Future Design L91 User`s Manuals - Environmental Test Chambers

Add to my manuals
52 Pages

advertisement

Future Design L91 User`s Manuals - Environmental Test Chambers | Manualzz

LIMIT

OP1 OP2 C

FDC-L91

F

PV HSP1 LSP1 SP2 LOCK

RESET

This Symbol calls attention to an operating procedure, practice, or the like, which, if not correctly performed or adhered to, could result in personal injury or damage to or destruction of part or all of the product and system. Do NOT proceed beyond a warning symbol until the indicated conditions are fully understood and met.

Installers

System Designer

Expert User

Read Chapter 1, 2

Read All Chapters

Read Page 12

NOTE:

Information in this user's manual is subject to change.

without notice.

This manual is applicable for L91 units with software version

1.9 and later.

Copyright a March 2006, Future Design Controls, all rights reserved. No part of this publication may be reproduced, transmitted, transcribed or stored in a retrieval system, or translated into any language in any form by any means without the written permission of Future Design Controls.

2

UM L91-Rev 8

Contents

1-1 General

1-2 Ordering Code

1-3 Programming Port

1-4 Keys and Display

Page No

5

6

7

7

1-5 Menu Overview

1-6 Limit Control Operation

12

13

1-7 Parameter Descriptions

16

Page No

3-4 PV Shift

3-5 Digital Filter

35

35

3-6 Process Alarms 36

3-7 RS-485 Communication

37

3-8 Display Mode

38

3-9 Signal Conditioner DC

Power Supply

3-10 Remote Reset

38

40

3-11 Remote Lock

3-12 Limit Annunciator

40

41

2-1 Unpacking

2-2 Mounting

2-3 Wiring Precautions

2-4 Power Wiring

2-5 Sensor Installation

Guidelines

25

2-6 Thermocouple Input

Wiring

26

2-7 RTD Input Wiring

2-8 Linear DC Input Wiring

27

28

2-9 Event Input Wiring

2-10 Output 1 Wiring

2-11 Output 2 Wiring

29

30

31

2-12 RS 485

32

2-13 Ma Retransmission

32

22

22

23

25

42

43

47

3-1 Process Input

3-2 Limit Control

3-3 Setpoint Range

33

34

34

UM L91-Rev 8

3

Page No

Figure 1-1 Programming Port Location

7

Figure 1-2 Front Panel Display

8

Figure 1-3 Power Up Sequence

10

Figure 1-4 High Limit Operation

13

Figure 1-5 Low Limit Operation

14

Figure 1-6 High/Low Limit Operation

15

Figure 2-1 Mounting Diagram

23

Figure 2-2 Lead Termination

24

Figure 2-3 Rear Terminal Connection Diagram

24

Figure 2-4 Power Supply Connections

25

Figure 2-5 Thermocouple Input Wiring

27

Figure 2-6 RTD Input Wiring

27

Figure 2-7 Linear Voltage Input Wiring

28

Figure 2-8 Linear Current Input Wiring

28

Figure 2-9 Event Input Wiring

29

Figure 2-10 Output 1 Wiring

30

Figure 2-11 Output 2 Wiring

31

Figure 2-12 RS-485 Wiring

32

Figure 3-1 Conversion of Linear Process Input --------------

33

Figure 3-2 Filter Characteristics

35

Figure 3-3 Normal Process Alarm

37

Figure 3-4 Latching Process Alarm

37

Figure 3-5 DC Power Supply Application

Figure 5-2 Cold Junction Calibration Setup

Figure 5-3 RTD Calibration

39

Figure 3-6 Remote Reset Application

40

Figure 3-7 Remote Lock Application

40

Figure 4-1 Over Temperature Protection w/ Remote Reset

42

Figure 5-1 Flow chart for Manual Calibration

44

45

46

Table 1-1 Display Form of Characters

Table 6-1 Input Characteristics

9

48

UM L91-Rev 8

4

The limit control is a microprocessor based high or low limit safety device with a latching output. The relay contacts open if an abnormal condition during the process is higher than the high limit set point or lower than the low limit set point.

Digital communication RS-485 is available as an additional option. This option allows L91 to be integrated with supervisory control system. An alarm output is another option. A variety of alarm function and alarm modes can be programmed for a specific application. The DC power supply output option is used for an external sensor or transmitter. The event input option can be programmed for remote reset or remote lock signal input.

The limit annunciator option can be used to energize an external audible alarm when limit is reached.

Ma retransmission option of Process variable or setpoint is also available.

and simple are the main features of L91.

NOTE: * Volt and Milliamp Inputs are NOT FM Approved.

5

UM L91-Rev 8

L91

1 2

3 4

4: 90 - 264 VAC, 50/60 HZ

5: 11 - 26 VAC or VDC

9: Special Order

1: Standard Input

Thermocouple: J, K, T, E, B,

R, S, N, L

RTD: PT100 DIN, PT100 JIS mV: 0~60 mV

2: Voltage: 0-1 V *

3: Voltage : 0-10 V *

4: Current: 0-20mA/4-20mA *

9: Special Order *

Example

Standard Model:

