TYCO 7110S Figure 71 10 in. Grooved x Flanged 250 psi Painted Ductile Iron Adapter Specification

Add to My manuals
2 Pages

advertisement

TYCO 7110S Figure 71 10 in. Grooved x Flanged 250 psi Painted Ductile Iron Adapter Specification | Manualzz

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 www.tyco-fire.com

Grinnell Grooved Fire Protection Products

Figure 71

Flange Adapter

General

Description

LPCB

Vd S

See Fire Protection

Submittal Sheet for

Pressure Rating and

Listing/Approval Information

The 71 Flange Adapter allows a direct transition from flanged components into a grooved piping system. Flange bolt patterns conform to ANSI

Class 125 and 150 standards and PN16 as indicated.

WARNING

The Figure 71 Flange Adapter described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection

Association, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of this device.

The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions.

Technical

Data

Figure: 71

Sizes: 2" - 12"

Approvals: UL, FM, ULC, VdS, and LPCB;

See Fire Protection Submittal Sheet for exact

Listing / Approval information.

Housing: Ductile iron conforming to

ASTM A-536, Grade 65-45-12

Protective Coatings:

• Non-lead orange paint

• Fire brigade red (optional) non-lead paint

• Hot dipped galvanized conforming to ASTM

A-153

Gasket: (specify when ordering)

• Grade “E” EPDM, green color code.

(See Data Sheet TFP1895 for aid in selecting proper gasket)

Ordering

Procedure

When placing an order, indicate the full product name. Please specify the quantity, figure number, type of gasket, Grade “E” EPDM, and size.

Grinnell Grooved Piping Products, valves, accessories and other products are available throughout the U.S., Canada, and internationally, through a network of distribution centers. You may write directly or call 215-362-0700 for the distributor nearest you.

Care and

Maintenance

The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in accordance with the applicable standards of the National Fire Protection

Association (e.g., NFPA 25), in addition to the standards of any authority having jurisdiction.

The installing contractor or product manufacturer should be contacted relative to any questions.

Any impairment must be immediately corrected.

It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service.

Limited

Warranty

Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by Tyco

Fire Products. No warranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to misuse, improper installation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protection Association (NFPA), and/or the standards of any other Authorities Having

Jurisdiction. Materials found by Tyco Fire Products to be defective shall be either repaired or replaced, at

Tyco Fire Products’ sole option. Tyco Fire Products neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. Tyco Fire

Products shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer’s representatives.

IN NO EVENT SHALL TYCO FIRE PRODUCTS BE

LIABLE, IN CONTRACT, TORT, STRICT LIABILITY

OR UNDER ANY OTHER LEGAL THEORY, FOR

INCIDENTAL, INDIRECT, SPECIAL OR

CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT

LIMITED TO LABOR CHARGES, REGARDLESS OF

WHETHER TYCO FIRE PRODUCTS WAS INFORMED

ABOUT THE POSSIBILITY OF SUCH DAMAGES,

AND IN NO EVENT SHALL TYCO FIRE PRODUCTS’

LIABILITY EXCEED AN AMOUNT EQUAL TO THE

SALES PRICE.

THE FOREGOING WARRANTY IS MADE IN LIEU OF

ANY AND ALL OTHER WARRANTIES EXPRESS OR

IMPLIED, INCLUDING WARRANTIES OF

MERCHANTABILITY AND FITNESS FOR A

PARTICULAR PURPOSE.

Page 1 of 2 September 2004 TFP1880

Page 2 of 2 TFP1880

Figure 71 Flange Adapter

A C

F B E D

Figure 71 ANSI Calss 125 and 150

Nominal

Pipe

Size

O.D.

Inches

Inches mm

2.375

2

60.3

2.875

2 1 /

2

73.0

3.500

3

88.9

4.500

4

114.3

5.563

5

141.3

6.625

6

168.3

8.625

8

219.1

10.750

10

273.0

12.750

12

323.9

Figure 71 PN16

Max † Max †

Pressure End Load psi kPa

Lbs.

N

250

1,724

250

1,724

1,107

4,924

1,622

7,215

250

1,724

250

1,724

250

1,724

250

1,724

2,404

10,693

3,974

17,676

6,073

27,013

8,614

38,315

250

1,724

250

1,724

250

1,724

14,599

64,936

22,679

100,876

31,903

141,905

190.5

9.00

228.6

10.00

254.0

11.00

279.4

13.50

A B

Nominal Dimensions

C *D *E F

Inches Inches Inches Inches Inches Inches mm

6.38

mm

4.75

mm

0.75

mm

2.38

mm

3.41

mm

7.25

162.1

7.00

178.0

7.50

120.7

5.50

140.0

6.00

19.1

0.88

22.0

0.94

60.5

2.88

73.0

3.50

86.6

3.91

99.0

4.53

184.2

7.88

200.0

9.88

342.9

16.00

406.4

19.00

482.6

152.4

7.50

190.5

8.50

215.9

9.50

241.3

11.75

298.5

14.25

362.0

17.00

431.8

23.9

0.94

23.9

1.00

25.4

1.00

25.4

1.13

28.7

1.19

30.2

1.25

31.8

88.9

4.50

114.3

5.56

141.2

6.62

168.1

8.62

218.9

10.75

273.1

12.75

323.9

115.1

5.53

140.5

6.72

170.7

7.78

197.6

9.94

252.5

12.31

312.7

14.31

363.5

365.3

16.88

428.8

20.00

508.0

251.0

9.90

251.5

11.38

289.1

11.88

301.8

14.38

Bolts ‡

Size

Dia. x Lg.

3

3

3

5

5

5

5

/

8

" x 3"

/

8

" x 3"

/

8

" x 3"

/

8

" x 3"

/

4

" x 3

/

4

" x 3

/

4

" x 3

7

7

1

1

1

/

2

"

/

2

"

/

2

"

/

8

" x 4"

/

8

" x 4"

Qty.

4

4

4

8

8

8

8

12

12

Pipe

Nom.Size

Inches mm

2"

50

2 1 /

2

"

65

3"

80

4"

100

5"

125

6"

150

O.D.

mm

60.3

76.1

88.9

114.3

139.7

165.1

6"

150

8"

200

10

273.0

12"

300

168.3

219.1

273.0

323.9

Max † Max †

Pressure End Load

Bar

Lbs.

N

16

16

1,028

4,573

1,640

7,295

16

16

16

16

16

16

16

16

2,232

9,928

3,690

16,413

5,512

24,517

7,698

34,241

7,997

35,571

13,555

60,293

21,057

93,662

29,621

131,754

A B

Nominal Dimensions

C *D *E F

Inches Inches Inches Inches Inches Inches mm

6.38

mm

4.92

mm

0.75

mm

2.38

mm

3.41

mm

7.25

162.1

7.28

184.9

7.88

200.2

9.00

228.6

9.84

249.9

11.25

285.8

11.00

279.4

13.38

339.9

16.00

406.4

18.12

460.2

125.0

5.71

145.0

6.30

160.0

7.09

180.1

8.27

210.1

9.45

240.0

9.49

241.1

11.61

294.9

13.98

355.1

16.14

410.0

19.1

0.88

22.4

0.94

23.9

0.94

23.9

1.00

25.4

1.00

25.4

1.00

25.4

1.13

28.7

1.19

30.2

1.25

31.8

60.5

3.00

76.1

3.50

88.9

4.50

114.3

5.50

139.7

6.50

165.1

6.62

168.1

8.62

218.9

10.75

273.1

12.75

323.9

86.6

4.03

102.4

4.53

115.1

5.53

140.5

6.53

165.9

7.53

191.3

7.78

197.6

9.94

252.5

12.31

312.7

14.31

363.9

184.2

8.09

205.5

8.75

222.3

9.90

251.5

10.69

271.5

12.12

307.8

11.88

301.8

14.31

363.5

16.88

428.8

19.19

487.4

Bolts ‡

Size

Dia. x Lg.

M16 x 76

M16 x 76

M16 x 76

M16 x 76

M16 x 89

M20 x 89

M20 x 89

M20 x 89

M22 x 102

M24 x 102

Qty.

4

4

8

8

8

8

8

12

12

12

† Maximum pressure and end load are total from all loads based on standard weight steel pipe. Pressure ratings and end loads may differ on other pipe materials and/or wall thickness. Contact Tyco Fire Products for details. See Fire Protection Equipment

Submittal Sheet for Listing and Approval pressure ratings.

* Dimensions D and E represent minimum and maximum sealing surfaces.

‡ Bolts and Nuts are not supplied. Bolt lengths are standard; it is the responsibility of the purchaser to verify correct length for the intended application.

6.6

3.0

7.0

3.2

9.2

4.2

10.0

4.5

Net

Wt.

lbs.

kg

3.0

1.4

5.6

2.5

10.0

4.5

16.6

7.5

21.8

9.9

28.0

12.7

5.6

2.5

7.0

3.2

9.2

4.2

10.0

4.5

Net

Wt.

lbs.

kg

3.0

1.4

5.0

2.3

16.6

7.5

21.8

9.9

24.2

11.0

General Notes: It is the Designer’s responsibility to select products suitable for the intended service and to ensure that pressure ratings and performance data is not exceeded. Always read and understand the installation instructions (IH-1000). Never remove any piping component or correct or modify any piping deficiencies without first depressurizing and draining the system. Material and gasket selection should be verified to be compatible for the specific application.

Certified Company

TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19946 Printed U.S.A.