Instructions

Add to my manuals
60 Pages

advertisement

Instructions | Manualzz
MX43 Central Digital and Analog
Measurement Unit
du 14 juin 2007
Version de contrôle n°2
User Manual
P/N : NPM43GB
Revision : F
Copyright  2011 by Industrial Scientific – Oldham S.A.S.
English version
Edition: July 2010 revision 0.
All rights reserved. The reproduction of all or any section of this
document in any form whatsoever without the written permission of
Industrial Scientific – Oldham S.A.S. is forbidden.
The information contained in this manual is accurate to our
knowledge.
As a result of continuous research and development, the
specifications of this product may be modified at any time without
prior notice.
Industrial Scientific Oldham S.A.S.
Rue Orfila
Z.I. Est – BP 20417
62027 ARRAS Cedex
Tel.: +33 (0)3 21 60 80 80
Fax: +33 (0) 3 21.60.80.00
E-mail: [email protected]
Website: http://www.oldhamgas.com
Table of contents
Chapter 1 І General Information.................................................... 1
User Manual ................................................................................................ 1
Symbols used .............................................................................................. 1
Safety Instructions ....................................................................................... 2
Important Information .................................................................................. 2
Liability Limits .............................................................................................. 2
Chapter 2 І General Introduction .................................................... 3
Purpose of the MX43 Central Measurement Unit ............................ 3
This central unit is intended for the continuous measurement and
control of the gases present in the atmosphere. ............................ 3
The COM43 Application............................................................................... 5
Chapter 3
І Mechanical Installation.............................................. 7
MX 43 Central Measurement Unit................................................................ 7
Digital Modules ............................................................................................ 9
Chapter 4
І The MX43 Central Unit............................................. 11
Overview of the Unit .................................................................................. 11
Front Face ................................................................................................. 15
Alarm and Relay Thresholds ..................................................................... 18
Name Plate................................................................................................ 19
Chapter 5
І Digital Modules ........................................................ 21
Addressable Digital Modules ..................................................................... 21
RS485 Transmission ................................................................................. 22
Configuration of Communication................................................................ 22
Relay modules........................................................................................... 24
16-Logic Input Module ............................................................................... 26
8-Analog Input Module............................................................................... 27
4-Analog Output Module............................................................................ 28
Table of Contents
i
Chapter 6
І Wiring and Electrical Connections ......................... 31
Central Unit Connection............................................................................. 31
4- or 8-Relay Modules ............................................................................... 36
16-Logic Input Module ............................................................................... 36
8-Analog Input Module............................................................................... 37
4-Analog Output Module............................................................................ 37
Chapter 7 І Menus....................................................................... 38
General Menu Tree ................................................................................... 38
Navigation Key Functions .......................................................................... 38
Display in normal mode ............................................................................. 38
Main Menu................................................................................................. 40
System ...................................................................................................... 40
Programming ............................................................................................. 41
Calibration ................................................................................................. 41
Maintenance .............................................................................................. 44
Information ................................................................................................ 44
Chapter 8
І Principal references ................................................ 48
Chapter 9
І Certificate of Compliance........................................ 50
Chapter 10 І Technical Specifications .......................................... 51
MX43 Central Unit........................................................................... 51
Relay Module............................................................................................. 53
16-Logic Input Module ............................................................................... 53
8-Analog Input Module............................................................................... 53
4-Analog Input Module............................................................................... 54
Chapter 11
ii
MX43
User manual
І Index....................................................................... 55
Chapter 1 І General Information
User Manual
The instructions given in this manual must be read thoroughly before
installation and start-up, particularly those concerning the points related to the
safety of the end-user. This user manual must be made available to every
person involved in the activation, use, maintenance, and repair of the unit.
The information, technical data, and diagrams contained in this manual are
based on the information that is available at a given time. In case of doubt,
contact Industrial Scientific Oldham for additional information.
The aim of this manual is to supply simple and accurate information to the
user. Industrial Scentific Oldham cannot be held liable for any
misinterpretations in the reading of this manual. In spite of our efforts to
produce an error-free manual, it may nonetheless contain some unintentional
technical inaccuracies.
In the client’s interest, Industrial Scientific Oldham reserves the right to modify
the technical characteristics of its equipment to increase their performance
without prior notice.
The present instructions and their content are the inalienable property of
Industrial Scientific Oldham.
Symbols used
Icon
Significance
This symbol indicates useful additional information.
This symbol indicates:
This equipment must be connected to ground.
This symbol denotes:
Protective earth terminal. A cable of the adequate diameter must
be connected to ground and to the terminal having this symbol.
This symbol denotes:
Attention! In the present mode of use, failure to adhere to the
instructions preceded by this symbol can result in a risk of
electric shock and/or death.
This symbol indicates:
You must refer to the instructions.
European Union (and EEA) only. This symbol indicates that this
product must not be discarded with household waste, as per the
EEA directive (2002/96/CE) and the regulations of your respective
country.
It must be disposed of at a collection point that is reserved for this purpose, for
example, an official site for the collection of electrical and electronic equipment
(EEE) in view of their recycling, or a point of exchange for authorized products that
is accessible when you acquire a new product of the same type.
1 – General Information
1
Any deviation as regards these recommendations for the disposal of this type of
waste can have negative effects on the environment and public health, as these
electric and electronic products generally contain substances that can be
dangerous. Your full cooperation in the proper disposal of this product promotes a
better use of natural resources.
Safety Instructions
Labels intended to remind you of the principal precautions of use have been
placed on the unit in the form of pictograms. These labels are considered an
integral part of the unit. If a label falls off or becomes illegible, see to it that it
is replaced. The significance of the labels is detailed below.
The installation and electrical connections must be carried out by
qualified personnel according to the instructions of the manufacturer
and the standards of the authorities competent in the field.
Failure to adhere to the instructions can have serious consequences on the safety of
persons. Absolute strictness is required above all as regards electricity and assembly
(coupling, network connections).
Important Information
The modification of the material and the use of parts of an unspecified origin
shall entail the cancellation of any form of warranty.
The use of the unit has been projected for the applications specified in the
technical characteristics. Exceeding the indicated values cannot in any case
be authorized.
Liability Limits
Neither Industrial Scientific Oldham nor any other associated company under
any circumstances can be held liable for any damage, including, without
limitations, damages for loss or interruption of manufacture, loss of
information, defect of the MX43 central unit, injuries, loss of time, financial or
material loss, or any direct or indirect consequence of loss occurring in the
context of the use or impossibility of use of the product, even in the event that
Industrial Scientific Oldham has been informed of such damage.
2
MX43
User manual
Chapter 2 І General Introduction
Purpose of the MX43 Central Measurement Unit
This central unit is intended for the continuous measurement and control of the gases
present in the atmosphere.
Wall-mounted MX43
Rack-mounted MX43
8-relay modules and 4 4-20
mA output modules
008
Figure 1: Wall-mounted MX43 and examples of the modules.
The system primarily comprises:
■ a wall-mounted MX43 (4 or 8 lines) or rack-mounted MX43 (8 lines);
■ different modules (detector with digital or analog output, logic inputs,
analog inputs, relay outputs, and analog outputs).
The MX43 instantly handles the measurements of detectors and input
modules. As soon as the measurements reach the programmed limit, a sound
and visual alarm are given. At the same time, the corresponding relay or
relays are activated, in turn controlling the additional internal or external
actions envisaged by the user.
The measurement unit is programmed by using the COM43 application.
Figure 2 presents a configuration example.
2 – General Introduction
3
Configuring PC with the
COM43 application
MX43
External
power supply
Liaison
2 logic inputs
USB
Digital detectors
Module 4 relays
Module 8 relays
Module
logic input
16 logic inputs
Module
4 * 4-20 mA outputs
Analog
detectors
8 analog
inputs
Analog recorders
002
Figure 2: Example of an MX43 configuration using different analog and digital detectors as
well as digital modules.
4
MX43
User manual
The MX43 Central Measurement Unit
Versions
The MX43 central measurement unit is available in 3 versions:
■ Wall version 4 lines.
■ Wall version 8 lines.
■ Rack version 8 lines.
0012
Figure 3: Wall mounted version MX43 (left illustration) or Rack mounted version (right
illustration).
The following table details the possibilities of configuration, depending on the
type of unit. On each line, it is possible to connect a 4-20mA analog detector
or one, or several, digitally addressable modules.
Maximum number of
Versions
Modules (1)
Detectors
External
relays
Logic inputs
Analog
ouputs
4 lines
16
16
8
16
16
8 lines
32
32
24
32
32
(1) Gas detectors, 4 or 8-analog output modules, and 16-logic input modules.
Table 1: Summary of the maximum configurations as per the central unit.
The COM43 Application
This is intended for setting the MX43 parameters from a PC in the Windows®
environment. The operation and use of this application is the subject of a
specific training course.
2 – General Introduction
5
6
MX43
User manual
Chapter 3
І Mechanical Installation
This chapter details the mechanical installation of MX 43 and the digital
modules.
MX 43 Central Measurement Unit
Location
The MX43 shall be installed in premises without explosive atmospheres, away
from direct sunlight exposure, and protected from humidity, dust, and
temperature variations. It shall preferably be located in a place under
supervision (guardhouse, control room, or instrument room, for example).
Attachment of the wall enclosure
Access to the central unit must be ensured in the front in order to facilitate
adjustments, monitoring, and cabling. A space of 400 mm is necessary in front
of the MX43 for opening the door.
(*) rear fixing legs included.
Figure 4: Size of the wall version.
044
3 - Mechanical Installation
7
Use 2 fixing screws 4x25 mm for fixing the support of the case.
072
Figure 5: Fixing of the wall mounted version MX43 with a support plate.
Setting-up of a 19” Rack – 4 U
Access to the unit must be ensured in order to facilitate adjustments and
monitoring, and likewise in the back in order to allow easy access to the
different connectors at the rear.
This rack is built into a bay or a standard 19” cabinet. A free space of ½ U (22
mm) shall be provided for above and below the rack so as to assure the
proper ventilation of the MX43.
046
Figure 6: Size of the rack version.
8
MX43
User manual
Digital Modules
The cabling is the subject of the paragraph Connection of digital
modules on page 26.
Gas detectors
Refer to the manual supplied with each detector.
Location
Each detector is positioned at the ground level, on the ceiling, at the height of
the respiratory tract, or near air extraction ducts, depending on the density of
the gas to be detected or applied. Heavy gases are detected close to the
ground, while lighter gases are present along the ceiling. If necessary, contact
Industrial Scientific Oldham for any questions regarding proper detector
positioning.
Fixing
The detectors shall preferably be positioned in an accessible place to facilitate
the operations of inspection and maintenance as well as the absolute safety of
the operators. The detectors must not be obstructed by anything that will
prevent them from measuring the ambient environment to be checked.
If mounting an OLCT10N on a vertical surface, position the cable gland
downwards.
Other models
Location
The relay modules, logic outputs, analog outputs, and analog inputs are
positioned depending on the installation layout, mandatorily in places free
from explosive atmospheres, protected from humidity, dust, and temperature
variations; for example in technical cabinets.
Fixing
These modules shall be mounted on
a DIN rail in a cabinet or in an
electrical cabinet.
For relay modules connected to low
voltage electrical parts, the
installation is carried out per the
standards in force.
134
Figure 7: Fixing of a module (relay, logic
outputs, or analog outputs or inputs) on a
DIN rail.
3 – Mechanical installation
9
10
MX43
User manual
Chapter 4
І The MX43 Central Unit
Overview of the Unit
External view
080
Rep.
Function
Rep.
Function
A.
Monochromatic, backlit graphic
display
H.
Failure/maintenance indicator
B.
Zone 1 status indicator
J.
Contextual soft keys
C.
Zone 2 status indicator
K.
Alarm release key
D.
Integrated siren (option)
L.
Free identification of zones
E.
Integrated flash (optional)
M.
Strip for locating zones
F.
Lock
N.
Handle
G.
Start/Stop indicator
Figure 8: External view of the wall-mounted and rack-mounted versions.
4 – The MX43 Central Unit
11
Internal motherboard view
084
Figure 9: Internal view of the wall-mounted version (top) and rack mounted version
(bottom).
Ref.
A.
Function
LED digital communication status indicators.
The information displayed by each red-green diode pair of a line is interpreted as follows:
LED Status
Red
Fast blinking
Significance
Green
Fast blinking
Normal functioning of the line
- Tx communication request
- Rx: response of digital module(s).
Irregular
blinking
Irregular
blinking
Bad communication quality with at least one
module.
Blinks 1X/sec
Off
Communication failure. Absence or failure of line
modules.
A communication failure is signaled by the
activation of the internal buzzer, the presence of
the orange failure indicator and via the default
relay.
Off
12
MX43
User manual
Off
No digital module active on the line.
B.
Optional 24 VDX NiMH battery pack.
C.
Terminal block for the analog card power supply.
D.
Connector for the direct current external supply.
E.
Battery fuse (4A) and external power supply (21 to 28 VDC, 3.2 to 4 A max.).
F.
Connector for
-- Internal siren 24 VDC – 19mA max. Sounder+ and Sounder- terminals
- Internal flash 24 VDC – 40 mA max. Flash+ and Flash- terminals
G.
Relays of alarms, from high to low Failure, R5, R4, R3, R2, R1.
- Failure: Non configurable failure relay
- R1 to R5: Configurable alarm relays
- Corresponding LED indicator: Lit when relay is under voltage.
Setting of alarm limits
The alarm limits governing relays R1 to R5 can only be set via the COM43 application.
The silkscreen image represents relays offline.
Relays R1 to R5 can be configured in positive or negative safety. Programming via
COM43 in:
-Normal mode: Operation of the relay as per the normal alarm management (the relay is released only
-Buzzer mode: The same as as in normal operation, with, in addition, the possibility of
releasing the buzzer relay even if the event is still present. The time delays are:
.Duration of maintenance: Minimum time of activation, adjustable from 0 to 900 seconds.
.Automatic release: Time adjustable between 15 and 900 seconds, beyond which the buzzer relay is a
.Reactivation: Time adjustable between 15 and 900 seconds, beyond which the buzzer
relay is reactivated.
Alarm Relay Controls
-Logic equations of up to 4 levels of parentheses by the logic operators OR-AND, NORNAND. The result of the equation controls the relay.
-Polling Operations (x over y): There must be at least “x” events over the total of “y” to
activate the relay. Optionally, the user may define whether a failure is considered an
event in the same category as an alarm.
H.
Alarm relay terminal block. CRT contacts, 250 V AC – 2A or 30 V DC – 2 A.
J.
Integrated siren (optional).
K.
Power supply sector block.
L.
Integrated flash (optional).
M.
Microcontroller PCB.
N.
Area of 12 + 6 cable glands (connections towards the exterior).
P.
Ground rod and bundle of shielded cables for digital and analog connections.
Q.
Terminal block for lines 1 to 8 (or 1 to 4 as per version). Refer to the Digital lines
paragraph on page 37.
R.
Connector for the connection of a remote release (dry contact NO.)
S.
Power supply sector input.
T.
Protective secondary ground connection.
U.
USB connector for connection with the PC supporting COM43 application.
V.
Programming switch.
W.
CR2032 lithium battery.
4 – The MX43 Central Unit
13
Wall-mounted version - View of a microcontroller PCB
026
Rep.
A.
Function
Connector for USB key (future function). Allows the loading of data from the MX43 to
the PC (values measured, history, etc.) or from the PC to the MX43 (transfer of settings,
updating of software loaded in MX43, storage of measurements).
B.
LCD graphic display card.
C.
USB port for programming MX43.
D.
Program (or modes) selector
0. Normal operation of MX43.
1. Transfer of settings information from PC to MX43.
2. Transfer of settings information from USB port to MX43.
3. Updating of the internal software of MX43 from a PC. MX43 restarts automatically.
4. Updating of the internal software of MX43 from a USB port. MX43 restarts
automatically.
Once the parameter setting or the update of the central unit is
completed, always reposition the selector to position “0”.
E.
CR2032 lithium battery. Safeguards the preservation of the records and real time clock
in case of total power failure. Autonomy of approx. 450 days with the power off. At each
battery change, power the MX43.
F.
Microcontroller PCB.
G.
Regulating LCD contrast.
H.
Microcontroller zero reset button. Press this button to reset the central unit.
Figure 10: Internal view of the wall-mounted version - microcontroller PCB and display.
14
MX43
User manual
Front Face
This has the following aspect:
034
Figure 11: Front face of the MX43 in wall-mounted and rack-mounted versions.
LCD
The display shows the measurements or the menus of the parameter setting,
and an inverse video display indicates that the module that is currently
displayed has an active alarm.
The details of the displays are the subject of the chapter Menus on page 44.
ECR_02_04
Figure 12: Example of a measurement display (screen) or parameter setting display (menu
on the left).
Refer to the paragraph Display in normal mode on page 45 for information
about what may be displayed on the screen.
Contextual Keys (B)
The function of each of the 5 keys indicated in the lower part of the display
changes depending on the page displayed.
Zone Status Indicators (C)
Eight bars of 7 indicators each are displayed on the central unit.
The 4 bars to the right are not operative on a 4-line MX43.
Each bar represents a geographic area of the complete installation
and not the 4 or 8 lines of the MX43.