L91-4110

90-264 VAC Operation

Input: Standard Input

Output 1: Relay

Option: None

1: Form C relay rated

2A/240VAC

2: Pulsed voltage to drive SSR, 5V/30mA

6: Triac Output

1A / 240VAC,SSR

9: Special order

Option

0: None

1: Form A Relay 2A/240VAC

2: SSR Drive 5VDC @ 30 ma

6: Triac Output, 1A / 240VAC, SSR

7: Isolated 20V / 25mA DC Supply

8: Isolated 12V / 40 mA DC Supply

9: Isolated 5V / 80mA DC Supply

A: RS-485

B: Event input

C: SSR Drive 14VDC @ 40 ma

D: Retransmit 4/20, 0/20 Ma

E: Retransmit 1/5, 0/5 VDC

F: Retransmit 0/10 VDC

H: Special order

Accessories

OM94-6 = Isolated 1A / 240VAC Triac Output Module ( SSR )

OM94-7 = 14VDC/40 ma SSR Drive module

DC 94-1 = Isolated 20V / 25mA DC Output Power Supply

DC 94-2 = Isolated 12V / 40mA DC Output Power Supply

DC 94-3 = Isolated 5V / 80mA DC Output Power Supply

CM 96-1 = Isolated RS-485 Interface Module

CM 96-3 = Isolated 4/20, 0/20 MA Retransmission Output Module

CM 96-4 = Isolated 1/5, 0/5 VDC Retransmission Output Module

CM 96-5 = Isolated 0/10 VDC Retransmission Output Module

EI96-1 = Event Input Module

NOTE: * Volt and Milliamp Inputs are NOT FM Approved.

UM L91-Rev 8

6

P11A = Hand-held Programmer for L91,C91 Series Controller

SNA10A = Smart Network Adaptor for Third Party Software,

Converts 255 channels of RS-485 or RS-422 to

RS-232 Network

SNA10B = Smart Network Adaptor for FD-Net Software, Converts

255 channels of RS-485 or RS-422 to RS-232 Network

Programming Port control board

Power board

Open the housing

Top view of L91

calibration procedures only. Do not attempt to make any connection to these jumpers when the unit is on-line. Por t is for bench setup only.

SCROLL KEY

This key is used to:

1. Select a setpoint to be displayed.

2. Select a parameter to be viewed or adjusted.

3. Advance display from a parameter code to the next parameter code

7

UM L91-Rev 8

ENTER KEY 4 seconds, 8 seconds

Press the scroll key for 4 seconds the display will enter the setup menu. Press this key for 8 seconds to enter the calibration mode.

UP KEY

This key is used to increase the selected parameter value during the lock indicator is off.

DOWN KEY

This key is used to decrease the selected parameter value during the lock indicator is off.

RESET KEY

RESET

This key is used to:

1.Reset the limit condition after the process is within the limit.

2.Revert the display to the normal display.

3.Reset the latching alarm.

4.Reset the limit annunciator.

If the RESET key is left pressed, only ONE reset operation will occur. If the unit subsequently goes into a state where reset is required again, the RESET key (or remote reset contacts) must be released (opened) and pressed (closed) again.

UNLOCK KEY

RESET

4 seconds

Press the RESET key for 4 seconds to enable up/down key function, and the lock indicator led will be extinguished.

However, this function is disabled when remote lock is selected for

EIFN (Event input function).

See section 3-16 .

LIMIT

OP1 OP2 C

FDC-L91

F

PV HSP1 LSP1 SP2 LOCK

RESET

Op1: Output 1 status indicator

OP2: Output 2 status indicator

C: Degree C indicator

F: Degree F indicator

PV: Process value

HSP1: High limit set point 1

LSP1: Low limit set point 1

SP2: Set point 2 for output 2

LOCK: Lock status indicator

UM L91-Rev 8

8

A

B

C

E

F

G

I

J

K

L

N

O

P

Q

S

T

U c

D

H h

M

R

V

W

: These characters are displayed differently.

X

Y

Z

?

=

For a number with decimal point the display will be shifted one digit right:

-199.99 will be displayed as -199.9, 4553.6 will be displayed as 4553

For a number without decimal point the display will be divided into two alternating phases:

-19999 will be displayed as:

45536 will be displayed as:

-9999 will be displayed as:

During normal operation, the unit can be configured to display the process value, high limit or low limit set point ( HSP1 or LSP1 dependent on OUT1 selection ) or the word SAFE.

Whenever the process is outside the normal range, the process value will be displayed.

UM L91-Rev 8

9

If a break is detected in the sensor circuit, the display will show:

If failure is detected in the A-D converter circuit, the display will show:

10

LIMIT FDC-L91

RESET

All segments of display and indicators are left off for 0.5 second.

LIMIT

OP1 OP2 L C

FDC-L91

L F

PV HSP1 LSP1 SP2 LOCK

RESET

All segments of display and indicators are lit for 1 second.

LIMIT

OP1 OP2 L C

FDC-L91

L F

PV HSP1 LSP1 SP2 LOCK

RESET

Display program code of the product for

1 second. The left diagram shows program no.1 with version 21.

LIMIT

OP1 OP2 L C

FDC-L91

L F

PV HSP1 LSP1 SP2 LOCK

RESET

Display Date Code for 1 second. The left diagram shows Year 2001, Month

February (2), Date 25'th. This means that the product is produced on February

25'th, 2001. Note that the month code is for is for and C is

UM L91-Rev 8

LIMIT

OP1 OP2 L C

FDC-L91

L F

PV HSP1 LSP1 SP2 LOCK

RESET

Display the serial number ( 001~999 ) for 1 second.

LIMIT

OP1 OP2 L C

FDC-L91

L F

PV HSP1 LSP1 SP2 LOCK

RESET

LIMIT

OP1 OP2 L C

FDC-L91

L F

PV HSP1 LSP1 SP2 LOCK

RESET

Display the hours used for 2 seconds. The left diagram shows that the unit has been used for 23456.7 hours since production.

UM L91-Rev 8

11

12

Process value

High limit setpoint 1 value

Low limit setpoint 1 value

Set point 2 value

Press for 4 sec.

INPT

UNIT

HSP.H

LSP.L

LSP.H

OUT2

ADDR

BAUD

PARI

AOFN

RESO

IN.LO

IN.HI

SHIF

FILT

OUT1

O1.HY

HSP.L

Input type

Process unit

Display resolution

Low scale value for linear input

High scale value for linear input

PV shift (offset) value

PV filter time constant

Output 1 function

Output 1 hysteresis value

Lower limit of HSP1

Upper limit of HSP1

Lower limit of LSP1

Upper limit of LSP1

Output 2 function

Address for digital communication

Baud rate

Parity bit

Analog output function

Analog output low scale

Analog output high scale

AOLO

AOHI

AL.FN

AL.MD

AL.HY

AL.FT

EIFN

DISP

Alarm function

Alarm mode

Alarm hysteresis value

Alarm failure transfer

Event input function

Normal display format

PV.HI

PV.LO

Max. historical PV

Min. historical PV

T.ABN

Abnormal time

UM L91-Rev 8

Note 1.

The flow charts show a complete listing of parameters. For the actual application the number of available parameters is dependent on the setup conditions, and should be less than that shown in the flow charts.

Note

2.

Press

RESET key for 4 seconds to enable up/down key function, and the LOCK indicator led will be extinguished.

If Hi. is selected for OUT1, the unit will perform high limit control. When power is applied the OUT1 relay is de-energized. After 6.5 seconds self-test period, if the process is below the high limit set point (HSP1), the output 1 relay will be energized and OP1 indicator will go off. If the process goes above the high limit set point, the relay will be de-energized, the OP1 indicator will go on and the display will show the process value. After the process falls below the high limit set point and the RESET key is pressed or the remote reset input is applied, the relay will be energized and the OP1 indicator will go off.

NOTE: Hysteresis is safe-sided.

PV

HSP1

HSP1 O1.HY

OUT1 Relay

ON

OFF

A B C

A, B ,C=Reset is applied

O1.HY= Output1 hysteresis

13

UM L91-Rev 8

If Lo. is selected for OUT1, the unit will perform low limit control. When power is applied the OUT1 relay is de-energized. After 6.5 seconds self-test period, if the process is above the low limit set point (LSP1), the output 1 relay will be energized and OP1 indicator will go off. If the process goes below the low limit set point, the relay will be de-energized, the OP1 indicator will go on and the display will show the process value. After the process rises above the low limit set point and the RESET key is pressed or the remote reset input is applied, the relay will be energized and the OP1 indicator will go off.

NOTE: Hysteresis is safe-sided.

LSP1+O1.HY

LSP1

OUT1 Relay

ON

OFF

A B C

A, B ,C=Reset is applied

O1.HY= Output1 hysteresis

14

UM L91-Rev 8

If Hi.Lo is selected for OUT1, the unit will perform high/low limit control. When power is applied the OUT1 relay is de-energized. After 6.5 seconds self-test period, if the process is below the high limit set point (HSP1) and above the low limit set point (LSP1), the output 1 relay will be energized and OP1 indicator will go off. If the process goes above the high limit set point or below the low limit set point, the relay will be de-energized, the OP1 indicator will go on and the display will show the process value. After the process is within the normal operation range, and the RESET key is pressed or the remote reset input is applied, the relay will be energized and the

OP1 indicator will go off. NOTE: Hysteresis is safe-sided.

A B C D E F

HSP1

HSP1 O1.HY

LSP1+O1.HY

LSP1

OUT1 Relay

ON

OFF

A, B, C, D, E, F =Reset is applied

O1.HY= Output1 hysteresis

15

UM L91-Rev 8

Parameter

Notation

HSP1

LSP1

SP2

Parameter

Description

Range

High Limit Set point 1

Low Limit Set point 1

Low: HSP.L

High: HSP.H

Low: LSP.L

High: LSP.H

Set point 2 Value for

Output 2

See Table 6-1

INPT

Input Type Selection

0

1

2

3

4

5

6

7

8

9

10

: J type thermocouple

: K type thermocouple

: T type thermocouple

: E type thermocouple

: B type thermocouple

: R type thermocouple

: S type thermocouple

: N type thermocouple

: L type thermocouple

: PT100 ohms DIN curve

: PT100 ohms JIS curve

Default

Value

100.0 C

(212.0 F)

0 C

(32.0 F)

90.0 C

(194.0 F)

1

( 0 )

16

UM L91-Rev 8

Parameter

Notation

Parameter

Description

Range

INPT

Input Type Selection

11 : 4~20 mA linear current

*

12 : 0~20 mA linear current*

13 : 0~60 mV linear voltage

14 : 0~1 V linear voltage

*

15

16

17

: 0~5 V linear voltage

*

: 1~5 V linear voltage

*

: 0~10V linear voltage *

UNIT Process Unit

0

1

:

Degree C unit

:

Degree F unit

2

0

:

Process unit

:

No decimal point

1 :

1 decimal point

RESO Display Resolution

2 :

2 decimal point

IN.LO

Low Scale Value for

Linear Input

3 :

3 decimal point

Low: -19999

High: IN.HI

NOTE: Inputs 11, 12, 14, 15, 16, and 17 are NOT FM Approved.

