RLW Reactor Users Manual
IMPORTANT USER INFORMATION
NOTICE
MTE Series RLW reactors are components designed to improve the reliability of three or
single phase AC adjustable frequency drives, DC drives and a wide variety of other types
of power electronic equipment. In addition they provide input line current harmonic
mitigation and 100 foot long lead protection for inverter fed motors. MTE reactors are
available in a large number of current ratings and a variety of inductance values. The
suitability of a reactor for a specific application must therefore be ultimately determined by
the customer. In no event will MTE Corporation assume responsibility or liability for any
direct or consequential damages resulting from the use or application of reactors. Nor will
MTE Corporation assume patent liability with respect to the use of information, circuits or
equipment described in this instruction manual.
Data subject to change without notice 9-09-30
1 of 25
INSTR--30
RLW Reactor Users Manual
Table of Contents
TABLE OF CONTENTS ............................................................................................................................... 2
1. IMPORTANT SAFETY NFORMATION WARNING.................................................................................. 3
2. INTRODUCTION....................................................................................................................................... 4
MODEL CODE PART NUMBER CONFIGURATION................................................................................... 5
SPECIFICATION DATA ............................................................................................................................... 6
SERVICE FACTOR ........................................................................................................................................ 6
AMBIENT TEMPERATURE ............................................................................................................................... 6
APPROVALS ................................................................................................................................................. 6
ENCLOSURES: ............................................................................................................................................. 6
DIN RAIL MOUNT ......................................................................................................................................... 6
REACTOR ELECTRICAL DATA ................................................................................................................. 8
SELECTION & APPLICATION GUIDE ...................................................................................................... 10
RL REACTOR CROSS TO RLW.................................................................................................................... 11
MECHANICAL DATA ................................................................................................................................. 12
OPEN PANEL ............................................................................................................................................. 12
ENCLOSED REACTOR MECHANICAL ............................................................................................................ 14
FACTORY CONFIGURED OPTIONS ........................................................................................................ 15
KIT-0038.................................................................................................................................................. 15
KIT-0039.................................................................................................................................................. 15
KIT-0040.................................................................................................................................................. 15
OUTLINE DRAWINGS ............................................................................................................................... 16
FIGURE 1 SNAP BASE MOUNT .................................................................................................................... 16
FIGURE 2 35MM DIN MOUNT OPTION........................................................................................................ 16
FIGURE 3 STANDARD MOUNTING ................................................................................................................ 16
FIGURE 4 CAB – 8...................................................................................................................................... 17
FIGURE 5 CAB 13V .................................................................................................................................... 17
FIGURE 6 CAB 12C ................................................................................................................................... 18
REACTOR INSTALLATION ........................................................................................................................ 19
POWER WIRING CONNECTION ............................................................................................................... 20
GROUNDING .............................................................................................................................................. 21
CONNECTION DIAGRAMS ....................................................................................................................... 22
STARTUP ................................................................................................................................................... 23
SEQUENCE OF OPERATION ......................................................................................................................... 23
Data subject to change without notice 9-09-30
2 of 25
INSTR--30
RLW Reactor Users Manual
1. IMPORTANT SAFETY NFORMATION WARNING
ONLY A QUALIFIED ELECTRICIAN CAN CARRY OUT THE ELECTRICAL
INSTALLATION OF LINE/LOAD REACTORS
WARNING
High voltage is used in the operation of line/load reactors. Use Extreme caution to avoid contact with high voltage
when operating, installing or repairing equipment containing line/load reactors.
INJURY OR DEATH MAY RESULT IF SAFETY PRECAUTIONS ARE NOT OBSERVED.
Line/load reactors are used in conjunction with inverters, or other electrical equipment that may feedback lethal
voltages. Follow the safety instructions in the equipment used with the reactor in addition to the safety instruction in
this manual.
WARNING
The opening of the branch circuit protective device may be an indication that a fault current has been
interrupted. To reduce the risk of fire or electrical shock, line/load reactors should be examined and
replaced if damaged.
WARNING
An upstream disconnect/protection device must be used as required by the National Electrical Code
(NEC).
WARNING
Even if the upstream disconnect/protection device is open, a drive or inverter down stream of the
line/load reactor may feed back high voltage to the reactor. The inverter or drive safety instructions
must be followed. INJURY OR DEATH MAY RESULT IF THE DRIVE SAFETY PRECAUTIONS ARE
NOT OBSERVED.
WARNING
The frame of line/load reactors must be grounded at least at one of the reactor’s mounting holes.
WARNING
Only spare parts obtained from MTE Corporation or an authorized MTE distributor can be used
Data subject to change without notice 9-09-30
3 of 25
INSTR--30
RLW Reactor Users Manual
2. INTRODUCTION
This manual was specifically developed to assist in the installation, interconnection and operation of
MTE Corporation Series RLW reactors
This manual is intended for use by personnel experienced in the operation and maintenance of electronic
drives, inverters and similar types of power electronic equipment. Because of the high voltages required by the
equipment connected to line/load reactors and the potential dangers presented by rotating machinery, it is
essential that all personnel involved in the operation and maintenance of line/load reactors know and practice
the necessary safety precautions for this type of equipment. Personnel should read and understand
the instructions contained in this manual before installing, operating or servicing line/load reactors and
the drive to which the reactor is connected.
Upon Receipt of a Reactor:
MTE Line/load Reactors have been subjected to demanding factory tests before shipment. Carefully
inspect the shipping container for damage that may have occurred in transit. Then unpack the filter and
carefully inspect for any signs of damage. Save the shipping container for future transport of the
reactor.
In the event of damage, please contact and file a claim with the freight carrier involved
immediately.
If the equipment is not going to be put into service upon receipt, cover and store the reactor in a clean, dry
location. After storage, ensure that the equipment is dry and that no condensation has accumulated on
the reactor before applying power.
Repair/Exchange Procedure
MTE Corporation requires a Returned Material Authorization Number before it can accept any reactors
that qualify for return or repair. If problems or questions arise during installation, setup, or operation of the filter,
please call us for assistance at:
Phone: 1-262-253-8200
FAX: 1-262-253-8222
Data subject to change without notice 9-09-30
4 of 25
INSTR--30
RLW Reactor Users Manual
Model Code Part Number Configuration
Model Number Code System:
RLW- _ _ _ _ X
X -
Reactor “W” world
.
Current Rating (i.e. 00P5 is 0.5 Amps)
Mechanical Configurations
0 = Base Mount
1 = NEMA 1
3 = NEMA 3R
Reactor relative impedance no.
1- 6 (1) is lowest value
Options:
KIT- 0038 = DIN Rail Mount
KIT-0039 = RL conversion Plate
KIT-0040 = Vibration Pads
Data subject to change without notice 9-09-30
5 of 25
INSTR--30
RLW Reactor Users Manual
Specification Data
Calculation:
Impedance basis
% Z= (I/V) x 2πfL√3 x 100
Service Factor:
Line (continuous):
Load
Overload Rating
Line side
100%
80% 100 foot long lead limit
150% of RMS rating for 1 minute
200% of RMS rating for 10 seconds
Maximum system voltage
690 Volts
Switching frequency
Maximum
Minimum
Insulation system
200º C
Temperature rise
140 C (average)
Ambient temperature
Full load:
-40 to 50º C Open
-40 to 45º C Enclosed
-40 to 90º C Storage
Altitude (de-rating)
see altitude de-rating curve
Fundamental frequency
50/60 Hz de-rate above 60 Hz
Inductance tolerance
+/- 10%
Inductance curve (typical)
100% at 100% current
80% at 150% current
50% at 200% current
Dielectric Strength
4000 volts RMS (2200 volts peak repetitive)
Max audible level at two meters:
Line applications: 65 dBa
Load applications: 76 dBa
Approvals:
CE, UL-508, Type RL cUL per CSA C22.2
20 KHz
1 KHz
Note: Short circuit rating not required under Exception No.1 of UL508A SB4.2.1 effective 4/25/06
Enclosures:
DIN Rail Mount:
MTECab-8,13V,17V have NEMA1
Cab 12C and up are NEMA1rated as NEMA2
(Indoor rating with ripping water protection)
MTE NEMA 3R is a type 3R outdoor rating
2 spring steel screw mounts for 35mm rail
With 10-32 screws
Data subject to change without notice 9-09-30
6 of 25
INSTR--30
RLW Reactor Users Manual
Current De-Rating Factor
Altitude Derating Curve
1.05
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0
3300
6600
9900
13200
16500
Altitude (Feet)
RLW Inductance curve
100
% N om inal Inductance
90
80
70
60
50
40
30
20
10
0
50
100
150
200
250
% Rated Current
Data subject to change without notice 9-09-30
7 of 25
INSTR--30
RLW Reactor Users Manual
Reactor Electrical Data
RMS
Amps
0.5
0.75
1.1
1.6
2.1
3.4
4.8
7.6
11
14
21
28
Open PN
NEMA 1
NEMA 3R
Inductance
mH
Watts Loss @ 60
Hz
RLW-00P501
RLW-00P503
RLW-00P505
RLW-00P506
RLW-0P7501
RLW-0P7503
RLW-0P7505
RLW-0P7506
RLW-01P101
RLW-01P103
RLW-01P105
RLW-01P106
RLW-01P601
RLW-01P603
RLW-01P605
RLW-01P606
RLW-02P101
RLW-02P103
RLW-02P105
RLW-02P106
RLW-03P401
RLW-03P403
RLW-03P405
RLW-03P406
RLW-04P801
RLW-04P803
RLW-04P805
RLW-04P806
RLW-07P601
RLW-07P603
RLW-07P605
RLW-07P606
RLW-001101
RLW-001103
RLW-001105
RLW-001106
RLW-001401
RLW-001403
RLW-001405
RLW-001406
RLW-002101
RLW-002103
RLW-002105
RLW-002106
RLW-002801
RLW-002803
RLW-002805
RLW-002806
RLW-00P511
RLW-00P513
RLW-00P515
RLW-00P516
RLW-0P7511
RLW-0P7513
RLW-0P7515
RLW-0P7516
RLW-01P111
RLW-01P113
RLW-01P115
RLW-01P116
RLW-01P611
RLW-01P613
RLW-01P615
RLW-01P616
RLW-02P111
RLW-02P113
RLW-02P115
RLW-02P116
RLW-03P411
RLW-03P413
RLW-03P415
RLW-03P416
RLW-04P811
RLW-04P813
RLW-04P815
RLW-04P816
RLW-07P611
RLW-07P613
RLW-07P615
RLW-07P616
RLW-001111
RLW-001113
RLW-001115
RLW-001116
RLW-001411
RLW-001413
RLW-001415
RLW-001416
RLW-002111
RLW-002113
RLW-002115
RLW-002116
RLW-002811
RLW-002813
RLW-002815
RLW-002816
RLW-00P531
RLW-00P533
RLW-00P535
RLW-00P536
RLW-0P7531
RLW-0P7533
RLW-0P7535
RLW-0P7536
RLW-01P131
RLW-01P133
RLW-01P135
RLW-01P136
RLW-01P631
RLW-01P633
RLW-01P635
RLW-01P636
RLW-02P131
RLW-02P133
RLW-02P135
RLW-02P136
RLW-03P431
RLW-03P433
RLW-03P435
RLW-03P436
RLW-04P831
RLW-04P833
RLW-04P835
RLW-04P836
RLW-07P631
RLW-07P633
RLW-07P635
RLW-07P636
RLW-001131
RLW-001133
RLW-001135
RLW-001136
RLW-001431
RLW-001433
RLW-001435
RLW-001436
RLW-002131
RLW-002133
RLW-002135
RLW-002136
RLW-002831
RLW-002833
RLW-002835
RLW-002836
22
46
74
92
15
31
49
61
10
21
33
42
6.9
14
23
29
5.3
11
18
22
3.2
6.8
11
14
2.3
4.8
7.7
10
1.5
3
4.8
6
1
2.1
3.3
4.3
0.79
1.6
2.6
3.3
0.53
1.1
1.8
2.2
0.39
0.82
1.3
1.6
2.3
3.6
4.8
5.4
4.2
6.6
8.8
10.1
4.8
7.8
10.1
11.9
6.9
10.9
15
17.7
9
14.3
19.6
22.3
12.3
19.6
26.5
31.5
13.8
23
37.5
40.1
19.2
37.2
47.8
53.8
26.8
40.9
54.4
59.1
32.7
48.2
60.6
66
38.3
57.4
73.5
78
48.2
66.8
93.8
110.6
Data subject to change without notice 9-09-30
8 of 25
INSTR--30
RLW Reactor Users Manual
Amps
35
46
55
65
83
104
130
160
200
250
322
414
515
600
750
Open PN
NEMA 1
NEMA 3R
RLW-003501
RLW-003503
RLW-003505
RLW-004601
RLW-004603
RLW-004605
RLW-005501
RLW-005503
RLW-005505
RLW-006501
RLW-006503
RLW-006505
RLW-008301
RLW-008303
RLW-008305
RLW-010401
RLW-010403
RLW-010405
RLW-013001
RLW-013003
RLW-013005
RLW-016001
RLW-016003
RLW-016005
RLW-020001
RLW-020003
RLW-020005
RLW-025001
RLW-025003
RLW-025005
RLW-032201
RLW-032203
RLW-032205
RLW-041401
RLW-041403
RLW-041405
RLW-051501
RLW-051503
RLW-051505
RLW-060001
RLW-060003
RLW-060005
RLW-075001
RLW-075003
RLW-075005
RLW-003511
RLW-003513
RLW-003515
RLW-004611
RLW-004613
RLW-004615
RLW-005511
RLW-005513
RLW-005515
RLW-006511
RLW-006513
RLW-006515
RLW-008311
RLW-008313
RLW-008315
RLW-010411
RLW-010413
RLW-010415
RLW-013011
RLW-013013
RLW-013015
RLW-016011
RLW-016013
RLW-016015
RLW-020011
RLW-020013
RLW-020015
RLW-025011
RLW-025013
RLW-025015
RLW-032211
RLW-032213
RLW-032215
RLW-041411
RLW-041413
RLW-041415
RLW-051511
RLW-051513
RLW-051515
RLW-060011
RLW-060013
RLW-060015
RLW-075011
RLW-075013
RLW-075015
RLW-003531
RLW-003533
RLW-003535
RLW-004631
RLW-004633
RLW-004635
RLW-005531
RLW-005533
RLW-005535
RLW-006531
RLW-006533
RLW-006535
RLW-008331
RLW-008333
RLW-008335
RLW-010431
RLW-010433
RLW-010435
RLW-013031
RLW-013033
RLW-013035
RLW-016031
RLW-016033
RLW-016035
RLW-020031
RLW-020033
RLW-020035
RLW-025031
RLW-025033
RLW-025035
RLW-032231
RLW-032233
RLW-032235
RLW-041431
RLW-041433
RLW-041435
RLW-051531
RLW-051533
RLW-051535
RLW-060031
RLW-060033
RLW-060035
RLW-075031
RLW-075033
RLW-075035
Data subject to change without notice 9-09-30
9 of 25
Inductance
mH
0.35
0.71
1.2
0.3
0.55
0.98
0.27
0.48
0.75
0.19
0.38
0.64
0.17
0.29
0.51
0.12
0.23
0.375
0.095
0.18
0.3
0.08
0.155
0.26
0.06
0.115
0.2
0.05
0.095
0.16
0.05
0.07
0.13
0.033
0.066
0.11
0.025
0.05
0.08
0.02
0.04
0.065
0.017
0.035
0.055
Watts Loss @ 60
Hz
68
102
121
77
99
179
67
109
149
87
105
214
119
155
197
94
200
208
132
152
197
110
195
309
159
224
293
275
284
402
300
383
494
333
531
588
314
496
695
375
747
780
468
838
858
INSTR--30
RLW Reactor Users Manual
Selection & Application Guide
The MTE World reactor (RLW) is an international product that is a low cost line side
alternative to the present line of MTE “RL” line/ load reactors. RLW’s are RMS current rated
impedance devices. Selection is based on the choice of inductance correlated to the
application motor full load amps, voltage and frequency and the number of phases. Use
PB-1101 selection tables to identify corresponding reactor part numbers for the desired
percent impedances. For critical impedance selection based on specific HP or load currents
consult MTE applications engineering.
Single phase applications: The RLW like RL reactors may also be sized to protect single
phase drives. Please see MTE application AN0120 for details
For load side applications use the indicated part number in PB-1101 or contact
MTE application engineering.
Choose the impedance level:
1.5%
Minimum impedance for reduction of low level voltage transients.
RLW reactors may be used as a supplement to already installed reactors.
3%
Helps minimize (95%) most drive nuisance tripping and faults caused by
over voltage and input line disturbances. 3% is typical impedance specified
by most drive manufacturers.
5%
The MTE recommended value to protect drive components from transient
over-voltage prevents (99.9%) nuisance trips and offers limited harmonic
protection to input line power from drive induced harmonics.
Data subject to change without notice 9-09-30
10 of 25
INSTR--30
RLW Reactor Users Manual
RL Reactor cross to RLW
Amps
1
2
4
8
12
18
25
35
45
55
RL Part No.
RL-00101
RL-00102
RL-00103
RL-00104
RL-00201
RL-00202
RL-00203
RL-00204
RL-00401
RL-00402
RL-00403
RL-00404
RL-00801
RL-00802
RL-00803
RL-00804
RL-01201
RL-01202
RL-01203
RL-01801
RL-01802
RL-01803
RL-02501
RL-02502
RL-02503
RL-03501
RL-03502
RL-03503
RL-04501
RL-04502
RL-04503
RL-05501
RL-05502
RL-05503
RLW Input
PN
RLW-00P506
RLW-01P106
RLW-01P105
RLW-01P103
RLW-02P103
RLW-02P105
RLW-02P106
RLW-02P101
RLW-04P801
RLW-04P805
RLW-04P806
RLW-04P806
RLW-07P601
RLW-07P603
RLW-07P605
RLW-07P606
RLW-001101
RLW-001103
RLW-001106
RLW-001401
RLW-001403
RLW-001405
RLW-002101
RLW-002103
RLW-002105
RLW-003501
RLW-003503
RLW-003505
RLW-004601
RLW-004603
RLW-004605
RLW-005501
RLW-005503
RLW-005505
RLW Output
PN
RLW-01P106
RLW-01P106
RLW-01P105
RLW-01P103
RLW-03P405
RLW-03P406
RLW-03P406
RLW-03P403
RLW-04P801
RLW-04P805
RLW-04P806
RLW-04P806
RLW-001101
RLW-001105
RLW-001106
RLW-001106
RLW-001403
RLW-001405
RLW-001406
RLW-002101
RLW-002105
RLW-002106
RLW-002801
RLW-002805
RLW-002806
RLW-004601
RLW-004605
RLW-004605
RLW-005501
RLW-005505
RLW-005505
RLW-006501
RLW-006503
RLW-006505
Amps
80
100
130
160
200
250
320
400
500
600
750
RL Part No.
RL-08001
RL-08002
RL-08003
RL-10001
RL-10002
RL-10003
RL-13001
RL-13002
RL-13003
RL-16001
RL-16002
RL-16003
RL-20001B14
RL-20002B14
RL-20003B14
RL-25001B14
RL-25002B14
RL-25003B14
RL-32001B14
RL-32002B14
RL-32003B14
RL-40001B14
RL-40002B14
RL-40003B14
RL-50001B14
RL-50002
RL-50003
RL-60001
RL-60002
RL-60003
RL-75001
RL-75002
RL-75003
RLW Input
PN
RLW-008301
RLW-008305
RLW-008305
RLW-010401
RLW-010403
RLW-010405
RLW-013001
RLW-013003
RLW-013005
RLW-016001
RLW-016003
RLW-016005
RLW-020001
RLW-020003
RLW-020005
RLW-025001
RLW-025003
RLW-025005
RLW-032201
RLW-032203
RLW-032205
RLW-041401
RLW-041403
RLW-041405
RLW-051501
RLW-051503
RLW-051505
RLW-060001
RLW-060003
RLW-060005
RLW-075001
RLW-075003
RLW-075005
RLW Output
PN
RLW-010403
RLW-010405
RLW-010405
RLW-013003
RLW-013005
RLW-013005
RLW-016001
RLW-016003
RLW-016005
RLW-020001
RLW-020003
RLW-020005
RLW-025001
RLW-025003
RLW-025005
RLW-033001
RLW-033003
RLW-033005
RLW-042001
RLW-042003
RLW-042005
RLW-050201
RLW-050203
RLW-050205
RLW-060001
RLW-060003
RLW-060005
RLW-075001
RLW-075003
RLW-075005
Note:
1. The RLW was designed to support global IEC and NEC input VFD drive motor
applications. To gain optimum performance and size advantages use the RLW
selections tables by HP and voltage in PB-1101.
2. RLW output selection is based on 80% of fundamental RLW current capacity for
output load applications up to 100 foot motor leads!
The above cross reference table is based on 480 VAC applications.
* Grey part numbers are NEMA 1-2 and 3R enclosed are not available for sale contact factory.
Data subject to change without notice 9-09-30
11 of 25
INSTR--30
RLW Reactor Users Manual
Mechanical Data
Open Panel
RMS
Amps
0.5
0.75
1.1
1.6
2.1
3.4
4.8
7.6
11
14
21
28
Open Part Number
Open PN
Wt
RLW-00P501
1.5
RLW-00P503
1.5
RLW-00P505
1.6
RLW-00P506
1.6
RLW-0P7501
1.4
RLW-0P7503
1.5
RLW-0P7505
1.5
RLW-0P7506
1.6
RLW-01P101
1.5
RLW-01P103
1.6
RLW-01P105
1.6
RLW-01P106
1.7
RLW-01P601
1.5
RLW-01P603
1.6
RLW-01P605
1.6
RLW-01P606
1.7
RLW-02P101
1.5
RLW-02P103
1.6
RLW-02P105
1.7
RLW-02P106
1.7
RLW-03P401
1.6
RLW-03P403
1.6
RLW-03P405
2.7
RLW-03P406
2.8
RLW-04P801
1.7
RLW-04P803
1.8
RLW-04P805
2.8
RLW-04P806
4.0
RLW-07P601
1.8
RLW-07P603
2.8
RLW-07P605
4.1
RLW-07P606
4.2
RLW-001101
2.7
RLW-001103
4.2
RLW-001105
5.3
RLW-001106
7.1
RLW-001401
2.8
RLW-001403
4.3
RLW-001405
7.1
RLW-001406
9.4
RLW-002101
4.2
RLW-002103
7.2
RLW-002105
10.0
RLW-002106
13.3
RLW-002801
5.1
RLW-002803
9.5
RLW-002805
10.4
RLW-002806
14.3
Fig
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
3
3
1-2
1-2
3
3
1-2
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Data subject to change without notice 9-09-30
A
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.4
4.4
4.5
4.5
4.4
4.4
4.5
4.4
4.4
4.4
4.4
4.4
4.4
6
4.4
4.4
6
6
4.4
6
6
7.2
4.4
6
6
7.2
12 of 25
Dimension in inches
B
C
D
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
3.7
1.5
0.0
5
2.8
2.0
5
2.8
2.0
3.7
1.5
0.0
3.7
1.5
0.0
5
2.8
2.0
5
3.1
2.1
3.7
1.5
0.0
5
2.8
2.0
5
3.1
2.1
5
3.1
2.1
5
2.8
2.0
5
3.1
2.1
5
3.5
2.6
5.8
2.9
2.1
5.3
2.8
2.0
5
3.1
2.1
5.8
2.9
2.1
5.8
3.3
2.5
5.3
3.3
2.4
6.1
2.9
2.1
6.1
3.3
2.5
7
3.8
2.3
5.3
3.5
2.6
6.1
3.3
2.5
6.1
3.3
2.3
7
3.8
2.3
E
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
1.4
1.4
4.0
4.0
1.4
1.4
4.0
1.4
1.4
1.4
1.4
1.4
1.4
2.0
1.4
1.4
2.0
2.0
1.4
2.0
2.0
3.0
1.4
2.0
2.0
3.0
F
-
INSTR--30
RLW Reactor Users Manual
Open Panel Mechanical cont.
RMS
Amps
35
46
55
65
83
104
130
160
200
250
322
414
515
600
750
Open Part Number
Open PN
Wt
Fig
10
RLW-003501
3
13
RLW-003503
3
18
RLW-003505
3
13
RLW-004601
3
17
RLW-004603
3
24
RLW-004605
3
18
RLW-005501
3
20
RLW-005503
3
26
RLW-005505
3
18
RLW-006501
3
22
RLW-006503
3
26
RLW-006505
3
19
RLW-008301
3
26
RLW-008303
3
35
RLW-008305
3
22
RLW-010401
3
28
RLW-010403
3
41
RLW-010405
3
26
RLW-013001
3
37
RLW-013003
3
52
RLW-013005
3
34
RLW-016001
3
49
RLW-016003
3
53
RLW-016005
3
34
RLW-020001
3
49
RLW-020003
3
75
RLW-020005
3
35
RLW-025001
3
55
RLW-025003
3
75
RLW-025005
3
57
RLW-032201
3
76
RLW-032203
3
108
RLW-032205
3
78
RLW-041401
3
98
RLW-041403
3
125
RLW-041405
3
81
RLW-051501
3
118
RLW-051503
3
193
RLW-051505
3
86
RLW-060001
3
144
RLW-060003
3
204
RLW-060005
3
105
RLW-075001
3
179
RLW-075003
3
245
RLW-075005
3
Data subject to change without notice 9-09-30
A
6.0
7.2
7.2
7.2
7.2
9
7.2
7.2
9.0
7.2
7.2
9.0
7.2
9.0
9.0
7.2
9.0
9.0
9.25
9.25
9.25
9.25
9.25
9.25
9.25
9.25
10.8
9.25
9.25
10.8
9.25
10.8
9
9
9
9
9
9
14.4
9
14.4
14.4
9
14.4
14.4
Dimension in inches
B
C
D
6.0
3.5
2.73
6.0
3.75
2.25
6.0
4.3
2.75
6.0
3.75
2.25
6.0
4.3
2.75
8.3
4.8
3.24
6.0
4.0
2.75
6.0
4.25
2.75
7.0
6.5
3.24
6.0
4.0
4.25
6.0
4.25
2.75
7.0
6.5
3.24
6.0
4.25
2.75
7.0
6.5
3.24
7.0
6.75
3.74
6.0
6.5
2.75
7.0
7.0
3.24
7.0
7.25
4.24
7.5
6.75
3.25
7.5
6.75
3.75
7.5
8.25
4.75
7.5
6.75
3.75
7.5
8.25
4.75
7.5
8.25
4.75
7.5
7.00
.375
7.5
8.25
4.75
8.25
9.00
5.87
7.5
7.5
3.75
7.5
8.5
4.75
8.75
9.00
5.87
7.5
9
4.75
8.75
8.5
5.37
8.75
11
7.37
8.75
9.5
5.37
8.75
11.5
6.87
8.75
12.5
7.37
8.75
9.5
5.37
8.75
12
6.37
11.5
13.5
9.62
8.75
10.5
5.37
11.5
12.5
8.12
11.5
13.75
8.62
8.75
11.5
6.87
11.5
12.5
7.62
11.5
15
8.62
13 of 25
E
2.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.63
3.0
3.0
3.63
3
3.63
3.63
3.63
3.63
3.63
3.63
3.63
4.6
3.63
4.6
3.63
3.63
4.6
4.6
F
3.0
4.26
4.26
4.26
4.26
4.26
4.26
4.26
4.26
4.26
4.26
4.26
4.26
4.26
4.26
4.26
4.26
5.58
4.26
4.26
5.58
4.26
5.58
5.58
5.58
5.58
5.58
5.58
5.58
5.9
5.58
5.9
5.58
5.58
7.2
7.2
INSTR--30
RLW Reactor Users Manual
Enclosed Reactor Mechanical
RMS
Amps
0.5
0.75
1.1
1.6
2.1
3.4
4.8
7.6
11
14
21
28
NEMA 1
Part number
Wt
Fig
RLW-00P511
RLW-00P513
RLW-00P515
RLW-00P516
RLW-0P7511
RLW-0P7513
RLW-0P7515
RLW-0P7516
RLW-01P111
RLW-01P113
RLW-01P115
RLW-01P116
RLW-01P611
RLW-01P613
RLW-01P615
RLW-01P616
RLW-02P111
RLW-02P113
RLW-02P115
RLW-02P116
RLW-03P411
RLW-03P413
RLW-03P415
RLW-03P416
RLW-04P811
RLW-04P813
RLW-04P815
RLW-04P816
RLW-07P611
RLW-07P613
RLW-07P615
RLW-07P616
RLW-001111
RLW-001113
RLW-001115
RLW-001116
RLW-001411
RLW-001413
RLW-001415
RLW-001416
RLW-002111
RLW-002113
RLW-002115
RLW-002116
RLW-002811
RLW-002813
RLW-002815
RLW-002816
8.5
8.5
8.6
8.6
8.4
8.5
8.5
8.6
8.5
8.6
8.6
8.7
8.5
8.6
8.6
8.7
8.5
8.6
8.7
8.7
8.6
8.7
9.7
20.8
8.7
8.8
20.7
22.0
8.8
20.7
22.1
22.2
20.7
22.2
23.2
25.1
20.8
22.3
25.1
27.4
22.2
25.2
28.0
31.3
23.1
27.5
31.7
32.3
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
5
4
4
5
5
4
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
Data subject to change without notice 9-09-30
14 of 25
NEMA 3R
Part Number
Wt
RLW-00P531
RLW-00P533
RLW-00P535
RLW-00P536
RLW-0P7531
RLW-0P7533
RLW-0P7535
RLW-0P7536
RLW-01P131
RLW-01P133
RLW-01P135
RLW-01P136
RLW-01P631
RLW-01P633
RLW-01P635
RLW-01P636
RLW-02P131
RLW-02P133
RLW-02P135
RLW-02P136
RLW-03P431
RLW-03P433
RLW-03P435
RLW-03P436
RLW-04P831
RLW-04P833
RLW-04P835
RLW-04P836
RLW-07P631
RLW-07P633
RLW-07P635
RLW-07P636
RLW-001131
RLW-001133
RLW-001135
RLW-001136
RLW-001431
RLW-001433
RLW-001435
RLW-001436
RLW-002131
RLW-002133
RLW-002135
RLW-002136
RLW-002831
RLW-002833
RLW-002835
RLW-002836
76.5
76.5
76.6
76.6
76.4
76.5
76.5
76.6
76.5
76.6
76.6
76.7
76.5
76.6
76.6
76.7
76.5
76.6
76.7
76.7
76.6
76.7
77.7
77.8
76.7
76.8
77.7
79.0
76.8
77.7
79.1
79.2
77.7
79.2
80.2
82.1
77.8
79.3
82.1
84.4
79.2
82.2
85.0
88.3
80.1
84.5
88.7
89.3
Fig
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
INSTR--30
RLW Reactor Users Manual
Factory Configured Options
KIT-0038
DIN rail Mount.
A DIN rail mounting option is provided to utilize standard 35mm panel mounted DIN rail for securing
the reactor via two steel mounting clips. The DIN rail kit is only available on snap channel reactors up
to 7 amps and indicated by figure 1- 2 on mechanical table.
KIT-0039
RL base mount converter plate.
The base plate adaptor option will allow the RLW to use existing RL bolt hole mounting patterns.
KIT-0040
Vibration pads for enclosure mounting.
Vibration isolation for enclosed reactors may be fitted with an optional vibration pad to dampen
cabinet vibrations from the reactor.
KIT -0039 converter plate
Data subject to change without notice 9-09-30
15 of 25
INSTR--30
RLW Reactor Users Manual
Outline Drawings
See mtecorp.com for complete mechanical details and CAD drawing download.
Figure 1 Snap Base Mount
Figure 2
35mm DIN Mount option
Figure 3 Standard Mounting
Data subject to change without notice 9-09-30
16 of 25
INSTR--30
RLW Reactor Users Manual
Outline Drawings
Figure 4 Cab – 8
Figure 5 Cab 13V
Data subject to change without notice 9-09-30
17 of 25
INSTR--30
RLW Reactor Users Manual
Figure 6 Cab 12C
Data subject to change without notice 9-09-30
18 of 25
INSTR--30
RLW Reactor Users Manual
Reactor Installation
MTE world reactors are available in open construction and in NEMA 1 enclosures. Open reactors are
designed for mounting within an appropriate electrical equipment enclosure. Reactors rated 300
amperes RMS and under are designed for mounting in both a vertical and horizontal position. Larger
reactors must be mounted in a horizontal position typically on the floor of the enclosure. Include the power
dissipation of the reactor along with all the other components located in the enclosure to determine the
internal temperature rise and cooling requirements of the enclosure.
Reactors may be located in any region of the enclosure where the ambient temperature does not exceed
45 degrees C. Allow a minimum side clearances of four (4) inches and vertical clearances of six (6) inches
for proper heat dissipation and access. Do not locate the reactor next to resistors or any other component
with operating surface temperatures above 125 degree C.
Select a well ventilated, dust-free area away from direct sunlight, rain or moisture. Do not install in or near a
corrosive environment. Avoid locations where the reactor will be subjected to excessive vibrations.
NEMA 1 Enclosed world Reactor Installation
MTE RLW reactors mounted in enclosures with part number, CAB-8, are designed for wall mounting.
All other enclosures are designed for floor mounting.
WARNING
MTE NEMA 1 enclosures designed for floor mounting must be mounted with the enclosure base
horizontal for proper ventilation. Wall mounting a floor mounted enclosure with the base
against the wall will cause the reactor to over heat resulting in equipment damage.
Allow a minimum side, front, and back clearances of twelve (12) inches and vertical clearances of
eighteen (18) inches for proper heat dissipation and access. Do not locate the enclosure next to resistors
or any other component with operating surface temperatures above 125 degree C.
Select a well ventilated, dust-free area away from direct sunlight, rain or moisture where the ambient
temperature does not exceed 40 degrees C.
Do not install in or near a corrosive environment.
Avoid locations where the reactor will be subjected to excessive vibrations.
Where desirable, reactors or enclosures may be mounted on vibration isolating pads to reduce audible
noise. Standard vibration control pads made from neoprene or natural rubber and selected for the
weight of the enclosed reactor are effective.
Data subject to change without notice 9-09-30
19 of 25
INSTR--30
RLW Reactor Users Manual
Power Wiring Connection
WARNING
Input and output power wiring to the reactor should be performed by authorized
personnel in accordance with the NEC and all local electrical codes and
regulations.
Verify that the power source to which the reactor is to be connected is in agreement with the nameplate
data on the reactor. A fused disconnect switch or circuit breaker should be installed between the reactor
and its source of power in accordance with the requirements of the NEC and all local electrical codes and
regulations. Refer to the drive, inverter, or other electrical equipment user manual for selection of the correct
fuse rating and class.
The reactor is suitable for use on a circuit capable of delivering not more than 65,000 rms symmetrical
amperes at 480 volts when protected by Bussman type JJS, KTK, KTK-R, SPP or T class fuses.
Reactor are designed for use with copper conductors with a minimum temperature rating of 75 degrees
C. Table 2 lists the wire range and terminal torque requirements for the power input and output
connections by reactor part number.
Refer to Figure 7 for typical electrical diagrams describing the application of reactors in both line and
load applications. For reactors supplied as a component part of a drive system or a component part of
power electronic apparatus follow the interconnection diagram supplied by the System Engineer.
Where desirable, a flexible conduit connection to the reactor enclosure should be made to reduce
audible noise.
WARNING
Failure to connect reactors supplied as a component part of a drive system or other power
electronic system according to the system interconnection diagram supplied by the System
Engineer will result in equipment damage, injury, or death.
WARNING
If a line reactor or a line reactor and a load reactor are used with a drive equipped with a bypass
circuit, the reactors must be removed from the motor circuit in the bypass mode. Damage to the
motor and other equipment will result if this warning is not observed.
Data subject to change without notice 9-09-30
20 of 25
INSTR--30
RLW Reactor Users Manual
Grounding
A stud is provided on enclosed reactors for grounding the enclosure. The enclosure must be
grounded. Open reactors must be grounded at the designated grounding terminal or the
reactor mounting holes if no designated grounding terminal is provided.
WARNING
The frame of line/load reactors must be grounded at the designated grounding terminal or one of the
reactor mounting holes if no designated grounding terminal is provided. The enclosure of reactors
supplied in enclosures must be grounded.
INJURY OR DEATH MAY RESULT IF SAFETY PRECAUTIONS ARE NOT OBSERVED.
Data subject to change without notice 9-09-30
21 of 25
INSTR--30
RLW Reactor Users Manual
Connection Diagrams
Load reactor connections
Note RLW requires current de-rating for load
applications see PB-1101 for selection tables
Conventional Line side reactor to VFD
connections
Note; Actual marking of U1 -U2, V1-V2,
W1-W2 designations on reactor
terminals in place of A1-A2, B1-B2, C1C2 as shown to left.
Single phase connection
Standard three phase reactors may be used for single phase applications. Refer to Application Note
AN0102 for proper selection. Application Notes are available on our website at www.mtecorp.com.
Data subject to change without notice 9-09-30
22 of 25
INSTR--30
RLW Reactor Users Manual
STARTUP
Safety Precautions
Before startup, observe the following warnings and instructions:
WARNING
A Reactor is at line potential when the Reactor is connected to the utility. This voltage is
extremely dangerous and may cause death or severe injury if you come in contact with it.
WARNING
High voltage is used in the operation of line/load reactors. Use Extreme caution to avoid
contact with high voltage when operating, installing or repairing equipment
containing reactors. RLW reactors are used in conjunction with inverters, or other
electrical equipment that may feedback lethal voltages.
Follow the safety instructions in the equipment used with the reactor in addition to the safety
instruction in this manual.
INJURY OR DEATH MAY RESULT IF SAFETYPRECAUTIONS ARE NOT OBSERVED.
Sequence of Operation
1. Read and follow safety precautions.
2. After installation, ensure that:
• All Reactor ground terminals are connected to ground.
• Power wiring to the utility, drive and motor is in accordance with the interconnection
diagrams supplied by the System Engineer.
3. Check that moisture has not condensed on the Reactor. If moisture is present, do not
proceed with startup until the moisture has been removed.
4. Proceed with startup according to the instructions provided by the system supplier.
WARNING
Reactors are a component part of an electrical system. Do not proceed with startup until the
system startup instructions provided by the System Engineer are understood and followed.
Injury, death and damage to equipment may result if the system startup instructions are not
followed.
WARNING
Use extreme caution to avoid contact with line voltage when checking for power
.
INJURY OR DEATH MAY RESULT IF SAFETY PRECAUTIONS ARE NOT OBSERVED.
Data subject to change without notice 9-09-30
23 of 25
INSTR--30
RLW Reactor Users Manual
ISO 7.2.3
AC Line / Load Reactors
PB-1101
Responsibility:
MTE Corporate
Approved by:
Wayne Walcott
File Location:
P:\Public\Controlled Documents\Sales\Price Book
Revision
Date
Revision History
--5/29/09
WRW New document written by Wayne Walcott –
9-18-09
WRW Revised to add phase 2-3 specifications
Data subject to change without notice 9-09-30
24 of 25
INSTR--30
Download PDF