Outdoor Heat Pump User’s Information/Installation Instructions 10 SEER High Efficiency Split System These units have been designed and tested for capacity and efficiency in accordance with A.R.I. Standards. Split System Heat Pump units are designed for use with a wide variety of fossil fuel furnaces, electric furnaces, air handlers, and evaporator coil combinations. These instructions are primarily intended to assist qualified individuals experienced in the proper installation of heating and/or air conditioning appliances. Some local codes require licensed installation/service personnel for this type of equipment. Read all instructions carefully before starting the installation. USER’S INFORMATION IMPORTANT Read this owner information to become familiar with the capabilities and use of your appliance. Keep this with literature on other appliances where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your servicing contractor. Heat Pump Principle of Operation 5 4 2 5 1 2 3 6 1 3 4 6 WINTER HEATING SUMMER COOLING 1. Outdoor air enters heat pump. 2. Cold, heat-transfer section (outdoor coil) extracts heat from outdoor air as refrigerant evaporates from a liquid to a gas. 3. Refrigerant, compressed to a hot gas by heat pump, carries the heat to the hot heattransfer section (indoor coil). 4. Hot, heat-transfer section (indoor coil) releases the heat to indoor air as refrigerant condenses from a gas to a liquid. 5. Air handler circulates the heat throughout the home. 6. Refrigerant returns to outdoor coil and evaporates once again to absorb more heat. 1. Indoor air enters the air handler section. 2. Cold, heat-transfer section (indoor coil) extracts heat from indoor air as refrigerant evaporates from a liquid to a cold gas. 3. Refrigerant, drawn to heat pump and compressed to a hot gas by heat pump, carries the heat outdoors. 4. Hot, heat-transfer section (outdoor coil) releases the heat as refrigerant condenses from a gas to a liquid. 5. Heat pump (outdoor fan) discharges the heat to outside air. 6. Refrigerant returns to indoor coil and evaporates once again to absorb more heat. 2 OPERATING INSTRUCTIONS TO OPERATE YOUR HEAT PUMP FOR COOLING — 1. Set the thermostat system switch to COOL and the thermostat fan switch to AUTO. (See Figure 1) 2. Set the thermostat temperature to the desired temperature level by pressing the WARMER or COOLER button. Please refer to the separate detailed thermostat user's manual for complete instructions regarding thermostat programming. The outdoor unit and indoor blower will both cycle on and off to maintain the indoor temperature at the desired cooling level. NOTE: If the thermostat temperature level is re-adjusted, or the thermostat system switch is repositioned, the outdoor unit may not start immediately. The outdoor unit contains a protective timer circuit which holds the unit off for approximately five minutes following a previous operation, or the interruption of the main electrical power. TO OPERATE YOUR HEAT PUMP FOR HEATING — 1. Set the thermostat system switch to HEAT and the thermostat fan switch to AUTO. (See Figure 1) 2. Set the thermostat temperature to the desired temperature level by pressing the WARMER or COOLER button. Please refer to the separate detailed thermostat user's manual for complete instructions regarding thermostat programming. The outdoor unit and indoor blower will both cycle on and off to maintain the indoor temperature at the desired heating level. NOTE: If the thermostat temperature level is re-adjusted, or the thermostat system switch is repositioned, the outdoor unit may not start immediately. The outdoor unit contains a protective timer circuit which holds the unit off for approximately five minutes following a previous operation, or the interruption of the main electrical power. Emergency Heat: The thermostat includes a system switch position termed EM. HT. This is a back-up heating mode to be used only if there is a suspected problem with the outdoor unit. With the system switch set to EM. HT. the outdoor unit will be locked off, and supplemental heat (typically electric resistance heating) will be used as a source of heat. Sustained use of electric resistance heat in place of the heat pump will result in an increase in electric utility costs. Defrost: During cold weather heating operation, the outdoor unit will develop a coating of Figure 1. Typical Thermostat 3 snow and ice on the heat transfer coil. This is normal, and the unit will periodically defrost itself. During the defrost cycle, the outdoor fan will stop, and the compressor will continue to run and heat the outdoor coil, causing the snow and ice to melt. After the snow and ice have melted, some steam may rise from the outdoor unit as the warm coil causes some melted frost to evaporate. TO OPERATE YOUR HEAT PUMP FOR AUTOMATIC COOLING AND HEATING a temperature unbalance due to a sun load, cooking, or fireplace operation. TO MAINTAIN YOUR HEAT PUMP — ! CAUTION: Be certain the electrical power to the outdoor unit and the furnace/air handler is disconnected before doing the following recommended maintenance. 1. 1. Set the thermostat system switch to AUTO and the thermostat fan switch to AUTO. (See Figure 1) Note: Thermostats will vary. Some models will not include the AUTO mode, and others will have the AUTO in place of the HEAT and COOL, and some will include all three. 2. Set the thermostat temperature to the desired heating and cooling temperature level(s). The outdoor unit and the indoor blower will then cycle on and off in either the heating or cooling mode of operation as required to automatically maintain the indoor temperature within the desired limits. TO SHUT OFF YOUR HEAT PUMP — Set the thermostat system switch to OFF and the thermostat fan switch to AUTO. (See Figure 1) The system will not operate, regardless of the thermostat temperature selector(s) setting. TO OPERATE THE INDOOR BLOWER CONTINUOUSLY — Set the thermostat fan switch to ON (See Figure 1). The indoor blower will start immediately, and will run continually until the fan switch is reset to AUTO. The continuous indoor blower operation can be obtained with the thermostat system switch set in any position, including OFF. The continuous indoor blower operation is typically used to circulate the indoor air to equalize 4 Regularly: a. Clean or replace the indoor air filter at the start of each heating and cooling season, and when an accumulation of dust and dirt is visible on the air filter. Inspect the filter monthly. b. Remove any leaves and grass clippings from the coil in the outdoor unit, being careful not to damage the aluminum fins. c. Check for any obstruction such as twigs, sticks, etc. ! CAUTION: Do not over-oil, or oil motors not factoryequipped with oil tubes. The compressor is hermetically “sealed” and does not require lubrication. 2. Before Calling a Service Technician, Be Certain: a. The unit thermostat is properly set — see “To Operate Your Heat Pump for Cooling” and “To Operate Your Heat Pump for Heating.” b. The unit disconnect fuses are in good condition, and the electrical power to the unit is turned on. Read Your Warranty Please read the separate warranty document completely. It contains valuable information about your system. GENERAL INFORMATION Read the following instructions completely before performing the installation. Outdoor Unit Section — Each outdoor unit is shipped with a refrigerant charge adequate to operate the outdoor section with an indoor matching coil or air handler. Units with braze connections include the proper amount of refrigerant for an additional 15 ft. of refrigerant lines the same size as the valve fittings. NOTE: DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING. Matching coils and air handlers may be shipped with a small holding charge to pressurize them to keep out contaminants. To release the pressure, read the indoor section installation instructions carefully. Liquid and Suction Lines — Fully annealed, refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated. Field Connections for Electrical Power Supply — All wiring must comply with current provisions of the “National Electrical Code” (ANSI C1.) and with applicable local codes having jurisdiction. The minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label. SAFETY CONSIDERATIONS Pressures within the System — Split system heat pump equipment contains liquid and gaseous refrigerant under pressure. Installation and servicing of this equipment should be accomplished by qualified, trained personnel thoroughly familiar with this type of equipment. Under no circumstances should the Homeowner attempt to install and/or service the equipment. Labels, Tags, Precautions — When working with this equipment, follow all precautions in the literature, on tags, and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment. Brazing Operations — Installation of equipment may require brazing operations. Safety codes must be complied with. Safety equipment (e.g.; safety glasses, work gloves, fire extinguisher, etc.) must be used when performing brazing operations. ! WARNING: Ensure all electrical power to the unit is off prior to installing or servicing the equipment. Failure to do so may cause personal injury or death. SITE PREPARATION Unpacking Equipment — Remove the cardboard carton and User's Manual from the equipment. Take care to not damage tubing connections when removing from the carton. Inspect for Damage — Inspect the equipment for damage prior to installing the equipment at the job site. Ensure coil fins are straight and, if necessary, comb fins to remove flattened and bent fins. Preferred Location of the Outdoor Unit at the Job Site — Conduct a survey of the job site to determine the optimum location for mounting the outdoor unit. Overhead obstructions, poorly ventilated areas, and areas subject to accumulation of debris should be avoided. The outdoor unit should be installed no closer than 18 inches from the outside walls of the facility and in an area free from overhead obstructions to ensure unrestricted airflow through the outdoor