Allen-Bradley 1747 DCM Direct Communication Module User Manual
Below you will find brief information for Direct Communication Module 1747 DCM. The Direct Communication Module (DCM) connects a supervisory PLC-5r or SLC 500 to a remote SLC 500 via the RIO link and provides a distributed processing system. The DCM module can communicate with supervisory PLC or SLC controllers through RIO scanners, as if they were addressing a logical rack. However, the DCM does not scan the I/O in its local I/O chassis, rather it passes the supervisory data to the distributed SLC processor.
Advertisement
Advertisement
Allen-Bradley
Direct
Communication
Module
(Cat. No. 1747-DCM)
User
Manual
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. “Safety Guidelines for the Application,
Installation and Maintenance of Solid State Controls” (Publication SGI-1.1) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will the Allen-Bradley Company be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, the Allen-Bradley Company cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Allen-Bradley Company with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of the Allen-Bradley Company is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
!
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
Attentions help you:
• identify a hazard
• avoid the hazard
• recognize the consequences
Important: Identifies information that is especially important for successful application and understanding of the product.
PLC, PLC-2, PLC-3, and PLC-5 are registered trademarks of Allen-Bradley Company, Inc.
SLC, SLC 500, Dataliner, PanelView, RediPANEL, PLC-5/11, PLC-5/15, PLC-5/20, PLC-5/12,
PLC-5/25, PLC-5/30, PLC-5/40, PLC-5/60 are trademarks of Allen-Bradley Company, Inc.
IBM is a registered trademark of International Business Machines, Incorporated.
New Information
Summary of Changes
Summary of Changes
The information below summarizes the changes to this manual since the last printing as 1747-NM007–September 1993.
To help you find new information and updated information in this release of the manual, we have included change bars as shown to the right of this paragraph.
The table below lists sections that document new features and additional information about existing features, and shows where to find this new information.
For This New Information
Related documentation updated
Quick Start for Experienced Users
Default DIP switch settings
CE certification
DCM clear on fault DIP switch
See
preface chapter 2 chapter 4 chapter 5, appendix A chapter 6
Overview
Quick Start for Experienced Users
Addressing
Module Configuration
Table of Contents
Direct Communication Module
User Manual
Preface
Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terms and Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Common Techniques Used in this Manual . . . . . . . . . . . . . . . . . . . . . . . . . .
Allen-Bradley Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Local Product Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Product Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Your Questions or Comments on this Manual . . . . . . . . . . . . . . . . . . . . .
Chapter 1
Hardware Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
What Is a Remote I/O Adapter?
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Extended Node Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scanner Image Division . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scanner Image Division Configuration Example . . . . . . . . . . . . . . . . . . .
Data Exchange Between RIO Scanners and the DCM . . . . . . . . . . . . . . . . .
What Is the Status Word?
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter
2
Required Tools and Equipment
Procedures
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 3
Addressing Ladder Logic Instructions
PLC/Scanner Addresses
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SLC Addresses
I/O Image Tables
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLC to DCM/SLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DCM/SLC to PLC
Image Mapping
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 4
DIP Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DIP Switch 1 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting I/O Group Number (SW1-7 and SW1-8) . . . . . . . . . . . . . . . . . . .
Rack Address (SW1-1 through SW1-6) . . . . . . . . . . . . . . . . . . . . . . . . .
DIP Switch 2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rack Size (SW2-5 and SW2-6))
Last Rack (SW2-4)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Clear On Fault (SW2-3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Rate (SW2-1 and SW2-2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
i
ii
Table of Contents
Direct Communication Module
User Manual
Installation and Wiring
Programming
Troubleshooting
Application Examples
Chapter 5
Compliance to European Union Directives
EMC Directive
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DCM Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation
Removal
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Network Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 6
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Physical Input into PLC – Physical Output from SLC . . . . . . . . . . . . . . . .
Physical Input into SLC – Physical Output from PLC . . . . . . . . . . . . . . . .
Physical Input into Both PLC and SLC (Logical AND) –
Physical Output from SLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Physical Input into First SLC – Physical Output from Second SLC
Status Words
. . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RIO Scanner Input Status Word Examination (Decimal)
DCM/SLC Output Status Word Examination (Octal)
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
Applications Using I/O Status Word Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RIO Scanner Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the Program/Test/Fault Mode Bit . . . . . . . . . . . . . . . . . . . . . . .
DCM/SLC Output Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the Data Invalid Bit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the User Status Flag Bit . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RIO Scanner Input Status and DCM/SLC Output Status . . . . . . . . . . . . .
Using the Logical OR Bit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 7
DCM Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting Using the FAULT LED (Red) . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting Using the COMM LED (Green) . . . . . . . . . . . . . . . . . . . . . .
Chapter 8
Basic Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1747-SN Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Configuration for Rack 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Configuration for Rack 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Image Table Configuration
Program Listing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Supplementary Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Configuration
DIP Switch Settings
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Image Table Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications
DCM Addressing
Worksheet
Table of Contents
Direct Communication Module
User Manual
Program Listing for 5/01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Program Listing for PLC5/15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix A
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Network Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Throughput Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix B
Directions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Addressing Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLC Addresses
SLC Addresses
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iii
Preface
Who Should Use this
Manual
Purpose of this Manual
Preface
Read this preface to familiarize yourself with the rest of the manual. This preface covers the following topics:
• who should use this manual
• the purpose of this manual
• terms and abbreviations
• conventions used in this manual
•
Allen–Bradley support
Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use Allen–Bradley small logic controllers.
You should have a basic understanding of SLC 500 t products. You should understand programmable controllers and be able to interpret the ladder logic instructions required to control your application. If you do not, contact your local Allen–Bradley representative for information on available training courses before using this product. If using Advanced Programming
Software (APS), we recommend that you review The APS Quick Start for
New Users, Publication 9399-APSQS.
This manual is a reference guide for the Direct Communication Module
(DCM). It describes the procedures you use to address, configure and program the DCM for application with PLCs and SLCs.
P–1
Preface
Contents of this Manual
Chapter
Title
Preface
Overview
Content
Describes the purpose, background, and scope of this manual. Also specifies the audience for whom this manual is intended.
Provides a hardware and system overview including physical features, system communication, scanner image division and communications flow.
Quick Start for Experienced Users
Addressing
Module Configuration
Installation and Wiring
Programming
Troubleshooting
Application Examples
Specifications
DCM Addressing Worksheet
Serves as a Quick Start Guide for using the DCM.
Explains slot numbering and image mapping.
Provides DIP switch setting information.
Provides installation procedures and a wiring diagram.
Shows how to program ladder logic in the PLC r and the SLC 500, including an examination of special programming instructions that affect system response. Also examines the status word and its applications.
Describes troubleshooting using front panel LEDs.
Provides and examines both basic and supplementary applications.
Provides module and system specifications and discusses throughput.
Helps you to work out the image table configuration for DCMs in your system.
P–2
Preface
Related Documentation
The following documents contain additional information concerning
Allen–Bradley SLC t and PLC products. To obtain a copy, contact your local Allen–Bradley office or distributor.
For
An overview of the SLC 500 family of products
A description on how to install and use your Fixed SLC 500 programmable controller
A description on how to install and use your Modular SLC 500 programmable controller
A reference manual that contains information regarding the use of the PLC–5 r programmable controller
A procedural manual for technical personnel who use APS to develop control applications
A reference manual that contains status file data, and instruction set information for the SLC 500 processors and MicroLogix 1000 controllers.
Information regarding the use of the 1747–SN SLC RIO scanner
An introduction to APS for first–time users, containing basic concepts but focusing on simple tasks and exercises, and allowing the reader to begin programming in the shortest time possible
Read This Document
SLC 500 System Overview
Installation & Operation Manual for Fixed Hardware
Style Programmable Controllers
Installation & Operation Manual for Modular
Hardware Style Programmable Controllers
PLC–5 Reference Instruction Set
Rockwell Software Advanced Programming
Software (APS) User Manual
SLC 500 t and MicroLogix 1000t Instruction Set
Reference Manual
Remote I/O Scanner User Manual
Quick Start for New Users
Document
Number
1747-2.30
1747-6.21
1747-6.2
1785-6.1
9399-APSUM
1747-6.15
1747-6.6
9399-APSQS
A training and quick reference guide to APS
A common procedures guide to APS.
A procedural and reference manual for technical personnel who use an HHT to develop control applications
An introduction to HHT for first–time users, containing basic concepts but focusing on simple tasks and exercises, and allowing the reader to begin programming in the shortest time possible
SLC 500 Software Programmer’s Quick Reference
Guide
available on PASSPORT at a list price of
$50.00
SLC 500 Common Procedures Guide
available on
PASSPORT at a list price of $50.00
Allen–Bradley Hand–Held Terminal User Manual
Getting Started Guide for HHT
ABT-1747-TSG001
ABT-1747-TSJ50
1747-NP002
1747-NM009
An article on wire sizes and types for grounding electrical equipment
National Electrical Code
Published by the
National Fire
Protection
Association of
Boston, MA.
A complete listing of current Allen–Bradley documentation, including ordering instructions. Also indicates whether the documents are available on CD–ROM or in multi–languages.
A glossary of industrial automation terms and abbreviations
Allen–Bradley Publication Index
Allen–Bradley Industrial Automation Glossary
SD499
AG-7.1
P–3
Preface
Terms and Abbreviations
The following terms and abbreviations are specific to this product. For a complete listing of Allen–Bradley terminology, refer to the Allen–Bradley
Industrial Automation Glossary, Publication Number ICCG–7.1.
Adapter – Any physical device that is a slave on the RIO link.
Adapter Image – The portion of scanner image assigned to an individual adapter. You configure the adapter image by assigning it a starting logical rack number, starting logical group number and the number of logical groups it uses. In the case of the DCM, this is referred to as the DCM image.
DCM – Refers to the Direct Communication Module.
Distributed Control/Controller – Refers to a control system that employs a number of different hardware controllers/processors, each designed to perform a different subtask on behalf of an overall program or process. In a single processor (non–distributed) system, each task would be done by the single processor controlling the process. In a distributed system, each task is targeted to the specific processor required to perform its needs. Since all processors run simultaneously and independently, the time required to perform each task of the overall process is reduced in comparison to a single processor system. Therefore, overall program or process performance is typically better.
Inhibit – A function by which the scanner stops communicating with a logical device. The logical device will consider itself inhibited if it does not receive communications from the scanner within a certain period of time.
Logical Device – Any portion of a logical rack assigned to a single adapter.
Logical Group – A logical group consists of one input and one output word within a logical rack. A word consists of 16 bits, each bit represents one terminal on a discrete I/O module. Also referred to as an I/O Group.
Logical Rack – A fixed section of the scanner image comprised of eight input words and eight output words. Also referred to as a rack.
Logical Slot – A logical slot consists of one input and one output byte within a logical group. A byte consists of 8 bits, each bit represents one terminal on a discrete I/O module.
Physical Device – The number of devices that the supervisory processor/ scanner will support.
PLC Chassis – A physical PLC (Programmable Logic Controller) rack that houses PLC processors and 1771 I/O modules.
P–4
Preface
Rack Size – The logical rack size of the DCM image.
RIO Link – (Remote Input/Output) Refers to an Allen–Bradley communication system supporting high–speed serial transfer of Remote I/O
(RIO) control information.
Scanner – The communication master on the RIO link.
Scanner Image – The data table area within the scanner, used to exchange
I/O information between the scanner and all the adapters on the RIO link.
The scanner image is a portion of the SLC or PLC processor image.
Slave – In a communication link, a station that cannot initiate communication.
SLC Chassis – A physical SLC (Small Logic Controller) rack that houses
SLC processors and 1746 and 1747 I/O modules.
Slot – The physical location in any chassis used to insert I/O (or specialty) modules.
Supervisory Control/Controller – A control system whereby a host
(supervisory) controller/processor monitors and intermittently adjusts control parameters, as necessary, of one or several lower level processors while the lower level processor(s) performs the control task continuously in real time.
Common Techniques Used in this Manual
The following conventions are used throughout this manual:
•
Bulleted lists such as this one provide information, not procedural steps.
•
Numbered lists provide sequential steps or hierarchical information.
•
Italic type is used for emphasis.
P–5
Preface
Allen–Bradley Support
Allen–Bradley offers support services worldwide, with over 75 Sales/Support
Offices, 512 authorized Distributors and 260 authorized Systems Integrators located throughout the United States alone, plus Allen–Bradley representatives in every major country in the world.
Local Product Support
Contact your local Allen–Bradley representative for:
• sales and order support
• product technical training
• warranty support
• support service agreements
Technical Product Assistance
If you need to contact Allen–Bradley for technical assistance, please review the information in the Troubleshooting chapter first. Then call your local
Allen–Bradley representative.
Your Questions or Comments on this Manual
If you find a problem with this manual, please notify us of it on the enclosed
Publication Problem Report.
If you have any suggestions for how this manual could be made more useful to you, please contact us at the address below:
Allen–Bradley Company, Inc.
Automation Group
Technical Communication, Dept. 602V, T122
P.O. Box 2086
Milwaukee, WI 53201–2086
P–6
Chapter
1
Overview
This chapter provides a hardware and system overview including physical features and connectivity illustrations. It also explains data exchange between processors and discusses rack size. Topics include:
• hardware overview
• system overview
• scanner image division
• communications flow
Hardware Overview
FAULT LED
(Red)
COMM LED
(Green)
Door Label
Front Label
RIO Link Connector
Cable Tie Slots
The Direct Communication Module, Catalog Number 1747–DCM, is used to connect an SLC 500 Fixed Programmable Controller with expansion chassis or any SLC 500 Modular Programmable Controller to a supervisory
Allen–Bradley Programmable Controller via the RIO Link, thereby providing a distributed processing system. The DCM occupies one slot in any SLC 500 chassis.
Self–Locking Tab
Side Label
DIP Switches
DCM
FAULT
COMM
CONFIGURATION
RACK ADDR
RACK SIZE
1/4 1/2 3/4 1
FIRST I/O GROUP
0 2 4 6
DATA RATE (K B/S)
57.6 115.2 230.4
LINE 1 _______
SHIELD ______
LINE 2 _______
I/O
GROUP
(LSB)
RACK
ADDRESS
(MSB)
X
X
RACK
SIZE
LAST RACK
CLR ON FLT
DATA
RATE
SW 1
(LSB)
RACK
ADDR
(MSB)
2
1
4
3
6
5
8
7
SW 2
X
X
LAST RACK
CLR ON FLT
DATA
RATE
2
1
4
3
6
5
8
7
1747–DCM
Self–Locking Tab
Hardware Features
Hardware
FAULT LED
COMM LED
Front, Side and Door Labels
RIO Link Connector
Cable Tie Slots
DIP Switches
Self–Locking Tabs
Displays operating status
Function
Displays communication status
Provide module configuration information
Provides physical connection to RIO network
Secure and route wiring from module
Establish configuration parameters for the module
Secure module in chassis slot
1–1
Chapter 1
Overview
System Overview
Supervisory PLC or SLC
The Direct Communication Module is an SLC 500 family Remote I/O (RIO) adapter. It allows supervisory processors, such as PLC–5s, and distributed
SLC–500 processors residing on an Allen–Bradley RIO Communication
Link to transfer data between each other. The DCM appears as an RIO adapter to:
• a PLC processor with integral RIO scanner on the RIO Communication
Link
• an RIO scanner, Catalog Number 1771–SN or 1747–SN, on the RIO
Communication Link
DCM 1
RIO Scanner Distributed SLCs with
DCMs (adapters)
PanelView t (adapter)
DCM 2
DCM 3
RIO Communication Link
DCM modules are connected in a daisy–chain configuration using Belden
9463 cable.
What Is a Remote I/O Adapter?
A remote I/O adapter (RIO adapter) is any module that acts as a slave to an
RIO scanner, the master on the RIO link. The DCM is an RIO adapter.
All RIO scanners have defined physical and logical specifications. Physical
specifications are the maximum number of adapters that can be connected to
the scanner. (See Extended Node Capability on page 1–4.) Logical
specifications are the maximum number of logical racks the scanner can address, the ways logical racks can be assigned, and the ability of the scanner to perform block transfers. Refer to the appropriate scanner manual for details concerning physical and logical specifications.
The DCM can physically reside on the RIO link with any other adapter. The following table lists the adapters available for use with an RIO link.
1–2
Chapter 1
Overview
1784-F30D
1771-RIO
1771-JAB
1771-DCM
1778-ASB
1747-ASB
2706-xxxx
2705-xxx
2711-xx
1336-RIO
Compatible Adapters
Catalog
Number
1785-LT/x
1785-LT2
1785-LT3
1785-L30x
1785-L40x
1785-L60x
1771-ASC
1771-ASB
Device
PLC-5/15
PLC-5/25
PLC-5/12
PLC-5/30
PLC-5/40
PLC-5/60
Remote I/O Adapter Module
Remote I/O Adapter Module
1771-AM1
1771-AM2
1395-NA
1747-ASB
1-Slot I/O Chassis with Integral
Power Supply and Adapter
2-Slot I/O Chassis with Integral
Power Supply and Adapter
Plant Floor Terminal Remote I/O
Expansion Module
Remote I/O Interface Module
Single Point I/O Adapter Module
Direct Communication Module
Remote I/O Adapter Module
Remote I/O Adapter Module
DL40 Dataliner t
RediPANEL t
PanelView Terminal
Remote I/O Adapter for 1336 AC
Industrial Drives
Remote I/O Adapter for 1395 DC
Industrial Drives
SLC 500 Remote I/O Adapter
Module
Yes
No
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Extended
Node
Capability
Yes
Yes
Yes
Yes
Yes
Yes
No
Series B and
C only
Comments
In adapter mode
In adapter mode
In adapter mode
In adapter mode
In adapter mode
In adapter mode
Series A, B, and C
Yes
Yes
Yes
Yes
Must be catalog number
2706-ExxxxxB1.
1–3
Chapter 1
Overview
Scanner Image Division
Extended Node Capability
Both scanners and adapters can have extended node capability. Extended node capability allows you to have up to 32 adapters on the RIO link using an 82 Ohm termination resistor at both ends of the RIO link for all baud rates.
Extended node capability can only be used if the scanner and all adapters on the RIO link have extended node capability. The DCM has extended node
capability.
The scanner allows each adapter to use a fixed amount (user defined) of its input and output image.
The scanner image is divided into logical racks and further divided into logical groups. A full logical rack consists of eight input and eight output image words. A logical group consists of one input and one output word in a logical rack. Each logical group is assigned a number from 0–7. The number of racks available for data and I/O transfer depends on the scanner you are using.
Local I/O
Logical Rack 0
Logical Rack 1
Remote I/O
(Scanner Image)
Logical Rack 2
Logical Rack 3
Logical Group 0
Logical Group 7
Scanner I/O Image Processor I/O Image Adapter
Image
The scanner image also contains the image of each adapter on the RIO link.
The adapter is assigned a portion of the scanner image, which is referred to as the adapter image.
1–4
Chapter 1
Overview
Scanner Image Division Configuration Example
The example presented here can help you configure your RIO architecture.
Refer to it as necessary.
The following figure shows how a portion of a scanner’s input image table might be configured. An output image table would be identically configured.
Logical
Rack 0
Logical
Rack 1
Logical
Rack 2
Decimal Bit Number
Rack 0 Group 0
Rack 0 Group 1
Rack 0 Group 2
Rack 0 Group 3
Rack 0 Group 4
Rack 0 Group 5
Rack 0 Group 6
Rack 0 Group 7
Rack 1 Group 0
Rack 1 Group 1
Rack 1 Group 2
Rack 1 Group 3
Rack 1 Group 4
Rack 1 Group 5
Rack 1 Group 6
Rack 1 Group 7
Rack 2 Group 0
Rack 2 Group 1
Rack 2 Group 2
Rack 2 Group 3
Rack 2 Group 4
Rack 2 Group 5
Rack 2 Group 6
Rack 2 Group 7
Octal Bit Number
Word 11
Word 12
Word 13
Word 14
Word 15
Word 16
Word 17
Word 18
Word 19
Word 20
Word 21
Word 22
Word 23
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
Word 8
Word 9
Word 10
15
17
14
16
13
15
12
14
11
13
10
12
9
11
8
10
7
7
6
6
5
5
4
4
3
3
2
2
1
1
0
0
Device 1
(Full logical rack)
Device 2
(3/4 logical rack)
Device 3
(1/4 logical rack)
Device 4
(1/2 logical rack)
Device 5
(1/2 logical rack)
Important: The configured image size of a DCM cannot cross logical rack boundaries; it cannot use a portion of rack 0 and a portion of rack 1.
1–5
Chapter 1
Overview
Data Exchange Between RIO
Scanners and the DCM
Processor Scan
Supervisory PLC or SLC
Information is transferred between the RIO scanner and the DCM every RIO scan. RIO transmissions are asynchronous to the processor scans.
Important: The DCM provides word integrity on all words transferred via the SLC backplane.
The DCM communicates with supervisory PLC or SLC controllers through
RIO scanners, as if they were addressing a logical rack. However, the DCM does not scan the I/O in its local I/O chassis, rather it passes the supervisory data to the distributed SLC processor.
In the DCM, outputs from the SLC output image table are inputs to the supervisory processor input image table. Likewise, outputs from the supervisory processor output image table are inputs to the SLC input image table.
The diagram that follows depicts the communications flow between an RIO scanner and the DCM.
Distributed Processor Scan
SLC Distributed
Processor
DCM I/O Module I/O Module
Scanner
RIO Scan
Outputs from PLC,
Input Data to DCM
Inputs to PLC, Output
Data from DCM
SLC Chassis
Inputs to Modules
SLC Expansion
Chassis
Outputs from
Modules
Output Device
Input Device
What Is the Status Word?
The first word of the DCM input and output image is the status word. The status word indicates the status of communication and data between the RIO scanner and the DCM. For more information on status words and their
applications, see chapter 6, Programming.
1–6
Required Tools and
Equipment
Chapter
2
Quick Start for Experienced Users
This chapter helps you to get started using the Direct Communication
Module (DCM). We base the procedures here on the assumption that you have a basic understanding of SLC 500 products.
You must:
• understand electronic process control
• be able to interpret the ladder logic instructions for generating the electronic signals that control your application
Because it is a start-up guide for experienced users, this chapter does not contain detailed explanations about the procedures listed. It does, however, reference other chapters in this book where you can get more detailed information. It also references other documentation that may be helpful if you are unfamiliar with programming techniques or system installation requirements.
If you have any questions, or are unfamiliar with the terms used or concepts presented in the procedural steps, always read the referenced chapters and other recommended documentation before trying to apply the information.
This chapter:
• tells you what tools and equipment you need
• lists preliminary considerations
• describes when to address, configure and program the module
• explains how to install and wire the module
• discusses system power-up procedures
Have the following tools and equipment ready:
• medium blade screwdriver
•
(2) 1/2 watt terminating resistors (See chapter 5, Installation and Wiring,
for correct size.)
• programming equipment (All programming examples shown in this manual demonstrate the use of Allen-Bradley’s Advanced Programming
Software [APS] for personal computers.)
2–1
Chapter 2
Quick Start for Experienced Users
Procedures
1.
Check the contents of the shipping box.
Unpack the module making sure that the contents include:
•
Direct Communication Module (Catalog Number 1747-DCM)
• removable connector (factory-installed on module)
• cable tie
• user manual (Catalog Number 1747-NM007)
If the contents are incomplete, call your local Allen-Bradley representative for assistance.
Reference
–
Select a scanner.
Reference
To begin configuration of your RIO system, you should know three things:
• which scanner is compatible with your PLC/SLC controller. Use the table below to select a scanner that is compatible with your processor. The DCM is compatible with all RIO scanners.
The manual for the scanner you select
1747-SN
➀
Catalog Number
1771-SN
➁
1772-SD, -SD2
➂➃
1775-S4A, -S4B, -S5
➀
1775-SR, -SR5
➀
1785-L11B
➀
1785-LT/x
➀➄
1785-L20B
➀
1785-LT2
➀➄
1785-L30x
➀
1785-L40x
➀
1785-L60x
➀
5250-RS
➀
6008-SI
➀
6008-SV
➀
6008-SQH1, -SQH2
Description
SLC Remote I/O Scanner
Sub I/O scanner for Mini–PLC-2 r
and PLC-5 families
Remote scanner/distribution panel for PLC-2 family
I/O scanner-programmer interface module for PLC-3 r
family
Remote scanner/distribution panel for PLC-3/10 family
PLC 5/11 t (in scanner mode)
PLC 5/15 (in scanner mode)
PLC 5/20 t (in scanner mode)
PLC 5/25 (in scanner mode)
PLC 5/30 t (in scanner mode)
PLC 5/40 t (in scanner mode)
PLC 5/60 t (in scanner mode)
Remote scanner for PLC 5/250
IBM r PC I/O Scanner Module
VMEbus I/O Scanner Module
Q-bus I/O Scanner Module
➀
Extended node capability.
➁
Revision D or later.
➂
Rev. 3 or later.
➃
Extended node capability not available with Series A.
➄
Rev. 3 or later.PLC 5/15 Series B Revision H or later have partial rack addressing. Earlier versions are limited to 3 devices.
PLC 5/25 Series A Revision D or later have partial rack addressing. Earlier versions are limited to 7 devices.
2–2
Chapter 2
Quick Start for Experienced Users
• the maximum number of physical devices and logical racks your scanner supports.
• the logical rack size of each DCM. This depends on how many I/O data words you need to transfer. The first word is always the status word. The table below shows the number of data words transferred relative to the rack size.
If you configure the DCM as:
1/4 Rack
1/2 Rack
3/4 Rack
Full Rack
Then:
1 data word (16 bits of I/O data) are transferred.
3 data words (48 bits of I/O data) are transferred.
5 data words (80 bits of I/O data) are transferred.
7 data words (112 bits of I/O data) are transferred.
Including the Status Word
Total transfer = 2 words
Total transfer = 4 words
Total transfer = 6 words
Total transfer = 8 words
3.
Choose the type of slot addressing you will use.
Select DCM addressing. (A configuration worksheet is included in appendix B to assist you in DCM
image table addressing.)
4.
Configure your system by setting the DIP switches.
5.
Configure the module using the DIP switches.
Insert the 1747-DCM module into the chassis.
Reference
(Addressing)
(DCM Worksheet)
Reference
(Module
Configuration)
Reference
!
ATTENTION: Never install, remove, or wire modules with power applied to the chassis or devices wired to the module.
Review SLC/DCM power requirements to ensure your SLC power supply has adequate reserve power.
Make sure system power is off; then insert the DCM into your 1746 chassis. In this example procedure, local slot 1 is selected.
(Installation and
Wiring)
Card Guide
Cable Tie
...
Module Release
2–3
Chapter 2
Quick Start for Experienced Users
To wire the network, a 1/2 watt terminating resistor must be attached across line 1 and line 2 of the connectors at each end (scanner and last physical device) of the network. The size of the resistor depends on the baud rate and extended node capability, as shown below:
Us n xten e xten e
Capability o e
Baud Rate
57.6K baud
115.2K baud
230.4K baud
57.6K baud
115.2K baud
230.4K baud
Maximum Cable Distance
(Belden 9463)
3048 meters (10,000 feet)
1524 meters (5,000 feet)
762 meters (2,500 feet)
3048 meters (10,000 feet)
1524 meters (5,000 feet)
762 meters (2,500 feet)
Resistor Size
8
W 1
Gr r G
150
W 1/2 Watt
Brown–Green–Brown–Gold
82
W 1/2 Watt
Gray–Red–Black–Gold
6.
Enter your ladder program.
Define the application requirements. Write and enter the ladder logic program.
7.
Go through the system start-up procedure.
Power up your system by performing standard start-up procedures as indicated in your processor manual. No special start-up procedures are required when using the DCM module.
Reference
(Programming)
(Application
Examples)
Reference
–
2–4
Addressing Ladder Logic
Instructions
Chapter
3
Addressing
This chapter provides general information about how to address supervisory
PLC and distributed SLC ladder logic instructions. It also illustrates image mapping and provides an example of how a PLC output image is mapped into an SLC input image.
All PLC and SLC processors use 3-part addresses. These three parts include:
• logical rack or physical slot address
• logical group or word address
• bit address
PLC processors use the octal number system for bit addressing. SLC processors use the decimal number system for bit addressing.
PLC Processors/Scanners Address By:
Logical Rack: PLC/scanner input and output images are organized in logical racks, which consist of eight groups.
The rack address does not need to match the SLC slot address.
Logical Group: There are eight logical groups per logical rack, numbered 0–7. One group consists of one input and one output word. Each word is made up of 16 bits.
SLC Processors Address By:
Physical Slot: The slot address is determined by what slot number you place your DCM. SLC slots are numbered 0–30.
The slot address does not need to match the PLC rack address.
Word: One word is 16 bits in size. The number of words used in input and output images varies according to how many you specify in your setup. Words are numbered consecutively beginning with 0.
Logical
Rack
#x
The group number does not need to match the SLC word address.
Bit: PLC bits are numbered octally, from
0 to 7 and 10 to 17.
The bit number does not need to match the SLC bit number
(because SLCs use decimal); however, the position of the bit in the word must be the same.
Octal
Bit Number 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0
Group 0
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7
The word number does not need to match the PLC group number.
Bit: SLC bits are numbered decimally, from 0–15.
The bit number does not need to match the PLC bit number
(because PLCs use octal); however, the position of the bit in the word must be the same.
Decimal
Bit Number 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
Physical
Slot
#x
3–1
Chapter 3
Addressing
PLC/Scanner Addresses
The three parts of the PLC address include the:
• logical rack
• logical group (I/O group)
• bit
PLC Input Address PLC Output Address
I:023/10 O:017/10
I = Input
02 = Logical Rack
3 = I/O Group
10 = Bit (octal)
O = Output
01 = Logical Rack
7 = I/O Group
10 = Bit (octal)
The rack address refers to the logical rack assigned to the DCM in the PLC/ scanner I/O image table. It is selected using switches 1 through 6 of SW1 on the DCM. This address does not need to match the physical slot address of
the DCM. Complete information about DIP switch selection is in chapter 4,
Module Configuration.
The I/O group address refers to the word in the PLC/scanner image table that contains the referenced I/O data bit. The I/O group address does not need to match the word address of the SLC I/O instruction.
The bit address is the bit within the word being addressed. Bits are numbered 0–17 (octal) for the PLC and 0–15 (decimal) for the SLC. The physical position of the bit in the PLC word must match the position of the bit in the SLC word to address the correct bit.
3–2
Chapter 3
Addressing
SLC Addresses
The three parts of the SLC address include the:
• physical slot
• word
• bit
SLC Input Address
I:2.3/8
SLC Output Address
O:1.7/8
I = Input
2 = Physical Slot
3 = Word
8 = Bit (decimal)
O = Output
1 = Physical Slot
7 = Word
8 = Bit (decimal)
The slot address refers to the physical slot (1–30) in the modular SLC chassis or fixed SLC expansion chassis where the DCM is installed. This address does not need to match the logical rack address of the PLC I/O instruction.
The word address refers to the word number (0–7) of the slot being addressed. The maximum number of SLC I/O words that a DCM can be assigned is 8.
The bit address is the bit within the word being addressed. Bits are numbered 0–15 (decimal) for the SLC and 0–17 (octal) for the PLC. Outputs from the SLC output image are inputs to the supervisory processor input image table. Likewise, outputs from the supervisory processor output image table are inputs to the SLC image table.
As noted, if the supervisory processor is a PLC the I/O image bits are octal and SLC bits are decimal. While the addresses are different, the position of the bit in the SLC word must match the position of the bit in the PLC word.
The following diagrams show this relationship.
3–3
Chapter 3
Addressing
I/O Image Tables
PLC to DCM/SLC
DCM/SLC configuration: Logical Rack Address = 1
Physical Slot Number = 1
Logical I/O Group = 0
Full Logical Rack
Decimal
Octal
PLC Output Image Table
15 14 13 12 11 10
17 16 15 14 13 12
9 8
11 10
7 6 5 4 3 2 1 0
7 6 5 4 3 2 1 0
DCM Input Image Table SLC Input Image Table
Decimal
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
Decimal
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
O:011/10 I:1.1/8
O = Output
01 = Logical Rack
1 = Logical I/O Group
10 = Bit (octal)
I = Input
1 = Physical DCM Slot
1 = Word
8 = Bit (decimal)
DCM/SLC to PLC
DCM/SLC configuration: Logical Rack Address = 1
Physical Slot Number = 1
Logical I/O Group = 0
Full Logical Rack
Decimal
Octal
PLC Input Image Table
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0
DCM Output Image Table
Decimal
15 14 13 12 11 10 9 8
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
SLC Output Image Table
7 6 5 4 3 2 1 0
Decimal
15 14 13 12 11 10 9 8
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
7 6 5 4 3 2 1 0
I:016/2 O:1.6/2
I = Input
01 = Logical Rack
6 = Logical I/O Group
2 = Bit (octal)
O = Output
1 = Physical DCM Slot
6 = Word
2 = Bit (decimal)
3–4
Image Mapping
Chapter 3
Addressing
An image map is a diagram showing how the scanner image is mapped into the image of multiple adapters. The following table and illustration show how an example PLC output image is mapped into the image of multiple
SLC processors through the DCM.
PLC Scanner Output Image
O:011/10 Starting Group 0
(Rack 01, Group 1, Bit 10 octal)
O:021/3
Starting Group 0
(Rack 02, Group 1, Bit 3 octal)
O:025/13 Starting Group 2
(Rack 02, Group 5, Bit 13 octal)
To: DCM
→
1
→
→
2
3
SLC Input Image
I:1.1/8
(Slot 1, Word 1, Bit 8 decimal)
I:1.1/3
(Slot 1, Word 1, Bit 3 decimal)
I:2.3/11
(Slot 2, Word 3, Bit 11 decimal)
Each row in the table represents the address of a data bit being transferred from the PLC scanner output image to the SLC input image via three different DCMs. The figure on the next page illustrates this data transfer.
Appendix B contains a worksheet designed to help you work out your DCM
system addressing. Use it if necessary to record I/O addresses.
3–5
Chapter 3
Addressing
Scanner Output Image
Bit Number:
Decimal
Octal
Group 0
Group 1
15 14
17 16
13 12 11 10 9 8 7 6 5 4
15 14 13 12 11 10 7 6 5 4
3
3
2
2
1
1
0
0
Reserved for Status Word
DCM 1
DCM 2
DCM 3
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7
Group 0
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7
Reserved for Status Word
Reserved for Status Word
Supervisory SLC or
PLC Processor
O:011/10
(Rack 1, Group 1, Bit 10 Octal)
O:021/2
(Rack 2, Group 1, Bit 3 Octal)
O:025/13
(Rack 2, Group 5, Bit 13 Octal)
RIO Link
Supervisory SLC or PLC
Remote I/O Scanner
SLC 1 Input Image for DCM 1
Bit Number: Decimal
15 14 13 12 11 10 9 8
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
7 6 5 4 3 2 1 0
I:1.1/8
(Slot 1, Word 1, Bit 8 Decimal)
Distributed SLC
Processor 1
DCM 1
Module 1 Configured As:
Rack Address 1
I/O Group 0
Slot Number 1
Rack Size Full
SLC 2 Input Image for DCM 2
15 14 13 12 11 10 9 8
Bit Number: Decimal
7 6 5 4
Reserved for Status Word
Word 0
Word 1
3 2 1 0
I:1.1/3
(Slot 1, Word 1, Bit 3 Decimal)
Distributed SLC
Processor 2
DCM 2
Module 2 Configured As:
Rack Address 2
I/O Group 0
Slot Number 1
Rack Size 1/4
SLC 3 Input Image for DCM 3
Bit Number: Decimal
15 14 13 12 11 10
Word 0
9 8 7 6 5 4
Reserved for Status Word
3 2 1
Word 1
Word 2
Word 3
0
I:1.3/11
(Slot 2, Word 3, Bit 11 Decimal)
Distributed SLC
Processor 3
DCM 3
Module 3 Configured As:
Rack Address 2
I/O Group 2
Slot Number 2
Rack Size 1/2
3–6
DIP Switches
Chapter
4
Module Configuration
This chapter provides DIP switch setting information for the DCM. Topics include:
•
DIP switches
•
DIP switch 1 settings
•
DIP switch 2 settings
To configure the DCM for your application, you must set the DIP switches.
These switches enable the DCM to properly interpret the RIO system addressing. The DCM has two banks of DIP switches mounted on its circuit board. Each bank contains eight switches. The default settings are shown below.
Starting I/O Group Number
Rack Address
SW1
Reserved
Rack Size
Last Rack
Clear On Fault
Data Rate
SW2
DIP Switch 1
(SW1)
DIP Switch 2
(SW2)
4–1
Chapter 4
Module Configuration
DIP Switch 1 Settings
Starting I/O Group Number (SW1-7 and SW1-8)
The starting I/O group number is the first word assigned to the DCM from the scanner’s image table. The starting I/O group number must be an even number from 0 to 6 and is dependent upon whether the DCM has been configured as a full, 3/4, 1/2, or 1/4 rack. The first word transferred is always the status word for the DCM.
Rack Size
1/4 Logical Rack
1/2 Logical Rack
3/4 Logical Rack
Full Logical Rack
Number of RIO Words Transferred
1 Status and 1 Data
1 Status and 3 Data
1 Status and 5 Data
1 Status and 7 Data
Total Words
2
4
6
8
Reference the table below to set the starting I/O group number.
Starting I/O Group Number
0
2
4
6
SW1-7
ON
ON
OFF
OFF
SW1-8
ON
OFF
ON
OFF
Valid Rack Configuration
All
3/4, 1/2, 1/4
1/2, 1/4
1/4
Starting Group 0
Starting Group 2
Starting Group 6
Example of different starting groups:
Bit Number:
Octal
17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0
Decimal
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Group 0, Word 0
Group 1, Word 1
R R S T A T U S W O R D
S T A T U S W O R D
Group 2, Word 2
Group 3, Word 3
Group 4, Word 4
Group 5, Word 5
Group 6, Word 6
Group 7, Word 7
S T A T U S W O R D
DCM 1 Rack Size
= 1/4 Rack
DCM 2 Rack Size
= 1/2 Rack
DCM 3 Rack Size
= 1/4 Rack
In the above image map example, selecting I/O Group Number 2 instructs the scanner to address Word 2 as the beginning of DCM 2 image. In this example, a half rack is selected for DCM 2 (using SW2 switches 5 and 6). Since Word 2 is the first word assigned, it becomes the Status Word.
4–2
Chapter 4
Module Configuration
Rack Address (SW1-1 through SW1-6)
The rack address refers to the logical rack number from the scanner image that contains a particular DCMs image.
The table on page 4–4 gives the switch settings that define possible rack
address choices for all scanners. To use this table, first determine which of the following categories applies to your scanner:
•
PLC-2, mini PLCs, PLC-2/30 with 1772-SD, SD2 remote scanner
•
PLC-3 and PLC-5/250 processors. (This category includes those with built-in scanners, as well as the following without built-in scanners: catalog numbers 1775-54A, -54B, -S5, -SR, -SR5 and 5250-RS.)
•
PLC-5/11, PLC-5/15, PLC-5/20, PLC-5/25, PLC-5/30, PLC-5/40, or
PLC-5/60 and 1771-SN. (This category includes all smaller in-rack processors and standalone scanners that have local and remote I/O and begin rack addressing at rack 1.)
•
SLC-5/02 (or above) with 1747-SN scanner
After determining which category applies to your DCM application:
1. Find the column for the scanner used in your application.
2. Go down the column to the rack address that you assigned to the DCM.
3. Use the switch settings in the right-most columns of the table that correspond to your rack address.
4–3
Chapter 4
Module Configuration
33
34
31
32
26
27
30
23
24
25
20
21
22
40
41
42
43
44
35
36
37
11
12
13
6
7
10
16
17
14
15
3
4
5
1
2
Use this table to set SW1 – switches 1 through 6.
1747-
SN
0
PLC-
2
1
PLC-
3
Logical Rack Number (Octal)
PLC-
5/15
PLC-
5/25
PLC-
5/40
0 – – –
PLC-
5/60
–
PLC-
5/250
0
1
ON
1
2
3
2
3
4
5
6
7
1
2
3 3
4
5
6
7
1
2
11
12
13
6
7
10
16
17
14
15
3
4
5
1
2
11
12
13
6
7
10
16
17
14
15
3
4
5
1
2
23
24
25
26
27
20
21
22
33
34
31
32
26
27
30
35
36
37
23
24
25
20
21
22
11
12
13
6
7
10
16
17
14
15
3
4
5
1
2
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
2
Switch Number (SW1)
3 4 5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
ON
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
ON
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
Continued on next page.
6
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
4–4
Chapter 4
Module Configuration
1747-
SN
PLC-
2
77 77
71
72
67
70
64
65
66
61
62
63
56
57
60
73
74
75
76
77
47
50
51
PLC-
3
45
46
54
55
52
53
PLC-
5/15
77
PLC-
5/25
PLC-
5/40
77 77
PLC-
5/60
PLC-
5/250
77 77
5
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
3 4
ON
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF OFF
Reserved
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
6
OFF
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
4–5
Chapter 4
Module Configuration
DIP Switch 2 Settings
Rack Size (SW2-5 and SW2-6)
The logical rack size allocates image space in the scanner for each DCMs I/O data. The DCM allows 1/4, 1/2, 3/4, and full rack addressing. SW2 switches
5 and 6 define the rack size.
Rack Size
1/4 Logical Rack
1/2 Logical Rack
3/4 Logical Rack
Full Logical Rack
SW2-5
ON
ON
OFF
OFF
SW2-6
ON
OFF
ON
OFF
Important: The DCM image cannot cross logical rack boundaries.
Therefore, as an example, configuring the module for 1/2 logical rack with starting group 6 will cause a configuration
error. Refer to Starting I/O Group Number on page 4–2.
Last Rack (SW2-4)
Switch 4 of SW2 must be set to the OFF position if the DCM shares its logical rack with at least one other adapter and has been assigned the highest
I/O group number in that logical rack.
Last Rack
Yes
SW2-4
OFF
No ON
Remote I/O Scanner
Direct Communications Module 1
Module 1 Configured As:
Logical Rack Address 1
I/O Group 0
Module Rack Size 1/4
Logical
Rack 1
Decimal
Bit Number:
Octal
Group 0, Word 0
Module 1
Group 1, Word 1
Module 2
Module 3
Module 4
Group 2, Word 2
Group 3, Word 3
Group 4, Word 4
Group 5, Word 5
Group 6, Word 6
Group 7, Word 7
SLC Output Image (to the PLC)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0
Module 4 is the last device in the logical rack.
Because Module 4 is the last RIO adapter in a logical rack shared by other adapter(s),
SW2 switch 4 must be in the OFF position.
4–6
Module 2 Configured As:
Logical Rack Address 1
I/O Group 2
Module Rack Size 1/4
Module 3 Configured As:
Logical Rack Address 1
I/O Group 4
Module Rack Size 1/4
Module 4 Configured As:
Logical Rack Address 1
I/O Group 6
Module Rack Size 1/4
Chapter 4
Module Configuration
Clear On Fault (SW2-3)
!
ATTENTION: Before setting SW2-3 to ON, make sure that holding all DCM input bits in their last state, in the event a communication error occurs, does not create an unsafe condition in the distributed SLC processor.
Clear On Fault
Yes
No
SW2-3
OFF
ON
Turn switch to OFF position if you want the DCM to clear and hold clear all data bits in its input image table, in the event of an RIO communication failure or when the supervisory processor enters Program/Test/Fault Mode.
Status bits will not be cleared.
Turn switch to ON position if you want the DCM to hold all input data bits in their last state when an RIO communication failure occurs or when the supervisory processor enters Program/Test/Fault Mode.
Data Rate (SW2-1 and SW2-2)
Data Rate
57.6K baud
115.2K baud b
SW2-1
ON
ON
OFF
OFF
SW2-2
ON
OFF
ON
OFF
Cable Length (Belden 9463)
3048 meters (10,000 feet)
1524 meters (5,000 feet) r f
4–7
Compliance to European
Union Directives
DCM Installation
Chapter
5
Installation and Wiring
This chapter explains how to install the DCM into the SLC chassis and provides information about terminal wiring. Topics include:
•
DCM installation
• network wiring
If this product has the CE mark it is approved for installation within the
European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file:
•
EN 50081-2
EMC – Generic Emission Standard, Part 2 – Industrial Environment
•
EN 50082-2
EMC – Generic Immunity Standard, Part 2 – Industrial Environment
This product is intended for use in an industrial environment.
Installation procedures for this module are the same as for any other discrete
I/O or specialty module. Refer to the illustration on page 5–2 to identify
chassis and module components listed in the procedures below.
!
ATTENTION: Disconnect power before attempting to install, remove, or wire the DCM.
Important: Make sure you have set the DIP switches properly before installing the DCM.
Before installation make sure your modular SLC power supply has adequate reserve current capacity. The DCM requires
360mA @ 5 volts. Each Fixed SLC 500 controller can support up to one DCM in a 2-slot expansion chassis, depending on which I/O module is in the second slot. Refer to the Discrete
I/O Modules Product Data, Publication Number 1746-2.35.
5–1
Chapter 5
Installation and Wiring
Installation
1. Disconnect power.
2. Align the full-sized circuit board with the chassis card guides. The first slot (slot 0) of the first rack is reserved for the CPU.
3. Slide the module into the chassis until the top and bottom latches are latched.
4. Attach the RIO link cable to the connector on the front of the module behind the door.
5. Insert the cable tie in the slots.
6. Route the cable down and away from module, securing it with the cable tie.
7. Cover all unused slots with the Card Slot Filler, Catalog Number 1746-N2.
Module Release
Card Guide
...
19627
Cable Tie
Removal
1. Disconnect power.
2. Press the releases at the top and bottom of the module and slide the module out of the chassis slot.
3. Cover all unused slots with the Card Slot Filler, Catalog Number
1746-N2.
5–2
Chapter 5
Installation and Wiring
Network Wiring
Using Extended
Node Capability
A 1/2 watt terminating resistor must be attached across line 1 and line 2 of the connectors at each end (scanner and last physical device) of the network.
The size of the resistor depends upon the baud rate and extended node capability, as shown below:
Baud Rate
All Baud Rates
57.6K baud
115.2K baud
230.4K baud
Terminating Resistor Size
82
W 1/2 Watt
150
W 1/2 Watt
150
W 1/2 Watt
82
W 1/2 Watt
Maximum Cable Distance
(Belden 9463)
10,000 feet at 57.6K baud
5,000 feet at 115.2K baud
2,500 feet at 230.4K baud
3048 meters (10,000 feet)
1524 meters (5,000 feet)
762 meters (2,500 feet)
Terminating
Resistor
RIO Scanner
Line 1 – Blue
Shield – Shield
Line 2 – Clear
DCM
FAULT
COMM
RIO Link
Connector
CONFIGURATION
RACK ADDR
RACK SIZE
1/4 1/2 3/4 1
FIRST I/O GROUP
0 2 4 6
DATA RATE (K B/S)
57.6 115.2 230.4
LINE 1 _______
SHIELD ______
LINE 2 _______
I/O
GROUP
(LSB)
RACK
ADDRESS
(MSB)
X
X
RACK
SIZE
LAST RACK
CLR ON FLT
DATA
RATE
1747-DCM
Direct Communication Module
Line 1 – Blue
Shield – Shield
Line 2 – Clear
1747–DCM
1747-DCM
Direct Communication Module
Line 1 – Blue
Shield – Shield
Line 2 – Clear
Terminating
Resistor
5–3
Overview
Chapter
6
Programming
This chapter shows you how to program ladder logic in the supervisory processor/scanner and the distributed SLC to transfer data via the DCM.
Topics include:
• overview
• programming examples
• status words
• applications using status word bits
Both the supervisory processor/scanner and the distributed SLC transfer data to and from the DCM automatically via their I/O and the RIO scan. The
DCM, as a common memory site for both supervisory and distributed processors, has two addresses; one for the supervisory processor/ scanner and one for the SLC. The supervisory processor/scanner address is the DCM logical rack address as set by DCM SW-1 switches 1 through 6.
The distributed SLC address is determined by the slot where the DCM is physically installed.
The supervisory processor/scanner and distributed SLC addresses can be different; however, the bit position part in each word must be the same.
In the programming examples on the following page, an Examine If Open contact similar to the one shown below is used in each output rung:
I:4.0
]/[
08
This instruction checks that the Logical OR bit of the status word is false.
Whenever any of the status word bits (except the User Status Flag bit) is set, it is indication that a condition has occurred in your logic program that may require inspection. If this happens you would normally want to inhibit some outputs by using a ladder logic instruction. Using an Examine If Open (XIO) instruction examining the Logical OR bit (word 0, bit 8 for SLC; word 0, bit
10 for PLC) is the easiest way of doing this.
6–1
Chapter 6
Programming
Programming Examples
The following programming examples are typical of applications using the
DCM. In each example the portion of the scanner image assigned to the
DCM is logical rack 2, starting group 0, 1 full rack, and is located in SLC physical slot 3.
6–2
PLC
SLC
Input
Physical Slot # 0 1 2 3 4 5 6
PLC
Processor
Physical Input into PLC – Physical Output from SLC
RIO
Scanner
RIO
DCM
SLC
Processor Output
IN
I:000
] [
00
O:021
( )
00
I:3.1
] [
00
I:3.0
]/[
08
Logical Or Status Bit
O:1.0
( )
00
OUT
In the example above, PLC output O:021/00 controls the (on/off) status of
DCM input I:3.1/00.
I:3.1/00 is used as a conditional ladder logic along with the Logical OR input status bit to control SLC output O:1.0/00.
Chapter 6
Programming
Input
SLC
Processor
Physical Input into SLC – Physical Output from PLC
DCM
RIO
RIO
Scanner
PLC
Processor
Output
ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ
SLC
IN ] [
( )
ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ 00
00
ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ
ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ
I:021
I:020
O:001
PLC ] [ ]/[
( ) OUT
00 10
00
Logical Or Status Bit
PLC
SLC
Input
PLC
Processor
Physical Input into Both PLC and SLC (Logical AND) – Physical Output from SLC
RIO
Scanner
RIO
DCM
SLC
Processor
Input
Output
IN
I:000
] [
00
IN
I:2.0
] [
00
O:021
( )
00
I:3.1
] [
00
I:3.0
]/[
08
Logical Or Status Bit
O:1.0
( )
00
OUT
6–3
Chapter 6
Programming
Input
First
SLC
Processor
Physical Input into First SLC – Physical Output from Second SLC
For this example the second SLC has a logical PLC rack address of 3 and an
SLC slot address of 4.
PLC with
RIO scanner
DCM
RIO
DCM
Second
SLC
Processor
Output
SLC
PLC
IN
I:2.0
] [
00
(No physical input into the PLC)
O:3.1
( )
00
I:4.1
] [
00
I:4.0
]/[
08
Logical Or Status Bit
O:1.0
( )
00
I:021
] [
00
I:020
]/[
10
Logical Or Status Bit
O:031
( )
00
OUT
When transmitting data from a PLC to an SLC, if the Clear On Fault (CLR
ON FLT) is active (switch is OFF), the instruction to examine the Logical
OR bit of the status word can be omitted as long as clearing the DCM input image table puts SLC outputs into a safe state for the specific application.
6–4
Chapter 6
Programming
Status Words
The first word of the DCM I/O image is the status word. The status word indicates the status of communication and data between the RIO scanner and the DCM. Depending on what logical rack size the DCM is configured for, it will transfer the following number of I/O words:
Rack Size
1/4 Logical Rack
1/2 Logical Rack
3/4 Logical Rack
Full Logical Rack
Number of RIO Words Transferred
One (plus one Status Word)
Three (plus one Status Word)
Five (plus one Status Word)
Seven (plus one Status Word)
Total Words
2
4
6
8
The figure below shows how I/O bits are transferred from the scanner to two
DCMs, each configured as a 1/2 logical rack device.
Bit Number: Decimal
Status Word:
Word 0
Word 1
Data Words:
Word 2
Word 3
Status Word:
Word 4
Word 5
Data Words:
Word 6
Word 7
15 14 13 12 11 10 9 8
ÍÍ ÍÍ ÍÍ Í
R
R
R
R R R
ÍÍ ÍÍ ÍÍ Í
7 6
R R
R
R
ÍÍ ÍÍ ÍÍ Í
R
R R R R R
ÍÍ ÍÍ ÍÍ Í
5 4
R R
3 2 1
R R R R
0
R R R R R R
DCM 1
1/2 Rack Device
DCM 2
1/2 Rack Device
R = Reserved for future use
RIO Scanner Input Status Word Examination (Decimal)
This is the input status word sent in a data transfer from a supervisory processor/RIO scanner to a DCM. These bits can be used as conditional logic in your SLC program to flag DCM, RIO, or supervisory processor system errors and/or status. Scanner status bits not defined below are reserved for future use.
DCM
ÉÉ ÉÉÉ ÉÉ ÉÉ É ÉÉ ÉÉ É ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉÉ ÉÉ ÉÉ ÍÍ ÉÉ ÉÉ ÉÉ ÉÉ É ÉÉ ÉÉÉ ÉÉ ÉÉÉ ÉÉ ÉÉ ÉÉÉ ÉÉ
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
ÉÉ ÉÉÉ ÉÉ ÉÉ É ÉÉ ÉÉ É ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉÉ ÉÉ ÉÉ ÍÍ ÉÉ ÉÉ ÉÉ ÉÉ É ÉÉ ÉÉÉ ÉÉ ÉÉÉ ÉÉ ÉÉ ÉÉÉ ÉÉ
ÉÉ
Reserved Bits
ÉÉ
Status Bits
Logical OR of other Status Word bits. It is set when any other bit is set. It is cleared when all other bits are cleared.
Program/Test/Fault Mode bit. This bit is set whenever the supervisory processor is in the Program, Test, or Fault Mode.
DCM Initialization bit. This bit is set when the DCM is in its power-up initialization.
It will be cleared when valid data is received from the supervisory processor output image table.
Communication Error bit. This bit is set whenever the DCM detects an RIO communication error. It is cleared when the Communication error is cleared.
6–5
Chapter 6
Programming
DCM/SLC Output Status Word Examination (Octal)
This is the output image status word sent in a data transfer from a DCM to a supervisory processor/scanner. These bits can be used as conditional logic in your supervisory processor program to flag DCM or SLC system errors and/or status. DCM/SLC status bits not defined below are reserved for future use.
Both the decimal and octal bit addresses are shown below to assist you in programming your supervisory (PLC) processor and distributed SLC processor.
SLC 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
ÉÉ ÉÉÉ ÉÉ É ÉÉ ÉÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉÉ ÉÉ ÉÉ É ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ É É ÉÉÉ ÉÉ ÉÉ ÉÉÉ ÉÉ ÉÉ ÉÉÉ
PLC
ÉÉ ÉÉ ÉÉÉ ÉÉ ÍÍ ÍÍ ÍÍ ÍÍ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉÉ ÉÉ ÉÉ ÉÉ ÉÉÉ ÉÉ ÉÉ É ÉÉ ÉÉ É ÉÉ É ÉÉÉ ÉÉ
17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0
ÉÉ ÉÉ ÉÉÉ ÉÉ ÍÍ ÍÍ ÍÍ ÍÍ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉÉ ÉÉ ÉÉ ÉÉ ÉÉÉ ÉÉ ÉÉ É ÉÉ ÉÉ É ÉÉ É ÉÉÉ ÉÉ
ÉÉ
Reserved Bits
ÉÉ
Status Bits
Logical OR of Status Word bits 11 and 12 (9 and 10 for
SLC). It is set when either 11 or 12 (9 or 10) is set. It is cleared when 11 or 12 (9 or 10) is cleared.
Program/Test/Fault Mode bit. This bit is set whenever the SLC controlling the DCM is in the Program, Test, or
Fault Mode.
DCM Output Data Invalid bit.
➀
This bit is set when DCM output image data could be invalid.
User Status Flag bit. This status bit is available for you to use in your application.
➀
Always use the DCM Output Data Invalid bit to determine the validity of SLC data sent from the DCM to the scanner. If you use the Program/Test/Fault Mode bit you may incorrectly receive an indication that the SLC data being sent from the DCM to the scanner is valid. This occurs because for a brief period after the
Program/Test/Fault mode bit is cleared the data sent from the DCM to the scanner will not be valid.
6–6
Chapter 6
Programming
Applications Using I/O Status
Word Bits
You can use the status bits in your ladder logic to monitor various conditions of the remote processor and the RIO network. Some examples for using the status word bits are given here. Each of the examples shows how ladder logic rungs could be programmed in the SLC processor to respond to the condition of a status bit from the RIO scanner.
Important: The application examples assume the portion of the scanner image assigned to the DCM is logical rack 2, starting group 0, 1 full rack, and is located in SLC physical slot 3.
RIO Scanner Status Word
Using the Program/Test/Fault Mode Bit
When the RIO scanner’s supervisory processor is in Program, Test, or Fault
Mode, its outputs are automatically inhibited (reset off) unless Hold Last
State is used. However, outputs sent to the DCM (DCM inputs) are not automatically inhibited. If you want to inhibit any one SLC output controlled by a DCM input, you can use an Examine If Open (XIO) instruction addressed to the Program/Test/Fault Mode bit (I:3.0/9 in the example below). This assumes an SLC output is being driven by an input
(I:3.1/0) from the scanner to the DCM, as shown below.
SLC Rung to Monitor
RIO Scanner Status Bit 09
DCM Conditional Program/Test/Fault SLC
I:3.1
] [
00
Input
I:3.0
]/[
09
Status Bit
O:1.0
( )
00
Output
If you want to clear the DCM’s entire input image (data from the RIO scanner when the RIO scanner’s supervisory processor is in Program/Test/
Fault Mode), you can set the DCM Clear On Fault DIP switch to the OFF
position. Please refer to chapter 4, Module Configuration, for more
information on this DIP switch.
DCM/SLC Output Status Word
Using the Data Invalid Bit
Whenever the distributed SLC leaves Program/Test/Fault Mode and enters
Run Mode, there is a time period after the Program/Test/Fault Mode bit is cleared when the data sent from the DCM/SLC to the RIO scanner is invalid.
For this reason, the Program/Test/Fault Mode bit should not be used by the
RIO scanner’s supervisory processor to determine the validity of data sent from the DCM. Instead, both processors’ programs should use the DCM output Data Invalid bit (12 octal).
6–7
6–8
Chapter 6
Programming
To ensure that the DCM output Data Invalid bit is cleared (signifying to the
RIO scanner’s supervisory processor that data is valid), the SLC ladder logic rung shown below must be included as the last rung in your SLC ladder logic program.
SLC Rung addresses bit 10 (decimal);
RIO Scanner ’s supervisory processor receives bit 12 (octal).
O:3.0
(U)
10
The RIO scanner’s supervisory processor ladder logic program should use the DCM output Data Invalid bit to condition any supervisory processor outputs whose state is dependent upon valid data from the DCM/distributed
SLC. An example of a PLC-5 processor rung that requires this conditioning is shown below.
PLC-5 Rung
SLC addresses bit 10 (decimal);
PLC receives bit 12 (octal).
I:021
] [
00
I:020
]/[
12
O:000
( )
00
This rung uses data from the DCM (word 1, bit 0 PLC address I:021/00) to energize a PLC-5 output: bit 0, of rack 0, module group 0. It is conditioned with the Data Invalid bit. By using the DCM output Data Invalid bit in this example, the PLC-5 will not energize the output shown above unless the data received from the SLC/DCM is valid.
Using the User Status Flag Bit
This status bit (13) is available for your particular application. It is cleared on powerup and thereafter is never operated on by the DCM. After powerup this bit is only set (1) or cleared (0) by your SLC ladder logic program.
A typical application using this bit would be to inform the RIO scanner’s supervisory processor that the SLC is disabling the slot where the DCM is located. If the DCM slot is disabled while the SLC is in the Run Mode, data sent to the RIO scanner will be last state data (invalid). Without using the
User Status Flag bit, no indication that data is not being updated would be sent to the RIO scanner (that is, neither the Program/Test/Fault Mode bit nor the Invalid Data bit would be set). If your SLC ladder logic program sets the
User Status Flag bit prior to disabling the DCM slot, the supervisory processor can use this bit in its ladder logic where appropriate.
!
ATTENTION: Make certain that you have thoroughly examined the effects of disabling the DCM slot before doing so in your application.
An example of how rungs might be programmed in the two processors to indicate disabling of the DCM slot is shown on the next page.
Chapter 6
Programming
SLC Rungs
Set User Status Flag Bit
Condition(s)
➀
Disable DCM
Enable DCM
Clear User Status Flag Bit
➀
Condition(s)
Condition(s)
➁
Condition(s)
➁
User Status Flag Bit
O:13.0
(L)
11
➂
IOM
IMMEDIATE OUT w MASK
Slot 0:3.0
Mask 0800
S2:11
(U)
➃
03
S2:11
➃
(L)
03
O:3.0
(U)
11
➂
➀
Condition(s) to set User Status Flag bit is the same condition(s) to disable the DCM slot. When setting the
User Status Flag bit, an Immediate I/O (IOM) instruction must be used.
➁
Condition(s) to clear User Status Flag bit is the same condition(s) to enable the DCM slot.
➂
The SLC addresses this bit as bit 11 (decimal); the PLC-5 receives this bit as bit 13 (octal).
➃
S2:11-S2:12 – These two words are bit mapped to represent the 30 possible I/O slots in an SLC system.
S2:11/0 represents I/O slot 0 up through S2:12/14 which represents slot 30. S2:12/15 is unused.
After programming the SLC to set and clear the User Status Flag bit, this bit can be used to condition any PLC-5 output in this example whose state is dependent upon the data from the distributed SLC being valid.
PLC-5 Rung
I:021
] [
00
I:020
]/[
13
O:000
( )
00
The PLC-5 rung uses data from the DCM (word 1, bit 0) to energize PLC-5 output 0. It is conditioned on the User Status Flag bit being cleared. If the
SLC is programmed to set the User Status Flag bit prior to disabling the
DCM slot, the PLC-5 will never energize output 0 when data from the SLC is invalid. For more information on how to enter PLC ladder logic, see your
PLC-5 programming manual.
6–9
Chapter 6
Programming
RIO Scanner Input Status and DCM/SLC Output Status
Using the Logical OR Bit
Whenever any of the status word bits (except the User Status Flag bit) are set, the Logical OR bit is set. Using an Examine If Open (XIO) instruction examining the Logical OR bit (word 0, bit 8 for SLC; word 0, bit 10 for
PLC-5) in your ladder logic, you could inhibit any outputs or processors when this bit is set.
SLC Rung to Monitor
PLC-5 Status Bit 08
I:3.1
] [
00
I:3.0
]/[
08
O:1.0
( )
00
6–10
DCM Status Indicators
Chapter
7
Troubleshooting
This chapter shows you how to identify and correct errors that you may encounter using LEDs. The topics include:
•
DCM status indicators
• troubleshooting using the FAULT LED (red)
• troubleshooting using the COMM LED (green)
Two LEDs indicate the status of the DCM.
DCM
FAULT
COMM
Red
Green
Troubleshooting Using the
FAULT LED (Red)
If LED is:
On
Blinking
Cause:
Internal Fault
Configuration Error
Corrective action:
Cycle power to the I/O chassis containing the DCM.
Replace DCM if red LED remains lit after powerup.
Check that the DIP switch settings are correct. Make sure that I/O group and rack size settings are compatible.
➀
Also see that the setting for rack address is correct. Refer
to chapter 4, Module Configuration, for help with DIP
switches.
No action required.
Off
Normal State
➀
The DCM cannot cross logical rack boundaries. Therefore, as an example, configuring the module for 1/2 logical rack with starting group 6 will cause a configuration error.
7–1
Chapter 7
Troubleshooting
Troubleshooting Using the
COMM LED (Green)
If LED is:
On
Blinking
Off
Cause:
Normal State
RIO scanner’s processor in Program/Test Fault
Mode
RIO scanner’s processor not connected to scanner
RIO scanner’s processor rack inhibited between RIO scanner’s
No action required.
Corrective action:
Check for RIO scanner’s processor error, correct condition, and cycle power to DCM.
Check that the scanner is properly installed in rack (RIO scanner’s processor–2, #3).
Check RIO scanner’s processor rack integrity, correct any problem, and cycle power to DCM.
Check that the baud rate of the DCM matches the baud rate of the scanner.
Check cable connections from the RIO scanner’s processor or scanner to the DCM.
Check that the DCM connector is properly installed.
7–2
Chapter
8
Application Examples
This chapter provides and examines two applications of the DCM.
• basic example
• supplementary example
Basic Example
Rack 1
Input Switch
In the following application, the 1747-DCM in the remote rack 2 will monitor the 1747-SN data from the local rack 1. The program examples in both local and remote rack CPUs consist of 1 rung each. When input I:1/0 is enabled in the local rack, the output O:3.1/0 condition is transferred to the
1747-DCM input image via the 1747-SN output image. This condition enables O:2/0 in the remote rack output card.
Rack 2
ÉÉ
É É ÉÉ
É É ÉÉ
É É ÉÉ
É É ÉÉ
É É ÉÉ
É É ÉÉ
ÉÉ
= slot not used
ÉÉ
RIO
(Belden 9463)
1747-SN Module Configuration
➀
Baud Rate =
G-file Size =
57.6K baud
3 words
G-File
Word 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Reserved
Word 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
= Starting Address 0
Word 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
= 1/4 Rack Size
➀
See SN manual for further details on configuration.
8–1
Chapter 8
Application Examples
DCM configuration:
Rack Address = 1
I/O Group =
Baud Rate =
0
57.6K baud
Clear On Fault = no
Last Rack =
Rack Size = no
1/4
DIP Switch Settings
Switch 1
1 2 3 4 5 6
ON X X X X X
OFF X
Switch 2
7 8 1 2 3 4 5 6
X X X X X X X X
7 8
= Not used
System Configuration for Rack 1
Amount
1
1
1
1
1
1
Device
Power Supply
SLC 5/02 Processor
4-Slot Rack
AC Input, 16 Inputs
Relay Output, 16 Outputs
Scanner
Catalog Number
1746-P2
1747-L524
1746-A4
1746-IA16
1746-OW16
1747-SN
System Configuration for Rack 2
Amount
1
1
1
1
1
Device
Power Supply
SLC 5/01 Processor
4-Slot Rack
Relay Output, 16 Outputs
DCM
Catalog Number
1746-P2
1747-L511
1746-A4
1746-OW16
1747-DCM
8–2
Chapter 8
Application Examples
Image Table Configuration
Output Image
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
SN
O:3.1/0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Input Image
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
DCM
I:1.1/0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Program Listing
When I:1/0 is set, enabling O:3.1/0 in the SN output image, the data is sent to the input image of the DCM I:1.1/0. The output in rack 2 is then set to output module O:2/0.
Rack 1, Program 1
I:1
] [
0
From Input Switch
O:3.1
( )
0
To SN Output
Word 1, Bit 0
Rack 2, Program 2
I:1.1
] [
0
From DCM Input
Word 1, Bit 0
O:2
( )
0
8–3
Chapter 8
Application Examples
Supplementary Example
In the following application, the PLC-5/15, via its integrated RIO scanner and the DCM, will monitor the analog data from an SLC 500. This case is unique in that the data to be monitored is twice what the DCM can transfer.
The program in the SLC 500 will multiplex the data into four, 4-word packets with a start and end of data word attached. The start and end of data word is also used to designate which module the data is coming from. This is also used by the PLC-5/15 to indicate that the data was transferred successfully.
RIO
(Belden 9463)
Module Configuration
PLC-5 configuration for scanner I/O status, inhibit bits:
S:27/0 =
*
S:27/1 =
S:27/2 =
S:27/3 =
* = Don’t care
0
1
1
DCM configuration:
Rack Address = 1
I/O Group = 0
Baud Rate = 57.6K baud
Clear on Faults = No
Last Rack =
Rack Size =
No
Full Rack
É
É
É
É
É
É
É
ÉÉ
= slot not used
ÉÉ
8–4
Chapter 8
Application Examples
DIP Switch Settings
ON
OFF
1 2 3
Switch 1
4 5
X X X X X
6
X
7 8 1 2 3
Switch 2
4
X X X X X X
5 6
X X
7 8
= Not used
System Configuration
Amount
1
1
1
2
2
1
Device
Power Supply
SLC 5/01 Processor
7-Slot Rack
Analog Input, 4 point
Analog Output, 4 point
DCM
Catalog Number
1746-P2
1747-L511
1746-A7
1746-NI4
1746-NO4I
1747-DCM
Image Table Configuration
DCM
O:1.7
O:4.0
O:4.1
O:4.2
O:4.3
O:5.0
O:5.1
O:5.2
O:5.3
O:1.0
O:1.1
O:1.2
O:1.3
O:1.4
O:1.5
O:1.6
Output Image
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Status Word to PLC-5 from SLC
Counter ACC word denotes module being read
Word 0 of analog module being read
Word 1 of analog module being read
Word 2 of analog module being read
Word 3 of analog module being read
Counter ACC word denotes module being read
Not used
NO4I word 0
NO4I word 1
NO4I word 2
NO4I word 3
NO4I word 0
NO4I word 1
NO4I word 2
NO4I word 3
8–5
Chapter 8
Application Examples
DCM
NI4
NI4
I:1.0
I:1.1
I:1.2
I:1.3
I:1.4
I:1.5
I:1.6
I:1.7
I:2.0
I:2.1
I:2.2
I:2.3
I:3.0
I:3.1
I:3.2
I:3.3
Input Image
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Status Word to SLC from PLC-5
Not used
Not used
Not used
Not used
Not used
Not used
Not used
NI4 word 0
NI4 word 1
NI4 word 2
NI4 word 3
NI4 word 0
NI4 word 1
NI4 word 2
NI4 word 3
Program Listing for 5/01
Processor File: MULTPLX1.ACH
Rung 0 sets the starting point of the C5:0 counter. This is done on the first scan of the program S:1/15
(first scan bit) and C5:0/DN (done bit 0) of the counter, ensuring that only the analog modules in slots 2 through 5 are read.
RUNG
2.0
C5:0
] [
DN
MOV
MOVE
Source
Dest
2
C5:0.ACC
S:1
] [
15
Rung 1 increments the C5:0 every 5.12 seconds. The value in the ACC is referenced to the slot that the
DCM will send the data from, starting at slot 2.
RUNG
2.1
S:4
] [
8
5.12 Seconds Time Bit
CTU
Countup
Counter
Preset
Accum
C5:0
6
0
8–6
Chapter 8
Application Examples
For rungs 2.2 through 2.5 the module number being monitored is shown above each example. For each rung, when SOURCE A = C5:0.ACC equals the value in SOURCE B = MODULE #, the rung moves the module number to word 1 of the DCM output file. This verifies the start of the data and the module number it’s coming from. Then it copies the four words of analog data to the DCM output words 2 through 5, followed by the module number at word 6 to indicate the end of data.
Module Number Monitored = 2
RUNG
2.2
EQU
EQUAL
Source A C5:0.ACC
Source B
0
2
MOV
MOVE
Source
Dest
C5:0.ACC
0
0:1.1
0
COP
COPY FILE
Source
Dest
Length
#I:2.0
#0:1.2
4
MOV
MOVE
Source
Dest
C5:0.ACC
0
0:1.6
0
RUNG
2.3
Module Number Monitored = 3
EQU
EQUAL
Source A C5:0.ACC
0
Source B 3
MOV
MOVE
Source
Dest
C5:0.ACC
0
0:1.1
0
COP
COPY FILE
Source
Dest
Length
#I:3.0
#0:1.2
4
MOV
MOVE
Source
Dest
C5:0.ACC
0
0:1.6
0
8–7
Chapter 8
Application Examples
RUNG
2.4
Module Number Monitored = 4
EQU
EQUAL
Source A C5:0.ACC
0
Source B 4
RUNG
2.5
Module Number Monitored = 5
EQU
EQUAL
Source A C5:0.ACC
Source B
0
5
<END>
MOV
MOVE
Source
Dest
C5:0.ACC
0
0:1.1
0
COP
COPY FILE
Source
Dest
Length
#I:4.0
#0:1.2
4
MOV
MOVE
Source
Dest
C5:0.ACC
0
0:1.6
0
MOV
MOVE
Source
Dest
C5:0.ACC
0
0:1.1
0
COP
COPY FILE
Source
Dest
Length
#I:5.0
#0:1.2
4
MOV
MOVE
Source
Dest
C5:0.ACC
0
0:1.6
0
8–8
Chapter 8
Application Examples
RUNG
2.0
Module Number Monitored = 2
Program Listing for PLC5/15
The following examples are for rungs 2.0 through 2.3. The module number being monitored is shown above the examples. For each rung, the first EQU monitors the module number and the start of the data transfer, while the second EQU monitors the module number and the end of the data transfer.
The COP then moves the four words of analog data to an integer file.
EQU
EQUAL
Source A
Source B
I:011
0
2
EQU
EQUAL
Source A
Source B
I:016
0
2
COP
COPY FILE
Source
Dest
Length
#I:012
#N7:0
4
RUNG
2.1
Module Number Monitored = 3
EQU
EQUAL
Source A
Source B
I:011
0
3
EQU
EQUAL
Source A
Source B
I:016
0
3
RUNG
2.2
Module Number Monitored = 4
EQU
EQUAL
Source A
Source B
I:011
0
4
EQU
EQUAL
Source A
Source B
I:016
0
4
COP
COPY FILE
Source
Dest
Length
#I:012
#N7:4
4
COP
COPY FILE
Source
Dest
Length
#I:012
#N7:8
4
RUNG
2.3
Module Number Monitored = 5
EQU
EQUAL
Source A
Source B
I:011
0
5
EQU
EQUAL
Source A
Source B
I:016
0
5
COP
COPY FILE
Source
Dest
Length
#I:012
#N7:12
4
<END>
8–9
Appendix
A
Specifications
This appendix provides the following module and system specifications.
• electrical specifications
• environmental specifications
• network specifications
It also discusses throughput time for the DCM.
Electrical Specifications
Backplane Current Consumption
Environmental Specifications
Operating Temperature
Storage Temperature
Humidity Rating
Agency Certification
(when product or packaging is marked)
360mA at 5V
0
°
C to 60
°
C (32
°
F to 140
°
F)
−
40
°
C to
+
85
°
C (
−
40
°
F to
+
185
°
F)
5% to 95% noncondensing
•
CSA certified
•
CSA Class I, Division 2
Groups A, B, C, D certified
•
UL listed
•
CE marked for all applicable directives
Network Specifications
Us n xten e
Baud Rate
57.6K baud
115.2K baud
230.4K baud
57.6K baud
115.2K baud
230.4K baud
Maximum Cable Distance
(Belden 9463)
10,000 feet at 57.6K baud
5,000 feet at 115.2K baud
2,500 feet at 230.4K baud
3048 meters (10,000 feet)
1524 meters (5,000 feet)
762 meters (2,500 feet)
82
W 1/2 Watt
1
82
Resistor Size
W 1
W 1/2 Watt
A–1
Appendix A
Specifications
Throughput Timing
Use the following steps to determine the maximum throughput time in your application.
1. Determine and record the PLC and SLC delay by following these instructions:
PLC
SLC
I/O circuit delay:
I/O scan time:
Program scan time:
+
+
+
+
PLC Delay:
=
SLC Delay:
=
2. Record the remote I/O delay:
Remote I/O delay:
3. Record the DCM delay. This should be <10 msec.:
DCM delay:
4. Using your recorded values above, determine the maximum throughput time for your application as shown below:
PLC Delay:
Remote I/O delay:
+
DCM delay:
+
SLC Delay:
+
Maximum throughput time:
=
A–2
Directions
Addressing Review
Appendix
B
DCM Addressing Worksheet
This appendix provides a worksheet for keeping track of the elements of each
I/O address for your system’s DCMs. Topics include:
• directions
• addressing review
In the table on the next page, enter the elements of each I/O address for each
DCM in your system. All DCM inputs and outputs are addressed with respect to the SLC.
Make sufficient copies of this worksheet to cover all DCMs in your system.
PLC Addresses
PLC Input Address
I:023/10
I = Input
02 = Logical Rack
3 = I/O Group
10 = Bit (octal)
PLC Output Address
O:017/10
O = Output
01 = Logical Rack
7 = I/O Group
10 = Bit (octal)
SLC Addresses
SLC Input Address
I:2.3/8
I = Input
2 = Physical Slot
3 = Word
8 = Bit (decimal)
SLC Output Address
O = Output
1 = Physical Slot
7 = Word
8 = Bit (decimal)
If you configure the DCM as:
1/4 Rack
1/2 Rack
3/4 Rack
Full Rack
Then:
1 data word (16 bits of I/O data) is transferred.
3 data words (48 bits of I/O data) are transferred.
5 data words (80 bits of I/O data) are transferred.
7 data words (112 bits of I/O data) are transferred.
O:1.7/8
Including the Status Word
Total transfer = 2 words
Total transfer = 4 words
Total transfer = 6 words
Total transfer = 8 words
B–1
Appendix B
DCM Addressing Worksheet
1/4
Logical
Rack
1/2
Logical
Rack
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
PLC Output
O:
O:
O:
O:
O:
O:
Rack #
DCM Input Image Table
I/O Group Bit (octal) SLC Input
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
Slot # Word Bit (decimal)
Continued on next page.
B–2
Appendix B
DCM Addressing Worksheet
3/4
Logical
Rack
Full
Logical
Rack
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
PLC Output
O:
O:
O:
O:
O:
O:
Rack #
DCM Input Image Table (continued)
I/O Group Bit (octal) SLC Input Slot #
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
Word Bit (decimal)
B–3
Appendix B
DCM Addressing Worksheet
1/4
Logical
Rack
1/2
Logical
Rack
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
PLC Input
I:
I:
I:
I:
I:
I:
Rack #
DCM Output Image Table
I/O Group Bit (octal) SLC Output
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
Slot # Word Bit (decimal)
Continued on next page.
B–4
Appendix B
DCM Addressing Worksheet
3/4
Logical
Rack
Full
Logical
Rack
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
I:
PLC Input
I:
I:
I:
I:
I:
I:
Rack #
DCM Output Image Table (continued)
I/O Group Bit (octal) SLC Output Slot #
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
O:
Word Bit (decimal)
B–5
Index
Direct Communication Module
User Manual
Numbers
A
adapter, 1–4 extended node capability, 1–4
interaction with scanners, 1–2 on RIO link as slave device, 1–2
addressing ladder logic instructions, 3–1
addressing worksheet directions, B–1
Allen-Bradley, P–4 contacting for assistance, P–4
application examples
using status word bits, 6–7 applications using status word bits, 6–7
Data Invalid bit in the SLC Status Word,
Program/Test/Fault Mode bit in the RIO
User Status Flag bit in the SLC Status
B
backplane current consumption, A–1
basic DCM application example, 8–1
baud rate
resistor, 2–4 specifications, 2–4, 5–3, A–1
Belden 9463 cable, maximum distance, 2–4,
chassis slot
contacting Allen-Bradley for assistance, P–4
D
Data Rate (SW2-1 and SW2-2), 4–7
DCM features, 1–1 hardware, 1–1 cable tie slots, 1–1
FAULT LED, 1–1 front, side and door labels, 1–1 self-locking tabs, 1–1
DCM installation and wiring, 5–1
DCM Output Data Invalid bit, 6–6
DCM status word bit examination (decimal)
DCM output data invalid bit, 6–6
determining maximum throughput time, A–2
I/O Group (SW1-7 and SW1-8), 4–2
Rack Addresses (SW1-1 through
Data Rate (SW2-1 and SW2-2), 4–7
Module Rack Size (SW2-5 and SW2-6),
C
cable distance, maximum, 2–4, 5–3, A–1
I–1
I–2
Index
Direct Communication Module
User Manual
E
electrical specifications, A–1
environmental specifications, A–1
European Union Directives Compliance, 5–1
Examine If Open instruction (XIO), 6–7, 6–10
examples
status word bit application, 6–7
supplementary DCM application, 8–4
extended node capability, 1–4 of scanners and adapters, 1–4 of the DCM, 1–4
F
I
I/O Group (SW1-7 and SW1-8), 4–2
image division configuration, scanner, 1–5
installation, getting started, 2–1
L
labels, front, side and door, 1–1
ladder logic instructions, addressing, 3–1
FAULT (red), 7–1 steady state, 7–1 troubleshooting using, 7–1
Logical OR bit, 6–5, 6–6, 6–10
G
green LED, troubleshooting using, 7–2
M
Module Rack Size (SW2-5 and SW2-6), 4–6
H
hardware features, 1–1 cable tie slots, 1–1
FAULT LED, 1–1 front, side and door labels, 1–1
RIO link connector, 1–1 self-locking tabs, 1–1 hardware overview, 1–1 hardware features, 1–1
Hold Last State, in status word applications,
N
P
PLC addresses, 3–2 bit address, 3–2
I/O group address, 3–2 rack address, 3–2
Index
Direct Communication Module
User Manual
PLC scanner output image, 3–5, 3–6
Program/Test/Fault Mode bit, 6–5, 6–6, 6–7
physical input into both PLC and SLC –
physical input into first SLC – physical
physical input into PLC – physical output
physical input into SLC – physical output
R
Rack Address (SW1-1 through SW1-6), 4–3
rack size
3/4 rack, 2–3, 4–6 full rack, 2–3, 4–6
number of data words transferred
red LED, troubleshooting using, 7–1
remote I/O
adapter, 1–2 communications link, 1–2
required tools and equipment, 2–1
RIO scanner status word bit examination
Logical OR of other status word bits, 6–5
Program/Test/Fault Mode bit, 6–5
S
scanner, image division, 1–4 logical groups, 1–4 logical racks, 1–4 scanner image division, 1–4
scanners number of physical and logical devices
SLC addresses, 3–3 bit address, 3–3 slot address, 3–3 word address, 3–3
electrical, A–1 environmental, A–1 network, A–1
status words, 1–6, 6–5 about the, 1–6
DCM status word bit examination (octal),
RIO scanner status word bit examination
supplementary DCM application example,
SW1-1 through SW1-6, DIP switch, Rack
SW1-7 and SW1-8, DIP switch, I/O Group,
SW2-1 and SW2-2, DIP switch, Data Rate,
SW2-3, DIP switch, Clear On Fault, 4–7
SW2-4, DIP switch, Last Rack, 4–6
I–3
I–4
Index
Direct Communication Module
User Manual
SW2-5 and SW2-6, DIP switch, Module Rack
data exchange between a PLC and SLC,
1–2 logical rack, 1–2 remote I/O analysis, 1–2
system configuration restriction factors,
using the COMM LED (green), 7–2
using the FAULT LED (red), 7–1
U
User Status Flag bit, 6–6, 6–8
T
temperature specifications, A–1 operating, A–1 storage, A–1
terminating resistor, size of, 5–3
W
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world’s leading technology companies.
Worldwide representation.
Argentina
•
Australia
•
Austria
•
Bahrain
•
Belgium
•
Brazil
•
Bulgaria
•
Canada
•
Chile
•
China, PRC
•
Colombia
•
Costa Rica
•
Croatia
•
Cyprus
•
Czech Republic
•
Denmark
•
Ecuador
•
Egypt
•
El Salvador
•
Finland
•
France
•
Germany
•
Greece
•
Guatemala
•
Honduras
•
Hong Kong
•
Hungary
•
Iceland
•
India
•
Indonesia
•
Ireland
•
Israel
•
Italy
•
Jamaica
•
Japan
•
Jordan
•
Korea
•
Kuwait
•
Lebanon
•
Malaysia
•
Mexico
•
Netherlands
•
New Zealand
•
Norway
•
Pakistan
•
Peru
•
Philippines
•
Poland
•
Portugal
•
Puerto
Rico
•
Qatar
•
Romania
•
Russia–CIS
•
Saudi Arabia
•
Singapore
•
Slovakia
•
Slovenia
•
South Africa, Republic
•
Spain
•
Sweden
•
Switzerland
•
Taiwan
•
Thailand
•
Turkey
•
United Arab Emirates
•
United Kingdom
•
United States
•
Uruguay
•
Venezuela
•
Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 1747-6.8 – June 1996
Supersedes Publication 1747-NM007 – September 1993
40072-032-01(A)
Advertisement
Key Features
- Connects PLC-5r or SLC 500 to a remote SLC 500
- Provides a distributed processing system
- Communicates with supervisory PLC or SLC controllers through RIO scanners
- Does not scan the I/O in its local I/O chassis
- Passes supervisory data to the distributed SLC processor