 7000 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and

YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

72 RT-PRC028AC-EN

Performance Data

Table 41. Gross cooling capacities 25 tons three phase high efficiency T/YH*300G3,4,W (stage 2)

Air

Flow cfm (a)

Ambient Temperature

85 95

Ent Entering Wet Bulb

DB 61 67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

4000

5000

6000

7000

8000

75 135.6 118.7 146.9 92.7 156.4 43.8 127.9 113.4 138.5 88.3 147.4 40.5

80 140.7 132.3 148.2 116.5 159.0 84.6 132.9 126.3 139.8 111.3 150.0 80.4

85 146.9 142.2 152.0 132.5 161.5 111.5 138.9 135.7 143.6 126.7 152.5 106.4

90 153.5 150.3 157.2 144.1 164.1 129.8 145.3 143.4 148.6 137.8 155.0 124.2

75 141.2 127.5 151.3 101.4 165.2 52.4 133.0 121.6 142.4 96.4 155.5 48.5

80 147.0 141.5 153.5 125.6 165.8 93.7 138.7 134.9 144.5 119.9 156.2 88.8

85 153.7 151.8 157.9 142.1 166.4 121.0 145.2 144.8 149.0 135.7 156.8 115.4

90 160.7 160.3 163.6 154.1 169.7 139.7 152.0 152.0 154.5 147.2 160.0 133.5

75 145.8 134.8 154.6 108.6 167.3 59.5 137.0 128.2 145.1 103.0 157.1 55.0

80 152.2 149.2 157.6 133.2 168.7 101.2 143.4 142.0 148.2 126.9 158.6 95.8

85 159.4 159.4 162.7 150.1 170.2 128.9 150.4 150.4 153.3 143.2 160.1 122.7

90 166.8 166.8 169.0 162.6 174.1 148.1 157.6 157.6 159.3 155.1 164.0 141.3

75 149.2 140.5 156.8 114.2 168.3 65.0 140.0 133.4 146.9 108.1 157.6 59.9

80 156.3 155.3 160.7 139.3 170.6 107.2 147.0 147.0 150.8 132.4 160.0 101.2

85 164.0 164.0 166.5 156.7 172.9 135.4 154.6 154.6 156.5 149.1 162.3 128.6

90 171.8 171.8 173.2 169.5 177.5 155.0 162.1 162.1 163.1 161.4 166.8 147.6

75 151.6 144.7 158.0 118.3 169.0 69.0 141.9 137.0 147.5 111.6 158.0 63.4

80 159.4 159.4 162.7 143.9 171.4 111.7 149.6 149.6 152.2 136.4 160.3 105.1

85 167.6 167.6 169.1 161.6 174.5 140.3 157.6 157.6 158.7 153.5 163.5 132.9

90 175.7 175.7 176.4 174.9 179.8 160.3 165.5 165.5 165.7 165.7 168.6 152.3

8750

75 152.7 146.8 158.1 120.4 171.3 71.0 142.6 138.7 147.9 113.2 159.6 64.9

80 161.0 161.0 163.4 146.3 172.0 114.0 150.8 150.8 152.7 138.3 161.0 107.0

85 169.5 169.5 170.4 164.3 175.1 142.9 159.2 159.2 159.6 155.8 163.6 135.1

90 178.0 178.0 178.0 177.9 180.8 163.3 166.0 167.4 167.0 167.0 169.3 154.9

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

(a)For 4000, 5000, 6000, and 7000 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and

YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

RT-PRC028AC-EN 73

Performance Data

Table 42. Gross cooling capacities 25 tons three phase high efficiency T/YH*300G3,4,W (stage 3)

Air

Flow cfm (a)

Ambient Temperature

85 95

Ent Entering Wet Bulb

DB 61 67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

4000

5000

6000

7000

8000

75 188.9 150.3 205.8 121.4 226.6 71.4 179.7 145.2 195.3 117.2 214.8 68.3

80 193.3 167.2 208.8 147.0 228.3 111.8 184.1 161.3 198.4 142.0 216.6 107.6

85 199.5 180.7 211.8 165.8 230.0 140.0 190.3 174.2 201.4 160.0 218.4 135.0

90 207.0 192.0 217.1 180.3 231.7 160.6 197.5 185.0 206.7 174.0 220.2 154.9

75 199.5 162.2 218.5 131.4 234.4 79.3 189.4 156.2 206.9 126.4 221.8 75.4

80 204.9 180.5 219.0 158.8 237.2 121.8 194.9 173.8 207.8 153.0 224.7 116.9

85 212.0 195.3 223.1 179.1 240.0 151.8 202.0 188.0 211.9 172.5 227.6 146.0

90 220.2 207.7 229.3 194.9 242.7 173.9 209.9 199.9 218.0 187.7 230.4 167.4

75 208.4 172.8 225.7 140.2 247.8 86.1 197.5 166.0 213.4 134.4 234.0 81.4

80 214.8 192.7 227.6 169.4 248.1 130.7 204.1 185.1 215.6 162.7 234.6 124.9

85 222.8 208.7 232.7 191.2 248.3 162.4 212.0 200.6 220.8 183.8 235.1 155.8

90 231.7 222.2 239.8 208.3 252.1 186.0 220.6 213.6 227.8 200.3 239.0 178.7

75 215.6 182.2 231.3 147.8 251.9 91.6 204.0 174.6 218.2 141.2 237.3 86.1

80 223.2 203.6 234.5 178.8 253.4 138.3 211.6 195.2 221.7 171.3 239.1 131.7

85 232.0 220.9 240.7 202.1 255.0 171.8 220.4 211.9 228.0 193.8 241.0 164.4

90 241.6 235.5 248.7 220.5 259.9 197.0 229.7 226.1 235.9 211.7 246.0 188.8

75 221.2 190.4 235.3 154.2 254.3 96.0 208.8 181.9 221.3 146.7 238.9 89.6

80 229.8 213.3 239.8 187.0 257.1 144.7 217.5 204.1 226.2 178.6 242.0 137.3

85 239.6 231.8 247.1 211.8 260.0 180.0 227.1 222.1 233.5 202.7 245.2 171.7

90 249.9 247.6 255.9 231.5 266.0 206.7 237.2 237.2 242.3 221.8 251.3 197.7

8750

75 224.3 195.7 237.2 158.2 255.0 98.4 211.3 186.6 222.6 150.1 239.0 91.4

80 233.7 219.7 242.7 192.3 258.9 148.8 220.8 209.9 228.5 183.3 243.1 140.7

85 244.1 239.3 250.8 218.2 262.7 185.4 231.1 228.9 236.6 208.5 247.3 176.5

90 255.0 255.0 260.3 238.9 269.5 213.2 241.7 241.7 246.1 228.6 254.2 203.5

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

(a)For 4000, 5000, 6000, and 7000 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and

YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

74 RT-PRC028AC-EN

Performance Data

Table 43. Gross cooling capacities 25 tons three phase high efficiency T/YH*300G3,4,W (full load)

Air

Flow cfm (a)

5000

6000

7000

8000

9000

10000

11000

85

Ambient Temperature

95 105

Ent Entering Wet Bulb

DB 61 67 73 61 67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 244.4 192.5 271.7 152.0 293.2 82.9 232.4 184.9 257.9 146.3 278.4 79.2 219.4 176.7 243.2 139.9 262.5 74.8

80 250.0 215.3 270.3 187.5 295.4 139.2 238.0 206.6 256.8 180.3 280.5 133.8 225.0 197.3 242.2 172.5 264.5 127.7

85 258.5 233.2 274.2 213.2 297.6 178.4 246.2 223.6 260.6 204.8 282.6 171.4 232.8 213.3 246.0 195.8 266.5 163.9

90 268.6 248.1 281.3 232.8 299.8 206.6 255.9 237.7 267.4 223.5 284.7 198.6 242.1 226.7 252.6 213.6 268.6 189.9

75 255.4 206.3 281.1 164.5 301.6 93.9 242.7 198.1 266.6 158.1 286.0 89.5 228.9 189.1 251.1 150.9 269.3 84.3

80 262.0 230.2 280.9 201.3 304.7 151.7 249.2 220.8 266.6 193.4 289.1 145.6 235.5 210.7 251.4 184.8 272.3 138.7

85 271.2 249.0 285.7 228.0 307.8 192.1 258.2 238.7 271.4 219.0 292.1 184.5 244.1 227.7 256.1 209.2 275.3 176.2

90 282.0 264.7 293.6 248.6 311.0 221.4 268.5 253.6 279.0 238.6 295.1 212.7 253.9 241.8 263.4 227.9 278.3 203.3

75 265.0 218.8 289.1 175.7 308.5 103.5 251.6 209.8 273.9 168.5 292.2 98.3 237.1 200.1 257.7 160.6 274.8 92.5

80 272.6 243.7 290.1 213.7 312.6 162.9 259.1 233.6 275.1 205.1 296.2 156.0 244.6 222.8 259.1 195.8 278.8 148.4

85 282.6 263.5 295.9 241.5 316.7 204.5 268.8 252.4 280.9 231.7 300.2 196.1 254.0 240.6 264.8 221.2 282.7 187.1

90 293.9 279.9 304.6 263.0 320.8 234.9 279.7 268.1 289.2 252.2 304.2 225.4 264.4 255.6 272.9 240.8 286.7 215.3

75 273.3 229.9 295.7 185.4 324.1 111.8 259.1 220.1 279.8 177.5 306.4 105.9 243.9 209.7 262.8 168.9 287.8 99.3

80 281.8 255.9 298.0 224.7 324.2 172.6 267.6 245.0 282.2 215.4 306.7 165.0 252.3 233.5 265.5 205.3 288.3 156.6

85 292.5 276.6 304.7 253.7 324.2 215.6 278.0 264.7 288.9 243.1 307.0 206.4 262.5 252.2 272.1 231.9 288.7 196.7

90 304.5 293.8 314.1 276.0 329.2 247.0 289.5 281.2 298.1 264.5 311.9 236.8 273.5 268.0 281.0 252.4 293.6 225.9

75 280.1 239.6 301.0 193.8 327.8 118.7 265.2 229.1 284.3 185.2 309.4 112.0 249.3 218.0 266.6 175.8 290.0 104.7

80 289.6 266.7 304.4 234.4 329.1 181.0 274.7 255.1 288.0 224.3 310.9 172.6 258.7 242.8 270.5 213.5 291.7 163.6

85 301.1 288.3 312.1 264.4 330.3 225.2 285.9 275.7 295.6 253.1 312.3 215.4 269.6 262.5 278.1 241.2 293.3 204.9

90 313.7 306.3 322.3 287.7 336.3 257.8 297.9 293.0 305.5 275.5 318.3 246.8 281.2 279.0 287.7 262.6 299.2 235.1

75 285.6 247.9 304.9 200.8 330.2 124.2 270.0 236.7 287.4 191.4 311.0 116.8 253.3 224.8 269.0 181.3 290.9 108.7

80 296.1 276.1 309.5 242.7 332.6 188.0 280.4 263.8 292.3 231.9 313.7 178.9 263.6 250.7 274.1 220.3 293.7 169.1

85 308.3 298.6 318.2 273.8 335.0 233.5 292.3 285.3 300.9 261.7 316.3 222.9 275.3 271.3 282.6 249.0 296.6 211.7

90 321.4 317.4 329.1 298.0 342.0 267.1 305.0 303.3 311.6 285.0 323.2 255.4 287.5 287.5 293.0 271.4 303.4 243.0

75 289.7 254.9 307.3 206.5 331.1 128.3 273.3 243.0 289.2 196.3 311.2 120.2 255.9 230.3 270.0 185.5 291.5 111.3

80 301.1 284.2 313.2 249.6 334.7 193.7 284.7 271.1 295.2 238.0 315.1 183.8 267.2 257.3 276.3 225.8 294.4 173.2

85 314.1 307.6 322.8 281.8 338.3 240.4 297.4 293.5 304.8 269.0 318.9 229.1 279.6 278.8 285.8 255.6 298.4 217.1

90 327.9 327.1 334.5 306.9 346.3 275.1 310.7 310.7 316.3 293.2 326.8 262.7 292.5 292.5 297.0 278.8 306.2 249.5

RT-PRC028AC-EN 75

Performance Data

Table 43. Gross cooling capacities 25 tons three phase high efficiency T/YH*300G3,4,W (full load)

Air

Flow cfm

(a)

5000

115

Ambient Temperature

120 125

Ent

DB 61 67 73 61

Entering Wet Bulb

67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 205.4 167.9 227.4 132.8 245.5 69.7 198.0 163.2 219.2 129.0 236.7 66.9 190.4 158.3 210.7 125.0 227.6 64.0

80 210.9 187.2 226.7 164.0 247.5 120.9 203.5 182.0 218.5 159.5 238.6 117.2 195.9 176.5 210.1 154.8 229.5 113.4

85 218.5 202.3 230.4 186.2 249.5 155.7 211.0 196.6 222.2 181.1 240.6 151.3 203.2 190.7 213.8 175.8 231.4 146.8

90 227.3 215.0 236.7 202.9 251.5 180.5 219.5 208.8 228.4 197.4 242.5 175.5 211.5 202.5 219.8 191.6 233.4 170.4

75 214.2 179.5 234.6 143.1 251.7 78.5 206.5 174.4 226.0 138.9 242.5 75.3 198.5 169.2 217.1 134.6 233.0 72.0

6000

7000

8000

9000

10000

80 220.7 199.9 235.1 175.6 254.6 131.2 212.9 194.3 226.6 170.7 245.4 127.1 204.9 188.5 217.8 165.6 235.9 122.9

85 229.0 216.0 239.7 198.8 257.5 167.2 221.1 209.8 231.2 193.3 248.3 162.5 213.0 203.6 222.4 187.7 238.8 157.6

90 238.4 229.3 246.8 216.5 260.5 193.1 230.3 222.9 238.1 210.6 251.2 187.8 221.9 216.2 229.2 204.5 241.6 182.3

75 221.7 189.7 240.4 152.0 256.4 85.9 213.6 184.3 231.5 147.5 246.8 82.4 205.2 178.7 222.2 142.8 237.0 78.7

80 229.1 211.3 242.1 185.8 260.3 140.1 220.9 205.2 233.2 180.5 250.7 135.7 212.6 199.1 224.1 175.1 240.8 131.1

85 238.2 228.2 247.7 210.1 264.2 177.4 229.9 221.7 238.8 204.3 254.6 172.3 221.4 215.1 229.6 198.2 244.7 167.0

90 248.2 242.4 255.6 228.7 268.1 204.4 239.7 235.5 246.5 222.4 258.4 198.7 230.9 228.5 237.2 215.9 248.5 192.8

75 227.7 198.6 244.9 159.6 268.2 92.0 219.2 192.8 235.5 154.6 258.0 88.1 210.5 186.8 225.9 149.6 247.5 84.0

80 236.1 221.2 247.7 194.6 268.8 147.6 227.6 214.8 238.5 189.0 258.7 142.8 218.8 208.3 229.0 183.2 248.4 137.9

85 245.9 239.0 254.3 220.0 269.5 186.2 237.3 232.2 245.0 213.8 259.5 180.8 228.4 225.2 235.5 207.4 249.2 175.1

90 256.5 254.0 262.9 239.5 274.3 214.3 247.7 246.8 253.5 232.9 264.3 208.2 238.5 238.5 243.9 226.0 254.0 202.0

75 232.4 206.1 247.9 165.7 269.7 96.6 223.5 200.0 238.2 160.5 259.1 92.4 214.4 193.6 228.2 155.0 248.3 87.9

80 241.7 229.8 252.0 202.0 271.5 153.8 232.8 223.0 242.4 196.0 261.0 148.6 223.7 216.1 232.5 189.9 250.3 143.3

85 252.3 248.5 259.5 228.5 273.4 193.7 243.3 241.3 249.9 221.9 263.0 187.8 234.1 233.9 240.0 215.2 252.4 181.8

90 263.5 263.5 268.9 249.0 279.2 222.8 254.3 254.3 259.1 241.9 268.8 216.4 244.8 244.8 249.1 234.7 258.1 209.8

75 235.6 212.3 249.6 170.5 269.8 99.9 226.4 205.7 239.5 164.9 260.5 95.3 217.0 199.0 229.2 159.1 249.2 90.5

80 245.9 237.0 254.9 208.1 272.8 158.6 236.7 229.9 244.9 201.7 262.0 153.1 227.2 222.6 234.6 195.2 250.9 147.4

85 257.3 256.6 263.3 235.7 275.9 199.7 247.9 247.9 253.3 228.7 265.1 193.5 238.3 238.3 243.1 221.6 254.1 187.1

90 269.1 269.1 273.5 257.1 282.7 229.9 259.5 259.5 263.4 249.6 271.9 223.2 249.6 249.6 253.0 242.0 260.9 216.2

75 237.5 217.0 249.9 174.0 271.0 101.8 228.0 210.1 240.5 167.9 261.3 96.8 218.1 203.0 229.8 161.7 252.3 91.6

11000

80 248.8 242.8 256.3 212.8 274.0 162.0 239.2 235.3 246.0 206.1 263.6 156.1 229.3 227.7 235.4 199.2 253.4 150.1

85 260.9 260.9 265.8 241.4 277.0 204.4 251.2 251.2 255.4 234.1 265.9 197.9 241.2 241.2 244.8 226.6 254.5 191.1

90 273.3 273.3 276.7 263.8 284.7 235.7 263.3 263.3 266.2 256.0 273.6 228.5 253.1 253.1 255.4 248.0 262.2 221.2

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

(a)For 5000, 6000, and 7000 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

76 RT-PRC028AC-EN

Performance Data

Table 44. Gross cooling capacities 25 tons three phase dehumidification (hot gas reheat) option high efficiency

T/YHD300G3,4,W (Digit 22 = B)

Air

Flow cfm (a)

5000

6500

8000

9000

10000

10500

11000

85

Ambient Temperature

95 105

Ent Entering Wet Bulb

DB 61 67 73 61 67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 237.6 170.2 266.9 137.2 298.3 101.7 226.6 164.3 254.2 130.9 284.0 95.4 215.0 158.1 241.1 124.7 269.5 89.1

80 237.8 197.2 266.6 164.6 298.3 130.4 226.8 191.3 254.2 158.7 284.5 124.4 215.2 184.8 241.2 152.8 269.5 117.9

85 238.0 223.6 266.8 192.2 298.3 157.9 227.3 217.6 254.4 186.3 284.5 150.8 216.0 211.0 241.3 180.0 269.3 145.0

90 244.4 244.4 267.0 219.3 298.3 185.7 235.5 235.5 254.6 213.1 284.2 179.6 226.0 225.9 241.7 206.9 269.5 173.2

75 251.7 194.9 281.3 151.1 313.6 103.1 239.4 188.7 267.3 144.8 297.7 96.7 226.4 182.1 252.8 138.0 281.0 90.0

80 252.2 230.1 281.5 185.9 313.9 142.8 239.8 223.7 267.7 179.8 299.0 134.7 227.0 216.7 253.1 173.7 281.5 129.6

85 257.9 257.7 282.0 223.2 313.7 176.7 248.0 247.9 268.2 217.0 297.6 170.9 237.2 237.2 253.6 210.5 281.8 163.8

90 272.5 272.4 282.5 258.1 314.3 213.5 262.0 261.9 268.8 251.7 298.7 207.5 250.8 250.7 254.4 244.6 282.3 201.7

75 260.7 217.8 290.3 162.9 322.7 103.2 247.6 211.8 276.0 155.2 305.8 96.6 233.7 205.3 260.1 149.5 288.2 90.1

80 262.3 259.5 291.1 207.3 323.0 153.7 249.7 247.8 276.3 201.2 306.2 146.9 238.4 236.1 260.8 195.0 288.7 139.6

85 277.8 277.7 291.9 252.8 324.9 192.8 266.3 266.3 277.0 246.3 307.1 188.1 254.2 254.2 261.6 239.2 289.8 182.0

90 293.7 293.6 293.9 292.8 324.5 241.9 281.8 281.8 280.5 277.0 307.8 235.5 269.1 269.1 269.3 268.3 290.6 229.1

75 265.2 233.5 294.9 170.4 326.8 103.2 251.5 226.7 279.5 163.8 309.5 97.1 237.2 219.2 263.4 156.9 291.4 90.9

80 269.5 264.6 294.7 223.9 328.3 159.2 259.7 259.5 280.4 215.9 310.2 152.6 247.7 247.6 264.4 209.5 292.4 145.4

85 288.2 288.1 296.6 271.4 328.6 206.7 276.1 275.9 281.4 264.7 311.4 201.1 263.2 263.2 265.9 256.5 293.6 196.0

90 302.2 301.5 303.9 299.6 329.4 260.3 292.3 292.2 292.9 292.7 311.8 255.6 278.9 278.9 279.6 279.5 294.5 248.5

75 268.8 247.3 298.4 178.1 330.1 104.0 254.7 240.1 282.6 171.2 312.4 98.0 240.0 233.0 266.2 164.6 293.6 91.6

80 279.8 279.8 299.5 236.4 331.3 165.7 267.6 267.5 284.2 228.6 313.0 159.1 254.0 254.5 267.3 223.1 295.4 151.0

85 297.2 297.2 300.7 289.4 332.4 221.0 284.4 284.3 285.0 281.9 314.7 215.8 270.9 270.7 269.0 265.0 296.6 209.8

90 315.0 315.0 315.6 315.6 333.5 279.6 301.5 301.5 302.1 301.9 316.4 271.6 287.3 287.2 287.9 287.6 297.7 265.0

75 270.3 254.1 300.1 181.8 332.2 103.2 256.1 246.9 283.8 175.0 313.4 98.3 241.2 239.6 267.4 168.8 294.6 91.9

80 283.5 283.4 301.2 243.4 332.8 168.0 271.0 270.7 285.1 236.6 314.6 149.6 257.8 257.6 268.5 229.6 296.6 153.9

85 301.2 301.2 302.5 297.8 334.1 228.5 287.5 287.2 286.5 283.2 316.3 222.6 274.3 274.2 271.3 263.2 297.9 216.4

90 319.3 319.3 320.0 319.8 335.2 288.2 305.5 305.3 306.2 305.9 317.5 280.7 291.0 290.9 291.6 291.5 299.1 272.8

75 271.7 260.7 301.5 185.8 332.6 105.1 257.3 253.5 285.1 179.1 314.5 98.9 242.4 239.2 268.5 173.1 295.9 92.6

80 287.0 286.7 302.6 250.0 334.2 170.7 273.9 273.7 286.4 243.2 316.9 162.5 260.6 260.6 269.7 235.9 297.6 156.7

85 305.1 304.9 304.5 304.2 335.6 235.1 291.3 291.2 288.4 280.2 317.6 229.0 277.4 277.4 274.0 262.8 299.1 222.8

90 323.4 323.3 324.1 323.8 336.7 295.8 309.2 309.1 309.9 309.7 318.9 288.2 294.5 294.5 295.1 295.0 300.4 280.4

RT-PRC028AC-EN 77

Performance Data

Table 44. Gross cooling capacities 25 tons three phase dehumidification (hot gas reheat) option high efficiency

T/YHD300G3,4,W (Digit 22 = B)

Air

Flow cfm

(a)

5000

115

Ambient Temperature

120 125

Ent

DB 61 67 73 61

Entering Wet Bulb

67 73 61 67 73

(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC

75 202.6 151.6 227.5 118.5 253.9 82.4 196.1 148.2 220.0 114.8 245.8 79.0 189.5 144.9 212.3 111.2 237.3 75.6

80 202.9 178.2 227.2 145.7 253.8 111.3 196.5 175.0 220.0 142.3 245.6 107.9 189.8 171.5 212.6 138.9 237.3 104.5

85 204.6 203.6 227.5 173.3 253.9 138.4 199.2 199.2 220.4 170.0 245.9 135.1 193.9 193.9 213.0 166.6 237.6 131.8

90 215.9 215.9 227.9 200.1 254.2 166.7 210.6 210.6 220.7 196.6 246.2 163.4 205.0 204.9 213.3 193.2 237.9 160.1

75 212.7 175.3 237.9 130.0 264.1 83.1 205.6 171.9 229.7 127.2 255.2 79.7 198.4 168.5 221.5 123.5 246.0 76.1

6500

8000

9000

10000

10500

80 214.0 209.1 238.0 167.4 264.3 122.8 207.2 205.4 230.1 164.0 255.6 119.4 200.5 199.9 222.1 160.6 246.4 116.0

85 225.8 225.7 238.7 203.5 265.1 157.2 219.7 219.6 230.7 199.9 256.2 153.7 213.5 213.5 222.7 196.3 247.2 150.4

90 238.9 238.9 240.2 236.6 265.6 195.5 232.7 232.6 232.7 232.0 256.8 192.1 226.1 226.1 226.1 225.3 247.8 188.5

75 219.2 198.0 244.4 141.6 269.9 83.7 211.7 194.1 235.6 139.0 260.8 80.6 204.1 190.2 227.1 135.5 251.1 77.2

80 227.1 227.0 244.7 188.9 271.1 132.5 220.8 220.8 236.4 185.6 261.6 128.7 214.1 214.1 227.9 182.0 252.2 125.1

85 241.4 241.3 245.6 232.1 271.9 176.3 234.7 234.6 237.3 228.3 262.7 173.5 227.8 227.7 228.8 224.1 253.2 170.8

90 255.9 255.8 256.4 256.2 272.7 223.1 248.8 248.8 249.4 249.3 263.5 219.9 241.6 241.6 242.1 242.1 254.1 216.4

75 222.3 211.8 247.1 150.1 272.7 84.4 214.6 208.1 238.5 146.8 263.2 81.0 206.8 204.1 229.7 143.2 253.2 77.4

80 234.7 234.5 247.9 202.7 274.0 137.8 228.0 227.7 239.4 199.2 265.6 132.5 220.9 220.7 230.7 195.4 255.1 130.9

85 249.7 249.5 249.2 248.6 275.2 190.4 242.6 242.5 241.3 238.4 265.8 187.3 235.2 235.1 233.6 228.6 256.1 184.1

90 264.8 264.8 265.3 265.1 276.2 241.1 257.5 257.3 258.0 257.7 266.8 237.2 249.8 249.7 250.3 250.1 257.1 233.0

75 224.8 224.5 249.4 158.3 274.8 84.8 217.2 214.2 240.6 155.1 265.0 81.9 209.8 204.0 231.7 152.2 254.7 80.2

80 241.0 241.0 250.5 215.8 277.5 141.3 233.9 233.9 241.8 212.1 267.0 140.3 226.6 226.4 232.8 208.4 257.0 136.7

85 256.6 256.6 254.1 246.2 277.8 203.4 249.2 249.2 247.5 240.9 268.3 200.1 241.5 241.4 241.8 241.5 258.3 196.6

90 272.5 272.5 272.9 272.9 279.0 256.9 264.7 264.7 265.2 265.1 269.4 252.9 256.6 256.6 257.1 256.9 259.5 249.1

75 226.2 222.1 250.4 162.6 275.7 85.3 218.8 211.8 241.5 159.9 265.6 83.7 211.7 204.3 232.6 157.1 255.4 82.4

80 243.8 243.8 251.6 222.3 277.7 147.0 236.6 236.4 242.8 218.6 268.0 143.5 229.1 228.8 234.2 213.6 258.0 140.1

85 259.7 259.7 258.1 251.8 279.0 209.7 252.1 251.9 252.5 252.2 269.3 206.4 244.3 244.1 244.7 244.3 259.3 203.0

90 275.9 275.8 276.3 276.2 280.7 263.7 267.9 267.8 268.4 268.1 270.5 261.0 259.7 259.6 260.1 259.8 260.6 257.1

75 227.7 219.7 251.2 167.7 276.4 87.2 220.8 212.4 242.4 164.9 266.3 86.0 214.6 210.1 233.3 161.8 256.1 84.1

11000

80 246.4 246.2 252.6 228.5 278.6 149.9 239.1 238.8 243.7 224.6 268.8 146.8 231.5 231.3 234.6 220.7 259.6 141.2

85 262.6 262.4 263.0 262.6 280.5 214.9 254.8 254.6 255.2 254.9 270.2 212.8 246.9 246.7 247.2 246.9 260.2 209.1

90 279.0 278.9 279.5 279.2 281.4 272.9 270.9 270.8 271.3 271.0 271.6 269.0 262.5 262.4 263.0 262.8 261.5 258.0

Notes:

1.

All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.

2.

MBh = Total Gross Capacity

3.

SHC = Sensible Heat Capacity

4.

*Indicates both downflow and horizontal units.

(a)For 5000, 6000, and 7000 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

78 RT-PRC028AC-EN

Performance Data

Table 45. Evaporator fan performance 12½ tons TSD150G standard refrigeration system downflow

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Low Static Drive 3-hp Standard Motor & Drive

4000 461 0.60

522 0.79

575 0.98

624 1.18

667 1.37

707 1.56

743 1.75

773 1.90

802 2.05

4500 410 0.51

485 0.74

545 0.95

598 1.17

645 1.39

688 1.60

728 1.82

765 2.04

800 2.25

833 2.47

5000 437 0.64

509 0.89

569 1.14

621 1.38

667 1.62

710 1.86

749 2.10

786 2.34

821 2.58

853 2.82

5500 465 0.79

535 1.08

593 1.35

644 1.62

690 1.88

732 2.14

771 2.41

807 2.67

842 2.94

874 3.20

6000 493 0.97

561 1.28

618 1.58

668 1.87

713 2.16

754 2.45

793 2.75

829 3.03

863 3.31 896 (a)

3-hp Standard Motor & High Static Drive

3.60

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & High Static Drive

4000 826 2.17

856 2.33

880 2.47

902 2.60

923 2.72

944 2.84

963 2.96

982 3.08 1002 3.20

1021 3.32

4500 858 2.64

888 2.82

909 2.96

932 3.11

958 3.29

981 3.46 1000 3.59 1020 3.73 1038 3.87

1056 4.00

5000 885 3.06

916 3.31

941 3.51

963 3.69

991 3.89 1010 4.06 1029 4.22 1051 4.40 1074 4.60

1094 4.78

5500 906 3.46

936 3.73

965 4.00

993 4.26 1019 4.53 1040 4.73 1061 4.93 1087 5.15 1104 5.34

1122 5.52

6000 927 3.89

957 4.18

986 4.47 1014 4.76 1041 5.06 1066 5.34 1091 5.64

-

5-hp Oversized Motor & Drive

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

8.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.

(a)5-hp Oversized Motor & Drive

RT-PRC028AC-EN 79

Performance Data

Table 46. Evaporator fan performance 12½ tons TSH150G standard refrigeration system horizontal

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

4000

4500

-

-

3-hp Standard Motor & Low Static Drive

-

-

3-hp Standard Motor & Drive

3 hp

Standard

Motor & High

Static Drive

494 0.80

558 1.02

613 1.23

662 1.44

707 1.64

749 1.84

787 2.04

824 2.24

851 2.40

521 1.00

584 1.26

638 1.50

686 1.74

731 1.98

772 2.21

811 2.43

847 2.66

882 2.88

5000 475 0.92

549 1.24

610 1.53

663 1.80

711 2.08

756 2.34

797 2.61

835 2.86

871 3.12

905 3.37

5500 506 1.15

578 1.50

637 1.83

690 2.15

737 2.45

781 2.75

821 3.04

859 3.34

895 3.62

929 3.91

6000 538 1.42

607 1.81

666 2.18

717 2.53

764 2.87

807 3.20

846 3.52

884 3.85

920 4.17

953 4.48

5-hp Oversized Motor & Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & High Static Drive

4000 882 2.63

909 2.80

935 2.99

961 3.19

991 3.42 1017 3.65 1043 3.88 1069 4.12 1093 4.35

1116 4.58

4500 915 3.10

941 3.27

968 3.53

994 3.75 1016 3.94 1042 4.18 1063 4.36 1090 4.62 1117 4.89

1139 5.13

5000 938 3.62

969 3.86

999 4.11 1029 4.36 1049 4.52 1074 4.82 1100 5.10 1118 5.28 1141 5.54

1162 5.77

5500 961 4.18

993 4.46 1022 4.73 1051 5.00 1080 5.28 1107 5.55

-

6000 986 4.79 1016 5.09 1046 5.40 1076 5.71

-

5-hp Oversized Motor & Drive

-

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

8.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.

80 RT-PRC028AC-EN

Performance Data

Table 47. Evaporator fan performance 12½ tons with gas heat YSD150G standard refrigeration system downflow

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Low Static Drive 3-hp Standard Motor & Drive

4000 511 0.75

559 0.92

601 1.08

639 1.24

673 1.40

706 1.56

736 1.71

763 1.85

793 2.00

816 2.12

4500 562 1.02

607 1.21

647 1.40

683 1.58

717 1.76

748 1.94

777 2.11

805 2.29

831 2.46

854 2.61

5000 614 1.35

656 1.56

694 1.77

729 1.98

761 2.18

791 2.38

820 2.57

847 2.77

873 2.97

898 3.17

5500 667 1.74

706 1.98

742 2.21

776 2.44

807 2.67

836 2.89

863 3.11

890 3.32

915 3.55

940 3.76

6000 720 2.21

757 2.48

791 2.73

823 2.98

853 3.23

881 3.47

908 3.72

934 3.96

959 4.20

982 4.43

3-hp Standard Motor & High Static Drive 5-hp Oversized Motor & Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & High Static Drive

4000 844 2.27

868 2.41

889 2.52

910 2.64

929 2.76

948 2.87

967 2.98

986 3.10 1003 3.21

1020 3.32

4500 883 2.78

905 2.93

926 3.07

951 3.24

973 3.40

993 3.54 1011 3.67 1028 3.79 1047 3.93

1064 4.06

5000 921 3.36

942 3.52

967 3.72

990 3.89 1009 4.05 1027 4.20 1051 4.39 1072 4.59 1091 4.75

1107 4.89

5500 962 3.97

985 4.19 1006 4.40 1027 4.60 1046 4.79 1069 5.00 1090 5.18 1108 5.37 1123 5.53

1144 5.72

6000 1005 4.67 1026 4.90 1048 5.14 1069 5.38 1089 5.61

-

5-hp Oversized Motor & Drive

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

8.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.

RT-PRC028AC-EN 81

Performance Data

Table 48. Evaporator fan performance 12½ tons with gas heat YSH150G standard refrigeration system horizontal

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Low

Static Drive

3-hp Standard Motor & Drive

3-hp

Standard

Motor & High

Static Drive

4000 562 1.04

610 1.22

653 1.40

692 1.57

727 1.74

760 1.90

791 2.06

820 2.22

842 2.34

875 2.58

4500 619 1.42

665 1.63

705 1.84

742 2.03

776 2.23

808 2.42

838 2.60

866 2.78

893 2.95

920 3.14

5000 678 1.88

720 2.13

758 2.36

793 2.58

826 2.80

857 3.02

886 3.23

914 3.43

940 3.64

966 3.84

5500 737 2.45

776 2.72

813 2.98

846 3.23

877 3.48

907 3.72

935 3.96

963 4.19

988 4.42

1013 4.64

6000 796 3.12

834 3.42

868 3.71

900 3.99

930 4.26

959 4.53

986 4.79 1012 5.05 1037 5.31

1062 5.56

5-hp Oversized Motor & Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & High Static Drive

4000 900 2.74

926 2.93

952 3.11

981 3.34 1008 3.56 1032 3.78 1057 4.01 1079 4.22 1102 4.45

1127 4.70

4500 939 3.26

967 3.53

992 3.74 1014 3.92 1037 4.13 1060 4.34 1085 4.57 1110 4.82 1134 5.07

1156 5.33

5000 990 4.03 1014 4.23 1035 4.41 1051 4.54 1079 4.89 1102 5.12 1121 5.31 1142 5.54

-

5500 1037 4.87 1060 5.08 1082 5.30 1104 5.52 1125 5.73

6000 -

-

-

-

-

-

-

5-hp Oversized Motor & Drive

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

8.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.

82 RT-PRC028AC-EN

Performance Data

Table 49. Evaporator fan performance 15 tons TSD180G standard refrigeration system downflow

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor Drive

4800

5400

-

-

-

-

385 0.83

419 0.95

455 1.11

486 1.28

517 1.48

545 1.63

571 1.78

596 1.92

620 2.05

415 1.06

450 1.25

478 1.39

510 1.57

538 1.75

565 1.98

592 2.18

616 2.35

640 2.51

6000 387 1.03

447 1.38

477 1.59

507 1.75

533 1.92

562 2.12

588 2.30

613 2.55

637 2.82

660 3.02

6600 411 1.28

472 1.71

507 1.94

536 2.19

562 2.36

585 2.55

612 2.77

635 2.97

658 3.19

681 3.49

7200 436 1.58

496 2.05

539 2.41

564 2.64

591 2.89

614 3.07

635 3.28

659 3.51

682 3.74

703 3.96

5-hp Oversized Motor & Drive

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Drive 3HP Standard Motor & High Static Drive

4800 643 2.19

664 2.32

685 2.44

705 2.57

724 2.69

743 2.81

761 2.93

779 3.05

797 3.16

813 3.27

5400 662 2.67

683 2.82

704 2.98

724 3.12

743 3.27

762 3.41

780 3.55

798 3.70

816 3.84

832 3.97

6000 682 3.20

704 3.38

724 3.56

744 3.73

763 3.91

782 4.07

800 4.24

817 4.40

835 4.57

851 4.73

6600 703 3.78

724 3.99

744 4.19

764 4.40

783 4.59

802 4.79

819 4.98

836 5.16

853 5.35

871 5.54

7200 725 4.24

745 4.56

765 4.89

784 5.11

803 5.34

822 5.56

840 5.78

857 6.00

873 6.20

890 6.42

5-hp Oversized Motor & Drive 7.5hp OS Motor & High Static Drive (a)

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 89, p. 120

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 90, p. 122

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 91, p. 122 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 92, p. 123 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

9.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.

(a)7.5HP high static oversized motor offering is field installed only.

RT-PRC028AC-EN 83

Performance Data

Table 50. Evaporator fan performance 15 tons TSH180G standard refrigeration system horizontal

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Low Static Drive 3-hp Standard Motor & Drive

4800 420 0.77

453 0.91

481 1.05

508 1.18

532 1.31

563 1.47

587 1.61

614 1.77

638 1.93

658 2.08

5400 464 1.06

494 1.22

521 1.37

546 1.52

570 1.67

592 1.81

619 2.00

642 2.15

664 2.32

687 2.50

6000 509 1.41

537 1.59

562 1.76

586 1.93

609 2.09

629 2.26

649 2.42

669 2.58

695 2.80

716 2.97

6600 554 1.83

580 2.03

604 2.22

627 2.41

648 2.59

668 2.78

687 2.96

706 3.14

724 3.32

745 3.53

7200 599 2.34

624 2.56

647 2.77

668 2.97

689 3.18

708 3.38

727 3.58

744 3.77

762 3.97

778 4.17

5-hp Oversized Motor & Standard Drive

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor &

Drive

3HP Standard Motor & High Static Drive

4800 678 2.23

698 2.39

719 2.55

738 2.71

756 2.88

774 3.05

791 3.22

808 3.38

825 3.56

841 3.73

5400 709 2.67

728 2.84

747 3.02

764 3.19

782 3.37

800 3.55

818 3.73

835 3.91

851 4.10

868 4.30

6000 735 3.16

757 3.36

777 3.55

796 3.75

812 3.93

828 4.12

844 4.32

860 4.52

877 4.73

893 4.92

6600 767 3.75

785 3.93

804 4.14

822 4.35

841 4.57

860 4.79

876 5.00

891 5.20

907 5.42

920 5.63

7200 794 4.36

815 4.61

835 4.86

852 5.05

869 5.27

886 5.50

902 5.73

921 5.98

937 6.20

952 6.43

5-hp Oversized Motor & Standard Drive 7.5hp OS Motor & High Static Drive (a)

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 89, p. 120

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 90, p. 122

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 91, p. 122 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 92, p. 123 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

9.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.

(a)7.5HP high static oversized motor offering is field installed only.

84 RT-PRC028AC-EN

Performance Data

Table 51. Evaporator fan performance 15 tons with gas heat YSD180G standard refrigeration system downflow

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Low Static Drive 3-hp Standard Motor & Drive

4800 379 0.80

415 0.93

449 1.08

484 1.26

513 1.46

544 1.63

573 1.79

600 1.94

627 2.09

651 2.24

5400 417 1.07

450 1.25

480 1.41

512 1.58

543 1.79

568 2.01

596 2.21

623 2.39

648 2.57

673 2.74

6000 456 1.43

486 1.64

515 1.80

542 1.98

571 2.18

599 2.41

622 2.65

645 2.89

671 3.10

695 3.30

6600 496 1.86

524 2.11

550 2.28

576 2.47

600 2.67

626 2.89

653 3.13

674 3.40

695 3.68

718 3.93

7200 535 2.39

562 2.61

587 2.86

610 3.05

633 3.26

655 3.47

679 3.71

705 3.97

726 4.26

745 4.57

5hp Oversized Motor & Low

Static Drive

5hp Oversized Motor & Standard Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Drive 3-hp Standard Motor & High Static Drive

4800 674 2.38

697 2.52

719 2.66

739 2.78

759 2.92

779 3.04

797 3.16

816 3.29

834 3.41

851 3.52

5400 696 2.92

718 3.08

740 3.24

760 3.40

780 3.55

799 3.71

819 3.86

837 4.01

854 4.15

872 4.29

6000 718 3.50

740 3.70

761 3.89

782 4.08

801 4.25

821 4.44

840 4.61

857 4.78

876 4.96

893 5.13

6600 740 4.15

762 4.38

783 4.59

803 4.81

824 5.02

842 5.22

861 5.44

880 5.64

896 5.83

914 6.03

7200 764 4.87

785 5.13

806 5.38

826 5.61

846 5.86

864 6.09

883 6.32

901 6.55

918 6.78

935 7.00

5-hp Oversized Motor & Standard Drive 7.5hp Oversized Motor & High Static Drive (a)

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 89, p. 120

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 90, p. 122

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 91, p. 122 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 92, p. 123 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

9.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating ranges.

(a)7.5HP high static oversized motor offering is field installed only.

RT-PRC028AC-EN 85

Performance Data

Table 52. Evaporator fan performance 15 tons with gas heat YSH180G standard refrigeration system horizontal

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Low Static Drive 3-hp Standard Motor & Drive

4800 419 0.77

455 0.92

487 1.07

515 1.22

548 1.39

578 1.55

607 1.73

634 1.90

659 2.08

681 2.26

5400 462 1.05

496 1.22

526 1.39

553 1.56

578 1.72

603 1.89

635 2.10

661 2.29

687 2.49

711 2.68

6000 506 1.39

537 1.59

566 1.78

592 1.97

616 2.15

639 2.33

661 2.52

690 2.76

713 2.95

736 3.17

6600 550 1.81

579 2.03

606 2.24

631 2.45

654 2.65

677 2.86

698 3.06

717 3.25

738 3.46

766 3.74

7200 595 2.30

622 2.54

648 2.77

671 3.00

694 3.23

715 3.46

735 3.68

755 3.89

773 4.11

791 4.33

5hp Oversized Motor & Low Static Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor &

Drive

3-hp Standard Motor & High Static Drive

4800 704 2.44

728 2.63

750 2.83

772 3.03

793 3.23

813 3.43

833 3.64

852 3.85

872 4.07

890 4.28

5400 732 2.88

753 3.08

774 3.29

795 3.49

815 3.70

835 3.92

855 4.15

874 4.38

892 4.60

911 4.84

6000 761 3.40

783 3.61

803 3.82

822 4.04

841 4.27

859 4.50

877 4.73

896 4.95

914 5.18

933 5.44

6600 787 3.95

809 4.20

830 4.45

850 4.68

870 4.92

887 5.15

905 5.39

921 5.64

939 5.90

955 6.15

7200 814 4.60

838 4.88

856 5.11

876 5.37

896 5.64

916 5.91

934 6.16

951 6.42

968 6.68

983 6.93

5-hp Oversized Motor & Standard Drive 7.5hp Oversized Motor & High Static Drive (a)

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 89, p. 120

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 90, p. 122

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 91, p. 122 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 92, p. 123 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

9.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating ranges.

(a)7.5HP high static oversized motor offering is field installed only.

86 RT-PRC028AC-EN

Performance Data

Table 53. Evaporator fan performance 17½ tons TSD210/211G standard refrigeration system downflow

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Low Static Drive Accessory

5600 424 1.01

474 1.31

509 1.52

540 1.72

567 1.87

594 2.08

620 2.26

643 2.43

664 2.60

6300 392 001 450 1.27

498 1.60

541 1.93

572 2.16

599 2.39

622 2.55

648 2.75

671 2.99

695 3.20

7000 421 001 477 1.56

524 1.93

566 2.30

603 2.67

631 2.93

656 3.16

679 3.40

700 3.57

723 3.80

7700 451 001 505 1.90

551 2.31

591 2.72

628 3.12

662 3.53

689 3.84

711 4.06

733 4.37

752 4.58

8400 482 002 533 2.30

578 2.75

617 3.20

653 3.64

687 4.09

718 4.53

745 4.91

764 5.13

785 5.42

5-hp Standard Motor & Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive

5600 685 2.77

705 2.93

724 3.09

743 3.26

761 3.42

778 3.58

795 3.73

812 3.90

828 4.06

843 4.20

6300 715 3.39

734 3.58

753 3.76

772 3.96

790 4.14

807 4.33

824 4.51

840 4.69

856 4.87

871 5.04

7000 744 4.08

765 4.31

784 4.52

802 4.74

820 4.95

837 5.16

853 5.37

870 5.58

885 5.78

901 5.98

7700 772 4.77

792 5.02

812 5.34

831 5.60

850 5.85

867 6.09

884 6.32

900 6.56

914 6.78

930 7.01

8400 805 5.76

822 5.96

841 6.17

860 6.45

878 6.77

895 7.09

913 7.37

930 7.64

945 7.88

961 8.15

7.5-hp Oversized Motor & Drive

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

9.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.

RT-PRC028AC-EN 87

Performance Data

Table 54. Evaporator fan performance 17½ tons TSH210/211G standard refrigeration system horizontal

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Low Static Drive

5600 439 1.10

487 1.40

530 1.68

568 1.98

591 2.10

614 2.32

634 2.53

654 2.76

673 2.98

692 3.20

6300 477 1.45

531 1.85

567 2.15

603 2.46

637 2.80

658 2.91

678 3.15

698 3.40

716 3.64

734 3.89

7000 517 1.87

571 2.36

605 2.70

641 3.05

672 3.39

703 3.78

725 3.97

742 4.15

760 4.42

777 4.69

7700 557 2.38

609 2.92

649 3.38

676 3.73

710 4.12

738 4.49

765 4.90

790 5.28

805 5.32

822 5.61

8400 598 2.97

647 3.57

690 4.16

719 4.54

745 4.95

776 5.38

801 5.78

826 6.20

852 6.67

868 6.88

5-hp Standard Motor & Drive 7.5-hp Oversized Motor & Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Drive

5-hp Standard Motor &

High Static Drive

5600 709 3.42

726 3.65

743 3.88

759 4.11

774 4.34

789 4.57

803 4.81

817 5.05

831 5.28

845 5.54

6300 751 4.14

767 4.39

783 4.64

798 4.89

814 5.15 829 (a) 5.41

843 5.67

857 5.92

870 6.18

884 6.46

7000 794 4.97

810 5.24

825 5.51

840 5.79

855 6.07

870 6.35

884 6.63

897 6.92

911 7.20

924 7.48

7700 838 5.92

854 6.22

869 6.52

883 6.81

898 7.13

912 7.43

925 7.72

939 8.04

952 8.34

8400 883 7.00

898 7.32

913 7.65

927 7.98

941 8.31

954 8.62

-

-

-

-

-

7.5-hp Oversized Motor & High Static Drive

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

9.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.

(a)5-hp Standard Motor & High Static Drive

88 RT-PRC028AC-EN

Performance Data

Table 55. Evaporator fan performance 17½ tons with gas heat YSD210/211G standard refrigeration system downflow

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Low Static Drive

5600 434 1.07

472 1.30

504 1.49

533 1.68

560 1.82

585 2.01

611 2.20

634 2.37

655 2.53

676 2.69

6300 478 1.45

514 1.71

546 1.97

571 2.15

598 2.37

622 2.55

645 2.71

668 2.96

691 3.16

711 3.35

7000 522 1.92

556 2.21

587 2.50

615 2.79

636 2.96

660 3.20

683 3.43

703 3.59

724 3.81

745 4.09

7700 568 2.48

599 2.81

628 3.13

655 3.45

680 3.75

699 3.93

720 4.18

742 4.47

761 4.67

779 4.85

8400 614 3.15

643 3.52

671 3.87

696 4.21

720 4.56

742 4.88

760 5.08

780 5.32

799 5.67 818 (a) 5.92

5-hp Standard Motor & Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Drive

5-hp Standard Motor &

High Static Drive

5600 695 2.85

714 3.01

732 3.16

750 3.32

766 3.47

783 3.62

799 3.77

814 3.92

830 4.07

845 4.22

6300 730 3.53

748 3.71

766 3.90

783 4.07

800 4.25

816 4.42

832 4.60

847 4.77

862 4.94

876 5.11

7000 765 4.31

784 4.53

801 4.73

818 4.93

834 5.13

850 5.33

866 5.53

881 5.73

896 5.93

910 6.11

7700 798 5.11

817 5.41

836 5.67

854 5.90

870 6.12

886 6.36

901 6.58

916 6.79

930 7.02

945 7.24

8400 835 6.11

852 6.31

870 6.62

886 6.94

904 7.22

921 7.50

937 7.75

952 8.00

966 8.24

980 8.49

7.5-hp Oversized Motor & Drive 7.5-hp Oversized Motor & High Static Drive

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

9.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.

(a)7.5-hp Oversized Motor & Drive

RT-PRC028AC-EN 89

Performance Data

Table 56. Evaporator fan performance 17½ tons with gas heat YSH210/211G standard refrigeration system horizontal

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Low Static Drive 5-hp Standard Motor & Drive

5600 479 1.35

523 1.63

560 1.91

584 2.03

607 2.25

630 2.48

651 2.72

671 2.95

690 3.18

709 3.42

6300 531 1.85

566 2.14

604 2.47

637 2.79

655 2.87

677 3.13

697 3.39

716 3.64

735 3.91

753 4.17

7000 583 2.48

613 2.80

649 3.14

678 3.47

709 3.85

726 3.96

744 4.17

763 4.46

780 4.74

798 5.03

7700 636 3.24

662 3.55

692 3.91

726 4.33

750 4.67

779 5.11

795 5.31

810 5.40

827 5.72

844 6.03

8400 687 4.11

713 4.45

739 4.87

768 5.26

798 5.73

819 6.08

846 6.57

864 6.90

875 6.84 891 (a) 7.17

7.5-hp Oversized Motor & Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Drive

5-hp Standard Motor &

High Static Drive

5600 727 3.66

744 3.91

761 4.15

777 4.39

793 4.65

808 4.88

823 5.13

837 5.39

851 5.64

865 5.90

6300 770 4.44

787 4.70

803 4.96

819 5.23

835 5.51

849 5.78

864 6.06

878 6.33

892 6.61

905 6.88

7000 815 5.33

831 5.62

847 5.91

862 6.20

877 6.50

892 6.80

906 7.10

920 7.41

933 7.70

947 8.01

7700 860 6.35

876 6.67

892 7.00

907 7.31

921 7.63

935 7.95

949 8.27

963 8.60

8400 907 7.52

922 7.86

937 8.21

952 8.56

-

7.5-hp Oversized Motor & High Static Drive

-

-

-

-

-

-

-

-

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

9.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.

(a)7.5-hp Oversized Motor & High Static Drive

90 RT-PRC028AC-EN

Performance Data

Table 57. Evaporator fan performance 20 tons TSD240G standard refrigeration system downflow

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Low Static Drive 5-hp Standard Motor & Drive

6400 473 1.55

504 1.76

533 1.96

560 2.15

585 2.33

609 2.51

633 2.69

656 2.89

677 3.10

699 3.31

7200 525 2.18

553 2.41

579 2.58

605 2.85

628 3.05

651 3.25

673 3.46

694 3.65

715 3.86

735 4.08

8000 577 2.95

603 3.14

627 3.42

651 3.62

674 3.93

695 4.15

715 4.36

735 4.59

755 4.82

774 5.04

8800 629 3.89

653 4.06

676 4.40

698 4.63

719 4.87

740 5.21

759 5.46

778 5.69

796 5.94

814 6.19

9600 682 5.02

704 5.20

726 5.48

747 5.84

766 6.06

785 6.35

805 6.72

823 7.01

840 7.26

857 7.52

7.5-hp Oversized Motor & Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive

6400 721 3.53

742 3.75

762 3.96

782 4.17

802 4.39

819 4.59

837 4.81

855 5.02

872 5.22

889 5.44

7200 754 4.32

774 4.56

793 4.80

813 5.05

832 5.30

850 5.54

868 5.78

884 6.01

902 6.26

918 6.49

8000 793 5.27

810 5.51

828 5.77

845 6.03

862 6.29

881 6.58

898 6.84

916 7.12

932 7.39

948 7.65

8800 832 6.44

849 6.69

866 6.93

883 7.20

899 7.47

915 7.75

930 8.03

947 8.35

9600 873 7.78

889 8.06

905 8.33

-

-

-

-

-

-

-

-

-

7.5-hp Oversized Motor & High Static Drive

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

9.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.

RT-PRC028AC-EN 91

Performance Data

Table 58. Evaporator fan performance 20 tons TSH240G standard refrigeration system horizontal

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Low Static Drive 5-hp Standard Motor & Drive

6400 503 1.62

541 1.88

570 2.13

611 2.42

635 2.64

658 2.86

680 3.08

701 3.30

721 3.51

740 3.73

7200 555 2.20

590 2.52

620 2.81

648 3.10

685 3.43

707 3.68

729 3.93

749 4.17

768 4.42

786 4.67

8000 607 2.91

642 3.32

673 3.63

695 3.94

722 4.27

757 4.64

778 4.93

797 5.21

816 5.48

834 5.76

8800 660 3.76

695 4.25

721 4.60

748 4.97

768 5.30

793 5.66

826 6.09

847 6.42

865 6.72

883 7.03

9600 714 4.78

747 5.33

773 5.78

798 6.14

821 6.54

838 6.89

861 7.29

892 7.76

916 8.16

932 8.49

7.5-hp Oversized Motor & Drive

7.5-hp Oversized Motor & High Static

Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor &

Drive

5-hp Standard Motor & High Static Drive

6400 759 3.95

776 4.16

794 4.37

810 4.59

826 4.80

843 5.02

858 5.23

873 5.44

887 5.65

902 5.87

7200 805 4.91

822 5.15

838 5.39

855 5.64

871 5.88

886 6.12

901 6.35

916 6.60

931 6.84

944 7.07

8000 851 6.03

868 6.30

885 6.58

900 6.85

916 7.12

931 7.38

945 7.65

960 7.93

974 8.19

988 8.46

8800 899 7.33

916 7.63

932 7.94

947 8.24

962 8.53

-

9600 -

7.5-hp Oversized Motor & High Static Drive

-

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

9.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.

92 RT-PRC028AC-EN

Performance Data

Table 59. Evaporator fan performance 20 tons with gas heat YSD240G standard refrigeration system downflow

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Low Static Drive 5-hp Standard Motor & Drive

6400 497 1.73

526 1.90

553 2.11

579 2.29

604 2.47

628 2.65

651 2.85

673 3.06

695 3.27

717 3.49

7200 552 2.39

578 2.58

603 2.82

627 3.04

650 3.24

672 3.45

694 3.65

715 3.86

735 4.09

754 4.32

8000 608 3.21

632 3.46

654 3.67

676 3.95

698 4.18

719 4.41

739 4.64

759 4.87

778 5.09

797 5.32

8800 664 4.20

686 4.52

707 4.71

727 5.00

747 5.30

767 5.56

786 5.80

804 6.06

822 6.31

840 6.56

9600 721 5.39

741 5.76

760 6.00

780 6.24

797 6.57

815 6.90

834 7.17

852 7.44

869 7.72

886 8.00

7.5-hp Oversized Motor & Drive 7.5-hp Oversized Motor &

High Static Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive

6400 739 3.71

759 3.92

779 4.14

798 4.35

817 4.57

835 4.78

852 4.98

869 5.19

887 5.41

903 5.62

7200 774 4.56

794 4.80

814 5.06

833 5.31

851 5.55

869 5.79

886 6.03

902 6.26

919 6.51

935 6.74

8000 815 5.57

832 5.83

849 6.10

868 6.38

886 6.65

903 6.92

920 7.19

937 7.47

953 7.74

969 8.00

8800 858 6.81

875 7.06

891 7.34

907 7.62

922 7.90

938 8.19

955 8.50

9600 902 8.27

918 8.53

-

-

-

-

-

-

-

-

-

-

-

-

-

7.5-hp Oversized Motor & High Static Drive

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

9.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.

RT-PRC028AC-EN 93

Performance Data

Table 60. Evaporator fan performance 20 tons with gas heat YSH240G standard refrigeration system horizontal

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Low Static 5-hp Standard Motor & Drive

6400 533 1.82

560 2.05

599 2.33

628 2.57

653 2.81

676 3.04

698 3.27

720 3.50

740 3.73

759 3.95

7200 592 2.54

620 2.82

643 3.04

680 3.37

705 3.64

727 3.91

748 4.17

769 4.43

789 4.70

807 4.95

8000 650 3.40

678 3.70

698 3.98

724 4.28

757 4.64

779 4.95

800 5.24

819 5.53

838 5.83

856 6.11

8800 709 4.45

736 4.77

758 5.15

774 5.39

801 5.77

832 6.17

852 6.50

871 6.82

889 7.14

907 7.47

9600 769 5.71

794 6.08

816 6.44

833 6.80

849

7.5-hp Oversized Motor & Standard Drive

7.08

876 7.53

904 7.95

924 8.32

-

7.5-hp Oversized Motor & High Static Drive

-

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive

6400 778 4.18

796 4.40

814 4.63

831 4.85

847 5.08

863 5.30

879 5.53

895 5.76

909 5.97

924 6.20

7200 825 5.21

843 5.46

861 5.72

876 5.96

893 6.22

909 6.48

924 6.74

939 6.99

953 7.23

968 7.49

8000 874 6.40

891 6.69

907 6.97

924 7.26

939 7.54

955 7.82

970 8.11

984 8.38

-

8800 924 7.79

941 8.11

957 8.43

9600 -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

7.5-hp Oversized Motor & High Static Drive

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

9.

For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.

94 RT-PRC028AC-EN

Performance Data

Table 61. Evaporator fan performance 25 tons TSD300/301G standard refrigeration system downflow

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

7.5-hp Standard Motor & Low Static Drive 7.5-hp Standard Motor & Drive

7000 532 2.08

559 2.25

588 2.49

612 2.62

637 2.87

662 3.09

686 3.28

708 3.48

729 3.68

750 3.87

7500 566 2.52

593 2.73

618 2.95

642 3.12

665 3.33

689 3.59

712 3.82

734 4.03

755 4.24

775 4.45

8000 600 3.04

626 3.27

648 3.44

674 3.72

694 3.86

717 4.14

739 4.40

760 4.65

781 4.87

800 5.09

8500 635 3.62

659 3.87

680 4.03

705 4.35

725 4.52

745 4.72

766 5.03

787 5.31

807 5.57

826 5.80

9000 670 4.28

692 4.52

713 4.73

734 4.97

757 5.29

775 5.43

794 5.69

814 6.01

834 6.31

853 6.58

9500 705 5.00

725 5.24

747 5.51

764 5.68

787 6.07

806 6.28

823 6.44

842 6.76

861 7.10

880 7.41

10000 740 5.81

758 6.04

781 6.37

797 6.54

816 6.85

838 7.23

854 7.38

871 7.59

889 7.93

907 8.29

10500 775 6.71

793 6.93

813 7.27

831 7.50

847 7.72

868 8.16

886 8.43

902 8.59

-

11000 811 7.69

827 7.93

846 8.25

865 8.56

-

7.5-hp Standard Motor & High Static Drive

-

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

7.5-hp Standard Motor & Drive

7000 769 4.05

788 4.24

806 4.42

824 4.60

841 4.78

858 4.95

874 5.12

890 5.29

906 5.46

920 5.62

7500 794 4.66

813 4.86

831 5.06

848 5.26

865 5.45

881 5.64

897 5.83

913 6.01

928 6.20

944 6.39

8000 819 5.31

837 5.54

855 5.76

873 5.97

889 6.18

905 6.39

921 6.60

937 6.80

952 7.00

967 7.21

8500 845 6.03

863 6.27

881 6.52

897 6.75

914 6.98

930 7.21

946 7.43

962 7.66

977 7.88

991 8.09

9000 872 6.84

889 7.08

906 7.34

923 7.59

939 7.84

956 8.09

971 8.33

986 8.57

-

9500 898 7.70

915 7.97

932 8.23

949 8.50

10000 925 8.62

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

10500

11000

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

7.5-hp Standard Motor & High Static Drive Accessory

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

RT-PRC028AC-EN 95

Performance Data

Table 62. Evaporator fan performance 25 tons TSH300/301G standard refrigeration system horizontal

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

7.5-hp Standard Motor & Low Static Drive 7.5-hp Standard Motor & Drive

7000 589 2.44

620 2.65

652 2.96

688 3.30

707 3.52

724 3.73

741 3.94

758 4.15

774 4.36

7500 583 2.57

618 2.85

651 3.18

682 3.56

715 3.78

742 4.12

759 4.35

775 4.58

791 4.80

807 5.03

8000 617 3.09

649 3.33

685 3.79

711 3.99

739 4.37

774 4.75

794 5.04

810 5.29

825 5.53

841 5.77

8500 652 3.67

681 3.92

717 4.39

742 4.65

770 5.10

794 5.31

828 5.79

845 6.08

860 6.33

875 6.60

9000 687 4.33

715 4.60

747 5.00

775 5.44

798 5.65

824 6.18

850 6.42

881 6.94

896 7.23

910 7.50

9500 722 5.05

749 5.34

776 5.66

808 6.26

829 6.49

853 6.92

877 7.32

904 7.67

931 8.20

945 8.48

10000 757 5.86

783 6.17

807 6.45

839 7.06

863 7.48

882 7.66

907 8.36

928 8.58

10500 792 6.75

817 7.08

840 7.37

868 7.87

895 8.50

-

11000 828 7.73

852 8.07

874 8.40

-

-

-

-

7.5-hp Standard Motor & High Static Drive

-

-

-

-

-

-

-

-

-

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

7.5-hp Standard Motor & Drive

7000 789 4.57

803 4.77

818 4.99

832 5.20

845 5.40

859 5.61

872 5.83

885 6.03

897 6.24

909 6.45

7500 821 5.25

836 5.48

850 5.70

864 5.93

877 6.15

891 6.38

904 6.61

915 6.82

928 7.05

940 7.27

8000 855 6.01

869 6.25

883 6.50

897 6.74

910 6.97

922 7.21

935 7.45

947 7.68

959 7.92

972 8.18

8500 889 6.85

903 7.11

916 7.36

930 7.62

942 7.87

955 8.12

967 8.38

-

9000 924 7.77

937 8.04

950 8.31

963 8.59

-

9500

10000

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

10500

11000

-

-

-

-

-

-

-

-

-

-

-

-

7.5-hp Standard Motor & High Static Drive Accessory

-

-

-

-

-

-

-

-

-

-

-

-

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

96 RT-PRC028AC-EN

Performance Data

Table 63. Evaporator fan performance 25 tons with gas heat YSD300/301G standard refrigeration system downflow

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

7.5-hp Standard Motor & Low Static Drive 7.5-hp Standard Motor & Drive

7000 554 2.22

580 2.43

604 2.56

629 2.79

654 3.02

678 3.22

700 3.41

721 3.61

742 3.80

762 3.98

7500 590 2.72

614 2.90

638 3.10

660 3.28

684 3.54

707 3.77

729 3.98

749 4.19

769 4.40

789 4.60

8000 627 3.28

647 3.44

672 3.71

692 3.84

714 4.10

736 4.37

758 4.62

778 4.84

798 5.06

816 5.28

8500 663 3.90

682 4.05

706 4.37

726 4.53

745 4.73

766 5.03

787 5.31

807 5.56

826 5.80

844 6.03

9000 699 4.60

718 4.77

739 5.06

760 5.31

778 5.45

797 5.74

817 6.05

836 6.34

855 6.62

873 6.86

9500 735 5.37

754 5.58

773 5.82

794 6.17

811 6.32

829 6.53

847 6.85

866 7.18

884 7.49

902 7.77

10000 771 6.23

790 6.47

807 6.67

827 7.06

845 7.29

861 7.44

878 7.73

896 8.08

914 8.42

10500 807 7.17

827 7.46

842 7.63

861 8.00

880 8.36

895 8.52

-

11000 844 8.20

863 8.54

-

7.5-hp Standard Motor & High Static Drive

-

-

-

-

-

-

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

7.5-hp Standard Motor & Drive

7000 780 4.17

798 4.34

817 4.53

834 4.70

850 4.87

866 5.04

882 5.21

897 5.37

913 5.54

928 5.70

7500 808 4.81

825 5.00

843 5.20

859 5.39

876 5.58

892 5.77

908 5.95

922 6.13

937 6.31

952 6.49

8000 835 5.50

852 5.72

869 5.93

886 6.15

902 6.35

918 6.55

933 6.75

948 6.95

963 7.15

978 7.35

8500 862 6.27

880 6.50

896 6.73

913 6.96

929 7.19

944 7.41

960 7.63

975 7.85

989 8.06

9000 891 7.11

908 7.36

924 7.61

940 7.86

956 8.10

971 8.34

986 8.58

-

9500 919 8.04

936 8.29

952 8.56

10000 -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

10500

11000

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

7.5-hp Standard Motor & High Static Drive

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

RT-PRC028AC-EN 97

Performance Data

Table 64. Evaporator fan performance 25 tons with gas heat YSH300/301G standard refrigeration system horizontal

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

7.5-hp Standard Motor & Low Static Drive 7.5-hp Standard Motor & Drive

7000

7500

8000

8500

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

596 2.17

628 2.44

659 2.72

687 2.99

715 3.27

741 3.55

586 2.20

618 2.48

646 2.74

676 3.04

705 3.34

732 3.63

758 3.93

608 2.50

639 2.81

667 3.10

694 3.38

722 3.70

749 4.01

775 4.33

604 2.58

633 2.85

660 3.16

689 3.49

715 3.78

741 4.10

767 4.43

793 4.77

9000 598 2.65

629 2.96

657 3.23

682 3.54

710 3.88

737 4.23

760 4.54

785 4.87

810 5.23

9500 598 2.80

624 3.03

654 3.38

682 3.67

707 3.97

731 4.32

757 4.68

782 5.04

804 5.36

828 5.72

10000 628 3.26

649 3.44

680 3.84

707 4.15

732 4.46

755 4.80

778 5.17

803 5.56

826 5.93

848 6.27

10500 657 3.76

676 3.91

705 4.32

732 4.68

756 4.99

779 5.33

801 5.70

824 6.10

848 6.51

869 6.88

11000 687 4.31

703 4.44

731 4.83

757 5.24

781 5.58

803 5.91

825 6.28

845 6.68

868 7.10

891 7.54

7.5-hp Standard Motor & High Static

Drive

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

7.5-hp Standard Motor & Drive

7000 766 3.82

789 4.09

812 4.38

834 4.65

856 4.94

877 5.22

897 5.51

916 5.78

936 6.07

954 6.35

7500 782 4.22

806 4.52

829 4.82

851 5.11

872 5.41

893 5.71

913 6.01

933 6.31

952 6.61

969 6.90

8000 800 4.65

823 4.97

845 5.28

867 5.59

889 5.92

909 6.23

929 6.54

948 6.85

967 7.18

985 7.49

8500 817 5.10

840 5.44

862 5.76

884 6.10

905 6.44

926 6.78

945 7.11

965 7.45

983 7.77 1001 8.11

9000 834 5.58

857 5.93

880 6.30

901 6.64

922 6.99

942 7.34

962 7.72

981 8.06 1000 8.42

-

9500 851 6.09

874 6.46

896 6.84

919 7.22

939 7.59

959 7.96

979 8.35

10000 869 6.63

892 7.04

915 7.43

935 7.81

957 8.22

-

-

-

-

-

-

-

-

-

-

-

-

-

10500 889 7.24

910 7.62

932 8.04

953 8.47

11000 911 7.92

930 8.30

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

7.5-hp Standard Motor & High Static Drive

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

98 RT-PRC028AC-EN

Performance Data

Table 65. Evaporator fan performance—12½ tons—TH*150G

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive

2500 (a)

3000 (a)

3500 (a)

4000

-

-

-

-

-

-

-

-

-

-

-

-

370 0.32

417 0.43

458 0.54

496 0.66

531 0.79

564 0.91

593 1.03

623 1.16

386 0.42

430 0.54

472 0.67

508 0.80

543 0.94

576 1.08

606 1.22

635 1.35

360 0.43

404 0.55

447 0.68

486 0.81

522 0.96

556 1.11

588 1.26

619 1.40

647 1.55

387 0.59

426 0.71

465 0.85

502 0.99

537 1.14

570 1.29

602 1.44

631 1.59

660 1.74

4500 377 0.66

417 0.79

452 0.92

486 1.06

521 1.20

555 1.36

586 1.50

617 1.65

645 1.80

673 1.95

5000 409 0.88

448 1.03

481 1.17

512 1.30

542 1.44

573 1.59

604 1.74

633 1.89

662 2.04

688 2.18

5500 441 1.14

479 1.30

510 1.44

539 1.58

567 1.71

594 1.85

624 2.01

652 2.16

679 2.31

705 2.46

6000 474 1.42

510 1.59

540 1.74

568 1.88

594 2.01

620 2.15

645 2.29

671 2.45

698 2.62

724 2.81

3-hp Standard Motor & High Static Drive Accessory (b)

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & High Static Drive Accessory

(b)

3-hp Standard Motor & High Static Drive Accessory (c)

2500 (a)

3000 (a)

3500 (a)

650 1.28

676 1.40

701 1.52

726 1.64

748 1.76

771 1.87

793 1.98

814 2.09

835 2.21

855 2.32

662 1.48

688 1.61

713 1.74

737 1.86

760 1.98

783 2.11

806 2.23

827 2.36

847 2.48

867 2.61

674 1.69

701 1.82

726 1.96

750 2.09

772 2.22

795 2.35

818 2.49

839 2.64

859 2.78

879 2.96

4000 687 1.89

713 2.04

738 2.18

762 2.32

785 2.47

808 2.62

829 2.79

851 2.97

871 3.17

891 3.40

4500 700 2.10

726 2.26

750 2.41

775 2.58

798 2.75

821 2.95

842 3.15

864 3.41

885 3.71

904 4.06

5000 714 2.34

740 2.50

765 2.68

788 2.87

811 3.09

834 3.36

855 3.66

875 4.02

897 4.49

917 5.04

5500

6000

730

748

2.63

3.02

755

772

2.81

3.26

778

795

3.02

3.54

801

818

3.26

3.89

824

839

3.56

4.32

846

860

3.93

4.85

868

881

5-hp Oversized Motor & Drive

4.40

5.51

889

-

4.96

-

909

-

5.65

-

-

-

-

-

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.

(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.

RT-PRC028AC-EN 99

Performance Data

Table 66. Evaporator fan performance—12½ tons—THD150G—dehumidification (hot gas reheat) option

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive

2500 (a)

3000 (a)

3500 (a)

4000

369 0.32 416 0.42 458 0.52 496 0.63 530 0.74 561 0.85 591 0.97 618

383 0.41 429 0.52 470 0.64 508 0.76 543 0.88 575 1.01 606 1.13 634

358 0.42 403 0.53 444 0.64 484 0.77 520 0.90 554 1.04 587 1.18 618 1.32 647

386 0.57 424 0.67 464 0.80 500 0.93 535 1.07 569 1.21 600 1.36 629 1.52 658

1.09

1.26

1.47

1.69

4500 375 0.62 415 0.75 450 0.86 484 0.99 519 1.13 552 1.28 583 1.42 615 1.58 644 1.75 671

5000 407 0.82 446 0.97 479 1.09 510 1.22 540 1.37 572 1.53 602 1.69 630 1.84 658 2.01 686

1.92

2.20

5500 440 1.06 477 1.22 508 1.37 537 1.50 565 1.65 592 1.81 621 1.99 650 2.16 676 2.34 701

6000 471 1.34 508 1.52 538 1.69 566 1.84 592 1.99 617 2.15 643 2.32 669 2.51 695 2.71 721

2.51

2.90

3-hp Standard Motor & High Static Drive Accessory (b)

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & High Static Drive Accessory (b)

3-hp Standard Motor & High Static Drive Accessory (c)

2500 (a)

3000 (a)

3500 (a)

645 1.22 670 1.35 694 1.48 718 1.61 740 1.75 762 1.88 783 2.02 803 2.17 823 2.31 843

660 1.40 686 1.54 710 1.69 733 1.83 755 1.98 777 2.13 798 2.28 819 2.44 839 2.60 858

674 1.61 700 1.76 725 1.91 749 2.07 771 2.23 793 2.39 814 2.56 834 2.73 854 2.90 873

2.46

2.76

3.07

4000 686 1.85 712 2.02 737 2.18 762 2.35 785 2.51 808 2.68 830 2.86 850 3.04 870 3.22 889

4500 698 2.10 724 2.28 749 2.47 773 2.65 797 2.84 820 3.02 842 3.21 863 3.39 884 3.58 904

5000 712 2.38 737 2.57 762 2.76 785 2.97 809 3.17 831 3.38 853 3.58 875 3.79 895 3.99 916

5500 727 2.70 753 2.90 776 3.10 799 3.31 822 3.52 844 3.74 865 3.96 886 4.19 907 4.42 927

6000 744 3.09 767 3.28 791 3.49 815 3.71 837 3.92 858 4.15 879 4.37 899 4.60 919 4.84 939

5-hp Oversized Motor & Drive

3.41

3.77

4.20

4.64

5.08

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.

(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.

100 RT-PRC028AC-EN

Performance Data

Table 67. Evaporator fan performance—12½ tons—YH*150G

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

5500 462 1.23

496 1.38

525 1.51

553 1.64

582 1.79 610 1.93

638 2.08

666 2.23

692 2.38

718

6000 497 1.53

530 1.69

558 1.83

584 1.96

610 2.09 636 2.24

662 2.39

688 2.56

713 2.73

738

3-hp Standard Motor & High Static Drive Accessory (b)

Continued

External Static Pressure (Inches of Water)

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive

2500 (a)

3000 (a)

263 0.15

322 0.23

375 0.33

421 0.44

463 0.56 501 0.68

536 0.80

568 0.92

599 1.04

627 1.16

292 0.23

344 0.33

393 0.43

436 0.55

477 0.69 515 0.82

549 0.96

582 1.10

612 1.23

640 1.36

3500 (a)

324 0.35

369 0.45

413 0.57

455 0.71

494 0.84 529 0.99

563 1.14

595 1.29

626 1.43

655 1.57

4000 358 0.51

398 0.62

437 0.75

475 0.89

512 1.03 547 1.18

579 1.33

609 1.48

639 1.63

668 1.78

4500 392 0.71

429 0.84

464 0.97

499 1.11

532 1.25 566 1.41

597 1.55

627 1.70

655 1.85

682

5000 427 0.95

462 1.09

493 1.22

525 1.36

556 1.51 587 1.66

617 1.80

645 1.95

673 2.10

700

2.00

2.25

2.54

2.92

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & High Static Drive Accessory

(b)

3-hp Standard Motor & High Static Drive Accessory (c)

2500 (a)

3000 (a)

3500 (a)

655 1.28

681 1.40

706 1.51

730 1.63

754 1.74 776 1.85

798 1.96

820 2.07

839 2.17

860 2.28

668 1.49

694 1.62

719 1.74

743 1.87

766 1.98 790 2.11

811 2.22

833 2.35

852 2.46

873 2.59

681 1.71

708 1.85

732 1.97

756 2.10

780 2.24 803 2.37

824 2.50

846 2.65

866 2.79

887 2.96

4000 695 1.93

721 2.07

746 2.22

770 2.36

794 2.50 816 2.66

838 2.82

859 3.00

879 3.20

899

4500 708 2.15

735 2.31

760 2.47

784 2.63

807 2.81 830 3.01

852 3.24

873 3.50

893 3.79

913

5000 725 2.41

750 2.57

773 2.75

798 2.97

821 3.20 843 3.47

865 3.81

887 4.22

907 4.71

926

5500 744 2.73

767 2.92

790 3.14

813 3.41

836 3.75 857 4.16

878 4.65

900 5.31

920 6.07

940

6000 761 3.14

786 3.42

809 3.74

831 4.15

852 4.64 873 5.25

894 6.07

913 6.97

934 8.19

954

5-hp Oversized Motor & Drive

3.44

4.18

5.27

7.01

9.61

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.

(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.

RT-PRC028AC-EN 101

Performance Data

Table 68. Evaporator fan performance—12½ tons—YHD150G—dehumidification (hot gas reheat) option

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

5500 460 1.15 493 1.30 523 1.44 552 1.58 579 1.73 607 1.90 636 2.08 664 2.26 689 2.43 714

6000 495 1.45 527 1.63 555 1.78 582 1.93 608 2.09 633 2.25 659 2.44 685 2.64 711 2.83 736

3-hp Standard Motor & Drive 3-hp Standard Motor & High Static Drive Accessory (b)

Continued

External Static Pressure (Inches of Water)

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive

2500 (a)

3000 (a)

374 0.33 420 0.43 462 0.54 500 0.64 534 0.75 565 0.87 594 0.99 621

391 0.43 436 0.54 476 0.65 513 0.78 548 0.90 580 1.03 610 1.15 638

3500 (a)

— — 368 0.44 412 0.55 453 0.67 492 0.79 528 0.93 561 1.07 593 1.21 624 1.36 653

4000 356 0.49 397 0.60 435 0.71 474 0.84 509 0.96 545 1.11 577 1.25 608 1.41 638 1.57 666

1.11

1.29

1.50

1.74

4500 390 0.67 428 0.79 462 0.90 496 1.04 531 1.18 563 1.33 594 1.48 625 1.64 653 1.81 681

5000 425 0.89 460 1.02 492 1.15 522 1.28 554 1.43 585 1.60 614 1.76 642 1.91 671 2.09 698

1.98

2.27

2.61

3.02

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & High Static Drive Accessory (b)

3-hp Standard Motor & High Static Drive Accessory (c)

2500 (a)

3000 (a)

3500 (a)

648 1.23 673 1.36 697 1.49 720 1.62 742 1.76 764 1.90 785 2.04 806 2.18 825 2.33 845

664 1.42 689 1.56 713 1.71 737 1.86 759 2.00 781 2.15 802 2.31 822 2.46 842 2.62 861

680 1.64 706 1.79 730 1.94 754 2.10 776 2.27 797 2.43 818 2.60 839 2.77 858 2.94 878

2.47

2.78

3.11

4000 693 1.90 719 2.06 744 2.23 768 2.39 792 2.56 814 2.73 835 2.91 855 3.09 875 3.27 894

4500 707 2.16 733 2.35 758 2.53 782 2.72 805 2.90 827 3.09 849 3.27 870 3.46 891 3.65 911

5000 723 2.46 748 2.65 772 2.85 795 3.05 818 3.26 841 3.47 862 3.67 884 3.88 904 4.08 924

5500 741 2.81 765 3.01 788 3.21 811 3.42 833 3.63 855 3.85 876 4.08 897 4.31 917 4.53 937

6000 758 3.21 782 3.41 806 3.62 829 3.84 850 4.06 871 4.28 892 4.51 912 4.75 932 4.99 951

5-hp Oversized Motor & Drive

3.46

3.84

4.28

4.76

5.24

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.

(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.

102 RT-PRC028AC-EN

Performance Data

Table 69. Evaporator fan performance—15 tons—TH*180G

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive

3000 (a)

3600 (a)

-

-

-

-

-

-

-

-

369 0.38

411 0.47

448 0.57

483 0.68

514 0.78

543 0.89

570 1.00

596 1.11

391 0.50

429 0.61

465 0.72

499 0.84

530 0.96

560 1.08

587 1.21

614 1.33

4200 (a)

378 0.55

416 0.66

451 0.78

485 0.90

516 1.03

547 1.16

575 1.30

603 1.44

629 1.58

4800 370 0.62

408 0.74

443 0.87

476 0.99

507 1.12

537 1.26

565 1.40

593 1.55

619 1.71

645 1.86

5400 405 0.84

439 0.97

472 1.11

502 1.25

532 1.39

560 1.54

587 1.69

613 1.85

638 2.01

662 2.18

6000 440 1.11

472 1.25

502 1.40

531 1.56

558 1.72

584 1.87

610 2.03

635 2.20

659 2.37

682 2.54

6600 476 1.43

505 1.58

533 1.74

560 1.92

586 2.09

611 2.26

635 2.44

659 2.61

682 2.79

704 2.97

7200 512 1.81

539 1.98

565 2.15

590 2.33

615 2.52

639 2.71

661 2.90

683 3.08

706 3.28

727 3.47

3-hp Standard Motor & High Static Drive Accessory (b)

5-hp

Oversized

Motor &

Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & High Static Drive Accessory

(b)

3HP Standard Motor & High Static Drive Accessory (c)

620 1.23

643 1.35

664 1.47

684 1.59

703 1.72

722 1.86

740 1.99

757 2.13

775 2.27

791 2.41

3000 (a)

3600 (a)

4200 (a)

638 1.46

662 1.59

684 1.73

705 1.86

726 2.00

746 2.14

765 2.28

784 2.42

801 2.57

817 2.72

654 1.73

678 1.87

701 2.02

723 2.17

744 2.32

764 2.47

784 2.62

802 2.78

821 2.94

839 3.10

4800 670 2.02

693 2.18

716 2.34

738 2.51

760 2.67

780 2.84

800 3.01

820 3.18

838 3.35

856 3.52

5400 686 2.35

709 2.52

732 2.70

753 2.88

775 3.06

795 3.24

815 3.42

835 3.61

854 3.80

872 3.98

6000 705 2.73

727 2.91

749 3.10

770 3.29

790 3.48

810 3.68

830 3.88

850 4.08

869 4.28

887 4.48

6600 725 3.16

747 3.35

767 3.55

788 3.75

808 3.96

827 4.17

846 4.37

865 4.59

884 4.80

902 5.02

7200 748 3.66

768 3.86

788 4.07

808 4.28

827 4.49

846 4.71

864 4.93

883 5.15

900 5.38

918 5.61

5-hp Oversized Motor & Drive

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.

(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.

RT-PRC028AC-EN 103

Performance Data

Table 70. Evaporator fan performance—15 tons—THD180G—dehumidification (hot gas reheat) option

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

0.80

0.90

1.00

rpm bhp rpm bhp rpm bhp

3000 (a)

3600 (a)

4200 (a)

3-hp Standard Motor & Low Static Drive Accessory

— — — — — 387 0.49 424 0.61 458 0.72 489

3-hp Standard Motor & Drive

0.84 516 0.96 541 1.08 565 1.20

— — 367 0.51 407

354 0.54 391 0.67 426

0.63 441

0.80 460

0.76 472

0.94 492

0.89 502

1.08 520

1.02

1.23

532

546

1.16 559

1.38 572

1.30 584

1.54 598

1.44

1.70

4800 — — 383 0.73 418 0.86 449 1.01 480 1.15 510 1.31 540 1.48

5400 371 0.82 412 0.97 446 1.11 476 1.26 504 1.43 531 1.59 558 1.76

567

585

6000 403 1.08 441 1.25 475 1.41 504 1.57 530 1.74 555 1.93 580 2.11 604

6600 435 1.39 472 1.59 504 1.78 532 1.94 558 2.12 582 2.31 605 2.51 628

7200 467 1.75 502 1.98 533 2.19 561 2.38 587 2.56 610 2.76 632 2.97

3-hp Standard Motor & High Static Drive Accessory (b)

653

1.65 591

1.94 611

2.29 629

2.71

1.81 614

2.13 635

2.48 653

672

1.98

2.32

2.69

3.11

3.19 674 3.41 694

5-hp Oversized Motor & Drive

3.62

1.80

rpm

1.90

2.00

bhp rpm bhp rpm bhp

3-hp Standard Motor &

Drive

3-hp Standard Motor & High Static Drive Accessory (b)

3-hp Standard

Motor & High

Static Drive

Accessory (c)

3000 (a)

3600 (a)

587 1.32 609 1.44 629 1.57 649 1.70 668 1.83 687 1.97 705 2.11

608 1.58 629 1.72 650 1.87 670 2.01 689 2.16 708 2.30 725 2.45

723 2.25 740 2.39 758

743 2.61 760 2.76 776

2.54

2.92

4200 (a)

623 1.86 647 2.03 669 2.19 690 2.36 709 2.52 728 2.68 746 2.85 764

4800 636 2.16 659 2.34 682 2.52 704 2.71 726 2.90 746 3.09 765 3.28 783

3.01 781

3.46

3.18 797

817

3.35

3.83

5400 656 2.51 677 2.70 698 2.89 717 3.09 738 3.29 758 3.50 778 3.71

6000 676 2.90 698 3.11 718 3.32 737 3.53 756 3.74 774 3.95 792 4.17

6600 694 3.33 716 3.56 737 3.79 758 4.02 777 4.25 795 4.48 812 4.71 829 4.94 846 5.18 862 5.42

7200 715 3.84 735 4.06 755 4.30 775 4.55 795 4.80 814 5.05 833 5.31 849.90 5.56 — — — —

5-hp Oversized Motor & Drive

798

810

3.92 817 4.13 835 4.34

4.40 829 4.63 847 4.86

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.

(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.

104 RT-PRC028AC-EN

Performance Data

Table 71. Evaporator fan performance—15 tons—YH*180G

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive

3000 (a)

3600 (a)

-

-

-

-

376 0.39

417 0.49

454 0.59

488 0.69

519 0.80

547 0.91

574 1.02

600 1.13

359 0.42

400 0.52

438 0.63

473 0.75

506 0.87

537 0.99

566 1.11

594 1.24

619 1.36

4200 (a)

390 0.59

427 0.70

462 0.81

495 0.94

526 1.07

555 1.21

584 1.34

611 1.48

637 1.63

4800 386 0.66

422 0.79

456 0.92

489 1.04

519 1.18

548 1.32

577 1.46

604 1.61

630 1.77

655 1.92

5400 422 0.90

456 1.04

487 1.18

517 1.32

546 1.47

574 1.62

600 1.77

626 1.93

651 2.09

675 2.26

6000 460 1.19

491 1.34

520 1.50

548 1.66

574 1.81

601 1.97

626 2.14

650 2.30

673 2.48

696 2.66

6600 498 1.54

526 1.70

554 1.87

580 2.05

605 2.22

629 2.39

653 2.57

676 2.75

699 2.93

720 3.11

7200 536 1.96

562 2.13

588 2.31

613 2.50

636 2.69

659 2.88

681 3.07

703 3.26

725 3.45

746 3.65

3-hp Standard Motor & High Static Drive Accessory (b)

5-hp

Oversized

Motor &

Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & High Static Drive Accessory

(b)

3HP Standard Motor & High Static Drive Accessory (c)

624 1.25

646 1.36

667 1.49

687 1.62

706 1.74

725 1.88

743 2.01

760 2.15

777 2.29

794 2.43

3000 (a)

3600 (a)

4200 (a)

643 1.49

667 1.62

689 1.76

710 1.89

731 2.03

750 2.17

769 2.31

788 2.45

804 2.60

821 2.76

662 1.77

685 1.92

708 2.07

729 2.21

750 2.37

770 2.52

789 2.67

808 2.83

826 2.99

844 3.14

4800 679 2.08

703 2.24

725 2.41

747 2.57

768 2.74

789 2.91

808 3.08

827 3.25

845 3.42

863 3.59

5400 698 2.44

721 2.61

743 2.79

764 2.97

785 3.15

806 3.33

825 3.52

845 3.70

863 3.89

881 4.08

6000 719 2.84

741 3.03

762 3.22

783 3.41

803 3.61

823 3.80

842 4.00

862 4.20

880 4.40

898 4.61

6600 742 3.30

763 3.50

783 3.70

803 3.91

823 4.11

842 4.32

861 4.54

879 4.75

897 4.97

915 5.19

7200 766 3.84

786 4.05

806 4.26

825 4.47

844 4.68

863

5-hp Oversized Motor & Drive

4.91

881 5.13

899 5.36

916 5.58

-

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.

(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.

RT-PRC028AC-EN 105

Performance Data

Table 72. Evaporator fan performance—15 tons—YHD180G—dehumidification (hot gas reheat) option

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor & Low Static Drive Accessory

3000 (a)

3600 (a)

355 0.40 393 0.51 429 0.63 463 0.74 493

377 0.53 415 0.66 448 0.79 478 0.91 509

4200 (a)

— — 366 0.58 402 0.71 436 0.84 470 0.98 501 1.13 528

4800 358 0.66 397 0.78 430 0.92 461 1.07 492 1.21 522 1.38 551

3-hp Standard Motor & Drive

0.86 520 0.98 545 1.10 568

1.05 538 1.19 565 1.33 590

1.28 554 1.43 580 1.59 606

1.54 576 1.71 600 1.88 623

1.22

1.47

1.75

2.05

5400 393 0.90 430 1.04 461 1.19 490 1.35 517 1.51 545 1.67 572

6000 428 1.19 463 1.35 493 1.51 520 1.68 546 1.86 571 2.04 595

1.85 598 2.04 623 2.23 646

2.22 619 2.41 644 2.61 667

2.41

2.82

6600 463 1.54 496 1.73 525 1.90 552 2.07 576 2.26 599 2.46 622

7200 499 1.96 531 2.18 559 2.36 584 2.55 607 2.74 630 2.95 651

2.66 644

3.17 672

3-hp Standard Motor & High Static Drive Accessory (b)

2.86 666

3.38 692

3.06 688

3.60 713

3.27

3.82

5-hp Oversized Motor & Drive

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

3-hp Standard Motor &

Drive

591 1.34 612 1.46 632 1.59 652

3-hp Standard Motor & High Static Drive Accessory

1.72 671 1.86 690 1.99 708

(b)

3HP Standard

Motor & High

Static Drive

Accessory (c)

2.13 725 2.27 743 2.42 761 2.56

3000 (a)

3600 (a)

4200 (a)

613 1.61 634 1.76 655 1.90 674 2.04 693 2.19 712 2.34 729

631 1.91 654 2.08 676 2.24 696 2.40 715 2.57 734 2.73 752

2.49 746 2.64 763 2.79 780

2.90 769 3.07 786 3.23 802

2.95

3.41

4800

5400

6000

6600

7200

645 2.23 668

667 2.60 687

690 3.03 711

711 3.50 732

733 4.04 753

2.41 691

2.79 708

3.24 730

3.73 753

4.28 773

2.60 713

2.99 728

3.45 749

3.96 772

4.52 793

2.79 734 2.98 754

3.19 748 3.40 768

3.66 767 3.87 785

4.20 790 4.42 808

4.77 812 5.02 831

5-hp Oversized Motor & Drive

3.16 772

3.60 788

4.09 803

4.66 825

3.35 790 3.54 807 3.72 824

3.81 807 4.03 826 4.24 844

4.31 822 4.54 840 4.77 858

4.88 841 5.12 858 5.36 874

5.28 848.25 5.53 — — — — —

3.91

4.45

5.00

5.60

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.

(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.

106 RT-PRC028AC-EN

Performance Data

Table 73. Evaporator fan performance— 17½ tons — TH*210G

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Low Static Drive Accessory

3500 (a)

4200 (a)

4900 (a)

5600

— — 470 0.86 501 1.00 531 1.13 558 1.27 582

462 0.94 494 1.09 521 1.24 547 1.39 573 1.54 599

— — 455 1.06 485 1.20 515 1.36 544 1.53 572 1.70 596 1.88 619

458 1.21 487 1.37 514 1.54 541 1.71 567 1.88 593 2.07 619 2.26 643

1.41

1.71

2.05

2.46

6300 — — 459 1.43 492 1.60 520 1.76 546 1.94 570 2.13 594 2.32 618 2.51 641 2.70 664

7000 460 1.65 495 1.86 526 2.07 554 2.24 580 2.42 603 2.63 625 2.83 646 3.05 668 3.25 689

7700 498 2.13 531 2.38 562 2.62 589 2.82 614 3.02 637 3.22 658 3.44 678 3.66 698 3.90 717

8400 537 2.71 568 2.99 597 3.26 624 3.50 648 3.71 670 3.93 692 4.15 711 4.38 730 4.63 748

5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive Accessory

2.91

3.47

4.13

4.88

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive Accessory

3500 (a)

4200 (a)

4900 (a)

605 1.54 627 1.68 648 1.82 667 1.96 686 2.11 705 2.25 723 2.40 740 2.55 757 2.70 773

624 1.87 648 2.04 670 2.20 691 2.36 710 2.53 729 2.69 747 2.86 765 3.03 782 3.19 798

641 2.22 663 2.41 686 2.59 708 2.79 729 2.98 750 3.17 769 3.36 788 3.55 805 3.74 822

2.86

3.36

3.93

5600 665 2.65 686 2.85 706 3.05 725 3.25 745 3.45 764 3.66 784 3.88 803 4.09 822 4.31 841

6300 687 3.13 709 3.35 730 3.57 750 3.79 768 4.01 786 4.23 804 4.46 821 4.69 838 4.92 856

7000 710 3.68 731 3.91 752 4.15 772 4.40 792 4.64 811 4.89 828 5.14 845 5.38 861 5.62 878

7700 737 4.36 756 4.59 775 4.83 794 5.07 813 5.33 832 5.60 850 5.87 868 6.14 886 6.41 902

8400 767 5.14 784 5.38 802 5.63 820 5.89 837 6.15 854 6.41 872 6.68 889 6.97 907 7.26 924

7.5-hp Oversized Motor & Drive

4.54

5.15

5.87

6.68

7.55

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

RT-PRC028AC-EN 107

Performance Data

Table 74. Evaporator fan performance — 17½ tons — THD210G — dehumidification (hot gas reheat) option

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

— — — — — — — — — —

5HP Standard Motor & Low

Static Drive Accessory

5HP Standard Motor & Drive

470 0.86 501 1.00 531 1.13 558 1.27 582 1.41 3500 (a)

4200 (a)

4900 (a)

— — 462 0.94 494 1.09 521 1.24 547 1.39 573 1.54 599

455 1.06 485 1.20 515 1.36 544 1.53 572 1.70 596 1.88 619

1.71

2.05

5600 — — — — 458 1.21 487 1.37 514 1.54 541 1.71 567 1.88 593 2.07 619 2.26 643

6300 — — 459 1.43 492 1.60 520 1.76 546 1.94 570 2.13 594 2.32 618 2.51 641 2.70 664

7000 460 1.65 495 1.86 526 2.07 554 2.24 580 2.42 603 2.63 625 2.83 646 3.05 668 3.25 689

7700 498 2.13 531 2.38 562 2.62 589 2.82 614 3.02 637 3.22 658 3.44 678 3.66 698 3.90 717

2.46

2.91

3.47

4.13

8400 537 2.71 568 2.99 597 3.26 624 3.50 648 3.71 670 3.93 692 4.15 711 4.38 730 4.63 748 4.88

5HP Standard Motor & High Static Drive Accessory

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5HP Standard Motor & Drive 5HP Standard Motor & High Static Drive Accessory

3500 (a)

4200 (a)

605 1.54 627 1.68 648 1.82 667 1.96 686 2.11 705 2.25 723 2.40 740 2.55 757 2.70 773

624 1.87 648 2.04 670 2.20 691 2.36 710 2.53 729 2.69 747 2.86 765 3.03 782 3.19 798

4900 (a)

641 2.22 663 2.41 686 2.59 708 2.79 729 2.98 750 3.17 769 3.36 788 3.55 805 3.74 822

5600 665 2.65 686 2.85 706 3.05 725 3.25 745 3.45 764 3.66 784 3.88 803 4.09 822 4.31 841

2.86

3.36

3.93

4.54

6300 687 3.13 709 3.35 730 3.57 750 3.79 768 4.01 786 4.23 804 4.46 821 4.69 838 4.92 856

7000 710 3.68 731 3.91 752 4.15 772 4.40 792 4.64 811 4.89 828 5.14 845 5.38 861 5.62 878

7700 737 4.36 756 4.59 775 4.83 794 5.07 813 5.33 832 5.60 850 5.87 868 6.14 886 6.41 902

8400 767 5.14 784 5.38 802 5.63 820 5.89 837 6.15 854 6.41 872 6.68 889 6.97 907 7.26 924

5.15

5.87

6.68

7.55

7.5HP Oversized Motor & Drive

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

108 RT-PRC028AC-EN

Performance Data

Table 75. Evaporator fan performance—17½ tons—YH*210G

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Low Static Drive Accessory 5-hp Standard Motor & Drive

3500 (a)

4200

(a)

4900

(a)

5600

— — 476 0.89 508 1.02 537 1.16 563 1.30 587 1.43

472 0.99 502 1.14 529 1.28 555 1.43 581 1.59 607 1.76

— — 468 1.12 497 1.27 527 1.43 556 1.60 582 1.78 605 1.95 628 2.12

474 1.29 501 1.46 528 1.63 555 1.80 581 1.98 607 2.17 632 2.37 655 2.56

6300 — — 482 1.55 512 1.71 538 1.88 563 2.07 587 2.26 610 2.45 634 2.64 657 2.84 680 3.06

7000 490 1.84 522 2.04 550 2.22 576 2.39 599 2.59 621 2.80 643 3.01 665 3.22 686 3.43 707 3.65

7700 532 2.39 562 2.62 589 2.83 614 3.02 637 3.22 658 3.44 679 3.67 698 3.90 718 4.13 737 4.36

8400 574 3.03 603 3.30 629 3.55 653 3.76 675 3.97 696 4.20 715 4.43 734 4.68 752 4.93 770 5.18

5-hp Standard Motor & High Static Drive Accessory

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive Accessory

3500

(a)

4200

(a)

4900

(a)

610 1.57 631 1.71 652 1.85 672 1.99 690 2.14 709 2.28 726 2.43 744 2.58 760 2.73 777 2.89

632 1.92 655 2.09 677 2.25 697 2.41 716 2.58 735 2.74 753 2.91 770 3.08 787 3.24 803 3.42

650 2.30 673 2.48 695 2.67 717 2.86 738 3.06 758 3.25 777 3.44 795 3.63 812 3.82 829 4.01

5600 677 2.76 697 2.96 717 3.15 736 3.36 755 3.56 775 3.78 795 3.99 814 4.21 832 4.43 850 4.65

6300 702 3.28 724 3.50 744 3.72 762 3.94 781 4.17 798 4.39 816 4.61 833 4.84 850 5.08 868 5.32

7000 727 3.88 748 4.11 769 4.36 789 4.60 808 4.85 826 5.10 843 5.34 859 5.59 875 5.83 891 6.08

7700 756 4.59 775 4.83 794 5.08 813 5.34 832 5.60 851 5.87 869 6.15 886 6.41 903 6.69 918 6.96

8400 788 5.44 806 5.69 824 5.95 841 6.21 858 6.46 876 6.74 893 7.03 910 7.32 927 7.61 944 7.91

7.5-hp Oversized Motor & Drive

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

RT-PRC028AC-EN 109

Performance Data

Table 76. Evaporator fan performance — 17½ tons — YHD210G — dehumidification (hot gas reheat) option

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

7700 532 2.39 562 2.62 589 2.83 614 3.02 637 3.22 658 3.44 679 3.67 698 3.90 718 4.13 737

8400 574 3.03 603 3.30 629 3.55 653 3.76 675 3.97 696 4.20 715 4.43 734 4.68 752 4.93 770

5HP Standard Motor & High Static Drive Accessory

Continued

External Static Pressure (Inches of Water)

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5HP Standard Motor &

Low Static Drive

Accessory

5HP Standard Motor & Drive

474 1.29 501 1.46 528 1.63 555 1.80 581 1.98 607 2.17 632 2.37 655 5600 — — — —

6300 — —

482 1.55

(a) 512

1.71 538 1.88 563 2.07 587 2.26 610 2.45 634 2.64 657 2.84 680

7000 490 1.84

(a) 522 2.04 550 2.22 576 2.39 599 2.59 621 2.80 643 3.01 665 3.22 686 3.43 707

2.56

3.06

3.65

4.36

5.18

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5HP Standard Motor & High Static Drive Accessory

5600 677 2.76

(b) 697 2.96 717 3.15 736 3.36 755 3.56 775 3.78 795 3.99 814 4.21 832 4.43 850 4.65

6300 702 3.28 724 3.50 744 3.72 762 3.94 781 4.17 798 4.39 816 4.61 833 4.84 850 5.08 868 5.32

7000 727 3.88 748 4.11 769 4.36 789 4.60 808 4.85 826 5.10 843 5.34 859 5.59 875 5.83 891 6.08

7700 756 4.59 775 4.83 794 5.08 813 5.34 832 5.60 851 5.87 869 6.15 886 6.41 903 6.69 918 6.96

8400 788 5.44 806 5.69 824 5.95 841 6.21 858 6.46 876 6.74 893 7.03 910 7.32 927 7.61 944

7.5HP Oversized Motor & Drive

7.91

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)5HP Standard Motor & Low Static Drive Accessory

(b)5HP Standard Motor & Drive

110 RT-PRC028AC-EN

Performance Data

Table 77. Evaporator fan performance—20 tons—TH*240G

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Low Static Drive Accessory 5-hp Standard Motor & Drive

4000 (a)

4800 (a)

5600 (a)

6400

— — 456 0.88 486 1.02 514 1.16 541 1.31 569 1.46 595

451 1.02 481 1.16 512 1.32 541 1.49 568 1.66 592 1.82 615

— — 458 1.21 487 1.37 514 1.54 541 1.71 567 1.88 593 2.07 619 2.26 643

464 1.49 497 1.66 525 1.82 551 2.00 575 2.20 598 2.39 622 2.58 645 2.78 667

1.62

1.99

2.46

2.98

7200 470 1.77 505 2.00 536 2.21 564 2.40 589 2.58 612 2.78 634 3.00 655 3.21 676 3.43 697

8000 514 2.37 547 2.63 577 2.87 603 3.10 628 3.30 651 3.51 672 3.73 692 3.96 711 4.20 730

8800 560 3.10 590 3.38 618 3.65 644 3.92 667 4.16 690 4.39 711 4.61 731 4.84 749 5.09 767

9600 606 3.97 633 4.27 660 4.59 685 4.88 708 5.15 729 5.42 750 5.66 769 5.91 788 6.16 805

5-hp Standard Motor & High Static Drive Accessory

7.5-hp Oversized Motor & Field Supplied Motor Sheave (b)

Continued

External Static Pressure (Inches of Water)

3.65

4.44

5.35

6.42

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive Accessory

4000 (a)

4800 (a)

5600 (a)

620 1.78 643 1.93 664 2.09 685 2.25 704 2.40 722 2.56 740 2.72 758 2.88 775 3.05 791

638 2.17 661 2.35 684 2.54 706 2.72 727 2.91 747 3.10 767 3.29 785 3.48 802 3.66 819

665 2.65 686 2.85 706 3.05 725 3.25 745 3.45 764 3.66 784 3.88 803 4.09 822 4.31 841

3.21

3.85

4.54

6400 690 3.20 712 3.43 733 3.65 753 3.88 772 4.10 790 4.32 807 4.55 824 4.78 841 5.01 858

7200 717 3.86 737 4.09 758 4.33 778 4.58 798 4.83 817 5.08 835 5.34 852 5.59 868 5.84 885

8000 749 4.68 768 4.92 786 5.16 804 5.41 823 5.66 841 5.93 859 6.20 877 6.48 895 6.76 912

8800 784 5.61 802 5.89

(b) 819 6.15 836 6.41 853 6.67 869 6.95 886 7.21 902 7.49 919 7.78 936

9600 822 6.69 839 6.98 854 7.26 870

7.5-hp Oversized Motor & Drive

7.55 886 7.85 901 8.13 917 8.42 — — —

7.5-hp Oversized Motor & Field Supplied Motor Sheave (c)

— —

5.25

6.10

7.04

8.09

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Refer to Table 89, p. 120 to determine additional static pressure drop due to other options/accessories.

8.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

9.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

(b)7.5-hp Oversized Motor & Field Supplied Motor Sheave (c)

(c) Field supplied motor sheave 1VP50 x 1 1/8 required.

RT-PRC028AC-EN 111

Performance Data

Table 78. Evaporator fan performance—20 tons—THD240G—dehumidification (hot gas reheat) option

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Low Static Drive Accessory 5-hp Standard Motor & Drive

4000 (a)

4800 (a)

5600 (a)

6400

— — 454 0.88 485 1.01 513 1.16 540 1.30 568 1.46 594

449 1.01 480 1.15 510 1.31 540 1.48 567 1.65 591 1.81 614

— — 456 1.20 485 1.36 512 1.53 539 1.70 565 1.87 591 2.05 617 2.24 641

461 1.47 494 1.65 523 1.81 549 1.99 573 2.18 596 2.37 619 2.56 642 2.76 665

1.61

1.98

2.44

2.96

7200 467 1.75 502 1.98 533 2.19 561 2.38 587 2.56 610 2.76 632 2.97 653 3.19 674 3.41 694

8000 511 2.35 544 2.60 573 2.85 601 3.08 625 3.28 648 3.48 670 3.70 690 3.93 709 4.16 728

3.62

4.41

8800 556 3.06 586 3.34 614 3.62 640 3.89 664 4.13 687 4.36 708 4.58 728 4.80 746 5.05 764

9600 601 3.91 629 4.22 656 4.53 680 4.82 704 5.12 726 5.38 746 5.62 766 5.87 784 6.10 802

5-hp Standard Motor & High Static Drive Accessory 7.5-hp Oversized Motor & Field Supplied Motor Sheave (b)

5.31

6.37

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive Accessory

4000 (a)

4800 (a)

5600 (a)

619 1.77 642 1.93 663 2.08 683 2.24 703 2.39 721 2.55 739 2.71 757 2.87 774 3.04 790

636 2.16 659 2.34 682 2.52 704 2.71 726 2.90 746 3.09 765 3.28 783 3.46 801 3.65 817

663 2.64 684 2.83 704 3.03 724 3.23 743 3.43 763 3.64 782 3.86 802 4.08 821 4.29 839

3.20

3.83

4.51

6400 688 3.18 710 3.40 731 3.63 751 3.85 770 4.08 788 4.30 805 4.52 822 4.75 839 4.98 856

7200 715 3.84 735 4.06 755 4.30 775 4.55 795 4.80 814 5.05 833 5.31 850 5.56 866 5.81 882

8000 747 4.65 765 4.89 784 5.12 802 5.37 820 5.62 838 5.89 856 6.16 874 6.44 892 6.71 909

8800 782 5.57 799 5.84

(c) 816 6.10 833 6.36 850 6.63 866 6.89 883 7.16 899 7.44 916 7.73 933

9600 819 6.64 835 6.92 851 7.21 867 7.49 883 7.79 898

7.5-hp Oversized Motor & Field Supplied Motor Sheave

(b)

8.08 914 8.36 —

7.5-hp Oversized Motor & Drive

— — — —

5.22

6.06

7.00

8.03

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

(b)Field supplied motor sheave 1VP50 x 1 1/8 required.

(c) 7.5-hp Oversized Motor & Field Supplied Motor Sheave (b)

112 RT-PRC028AC-EN

Performance Data

Table 79. Evaporator fan performance—20 tons—YH*240G

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Low Static Drive Accessory 5-hp Standard Motor & Drive

4000 (a)

4800 (a)

— — 465 0.92 494 1.06 522 1.20 549 1.35 576 1.51 602 1.66

463 1.07 493 1.22 524 1.39 552 1.56 578 1.72 601 1.89 624 2.06

5600 (a)

— — — — 474 1.29 501 1.46 528 1.63 555 1.80 581 1.98 607 2.17 632 2.37 655 2.56

6400 454 1.43 487 1.61 517 1.77 544 1.95 568 2.14 591 2.33 615 2.52 638 2.72 661 2.92 684 3.14

7200 502 1.98 533 2.19 561 2.38 587 2.56 610 2.76 632 2.97 653 3.19 674 3.41 695 3.63 715

8000 550 2.64 579 2.89 606 3.12 631 3.32 653 3.53 674 3.75 694 3.98 713 4.22 732 4.47 751

8800 599 3.46 627 3.75 652 4.00 675 4.23 697 4.45 718 4.69 737 4.93 755 5.18 773 5.44 790

9600 648 4.44 674 4.74 698 5.04 721 5.33 742 5.56 761 5.80 780 6.05 798 6.30 815 6.58 832

5-hp Standard Motor &

High Static Drive Accessory

7.5-hp Oversized Motor &

Field Supplied Motor Sheave (b)

7.5-hp Oversized

Motor & Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

3.84

4.70

5.71

6.86 cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor Drive 5-hp Standard Motor & High Static Drive Accessory

4000 (a)

4800 (a)

627 1.82 649 1.98 670 2.13 690 2.29 709 2.45 728 2.61 745 2.77 763 2.93 779 3.09 796 3.26

647 2.24 670 2.42 693 2.61 714 2.80 735 2.99 755 3.18 774 3.36 792 3.55 809 3.74 825 3.92

5600 (a)

677 2.76 697 2.96 717 3.15 736 3.36 755 3.56 775 3.78 795 3.99 814 4.21 832 4.43 850 4.65

6400 706 3.36 727 3.58 748 3.81 766 4.03 784 4.26 802 4.48 819 4.71 836 4.94 853 5.18 870 5.42

7200 735 4.07 756 4.31 776 4.56 795 4.80 815 5.06 833 5.31 850 5.57 867 5.81 883 6.06 899

8000 770 4.94 788 5.18 806 5.44 825 5.69 843 5.96 861 6.23 879 6.51 896 6.79 913 7.07 930

8800 807 5.97 825 6.23 841 6.50 858 6.77 875 7.03 891 7.30 908 7.58 925 7.89 941 8.19 958

9600 848 7.14 864 7.43 879 7.73 895 8.01 911 8.30 926 8.59 — — — — — — —

6.32

7.36

8.49

7.5-hp Oversized Motor & Drive

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

(b)Field supplied motor sheave 1VP50 x 1 1/8 required.

RT-PRC028AC-EN 113

Performance Data

Table 80. Evaporator fan performance—20 tons—YHD240G—dehumidification (hot gas reheat) option

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5-hp Standard Motor & Low Static Drive Accessory 5-hp Standard Motor & Drive

4000 (a)

4800 (a)

— — 464 0.91 493 1.05 521 1.20 548 1.34 575 1.50 601 1.66

461 1.07 492 1.21 522 1.38 551 1.54 576 1.71 600 1.88 623 2.05

5600 (a)

— — — — 472 1.28 500 1.45 527 1.62 553 1.79 579 1.96 605 2.15 630 2.35 654 2.55

6400 451 1.42 485 1.60 515 1.76 541 1.93 566 2.12 589 2.32 613 2.51 636 2.70 658 2.90 681 3.12

7200 499 1.96 531 2.18 559 2.36 584 2.55 607 2.74 630 2.95 651 3.17 672 3.38 692 3.60 713

8000 548 2.64 577 2.88 603 3.10 627 3.29 650 3.50 672 3.72 691 3.95 711 4.19 730 4.43 748

3.82

4.67

8800 596 3.45 623 3.71 649 3.97 672 4.21 694 4.43 715 4.66 734 4.89 752 5.13 770 5.39 787 5.66

(b)

9600 645 4.41 670 4.70 694 4.98 717 5.26 738 5.52 758 5.76 777 6.00 795 6.25 812 6.52 829 6.80

5-hp Standard Motor

& High Static Drive

Accessory

7.5-hp Oversized Motor

& Field Supplied Motor Sheave (c)

7.5-hp Oversized Motor & Drive

Continued

1.10

1.20

1.30

External Static Pressure (Inches of Water)

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

4000 (a)

4800 (a)

5600 (a)

5-hp Standard Motor Drive 5-hp Standard Motor & High Static Drive Accessory

626 1.81 648 1.97 669 2.12 689 2.28 708 2.44 726 2.60 744 2.76 762 2.92 778 3.08 795 3.25

645 2.23 668 2.41 691 2.60 713 2.79 734 2.98 754 3.16 772 3.35 790 3.54 807 3.72 824 3.91

675 2.74 695 2.94 715 3.14 734 3.34 753 3.54 773 3.76 793 3.97 812 4.19 831 4.41 849 4.63

6400 704 3.34 725 3.56 746 3.79 764 4.01 783 4.23 800 4.46 817 4.69 834 4.91 851 5.15 868 5.39

7200 733 4.04 753 4.28 773 4.52 793 4.77 812 5.02 831 5.28 848 5.53 865 5.78 881 6.03 896

8000 767 4.91 785 5.15 804 5.40 822 5.65 840 5.92 858 6.19 876 6.46 894 6.75 911 7.03 927

8800 805 5.93

(d) 822 6.19 839 6.45 855 6.72 872 6.99 888 7.25 905 7.54 922 7.83 938 8.13 955

— — — — — — 9600 845 7.09 861 7.38 876 7.67 892 7.96 907 8.24 923 8.52 —

7.5-hp Oversized Motor

& Field Supplied Motor Sheave (c)

7.5-hp Oversized Motor & Drive

6.29

7.31

8.43

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

(b)5-hp Standard Motor & High Static Drive Accessory

(c) Field supplied motor sheave 1VP50 x 1 1/8 required.

(d)7.5-hp Oversized Motor & Field Supplied Motor Sheave (c)

114 RT-PRC028AC-EN

Performance Data

Table 81. Evaporator fan performance—25 tons—TH*300G

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

7.5-hp Standard Motor & Drive

5000 (a)

6500 (a)

7000 (a)

7500 (a)

— — — — 575 1.75 599 1.93 622 2.10

579 2.26 603 2.46 626 2.65 648 2.85 671 3.06

— — 580 2.42 603 2.63 625 2.83 646 3.05 668 3.25 689 3.47

579 2.65 604 2.84 627 3.04 648 3.26 669 3.48 689 3.71 709 3.93

8000

8500

— — 577 2.87 603 3.10 628 3.30 651 3.51 672 3.73 692 3.96 711 4.20 730 4.44

574 3.09 602 3.34 628 3.60 653 3.83 675 4.04 696 4.25 716 4.49 735 4.74 753 5.00

9000 572 3.31 600 3.58 628 3.87 654 4.15 678 4.40 700 4.63 720 4.86 740 5.08 759 5.34 777 5.60

9500 600 3.85 628 4.17 655 4.47 680 4.75 703 5.02 724 5.27 745 5.52 764 5.76 783 6.00 801 6.28

10000 627 4.42 656 4.78 681 5.09 705 5.41 728 5.71 749 5.99 770 6.26 789 6.50 807 6.76 825 7.02

10500 657 5.13 683 5.45 708 5.80 731 6.13 753 6.44 775 6.76 794 7.04 813 7.31 831 7.57 849 7.84

11000 685 5.81 711 6.21 735 6.58 758 6.93 778 7.23 800 7.58 819 7.88 838 8.19 856 8.45 —

7.5-hp Standard Motor & High Static Drive Accessory

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

7.5-hp Standard Motor & Drive

5000 (a)

6500 (a)

7000 (a)

644

693

710

2.28 666

3.28 715

3.68 731

2.46 688

3.50 736

3.91 752

2.65 710

3.73 757

4.15 772

2.85 731

3.96 775

4.40 792

3.04

4.19

4.64

7500 (a)

729 4.16 748 4.38 768 4.62 787 4.87 807 5.13

8000 749 4.68 768 4.92 786 5.16 804 5.41 823 5.66

8500 771 5.25 789 5.51 806 5.76 824 6.02 841 6.28

9000 794 5.87 811 6.14 827 6.41 844 6.69 861 6.95

9500 817 6.55 834 6.83 850 7.12 866 7.41 882 7.69

10000 841 7.29 857 7.59 873 7.87 888 8.18 904 8.48

10500 865 8.11 881 8.41 —

11000 — — — — —

7.5-hp Standard Motor & High Static Drive Accessory

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

RT-PRC028AC-EN 115

Performance Data

Table 82. Evaporator fan performance—25 tons—THD300G—dehumidification (hot gas reheat) option

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

7.5-hp Standard Motor & Low Static Drive

5000 (a)

6500 (a)

7000 (a)

7500 (a)

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

602 1.57

633 1.73

661 1.89

688 2.05

587 2.00

614 2.18

640 2.35

665 2.53

690 2.70

714 2.89

739 3.08

588 2.19

616 2.39

641 2.57

666 2.75

690 2.94

713 3.13

736 3.32

759 3.52

593 2.42

620 2.63

645 2.82

670 3.02

693 3.21

716 3.41

738 3.61

760 3.82

782 4.02

8000 597 2.66

625 2.89

650 3.09

674 3.29

698 3.51

722 3.73

743 3.93

765 4.15

785 4.36

806 4.57

8500 632 3.18

658 3.41

683 3.64

706 3.86

728 4.07

750 4.29

771 4.51

792 4.74

812 4.97

832 5.20

9000 666 3.74

692 4.00

714 4.22

737 4.46

757 4.67

779 4.92

799 5.15

819 5.39

839 5.64

858 5.88

9500 701 4.38

726 4.67

746 4.87

769 5.15

788 5.36

808 5.61

828 5.86

847 6.10

866 6.36

885 6.62

10000 737 5.11

760 5.39

778 5.60

800 5.89

819 6.11

838 6.37

858 6.64

876 6.89

895 7.17

913 7.45

10500 766 5.76

792 6.15

813 6.44

832 6.70

851 6.96

869 7.21

888 7.50

905 7.75

923 8.05

941 8.33

11000 806 6.73

824 6.98

844 7.27

864 7.56

883 7.88

900 8.14

918 8.44

7.5-hp Standard Motor & Drive

-

7.5-hp Standard Motor & High Static Drive Accessory

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

7.5-hp Standard Motor &

Low Static Drive

7.5-hp Standard Motor & Drive

5000 (a)

6500 (a)

712 2.20

736 2.36

758 2.52

779 2.67

799 2.82

763 3.28

787 3.48

810 3.69

833 3.90

855 4.11

7000 (a)

7500 (a)

782 3.73

805 3.94

827 4.15

849 4.37

871 4.59

803 4.23

825 4.44

846 4.66

867 4.89

888 5.12

8000 826 4.79

846 5.01

867 5.24

886 5.47

906 5.71

8500 851 5.42

870 5.65

889 5.88

908 6.12

927 6.37

9000 876 6.11

895 6.36

913 6.61

931 6.85

949 7.09

9500 903 6.88

921 7.13

938 7.38

955 7.63

973 7.89

10000 930 7.70

947 7.97

964 8.22

981 8.50

-

10500 958 8.60

11000 -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

7.5-hp Standard Motor & High Static Drive Accessory

-

-

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

116 RT-PRC028AC-EN

Performance Data

Table 83. Evaporator fan performance—25 tons—YH*300G

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

7.5-hp Standard Motor & Drive

5000 (a)

6500 (a)

7000 (a)

7500 (a)

— — — — 586 1.83 609 2.00 632 2.18

596 2.41 619 2.60 642 2.80 664 3.00 687 3.22

— — 599 2.59 621 2.80 643 3.01 665 3.22 686 3.43 707 3.65

603 2.83 626 3.03 648 3.25 668 3.47 688 3.70 708 3.92 728 4.15

8000 — — — — 606 3.12 631 3.32 653 3.53 674 3.75 694 3.98 713 4.22 732 4.47 751

8500 582 3.16 609 3.41 635 3.66 658 3.87 680 4.09 701 4.31 721 4.55 739 4.80 757 5.05 775

9000 611 3.68 639 3.99 664 4.25 687 4.49 708 4.73 728 4.95 748 5.18 766 5.44 783 5.71 800

9500 644 4.36 668 4.60 692 4.89 715 5.16 736 5.41 756 5.66 775 5.89 793 6.15 810 6.43 826

10000 676 5.05 698 5.31 722 5.62 744 5.93 764 6.19 784 6.44 802 6.68 820 6.95 837 7.22 853

10500 703 5.70 728 6.07 752 6.43 772 6.72 792 7.00 811 7.27 829 7.54 847 7.81 864 8.08 880

11000 739 6.65 759 6.93 780 7.27 801 7.58 821 7.92 840 8.23 857 8.48 —

7.5-hp Standard Motor & High Static Drive Accessory

— — — —

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

4.70

5.31

5.98

6.71

7.51

8.38

7.5-hp Standard Motor & Drive

5000 (a)

6500 (a)

7000 (a)

653 2.36 675 2.54 697 2.74 719 2.93 740 3.13

709 3.44 731 3.67 751 3.90 770 4.13 788 4.35

727 3.88 748 4.11 769 4.36 789 4.60 808 4.85

7500 (a)

748 4.37 767 4.61 787 4.86 806 5.12 825 5.38

8000 770 4.94 788 5.18 806 5.44 825 5.69 843 5.96

8500 793 5.57 811 5.83 828 6.08 845 6.34 862 6.61

9000 817 6.25 834 6.52 851 6.79 867 7.06 884 7.34

9500 843 6.99 858 7.27 875 7.57 890 7.84 906 8.13

10000 869 7.79 884 8.10 899 8.39 — — — —

10500

11000

7.5-hp Standard Motor & High Static Drive Accessory

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

RT-PRC028AC-EN 117

Performance Data

Table 84. Evaporator fan performance—25 tons—YHD300G—dehumidification (hot gas reheat) option

0.10

0.20

0.30

External Static Pressure (Inches of Water)

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

7.5-hp Standard Motor & Low Static Drive Accessory

5000 (a)

6500 (a)

7000 (a)

7500 (a)

-

-

-

-

-

-

-

-

-

-

-

-

584 1.48

613 1.63

642 1.78

670 1.94

696 2.10

606 2.13

633 2.30

658 2.47

683 2.65

708 2.84

732 3.03

756 3.22

585 2.17

612 2.36

637 2.54

662 2.72

686 2.91

710 3.10

733 3.30

756 3.49

779 3.70

593 2.44

618 2.60

645 2.82

668 3.01

692 3.20

716 3.41

737 3.60

760 3.81

781 4.01

803 4.23

8000 626 2.88

654 3.12

677 3.32

700 3.53

723 3.75

745 3.95

767 4.17

788 4.38

808 4.60

829 4.82

8500 665 3.48

688 3.68

711 3.90

733 4.13

755 4.35

776 4.57

797 4.80

816 5.02

836 5.25

855 5.47

9000 702 4.11

723 4.31

745 4.54

766 4.78

787 5.02

807 5.26

827 5.49

846 5.73

865 5.97

884 6.21

9500 734 4.72

758 5.01

780 5.27

799 5.49

820 5.77

838 5.99

858 6.27

876 6.50

895 6.76

913 7.02

10000 771 5.49

796 5.83

815 6.09

835 6.34

852 6.55

871 6.82

889 7.10

907 7.35

925 7.63

942 7.89

10500 814 6.50

831 6.68

848 6.90

869 7.23

886 7.46

903 7.73

921 8.00

939 8.30

956 8.57

-

11000 848 7.34

866 7.61

885

7.5-hp Standard Motor & Drive

7.92

903 8.19

920 8.46

-

7.5-hp Standard Motor & High Static Drive Accessory

-

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

5000 (a)

6500

7000

(a)

(a)

722 2.27

(b) 746

7.5-hp Standard Motor & Drive

2.43

770 2.60

791 2.76

812 2.92

779 3.41

801 3.61

823 3.81

845 4.01

866 4.22

801 3.90

822 4.10

844 4.31

865 4.53

885 4.75

7500 (a)

824 4.44

845 4.66

866 4.88

886 5.10

905 5.32

8000 849 5.05

869 5.27

889 5.51

908 5.73

927 5.97

8500 875 5.72

895 5.96

913 6.19

932 6.43

951 6.68

9000 902 6.45

921 6.71

938 6.94

956 7.19

975 7.46

9500 930 7.26

948 7.52

965 7.77

983 8.04

10000 959 8.15

976 8.41

-

-

-

-

-

10500

11000

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

7.5-hp Standard Motor & High Static Drive Accessory

-

-

Notes:

1.

For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119

.

2.

For High Evaporator Fan Speed (rpm), reference

Table 87, p. 119

.

3.

For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .

4.

Fan motor heat (MBh) = 3.15 x Fan bhp.

5.

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

6.

For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.

7.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

(b)7.5-hp Standard Motor & Low Static Drive Accessory.

118 RT-PRC028AC-EN

Performance Data

Table 85. Standard motor and drive/fan speed (rpm)

Tons Unit Model Number

12½

15

T/YS*150G3,4,W,K

T/YH*150G3,4,W

T/YS*180G3,4,W,K

T/YH*180G3,4,W

17½ T/YS*210/211G3,4,W,K

T/YH*210G3,4,W

T/YS*240G3,4,W,K 20

T/YH*240G3,4,W

T/YS*300/301G3,4,W,K

T/YH*300G3,4,W

25

T/YH*300G3,4,W with

Reheat

Note: Factory set at 3 turns open.

6 Turns

Open

605

506

605

506

694

581

642

452

559

452

694

5 Turns

Open

650

544

650

544

731

619

683

485

600

485

739

4 Turns

Open

695

582

695

582

768

657

725

518

642

518

784

3 Turns

Open

740

620

740

620

805

695

766

551

683

551

829

2 Turns

Open

785

658

785

658

842

733

808

584

725

584

874

1 Turn

Open

829

694

829

694

881

769

849

619

766

619

919

Closed

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Table 86. Standard motor and low static fan drive

Tons

12½

15

17½

20

25

Unit Model Number

T/YS*150G3,4,W,K

T/YH*150G3,4,W

T/YS*180G3,4,W,K

T/YH*180G3,4,W

T/YS*210/211G3,4,W,K

T/YH*210G3,4,W

T/YS*240G3,4,W,K

T/YH*240G3,4,W

T/YS*300/301G3,4,W,K

T/YH*300G3,4,W with

Reheat

6 Turns

Open

452

450

506

450

581

351

452

351

506

581

5 Turns

Open

485

480

544

480

619

377

485

377

544

619

4 Turns

Open

518

510

582

510

657

403

518

403

582

657

3 Turns

Open

551

540

620

540

695

429

551

429

620

695

2 Turns

Open

584

570

658

570

733

455

584

455

658

733

1Turn

Open Closed

619 N/A

600

694

600

769

480

619

480

694

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

769 N/A

Table 87. Standard motor and high static drive accessory sheave/fan speed (rpm)

Tons

12½

15

17½

20

25

Unit Model Number

T/YS*150G3,4,W,K

T/YH*150G3,4,W

T/YS*180G3,4,W,K

T/YH*180G3,4,W

T/YS*210/211G3,4,W,K

T/YH*210G3,4,W

T/YS*240G3,4,W,K

T/YH*240G3,4,W

T/YS*300/301G3,4,W,K

T/YH*300G3,4,W

T/YH*300G3,4,W with

Reheat

6 Turns

Open

694

829

694

806

694

766

619

719

619

829

806

5 Turns

Open

731

874

731

844

739

808

652

753

652

874

844

4 Turns

Open

768

919

768

882

784

849

685

786

685

919

882

3 Turns

Open

805

964

805

920

829

891

718

820

718

964

920

2 Turns

Open

842

1009

842

958

874

891

751

853

751

1009

958

1 Turn

Open

881

1053

881

994

919

974

786

887

786

1053

994

Closed

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

RT-PRC028AC-EN 119

Performance Data

Table 88. Oversized motor and drive/fan speed (rpm)

Tons

12½

15

17½

20

Unit Model

Number

T/YS*150G3,4,W,K

T/YH*150G3,4,W

T/YS*180G3,4,W,K

T/YH*180G3,4,W

T/YS*210/211G3,4,W,K

T/YH*210G3,4,W

T/YS*240G3,4,W,K

T/YH*240G3,4,W

6 Turns

Open

863

695

695

695

806

806

806

806

5 Turns

Open

919

747

747

747

844

844

844

844

4 Turns

Open

974

799

799

799

882

882

882

882

3 Turns

Open

1030

851

851

851

920

920

920

920

2 Turns

Open

1085

903

903

903

958

958

958

958

1 Turn

Open Closed

1141 N/A

953

953

953

994

994

N/A

N/A

N/A

N/A

N/A

994

994

N/A

N/A

Table 89. Static pressure drop through accessories (inches water column)

Tons

12½

15

6000

2500

4000

5000

6000

4800

6000

7200

4000

5000

6000

4000

5000

6000

4000

5000

4800

6000

7200

4800

6000

7200

3000

4800

6000

7200

Unit Model

Number cfm (a)

Std

Filters (b)

Through

Reheat

Coil

2”

MERV 8

Filter (c)

2”

MERV 13

Filter

(c)

T/YSH150G

T/YSD150G

T/YHH150G

T/YHD150G

T/YSH180G

T/YSD180G

T/YHH180G

T/YHD180G

0.05

0.07

0.10 —

0.05

0.07

0.10 —

0.02 —

0.03 —

0.08

0.11

0.15

0.08

0.11

0.15

0.05 —

0.01 0.00 0.01 0.03

0.02 0.01 0.04 0.08

0.03 0.02 0.05 0.11

0.05 0.03 0.07 0.13

0.03 — 0.06

0.09

0.05 —

0.07 —

0.09

0.11

0.13

0.16

0.07

0.11

0.04 —

0.06 —

0.09 —

0.03 —

0.05 —

0.07 —

0.02 0.01

0.04 0.01

0.06 0.02

0.09 0.03

0.13

0.04

0.06

0.08

0.02

0.05

0.06

0.08

0.18

0.06

0.1

0.13

0.03

0.08

0.11

0.14

0.12

0.15

0.19

0.12

0.15

0.19

Std

Economizer with

OA/RA

Dampers (d)

100%

OA

100%

RA

Low Leak

Economizer with

OA/RA

Dampers (d)

Electric Heater

Accessory (kW)

100%

OA

100%

RA 14–27 36 54

(e)

72

0.33

0.07

0.19

0.26

0.33

0.14

0.19

0.26

0.33

0.19

0.26

0.33

0.19

0.26

0.27

0.14

0.27

0.14

0.27

0.07

0.14

0.2

0.27

0.04

0.01

0.02

0.03

0.04

0.03

0.02

0.03

0.04

0.02

0.03

0.04

0.02

0.03

0.05

0.03

0.05

0.03

0.05

0.03

0.03

0.04

0.05

0.57

0.07

0.16

0.24

0.33

0.36

0.57

0.81

0.27

0.42

0.61

0.27

0.41

0.58

0.25

0.39

0.22

0.33

0.45

0.36

0.57

0.81

0.10

0.22

0.33

0.45

0.10

0.04

0.10

0.16

0.24

0.06

0.10

0.14

0.06

0.10

0.14

0.18

0.29

0.44

0.04

0.07

0.15

0.24

0.35

0.06

0.10

0.14

0.06

0.15

0.24

0.35

0.07

*

0.03

0.05

0.07

0.04

0.07

0.03

0.05

0.07

0.03

0.05

0.07

0.03

0.05

0.06

*

0.03

0.04

0.06

0.04

0.06

0.09

0.03

0.04

0.06

0.03

0.04

0.06

0.03

0.04

0.04

0.06

0.09

0.04

0.06

0.09

*

0.04

0.06

0.09

0.04

0.07

0.04

0.07

*

0.04

0.07

0.1

0.09

*

0.04

0.06

0.09

0.05

0.08

0.04

0.06

0.09

0.04

0.06

0.09

0.04

0.06

0.05

0.08

0.05

0.08

*

0.05

0.08

0.12

120 RT-PRC028AC-EN

Performance Data

Table 89. Static pressure drop through accessories (inches water column) (continued)

Tons

17½

20

25

Unit Model

Number cfm (a)

Std

Filters (b)

Through

Reheat

Coil

2”

MERV 8

Filter (c)

2”

MERV 13

Filter (c)

T/YSH210/

211G

T/YSD210/

211G

T/YHH210G

T/YHD210G

T/YSH240G

T/YSD240G

T/YHH240G

T/YHD240G

T/YSH300/

301G

T/YSD300/

301G

T/YHH300G

T/YHD300G

8000

9600

7000

9000

11000

7000

9000

11000

6400

8000

9600

6400

8000

9600

4000

6400

7000

9000

11000

5000

7000

9000

11000

8400

3500

5600

7000

8400

6400

8000

9600

5600

7000

8400

5600

7000

8400

5600

7000

0.05 —

0.07 —

0.10 —

0.06 —

0.09 —

0.12 —

0.03 —

0.05 —

0.07 —

0.01 0.04

0.04 0.10

0.06 0.13

0.08 0.16

0.06 —

0.09 —

0.13 —

0.02 0.04

0.05 0.10

0.08 0.13

0.10 0.16

0.17

0.21

0.07 —

0.11 —

0.16 —

0.04 —

0.06 —

0.09 —

0.02 0.02 0.03 0.06

0.05 0.05 0.08 0.12

0.08 0.07 0.10 0.15

0.11 0.11 0.14 0.19

0.07

0.11

0.11

0.15

0.15

0.20

0.17

0.09

0.14

0.21

0.22

0.13

0.18

0.25

0.26

0.17

0.23

0.32

0.05 —

0.08 —

0.12 —

0.03 0.02

0.06 0.04

0.10 0.06

0.10

0.08

0.04 0.08

0.09 0.13

0.12 0.18

0.17

0.22

Std

Economizer with

OA/RA

Dampers (d)

100%

OA

100%

RA

Low Leak

Economizer with

OA/RA

Dampers (d)

Electric Heater

Accessory (kW)

100%

OA

100%

RA 14–27 36 54

(e)

72

0.32

0.44

0.26

0.4

0.6

0.26

0.4

0.57

0.22

0.32

0.44

0.22

0.32

0.44

0.11

0.22

0.26

0.4

0.6

0.15

0.26

0.4

0.57

0.35

0.09

0.18

0.26

0.35

0.22

0.32

0.44

0.18

0.26

0.35

0.18

0.26

0.35

0.18

0.26

0.05

0.07

0.04

0.07

0.1

0.04

0.07

0.1

0.04

0.05

0.07

0.04

0.05

0.07

0.03

0.04

0.04

0.07

0.1

0.03

0.04

0.07

0.10

0.06

0.03

0.04

0.04

0.06

0.04

0.05

0.07

0.04

0.04

0.06

0.04

0.04

0.06

0.04

0.04

0.54

0.75

0.77

1.27

1.89

0.43

0.67

0.95

0.37

0.54

0.75

0.64

1.0

1.44

0.16

0.37

0.77

1.27

1.89

0.24

0.43

0.67

0.95

1.11

0.13

0.29

0.43

0.59

0.64

1.0

1.44

0.49

0.77

1.11

0.29

0.43

0.59

0.49

0.77

0.43

0.62

0.13

0.21

0.32

0.33

0.55

0.82

0.27

0.43

0.62

0.11

0.17

0.24

0.10

0.27

0.13

0.21

0.32

0.16

0.33

0.55

0.82

0.19

0.08

0.21

0.33

0.48

0.11

0.17

0.24

0.08

0.13

0.19

0.21

0.33

0.48

0.08

0.13

0.08

0.13

0.18

*

0.08

0.13

0.18

0.05

0.08

0.12

0.05

0.08

0.12

0.05

0.08

0.12

*

0.05

0.08

0.13

*

0.06

0.09

0.12

0.06

0.13

0.08

0.10 0.12

0.14

0.17

0.06

0.09

0.13

0.06

0.09

0.13

0.06

0.09

0.06

0.08

0.10 0.12

0.14

0.06

0.17

0.08

0.10 0.12

0.14

0.17

*

0.06

*

0.08

0.10 0.12

0.14

0.17

0.08

0.13

0.14

0.20

0.10 0.11

0.15

0.18

0.18

0.08

0.13

0.18

0.22

0.15

0.22

0.26

0.10 0.11

0.18

0.26

0.09

0.14

0.20

0.09

0.14

0.20

*

0.09

0.10 0.11

0.15

0.18

0.22

*

0.26

*

0.1

0.15

0.22

0.11

0.18

0.26

0.07

0.11

0.16

0.07

0.11

0.16

0.07

0.11

0.16

*

0.07

0.11

0.16

0.09

0.14

0.20

(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:

- Electric heaters on applications below 320 cfm/ton.

- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.

- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.

(b)Tested with: 2” filters 12½–25 tons.

(c) Difference in pressure drop should be considered when utilizing optional 2” pleated filters.

(d)OA = Outside Air and RA = Return Air.

(e)Nominal kW ratings at 240, 480, 600 volts.

RT-PRC028AC-EN 121

Performance Data

Table 90. Gas fired heating capacities

Tons Unit Model Number Heating Input MBh (a)

Heating Output MBh (a)

12½

15

17½

YS/H*150G-L1

YS/H*150G-H1

150/100

250/175

YS/H*150G-V1 350/140

YS/H*180G-L1 250/175

YS/H*180G-H1

YS/H*180G-V1

YS/H*210G-L1

YS/H*210G-H1

350/250

350/140

250/175

350/250

120/80

200/140

280/112

200/140

280/200

280/112

200/140

280/200

20

YS/H*210G-V1

YS/H*240G-L1

YS/H*240G-H1

YS/H*240G-V1

350/140

250/175

400/300

350/140

280/112

200/140

320/240

280/112

25

YS/H*300G-L1

YS/H*300G-H1

250/175

400/300

200/140

320/240

YS/H*300G-V1 350/140 280/112

(a)For two stage heaters (input or output), second stage is total heating capacity. Second stage/first stage.

Air Temp. Rise, °F

35–65

15–45

25–55

35–65

15–45

25–55

35–65

10–40

25–55

35–65

25–55

35–65

35–65

25–55

35–65

Table 91. Auxiliary electric heat capacity

Tons Unit Model Number kW

Input

Total (a)

(b)

MBh

Output

No. of

Stages kW

Input

MBh

Output kW

Input

12½–15

TS/H*150G3,4,W

TS/H*180G3,4,W

18.00

27.00

(c)

36.00

54.00

61.47

92.15

122.94

184.41

1

2

2

2

18.00

9.00

18.00

36.00

61.47

30.72

61.47

122.94

18.00

18.00

18.00

17½–25

TS/H*210/211G3,4,W

TS/H*240G3,4,W

TS/H*300/301G3,4,W

36.00

54.00

122.94

184.41

2

2

18.00

36.00

61.47

122.94

18.00

18.00

72.00

245.88

2 36.00

122.94

36.00

(a)Heaters are rated at 240V, 380V, 480V, and 600V. For other than rated voltage, CAP = (voltage/rated voltage) 2 x rated cap.

(b)For all input/output categories, does not include fan power or heat.

(c) 27 kW heater can be used with TSD180F4, TSD210F4, TSD240F4, and TSD300F4 only. Cannot be used with oversized motor.

* Indicates both downflow and horizontal units.

MBh

Output

61.43

61.47

61.47

61.47

61.47

122.94

122 RT-PRC028AC-EN

Performance Data

Table 92. Electric heater voltage correction factors (applicable to auxiliary heat capacity)

Nominal

Voltage

240

480

600

Distribution

Voltage

208

230

240

440

460

480

540

575

600

Capacity

Multiplier

0.75

0.92

1.00

0.84

0.94

1.00

0.81

0.92

1.00

Table 93. Air temperature rise across electric heaters (°F) kW

9.00

Stages

1

12½ Tons

5000 cfm

Three Phase

TS*150G

TH*150G

15 Tons

6000 cfm

Three Phase

TS*180G

TH*180G

17½ Tons

7000 cfm

Three Phase

TS*210/211G

TH*210G

20 Tons

8000 cfm

Three Phase

TS*240G

TH*240G

25 Ton

9000 cfm

Three Phase

TS*300/301G

TH*300G

17.30

18.00

27.00

36.00

54.00

72.00

1

1

2

2

2

2

11.4

22.8

34.1

9.5

14.2

(a)

19.0

28.5

12.2

16.3

24.4

32.5

10.7

14.2

21.3

28.5

9.5

12.6

19.0

25.3

Notes:

1.

For minimum design airflow, see airflow performance table for each unit. To calculate temp rise at different airflow, use the following formula:

Temp. rise across Electric Heater = kW x 3414/1.08 x cfm.

2.

*Indicates both downflow and horizontal units.

(a)27 kW heater can be used with TSD180F4, TSD210F4, TSD240F4, and TSD300F4 only. Cannot be used with oversized motor.

Table 94. Hot gas reheat temperature rise (a), (b)

Tons

12½

SCFM

2500

3000

3500

4000

4500

5000

5500

6000

Leaving Evaporator Dry Bulb [°F] (c)

35 40 45 50 55 60 65

30.6 31.8 32.9 33.8 34.7 35.5 36.2

25.7 26.8 27.8 28.7 29.5 30.2 30.8

22.2 23.2 24.1 24.9 25.6 26.3 26.9

19.4 20.4 21.2 22.0 22.6 23.2 23.8

17.3 18.2 19.0 19.7 20.3 20.9 21.5

15.6 16.4 17.2 17.8 18.4 19.0 19.5

14.2 15.0 15.7 16.3 16.9 17.4 17.9

13.0 13.8 14.5 15.1 15.6 16.1 16.5

RT-PRC028AC-EN 123

Performance Data

Table 94. Hot gas reheat temperature rise (a), (b)

Tons SCFM

3000

Leaving Evaporator Dry Bulb [°F] (c)

35 40 45 50 55 60 65

30.4 31.5 32.5 33.3 34.1 34.9 35.5

6400

7200

8000

8800

9600

5000

7000

7700

8400

4000

4800

5600

7200

3500

4200

4900

5600

6300

3600

4200

4800

5400

6000

6600

15

17½

20

25

5800

6600

7400

8000

8800

9600

10400

25.4 26.4 27.3 28.1 28.8 29.4 30.0

21.9 22.8 23.6 24.4 25.1 25.7 26.3

19.1 20.0 20.8 21.5 22.2 22.7 23.3

17.0 17.8 18.6 19.2 19.8 20.4 20.9

15.3 16.1 16.8 17.4 18.0 18.5 19.0

13.9 14.7 15.3 15.9 16.4 16.9 17.4

12.7 13.5 14.1 14.7 15.2 15.6 16.1

34.5 37.9 41.5 45.2 48.5 50.6 50.6

28.0 30.9 33.9 36.8 39.6 42.0 43.8

23.5 26.0 28.6 31.4 34.0 36.2 37.9

20.3 22.4 24.7 27.2 29.7 31.9 33.5

17.9 19.7 21.7 23.8 26.1 28.3 29.9

16.0 17.5 19.3 21.3 23.4 25.3 26.9

14.4 15.8 17.4 19.2 21.1 23.0 24.5

13.2 14.4 15.8 17.4 19.3 21.0 22.5

30.5 31.8 33.0 34.0 35.0 35.8 36.6

25.5 26.7 27.8 28.8 29.6 30.4 31.2

21.8 23.0 24.0 24.9 25.7 26.4 27.1

19.1 20.2 21.1 22.0 22.8 23.4 24.1

17.0 18.0 18.9 19.6 20.3 21.0 21.6

15.3 16.2 17.1 17.8 18.5 19.1 19.6

13.9 14.8 15.6 16.3 16.9 17.5 18.0

12.7 13.6 14.3 15.0 15.6 16.1 16.6

25.5

27.3

29.03

30.4

31.7

32.5

32.4

21.9

19.2

17.1

15.8

14.3

13.1

12.1

23.5

20.7

18.4

17

15.5

14.2

13.1

25.1

22.1

19.7

18.3

16.6

15.2

14

11200

12000

11.2

10.4

12.1

11.2

(a) 70°F OD Ambient Temperature.

(b) For units with the Dehumidification (Hot Gas Reheat) option.

(c) Temperature does not account for indoor fan heat.

13

12.2

26.5

23.4

20.9

19.3

17.6

16.2

14.9

13.9

13

27.5

24.3

21.7

20.3

18.7

17.1

15.8

14.7

13.7

28.4

25.2

22.7

21.1

19.2

17.7

16.4

15.1

14.2

28.8

25.7

23.2

21.6

19.8

18.3

16.9

15.8

14.8

124 RT-PRC028AC-EN

Controls

Economizer Controls

The standard equipment offering is a fixed dry bulb changeover control. In addition, there are two optional controls, Enthalpy and Differential Enthalpy Control.

Enthalpy Control

Replaces the dry bulb control with a wet bulb changeover controller which has a fully adjustable setpoint. Enthalpy control offers a higher level of comfort control, along with energy savings potential, than the standard dry bulb control. This is due to the additional wet bulb sensing capability.

Differential Enthalpy Control

Differential Enthalpy replaces the standard dry bulb control with two enthalpy sensors that compare total heat content of the indoor air and outdoor air to determine the most efficient air source. This control option offers the highest level of comfort control, plus energy efficiency, available.

Remote Potentiometer

Minimum position setting of economizer can be remotely adjusted with this accessory.

Zone Sensors

Zone Sensors are the building occupant’s comfort control devices. They replace the conventional electro-mechanical thermostats.

Note: Zone sensor required for units configured for Single Zone VAV indoor fan system control to enable Single Zone VAV functionality.

Differential Pressure Switches

This factory or field-installed option allows individual fan failure and dirty filter indication. The fan failure switch will disable all unit functions and “flash” the Service LED on the zone sensor. The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation.

Manual Changeover Manual/Automatic

Changeover

Manual/Automatic

Changeover

RT-PRC028AC-EN

Heat, Cool or Off System

Switch. Fan Auto or Off Switch.

One temperature setpoint lever.

Auto, Heat, Cool or Off

System Switch. Fan Auto or

Off Switch. Two temperature setpoint levers.

Auto, Heat, Cool or Off

System Switch. Fan Auto or

Off Switch. Two temperature setpoint levers. Status

Indication LED lights, System

On, Heat, Cool, or Service.

125

Controls

RA Remote Sensor & Room Remote Sensor

The RA Remote Sensor is a Return Air Remote Sensor which can be mounted in the return air duct to report return air temperature. The Room Remote Sensor is a Space Remote Sensor which can be mounted on the wall to report/control from a remote location in the space.

Wireless Zone Sensor

LCD display that provides heat, cool, auto, or off. Includes two temperature setpoints and a lockable setting with °F or

°C indicators.

Manual/Automatic

Changeover

Remote Sensor Integrated Comfort™

System

Auto, Heat, Cool or Off System

Switch. Fan Auto or Off Switch.

Two temperature setpoint levers.

Sensor(s) available for all zone sensors to provide remote sensing capabilities.

Sensor(s) available with optional temperature adjustment and override buttons to provide central control through a Trane

Integrated Comfort™ system.

126 RT-PRC028AC-EN

Programmable Night

Setback

CO

2

Sensor

Controls

Humidity Sensor

RT-PRC028AC-EN

Auto or manual changeover with seven-day programming.

Keyboard selection of Heat,

Cool, Fan, Auto, or On. All programmable sensors have

System On, Heat, Cool, Service

LED/indicators as standard.

Night Setback Sensors have one (1) Occupied, one (1) Unoccupied, and one (1) Override program per day.

The CO

2

sensor shall have the ability to monitor the concentration (parts per million, ppm) of CO

2

(Carbon

Dioxide) in the air. As the CO

2 concentration changes, the outside air damper modulates to meet the current ventilation needs of the zone.

Field installed, wall-mounted or duct-mounted humidity sensor is used to control activation of the hot gas reheat dehumidification option. The humidity sensor can be set for humidity levels between 40 percent and

60 percent relative humidity by adjusting the ReliaTel

Options Module.

Digital Display

Programmable

Thermostat with Built-

In Relative Humidity

Sensing (3H/2C)

Tue

Digital Display

Programmable

Thermostat (3H/2C)

Touchscreen

Programmable

Thermostat (2H/2C)

MON TUE WED

FAN

ON

AUTO

CIRC

SYSTEM

EM HEAT

HEAT

OFF

COOL

AUTO

RESET

CANCEL

PERIOD

PM

THU FRI SAT SUN

HEAT

DEHUMIDIFIER

COOL

DONE EDIT WAKE LEAVE RETURN SLEEP CANCEL

Three Heat/Two Cool digital display thermostat with builtin humidity control and display. This thermostat combines both humidity and dry bulb into one. Fully programmable with night setback.

Three Heat/Two Cool auto changeover digital display thermostat. 7-day programmable stat with night setback shall be available.

Two Heat/Two Cool programmable thermostat with touch screen digital display. Menu-driven programming. Effortless setup. Program each day separately with no need to copy multiple days. All programming can be done on one screen. Easy to read and use. Large, clear backlit digital display.

127

Controls

Digital Display Thermostat (3H/2C)

Three Heat, Two Cool auto changeover digital display thermostat.

Communication Interfaces

Air-Fi™ Wireless Communication - Factory Installed

The factory installed Air-Fi Wireless communication allows customers to benefit from reduced installed/labor cost. This factory installed solution comes pre-wired and tested.

BACnet ® Communications Interface - Factory or Field Installed

The BACnet communications interface allows the unit to communicate directly with a generic open protocol BACnet MS/TP Network Building Automation System Controls.

LonTalk

®

Communications Interface - Factory or Field Installed

The LonTalk communications interface allows the unit to communicate as a Tracer™ LCI-V device or directly with generic LonTalk Network Building Automation System Controls.

Trane Communication Interface (TCI) - Factory or Field Installed

This factory or field-installed micro-processor interface allows the unit to communicate with

Trane’s Integrated Comfort™ system.

128 RT-PRC028AC-EN

Electrical Data

Table 95. Unit wiring with cooling (no electric heat) or gas heat—standard refrigeration system

Tons

Unit Model

Number

Unit Operating

Voltage Range

Standard Indoor Fan Motor

Minimum Circuit

Ampacity (a)

Maximum Fuse Size or Maximum Circuit

Breaker

12½

15

T/YS*150G3

T/YS*150G4

T/YS*150GW

T/YS*150GK

T/YS*180G3

T/YS*180G4

T/YS*180GW

T/YS*180GK

T/YS*210/211G3

187–253

414–506

517–633

342–418

187–253

414–506

517–633

342–418

187–253

36

69

34

61

29

22

31

45

77

45

90

45

80

40

30

40

60

100

17½

20

T/YS*210/211G4

T/YS*210/211GW

T/YS*210GK

T/YS*240G3

T/YS*240G4

T/YS*240GW

T/YS*240GK

T/YS*300/301G3

414–506

517–633

342–418

187–253

414–506

517–633

342–418

187–253

37

34

52

105

50

43

60

112

50

45

70

125

70

60

80

150

25

T/YS*300/301G4

T/YS*300/301GW

T/YS*300GK

414–506

517–633

342–418

53

45

69

70

60

90

(a)For Standard and Oversized Indoor Fan Motor, values do not include power exhaust accessory.

* Indicates both downflow and horizontal units.

Oversized Indoor Fan Motor

Minimum Circuit

Ampacity

Maximum Fuse Size or Maximum Circuit

Breaker

41

37

56

112

54

46

64

39

75

37

67

32

24

32

47

85

50

50

70

150

70

60

80

90

40

30

50

100

50

45

60

110

RT-PRC028AC-EN 129

Electrical Data

Standard Efficiency

Table 96. Unit wiring with electric heat (single point connection)—standard refrigeration system (downflow and horizontal)

Tons

12½

15

17½

20

25

12½

15

17½

20

25

Unit Model

Number

TS*150G3

TS*180G3

TS*210/

211G3

TS*240G3

TS*300/

301G3

TS*150G4

TS*180G4

TS*210/

211G4

TS*240G4

TS*300/

301G4

Heater Model

Number (a)

AYDHTRK318/AYHHTRN318

AYDHTRK336/AYHHTRP336

AYDHTRK354/AYHHTRP354

AYDHTRK318/AYHHTRN318

AYDHTRK336/AYHHTRM336

AYDHTRK354/AYHHTRM354

AYDHTRL336/AYHHTRN336

AYDHTRL354/AYHHTRN354

AYDHTRK372/AYHHTRN372

AYDHTRL336/AYHHTRN336

AYDHTRL354/AYHHTRN354

AYDHTRK372/AYHHTRN372

AYDHTRL336/AYHHTRN336

AYDHTRL354/AYHHTRN354

AYDHTRK372/AYHHTRN372

AYDHTRL418 (AYDHTRK418)

(a)

AYHHTRN418

/

AYDHTRK436/AYHHTRP436

AYDHTRK454/AYHHTRP454

AYDHTRL418 (AYDHTRK418)

(a)

AYHHTRM418

/

AYDHTRK436/AYHHTRM436

AYDHTRK454/AYHHTRM454

AYDHTRL436/AYHHTRN436

AYDHTRL454/AYHHTRN454

AYDHTRK472/AYHHTRN472

AYDHTRL436/AYHHTRN436

AYDHTRL454/AYHHTRN454

AYDHTRK472/AYHHTRN472

AYDHTRL436/AYHHTRN436

AYDHTRL454/AYHHTRN454

AYDHTRK472/AYHHTRN472

Standard Indoor Motor Oversized Indoor Motor

Heater kW

Rating

Control

Stages

208/230 Volts Three Phase

MCA

Max Fuse Size or Max Circuit

Breaker MCA

Max Fuse Size or Max Circuit

Breaker (b)

13.5/18.0

27.0/36.0

40.5/54.0

13.5/18.0

27.0/36.0

40.5/54.0

27.0/36.0

40.5/54.0

54.0/72.0

27.0/36.0

40.5/54.0

54.0/72.0

27.0/36.0

40.5/54.0

2

2

2

2

2

2

2

2

54.0/72.0

2

460 Volts Three Phase

1

2

2

1

2

2

62/69

109/123

155/145

69/69

109/123

155/145

116/131

163/152

172/196

116/131

163/152

172/196

126/140

172/162

182/205

80/80

110/125

175/175

90/90

110/125

175/175

125/150

175/175

200/225

125/150

175/175

200/225

150/150

175/175

200/225

69/77

116/131

163/152

75/77

116/131

163/152

126/140

172/162

182/205

126/140

172/162

182/205

90/90

125/150

175/175

100/100

125/150

175/175

150/150

175/175

200/225

150/150

175/175

200/225

18.0

36.0

54.0

18.0

36.0

54.0

72.0

36.0

54.0

72.0

36.0

54.0

36.0

54.0

72.0

1

2

2

1

2

2

2

2

2

2

2

2

2

2

2

28

62

72

36

65

76

98

69

80

102

62

72

65

76

98

30

70

90

50

70

90

110

70

90

110

70

90

70

90

110

38

65

76

39

69

80

102

65

76

69

80

102

40

70

90

50

70

90

110

70

90

70

90

110

130 RT-PRC028AC-EN

Electrical Data

Standard Efficiency

Table 96. Unit wiring with electric heat (single point connection)—standard refrigeration system (downflow and horizontal) (continued)

Tons

12½

15

17½

20

25

12½

15

Unit Model

Number

TS*150GW

TS*180GW

TS*210/

211GW

TS*240GW

TS*300/

301GW

TS*150GK

TS*180GK

Heater Model

Number (a)

Heater kW

Rating

Control

Stages

575 Volts Three Phase

AYDHTRKW18 (AYDHTRLW18) (a)

AYHHTRNW18

/

18.0

1

AYDHTRMW36/AYHHTRPW36

AYDHTRKW54/AYHHTRPW54

AYDHTRKW18 (AYDHTRMW18) (a)

AYHHTRMW18 (AYHHTRQW18)

/

AYDHTRMW36 (AYDHTRKW36) (a)

AYHHTRMW36 (AYHHTRSW36)

/

AYDHTRKW54/AYHHTRMW54

AYDHTRMW36 (AYDHTRLW36) (a)

AYHHTRMW36 (AYHHTRNW36)

/

AYDHTRLW54/AYHHTRNW54

AYDHTRKW72/AYHHTRNW72

AYDHTRMW36 (AYDHTRLW36) (a)

AYHHTRMW36 (AYHHTRNW36)

/

AYDHTRLW54/AYHHTRNW54

AYDHTRKW72/AYHHTRNW72

AYDHTRMW36 (AYDHTRLW36) (a)

AYHHTRMW36 (AYHHTRNW36)

/

AYDHTRLW54/AYHHTRNW54

AYDHTRKW72/AYHHTRNW72

36.0

54.0

18.0

36.0

54.0

36.0

54.0

72.0

36.0

54.0

72.0

36.0

2

2

2

2

1

2

2

2

2

2

2

2

54.0

72.0

2

2

380 Volts Three Phase

AYDHTRL418 (AYDHTRK418) (a)

AYHHTRN418

/

AYDHTRK436/AYHHTRP436

AYDHTRK454/AYHHTRP454

AYDHTRL418 (AYDHTRK418) (a)

AYHHTRM418

/

AYDTRK436/AYHHTRM436

18.0

36.0

54.0

18.0

36.0

2

2

2

2

2

Standard Indoor Motor Oversized Indoor Motor

MCA

Max Fuse Size or Max Circuit

Breaker MCA

Max Fuse Size or Max Circuit

Breaker (b)

28

50

58

30

50

58

52

61

78

52

61

78

56

65

82

36

52

60

44

30

50

70

45

50

70

60

70

90

60

70

90

60

70

90

45

60

70

60

31

52

61

32

52

61

56

65

82

56

65

82

35

60

70

45

60

70

60

70

90

60

70

90

17½ TS*210GK

AYDTRK454/AYHHTRM454

AYDHTRL436/AYHHTRN436

AYDHTRL454/AYHHTRN454

AYDHTRL436/AYHHTRN436

54.0

36.0

54.0

36.0

2

2

2

2

20 TS*240GK AYDHTRL454/AYHHTRN454

AYDHTRK472/AYHHTRN472

AYDHTRL436/AYHHTRN436

AYDHTRL454/AYHHTRN454

54.0

72.0

36.0

54.0

2

2

2

2

25 TS*300GK

AYDHTRK472/AYHHTRN472 72.0

2

(a) Heater model numbers in parenthesis apply to units with an optional high SCCR rating.

(b)Values do not include power exhaust accessory.

* Indicates both downflow and horizontal units.

64

60

64

82

52

60

56

69

70

87

70

80

80

90

60

70

70

90

90

90

RT-PRC028AC-EN 131

Electrical Data

Standard Efficiency

Table 97. Electrical characteristics—compressor motor and condenser motor—60 cycle—standard efficiency

Tons

12½

15

17½

T/YS*210/211G3

T/YS*210/211G4

T/YS*210/211GW

T/YS*210GK

20

T/YS*240G3

T/YS*240G4

T/YS*240GW

T/YS*240GK

25

Unit

Model No.

T/YS*150G3

T/YS*150G4

T/YS*150GW

T/YS*150GK

T/YS*180G3

T/YS*180G4

T/YS*180GW

T/YS*180GK

T/YS*300/301G3

T/YS*300/301G4

T/YS*300/301GW

T/YS*300GK

No.

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

Volts

208–230

460

575

380

208–230

460

575

380

208–230

460

575

380

208–230

460

575

380

208–230

460

575

380

Phase

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

Compressor Motors

hp (b)

6.9/3.5

6.9/3.5

6.9/3.5

6.9/3.5

9.2/4.5

9.2/4.5

9.2/4.5

9.2/4.5

9.2/4.5

9.2/4.5

9.2/4.5

9.2/4.5

12.9/6.3

12.9/6.3

12.9/6.3

12.9/6.3

13.4/6.9

13.4/6.9

13.4/6.9

13.4/6.9

rpm

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

Amps

RLA

25/13.7

12.2/6.2

9.0/4.8

13.9/8.1

29.4/15.6

14.7/7.7

14.7/5.8

103/38.9

16.6/10.1

160/65.6

29.4/15.6

14.7/7.7

14.7/5.8

103/38

16.6/10.1

160/65.6

44.2/25

21.1/12.8

18.6/9.6

23/12.5

44.2/25

21.1/12.2

(a)

LRA

164/83.1

100/41

78/33

94.3/56

267/110

142/52

267/110

142/52

315/164

158/100

136/78

177/94.3

315/164

158/100

18.6/9 136/78

23.7/13.9

177/94.3

No. Phase

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

Condenser Fan Motors

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

hp

1.0

1.0

1.0

0.5

1.0

1.0

1.0

0.5

1.0

1.0

1.0

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

Amps

FLA

3.8

1.8

1.84

2.1

3.8

1.8

1.84

2.1

2.7

1.35

0.8

1.2

2.7

1.35

0.8

1.2

3.8

1.8

1.84

2.1

(a)For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.

(b)Horsepower for each compressor.

*Indicates both downflow and horizontal units.

(a)

LRA

16.42

7.7

7.4

9.06

16.42

7.7

7.4

9.06

9.65

4.82

3.40

4.10

9.65

4.82

3.40

4.10

16.42

7.7

7.4

9.06

132 RT-PRC028AC-EN

Electrical Data

Standard Efficiency

Table 98. Electrical characteristics—evaporator fan motor—60 cycle—standard and oversized

Tons

Unit Model

Number

T/YS*150G3

No.

Standard Evaporator Fan Motor

Amps (b)

Volts

1 208–230

Phase

3 hp (a)

3.00

FLA

10.6

LRA

81.0

No.

1

Oversized Evaporator Fan Motor

Volts

208–230

Phase

3 hp

5.00

FLA

Amps

16.7

12½

15

17½

20

T/YS*150G4

T/YS*150GW

T/YS*150GK

T/YS*180G3

1

1

460

575

1 380

1 208–230

T/YS*180G4

T/YS*180GW

1

1

460

575

T/YS*180GK 1 380

T/YS*210/211G3 1 208–230

T/YS*210/2114

T/YS*210/211W

T/YS*210GK

T/YS*240G3

1

1

460

575

1 380

1 208–230

T/YS*240G4

T/YS*240GW

1

1

460

575

T/YS*240GK 1 380

T/YS*300/301G3 1 208–230

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3.00

3.00

5.00

3.00

3.00

3.00

5.00

5.00

5.00

5.00

7.50

5.00

5.00

5.00

7.50

7.50

4.8

3.9

9.2

10.6

4.8

3.9

9.2

16.7

7.6

6.1

13.3

16.7

7.6

6.1

13.3

40.5

31.0

66.5

81.0

40.5

31.0

66.5

109.8

54.9

41.6

83.5

109.8

54.9

41.6

83.5

24.2 120.4

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

460

575

208–230

460

575

208–230

460

575

208–230

460

575

3

3

3

3

3

3

3

3

3

3

3

5.00

5.00

5.00

5.00

5.00

7.50

7.50

7.50

7.50

7.50

7.50

7.6

6.1

16.7

7.6

6.1

24.2

11.0

9.0

24.2

11.0

9.0

25

T/YS*300/301G4 1

T/YS*300/301GW 1

460

575

3

3

7.50

7.50

11.0

9.0

74.0

60

T/YS*300GK 1 380 3 7.50

13.3

83.5

— — — — —

(a)Horsepower for each compressor.

* Indicates downflow and horizontal units.

(b)For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.

LRA

109.8

74.0

60.0

120.4

74.0

60.0

54.9

41.6

109.8

54.9

41.6

120.4

Table 99. Electrical characteristics—power exhaust (cooling and gas/electric)

Amps

Tons

12½–25

Volts

208–230

460

575

Phase

1

1

1 hp

3/4

3/4

3/4 rpm

1040

1040

1040

FLA

6.6

3.2

2.1

LRA

13.5

8.4

5.2

RT-PRC028AC-EN 133

Electrical Data

High Efficiency

Table 100.Unit wiring with cooling (no electric heat) or gas heat—high efficiency

Tons

Unit Model

Number

T/YH*150G3

Unit Operating

Voltage Range

187–253

Standard Indoor Fan Motor

Minimum Circuit

Ampacity

64

(a)

Maximum Fuse Size or Maximum Circuit

Breaker

90

12½

15

17½

T/YH*150G4

T/YH*150GW

T/YH*180G3

T/YH*180G4

T/YH*180GW

T/YH*210G3

T/YH*210G4

414–506

517–633

187–253

414–506

517–633

187–253

414–506

30

23

68

33

25

83

41

40

30

90

45

35

110

50

20

T/YH*210GW

T/YH*240G3

T/YH*240G4

T/YH*240GW

T/YH*300G3

517–633

187–253

414–506

517–633

187–253

33

96

44

38

117

45

125

60

50

150

25 T/YH*300G4

T/YH*300GW

414–506

517–633

54

44

70

50

(a)For Standard and Oversized Indoor Fan Motor, values do not include power exhaust accessory.

* Indicates both downflow and horizontal units.

Oversized Indoor Fan Motor

Minimum Circuit

Ampacity

71

Maximum Fuse Size or Maximum Circuit

Breaker

90

36

103

48

41

N/A

N/A

N/A

33

25

74

36

27

91

44

45

125

60

50

N/A

N/A

N/A

45

35

100

50

35

110

60

Table 101. Unit wiring with cooling (no electric heat) or gas heat—dehumidification (hot gas reheat) option (downflow only)

Tons

12½

15

17½

20

25

Unit Model

Number

T/YHD150G3

T/YHD150G4

T/YHD150GW

T/YHD180G3

T/YHD180G4

T/YHD180GW

T/YHD210G3

T/YHD210G4

T/YHD210GW

T/YHD240G3

T/YHD240G4

T/YHD240GW

T/YHD300G3

T/YHD300G4

T/YHD300GW

Unit Operating

Voltage Range

187–253

414–506

517–633

187–253

414–506

517–633

187-253

414-506

517-633

187–253

414–506

517–633

187–253

414–506

517–633

Standard Indoor Fan Motor

Minimum Circuit

Ampacity

113

53

45

115

54

42

73

35

27

67

32

23

84

41

34

(a)

Maximum Fuse Size or Maximum Circuit

Breaker

150

70

50

150

70

50

90

45

35

80

40

30

110

50

45

(a)For Standard and Oversized Indoor Fan Motor, values do not include power exhaust accessory.

Oversized Indoor Fan Motor

Minimum Circuit

Ampacity

Maximum Fuse Size or Maximum Circuit

Breaker

120

57

48

-

-

-

79

38

29

73

35

26

92

45

37

150

70

60

-

-

-

90

40

30

100

45

35

110

50

45

134 RT-PRC028AC-EN

Electrical Data

High Efficiency

Table 102.Unit wiring with electric heat (single point connection)—high efficiency

Tons

12½

15

17½

20

25

12½

15

17½

20

25

Unit Model

Number

TH*150G3

TH*180G3

TH*210G3

TH*240G3

TH*300G3

TH*150G4

TH*180G4

THD180G4

TH*180G4

THD210G4

TH*210G4

THD240G4

TH*240G4

THD300G4

TH*300G4

Heater Model

Number (a)

AYDHTRK318/AYHHTRM318

AYDHTRK336/AYHHTRM336

AYDHTRK354/AYHHTRM354

AYDHTRK318/AYHHTRM318

AYDHTRK336/AYHHTRM336

AYDHTRK354/AYHHTRM354

AYDHTRL336/AYHHTRN336

AYDHTRL354/AYHHTRN354

AYDHTRK372/AYHHTRN372

AYDHTRL336/AYHHTRN336

AYDHTRL354/AYHHTRN354

AYDHTRK372/AYHHTRN372

AYDHTRL336/AYHHTRN336

AYDHTRL354/AYHHTRN354

AYDHTRK372/AYHHTRN372

AYDHTRL418 (AYDHTRK418)

(a)

AYHHTRM418

/

AYDHTRK436/AYHHTRM436

AYDHTRK454/AYHHTRM454

AYDHTRL418 (AYDHTRK418)

(a)

AYHHTRM418

/

AYDHTRK427

AYDHTRK436/AYHHTRM436

AYDHTRK454/AYHHTRM454

AYDHTRL427

AYDHTRL436/AYHHTRN436

AYDHTRL454/AYHHTRN454

AYDHTRK472/AYHHTRN472

AYDHTRL427

AYDHTRL436/AYHHTRN436

AYDHTRL454/AYHHTRN454

AYDHTRK472/AYHHTRN472

AYDHTRL427

AYDHTRL436/AYHHTRN436

AYDHTRL454/AYHHTRN454

AYDHTRK472/AYHHTRN472

54.0

72.0

27.0

36.0

54.0

72.0

27.0

36.0

54.0

27.0

36.0

54.0

72.0

27.0

36.0

Standard Indoor Motor Oversized Indoor Motor

Heater kW

Rating

Control

Stages

208/230 Volts Three Phase

MCA

Max Fuse Size or Max Circuit

Breaker MCA

Max Fuse Size or Max Circuit

Breaker (b)

13.5/18.0

27.0/36.0

40.5/54.0

13.5/18.0

27.0/36.0

40.5/54.0

27.0/36.0

40.5/54.0

54.0/72.0

27.0/36.0

40.5/54.0

54.0/72.0

27.0/36.0

2

2

2

40.5/54.0

54.0/72.0

2

2

460 Volts Three Phase

2

2

2

2

2

2

1

2

2

1

64/69

109/123

155/145

68/69

109/123

155/145

116/131

163/152

172/196

116/131

163/152

172/196

126/140

172/162

182/205

90/90

110/125

175/175

90/90

110/125

175/175

125/150

175/175

200/225

125/150

175/175

200/225

150/150

175/175

200/225

71/77

116/131

163/152

74/77

116/131

163/152

126/140

172/162

182/205

126/140

172/162

182/205

90/90

125/150

175/175

100/100

125/150

175/175

150/150

175/175

200/225

150/150

175/175

200/225

18.0

36.0

54.0

18.0

1

2

2

1

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

35

62

72

35

76

98

56

69

80

102

52

65

76

48

62

72

98

52

65

40

70

90

45

90

110

70

70

90

110

60

70

90

50

70

90

110

60

70

38

65

76

38

80

102

56

69

80

52

65

76

102

56

69

45

70

90

50

90

110

60

70

90

60

70

90

110

60

70

RT-PRC028AC-EN 135

Electrical Data

High Efficiency

Table 102.Unit wiring with electric heat (single point connection)—high efficiency

Tons

Unit Model

Number

Heater Model

Number (a)

Heater kW

Rating

Control

Stages

575 Volts Three Phase

12½ TH*150GW

AYDHTRKW18 (AYDHTRLW18) (a)

AYHHTRMW18 (AYHHTRPW18)

/

AYDHTRMW36/AYHHTRMW36

(AYHHTRRW36)

18.0

36.0

1

2

15 TH*180GW

AYDHTRKW54/AYHHTRMW54

AYDHTRKW18 (AYDHTRMW18)

(a)

AYHHTRMW18 (AYHHTRQW18)

/

AYDHTRMW36 (AYDHTRKW36)

(a)

AYHHTRMW36 (AYHHTRSW36)

/

AYDHTRKW54/AYHHTRMW54

AYDHTRMW36 (AYDHTRLW36)

(a)

AYHHTRMW36 (AYHHTRNW36)

/

54.0

18.0

36.0

54.0

36.0

2

1

2

2

2

17½ TH*210GW

AYDHTRLW54/AYHHTRNW54

AYDHTRKW72/AYHHTRNW72

AYDHTRMW36 (AYDHTRLW36)

(a)

AYHHTRMW36 (AYHHTRNW36)

/

54.0

72.0

36.0

2

2

2

20

25

TH*240GW

TH*300GW

AYDHTRLW54/AYHHTRNW54

AYDHTRKW72/AYHHTRNW72

AYDHTRMW36 (AYDHTRLW36)

(a)

AYHHTRMW36 (AYHHTRNW36)

/

AYDHTRLW54/AYHHTRNW54

AYDHTRKW72/AYHHTRNW72

54.0

72.0

36.0

54.0

72.0

2

2

2

2

2

(a) Heater model numbers in parenthesis apply to units with an optional high SCCR rating.

(b)Values do not include power exhaust accessory.

* Indicates both downflow and horizontal units.

Standard Indoor Motor Oversized Indoor Motor

MCA

Max Fuse Size or Max Circuit

Breaker MCA

Max Fuse Size or Max Circuit

Breaker (b)

28

50

58

28

50

58

52

61

78

52

61

78

56

65

82

30

50

70

35

50

70

60

70

90

60

70

90

60

70

90

31

52

61

31

52

61

56

65

82

56

65

82

35

60

70

35

60

70

60

70

90

60

70

90

136 RT-PRC028AC-EN

Electrical Data

High Efficiency

Table 103.Unit wiring with electric heat (single point connection)—dehumidification (hot gas reheat) refrigeration system

(downflow only)

Tons

12½

15

17½

20

25

12½

15

17½

20

25

Unit Model

Number

THD150G3

THD180G3

THD210G3

THD240G3

THD300G3

THD150G4

THD180G4

THD210G4

THD240G4

THD300G4

Heater Model

Number (a)

AYDHTRK318

AYDHTRK336

AYDHTRK354

AYDHTRK318

AYDHTRK336

AYDHTRK354

AYDHTRL336 / AYHHTRN336

AYDHTRL354/ AYHHTRN354

AYDHTRK372/ AYHHTRN372

AYDHTRL336

AYDHTRL354

AYDHTRK372

AYDHTRL336

AYDHTRL354

AYDHTRL372

AYDHTRL418 (AYDHTRK418)

(a)

AYDHTRK436

AYDHTRK454

AYDHTRL418 (AYDHTRK418)

(a)

AYDHTRK427

AYDHTRK436

AYDHTRK454

AYDHTRL427

AYDHTRL436 / AYHHTRN436

AYDHTRL454/ AYHHTRN454

AYDHTRK472/ AYHHTRN472

AYDHTRL427

AYDHTRL436

AYDHTRL454

AYDHTRK472

AYDHTRL427

AYDHTRL436

AYDHTRL454

AYDHTRK472

Standard Indoor Motor Oversized Indoor Motor

Heater kW

Rating

Control

Stages

208/230 Volts Three Phase

MCA

Max Fuse Size or Max Circuit

Breaker MCA

Max Fuse Size or Max Circuit

Breaker (b)

72.0

27.0

36.0

54.0

72.0

36.0

54.0

72.0

27.0

36.0

54.0

13.5/18.0

27.0/36.0

40.5/54.0

13.5/18.0

27.0/36.0

40.5/54.0

27.0/36.0

40.5/54.0

54.0/72.0

27.0/36.0

40.5/54.0

54.0/72.0

27.0/36.0

40.5/54.0

54.0/72.0

2

2

2

460 Volts Three Phase

18.0

1

36.0

2

54.0

18.0

27.0

36.0

54.0

27.0

2

1

2

2

2

2

2

2

2

2

2

2

1

2

2

1

2

2

2

2

2

2

2

2

2

2

2

2

2

69

80

102

57

69

80

38

65

76

38

52

65

76

56

102

-

-

-

-

70

90

110

70

70

90

40

70

90

45

50

70

90

60

110

70

70

90

110

65

76

98

53

65

76

35

62

72

35

48

62

72

52

98

56

69

80

102

67/69

109/123

155/145

73/73

109/123

155/145

116/131

163/152

172/196

116/131

163/152

172/196

126/140

172/162

182/205

80/80

110/125

175/150

90/90

110/125

175/175

125/150

175/175

200/225

125/150

175/175

200/225

150/150

175/175

200/225

73/77

116/131

163/152

79/79

116/131

163/152

126/140

172/162

182/205

126/140

172/162

182/205

-

-

-

90/90

125/150

175/175

100/100

125/150

175/175

150/150

175/175

200/225

150/150

175/175

200/225

-

-

-

70

90

110

70

70

90

40

70

90

45

60

70

90

60

110

-

-

-

-

RT-PRC028AC-EN 137

Electrical Data

High Efficiency

Table 103.Unit wiring with electric heat (single point connection)—dehumidification (hot gas reheat) refrigeration system

(downflow only)

Tons

12½

15

17½

20

25

Unit Model

Number

THD150GW

THD180GW

THD210GW

THD240GW

THD300GW

Heater Model

Number (a)

AYDHTRKW18 (AYDHTRLW18) (a)

AYDHTRMW36

AYDHTRKW54

AYDHTRKW18 (AYDHTRMW18)

(a)

AYDHTRMW36 (AYDHTRKW36)

(a)

AYDHTRKW54

AYDHTRLW36 / AYHHTRNW36

AYDHTRLW54/ AYHHTRNW54

AYDHTRKW72/ AYHHTRNW72

AYDHTRMW36 (AYDHTRLW36)

(a)

AYDHTRLW54

AYDHTRKW72

AYDHTRL336

AYDHTRL354

AYDHTRK372

Heater kW

Rating

575 Volts Three Phase

18.0

1

36.0

54.0

18.0

2

2

1

36.0

54.0

36.0

54.0

72.0

36.0

54.0

72.0

36.0

54.0

72.0

Control

Stages

2

2

2

2

2

2

2

2

2

2

2

(a) Heater model numbers in parenthesis apply to units with an optional high SCCR rating.

(b)Values do not include power exhaust accessory.

Standard Indoor Motor Oversized Indoor Motor

MCA

Max Fuse Size or Max Circuit

Breaker MCA

Max Fuse Size or Max Circuit

Breaker (b)

61

78

56

65

82

61

78

52

28

50

58

28

50

58

52

70

90

60

70

90

70

90

60

30

50

70

35

50

70

60

65

82

-

-

-

65

82

56

31

52

61

31

52

61

56

70

90

-

-

-

70

90

60

35

60

70

35

60

70

60

Table 104.Electrical characteristics—compressor motor and condenser motor—60 cycle—high efficiency

Tons Model No. No.

T/YH*150G3 2

12½

15

17½

20

25

Unit

T/YH*150G4

T/YH*150GW 2

T/YH*180G3 2

T/YH*180G4 2

T/YH*180GW

T/YH*210G3

T/YH*210G4 2

T/YH*210GW 2

T/YH*240G3

T/YH*240G4

2

2

2

2

2

T/YH*240GW 2

T/YH*300G3 3

T/YH*300G4 3

T/YH*300GW 3

Volts

208–230

460

575

208–230

460

575

208–230

460

575

208–230

460

575

208–230

460

575

Phase

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

hp

Compressor Motors

(b)

5.6/3.67

5.6/3.67

5.6/3.67

7.5/4.75

7.5/4.75

7.5/4.75

8.6/4.75

8.6/4.75

8.6/4.75

11.7/6.9

11.7/6.9

11.7/6.9

12.8/6.9

12.8/6.9

12.8/6.9

rpm

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

3450

RLA

27.5/13.6

Amps (a)

LRA

191/100

12.8/6.1

10.38/4.2

28.3/15.9

14.7/7.0

11.3/5.1

34.1/15.6

17.3/7.7

13.32/5.8

41.0/19.6

19.75/8.2

16.7/6.6

19.6/19.6/36.63

8.2/8.2/18.26

100/41

78/33

240/110

130/52

93.7/39.5

240/110

140/52

107.6/38.9

304/136

147/66.1

122/55.3

136/136/240

66.1/66.1/140

Condenser Fan Motors

No. Phase hp

2

2

2

2

2

2

2

2

2

2

2

2

2

2

6.6/6.6/14.06 55.3/55.3/107.6 2

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

0.5

0.5

0.5

0.5

0.5

0.5

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Amps (a)

FLA

2.7

1.35

0.8

2.7

1.35

0.8

3.8

1.8

1.84

3.8

1.8

1.84

3.8

1.8

1.84

(a)For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.

(b)Horsepower for each compressor.

*Indicates both downflow and horizontal units.

LRA

9.65

4.82

3.40

9.65

4.82

3.40

16.42

7.7

7.4

16.42

7.7

7.4

16.42

7.7

7.4

138 RT-PRC028AC-EN

Electrical Data

High Efficiency

Table 105.Electrical characteristics—compressor motor and condenser motor—60 cycle—dehumidification (hot gas reheat) option (downflow only)

15

17½

Tons Unit Model No. No.

T/YHD150G3 2

12½ T/YHD150G4 2

T/YHD150GW

T/YHD180G3

T/YHD180G4

T/YHD180GW

T/YHD210G3

T/YHD210G4

2

2

2

2

2

2

Volts

208–230

460

575

208–230

460

575

208-230

460

Phase

3

3

3

3

3

3

3

3

Compressor Motors

hp (b)

5.6

5.6

5.6

6.9

6.9

6.9

7.5 / 6.9

7.5 / 6.9

rpm

3450

3450

3450

3450

3450

3450

3450

3450

Amps (a)

RLA

22.4/22.4

10.6/10.6

LRA

149/149

75/75

7.7/7.7

26.2/26.2

13.2/13.2

54/54

149/149

75/75

11.5/11.5

54/54

27.6 / 26.2 203 / 164

14.1 / 13.2

98 / 100

No. Phase hp

2 3 0.5

2 3 0.5

2

2

2

2

2

2

Condenser Fan Motors

Amps

(a)

3

3

3

3

3

3

0.5

0.5

0.5

0.5

1.0

1.0

FLA

2.7

1.35

0.8

2.7

1.35

0.8

3.8

1.8

20

T/YHD210GW

T/YHD240G3

T/YHD240G4

2

2

2

575

208–230

460

3

3

3

7.5 / 6.9

10

10

3450

3450

3450

11.6 / 11.5

39.1/39.1

18.6/18.6

84 / 78

267/267

142/142

2

2

2

3

3

3

1.0

1.0

1.0

1.84

3.8

1.8

25

T/YHD240GW

T/YHD300G3

T/YHD300G4

2

2

2

575

208–230

460

3

3

3

10

10

10

3450

3450

3450

15.4/15.4

36.6/36.6

17.2/17.8

103/103

240/240

140/140

2

2

2

3

3

3

1.0

1.0

1.0

1.84

3.8

1.8

T/YHD300GW 2 575 3 10 3450 12.9/12.9

108/108 2 3 1.0

1.84

(a)For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.

(b)Horsepower for each compressor.

LRA

9.65

4.82

3.40

9.65

4.82

3.40

16.42

7.7

7.4

16.42

7.7

7.4

16.42

7.7

7.4

Table 106.Electrical characteristics—evaporator fan motor—60 cycle—standard and oversized

Tons

Unit Model

Number No.

Standard Evaporator Fan Motor

Amps (b)

Volts Phase hp (a) FLA LRA No.

Oversized Evaporator Fan Motor

Amps

Volts Phase hp FLA LRA

12½

15

17½

T/YH*150G3

T/YH*150G4

T/YH*150GW

T/YH*180G3

T/YH*180G4

T/YH*180GW

T/YH*210G3

T/YH*210G4

1

1

1

1

1

1

1

1

208–230

460

575

208–230

460

575

208–230

460

3

3

3

3

3

3

3

3

5

5

3

3

3

3

3

3

10.6

4.8

3.9

10.6

4.8

3.9

16.7

7.6

81

40.5

31

81

40.5

31

109.8

54.9

1

1

1

1

1

1

1

1

208–230

460

575

208–230

460

575

208–230

460

3

3

3

3

3

3

3

3

5

5

7.5

7.5

5

5

5

5

16.7

7.6

6.1

16.7

7.6

6.1

24.2

11

20

T/YH*210GW

T/YH*240G3

T/YH*240G4

T/YH*240GW

1

1

1

1

575

208–230

460

575

3

3

3

3

5

5

5

5

6.1

16.7

7.6

6.1

41.6

109.8

54.9

41.6

1

1

1

1

575

208–230

460

575

3

3

3

3

7.5

7.5

7.5

7.5

9

24.2

11

9

25

T/YH*300G3

T/YH*300G4

1

1

208–230

460

3

3

7.5

7.5

24.2

11

120.4

74

T/YH*300GW 1 575 3 7.5

9 60 — — — — — —

(a)Horsepower for each compressor.

*Indicates both downflow and horizontal units.

(b)For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.

60

120.4

74

60

109.8

54.9

41.6

109.8

54.9

41.6

120.4

74

RT-PRC028AC-EN 139

Electrical Data

Table 107. Electrical characteristics—power exhaust (cooling and gas/electric)

Amps

Tons

12½–25

Volts

208–230

460

575

Phase

1

1

1 hp

3/4

3/4

3/4 rpm

1040

1040

1040

FLA

6.6

3.2

2.1

LRA

13.5

8.4

5.2

140 RT-PRC028AC-EN

Jobsite Connections

Table 108.Typical number of wires

Zone Sensors

A Manual Changeover..............................

Manual/Auto Changeover......................

4

5

Manual/Auto Changeover with

Status Indication LEDs.........................

10

Programmable Night Setback with Status Indication LEDs...................

Thermostats

B

7

3 Power Wires + 1 Ground Wire (three phase)

2 Power Wires + 1 Ground Wire (single phase)

ZONE SENSOR OR

THERMOSTAT

A

B

DISCONNECT

SWITCH

(BY OTHERS)

ROOFTOP

UNIT

Notes:

• For specific wiring information, see the installation instructions.

• All wiring except power wire is low voltage.

• All customer supplied wiring to be copper and must conform to applicable electrical codes and local electric codes. Wiring shown dotted is to be furnished and installed by the customer.

• Zone sensors are required for units configured for Single Zone VAV indoor fan system control in order to enable Single Zone VAV functionality.

RT-PRC028AC-EN 141

Dimensional Data

Figure 1.

Cooling with optional electric heat and gas/electric models—12½ tons standard efficiency

Figure 2.

Cooling with optional electric heat and gas/electric models—12½ tons standard efficiency horizontal unit clearance

CLEARANCE 48”

1219 MM

CLEARANCE 60”

1524 MM

SUPPLY

CLEARANCE 72”

1829 MM

RETURN

FILTER ACCESS DOOR

HORIZONTAL UNITS

ONLY

HORIZONTAL

CONDENSATE

DRAIN CONNECTION

1.0 IN. NPT

CLEARANCE 38”

965 MM

CLEARANCE 18”

457 MM

142 RT-PRC028AC-EN

Dimensional Data

Figure 3.

Cooling with optional electric heat and gas/electric models 12½ tons standard efficiency—roof curb

Figure 4.

Cooling with optional electric heat and gas/electric models 12½ tons standard efficiency—downflow duct connections—field fabricated

26 5/16

Notes:

• Duct flanges mount 7-7/16” down inside the curb on the 1-1½” curb flanges.

• Roofcurb is intended for downflow use only.

RT-PRC028AC-EN 143

Dimensional Data

Figure 5.

Cooling with optional electric heat and gas/electric models—12½ tons standard efficiency—downflow unit supply/return and unit clearance

Figure 6.

Cooling with optional electric heat and gas/electric models—15–25 tons standard efficiency & 12.5 ton high efficiency

144 RT-PRC028AC-EN

Dimensional Data

Figure 7.

Cooling with optional electric heat and gas/electric models—15–25 tons high efficiency

Figure 8.

Cooling with optional electric heat and gas/electric models—15–25 tons standard efficiency, 12½–25 tons high efficiency—unit clearance and horizontal unit supply/return

RT-PRC028AC-EN 145

Dimensional Data

Figure 9.

Cooling with optional electric heat and gas/electric models—15–25 tons standard efficiency, 12½–25 tons high efficiency—roof curb

Figure 10. Cooling with optional electric heat and gas/electric models—15–25 tons standard efficiency, 12½–25 tons high efficiency—downflow duct connections—field fabricated

9

Notes:

• Duct flanges mount 7-7/16” down inside the curb on the 1-1½” curb flanges.

• Roofcurb is intended for downflow use only.

1”

25.4 MM

CURB FLANGE

LONG SIDES

SHORT SIDES

146 RT-PRC028AC-EN

Dimensional Data

Figure 11. Cooling with optional electric heat and gas/electric models—15–25 tons standard efficiency, 12½–25 tons high efficiency—downflow unit clearance

Figure 12. Downflow & horizontal condensate locations

Table 109.Standard efficiency units (cooling and gas/electric)

Tons

12½

15–25

A B C

Downflow Only

D F

26 7/16 22 1/2 18 11/16 4 1/4

26 7/16 28 3/4 19 15/16 4 1/4

4 1/4

4 1/4

G H

62 7/16 54 11/16

76 5/16 68 11/16

Condensate

Drain Size

1 NPT

1 NPT

Condensate Drain

Location

Downflow

J

Horizontal

K

25 5/8

26 3/4

6

5 3/8

RT-PRC028AC-EN 147

Dimensional Data

Table 110. High efficiency units (cooling and gas/electric)

Tons A B C

Downflow Only

D

12½–25 26 7/16 28 3/4 19 15/16 4 1/4

F G H

4 1/4 76 5/16 68 11/16

Condensate

Drain Size

1 NPT

Condensate Drain

Location

Downflow Horizontal

J K

26 3/4 5 3/8

Table 111. Cooling unit—swing diameter & through the base electrical

Unit Model #

TSD150G

TSD180–300/301G, THD150–300G

TSH150G

TSH180–301G, THH150–300G

Note: All dimensions are in inches.

A

42 3/8

29 1/2

42 3/8

29 1/2

B

48 3/8

56

N/A

N/A

C

31

38 1/2

31

38 1/2

D

N/A

18 1/2

N/A

18 1/2

E

N/A

N/A

12

14

TOP VIEW SHOWING THROUGH THE BASE

ELECTRICAL UTILITY LOCATIONS AND ACCESS PANEL SWING CLEARANCES.

SWING RADIUS (E)

HORIZONTAL FILTER

ACCESS PANEL

SWING RADIUS (A)

ID SECTION

ACCESS PANEL

SWING RADIUS (D)

ID FAN SECTION

ACCESS PANEL

B

6 7/8"

THROUGH THE

BASE ELECTRICAL

SWING RADIUS (C)

OD SECTION

ACCESS PANEL

148 RT-PRC028AC-EN

Dimensional Data

Table 112.Gas/electric unit—swing diameter & through the base electrical; height of gas pipe

Unit Model #

YSD150G

YSD180–301G, YHD150–300G

YSH150G

YSH180–301G, YHH150–300G

Note: All dimensions are in inches.

A

42 3/8

29 1/2

42 3/8

29 1/2

B

66 3/8

77 7/8

N/A

N/A

C

48 3/8

56

N/A

N/A

D

N/A

18 1/2

N/A

18 1/2

E

N/A

N/A

12

14

F

31

38 1/2

31

38 1/2

TOP VIEW SHOWING THROUGH THE BASE

ELECTRICAL UTILITY LOCATIONS AND ACCESS PANEL SWING CLEARANCES.

SWING RADIUS (E)

HORIZONTAL FILTER

ACCESS PANEL

SWING RADIUS

(A ) ID SECTION

ACCESS PANEL

SWING RADIUS (D) ID FAN SECTION

ACCESS PANEL

Figure 13. Fresh air hood (horizontal units)

C

B

6 7/8" 7 3/8"

THROUGH

THE BASE

ELECTRICAL

THROUGH THE

BASE GAS

SEE DETAIL A

SWING RADIUS (F) OD SECTION

ACCESS PANEL

Figure 14. Fresh air hood (downflow units)

RT-PRC028AC-EN 149

Dimensional Data

Figure 15. Power exhaust—downflow economizers

Figure 16. Power exhaust—downflow economizers—side view

Figure 17. Economizer—horizontal units

C

POWER EXHAUST w i th DOWNFLOW

ECONOMIZERS only, SIDE VIEW

Figure 18. Economizer—downflow units

Note: When applying economizer to horizontal units, connected ductwork must be run full size to allow proper operation of economizer damper.

Table 113.Power exhaust dimensions

Unit Model # A B (a)

T/YS*150G

T/YH*150G, T/YS*180–301G, T/YH*180-300G

17½

19½

53¾

64¾

(a)Horizontal dimension only. Downflow economizer is width of end panel.

(b)Power exhaust is applied on downflow economizer only.

C (b)

36

39

150 RT-PRC028AC-EN

Weights

Table 114.Maximum unit & corner weights (lb) and center of gravity dimensions (in.) cooling with optional electric heat units only

Tons

Unit

Model No.

Weights (lb) (a), (b)

Shipping Net A

Corner Weights (c)

B C D

Center of Gravity (in.)

Length Width

12½

15

TS*150G

TH*150G

THD150G(Reheat Units)

TS*180G

TH*180G

THD180G (Reheat Units)

1745

2299

2390

2194

2519

2469

1373

1868

1959

1763

2076

2026

516

632

693

575

619

701

364

503

470

480

564

491

208

345

337

338

425

360

285

391

458

370

469

474

44

55

50

56

58

51

25

33

34

34

36

35

17½

20

25

TS*210/211G

TH*210G

THD210G (Reheat Units)

TS*240G

TH*240G

THD240G (Reheat Units)

TS*300/301G

TH*300G

2251

2480

2514

2334

2550

2534

2376

2551

1819

2037

2071

1902

2107

2091

1945

2108

583

622

736

615

671

751

624

672

494

542

495

498

552

497

512

556

354

399

360

357

401

361

369

400

388

474

480

433

483

482

440

481

57

56

50

55

55

50

55

55

34

36

34

35

35

34

35

35

THD300G (Reheat Units) 2576 2133 738 522 385 487 52 34

(a)Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.

(b)Weights do not include additional factory or field installed options/accessories. For option/accessory additional weights, reference Table 116, p. 152

to be added to unit weights.

(c) Corner weights are given for information only. 12½–25 ton models must be supported continuously by a curb or equivalent frame support.

* Indicates both downflow and horizontal units.

RT-PRC028AC-EN 151

Weights

Table 115.Maximum unit & corner weights (lb) and center of gravity dimensions (in.) gas/electric heat units only

Tons

Unit

Model No.

Weights (lb) (a) , (b)

Shipping Net A

Corner Weights (c)

B C D

Center of Gravity (in.)

Length Width

12½

15

YS*150G

YH*150G

YHD150G (Reheat Units)

YS*180G

YH*180G

YHD180G (Reheat Units)

1820

2402

2465

2269

2665

2544

1448

1971

2034

1838

2222

2101

537

680

714

595

665

722

381

515

487

497

602

508

225

352

354

355

453

377

306

423

478

390

503

494

45

54

50

56

58

51

26

33

34

34

36

35

17½

20

25

YS*210/211G

YH*210G

YHD210G (Reheat Units)

YS*240G

YH*240G

YHD240G (Reheat Units)

YS*300/301G

YH*300G

2326

2629

2589

2409

2700

2609

2451

2734

1894

2186

2146

1977

2257

2166

2020

2291

604

670

756

635

719

771

644

734

511

581

512

515

591

514

529

603

371

427

377

374

430

378

386

432

409

508

500

454

517

503

461

523

57

56

50

55

55

50

55

55

35

36

34

35

35

34

35

35

YHD300G (Reheat Units) 2651 2208 759 539 402 508 52 35

(a)Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.

(b)Weights do not include additional factory or field installed options/accessories. For option/accessory additional weights, reference Table 116, p. 152

to be added to unit weights.

(c) Corner weights are given for information only. 12½–25 ton models must be supported continuously by a curb or equivalent frame support.

* Indicates both downflow and horizontal units.

Table 116.Factory installed options (FIOPS)/accessory net weight (lb) (a), (b)

Accessories

Standard Economizer

Low Leak Economizer

Manual Outside Air

Damper

Motorized Outside Air

Damper

Power Exhaust (c)

Roof Curb

(c)

Oversized Motor

Hail Guard

Hinged Access Doors (d)

Powered Conv. Outlet

Through the Base

Electrical

Circuit Breaker

Disconnect

Smoke Detector Supply

Smoke Detector Return

Novar

High Static Drive Kit (e)

B Cabinet

T/YSD150G T/YSH150G

65

180

50

180

C Cabinet

T/YSD180-301G

T/YHD150G

T/YSH180-301G

T/YHH150G

80

250

65

250

C+ Cabinet

T/YHD180-300G T/YHH180-300G

80

250

65

250

32

60

95

205

5

34

27

38

23

10

10

5

5

7

2

32

60

34

27

38

5

23

10

10

5

5

7

2

32

75

95

235

5

43

27

38

23

10

10

5

5

7

2

32

75

43

27

38

5

23

10

10

5

5

7

2

32

75

95

235

5

51

27

38

23

10

10

5

5

7

2

32

75

51

27

38

5

23

10

10

5

5

7

2

152 RT-PRC028AC-EN

Weights

Table 116.Factory installed options (FIOPS)/accessory net weight (lb) (a), (b)

B Cabinet C Cabinet

T/YSD180-301G

T/YHD150G

T/YSH180-301G

T/YHH150G Accessories

Low Static Drive Kit (e)

LP Gas Conversion

All Zone Sensors

Electric Heaters

6–23 kW (f) (g)

27–36 kW

(f) (g)

54 kW

(f) (g)

72 kW (f) (g)

(i)

Stainless Steel Heat

Exchanger

150 MBh

250 MBh

350 MBh

400 MBh (j)

T/YSD150G T/YSH150G

2

5

1

28/21

31/27

38/32

50

50

75

2

5

1

28/21

31/27

38/32

50

50

75

5

1

28/21 (h)

33/27

40/32

43/34

50 (h)

50

75

75

5

1

28/21 (h)

33/27

40/32

43/34

50

(h)

50

75

75

Stainless Steel Drain

Pan

VFD

3 & 5 HP

7.5 HP

(k)

(i)

6.6

32

6.6

34

8.1

32

63

8.1

34

65

(a)Net weight should be added to unit weight when ordering factory-installed accessories.

(b)Weights for FIOP accessories not listed are < 5 lb.

(c) Downflow only.

(d)An additional 30lbs should be added to the shipping weight when hinged door option is ordered.

(e)Not available on all models (see Fan Performance tables for specific models).

(f) For 600V heaters net weights are same as 480V heaters.

(g)To estimate shipping weight add 5 lb to net weight.

(h)Applicable to T/YH*150G units only.

(i) Not applicable to T/YH*150-180G, and T/YS*180G units.

(j) Applicable to T/Y**240-300* units only.

(k)Not applicable to T/Y**300* units.

T/YHD180-300G T/YHH180-300G

5

1

5

1

33/27

40/32

43/34

50

75

75

8.1

32

63

C+ Cabinet

33/27

40/32

43/34

50

75

75

8.1

34

65

RT-PRC028AC-EN 153

Mechanical Specifications

General

The units shall be dedicated downflow or horizontal airflow. The operating range shall be between

115°F and 0°F in cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and blower rotation and control sequence, before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be UL listed and labeled, classified in accordance to UL 1995/C 22.2, 236-05 3 rd Edition.

Packaged Rooftop units cooling, heating capacities, and efficiencies are AHRI certified within scope of AHRI Standard 340/360 (I-P) and ANSIZ21.47 and 10 CFR Part 431 pertaining to Commercial Warm

Air Furnaces (gas heating units).

Casing

Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit's surface shall be tested 672 hours in a salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the unit. In order to ensure a water and air tight seal, service panels shall have lifting handles and no more than three screws to remove.

All exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2-inch,

1-pound density foil-faced, fire-resistant, permanent, odorless, glass fiber material. The base of the downflow unit shall be insulated with 1/2-inch, 1-pound density foil-faced, closed-cell material. The downflow unit’s base pan shall have no penetrations within the perimeter of the curb other than the raised 11/8-inch high supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting.

Compressors

All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps.

Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus

10 percent of nameplate voltage. Internal overloads shall be provided with the scroll compressors.

All models shall have crankcase heaters, phase monitors and low and high pressure control as standard. Dual compressors are available on all standard efficiency models and 12.5 to 20 tons high efficiency models and allow for efficient cooling utilizing 3 stages of compressor operation (high efficiency models only). 25 tons high efficiency units have 3 compressors for up to 4 stages of compressor operation.

Controls

Unit shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device. ReliaTel controls shall be provided for all 24-volt control functions. The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized control shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection.

Crankcase Heaters

These band heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or low ambient conditions. These are standard on all Voyager models.

Defrost Controls

Adaptive demand defrost shall be provided to permit defrost wherever coil icing conditions begin to significantly reduce unit capacity.

154 RT-PRC028AC-EN

RT-PRC028AC-EN

Mechanical Specifications

Discharge Line Thermostat

A bi-metal element discharge line thermostat is installed as a standard option on the discharge line of each system. This standard option provides extra protection to the compressors against high discharge temperatures in case of loss of charge, extremely high ambient and other conditions which could drive the discharge temperature higher. Discharge line thermostat is wired in series with high pressure control. When the discharge temperature rises above the protection limit, the bi-metal disc in the thermostat switches to the off position, opening the 24 Vac circuit. When the temperature on the discharge line cools down, the bi-metal disc closes the contactor circuit, providing power to the compressor. When the thermostat opens the fourth time, the ReliaTel control must be manually reset to resume operation on that stage.

Evaporator and Condenser Coils

Microchannel coils will be burst tested by the manufacturer. Internally finned, 5/16” copper tubes mechanically bonded to a configured aluminum plate fin shall be standard on high efficiency models and microchannel shall be standard on standard efficiency for evaporator coils.

Microchannel condenser coils shall be standard on all units. Coils shall be leak tested to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 225 psig and pressure tested to 450 psig. Sloped condensate drain pans are standard.

Filters

Two inch standard filters shall be factory supplied on all units. Optional MERV 8 or MERV 13 filters with filter removal tool shall be available.

Gas Heating Section

The heating section shall have a drum and tube heat exchanger design using corrosion resistant steel components. A forced combustion blower shall supply premixed fuel to a single burner ignited by a pilotless hot surface ignition system.

In order to provide reliable operation, a negative pressure gas valve shall be used on standard furnaces and a pressure switch on furnaces with modulating heat that requires blower operation to initiate gas flow. On an initial call for heat, the combustion blower shall purge the heat exchanger

45 seconds before ignition.

After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat. Units shall be suitable for use with natural gas or propane (field installed kit) and shall also comply with California requirements for low NO x

emissions. The 12½–

25 tons shall have two stage heating (Gas/Electric only).

Indoor Fan

Units above shall have belt driven, FC centrifugal fans with adjustable motor sheaves. Units with standard motors shall have an adjustable idler-arm assembly for quick-adjustment of fan belts and motor sheaves. All motors shall be thermally protected. Oversized motors shall be available for high static application. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT).

Outdoor Fans

The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position. The fan motor(s) shall be permanently lubricated and shall have builtin thermal overload protection.

Phase Monitor

The Phase Monitor is a three-phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating input voltage range of 190–600 Vac, and LED indicators for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition.

155

Mechanical Specifications

Refrigerant Circuits

Each refrigerant circuit shall have independent fixed orifice or thermostatic expansion devices, service pressure ports, and refrigerant line filter driers factory installed as standard. An area shall be provided for replacement suction line driers. Thermal Expansion Valves (TXVs) shall be standard on all high efficiency units.

Unit Top

The top cover shall be one piece, or where seams exist, double hemmed and gasket sealed to prevent water leakage.

Variable Frequency Drive

Variable Frequency Drives are factory installed and tested to provide supply fan motor speed modulation, as well as modulating gas heat. VFDs on the supply fan, as compared to inlet guide vanes or discharge dampers, are quieter, more efficient, and are eligible for utility rebates. All VFDs are designed to allow bypass if required.

Note: It has to be hard wired with relay and removed for temporary operations; see wave 121927.

Bypass control will simply provide full nominal airflow in the event of drive failure.

Modulating gas heat models with VFDs allow tighter space temperature control with less temperature swing.

Factory Installed Options

CO

2

Sensor Wiring

The unit wiring for field installed C0

2

sensors. Factory-installed C0

2

sensor wiring saves time and ensures proper unit connections for the field installed C0

2

sensor kits.

Complete Coat™ Microchannel Condenser Coil

The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number of different types of heat exchangers. The coating is selected to provide excellent resistance and durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salty air, and other corrosive environments. This coating shall be available on microchannel condenser coils.

Condensate Overflow Switch

This option shall shut the unit down in the event that a clogged condensate drain line prevents proper condensate removal from the unit.

Fault Detection & Diagnostics (FDD)

This offering meets the mandatory requirement of Title 24. This option provides detection of the following faults: Air temperature sensor failure/fault, not economizing when it should, economizing when it should not, damper not modulating, and excessive outdoor air. The FDD system shall be certified by the Energy Commission as meeting the requirements.

High Efficiency Motors

This option is available with efficiency ratings from 86.5 up to 91.0. It is not available for all models.

High Short Circuit Current Rating

Unit shall be provided with electrical subsystem that will withstand fault currents up to 65kA (208/

230, 460 VAC) or 25kA (575 VAC) compliant with UL 1995 and NEC 440.4 (B). Each compressor circuit and the indoor fan shall have dedicated overcurrent protection. Three phase motors shall be protected by Class J time delay fuses. Single phase motors shall be protected by Class CC time delay fuses. All transformers shall also be protected with Class CC time delay fuses. Contactors shall be din rail mounted.

156 RT-PRC028AC-EN

Mechanical Specifications

RT-PRC028AC-EN

Hinged Access Doors

Sheet metal hinges are available on the Filter/Evaporator Access Door and the Compressor/Control

Access Door. This option is available on all downflow models.

Horizontal Side Access with Circuit Breaker

This option is a thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. The circuit breaker will be installed in a water tight enclosure in the unit with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The circuit breaker will provide overcurrent protection, be sized per NEC and UL guidelines, and be agency recognized by UL/CSA.

Horizontal Side Access with Disconnect Switch

Three-pole, molded case, disconnect switch with provisions for through the base electrical connections are available. The disconnect switch will be installed in the unit in a water tight enclosure with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The switch will be UL/CSA agency recognized.

Note: The disconnect switch will be sized per NEC and UL guidelines but will not be used in place of unit overcurrent protection.

Human Interface

The Human Interface shall have a 5 inch color touchscreen display that conforms to FCC Part 15

Class B with an Ingress Protection Rating of IP24. The display text shall be readable by a person with 20/20 vision at a distance of 3 feet and 60° angle at lighting levels ranging from 100 lux - 25,000 lux. Also, the display shall operate at temperatures of -40° C to 70° C. Firmware and unit configurations shall be able to be restored via a USB storage device.

Multi-Speed Indoor Fan System

The multiple-speed (two-speed) indoor fan control option shall automatically switch operation of the indoor fan between high speed and low speed, based on the number of compressors operating.

The indoor fan shall operate at high speed whenever the gas or electric heater is operating.

Multiple-Zone VAV Control

Multiple-zone VAV control shall vary the speed of the indoor fan to maintain the duct static pressure at a setpoint. In cooling mode, the compressors shall be cycled (or economizer modulated) to maintain the supply air temperature (SAT) at the desired setpoint. In heating mode, the indoor fan shall operate at maximum speed whenever the heater operating.

Powered or Unpowered Convenience Outlet

This option is a GFCI, 120V/15amp, 2-plug, convenience outlet, either powered or unpowered.

When the convenience outlet is powered, a service receptacle disconnect will be available. The convenience outlet is powered from the line side of the disconnect or circuit breaker, and therefore will not be affected by the position of the disconnect or circuit breaker. This option can only be ordered when the Through the Base Electrical with either the Disconnect Switch, or Circuit Breaker, option is ordered. This option is available on all downflow models (Gas/Electric only).

Single Zone VAV

SZVAV systems combine Trane application, control and system integration knowledge to exactly match fan speed with cooling and heating loads, regardless of the operating condition.

Note: Zone sensors are required for units configured for Single Zone VAV indoor fan system control in order to enable Single Zone VAV functionality.

Stainless Steel Drain Pan

This option provides excellent corrosion and oxidation resistance. Drain pan shall be constructed of 304 stainless steel.

157

Mechanical Specifications

Stainless Steel Heat Exchanger

Gas heat exchanger shall be of drum and tube design constructed from a minimum 304 Grade stainless steel. The stainless steel heat exchanger shall have a 10-year warranty as standard (Gas/

Electric only).

Supply, Return and Plenum Air Smoke Detector

With this option installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models. See the Installation, Operation, and Maintenance (IOM) manual for the models affected and the minimum allowable airflow required. This option is available on all downflow models. Supply and/or Return Detectors may not be used with the Plenum Smoke Detector.

Through the Base Electrical with Circuit Breaker

This option is a thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. The circuit breaker will be installed in a water tight enclosure in the unit with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The circuit breaker will provide overcurrent protection, be sized per NEC and UL guidelines, and be agency recognized by UL/CSA.

Through the Base Electrical with Disconnect Switch

Three-pole, molded case, disconnect switch with provisions for through the base electrical connections are available. The disconnect switch will be installed in the unit in a water tight enclosure with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The switch will be UL/CSA agency recognized.

Note: The disconnect switch will be sized per NEC and UL guidelines but will not be used in place of unit overcurrent protection.

Through the Base Utilities Access

An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of the unit. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch.

Trane® Air-Fi™ Wireless

Trane® Air-Fi™ wireless communication shall be factory installed and pre-wired. Air-Fi must also be Zigbee® Building Automation certified and the system communicates using standard BACnet™ open protocol.

Two-Inch Pleated Filters

Two-inch MERV 8 and MERV 13 media filters with filter removal tool shall be available on all models.

VAV Operation

The VFD shall receive a 0-10 Vdc signal from the unit control based upon supply static pressure, and shall cause the drive to accelerate or decelerate as required to maintain the supply static pressure setpoint. When subjected to high ambient return conditions the VFD shall reduce its output frequency to maintain operation.

Factory or Field Installed Options

BACnet™ Communications Interface

This option shall be provided to allow the unit to communicate directly with a generic open protocol

BACnet MS/TP Network Building Automation System Controls.

158 RT-PRC028AC-EN

Mechanical Specifications

RT-PRC028AC-EN

Barometric Relief

Designed to be used on downflow units, barometric relief is an unpowered means of relieving excess building pressure.

Clogged Filter/Fan Failure Switch

A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication. These indications will be registered with either a zone sensor with status indication lights or an Integrated Comfort™ System.

Differential Pressure Switches

These options allow for individual fan failure and dirty filter indication. The fan failure switch will disable all unit functions and “flash” the Service LED on the zone sensor. The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation.

Discharge Air Temperature Sensing Kit

This kit provides true discharge air temperature sensing in heating models. This sensor is a status indicator readable through Tracer™ or Tracker™. The kit is functional only with the ReliaTel Options

Module.

Economizer— Standard, Downflow

The assembly includes fully modulating 0–100% motor and dampers, barometric relief, minimum position setting, preset linkage, wiring harness with plug, fixed dry bulb and spring return actuator.

The barometric relief damper shall be standard with the downflow economizer and shall provide a pressure operated damper that shall be gravity closing and shall prohibit entrance of outside air during the equipment “off” cycle. Solid state enthalpy and differential enthalpy control shall be field-installed.

Economizer - Low Leak, Downflow

This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3 cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air). This option allows 100% outdoor air supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired with powered exhaust for additional building pressure relief.This option can be paired with or without Fault Detection & Diagnostics (FDD) to meet current mandatory CA Title 24 requirements.

Available on downflow units only. The economizers come with three control options, dry bulb and reference or comparative enthalpy (optional).

Electric Heaters

Electric heat modules shall be available for installation within the basic unit. Electric heater elements shall be constructed of heavy-duty nickel chromium elements internally delta connected for 240 volt, wye connected for 480 and 600 volt. Staging shall be achieved through ReliaTel. Each heater package shall have automatically reset high limit control operating through heating element contactors. All heaters shall be individually fused from the factory, where required, and shall meet all NEC and CEC requirements when properly installed. Power assemblies shall provide singlepoint connection. Electric heat modules shall be UL listed or CSA certified. If ordering the Through the Base Electrical option with an Electric Heater, the heater must be factory installed.

Indoor Fan Motor Shaft Grounding Ring

Shaft grounding rings are used on all VFD driven motors to provide a conductive discharge path away from the motor bearings to ground. Bearing Protection Ring shall be maintenance free circumferential ring of conductive micro fibers that discharges voltages to ground.

LonTalk

®

Communications Interface

The LonTalk communications interface, when installed in a Voyager unit, allows the unit to communicate as a Tracer™ LCI-V device or directly with generic LonTalk Network Building

Automation System Controls.

159

Mechanical Specifications

Oversized Motors

Oversized motors shall be available for high static applications.

Reference or Comparative Enthalpy

Reference Enthalpy is used to measure and communicate outdoor humidity. The unit receives and uses this information to provide improved comfort cooling while using the economizer.

Comparative Enthalpy measures and communicates humidity for both outdoor and return air conditions, and return air temperature. The unit receives and uses this information to maximize use of economizer cooling, and to provide maximum occupant comfort control. Reference or

Comparative Enthalpy option shall be available when a factory or field installed Downflow

Economizer is ordered. This option is available on all downflow models.

Tool-less Hail Guards

Tool-less, hail protection quality coil guards are available for condenser coil protection.

Trane Communication Interface

This factory or field-installed option shall be provided to interface ReliaTel™ controlled units with the Trane Integrated Comfort™ systems.

Field Installed Options

CO

2

Sensor

The CO

2

sensor shall have the ability to monitor the concentration (parts per million, ppm) of CO

2

(Carbon Dioxide) in the air. As the CO

2

concentration changes, the outside air damper modulates to meet the current ventilation needs of the zone.

Note: Two field installed kits are offered: CO

2

sensor and wiring or CO

2

sensor only. The CO

2 sensor only kit should be ordered with factory installed CO

2

sensor wiring. Factory installed

CO

2

sensor wiring saves set-up time and ensures proper unit connections for the CO

2 sensor.

Economizer — Standard, Horizontal

The horizontal economizer shall contain the same features as the downflow economizer with the exception of barometric relief.

Economizer - Low Leak, Downflow & Horizontal

This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3 cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air).This option allows 100% outdoor air supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired with powered exhaust for additional building pressure relief.

High Static Drive

The high static drive option shall allow the standard motor on the 12½ , 15, 17½, 20 and 25 ton units to operate with improved external static capabilities.

Humidity Sensor

Field installed, wall-mounted or duct-mounted humidity sensor is used to control activation of the hot gas reheat dehumidification option. The humidity sensor can be set for humidity levels between 40% and 60% relative humidity by adjusting the ReliaTel Options Module.

Manual Outside Air Damper

The rain hood and screen shall provide up to 25% outside air.

160 RT-PRC028AC-EN

RT-PRC028AC-EN

Mechanical Specifications

Motorized Outside Air Dampers

Manually set outdoor air dampers shall provide up to 50% outside air. Once set, outdoor air dampers shall open to set position when indoor fan starts. The damper shall close to the full closed position when indoor fan shuts down.

Powered Exhaust

The powered exhaust shall provide exhaust of return air, when using an economizer, to maintain better building pressurization.

Roof Curb—Downflow

The roof curb shall be designed to mate with the downflow unit and provide support and a water tight installation when installed properly. The roof curb design shall allow field-fabricated rectangular supply/return ductwork to be connected directly to the curb. Curb shall be shipped knocked down for field assembly and shall include wood nailer strips.

Remote Potentiometer

The minimum position setting of the economizer shall be adjusted with this accessory.

Ventilation Override Accessory

With the Ventilation Override Accessory installed, the unit can be set to transition up to three different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector or fire control panel.

Wireless Zone Sensor

LCD display that provides heat, cool, auto, or off. Includes two temperature setpoints and a lockable setting with °F or °C indicators.

Zone Sensors

This option shall be provided to interface with ReliaTel and shall be available in either manual, automatic, programmable with night setback, with system malfunction lights or remote sensor options.

Note: Zone sensors are required for units configured for Single Zone VAV indoor fan system control in order to enable Single Zone VAV functionality.

161

Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient environments. Our people and our family of brands—including Club Car®, Ingersoll Rand®, Thermo King® and

Trane®—work together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress and enduring results.

i

ngersollr

a

nd.

c

om

The AHRI Certified mark indicates Ingersoll Rand’s participation in the AHRI Certification program. For verification of individual certified products, go to www.ahridirectory.org.

Ingersoll Rand has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

We are committed to using environmentally conscious print practices.

RT-PRC028AC-EN 17 Mar 2017

Supersedes RT-PRC028AB-EN (02 Mar 2017) ©2017 Ingersoll Rand

advertisement