Default

Value

1

( 0 )

0

( 1 )

1

0

17

UM L91-Rev 8

Parameter

Notation

IN.HI

Parameter

Description

High Scale Value for

Linear Input

SHIF

FILT

OUT1

PV Shift ( offset )

Value

PV Filter Time

Constant

Output 1 Function

Range

Default

Value

Low: IN.LO

High: 45536

Low: -200.0 C

(-360.0 F)

High: 200.0 C

(360.0

F)

0

1

2

3

4

5

6

7

8

9

2

3

4

: 0 second time constant

: 0.2 second time constant

: 0.5 second time constant

: 1 second time constant

: 2 seconds time constant

: 5 seconds time constant

: 10 seconds time constant

: 20 seconds time constant

: 30 seconds time constant

: 60 seconds time constant

: High limit control

: Low limit control

: High/Low limit control

100.0

0.0

2

2

18

UM L91-Rev 8

Parameter

Notation

O1.HY

HSP.L

HSP.H

LSP.L

LSP.H

OUT 2

ADDR

Parameter

Description

Output 1 Hysteresis

Value

Lower Limit of HSP1

Upper Limit of HSP1

Lower Limit of LSP1

Upper Limit of LSP1

Range

Low: 0.1

High: 10.0 BC (18.0 BF)

Low: -19999

High: HSP.H

Low: HSP.L

High: 45536

Low: -19999

High: LSP.H

Low: LSP.L

High: 45536

Output 2 Function

3

4

5

6

0

1

2

7

8

9

10

11

: No function

: DC power supply output

: RS-485

Communication

:Alarm output

: Limit annunciator

:Event input

:4-20mA analog retransmission output

:0-20mA analog retransmission output

:0-1V analog retransmission output

:0-5V analog retransmission output

:1-5V analog retransmission output

:0-10V analog retransmission output

Address Assignment of Digital COMM

Low: 1

High: 255

Default

Value

0.1

0 C

(32.0 F)

1000.0 C

(1832.0 F)

-100.0 C

(-148.0 F)

0 C

(32.0 F)

4

1

BAUD

0

Baud Rate of Digital

COMM 1

: 0.3 Kbits/s baud rate

: 0.6 Kbits/s baud rate

UM L91-Rev 8

19

Parameter

Notation

BAUD

PARI

AOFN

AOLO

AOHI

AL.FN

Parameter

Description

Parity Bit of Digital

COMM

2

3

4

Baud Rate of Digital

COMM

5

6

7

8

9

0

1

2

Range

: 1.2 Kbits/s baud rate

: 2.4 Kbits/s baud rate

: 4.8 Kbits/s baud rate

: 9.6 Kbits/s baud rate

: 14.4 Kbits/s baud rate

: 19.2 Kbits/s baud rate

: 28.8 Kbits/s baud rate

: 38.4 Kbits/s baud rate

: 8 bit even parity

: 8 bit odd parity

: 8 bit none parity

Default

Value

5

0

Analog Output

Function

Analog Output Low

Scale Value

Analog Output High

Scale Value

Alarm function

0

1

2

: Process value

: High Limit

Set point 1

: Low Limit

Set point 1

0

Low: -19999

High: 45536

Low: -19999

High: 45536

6

7

: Process value high alarm

: Process value low alarm

0 C

(32.0 F )

100.0 C

(212.0 F )

6

20

UM L91-Rev 8

Parameter

Notation

Parameter

Description

Range

Default

Value

AL.MD

AL.HY

AL.FT

EIFN

DISP

PV.HI

PV.LO

T.ABN

Alarm mode

Alarm hysteresis value

0

1

: Normal alarm action

: Latching alarm action

Low: 0.1

High: 10 BC

(18.0 BF )

Alarm failure transfer

Event input function

0

1

0

1

2

: Alarm output goes off as unit fails

: Alarm output goes on as unit fails

: No event function

: Remote reset for output 1, output 1 on.

: Remote lock for the unit

0 : Display process value

Normal display format

1 : Display

HSP1 or LSP1 value

Historical Max. value of PV

2 : Display the word SAFE

Low: -19999

High: 45536

Historical Min. value of PV

Accumulated time during abnormal condition

Low: -19999

High: 45536

Low: 0

High:6553.5 minutes

0

0.1

1

0

0

Read

Only

Read

Only

Read

Only

21

UM L91-Rev 8

Dangerous voltages capable of causing death are present in this instrument. Before installation or beginning any troubleshooting procedures the power to all equipment must be switched off and isolated. Units suspected of being faulty must disconnected and removed to a properly equipped workshop for testing and repair. Component replacement and internal must be made by a qualified maintenance person only.

To minimize the possibility of fire or shock hazards, do not expose this instrument to rain or excessive moisture.

Do not use this instrument in areas under hazardous conditions such as excessive shock, vibration, dirt, moisture, corrosive gases or oil. The ambient temperature of the areas should not exceed the maximum rating specified in Chapter 6.

Upon receipt of the shipment remove the unit from the carton and inspect the unit for shipping damage.

If any damage due to transit , report and claim with the carrier.

Write down the model number, serial number, and date code for future reference when corresponding with our ser vice center. The serial number (S/N) and date code (D/C) are labeled on the box and the housing of the unit.

Make panel cutout to dimension shown in Figure 2-1.

22

UM L91-Rev 8

I nstall both mounting clamps and insert the housing into panel cutout.

45

+0.5

_

0

45

+0.5

_

0

Panel cutout

Panel

86 mm

94 mm

*

Before wiring, verify the label for correct model number and options. Switch off the power when checking.

*

Care must be taken to ensure that maximum voltage rating specified on the label are not exceeded.

*

It is recommended that power of these units to be protected by fuses or circuit breakers rated at the minimum value possible.

*

All units should be installed inside a suitably grounded metal enclosure to prevent live parts being accessible from human hands and metal tools.

*

All wiring must conform to appropriate standards of good practice and local codes and regulations. Wiring must be suitable for maximum voltage, current, and temperature rating of the system.

*

Take care not to over-tighten the terminal screws.

UM L91-Rev 8

23

*

Unused control terminals should not be used as jumper points as they may be internally connected, causing damage to the unit.

* Verify that the ratings of the output devices and the inputs as specified in Chapter 6 are not exceeded.

*

Electric power in industrial environments contains a certain amount of noise in the form of transient voltage and spikes. This electrical noise can enter and adversely affect the operation of microprocessor-based controls. For this reason we strongly recommend the use of shielded thermocouple extension wire which connects the sensor to the unit. This wire is a twisted-pair construction with foil wrap and drain wire. The drain wire is to be attached to earth ground at the sensor end only.

3.2mm min.

7.0mm max.

24

I

B

V

_

B

A

RTD

_

5

3

4

1

2

_

LL

8

9

6

7

10

_

UM L91-Rev 8

The unit is supplied to operate at 11-26 VAC / VDC or 90-264VAC.Check

that the installation voltage corresponds with the power rating indicated on the product label before connecting power to the unit.

6

7

8

9

10

Fuse

4

5

1

2

3

90

11

~

~

264 VAC or

26 VAC / VDC

This equipment is designed for installation in an enclosure which provides adequate protection against electric shock. The enclosure must be connected to earth ground.

Local requirements regarding electrical installation should be rigidly observed. Consideration should be given to prevent from unauthorized person access to the power terminals.

Proper sensor installation can eliminate many problems in a control system. The probe should be placed so that it can detect any temperature change with minimal thermal lag. In a process that requires fairly constant heat output, the probe should be placed closed to the heater. In a process where the heat demand is variable, the probe should be closed to the work area. Some experiments with probe location are often required to find this optimum position.

25

UM L91-Rev 8

In a liquid process, addition of a stirrer will help to eliminate thermal lag. Since the thermocouple is basically a point measuring device, placing more than one thermocouple in parallel will provide an average temperature readout and produce better results in most air heated processes.

Proper sensor type is also a very important factor to obtain precise measurements. The sensor must have the correct temperature range to meet the process requirements. In special processes the sensor might need to have different requirements such as leakproof, anti-vibration, antiseptic, etc.

Standard thermocouple sensor limits of error are +/-4degrees F

(+/- 2 degrees C ) or 0.75% of sensed temperature (half that for special ) plus drift caused by improper protection or an overtemperature occurrence. This error is far greater than controller error and cannot be corrected at the sensor except by proper selection and replacement.

Thermocouple input connections are shown in Figure 2-5. The correct type of thermocouple extension lead-wire or compensating cable must be used for the entire distance between the unit and the thermocouple, ensuring that the correct polarity is observed throughout. Joints in the cable should be

If the length of thermocouple plus the extension wire is too long, it may affect the temperature measurement. A 400 ohms K type or a 500 ohms J type thermocouple lead resistance will produce approximately 1 degree C temperature error .

26

UM L91-Rev 8

+

1

2

3

4

5

6

7

8

9

10

RTD connection are shown in Figure 2-6, with the compensating lead connected to terminal 4. For two-wire RTD inputs, terminals 4 and 5 should be linked. The three-wire RTD offers the capability of lead resistance compensation provided that the three leads are of same gauge and equal length.

Two-wire RTD should be avoided, if possible, for the purpose of accuracy.

A 0.4 ohm lead resistance of a two-wire RTD will produce 1 degree C temperature error.

RTD

1

2

3

4

5

6

7

8

9

10

RTD

1

2

3

4

5

6

7

8

9

10

UM L91-Rev 8

27

DC linear voltage and linear current connections are shown in Figure 2-7 and Figure 2-8 .

3

4

5

1

2

8

9

10

6

7

Input Wiring

*

4

5

1

2

3

Input Wiring *

NOTE: Volt and Milliamp inputs are NOT FM Approved.

8

9

6

7

10

28

UM L91-Rev 8

+

2

1

3

4

5

8

9

6

7

10

3

4

5

1

2

8

9

6

7

10

The event input can accept a switch signal as well as an open collector signal. The event input function (EIFN) is activated as the switch is closed or an open collector (or a logic signal ) is pulled down.

UM L91-Rev 8

29

3

4

5

1

2

3

4

5

1

2

30

1

2

3

4

5

6

7

8

9

10

Load

8

9

6

7

10

Contactor

6

7

8

9

10

+

SSR

_

+

Load

5V

0V

33

33

10

9

+

UM L91-Rev 8

120V/240V

Supply

Max. 2A

Resistive

LOAD

3

4

5

1

2

120V/240V

Supply

LOAD

SSR

_

+

+

2

1

3

4

5

Sensor or

Transmitter

+

3

4

5

1

2

UM L91-Rev 8

6

7

8

9

10

8

9

6

7

10

8

9

6

7

10

31

TX2

1

TX1

2

3

4

5

6

7

8

9

10

RS-485

Twisted-Pair Wire

RS-485 to RS-232 network adaptor

SNA10A or

SNA10B

TX1

TX2

RS-232

PC

1

2

3

6

7

8

4 9

5

10

Max. 247 units can be linked

Output options include: Ma and VDC

-

+

MA/VDC

3

4

5

1

2

6

9

10

7

8

32

UM L91-Rev 8

Press for 4 seconds to enter setup mode. Press to select the parameter. The display will indicate the parameter symbol and the value

( or selection ) for that parameter.

most (not all) process related parameters.

If 4-20mA is selected for INPT, let SL specifies the input signal low (ie.

4mA), SH specifies the signal high (ie. 20mA), S specifies the current input signal value, the conversion cur ve of the process value is shown as follows:

process value

IN.LO

PV

IN.HI

SL S SH

input signal

33

UM L91-Rev 8

S-SL

SH-SL following setup:

INPT = 4-20 mA

UNIT = PU

RESO = 1-DP

IN.LO = 0.0

IN.HI = 15.0

Of course, you may select other value for RESO to alter the resolution.

a proper value to eliminate the relay jitter in a noisy environment.

Hidden if LO is selected for OUT1

Hidden if LO is selected for OUT1

Hidden if HI is selected for OUT1

Hidden if HI is selected for OUT1

HSP.L and HSP.H in setup menu are used to confine the adjustment range of HSP1. LSP.L and LSP.H are used to confine the adjustment range of LSP1.

34

UM L91-Rev 8

In certain application it is desirable to shift the indicated value from its actual value. This can be easily accomplished with this unit by using the PV shift function.

Cycle the unit to the SHIF parameter by using the scroll key.

The number you adjust here, either positive or negative, will

In certain applications the process value is too unstable to be read. To Improve this a programmable low pass filter incorporated in the L91 can be used. This is a first order filter with time constant specified by FILT parameter which is contained in setup menu. The

FILT is defaulted to 0.5 sec. before shipping. Adjust FILT to change the time constant from 0 to 60 seconds. 0 second represents no filter is applied to the input signal. The filter is characterized by the following diagram.

PV

1sec

FILT=0

FILT=1

FILT=30

1sec

Time

35

UM L91-Rev 8

The output 2 will per form process alarm function by selecting

ALM for OUT2 and PV.H.A or PV.L.A for AL.FN. If PV.H.A is selected the alarm will per form process high alarm. If PV.L.A

is selected the alarm will per form process low alarm. The process alarm sets an absolute trigger level. When the process exceeds that absolute trigger level an alarm occurs.

The trigger level is determined by SP2 (Set point 2 value) and

AL.HY (Alarm hysteresis value). The hysteresis value is introduced to avoid inter ference action of alarm in a noisy environment. Normally AL.HY can be set with a minimum value(0.1).

Trigger levels for process high alarm are SP2 and SP2 AL.HY.

Trigger level for process low alarm are SP2+AL.HY and Sp2.

There are two types of alarm mode can be selected, these are: normal alarm and latching alarm.

When a normal alarm is selected, the alarm output is deenergized in the non-alarm condition and energized in an alarm condition.

If a latching alarm is selected, once the alarm output is energized, it will remain unchanged even if the alarm condition has been cleared unless the power is shut off or the RESET key (or remote reset button) is pressed.

In case of Sensor Break or A-D Failure occurs, the alarm output will be on or off according to the selection of AL.FT.

Examples:

SP2 = 200

AL.MD = NORM

AL.HY = 10.0

AL.FN = PV.H.A

36

UM L91-Rev 8

Examples:

200

190

200

190

ON

200

190

200

190

OFF

200

190

200

190

200

190

ON 200

190

200

190

200

190

Using a PC for data communication is the most economic way.

The signal is transmitted and received through the PC communication Port (generally RS-232). Since a standard PC can't support RS-485 port, a network adaptor (such as SNA10A, SNA10B) has to be used to convert RS-485 to RS-232 for a PC if RS-485 is required for the data communication. Many RS-485 units (up to

247 units) can be connected to one RS-232, that is a PC with 4 comm ports can communicate with 988 units.

37

UM L91-Rev 8

Select COMM for OUT2 in setup menu, the output 2 will perform

RS-485 interface with protocol.

Setup

1. Select COMM for OUT2

2. Set an unequal address (ADDR) for those units which are connected to the same port.

3. Set the Baud Rate (BAUD) and Parity Bit (PARI) such that these values are accordant with PC setup conditions.

The DISP in the setup menu is used to select the display format for the normal condition. If PV is selected, the display will indicate the process value. If SP1 is selected, the display will indicate HSP1 value for high limit control (OUT1= HI) and high/low limit control (OUT1= HI.LO) or indicate LSP1 value for low limit control(OUT1=LO). IF SAFE is selected, the display will indicate the word SAFE for the normal condition.

However the display will indicate the process value if the process value goes beyond high limit or low limit. If an error condition occurs, the display will indicate the error symbol.

The SAFE display will return when the process has returned to within SAFE values. Depressing reset key will reset output relay.

Three types of isolated DC power supply are available to supply an external transmitter or sensor. These are 20V rated at 25mA, 12V rated at 40 mA and 5V rated at 80 mA. The DC voltage is delivered to the output 2 terminals by selecting

DCPS for OUT2 in setup menu.

38

UM L91-Rev 8

+

4-20mA

+

2

3

1

4

5

COM

IN

OUT

V or mA

+

2

3

+

4

5

1

6

7

8

9

10

6

7

8

9

10

DC Power Supply

+

2

1

3

+

4

5

6

7

8

9

10

Don't use the DC power supply beyond its rating current to avoid damage.

Purchase a correct voltage to suit your external devices. See ordering code in section 1-2.

39

UM L91-Rev 8

If EIFN is selected for OUT2 and REST is selected for EIFN, terminals

1 & 2 will act as remote reset input. Pressing remote reset button will perform the same function as pressing the RESET key. Refer to for RESET key function.

Remote

Reset

3

4

5

1

2

8

9

10

6

7

Setup

If EIFN is selected for OUT2 and LOCK is selected for EIFN, terminals

1 & 2 will act as remote lock input. Turning the remote lock switch on will keep all the parameter setting from been changed.

Remote

Lock

3

4

5

1

2

6

Setup

9

10

7

8

40

UM L91-Rev 8

If L_AN (Limit annunciator) is selected for OUT2, the output 2 will act as a

Limit Annunciator. If the limit is or has been reached and the RESET key

(or remote reset contacts)has not been pressed since the limit was reached, then the limit annunciator output will be energized and the

OP2 indicator will be lit and remain unchanged until the RESET key or remote reset input is applied.

There are three reference data contained in setup menu. The reference data are read only data. The maximum historical PV, displayed by ,which shows the maximum process value since the last UNLOCK operation. The minimum historical PV, displayed by , which shows the minimum process value since the last UNLOCK operation. The abnormal time, displayed by ,which shows the total accumulated time (minutes) during the process has been in abnormal condition since the last

UNLOCK operation.

The values of reference data will be initiated as soon as the RESET key is pressed for 4 seconds (UNLOCK operation). After UNLOCK operation, the PV.HI and PV.LO values will start from the current process value and T.ABN value will start from zero.

UM L91-Rev 8

41

42

Temperature

Control

3

4

5

1

2

8

9

6

7

10

_

+

Rear View

Reset

Button

1

Limit Control

2

3

4

5

L91

Rear View

8

9

6

7

10

Mechanical

Contactor

Heater

L N

UM L91-Rev 8

Do not proceed through this section unless there is a definite need to re-calibrate the controller. Otherwise, all previous calibration data will be lost. Do not attempt re-calibration unless you have appropriate calibration equipment. If calibration data is lost, you will need to return the unit to your supplier who may change you a service fee to re-calibrate the unit.

Entering calibration mode will break the control loop. Make sure that if the system is allowable to apply calibration mode.

Equipment needed for calibration:

(1) A high accuracy calibrator (Fluke 5520A Calibrator recommended) with following function:

0-100mA millivolt source with +/-0.005% accuracy

0-10V voltage source with +/-0.005% accuracy

0-20mA current source with +/-0.005% accuracy

0-300 ohm resistant source with +/-0.005% accuracy

(2) A test chamber providing 25 C - 50 C temperature range

(3) A switching network (SCANNER 80, optional for automatic calibration)

(4) A calibration fixture equipped with programming units

(optional for automatic calibration)

(5) A PC with calibration software FD-Net and Smart Network

Adaptor SNA10B (optional for automatic calibration)

Since each unit needs 30 minutes to warm up before calibration.

The calibration procedures described in the following are a step by

Apply Enter Key (press calibration mode. see for 8 seconds) to enter the

.

43

UM L91-Rev 8

RESET

RESET

Normal Mode

4 seconds

Setup Mode

4 seconds

Ad0

Step 1

4 seconds

RESET

RESET

RESET

RESET

ADG

CJTL

CJG

REF

Step 2

4 seconds

Step 3

4 seconds

Step 4

4 seconds

Step 5

4 seconds

RESET

SR

Step 6

4 seconds

Step1: Calibrate Zero of A to D converter.

Short terminal 4 and 5, then press for at least 4 seconds.

The display will blink a moment. If the display didn't blink, then the calibration has failed.

44

UM L91-Rev 8

Step 2: Calibrate Gain of A to D converter.

Send a span signal to terminal 4 and 5 with correct polarity.

The span signal is 60 mV for thermocouple input, 1V for

0-1V input, 10V for 0-10V input and 20mA for 0-20 mA input.

Press for at least 4 seconds. The display will blink a moment. If the display didn't blink, then the calibration failed.

Step 3: Calibrate offset of cold junction .

Setup the equipment according to the following diagram for calibrating the cold junction compensation. Note that a

K type thermocouple must be used.

Calibrator

K-TC

K+

4

L 9 1

5

K

Stay at least 20 minutes in stillair room room temperature

25 +/- 3 C

The L91 being calibrated for Cold Junction Compensation MUST be programmed for K t/c input, Celsius display

prior

to performing the CJTL calibration.

Set the calibrator to be configured as K type thermocouple output. Calibrator must have an internal compensation.

Send a 0.00 C signal to the unit under calibration.

With CJTL on the display adjust the value to 0.00 reading.

Once adjusted, Press for at least 4 seconds. The display will blink a moment. If the display didn't blink, then the calibration failed.

45

UM L91-Rev 8

Step 4: Calibrate gain of cold junction .

Setup the equipment same as step 3.

The L91 being calibrated for Cold Junction Compensation MUST be programmed for K t/c input, Celsius display

prior

to performing the CJG calibration.

Set the calibrator to be configured as K type thermocouple output. Calibrator must have an internal compensation.

Send a 0.00 C signal to the unit under calibration.

With CJG on the display adjust the value to 0.00 reading.

Once adjusted, Press for at least 4 seconds. The display will blink a moment. If the display didn't blink, then the calibration failed.

Step 5: Calibrate RTD reference voltage .

Send a 100 ohms signal to terminal 3, 4 and 5 according to

.

100 ohms

3

4

5

1

2

8

9

6

7

10

Press for at least 4 seconds. The display will blink a moment. If the display didn't blink, then the calibration failed.

Step 6: Calibrate RTD serial resistance .

Change the ohm's value of the calibrator to 300 ohms. Press for at least 4 seconds. The display will blink a moment.

If the display didn't blink, then the calibration failed.

46

UM L91-Rev 8

90-264 VAC, 49-63 Hz, 10 VA, 5W maximum

11-26 VAC/VDC, 10 VA, 5W maximum

18 bits

5 times/second

-2 VDC minimum, 12 VDC maximum

(1 minute for mA input)

A1.5 uV / C

T/C: 0.2 uV/ohm

3-wire RTD: 2.6 C/ohm of resistance difference of two leads

2 -wire RTD: 2.6 C/ohm of resistance sum of two leads

200nA

120db

Sensor open for TC, RTD and mV inputs, below 1 mA for 4-20 mA input, below 0.25V for 1-5 V input, unavailable for other inputs.

Within 4 seconds for TC, RTD and mA inputs,

0.1 second for 4-20 mA and 1-5V inputs.

Interface : RS-485 ( up to 247 units )

Protocol : Modbus Protocol RTU mode

Address : 1 - 247

Baud Rate : 0.3 ~ 38.4 Kbits/sec

Data Bits : 8 bits

Parity Bit : None, Even or Odd

Stop Bit : 1 or 2 bits

Communication Buffer : 50 bytes

47

C h a r a c t e r i s t i c s :

K

T

E

Type

J

Range

( -184 F 1832 F )

-200 C 1370 C

( -328 F 2498 F )

-250 C 400 C

( -418 F 752 F )

-100 C 900 C

( -148 F 1652 F )

B

0 C 1820 C

( - 32 F 3308 F )

R

S

N

L mV mA

V

0 C 1767.8 C

( - 32 F 3214 F )

0 C 1767.8 C

( - 32 F 3214 F )

-250 C 1300 C

( -418 F 2372 F )

-200 C 900 C

( -328 F 1652 F )

-210 C 700 C

( -346 F 1292 F )

-200 C 600 C

( -328 F 1112 F )

-8mV 70mV

-3mA 27mA

-1.3V

11.5V

48

UM L91-Rev 8

100

-10V minimum, 0.8V maximum.

2V minimum, 10V maximum.

Remote reset, remote lockout.

2A/240 VAC, life cycles 200,000 for resistive load.

Source Voltage 5V, current limiting resistance

66 ohms.

1/240 VAC

20A for 1 cycle

50 mA rms

3 mA rms

1.5 V rms

1000 Mohms min. at 500 VDC

2500 VAC for 1 minute

Ripple

Voltage

20 V +/-0.5 V 25 mA

0.2 Vp-p

500 VAC

12 V +/-0.3 V 40 mA

0.1 Vp-p

5 V +/-0.15 V 80 mA

0.05 Vp-p

Analog Retransmission

Functions: Process Variable

Output Signal: 4-20 mA, 0-20 mA, 0 - 5V, 1 - 5V, 0 - 10V

Resolution : 15 bits

Accuracy : +/-0.05 % of span +/-0.0025 %/ C

Load Resistance : 0 - 500 ohms ( for current output )

10 K ohms minimum ( for voltage output )

Regulation: 0.01 % for full load change

Settling Time: 0.1 sec. (stable to 99.9 % )

Breakdown Volts: 1000 VAC min.

Linearity Error : +/-0.005 % of span

Temp Effect: +/-0.0025 % of span / C

Saturation Low : 0 mA ( or 0V )

Saturation High : 22.2 mA ( or 5.55V, 11.1V min. )

Output Range :0-22.2mA(0-20mA or 4-20mA)

0-5.55V ( 0 - 5V, 1 - 5V )

0 - 11.1 V ( 0 - 10V )

49

4 keys

0.4" (10mm),

For automatic setup, calibration and testing.

Connection to PC for supervisory control.

programmable

First order

0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60 seconds programmable

2

2

50

EMC EN61326

UM L91-Rev 8

Warranty and Return Statement:

Warranty:

Future Design Controls products described in this brochure are warranted to be free from functional defects in material and workmanship at the time the products leave Future Design Controls facilities and to conform at that time to the specifications set forth in the relevant Future Design Controls manual, sheet or sheets for a period of TWO years after delivery to the first purchaser.

There are no expressed or implied Warranties extending beyond the Warranties herein and above set forth.

Limitations:

Future Design Controls provides no warranty or representations of any sort regarding the fitness of use or application of its products by the purchaser. Users are responsible for the selection, suitability of the products for their application or use of Future Design Controls products.

Future Design Controls shall not be liable for any damages or losses, whether direct, indirect, incidental, special, consequential or any other damages, costs or expenses excepting only the cost or expense of repair or replacement of Future Design Control products as described below.

Future Design Controls sole responsibility under the warranty, at

Future Design Controls option, is limited to replacement or repair, free of charge, or refund or purchase price within the warranty period specified. This warranty does not apply to damage resulting from transportation, alteration, misuse or abuse.

Future Design Controls reserves the right to make changes without notification to purchaser to materials or processing that do not effect compliance with any applicable specifications.

Return Material Authorization:

Contact Future Design Controls for Return Material Authorization prior to returning any product to our facility.

30

Future Design Controls, Inc.

7524 West 98th Place, PO Box 1196,Bridgeview, IL 60455

888.751.5444 - Main Office

888.307.8014 - Fax

866.342.5332 - Technical Suport

E-mail

Website [email protected]

www.futuredesigncontrols.com

UM L91-Rev 8

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement