Continental Hydraulics Installation Manual
CEM-PA-B
Product Description:
This closed loop PID amplifier, drives a single solenoid proportional pressure or flow control valve coil up to 2.6A. It is suitable to provide precise closed loop control in pressure, force, or velocity systems. This module uses traditional PID error correction to provide stable control in dynamic systems.
A wide range of analog signals are accepted. User may select either voltage or current input mode. These inputs are easily scaled to match system requirements. Input command can be ramped. PID variables are adjustable over a wide range. The
Amplifier is easily switched from open loop to closed loop control.
Min and Max output current are adjustable. Output characteristics can be independently customized. The module is disabled if the coil outputs are shorted or open. If command current signal is outside of the proper range, the module is disabled. PWM and Dither are user adjustable.
This module is easily adapted to a variety of system requirements. All variables are user adjusted with easy to use software on your Microsoft Windows laptop. Control variables are stored in non-volatile memory internal to the module. All variables can be read by the laptop, and reproduced exactly on other modules.
Page 1 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
Table of Contents
Information Description Page #
Technical Data ………………………………………………………………….. 3
Steps to install and configure a new application ……………………………. 4-5
Module Mounting Location …………………………………………………….. 5
Power Supply …………………………………………………………………… 5
Wirin g to Valve ………………………………………………………………….. 5
Circuit Diagram …………………………………………………………………. 6
LED Definitions …………………………………………………………………. 7
Terminal Identification ………………………………………………………….. 7
Parameter List …………………………………………………………………… 8
Command Parameter Descriptions
LG (Language) ………………………………………………………….. 9
MODE ……………………………………………………………………. 9
SENS …………………………………………………………………….. 9
EOUT …………………………………………………………………….. 10
SYS_RANGE ……………………………………………………………. 10
SIGNAL:X / SIGNAL:W ………………………………………………… 10
AINMODE (Signal Scaling mode)……………………………………… 11-12
N_RANG E:X …………………………………………………………….. 13
OFFSET :X ……………………………………………………………….. 13
RA:UP / RA:DOWN (Ramp times) …………………………………….. 14
C:P, C:I, C:D, C: D_TI, C:D_FF ………………………………………… 15
C:I_LIM / C :I_ACT ………………………………………………………. 16
MIN ………………………………………………………………………... 17
MAX ………………………………………………………………………. 17
TRIG GER ………………………………………………………………… 17
SIGNA
L:U ………………………………………………………………… 18
CURRE
NT ……………………………………………………………….. 18
DFREQ / DAMPL ………………………………………………………... 18
PW
M ……………………………………………………………………… 19
ACC ………………………………………………………………………. 19
PPWM / IPWM …………………………………………………………… 20
Process Data (Moni toring) ……………………………………………………… 20
Failure Monitori ng ……………………………………………………………….. 21
Troubleshooti ng …………………………………………………………………. 22-24
Page 2 of 24 CEM-PA-B CHI 1020688 01/2016
Technical data
Continental Hydraulics Installation Manual
Supply voltage
Current requirement
External protection
Reference voltage
Digital inputs
Input resistance
Digital outputs
Analogue inputs:
Command value
Signal resolution
Sensor value
Signal resolution
PWM output
PWM frequency
Sample time (pressure control)
Sample time (solenoid current control)
Serial interface
Housing
Weight
Protection class
Temperature range
Storage temperature
Humidity
Connections
EMC
Page 3 of 24
[mA] 60 + solenoid current
[A] 3 medium time lag
[V] 8 (max. 25 mA load)
[V] logic 0: < 2
[V] logic 1: > 10
[kOhm] 25
[V] logic 0: < 2
[V] logic 1: > 12 (50 mA)
[V]
0… 10; 150 kOhm
[mA]
4… 20; 390 Ohm
[%] 0.006 incl. Oversampling
[V]
0… 10; 90 kOhm
[mA]
4… 20; 390 Ohm
[%] 0.006 incl. Oversampling
[A]
0.5, to 2.6 Amp; broken wire and short circuit monitored
[Hz] 61… 2604
[ms] 1
[ms] 0.125
USB type B
Virtual COM port driver (CHI-PC):
9600… 57600 Baud (Default = 57600),
1 Stop bit, No parity, No handshake
Snap-on module to EN 50022
PA 6.6 polyamide
Flammability class V0 (UL94)
[kg] 0,190
IP20
[°C]
-20… 60
[°C]
-20… 70
[%] < 95 (non-condensing)
USB Typ B
4 x 4-pole terminal blocks
PE: via the DIN mounting rail
EN 61000-6-2: 8/2005
EN 61000-6-4: 6/2007 + A1:2011
CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
Steps to install and configure a new application:
All parameters are adjusted using VEA-BUSB-A programming cable and CHI-PC Microsoft
Windows application.
1. Mount the module in suitable location. See page 5.
2. Connect the power supply, valve connections and enable.
3. Download and open the GUI program ( www.continentalhydraulics.com/wpcontent/uploads/2015/01/setup-CEWMPC-10-v3.5.0.zip
)
4. Connect to laptop via USB to USB Type B communication cable.
5. Select com port in upper left hand corner of the GUI program.
6. Open the Options Tab and verify that the correct com port, full Duplex and 57.6K Baud rates are selected.
7. Connect with the CEM by selecting the connect button.
8. Click on the ID Button.
9. Adjust CURRENT parameter to match the nominal solenoid current.
10. Adjust dither amplitude, DAMPL , and dither frequency, DFREQ , to optimize performance of valve.
11. Set the SIGNAL type to voltage (0-10V) or current (4-20ma). See ANIMODE if the signals are other than standard. Some scaling may be required.
12. Set the MIN, MAX, and TRIGGER, for the desired system output.
13. Adjust the SYS_RANGE to the pressure output of the valve at rated current. For example, the Continental model VER03M-210-A-K1-24D is rated for 210 bar. Set the
SYS_RANGE X to 210. The units on this parameter is bar.
Page 4 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
14. Set the N_RANGE:X to the maximum pressure rating of the pressure sensor. For a 0-
210 bar pressure transducer, set N_RANGE:X to 210 bar. This setting should be the same or greater than the SYS_RANGE value.
15. Use the OFFSET:X to compensate for the pressure transducer reading at actual 0bar pressure.
16. Adjust RAMP as required.
17. Set internal monitor function, SENS , as required.
18. Adjust PID error correction parameters, (C:P, C:I, C:D, C:D_TI, C:FF), to tune the system performance.
Module Mounting Location:
This module is to be mounted in a cabinet for protection from the local environment.
Ensure there is adequate free space around the module to allow for cooling air flow.
This module is designed to snap onto an industry standard 35mm DIN rail.
Do not mount near other modules that emit high power electrical interference, such as motor controllers and high power contactors.
Power Supply:
This module is designed to operate on DC power from a regulated power supply ranging from 12 to 30 volts. Match valve solenoid voltage rating to power supply, typically 12 or
24 volts. A 3 amp medium action fuse is recommended in the “+” power supply line.
Wiring to Valve:
Two conductors are required for each solenoid. There is no need for shielding on these power conductors.
Wire size is chosen to provide an acceptable voltage drop between the module and the valve solenoid. The following chart is based on 5% drop for 12v and 24v applications.
The listed cable length is distance from module to valve, and includes the voltage drop of the return conductor.
Wire size
12 gauge
14 gauge
16 gauge
18 gauge
20 gauge
22 gauge
2.6A 12v
66 ft. max
49 ft. max 159 ft. max 295 ft. max
31 ft. max 100 ft. max 186 ft. max
19 ft. max
13 ft. max
8 ft. max
1.6A 24v
215 ft. max
63 ft. max
39 ft. max
25 ft. max
0.86A 24v
400 ft. max
117 ft. max
73 ft. max
46 ft. max
All analog input signal cables must be shielded!
Good analog system design requires that all analog signals in an electrically noisy environment be shielded. Long wires act like antennas that pick up analog noise. The wire connecting the analog command source to command this module must be shielded!
Shielding a noise sensitive wire is accomplished by wrapping a noise blocking foil or braided shield around the signal wire. This shield must be grounded at only one end, usually the end that sends the signal. A control cable may have many individual conductors. The conductors may be shielded individually, or may be shielded as a group. Short signal wires in electrically quiet environments may not need to be shielded.
The CEM family of modules all have an internal ground connection to the DIN rail. For this module ground to be effective, please insure the DIN rail is properly grounded.
Page 5 of 24 CEM-PA-B CHI 1020688 01/2016
Circuit Diagram
Continental Hydraulics Installation Manual
Page 6 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
LED Definitions
LEDs Description of the LED function
Identical to the READY output.
OFF: No power supply or ENABLE is not activated
ON: System is ready for peration
GREEN
YELLOW A
Flashing: Error discovered
Only active when SENS = ON
Intensity of the solenoid current
1.
Chasing light (over all LEDs): The bootloader is active. No normal functions are possible.
GREEN + YELLOW A
YELLOW A +
YELLOW B
2.
All LEDs flash shortly every 6 s: An internal data error was detected and corrected automatically! The module still works regularly. To acknowledge the error the module has to be cycle powered.
Both yellow LEDs flash oppositely every 1 s: The nonvolatile stored parameters are inconsistent! To acknowledge the error, data has to be saved with the SAVE command or the corresponding button in the
CHI-PC.
Terminal Identification - Input and output signals
Connection
PIN 7
PIN 8
Connection
PIN 9 / 10
PIN 13 /14
PIN 11
PIN 12
PIN 3 / 4
Connection
PIN 15
PIN 6
PIN 5
Supply
Power supply (see technical data)
0 V (GND) connection.
Analogue signals
Pressure command value (WA), signal range 0… 10 V or 4… 20 mA, scalable (SIGNAL W)
Pressure feedback value (X), signal range 0… 10 V or 4… 20 mA, scalable (SIGNAL X)
0 V (GND) connection for analogue signals
8V reference voltage output
PWM output to the solenoid
Digital inputs and outputs
Enable input:
Generally enabling of the application.
RUN (Start) Input :
ON: The controller is active.
OFF: The controller is not active.
READY output:
ON: The module is enabled; there are no discernable errors.
OFF: ENABLE (PIN 15) is not active or an error has been detected.
Page 7 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
Ref Page Command
9
9
LG
MODE
9 SENS
10 EOUT
10 SYS_RANGE
10 SIGNAL:X
13 N_RANGE:X
13 OFFSET:X
10 SIGNAL:W
14 RA:UP
14 RA:DOWN
15 C:P
15 C:I
15 C:D
15 C:D_T1
15 C:FF
16 C:I_LIM
16 C:I_ACT
17 MIN
17 MAX
17 TRIGGER
18 SIGNAL:U
18 CURRENT
18 DFREQ
18 DAMPL
19 PWM
19 ACC
20 PPWM
20 IPWM
CEM-PA-B Function Parameter layout
Parameter Help / Description
EN EN English
EXP Standard / Expert mode
AUTO Malfunction monitoring [ON / OFF /AUTO]
0 Output signal if not ready [0.01%]
100 System pressure [bar]
U0-10 Type of Input
100 Sensor nominal pressure [bar]
0 Sensor offset [mbar]
U0-10 Type of Input
100 Command signal ramp time [ms]
100 Command signal ramp time [ms]
50 P gain [x 0.01]
4000 I gain [0.01ms]
0 D gain [0.1ms]
500 D gain filter [0.1ms]
8000 Feed forward [0.01%]
2500 Integrator limitation [0.01%]
2500 Integrator activation threshold [0.01%]
0 Deadband compensation [0.01%]
10000 Output Scaling [0.01%]
200 Trigger point of the MIN function in 0.01%
+ Output polarity
1000 Rated solenoid current [mA]
121 Dither frequency [Hz]
500 Dither amplitude [0.01%]
2604 PWM frequency [Hz]
ON Auto Adjustment of the current loop [OFF / ON]
7 P-Gain of the current loop
40 I-Gain of the current loop
STD
MODE
EXP
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X x
X
X
X
X x
X
X
X
X
X
X
X
X
X
X
X
X
Page 8 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
Command Parameter Descriptions
LG (Changing the language)
Command
LG x
Parameters x= DE|EN
Unit
-
Group
STD
Either English or German can be selected for the help texts.
After changing the language settings, the ID button in the menu bar (CHI-PC) must be pressed (module identification).
MODE (Parameter view)
Command
MODE x
Parameters x= STD|EXP
Unit
-
Group
STD
This command changes the operating mode. Various commands (defined via STD/EXP) are blanked out in Standard Mode. The commands in Expert Mode have a more significant influence on system behavior and should accordingly be changed with care.
SENS (Malfunction monitor)
Command Parameters Unit Group
SENS x x= ON|OFF|AUTO - STD
This command is used to activate/deactivate the monitoring functions (4… 20 mA sensors, output current, signal range and internal failures) of the module.
ON: All monitoring functions are active. Detected failures can be reset by deactivating the ENABLE input.
OFF: No monitoring function is active.
AUTO: Auto reset mode. All monitoring functions are active. If the failure doesn’t exist anymore, the module automatically resumes to work.
Normally the monitoring functions are always active because otherwise no errors are detectable via the READY output. Deactivating is possible mainly for troubleshooting.
Page 9 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
EOUT (Output signal if not ready)
Command
EOUT X
Parameters Unit x= -10000… 10000 0.01 %
Group
EXP
Output value in case of a detected error or a deactive ENABLE input. A value (degree of valve opening) for use in the event of a sensor error (or the module is disabled) can be defined here. This function can be used if, for example, the drive is to move to one of the two end positions (at the specified speed) in case of a sensor error.
|EOUT| = 0 The output is switched off in the event of an error. This is normal behavior.
The output value defined here is stored permanently (independently of the parameter set). The effects should be analyzed by the user for each application from the point of view of safety.
SYS_RANGE (System pressure)
Command Parameters
SYS_RANGE X x= 10… 1000
Unit bar
Group
STD
This command defines the maximum pressure of the selected valve at rated current applied, which corresponds to 100 % of the input signal. If the demand is set incorrectly, this leads to incorrect system settings, and the dependent parameters cannot be calculated correctly.
SIGNAL (Type of input signal)
Command Parameters Unit Group
SIGNAL:I X i= W|X x= OFF|U0-10|I4-20
- EASY
This command can be used to change the type of input signal (voltages or current) and to define the direction of the signal. This command is available for all analogue inputs (W and X).
OFF= Deactivation of the input
See ANIMODE section if the signals used are not listed above, for re-scaling as required.
Page 10 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
AINMODE
The AINMODE is used to define the type of analog input signals being used.
The standard default setting of AINMODE is EASY. In the EASY mode the SIGNAL:W/X/V (see page 13) are only available in the most commom 0-10 volt or 4-20mA values.
If the input signal being used are not as listed, the AINMODE is available in the MATH mode where the input signals can be scaled by a linear equation.
To enter the MATH option, you must change the AINMODE to MATH by use of the Terminal
Window. (see steps 1-4 below)
Once in the Termainal Window screen type in AINMODE MATH (ENTER), and click the Save button. At this time you may go back to the Parameter screen where you can use the user defined scalling feature.
Once in the MATH mode you will be able to scale the various input signals as shown below.
Page 11 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
AINMODE - Analogue input scaling parameters
Command Parameters
AIN:I a b c x i = A|B a= -10000… 10000 b= -10000… 10000 c= -10000… 10000 x = V|C
Unit
-
-
-
0.01%
-
Group
EXP
FUNCTION
AA
A-B
This command offers an individual scalable input. The following linear equation is used for the scaling.
Output = A/B ∙ (Input – C)
The
“C” value is the offset (e.g. to compensate the 4 mA in case of a 4… 20 mA input signal).
The variables A and B are defining the gain factor with which the signal range is scaled up to
100 % (e.g. 1.25 if using 4… 20mA input signal, defined in default current settings by A = 1250 and B = 1000). The internal shunt for the current input signal is activated when parameters AIN:A and AIN:B are set to Current (X=C).
The gain factor is calculated by dividing total input signal range ( A ) by the actual input range ( B ).
In the case of a 4-20mA with a single solenoid valve, the total range is 0-20mA, which means
A=20 . The actual range is 4-20 mA, therefore, B= (20-4) =16 . An offset, C , must be added to compensate for the 0-4mA not being used of the full range. The offset is 4mA/20mA=0.2 or 20%.
Therefore C=2000 since the unit value for C is 0.01%.
Shown in the below table are the most common input command signal and the corresponding settings to be used.
Typical settings (examples):
Command
AIN:X 1000 1000 0 V
AIN:X 10 8 1000 V OR
AIN:X 1000 800 1000 V
AIN:X 10 4 500 V OR
AIN:X 1000 400 500 V
AIN:X 20 16 2000 C OR
AIN:X 2000 1600 2000 C OR
AIN:X 1250 1000 2000 C
Input Description
0… 10 V Range: 0… 100 %
1… 9 V Range: 0… 100 %; 1 V = 1000 used for the offset and gained by 10 / 8 (10 V divided by 8 V (9 V -1 V))
0.5… 4.5 V Range: 0… 100 %; 0.5 V = 500 used for the offset and gained by 10 / 4 (10 V divided by 4 V (4.5 V -0.5 V))
4… 20mA Range: 0… 100 %
The offset will be compensated on 20 % (4 mA) and the signal (16 mA = 20 mA – 4 mA) will be gained to 100 %
(20 mA).
Each of this parameterization for 4… 20 mA is setting the range to 0… 100 %.
Page 12 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
N_RANGE:X (Sensor nominal pressure)
Command Parameter Unit Group
N_RANGE:X X x= 10… 10000 bar
EASY
N_RANGE (nominal range) is used to define the pressure range of the sensor. This value should be always same as or higher than SYS_RANGE. The control parameter cannot be calculated correctly in case of wrong values.
OFFSET:X (Sensor offset)
Command Parameter Unit Group
OFFSET:X X x= -60000… 60000 mbar EASY
Adjustment of the zero point of the sensor. If the command signal and feedback signals are not zeroed to each other this offset should be used.
Using of the commands SYS_RANGE, N_RANGE:X and OFFSET:X
Example of use:
With these commands, the feedback sensor is scaled. Suppose you have a pressure control with the following characteristics:
The system pressure is 350 bar
The pressure sensor has a 4-20mA current output
The nominal pressure of the sensor is 600bar (20mA at 600bar)
The sensor has an offset of 3bar (at 0bar real pressure 3bar is displayed)
To scale this sensor correctly the following settings should be made:
SYS_RANGE 350 bar
SIGNAL:X I4-20
N_RANGE:X 600 bar
OFFSET:X -3000 mbar
Page 13 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
RA (Command signal ramp time)
Command Parameter
RA:I X i= UP|DOWN x= 1… 600000
Unit ms
Two quadrant ramp function.
The ramp time is separately set for UP and DOWN ramps.
Group
STD
Page 14 of 24
A:UP A:DOWN t
CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
C:P, C:I, C:D C:D_TI, C:FF Control parameters (PID controller)
Command Parameter Unit Group
C:I X STD I= P|I|D|D_T1|FF
:P x= 0… 10000
:I x= 0… 30000
0.01
0.1 ms
:D x= 0… 1200
:D_T1 x= 0… 1000
:FF x= 0… 10000
0.1 ms
0.1 ms
0.01 %
The control function will be parameterized via this command.
The C:P, I and D gain are similar to a standard PID controller.
The T1 factor is used for the D-gain in order to suppress high-frequency noise.
The FF value is a forward control value to control the output by the input signal directly.
The PID closed loop control function has only to adjust the difference (the error).
Value 0 deactivates the integrator.
Page 15 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
C:I_LIM, C:I_ACT Integrator control function
Command Parameter Unit Group
C:I_LIM X
C:I_ACT X x= 0… 10000 x= 0… 10000
0.01 %
0.01 %
STD
The integrator function is controlled by this command.
C:I_LIM Limitation of the integrator range (faster control function by reduced pressure overshoots). By a high nonlinearity of the valve the LIM value must be sufficient to compensate it.
C:I_ACT Controls the integrator function. To reduce pressure overshoots, an activation point for the integrator can be programmed via the (I_ACT) value. The integrator is activated if the actual pressure is higher than the programmed threshold:
Page 16 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
MIN (Deadband compensation)
MAX (Output scaling)
TRIGGER (Response threshold for the MIN parameter)
Command Parameters
MIN:I
MAX:I
X
X x= 0… 6000 x= 3000… 10000
Unit
0.01 %
0.01 %
Group
STD
TRIGGER X x= 0… 3000 0,01 %
With this command, the output signal is adjusted to the valve characteristics. With the
MAX value the output signal (the maximum valve current) will be defined. With the MIN value the overlap (dead band of the valve) will be compensated. Via the TRIGGER the activation point of the MIN function is set and so a non-sensitive range around the zeropoint 1 can be specified.
If the MIN value is set too high, it influences the minimal pressure, which cannot be adjusted any longer. In extreme case this causes to an oscillating at small input values.
10V
MAX
MIN
Eingang / Input
100%
TRIGGER
1 This dead band is necessary, in order to avoid unrequested activations caused by small variations of the input signal. If this module is used in pressure controls, the TRIGGER value should be reduced (typical:
1…10).
Page 17 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
SIGNAL:U (Output polarity)
Command Parameter Unit Group
SIGNAL:U X x= + | - -
+
-
This command is used to define the output polarity.
0 % to 100 %, normal output
100 % to 0 %, changed output polarity
EXP
CURRENT (Rated solenoid current)
Command Parameters Unit Group
CURRENT X x= 500… 2600 mA
STD
The nominal output current is set. Dither and also MIN/MAX always refer to this current range.
DFREQ (Dither frequency) / DAMPL (Dither amplitude)
Command Parameters Unit
DFREQ X x= 60… 400 Hz
Group
STD
DAMPL X x= 0… 3000 0.01 %
The dither 2 can be defined with this commands. Different amplitudes or frequencies may be required depending on the valve.
The dither amplitude is defined in % (peak to peak value) of the nominal output current 3
(see: CURRENT command).
The dither frequency is defined in Hz. Depending on the internal calculations, the frequency is adjustable in steps only 4 .
The PPWM and IPWM parameters influence the effect of the dither setting. These parameters should not be altered again after the dither has been optimized.
2 The dither is a ripple signal which is superimposed on the current set point and is defined by the amplitude and frequency: the dither frequency and the PWM frequency.
The dither frequency should not be confused with the PWM frequency . In some documentations the PWM frequency is described as a dither. This can be recognized by the lack of the dither amplitude.
3 The dither amplitude is a command signal. Derivations between the commanded amplitude and the real amplitude are possible, depending on the dynamic of the solenoid.
4 The lower the dither frequency, the smaller the steps. Therefore no practical problems are expected.
Page 18 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
PWM (PWM Frequency)
Command Parameter
PWM X x= 61… 2604
Unit
Hz
Group
EXP
The frequency can be changed in defined steps (61 Hz, 72 Hz, 85 Hz, 100 Hz, 120 Hz,
150 Hz, 200 Hz, 269 Hz, 372 Hz, 488 Hz, 624 Hz, 781 Hz, 976 Hz, 1201 Hz, 1420 Hz,
1562 Hz, 1736 Hz, 1953 Hz, 2232 Hz and 2604 Hz). The optimum frequency depends on the valve.
If the PWM frequency is less than 500 Hz, the dither amplitude DAMPL should be set to zero.
The PPWM and IPWM parameters should be adapted when using low PWM frequencies because of the longer dead times which forces a reduced stability of the closed loop control.
ACC (Current loop auto adjustment)
Command Parameter Unit Group
ACC X x= ON|OFF -
EXP
Operation mode of the closed loop current control.
ON : In automatic mode PPWM and IPWM are calculated depending on the pre-set
PWM-frequency.
OFF : Manual adjustment.
Page 19 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
PPWM (P gain of the current loop)
IPWM (I gain of the current loop)
Command Parameters
PPWM
IPWM
X
X x= 0… 30 x= 1… 100
Unit
-
-
Group
EXP
The PI current controller for the solenoids is parameterized with these commands.
These parameters should not be changed without adequate measurement facilities and experience.
Attention, if the parameter ACC is set to ON, these adjustments are done automatically.
If the PWM frequency is < 250 Hz, the dynamic of the current controller has to be decreased.
Typical values are: PPWM = 1… 3 and IPWM = 40… 80.
If the PWM frequency is > 1000 Hz, the default values of PPWM = 7 and IPWM = 40 should be chosen.
PROCESS DATA (Monitoring)
Command
WA
Description
Input signal
W
Command value
X
Feedback value
E
Control error
U
Output
IA
Solenoid current
5
Unit mm mm mm mm
% mA
The process data are the variables which can be observed continuously on the monitor or on the oscilloscope.
5 The display of the solenoid current (in CHI-PC program) is damped in order to be able to bring out a stable signal.
Page 20 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
Failure monitoring
Following possible error sources are monitored continuously when SENS =
ON/AUTO:
Source Fault Characteristic
Command signal PIN
9/10
4... 20 mA
Feedback signal PIN 14
4… 20 mA
Out of range or broken wire
Out of range or broken wire
The output will be switched off.
The output will be switched off.
Solenoids on PIN 3-4
EEPROM
(when switching on)
Wrong cabling, broken wire
The power stage will be deactivated.
Data error The output is deactivated.
The module can only be activated by saving the parameters again!
CAUTION: Take care of the EOUT command. Changes will influence the behavior.
Page 21 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
Troubleshooting
It is assumed that the device is in an operable state and there is communication between the module and the CHI-PC. Furthermore, the valve control parameterization has been set with the assistance of the valve data sheets.
FAULT CAUSE / SOLUTION
There is presumably no power supply or no ENABLE signal (PIN 15) present.
Other faults are signalized with a flashing READY LED.
ENABLE is active, the module does not respond, and the READY LED is off.
ENABLE is active, the
READY LED is flashing.
ENABLE is active; the
READY LED is active; no current to the solenoid (no pressure-build-up).
The flashing READY LED signals that a fault is detected by the module. The fault could be:
A cable breakdown or no signal at the inputs (PIN 9 or PIN 14) if 4… 20 mA signals are parameterized.
A cable breakdown or incorrect cabling to the solenoids (in the P version only).
Internal data error: press the SAVE button to delete the data error. The system reloads the DEFAULT data.
With the CHI-PC operating program the fault can be localized directly via the monitor.
To locate errors in the pressure-control-circuit, it is useful to start with the open loop pressure control (PIN 6 is not activated). In this case the module works like a power amplifier.
No pressure command input is available or the parameterization is incorrect. With the CHI-PC tool you can check if a command input is available. If not, you should check the wiring and/or the command setpoint (in the PLC for example).
If the command input is correct, you have to check the valve control parameter. If the current is set too low (parameter CURRENT), the output current and the expected pressure are too low.
Wrong configured pressure sensor (if PIN 6 is active). If the input-scaling is set to voltage (V) and the pressure sensor supplies a current signal (4...
20mA), the measured pressure value is always high. The output signal to the valve is therefore low. For further checking: disable PIN 6.
The pressure valve is controlled correctly (the output is going up to the nominal current). In this case you may have a hydraulic problem or you are using free-wheeling-diodes in the solenoid plug. Please remove the free-wheeling-diodes to allow a correct current measurement.
Page 22 of 24 CEM-PA-B CHI 1020688 01/2016
FAULT
ENABLE is active, the
READY LED is active and the pressure is instable.
Continental Hydraulics Installation Manual
CAUSE / SOLUTION
In many cases you may have a hydraulic problem.
Electrical problems may be:
Electrical noise at the wire of the power supply.
Very long solenoid wiring (> 40 m), disturbance in the current control loop 6 .
Unstable current control loop. The adjustments of the PWM-frequency and the dither (frequency and amplitude) have to be checked carefully. Good experiences are made with: a. PWM-frequency = 2600 Hz (higher frequency), the dither has to be aligned to the valve (amplitude and frequency). b. PWMfrequency = 100… 400 Hz (lower frequency), the dither amplitude is set to 0 % (disabled) 7 .
The system works generally, but wrong control loop settings or wrong adjustment of the input signals cause control errors.
ENABLE and START
(PIN 6) are active,
READY LED is ON, the pressure control works, but the pressure is not equal to the command input.
1. The feedback pressure is proportional to the command input pressure, but the values are too high or too low.
The scaling of the pressure valve is affected by the adjustment of the output current and the parameter MAX .
The valve has a nominal range of 320 bar and the working pressure range is 240 bar, the parameter MAX has to be decreased. Procedure: Deactivate PIN 6, set the command input to 100 % and adjust the correct pressure by reducing the MAX parameter.
6 Maybe you have to adjust / optimize the solenoid control loop (P and I).
7 In most applications (particularly pressure-actuated pumps) with pressure valves a lower PWM-frequency is the better solution.
Page 23 of 24 CEM-PA-B CHI 1020688 01/2016
FAULT
Continental Hydraulics Installation Manual
CAUSE / SOLUTION
ENABLE and START
(PIN 6) are active, the
READY LED is active, the pressure control loop works, but the pressure is oscillating or the pressure UP and
DOWN time is too slow.
ENABLE and START
(PIN6) are active, the
READY LED is active, and the pressure control loop works, but there are high errors mainly at lower or higher command pressure.
The capability of the hydraulic system has to be checked. Deactivate PIN 6 for open loop control and check the pressure build up and down time. If the system is in open loop still unstable, check the hydraulic and the dither/ PWM setup first.
1. Check the parameters C:I, C:P and C:SC.The parameter C:SC has the following relevance:
With this parameter you can increase or decrease the feed forward gain to the valve. C:SC 8000 (80 %) means, the remaining 20 % must be provided by the PID compensator. The integrator limitation should be set to 2500...
3500 (25 % ... 35 %)
8
.
2. The C:P (P-gain) is to increase in steps
9
to the point where the pressure is going to be u nstable. At this point, C:P should be decreased for 30… 50 % to get an effectual stability margin.
3. The integrator time constant C:I fixes the static error. Typical values are:
100 ms to 1200 ms. Optimize this parameter by monitoring the transient response.
The non-linearity of the valve is higher than the controlling range of the integrator. The parameter LIM:I should be increased.
In this case, the integrator threshold (activation point of the integrator) in combination with the controller setting is too high. The parameter LIM: S should be reduced.
ENABLE and START
(PIN 6) are active, the
READY LED is active, and the pressure control loop works. Lower pressure at the beginning causes that the system is not actuated and that no pressure build-up occurs.
8 The limit value should be higher than the remaining control range (100 % - C:SC), additionally you have to add a value to compensate the non-linearity of the valve.
9 Optimizing in steps is a general description. Our experience: you can change the parameters in steps from
+20 % or rather -20 % for a rough adjustment of the actual value. For a fine adjustment you can select smaller steps.
Page 24 of 24 CEM-PA-B CHI 1020688 01/2016