unit. Facility Prerequisites — Electrical power supplied must be adequate for proper operation of the equipment. The system must be wired and provided with circuit protection in accordance with local building codes and the National Electrical Code. INSTALLING THE OUTDOOR UNIT Slab Mount — The site selected for a slab mount installation requires a stable foundation and one not subject to erosion. The slab should be level and anchored (if necessary) prior to placing the equipment on the slab. 5 Cantilever Mount — The cantilever mount should be designed with adequate safety factor to support the weight of the equipment, and for loads subjected to the mount during operation. Installed equipment should be adequately secured to the cantilever mount and levelled prior to operation of the equipment. Optional Equipment — Optional equipment (e.g.: filter/driers, liquid line solenoid valves, etc.) should be installed in strict accordance with the manufacturer’s installation instructions. Roof Mount — The method of mounting should be designed so as not to overload roof structures nor transmit noise to the interior of the structure. Refrigerant and electrical line should be routed through suitably waterproofed openings to prevent water leaking into the structure. 1. Remove protective caps from the unit and the refrigerant line couplings. INSTALLING THE INDOOR UNIT 3. Using refrigerant oil, lightly lubricate the diaphragm, seal and threads on the male unit coupling. The indoor section should be installed before proceeding with routing of refrigerant piping. Consult the Installation Instructions of the indoor unit (i.e.: air handler, furnace, etc.) for details regarding installation. CONNECTING REFRIGERANT TUBING BETWEEN THE INDOOR AND OUTDOOR UNIT General — Once outdoor and indoor unit placement has been determined, route refrigerant tubing between the equipment in accordance with sound installation practices. Refrigerant tubing should be routed in a manner that minimizes the length of tubing and the number of bends in the tubing. Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation. Tubing should be kept clean of foreign debris during installation and installation of a liquid line filter drier is recommended if cleanliness or adequacy of system evacuation is unknown or compromised. Every effort should be made by the installer to ensure that the field installed, refrigerant containing components of the system have been installed in accordance with these instructions and sound installation practices so as to insure reliable system operation and longevity. The maximum recommended interconnecting refrigerant line length is 75 feet, and the vertical elevation difference between the indoor and outdoor sections should not exceed 20 feet. Consult long line application guide for installations in excess of these limits. 6 For refrigerant line sets that incorporate single shot couplings only: 2. Carefully wipe all coupling threads and seals with a clean cloth to remove any dust or foreign material which could contaminate the refrigerant system. 4. Connect couplings as follows: Note: Start with indoor section first. a. HOLD REFRIGERANT LINE IN STRAIGHT POSITION TO UNIT COUPLING AND THREAD COUPLING HALVES TOGETHER BY HAND TO INSURE PROPER CONNECTION. Hold body of the line coupling hex with wrench, while slowly tightening the union nut until a definite resistance (bottoming out) is felt. b. Mark the position of union nut (match lines on the line coupling and the unit bulk head), and then tighten the coupling an additional 1/4 turn to insure leak-proof connection. (See Table of Torque Values for recommended torque values if a torque wrench is used.) TABLE OF TORQUE VALUES Coupling Size 3/8" (10 mm) Liquid Line Coupling Torque 10 - 12 ft. lbs. (Metric: 14-16 N-m) 3/4" (19 mm) or 7/8" (22 mm) Vapor Line Coupling 34 - 45 ft. lbs. (Metric: 47-61 N-m) Service Valve Cap 5 - 6 ft. lbs. (Metric: 7 - 8 N-m) Figure 2. Single Phase Wiring Diagram 7 RVS CC LLS If Equipped DFT C T1 T2 C Y O W2 R 4 DFT 1 R Outdoor Fan Motor S C S Compressor R 1 3 Control Logic DF2 2 T2 Compressor Contacts S Outdoor Fan Motor DF1 O O W2 R R C Y T2 DF1 DF2 Black Black Reversing Valve Solenoid DFT Low Voltage E Terminals See Note 6 C Y O W2 R E TEST High Voltage F Blue Orange Black Contactor Yellow Red Black L2 T2 L1 L2 Grd L1 T1 3 3 Yellow 11 22 Grounding Screw Start Capacitor (Optional) Yellow Black 710235A (Single Phase) Field Supply S Compressor C R Yellow or Yellow Black Black or Black White Black Orange Black CCH (If Equipped) Red or Red Black Field Wiring Factory Wiring: Low Voltage Legend Red Terminal or Gray Wire Defrost Thermostat Red Gray ODT (Select Models Only) H T1 C Dual Capacitor Blue T2 DFT LLS If Equipped C Orange Defrost Control Board Yellow Note: For field added limits, remove yellow jumper wire and attach between Y and T1 on defrostcontrolboard. Black R Start Relay (Optional) Single Phase 1. Couper le courant avant de faire letretien. 2. Employez uniquement des conducteurs en cuivre. 3. Ne convient pas aux installations de plus de 150 volt a la terre. Defrost Board Operation: Defrost Control Board 1 Closing during defrost. Rating: 1 Amp. Max. CC - Contactor Coil 2 Opens during defrost. Rating: 2 HP at 230 Vac Max. CCH - Crankcase Heater (If Equipped) 3 Closed when "Y" is on. Open when "Y" is off. DFT - Defrost Thermostat Provides "off" delay time of 5 min. when "Y" opens. LLS - Liquid Line Solenoid (If Equipped) 4 With DFT closed and "Y" closed, compressor run time is accumulated. RVS - Reversing Valve Solenoid Opening of DFT during defrost or interval period resets the interval to 0. ODT - Outdoor Thermostat (Select Models Only) Low Voltage Terminals C Y O W2 R ODT Dual Capacitor F C H CCH (If Equipped) L2 Disconnect all power before servicing. For supply connections use copper conductors only. Not suitable on systems that exceed 150 volts to ground. For replacement wires use conductors suitable for 105 C. For ampacities and overcurrent protection, see unit rating plate. Connect to 24 vac/40va/class 2 circuit. See furnace/air handler instructions for control circuit and optional relay/transformer kits. E T1 L1 1. 2. 3. 4. 5. 6. NOTES: Split System Heat Pump (Outdoor Section) Figure 3. Three Phase Wiring Diagram C Y O W2 R E Closes during defrost. Rating: 1 Amp. Max. Opens during defrost. Rating: 2 HP. at 230 Vac Max. Closed when “Y” is on. Open when “Y” is off. Provides “off” delay time of 5 min. when “Y” opens. 2 3 3 CONTROL LOGIC 1 2 Defrost Control Board 1 DF1 Ground on location provided inside compressor terminal box. T1 T2 C Y O 4 DF2 5 RVS W2 R DFT Outdoor Fan Motor C T1 Compressor Motor With DFT closed and “Y” closed, compressor run time is accumulated. Opening of DFT during defrost or interval period resets the interval to 0. CC DFT R S T3 T2 4 Capacitor 1 Defrost Board Operation: Low Voltage Terminals T3 T2 5 O E R W2 Black T1 T2 C Y O O W2 R R DFT E High Voltage Black DF1 DF2 Reversing Valve Solenoid Legend See Note 6 Low Voltage Terminals C Y T2 DFT TEST Defrost Control Board DFT RVS CC CCH ODT Blue Capacitor Orange L2 L1 Red Red T2 T1 Yellow T3 T1 Compressor T2 L3 T3 5 - Defrost Thermostat - Reversing Valve Solenoid - Contactor Coil - Crankcase Heater ( If Equipped ) - Outdoor Thermostat (Select Models Only Note: For field added limits, remove yellow jumper wire and attach between Y and T1 on defrost control board. Field Wiring Factory Wiring Low Voltage T1 Outdoor Fan S Motor C Contactor Blue CCH (If Equipped) L1 L2 L3 Black or Black White R Black Red or Red Black Black CCH (If Equipped) Defrost Thermostat Grounding Screw 703948C (3 Phase) Field Supply L1 L2 L3 Grd 1. Couper le courant avant de faire letretien. 2. Employez uniquement des conducteurs en cuivre 3. Ne convient pas aux installations de plus de 150 volt a la terre. Three Phase Yellow or Yellow Black Split System Heat Pump (Outdoor Section) Black NOTES: 1. Disconnect all power before servicing. 2. For supply connections use copper conductors only. 3. Not suitable on systems that exceed 150 volts to ground. 4. For replacement wires use conductors suitable for 105 deg. C 5. For supply wire ampacities and overcurrent protection, see unit data label. 6. Connect to 24 vac/40va/class 2 circuit. See furnace/air handler installation instructions for control circuit and optional Relay/Transformer Kits. Black 8 Outdoor Unit Connections — The outdoor unit requires both power and control circuit electrical connections. Refer to the unit wiring diagram/schematic for identification and location of outdoor unit field wiring interfaces. ELECTRICAL CONNECTIONS ! WARNING: Turn off all electrical power at the main circuit box before wiring electrical power to the outdoor unit. Failure to comply may cause severe personnel injury or death. Control Circuit Wiring — The outdoor unit is designed to operate from a 24 VAC Class II control circuit. Control circuit wiring must comply with the current provisions of the “National Electrical Code” (ANSI C1.) and with applicable local codes having jurisdiction. Wiring Diagram/Schematic — A wiring diagram/schematic is located on the inside cover of the electrical box of the outdoor unit and on the opposite page of these instructions. The installer should become familiar with the wiring diagram/schematic before making any electrical connections to the outdoor unit. (See Figure 3). Thermostat connections should be made in accordance with the instructions supplied with the thermostat, and with the instructions supplied with the indoor equipment. A typical residential installation with a heat pump thermostat and air handler are shown below. Thermostat G R W 2C E O Y Green G Red R Brown W NOTE: Jumper between W2 and E is required when no OD T-Stat is used. R W2 Orange W 2 For 2-Stage Heater Kits Grey C O Y C Air Handler Heat Pump OD Section Typical Heat Pump with Standard Air Handler 9 A typical installation with a heat pump thermostat, air handler, and heat pump with an outdoor thermostat. Thermostat G R W 2C E O Y Green G Red R E R White W W2 C O Y Grey C Air Handler Heat Pump OD Section Typical Heat Pump with Outdoor Thermostat and Air Handler 10 Electrical Power Wiring — Electrical power wiring must comply with the current provisions of the “National Electrical Code” (ANSI C1.) and with applicable local codes having jurisdiction. Use of rain tight conduit is recommended. Electrical conductors shall have minimum circuit ampacity in compliance with the outdoor unit rating label. The facility shall employ electrical circuit protection at a current rating no greater than that indicated on the outdoor unit rating label. Refer to the unit wiring diagram for connection details. Minimum Circuit Ampacity — Electrical wiring to the equipment must be compatible and in COPPER WIRE SIZE — AWG (1% Voltage Drop) Supply Wire Length-Feet Supply Circuit 200 150 100 50 Ampacity 6 8 10 14 15 4 6 8 12 20 4 6 8 10 25 4 4 6 10 30 3 4 6 8 35 3 4 6 8 40 2 3 4 6 45 2 3 4 6 50 Wire Size based on N.E.C. for 60° type copper conductors. compliance with the minimum circuit ampacity listed on the outdoor unit data label. Maximum Fuse/Circuit Breaker Size — Circuit protection for the outdoor unit must be compatible with the maximum fuse/circuit breaker size listed on the outdoor unit data label. Disconnect Switch — An electrically compatible disconnect switch must be within line of sight of the outdoor unit. This switch shall be capable of electrically de-energizing the outdoor unit. Optional Equipment — Optional equipment requiring connection to the power or control circuits must be wired in strict accordance with current provisions of the “National Electrical Code” (ANSI C1.), with applicable local codes having jurisdiction, and the installation instructions provided with the equipment. Optional Equipment (e.g.: liquid line solenoid valves, hard start kits, low suction pressure cutout switch kit, high pressure cutout switch kit, refrigerant compressor crankcase heater, etc.) should be installed in strict accordance with the manufacturer’s installation instructions. STARTUP AND CHECKOUT ! WARNING: Ensure electrical power to the unit is off prior to performing the following steps. Failure to do so may cause personal injury or death. Air Filters — Ensure air filters are clean and in place prior to operating the equipment. Thermostat — Set the room thermostat function switch to OFF, fan switch to AUTO, and adjust the temperature setpoint to its highest setting. Prior to applying electrical power to the outdoor unit, ensure that the unit has been properly and securely grounded, and that power supply connections have been made at both the facility power interface and outdoor unit. Outdoor Unit — Ensure the outdoor coil and top of the unit are free from obstructions and debris, and all equipment access/control panels are in place. Using extreme caution, apply power to the unit and inspect the wiring for evidence of open, shorted, and/or improperly wired circuits. Functional Checkout: ! CAUTION: If equipped with a compressor crankcase heater, wait 24 hours prior to performing a function checkout to allow for heating of the compressor crankcase. Failure to comply may result in damage and could cause premature failure of the system. 11 Indoor Blower — Set the thermostat function switch to COOLING and the fan switch to ON. Verify that the indoor blower is operating and that airflow is not restricted. Set the fan switch back to AUTO. Cooling — Gradually lower the thermostat temperature setpoint below the actual room temperature and observe that the outdoor unit and indoor blower energize. Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature. Listen for any unusual noises. If present, locate and determine the source of the noise and correct as necessary. Short Cycle Protection — With the system operating in COOLING mode, note the setpoint temperature setting of the thermostat, and gradually raise the setpoint temperature until the outdoor unit and indoor blower de-energize. Immediately lower the setpoint temperature of the thermostat to its original setting and verify that the indoor blower is energized and that the outdoor unit remains de-energized. Verify that, after approximately 5 minutes, the outdoor unit energizes and that the temperature of the air supplied to the facility is cooler than ambient temperature. Heating — Lower the thermostat setpoint temperature to the lowest obtainable setting and set the thermostat function switch to HEATING. The indoor blower and outdoor unit should stop running. After a minimum of five minutes, increase the setpoint temperature of the thermostat to the maximum setting. Verify that the outdoor unit and indoor blower have energized. Feel the air being circulated by the indoor blower and verify that it is warmer than ambient temperature. Listen for any unusual noises. If present, locate and determine the source of the noise and correct as necessary. OUTDOOR THERMOSTAT (if supplied) The outdoor thermostat prevents the electrical auxiliary heat (if used) from operating when the outdoor temperature is above 40°F. Defrost Cycle Timer — The defrost cycle timer controls the time interval of the hot gas defrost after the defrost sensor closes. It is located in the lower left corner of the defrost control board. 12 Three interval settings are available: 30 minutes, 60 minutes, and 90 minutes. Time setting selection is dependent on the climate where the unit is being installed. Example 1. Dry climate of Southern Arizona. A 90 minute setting is recommended. Example 2. Moist climate of Seattle, Washington. A 30 minute setting is recommended. To set the cycle timer, place the timing pin on the defrost control board to the desired time interval post. Note: All units are shipped from the factory with the default time setting of 30 minutes. Maximum heating performance can be achieved by setting the time to 90 minutes. Defrost Test Procedure 1. 2. Terminals “R”-”C” must have 18-30v present between them in order for time delay and defrost sequences to be initiated. With compressor running in heat mode, first jump the “T2”-”DFT” test pins. This will indicate to board that defrost T-stat is closed. Defrost T-stat closes at 32°, opens at 68°. 3. Next jump the “Test” pin to “C” on terminal strip. This will initiate defrost test in 5, 10 or 15 seconds (This is determined by 30, 60 or 90 minutes defrost pin settings). Factory setting will be 30 minutes. 4. When the reversing valve shifts to the defrost mode, quickly remove jumper from “Test”-”C”. If the jumper is not removed within a 5 second period, the defrost test will terminate. Unit will continue to stay in defrost mode Until : A) Board recognizes that defrost sensor has reached 68° and opened or B) “T2”-”DFT” jumper is removed or C) 10 minutes have elapsed (board override) If the above steps will not initiate a defrost, replace the defrost board. Anti Short Cycle Timer Test The 5 minute time delay feature can be bypassed or shortened to 1 second by jumping the “Test” to “C” terminal. Note: If jumper is left on the “Test” to “common” pins permanently, the defrost cycle will become inoperable. Optional Equipment — A functional checkout should be performed in accordance with the checkout procedures supplied with the equipment. NOTE: The following Refrigerant Charging Charts are applicable to listed assemblies of equipment and at listed airflows for the indoor coil. Assemblies of indoor coils and outdoor units not listed are not recommended. Adjustment of Refrigerant Charge: ! CAUTION: Split system heat pump equipment contains liquid and gaseous refrigerant under pressure. Adjustment of refrigerant charge should only be attempted by qualified, trained personnel thoroughly familiar with the equipment. Under no circumstances should the homeowner attempt to install and/or service this equipment. Failure to comply with this warning could result in equipment damage, personal injury, or death. 10 SEER SPLIT SYSTEM HEAT PUMP ORIFICE USAGE 10 SEER SPLIT SYSTEM HEAT PUMP ORIFICE Restrictor Bore Size (in.) Model 1 Ton (KB) 1-1/2 Ton (KA) 1-1/2 Ton (KB) 2 Ton 2-1/2 Ton 3 Ton 3-1/2 Ton 4 Ton 5 Ton Indoor .040 .053 .050 .060 .067 .071 .077 .082 .093 Outdoor .035 .041 .044 .049 .055 .059 .063 .065 .071 System Charge R-22 (oz.) 69 69 69 70 79 95 103 134 198 13 REFRIGERANT CHARGING CHARTS FOR COOLING MODE OF OPERATION * Note: All pressures are listed in psig. and all temperatures in degrees F. - Shaded Boxes indicate flooded conditions - Rated Design Values. Suction Pressure will be lower than design value if indoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design. - Discharge temperatures greater than charted values indicate a refrigerant undercharge. S.P. = Suction Pressure L.P. = Liquid Pressure D.T. = Discharge Temperature 1 Ton (KB) S. P. 70 72 74 76 78 80 82 84 86 88 70 75 L. P. D. T. 153 155 157 156 156 143 148 153 193 220 80 L. P. D. T. 168 170 171 172 173 146 151 156 168 177 L. P. D. T. 183 184 186 187 188 150 154 159 166 172 OUTDOOR TEMPERATURE (°F) 85 90 L. P. D. T. L. P. D. T. 198 199 201 202 203 204 153 158 162 167 171 176 212 214 215 217 218 219 157 161 165 169 173 176 90 92 94 96 1 1/2 Ton (KA) S.P. 71 73 75 77 79 81 83 85 87 89 91 93 95 97 14 70 75 L.P. D.T. 165 168 171 174 177 145 148 150 153 157 80 L.P. D.T. 180 183 186 189 193 149 151 154 157 161 L.P. D.T. 196 199 201 205 208 153 155 158 161 165 OUTDOOR TEMPERATURE (°F) 85 90 L.P. D.T. L.P. D.T. 211 214 217 220 223 226 156 159 162 165 168 171 226 229 232 235 238 242 160 164 167 169 172 174 95 100 105 L. P. D. T. L. P. D. T. L. P. D. T. 227 229 230 231 233 160 164 169 172 175 242 243 245 246 164 168 172 175 257 258 259 168 171 175 234 178 247 249 177 180 261 262 264 178 180 183 L.P. D.T. L.P. D.T. L.P. D.T. 241 244 247 250 254 164 168 171 173 175 257 260 262 266 168 172 175 177 272 275 278 173 176 179 257 178 269 272 179 181 281 284 288 180 182 184 95 100 105 REFRIGERANT CHARGING CHARTS FOR COOLING MODE OF OPERATION (Cont.) 1 1/2 Ton (KB) S. P. 73 75 77 79 81 83 85 87 89 91 70 75 L. P. D. T. 172 174 175 176 176 132 137 142 163 190 80 L. P. D. T. 188 189 191 192 193 138 143 148 156 166 L. P. D. T. 203 205 207 208 209 144 149 153 