Installation Manual
HPCCS
WARNING: DO NOT LIFT FIXTURE BY CABLES.
This could result in permanent damage to both the fixture and the cables. Damage resulting from grasping cables and/ or putting undue pressure on the cable connections will not be covered under the warranty!
DO NOT ATTEMPT TO INSTALL OR USE THE HPCCS FIXTURE WITHOUT READING THE INSTALLATION
INSTRUCTIONS AND SAFETY LABELS COMPLETELY.
Failure to adhere to these instructions could result in serious injury or property damage.
DO NOT MODIFY, ALTER OR ATTEMPT TO SERVICE THE HPCCS. DOING SO WILL VOID THE WARRANTY.
Installation Instructions
HPCCS
Indoor/Outdoor Line Voltage
Introduction:
The Boca Flasher’s HPCCS is perfect for color washing long runs and large areas. LEDs are spaced 1.00” apart in a two rows to create an even wide wash of light. The housing is anodized aluminum and is weather and abrasion resistant. This light fixture can use any standard
DMX 512 controller or can incorporate Boca Flasher’s Digital Mainframe controller (Demo Version Only). The Digital Mainframe can run independently, creating many stand-alone color washing and solid color effects, as well as responding to DMX commands for total control of your lighting experience.
Maintenance:
CLEAnInG Dry and Damp (IP65) Rated Fixtures: To clean surface use a soft damp cloth.
Wet (IP68) Rated Fixtures: To clean surface use a soft cloth with mild soap & water.
STORAGE Store in a dry, well-ventilated area when product is not in use.
Keep the electrical cord away from heated surfaces when in use or not in use.
If cord shows signs of damage do not use, return product to manufacturer.
Electrical Specifications:
1. Input Voltage: 90-120VAC or 230-277VAC
(See layout drawings for spec.)
2. Total linear ft per 20A breaker: 55 ft.
3. Total linear ft per 15A breaker: 40 ft.
4. Input Current: 272mA RMS per linear ft. for RGB,
272mA RMS per linear foot for WM
Fixtures must be installed by a qualified and licensed electrician in accordance with all national, state and local electrical codes and regulations. If any part of this manual does not meet the necessary codes and regulations, contact the factory for more information before attempting to install.
IP65
DAMP LISTING
IP68
WET LISTING
Model Dependent
Max temp: 55C
Min. temp: -40C
Turn Power Off At Circuit Breaker Before Beginning Installation!
DO NOT LIFT FIXTURE BY CABLES!
INCLUDED IN ThIS PACkAGE:
1 HPCCS Fixture
(In lengths shown on job specific drawings)
2 Mounting Brackets
(2 brackets per fixture)
3 Job Specific Drawings
Fixed
Rotate Fixture to see label on bottom.
Power cord length is
6.5 ft. per UL standard.
DMX cables are
5 ft. long.
PAGE 2 OF 6 or
Hinged
AC100
Installation Instructions
HPCCS
1. INSTALL CLIPS INTO SUBSTRATE
1a 1b 1c
Determine layout of fixture or composition of fixtures and locate appropriate clip location.
CLIP MUST BE A MINIMUM OF 4.5” FROM END-CAP TO
ALLOW CLEARANCE OF MOLDED CORDS.
Screw Information:
1. Screws not provided by Boca Flasher.
2. Boca Flasher recommends wide washer flat head Philips
#8 screw (not to exceed .418”).
3. Length of screw will vary depending on mounting surface.
4. For outdoor installations, installer should use a screw with weather proof coating.
5. One foot fixtures only require one hinge bracket.
2. INSTALL FIXTURE INTO FIXED CLIPS
2a
Angle fixture into opening, pushing clip wider as you push.
2b
Tab on side of clip should go in notch at the top of the fixture.
2c
Clip will securely snap into place.
snap!
3.
INSTALL FIXTURE INTO HINGE CLIPS
3a 3b
Installing Hinge Clips:
Hinge clips come installed on the fixture.
Therefore it is easy to determine where to predrill the holes into the substrate before doing so. Installing is only a matter of drilling in the proper screws, recommended.
PAGE 3 OF 6
4. CONNECT DMX CABLES TOGEThER
AS ShOwn On jOb SPECIFIC dRAwInGS
4a
Rotate fixture to see bottom and note each label.
4a
Cross-reference with Job
Specific Drawing.
▶
▶
▶
Labels on fixtures correspond with nomenclatures on drawings.
BF-01
◀
▶
▶
HPCCS
The HPCCS does not daisy-chain by power.
*
* Consult factory for options.
Installation Instructions
HPCCS
NOTE:
Contractor cannot install more than 32 fixtures per data stream.
4c
Connect DMX IN on a fixture with
DMX out separate fixture.
4d
Push together until you hear a “Click”.
DMX Out
DMX In
DMX Out
Power Feed
DMX In
DMX Out
click!
DMX In
NOTE:
Outdoor version will screw together, not click.
PAGE 4 OF 6
Installation Instructions
HPCCS
5. CONNECT FIXTURES TO POWER AND CONTROLS
SInGLE Run InSTALLATIOn
Black (Line)
White (Neutral)
Black (Line)
White (Neutral)
Note: More than one connection can be made in each connection box.
Green (Ground)
Green (Ground)
NOTE:
Contractor cannot install more than 32 fixtures per data stream.
For Exterior use Only
Power Cable is 6.5ft per UL standard
*Note: XLR 5 pin DMX connection standard.
Cable is typically 5 ft in length. Call Factory for more information.
RJ45 (Ethernet) to an XLR connection is available upon request.
MuLTI Run InSTALLATIOn
Power Cable is 6.5ft per UL standard
(5 ft)
ADD Tape
(5 ft) (5 ft) (5 ft)
* For weather-tight applications only . See additional instructions for weather-tight tape .
* Add tape to twist locks.
Place thumb over tape at starting point and
PULL around connector area until tape overlaps itself.
Note: More than one connection can be made in each connection box.
NOTE:
Contractor cannot install more than 32 fixtures per data stream.
Black (Line)
White (Neutral)
*Note: XLR 5 pin DMX connection standard. Cable is typically 5ft in length. Call Factory for more information. RJ45 (Ethernet) to an XLR c o n n e c it o n i s a v a li a b l e u p o n r e q u e s t .
(XLR 5-pin)
(XLR 5-pin)
(5 ft) (5 ft) (5 ft) (5 ft)
Green (Ground)
White (Neutral)
Green (Ground)
(5 ft)
(5 ft)
ADD Tape
(5 ft)
(5 ft)
* For weather-tight applications only . See additional instructions for weather-tight tape .
PAGE 5 OF 6
* Add tape to twist locks.
Place thumb over tape at starting point and
PULL around connector area until tape overlaps itself.
Installation Instructions
HPCCS
IMPORTANT SAFETY REMINDERS:
1. DANGER:
To reduce the risk electric shock, always unplug the HPCCS from electrical outlet before
cleaning. Cut breaker if outlet is not available.
2. To reduce the risk of burns, fire, electric shock or injury to persons:
• Use the HPCCS only for its intended use as described in these instructions.
• Do not use attachments not recommended by Boca Flasher.
• Never operate the HPCCS if it has a damaged cord, cable or plug, if it is not working
properly, if it has been dropped or damaged, or dropped into water.
• If the seal appears to be damaged/broken/torn return the fixture to a service center for
examination or repair.
• Keep cables away from heated surfaces.
• Never drop or insert any object into any opening.
• Do not operate where aerosol (spray) products are being used or where oxygen is
being administered.
3. WARNING:
Do not attempt to install or use the HPCCS without reading the installation instructions
and safety labels. Failure to adhere to these instructions could result in serious injury
or property damage.
4. Do not modify, alter or attempt to service the HPCCS:
Doing so will void the warranty.
5. Do not use sharp tools near or on the fixture lens:
Doing so will result in property damage and void the warranty.
boca Flasher, Inc.
508 S. Military Trail n deerfield beach, Florida n 33442 uSA
Phone: 561-989-5338 n Fax: 561-982-8323 www.bocaflasher.com
We are constantly improving our fixtures and reserve the right to change options and specifications. Additional information & details at www.bocaflasher.com. For specific requirements, contact your Boca Flasher sales representative. Boca Flasher, Inc. 508
S. Military Trail, Deerfield Beach, Florida 33442 USA Phone: 561.989.5338 Fax: 561.982.8323 © 2017 Boca Flasher, Inc. All rights reserved. All names and trademarks are property of their respective owners. REV 06-2017
IP65
DAMP LISTING
IP68
WET LISTING

Public link updated
The public link to your chat has been updated.
Advertisement