Each bar displays the status of the group of detectors of the pertinent zone as
follows:
4 – The MX43 Central Unit
15
Icon
Function
Orange indicator of high-range excess (OVS: overscale, high-range excess). This
value is adjustable up to 110% of the range.
- Off: The measurement is lower than the OVS value programmed.
- Lit: The measurement is higher than the OVS value programmed. The alarm
relays are activated in accordance with the program. In parallel, the display
indicates « > ».
OVS resetting is done manually and is only possible if the value measured drops
below the programmed value.
Management of « Clear doubt »
The Clear doubt alarm is only applicable to the detection of explosive gases in a
range of 0-100%LEL, and is subject to the decision of the operator. Upon the
detection of a concentration of gas higher than 100% LEL, the LCD indicates a
measurement blocked at 100% LEL and the message > 100% LEL. The message
Strong concentaration Resetting by a person authorized in the maintenance menu
is displayed. The OVS and FAILURE indicators are activated. The alarm can only
be deactivated by stopping the detector via the maintenance menu once the gas
level decreases below this limit.
ALARM 3
Red indicators of alarm status:
ALARM 2
- Off: Measurement lower than the threshold defined.
ALARM 1
- Fixed light: At least one of the gas detectors has an active alarm. The release is
programmed in automatic mode or has already been requested by pressing the
Alarm reset key on the front face.
- Blinking light: At least one of the gas detectors has an active alarm. The release
is programmed in manual mode.
The alarm relays are activated in accordance with the programming.
Orange indicator of low- range excess (UDS: Under scale, low-range excess). This
value is adjustable from 0-10% of the range.
- Off: The measurement is higher than the UDS value programmed.
- Lit: The measurement is lower than the UDS value programmed. The alarms of
the relays are activated in accordance with the programming. In parallel, the
display indicates « < ».
UDS resetting is automatic once the failure disappears.
FAULT
Orange failure indicator
- Off: No failing module or detector.
- Fixed light: Communication problem with one of the modules or invalid detector
measurement, that is to say either below -10% of the range or above 110% of
the range.
- Blinking light: Central unit in maintenance mode (test, calibration).
The Failure reset is automatic once the failure disappears.
POWER
Green start/stop indicator for the detectors/modules of the zone.
- Off: All the detectors of the zone are stopped.
- Fixed light: At least one of the detectors of the zone is working.
- Blinking: The information details of one of the detectors/modules of the zone are
actually displayed on the LCD screen.
Flash and siren (D and E)
Siren (Figure 11, D)
Located in the upper portion of the box, the siren is optionally available solely
in the wall-mounted version. It is always discontinuous and is configured via
the COM43 application.
16
MX43
User manual
Flash (Figure 11, E)
Located in the upper portion of the box, the Flash is optionally available solely
in the wall-mounted version. It is configured via the COM43 application.
The technical indicators (F and G)
These two indicators reflect the status of the MX43.
Icon
Function
Green general start/stop indicator denoting the power supply status
- Fixed: Correct power supply.
- Off: No power supply.
- Blinking: Power supply problem (absence of power in the sector or problems in the
internal battery pack.
Failure/maintenance orange indicator
- Off: No failure detected.
- Fixed light: Presence of some failure (central unit, detector, communication,
memory). The alarm goes off automatically on the clearing of the failure.
- Blinking light: MX43 in maintenance mode (test, calibration).
Alarm reset Key (H)
Pressing this key has the effect of releasing the internal buzzer and the
alarms that it enables. This key has the same function as the remote release
key that is possibly connected; see paragraph on the Remote release
connector on page 39.
Zone Identification (J and K)
Draw the tab (Figure 11, K) to enable the input (Figure 11, in J) of terms for
the zones.
036
Figure 13: Drawing of the tab.
4 – The MX43 Central Unit
17
Alarm and Relay Thresholds
Alarm thresholds, relay programming, the management of time delays, and
methods of release are controlled over the COM43 application.
Note: It is possible to modify an alarm limit via the Programming menu of
MX43.
Parameters of Detector alarms
It is possible to program the following for each detector:
■ 3 alarm thresholds.
■ Each value is configurable in increasing or decreasing values.
■ Each alarm is configurable as an instantaneous and/or average alarm of
15 to 480 minutes.
■ Each alarm has an adjustable lag of 0 to +3% (or -3% for a negative alarm)
for the value of the range of measurement, by pitch steps of 1%.
■ A high-range excess alarm (OVS: over scale).
■ A UDS low-range excess alarm (UDS: underscale).
■ A “clear doubt” alarm (in the case of explosive gas detectors).
The alarms may be programmed for automatic or manual release (except
OVS, UDS, and clear doubt).
Automatic deletion of alarms
The release (resetting) of alarms does not require any intervention. The
management of alarms (relays, indicators, buzzer) is carried out according to
the following table:
Event
Appearance
Message
screen
Alarm relay
(normal)
Alarm
LED alarm
Internal
buzzer
AL (1,2,3)
Activated
Activated
Fixed light:
Activated
Relay
(buzzer)
and inverse
video of the
detector
Press alarm
reset
AL (1,2,3)
and inverse
video of the
detector
Activated
Deactivated
Fixed light:
Deactivated
Disappearan
ce
Normal
display
Deactivated
Deactivated
Off:
(a)
(a):
(b):
Manual release compulsory to stop the internal buzzer.
Automatic deactivation upon the disappearance of an alarm, even if no release has been
requested before the disappearance of the alarm.
(c): If programmed
Table 2: Automatic deletion of alarms.
Manual deletion of alarms
Release (resetting) by the operator is compulsory. The management of alarms
18
MX43
User manual
(relay, indicator, buzzer) is carried out per the following table:
Event
Appearance
Message
screen
Alarm relay
(normal)
Alarm relay
LED alarm
Internal
buzzer
AL(1,2,3)
Activated
Activated
Blinking light
Activated
AL(1,2,3)
Activated in
and inverse
video of the
detector
the presence
of an event
Deactivated
Fixed light if
Deactivated
AL(1,2,3)
Deactivated
and inverse
video of the
detector
if the event
disappears
Normal
display
Deactivated
(1)
(buzzer)
Alarm relay
(normal)
and inverse
video of
detector
Release
activated
Disappearan
ce
an event is
present
Deactivated
Off if an
event
disapears
Deactivated
Off (1)
Deactivated
(1)
(1): compulsory after manual release.
Table 3: Manual alarm deletion.
Internal relays and buzzers
The operating mode of relays and optional visual and sound alarms (Figure 9,
F and G) is configured over the COM43 application.
■ Relays: 5 alarm relays (R1 to R5) are common to all the lines.
■ The internal buzzer is common to all the alarms of all the lines: it is
activated on the appearance of an event (failure or alarm). The common
failure relay is active in parallel. The sound frequency of the internal buzzer
differs in accordance with the alarm threshold. High alarm thresholds have
a faster sound frequency, thus making it possible to distinguish the alarm
level. The internal buzzer can be deactivated by the internal programming
menu or the COM43 application.
Note: The failure relay cannot be programmed via the COM43 application, but
is activated on the occurence of a failure.
Name Plate
The name plate is attached on the right side of the MX43. It contains the
following information:
■ Function and type of equipment.
■ Precautions of use.
■ Alternative voltage supply, frequency, rating of protective fuse, nominal
power.
■ Continuous voltage supply, frequency, rating of protective fuse, nominal
power.
■ Symbol of destruction and danger.
■ Product reference and serial number, manufacturer logo.
■ Version: 4 or 8 lines.
4 – The MX43 Central Unit
19
Communication
A digital RS485 Modbus output is available. The manual is pending. Please
contact Oldham at [email protected] for further information
20
MX43
User manual
Chapter 5
І Digital Modules
This chapter presents the digital modules that may be installed on the lines of
MX43.
The details of module connection are given on page 26.
Digital modules are configured via the COM43 application.
Addressable Digital Modules
These modules are connected on each of the available 4 or 8 lines of the MX43,
up to a limit of 32 modules on a version of 8-lines or 16 modules on a 4-line
version. The following table regroups the available modules:
Type of module
Illustration
Page
Digital gas detector (OLCT10N, OLCT80…).
048A-B
Output module, 4 relays with 2 additional logic inputs
24
904
Output module, 8 relays with 2 additional logic inputs
24
906
Module with 8 analog inputs
26
050
Module with 16 logic inputs
25
910
Module with 4 analog 4-20mA outputs and 2 additional logic
inputs
27
912
Table 4: Addressable digital modules.
5 – Digital Modules
21
RS485 Transmission
General Topology of RS 485 Network
The digital modules are linked by 2 twisted cable pairs of 4 x 0.22 m² minimum,
type MPI-22A, nominal resistance of 120 Ohms. This cable carries the RS485 (A
and B) signal on one pair and the power supply of the modules (0–24 VDC)
connected to the line on the other pair. Shielding necessarily links all the modules
to the terminal block of MX43.
The + 24 VDC, 0V, A, B terminals are respectively connected to +24VDC, 0V, A,
B terminals of the other modules on the line and then to the connector of the
corresponding line on the central unit. The cable shielding must be connected to
the grounding rod of the MX43.
At the end of the busbar, the 120-Ohm end of line resistor (EOL
RESISTOR/RESISTANCE F.D.L) must be activated (whatever the last module).
No portion of the bare end of the terminal wires should be visible.
For protection against any electromagnetic disturbances, the data
as well as screen wires (or braids) must be cut as short as
possible.
MX43 line terminal
Earthing
terminal
MX43
Terminal (detector,
module)
042
Figure 14: Principle of connecting modules to a MX43 line.
An incorrect installation of the cables or cable glands can cause
measurement errors or a malfunctioning of the system.
Do not lay the cables close to equipment such as engines,
transformers, or lines generating important magnetic fields.
It is recommendable to always ensure a distinct separation
between these cables and the cables of other circuits.
Configuration of Communication
Module Address
All the digital modules on a line must be
identified by a unique address.
Switches 1 to 5 of the configuration block of
each module make it possible to establish an
address number (1 to 32) in binary mode.
In the illustration to the right, the address 9
(10010) has been defined.
The Addressing Table below lists the possible
combinations.
22
MX43
User manual
004
Figure 15: Switches of
address configuration.
1
2
3
4
5
1
1
0
0
0
0
2
0
1
0
0
0
3
1
1
0
0
4
0
0
1
0
5
1
0
1
6
0
1
1
7
1
1
8
0
0
M odule
Address
Module
address
Swiches
(On: 1; OFF: 0)
Switches
(ON = 1; OFF = 0)
1
2
3
4
5
17
1
0
0
0
1
18
0
1
0
0
1
0
19
1
1
0
0
1
0
20
0
0
1
0
1
0
0
21
1
0
1
0
1
0
0
22
0
1
1
0
1
1
0
0
23
1
1
1
0
1
0
1
0
24
0
0
0
1
1
9
1
0
0
1
0
25
1
0
0
1
1
10
0
1
0
1
0
26
0
1
0
1
1
11
1
1
0
1
0
27
1
1
0
1
1
12
0
0
1
1
0
28
0
0
1
1
1
13
1
0
1
1
0
29
1
0
1
1
1
14
0
1
1
1
0
30
0
1
1
1
1
15
1
1
1
1
0
31
1
1
1
1
1
16
0
0
0
0
1
32
0
0
0
0
0
Table 5: Addressing table (address depends on switch positions).
Remarks:
■ The physical address of a module (1 to 32) must be identical to the address
stated on the configuration program COM43 in the central unit.
■ During module replacement, all the configuration switches of a new module
must be positioned in the same configuration as those of the the previous
module.
■ The 6 switch (FRAME FILLING/REMPLISS TRAME) must be set to OFF and the 7
switch (DELAY/TEMPORISATION) must be set to ON (options unused).
■
An analog-input module systematically takes 8 addresses.
End of line Resistor
Solely for the last module of each line,
set switch no.8 (EOL
RESISTOR/RESISTANCE F.D.L.) to ON or set
the jumper of the analog input PCB to
Closed.
006
Figure 16: End of line resistor switch in
position “ON”.
6 – Digital Modules
23
Relay modules
Function
This digital module, available in two
versions, allows for the management
of:
■ 1 to 4 relay outputs;
■ Or 1 to 8 relays.
In addition, it has 2 logic inputs.
2 logic inputs
Digital line
4 wires
4 or 8 output relays
(CRT 250 VAC – 2A)
108
Figure 17: 8-relay module.
Introduction
Ref..
Description
A.
Connector for 2 logic inputs.
B.
Configuration switches of the module
(digital address, delay, and end of line
resistor).
C.
Switches for relay configuration.
D.
Power supply and digital network
connector.
E.
Programmable relay (4 or 8).
F.
Relay status indicator.
G.
Connection terminal.
100
Figure 18: 8-relay module.
A – Logic input connectors
Each of these two terminals (Figure18 A) may be connected to a voltage-free
contact as per Figure 34. There is no alarm when the contact is open.
B – Module configuration switches
These switches are set according to the following table.
Term
Symbol
Slave number
Numéro esclave
See details in the paragraph Module Address on page 26.
Frame filling
Remplissage de trame
Factory settings. Do not modify.
Delay
Temporisation
Factory settings. Do not modify.
E.O.L Resistor
Résistance F.D.L.
See details in paragraph End of line Resistor, on page 27.
Table 6: Relay module configuration switches.
C: Relay configuration switches
The output status of each relay also depends on the configuration of
Positive/negative safety set by this switch block (Figure 18, C). Set the switch to
ON (positive safety) or OFF (negative safety) according to the safety type desired;
each switch acts on the relay having the same number (switch 1 acts on relay 1).
24
MX43
User manual
The contacts are represented in silkscreen as voltage-free, with no alarm in
positive safety.
For the 4-relay module, only switches 1 to 4 are active.
E – Programmable relays
In its maximum configuration, the MX43 can manage 24 external relays (or 24
modules with 1 stated relay or 3 modules of 8, all stated relays). The relays are
programmable indivisually. The operation of each relay depends on its
configuration.
Each of the 6 detector events [AL1 - AL2 - AL3 – High-range excess – Low-range
excess – Failure] can control one or several external or internal relays. Several
events can be connected to the same relay.
Setting of relay parameters
The alarm limits governing the relays can only be set by the COM43 application.
-
Normal: Relay operation as per the normal management of an alarm. (The
relay is launched only if the event exceeds the duration of time lapse).
-
Buzzer function (releasable relays): The same as in normal operation, with,
in addition, the release of the relay even if the event is still present. The time
lapses are:
.
Duration of maintenance: Minimum time of activation, adjustable from 0 to
900 seconds.
.
Automatic release: If activated, the time is adjustable between 15 and 900
seconds, beyond which the buzzer relay is automatically released.
.
Reactivation: If checked, time is adjustable between 15 and 900 seconds,
beyond which the buzzer relay is reactivated.
Controls of the alarm relay.
-
Logic equations of up to 4 levels of parentheses by the logic operators OR,
AND, NOR, and NAND. The result of the equation controls the relay.
-
Polling operations (x over y). There must be at least “x” events over the total of
“y” to activate the relay. Optionally, the user may define whether a failure is
considered an event in the same category as an alarm.
F – Relay status indicator
The status of each relay is visualized by a red LED (Figure 18, F):
■ LED off: Coil not powered.
■ LED lit: Coil powered.
G – Relay output connectors
The normal resistive load of each contact is 2A / 250 V AC or 2 A / 30 V DC.
Connection
Refer to chapter 6 on page 35.
Configuration
Configured via the COM 43 application.
6 – Digital Modules
25
16-Logic Input Module
Function
This digital module allows the
monitoring of 1 to 16 logic inputs by the
MX43.
In the 8-line version, the central unit
can manage a maximum of 32 logic
inputs distributed, for example, either
on 32 logic input modules with one
input declared per module, or on 2
modules with 16 logic inputs each.
In the 4-line version, the central unit
can manage a maximum of 16 logic
inputs.
Digital line
16 logic inputs
4 wires
Figure 19: Module with 16 logic inputs.
110
Introduction
Ref.
Description
A.
Module configuration switches (digital
address, delay, and end of line
resistor).
B.
Power supply and digital network
connector.
C.
Logic inputs 1 to 16.
104
Figure 20: Module of 16 logic inputs.
A – Module configuration switches
These switches are set according to the following table:
Term
Symbol
Slave number
Numéro esclave
See details in paragraph Module Address on page 26.
Frame filling
Remplissage de trame
Factory settings. Do not modify.
Delay
Temporisation
Factory settings. Do not modify.
E.O.L Resistor
Résistance F.D.L.
See details in paragraph End of line Resistor on page 27.
Table 7: Configuration switches of the Logic input module.
C –Logic input connectors
Each of these 16 inputs can be connected to a voltage-free contact as per Figure
35. Input status is transmitted by the digital line to the MX43. There is no alarm
when the contact is closed.
Connection
Refer to chapter 6 on page 35.
26
MX43
User manual
Configuration
Configured via the COM 43 application.
8-Analog Input Module
Function
This digital module enables the
monitoring of 8 analog (4-20 mA or
Wheatstone bridge) inputs.
8 analog inputs
Digital line
4 wires
Figure 21: 8-analog inputs.
122
Introduction
Ref..
Description
A.
Jumper of configuration 4-20mA or a
Wheatstone bridge.
B.
Sensitivity calibration.
C.
Zero calibration.
D.
Measuring point of each line.
E.
Reference 1.2 V for bridge calibration.
F.
Start/stop input switches not used,
always in ON position.
G.
Lug 0V for 4-20mA calibration.
H.
PCB configuration switches (digital
address, delay).
J.
Inputs no.1 to 8 (4-20mA or Wheatstone
bridge as per. A.
K.
Filament current calibration (factory
setting).
L.
4-20mA division strap in case of parallel
operation of several analog detectors on
the same line (application parking).
M.
Power supply
and digital network connector.
N.
End of line resistor jumper. (raised
position, EOL resistor connected).
120
Figure 22: Module of 8-analog inputs.
E – Module configuration switches
These switches are set according to the following table:
Term
Symbol
Slave number
Numéro esclave
See details in paragraph Module Address on page 26.
Frame filling
Remplissage de trame
Factory settings. Do not modify.
Delay
Temporisation
Factory settings. Do not modify.
E.O.L. Resistor
Résistance F.D.L.
See details in paragraph End of line Resistor on page 27.
Table 8: Analog input module configuration switches.
6 – Digital Modules
27
Connection
Refer to chapter 6 on page 35.
Configuration
Configured via the COM 43 application.
Note related to manual calibration of the detectors connected to an 8analog input module.
1. Zero calibration
Inject standard gas to obtain 4 mA. Place the multimeter between points E and D
(Figure 22). If the value measured is different from 0 V, adjust C.
2. Sensitivity calibration
After injecting the gas, place the multimeter between points E and D (Figure 22). If
the value measured is different from 1.6 V, adjust B.
Should the adjustment value be different, calculate:
V= I (mA) x 0.10 (V/mA)
Example: If the current is 12 mA, “V” must be equal to 0.8 V.
If the point E is not on the module use the G-spot and add 1.2V to the
measurement
4-Analog Output Module
Function
This digital module delivers 1 to 4
independent analog values (4-20 mA
outputs) opto-isolated from the values
given by the MX43, capable of being
independently activated or deactivated:
■ Activated: The 4-20mA signal varies
depending on the input.
■ Deactivated: The 4-20mA signal is
blocked at 0 mA, whatever the input
signal.
2 logic inputs
Digital line
4 wires
4 analog outputs
4-20 mA
Figure 23: Principle 4-analog output
module.
Several analog values may be associated to the same 4-20mA output
authorizing the management of minimums, maximums, or averages from a
group of detectors This module likewise has 2 logic inputs.
28
MX43
User manual
112
Introduction
Ref.
Description
A.
Connector for 2 logic inputs.
B.
Power supply and digital network
connector.
C.
Module configuration switches (digital
address, delay, and end of line
resistor).
D.
Push-button. Pressing this button
generates 20mA current in the output
of each line.
E.
(E1 to E4) opto-isolated independent
4-20mA analog outputs.
F.
(F1 to F4) 20mA calibration in line
output.
114
Figure 24: 4-analog output module.
A –Logic input connectors
Each of these two terminal jacks (Figure 24, A) may be connected to a voltagefree contact in accordance with Figure 38. Input status is transmitted by the digital
line to the MX43.
C – Module configuration switches
These switches are set according to the following table:
Term
Symbol
Slave number
Numéro esclave
See details in paragraph Module Address on page 26.
Frame filling
Remplissage de trame
Factory settings. Do not modify.
Delay
Temporisation
Factory settings. Do not modify.
E.O.L. Resistor
Résistance F.D.L.
See details in paragraph End of line Resistor on page 27.
Table 9: Analog output module configuration switches.
Connection
Refer to chapter 6 on page 35.
Configuration
Configured via the COM 43 application.
6 – Digital Modules
29
30
MX43
User manual
Chapter 6
І Wiring and Electrical
Connections
This chapter details the electrical connections of all the system components
(MX43, modules, additional equipment).
Central Unit Connection
The electrical connections must be carried out by qualified personnel in
compliance with the different directives in force in the country of installation.
The MX43 does not have a start/stop switch.
Certain voltage levels are capable of causing serious injuries or even
death. It is advised to install the material and cabling before applying
live voltage.
As an incorrect or poor installation may cause measurement errors
or system failures, it is necessary to strictly follow all the instructions
in this manual in order to guarantee the proper operation of the
system.
Access to terminal blocks
■ In wall-mounted version: After unblocking the two locks, swing the front cover
towards the left so as to reach the cabling terminal blocks (A).
■ In rack version: The terminal blocks are cabled from behind the central unit
(B).
056
Figure 25: Access in wall-mounted version (left) and rack-mounted version (right).
Sector Power Supply
The MX43 can be powered from a 110-240 V AC source at 50/60 Hz, 1.5 A max.
Check the nature of the current and the network voltage prior to any connection.
The electrical connections must be carried out with the equipment disconnected.
The MX43 must be protected upstream by a differential bipolar circuit breaker with
a type D response curve, size 4A. This cicuit breaker must be included in the
7 – Menus
31
electrical installation of the building, in the immediate proximity of the MX43, and
be easily accessible to operators. It shall be marked as the cut-off device of the
MX43.
The sector power shall be connected to the terminal block as indicated in Figure
26. The ground conductor shall be connected to the ground terminal (B).
058
Figure 26: Connection of sector power in wall mounted and rack versions.
External 24V DC Power Supply
The MX43 can be powered from a 22 to 28 V AC source at 50/3.2 A, 1.5 A max. In
this case, connect the 24VDC source to the corresponding terminal jack (Figure
26, A) respecting polarities. This jack is protected by Fuse F1.
060
Figure 27: Connection of 24VDC external power supply (A).
The main power supply charges the internal pack. The external 110-240 VAC, 24
VDC and battery pack sources can be used simultaneously, as there is internal
protection installed.
Integrated Backup Power Supply
The MX43 can be equipped with a 24-VDC NiMh battery pack that maintains
power to the central unit in the absence of the sector current or external 24VDC.
The batteries are charged by the mains supply (110-240 VAC).
The battery pack requires continuous charging for 7 days before reaching its
maximum capacity. Its autonomy depends on the MX43 configuration.
If the battery pack is not installed at delivery, proceed as follows:
1. Position and fix the battery pack (A) at the place indicated using the 4 screws
supplied.
2. Connect the battery pack connector to the connector (B) of the PCB. A failsafe
slot impedes any connection error.
062
Figure 28: Positioning the battery pack.
32
MX43
User manual
Earthing
The MX43 is intended to be used in the parts of installations corresponding to the
category of overvoltage II and pollution degree 2 as per EN/IEC 60947-1. In order
to comply with this category of protection, it is absolutely necessary to connect the
ground terminal.
(Figure 26. Grounding at site. Moreover, the cable braids of the digital lines shall also be
connected to this ground rod. (
Figure 29: Ground connection through the ground rod.
9 A).
064
Figure 29: Ground connection through the ground rod.
Digital lines
The cabling of the digital lines connecting the central unit to the different modules
deployed along the lines are the subject of the paragraphs OLCT1ON Modules, 4or 8-relay modules, 16-logic input modules, 8-analog input modules and 4-analog
output modules of this same chapter. It should be remembered that this cable
comes in 2 twisted pairs of 4 x 0.22 m² minimum, type MPI-22A, nominal
resistance of 120 Ohms.
Analog channels
For an analog 4-20mA detector connected directly on the MX43 channels, please
connect the detector like below.
I is the 4-20mA signal, 0 and 24V correspond to the power supply.
MX43
terminal
block for
channel
connexion
Figure 30 : 4-20mA detector connected directly on the MX43 channels.
7 – Menus
33
Please see below the figure for the motherboard with position for channel connexion
and relays.
Figure 30 : MX43 Motherboard.
Internal alarm relays
The MX43 has 6 relays of the following internal alarms:
Output
Function
R1
Relay of freely programmable function
R2
Relay of freely programmable function
R3
Relay of freely programmable function
R4
Relay of freely programmable function
R5
Relay of freely programmable function
Failure :
Non-programmable common relay in positive safety, activated upon the presence
(Default)
of a failure in the MX43 (detector and/or module, increased internal temperature,
transition to power supply from the backup battery pack, system anomaly, etc).
The deletion of this relay is automatic.
Table 10: Internal alarm relays.
34
MX43
User manual
The RCT dry contacts (nominal resistive load of 2 A at 250 VAC, and 2 A 30 V DC) of the 6
internal relays R1, R2, R3, R4, R5 and Default are deployed on the backplane board of MX43 on
the R1, R2, R3, R4, R5 and Default connectors (Figure 31: Internal alarm relay connectors (A).
).
066
Figure 31: Internal alarm relay connectors (A).
Connect the external equipment to the control on terminal jacks R1 to R5.
The relays are represented as disconnected. The position of the
contacts (no alarm) once the MX43 is powered will depend on the
purpose of the relay configuration (positive or negative safety).
The relays are programmed via the COM 43 application.
Remote Release Connector
If necessary, connect the RELEASE (dry contact NO) terminal to a remote release
system.
068
Figure 32: Remote release connection (A).
Flash and Siren Control Connector
This connector, powered at 24VDC by the MX43,
allows power supply for a rotating light and a siren
optionally available for the MX43 in wall-mounted
version. In the rack version, these connectors may
be taken over to power a sound alarm (24VDC,
19mA max.) and a visual alarm (24 VDC, 40 mA
max.). Ensure to match the polarities.
082
Figure 33: Flash and siren
connector (A).
070
Figure 34 : Location of the flash and siren connector (A).
7 – Menus
35
4- or 8-Relay Modules
Supervised contact
Supervised
contact
To MX43
or previous module
To next module
4- or 8-output contacts
RTC (250VAC or 30 V
DC – 2A)
102
Figure 35: 4- or 8-relay module connections
If this module is the last on the line, do not forget to set the switch
marked EOL resistor/resistance FDL to ON.
16-Logic Input Module
Supervised contacts
Supervised contact
To MX43
or previous module
To next module
106
Figure 36: 16-logic input module connections.
If this module is the last on the line, do not forget to set the switch
marked EOL resistor/resistance FDL to ON.
36
MX43
User manual
8-Analog Input Module
To MX43
or previous module
To next module
128
Figure 37: Connections of 8-analog input modules for 1 4-20mA detector with 3 wires
(explosive gas, toxicity detection).
30x
Wheatstone bridge type
detector
To MX43
or previous module
To next module
Figure 38: 8-analog input module connections for an explosive gas detection detector of the
Wheatstone Brdge CEX300 ou OLC type.
1
If this module is the last of the line, do not forget to set the jumper
marked EOL Resistor to Closed position.
4-Analog Output Module
Positioned contacts
Positioned contact
Output
4-20 mA n°1
Output
4-20 mA n°3
Output
4-20 mA no. 2
To MX43
or the previous module
Output
4-20 mA no. 4
To the next module
118
Figure 40: 4 Analog output module connections.
If this module is the last of the line, do not forget to set the jumper
switch marked EOL Resistor/FDL resistance to the ON position.
7 – Menus
37
Chapter 7 І Menus
General Menu Tree
The following figure shows the general tree of the group of menus.
See page 44
↓
See page 46
↓
↓
↓
↓
↓
1 SYSTEM
2 PROGRAM
3 CALIBRATION
4 MAINTENANCE
5 INFORMATION
See page 46
See page 47
See page 48
See page 50
See page 50
ECR_90_91_92_93_94
Figure 41: General menu tree of the MX43.
Navigation Key Functions
Key
Function
Vertical displacement in the selected menu block.

Horizontal displacement between two menu blocks.
Enter
Validation of the selected line.
Escape
Return to previous screen.
Table 11: Function of the navigation keys.
Display in normal mode
Measurement Display
A B
G.
C. D
H.
J.
E
F.
K.
ECR_06_08
Figure 42: Example of the measurement display in normal mode and in inverse video.
38
MX43
User manual
Ref.
Significance
A.
Barograph with an indication of alarm limits.
B.
Measurement range, gas detected, and detector language.
C.
Value of the current measurement with the unit and gas detected.
D.
Value of the average measurement if the programming was carried out via
the COM 43 application.
E.
Indicator of measurement
trend
Ascending tendency
Descending tendency
F.
Address of digital detector on a digital line or channel number for a analog
detector
G.
Function keys.
■ Previous detector: Display of measurements of previous detector;
scanning of all the detectors on all the lines.
■ Next detector: Display of measurements of next detector; scanning of
all the detectors on all the lines.
■ Menu: Display of main menu See paragraph "Main menu" on page 46.
■ See 4 Detectors: Display of a group of 4 detectors (detector tag,
barograph with indication of alarms, value of current measurement with
unit and gas detected). Use the Page down or Page up keys to display
all of the next 4 detectors; passage to the next zone is automatic.
■ See 8 Detectors: Display of a group of 8 detectors (detector tag, value
of current measurement with unit and gas detected). Other buttons
similar to the selection. See 4 detectors.
■ See 16 Detectors: Display of a group of 16 detectors ( detector tag,
value of current measurement with unit and gas detected). Other buttons
similar to the selection. See 4 detectors.
■ See 1 detector: Display in normal mode (Figure 40).
■ Curve: Display of the measurement curves of the last 4 hours (Figure
41). The and  keys allow cursor displacement through the time
scale. The vertical dotted line displays the concentration and time stamp
of the point being considered. Escape: return to display of values.
H.
Information on the detector status.
J.
Information on the MX43 status.
K.
Zone of indication of activated alarms with blinking threshold display. The
screen changes to inverse video (Figure 40, screen on the right).
ECR_10
Figure 39: Example of a curve display screen.
7 – Menus
39
Main Menu
This displays all the management menus of MX43.
ECR_12
Figure 40: Main menu.
System
■
System Info
■ Passwords
Displays the version of the program, the bootloader
(internal micro-software for loading the program), and
the configuration, as well as software application
verifications.
The central unit is protected by two access codes,
both set at 1000 by default upon leaving the factory.
You can change the passwords in this menu via
COM43. The passwords are required each time you
enter one of the menus that they protect.
First-level password: Authorizes access to the
Calibration menu.
Second–level password: Authorizes access to the
Programming, Calibration, and Maintenance menus.
This password is also required before menu data are
deleted.
40
MX43
User manual
■ Date and time
Time stamp settings (year, month, day, hour, minute,
second).
■ Display settings
Static: Display frozen on a selected detector.
Cyclic: Examines each of the detectors connected
every 2 seconds.
With screensaver: Displays screensaver (logo) after a
period of inactivity without key movement.
Without screensaver: Displays the measurements
continuously.
■ Language
Selection of the display menu language.
Program
■ Buzzer On/Off
Activates or deactivates the internal buzzer of the
MX43.
■ Tag set
Allows for the modification of detector tags previously
programmed via COM43.
■ Alarm settings
Allows for the modification of detector alarms
previously programmed via COM43.
Calibration
If the measurement cell has changed, it is important to declare this
through a menu no. 5 Cell change.
1. Detector select.
This menu enables the selection of detectors to be calibrated (calibration from
MX43 or on the detector).
A.
Display of information described by the COM 43 application: i.e.,
measurement range, gas detected, current detector ID and its type.
B.
Display for the current detector:
■ Last passed calibration: Date and time of the last calibration
carried out and completed.
■ Last sensor replacement : Date and time of last cell change.
■ Wear rate : Relation between the value of the standard gas and the
value read (sensitivity measurement). A wear rate in excess of 100%
entails a sensor replacement.
C.
Display of the address (digital detector) or line number (analog detector)
to which the detector is connected.
D.
Selecting the detectors to be calibrated:
■ Select one or several detectors using the previous detector or next
detector keys.
■ On pressing the Select key, press Cal gas to enter its value by
means of the ↑↓ keys. Validate by pressing Enter.
Note: Only analog detectors that are not equipped with a local
display can be calibrated from the MX43 central unit. For the
other detectors, the menu “Sel. Detector” only makes it possible
to put them in calibration mode so that they do not activate
alarms during their manual calibration.
■ Press Escape to launch the procedure of recording the
measurements on the detectors to be calibrated. Proceed to
paragraph “2 Recording”.
E.
Display the calibration gas.
7 – Menus
41
A.
B.
D.
C.
E.
ECR_14
Figure 41: Example of the “Select detectors” screen.
2 Start Recording
■ Yes: Launches the recording of calibration measurements for the selected
detectors. From this moment onwards, all the calibration measurements are
recorded for these detectors. “Start recording” is then displayed. The
calibration of the detectors with the help of the standard gas can begin.
For a detector in which the cell has been changed, it is important to adjust the
detector locally to obtain a 4-20mA output corresponding to the detector range.
For detectors connected to the analog input module, perform the
adjustments directly on the module (cf page 28).
Attention: During calibration, the standard gas must be injected for at least
thirty seconds.
■ No: Exits the recording procedure.
3. Stop recording
■ Yes: Detector calibration having finished, this validates the end of calibration
measurement recording for the detectors previously selected. From this
moment onward, no calibration measurement is recorded. “Stop recording” is
then displayed.
■ No: Exits the end of the recording procedure.
4 Validation
This allows the adjustment and validation of zero and detector sensitivity once
calibration is completed.
ECR_22_24
Figure 42: Adjustment of zero (left) and sensitivity (right).
42
MX43
User manual
Operating mode
Detector selection
1. Select the detector to be calibrated with the help of the Previous detector and
Next detector keys and press Validate.
Zero calibration
1. The Zoom command is active.
2. Select the area of interest of the curve with the  and keys. Press Zoom +
up to the activation of the Zero command. Adjust the position of the cursor so
as to make the “OK” appear, in turn indicating that the range selected is
sufficiently stable.
3. Press to select the term Zero.
4. Confirm the zero calibration by pressing Validate zero.
5. The term Sens (for sensitivity) is active from now on.
If sensitivity is not to be calibrated, press and END; to the message “Do you
only want to calibrate zero for the detector?”, press Validate calibration. Only
the zero calibration of the detector will have been carried out.
If sensitivity is to be calibrated, proceed directly to the following paragraph.
Sensitivity calibration
1. The Sens command is active.
2. Select the area of interest of the curve with the  and keys. Press Zoom +
up to the activation of the command Sens. If applicable, adjust the position of
the cursor so as to make the “OK” appear, in turn indicating that the range that
has been selected is sufficiently stable.
3. Confirm the sensitivity calibration by pressing Validate Sens.
Record the calibration
1. The message “Do you want to validate zero and detector sensitivity?” is
displayed. Press Validate calibration to confirm the adjustment of zero and
sensitivity or Esc to exit the procedure.
2. The detector is calibrated.
5 Sensor exchange
This function reboots the parameters (rate of wear, calibration date, internal
parameters corresponding to the 4-20mA range, etc.) from the selected
detector(s) following or in view of a change of cell.
Detector Selection
1. Select the detector(s) to be rebooted with the help of the Previous detector,
and Next detector keys and press Selec.
Detector Rebooting
1. Press Escape to launch the reboot of the selected cells.
2. Proceed next to the changing of the cell and then to a calibration of the
corresponding detectors via the menus “1 Sel detectors”, “2 recording”, "End
recording” and “4 validation”.
7 – Menus
43
Maintenance
Access
Successively press the keys Menus and Maintenance.
1 Line On/Off
Sets the line to stop (the line is not powered and the detectors are at stop; no
event can be generated from then on).
2 Detector On/Off
Sets the detector to stop (no event can be generated from then on) if it was not
issuing an alarm or failure.
3 Test On/Off
Allows for the verification of the proper operation of a detector. In this mode,
recordings and alarm relays are suppressed.
4 Simulation
Upon its selection, the message “The central unit no longer ensures detection” is
displayed.
□ The central unit no longer keeps account of inputs (detectors, logic inputs).
□ The simulation measurements/status are initialized to the current
measurement/status values. The relays, the internal buzzer, and the analog
outputs remain in their current status.
□ The screens, management of relays, outputs, etc. are those of Normal
operation.
□ The internal relay and the common default LED are activated.
□ To change the value of a detector, use the keys to increase or decrease
the measurement value simulated from –15% to 115%. For a logic input, use
the  keys to select the input, to select Alarm or Alarm Off.
□ The banner of alarms does not appear.
□ The events log indicates Begin Simulation and End Simulation.
□ Exit the simulation mode by pressing the End simul key. Automatic release
then occurs and resets the average values to zero. The current measurements
are displayed once more.
Information
1 Detectors
This displays the main information on the detector (type, range, detected gas).
44
MX43
User manual
2. Events
1. Alarm events
This displays, for each of the detectors concerned: detector ID, alarm type (Al1, Al2,
Al3, Al1mean, Al2mean, Al3mean, OVS), status (activated = ON or deactivated =
OFF) as well as the date and time of occurrence or of the release.
The letter “S” appears on the line if the events were obtained when the MX43 was in
simulation mode
Delete deletes all the data. Up to 512 events can be memorized. Beyond that, the
most recent event deletes the oldest.
Previous page, Next page, and Last page access the corresponding pages of
the file.
ECR_20
Figure 43: Example of gas alarm files.
Message
Significance
AL1
Detector in level 1 alarm
AL2
Detector in level 2 alarm
AL3
Detector in level 3 alarm
OVS
Detector in OVS alarm
AL1 M
Detector in alarm set to level 1 mean value
AL2 M
Detector in alarm set to level 2 mean value
AL3 M
Detector in alarm set to level 3 mean value
Table 12: Gas alarm file messages.
2. Fault records
This displays, for each detector concerned: event type (UDS = Under-scale),
RANGE = measurement out of range, DEF =Failure, DOUBT = clear doubt),
status (activated = ON or deactivated = OFF) as well as the date and time of
appearance or release. This file cannot be deleted.
Message
Significance
UDS
The measurement is lower or equal to the value of the UDS programmed.
DEF
Detector failure (out of range, line cut, defective cell, etc.)
RANGE
Measurement out of range.
>> LEL
Concentaration higher than 100% of LEL.
Table 13: Failure file messages.
7 – Menus
45
3. Inputs and relays records
This displays, for each relay and logic input concerned: activated relay/input ID,
type (REL = relay, EL = Logic input), its status (activated = ON, Deactivated =
OFF) as well as the date and time of occurrence or release.
Delete allows for the deletion of this entire file. Up to 512 events can be
memorized. Beyond that, the most recent event deletes the oldest.
Previous page, Next page, and Last page access the corresponding pages of
the file.
Message
Significance
RELAY
Status change of the designated relay.
INPUT
Status change of the designated input.
Table 14: Relay and logic input file messages.
4. Working conditions records
This displays the actions carried out on the MX43 (simulation mode, calibration
mode, programming mode, release request, operation on internal battery), as well
as the date and time of beginning and end of the event.
Delete allows for the deletion of this entire monitoring file. Up to 512 events can
be memorized. Beyond that, the the most recent event deletes the oldest.
Previous page, Next page, and Last page allow access to the corresponding
pages of the file; each page can display a maximum of 8 lines.
Message
Significance
Lines On/Off
Start or stop the line
Detectors On/Off
Start or stop the detector
External ack
Press the external acknowledgement button
MX43 ack
Acknowledgement by the acknowledgement button on the front face of
MX43
Simulation
Switch to simulation mode
Calibration
At least one of the detectors is selected in calibration mode.
Test detectors
Switch to test mode
Program
Programming done on MX43
Time settings
Time settings on MX43
Line 1 On/Off
Start or stop line 1
Line 2 On/Off
Start or stop line 2
Line 3 On/Off
Start or stop line 3
Line 4 On/Off
Start or stop line 4
Line 5 On/Off
Start or stop line 5
Line 6 On/Off
Start or stop line 6
Line 7 On/Off
Start or stop line 7
Line 8 On/Off
Start or stop line 8
Table 15: Operation monitoring file messages.
5. Hardware troubles records
This displays, for each material incident detected: incident ID, status (activated =
ON or deactivated = OFF) as well as the date and time of occurrence or release of
the event.
46
MX43
User manual
Previous page, Next page, and Last page allow access to the corresponding
pages of the file: each page can display a maximum of 8 lines.
Message
Significance
DEAD
Digital module no longer responding (line cut, module failure, wrong address,
module absent).
MODUL
Configuration or module address error.
TEMP+
Internal temperature of the MX43 higher than maximum tolerated value.
TEMP-
Internal temperature of the MX43 lower than maximum tolerated value.
BAT
Switching to external power supply.
LINE 1
Incident on line 1 (short-circuit).
LINE 2
Incident on line 2 (short-circuit).
LINE3
Incident on line 3 (short-circuit)
LINE4
Incident on line 4 (short-circuit).
LINE 5
Incident on line 5 (short-circuit).
LINE 6
Incident on line 6 (short-circuit).
LINE7
Incident on line 7 (short-circuit).
LINE 8
Incident on line 8 (short-circuit).
CAL O
Calibration defect (zero shifted).
CAL S
Calibration defect (used cell).
CAL F
Calibration defect (cell oversensitive).
CAL D
Calibration defect (measurement unstable).
Table 16: Material incidents file messages.
6. System troubles records
This displays the events relative to MX43 operation (power failure/fluctuation,
On/Off, etc.).
Previous page, Next page, and Last page allow access to the corresponding
pages of the file; each page can display a maximum of 8 lines.
Message
Significance
ON
MX43 on live voltage
OFF
MX43 off voltage
Self-testing failure
Failure of internal tests
Other messages
Contact Post-Sales Service
Table 17: System incidents file messages.
3. Slave info
These data enable maintenance technicians to visualize the communication
framework between MX43 and the digital modules.
4. Controller info
These data allow technicians to visualize MX43 counters set to zero since the last
zero setting.
7 – Menus
47
Chapter 8
І Main Part number
Description
Reference
MX43 4-line central unit, wall-mounted version
6 514 886
MX43 8-line central unit, wall-mounted version
6 514 884
MX43 8-line central unit, rack version
6 514 885
Module with 8 analog inputs
6 314 061
Module with 8 analog inputs for Wheatstone bridge or
4-20mA detector
6 314 063
4-analog input PCB
6 314 085
Module with 4 analog outputs
6 313 980
Module with 16 logic inputs
6 313 964
Battery pack
6 311 104
Image
8 – Principal References
48
Description
Reference
4-relay module
6 313 962
8-relay module
6 313 963
Flash and buzzer kit
6 314 066
Image
11 – Index
49
Chapter 9
І Certificate of Compliance
10 - Index
50
Chapter 10 І Technical Specifications
MX43 Central Unit
Function
Function:
Central measurement unit with multiple-channel
alarm.
Number of lines:
4 or 8 as per model.
Display and indicators
Display:
Back-lit graphic LCD
Status indicators:
- 7 LEDs for each of the 8 lines, or 56 LEDs.
- 1 live voltage indicator for the central unit.
- 1 general failure indicator.
Keys
Selection:
5 multifunction soft-touch keys.
Alarm release:
Dedicated soft-touch key.
Alarms
Limits:
Parameter setting by COM43 application.
Indicators:
6 status LEDs per line (high- and low-range
excess, Alarm 3, Alarm 2, Alarm 1, failure).
Internal relay:
- 5 completely programmable relays
(configuration in positive safety or normal mode
over COM43).
- 1 failure relay (non-modifiable).
- RCT contact on each relay. Nominal load of
contacts: 250 V AC – 2A or 30 V DC – 2 A,
resistive load.
- Output at screwed terminals Maximum
admissible cable diameter 2.5 mm².
Measurement Lines
Digital lines:
- 8 maximum.
- RS485 Modbus, 9600 Bauds.
- Industrial computer cable, 2 shielded twisted
pairs (1 for the line and 1 for communication),
adapted to 120 Ohms.
Analog lines:
-
Nominal voltage:
21 to 28 V on external DC.
Maximum current
available per line:
500 mA.
8 maximum.
Input range 4 to 20 mA.
Load resistance 120 Ohms.
Analog transmitter cable 2 or 3 shielded wires.
11 – Index
51
Total maximum current
for lines:
2.4 A CC or 3.2 A per peak.
Total power available as
per temperature:
Room
Room
Room
Room
Cables outputs:
(only for wall-mounted version)
■ 12 PE M16 for cables of 4 to 8 mm².
■ 6 PE M20 for cables of 6 to 12 mm².
Insulation:
1500 V AC (power–digital network).
Output
On screwed terminals. Maximum admissible
conductor section 2.5 mm².
T° ≤ 20°C = 68 W.
T° 20 to 30°C = 55 W.
T° 30 to 40°C = 41 W.
T° 40 to 50°C = 27 W.
Electrical characteristics
AC power supply:
■ 100 to 240 V AC, 50/60 Hz.
■ Maximum input current 1.5 A.
■ Maximum consumption: 230 VA.
DC power supply:
■ 21 to 28 V DC.
■ Maximum input current 3.2 A.
■ Maximum consumption: 112 VA.
Mechanical characteristics
Installation:
■ Wall-mounted version: on special screwed
support.
■ Rack version: Cut-out of 177 x 437 mm.
Dimensions:
■ Wall-mounted version: 370 x 299 x 109 mm.
■ Rack version: 482.8 x 177 x 192.5 mm (19’’,
4 U).
See Figure 4 and Figure 6.
Weight:
■ Wall-mounted version: 4.0 kg.
■ Rack version: 2.0 kg.
Protection level:
■ Wall-mounted version: IP55.
■ Rack version: IP 31.
Locking:
■ Wall-mounted version: by 2 locks with a key.
■ Rack version: none.
Environmental characteristics
Conditions of use
Temperature of use:
-20 to +50°C. (as per power used; cf. preceding
page).
Storage temperature:
-20 to +50°C.
Humidity:
5 to 95% relative humidity.
Standards
52
MX43
User manual
Electromagnetic
compatibility:
as per EN50270, industrial type 2.
ATEX:
60079-29-1 and EN50271 (current).
Low voltage directive:
as per EN61010.
CSA:
as per C22.2 no.152 (current).
Relay Module
Function
Function
Management of 4 or 8 relays from the digital
signals issued by the MX43.
Number of relays:
■ 4 or 8 relays.
■ CRT outputs
Relay type:
■ Bistable.
■ Configuration in positive or negative safety by
mini-switches.
■ Setting of relay parameters by COM43
application.
Nominal load of contacts:
250 V AC – 2 A or 30 V DC – 2A, resistive load.
Consumption:
3.5 mA in normal.operation.
Connections:
■ Screwed terminals.
■ Connector detachable without cutting the line.
■ Tightening torque: 0.5-0.6 Nm.
■ Cable: 2.5 mm² maximum.
Logic inputs:
2 additional logic inputs (dry contacts).
Assembly:
Snap-on on DIN rail.
Dimensions:
125 x 165 x 60 mm.
16-Logic Input Module
Function
Function
Logic input monitoring.
Capacity:
1 to 16 logic inputs (dry contacts).
Connections:
■ Screwed terminals.
■ Connector detachable without cutting the line
■ Tightening torque: 0.5-0.6 Nm.
■ Cable: 2.5 mm² maximum.
Consumption:
2 mA in normal operation.
Assembly:
Snap-on on DIN rail.
Dimensions:
125 x 165 x 60 mm.
8-Analog Input Module
Function
Function:
4-20mA detector or Wheatstone bridge
connections.
Capacity:
1 to 8 independent inputs.
11 – Index
53
Connections:
■ Screwed terminals.
■ Connector detachable without cutting the line.
■ Tightening torque: 0.5-0.6 Nm.
■ Cable: 2.5 mm² maximum.
Consumption:
53 mA max (detector excluded).
Operating temperature:
8 bridges
- 30°C (8 bridges
- 40°C (8 bridges
4 bridges
- 45°C (4 bridges
- 50°C (4 bridges
up to 1 km).
up to 500 m).
up to 1 km).
up to 500 m).
Assembly:
Snap-on on DIN rail or mounted on the inside of
MX43.
Dimensions:
125 x 165 x 60 mm.
4-Analog Output Module
Function
54
MX43
User manual
Function:
Generation of 1 to 4 analog values.
Capacity:
■ 4 independent opto-isolated outputs 4-20mA
(recopy detector, minimum, maximum, or
average of a detector group).
■ Resistance of maximum load 500 Ω.
Logic inputs:
2 additional logic inputs (dry contacts).
Connections:
■ Screwed terminals.
■ Connector detachable without cutting the line
■ Tightening torque: 0.5-0.6 Nm.
■ Cable: 2.5 mm² maximum.
Consumption:
■ < 5 mA with the 4 lines at stop.
■ < 36 mA for an activated line.
■ < 130 mA for the 4 activated lines.
Assembly:
Snap-on on DIN rail.
Dimensions:
125 x 165 x 60 mm.
Chapter 11
І Index
A
Alarm
Automatic deletion of alarms, 18
Manual deletion of alarms, 19
Clear doubt, 18
OVS, 18
Reset, 17
Limits, 18
UDS, 18
B
Battery pack, 32
C
Clear doubt, 18
Contextual Keys, 19
COM43, 5
General information, 5
CR2032, 14
D
Defect
Indicator, 17
Digital address module, 22
F
Flash, 17
Front face MX43, 15
G
General Introduction, 3
General Menu Tree, 39
E
Earthing
MX43, 33
End of line, 23
Electrical connections
Module with 16 logic inputs, 35
4-relay Module, 35
Module with 4 analog outputs, 37
Module with 8 analog inputs, 36
8-relay Module, 35
MX43, 31
End of line Resistor, 27
External Power Supply 24 V DC, 32
I
Indicators, 17
Integrated Backup Power Supply, 32
L
LCD, 15
Liability Limits, 2
Lithium battery, 14
Localization, 7
M
Maintenance
Indicator, 17
Mechanical Installation, 7
Menu
General tree, 39
Calibration, 42
Information, 45
Maintenance, 44
Main Menu, 41
Programming, 42
System, 41
Menus
Navigation keys, 39
Module with 16 analog inputs
Caracteristics, 54
Introduction, 26
Electrical connections, 35
4-relay Module
Electrical connection, 35
Module with 4 analog outputs
Introduction, 28
Electrical connections, 37
Module with 8 analogic inputs
Caracteristics, 54
Introduction, 27
Electrical connections, 36
8-relay Module
Electrical connections, 35
Module with 8 analog outputs
Caracteristics, 55
N
Navigation Key Functions, 44
P
Programming switch, 14
R
Remote Release, 39
References, 49
Relay Module
Introduction, 24
RS485 (topology), 26
S
Safety instructions, 2
Sector Power Supply, 31
Detector module
Fixation, 9
Localization, 9
Siren, 16
T
Technical specifications, 51
The MX43 Central unit
General information, 5
11 – Index
55

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement