Festo CPX is a versatile and powerful terminal that offers a wide range of features and benefits. With its modular design, it can be easily customized to meet your specific needs. The CPX can be used to control pneumatic-electric actuators, interrogate sensors, and more. It is also designed to withstand vibration, shock, and continuous shock, making it ideal for use in demanding industrial environments.
advertisement
Assembly instructions (original: de)
8031389
1401NH
[8031391]
Terminal CPX / Valve terminal VTSA
CPX, CPX-M, VTSA, VTSA-F
†‡
Festo SE & Co. KG
Postfach
73726 Esslingen
Germany
+49 711 347-0 www.festo.com
1. Safety instructions and notes on mounting .............................................. 1
2. Parts list ................................................................................................... 2
3. Explanations of terms .............................................................................. 2
4. Intended use ............................................................................................ 2
5. Wall mounting .......................................................................................... 3
5a. Check positions of the mountings ....................................................... 3
5b. Assemble mountings ........................................................................... 3
5c. Overview of the mounting points ......................................................... 4
5d. Mount VTSA/VTSA-F-modules (65 mm) ............................................... 5
6. Mounting system assembly ..................................................................... 6
6a. Check positions of the mountings ....................................................... 6
6b. Assemble mountings ........................................................................... 6
6c. Mount CPX-terminal to the mounting system ....................................... 6
7. H-rail mounting ........................................................................................ 7
7a. Mount H-rail ........................................................................................ 7
7b. Mount CPX-terminal to H-rail ............................................................... 7
1)
2)
1)
SL1 = Severity level 1
SL2 = Severity level 2
2)
CPX terminals 1 with 1 … 3 VTSA/VTSA-F-modules a maximum of one vertical stacking component per VTSA/VTSA-F-module.
CPX terminals 1 with 4 … 5 VTSA/VTSA-F-modules a maximum of one vertical stacking component on the VTSA/VTSA-F-valve terminal.
CPX terminals 1 with more than 5 VTSA/VTSA-F-modules and at least one vertical stacking on the VTSA/VTSA-F-valve terminal no mounting system assembly permitted.
1. Safety instructions and notes on mounting
Warning
Electric voltage.
Injury (death) due to electric shock.
Switch off power supply before assembly work.
Caution
Unexpected movement of components.
Injury due to electric shock, impact, squeezing.
Switch off compressed air before assembly work.
Note
Electrostatic charge.
Damage to the internal electronics.
Electrostatically discharge assembly personnel prior to assembly work.
Note
Malfunction due to incorrect earthing.
Earth in accordance with regulations
CPX-system description: Potential equalisation.
Note
Malfunction and material damage due to incorrect assembly.
Plan sufficient space:
– permit heat dissipation through air circulation
CPX-system description
VTSA/VTSA-F-description of pneumatics.
– permit access to the connections.
Requirements of the mounting surface:
– torsion-free operation of the product
– acceptance of the weight and other forces that occur.
Observe assembly conditions ( following tables).
Assembly
CPX-modules (plastic)
CPX-modules (metal) and
VTSA/VTSA-F-modules
(18 … 52 mm)
VTSA/VTSA-F-modules (65 mm)
√
√
√ system
−
√
−
H-rail
√
√
−
Resistance to vibration/ resistance to shock in accordance with
EN 60068
Wall
Vibration
Shock
Continuous shock Part 2-27 SL1
Mounting system
H-rail
SL1 SL2
2)
−
SL1 SL2
2)
−
Vibration load
Frequency range
SL1 SL2
[Hz] Acceleration
SL1
2 … 8
8 … 27
27 … 58
58 … 160
2 … 8
8 … 27
27 … 60
60 … 160
−
10
−
20
160 … 200 160 … 200 10
SL2
−
10
−
50
10
[m/s 2 ] Displacement
SL1 SL2
−
−
−
−
−
−
[mm]
Shock load
Acceleration
SL1 SL2
±150 ±300
[m/s 2 ] Duration
SL1
11
Continuous shock load
Acceleration [m/s 2 ] Duration
±150 6
SL2
11
[ms] Shocks per direction
[ms]
SL1
5
SL2
5
Shocks per direction
1000
1
18373d_1
18373d_2
18373d_3
18373d_5
18373d_4
2.
Parts list
1
1 Terminal
CPX
with
VTSA/VTSA-F
(1x)
9
H-rail mounting
Not included in delivery:
9 H-rail
(EN 60715 - 35x7.5 or
35x15)
(1x)
2
3
4
Wall mounting
CPX-modules (plastic):
2 Mounting
...
CPX-modules (metal):
3 Mounting
CPX-M-BG-RW-...
4 Screw
(thread-cutting)
5
6
7
8
VTSA/VTSA-F-modules:
5 Mounting
VAME-S6-W-M46
6 Screw
Mounting system assembly
CPX-modules (metal):
7 Mounting
CPX-M-BG-VT-2X
8 Screw
(thread-cutting)
18373d_6 aJ
Mounting
CPX-CPA-BG-NRH: aA aJ Clamping aA Screw
(3x)
(3x)
18373d_7
3.
Explanations of terms
1.
The CPX-terminal with VTSA/VTSA-F-valve terminal 1 is designated in these assembly instructions as CPX-terminal 1 .
2.
The widths of the VTSA/VTSA-F-modules are designated in these assembly instructions as (18 … 52 mm) and (65 mm).
4.
Intended use
Product Usage
CPX-terminal 1 Control of pneumatic-electric actuators.
Interrogation of the sensors.
Mounting 2 / 3 / 5 Additional wall mounting of the CPX-terminal 1 .
Mounting 7 Mounting of the CPX-terminal 1 to the mounting system.
2
5.
Wall mounting
In case of loads from vibration, shock or continuous shock with severity level 1 ( tables in section 1), the mountings 5 are not required.
5a.
Check positions of the mountings
Information
Information
5b.
Assemble mountings
Mounting 2 to CPX-modules (plastic)
2
A
Press mounting 2 inclined into the modules (A).
Tilt mounting 2 until it catches.
Assemble additional mounting 2 opposite.
U V
Counting direction of the modules:
CPX:
– from end plate (U).
VTSA/VTSA-F (18 ... 52 mm):
– from pneumatic interface (V).
18375d_34
Information
Mountings are pre-assembled, dependent on the configuration.
Directly fasten VTSA/VTSA-F-modules (65 mm) ( section 5d).
Check positions of the pre-assembled mountings ( tables) and correct, if required ( section 5b).
Mounting 2 with CPX-modules (plastic)
Number of modules Mounting between the modules
2
18375d_4
Mounting 3 to CPX-modules (metal)
Information
For CPX-modules (metal) without system supply, the mounting 3 can be assembled on both sides of the module.
4
Place mounting 3 aligned
3
1.5 Nm ± 10 % with the module (B).
Tighten screws 4 . If you screw it in again, use the threads already present.
B
Observe tightening torque.
1 … 3
4 … 5
6 … 8
−
•
• •
• • • 9 … 10
Mounting 3 for CPX-modules (metal)
Number of modules Mounting to the modules
2 3 4 6 7
1 … 3
4
5 … 6
−
•
•
• 7
8
9 … 10
• •
• •
Mounting 5 at VTSA/VTSA-F-modules (18 … 52 mm)
Number of modules Mounting to the modules
1 … 2
3 … 5
6 … 8
9 … 12
13 … 16
17 … 20
, 20
•
•
•
• •
• • •
• • • •
Mounting 5 to every 4th module
3)
.
18375d_14
Mounting 5 at VTSA/VTSA-F-modules (18 … 52 mm)
6
Place mounting 5 on the
3 Nm ± 20 % module (C).
Tighten screw 6 . Observe
5 the tightening torque.
C
18376d_4
3)
No additional mounting is required at a module directly next to the right end plate. Mounting via the end plate is sufficient.
3
5c.
Overview of the mounting points
Note
Material damage due to incorrect assembly.
Select screws suitable for the installation situation.
CPX-terminal (plastic) with VTSA/VTSA-F-valve terminal (18 … 52 mm)
E 2 F G 5
D
D
H
H
18373d_32
Mounting point
E F
Screw size Number
(D) M6 2x
CPX-terminal (plastic) with VTSA/VTSA-F-valve terminal (65 mm)
D E 2 F G 5
N
E F J M
N
Mounting point Screw size Number
(D) M6 2x
(F) M6 2x (F) M6 2x
(H) M6 2x
CPX-terminal (metal) with VTSA/VTSA-F-valve terminal (18 … 52 mm)
K 3 F 5 L
D H
D
H
F
18373d_42
Mounting point Screw size Number
(D) M6 2x
(J) M8 1x
(M) M8 section 5d
(N) M8 2x
CPX-terminal (metal) with VTSA/VTSA-F-valve terminal (65 mm)
D K 3
F
F 5 L
J M
N
N
Mounting point Screw size Number
(D) M6 2x
(F) M6 2x (F) M6 2x
(H) M6 2x (J) M8 1x
(M) M8 section 5d
(N) M8 2x
4
5d.
Mount VTSA/VTSA-F-modules (65 mm)
Information
Counting direction of the modules:
VTSA/VTSA-F (65 mm):
– from adapter plate (W).
Alternative mounting
M
18373d_60
W
Determine mounting points (M) ( table).
Mounting to VTSA/VTSA-F-modules (65 mm)
Number of modules Mounting with M8 screw to the modules
2 3 6 9
1 … 2
3
4 … 6
7 … 9
10 … 12
, 12
−
•
•
• •
• • •
Mounting to every 3rd module 4) .
Information
If the mounting point (M) is covered:
Remove module components.
Fasten CPX-terminal 1 to the wall.
Remount removed components.
Dismantling
Remove components until the mounting point (M) is freely accessible.
Assembly
1837 osr6
M
As an alternative to the mounting point (M), there is the option to fasten to the blind hole (X) on the reverse side of the modules.
Determine mounting points
( table).
Cut M8 thread into the blind holes (X).
Use M8 thread for mounting.
Mount components.
Observe tightening torques.
Check: Status and correct position of the seals.
3 Nm ± 20 %
3 Nm ± 20 %
M
M
18376d_21
4)
Mounting is not required to a module directly next to an end plate. Mounting via the end plate is sufficient.
18376d_22
5
6.
Mounting system assembly
6a.
Check positions of the mountings
Information
Counting direction of the modules:
CPX (metal):
– from end plate (U).
6b.
Assemble mountings
Mounting 7 to CPX-modules (metal)
O
7
Place mounting 7 on the module (C).
Tighten screws 8 . If you screw it in again, use the threads already present.
Observe tightening torques. U
18375d_52
Information
Mountings are pre-assembled, dependent on the configuration.
Check positions of the pre-assembled mountings ( tables) and correct, if required ( section 5b).
Mounting 7 for CPX-modules (metal)
Without system feed to module 1
Number of modules Mounting to the modules
1 4 5 8
1 … 2
3 … 4
5 … 6
−
•
• •
7 … 8
9 … 10
• •
• • •
With system feed to module 1
Number of modules Mounting to the modules
1 … 2
3 … 5
6 … 8
9 … 10
−
•
• •
• • •
With system feed to module 1 and module 2
Number of modules Mounting to the modules
18373d_50
1.5 Nm ± 10 %
6c.
Mount CPX-terminal to the mounting system
Note
8
Material damage due to incorrect assembly.
Select screws and slot nuts suitable for the installation situation.
D F H
Y
7
P F H
18373d_51
Screw size Number
(D) M6 1x
(F) M6 2x
(H) M6 2x
1 … 3
3 … 6
7 … 8
9 … 10
−
•
• •
• • •
If mounting of an attachment 7 is prevented, through an existing system feed, for example:
Mount attachment 7 to the left or right of the system feed.
Check:
Maximum 3 CPX-modules between 2 mountings 7 .
6
7.
H-rail mounting
7a.
Mount H-rail
18373d_20
9
Mount H-rail 9 horizontally.
7b.
Mount CPX-terminal to H-rail
Q
Remove pre-assembled mountings 2 / 3 / 5 / 7 .
Q
18373d_43
Q
1
On the reverse side of the modules:
Place clamping components aA on the mounting points (Q).
Fix clamping components aA with screws aJ . aJ aA
Q
18373d_26 aA aJ
R
Align clamping components aA parallel to the slot (R).
18373d_22
1
18373d_24
R
9
Hang CPX-terminal 1 onto the H-rail 9 at the slot (R).
Swivel CPX-terminal 1 onto the H-rail 9 .
Tighten screws aJ .
Observe tightening torque. aJ
1.3 Nm ± 10 %
18373d_27 aA
18373d_23
9
1
Tightening the screws aJ turns the clamping components aA by 90°.
CPX-terminal 1 is secured against tilting and slipping.
7
advertisement
Related manuals
advertisement
Table of contents
- 1 1. Safety instructions and notes on mounting
- 2 2. Parts list
- 2 3. Explanations of terms
- 2 4. Intended use
- 3 5. Wall mounting
- 3 5a. Check positions of the mountings
- 3 5b. Assemble mountings
- 4 5c. Overview of the mounting points
- 5 5d. Mount VTSA/VTSA-F-modules (65 mm)
- 6 6. Mounting system assembly
- 6 6a. Check positions of the mountings
- 6 6b. Assemble mountings
- 6 6c. Mount CPX-terminal to the mounting system
- 7 7. H-rail mounting
- 7 7a. Mount H-rail
- 7 7b. Mount CPX-terminal to H-rail