Installation Instructions

ODH-4500R Over Door Heater

Reference

J356d

SAFETY

The correct procedures for working at height must be adopted when installing this heater.

The heater must be installed by a suitably qualified person in accordance with current regulations.

CONTENTS

Remove from carton and check contents:

- heater unit

- mounting bracket

- 2 no. M6 bolts, 2 no. shake proof washers, 4 no. plain washers.

Ensure all packing material is removed and inlet/outlet grilles are clear.

LOCATION

This heater is designed for high level use above frequently used doorways. It must not be installed less than 1.8metres from floor level and the maximum recommended mounting height is 2.8m. It should not be positioned immediately below a fixed socket outlet. Optimum performance is achieved when the heater is positioned as close to the top of the door as possible. For wider doorways multiple units can be installed giving a continuous curtain of hot air.

FIXING

The heater can be mounted either a) directly to the wall or b) to the wall or ceiling using the bracket supplied.

a) The unit is mounted directly to the wall via two keyhole slots and fixed via two holes.

1) Securely fix two No.10 screws (not supplied) at 500mm centres 208mm above desired position for outlet grille.

2) Slide unit over screws and ensure secure fixing.

3) For extra security the front cover can be removed and the two additional mounting holes used

.

(DISCONNECT FROM POWER SUPPLY BEFORE REMOVING COVER) b) The bracket can be fixed to either the wall or ceiling provided secure fixings can be made

1) Loosely fit M6 bolts with 2 plain washers and shake proof washer closest to head.

2) Provisionally place in bracket to ascertain optimum location and mark fixing holes.

3) Remove from heater and securely fix bracket

4) Replace heater at appropriate angle and tighten bolts securely.

CONTROL

Remote Switch

The Remote Switching Unit (ODH-RSW) allows ON/OFF, Fan only with 2.25 or 4.5 kW.

Thermostat

If a thermostat is required a unit of sufficient switching capacity(25A) can be connected in the power

ELECTRICAL CONNECTION

The heater should be installed in accordance with the latest edition of the IEE Requirements for

Electrical Installation (BS 7671:2001)

Position remote switch unit in suitable location. A means of disconnection having a contact separation of

3mm in all poles should be incorporated.

Remove heater cover plate (4 screws)

Select cabling with 4 cores and earth of appropriate size for current and volt drop.

Pass cable/s through cord grip in top of unit. Leave sufficient length for connection but ensuring cables do not foul blower unit. Make off connections to connector block and earth stud in accordance with circuit diagram ODH-W-006 ( copy on back page)

If remote switching is not required connect power supply to L and N and link L,LI and LII with 1.5sqmm cable.

Tighten up cord grip. Replace connection cover.

IMPORTANT : always check to ensure the heating elements cannot be energised without the fan running.

.

WARNING: THE HEATER MUST BE EARTHED.

OVER TEMPERATURE CUT OUT

Should the heater exceed normal operating temperature the over temperature cut out on the heating element will operate.

switch off power to the unit and allow to cool before switching on again. If the problem persists consult a suitably qualified person.

Note:- Do not cover the unit possible damage.

or allow the inlet grille to be obstructed as this could cause over heating and

CONTROLS.

On/off control is by remote switch. Heat control is by the 2 switches located next to the outlet grille.

One on - half heat (2.25 kW)

Two on - full heat (4.5 kW)

Both off - fan only

Note: the switches are electrically interlocked to ensure the heat cannot be on without the fan operating.

They operate in parallel with the remote switch.

CLEANING.

The heater should be cleaned occasionally to reduce the build up of dust which may cause the unit to overheat

WARRANTY

This product is guaranteed, in accordance with our Conditions of Sale, for a period of 12 months from date of purchase. We will repair or replace, at our discretion, any part found to be defective. We cannot accept responsibility for any consequential liability.

The warranty will be invalid if the heater has not been installed in accordance with these instructions.

This does not affect your statutory rights.

Remote Switch ODH-RSW (Optional)

Note:- operates in parallel

L N

L

L L1 L11

II I L N

Connector

Block

3

3

4

1

2

5

No

Commercial Electric Heat Limited

HAWICK TD9 8SL

Part No Description

B033-01

D002-01

F015

C001

E077

Heating element

Fan motor

Connector block

Blower unit

SPST 16A sw red

Heater

Rocker

Switches

5

No

1

2

Revision

Add external cut outs

Change motor connection

Date

11/04

02/09 Fan

Motor

2

1

Schematic diagram

Each heating element incorporates over-temperature cut out in common terminals

To reset:-

Switch off and allow to cool (5 minutes) then restore supply

Heater does not function again until power has

been removed from cut out

All wiring 1.5mm 105 C Tri rated Panel wire unless marked 2.

5mm 2

L

N

2

2.25kW

1

2.25kW

Title

ODH-4500R 4.5kW

Over Door Heater c/w remote switch

Drawn by Date

NEB 29.05.03

Scale nts

Drawing No.

ODH-W-006

Rev

2

L011

Please keep these instructions for future reference

The Manufacturers reserve the right to change the specification without prior notice EO&E