USER MANUAL
i
ii © Copyright Reserved KONICS Co., Ltd.
Preface
Preface
Thank you very much for selecting KONICS products.
Please familiarize yourself with the information contained in the Safety Precautions section before using this product.
This user manual contains information about the product and its proper use, and should be kept in a place where it will be easy to access.
© Copyright Reserved KONICS Co., Ltd. iii
User Manual Guide
User Manual Guide
This user manual contains information about the product and its proper use, and should be kept in a place where it will be easy to access.
Please familiarize yourself with the information in this manual before using the product.
This manual provides detailed information on the product's features. It does not offer any guarantee concerning matters beyond the scope of this manual.
This manual may not be edited or reproduced in either part or whole without permission.
A user manual is provided as part of the product package.
Visit our home-page (www.konics.com) to download a copy.
The manual's content may vary depending on changes to the product's software and other unforeseen developments within KONICS, and is subject to change without prior notice.
We contrived to describe this manual more easily and correctly. However, if there are any corrections or questions, please notify us these on our homepage.
iv © Copyright Reserved KONICS Co., Ltd.
User Manual Symbols
User Manual Symbols
Symbol
※
1
Description
Supplementary information for a particular feature.
Failure to follow instructions can result in serious injury or death.
Failure to follow instructions can lead to a minor injury or product damage.
An example of the concerned feature's use.
Annotation mark.
© Copyright Reserved KONICS Co., Ltd. v
Safety Precautions
Safety Precautions
Following these safety precautions will ensure the safe and proper use of the product and help prevent accidents and minimize hazards.
Safety precautions are categorized as Warnings and Cautions, as defined below:
vi
In case of using this unit with machinery (Ex: nuclear power control, medical equipment, ship, vehicle, train, airplane, combustion apparatus, safety device, crime/disaster prevention equipment, etc) which may cause damages to human life or property, it is required to install fail-safe device.
It may cause a fire, human injury or property loss.
It must be mounted on panel.
It may cause electric shock.
Do not connect, inspect or repair this unit when power is ON.
It may cause electric shock.
Check input power specification and check power terminal number when wiring power cable.
It may cause a fire or damage by a fire.
Lithium battery is used in this product, do not disassemble or burn up this unit.
It may cause an explosion.
Do not touch the product or connect terminal within 30 sec. after turn off the power.
It may cause electric shock.
F.G. terminal should be isolation grounded. Grounded wire should be over AWG16(1.25 mm
2
).
It may cause electric shock.
Do not insert your finger or object into the vent of this unit.
It may cause electric shock or human injury.
Do not disassemble or modify this unit. Please contact us if it is required.
It may cause a fire, human injury or property loss.
This unit shall not be used outdoors.
It may shorten the life cycle of the product or cause electric shock.
When wiring power input terminal and measuring input terminal, power line should be over
AWG 20(0.50mm
2
). Terminal screw should be tightened with 0.74 N•m to 0.90 N•m torque.
Please observe the rated specifications.
It may cause shorten the life cycle of the product and cause a fire.
© Copyright Reserved KONICS Co., Ltd.
Safety Precautions
Do not use the load over the rated switch capacity value of relay contact part.
It may cause insulation failure, contact melt, contact failure, relay broken, fire etc.
When connecting magnet contact as load of relay contact output, connect surge absorber on coil part of contact.
It may cause malfunction.
In cleaning the unit, do not use water or organic solvent. And use dry cloth.
It may cause electric shock or a fire.
Do not use this unit in place where there is flammable, explosive gas, humidity, direct light, radiant heat, vibration, or impact.
It may cause a fire or explosion.
Do not inflow dust or wire dregs into the unit.
It may cause a fire or malfunction.
Wire properly after checking the terminal polarity.
It may cause a fire or explosion.
Wire properly after checking the terminal polarity when connecting temperature sensor.
It may cause malfunction.
Connection should be followed as connection diagram of this manual. Before power ON, check the connection correct.
It may cause a fire.
Do not touch terminal during dielectric or insulation resistance test.
It may cause electric shock.
It is recommended to use insulation transformer and noise filter power in case of too much noise from power. Attach noise filter on the grounded panel, etc. Wire between noise filter output part and power terminal of the product should be short as possible.
It may cause damage to the product, malfunction by surge, etc.
Before connecting temperature sensor (thermocouple, RTD) and analog (voltage, current) input, set jumper pin of universal input card as input type.
It may cause damage and malfunction to this unit.
Do not connect or separate input, output card when the product power is ON.
It may cause serious damage.
Do not open the cover or insert your finger during operation.
It may cause electric shock.
Do not control with alarm output or measure data during firmware upgrade. Alarm output, contact input, data measurement, etc do not operate normally. Therefore, this unit does not operate as intended.
Check the complete message for firmware upgrade and turn OFF to ON the power.
If do not turn OFF to ON the power, it does not operate normally.
All parameter set value is initialized after firmware upgrade. It may not operate as same way with before upgrade operation.
Use voltage output of transmitter power output card only for transmitter power.
It may cause damage to output module.
The specifications and dimensions of this manual are subject to change without any notice.
© Copyright Reserved KONICS Co., Ltd. vii
Table of Contents
Table of Contents
viii
1 Overview .................................................................................................... 13
2 Specification .............................................................................................. 21
3 Dimensions ................................................................................................ 27
4 Connection ................................................................................................ 29
5 Installation ................................................................................................. 33
6 Display ....................................................................................................... 39
7 Operation ................................................................................................... 45
© Copyright Reserved KONICS Co., Ltd.
Table of Contents
....................................................................................... 51
8 Parameter detail setup .............................................................................. 55
8.1.1 Select UI Card (Select universal input card)
8.1.2 Input Set Copy (Copy input parameter)
.............................................. 57
..................................................... 57
8.1.3 LCD/Paper Record (Display and record measuring value) ........................ 58
8.1.9 Display/Temp Unit (Display unit/Temperature unit) .................................... 60
8.1.11 Low Scale/High Scale (Lower limit/Upper limit scale value) ...................... 63
8.1.12 Special Function (Special function)
............................................................ 65
8.1.13 Reference Channel (Reference channel)
8.1.14 Input Bias(Error correction)
.................................................. 69
........................................................................ 69
8.1.16 Record Method (Data storage method) ..................................................... 71
8.2.1 Select UI Card (Select universal card input) .............................................. 75
8.2.2 Alarm Set Copy (Copy alarm parameter) ................................................... 75
8.2.3 Alarm□ Type(Alarm□ operation mode) ....................................................... 76
8.2.4 Alarm□ Ref Channel(Alarm□ reference channel) ....................................... 78
8.2.8 Alarm□ ON/OFF Delay(Alarm□ ON/OFF output delay time) ..................... 82
8.2.9 Alarm□ Alarm No(Alarm□ output alarm number) ....................................... 83
8.2.10 Select Alarm Card(Select alarm output card) ............................................. 83
8.2.11 Alarm-□ Status(Relay and TR output method) ........................................... 84
DIGITAL INPUT SETUP(Digital input setting) ................................................... 85
8.3.1 Select DI Card (Select digital input card)
8.3.2 DI-□ Type (Select digital input □ )
................................................... 86
................................................................ 87
8.3.3 DI-□ Reset No (Reset alarm number)
8.3.4 DI-□ Status (Operation status)
........................................................ 88
................................................................... 88
COMMUNICATION SETUP (Communication setting) ...................................... 89
8.4.1 Modbus Address (Communication address) .............................................. 92
8.4.2 RS485 Port (Use RS485 communication) ................................................. 92
© Copyright Reserved KONICS Co., Ltd. ix
Table of Contents x
8.4.7 Response Wait Time (Communication response wait time) ...................... 94
8.4.9 RS485 Com Write (RS485 communication write) ...................................... 94
8.4.10 Ethernet Port (Use Ethernet communication) ............................................ 95
8.4.14 Ethernet Com Write (Ethernet communication write) ................................. 98
8.4.15 USB Device Port (Use USB communication) ............................................. 98
8.4.16 USB Com Write (USB communication write) ............................................. 98
RECORD SETUP (Record setting) ................................................................... 99
8.5.2 Digital Print type (1 line record channel during numeric recording) ......... 101
8.5.3 Standard Speed (Standard record speed) ................................................ 102
8.5.4 Option Speed (Option record speed) ....................................................... 102
8.5.5 Memo Period (Digital memo period) ........................................................ 103
8.5.7 Standard Period (Standard record period) ............................................... 106
8.5.9 Listing Language (Language for list output) ............................................. 107
8.5.11 Power On Status (Record status when power ON) .................................. 108
8.5.14 Zone Dot Line Distance (Dot line for zone division) .................................. 111
8.5.15 CH Print Distance (Record interval for each channel graph) .................... 111
8.5.17 Range Print Time (Input range record period) .......................................... 112
SYSTEM SETUP (System setting) .................................................................. 113
8.6.5 Summer Time Period (Summer time period) ............................................ 115
8.6.6 Reservation Type (Reservation record) ................................................... 116
8.6.7 Reservation Period (Reservation record period) ...................................... 117
8.6.8 Reservation Time (Reservation record time) ............................................ 117
8.6.13 Backlight On/Off (LCD backlight ON method) .......................................... 119
FILE/MEMORY SETUP(File/Memory setting) ................................................. 120
8.7.1 Load Set File (Open parameter setting file) ............................................. 121
8.7.2 Save Set File (Save parameter setting file) .............................................. 121
© Copyright Reserved KONICS Co., Ltd.
Table of Contents
8.7.5 USB LogData Save (USB storage function) ............................................ 123
8.7.6 Memory Save Option (Memory storage option) ....................................... 124
8.7.7 USB Memory Copy/Move (Move/Copy data) ........................................... 125
USER INFORMATION SETUP(User information setting) ............................... 126
8.8.3 Change Admin Password (Change password by administrator)
8.8.4 User Lock (Change user authority)
.......................................................... 129
8.8.5 Information (Check system information) .................................................. 129
8.8.6 Firmware Upgrade (Firmware upgrade) ................................................... 130
RECORD BACKUP_ SETUP (Backup data record setting) ............................ 132
8.9.1 Record Backup (Backup data record)
8.9.2 Backup Data List (Backup data list)
...................................................... 133
......................................................... 133
8.9.3 Start Date and Time (Start time for data storage) .................................... 134
8.9.4 End Date and Time (End time for data storage) ...................................... 134
8.9.5 Backup Print Mode (Backup data record mode) ...................................... 134
8.9.6 Select Print Mode (Backup data recording mode setting) ....................... 135
9 DAQMaster .............................................................................................. 137
10 Maintenance ............................................................................................ 145
11 Troubleshooting ...................................................................................... 151
© Copyright Reserved KONICS Co., Ltd. xi
Table of Contents xii © Copyright Reserved KONICS Co., Ltd.
1
1.1
1 Overview
Overview
Feature of KRN 100
KRN100 is 100mm hybrid recorder with dot. It combines functions of paper recorder and paperless recorder by saving function with an USB memory (the world’s first) and by adopting
Trend graph, Bar graph, digital number display function through graphic LCD.
KRN100 enables to print the saved data of system memory as data backup function when run out of recording paper. KRN100 improves convenience by parameter setting, data transmittion through RS485 and Ethernet communication (USB device is only for parameter setting), and backup data logger function.
It also adopts slot type input, output card to connect option card up to 12 channels. It supports several communication types, of course, and graphic user interface(GUI) with graphic display for easire and convenient use.
Combines functions of paper recorder and paperless recorder
Enables to print the saved data of inner memory when run out of recording paper (Data logger function)
Inner data backup with an USB memory
High legibility and setting convenient by graph LCD
25ms high sampling, 240mm/h high speed record function
100mm paper record (Selectable 6 kinds of record color)
Supports system memory and external memory data backup (storage)
Supports several input up to 12 channel with slot type input card
Enables to select several option card with slot type output card
Supports several communication(RS485, Ethernet) to transfer real time data
Enables to set parameter with USB Device※1
Space saving for installation with compact design (Rear length: 168mm)
Supports total 27 kinds of input sensor
Enables to order several type input card (weight, voltage, current, frequency, potential meter, etc)
© Copyright Reserved KONICS Co., Ltd. 13
1 Overview
1.2
Component and sold separately
1.2.1 Component
Before using KRN100, check the component.
If any component is left out or damaged, contact our company or seller.
KONICS service center: +82-32-820-2343
1.2.2 Accessory
(1) I/O card
14
(2) Communication converter
Appearances of SCM-38I (RS232C to RS485 converter) and SCM-US48I (USB to RS485 converter) are same.
© Copyright Reserved KONICS Co., Ltd.
1.3
1 Overview
Ordering information
(1) Ordering information
KRN100 - 12 0 0 0 - 0 0 - 0 S
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨
Item
①
Item
②
Input channel
③
Digital input
④
Alarm TR output
⑤
Alarm Relay output
⑥
Transmitter power output
⑦
Communication output
⑧
Power voltage
⑨
Case
1
2
3
3
0
1
2
1
0
4
0
S
1
2
0
2
0
0
1
Description
KRN100 New KONICS 100mm Paper Type Recorder
04
06
08
10
12
4 channel (KRN-UI2 X 2ea)
6 channel (KRN-UI2 X 3ea)
8 channel (KRN-UI2 X 4ea)
10 channel (KRN-UI2 X 5ea)
12 channel (KRN-UI2 X 6ea)
None
6ea(KRN-DI6 X 1ea)
12ea(KRN-DI6 X 2ea)
None
6ea( KRN-AT6 X 1ea)
12ea( KRN-AT6 X 2ea)
None
4ea( KRN-AR4 X 1ea)
8ea( KRN-AR4 X 2ea)
12ea( KRN-AR4 X 3ea)
None
3ea( KRN-24V3 X1ea)
6ea( KRN-24V3 X 2ea)
9ea( KRN-24V3 X 3ea)
12ea( KRN-24V3 X 4ea)
None
RS485/Ethernet/USB( KRN-COM X 1ea)
100 to 240VAC, 50/60Hz
Standard panel mounting type
© Copyright Reserved KONICS Co., Ltd. 15
1 Overview
(2) I/O card model name
Type Model name
Function and number of channel
Max. connectable card
Slot number
Universal input card
KRN-UI2
Digital input card KRN-DI6
Universal input 2 channel 6ea 1 to 6
Alarm output card
KRN-AR4
KRN-AT6
Digital input 6 channel 2ea
Alarm relay output 4 channel
3ea
Alarm TR output 6 channel 2ea
7 to
10
※ 1
Transmitter power output card
Communication output card
KRN-24V3
KRN-COM
Transmitter 24VDC power output 3 channel
RS485+USB+Ethernet communication channel
4ea
1ea C
※1.
Digital input card, alarm output card, transmitter power output card are connectable up to
4ea as mixed.
(3) Example of ordering
To use universal input 10 channel, digital input 4 channel, alarm relay output 5 channel, and
RS485 communication output, it is ordered as KRN100-10102-01-0S and connected I/O card is as below.
KRN100(Recorder): 1ea
KRN-UI2(Universal input card): 5ea
(Universal input card 2ea is factory default. 5ea X 2 channel =10 channel)
KRN-DI6(Digital input card): 1ea
KRN-AR4(Alarm relay output card): 2ea
KRN-COM(Communication output card): 1ea
16 © Copyright Reserved KONICS Co., Ltd.
1.4
Part description
1.4.1 Front and side part
1 Overview
① Display part: Displays measurement values as trend graph, bar graph, or digital number
(1/8/12 channel).
Please refer to ‘7.1 Screen display ’.
② Recording print part: Records measuring value of data by each channel with designated color.
③ Channel information part: Write the information by each channel.
④ Control key/Function key: Executes parameter setting and recording, and special function
Key Function
Using this key for starting/stopping recording, changing input characters on virtual keyboard status, and displaying Function key.
Press this key for 3 sec in stop state, ink cartridge moves to the center.
(Use this to replace ink cartridge.)
Using this key for going out from parameter setting group or setting manual channel switch mode.
It also executes to release auto channel switch mode and printer list output
(3 sec) function.
Using this key for moving parameter in setting mode, setting manual channel switch mode and forced alarm reset (3 sec).
Using this key for moving parameter in setting mode, increasing digit value, setting auto channel switch mode, and manual feed function (by pressing over 3 sec.) in stop state.
Using this key for moving parameter in setting mode, decreasing digit value, changing display mode and executing manual digital memo (3 sec) in recording state.
Using this key for entering setting mode (3 sec) and set value change mode.
⑤ USB Host: Connects an USB memory. It recognizes max. 32Gbyte and if using cable, it is available up to 1.5m.
© Copyright Reserved KONICS Co., Ltd. 17
1 Overview
Function key: Use this key to enter virtual keyboard in parameter setting.
Press
, ,
key, and Function key appears on lower screen as below figure. Press
, or
,
key as below Function key, it operates the appropriate Function key’s operation.
18 © Copyright Reserved KONICS Co., Ltd.
1.4.2 Back side
1 Overview
① Slot(C) for connecting communication output card(KRN-COM)
② Slot(7to10) for connecting digital input card(KRN-DI6), alarm relay output card(KRN-AR4), alarm TR output card (KRN-AT6), transmitter power output card(KRN-24V3)
You can connect total 4ea by combining digital input card, alarm output card, and transmitter power output card, as below combination example.
KRN-DI6
1ea
+
KRN-AR4
1ea
+
KRN-AT6
1ea
+
KRN-24V3
1ea
=
Total 4ea
KRN-DI6
2ea
+
KRN-AR4
1ea
+
KRN-AT6
1ea
= Total 4ea
KRN-AT6
1ea
+
KRN-24V3
3ea
= Total 4ea
③ Slot(1 to 6) for connecting universal input card(KRN-UI2)
④ Power connecting part (100-240VAC, 50/60Hz)
※ Above back side image is connected every otuput card to help your understand. Factory default is only connected with universal input cards (Slot1 and 2).
© Copyright Reserved KONICS Co., Ltd. 19
1 Overview
1.4.3 Inside
① Ink cartridge: Record ink cartridge to record data on recording paper.
(Model name: D33006B-66X-01)
② Recording paper cassette: Cassette saves the recording paper.
③ Recording paper cassette lever: Press the lever down and this recording paper cassette is removed from KRN100.
Remove the recording paper cassette for recording paper replacement, ink cartridge replacement.
1.4.4 Paper cassette
20
① Recording paper holder: Movement holder of recording paper when recording
② Recording paper storage part: Storage part for recorded recording paper
③ Front cover of recording paper storage: Open recording paper guide for recording paper replacement
④ New recording paper storage: Storage part for new recording paper (1EA recording paper is storable.)
⑤ Back cover of recording paper storage
© Copyright Reserved KONICS Co., Ltd.
2 Specification
2
2.1
Specification
KRN100
Model
Power voltage
KRN100
100 - 240VAC, 50/60Hz
Allowable voltage range 85 - 264VAC
Power consumption
Screen
LCD type
Resolution
Adjusting brightness
Max. 55VA
STN Graphic LCD
320 X 120Pixel
4 level(OFF / Min / Standard / Max)
Backlight
The number of input channel
Universal input ※1
White LED, 2 level(Temp/Always)
4 / 6 / 8 / 10 / 12 channel(2 channel/card) – Expandable
Sampling period
Temperature sensor(RTD, thermocouple), analog
1 to 4 channel: 25 ㎳/125 ㎳/250 ㎳, 5 to 12 channel: 125 ㎳/250 ㎳
(Inner sampling period is operation unit time for average movement filter and alarm output function.)
※
Max. sampling period for TC-R, U, S, and T sensor is 50ms.
Recording period in graph mode
10, 20, 40, 60, 120, 240mm/h
Storage period
Inner memory
USB memory
1 to 3,600 sec
(Storage interval time to inner log file is 1 sec.)
512MByte
User purchased, recognizes max. 32GByte, enables to use cable up to 1.5m
Function
Dielectric
Record color, Record zone, Input special function, Input digital filter,
Reservation set, Summer time, Delay alarm, Record speed change, Data storage, Backup data record, etc
2,500VAC 50/60Hz for 1 min. (power terminal and case)
※
USB Device and Ethernet are excepted
Vibration strength
(for convey and storage) and operating vibration
Vibration strength: 10to60Hz 4.9m/s2 (in X, Y, Z axes for each 1time)
Operating vibration: 10to60 1m/s2 (in X, Y, Z axes for each 10 min.)
Insulated resistance
Noise
Time accuracy
Mechanism
Ink cartridge
Min. 20MΩ (at 500VDC megger)
±2kV the square wave noise (pulse width 1µs) by the noise simulator
Within ±2min/year (Enables to use up to 2100 year)
Enables to normal print with going and returning printing max.5 times within 7 days after opening the unit
© Copyright Reserved KONICS Co., Ltd. 21
2 Specification
Protection
Ink dry time
Recording paper
Installation environment
Max. 15 minutes
IP40(for front panel)
113mm X 9m
It shall be used indoor, Altitude Max. 2,000m, Pollution Degree2
Installation category II
Temperat ure
0 to 50℃, Storage: -20 to 60℃, (without ink cartridge)
Environment
※ 2
Humidity
35 to 85% RH, Storage: 35 to 85% RH
※
If using this unit at place with high humidity, it may cause paper jam.
Please do not use this unit at place with high humidity.
Approval
Unit weight Approx. 1.7 to 2.0kg
※1.
For more information of universal input, please refer to ‘2.2 I/O card’.
※2.
Environment resistance is rated at no freezing or condensation.
22 © Copyright Reserved KONICS Co., Ltd.
2.2
2 Specification
I/O card
Type Model I/O specification
RTD
Description
JPT100Ω, DPT100Ω, DPT50Ω, CU100Ω,
CU50Ω(Supply current 420µA)
Universal input card
KRN-UI2
Input specific ation
※ 1
Display accurac y
※ 2
Thermoco uple
Analog
Input impedance
RTD
Thermoco uple
Analog
Resolution
B, C(W5), E, G, J, K, L, L(Russia), N, P, R, S, T, U
Voltage: ±60mV ±200mV ±2V, 1-5V, ±5V, -1V to
10V
Current: 0.00to20.00 ㎃ 4.00to20.00 ㎃
Voltage(V): Min. 150kΩ
RTD, thermocouple, voltage(mV): min. 2MΩ current: 51Ω
Warm-up time: Min. 30 minutes
·
Room temperature (25℃±5℃) section: ±0.1% F.S.±
1 Digit
·
Out of range of room temperature: ±0.2% F.S.±1 Digit
RTD: 500 to 850℃ is PV value±0.5%±1 Digit
Thermocouple: Below -100℃ is ±0.3% F.S. ±1 Digit
16Bit
ON: Max. 1V of residual voltage, OFF: Max. 0.1 ㎃ leakage current
ON: Max. 1kΩ, OFF: Min. 100kΩ, Short: Approx. 4 ㎃
Digital input card
KRN-DI6
Noncontact input
Contact input
Alarm output card
KRN-AR4
Alarm relay output
Capacity 250VAC 3A, 30VDC 3A, 1 Form A (resistance load)
Life
KRN-AT6 Alarm TR output
Mechanical: Min. 50,000,000 operations
Electrical: Min. 100,000 operations
(3A 250V AC, 3A 30V DC)
NPN Open Collector, 12-24VDC / 30 ㎃ Max.
Transmitt er power output card
KRN-
24V3
Power output for transmitter
※
5
24±2VDC, total 3 channel, max. 30 ㎃ per 1 channel built-in over-current protection circuit
Communi cation output card
※ 3
Commu nication output
RS485
Modbus RTU
※
Recommended to use shield cable over AWG24
KRN-
COM
Ethernet IEEE802.3(U), 10/100 BASE-T(Modbus TCP)
USB
Device
※
4
USB V2.0 Full Speed(Device Control)
※1.
To change input specification, you must turn OFF the power of KRN100, remove universal
input card, set inner jumper pin (Please refer to 4.2 I/O card.) and re-connect it.
© Copyright Reserved KONICS Co., Ltd. 23
2 Specification
※2.
Exception range for better accuracy by sensor (Accuracy after 30min warm-up time)
R,S,C,G: 0≤T≤100 ±4.0℃,
B: No regulation accuracy below 400 ℃
T, U: -200≤T≤-100±3.0℃, -100≤T≤400±2.0℃,
CU50: -200≤T≤200±1.0℃,
DPT50: -200≤T≤500±1.5℃
※3.
RS485, Ethernet communication output are not available at the same time.
※4.
USB Device is available only for parameter setting.
※5.
It is recommended to use shield cable to decrease noise when supplying power for transmitter.
If connecting or disconnecting input/output card when power is ON, it may cause malfunction.
To connect or disconnect input/output card, you must turn OFF the power.
24 © Copyright Reserved KONICS Co., Ltd.
2 Specification
2.3
Input specification and measuring range
Measuring range
Input sensor Mark
℃ ℉
K
Thermocouple
Resistance temperature detector
(RTD)
K(CA)
J(IC)
E(CR)
T(CC)
B(PR)
R(PR)
S(PR)
N(NN)
C(TT) ※1
G(TT)
※2
L(IC)
L (Russian type) ※3
U(CC)
Platinel Ⅱ
CU50Ω
CU100Ω
TC-P
CU50
CU100
JPT100Ω
DPT50Ω
JPT100
DPT50
DPT100Ω DPT100
-60.00 to 60.00 ㎷ ±60 ㎷
TC-N
TC-C
TC-G
TC-L
TC-L_R
TC-U
TC-K
TC-J
TC-E
TC-T
TC-B
TC-R
TC-S
-200.0 to 1350.0 -328.0 to 2462.0 73.2 to 1623.2
-200.0 to 800.0 -328.0 to 1472.0 73.2 to 1073.2
-200.0 to 800.0 -328.0 to 1472.0 73.2 to 1073.2
-200.0 to 400.0 -328.0 to 752.0 73.2 to 673.2
100.0 to 1800.0 212.0 to 3272.0 373.2 to 2073.2
0.0 to 1750.0
0.0 to 1750.0
32.0 to 3182.0
32.0 to 3182.0
273.2 to 2023.2
273.2 to 2023.2
-200.0 to 1300.0 -328.0 to 2372.0 73.2 to 1573.2
0.0 to 2300.0 32.0 to 4172.0 273.2 to 2573.2
0.0 to 2300.0 32.0 to 4172.0 273.2 to 2573.2
-200.0 to 900.0 -328.0 to 1652.0 73.2 to 1173.2
0.0 to 600.0 32.0 to 1112.0 273.2 to 873.2
-200.0 to 400.0 -328.0 to 752.0 73.2 to 673.2
0.0 to 1350.0 32.0 to 2462.0 273.2 to 1623.2
-200.0 to 200.0 -328.0 to 392.0 73.2 to 473.2
-200.0 to 200.0 -328.0 to 392.0 73.2 to 473.2
-200.0 to 600.0 -328.0 to 1112.0 73.2 to 873.2
-200.0 to 600.0 -328.0 to 1112.0 73.2 to 873.2
-200.0 to 850.0 -328.0 to 1562.0 73.2 to 1123.2
Resolution:10µV
Analog
-200.00 to
200.00 ㎷
Voltage
-2.000 to 2.000V
1.000 to 5.000V
-5.000 to 5.000V
-1.00 to 10.00V
±200 ㎷
±2V
1 to 5V
±5V
-1V to 10V
Resolution:10µV
Resolution: 1mV
Resolution: 1mV
Resolution: 1mV
Resolution:
10mV
Depending on decimal point position setting;
-99999 to 99999
-9999.9 to 9999.9
-999.99 to 999.99
-99.999 to 99.999
-9.9999 to 9.9999
Current
0.00 to 20.00 ㎃
4.00 to 20.00 ㎃
0 to 20 ㎃ Resolution:10µA
4 to 20 ㎃ Resolution:10µA
※1.
C(TT): Same temperature sensor type as existing W5(TT).
※2.
G(TT): Same temperature sensor type as existing W(TT).
※3.
Russian type L type temperature sensor is divided from general purpose L type.
To change input specification, set jumper pin of KRN-UI2(Universal input card).
(Please refer to ‘4.2 I/O card.)
© Copyright Reserved KONICS Co., Ltd. 25
2 Specification
26 © Copyright Reserved KONICS Co., Ltd.
3 Dimensions
(1) KRN100
3 Dimensions
※ Back side dimension is with installed I/O cards to every slot.
(2) Panel cut-out
※ Use panel which is 2 to 8mm thickness.
© Copyright Reserved KONICS Co., Ltd. 27
3 Dimensions
28 © Copyright Reserved KONICS Co., Ltd.
4
4.1
Connection
KRN100
This figure is back side of KRN100-04000-00-0S model.
4 Connection
Slot Description
1 to 6 Connects universal input card (KRN-UI2).
7 to 10
C
Connect digital input card (KRN-DI6), alarm output card (KRN-AR4, KRN-AT6), and transmitter power output card (KRN-24V3).
Connects communication output card (KRN-COM).
© Copyright Reserved KONICS Co., Ltd. 29
4 Connection
4.2
I/O card
Universal input card (KRN-UI2) Digital input card (KRN-DI6)
Alarm output card
(KRN-AR4(Relay output))
Alarm output card
(KRN-AT6(TR output))
30
Transmitter power output card
(KRN-24V3)
Communication output card (KRN-COM)
© Copyright Reserved KONICS Co., Ltd.
4 Connection
Depending on input specification, set the jumper pin of universal input card (KRN-UI2) channel 1, channel 2 as below figure.
Jumper pin Input specification
①
②
③
0 to 20 ㎃, 4 to 20 ㎃
TC, RTD, ±60mV, ±200mV
±
2V, 1 to 5V, ±5V, -1 to 10V
© Copyright Reserved KONICS Co., Ltd.
Input break alarm
Enables only 4 to 20 ㎃
Enables
Disables
31
4 Connection
32 © Copyright Reserved KONICS Co., Ltd.
5
5.1
5 Installation
Installation
Installation place
Install this unit in place where the below conditions are satisfied.
Place where ventilation is well
To prevent from malfunction and damage by overheating (use temperature range: 0 to 50℃), install this unit where ventilation is well.
In case installing several KRN100, space each other by panel cut-out.
Place where vibration is not severe
If there is too much vibration, it may cause malfunction such as print error.
For more information about vibration, please refer to ‘2 Specification’.
In case of temperature measurement with thermocouple temperature sensor at the place where temperature is fluctuated, data error may occur. You should warm-up this unit over 30 min. to acquire accurate data before using it.
At the place where temperature and humidity is fluctuated excessively, recording paper color may be changed.
© Copyright Reserved KONICS Co., Ltd. 33
5 Installation
5.2
Installation
5.2.1 Bracket mounting
1st
Install KRN100 on the processed panel as panel cut-out diagram. Mount fixing brackets on upper/lower parts.
34
2nd
Tighten fixing brackets on upper/lower parts to fix on the panel with phillips screwdriver (+). (Torque: 0.4N•m)
© Copyright Reserved KONICS Co., Ltd.
5 Installation
5.2.2 Additional I/O card connection
1st
To connect I/O card additionally, turn OFF the power of KRN100.
Remove the proper slot cover to insert I/O card with flat-head screwdriver or knife.
2nd
Insert I/O card to the proper slot and turn ON the power of KRN100.
© Copyright Reserved KONICS Co., Ltd. 35
5 Installation
5.3
USB to Serial driver
Install USB to serial driver which is applied for KRN100 sereis and connect DAQMaster and you can set parameter setting.(It is available only when communication output card (KRN-COM) is connected. Supporing OS for USB to Serial driver is Windows XP 32/64bit, Windows 7 32/64bit.)
5.3.1 Driver installation
1st
Visit our homepage www.konics.com and downlaod 'KRN100_USB_Serial_Drivers’.
Unzip this file to the desired folder.
2nd
Connect KRN100 USB port of communication output card(KRN-COM) and PC USB port with USB cable (A-Mini 5P, 1.5m).
3rd
‘Found New Hardware Wizard’ appears.
Select ‘Install from a list or specific location (Advanced)’ and click ‘Next>’.
36 © Copyright Reserved KONICS Co., Ltd.
5 Installation
4th
Select ‘Search for the best driver in these locations’ and check ‘Include this locationin the search:’.
Click ‘Browse’ and select the folder which has 'KRN100_USB_Serial_Drivers’ and click ‘OK’.
5th
If hardware compatibility message appears, click ‘Continue Anyway’ and it processes the next.
6th
At ‘Completing the Found New Hardware Wizard’, click ‘Finish’ and driver installation is complete.
© Copyright Reserved KONICS Co., Ltd. 37
5 Installation
5.3.2 Checking driver
To check the driver, right click 'My computer' and select 'Properties' on pop-up menu. 'System
Properties' dialog appears.
Select ‘Hardware’ tab and click 'Device Manager'. ‘Device Manager’dialog appears.
Check ‘Ports(COM & LPT)’ - 'KRN100 USB To Serial Converter (COMx)'.
38 © Copyright Reserved KONICS Co., Ltd.
6
6.1
6 Display
Display
Initial booting screen
Below booting screens are initially displayed when power is supplied to KRN100. These screens progresses initial settings for KRN100 to operate normally and checks inner system memory.
If there is no error for inner system memory, booting is finished and KRN100 operates normally.
Screen for progressing initial setting
Screen for checking error of inner system memory
If there are lots of log data files, booting time may take a long time.
Delete log data file. For more information, refer to ‘8.7.4 Memory Clear (Delete memory)’.
Screen for error of inner system memory
Above this figure, if there is error of inner system memory, KRN100 cannot operate normally.
Please contact us. KONICS service center: +82-32-820-2343
© Copyright Reserved KONICS Co., Ltd. 39
6 Display
6.2
Screen layout
Screen layout is divided as two; upper screen for status display, lower screen for measuring value display, virtual keyboard display, parameter display.
6.2.1 Status display
Upper screen displays recorder status and information of recorder as icon.
40
Section Icon
1
2
Name
Record start icon
Record stop icon
Description
Marks if for starting recording measuring value of recordable channels.
Stops recording measuring value.
List record icon Flashes during list recording.
Reservation record icon Flashes during reservation recording.
FEED icon Flashes during feeding recording paper.
Backup data print icon Flashes during backup data printing.
Digital mode icon Marks it for digital record mode.
Graph mode icon Marks it for graph record mode.
Record memory status icon
Marks it storage capacity of record memory in digital mode or graph mode.
© Copyright Reserved KONICS Co., Ltd.
6 Display
Section Icon
3
Name
No recording paper icon
※ 1
USB communication icon
Ethernet communication icon
RS485 communication icon
Description
Marks it for no recording paper. Please replace new recording paper.
Marks icon during Modbus RTU communication using USB.
Marks icon during ModBus TCP communication using Ethernet.
Marks icon during Modbus RTU communication using RS485.
4
Alarm ON icon
Digital input(DI) icon
Marks occurs.
channel icon which alarm
Marks the below icon according to input function setting during digital input (DI).
Marks it when digital memo of digital input or front
5
6
Digital input(DI)- memo icon
Digital input(DI)- alarm reset icon
Digital input(DI)- start record icon
Digital input(DI)- stop record icon
Digital input(DI)- LIST output icon
Digital input(DI)- record speed icon
Unlock icon
User(general user) lock icon
is input in recording status.
Marks it when alarm reset signal of digital input
(DI) is input.
Marks it when start record signal of digital input
(DI) is input.
Marks it when stop record signal of digital input
(DI) is input.
Marks it when LIST output signal of digital input
(DI) is input.
Marks it when changing record speed signal of digital input (DI) is input.
Marks it for unlock status.
Marks it for user (general user) lock status.
7
8
Administrator lock icon
Inner and external (USB) memory capacity icon
Date/Time display
Marks it for administrator and general user lock status.
Displays data capacity of internal memory as bar graph. When an USB memory is connected, it displays data capacity of an USB memory as bar graph . If used memory capacity is over 90% of total capacity, it flashes.
Displays current date and time. In summer time season, (S) mark is also displayed at front of year.
※1.
If there is no recording paper, icon flashes. After replacing recording paper, P.END
BACKUP PRINT screen as below is activated.
© Copyright Reserved KONICS Co., Ltd. 41
6 Display
Backup data recording function by P.END is same as RECORD BACKUP. Backup Data List cannot be changed.
Starting print by P.END Backup, it prints the data but backup data file date, file name, and backup record starting line.
42 © Copyright Reserved KONICS Co., Ltd.
6 Display
6.2.2 Virtual keyboard
You can enter set value with vertual keyboard. (Supports only English letters for entering character.).
Virtual keyboard is activated when set value is input.
You can enter English letters, numbers, special characters by , , , , and keys.
,
No
1
Front key Description
Press key once and English capital letters, English small letters, and special character virtual keyboard is switching.
※
1
When pressing and holding key, screen of Function key is displayed.
※ 2
2
, , , Moves digit to select character of virtual keyboard
3 Enters set characters
※1.
Enterable characters are as below.
English capital letters
English small letters
Special character
※2.
Screen of Function key using
© Copyright Reserved KONICS Co., Ltd. 43
6 Display
6.2.3 Parameter setting display
44
Press front key for 3 sec, and it enters parameter setting group.
When entering parameter setting group, setable parameter setting groups are displayed. At parameter setting group, press key to enter parameter setting.
For more information of parameter detail setup, please refer to ‘8 Parameter detail setup’.
© Copyright Reserved KONICS Co., Ltd.
7 Operation
7 Operation
© Copyright Reserved KONICS Co., Ltd. 45
7 Operation
7.1
Screen display
7.1.1 Measuring value display
KRN100 displays measuring value as trend graph, bar graph, and digital number display(1 channel, 8 channels, 12 channels). You can select one by key.
(1) Trend graph
Displays input measuring value of each channel as trend graph (left) and digital number
(right).
4 channels are displayed per one screen. To switch channel, please refer to “7.1.2 Channel switch".
(2) Bar graph
46
Displays input measuring value of each channel as bar graph (left) and digital number (right).
You can easily check present measuring value within the set display range as level (%).
4 channels are displayed per one screen. To switch channel, please refer to “7.1.2 Channel switch".
© Copyright Reserved KONICS Co., Ltd.
7 Operation
(3) Digital number
Displays input measuring value of each channel as digital number.
Digital number display is divided as 1 channel digital number, 8 channels digital number, 12 channels digital number.
Display of 1 channel digital number: Displays 1 channel per 1 screen with big font size.
It has high visibility.
Display of 8 channels digital number: Displays 8 channels per 1 screen.
Display of 12 channels digital number: Displays 12 channels (all channels) per 1 screen.
© Copyright Reserved KONICS Co., Ltd. 47
7 Operation
7.1.2 Channel switch
It displays measuring value of all input channels by switching channel of display types. You can set channel switch mode as auto channel switch or manual channel switch.
7.1.2.1 Auto channel switch
A screen displays 4 channels and automatically switches other screens by 3 sec period.
(1) Trend graph
(2) Bar graph
48 © Copyright Reserved KONICS Co., Ltd.
(3) Digital number(1 channel)
7 Operation
(4) Digital number(8 channels)
(5) Digital number(12 channels)
Digital number (12 channels) displays all channels (1 to 12 channel). It does not support auto/manual channel switch function.
7.1.2.2 Auto channel switch mode↔ Manual channel switch mode
1st
When supplying/re-supplying power to KRN100, it is display currently display and auto channel switch mode.
2nd
If you want to change manual channel switch mode, press
3rd
You can switch/select the to-be displayed channel by pressing
key or
key or
key. key.
4th
In manual channel switch mode, press mode.
key to change to auto channel switch
© Copyright Reserved KONICS Co., Ltd. 49
7 Operation
7.2
Special operation for record
KRN100 executes special operation for record with front keys ( , , , ).
(1) Start record (RUN)/Stop record (STOP)
Press front recording.
key at once, it starts recording and press this key once again, it stops
When digital input operation status is set as ‘Level’, you cannot start/stop record by front
key. In case of as ‘Edge’, start record (RUN)/stop record (STOP) function is available with front key.
(2) Parameter’s set information print (List Print)
This function is to record the main parameter’s set information on recording paper. Press
key for over 3 sec. during recording or stop state, and it records the set information of each menu.
For more information, please refer to ‘8.5.13 List Out Option (List record option)’.
Even if you print the parameter set information with max record speed (240mm/h), it takes a lot of time. (It takes approx. 40 minutes for 12 channels.)
Be sure that for printing the list.
(3) Manual feed (FEED)
In record STOP state, press front key for over 3 sec, record state icon is changed to
icon and you can feed recording paper manually.
To tear recording paper, use this manual feed function at first.
(4) Digital memo (Digital Memo)
Press for over 3 sec, during recording status, digital input icon changes to
memo icon. It records current time (hh:mm:ss) and display value of each channel as digital number on recording paper. It also displays ‘M’ which means the recording by memo at front of current time.
50 © Copyright Reserved KONICS Co., Ltd.
7 Operation
7.3
Parameter setting group
7.3.1 Parameter setting
The setting order of KRN100 basic parameters is as below.
For more information of detail setup of each parameter, please refer to ‘8 Parameter detail setup’.
To enter parameter setting group: Press key for 3 sec.
To move among setting group: ,
To move the setting:
To move upper parameter after setting: Press key and Function key is activated which is placed at bottom right as below figure. Press OK ( ) key or Cancel ( ) key.
Cancel: Moves to upper parameter after not saving the setting.
OK: Moves to upper parameter after saving the setting.
© Copyright Reserved KONICS Co., Ltd. 51
7 Operation
7.3.2 Parameter
52 © Copyright Reserved KONICS Co., Ltd.
7 Operation
※Dot-lined parameters are affected by set value of other parameters.
© Copyright Reserved KONICS Co., Ltd. 53
7 Operation
54 © Copyright Reserved KONICS Co., Ltd.
8
8.1
8 Parameter detail setup
Parameter detail setup
INPUT SETUP(Input setting)
You can set details for input specification and scale by universal input channel, record method, input digital filter, input error correction, etc.
Move to INPUT SETUP with , keys, press key to enter INPUT SETUP.
Parameter list
Parameter Set range
Select UI Card (Select universal input card)
CH□-S□UI-□
Input Set Copy (Copy input parameter)
None, CH□-S□UI-□
LCD/Paper Record (Display and record measuring value)
OFF ↔ ON
1-Violet ↔ 2-Red ↔ 3-Black ↔ 4-Green ↔ 5-Blue
↔ 6-Brown
Input Type (Input specification)
None, 1 ↔ Zone n
None/1 to 6 characters
Refer to detail descriptions.
TC, RTD: 0 ↔ 0.0
Range/Scale Point (Decimal point)
Analog: 0 ↔ 0.0 ↔ 0.00 ↔ 0.000 ↔ 0.0000
If special function is two unit: 0 ↔ 0.0 ↔ 0.00
Display/Temp Unit (Display unit/Temperature unit)
Scale(Upper/Lower limit input value and graph scale value)
Low Scale/High Scale (Lower limit/Upper limit scale value)
Special Function (Special function)
TC, RTD: ℃ ↔ ℉ ↔ ˚K
Analog: Refer to detail descriptions.
Low: Input range/Min. graph scale value to upper limit input value /Graph scale value (High Range/Graph
Scale)– F.S. 5%
High: Lower limit input value/Graph scale value (Low
Range/Graph Scale) + F.S 5% to input range/Max. graph scale value
Low: Set the range by set value of scale point
High: Set the range by set value of scale point
TC, RTD: None ↔ Difference
Analog: Linear ↔ Square ↔ Root ↔ Two Unit
Two Unit (Display the degree of a
vacuum, static pressure)
1 to 35
Factory default
Automatica lly set
CH Select
ON
None
CH-1to12
TC-K
0.0
0.0
-
-
Automatica lly set
℃
%
-200.0
1350.0
None
-
Reference Channel (Reference channel) None ↔ CH□-S□UI-□
(Activates connected universal input(2 channel per one
-
© Copyright Reserved KONICS Co., Ltd. 55
8 Parameter detail setup
Parameter Set range
card))
-999.9 to 999.9
0.100 to 5.000
Record Method (Data storage method)
Instant ↔ Average ↔ Minimum ↔ Maximum
Filter Type (Input digital filter)
Filter Counter (The number of digital filter)
Burnout Action (Display setting for break)
None ↔ Moving
1 to 128
OFF ↔ Up_Scale ↔ Down_Scale
Factory default
0.0
-
Instant
None
-
OFF
※Shaded parameters are affected by set value of other parameters. Please refer to specific descriptions of each parameter.
When changing set value of
Input Type(input type) parameter,
▶
Range/Scale Point(Decimal point position)
Display/Temp Unit(Display unit/Temperature unit)
Low Range & Graph Scale (Lower limit input value and graph scale value)
High Range & Graph Scale (Upper limit input value and graph scale value)
Low Scale(Analog lower limit scale value)
High Scale(Analog upper limit scale value)
Special Function (Input special function) parameters’ set values are initialized.
56 © Copyright Reserved KONICS Co., Ltd.
8.1.1 Select UI Card (Select universal input card)
8 Parameter detail setup
Select the channel of universal input card (KRN-UI2) to be set.
One universal input card has two channels.
KRN100 automatically searches slot connected universal input card (KRN-UI2) and displays as channel as soon as power is ON.
Channel name form is as below.
CH
Channel number
- S
Slot number
UI - card input
CH06-S3UI-2: It means 6th channel and 2nd input of 3rd slot connected universal input card.
8.1.2 Input Set Copy (Copy input parameter)
You do not need to repeat the setting of same parameter for each channel. KRN100 copies set values of the set-completed channel to other channels.
Copyable parameters are as following.
Input Type (Input specification)
Display/Temp Unit (Display/Temperature unit)
High Scale (Upper scale)
Two Unit (Display the degree of a vacuum, static pressure)
Input Bias (Error correction)
Record Method (Data storage method)
Filter Counter (The number of digital filter)
High Range & Graph Scale (Upper limit input value and graph scale value)
Set range: None/CH□-S□UI-□
Range/Scale point (Decimal point)
Low Scale (Lower limit scale)
Special Function (Special function)
Reference Chanel (Reference channel)
Span (Gradient adjustment)
Filter Type (Input digital filter)
Burnout Action (Display setting for break)
Low Range & Graph Scale (Lower limit input value and graph scale value)
Factory default: CH Select
© Copyright Reserved KONICS Co., Ltd. 57
8 Parameter detail setup
8.1.3 LCD/Paper Record (Display and record measuring value)
Set whether to record measuring value.
If you set ON, KRN100 displays and records measuring value on LCD screen, and recording paper. If you set OFF, KRN100 does not display and record measuring value on LCD screen, and recording paper.
Set range: ON ↔ OFF
Factory default: ON
8.1.4 Pen Color (Record color)
Designate record color when recordingmeasuring value.
Set range: 1-Violet ↔ 2-Red ↔ 3-Black ↔ 4-Green ↔ 5-Blue ↔ 6-Brown
Factory default: Automatically set
8.1.5 Record Zone (Record zone)
In case record mode is graph mode, you can select record zone for to graph measuring value when recording.
Set range is set accoridng to the set value of ‘8.5.6 Divide Zone (Record zone division)’ from
RECORD SETUP .
If the set is ‘None’, record zone is full width(100mm) of recording paper.
Set range: None, 1 ↔ Zone n (n: set value of Divide Zone (Record zone division))
Factory default: None
58 © Copyright Reserved KONICS Co., Ltd.
8.1.6 Tag Name (Channel name)
8 Parameter detail setup
Designate channel name with virtual keyboard.
You can enter max. 6 characters with English capital letters, English small letters, and speical characters.
Set range: 1 to 6 characters
Factory default: CH-1 to CH-12(Channel number by slot)
Some special character may be printed in low quality due to low print resolution.
8.1.7 Input Type (Input specification)
Set input specification of channel.
Set input speicfication is total 27 such as thermocouple, RTD, voltage, and current. For more
details, please refer to ‘2.3 Input specification and measuring range’. For jumper pin setting of
universal input card (KRN-UI2) by inpust specification, refer to ‘4.2 I/O card’.
Set range: Refer to ‘2.3 Input specification and measuring range’
Factory default: TC-K
8.1.8 Range/Scale Point (Decimal point)
In case Input Type(Input specification) is temperature sensor(thermocouple, RTD), set wheter to display decimal point to measuring value. In case analog(voltage, current), set decimal point position of Low Scale(Lower limit scalevalue), High Scale(Upper limit scale value).
Set range
In case Input Type(Input specification) is temperature sensor(thermocouple, RTD): 0 ↔ 0.0
In case analog(current, voltage): 0 ↔ 0.0 ↔ 0.00 ↔ 0.000 ↔ 0.0000
Factory default: 0.0
If you want high accuracy display, select ‘0.0(decimal point)’. If you want to stable accuracy display, select ‘0 (no dicimal point)’.
© Copyright Reserved KONICS Co., Ltd. 59
8 Parameter detail setup
8.1.9 Display/Temp Unit (Display unit/Temperature unit)
In case Input Type(Input specification) is temperature sensor(thermocouple, RTD), temperature unit is activated. In case analog(current, voltage), display unit is actiaved.
6
7
8
9 l
10 ml
11 t cal j
Btu
12 gal
13 lb
14 oz
15 barrel
16 -
3
4
5
Set range
In case Input Type(Input specification) is temperature sensor(thermocouple, RTD): ℃ ↔ ℉ ↔ ˚K
In case analog : Refer to below table.
Factory default: ℃
Set range in case analog (current, voltage)
No Unit
1 °C
2 °F
°K
Kcal/m
3
Kcal
19
20
21
No Unit
17 %
18 Wt% mass%
Vol% ppm
34
35
36
No Unit
32 V
33 mV
µV kV
□
50
51
52
No Unit
48 mA
49 A kg/cm
2
Pa kPa
28
29
30
31
32
25
26
27
22
23
24 ppb mol
Blank lx cd lm cd/m
2 rpm
Hz m
2
/s cp kW
MW
Var kVar
MVar
µs
VA
W m□
µ□ s
43
44
45
46
47
40
41
42
37
38
39
59
60
61
62
63
56
57
58
53
54
55
MPa
N/m
2
N/mm
2 inH
2
O mmH
2
O bar
Torr mmHg mmAq psi
Blank
70
71
72
66
67
68
69
73
No Unit
64 User0
65 User1
User2
User3
User4
User5
User6
User7
User8
User9
You can use user-defined unit image by selecting user-defined (User0 to User9) unit. Please
refer to ‘9.3.2 User unit setting’.
The unit with multiplier such as kg/cm low print resolution.
2
or complicated unit may be printed in low quality due to
60 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
8.1.10 High/Low Range & Graph Scale(Upper/Lower limit input value and graph scale value)
Set the actual used input range (Lower limit input value/Upper limit input value) in analog input.
If input range becomes small, the resoultion also becomes low in proportion to total range.
Decimal point position is changed by ‘Scale Point(Scale decimal point position)’ setting.
(1) Low Range (Lower limit input value)
Set the actual used lower limit input value within input range of Input Type(Input specification).
Set range: Min. input range value to upper limit input value(High Range) – F.S. 5%
In case input range is 0 to 100℃, set range is 0 to 95℃.
Factory default: -
(2) High Range (Upper limit input value)
Set the actual used upper limit input value within input range of Input Type(Input specification).
Set range: Lower limit input value(Low Range) + F.S. 5% to max. input range value
In case input range is 0 to 100℃, set range is 5 to 100℃.
Factory default: -
Set the displayed graph scale value on recording paper and LCD in temperature sensor input type (Thermocouple, RTD), (They does not displayed in analog input type.).
You can designate the record range and record specific section as detail graph by these parameters. ( If graph scale range is small, resoultion is also lower in proportion to recording range.)
(3) Low Graph Scale (Lower limit graph scale value)
Within the input range of Input Type (Input specification), set lower limit graph scale value.
Set range: Min. value of input range to upper limit graph scale value (High Graph
Scale) – F.S. 5%
When TC-K input range is -200.0 to 1350℃, set range is -200.0 to 1272.5℃.
Factory default: -200.0
© Copyright Reserved KONICS Co., Ltd. 61
8 Parameter detail setup
(4) High Graph Scale (Upper limit graph scale value)
62
Within the input range of Input Type (Input specification), set upper limit graph scale value.
They does not displayed in analog input type.
Set range: Lower limit graph scale value (Low Graph Scale) + F.S. 5% to Max. value of input range
When TC-K input range is -200.0 to 1350℃, set range is -122.5 to 1272.5℃.
Factory default: 1350.0
© Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
8.1.11 Low Scale/High Scale (Lower limit/Upper limit scale value)
This function is for set the desired display value based on measuring value. It is applied to analog (voltage, current) input type only.
As below figure, for example, measuring input value are ‘a’ and ‘b’ and the desired display value are ‘A’ and ‘B’ . In this case, about the input ‘a’ and ‘b’, it displays a=A, b=B as linearly.
You can change display value about min./max. input value of measuring value.
In case input specification is 0 to 20 ㎃
Set Low Scale (Lower limit scale value) = 0.0, High Scale (Upper limit scale value) = 10.0,
20.0, 30.0, -20.0.
Set Low Scale (Lower limit scale value) = 20.0, High Scale (Upper limit scale value) = -20.0.
© Copyright Reserved KONICS Co., Ltd. 63
8 Parameter detail setup
Set Low Scale (Lower limit scale value) = -20.0, High Scale (Upper limit scale value) = 20.0.
(1) Low Scale(Lower limit scale value)
Set scale value for lower limit input value (Low Range).
Set range: -99999 to 99999 ↔ -9999.9 to 9999.9 ↔ -999.99 to 999.99 ↔ -99.999 to
99.999 ↔ -9.9999 to 9.9999 (Depending on Scale Point setting, the range is different.)
Factory default: -
(2) High Scale(Upper limit scale value)
64
Set scale value for upper limit input value (High Range).
Set range: -99999 to 99999 ↔ -9999.9 to 9999.9 ↔ -999.99 to 999.99 ↔ -99.999 to
99.999 ↔ -9.9999 to 9.9999 (Depending on Scale Point setting, the range is different.)
Factory default: -
© Copyright Reserved KONICS Co., Ltd.
8.1.12 Special Function (Special function)
8 Parameter detail setup
It dispalys the applied measuring value of the set special function.
Depending on Input Type(Input specification), appliable special function is different.
Set range
When input type(input specification) is temperature sensor (thermocouple, RTD): None ↔ Difference analog (voltage, current): Linear ↔ Root ↔ Squre ↔ Two Unit (Two Unit is displayed when Input Type (input specification) is set as 0 to 20 ㎃, 4 to 20 ㎃.)
Factory default: None
Below graph’s patterns are liner, root, square for analog input.
Lower limit input value: -5V, Upper limit input value: +5V, Lower limit scale: -1000, Upper limit scale: 1000
© Copyright Reserved KONICS Co., Ltd. 65
8 Parameter detail setup
(1) Difference(Deviation)
It is available to set when Input Type(input specification) is temperature sensor
(thermocouple, RTD). It displays the deviation of Reference Channel (Reference channel) measuring value.
(Display value = standard channel measuring value – reference channel measuring value)
66
The set channel as analog (current, voltage) of Input Type (Input specification) is not able to set as Reference Channel (reference channel).
If there is no set reference channel, it displays standard channel measuring value.
If any one of reference channel, or standard channel is break (BURN), upper limit value (HHHH), lower limit value(LLLL) status, it displays as correspond value. If you select the channel which is used Difference function as reference channel, it displays the value based on calculating actual measuring value, not display value of reference channel.
(2) Linear
It applies lower limit scale and upper limit scale to lower limit input value and upper limit input value and displays this values.
In case lower limit input value: -5V, Upper limit input value: +5V and in case lower limit scale: -1000, upper limit scale: 1000 if current input value is 2V, display value is 400.
Display value =
Input value −Lower limit input value
× (Upper limit scale − Lower limit scale) +
Upper limit input value −Lower limit input value
Lower limit scale
400 =
7
10 × 2000 − 1000
(3) Root
In case voltage, current input type, this mode is used when input value is calculated by Root
( √ ) for the desired display value. Differential pressure signal of differential pressure flow meter is calculated Root(
√ ) for the to-be measured flux. This function is used to measure flux by input value.
In case lower limit input value: -5V, upper limit input value: +5V and in case lower limit scale: -1000, upper limit scale: 1000, if current input value is 2V, display value is approx. 673.32.
Display value =
�
Input value −Lower limit input value
Upper limit input value −Lower limit input value
Lower limit scale
× (Upper limit scale − Lower limit scale) +
673.32 = �
7
10
× 2000 − 1000
© Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
(4) Square
In case of voltage, current input type, this mode is used when input value is calculated by square for the desired display value. Reverse of Root, flux signal is calculated by square for differential pressure signal.
In case lower limit range: -5V, upper limit range: +5V and in case lower limit scale: -1000, upper limit scale: 1000, if current input value is 2V, display value is -20.
Display value
Input value − Lower limit input value
�
2
= �
Upper limit input value − Lower limit input value
× (Upper limit scale − Lower limit scale) + Lower limit scale
−20 = �
7
10�
2
× 2000 − 1000
(5) Two Unit
For compound pressure, if input pressure is lower than atmospheric pressure(0), it displays the degree of a vacuum with ㎜ Hg unit. If input pressure is higher than or same as atmospheric pressure(0), it displays positive pressure with kg/㎠ unit.
When using Two Unit function, lower limit value is fixed as -760mmHg and kg/cm
2
value is able to set within set range 1 to 35.
Two Unit limits scale point as 0 □ 0.0 □ 0.00. When using Two Unit, display unit is automatically changed as mmHg or kg/cm
2
.
The calculation with Record Method (Data storage method) and Filter type (Input digital filter) is impossible and ignored due to different type of two unit value.
Set range: 1 to 35
Factory default: -
© Copyright Reserved KONICS Co., Ltd. 67
8 Parameter detail setup
68
If pressure range is -760mmHg to 3kg/cm
2
, and pressure transmitter outputs 4 to 20 ㎃, for 4 ㎃ input it displays -760 mmHg, 8mA input is unit changing point. For 20 ㎃ input, it displays
3kg/cm
2
.
Range
Unit changing point (㎃)
-760mmHg to 1kg/cm2 12.130
-760mmHg to 5kg/cm2 6.740
-760mmHg to 10kg/cm2 5.498
-760mmHg to 15kg/cm2 5.031
-760mmHg to 20kg/cm2 4.786
-760mmHg to 25kg/cm2 4.635
-760mmHg to 30kg/cm2 4.533
-760mmHg to 35kg/cm2 4.459
Unit changing point = (
16
X
16
X+1.033
× Y) + 4
4 to 20 ㎃ output interval
Max. pressure range value (Ex. For 760 to 3 kg/cm
2
, it is " 3 ". )
1.033 Converted value from 760 mmHg to kg/cm
2
unit value (same unit)
Y Use pressure + 1.033 (Ex. Use pressure is ‘0’, Y is 1.033.)
4
Output value for zero, 4.00 ㎃
Set range
In case Input Type(Input specification) is temperature sensor(thermocouple, RTD): None ↔
Difference
In case Input Type(Input specification) is analog(voltage, current): Linear ↔ Root ↔
Square ↔ Two Unit (Two Unit is activated for current input(0 to 20 ㎃, 4 to 20 ㎃).)
Factory default: None
© Copyright Reserved KONICS Co., Ltd.
8.1.13 Reference Channel (Reference channel)
8 Parameter detail setup
In case Input Type(Input specification) is temperature sensor(thermocouple, RTD), set Special
Function(special function) as Difference to set reference channel.
Set range: None / CH
□-S□UI-□
Factory default: -
8.1.14 Input Bias(Error correction)
This function is for error correction from input (thermocouple, RTD, voltage, current) not from this recorder.
When temperature sensor cannot be installed near measured subject, there may be the temperature deviation between temperature sensor area and measured subject area. This function calculates and corrects this errors. Several kinds of temperature sensor has specified grade. High accuracy type is high price and ordinary product is generally used. To correct input by measuring error from each helps more accurate temperature measurement.
For using this error correction function, you should accurately measure the deviation from input part , at first. If this deviation is not correct, the error may be higher.
Set range: -9999 to 9999 ↔ -999.9 to 999.9 ↔ -99.99 to 99.99 ↔ -9.999 to 9.999
↔ -0.9999 to 0.9999 (Depending on the set scale point, range is different.)
Factory default: 0.0
In case actual temperature is 80℃ but display temprature from recorder is 78℃, set Input
Bias(Error correction) as ‘2’ and display temperature is 80℃.
© Copyright Reserved KONICS Co., Ltd. 69
8 Parameter detail setup
8.1.15 Span (Gradient adjustment)
This menu is for adjusting upper limit error by regulating display value which is about measuring value or applied scale.
In case Low Scale(Lower limit scale value) and High Scale(Upper limit scale value) are fixed, and Span (Gradient adjustment) is only set. When Input range is 0 to 10V, Low Scale(Lower limit scale) value is 0.00, and High Scale(Upper limit scale) value is 10.00.
If changing gradient adjustment value as 0.500, 1.000 or 1.500, display value by each changed gradient adjustment value is below.
Lower limit scale value
0.00
0.00
0.00
Upper limit scale value
10.00
10.00
10.00
Gradient adjustment value
0.500
1.000
1.500
Range of display value
0.00 to 5.00
0.00 to 10.00
0.00 to 15.00
Same result
=
Lower limit scale value
0.00
0.00
0.00
Upper limit scale value
5.00
10.00
15.00
Gradient adjustment value
1.000
1.000
1.000
70
In case Low Scale(Lower limit scale value) and High(Upper limit scalevalue) are fixed, and Span
(Gradient adjustment) is only set (reverse gradient). When Input range is 0 to 10V, Low
Scale(Lower limit scale) value is 10.00, High Scale(Upper limit scale) value is 0.00.
If changing gradient adjustment value as 0.500, 1.000, or 1.500, display value by each changed gradient adjustment value is below.
Lower limit scale value
10.00
10.00
10.00
Upper limit scale value
0.00
0.00
0.00
Gradient adjustment value
0.500
1.000
1.500
Range of display value
10.00 to 5.00
10.00 to 0.00
10.00 to -5.00
Same result
=
Lower limit scale value
10.00
10.00
10.00
Upper limit scale value
5.00
0.00
-5.00
Gradient adjustment value
1.000
1.000
1.000
© Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
8.1.16 Record Method (Data storage method)
Set storage method for measured data by channel to inner/external memory.
Display and print method is Record Method.
Set value
Instant(Instant value)
Description
Saves measuring value by every record period (Log Speed)
Average(Average value) Saves averaged measuring value during record period (Log Speed).
Minimum(Min. value)
Maximum(Max. value)
Saves min. measuring value during record period (Log Speed).
Saves max. measuring value during record period (Log Speed).
Set range: Instant ↔ Average ↔ Minimum ↔ Maximum
Factory default: Instant
8.1.17 Filter Type (Input digital filter)
In some applications the fluctuating measuring input causes the display value to fluctuate. In this case accurate display/record is disable. This function is able to make display value stable by input digital filter.
Input digital filter uses moving average method (Moving Average Filter). It does not affet to display period but display value may be different with input value.
Set range: None ↔ Moving
Factory default: None
© Copyright Reserved KONICS Co., Ltd. 71
8 Parameter detail setup
8.1.18 Filter Counter (The number of digital filter)
Designate the number of sampling which apply to digital filter.
When you set Filter Type(Input digital filter), this parameter is activated.
Set range: 1 to 128
Factory default: -
When the set value of input digital filter is ‘4’, it does moving average input sampling values for
0.1 sec (100ms) and displays this value.
D1=S1
D2 =
S1 + S2
2
, D3 =
S1 + S2 + S3
3
Display values of D1, D2, D3 is the initial operation before averaging 4 sampling values.
D4 =
D6 =
D8 =
S1 + S2 + S3 + S4
4
, D5 =
S3 + S4 + S5 + S6
4
, D7 =
S5 + S6 + S7 + S8
4
S2 + S3 + S4 + S5
4
S4 + S5 + S6 + S7
4
72 © Copyright Reserved KONICS Co., Ltd.
8.1.19 Burnout Action (Display setting for break)
8 Parameter detail setup
In case Input Type(Input specification) is temperature sensor(thermocouple, RTD), set alarm operation and alarm option for break input. (In case Input Type(Input specification) is analog(voltage, current), this function does not operate.)
Set value
OFF
Up Scale
Down Scale
Description
When input break, after moving display value downward or upward according to circuit structure
※ 1
(max. or min. value in graph record state) it displays BURN.
When input break, after moving display value only upward (records max. value in graph record state) it displays BURN.
When input break, after moving display value only downward (records min. value in graph record state) it displays BURN.
Set range: OFF ↔ Up Scale ↔ Down Scale
Factory default: OFF
According to circuit structure, when thermocouple(Thermo Couple) temperature sensor,
RTD(RTD) temperature sensor’s A-B terminal or voltage input ±60mV, ±200mV input is break, it displays Down Scale.
When RTD(RTD) temperature sensor’s B-B' terminal input is break, it displays Up Scale.
© Copyright Reserved KONICS Co., Ltd. 73
8 Parameter detail setup
8.2
ALARM SETUP (Alarm setting)
You can set alarm output specification such as alarm operation mode and alarm option by input channel, alarm ON/OFF delay, alarm output relay, relay contact, etc.
Move to ALARM SETUP with , keys, press key to enter ALARM SETUP.
74
Parameter list
Parameter Set range
Select UI Card (Select universal card input) CH□-S□UI-□
Alarm Set Copy (Copy alarm parameter)
No Select/ CH□-S□UI-□
Alarm□ Type(Alarm□ operation mode)
OFF ↔ PV.Hi ↔ PV.Lo ↔ DV.Hi
↔ DV.Lo ↔ SBA ↔ P.END
Alarm□ Ref Channel(Alarm□ reference channel)
Alarm□ Value(Alarm□ set value)
None / CH□-S□UI-□
None ↔ Latch ↔ StBy ↔ La+St
F.S. of INPUT TYPE by channel
Unit
-
-
-
-
-
Digit
Alarm□ Hysteresis(Alarm□ hysteresis) ※1
F.S. of INPUT TYPE by channel
Alarm□ ON/OFF Delay(Alarm□ ON/OFF output delay time) ※1
0 to 3600
Alarm□ Alarm No(Alarm□ output alarm number) ※1
Select Alarm Card(Select alarm output card)
None / S□AO-□
-
Alarm-□ Status(Relay and TR output method) ※1
Digit sec
-
-
N.O.↔N.C.
N.O.↔N.C.
N.O.↔N.C.
N.O.↔N.C.
N.O.↔N.C.
When connecting Relay type KRN-AR4
(alarm output card), AL1 to AL4 are activated.
When connecting TR type KRN-AT6
(alarm output card), AL1 to AL6 are activated.
N.O.↔N.C.
None
Automaticall y set
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
None
Alarm1
Value:
1350.0
Alarm2
Value to
Alarm4
Value: -
0.0
Factory default
Automaticall y set
CH Select
Alarm1
Type: PV.Hi
Alarm2
Type to
Alarm4
Type: None
-
0s
© Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
※1.
Alarm□ Type to Alarm□ Alarm No parameters are displayed as the number of connected alarm output card.
※Shaded parameters are affected by set value of other parameters. Please refer to specific descriptions of each parameter.
8.2.1 Select UI Card (Select universal card input)
Select the channel of universal input card (KRN-UI2) to be set.
One universal input card has two channels.
KRN100 automatically searches connected input/output card on slot power when power ON and recognizes the number of universal input card(KRN-UI2).
Set range: CH□-S□UI-□(Activated connected universal input(2 channels per input card))
Factory default: Automatically set
8.2.2 Alarm Set Copy (Copy alarm parameter)
You do not need to set same parameter settings repeatedly for other channels. This function is to copy set value of alarm parameter of the set channel and applys it to other channels.
Copiable parameters are as below.
Alarm□ Type
(Alarm□ operation mode)
Alarm□ Ref Channel
(Alarm□ reference channel)
Alarm□ Option
(Alarm□ option)
Alarm□ Value
(Alarm□ Set value)
Alarm□ Hysteresis
(Alarm□ hysteresis)
Alarm□ ON Delay
(Alarm□ ON delay time)
Alarm□ OFF Delay
(Alarm□ OFF delay time)
Alarm□ Alarm No
(Alarm□ output relay number)
Set range: No Select/CH□-S□UI-□(Activated connected universal input(2 channels per input card)
Factory default: CH Select
© Copyright Reserved KONICS Co., Ltd. 75
8 Parameter detail setup
8.2.3
Alarm□ Type(Alarm□ operation mode)
76
Designate alarm operation when alarm ON.
You can set up to 4 operations by each channel and alarm operations are as below.
Type Record Alarm operation
1 No alarm - -
2
3
4
5
6
Absolute value upper limit alarm
Absolute value lower limit alarm
Deviation upper limit alarm
Deviation lower limit alarm
Input break alarm
PV.Hi
(▲)
PV.Lo
(▼)
DV.Hi
(△)
DV.Lo
(▽)
SBA
(S)
Description
-
Alarm set value: 90℃ If display value is same or higher than alarm set value, alarm output turns ON.
Alarm set value: 90℃
If display value is same or lower than alarm set value, alarm output turns ON.
Alarm set value:
-10℃
Alarm set value:
10℃
Alarm set value:
10℃
Alarm set value:
-10℃
If the deviation between display value and the display value of reference channel is same or higher than alarm set value, alarm output turns ON.
If the deviation between display value and the display value of reference channel is same or lower than alarm set value, alarm output turns ON.
In case input is not connected, or input cable is break during controlling, alarm output turns ON. You can check whether input cable is break by external contact of alarm output using buzzer or other devices.
7
No recording paper alarm
P.End
(P)
In case of no recording paper during recording, record operation stops and this alarm output turns ON. (Measuring value is saved at system memory automatically.)
Alarm is automatically cleared when recording paper is replaced (in case of general alarm). P.END BACKUP PRINT window is activated and it is available to output backup data.
© Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
※ H: Alarm output hysteresis(Hysteresis)
If even one alarm occurs, alarm ON icon marks the specified channel to check whether alarm has occurred.
(1) Record Mode(Record mode) is Graph
It records alarm sign, alarm operation mode, and occurrence time on recording paper with the set record color in 'Pen Color' of INPUT SETUP. Alarm sign is recorded at alarm set value position.
Alarm ON from 1 channel,
Alarm ON at the same time from over 2 channels,
Over 2 alarms ON from 1 channel,
Records alarm sign of corresponding channel’s graph.
Records also alarm and time information at right.
Records alarm sign of corresponding channel’s graph. Records only time information at right.
Records alarm sign and ‘CH1 AL-□(the number of alarm)
14:00:33’ form.
If alarm occurs at digital memo time, memo information includes alarm information.
Therefore, as below figure, alarm sign, alarm information, time information is not recorded and is replaced as digital memo.
[Alarm sign]
No. Name
1 Absolute value upper limit alarm
2 Absolute value lower limit alarm
3 Deviation upper limit alarm
4
5
6
Deviation lower limit alarm
Input break alarm
No recording paper
© Copyright Reserved KONICS Co., Ltd.
▽
S
P
Alarm sign
▲
▼
△
77
8 Parameter detail setup
(2) Record Mode(Record mode) is Digital
It records alarm ON channel, data information, alarm abbreviation, time with the set record color of corresponding channel.
In front of ON time, as below, ‘A’ is marked to mean the data by alarm.
3
4
5
6
After alarm recording, if it maintains same alarm or alarm is cleared, it does not record the relevant data.
In case of record by digital memo, it prints alarm abbreviation of occurring alarm as below.
No. Name
Alarm abbreviation Note
1 Absolute value upper limit alarm PH -
2 Absolute value lower limit alarm PL -
7
Deviation upper limit alarm
Deviation lower limit alarm
Input break alarm
No recording paper
Several alarm ON
DH
DL
SB
PE
AL
-
-
-
-
It is used when printing 2 channels in one line.
Set range: OFF ↔ PV.Hi ↔ PV.Lo ↔ DV.Hi ↔ DV.Lo ↔ SBA ↔ P.End
Factory default
Alarm1 Type: PV.Hi, Alarm2 Type to Alarm4 Type: None
8.2.4
Alarm□ Ref Channel(Alarm□ reference channel)
Designate reference channel which is standard of deviation upper limit alarm(DV.Hi) or deviation lower limit alarm(DV.Lo).
If display value of relevant channel is lower than the display value of set reference channel, deviation upper limit alarm or deviation lower limit alarm turns ON.
This parameter is activated when Alarm□ Type(Alarm operation mode) is set as deviation upper limit alarm(DV.Hi) or deviation lower limit alarm(DV.Lo).
Set range: None / CH□-S□UI-□
Factory default: -
78 © Copyright Reserved KONICS Co., Ltd.
8.2.5
Alarm□ Option(Alarm□ option)
8 Parameter detail setup
Set alarm output by alarm operation.
Set value Description
None
Standard alarm
If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output is OFF.
Latch
StBy
※
※
2
1
Alarm latch
Standby sequence
If it is an alarm condition, alarm output is ON and maintains ON status.
(Alarm output HOLD)
First alarm condition is ignored and from second alarm condition, standard alarm operates.
La+St
Alarm latch and standby sequence
If it is an alarm condition, it operates both alarm latch and standby sequence. When power is supplied and it is an alarm condition, this first alarm condition is ignored and from the second alarm condition, alarm latch operates.
※1.
In case Alarm□ Type (Alarm□ operation mode) is SBA(Input break alarm) or P.End(No recording paper alarm), you can only select Latch(Alarm latch).
※2.
Condition of re-applied standby sequence: Power ON, changing the set alarm temperature, forced alarm reset.
Set range: None↔Latch↔StBy↔La+St
Factory default: None
In case for input break alarm(SBA), no recording paper alarm (P.END), standby sequence, or alarm latch and standby sequence option does not operates and you cannot set it.
In case of alarm by alarm latch, to reset alarm output, press key for 3 sec at not alarm condition, use alarm reset function by digital input, or turn OFF the power and ON.
To reset alarm output by digital input, DI-□ Type(Select digital input□) from DIGITAL INPUT
SETUP is should be set as ‘Alarm Reset’.
Reset alarm output is available only when alarm option is set as alarm latch or alarm latch and standby sequence, or when current temperature is out of alarm operation range. At the next alarm output ON, alarm output operates normally.
Alarm□ Type(Alarm□ operation mode): PV.Lo (Absolute value lower limit alarm)
Alarm□ Value(Alarm□ set value): 90
Alarm□ Hysteresis(Alarm□ hysteresis): 5
Alarm□ Option(Alarm□ option): StBy(Standby sequence)
© Copyright Reserved KONICS Co., Ltd. 79
8 Parameter detail setup
When power is ON, it is alarm condition and it is ignored. From second alarm conditions, it operates as standard alarm.
8.2.6
Alarm□ Value(Alarm□ set value)
Set alarm set value based on alarm output operation mode, it executes alarm operation.
Set range: Using set input from Input Type(Input specification)/within display range
Factory default: Alarm1 value: 1350.0, Alarm2 Value to Alarm4 Value: -
80 © Copyright Reserved KONICS Co., Ltd.
8.2.7
Alarm□ Hysteresis(Alarm□ hysteresis)
8 Parameter detail setup
Set the interval between alarm output ON and OFF.
If PV is over or below alarm output SV, output turns ON and it sets OFF time by hysteresis settings.
When input value is changed near SV, alarm output is often. Set hysteresis and it can be prevent from often alarm output.
Set range: 0.0 to 9999.9 (Decimal point position is different by the set decimal point position of input.)
Factory default: 0.0
The below graph is when Alarm□ Type(Alarm□ operation mode) is set as absolute value upper limit alarm, Alarm□ Value(Alarm□ set value) is set as 200, and Alarm□
Hysteresis(Alarm□ hysteresis) is set as 10.
© Copyright Reserved KONICS Co., Ltd. 81
8 Parameter detail setup
8.2.8
Alarm□ ON/OFF Delay(Alarm□ ON/OFF output delay time)
Set delay time (unit: sec.) to prevent alarm malfunction by wrong input from external disturbance and noise.
Item
Alarm On Delay
Alarm OFF Delay
Description
Even after standby the set time when alarm ON condition (alarm ON channel flashes on screen), if it is still alarm condition, alarm output turns
ON. (Alarm ON channel flashes on screen).
Even after standby the set time when alarm reset condition (alarm ON channel display is hold), if it is still alarm reset condition, alarm output turns
OFF. (Alarm ON channel resets the display.)
Set range: 0 to 3600
Factory default: 0s
82 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
8.2.9
Alarm□ Alarm No(Alarm□ output alarm number)
Select alarm output number to output alarm in alarm ON.
If the setting as ‘None’ and when alarm operation occurs, it displays alarm on the screen and records alarm operation mode, and alarm occurrence time on recording paper, but it does not output alarm.
There are two alarm output types; TR and RELAY output. KRN recognizes automatically the connected type and displays it.
In this parameter, TR output type is displayed as TR-S□AL-□(□), and RELAY output type is displayed as RELAY-S□AL-□(□).
These parameter’s meaning is as below.
S□: The number of module connected SLOT,
AL-□: Alarm output channel number,
Number in parenthesis ‘(□)’: the number of designated alarm as output in the specified channel
Set range: None / □-S□AO-□(□)
Factory default: None
8.2.10 Select Alarm Card(Select alarm output card)
Select alarm output card(KRN-AR4, KRN-AT6) to set output type (Normally Open, Normally
Closed) of alarm output. In front of output card name, RELAY or TR abbreviation is displayed for easy to know connected module type when selecting output card.
© Copyright Reserved KONICS Co., Ltd. 83
8 Parameter detail setup
8.2.11 Alarm-□ Status(Relay and TR output method)
84
Set alarm output method (Normally Open, Normally Closed) of each alarm output channel from the set alarm output card in Select Alarm Card (Select alarm output card).
You can use alarm output as relay output or TR output by inserting the desired alarm output card(Relay output: KRN-AR4, TR output: KRN-AT6).
Set value
Description
Alarm occurrence
Alarm output
Relay TR
N.O.
Normally
Open
In normal status it is open.
If alarm occurs, it is closed.
OFF
ON
Contact Open TR OFF
Contact Close TR ON
N.C.
Normally
Closed
In normal status it is closed.
If alarm occurs, it is open.
OFF
ON
Contact Close TR ON
Contact Open TR OFF
This function displays as Alarm-□ Status and it is connected Relay or TR Type’s output card information. One card for relay has 4 outputs(Alarm-1 Status to Alarm-4 Status), for TR has 6 outputs (Alarm-1 Status to Alarm 6 Status).
Relay output card(KRN-AR4) is connectable up to 3, and TR output card (KRN-AT6) is connectable up to 2 at Slot7 to 10.
Alarm output turns ON or OFF by total 4 alarm conditions and relay, TR output are able to output by max. 48 alarm conditions. However, every relay output and TR output condition is OR operation (Among several alarm conditions connected one alarm output, even one alarm condition is met, output must turn ON.).
Set range: N.O. ↔ N.C.
Factory default: N.O.
REALY and TR type output is basically fixed as Normally Opened method and H/W when power is ON.
Therefore, KRN100 takes booting time max. 20sec and maintains Normally open status. In case of RUN mode after booting, it maintains use-defined output type; Normally Open or Normally
Closed.
© Copyright Reserved KONICS Co., Ltd.
8.3
8 Parameter detail setup
DIGITAL INPUT SETUP(Digital input setting)
You can set executing function by digital input card, operation stauts, etc.
Move to DIGITAL INPUT SETUP with
INPUT SETUP.
, keys, press key to enter DIGITAL
Parameter list
Parameter Set range
Select DI Card (Select digital input card)
S7DI ↔ S8DI ↔ S9DI ↔ S10DI
DI-□ Type (Select digital input □)
None ↔ Run ↔ Memo ↔ ListOut ↔ Speed ↔
Alarm Reset
DI-□ Reset No (Reset alarm number)
None ↔ ALL ↔ S□AL-□ -
-
Factory default
Automatically set
None
DI-□ Status (Operation status)
Edge ↔ Level
※Shaded parameters are affected by set value of other parameters. Please refer to specific descriptions of each parameter.
© Copyright Reserved KONICS Co., Ltd. 85
8 Parameter detail setup
8.3.1 Select DI Card (Select digital input card)
Select digital input card (KRN-DI6) to be selected.
KRN100 searches connected digital input card automatically on slot and recognizes the number of digital input card as soon as power is ON.
Channel name is as below.
S Slot number DI
Set range:
S7DI ↔ S8DI ↔ S9DI ↔ S10DI
Factory default: Automatically set
S9DI: This means connected digital input card on 9th slot
86 © Copyright Reserved KONICS Co., Ltd.
8.3.2
DI-□ Type (Select digital input □)
8 Parameter detail setup
Select digital input.
Operation description
Level
Open Short
Edge
Min. signal input
※1
Icon ※2
None - No function - - -
Run ※3
Start/Stop recording
Starts/Stops recording on recording paper.
STOP RUN
STOP↔RU
N
,
Memo Digital memo
ListOut List output
Executes digital memo function
Outputs parameter set information
-
-
-
-
Memo
ListOut
Speed
Record speed
(graph) and period (digital)
Executes to record with set option record speed and period (Option speed, period).
Standa rd
Option
Standard
↔Option
Alarm
Reset
Forced alarm reset
In case alarm option is alarm latch, alarm output is reset by force.
- - Alarm Reset
※1.
At every min. signal input width (over 0.3 sec.), it executes the function repeatedly.
※2.
The appropriate icon is displays on the screen, digital input function is operating.
※3.
When digital input operation status is set as Level in RUN mode, you cannot operate starting/stopping recording with front key. (If it set as ‘Edge’, front key operates starting/stopping recording.)
When reservation record(Reservation) is set and now is reservation recording state, digital input function is not available as RUN mode. This is available in record stop state by reservation record.
Set range: None ↔ Run ↔ Memo ↔ ListOut ↔ Speed ↔ Alarm Reset
Factory default: None
© Copyright Reserved KONICS Co., Ltd. 87
8 Parameter detail setup
8.3.3
DI-□ Reset No (Reset alarm number)
Select alarm to reset at digital input.
Set DI-□ Type(Select digital input□) as forced alarm recet (Alarm Reset), it is activated.
Alarm reset is available when alarm option is Alarm latch or Alarm latch and standby sequence and it is not alarm condition.
Set range: None↔ALL↔ S□-AL-□
Factory default: -
8.3.4
DI-□ Status (Operation status)
88
Designate operation status of set digital input.
Set value Description
Edge
When digital input is input over 0.3 sec., the set function operates. If digital input is reinput the reverse function operates.
Level
When digital input is short over 0.3 sec., the set function operates. If digital input is open over 0.3 sec., the operation is stop.
Set range: Edge ↔ Level(Please refer to ‘8.3.2 DI-□ Type (Select digital input □)’.)
Factory default: -
In digital input setting, when DI-□ Type is set as Run or Seed, and DI-□ Status is set as Edge, overlap setting is available. But DI-□ Status is set as Level, overlap setting is not available.
If even one Level is set, DI-□ Status’s overlap setting to Level or setting to Edge is not available.
In case DI-□ Status(operation status) is Edge: You can execute to start/stop recording with front key.
In case DI-□ Status(operation status) is Level: You cannot execute to start/stop recording with front key.
© Copyright Reserved KONICS Co., Ltd.
8.4
8 Parameter detail setup
COMMUNICATION SETUP (Communication setting)
Set the related parameters with communication output card(KRN-COM).
You can only check the item of COMMUNICATION SETUP by communication but cannot change the set.
This parameter is for setting and monitoring parameters from external upper system (PC and graph panel, etc) or transmitting the data to external devices by RS485, Ethernet, or USB Device communication
It is recommended to use our dedicated software program DAQMaster for monitoring. If you want to develop monitoring program not using our DAQMaster program or to use the related
Modbus program, please refer to user manual for communication.
Visit our homepage (www.konics.com) to download DAQMaster program, and user manual for communication.
Move to COMMUNICATION SETUP with
COMMUNICATION SETUP.
, keys, press key to enter
Parameter list
Parameter
Modbus Address (Communication address)
Set range
1 to 127
RS485 Port (Use RS485 communication)
Enable ↔ Disable
2400↔4800↔9600 ↔ 19200 ↔ 38400
Parity Bit (Communication parity bit)
None ↔ Odd ↔ Even
Stop Bit(Communication stop bit)
1 ↔ 2
Termination Set (Terminating resistance)
Response Wait Time (Communication response wait time)
Protocol (Communication protocol)
Disable ↔ Enable
5 to 99ms
Modbus RTU
RS485 Com Write (RS485 communication write)
Ethernet Port (Use Ethernet communication)
Default Gateway (Default gateway)
Enable↔Disable
Enable↔Disable
0.0.0.0 to 255.255.255.255
0.0.0.0 to 255.255.255.255
0.0.0.0 to 255.255.255.255
Ethernet Com Write (Ethernet communication write) Enable ↔ Disable
USB Device Port (Use USB communication)
Enable ↔ Disable
USB Com Write (USB communication write)
Enable ↔ Disable
KRN100 does not supports RS485 port, Ethernet port at the same time for preventing system overload. If you change one as ‘Enable’, the other is changed ‘Disable’ automatically.
In case USB Device, it is able to set 'Enable', 'Disable' regardless of RS485 or Ethernet setting.
Factory default
1
Enable
9600
None
2
Disable
20ms
Modbus RTU
Enable
-
-
Disable
-
-
Enable
Enable
© Copyright Reserved KONICS Co., Ltd. 89
8 Parameter detail setup
90
Interface
Item
Application standard
Max. connection
Communication distance
※
1
RS485
Compliance with EIA
RS485
31 units
(address: 1 to 127)
Max. 1Km
(Below 9600bps)
Ethernet
-
USB Device
Compliance with USB
V2.0
1 units
(number of occupations per a unit)
1 units
Single cable within
100m
(Recommended over
CAT5E)
Single cable within
1.5m
Communication method
Half Duplex Full Duplex -
Communication synchronization method
Communication speed
Communication response wait time
Start Bit
Data Bit
Asynchronous
2400/4800/9600/19200
/38400bps
5to99 ms
Asynchronous
10/100Mbps
-
Asynchronous
-
12Mbps(Full Speed)
1 bit(fixed)
8 bit(fixed)
-
-
-
-
Parity Bit
Stop Bit
None, Odd, Even
1, 2 bit
-
-
-
-
Protocol Modbus RTU Modbus TCP Modbus RTU
※1.
When connecting through the network such as network hub (HUB) and gateway, etc, there is no distance limit, but it is recommaned to use min. network.
Please use communication cables which is satisfied the below conditions.
RS485 communication
Shield Twist Pair over AWG24, characteristic impedance
100Ω, capacity component 50pF/m cable length max. 1km
Ethernet communication
USB Device communication
Over CAT5E, cable max. length: 100m
Single cable built-in ferrite core within 1.5m
USB Device communication may cause recognition error by external noise and environment during connecting PC. If there is error, please re-connect this.
Please use USB Device as for setting.
© Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
During communication, if you chaging the communication settings, it may cause communication error.
RS485 communication port of KRN100 is connected for 3 A, B, SG terminals.
SG terminal is connectable with shield or SG of converter, and you do not need to connect SG terminal.
To remove noise during RS485 communication, use shield cable. There are three methods for shield processing.
1
Connects shield cable only for
SG terminal of communication module.
When electric potential occurs between computer and recorder grounded, connect shield cable for SG terminal of recorder to minimize noise effect not to flow current on shield cable. (It is used generally.)
2
3
Connects shield for both SG terminal of communication module and the grounding of computer.
Connects shield for one of SG terminal of communication module or the grounding of computer.
When electric optional does not occur between computer and recorder grounded, it is effective to minimize noise influence.
It can minimize noise effect in case of connecting nonpolarity condenser in series.
It is recommended to use SCM-US 48I(USB/RS485 converter) or SCM-38I(RS232C/RS485 converter) for RS485 communication between PC and KRN100.
If using the non-grounded converter between FG and SG, it may cause damage to KRN100 and communication error by electric potential of between ground during long-distance communication.
For using terminating resistance, turn ON only terminal resistance of recoder on end of connected communication line (Enables to set using terminating resistance in communication set function), and also turn ON terminal resistance of connected communication to PC.
© Copyright Reserved KONICS Co., Ltd. 91
8 Parameter detail setup
8.4.1 Modbus Address (Communication address)
Designate communication address.
The designated communication address is able to apply to RS485, USB Device, also Ethernet communication. However, duplicated communication address setting in same communication line does not allow.
Set range: 1 to 127
Factory default: 1
8.4.2 RS485 Port (Use RS485 communication)
Set whether using RS485 communication.
If you set RS485 Port’s set value as ‘Enable’, Ethernet Port’s set value is changed ‘Disable’ automatically.
Set range: Enable ↔ Disable
Factory default: Enable
8.4.3 Baud Rate (Baud rate)
Designate baud rated.
Set range: 2400 ↔ 4800 ↔ 9600 ↔ 19200 ↔ 38400 (unit: bps)
Factory default: 9600
92 © Copyright Reserved KONICS Co., Ltd.
8.4.4 Parity Bit (Communication parity bit)
8 Parameter detail setup
Designate communication parity bit.
Set range: None ↔ Odd ↔ Even
Factory default: None
8.4.5 Stop Bit(Communication stop bit)
Designate communication stop bit.
Set range: 1 ↔ 2 (unit: bps)
Factory default: 2
8.4.6 Termination Set (Terminating resistance)
Desigante wheter using terminating resistance .
You do not need to external terminating resistance (120Ω) because KRN100 is enable to use terminating resistance by parameter setting.
Set range: Enable □ Disable
Factory default: Disable
© Copyright Reserved KONICS Co., Ltd. 93
8 Parameter detail setup
8.4.7 Response Wait Time (Communication response wait time)
To prevent possible error due to communicating with low speed Master (PC, PLC, etc), set communication response wait time.
If you set too short communication response wait time, communication error may occur in Master.
Set range: 5 to 99 (unit: ms)
Factory default: 20ms
8.4.8 Protocol (Communication protocol)
It supports Modbus RTU(Remote Terminal Uint) as communication protocol.
(Data Length: 8bit, Data interval: 24bits or less,Error Detection: CRC-16)
Set range: Modbus RTU
Factory default: Modbus RTU
8.4.9 RS485 Com Write (RS485 communication write)
Set whether changing the set value of KRN100 parameter by RS485 communication.
To read the set value of each parameter is available regardless of the communication write enable/disable setting.
Set range : Enable ↔ Disable
Factory default : Enable
94 © Copyright Reserved KONICS Co., Ltd.
8.4.10 Ethernet Port (Use Ethernet communication)
8 Parameter detail setup
Set whether using Ethernet communication.
If you set Ethernet Port as ‘Enable’, RS485 Port is changed as ‘Disable’ automatically.
Set range: Enable ↔ Disable
Factory default: Disable
You can monitor or set parameter KRN100 with DAQMaster or the related Modbus program
(Modbus Poll, etc). For more information, refer to ‘KRN100 user manual for communication.’
[Modbus TCP communication]
The following is based on Windows XP.
1st
First of all connect Ethernet slot of KRN-100 communication output card (KRN-COM) and LAN slot of PC with LAN cable.
2nd
Execute Start > Run to check IP address of PC.
© Copyright Reserved KONICS Co., Ltd. 95
8 Parameter detail setup
3rd
Enter “ipconfig” at “Open” in Run dialog box and you can check IP address of PC.
4th
Set KRN100 Ethernet Port(Use Ethernet communication) as ‘Enable’ at
COMMUNICATION SETUP (Communication setting) of KRN100. Set IP Address(IP address) as installation environment.
IP Address
PC
192.168.1.1
Subnet Mask 255.255.255.0
Default Gateway 192.168.1.1
KRN100
192.168.1.2
96
IP address set for Modbus TCP communication is complete.
© Copyright Reserved KONICS Co., Ltd.
8.4.11 IP Address (IP address)
8 Parameter detail setup
Designate used IP address to identify the device on the network.
If there is same IP address on the network, communication does not operate by IP conflict.
Set range: 0.0.0.0 to 255.255.255.255
Factory default: -
8.4.12 Subnet Mask (Subnet Mask)
To recognize network ID part and host ID part of IP address, set 32 bit address allowing to IP packet receiver.
, keys, it displays inputable subnet To enter correct set value, whenever press mask value is displayed.
Set range: 0.0.0.0 to 255.255.255.255
Factory default: -
8.4.13 Default Gateway (Default gateway)
Designate IP address to connect IP router directly.
Set range: 0.0.0.0 to 255.255.255.255
Factory default: -
© Copyright Reserved KONICS Co., Ltd. 97
8 Parameter detail setup
8.4.14 Ethernet Com Write (Ethernet communication write)
Set whether changing the set value of KRN100 parameter by Ethernet communication.
To read the set value of each parameter is available regardless of the communication write enable/disable setting.
Set range: Enable ↔ Disable
Factory default: -
8.4.15 USB Device Port (Use USB communication)
Set whether using USBcommunication.
USB communication is available regardless of RS485 Port or Ethernet Port setting.
Set range: Enable ↔ Disable
Factory default: Enable
8.4.16 USB Com Write (USB communication write)
98
Set whether changing the set value of KRN100 parameter by USB communication.
To read the set value of each parameter is available regardless of the communication write enable/disable setting.
Set range: Enable ↔ Disable
Factory default: Enable
© Copyright Reserved KONICS Co., Ltd.
8.5
8 Parameter detail setup
RECORD SETUP (Record setting)
You can set record mode, record speed, record language, and digital memo, etc.
Depending on record mode (Digital, Graph), below parameters are changed.
Move to RECORD SETUP with
SETUP.
, keys, press key to enter RECORD
Parameter list
Parameter Set range Factory default
Digital Print type (1 line record channel during numeric recording)
Standard Speed (Standard record speed)
Graph ↔ Digital
OneCH ↔ TwoCH
Graph
TwoCH
10 ↔ 20 ↔ 40 ↔ 60 ↔ 120 ↔ 240mm/h 20mm/h
Option Speed (Option record speed)
10 ↔ 20 ↔ 40 ↔ 60 ↔ 120 ↔ 240mm/h 20mm/h
Memo Period (Digital memo period)
Divide Zone (Record zone division)
Standard Period (Standard record period)
Option Period (Option record period)
Listing Language (Language for list output)
Alarm Speed (Alarm record speed)
Refer to detail descriptions.
None, 2 to 12
00m01s to 99m99s
00m01s to 99m99s
Korea ↔ English
2hour
None
-
-
English
10 ↔ 20 ↔ 40 ↔ 60 ↔ 120 ↔ 240mm/h 20mm/h
Power On Status (Record status when power ON)
Hold ↔ Run ↔ Stop Hold
Run Status (List printing at start recording)
List Out Option (List record option)
Zone Dot Line Distance (Dot line for zone division)
CH Print Distance (Record interval for each channel graph)
Start Line Print (Start line when starting record)
OFF ↔ ON
Standard ↔ Option
None to 8.0mm
None to 100.0mm
ON ↔ OFF
Range Print Time (Input range record period)
Disable,1to 24 hour
OFF
Standard
4.0mm
20.0mm
ON
Disable
※ Shaded parameters are affected by set value of other parameters. Please refer to specific descriptions of each parameter.
© Copyright Reserved KONICS Co., Ltd. 99
8 Parameter detail setup
8.5.1 Record Mode (Recode mode)
Set record mode to record display value on recording paper. KRN100 supports Graph, and
Digital record modes.
(1) Graph
Records display value as graph type on recording paper.
It records current time (hh:mm:ss), display value by channel in set Memo Period(Digital memo record period)
100
(2) Digital
Records display value as numeric on recording paper.
It records current time (hh:mm:ss), display value by channel in set Standard Period
(Print/Record period) and also records current date (Year-Month-Day) and time in every
00:00:00.
You can record digital memo manually by front key (press input terminal.
key for 3 sec), or digital
Set range: Graph ↔ Digital
Factory default: Graph
© Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
8.5.2 Digital Print type (1 line record channel during numeric recording)
Designate the number of channels to be printed when recording display value on recording paper.
It prints channel information between Graph and Digital record mode.
Set range: OneCH ↔ TwoCH
Factory default: TwoCH
(1) TwoCH
It records 2 channels in one line and records occurring alarm as abbreviation. In case of multi alarms, it records as ‘AL’.
Print form is as below.
(2) OneCH
It records 2 channels in one line and records occurring alarm as abbreviation. Not as
TwoCH, it also records one channel’s error message and occurring alarms in 4 alarms.
Print form is as below.
For the information about error abbreviations, please refer to ‘11.1 Error message’.
© Copyright Reserved KONICS Co., Ltd. 101
8 Parameter detail setup
8.5.3 Standard Speed (Standard record speed)
Designate record speed on recording paper.
Recorder speed is indicated as feed length of recording paper per an hour (mm/h) and it is activated only when Record Mode(Record mode) is set as ‘Graph(Graph)’.
Set range: 10 ↔ 20 ↔ 40 ↔ 60 ↔ 120 ↔ 240mm/h
Factory default: 20mm/h
8.5.4 Option Speed (Option record speed)
Designate option record speed.
Recorder speed is indicated as feed length of recording paper per an hour (mm/h) and it is activated only when Record Mode(Record mode) is set as ‘Graph(Graph)’.
After setting DI-□ Type(Select digital input□) as ‘Speed’, select either Standard
Speed(standard record speed) ↔ Option Speed(option record speed) by digital input.
When changing the set value of Standard Speed(Standard record speed), the set value of Option
Speed(Pption record speed) is also changed as same as the set value of Standard Speed.
(Option Speed should not be lower than Standard Speed.)
Set range: 10 ↔ 20 ↔ 40 ↔ 60 ↔ 120 ↔ 240 mm/h
Factory default: 20mm/h
102 © Copyright Reserved KONICS Co., Ltd.
8.5.5 Memo Period (Digital memo period)
8 Parameter detail setup
Designate record period (unit: min) for digital memo(current time, current value by channel).
Digital memo time is recorded at right time. You can record digital memo manually by pressing
key for 3 sec or using digital input terminal (DI-2).
Set range: Recording record speed and record channel, set range of digital memo period is limited.
Factory default: 2hour
If digital memo period is set as 60 min. and record start time is ‘09:20’, first record time is ‘10:00’, not ‘10:20’.
Digital record time is ‘10:00 → 11:00 → 12:00 → 13:00 → record end time’.
If digital memo period is set as 10 min, and record start time is ‘09:23’, first record time is ‘09:30’, not ‘09:33’.
Digital record time is ‘09:30 → 09:40 → 09:50 → 10:00 → record end time’.
Depending on record speed and the number of record channels, memo period setting time is limited. (Record speed unit: mm/h)
Digital memo period setting time when record channel is 1 to 2CH
Record speed
10
20
40
60
120
1 min 5 min 10 min 15 min 30 min 1 hour 2 hour 3 hour 4 hour 8 hour 16 hour 24 hour
X
X
○
X
○
X
○
○ ○
240
○
Digital memo period setting time when record channel is 3 to 4CH
Record speed
10
20
40
60
120
240
1 min 5 min 10 min 15 min 30 min 1 hour 2 hour 3 hour 4 hour 8 hour 16 hour 24 hour
X
X
○
X
○
X
○
X
○
○
© Copyright Reserved KONICS Co., Ltd. 103
8 Parameter detail setup
Digital memo period setting time when record channel is 5 to 6CH
Record speed
10
20
1 min 5 min 10 min 15 min 30 min 1 hour 2 hour 3 hour 4 hour 8 hour 16 hour 24 hour
X
X
X
X
40
60
120
X
X
○
○
○
○
○
240
○
Digital memo period setting time when record channel is 7 to 8CH
Record speed
10
20
40
60
120
1 min 5 min 10 min 15 min 30 min 1 hour 2 hour 3 hour 4 hour 8 hour 16 hour 24 hour
X
X X
X
X
○
X
○
○
○
240
○ ○
Digital memo period setting time when record channel is 9 to 10CH
Record speed
10
20
40
60
120
1 min 5 min 10 min 15 min 30 min 1 hour 2 hour 3 hour 4 hour 8 hour 16 hour 24 hour
X
X X
X
X
○
X
○
○
○
240
○ ○
Digital memo period setting time when record channel is 11 to 12CH
Record speed
10
20
40
60
120
1 min 5 min 10 min 15 min 30 min 1 hour 2 hour 3 hour 4 hour 8 hour 16 hour 24 hour
X X
X
X
X
○
X
○
X
○
○
○
240
○
104 © Copyright Reserved KONICS Co., Ltd.
8.5.6 Divide Zone (Record zone division)
8 Parameter detail setup
Divides record zone for measuring value by channel.
It divides equally max. 12 zones as equal value. User needs to set record zone by channel in
Record Zone setting at Input Setup.
It is easy to check measuring value due not to duplicated record zone with divided record zone by channel which is set in Record Zone setting at Input Setup.
If there is too many division for record zone, record value check accuracy is low.
Set range: None, 2 to 12
Factory default: None
Set value of record zone division: None
Set value of record zone division : 5
© Copyright Reserved KONICS Co., Ltd. 105
8 Parameter detail setup
8.5.7 Standard Period (Standard record period)
Set record period to record current time, display value by channel as digital number on recording paper.
It is actiaved when Record Mode(Record mode) is Digital.
Set range: 00m 01s to 99m 59s (Depending on the number of recording channel, min. set range is limited as below.)
Record channel Set range
1 to 2
3 to 4
01m 00s to 99m 59s
02m 00s to 99m 59s
5 to 6
Factory default: -
03m 00s to 99m 59s
Record channel
7 to 8
9 to10
11 to 12
Set range
04m 00s to 99m 59s
05m 00s to 99m 59s
06m 00s to 99m 59s
8.5.8 Option Period (Option record period)
When Record Mode(Record mode) is set as ‘Digital’, set record period for current time
(hh:mm:ss) and measuring value by channel (min:sec) through digital input(Speed set).
Set range: 00m 01s to 99m 59s (Depending on the number of recording channel, min. set range is limited as below.)
Record channel
1 to 2
3 to 4
5 to 6
Factory default: -
Set range
01m 00s to 99m 59s
02m 00s to 99m 59s
03m 00s to 99m 59s
Record channel Set range
7 to 8
9 to 10
11 to 12
04m 00s to 99m 59s
05m 00s to 99m 59s
06m 00s to 99m 59s
106 © Copyright Reserved KONICS Co., Ltd.
8.5.9 Listing Language (Language for list output)
8 Parameter detail setup
Desigante recorded langauge when list output.
Language Example of recording
English
Korea
Set range: English ↔ Korea
Factory default: English
© Copyright Reserved KONICS Co., Ltd. 107
8 Parameter detail setup
8.5.10 Alarm Speed (Alarm record speed)
Set record speed for alarm cause and details when alarm occurs.
It is actiaved when Record Mode(Record mode) is set as Graph.
You cannot set Alarm Speed(Alarm record speed) as below Standard Speed(Standard record speed). If you change Standard Speed, Alarm Speed is changed as the same set value automatically.
When alarm occurs, record progresses with set Alarm Speed. When alarm is reset, it returns to
Standard Speed.
Set range: 10↔20↔40↔60↔120↔240mm/h
Factory default: 20mm/h
If alarm and digital input occur at the same time, digital input is ignored and it records with the set value of Alarm Speed(Alarm record speed). When alarm is reset, it returns to
Standard Speed (Standard record speed).
In graph mode, record speed is change by Standard speed, Alarm and Option Speed.
Backup data is printable only with Standard speed. Therefore, original graph mode printout and backup graph mode printout may be different.
8.5.11 Power On Status (Record status when power ON)
Designate one record operation stauts from 3 mode for when KRN100 re-turns ON from OFF by power failure.
Hold(Maintain)
Run(Record)
Maintains record status of before power OFF (recording or stop recording).
Operates recording when power is ON.
Stop(Stop recording) No recording when power is ON.
Set range: Hold↔Run↔Stop
Factory default: Hold
108 © Copyright Reserved KONICS Co., Ltd.
8.5.12 Run Status (List printing at start recording)
8 Parameter detail setup
Set wheter to print setting list when starting recording. When printing list, icon for record in section 1 is changed as and flashes. After printing list with 240mm/h record speed, it processes record with changed set record speed.
Please refer to List Out Option(List record option) for the set list item.
Set range: ON / OFF
Factory default: OFF
© Copyright Reserved KONICS Co., Ltd. 109
8 Parameter detail setup
8.5.13 List Out Option (List record option)
Select parameter set value recording either Standard or Option and, it starts record.
It is activated when Run Status(List printing at start recording) is set as ‘ON’.
Set Description Example of recording
Standard
Records standard parameters only.
Input specification(INPUT), channel name (TAG), lower limit input value(LO-RNG), upper limit input value(HI-RNG), display unit(UNIT), input digital filter(FILT)
110
Option
Records standard parameters and option parameters.
Input specification(INPUT), channel name (TAG), lower limit input value(LO-RNG), upper limit input value(HI-RNG), display unit(UNIT), input digital filter(FILT), alarm mode(ALM□), alarm set value(VALUE), alarm number(RELAY), communication interface
(NETWORK, USB, E_NET)
Set range: Standard↔Option
Factory default: Standard
List is printed with max. record speed (240mm/h). Depending on the number of channel, it may take long time. Therefore, be sure this when printing the list.
© Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
8.5.14 Zone Dot Line Distance (Dot line for zone division)
Designate present/absence and interval of dot line at right to divide zone when zone is set. Dot line for zone division is printed in violet.
Set range: None to 8.0mm (Set with 0.8mm interval)
Factory default: 4.0mm
Set the interval between dots.
8.5.15 CH Print Distance (Record interval for each channel graph)
Designate the interval for printing channel number of each graph as below figure.
It is activated when Record Mode(Record mode) is set as ‘Graph’.
Set range: No Print to 100.0mm(Set by 10mm interval)
Factory default: 20.0mm
3
2
1
© Copyright Reserved KONICS Co., Ltd. 111
8 Parameter detail setup
8.5.16 Start Line Print (Start line when starting record)
Set whether to draw start line when starting record.
Set range: ON ↔ OFF
Factory default: ON
8.5.17 Range Print Time (Input range record period)
It is actiaved when Record Mode(Record mode) is set as Graph. Set record period of High/Low
Range & Graph Scale(High/ Low input value and graph scale value).
Set range: Disable ↔ 1 to 24hour
Factory default: Disable
112
During Range printing, the other data except graph is not recorded within pritted range. Be sure that if there is too many channel numbers or if Range Print Time interval is too short with low speed, various information about channel is not printed at Range print zone.
© Copyright Reserved KONICS Co., Ltd.
8.6
8 Parameter detail setup
SYSTEM SETUP (System setting)
You can set system parameters of KRN100.
Set the item related system (date and time, reservation record, option, etc).
Move to SYSTEM SETUP with , keys, press key to enter SYSTEM SETUP.
Parameter list
Parameter Set range Factory default
Max. 16 characters
Date: 2000y01m01d to 2099y12m 31d
Time: 00h 00m 00s to 23h 59m 59s
yyyy/mm/dd ↔ mm/dd/yy ↔ dd/mm/yy
Disable ↔ Enable
Summer Time Period (Summer time period) 01m 01d 00h to 12m 31d 23h
Reservation Type (Reservation record)
Reservation Period (Reservation record period)
Disable ↔ Single ↔ Repeat
2000y 01m 01d to 2099y 12m 31d
Reservation Time (Reservation record time) 00h 00m 00s to 23h 59m 59s
OFF ↔ Min ↔ Standard ↔ Max
Sampling Rate (Sampling period)
1 channel to 4 channel: 25, 125, 250
5 channel to 12 channel: 125, 250
Backlight (LCD backlight brightness)
0 to 3600
OFF ↔ Min ↔ Standard ↔ Max
Backlight On/Off (LCD backlight ON method) Temp ↔ Always
KRN100 Recorder
Set as factory default yyyy/mm/dd
Disable
--
Disable
--
--
OFF
125ms
1s
Standard
Temp
※ Shaded parameters are affected by set value of other parameters. Please refer to specific descriptions of each parameter.
© Copyright Reserved KONICS Co., Ltd. 113
8 Parameter detail setup
8.6.1 Device Name (Device name)
Designate user defined KRN100 name.
It supports up to 16 characeters with English capital letters, English small letters, and special letter.
Set range: 16 characters
Factory default: KRN100 Recorder
8.6.2 Date/Time (Date/Time)
Desigante system date and time of KRN100.
When you set the date, the day of week is automatically set and time is displayed in 24-hours format.
Based on set date and time, it records and saves the data.
Set range
Date: 2000y01m01d to 2099y12m31d, Time: 00h00m00s to 23h59m59s
Factory default: Set as factory default
8.6.3 Date Type (Date type)
Set KRN100 system date display method on the screen and record method on the recording paper.
You can select one display method among yyyy(year)/mm(month)/dd(day), mm(month)/dd(day)/yy(year), or dd(day)/mm(month)/yy(year).
Set range: yyyy/mm/dd ↔ dd/mm/yy ↔ mm/dd/yy
Factory default: yyyy/mm/dd
114 © Copyright Reserved KONICS Co., Ltd.
8.6.4 Summer Time (Summer time)
8 Parameter detail setup
This function is for applying summer time (daylight saving time) in specific contries and regions.
When you set Summer Time, it adds current time and 1 hour and displays ‘(S)’ mark in front of the date and time on LCD screen or in front of the date on recording paper.
Set range: Disable ↔ Enable
Factory default: Disable
8.6.5 Summer Time Period (Summer time period)
Designate summer time (daylight saving time) period.
When Summer Time is set as ‘Enable’, it is activated. Designate Start date/Time, and End
Date/Time.
Set range: 01m01d 00h to 12m31d 23h
Factory default: --
When changing summer time, it creates new backup data.
© Copyright Reserved KONICS Co., Ltd. 115
8 Parameter detail setup
8.6.6 Reservation Type (Reservation record)
This function is to set reservation time. At the set time, it starts/stops recording automatically.
You can select reservation record either Repeat(Repeat ON/OFF) or Single(Single ON/ OFF).
When selecting reservation record, ‘Reservation Period(Reservation record period)’ and
‘Reservation Time(Reservation record time)’ are activated. When reservation record is set, icon flashes with (recording) or (stop recording) icon.
icon tuns OFF when reservation setting is ‘Disable’.
Set range: Disable ↔ Repeat ↔ Single
Factory default: Disable
(1) Repeat(Repeat ON/OFF)
From start recording date to end recording date, it records data at from the set start time to the set end time. End time must be later than Start time.
Reservation Period(Reservation record period) setting: Start Date 2011/ 1/ 1, End Date
2011/ 1/ 3
Reservation Time(Reservation record time) setting: Start Time 12/ 00/ 00, End Time 23/ 59/
59
It records data every at from 12:00:00 to 23:59:59 in from 1 st
, Jan, 2011 to 3 rd
, Jan, 2011.
(2) Single(Single ON/OFF)
Starts recording at the start set time on start date and finishes recording at the end set time on end date.
Reservation Period(reservation record period): Start Date 2011/ 1/ 1, End Date 2011/ 1/ 5
Reservation Time(reservation record time): Start Time 12/ 00/ 00, End Time 23/ 59/ 59
It starts recording at 12:00:00 on January 1
2011. st
2011 and finishes it at 23:59:59 January 5 th
116 © Copyright Reserved KONICS Co., Ltd.
8.6.7 Reservation Period (Reservation record period)
8 Parameter detail setup
Designate reservation record period. When Reservation Type(Reservation record) is set as
‘Repeat(Repeat ON/OFF)’ or ‘Single(Single ON/OFF)’, it is activated to designate Start
Date(Start date) and End Date(End date).
Set range: 2000 / 01 / 01 to 2099 / 12 / 31
Factory default: --
8.6.8 Reservation Time (Reservation record time)
Designate reservation record time. When Reservation Type(Reservation record) is set as
‘Repeat(Repeat ON/OFF)’ or ‘Single(Single ON/OFF)’, it is activated to designate Start
Time(Start time) and End Time(End time).
Set range: 0/ 00/ 00 to 23/ 59/ 59
Factory default: --
If reservation record(Reservation record) is set and during reservation recording, digital input is not available as RUN mode. In stopping recording status by reservation record, it is available.
© Copyright Reserved KONICS Co., Ltd. 117
8 Parameter detail setup
8.6.9 Alarm Sound (Alarm sound)
Designate Alarm Sound (alarm sound) level when alarm operation turns ON.
Set range: OFF ↔ Min ↔ Standard ↔ Max
Factory default: OFF
8.6.10 Sampling Rate (Sampling period)
Designate sampling rate (Sampling period) of measuring value.
Set range may be different by the number of connected universal input card(KRN-UI6).
Set range
When connecting 1 to 2 universal input card(KRN-UI2): 25↔125↔250ms
When connecting 3 to 6 universal input card(KRN-UI2): 125↔250ms
Factory default: 125ms
Min. sampling period for TC-R, U, S, T sensors is 50ms.
118 © Copyright Reserved KONICS Co., Ltd.
8.6.11 Log Speed (Save period)
8 Parameter detail setup
Designate the save period of measured data by universal input card (KRN-UI2) to system memory. The recorded data on recording paper is also recorded by save period.
For example, 3 sec save period records every 3 sec data, but it does not record during 3 sec of data which are changed.
Set range: 0 to 3600
Factory default: 1s
If save period is set longer, the relation between graph data and alarm ON data is lower because of the occuring alarm record in the middle of save period during recording.
When setting as ‘0s’ for Log Speed(save period), recording operates normally but the data does not saved at inner/external memory. If no recording paper (P.END) alarm occurs, there is no designated data and backup data is not recorded.
8.6.12 Backlight (LCD backlight brightness)
Designate LCD backlight brightness as 4 levels.
Set range: OFF ↔ Min ↔ Standard ↔ Max
Factory default: Standard
8.6.13 Backlight On/Off (LCD backlight ON method)
Designate LCD backlight ON method.
If you set as ‘Always’, it maintins ON status, as ‘Temp’, it maintains only for 30 sec when key is input.
Set range: Always ↔ Temp
Factory default: Temp
© Copyright Reserved KONICS Co., Ltd. 119
8 Parameter detail setup
8.7
FILE/MEMORY SETUP(File/Memory setting)
You can set the parameter about parameter set file and storage data.
Move to FILEMEMORY SETUP with
FILE/MEMORY SETUP.
, keys, press key to enter
Parameter list
Parameter
Load Set File (Open parameter setting file)
Save Set File (Save parameter setting file)
Memory Status (Memory capacity)
Set range
None, Default.pms, User1.pms, User2.pms,
User3.pms, User4.pms, User5.pms,
User1.pms(USB), User2.pms(USB),
User3.pms(USB), User4.pms(USB),
User5.pms(USB)
None, Default.pms, User1.pms, User2.pms,
User3.pms, User4.pms, User5.pms,
User1.pms(USB), User2.pms(USB),
User3.pms(USB), User4.pms(USB),
User5.pms(USB)
0% to 100%(display range)
Cancel ↔ All Clear
USB LogData Save (USB storage function)
Enable ↔ Disable
Memory Save Option (Memory storage option) Overwrite ↔ Stop
USB Memory Copy/Move (Move/Copy data)
-
Factory default
None
Select ...
0%
Clear ...
Disable
Stop
USB Copy/Move ...
120 © Copyright Reserved KONICS Co., Ltd.
8.7.1 Load Set File (Open parameter setting file)
8 Parameter detail setup
Applies set value of saved parameter set file.
When applying this set, backup data, user unit and booting logo are not changed.
None, Default.pms file is activated and if there is User1.pms to User5.pms, User1.pms(USB) to
User5.pms(USB) file(parameter set save file), it is activated.
Set range: None ↔ Default.pms ↔ User1.pms to User5.pms ↔ User1.pms(USB) to
User5.pms(USB)
Factory default: None
Be sure that if selecting ‘Default.pms’ file, every set value is initialized as factory default. Save the current set parameter as Save Set File (parameter setting file storage) at first and initialize it for the provision.
User1.pms to User5.pms, User1.pms(USB) to User5.pms(USB) file is selected, all parameter setting information of KRN100 is changed as the set value of the selected parameter save file.
Set value changing may be also affected to every setting of KRN100’s overall operations. Check possible problems occuring on system and change the desired set value.
8.7.2 Save Set File (Save parameter setting file)
Saves current set parameter set value to User1.pms to User5.pms file of inner memory.
In case of empty file, it displays gray.
Set range: None ↔ User1.pms to User5.pms, User1.pms(USB) to User5.pms(USB)
Factory default: Select …
© Copyright Reserved KONICS Co., Ltd. 121
8 Parameter detail setup
8.7.3 Memory Status (Memory capacity)
Displays system memory usage in %.
Display range: 0 to 100%
Factory default: 0%
Inner system memory of KRN100 is 512 Mbyte, and KRN100 supports an external USB memory up to 32 Gbyte. Another file to be saved data is created when it is over 100 Mbyte.
Below table is save time for 100Mbyte data by the number of input channels.
The number of CH Saved time
1 channel
2 channels
Approx. 50 days
Approx. 43 days
3 channels
4 channels
5 channels
6 channels
Approx. 37 days
Approx. 33 days
Approx. 30 days
Approx. 27 days
The number of CH Saved time
7 channels
8 channels
Approx. 25 days
Approx. 23 days
9 channels
10 channels
11 channels
12 channels
Approx. 21 days
Approx. 20 days
Approx. 18 days
Approx. 17 days
8.7.4 Memory Clear (Delete memory)
122
Delete the saved log data on system memory.
Current saving backup data is not deleted when deleting backup data.
Set range: Cancel ↔ All Clear
Factory default: Clear …
© Copyright Reserved KONICS Co., Ltd.
8.7.5 USB LogData Save (USB storage function)
8 Parameter detail setup
Set whether to save backup data which is saved on system on an USB memory.
When selecting Enable to saving data to an USB memory, it also saves data to system memory at the same time. A connected USB memory at left side USB Slot, KRN100 starts to save. It takes check time for storage free space approx. 10 to 60 sec. depending on memory capacity.
The data is saved as ‘KRN100_20100815(year month day)_091050(hour min. sec.).KRD’ file name and if main set ※1 is changed or backup data capacity is over 100MByte, it creates new file.
Set range: Disable ↔ Enable
Factory default: Disable
※1.
Main set is as follwoings.
Sampling Rate(Sampling period), Display/Temp Unit(Display/Temperature unit),
Input Type(Input specification), Range/Scale Point(Decimal point),
Special Function(Special function), High/Low Range & Graph Scale(High/Low input value and graph scale value), Low Scale/High Scale(Lower/Upper limit scale value),
Alarm□ Type(Alarm□ operation mode), Alarm□ Alarm No(Alarm□ output alarm number)
, Record Mode(Record mode), Divide Zone(Record zone division),
Standard Speed(Standard record speed), Memo Period(Digital memo period),
Log Speed(Save period), Summer Time(Summer time)
Supporting file system is FAT16, FAT32 when using an USB memory.
Microsoft’s file system, NTFS, and Linux’s file system, EXT2, EXT3, etc., are not supportable.
When connecting an USB memory, KRN100 pauses backup data download by Modbus function, and backup data printer function to recognize memory for a while (dending on the capacity, max.
30 sec).
If an USB memory’s LED flashes, do not remove an USB memory, or it may damage to the data.
If the damage of USBmemory data occurs, you can find the saved data from KRN100 inner memory and save the desired file to an USB memory.
Set USB LogData Save(USB storage function) as ‘Disable’ and when the below message disappears, remove an USB memory.
© Copyright Reserved KONICS Co., Ltd. 123
8 Parameter detail setup
8.7.6 Memory Save Option (Memory storage option)
124
Set the operation how to storage new data when inner memory storage space is used all as
100%.
Set value
Overwrite
Stop(Stop saving)
Description
Deletes the oldest backup data file in order and saves new data.
Important backup data should be backup at first.
Stops backup data.
It does not save Backup data. Even though new recording paper is replaced, output function for backup data does not operate.
Set range: Overwrite ↔ Stop
Factory default: Stop
© Copyright Reserved KONICS Co., Ltd.
8.7.7 USB Memory Copy/Move (Move/Copy data)
8 Parameter detail setup
Moves, copies or deletes the saved backup data on inner Memory to an USB memory.
Currently saving backup data has ‘*’ mark and it is not able to copy, move and delete.
Item
None
Copy to USB
Memory
Move to USB
Memory
Delete File
File Information
Description
No operation
Saves selected backup data to an USB memory and preserves backup data of system memory.
Saves selected backup data to an USB memory and deletes backup data of system memory.
Deletes backup data.
Displays backup data information.
Displayed information is Name, Path, Size, Log Channel, Log Speed.
<< Prev Page
Next Page >>
Up Directory
Into Directory
Moves to previous page of file or directory list.
Moves to next page of file or directory list.
Moves to parent folder
Moves to sub folder.
Set range: (For the desired file) Copy to USB Memory, Move to USB Memory, Delete File
Factory default: USB Copy/Move ...
Copy(Move) to USB Memory
Into Directory
File Information
© Copyright Reserved KONICS Co., Ltd. 125
8 Parameter detail setup
8.8
USER INFORMATION SETUP(User information setting)
You can set user management, check system information, firmware upgrade.
Move to USER INFORMATION SETUP with
USER INFORMATION SETUP.
, keys, preess key to enter
Parameter list
Parameter
Login Admin (Administrator log in)
Change Admin Password (Change password by administrator)
User Lock (Change user authority)
Information (Check system information)
Firmware Upgrade (Firmware upgrade)
Set range
Disable ↔ Enable
0000 to 9999
0000 to 9999
OFF ↔ LOCK1 ↔ LOCK2, ↔ LOCK3
-
-
Factory default
Disable
-
-
OFF
Display ...
Automatically display
126 © Copyright Reserved KONICS Co., Ltd.
8.8.1 Password (Password mode)
8 Parameter detail setup
You can set password and the mode as user(general user) mode and administrator mode to restrict parameter setting and record function.
Administrator has every operate authority and user(general user) has only administrator-defined authority.
Item Description
Disable Allows every user operation authorization to use all functions.
Enable With administrator’s or user’s log-in and password, allows operation authorization.
When setting the password, lock icon is displayed. In user(general user) mode, lock icon marks as , and in administrator mode, it marks as .
Set range: Disable ↔ Enable
Factory default: Disable
Password mode setting: Disable → Enable is available without authority. But Enable → Disable changing is only available by administrator’s authority. Enter the set password at Login Admin to change the mode. In administrator lock state, when power turns OFF/ON, it changes user lock mode.
© Copyright Reserved KONICS Co., Ltd. 127
8 Parameter detail setup
8.8.2 Login Admin (Administrator log in)
Log in to the parameter by entering password as administrator.
Set range: 4 digit number
Factory default: -
When password is not set yet, default password is “0000”.
When entered administrator’s password is wrong, it displays ‘Fail, ASKey: xxxx’.
Please call our service center (+82-32-820-2343) and tell us ASKey and you can check administrator’s password.
8.8.3 Change Admin Password (Change password by administrator)
Change the previous password. Changing password is able only when login status as administrator.
Set range: 4 digit number
Factory default: -
128 © Copyright Reserved KONICS Co., Ltd.
8.8.4 User Lock (Change user authority)
8 Parameter detail setup
User(general user) mode has three levels for function set authority.
Setable parameter by function set authority is as below.
OFF Lock1 Lock2 Lock3 Item
DIGITAL INPUT
ALARM SETUP
INPUT SETUP
RECORD SETUP
SYSTEM SETUP
COMMUNICATION SETUP
RECORD BACKUP DATA
FILEMEMORY SETUP
●
●
●
●
●
▲
●
▲
Ⅹ
▲
Ⅹ
Ⅹ
●: Enables to check and change set value, ▲: Enables to check set value, Ⅹ: Disable to check and change set value
Set range: OFF ↔ LOCK1 ↔ LOCK2 ↔ LOCK3
Factory default: OFF
Regardless of User Lock(change user authority) setting, User(general user) mode cannot change firmware upgrade, the set file initialize, password mode disable functions.
8.8.5 Information (Check system information)
Check system information of KRN100.
You can firmware version, an USB memory capacity, communication concerns, slot connection status, etc.
If connected and displayed card on slot and actaul connected card is inconsists, check the connect status of card and re-supply power. If it is not recognized even though re-supplying power, please contact our service center. KONICS service center: +82-32-820-2343
© Copyright Reserved KONICS Co., Ltd. 129
8 Parameter detail setup
8.8.6 Firmware Upgrade (Firmware upgrade)
130
Updates KRN100 firmware.
When upgrading firmware, parameters’ set values are initialized.
Set range: -
Factory default: Automatically set
Firmware upgrade
1st
Visit our homepage ( www.konics.co
m) to download ‘KRN100 firmware file
(krn100.fwu)’.
2nd
Copy the downloaded firmware file to an USB memory’s loot (top) directory and connect an USB memory to KRN100.
3rd
Check that firmware is recognized on "USERINFORMATION SETUP -Firmware
Upgrade" menu.
4th
Check currrent version’s date and to-be upgraded version’s date. Select ‘Upgrade’ button and it starts firmware upgrade.
Before processing, warning message appears. Select ‘OK’.
© Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
5th
After completing firmware upgrade, below message appears. Turn OFF the power and turn ON it again.
6th
At first booting after upgrade, initialize and delete every parameter set file (Inner default set file, User1.pms to User5.pms) to consider firmware version information print, and compatibility with previous parameter setting.
During firmware upgrade, alarm output, digital input and log file save, etc functions does not operate normally. Therefore, please take proper measure to prevent malfunction of KRN100 system before starting firmware upgrade.
After completing firmware upgrade, you must turn OFF and ON the power of KRN100 to operate normally.
In process of firmware upgrade, when power turns OFF, firmware upgrade is not complete.
When power turns ON again, KRN100 operates with previous firmware version. Try firmware upgrade again.
After completing firmware upgrade and OFF/ON the power, if KRN100 displays booting screen and does not operate normally, it may have damage to the inner firmware during firmware upgrade. It is required to repair.
Please contact our service center. KONICS service center: +82-32-820-2343
© Copyright Reserved KONICS Co., Ltd. 131
8 Parameter detail setup
8.9
RECORD BACKUP_ SETUP (Backup data record setting)
Record Backup creates file when power ON regardless of starting/stopping record and saves the data to inner system memory (An USB memory storage is available (Enable) by the set.) according the set record mode.
This parameter is useful to print the desired time data with backup data or check data by computer with DAQ Master (dedicated software).
Therefore, backup data set function is for printing the saved backup data at inner system memory and an USB memory.
Move to RECORD BACKUP SETUP with
RECORD BACKUP SETUP.
, keys, press key to enter
Parameter list
Parameter
Record Backup (Backup data record)
Backup Data List (Backup data list)
Start Date and Time (Start time for data storage)
End Date and Time (End time for data storage)
Backup Print Mode (Backup data record mode)
Select Print Mode (Backup data recording mode setting)
Set range
Stop ↔ Start
-
Date: yyyy/ mm/ dd, Time: hh: mm :ss
Date: yyyy/ mm/ dd, Time: hh: mm :ss
-
Graph ↔ Digital
Factory default
Stop
File Not Found!!
0000/00/00
00:00:00
0000/00/00
00:00:00
Graph
Graph
When printing with backup data, the saved data in backup data is accurate but backup data printout may not be same 100% with the real-data due to the difference between printing time and backup time. Please use backup data as only for reference.
For printing backup data, KRN100 reads saved backup data in memory from beginning to end at first and starts printing. If backup data section is long or backup data is saved as low speed record mode, reading takes a lot of time. Therefore, print only for the desired section.
In graph mode, record speed is changed by Standard speed, Alarm, or Option Speed.
Backup data is printed with Standard speed. Therefore, original printout and backup printout in graph mode may be different.
132 © Copyright Reserved KONICS Co., Ltd.
8.9.1 Record Backup (Backup data record)
8 Parameter detail setup
Designate whether recording saved backup data.
Item
Stop
Start
Description
Not printing the designated backup data on Backup Data List, it returns to RUN mode.
Records the designated backup data on Backup Data List from start date and time to end date and time and returns to RUN mode.
At RUN mode, the icon for record changes as reads backup data to the end and starts recording.
and flashes. KRN100
(Depending on backup data file size, reading time may take longer.)
When starting printing by Record Backup function, starts recording as below figure.
Set range: Start ↔ Stop
Factory default: Stop
8.9.2 Backup Data List (Backup data list)
You can check saved Backup Data List(Backup data list).
Backup Data is sorted automatically according to the recently occuring order.
For the information of file selection of backup data list, please refer to ‘8.9.6 Select Print Mode
(Backup data recording mode setting)’.
© Copyright Reserved KONICS Co., Ltd. 133
8 Parameter detail setup
8.9.3 Start Date and Time (Start time for data storage)
Set storage start date and time for backup data. You can set start date and time.
Set range is within start date and time to end date and time.
Set range
Date: yyyy/ mm/ dd, Time: hh: mm :ss
Factory default: 0000/00/00 00:00:00
8.9.4 End Date and Time (End time for data storage)
Set storage end date and time for backup data. You can set end date and time.
Set range is within start date and time to end date and time.
Set range
Date: yyyy/ mm/ dd, Time: hh: mm :ss
Factory default: 0000/00/00 00:00:00
8.9.5 Backup Print Mode (Backup data record mode)
You can check record mode of current saved backup data.
134 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
8.9.6 Select Print Mode (Backup data recording mode setting)
It is able to print with different record mode from original backup data’s record mode.
Set range: Graph ↔ Digital
Factory default: Graph
To print with different record mode from original backup data’s record mode, it records with the set record speed(in case record mode is Graph) or the set record period (in case record mode is set as Digital) from record mode(Digital or Graph) on current record setup.
For example, in case original backup data is saved as Digital mode (Backup Print Mode: displays digital). To print with Graph mode (Select Print Mode: set as Graph), Graph mode’s record speed follows the set record speed of graph mode in current record setup.
How to select record backup file
1st
Move to RECORD BACKUP SETUP parameter setting group.
2nd In Backup Data List, press key and system memory and the saved backup data in USB are also display. (If backup data is not designated or does not exist, it displays "File Not Found!!".)
3rd Select the desired file in Basckup Data List and press displayed.
(Marked ‘*’ files displays currently saving file.)
key and menu is
© Copyright Reserved KONICS Co., Ltd. 135
8 Parameter detail setup
2nd
4th In menu screen, select Select File and press key and “S” is displayed in front of backup data. Select currently saving file, it displays only ’*’.
Press selected.
key to operate Function key and press key to enter and it
File Information: Checkes Backup Data information
Prev Page, Next Page: Moves page (If there are lots of files)
Up Directory: Moves parent folder
Into Directory: Enter the folder
5th You can check save time information of the selected Backup Data.
Moves parent folder
1st
Press key in selected file to activate selected screen. Select 'Up Directory' and it moves to parent-folder.
2nd
To moving parent-folder, you can check folders by created date.
3rd
To move desired date folder, press key at the selected folder and menu screen is activated. Select 'Into Directory' in this menu, it moves to inner folder.
4th
Below screen shows inner folder and saved files.
136 © Copyright Reserved KONICS Co., Ltd.
9
9.1
9 DAQMaster
DAQMaster
Overview
DAQMaster is integrated device management program and is able to utilize for temperature controller product line, meter product line, and counter product line of Autonics and recorder product line of KONICS.
DAQMaster provides graph user interface (GUI) for easy and convenient integrated several products’ parameter setting and data monitoring.
Visit our homepage ( www.konics.com
) to download ‘DAQMaster user manual’.
This ‘KRN100 user manual’ describes only for dedicated KRN100 functions. For more information about DAQMaster, please refer to ‘DAQMaster user manual’.
© Copyright Reserved KONICS Co., Ltd. 137
9 DAQMaster
9.2
Features
DAQMaster has the following features.
Supports multiple device
DAQMaster is able to simultaneously monitor multiple devices and set parameters of the devices. The units with different addresses in a single device are connectable at the same time. In Modbus RTU communication, several RS232 port are available.
Device scan
In case multiple units (with different addresses) are connected together, use unit scan function to automatically search for units.
Convenient user interface
User can arrange windows, attributes, and project screens, etc to monitor the data as convenient.
When saving the project, set screen is also saved.
Project management
You can save the setting of monitoring for added device and data, selection of I/O source, etc as the project. When loading the project, this file has the saved setting status.
You can also construct project list for convenient project file management.
Monitoring data log
It logs the data during monitoring and is able to save it as one of DAQMaster data file (*.ddf) or CSV file (*.csv). You can load the saved CSV file in Microsoft Excel directly. You can also designate file name, storage rules, and storage folders for easy file management.
Data analysis
You can analyze data file (*.ddf) with DAQMaster’s data analysis function as spread or graph.
You can save the analysis as *.rtf, *.txt, *.html, or *.csv file on spread.
Modbus map table reporting output
It can output the registered Modbus device address map as report. You can save the report for Modbus map table as HTML file (*.html) or PDF file (*.pdf).
Supports multi-language
It supports Korean, English, Japanese and Simplified Chinese.
To add a different language, modify the files in the Lang folder, rename, and save it.
Supports script
You can designate each other different I/O process by device using Lua script language.
138 © Copyright Reserved KONICS Co., Ltd.
9.3
9 DAQMaster
Dedicated KRN100 functions
Among DAQMaster’s functions, there are dedicated KRN100 functions during communicating with DAQMaster
9.3.1 Record Backup
You can download backup data which is saved in KRN100 inner memory from “Record Backup” section.
Directory form is year, month, day. Click the relevant icon and check below list.
To download backup file, click the file name with right mouse button and select "Download Log
File" menu.
Backup files are strucured as tree type directory at KRN100 inner memory. You can easily fine and download the desired file.
© Copyright Reserved KONICS Co., Ltd. 139
9 DAQMaster
When checking backup data by DAQMaster, it may not be same as origital print out 100%.
Therefore, please use backup data as reference.
9.3.2 User unit setting
Total 3 sizes user units are needed; two for display output, one for printing.
Image type
Unit image for printing
Unit image in several channel for displaying
Unit image in 1 channel for displaying
How to register user unit image
Size
32X10(Small unit)
32X12(Middle unit)
72X64(Large unit)
1st
Make 3 sizes images (file type: bmp) using image tools.
2nd
Double-click the arrow area as below figure and select the desired image files.
If you not select the image, this unit is proceses as blank.
140 © Copyright Reserved KONICS Co., Ltd.
9 DAQMaster
3rd
Select image files by type and size, click “Download” to download user images.
9.3.3 Boot logo image setting
You can set boot logo image to display during KRN100 booting.
After making ‘320x120’ size image with image tools and download it.
© Copyright Reserved KONICS Co., Ltd. 141
9 DAQMaster
9.3.4 Backup data checking function
This function is output downloaded backup data by DAQMater or an USB memory.
1st
Execute Data Anal. At taskbar, click [Start]-[Program]-[DAQMaster]-[DataAnal] or at
DAQMaster menu, click [Tool]-[Data Anal].
2nd
‘Data Anal’ program opens. Click open file icon and select downloaded ".KRD" file.
142 © Copyright Reserved KONICS Co., Ltd.
9 DAQMaster
3rd
Open chart and drag the desired channel to check waveforms or values.
For more information, please refer to ‘DAQMaster user manual’.
When checking backup data by DAQMaster, it may not be 100% same with original print out.
Please use backup data only for reference.
© Copyright Reserved KONICS Co., Ltd. 143
9 DAQMaster
144 © Copyright Reserved KONICS Co., Ltd.
10 Maintenance
10 Maintenance
10.1
Ink cartridge replacement
1st
Press key for 3 sec. in stop recording state and Ink cartridge moves to the center to be replaced easily. Open front cover of KRN100.
2nd
Push down recording paper cassette lever placed at below recording paper cassette, recording paper cassette is removed from KRN100.
© Copyright Reserved KONICS Co., Ltd. 145
10 Maintenance
3rd
Pull out ink cartridge and it is removed from KRN100.
Insert new ink cartridge.
10.2
Recording paper replacement
1st
From 1st to 2nd steps are same as Ink cartridge replacement method. Please refer to this.
Below figure is detached recording paper cassette.
2nd
Open new recording paper storage cover and finished recording paper storage cover of recording paper cassette.
146 © Copyright Reserved KONICS Co., Ltd.
10 Maintenance
3rd
For better print, recording paper should be loosen by entering the air.
If not as below figure, it may cause paper jam.
4th
Remove finished recording paper in finished recording paper storage and replace ne recording paper.
© Copyright Reserved KONICS Co., Ltd. 147
10 Maintenance
5th
Put recording paper’s holes (circle, oval) at recording paper holder and close new recording paper storage cover and finished recording paper storage cover.
148 © Copyright Reserved KONICS Co., Ltd.
10 Maintenance
6th
Push recording paper cartridge into KRN100 until click sound. Close front cover of
KRN100.
7th
Check recording paper operates normally by pressing front function in stop recording state.
© Copyright Reserved KONICS Co., Ltd.
key with FEED
149
10 Maintenance
150 © Copyright Reserved KONICS Co., Ltd.
11 Troubleshooting
11 Troubleshooting
Check KRN100 normal operation regularly.
No
1
2
3
4
5
6
7
8
9
10
Error
When power ON, KRN100 does not display anything on LCD screen and operate.
Displayed date and time is not correct.
Sensor input value is not right.
Troubleshooting
Check power supply and power connector is connected normally.
KRN100 has date and time error within
±2min/year (Useable until in 2100). Set date and time again.
Check sensor input settings are correct in
INPUT SETUP.
Turn OFF the power of KRN100 and remove input cards from KRN100 and check jumper pin settings according to input specification.
KRN100 records former digital data not current time’s.
Displaying record memory status icon ( or
) is the state of recording former digital data.
Because there are lots of alarms and record events or recorded data is accumulated due to short memo period.
To cancel former data recording, pause and re-start record.
Change the settings about record for proper operation.
In graph mode, printout for line and letters is not clear and spread.
Replace ink cartridge.
Recording paper’s terminal mark, red star shape, is displayed.
Recording paper should be replaced. Present recording paper lefts only 330mm from terminal mark.
When power ON, after booting screen,
KRN100 does not change normal operation screen.
SD card of inner KRN100 has problem.
Please contact our service center.
USB memory is not recognized.
Cannot connect communication by RS485 communication.
USB memory’s file system supports only
FAT16 and FAT32. Format as FAT16 or
FAT32.
If partitions of an USB memory are divided,
KRN100 recognizes only first partition.
Cannot connect communication by Ethernet.
Check communication line connection and
reset it as following ‘8.4 COMMUNICATION
SETUP (Communication setting)’.
Check communication line’s A, B signal polarity is connected correctly. Reset it as
following ‘8.4 COMMUNICATION SETUP
© Copyright Reserved KONICS Co., Ltd. 151
11 Troubleshooting
11.1
Error message
Displays error messages on screen and print data when error occurs.
Error message Description
In case Input Type is temperature sensor(thermocouple, RTD), if input value is higher than upper limit range, this error message flashes. If input value is within upper limit range, it is removed automatically.
HHHH
In case Input Type is analog(current, voltage), if input value is higher than over
10% of upper limit input range, this error message flashes. If input value is within
10% of upper limit input range, it is removed automatically.
Prints HH.
In case Input Type is temperature sensor(thermocouple, RTD), if input value is lower than lower limit range, this error message flashes. If input value is within lower limit range, it is removed automatically.
LLLL
In case Input Type is analog(current, voltage), if input value is lower than over
10% of lower limit input range, this error message flashes. If input value is within
10% of lower limit input range, it is removed automatically.
Prints LL.
_H
_L
In case Input Type is analog(current, voltage), if input value is higher than below
10% of upper limit input range, “_H” is displayed with current value to notify that current value is higher than upper limit input range.
Ex) When upper limit input range is 100 and current value is 102, it displays as
102_H.
In case Input Type is analog(current, voltage), if input value is lower than below
10% of lower limit input range, “_L” is displayed with current value to notify that current value is lower than lower limit input range.
Ex) When lower limit input range is 0 and current value is -1, it displays as -1_L.
If input is break, this error message flashes. When input is connected, it is removed automatically.
BURN
Prints BH(display value by break is High) or BL (display value by break is Low).
Refer to ‘8.1.19 Burnout Action (Display setting for break)’.
NONE
If universal input card is not connected, this error message flashes.
ERR
When there is parameter setting error, card recognition error, etc, this error message flashes twice and KRN100 returns to previous screen.
152
Inner Memory
Access
As above screen, if excess error message for inner system memory Read/Write occurs frequently, please contact our service center.
© Copyright Reserved KONICS Co., Ltd.
11 Troubleshooting
© Copyright Reserved KONICS Co., Ltd. 153
11 Troubleshooting
© Copyright Reserved KONICS Co., Ltd. 155