Graco 308504D Owner's Manual

INSTRUCTIONS-PARTS LIST 308–504 Rev. D Supersedes C This manual contains important warnings and information. READ AND KEEP FOR REFERENCE. INSTRUCTIONS H2O PROt Continuous Flow System 100 psi (0.7 MPa, 7 bar) Maximum Working Air and Fluid Pressure Part No. 237–928 Waterborne Voltage Block For use with Graco PRO 5500wbt and PRO 3500wbt guns when electrostatically spraying conductive, waterborne fluids that meet at least one of the following conditions of nonflammability: 1. The fluid has a flash point above 140_F (60_C) and a maximum organic solvent concentration of 20%, by weight, as determined in accord with the Standard Method of Testing for Flash Point by the PenskyMartens Closed Tester, ASTM D93. 2. The fluid does not sustain burning characteristics in accordance with the Standard Method for Sustained Burning of Liquid Mixtures by the Setaflash Apparatus, ASTM D4206. U.S. Patent No. 5,526,986 05307A GRACO INC. P.O. BOX 1441 MINNEAPOLIS, MN ECOPYRIGHT 1995, GRACO INC. Graco Inc. is registered to I.S. EN ISO 9001 55440–1441 Table of Contents Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3. . . Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ... Voltage Block Component Identification . . . . . . . . 7 Sequence of Operation . . . . . . . . . . . . . . . . . . . . . .10 . Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 .. Warning Signs . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 .. Ventilate the Spray Booth . . . . . . . . . . . . . . . . . .12 . Fluid Supply Unit . . . . . . . . . . . . . . . . . . . . . . . . 12 .. Air Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 .. Leveling the Voltage Block . . . . . . . . . . . . . . . . . 12 . Remote Terminal Strip . . . . . . . . . . . . . . . . . . . . .13 . Interlock the Gun Turbine Air Supply . . . . . . . . .13 Connect the Hoses . . . . . . . . . . . . . . . . . . . . . . . 14 .. Ground the System. . . . . . . . . . . . . . . . . . . . . . . .16 . Check the System Grounding . . . . . . . . . . . . . . 16 . Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 ... Fluid Voltage Discharge and Grounding Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 .. Pressure Relief Procedure . . . . . . . . . . . . . . . . . 19 . Emergency Fluid Shutoff . . . . . . . . . . . . . . . . . . .19 . Operating Checklist . . . . . . . . . . . . . . . . . . . . . . .19 . 2 308–504 Voltage Block Startup Procedure . . . . . . . . . . . . .20 Operating the Voltage Block . . . . . . . . . . . . . . . . 22 . Flushing and Shutdown . . . . . . . . . . . . . . . . . . . .23 . Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 .. Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 .. Cycle Counting . . . . . . . . . . . . . . . . . . . . . . . . . . 27 .. TSL System Maintenance . . . . . . . . . . . . . . . . . .27 . PTFE Tubing Replacement . . . . . . . . . . . . . . . 27 . Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 ... Isolator Service . . . . . . . . . . . . . . . . . . . . . . . . . . 28 .. Accumulator Service . . . . . . . . . . . . . . . . . . . . . .33 . Voltage Block Assembly Parts . . . . . . . . . . . . . . . 36 . Accumulator Assembly Parts . . . . . . . . . . . . . . . . 40 . Isolator Assembly Parts . . . . . . . . . . . . . . . . . . . . .42 . Air Logic Schematic and Parts . . . . . . . . . . . . . . . 44 . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45 .. Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46 .. The Graco Warranty and Disclaimers . . . . . . . . . .48 Graco Phone Number . . . . . . . . . . . . . . . . . . . . . . .48 . Symbols Warning Symbol Caution Symbol WARNING CAUTION This symbol alerts you to the possibility of serious injury or death if you do not follow the instructions. This symbol alerts you to the possibility of damage to or destruction of equipment if you do not follow the instructions. WARNING FIRE AND EXPLOSION HAZARD Improper grounding, poor air ventilation, open flames, or sparks can cause a hazardous condition and result in a fire or explosion. Electrostatic equipment must be used only by trained, qualified personnel who understand the requirements stated in this instruction manual. Ground the equipment, personnel in or close to the spray area, the object being sprayed, and all other electrically conductive objects in the spray area. See Ground the System on page 16. Provide fresh air ventilation to avoid the buildup of toxic vapors. Interlock the automatic gun air supply to prevent operation of the power supply unless the ventilating fans are on. See Ventilate the Spray Booth on page 12. Only use this equipment to spray non-flammable, waterborne fluids, as defined on the front cover of this manual. Only flush, purge, or clean the electrostatic, waterborne spray system with non-flammable fluids, as defined on the front cover of this manual. Do not flush the system with the gun electrostatics turned on. Use only non-sparking tools to clean residue from the booth and hangers. Extinguish all open flames or pilot lights in the spray area. Keep the spray area free of debris, including solvent, rags, and gasoline. Do not store any flammable fluids in the spray area. Do not turn on or off any light switch in the spray area while operating or if fumes are present. Do not smoke in the spray area. Do not operate a gasoline engine in the spray area. Warnings are continued on the next page. 308–504 3 WARNING ELECTRIC SHOCK HAZARD Improper grounding or an improper setup and usage of the voltage block system can cause a hazardous condition and result in an electric shock or other serious injury. Ground the equipment, personnel in or close to the spray area, the object being sprayed, and all other electrically conductive objects in the spray area. See Ground the System on page 16. The components of the voltage block system that are charged with high voltage when the spray gun is operating are inside the voltage block enclosure to make these components inaccessible to personnel and prevent electric shock. The enclosure door must be closed when any gun connected to the system is operating. The enclosure door has a switch that moves the isolator to discharge the voltage if the door is opened, which helps prevent personnel from making contact with the components when they are charged with high voltage. Do not tamper with or bypass the door switch or other safety devices. The automatic gun air supply must be interlocked with the voltage block system to shut of f the turbine air supply whenever the enclosure door is opened. Only use the red-colored Graco electrically conductive gun air hose with this system. Do not use the black or grey-colored Graco air hoses. The areas of the Graco waterborne fluid hose that are accessible to the personnel must be covered by the conductive, grounded hose layer. The area on the hose that is not covered by the conductive hose layer must be inside the voltage block system enclosure. Install only one continuous Graco waterborne fluid hose between the voltage block system and the spray gun. Do not splice hoses together. Follow the Fluid Voltage Discharge and Grounding Procedure on page 18 when instructed to discharge the voltage; before cleaning, flushing, or servicing the system; before approaching the gun; and when opening the voltage block enclosure door. Do not touch the gun electrode or come within 4 inches (101.6 mm) of the nozzle during gun operation until the Fluid Voltage Discharge and Grounding Procedure , page 18, has been completed. Do not enter a high voltage or hazardous area until all high voltage equipment has been discharged. If there is any static sparking while using the equipment, stop spraying immediately. Identify and correct the problem. Follow the warnings and instructions in the spray gun manual. PRESSURIZED EQUIPMENT HAZARD Spray from the gun, hose leaks, or ruptured components can splash fluid in the eyes or on the skin and cause a serious injury. Do not stop or deflect fluid leaks with your hand, body, glove, or rag. Follow the Pressure Relief Procedure on page 19 whenever you: are instructed to relieve the pressure; stop spraying; clean, check, or service the equipment; and install or clean the fluid nozzles. Tighten all the fluid connections before each use. Check the hoses, tubes and couplings daily. Replace worn, damaged, or loose parts immediately. Permanently coupled hoses cannot be repaired; replace the entire hose. 4 308–504 Warnings are continued on the next page. WARNING EQUIPMENT MISUSE HAZARD INSTRUCTIONS Equipment misuse can cause the equipment to rupture, malfunction, or start unexpectedly and result in a serious injury. Only use the Graco PRO 5500wb automatic gun or PRO 3500wb hand-held gun with this system. This equipment is for professional use only. Read all the instruction manuals, tags, and labels before operating the equipment. Use the equipment only for its intended purpose. If you are uncertain about usage, call your Graco distributor. Do not alter or modify this equipment. Use only genuine Graco parts and accessories. Check the equipment daily. Repair or replace worn or damaged parts immediately. Do not exceed the maximum working pressure of the lowest rated system component. This equipment has a 100 psi (0.7 MPa, 7 bar) maximum working air and fluid pressure . Do not lift pressurized equipment. Use fluids that are compatible with the equipment wetted parts. See the Technical Data section of all the equipment manuals. Read the fluid manufacturer’s warnings. Do not use MEK or any ketone solvent mixture to flush the system. Route the hoses away from traffic areas, sharp edges, moving parts, and hot surfaces. Do not expose Graco hoses to temperatures above 180F (82C) or below –40F (–40C). Do not use the hoses to pull equipment. Comply with all applicable local, state, and national fire, electrical, and other safety regulations. TOXIC FLUID HAZARD Hazardous fluids or toxic fumes can cause a serious injury or death if splashed in the eyes or on the skin, swallowed, or inhaled. Know the specific hazards of the fluid you are using. Read the fluid manufacturer ’s warnings. Store hazardous fluid in an approved container. Dispose of the hazardous fluid according to all local, state, and national guidelines. Wear appropriate protective clothing, gloves, eyewear, and respirator. MOVING PARTS HAZARD Moving parts can pinch or amputate fingers. Keep clear of moving isolator parts. 308–504 5 6 308–504 Voltage Block Component Identification 20 Fluid Pressure Air Pilot Regulator The air pilot regulator is used to adjust the pressure setting of the fluid regulator (2) at the voltage block fluid outlet. 72 Fluid Pressure Gauge The gauge shows the air pilot regulator (20) pressure, which controls the fluid regulator (2) pressure. See Fig. 2 YY Remote Terminal Strip 72 The remote terminal strip provides 8 ports for sending input or output signals to operate the system remotely. See page 13. 20 A B C Fig. 1 ZZ Optional Pneumatic Counter Kit (purchased separately) 05316 See Fig. 1. Refer to Fig. 2 and 3. A Fill/Run Button The Fill/Run Button is pressed to initially fill the accumulators (74) or restart operation after a period when spraying had stopped or the door has been opened. B Flush/Reset Button The pneumatic counter kit, part no. 238–026, counts the number of isolator cycles for maintenance tracking. 99 Air Logic Assembly The air logic assembly is mounted inside, on the enclosure door. It receives and sends signals that enable the voltage block to operate properly. No adjustments to the air logic assembly are necessary. Do not alter components or connections. The Flush/Reset Button has the following uses: To reset the air logic assembly (99) components when initially starting the system or when the air logic was shut down due to air supply depressurization. ZZ YY To pressurize the accumulators (74) to prepare to flush the system. To prepare to empty the accumulators (74) and depressurize the voltage control fluid section before shutting down the system. 99 To stop the filling process. C Optional kV Display (purchased separately) The kV display, part no. 238–095, is an accessory that can be added to the voltage block to provide a system voltage reading. 05826 Fig. 2 308–504 7 Voltage Block Component Identification 13 22 90 76 77 53 74 4 138 waste supply 43 75 106 D 103 2 SIDE 1 SIDE 2 SIDE 1 SIDE 2 05315B Fig. 3 See Fig. 3 2 D The voltage block fluid regulator regulates the fluid pressure to the gun. The setting is adjusted with the air pilot regulator (20–see Fig. 1). A small air bleed hole constantly bleeds the pilot air for fluid control accuracy. Graco Waterborne Fluid Hose (purchased separately) A Graco waterborne fluid hose must be used between the voltage block fluid regulator (2) outlet and the spray gun. This fluid hose consists of three layers (see Fig. 5, page 15): Inner Hose Layer: is a PTFE tube. Conductive Hose Layer: covers the PTFE tube. Outer Hose Jacket: is a protective polyethylene hose cover. If a hose failure occurs, where the high voltage arcs through the PTFE core, the voltage will be discharged to ground through the conductive hose layer. When properly installed, the hose is grounded through its connection to the enclosure. All areas of the fluid hose that are accessible to personnel must be covered by the conductive hose layer. 8 308–504 4 Fluid Regulator TSL Supply Bottle The TSL supply bottle contains fresh throat seal liquid (TSL) for lubricating the isolator assembly (75) rod and seals. 13 Air Inlet Quick-disconnect The connector for the voltage block air supply hose. The quick-disconnect allows for quick disconnection of the air line to shutdown the system in an emergency. 22 Voltage Block Air Pressure Regulator This air regulator is used to adjust air pressure to the voltage block components. Voltage Block Component Identification See Fig. 3 43 Voltage Bleed Resistor The voltage bleed resistor completely bleeds off the voltage from the gun in about 30 seconds after the gun trigger is released. The actual time depends on the hose length. 53 Door Switch When the enclosure door is opened, the door switch signals the isolator (75) to ground the fluid in the voltage block and bleed off the high voltage. 74 Accumulator The accumulator is a container inside the voltage block enclosure (106). It fills with fluid from the fluid supply unit and supplies that fluid to the spray gun. The accumulator has a full level switch (76) and low level switch (77) for the fluid. 75 Isolator The isolator can move up or down on the isolator rod. The position the isolator is in depends on which operating phase the voltage block is in. Spraying Position: is the upward position of the isolator. This position isolates the waterborne fluid in the accumulator (74) (which is connected to the isolator) from the fluid supply (which is at ground) and enables the fluid to be sprayed electrostatically. Fill Position: is the downward position of the isolator. In this position, the valve in the isolator rod opens so the accumulator (74) can be refilled by the fluid supply. 76 Full Level Switch When the accumulator (74) is filling, the full level switch sets the maximum amount of fluid the accumulator will allow. To reduce the number of times the accumulator has to refill and decrease the wear on the equipment, set the full level at the highest setting. 77 Low Level Switch When the fluid in the accumulator (74) reaches this switch and the gun is triggered, the Voltage Block will begin supplying fluid to the spray gun from the second accumulator and will also refill the accumulator that is low on fluid. 90 TSL Pump The TSL pump circulates the TSL through the isolator (75) fluid block and seals. 103 Fluid Inlet Connector The connector for the voltage block fluid supply hose. 106 Enclosure The enclosure houses the internal components of the voltage block and helps prevent personnel from coming in contact with the components when they are charged with high voltage. 138 TSL Waste Bottle The TSL waste bottle receives the used throat seal liquid (TSL). See Fig. 4, page 15 25 Ground Lug The ground lug is used to ground the voltage block by connecting the main ground wire (123) between the lug and a true earth ground. 123 Main Ground Wire The ground wire is connected between the ground lug (25) and a true earth ground. 308–504 9 Sequence of Operation The following charts show the sequence of how the system or voltage block operates during various operation modes. The charts do not cover how to actually operate the system or voltage block. For operating instructions, see the Operation section. NOTE: Refer to Fig. 3, page 8. Key: Vented – accumulator is filling Pressurized – accumulator is dispensing fluid Air Blocked – accumulator piston is holding its current position, it is neither filling or dispensing. FILL/RUN FILL Sequence Isolator 1 Position Accumulator 1 Isolator 2 Position Accumulator 2 1. Accumulator 1 starts filling down vented up pressurized 2. Accumulator 1 is full down vented up pressurized 3. Accumulator 1 dispenses to Accumulator 2 up pressurized down vented 4. Accumulator 2 is full up pressurized down air blocked 5. Accumulator 1 starts refilling down vented up air blocked 6. Accumulator 1 is full up pressurized down air blocked 7. System is ready to spray up pressurized down air blocked Isolator 1 Position Accumulator 1 Isolator 2 Position Accumulator 2 1. Accumulator 1 dispenses to spray gun up pressurized down air blocked 2. Accumulator 1 is empty down vented up pressurized 3. Accumulator 2 dispenses to spray gun while Accumulator 1 starts refilling down vented up pressurized 4. Accumulator 1 is full down vented up pressurized 5. Accumulator 1 dispenses to spray gun and refills Accumulator 2 up pressurized down vented 6. Accumulator 2 is full up pressurized down air blocked RUN Sequence Operation Operation 7. Operation continues with the Run Sequence, steps 2 to 6, until the operator stops spraying 10 308–504 Sequence of Operation FLUSH/RESET FLUSH Sequence– through gun Operation Isolator 1 Position Accumulator 1 Isolator 2 Position Accumulator 2 1. Both accumulators dispense to spray gun up pressurized down pressurized 2. Both accumulators are empty down pressurized down pressurized 3. Water supply flushes down through the system until clear fluid is seen pressurized down pressurized 4. Voltage block remains in this mode until the fill sequence is activated pressurized down pressurized down Paint Saver This operation sequence pushes the fluid in the accumulator back into the fluid supply to help save fluid. Refer to page 23. Paint Saver Sequence Operation Isolator 1 Position Accumulator 1 Isolator 2 Position Accumulator 2 1. Both accumulators dispense their fluid back to the depressurized fluid supply or to a container down pressurized down pressurized 2. Both accumulators are empty down pressurized down pressurized 3. Remains in this mode until the enclosure door is closed and the Fill/Run button is pressed. down pressurized down pressurized 308–504 11 Installation IMPORTANT: Only use the Graco PRO 5500wb automatic gun or PRO 3500wb hand-held gun with this system. The instructions in this manual are based on a typical system, where one of these Graco guns would be used. WARNING ELECTRIC SHOCK HAZARD Installing and servicing this equipment requires access to parts which could cause an electric shock or other serious injury if the work is not performed properly. Electrically interlock the gun air supply with the ventilators to prevent operation of the electrostatic power supply unless the ventilating fans are on. Check and follow all local, state, and national codes regarding air exhaust velocity requirements. High velocity air exhaust will decrease the operating efficiency of the electrostatic system. The minimum allowable air exhaust velocity is 60 ft./min. (19 linear meters/min.). Fluid Supply Unit Do not install or service this equipment unless you are trained and qualified. Comply with all local, state, and national codes for the installation of electrical apparatus in a Class I, Group D, Hazardous Location. Comply with all applicable local, state, and national fire, electrical, and other safety regulations. Warning Signs Mount the warning sign, part no. 186–118 (included with the PRO 5500wb automatic gun or PRO 3500wb hand-held gun), in the spray area where it can easily be seen and read by all operators. Read the warning and instruction labels on the enclosure. Additional warning labels and signs are available at no charge. Ventilate the Spray Booth WARNING TOXIC FLUID HAZARD Provide fresh air ventilation to avoid the buildup of toxic vapors. The gun air supply must be interlocked with the ventilators to prevent operation of the electrostatic power supply unless the ventilating fans are on. 12 308–504 WARNING COMPONENT RUPTURE HAZARD To reduce the risk of serious injury due to component rupture, do not exceed the maximum working pressure of the lowest rated system component. This equipment has a 100 psi (0.7 MPa, 7 bar) maximum air and fluid working pressure. Follow the installation instructions in the manual for your fluid supply unit. It is recommended that the fluid be filtered with a 60 mesh filter. Air Supply The air supply must be filtered and dry for the voltage block to operate properly. At a minimum, use a 40 micron filter. A Graco air filter, part no. 106–148, is available. Leveling the Voltage Block The voltage block must be level to ensure proper alignment of the door latches and for system stability. Loosen the jam nut (86) and adjust the leg leveler (12) until the voltage block is level. See the parts drawing on page 36. Installation Remote Terminal Strip The remote terminal strip is mounted on the inside of the clear plastic cover that covers the air logic assembly. See Fig. 2, page 7. There are 8 ports available to connect to for sending or receiving air signals to operate the system remotely from an external control, such as a PLC (programmable logic controller) system. Use polyethylene, 5/32 in. (4 mm) O.D., tubing for connection to the terminal strip ports. This tubing is available from Graco in 100 ft. (30.5 m) lengths. The chart below shows the part numbers and colors. Tubing Part No. Color 054–730 Natural (clear) 054–731 Blue 054–732 Red 054–733 Yellow 054–734 Black NOTE: See page 44 for the air logic assembly schematic. The 8 ports are labeled in the air logic circuit as: #1 FILL/RUN: Accepts an input air signal (minimum 60 psi [410 kPa, 4.1 bar]) from an external source that duplicates the FILL/RUN button on the voltage block door. #2 FLUSH/RESET: Accepts an input air signal (minimum 60 psi [410 kPa, 4.1 bar]) from an external source that duplicates the FLUSH/RESET button on the voltage block door. #3 QUICK DUMP: Accepts an input air signal (minimum 60 psi (410 kPa, 4.1 bar]) from an external source that duplicates the function of opening the voltage block door to initiate the “paint saver” option. In order for this function to operate, the installation must also be set up to activate color change valves to close the paint inlet line and open a dump valve line. #4 FLUID PRESSURE: Accepts an input air signal from an external source that duplicates the air pressure setting from the air pilot regulator on the voltage block door, which controls the fluid regulator. #5 READY TO FLUSH: Sends an output air signal to an external controller or indicator to signal when both of the accumulators have dispensed the fluid and are in their empty position, ready for water flushing. #6 READY TO SPRAY: Sends an output air signal to an external controller or indicator to signal when both of the accumulators are full and have actuated their full level switches. #7 DOOR OPEN: Sends an output air signal to an external controller or indicator to signal when the door switch is activated “open” and it is an unsafe condition for spraying. #8 VOLTAGE DUMP: Accepts an input air signal from an external source that duplicates the door open switch operation that sends both of the isolators down to immediately ground out the high voltage charge of the fluid. Interlock the Gun Turbine Air Supply WARNING ELECTRIC SHOCK HAZARD If the PRO 5500wb Automatic Gun is being used, the turbine air supply must be interlocked with the voltage block system to shut off the turbine air supply anytime the voltage block door is opened. The remote terminal strip must be used to interlock the turbine air supply and the voltage block door, by using the door open port (see description of port #7, above). To reduce the risk of an electric shock, do not tamper with or bypass the air line interlock. 308–504 13 Installation Connect the Hoses 3. Connect the gun air supply line(s) as instructed in the gun manual. WARNING ELECTRIC SHOCK HAZARD To reduce the risk of an electric shock: Install only one continuous Graco waterborne fluid hose between the voltage block and the spray gun. Do not splice hoses together. The areas of the waterborne fluid hose that are accessible to personnel during normal operation must be covered by the outer hose jacket (FF). See Fig. 5. NOTE: If multiple automatic gun operation is needed, contact your Graco representative for ordering requirements for the Multiple Gun Fluid Manifold Kit, part no. 237–965, for the PRO 5500wb Automatic Guns. WARNING ELECTRIC SHOCK HAZARD The Multiple Gun Fluid Manifold Kit can only be used with automatic guns. Regulations applying to this type of equipment prohibit the use of multiple hand-held guns. WARNING ELECTRIC SHOCK HAZARD To reduce the risk of an electric shock or other serious injury, you must use the red Graco Electrically Conductive Air Hose for a hand-held gun’s air supply hose or for an automatic gun’s turbine air hose, and you must connect the hose ground wire to a true earth ground. Do not use the black or grey-colored Graco air hoses. Graco Electrically Conductive Air Hose Part Numbers 100 psi (0.7 MPa, 7 bar) Maximum Working Pressure Conductive SST wire braid for grounding; polyurethane tube and cover; 0.315 inch I.D.; 1/4 npsm(f) x 1/4 npsm(f) left-hand thread; the hose is color-coded red Part No. Length 235–068 235–069 235–070 235–071 235–072 235–073 235–074 6 ft. (1.8 m) 15 ft. (4.6 m) 25 ft. (7.6 m) 36 ft. (11.0 m) 50 ft. (15.2 m) 75 ft. (23.0 m) 100 ft. (30. 5 m) 4. Loosen the fluid hose ferrule nut (8) and hose compression nut (AA). See Fig. 5. 1. Connect the air supply hose between the air supply and the air inlet quick-disconnect (13). See Fig. 4. 5. Install the Graco waterborne fluid supply hose through the fluid hose port (P) in the enclosure and into the fluid regulator fitting (49). See Fig. 4 and 5. 2. Connect the fluid supply hose between the grounded fluid supply and the 3/8 npsm voltage block fluid inlet (103). Use a 5/16 in. (7.9 mm) or 3/8 in. (9.5 mm) I.D. hose for minimal pressure drop. 6. Hand-tighten the hose compression nut (AA) securely. See Fig. 5. Graco Waterborne Fluid Hoses Part Numbers 100 psi (0.7 MPa, 7 bar) Maximum Working Pressure 0.25 in. (6.35 mm) I.D.; PTFE Spray Gun Model Hose Part No. Length Manual PRO 3500wb Spray Gun 237–924 237–925 237–926 25 ft. (7.6 m) 36 ft. (11.0 m) 50 ft. (15.2 m) Automatic PRO 5500wb Spray Gun 237–920 237–921 237–922 25 ft. (7.6 m) 36 ft. (11.0 m) 50 ft. (15.2 m) 14 308–504 NOTE: The two hose ferrules (BB & CC) must be orientated as shown in Fig. 5, with the taper of the solid ferrule (BB) facing toward the fluid regulator (2) and the taper of the split ferrule (CC) facing away from the fluid regulator. 7. The hose ferrule nut (8) grounds the conductive layer (DD) of the Graco waterborne fluid hose and provides strain relief for the hose. See Fig. 5. Tighten the hose ferrule nut securely. 8. Connect the other end of the fluid hose to the gun fluid inlet. Read the instructions on fluid hose connection in your gun manual. Installation KEY-Fig. 4 N P 13 22 25 True Earth Ground Enclosure Fluid Hose Port Voltage Block Air Inlet (quick-disconnect) Voltage Block Air Regulator Ground Lug 49 Fluid Regulator Nut 103 Voltage Block Fluid Inlet 106 Voltage Block Enclosure 119 Main Ground Wire Clamp 123 Main Ground Wire 22 106 25 13 123 119 N P 103 49 2 05318A Fig. 4 KEY-Fig. 5 AA Hose Compression Nut BB Hose Ferrule CC Hose Ferrule DD Conductive Hose Layer EE Inner Hose Layer FF Outer Hose Jacket 8 Hose Ferrule Nut 2 Fluid Regulator 49 Fluid Regulator Fitting 106 Voltage Block Enclosure The areas of the waterborne fluid hose that are accessible to personnel during normal operation must be covered by the outer hose jacket (FF). The portion of the inner hose layer (EE) that is not covered by the outer hose jacket (FF) must be inside the enclosure (106). 2 49 BB CC AA 8 EE FF DD 106 05375 Fig. 5 308–504 15 Installation Ground the System See Fig. 4 2. Fluid Supply: Ground the fluid supply by connecting a ground wire and clamp. See your fluid supply instruction manual for grounding instructions. WARNING FIRE, EXPLOSION, AND ELECTRIC SHOCK HAZARD When operating the electrostatic gun, any ungrounded objects in the spray area (such as people, containers, tools, etc.) can become electrically charged. Improper grounding can result in static sparking, which can cause a fire, explosion, or electric shock. Follow the grounding instructions below. The following grounding instructions are minimum requirements for a basic electrostatic, waterborne system. Your system may include other equipment or objects which must be grounded. Check your local electrical code for detailed grounding instructions for your area and type of equipment. Your system must be connected to a true earth ground. 1. Voltage Block: Connect one end of the main ground wire (123), which is included with the system, to the ground lug (25) on the outside of the voltage block enclosure. Connect the other end of the ground wire to a true earth ground (N). Do not disconnect or tamper with the internal ground wire connections (112) inside the voltage block enclosure. They should be connected as shown in Fig. 6. 112 3. Gun Air Supply Hose or Turbine Air Supply on the PRO 5500wb Automatic Gun: You must use the red-colored Graco electrically conductive gun air hose. Do not use the black or grey-colored Graco air hoses. Ground the hose by connecting the air hose ground wire to a true earth ground. 4. Graco PRO 5500wb or PRO 3500wb Spray Gun: Ground the gun by connecting the grounded red-colored Graco electrically conductive air hose to the gun. Check the electrical grounding of the gun as instructed in the spray gun manual. 5. Graco Waterborne Fluid Hose: The hose must be properly grounded as instructed on page 14 and in the spray gun manual. 6. All persons entering the spray area: Their shoes must have conductive soles, such as leather, or personal grounding straps must be worn. Rubber or plastic soles are not conductive. 7. Object being sprayed: Keep the workpiece hangers clean and grounded at all times. Contact points must be sharp points or knife edges. 8. The floor of the spray area: The floor must be electrically conductive and grounded. Do not cover the floor with cardboard or any non-conductive material which would interrupt grounding continuity. 9. All electrically conductive objects or devices in the spray area: They must be properly grounded. W Check the System Grounding 05322B Fig. 6 16 308–504 After grounding the system, check the resistance between the exterior of the voltage block enclosure and a true earth ground. The resistance must be less than 20 ohms. Notes 308–504 17 Operation WARNING ELECTRIC SHOCK HAZARD The voltage block door switch helps to prohibit personnel from making contact with the enclosed voltage block components before the system voltage is discharged. To reduce the risk of an electric shock, do not tamper with or bypass the voltage block door switch. IMPORTANT: Only use the Graco PRO 5500wb automatic gun or PRO 3500wb hand-held gun with this system. The instructions in this manual are based on a typical system, where one of these Graco guns would be used. NOTE: When the voltage block is used with a 60 kV Graco spray gun, the typical “actual” voltage on the voltage block system is in the 45 to 55 kV range when the gun tip is at least 1 ft. (305 mm) away from a grounded object. Fluid Voltage Discharge and Grounding Procedure WARNING ELECTRIC SHOCK HAZARD The voltage block is charged with high voltage until the voltage is discharged. Contact with the charged components of the isolation system or spray gun will cause an electric shock. To avoid an electric shock, follow the Fluid Voltage Discharge and Grounding Procedure: For Manual Spray Guns 1. Turn off the gun electrostatics. If the PRO 3500wb is being used, turn the ES lever on the gun to the OFF position. 2. Wait at least 30 seconds for the voltage to discharge through the voltage block bleed resistor. If the voltage block has the optional kV meter, wait until the meter registers zero kV before proceeding. 3. Touch the electrode of the gun with a grounded rod to make sure that the voltage has been discharged. If an arc is seen, verify that the electrostatics are turned off or see Troubleshooting , page 25, or your gun instruction manual for other possible problems. Resolve the problem before proceeding. 4. Cleaning or typical adjustments of the gun, such as air cap positioning or cleaning, can be made after completing step 3. Before doing further service, such as gun or voltage block servicing, complete steps 5 and 6. 5. Unscrew the voltage block door latches to bring the isolators down and ground the high voltage charge of the fluid. 6. Touch the wire connector (R) of the fluid regulator with a grounded rod to make sure that the voltage has been discharged. See Fig. 7. If an arc is seen, see Troubleshooting , page 25, or your gun instruction manual for other possible problems. Resolve the problem before proceeding. NOTE: After service is complete and the doors are closed, the FILL/RUN button must be pressed to restart operation. when instructed to discharge the voltage, before cleaning, flushing, or servicing the system equipment, before approaching the gun, and before opening the voltage block door. NOTE: The metal enclosure of the H 2O PRO voltage block is always grounded if properly connected to a true earth ground by the main ground wire. An accessory grounding rod, part no. 210–084, is available to discharge any voltage remaining on a system component. Contact your Graco representative to order it. 18 308–504 R Fig. 7 05816A Operation Fluid Voltage Discharge and Grounding Procedure (continued) For Automatic Spray Guns 1. Turn off the gun electrostatics to all the spray guns connected to the voltage block. 2. Unscrew the voltage block door latches to bring the isolators down and ground the high voltage charge of the fluid. 3. Touch the wire connector (R) of the fluid regulator with a grounded rod to make sure that the voltage has been discharged. See Fig. 7. If an arc is seen, see Troubleshooting , page 25, or your gun instruction manual for other possible problems. Resolve the problem before proceeding. 4. If servicing the spray gun(s), touch the electrode of the gun with a grounded rod to make sure that the voltage has been discharged. If an arc is seen, verify that the electrostatics are turned off or see Troubleshooting , page 25, or your gun instruction manual for other possible problems. Resolve the problem before proceeding. NOTE: After service is complete and the doors are closed, the FILL/RUN button must be pressed to restart operation. Pressure Relief Procedure WARNING PRESSURIZED EQUIPMENT HAZARD The system pressure must be manually relieved to prevent the system from starting or spraying accidentally. To reduce the risk of an injury from accidental spray from the gun, splashing fluid, or moving parts, follow the Pressure Relief Procedure whenever you: are instructed to relieve the pressure, stop spraying, check or service any of the system equipment, or install or clean the spray nozzle. 1. Follow the Fluid Voltage Discharge and Grounding Procedure , page 18. 2. Shut off the fluid supply to the voltage block. 3. Shut off the air supply to the voltage block. The shut-off device must bleed the air out of the system. 4. Trigger the gun(s) to relieve the pressure in the fluid lines. 5. For automatic guns, shut off any other air supplies to the spray gun(s). Use bleed-type shut-off valves to relieve the pressure in the air lines. NOTE: After service is complete and the doors are closed, press the FLUSH/RESET button, then press the FILL/RUN button to restart operation. Emergency Fluid Shutoff Use this procedure if rapid fluid depressurization is needed, such as in the case of a hose leak. 1. Disconnect the air line from the voltage block quick-disconnect air inlet. The air pressure will bleed off to zero. 2. Turn the fluid supply unit off. The accumulator pistons will slowly rise until the fluid and air pressures are both at zero. Operating Checklist Check the following list daily, before starting to operate the system, to help ensure safe, efficient operation. ____ 1. Be sure all the operators are properly trained to safely operate an electrostatic, waterborne, air spray system as instructed in this manual and the gun manual. ____ 2. Be sure all the operators are trained how to properly relieve system pressure as instructed at left and in the gun manual. ____ 3. Be sure all the operators are trained how to properly discharge the voltage as instructed on page 18. ____ 4. Be sure the system is thoroughly grounded and the operator and all persons entering the spray area are properly grounded. See Ground the System, page 16. ____ 5. Be sure the ventilation fans are operating properly. ____ 6. Be sure all the debris, including flammable liquids and rags, is removed from the spray area. 308–504 19 Operation Voltage Block Startup Procedure 1. Install and ground the system as instructed in the Installation section. 2. Remove the TSL supply bottles (4) and (toward front door side) and replace them with the full TSL bottles (4) sent with the system. See to Fig. 3, page 8. NOTE: To help ensure fresh TSL always enters the seal area, replace the TSL supply bottle periodically as instructed on page 27. 3. If adjusting the position of the accumulator full level switch (76), be sure to push the switch bracket (AB) fully to the left and hold it in place until the screws (39) are tight. See Fig. 8. CAUTION Do not set the air pressure to the voltage block below 60 psi (410 kPa, 4.1 bar) or the voltage block will not operate properly. 6. Repeatedly push the manual switch button near the TSL pump (90) until all air is purged out through the tubing and is visibly pumping into the waste container. Refer to Fig. 3, page 8. CAUTION Make sure that the fluid inlet pressure is a minimum of 5 psi (34 kPa, 0.34 bar) lower than the voltage block air regulator (22 – Fig. 9) pressure or the accumulators will fill during step 6. AB 39 NOTE: Be sure to turn on the air to the voltage block before pressing the FLUSH/RESET button or the system components will not operate. 76 7. Check the voltage block operation and check for fluid leaks with water before connecting the paint. 05894 Fig. 8 4. If using a hand-held gun, remove the air cap from the gun. 5. With the voltage block door open, turn on the air to the voltage block. Set the air pressure between 80–100 psi (0.5–0.7 MPa, 5.5–7 bar). The air inlet pressure is set with the air regulator (22) installed at the voltage block air inlet. See Fig. 9. 20 308–504 22 Fig. 9 05323 Operation 8. Set the fluid outlet pressure to the gun by adjusting the air pilot regulator (20) on the front cover of the voltage block. See Fig. 10. NOTE: The voltage block fluid inlet pressure will affect the accumulators fill time only. 13. Press the FILL/RUN button (A) to fill the accumulators. 14. Wipe off the fluid nozzle, and install the air cap. 15. Follow the procedure Operating the Voltage Block, page 22, to begin spraying. 9. Trigger the gun until all the air is purged through the voltage block and fluid lines. 10. Close the door and press the FILL/RUN button (A) to fill and dispense the accumulators. See Fig. 10. Press the FLUSH/RESET button (B), and dispense all water out of the accumulators. 11. Shut off the water supply, and connect the paint supply line. 12. Trigger the gun until the water is purged and paint starts to dispense from the gun nozzle. 20 Fig. 10 A B 308–504 05316 21 Operation Operating the Voltage Block WARNING FIRE, EXPLOSION AND ELECTRIC SHOCK HAZARD To reduce the risk of fire, explosion, and electric shock: Only use this equipment to spray non-flammable, waterborne fluids as defined on the front cover of this manual. The voltage block door must be closed when any gun connected to the system is operating. Do not tamper with or bypass the door switch or other safety devices. WARNING COMPONENT RUPTURE HAZARD To reduce the risk of component rupture, which can cause serious injury, do not exceed the maximum working pressure of the lowest rated system component. This equipment has a 100 psi (0.7 MPa, 7 bar) maximum working air and fluid pressure . 1. Turn on the air to the voltage block. Set the air pressure between 80–100 psi (0.5–0.7 MPa, 5.5 –7 bar). 22 308–504 The air inlet pressure is set with the air regulator (22) installed at the voltage block air inlet. See Fig. 9, page 20. NOTE: Be sure to turn on the air to the voltage block before pressing the FLUSH/RESET button or the system components will not operate. CAUTION Do not set the air pressure to the voltage block below 60 psi (410 kPa, 4.1 bar) or the voltage block will not operate properly. 2. Press the FLUSH/RESET button (B) to reset the air logic components. See Fig. 10, page 21. 3. Set the voltage block fluid pressure for the desired fluid flow through the gun. Set the fluid pressure with the regulator knob (20) on the voltage block door. 4. Turn on the fluid supply to the voltage block. NOTE: The voltage block fluid inlet pressure will affect the accumulators fill time only. 5. Press the FILL/RUN button (A) to fill the accumulators. 6. Open the gun air supply. 7. Follow the gun operation instructions in the gun manual. Use the same spraying technique you would use without the voltage block to coat the workpiece. Operation Flushing and Shutdown WARNING FIRE AND EXPLOSION HAZARD To reduce the risk of fire and explosion: Only flush, purge, or clean the electrostatic, waterborne spray system with non-flammable fluids, as defined on the front cover of this manual. Do not flush the system with the gun electrostatics turned on. WARNING ELECTRIC SHOCK HAZARD Follow the Fluid Voltage Discharge and Grounding Procedure on page 18 when shutting down the system to ensure the voltage is discharged and avoid serious injury from an electric shock. WARNING PRESSURIZED EQUIPMENT HAZARD To reduce the risk of an injury from accidental spray from the gun, splashing fluid, or moving parts, follow the Pressure Relief Procedure on page 19 when you stop spraying and whenever you are instructed to relieve the pressure. To save the fluid in the accumulator, follow the Paint Saver Option procedure, below. For general gun flushing and shutdown, follow the General Flushing and Shutdown procedure, at right. Paint Saver Option To save fluid at shutdown: 1. Follow the Fluid Voltage Discharge and Grounding Procedure on page 18. 2. Depressurize the fluid supply to the voltage block. 3. Open the voltage block door latch enough to actuate the door switch, which will send both the isolators down and allow the fluid in the accumulators to be pushed back to the fluid supply. 4. Continue with the General Flushing and Shutdown procedure. General Flushing and Shutdown NOTE: Before flushing, make sure the fluid inlet pressure is a minimum of 5 psi (34 kPa, 0.3 bar) lower than the voltage block air pressure regulator (22) setting or the accumulators will fill during the flush cycle. Refer to Fig. 9, page 20. 1. Follow the Fluid Voltage Discharge and Grounding Procedure on page 18. 2. Shut off the fluid supply. Trigger the gun until the fluid pressure is relieved. 3. If using a hand-held gun, remove the air cap from the gun. 4. Change the fluid supply to water or the appropriate flushing material. Do not use MEK or related ketone mixtures. 5. Press the FLUSH/RESET button. 6. Turn off the air supply to the gun, except the air to actuate the gun trigger if it is an automatic gun. If the automatic gun has an air pilot regulator, the pilot air must also be left on. 7. Make sure the gun electrostatics are turned off. 8. Trigger the gun to dispense the fluid out of the voltage block until the fluid section is completely flushed. NOTE: After the accumulators empty, the first isolator will connect to the water supply. 9. Shut off the fluid supply. Trigger the gun until the fluid pressure is relieved. 10. Do not purge the system with air; leave water in the fluid lines until you operate the system again. 11. Shut off the air supply to the enclosure. 12. Wipe the gun clean. If the gun air cap was removed, wipe off the fluid nozzle and install the air cap. 13. Make sure that the voltage block door is closed and that the main ground wire is connected between the enclosure ground lug and a true earth ground before operating the system again. 308–504 23 Troubleshooting WARNING ELECTRIC SHOCK HAZARD Follow the Fluid Voltage Discharge and Grounding Procedure on page 18 before checking or servicing the system to ensure the voltage is discharged and avoid serious injury from an electric shock. WARNING PRESSURIZED EQUIPMENT HAZARD To reduce the risk of an injury from accidental spray from the gun, splashing fluid, or moving parts, follow the Pressure Relief Procedure on page 19 before checking or servicing any part of the system and whenever you are instructed to relieve the pressure. Problem: Voltage Loss A loss of spraying voltage can be caused by a problem with the spray gun, fluid hose, or voltage block, since all of the system components are electrically connected through the conductive, waterborne fluid. Before troubleshooting or servicing the voltage block itself, determine which component in the system is most likely causing a problem. Possible causes include: Spray Gun Fluid leakage Dielectric breakdown at the fluid hose connection or fluid packings Not enough air pressure for the turbine Faulty power supply Excessive overspray on gun surfaces Fluid in the air passages Waterborne Fluid Hose Dielectric failure of hose (pin-hole leak through PTFElayer) Air gap in the fluid column between the gun and isolated fluid supply Voltage Block Fluid leakage Dielectric breakdown of hoses, seals, or connections Isolators not functioning properly 24 308–504 First, check the system for any visible faults or errors to help isolate whether the spray gun, fluid hose or voltage block has failed. 1. Check that all of the air and fluid tubes and hoses are properly connected. 2. Check that the valves and controls are properly set for operation. Refer to the Operation procedures. 3. Check that the spray gun power supply and voltage block have sufficient air pressure. 4. PRO 3500wb Gun Only: Check that the spray gun ES lever is in the ON position and that the gun ES indicator light comes on. If the ES indicator light does not come on, remove the spray gun for service. 5. Check that the voltage block door is closed and that any safety interlocks are engaged and working properly. 6. To eliminate air gaps in the fluid column, spray enough fluid to purge the air out between the voltage block and the spray gun. An air gap in the fluid hose can break the electrical continuity between the spray gun and the fluid in the voltage block accumulators and cause a low voltage reading on the optional kV meter connected to the voltage block accumulators. 7. Check the spray gun cover and barrel for accumulated overspray. Excessive overspray can create a conductive path back to the grounded gun handle. Install a new gun cover and clean the exterior of the barrel. 8. Inspect the entire system for any visible fluid leakage, paying special attention to the following areas: Packing area of the spray gun Fluid hose: check for leakage or any bulges in the outer jacket, which may indicate an internal leak Internal voltage block components If you still have no voltage, separate the spray gun and hose from the voltage block and check them for problems as instructed in the spray gun manual. The optional kV Probe and Meter, part no. 236–003, is recommended to measure voltage levels at key points in the system. Follow the troubleshooting chart for more detailed checking of the voltage block. Troubleshooting Problem Cause Solution Voltage loss* Voltage block enclosure door is not closed Close the door. Voltage block is in the end of the flush mode and the fluid is connected to a grounded fluid supply Push the FILL/RUN button. Waterborne fluid hose has a pin-hole leak through the PTFE layer, causing dielectric failure Check for leakage or any bulges in the outer jacket, which may indicate an internal leak. Inspect the end of the hose connected to the voltage block. Look for cuts or nicks. Make sure the hose is properly stripped; see the spray gun manual for hose stripping dimensions. Restrip or replace the hose. Fluid is leaking at the gun fluid hose connection Remove the hose at the gun connection. Clean and dry the gun barrel I.D. and the hose O.D. Lubricate the hose O.D. and o-rings with dielectric grease and reinstall them. Excessive fluid overspray on the outside of the gun barrel, shroud, or gun cover Clean the outside of the gun barrel or shroud. Replace the gun cover. Excessive waterborne fluid leaking into the TSL return line Make sure the TSL supply bottle is full. See Service. If the problem reoccurs quickly, replace the isolator seals with the seal kit. Fluid is leaking on the components inside the voltage block Replace the seals as necessary. Air in the fluid line to the gun (can cause low voltage reading on the optional voltage block kV meter) Trigger the gun until the air is purged out through the gun nozzle. Gun electrostatics (turbine air or gun ES lever) not turned off Turn off the gun electrostatics. Did not wait long enough for the voltage to discharge through the voltage bleed resistor Wait the 30 second time period before making contact with the gun or internal voltage block components. Air pocket in the fluid lines Purge the air out of the fluid lines. Faulty bleed resistor Check for loose wire connection or replace the bleed resistor if necessary. Voltage is still present at the gun or fluid regulator after following the Fluid Voltage Discharge and Grounding Procedure * Normal spraying voltage is 45 to 55 kV. 308–504 25 Troubleshooting Problem Cause Solution TSL waste bottle level is rising quickly Waterborne fluid is leaking into the TSL lines Replace the isolator seals with the seal kit. See Service. TSL supply bottle level is dropping quickly TSL is leaking or slowly evaporating with use Refill the TSL bottle or replace the isolator seals. TSL, TSL tubing, or TSL waste bottle color changing to color of waterborne fluid This is normal unless the kV level is dropping (see Voltage Loss, page 25) No action necessary. The dirty TSL can be pumped out with clean TSL as necessary. Cartridge seals worn allowing excessive fluid into the TSL ports Replace the isolator seals with the seal kit. TSL circulating pump seals worn Replace TSL pump seals with the pump fluid seal repair kit. Check valve(s) in TSL tubing line(s) failed Replace check valve(s) and tubing if necessary with TSL tube repair kit. Air restrictor to TSL pump closed too far Open the adjustment screw on the restrictor 1/2 turn and test with the manual pump actuator. Retaining collar nut has loosened causing loss of spring pressure Re-tighten the collar. Secure the collar with its retaining screw. See Service. Rod o-ring is worn or damaged Replace the o-ring and cartridge seals with the replacement seal kit. See Service. Fitting nut is not tight Hand-tighten the nut. Hand-tighten only; do not use tools. Fitting threads are stripped Replace the fitting. Install the new hose or nut assembly as needed. Isolator air cylinder moving too slow or too fast (normal speed is approximately 2 seconds per stroke) Cylinder restrictors misadjusted or plugged Adjust air cylinder exhaust port for speed adjustment of about 2 seconds per stroke. Isolator cylinder is not operating properly Voltage block air pressure set below 60 psi (410 kPa, 4.1 bar); recommended pressure is 65–95 psi (450–650 kPa, 4.5–6.5 bar) Set air to proper pressure. See Operation. Accumulator fills past the full setting switch Switch position is not adjusted properly Re-adjust the switch position. Air leak at fluid regulator pilot air fitting Constant air exhaust from small hole in pilot air fitting is normal and used for pressure control accuracy. No action necessary. TSL not circulating Fluid leak at isolator rod seam PTFE fluid hose connections are leaking 26 308–504 Maintenance Cycle Counting Gradual reduction of the spraying voltage. A Pneumatic Cycle Counter Kit, part no. 238–026, is available to count the number of isolator cycles for maintenance tracking. If the Cycle Counter Kit is not installed, time how long one voltage block cycle takes during normal operation. Use the following formula to convert the voltage block cycles to production hours: Fluid Seal Time in Hours = (15,000 x Cycle Time in minutes) 60 TSL System Maintenance To prolong the life of the isolator and to avoid expensive repairs and downtime, perform the following maintenance: 1. Replace the isolator seals every 15,000 voltage block cycles, or every four months, whichever comes first. See page 28. 2. Inspect the condition of the TSL fluid in the sight glass and in the TSL waste bottle (138) daily. Refer to Fig. 11, page 28. Signs of excessive TSL contamination include: Greatly increased discoloration of the TSL in the waste bottle Quick rise in the TSL level in the waste bottle 3. Make sure that only fresh TSL enters the seal area by checking the TSL supply bottle (4) level daily. CAUTION Do not allow the TSL supply bottle to become empty or voltage breakdown could quickly occur. 