159 165 OUTDOOR TEMPERATURE (°F) 85 90 L. P. D. T. L. P. D. T. 219 221 222 223 225 226 150 154 159 164 168 173 235 236 238 239 240 242 156 160 165 168 172 176 93 95 97 99 2 Ton S.P. 68 70 72 74 76 78 80 82 84 86 70 75 L.P. D.T. 171 173 176 179 182 158 161 163 166 170 80 L.P. D.T. 186 189 192 195 198 160 163 166 169 172 L.P. D.T. 202 205 208 211 214 163 166 169 172 175 OUTDOOR TEMPERATURE (°F) 85 90 L.P. D.T. L.P. D.T. 218 221 224 227 230 233 166 169 172 175 178 180 234 236 239 243 246 249 169 172 175 177 180 183 88 90 92 94 2 1/2 Ton S.P. 68 70 72 74 76 78 80 82 84 86 88 90 92 94 70 75 L.P. D.T. 161 164 167 170 173 149 152 155 158 161 80 L.P. D.T. 182 185 188 191 194 154 157 160 163 167 L.P. D.T. 203 206 209 212 215 159 162 165 168 171 OUTDOOR TEMPERATURE (°F) 85 90 L.P. D.T. L.P. D.T. 224 227 230 233 236 240 165 168 171 174 176 179 245 248 251 254 257 261 170 173 176 179 181 184 95 100 105 L. P. D. T. L. P. D. T. L. P. D. T. 251 252 253 255 256 162 166 170 173 176 266 268 269 270 168 172 176 178 282 283 285 174 178 181 257 180 272 273 181 184 286 287 289 184 186 189 L.P. D.T. L.P. D.T. L.P. D.T. 249 252 255 258 262 171 175 178 180 182 265 268 271 274 174 178 181 183 281 284 287 177 181 184 265 185 278 281 185 187 290 293 297 185 187 188 L.P. D.T. L.P. D.T. L.P. D.T. 266 269 272 275 278 175 178 182 184 186 287 290 293 296 180 184 187 189 308 311 314 186 189 192 282 188 299 303 191 193 317 320 324 194 196 197 95 100 95 105 100 105 15 REFRIGERANT CHARGING CHARTS FOR COOLING MODE OF OPERATION (Cont.) 3 Ton S.P. 64 66 68 70 72 74 76 78 80 82 70 75 L.P. D.T. 173 176 179 182 186 175 178 180 184 188 80 L.P. D.T. 189 192 195 198 201 176 179 181 185 188 L.P. D.T. 204 207 210 214 217 177 180 182 186 189 OUTDOOR TEMPERATURE (°F) 85 90 L.P. D.T. L.P. D.T. 220 223 226 229 233 236 178 181 184 186 189 192 236 239 242 245 248 252 178 182 185 187 190 192 84 86 88 90 3 1/2 Ton S.P. 63 65 67 69 71 73 75 77 79 81 70 75 L.P. D.T. 168 171 174 176 180 147 150 152 154 158 80 L.P. D.T. 185 188 191 193 197 151 154 157 159 163 L.P. D.T. 202 205 208 211 214 156 159 162 165 168 OUTDOOR TEMPERATURE (°F) 85 90 L.P. D.T. L.P. D.T. 219 222 225 228 231 234 161 164 167 170 173 175 236 239 242 245 248 252 165 169 172 174 177 180 83 85 87 89 4 Ton S.P. 63 65 67 69 71 73 75 77 79 81 83 85 87 89 16 70 75 L.P. D.T. 160 163 166 168 172 151 154 157 158 162 80 L.P. D.T. 178 180 183 186 189 154 157 160 162 166 L.P. D.T. 195 198 201 203 207 158 161 164 167 170 OUTDOOR TEMPERATURE (°F) 85 90 L.P. D.T. L.P. D.T. 212 215 218 221 224 227 161 164 167 170 173 176 229 232 235 238 241 245 165 168 171 174 177 179 95 100 105 L.P. D.T. L.P. D.T. L.P. D.T. 251 254 257 261 264 179 183 186 188 190 267 270 273 276 180 184 187 189 283 286 289 181 185 188 267 193 280 283 191 193 292 295 298 190 192 193 L.P. D.T. L.P. D.T. L.P. D.T. 253 256 259 262 265 170 174 177 179 181 270 273 276 279 175 179 182 183 287 290 293 180 184 187 269 184 282 286 185 187 296 300 303 187 189 191 L.P. D.T. L.P. D.T. L.P. D.T. 246 249 252 255 259 169 172 175 177 180 264 267 269 273 173 176 179 180 281 284 287 176 180 183 262 182 276 279 182 184 290 294 297 183 185 187 95 100 95 105 100 105 REFRIGERANT CHARGING CHARTS FOR COOLING MODE OF OPERATION (Cont.) 5 Ton S.P. 70 61 63 65 67 69 71 73 75 77 79 75 L.P. D.T. 166 169 172 174 177 156 159 161 162 166 80 L.P. D.T. 184 187 189 192 195 161 164 167 169 172 L.P. D.T. 201 204 207 210 213 166 169 172 175 178 OUTDOOR TEMPERATURE (°F) 85 90 L.P. D.T. L.P. D.T. 219 222 225 227 231 234 171 175 178 181 183 186 236 239 242 245 249 252 177 180 183 186 189 191 81 83 85 87 95 100 105 L.P. D.T. L.P. D.T. L.P. D.T. 254 257 260 263 266 183 186 189 191 193 272 275 278 281 188 191 195 196 289 292 295 194 197 201 270 196 284 288 198 200 299 302 305 200 202 204 REFRIGERANT CHARGING CHARTS FOR HEATING MODE OF OPERATION 1 TON (KB) OUTDOOR TEMPERATURE (DEG. F) 0 10 20 30 40 50 60 S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. 15 16 17 18 19 20 21 109 116 123 130 137 144 151 80 78 76 74 72 70 68 24 25 26 27 28 29 30 126 132 138 144 150 155 161 93 91 89 87 85 83 81 33 34 35 36 37 38 39 143 147 152 157 162 167 171 106 104 102 100 98 96 94 1-1/2 TON (KA) 42 43 44 45 46 47 48 159 163 167 170 174 178 181 119 117 115 113 111 109 107 52 53 54 55 56 57 58 164 171 178 185 192 199 206 135 132 129 126 123 120 118 62 63 64 65 66 67 68 181 188 195 202 209 216 223 152 148 143 139 134 130 125 72 73 74 75 76 77 78 198 205 212 219 226 233 240 170 164 158 151 145 139 133 OUTDOOR TEMPERATURE (DEG. F) 0 10 20 30 40 50 60 S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. 15 16 17 18 108 115 122 129 115 113 111 109 23 24 25 26 127 133 139 145 120 118 116 114 31 32 33 34 146 151 156 161 126 124 122 120 39 40 41 42 166 169 173 177 132 130 128 126 48 49 50 51 176 183 190 197 147 144 141 139 58 59 60 61 199 206 213 220 171 167 162 158 68 69 70 71 223 230 237 244 196 190 184 177 19 20 21 136 107 143 105 150 103 27 28 29 151 112 157 110 162 108 35 36 37 165 118 170 116 175 114 43 44 45 180 124 184 122 188 120 52 53 54 204 136 211 133 218 130 62 63 64 227 153 234 149 241 144 72 73 74 251 171 258 165 265 159 17 REFRIGERANT CHARGING CHARTS FOR HEATING MODE OF OPERATION (Cont.) 1-1/2 TON (KB) OUTDOOR TEMPERATURE (DEG. F) 0 10 20 30 40 50 60 S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. 12 13 14 15 16 17 18 115 122 129 136 143 150 157 88 86 84 82 80 78 76 21 22 23 24 25 26 27 129 102 135 100 141 98 147 96 153 94 159 92 164 90 29 30 31 32 33 34 35 144 149 153 158 163 168 172 116 114 112 110 108 106 104 2 TON 38 39 40 41 42 43 44 158 162 166 169 173 177 180 130 128 126 124 122 120 118 47 48 49 50 51 52 53 159 166 173 180 187 194 201 145 143 140 137 134 131 128 55 56 57 58 59 60 61 170 177 184 191 198 205 212 162 158 153 149 144 140 135 64 65 66 67 68 69 70 181 188 195 202 209 216 223 179 173 167 161 155 148 142 OUTDOOR TEMPERATURE (DEG. F) 0 10 20 30 40 50 60 S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. 13 14 15 16 108 115 122 129 123 121 119 117 21 22 23 24 127 133 139 145 128 126 124 122 29 30 31 32 147 152 157 162 133 131 129 127 37 38 39 40 167 171 174 178 137 135 133 131 46 47 48 49 174 181 188 195 151 148 145 143 54 55 56 57 193 200 207 214 174 169 165 160 63 64 65 66 211 218 225 232 17 18 19 136 115 143 113 150 111 25 26 27 151 120 157 118 163 116 33 34 35 166 125 171 123 176 121 41 42 43 182 129 185 127 189 125 50 51 52 202 140 209 137 216 134 58 59 60 221 156 228 151 235 147 67 68 69 239 171 246 165 253 159 2-1/2 TON 196 190 184 178 OUTDOOR TEMPERATURE (DEG. F) 0 10 20 30 40 50 60 S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. 13 14 15 16 108 115 122 129 123 121 119 117 21 22 23 24 127 133 139 145 128 126 124 122 30 31 32 33 146 151 156 160 133 131 129 127 38 39 40 41 165 169 173 176 139 137 135 133 47 48 49 50 171 178 185 192 153 151 148 145 55 56 57 58 186 193 200 207 177 173 168 164 63 64 65 66 201 208 215 222 17 18 19 136 115 143 113 150 111 25 26 27 150 120 156 118 162 116 34 35 36 165 125 170 123 175 121 42 43 44 180 131 184 129 187 127 51 52 53 199 142 206 139 213 136 59 60 61 214 159 221 155 228 150 67 68 69 229 176 236 170 243 164 3 TON 201 195 188 182 OUTDOOR TEMPERATURE (DEG. F) 0 10 20 30 40 50 60 S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. 13 14 15 16 114 121 128 135 133 131 129 127 20 21 22 23 131 137 143 149 137 135 133 131 27 28 29 30 148 153 158 163 140 138 136 134 34 35 36 37 166 169 173 177 144 142 140 138 43 44 45 46 175 182 189 196 156 153 151 148 55 56 57 58 200 207 214 221 178 173 169 164 67 68 69 70 226 233 240 247 17 18 19 142 125 149 123 156 121 24 25 26 155 129 161 127 166 125 31 32 33 167 132 172 130 177 128 38 39 40 180 136 184 134 188 132 47 48 49 203 145 210 142 217 139 59 60 61 228 160 235 155 242 151 71 72 73 254 175 261 169 268 163 18 200 193 187 181 REFRIGERANT CHARGING CHARTS FOR HEATING MODE OF OPERATION (Cont.) 3-1/2 TON OUTDOOR TEMPERATURE (DEG. F) 0 10 20 30 40 50 60 S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. 9 10 11 12 119 126 133 140 138 136 134 132 16 17 18 19 136 141 147 153 139 137 135 133 23 24 25 26 152 157 162 167 140 138 136 134 30 31 32 33 169 173 177 180 140 138 136 134 38 39 40 41 176 183 190 197 156 153 150 148 49 50 51 52 196 203 210 217 186 182 177 173 59 60 61 62 216 223 230 237 13 14 15 147 130 154 128 161 126 20 21 22 159 131 165 129 171 127 27 28 29 172 132 176 130 181 128 34 35 36 184 132 188 130 191 128 42 43 44 204 145 211 142 218 139 53 54 55 224 168 231 164 238 159 63 64 65 244 192 251 186 258 180 4 TON 217 210 204 198 OUTDOOR TEMPERATURE (DEG. F) 0 10 20 30 40 50 60 S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. 15 16 17 18 125 132 139 146 128 126 124 122 19 20 21 22 137 143 149 155 130 128 126 124 23 24 25 26 150 154 159 164 131 129 127 125 28 29 30 31 162 166 169 173 133 131 129 127 38 39 40 41 175 182 189 196 143 140 137 134 54 55 56 57 213 220 227 234 161 157 152 148 70 71 72 73 251 258 265 272 19 20 21 153 120 160 118 167 116 23 24 25 161 122 166 120 172 118 27 28 29 169 123 173 121 178 119 32 33 34 177 125 180 123 184 121 42 43 44 203 131 210 129 217 126 58 59 60 241 143 248 139 255 134 74 75 76 279 155 286 148 293 142 5 TON 179 173 167 161 OUTDOOR TEMPERATURE (DEG. F) 0 10 20 30 40 50 60 S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. S.P. L.P. D.T. 8 9 10 11 116 123 130 137 134 132 130 128 16 17 18 19 140 146 151 157 139 137 135 133 25 26 27 28 163 168 173 178 144 142 140 138 33 34 35 36 187 190 194 198 149 147 145 143 41 42 43 44 199 206 213 220 159 156 153 151 50 51 52 53 222 229 236 243 175 170 166 162 59 60 61 62 246 253 260 267 191 185 179 173 12 13 14 144 126 151 124 158 122 20 21 22 163 131 169 129 175 127 29 30 31 182 136 187 134 192 132 37 38 39 201 141 205 139 209 137 45 46 47 227 148 234 145 241 142 54 55 56 250 157 257 153 264 148 63 64 65 274 166 281 160 288 154 19 INSTALLER: PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER. ¢708105}¤ 708105C 708105C (Replaces 708105B) Specifications and illustrations subject to change without notice and without incurring obligations. Printed in U.S.A. (12/04)
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement