Tyco 51-893-1-155 TY5237 3/4 in. 155F 11.2K Pendent Sprinkler Head Specification

Add to My manuals
8 Pages

advertisement

Tyco 51-893-1-155 TY5237 3/4 in. 155F 11.2K Pendent Sprinkler Head Specification | Manualzz

Technical Services

800-381-9312

+1-401-781-8220 www.tyco-fire.com

Series EC-11 and EC-14 Sprinklers,

11.2 K and 14.0 K Upright, and Pendent

Extended Coverage Light and Ordinary Hazard

General

Description

TYCO Series EC-11 and EC-14

Extended Coverage Upright and

Pendent Sprinklers are decorative glass-bulb sprinklers designed for use in light or ordinary hazard occupancies.

They are intended for use in automatic sprinkler systems designed in accordance with standard installation rules

(for example, NFPA 13) for a maximum coverage area of 400 ft 2 (37,2 m 2 ), as compared to the maximum coverage area of 130 ft 2 (12,1 m 2 ) for standard coverage sprinklers used in ordinary hazard occupancies or 225 ft 2 (20,6 m 2 ) for standard coverage sprinklers used in light hazard occupancies.

Series EC-11 and EC-14 Sprinklers feature a UL and C-UL Listing that permits their use with unobstructed or non-combustible obstructed ceiling construction as defined and permitted by NFPA 13, as well as a specific application listing for use under concrete tees.

Series EC-11 and EC-14 Extended

Coverage Sprinklers have been fire tested to compare their performance to that of standard coverage spray sprinklers. These tests have shown that the protection provided is equal to or more effective than standard coverage spray sprinklers.

Corrosion-resistant coatings, where applicable, help extend the life of copper alloy sprinklers beyond that which occurs when exposed to corrosive atmospheres. Although corrosion-resistant coated sprinklers passed standard corrosion tests of the applicable approval agencies, this testing is not representative of all possible corrosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suitability of these corrosion-resistant coatings for any given corrosive environment.

The effects of ambient temperature, concentration of chemicals, and gas/ chemical velocity should be considered, along with the corrosive nature of the chemical to which the sprinklers will be exposed.

NOTICE

Series EC-11 and EC-14 Extended

Coverage Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the

National Fire Protection Association, in addition to the standards of any other

Authorities Having Jurisdiction. Failure to do so may impair the performance of these devices.

Owners are responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions.

IMPORTANT

Always refer to Technical Data

Sheet TFP700 for the “INSTALLER

WARNING” that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.

Model/Sprinkler

Identification

Numbers (SINs)

TY5137 - Upright, 11.2K

TY5237 - Pendent, 11.2K

TY6137 - Upright, 14.0K

TY6237 - Pendent,14.0K

TY5137 is a redesignation for C5137,

G1894, and S2510.

TY5237 is a redesignation for C5237,

G1893, and S2511.

TY6137 is a redesignation for C6137,

G1896, and S2610.

TY6237 is a redesignation for C6237,

G1895, and S2611.

Page 1 of 8 SEPTEMBER 2011 TFP220

TFP220

Page 2 of 8

Technical

Data

Approvals

TYCO Series EC-11 and EC-14 Extended

Coverage Upright, Pendent, and

Recessed Pendent Sprinklers are UL and C-UL Listed. Refer to Table A for complete sprinkler approval information including corrosion-resistant status. The approvals apply to the service conditions indicated in the Design Criteria section.

Series EC-11 and EC-14 Extended

Coverage Upright and Pendent

Sprinklers are FM Approved. Refer to

Table A for complete sprinkler approval information including corrosion-resistant status. The approvals apply to the service conditions indicated in the

Design Criteria section.

The Style 60 Two-Piece Flush

Escutcheon (Figure 4) is UL Listed and

FM Approved for use with the Series

EC-11 and EC-14 Pendent Sprinklers.

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connection

3/4 inch NPT

Discharge Coefficients

• K = 11.2 GPM/psi 1/2

(161,3 LPM/bar 1/2 )

• K = 14.0 GPM/psi 1/2

(201,6 LPM/bar 1/2 )

Temperature Ratings

135°F (57°C) to 286°F (141°C)

Finish

• Sprinkler:

Refer to Table A.

• Recessed or Flush Escutcheon:

White-Coated, Chrome-Plated, and

Brass-Plated

Physical Characteristics

Frame . . . . . . . . . . . . . . . . . . . .Bronze

Button . . . . . . . . . . . . . . . . . . . .Bronze

Sealing Assembly . . . Beryllium Nickel w/TEFLON

Bulb . . . . . . . . . . . . . Glass (3 mm dia.)

Compression Screw . . . . . . . . .Bronze

Deflector . . . . . . . . . . . . . . . . . . . Brass

Operation

The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, which then allows the sprinkler to activate and flow water.

1/2±1/8"

(12,7±3,2 mm)

FACE OF

SPRINKLER

FITTING

MOUNTING

SURFACE

CLOSURE

2-7/8" DIA.

(73,0 mm)

2-1/4" DIA.

(57,2 mm)

1/2" (12,7 mm)

1/4" (6,4 mm)

1/8"

(3,2 mm)

MOUNTING

PLATE

1-3/8" (34,9 mm)

1-1/8" (28,6 mm)

FIGURE 1

SERIES EC-11 AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY

WITH TWO-PIECE 1/2-INCH TOTAL ADJUSTMENT

STYLE 30 RECESSED ESCUTCHEON

Design

Criteria

TYCO Series EC-11 and EC-14

Extended Coverage Sprinklers must only be installed in accordance with the applicable UL and C-UL Listing or FM Approval requirements as indicated below. Only the Style 30 or

40 Recessed Escutcheon is to be used for recessed installation, as applicable.

Refer to Tables A, B, and C.

3. Series EC-11 and EC-14 Sprinklers, specifically tested and listed for non-combustible obstructed construction, are permitted to be used within trusses or bar joists having non-combustible web members greater than 1 inch (25.4 mm) when applying the 4 times obstruction criteria rule defined under “Obstructions to Sprinkler

Discharge Pattern Development”.

UL and C-UL

Listing Requirements

1. Series EC-11 and EC-14 Sprinklers may be used for the coverage areas shown in Table D, based on maintaining the minimum specified flow rate as a function of coverage area and hazard group for all sprinklers in the design area.

2. Series EC-11 and EC-14 Sprinklers are permitted to be used with unobstructed or non-combustible obstructed ceiling construction as defined and permitted by NFPA 13; for example:

• Unobstructed, combustible or noncombustible, ceiling construction with a deflector to ceiling/roof deck distance of 1 to

12 inches (25 to 300 mm).

4. To prevent cold soldering, the minimum allowable spacing between Series EC-11 and EC-14

Sprinklers, is 8 feet (2,4 m) for upright sprinklers and 9 feet

(2,7 m) for pendent sprinklers.

5. Series EC-11 and EC-14 Sprinklers are to be installed in accordance with all other requirements of

NFPA 13 for extended coverage upright and pendent sprinklers; For example, obstructions to sprinkler discharge, obstructions to sprinkler pattern development, obstructions to prevent sprinkler discharge from reaching hazard and clearance to storage.

• Obstructed, non-combustible, ceiling construction with a deflector location below structural members of 1 to 6 inches

(25 to 150 mm) and a maximum deflector to ceiling/roof deck distance of 22 inches (550 mm).

TFP220

Page 3 of 8

UL and C-UL

Specific Application Listing

Requirements for Installation under Concrete Tees

Series EC-11 and EC-14 Extended

Coverage Upright and Pendent

Sprinklers (TY5137, TY5237, TY6137 and TY6237) have a UL and C-UL

Specific Application Listing for use under concrete tees when installed as follows:

1. Stems of the concrete tee construction must spaced at less than 7.5 feet (2,3 m) on center but more than

3 feet (0,9 m) on center. The depth of the concrete tees must not exceed

30 inches (762 mm). The maximum permitted concrete tee length is 32 feet (9,8 m). However, where the concrete tee length exceeds 32 feet

(9,8 m), non-combustible baffles, equal in height to the depth of the tees, can be installed so that the space between the tees does not exceed 32 feet (9,8 m) in length.

2. The sprinkler deflectors are to be located in a horizontal plane at or above 1 inch (25,4 mm) below the bottom of the concrete tee stems.

3. When the sprinkler deflectors are located higher than a horizontal plane 1 inch (25,4 mm) beneath the bottom of the concrete tee stems, the obstruction to sprinkler discharge criteria requirements of

NFPA 13 for extended coverage upright sprinklers applies.

FM Approval Requirements

Series EC-11 and EC-14 Extended

Coverage Sprinklers are to be installed in accordance with the applicable

Factory Mutual Loss Prevention Data

Sheet for limited use in buildings of specific roof construction and for the protection of certain specific ordinary hazard (non-storage and/or non-flammable or combustible liquid) occupancies. Information provided in the

FM Loss Prevention Data Sheets relates to, but not limited to, hydraulic design, ceiling slope, and obstructions, minimum and maximum allowable spacing, and deflector-to-ceiling distance.

These criteria may differ from UL and/or

NFPA criteria. Therefore, the designer should review and become familiar with

Factory Mutual requirements before proceeding with design.

5/8±1/4"

(15,9±6,4 mm)

FACE OF

SPRINKLER

FITTING

2-7/8" DIA.

(73,0 mm)

2-1/4" DIA.

(57,2 mm)

3/4" (19,1 mm)

1/4" (6,4 mm)

1/8"

(3,2 mm)

MOUNTING

SURFACE

MOUNTING

PLATE

CLOSURE

1-3/8" (34,9 mm)

7/8" (22,2 mm)

FIGURE 2

SERIES EC-11 AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY

WITH TWO-PIECE 3/4-INCH TOTAL ADJUSTMENT

STYLE 40 RECESSED ESCUTCHEON

FACE OF

SPRINKLER FITTING:

3/8" (9,5 mm) ABOVE

TO 1/8" (3,2 mm) BELOW

MOUNTING SURFACE

ESCUTCHEON PLATE

SEATING SURFACE:

1/4" (6,4 mm) ABOVE

TO 1/2" (12,7 mm) BELOW

MOUNTING SURFACE;

3/4" (19,1 mm) TOTAL

ADJUSTMENT

2-7/8" DIA.

(73,0 mm)

2-1/4" DIA.

(57,2 mm)

INTERNAL

DIMENSIONS OF

STYLE 60 ESCUTCHEON

ACCOMMODATE

CLASS 150 MALLEABLE

IRON REDUCING

SPRINKLER FITTING

1/8"

(3,2 mm)

MOUNTING

SURFACE

CLOSURE

3/4" NPT

MOUNTING

PLATE

2-5/16" (58,7 mm)

1-13/16" (46,0 mm)

FIGURE 3

SERIES EC-11 AND EC-14 PENDENT SPRINKLER ASSEMBLY

WITH 3/4-INCH TOTAL ADJUSTMENT

STYLE 60 TWO-PIECE FLUSH ESCUTCHEON

TFP220

Page 4 of 8

1 - Frame

2 - Button

3 - Sealing Assembly

4 - Bulb

5 - Compression Screw

WRENCH

FLAT

3/4"

NPT **

ESCUTCHEON PLATE

SEATING SURFACE

* Temperature rating is

indicated on deflector

** Pipe thread connections per

ISO 7/1 can be provided on

special request.

2-7/16"

(61,9 mm)

UPRIGHT &

PENDENT

1-11/16"

(42,7 mm)

1/2" (12,7 mm)

NOMINAL MAKE-IN

UPRIGHT PENDENT

FIGURE 4

SERIES EC-11 AND EC-14 EXTENDED COVERAGE SPRINKLERS

11.2 K-FACTOR UPRIGHT (TY5137) AND PENDENT (TY5237)

14.0 K-FACTOR UPRIGHT (TY6137) AND PENDENT (TY6237)

— ASSEMBLY —

CROSS

SECTION

3

4

1

2

5

6 *

Hazard Type Temperature

Light

Table B describes

UL and C-UL

Sensitivity Rating

Table C describes

FM

Sensitivity Rating

Upright

K=11.2 (TY5137)

Pendent

K=11.2 (TY5237)

K=14.0 (TY6237)

Recessed Pendent

K=11.2 (TY5237)

K=14.0 (TY6237)

With Style 30

Escutcheon

Ordinary

Upright

K=11.2 (TY5137)

K=14.0 (TY6137)

Pendent

K=11.2 (TY5237)

K=14.0 (TY6237)

Table B describes

UL and C-UL

Sensitivity Rating

Table C describes

FM

Sensitivity Rating

Recessed Pendent

K=11.2 (TY5237)

K=14.0 (TY6237)

With Style 40

Escutcheon

Notes

(1). Listed by Underwriters Laboratories, Inc. (UL)

(2). Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL)

(3). Approved by Factory Mutual Research Corporation (FM)

(4). Approved by the City of New York under MEA 177-03-E

135°F (57°C)

155°F (68°C)

175°F (79°C)

200°F (93°C)

286°F (141°C)

135°F (57°C)

155°F (68°C)

175°F (79°C)

200°F (93°C)

286°F (141°C)

135°F (57°C)

155°F (68°C)

175°F (79°C)

200°F (93°C)

286°F (141°C)

135°F (57°C)

155°F (68°C)

175°F (79°C)

200°F (93°C)

Bulb

Liquid

Orange

Red

Yellow

Green

Blue

Orange

Red

Yellow

Green

Blue

Orange

Red

Yellow

Green

Blue

Orange

Red

Yellow

Green

Natural

Brass

Sprinkler Finish (See Note 5)

Chrome

Plated

1, 2, 4

White*

Polyester

1, 2, 3**, 4

1, 2, 3, 4

1, 2, 4

1, 2, 3, 4

1, 2, 4

Lead

Coated

1, 2, 4

N/A

1, 2, 3, 4

1, 2, 4

N/A

(5). Where Polyester Coated or Lead Coated Sprinklers are noted to be

UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers

* Frame and Deflector only. Listings and approvals apply to color

(Special Order)

** Pendent Only

N/A: Not Available

TABLE A

— LABORATORY LISTINGS AND APPROVALS —

TFP220

Page 5 of 8

Light Hazard Ordinary Hazard

Area Style

14 x 14

16 x 16

Upright or Pendent

Style 30 Recessed

Style 40 Recessed

Upright or Pendent

Style 30 Recessed

Style 40 Recessed

Upright or Pendent

Style 30 Recessed 18 x 18

20 x 20

Style 40 Recessed

Upright or Pendent

Style 30 Recessed

Style 40 Recessed

QR: Quick Response

SR: Standard Response

N/A: Not Applicable

* Does not apply to Upright K=14.0

N/A

QR*

QR*

N/A

QR*

QR*

N/A

135°F

(57°C)

-

-

-

QR*

QR*

N/A

QR*

QR*

N/A

QR*

QR*

N/A

155°F

(68°C)

-

-

-

QR*

QR*

N/A

QR*

QR*

N/A

QR*

QR*

N/A

175°F

(79°C)

-

-

-

QR*

QR*

N/A

QR*

QR*

N/A

SR*

SR*

N/A

200°F

(93°C)

-

-

-

QR*

QR*

N/A

QR*

QR*

N/A

SR*

SR*

N/A

286°F

(141°C)

-

-

-

QR*

QR*

SR

SR

SR

SR

SR

SR

SR

135°F

(57°C)

QR

QR

QR

SR

SR

SR

SR

SR

SR

SR

SR

SR

155°F

(68°C)

QR

QR

QR

SR

SR

TABLE B

SENSITIVITY RATING FOR UL AND C-UL LISTING OF SERIES EC-11 OR EC-14 SPRINKLERS

(Refer to Table D for Permitted K-Factor/Area Combinations)

SR

SR

SR

SR

SR

SR

SR

175°F

(79°C)

QR

QR

QR

SR

SR

SR

SR

SR

SR

SR

SR

SR

200°F

(93°C)

QR

QR

QR

SR

SR

N/A

SR

N/A

N/A

SR

N/A

N/A

286°F

(141°C)

SR

N/A

N/A

SR

N/A

Area Style

14 x 14

16 x 16

18 x 18

Upright or Pendent

Style 30 Recessed

Style 40 Recessed

Upright or Pendent

Style 30 Recessed

Style 40 Recessed

Upright or Pendent

Style 30 Recessed

Style 40 Recessed

20 x 20

Upright or Pendent

Style 30 Recessed

Style 40 Recessed

QR: Quick Response

SR: Standard Response

N/A: Not Applicable

* Does not apply to Upright K=14.0

N/A

QR *

QR

N/A

QR *

QR

N/A

135°F

(57°C)

-

-

-

QR *

QR *

Light Hazard

N/A

QR *

QR

N/A

QR *

QR

N/A

155°F

(68°C)

-

-

-

QR *

QR *

N/A

N/A

N/A

N/A

N/A

N/A

N/A

175°F

(79°C)

-

-

-

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

200°F

(93°C)

-

-

-

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

286°F

(141°C)

-

-

-

N/A

N/A

N/A

SR

N/A

N/A

SR

N/A

N/A

135°F

(57°C)

SR

N/A

N/A

SR

N/A

Ordinary Hazard

N/A

SR

N/A

N/A

SR

N/A

N/A

155°F

(68°C)

SR

N/A

N/A

SR

N/A

N/A

SR

N/A

N/A

SR

N/A

N/A

175°F

(79°C)

SR

N/A

N/A

SR

N/A

N/A

SR

N/A

N/A

SR

N/A

N/A

200°F

(93°C)

SR

N/A

N/A

SR

N/A

TABLE C

SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC-11 OR EC-14 SPRINKLERS

( NOTE: REFER TO FM LOSS PREVENTION DATA SHEET 2-8N FOR PERMITTED K-FACTOR/AREA COMBINATIONS )

N/A

SR

N/A

N/A

SR

N/A

N/A

286°F

(141°C)

SR

N/A

N/A

SR

N/A

TFP220

Page 6 of 8

Installation

Series EC-11 and EC-14 Sprinklers must be installed in accordance with the following instructions.

Care and

Maintenance

TYCO Series EC-11 and EC-14

Sprinklers must be maintained and serviced in accordance with the following instructions.

NOTICE

Do not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch

(1,6 mm) for the 135°F (57°C) to 3/32 inch (2,4 mm) for the 286°F (141°C) temperature ratings.

Obtain a 3/4 inch NPT sprinkler joint by applying a minimum-to-maximum torque of 10 to 20 ft.-lbs. (13,4 to 26,8

Nm). Higher levels of torque may distort the sprinkler inlet with consequent leakage or impairment of the sprinkler.

Do not attempt to compensate for insufficient adjustment in an

Escutcheon Plate by under or overtightening the Sprinkler. Re-adjust the position of the sprinkler fitting to suit.

1. Install the sprinkler with the deflector parallel to the mounting surface. Install pendent sprinklers in the pendent position; install upright sprinklers in the upright position.

2. After installing the Style 30, 40, or

60 mounting plate (or other applicable escutcheon) over the sprinkler pipe threads and with pipe-thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting.

3. For upright or pendent sprinklers wrench-tighten using only the

W-Type 3 (End A) Sprinkler Wrench.

For the pendent sprinkler installed with Style 30, 40, or 60 Escutcheon, wrench-tighten the sprinkler using only the W-Type 22 Sprinkler

Wrench.

Apply the wrench recess of the applicable sprinkler wrench (Figure

5 and 6) to the sprinkler wrench flats

(Figure 1).

NOTICE

Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action.

Exercise care to avoid damage to sprinklers before, during, and after installation. Never paint, plate, coat, or otherwise alter automatic sprinklers after they leave the factory.

Replace sprinklers that:

• were modified or over-heated.

• were damaged by dropping, striking, wrench twisting, wrench slippage, or the like.

• are leaking or exhibiting visible signs of corrosion.

• were exposed to corrosive products of combustion but have not operated, if you cannot easily remove combustion by-products with a cloth.

• have a cracked Bulb or have lost liquid from the Bulb. Refer to the

Installation section in this data sheet.

Frequent visual inspections are recommended to be initially performed for corrosion resistant coated sprinklers, after the installation has been completed, to verify the integrity of the corrosion resistant coating. Thereafter, annual inspections per NFPA 25 should suffice; however, instead of inspecting from the floor level, a random sampling of close-up visual inspections should be made, so as to better determine the exact sprinkler condition and the long term integrity of the corrosion resistant coating, as it may be affected by the corrosive conditions present.

"FITTING SIDE"

TOWARDS SPRINKLER

FITTING

WRENCH

RECESS

WRENCH

RECESS

(END "A")

FIGURE 5

W-TYPE 3 SPRINKLER

WRENCH

WRENCH

HEX

FIGURE 6

W-TYPE 22 RECESSED

SPRINKLER WRENCH

Responsibility lies with the owner for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards recognized by the

Approval agency (for example, NFPA

25), in addition to the standards of any authorities having jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions.

Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspection

Service in accordance with local requirements and/or national codes.

TFP220

Page 7 of 8

Description

TY5137

(K=11.2) Upright

TY5237

(K=11.2) Pendent

TY6137

(K=14.0) Upright

TY6237

(K=14.0) Pendent

1 ft. = 0.3048 m

1 ft.

2 =0.093 m 2

1 GPM = 3.785 LPM

14 x 4

16 x 16

18 x 18

20 x 20

14 x 4

16 x 16

18 x 18

20 x 20

14 x 4

16 x 16

18 x 18

20 x 20

14 x 4

16 x 16

18 x 18

20 x 20

Area

N/A

-

37

37

40

40

N/A

N/A

N/A

40

-

30

33

Light Hazard

0.10 GPM/ft 2

GPM PSI

-

30

33

7.2

8.7

12.8

-

7.2

8.7

12.8

N/A

N/A

N/A

-

7.0

7.0

8.2

1 psi = 0.06895 bar

1 GPM/ft 2 = 40.74 mm/min

60

-

39

49

60

60

-

39

49

60

30

39

49

Group I

Ordinary Hazard

0.15 GPM/ft 2

GPM PSI

30 7.2

39

49

12.1

19.1

28.7

7.2

12.1

19.1

18.4

-

7.8

12.3

18.4

28.7

-

7.8

12.3

TABLE D

FLOW CRITERIA FOR UL AND C-UL LISTING OF SERIES EC-11 AND EC-14 SPRINKLERS

80

-

51

65

80

80

-

51

65

80

39

51

65

Group II

Ordinary Hazard

0.20 GPM/ft 2

GPM PSI

39 12.1

51

65

20.7

33.7

51.0

12.1

20.7

33.7

32.7

-

13.3

21.6

32.7

51.0

-

13.3

21.6

TFP220

Page 8 of 8

P/N 51 – XXX – X – XXX

893 11.2K Pendent

894 11.2K Upright

895 14.0K Pendent

896 14.0K Upright

Model/SIN

TY5237

TY5137

TY6237

TY6137

7

9

1

4

Sprinkler

Finish *

Natural Brass

White Polyester

Lead Coated

Chrome-Plated

135

155

175

200

286

Temperature Rating

135°F (57°C)

155°F (68°C)

175°F (79°C)

200°F (93°C)

286°F (141°C)

Notes

* Escutcheon ordered separately

TABLE E

PART NUMBERS FOR

SERIES EC-11 AND EC-14 SPRINKLERS

Limited

Warranty

Products manufactured by Tyco

Fire Protection Products (TFPP) are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFPP . No warranty is given for products or components manufactured by companies not affiliated by ownership with TFPP or for products and components which have been subject to misuse, improper installation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire

Protection Association, and/or the standards of any other Authorities

Having Jurisdiction. Materials found by TFPP to be defective shall be either repaired or replaced, at TFPP ’s sole option. TFPP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. TFPP shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer’s representatives.

In no event shall TFPP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential damages, including but not limited to labor charges, regardless of whether

TFPP was informed about the possibility of such damages, and in no event shall TFPP ’s liability exceed an amount equal to the sales price.

The foregoing warranty is made in lieu of any and all other warranties, express or implied, including warranties of merchantability and fitness for a particular purpose.

This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materials or components, whether the claim is made in contract, tort, strict liability or any other legal theory.

This warranty will apply to the full extent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder.

Ordering

Procedure

Contact your local distributor for availability. When placing an order, indicate the full product name, description, and

P/N. Refer to the Price List for complete listing of Part Numbers.

Sprinkler Assemblies with

NPT Thread Connections

Specify (SIN), (K-Factor), (temperature rating), (Pendent or Upright) Extended

Coverage Sprinkler with (finish), P/N.

Refer to Table E

Recessed Escutcheon, Two-Piece

Specify Style (30 or 40) Two-Piece

Recessed Escutcheon with (material or finish), P/N. Refer to Technical Data

Sheet TFP770.

Flush Escutcheon, Two-Piece

Specify Style 60 Two-Piece Flush

Escutcheon with (finish), P/N (specify).

Refer to Technical Data Sheet TFP778.

Sprinkler Wrenches

Specify W-Type 3 Sprinkler Wrench,

P/N 56-895-1-001.

Specify W-Type 22 Recessed Sprinkler

Wrench, P/N 56-665-7-001.

Copyright © 2007, 2011 Tyco Fire Protection Products. All rights reserved.

TEFLON is trademark of The DuPont Corporation.