4. Once a week, manually check the operation of the TSL pump (90). Refer to Fig. 11. The isolator must be in the down position* and the voltage block must be pressurized for the pump to operate. Operate the TSL pump by pressing the button on the pump. Watch the sight glass in the TSL line to see if the fluid is moving. * The isolator will automatically stop in the down position when the voltage block door is opened. PTFETubing Replacement The PTFE flared tube assembly (101) will fatigue over time. To prevent failure during operation, replace the tube assembly after dispensing about 50,000 gal. (189,250 liters) of fluid or after about 6,000 hours of operation. If a cycle counter is used, replace the tube assembly every 70,000 cycles. 308–504 27 Service Isolator Service WARNING ELECTRIC SHOCK HAZARD Follow the Fluid Voltage Discharge and Grounding Procedure on page 18 before checking or servicing the system to ensure the voltage is discharged and avoid serious injury from an electric shock. WARNING PRESSURIZED EQUIPMENT HAZARD To reduce the risk of an injury from accidental spray from the gun, splashing fluid, or moving parts, follow the Pressure Relief Procedure on page 19 before checking or servicing any part of the system and whenever you are instructed to relieve the pressure. 3. Disconnect the TSL supply bottle outlet tube (A) from the fluid block (330). See Fig. 11. Drain the TSL into a waste container. 4. Disconnect the two air tubes from the air cylinder connectors (B). Mark or tag the tubes so it is apparent which connector they attach to for reassembly. 5. Disconnect the two PTFE fluid tubes (C) from the isolator elbows. 6. Disconnect the TSL return tube (E) from the fluid block (330) fitting. 7. Remove the screw (305), and disconnect the ground wire from the air cylinder. Reinstall the screw to avoid losing it. 8. Remove the four 3/8” screws (97), and remove the isolator assembly (75) from the enclosure (106). 9. Take the isolator to a clean service bench. NOTE: An Isolator Seal Kit, part no. 237–977, is available. It includes the o-rings (302, 306, 308, 309, 319) and seals (320) for the seal cartridges. Replace the isolator seals every 15,000 voltage block cycles, or every four months, whichever comes first. When installing the Isolator Seal Kit, inspect the isolator parts for signs of arcing or carbon tracking. A carbon track will look like a pencil line, which you can feel with your fingernail. It will typically appear near the bottom of the rod connection seam. Replace any parts that look damaged to avoid system failure. 90 L A suppy waste 4 138 B 305 330 E Isolator Disassembly 1. Follow the General Flushing and Shutdown procedure on page 23. C NOTE: As part of the General Flushing and Shutdown, the Fluid Voltage Discharge and Grounding Procedure, page 18, and the Pressure Relief Procedure, page 19, should have been completed. Do not proceed until you have followed those procedures. Follow the steps below to remove either one or both of the isolators. 2. Remove the TSL supply bottle (4) from the supply tube. 28 308–504 106 Fig. 11 75 97 101 05817B Service Isolator Disassembly (continued) 10. Remove the retainer screw (343) from the bottom support (331). See Fig. 12. 19. While holding the parts over a waste container, pull the isolator rod (334) out of the fluid block (330). Be careful not to nick or scratch the rod surfaces. 11. Remove the spring retainer collar (336). 20. Remove the isolator rod o-ring (319). 12. If servicing the right side isolator, rotate the fluid tube (335) until the arc bypass wire assembly (354) is accessible. Remove the screw (338) and washer (350). 21. Remove both seal cartridges (332, 333), the high voltage electrode (326), plug (325), and o-ring (306) from the fluid block (330). 13. Pull the fluid tube (335) out of the bottom support (331). Remove the plug (325) and o-ring (306). 14. Remove the bottom support (331) by removing the four screws (318) that fasten it to the mounting brackets (324, 337). 15. Loosen the screw (307) holding the cover retainer (328), and rotate the cover retainer off of the cylinder rod cover (327). 16. Push the cylinder rod cover (327) up until the air cylinder rod (G) is accessible. Unscrew the cylinder rod from the adapter in the fluid block (330). 17. Remove the plastic screw (304) holding the isolator rod (334). 18. Slide the fluid block (330) [with the isolator rod still in place] off the metal guide rod (321). CAUTION Be careful not to nick or scratch the cartridges (332, 333) surfaces when removing o-rings and seals. Note the o-ring and seal sizes and positions as they are removed to ensure they are reinstalled correctly. 22. Remove all the o-rings (302, 308, 309) from both seal cartridges (332, 333). 23. Use a dental pick to remove the wiping seals (320) from both seal cartridges (332, 333). Be careful not to scratch the cartridges surfaces. 24. Thoroughly clean and inspect all the parts. Inspect the fluid tube (335) and isolator rod (334) for nicks, grooves, and high voltage burn marks on sealing and wiping surfaces. Inspect the guide rod bearings (312) for wear. Replace all the parts that appear to be worn or damaged. Continue on page 31 308–504 29 Service 320 311 308* 304 A 305 324 337 333 329 320 G 334 320* 319* 332 306* 348 325 350 352 338 351 *309 349 *302 B 354 A 321 *320 353 B 335 318 331 327 343 326 307 313 325 328 306* 336 330 F Fig. 12 30 8565A Apply lubricant. Torque to 15 in-lbs (1.7 NSm). Torque to 8 in-lbs (0.9 NSm). Tighten securely, until bottomed out. Lips face down 308–504 Lips face up On right isolator only On left isolator only * Included in Kit 237–977 Service Isolator Assembly NOTE: Parts that are marked with an asterisk (*) are included with the Isolator Seal Kit, part no. 237–977. 1. Lubricate the new seals (320*) and install them into the cartridges (332, 333), orientated as shown in Fig. 12, page 30. Make sure the seals sit straight in the cartridge and that the seal quad-ring is in place. 2. Lubricate the new o-rings (302*, 308*, 309*) and install them in the grooves on the cartridges (332, 333) in the order shown in Fig. 12. 3. Install the o-ring (306*), plug (325), and high voltage electrode (326) in the fluid block (330). Tighten the plug and the electrode until they bottom out. 4. Carefully install the seal cartridges (332, 333) into the fluid block (330). Tighten the cartridges until they bottom out. 5. Install the o-ring (319*) on the end of the isolator rod (334). 6. Slide the tapered end of the isolator rod (334) through the seal cartridges (332, 333) in the fluid block (330). 7. Place the cylinder rod cover (327) in the locating groove (F). Do not fasten the cover with the retainer (328) and screw (307) yet. 11. Secure the bottom support (331) to the mounting brackets (324, 337) with the four screws (318). Tighten the screws to 15 in-lbs (1.7 N m). 12. Install the fluid tube (335) into the bottom support (331). 13. On the right side isolator, secure the arc bypass wire assembly (354) to the fluid tube (335) with the washer (350) and screw (338). 14. Install the spring (313) into the retainer collar (336), and screw the collar into the bottom support (331) until the collar bottoms out. Secure the collar with the retainer screw (343). 15. Secure the isolator assembly (75) into the enclosure (106), using the four 3/8” screws (97). See Fig. 11, page 28. 16. Connect the two air tubes to the air cylinder connectors (B). 17. Connect the two PTFEfluid tubes (C) to the isolator elbows. CAUTION Tighten the tube retaining nuts by hand only to avoid damaging the threads. 18. Remove the screw (305). Connect the ground wire to the air cylinder, and secure the wire with the screw. 8. Slide the fluid block (330) onto the metal guide rod (321). Push the isolator rod (334) into the counterbore in the top support (329), and secure the rod with the plastic screw (304). Tighten the screw to 8 in-lbs (0.9 N m). 19. Connect the TSL supply tube (A) to the fluid block (330). See Fig. 11, page 28. 9. Push the fluid block (330) partially down to slide the cylinder rod cover (327) up and tighten the air cylinder rod (G). Tighten the rod until it bottoms out. 21. Turn on the air inlet pressure to the voltage block. 10. Slide the cylinder rod cover (327) down and secure the cover with the retainer (328) and screw (307). Tighten the screw to 8 in-lbs (0.9 N m). 20. Connect the TSL return tube (E) to the fluid block (330). 22. Press the button on the TSL pump (90) to manually activate it and flush the remaining TSL out of the pump and into the waste bottle. Press the button on the TSL pump repeatedly until all air and contaminated TSL are purged from the tubing. View the air pockets in the sight tube. 308–504 31 Notes 32 308–504 Service Accumulator Service WARNING ELECTRIC SHOCK HAZARD Follow the Fluid Voltage Discharge and Grounding Procedure on page 18 before checking or servicing the system to ensure the voltage is discharged and avoid serious injury from an electric shock. WARNING PRESSURIZED EQUIPMENT HAZARD To reduce the risk of an injury from accidental spray from the gun, splashing fluid, or moving parts, follow the Pressure Relief Procedure on page 19 before checking or servicing any part of the system and whenever you are instructed to relieve the pressure. Signs of accumulator piston seal failure include a noticeable and repeated spitting of fluid while spraying (indicating that air is entering into the fluid stream) or a visible amount of fluid in the top air exhaust line that is exiting through the enclosure bottom. NOTE: An Accumulator Seal Kit, part no. 237–976, is available. It includes the o-rings (211) and u-cups (208, 214). Accumulator Disassembly 4. Disconnect the air pilot tube from the fluid regulator air pilot connector (48). 5. Loosen the hose ferrule nut (8). 6. Loosen (but do not remove) the hose compression nut (AA) connecting the gun fluid supply hose to the fluid regulator outlet. Pull the hose out of the fitting. 7. Remove the four top plastic screws (54) that secure the accumulator (74) to the mounting plate (X) in the enclosure. 8. Remove the accumulator (74) from the mounting plate (X). 9. Remove the four thread caps (225) and cap plugs (224). See Fig. 14. 10. Loosen the four hex nuts (213) evenly. 11. Remove the four 12.6” screws (212), washers (204), and high voltage shields (223). 12. Tap the end blocks (216, 217) off of the cylinder (219). 13. Remove the piston assembly (221, 222, 214 1, 220) from the cylinder (219). 14. Remove the u-cups (208, 2142) and o-rings (201, 202, 211). Clean and inspect the parts. Replace all the parts that are worn or damaged. Continue on page 35 1. Follow the General Flushing and Shutdown procedure on page 23. H NOTE: As part of the General Flushing and Shutdown, the Fluid Voltage Discharge and Grounding Procedure, page 18, and the Pressure Relief Procedure, page 19, should have been completed. Do not proceed until you have followed those procedures. 54 74 X Follow the steps below to remove either one or both of the accumulators. J 8 2. Disconnect the exhaust air tube from the top accumulator fitting (H). See Fig. 13. AA 3. Disconnect the fluid hose nut (J) from the fluid inlet flared hose end. NOTE: Follow steps 4 to 6 to disconnect the fluid regulator (2), which is connected to accumulator #2, from the system. If disconnecting accumulator #1 only, disconnect the fluid tube from the accumulator outlet fitting and continue with step 7. 48 2 Fig. 13 05817B 308–504 33 Service 225 211* 202 213 219 210 201 217 223 *208 201 221 215 *2142 222 211* 216 *2141 220 204 212 202 224 05296 Fig. 14 Install the u-cups (2141, 2142) with the lips facing to the outside of the piston (220). Install the piston assembly (221, 222, 2141, 220) into the end of the cylinder (219) with the internal chamfer . The cylinder end with the chamfer must face toward the upper end block (217). Apply lubricant to the seal contact surfaces. 34 308–504 Do not use lubricant on the o-rings (202) that are in the cap plugs (224). Torque to 15 ft-lbs (20.25 NSm). Torque to 15 in-lbs (1.7 NSm). Apply dielectric lubricant to the o-ring. * Included in Kit 237–976 Service Accumulator Assembly NOTE: Parts that are marked with an asterisk (*) are included with the Accumulator Seal Kit, part no. 237–976. Lubricate the o-rings and u-cups as directed in Fig. 14, page 34. Do not use lubricant on the o-rings (202) that are in the cap plugs (224). 1. Install the u-cup (2141*) on the air side of the piston (220) with the lips of the u-cup facing up, away from the piston, as shown in Fig. 14. Using a blunt instrument, carefully press around all sides of the u-cup lips until it is completely engaged in the piston (220) groove. Lightly lubricate the outside edge of the u-cup. 2. Secure the piston extension (222) to the piston (220) with the four screws (215). Tighten the screws to 15 in-lbs (1.7 Nm). 3. Install the piston assembly (221, 222, 214 1, 220) into the end of the cylinder (219) with the internal chamfer. Make sure the fluid side of the piston faces down into the cylinder. See Fig. 14. 4. Push the piston assembly to the the bottom of the cylinder until the bottom edge of the piston (220) is exposed. 5. Install the u-cup (2142*) on the piston (220) with the lips of the u-cup facing down away from the piston, as shown in Fig. 14. Using a blunt instrument, carefully press around all sides of the u-cup lips until it is completely engaged in the piston (220) groove. Lightly lubricate the outside edge of the u-cup. 6. Install the new piston rod u-cup (208*) with the u-cup lips facing toward the piston (220). Lightly lubricate the outside edge of the u-cup. 7. Install the two new o-rings (211*) into the end blocks (216, 217). Lightly lubricate the o-rings. 8. Install the eight o-rings (201) into the grooves in the end block (216, 217) ports. Apply dielectric grease to the o-rings. 9. Place the upper end block (217) on the end of the cylinder (219) with the internal chamfer. 10. Install the o-rings (201) and high voltage shields (223) into the upper end block (217). 11. Place the lower end block (216) on the other end of the cylinder. Make sure the eight o-rings (201) stay correctly placed in the end blocks. 12. Secure the end blocks (216, 217) with the washers (204), screws (212), and nuts (213). Tighten the screws oppositely and evenly to 15 ft-lbs (20.25 Nm). 13. Install the o-rings (202) into the thread caps (225) and onto the grooves on the cap plugs (224). 14. Apply dielectric grease to the o-rings (202) in the thread caps (225). Do not apply grease to the o-rings (202) on the cap plugs (224). 15. Install the thread caps (225) and cap plugs (224). 16. Add 0.7 oz. (20 cc) of TSL into the top end (piston rod end) of the accumulator. Remove the top air fitting for easier access if necessary. 17. Secure the accumulator (74) to the mounting plate (X) with the four plastic screws (54). See Fig. 13, page 33. Tighten the screws until they are snug; do not over-tighten them. 18. Reconnect the Graco waterborne fluid hose as instructed on page 14. 19. Connect the exhaust air tube to the top accumulator fitting (H). See Fig. 13, page 33. NOTE: If installing accumulator #1, connect the fluid tube to the accumulator outlet fitting. 20. Connect the fluid hose nut (J) to the fluid inlet flared hose end. 21. Connect the air pilot tube to the fluid regulator air pilot connector (48). 308–504 35 Parts Part No. 237–928 Waterborne Voltage Block DETAIL C 136 129 137 141 143 106 138 79 65 24 29 140 57 Ref. 31 25 4 139 53 See DETAIL B, below, and page 44 for replaceable air logic assembly parts 142 144 10 7 17 9 51 52 60 21 8 73 22 30 71 16 11 48 31 72 13 103 See DETAIL C. 83 61 20 18 6 34 38 35 68 15 59 58 See page 38 for parts. See DETAIL A for tube parts. 46 44 120 14 86 12 DETAIL A 100 ** NOTE: The washers (80) are installed for grounding continuity. Install them in the location shown, not next to the nuts (56). DETAIL B **80 99 110 93 56 113 107 101 05819A 36 308–504 Parts Part No. 237–928 Waterborne Voltage Block NOTE: Parts for the voltage block assembly are continued on the next page. Ref. No. Part No. Description 6 7 8 9 10 11 12 13 290–098 101–390 185–549 185–548 185–547 114–558 110–544 169–970 14 15 16 17 18 20 109–570 113–348 156–971 154–636 112–308 110–438 21 22 110–436 111–804 24 25 29 30 31 110–911 104–029 100–732 100–731 104–641 35 38 44 46 48 100–307 100–056 113–078 113–080 113–058 51 52 113–069 113–068 53 56 57 58 113–067 113–127 113–128 113–129 59 60 113–130 290–089 61 290–090 WARNING LABEL LOCK WASHER HOSE FERRULE NUT, 5/8–24 FERRULE HOUSING AIR LINE COUPLING LEG LEVELER AIR LINE FITTING, quick-disconnect WASHER LOCK WASHER SHORT NIPPLE WASHER NUT, regulator panel AIR REGULATOR, self relieving, 0–100 psi (0–0.7 Mpa, 0–7 bar) AIR PRESSURE GAUGE AIR REGULATOR, self relieving, 0–125 psi (0–0.85 Mpa, 0–8.5 bar) HEX JAM NUT GROUND LUG LOCK WASHER WASHER FITTING, 3/8 npt(f) x 3/4–20 unef–2a HEX NUT HEX JAM NUT SCREW SCREW RETAINER CONNECTOR, 5/32 x 1/4 npt(m) 90 ELBOW, 1/4 npt(f) CONNECTOR, 5/32 x 1/8 npt(m) PNEUMATIC SWITCH NUT, hex, 1/4–20, nylon STANDOFF; 3/4” (19 mm) CAP SCREW, 1/4–20 x 1.25” WASHER LABEL, air inlet, max. pressure LABEL, fluid inlet, max. pressure Ref. No. Part No. Description 65 113–179 68 71 72 113–062 113–268 113–060 73 79 113–061 113–150 80 83 86 93 99 100 101 100–985 100–333 100–338 113–154 113–167 113–170 113–181 103 190–715 2 2 2 4 1 106 190–721 107 113–180 110 113 190–712 113–182 4 1 2 2 3 120 136 137 138 190–734 114–599 193–641 102–379 139 140 193–474 110–823 141 142 143 144 100–015 100–016 193–618 193–619 CONNECTOR, 1/4 npt(m), for 1/4” O.D. tube UNION BUSHING FLUID PRESSURE GAUGE; 0–100 psi (0–0.7 Mpa, 0–7 bar) PUSH SWITCH STANDOFF; 1–1/4” (32 mm) WASHER CAP SCREW JAM NUT AIR LOGIC COVER AIR LOGIC ASSEMBLY ADAPTER NUT FLARED TUBE ASSY., 15.5” (394 mm) BULKHEAD FITTING, 3/8–18.6 special form straight pipe thread VOLTAGE BLOCK ENCLOSURE FLARED TUBE ASSY., 23” (584 mm) AIR LOGIC STANDOFF FLARED TUBE ASSY., 5.5” (139.7 mm) PEDESTAL BUSHINGS, 3/8” CAP, spout BOTTLE, empty; 1 quart (0.95 liter) BRACKET, dual bottle SCREW, pan hd. 1/4–20 x 1” NUT, hex; 1/4–20 LOCK WASHER, 1/4” TUBE, drain TUBE, supply Qty. 1 1 1 1 1 1 4 1 4 1 1 1 2 1 1 1 1 4 1 4 4 2 4 1 Qty. 1 2 1 1 2 4 4 8 4 1 1 1 1 1 1 2 4 1 2 4 4 2 2 4 4 4 2 2 Replacement Danger and Warning labels, tags and cards are available at no cost. 1 308–504 37 Parts Part No. 237–928 Waterborne Voltage Block 96 39 52 90 104 88 98 39 105 109 76 116 77 *117 34 *1 87 129 27 39 39 74 See parts on page 40 32 B 121 134 94 ]122 37 19 43 42 41 B 50 42 49 54 97 A 75 See parts on page 42 2 95 Isolator 2 92 Isolator 1 115 Accumulator 1 36 102 48 47 Accumulator 2 ]The other cable end connects to the ground lug (25) inside the enclosure (106). 38 Tapered end of the check valve (1) must face up. 308–504 05820B Parts Part No. 237–928 Waterborne Voltage Block Ref. No. Part No. Description 1* 2 M71–256 238–159 CHECK VALVE FLUID REGULATOR, 3–100 psi (0.021–0.7 MPa, 0.2–7 bar), see manual 308–325 for parts TSL FLUID, 1 qt. (0.95 liter) bottle (not shown) SCREW, nylon MACHINE SCREW MACHINE SCREW WASHER MACHINE SCREW HEX NUT MACHINE SCREW TSL TUBING (not shown) CRUSH RING WASHER BLEED RESISTOR 90_ ELBOW, 1/4 npt(f) CONNECTOR, male, 5/32 x 1/4 npt TUBE ADAPTER, male, 1/4 npt(m), for 3/8” O.D. tube REDUCER NIPPLE, 3/8–1/4 npt(m) CONNECTOR, male, 5/32 x 1/8 npt CAP SCREW, 3/8–16 x 2” ACCUMULATOR, see page 40 for parts ISOLATOR ASSY., see page 42 for parts FULL LEVEL SWITCH LOW LEVEL SWITCH TSL PUMP SWITCH SWITCH BRACKET TSL PUMP TUBE ADAPTER 90_ ELBOW, 3/8 npt(f), for 3/8” O.D. tube BLEED RESISTOR CLAMP TUBE ADAPTER, 3/8 npt(f), for 1/2” O.D. tube BLOCKING EXHAUST VALVE CAP SCREW, 3/8–16 x 1” EXHAUST VALVE RESISTOR FITTING, 10–24 unc–2b x 1/4–18 npt(m) 4* 206–995 19 27 32 34 36 37 39 40* 41 42 43 47 48 110–620 101–816 110–823 100–527 100–268 100–166 103–774 – 113–135 113–075 190–410 113–071 113–058 49 113–081 50 113–070 52 113–068 54 74 113–125 237–929 75 237–930 76 77 87 88 90l 92 113–123 113–124 113–174 113–175 113–143 113–151 94 113–155 95 113–152 96 113–166 97 98 102 113–126 113–165 190–714 Qty. Ref. No. Part No. Description 2 1 104 105 191–971 190–719 109 190–733 112 237–939 115 113–169 116 112–698 SWITCH BRACKET SWITCH BRACKET NUT, 10–24 unc–2b ACCUMULATOR ROD GUIDE WIRE ASSY., component to ground (not shown–refer to Fig. 6, page 16) TUBE ADAPTER, 3/8 npt(m), for 1/2” O.D. tube ADAPTER SWIVEL ELBOW, 1/8 npt(m) BARB FLUID CONNECTOR HOSE CLAMP (not shown) CABLE CLAMP (not shown) NUT WIRE ASSY., bleed resistor to ground WIRE ASSY, 25 ft. (7.6 m) (not shown) TOOL KIT, Includes items 124a & 124b (not shown), Required to install pump seal repair kit, part no. 237–969. S PUMP ASSY. TOOL S PUMP O-RING TOOL CLAMP, tube TUBE, sight 2 2 4 4 12 1 3 12 – 2 16 1 1 3 1 117* – 118 119 121 122 113–190 113–191 181–328 237–938 123 237–569 124 237–968 124a 124b 129 134 113–226 113–227 113–894 191–077 1 4 8 2 Qty. 2 6 2 2 1 4 4 2 9 2 1 1 1 1 1 16 2 2 * 2 2 2 2 2 1 l A pump fluid seal repair kit, part no. 237–969, is available. An installation tool kit, part no. 237–968, is required for seal installation. 2 Use polyethylene, 5/32 in. (4 mm) O.D., tubing. This tubing is available from Graco in 100 ft. (30.5 m) lengths. The chart below shows the part numbers and colors. 1 1 8 1 1 These parts are available to order as part of a TSL Tube Repair Kit, part no. 238–024. The kit also includes ref. no. 310, listed on page 43. AIR LOGIC TUBING Tubing Part No. Color 054–730 Natural (clear) 054–731 Blue 054–732 Red 054–733 Yellow 054–734 Black 308–504 39 Parts Item 74: Part No. 237–929 Accumulator Assembly 225 211{ 202 213 219 210 201 203 217 223 226 207 214{ 209 201 {208 205 221 218 206 215 {211 216 222 {214 204 220 226 207 209 212 202 224 40 Install the u-cups (214) with the lips facing to the outside of the piston (220). Install the piston assembly (222, 214, 220) into the end of the cylinder (219) with the internal chamfer. The cylinder end with the chamfer must face toward the upper end block (217). Apply lubricant to the seal contact surfaces. 308–504 Do not use lubricant on the o-rings (202) that are in the cap plugs (224). Apply anaerobic pipe sealant on the threads. Torque to 15 ft-lbs (20.25 NSm). Torque to 15 in-lbs (1.7 NSm). Apply dielectric lubricant to the o-ring. Parts Item 74: Part No. 237–929 Accumulator Assembly Ref. No. Part No. Description 201 202 203 722–834 188–555 113–058 204 205 206 109–570 113–135 113–074 207 208{ 209 210 211{ 212 113–075 – 113–164 113–066 – 113–140 213 113–141 O-RING, Vitonr O-RING, Viton CONNECTOR, 5/32 x 1/4 npt WASHER CRUSH RING TUBE ADAPTER 90_ elbow, 3/8 npt(m), for 1/2” O.D. tube WASHER U-CUP, urethane CAP SCREW, 3/8–16 x 1.5” WASHER O-RING, Viton CAP SCREW, 1/2–13 x 12.625” HEX NUT, 1/2” Qty. 8 8 1 4 1 1 4 1 4 4 2 4 4 Ref. No. Part No. 214{ – 215 108–630 216 217 218 219 220 221 222 223 224 225 226 190–693 190–694 190–695 190–696 190–697 190–698 190–699 190–700 190–701 190–702 190–703 Description Qty. U-CUP, hytrel & Viton MACHINE SCREW, 10–24 x 0.75” LOWER END BLOCK UPPER END BLOCK SHOULDER PIN CYLINDER PISTON PISTON ROD PISTON EXTENSION HIGH VOLTAGE SHIELD CAP PLUG THREAD CAP SUPPORT BLOCK 2 4 1 1 3 1 1 1 1 4 4 4 4 { These parts are available to order as part of an Accumulator Seal Kit, part no. 237–976Parts 308–504 41 Item 75: Part No. 237–930 Isolator Assembly 320 311 308* 304 A 305 324 337 333 329 320 G 334 320* 319* 332 306* 348 325 350 352 338 351 *309 349 *302 B 354 A 321 *320 353 B 335 318 331 327 343 326 307 313 325 328 306* 336 330 F 8565A 42 Apply lubricant. Torque to 15 in-lbs (1.7 NSm). Torque to 8 in-lbs (0.9 NSm). Tighten securely, until bottomed out. Lips face down 308–504 Lips face up On right isolator only On left isolator only. * Included in Kit 237–977 Parts Item 75: Part No. 237–930 Isolator Assembly Ref. No. Part No. 302} – 304 112–325 305 111–788 306} – 307 110–620 308} 309} 310* 311 313 314 315 – – 113–213 113–131 113–136 113–135 113–074 316 113–134 318 113–126 319} – 320} – 321 322 323 324 325 326 190–636 190–637 190–638 190–639 190–640 190–641 327 328 190–717 190–718 Description O-RING, Vitonr THUMB SCREW, 1/4–20 nc x 1” CAP SCREW, 1/4–20 unc–3a x 0.75” O-RING, Viton SCREW, 10–24 unc–2a x 0.5” O-RING, Viton O-RING, Viton BARBED HOSE FITTING AIR CYLINDER COMPRESSION SPRING CRUSH RING TUBE ADAPTER 90_ elbow, 3/8 npt(m), for 1/2” O.D. tube JAM NUT, 1–1/4 uns–2b CAP SCREW, 3/8–16 x 1” O-RING, CV75 WIPING SEAL, lubrithane & Vitonr GUIDE ROD AIR CYLINDER ADAPTER CAP PLUG BRACKET, isolator, left GROUND PLUG HIGH VOLTAGE ELECTRODE CYLINDER ROD COVER COVER RETAINER Qty. Ref. No. Part No. Description 1 1 329 330 331 332 333 190–642 239–017 190–644 190–645 190–646 334 335 336 337 338 190–647 190–689 238–085 240–691 103–310 343 100–609 344 346 192–840 113–058 347 348 349 113–184 240–680 240–656 350 112–905 351 352 353 110–755 113–127 114–590 354 240–657 TOP SUPPORT FLUID BLOCK BOTTOM SUPPORT TOP SEAL CARTRIDGE BOTTOM SEAL CARTRIDGE ISOLATOR ROD FLUID TUBE SPRING RETAINER BRACKET, isolator, right MACHINE SCREW, 8–32 unc–2a x 1/4” MACHINE SCREW, 1/4–20 unc–2a x 0.375”, right isolator only WARNING LABEL CONNECTOR, male, 5/32 x 1/4 npt ELBOW ADAPTER ROLLER, arc bypass WIRE ASSY., left isolator only WASHER, flat, #8 , right isolator only WASHER, flat NUT, hex, 1/4–20, nylon SCREW, cap, hex head, 1/4–20 x 3/4” WIRE ASSY., right isolator only 1 2 1 3 2 4 1 1 1 1 1 8 1 4 1 1 1 1 2 1 1 1 Qty. 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 2 2 2 1 } These parts are available to order as part of an Isolator Seal Kit, part no. 237–977. * This part (along with items 1, 4, 40, and 117) is included in TSL Tube Repair Kit 238–024, which may be purchased separately. 308–504 43 1 2 QUICK DUMP 46 10 PB YEL 47 OUTER PORT 11 RED 22 5 A1 SM2 22 PRT SM3 19 A1 A– C– 23 PRT SM4 28 B1 B+ SM5 D+ 13 12 13 21 A+ C+ 12 C1 C0 30 53 INSIDE PORT A PB 26 08 51 22 YEL 16 P 2 14 16 20 RED 8 15 OUTER 113–279 push-in tube fitting plug VOLT DUMP 8 7 PA 09 BLUE 6 21 V2 8.5” TYP. READY TO FLASH INDICATOR 5 READY TO SPRAY INDICATOR EV1 PAINT SOURCE V3 E A 25 P OUTER PORT B PA E V4 21 LOOSE HOSE DOOR OPEN INDICATOR PA E SIDE PORT 41 B PORT BLUE BLUE 113–284 push-in tube fitting A B PORT EX INSIDE PORT RED 49 16 07 BLUE PB 16 P TOP PORT 15 5 PB 25 20 INSIDE PORT 44 29 BOT. PORT OUTER PORT DOOR 06 TSL V1 24 20 18 YEL PA E 28 OUTER 24 01 14 PB 05 02 A2 FULL 10 20 B– D– 40 OUTER A B PORT P 26 X PRT SM1 29 BO 5 OUTER PORT 18 OUTER PORT 04 13 17 19 INSIDE PORT 03 23 12 A2 LOW 010 5 16 13 & 52 3 18 OUTER PORT PA YEL 43 A B 14 A1 FULL TSL INSIDE PORT 17 10 V5 YEL 48 OUTER PORT 55 REGULATED AIR INLET 12 P E A1 LOW pneumatic AND valve 10 OUTER PORT YEL FILL/ RUN 113–282 A1 RED Air Logic Schematic and Parts YEL pneumatic OR valve 3 11 FLUSH/ RESET 4-way remote air valve O1 to O10 113–281 3 2 113–338 SIGNAL WILL ONLY APPEAR WHEN 2ND ACCUMULATOR IS FULL ACCUM. #1 15 42 BOT. PORT EV2 ACCUM. #2 308–504 REMOTE FLUSH/ RESET Part No. Description V1 to V5 44 REMOTE FILL/RUN Item 05327 113–284 push-in tube fitting Dimensions Measurements, inches (mm) AA BB AA BB CC DD Width* 53.625 (1362) 49.625 (1260) 37.50 (953) 51.0 (1295) 17.0 (432) * Width at the widest point of the voltage block assembly CC DD 05332A 308–504 45 Technical Data Category Data Maximum Working Pressure 100 psi (0.7 MPa, 7 bar) Air Pressure Operating Range 60–100 psi (0.4–0.7 MPa, 4.1–7 bar); Typical Pressure 80 psi (0.5 MPa, 5.5 bar) Fluid Pressure Operating Range 0–100 psi (0–0.7 MPa. 0–7 bar) Maximum Voltage 60 kV Fluid Specification For use with Graco PRO 5500wbt and PRO 3500wbt guns when electrostatically spraying conductive, waterborne fluids that meet at least one of the following conditions of non-flammability: D The fluid has a flash point above 140_F (60_C) and a maximum organic solvent concentration of 20%, by weight, as determined in accord with the Standard Method of Testing for Flash Point by the Pensky-Martens Closed Tester, ASTM D93. D The fluid does not sustain burning characteristics in accordance with the Standard Method for Sustained Burning of Liquid Mixtures by the Setaflash Apparatus, ASTM D4206. Accumulator Capacity 100 oz. (3 liters) Maximum Fluid Temperature 120_F (49_C) Weight 257.0 lbs. (115.65 kg) Air Inlet 1/4 npt(f) quick-disconnect Fluid Inlet 3/8–18 npsm (R3/8–19) compound thread Wetted Parts 304 SST, PTFE,rPEEK, Vitonr, Epoxy, Acetal Sound Pressure at 80 psi (550 kPa, 5.5 bar){ 74.6 Db(A) { Sound pressure was measured per a time weighted average over a 4 minute complete dispense/refill cycle. Vitonr r 46 308–504 Notes 308–504 47 Graco Standard Warranty Graco warrants all equipment referenced in this document which is manufactured by Graco and bearing its name to be free from defects in material and workmanship on the date of sale by an authorized Graco distributor to the original purchaser for use. With the exception of any special, extended, or limited warranty published by Graco, Graco will, for a period of twelve months from the date of sale, repair or replace any part of the equipment determined by Graco to be defective. This warranty applies only when theipment equ is installed, operated and maintained in accordance with Graco’s written recommendations. This warranty does not cover, and Graco shall not be liable for general wear and tear , or any malfunction, damage or wear caused by faulty installation, misapplication, abrasion, corrosion, inadequate or improper maintenance, negligence, accident, tampering, or substitution of non–Graco component parts. Nor shall Graco be liable for malfunction, damage or wear caused by the incompatibilit y of Graco equipment with structures, accessories, equipment or materials not supplied by Graco, or the improper design, manufacture , installation, operation or maintenance of structures, accessories, equipment or materials not supplied by Graco. This warranty is conditioned upon the prepaid return of the equipment claimed to be defective to an authorized Graco distributo r for verification of the claimed defect. If the claimed defect is verified, Graco will repair or replace free of charge any defecti ve parts. The equipment will be returned to the original purchaser transportation prepaid. If inspection of the equipment does not disclose any defect in material or workmanship, repairs will be made at a reasonable charge, which charges may include the costs of parts, labor, and transportation. THIS WARRANTY IS EXCLUSIVE, AND IS IN LIEU OF ANY OTHER W ARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. Graco’s sole obligation and buyer’s sole remedy for any breach of warranty shall be as set forth above. The buyer agrees no thatother remedy (including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person operty, or pr or any other incidental or consequential loss) shall be available. Any action for breach of warranty must be brought within two ears (2) yof the date of sale. GRACO MAKES NO WARRANTY, AND DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IN CONNECTION WITH ACCESSORIES, EQUIPMENT, MATERIALS OR COMPONENTS SOLD BUT NOT MANUFACTURED BY GRACO. These items sold, but not manufactured by Graco (such as electric motors, switches, hose, etc.), are subject to the warranty, if any, of their manufacturer. Graco will provide purchaser with reasonable assistan ce in making any claim for breach of these warranties. In no event will Graco be liable for indirect, incidental, special or consequential damages resulting from Graco supplying equi pment hereunder, or the furnishing, performance, or use of any products or other goods sold hereto, whether due to a breach of contract, breach of warranty, the negligence of Graco, or otherwise. FOR GRACO CANADA CUSTOMERS The parties acknowledge that they have required that the present document, as well as all documents, notices and legal proceedi ngs entered into, given or instituted pursuant hereto or relating directly or indirectly hereto, be drawn up in English. Les parti es reconnaissent avoir convenu que la rédaction du présente document sera en Anglais, ainsi que tous documents, avis et procédures judiciai res exécutés, donnés ou intentés à la suite de ou en rapport, directement ou indirectement, avec les procedures concernées. Manual Change Summary Graco Phone Number TO PLACE AN ORDER , contact your Graco distributor, or call this number to identify the distributor closest to you: 1–800–367–4023 Toll Free The manual was revised per ECO V5284. All written and visual data contained in this document reflects the latest product information available at the time of publication. Graco reserves the right to make changes at any time without notice. Sales Offices: Minneapolis, Detroit Foreign Offices: Belgium, England, Korea, France, Germany, Hong Kong, Japan GRACO INC. P.O. BOX 1441 MINNEAPOLIS, MN 55440–1441 http://www.graco.com 48 308–504 PRINTED IN U.S.A. 308–504 July 1995 Revised October 1998
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
Download PDF
advertisement