Telemecanique Altivar 28 speed controller User's manual
The Altivar 28 speed controller can communicate using the integrated RS485 serial link, with the connection kit (order separately). The speed controller status can be modified by sending a control word (CMD) or by the occurrence of an event (example : lock following malfunction). The speed controller status is given by the value of the status register (ETA). The speed controller can be used to control the speed of a motor and can be configured with a variety of parameters, including the motor type, the speed reference, the acceleration and deceleration rates, and the fault handling behavior.
Advertisement
Advertisement
Guide d'exploitation
User's manual
Altivar 28
Telemecanique
Variables internes de communication
Internal Communication Variables
Altivar 28
Variables internes de communication
Internal Communication Variables
Page 2
Page 26
2
26
While every care has been taken in the preparation of this document, Schneider Electric SA cannot guarantee the content and cannot be held responsible for any errors it may contain nor for any damage which may result from its use or application.
NOTE
Contents
Control and Monitoring of the Altivar 28 ______________________________________________ 28
Summary of "DRIVECOM" standard _________________________________________________ 30
Altivar 28 Variables _______________________________________________________________ 33
General configuration parameters _______________________________________ 33
I/O configuration parameters ___________________________________________ 35
Fault configuration parameters _________________________________________ 36
Adjustment parameters _______________________________________________ 37
Control parameters ___________________________________________________ 39
Monitoring parameters ________________________________________________ 41
Special "DRIVECOM" parameters _______________________________________ 46
Index of addresses ________________________________________________________________ 48
27
Control and Monitoring of the Altivar 28
The Altivar 28 speed controller can communicate using the integrated RS485 serial link, with the connection kit (order separately).
This document defines the variable speed controller control process using the serial link as well as the internal variables for the speed controller.
The Altivar 28 user’s manual should be consulted in order to obtain more detailed explanation (operation,
"factory" settings, etc).
The Altivar 28 control process using the serial link conforms to the DRIVECOM standard state chart. The chart below has been adapted to the characteristics of the Altivar 28 to simplify programming. Each state represents an aspect of the internal behaviour of the speed controller.
The speed controller status can be modified by sending a control word (CMD) or by the occurrence of an event (example : lock following malfunction). The speed controller status is given by the value of the status register (ETA).
Enter
state diagram
Irrespective of ATV28 status
ETA = H'xxxx'
Occurrence of a fault
ATV28 faulty
ETA = H'xxxF' or
ETA = H'xxx8'
Freewheel stop command.
Send
CMD = H'0000' or
Modification of a configuration parameter which can be modified with motor stopped
ATV28 on and locked
ETA = H'xx40'
Send
CMD = H'0000'
Standby status
ETA = H'xx21'
Send
CMD = H'0006'
Speed controller switched on
Send
CMD = H'0006'
Send
CMD = H'0007'
ATV28 ready
ETA = H'xx23'
Reset faults
Send CMD = H'0080'
Send
CMD = H'0000'
Send
CMD = H'0000'
Send
CMD = H'0006'
Send
CMD = H'0007'
Motor control command
Send CMD =
H'000F' : forward run command
H'080F' : reverse run command
ATV28 running
ETA = H'xx27'
Emergency stop command
Send CMD =
H'000B'
ATV28 at emergency stop
ETA = H'xx07'
Send CMD = H'000F' : forward run command
H'080F' : reverse run command
H'100F' : stop on ramp
H'200F' : DC injection stop
H'400F' : fast stop
Key
Speed controller status
Transition
H'xxxx' hexadecimal value shows a hexadecimal value
28
Control and Monitoring of the Altivar 28
Stop requests which can be activated by the terminal always have priority:
Type of stop
Freewheel stop
Fast stop
DC injection stop
3-wire control stop via logic input STOP (LI1)
Corresponding DRIVECOM state
"ATV28 powered up"
"ATV28 running"
"ATV28 running"
"ATV28 powered up"
Actions for restoring control of the Altivar 28 using the serial link
- set the logic input assigned to the "Freewheel stop" function to 1 (active at 0)
- perform the transitions required to return the speed controller to “run” status.
- set the logic input assigned to the "Fast stop" function to 1 (active at 0)
- set the logic input assigned to the "DC injection braking" function to 0 (active at 1)
- set the logic input assigned to the STOP function to 1
(active at 0)
- perform the transitions required to return the speed controller to “run” status.
Forced to local
If a logic input assigned to the forced to local function is set to 1, the commands present at the terminals are taken into account.
In forced to local mode all write requests from the fieldbus are refused.
Warning: when forced to local mode ceases, line control is restored at the point which was active at the moment of interrupt caused by forced to local.
Communication bus monitoring
Bit 14 (NTO) of control word CMI is used to inhibit communication monitoring.
If NTO = 1, the speed controller no longer takes into account communication errors from the communication bus controlling the speed controller.
For safety reasons its use must be restricted to the debug phase.
Warning
Only those addresses and values defined in this document may be used. All other addresses and values should be considered as reserved and should not be written. If this precaution is not respected it may result in malfunctions.
29
Summary of "DRIVECOM" standard
Definition of bits in the control register and the status register.
The bits in the CMD control register ("controlword") have the following meaning:
bit 0
SWITCH
ON
Switch to speed controller ready bit 1
DISABLE
VOLTAGE
Return to
ATV 28 powered up status bit 2
QUICK
STOP bit 3
ENABLE
OPERATION
Emergency stop run / stop bit 4 optional bit 5 optional bit 6 optional bit 7
RESET
MALFUNCTION reserved reserved reserved Reset fault acknowledged bit 8 reserved reserved bit 9 reserved reserved bit 10 bit 11 reserved specific to manufacturer reserved reverse the motor direction bit 12 specific to manufacturer bit 13 specific to manufacturer run / stop stop by injection bit 14 specific to manufacturer fast stop bit 15 specific to manufacturer reserved
Note
: The grey boxes correspond to the "DRIVECOM" standard, the white boxes correspond to the adaptation of the Altivar 28 to this standard.
The commands are combinations of 5 mandatory bits.
command bit 7 bit 3 bit 2 bit 1 bit 0 initializes state
Switch on disabled
SHUT DOWN
SWITCH ON
DISABLE VOLTAGE
QUICK STOP
DISABLE OPERATION
ENABLE OPERATION
RESET MALFUNCTION x : state is not significant
0>1 : "rising edge" (switch from 0 to 1).
1 0 0 0 0 x x x x x x
1
1 x
1
1
0
0
1 x x x 0 1 x x 0 1 1 1 x 1 1 1 1
0>1 x x x x transition in
DRIVECOM diagram
1
2, 6, 8
3
7, 9, 10, 12
11
5
4
15 sample values of the control register
00 F0H
00 76H
00 77H
00 70H
00 72H
00 77H
00 7FH
00 F0H
30
Summary of "DRIVECOM" standard
The bits in the ETA status register ("statusword") have the following meaning:
bit 0
Ready to switch on not ready/ ready for startup bit 1
Switched on speed controller not ready/ ready bit 2
Operation enabled stop/ run bit 3
Malfunction no malfunction/ malfunction bit 4
Voltage disabled power on/off bit 5
Quick
Stop emergency stop in progress bit 6
Switch on disabled speed controller locked bit 8
Message reserved bit 9
Remote forced to local/ remote bit 10
Setpoint reached reference reached bit 11
Limit value min or max value reached bit 12 reserved reserved bit 13 reserved reserved bit 14 specific to manufacturer stop via
STOP key bit 7
Warning
Alarm bit 15 specific to manufacturer direction of rotation forward/reverse
Note
: The grey boxes correspond to the "DRIVECOM" standard, the white boxes correspond to the adaptation of the Altivar 28 to this standard.
The states are coded in combinations of bits: (Note: bit 4 is not significant and is therefore not shown in the table).
command
NOT RDY TO SWITCH ON
SWITCH ON DISABLED
READY TO SWITCH ON
SWITCH ON
OPERATION ENABLED
MALFUNCTION
MALFUNC. REACT. ACTIVE
QUICK STOP ACTIVE x : state is not significant
Description of other bits: bit 4 - Voltage disabled bit 7 - Warning bit 8 - Message bit 9 - Remote bit 10 - Setpoint reached bit 11 - Limit value bit 6 bit 5 bit 3 bit 2 bit 1 bit 0
0
1
0
0
0
0
0
0 x x
1
1
1 x x
0
0
0
0
0
0
1
1
0
0
0
0
0
1
0
1
1
0
0
0
1
1
0
1
1
0
0
1
1
1
0
1
1 value of the status register expected value after masking mask
-
00 40H
00 21H
00 23H
00 27H
00 08H
-
00 00H
-
00 4FH
00 6FH
00 6FH
00 6FH
00 4FH
-
00 08H
= 1 power absent
= 1 a standard or user-specific warning is present
= 1 a message (an event) is present (optional)
= 1 if the parameters can be modified via bus when not forced to local
= 1 if the reference value is reached
= 1 if a limit value is reached (min-max speed)
31
Summary of "DRIVECOM" standard
Managing the status diagram according to the commands written by the CMD control register (controlword)
0
Malfunction
Reaction active xxxFH
14
No malfunction
& com. reg. =
DISABLE
VOLTAGE
9
No malfunction
& com. reg. =
SHUT DOWN
8
Not operable xx00H
Malfunction
13
No malfunction
& com. reg. = RESET
MALFUNCTION
No malfunction
1 15
Malfunction
12
13
Switch ON
Disabled xx40H
No malfunction
& com. reg. =
SHUT
DOWN
No malfunction
& com. reg. =
DISABLE
VOLTAGE or
QUICK STOP
7 2
Ready to Switch
ON xx21H
Malfunction
No malfunction
& power present
& com. reg. =
SWITCH ON
3
No malfunction
& com. reg. =
SHUT DOWN
6
13
No malfunction
& com. reg. =
DISABLE
VOLTAGE or
QUICK STOP
10
Switched ON xx23H
Malfunction
13
No malfunction
& com. reg. =
ENABLE
OPERATION
4
No malfunction
& com. reg. =
DISABLE
OPERATION
5
Malfunction
13
Malfunction
Operation
Enabled xx27H
11
No malfunction
& com. reg. = QUICK
STOP
New com. reg.
value or
Speed Reference Value
Malfunction xxx8H
Malfunction
No malfunction
& com. reg. =
DISABLE
VOLTAGE
Quick Stop
Active xx07H
32
Altivar 28 Variables
W51
W52
W53
W55
W40
W41
W42
General configuration parameters
(read and write)
These parameters may only be adjusted with the motor stopped, except SdS and SFr, which can be adjusted with the motor running.
Word
W4
Code Unit Description
CrL 0.1 mA Minimum reference of input AI2
Possible values or range
0 to 200
W5 CrH 0.1 mA Maximum reference of input AI2 40 to 200
W6
W10
W16 tCC
Add
2-wire / 3-wire control via terminals
Modification of this parameter will reassign the I/O
0 = 2 C : 2-wire control
1 = 3 C : 3-wire control
2 = OPt : local control option present, in this case writing is impossible.
Address of the speed controller via the standard serial link
1 to 31 bdr bFr
Serial link transmission speed. This parameter is not actually modified until the speed controller has been switched off and on again.
Motor configuration 50 or 60 Hz
7 = 9600 bps
8 = 19200 bps
0 = 50 Hz
1 = 60 Hz
1 to 200 SdS
AOt
Scale factor of SPd parameter
(speed display)
Can be adjusted whilst operating
Configuration of analogue output as 0 - 20 mA or 4 - 20 mA
SFr 0.1 kHz Switching frequency
Can be adjusted whilst operating
0 = 0 - 20 mA
1 = 4 - 20 mA
20 to 150 (2 to 15 kHz) tFr 0.1 Hz Maximum frequency 400 to 4000
FrS 0.1 Hz Nominal motor frequency
UnS 1 V Nominal motor voltage
400 to 4000
ATV-28•••M2 : 200 to 240
ATV-28•••N4 : 380 to 500
33
Altivar 28 Variables
General configuration parameters
(read and write)
These parameters may only be adjusted with the motor stopped, except nrd and Frt, which can be adjusted with the motor running.
Word
W59
W60
W61
W64
W65
Code tUn nrd
UFt brA
Frt
Unit Description
Autotune
Motor noise reduction
Can be adjusted whilst operating
Voltage frequency ratio (U/F ratio)
Possible values or range
0 = nO : Autotune not performed
(value from table used).
If written : return to value from table
1 = donE : Autotune performed.
If written : parameters set by previous autotuning in use.
2 = YES : Autotune command
0 = nO
1 = YES
0 = L : Constant torque for parallel motors or special motors
1 = P : Variable torque
2 = n : Sensorless flux vector control for applications with constant torque.
3 = nLd : energy saving for applications with variable torque
0 = nO
1 = YES
Deceleration ramp adaptation
(avoids switch to obF fault)
0.1 Hz Ramp switching threshold
(Switch to AC2 and dE2 if output frequency
> FrT and FrT
≠
0)
Can be adjusted whilst operating
If a logic input is assigned to the ramp switching threshold function (rP2), this parameter is not accessible.
0 to HSP
34
Altivar 28 Variables
I/O configuration parameters
(read and write)
These parameters may only be adjusted with the motor stopped.
Word
W100
W101
W102
W103
Code
LI1
LI2
LI3
LI4
Description
Assignment of logic input "LI1"
Write protected
Possible values or range
0 = Not assigned (local control option present,
tCC = OPt)
1 = Stop (if tCC = 3C)
2 = Forward operation (if tCC = 2C)
Assignment of logic input "LI2"
Write protected if tCC = 3C
0 = nO : Not assigned
2 = For : Forward operation. (If tCC = 3C)
3 = rrS : Reverse operation
4 = rP2 : Ramp switching
5 = JOG : Jog operation
8 = PS2 : 2 preset speeds
9 = PS4 : 4 preset speeds
10 = PS8 : 8 preset speeds
11 = rFC : Reference switching
12 = nSt : Freewheel stop
13 = dCI : Injection stop
14 = FSt : Fast stop
17 = FLO : Forced local
18 = rSt : Clear faults
Assignment of logic input "LI3" 0 = nO : Not assigned
3 = rrS : Reverse operation
4 = rP2 : Ramp switching
5 = JOG : Jog operation
8 = PS2 : 2 preset speeds
9 = PS4 : 4 preset speeds
10 = PS8 : 8 preset speeds
11 = rFC : Reference switching
12 = nSt : Freewheel stop
13 = dCI : Injection stop
14 = FSt : Fast stop
17 = FLO : Forced local
18 = rSt : Clear faults
Assignment of logic input "LI4" 0 = nO : Not assigned
3 = rrS : Reverse operation
4 = rP2 : Ramp switching
5 = JOG : Jog operation
8 = PS2 : 2 preset speeds
9 = PS4 : 4 preset speeds
10 = PS8 : 8 preset speeds
11 = rFC : Reference switching
12 = nSt : Freewheel stop
13 = dCI : Injection stop
14 = FSt : Fast stop
17 = FLO : Forced local
18 = rSt : Clear faults
35
Altivar 28 Variables
I/O configuration parameters
(read and write)
These parameters may only be adjusted with the motor stopped.
Word
W107
Code Description
AI2 Assignment of analogue input
"AIC / AI2"
W110
W112 r2 Assignment of relay "R2"
AO Assignment of analogue output "AO"
Possible values or range
0 = nO : Not assigned
3 = SAI : Summing reference
4 = PIA : PI feedback
(PI regulator with AI1 reference)
8 = PII : PI feedback
(PI regulator with internal reference)
0 = nO : Not assigned
4 = FtA : Frequency threshold (Ftd) reached
6 = CtA : Current threshold (Ctd) reached
7 = SrA : Frequency reference reached
8 = tSA : Thermal threshold (ttd) reached
0 = nO : Not assigned
1 = OCr : Motor current
2 = rFr : Motor frequency
4 = OLO : Motor torque
5 : OPr : Motor rating
Fault configuration parameters
(read and write)
These parameters may be adjusted with the motor stopped or running.
Word
W150
W151
W152
W155
W156
W190
Code
Atr
OPL
IPL
FLr
Description
Automatic restart
Motor phase loss
Line supply phase loss
Catch a spinning load
Possible values or range
0 = nO
1 = YES
2 = On USF fault (in 2-wire control)
0 = nO
1 = YES
0 = nO
1 = YES
0 = nO
1 = YES
StP drn
Controlled stop on line supply loss 0 = nO
1 = YES
Downgraded operation on line supply at -
40%
0 = nO
1 = YES
36
Altivar 28 Variables
W253
W254
W255
W258
W259
W260
W261
W262
W264
W265
W266
W267
Adjustment parameters
(read and write)
These parameters may be adjusted with the motor stopped or running.
Word
W250
Code Unit Description
HSP 0.1 Hz High speed
Possible values or range
LSP to tFr
W251
W252
LSP 0.1 Hz Low speed 0 to HSP
ACC 0.1 s Acceleration
(Time between 0 and 50/60 Hz) dEC 0.1 s Deceleration
(Time between 50/60 Hz and 0)
UFr 1 % IR compensation
0 : ramp 0.05 s (special case)
1 to 36000 : ramp 0.1 s to 3600 s
0 : ramp 0.05 s (special case)
1 to 36000 : ramp 0.1 s to 3600 s
0 to 100
FLG 1 % Frequency loop gain
ItH 0.1 A Thermal protection current
SLP 0.1 Hz Slip compensation
0 to 100
0.5 x INV to 1.15 x INV
INV = speed controller nominal current
0 to 50
AC2 0.1 s Acceleration 2
(Time between 0 and 50/60 Hz) dE2 0.1 s Deceleration 2
(Time between 50/60 Hz and 0)
JOG 0.1 Hz JOG frequency
(Jog operation)
SP2 0.1 Hz Preset speed 2
0 : ramp 0.05 s (special case)
1 to 36000 : ramp 0.1 s to 3600 s
0 : ramp 0.05 s (special case)
1 to 36000 : ramp 0.1 s to 3600 s
0 to 100
LSP to HSP
SP3 0.1 Hz Preset speed 3
SP4 0.1 Hz Preset speed 4
SP5 0.1 Hz Preset speed 5
LSP to HSP
LSP to HSP
LSP to HSP
37
Altivar 28 Variables
W281
W282
W283
W284
W286
W287
W340
W271
W272
W279
W280
Adjustment parameters
(read and write)
These parameters may be adjusted with the motor stopped or running.
Word
W268
Code Unit Description
SP6 0.1 Hz Preset speed 6
Possible values or range
LSP to HSP
W269
W270
SP7 0.1 Hz Preset speed 7
IdC 0.1 A Injection current tdC 0.1 s Injection time
(In the case of automatic injection on stopping) tLS 0.1 s Maximum time at low speed
(LSP) rPG 0.01
PI proportional gain rIG 0.01/s PI integral gain
LSP to HSP
0.1 ItH to INV
(INV = speed controller nominal current)
0 to 254 = time 0.0 s to 25.4 s
255 = CONT : continuous injection
0 = NO : no limit
1 to 255 = time from 0.1 s to 25.5 s
1 to 10000 (gain from 0.01 to 100)
1 to 10000 (gain from 0.01/s to 100/s)
FbS
Ctd ttd
Ftd
0,1
0.1 A
PI feedback scale factor
Current threshold reached
1 % Thermal threshold reached
0.1 Hz Frequency threshold reached
1 to 1000 (factor 0.1 to 100)
0.1 x INV to 1.5 x INV
INV. = speed controller nominal current
1 to 118
0 to HSP
JPF 0.1 Hz Skip frequency on a frequency range of ± 1 Hz around the adjusted value
PIC Reversal of direction of correction of PI regulator
0 to HSP
0 = nO
1 = YES rOt Control of operating direction with
"local control" option.
This parameter is only accessible in read mode.
0 = FOr : forward
1 = rrS : reverse
38
Altivar 28 Variables
Control parameters
(read and write)
Word
W400
W401
Code
CMD
Unit Description
DRIVECOM control register
Parameter reinitialized at end of "time-out" unless bit 14 of CMI is set to 1 (W402)
LFR 0.1 Hz Frequency reference in line mode (signed in two’s complement)
Parameter reinitialized at end of "time-out" unless
bit 14 of CMI is set to 1 (W402)
Possible values or range
Bit 0 = 0 and Bit 15 = 0 : Not ready
Bit 1 = 0 and Bit 15 = 0 : Ready
Bit 1 = 0 : Return to "Switch ON disabled" status
Bit 1 = 1 : No action
Bit 2 = 0 and Bit 15 = 0 : Emergency stop
Bit 2 = 1 : No action
Bit 3 = 0 and Bit 15 = 0 : DRIVECOM stop command
Bit 3 = 1 and Bit 15 = 0 : DRIVECOM run command
Bits 4 to 6: Reserved
Bit 7 = 0 : No action
Bit 7 = 1 : Reset faults
Bit 8 = 0 and Bit 15 = 1 : Activate control via serial link
Bit 8 = 1 and Bit 15 = 1 : Deactivate control via serial link
Bits 9 and 10 : Reserved
Bit 11 = 0 : Normal direction command
Bit 11 = 1 : Reverse direction command
Bit 12 = 0 : Motor running command (RUN)
Bit 12 = 1 : Motor stop command
Bit 13 = 0 : No action
Bit 13 = 1 : Stop by DC injection command
Bit 14 = 0 : No action
Bit 14 = 1 : Fast stop command
Bit 15 = 0 : DRIVECOM control register
Bit 15 = 1 : Drive control register
LSP to HSP
39
Altivar 28 Variables
Control parameters
(read and write)
Word
W402
W440
Code Unit Description
CMI Internal control register (application program)
Parameter reinitialized at end of "time-out" unless bit 14 of CMI is set to 1
Possible values or range
Bit 0 = 0 : No action
Bit 0 = 1 : (1) Return to factory settings.
This bit automatically resets to 0 after accepting the request.
Bit 1 = 0 : No action
Bit 1 = 1 : (1) Memorize in EEPROM configuration and adjustment words which have been the object of a write request. This bit must be reset to 0 by the
PLC after accepting the request.
Bit 2 = 0 : No action
Bit 2 = 1 : (1) Return to parameters memorized in
EEPROM (cancel write operations). This bit must be reset to 0 by the PLC after accepting the request.
Bit 3 : Reserved
Bit 4 = 0 : No action
Bit 4 = 1 : Ramp switching command
Bits 5 to 12 : Reserved
Bit 13 = 0 : Speed controller not locked on stop
Bit 13 = 1 : Speed controller locked on stop
Bit 14 (NTO) = 0 : Control with monitoring of communication.
Bit 14 (NTO) = 1 : Control without monitoring of communication.
For safety reasons this should be reserved for the debug phase.
rPI
Bit 15 : Reserved
0 to 1000 0.1% PI regulator internal setpoint
(if AIC / AI2 = PII)
(1) Each action of bits 0, 1, and 2 of W402 is only accepted if the motor is stopped and the speed controller powered up without a USF fault. When accepted, it interrupts communication while it executes, or for 2 seconds max.
The PLC "time out" must therefore be set to a higher value in order to avoid tripping.
During this time the speed controller display indicates :
•
I n
•
N E t to return to factory settings and to return to EEPROM parameters (bits 0 and 2) to memorize write operations in EEPROM (bit 1).
If several of these bits are activated simultaneously, the following priorities are respected :
• bit 0 has priority over bits 1 and 2
• bit 1 has priority over bit 2
40
Altivar 28 Variables
W453
W454
W455
W456
Word
W450
W451
W452
W457
Monitoring parameters
Read only, except for outputs if not assigned
Code Unit Description
FrH 0.1Hz
Frequency reference
(absolute value)
Possible values or range
Value read rFr 0.1Hz
Output frequency applied to motor
(absolute value)
SPd 1 Motor speed estimated by speed controller (absolute value)
Value read
Value read
LCr 0.1A
Current in motor Value read
ULn 0.1V
Line voltage
(from bus) tHr 1% tHd
LFt
1%
Motor thermal state
(100 % = Nominal thermal state, 118 % = OLF threshold)
Speed controller thermal state
(100 % = Nominal thermal state, 118 % = OHF threshold)
Last fault
Value read
Value read
Value read
0 = nOF : No fault memorized
1 = InF : Internal fault
2 = EEF : EEPROM memory fault
5 = SLF : Serial link fault
(link break)
9 = OCF : Overcurrent fault
16 = OHF : Speed controller overheating fault
(on heatsink)
17 = OLF : Motor overload fault
18 = ObF : DC bus overvoltage fault
19 = OSF : Line supply overvoltage fault
20 = OPF : Motor phase failure fault
21 = PHF : Line supply phase failure fault
23 = SCF : Motor short circuit fault
(phase, earth)
25 = tnF : Autotuning fault
41
Altivar 28 Variables
Monitoring parameters
Read only, except for outputs if not assigned
Word
W458
Code Description
ETA DRIVECOM speed controller status register
Possible values or range
Bit 0 = 0 : Power not ready
Bit 0 = 1 : Power ready for startup
Bit 1 = 0 : Speed controller not ready
Bit 1 = 1 : Speed controller ready (rdY)
Bit 2 = 0 : DRIVECOM stop
Bit 2 = 1 : DRIVECOM run
Bit 3 = 0 : Fault absent
Bit 3 = 1 : Fault present (FAI)
Bit 4 = 0 : Power present
Bit 4 = 1 : Power absent
Bit 5 = 0 : Emergency stop in progress
Bit 5 = 1 : Emergency stop absent
Bit 6 = 0 : Status
≠
SWITCH ON DISABLED (freewheel stop)
Bit 6 = 1 : Status
≠
SWITCH ON DISABLED (freewheel stop)
Bit 7 = 0 : Alarm absent
Bit 7 = 1 : Alarm present
Bit 8 = Reserved
Bit 9 = 0 : Forced local in progress (FLO)
Bit 9 = 1 : Forced local absent
Bit 10 = 0 : Reference not reached (transient state)
Bit 10 = 1 : Reference reached (steady state)
Bit 11 = 0 : LFRD reference normal
Bit 11 = 1 : LFRD reference exceeded (> HSP or < LSP)
Bits 12 and 13 : Reserved
Bit 14 = 0 : No stop from STOP key
(remote keypad)
Bit 14 = 1 : Stop from STOP key
(remote keypad)
Bit 15 = 0 : Forward direction of rotation (output frequency)
Bit 15 = 1 : Reverse direction of rotation (output frequency)
42
Altivar 28 Variables
Monitoring parameters
Read only, except for outputs if not assigned
Word
W459
W460
W461
Code Description
ETI Speed controller internal status register no. 1
ETI2 Speed controller internal status register no. 2
ETI3 Speed controller internal status register no. 3
Possible values or range
Bits 0 to 3: Reserved
Bit 4 = 0 : Motor stopped
Bit 4 = 1 : Motor running
Bit 5 = 0 : No DC injection
Bit 5 = 1 : DC injection
Bit 6 = 0 : Speed controller in steady state
Bit 6 = 1 : Speed controller in transient state
Bit 7 = 0 : No thermal overload alarm
Bit 7 = 1 : Thermal overload alarm
Bit 8 = 0 : No alarm if excessive braking
Bit 8 = 1 : Alarm if excessive braking
Bits 9 and 10 = Reserved
Bit 11 = 0 : No current limit alarm
Bit 11 = 1 : Current limit alarm
Bit 12 = Reserved
Bit 14 = 0, Bit 13 = 0 : Drive controlled via terminals
Bit 14 = 0, Bit 13 = 1 : Drive controlled via remote keypad
Bit 14 = 1, Bit 13 = 0 : Drive controlled via serial link
Bit 15 = 0 : Forward direction of rotation requested (reference)
Bit 15 = 1 : Reverse direction of rotation requested (reference)
Bits 0 to 3: Reserved
Bit 4 = 0 : Speed reference not reached
Bit 4 = 1 : Speed reference reached
Bit 5 = 0 : Frequency threshold (Ftd) not reached
Bit 5 = 1 : Frequency threshold (Ftd) reached
Bit 6 = 0 : Current threshold (Ctd) not reached
Bit 6 = 1 : Current threshold (Ctd) reached
Bits 7 to 15: Reserved
Reserved
43
Altivar 28 Variables
W464
W466
W468
W478
Monitoring parameters
Read only, except for outputs if not assigned
Word
W462
W479
W480
W482
Code
DP1
Unit Description
Past fault No. 1
Possible values or range
0 = nOF : No fault memorized
1 = InF : Internal fault
2 = EEF : EEPROM memory fault
5 = SLF : Serial link fault (link break)
9 = OCF : Overcurrent fault
16 = OHF : Speed controller overheating fault
17 = OLF : Motor overload fault
18 = ObF : DC bus overvoltage fault
19 = OSF : Line supply overvoltage fault
20 = OPF : Motor phase failure fault
21 = PHF : Line supply phase failure fault (> 1s)
23 = SCF : Motor short circuit fault (phase, earth)
25 = tnF : Autotuning fault
Same format as DP1 (W462) DP2
DP3
Past fault No. 2
Past fault No. 3 Same format as DP1 (W462)
Same format as DP1 (W462) DP4 Past fault No. 4
IOLR Image of logic I/O
Bit 0 = Image of logic input "LI1" (active at 1)
Bit 1 = Image of logic input "LI2" (active at 1)
Bit 2 = Image of logic input "LI3" (active at 1)
Bit 3 = Image of logic input "LI4" (active at 1)
Bits 4 to 7: Reserved
Bit 8 = Image of relay "R1" (active at 1)
Bit 9 = Image of relay "R2" (active at 1)
Write authorized if r2 = "nO" (not assigned),
Bits 10 to 15: Reserved
Value read AI1R 0.001V
Image of analog input "AI1"
(actual size calibrated and scaled)
AI2R 0.001mA Image of analog input "AIC / AI2"
(actual size calibrated and scaled)
AOR 0.001mA Image of analog output "AO"
Value read
Write authorized if AO = "nO" (not assigned) :
0 to 20000
Read only if AO is assigned : Value read
44
Altivar 28 Variables
Monitoring parameters
Read only, except for outputs if not assigned
Word
W483
W484
W487
W491
W530
W551
W552
W553
W555
Code
DF1
DF2
OLO
OPr
Unit
1%
1%
Description
Register of active faults No. 1
(no fault if bit = 0)
Register of active faults No. 2
(no fault if bit = 0)
Motor torque
Output power
Possible values or range
Bit 0 = 1 : Incorrect calibration constants (InF)
Bit 1 = 1 : Unknown speed controller rating (InF)
Bit 2 = 1 : Unknown or incompatible hardware (InF)
Bit 3 = 1 : Control card EEPROM fault (EEF)
Bits 4 to 7: Reserved
Bit 8 = 1 : Serial link fault (SLF)
Bits 9 to 12: Reserved
Bit 13 = 1 : Motor short circuit (SCF)
Bits 14 and 15 : reserved
Bits 0 to 2: Reserved
Bit 3 = 1 : Overcurrent fault (OCF)
Bits 4 to 6: Reserved
Bit 7 = 1 : Speed controller overheating fault (OHF)
Bit 8 = 1 : Motor overload fault (OLF)
Bit 9 : Reserved
Bit 10 = 1 : DC bus overvoltage fault (ObF)
Bit 11 = 1 : Line supply overvoltage fault (OSF)
Bit 12 = 1 : Motor phase failure fault (OPF)
Bit 13 = 1 : Line supply phase failure fault (PHF)
Bit 14 = 1 : Line supply undervoltage fault (USF)
Bit 15 = 1 : Control card power supply fault (InF)
Value read
100% = nominal motor torque
Value read
100% = nominal motor power
Value read TIM 1 H Cumulative operating time in hours
CPU Software version of speed controller
Bits 0 to 7: hexadecimal upgrade index
Bits 8 to 15: software version in hexadecimal format
NCV
VCAL
Speed controller power rating
Speed controller voltage rating
4 = U09 ; 5 = U18 ; 6 = U29 ; 7 = U41 ; 8 = U54
10 = U72 ; 11 = U90 ; 12 = D12 ; 13 = D16
14 = D23
1 = Single phase 200 / 240 V
2 = 3-phase 380 / 500 V
3 = 3-phase 200 / 230 V
INV 0.1 A Speed controller nominal current
Value read
45
Altivar 28 Variables
Special "DRIVECOM" parameters
(read and write)
Use of parameters W603 to W615 necessitates a special configuration of parameter SdS (W41) in drive parameter menu drC- :
SdS = 60/p where p = number of pairs of poles in motor.
Example : motor 1450 Rpm (revolutions per minute) at 50Hz : 4-pole motor, so SdS = 30.
This parameter enables the speed controller to establish the relationship between the frequency in Hz and the speed in Rpm.
Word
W600
W601
W602
W603
W604
W605
W606
W607
Code
ERRD
Unit Description
Error code (603FH)
Write protected
Possible values or range
0 = nOF : No fault
1000H = OLF : Motor overload fault
2310H = OCF : Overcurrent fault
3110H = OSF : Line supply overvoltage fault
3120H = USF : Line supply undervoltage fault
3130H = PHF : Line supply phase failure fault
3310H = ObF : DC bus overvoltage fault or
3310H = OPF : Motor phase failure fault
4210H = OHF : Speed controller overheating fault
5520H = EEF : EEPROM memory fault
6100H = InF : Internal fault
7510H = SLF : Serial link fault
CMDD
ETAD
Control word
Same as parameter "CMD"
(W400)
Status word
Same as parameter "ETA"
(W458)
Write protected
LFRD 1 Rpm Speed reference
(reference not peak limited)
- 32768 to 32767
FRHD 1 Rpm Ramp output signed
Write protected
- 32768 to 32767
RFRD 1 Rpm Motor speed
Write protected
0 to 65535
SMIL 1 Rpm Low speed, equivalent to
LSP (W251), but in revolutions/minute
SMIH Reserved
0 to (HSP x SdS)
0
W608
W609
SMAL 1 Rpm High speed, equivalent to
HSP (W250), but in revolutions/minute
SMAH Reserved
(LSP x SdS) to (tFr x SdS)
0
46
Altivar 28 Variables
Special "DRIVECOM" parameters
(read and write)
Word
W610
W611
W612
W613
W614
W615
Code Unit Description
SPAL 1 Rpm Speed for calculating the acceleration ramp
SPAH Reserved
Possible values or range
1 to 65535
0
SPAT 1 s Time for calculating the acceleration ramp
Time to go from 0 to SPAL
(W610)
SPDL 1 Rpm Speed for calculating the deceleration ramp
0 to 65535
1 to 65535
SPDH Reserved 0
SPDT 1 s Time for calculating the deceleration ramp
Time to go from SPDL
(W613) to 0
0 to 65535
47
W107 to
W112
W150 to
W190
W250 to
W267
W268 to
W340
Address
W4 to
W55
W59 to
W65
W100 to
W103
W400 to
W401
W402 to
W440
W450 to
W457
W458
W459 to
W461
W462 to
W482
W483 to
W555
W600 to
W609
W610 to
W615
48
Index of addresses
Description
General configuration parameters
General configuration parameters
I/O configuration parameters
I/O configuration parameters
Fault configuration parameters
Adjustment parameters
Adjustment parameters
Control parameters
Control parameters
Monitoring parameters
Monitoring parameters
Monitoring parameters
Monitoring parameters
Monitoring parameters
Special "DRIVECOM" parameters
Special "DRIVECOM" parameters
Page
VVDED399064
27454
W9 1494186 01 11 A01
1999-11
Download
Advertisement
Key features
RS485 serial link
DRIVECOM standard
Adjustable speed
Adjustable frequency
Adjustable voltage
Motor monitoring
Fault detection
Adjustable parameters
Internal communication variables
Frequently asked questions
The DRIVECOM standard defines the variable speed controller control process using the serial link and the internal variables for the speed controller.
You can modify the speed controller status by sending a control word (CMD) or by the occurrence of an event (example: lock following malfunction). The speed controller status is given by the value of the status register (ETA).
The following parameters can be adjusted with the motor running: SdS (W41), SFr (W51), nrd (W60), and Frt (W65).