- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Trane
- THD210G3R0B1KMC
- Specification
Trane THD210G3R0B1KMC Voyager™ 17.5 Tons 230V Three Phase Commercial Packaged Gas/Electric Unit Specification 162 Pages
Trane THD210G3R0B1KMC Voyager™ 17.5 Tons 230V Three Phase Commercial Packaged Gas/Electric Unit Specification
Add to My manuals162 Pages
advertisement
Product Catalog
Packaged Rooftop Air Conditioners
Voyager™ Light Commercial – Cooling, Gas/Electric
12.5 to 25 Tons, 60 Hz
March 2017
RT-PRC028AC-EN
Introduction
Packaged Rooftop Air Conditioners
Through the years, Trane has designed and developed the most complete line of Packaged
Rooftop products available in the market today. Trane was the first to introduce the Micro— microelectronic unit controls—and has continued to improve and revolutionize this design concept.
The ReliaTel™control platform offers the same great features and functionality as the original
Micro, with additional benefits for greater application flexibility.
Voyager™ continues to provide the highest standards in quality and reliability, comfort, ease of service, and the performance of Trane light commercial products.
Trane customers demand products that provide exceptional reliability, meet stringent performance requirements, and are competitively priced. Trane delivers with Voyager.
Voyager features cutting edge technologies: reliable compressors, Trane engineered ReliaTel controls, computer-aided run testing, and Integrated Comfort™ Systems. So, whether you’re the contractor, the engineer, or the owner, you can be certain Voyager products are built to meet your needs.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
Trane and the Trane logo, CompleteCoat, Frostat, Integrated Comfort Systems, ReliaTel, Tracer,
Voyager, are trademarks of Trane in the United States and other countries. All trademarks referenced in this document are the trademarks of their respective owners.
Revision Summary
• Added New 17½ & 25 Tons Standard Efficiency models.
• Updated Features & Benefits, Model Number Description, General Data, Electrical Data,
Dimensional Data, Weight, Mechanical Specifications sections.
© 2017 Ingersoll Rand RT-PRC028AC-EN
Table of Contents
Features and Benefits
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Standard Features and Available Options
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Standard Features
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Variety of Options
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Factory or Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Other Benefits
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Application Considerations
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Selection Procedure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Cooling Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Air Delivery Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Model Number Description
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Model Number Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
General Data
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Performance Data
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Controls
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Economizer Controls
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Zone Sensors
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Communication Interfaces
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Electrical Data
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Jobsite Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Dimensional Data
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Weights
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Mechanical Specifications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Factory or Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
RT-PRC028AC-EN 3
4
Features and Benefits
Note: Packaged Rooftop units cooling, heating capacities, and efficiencies are AHRI certified within scope of AHRI Standard 340-360 (I-P) and ANSIZ21.47 and 10 CFR Part 431 pertaining to Commercial Warm Air Furnaces (gas heating units).
Standard Features and Available Options
Table 1.
Voyager™ Light Commercial control options — standard and optional
BACnet® Communications Interface (BCI)
Discharge Line Thermostat
Humidity Sensor
LonTalk® Communications Interface (LCI)
ReliaTel™ Microprocessor Controls
ReliaTel™ Options Module
Thermostat
Trane® Air-Fi™ Wireless Communication Interface
Trane® Communications Interface (TCI)
Wireless Zone Sensor
Zone Sensors and Remote Zone Sensors
(a)Refer to model number description for option availability
Standard
Features
Factory
Installed
X
X
X
Options (a)
Factory or
Field
Installed
X
Field
Installed
X
X
X
X
X
X
X
Table 2.
Voyager™ Light Commercial features - standard and optional
1-year Limited Parts Warranty
5-year Limited Compressor Warranty
5-year Limited Heat Exchanger Warranty (12½–17½ Tons); 1 Year on 20 and
25 Tons
2” MERV 8 Filters or 2” MERV 13 Filters with Filter Removal Tool
2” throwaway filters
3 Stages of Cooling Capability on 12½–20 Tons, 4 Stages of Cooling Capability on 25 Tons (High Efficiency Units Only)
Anti-Short Cycle Timer
Barometric Relief
Belt Drive Motors
Clogged Filter/Fan Failure Switch
CO
2
Sensor
CO
2
Sensor Wiring (Wiring Only)
Colored and Numbered Wiring
Complete Coat™ Microchannel Condenser Coil
Condensate Overflow Switch
Crankcase Heaters
Dedicated Airflow
Standard
Features
X
X
X
X
X
X
X
X
X
X
Factory
Installed
X
X
X
X
Options (a)
Factory or
Field
Installed
Field
Installed
X
X
X
RT-PRC028AC-EN
Features and Benefits
Table 2.
Voyager™ Light Commercial features - standard and optional
Dehumidification (Hot Gas Reheat)
Digital Display Zone Sensor
Discharge Air Temperature Sensing Kit
Easy Access Low Voltage Terminal Board (LTB)
Economizer - Standard, Downflow
Economizer - Standard, Horizontal
Electric Heaters
Fault Detection & Diagnostics (FDD)
Foil-Faced and Edge Captured Insulation
Frostat™
High and Low Static Drive Kits
High Efficiency Drum and Tube Heat Exchanger
High Efficiency Gas Heat with Hot Surface Ignition
High Efficiency Motors
High Pressure Cutout
High Short Circuit Current Rated (SCCR) Electrical Subsystem
Hinged Access Doors
Human Interface - 5 inch Color Touchscreen
IAQ Sloped Condensate Drain Pan
Indoor Fan Motor Shaft Grounding Ring
Liquid Line Refrigerant Drier
Low Ambient Cooling to 0°F
Low Leak Economizer - Downflow
Low Leak Economizer - Downflow and Horizontal
LP Conversion Kit
Manual Outside Air Dampers
Microchannel Type Condenser Coils
Microchannel Type Evaporator Coils (Standard Efficiency Only)
Modulating Gas Heat Furnace with a 2.5:1 Turndown Ratio
Motorized Outside Air Dampers
Multi-Speed Indoor Fans
Multiple Zone Variable Air Volume (MZVAV)
Operating Charge of R-410A
Oversized Motors
Phase Monitor
Powered Exhaust
Powered or Unpowered Convenience Outlet
Provisions for Through-the-Base Gas Connections
Quick Access Panels
Quick Adjust Idler Arm Pulley
Reference or Comparative Enthalpy
Remote Potentiometer
Roof Curb (Downflow Only)
RT-PRC028AC-EN
Standard
Features
Factory
Installed
X
X
Options (a)
Factory or
Field
Installed
Field
Installed
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
5
Features and Benefits
6
Table 2.
Voyager™ Light Commercial features - standard and optional
Single Point Power
Single Side Service
Single Zone Variable Air Volume (SZ VAV)
Stainless Steel Drain Pan
Stainless Steel Heat Exchanger with 10 Year Warranty
Standardized Components
Supply and/or Return Air Smoke Detector
Thermal Expansion Valve
Through the Base Electrical Access
Through the Base Electrical with Circuit Breaker
Through the Base Electrical with Disconnect Switch
Through the Base Gas Piping
Tool-less Hail Guards
U-shaped Airflow Pattern
Variable Frequency Drive (Multispeed Indoor Fan, VAV, and Single Zone VAV)
Ventilation Override Accessory
(a)Refer to model number description for option availability.
Standard
Features
X
X
X
X
X
X
Factory
Installed
X
X
X
X
X
X
X
X
Options (a)
Factory or
Field
Installed
Field
Installed
X
X
Note: Most Factory Installed Options (FIOPS) available for Downflow Air Discharge units only.
Please verify with ordering system for availability.
Standard Features
Anti-Short Cycle Timer
Provides a 3 minute minimum “ON” time and 3 minute “OFF” time for compressors to enhance compressor reliability by assuring proper oil return.
Colored and Numbered Wiring
Save time and money tracing wires and diagnosing the unit.
Compressors
Voyager contains the best compressor technology available to achieve the highest possible performance. Dual compressors are outstanding for humidity control, light load cooling conditions and system back-up applications. Dual compressors are available on all models and allow for efficient cooling utilizing three stages of compressor operation (high efficiency 12½–20 Tons models only). 25 tons high efficiency units have 4 stages of cooling with a single compressor and tandem set (similar to variable speed).
Controls—ReliaTel™
ReliaTel microprocessor controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure indoor and outdoor temperature and other zone sensors. ReliaTel
RT-PRC028AC-EN
Features and Benefits also provides outputs for building automation systems and expanded diagnostics. For a complete list of ReliaTel offerings, refer to
.
Conversionless Units
The dedicated design units (either downflow or horizontal) require no panel removal or alteration time to convert in the field — a major cost savings during installation. Horizontal units come complete with duct flanges so the contractor doesn’t have to field fabricate them. These duct flanges are a time and cost saver.
Crankcase Heaters
These band or insertion heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or low ambient conditions. These are standard on all Voyager models.
Discharge Line Thermostat
A bi-metal element discharge line thermostats installed as a standard feature on the discharge line of each system. This standard feature provides extra protection to the compressors against high discharge temperatures in case of loss of charge, extremely high ambient and other conditions which could drive the discharge temperature higher.
Efficiencies
Standard or High Efficiency Cooling available.
Easy Access Low Voltage Terminal Board
Foil Faced Insulation
RT-PRC028AC-EN
Voyager’s Low Voltage Terminal Board is external to the electrical control cabinet. It is extremely easy to locate and attach the thermostat wire and test operation of all unit functions. This is another cost and time saving installation feature.
All panels in the evaporator section of the unit have cleanable foil-faced insulation. All edges are either captured or sealed to ensure no insulation fibers get into the airstream.
Fork Pocket Access
Voyager™ has the ability to be forked from 3 sides.
Heat Exchanger—Drum and Tube
The cabinet features a drum and tube heat exchanger (pictured right) that is manufactured using aluminized steel with stainless steel components for maximum durability.
The requirement for cycle testing of heat exchangers is 10,000 cycles by ANSI Z21.47.
This is the standard required by both UL and
AGA for cycle test requirements.
For c ed Com b ust i on Blower
Ne ga t i ve Pressure Ga s V a lve
Hot Surf ac e I g n i tor
7
Features and Benefits
Trane requires the design to be tested to 2½ times this current standard. The drum and tube design has been tested and passed over 150,000 cycles, which is over 15 times the current ANSI cycling requirements. The negative pressure gas valve is used in the standard furnaces. This is one of our unique safety features. Modulating heaters use a pressure switch to ensure that the blower motor is operating before the gas valve is allowed to open.
The forced combustion blower supplies pre-mixed fuel through a single stainless steel burner screen into a sealed drum where ignition takes place. It is more reliable to operate and maintain than a multiple burner system. Modulating furnaces contain a metal fiber material to ensure proper flame distribution at low fire. The hot surface ignitor is a gas ignition device which doubles as a safety device utilizing a continuous test to prove the flame. The design is cycle tested at the factory for quality and reliability. Our gas/electric rooftops exceed all California seasonal efficiency requirements and perform even better than the California NO x
emission requirements.
Low Ambient Cooling
All Voyager microprocessor units have cooling capabilities down to 0°F as standard.
Low Voltage Connections
The wiring of the low voltage connections to the unit and the zone sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to wire.
8
Microchannel Coils
Air Inlet
Slit Fins and Braze Contact for Improved Heat Transfer and Strength
Microchannels for Refrigerant
Air Outlet
Microchannel coils are all-aluminum coils with fullybrazed construction. This design reduces risk of leaks and provides increased coil rigidity — making them more rugged on the jobsite. Their flat streamlined tubes with small ports and metallurgical tube-to-fin bond allow for exceptional heat transfer.
Microchannel all-aluminum construction provides several additional benefits:
• Light weight (simplifies coil handling)
• Easy to recycle
• Minimize galvanic corrosion
Motors
All indoor fan motors are belt drive as standard.
Pressure Cutouts
Low and high pressure cutouts are standard on all Voyager models.
Phase Monitor
Voyager features a three-phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating input voltage range of 190–600 Vac, and LED indicators for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition.
RT-PRC028AC-EN
Features and Benefits
Quick-Access Panels
Remove three or more screws for access to the standardized internal components and wiring.
Quick-Adjust Slider Plate
With the Quick-Adjust Slider Plate (pictured right), the belt and sheaves can be quickly adjusted without moving the mounted fan motor. The result is a major savings in time and money.
Single Point Power
A single electrical connection powers the unit.
Single Side Service
Single side service is standard on all units.
Sloped Drain Pans
Every Voyager unit has a non-corrosive, sloped drain pan made of pre-painted steel and standard on all units.
Standardized Components
Components are placed in the same location on all Voyager units. Familiarize yourself with one
Voyager and you are familiar with every Voyager. Due to standardized components throughout the
Voyager line, contractors/owners can stock fewer parts.
U-Shaped Airflow Pattern
The U-shaped airflow allows for improved static capabilities.
Variable Frequency Drives - VFD (Multispeed Indoor Fan, VAV, and SZ VAV
Only)
Variable Frequency Drives are factory installed and tested to provide supply fan motor speed modulation. VFDs on the supply fan, as compared to inlet guide vanes or discharge dampers, are quieter, more efficient, and are eligible for utility rebates. All VFDs are designed to allow bypass if required. Bypass control will simply provide full nominal airflow in the event of drive failure.
Bypass mode is indicated in the unit wiring manual. Modulating gas heat models with SZVAV allow tighter space temperature control with less temperature swing.
Variety of Options 1
Factory Installed Options
Trane® Air-Fi™ Wireless
Trane® Air-Fi™ wireless communication is a reliable, flexible solution that frees you from the hassles associated with wired components for your building controls system. With Air-Fi wireless, you get easy problem solving, efficient performance, and cost savings over the life of the equipment.
CO
2
Sensor Wiring
This is the unit wiring for field installed C0
2
sensors. Factory-installed C0
2
sensor wiring saves time and ensures proper unit connections for the field installed C0
2
sensor kits.
1 Refer to
“Model Number Description,” p. 23 for option availability.
RT-PRC028AC-EN 9
Features and Benefits
10
Complete Coat™ Condenser Coil
The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number of different types of heat exchangers. The coating is selected to provide excellent resistance and durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salt air, and corrosive environments. This coating is available for microchannel coils only.
Circuit Breaker (Required with Through-the-Base Electrical)
This option is a factory installed thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. Available on all models.
Condensate Overflow Switch
A condensate overflow switch is available to shut the unit down in the event that the condensate drain line becomes clogged. This option protects the unit from water overflowing from the drain pan and entering the base of the units.
Dehumidification (Hot Gas Reheat)
This option allows for increased outdoor air ventilation. It reduces humidity levels while increasing comfort level in the air space. Cooling can operate without a demand for dehumidification. The hot gas reheat coil is designed to deliver maximum reheat temperature.
Disconnect Switch (Required with Through-the-Base Electrical)
Factory installed 3-pole, molded case, disconnect switch with provisions for through the base electrical connections are available.
Available on all models.
Codes require a method of assured unit shutdown for servicing. Field-installed disconnects sometimes interfere with service access. Factory installation of unit disconnects reduces costs, assures proper mounting and provides the opportunity to upgrade to unit circuit breaker protection.
Fault Detection & Diagnostics (FDD)
This offering meets the mandatory requirement of CA Title 24 of fully configurable diagnostics allowing fault history and reading fault codes at the unit.This option provides detection of the following faults: Air temperature sensor failure/fault and notification of acceptable economizer mode.The FDD system shall be certified by the Energy Commission as meeting the requirements.
High Efficiency Filtration
Voyager units offer a variety of high efficiency filtration options. MERV 8 and MERV 13 filters provide additional filtration beyond the capabilities of typical 2” throwaway filters. Also, when
MERV 8 or MERV 13 filters are ordered, units come equipped with a filter removal tool.
High Efficiency Motors
High efficiency motors are available with efficiency ratings from 86.5 up to 91.0. It is not available for all models.
High Short Circuit Current Rating (SCCR)
Voyager rooftop units now have an optional high short circuit current rated electrical subsystem for units with an MOP above 60A. This option is a perfect fit for applications that need protection against high potential fault currents. This option also includes individual over current protection for each compressor and the indoor fan, as well as a dedicated over current protection to the
RT-PRC028AC-EN
Features and Benefits condenser fan motor(s). When the high SCCR is ordered, the control box will have components separated into two sections - high and low voltage components.
Hinged Access Doors
These doors permit easy access to the filter, fan/ heat, and compressor/control sections. They reduce the potential roof damage from screws or sharp access door corners.
RT-PRC028AC-EN
Human Interface
The 5 inch Color Touchscreen Human Interface provides an intuitive user interface to the rooftop unit that speeds up unit commissioning, shortens unit troubleshooting times, and enhances preventative maintenance measures. The human interface includes several features such as:
• Data trending capabilities by means of time series graphs
• Historical alarm messages
• Real-time sensor measurements
• On board system setpoints
• USB port that enables the downloading of component runtime information as well as trended historical sensor data
• Customizable reports
Modulating Gas Heat with a 2.5:1 Turndown Ratio
Upon receiving a call for heat, modulating gas heat units with a 2.5:1 turndown ratio light their burner at full fire (100%). After the burner is lit, the unit controls will monitor the discharge air temperature and modulate the input rate down to match the load.
Note: Modulating gas heat units are equipped with a stainless steel heat exchanger as standard.
Multi-Speed Indoor Fan System
Multi-speed indoor fan system is designed for use in applications for meeting the minimum requirement of CA Title 24. This system incorporates a multi-speed fan control to change the speed of the fan to 67% of full airflow based off compressor stages.
Multiple-Zone VAV Control
A multiple-zone VAV (MZVAV) system consists of a packaged rooftop unit that serves several individually controlled zones. Each zone is equipped with a VAV terminal unit that varies the quantity of air delivered to maintain the desired temperature in that zone. The rooftop unit controller varies the speed of the indoor fan to maintain the static pressure in the supply ductwork at a setpoint, ensuring that all zones receive the necessary quantity of air. In addition, cooling capacity is cycled to maintain the supply air temperature at the desired setpoint.
For decades, Trane has been an industry leader in rooftop VAV systems. Now, multiple-zone VAV control is available in Trane’s light commercial rooftop platform (3-25 tons).
11
Features and Benefits
Novar Unit Controls
Novar 3051 and 2024 are available for Voyager Cooling and Gas/Electric models.
Powered or Unpowered Convenience Outlet
This option is a GFCI, 120V/15amp, 2-plug, convenience outlet, either powered or unpowered. This option can only be ordered when Through the Base Electrical with either the Disconnect Switch or
Circuit Breaker option is ordered. This option is available on all models.
Single Zone VAV - One Zone Variable Air Volume Mode
Note: Single Zone VAV is designed to be used with a zone sensor. If a unit is configured for Single
Zone VAV operation but is connected to a thermostat, the control will revert to multi-speed
(2-Speed) indoor fan control. (See "Multi-Speed Indoor Fan System" above.)
Single zone VAV is designed for use in single zone applications like gymnasiums, auditoriums, manufacturing facilities, retail box stores, and any large open spaces, where there is a lot of diversity in the load profile. Single Zone VAV (SZ VAV) is an ideal replacement to "yesterday's" constant volume (CV) systems, by reducing operating costs while improving occupant comfort.
SZ VAV systems combine Trane application, control and system integration knowledge to exactly match fan speed with cooling and heating loads, regardless of the operating condition. Trane algorithms meet/exceed ASHRAE 90.1- 2010, SZ VAV energy-saving recommendations, and those of CA Title 24. The result is an optimized balance between zone temperature control and system energy savings. Depending on your specific application, energy savings can be as much as 20%.
Note: Building system modeling in energy simulation software like TRACE is recommended to evaluate performance improvements for your application.
SZ VAV is fully integrated into the ReliaTel Control system and is available today. It provides the simplest and fastest commissioning in the industry through proven factory-installed, wired, and tested system controllers. All control modules, logic and sensors are factory installed, and tested to assure the highest quality and most reliable system available. This means no special programming of algorithms, or hunting at the jobsite for sensors, boards, etc. that need to be installed in the field. Single zone VAV is a quick and simple solution for many applications and is available from your most trusted rooftop VAV system solution provider- Trane.
Stainless Steel Drain Pan
For excellent corrosion and oxidation resistance, the optional stainless steel drain pan provides a cleanable surface that complement other IAQ solutions such as high efficiency filtration (MERV 8 or 13), demand control ventilation (CO
2
), and hot gas reheat.
Stainless Steel Heat Exchanger
The optional stainless steel heat exchanger is constructed of 304 stainless steel. It is resistant to corrosion and oxidation and easy to clean. The high strength to weight ratio allows for high ventilation rates with gas units and comes standard with a modulating gas heat option. With this option, a 10-year stainless steel heat exchanger warranty is standard.
Supply, Return, and Plenum Air Smoke Detector
With this option (pictured right) installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models.
Supply and/or Return Smoke Detectors may not be used with the Plenum Smoke Detector.
12 RT-PRC028AC-EN
Features and Benefits
Through-the-Base Electrical Utility Access
An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of the unit. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch.
Factory provided through the base openings simplify wiring and piping. Because these utility openings frequently minimize the number of roof penetrations, the integrity of roofing materials is enhanced.
Through-the-Base Gas Piping (Gas/Electric Only)
This option (pictured right) shall have all piping necessary including, black steel, manual gas shut-off valve, elbows, and union. This assembly will require minor field labor to install.
Factory or Field Installed Options 1
BACnet™ Communications Interface
The BACnet communications interface allows the unit to communicate directly with a generic open protocol BACnet MS/TP Network Building Automation System Controls.
Barometric Relief
Designed to be used on downflow units, barometric relief is an unpowered means of relieving excess building pressure.
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication. These sensors allow a zone sensor service light or Integrated Comfort
System to indicate a dirty filter or a fan that’s not working. The field installation charges for these valuable feedback devices often eliminate them from consideration. Factory installation can make such features a good investment.
Discharge Air Temperature Sensing Kit
Provides true discharge air temperature sensing in heating models. The kit is functional only with the ReliaTel Options Module.
Economizer - Standard, Downflow
Economizers are equipped with either dry bulb, reference, or comparative enthalpy sensing. These economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly installed, they offer a valuable energy savings. Factory-installed economizers save time and ensure proper installation.
Note: Factory-installed economizers require some field set-up.
Economizer - Low Leak, Downflow
This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3 cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air). This option allows 100% outdoor air supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired with powered exhaust for additional building pressure relief. This option can be paired with or without Fault Detection & Diagnostics (FDD) to meet current mandatory CA Title 24 requirements.
1 Refer to
“Model Number Description,” p. 23 for option availability.
RT-PRC028AC-EN 13
Features and Benefits
Available on downflow units only. The economizers come with three control options, dry bulb and reference or comparative enthalpy (optional).
Electric Heaters
Electric heat modules are available within the basic unit. If ordering the Through the Base Electrical option with an Electrical Heater, the heater must be factory installed.
Frostat™
A capillary bulb embedded in the face of the evaporator coil or a thermostat on the suction line monitors coil temperature to prevent evaporator icing and protect the compressor. Recommended for applications with low leaving air temperatures, low airflow and/or high latent load applications.
Note: Frostat is standard on all Single-Zone VAV, Multiple-Zone VAV, and high efficiency units.
Indoor Fan Motor Shaft Grounding Ring
Shaft grounding rings are used on all VFD driven motors to provide a conductive discharge path away from the motor bearings to ground. Bearing Protection Rings shall be maintenance free circumferential rings of conductive micro fibers that discharge voltages to ground.
LonTalk ® Communications Interface
The LonTalk communications interface allows the unit to communicate as a Tracer™LCI-V device or directly with generic LonTalk Network Building Automation System Controls.
Oversized Motors
Factory or field installed oversized motors are available for high static applications.
Reference or Comparative Enthalpy
Measures and communicates humidity while maximizing comfort control.
ReliaTel Options Module (RTOM)
The RTOM monitors the supply fan proving, clogged filter, supply air temperature, exhaust fan setpoint, dehumidification setpoint, supply air tempering, Frostat™ and smoke detector.
Note: The RTOM is standard on high efficiency units.
Tool-less Hail Guards
Tool-less, hail protection quality coil guards (pictured right) shall be either factory or field-installed for condenser coil protection. This option protects the condenser coil from vandalism and/or hail damage.
Trane Communication Interface (TCI)
Available factory or field installed. This module when applied with the
ReliaTel™ easily interfaces with Trane’s Integrated Comfort™ System.
Field Installed Options
1
CO
2
Sensor - Demand Control Ventilation (DCV)
Demand-controlled ventilation (DCV) is a control strategy that responds to the actual demand
(need) for ventilation by regulating the rate at which the HVAC system brings outdoor air into the building. A CO
2
sensor measures the concentration (parts per million, ppm) of CO
2
(Carbon
Dioxide) in the air. As the CO
2
concentration changes, the outside air damper modulates to meet the current ventilation needs of the zone. The CO
2
sensor kit is available as a field installed
1 Refer to
“Model Number Description,” p. 23 for option availability.
14 RT-PRC028AC-EN
Features and Benefits
RT-PRC028AC-EN accessory. Two field installed kits are offered; C0
2
sensor and wiring or C0
2
sensor only. The C0
2 sensor only kit should be ordered with factory installed C0
2
sensor wiring. Factory installed C0
2 sensor wiring saves set-up time and ensures proper unit connections for the C0
2
sensor.
Dampers
0–25 percent manual or 0–50 percent motorized outside air dampers are available.
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors.
Economizer - Standard, Horizontal
Economizers are equipped with either dry bulb or reference or comparative enthalpy sensing.
These economizers provide free cooling as the outdoor temperature and/or humidity decreases.
Correctly installed, they offer a valuable energy savings.
Economizer - Low Leak, Downflow & Horizontal
This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3 cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air). This option allows 100% outdoor air supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired with powered exhaust for additional building pressure relief.
Humidity Sensor/Humidistat
Used in conjunction with our Dehumidification (Hot Gas Reheat) units to provide outstanding humidity control and comfort. Humidity sensors can be wall or duct mounted and set for levels between 40% and 60%.
LP Conversion Kit
Provided for field conversion of gas/electric units from natural gas to propane.
Powered Exhaust
This option is available on downflow units and provides exhaust of the return air, when using a downflow economizer, to maintain proper building pressurization. Great for relieving most building overpressurization problems.
Remote Potentiometer
When properly installed in the economizer control circuitry, this accessory provides a remote variable resistance to enable the operator to adjust the minimum damper position.
Roof Curbs
Available for downflow units. Only two roof curbs for the entire Voyager line simplifies curb selection.
Static Drive Accessories
Available on many models, this high and low static drive accessories extend the capability of the standard motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory.
Ventilation Override Accessory
With the Ventilation Override Accessory installed, the unit can be set to transition to up to 3 different pre-programmed sequences for Smoke Purge, Pressurization and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector or fire control panel. The ventilation override kit is available as a field installed accessory.
15
Features and Benefits
Wireless Zone Sensor
LCD display that provides heat, cool, auto, or off. Includes two temperature setpoints and a lockable setting with °F or °C indicators.
Zone Sensors/Thermostats
Available in programmable, automatic and manual styles.
Note: Zone sensors required for units configured for Single Zone VAV indoor fan system control to enable Single Zone VAV functionality.
Other Benefits
Cabinet Integrity
For added water integrity, Voyager has a raised 1-1/8” lip around the supply and return of the downflow units to prevent water from blowing into the ductwork.
Easy to Install, Service and Maintain
Because today’s owners are very cost-conscious when it comes to service and maintenance,
Voyager was designed with direct input from service contractors. This valuable information helped to design a product that would get the serviceman off the job quicker and save the owner money.
Voyager does this by offering outstanding standard features enhanced by a variety of factory and field installed options, multiple control options, rigorously tested proven designs and superior product and technical support.
Outstanding Airflow Distribution
Airflow is outstanding. The Voyager can replace an older machine with old ductwork and, in many cases, improve the comfort through better air distribution.
ReliaTel™ Controls Benefits
ReliaTel controls provide unit control for heating, cooling and ventilating by utilizing input from sensors that measure outdoor and indoor temperature.
Quality and Reliability are enhanced through ReliaTel control and logic:
– Prevents the unit from short cycling, considerably improving compressor life.
– Ensures the compressor will run for a specific amount of time which allows oil to return for better lubrication, enhancing the reliability of the compressor.
Voyager with ReliaTel reduces the number of components required to operate the unit, thereby reducing possibilities for component failure.
ReliaTel Makes Installing and Servicing Easy
ReliaTel eliminates the need for field installed anti-shortcycle timer and time delay relays.
ReliaTel controls provide these functions as an integral part of the unit. The contractor no longer has to purchase these controls as options and pay to install them. The wiring of the low voltage connections to the unit and the zone sensors is as easy as 1-1, 2-2, and 3-3. This simplified system makes wiring easier for the installer.
16 RT-PRC028AC-EN
RT-PRC028AC-EN
Features and Benefits
ReliaTel Makes Testing Easy
ReliaTel requires no special tools to run Voyager unit through its paces. Simply place a jumper between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk through its operational steps automatically.
The unit automatically returns control to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit.
As long as the unit has power and the “system on” LED is lit, ReliaTel is operational. The light indicates that the controls are functioning properly.
ReliaTel features expanded diagnostic capabilities when utilized with Trane Integrated Comfort™
Systems.
Some zone sensor options have central control panel lights which indicate the mode the unit is in and possible diagnostic information (dirty filters for example).
Other ReliaTel Benefits
The ReliaTel built-in anti-shortcycle timer, time delay relay and minimum “on” time control functions are factory tested to assure proper operation. ReliaTel softens electrical “spikes” by staging on fans, compressors and heaters. Intelligent Fallback is a benefit to the building occupant.
If a component goes astray, the unit will continue to operate at predetermined temperature setpoint.
Intelligent Anticipation is a standard ReliaTel feature. It functions continuously as ReliaTel and zone sensor(s) work together in harmony to provide much tighter comfort control than conventional electro-mechanical thermostats.
The same ReliaTel Board fits all Packaged Gas/Electric, Cooling, and Heat Pump models. This provides standardization of parts for contractors. Less money is tied up in inventory with ReliaTel.
Rigorous Testing
All of Voyager’s designs were rigorously rain tested at the factory to ensure water integrity. Voyager units incorporate either a one piece top or the Trane-Tite-Top (T3). Each part of the top (either two or three pieces) overlaps in such a way that water cannot leak into the unit. These overlapped edges are gasketed and sealed to ensure superior water integrity.
Actual shipping tests were performed to determine packaging requirements. Units were test shipped around the country to determine the best packaging. Factory shake and drop tests were used as part of the package design process to help assure that the unit arrives at the job site in top condition.
Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress. For the microchannel coils, the supplier will perform the leak check at 450 psig. The completely assembled refrigerant system is leak tested at a minimum of
225 psig with a refrigerant and nitrogen mixture.
All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately. Every unit receives a 100% unit run test before leaving the production line to make sure it lives up to rigorous Trane requirements.
Unmatched Support
Trane Sales Representatives are a Support Group that can assist you with:
• Product
• Application
• Service
• Training
• Special Applications
• Specifications
• Computer Programs and much more
17
Features and Benefits
VariTrac® – Changeover-Bypass System
A changeover-bypass system consists of a packaged rooftop unit that serves several individually controlled zones. Each zone is equipped with a damper that varies the quantity of air delivered to maintain the desired temperature in that zone. However, unlike a conventional multiple-zone VAV system, the fan inside the rooftop unit operates at a constant speed. Any unneeded air is diverted to the return air stream through a bypass damper.
The term “changeover” refers to how this system handles the cooling and heating requirements of the building. The central rooftop unit can provide either cooled or heated air, and it makes this decision by periodically “polling” the zones.
Note: VariTrac is for Voyager units with constant-speed indoor fan control. It is not recommended for use with Multiple-Speed Indoor Fan Control, Single-Zone VAV Control, or Multiple-Zone
VAV Control.
18 RT-PRC028AC-EN
Application Considerations
Application of this product should be within the cataloged airflow and cooling considerations.
Air-Fi™ Wireless
Please refer to Air-Fi Network Design Installation, Operation, and Maintenance manual BAS-
SVX55*-EN for additional details on applications with factory installed wireless.
Barometric Relief
This product line offers an optional barometric relief damper for use in conjunction with economizer option. This accessory consists of gravity dampers which open with increased pressure. As the building air pressure increases, the pressure in the unit return air section also increases, opening the dampers and relieving the conditioned space.
Note: The effectiveness of barometric relief damper during economizing operation is limited, depending on the pressure drop of the return-air path. For some applications, powered exhaust may be better suited for preventing over-pressurization when economizing.
Clearance Requirements
The recommended clearances identified with unit dimensions should be maintained to ensure adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with local Trane sales personnel.
Complete Coat™ Microchannel Condenser Coil
The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number of different types of heat exchangers. The coating is selected to provide excellent resistance and durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salt air, and corrosive environments. This coating shall be available on microchannel condenser coils.
Condensate Trap
The evaporator is a draw-through configuration. A trap must be field provided prior to start-up on the cooling cycle.
Dual Compressors — 3 Stages of Cooling (12½–20 Tons)
Using the ReliaTel™ microprocessor controls, the Voyager™ high efficiency line can provide three stages of cooling, allowing for a more efficient and comfortable cooling operation.
Important: All high efficiency products will have intertwined evaporator coils as standard. No face split coils are allowed with 3 or 4 stages of cooling.
Note: Standard efficiency models do not have 3 stages of cooling operation.
4 Stages of Cooling (25 Tons)
25 tons high efficiency units have 4 stages of cooling with a single compressor and tandem set
(similar to variable speed).
Heating Operation
The heat exchanger is manufactured with aluminized steel. To prevent condensation within the heat exchanger, do not exceed 50 percent outside air or a minimum mixed air temperature of 40°F.
Optional Stainless Steel Heat Exchanger
The optional stainless steel heat exchanger is manufactured with 304 stainless steel. To prevent corrosion and prolong heat exchanger reliability, the minimum mixed air temperature allowed across the heat exchanger is 20°F. The stainless steel heat exchanger option is an excellent option that compliments the dehumidification package and is used in conjunction with the modulating heat option. Whenever high outside air or outside applications exist, these options should be utilized.
RT-PRC028AC-EN 19
Application Considerations
Low Ambient Cooling
The Voyager line features, with ReliaTel™ microprocessor controls, low ambient cooling down to
0°F. The following options need to be included/considered when low ambient applications are required: continuous fan operation, crankcase heaters (standard), thermal expansion valves, frostat. Contact your local Trane Representative for more assistance with low ambient cooling applications.
Unit Pitch
These units have sloped condensate drain pans. Units must be installed level. Any unit slope must be toward access side of the unit.
Low Airflow
Unit applications designed for airflow below 320 cfm/ton are available on cooling only units and gas heat units equipped with modulating gas heat. Units must be high efficiency units with dehumidification (hot gas reheat) or TXV with Frostat and Crankcase heaters. Electric heat is restricted below 320 cfm/ton. Standard efficiency units are restricted below 250 cfm/ton. Multispeed or single zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
VariTrac®
VariTrac is for Voyager units with constant-speed indoor fan control. It is not recommended for use with Multiple-Speed Indoor Fan Control, Single-Zone VAV Control, or Multiple-Zone VAV Control.
20 RT-PRC028AC-EN
Selection Procedure
Cooling Capacity
Note: Cooling Capacity Procedure is the same for cooling (T*) and gas/electric (Y*).
Step 1.
Calculate the building’s total and sensible cooling loads at design conditions. Use the following calculation methods or any other standard accepted method. Factors used in unit selection:
Total Cooling Load: 180 MBh
Sensible Cooling Load: 126 MBh
Airflow: 6000 cfm
Electrical Characteristics: 460/60/3
Summer Design Conditions: Entering Evaporator Coil: 80 DB, 67 WB Outdoor Ambient: 95 DB
External Static Pressure: 0.39 in. wg
Rooftop—downflow configuration
Accessories
• Roof curb
• Economizer
• Electric Heat
Step 2.
As a starting point, a rough determination must be made of the size of the unit. The final selection will be made after examining the performance at the given conditions. Divide the total cooling load by nominal Btu/h per ton (12 MBh per ton); then round up to the nearest unit size.
180 MBh / 12 MBh = 15.0 tons
Step 3.
shows that a TSD180F4 has a gross cooling capacity of 186.1 MBh and 139.1 MBh sensible capacity at 6000 cfm and 95 DB outdoor ambient with 80 DB, 67 WB air entering the evaporator.
To Find Capacity at Intermediate Conditions Not in the Table.
When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity.
Note: Extrapolation outside of the table conditions is not recommended.
Step 4.
In order to select the correct unit which meets the building’s requirements, the fan motor heat must be deducted from the gross cooling capacity. The amount of heat that the fan motor generates is dependent on the effort by the motor—cfm and static pressure. To determine the total unit static pressure you add the external static pressure to the additional static related by the added features:
External Static Duct System
Standard Filter 2 in. from
0.39 wg
0.06 wg
Economizer from
(100% Return Air)
Electric Heater Size 36 kW from
0.04 wg
0.07 wg
(Reference
for determination of heater size.) No additional static add for gas/heat exchanger.
Total Static Pressure 0.56 wg
Note: The Evaporator Fan Performance
has already accounted for the pressure drop for standard filters and wet coils (see note below
).
Therefore, the actual total static pressure is 0.56 - 0.06 (from
= 0.50 wg).
RT-PRC028AC-EN 21
Selection Procedure
With 6000 cfm and 0.50 wg.
Table 49, p. 83 shows 1.95 bhp for this unit. Note below the table gives a formula to calculate Fan
Motor Heat,
3.15 x bhp = MBh.
3.15 x 1.95 = 6.14 MBh.
Now subtract the fan motor heat from the gross cooling capacity of the unit:
Net Total Cooling Capacity = 186.1 MBh - 6.14 = 179.96 MBh.
Net Sensible Cooling Capacity = 139.1 MBh - 6.14 = 132.96 MBh.
Step 5.
If the performance will not meet the required load of the building—total or sensible cooling load, try a selection at the next higher size unit.
Heating Capacity
Note: Heating capacity procedures DIFFER for cooling (T*) and gas/electric (Y*) units.
Step 1.
Calculate the building heating load.
Step 2.
Size the system heating capacity to match the calculated building heating load. The following are building heating requirements:
T* cooling units:
460 volt/3 phase Power Supply
Total heating load of 115.0 MBh
6000 cfm
will deliver 122.94 MBh at 480 volts. In order to determine capacity at 460 volts, the heater voltage
correction factor from Table 92, p. 123
must be used. Therefore, 122.94 MBh x .94 (voltage correction factor) = 115.6 MBh.
Y* gas/electric: Fuel natural gas total heating load of 195 MBh. Table Table 90, p. 122
shows
250 MBh and 350 MBh input models. The output capacities of these furnaces are 203 MBh and
284 MBh respectively. The low heat model with 203 MBh output best matches the building requirements.
Air Delivery Selection
Note: Air Delivery procedures is the same for cooling (T*) and gas/electric (Y*) units.
External static pressure drop through the air distribution system has been calculated to be
0.50 inches of water. From Table 89, p. 120
static pressure drop through the economizer is 0.04 and the 36 kW heater is 0.07 inches of water (0.39 + 0.04 + 0.07). Enter
for a TSD180F4 at 6000 cfm and 0.50 static pressure. The standard motor at 533 rpm will give the desired airflow at a rated bhp of 1.92.
22 RT-PRC028AC-EN
Y
1
S
2
D
3
1
4
5
5
Digit 1 — Unit Type
T = Packaged Cooling, Electric Heat
Y = Packaged Cooling, Gas Heat
Digit 2 — Efficiency
S = Standard Efficiency
H = High Efficiency
Digit 3 — Airflow Configuration
D = Downflow
H = Horizontal
Digit 4, 5, 6 — Nominal Gross
Cooling Capacity (MBh)
150 = 12½ Tons
180 = 15 Tons
210 = 17½ Tons, 60Hz DOE 2018
211 = 17½ Tons, 60Hz
240 = 20 Tons
300 = 25 Tons, 60Hz DOE 2018
301 = 25 Tons, 60Hz
Digit 7 — Major Design
Sequence
G = ASHRAE 90.1-2013 (Fan/
Compressor Staging)
or
Microchannel Type Evaporator &
Condenser Coils
Digit 8 — Voltage Selection
3 = 208-230/60/3
4 = 460/60/3
W = 575/60/3
K = 380/60/3
Digit 9 — Unit Controls
R = Reliatel
Digit 10 — Heating Capacity
Note: (Applicable to Digit 1 T models only)
0 = No Heat
G = 18 kW Electric Heat
K = 27 kW Electric Heat
N = 36 kW Electric Heat
P = 54 kW Electric Heat
R = 72 kW Electric Heat
Note: (Applicable to Digit 1 Y models only)
H = Gas Heat - High
L = Gas Heat - Low
V = Gas Heat - SS Ht Ex - Modulating
X = Gas Heat - SS Ht Ex - Low
Z = Gas Heat - SS Ht Ex - High
Digit 11 — Minor Design
Sequence
RT-PRC028AC-EN
0
6
G
7
3
8
R
9
Digit 12, 13 — Service Sequence
00 = None
01 = 18mm Microchannel Condenser
Coil
Note: ‘01’ only available on select models.
Digit 14 — Fresh Air Selection
0 = No Fresh Air
D = Econ Dry Bulb w/ Barometric
Relief
F = Econ Reference Enthaply w/
Barometric Relief
H = Econ Comparative Enthaply w/
Barometric Relief
K = Low Leak Econ w/ Barometric
Relief
M = Low Leak Econ Reference
Enthalpy w/ Barometric Relief
P = Low Leak Econ Comparative
Enthalpy w/ Barometric Relief
Digit 15 — Supply Fan/Drive
Type/Motor
0 = Standard Motor
1 =
3 =
6 = Single Zone Variable Air Volume
Standard Motor
7 = Multi-Speed Standard Motor
8 = Single Zone Variable Air Volume
Oversized Motor
9 = Multi-Speed Oversized Motor
A = Single Zone Variable Air Volume
Standard Motor w/ Shaft
Grounding Ring
B = Multi-Speed Standard Motor w/
Shaft Grounding Ring
C = Single Zone Variable Air Volume
Oversized Motor w/ Shaft
Grounding Ring
D = Multi-Speed Oversized Motor w/
Shaft Grounding Ring
E = VAV Supply Air Temperature
Control - Standard Motor
F = VAV Supply Air Temperature
Control - Oversized Motor
G = VAV Supply Air Temperature
Control - Standard Motor w/ Shaft
Grounding Ring
H = VAV Supply Air Temperature
Control - Oversized Motor w/
Shaft Grounding Ring
Digit 16 — Hinged Service
Access / Filters
0 = Standard Panels/Standard
Filters
A = Hinged Access/Standard Filters
B =
Standard Panels/MERV 8 Filters 6
C =
Hinged Access/MERV 8 Filters 6
D = Standard Panels/MERV 13 Filters
E = Hinged Access/MERV 13 Filters
Z B 0
10 11 12
Digit 17 — Condenser Coil
Protection
0
13
0 = Standard Coil
1 = Standard Coil With Hail Guard
4 = CompleteCoat™Condenser Coil
5 = CompleteCoat™Condenser Coil with Hail Guard
Digit 18 — Through The Base
Provisions
Note: Applicable to Digit 1, T or Y models.
0 = No Through The Base Provisions
A = Through The Base Electric
Note: Applicable to Digit1, Y models only.
B = Through The Base Gas
C = Through The Base Electric/Gas
D = Through The Base Access
Digit 19 — Disconnect Switch/
0 = No Disconnect/circuit break
1 = Unit Mounted Non-Fused
Disconnect Switch
2 = Unit Mounted Circuit Breaker
Digit 20 — Convenience Outlet
Option
0 = Without Convenience Outlet
A = Unpowered Convenience Outlet
B =
Digit 21 — Communications
Options
0 = Without Communications Options
1 = Trane Communications Interface
,
2 = Lontalk Communications
6 = Building Automation Control
Network Communications
Interface
7 =
Air-Fi™ Wireless Communications 24
Digit 22 — Refrigeration System
Option
0 = Standard refrigeration system
B = Dehumidification (Hot Gas
Digit 23 — Refrigeration Controls
0 = Without Refrigeration Controls
1 =
,
Digit 24 — Smoke Detector
0 = Without Smoke Detector
A = Return Air Smoke Detector
B = Supply Air Smoke Detector
C = Return/Supply Air Smoke
Detector
D = Plenum Smoke Detector
Digit 25 — System Monitoring
Controls
0 = No Monitoring Controls
23
Model Number Description
1 = Clogged Filter Switch
2 = Fan Failure Switch
3 =
4 = Clogged Filter Switch and Fan
5 = Clogged Filter Switch and
6 = Fan Failure Switch and Discharge
7 = Clogged Filter Switch, Fan Failure
Switch and Discharge Air
A = Condensate Drain Pan Overflow
Switch
B = Clogged Filter Switch and
Condensate Drain Pan Overflow
C = Fan Failure Switch and
Condensate Drain Pan Overflow
D = Discharge Air Sensing and
Condensate Drain Pan Overflow
E = Clogged Filter Switch, Fan Failure
Switch and Condensate Drain Pan
Overflow Switch
F = Clogged Filter Switch, Discharge
Air Sensing Tube and Condensate
Drain Pan Overflow Switch
G = Fan Failure Switch, Discharge Air
Sensing Tube and Condensate
Drain Pan Overflow Switch
H = Clogged Filter Switch, Fan Failure
Switch, Discharge Air Sensing and Condensate Drain Pan
Overflow Switch
Digit 26 - System Monitoring
Controls
0 = No Monitoring Controls
A = Demand Control Ventilation
(CO
2
)
B = FDD (Fault Detection and
Diagnostics)
C = FDD (Fault Detection Diagnostics)
& Demand Control Ventilation
(CO
2
)
Digit 27 - Unit Hardware
Enhancements
0 = No Enhancements
1 = Stainless Steel Drain Pan
Digit 28 - Short Circuit Current
Rating
0 = Standard SCCR
A = 65kA SCCR Option
,
Digit 31 - Advanced Unit
Controls
0 = Standard Unit Controls
1 =
Note: Most Factory Installed Options available for Downflow Air
Discharge units only. Please verify with ordering system for availability.
Model Number Notes
1.
Some field set up required.
2. Requires ReliaTel Options Module.
3. Requires Economizer.
4. All 22 nd digit model numbers for reheat coil (B) require additional factory installed options: Frostat, and 2” pleated filters.
5. Must be ordered with Throughthe-Base Electrical option or
Horizontal-Side Access and either
Unit Mounted Disconnect or
Circuit Breaker.
6. Available factory installed on downflow AND horizontal units.
Verify with ordering system.
7.
Cannot be fused.
8. Must be factory installed when using Through-the-Base Options.
9. ReliaTel Options Module is required when ordering the following accessories: 4 Stage
Cooling, Clogged Filter Switch,
Fan Fail Switch, Condensate
Overflow Switch, Discharge Air
Sensing Kit, Frostat, Ventilation
Override, Smoke Detector,
Dehumidification and Modulating
Gas Heat Furnace.
10. Option cannot be ordered in conjunction with field installed economizer on downflow units.
Must be factory installed. The return air smoke detector may not fit up or work properly on the
Voyager units when used in conjunction with 3 rd party accessories (such as bolt on heat wheels, economizers, and power exhaust). Do not order the return air smoke detectors when using this type of accessory.
11. Unit mounted disconnect and circuit breakers are mutually exclusive of each other.
12. Through-the-base electrical option or Horizontal-Side Access must be ordered with either unit mounted disconnect or circuit breaker. When adding heat, you must order Trane Electric Heat.
13. Available on high efficiency units only.
14. All Factory Installed Options are
Built-to-Order. Check order services for estimated production cycle.
15. TCI is for use with non-VariTrac systems and VariTrac systems.
16. For use with multi-speed and
SZVAV units only.
17. Demand Control Ventilation
Option includes wiring only. The
C0
2
sensor is a field-installed only option.
18. Frostat is standard on VAV and high efficiency units.
19. Supply and/or return smoke detector may not be used with the plenum smoke detector.
20. Only available where MOP is above 60A.
21. 575 VAC option is 25kA.
22. Standard filters are not available with Low Leak Economizers.
23. Human Interface is standard with
FDD (Fault Detection Diagnostics).
24. Must be used with BACnet™ open protocol.
24 RT-PRC028AC-EN
General Data
Table 3.
General data—cooling 12½–15 tons standard efficiency
Cooling Performance (a)
Gross Cooling Capacity
EER (Downflow/Horizontal) (b)
Nominal Airflow CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (d)
Outdoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI (DF/HZ)
Indoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
TS*150G3,4,W,K YS*150G3,4,W,K TS*180G3,4,W,K YS*180G3,4,W,K
150,000
11
5,000 / 4,000
140,000
12.4/13.5
66/100
12.73
2 / Scrolls
9.2
Microchannel
0.71
25.9
1/23
Microchannel
1.00
17.30
2/16
TXV
1/1.00 NPT
150,000
11
5,000 / 4,000
140,000
12.2/13.5
66/100
12.73
2 / Scrolls
9.2
Microchannel
0.71
25.9
1/23
Microchannel
1.00
17.30
2/16
TXV
1/1.00 NPT
186,000
11
6,000 / 5,400
176,000
12.4/13.2
67/100
16.00
2 / Scrolls
9.2
Microchannel
0.71
35.2
1/23
Microchannel
0.81
23.00
2/16
TXV
1/1.00 NPT
186,000
11
6,000 / 5,400
176,000
12.2/13.2
67/100
16.00
2 / Scrolls
9.2
Microchannel
0.71
35.2
1/23
Microchannel
0.81
23.00
2/16
TXV
1/1.00 NPT
Propeller
2 / 26
Propeller
2 / 26
Propeller
2 / 26
Propeller
2 / 26
Direct / 1 Direct / 1 Direct / 1 Direct / 1
11,000 11,000 11,000 11,000
2 / 0.50
2 / 0.50
2 / 0.50
2 / 0.50
1,100 1,100 1,100 1,100
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard/Oversized) (e)
Motor rpm (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
FC Centrifugal
1 / 15x15
Belt / 1
1
3.0 / 5.0
1,740 / 3,450
56HZ / 56HZ
FC Centrifugal
1 / 15x15
Belt / 1
1
3.0 / 5.0
1,740 / 3,450
56HZ / 56HZ
FC Centrifugal
1 / 18x18
Belt / 1
1
3.0 / 5.0 or 7.5
(f)
1,740 / 3,450
FC Centrifugal
1 / 18x18
Belt / 1
1
3.0 / 5.0 or 7.5
1,740 / 3,450
184TZ / 56HZ/184TZ 56HZ / 56HZ/184TZ
RT-PRC028AC-EN 25
General Data
Table 3.
General data—cooling 12½–15 tons standard efficiency
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
TS*150G3,4,W,K YS*150G3,4,W,K TS*180G3,4,W,K YS*180G3,4,W,K
Filters
Type Furnished (g)
Number Size Recommended
Throwaway Throwaway Throwaway Throwaway
Downflow
Horizontal
(2)20x20x2
(4)20x25x2
(2)20x20x2
(4)20x25x2
(2)20x20x2
(4)20x25x2
(2)20x20x2
(4)20x25x2
(4)20x20x2
(4)20x25x2
(8)20x25x2
(4)20x20x2
(4)20x25x2
(8)20x25x2
Refrigerant Charge
(Pounds of R-410A) (h)
Cir#1 / Cir#2 (DF)
Cir#1 / Cir#2 (HZ)
8.1/5.1
8.1/5.2
8.1/5.1
8.1/5.2
9.0/5.0
9.2/5.1
9.0/5.0
9.2/5.1
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(e)For 380V/60Hz units, the oversized motor (Indoor Fan) is used as the standard motor. Refer to oversized motor data.
(f) Offered only as a field installed accessory.
(g)An optional 2-inch pleated filter is also available.
(h)Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
Table 4.
General data—heating—12½–15 tons standard efficiency
Heating Models
Heating Input (Btu/h)
1st Stage (Btu)
Heating Output (Btu/h)
1st Stage (Btu)
Steady State Efficiency%
No. Burners
No. Stages
Gas Supply Line Pressure (in. wc)
Natural or LP (minimum/maximum)
Gas Connection Pipe Size (in.)
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
Heating Performance (a) (Gas/Electric Only)
Low High
Modulating
Turn Down
= 2.5:1 Low High
Modulating
Turn Down
= 2.5:1
150,000
100,000
120,000
80,000
80
1
250,000
175,000
200,000
140,000
80
1
2
2.5/14.0
2
2.5/14.0
Natural or LP Natural or LP
1/2 1/2
350,000
140,000
280,000
112,000
80
1
N/A
2.5/14.0
Natural Only
3/4
250,000
175,000
200,000
140,000
80
1
350,000
250,000
280,000
200,000
80
1
2
2.5/14.0
2
2.5/14.0
Natural or LP Natural or LP
1/2 3/4
350,000
140,000
280,000
112,000
80
1
N/A
2.5/14.0
Natural Only
3/4
(a) Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards
Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
26 RT-PRC028AC-EN
General Data
Table 5.
General data—17½–20 tons standard efficiency
Cooling Performance (a)
Gross Cooling Capacity
EER (Downflow/Horizontal) (b)
Nominal Airflow CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (d)
Outdoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI (DF/HZ)
Indoor Coil
Type
Tube Size (in.) ID
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
Motor rpm
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard/Oversized) (e)
Motor rpm (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units
TS*210G3,4,W,K YS*210G3,4,W,K TS*240G3,4,W,K YS*240G3,4,W,K
210,000
11
7,000 / 6,125
196,000
12.4/13.2
67/100
17.82
2 / Scrolls
9.4
Microchannel
1.00
35.2
1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
14,500
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
56HZ / 184T
210,000
11
7,000 / 6,125
196,000
12.2/13.2
67/100
17.82
2 / Scrolls
9.4
Microchannel
1.00
35.2
1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
14,500
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
56HZ / 184T
259,000
10
8,000 / 6,400
240,000
11.6/12.4
67/100
24.00
2 / Scrolls
9.4
Microchannel
1.0
35.2
1/23 / 1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
15,500
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
56HZ / 184T
259,000
10
8,000 / 6,400
240,000
11.4/12.4
67/100
24.00
2 / Scrolls
9.4
Microchannel
1.0
35.2
1/23 / 1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
15,500
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
56HZ / 184T
RT-PRC028AC-EN 27
General Data
Table 5.
General data—17½–20 tons standard efficiency
17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units
TS*210G3,4,W,K YS*210G3,4,W,K TS*240G3,4,W,K YS*240G3,4,W,K
Filters
Type Furnished (f)
Number Size Recommended
Throwaway Throwaway Throwaway Throwaway
Downflow
Horizontal
Refrigerant Charge
(Pounds of R-410A)
Cir#1/Cir#2 (DF)
Cir#1/Cir#2 (HZ)
(4)20x20x2
(4)20x25x2
(8)20x25x2
12.6/6.8
12.0/6.8
(4)20x20x2
(4)20x25x2
(8)20x25x2
12.6/6.8
12.0/6.8
(4)20x20x2
(4)20x25x2
(8)20x25x2
12.4/7.2
11.7/6.8
(4)20x20x2
(4)20x25x2
(8)20x25x2
12.4/7.2
11.7/6.8
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(e)For 380V/60Hz units, the oversized motor (Indoor Fan) is used as the standard motor. Refer to oversized motor data.
(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
Table 6.
General data—17½ standard efficiency
Cooling Performance (a)
Gross Cooling Capacity
EER (Downflow/Horizontal) (b)
Nominal Airflow CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (d)
Outdoor Coil
17½ Tons Downflow & Horizontal Units
TS*211G3,4,W YS*211G3,4,W
210,000
11
7,000 / 6,125
196,000
11.8/12.9
73/100
17.82
2 / Scrolls
9.4
210,000
11
7,000 / 6,125
196,000
11.8/12.9
73/100
17.82
2 / Scrolls
9.4
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI (DF/HZ)
Indoor Coil
Type
Tube Size (in.) ID
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
Microchannel
1.00
35.2
1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
Microchannel
1.00
35.2
1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
28 RT-PRC028AC-EN
RT-PRC028AC-EN
Table 6.
General data—17½ standard efficiency
17½ Tons Downflow & Horizontal Units
TS*211G3,4,W YS*211G3,4,W
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
Motor rpm
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard/Oversized) (e)
Motor rpm (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
Filters
Type Furnished (f)
Number Size Recommended
Propeller
2 / 26
Direct / 1
14,500
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
145T / 184T
Throwaway
Propeller
2 / 26
Direct / 1
14,500
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
145T / 184T
Throwaway
Downflow
Horizontal
Refrigerant Charge
(Pounds of R-410A)
Cir#1/Cir#2 (DF)
Cir#1/Cir#2 (HZ)
(4)20x20x2
(4)20x25x2
(8)20x25x2
14.4/7.4
14.4/7.4
(4)20x20x2
(4)20x25x2
(8)20x25x2
14.4/7.4
14.4/7.4
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb.
Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard
340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or
340/360.
(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(e)For 380V/60Hz units, the oversized motor (Indoor Fan) is used as the standard motor. Refer to oversized motor data.
(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
General Data
29
General Data
Table 7.
General data—heating—17½–20 tons standard efficiency
17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units
Heating Performance (a) (Gas/Electric Only)
Low High
Modulating
Turn
Down = 2.5:1 Low High
Modulating
Turn
Down =
2.5:1 Heating Models
Heating Input (Btu/h)
1st Stage (Btu)
Heating Output (Btu/h)
1st Stage (Btu)
Steady State Efficiency%
No. Burners
250,000
175,000
200,000
140,000
80
1
2
350,000
250,000
280,000
200,000
80
1
2
350,000
140,000
280,000
112,000
80
1
N/A
250,000
175,000
200,000
140,000
80
1
2
400,000
300,000
320,000
240,000
80
1
2
350,000
140,000
280,000
112,000
80
1
N/A No. Stages
Gas Supply Line Pressure (in. wc)
Natural or LP (minimum/maximum)
2.5/14.0
Natural or LP
1/2
2.5/14.0
Natural or LP
3/4
2.5/14.0
Natural Only
3/4
2.5/14.0
2.5/14.0
2.5/14.0
Natural or LP Natural or LP Natural Only
1/2 3/4 3/4 Gas Connection Pipe Size (in.)
(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards
Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
30 RT-PRC028AC-EN
RT-PRC028AC-EN
General Data
Table 8.
General data—25 ton standard efficiency
25 Tons Downflow & Horizontal Units
TS*300G3,4,W,K YS*300G3,4,W,K
Cooling Performance (a)
Gross Cooling Capacity
EER (Downflow/Horizontal) (b)
Nominal Airflow CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (d)
Outdoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI (DF/HZ)
Indoor Coil
Type
Tube Size (in.) ID
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
Motor rpm
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard/Oversized)
Motor rpm (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
296,400
10
10,000 / 7,750
270,000
11.6/12.4
66/100
27
2 / Scrolls
9.4
Microchannel
1.0
35.2
1/23 / 1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
Propeller
2 / 28
Direct / 1
16,100
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
7.5 / N/A
3,470 / N/A
184T / N/A
296,400
10
10,000 / 7,750
270,000
11.4/12.4
66/100
27
2 / Scrolls
9.4
Microchannel
1.0
35.2
1/23 / 1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
Propeller
2 / 28
Direct / 1
16,100
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
7.5 / N/A
3,470 / N/A
184T / N/A
31
General Data
Table 8.
General data—25 ton standard efficiency
25 Tons Downflow & Horizontal Units
TS*300G3,4,W,K YS*300G3,4,W,K
Filters
Type Furnished (e)
Number Size Recommended
Downflow
Horizontal
Refrigerant Charge
(Pounds of R-410A) (f)
Cir#1/Cir#2 (DF)
Cir#1/Cir#2 (HZ)
Throwaway
(4)20x20x2 (4)20x25x2
(8)20x25x2
Throwaway
(4)20x20x2 (4)20x25x2
(8)20x25x2
12.5/6.7
11.7/6.7
12.5/6.7
11.7/6.7
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
Certification Program, which is based on ARI Standard 340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(e)An optional 2-inch pleated filter is also available.
(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
Table 9.
General data—25 tons standard efficiency
25 Tons Downflow & Horizontal Units
TS*301G3,4,W YS*301G3,4,W
Cooling Performance (a)
Gross Cooling Capacity
EER (Downflow/Horizontal) (b)
Nominal Airflow CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (d)
Outdoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI (DF/HZ)
Indoor Coil
Type
Tube Size (in.) ID
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
296,400
10
10,000 / 8,000
272,000
10.4/12.0
50/100
27.20
2 / Scrolls
9.4
Microchannel
1.0
35.2
1/23 / 1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
296,400
10
10,000 / 8,000
272,000
10.4/12.0
50/100
27.20
2 / Scrolls
9.4
Microchannel
1.0
35.2
1/23 / 1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
32 RT-PRC028AC-EN
RT-PRC028AC-EN
General Data
Table 9.
General data—25 tons standard efficiency
25 Tons Downflow & Horizontal Units
TS*301G3,4,W YS*301G3,4,W
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
Motor rpm
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard/Oversized)
Motor rpm (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
Filters
Type Furnished (e)
Number Size Recommended
Downflow
Horizontal
Refrigerant Charge
(Pounds of R-410A) (f)
Cir#1/Cir#2 (DF)
Cir#1/Cir#2 (HZ)
Propeller
2 / 28
Direct / 1
16,100
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
7.5 / N/A
3,470 / N/A
184T / N/A
Throwaway
(4)20x20x2 (4)20x25x2
(8)20x25x2
Propeller
2 / 28
Direct / 1
16,100
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
7.5 / N/A
3,470 / N/A
184T / N/A
Throwaway
(4)20x20x2 (4)20x25x2
(8)20x25x2
10.5
10.5
10.5
10.5
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
Certification Program, which is based on ARI Standard 340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(e)An optional 2-inch pleated filter is also available.
(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
33
General Data
Table 10. General data—heating—25 tons
25 Tons Downflow & Horizontal Units
Heating Performance (a) (Gas/Electric Only)
Low High
Modulating Turn
Down = 2.5:1 Heating Models
Heating Input (Btu/h)
1st Stage (Btu)
Heating Output (Btu/h)
250,000
175,000
200,000
400,000
300,000
320,000
350,000
140,000
280,000
1st Stage (Btu)
Steady State Efficiency%
No. Burners
No. Stages
Gas Supply Line Pressure (in. wc)
Natural or LP (minimum/maximum)
Gas Connection Pipe Size (in.)
140,000
80
1
2
2.5 / 14.0
Natural or LP
½
240,000
80
1
2
2.5 / 14.0
Natural or LP
¾
112,000
80
1
N/A
2.5 / 14.0
Natural Only
¾
(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
34 RT-PRC028AC-EN
General Data
Table 11. General data—12½–15 ton high efficiency
Cooling Performance (a)
Gross Cooling Capacity
EER (b)
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2/Stage 3) (d)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (e)
Outdoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI
Indoor Coil
Type
Tube Size (in.) ID
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
Motor rpm
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard/Oversized)
Motor rpm (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
TH*150G3,4,W YH*150G3,4,W TH*180G3,4,W YH*180G3,4,W
152,400
12.1
5,000 / 4,000
144,000
13.5/15.0
30/70/100
11.90
2 / Scrolls
9.2
Microchannel
1.0
35.2
1 / 20
Hi-Performance
0.3125
26.00
4 / 15
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
2 / 0.50
1,100
FC Centrifugal
1 / 18x18
Belt / 1
1
3.0 / 5.0
1,740 / 3,450
145T / 145T
152,400
12.1
5,000 / 4,000
144,000
13.5/15.0
30/70/100
11.90
2 / Scrolls
9.2
Microchannel
1.0
35.2
1 / 20
Hi-Performance
0.3125
26.00
4 / 15
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
2 / 0.50
1,100
FC Centrifugal
1 / 18x18
Belt / 1
1
3.0 / 5.0
1,740 / 3,450
145T / 145T
180,500
12.1
6,000 / 5,250
174,000
14.0/15.0
32/68/100
14.38
2 / Scrolls
9.2
Microchannel
1.0
42.6
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
2 / 0.50
1,100
FC Centrifugal
1 / 18x18
Belt / 1
1
3.0 / 5.0
1,740 / 3,450
145T / 145T
180,500
12.1
6,000 / 5,250
174,000
14.0/15.0
32/68/100
14.38
2 / Scrolls
9.2
Microchannel
1.0
42.6
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
2 / 0.50
1,100
FC Centrifugal
1 / 18x18
Belt / 1
1
3.0 / 5.0
1,740 / 3,450
145T / 145T
RT-PRC028AC-EN 35
General Data
Table 11. General data—12½–15 ton high efficiency
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
TH*150G3,4,W YH*150G3,4,W TH*180G3,4,W YH*180G3,4,W
Filters
Type Furnished (f)
Number Size Recommended
Throwaway Throwaway Throwaway Throwaway
Downflow
Horizontal
Refrigerant Charge (Pounds of
R-410A) (g)
Downflow & Horizontal (Cir#1/Cir#2)
Optional Hot Gas Reheat Coil (Cir#1/Cir#2)
(4)20x20x2 (4)20x25x2 (4)20x20x2 (4)20x25x2
(8)20x25x2
12.5/7.1
9.2 / 6.9
(8)20x25x2
12.5/7.1
9.2 / 6.9
(8)20x20x2
(4)20x16x2
(12)20x20x2
13.0/8.5
10.9 / 8.9
(8)20x20x2
(4)20x16x2
(12)20x20x2
13.0/8.5
10.9 / 8.9
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
(d)3 stages not available with Reheat models.
(e)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(f) An optional 2 inch pleated filter is also available.
(g)Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
Table 12. General data—heating—12½-15 ton high efficiency
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
Heating Performance (a) (Gas/Electric Only)
Low High
Modulating
Turn Down
= 2.5:1 Low High
Modulating
Turn Down
= 2.5:1 Heating Models
Heating Input (Btu/h)
1st Stage (Btu)
Heating Output (Btu/h)
1st Stage (Btu)
Steady State Efficiency%
No. Burners
No. Stages
150,000 250,000 350,000
100,000 175,000 140,000
120,000 200,000 280,000
80,000 140,000 112,000
80 80 80
1 1 1
Gas Supply Line Pressure (in. wc) 2.5 / 14.0
Natural or LP (minimum/maximum)
Gas Connection Pipe Size (in.) ½
2.5 / 14.0
½
2.5 / 14.0
Natural Only
¾
250,000 350,000 350,000
175,000 250,000 140,000
200,000 280,000 280,000
140,000 200,000 112,000
80 80 80
1 1 1
2 2 N/A
2.5 / 14.0
2.5 / 14.0
2.5 / 14.0
½ ¾
Natural Only
¾
(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards
Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
36 RT-PRC028AC-EN
General Data
Table 13. General data—17½–20 ton high efficiency
17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units
TH*210G3,4,W YH*210G3,4,W TH*240G3,4,W YH*240G3,4,W
Cooling Performance (a)
Gross Cooling Capacity
EER (b)
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2/Stage 3) (d)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (e)
Outdoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI
Indoor Coil
Type
Tube Size (in.) ID
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
Motor rpm
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard/Oversized)
Motor rpm (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
214,800
11.8
7,000 / 5,600
204,000
13.0/14.0
31/69/100
17.29
2 / Scrolls
9.2
Microchannel
1.0
42.6
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
214,800
11.8
7,000 / 5,600
204,000
13.0/14.0
31/69/100
17.29
248,500
11.0
8,000 / 6,400
234,000
12.4/14.0
30/70/100
21.27
248,500
11.0
8,000 / 6,400
234,000
12.4/14.0
30/70/100
21.27
Propeller
2 / 26
Direct / 1
Propeller
2 / 26
Direct / 1
Propeller
2 / 28
Direct / 1
Propeller
2 / 28
Direct / 1
15,800 15,800 16,500 16,500
2 / 1.0
1,125
2 / 1.0
1,125
2 / 1.0
1,125
2 / 1.0
1,125
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
145T / 184T
2 / Scrolls
9.2
Microchannel
1.0
42.6
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
145T / 184T
2 / Scrolls
9.4
Microchannel
1.0
42.6
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
145T / 184T
2 / Scrolls
9.4
Microchannel
1.0
42.6
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
145T / 184T
RT-PRC028AC-EN 37
General Data
Table 13. General data—17½–20 ton high efficiency
17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units
TH*210G3,4,W YH*210G3,4,W TH*240G3,4,W YH*240G3,4,W
Filters
Type Furnished (f)
Number Size Recommended
Throwaway Throwaway Throwaway Throwaway
Downflow
Horizontal
Refrigerant Charge
(Pounds of R-410A) (g)
Downflow & Horizontal (Cir#1/Cir#2)
Optional Hot Gas Reheat Coil (Cir#1/Cir#2)
(8)20x20x2
(4)20x16x2
(12)20x20x2
14.0 / 7.3
12.2/8.9
(8)20x20x2
(4)20x16x2
(12)20x20x2
14.0 / 7.3
12.2/8.9
(8)20x20x2
(4)20x16x2
(12)20x20x2
15.5 / 7.5
11.9 / 9.6
(8)20x20x2
(4)20x16x2
(12)20x20x2
15.5 / 7.5
11.9 / 9.6
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
(d)3 stages not available with Reheat models.
(e)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(f) An optional 2 inch pleated filter is also available.
(g)Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
Table 14. General data—heating—17½–20 ton high efficiency
Heating Models
Heating Input (Btu/h)
17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units
Heating Performance (a) (Gas/Electric Only)
Low High
Modulating
Turn
Down = 2.5:1
250,000 350,000 350,000
175,000 250,000 140,000
Heating Output (Btu/h) 200,000 280,000 280,000
140,000 200,000 112,000
Steady State Efficiency%
No. Burners
No. Stages
80 80 80
1 1 1
Gas Supply Line Pressure (in. wc)
Natural or LP (minimum/maximum)
Gas Connection Pipe Size (in.)
2 2 N/A
2.5 / 14.0
½
2.5 / 14.0
¾
2.5/14.0
Natural Only
¾
Low High
Modulating
Turn
Down = 2.5:1
250,000 400,000 350,000
175,000 300,000 140,000
200,000 320,000 280,000
140,000 240,000 112,000
80 80 80
1 1 1
2 2 N/A
2.5 / 14.0
2.5 / 14.0
2.5/14.0
½ ¾
Natural Only
¾
(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards
Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
38 RT-PRC028AC-EN
RT-PRC028AC-EN
General Data
Table 15. General data—25 ton high efficiency
25 Tons Downflow & Horizontal Units
TH*300G3,4,W YH*300G3,4,W
Cooling Performance (a)
Gross Cooling Capacity
EER (b)
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2/Stage 3/Stage 4) (d)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (e)
Outdoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI
Indoor Coil
Type
Tube Size (in.) ID
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
Motor rpm
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard)
Motor rpm (Standard)
Motor Frame Size (Standard)
292,300
10.6
10,000 / 8,000
274,000
12.4/15.0
25/50/75/100
25.85
3 / Scrolls
9.4
Microchannel
1.0
42.58
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
292,300
10.6
10,000 / 8,000
274,000
12.4/15.0
25/50/75/100
25.85
Propeller
2 / 28
Direct / 1
Propeller
2 / 28
Direct / 1
16,500 16,500
2 / 1.0
1,125
2 / 1.0
1,125
FC Centrifugal
1 / 18x18
Belt / 1
1
7.5
3,470
184T
3 / Scrolls
9.4
Microchannel
1.0
42.58
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
FC Centrifugal
1 / 18x18
Belt / 1
1
7.5
3,470
184T
39
General Data
Table 15. General data—25 ton high efficiency
25 Tons Downflow & Horizontal Units
TH*300G3,4,W YH*300G3,4,W
Filters
Type Furnished (f)
Number Size Recommended
Downflow
Horizontal
Refrigerant Charge
(Pounds of R-410A) (g)
Downflow & Horizontal (Cir#1/Cir#2)
Optional Hot Gas Reheat Coil (Cir#1/Cir#2)
Throwaway
(8)20x20x2 (4)20x16x2
(12)20x20x2
Throwaway
(8)20x20x2 (4)20x16x2
(12)20x20x2
11.8 / 10.6
13.2 / 11.4
11.8 / 10.6
13.2 / 11.4
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
(d)3 and 4 stages not available with Reheat models.
(e)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(f) An optional 2-inch pleated filter is also available.
(g)Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
Table 16. General data—heating—25 ton high efficiency
Heating Models
Heating Input (Btu/h)
1st Stage (Btu)
Heating Output (Btu/h)
1st Stage (Btu)
Steady State Efficiency%
No. Burners
No. Stages
Gas Supply Line Pressure (in. wc)
Natural or LP (minimum/maximum)
Gas Connection Pipe Size (in.)
25 Tons Downflow & Horizontal Units
Heating Performance (a) (Gas/Electric Only)
Low High
Modulating Turn
Down = 2.5:1
250,000 400,000 350,000
175,000 300,000 140,000
200,000 320,000 280,000
140,000 240,000 112,000
80 80 80
1 1 1
2.5 / 14.0
2.5 / 14.0
2.5/14.0
Natural Only
¾ ½ ¾
(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
40 RT-PRC028AC-EN
Performance Data
Table 17. Gross cooling capacities 12½ tons three phase standard efficiency T/YS*150G3,4,W,K
Air
Flow cfm
4000
4500
5000
5500
6000
Air
Flow cfm
4000
Ent
DB
(°F)
75
80
85
90
75
75
80
85
90
85
90
75
80
85
80
85
90
75
80
90
Ent
DB
(°F)
61
153
161
142
147
156
164
157
161
159
159
158
164
85
67
157
161
105
138
158
164
173
172
173
174
174
173
73
124
154
63
97
130
163
61
Ambient Temperature
95
Entering Wet Bulb
67 73 61
105
67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
135
135
140
148
137
138
145
153
139
141
149
157
141
144
153
161
142
147
156
164
113
134
140
148
121
137
145
153
129
141
149
157
137
144
152
152
151
151
154
154
154
154
156
156
156
157
158
158
115
87
109
131
151
92
117
141
154
96
124
151
157
101
131
166
166
166
166
168
169
169
169
170
171
171
171
172
172
59
81
104
126
60
85
110
135
61
89
117
144
62
93
128
128
134
142
131
131
139
147
132
135
143
151
133
138
110
128
134
142
118
131
139
147
126
144
144
144
144
146
146
146
147
148
135 148
143 148
151 151
133 150
138 149
84
106
128
144
89
113
138
147
93
121
147
151
97
128
157
158
158
158
160
160
160
160
161
162
162
162
162
163
56
78
101 128.7 128.7 136.1 124.8 148.9 97.4
123 136.0 136.0 136.2 136.1 148.8 119.4
57
82
58
121.3 107.0 136.2 81.0 148.3 52.7
121.5 121.4 136.2 103.0 148.6 75.1
123.3 114.8 138.2 85.4 150.0 53.7
125.1 125.1 138.1 110.2 150.4 78.9
107 133.0 133.0 137.8 134.5 150.7 104.0
132 140.3 140.3 140.5 140.5 150.5 128.7
124.7 122.3 139.7 89.7 151.4 54.7
86 128.6 128.6 139.6 117.2 151.9 82.7
114 136.5 136.5 139.2 138.9 152.1 110.5
141 143.7 143.7 143.9 143.9 151.9 137.9
59 125.8 125.6 140.9 94.1 152.4 55.7
90 131.5 131.5 140.8 124.2 153.1 86.5
146
154
135
141
149
146 149
154 154
134 151
141 150
149 150
149
154
102
135
150
163
163
163
164
164
121 139.4 139.4 140.3 140.1 153.6 117.0
151 146.4 146.4 146.5 146.5 152.8 147.1
60 126.8 126.5 141.9 98.4 153.3 56.6
94 134.0 134.0 141.6 131.2 154.2 90.3
127 141.9 141.9 142.0 142.0 153.9 123.8
157
61
157 157 157 164
Ambient Temperature
120
Entering Wet Bulb
67 73
160 148.9 148.9 149.0 149.0 153.3 152.9
61
125
67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 114.1 103.8 127.9 77.7 138.5 49.3 110.4 102.1 123.6 76.0 133.4 47.5 106.5 100.4 119.0 74.1 127.9 45.6
80 115.3 115.3 127.9 99.7 138.9 71.7 112.3 112.3 123.6 98.0 133.7 69.9 109.1 109.1 119.1 96.2 128.3 68.1
85 122.6 122.6 127.8 121.5 139.2 94.0 119.3 119.3 123.3 119.7 134.1 92.3 115.7 115.7 118.7 117.8 128.8 90.4
90 129.4 129.4 129.5 129.5 139.2 116.0 125.8 125.8 125.9 125.9 134.1 114.3 121.9 121.9 122.0 122.0 128.7 112.4
4500
5000
75 115.8 111.5 129.6 82.0 140.0 50.3 111.8 109.7 125.1 80.3 134.6 48.4 107.8 107.6 120.4 78.5 128.9 46.5
80 119.0 119.0 129.5 106.8 140.4 75.5 115.8 115.8 125.0 105.0 135.1 73.7 112.3 112.3 120.3 103.2 129.5 71.8
85 126.4 126.4 129.2 129.0 140.7 100.6 122.8 122.8 124.7 124.5 135.3 98.7 119.0 119.0 120.0 119.8 129.7 96.8
90 133.1 133.1 133.2 133.2 140.5 125.2 129.1 129.1 129.3 129.3 135.2 123.4 124.9 124.9 125.0 125.0 129.5 121.5
75 116.9 116.7 130.9 86.4 141.0 51.2 113.0 112.8 126.3 84.6 135.5 49.4 108.9 108.7 121.4 82.8 129.7 47.5
80 122.1 122.1 130.8 113.8 141.7 79.3 118.7 118.7 126.1 112.0 136.3 77.5 114.9 114.9 121.3 110.2 130.6 75.6
85 129.5 129.5 130.4 130.2 141.8 107.0 125.7 125.7 125.9 125.8 136.3 105.2 121.6 121.6 121.7 121.7 130.5 103.3
90 135.9 135.9 136.0 136.0 141.5 134.4 131.6 131.6 131.7 131.7 135.9 132.4 127.0 127.0 127.1 127.1 130.0 129.5
75 118.0 117.8 131.9 90.7 141.8 52.1 114.0 113.8 127.2 88.9 136.2 50.3 109.9 109.8 122.2 87.1 130.3 48.4
80 124.7 124.7 131.7 120.8 142.7 83.0 121.0 121.0 127.0 119.0 137.3 81.2 117.1 117.1 121.9 117.1 131.5 79.4
5500
6000
85 132.0 132.0 132.1 132.1 142.6 113.5 127.9 127.9 128.0 128.0 137.0 111.6 123.6 123.6 123.7 123.7 131.1 109.7
90 138.2 138.2 138.3 138.3 142.0 141.6 133.7 133.7 133.8 133.8 136.3 135.9 128.8 128.8 128.9 128.9 130.3 130.0
75 118.9 118.8 132.7 94.9 142.5 53.1 115.3 115.3 127.8 93.1 136.8 51.2 111.6 111.6 122.8 91.3 130.8 49.3
80 126.8 126.8 132.4 127.7 143.7 86.9 123.0 123.0 127.4 125.8 138.0 85.1 118.9 118.9 122.2 121.9 132.0 83.1
85 134.0 134.0 134.1 134.1 143.2 119.9 129.7 129.7 129.8 129.8 137.5 118.1 125.2 125.2 125.3 125.3 131.5 116.2
90 140.3 140.3 140.3 140.3 142.4 142.0 135.5 135.5 135.6 135.6 136.7 136.4 130.4 130.4 130.4 130.4 130.8 130.5
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
* Stands for both downflow and horizontal unit.
RT-PRC028AC-EN 41
Performance Data
Table 18. Gross cooling capacities 15 tons three phase standard efficiency T/YS*180G3,4,W,K
Air
Flow cfm
4800
5400
6000
Ambient Temperature
Ent
DB
(°F)
85 95
Entering Wet Bulb
105
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 163.2 138.4 185.0 107.5 206.8 74.7 155.6 134.9 176.1 103.9 195.7
70.7
147.4 131.1 166.3
99.8
183.0
66.1
80 162.9 162.6 185.1 134.2 206.9 101.8 155.4 155.2 176.2 130.5 195.8
97.7
147.3 147.0 166.3 126.5 183.1
93.1
85 164.5 164.4 185.0 160.7 206.9 128.7 157.8 157.7 176.0 157.1 195.9 124.6 151.2 151.2 166.2 152.9 183.2 120.0
90 173.3 173.3 184.6 184.2 207.0 155.3 167.1 167.1 175.7 175.4 195.9 151.3 160.1 160.1 166.1 165.8 183.2 146.7
75 167.9 148.7 190.1 113.9 211.1 76.6 159.8 145.1 180.5 110.0 198.9
72.2
150.9 141.1 170.0 105.8 185.0
67.4
80 167.5 167.2 190.1 143.8 211.2 107.0 159.6 159.3 180.5 140.0 199.0 102.7 151.0 150.7 170.0 135.8 185.2
97.8
85 170.5 170.5 189.9 173.5 211.3 137.2 164.2 164.2 180.3 169.6 199.1 132.9 157.1 157.1 169.8 165.4 185.3 128.0
90 180.7 180.7 189.4 189.1 211.3 167.2 174.0 174.0 180.0 179.7 199.2 162.9 166.3 166.3 169.8 169.5 185.4 158.0
75 171.7 158.9 194.2 120.0 214.3 78.2 163.1 155.1 184.1 115.9 201.1
73.6
153.9 151.0 173.0 111.6 186.5
68.6
80 171.3 171.0 194.2 153.2 214.4 112.0 162.8 162.6 184.1 149.2 201.3 107.4 154.0 153.9 173.0 144.9 186.6 102.3
85 176.6 176.6 193.8 186.2 214.4 145.5 169.8 169.8 183.6 181.7 201.4 141.0 162.2 162.2 172.5 172.1 186.7 135.9
6600
7200
Air
Flow cfm
4800
90 187.2 187.2 193.3 192.9 214.5 178.8 179.9 179.9 183.4 183.2 201.4 174.3 171.6 171.6 172.9 172.8 186.6 169.2
75 174.9 168.9 197.5 125.9 216.5 79.6 165.9 164.6 187.0 121.7 202.5
74.8
156.2 155.8 175.3 117.2 188.2
70.0
80 174.4 174.2 197.5 162.5 216.7 116.8 165.8 165.7 186.9 158.3 202.6 112.0 156.7 156.6 175.2 153.8 188.3 107.1
85 181.9 181.9 196.9 196.4 216.8 153.7 174.7 174.7 186.3 185.8 202.7 148.9 166.5 166.5 174.7 174.3 188.4 144.0
90 192.8 192.8 196.4 196.1 216.8 190.3 184.9 184.9 186.5 186.3 202.9 185.5 176.0 176.0 176.1 176.1 188.3 180.6
75 177.6 177.1 200.3 131.7 218.1 80.9 168.3 167.8 189.3 127.4 204.3
76.2
158.2 157.8 177.1 122.8 189.5
71.3
80 177.2 177.0 200.3 171.5 218.3 121.4 168.5 168.3 189.2 167.3 204.4 116.8 160.2 160.2 177.0 162.6 189.7 111.8
85 186.6 186.6 199.4 198.9 218.4 161.7 178.9 178.9 188.4 187.9 204.5 157.0 170.3 170.3 176.4 175.9 189.8 152.1
90 197.7 197.7 199.4 199.2 218.4 201.7 189.3 189.3 189.4 189.2 204.2 196.9 179.6 179.6 179.6 179.6 189.5 188.8
Ambient Temperature
Ent
DB
(°F)
115 120
Entering Wet Bulb
125
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 138.6 127.2 155.7 95.6 168.4 61.0 134.2 125.2 150.1 93.3 160.9
58.4
144.2
91.0
153.4
55.8
80 138.8 138.5 155.7 122.2 168.6 88.0 134.5 134.3 150.1 120.0 161.0
85.4
144.3 117.7 153.5
82.8
85 144.0 144.0 155.6 148.6 168.7 114.9 140.2 140.2 150.0 146.4 161.1 112.3 136.3 136.3 144.2 143.7 153.6 109.7
90 152.4 152.4 155.7 155.5 168.8 141.6 148.2 148.2 150.3 150.0 161.1 138.9 143.8 143.8 144.8 144.7 153.7 136.4
75 141.6 137.0 158.7 101.3 170.1 62.3 136.9 134.9 152.6 99.0 162.5
59.7
132.1 131.8 146.3
96.6
154.4
57.0
80 142.0 141.9 158.7 131.3 170.2 92.7 137.6 137.4 152.7 128.9 162.6
90.1
133.1 132.9 146.4 126.5 154.6
87.4
5400
6000
6600
85 149.3 149.3 158.4 158.0 170.3 122.8 145.2 145.2 152.5 152.1 162.7 120.3 140.8 140.8 146.3 145.9 154.7 117.6
90 157.8 157.8 159.0 158.8 170.4 152.8 153.1 153.1 153.3 153.1 162.8 150.3 147.9 147.9 148.0 148.0 154.8 147.6
75 144.0 143.6 160.9 106.9 171.6 63.5 139.0 138.6 154.5 104.5 163.5
60.9
134.0 133.6 147.8 102.0 155.0
58.1
80 144.8 144.8 160.9 140.2 171.7 97.3 140.7 140.7 154.5 137.7 163.7
94.6
136.5 136.5 147.8 135.2 155.2
91.8
85 153.8 153.8 160.6 160.3 171.8 130.9 149.2 149.2 154.4 154.0 163.8 128.2 144.4 144.4 147.9 147.5 155.4 125.4
90 162.2 162.2 162.3 162.3 171.8 164.2 156.8 156.8 156.9 156.9 163.8 161.5 150.8 150.8 150.8 150.8 155.6 154.8
75 146.0 145.6 162.6 112.4 172.5 64.8 140.8 140.4 155.9 109.9 164.1
62.0
135.4 135.1 148.9 107.3 155.2
59.1
80 148.4 148.4 162.6 149.0 172.7 101.9 144.1 144.1 155.9 146.5 164.3
99.2
139.6 139.6 148.9 143.9 155.5
96.3
85 157.5 157.5 162.3 161.9 172.9 138.8 152.6 152.6 155.6 155.2 164.5 136.1 147.2 147.2 148.8 148.5 155.8 133.2
90 165.5 165.5 165.6 165.6 172.9 172.2 159.3 159.3 159.4 159.4 164.7 164.0 152.2 152.2 152.2 152.2 156.1 155.5
7200
75 147.6 147.2 163.9 117.8 173.2 66.0 142.2 141.8 156.9 115.2 164.5
63.2
136.6 136.2 149.6 112.5 155.3
60.2
80 151.6 151.6 163.8 157.7 173.4 106.5 147.0 147.0 156.9 155.1 164.7 103.6 142.1 142.1 149.6 149.0 155.5 100.7
85 160.6 160.6 163.3 163.0 173.6 146.7 155.2 155.2 156.6 156.4 165.0 143.9 149.4 149.4 149.7 149.4 156.0 141.1
90 167.9 167.9 167.9 167.9 173.7 173.0 160.7 160.7 160.8 160.8 165.2 164.6 153.9 153.9 154.0 154.0 156.4 155.7
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Stands for both downflow and horizontal unit.
42 RT-PRC028AC-EN
Performance Data
Table 19. Gross cooling capacities 17½ tons three phase standard efficiency T/YS*210G3,4,W,K
Air
Flow cfm
5600
6300
7000
Ambient Temperature
Ent
DB
(°F)
85 95
Entering Wet Bulb
105
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 186.0 161.1 210.2 124.5 233.8 85.5 176.4 156.7 199.5 120.1 221.1 80.9 166.4 152.2 188.0 115.4 207.2 76.0
80 185.1 184.9 209.9 155.7 233.8 117.2 175.8 175.6 199.3 151.4 221.1 112.6 166.2 166.1 187.8 146.7 207.3 107.7
85 191.8 191.8 209.4 186.6 233.7 148.7 184.3 184.3 198.6 182.2 221.0 144.1 176.1 176.1 187.1 177.5 207.2 139.2
90 203.1 203.1 208.5 208.2 233.5 180.1 195.2 195.2 198.0 197.7 220.9 175.5 186.5 186.5 187.0 186.9 207.0 170.5
75 189.9 172.8 214.5 131.5 237.5 87.3 179.9 168.3 203.2 126.9 224.3 82.7 169.5 163.7 191.1 122.1 209.7 77.6
80 189.1 188.9 214.2 166.6 237.5 123.0 179.8 179.7 203.0 162.1 224.3 118.4 171.3 171.3 190.9 157.3 209.8 113.3
85 199.0 199.0 213.3 201.1 237.4 158.5 191.0 191.0 202.1 196.4 224.2 153.8 182.3 182.3 190.0 189.1 209.8 148.9
90 210.7 210.7 212.4 212.2 237.1 193.7 202.2 202.2 202.4 202.4 223.9 189.0 192.8 192.8 193.0 193.0 209.5 183.9
75 193.1 184.2 218.0 138.3 240.3 89.1 182.8 179.0 206.3 133.6 226.6 84.4 171.9 171.4 193.7 128.7 211.5 79.2
80 193.0 193.0 217.6 177.2 240.4 128.8 185.0 185.0 205.9 172.6 226.7 124.0 176.3 176.3 193.3 167.7 211.7 118.9
85 205.2 205.2 216.5 213.8 240.3 168.2 196.7 196.7 204.5 204.1 226.7 163.5 187.4 187.4 191.9 191.6 211.8 158.4
7700
8400
Air
Flow cfm
5600
90 217.3 217.3 217.5 217.5 239.8 207.1 208.2 208.2 208.4 208.4 226.2 202.4 198.2 198.2 198.3 198.3 211.4 197.3
75 195.7 193.8 220.8 144.9 242.6 90.8 184.9 184.5 208.7 140.2 228.4 86.0 173.6 173.2 195.7 135.3 212.8 80.7
80 198.1 198.1 220.4 187.8 242.7 134.4 189.7 189.7 208.3 183.1 228.6 129.6 180.5 180.5 195.3 178.1 213.2 124.4
85 210.5 210.5 218.6 218.1 242.7 177.8 201.6 201.6 206.5 206.2 228.6 173.0 191.7 191.7 193.7 193.4 213.2 167.8
90 222.9 222.9 223.1 223.1 242.0 220.6 213.4 213.4 213.5 213.5 228.1 215.8 202.6 202.6 202.7 202.7 212.8 208.8
75 197.6 197.1 223.2 151.5 244.3 92.4 186.5 186.0 210.7 146.8 229.8 87.6 175.1 174.8 197.6 141.9 213.8 82.3
80 202.5 202.5 222.6 198.2 244.5 140.0 193.8 193.8 210.2 193.5 230.1 135.2 184.2 184.2 196.9 188.5 214.3 129.9
85 215.2 215.2 220.4 220.0 244.5 187.3 205.9 205.9 208.2 207.8 230.1 182.5 195.6 195.6 195.7 195.7 214.3 177.2
90 227.8 227.8 228.0 228.0 243.9 234.0 217.7 217.7 217.8 217.8 229.5 226.5 206.2 206.2 206.3 206.3 213.4 212.7
Ambient Temperature
Ent
DB
(°F)
115 120
Entering Wet Bulb
125
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 156.8 147.9 176.0 110.7 192.2 70.7 152.4 145.9 170.0 108.3 184.3 68.0
164.1 106.0 176.1 65.2
80 157.8 157.8 175.8 141.9 192.3 102.5 154.1 154.1 169.9 139.6 184.5 99.8
164.0 137.3 176.5 97.0
85 167.6 167.6 175.3 171.8 192.4 134.1 163.4 163.4 169.2 167.8 184.7 131.4 159.1 159.1 163.2 162.9 176.8 128.7
90 177.1 177.1 177.2 177.2 192.2 165.3 172.1 172.1 172.2 172.2 184.5 162.6 166.9 166.9 167.0 167.0 176.5 159.9
75 159.4 157.6 178.6 117.2 193.9 72.2 154.5 154.1 172.3 114.8 185.6 69.4 150.2 149.9 166.1 112.5 177.1 66.6
80 163.0 163.0 178.4 152.4 194.2 108.0 158.9 158.9 172.1 149.9 186.0 105.2 154.9 154.9 165.9 147.6 177.7 102.4
6300
7000
7700
85 173.0 173.0 177.3 177.0 194.3 143.5 168.3 168.3 171.1 170.8 186.2 140.8 163.4 163.4 164.9 164.6 177.9 138.0
90 182.5 182.5 182.7 182.7 194.1 178.6 177.0 177.0 177.2 177.2 186.0 175.9 171.1 171.1 171.2 171.2 177.7 172.5
75 161.1 160.8 180.6 123.7 195.1 73.7 156.2 155.9 174.2 121.3 186.5 70.8 151.7 151.4 167.8 118.9 177.7 67.9
80 167.4 167.4 180.3 162.7 195.6 113.5 162.9 162.9 173.8 160.2 187.2 110.7 158.5 158.5 167.3 157.8 178.6 107.8
85 177.4 177.4 179.1 178.7 195.7 152.9 172.2 172.2 172.7 172.5 187.3 150.1 166.8 166.8 166.9 166.9 178.6 147.2
90 187.0 187.0 187.1 187.1 195.4 190.8 180.9 180.9 181.0 181.0 187.0 185.9 174.4 174.4 174.5 174.5 178.1 177.5
75 162.7 162.4 182.3 130.3 195.9 75.2 157.6 157.3 175.7 127.8 187.1 72.3 153.1 152.9 169.2 125.3 178.1 69.3
80 171.1 171.1 181.8 173.0 196.6 118.9 166.3 166.3 175.1 170.3 188.1 116.1 161.5 161.5 168.5 166.3 179.4 113.3
85 181.2 181.2 181.3 181.3 196.6 162.3 175.6 175.6 175.7 175.7 188.0 159.4 169.7 169.7 169.8 169.8 179.1 156.8
90 190.5 190.5 190.6 190.6 196.0 195.3 183.8 183.8 183.9 183.9 187.2 186.7 176.6 176.6 176.7 176.7 178.2 177.7
8400
75 164.1 163.9 183.9 136.8 196.5 76.6 159.1 159.1 177.0 134.2 187.5 73.7 154.9 154.9 170.1 131.7
80 174.2 174.2 183.2 181.5 197.6 124.4 169.1 169.1 176.0 175.3 188.9 121.6 164.0 164.0 169.0 168.5
85 184.4 184.4 184.5 184.5 197.3 171.6 178.5 178.5 178.6 178.6 188.5 169.2 172.2 172.2 172.2 172.2
90 193.2 193.2 193.3 193.3 196.3 195.8 185.9 185.9 186.0 186.0 187.3 186.8 177.9 177.9 177.9 177.9
-
-
-
-
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Stands for both downflow and horizontal unit.
-
-
-
-
RT-PRC028AC-EN 43
Performance Data
Table 20. Gross cooling capacities 17½ tons three phase standard efficiency T/YS*211G3,4,W
Air
Flow cfm
5600
6300
7000
Ambient Temperature
Ent
DB
(°F)
85 95
Entering Wet Bulb
105
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 186.0 161.1 210.2 124.5 233.8 85.5 176.4 156.7 199.5 120.1 221.1 80.9 166.4 152.2 188.0 115.4 207.2 76.0
80 185.1 184.9 209.9 155.7 233.8 117.2 175.8 175.6 199.3 151.4 221.1 112.6 166.2 166.1 187.8 146.7 207.3 107.7
85 191.8 191.8 209.4 186.6 233.7 148.7 184.3 184.3 198.6 182.2 221.0 144.1 176.1 176.1 187.1 177.5 207.2 139.2
90 203.1 203.1 208.5 208.2 233.5 180.1 195.2 195.2 198.0 197.7 220.9 175.5 186.5 186.5 187.0 186.9 207.0 170.5
75 189.9 172.8 214.5 131.5 237.5 87.3 179.9 168.3 203.2 126.9 224.3 82.7 169.5 163.7 191.1 122.1 209.7 77.6
80 189.1 188.9 214.2 166.6 237.5 123.0 179.8 179.7 203.0 162.1 224.3 118.4 171.3 171.3 190.9 157.3 209.8 113.3
85 199.0 199.0 213.3 201.1 237.4 158.5 191.0 191.0 202.1 196.4 224.2 153.8 182.3 182.3 190.0 189.1 209.8 148.9
90 210.7 210.7 212.4 212.2 237.1 193.7 202.2 202.2 202.4 202.4 223.9 189.0 192.8 192.8 193.0 193.0 209.5 183.9
75 193.1 184.2 218.0 138.3 240.3 89.1 182.8 179.0 206.3 133.6 226.6 84.4 171.9 171.4 193.7 128.7 211.5 79.2
80 193.0 193.0 217.6 177.2 240.4 128.8 185.0 185.0 205.9 172.6 226.7 124.0 176.3 176.3 193.3 167.7 211.7 118.9
85 205.2 205.2 216.5 213.8 240.3 168.2 196.7 196.7 204.5 204.1 226.7 163.5 187.4 187.4 191.9 191.6 211.8 158.4
7700
8400
Air
Flow cfm
5600
90 217.3 217.3 217.5 217.5 239.8 207.1 208.2 208.2 208.4 208.4 226.2 202.4 198.2 198.2 198.3 198.3 211.4 197.3
75 195.7 193.8 220.8 144.9 242.6 90.8 184.9 184.5 208.7 140.2 228.4 86.0 173.6 173.2 195.7 135.3 212.8 80.7
80 198.1 198.1 220.4 187.8 242.7 134.4 189.7 189.7 208.3 183.1 228.6 129.6 180.5 180.5 195.3 178.1 213.2 124.4
85 210.5 210.5 218.6 218.1 242.7 177.8 201.6 201.6 206.5 206.2 228.6 173.0 191.7 191.7 193.7 193.4 213.2 167.8
90 222.9 222.9 223.1 223.1 242.0 220.6 213.4 213.4 213.5 213.5 228.1 215.8 202.6 202.6 202.7 202.7 212.8 208.8
75 197.6 197.1 223.2 151.5 244.3 92.4 186.5 186.0 210.7 146.8 229.8 87.6 175.1 174.8 197.6 141.9 213.8 82.3
80 202.5 202.5 222.6 198.2 244.5 140.0 193.8 193.8 210.2 193.5 230.1 135.2 184.2 184.2 196.9 188.5 214.3 129.9
85 215.2 215.2 220.4 220.0 244.5 187.3 205.9 205.9 208.2 207.8 230.1 182.5 195.6 195.6 195.7 195.7 214.3 177.2
90 227.8 227.8 228.0 228.0 243.9 234.0 217.7 217.7 217.8 217.8 229.5 226.5 206.2 206.2 206.3 206.3 213.4 212.7
Ambient Temperature
Ent
DB
(°F)
115 120
Entering Wet Bulb
125
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 156.8 147.9 176.0 110.7 192.2 70.7 152.4 145.9 170.0 108.3 184.3 68.0
164.1 106.0 176.1 65.2
80 157.8 157.8 175.8 141.9 192.3 102.5 154.1 154.1 169.9 139.6 184.5 99.8
164.0 137.3 176.5 97.0
85 167.6 167.6 175.3 171.8 192.4 134.1 163.4 163.4 169.2 167.8 184.7 131.4 159.1 159.1 163.2 162.9 176.8 128.7
90 177.1 177.1 177.2 177.2 192.2 165.3 172.1 172.1 172.2 172.2 184.5 162.6 166.9 166.9 167.0 167.0 176.5 159.9
75 159.4 157.6 178.6 117.2 193.9 72.2 154.5 154.1 172.3 114.8 185.6 69.4 150.2 149.9 166.1 112.5 177.1 66.6
80 163.0 163.0 178.4 152.4 194.2 108.0 158.9 158.9 172.1 149.9 186.0 105.2 154.9 154.9 165.9 147.6 177.7 102.4
6300
7000
7700
85 173.0 173.0 177.3 177.0 194.3 143.5 168.3 168.3 171.1 170.8 186.2 140.8 163.4 163.4 164.9 164.6 177.9 138.0
90 182.5 182.5 182.7 182.7 194.1 178.6 177.0 177.0 177.2 177.2 186.0 175.9 171.1 171.1 171.2 171.2 177.7 172.5
75 161.1 160.8 180.6 123.7 195.1 73.7 156.2 155.9 174.2 121.3 186.5 70.8 151.7 151.4 167.8 118.9 177.7 67.9
80 167.4 167.4 180.3 162.7 195.6 113.5 162.9 162.9 173.8 160.2 187.2 110.7 158.5 158.5 167.3 157.8 178.6 107.8
85 177.4 177.4 179.1 178.7 195.7 152.9 172.2 172.2 172.7 172.5 187.3 150.1 166.8 166.8 166.9 166.9 178.6 147.2
90 187.0 187.0 187.1 187.1 195.4 190.8 180.9 180.9 181.0 181.0 187.0 185.9 174.4 174.4 174.5 174.5 178.1 177.5
75 162.7 162.4 182.3 130.3 195.9 75.2 157.6 157.3 175.7 127.8 187.1 72.3 153.1 152.9 169.2 125.3 178.1 69.3
80 171.1 171.1 181.8 173.0 196.6 118.9 166.3 166.3 175.1 170.3 188.1 116.1 161.5 161.5 168.5 166.3 179.4 113.3
85 181.2 181.2 181.3 181.3 196.6 162.3 175.6 175.6 175.7 175.7 188.0 159.4 169.7 169.7 169.8 169.8 179.1 156.8
90 190.5 190.5 190.6 190.6 196.0 195.3 183.8 183.8 183.9 183.9 187.2 186.7 176.6 176.6 176.7 176.7 178.2 177.7
8400
75 164.1 163.9 183.9 136.8 196.5 76.6 159.1 159.1 177.0 134.2 187.5 73.7 154.9 154.9 170.1 131.7
80 174.2 174.2 183.2 181.5 197.6 124.4 169.1 169.1 176.0 175.3 188.9 121.6 164.0 164.0 169.0 168.5
85 184.4 184.4 184.5 184.5 197.3 171.6 178.5 178.5 178.6 178.6 188.5 169.2 172.2 172.2 172.2 172.2
90 193.2 193.2 193.3 193.3 196.3 195.8 185.9 185.9 186.0 186.0 187.3 186.8 177.9 177.9 177.9 177.9
-
-
-
-
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Stands for both downflow and horizontal unit.
-
-
-
-
44 RT-PRC028AC-EN
Performance Data
Table 21. Gross cooling capacities 20 tons three phase standard efficiency T/YS*240G3,4,W,K
Air
Flow cfm
6400
7200
8000
Ambient Temperature
Ent
DB
(°F)
85 95
Entering Wet Bulb
105
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 230.4 187.9 260.3 147.4 287.7 103.3 219.7 182.8 247.5 142.0 271.7 97.5 208.2 177.5 233.5 136.2 253.6 91.0
80 229.9 221.9 260.2 182.1 287.8 138.7 219.2 216.9 247.4 176.7 271.9 132.8 207.8 207.5 233.4 170.9 253.9 126.3
85 231.6 231.5 260.0 216.6 287.9 173.7 222.2 222.2 247.2 211.2 272.0 167.9 213.1 213.1 233.1 205.4 254.1 161.4
90 244.0 244.0 259.2 250.6 287.9 208.5 235.1 235.1 246.5 245.2 272.1 202.7 225.2 225.2 232.8 232.5 254.4 196.3
75 236.0 200.9 265.9 154.9 292.1 105.1 224.6 195.6 252.3 149.4 275.0 99.0 212.2 190.0 237.4 143.4 255.9 92.3
80 235.3 234.9 265.7 193.9 292.3 144.8 224.0 223.7 252.1 188.4 275.2 138.7 211.9 211.7 237.3 182.4 256.1 132.0
85 239.6 239.6 265.4 232.7 292.4 184.2 230.6 230.6 251.7 227.1 275.5 178.2 220.6 220.6 236.9 221.1 256.5 171.5
90 253.6 253.6 264.7 264.3 292.5 223.4 244.0 244.0 251.2 250.9 275.7 217.4 233.1 233.1 236.8 236.5 256.6 211.2
75 240.4 213.5 270.2 162.2 295.3 106.7 228.3 208.1 256.0 156.5 277.2 100.4 215.3 202.4 240.4 150.4 258.3 93.9
80 239.6 239.3 270.0 205.6 295.5 150.8 227.9 227.6 255.7 199.9 277.6 144.5 215.6 215.4 240.3 193.8 258.6 138.0
85 247.4 247.4 269.5 248.5 295.8 194.6 237.8 237.8 255.2 242.8 278.0 188.4 227.0 227.0 239.7 236.7 258.8 181.7
8800
9600
Air
Flow cfm
6400
90 261.8 261.8 268.9 268.5 295.9 238.2 251.4 251.4 255.0 254.7 278.1 232.0 239.5 239.5 240.4 240.2 258.4 225.6
75 243.8 225.9 273.8 169.4 297.6 108.2 231.2 220.4 258.9 163.6 279.5 101.9 217.8 214.6 242.7 157.3 260.1 95.4
80 243.2 242.9 273.5 217.1 298.0 156.7 231.5 231.3 258.8 211.5 279.5 150.4 219.1 219.1 242.7 205.1 260.4 143.9
85 254.2 254.2 272.7 264.2 298.3 204.9 243.9 243.9 258.0 257.1 279.9 198.5 232.4 232.4 242.1 241.6 260.5 192.0
90 268.8 268.8 272.5 272.3 298.4 252.8 257.6 257.6 258.7 258.4 279.8 246.5 244.7 244.7 244.9 244.9 260.4 239.8
75 246.6 238.2 276.6 176.5 299.5 109.6 233.8 232.7 261.3 170.6 281.4 103.5 219.9 219.4 244.6 164.2 261.5 96.9
80 246.7 246.5 276.5 228.6 299.8 162.5 234.7 234.7 261.3 222.7 281.7 156.4 223.6 223.6 244.5 216.3 261.9 149.8
85 260.1 260.1 275.5 274.8 300.3 215.2 249.2 249.2 260.3 259.7 281.7 209.0 237.0 237.0 243.7 243.3 262.2 202.4
90 274.9 274.9 276.0 275.8 300.2 267.3 262.9 262.9 263.1 263.1 281.3 260.9 249.0 249.0 249.2 249.2 261.8 254.3
Ambient Temperature
Ent
DB
(°F)
115 120
Entering Wet Bulb
125
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 196.3 172.1 218.4 130.1 234.3 84.1 190.2 169.3 210.4 126.9 224.3 80.6
202.2 123.7 214.0 77.1
80 196.0 195.8 218.4 164.8 234.5 119.4 190.1 189.9 210.5 161.7 224.6 116.0
85 203.1 203.1 218.1 199.3 234.6 154.4 198.0 198.0 210.2 196.1 224.9 151.0
-
-
-
-
202.4 158.5 214.4 112.4
202.2 192.9 214.8 147.5
90 214.2 214.2 218.0 217.8 234.7 189.3 208.2 208.2 210.3 210.1 225.0 185.9
202.5 202.3 214.9 182.4
75 199.5 184.4 221.4 137.1 236.4 85.5 193.1 181.5 213.0 133.8 226.0 82.0 186.8 178.8 204.4 130.4 215.2 78.4
80 199.6 199.5 221.4 176.2 236.7 125.3 193.6 193.5 213.1 172.9 226.4 121.7 187.8 187.8 204.6 169.6 215.7 118.1
7200
8000
8800
85 209.8 209.8 221.0 214.8 237.0 164.7 203.9 203.9 212.8 210.3 226.8 161.2 197.8 197.8 204.4 203.4 216.3 157.6
90 220.8 220.8 221.5 221.3 237.0 203.9 214.0 214.0 214.1 214.1 226.7 200.3 206.6 206.6 206.7 206.7 216.2 196.8
75 202.1 196.5 223.6 143.9 237.9 87.0 195.4 193.3 214.9 140.6 227.0 83.3 188.8 187.8 205.9 137.2 215.8 79.6
80 203.3 203.3 223.7 187.4 238.3 131.1 197.8 197.8 215.0 184.0 227.6 127.5 192.1 192.1 206.0 180.6 216.6 123.8
85 215.2 215.2 223.3 222.8 238.5 174.9 208.8 208.8 214.6 214.3 228.2 171.5 202.0 202.0 205.8 205.4 217.2 167.8
90 225.9 225.9 226.1 226.1 238.6 218.3 218.3 218.3 218.4 218.4 228.0 214.8 209.9 209.9 210.0 210.0 217.0 210.6
75 204.1 203.6 225.4 150.7 239.0 88.4 197.3 196.8 216.3 147.3 227.7 84.7 190.4 189.9 207.1 143.8
-
80 207.8 207.8 225.4 198.5 239.5 136.9 201.8 201.8 216.3 195.1 228.5 133.3 195.7 195.7 207.1 191.6
85 219.7 219.7 224.9 224.5 240.0 185.2 212.7 212.7 215.9 215.5 229.0 181.6 205.2 205.2 206.8 206.4
90 229.8 229.8 229.9 229.9 239.7 232.8 221.2 221.2 221.3 221.3 228.9 224.7 212.2 212.2 212.3 212.3
-
-
-
-
-
-
9600
75 205.8 205.3 226.7 157.5 239.7 89.8 198.5 198.1 217.4 154.0 228.2 86.0 191.4 191.0
80 211.6 211.6 226.6 209.5 240.4 142.7 205.2 205.2 217.3 206.0 229.1 139.1 198.5 198.5
85 223.3 223.3 226.1 225.7 240.9 195.4 215.8 215.8 216.9 216.5 229.6 191.7 207.7 207.7
90 232.6 232.6 232.7 232.7 240.7 239.0 223.6 223.6 223.7 223.7 229.5 228.8 214.5 214.5
-
-
-
-
-
-
-
-
-
-
-
-
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Stands for both downflow and horizontal unit.
-
-
-
-
RT-PRC028AC-EN 45
Performance Data
Table 22. Gross cooling capacities 25 tons three phase standard efficiency T/YS*300G3,4,W,K
Air
Flow cfm
7000
8000
9000
Ambient Temperature
Ent
DB
(°F)
85 95
Entering Wet Bulb
105
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 257.6 212.0 289.0 165.3 317.0 114.6 245.8 206.5 274.9 159.4 299.4 108.2 233.1 200.6 259.5 153.1 279.6 101.1
80 257.0 250.5 288.9 204.5 317.1 154.5 245.3 244.2 274.8 198.7 299.5 148.1 232.7 232.3 259.5 192.4 279.8 141.0
85 259.2 259.1 288.8 243.6 317.2 194.2 249.7 249.7 274.6 237.7 299.7 187.7 239.4 239.4 259.2 231.3 280.1 180.7
90 273.4 273.4 287.9 282.0 317.2 233.5 263.5 263.5 274.1 273.6 299.8 227.1 252.3 252.3 258.7 258.4 280.4 220.2
75 264.4 228.7 295.5 175.0 321.8 116.8 251.7 223.0 280.5 168.9 302.9 110.1 238.0 216.8 264.2 162.4 281.8 102.7
80 263.5 263.0 295.4 219.8 322.0 162.4 250.9 250.6 280.4 213.7 303.1 155.7 237.6 237.4 264.1 207.3 282.0 148.3
85 270.1 270.1 295.0 264.3 322.1 207.6 259.9 259.9 279.9 258.2 303.4 201.0 248.6 248.6 263.6 251.6 282.5 193.7
90 285.1 285.1 294.2 293.7 322.2 252.7 274.1 274.1 279.3 279.0 303.6 246.1 261.6 261.6 263.6 263.4 282.7 238.7
75 269.4 245.0 300.5 184.4 325.2 118.8 256.0 239.1 284.8 178.2 305.1 111.8 241.7 232.8 267.6 171.5 284.3 104.8
80 268.4 268.1 300.4 234.8 325.4 170.0 255.7 255.5 284.7 228.6 305.4 163.1 242.3 242.1 267.6 222.1 284.5 156.0
85 279.4 279.4 299.7 284.7 325.7 221.0 268.4 268.4 283.9 278.5 305.9 214.1 256.1 256.1 267.0 266.2 284.7 206.9
10000
11000
Air
Flow cfm
7000
90 294.7 294.7 299.1 298.8 325.8 271.6 282.6 282.6 284.2 284.0 306.1 264.8 268.8 268.8 269.0 269.0 284.4 257.6
75 273.3 261.1 304.4 193.6 327.7 120.8 259.5 255.0 288.0 187.3 307.8 114.0 244.7 244.0 270.1 180.4 286.4 106.9
80 273.1 272.9 304.3 249.8 328.0 177.7 260.3 260.3 288.1 243.4 307.8 170.8 248.3 248.3 270.2 236.5 286.7 163.8
85 287.3 287.3 303.3 302.5 328.3 234.3 275.4 275.4 287.0 286.2 307.9 227.3 262.1 262.1 269.1 268.5 286.9 220.4
90 302.6 302.6 303.8 303.5 328.2 290.4 289.5 289.5 289.7 289.7 307.7 283.6 274.4 274.4 274.5 274.5 286.4 276.4
75 276.5 275.7 307.6 202.8 330.2 122.9 262.3 261.6 290.6 196.3 310.1 116.2 247.0 246.2 272.1 189.3 288.1 109.0
80 277.6 277.6 307.6 264.5 330.3 185.5 266.1 266.1 290.6 258.0 310.3 178.8 253.4 253.4 272.0 251.0 288.4 171.5
85 293.9 293.9 306.1 305.3 331.2 247.7 281.3 281.3 289.1 288.4 310.4 241.0 267.1 267.1 270.8 270.4 288.6 233.8
90 309.2 309.2 309.4 309.4 330.3 309.3 295.0 295.0 295.2 295.2 309.5 302.3 278.5 278.5 278.7 278.7 288.1 286.9
Ambient Temperature
Ent
DB
(°F)
115 120
Entering Wet Bulb
125
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 219.7 194.5 243.0 146.4 258.2 93.6 212.8 191.4 234.3 143.0 247.2 89.8
236.0 85.9
80 219.4 219.2 243.0 185.7 258.2 133.4 212.8 212.5 234.3 182.3 247.5 129.7
85 228.2 228.2 242.7 224.7 258.5 173.0 222.2 222.2 234.1 221.2 247.8 169.3
90 239.8 239.8 242.5 242.2 258.7 212.5 233.0 233.0 234.1 233.9 247.9 208.7
75 223.7 210.5 246.5 155.4 260.3 95.4 216.5 207.3 237.3 151.9 248.8 91.5
80 224.1 224.0 246.6 200.4 260.5 140.9 217.8 217.8 237.4 196.8 249.1 137.1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
236.2 125.8
236.6 165.5
236.8 204.9
227.8 148.2 236.9 87.5
228.0 193.2 237.3 133.1
8000
9000
10000
85 236.1 236.1 246.2 243.9 260.9 186.2 229.4 229.4 237.1 236.4 249.6 182.4
90 247.4 247.4 247.6 247.6 260.9 231.2 239.5 239.5 239.7 239.7 249.6 227.3
75 226.8 224.9 249.1 164.3 261.8 97.2 219.3 218.6 239.4 160.7 249.9 93.3
80 230.0 230.0 249.1 214.9 262.2 148.5 223.5 223.5 239.5 211.2 250.3 144.6
85 242.4 242.4 248.5 248.1 262.5 199.5 234.9 234.9 238.9 238.5 250.7 195.6
-
-
-
-
-
-
-
-
-
-
227.6 227.1 238.0 178.6
231.1 231.1 238.0 223.4
229.5 156.9
229.6 207.4
229.1 228.7
-
-
-
-
-
-
90 252.9 252.9 253.0 253.0 262.4 249.9 243.8 243.8 243.9 243.9 251.0 246.1
233.9 233.9
75 229.3 228.7 251.0 173.2 263.2 99.2 221.2 220.7 241.0 169.4 250.7 95.1 213.2 212.8 230.8 165.7
80 235.2 235.2 250.9 229.2 263.6 156.2 228.2 228.2 240.9 225.5 251.4 152.2 220.9 220.9 230.7 221.7
85 247.3 247.3 250.1 249.6 263.9 212.8 239.1 239.1 240.3 240.0 251.7 208.8 230.3 230.3 230.4 230.4
90 256.6 256.6 256.7 256.7 263.7 262.7 246.2 246.2 246.3 246.3 251.6 250.6 236.1 236.1 236.2 236.2
-
-
-
-
-
-
-
-
-
-
11000
75 230.8 230.4 252.4 182.0 264.0 101.1 222.7 222.3 242.1 178.2 251.2 97.0 214.6 214.1
80 239.4 239.4 252.2 243.6 264.7 163.8 232.0 232.0 242.0 238.9 252.1 159.8 224.1 224.1
85 251.0 251.0 251.7 251.3 264.9 226.1 242.1 242.1 242.2 242.2 252.4 222.0 232.5 232.5
90 258.7 258.7 258.8 258.8 264.6 263.8 248.7 248.7 248.8 248.8 252.1 251.4 237.7 237.7
-
-
-
-
-
-
-
-
-
-
-
-
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Stands for both downflow and horizontal unit.
-
-
-
-
46 RT-PRC028AC-EN
Performance Data
Table 23. Gross cooling capacities 25 tons three phase standard efficiency T/YS*301G3,4,W
Air
Flow cfm
7000
8000
9000
Ambient Temperature
Ent
DB
(°F)
85 95
Entering Wet Bulb
105
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 257.6 212.0 289.0 165.3 317.0 114.6 245.8 206.5 274.9 159.4 299.4 108.2 233.1 200.6 259.5 153.1 279.6 101.1
80 257.0 250.5 288.9 204.5 317.1 154.5 245.3 244.2 274.8 198.7 299.5 148.1 232.7 232.3 259.5 192.4 279.8 141.0
85 259.2 259.1 288.8 243.6 317.2 194.2 249.7 249.7 274.6 237.7 299.7 187.7 239.4 239.4 259.2 231.3 280.1 180.7
90 273.4 273.4 287.9 282.0 317.2 233.5 263.5 263.5 274.1 273.6 299.8 227.1 252.3 252.3 258.7 258.4 280.4 220.2
75 264.4 228.7 295.5 175.0 321.8 116.8 251.7 223.0 280.5 168.9 302.9 110.1 238.0 216.8 264.2 162.4 281.8 102.7
80 263.5 263.0 295.4 219.8 322.0 162.4 250.9 250.6 280.4 213.7 303.1 155.7 237.6 237.4 264.1 207.3 282.0 148.3
85 270.1 270.1 295.0 264.3 322.1 207.6 259.9 259.9 279.9 258.2 303.4 201.0 248.6 248.6 263.6 251.6 282.5 193.7
90 285.1 285.1 294.2 293.7 322.2 252.7 274.1 274.1 279.3 279.0 303.6 246.1 261.6 261.6 263.6 263.4 282.7 238.7
75 269.4 245.0 300.5 184.4 325.2 118.8 256.0 239.1 284.8 178.2 305.1 111.8 241.7 232.8 267.6 171.5 284.3 104.8
80 268.4 268.1 300.4 234.8 325.4 170.0 255.7 255.5 284.7 228.6 305.4 163.1 242.3 242.1 267.6 222.1 284.5 156.0
85 279.4 279.4 299.7 284.7 325.7 221.0 268.4 268.4 283.9 278.5 305.9 214.1 256.1 256.1 267.0 266.2 284.7 206.9
10000
11000
Air
Flow cfm
7000
90 294.7 294.7 299.1 298.8 325.8 271.6 282.6 282.6 284.2 284.0 306.1 264.8 268.8 268.8 269.0 269.0 284.4 257.6
75 273.3 261.1 304.4 193.6 327.7 120.8 259.5 255.0 288.0 187.3 307.8 114.0 244.7 244.0 270.1 180.4 286.4 106.9
80 273.1 272.9 304.3 249.8 328.0 177.7 260.3 260.3 288.1 243.4 307.8 170.8 248.3 248.3 270.2 236.5 286.7 163.8
85 287.3 287.3 303.3 302.5 328.3 234.3 275.4 275.4 287.0 286.2 307.9 227.3 262.1 262.1 269.1 268.5 286.9 220.4
90 302.6 302.6 303.8 303.5 328.2 290.4 289.5 289.5 289.7 289.7 307.7 283.6 274.4 274.4 274.5 274.5 286.4 276.4
75 276.5 275.7 307.6 202.8 330.2 122.9 262.3 261.6 290.6 196.3 310.1 116.2 247.0 246.2 272.1 189.3 288.1 109.0
80 277.6 277.6 307.6 264.5 330.3 185.5 266.1 266.1 290.6 258.0 310.3 178.8 253.4 253.4 272.0 251.0 288.4 171.5
85 293.9 293.9 306.1 305.3 331.2 247.7 281.3 281.3 289.1 288.4 310.4 241.0 267.1 267.1 270.8 270.4 288.6 233.8
90 309.2 309.2 309.4 309.4 330.3 309.3 295.0 295.0 295.2 295.2 309.5 302.3 278.5 278.5 278.7 278.7 288.1 286.9
Ambient Temperature
Ent
DB
(°F)
115 120
Entering Wet Bulb
125
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 219.7 194.5 243.0 146.4 258.2 93.6 212.8 191.4 234.3 143.0 247.2 89.8
236.0 85.9
80 219.4 219.2 243.0 185.7 258.2 133.4 212.8 212.5 234.3 182.3 247.5 129.7
85 228.2 228.2 242.7 224.7 258.5 173.0 222.2 222.2 234.1 221.2 247.8 169.3
90 239.8 239.8 242.5 242.2 258.7 212.5 233.0 233.0 234.1 233.9 247.9 208.7
75 223.7 210.5 246.5 155.4 260.3 95.4 216.5 207.3 237.3 151.9 248.8 91.5
80 224.1 224.0 246.6 200.4 260.5 140.9 217.8 217.8 237.4 196.8 249.1 137.1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
236.2 125.8
236.6 165.5
236.8 204.9
227.8 148.2 236.9 87.5
228.0 193.2 237.3 133.1
8000
9000
10000
85 236.1 236.1 246.2 243.9 260.9 186.2 229.4 229.4 237.1 236.4 249.6 182.4
90 247.4 247.4 247.6 247.6 260.9 231.2 239.5 239.5 239.7 239.7 249.6 227.3
75 226.8 224.9 249.1 164.3 261.8 97.2 219.3 218.6 239.4 160.7 249.9 93.3
80 230.0 230.0 249.1 214.9 262.2 148.5 223.5 223.5 239.5 211.2 250.3 144.6
85 242.4 242.4 248.5 248.1 262.5 199.5 234.9 234.9 238.9 238.5 250.7 195.6
-
-
-
-
-
-
-
-
-
-
227.6 227.1 238.0 178.6
231.1 231.1 238.0 223.4
229.5 156.9
229.6 207.4
229.1 228.7
-
-
-
-
-
-
90 252.9 252.9 253.0 253.0 262.4 249.9 243.8 243.8 243.9 243.9 251.0 246.1
233.9 233.9
75 229.3 228.7 251.0 173.2 263.2 99.2 221.2 220.7 241.0 169.4 250.7 95.1 213.2 212.8 230.8 165.7
80 235.2 235.2 250.9 229.2 263.6 156.2 228.2 228.2 240.9 225.5 251.4 152.2 220.9 220.9 230.7 221.7
85 247.3 247.3 250.1 249.6 263.9 212.8 239.1 239.1 240.3 240.0 251.7 208.8 230.3 230.3 230.4 230.4
90 256.6 256.6 256.7 256.7 263.7 262.7 246.2 246.2 246.3 246.3 251.6 250.6 236.1 236.1 236.2 236.2
-
-
-
-
-
-
-
-
-
-
11000
75 230.8 230.4 252.4 182.0 264.0 101.1 222.7 222.3 242.1 178.2 251.2 97.0 214.6 214.1
80 239.4 239.4 252.2 243.6 264.7 163.8 232.0 232.0 242.0 238.9 252.1 159.8 224.1 224.1
85 251.0 251.0 251.7 251.3 264.9 226.1 242.1 242.1 242.2 242.2 252.4 222.0 232.5 232.5
90 258.7 258.7 258.8 258.8 264.6 263.8 248.7 248.7 248.8 248.8 252.1 251.4 237.7 237.7
-
-
-
-
-
-
-
-
-
-
-
-
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Stands for both downflow and horizontal unit.
-
-
-
-
RT-PRC028AC-EN 47
Performance Data
Table 24. Gross cooling capacities 12½ tons three phase high efficiency T/YH*150G3,4,W (stage 1)
Air
Flow cfm
Ent
DB
(°F)
Ambient Temperature
85 95
Entering Wet Bulb
61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
2000
2500
3000
3500
4000
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
42.0 39.3 45.3 31.2 49.8 15.0 39.2 37.2 42.3 29.4 46.7 13.6
44.2 43.5 46.2 39.1 50.3 29.0 41.5 41.2 43.3 37.1 47.2 27.2
46.9 46.6 48.0 44.3 50.7 38.0 44.1 44.1 45.1 42.1 47.6 36.1
49.6 49.3 50.4 48.1 52.2 44.1 46.9 46.8 47.5 45.8 49.1 42.1
43.3 41.5 46.2 33.6 50.4 17.5 40.4 39.2 43.1 31.6 47.1 15.9
45.7 45.7 47.4 41.6 51.1 31.5 42.8 42.8 44.3 39.3 47.9 29.6
48.5 48.5 49.5 46.9 51.8 40.7 45.6 45.6 46.4 44.6 48.6 38.6
51.5 51.5 52.0 50.9 53.5 47.0 48.5 48.5 48.9 48.4 50.3 44.7
44.4 43.3 46.9 35.5 50.8 19.5 41.3 40.8 43.7 33.3 47.3 17.7
47.0 47.0 48.4 43.6 51.7 33.6 44.0 44.0 45.1 41.2 48.3 31.6
50.0 50.0 50.6 49.1 52.7 42.9 46.9 46.9 47.4 46.5 49.3 40.6
53.0 53.0 53.3 53.2 54.6 49.3 49.9 49.9 50.1 50.1 51.2 46.9
45.2 44.7 47.4 37.0 50.9 21.1 42.0 42.0 44.0 34.6 47.7 19.1
48.1 48.1 49.1 45.2 52.1 35.3 44.8 44.8 45.7 42.6 48.5 33.0
51.2 51.2 51.6 50.8 53.3 44.7 48.1 47.9 48.2 48.0 49.8 42.2
54.3 54.3 54.4 54.4 55.4 51.3 50.6 50.6 51.0 51.0 51.9 48.6
45.8 45.6 47.6 38.0 51.3 22.3 42.4 42.4 44.3 35.4 48.4 20.0
48.9 48.9 49.6 46.3 52.2 36.6 45.5 45.5 46.0 43.5 48.7 34.1
52.1 52.1 52.3 52.1 53.7 46.1 48.6 48.6 48.7 48.7 50.0 43.4
54.8 54.8 55.2 55.2 56.0 52.8 51.2 51.2 51.7 51.7 52.3 49.9
4375
75
80
85
90
46.1 46.0 47.6 38.5 51.9 22.8 42.6 42.6 44.6 35.8 48.7 20.5
49.3 49.3 49.8 46.9 52.4 37.2 45.8 45.8 46.1 43.9 48.9 34.6
52.3 52.3 52.6 52.6 53.9 46.8 48.8 48.8 49.0 49.0 50.3 44.0
55.2 55.2 55.7 55.7 56.3 53.6 52.0 52.0 52.1 52.1 52.5 50.6
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
48 RT-PRC028AC-EN
Performance Data
Table 25. Gross cooling capacities 12½ tons three phase high efficiency T/YH*150G3,4,W (stage 2)
Air
Flow cfm
Ent
DB
(°F)
Ambient Temperature
85 95
Entering Wet Bulb
61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
2000
2500
3000
3500
4000
75
80
85
90
87.1 69.1 97.7 56.8 108.4 33.8 83.2 66.7 92.6 54.8 102.7 32.4
88.4 76.3 98.3 68.1 110.1 52.4 84.5 73.5 93.8 65.7 104.8 50.5
91.0 81.9 99.1 76.1 110.6 65.0 87.1 78.9 94.7 73.5 105.5 62.7
94.6 86.6 101.5 82.3 111.0 73.9 90.6 83.5 97.0 79.4 106.0 71.4
75
80
92.4 75.4 101.4 62.0 112.8 37.9 88.1 72.7 96.9 59.7 105.9 36.2
94.3 83.2 103.5 74.1 114.0 57.5 90.1 80.3 98.7 71.6 109.8 55.3
85 97.5 89.5 105.0 83.0 115.8 71.0 93.3 86.3 100.2 80.1 110.4 68.5
90 101.5 94.7 107.9 89.7 116.8 80.7 97.3 91.3 103.2 86.6 111.5 77.9
75
80
96.8 80.9 107.7 66.4 114.3 41.2 92.3 78.0 102.4 64.0 113.2 39.3
99.4 89.5 107.8 79.5 118.5 61.9 94.9 86.3 102.7 76.7 114.1 59.5
85 103.1 96.3 110.0 89.1 120.1 76.2 98.6 92.9 105.0 86.0 114.4 73.5
90 107.6 102.0 113.5 96.4 121.8 86.7 103.1 98.4 108.5 93.1 116.2 83.7
75 100.3 85.7 110.4 70.2 120.2 43.8 95.6 82.5 104.8 67.5 115.7 41.7
80 103.6 95.0 111.4 84.2 123.3 65.5 98.9 91.6 106.0 81.1 117.2 62.9
85 107.9 102.4 114.2 94.5 123.6 80.8 103.2 98.8 108.9 91.1 117.7 77.8
90 112.9 108.7 118.3 102.4 126.0 92.0 108.1 104.9 112.9 98.9 120.1 88.7
75 103.1 89.8 112.3 73.3 121.4 45.7 98.0 86.4 106.5 70.4 116.8 43.3
80 107.0 99.8 114.1 88.1 125.2 68.5 102.0 96.2 108.4 84.9 118.8 65.7
85 111.9 107.9 117.5 99.1 126.3 84.6 106.9 104.0 112.0 95.6 120.0 81.5
90 117.4 114.6 122.2 107.7 129.3 96.5 112.3 110.6 116.6 103.9 123.2 93.1
4375
75 104.6 92.4 113.2 75.1 122.6 46.7 99.3 88.8 107.1 72.0 117.4 44.1
80 109.0 103.0 115.5 90.6 126.1 70.3 103.8 99.1 109.7 87.2 119.4 67.3
85 114.3 111.5 119.5 102.2 127.7 87.1 109.1 107.4 113.7 98.5 121.3 83.7
90 120.1 118.6 124.6 111.2 131.3 99.5 114.8 114.4 118.8 107.3 124.9 95.9
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
RT-PRC028AC-EN 49
Performance Data
Table 26. Gross cooling capacities 12½ tons three phase high efficiency T/YH*150G3,4,W (full load)
Air
Flow cfm
2500
3000
3500
4000
4500
5000
5500
6000
Ent
DB
(°F)
85
Ambient Temperature
95 105
Entering Wet Bulb
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 125.0 96.9 138.0 75.5 153.6 38.3 118.3 92.7 130.4 72.3 145.1 36.2 111.1 88.1 122.3 68.7 136.2 33.8
80 127.7 109.0 139.6 94.4 154.2 68.6 121.0 104.1 132.0 90.4 145.7 65.6 113.8 98.9 123.9 86.0 136.7 62.2
85 132.0 118.4 141.2 108.0 154.7 89.5 125.1 113.0 133.5 103.4 146.2 85.7 117.8 107.3 125.5 98.4 137.2 81.5
90 137.2 126.3 144.6 118.4 155.2 104.6 130.0 120.5 136.8 113.3 146.7 100.1 122.5 114.3 128.6 107.7 137.8 95.3
75 131.2 104.5 143.4 82.5 158.2 44.6 124.1 99.9 135.4 78.9 149.3 42.1 116.5 94.9 126.9 74.9 140.0 39.3
80 134.4 117.1 145.5 102.0 159.3 75.6 127.3 111.8 137.5 97.6 150.4 72.2 119.7 106.2 129.0 92.9 141.0 68.4
85 139.1 127.0 147.6 116.2 160.4 97.2 131.8 121.2 139.6 111.1 151.4 93.0 124.1 115.1 131.1 105.7 142.1 88.4
90 144.6 135.3 151.5 127.1 161.4 112.8 137.1 129.1 143.3 121.5 152.5 107.9 129.1 122.5 134.6 115.6 143.1 102.7
75 136.7 111.4 148.1 88.8 162.1 50.2 129.2 106.4 142.1 84.8 152.8 47.4 121.2 101.0 133.1 80.4 143.1 44.2
80 140.5 124.5 150.7 108.9 163.7 82.0 132.9 118.8 142.3 104.1 154.4 78.2 124.9 112.8 133.4 99.0 144.6 74.0
85 145.6 134.9 153.4 123.6 165.3 104.2 137.8 128.7 144.9 118.2 156.0 99.5 129.7 122.2 136.0 112.4 146.2 94.6
90 151.4 143.6 157.6 135.0 166.9 120.3 143.4 137.0 149.0 129.0 157.6 115.1 135.0 130.0 140.0 122.7 147.8 109.5
75 141.5 117.6 154.6 94.4 165.3 55.2 133.5 112.2 145.6 90.0 155.6 51.9 125.1 106.4 136.1 85.3 145.4 48.3
80 145.8 131.3 155.2 115.2 167.4 87.7 137.8 125.2 146.4 110.0 157.7 83.4 129.4 118.8 137.0 104.5 147.5 78.9
85 151.3 142.1 158.4 130.4 169.6 110.5 143.2 135.5 149.5 124.6 159.8 105.5 134.6 128.6 140.2 118.4 149.6 100.1
90 157.4 151.2 163.1 142.3 171.7 127.2 149.1 144.2 154.0 135.9 161.9 121.5 140.2 136.9 144.6 129.2 151.7 115.5
75 145.6 123.2 157.7 99.4 173.0 59.4 137.2 117.4 148.3 94.6 162.6 55.8 128.4 111.2 138.4 89.4 151.7 51.8
80 150.4 137.3 159.0 120.8 173.0 92.7 142.0 130.9 149.7 115.2 162.7 88.1 133.2 124.1 140.0 109.3 152.0 83.1
85 156.3 148.7 162.7 136.6 173.1 116.1 147.8 141.7 153.4 130.3 162.9 110.7 138.8 134.4 143.7 123.7 152.3 105.0
90 162.8 158.2 167.8 148.9 175.8 133.4 154.0 150.8 158.4 142.1 165.6 127.3 144.7 143.1 148.5 135.0 155.0 120.9
75 149.0 128.0 160.1 103.7 174.5 63.1 140.2 121.8 150.2 98.5 163.6 59.0 130.9 115.3 139.9 92.9 152.3 54.6
80 154.3 142.8 162.1 125.7 175.2 97.0 145.5 135.9 152.4 119.7 164.5 92.0 136.2 128.7 142.2 113.4 153.3 86.7
85 160.6 154.5 166.3 142.0 175.9 121.1 151.6 147.2 156.6 135.4 165.3 115.3 142.2 139.5 146.5 128.4 154.3 109.1
90 167.4 164.5 171.8 154.8 179.1 138.9 158.2 156.7 162.0 147.6 168.5 132.4 148.5 148.5 151.7 140.1 157.5 125.6
75 151.6 132.3 161.8 107.3 175.2 66.0 142.4 125.7 151.5 101.7 164.0 61.5 132.7 118.7 140.8 95.8 152.8 56.8
80 157.5 147.5 164.5 129.9 176.6 100.7 148.2 140.3 154.3 123.6 165.5 95.3 138.6 132.7 143.8 116.8 153.9 89.5
85 164.2 159.7 169.2 146.8 178.0 125.4 154.8 152.0 159.1 139.8 167.0 119.2 145.0 143.9 148.5 132.4 155.6 112.6
90 171.3 170.1 175.1 160.0 181.8 143.7 161.7 161.7 164.9 152.5 170.7 136.9 151.6 151.6 154.2 144.6 159.3 129.7
75 153.6 135.8 162.8 110.2 175.3 68.2 143.9 128.8 152.1 104.2 164.5 63.4 133.8 121.5 140.9 97.9 153.2 58.2
80 160.0 151.6 166.1 133.5 177.4 103.7 150.3 144.0 155.6 126.7 165.8 97.9 140.2 136.0 144.6 119.6 154.5 91.7
85 167.1 164.3 171.4 150.9 179.4 129.0 157.3 156.1 160.9 143.5 168.0 122.4 147.0 147.0 149.9 135.7 156.2 115.5
90 174.5 174.5 177.7 164.6 183.7 147.9 164.4 164.4 167.1 156.7 172.3 140.6 154.0 154.0 155.9 148.4 160.4 133.1
50 RT-PRC028AC-EN
Performance Data
Table 26. Gross cooling capacities 12½ tons three phase high efficiency T/YH*150G3,4,W (full load)
Air
Flow cfm
2500
Ent
DB
(°F)
115
Ambient Temperature
120 125
61 67 73 61
Entering Wet Bulb
67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 103.5 83.2 113.8 64.9 126.9 31.1 99.5 80.7 109.4 62.8 122.0 29.6 95.5 78.0 104.9 60.6 117.0 28.0
80 106.2 93.3 115.4 81.4 127.4 58.5 102.2 90.4 110.9 78.9 122.5 56.5 98.1 87.5 106.4 76.4 117.5 54.4
85 110.0 101.2 116.9 93.0 127.9 77.0 105.9 98.1 112.5 90.3 123.0 74.7 101.8 94.8 107.9 87.4 118.0 72.2
90 114.5 107.9 119.9 101.9 128.4 90.2 110.3 104.5 115.4 98.8 123.5 87.5 106.0 101.1 110.8 95.7 118.5 84.7
75 108.5 89.6 118.0 70.6 130.2 36.2 104.3 86.8 113.3 68.4 125.1 34.5 100.0 84.0 108.6 66.0 120.0 32.7
3000
3500
4000
4500
5000
80 111.7 100.3 120.0 87.8 131.2 64.3 107.5 97.2 115.4 85.1 126.2 62.1 103.2 94.0 110.7 82.4 121.0 59.9
85 115.9 108.6 122.1 100.0 132.3 83.5 111.6 105.3 117.5 97.0 127.2 80.9 107.3 101.8 112.7 94.0 122.0 78.3
90 120.7 115.7 125.5 109.3 133.3 97.2 116.3 112.1 120.8 106.1 128.2 94.3 111.8 108.5 116.0 102.7 123.1 91.3
75 112.7 95.3 123.6 75.8 132.9 40.6 108.3 92.4 118.7 73.3 127.6 38.7 103.8 89.3 113.7 70.8 122.2 36.8
80 116.4 106.5 124.0 93.5 134.4 69.5 112.0 103.2 119.2 90.7 129.1 67.1 107.5 99.8 114.2 87.7 123.8 64.7
85 121.1 115.3 126.6 106.3 136.0 89.3 116.6 111.8 121.8 103.1 130.7 86.5 112.0 108.2 116.8 99.8 125.3 83.7
90 126.2 122.8 130.5 116.1 137.6 103.5 121.6 119.0 125.5 112.6 132.3 100.4 116.9 115.2 120.5 109.1 126.9 97.3
75 116.3 100.4 126.2 80.2 134.8 44.4 111.7 97.2 121.0 77.5 129.3 42.3 107.0 94.0 115.8 74.8 123.7 40.1
80 120.5 112.1 127.3 98.6 136.9 74.0 115.9 108.6 122.2 95.5 131.4 71.4 111.2 105.0 117.1 92.4 125.8 68.8
85 125.6 121.4 130.4 111.9 139.0 94.4 120.9 117.6 125.4 108.5 133.5 91.5 116.1 113.8 120.2 105.1 127.9 88.4
90 131.0 129.2 134.7 122.1 141.1 109.2 126.2 125.3 129.5 118.5 135.6 105.9 121.3 121.2 124.3 114.8 130.0 102.5
75 119.1 104.7 128.0 84.0 140.3 47.5 114.3 101.4 122.7 81.1 134.5 45.2 109.4 97.9 117.3 78.2 128.6 42.8
80 123.9 117.0 129.8 103.0 140.8 77.8 119.0 113.3 124.5 99.7 135.0 75.1 114.1 109.6 119.2 96.4 129.2 72.2
85 129.3 126.7 133.5 116.8 141.3 98.9 124.4 122.8 128.2 113.3 135.6 95.7 119.4 118.8 122.8 109.6 129.8 92.5
90 135.1 135.0 138.1 127.6 143.9 114.2 130.0 130.0 132.8 123.7 138.2 110.7 124.9 124.9 127.4 119.8 132.4 107.1
75 121.2 108.4 129.2 87.1 140.6 49.9 116.2 104.9 123.6 84.0 134.5 47.4 111.1 101.2 118.0 80.9 129.0 44.9
80 126.5 121.2 131.6 106.7 141.7 81.0 121.5 117.4 126.2 103.3 135.7 78.0 116.4 113.4 120.6 99.7 129.6 75.0
85 132.4 131.4 135.8 121.1 142.8 102.7 127.3 127.3 130.4 117.3 136.9 99.3 122.1 122.1 124.8 113.5 130.9 95.9
90 138.4 138.4 140.9 132.3 146.0 118.5 133.2 133.2 135.4 128.3 140.1 114.8 127.9 127.9 129.7 124.1 134.1 111.1
75 122.6 111.5 129.6 89.5 141.0 51.7 117.4 107.7 123.9 86.3 134.8 49.0 112.1 103.9 118.0 82.9 130.0 46.2
5500
80 128.4 124.8 132.7 109.8 141.9 83.5 123.2 120.7 127.1 106.1 136.2 80.3 117.9 116.6 121.3 102.4 130.7 77.1
85 134.7 134.7 137.5 124.7 143.7 105.8 129.4 129.4 131.8 120.7 137.6 102.2 124.0 124.0 126.0 116.7 131.4 98.6
90 141.1 141.1 143.0 136.4 147.4 122.2 135.7 135.7 137.2 132.1 141.3 118.3 130.1 130.1 131.4 127.8 135.1 114.3
75 123.3 113.8 130.0 91.3 142.0 52.7 117.9 109.9 125.0 87.8 135.3 49.9 112.3 105.8 119.0 84.3 130.2 46.9
6000
80 129.7 127.7 133.2 112.2 143.0 85.3 124.2 123.4 127.3 108.3 137.0 81.9 118.7 118.7 124.0 104.4 131.6 78.5
85 136.4 136.4 138.4 127.6 143.8 108.2 130.8 130.8 132.5 123.5 139.0 104.5 125.2 125.2 126.5 119.2 133.0 100.6
90 143.0 143.0 144.3 139.8 148.1 125.2 137.4 137.4 138.4 135.3 141.8 121.1 131.6 131.6 132.3 130.8 135.3 116.9
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
RT-PRC028AC-EN 51
Performance Data
Table 27. Gross cooling capacities 12½ tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD150G3,4,W (Digit 22 = B)
Air
Flow cfm
2500 (a)
3250
4000
4500
5000
5500
6000
Ent
DB
(°F)
85
Ambient Temperature
95 105
61 67 73 61
Entering Wet Bulb
67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 119.6 86.9 135.0 60.0 154.5 54.1 112.4 82.4 127.1 56.5 145.9 51.1 104.7 77.6 118.6 52.7 136.8 47.9
80 121.1 102.6 134.0 82.6 151.3 52.9 114.0 97.4 126.2 78.4 142.8 50.0 106.3 92.0 117.9 74.0 133.7 46.8
85 123.7 114.7 134.3 101.6 149.2 75.1 116.7 108.9 126.6 96.8 140.8 71.4 109.2 102.8 118.4 91.7 131.9 67.4
90 127.5 123.2 135.8 116.9 148.3 97.4 120.6 116.7 128.2 111.5 140.0 93.0 113.2 110.0 120.1 105.8 131.2 88.4
75 129.1 96.7 143.2 68.4 161.5 56.5 121.5 91.9 134.9 64.6 152.5 53.4 113.3 86.8 126.0 60.5 142.9 50.0
80 131.4 113.6 143.2 92.1 159.1 57.4 123.9 108.1 134.9 87.7 150.2 54.0 115.8 102.4 126.1 83.0 140.7 50.4
85 134.9 126.9 144.3 112.3 157.9 84.4 127.5 120.8 136.2 107.2 149.1 80.4 119.5 114.4 127.5 101.9 139.7 76.2
90 139.7 136.5 146.7 128.8 157.9 107.9 132.3 129.8 138.6 123.1 149.2 103.2 124.4 122.8 130.0 117.2 139.9 98.3
75 137.1 105.6 149.9 75.8 167.0 58.4 129.0 100.4 141.1 71.7 157.4 55.1 120.3 95.0 131.7 67.4 147.4 51.6
80 140.2 123.6 150.7 100.7 165.4 64.5 132.2 117.8 142.0 96.0 156.0 60.9 123.7 111.8 132.7 91.0 146.1 57.0
85 144.6 138.0 152.7 122.0 165.1 92.7 136.7 131.6 144.1 116.7 155.8 88.5 128.3 124.9 135.0 111.1 145.9 83.9
90 150.2 148.8 156.0 139.7 166.0 117.4 142.4 141.8 147.5 133.7 156.8 112.4 134.0 134.0 138.4 127.5 147.0 107.2
75 141.5 110.9 153.5 80.1 169.7 59.4 133.1 105.5 144.3 75.9 159.9 56.0 124.1 100.0 134.7 71.3 149.5 52.3
80 145.2 129.7 154.9 105.8 168.8 68.7 136.9 123.7 145.8 100.9 159.0 64.9 128.1 117.5 136.3 95.8 148.8 60.8
85 150.2 144.9 157.5 127.9 169.0 97.7 142.0 138.3 148.6 122.4 159.4 93.2 133.2 131.4 139.1 116.6 149.2 88.5
90 156.3 156.3 161.3 146.4 170.5 123.1 148.2 148.2 152.5 140.3 161.0 118.0 139.6 139.6 143.1 133.8 150.9 112.6
75 145.2 115.7 156.3 84.0 171.8 60.1 136.5 110.2 146.9 79.6 161.6 56.6 127.2 104.5 137.0 74.9 151.0 52.8
80 149.5 135.3 158.3 110.5 171.4 72.5 140.9 129.2 149.0 105.4 161.4 68.4 131.7 122.8 139.1 100.1 150.8 64.2
85 155.0 151.3 161.5 133.4 172.2 102.3 146.5 144.5 152.3 127.7 162.3 97.6 137.5 137.5 142.5 121.7 151.8 92.7
90 161.8 161.8 165.9 152.7 174.3 128.4 153.4 153.4 156.8 146.3 164.4 123.1 144.4 144.4 147.1 139.7 154.1 117.6
75 148.2 120.1 158.5 87.5 173.1 60.6 139.2 114.4 148.8 82.9 162.7 56.9 129.6 108.5 138.5 78.0 151.7 53.1
80 153.1 140.5 161.1 114.8 173.3 75.8 144.2 134.2 151.4 109.5 163.0 71.6 134.7 127.6 141.3 104.0 152.1 67.1
85 159.2 157.2 164.8 138.4 174.7 106.3 150.4 150.3 155.3 132.5 164.5 101.5 141.0 141.0 145.3 126.3 153.7 96.4
90 166.5 166.5 169.8 158.5 177.3 133.3 157.8 157.8 160.4 151.9 167.2 127.8 148.6 148.6 150.4 145.1 156.6 122.0
75 150.5 124.1 160.0 90.5 173.7 60.8 141.2 118.2 150.0 85.7 163.0 57.1 131.3 112.1 139.4 80.6 151.7 53.1
80 156.0 145.2 163.1 118.6 174.5 78.6 146.8 138.7 153.2 113.1 163.9 74.2 137.0 131.9 142.7 107.4 152.7 69.6
85 162.7 162.7 167.5 143.0 176.5 110.0 153.6 153.6 157.6 136.9 166.0 104.9 143.9 143.9 147.3 130.5 154.9 99.6
90 170.6 170.6 173.0 163.8 179.7 137.7 161.5 161.5 163.3 157.1 169.3 132.0 152.0 152.0 153.0 150.1 158.3 126.1
52 RT-PRC028AC-EN
Performance Data
Table 27. Gross cooling capacities 12½ tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD150G3,4,W (Digit 22 = B)
Air
Flow cfm
Ent
DB
(°F)
115
Ambient Temperature
120 125
61 67 73 61
Entering Wet Bulb
67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 96.4 72.5 109.7 48.7 127.1 44.5 92.1 69.8 105.0 46.6 122.1 42.7 87.7 67.2 100.2 44.4 116.9 40.9
2500
3250
4000
4500
80 98.2 86.3 109.0 69.4 124.1 43.5 93.9 83.3 104.4 66.9 119.2 41.7 89.5 80.3 99.6 64.4 114.0 39.9
85 101.1 96.4 109.6 86.4 122.4 63.2 96.9 93.2 105.0 83.7 117.5 60.9 92.5 89.8 100.3 80.9 112.4 58.7
90 105.3 103.0 111.4 99.9 121.8 83.5 101.1 99.4 106.9 96.9 116.9 81.0 96.8 95.8 102.2 93.7 111.9 78.4
75 104.6 81.4 116.5 56.2 132.7 46.5 100.0 78.7 111.6 54.0 127.5 44.6 95.3 75.8 106.6 51.7 122.1 42.7
80 107.2 96.4 116.8 78.1 130.7 46.5 102.7 93.3 111.9 75.5 125.4 44.5 98.0 90.2 106.9 72.9 120.1 42.3
85 111.0 107.7 118.3 96.3 129.8 71.6 106.5 104.3 113.4 93.4 124.6 69.3 101.9 100.9 108.5 90.5 119.3 66.9
90 116.0 115.5 120.9 111.0 130.1 93.2 111.6 111.6 116.2 107.8 125.0 90.5 107.1 107.1 111.3 104.5 119.7 87.8
75 111.1 89.4 121.8 62.8 136.8 47.9 106.3 86.5 116.7 60.4 131.3 46.0 101.4 83.5 111.4 57.9 125.7 44.0
80 114.6 105.5 123.0 85.8 135.6 52.8 109.9 102.3 117.9 83.1 130.1 50.6 105.0 99.0 112.7 80.3 124.6 48.4
85 119.3 118.0 125.3 105.2 135.6 79.1 114.6 114.5 120.3 102.2 130.2 76.6 109.8 109.8 115.1 99.1 124.7 74.0
90 125.2 125.2 128.8 121.0 136.7 101.8 120.5 120.5 123.8 117.7 131.4 99.0 115.8 115.8 118.7 114.3 125.9 96.1
75 114.6 94.1 124.5 66.6 138.6 48.5 109.7 91.1 119.2 64.1 133.0 46.5 104.6 88.1 113.8 61.5 127.2 44.5
80 118.7 111.0 126.2 90.4 138.0 56.4 113.8 107.7 121.0 87.6 132.4 54.2 108.8 104.3 115.6 84.7 126.7 51.8
85 123.9 123.9 129.1 110.6 138.6 83.5 119.1 119.1 123.9 107.4 133.0 80.9 114.1 114.1 118.6 104.3 127.3 78.3
90 130.4 130.4 133.2 127.1 140.3 107.0 125.6 125.6 128.1 123.7 134.8 104.1 120.7 120.7 122.8 120.2 129.2 101.1
75 117.4 98.4 126.5 69.9 139.8 48.9 112.3 95.3 121.0 67.4 134.0 46.9 107.1 92.2 115.4 64.7 128.0 44.8
5000
5500
80 122.1 116.1 128.8 94.5 139.7 59.6 117.0 112.7 123.4 91.6 134.0 57.2 111.8 109.2 117.8 88.6 128.1 54.8
85 127.9 127.9 132.2 115.5 140.8 87.5 122.9 122.9 126.9 112.3 135.1 84.8 117.8 117.8 121.4 109.0 129.3 82.0
90 134.9 134.9 136.9 132.8 143.2 111.7 130.0 130.0 131.6 129.3 137.5 108.7 125.0 125.0 126.2 125.7 131.8 105.7
75 119.5 102.3 127.7 72.8 140.2 49.1 114.3 99.1 122.1 70.2 134.2 47.0 108.9 95.8 116.4 67.4 128.2 44.9
80 124.7 120.7 130.6 98.2 140.7 62.3 119.5 117.2 125.0 95.2 134.8 59.9 114.2 113.6 119.4 92.1 128.8 57.4
85 131.1 131.1 134.7 119.9 142.4 91.0 126.0 126.0 129.2 116.6 136.6 88.2 120.7 120.7 123.5 113.2 130.6 85.4
90 138.5 138.5 139.9 138.1 145.4 116.0 133.1 133.1 134.5 134.4 139.6 112.9 128.9 128.9 128.9 128.9 133.6 109.8
75 120.9 105.7 128.3 75.3 139.9 49.0 115.5 102.4 122.5 72.5 133.8 46.8 110.0 99.0 116.7 69.7 127.6 44.7
6000
80 126.7 124.9 131.7 101.4 141.0 64.6 121.4 121.3 126.0 98.3 135.0 62.1 115.9 115.9 120.2 95.2 128.8 59.5
85 133.7 133.7 136.4 123.9 143.3 94.1 128.4 128.4 130.7 120.5 137.3 91.2 123.0 123.0 125.0 117.1 131.2 88.2
90 142.2 142.2 142.2 142.2 146.8 119.9 136.6 136.6 136.6 136.6 140.9 116.7 130.9 130.9 130.9 130.9 134.8 113.4
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
(a)For 2500 and 3250 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Dehumidification (Hot Gas Reheat) with Frostat and Crankcage heaters are required on applications below 320 cfm/ton.
- Multi-speed or single zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC028AC-EN 53
Performance Data
Table 28. Gross cooling capacities 15 tons three phase high efficiency T/YH*180G3,4,W (stage 1)
Air
Flow cfm
Ent
DB
(°F)
Ambient Temperature
85 95
Entering Wet Bulb
61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
2400
3000
3600
4200
4800
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
54.8 51.5 59.2 40.6 65.3 18.6 51.8 49.1 56.0 38.5 60.9 17.0
57.4 56.8 60.0 50.8 65.5 37.2 54.3 54.2 56.8 48.5 62.1 35.2
60.3 60.3 61.9 57.4 65.5 48.8 57.1 57.1 58.6 54.8 62.1 46.6
63.3 63.3 64.3 61.8 66.8 56.5 60.1 60.1 61.0 59.1 63.3 54.1
56.6 54.6 60.5 44.0 66.3 22.4 53.4 52.0 57.1 41.7 61.6 20.5
59.5 59.5 61.7 54.3 66.7 40.9 56.2 56.2 58.2 51.8 63.1 38.7
62.6 62.6 63.8 60.9 67.1 52.6 59.3 59.3 60.4 58.2 63.4 50.2
65.7 65.7 66.4 65.5 68.6 60.4 62.3 62.3 62.9 62.6 64.9 57.7
58.1 57.2 61.5 46.8 66.9 25.5 54.7 54.3 57.9 44.3 62.0 23.4
61.2 61.2 63.0 57.2 67.5 44.0 57.8 57.8 59.4 54.4 63.8 41.6
64.5 64.5 65.4 63.9 68.2 55.8 61.0 61.0 61.8 60.9 64.4 53.1
67.9 67.9 68.3 68.3 70.0 63.7 64.3 64.3 64.6 64.6 66.2 60.7
59.3 59.1 62.2 49.1 67.0 28.1 55.7 55.7 58.4 46.3 62.1 25.7
62.6 62.6 64.0 59.5 68.1 46.6 59.0 59.0 60.2 56.4 64.1 43.9
66.2 66.2 66.7 66.3 69.1 58.4 62.5 62.5 62.9 62.9 65.1 55.5
69.7 69.7 69.7 69.7 71.2 66.3 64.6 64.6 65.9 65.9 67.2 63.2
60.1 60.1 62.5 50.7 67.1 30.0 56.4 56.4 58.6 47.7 62.7 27.4
63.7 63.7 64.7 61.1 68.3 48.5 59.9 59.9 60.7 57.9 64.1 45.6
67.5 67.5 67.6 67.6 69.6 60.4 63.6 63.6 63.6 63.6 65.5 57.3
69.8 69.8 70.9 70.9 72.0 68.5 65.9 65.9 66.8 66.8 67.8 65.1
5250
75
80
85
90
60.5 60.5 62.5 51.6 67.2 31.1 56.6 56.6 58.8 48.4 63.0 28.4
64.3 64.3 65.0 62.0 68.5 49.6 60.4 60.4 60.9 58.6 64.1 46.5
67.8 67.8 68.1 68.1 69.8 61.6 63.8 63.8 64.0 64.0 65.5 58.2
70.7 70.7 71.5 71.5 72.4 69.6 66.7 66.7 67.4 67.4 68.0 66.1
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
54 RT-PRC028AC-EN
Performance Data
Table 29. Gross cooling capacities 15 tons three phase high efficiency T/YH*180G3,4,W (stage 2)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
2400
3000
3600
4200
4800
75 102.0 81.9 111.7 65.6 123.0 36.1 96.8 78.4 105.8 62.6 116.0 33.6
80 104.0 90.7 113.0 79.9 123.8 59.7 98.9 86.9 107.3 76.5 117.7 56.7
85 107.1 97.4 114.3 89.8 124.6 75.5 102.0 93.4 108.8 86.1 118.5 72.1
90 111.0 102.8 117.0 97.1 125.4 86.5 105.8 98.6 111.5 93.2 119.3 82.9
75 107.2 88.8 117.9 71.7 126.6 41.1 101.7 85.0 111.7 68.3 120.0 38.3
80 109.8 98.2 118.0 86.6 128.0 65.6 104.4 94.1 112.0 82.9 121.5 62.3
85 113.4 105.4 120.0 97.2 129.4 82.2 108.0 101.1 114.1 93.2 123.0 78.5
90 117.8 111.3 123.2 105.1 130.8 93.9 112.3 106.7 117.3 100.8 124.5 89.9
75 111.5 94.8 121.2 76.7 133.1 45.2 105.7 90.6 114.7 73.0 125.9 42.1
80 114.7 104.8 122.0 92.5 133.2 70.6 109.0 100.4 115.7 88.4 126.2 67.0
85 118.9 112.5 124.7 103.7 133.3 87.9 113.2 107.9 118.5 99.3 126.5 84.0
90 123.7 118.9 128.4 112.1 135.3 100.3 117.8 114.0 122.2 107.5 128.7 96.0
75 114.9 99.8 123.6 80.9 134.5 48.4 108.8 95.3 116.8 76.9 127.0 44.9
80 118.8 110.4 125.2 97.4 135.4 74.7 112.7 105.7 118.6 93.0 128.1 70.7
85 123.5 118.7 128.5 109.2 136.3 92.8 117.4 113.7 122.0 104.6 129.2 88.5
90 128.6 125.5 132.8 118.2 139.0 105.7 122.5 120.3 126.3 113.2 132.0 101.1
75 117.4 103.9 125.1 84.1 135.0 50.6 111.0 99.1 117.9 79.7 128.0 46.8
80 121.9 115.2 127.5 101.4 136.7 77.8 115.6 110.1 120.6 96.7 129.1 73.5
85 127.1 123.9 131.5 113.9 138.4 96.7 120.8 118.6 124.6 108.8 131.0 92.0
90 132.7 131.1 136.3 123.3 141.8 110.3 126.3 125.6 129.4 118.1 134.5 105.3
5250
75 118.7 106.3 125.6 85.9 135.5 51.7 112.0 101.3 118.2 81.3 129.0 47.6
80 123.7 118.1 128.7 103.7 137.1 79.5 117.1 112.7 121.5 98.8 129.3 75.0
85 129.3 127.3 133.1 116.7 139.4 99.0 122.7 121.7 126.0 111.4 131.8 94.1
90 135.2 134.8 138.3 126.6 143.3 113.0 128.5 128.5 131.2 121.1 135.7 107.9
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 2400, 3000, 3600, and 4200 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC028AC-EN 55
Performance Data
Table 30. Gross cooling capacities 15 tons three phase high efficiency T/YH*180G3,4,W (full load)
Air
Flow cfm (a)
3000
3600
4200
4800
5400
6000
6600
7200
Ent
DB
(°F)
85
Ambient Temperature
95 105
Entering Wet Bulb
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 149.8 116.6 163.9 91.6 180.9 48.7 142.5 112.1 155.7 88.3 172.0 46.6 134.3 106.9 146.7 84.2 162.1 43.8
80 153.0 130.6 165.9 113.6 181.8 83.7 145.7 125.4 157.8 109.4 172.9 80.6 137.5 119.5 148.7 104.5 163.1 76.8
85 157.9 141.6 167.9 129.4 182.8 108.0 150.5 135.8 159.8 124.5 173.8 104.0 142.2 129.4 150.8 118.9 164.0 99.3
90 163.8 150.7 171.9 141.5 183.7 125.5 156.2 144.5 163.7 136.0 174.7 120.8 147.7 137.7 154.6 129.9 164.9 115.5
75 156.6 125.2 169.8 99.5 186.1 55.7 148.9 120.2 161.3 95.7 176.7 53.2 140.3 114.6 151.8 91.2 166.5 50.1
80 160.4 139.8 172.4 122.2 187.5 91.6 152.7 134.2 163.9 117.5 178.2 88.1 144.1 127.9 154.4 112.2 168.0 83.9
85 165.7 151.3 175.0 138.6 189.0 116.6 157.9 145.1 166.5 133.2 179.7 112.2 149.2 138.3 157.0 127.2 169.4 107.1
90 172.0 160.9 179.5 151.2 190.5 134.7 163.9 154.2 170.8 145.3 181.2 129.6 155.0 147.0 161.3 138.7 170.9 123.8
75 162.6 133.0 177.9 106.6 190.4 62.0 154.5 127.6 168.8 102.4 180.7 59.1 145.5 121.6 158.9 97.5 170.0 55.5
80 166.9 148.2 178.1 129.9 192.5 98.7 158.8 142.1 169.2 124.9 182.7 94.8 149.8 135.4 159.4 119.1 172.1 90.1
85 172.7 160.2 181.3 147.0 194.5 124.4 164.5 153.6 172.3 141.2 184.8 119.5 155.4 146.3 162.5 134.8 174.1 114.1
90 179.3 170.2 186.2 160.1 196.6 143.1 170.9 163.1 177.2 153.8 186.8 137.6 161.6 155.5 167.2 146.8 176.2 131.4
75 167.9 139.9 182.2 112.8 194.0 67.4 159.3 134.2 172.7 108.2 183.8 64.1 149.9 127.7 162.3 102.9 172.8 60.2
80 172.7 155.7 183.1 136.9 196.6 105.0 164.2 149.3 173.7 131.4 186.5 100.6 154.8 142.2 163.5 125.3 175.4 95.6
85 179.0 168.2 186.8 154.5 199.2 131.4 170.3 161.2 177.5 148.4 189.1 126.1 160.8 153.6 167.2 141.5 178.0 120.2
90 185.9 178.7 192.2 168.2 201.9 150.7 177.1 171.3 182.7 161.4 191.7 144.7 167.3 163.2 172.4 154.0 180.7 138.2
75 172.3 146.1 185.6 118.3 202.7 72.1 163.4 139.9 175.7 113.3 191.8 68.4 153.6 133.1 164.9 107.6 180.1 64.0
80 177.8 162.5 187.3 143.1 202.9 110.5 168.8 155.6 177.5 137.2 192.2 105.7 159.0 148.1 166.9 130.6 180.6 100.3
85 184.4 175.5 191.6 161.3 203.2 137.6 175.4 168.1 181.8 154.7 192.6 131.9 165.5 160.0 171.2 147.5 181.2 125.6
90 191.7 186.4 197.4 175.5 206.4 157.5 182.5 178.6 187.5 168.3 195.8 151.1 172.3 170.1 176.8 160.5 184.4 144.1
75 176.0 151.5 188.3 123.0 204.4 76.0 166.7 144.9 178.0 117.5 193.1 71.9 156.5 137.6 166.8 111.4 181.0 67.1
80 182.0 168.5 190.7 148.5 205.4 115.2 172.7 161.2 180.5 142.2 194.3 110.0 162.5 153.3 169.5 135.2 182.3 104.1
85 189.1 182.0 195.5 167.3 206.3 143.0 179.7 174.2 185.4 160.3 195.4 136.9 169.3 165.7 174.3 152.6 183.5 130.2
90 196.8 193.3 201.8 181.9 210.1 163.5 187.1 185.1 191.5 174.4 199.1 156.7 176.6 176.2 180.4 166.2 187.3 149.3
75 178.9 156.1 190.2 126.9 205.4 79.1 169.2 149.1 179.5 121.0 193.7 74.5 158.6 141.4 167.9 114.5 181.2 69.3
80 185.5 173.7 193.3 153.1 207.0 119.1 175.7 166.0 182.7 146.3 195.5 113.5 165.1 157.6 171.3 139.0 183.1 107.2
85 193.0 187.7 198.7 172.5 208.7 147.6 183.2 179.5 188.2 165.1 197.3 141.1 172.4 170.6 176.7 157.0 185.1 134.0
90 201.0 199.5 205.5 187.6 213.0 168.7 190.9 190.8 194.8 179.7 201.7 161.5 180.0 180.0 183.2 171.1 189.4 153.7
75 181.0 159.9 191.4 130.0 205.6 81.4 170.9 152.5 180.3 123.7 194.3 76.4 159.9 144.4 168.3 116.8 181.3 70.8
80 188.2 178.1 195.2 156.8 207.9 122.2 178.0 170.0 184.2 149.7 196.0 116.2 167.0 161.2 172.3 141.9 183.2 109.5
85 196.1 192.6 201.1 176.9 210.3 151.4 185.9 184.0 190.2 169.0 198.5 144.5 174.7 174.6 178.3 160.6 185.9 137.0
90 204.5 204.5 208.3 192.5 215.2 173.1 194.0 194.0 197.2 184.2 203.4 165.5 182.7 182.7 185.3 175.1 190.8 157.3
56 RT-PRC028AC-EN
Performance Data
Table 30. Gross cooling capacities 15 tons three phase high efficiency T/YH*180G3,4,W (full load)
Air
Flow cfm
3000
115
Ambient Temperature
120 125
Ent
DB 61 67 73 61
Entering Wet Bulb
67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 125.3 101.0 136.8 79.5 151.4 40.4 120.4 97.8 131.5 76.9 145.7 38.5 115.3 94.5 126.0 74.1 139.8 36.4
80 128.5 113.0 138.8 98.9 152.4 72.3 123.6 109.5 133.6 95.9 146.7 69.9 118.5 105.8 128.1 92.7 140.8 67.2
85 133.0 122.3 140.9 112.6 153.3 94.0 128.1 118.5 135.6 109.3 147.6 91.1 122.9 114.6 130.1 105.7 141.7 88.1
90 138.3 130.2 144.6 123.1 154.2 109.5 133.3 126.2 139.2 119.4 148.5 106.2 128.0 122.0 133.7 115.6 142.6 102.8
75 130.9 108.3 141.5 86.1 155.4 46.3 125.8 105.0 138.6 83.3 149.5 44.1 120.5 101.4 132.9 80.4 143.4 41.8
3600
4200
4800
5400
6000
80 134.6 120.9 144.1 106.2 156.8 79.0 129.5 117.2 138.7 103.0 151.0 76.3 124.3 113.3 133.0 99.6 144.9 73.5
85 139.6 130.8 146.7 120.6 158.3 101.4 134.5 126.8 141.3 117.0 152.5 98.3 129.1 122.6 135.6 113.3 146.4 95.0
90 145.2 139.0 150.9 131.5 159.8 117.4 140.0 134.8 145.3 127.7 153.9 113.9 134.5 130.5 139.6 123.6 147.9 110.3
75 135.7 114.9 148.0 92.0 158.5 51.3 130.4 111.3 142.2 88.9 152.4 48.9 124.9 107.5 136.3 85.8 146.1 46.4
80 140.0 128.0 148.7 112.7 160.6 84.8 134.7 124.1 143.0 109.3 154.5 82.0 129.2 120.0 137.1 105.7 148.2 78.9
85 145.4 138.4 151.8 127.7 162.6 107.9 140.1 134.2 146.1 123.9 156.5 104.6 134.5 129.8 140.2 120.0 150.2 101.1
90 151.4 147.1 156.4 139.2 164.7 124.6 145.9 142.7 150.7 135.1 158.6 120.9 140.3 138.1 144.7 130.9 152.3 117.1
75 139.7 120.6 151.0 97.0 160.9 55.5 134.2 116.8 145.1 93.8 159.7 53.0 128.5 112.9 138.9 90.4 153.1 50.2
80 144.6 134.4 152.4 118.5 163.5 89.9 139.1 130.2 146.5 114.8 159.8 86.8 133.4 125.9 140.4 111.0 153.2 83.5
85 150.4 145.3 156.1 134.0 166.1 113.7 144.9 140.8 150.2 130.0 159.8 110.2 139.1 136.3 144.1 125.9 153.3 106.5
90 156.7 154.4 161.2 146.0 168.7 130.9 151.1 149.8 155.2 141.7 162.5 127.0 145.2 145.0 149.1 137.3 156.0 123.0
75 142.9 125.6 153.3 101.2 167.5 59.0 137.3 121.6 147.1 97.8 160.8 56.2 131.4 117.4 140.7 94.2 154.0 53.2
80 148.4 139.9 155.4 123.4 168.2 94.2 142.7 135.6 149.3 119.6 161.6 90.9 136.8 131.1 143.0 115.6 154.8 87.4
85 154.7 151.3 159.7 139.6 168.8 118.6 148.9 146.7 153.6 135.4 162.4 114.9 143.0 141.9 147.3 131.0 155.6 111.0
90 161.3 160.9 165.1 152.1 172.0 136.5 155.5 155.5 159.0 147.6 165.6 132.4 149.4 149.4 152.6 142.9 158.8 128.2
75 145.4 129.7 154.8 104.7 168.0 61.6 139.5 125.5 148.4 101.0 161.2 58.6 133.4 121.1 141.8 97.3 154.1 55.5
80 151.4 144.7 157.6 127.6 169.4 97.6 145.5 140.1 151.3 123.5 162.6 94.1 139.4 135.4 144.8 119.3 155.6 90.5
85 158.1 156.6 162.4 144.3 170.8 122.8 152.2 151.7 156.1 139.9 164.1 118.9 146.0 146.0 149.6 135.4 157.2 114.8
90 165.1 165.1 168.4 157.3 174.6 141.2 159.1 159.1 162.0 152.6 167.9 137.0 152.8 152.8 155.4 147.8 161.0 132.5
75 147.1 133.1 155.5 107.3 168.5 63.4 141.0 128.7 148.9 103.5 161.5 60.3 134.7 124.1 142.1 99.5 154.2 56.9
6600
80 153.6 148.6 159.0 130.9 169.9 100.3 147.6 143.9 152.5 126.7 162.9 96.6 141.3 138.9 145.8 122.2 155.7 92.7
85 160.8 160.8 164.4 148.3 172.0 126.2 154.7 154.7 157.9 143.7 165.1 122.0 148.3 148.3 151.2 138.9 158.0 117.7
90 168.2 168.2 170.8 161.8 176.3 145.2 161.9 161.9 164.2 156.9 169.4 140.7 155.5 155.5 157.5 151.8 162.3 136.1
75 148.0 135.6 156.1 109.2 169.1 64.5 141.7 131.0 149.4 105.1 161.8 61.1 135.2 126.2 142.4 100.9 154.4 57.5
7200
80 155.1 151.8 159.6 133.5 170.3 102.2 148.8 146.8 152.9 129.0 163.2 98.3 142.3 141.7 146.0 124.4 155.8 94.2
85 162.7 162.7 165.6 151.4 172.4 128.8 156.4 156.4 158.9 146.6 165.3 124.4 149.8 149.8 152.0 141.6 158.7 119.9
90 170.4 170.4 172.4 165.4 177.3 148.4 164.0 164.0 165.7 160.4 170.2 143.7 157.3 157.3 158.7 155.1 162.8 138.8
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 3000, 3600, and 4200 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Dehumidification (Hot Gas Reheat) with Frostat and Crankcage heaters are required on applications below 320 cfm/ton.
- Multi-speed or single zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC028AC-EN 57
Performance Data
Table 31. Gross cooling capacities 15 tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD180G3,4,W (Digit 22 = B)
Air
Flow cfm (a)
3000
3900
4800
5400
6000
6600
7200
85
61
Ambient Temperature
95
Entering Wet Bulb
67 73
105
Ent
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 149.8 108.9 167.7 71.3 190.8 66.8 141.5 104.7 158.6 68.7 180.8 63.3 132.6 99.7 148.8 65.2 170.1 59.5
80 151.5 129.2 166.7 101.1 187.0 65.5 143.4 124.3 157.7 97.7 177.1 62.0 134.7 118.5 148.1 93.4 166.7 58.3
85 154.6 144.8 167.0 126.0 184.5 89.1 146.7 139.2 158.2 121.9 174.9 86.5 138.1 132.6 148.8 116.9 164.6 83.0
90 159.1 155.7 168.7 146.3 183.5 118.7 151.3 149.2 160.1 141.4 174.0 115.3 143.0 141.9 150.9 135.6 163.9 111.1
75 160.4 120.9 176.9 82.0 198.6 69.5 151.6 116.3 167.3 79.0 188.1 65.8 142.3 110.9 157.1 75.1 177.0 61.9
80 163.1 142.6 176.9 113.1 195.8 68.5 154.6 137.2 167.5 109.3 185.5 64.9 145.4 131.0 157.4 104.6 174.5 61.1
85 167.2 159.5 178.2 139.4 194.4 101.1 158.8 153.4 169.0 134.8 184.2 98.1 149.8 146.4 159.1 129.4 173.5 94.2
90 172.7 171.6 180.9 160.9 194.3 132.0 164.5 164.5 171.9 155.6 184.3 128.2 155.7 155.7 162.2 149.4 173.8 123.5
75 169.3 131.7 184.4 91.5 204.6 71.6 160.0 126.7 174.3 88.0 193.7 67.8 150.2 120.8 163.6 83.7 182.1 63.7
80 173.0 154.7 185.4 123.8 202.8 74.8 164.0 148.9 175.5 119.6 192.1 72.1 154.3 142.3 164.9 114.5 180.7 68.6
85 178.1 172.9 187.7 151.4 202.4 111.8 169.3 166.4 178.0 146.5 191.8 108.4 159.8 159.0 167.7 140.6 180.6 104.0
90 184.6 184.6 191.4 174.3 203.4 144.0 176.0 176.0 181.9 168.5 192.9 139.8 166.7 166.7 171.7 161.9 181.9 134.7
75 174.2 138.2 188.4 97.1 207.7 72.7 164.7 132.9 178.0 93.4 196.4 68.7 154.6 126.8 167.0 88.8 184.5 64.6
80 178.6 162.0 190.0 130.3 206.6 80.4 169.3 156.0 179.8 125.8 195.5 77.4 159.3 149.1 169.0 120.4 183.8 73.6
85 184.4 181.1 193.1 158.8 206.8 118.2 175.3 174.3 183.0 153.5 195.9 114.5 165.5 165.5 172.4 147.4 184.4 109.9
90 191.6 191.6 197.4 182.5 208.4 151.4 182.6 182.6 187.6 176.5 197.7 146.9 173.0 173.0 177.2 169.5 186.4 141.5
75 178.4 144.1 191.6 102.1 210.0 73.5 168.5 138.6 180.9 98.1 198.4 69.4 158.1 132.1 169.6 93.2 186.2 65.2
80 183.5 168.8 193.9 136.2 209.5 85.4 173.8 162.5 183.4 131.4 198.1 82.2 163.6 155.3 172.3 125.8 186.1 78.1
85 189.9 188.8 197.6 165.5 210.4 124.1 180.5 180.5 187.3 160.0 199.2 120.1 170.4 170.4 176.4 153.6 187.4 115.3
90 197.8 197.8 202.7 190.1 212.7 158.1 188.5 188.5 192.6 183.8 201.7 153.4 178.6 178.6 181.8 176.6 190.1 147.7
75 181.8 149.5 194.1 106.6 211.5 74.0 171.6 143.7 183.0 102.3 199.6 69.9 160.9 137.0 171.4 97.1 187.1 65.5
80 187.5 175.0 197.1 141.5 211.7 89.9 177.6 168.5 186.2 136.5 200.0 86.4 167.0 161.0 174.8 130.6 187.7 82.0
85 194.7 194.7 201.4 171.8 213.3 129.5 184.9 184.9 190.8 166.0 201.8 125.2 174.5 174.5 179.5 159.2 189.7 120.0
90 203.2 203.2 207.2 197.2 216.3 164.3 193.6 193.6 196.7 190.6 204.9 159.3 183.4 183.4 185.6 183.2 193.0 153.3
75 184.4 154.3 195.7 110.5 212.2 74.3 173.9 148.2 184.4 105.9 200.0 70.0 162.9 141.2 172.5 100.5 187.2 65.5
80 190.8 180.7 199.4 146.3 213.1 93.8 180.6 173.9 188.3 141.0 201.1 90.0 169.7 166.1 176.5 134.8 188.5 85.3
85 198.7 198.7 204.5 177.4 215.4 134.2 188.6 188.6 193.5 171.3 203.6 129.7 177.9 177.9 181.9 164.3 191.1 124.2
90 207.8 207.8 210.9 203.8 219.0 170.0 198.0 198.0 200.1 196.9 207.4 164.6 188.7 188.7 188.7 188.7 195.1 158.4
58 RT-PRC028AC-EN
Performance Data
Table 31. Gross cooling capacities 15 tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD180G3,4,W (Digit 22 = B)
Air
Flow
Ent
DB 61
115
67 73 61
Ambient Temperature
120
Entering Wet Bulb
67 73 61
125
67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
3000
3900
4800
5400
75 123.1 93.8 138.4 60.9 158.9 55.6 118.1 90.5 133.0 58.3 153.0 53.5 112.9 87.0 127.4 55.6 147.0 51.4
80 125.3 111.8 137.9 88.3 155.6 54.5 120.4 108.1 132.6 85.4 149.8 52.4 115.4 104.2 127.1 82.2 143.9 50.4
85 129.0 125.1 138.8 111.0 153.7 78.6 124.2 121.1 133.5 107.7 148.0 76.1 119.2 116.8 128.1 104.1 142.2 73.3
90 134.0 133.7 141.0 128.9 153.1 105.9 129.3 129.2 135.9 125.2 147.6 103.0 124.4 124.4 130.6 121.3 141.8 99.9
75 132.3 104.6 146.2 70.3 165.3 57.8 127.1 101.1 140.6 67.6 159.2 55.7 121.7 97.3 134.7 64.6 152.9 53.5
80 135.6 123.9 146.7 99.0 163.0 57.1 130.5 120.0 141.2 95.9 157.0 54.9 125.2 115.9 135.4 92.6 150.8 52.8
85 140.2 138.5 148.6 123.0 162.1 89.3 135.2 134.2 143.1 119.5 156.2 86.6 130.0 129.7 137.5 115.8 150.1 83.6
90 146.3 146.3 151.9 142.3 162.6 118.0 141.3 141.3 146.5 138.4 156.8 114.8 136.2 136.2 140.9 134.2 150.8 111.5
75 139.8 114.1 152.3 78.5 169.9 59.5 134.3 110.4 146.4 75.5 163.6 57.3 128.7 106.4 140.4 72.4 157.1 55.0
80 144.1 134.7 153.8 108.5 168.7 64.1 138.7 130.6 148.0 105.2 162.4 61.6 133.2 126.3 142.1 101.6 156.0 58.8
85 149.8 149.8 156.7 133.8 168.8 98.8 144.5 144.5 151.0 130.1 162.6 95.9 139.1 139.1 145.1 126.2 156.4 92.7
90 156.8 156.8 161.0 154.4 170.3 128.7 151.6 151.6 155.4 150.3 164.2 125.4 146.3 146.3 149.6 145.9 158.0 121.8
75 143.8 119.7 155.4 83.3 172.0 60.2 138.2 115.9 149.3 80.2 165.6 57.9 132.4 111.8 143.1 76.9 158.9 55.6
80 148.8 141.3 157.6 114.2 171.5 68.9 143.3 137.0 151.6 110.7 165.1 66.2 137.6 132.6 145.5 107.0 158.5 63.3
85 155.1 155.1 161.1 140.3 172.3 104.4 149.7 149.7 155.3 136.5 166.0 101.3 144.1 144.1 149.3 132.4 159.5 98.0
90 162.8 162.8 166.1 161.7 174.4 135.2 157.5 157.5 160.3 157.5 168.2 131.7 152.9 152.0 154.4 153.0 161.9 128.0
6000
6600
75 147.1 124.8 157.7 87.5 173.4 60.7 141.3 120.8 151.5 84.2 166.8 58.4 135.4 116.6 145.1 80.8 160.0 56.0
80 152.7 147.2 160.5 119.2 173.5 73.1 147.0 142.8 154.4 115.6 167.0 70.2 141.2 138.2 148.2 111.8 160.3 67.2
85 159.7 159.7 164.8 146.3 175.0 109.5 154.2 154.2 158.8 142.3 168.5 106.2 148.4 148.4 152.6 138.0 161.9 102.8
90 168.7 168.1 170.4 168.5 177.8 141.1 162.8 162.8 164.5 164.2 171.5 137.5 158.4 158.4 158.4 158.4 165.0 133.7
75 149.5 129.4 159.2 91.1 174.0 60.9 143.6 125.2 152.8 87.7 167.2 58.5 137.6 120.9 146.3 84.1 160.3 56.1
80 155.9 152.6 162.7 123.7 174.8 76.7 150.0 148.1 156.5 120.0 168.1 73.7 144.1 143.4 150.1 116.0 161.2 70.5
85 163.6 163.6 167.7 151.6 176.9 114.0 157.8 157.8 161.5 147.5 170.3 110.6 151.9 151.9 155.2 143.1 163.6 107.0
90 174.0 174.0 174.0 174.0 180.4 146.5 167.9 167.9 167.9 167.9 173.9 142.7 161.7 161.7 161.7 161.7 167.3 138.8
7200
75 151.2 133.3 159.9 94.2 173.8 60.8 145.2 129.0 153.4 90.7 166.9 58.4 138.9 124.6 146.8 86.9 159.8 55.9
80 158.2 157.5 164.2 127.7 175.2 79.7 152.3 152.3 157.8 123.8 168.4 76.6 146.1 146.1 151.2 119.7 161.4 73.3
85 166.6 166.6 169.8 156.5 178.1 117.9 160.7 160.7 163.5 152.2 171.3 114.4 154.7 154.7 157.0 147.7 164.4 110.7
90 176.7 176.7 176.7 176.7 182.3 151.3 170.5 170.5 170.5 170.5 175.6 147.4 164.1 164.1 164.1 164.1 168.8 143.3
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
(a)For 3000 and 3900 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Dehumidification (Hot Gas Reheat) with Frostat and Crankcage heaters are required on applications below 320 cfm/ton.
- Multi-speed or single zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC028AC-EN 59
Performance Data
Table 32. Gross cooling capacities 17½ tons three phase high efficiency T/YH*210G3,4,W (stage 1)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
2800
3500
4200
4900
5600
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
63.9 60.0 68.3 47.4 74.6 22.7 59.8 56.7 64.0 44.6 70.2 20.3
67.5 66.8 70.0 59.7 75.7 44.0 63.4 63.4 65.8 56.6 71.3 41.4
71.6 71.6 73.0 68.1 76.7 58.1 67.5 67.5 68.8 64.8 72.4 55.2
75.8 75.8 76.7 74.3 79.2 67.9 71.7 71.7 72.5 70.9 74.8 64.8
65.8 63.2 69.7 50.8 75.5 26.3 61.5 59.7 65.2 47.7 70.8 23.7
69.8 69.8 71.9 63.3 77.0 47.8 65.5 65.5 67.4 59.9 72.3 44.9
74.1 74.1 75.2 71.9 78.4 62.1 69.8 69.8 70.8 68.3 73.8 58.9
78.6 78.6 79.1 78.4 81.2 72.1 74.2 74.2 74.7 74.7 76.7 68.7
67.3 65.7 70.6 53.5 76.0 29.2 62.8 61.9 65.9 50.1 71.1 26.3
71.6 71.6 73.2 66.2 77.8 50.9 67.0 67.0 68.5 62.5 73.0 47.7
76.2 76.2 76.9 75.0 79.7 65.4 71.6 71.6 72.2 71.2 74.9 61.9
80.9 80.9 81.1 81.1 82.8 75.6 76.3 76.3 76.4 76.4 78.0 71.9
68.4 67.6 71.1 55.5 76.8 31.5 63.6 63.5 66.2 51.9 71.5 28.2
72.9 72.9 74.1 68.4 77.9 53.3 68.2 68.2 69.2 64.5 73.1 49.7
77.8 77.8 78.1 77.4 80.5 67.9 73.0 73.0 73.2 73.2 75.5 64.1
81.0 81.0 82.6 82.6 84.0 78.3 76.5 75.0 77.7 77.7 79.0 74.4
68.9 68.7 71.2 56.9 77.0 33.0 63.7 63.7 67.0 52.9 72.2 29.5
73.9 73.9 74.6 69.9 78.2 55.0 68.9 68.9 69.5 65.7 73.9 51.1
78.0 78.0 78.9 78.9 80.9 69.8 73.2 71.0 73.8 73.8 75.6 65.7
82.1 82.1 83.7 83.7 84.7 80.4 77.0 77.0 78.6 78.6 79.4 76.1
6125
75
80
85
90
69.1 69.1 71.6 57.4 77.4 33.7 63.9 63.9 68.0 53.2 73.0 30.0
74.3 74.3 74.7 70.5 78.4 55.8 69.1 69.1 71.0 66.1 74.4 51.7
78.6 78.6 79.3 79.3 81.8 70.7 73.5 73.5 74.0 74.0 77.0 66.4
83.5 83.5 84.2 84.2 84.9 81.5 77.2 77.2 78.9 78.9 79.5 77.0
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 2800, 3500, 4200, and 4900 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
60 RT-PRC028AC-EN
Performance Data
Table 33. Gross cooling capacities 17½ tons three phase high efficiency T/YH*210G3,4,W (stage 2)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
2800
3500
4200
4900
5600
75 123.5 100.2 134.4 80.1 147.8 44.0 117.3 96.3 127.4 77.0 139.9 41.8
80 126.3 111.0 136.4 97.8 148.9 73.2 120.1 106.7 129.4 94.1 141.1 70.2
85 130.4 119.4 138.3 110.3 150.0 92.9 124.2 114.7 131.3 106.1 142.3 89.4
90 135.4 126.3 141.8 119.6 151.1 106.9 129.0 121.3 134.8 115.0 143.4 102.8
75 129.9 108.5 142.2 87.5 152.2 50.4 123.2 104.2 134.6 84.0 143.9 47.6
80 133.3 120.2 142.4 106.1 154.0 80.6 126.7 115.4 135.0 102.0 145.8 77.2
85 138.0 129.2 145.1 119.4 155.8 101.2 131.3 124.0 137.7 114.7 147.7 97.2
90 143.5 136.7 149.2 129.3 157.7 115.9 136.7 131.2 141.7 124.3 149.6 111.4
75 135.1 115.8 146.3 93.8 160.5 55.6 128.0 111.0 138.3 89.8 151.6 52.4
80 139.3 128.2 147.4 113.3 160.5 86.9 132.2 122.9 139.6 108.7 151.8 83.0
85 144.5 137.8 150.7 127.3 160.6 108.4 137.4 132.2 142.9 122.2 152.0 103.9
90 150.5 145.9 155.4 137.9 163.1 123.8 143.2 139.9 147.6 132.5 154.6 118.9
75 139.2 121.9 149.3 99.0 162.4 59.6 131.7 116.7 140.9 94.5 153.0 56.0
80 144.1 135.1 151.3 119.4 163.3 92.0 136.6 129.4 143.0 114.3 154.1 87.7
85 149.9 145.4 155.3 134.1 164.2 114.4 142.4 139.3 147.1 128.6 155.2 109.5
90 156.3 153.9 160.6 145.4 167.5 130.6 148.6 147.5 152.3 139.5 158.5 125.3
75 142.3 126.9 151.2 103.0 163.2 62.6 134.3 121.2 142.3 98.1 153.4 58.5
80 147.8 140.8 154.1 124.3 165.0 96.0 139.9 134.7 145.3 118.8 155.4 91.2
85 154.2 151.7 158.8 139.8 166.8 119.3 146.3 145.2 150.1 133.8 157.4 114.0
90 161.1 160.8 164.6 151.7 170.7 136.3 152.9 152.9 155.9 145.4 161.4 130.5
6125
75 143.8 129.9 151.9 105.3 164.1 64.0 135.5 123.9 142.7 100.0 154.0 59.6
80 149.9 144.4 155.4 127.3 165.5 98.3 141.7 137.9 146.4 121.4 155.6 93.2
85 156.7 155.8 160.7 143.3 168.0 122.3 148.4 148.4 151.7 137.0 158.2 116.6
90 163.9 163.9 167.0 155.7 172.5 139.8 155.4 155.4 157.9 149.0 162.8 133.6
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 2800, 3500, 4200, and 4900 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC028AC-EN 61
Performance Data
Table 34. Gross cooling capacities 17½ tons three phase high efficiency T/YH*210G3,4,W (full load)
Air
Flow cfm (a)
3500
4200
4900
5600
6300
7000
7700
8400
85
Ambient Temperature
95 105
Ent Entering Wet Bulb
DB 61 67 73 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 178.2 140.1 193.8 111.1 207.3 60.7 169.5 134.8 186.6 107.2 204.8 58.4 159.9 128.9 174.5 102.7 183.6 55.5
80 182.3 156.6 197.4 136.9 211.8 102.1 173.6 150.4 187.6 132.0 205.4 98.5 164.0 143.7 177.0 126.4 187.8 94.3
85 188.5 169.5 200.2 155.6 217.6 130.7 179.6 162.7 190.4 149.7 206.7 126.0 169.9 155.2 179.7 143.3 195.0 120.8
90 195.9 180.3 205.3 169.8 219.0 151.3 186.7 172.9 195.3 163.3 208.1 145.8 176.7 164.9 184.5 156.2 196.4 139.7
75 186.2 150.2 194.6 120.2 212.8 68.8 177.0 144.4 193.2 115.8 211.6 66.0 166.9 138.0 183.6 110.8 196.3 62.6
80 191.0 167.4 205.2 147.0 223.4 111.3 181.8 160.8 194.9 141.5 212.2 107.2 171.7 153.5 183.7 135.5 198.7 102.5
85 197.7 181.0 208.6 166.4 225.1 140.8 188.3 173.7 198.3 160.1 213.7 135.6 178.1 165.7 187.1 153.2 201.5 129.9
90 205.5 192.4 214.2 181.3 227.2 162.2 195.9 184.5 203.8 174.3 215.8 156.2 185.3 176.0 192.4 166.7 203.5 149.6
75 193.4 159.4 211.5 128.5 229.7 76.0 183.6 153.0 200.5 123.6 217.5 72.7 173.0 146.1 188.6 118.0 204.6 68.8
80 198.8 177.4 212.0 156.2 230.6 119.6 189.1 170.2 201.2 150.2 218.2 114.9 178.5 162.4 189.5 143.6 205.4 109.7
85 206.0 191.6 216.1 176.3 231.7 150.0 196.1 183.7 205.2 169.5 219.8 144.3 185.4 175.3 193.6 162.1 207.0 138.0
90 214.3 203.5 222.3 191.9 234.4 172.2 204.1 195.1 211.3 184.4 222.5 165.6 193.0 186.1 199.4 176.3 209.8 158.5
75 199.6 167.6 216.7 135.8 236.2 82.3 189.4 160.8 205.1 130.4 223.6 78.5 178.3 153.3 192.7 124.3 206.4 74.0
80 205.7 186.4 218.0 164.4 237.1 126.9 195.5 178.7 206.6 157.9 224.2 121.8 184.4 170.4 194.4 150.8 211.7 116.0
85 213.5 201.3 222.7 185.3 237.4 158.2 203.1 192.9 211.4 178.0 225.0 152.0 191.8 183.9 199.1 170.0 211.7 145.2
90 222.1 213.8 229.4 201.6 240.8 181.2 211.4 204.9 217.9 193.6 228.4 174.2 199.8 195.3 205.5 184.9 215.1 166.5
75 205.0 174.9 220.9 142.2 240.8 87.7 194.2 167.6 208.8 136.2 227.7 83.3 182.6 159.6 195.9 129.7 208.9 78.4
80 211.7 194.5 223.1 171.7 241.7 133.3 201.0 186.3 211.2 164.7 228.6 127.7 189.4 177.4 198.5 157.1 214.6 121.4
85 220.0 210.0 228.4 193.4 242.2 165.6 209.1 201.1 216.6 185.6 229.3 158.8 197.3 191.6 203.8 177.1 215.5 151.5
90 229.1 223.1 235.7 210.4 246.2 189.3 217.8 213.7 223.6 201.8 233.3 181.8 205.7 203.6 210.8 192.6 219.5 173.6
75 209.4 181.3 224.2 147.7 243.2 92.1 198.2 173.4 211.7 141.2 230.3 87.2 186.0 165.0 198.2 134.1 210.2 81.8
80 216.9 201.6 227.2 178.1 244.8 138.8 205.6 192.9 214.8 170.5 231.2 132.7 193.4 183.6 201.6 162.4 216.7 125.9
85 225.6 217.8 233.3 200.6 246.1 172.0 214.2 208.4 220.9 192.2 232.7 164.7 201.9 198.4 207.6 183.2 218.4 156.9
90 235.1 231.5 241.0 218.2 250.8 196.5 223.4 221.5 228.5 209.1 237.4 188.4 210.8 210.8 215.1 199.4 223.1 179.7
75 213.0 186.8 226.7 152.2 245.6 95.6 201.2 178.4 213.6 145.2 231.9 90.2 188.6 169.4 199.6 137.6 210.6 84.2
80 221.1 207.9 230.5 183.5 247.0 143.4 209.3 198.6 217.6 175.5 232.8 136.7 196.6 188.8 203.8 166.8 217.9 129.4
85 230.4 224.7 237.2 206.8 249.1 177.5 218.4 214.8 224.3 197.9 235.2 169.7 205.6 204.3 210.5 188.4 220.4 161.4
90 240.3 238.9 245.5 225.1 254.5 202.8 228.0 228.0 232.4 215.5 240.5 194.2 214.9 214.9 218.5 205.3 225.7 185.0
75 215.7 191.3 228.2 155.8 246.8 98.2 203.4 182.4 214.6 148.3 232.7 92.3 190.2 172.9 200.2 140.2 220.4 85.8
80 224.4 213.2 232.9 188.1 248.3 147.1 212.1 203.4 219.5 179.5 233.6 139.9 199.0 193.1 205.2 170.3 220.8 132.1
85 234.2 230.7 240.2 212.1 251.3 182.0 221.8 220.3 226.8 202.7 236.8 173.8 208.4 208.4 212.6 192.7 221.5 164.9
90 244.5 244.5 249.1 231.1 257.3 208.1 231.8 231.8 235.5 221.0 242.8 199.0 218.1 218.1 221.1 210.2 227.5 189.3
62 RT-PRC028AC-EN
Performance Data
Table 34. Gross cooling capacities 17½ tons three phase high efficiency T/YH*210G3,4,W (full load)
Air
Flow cfm
3500
115
Ambient Temperature
120 125
Ent
DB 61 67 73 61
Entering Wet Bulb
67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 149.5 122.4 158.0 97.6 172.5 52.1 144.0 119.0 155.8 94.8 165.9 50.1 138.2 115.3 148.3 91.9 160.8 48.0
80 153.6 136.3 165.4 120.3 176.7 89.5 148.1 132.4 159.3 117.0 169.4 86.9 142.3 128.4 153.0 113.5 163.4 84.1
85 159.3 147.2 168.2 136.3 182.4 114.9 153.7 143.0 162.1 132.6 175.8 111.8 147.8 138.6 155.8 128.7 169.0 108.4
90 165.8 156.4 172.8 148.5 183.8 133.0 160.1 151.8 166.7 144.4 177.2 129.4 154.1 147.2 160.3 140.2 170.4 125.7
75 156.0 131.0 171.4 105.2 184.6 58.6 150.2 127.2 164.9 102.2 174.8 56.4 144.2 123.3 158.3 99.0 162.4 54.0
4200
4900
5600
6300
7000
80 160.8 145.6 171.6 128.8 186.8 97.2 155.0 141.5 165.3 125.2 175.3 94.3 149.0 137.2 158.7 121.5 168.6 91.2
85 167.0 157.2 175.0 145.6 188.4 123.5 161.1 152.7 168.7 141.6 181.5 120.1 155.0 148.0 162.1 137.5 174.4 116.5
90 173.9 166.9 180.2 158.5 190.4 142.3 167.9 162.1 173.8 154.1 183.6 138.5 161.6 157.2 167.1 149.6 176.5 134.5
75 161.6 138.6 175.9 111.9 190.2 64.3 155.5 134.6 169.2 108.6 180.7 61.8 149.3 130.4 162.3 105.2 175.1 59.2
80 167.0 154.0 176.9 136.4 192.8 103.9 161.0 149.6 170.3 132.6 181.3 100.7 154.7 145.0 163.5 128.6 176.4 97.4
85 173.7 166.2 181.0 154.0 193.4 131.1 167.6 161.4 174.4 149.8 186.3 127.4 161.3 156.5 167.6 145.3 178.9 123.6
90 181.1 176.5 186.7 167.5 196.1 150.7 174.8 171.5 180.0 162.9 189.0 146.6 168.3 166.3 173.1 158.2 181.7 142.4
75 166.3 145.3 179.4 117.7 192.5 69.0 160.0 141.0 172.5 114.1 184.5 66.3 153.5 136.6 165.3 110.4 176.9 63.4
80 172.4 161.5 181.4 143.1 197.4 109.7 166.1 156.8 174.5 139.0 189.9 106.3 159.6 152.0 167.4 134.8 182.2 102.7
85 179.6 174.3 186.1 161.5 197.6 137.8 173.2 169.3 179.2 157.0 190.2 133.9 166.6 164.1 172.1 152.3 182.6 129.8
90 187.4 185.2 192.3 175.7 201.0 158.2 180.9 179.9 185.4 170.8 193.6 153.9 174.1 174.1 178.2 165.8 186.0 149.3
75 170.1 151.0 182.1 122.5 194.1 72.8 163.6 146.5 174.9 118.7 185.6 69.8 156.8 141.9 167.5 114.8 178.3 66.7
80 176.9 168.0 184.9 148.8 199.8 114.6 170.3 163.1 177.8 144.5 192.1 110.9 163.5 158.0 170.4 140.0 184.1 107.1
85 184.6 181.5 190.2 168.0 200.8 143.6 178.0 176.2 183.1 163.2 193.2 139.4 171.1 170.8 175.8 158.3 185.3 135.1
90 192.8 192.8 197.0 182.9 204.9 164.8 186.0 186.0 189.8 177.7 197.2 160.2 179.0 179.0 182.4 172.5 189.4 155.4
75 173.0 155.9 183.9 126.5 194.4 75.7 166.2 151.1 176.5 122.4 186.5 72.4 159.2 146.2 168.8 118.2 178.8 69.0
80 180.4 173.6 187.5 153.7 201.3 118.5 173.6 168.4 180.1 149.1 193.3 114.6 166.6 163.1 172.5 144.3 185.1 110.5
85 188.7 187.8 193.5 173.6 203.2 148.5 181.8 181.8 186.2 168.6 195.3 144.0 174.7 174.7 178.6 163.4 187.2 139.4
90 197.3 197.3 200.8 189.1 207.9 170.4 190.2 190.2 193.4 183.8 200.0 165.5 183.0 183.0 185.7 178.2 191.9 160.5
75 175.1 159.8 184.8 129.4 195.2 77.6 168.0 154.8 177.1 125.1 187.2 74.1 160.7 149.6 169.2 120.7 179.2 70.5
7700
80 183.1 178.3 189.2 157.6 202.0 121.5 176.0 172.9 181.6 152.7 193.7 117.4 168.7 167.3 173.8 147.7 185.3 113.0
85 191.9 191.9 195.9 178.3 204.7 152.4 184.8 184.8 188.3 173.0 196.5 147.7 177.4 177.4 180.4 167.6 188.1 142.8
90 200.9 200.9 203.8 194.5 210.1 175.1 193.6 193.6 196.0 188.8 201.9 170.0 186.1 186.1 188.1 183.1 193.5 164.7
75 176.2 162.8 184.8 131.5 195.6 78.7 168.9 157.5 177.8 126.9 187.9 74.9 161.3 152.0 170.0 122.2 180.3 71.0
8400
80 184.9 182.1 190.1 160.6 202.4 123.6 177.6 176.4 182.2 155.4 194.3 119.2 170.0 170.0 174.1 150.2 184.4 114.6
85 194.2 194.2 197.4 182.1 205.3 155.4 186.8 186.8 189.5 176.5 196.8 150.4 179.2 179.2 181.4 170.8 188.2 145.3
90 203.6 203.6 205.8 198.9 211.3 178.9 196.1 196.1 197.8 193.0 202.9 173.5 188.3 188.3 189.6 187.0 194.2 168.0
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 3500, 4200, and 4900 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC028AC-EN 63
Performance Data
Table 35. Gross cooling capacities 17½ tons three phase dehumidification (hot gas reheat) option high efficiency T/
YHD210G3,4,W (Digit 22 = B)
Air
Flow cfm (a)
3500
4550
5600
6300
7000
7700
8400
85
Ambient Temperature
95 105
Ent
DB 61 67 73 61
Entering Wet Bulb
67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 157.6 122.6 174.5 95.9 196.1 56.8 151.2 119.5 166.8 93.6 187.2 55.2 143.7 115.7 158.2 90.5 177.3 53.0
80 160.6 140.5 174.2 120.6 192.5 88.1 154.0 136.7 166.5 117.6 183.6 85.9 146.5 132.2 157.8 113.8 173.6 83.0
85 165.2 154.7 175.6 141.4 190.7 115.7 158.6 150.2 167.8 137.7 181.7 112.8 151.0 145.0 159.0 133.3 171.6 109.2
90 171.5 165.0 178.7 158.5 190.5 139.5 164.8 159.9 170.8 154.1 181.4 135.9 157.2 154.0 161.9 149.1 171.3 131.6
75 167.1 138.7 182.4 110.5 202.3 69.8 160.1 134.8 174.2 107.4 192.8 67.5 152.2 130.2 164.9 103.5 182.4 64.4
80 171.1 158.1 183.1 136.6 199.7 102.6 164.0 153.5 174.8 132.7 190.2 99.5 156.0 148.2 165.5 128.2 179.7 95.8
85 176.7 173.6 185.5 158.8 198.9 131.5 169.6 168.3 177.1 154.3 189.3 127.8 161.4 161.4 167.7 149.1 178.7 123.4
90 184.0 184.0 189.5 177.3 199.7 156.7 176.8 176.8 181.1 172.1 190.0 152.3 168.6 168.6 171.6 166.2 179.4 147.2
75 174.9 145.5 188.5 116.5 206.7 75.0 167.3 141.2 179.7 113.0 196.7 72.3 158.8 136.2 169.9 108.7 185.7 68.8
80 179.8 165.5 190.1 143.2 205.1 108.5 172.2 160.6 181.3 139.0 195.1 105.0 163.6 154.9 171.5 134.1 184.0 100.9
85 186.4 181.8 193.5 166.2 205.3 138.1 178.7 176.1 184.6 161.3 195.1 134.0 170.0 169.7 174.7 155.7 184.0 129.2
90 194.7 194.2 198.5 185.3 207.0 164.0 186.9 186.9 189.5 179.8 196.8 159.2 178.1 178.1 179.6 173.5 185.7 153.7
75 179.1 151.4 191.5 121.6 208.6 79.4 171.1 146.7 182.4 117.7 198.3 76.2 162.2 141.3 172.3 113.1 187.0 72.4
80 184.6 172.1 193.9 149.1 207.7 113.5 176.6 166.8 184.7 144.5 197.3 109.7 167.7 160.7 174.5 139.1 185.9 105.1
85 191.9 189.1 197.9 172.7 208.5 143.9 183.8 183.0 188.6 167.4 198.0 139.3 174.8 174.8 178.3 161.4 186.5 134.1
90 200.8 200.8 203.5 192.6 210.9 170.4 192.6 192.6 194.2 186.6 200.4 165.2 183.5 183.5 183.9 179.9 188.8 159.3
75 182.4 156.5 193.8 125.9 209.8 82.9 174.2 151.4 184.3 121.6 199.1 79.3 164.9 145.6 173.8 116.6 187.4 75.1
80 188.6 177.9 196.8 154.0 209.5 117.7 180.3 172.1 187.2 149.0 198.8 113.5 171.0 165.6 176.7 143.3 187.0 108.5
85 196.5 195.5 201.4 178.4 211.0 148.7 188.1 188.1 191.8 172.7 200.1 143.8 178.7 178.7 181.2 166.3 188.3 138.2
90 206.1 206.1 207.7 198.9 214.1 176.0 197.6 197.6 198.0 192.5 203.1 170.4 185.5 185.5 187.3 185.5 191.2 164.1
75 185.0 160.6 195.3 129.3 210.2 85.5 176.4 155.2 185.4 124.6 199.1 81.5 166.7 149.0 174.6 119.2 187.0 76.9
80 191.9 182.8 198.9 158.1 210.6 121.0 183.2 176.6 189.0 152.7 199.4 116.4 173.5 169.7 178.0 146.6 187.3 111.0
85 200.4 200.4 204.2 183.1 212.6 152.7 191.6 191.6 194.2 177.1 201.4 147.4 181.9 181.9 183.2 170.3 189.2 141.4
90 210.6 210.6 211.2 204.4 216.4 180.7 201.8 201.8 201.1 197.6 205.1 174.7 190.0 190.0 190.0 190.0 192.8 168.0
75 186.8 164.0 195.9 131.8 209.7 87.2 177.8 158.1 185.7 126.7 198.3 82.9 167.8 151.5 174.5 120.9 185.9 77.8
80 194.3 186.8 200.2 161.3 210.8 123.5 185.2 180.2 189.9 155.6 199.3 118.4 175.2 172.9 178.6 149.0 186.8 112.7
85 203.5 203.5 206.2 187.1 213.5 155.9 194.4 194.4 195.8 180.6 201.9 150.2 184.2 184.2 184.5 173.4 189.3 143.8
90 214.4 214.4 213.8 209.0 217.9 184.5 201.3 201.3 203.4 201.8 206.2 178.1 191.9 191.9 191.9 191.9 193.6 171.1
64 RT-PRC028AC-EN
Performance Data
Table 35. Gross cooling capacities 17½ tons three phase dehumidification (hot gas reheat) option high efficiency T/
YHD210G3,4,W (Digit 22 = B)
115
Ambient Temperature
120 125
Air
Flow
Ent
DB 61 67 73 61
Entering Wet Bulb
67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
3500
4550
5600
6300
75 135.3 111.1 148.5 86.8 166.4 50.0 130.7 108.6 143.3 84.7 160.6 48.2 125.9 105.9 137.9 82.4 154.5 46.3
80 138.0 127.0 148.0 109.4 162.7 79.3 133.4 124.2 142.8 106.9 156.8 77.2 128.5 121.1 137.3 104.3 150.8 75.0
85 142.4 139.2 149.2 128.2 160.6 104.8 137.8 136.0 143.9 125.4 154.8 102.4 132.9 132.6 138.4 122.4 148.6 99.8
90 148.5 147.5 152.1 143.3 160.3 126.6 143.8 143.8 146.8 140.1 154.3 123.8 138.9 138.9 141.2 136.8 148.2 120.9
75 143.2 124.9 154.8 99.0 171.0 60.6 138.3 119.0 149.3 93.8 164.9 56.2 133.2 118.9 143.6 93.8 158.6 56.2
80 146.9 142.2 155.2 123.0 168.2 91.3 142.0 135.6 149.7 117.2 162.1 86.3 136.9 135.5 144.0 117.1 155.8 86.2
85 152.3 152.3 157.4 143.2 167.2 118.3 147.4 147.4 151.9 136.7 161.0 112.5 142.2 142.2 146.1 136.6 154.6 112.4
90 159.6 159.6 161.2 159.6 167.8 141.4 154.4 154.4 155.7 152.4 161.6 134.9 149.8 149.8 149.8 149.8 155.1 134.9
75 149.3 130.5 159.2 103.8 173.8 64.6 144.2 127.4 153.5 101.1 167.4 62.3 138.8 124.1 147.5 98.2 160.8 59.8
80 154.0 148.5 160.7 128.5 172.0 96.1 148.8 145.0 154.9 125.4 165.6 93.4 143.4 141.4 148.9 122.2 159.0 90.5
85 160.4 160.4 163.8 149.4 171.9 123.7 155.2 155.2 158.0 146.0 165.5 120.6 149.7 149.7 151.9 142.4 158.8 117.4
90 168.4 168.4 168.6 166.5 173.5 147.5 162.8 162.8 162.8 162.8 167.0 144.1 156.7 156.7 156.7 156.7 160.3 140.6
75 152.4 135.2 161.2 107.7 174.6 67.8 147.0 131.9 155.2 104.8 168.1 65.3 141.5 128.4 149.1 101.7 161.3 62.5
80 157.7 153.9 163.3 133.1 173.5 99.9 152.4 150.2 157.3 129.9 166.9 97.0 146.8 146.4 151.1 126.4 160.1 94.0
85 164.7 164.7 167.1 154.7 174.1 128.2 159.4 159.4 161.1 151.1 167.5 125.0 153.7 153.7 154.8 147.3 160.6 121.6
90 172.5 172.5 172.5 172.5 176.3 152.7 166.5 166.5 166.5 166.5 169.7 149.2 160.2 160.2 160.2 160.2 162.8 145.4
7000
7700
75 154.6 139.1 162.3 110.8 174.7 70.1 149.1 135.5 156.2 107.7 168.0 67.4 143.4 131.9 149.9 104.4 161.0 64.4
80 160.6 158.4 165.1 136.9 174.2 102.9 155.1 154.6 159.0 133.4 167.5 99.8 149.3 149.3 152.6 129.8 160.5 96.6
85 168.3 168.3 169.6 159.2 175.4 131.9 162.8 162.8 163.4 155.4 168.7 128.5 156.9 156.9 157.0 151.4 161.6 124.9
90 175.7 175.7 175.7 175.7 178.3 157.1 169.4 169.4 169.4 169.4 171.5 153.3 163.0 163.0 163.0 163.0 164.4 149.4
75 156.1 142.0 162.7 113.0 174.0 71.5 150.5 138.3 156.4 109.7 167.1 68.6 144.5 134.4 149.9 106.2 159.9 65.5
80 162.8 162.1 166.1 139.8 174.2 105.0 157.1 157.1 159.8 136.1 167.2 101.7 151.1 151.1 153.3 132.3 160.0 98.3
85 171.1 171.1 171.2 162.8 176.0 134.7 165.4 165.4 164.9 158.8 169.0 131.1 159.4 159.4 158.3 154.6 161.8 127.3
90 178.0 178.0 178.0 178.0 179.5 160.6 171.6 171.6 171.6 171.6 172.5 156.7 165.0 165.0 165.0 165.0 165.3 152.5
8400
75 156.8 144.2 162.3 114.4 172.5 72.1 151.0 140.3 155.8 110.8 165.4 69.0 144.9 136.2 149.1 107.1 158.0 65.6
80 164.1 164.1 166.4 141.8 173.3 106.3 158.2 158.2 159.9 138.0 166.2 102.8 152.1 152.1 153.1 133.9 158.8 99.1
85 173.1 173.1 172.1 165.5 175.8 136.7 167.2 167.2 165.6 161.3 168.6 132.8 157.2 157.2 158.8 156.9 161.2 128.8
90 179.5 179.5 179.5 179.5 180.0 163.3 173.0 173.0 173.0 173.0 172.8 159.1 166.1 166.1 166.1 166.1 165.3 154.8
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
(a)For 3500, and 4550 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC028AC-EN 65
Performance Data
Table 36. Gross cooling capacities 20 tons three phase high efficiency T/YH*240G3,4,W (stage 1)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
3200
4000
4800
5600
6400
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
71.7 67.2 76.0 52.7 82.4 24.7 66.8 63.4 70.9 49.4 77.0 21.9
76.1 75.4 78.6 67.1 84.3 49.4 71.3 71.3 73.5 63.4 78.9 46.1
81.1 81.1 82.5 77.1 86.2 65.8 76.3 76.3 77.4 73.1 80.9 62.2
86.3 86.3 87.1 84.6 89.5 77.4 81.4 81.4 82.0 80.5 84.3 73.6
73.6 70.6 77.4 56.5 83.2 28.8 68.4 66.4 71.9 52.7 79.9 25.6
78.5 78.5 80.4 71.0 85.6 53.6 73.3 73.3 75.0 66.9 79.9 50.0
83.8 83.8 84.8 81.2 88.0 70.2 78.6 78.6 79.4 76.9 82.3 66.3
89.3 89.3 89.8 89.1 91.8 82.0 84.1 84.1 84.4 84.4 86.2 77.9
75.0 73.3 78.2 59.4 85.9 32.1 69.5 68.6 72.5 55.2 80.0 28.5
80.3 80.3 81.8 74.2 86.4 57.1 74.8 74.8 76.1 69.7 80.4 53.0
86.0 86.0 86.6 84.7 89.3 73.9 80.5 80.5 80.9 79.9 83.4 69.6
91.8 91.8 91.9 91.9 93.6 86.0 85.0 85.0 86.2 86.2 87.6 81.4
76.0 75.2 78.6 61.6 86.0 34.7 70.2 70.1 72.5 57.1 80.2 30.7
81.7 81.7 82.7 76.6 86.8 59.8 75.9 75.9 76.7 71.7 80.5 55.4
87.8 87.8 87.9 87.3 90.2 76.8 81.0 81.0 81.9 81.9 83.9 72.1
92.0 92.0 93.6 93.6 94.9 89.2 87.0 88.0 87.6 87.6 88.6 84.2
76.5 76.3 79.0 63.1 87.0 36.5 70.3 70.3 73.0 58.1 81.0 32.1
82.6 82.6 83.2 78.3 88.0 61.8 76.5 76.5 76.8 73.0 82.5 56.9
88.2 88.2 88.8 88.8 90.6 79.0 82.0 82.0 82.4 82.4 84.0 73.9
93.5 93.5 94.8 94.8 95.7 91.6 88.2 88.2 88.5 88.5 89.1 86.2
7000
75
80
85
90
76.5 76.5 81.0 63.7 88.0 37.4 70.2 70.2 75.0 58.4 82.0 32.7
83.0 83.0 83.2 79.0 91.0 62.7 76.6 76.6 78.0 73.4 84.0 57.6
89.0 89.0 89.1 89.1 94.0 80.1 82.2 82.2 82.5 82.5 86.0 74.7
95.0 95.0 95.4 95.4 96.0 92.9 88.4 89.0 88.8 88.8 89.1 87.3
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 3200, 4000, 4800, and 5600 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
66 RT-PRC028AC-EN
Performance Data
Table 37. Gross cooling capacities 20 tons three phase high efficiency T/YH*240G3,4,W (stage 2)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
3200
4000
4800
5600
6400
75 147.4 116.5 161.9 94.0 179.6 54.5 139.3 111.3 153.0 89.7 169.9 51.2
80 150.8 130.2 164.3 114.7 181.0 87.0 142.8 124.5 155.5 109.7 171.4 82.9
85 155.8 141.5 166.7 130.2 182.4 110.0 147.8 135.4 158.0 124.7 172.9 105.2
90 161.9 151.4 170.9 142.5 183.7 127.2 153.7 144.9 162.2 136.6 174.4 121.9
75 155.6 127.1 171.7 103.0 185.5 61.7 147.0 121.3 162.1 98.1 175.3 57.9
80 160.1 142.0 172.3 125.2 187.9 96.0 151.5 135.8 163.0 119.7 177.7 91.4
85 165.9 154.4 175.7 141.9 190.2 120.5 157.3 147.7 166.4 135.9 180.2 115.2
90 172.5 165.2 180.7 155.4 192.5 138.9 163.9 158.2 171.5 148.9 182.6 133.1
75 162.5 136.3 177.1 110.6 195.7 67.6 153.4 130.0 167.0 105.3 184.6 63.2
80 167.9 152.5 178.9 134.3 196.1 103.6 158.8 145.7 169.0 128.3 185.3 98.5
85 174.5 166.0 183.2 152.3 196.6 129.6 165.4 158.8 173.5 145.8 186.0 123.8
90 181.8 177.7 189.1 166.9 199.9 149.3 172.6 170.2 179.3 159.9 189.4 143.0
75 168.0 144.2 181.2 116.9 198.4 72.1 158.3 137.4 170.5 111.0 186.8 67.2
80 174.3 161.7 184.1 142.1 200.0 109.9 164.7 154.3 173.7 135.6 188.6 104.2
85 181.7 176.2 189.4 161.4 201.6 137.4 172.0 168.4 179.1 154.3 190.5 131.1
90 189.6 188.8 196.1 177.1 205.9 158.4 179.9 179.9 185.7 169.6 194.9 151.5
75 172.1 150.7 183.8 121.9 199.6 75.3 161.8 143.4 172.6 115.5 187.5 69.9
80 179.3 169.5 187.9 148.6 202.4 114.9 169.2 161.6 177.0 141.5 190.5 108.7
85 187.5 185.1 194.2 169.2 205.2 143.9 177.3 176.8 183.3 161.6 193.5 137.0
90 196.0 196.0 201.6 185.9 210.4 166.2 185.8 185.8 190.7 177.9 198.9 158.8
7000
75 174.2 154.7 184.8 124.8 199.6 76.8 163.5 147.0 173.2 117.9 190.8 71.0
80 182.2 174.4 189.9 152.6 203.3 117.8 171.6 166.2 178.5 145.1 191.0 111.1
85 190.9 190.8 196.8 174.1 207.0 147.9 180.3 180.3 185.5 166.1 194.9 140.6
90 199.9 199.9 204.9 191.6 212.9 171.1 189.3 189.3 193.6 183.2 201.0 163.3
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 3200, 4000, 4800, and 5600 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC028AC-EN 67
Performance Data
Table 38. Gross cooling capacities 20 tons three phase high efficiency T/YH*240G3,4,W (full load)
Air
Flow cfm (a)
4000
4800
5600
6400
7200
8000
8800
9600
85
Ambient Temperature
95 105
Ent Entering Wet Bulb
DB 61 67 73 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 204.7 159.8 224.3 126.6 248.0 69.4 194.8 153.5 213.3 121.7 235.9 66.2 184.1 146.6 201.4 116.3 223.0 62.4
80 209.6 179.2 227.5 156.5 249.7 116.6 199.7 172.0 216.5 150.5 237.6 112.1 189.0 164.2 204.7 143.9 224.8 106.9
85 217.0 194.6 230.8 178.3 251.4 149.6 206.9 186.7 219.8 171.4 239.4 143.9 195.9 178.1 208.0 163.9 226.5 137.7
90 225.7 207.7 236.9 195.3 253.2 173.8 215.3 199.2 225.7 187.6 241.1 167.2 204.1 190.1 213.7 179.4 228.2 160.0
75 214.2 171.5 232.6 137.1 255.1 78.6 203.7 164.6 225.1 131.7 242.5 74.8 192.4 157.1 212.5 125.6 229.0 70.4
80 220.0 191.9 236.7 168.2 257.7 127.2 209.5 184.0 225.1 161.6 245.1 122.0 198.1 175.6 212.7 154.4 231.6 116.3
85 228.0 208.1 240.9 191.0 260.3 161.4 217.3 199.6 229.2 183.5 247.7 155.1 205.7 190.4 216.8 175.4 234.2 148.2
90 237.3 221.9 247.6 208.8 262.9 186.5 226.3 212.8 235.9 200.6 250.2 179.3 214.5 203.1 223.2 191.7 236.7 171.5
75 222.7 182.1 243.9 146.6 261.2 86.7 211.5 174.6 231.5 140.5 248.0 82.3 199.6 166.5 218.3 133.9 233.9 77.4
80 229.3 203.5 244.8 178.8 264.7 136.7 218.1 195.0 232.6 171.6 251.4 130.9 206.2 186.0 219.5 163.8 237.3 124.6
85 237.9 220.6 249.8 202.6 268.1 172.0 226.6 211.4 237.6 194.5 254.8 165.1 214.5 201.7 224.5 185.8 240.7 157.6
90 247.8 235.1 257.3 221.2 271.6 198.1 236.2 225.3 244.9 212.4 258.3 190.3 223.7 215.0 231.6 203.0 244.2 181.9
75 230.0 191.6 249.9 154.9 274.8 93.8 218.3 183.5 236.8 148.3 260.5 88.8 205.7 174.8 223.0 141.0 245.5 83.2
80 237.5 214.0 251.8 188.3 274.8 145.1 225.7 204.9 239.0 180.5 260.7 138.7 213.1 195.3 225.3 172.1 245.9 131.8
85 246.8 231.9 257.6 213.1 274.8 181.6 234.9 222.1 244.8 204.4 260.9 174.1 222.1 211.8 231.1 195.1 246.2 166.0
90 257.2 247.1 265.8 232.6 279.1 208.6 245.0 236.8 252.8 223.1 265.2 200.2 231.9 225.9 239.0 213.1 250.5 191.2
75 236.2 200.1 254.7 162.2 278.3 99.8 223.9 191.4 241.1 155.0 263.4 94.2 210.7 182.0 226.6 147.1 247.8 88.0
80 244.5 223.4 257.7 196.7 279.4 152.5 232.2 213.7 244.3 188.3 264.7 145.5 219.0 203.5 230.0 179.4 249.2 137.9
85 254.6 242.2 264.4 222.5 280.4 190.0 242.0 231.8 250.9 213.2 265.9 181.9 228.7 220.8 236.7 203.3 250.6 173.3
90 265.5 258.1 273.2 242.8 285.6 218.1 252.6 247.2 259.6 232.8 271.1 209.1 239.0 235.6 245.2 222.2 255.8 199.5
75 241.4 207.5 258.4 168.5 280.7 104.7 228.4 198.1 244.2 160.6 265.2 98.5 214.6 188.2 229.1 152.1 249.0 91.7
80 250.5 231.7 262.5 204.1 282.8 158.7 237.6 221.5 248.5 195.1 267.5 151.1 223.8 210.7 233.6 185.5 251.4 143.0
85 261.2 251.3 270.1 230.8 284.9 197.4 248.1 240.4 256.0 220.9 269.8 188.7 234.1 228.8 241.1 210.5 253.9 179.4
90 272.7 268.0 279.6 252.0 291.0 226.5 259.2 256.5 265.4 241.4 275.8 216.9 245.0 244.3 250.3 230.2 259.9 206.7
75 245.4 213.8 261.1 173.6 282.0 108.5 231.9 203.8 246.2 165.1 265.9 101.7 217.5 193.3 230.6 156.1 249.1 94.3
80 255.4 239.0 266.2 210.4 285.2 163.9 241.8 228.2 251.6 200.8 269.3 155.7 227.4 216.7 236.1 190.6 252.6 146.9
85 266.8 259.4 274.6 238.1 288.4 203.8 253.0 247.9 259.9 227.6 272.6 194.4 238.5 235.7 244.4 216.5 256.1 184.6
90 278.8 276.8 284.8 260.1 295.2 233.8 264.7 264.7 270.0 248.9 279.5 223.6 249.9 249.9 254.3 237.1 263.0 212.8
75 248.4 219.0 262.6 177.6 282.2 111.2 234.2 208.4 247.2 168.6 265.5 103.8 219.2 197.3 230.9 158.9 248.1 95.8
80 259.2 245.2 268.8 215.6 286.4 168.0 245.0 233.7 253.6 205.4 270.0 159.2 230.0 221.7 237.5 194.6 252.6 149.8
85 271.3 266.5 278.1 244.3 290.7 209.0 256.9 254.3 262.8 233.2 274.4 199.1 241.7 241.5 246.7 221.5 257.2 188.6
90 283.8 283.8 289.0 267.2 298.4 240.0 269.1 269.1 273.5 255.3 282.1 229.2 253.7 253.7 257.3 242.9 264.9 217.8
68 RT-PRC028AC-EN
Performance Data
Table 38. Gross cooling capacities 20 tons three phase high efficiency T/YH*240G3,4,W (full load)
Air
Flow cfm
4000
115
Ambient Temperature
120 125
Ent
DB 61 67 73 61
Entering Wet Bulb
67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 172.5 139.1 188.8 110.3 209.3 58.1 166.4 135.1 182.1 107.1 202.2 55.7 160.1 131.0 175.3 103.7 194.8 53.1
80 177.4 155.8 192.0 136.8 211.0 101.2 171.3 151.4 185.4 133.0 203.9 98.1 164.9 146.8 178.5 129.1 196.5 94.9
85 184.2 169.0 195.3 155.9 212.8 130.8 178.0 164.3 188.6 151.7 205.6 127.2 171.6 159.4 181.8 147.3 198.2 123.4
90 192.0 180.4 200.9 170.7 214.5 152.2 185.7 175.3 194.2 166.1 207.3 148.1 179.1 170.1 187.2 161.3 199.9 143.9
75 180.2 149.0 199.0 119.0 214.7 65.5 173.8 144.7 192.0 115.5 207.2 62.8 167.2 140.3 184.7 111.8 199.6 60.0
4800
5600
6400
7200
8000
80 185.9 166.6 199.4 146.7 217.3 110.0 179.5 161.9 192.4 142.6 209.8 106.6 172.9 157.1 185.3 138.4 202.1 103.1
85 193.4 180.7 203.5 166.8 219.8 140.7 186.9 175.7 196.5 162.2 212.3 136.8 180.2 170.5 189.4 157.5 204.7 132.7
90 201.8 192.8 209.8 182.4 222.4 163.1 195.2 187.4 202.7 177.5 214.9 158.7 188.3 181.9 195.5 172.4 207.2 154.2
75 186.8 157.8 204.2 126.7 219.0 71.8 180.1 153.2 196.9 122.8 211.2 68.8 173.2 148.5 189.3 118.9 203.2 65.7
80 193.4 176.4 205.6 155.5 222.4 117.6 186.6 171.4 198.4 151.1 214.6 114.0 179.7 166.2 190.9 146.5 206.6 110.1
85 201.5 191.3 210.6 176.5 225.8 149.6 194.7 186.0 203.3 171.7 218.0 145.3 187.7 180.5 195.9 166.7 210.0 141.0
90 210.5 204.1 217.6 193.0 229.2 172.9 203.5 198.5 210.2 187.8 221.4 168.3 196.4 192.7 202.7 182.4 213.4 163.4
75 192.3 165.5 208.3 133.2 229.6 77.1 185.3 160.6 200.7 129.1 221.3 73.8 178.1 155.6 192.8 124.8 212.9 70.3
80 199.7 185.1 210.8 163.2 230.1 124.3 192.7 179.8 203.3 158.5 222.0 120.3 185.5 174.3 195.5 153.7 213.6 116.1
85 208.5 200.9 216.6 185.2 230.7 157.3 201.4 195.2 209.1 180.1 222.6 152.8 194.1 189.4 201.3 174.8 214.3 148.1
90 218.0 214.4 224.3 202.5 235.0 181.7 210.8 208.4 216.7 197.0 226.9 176.7 203.3 202.3 208.8 191.4 218.6 171.5
75 196.7 172.1 211.3 138.7 231.3 81.2 189.4 167.0 203.4 134.3 222.7 77.7 181.9 161.7 195.2 129.7 213.9 73.9
80 205.0 192.7 214.9 169.8 232.9 129.8 197.7 187.1 207.0 164.8 224.4 125.5 190.1 181.4 199.0 159.7 215.7 121.1
85 214.5 209.3 221.6 192.9 234.5 164.0 207.1 203.4 213.7 187.4 226.1 159.2 199.4 197.2 205.6 181.8 217.5 154.2
90 224.5 223.5 229.9 211.0 239.6 189.3 216.9 216.9 222.0 205.2 231.2 184.0 209.2 209.2 213.8 199.2 222.6 178.6
75 200.0 177.7 213.3 143.1 231.9 84.3 192.4 172.2 205.0 138.4 223.0 80.4 184.6 166.6 196.5 133.5 213.9 76.4
80 209.1 199.3 217.9 175.4 234.5 134.2 201.5 193.4 209.7 170.1 225.7 129.6 193.7 187.3 201.3 164.7 216.7 124.9
85 219.3 216.7 225.4 199.4 237.1 169.6 211.6 210.4 217.2 193.6 228.5 164.4 203.7 203.7 208.8 187.8 219.6 159.2
90 229.9 229.9 234.4 218.4 243.1 195.9 222.0 222.0 226.2 212.3 234.4 190.3 214.0 214.0 217.7 206.0 225.5 184.6
75 202.2 182.2 214.1 146.4 231.3 86.3 194.3 176.4 205.5 141.4 222.2 82.2 186.2 170.5 196.7 136.2 213.5 77.8
8800
80 212.2 204.7 219.7 179.9 235.0 137.6 204.3 198.5 211.3 174.3 226.0 132.7 196.1 192.1 202.6 168.5 217.0 127.7
85 223.1 223.0 228.1 204.8 238.7 174.1 215.0 215.0 219.6 198.8 229.7 168.7 206.8 206.8 211.0 192.6 220.5 163.1
90 234.2 234.2 237.8 224.7 245.6 201.4 226.0 226.0 229.3 218.3 236.6 195.5 217.6 217.6 220.5 211.7 227.4 189.5
75 203.4 185.6 216.0 148.7 233.2 87.3 195.1 179.5 207.0 143.3 224.1 82.8 186.7 173.3 198.0 137.9 213.0 78.1
9600
80 214.2 209.1 220.5 183.2 236.2 139.9 205.9 202.6 211.8 177.4 227.0 134.7 197.5 195.9 202.8 171.3 218.0 129.4
85 225.7 225.7 229.8 209.2 239.2 177.5 217.4 217.4 221.0 202.9 229.9 171.8 208.9 208.9 212.0 196.4 223.0 165.9
90 237.4 237.4 240.2 229.9 246.9 205.8 228.9 228.9 231.3 223.2 237.6 199.6 220.2 220.2 222.3 216.3 228.1 193.3
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 4000, 4800, and 5600 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC028AC-EN 69
Performance Data
Table 39. Gross cooling capacities 20 tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD240G3,4,W (Digit 22 = B)
Air
Flow cfm (a)
4000
5200
6400
7200
8000
8800
9600
85
61
Ambient Temperature
95
Entering Wet Bulb
67 73
105
Ent
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 203.7 145.0 228.5 96.2 259.7 90.9 193.4 139.5 217.0 92.5 247.0 86.4 182.4 133.4 204.8 88.3 233.5 81.7
80 206.0 171.4 227.3 134.7 254.8 89.2 195.8 164.9 215.8 130.0 242.1 84.7 184.8 157.8 203.6 124.6 228.6 80.0
85 210.1 191.8 227.8 167.0 251.7 118.8 199.9 184.2 216.3 161.3 239.0 114.9 189.0 176.0 204.1 154.9 225.5 110.4
90 216.1 206.0 230.1 193.2 250.4 157.1 205.9 197.4 218.6 186.5 237.7 152.1 194.9 188.2 206.4 179.1 224.2 146.5
75 218.6 159.9 241.6 108.8 271.0 94.8 207.5 153.9 229.3 104.6 257.4 90.1 195.7 147.3 216.2 99.8 243.0 85.1
80 222.2 188.3 241.6 149.2 267.3 93.6 211.1 181.3 229.3 144.0 253.7 88.8 199.3 173.6 216.2 138.2 239.4 83.8
85 227.6 210.6 243.4 183.5 265.5 133.0 216.5 202.5 231.1 177.3 251.9 128.6 204.7 193.8 218.0 170.4 237.6 123.5
90 234.8 226.8 247.0 211.7 265.4 173.2 223.7 217.7 234.6 204.4 251.9 167.7 211.9 207.9 221.6 196.5 237.5 161.6
75 231.3 173.2 252.5 119.7 280.0 98.0 219.3 166.7 239.3 115.1 265.5 92.9 206.6 159.6 225.3 109.8 250.3 87.6
80 236.2 203.6 253.7 162.1 277.6 97.2 224.2 196.0 240.5 156.4 263.2 93.4 211.5 187.9 226.6 150.1 248.0 88.8
85 242.8 227.8 256.8 198.4 277.0 145.5 230.9 219.3 243.6 191.6 262.6 140.6 218.2 210.0 229.7 184.2 247.4 135.0
90 251.2 245.9 261.6 228.5 278.2 187.7 239.3 236.3 248.4 220.7 263.8 181.7 226.7 226.1 234.5 212.3 248.6 175.1
75 238.5 181.2 258.5 126.2 284.8 99.7 226.0 174.4 244.7 121.2 269.7 94.4 212.7 166.9 230.2 115.5 253.9 88.9
80 244.2 212.9 260.6 169.9 283.2 103.4 231.7 205.0 246.8 163.8 268.2 99.2 218.5 196.5 232.3 157.1 252.4 94.3
85 251.7 238.4 264.4 207.4 283.5 153.0 239.2 229.5 250.7 200.3 268.4 147.7 226.0 220.0 236.2 192.6 252.7 141.8
90 261.0 257.9 270.1 238.9 285.5 196.5 248.5 247.9 256.3 230.7 270.5 190.2 235.3 235.3 241.9 222.0 254.7 183.2
75 244.8 188.5 263.5 131.9 288.6 101.0 231.7 181.3 249.2 126.5 272.9 95.5 217.8 173.5 234.1 120.5 256.6 89.8
80 251.3 221.5 266.4 176.9 287.8 108.9 238.2 213.2 252.1 170.5 272.2 104.3 224.4 204.4 237.0 163.5 255.9 99.1
85 259.6 248.3 271.1 215.8 288.9 159.8 246.5 239.1 256.8 208.3 273.3 154.2 232.7 229.2 241.7 200.2 257.0 147.9
90 269.7 269.0 277.6 248.5 291.8 204.5 256.7 256.7 263.3 240.0 276.2 197.9 242.9 242.9 248.2 230.9 259.9 190.6
75 250.0 195.1 267.5 136.9 291.3 102.0 236.3 187.5 252.6 131.2 275.2 96.3 221.9 179.4 236.9 124.9 258.2 90.4
80 257.4 229.3 271.3 183.2 291.5 113.6 243.7 220.8 256.4 176.5 275.3 108.7 229.3 211.6 240.7 169.1 258.4 103.2
85 266.5 257.5 276.8 223.4 293.4 165.8 252.9 247.9 261.9 215.6 277.2 159.9 238.5 237.7 246.3 207.2 260.3 153.3
90 277.5 277.5 284.1 257.4 297.1 211.9 263.8 263.8 269.2 248.6 280.9 204.9 249.5 249.5 253.6 239.2 264.0 197.3
75 254.3 200.9 270.6 141.2 293.1 102.6 240.0 193.1 255.1 135.2 276.4 96.7 225.0 184.6 238.8 128.5 258.9 90.6
80 262.5 236.5 275.1 188.8 294.1 117.7 248.2 227.6 259.7 181.7 277.4 112.4 233.3 218.1 243.4 174.0 259.9 106.5
85 272.4 266.0 281.5 230.3 296.8 171.2 258.2 256.0 266.0 222.2 280.1 164.9 243.3 243.3 249.8 213.4 262.6 157.9
90 284.2 284.2 289.6 265.7 301.4 218.6 270.0 270.0 274.2 256.5 284.7 211.2 255.1 255.1 258.0 246.7 267.2 203.2
70 RT-PRC028AC-EN
Performance Data
Table 39. Gross cooling capacities 20 tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD240G3,4,W (Digit 22 = B)
Air
Flow cfm (b)
Ent
DB 61
115
67 73 61
Ambient Temperature
120
Entering Wet Bulb
67 73 61
125
67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
4000
5200
6400
7200
75 170.7 126.7 191.8 83.3 219.2 76.7 164.5 123.1 185.0 80.6 211.8 74.1 158.2 119.3 178.1 77.8 204.2 71.5
80 173.1 150.0 190.6 118.7 214.4 75.0 166.9 145.9 183.8 115.5 207.0 72.4 160.6 141.6 176.8 112.1 199.4 69.8
85 177.3 167.2 191.1 147.9 211.3 105.2 171.1 162.6 184.4 144.2 203.9 102.4 164.8 157.7 177.4 140.3 196.3 99.4
90 183.2 178.3 193.5 171.0 210.0 140.3 177.1 173.1 186.7 166.8 202.6 137.0 170.8 167.8 179.8 162.3 195.1 133.5
75 183.1 140.0 202.3 94.4 227.9 79.8 176.5 136.2 195.1 91.4 220.1 77.0 169.7 132.1 187.7 88.3 212.0 74.2
80 186.7 165.3 202.4 131.7 224.3 78.5 180.1 160.9 195.2 128.2 216.5 75.8 173.4 156.4 187.8 124.6 208.4 73.0
85 192.1 184.5 204.2 162.9 222.5 117.8 185.6 179.6 197.0 158.9 214.7 114.7 178.8 174.5 189.6 154.7 206.7 111.5
90 199.4 197.5 207.8 187.9 222.5 154.9 192.8 192.1 200.6 183.4 214.6 151.3 186.1 186.1 193.2 178.7 206.6 147.5
75 193.2 151.8 210.6 103.8 234.3 82.0 186.2 147.7 203.0 100.6 226.1 79.1 179.0 143.4 195.2 97.2 217.6 76.2
80 198.1 179.1 211.9 143.1 232.0 83.6 191.1 174.4 204.3 139.3 223.7 80.8 183.9 169.6 196.5 135.4 215.3 77.8
85 204.8 200.2 215.0 176.2 231.4 128.8 197.8 195.0 207.4 172.0 223.2 125.5 190.6 189.7 199.5 167.5 214.8 122.0
90 213.3 213.3 219.8 203.2 232.7 167.8 206.3 206.3 212.2 198.5 224.4 164.0 199.1 199.1 204.4 193.5 216.0 160.0
75 198.7 158.8 214.9 109.2 237.4 83.1 191.4 154.5 207.0 105.8 228.9 80.1 183.9 150.0 198.9 102.3 220.1 77.0
80 204.4 187.3 217.0 149.8 235.9 88.8 197.2 182.5 209.1 145.9 227.4 85.8 189.7 177.5 201.0 141.8 218.6 82.6
85 212.0 209.8 220.9 184.2 236.2 135.3 204.7 204.4 213.0 179.8 227.6 131.7 197.2 197.2 204.9 175.2 218.9 128.1
90 221.3 221.3 226.6 212.5 238.2 175.6 214.0 214.0 218.7 207.6 229.7 171.6 206.6 206.6 210.6 202.5 221.0 167.4
8000
8800
75 203.2 165.0 218.2 113.9 239.5 83.8 195.7 160.6 210.0 110.3 230.6 80.7 187.9 155.9 201.6 106.6 221.6 77.6
80 209.8 194.9 221.2 155.8 238.8 93.2 202.2 189.9 213.0 151.7 230.0 90.1 194.5 184.7 204.6 147.5 221.0 86.7
85 218.2 218.2 225.9 191.5 239.9 141.0 210.6 210.6 217.7 186.9 231.1 137.3 202.9 202.9 209.3 182.2 222.1 133.5
90 228.3 228.3 232.4 221.2 242.8 182.7 220.8 220.8 224.2 216.0 234.0 178.4 213.0 213.0 215.9 210.8 225.0 174.1
75 206.8 170.6 220.5 117.9 240.6 84.2 198.9 165.9 212.0 114.2 231.4 81.0 190.9 161.1 203.3 110.3 222.1 77.7
80 214.2 201.7 224.3 161.1 240.7 97.0 206.3 196.6 215.8 156.8 231.6 93.6 198.3 191.2 207.1 152.4 222.3 90.1
85 223.4 223.4 229.9 198.1 242.7 146.0 215.5 215.5 221.4 193.3 233.6 142.2 207.5 207.5 212.7 188.4 224.3 138.1
90 234.3 234.3 237.2 229.1 246.4 189.0 226.5 226.5 228.8 223.8 237.3 184.6 217.9 217.9 220.1 218.3 228.0 180.1
9600
75 209.3 175.4 221.8 121.2 240.6 84.2 201.2 170.6 213.0 117.3 231.2 80.9 192.8 165.6 204.1 113.2 221.6 77.6
80 217.5 207.9 226.4 165.6 241.6 100.0 209.4 202.5 217.7 161.2 232.2 96.5 201.1 197.0 208.7 156.6 222.6 92.8
85 227.6 227.6 232.8 204.0 244.4 150.4 219.4 219.4 224.1 199.1 235.0 146.3 211.1 211.1 215.1 194.0 225.4 142.1
90 239.4 239.4 241.0 236.2 249.0 194.6 230.0 230.0 232.3 230.8 239.6 190.1 223.3 223.3 223.3 223.3 230.0 185.3
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity (a)
(a)For 4000, and 5200 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)For 4000, and 5200 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC028AC-EN 71
Performance Data
Table 40. Gross cooling capacities 25 tons three phase high efficiency T/YH*300G3,4,W (stage 1)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
4000
5000
6000
7000
8000
75
80
85
90
75
80
85
90
75
80
80.5 78.0 85.7 62.9 93.7 32.5 75.1 73.7 80.0 59.3 87.7 29.5
85.2 85.2 87.8 78.2 94.6 59.2 79.7 79.7 82.1 74.1 88.6 55.8
90.1 90.1 91.3 88.2 95.4 76.5 84.6 84.6 85.6 83.8 89.4 72.6
94.9 94.9 95.3 95.3 97.8 88.2 89.3 89.3 89.5 89.5 91.8 83.9
83.0 82.1 87.6 67.4 95.0 37.4 77.3 77.3 81.6 63.4 88.7 34.1
88.1 88.1 90.2 82.7 96.3 64.2 82.3 82.3 84.2 78.3 90.0 60.3
93.3 93.3 94.0 92.9 97.6 81.6 87.5 87.5 88.0 88.0 91.3 77.2
98.3 98.3 98.3 98.3 100.3 93.3 92.0 92.0 92.2 92.2 94.0 88.7
85.1 85.1 89.0 71.1 95.7 41.5 79.1 79.1 82.7 66.7 89.2 37.8
90.5 90.5 92.0 86.5 97.5 68.3 84.5 84.5 85.8 81.6 90.9 64.1
85
90
75
80
96.0 96.0 96.2 96.2 99.2 85.8 89.9 89.9 89.9 89.9 92.7 81.1
99.8 99.8 100.8 100.8 102.3 97.7 94.0 94.0 94.4 94.4 95.8 92.6
86.6 86.6 89.8 74.0 96.0 44.9 80.3 80.3 83.3 69.2 89.5 40.7
92.4 92.4 93.4 89.5 98.2 71.7 86.1 86.1 86.8 84.2 91.3 67.0
85 96.0 96.0 97.9 97.9 100.4 89.2 91.0 91.0 91.3 91.3 93.6 84.1
90 101.0 101.0 102.8 102.8 103.8 101.2 95.8 95.8 96.1 96.1 97.0 95.8
75
80
87.7 87.7 90.2 76.1 98.2 47.4 81.1 81.1 83.3 70.9 91.0 42.9
93.8 93.8 94.2 91.6 98.4 74.2 87.2 87.2 87.3 86.0 92.0 69.1
85 98.4 98.4 99.1 99.1 101.0 91.8 92.0 92.0 92.2 92.2 93.9 86.3
90 103.7 103.7 104.2 104.2 104.8 104.0 96.0 96.0 97.3 97.3 97.7 97.7
8750
75
80
88.1 88.1 91.0 77.1 98.5 48.8 81.3 81.3 84.0 71.6 92.0 43.9
94.0 94.0 94.5 92.7 99.0 75.6 87.3 87.3 87.4 86.7 93.5 70.2
85 99.0 99.0 99.7 99.7 101.2 93.2 92.4 92.4 92.6 92.6 95.0 87.4
90 104.0 104.0 105.0 105.0 105.2 105.2 97.0 97.0 97.8 97.8 97.9 97.9
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 4000, 5000, 6000, and 7000 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
72 RT-PRC028AC-EN
Performance Data
Table 41. Gross cooling capacities 25 tons three phase high efficiency T/YH*300G3,4,W (stage 2)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
4000
5000
6000
7000
8000
75 135.6 118.7 146.9 92.7 156.4 43.8 127.9 113.4 138.5 88.3 147.4 40.5
80 140.7 132.3 148.2 116.5 159.0 84.6 132.9 126.3 139.8 111.3 150.0 80.4
85 146.9 142.2 152.0 132.5 161.5 111.5 138.9 135.7 143.6 126.7 152.5 106.4
90 153.5 150.3 157.2 144.1 164.1 129.8 145.3 143.4 148.6 137.8 155.0 124.2
75 141.2 127.5 151.3 101.4 165.2 52.4 133.0 121.6 142.4 96.4 155.5 48.5
80 147.0 141.5 153.5 125.6 165.8 93.7 138.7 134.9 144.5 119.9 156.2 88.8
85 153.7 151.8 157.9 142.1 166.4 121.0 145.2 144.8 149.0 135.7 156.8 115.4
90 160.7 160.3 163.6 154.1 169.7 139.7 152.0 152.0 154.5 147.2 160.0 133.5
75 145.8 134.8 154.6 108.6 167.3 59.5 137.0 128.2 145.1 103.0 157.1 55.0
80 152.2 149.2 157.6 133.2 168.7 101.2 143.4 142.0 148.2 126.9 158.6 95.8
85 159.4 159.4 162.7 150.1 170.2 128.9 150.4 150.4 153.3 143.2 160.1 122.7
90 166.8 166.8 169.0 162.6 174.1 148.1 157.6 157.6 159.3 155.1 164.0 141.3
75 149.2 140.5 156.8 114.2 168.3 65.0 140.0 133.4 146.9 108.1 157.6 59.9
80 156.3 155.3 160.7 139.3 170.6 107.2 147.0 147.0 150.8 132.4 160.0 101.2
85 164.0 164.0 166.5 156.7 172.9 135.4 154.6 154.6 156.5 149.1 162.3 128.6
90 171.8 171.8 173.2 169.5 177.5 155.0 162.1 162.1 163.1 161.4 166.8 147.6
75 151.6 144.7 158.0 118.3 169.0 69.0 141.9 137.0 147.5 111.6 158.0 63.4
80 159.4 159.4 162.7 143.9 171.4 111.7 149.6 149.6 152.2 136.4 160.3 105.1
85 167.6 167.6 169.1 161.6 174.5 140.3 157.6 157.6 158.7 153.5 163.5 132.9
90 175.7 175.7 176.4 174.9 179.8 160.3 165.5 165.5 165.7 165.7 168.6 152.3
8750
75 152.7 146.8 158.1 120.4 171.3 71.0 142.6 138.7 147.9 113.2 159.6 64.9
80 161.0 161.0 163.4 146.3 172.0 114.0 150.8 150.8 152.7 138.3 161.0 107.0
85 169.5 169.5 170.4 164.3 175.1 142.9 159.2 159.2 159.6 155.8 163.6 135.1
90 178.0 178.0 178.0 177.9 180.8 163.3 166.0 167.4 167.0 167.0 169.3 154.9
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 4000, 5000, 6000, and 7000 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC028AC-EN 73
Performance Data
Table 42. Gross cooling capacities 25 tons three phase high efficiency T/YH*300G3,4,W (stage 3)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
4000
5000
6000
7000
8000
75 188.9 150.3 205.8 121.4 226.6 71.4 179.7 145.2 195.3 117.2 214.8 68.3
80 193.3 167.2 208.8 147.0 228.3 111.8 184.1 161.3 198.4 142.0 216.6 107.6
85 199.5 180.7 211.8 165.8 230.0 140.0 190.3 174.2 201.4 160.0 218.4 135.0
90 207.0 192.0 217.1 180.3 231.7 160.6 197.5 185.0 206.7 174.0 220.2 154.9
75 199.5 162.2 218.5 131.4 234.4 79.3 189.4 156.2 206.9 126.4 221.8 75.4
80 204.9 180.5 219.0 158.8 237.2 121.8 194.9 173.8 207.8 153.0 224.7 116.9
85 212.0 195.3 223.1 179.1 240.0 151.8 202.0 188.0 211.9 172.5 227.6 146.0
90 220.2 207.7 229.3 194.9 242.7 173.9 209.9 199.9 218.0 187.7 230.4 167.4
75 208.4 172.8 225.7 140.2 247.8 86.1 197.5 166.0 213.4 134.4 234.0 81.4
80 214.8 192.7 227.6 169.4 248.1 130.7 204.1 185.1 215.6 162.7 234.6 124.9
85 222.8 208.7 232.7 191.2 248.3 162.4 212.0 200.6 220.8 183.8 235.1 155.8
90 231.7 222.2 239.8 208.3 252.1 186.0 220.6 213.6 227.8 200.3 239.0 178.7
75 215.6 182.2 231.3 147.8 251.9 91.6 204.0 174.6 218.2 141.2 237.3 86.1
80 223.2 203.6 234.5 178.8 253.4 138.3 211.6 195.2 221.7 171.3 239.1 131.7
85 232.0 220.9 240.7 202.1 255.0 171.8 220.4 211.9 228.0 193.8 241.0 164.4
90 241.6 235.5 248.7 220.5 259.9 197.0 229.7 226.1 235.9 211.7 246.0 188.8
75 221.2 190.4 235.3 154.2 254.3 96.0 208.8 181.9 221.3 146.7 238.9 89.6
80 229.8 213.3 239.8 187.0 257.1 144.7 217.5 204.1 226.2 178.6 242.0 137.3
85 239.6 231.8 247.1 211.8 260.0 180.0 227.1 222.1 233.5 202.7 245.2 171.7
90 249.9 247.6 255.9 231.5 266.0 206.7 237.2 237.2 242.3 221.8 251.3 197.7
8750
75 224.3 195.7 237.2 158.2 255.0 98.4 211.3 186.6 222.6 150.1 239.0 91.4
80 233.7 219.7 242.7 192.3 258.9 148.8 220.8 209.9 228.5 183.3 243.1 140.7
85 244.1 239.3 250.8 218.2 262.7 185.4 231.1 228.9 236.6 208.5 247.3 176.5
90 255.0 255.0 260.3 238.9 269.5 213.2 241.7 241.7 246.1 228.6 254.2 203.5
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 4000, 5000, 6000, and 7000 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
74 RT-PRC028AC-EN
Performance Data
Table 43. Gross cooling capacities 25 tons three phase high efficiency T/YH*300G3,4,W (full load)
Air
Flow cfm (a)
5000
6000
7000
8000
9000
10000
11000
85
Ambient Temperature
95 105
Ent Entering Wet Bulb
DB 61 67 73 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 244.4 192.5 271.7 152.0 293.2 82.9 232.4 184.9 257.9 146.3 278.4 79.2 219.4 176.7 243.2 139.9 262.5 74.8
80 250.0 215.3 270.3 187.5 295.4 139.2 238.0 206.6 256.8 180.3 280.5 133.8 225.0 197.3 242.2 172.5 264.5 127.7
85 258.5 233.2 274.2 213.2 297.6 178.4 246.2 223.6 260.6 204.8 282.6 171.4 232.8 213.3 246.0 195.8 266.5 163.9
90 268.6 248.1 281.3 232.8 299.8 206.6 255.9 237.7 267.4 223.5 284.7 198.6 242.1 226.7 252.6 213.6 268.6 189.9
75 255.4 206.3 281.1 164.5 301.6 93.9 242.7 198.1 266.6 158.1 286.0 89.5 228.9 189.1 251.1 150.9 269.3 84.3
80 262.0 230.2 280.9 201.3 304.7 151.7 249.2 220.8 266.6 193.4 289.1 145.6 235.5 210.7 251.4 184.8 272.3 138.7
85 271.2 249.0 285.7 228.0 307.8 192.1 258.2 238.7 271.4 219.0 292.1 184.5 244.1 227.7 256.1 209.2 275.3 176.2
90 282.0 264.7 293.6 248.6 311.0 221.4 268.5 253.6 279.0 238.6 295.1 212.7 253.9 241.8 263.4 227.9 278.3 203.3
75 265.0 218.8 289.1 175.7 308.5 103.5 251.6 209.8 273.9 168.5 292.2 98.3 237.1 200.1 257.7 160.6 274.8 92.5
80 272.6 243.7 290.1 213.7 312.6 162.9 259.1 233.6 275.1 205.1 296.2 156.0 244.6 222.8 259.1 195.8 278.8 148.4
85 282.6 263.5 295.9 241.5 316.7 204.5 268.8 252.4 280.9 231.7 300.2 196.1 254.0 240.6 264.8 221.2 282.7 187.1
90 293.9 279.9 304.6 263.0 320.8 234.9 279.7 268.1 289.2 252.2 304.2 225.4 264.4 255.6 272.9 240.8 286.7 215.3
75 273.3 229.9 295.7 185.4 324.1 111.8 259.1 220.1 279.8 177.5 306.4 105.9 243.9 209.7 262.8 168.9 287.8 99.3
80 281.8 255.9 298.0 224.7 324.2 172.6 267.6 245.0 282.2 215.4 306.7 165.0 252.3 233.5 265.5 205.3 288.3 156.6
85 292.5 276.6 304.7 253.7 324.2 215.6 278.0 264.7 288.9 243.1 307.0 206.4 262.5 252.2 272.1 231.9 288.7 196.7
90 304.5 293.8 314.1 276.0 329.2 247.0 289.5 281.2 298.1 264.5 311.9 236.8 273.5 268.0 281.0 252.4 293.6 225.9
75 280.1 239.6 301.0 193.8 327.8 118.7 265.2 229.1 284.3 185.2 309.4 112.0 249.3 218.0 266.6 175.8 290.0 104.7
80 289.6 266.7 304.4 234.4 329.1 181.0 274.7 255.1 288.0 224.3 310.9 172.6 258.7 242.8 270.5 213.5 291.7 163.6
85 301.1 288.3 312.1 264.4 330.3 225.2 285.9 275.7 295.6 253.1 312.3 215.4 269.6 262.5 278.1 241.2 293.3 204.9
90 313.7 306.3 322.3 287.7 336.3 257.8 297.9 293.0 305.5 275.5 318.3 246.8 281.2 279.0 287.7 262.6 299.2 235.1
75 285.6 247.9 304.9 200.8 330.2 124.2 270.0 236.7 287.4 191.4 311.0 116.8 253.3 224.8 269.0 181.3 290.9 108.7
80 296.1 276.1 309.5 242.7 332.6 188.0 280.4 263.8 292.3 231.9 313.7 178.9 263.6 250.7 274.1 220.3 293.7 169.1
85 308.3 298.6 318.2 273.8 335.0 233.5 292.3 285.3 300.9 261.7 316.3 222.9 275.3 271.3 282.6 249.0 296.6 211.7
90 321.4 317.4 329.1 298.0 342.0 267.1 305.0 303.3 311.6 285.0 323.2 255.4 287.5 287.5 293.0 271.4 303.4 243.0
75 289.7 254.9 307.3 206.5 331.1 128.3 273.3 243.0 289.2 196.3 311.2 120.2 255.9 230.3 270.0 185.5 291.5 111.3
80 301.1 284.2 313.2 249.6 334.7 193.7 284.7 271.1 295.2 238.0 315.1 183.8 267.2 257.3 276.3 225.8 294.4 173.2
85 314.1 307.6 322.8 281.8 338.3 240.4 297.4 293.5 304.8 269.0 318.9 229.1 279.6 278.8 285.8 255.6 298.4 217.1
90 327.9 327.1 334.5 306.9 346.3 275.1 310.7 310.7 316.3 293.2 326.8 262.7 292.5 292.5 297.0 278.8 306.2 249.5
RT-PRC028AC-EN 75
Performance Data
Table 43. Gross cooling capacities 25 tons three phase high efficiency T/YH*300G3,4,W (full load)
Air
Flow cfm
5000
115
Ambient Temperature
120 125
Ent
DB 61 67 73 61
Entering Wet Bulb
67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 205.4 167.9 227.4 132.8 245.5 69.7 198.0 163.2 219.2 129.0 236.7 66.9 190.4 158.3 210.7 125.0 227.6 64.0
80 210.9 187.2 226.7 164.0 247.5 120.9 203.5 182.0 218.5 159.5 238.6 117.2 195.9 176.5 210.1 154.8 229.5 113.4
85 218.5 202.3 230.4 186.2 249.5 155.7 211.0 196.6 222.2 181.1 240.6 151.3 203.2 190.7 213.8 175.8 231.4 146.8
90 227.3 215.0 236.7 202.9 251.5 180.5 219.5 208.8 228.4 197.4 242.5 175.5 211.5 202.5 219.8 191.6 233.4 170.4
75 214.2 179.5 234.6 143.1 251.7 78.5 206.5 174.4 226.0 138.9 242.5 75.3 198.5 169.2 217.1 134.6 233.0 72.0
6000
7000
8000
9000
10000
80 220.7 199.9 235.1 175.6 254.6 131.2 212.9 194.3 226.6 170.7 245.4 127.1 204.9 188.5 217.8 165.6 235.9 122.9
85 229.0 216.0 239.7 198.8 257.5 167.2 221.1 209.8 231.2 193.3 248.3 162.5 213.0 203.6 222.4 187.7 238.8 157.6
90 238.4 229.3 246.8 216.5 260.5 193.1 230.3 222.9 238.1 210.6 251.2 187.8 221.9 216.2 229.2 204.5 241.6 182.3
75 221.7 189.7 240.4 152.0 256.4 85.9 213.6 184.3 231.5 147.5 246.8 82.4 205.2 178.7 222.2 142.8 237.0 78.7
80 229.1 211.3 242.1 185.8 260.3 140.1 220.9 205.2 233.2 180.5 250.7 135.7 212.6 199.1 224.1 175.1 240.8 131.1
85 238.2 228.2 247.7 210.1 264.2 177.4 229.9 221.7 238.8 204.3 254.6 172.3 221.4 215.1 229.6 198.2 244.7 167.0
90 248.2 242.4 255.6 228.7 268.1 204.4 239.7 235.5 246.5 222.4 258.4 198.7 230.9 228.5 237.2 215.9 248.5 192.8
75 227.7 198.6 244.9 159.6 268.2 92.0 219.2 192.8 235.5 154.6 258.0 88.1 210.5 186.8 225.9 149.6 247.5 84.0
80 236.1 221.2 247.7 194.6 268.8 147.6 227.6 214.8 238.5 189.0 258.7 142.8 218.8 208.3 229.0 183.2 248.4 137.9
85 245.9 239.0 254.3 220.0 269.5 186.2 237.3 232.2 245.0 213.8 259.5 180.8 228.4 225.2 235.5 207.4 249.2 175.1
90 256.5 254.0 262.9 239.5 274.3 214.3 247.7 246.8 253.5 232.9 264.3 208.2 238.5 238.5 243.9 226.0 254.0 202.0
75 232.4 206.1 247.9 165.7 269.7 96.6 223.5 200.0 238.2 160.5 259.1 92.4 214.4 193.6 228.2 155.0 248.3 87.9
80 241.7 229.8 252.0 202.0 271.5 153.8 232.8 223.0 242.4 196.0 261.0 148.6 223.7 216.1 232.5 189.9 250.3 143.3
85 252.3 248.5 259.5 228.5 273.4 193.7 243.3 241.3 249.9 221.9 263.0 187.8 234.1 233.9 240.0 215.2 252.4 181.8
90 263.5 263.5 268.9 249.0 279.2 222.8 254.3 254.3 259.1 241.9 268.8 216.4 244.8 244.8 249.1 234.7 258.1 209.8
75 235.6 212.3 249.6 170.5 269.8 99.9 226.4 205.7 239.5 164.9 260.5 95.3 217.0 199.0 229.2 159.1 249.2 90.5
80 245.9 237.0 254.9 208.1 272.8 158.6 236.7 229.9 244.9 201.7 262.0 153.1 227.2 222.6 234.6 195.2 250.9 147.4
85 257.3 256.6 263.3 235.7 275.9 199.7 247.9 247.9 253.3 228.7 265.1 193.5 238.3 238.3 243.1 221.6 254.1 187.1
90 269.1 269.1 273.5 257.1 282.7 229.9 259.5 259.5 263.4 249.6 271.9 223.2 249.6 249.6 253.0 242.0 260.9 216.2
75 237.5 217.0 249.9 174.0 271.0 101.8 228.0 210.1 240.5 167.9 261.3 96.8 218.1 203.0 229.8 161.7 252.3 91.6
11000
80 248.8 242.8 256.3 212.8 274.0 162.0 239.2 235.3 246.0 206.1 263.6 156.1 229.3 227.7 235.4 199.2 253.4 150.1
85 260.9 260.9 265.8 241.4 277.0 204.4 251.2 251.2 255.4 234.1 265.9 197.9 241.2 241.2 244.8 226.6 254.5 191.1
90 273.3 273.3 276.7 263.8 284.7 235.7 263.3 263.3 266.2 256.0 273.6 228.5 253.1 253.1 255.4 248.0 262.2 221.2
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 5000, 6000, and 7000 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
76 RT-PRC028AC-EN
Performance Data
Table 44. Gross cooling capacities 25 tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD300G3,4,W (Digit 22 = B)
Air
Flow cfm (a)
5000
6500
8000
9000
10000
10500
11000
85
Ambient Temperature
95 105
Ent Entering Wet Bulb
DB 61 67 73 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 237.6 170.2 266.9 137.2 298.3 101.7 226.6 164.3 254.2 130.9 284.0 95.4 215.0 158.1 241.1 124.7 269.5 89.1
80 237.8 197.2 266.6 164.6 298.3 130.4 226.8 191.3 254.2 158.7 284.5 124.4 215.2 184.8 241.2 152.8 269.5 117.9
85 238.0 223.6 266.8 192.2 298.3 157.9 227.3 217.6 254.4 186.3 284.5 150.8 216.0 211.0 241.3 180.0 269.3 145.0
90 244.4 244.4 267.0 219.3 298.3 185.7 235.5 235.5 254.6 213.1 284.2 179.6 226.0 225.9 241.7 206.9 269.5 173.2
75 251.7 194.9 281.3 151.1 313.6 103.1 239.4 188.7 267.3 144.8 297.7 96.7 226.4 182.1 252.8 138.0 281.0 90.0
80 252.2 230.1 281.5 185.9 313.9 142.8 239.8 223.7 267.7 179.8 299.0 134.7 227.0 216.7 253.1 173.7 281.5 129.6
85 257.9 257.7 282.0 223.2 313.7 176.7 248.0 247.9 268.2 217.0 297.6 170.9 237.2 237.2 253.6 210.5 281.8 163.8
90 272.5 272.4 282.5 258.1 314.3 213.5 262.0 261.9 268.8 251.7 298.7 207.5 250.8 250.7 254.4 244.6 282.3 201.7
75 260.7 217.8 290.3 162.9 322.7 103.2 247.6 211.8 276.0 155.2 305.8 96.6 233.7 205.3 260.1 149.5 288.2 90.1
80 262.3 259.5 291.1 207.3 323.0 153.7 249.7 247.8 276.3 201.2 306.2 146.9 238.4 236.1 260.8 195.0 288.7 139.6
85 277.8 277.7 291.9 252.8 324.9 192.8 266.3 266.3 277.0 246.3 307.1 188.1 254.2 254.2 261.6 239.2 289.8 182.0
90 293.7 293.6 293.9 292.8 324.5 241.9 281.8 281.8 280.5 277.0 307.8 235.5 269.1 269.1 269.3 268.3 290.6 229.1
75 265.2 233.5 294.9 170.4 326.8 103.2 251.5 226.7 279.5 163.8 309.5 97.1 237.2 219.2 263.4 156.9 291.4 90.9
80 269.5 264.6 294.7 223.9 328.3 159.2 259.7 259.5 280.4 215.9 310.2 152.6 247.7 247.6 264.4 209.5 292.4 145.4
85 288.2 288.1 296.6 271.4 328.6 206.7 276.1 275.9 281.4 264.7 311.4 201.1 263.2 263.2 265.9 256.5 293.6 196.0
90 302.2 301.5 303.9 299.6 329.4 260.3 292.3 292.2 292.9 292.7 311.8 255.6 278.9 278.9 279.6 279.5 294.5 248.5
75 268.8 247.3 298.4 178.1 330.1 104.0 254.7 240.1 282.6 171.2 312.4 98.0 240.0 233.0 266.2 164.6 293.6 91.6
80 279.8 279.8 299.5 236.4 331.3 165.7 267.6 267.5 284.2 228.6 313.0 159.1 254.0 254.5 267.3 223.1 295.4 151.0
85 297.2 297.2 300.7 289.4 332.4 221.0 284.4 284.3 285.0 281.9 314.7 215.8 270.9 270.7 269.0 265.0 296.6 209.8
90 315.0 315.0 315.6 315.6 333.5 279.6 301.5 301.5 302.1 301.9 316.4 271.6 287.3 287.2 287.9 287.6 297.7 265.0
75 270.3 254.1 300.1 181.8 332.2 103.2 256.1 246.9 283.8 175.0 313.4 98.3 241.2 239.6 267.4 168.8 294.6 91.9
80 283.5 283.4 301.2 243.4 332.8 168.0 271.0 270.7 285.1 236.6 314.6 149.6 257.8 257.6 268.5 229.6 296.6 153.9
85 301.2 301.2 302.5 297.8 334.1 228.5 287.5 287.2 286.5 283.2 316.3 222.6 274.3 274.2 271.3 263.2 297.9 216.4
90 319.3 319.3 320.0 319.8 335.2 288.2 305.5 305.3 306.2 305.9 317.5 280.7 291.0 290.9 291.6 291.5 299.1 272.8
75 271.7 260.7 301.5 185.8 332.6 105.1 257.3 253.5 285.1 179.1 314.5 98.9 242.4 239.2 268.5 173.1 295.9 92.6
80 287.0 286.7 302.6 250.0 334.2 170.7 273.9 273.7 286.4 243.2 316.9 162.5 260.6 260.6 269.7 235.9 297.6 156.7
85 305.1 304.9 304.5 304.2 335.6 235.1 291.3 291.2 288.4 280.2 317.6 229.0 277.4 277.4 274.0 262.8 299.1 222.8
90 323.4 323.3 324.1 323.8 336.7 295.8 309.2 309.1 309.9 309.7 318.9 288.2 294.5 294.5 295.1 295.0 300.4 280.4
RT-PRC028AC-EN 77
Performance Data
Table 44. Gross cooling capacities 25 tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD300G3,4,W (Digit 22 = B)
Air
Flow cfm
5000
115
Ambient Temperature
120 125
Ent
DB 61 67 73 61
Entering Wet Bulb
67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 202.6 151.6 227.5 118.5 253.9 82.4 196.1 148.2 220.0 114.8 245.8 79.0 189.5 144.9 212.3 111.2 237.3 75.6
80 202.9 178.2 227.2 145.7 253.8 111.3 196.5 175.0 220.0 142.3 245.6 107.9 189.8 171.5 212.6 138.9 237.3 104.5
85 204.6 203.6 227.5 173.3 253.9 138.4 199.2 199.2 220.4 170.0 245.9 135.1 193.9 193.9 213.0 166.6 237.6 131.8
90 215.9 215.9 227.9 200.1 254.2 166.7 210.6 210.6 220.7 196.6 246.2 163.4 205.0 204.9 213.3 193.2 237.9 160.1
75 212.7 175.3 237.9 130.0 264.1 83.1 205.6 171.9 229.7 127.2 255.2 79.7 198.4 168.5 221.5 123.5 246.0 76.1
6500
8000
9000
10000
10500
80 214.0 209.1 238.0 167.4 264.3 122.8 207.2 205.4 230.1 164.0 255.6 119.4 200.5 199.9 222.1 160.6 246.4 116.0
85 225.8 225.7 238.7 203.5 265.1 157.2 219.7 219.6 230.7 199.9 256.2 153.7 213.5 213.5 222.7 196.3 247.2 150.4
90 238.9 238.9 240.2 236.6 265.6 195.5 232.7 232.6 232.7 232.0 256.8 192.1 226.1 226.1 226.1 225.3 247.8 188.5
75 219.2 198.0 244.4 141.6 269.9 83.7 211.7 194.1 235.6 139.0 260.8 80.6 204.1 190.2 227.1 135.5 251.1 77.2
80 227.1 227.0 244.7 188.9 271.1 132.5 220.8 220.8 236.4 185.6 261.6 128.7 214.1 214.1 227.9 182.0 252.2 125.1
85 241.4 241.3 245.6 232.1 271.9 176.3 234.7 234.6 237.3 228.3 262.7 173.5 227.8 227.7 228.8 224.1 253.2 170.8
90 255.9 255.8 256.4 256.2 272.7 223.1 248.8 248.8 249.4 249.3 263.5 219.9 241.6 241.6 242.1 242.1 254.1 216.4
75 222.3 211.8 247.1 150.1 272.7 84.4 214.6 208.1 238.5 146.8 263.2 81.0 206.8 204.1 229.7 143.2 253.2 77.4
80 234.7 234.5 247.9 202.7 274.0 137.8 228.0 227.7 239.4 199.2 265.6 132.5 220.9 220.7 230.7 195.4 255.1 130.9
85 249.7 249.5 249.2 248.6 275.2 190.4 242.6 242.5 241.3 238.4 265.8 187.3 235.2 235.1 233.6 228.6 256.1 184.1
90 264.8 264.8 265.3 265.1 276.2 241.1 257.5 257.3 258.0 257.7 266.8 237.2 249.8 249.7 250.3 250.1 257.1 233.0
75 224.8 224.5 249.4 158.3 274.8 84.8 217.2 214.2 240.6 155.1 265.0 81.9 209.8 204.0 231.7 152.2 254.7 80.2
80 241.0 241.0 250.5 215.8 277.5 141.3 233.9 233.9 241.8 212.1 267.0 140.3 226.6 226.4 232.8 208.4 257.0 136.7
85 256.6 256.6 254.1 246.2 277.8 203.4 249.2 249.2 247.5 240.9 268.3 200.1 241.5 241.4 241.8 241.5 258.3 196.6
90 272.5 272.5 272.9 272.9 279.0 256.9 264.7 264.7 265.2 265.1 269.4 252.9 256.6 256.6 257.1 256.9 259.5 249.1
75 226.2 222.1 250.4 162.6 275.7 85.3 218.8 211.8 241.5 159.9 265.6 83.7 211.7 204.3 232.6 157.1 255.4 82.4
80 243.8 243.8 251.6 222.3 277.7 147.0 236.6 236.4 242.8 218.6 268.0 143.5 229.1 228.8 234.2 213.6 258.0 140.1
85 259.7 259.7 258.1 251.8 279.0 209.7 252.1 251.9 252.5 252.2 269.3 206.4 244.3 244.1 244.7 244.3 259.3 203.0
90 275.9 275.8 276.3 276.2 280.7 263.7 267.9 267.8 268.4 268.1 270.5 261.0 259.7 259.6 260.1 259.8 260.6 257.1
75 227.7 219.7 251.2 167.7 276.4 87.2 220.8 212.4 242.4 164.9 266.3 86.0 214.6 210.1 233.3 161.8 256.1 84.1
11000
80 246.4 246.2 252.6 228.5 278.6 149.9 239.1 238.8 243.7 224.6 268.8 146.8 231.5 231.3 234.6 220.7 259.6 141.2
85 262.6 262.4 263.0 262.6 280.5 214.9 254.8 254.6 255.2 254.9 270.2 212.8 246.9 246.7 247.2 246.9 260.2 209.1
90 279.0 278.9 279.5 279.2 281.4 272.9 270.9 270.8 271.3 271.0 271.6 269.0 262.5 262.4 263.0 262.8 261.5 258.0
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 5000, 6000, and 7000 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
78 RT-PRC028AC-EN
Performance Data
Table 45. Evaporator fan performance 12½ tons TSD150G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive 3-hp Standard Motor & Drive
4000 461 0.60
522 0.79
575 0.98
624 1.18
667 1.37
707 1.56
743 1.75
773 1.90
802 2.05
4500 410 0.51
485 0.74
545 0.95
598 1.17
645 1.39
688 1.60
728 1.82
765 2.04
800 2.25
833 2.47
5000 437 0.64
509 0.89
569 1.14
621 1.38
667 1.62
710 1.86
749 2.10
786 2.34
821 2.58
853 2.82
5500 465 0.79
535 1.08
593 1.35
644 1.62
690 1.88
732 2.14
771 2.41
807 2.67
842 2.94
874 3.20
6000 493 0.97
561 1.28
618 1.58
668 1.87
713 2.16
754 2.45
793 2.75
829 3.03
863 3.31 896 (a)
3-hp Standard Motor & High Static Drive
3.60
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive
4000 826 2.17
856 2.33
880 2.47
902 2.60
923 2.72
944 2.84
963 2.96
982 3.08 1002 3.20
1021 3.32
4500 858 2.64
888 2.82
909 2.96
932 3.11
958 3.29
981 3.46 1000 3.59 1020 3.73 1038 3.87
1056 4.00
5000 885 3.06
916 3.31
941 3.51
963 3.69
991 3.89 1010 4.06 1029 4.22 1051 4.40 1074 4.60
1094 4.78
5500 906 3.46
936 3.73
965 4.00
993 4.26 1019 4.53 1040 4.73 1061 4.93 1087 5.15 1104 5.34
1122 5.52
6000 927 3.89
957 4.18
986 4.47 1014 4.76 1041 5.06 1066 5.34 1091 5.64
-
5-hp Oversized Motor & Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
8.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
(a)5-hp Oversized Motor & Drive
RT-PRC028AC-EN 79
Performance Data
Table 46. Evaporator fan performance 12½ tons TSH150G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
4000
4500
-
-
3-hp Standard Motor & Low Static Drive
-
-
3-hp Standard Motor & Drive
3 hp
Standard
Motor & High
Static Drive
494 0.80
558 1.02
613 1.23
662 1.44
707 1.64
749 1.84
787 2.04
824 2.24
851 2.40
521 1.00
584 1.26
638 1.50
686 1.74
731 1.98
772 2.21
811 2.43
847 2.66
882 2.88
5000 475 0.92
549 1.24
610 1.53
663 1.80
711 2.08
756 2.34
797 2.61
835 2.86
871 3.12
905 3.37
5500 506 1.15
578 1.50
637 1.83
690 2.15
737 2.45
781 2.75
821 3.04
859 3.34
895 3.62
929 3.91
6000 538 1.42
607 1.81
666 2.18
717 2.53
764 2.87
807 3.20
846 3.52
884 3.85
920 4.17
953 4.48
5-hp Oversized Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive
4000 882 2.63
909 2.80
935 2.99
961 3.19
991 3.42 1017 3.65 1043 3.88 1069 4.12 1093 4.35
1116 4.58
4500 915 3.10
941 3.27
968 3.53
994 3.75 1016 3.94 1042 4.18 1063 4.36 1090 4.62 1117 4.89
1139 5.13
5000 938 3.62
969 3.86
999 4.11 1029 4.36 1049 4.52 1074 4.82 1100 5.10 1118 5.28 1141 5.54
1162 5.77
5500 961 4.18
993 4.46 1022 4.73 1051 5.00 1080 5.28 1107 5.55
-
6000 986 4.79 1016 5.09 1046 5.40 1076 5.71
-
5-hp Oversized Motor & Drive
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
8.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
80 RT-PRC028AC-EN
Performance Data
Table 47. Evaporator fan performance 12½ tons with gas heat YSD150G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive 3-hp Standard Motor & Drive
4000 511 0.75
559 0.92
601 1.08
639 1.24
673 1.40
706 1.56
736 1.71
763 1.85
793 2.00
816 2.12
4500 562 1.02
607 1.21
647 1.40
683 1.58
717 1.76
748 1.94
777 2.11
805 2.29
831 2.46
854 2.61
5000 614 1.35
656 1.56
694 1.77
729 1.98
761 2.18
791 2.38
820 2.57
847 2.77
873 2.97
898 3.17
5500 667 1.74
706 1.98
742 2.21
776 2.44
807 2.67
836 2.89
863 3.11
890 3.32
915 3.55
940 3.76
6000 720 2.21
757 2.48
791 2.73
823 2.98
853 3.23
881 3.47
908 3.72
934 3.96
959 4.20
982 4.43
3-hp Standard Motor & High Static Drive 5-hp Oversized Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive
4000 844 2.27
868 2.41
889 2.52
910 2.64
929 2.76
948 2.87
967 2.98
986 3.10 1003 3.21
1020 3.32
4500 883 2.78
905 2.93
926 3.07
951 3.24
973 3.40
993 3.54 1011 3.67 1028 3.79 1047 3.93
1064 4.06
5000 921 3.36
942 3.52
967 3.72
990 3.89 1009 4.05 1027 4.20 1051 4.39 1072 4.59 1091 4.75
1107 4.89
5500 962 3.97
985 4.19 1006 4.40 1027 4.60 1046 4.79 1069 5.00 1090 5.18 1108 5.37 1123 5.53
1144 5.72
6000 1005 4.67 1026 4.90 1048 5.14 1069 5.38 1089 5.61
-
5-hp Oversized Motor & Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
8.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
RT-PRC028AC-EN 81
Performance Data
Table 48. Evaporator fan performance 12½ tons with gas heat YSH150G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low
Static Drive
3-hp Standard Motor & Drive
3-hp
Standard
Motor & High
Static Drive
4000 562 1.04
610 1.22
653 1.40
692 1.57
727 1.74
760 1.90
791 2.06
820 2.22
842 2.34
875 2.58
4500 619 1.42
665 1.63
705 1.84
742 2.03
776 2.23
808 2.42
838 2.60
866 2.78
893 2.95
920 3.14
5000 678 1.88
720 2.13
758 2.36
793 2.58
826 2.80
857 3.02
886 3.23
914 3.43
940 3.64
966 3.84
5500 737 2.45
776 2.72
813 2.98
846 3.23
877 3.48
907 3.72
935 3.96
963 4.19
988 4.42
1013 4.64
6000 796 3.12
834 3.42
868 3.71
900 3.99
930 4.26
959 4.53
986 4.79 1012 5.05 1037 5.31
1062 5.56
5-hp Oversized Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive
4000 900 2.74
926 2.93
952 3.11
981 3.34 1008 3.56 1032 3.78 1057 4.01 1079 4.22 1102 4.45
1127 4.70
4500 939 3.26
967 3.53
992 3.74 1014 3.92 1037 4.13 1060 4.34 1085 4.57 1110 4.82 1134 5.07
1156 5.33
5000 990 4.03 1014 4.23 1035 4.41 1051 4.54 1079 4.89 1102 5.12 1121 5.31 1142 5.54
-
5500 1037 4.87 1060 5.08 1082 5.30 1104 5.52 1125 5.73
6000 -
-
-
-
-
-
-
5-hp Oversized Motor & Drive
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
8.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
82 RT-PRC028AC-EN
Performance Data
Table 49. Evaporator fan performance 15 tons TSD180G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor Drive
4800
5400
-
-
-
-
385 0.83
419 0.95
455 1.11
486 1.28
517 1.48
545 1.63
571 1.78
596 1.92
620 2.05
415 1.06
450 1.25
478 1.39
510 1.57
538 1.75
565 1.98
592 2.18
616 2.35
640 2.51
6000 387 1.03
447 1.38
477 1.59
507 1.75
533 1.92
562 2.12
588 2.30
613 2.55
637 2.82
660 3.02
6600 411 1.28
472 1.71
507 1.94
536 2.19
562 2.36
585 2.55
612 2.77
635 2.97
658 3.19
681 3.49
7200 436 1.58
496 2.05
539 2.41
564 2.64
591 2.89
614 3.07
635 3.28
659 3.51
682 3.74
703 3.96
5-hp Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Drive 3HP Standard Motor & High Static Drive
4800 643 2.19
664 2.32
685 2.44
705 2.57
724 2.69
743 2.81
761 2.93
779 3.05
797 3.16
813 3.27
5400 662 2.67
683 2.82
704 2.98
724 3.12
743 3.27
762 3.41
780 3.55
798 3.70
816 3.84
832 3.97
6000 682 3.20
704 3.38
724 3.56
744 3.73
763 3.91
782 4.07
800 4.24
817 4.40
835 4.57
851 4.73
6600 703 3.78
724 3.99
744 4.19
764 4.40
783 4.59
802 4.79
819 4.98
836 5.16
853 5.35
871 5.54
7200 725 4.24
745 4.56
765 4.89
784 5.11
803 5.34
822 5.56
840 5.78
857 6.00
873 6.20
890 6.42
5-hp Oversized Motor & Drive 7.5hp OS Motor & High Static Drive (a)
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 89, p. 120
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 91, p. 122 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
(a)7.5HP high static oversized motor offering is field installed only.
RT-PRC028AC-EN 83
Performance Data
Table 50. Evaporator fan performance 15 tons TSH180G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive 3-hp Standard Motor & Drive
4800 420 0.77
453 0.91
481 1.05
508 1.18
532 1.31
563 1.47
587 1.61
614 1.77
638 1.93
658 2.08
5400 464 1.06
494 1.22
521 1.37
546 1.52
570 1.67
592 1.81
619 2.00
642 2.15
664 2.32
687 2.50
6000 509 1.41
537 1.59
562 1.76
586 1.93
609 2.09
629 2.26
649 2.42
669 2.58
695 2.80
716 2.97
6600 554 1.83
580 2.03
604 2.22
627 2.41
648 2.59
668 2.78
687 2.96
706 3.14
724 3.32
745 3.53
7200 599 2.34
624 2.56
647 2.77
668 2.97
689 3.18
708 3.38
727 3.58
744 3.77
762 3.97
778 4.17
5-hp Oversized Motor & Standard Drive
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor &
Drive
3HP Standard Motor & High Static Drive
4800 678 2.23
698 2.39
719 2.55
738 2.71
756 2.88
774 3.05
791 3.22
808 3.38
825 3.56
841 3.73
5400 709 2.67
728 2.84
747 3.02
764 3.19
782 3.37
800 3.55
818 3.73
835 3.91
851 4.10
868 4.30
6000 735 3.16
757 3.36
777 3.55
796 3.75
812 3.93
828 4.12
844 4.32
860 4.52
877 4.73
893 4.92
6600 767 3.75
785 3.93
804 4.14
822 4.35
841 4.57
860 4.79
876 5.00
891 5.20
907 5.42
920 5.63
7200 794 4.36
815 4.61
835 4.86
852 5.05
869 5.27
886 5.50
902 5.73
921 5.98
937 6.20
952 6.43
5-hp Oversized Motor & Standard Drive 7.5hp OS Motor & High Static Drive (a)
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 89, p. 120
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 91, p. 122 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
(a)7.5HP high static oversized motor offering is field installed only.
84 RT-PRC028AC-EN
Performance Data
Table 51. Evaporator fan performance 15 tons with gas heat YSD180G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive 3-hp Standard Motor & Drive
4800 379 0.80
415 0.93
449 1.08
484 1.26
513 1.46
544 1.63
573 1.79
600 1.94
627 2.09
651 2.24
5400 417 1.07
450 1.25
480 1.41
512 1.58
543 1.79
568 2.01
596 2.21
623 2.39
648 2.57
673 2.74
6000 456 1.43
486 1.64
515 1.80
542 1.98
571 2.18
599 2.41
622 2.65
645 2.89
671 3.10
695 3.30
6600 496 1.86
524 2.11
550 2.28
576 2.47
600 2.67
626 2.89
653 3.13
674 3.40
695 3.68
718 3.93
7200 535 2.39
562 2.61
587 2.86
610 3.05
633 3.26
655 3.47
679 3.71
705 3.97
726 4.26
745 4.57
5hp Oversized Motor & Low
Static Drive
5hp Oversized Motor & Standard Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Drive 3-hp Standard Motor & High Static Drive
4800 674 2.38
697 2.52
719 2.66
739 2.78
759 2.92
779 3.04
797 3.16
816 3.29
834 3.41
851 3.52
5400 696 2.92
718 3.08
740 3.24
760 3.40
780 3.55
799 3.71
819 3.86
837 4.01
854 4.15
872 4.29
6000 718 3.50
740 3.70
761 3.89
782 4.08
801 4.25
821 4.44
840 4.61
857 4.78
876 4.96
893 5.13
6600 740 4.15
762 4.38
783 4.59
803 4.81
824 5.02
842 5.22
861 5.44
880 5.64
896 5.83
914 6.03
7200 764 4.87
785 5.13
806 5.38
826 5.61
846 5.86
864 6.09
883 6.32
901 6.55
918 6.78
935 7.00
5-hp Oversized Motor & Standard Drive 7.5hp Oversized Motor & High Static Drive (a)
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 89, p. 120
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 91, p. 122 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating ranges.
(a)7.5HP high static oversized motor offering is field installed only.
RT-PRC028AC-EN 85
Performance Data
Table 52. Evaporator fan performance 15 tons with gas heat YSH180G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive 3-hp Standard Motor & Drive
4800 419 0.77
455 0.92
487 1.07
515 1.22
548 1.39
578 1.55
607 1.73
634 1.90
659 2.08
681 2.26
5400 462 1.05
496 1.22
526 1.39
553 1.56
578 1.72
603 1.89
635 2.10
661 2.29
687 2.49
711 2.68
6000 506 1.39
537 1.59
566 1.78
592 1.97
616 2.15
639 2.33
661 2.52
690 2.76
713 2.95
736 3.17
6600 550 1.81
579 2.03
606 2.24
631 2.45
654 2.65
677 2.86
698 3.06
717 3.25
738 3.46
766 3.74
7200 595 2.30
622 2.54
648 2.77
671 3.00
694 3.23
715 3.46
735 3.68
755 3.89
773 4.11
791 4.33
5hp Oversized Motor & Low Static Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor &
Drive
3-hp Standard Motor & High Static Drive
4800 704 2.44
728 2.63
750 2.83
772 3.03
793 3.23
813 3.43
833 3.64
852 3.85
872 4.07
890 4.28
5400 732 2.88
753 3.08
774 3.29
795 3.49
815 3.70
835 3.92
855 4.15
874 4.38
892 4.60
911 4.84
6000 761 3.40
783 3.61
803 3.82
822 4.04
841 4.27
859 4.50
877 4.73
896 4.95
914 5.18
933 5.44
6600 787 3.95
809 4.20
830 4.45
850 4.68
870 4.92
887 5.15
905 5.39
921 5.64
939 5.90
955 6.15
7200 814 4.60
838 4.88
856 5.11
876 5.37
896 5.64
916 5.91
934 6.16
951 6.42
968 6.68
983 6.93
5-hp Oversized Motor & Standard Drive 7.5hp Oversized Motor & High Static Drive (a)
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 89, p. 120
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 91, p. 122 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating ranges.
(a)7.5HP high static oversized motor offering is field installed only.
86 RT-PRC028AC-EN
Performance Data
Table 53. Evaporator fan performance 17½ tons TSD210/211G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive Accessory
5600 424 1.01
474 1.31
509 1.52
540 1.72
567 1.87
594 2.08
620 2.26
643 2.43
664 2.60
6300 392 001 450 1.27
498 1.60
541 1.93
572 2.16
599 2.39
622 2.55
648 2.75
671 2.99
695 3.20
7000 421 001 477 1.56
524 1.93
566 2.30
603 2.67
631 2.93
656 3.16
679 3.40
700 3.57
723 3.80
7700 451 001 505 1.90
551 2.31
591 2.72
628 3.12
662 3.53
689 3.84
711 4.06
733 4.37
752 4.58
8400 482 002 533 2.30
578 2.75
617 3.20
653 3.64
687 4.09
718 4.53
745 4.91
764 5.13
785 5.42
5-hp Standard Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive
5600 685 2.77
705 2.93
724 3.09
743 3.26
761 3.42
778 3.58
795 3.73
812 3.90
828 4.06
843 4.20
6300 715 3.39
734 3.58
753 3.76
772 3.96
790 4.14
807 4.33
824 4.51
840 4.69
856 4.87
871 5.04
7000 744 4.08
765 4.31
784 4.52
802 4.74
820 4.95
837 5.16
853 5.37
870 5.58
885 5.78
901 5.98
7700 772 4.77
792 5.02
812 5.34
831 5.60
850 5.85
867 6.09
884 6.32
900 6.56
914 6.78
930 7.01
8400 805 5.76
822 5.96
841 6.17
860 6.45
878 6.77
895 7.09
913 7.37
930 7.64
945 7.88
961 8.15
7.5-hp Oversized Motor & Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
RT-PRC028AC-EN 87
Performance Data
Table 54. Evaporator fan performance 17½ tons TSH210/211G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive
5600 439 1.10
487 1.40
530 1.68
568 1.98
591 2.10
614 2.32
634 2.53
654 2.76
673 2.98
692 3.20
6300 477 1.45
531 1.85
567 2.15
603 2.46
637 2.80
658 2.91
678 3.15
698 3.40
716 3.64
734 3.89
7000 517 1.87
571 2.36
605 2.70
641 3.05
672 3.39
703 3.78
725 3.97
742 4.15
760 4.42
777 4.69
7700 557 2.38
609 2.92
649 3.38
676 3.73
710 4.12
738 4.49
765 4.90
790 5.28
805 5.32
822 5.61
8400 598 2.97
647 3.57
690 4.16
719 4.54
745 4.95
776 5.38
801 5.78
826 6.20
852 6.67
868 6.88
5-hp Standard Motor & Drive 7.5-hp Oversized Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive
5-hp Standard Motor &
High Static Drive
5600 709 3.42
726 3.65
743 3.88
759 4.11
774 4.34
789 4.57
803 4.81
817 5.05
831 5.28
845 5.54
6300 751 4.14
767 4.39
783 4.64
798 4.89
814 5.15 829 (a) 5.41
843 5.67
857 5.92
870 6.18
884 6.46
7000 794 4.97
810 5.24
825 5.51
840 5.79
855 6.07
870 6.35
884 6.63
897 6.92
911 7.20
924 7.48
7700 838 5.92
854 6.22
869 6.52
883 6.81
898 7.13
912 7.43
925 7.72
939 8.04
952 8.34
8400 883 7.00
898 7.32
913 7.65
927 7.98
941 8.31
954 8.62
-
-
-
-
-
7.5-hp Oversized Motor & High Static Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
(a)5-hp Standard Motor & High Static Drive
88 RT-PRC028AC-EN
Performance Data
Table 55. Evaporator fan performance 17½ tons with gas heat YSD210/211G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive
5600 434 1.07
472 1.30
504 1.49
533 1.68
560 1.82
585 2.01
611 2.20
634 2.37
655 2.53
676 2.69
6300 478 1.45
514 1.71
546 1.97
571 2.15
598 2.37
622 2.55
645 2.71
668 2.96
691 3.16
711 3.35
7000 522 1.92
556 2.21
587 2.50
615 2.79
636 2.96
660 3.20
683 3.43
703 3.59
724 3.81
745 4.09
7700 568 2.48
599 2.81
628 3.13
655 3.45
680 3.75
699 3.93
720 4.18
742 4.47
761 4.67
779 4.85
8400 614 3.15
643 3.52
671 3.87
696 4.21
720 4.56
742 4.88
760 5.08
780 5.32
799 5.67 818 (a) 5.92
5-hp Standard Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive
5-hp Standard Motor &
High Static Drive
5600 695 2.85
714 3.01
732 3.16
750 3.32
766 3.47
783 3.62
799 3.77
814 3.92
830 4.07
845 4.22
6300 730 3.53
748 3.71
766 3.90
783 4.07
800 4.25
816 4.42
832 4.60
847 4.77
862 4.94
876 5.11
7000 765 4.31
784 4.53
801 4.73
818 4.93
834 5.13
850 5.33
866 5.53
881 5.73
896 5.93
910 6.11
7700 798 5.11
817 5.41
836 5.67
854 5.90
870 6.12
886 6.36
901 6.58
916 6.79
930 7.02
945 7.24
8400 835 6.11
852 6.31
870 6.62
886 6.94
904 7.22
921 7.50
937 7.75
952 8.00
966 8.24
980 8.49
7.5-hp Oversized Motor & Drive 7.5-hp Oversized Motor & High Static Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
(a)7.5-hp Oversized Motor & Drive
RT-PRC028AC-EN 89
Performance Data
Table 56. Evaporator fan performance 17½ tons with gas heat YSH210/211G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive 5-hp Standard Motor & Drive
5600 479 1.35
523 1.63
560 1.91
584 2.03
607 2.25
630 2.48
651 2.72
671 2.95
690 3.18
709 3.42
6300 531 1.85
566 2.14
604 2.47
637 2.79
655 2.87
677 3.13
697 3.39
716 3.64
735 3.91
753 4.17
7000 583 2.48
613 2.80
649 3.14
678 3.47
709 3.85
726 3.96
744 4.17
763 4.46
780 4.74
798 5.03
7700 636 3.24
662 3.55
692 3.91
726 4.33
750 4.67
779 5.11
795 5.31
810 5.40
827 5.72
844 6.03
8400 687 4.11
713 4.45
739 4.87
768 5.26
798 5.73
819 6.08
846 6.57
864 6.90
875 6.84 891 (a) 7.17
7.5-hp Oversized Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive
5-hp Standard Motor &
High Static Drive
5600 727 3.66
744 3.91
761 4.15
777 4.39
793 4.65
808 4.88
823 5.13
837 5.39
851 5.64
865 5.90
6300 770 4.44
787 4.70
803 4.96
819 5.23
835 5.51
849 5.78
864 6.06
878 6.33
892 6.61
905 6.88
7000 815 5.33
831 5.62
847 5.91
862 6.20
877 6.50
892 6.80
906 7.10
920 7.41
933 7.70
947 8.01
7700 860 6.35
876 6.67
892 7.00
907 7.31
921 7.63
935 7.95
949 8.27
963 8.60
8400 907 7.52
922 7.86
937 8.21
952 8.56
-
7.5-hp Oversized Motor & High Static Drive
-
-
-
-
-
-
-
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
(a)7.5-hp Oversized Motor & High Static Drive
90 RT-PRC028AC-EN
Performance Data
Table 57. Evaporator fan performance 20 tons TSD240G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive 5-hp Standard Motor & Drive
6400 473 1.55
504 1.76
533 1.96
560 2.15
585 2.33
609 2.51
633 2.69
656 2.89
677 3.10
699 3.31
7200 525 2.18
553 2.41
579 2.58
605 2.85
628 3.05
651 3.25
673 3.46
694 3.65
715 3.86
735 4.08
8000 577 2.95
603 3.14
627 3.42
651 3.62
674 3.93
695 4.15
715 4.36
735 4.59
755 4.82
774 5.04
8800 629 3.89
653 4.06
676 4.40
698 4.63
719 4.87
740 5.21
759 5.46
778 5.69
796 5.94
814 6.19
9600 682 5.02
704 5.20
726 5.48
747 5.84
766 6.06
785 6.35
805 6.72
823 7.01
840 7.26
857 7.52
7.5-hp Oversized Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive
6400 721 3.53
742 3.75
762 3.96
782 4.17
802 4.39
819 4.59
837 4.81
855 5.02
872 5.22
889 5.44
7200 754 4.32
774 4.56
793 4.80
813 5.05
832 5.30
850 5.54
868 5.78
884 6.01
902 6.26
918 6.49
8000 793 5.27
810 5.51
828 5.77
845 6.03
862 6.29
881 6.58
898 6.84
916 7.12
932 7.39
948 7.65
8800 832 6.44
849 6.69
866 6.93
883 7.20
899 7.47
915 7.75
930 8.03
947 8.35
9600 873 7.78
889 8.06
905 8.33
-
-
-
-
-
-
-
-
-
7.5-hp Oversized Motor & High Static Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
RT-PRC028AC-EN 91
Performance Data
Table 58. Evaporator fan performance 20 tons TSH240G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive 5-hp Standard Motor & Drive
6400 503 1.62
541 1.88
570 2.13
611 2.42
635 2.64
658 2.86
680 3.08
701 3.30
721 3.51
740 3.73
7200 555 2.20
590 2.52
620 2.81
648 3.10
685 3.43
707 3.68
729 3.93
749 4.17
768 4.42
786 4.67
8000 607 2.91
642 3.32
673 3.63
695 3.94
722 4.27
757 4.64
778 4.93
797 5.21
816 5.48
834 5.76
8800 660 3.76
695 4.25
721 4.60
748 4.97
768 5.30
793 5.66
826 6.09
847 6.42
865 6.72
883 7.03
9600 714 4.78
747 5.33
773 5.78
798 6.14
821 6.54
838 6.89
861 7.29
892 7.76
916 8.16
932 8.49
7.5-hp Oversized Motor & Drive
7.5-hp Oversized Motor & High Static
Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor &
Drive
5-hp Standard Motor & High Static Drive
6400 759 3.95
776 4.16
794 4.37
810 4.59
826 4.80
843 5.02
858 5.23
873 5.44
887 5.65
902 5.87
7200 805 4.91
822 5.15
838 5.39
855 5.64
871 5.88
886 6.12
901 6.35
916 6.60
931 6.84
944 7.07
8000 851 6.03
868 6.30
885 6.58
900 6.85
916 7.12
931 7.38
945 7.65
960 7.93
974 8.19
988 8.46
8800 899 7.33
916 7.63
932 7.94
947 8.24
962 8.53
-
9600 -
7.5-hp Oversized Motor & High Static Drive
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
92 RT-PRC028AC-EN
Performance Data
Table 59. Evaporator fan performance 20 tons with gas heat YSD240G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive 5-hp Standard Motor & Drive
6400 497 1.73
526 1.90
553 2.11
579 2.29
604 2.47
628 2.65
651 2.85
673 3.06
695 3.27
717 3.49
7200 552 2.39
578 2.58
603 2.82
627 3.04
650 3.24
672 3.45
694 3.65
715 3.86
735 4.09
754 4.32
8000 608 3.21
632 3.46
654 3.67
676 3.95
698 4.18
719 4.41
739 4.64
759 4.87
778 5.09
797 5.32
8800 664 4.20
686 4.52
707 4.71
727 5.00
747 5.30
767 5.56
786 5.80
804 6.06
822 6.31
840 6.56
9600 721 5.39
741 5.76
760 6.00
780 6.24
797 6.57
815 6.90
834 7.17
852 7.44
869 7.72
886 8.00
7.5-hp Oversized Motor & Drive 7.5-hp Oversized Motor &
High Static Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive
6400 739 3.71
759 3.92
779 4.14
798 4.35
817 4.57
835 4.78
852 4.98
869 5.19
887 5.41
903 5.62
7200 774 4.56
794 4.80
814 5.06
833 5.31
851 5.55
869 5.79
886 6.03
902 6.26
919 6.51
935 6.74
8000 815 5.57
832 5.83
849 6.10
868 6.38
886 6.65
903 6.92
920 7.19
937 7.47
953 7.74
969 8.00
8800 858 6.81
875 7.06
891 7.34
907 7.62
922 7.90
938 8.19
955 8.50
9600 902 8.27
918 8.53
-
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Oversized Motor & High Static Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
RT-PRC028AC-EN 93
Performance Data
Table 60. Evaporator fan performance 20 tons with gas heat YSH240G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static 5-hp Standard Motor & Drive
6400 533 1.82
560 2.05
599 2.33
628 2.57
653 2.81
676 3.04
698 3.27
720 3.50
740 3.73
759 3.95
7200 592 2.54
620 2.82
643 3.04
680 3.37
705 3.64
727 3.91
748 4.17
769 4.43
789 4.70
807 4.95
8000 650 3.40
678 3.70
698 3.98
724 4.28
757 4.64
779 4.95
800 5.24
819 5.53
838 5.83
856 6.11
8800 709 4.45
736 4.77
758 5.15
774 5.39
801 5.77
832 6.17
852 6.50
871 6.82
889 7.14
907 7.47
9600 769 5.71
794 6.08
816 6.44
833 6.80
849
7.5-hp Oversized Motor & Standard Drive
7.08
876 7.53
904 7.95
924 8.32
-
7.5-hp Oversized Motor & High Static Drive
-
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive
6400 778 4.18
796 4.40
814 4.63
831 4.85
847 5.08
863 5.30
879 5.53
895 5.76
909 5.97
924 6.20
7200 825 5.21
843 5.46
861 5.72
876 5.96
893 6.22
909 6.48
924 6.74
939 6.99
953 7.23
968 7.49
8000 874 6.40
891 6.69
907 6.97
924 7.26
939 7.54
955 7.82
970 8.11
984 8.38
-
8800 924 7.79
941 8.11
957 8.43
9600 -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Oversized Motor & High Static Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
94 RT-PRC028AC-EN
Performance Data
Table 61. Evaporator fan performance 25 tons TSD300/301G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Low Static Drive 7.5-hp Standard Motor & Drive
7000 532 2.08
559 2.25
588 2.49
612 2.62
637 2.87
662 3.09
686 3.28
708 3.48
729 3.68
750 3.87
7500 566 2.52
593 2.73
618 2.95
642 3.12
665 3.33
689 3.59
712 3.82
734 4.03
755 4.24
775 4.45
8000 600 3.04
626 3.27
648 3.44
674 3.72
694 3.86
717 4.14
739 4.40
760 4.65
781 4.87
800 5.09
8500 635 3.62
659 3.87
680 4.03
705 4.35
725 4.52
745 4.72
766 5.03
787 5.31
807 5.57
826 5.80
9000 670 4.28
692 4.52
713 4.73
734 4.97
757 5.29
775 5.43
794 5.69
814 6.01
834 6.31
853 6.58
9500 705 5.00
725 5.24
747 5.51
764 5.68
787 6.07
806 6.28
823 6.44
842 6.76
861 7.10
880 7.41
10000 740 5.81
758 6.04
781 6.37
797 6.54
816 6.85
838 7.23
854 7.38
871 7.59
889 7.93
907 8.29
10500 775 6.71
793 6.93
813 7.27
831 7.50
847 7.72
868 8.16
886 8.43
902 8.59
-
11000 811 7.69
827 7.93
846 8.25
865 8.56
-
7.5-hp Standard Motor & High Static Drive
-
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Drive
7000 769 4.05
788 4.24
806 4.42
824 4.60
841 4.78
858 4.95
874 5.12
890 5.29
906 5.46
920 5.62
7500 794 4.66
813 4.86
831 5.06
848 5.26
865 5.45
881 5.64
897 5.83
913 6.01
928 6.20
944 6.39
8000 819 5.31
837 5.54
855 5.76
873 5.97
889 6.18
905 6.39
921 6.60
937 6.80
952 7.00
967 7.21
8500 845 6.03
863 6.27
881 6.52
897 6.75
914 6.98
930 7.21
946 7.43
962 7.66
977 7.88
991 8.09
9000 872 6.84
889 7.08
906 7.34
923 7.59
939 7.84
956 8.09
971 8.33
986 8.57
-
9500 898 7.70
915 7.97
932 8.23
949 8.50
10000 925 8.62
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
10500
11000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Standard Motor & High Static Drive Accessory
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
RT-PRC028AC-EN 95
Performance Data
Table 62. Evaporator fan performance 25 tons TSH300/301G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Low Static Drive 7.5-hp Standard Motor & Drive
7000 589 2.44
620 2.65
652 2.96
688 3.30
707 3.52
724 3.73
741 3.94
758 4.15
774 4.36
7500 583 2.57
618 2.85
651 3.18
682 3.56
715 3.78
742 4.12
759 4.35
775 4.58
791 4.80
807 5.03
8000 617 3.09
649 3.33
685 3.79
711 3.99
739 4.37
774 4.75
794 5.04
810 5.29
825 5.53
841 5.77
8500 652 3.67
681 3.92
717 4.39
742 4.65
770 5.10
794 5.31
828 5.79
845 6.08
860 6.33
875 6.60
9000 687 4.33
715 4.60
747 5.00
775 5.44
798 5.65
824 6.18
850 6.42
881 6.94
896 7.23
910 7.50
9500 722 5.05
749 5.34
776 5.66
808 6.26
829 6.49
853 6.92
877 7.32
904 7.67
931 8.20
945 8.48
10000 757 5.86
783 6.17
807 6.45
839 7.06
863 7.48
882 7.66
907 8.36
928 8.58
10500 792 6.75
817 7.08
840 7.37
868 7.87
895 8.50
-
11000 828 7.73
852 8.07
874 8.40
-
-
-
-
7.5-hp Standard Motor & High Static Drive
-
-
-
-
-
-
-
-
-
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Drive
7000 789 4.57
803 4.77
818 4.99
832 5.20
845 5.40
859 5.61
872 5.83
885 6.03
897 6.24
909 6.45
7500 821 5.25
836 5.48
850 5.70
864 5.93
877 6.15
891 6.38
904 6.61
915 6.82
928 7.05
940 7.27
8000 855 6.01
869 6.25
883 6.50
897 6.74
910 6.97
922 7.21
935 7.45
947 7.68
959 7.92
972 8.18
8500 889 6.85
903 7.11
916 7.36
930 7.62
942 7.87
955 8.12
967 8.38
-
9000 924 7.77
937 8.04
950 8.31
963 8.59
-
9500
10000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
10500
11000
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Standard Motor & High Static Drive Accessory
-
-
-
-
-
-
-
-
-
-
-
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
96 RT-PRC028AC-EN
Performance Data
Table 63. Evaporator fan performance 25 tons with gas heat YSD300/301G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Low Static Drive 7.5-hp Standard Motor & Drive
7000 554 2.22
580 2.43
604 2.56
629 2.79
654 3.02
678 3.22
700 3.41
721 3.61
742 3.80
762 3.98
7500 590 2.72
614 2.90
638 3.10
660 3.28
684 3.54
707 3.77
729 3.98
749 4.19
769 4.40
789 4.60
8000 627 3.28
647 3.44
672 3.71
692 3.84
714 4.10
736 4.37
758 4.62
778 4.84
798 5.06
816 5.28
8500 663 3.90
682 4.05
706 4.37
726 4.53
745 4.73
766 5.03
787 5.31
807 5.56
826 5.80
844 6.03
9000 699 4.60
718 4.77
739 5.06
760 5.31
778 5.45
797 5.74
817 6.05
836 6.34
855 6.62
873 6.86
9500 735 5.37
754 5.58
773 5.82
794 6.17
811 6.32
829 6.53
847 6.85
866 7.18
884 7.49
902 7.77
10000 771 6.23
790 6.47
807 6.67
827 7.06
845 7.29
861 7.44
878 7.73
896 8.08
914 8.42
10500 807 7.17
827 7.46
842 7.63
861 8.00
880 8.36
895 8.52
-
11000 844 8.20
863 8.54
-
7.5-hp Standard Motor & High Static Drive
-
-
-
-
-
-
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Drive
7000 780 4.17
798 4.34
817 4.53
834 4.70
850 4.87
866 5.04
882 5.21
897 5.37
913 5.54
928 5.70
7500 808 4.81
825 5.00
843 5.20
859 5.39
876 5.58
892 5.77
908 5.95
922 6.13
937 6.31
952 6.49
8000 835 5.50
852 5.72
869 5.93
886 6.15
902 6.35
918 6.55
933 6.75
948 6.95
963 7.15
978 7.35
8500 862 6.27
880 6.50
896 6.73
913 6.96
929 7.19
944 7.41
960 7.63
975 7.85
989 8.06
9000 891 7.11
908 7.36
924 7.61
940 7.86
956 8.10
971 8.34
986 8.58
-
9500 919 8.04
936 8.29
952 8.56
10000 -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
10500
11000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Standard Motor & High Static Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
RT-PRC028AC-EN 97
Performance Data
Table 64. Evaporator fan performance 25 tons with gas heat YSH300/301G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Low Static Drive 7.5-hp Standard Motor & Drive
7000
7500
8000
8500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
596 2.17
628 2.44
659 2.72
687 2.99
715 3.27
741 3.55
586 2.20
618 2.48
646 2.74
676 3.04
705 3.34
732 3.63
758 3.93
608 2.50
639 2.81
667 3.10
694 3.38
722 3.70
749 4.01
775 4.33
604 2.58
633 2.85
660 3.16
689 3.49
715 3.78
741 4.10
767 4.43
793 4.77
9000 598 2.65
629 2.96
657 3.23
682 3.54
710 3.88
737 4.23
760 4.54
785 4.87
810 5.23
9500 598 2.80
624 3.03
654 3.38
682 3.67
707 3.97
731 4.32
757 4.68
782 5.04
804 5.36
828 5.72
10000 628 3.26
649 3.44
680 3.84
707 4.15
732 4.46
755 4.80
778 5.17
803 5.56
826 5.93
848 6.27
10500 657 3.76
676 3.91
705 4.32
732 4.68
756 4.99
779 5.33
801 5.70
824 6.10
848 6.51
869 6.88
11000 687 4.31
703 4.44
731 4.83
757 5.24
781 5.58
803 5.91
825 6.28
845 6.68
868 7.10
891 7.54
7.5-hp Standard Motor & High Static
Drive
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Drive
7000 766 3.82
789 4.09
812 4.38
834 4.65
856 4.94
877 5.22
897 5.51
916 5.78
936 6.07
954 6.35
7500 782 4.22
806 4.52
829 4.82
851 5.11
872 5.41
893 5.71
913 6.01
933 6.31
952 6.61
969 6.90
8000 800 4.65
823 4.97
845 5.28
867 5.59
889 5.92
909 6.23
929 6.54
948 6.85
967 7.18
985 7.49
8500 817 5.10
840 5.44
862 5.76
884 6.10
905 6.44
926 6.78
945 7.11
965 7.45
983 7.77 1001 8.11
9000 834 5.58
857 5.93
880 6.30
901 6.64
922 6.99
942 7.34
962 7.72
981 8.06 1000 8.42
-
9500 851 6.09
874 6.46
896 6.84
919 7.22
939 7.59
959 7.96
979 8.35
10000 869 6.63
892 7.04
915 7.43
935 7.81
957 8.22
-
-
-
-
-
-
-
-
-
-
-
-
-
10500 889 7.24
910 7.62
932 8.04
953 8.47
11000 911 7.92
930 8.30
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Standard Motor & High Static Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
98 RT-PRC028AC-EN
Performance Data
Table 65. Evaporator fan performance—12½ tons—TH*150G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive
2500 (a)
4000
-
-
-
-
-
-
-
-
-
-
-
-
370 0.32
417 0.43
458 0.54
496 0.66
531 0.79
564 0.91
593 1.03
623 1.16
386 0.42
430 0.54
472 0.67
508 0.80
543 0.94
576 1.08
606 1.22
635 1.35
360 0.43
404 0.55
447 0.68
486 0.81
522 0.96
556 1.11
588 1.26
619 1.40
647 1.55
387 0.59
426 0.71
465 0.85
502 0.99
537 1.14
570 1.29
602 1.44
631 1.59
660 1.74
4500 377 0.66
417 0.79
452 0.92
486 1.06
521 1.20
555 1.36
586 1.50
617 1.65
645 1.80
673 1.95
5000 409 0.88
448 1.03
481 1.17
512 1.30
542 1.44
573 1.59
604 1.74
633 1.89
662 2.04
688 2.18
5500 441 1.14
479 1.30
510 1.44
539 1.58
567 1.71
594 1.85
624 2.01
652 2.16
679 2.31
705 2.46
6000 474 1.42
510 1.59
540 1.74
568 1.88
594 2.01
620 2.15
645 2.29
671 2.45
698 2.62
724 2.81
3-hp Standard Motor & High Static Drive Accessory (b)
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive Accessory
3-hp Standard Motor & High Static Drive Accessory (c)
650 1.28
676 1.40
701 1.52
726 1.64
748 1.76
771 1.87
793 1.98
814 2.09
835 2.21
855 2.32
662 1.48
688 1.61
713 1.74
737 1.86
760 1.98
783 2.11
806 2.23
827 2.36
847 2.48
867 2.61
674 1.69
701 1.82
726 1.96
750 2.09
772 2.22
795 2.35
818 2.49
839 2.64
859 2.78
879 2.96
4000 687 1.89
713 2.04
738 2.18
762 2.32
785 2.47
808 2.62
829 2.79
851 2.97
871 3.17
891 3.40
4500 700 2.10
726 2.26
750 2.41
775 2.58
798 2.75
821 2.95
842 3.15
864 3.41
885 3.71
904 4.06
5000 714 2.34
740 2.50
765 2.68
788 2.87
811 3.09
834 3.36
855 3.66
875 4.02
897 4.49
917 5.04
5500
6000
730
748
2.63
3.02
755
772
2.81
3.26
778
795
3.02
3.54
801
818
3.26
3.89
824
839
3.56
4.32
846
860
3.93
4.85
868
881
5-hp Oversized Motor & Drive
4.40
5.51
889
-
4.96
-
909
-
5.65
-
-
-
-
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
RT-PRC028AC-EN 99
Performance Data
Table 66. Evaporator fan performance—12½ tons—THD150G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive
2500 (a)
4000
—
—
—
—
—
—
—
—
—
—
—
—
369 0.32 416 0.42 458 0.52 496 0.63 530 0.74 561 0.85 591 0.97 618
383 0.41 429 0.52 470 0.64 508 0.76 543 0.88 575 1.01 606 1.13 634
358 0.42 403 0.53 444 0.64 484 0.77 520 0.90 554 1.04 587 1.18 618 1.32 647
386 0.57 424 0.67 464 0.80 500 0.93 535 1.07 569 1.21 600 1.36 629 1.52 658
1.09
1.26
1.47
1.69
4500 375 0.62 415 0.75 450 0.86 484 0.99 519 1.13 552 1.28 583 1.42 615 1.58 644 1.75 671
5000 407 0.82 446 0.97 479 1.09 510 1.22 540 1.37 572 1.53 602 1.69 630 1.84 658 2.01 686
1.92
2.20
5500 440 1.06 477 1.22 508 1.37 537 1.50 565 1.65 592 1.81 621 1.99 650 2.16 676 2.34 701
6000 471 1.34 508 1.52 538 1.69 566 1.84 592 1.99 617 2.15 643 2.32 669 2.51 695 2.71 721
2.51
2.90
3-hp Standard Motor & High Static Drive Accessory (b)
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive Accessory (b)
3-hp Standard Motor & High Static Drive Accessory (c)
645 1.22 670 1.35 694 1.48 718 1.61 740 1.75 762 1.88 783 2.02 803 2.17 823 2.31 843
660 1.40 686 1.54 710 1.69 733 1.83 755 1.98 777 2.13 798 2.28 819 2.44 839 2.60 858
674 1.61 700 1.76 725 1.91 749 2.07 771 2.23 793 2.39 814 2.56 834 2.73 854 2.90 873
2.46
2.76
3.07
4000 686 1.85 712 2.02 737 2.18 762 2.35 785 2.51 808 2.68 830 2.86 850 3.04 870 3.22 889
4500 698 2.10 724 2.28 749 2.47 773 2.65 797 2.84 820 3.02 842 3.21 863 3.39 884 3.58 904
5000 712 2.38 737 2.57 762 2.76 785 2.97 809 3.17 831 3.38 853 3.58 875 3.79 895 3.99 916
5500 727 2.70 753 2.90 776 3.10 799 3.31 822 3.52 844 3.74 865 3.96 886 4.19 907 4.42 927
6000 744 3.09 767 3.28 791 3.49 815 3.71 837 3.92 858 4.15 879 4.37 899 4.60 919 4.84 939
5-hp Oversized Motor & Drive
3.41
3.77
4.20
4.64
5.08
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
100 RT-PRC028AC-EN
Performance Data
Table 67. Evaporator fan performance—12½ tons—YH*150G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
5500 462 1.23
496 1.38
525 1.51
553 1.64
582 1.79 610 1.93
638 2.08
666 2.23
692 2.38
718
6000 497 1.53
530 1.69
558 1.83
584 1.96
610 2.09 636 2.24
662 2.39
688 2.56
713 2.73
738
3-hp Standard Motor & High Static Drive Accessory (b)
Continued
External Static Pressure (Inches of Water)
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive
2500 (a)
263 0.15
322 0.23
375 0.33
421 0.44
463 0.56 501 0.68
536 0.80
568 0.92
599 1.04
627 1.16
292 0.23
344 0.33
393 0.43
436 0.55
477 0.69 515 0.82
549 0.96
582 1.10
612 1.23
640 1.36
324 0.35
369 0.45
413 0.57
455 0.71
494 0.84 529 0.99
563 1.14
595 1.29
626 1.43
655 1.57
4000 358 0.51
398 0.62
437 0.75
475 0.89
512 1.03 547 1.18
579 1.33
609 1.48
639 1.63
668 1.78
4500 392 0.71
429 0.84
464 0.97
499 1.11
532 1.25 566 1.41
597 1.55
627 1.70
655 1.85
682
5000 427 0.95
462 1.09
493 1.22
525 1.36
556 1.51 587 1.66
617 1.80
645 1.95
673 2.10
700
2.00
2.25
2.54
2.92
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive Accessory
3-hp Standard Motor & High Static Drive Accessory (c)
655 1.28
681 1.40
706 1.51
730 1.63
754 1.74 776 1.85
798 1.96
820 2.07
839 2.17
860 2.28
668 1.49
694 1.62
719 1.74
743 1.87
766 1.98 790 2.11
811 2.22
833 2.35
852 2.46
873 2.59
681 1.71
708 1.85
732 1.97
756 2.10
780 2.24 803 2.37
824 2.50
846 2.65
866 2.79
887 2.96
4000 695 1.93
721 2.07
746 2.22
770 2.36
794 2.50 816 2.66
838 2.82
859 3.00
879 3.20
899
4500 708 2.15
735 2.31
760 2.47
784 2.63
807 2.81 830 3.01
852 3.24
873 3.50
893 3.79
913
5000 725 2.41
750 2.57
773 2.75
798 2.97
821 3.20 843 3.47
865 3.81
887 4.22
907 4.71
926
5500 744 2.73
767 2.92
790 3.14
813 3.41
836 3.75 857 4.16
878 4.65
900 5.31
920 6.07
940
6000 761 3.14
786 3.42
809 3.74
831 4.15
852 4.64 873 5.25
894 6.07
913 6.97
934 8.19
954
5-hp Oversized Motor & Drive
3.44
4.18
5.27
7.01
9.61
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
RT-PRC028AC-EN 101
Performance Data
Table 68. Evaporator fan performance—12½ tons—YHD150G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
5500 460 1.15 493 1.30 523 1.44 552 1.58 579 1.73 607 1.90 636 2.08 664 2.26 689 2.43 714
6000 495 1.45 527 1.63 555 1.78 582 1.93 608 2.09 633 2.25 659 2.44 685 2.64 711 2.83 736
3-hp Standard Motor & Drive 3-hp Standard Motor & High Static Drive Accessory (b)
Continued
External Static Pressure (Inches of Water)
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive
2500 (a)
—
—
—
—
—
—
—
—
374 0.33 420 0.43 462 0.54 500 0.64 534 0.75 565 0.87 594 0.99 621
391 0.43 436 0.54 476 0.65 513 0.78 548 0.90 580 1.03 610 1.15 638
— — 368 0.44 412 0.55 453 0.67 492 0.79 528 0.93 561 1.07 593 1.21 624 1.36 653
4000 356 0.49 397 0.60 435 0.71 474 0.84 509 0.96 545 1.11 577 1.25 608 1.41 638 1.57 666
1.11
1.29
1.50
1.74
4500 390 0.67 428 0.79 462 0.90 496 1.04 531 1.18 563 1.33 594 1.48 625 1.64 653 1.81 681
5000 425 0.89 460 1.02 492 1.15 522 1.28 554 1.43 585 1.60 614 1.76 642 1.91 671 2.09 698
1.98
2.27
2.61
3.02
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive Accessory (b)
3-hp Standard Motor & High Static Drive Accessory (c)
648 1.23 673 1.36 697 1.49 720 1.62 742 1.76 764 1.90 785 2.04 806 2.18 825 2.33 845
664 1.42 689 1.56 713 1.71 737 1.86 759 2.00 781 2.15 802 2.31 822 2.46 842 2.62 861
680 1.64 706 1.79 730 1.94 754 2.10 776 2.27 797 2.43 818 2.60 839 2.77 858 2.94 878
2.47
2.78
3.11
4000 693 1.90 719 2.06 744 2.23 768 2.39 792 2.56 814 2.73 835 2.91 855 3.09 875 3.27 894
4500 707 2.16 733 2.35 758 2.53 782 2.72 805 2.90 827 3.09 849 3.27 870 3.46 891 3.65 911
5000 723 2.46 748 2.65 772 2.85 795 3.05 818 3.26 841 3.47 862 3.67 884 3.88 904 4.08 924
5500 741 2.81 765 3.01 788 3.21 811 3.42 833 3.63 855 3.85 876 4.08 897 4.31 917 4.53 937
6000 758 3.21 782 3.41 806 3.62 829 3.84 850 4.06 871 4.28 892 4.51 912 4.75 932 4.99 951
5-hp Oversized Motor & Drive
3.46
3.84
4.28
4.76
5.24
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
102 RT-PRC028AC-EN
Performance Data
Table 69. Evaporator fan performance—15 tons—TH*180G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive
3000 (a)
-
-
-
-
-
-
-
-
369 0.38
411 0.47
448 0.57
483 0.68
514 0.78
543 0.89
570 1.00
596 1.11
391 0.50
429 0.61
465 0.72
499 0.84
530 0.96
560 1.08
587 1.21
614 1.33
378 0.55
416 0.66
451 0.78
485 0.90
516 1.03
547 1.16
575 1.30
603 1.44
629 1.58
4800 370 0.62
408 0.74
443 0.87
476 0.99
507 1.12
537 1.26
565 1.40
593 1.55
619 1.71
645 1.86
5400 405 0.84
439 0.97
472 1.11
502 1.25
532 1.39
560 1.54
587 1.69
613 1.85
638 2.01
662 2.18
6000 440 1.11
472 1.25
502 1.40
531 1.56
558 1.72
584 1.87
610 2.03
635 2.20
659 2.37
682 2.54
6600 476 1.43
505 1.58
533 1.74
560 1.92
586 2.09
611 2.26
635 2.44
659 2.61
682 2.79
704 2.97
7200 512 1.81
539 1.98
565 2.15
590 2.33
615 2.52
639 2.71
661 2.90
683 3.08
706 3.28
727 3.47
3-hp Standard Motor & High Static Drive Accessory (b)
5-hp
Oversized
Motor &
Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive Accessory
3HP Standard Motor & High Static Drive Accessory (c)
620 1.23
643 1.35
664 1.47
684 1.59
703 1.72
722 1.86
740 1.99
757 2.13
775 2.27
791 2.41
638 1.46
662 1.59
684 1.73
705 1.86
726 2.00
746 2.14
765 2.28
784 2.42
801 2.57
817 2.72
654 1.73
678 1.87
701 2.02
723 2.17
744 2.32
764 2.47
784 2.62
802 2.78
821 2.94
839 3.10
4800 670 2.02
693 2.18
716 2.34
738 2.51
760 2.67
780 2.84
800 3.01
820 3.18
838 3.35
856 3.52
5400 686 2.35
709 2.52
732 2.70
753 2.88
775 3.06
795 3.24
815 3.42
835 3.61
854 3.80
872 3.98
6000 705 2.73
727 2.91
749 3.10
770 3.29
790 3.48
810 3.68
830 3.88
850 4.08
869 4.28
887 4.48
6600 725 3.16
747 3.35
767 3.55
788 3.75
808 3.96
827 4.17
846 4.37
865 4.59
884 4.80
902 5.02
7200 748 3.66
768 3.86
788 4.07
808 4.28
827 4.49
846 4.71
864 4.93
883 5.15
900 5.38
918 5.61
5-hp Oversized Motor & Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
RT-PRC028AC-EN 103
Performance Data
Table 70. Evaporator fan performance—15 tons—THD180G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
0.80
0.90
1.00
rpm bhp rpm bhp rpm bhp
3000 (a)
—
—
—
3-hp Standard Motor & Low Static Drive Accessory
— — — — — 387 0.49 424 0.61 458 0.72 489
3-hp Standard Motor & Drive
0.84 516 0.96 541 1.08 565 1.20
—
—
— — 367 0.51 407
354 0.54 391 0.67 426
0.63 441
0.80 460
0.76 472
0.94 492
0.89 502
1.08 520
1.02
1.23
532
546
1.16 559
1.38 572
1.30 584
1.54 598
1.44
1.70
4800 — — 383 0.73 418 0.86 449 1.01 480 1.15 510 1.31 540 1.48
5400 371 0.82 412 0.97 446 1.11 476 1.26 504 1.43 531 1.59 558 1.76
567
585
6000 403 1.08 441 1.25 475 1.41 504 1.57 530 1.74 555 1.93 580 2.11 604
6600 435 1.39 472 1.59 504 1.78 532 1.94 558 2.12 582 2.31 605 2.51 628
7200 467 1.75 502 1.98 533 2.19 561 2.38 587 2.56 610 2.76 632 2.97
3-hp Standard Motor & High Static Drive Accessory (b)
653
1.65 591
1.94 611
2.29 629
2.71
1.81 614
2.13 635
2.48 653
672
1.98
2.32
2.69
3.11
3.19 674 3.41 694
5-hp Oversized Motor & Drive
3.62
1.80
rpm
1.90
2.00
bhp rpm bhp rpm bhp
3-hp Standard Motor &
Drive
3-hp Standard Motor & High Static Drive Accessory (b)
3-hp Standard
Motor & High
Static Drive
Accessory (c)
587 1.32 609 1.44 629 1.57 649 1.70 668 1.83 687 1.97 705 2.11
608 1.58 629 1.72 650 1.87 670 2.01 689 2.16 708 2.30 725 2.45
723 2.25 740 2.39 758
743 2.61 760 2.76 776
2.54
2.92
623 1.86 647 2.03 669 2.19 690 2.36 709 2.52 728 2.68 746 2.85 764
4800 636 2.16 659 2.34 682 2.52 704 2.71 726 2.90 746 3.09 765 3.28 783
3.01 781
3.46
3.18 797
817
3.35
3.83
5400 656 2.51 677 2.70 698 2.89 717 3.09 738 3.29 758 3.50 778 3.71
6000 676 2.90 698 3.11 718 3.32 737 3.53 756 3.74 774 3.95 792 4.17
6600 694 3.33 716 3.56 737 3.79 758 4.02 777 4.25 795 4.48 812 4.71 829 4.94 846 5.18 862 5.42
7200 715 3.84 735 4.06 755 4.30 775 4.55 795 4.80 814 5.05 833 5.31 849.90 5.56 — — — —
5-hp Oversized Motor & Drive
798
810
3.92 817 4.13 835 4.34
4.40 829 4.63 847 4.86
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
104 RT-PRC028AC-EN
Performance Data
Table 71. Evaporator fan performance—15 tons—YH*180G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive
3000 (a)
-
-
-
-
376 0.39
417 0.49
454 0.59
488 0.69
519 0.80
547 0.91
574 1.02
600 1.13
359 0.42
400 0.52
438 0.63
473 0.75
506 0.87
537 0.99
566 1.11
594 1.24
619 1.36
390 0.59
427 0.70
462 0.81
495 0.94
526 1.07
555 1.21
584 1.34
611 1.48
637 1.63
4800 386 0.66
422 0.79
456 0.92
489 1.04
519 1.18
548 1.32
577 1.46
604 1.61
630 1.77
655 1.92
5400 422 0.90
456 1.04
487 1.18
517 1.32
546 1.47
574 1.62
600 1.77
626 1.93
651 2.09
675 2.26
6000 460 1.19
491 1.34
520 1.50
548 1.66
574 1.81
601 1.97
626 2.14
650 2.30
673 2.48
696 2.66
6600 498 1.54
526 1.70
554 1.87
580 2.05
605 2.22
629 2.39
653 2.57
676 2.75
699 2.93
720 3.11
7200 536 1.96
562 2.13
588 2.31
613 2.50
636 2.69
659 2.88
681 3.07
703 3.26
725 3.45
746 3.65
3-hp Standard Motor & High Static Drive Accessory (b)
5-hp
Oversized
Motor &
Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive Accessory
3HP Standard Motor & High Static Drive Accessory (c)
624 1.25
646 1.36
667 1.49
687 1.62
706 1.74
725 1.88
743 2.01
760 2.15
777 2.29
794 2.43
643 1.49
667 1.62
689 1.76
710 1.89
731 2.03
750 2.17
769 2.31
788 2.45
804 2.60
821 2.76
662 1.77
685 1.92
708 2.07
729 2.21
750 2.37
770 2.52
789 2.67
808 2.83
826 2.99
844 3.14
4800 679 2.08
703 2.24
725 2.41
747 2.57
768 2.74
789 2.91
808 3.08
827 3.25
845 3.42
863 3.59
5400 698 2.44
721 2.61
743 2.79
764 2.97
785 3.15
806 3.33
825 3.52
845 3.70
863 3.89
881 4.08
6000 719 2.84
741 3.03
762 3.22
783 3.41
803 3.61
823 3.80
842 4.00
862 4.20
880 4.40
898 4.61
6600 742 3.30
763 3.50
783 3.70
803 3.91
823 4.11
842 4.32
861 4.54
879 4.75
897 4.97
915 5.19
7200 766 3.84
786 4.05
806 4.26
825 4.47
844 4.68
863
5-hp Oversized Motor & Drive
4.91
881 5.13
899 5.36
916 5.58
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
RT-PRC028AC-EN 105
Performance Data
Table 72. Evaporator fan performance—15 tons—YHD180G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory
3000 (a)
—
—
—
—
—
—
—
—
355 0.40 393 0.51 429 0.63 463 0.74 493
377 0.53 415 0.66 448 0.79 478 0.91 509
— — 366 0.58 402 0.71 436 0.84 470 0.98 501 1.13 528
4800 358 0.66 397 0.78 430 0.92 461 1.07 492 1.21 522 1.38 551
3-hp Standard Motor & Drive
0.86 520 0.98 545 1.10 568
1.05 538 1.19 565 1.33 590
1.28 554 1.43 580 1.59 606
1.54 576 1.71 600 1.88 623
1.22
1.47
1.75
2.05
5400 393 0.90 430 1.04 461 1.19 490 1.35 517 1.51 545 1.67 572
6000 428 1.19 463 1.35 493 1.51 520 1.68 546 1.86 571 2.04 595
1.85 598 2.04 623 2.23 646
2.22 619 2.41 644 2.61 667
2.41
2.82
6600 463 1.54 496 1.73 525 1.90 552 2.07 576 2.26 599 2.46 622
7200 499 1.96 531 2.18 559 2.36 584 2.55 607 2.74 630 2.95 651
2.66 644
3.17 672
3-hp Standard Motor & High Static Drive Accessory (b)
2.86 666
3.38 692
3.06 688
3.60 713
3.27
3.82
5-hp Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor &
Drive
591 1.34 612 1.46 632 1.59 652
3-hp Standard Motor & High Static Drive Accessory
1.72 671 1.86 690 1.99 708
3HP Standard
Motor & High
Static Drive
Accessory (c)
2.13 725 2.27 743 2.42 761 2.56
613 1.61 634 1.76 655 1.90 674 2.04 693 2.19 712 2.34 729
631 1.91 654 2.08 676 2.24 696 2.40 715 2.57 734 2.73 752
2.49 746 2.64 763 2.79 780
2.90 769 3.07 786 3.23 802
2.95
3.41
4800
5400
6000
6600
7200
645 2.23 668
667 2.60 687
690 3.03 711
711 3.50 732
733 4.04 753
2.41 691
2.79 708
3.24 730
3.73 753
4.28 773
2.60 713
2.99 728
3.45 749
3.96 772
4.52 793
2.79 734 2.98 754
3.19 748 3.40 768
3.66 767 3.87 785
4.20 790 4.42 808
4.77 812 5.02 831
5-hp Oversized Motor & Drive
3.16 772
3.60 788
4.09 803
4.66 825
3.35 790 3.54 807 3.72 824
3.81 807 4.03 826 4.24 844
4.31 822 4.54 840 4.77 858
4.88 841 5.12 858 5.36 874
5.28 848.25 5.53 — — — — —
3.91
4.45
5.00
5.60
—
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
106 RT-PRC028AC-EN
Performance Data
Table 73. Evaporator fan performance— 17½ tons — TH*210G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive Accessory
3500 (a)
5600
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
— — 470 0.86 501 1.00 531 1.13 558 1.27 582
462 0.94 494 1.09 521 1.24 547 1.39 573 1.54 599
— — 455 1.06 485 1.20 515 1.36 544 1.53 572 1.70 596 1.88 619
458 1.21 487 1.37 514 1.54 541 1.71 567 1.88 593 2.07 619 2.26 643
1.41
1.71
2.05
2.46
6300 — — 459 1.43 492 1.60 520 1.76 546 1.94 570 2.13 594 2.32 618 2.51 641 2.70 664
7000 460 1.65 495 1.86 526 2.07 554 2.24 580 2.42 603 2.63 625 2.83 646 3.05 668 3.25 689
7700 498 2.13 531 2.38 562 2.62 589 2.82 614 3.02 637 3.22 658 3.44 678 3.66 698 3.90 717
8400 537 2.71 568 2.99 597 3.26 624 3.50 648 3.71 670 3.93 692 4.15 711 4.38 730 4.63 748
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive Accessory
2.91
3.47
4.13
4.88
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive Accessory
605 1.54 627 1.68 648 1.82 667 1.96 686 2.11 705 2.25 723 2.40 740 2.55 757 2.70 773
624 1.87 648 2.04 670 2.20 691 2.36 710 2.53 729 2.69 747 2.86 765 3.03 782 3.19 798
641 2.22 663 2.41 686 2.59 708 2.79 729 2.98 750 3.17 769 3.36 788 3.55 805 3.74 822
2.86
3.36
3.93
5600 665 2.65 686 2.85 706 3.05 725 3.25 745 3.45 764 3.66 784 3.88 803 4.09 822 4.31 841
6300 687 3.13 709 3.35 730 3.57 750 3.79 768 4.01 786 4.23 804 4.46 821 4.69 838 4.92 856
7000 710 3.68 731 3.91 752 4.15 772 4.40 792 4.64 811 4.89 828 5.14 845 5.38 861 5.62 878
7700 737 4.36 756 4.59 775 4.83 794 5.07 813 5.33 832 5.60 850 5.87 868 6.14 886 6.41 902
8400 767 5.14 784 5.38 802 5.63 820 5.89 837 6.15 854 6.41 872 6.68 889 6.97 907 7.26 924
7.5-hp Oversized Motor & Drive
4.54
5.15
5.87
6.68
7.55
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC028AC-EN 107
Performance Data
Table 74. Evaporator fan performance — 17½ tons — THD210G — dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
— — — — — — — — — —
5HP Standard Motor & Low
Static Drive Accessory
5HP Standard Motor & Drive
470 0.86 501 1.00 531 1.13 558 1.27 582 1.41 3500 (a)
—
—
—
—
—
—
—
—
—
—
—
—
— — 462 0.94 494 1.09 521 1.24 547 1.39 573 1.54 599
455 1.06 485 1.20 515 1.36 544 1.53 572 1.70 596 1.88 619
1.71
2.05
5600 — — — — 458 1.21 487 1.37 514 1.54 541 1.71 567 1.88 593 2.07 619 2.26 643
6300 — — 459 1.43 492 1.60 520 1.76 546 1.94 570 2.13 594 2.32 618 2.51 641 2.70 664
7000 460 1.65 495 1.86 526 2.07 554 2.24 580 2.42 603 2.63 625 2.83 646 3.05 668 3.25 689
7700 498 2.13 531 2.38 562 2.62 589 2.82 614 3.02 637 3.22 658 3.44 678 3.66 698 3.90 717
2.46
2.91
3.47
4.13
8400 537 2.71 568 2.99 597 3.26 624 3.50 648 3.71 670 3.93 692 4.15 711 4.38 730 4.63 748 4.88
5HP Standard Motor & High Static Drive Accessory
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5HP Standard Motor & Drive 5HP Standard Motor & High Static Drive Accessory
605 1.54 627 1.68 648 1.82 667 1.96 686 2.11 705 2.25 723 2.40 740 2.55 757 2.70 773
624 1.87 648 2.04 670 2.20 691 2.36 710 2.53 729 2.69 747 2.86 765 3.03 782 3.19 798
641 2.22 663 2.41 686 2.59 708 2.79 729 2.98 750 3.17 769 3.36 788 3.55 805 3.74 822
5600 665 2.65 686 2.85 706 3.05 725 3.25 745 3.45 764 3.66 784 3.88 803 4.09 822 4.31 841
2.86
3.36
3.93
4.54
6300 687 3.13 709 3.35 730 3.57 750 3.79 768 4.01 786 4.23 804 4.46 821 4.69 838 4.92 856
7000 710 3.68 731 3.91 752 4.15 772 4.40 792 4.64 811 4.89 828 5.14 845 5.38 861 5.62 878
7700 737 4.36 756 4.59 775 4.83 794 5.07 813 5.33 832 5.60 850 5.87 868 6.14 886 6.41 902
8400 767 5.14 784 5.38 802 5.63 820 5.89 837 6.15 854 6.41 872 6.68 889 6.97 907 7.26 924
5.15
5.87
6.68
7.55
7.5HP Oversized Motor & Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
108 RT-PRC028AC-EN
Performance Data
Table 75. Evaporator fan performance—17½ tons—YH*210G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive Accessory 5-hp Standard Motor & Drive
3500 (a)
4200
4900
5600
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
— — 476 0.89 508 1.02 537 1.16 563 1.30 587 1.43
472 0.99 502 1.14 529 1.28 555 1.43 581 1.59 607 1.76
— — 468 1.12 497 1.27 527 1.43 556 1.60 582 1.78 605 1.95 628 2.12
474 1.29 501 1.46 528 1.63 555 1.80 581 1.98 607 2.17 632 2.37 655 2.56
6300 — — 482 1.55 512 1.71 538 1.88 563 2.07 587 2.26 610 2.45 634 2.64 657 2.84 680 3.06
7000 490 1.84 522 2.04 550 2.22 576 2.39 599 2.59 621 2.80 643 3.01 665 3.22 686 3.43 707 3.65
7700 532 2.39 562 2.62 589 2.83 614 3.02 637 3.22 658 3.44 679 3.67 698 3.90 718 4.13 737 4.36
8400 574 3.03 603 3.30 629 3.55 653 3.76 675 3.97 696 4.20 715 4.43 734 4.68 752 4.93 770 5.18
5-hp Standard Motor & High Static Drive Accessory
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive Accessory
3500
4200
4900
610 1.57 631 1.71 652 1.85 672 1.99 690 2.14 709 2.28 726 2.43 744 2.58 760 2.73 777 2.89
632 1.92 655 2.09 677 2.25 697 2.41 716 2.58 735 2.74 753 2.91 770 3.08 787 3.24 803 3.42
650 2.30 673 2.48 695 2.67 717 2.86 738 3.06 758 3.25 777 3.44 795 3.63 812 3.82 829 4.01
5600 677 2.76 697 2.96 717 3.15 736 3.36 755 3.56 775 3.78 795 3.99 814 4.21 832 4.43 850 4.65
6300 702 3.28 724 3.50 744 3.72 762 3.94 781 4.17 798 4.39 816 4.61 833 4.84 850 5.08 868 5.32
7000 727 3.88 748 4.11 769 4.36 789 4.60 808 4.85 826 5.10 843 5.34 859 5.59 875 5.83 891 6.08
7700 756 4.59 775 4.83 794 5.08 813 5.34 832 5.60 851 5.87 869 6.15 886 6.41 903 6.69 918 6.96
8400 788 5.44 806 5.69 824 5.95 841 6.21 858 6.46 876 6.74 893 7.03 910 7.32 927 7.61 944 7.91
7.5-hp Oversized Motor & Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC028AC-EN 109
Performance Data
Table 76. Evaporator fan performance — 17½ tons — YHD210G — dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
7700 532 2.39 562 2.62 589 2.83 614 3.02 637 3.22 658 3.44 679 3.67 698 3.90 718 4.13 737
8400 574 3.03 603 3.30 629 3.55 653 3.76 675 3.97 696 4.20 715 4.43 734 4.68 752 4.93 770
5HP Standard Motor & High Static Drive Accessory
Continued
External Static Pressure (Inches of Water)
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5HP Standard Motor &
Low Static Drive
Accessory
5HP Standard Motor & Drive
474 1.29 501 1.46 528 1.63 555 1.80 581 1.98 607 2.17 632 2.37 655 5600 — — — —
6300 — —
1.71 538 1.88 563 2.07 587 2.26 610 2.45 634 2.64 657 2.84 680
7000 490 1.84
(a) 522 2.04 550 2.22 576 2.39 599 2.59 621 2.80 643 3.01 665 3.22 686 3.43 707
2.56
3.06
3.65
4.36
5.18
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5HP Standard Motor & High Static Drive Accessory
5600 677 2.76
(b) 697 2.96 717 3.15 736 3.36 755 3.56 775 3.78 795 3.99 814 4.21 832 4.43 850 4.65
6300 702 3.28 724 3.50 744 3.72 762 3.94 781 4.17 798 4.39 816 4.61 833 4.84 850 5.08 868 5.32
7000 727 3.88 748 4.11 769 4.36 789 4.60 808 4.85 826 5.10 843 5.34 859 5.59 875 5.83 891 6.08
7700 756 4.59 775 4.83 794 5.08 813 5.34 832 5.60 851 5.87 869 6.15 886 6.41 903 6.69 918 6.96
8400 788 5.44 806 5.69 824 5.95 841 6.21 858 6.46 876 6.74 893 7.03 910 7.32 927 7.61 944
7.5HP Oversized Motor & Drive
7.91
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)5HP Standard Motor & Low Static Drive Accessory
(b)5HP Standard Motor & Drive
110 RT-PRC028AC-EN
Performance Data
Table 77. Evaporator fan performance—20 tons—TH*240G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive Accessory 5-hp Standard Motor & Drive
4000 (a)
6400
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
— — 456 0.88 486 1.02 514 1.16 541 1.31 569 1.46 595
451 1.02 481 1.16 512 1.32 541 1.49 568 1.66 592 1.82 615
— — 458 1.21 487 1.37 514 1.54 541 1.71 567 1.88 593 2.07 619 2.26 643
464 1.49 497 1.66 525 1.82 551 2.00 575 2.20 598 2.39 622 2.58 645 2.78 667
1.62
1.99
2.46
2.98
7200 470 1.77 505 2.00 536 2.21 564 2.40 589 2.58 612 2.78 634 3.00 655 3.21 676 3.43 697
8000 514 2.37 547 2.63 577 2.87 603 3.10 628 3.30 651 3.51 672 3.73 692 3.96 711 4.20 730
8800 560 3.10 590 3.38 618 3.65 644 3.92 667 4.16 690 4.39 711 4.61 731 4.84 749 5.09 767
9600 606 3.97 633 4.27 660 4.59 685 4.88 708 5.15 729 5.42 750 5.66 769 5.91 788 6.16 805
5-hp Standard Motor & High Static Drive Accessory
7.5-hp Oversized Motor & Field Supplied Motor Sheave (b)
Continued
External Static Pressure (Inches of Water)
3.65
4.44
5.35
6.42
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive Accessory
620 1.78 643 1.93 664 2.09 685 2.25 704 2.40 722 2.56 740 2.72 758 2.88 775 3.05 791
638 2.17 661 2.35 684 2.54 706 2.72 727 2.91 747 3.10 767 3.29 785 3.48 802 3.66 819
665 2.65 686 2.85 706 3.05 725 3.25 745 3.45 764 3.66 784 3.88 803 4.09 822 4.31 841
3.21
3.85
4.54
6400 690 3.20 712 3.43 733 3.65 753 3.88 772 4.10 790 4.32 807 4.55 824 4.78 841 5.01 858
7200 717 3.86 737 4.09 758 4.33 778 4.58 798 4.83 817 5.08 835 5.34 852 5.59 868 5.84 885
8000 749 4.68 768 4.92 786 5.16 804 5.41 823 5.66 841 5.93 859 6.20 877 6.48 895 6.76 912
8800 784 5.61 802 5.89
(b) 819 6.15 836 6.41 853 6.67 869 6.95 886 7.21 902 7.49 919 7.78 936
9600 822 6.69 839 6.98 854 7.26 870
7.5-hp Oversized Motor & Drive
7.55 886 7.85 901 8.13 917 8.42 — — —
7.5-hp Oversized Motor & Field Supplied Motor Sheave (c)
— —
5.25
6.10
7.04
8.09
—
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
9.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)7.5-hp Oversized Motor & Field Supplied Motor Sheave (c)
(c) Field supplied motor sheave 1VP50 x 1 1/8 required.
RT-PRC028AC-EN 111
Performance Data
Table 78. Evaporator fan performance—20 tons—THD240G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive Accessory 5-hp Standard Motor & Drive
4000 (a)
6400
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
— — 454 0.88 485 1.01 513 1.16 540 1.30 568 1.46 594
449 1.01 480 1.15 510 1.31 540 1.48 567 1.65 591 1.81 614
— — 456 1.20 485 1.36 512 1.53 539 1.70 565 1.87 591 2.05 617 2.24 641
461 1.47 494 1.65 523 1.81 549 1.99 573 2.18 596 2.37 619 2.56 642 2.76 665
1.61
1.98
2.44
2.96
7200 467 1.75 502 1.98 533 2.19 561 2.38 587 2.56 610 2.76 632 2.97 653 3.19 674 3.41 694
8000 511 2.35 544 2.60 573 2.85 601 3.08 625 3.28 648 3.48 670 3.70 690 3.93 709 4.16 728
3.62
4.41
8800 556 3.06 586 3.34 614 3.62 640 3.89 664 4.13 687 4.36 708 4.58 728 4.80 746 5.05 764
9600 601 3.91 629 4.22 656 4.53 680 4.82 704 5.12 726 5.38 746 5.62 766 5.87 784 6.10 802
5-hp Standard Motor & High Static Drive Accessory 7.5-hp Oversized Motor & Field Supplied Motor Sheave (b)
5.31
6.37
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive Accessory
619 1.77 642 1.93 663 2.08 683 2.24 703 2.39 721 2.55 739 2.71 757 2.87 774 3.04 790
636 2.16 659 2.34 682 2.52 704 2.71 726 2.90 746 3.09 765 3.28 783 3.46 801 3.65 817
663 2.64 684 2.83 704 3.03 724 3.23 743 3.43 763 3.64 782 3.86 802 4.08 821 4.29 839
3.20
3.83
4.51
6400 688 3.18 710 3.40 731 3.63 751 3.85 770 4.08 788 4.30 805 4.52 822 4.75 839 4.98 856
7200 715 3.84 735 4.06 755 4.30 775 4.55 795 4.80 814 5.05 833 5.31 850 5.56 866 5.81 882
8000 747 4.65 765 4.89 784 5.12 802 5.37 820 5.62 838 5.89 856 6.16 874 6.44 892 6.71 909
8800 782 5.57 799 5.84
(c) 816 6.10 833 6.36 850 6.63 866 6.89 883 7.16 899 7.44 916 7.73 933
9600 819 6.64 835 6.92 851 7.21 867 7.49 883 7.79 898
7.5-hp Oversized Motor & Field Supplied Motor Sheave
8.08 914 8.36 —
7.5-hp Oversized Motor & Drive
— — — —
5.22
6.06
7.00
8.03
—
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Field supplied motor sheave 1VP50 x 1 1/8 required.
(c) 7.5-hp Oversized Motor & Field Supplied Motor Sheave (b)
112 RT-PRC028AC-EN
Performance Data
Table 79. Evaporator fan performance—20 tons—YH*240G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive Accessory 5-hp Standard Motor & Drive
4000 (a)
—
—
—
—
—
—
—
—
—
—
—
—
— — 465 0.92 494 1.06 522 1.20 549 1.35 576 1.51 602 1.66
463 1.07 493 1.22 524 1.39 552 1.56 578 1.72 601 1.89 624 2.06
— — — — 474 1.29 501 1.46 528 1.63 555 1.80 581 1.98 607 2.17 632 2.37 655 2.56
6400 454 1.43 487 1.61 517 1.77 544 1.95 568 2.14 591 2.33 615 2.52 638 2.72 661 2.92 684 3.14
7200 502 1.98 533 2.19 561 2.38 587 2.56 610 2.76 632 2.97 653 3.19 674 3.41 695 3.63 715
8000 550 2.64 579 2.89 606 3.12 631 3.32 653 3.53 674 3.75 694 3.98 713 4.22 732 4.47 751
8800 599 3.46 627 3.75 652 4.00 675 4.23 697 4.45 718 4.69 737 4.93 755 5.18 773 5.44 790
9600 648 4.44 674 4.74 698 5.04 721 5.33 742 5.56 761 5.80 780 6.05 798 6.30 815 6.58 832
5-hp Standard Motor &
High Static Drive Accessory
7.5-hp Oversized Motor &
Field Supplied Motor Sheave (b)
7.5-hp Oversized
Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
3.84
4.70
5.71
6.86 cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor Drive 5-hp Standard Motor & High Static Drive Accessory
627 1.82 649 1.98 670 2.13 690 2.29 709 2.45 728 2.61 745 2.77 763 2.93 779 3.09 796 3.26
647 2.24 670 2.42 693 2.61 714 2.80 735 2.99 755 3.18 774 3.36 792 3.55 809 3.74 825 3.92
677 2.76 697 2.96 717 3.15 736 3.36 755 3.56 775 3.78 795 3.99 814 4.21 832 4.43 850 4.65
6400 706 3.36 727 3.58 748 3.81 766 4.03 784 4.26 802 4.48 819 4.71 836 4.94 853 5.18 870 5.42
7200 735 4.07 756 4.31 776 4.56 795 4.80 815 5.06 833 5.31 850 5.57 867 5.81 883 6.06 899
8000 770 4.94 788 5.18 806 5.44 825 5.69 843 5.96 861 6.23 879 6.51 896 6.79 913 7.07 930
8800 807 5.97 825 6.23 841 6.50 858 6.77 875 7.03 891 7.30 908 7.58 925 7.89 941 8.19 958
9600 848 7.14 864 7.43 879 7.73 895 8.01 911 8.30 926 8.59 — — — — — — —
6.32
7.36
8.49
—
7.5-hp Oversized Motor & Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Field supplied motor sheave 1VP50 x 1 1/8 required.
RT-PRC028AC-EN 113
Performance Data
Table 80. Evaporator fan performance—20 tons—YHD240G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive Accessory 5-hp Standard Motor & Drive
4000 (a)
—
—
—
—
—
—
—
—
—
—
—
—
— — 464 0.91 493 1.05 521 1.20 548 1.34 575 1.50 601 1.66
461 1.07 492 1.21 522 1.38 551 1.54 576 1.71 600 1.88 623 2.05
— — — — 472 1.28 500 1.45 527 1.62 553 1.79 579 1.96 605 2.15 630 2.35 654 2.55
6400 451 1.42 485 1.60 515 1.76 541 1.93 566 2.12 589 2.32 613 2.51 636 2.70 658 2.90 681 3.12
7200 499 1.96 531 2.18 559 2.36 584 2.55 607 2.74 630 2.95 651 3.17 672 3.38 692 3.60 713
8000 548 2.64 577 2.88 603 3.10 627 3.29 650 3.50 672 3.72 691 3.95 711 4.19 730 4.43 748
3.82
4.67
8800 596 3.45 623 3.71 649 3.97 672 4.21 694 4.43 715 4.66 734 4.89 752 5.13 770 5.39 787 5.66
(b)
9600 645 4.41 670 4.70 694 4.98 717 5.26 738 5.52 758 5.76 777 6.00 795 6.25 812 6.52 829 6.80
5-hp Standard Motor
& High Static Drive
Accessory
7.5-hp Oversized Motor
& Field Supplied Motor Sheave (c)
7.5-hp Oversized Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor Drive 5-hp Standard Motor & High Static Drive Accessory
626 1.81 648 1.97 669 2.12 689 2.28 708 2.44 726 2.60 744 2.76 762 2.92 778 3.08 795 3.25
645 2.23 668 2.41 691 2.60 713 2.79 734 2.98 754 3.16 772 3.35 790 3.54 807 3.72 824 3.91
675 2.74 695 2.94 715 3.14 734 3.34 753 3.54 773 3.76 793 3.97 812 4.19 831 4.41 849 4.63
6400 704 3.34 725 3.56 746 3.79 764 4.01 783 4.23 800 4.46 817 4.69 834 4.91 851 5.15 868 5.39
7200 733 4.04 753 4.28 773 4.52 793 4.77 812 5.02 831 5.28 848 5.53 865 5.78 881 6.03 896
8000 767 4.91 785 5.15 804 5.40 822 5.65 840 5.92 858 6.19 876 6.46 894 6.75 911 7.03 927
8800 805 5.93
(d) 822 6.19 839 6.45 855 6.72 872 6.99 888 7.25 905 7.54 922 7.83 938 8.13 955
— — — — — — 9600 845 7.09 861 7.38 876 7.67 892 7.96 907 8.24 923 8.52 —
7.5-hp Oversized Motor
& Field Supplied Motor Sheave (c)
7.5-hp Oversized Motor & Drive
6.29
7.31
8.43
—
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)5-hp Standard Motor & High Static Drive Accessory
(c) Field supplied motor sheave 1VP50 x 1 1/8 required.
(d)7.5-hp Oversized Motor & Field Supplied Motor Sheave (c)
114 RT-PRC028AC-EN
Performance Data
Table 81. Evaporator fan performance—25 tons—TH*300G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Drive
5000 (a)
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
— — — — 575 1.75 599 1.93 622 2.10
579 2.26 603 2.46 626 2.65 648 2.85 671 3.06
— — 580 2.42 603 2.63 625 2.83 646 3.05 668 3.25 689 3.47
579 2.65 604 2.84 627 3.04 648 3.26 669 3.48 689 3.71 709 3.93
8000
8500
—
—
—
—
— — 577 2.87 603 3.10 628 3.30 651 3.51 672 3.73 692 3.96 711 4.20 730 4.44
574 3.09 602 3.34 628 3.60 653 3.83 675 4.04 696 4.25 716 4.49 735 4.74 753 5.00
9000 572 3.31 600 3.58 628 3.87 654 4.15 678 4.40 700 4.63 720 4.86 740 5.08 759 5.34 777 5.60
9500 600 3.85 628 4.17 655 4.47 680 4.75 703 5.02 724 5.27 745 5.52 764 5.76 783 6.00 801 6.28
10000 627 4.42 656 4.78 681 5.09 705 5.41 728 5.71 749 5.99 770 6.26 789 6.50 807 6.76 825 7.02
10500 657 5.13 683 5.45 708 5.80 731 6.13 753 6.44 775 6.76 794 7.04 813 7.31 831 7.57 849 7.84
11000 685 5.81 711 6.21 735 6.58 758 6.93 778 7.23 800 7.58 819 7.88 838 8.19 856 8.45 —
7.5-hp Standard Motor & High Static Drive Accessory
—
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Drive
644
693
710
2.28 666
3.28 715
3.68 731
2.46 688
3.50 736
3.91 752
2.65 710
3.73 757
4.15 772
2.85 731
3.96 775
4.40 792
3.04
4.19
4.64
729 4.16 748 4.38 768 4.62 787 4.87 807 5.13
8000 749 4.68 768 4.92 786 5.16 804 5.41 823 5.66
8500 771 5.25 789 5.51 806 5.76 824 6.02 841 6.28
9000 794 5.87 811 6.14 827 6.41 844 6.69 861 6.95
9500 817 6.55 834 6.83 850 7.12 866 7.41 882 7.69
10000 841 7.29 857 7.59 873 7.87 888 8.18 904 8.48
10500 865 8.11 881 8.41 —
11000 — — — — —
—
—
—
—
—
—
—
—
7.5-hp Standard Motor & High Static Drive Accessory
—
—
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC028AC-EN 115
Performance Data
Table 82. Evaporator fan performance—25 tons—THD300G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Low Static Drive
5000 (a)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
602 1.57
633 1.73
661 1.89
688 2.05
587 2.00
614 2.18
640 2.35
665 2.53
690 2.70
714 2.89
739 3.08
588 2.19
616 2.39
641 2.57
666 2.75
690 2.94
713 3.13
736 3.32
759 3.52
593 2.42
620 2.63
645 2.82
670 3.02
693 3.21
716 3.41
738 3.61
760 3.82
782 4.02
8000 597 2.66
625 2.89
650 3.09
674 3.29
698 3.51
722 3.73
743 3.93
765 4.15
785 4.36
806 4.57
8500 632 3.18
658 3.41
683 3.64
706 3.86
728 4.07
750 4.29
771 4.51
792 4.74
812 4.97
832 5.20
9000 666 3.74
692 4.00
714 4.22
737 4.46
757 4.67
779 4.92
799 5.15
819 5.39
839 5.64
858 5.88
9500 701 4.38
726 4.67
746 4.87
769 5.15
788 5.36
808 5.61
828 5.86
847 6.10
866 6.36
885 6.62
10000 737 5.11
760 5.39
778 5.60
800 5.89
819 6.11
838 6.37
858 6.64
876 6.89
895 7.17
913 7.45
10500 766 5.76
792 6.15
813 6.44
832 6.70
851 6.96
869 7.21
888 7.50
905 7.75
923 8.05
941 8.33
11000 806 6.73
824 6.98
844 7.27
864 7.56
883 7.88
900 8.14
918 8.44
7.5-hp Standard Motor & Drive
-
7.5-hp Standard Motor & High Static Drive Accessory
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor &
Low Static Drive
7.5-hp Standard Motor & Drive
712 2.20
736 2.36
758 2.52
779 2.67
799 2.82
763 3.28
787 3.48
810 3.69
833 3.90
855 4.11
782 3.73
805 3.94
827 4.15
849 4.37
871 4.59
803 4.23
825 4.44
846 4.66
867 4.89
888 5.12
8000 826 4.79
846 5.01
867 5.24
886 5.47
906 5.71
8500 851 5.42
870 5.65
889 5.88
908 6.12
927 6.37
9000 876 6.11
895 6.36
913 6.61
931 6.85
949 7.09
9500 903 6.88
921 7.13
938 7.38
955 7.63
973 7.89
10000 930 7.70
947 7.97
964 8.22
981 8.50
-
10500 958 8.60
11000 -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Standard Motor & High Static Drive Accessory
-
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
116 RT-PRC028AC-EN
Performance Data
Table 83. Evaporator fan performance—25 tons—YH*300G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Drive
5000 (a)
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
— — — — 586 1.83 609 2.00 632 2.18
596 2.41 619 2.60 642 2.80 664 3.00 687 3.22
— — 599 2.59 621 2.80 643 3.01 665 3.22 686 3.43 707 3.65
603 2.83 626 3.03 648 3.25 668 3.47 688 3.70 708 3.92 728 4.15
8000 — — — — 606 3.12 631 3.32 653 3.53 674 3.75 694 3.98 713 4.22 732 4.47 751
8500 582 3.16 609 3.41 635 3.66 658 3.87 680 4.09 701 4.31 721 4.55 739 4.80 757 5.05 775
9000 611 3.68 639 3.99 664 4.25 687 4.49 708 4.73 728 4.95 748 5.18 766 5.44 783 5.71 800
9500 644 4.36 668 4.60 692 4.89 715 5.16 736 5.41 756 5.66 775 5.89 793 6.15 810 6.43 826
10000 676 5.05 698 5.31 722 5.62 744 5.93 764 6.19 784 6.44 802 6.68 820 6.95 837 7.22 853
10500 703 5.70 728 6.07 752 6.43 772 6.72 792 7.00 811 7.27 829 7.54 847 7.81 864 8.08 880
11000 739 6.65 759 6.93 780 7.27 801 7.58 821 7.92 840 8.23 857 8.48 —
7.5-hp Standard Motor & High Static Drive Accessory
— — — —
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
4.70
5.31
5.98
6.71
7.51
8.38
—
7.5-hp Standard Motor & Drive
653 2.36 675 2.54 697 2.74 719 2.93 740 3.13
709 3.44 731 3.67 751 3.90 770 4.13 788 4.35
727 3.88 748 4.11 769 4.36 789 4.60 808 4.85
748 4.37 767 4.61 787 4.86 806 5.12 825 5.38
8000 770 4.94 788 5.18 806 5.44 825 5.69 843 5.96
8500 793 5.57 811 5.83 828 6.08 845 6.34 862 6.61
9000 817 6.25 834 6.52 851 6.79 867 7.06 884 7.34
9500 843 6.99 858 7.27 875 7.57 890 7.84 906 8.13
10000 869 7.79 884 8.10 899 8.39 — — — —
10500
11000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7.5-hp Standard Motor & High Static Drive Accessory
—
—
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC028AC-EN 117
Performance Data
Table 84. Evaporator fan performance—25 tons—YHD300G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Low Static Drive Accessory
5000 (a)
-
-
-
-
-
-
-
-
-
-
-
-
584 1.48
613 1.63
642 1.78
670 1.94
696 2.10
606 2.13
633 2.30
658 2.47
683 2.65
708 2.84
732 3.03
756 3.22
585 2.17
612 2.36
637 2.54
662 2.72
686 2.91
710 3.10
733 3.30
756 3.49
779 3.70
593 2.44
618 2.60
645 2.82
668 3.01
692 3.20
716 3.41
737 3.60
760 3.81
781 4.01
803 4.23
8000 626 2.88
654 3.12
677 3.32
700 3.53
723 3.75
745 3.95
767 4.17
788 4.38
808 4.60
829 4.82
8500 665 3.48
688 3.68
711 3.90
733 4.13
755 4.35
776 4.57
797 4.80
816 5.02
836 5.25
855 5.47
9000 702 4.11
723 4.31
745 4.54
766 4.78
787 5.02
807 5.26
827 5.49
846 5.73
865 5.97
884 6.21
9500 734 4.72
758 5.01
780 5.27
799 5.49
820 5.77
838 5.99
858 6.27
876 6.50
895 6.76
913 7.02
10000 771 5.49
796 5.83
815 6.09
835 6.34
852 6.55
871 6.82
889 7.10
907 7.35
925 7.63
942 7.89
10500 814 6.50
831 6.68
848 6.90
869 7.23
886 7.46
903 7.73
921 8.00
939 8.30
956 8.57
-
11000 848 7.34
866 7.61
885
7.5-hp Standard Motor & Drive
7.92
903 8.19
920 8.46
-
7.5-hp Standard Motor & High Static Drive Accessory
-
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
722 2.27
(b) 746
7.5-hp Standard Motor & Drive
2.43
770 2.60
791 2.76
812 2.92
779 3.41
801 3.61
823 3.81
845 4.01
866 4.22
801 3.90
822 4.10
844 4.31
865 4.53
885 4.75
824 4.44
845 4.66
866 4.88
886 5.10
905 5.32
8000 849 5.05
869 5.27
889 5.51
908 5.73
927 5.97
8500 875 5.72
895 5.96
913 6.19
932 6.43
951 6.68
9000 902 6.45
921 6.71
938 6.94
956 7.19
975 7.46
9500 930 7.26
948 7.52
965 7.77
983 8.04
10000 959 8.15
976 8.41
-
-
-
-
-
10500
11000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Standard Motor & High Static Drive Accessory
-
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 120 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)7.5-hp Standard Motor & Low Static Drive Accessory.
118 RT-PRC028AC-EN
Performance Data
Table 85. Standard motor and drive/fan speed (rpm)
Tons Unit Model Number
12½
15
T/YS*150G3,4,W,K
T/YH*150G3,4,W
T/YS*180G3,4,W,K
T/YH*180G3,4,W
17½ T/YS*210/211G3,4,W,K
T/YH*210G3,4,W
T/YS*240G3,4,W,K 20
T/YH*240G3,4,W
T/YS*300/301G3,4,W,K
T/YH*300G3,4,W
25
T/YH*300G3,4,W with
Reheat
Note: Factory set at 3 turns open.
6 Turns
Open
605
506
605
506
694
581
642
452
559
452
694
5 Turns
Open
650
544
650
544
731
619
683
485
600
485
739
4 Turns
Open
695
582
695
582
768
657
725
518
642
518
784
3 Turns
Open
740
620
740
620
805
695
766
551
683
551
829
2 Turns
Open
785
658
785
658
842
733
808
584
725
584
874
1 Turn
Open
829
694
829
694
881
769
849
619
766
619
919
Closed
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Table 86. Standard motor and low static fan drive
Tons
12½
15
17½
20
25
Unit Model Number
T/YS*150G3,4,W,K
T/YH*150G3,4,W
T/YS*180G3,4,W,K
T/YH*180G3,4,W
T/YS*210/211G3,4,W,K
T/YH*210G3,4,W
T/YS*240G3,4,W,K
T/YH*240G3,4,W
T/YS*300/301G3,4,W,K
T/YH*300G3,4,W with
Reheat
6 Turns
Open
452
450
506
450
581
351
452
351
506
581
5 Turns
Open
485
480
544
480
619
377
485
377
544
619
4 Turns
Open
518
510
582
510
657
403
518
403
582
657
3 Turns
Open
551
540
620
540
695
429
551
429
620
695
2 Turns
Open
584
570
658
570
733
455
584
455
658
733
1Turn
Open Closed
619 N/A
600
694
600
769
480
619
480
694
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
769 N/A
Table 87. Standard motor and high static drive accessory sheave/fan speed (rpm)
Tons
12½
15
17½
20
25
Unit Model Number
T/YS*150G3,4,W,K
T/YH*150G3,4,W
T/YS*180G3,4,W,K
T/YH*180G3,4,W
T/YS*210/211G3,4,W,K
T/YH*210G3,4,W
T/YS*240G3,4,W,K
T/YH*240G3,4,W
T/YS*300/301G3,4,W,K
T/YH*300G3,4,W
T/YH*300G3,4,W with
Reheat
6 Turns
Open
694
829
694
806
694
766
619
719
619
829
806
5 Turns
Open
731
874
731
844
739
808
652
753
652
874
844
4 Turns
Open
768
919
768
882
784
849
685
786
685
919
882
3 Turns
Open
805
964
805
920
829
891
718
820
718
964
920
2 Turns
Open
842
1009
842
958
874
891
751
853
751
1009
958
1 Turn
Open
881
1053
881
994
919
974
786
887
786
1053
994
Closed
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
RT-PRC028AC-EN 119
Performance Data
Table 88. Oversized motor and drive/fan speed (rpm)
Tons
12½
15
17½
20
Unit Model
Number
T/YS*150G3,4,W,K
T/YH*150G3,4,W
T/YS*180G3,4,W,K
T/YH*180G3,4,W
T/YS*210/211G3,4,W,K
T/YH*210G3,4,W
T/YS*240G3,4,W,K
T/YH*240G3,4,W
6 Turns
Open
863
695
695
695
806
806
806
806
5 Turns
Open
919
747
747
747
844
844
844
844
4 Turns
Open
974
799
799
799
882
882
882
882
3 Turns
Open
1030
851
851
851
920
920
920
920
2 Turns
Open
1085
903
903
903
958
958
958
958
1 Turn
Open Closed
1141 N/A
953
953
953
994
994
N/A
N/A
N/A
N/A
N/A
994
994
N/A
N/A
Table 89. Static pressure drop through accessories (inches water column)
Tons
12½
15
6000
2500
4000
5000
6000
4800
6000
7200
4000
5000
6000
4000
5000
6000
4000
5000
4800
6000
7200
4800
6000
7200
3000
4800
6000
7200
Unit Model
Number cfm (a)
Std
Filters (b)
Through
Reheat
Coil
2”
MERV 8
Filter (c)
2”
MERV 13
Filter
T/YSH150G
T/YSD150G
T/YHH150G
T/YHD150G
T/YSH180G
T/YSD180G
T/YHH180G
T/YHD180G
0.05
0.07
—
—
0.10 —
0.05
—
0.07
—
0.10 —
0.02 —
0.03 —
0.08
0.11
0.15
0.08
0.11
0.15
0.05 —
0.01 0.00 0.01 0.03
0.02 0.01 0.04 0.08
0.03 0.02 0.05 0.11
0.05 0.03 0.07 0.13
0.03 — 0.06
0.09
0.05 —
0.07 —
0.09
0.11
0.13
0.16
0.07
0.11
0.04 —
0.06 —
0.09 —
0.03 —
0.05 —
0.07 —
0.02 0.01
0.04 0.01
0.06 0.02
0.09 0.03
0.13
0.04
0.06
0.08
0.02
0.05
0.06
0.08
0.18
0.06
0.1
0.13
0.03
0.08
0.11
0.14
0.12
0.15
0.19
0.12
0.15
0.19
Std
Economizer with
OA/RA
Dampers (d)
100%
OA
100%
RA
Low Leak
Economizer with
OA/RA
Electric Heater
Accessory (kW)
100%
OA
100%
RA 14–27 36 54
(e)
72
0.33
0.07
0.19
0.26
0.33
0.14
0.19
0.26
0.33
0.19
0.26
0.33
0.19
0.26
0.27
0.14
0.27
0.14
0.27
0.07
0.14
0.2
0.27
0.04
0.01
0.02
0.03
0.04
0.03
0.02
0.03
0.04
0.02
0.03
0.04
0.02
0.03
0.05
0.03
0.05
0.03
0.05
0.03
0.03
0.04
0.05
0.57
0.07
0.16
0.24
0.33
0.36
0.57
0.81
0.27
0.42
0.61
0.27
0.41
0.58
0.25
0.39
0.22
0.33
0.45
0.36
0.57
0.81
0.10
0.22
0.33
0.45
0.10
0.04
0.10
0.16
0.24
0.06
0.10
0.14
0.06
0.10
0.14
0.18
0.29
0.44
0.04
0.07
0.15
0.24
0.35
0.06
0.10
0.14
0.06
0.15
0.24
0.35
0.07
*
0.03
0.05
0.07
0.04
0.07
0.03
0.05
0.07
0.03
0.05
0.07
0.03
0.05
0.06
*
0.03
0.04
0.06
0.04
0.06
0.09
0.03
0.04
0.06
0.03
0.04
0.06
0.03
0.04
0.04
0.06
0.09
0.04
0.06
0.09
*
0.04
0.06
0.09
0.04
0.07
0.04
0.07
*
0.04
0.07
0.1
0.09
*
0.04
0.06
0.09
0.05
0.08
0.04
0.06
0.09
0.04
0.06
0.09
0.04
0.06
0.05
0.08
0.05
0.08
*
0.05
0.08
0.12
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
120 RT-PRC028AC-EN
Performance Data
Table 89. Static pressure drop through accessories (inches water column) (continued)
Tons
17½
20
25
Unit Model
Number cfm (a)
Std
Filters (b)
Through
Reheat
Coil
2”
MERV 8
Filter (c)
2”
MERV 13
Filter (c)
T/YSH210/
211G
T/YSD210/
211G
T/YHH210G
T/YHD210G
T/YSH240G
T/YSD240G
T/YHH240G
T/YHD240G
T/YSH300/
301G
T/YSD300/
301G
T/YHH300G
T/YHD300G
8000
9600
7000
9000
11000
7000
9000
11000
6400
8000
9600
6400
8000
9600
4000
6400
7000
9000
11000
5000
7000
9000
11000
8400
3500
5600
7000
8400
6400
8000
9600
5600
7000
8400
5600
7000
8400
5600
7000
0.05 —
0.07 —
0.10 —
0.06 —
0.09 —
0.12 —
0.03 —
0.05 —
0.07 —
0.01 0.04
0.04 0.10
0.06 0.13
0.08 0.16
0.06 —
0.09 —
0.13 —
0.02 0.04
0.05 0.10
0.08 0.13
0.10 0.16
0.17
0.21
0.07 —
0.11 —
0.16 —
0.04 —
0.06 —
0.09 —
0.02 0.02 0.03 0.06
0.05 0.05 0.08 0.12
0.08 0.07 0.10 0.15
0.11 0.11 0.14 0.19
0.07
0.11
—
—
0.11
0.15
0.15
0.20
0.17
0.09
0.14
0.21
—
—
—
—
0.22
0.13
0.18
0.25
0.26
0.17
0.23
0.32
0.05 —
0.08 —
0.12 —
0.03 0.02
0.06 0.04
0.10 0.06
0.10
0.08
0.04 0.08
0.09 0.13
0.12 0.18
0.17
0.22
Std
Economizer with
OA/RA
Dampers (d)
100%
OA
100%
RA
Low Leak
Economizer with
OA/RA
Dampers (d)
Electric Heater
Accessory (kW)
100%
OA
100%
RA 14–27 36 54
(e)
72
0.32
0.44
0.26
0.4
0.6
0.26
0.4
0.57
0.22
0.32
0.44
0.22
0.32
0.44
0.11
0.22
0.26
0.4
0.6
0.15
0.26
0.4
0.57
0.35
0.09
0.18
0.26
0.35
0.22
0.32
0.44
0.18
0.26
0.35
0.18
0.26
0.35
0.18
0.26
0.05
0.07
0.04
0.07
0.1
0.04
0.07
0.1
0.04
0.05
0.07
0.04
0.05
0.07
0.03
0.04
0.04
0.07
0.1
0.03
0.04
0.07
0.10
0.06
0.03
0.04
0.04
0.06
0.04
0.05
0.07
0.04
0.04
0.06
0.04
0.04
0.06
0.04
0.04
0.54
0.75
0.77
1.27
1.89
0.43
0.67
0.95
0.37
0.54
0.75
0.64
1.0
1.44
0.16
0.37
0.77
1.27
1.89
0.24
0.43
0.67
0.95
1.11
0.13
0.29
0.43
0.59
0.64
1.0
1.44
0.49
0.77
1.11
0.29
0.43
0.59
0.49
0.77
0.43
0.62
0.13
0.21
0.32
0.33
0.55
0.82
0.27
0.43
0.62
0.11
0.17
0.24
0.10
0.27
0.13
0.21
0.32
0.16
0.33
0.55
0.82
0.19
0.08
0.21
0.33
0.48
0.11
0.17
0.24
0.08
0.13
0.19
0.21
0.33
0.48
0.08
0.13
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.08
0.13
0.18
*
0.08
0.13
0.18
0.05
0.08
0.12
0.05
0.08
0.12
0.05
0.08
0.12
*
0.05
0.08
0.13
*
0.06
0.09
0.12
0.06
0.13
0.08
0.10 0.12
0.14
0.17
0.06
0.09
0.13
0.06
0.09
0.13
0.06
0.09
0.06
0.08
0.10 0.12
0.14
0.06
0.17
0.08
0.10 0.12
0.14
0.17
*
0.06
*
0.08
0.10 0.12
0.14
0.17
0.08
0.13
0.14
0.20
0.10 0.11
0.15
0.18
0.18
0.08
0.13
0.18
0.22
0.15
0.22
0.26
0.10 0.11
0.18
0.26
0.09
0.14
0.20
0.09
0.14
0.20
*
0.09
0.10 0.11
0.15
0.18
0.22
*
0.26
*
0.1
0.15
0.22
0.11
0.18
0.26
0.07
0.11
0.16
0.07
0.11
0.16
0.07
0.11
0.16
*
0.07
0.11
0.16
0.09
0.14
0.20
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Tested with: 2” filters 12½–25 tons.
(c) Difference in pressure drop should be considered when utilizing optional 2” pleated filters.
(d)OA = Outside Air and RA = Return Air.
(e)Nominal kW ratings at 240, 480, 600 volts.
RT-PRC028AC-EN 121
Performance Data
Table 90. Gas fired heating capacities
Tons Unit Model Number Heating Input MBh (a)
12½
15
17½
YS/H*150G-L1
YS/H*150G-H1
150/100
250/175
YS/H*150G-V1 350/140
YS/H*180G-L1 250/175
YS/H*180G-H1
YS/H*180G-V1
YS/H*210G-L1
YS/H*210G-H1
350/250
350/140
250/175
350/250
120/80
200/140
280/112
200/140
280/200
280/112
200/140
280/200
20
YS/H*210G-V1
YS/H*240G-L1
YS/H*240G-H1
YS/H*240G-V1
350/140
250/175
400/300
350/140
280/112
200/140
320/240
280/112
25
YS/H*300G-L1
YS/H*300G-H1
250/175
400/300
200/140
320/240
YS/H*300G-V1 350/140 280/112
(a)For two stage heaters (input or output), second stage is total heating capacity. Second stage/first stage.
Air Temp. Rise, °F
35–65
15–45
25–55
35–65
15–45
25–55
35–65
10–40
25–55
35–65
25–55
35–65
35–65
25–55
35–65
Table 91. Auxiliary electric heat capacity
Tons Unit Model Number kW
Input
Total (a)
(b)
MBh
Output
No. of
Stages kW
Input
MBh
Output kW
Input
12½–15
TS/H*150G3,4,W
TS/H*180G3,4,W
18.00
27.00
(c)
36.00
54.00
61.47
92.15
122.94
184.41
1
2
2
2
18.00
9.00
18.00
36.00
61.47
30.72
61.47
122.94
—
18.00
18.00
18.00
17½–25
TS/H*210/211G3,4,W
TS/H*240G3,4,W
TS/H*300/301G3,4,W
36.00
54.00
122.94
184.41
2
2
18.00
36.00
61.47
122.94
18.00
18.00
72.00
245.88
2 36.00
122.94
36.00
(a)Heaters are rated at 240V, 380V, 480V, and 600V. For other than rated voltage, CAP = (voltage/rated voltage) 2 x rated cap.
(b)For all input/output categories, does not include fan power or heat.
(c) 27 kW heater can be used with TSD180F4, TSD210F4, TSD240F4, and TSD300F4 only. Cannot be used with oversized motor.
* Indicates both downflow and horizontal units.
MBh
Output
—
61.43
61.47
61.47
61.47
61.47
122.94
122 RT-PRC028AC-EN
Performance Data
Table 92. Electric heater voltage correction factors (applicable to auxiliary heat capacity)
Nominal
Voltage
240
480
600
Distribution
Voltage
208
230
240
440
460
480
540
575
600
Capacity
Multiplier
0.75
0.92
1.00
0.84
0.94
1.00
0.81
0.92
1.00
Table 93. Air temperature rise across electric heaters (°F) kW
9.00
Stages
1
12½ Tons
5000 cfm
Three Phase
TS*150G
TH*150G
—
15 Tons
6000 cfm
Three Phase
TS*180G
TH*180G
—
17½ Tons
7000 cfm
Three Phase
TS*210/211G
TH*210G
—
20 Tons
8000 cfm
Three Phase
TS*240G
TH*240G
—
25 Ton
9000 cfm
Three Phase
TS*300/301G
TH*300G
—
17.30
18.00
27.00
36.00
54.00
72.00
1
1
2
2
2
2
—
11.4
—
22.8
34.1
—
—
9.5
14.2
(a)
19.0
28.5
—
—
—
12.2
16.3
24.4
32.5
—
—
10.7
14.2
21.3
28.5
—
—
9.5
12.6
19.0
25.3
Notes:
1.
For minimum design airflow, see airflow performance table for each unit. To calculate temp rise at different airflow, use the following formula:
Temp. rise across Electric Heater = kW x 3414/1.08 x cfm.
2.
*Indicates both downflow and horizontal units.
(a)27 kW heater can be used with TSD180F4, TSD210F4, TSD240F4, and TSD300F4 only. Cannot be used with oversized motor.
Table 94. Hot gas reheat temperature rise (a), (b)
Tons
12½
SCFM
2500
3000
3500
4000
4500
5000
5500
6000
Leaving Evaporator Dry Bulb [°F] (c)
35 40 45 50 55 60 65
30.6 31.8 32.9 33.8 34.7 35.5 36.2
25.7 26.8 27.8 28.7 29.5 30.2 30.8
22.2 23.2 24.1 24.9 25.6 26.3 26.9
19.4 20.4 21.2 22.0 22.6 23.2 23.8
17.3 18.2 19.0 19.7 20.3 20.9 21.5
15.6 16.4 17.2 17.8 18.4 19.0 19.5
14.2 15.0 15.7 16.3 16.9 17.4 17.9
13.0 13.8 14.5 15.1 15.6 16.1 16.5
RT-PRC028AC-EN 123
Performance Data
Table 94. Hot gas reheat temperature rise (a), (b)
Tons SCFM
3000
Leaving Evaporator Dry Bulb [°F] (c)
35 40 45 50 55 60 65
30.4 31.5 32.5 33.3 34.1 34.9 35.5
6400
7200
8000
8800
9600
5000
7000
7700
8400
4000
4800
5600
7200
3500
4200
4900
5600
6300
3600
4200
4800
5400
6000
6600
15
17½
20
25
5800
6600
7400
8000
8800
9600
10400
25.4 26.4 27.3 28.1 28.8 29.4 30.0
21.9 22.8 23.6 24.4 25.1 25.7 26.3
19.1 20.0 20.8 21.5 22.2 22.7 23.3
17.0 17.8 18.6 19.2 19.8 20.4 20.9
15.3 16.1 16.8 17.4 18.0 18.5 19.0
13.9 14.7 15.3 15.9 16.4 16.9 17.4
12.7 13.5 14.1 14.7 15.2 15.6 16.1
34.5 37.9 41.5 45.2 48.5 50.6 50.6
28.0 30.9 33.9 36.8 39.6 42.0 43.8
23.5 26.0 28.6 31.4 34.0 36.2 37.9
20.3 22.4 24.7 27.2 29.7 31.9 33.5
17.9 19.7 21.7 23.8 26.1 28.3 29.9
16.0 17.5 19.3 21.3 23.4 25.3 26.9
14.4 15.8 17.4 19.2 21.1 23.0 24.5
13.2 14.4 15.8 17.4 19.3 21.0 22.5
30.5 31.8 33.0 34.0 35.0 35.8 36.6
25.5 26.7 27.8 28.8 29.6 30.4 31.2
21.8 23.0 24.0 24.9 25.7 26.4 27.1
19.1 20.2 21.1 22.0 22.8 23.4 24.1
17.0 18.0 18.9 19.6 20.3 21.0 21.6
15.3 16.2 17.1 17.8 18.5 19.1 19.6
13.9 14.8 15.6 16.3 16.9 17.5 18.0
12.7 13.6 14.3 15.0 15.6 16.1 16.6
25.5
27.3
29.03
30.4
31.7
32.5
32.4
21.9
19.2
17.1
15.8
14.3
13.1
12.1
23.5
20.7
18.4
17
15.5
14.2
13.1
25.1
22.1
19.7
18.3
16.6
15.2
14
11200
12000
11.2
10.4
12.1
11.2
(a) 70°F OD Ambient Temperature.
(b) For units with the Dehumidification (Hot Gas Reheat) option.
(c) Temperature does not account for indoor fan heat.
13
12.2
26.5
23.4
20.9
19.3
17.6
16.2
14.9
13.9
13
27.5
24.3
21.7
20.3
18.7
17.1
15.8
14.7
13.7
28.4
25.2
22.7
21.1
19.2
17.7
16.4
15.1
14.2
28.8
25.7
23.2
21.6
19.8
18.3
16.9
15.8
14.8
124 RT-PRC028AC-EN
Controls
Economizer Controls
The standard equipment offering is a fixed dry bulb changeover control. In addition, there are two optional controls, Enthalpy and Differential Enthalpy Control.
Enthalpy Control
Replaces the dry bulb control with a wet bulb changeover controller which has a fully adjustable setpoint. Enthalpy control offers a higher level of comfort control, along with energy savings potential, than the standard dry bulb control. This is due to the additional wet bulb sensing capability.
Differential Enthalpy Control
Differential Enthalpy replaces the standard dry bulb control with two enthalpy sensors that compare total heat content of the indoor air and outdoor air to determine the most efficient air source. This control option offers the highest level of comfort control, plus energy efficiency, available.
Remote Potentiometer
Minimum position setting of economizer can be remotely adjusted with this accessory.
Zone Sensors
Zone Sensors are the building occupant’s comfort control devices. They replace the conventional electro-mechanical thermostats.
Note: Zone sensor required for units configured for Single Zone VAV indoor fan system control to enable Single Zone VAV functionality.
Differential Pressure Switches
This factory or field-installed option allows individual fan failure and dirty filter indication. The fan failure switch will disable all unit functions and “flash” the Service LED on the zone sensor. The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation.
Manual Changeover Manual/Automatic
Changeover
Manual/Automatic
Changeover
RT-PRC028AC-EN
Heat, Cool or Off System
Switch. Fan Auto or Off Switch.
One temperature setpoint lever.
Auto, Heat, Cool or Off
System Switch. Fan Auto or
Off Switch. Two temperature setpoint levers.
Auto, Heat, Cool or Off
System Switch. Fan Auto or
Off Switch. Two temperature setpoint levers. Status
Indication LED lights, System
On, Heat, Cool, or Service.
125
Controls
RA Remote Sensor & Room Remote Sensor
The RA Remote Sensor is a Return Air Remote Sensor which can be mounted in the return air duct to report return air temperature. The Room Remote Sensor is a Space Remote Sensor which can be mounted on the wall to report/control from a remote location in the space.
Wireless Zone Sensor
LCD display that provides heat, cool, auto, or off. Includes two temperature setpoints and a lockable setting with °F or
°C indicators.
Manual/Automatic
Changeover
Remote Sensor Integrated Comfort™
System
Auto, Heat, Cool or Off System
Switch. Fan Auto or Off Switch.
Two temperature setpoint levers.
Sensor(s) available for all zone sensors to provide remote sensing capabilities.
Sensor(s) available with optional temperature adjustment and override buttons to provide central control through a Trane
Integrated Comfort™ system.
126 RT-PRC028AC-EN
Programmable Night
Setback
CO
2
Sensor
Controls
Humidity Sensor
RT-PRC028AC-EN
Auto or manual changeover with seven-day programming.
Keyboard selection of Heat,
Cool, Fan, Auto, or On. All programmable sensors have
System On, Heat, Cool, Service
LED/indicators as standard.
Night Setback Sensors have one (1) Occupied, one (1) Unoccupied, and one (1) Override program per day.
The CO
2
sensor shall have the ability to monitor the concentration (parts per million, ppm) of CO
2
(Carbon
Dioxide) in the air. As the CO
2 concentration changes, the outside air damper modulates to meet the current ventilation needs of the zone.
Field installed, wall-mounted or duct-mounted humidity sensor is used to control activation of the hot gas reheat dehumidification option. The humidity sensor can be set for humidity levels between 40 percent and
60 percent relative humidity by adjusting the ReliaTel
Options Module.
Digital Display
Programmable
Thermostat with Built-
In Relative Humidity
Sensing (3H/2C)
Tue
Digital Display
Programmable
Thermostat (3H/2C)
Touchscreen
Programmable
Thermostat (2H/2C)
MON TUE WED
FAN
ON
AUTO
CIRC
SYSTEM
EM HEAT
HEAT
OFF
COOL
AUTO
RESET
CANCEL
PERIOD
PM
THU FRI SAT SUN
HEAT
DEHUMIDIFIER
COOL
DONE EDIT WAKE LEAVE RETURN SLEEP CANCEL
Three Heat/Two Cool digital display thermostat with builtin humidity control and display. This thermostat combines both humidity and dry bulb into one. Fully programmable with night setback.
Three Heat/Two Cool auto changeover digital display thermostat. 7-day programmable stat with night setback shall be available.
Two Heat/Two Cool programmable thermostat with touch screen digital display. Menu-driven programming. Effortless setup. Program each day separately with no need to copy multiple days. All programming can be done on one screen. Easy to read and use. Large, clear backlit digital display.
127
Controls
Digital Display Thermostat (3H/2C)
Three Heat, Two Cool auto changeover digital display thermostat.
Communication Interfaces
Air-Fi™ Wireless Communication - Factory Installed
The factory installed Air-Fi Wireless communication allows customers to benefit from reduced installed/labor cost. This factory installed solution comes pre-wired and tested.
BACnet ® Communications Interface - Factory or Field Installed
The BACnet communications interface allows the unit to communicate directly with a generic open protocol BACnet MS/TP Network Building Automation System Controls.
LonTalk
®
Communications Interface - Factory or Field Installed
The LonTalk communications interface allows the unit to communicate as a Tracer™ LCI-V device or directly with generic LonTalk Network Building Automation System Controls.
Trane Communication Interface (TCI) - Factory or Field Installed
This factory or field-installed micro-processor interface allows the unit to communicate with
Trane’s Integrated Comfort™ system.
128 RT-PRC028AC-EN
Electrical Data
Table 95. Unit wiring with cooling (no electric heat) or gas heat—standard refrigeration system
Tons
Unit Model
Number
Unit Operating
Voltage Range
Standard Indoor Fan Motor
Minimum Circuit
Ampacity (a)
Maximum Fuse Size or Maximum Circuit
Breaker
12½
15
T/YS*150G3
T/YS*150G4
T/YS*150GW
T/YS*150GK
T/YS*180G3
T/YS*180G4
T/YS*180GW
T/YS*180GK
T/YS*210/211G3
187–253
414–506
517–633
342–418
187–253
414–506
517–633
342–418
187–253
36
69
34
61
29
22
31
45
77
45
90
45
80
40
30
40
60
100
17½
20
T/YS*210/211G4
T/YS*210/211GW
T/YS*210GK
T/YS*240G3
T/YS*240G4
T/YS*240GW
T/YS*240GK
T/YS*300/301G3
414–506
517–633
342–418
187–253
414–506
517–633
342–418
187–253
37
34
52
105
50
43
60
112
50
45
70
125
70
60
80
150
25
T/YS*300/301G4
T/YS*300/301GW
T/YS*300GK
414–506
517–633
342–418
53
45
69
70
60
90
(a)For Standard and Oversized Indoor Fan Motor, values do not include power exhaust accessory.
* Indicates both downflow and horizontal units.
Oversized Indoor Fan Motor
Minimum Circuit
Ampacity
Maximum Fuse Size or Maximum Circuit
Breaker
41
37
56
112
54
46
64
—
—
—
—
39
75
37
67
32
24
32
47
85
50
50
70
150
70
60
80
—
—
—
—
90
40
30
50
100
50
45
60
110
RT-PRC028AC-EN 129
Electrical Data
Standard Efficiency
Table 96. Unit wiring with electric heat (single point connection)—standard refrigeration system (downflow and horizontal)
Tons
12½
15
17½
20
25
12½
15
17½
20
25
Unit Model
Number
TS*150G3
TS*180G3
TS*210/
211G3
TS*240G3
TS*300/
301G3
TS*150G4
TS*180G4
TS*210/
211G4
TS*240G4
TS*300/
301G4
Heater Model
Number (a)
AYDHTRK318/AYHHTRN318
AYDHTRK336/AYHHTRP336
AYDHTRK354/AYHHTRP354
AYDHTRK318/AYHHTRN318
AYDHTRK336/AYHHTRM336
AYDHTRK354/AYHHTRM354
AYDHTRL336/AYHHTRN336
AYDHTRL354/AYHHTRN354
AYDHTRK372/AYHHTRN372
AYDHTRL336/AYHHTRN336
AYDHTRL354/AYHHTRN354
AYDHTRK372/AYHHTRN372
AYDHTRL336/AYHHTRN336
AYDHTRL354/AYHHTRN354
AYDHTRK372/AYHHTRN372
AYDHTRL418 (AYDHTRK418)
AYHHTRN418
AYDHTRK436/AYHHTRP436
AYDHTRK454/AYHHTRP454
AYDHTRL418 (AYDHTRK418)
AYHHTRM418
AYDHTRK436/AYHHTRM436
AYDHTRK454/AYHHTRM454
AYDHTRL436/AYHHTRN436
AYDHTRL454/AYHHTRN454
AYDHTRK472/AYHHTRN472
AYDHTRL436/AYHHTRN436
AYDHTRL454/AYHHTRN454
AYDHTRK472/AYHHTRN472
AYDHTRL436/AYHHTRN436
AYDHTRL454/AYHHTRN454
AYDHTRK472/AYHHTRN472
Standard Indoor Motor Oversized Indoor Motor
Heater kW
Rating
Control
Stages
208/230 Volts Three Phase
MCA
Max Fuse Size or Max Circuit
Breaker MCA
Max Fuse Size or Max Circuit
Breaker (b)
13.5/18.0
27.0/36.0
40.5/54.0
13.5/18.0
27.0/36.0
40.5/54.0
27.0/36.0
40.5/54.0
54.0/72.0
27.0/36.0
40.5/54.0
54.0/72.0
27.0/36.0
40.5/54.0
2
2
2
2
2
2
2
2
54.0/72.0
2
460 Volts Three Phase
1
2
2
1
2
2
62/69
109/123
155/145
69/69
109/123
155/145
116/131
163/152
172/196
116/131
163/152
172/196
126/140
172/162
182/205
80/80
110/125
175/175
90/90
110/125
175/175
125/150
175/175
200/225
125/150
175/175
200/225
150/150
175/175
200/225
69/77
116/131
163/152
75/77
116/131
163/152
126/140
172/162
182/205
126/140
172/162
182/205
—
—
—
90/90
125/150
175/175
100/100
125/150
175/175
150/150
175/175
200/225
150/150
175/175
200/225
—
—
—
18.0
36.0
54.0
18.0
36.0
54.0
72.0
36.0
54.0
72.0
36.0
54.0
36.0
54.0
72.0
1
2
2
1
2
2
2
2
2
2
2
2
2
2
2
28
62
72
36
65
76
98
69
80
102
62
72
65
76
98
30
70
90
50
70
90
110
70
90
110
70
90
70
90
110
38
65
76
39
69
80
102
—
—
—
65
76
69
80
102
40
70
90
50
—
—
—
70
90
110
70
90
70
90
110
130 RT-PRC028AC-EN
Electrical Data
Standard Efficiency
Table 96. Unit wiring with electric heat (single point connection)—standard refrigeration system (downflow and horizontal) (continued)
Tons
12½
15
17½
20
25
12½
15
Unit Model
Number
TS*150GW
TS*180GW
TS*210/
211GW
TS*240GW
TS*300/
301GW
TS*150GK
TS*180GK
Heater Model
Number (a)
Heater kW
Rating
Control
Stages
575 Volts Three Phase
AYHHTRNW18
/
18.0
1
AYDHTRMW36/AYHHTRPW36
AYDHTRKW54/AYHHTRPW54
AYHHTRMW18 (AYHHTRQW18)
AYHHTRMW36 (AYHHTRSW36)
AYDHTRKW54/AYHHTRMW54
AYHHTRMW36 (AYHHTRNW36)
AYDHTRLW54/AYHHTRNW54
AYDHTRKW72/AYHHTRNW72
AYHHTRMW36 (AYHHTRNW36)
AYDHTRLW54/AYHHTRNW54
AYDHTRKW72/AYHHTRNW72
AYHHTRMW36 (AYHHTRNW36)
AYDHTRLW54/AYHHTRNW54
AYDHTRKW72/AYHHTRNW72
36.0
54.0
18.0
36.0
54.0
36.0
54.0
72.0
36.0
54.0
72.0
36.0
2
2
2
2
1
2
2
2
2
2
2
2
54.0
72.0
2
2
380 Volts Three Phase
AYHHTRN418
AYDHTRK436/AYHHTRP436
AYDHTRK454/AYHHTRP454
AYHHTRM418
AYDTRK436/AYHHTRM436
18.0
36.0
54.0
18.0
36.0
2
2
2
2
2
Standard Indoor Motor Oversized Indoor Motor
MCA
Max Fuse Size or Max Circuit
Breaker MCA
Max Fuse Size or Max Circuit
Breaker (b)
28
50
58
30
50
58
52
61
78
52
61
78
56
65
82
36
52
60
44
30
50
70
45
50
70
60
70
90
60
70
90
60
70
90
45
60
70
60
31
52
61
32
52
61
56
65
82
56
65
82
—
—
—
—
—
—
—
35
60
70
45
60
70
60
70
90
60
70
90
—
—
—
—
—
—
—
17½ TS*210GK
AYDTRK454/AYHHTRM454
AYDHTRL436/AYHHTRN436
AYDHTRL454/AYHHTRN454
AYDHTRL436/AYHHTRN436
54.0
36.0
54.0
36.0
2
2
2
2
20 TS*240GK AYDHTRL454/AYHHTRN454
AYDHTRK472/AYHHTRN472
AYDHTRL436/AYHHTRN436
AYDHTRL454/AYHHTRN454
54.0
72.0
36.0
54.0
2
2
2
2
25 TS*300GK
AYDHTRK472/AYHHTRN472 72.0
2
(a) Heater model numbers in parenthesis apply to units with an optional high SCCR rating.
(b)Values do not include power exhaust accessory.
* Indicates both downflow and horizontal units.
64
60
64
82
52
60
56
69
70
87
70
80
80
90
60
70
70
90
90
90
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
RT-PRC028AC-EN 131
Electrical Data
Standard Efficiency
Table 97. Electrical characteristics—compressor motor and condenser motor—60 cycle—standard efficiency
Tons
12½
15
17½
T/YS*210/211G3
T/YS*210/211G4
T/YS*210/211GW
T/YS*210GK
20
T/YS*240G3
T/YS*240G4
T/YS*240GW
T/YS*240GK
25
Unit
Model No.
T/YS*150G3
T/YS*150G4
T/YS*150GW
T/YS*150GK
T/YS*180G3
T/YS*180G4
T/YS*180GW
T/YS*180GK
T/YS*300/301G3
T/YS*300/301G4
T/YS*300/301GW
T/YS*300GK
No.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Volts
208–230
460
575
380
208–230
460
575
380
208–230
460
575
380
208–230
460
575
380
208–230
460
575
380
Phase
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Compressor Motors
hp (b)
6.9/3.5
6.9/3.5
6.9/3.5
6.9/3.5
9.2/4.5
9.2/4.5
9.2/4.5
9.2/4.5
9.2/4.5
9.2/4.5
9.2/4.5
9.2/4.5
12.9/6.3
12.9/6.3
12.9/6.3
12.9/6.3
13.4/6.9
13.4/6.9
13.4/6.9
13.4/6.9
rpm
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
Amps
RLA
25/13.7
12.2/6.2
9.0/4.8
13.9/8.1
29.4/15.6
14.7/7.7
14.7/5.8
103/38.9
16.6/10.1
160/65.6
29.4/15.6
14.7/7.7
14.7/5.8
103/38
16.6/10.1
160/65.6
44.2/25
21.1/12.8
18.6/9.6
23/12.5
44.2/25
21.1/12.2
(a)
LRA
164/83.1
100/41
78/33
94.3/56
267/110
142/52
267/110
142/52
315/164
158/100
136/78
177/94.3
315/164
158/100
18.6/9 136/78
23.7/13.9
177/94.3
No. Phase
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Condenser Fan Motors
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
hp
1.0
1.0
1.0
0.5
1.0
1.0
1.0
0.5
1.0
1.0
1.0
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Amps
FLA
3.8
1.8
1.84
2.1
3.8
1.8
1.84
2.1
2.7
1.35
0.8
1.2
2.7
1.35
0.8
1.2
3.8
1.8
1.84
2.1
(a)For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.
(b)Horsepower for each compressor.
*Indicates both downflow and horizontal units.
LRA
16.42
7.7
7.4
9.06
16.42
7.7
7.4
9.06
9.65
4.82
3.40
4.10
9.65
4.82
3.40
4.10
16.42
7.7
7.4
9.06
132 RT-PRC028AC-EN
Electrical Data
Standard Efficiency
Table 98. Electrical characteristics—evaporator fan motor—60 cycle—standard and oversized
Tons
Unit Model
Number
T/YS*150G3
No.
Standard Evaporator Fan Motor
Amps (b)
Volts
1 208–230
Phase
3 hp (a)
3.00
FLA
10.6
LRA
81.0
No.
1
Oversized Evaporator Fan Motor
Volts
208–230
Phase
3 hp
5.00
FLA
Amps
16.7
12½
15
17½
20
T/YS*150G4
T/YS*150GW
T/YS*150GK
T/YS*180G3
1
1
460
575
1 380
1 208–230
T/YS*180G4
T/YS*180GW
1
1
460
575
T/YS*180GK 1 380
T/YS*210/211G3 1 208–230
T/YS*210/2114
T/YS*210/211W
T/YS*210GK
T/YS*240G3
1
1
460
575
1 380
1 208–230
T/YS*240G4
T/YS*240GW
1
1
460
575
T/YS*240GK 1 380
T/YS*300/301G3 1 208–230
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3.00
3.00
5.00
3.00
3.00
3.00
5.00
5.00
5.00
5.00
7.50
5.00
5.00
5.00
7.50
7.50
4.8
3.9
9.2
10.6
4.8
3.9
9.2
16.7
7.6
6.1
13.3
16.7
7.6
6.1
13.3
40.5
31.0
66.5
81.0
40.5
31.0
66.5
109.8
54.9
41.6
83.5
109.8
54.9
41.6
83.5
24.2 120.4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
—
460
575
—
208–230
460
575
—
208–230
460
575
—
208–230
460
575
—
—
3
3
—
3
3
3
—
3
3
3
—
3
3
3
—
—
5.00
5.00
—
5.00
5.00
5.00
—
7.50
7.50
7.50
—
7.50
7.50
7.50
—
—
7.6
6.1
—
16.7
7.6
6.1
—
24.2
11.0
9.0
—
24.2
11.0
9.0
—
—
25
T/YS*300/301G4 1
T/YS*300/301GW 1
460
575
3
3
7.50
7.50
11.0
9.0
74.0
60
—
—
—
—
—
—
—
—
—
—
T/YS*300GK 1 380 3 7.50
13.3
83.5
— — — — —
(a)Horsepower for each compressor.
* Indicates downflow and horizontal units.
(b)For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.
LRA
109.8
74.0
60.0
—
120.4
74.0
60.0
—
—
54.9
41.6
—
109.8
54.9
41.6
—
120.4
—
—
—
Table 99. Electrical characteristics—power exhaust (cooling and gas/electric)
Amps
Tons
12½–25
Volts
208–230
460
575
Phase
1
1
1 hp
3/4
3/4
3/4 rpm
1040
1040
1040
FLA
6.6
3.2
2.1
LRA
13.5
8.4
5.2
RT-PRC028AC-EN 133
Electrical Data
High Efficiency
Table 100.Unit wiring with cooling (no electric heat) or gas heat—high efficiency
Tons
Unit Model
Number
T/YH*150G3
Unit Operating
Voltage Range
187–253
Standard Indoor Fan Motor
Minimum Circuit
Ampacity
64
(a)
Maximum Fuse Size or Maximum Circuit
Breaker
90
12½
15
17½
T/YH*150G4
T/YH*150GW
T/YH*180G3
T/YH*180G4
T/YH*180GW
T/YH*210G3
T/YH*210G4
414–506
517–633
187–253
414–506
517–633
187–253
414–506
30
23
68
33
25
83
41
40
30
90
45
35
110
50
20
T/YH*210GW
T/YH*240G3
T/YH*240G4
T/YH*240GW
T/YH*300G3
517–633
187–253
414–506
517–633
187–253
33
96
44
38
117
45
125
60
50
150
25 T/YH*300G4
T/YH*300GW
414–506
517–633
54
44
70
50
(a)For Standard and Oversized Indoor Fan Motor, values do not include power exhaust accessory.
* Indicates both downflow and horizontal units.
Oversized Indoor Fan Motor
Minimum Circuit
Ampacity
71
Maximum Fuse Size or Maximum Circuit
Breaker
90
36
103
48
41
N/A
N/A
N/A
33
25
74
36
27
91
44
45
125
60
50
N/A
N/A
N/A
45
35
100
50
35
110
60
Table 101. Unit wiring with cooling (no electric heat) or gas heat—dehumidification (hot gas reheat) option (downflow only)
Tons
12½
15
17½
20
25
Unit Model
Number
T/YHD150G3
T/YHD150G4
T/YHD150GW
T/YHD180G3
T/YHD180G4
T/YHD180GW
T/YHD210G3
T/YHD210G4
T/YHD210GW
T/YHD240G3
T/YHD240G4
T/YHD240GW
T/YHD300G3
T/YHD300G4
T/YHD300GW
Unit Operating
Voltage Range
187–253
414–506
517–633
187–253
414–506
517–633
187-253
414-506
517-633
187–253
414–506
517–633
187–253
414–506
517–633
Standard Indoor Fan Motor
Minimum Circuit
Ampacity
113
53
45
115
54
42
73
35
27
67
32
23
84
41
34
(a)
Maximum Fuse Size or Maximum Circuit
Breaker
150
70
50
150
70
50
90
45
35
80
40
30
110
50
45
(a)For Standard and Oversized Indoor Fan Motor, values do not include power exhaust accessory.
Oversized Indoor Fan Motor
Minimum Circuit
Ampacity
Maximum Fuse Size or Maximum Circuit
Breaker
120
57
48
-
-
-
79
38
29
73
35
26
92
45
37
150
70
60
-
-
-
90
40
30
100
45
35
110
50
45
134 RT-PRC028AC-EN
Electrical Data
High Efficiency
Table 102.Unit wiring with electric heat (single point connection)—high efficiency
Tons
12½
15
17½
20
25
12½
15
17½
20
25
Unit Model
Number
TH*150G3
TH*180G3
TH*210G3
TH*240G3
TH*300G3
TH*150G4
TH*180G4
THD180G4
TH*180G4
THD210G4
TH*210G4
THD240G4
TH*240G4
THD300G4
TH*300G4
Heater Model
Number (a)
AYDHTRK318/AYHHTRM318
AYDHTRK336/AYHHTRM336
AYDHTRK354/AYHHTRM354
AYDHTRK318/AYHHTRM318
AYDHTRK336/AYHHTRM336
AYDHTRK354/AYHHTRM354
AYDHTRL336/AYHHTRN336
AYDHTRL354/AYHHTRN354
AYDHTRK372/AYHHTRN372
AYDHTRL336/AYHHTRN336
AYDHTRL354/AYHHTRN354
AYDHTRK372/AYHHTRN372
AYDHTRL336/AYHHTRN336
AYDHTRL354/AYHHTRN354
AYDHTRK372/AYHHTRN372
AYDHTRL418 (AYDHTRK418)
AYHHTRM418
/
AYDHTRK436/AYHHTRM436
AYDHTRK454/AYHHTRM454
AYDHTRL418 (AYDHTRK418)
AYHHTRM418
/
AYDHTRK427
AYDHTRK436/AYHHTRM436
AYDHTRK454/AYHHTRM454
AYDHTRL427
AYDHTRL436/AYHHTRN436
AYDHTRL454/AYHHTRN454
AYDHTRK472/AYHHTRN472
AYDHTRL427
AYDHTRL436/AYHHTRN436
AYDHTRL454/AYHHTRN454
AYDHTRK472/AYHHTRN472
AYDHTRL427
AYDHTRL436/AYHHTRN436
AYDHTRL454/AYHHTRN454
AYDHTRK472/AYHHTRN472
54.0
72.0
27.0
36.0
54.0
72.0
27.0
36.0
54.0
27.0
36.0
54.0
72.0
27.0
36.0
Standard Indoor Motor Oversized Indoor Motor
Heater kW
Rating
Control
Stages
208/230 Volts Three Phase
MCA
Max Fuse Size or Max Circuit
Breaker MCA
Max Fuse Size or Max Circuit
Breaker (b)
13.5/18.0
27.0/36.0
40.5/54.0
13.5/18.0
27.0/36.0
40.5/54.0
27.0/36.0
40.5/54.0
54.0/72.0
27.0/36.0
40.5/54.0
54.0/72.0
27.0/36.0
2
2
2
40.5/54.0
54.0/72.0
2
2
460 Volts Three Phase
2
2
2
2
2
2
1
2
2
1
64/69
109/123
155/145
68/69
109/123
155/145
116/131
163/152
172/196
116/131
163/152
172/196
126/140
172/162
182/205
90/90
110/125
175/175
90/90
110/125
175/175
125/150
175/175
200/225
125/150
175/175
200/225
150/150
175/175
200/225
71/77
116/131
163/152
74/77
116/131
163/152
126/140
172/162
182/205
126/140
172/162
182/205
—
—
—
90/90
125/150
175/175
100/100
125/150
175/175
150/150
175/175
200/225
150/150
175/175
200/225
—
—
—
18.0
36.0
54.0
18.0
1
2
2
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
35
62
72
35
76
98
56
69
80
102
52
65
76
48
62
72
98
52
65
40
70
90
45
90
110
70
70
90
110
60
70
90
50
70
90
110
60
70
38
65
76
38
—
—
—
80
102
—
56
69
80
52
65
76
102
56
69
45
70
90
50
—
—
—
90
110
—
60
70
90
60
70
90
110
60
70
RT-PRC028AC-EN 135
Electrical Data
High Efficiency
Table 102.Unit wiring with electric heat (single point connection)—high efficiency
Tons
Unit Model
Number
Heater Model
Number (a)
Heater kW
Rating
Control
Stages
575 Volts Three Phase
12½ TH*150GW
AYHHTRMW18 (AYHHTRPW18)
AYDHTRMW36/AYHHTRMW36
(AYHHTRRW36)
18.0
36.0
1
2
15 TH*180GW
AYDHTRKW54/AYHHTRMW54
AYDHTRKW18 (AYDHTRMW18)
AYHHTRMW18 (AYHHTRQW18)
/
AYDHTRMW36 (AYDHTRKW36)
AYHHTRMW36 (AYHHTRSW36)
/
AYDHTRKW54/AYHHTRMW54
AYDHTRMW36 (AYDHTRLW36)
AYHHTRMW36 (AYHHTRNW36)
54.0
18.0
36.0
54.0
36.0
2
1
2
2
2
17½ TH*210GW
AYDHTRLW54/AYHHTRNW54
AYDHTRKW72/AYHHTRNW72
AYDHTRMW36 (AYDHTRLW36)
AYHHTRMW36 (AYHHTRNW36)
54.0
72.0
36.0
2
2
2
20
25
TH*240GW
TH*300GW
AYDHTRLW54/AYHHTRNW54
AYDHTRKW72/AYHHTRNW72
AYDHTRMW36 (AYDHTRLW36)
AYHHTRMW36 (AYHHTRNW36)
AYDHTRLW54/AYHHTRNW54
AYDHTRKW72/AYHHTRNW72
54.0
72.0
36.0
54.0
72.0
2
2
2
2
2
(a) Heater model numbers in parenthesis apply to units with an optional high SCCR rating.
(b)Values do not include power exhaust accessory.
* Indicates both downflow and horizontal units.
Standard Indoor Motor Oversized Indoor Motor
MCA
Max Fuse Size or Max Circuit
Breaker MCA
Max Fuse Size or Max Circuit
Breaker (b)
28
50
58
28
50
58
52
61
78
52
61
78
56
65
82
30
50
70
35
50
70
60
70
90
60
70
90
60
70
90
31
52
61
31
52
61
56
65
82
56
65
82
—
—
—
35
60
70
35
60
70
60
70
90
60
70
90
—
—
—
136 RT-PRC028AC-EN
Electrical Data
High Efficiency
Table 103.Unit wiring with electric heat (single point connection)—dehumidification (hot gas reheat) refrigeration system
(downflow only)
Tons
12½
15
17½
20
25
12½
15
17½
20
25
Unit Model
Number
THD150G3
THD180G3
THD210G3
THD240G3
THD300G3
THD150G4
THD180G4
THD210G4
THD240G4
THD300G4
Heater Model
Number (a)
AYDHTRK318
AYDHTRK336
AYDHTRK354
AYDHTRK318
AYDHTRK336
AYDHTRK354
AYDHTRL336 / AYHHTRN336
AYDHTRL354/ AYHHTRN354
AYDHTRK372/ AYHHTRN372
AYDHTRL336
AYDHTRL354
AYDHTRK372
AYDHTRL336
AYDHTRL354
AYDHTRL372
AYDHTRL418 (AYDHTRK418)
AYDHTRK436
AYDHTRK454
AYDHTRL418 (AYDHTRK418)
AYDHTRK427
AYDHTRK436
AYDHTRK454
AYDHTRL427
AYDHTRL436 / AYHHTRN436
AYDHTRL454/ AYHHTRN454
AYDHTRK472/ AYHHTRN472
AYDHTRL427
AYDHTRL436
AYDHTRL454
AYDHTRK472
AYDHTRL427
AYDHTRL436
AYDHTRL454
AYDHTRK472
Standard Indoor Motor Oversized Indoor Motor
Heater kW
Rating
Control
Stages
208/230 Volts Three Phase
MCA
Max Fuse Size or Max Circuit
Breaker MCA
Max Fuse Size or Max Circuit
Breaker (b)
72.0
27.0
36.0
54.0
72.0
36.0
54.0
72.0
27.0
36.0
54.0
13.5/18.0
27.0/36.0
40.5/54.0
13.5/18.0
27.0/36.0
40.5/54.0
27.0/36.0
40.5/54.0
54.0/72.0
27.0/36.0
40.5/54.0
54.0/72.0
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
460 Volts Three Phase
18.0
1
36.0
2
54.0
18.0
27.0
36.0
54.0
27.0
2
1
2
2
2
2
2
2
2
2
2
2
1
2
2
1
2
2
2
2
2
2
2
2
2
2
2
2
2
69
80
102
57
69
80
38
65
76
38
52
65
76
56
102
-
-
-
-
70
90
110
70
70
90
40
70
90
45
50
70
90
60
110
70
70
90
110
65
76
98
53
65
76
35
62
72
35
48
62
72
52
98
56
69
80
102
67/69
109/123
155/145
73/73
109/123
155/145
116/131
163/152
172/196
116/131
163/152
172/196
126/140
172/162
182/205
80/80
110/125
175/150
90/90
110/125
175/175
125/150
175/175
200/225
125/150
175/175
200/225
150/150
175/175
200/225
73/77
116/131
163/152
79/79
116/131
163/152
126/140
172/162
182/205
126/140
172/162
182/205
-
-
-
90/90
125/150
175/175
100/100
125/150
175/175
150/150
175/175
200/225
150/150
175/175
200/225
-
-
-
70
90
110
70
70
90
40
70
90
45
60
70
90
60
110
-
-
-
-
RT-PRC028AC-EN 137
Electrical Data
High Efficiency
Table 103.Unit wiring with electric heat (single point connection)—dehumidification (hot gas reheat) refrigeration system
(downflow only)
Tons
12½
15
17½
20
25
Unit Model
Number
THD150GW
THD180GW
THD210GW
THD240GW
THD300GW
Heater Model
Number (a)
AYDHTRMW36
AYDHTRKW54
AYDHTRKW18 (AYDHTRMW18)
AYDHTRMW36 (AYDHTRKW36)
AYDHTRKW54
AYDHTRLW36 / AYHHTRNW36
AYDHTRLW54/ AYHHTRNW54
AYDHTRKW72/ AYHHTRNW72
AYDHTRMW36 (AYDHTRLW36)
AYDHTRLW54
AYDHTRKW72
AYDHTRL336
AYDHTRL354
AYDHTRK372
Heater kW
Rating
575 Volts Three Phase
18.0
1
36.0
54.0
18.0
2
2
1
36.0
54.0
36.0
54.0
72.0
36.0
54.0
72.0
36.0
54.0
72.0
Control
Stages
2
2
2
2
2
2
2
2
2
2
2
(a) Heater model numbers in parenthesis apply to units with an optional high SCCR rating.
(b)Values do not include power exhaust accessory.
Standard Indoor Motor Oversized Indoor Motor
MCA
Max Fuse Size or Max Circuit
Breaker MCA
Max Fuse Size or Max Circuit
Breaker (b)
61
78
56
65
82
61
78
52
28
50
58
28
50
58
52
70
90
60
70
90
70
90
60
30
50
70
35
50
70
60
65
82
-
-
-
65
82
56
31
52
61
31
52
61
56
70
90
-
-
-
70
90
60
35
60
70
35
60
70
60
Table 104.Electrical characteristics—compressor motor and condenser motor—60 cycle—high efficiency
Tons Model No. No.
T/YH*150G3 2
12½
15
17½
20
25
Unit
T/YH*150G4
T/YH*150GW 2
T/YH*180G3 2
T/YH*180G4 2
T/YH*180GW
T/YH*210G3
T/YH*210G4 2
T/YH*210GW 2
T/YH*240G3
T/YH*240G4
2
2
2
2
2
T/YH*240GW 2
T/YH*300G3 3
T/YH*300G4 3
T/YH*300GW 3
Volts
208–230
460
575
208–230
460
575
208–230
460
575
208–230
460
575
208–230
460
575
Phase
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
hp
Compressor Motors
(b)
5.6/3.67
5.6/3.67
5.6/3.67
7.5/4.75
7.5/4.75
7.5/4.75
8.6/4.75
8.6/4.75
8.6/4.75
11.7/6.9
11.7/6.9
11.7/6.9
12.8/6.9
12.8/6.9
12.8/6.9
rpm
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
RLA
27.5/13.6
Amps (a)
LRA
191/100
12.8/6.1
10.38/4.2
28.3/15.9
14.7/7.0
11.3/5.1
34.1/15.6
17.3/7.7
13.32/5.8
41.0/19.6
19.75/8.2
16.7/6.6
19.6/19.6/36.63
8.2/8.2/18.26
100/41
78/33
240/110
130/52
93.7/39.5
240/110
140/52
107.6/38.9
304/136
147/66.1
122/55.3
136/136/240
66.1/66.1/140
Condenser Fan Motors
No. Phase hp
2
2
2
2
2
2
2
2
2
2
2
2
2
2
6.6/6.6/14.06 55.3/55.3/107.6 2
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
0.5
0.5
0.5
0.5
0.5
0.5
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
FLA
2.7
1.35
0.8
2.7
1.35
0.8
3.8
1.8
1.84
3.8
1.8
1.84
3.8
1.8
1.84
(a)For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.
(b)Horsepower for each compressor.
*Indicates both downflow and horizontal units.
LRA
9.65
4.82
3.40
9.65
4.82
3.40
16.42
7.7
7.4
16.42
7.7
7.4
16.42
7.7
7.4
138 RT-PRC028AC-EN
Electrical Data
High Efficiency
Table 105.Electrical characteristics—compressor motor and condenser motor—60 cycle—dehumidification (hot gas reheat) option (downflow only)
15
17½
Tons Unit Model No. No.
T/YHD150G3 2
12½ T/YHD150G4 2
T/YHD150GW
T/YHD180G3
T/YHD180G4
T/YHD180GW
T/YHD210G3
T/YHD210G4
2
2
2
2
2
2
Volts
208–230
460
575
208–230
460
575
208-230
460
Phase
3
3
3
3
3
3
3
3
Compressor Motors
hp (b)
5.6
5.6
5.6
6.9
6.9
6.9
7.5 / 6.9
7.5 / 6.9
rpm
3450
3450
3450
3450
3450
3450
3450
3450
Amps (a)
RLA
22.4/22.4
10.6/10.6
LRA
149/149
75/75
7.7/7.7
26.2/26.2
13.2/13.2
54/54
149/149
75/75
11.5/11.5
54/54
27.6 / 26.2 203 / 164
14.1 / 13.2
98 / 100
No. Phase hp
2 3 0.5
2 3 0.5
2
2
2
2
2
2
Condenser Fan Motors
Amps
3
3
3
3
3
3
0.5
0.5
0.5
0.5
1.0
1.0
FLA
2.7
1.35
0.8
2.7
1.35
0.8
3.8
1.8
20
T/YHD210GW
T/YHD240G3
T/YHD240G4
2
2
2
575
208–230
460
3
3
3
7.5 / 6.9
10
10
3450
3450
3450
11.6 / 11.5
39.1/39.1
18.6/18.6
84 / 78
267/267
142/142
2
2
2
3
3
3
1.0
1.0
1.0
1.84
3.8
1.8
25
T/YHD240GW
T/YHD300G3
T/YHD300G4
2
2
2
575
208–230
460
3
3
3
10
10
10
3450
3450
3450
15.4/15.4
36.6/36.6
17.2/17.8
103/103
240/240
140/140
2
2
2
3
3
3
1.0
1.0
1.0
1.84
3.8
1.8
T/YHD300GW 2 575 3 10 3450 12.9/12.9
108/108 2 3 1.0
1.84
(a)For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.
(b)Horsepower for each compressor.
LRA
9.65
4.82
3.40
9.65
4.82
3.40
16.42
7.7
7.4
16.42
7.7
7.4
16.42
7.7
7.4
Table 106.Electrical characteristics—evaporator fan motor—60 cycle—standard and oversized
Tons
Unit Model
Number No.
Standard Evaporator Fan Motor
Amps (b)
Volts Phase hp (a) FLA LRA No.
Oversized Evaporator Fan Motor
Amps
Volts Phase hp FLA LRA
12½
15
17½
T/YH*150G3
T/YH*150G4
T/YH*150GW
T/YH*180G3
T/YH*180G4
T/YH*180GW
T/YH*210G3
T/YH*210G4
1
1
1
1
1
1
1
1
208–230
460
575
208–230
460
575
208–230
460
3
3
3
3
3
3
3
3
5
5
3
3
3
3
3
3
10.6
4.8
3.9
10.6
4.8
3.9
16.7
7.6
81
40.5
31
81
40.5
31
109.8
54.9
1
1
1
1
1
1
1
1
208–230
460
575
208–230
460
575
208–230
460
3
3
3
3
3
3
3
3
5
5
7.5
7.5
5
5
5
5
16.7
7.6
6.1
16.7
7.6
6.1
24.2
11
20
T/YH*210GW
T/YH*240G3
T/YH*240G4
T/YH*240GW
1
1
1
1
575
208–230
460
575
3
3
3
3
5
5
5
5
6.1
16.7
7.6
6.1
41.6
109.8
54.9
41.6
1
1
1
1
575
208–230
460
575
3
3
3
3
7.5
7.5
7.5
7.5
9
24.2
11
9
25
T/YH*300G3
T/YH*300G4
1
1
208–230
460
3
3
7.5
7.5
24.2
11
120.4
74
—
—
—
—
—
—
—
—
—
—
—
—
T/YH*300GW 1 575 3 7.5
9 60 — — — — — —
(a)Horsepower for each compressor.
*Indicates both downflow and horizontal units.
(b)For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.
60
120.4
74
60
109.8
54.9
41.6
109.8
54.9
41.6
120.4
74
RT-PRC028AC-EN 139
Electrical Data
Table 107. Electrical characteristics—power exhaust (cooling and gas/electric)
Amps
Tons
12½–25
Volts
208–230
460
575
Phase
1
1
1 hp
3/4
3/4
3/4 rpm
1040
1040
1040
FLA
6.6
3.2
2.1
LRA
13.5
8.4
5.2
140 RT-PRC028AC-EN
Jobsite Connections
Table 108.Typical number of wires
Zone Sensors
A Manual Changeover..............................
Manual/Auto Changeover......................
4
5
Manual/Auto Changeover with
Status Indication LEDs.........................
10
Programmable Night Setback with Status Indication LEDs...................
Thermostats
B
7
3 Power Wires + 1 Ground Wire (three phase)
2 Power Wires + 1 Ground Wire (single phase)
ZONE SENSOR OR
THERMOSTAT
A
B
DISCONNECT
SWITCH
(BY OTHERS)
ROOFTOP
UNIT
Notes:
• For specific wiring information, see the installation instructions.
• All wiring except power wire is low voltage.
• All customer supplied wiring to be copper and must conform to applicable electrical codes and local electric codes. Wiring shown dotted is to be furnished and installed by the customer.
• Zone sensors are required for units configured for Single Zone VAV indoor fan system control in order to enable Single Zone VAV functionality.
RT-PRC028AC-EN 141
Dimensional Data
Figure 1.
Cooling with optional electric heat and gas/electric models—12½ tons standard efficiency
Figure 2.
Cooling with optional electric heat and gas/electric models—12½ tons standard efficiency horizontal unit clearance
CLEARANCE 48”
1219 MM
CLEARANCE 60”
1524 MM
SUPPLY
CLEARANCE 72”
1829 MM
RETURN
FILTER ACCESS DOOR
HORIZONTAL UNITS
ONLY
HORIZONTAL
CONDENSATE
DRAIN CONNECTION
1.0 IN. NPT
CLEARANCE 38”
965 MM
CLEARANCE 18”
457 MM
142 RT-PRC028AC-EN
Dimensional Data
Figure 3.
Cooling with optional electric heat and gas/electric models 12½ tons standard efficiency—roof curb
Figure 4.
Cooling with optional electric heat and gas/electric models 12½ tons standard efficiency—downflow duct connections—field fabricated
26 5/16
Notes:
• Duct flanges mount 7-7/16” down inside the curb on the 1-1½” curb flanges.
• Roofcurb is intended for downflow use only.
RT-PRC028AC-EN 143
Dimensional Data
Figure 5.
Cooling with optional electric heat and gas/electric models—12½ tons standard efficiency—downflow unit supply/return and unit clearance
Figure 6.
Cooling with optional electric heat and gas/electric models—15–25 tons standard efficiency & 12.5 ton high efficiency
144 RT-PRC028AC-EN
Dimensional Data
Figure 7.
Cooling with optional electric heat and gas/electric models—15–25 tons high efficiency
Figure 8.
Cooling with optional electric heat and gas/electric models—15–25 tons standard efficiency, 12½–25 tons high efficiency—unit clearance and horizontal unit supply/return
RT-PRC028AC-EN 145
Dimensional Data
Figure 9.
Cooling with optional electric heat and gas/electric models—15–25 tons standard efficiency, 12½–25 tons high efficiency—roof curb
Figure 10. Cooling with optional electric heat and gas/electric models—15–25 tons standard efficiency, 12½–25 tons high efficiency—downflow duct connections—field fabricated
9
Notes:
• Duct flanges mount 7-7/16” down inside the curb on the 1-1½” curb flanges.
• Roofcurb is intended for downflow use only.
1”
25.4 MM
CURB FLANGE
LONG SIDES
SHORT SIDES
146 RT-PRC028AC-EN
Dimensional Data
Figure 11. Cooling with optional electric heat and gas/electric models—15–25 tons standard efficiency, 12½–25 tons high efficiency—downflow unit clearance
Figure 12. Downflow & horizontal condensate locations
Table 109.Standard efficiency units (cooling and gas/electric)
Tons
12½
15–25
A B C
Downflow Only
D F
26 7/16 22 1/2 18 11/16 4 1/4
26 7/16 28 3/4 19 15/16 4 1/4
4 1/4
4 1/4
G H
62 7/16 54 11/16
76 5/16 68 11/16
Condensate
Drain Size
1 NPT
1 NPT
Condensate Drain
Location
Downflow
J
Horizontal
K
25 5/8
26 3/4
6
5 3/8
RT-PRC028AC-EN 147
Dimensional Data
Table 110. High efficiency units (cooling and gas/electric)
Tons A B C
Downflow Only
D
12½–25 26 7/16 28 3/4 19 15/16 4 1/4
F G H
4 1/4 76 5/16 68 11/16
Condensate
Drain Size
1 NPT
Condensate Drain
Location
Downflow Horizontal
J K
26 3/4 5 3/8
Table 111. Cooling unit—swing diameter & through the base electrical
Unit Model #
TSD150G
TSD180–300/301G, THD150–300G
TSH150G
TSH180–301G, THH150–300G
Note: All dimensions are in inches.
A
42 3/8
29 1/2
42 3/8
29 1/2
B
48 3/8
56
N/A
N/A
C
31
38 1/2
31
38 1/2
D
N/A
18 1/2
N/A
18 1/2
E
N/A
N/A
12
14
TOP VIEW SHOWING THROUGH THE BASE
ELECTRICAL UTILITY LOCATIONS AND ACCESS PANEL SWING CLEARANCES.
SWING RADIUS (E)
HORIZONTAL FILTER
ACCESS PANEL
SWING RADIUS (A)
ID SECTION
ACCESS PANEL
SWING RADIUS (D)
ID FAN SECTION
ACCESS PANEL
B
6 7/8"
THROUGH THE
BASE ELECTRICAL
SWING RADIUS (C)
OD SECTION
ACCESS PANEL
148 RT-PRC028AC-EN
Dimensional Data
Table 112.Gas/electric unit—swing diameter & through the base electrical; height of gas pipe
Unit Model #
YSD150G
YSD180–301G, YHD150–300G
YSH150G
YSH180–301G, YHH150–300G
Note: All dimensions are in inches.
A
42 3/8
29 1/2
42 3/8
29 1/2
B
66 3/8
77 7/8
N/A
N/A
C
48 3/8
56
N/A
N/A
D
N/A
18 1/2
N/A
18 1/2
E
N/A
N/A
12
14
F
31
38 1/2
31
38 1/2
TOP VIEW SHOWING THROUGH THE BASE
ELECTRICAL UTILITY LOCATIONS AND ACCESS PANEL SWING CLEARANCES.
SWING RADIUS (E)
HORIZONTAL FILTER
ACCESS PANEL
SWING RADIUS
(A ) ID SECTION
ACCESS PANEL
SWING RADIUS (D) ID FAN SECTION
ACCESS PANEL
Figure 13. Fresh air hood (horizontal units)
C
B
6 7/8" 7 3/8"
THROUGH
THE BASE
ELECTRICAL
THROUGH THE
BASE GAS
SEE DETAIL A
SWING RADIUS (F) OD SECTION
ACCESS PANEL
Figure 14. Fresh air hood (downflow units)
RT-PRC028AC-EN 149
Dimensional Data
Figure 15. Power exhaust—downflow economizers
Figure 16. Power exhaust—downflow economizers—side view
Figure 17. Economizer—horizontal units
C
POWER EXHAUST w i th DOWNFLOW
ECONOMIZERS only, SIDE VIEW
Figure 18. Economizer—downflow units
Note: When applying economizer to horizontal units, connected ductwork must be run full size to allow proper operation of economizer damper.
Table 113.Power exhaust dimensions
Unit Model # A B (a)
T/YS*150G
T/YH*150G, T/YS*180–301G, T/YH*180-300G
17½
19½
53¾
64¾
(a)Horizontal dimension only. Downflow economizer is width of end panel.
(b)Power exhaust is applied on downflow economizer only.
C (b)
36
39
150 RT-PRC028AC-EN
Weights
Table 114.Maximum unit & corner weights (lb) and center of gravity dimensions (in.) cooling with optional electric heat units only
Tons
Unit
Model No.
Weights (lb) (a), (b)
Shipping Net A
Corner Weights (c)
B C D
Center of Gravity (in.)
Length Width
12½
15
TS*150G
TH*150G
THD150G(Reheat Units)
TS*180G
TH*180G
THD180G (Reheat Units)
1745
2299
2390
2194
2519
2469
1373
1868
1959
1763
2076
2026
516
632
693
575
619
701
364
503
470
480
564
491
208
345
337
338
425
360
285
391
458
370
469
474
44
55
50
56
58
51
25
33
34
34
36
35
17½
20
25
TS*210/211G
TH*210G
THD210G (Reheat Units)
TS*240G
TH*240G
THD240G (Reheat Units)
TS*300/301G
TH*300G
2251
2480
2514
2334
2550
2534
2376
2551
1819
2037
2071
1902
2107
2091
1945
2108
583
622
736
615
671
751
624
672
494
542
495
498
552
497
512
556
354
399
360
357
401
361
369
400
388
474
480
433
483
482
440
481
57
56
50
55
55
50
55
55
34
36
34
35
35
34
35
35
THD300G (Reheat Units) 2576 2133 738 522 385 487 52 34
(a)Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.
to be added to unit weights.
(c) Corner weights are given for information only. 12½–25 ton models must be supported continuously by a curb or equivalent frame support.
* Indicates both downflow and horizontal units.
RT-PRC028AC-EN 151
Weights
Table 115.Maximum unit & corner weights (lb) and center of gravity dimensions (in.) gas/electric heat units only
Tons
Unit
Model No.
Weights (lb) (a) , (b)
Shipping Net A
Corner Weights (c)
B C D
Center of Gravity (in.)
Length Width
12½
15
YS*150G
YH*150G
YHD150G (Reheat Units)
YS*180G
YH*180G
YHD180G (Reheat Units)
1820
2402
2465
2269
2665
2544
1448
1971
2034
1838
2222
2101
537
680
714
595
665
722
381
515
487
497
602
508
225
352
354
355
453
377
306
423
478
390
503
494
45
54
50
56
58
51
26
33
34
34
36
35
17½
20
25
YS*210/211G
YH*210G
YHD210G (Reheat Units)
YS*240G
YH*240G
YHD240G (Reheat Units)
YS*300/301G
YH*300G
2326
2629
2589
2409
2700
2609
2451
2734
1894
2186
2146
1977
2257
2166
2020
2291
604
670
756
635
719
771
644
734
511
581
512
515
591
514
529
603
371
427
377
374
430
378
386
432
409
508
500
454
517
503
461
523
57
56
50
55
55
50
55
55
35
36
34
35
35
34
35
35
YHD300G (Reheat Units) 2651 2208 759 539 402 508 52 35
(a)Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.
to be added to unit weights.
(c) Corner weights are given for information only. 12½–25 ton models must be supported continuously by a curb or equivalent frame support.
* Indicates both downflow and horizontal units.
Table 116.Factory installed options (FIOPS)/accessory net weight (lb) (a), (b)
Accessories
Standard Economizer
Low Leak Economizer
Manual Outside Air
Damper
Motorized Outside Air
Damper
Power Exhaust (c)
Roof Curb
Oversized Motor
Hail Guard
Hinged Access Doors (d)
Powered Conv. Outlet
Through the Base
Electrical
Circuit Breaker
Disconnect
Smoke Detector Supply
Smoke Detector Return
Novar
High Static Drive Kit (e)
B Cabinet
T/YSD150G T/YSH150G
65
180
50
180
C Cabinet
T/YSD180-301G
T/YHD150G
T/YSH180-301G
T/YHH150G
80
250
65
250
C+ Cabinet
T/YHD180-300G T/YHH180-300G
80
250
65
250
32
60
95
205
5
34
27
38
23
10
10
5
5
7
2
32
60
34
27
38
—
—
5
23
10
10
5
5
7
2
32
75
95
235
5
43
27
38
23
10
10
5
5
7
2
32
75
43
27
38
—
—
5
23
10
10
5
5
7
2
32
75
95
235
5
51
27
38
23
10
10
5
5
7
2
32
75
51
27
38
—
—
5
23
10
10
5
5
7
2
152 RT-PRC028AC-EN
Weights
Table 116.Factory installed options (FIOPS)/accessory net weight (lb) (a), (b)
B Cabinet C Cabinet
T/YSD180-301G
T/YHD150G
T/YSH180-301G
T/YHH150G Accessories
LP Gas Conversion
All Zone Sensors
Electric Heaters
6–23 kW (f) (g)
27–36 kW
54 kW
(i)
Stainless Steel Heat
Exchanger
150 MBh
250 MBh
350 MBh
400 MBh (j)
T/YSD150G T/YSH150G
2
5
1
28/21
31/27
38/32
—
50
50
75
—
2
5
1
28/21
31/27
38/32
—
50
50
75
—
—
5
1
28/21 (h)
33/27
40/32
43/34
50
75
75
—
5
1
33/27
40/32
43/34
50
50
75
75
Stainless Steel Drain
Pan
VFD
3 & 5 HP
(k)
6.6
32
—
6.6
34
—
8.1
32
63
8.1
34
65
(a)Net weight should be added to unit weight when ordering factory-installed accessories.
(b)Weights for FIOP accessories not listed are < 5 lb.
(c) Downflow only.
(d)An additional 30lbs should be added to the shipping weight when hinged door option is ordered.
(e)Not available on all models (see Fan Performance tables for specific models).
(f) For 600V heaters net weights are same as 480V heaters.
(g)To estimate shipping weight add 5 lb to net weight.
(h)Applicable to T/YH*150G units only.
(i) Not applicable to T/YH*150-180G, and T/YS*180G units.
(j) Applicable to T/Y**240-300* units only.
(k)Not applicable to T/Y**300* units.
T/YHD180-300G T/YHH180-300G
—
5
1
—
5
1
—
33/27
40/32
43/34
—
50
75
75
8.1
32
63
C+ Cabinet
—
33/27
40/32
43/34
—
50
75
75
8.1
34
65
RT-PRC028AC-EN 153
Mechanical Specifications
General
The units shall be dedicated downflow or horizontal airflow. The operating range shall be between
115°F and 0°F in cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and blower rotation and control sequence, before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be UL listed and labeled, classified in accordance to UL 1995/C 22.2, 236-05 3 rd Edition.
Packaged Rooftop units cooling, heating capacities, and efficiencies are AHRI certified within scope of AHRI Standard 340/360 (I-P) and ANSIZ21.47 and 10 CFR Part 431 pertaining to Commercial Warm
Air Furnaces (gas heating units).
Casing
Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit's surface shall be tested 672 hours in a salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the unit. In order to ensure a water and air tight seal, service panels shall have lifting handles and no more than three screws to remove.
All exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2-inch,
1-pound density foil-faced, fire-resistant, permanent, odorless, glass fiber material. The base of the downflow unit shall be insulated with 1/2-inch, 1-pound density foil-faced, closed-cell material. The downflow unit’s base pan shall have no penetrations within the perimeter of the curb other than the raised 11/8-inch high supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting.
Compressors
All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps.
Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus
10 percent of nameplate voltage. Internal overloads shall be provided with the scroll compressors.
All models shall have crankcase heaters, phase monitors and low and high pressure control as standard. Dual compressors are available on all standard efficiency models and 12.5 to 20 tons high efficiency models and allow for efficient cooling utilizing 3 stages of compressor operation (high efficiency models only). 25 tons high efficiency units have 3 compressors for up to 4 stages of compressor operation.
Controls
Unit shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device. ReliaTel controls shall be provided for all 24-volt control functions. The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized control shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection.
Crankcase Heaters
These band heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or low ambient conditions. These are standard on all Voyager models.
Defrost Controls
Adaptive demand defrost shall be provided to permit defrost wherever coil icing conditions begin to significantly reduce unit capacity.
154 RT-PRC028AC-EN
RT-PRC028AC-EN
Mechanical Specifications
Discharge Line Thermostat
A bi-metal element discharge line thermostat is installed as a standard option on the discharge line of each system. This standard option provides extra protection to the compressors against high discharge temperatures in case of loss of charge, extremely high ambient and other conditions which could drive the discharge temperature higher. Discharge line thermostat is wired in series with high pressure control. When the discharge temperature rises above the protection limit, the bi-metal disc in the thermostat switches to the off position, opening the 24 Vac circuit. When the temperature on the discharge line cools down, the bi-metal disc closes the contactor circuit, providing power to the compressor. When the thermostat opens the fourth time, the ReliaTel control must be manually reset to resume operation on that stage.
Evaporator and Condenser Coils
Microchannel coils will be burst tested by the manufacturer. Internally finned, 5/16” copper tubes mechanically bonded to a configured aluminum plate fin shall be standard on high efficiency models and microchannel shall be standard on standard efficiency for evaporator coils.
Microchannel condenser coils shall be standard on all units. Coils shall be leak tested to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 225 psig and pressure tested to 450 psig. Sloped condensate drain pans are standard.
Filters
Two inch standard filters shall be factory supplied on all units. Optional MERV 8 or MERV 13 filters with filter removal tool shall be available.
Gas Heating Section
The heating section shall have a drum and tube heat exchanger design using corrosion resistant steel components. A forced combustion blower shall supply premixed fuel to a single burner ignited by a pilotless hot surface ignition system.
In order to provide reliable operation, a negative pressure gas valve shall be used on standard furnaces and a pressure switch on furnaces with modulating heat that requires blower operation to initiate gas flow. On an initial call for heat, the combustion blower shall purge the heat exchanger
45 seconds before ignition.
After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat. Units shall be suitable for use with natural gas or propane (field installed kit) and shall also comply with California requirements for low NO x
emissions. The 12½–
25 tons shall have two stage heating (Gas/Electric only).
Indoor Fan
Units above shall have belt driven, FC centrifugal fans with adjustable motor sheaves. Units with standard motors shall have an adjustable idler-arm assembly for quick-adjustment of fan belts and motor sheaves. All motors shall be thermally protected. Oversized motors shall be available for high static application. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT).
Outdoor Fans
The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position. The fan motor(s) shall be permanently lubricated and shall have builtin thermal overload protection.
Phase Monitor
The Phase Monitor is a three-phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating input voltage range of 190–600 Vac, and LED indicators for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition.
155
Mechanical Specifications
Refrigerant Circuits
Each refrigerant circuit shall have independent fixed orifice or thermostatic expansion devices, service pressure ports, and refrigerant line filter driers factory installed as standard. An area shall be provided for replacement suction line driers. Thermal Expansion Valves (TXVs) shall be standard on all high efficiency units.
Unit Top
The top cover shall be one piece, or where seams exist, double hemmed and gasket sealed to prevent water leakage.
Variable Frequency Drive
Variable Frequency Drives are factory installed and tested to provide supply fan motor speed modulation, as well as modulating gas heat. VFDs on the supply fan, as compared to inlet guide vanes or discharge dampers, are quieter, more efficient, and are eligible for utility rebates. All VFDs are designed to allow bypass if required.
Note: It has to be hard wired with relay and removed for temporary operations; see wave 121927.
Bypass control will simply provide full nominal airflow in the event of drive failure.
Modulating gas heat models with VFDs allow tighter space temperature control with less temperature swing.
Factory Installed Options
CO
2
Sensor Wiring
The unit wiring for field installed C0
2
sensors. Factory-installed C0
2
sensor wiring saves time and ensures proper unit connections for the field installed C0
2
sensor kits.
Complete Coat™ Microchannel Condenser Coil
The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number of different types of heat exchangers. The coating is selected to provide excellent resistance and durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salty air, and other corrosive environments. This coating shall be available on microchannel condenser coils.
Condensate Overflow Switch
This option shall shut the unit down in the event that a clogged condensate drain line prevents proper condensate removal from the unit.
Fault Detection & Diagnostics (FDD)
This offering meets the mandatory requirement of Title 24. This option provides detection of the following faults: Air temperature sensor failure/fault, not economizing when it should, economizing when it should not, damper not modulating, and excessive outdoor air. The FDD system shall be certified by the Energy Commission as meeting the requirements.
High Efficiency Motors
This option is available with efficiency ratings from 86.5 up to 91.0. It is not available for all models.
High Short Circuit Current Rating
Unit shall be provided with electrical subsystem that will withstand fault currents up to 65kA (208/
230, 460 VAC) or 25kA (575 VAC) compliant with UL 1995 and NEC 440.4 (B). Each compressor circuit and the indoor fan shall have dedicated overcurrent protection. Three phase motors shall be protected by Class J time delay fuses. Single phase motors shall be protected by Class CC time delay fuses. All transformers shall also be protected with Class CC time delay fuses. Contactors shall be din rail mounted.
156 RT-PRC028AC-EN
Mechanical Specifications
RT-PRC028AC-EN
Hinged Access Doors
Sheet metal hinges are available on the Filter/Evaporator Access Door and the Compressor/Control
Access Door. This option is available on all downflow models.
Horizontal Side Access with Circuit Breaker
This option is a thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. The circuit breaker will be installed in a water tight enclosure in the unit with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The circuit breaker will provide overcurrent protection, be sized per NEC and UL guidelines, and be agency recognized by UL/CSA.
Horizontal Side Access with Disconnect Switch
Three-pole, molded case, disconnect switch with provisions for through the base electrical connections are available. The disconnect switch will be installed in the unit in a water tight enclosure with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The switch will be UL/CSA agency recognized.
Note: The disconnect switch will be sized per NEC and UL guidelines but will not be used in place of unit overcurrent protection.
Human Interface
The Human Interface shall have a 5 inch color touchscreen display that conforms to FCC Part 15
Class B with an Ingress Protection Rating of IP24. The display text shall be readable by a person with 20/20 vision at a distance of 3 feet and 60° angle at lighting levels ranging from 100 lux - 25,000 lux. Also, the display shall operate at temperatures of -40° C to 70° C. Firmware and unit configurations shall be able to be restored via a USB storage device.
Multi-Speed Indoor Fan System
The multiple-speed (two-speed) indoor fan control option shall automatically switch operation of the indoor fan between high speed and low speed, based on the number of compressors operating.
The indoor fan shall operate at high speed whenever the gas or electric heater is operating.
Multiple-Zone VAV Control
Multiple-zone VAV control shall vary the speed of the indoor fan to maintain the duct static pressure at a setpoint. In cooling mode, the compressors shall be cycled (or economizer modulated) to maintain the supply air temperature (SAT) at the desired setpoint. In heating mode, the indoor fan shall operate at maximum speed whenever the heater operating.
Powered or Unpowered Convenience Outlet
This option is a GFCI, 120V/15amp, 2-plug, convenience outlet, either powered or unpowered.
When the convenience outlet is powered, a service receptacle disconnect will be available. The convenience outlet is powered from the line side of the disconnect or circuit breaker, and therefore will not be affected by the position of the disconnect or circuit breaker. This option can only be ordered when the Through the Base Electrical with either the Disconnect Switch, or Circuit Breaker, option is ordered. This option is available on all downflow models (Gas/Electric only).
Single Zone VAV
SZVAV systems combine Trane application, control and system integration knowledge to exactly match fan speed with cooling and heating loads, regardless of the operating condition.
Note: Zone sensors are required for units configured for Single Zone VAV indoor fan system control in order to enable Single Zone VAV functionality.
Stainless Steel Drain Pan
This option provides excellent corrosion and oxidation resistance. Drain pan shall be constructed of 304 stainless steel.
157
Mechanical Specifications
Stainless Steel Heat Exchanger
Gas heat exchanger shall be of drum and tube design constructed from a minimum 304 Grade stainless steel. The stainless steel heat exchanger shall have a 10-year warranty as standard (Gas/
Electric only).
Supply, Return and Plenum Air Smoke Detector
With this option installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models. See the Installation, Operation, and Maintenance (IOM) manual for the models affected and the minimum allowable airflow required. This option is available on all downflow models. Supply and/or Return Detectors may not be used with the Plenum Smoke Detector.
Through the Base Electrical with Circuit Breaker
This option is a thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. The circuit breaker will be installed in a water tight enclosure in the unit with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The circuit breaker will provide overcurrent protection, be sized per NEC and UL guidelines, and be agency recognized by UL/CSA.
Through the Base Electrical with Disconnect Switch
Three-pole, molded case, disconnect switch with provisions for through the base electrical connections are available. The disconnect switch will be installed in the unit in a water tight enclosure with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The switch will be UL/CSA agency recognized.
Note: The disconnect switch will be sized per NEC and UL guidelines but will not be used in place of unit overcurrent protection.
Through the Base Utilities Access
An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of the unit. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch.
Trane® Air-Fi™ Wireless
Trane® Air-Fi™ wireless communication shall be factory installed and pre-wired. Air-Fi must also be Zigbee® Building Automation certified and the system communicates using standard BACnet™ open protocol.
Two-Inch Pleated Filters
Two-inch MERV 8 and MERV 13 media filters with filter removal tool shall be available on all models.
VAV Operation
The VFD shall receive a 0-10 Vdc signal from the unit control based upon supply static pressure, and shall cause the drive to accelerate or decelerate as required to maintain the supply static pressure setpoint. When subjected to high ambient return conditions the VFD shall reduce its output frequency to maintain operation.
Factory or Field Installed Options
BACnet™ Communications Interface
This option shall be provided to allow the unit to communicate directly with a generic open protocol
BACnet MS/TP Network Building Automation System Controls.
158 RT-PRC028AC-EN
Mechanical Specifications
RT-PRC028AC-EN
Barometric Relief
Designed to be used on downflow units, barometric relief is an unpowered means of relieving excess building pressure.
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication. These indications will be registered with either a zone sensor with status indication lights or an Integrated Comfort™ System.
Differential Pressure Switches
These options allow for individual fan failure and dirty filter indication. The fan failure switch will disable all unit functions and “flash” the Service LED on the zone sensor. The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation.
Discharge Air Temperature Sensing Kit
This kit provides true discharge air temperature sensing in heating models. This sensor is a status indicator readable through Tracer™ or Tracker™. The kit is functional only with the ReliaTel Options
Module.
Economizer— Standard, Downflow
The assembly includes fully modulating 0–100% motor and dampers, barometric relief, minimum position setting, preset linkage, wiring harness with plug, fixed dry bulb and spring return actuator.
The barometric relief damper shall be standard with the downflow economizer and shall provide a pressure operated damper that shall be gravity closing and shall prohibit entrance of outside air during the equipment “off” cycle. Solid state enthalpy and differential enthalpy control shall be field-installed.
Economizer - Low Leak, Downflow
This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3 cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air). This option allows 100% outdoor air supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired with powered exhaust for additional building pressure relief.This option can be paired with or without Fault Detection & Diagnostics (FDD) to meet current mandatory CA Title 24 requirements.
Available on downflow units only. The economizers come with three control options, dry bulb and reference or comparative enthalpy (optional).
Electric Heaters
Electric heat modules shall be available for installation within the basic unit. Electric heater elements shall be constructed of heavy-duty nickel chromium elements internally delta connected for 240 volt, wye connected for 480 and 600 volt. Staging shall be achieved through ReliaTel. Each heater package shall have automatically reset high limit control operating through heating element contactors. All heaters shall be individually fused from the factory, where required, and shall meet all NEC and CEC requirements when properly installed. Power assemblies shall provide singlepoint connection. Electric heat modules shall be UL listed or CSA certified. If ordering the Through the Base Electrical option with an Electric Heater, the heater must be factory installed.
Indoor Fan Motor Shaft Grounding Ring
Shaft grounding rings are used on all VFD driven motors to provide a conductive discharge path away from the motor bearings to ground. Bearing Protection Ring shall be maintenance free circumferential ring of conductive micro fibers that discharges voltages to ground.
LonTalk
®
Communications Interface
The LonTalk communications interface, when installed in a Voyager unit, allows the unit to communicate as a Tracer™ LCI-V device or directly with generic LonTalk Network Building
Automation System Controls.
159
Mechanical Specifications
Oversized Motors
Oversized motors shall be available for high static applications.
Reference or Comparative Enthalpy
Reference Enthalpy is used to measure and communicate outdoor humidity. The unit receives and uses this information to provide improved comfort cooling while using the economizer.
Comparative Enthalpy measures and communicates humidity for both outdoor and return air conditions, and return air temperature. The unit receives and uses this information to maximize use of economizer cooling, and to provide maximum occupant comfort control. Reference or
Comparative Enthalpy option shall be available when a factory or field installed Downflow
Economizer is ordered. This option is available on all downflow models.
Tool-less Hail Guards
Tool-less, hail protection quality coil guards are available for condenser coil protection.
Trane Communication Interface
This factory or field-installed option shall be provided to interface ReliaTel™ controlled units with the Trane Integrated Comfort™ systems.
Field Installed Options
CO
2
Sensor
The CO
2
sensor shall have the ability to monitor the concentration (parts per million, ppm) of CO
2
(Carbon Dioxide) in the air. As the CO
2
concentration changes, the outside air damper modulates to meet the current ventilation needs of the zone.
Note: Two field installed kits are offered: CO
2
sensor and wiring or CO
2
sensor only. The CO
2 sensor only kit should be ordered with factory installed CO
2
sensor wiring. Factory installed
CO
2
sensor wiring saves set-up time and ensures proper unit connections for the CO
2 sensor.
Economizer — Standard, Horizontal
The horizontal economizer shall contain the same features as the downflow economizer with the exception of barometric relief.
Economizer - Low Leak, Downflow & Horizontal
This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3 cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air).This option allows 100% outdoor air supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired with powered exhaust for additional building pressure relief.
High Static Drive
The high static drive option shall allow the standard motor on the 12½ , 15, 17½, 20 and 25 ton units to operate with improved external static capabilities.
Humidity Sensor
Field installed, wall-mounted or duct-mounted humidity sensor is used to control activation of the hot gas reheat dehumidification option. The humidity sensor can be set for humidity levels between 40% and 60% relative humidity by adjusting the ReliaTel Options Module.
Manual Outside Air Damper
The rain hood and screen shall provide up to 25% outside air.
160 RT-PRC028AC-EN
RT-PRC028AC-EN
Mechanical Specifications
Motorized Outside Air Dampers
Manually set outdoor air dampers shall provide up to 50% outside air. Once set, outdoor air dampers shall open to set position when indoor fan starts. The damper shall close to the full closed position when indoor fan shuts down.
Powered Exhaust
The powered exhaust shall provide exhaust of return air, when using an economizer, to maintain better building pressurization.
Roof Curb—Downflow
The roof curb shall be designed to mate with the downflow unit and provide support and a water tight installation when installed properly. The roof curb design shall allow field-fabricated rectangular supply/return ductwork to be connected directly to the curb. Curb shall be shipped knocked down for field assembly and shall include wood nailer strips.
Remote Potentiometer
The minimum position setting of the economizer shall be adjusted with this accessory.
Ventilation Override Accessory
With the Ventilation Override Accessory installed, the unit can be set to transition up to three different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector or fire control panel.
Wireless Zone Sensor
LCD display that provides heat, cool, auto, or off. Includes two temperature setpoints and a lockable setting with °F or °C indicators.
Zone Sensors
This option shall be provided to interface with ReliaTel and shall be available in either manual, automatic, programmable with night setback, with system malfunction lights or remote sensor options.
Note: Zone sensors are required for units configured for Single Zone VAV indoor fan system control in order to enable Single Zone VAV functionality.
161
Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient environments. Our people and our family of brands—including Club Car®, Ingersoll Rand®, Thermo King® and
Trane®—work together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress and enduring results.
i
ngersollr
a
nd.
c
om
The AHRI Certified mark indicates Ingersoll Rand’s participation in the AHRI Certification program. For verification of individual certified products, go to www.ahridirectory.org.
Ingersoll Rand has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
We are committed to using environmentally conscious print practices.
RT-PRC028AC-EN 17 Mar 2017
Supersedes RT-PRC028AB-EN (02 Mar 2017) ©2017 Ingersoll Rand
advertisement
Related manuals
advertisement
Table of contents
- 4 Features and Benefits
- 4 Standard Features and Available Options
- 6 Standard Features
- 9 Variety of Options
- 9 Factory Installed Options
- 13 Factory or Field Installed Options
- 14 Field Installed Options
- 16 Other Benefits
- 19 Application Considerations
- 21 Selection Procedure
- 21 Cooling Capacity
- 22 Heating Capacity
- 22 Air Delivery Selection
- 23 Model Number Description
- 24 Model Number Notes
- 25 General Data
- 41 Performance Data
- 125 Controls
- 125 Economizer Controls
- 125 Zone Sensors
- 128 Communication Interfaces
- 129 Electrical Data
- 141 Jobsite Connections
- 142 Dimensional Data
- 151 Weights
- 154 Mechanical Specifications
- 156 Factory Installed Options
- 158 Factory or Field Installed Options
- 160 Field Installed Options