Below you will find brief information for Water Storage & Booster Package VX2 ScubaTANK. The ScubaTANK is a space-saving dual-pump booster system designed to supply water to properties where mains pressure is insufficient. The overall design, combining submersible pumps in an insulated tank, eliminates most of the noise associated with domestic booster systems. Also the internal pipework design has been optimised to minimise hydraulic noise, and the controllers selected for optimum reliability and low running costs.
advertisement
ScubaTANK™
VX2
SERIES
Combined Water Storage
& Booster Package
FULL USER GUIDE
© Manual Copyright Dutypoint Systems 2011/12/13/14
The contents, information and copyright of this manual are the sole property of Dutypoint Systems. No part of this manual may be copied, reproduced, stored or transmitted in any form, or be translated into any language without prior written permission of the owners.
Every effort has been made to ensure the accuracy of this manual at the time of printing, however our policy of continuous improvement means that specifications and instructions may change without notice.
DUTYPOINT SYSTEMS
SHEPHERD ROAD
GLOUCESTER
GL2 5EL
UK
Tel: 44 (0) 1452 300592
Fax: 44 (0) 1452 303691
Email: sales@dutypoint.
com www.dutypoint.
com
Dutypoint Part Number ScubaTANK™ VX2 - M03
Iss.2 - Mar 2014
Contents
ScubaTANK™ VX2
Iss.2 - Mar 2014
1
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
2
Important Health & Safety Information
High voltage testing may damage electronic components ..............................8
Operating Limits For The Standard Dutypoint ScubaTANK™ Range ........................8
Specifications, Configurations & Dimensions
XPR3000 Series Pumps @ 2850rpm ..............................................................25
XPR5000 Series Pumps @ 2850rpm ..............................................................26
XPR9000 Series Pumps @ 2850rpm ..............................................................27
Identifying your ScubaTANK™ system ...........................................................30
ScubaTANK™ VX2
Iss.2 - Mar 2014
Operational Alarms and Alerts (VASCO Pump Controllers) ....................................... 44
Recommended user weekly checks ............................................................... 46
Recommended user monthly checks .............................................................. 46
Recommended user 6 monthly checks ........................................................... 46
Essential 12 monthly (maximum interval) service ........................................... 46
General guidance notes for vessel repair & replacement ............................... 48
Inlet Solenoid Close Control & Bypass Screw Adjustment ......................................... 49
Miscellaneous Technical Information
General Operating Limits (Standard Dutypoint Pumpsets) ........................................ 82
Contents
ScubaTANK™ VX2
Iss.2 - Mar 2014
3
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
4
ScubaTANK™ VX2
Iss.2 - Mar 2014
ScubaTANK™ VX2
Iss.2 - Mar 2014
SAFETY
Important Health & Safety
Information
Please read this section before attempting to use
or work on your ScubaTANK™ VX2 Combined
Water Storage & Booster Package as it contains
important Safety Information and the System
Operating Limitations.
5
6
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
User Guide - Document Conventions
Throughout this manual, text may be accompanied by one of the following icons.
Where these occur the conventions shown below are applied.
In general these conventions will also apply to OEM Manufacture’s manuals that are included within this User Guide, however variations may occur, but these will be redefined at the beginning of their manual.
DANGER
Denotes attention to the possibility of the risk of personal injury or damage to adjacent property if the information is ignored.
ELECTRIC
SHOCK
Denotes attention to the possibility of life-threatening electric shock if the information is ignored.
or
WARNING
WARNING
Denotes attention to a condition that may result in under-performance or damage to the equipment if the information is ignored.
NOTE
Denotes attention to an important factor applicable to the action being performed.
PLEASE READ THE FOLLOWING INFORMATION WHICH IS PROVIDED FOR YOUR SAFETY
ScubaTANK™ VX2
Iss.2 - Mar 2014
Important Health & Safety Information
United Kingdom Health & Safety at Work Act 1974
Dutypoint responsibility
Section 6(a) of this Act requires manufacturers to advise their customers on the safety and the handling precautions to be observed when installing, operating, maintaining and servicing their products. The user’s attention is therefore drawn to the following:
• The appropriate sections of this manual must be read before working on the equipment.
• Installation, operating and maintenance must only be carried out by suitably trained/qualified personnel.
• Normal safety precautions must be taken and appropriate procedures observed to avoid accidents.
Refer to DUTYPOINT SYSTEMS for any technical advice or product information.
Customer / Contractor responsibility
It is the responsibility of the customer and/or the contractor:
• To ensure that anyone working on the equipment is wearing all necessary protective gear/clothing.
• Is aware of appropriate health & safety warnings
• has read the information in this section of the manual.
ScubaTANK™ Servicing
Before attempting to open any unit or service a pump:
• Familiarise yourself with the relevant contents of this manual.
• Installation, maintenance and repair work must only be carried out by trained, skilled and suitably qualified personnel.
• Disconnect or lock-out the power source to ensure that the pump(s) will remain inoperative.
Locking out the equipment by switching off the release mechanism or set value WILL NOT prevent accidental starting of the motor.
• Allow the pump(s) to cool if over-heated.
• CLOSE the isolating valves on the suction and discharge connections of the affected pump(s).
• VENT the pump(s) slowly and cautiously – Refer to Section 4 of this
manual.
• DRAIN the pump(s).
Electrical Safety
High voltages
Especially applicable when Variable Speed Controllers (Inverters) are fitted.
• When the inverter variable speed drive head is connected to the power supply the components of the power unit – as well as certain components of the master control unit – are also connected to the power supply.
TOUCHING THESE COMPONENTS CAN SERIOUSLY ENDANGER LIFE!
ScubaTANK™ VX2
Iss.2 - Mar 2014
7
8
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
• Before removing the frequency inverter cover, the system must be disconnected from the power supply. After switching off the power supply
wait at least 5 minutes before starting work on or in the inverter drive head
– the capacitors in the intermediate circuit must be given time to discharge completely via the discharge resistors.
Up to 800 volts can be present – if there are faults this can be higher.
• All work carried out when the frequency inverter is open must be performed only by suitably qualified and properly authorised personnel.
When connecting external control wires care must be taken not to short circuit adjacent components. Bare cable ends which are not in use must be insulated.
THE SYSTEM MUST ONLY BE OPERATED WHEN IT HAS BEEN CORRECTLY
EARTHED AND PIPES BONDED TO EARTH IN ACCORDANCE WITH IEE
REGULATIONS
Electronic safety devices
• The inverter drive heads used in Dutypoint Systems Pumpsets contain electronic safety devices which switch off the control element in the event of a fault developing.
The motor will have zero current but will remain energised as it stops.
• The motor can also be stopped by ‘mechanical blocking’.
• If it is switched off electronically, the motor is disconnected from the mains voltage supply via the electronics in the frequency converter.
The motor is not voltage-free in the circuit itself.
• Voltage fluctuations and power failures (temporary outages) can cause the motor to switch itself off.
Repair of faults can cause the motor to start up again unexpectedly!
High voltage testing may damage electronic components
• High voltage tests of the inverter or the motor may damage the electronic components.
Bridge before the incoming/outgoing terminals L-L2-L3 and U-V-W.
• To avoid incorrect metering by capacitors incorporated in the electronic circuits, isolate the motor from the inverter drive head.
Operating Limits For The Standard Dutypoint ScubaTANK™ Range
Type of pumped liquids.
Water with no gas or aggressive substances.
Maximum pumped liquids temperature. +23°C
Minimum pumped liquid temperature.
1°C to avoid icing.
Operating ambient temperature.
Relative humidity.
+5°C to 40°C for indoor installation.
(CEI EN 60439-1).
Max 50% at 40°C.
Storage temperature.
+5°C to 50°C.
ScubaTANK™ VX2
Iss.2 - Mar 2014
Important Health & Safety Information
ScubaTANK™ VX2
Iss.2 - Mar 2014
9
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
10
ScubaTANK™ VX2
Iss.2 - Mar 2014
ScubaTANK™ VX2
Iss.2- Mar 2014
1
Introduction
This Section introduces the Dutypoint
ScubaTANK™ VX2 Combined Water Storage &
Booster Package and provides an overview of the
Pumps and Controllers.
11
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
Welcome
Thank you for purchasing one of the DUTYPOINT range of ScubaTANK™ VX2
Combined Water Storage & Booster Packages.
Dutypoint Systems is a Division of Elmbridge Pumps Company and manufactures pressure boosting pump systems. Since its beginnings as a supplier of pumpsets to the water industry the name 'Dutypoint' has become synonymous with unrivalled quality, service and reliability.
This manual is compiled as a composite to include both the Dutypoint package information and the specific manufacturer’s information necessary for the installation, safe operation and user maintenance of your ScubaTANK™.
Please read and familiarise yourself with the contents of this manual.
Overview
The ScubaTANK™VX2 is a space-saving dual-pump booster system designed to supply water to properties where mains pressure is insufficient.
The vented insulated tank incorporates two stainless steel submersible pumps variable speed inverter drives. A pressure vessel and required valves are also integrated into the assembly. The inlet water supply is controlled by a slow-close solenoid valve.
It is the Installer’s responsibility to ensure that the Overflow and Warning Pipe (if fitted) are suitably piped.
The overall design, combining submersible pumps in an insulated tank, eliminates most of the noise associated with domestic booster systems. Also the internal pipework design has been optimised to minimise hydraulic noise, and the controllers selected for optimum reliability and low running costs.
Pressure Vessel
Vessel
Isolation/Drain
Valve
Control Panel
& Isolator
Submersible
Pumps x2
GRP Tank
Fixing
Bracket
Outlet &
Isolation Valve
VASCO Pump
Controllers x2
Vent
Overflow
Connection
Overflow
Warning Pipe
(Tanks over
800ltr only)
Inlet/Solenoid
Valve
Fig. 1-1 ScubaTANK™ VX2
12
ScubaTANK™ VX2
Iss.2- Mar 2014
Section 1 Introduction
Technical features
• GRP construction tank, 25mm insulation (HCFC and
CFC free).
Reinforced base (encapsulated multi-ply board).
• Stainless steel submersible pumps.
• Stainless steel pressure vessel with drain valve.
• 1” Probe-controlled high-flow solenoid valve input.
• 1¼” BSP full-bore discharge connection (2” available on request).
• 2“Overflow pipe. Overflow warning pipe fitted to tanks above 800 litres.
• Low water level pump protection device.
• Stainless steel pumps.
• 2xVASCO Inverter pump controllers (230 volt single phase).
• LED system status display.
• Control box with MCB protection.
Options
• Remote alarm panel with common fault volt-free contacts.
• Integral flow meter.
Full details of tank sizes and technical specifications are provided in Section 2 of this
manual.
Pump
The ScubaTANK™ uses a pair of submersible pumps selected from the stainless steel Modus XPR range.
Various pumps pressure and flow rate are available allowing selection to suit a wide usage range.
The specification curves for these pumps can be found
Fig. 1-2 Modus XPR Pump
VASCO variable speed controllers
The pumps are driven by VASCO (variable speed controller) units fitted to each pump. These are variable frequency drive units designed to control and protect pumping systems by varying the output frequency to the pump.
They manages the system operation to maintain a certain constant physical quantity
(pressure, differential pressure, flow, temperature, etc.) regardless of the conditions of use. The pumps (configured in duty/assist or duty/standby mode) are operated only when needed thus avoiding unnecessary energy consumption and providing overall energy cost saving, longer pump life and improved reliability.
ScubaTANK™ VX2
Iss.2- Mar 2014
13
14
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
The design of the controller incorporates motor overload and dry-running protection with soft-start/stop functionality for increased system life and reduction in current surges. An indication of current consumption, voltage, and power is provided together with a run time record, and list any errors and/or failures reported by the system.
Dangerous induced surges associated with long power cables can be eliminated by using the units in association an optional inductive filter.
Full detail of operating display and setting up of the VASCO controller is given in the manufacturer’s manuals republished in
Appendix B of this manual.
Fig. 1-3 VASCO Controller
Control box
Power to the ScubaTANK™ pumps and controllers is connected through a control box mounted between the two VASCO pump controller units. Two MCBs in the box act as electrical isolators for each pump. The input power requirement varies from 5 to 12A @230v
50hz dependent upon tank/pump size.
The control box also houses the probe relay units which services the flow control system.
Pressure vessel
Fig. 1-4 Control Box
The ScubaTANK™ system has an integral stainless steel sealed pressurisation vessel of 12ltr capacity. An isolation/drain valve is provided below the vessel to facilitate maintenance.
Fig. 1-5 Pressure Vessel
ScubaTANK™ VX2
Iss.2- Mar 2014
ScubaTANK™ VX2
Iss.2- Mar 2014
2
Specifications,
Configurations &
Dimensions
This Section lists specifications and the specific details for available variants of the ScubaTANK™
VX2 Combined Water Storage & Booster Package.
15
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
Identifying Your ScubaTANK™
Attached to each tank is a label (fig 2-1) that identifies the type and specification.
XPR Pump Type
Controller
Type &
Quantity.
VX2 3080
250
Actual
Tank
Capacity
Fig. 2-1 Labelling
Detailed Specifications
Suitability
Flow range
Pressure range
Liquid temperature
Water with no gas or aggressive substances.
1.2 - 3.1Litres/sec.
2.5 - 7.0 Bar.
Max +
23°C for domestic uses. Min +1°C to avoid icing.
Operating temperature +5 to 40°C for indoor installation. Relative humidity Max 50% @ +40°C.
Storage temperature
+5 to 50°C.
Controller type
Protection
Tank construction
Tank Capacity
Tank Dimensions
Modus VASCO (x2).
Low water level via probe control.
GRP construction.
25mm Insulation (HCFC and CFC free).
Base reinforced with encapsulated multi-ply board and fitted with security fixing brackets.
375ltr, 650ltr, 800ltr, 1050ltr, 1250ltr, 1650ltr,
2250ltr.
Inlet Valve
Discharge
Pressure vessel
Pump rating
1” Full bore solenoid valve
1¼” BSP (2” available on request).
Screened vent and overflow.
12ltr, Stainless steel construction.
3040
3060
3080
5040
5060
5080
9040
9060
Pump
Type
XPR3040
XPR3060
XPR3080
XPR5040
XPR5060
XPR5080
XPR9040
XPR9060
Motor
Power
0.55kW
0.75kW
1.10kW
0.75kW
1.10kW
1.50kW
1.50kW
2.20kW
Full Load
Current
4.1A
5.2A
7.4A
5.0A
7.4A
10.5A
10.5A
11.9A
16
ScubaTANK™ VX2
Iss.2- Mar 2014
Arrangement & Dimensions
ScubaTANK™ VX2 375
Section 2 Specifications, Configurations & Dimensions
600
ScubaTANK™ VX2
Iss.2- Mar 2014
160 196
50mm CLEARANCE 1
MIN
62
03 17
1200
17
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
ScubaTANK™ VX2 490
18
750
160 196
50mm CLEARANCE 1
MIN
62
1200
03 17
ScubaTANK™ VX2
Iss.2- Mar 2014
ScubaTANK™ VX2 650
Section 2 Specifications, Configurations & Dimensions
160 196
50mm CLEARANCE 1
MIN
62
750
ScubaTANK™ VX2
Iss.2- Mar 2014
03 17
1200
19
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
ScubaTANK™ VX2 800
20
1160
160 196
E 150mm CLEARANC
MIN
62
1000
1503
ScubaTANK™ VX2
Iss.2- Mar 2014
ScubaTANK™ VX2 1050
Section 2 Specifications, Configurations & Dimensions
160 196
50mm CLEARANCE 1
MIN
62
800
ScubaTANK™ VX2
Iss.2- Mar 2014
2003
1500
21
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
ScubaTANK™ VX2 1250
22
1160
160 196
50mm CLEARANCE 1
MIN
62
2003
1500
ScubaTANK™ VX2
Iss.2- Mar 2014
ScubaTANK™ VX2 1650
Section 2 Specifications, Configurations & Dimensions
160 196
50mm CLEARANCE 1
MIN
62
ScubaTANK™ VX2
Iss.2- Mar 2014
1160
2003
1500
23
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
ScubaTANK™ VX2 2250
160 196
50mm CLEARANCE 1
MIN
62
24
1160
2003
1500
ScubaTANK™ VX2
Iss.2- Mar 2014
Section 2 Specifications, Configurations & Dimensions
Pump Performance
XPR3000 Series Pumps @ 2850rpm
ScubaTANK™ VX2
Iss.2- Mar 2014
25
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
XPR5000 Series Pumps @ 2850rpm
26
ScubaTANK™ VX2
Iss.2- Mar 2014
Section 2 Specifications, Configurations & Dimensions
XPR9000 Series Pumps @ 2850rpm
ScubaTANK™ VX2
Iss.2- Mar 2014
27
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
Pump Controller Specification
Modus VASCO Type 209 or 214
• Input Voltage
• Max. Input Current
• Max. Motor Current
• Typical P2 Motor
• Protection index
• Max. altitude
• Max. ambient temperature
Nominal 230Vac, single phase, 50/60 Hz.
[209] 15A, [214] 20A
230V ~1 9A / phase.
1.1KW, 1.5HP.
IP55 (NEMA 4).
1000m @ nominal current.
40°C at nominal current.
• PWM configurable
• Serial Comms
2.5, 4, 6, 8,10 kHz.
RS485.
VASCO is able to power the motor with a higher current for a short period of time according to the linear relation: 101% of the nominal current for 10min., 110% nominal current for 1 min.
28
ScubaTANK™ VX2
Iss.2- Mar 2014
ScubaTANK™ VX2
Iss.2- Mar 2014
3
Installation &
Commissioning
This Section provides information on siting, connecting and commissioning the ScubaTANK™
VX2 Combined Water Storage & Booster Package.
• Basic Installation Information
29
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
Basic Installation Information
Installation help
Before shipment, all Dutypoint ScubaTANKs are run and pressure tested. Parameters including pressure settings and delay timers can be adjusted on commissioning to suit the site conditions. In practice, a system can almost invariably be made to perform more efficiently on site.
For pre or post-installation help, call the Dutypoint Technical Service Help line:
01452 300590
Identifying your ScubaTANK™ system
The label attached to the tank identifies the system, allowing the installation requirements to be clarified. The label information and resulting full specification can
be found by referring to Section 2.
30
Fig. 3-1 ScubaTANK VX2 Typical Installation
ScubaTANK™ VX2
Iss.2- Mar 2014
Section 3 Installation & Commissioning
Installation Sequence
• Position and secure the Tank.
• Connect the inlet water supply via a Y-type strainer and an isolation valve.
• Connect the overflow system.
• Connect the outlet pipe.
• Connect the electrical supply cable.
• Fill the system and vent the pump.
• Test and commission.
Siting the ScubaTANK™
The ScubaTANK
VX2
™ MUST be installed on a level stable floor or plinth capable of supporting the liquid weight of the full tank. (Details of the tank footprint and height are shown in fig 3-2.)
• Refer to fig 3-2 for an overview of tank dimensions and footprint or to
An additional 150mm MUST be allowed below any top surface to allow access for maintenance.
• The area should be dry, frost-free and well ventilated, away from extremes
of temperature (refer to page 16 for temperature information). All pipe work
must be adequately protected from freezing.
• Adequate provision should be made for drainage, leakage damage protection and service access
• The tank is freestanding and is provided with fixing feet for secure fastening to the floor.
Tank
375
490
650
800
1050 **
1250 **
1650 **
2250 **
Footprint (mm)
D x W (mm)
600 x 950
750 x 950
750 x 1200
1160 x 1160
800 x 1500
1160 x 1160
1160 x 1500
1160 x 2000
Overall Height
(mm) *
Height to Top of
Open Tank (mm)
1703
1703
1703
1503
1200
1200
1200
1000
2003
2003
2003
1500
1500
1500
2003 1500
Fig. 3-2 ScubaTANK™ Dimensions
• * An additional 150mm minimum clearance is required above overall height.
• Inlet centre: 62mm below open tank top height.
• ** Additional Overflow Warning
Pipe: ¾” pushfit
ScubaTANK™ VX2
Iss.2- Mar 2014
31
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
Hydraulic Connection
• All pipework must be in accordance with local Water Authority regulations.
• A Y-type strainer, fitted horizontally) and an isolation valve should be fitted to the mains water supply to the unit.
• The discharge pipework must be sized according to the system demand.
• All pipework must be securely supported and not over-stressed.
• The overflow and the warning pipe (if fitted) must be suitably piped.
The factory-set closing speed screw on the inlet solenoid valve adjusts the input flow rate and MUST NOT be re-adjusted except by a competent engineer following the
procedure on page 49. Correct operation MUST be verified before leaving the unit
unattended.
ADJUSTING WILL INVALIDATE THE WARRANTY.
The bypass screw is only for temporarily use in the event of an electrical failure.
Electrical Supply
ALL ELECTRICAL WORK MUST BE CARRIED OUT BY A SUITABLY QUALIFIED
PERSON FOLLOWING THE LATEST IEE REGULATIONS
THE SYSTEM MUST ONLY BE OPERATED WHEN IT HAS BEEN CORRECTLY
EARTHED AND PIPES BONDED TO EARTH IN ACCORDANCE WITH THE LATEST IEE
REGULATIONS.
VASCOCONTROLLER ELECTRIC SHOCK DANGER
The Controller contains high voltage. NEVER open the Controller or work with any electrical connections within it, unless the electrical supply to the unit is isolated.
Wait a further 2 minutes after isolation for the internal circuitry to discharge.
• The electrical supply feed to the ScubaTANK™ should be a dedicated line to minimise electromagnetic interference.
• The electrical supply rating can be ascertained from the inset pump rating table.
• The control panel isolator cable should be connected via a suitably rated external MCB.
The probe relay settings are factory preset and should conform with the inset
.
ADJUSTMENT WILL INVALIDATE THE WARRANTY
Commissioning
• Refer to fig 3-3 and ensure that the probe relay is set correctly.
• Refer to Section 4, and run up the system to fill the tank.
• Verify that there are no leaks.
• Verify correct running.
• If required, refer to Appendix A to access the control parameters to optimise
them.
• Advise the user on correct operation.
32
ScubaTANK™ VX2
Iss.2- Mar 2014
Section 3 Installation & Commissioning
Electrical Supply Ratings
Pump
Type
Motor
Power
3040 XPR3040 0.55kW
3060 XPR3060 0.75kW
3080 XPR3080 1.10kW
5040 XPR5040 0.75kW
5060 XPR5060 1.10kW
5080 XPR5080 1.50kW
9040 XPR9040 1.50kW
9060 XPR9060 2.20kW
Full Load
Current
4.1A
5.2A
7.4A
5.0A
7.4A
10.5A
10.5A
11.9A
Probe Relay Settings
Time = 1
Sensitivity
= 0.9
Mode = A
The probe relay settings are factory preset.
ADJUSTMENT WILL INVALIDATE THE
WARRANTY
Fig. 3-3 Electrical Connections & Probe Relay Settings
ScubaTANK™ VX2
Iss.2- Mar 2014
33
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
34
ScubaTANK™ VX2
Iss.2- Mar 2014
ScubaTANK™ VX2
Iss.2- Mar 2014
4
Using the ScubaTANK™
This Section provides information on controlling and adjusting the ScubaTANK™ VX2 Combined
Water Storage & Booster Package.
• Basic Operational Information
• Restoring the Controller Configuration
• Starting and Running the ScubaTANK™
• Accessing the Advanced Parameters
35
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
The User Control Panels
System Isolation
The individual pump/controller system can be isolated using the MCBs located in the control box. All other pump control is carried out using the VASCO controllers.
Probe Relay
Timers
The probe relay settings are factory preset and should conform with the inset
ADJUSTMENT WILL INVALIDATE THE
WARRANTY
Pump/
Vasco MCB
Isolators
Fig. 4-1 System Isolators
Basic Operational Information
The VASCO display
The display screen on the VASCO is a back-lit LCD displaying 2 rows of 16 digits each. Alarms are indicated by an audible signal
Initial view
When first powering the VASCO, the display shows:
LCD = X.XX
INV = X.XX
Release of display software
Release of inverter software
ENTER
Scroll
Down
START motor
Scroll Up
STOP motor
Menu exit
Alarms reset
Fig. 4-2 The VASCO Display
.
One pump/VASCO combination will have been set as master (display name 00) and one as slave (display name 01). The term “INV:” will be replaced by the appropriate display name, “00:” or “01:”
Various End User messages are then displayed. Increment to the next by pushing the
Scroll buttons:
The First Row of the display gives the VASCO/Pump status as follows:
• Inv: ON XXX.X Hz VASCO is powered and is powering the motor showing its frequency.
• Inv: ON Mot: OFF VASCO is powered but motor is not running (i.e.
motor/pump was stopped due to minimum frequency being reached).
• Inv: OFF Mot: OFF VASCO is not powered.
The Second Row of the display provided the following information:
Inv: ON/OFF Mot: ON/OFF p_m = XX.X [bar]
p_m is the value read by the pressure transducer.
By pressing ENTER the pressure set value is displayed. By keeping ENTER pressed for more than 5 seconds, it is possible to modify the set pressure in real time.
36
ScubaTANK™ VX2
Iss.2- Mar 2014
Section 4 Using the ScubaTANK™
Inv: ON/OFF Mot: ON/OFF f = XXX [Hz]
Inv: ON/OFF Mot: ON/OFF
V = X.XX [V] I= XX.X [A]
f is the supply frequency to the motor.
By pressing ENTER you can change the f value manually (the word “set” is displayed). Press ENTER again to exit parameter setting (the word “set” disappears).
V is the voltage supplied to the motor.
This value is displayed only if motor is OFF.
If the motor is ON, a value I equal to the absorbed motor current is displayed.
cosphi index means the phase angle phi between the voltage and current absorbed by the motor.
Inv: ON/OFF Mot: ON/OFF cosphi = XXX
Inv: ON/OFF Mot: ON/OFF
P = XXXXX [W]
Inv: ON/OFF Mot: ON/OFF
STATUS: NORMAL
Inverter Life xxxxx h : xx m
Motor Life xxxxx h : xx m
%f 25 50 75 100
%h XX XX XX XX
XXXXXXXXXXXXXXX
XXXXXXX h : XX m
Menù
ENT to access
P is the power in Watts supplied to the pump.
NORMAL status means no alarms.
If an alarm occurs, a message blinks on the display and an audible signal is activated.
Pressing ENTER accesses:
VASCO hours run, PUMP hours run, Consumption statistics,
Alarm list.
PUMP hours refer to pump powered time.
To return to previous views, press ENTER.
Menu view
Pressing ENTER when you are in initial display [MENU / ENT] will display the following sub MENUs to allow access to the installer and advanced options.
You should only access and adjust installation and advanced parameters if you are trained to do so, as improper setting of them could compromise the integrity and the life of the controller and the pump. A full description of the installation and advanced
parameters is available in Appendix A of this manual.
Call the Dutypoint Technical Service Help line 01452 300590.
MENU’
Install. param.
Installer password required to enter level 1 (default 001)
MENU’
Advanced. param.
MENU’
Retrive init. set
Advanced password required to enter level 2 (default 002)
Installer password required to enter level 1 (default 001)
Here it is possible to return to original set parameters.
MENU’
Change init. set.
Advanced password required to enter level 2 (default 002)
To exit the MENU level and return to initial display, press the STOP button.
ScubaTANK™ VX2
Iss.2- Mar 2014
37
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
Restoring the Controller Configuration
Your pumpset will have been tested and set to a default initial set of parameters to configure pump characteristics, pressure sensor range, and system characteristics.
Without these initial settings it is impossible to run the pump.
If required, the initial settings can be restored using the 1st level password as described above.
A full description of these settings is available
Call the Dutypoint Technical Service Help line 01452 300590.
Starting and Running the ScubaTANK™
Initial installation
As supplied the tank will have been tested and set to a default initial set of parameters configuring pump, sensor range, and system characteristics, allowing the user to run the pump on installation.
The master pump/VASCO will be identified as “00” and the slave as “01”.
Ensure that the Outlet Valve is OFF (no demand).
Switch on the pumps as follows:
• Power On the VASCOs in turn using the control box contact breakers.
Ensure that the LCD screens initially display the software issue, then
reports 00:(or 01:) On Motor Off, (refer to page 36).
The tank should start to fill.
• Turn on one pump by pressing the START MOTOR button on the associated VASCO.
The LCD screen then reports 00:(or 01:) On Motor On on the duty pump.
• Open the Tank outlet to create a demand.
The pump should respond to demand.
• Turn off the running pump using the STOP MOTOR button.
• Turn on the other pump by pressing the START MOTOR button on the associated VASCO.
The LCD screen then reports 01:(or 00:) On Motor On on the duty pump.
• Open the Tank outlet to create a demand.
The pump should respond to demand and confirms that both pumps are working.
• Turn the other pump back on by pressing the START MOTOR button on the associated VASCO.
The LCD screen should only reports 00:(or 01:) On Motor On on the duty pump.
• Open the Tank outlet to create a demand.
• Simulate a failure of the running pump by switching its main MCB isolator off.
The off -line pump should start to maintain output flow.
• Switch the “faulted” pump back on and repeat the test by turning off the other MCB isolator.
The standby pump should immediately come on to satisfy demand.
38
ScubaTANK™ VX2
Iss.2- Mar 2014
Section 4 Using the ScubaTANK™
Normal running
Ensure that the tank is full before starting the VASCOs
Switch on the pumps as follows:
• Power On the VASCOs in turn using the control box contact breakers.
Ensure that the LCD screens initially display the software issue, then
reports 00:(or 01:) On Motor Off (refer to page 36).
• Turn on both pumps by pressing the START MOTOR button on the
VASCOs.
The LCD screen then reports 00:(or 01:) On Motor On on the duty pump;
01:(or 00:) On Motor Off on the standby pump.
Both pump/VASCO combinations will have been configured to identical parameters.
In case of an alarm or failure of a pump in a system, this pump’s operation will be replaced
(temporary or permanently) by the other pump.
Protection and Fault Alarms
Whenever a fault is detected, a flashing message is displayed on the Controller display together with an audible alarm.
The STATUS message in the initial view will display the fault.
• Pressing the STOP button will attempt to reset the alert. If the reset is unsuccessful the message is re-displayed and the alarm re-sounds.
• If dry-running occurs for over 2 seconds, the Controller will stop the pump. It will then attempt to re-run the pump at 10, 20, 40, 80, 160 minute intervals and then permanently stop it.
If dry-running occurs, the Controller will try to restart the pump automatically.
ENSURE YOU SWITCH OFF THE POWER BEFORE ATTEMPTING MAINTENANCE.
• The Controller will stop the pump if the motor current is higher than the preset motor current for an extended time.
By pressing the START button it is possible to run the pump again.
• The Controller will stop the pump if the input voltage goes higher than the preset voltage for an extended time.
By pressing the START button it is possible to run the pump again.
• The Controller will stop the pump if the input voltage goes lower than the preset voltage for an extended time.
By pressing the START button it is possible to run the pump again.
Other possible causes of general faults and their solutions can be found in
ScubaTANK™ VX2
Iss.2- Mar 2014
39
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
Alert Messages and Possible Causes
You should only adjust attempt to rectify faults by accessing and adjusting installation and advanced parameters if you are trained to do so, as any improper setting of them could compromise the integrity and the life of the controller and the pump. A description of the installation and advanced parameters is available
Call the Dutypoint Technical Service Help line 01452 300590.
ALARM MESSAGE
OVERCURRENT MOT.
UNDER VOLTAGE
OVER VOLTAGE
OVER TEMP. INV.
NO LOAD
SENSOR FAULT
NO WATER
(DRY RUN COSPHI)
MAX.VALUE ALARM
MIN.VALUE ALARM
ALARM DESCRIPTION
Motor overload. The input current of the motor is higher than the rated motor current setting parameter.
Motor voltage drop caused by the inverter causes the motor input current to be higher than the rated current.
Contact the manufacturer to check if the motor is capable of accepting this current.
Supply voltage too low.
POSSIBILE SOLUTIONS
Make sure that the motor current setting parameter is higher than the rated current.
Check for other possible causes of over current.
Check possible causes of undervoltage.
Supply voltage too high.
Inverter over temperature.
No load.
Sensor error.
Motor cosphi is lower than the set value of the dry running cosphi.
Check possible causes of overvoltage.
Make sure than ambient temperature is less than 40 °C (104 °F).
Check the cooling fan is working properly and providing proper cooling.
Reduce the PWM value (Advanced Parameter
Menu).
Check if motor is properly connected to the
VASCO terminals.
Check the transducer.
Check the wiring from the transducer.
Check if the pump is primed.
Check the set value of dry running cosphi. Dry
running cosphi is approximately 60% of the rated cosphi (at rated frequency) listed on the motor plate.
If pump’s cosphi is lower than the set dryrunning cosphi for at least 2 seconds, the controller stops the pump. It then tries to run the pump again at 10, 20, 40, 80, 160 minute intervals and then the pump is stopped.
WARNING: If dry running protection occurs, the controller will try to start the pump automatically. Be sure to switch off the power
source to before performing any maintenance.
Measured value has reached the maximum value accepted by the system.
Check possible causes of max value.
Check max value parameter setting.
Measured value has reached the lowest value accepted by the system.
Check possible causes of min value (e.g.
broken pipe, open pressure relief valve, etc.).
Check min alarm value parameter setting.
40
ScubaTANK™ VX2
Iss.2- Mar 2014
Section 4 Using the ScubaTANK™
IGBT TRIP ALARM
NO COMMUNICATION
ADDRESS ERROR
KEYBOARD FAULT
DIGITAL INPUT
ALARM SLAVE XX
The current drawn by the load exceeds the capacity of the fitted controller.
The controller is still able to continue to power the load for 10 minutes with an output current of 101% of nominal and for 1 minute with an output current of
110% of nominal.
Increase the ramp-up time.
Make sure that the load current is at least 10% below the controller nominal current.
Check the voltage drop along the supply cable to the motor.
Communication between Master and
Slave(s) has been interrupted.
Same address as other Controllers in the group.
A button on the keyboard has been pressed for more than 150 seconds.
Digital input opened/closed.
Slave XX error detected by Master
Check the wiring connections.
Make sure the Master is not in the Menu level.
If so, exit from the level.
In STATUS on the Slave (where the alarm is displayed) try to reset the alarm by pushing
STOP button.
The address of each controller needs to be set differently.
Make sure buttons are not depressed.
Call manufacturer’s service assistance.
Check the input digital configuration (Located in
Installer Parameters menu.)
Check the status of the Slave.
Accessing the Advanced Parameters
You should only adjust attempt to rectify faults by accessing and adjusting installation and advanced parameters if you are trained to do so, as any improper setting of them could compromise the integrity and the life of the controller and the pump. A description of the installation and advanced parameters is available
Call the Dutypoint Technical Service Help line 01452 300590.
ScubaTANK™ VX2
Iss.2- Mar 2014
41
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
42
ScubaTANK™ VX2
Iss.2- Mar 2014
5
Troubleshooting
This Section provides general troubleshooting tips applicable to the Dutypoint ScubaTANK™
VX2 Combined Water Storage & Booster Package.
ScubaTANK™ VX2
Iss.2 - Mar 2014
43
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
When a fault first occurs, turning off the main power to the Tank, leaving off for around 1 minute before powering back on, may be sufficient to clear the fault.
Operational Alarms and Alerts (VASCO Pump Controllers)
The VASCO controllers continuously monitor and provide operational alarms and
alerts. These are listed in this manual in Section 4 (page 39). Additional VASCO
troubleshooting information can be found in the manufacturers manual in Appendix A.
General Tank Troubleshooting
Item/Fault
Pump will not start.
Low (or zero) output
(discharge rate).
Pump vibrates and/ or is noisy
Pump running continuously
Overload Trip
1. No electrical power.
2. Blown fuse(s).
3. Overload trip.
4. Faulty Controller
1. Check and rectify.
2. Check and rectify.
3. Check and try to reset the overload trip.
4. Refer to controller operational troubleshooting in Section 4 (page 38).
1. Open the tank to examine the pump to
inspect and rectify. Refer to page 49.
1. The rotating part of the pump is partially or completely obstructed e.g: impeller obstructed by foreign matter.
2. Pump not primed.
WARNING: running the pump ‘dry’ can cause serious damage to the mechanical seal.
3. Valve fully or partially closed.
4. Incorrect pump rotation direction.
5. Pump failing.
1. Pump is cavitating.
2. Low water level. Check and rectify.
3. Check all appropriate valves are fully open.
4. Pump is either incorrectly wired or the controller is incorrectly programmed.
Refer Section 6 to check and rectify.
5. Replace pump.
1. Increase the discharge back pressure slightly by progressively closing a manual isolating valve on the discharge side until the cavitation stops.
2. Replace pump.
3. Open the tank to examine the pump to inspect
and rectify. Refer to page 49.
1. Motor bearings worn.
2. The rotating part of the pump is partially or completely obstructed e.g: impeller obstructed by foreign matter.
1. The pump is switched to “Hand” operation.
2. Controller fault.
1. Pipework or the pump chamber has a partial blockage.
2. Momentary loss of power supply.
3. Discharge flow rate too high.
4. Incorrect overload trip value.
1. Switch back to “Auto”.
2. Arrange an immediate service visit.
1. Check and rectify.
Reset the trip and try again.
2. Reset the trip and try again.
3. Reduce by the discharge flow rate by increasing the discharge back pressure slightly by progressively closing the manual isolating valve on the discharge side.
Reset the trip and try again.
4. Check value (Section 3) and if incorrect
change the overload trip.
44
ScubaTANK™ VX2
Iss.2 - Mar 2014
ScubaTANK™ VX2
Iss.2 - Mar 2014
6
Routine Maintenance &
Repair
This Section provides information on maintenance and repair ScubaTANK™ VX2
Combined Water Storage & Booster Package.
45
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
Routine User Maintenance
Dutypoint Pumpsets have been designed to keep major maintenance requirements to a minimum. Planned maintenance of the pumps and other principal components should therefore be undertaken at the intervals recommended below.
In addition, the user should routinely make visual checks of the equipment during use, noting particularly any unusual noises or vibrations. This will give an immediate indication of any irregularity in the operation of the system.
It is essential that a full test following the Commissioning procedure (refer to
Section 3) is carried out on an annual basis.
DO NOT COMMENCE ANY MAINTENANCE WORK UNLESS YOU ARE SUITABLY
QUALIFIED TO SO AND HAVE READ THE SAFETY SECTION AT THE BEGINNING OF
THIS MANUAL.
Refer to the information that is provided in this section for procedures.
Recommended user weekly checks
• Inspect the ScubaTANK™ and system for leaks, etc.
• Observe the running of the pump and note any unusual vibration, etc.
Recommended user monthly checks
• Switch off and visually check the security of the ScubaTANK™ hydraulic and electrical connections.
• Observe the running of the pump and note any unusual vibration, etc.
• Check the vents on the controller and clear any dust or other obstructions.
• Operate the manual isolating valve three times to ensure continued efficient working.
Recommended user 6 monthly checks
• The pressure vessel should be drained and the pre-charge pressure
checked with a gauge and if necessary corrected (refer to page 47).
• Undo the tank lid (refer to page 49), and check the cleanliness of the pump
inlet grating. Replace the lid.
Essential 12 monthly (maximum interval) service
Carry out the full Commissioning procedure to verify correct safe operation. Refer to
46
ScubaTANK™ VX2
Iss.2 - Mar 2014
Section 6 Routine Maintenance & Repair
Pressure Vessel Servicing
Service information below is taken from the Manufacturer’s Installation Manual.
Periodic maintenance
Periodic maintenance is recommended at least twice a year and should be carried out by authorised specialised personnel only.
1. First check that the expansion or pressure tank is totally drained of water, and that the system is switched off and no electrical parts are live.
2. Check and, if necessary reset the precharge pressure, using the following procedure. Ensure that the pressure does not exceed the value specified.
Precharge pressure check
The precharge air pressure for vessels should be 90% of the maximum pressure generated by the pump in the pipework system. e.g: If the max. pressure generated
by the pump in a system is 6 bar, the required pre-charge pressure is 5.4 bar.
Refer to the following table:
Required Pressure
Precharge Pressure
Fig. 6-1 Pump PreCharge Pressure Calculator
Refer to fig 6-2 to verify the precharge pressure:
1. First check that the expansion vessel is totally drained of water, and that the system is switched off and no electrical parts are live. Use the drain valve to drain the vessel.
2. Locate the vessel charging valve (either underneath or adjacent to the plastic cap on top of the vessel, and connect a portable pressure gauge which has a flexible hose and Schrader-type connector to the valve. (The gauge measuring range must be compatible with the expected pressures in your application.)
3. Verify that the pre-charge pressure above the diaphragm corresponds to the 90% criteria in fig 6-1.
4. If necessary, release or add air.
To add air, inflate the diaphragm using a hand or footpump.
5. When the precharge pressure is correct replace the air valve cap and vent cover.
2
3
2
Fig. 6-2 Pre-charging a Vessel
ScubaTANK™ VX2
Iss.2 - Mar 2014
47
48
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
General guidance notes for vessel repair & replacement
• Always ensure that the maximum working pressure and temperature is never exceed.
• During installation ensure adequate drainage to limit potential damage caused by leakage during draining.
• The vessel must be installed and regularly inspected to conform to current legislation by qualified personnel only.
• The appliance must be protected by an appropriate earthing systems or isolated from the system by a dielectric joint.
• The manufacturer shall not be held liable for any personal or material damage caused by the product or to the product if it is installed and/or used improperly or in way that differs from the manufacturer’s specifications.
ELECTRIC SHOCK DANGER
Before beginning to work on the vessel you MUST isolate the Electrical Supply and make sure that it cannot be accidentally reconnected.
It is the installer’s responsibility to perform the connection in compliance with local regulations and all electrical guidelines.
Replacing the diaphragm
To replace the diaphragm refer to fig 6-3.
1. Turn off the ScubaTANK™.
2. Empty the expansion tank.
3. Remove the pre-charging by releasing the air-vent.
Air Vent Cover
Air Vent
Tank
4. Loosen the M8 screws fastening the flange.
5. Remove the flange.
6. Extract the diaphragm and replace it.
Diaphragm
Installing a replacement vessel
1. Turn off the ScubaTANK™ and remove the old vessel
2. Make sure the replacement is in good condition. If the product is damaged do not start on installation.
3. The product must be installed in the same position as the original.
Flange
M8 Washers &
Screws
Fig. 6-3 Pressure Vessel Diaphragm
4. Set the precharge pressure, using the
procedure given earlier in this section on page 47. Ensure that the pressure does
not exceed the value specified in the procedure.
5. Make sure the cap of the valve is fitted tightly after pre-charging and that there is no leakage.
ScubaTANK™ VX2
Iss.2 - Mar 2014
Section 6 Routine Maintenance & Repair
Inlet Solenoid Close Control & Bypass Screw Adjustment
The factory-set closing speed screw on the inlet solenoid valve adjusts the input flow rate and MUST NOT normally be re-adjusted except by a competent engineer following the procedure below. Correct operation MUST be verified before leaving the unit unattended.
ADJUSTING WILL INVALIDATE THE WARRANTY.
The bypass screw is only for temporarily use in the event of an electrical failure.
The closing speed screw alters the operating speed of the solenoid and is used to reduce water-hammer and flow noise.
If the input flow is set higher than the overflow discharge capability, there is a high possibility that the tank will overfill.
The bypass screw permanently opens the valve to temporarily allow tank use in the event of an electrical failure.
If either screws are adjusted, verify correct operation before leaving the unit unattended.
Off
BYPASS
On
CLOSING
SPEED
Reduce
Increase
Fig. 6-4 Inlet Solenoid Valve Control Screws
Opening the Tank
To remove the tank lid:
1. Remove the 4x plastic covers to expose the M6 domed screws securing the lid.
2. Remove the screws to open the lid.
3. Replace the lid, screws and caps before returning the tank to use.
Pump Servicing
The following information is extracted from the manufacturer’s documentation.
Routine maintenance
The pump requires no detailed maintenance except to:
• Periodically verify that the suction grate is clear
• Periodically with the supply power turned off, check the condition of the cables and electrical power and earth connections.
Pump replacement
The electrical pump must never be used outside the limitations described in the technical specifications. Replacement pumps should remain in their supplied original packing until installation.
ScubaTANK™ VX2
Iss.2 - Mar 2014
49
User Guide - ScubaTANK™ VX2 Combined Water Storage & Booster Package
1. Before installation, check the new pump and verify its integrity and that it is the correct type/rating. Contact the supplier if there are any anomalies.
ELECTRIC SHOCK DANGER
Before beginning to work on the pump, you MUST isolate the Electrical Supply and make sure that it cannot be accidentally reconnected.
Wait a further 2 minutes for the internal circuitry to discharge BEFORE opening or working with any electrical connections on the MODULATOR controller.
It is the installer’s responsibility to perform the connection in compliance with local regulations and all electrical guidelines.
2. Locate the 4x plastic screw covers protecting the M6 screws securing the tank lid.
Remove the covers and screws and lift off the tank lid to access the old pump.
3. Disconnect the pump pipework.
4. Referring to the instructions in Section A disconnect the pump electrical cable,
noting the cable colour coding.
5. Insert the replacement pump into the tank and reconnect the pipework.
To avoid damage, do not use excessive force when screwing the pipe to the pump discharge outlet.
6. Feed the pump cable through the watertight glands and make the electrical
connections to the controller as noted in step 4 above, verifying that the earth
connection is securely made
.
7. Fix the power cable to the delivery pipe using suitable strap.
8. Replace the covers on the controller.
9. Test the system, checking rotation direction (see below).
10. When testing is complete, replace the tank lid and screw it down, refitting the plastic caps.
Checking the direction of rotation
If the direction of rotation is reversed due to incorrect connection or controller programming, the pump performance will be significantly lower than the nominal values. To verify a correct connection, proceed as follows:
1. Start the electrical pump before it is submerged. Correct rotation is in a counterclockwise direction as viewed from above.
This operation will be performed dry and MUST NOT last more than a few seconds.
2. With the pump operating, installed and submerged, use a clamp meter to measure the current. If the rotation is reversed, you will see values about double those indicated on the name plate.
3. Correct before using the system.
VASCO Controller Servicing
Maintenance, repair and replacement of the VASCO controllers is contained in the
manufacturer’s guide published in Appendix A of this manual.
50
ScubaTANK™ VX2
Iss.2 - Mar 2014
ScubaTANK™ VX2
Iss.2 - Mar 2014
A
Appendix A
Manufacturer’s Guide -
VASCO
This Section contains a facimile copy of the
Installation, Safety and Configuration instructions provided by supplier of the VASCO Controller series:
All data is subject to change without notice.
51
User Guide -ScubaTANK™ VX2 Combined Water Storage & Booster Package
VASCO User Manual
VASCO PUMP CONTROLLER
Vasco 209, 214, 406, 409, 414, 418, 425, 430
User & Installation Guide
52
Iss 2_11.13
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
ScubaTANK™ VX2
Iss.2 - Mar 2014
Appendix A
Contents
Contents
Safety Information .................................................................................................................2
Introduction ............................................................................................................................3
Basic Operational Information ...............................................................................................3
The VASCO Display .........................................................................................................3
Initial View ...................................................................................................................4
Menu view ...................................................................................................................5
Restoring the Controller Configuration .............................................................................5
Protection and Fault Alarms ..................................................................................................6
Alert Messages and possible causes ...............................................................................6
Troubleshooting VASCO .......................................................................................................8
VASCO Installation, Replacement & Connection Details ......................................................9
Electrical Considerations ..................................................................................................9
Technical Characteristics ..................................................................................................9
Mounting instructions ........................................................................................................10
Electrical and signal connection .......................................................................................11
VASCO serial connection .................................................................................................15
Pressure control ................................................................................................................15
Pressure Vessel ..........................................................................................................15
Sensor installation or replacement ..............................................................................15
Parameter Setting .................................................................................................................16
Accessing the VASCO Parameters ..................................................................................16
Access Passwords ............................................................................................................16
Initial Controller Configuration ..........................................................................................16
Installer Parameters ..........................................................................................................17
Advanced Parameters ......................................................................................................21
Setting Up a Multi-pump COMBO Function ......................................................................25
Master setup ...............................................................................................................25
Slave setup .................................................................................................................26
IMPORTANT SAFETY INFORMATION
Safety Information
BEFORE INSTALLING OR OPERATING ANY CONTROL SWITCH, ENSURE THAT YOU HAVE CAREFULLY READ
AND UNDERSTOOD THIS MANUAL
This manual contains safety, installation and troubleshooting information for the Vasco 209, 214, 409, 414, 415, 425
Controllers current at the time of compilation. Do not throw away this manual after installation. The manufacturer declines all responsibility in the event of accident or damage due to negligence or failure to observe the instructions described in this manual or in conditions that differ from those indicated on the device. Failure to observe and follow the instructions in this manual may result in dangerous and potentially lethal electric shock.
Safety symbols are used in manual are:
Denotes attention to the possibility of the risk of personal injury or damage to the equipment or adjacent property if the information is ignored.
Denotes attention to the possibility of lifethreatening electric shock if the information is ignored.
Hydraulic and electrical installations must be carried out by qualified personnel according to the local safety regulations, standards and legislation.
Disconnect the VASCO from the main power supply before commencing any work. The device must be connected to the main power supply via a switch to ensure provision for complete disconnection before any work is commenced (including visual inspection) on it or the connected load.
For the entire period VASCO is powered, high voltage is present on the output terminals of the inverter whether or not the pump is running. Do not remove the cover and the cable plate for any reason without having first disconnected the device from the main power supply and waiting at least a further
5 minutes.
The VASCO and pumping system must be grounded properly before operation. To eliminate the risk of electric shock or even death, before powering the device after installation or maintenance, it is recommended to retighten all 4 washered cover screws to ensure a maintained ground connection
Avoid any shock or significant impact when handling.
Check any replacement VASCO immediately upon delivery for damage and/or missing parts. If either occurs, immediately notify the supplier. Damages due to transport, incorrect installation, or improper use of the device will null and void the warranty. Tampering or disassembly of any component will automatically void the warranty.
2
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
Iss2_11.13
ScubaTANK™ VX2
Iss.2 - Mar 2014
53
User Guide -ScubaTANK™ VX2 Combined Water Storage & Booster Package
User Guide - VASCO Pump Controller
Introduction
VASCO is a variable frequency drive designed to control and protect pumping systems by varying the output frequency to the pump. VASCO can be applied to both new and existing pumping systems, and provides:
• energy and cost savings.
• simplified installation and an overall lower pumping system cost.
• longer life of the pumping system and relevant components.
• improved reliability.
When connected to a pump, VASCO manages the system operation to maintain a certain constant physical quantity (pressure, differential pressure, flow, temperature, etc.) regardless of the conditions of use. The pump is operated only when needed thus avoiding unnecessary energy consumption. VASCO is able to:
• protect the motor from overload and dry running.
• implement soft start and soft stop to increase the system life and reduce current peaks.
• provide an indication of current consumption, voltage, and power.
• maintain a record of run time and display any errors and/or failures reported by the system.
• control up to two additional pumps at a constant speed (Direct
On Line).
• connect to other VASCO units for combined operation.
To implement this each controller has a Control/Display panel which provides user access to general running information and allows user intervention and parameter modification under password protection.
Fig. 1-1 VASCO Single and
3 Phase Units
If supplied fitted to a pumpset it will have been tested and set to a default initial set of parameters to configure pump characteristics, pressure sensor range, and system characteristics. Without these initial settings it is impossible to run the pump.
Basic Operational Information
The VASCO Display
The display screen on the VASCO is a back-lit LCD displaying 2 rows of 16 digits each. Alarms are indicated by an audible signal
54
Iss 2_11.13
Fig. 1-2 The VASCO Display
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
3
ScubaTANK™ VX2
Iss.2 - Mar 2014
Appendix A
User Guide - User Guide - VASCO Pump Controller
Initial View
When first powering the VASCO, the display shows:
LCD = X.XX
INV = X.XX
Release of display software
Release of inverter software
Various End User messages are displayed. Increment to the next one by pushing the Scroll buttons:
The First Row of the display gives the VASCO/Pump status as follows:
• Inv: ON XXX.X Hz VASCO is powered and is powering the motor showing its frequency.
• Inv: ON Mot: OFF VASCO is powered but motor is not running (i.e. motor/pump was stopped due to minimum frequency being reached).
• Inv: OFF Mot: OFF VASCO is not powered.
If the Combo function is activated (e.g. Duty/Standby mode), the VASCO address is placed close to the word “Inv”.
The Second Row of the display provided the following information:
Inv: ON/OFF Mot: ON/OFF p_m = XX.X [bar]
Inv: ON/OFF Mot: ON/OFF f = XXX [Hz]
Inv: ON/OFF Mot: ON/OFF
V = X.XX [V] I= XX.X [A]
p_m is the value read by the pressure transducer.
By pressing ENTER the pressure set value is displayed. By keeping ENTER pressed for more than 5 seconds, it is possible to modify the set pressure in real time.
f is the supply frequency to the motor.
By pressing ENTER you can change the f value manually (the word “set” is displayed). Press ENTER again to exit parameter setting (the word “set” disappears).
V is the voltage supplied to the motor.
This value is displayed only if motor is OFF.
If the motor is ON, a value I equal to the absorbed motor current is displayed.
Inv: ON/OFF Mot: ON/OFF cosphi = XXX
cosphi index means the phase angle phi between the voltage and current absorbed by the motor.
Inv: ON/OFF Mot: ON/OFF
P = XXXXX [W]
P is the power in Watts supplied to the pump.
Inv: ON/OFF Mot: ON/OFF
STATUS: NORMAL
Inverter Life xxxxx h : xx m
Motor Life xxxxx h : xx m
%f 25 50 75 100
%h XX XX XX XX
XXXXXXXXXXXXXXX
XXXXXXX h : XX m
Menù
ENT to access
NORMAL status means no alarms.
If an alarm occurs, a message blinks on the display and an audible signal is activated.
Pressing ENTER accesses:
VASCO hours run, PUMP hours run, Consumption statistics,
Alarm list.
PUMP hours refer to pump powered time.
To return to previous views, press ENTER.
4
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
ScubaTANK™ VX2
Iss.2 - Mar 2014
Iss2_11.13
55
User Guide -ScubaTANK™ VX2 Combined Water Storage & Booster Package
User Guide - VASCO Pump Controller
Menu view
Pressing ENTER when you are in initial display [MENU / ENT] will display the following sub MENUs to allow access to the installer and advanced options, (refer to page 16 for further information).
You should only access and adjust these parameters if you are trained to do so.
Improper setting of these advanced parameters could compromise the integrity and the life of the controller and the pump.
MENU’
Install. param.
MENU’
Advanced. param.
MENU’
Retrive init. set
MENU’
Change init. set.
Installer password required to enter level 1 (default 001)
Advanced password required to enter level 2 (default 002)
Installer password required to enter level 1 (default 001)
Here it is possible to return to original set parameters.
Advanced password required to enter level 2 (default 002)
To exit the MENU level and return to initial display, press the STOP button.
Restoring the Controller Configuration
Your pumpset will have been tested and set to a default initial set of parameters to configure pump characteristics, pressure sensor range, and system characteristics. Without these initial settings it is impossible to run the pump.
If required, the initial settings can be restored using the 1st level password as described above.
A full description of the parameters and their allowable settings can be found in the Advanced Parameter Section of this manual on page 16.
56
Iss 2_11.13
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
5
ScubaTANK™ VX2
Iss.2 - Mar 2014
Appendix A
User Guide - User Guide - VASCO Pump Controller
Protection and Fault Alarms
Whenever a fault is detected, a flashing message is displayed on the Controller display together with an audible alarm.
The STATUS message in the initial view will display the fault.
• Pressing the STOP button will attempt to reset the alert. If the reset is unsuccessful the message is redisplayed and the alarm re-sounds.
• If dry-running occurs for over 2 seconds, the Controller will stop the pump. It will then attempt to re-run the pump at 10, 20, 40, 80, 160 minute intervals and then permanently stop it.
If dry-running occurs, the Controller will try to restart the pump automatically.
ENSURE YOU SWITCH OFF THE POWER BEFORE ATTEMPTING MAINTENANCE.
• The Controller will stop the pump if the motor current is higher than the preset motor current for an extended time.
By pressing the START button it is possible to run the pump again.
• The Controller will stop the pump if the input voltage goes higher than the preset voltage for an extended time.
By pressing the START button it is possible to run the pump again.
• The Controller will stop the pump if the input voltage goes lower than the preset voltage for an extended time.
By pressing the START button it is possible to run the pump again.
A full list of messages, together with possible causes and solutions can be found in this manual in the Troubleshooting Section on page 8.
Alert Messages and possible causes
ALARM MESSAGE
OVERCURRENT MOT.
UNDER VOLTAGE
OVER VOLTAGE
OVER TEMP. INV.
NO LOAD
SENSOR FAULT
ALARM DESCRIPTION POSSIBILE SOLUTIONS
Motor overload. The input current of the motor is higher than the rated motor current setting parameter.
Motor voltage drop caused by the inverter causes the motor input current to be higher than the rated current.
Contact the manufacturer to check if the motor is capable of accepting this current.
Supply voltage too low.
Make sure that the motor current setting parameter is higher than the rated current.
Check for other possible causes of over current.
Check possible causes of undervoltage.
Supply voltage too high.
Inverter over temperature.
No load.
Sensor error.
Check possible causes of overvoltage.
Make sure than ambient temperature is less than 40 °C (104 °F).
Check the cooling fan is working properly and providing proper cooling.
Reduce the PWM value (Advanced Parameter
Menu).
Check if motor is properly connected to the
VASCO terminals.
Check the transducer.
Check the wiring from the transducer.
6
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
ScubaTANK™ VX2
Iss.2 - Mar 2014
Iss2_11.13
57
User Guide -ScubaTANK™ VX2 Combined Water Storage & Booster Package
User Guide - VASCO Pump Controller
NO WATER
(DRY RUN COSPHI)
MAX.VALUE ALARM
MIN.VALUE ALARM
IGBT TRIP ALARM
NO COMMUNICATION
ADDRESS ERROR
KEYBOARD FAULT
DIGITAL INPUT
ALARM SLAVE XX
Motor cosphi is lower than the set value of the dry running cosphi.
Measured value has reached the lowest value accepted by the system.
Check if the pump is primed.
Check the set value of dry running cosphi. Dry
running cosphi is approximately 60% of the rated cosphi (at rated frequency) listed on the motor plate.
If pump’s cosphi is lower than the set dryrunning cosphi for at least 2 seconds, the controller stops the pump. It then tries to run the pump again at 10, 20, 40, 80, 160 minute intervals and then the pump is stopped.
WARNING: If dry running protection occurs, the controller will try to start the pump automatically. Be sure to switch off the power
source to before performing any maintenance.
Measured value has reached the maximum value accepted by the system.
Check possible causes of max value.
Check max value parameter setting.
Check possible causes of min value (e.g.
broken pipe, open pressure relief valve, etc.).
Check min alarm value parameter setting.
The current drawn by the load exceeds the capacity of the fitted controller.
The controller is still able to continue to power the load for 10 minutes with an output current of 101% of nominal and for 1 minute with an output current of
110% of nominal.
Increase the ramp-up time.
Make sure that the load current is at least 10% below the controller nominal current.
Check the voltage drop along the supply cable to the motor.
Communication between Master and
Slave(s) has been interrupted.
Same address as other Controllers in the group.
A button on the keyboard has been pressed for more than 150 seconds.
Digital input opened/closed.
Check the wiring connections.
Make sure the Master is not in the Menu level.
If so, exit from the level.
In STATUS on the Slave (where the alarm is displayed) try to reset the alarm by pushing
STOP button.
The address of each controller needs to be set differently.
Make sure buttons are not depressed.
Call manufacturer’s service assistance.
Check the input digital configuration (Located in
Installer Parameters menu.)
Slave XX error detected by Master Check the status of the Slave.
58
Iss 2_11.13
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
7
ScubaTANK™ VX2
Iss.2 - Mar 2014
Appendix A
User Guide - User Guide - VASCO Pump Controller
Troubleshooting VASCO
Fault Possible Cause / Solution
LCD does not switch on after powering the VASCO
Power line of VASCO is interrupted by the differential protection contactor
When performing the Offset operation of the pressure device, a SENS.PRESS.OFF alarm occurs
Check the connecting flat cable between the LCD board (attached to the cover) and the control board.
Check the fuses.
Check that the power cables are properly connected.
Check the EMC filter leakage current to ground.
Following a rapid off/on the power supply, the differential contactor can interrupt the power. After turning off the VASCO it is recommended to wait at least 1 minute before restarting.
Check that the sensor cable is properly connected to the sensor device and to the VASCO.
Make sure that the sensor and its cable are not damaged.
Frequency and pressure oscillation on constant pressure control mode
DOL pump stops and starts continuously
Measured pressure drops too much before VASCO starts the pump
Check that the operating range of pressure sensor is of 4 -20mA type and the value of 15V is within the voltage feed range of the sensor
Check that the pressure vessel and its air pressure is correctly set. It may be necessary to increase the tank volume or reduce the precharge pressure.
Check the Ki & Kp parameters (Installer Parameters menu). At first, try increasing the Ki value. If there is still oscillation, try reducing the last digit of the Kp value by one.
Increase the delta start pressure (Installer Parameters menu)
Check to see if the water tank and it’s air pressure are correctly set. It may be necessary to increase the tank volume or reduce the precharge pressure.
Decrease the delta start pressure (Installer Parameters menu)
Check to see if the water tank and it’s air pressure are correctly set. It may be necessary to increase the tank volume or reduce the precharge pressure.
Modify the value of the Ki & Kp parameters (Installer Parameters menu). At first, try reducing the Ki value. If the start is still incorrect try increasing the last digit of the Kp value by one.
8
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
ScubaTANK™ VX2
Iss.2 - Mar 2014
Iss2_11.13
59
User Guide -ScubaTANK™ VX2 Combined Water Storage & Booster Package
User Guide - VASCO Pump Controller
VASCO Installation, Replacement & Connection
Details
Electrical Considerations
Protection
The protections required upstream of each VASCO depends on the type of installation and local regulations. We recommend to use overload protection with the characteristic curve of type C and type B circuit breaker, sensitive to both AC and DC current.
Electromagnetic compliance
To ensure electromagnetic compatibility (EMC) of the system, it is necessary to apply the following measures:
• Always ensure that the device connected to ground.
• Use shielded signal cables connecting the screen at one end only.
• Keep the motor cable as short as possible (<1 m / <3 ft). For longer lengths, it is recommended to use shielded cables, connecting the screen at both ends.
• Separate signal, motor, and power supply cables.
VASCO will periodically refresh the display to maintain the screen information in the event of electromagnetic corruption.
Installation with long motor cables
With long motor cables it’s recommended to decrease the commutation frequency from 10 kHz (default) to 2.5 kHz
(advanced parameters). This reduces the probability of voltage spikes in the motor windings which may damage the insulation.
Fig. 1-3 Commutation Frequency
60
Technical Characteristics
Model
Vin+/-15%
(V AC)
209
214
406
230 x 1 phase
Vout max
(V)
1 x Vin
3 x Vin
1 x Vin
3 x Vin
3 x Vin
Line Current max
(A)
15
20
10
Motor Current max
(A)
9
7
9
11
6
Typical P2 Motor
(KW
1.1
1.5
1.1
3
1.5
HP)
2
1.5
4
2.2
3
409
414
418
425
430
230 x 1 phase
380 - 460 x 3 phase
380 - 460 x 3 phase
380 - 460 x 3 phase
380 - 460 x 3 phase
380 - 460 x 3 phase
380 - 460 x 3 phase
3 x Vin
3 x Vin
3 x Vin
3 x Vin
3 x Vin
13.5
16
21
31
35
9
14
18
25
30
4
5.5
7.5
11
15
5.5
7.5
10
15
20
Power frequency: 50-60Hz, Max amb. temp at nom. current:
40°C (104 °F )
Max altitude at nom. current:
1000m
Protection: IP55 (NEMA 4, Serial connect: RS485, PWM configurable: 2.5, 4, 6, 8, 10 kHz.
Iss 2_11.13
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
9
ScubaTANK™ VX2
Iss.2 - Mar 2014
Appendix A
User Guide - User Guide - VASCO Pump Controller
Mounting instructions
The VASCO is installed directly on the fan cover of the motor and is cooled by the motor fan. A supplied Motor
Mounting Kit allows a solid coupling of the two units.
VASCO 209, 214, 406, 409
Motor Mounting Kit
Qty 4 x Rods
Qty 4 x M5 nuts
Qty 4 x Hooks
Qty 1 x Cooling ring
Use the cooling ring for best cooling of VASCO during operation.
Warning: when using the cooling ring, the cooling air of the motor is slightly warmer than without the
VASCO; if the resulting motor temperature exceeds the indicated maximum allowable value, remove the cooling ring, leaving the VASCO to be cooled by itself.
If possible, coupling hooks should be attached to the motor shield instead of the cooling fan cover.
Fig. 1-4 VASCO 209 Motor Mounting
VASCO 414,418,425,430
Motor Mounting Kit
Qty 4 x M5 screws
Qty 4 x Clamps
Qty 1 x Centre pin
Fig. 1-5 VASCO 414,418,425 Motor Mounting
10
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
ScubaTANK™ VX2
Iss.2 - Mar 2014
Iss2_11.13
61
User Guide -ScubaTANK™ VX2 Combined Water Storage & Booster Package
User Guide - VASCO Pump Controller
Electrical and signal connection
Power Connection to Model VASCO 209, 214
Power Board
Control Board
Power Supply In
LINE: L1, earth, L2
It is recommended to use cable lugs
Aux Fan Connection
FAN: F1, F2
230VAC
(Wall mounting kit)
Output to Motor
1 Phase Motor:
earth, U (common), V (running)
3 Phase Motor:
earth, U, V, W
It is recommended to use cable lugs
For Signal connections to the Control Board refer to fig 1-9
For Combo (multi-pump) RS485 connection to other VASCOs refer to fig 1-10
Recommended Line and Motor Cable Stripping
Fig. 1-6 VASCO 209, 214 Power Board Connection
62
Iss 2_11.13
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
11
ScubaTANK™ VX2
Iss.2 - Mar 2014
Appendix A
User Guide - User Guide - VASCO Pump Controller
Power & Signal Connection to three phase model VASCO 406, 409
Power Board
Control Board
Power Supply In
LINE
Earth, L1, L2, L3
It is recommended to use cable lugs
Output to Motor
MOTOR U, V, W, Earth,
It is recommended to use cable lugs
Aux Fan Connection
0
VE
, +
VE
12VDC
Warning: Respect
Polarity
For Signal connections to the Control Board refer to fig 1-9
For Combo (multi-pump) RS485 connection to other VASCOs refer to fig 1-10
Recommended Line and Motor Cable Stripping
50
5
Fig. 1-7 VASCO 406, 409 Power Board Connection
12
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
ScubaTANK™ VX2
Iss.2 - Mar 2014
Iss2_11.13
63
User Guide -ScubaTANK™ VX2 Combined Water Storage & Booster Package
User Guide - VASCO Pump Controller
Power Connection to three phase model VASCO, 414, 415, 425, 430
Control Board
Power Board
Power Supply In Output to Motor earth, LINE: L1, L2, L3
It is recommended to use cable lugs
MOTOR: U, V, W, earth,
It is recommended to use cable lugs
Aux Fan Connection
VENT:
-, +
12VDC
Warning: Respect Polarity
For Signal connections to the Control Board refer to fig 1-9
For Combo (multi-pump) RS485 connection to other VASCOs refer to fig 1-10
Recommended Line and Motor Cable Stripping
64
Iss 2_11.13
Fig. 1-8 VASCO 414, 418, 425, 430 Power Board Connection
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
13
ScubaTANK™ VX2
Iss.2 - Mar 2014
Signal (Control Board) Connections
Appendix A
User Guide - User Guide - VASCO Pump Controller
•
•
RS485
• S+
S-
G
It is recommended to respect the polarity linking more
VASCOs in series.
Digital Outputs
Motor run signal:
• NO1, COM1: closed contact with motor running.
• NC1,COM1: closed contact with motor stopped.
Alarm signal
• NO2,COM2: opened contact without alarm.
• NC2,COM2: closed contact without alarm.
DOL1 pump relay:
• NO3,COM3: closed contact with DOL1 running.
• NC3,COM3: opened contact with DOL1 running.
DOL2 pump relay:
• NO4,COM4: closed contact with DOL2 running.
• NC4,COM4: opened contact with DOL2 running.
Relays are no voltage contacts.
Max. voltage to the contacts is 250V with max current of 5A.
• IN1
• IN2
• IN3
• IN4
• 0V
Digital Inputs
We recommend using only no voltage contacts. Opening or closing the digital contacts (depending on software configuration set (see inst. parameters) you can start or stop the motor.
Analog Inputs (10 or 15 Vdc)
• AN1: 4-20 mA
• AN2: 4-20 mA
• AN3: 4-20 mA / 0 - 10 Vdc
(settable by jumper C.C.)
• AN4: 4-20 mA / 0 - 10 Vdc
(settable by C.C.)
Fig. 1-9 VASCO Control Board Connection
14
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
ScubaTANK™ VX2
Iss.2 - Mar 2014
Iss2_11.13
65
User Guide -ScubaTANK™ VX2 Combined Water Storage & Booster Package
User Guide - VASCO Pump Controller
VASCO serial connection
For Combo (multi-pump) use, VASCO’s communication is made through a protocol using the RS485 port. Each VASCO must be connected to each other by using a tripolar cable (0,5 mm2) wired on
S+,S-,G pins on the control board, see fig 1-9.
Fig. 1-10 RS485 Serial Connection
Pressure control
Vasco controls pump speed to maintain a constant pressure independent of water demand using a sensor,
(see fig 1-11)
Pressure Vessel
66
Check
Valve
Valve
Pressure Vessel
Installation of a pressure tank in the hydraulic system is recommended to compensate leakage of water in the system (or during minimum water demand) and to avoid continuous start/stop cycling of the pump. Selecting the proper volume and pre-charge pressure of the tank is very important; smaller tank volumes will not compensate adequately for minimum water usage or leakage, while larger volumes make it more difficult for VASCO to control the pressure evenly.
Recommended tank volume is equal to the 10% of the maximum water flow of the system (expressed in volume unit/min) e.g. Flow = 50litres/min, Tank = 5 Litres
Pre-charge pressure of the pressure tank should be at least 80% than the set-pressure of the system. e.g. Set system pressure = 4 bar, Precharge pressure = 3.2 bar.
Sensor installation or replacement
To use the Combo (multi-pump) function in a system incorporating several interconnected VASCOs an individual pressure sensor must be connected to each VASCO. The value of the set pressure is communicated to the slaves via the serial port.
VASCO requires a pressure sensor with a linear output signal within the range 4 – 20 mA. The pressure transducer can be powered by any range of DC Voltage which includes the value 15VDC.
A 2nd pressure sensor can be connected to the VASCO:
• to prevent the shutdown of the system due to single pressure sensor failure.
• to action constant differential pressure (AN1 - AN2)
• switch pressure sensor by closing digital input 1N2
It will be necessary to set the pressure sensor characteristics in the initial configuration, or in the installer menu.
Referring fig 1-9, connect the sensor wires to the analogue input terminals as below:
Iss 2_11.13
Pump
Pressure
Sensor
Fig. 1-11 Pressure Control
Valve
Primary
Sensor
0V GND signal (if available)
AN1 signal 4-20mA (-)
+15 Power supply 15Vdc (+)
Secondary
Sensor
(if fitted)
0V GND signal (if available)
AN2 signal 4-20mA (-)
+15 Power supply 15Vdc (+)
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
15
ScubaTANK™ VX2
Iss.2 - Mar 2014
Appendix A
User Guide - User Guide - VASCO Pump Controller
Parameter Setting
Accessing the VASCO Parameters
Although the VASCO software is extremely simple to use, it allows a wide variety of parameters to be set for ideal system configuration. A password is required to gain access to the set up parameters. Without a password it is impossible to set up and/or modify any parameters although they can however still be displayed.
You should only adjust these parameters if you are trained to do so.
Improper setting of these advanced parameters could compromise the integrity and the life of the controller and the pump.
Access Passwords
There are two levels of access to Parameter setting permitted, both requiring passwords:
• Installer level - Default password 001
• Advanced level - Default password 002
A different password can be set up if required once the menu is accessed.
Initial Controller Configuration
The pumpset will have been tested and set to a default initial set of parameters to configure pump characteristics, pressure sensor range, and system characteristics. Without these initial settings it is impossible to run the pump.
If required, the initial setting procedure can be repeated by accessing the controller using the 2rd level password.
This will allow alteration of the parameters.
A brief description of the initial configuration parameters and their allowable ranges is as follows:
Default Description Parameter
Language
XXXXXX
Unit bar/psi
Motor type singlephase/threephase
XXXXXXX bar threephase
End user communication language.
Pressure unit.
Rated motor Amp
I + XX.X [A]
XX
Type of motor connected.
(VASCO 209, 214)
Rated current of the motor on its nameplate plus 10%.
Note: The voltage drop caused by the inverter leads to higher input current than nominal. Make sure motor is capable of accepting increased current.
Rated motor frequency f + XX.X [Hz]
50 Rated frequency of the motor on its nameplate.
F.s press.sensor
20mA = XX.X [bar]
Sensor test
Press ENT
Max alarm press p = XX.X [bar]
Control mode: Constant pressure
16
Maximum pressure of pressure transducer. Set the upper value of the pressure transducer i.e. the 20mA output signal level.
(i.e. 0 – 10 bars transducer range) 10 bars = 20 mA
If the transducer is not connected or connected improperly, the signal SENS. PRESS OFF is displayed when pressing ENTER.
10
Maximum pressure allowed in the system. If the pressure goes over this value, an alarm occurs and the pump is stopped. Pump is automatically restarted if the pressure goes below the maximum value for a at least 5 seconds.
16
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
ScubaTANK™ VX2
Iss.2 - Mar 2014
Iss2_11.13
67
User Guide -ScubaTANK™ VX2 Combined Water Storage & Booster Package
Motor test
START / STOP
Rotation sense
---
> / <
---
Set pressure p = XX.X [bar]
Autorestart
ON/OFF
INITIAL SETUP
COMPLETED
User Guide - VASCO Pump Controller
---
3
>
OFF
Press START/STOP to run a test at rated frequency
Warning: This will start the system. Make sure it is safe to run without damage.
When testing the system, if the motor runs in reverse, it is possible to reverse the rotation via software without physically changing wires at the terminals.
The pressure value to be kept constant.
If ON is selected, VASCO automatically returns to its normal status after a voltage failure. i.e. if it was powering the pump before, it resumes powering the pump.
THIS MAY BE CONSIDERED HAZARDOUS
Once the Setting procedure is completed you will get this indication on the display and the setting parameters are stored.
These parameters can be individually changed later in either the
INSTALLER Parameters menu or ADVANCED Parameters menu.
Installer Parameters
Many of the Installer Parameters are set during the Initial Configuration (page 16).
However, through the Installer Parameters menu, it is possible to change the set parameters or set others in order to perfect the calibration of VASCO to the pumping system.
Parameter Description
Control Mode
Constant value.
Fix Speed
Const.value.2val
Fix speed 2 val
External speed
Mode of control:
Constant value:
VASCO changes the speed of pump to keep the set value constant, independent of water demand.
Fixed frequency:
VASCO feeds the pump a set frequency, so the speed of motor is kept constant.
Constant pressure control with two values:
the two values are selected by opening or closing the digital input IN2.
Fixed frequency control with two values:
the two values to be selected by opening or closing the digital input IN2.
External speed:
control motor frequency by using analogue control signal AN4.
68
Iss 2_11.13
Unit bar/psi
F.scale.sensor
p = XX.X [bar]
Min value sensor
20mA = XX.X [°C]
bar
16
0
Pressure unit
Sensor full scale value
Sensor minimum value
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
17
ScubaTANK™ VX2
Iss.2 - Mar 2014
Appendix A
User Guide - User Guide - VASCO Pump Controller
Parameter Description
Max alarm value p = XX.X [bar]
Min alarm value p = XX.X [bar]
Ext set enabling
ON/OFF
Set value p = XX.X [bar]
Compensation p = XX.X [bar]
Set value 2 p = XX.X [bar]
Compensation2 p = XX.X [bar]
Set value update.
t = XX [s]
Operating freq.
f = xxx [Hz]
Operating freq. 2 f = xxx [Hz]
Freq min control fmin = xxx [Hz]
Stop delay
t = XX [s]
Control Ramp t = XX [s]
10
0
OFF
Maximum value allowed in the system. If the monitored value goes over this value, an alarm occurs and the pump is stopped.
The pump is automatically restarted if the monitored value goes below the maximum value for at least 5 seconds.
Minimum pressure allowed in the system. If the monitored value goes lower than this value, an alarm occurs and the pump is stopped.
The pump is automatically restarted if the monitored value goes higher than the minimum value for at least 5 seconds.
This parameter is particularly useful in the event a system pipe breaks. It is suggested to set a value higher than 0.
This enables the changing of Set Value via the analogue input AN3
3
0
3
0
5
The set value to be kept constant.
Value compensation at the maximum frequency for each pump. See fig 1-12 on page 21. You can reverse the sign (+/-) by pressing the green button.
The pressure value to be kept constant.
Value compensation at the maximum frequency for each pump. See fig 1-12 on page 21. You can reverse the sign (+/-) by pressing the green button.
Time to update the set value for compensation.
50
50
50
Set the frequency (speed) value to feed the pump.
Set the frequency value (or the speed) to feed the pump.
Minimum frequency at which the pump must stop.
5
20
Delay after which the pump will stop once the minimum frequency is reached (f min Q=0)
Ramp time from freq min control to motor freq min.
If, during this time, the p checked goes below the
(set value - delta control), VASCO powers the motor again; otherwise, VASCO will stop the pump.
See fig 1-13 on page 21.
18
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
ScubaTANK™ VX2
Iss.2 - Mar 2014
Iss2_11.13
69
User Guide -ScubaTANK™ VX2 Combined Water Storage & Booster Package
User Guide - VASCO Pump Controller
Parameter Description
70
Iss 2_11.13
Delta control p = XX.X [bar]
0.1
This value represents the value drop below the set value required to restart the pump during the control ramp period.
Delta start p = XX.X [bar]
0.5
This value represents the value drop below the set value required to start the pump from stopped.
Delta stop p = XX.X [bar]
Ki
XXX
Kp
XXX
0.5
This value is the increase of value above the value set which must be passed so that there is a forced shutdown of the pump.
Kp and Ki parameters allow the dynamic control of system by VASCO.
Set values (Ki=50, Kp=005) are usually enough to get a valid dynamic control.
If the set pressure do not provide a valid control, proceed as follows:
Increase or reduce Ki while keeping Kpconstant; if the problem persists, increase Kp value and increase or reduce the Ki value again till a good dynamic control is reached.
Pump DOL 1
ON/OFF
OFF
Function to activate (ON) the second auxiliary pump
DOL 1 (Direct On Line pump).
Pump DOL 2
ON/OFF
OFF
Function to activate (ON) the second auxiliary pump
DOL 2 (Direct On Line pump).
Alternance
ON/OFF
Start delay AUX t = XX [s]
COMBO
ON/OFF
PI control
Direct/Reverse
Rotation sense
---> / <---
Dry run cosphi cosphi = X.XX
OFF
1
OFF
Direct
--->
0.65
Function to allow alternating starting priority between the DOL pumps in order to allow equality of use.
Delay time for the DOL pumps start after the variable speed pump has reached the maximum speed and the pressure value has fallen below the set pressure (Delta start pressure).
Enable multiple VASCOs to work in parallel.
e.g. duty/standby /assist modes.Theoretically up to
8 VASCO units can be connected in parallel.
Communication is RS485 by a private protocol.
Direct: Increasing the measured pressure, VASCO decreases motor frequency.
Inverse: Increasing the measured pressure, VASCO increase motor frequency.
When testing the system, if the motor runs in reverse, it is possible to reverse the rotation via software without physically changing wires at the terminals.
If the pump goes into dry running, the cosphi reaches its lowest level. To set this value, contact the pump Manufacturer.
Alternatively test by closing the suction and then checking the value on the VASCO display. A value can then be set by assuming a dry cosphi equivalent to 60% of the rated cosphi specified by the manufacturer.
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
19
ScubaTANK™ VX2
Iss.2 - Mar 2014
Appendix A
User Guide - User Guide - VASCO Pump Controller
Parameter Description
Restarts delay t = XX [min]
Digital input 1
N.O. / N.C
Digital input 2
N.O. / N.C
.
.
Digital input 3
N.O. / N.C.
Digital input 4
N.O. / N.C
.
Dig.In2/3 delay t = xx [s] .
Change PASSWORD1
ENT
10
N.O.
N.O.
N.O.
N.O.
1
The restart delay after a dry running alarm.
At each attempt (max 5) the restart delay will be doubled
By selecting N.A. (normally open) the motor runs if the digital input 1 is open, and stops if the digital input 1 is closed.
By selecting N.C. (normally closed) the motor runs if the digital input 1 is closed, and stops if the digital input 1 is opened.
By selecting N.A. (normally open) the motor runs if the digital input 2 is open, and stops if the digital input 2 is closed.
By selecting N.C. (normally closed) the motor runs if the digital input 2 is closed, and stops if the digital input 2 is opened.
Vasco 209, 214, 414, 418, 425 Only
By selecting N.A. (normally open) the motor runs if the digital input 3 is open, and stops if the digital input 3 is closed.
By selecting N.C. (normally closed) the motor runs if the digital input 3 is closed, and stops if the digital input 3 is opened.
Vasco 209, 214, 414, 418, 425 Only
By selecting N.A. (normally open) the motor runs if the digital input 4 is open, and stops if the digital input 4 is closed.
By selecting N.C. (normally closed) the motor runs if the digital input 4 is closed, and stops if the digital input 4 is opened.
Digital input IN2 and IN3 delay.
Digital input IN1 and IN4 have a 1 second fixed delay.
Pressing ENTER allows the installer level password
(1st level) (default 001) to be changed.
20
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
ScubaTANK™ VX2
Iss.2 - Mar 2014
Iss2_11.13
71
User Guide -ScubaTANK™ VX2 Combined Water Storage & Booster Package
User Guide - VASCO Pump Controller
To ensure proper operation of pressure control is recommended to place the sensor near the pump.
To compensate the pressure loss in the pipes (proportional to flow) it is possible to vary the pressure set in a linear relation with respect to frequency.
Perform the following test to verify the correct value of compensation:
1. Install another pressure gauge away from the pressure sensor. Open the valve completely and read the gauge.
2. Set the value of compensation to equal to the difference of the values from the two gauges.
For a group of pumps, the pressure compensation to be applied to each pump is equal to the total pressure compensation (when all the pumps are running at full speed) divided by the number of pumps in the group.
Fig. 1-12 Compensation Calculation
Fig. 1-13 Ramp Time Calculation
72
Advanced Parameters
All the advanced parameters, due to their importance, are already set during initial setup (see page 16), however it is always possible to modify individual parameters or modify the Advanced password from default 002.
Iss 2_11.13
Parameter
Rated motor Volt.
V = XXX [V]
Voltage boost
V = XX [%]
Default
Vasco 209,214
230 or 400
Vasco 409,
414,418,425
400
1%
Description
Motor rated voltage (as shown on the motor plate)
Average voltage drop due to the inverter is between 20V and 30Vrms based on load condition.
e.g. when the input voltage is 230V the average VASCO output voltage will be 200/210V.
This sets a voltage increase during the start up of the motor.
Warning: An excessive value can seriously damage the motor. Contact the manufacturer for information.
If a single-phase motor is used, a value of 1% is suggested to increase the starting torque.
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
21
ScubaTANK™ VX2
Iss.2 - Mar 2014
Parameter
Rated motor Amp.
I = XX.X [A]
Rated motor freq f = XXX [Hz]
Max motor freq.
f = XXX [Hz]
Min motor freq. f = XXX [Hz]
Ramp up time t = XX [sec]
Ramp down time t = XX [sec]
Ramp f min mot.
t = XX [sec]
PWM f = XX kHz]
V/f lin. --> quad.
XXX %
Autorestart
ON/OFF
Appendix A
User Guide - User Guide - VASCO Pump Controller
Default
XX
50
50
30
4
4
1.5
8
85%
OFF
Description
Rated current of the motor (as shown on the motor plate) increased by 10%.
The voltage drop caused by the inverter leads to higher input current than nominal. Make sure motor is capable of accepting increased current.
Rated frequency of the motor from its nameplate.
Maximum frequency of the motor.
Note: Reducing the maximum frequency of the motor, will also reduce the maximum current.
Minimum frequency of the motor.
Note: It is not advisable to set minimum frequency lower than 30 Hz in order to protect the integrity of the thrust bearings.
Ramp-up time to reach the speed required to achieve the set pressure (or speed value).
Refer to fig 1-14 on page 24.
Longer times delay the system reaching the preset value but better protect system components.
Excessively long ramp-up times can create difficulties in setup, and can also cause false overload alarms.
Ramp-down time to reach zero speed.
Refer to fig 1-14 on page 24.
Longer times keep the system pressurised, while still protecting the system components.
Excessively long ramp-down times can create difficulties in setup. Excessively short ramp-down times can cause false overload alarms.
Time to reach the minimum frequency (speed) of the motor and vice versa.
Refer to fig 1-14 on page 24.
Carrier frequency (switching frequency).
Choose PWM in the range of 2.5, 4, 8, 10 kHz.
Higher values give a more sinusoidal wave with fewer losses. Refer to fig 1-15 on page 24.
If long cables are used (>20 m / >76 ft), it is recommended to install an inductive filter between the controller and the motor (available upon request) and to set the value of PWM to 2.5 kHz. This reduces the risk of voltage spikes, which can damage motor and cable insulation.
This parameter allows you to change the V/f characteristic with which VASCO feeds the pump. The linear
characteristic corresponds to constant torque with variable speed. The quadratic characteristic is normally used with centrifugal pumps. The selection of torque characteristic should be done to ensure a smooth operation, a reduction of energy consumption and a lower level of heat and
acoustic noise. Refer to fig 1-15 on page 24.
If ON is selected, VASCO automatically returns to its normal status after a voltage failure. i.e. if it was powering the pump before, it resumes powering the pump.
THIS MAY BE CONSIDERED HAZARDOUS
22
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
ScubaTANK™ VX2
Iss.2 - Mar 2014
Iss2_11.13
73
74
Iss 2_11.13
User Guide -ScubaTANK™ VX2 Combined Water Storage & Booster Package
User Guide - VASCO Pump Controller
Parameter
Rated motor Amp.
I = XX.X [A]
Rated motor freq f = XXX [Hz]
Max motor freq.
f = XXX [Hz]
Min motor freq. f = XXX [Hz]
Ramp up time t = XX [sec]
Ramp down time t = XX [sec]
Ramp f min mot.
t = XX [sec]
PWM f = XX kHz]
V/f lin. --> quad.
XXX %
Autorestart
ON/OFF
Default
XX
50
50
30
4
4
1.5
8
85%
OFF
Description
Rated current of the motor (as shown on the motor plate) increased by 10%.
The voltage drop caused by the inverter leads to higher input current than nominal. Make sure motor is capable of accepting increased current.
Rated frequency of the motor from its nameplate.
Maximum frequency of the motor.
Note: Reducing the maximum frequency of the motor, will also reduce the maximum current.
Minimum frequency of the motor.
Note: It is not advisable to set minimum frequency lower than 30 Hz in order to protect the integrity of the thrust bearings.
Ramp-up time to reach the speed required to achieve the set pressure (or speed value).
Refer to fig 1-14 on page 24.
Longer times delay the system reaching the preset value but better protect system components.
Excessively long ramp-up times can create difficulties in setup, and can also cause false overload alarms.
Ramp-down time to reach zero speed.
Refer to fig 1-14 on page 24.
Longer times keep the system pressurised, while still protecting the system components.
Excessively long ramp-down times can create difficulties in setup. Excessively short ramp-down times can cause false overload alarms.
Time to reach the minimum frequency (speed) of the motor and vice versa.
Refer to fig 1-14 on page 24.
Carrier frequency (switching frequency).
Choose PWM in the range of 2.5, 4, 8, 10 kHz.
Higher values give a more sinusoidal wave with fewer losses. Refer to fig 1-15 on page 24.
If long cables are used (>20 m / >76 ft), it is recommended to install an inductive filter between the controller and the motor (available upon request) and to set the value of PWM to 2.5 kHz. This reduces the risk of voltage spikes, which can damage motor and cable insulation.
This parameter allows you to change the V/f characteristic with which VASCO feeds the pump. The linear
characteristic corresponds to constant torque with variable speed. The quadratic characteristic is normally used with centrifugal pumps. The selection of torque characteristic should be done to ensure a smooth operation, a reduction of energy consumption and a lower level of heat and
acoustic noise. Refer to fig 1-15 on page 24.
If ON is selected, VASCO automatically returns to its normal status after a voltage failure. i.e. if it was powering the pump before, it resumes powering the pump.
THIS MAY BE CONSIDERED HAZARDOUS
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
23
ScubaTANK™ VX2
Iss.2 - Mar 2014
Appendix A
User Guide - User Guide - VASCO Pump Controller
Parameter
Periodic Autorun t + xx[h]
AN1,AN2 function
ON/OFF
Offset input 1 x = XX.X[%]
Offset input 2 x = XX.X[%]
Offset input 3 x = XX.X[%]
Offset input 4 x = XX.X[%]
Change PASSWORD2
ENT
Default
0
Independent
20%
20%
20%
00%
Description
Pump periodic auto run after XX hours of inactivity.
THIS MAY BE CONSIDERED HAZARDOUS
A value 0 disables the function
Function logic for analogue AN1, AN2.
(VASCO 209, 214, 414, 418, 425 only)
Zero correction for analogue input 1.
(20mA x20% =4mA)
Zero correction for analogue input 2.
(20mA x20% =4mA)
Zero correction for analogue input 3.
(20mA x20% =4mA)
Zero correction for analogue input 4 (default 0-10).
(10v x00% = 0v)
Pressing ENTER allows the advanced level password (2st level) (default 002) to be changed.
Fig. 1-14 Advanced Ramp Time Calculation Graph
Fig. 1-15 Voltage/Frequency Graph
24
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
ScubaTANK™ VX2
Iss.2 - Mar 2014
Iss2_11.13
75
User Guide -ScubaTANK™ VX2 Combined Water Storage & Booster Package
User Guide - VASCO Pump Controller
Setting Up a Multi-pump COMBO Function
For VASCOs to interact when used in multi-pump applications e.g in a duty/standby/assist mode, the Combo function in the Installer Parameters menu must be enabled. (This Combo function will theoretically allows serial
communication between up to 8 VASCO pumps). One pump will be designated as the Master and the others as
Slaves. Communication is made through a protocol using the RS485 port. Refer to page 15 for connection details.
To achieve the Combo function in a system requires the use a pressure sensor connected to each VASCO. The value of the set pressure is then communicated to the slaves via the serial port. To prevent the shutdown of the system due to pressure sensor failure, a 2nd identical pressure sensor can also be connected to each VASCO.
The procedure below sets up the offset operation of the sensors in the Combo (multi-pump) system and MUST be done to EACH VASCO using the Installer Parameters menu.
Whenever the user accesses the Menu screen of the VASCO Master, the communication between
VASCOs is automatically interrupted.
In case of alarm or failure of a pump in a Combo (multi-pump) system, this pump’s operation will be replaced (temporary or permanently) by another pump.
In case of failure of the Master in a Combo (multi-pump) system, it will be replaced by the next Slave.
To achieve this, all parameters must independently be setup as Master mode on each inverter.
Master setup
Supply power to the VASCO master and if not yet done, perform the initial configuration as described on page 16.
Initial View
Inv: ON/OFF Mot: ON/OFF p_mis =XX.X [bar]
1. Scroll until
Menu
ENT to access
2. Press ENTER
MENU
Param. install.
3. Press ENTER
4. Insert password
5. Scroll until
6. Set ON
001
Combo
ON/OFF
Default 001
7. Set 00
Address
XX
Vasco’s address in parallel operation.
00 = VASCO master
76
Iss 2_11.13
8. Set OFF
Alternance
ON/OFF
This function allows alternating between the VASCOs connected in parallel.
9. Set 1
Start delay AUX t = XX [s]
Sets the Delay time for the slaves to start after the variable speed pump has reached the maximum frequency and the pressure value has fallen below set pressure – delta start pressure.
10. Press STOP
11. Press STOP
RED Button
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
25
ScubaTANK™ VX2
Iss.2 - Mar 2014
Appendix A
User Guide - User Guide - VASCO Pump Controller
Slave setup
In case of a failure of the master in a Combo system, it will be replaced by slave. As a consequence, all master mode parameters must be setup independently on each inverter.
Follow Master setup until point 10 then, instead of exiting (Stop):
11. Set 01
Address
XX
Vasco’s address in parallel operation.
01...07 = VASCO slave.
12. Press STOP
RED Button
This will be repeated to set other slaves - 02, etc.
Proceed to the advanced menu.
1. Scroll until
Menu
ENT to access
2. Press ENTER
MENU
Param. install.
3. Press ENTER
4. Insert password
002
Default 002
This enters the Advanced menu
5. Scroll until
6. Set ON
7. Press STOP
8. Press STOP
Autorestart
ON/OFF
RED Button
26
Modus Fluid Technology Tel: 0844 8007052 www.modusfluidtechnology.com
ScubaTANK™ VX2
Iss.2 - Mar 2014
Iss2_11.13
77
User Guide -ScubaTANK™ VX2 Combined Water Storage & Booster Package
78
ScubaTANK™ VX2
Iss.2 - Mar 2014
ScubaTANK™ VX2
Iss.2 - Mar 2014
B
Appendix B
Miscellaneous Technical
Information
This Appendix contains miscellaneous technical information applicable to Dutypoint equipment.
• Net Positive Suction Head (NPSH)
• Variable Speed Flow, Head and Power
• General Operating Limits (Standard
79
User Guide - ScubaTANK/TM VX2 Combined Water Storage & Booster Package
Net Positive Suction Head (NPSH)
The minimum operating values that can be reached at the pump suction end are limited by the onset of cavitation.
Cavitation
Cavitation is the formation of vapour-filled cavities within liquids where the pressure is locally reduced to a critical value, or where the local pressure is equal to, or just below the vapour pressure of the liquid. The vapour-filled cavities flow with the current and when they reach a higher pressure area the vapour contained in the cavities condenses.
The cavities collide, generating pressure waves that are transmitted to the walls.
These, being subjected to stress cycles, gradually become deformed and yield due to fatigue. This phenomenon, characterised by a metallic noise produced by the hammering on the pipe walls, is called incipient cavitation.
The damage caused by cavitation may be magnified by electro-chemical corrosion and a local rise in temperature due to the plastic deformation of the walls. The materials that offer the highest resistance to heat and corrosion are alloy steels, especially austenitic steel. The conditions that trigger cavitation may be assessed by calculating the total net suction head, referred to in technical literature with the code
NPSH (Net Positive Suction Head).
Calculating NPSH
The NPSH represents the total energy (expressed in m) of the liquid measured at suction under conditions of incipient cavitation, excluding the vapour pressure
(expressed in m.) that the liquid has at the pump inlet.
To find the static height h
z
at which to install the machine under safe conditions, the following formula must be verified:
h p
+ h z
≥
(NPSH r
+ 0.5) + h f
+ h pv
Where:
h p
is the absolute pressure applied to the free liquid surface in the suction tank, expressed in m. of liquid; h p
is the quotient between the barometric pressure and the specific weight of the liquid.
h z
is the difference in height between the pump axis and the free liquid surface in the suction tank, expressed in m; h z liquid level is lower than the pump axis.
is negative when the
h f
is the friction loss in the suction line and its accessories, such as: fittings, foot valve, gate valve, elbows, etc.
hp v
the vapour pressure of the liquid at the operating temperature, expressed in m of liquid. hpv is the quotient between the Pv vapour pressure and the liquid’s specific weight.
0.5 is the safety factor.
The maximum possible suction head for installation depends on the value of the atmospheric pressure (i.e. the elevation above sea level at which the pump is installed) and the temperature of the liquid.
To help the user, with reference to water temperature (4°C) and to the elevation above sea level, the following tables show the drop in hydraulic pressure head in relation to the elevation above sea level, and the suction loss in relation to temperature.
80
ScubaTANK™ VX2
Iss.2 - Mar 2014
Appendix B Miscellaneous Technical Information
Water temp
(°C)
Suction loss
(m)
20 40 60 80 90 110 120
20 40 60 80 90 110 120
Elevation above sea level (m)
500 1000 1500 2000 2500 3000
Suction loss (m)
0,55 1,1 1,65 2,2 2,75 3,3
Friction loss must be calculated using a recognised formula. To reduce it to a minimum, especially in cases of high suction head (over 4-5m.) or within the operating limits with high delivery values, we recommend using a suction line having a larger diameter than that of the pump’s suction inlet.
It is always a good idea to position the pump as close as possible to the liquid to be pumped.
Make the following calculation:
Liquid:
Delivery required: water at ~ 15 °C g = 1 Kg/dm3
30 m3/h
Head for required delivery: 43 m
Suction difference in height: 3,5 m
The selection is a FHE 40-200/75 pump whose NPSH required value is 2.5m @ 30 m
3
/h
For water at 15°C the h pv
term is: Pv/g = 0.174 m (0.01701 bar) eh = Pa/g = 10.33 m
The h f
friction loss in the suction line with foot valves is 1.2 m.
By substituting the parameters in formula with the numeric values above:
10.33 + (-3.5)
≥
(2.5 + 0.5) + 1,2 + 0.17
6.8 > 4.4. The relation is therefore verified.
Convertion Factors
L/min. m
3
/hr
Gpm
Kg/Sec
Flow conversion
÷ 60
÷ 3.6
÷ 13.2
÷ 1.0
= L/Sec
= L/Sec
= L/Sec
= L/Sec
Pressure conversion
m Hd
Psi
Kpa
Kg/cm
3
÷ 10.2
÷ 14.47
÷ 100
÷ 1.02
= Bar
= Bar
= Bar
= Bar
ScubaTANK™ VX2
Iss.2 - Mar 2014
81
User Guide - ScubaTANK/TM VX2 Combined Water Storage & Booster Package
Variable Speed Flow, Head and Power Calculations
V
1
= Full speed
V
2
= Reduced speed
Q
1
= Flow rate at full speed
Q
2
= Flow rate at reduced speed
H
1
= Head at full speed
H
2
= Head at reduced speed
P
1
= Power at full speed
P
2
= Power at reduced speed
Q
2
=
⎛
⎝
--------
⎠
1
H
2
=
⎛
⎝
--------
⎞
⎠
2
H
1
P
2
=
⎛
⎝
--------
⎞
⎠
2
P
1
General Operating Limits (Standard Dutypoint Pumpsets)
Type of pumped liquids
Water with no gas or aggressive substances
Maximum pumped liquids temperature
Minimum pumped liquid temperature
Operating ambient temperature
Relative humidity
Air impurities
Storage temperature
Suction Conditions
+
23°C
1°C to avoid icing
+5°C to 40°C for indoor installation
(CEI EN 60439-1)
Max 50% at 40°C
The air must be clean and free of acid vapours, corrosive gases and excessive amounts of dust
+5°C to 50°C
Minimum positive pressure 0.1 Bar,
Max 0.5 Bar
82
ScubaTANK™ VX2
Iss.2 - Mar 2014
DUTYPOINT SYSTEMS
SHEPHERD ROAD
GLOUCESTER
GL2 5EL
UK
Tel: 44 (0) 1452 300592
Fax: 44 (0) 1452 303691
Email: [email protected]
www.dutypoint.net
advertisement
Key Features
- GRP construction tank
- Stainless Steel Pumps
- VASCO Inverter pump controllers
- LED system status display
- Low water level pump protection device
Related manuals
Frequently Answers and Questions
What is the maximum ambient temperature for the ScubaTANK VX2?
What is the minimum pumped liquid temperature for the ScubaTANK VX2?
What type of pump controllers are used in the ScubaTANK VX2?
How do I isolate the individual pump/controller system in the ScubaTANK VX2?
advertisement
Table of contents
- 3 Contents
- 7 Important Health & Safety Information
- 8 User Guide - Document Conventions
- 9 United Kingdom Health & Safety at Work Act 1974
- 9 Dutypoint responsibility
- 9 Customer / Contractor responsibility
- 9 ScubaTANK™ Servicing
- 9 Electrical Safety
- 9 High voltages
- 10 Electronic safety devices
- 10 High voltage testing may damage electronic components
- 10 Operating Limits For The Standard Dutypoint ScubaTANK™ Range
- 11 Water Regulations
- 13 Introduction
- 14 Welcome
- 14 Overview
- 15 Technical features
- 15 Pump
- 15 VASCO variable speed controllers
- 16 Control box
- 16 Pressure vessel
- 17 Specifications, Configurations & Dimensions
- 18 Identifying Your ScubaTANK™
- 18 Detailed Specifications
- 18 Pump rating
- 19 Arrangement & Dimensions
- 19 ScubaTANK™ VX2 375
- 20 ScubaTANK™ VX2 490
- 21 ScubaTANK™ VX2 650
- 22 ScubaTANK™ VX2 800
- 23 ScubaTANK™ VX2 1050
- 24 ScubaTANK™ VX2 1250
- 25 ScubaTANK™ VX2 1650
- 26 ScubaTANK™ VX2 2250
- 27 Pump Performance
- 27 XPR3000 Series Pumps @ 2850rpm
- 28 XPR5000 Series Pumps @ 2850rpm
- 29 XPR9000 Series Pumps @ 2850rpm
- 30 Pump Controller Specification
- 31 Installation & Commissioning
- 32 Basic Installation Information
- 32 Installation help
- 32 Water regulations
- 32 Identifying your ScubaTANK™ system
- 33 Installation Sequence
- 33 Siting the ScubaTANK™
- 34 Hydraulic Connection
- 34 Electrical Supply
- 34 Commissioning
- 37 Using the ScubaTANK™
- 38 The User Control Panels
- 38 System Isolation
- 38 Basic Operational Information
- 38 The VASCO display
- 38 Initial view
- 39 Menu view
- 40 Restoring the Controller Configuration
- 40 Starting and Running the ScubaTANK™
- 40 Initial installation
- 41 Normal running
- 41 Protection and Fault Alarms
- 42 Alert Messages and Possible Causes
- 43 Accessing the Advanced Parameters
- 45 Troubleshooting
- 46 Operational Alarms and Alerts (VASCO Pump Controllers)
- 46 General Tank Troubleshooting
- 47 Routine Maintenance & Repair
- 48 Routine User Maintenance
- 48 Recommended user weekly checks
- 48 Recommended user monthly checks
- 48 Recommended user 6 monthly checks
- 48 Essential 12 monthly (maximum interval) service
- 49 Pressure Vessel Servicing
- 49 Periodic maintenance
- 49 Precharge pressure check
- 50 General guidance notes for vessel repair & replacement
- 50 Replacing the diaphragm
- 50 Installing a replacement vessel
- 51 Inlet Solenoid Close Control & Bypass Screw Adjustment
- 51 Opening the Tank
- 51 Pump Servicing
- 51 Routine maintenance
- 51 Pump replacement
- 52 Checking the direction of rotation
- 52 VASCO Controller Servicing
- 81 Miscellaneous Technical Information
- 82 Net Positive Suction Head (NPSH)
- 82 Cavitation
- 82 Calculating NPSH
- 83 Convertion Factors
- 84 Variable Speed Flow, Head and Power Calculations
- 84 General Operating Limits (Standard Dutypoint Pumpsets)