Manning VL-F7-N4 LPA-MK Vent Line Sensor Instruction and Installation Manual

The Manning VL-F7-N4 LPA-MK Vent Line Sensor is designed to detect ammonia and other refrigerants in vent lines for refrigeration systems. The sensor features a solid-state sensor imbedded in a 2" forged steel bull plug and transmits a linear 4/20 mA signal to readout equipment. This manual provides instructions for installing and operating the sensor for safe and reliable performance.

PDF Download
Document
Manning VL-F7-N4 LPA-MK Vent Line Sensor Instruction and Installation Manual | Manualzz

Advertisement

Advertisement

Advertisement

Key Features

  • Solid-state sensor
  • Linear 4/20 mA output
  • NEMA 4 enclosure
  • Broad-spectrum detection
  • Long life (5-8 years)
  • Optional compressed air purge
  • Easy-to-use calibration
  • LED fault indicator
  • 24 VDC power requirements

Frequently Answers and Questions

How do I properly mount the sensor?

The sensor should be mounted no more than 1 to 2 feet from the discharge point in the vent line. Make sure that the discharge does not hit the sensor housing, and provide a means of inducing a draft through the vent header to remove residual refrigerant after a leak.

What are the start-up procedures for the sensor?

After power-up, allow 24 hours for the system to stabilize before testing the sensors. You can then expose each sensor to a small amount of the gas that is being monitored to verify that it is connected to the proper input and responds appropriately.

What is the recommended trip point level for the sensor?

The recommended trip point level is approximately 17 mA. Lower setpoints can result in false trips, and alarm points should never be set higher than 20 mA.

What are some troubleshooting tips if the sensor output is 0 mA?

First, verify the +24 VDC power supply and check for any loose or reversed wiring connections. Second, check the signal voltage between Test- and Test+. If the voltage is 0 mV, there is no path to ground, so check the monitoring equipment connections and configuration.

How do I calibrate the sensor?

The sensor is factory calibrated and normally does not need to be spanned. If span adjustment is required, apply span gas at 0.8 L/min and adjust the span pot until the correct output is achieved.

What maintenance is required for the sensor?

Manning Systems recommends testing each sensor with a gas sample once every six months. Also, the signal being sent by the sensor should be logged on a monthly basis.

What are some common causes for sensor failure?

The most common reasons for failure are improper mounting, exposure to excessive gas concentrations, and improper wiring or monitor configuration.

Where can I find replacement parts for the sensor?

Contact Manning Systems, Inc. and provide the serial number of the unit.
Preparing document for printing…
0%