Continental Hydraulics CEM-SA-B Installation Manual
Continental Hydraulics CEM-SA-B is a closed loop position module for controlling hydraulic positioning drives. It can be used with proportional valves with integrated or external electronics. The differential output provides an analog signal of either voltage (0 to +/- 10v) or current (4-20mA), suitable for directly driving a proportional directional valve with on-board electronics.
The internal profile generation is optimized for stroke-dependent deceleration or the NC control mode. The controller and the controller settings are factory preset to typical requirements and can be optimized for the control behavior as required. The optimized control function offers a high degree of precision together with high stability for hydraulic drives. The movement cycle is controlled via the external position and speed inputs.
Advertisement
Advertisement
Continental Hydraulics Installation Manual
CEM-SA-B
Description:
This closed loop position module has been developed for controlling hydraulic positioning drives.
Proportional valves with integrated or external electronics can be controlled with the differential output. Output is an analog signal of either voltage, 0 to +/- 10v or current 4-20mA, suitable for directly driving a proportional directional valve with on board electronics.
The internal profile generation is optimized for stroke-dependent deceleration or the NC control mode. The controller and the controller settings are factory preset to typical requirements and can be optimized for the control behavior as required. The optimized control function offers a high degree of precision together with high stability for hydraulic drives. The movement cycle is controlled via the external position and speed inputs.
The high resolution of the analogue signals ensures good positioning behavior. A wide range of analog signals are accepted. User may select either voltage or current input mode. These inputs are easily scaled to match system requirements.
Forward and Reverse “jog” inputs allow for manual load control. A user definable window for “in position” triggers an output for communication to the next machine function.
This module is easily adapted to a variety of system requirements. All variables are user adjusted with easy to use
CHI-PC
software on your Microsoft Windows laptop. Control variables are stored in non-volatile memory internal to the module. All variables can be read by the laptop, and reproduced exactly on other modules.
Page 1 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
Table of Contents
Information Description Page #
Technical Data - ……………………………………….…………………….………..…………… 3
Functional
Diagram …….…….…………………….……………………………………………... 4
Wiring
Example…………………………………………………………………………………… 4
Dimensions …………………………………………….…………………………………………… 4
Terminal Identification …………………………………………………………………………….. 5
Steps to install and configure a new application ……………………….………………………. 6
Module Mounting Location ………………………………………….…………………………….. 7
Power Supply ………………………………………………………………………………….…… 7
Wiring to valve ……………………………………………………………………………………… 7
Parameter List …………………………………………….…………………………..…………… 8
LED
Indications ……………………….…………………………………………………………… 9
Command Parameter Descriptions
LG (Language)…………………………………………………………………………… 10
MODE……………………………………………………………………………………... 10
SENS ……………………..……………………………………………………. ………... 10
EOUT …………………………………………………………………………………… 11
ENABLE…………………………………………………………………………………. 11
START (RUN)…………………………………………………………………………… 11
HAND:A /
HAND :B……………………………………………………………………… 12
INPOS ……………………………………………………………………………………. 12
SYS_RANGE ……………………………………………………………………………. 12
SIGNAL: W/X/V.………………………………………………………………………… 13
N_RANGE:X …………………………………………………………………………….. 13
OFFSET:X ……………………………………………………………………………….. 13
Using SYS_RANGE, N_RANGE and OFFSET ……………………………………… 14
Speed Commands SIGNAL:V …………………………………………………………. 15
VELO ……………………………………………………………………………………… 15
VRAMP …………………………………………………………………………………… 15
VMODE …………………………………………………………………………………… 16
ACCEL ……………………………………………………………………………………. 16
VMAX ……………………………………………………………………………………. 16
A:A and A:B………………………………………………………………………………. 17
D:A / D:B / D:S …………………………………………………………………………… 17
V0:A / V0:B / V0:RES …………………………………………………………………… 18
PT1 ……………………………………………………………………………………….. 18
C
TRL ……………………………………………………………………………………… 19
MIN:A / MIN:B ……………………………………………………………………………. 20
MAX:A / MAX:B …………………………………………………………………………. 20
TRIGGER ………………………………………………………………………………… 20
OFFSET ………………………………………………………………………………….. 21
SIGNAL:U ………………………………………………………………………………… 21
Special Command descriptions ……………………………………………………….. 22
DC:AV ……………………………………………………………………………………. 23
DC:DV ……………………………………………………………………………………. 23
DC:I ………………………………………………………………………………………. 23
DC:CR ……………………………………………………………………………………. 23
Process Data (Mon itoring) …………………………………………………………….. 23
AINMODE………………………………………………………………………………… 24-25
Troubleshooting …………………………………………………………………………………… 26-27
Page 2 of 27 CEM-SA-B CHI 1020687 01/2016
Technical data
Continental Hydraulics Installation Manual
Supply voltage
Current requirement
External protection
Digital inputs
Input resistance
Digital outputs
Analogue inputs (sensor and demand value signal)
Signal resolution
Speed input
Analogue outputs
Voltage
Signal resolution
Current
Signal resolution
Controller sample time
Serial interface
Housing
Weight
Protection class
Temperature range
Storage temperature
Humidity
Connections
EMC
[mA] <100
[A] 1 medium time lag
[V] logic 0: <2
[V] logic 1: >10
[kOhm] 25
[V] logic 0: <2
[V] logic 1: >12 (50 mA)
[V]
0… 10; 25 kOhm
[mA] 4… 20; 240 Ohm
[%] 0,003 incl. Oversampling
( maximum resolution 1 µm )
[V]
0… 10; 90 kOhm
[mA] 4… 20; 240 Ohm
[%] 0,003
[V]
2 x 0… 10; differential output
[mA] 10 (max. load)
[%] 0,006
[mA] 4… 20; 390 Ohm maximum load
[%] 0,006
[ms] 1
USB in RS 232C Emulation
(9600… 57600 Baud, 1 stop bit, no parity, echo mode)
Snap-on module to EN 50022
PA 6.6 polyamide
Flammability class V0 (UL94)
[kg] 0,170
IP20
[°C] -20… 60
[°C]
-20… 70
[%] < 95 (non-condensing)
USB-B
4 x 4-pole terminal blocks
PE: via the DIN mounting rail
EN 61000-6-2: 8/2005
EN 61000-6-4: 6/2007 ; A1:2011
Page 3 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
Functional Diagram:
Wiring Example:
Analog Speed (optional)
10/9
Speed
Analog Command Position
13/11
Analog Position Feedback
14/11
Command
Feedback
+24v
Dimensions:
+24v
Gnd
3
4
Power
Supply
8
7
5
6
Enable
Start (Run)
Hand + (jog)
Hand - (jog)
3.9"
Valve out +
15
Valve out -
16
+
-
Gnd
In Pos
12
Ready
1
2
Differential
Input on
Control Valve
0.9"
4.5"
Page 4 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
CEM-SA-B Input and output Terminal Identification
Connection
PIN 3
PIN 4
Connection
PIN 9 / 10
PIN 13
PIN 14
PIN 11 / PIN 12
PIN 15 / 16
Connection
PIN 8
PIN 7
PIN 6
PIN 5
PIN 1
PIN 2
Supply
Power supply (see technical data)
0 V (GND) connection.
Analogue signals
External speed demand (V), range 0… 10 V or 4… 20 mA (scalable)
Position demand value (W), range 0… 10 V or 4… 20 mA (scalable)
Analogue position actual value (X), range 0… 10 V or 4… 20 mA (scalable)
0 V (GND) connection for analogue signals
Valve control Output signal.
Type of signal and polarity can be selected by the parameter SIGNAL:U.
Digital inputs and outputs
Enable input:
This digital input signal initializes the application and error messages are deleted. The controller and the READY signal are activated. The output signal to the control element is enabled.
The actual position is accepted as the command position and the drive remains stationary under control at this position.
If the input is disabled, the output (control signal) is switched off(disabled). Take care of the EOUT-command!
START (RUN) input:
The position controller is active and the external analogue demand position is accepted as the demand value. If the input is disabled during the movement, the system is stopped within the set emergency stopping distance (D:S).
HAND + input:
Manual operation (START = OFF): the drive moves at the programmed speed in the programmed direction. After deactivation, the actual current position is accepted as the demand position. The START (RUN) input has priority over the HAND+ input.
If the sensor signal is missing (external ENABLE signal = ON), the drive can be operated in manual mode.
HAND - input:
Manual operation (START = OFF); the drive moves with the programmed speed in the programmed direction. After deactivation, the actual current position is accepted as the required position. The START (RUN) input has priority over the HAND- input.
If the sensor signal is missing (external ENABLE signal = ON), the drive can be operated in manual mode.
READY output:
ON: The module is enabled; there are no discernable errors.
OFF: Enable (PIN 8) is disabled or an error (sensor or internal error) has been detected.
STATUS output:
ON: INPOS message. The axis is within the INPOS window.
OFF: INPOS message. The axis is outside the INPOS window.
Page 5 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
Steps to install and configure a new application:
All parameters are adjusted using VEA-BUSB programming cable and CHI-PC Microsoft
Windows application.
1. Mount the module in a suitable location
2. Connect the power supply and valve solenoids
3. Down load and open the GUI program ( www.continentalhydraulics.com/wpcontent/uploads/2015/01/setup-CEWMPC-10-v3.5.0.zip
)
4. Connect to Laptop via USB to USB Type B communication cable.
5. Open the Options and check setting make sure the correct com port, full-Duplex and
57.6K Baud rate are selected.
Page 6 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
Module Mounting Location:
This module is to be mounted in a cabinet for protection from the local environment.
Ensure there is adequate free space around the module to allow for cooling air flow.
This module is designed to snap onto an industry standard 35mm DIN rail.
Do not mount near other modules that emit high power electrical interference, such as motor controllers and high power contactors.
Power Supply:
This module is designed to operate on DC power from a regulated power supply ranging from 12 to 30 volts. Match valve solenoid voltage rating to power supply, typically 12 or 24 volts.
A 1 amp medium ac tion fuse is recommended in the “+” power supply line.
Wiring to Valve:
Two conductors are required for each solenoid. There is no need for shielding on these power conductors.
Wire size is chosen to provide an acceptable voltage drop between the module and the valve solenoid. The following chart is based on 5% drop for 12v and 24v applications. The listed cable length is distance from module to valve, and includes the voltage drop of the return conductor.
Wire size
12 gauge
2.6A 12v
66 ft. max
1.6A 24v
215 ft. max
0.86A 24v
400 ft. max
14 gauge
16 gauge
18 gauge
20 gauge
22 gauge
49 ft. max
31 ft. max
19 ft. max
13 ft. max
8 ft. max
159 ft. max
100 ft. max
63 ft. max
39 ft. max
25 ft. max
295 ft. max
186 ft. max
117 ft. max
73 ft. max
46 ft. max
Page 7 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
Ref Page Command
10 LG
10 MODE
10 SENS
11 EOUT
12 HAND:A
12 HAND:B
12 INPOS
12 SYS_RANGE
13 SIGNAL:X
13 N_RANGE:X
13 OFFSET:X
13 SIGNAL:W
15 SIGNAL:V
15 VELO
15 VRAMP
16 VMODE
16 ACCEL
16 VMAX
17 A:A
17 A:B
17 D:A
17 D:B
17 D:S
18 V0:A
18 V0:B
18 V0:RES
18 PT1
19 CTRL
20 MIN:A
20 MIN:B
20 MAX:A
20 MAX:B
20 TRIGGER
21 OFFSET
21 SIGNAL:U
23 DC:I
23 DC:AV
23 DC:DV
23 DC:CR
CEM-SA-B Function Parameter layout
Parameter Help / Description
EN EN English
EXP Standard / Expert mode
ON Malfunction monitoring [ON / OFF /AUTO]
0 Output signal if not ready [0.01%]
3333 Manual speed [0.01%]
-3333 Manual speed [0.01%]
200 In-position-window [µm]
100 Axis working Stroke [mm]
U0-10 Type of Input
100 sensor nominal length [mm]
0 sensor offset [µm]
U0-10 Type of Input
OFF Type of Input
10000 Internal speed limitation [0.01%]
200 Ramp time for the external speed [ms] [SINGNAL:V - ON]
SDD Method of positioning
250 Acceleration [mm/s^2]
50 Maximum speed [mm/s]
100 Acceleration time [ms]
100 Acceleration time [ms]
25 Deceleration stroke [mm]
25 Deceleration stroke [mm]
10 Overtravel [mm]
25 Loop gain [1/s]
25 Loop gain [1/s]
1 Loop gain resolution
1 PR1-filter time constant [ms]
SQRT1 Control characteristic
0 Compensation of the Deadband in 0.01%
0 Compensation of the Deadband in 0.01%
10000 Output Scaling in 0.01%
10000 Output Scaling in 0.01%
200 Trigger point of the MIN function in 0.01%
0 Output offset [0.01%]
U+-10 Type and polarity of the output signal
2000 Drift compensator, I-gain [ms]
0 Drift compensator, activation value [0.01%]
0 Drift compensator, deactivation value [0.01%]
500 Drift compensator, control range [0.01%]
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
MODE
STD EXP-SDD EXP-NC
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Page 8 of 27 CEM-SA-B CHI 1020687 01/2016
LED Indications
LEDs
GREEN
Continental Hydraulics Installation Manual
Description of the LED function
Identical to the READY output.
OFF: No power supply or ENABLE is not activated
ON: System is ready for peration
Flashing: Error discovered
Only active when SENS = ON
YELLOW A
GREEN +
YELLOW A+B
Identical to the STATUS output.
OFF: The axis is outside the INPOS window.
ON: The axis is within the INPOS window.
1.
Chasing light (over all LEDs): The boot loader is active. No normal functions are possible.
YELLOW A +
YELLOW B
2.
All LEDs flash shortly every 6 s: An internal data error was detected and corrected automatically! The module still works regularly.
To acknowledge the error the module has to have power cycled.
Both yellow LEDs flash oppositely every 1 s: The nonvolatile stored parameters are inconsistent! To acknowledge the error, the data have to be saved with the SAVE command or the corresponding button in the CHI-PC. If the function of the module has changed via the FUNCTION parameter, all parameters are deleted purposely and set to default values. In this case the LEDs indicate no error, but a desired state. To acknowledge please save.
Page 9 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
Parameter Descriptions
LG (Changing the language)
Command
LG x
Parameters x= DE|EN
Unit
-
Group
STD
Either English or German can be selected for the displayed texts.
After changing the language settings, the ID button in the menu bar (CHI-PC) must be pressed
(module identification).
MODE (Switching between parameter groups)
Command
MODE x
Parameters x= STD|EXP
Unit
-
Group
STD
This command changes the operating mode. Various commands (defined via STD/EXP) are blanked out in Standard Mode. The commands in Expert Mode have a more significant influence on system behavior and should accordingly be changed with care. (see page 8)
SENS (monitoring of the modul functions)
Command Parameters Unit Group
SENS x x= ON|OFF|AUTO - STD
This command is used to activate/deactivate the monitoring functions (4… 20 mA sensors, output current, signal range and internal failures) of the module.
ON: All monitoring functions are active. Detected failures can be reset by deactivating the
ENABLE input PIN 8.
OFF: No monitoring function is active. The READY output will not function in OFF.
AUTO: Auto reset mode. All monitoring functions are active. If the failure doesn’t exist anymore, the module automatically resumes to work without deactivating the ENABLE input PIN 8.
Normally the monitoring functions are always active because otherwise no errors are detectable via the READY output. Deactivating is possible mainly for troubleshooting.
Page 10 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
EOUT (Output signal: READY = OFF)
Command Parameters Unit Group
EOUT x x= 10000… 10000 0.01 % EXP
Output value in case of a detected error or a deactive ENABLE input. A value (degree of valve opening) for use in the event of a sensor error (or the module is disabled) can be defined here.
This function can be used if, for example, the drive is to move to one of the two end positions (at the specified speed) in case of a sensor error.
|EOUT| = 0 The output is switched off in the event of an error. This is normal behavior.
CAUTION! If the output signal is 4… 20 mA, the output is switched off when |EOUT| = 0 . If a null value = 12 mA is to be output in the event of an error, EOUT must be set to 1 1 .
The output value defined here is stored permanently (independently of the parameter set). The effects should be analyzed by the user for each application from the point of view of safety.
Do not use the manual mode in conjunction with the EOUT command. After the deactivation of the HAND input the output is set to the EOUT value.
ENABLE (pin 8) digital input:
ENABLE is a digital input that is active high.
When the ENABLE input is low, there is no output to the valve. Command input and feedback input values are ignored. All other inputs are also ignored. To activate the HAND function,
ENABLE must be held active.
If ENABLE is removed during an active motion profile, the output to the valve is instantly brought to zero.
START (RUN) (pin 7) digital input:
START (RUN) is a digital input that is active high.
Bringing pin 7 high (while holding pin 8 (ENABLE) high), forces the module into closed loop position control mode.
If RUN is removed during an active motion profile, the output to the valve is ramped to zero.
1 This is necessary if using valves without error detection for signals lower than 4 mA. If the valve has an error detection, it moves into a defined position after switching off the output.
Page 11 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
HAND (Manual speed)
The Hand functions are not active when Start PIN 7 is active, to use the Hand manual speed functions the Start function must be deactivated.
Command Parameters Unit Group
HAND:i x i= A|B x= 10000… 10000 0.01%
STD
The manual speeds are set with these parameters. The drive moves in a controlled manner in the defined direction when the manual signal is active. The direction is defined by the sign of the parameters. After the manual signal has been disabled, the drive remains under control in the current position.
In case of a fault (position sensor fault), the drive can still be moved with the manual function. The output will be switched off when hand signals are turned off.
The manual speed is also limited by the (internal or external) speed demand (MIN evaluation).
Caution! Do not use the manual mode in conjunction with the EOUT command. After the deactivation of the HAND input the output is set to the EOUT value.
INPOS (In position range)
Command Parameters Unit Group
INPOS x x= 2… 200000 µm STD
This parameter is entered in µm.
The INPOS command defines a range for which the INPOS message is generated. This function monitors the failure between the command and actual position. If the failure is less than the programmed value a INPOS message at the status output (see Pin description). The positioning process is not influenced by this message.
PIN 7 (START) must be activated to generate the INPOS messages.
SYS_RANGE (Working stroke)
Command Parameters Unit Group
This command defines the full stroke, which corresponds to 100 % of the input signal. If the demand is set incorrectly, this leads to incorrect system settings, and the dependent parameters such as speed and gain cannot be calculated correctly.
Page 12 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
SIGNAL (Type of input)
Command Parameter Unit Group
SIGNAL:i x i= x=
W|X|V
OFF
U0-10
- EASY
U10-0
I4-20
I20-4
This command can be used to change the type of input signal (voltages or current) and to define the direction of the signal. This command is available for all analog inputs (W, X, and V).
OFF= Deactivation of the input 2 .
See ANIMODE section (page 24-25) if the Signals used are not listed above, for re-scaling as required.
N_RANGE: X (Nominal range of the sensor)
Command Parameter Unit Group
N_RANGE:X x x= 10… 10000 mm EASY
N_RANGE (nominal range or nominal stroke) is used to define the length of the sensor. This value should be always higher than SYS_RANGE. The control parameter cannot be calculated correctly in case of wrong values.
OFFSET: X (Sensor offset)
Command Parameter Unit
OFFSET:X x x= 100000… 100000 µm
Adjustment of the zero point of the sensor.
Group
EASY
2 The deactivation can be used to deactivate the velocity (speed) input PIN_9/10 (the VELO value is active).
Page 13 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
Using of the commands SYS_RANGE, N_RANGE: X and OFFSET: X
If the Cylinder stroke and the feedback device are matched, the standard factory settings will not require any changes.
In systems where these are not matched, the commands SYS_RANGE, N_RANGE: X and
OFFSET: X must be scaled to match. The application scaling will be done by these three commands.
In this example (Figure 1) the system is defined by a length of 120 mm of the sensor, a working stroke of 100 mm of the cylinder and an offset of 5 mm. These parameters have to be typed in and the axis is driving between 5 mm and 105 mm of the sensor stroke and between 0 mm and
100 mm of the cylinder stroke.
Correct scaling:
SYS_RANGE = 100 (mm)
N_RANGE: X = 120 (mm)
OFFSET: X = -5000 (µm)
100,00 mm
120,00 mm
5,00 mm
Figure 1 (Input scaling of the sensor)
Page 14 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
Speed commands
The SIGNAL: V command is used to switch over between external or internal speed limitations.
SIGNAL: V = OFF Internal speed limitation (VELO command)
SIGNAL: V = U0-10 External speed limitation (0-10 Volt)
PIN 9/10 is used for external speed limitation 3 .
See ANIMODE section (page 24-25) if the Signals used are not listed above, for re-scaling as required.
VELO (Internal speed demand value)
Command Parameters
VELO x x= 1… 10000
Unit
0.01 %
Group
SIGNAL:V =
OFF
Specification of the internal speed limitation.
VRAMP (Ramp time for external speed demand)
Command Parameters Unit Group
VRAMP x x= 10… 5000 ms SIGNAL:V
The rate of change of the external speed demand can be limited by this ramp time. The command is only active if external speed demand (SIGNAL:V <> OFF) has been parameterized.
3 The output signal is directly limited in SDD mode (default mode). In NC mode the speed profile of the generator is limited. The lowest adjustable speed is 0.01 mm/s (VMAX = 1 mm/s and VELO = 1 %).
Page 15 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
VMODE (Methode of positioning)
Command Parameters Unit Group
VMODE x x= SDD|NC EXP
The fundamental control structure can be changed with this parameter.
SDD: S trokeD ependent D eceleration. In this mode, stroke-dependent deceleration is activated. This mode is the default mode and is suitable for most applications. With stroke-dependent deceleration, the drive comes to a controlled stop at the target
NC: position. From the deceleration setpoint, the drive then switches to closed loop control mode and moves accurately to the desired position. This control structure is very robust and is insensitive to external influences such as fluctuating pressures. One disadvantage is that the speed varies with the fluctuating pressure as the system runs under open-loop control.
N umerically C ontrolled. In this mode a position profile is generated internally. The system always works under control and uses the following error to follow the position profile. The magnitude of the following error is determined by the dynamics and the closed loop gain. The advantage is that the speed is constant (regardless of external influences) due to the profile demand. Because of continuous control, it is necessary to run at less than 100 % speed, as otherwise the errors cannot be corrected. 70… 80
% of the maximum speed is typical although especially the system behavior and the load pressure should be taken into account when specifying the speed.
ACCEL (Acceleration in NC mode)
Command Parameters Unit Group
ACCEL x x= 1… 20000 mm/s² VMODE=NC
This command is used to define the acceleration rate in NC mode. The command is only active if the VMODE has been parameterized to NC.
VMAX (Maximum speed in NC mode)
Command Parameters Unit Group
VMAX x x= 1… 2000 mm/s VMODE=NC
Specification of the maximum speed in NC mode. This value is defined by the drive system and should be specified as precisely as possible (not too high under any circumstances). The speed is scaled by means of the VELO value or via the external speed demand (PIN 10 and 9). The command is only active if the VMODE has been parameterized to NC.
Page 16 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
A:A and A:B (Acceleration (ramp) time)
Command Parameters Unit Group
A:i x i= A|B VMODE=SDD x= 1… 5000 ms
Ramp function for the 1 st (A solenoid) and 3 rd (B solenoid) acceleration quadrants only.
The acceleration time for positioning is dependent on the direction. “A” corresponds to connection
15 and “B” corresponds to connection 16 (if POL = +).
Normally A = flow P-A, B-T and B = flow P-B, A-T.
For quadrants 2 and 4, parameters D:A and D:B are used as the deceleration distance demand when the SDD funcion is in control.
D:A / D:B / D:S (Deceleration / braking distance)
Command Parameters Unit Group
D:i x i= A|B|S x= 1… 10000 mm
VMODE = SDD
This parameter is specified in mm 4 .
The deceleration stroke is set for each direction of movement (A or B). The control gain is calculated internally depending on the deceleration distance. The shorter the deceleration distance, the higher the gain. A longer deceleration distance should be specified in the event of instability.
Parameter D:S is used as the stopping ramp when disabling the START (PIN 7) signal. After disabling, a new target position (current position plus D:S) is calculated in relation to the speed and is specified as a command value.
G
Intern
STROKE
Calculation of control gain
D i
CAUTION: If the maximum stroke (SYS_RANGE command) is changed, the deceleration distance must also be adjusted. Otherwise this can result in instability and uncontrolled movements.
4 CAUTION!
In older modules this parameter was specified in % of the maximum stroke. Since data specification for this module has now been converted to mm, the relationship between the stroke
(SYS_RANGE command) and these parameters must be taken into account.
Page 17 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
V0:A / V0:B (Loop gain setting)
Command Parameters Unit Group
V0:i x i= A|B x= 1… 400 s -1
VMODE = NC
This parameter is specified in s -1 (1/s).
In NC Mode normally the loop gain is specified rather than the deceleration stroke 5 .
The internal gain is calculated from this gain value together with the parameters VMAX and
SYS_RANGE.
D i
v max
V
0
Calculation of the internal control gain
G
Intern
STROKE
D i
In NC Mode the following error at maximum speed is calculated by means of the loop gain. This following error corresponds to the deceleration stroke with stroke-dependent deceleration. The conversion and therefore also the correct data demands related to the closed loop control system are relatively simple if the relationship described here is taken into account.
V0:RES (Scaling of the loop gain)
Command Parameters Unit
V0:RES x x= 1|100 -
V0:RES = 1 loop gain in s -1 (1/s) units.
V0:RES = 100 loop gain in 0.01 s -1 units 6 .
The increased resolution should be used in case of V0 < 4.
Group
VMODE = NC
PT1 (Timing of the controller)
Command Parameter Unit Group
PT1 x x= 0… 300 ms EXP
This parameter can be used to change the internal timing of the control function.
Hydraulic drives are often critical to control especially in case of high speeds and very fast valves.
The PT1 filter can be used to improve the damping rate and allows therefore higher loop gains.
Requirements for the use are: The natural frequency of the valve should be equal or higher than the natural frequency of the drive.
5 The loop gain is alternatively defined as a KV factor with the unit (m/min)/mm or as V
0
in 1/s. The conversion is
KV = V
0
/16,67.
6 In case of very low loop gains (1 s -1 to 3 s -1 ) the better resolution of the adjustment should be selected.
Page 18 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
CTRL (Deceleration characteristics)
Command Parameters Unit Group
CTRL x x=
LIN|SQRT1|SQRT2
- STD
The deceleration characteristic is set with this parameter. In case of positively overlapped proportional valves the SQRT function should be used. The non-linear flow function of these valves is linearized by the SQRT 7 function.
In case of zero lapped valves (control valves and servo valves) the LIN or SQRT1 function should be used regardless of the application. The progressive characteristic of the SQRT1 function has better positioning accuracy but can also lead to longer positioning times in individual cases.
LIN: Linear deceleration characteristic (gain is increased by a factor of 1).
SQRT1: Root function for braking curve calculation. The gain is increased by a factor of 3 (in the target position). This is the default setting.
SQRT2: Root function for braking curve calculation. The gain is increased by a factor of 5 (in the target position). This setting should only be used with a significantly progressive flow through the valve.
Braking stroke
D:A or D:B
Deceleration time
D:A or D:B
CTRL = SQRT
CTRL = SQRT
CTRL = LIN
CTRL = LIN
Stroke Time
Figure 2 (Braking function with respect to stroke and time)
7 The SQRT function generates constant deceleration and thus reaches the target position faster. This is achieved by increasing the gain during the deceleration process.
Page 19 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
MIN:A / MIN:B (Dead band compensation)
MAX:A / MAX:B (Output scaling)
TRIGGER (Response threshold for the MIN parameter activation)
Command Parameters Unit Group
MIN:i x i= A|B x= 0… 6000 x= 3000… 10000
-
0.01 %
STD
MAX:i x 0.01 %
TRIGGER x x= 0… 4000 0.01 %
The output signal to the valve is adjusted by means of these commands. A kinked volume flow characteristic is used instead of the typical overlap step for the position controls. The advantage is better and more stable positioning behavior. At the same time, kinked volume flow characteristics can also be adjusted with this compensation 8 .
If there should also be adjustment options for deadband compensation on the valve or valve amplifier, it must be ensured that the adjustment is performed either at the power amplifier or in the module.
If the MIN value is set too high, this has an effect on the minimum speed, which can then no longer be adjusted. In extreme cases this leads to oscillation around the controlled position.
MAX:A non lineare Flow compensation
Standard deadband compensation
MIN:A
Input
MIN:B TRIGGER
MAX:B
8 Various manufacturers have valves with a defined nonlinear curve: e.g. a kink at 40 or 60 %
(corresponding to 10 % input signal) of the nominal volume flow. In this case the TRIGGER value should be set to 1000 and the MIN value to 4000 (6000).
If zero lapped or slightly underlapped valves are used, the volume flow gain in the zero range (within the underlap) is twice as high as in the normal working range. This can lead to vibrations and jittery behavior. To compensate this, the TRIGGER value should be set to approximately 200 and the MIN value to 100. The gain in the zero point is thus halved and an overall higher gain can often be set.
Page 20 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
OFFSET (Zero correction)
Command Parameters Unit Group
OFFSET x x= 4000… 4000 0.01 % STD
This parameter is entered in 0.01% units.
The offset value is added to the output value. Valve zero offsets can be compensated with this parameter.
SIGNAL:U (Type and polarity of the output signal)
Command Parameter Unit Group
SIGNAL:U x x= U+-10
I4-12-20
U-+10
- EXP
I20-12-4
This command is used to define the output signal (voltage or current) and to change the polarity 9 .
Differential output ± 100 % corresponds with ± 10 V (0… 10 V at PIN 15 and PIN 16).
Current output ± 100 % corresponds with 4… 20 mA (PIN 15 to PIN 12). 12 mA (0 %) = center point of the valve.
An output current of << 4 mA indicates an error and the module is disabled. The current input of the proportional valves should be monitored by the valve. The valve have to be deactivated in case of < 4 mA input signal. Otherwise the EOUT command can be used to get a defined output signal.
See ANIMODE section (page 24-25) if the Signals used are not listed above, for re-scaling as required.
9 The older POL command is removed.
Page 21 of 27 CEM-SA-B CHI 1020687 01/2016
Special commands
Continental Hydraulics Installation Manual
Drift compensation / high accurate positioning
The high accurate positioning or the drift compensation can be used in case of external influence which is limiting the positioning accuracy. This function could be critical if limit cycling 10 by wrong parameterization or the system behavior was not taken into account.
Which positioning errors can be compensated 11 ?
1. Zero point adjustment of the valve. By this kind of failure, a constant offset between command and feedback signal remains. This failure is more or less constant.
2. Zero point failure depending on the temperature. The same behavior as point 1, but the failure is increasing slowly (over the temperature).
3. Position failure caused by an external force. All control and servo valves have a typical pressure gain characteristic. In case of external forces an output signal of 2…3 % has to be generated for the compensation of this force. And this signal is proportional to the positioning error. Compared with point 1 and 2, the positioning failure generated by the force signal can vary cycle to cycle.
How does it work?
High accurate positioning
These kinds of position errors should be compensated when the axis is near by the target position. The output signal is going lower and lower but a system specific position error remains.
At the activation point this function – a slowly working integrator – is active. This integrator signal is added to the output signal and will compensate offsets and other failure. To prevent instabilities, the integrator value will be frozen when the output value is lower than the deactivation point.
Typical setup
Valve pressure gain: 2.5 %; the activation point has to be set to 3 … 5 % (DC:AV 300… 500).
Valve hysteresis: 0.5 %; the deactivation point has to be set to 0 .7… 1.0 % (DC: DV 70… 100).
The lower the value the better the accuracy.
DC:CR should be equal to DC:AV.
The optimum integrator time has to be determined experimentally. Starting with higher values is recommended.
10 The “limit cycling” is a small and permanent oscillation around the target position. The main reason are static frictions and the hysteresis of the valve. By proper parameter setting, this can be avoided under the boundary condition that the desired accuracy is not achieved. In this case, the hydraulic system is the limiting factor in the accuracy.
11 This is relevant for zero lapped control valves and servo valves.
Page 22 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
DC:AV (Activation value)
DC:DV (Deactivation value)
DC:I (Integrator time)
DC:CR (Integrator limitation)
Command Parameter Unit Group
DC:AV
DC:DV
DC:I x x x x= 0… 2000 x= 0… 1000 x= 0… 2000
0.01 %
0.01 % ms
EXP
DC:CR x x= 0… 500 0.01 %
DC:AV This parameter is used to define the activation point (activation value). The DC function is completely deactivated in case of DC: AV = 0.
DC:DV This parameter is used to define the deactivation point (DV = deactivation value) Within the deactivation window no compensation value will be calculated
(frozen state). DC: AV = 0 should be used for best positioning, but „limit cycling
“can occur. This value should be set to 50 % of an acceptable error.
DC:I This parameter is used to define the integrator time. The lower this value the faster the compensation. Low values will result in „limit cycling“.
DC:CR the output range of the DC function will be limited (CR = control range) by this parameter.
PROCESS DATA (Monitoring)
Command
WA
Description
Demand value (input signal)
Unit
mm
W
Demand value (according to the profile generator) mm
V
Speed input %
X
Actual value mm
E
Error value mm
C
Output of the controller %
U
Output signal of the module %
IA
Solenoid current A mA (P Version only)
IB
Solenoid current B mA (P Version only)
The process data are the variables which can be observed continuously on the monitor or on the oscilloscope
Page 23 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
AINMODE
The AINMODE is used to define the type of analog input signals being used.
The standard default setting of AINMODE is EASY. In the EASY mode the SIGNAL:W/X/V (see page 13) are only available in the most commom 0-10 volt or 4-20mA values.
If the input signal being used are not as listed, the AINMODE is available in the MATH mode where the input signals can be scaled by a linear equation.
To enter the MATH option, you must change the AINMODE to MATH by use of the Terminal
Window. (see steps 1-4 below)
Once in the Termainal Window screen type in AINMODE MATH and click the Save button. At this time you may go back to the Parameter screen where you can use the user defined scalling feature.
Once in the MATH mode you will be able to scale the various input signals as shown below.
Page 24 of 27 CEM-SA-B CHI 1020687 01/2016
Continental Hydraulics Installation Manual
Analogue input scaling parameters
Command Parameters
AIN:I a b c x i = A|B a= -10000… 10000 b= -10000… 10000 c= -10000… 10000 x = V|C
Unit
-
-
-
0.01%
-
Group
EXP
FUNCTION
AA
A-B
This command offers an individual scalable input. The following linear equation is used for the scaling.
Output = A/B ∙ (Input – C)
The
“C” value is the offset (e.g. to compensate the 4 mA in case of a 4… 20 mA input signal).
The variables A and B are defining the gain factor with which the signal range is scaled up to
100 % (e.g. 1.25 if using 4… 20mA input signal, defined in default current settings by A = 1250 and B = 1000). The internal shunt for the current input signal is activated when parameters AIN:A and AIN:B are set to Current (X=C).
The gain factor is calculated by dividing total input signal range ( A ) by the actual input range ( B ).
In the case of a 4-20mA with a single solenoid valve, the total range is 0-20mA, which means
A=20 . The actual range is 4-20 mA, therefore, B= (20-4) =16 . An offset, C , must be added to compensate for the 0-4mA not being used of the full range. The offset is 4mA/20mA=0.2 or 20%.
Therefore C=2000 since the unit value for C is 0.01%.
Shown in the below table are the most common input command signal and the corresponding settings to be used.
Typical settings (examples):
Command
AIN:X 1000 1000 0 V
AIN:X 10 8 1000 V OR
AIN:X 1000 800 1000 V
AIN:X 10 4 500 V OR
AIN:X 1000 400 500 V
AIN:X 20 16 2000 C OR
AIN:X 2000 1600 2000 C OR
AIN:X 1250 1000 2000 C
Input Description
0… 10 V Range: 0… 100 %
1… 9 V Range: 0… 100 %; 1 V = 1000 used for the offset and gained by 10 / 8 (10 V divided by 8 V (9 V -1 V))
0.5… 4.5 V Range: 0… 100 %; 0.5 V = 500 used for the offset and gained by 10 / 4 (10 V divided by 4 V (4.5 V -0.5 V))
4… 20mA Range: 0… 100 %
The offset will be compensated on 20 % (4 mA) and the signal (16 mA = 20 mA – 4 mA) will be gained to 100 %
(20 mA).
Each of this parameterization for 4… 20 mA is setting the range to 0… 100 %.
Page 25 of 27 CEM-SA-B CHI 1020687 01/2016
Troubleshooting
Continental Hydraulics Installation Manual
It is assumed that the device is in an operable state and there is communication between the module and the CHI-PC. Furthermore, the valve control parameterization has been set with the assistance of the valve data sheets.
FAULT CAUSE / SOLUTION
ENABLE is active, the module does not respond and the READY LED is off.
ENABLE is active, the READY LED is flashing.
There is presumably no power supply or the ENABLE signal (PIN 8) is not present.
If there is no power supply, there is also no communication via our operating program. If a connection has been made to the CHI-PC, then a power supply is also available.
If the power supply exists, an attempt should be made to see whether the system can be moved by means of the HAND+ and HAND- inputs (measuring the output signal to the valve helps).
The flashing READY LED signals that a fault has been detected by the module.
The fault could be:
A broken cable or no signal at the input (PIN 13 or PIN 14), if 4… 20 mA signals are parameterized.
Internal data error: press the command/SAVE button to delete the data error. The system reloads the DEFAULT data.
With the CHI-PC operating program the fault can be localized directly via the monitor.
ENABLE is active; the READY LED is on, the system moves to an end position.
ENABLE is active, the READY LED is on, the STATUS
LED is not on, the system moves to the target position but do esn’t reach it
(positioning error).
The control circuit polarity is incorrect. The polarity can be changed with the
POL command or by reversing the connections to PIN 15 and PIN 16.
Serious positioning errors can result from incorrect parameterization or incorrect system design.
Is the cylinder position specified correctly?
Are the deceleration strokes correct (to start the system, the deceleration distances should be set to approx. 20… 25 % of the cylinder position
12) ?
Is the valve a zero lapped control valve or a standard proportional valve?
In the case of a proportional valve, the valve overlap which may be present should be compensated for with the MIN parameters. Typical values are to be found in the valve data sheet.
ENABLE is active,
The system is working and also actuating the valve.
12 The stability criterion of the hydraulic axes must be taken into account.
Page 26 of 27 CEM-SA-B CHI 1020687 01/2016
FAULT the READY LED is on, and the system oscillates on the target.
Continental Hydraulics Installation Manual
CAUSE / SOLUTION
Various potential problems could be:
The parameterization is not yet adjusted to the system (gain too high).
There is severe interference on the power supply.
Very long sensor cables (> 40 m) and sensor signal interference.
The MIN setting to compensate the valve overlap is too high.
As a basic principle, the parameterization of the sensor data and the controller settings must be carried out first (before switching on). An incorrect demand is equivalent to incorrect system design which then leads to incorrect operation. If the system oscillates, the gain should first be reduced (longer deceleration distances for D:A and D:B) and in the case of overlapped valves the MIN parameter should also be reduced.
Speed too low
Speed too high
The drive may be able to move to position but the speed is too low.
Check the control signal to the valve.
Via the integrated oscilloscope (U variable).
Measure the signal to the valve with an external oscilloscope / voltmeter.
If the control is within the range of ± 100 % (± 10 V), the fault must be sought in the hydraulics.
If the control signal is relatively low, the following points should be checked:
Is the internal/external speed signal limiting the speed?
Which setting has been specified for the deceleration distance in relation to the POSITION?
The drive should move to position. The drive moves in and out too fast leading to uncontrolled behavior. Reducing the speed (MAX or VELO parameter) has very little or no effect.
The hydraulic system is over-sized. The entire parameterization of the movement cycle cannot be reproduced (overlap and deceleration distance settings)
Page 27 of 27 CEM-SA-B CHI 1020687 01/2016