TYCO 512014155 TY2234 1/2 in. White 155 Degrees F Residential Pendent Sprinkler Head Specification

Add to My manuals
10 Pages

advertisement

TYCO 512014155 TY2234 1/2 in. White 155 Degrees F Residential Pendent Sprinkler Head Specification | Manualzz

Technical Services 800-381-9312 | +1-401-781-8220 www.tyco-fire.com

Series LFII Residential Sprinklers

4.2K Horizontal and Recessed Horizontal Sidewall

Wet Pipe and Dry Pipe Systems

General

Description

The TYCO RAPID RESPONSE Series

LFII Residential Horizontal Sidewall

Sprinklers (TY1334) are decorative, fast response, frangible bulb sprinklers designed for use in residential occupancies such as homes, apartments, dormitories, and hotels. When aesthetics and optimized flow characteristics are the major consideration, the Series LFII Residential Sidewall

Sprinklers should be the first choice.

The Series LFII Residential Sprinklers are intended for use in the following scenarios:

• wet and dry pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per

NFPA 13D

• wet and dry pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R

• wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

Historically residential sprinklers, based on their Listing, have been limited to wet pipe sprinkler systems to assure speed of water delivery for a given prescribed design area (number of design sprinklers).

IMPORTANT

Always refer to Technical Data

Sheet TFP700 for the “INSTALLER

WARNING” that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely .

The Listing for the Series LFII

Residential Horizontal and Recessed

Horizontal Sidewall Sprinklers now offers the laboratory approved option of designing dry pipe residential sprinkler systems.

Through extensive testing, it has been determined that the number of design sprinklers (hydraulic design area) for the

Series LFII Residential Sprinklers need not be increased over the number of design sprinklers (hydraulic design area) as specified for wet pipe sprinkler systems, as is accustomed for density/ area sprinkler systems designed per

NFPA 13.

Consequently, the Series LFII

Residential Sprinklers offer the features of non-water filled pipe in addition to not having to increase the number of design sprinklers (hydraulic design area) for systems designed to NFPA

13, 13D, or 13R. Non-water filled pipe will permit options for areas sensitive to freezing

The Series LFII Residential Sprinklers has a 4.2 (60,5) K-Factor that provides the required residential flow rates at reduced pressures, enabling smaller pipe sizes and water supply requirements.

The recessed version of the Series

LFII Residential Sprinklers is intended for use in areas with finished walls.

It employs a two-piece Style 20

Recessed Escutcheon. The Recessed

Escutcheon provides 1/4 inch (6,4 mm) of recessed adjustment or up to 1/2 inch (12,7 mm) of total adjustment from the flush mounting surface position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the pipe nipples to the sprinklers must be cut.

The Series LFII Residential Sprinklers has been designed with heat sensitivity and water distribution characteristics proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated.

NOTICE

The Series LFII Residential Horizontal

Sidewall Sprinklers described herein must be installed and maintained in compliance with this document and the applicable standards of the National

Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices.

Owners are responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions.

Model/Sprinkler

Identification

Number (SIN)

TY1334

Page 1 of 10 SEPTEMBER 2010 TFP410

TFP410

Page 2 of 10

Components:

*

1

2

-

-

-

-

-

-

3

4

5

6

Frame

Button Assembly

Sealing Assembly

Bulb

Compression Screw

Deflector

*

Temperature rating is indicated on top of Deflector.

TOP-OF-

DEFLECTOR

7/16"

(11,1 mm)

END-OF-

DEFLECTOR

BOSS

5

6

*

3

4

1-5/8"

(41,3 mm)

2-1/4"

(57,2 mm)

2 1

7/16" (11,1 mm)

NOMINAL

MAKE-IN

CENTERLINE

OF WATERWAY

1/2" NPT

ESCUTCHEON

PLATE SEATING

SURFACE

WRENCH

FLATS

STYLE 20

RECESSED

ESCUTCHEON

FIGURE 1

RAPID RESPONSE SERIES LFII RESIDENTIAL

HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY1334)

2-7/8" DIA.

(73,0 mm)

MOUNTING

SURFACE

TOP-OF-

DEFLECTOR

CLOSURE

TY1334

7/16±1/8"

(11,1±3,2 mm)

FACE OF

SPRINKLER

FITTING

2-7/8" DIA.

(73,0 mm)

2-1/4" DIA.

(57,2 mm)

7/16"

(11,1 mm)

MOUNTING

PLATE

END-OF-

DEFLECTOR

BOSS

1-3/8" (34,9 mm)

1-1/8" (28,6 mm)

1/8"

(3,2 mm)

1/2" (12,7 mm)

1/4" (6,4 mm)

FIGURE 2

STYLE 20 RECESSED ESCUTCHEON

FOR USE WITH THE RAPID RESPONSE SERIES LFII RESIDENTIAL

HORIZONTAL SIDEWALL SPRINKLER (TY1334)

WRENCH RECESS

(END "A" USED

FOR TY1334)

FIGURE 3

W-TYPE 6

SPRINKLER WRENCH

WRENCH

RECESS

PUSH WRENCH

IN TO ENSURE

ENGAGEMENT

WITH SPRINKLER

WRENCHING AREA

FIGURE 4

W-TYPE 7 RECESSED

SPRINKLER WRENCH

TFP410

Page 3 of 10

Technical

Data

Approvals

• UL Listed for use with wet pipe and dry pipe systems

• C-UL Listed for use only with wet pipe systems

• NYC Approved under MEA 44-03-E

For details on these approvals, refer to the Design Criteria section.

Maximum Working Pressure

175 psi (12,1 bar)

Discharge Coefficient

K=4.2 GPM/psi 1/2 (60,5 LPM/bar 1/2 )

Temperature Rating

155°F (68°C) or 175°F (79°C)

Finishes

• White Polyester

• Chrome Plated

• Natural Brass

Physical Characteristics

Frame . . . . . . . . . . . . . . . . . . . . Brass

Button . . . . . . . . . . . . . . . . . . . Bronze

Sealing Assembly . . . . . . . . Beryllium

Nickel w/Teflon*

Bulb (3 mm) . . . . . . . . . . . . . . . . Glass

Compression Screw . . . . . . . . Bronze

Deflector . . . . . . . . . . . . . . . . .Copper

Operation

The glass Bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass Bulb, allowing the sprinkler to activate and flow water.

Design

Criteria

The RAPID RESPONSE Series LFII

Residential Horizontal and Recessed

Horizontal Sidewall Sprinklers (TY1334) are UL and C-UL Listed for installation in accordance with the following criteria.

Note: When conditions exist that are outside the scope of the provided criteria, refer to the Residential

Sprinkler Design Guide TFP490 for the manufacturer’s recommendations that may be acceptable to the local authority having jurisdiction.

System Types

Per the UL Listing, wet pipe and dry pipe systems may be utilized. Per the

C-UL Listing, only wet pipe systems may be utilized.

• For dry systems corrosion-resistant or internally galvanized pipe shall be utilized with the sprinklers described in this data sheet.

• For dry systems not using CPVC, pendent sprinklers shall be installed on return bends, where the sprinklers, return bends, and branch line piping (that is, potential areas for trapped water) are in areas at or above 40°F (4°C).

Refer to technical data sheet TFP485 about the use of Residential Sprinklers in residential dry pipe systems.

NOTICE

When corrosion-resistant or internally galvanized pipe and fittings with a potable water supply is utilized, return bends need not be installed.

However, any portion of the piping that has the potential to trap water must be maintained at or above 40°F (4°C) unless provision to drain such areas is provided and maintained dry.

Water Delivery

When using the Series LFII Residential

Horizontal Sidewall Sprinklers (TY1334) in dry pipe sprinkler systems, the requirements for “Dry System Water

Delivery” per the Section 8.3.4.3 of the

2010 edition of NFPA 13D apply. For a residential hazard, in no case shall the time of water delivery exceed 15 seconds for the most remote operating sprinkler.

Hydraulic Design

(NFPA 13D and 13R)

The minimum re quired sprinkler flow rate for systems designed to NFPA 13D or NFPA 13R are given in Tables A, B,

C, D and E as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from each of the total number of

“design sprinklers” as specified in

NFPA 13D or NFPA 13R.

NOTICE

The number of “design sprinklers” specified in NFPA 13D and 13R for wet pipe systems is to be applied when designing dry pipe systems. There is no need to increase the design area, as is the case for density/area systems, in accordance with U.S. Patent 7,712,543.

Hydraulic Design

(NFPA 13)

For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following:

• The flow rates given in Tables A or B for NFPA 13D and 13R as a function of temperature rating and the maximum allowable coverage area.

• A minimum discharge of 0.1 GPM/ sq. ft. over the “design area” comprised of the four most hydraulically demanding sprinklers for actual coverage areas protected by the four sprinklers.

NOTICE

The number of “design sprinklers” specified in NFPA 13 for wet pipe systems is to be applied when designing dry pipe systems. There is no need to increase the design area, as is the case for density/area systems, in accordance with U.S. Patent 7,712,543.

Obstruction to Water Distribution

Sprinklers are to be located in accordance with the obstruction rules defined by NFPA 13 for residential sprinklers.

Operational Sensitivity

The sprinklers are to be installed with an end-of- deflector-boss to wall distance of 1-3/8 to 6 inches or in the recessed position using only the Style

20 Recessed Escutcheon as shown in

Figure 2.

In addition the top-of-deflector-toceiling distance is to be within the range

(Tables A, B, C, D or E) being hydraulically calculated.

Sprinkler Spacing

The minimum spacing between sprinklers is 8 feet (2,4 m). The maximum spacing between sprinklers cannot exceed the width of the coverage area

(Tables A and B) being hydraulically calculated; (maximum 12 feet for a 12 ft. x 12 ft. coverage area, or 16 feet for a 16 ft. x 20 ft. coverage area.

*Registered trademark of Dupont

TFP410

Page 4 of 10

ELEVATION

Maximum

Coverage Area (a)

Width x Length (b)

Ft. x Ft. (m x m)

Maximum

Spacing

Ft. (m)

12 x 12 (3,7 x 3,7)

14 x 14 (4,3 x 4,3)

16 x 16 (4,9 x 4,9)

16 x 18 (4,9 x 5,5)

16 x 20 (4,9 x 6,1)

12 (3,7)

14 (4,3)

16 (4,9)

16 (4,9)

16 (4,9)

WET PIPE SYSTEM

Minimum Flow (c) and Residual Pressure

Top-of-Deflector-to-Ceiling:

4 to 6 Inches (100 to 150 mm)

Top-of-Deflector-to-Ceiling:

6 to 12 Inches (150 to 300 mm)

155°F (68°C) 175°F (79°C) 155°F (68°C) 175°F (79°C)

12 GPM (45,4 LPM)

8.2 psi (0,57 bar)

14 GPM (53,0 LPM)

11.1 psi (0,77 bar)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

19 GPM (71,9 LPM)

20.5 psi (1,41 bar)

23 GPM (87,1 LPM)

30.0 psi (2,07 bar)

12 GPM (45,4 LPM)

8.2 psi (0,57 bar)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

19 GPM (71,9 LPM)

20.5 psi (1,41 bar)

23 GPM (87,1 LPM)

30.0 psi (2,07 bar)

13 GPM (49,2 LPM)

9.6 psi (0,66 bar)

17 GPM (64,3 LPM)

16.4 psi (1,13 bar)

18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

21 GPM (79,5 LPM)

25.0 psi (1,72 bar)

26 GPM (98,4 LPM)

38.3 psi (2,64 bar)

13 GPM (49,2 LPM)

9.6 psi (0,66 bar)

18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

21 GPM (79,5 LPM)

25.0 psi (1,72 bar)

26 GPM (98,4 LPM)

38.3 psi (2,64 bar)

Sidewall sprinklers, where installed under a ceiling with a slope greater than a 0-inch rise for a 12-inch run to a slope up to a 2-inch rise for a 12-inch run, must be located per one of the following:

• At the high positioned to discharge down the slope.

• Along the slope and positioned to discharge across the slope.

(a). For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated.

(b). The Width x Length dimension refers to Width (backwall where sprinkler is located) times Length (horizontal throw of sprinkler).

(c). The Minimum Flow Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design in the Design Criteria section for details.

TABLE A

SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY1334)

FOR HORIZONTAL CEILINGS

NFPA 13D AND 13R HYDRAULIC DESIGN CRITERIA

WET PIPE SYSTEMS

(Maximum 2-Inch Rise for 12-Inch Run)

TFP410

Page 5 of 10

ELEVATION

Maximum

Coverage Area (a)

Width x Length (b)

Ft. x Ft. (m x m)

Maximum

Spacing

Ft. (m)

12 x 12

(3,7 x 3,7)

14 x 14

(4,3 x 4,3)

16 x 16

(4,9 x 4,9)

16 x 18

(4,9 x 5,5)

16 x 20

(4,9 x 6,1)

12

(3,7)

14

(4,3)

16

(4,9)

16

(4,9)

16

(4,9)

DRY PIPE SYSTEM

Minimum Flow (c) and Residual Pressure

Top-of-Deflector-to-Ceiling:

4 to 6 Inches (100 to 150 mm)

Top-of-Deflector-to-Ceiling:

6 to 12 Inches (100 to 150 mm)

155°F (68°C) 175°F (79°C) 155°F (68°C) 175°F (79°C)

12 GPM (45,4 LPM)

8.2 psi (0,57 bar)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

19 GPM (71,9 LPM)

20.5 psi (1,41 bar)

23 GPM (87,1 LPM)

30.0 psi (2,07 bar)

12 GPM (45,4 LPM)

8.2 psi (0,57 bar)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

Not Applicable

Not Applicable

13 GPM (49,2 LPM)

9.6 psi (0,48 bar)

18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

21 GPM (79,5 LPM)

25.0 psi (1,72 bar)

Not Applicable

13 GPM (49,2 LPM)

9.6 psi (0,48 bar)

18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

21 GPM (79,5 LPM)

25.0 psi (1,72 bar)

21 GPM (79,5 LPM)

25.0 psi (1,72 bar)

Not Applicable

Sidewall sprinklers, where installed under a ceiling with a slope greater than a 0-inch rise for a 12-inch run to a slope up to a 2-inch rise for a 12-inch run, must be located per one of the following:

• At the high positioned to discharge down the slope.

• Along the slope and positioned to discharge across the slope.

(a). For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated.

(b). The Width x Length dimension refers to Width (backwall where sprinkler is located) times Length (horizontal throw of sprinkler).

(c). The Minimum Flow Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design in the Design Criteria section for details.

TABLE B

SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY1334)

FOR HORIZONTAL CEILINGS

NFPA 13D HYDRAULIC DESIGN CRITERIA

DRY PIPE SYSTEMS

(Maximum 2-Inch Rise for 12-Inch Run)

TFP410

Page 6 of 10

12"

8" MAXIMUM

ELEVATION

Maximum

Coverage Area (a)

Width x Length (b)

Ft. x Ft. (m x m)

Maximum

Spacing

( I ) Two sprinkler design with the sprinklers at the high point of the slope and positioned to discharge down the slope.

Ft. (m)

WET PIPE SYSTEM

Minimum Flow (c) and Residual Pressure

Top-of-Deflector-to-Ceiling:

4 to 6 Inches (100 to 150 mm)

Top-of-Deflector-to-Ceiling:

6 to 12 Inches (150 to 300 mm)

155°F (68°C) 175°F (79°C) 155°F (68°C) 175°F (79°C)

12 x 12 (3,7 x 3,7)

14 x 14 (4,3 x 4,3)

16 x 16 (4,9 x 4,9)

16 x 18 (4,9 x 5,5)

16 x 20 (4,9 x 6,1)

12 (3,7)

14 (4,3)

16 (4,9)

16 (4,9)

16 (4,9)

I 12 GPM (45,4 LPM)

8.2 psi (0,57 bar)

I 14 GPM (53,0 LPM)

11.1 psi (0,77 bar)

I 16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

I 19 GPM (71,9 LPM)

20.5 psi (1,41 bar)

I 24 GPM (90,8 LPM)

32.7 psi (2,25 bar)

I 12 GPM (45,4 LPM)

8.2 psi (0,57 bar)

I 14 GPM (53,0 LPM)

11.1 psi (0,77 bar)

I 16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

I 19 GPM (71,9 LPM)

20.5 psi (1,41 bar)

I 24 GPM (90,8 LPM)

32.7 psi (2,25 bar)

I 13 GPM (49,2 LPM)

9.6 psi (0,66 bar)

I 17 GPM (64,3 LPM)

16.4 psi (1,13 bar)

I 18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

I 21 GPM (79,5 LPM)

25.0 psi (1,72 bar)

I 26 GPM (98,4 LPM)

38.3 psi (2,64 bar)

I 13 GPM (49,2 LPM)

9.6 psi (0,66 bar)

I 17 GPM (64,3 LPM)

16.4 psi (1,13 bar)

I 18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

I 21 GPM (79,5 LPM)

25.0 psi (1,72 bar)

I 26 GPM (98,4 LPM)

38.3 psi (2,64 bar)

(a). For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated.

(b). The Width x Length dimension refers to Width (backwall where sprinkler is located) times Length (horizontal throw of sprinkler).

(c). The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design in the Design Criteria section for details.

TABLE C

SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY1334)

AT THE HIGH POINT OF THE SLOPE AND DISCHARGING DOWN THE SLOPE

NFPA 13D AND 13R HYDRAULIC DESIGN CRITERIA

WET PIPE SYSTEMS

(Greater Than 2-Inch Rise for 12-Inch Run Up To 8-Inch Rise for 12-Inch Run)

TFP410

Page 7 of 10

12"

4" MAXIMUM

ELEVATION

Maximum

Coverage Area (a)

Width x Length (b)

Ft. x Ft. (m x m)

Maximum

Spacing

( II ) Two sprinkler design with the sprinklers located along the slope and positioned

to discharge across the slope.

Ft. (m)

WET PIPE SYSTEM

Minimum Flow (c) and Residual Pressure

( III ) Three sprinkler design when there are more than two sprinklers in a compartment and

with the sprinklers located along the slope and positioned to discharge across the slope.

12 x 12 (3,7 x 3,7) 12 (3,7)

14 x 14 (4,3 x 4,3) 14 (4,3)

16 x 16 (4,9 x 4,9) 16 (4,9)

16 x 18 (4,9 x 5,5) 16 (4,9)

16 x 20 (4,9 x 6,1) 16 (4,9)

Top-of-Deflector-to-Ceiling:

4 to 6 Inches (100 to 150 mm)

155°F (68°C) 175°F (79°C)

Top-of-Deflector-to-Ceiling:

6 to 12 Inches (150 to 300 mm)

155°F (68°C) 175°F (79°C)

II 16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

II 16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

II 18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

II 16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

II 16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

II 16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

II 16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

II 18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

II 18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

II 18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

II 18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

II 18 GPM (68,1 LPM)

18.4 psi (1,27 bar)

II 22 GPM (83,3 LPM)

27.4 psi (1,89 bar)

II 22 GPM (83,3 LPM)

27.4 psi (1,89 bar)

II 22 GPM (83,3 LPM)

27.4 psi (1,89 bar)

II 22 GPM (83,3 LPM)

27.4 psi (1,89 bar)

III 23 GPM (87,1 LPM)

30.0 psi (2,07 bar)

III 23 GPM (87,1 LPM)

30.0 psi (2,07 bar)

III 26 GPM (98,4 LPM)

38.3 psi (2,64 bar)

III 26 GPM (98,4 LPM)

38.3 psi (2,64 bar)

(a). For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated.

(b). The Width x Length dimension refers to Width (backwall where sprinkler is located) times Length (horizontal throw of sprinkler).

(c). The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design in the Design Criteria section for details.

TABLE D

SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY1334)

LOCATED ALONG A SLOPE AND DISCHARGING ACROSS THE SLOPE

NFPA 13D AND 13R HYDRAULIC DESIGN CRITERIA

WET PIPE SYSTEMS

(Greater Than 2-Inch Rise for 12-Inch Run Up To 4-Inch Rise for 12-Inch Run)

TFP410

Page 8 of 10

12"

8" MAXIMUM

ELEVATION

Maximum

Coverage Area (a)

Width x Length (b)

Ft. x Ft. (m x m)

Maximum

Spacing

Ft. (m)

WET PIPE SYSTEM

Minimum Flow (c) and Residual Pressure

( III ) Three sprinkler design when there are more than two sprinklers in a compartment and

with the sprinklers located along the slope and positioned to discharge across the slope.

Top-of-Deflector-to-Ceiling:

4 to 6 Inches (100 to 150 mm)

155°F (68°C) 175°F (79°C)

12 x 12 (3,7 x 3,7)

14 x 14 (4,3 x 4,3)

16 x 16 (4,9 x 4,9)

16 x 18 (4,9 x 5,5)

12 (3,7)

14 (4,3)

16 (4,9)

16 (4,9)

III

III

III

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

N/A

III

III

III

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

16 GPM (60,6 LPM)

14.5 psi (1,00 bar)

N/A

16 x 20 (4,9 x 6,1) 16 (4,9)

N/A N/A

(a). For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated.

(b). The Width x Length dimension refers to Width (backwall where sprinkler is located) times Length (horizontal throw of sprinkler).

(c). The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design in the Design Criteria section for details.

TABLE E

SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY1334)

LOCATED ALONG A SLOPE AND DISCHARGING ACROSS THE SLOPE

NFPA 13D AND 13R HYDRAULIC DESIGN CRITERIA

WET PIPE SYSTEMS

(Greater Than 4-Inch Rise for 12-Inch Run Up to 8-Inch Rise for 12-Inch Run)

TFP410

Page 9 of 10

Installation

The RAPID RESPONSE Series LFII

Residential Horizontal and Recessed

Horizontal Sidewall Sprinklers (TY1334) must be installed in accordance with the following instructions.

NOTICE

Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch

(1,6 mm).

Obtain a leak-tight 1/2 inch NPT sprinkler joint by applying a minimum to maximum torque of 7 to 14 ft. lbs.

(9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler.

Do not attempt to compensate for insufficient adjustment in an

Escutcheon Plate by under- or overtightening the Sprinkler. Re-adjust the position of the sprinkler fitting to suit.

Series LFII Residential Horizontal

Sidewall Sprinklers

The Series LFII Residential Horizontal

Sidewall Sprinklers must be installed in accordance with the following instructions.

1. Install horizontal sidewall sprinklers in the horizontal position with their center-line of waterway perpendicular to the backwall and parallel to the ceiling. The word “TOP” on the Deflector is to face towards the ceiling with the front edge of the

Deflector parallel to the ceiling.

2. With pipe-thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting.

3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6

Sprinkler Wrench. (Figure 3). With reference to Figure 1, apply the

W-Type 6 Sprinkler Wrench to the wrench flats.

Series LFII Residential Recessed

Horizontal Sidewall Sprinklers

The Series LFII Residential Recessed

Horizontal Sidewall Sprinklers must be installed in accordance with the following instructions.

1. Install recessed horizontal sidewall sprinklers in the horizontal position with their center-line of waterway perpendicular to the backwall and parallel to the ceiling. The word

“TOP” on the Deflector is to face towards the ceiling.

2. After installing the Style 20

Mounting Plate over the sprinkler threads and with pipe-thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting.

3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7

Recessed Sprinkler Wrench (Figure

4). With reference to Figure 1, apply the W-Type 7 Recessed Sprinkler

Wrench to the sprinkler wrench flats.

4. After the ceiling has been installed or the finish coat has been applied, slide on the Style 20 Closure over the Series LFII Residential Sprinkler and push the Closure over the

Mounting Plate until its flange comes in contact with the ceiling.

Care and

Maintenance

The RAPID RESPONSE Series LFII

Residential Horizontal and Recessed

Horizontal Sidewall Sprinklers (TY1334) must be maintained and serviced in accordance with the following instructions.

NOTICE

Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action.

Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation.

Owners must assure that the sprinklers are not used for hanging of any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, nonoperation in the event of a fire or inadvertent operation may result.

Exercise care to avoid damage to sprinklers before, during, and after installation. Never paint, plate, coat, or otherwise alter automatic sprinklers after they leave the factory.

Replace sprinklers that:

• were modified or over-heated.

• were damaged by dropping, striking, wrench twisting, wrench slippage, or the like.

• are leaking or exhibiting visible signs of corrosion.

• were exposed to corrosive products of combustion but have not operated, if you cannot easily remove combustion by-products with a cloth.

• have a cracked bulb or have lost liquid from the bulb. Refer to the

Installation section in this data sheet.

Initial and frequent visual inspections of random samples are recommended for corrosion-resistant sprinklers to verify the integrity of the corrosion-resistant material of construction. Thereafter, annual inspections per NFPA 25 should suffice.

Inspections of corrosion-resistant sprinklers are recommended at close range, instead of from the floor level per NFPA. Inspection at close range can better determine the exact sprinkler condition and the long-term integrity of the corrosion-resistant material, which can be affected by the corrosive conditions present.

Responsibility lies with the owner for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire

Protection Association (that is, NFPA

25), in addition to the standards of any authorities having jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions.

Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspection

Service in accordance with local requirements and/or national codes.

TFP410

Page 10 of 10

Limited

Warranty

Products manufactured by Tyco Fire

Suppression & Building Products

(TFSBP) are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFSBP. No warranty is given for products or components manufactured by companies not affiliated by ownership with TFSBP or for products and components which have been subject to misuse, improper installation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire

Protection Association, and/or the standards of any other Authorities

Having Jurisdiction. Materials found by

TFSBP to be defective shall be either repaired or replaced, at TFSBP’s sole option. TFSBP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. TFSBP shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer’s representatives.

In no event shall TFSBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential damages, including but not limited to labor charges, regardless of whether

TFSBP was informed about the possibility of such damages, and in no event shall TFSBP’s liability exceed an amount equal to the sales price.

The foregoing warranty is made in lieu of any and all other warranties, express or implied, including warranties of merchantability and fitness for a particular purpose.

This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materials or components, whether the claim is made in contract, tort, strict liability or any other legal theory.

This warranty will apply to the full extent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder.

Ordering

Procedure

Contact your local distributor for availability. When placing an order, indicate the full product name and Part

Number (P/N).

Sprinkler Assembly

Specify Series LFII Residential

Horizontal Sidewall Sprinkler (TY1334),

K=4.2, with (temperature rating) and

(finish), and P/N (below).

155°F (68°C)

Chrome Plated . . . . . . . . . . . . P/N 51-211-9-155

155°F (68°C)

White Polyester . . . . . . . . . . . . P/N 51-211-4-155

155°F (68°C)

White

(RAL9010)* . . . . . . . . . . . . . . . . P/N 51-211-3-155

155°F (68°C)

Natural Brass . . . . . . . . . . . . . . .P/N 51-211-1-155

175°F (79°C) or

Chrome Plated . . . . . . . . . . . . P/N 51-211-9-175

175°F (79°C)

White Polyester . . . . . . . . . . . . P/N 51-211-4-175

175°F (79°C)

White

(RAL9010)* . . . . . . . . . . . . . . . . P/N 51-211-3-175

175°F (79°C)

Natural Brass . . . . . . . . . . . . . . .P/N 51-211-1-175

*Eastern Hemisphere sales only.

Recessed Escutcheon

Specify Style 20 Recessed Escutcheon with finish and P/N. Refer to Technical

Data Sheet TFP770.

Sprinkler Wrench

Specify W-Type 6 Sprinkler Wrench,

P/N 56-000-6-387.

Specify W-Type 7 Sprinkler Wrench,

P/N 56-850-4-001.

Copyright © 2006-2010 Tyco Fire Suppression & Building Products. All rights reserved.