Series 90-70 High Speed Counter User`s Manual, GFK

Series 90-70 High Speed Counter User`s Manual, GFK
ÎÎ
GE Fanuc Automation
Programmable Control Products
t
Series 90 -70
High Speed Counter
User’s Manual
GFK-1062A
November 1995
GFL–002
Warnings, Cautions, and Notes
as Used in this Publication
Warning
Warning notices are used in this publication to emphasize that
hazardous voltages, currents, temperatures, or other conditions that
could cause personal injury exist in this equipment or may be
associated with its use.
In situations where inattention could cause either personal injury or
damage to equipment, a Warning notice is used.
Caution
Caution notices are used where equipment might be damaged if care is
not taken.
Note
Notes merely call attention to information that is especially significant to
understanding and operating the equipment.
This document is based on information available at the time of its publication. While
efforts have been made to be accurate, the information contained herein does not
purport to cover all details or variations in hardware or software, nor to provide for
every possible contingency in connection with installation, operation, or maintenance.
Features may be described herein which are not present in all hardware and software
systems. GE Fanuc Automation assumes no obligation of notice to holders of this
document with respect to changes subsequently made.
GE Fanuc Automation makes no representation or warranty, expressed, implied, or
statutory with respect to, and assumes no responsibility for the accuracy, completeness,
sufficiency, or usefulness of the information contained herein. No warranties of
merchantability or fitness for purpose shall apply.
The following are trademarks of GE Fanuc Automation North America, Inc.
Alarm Master
CIMPLICITY
CIMPLICITY
PowerTRAC
CIMPLICITY 90–ADS
CIMSTAR
Field Control
GEnet
Genius
Genius PowerTRAC
Helpmate
Logicmaster
Modelmaster
ProLoop
PROMACRO
Series Five
Series 90
Series One
Series Six
Series Three
VuMaster
Workmaster
Copyright 1995 GE Fanuc Automation North America, Inc.
All Rights Reserved
Preface
This manual provides the specifications, hardware interface requirements, and
programming information needed to install and use the High Speed Counter module for
the Series 90t-70 Programmable Logic Controller. The Series 90-70 Programmable Controller
Installation Manual, GFK-0262, should be your primary reference for information about the
Series 90-70 Programmable Logic Controller. It describes types of systems, system planning,
installation procedures, and system components for the Series 90-70 PLC. Note that the
High Speed Counter requires Logicmaster 90-70 release 5.0, or later.
Compatibility Requirements
The compatibility requirements for Series 90-70 CPU models and Logicmaster 90-70
programming software that are required for operation with the High Speed Counter are
listed in the following table.
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Product
Required Version
Series 90-70 CPU
5.03 or later (Models 731, 732, 771, 772)
5.50 or later (Adds Models 781, 782, 914, 924)
6.00 or later (Adds Models 915, 925)
Logicmaster 90-70 ProgrammingSoftware
5.0x or later
Revisions to This Manual
This version of the Series 90-70 High Speed Counter User’s Manual includes some
additions and several corrections to the manual. These changes as compared to the
previous version are listed below.
H Page 1-4, deleted reference to Hand-Held Programmer at end of third paragraph.
H Page 1-7, deleted sentence beginning with Each output . . . at end of first paragraph
under Outputs.
H Page 3-14, added Error Code 31 to table at top of page.
H Page 4-4, deleted last two sentences in second paragraph under Strobe Linkage.
Added third paragraph, beginning with The following illustration . . and added the
following illustration and sentence after the illustration.
H
H
H
H
H
D
GFK-1062A
Page 4-16, added Error Code 31 to table at top of page.
Page 5-2, added statement at end of first sentence beginning with that can be . . . .
Page 5-5, added heading Differential Counting and following illustrations.
Page 5-18, added Error Code 31 to table.
Page 6-15, added Error Code 31 to table at bottom of page.
Page 7-4, added new paragraph beginning with At power-up . . . at top of page.
Series 90t-70 High Speed Counter User’s Manual – November 1995
iii
Preface
H
H
Page 7-6, change wording of first two paragraphs under Preset Outputs (Standard).
Page 7-9, changed Output Mode Default entry in table to Pulse, and added a third
value, DISABLE, for Preset CTR#.
H
H
Page 7-16, added Error Code 31 to table (Error Codes for Type E Counter).
H
H
Page C-5, added Error Descriptor 3 under Nibble 1.
H
Page 7-20, Changed heading beginning with Preset Accumulator . . . to read Preset
Accumulator (0, 1, or 2, presets 3 and 4 only), and added sentence under that
heading beginning with A data value . . .
Page D-2, deleted environmental and general specifications from table and added
reference to GFK-0867B after table.
Page E-9, E-10, added description of application - Measuring or Comparing Pulse Rates.
Content of this Manual
This manual contains the following information:
Chapter 1. Introduction: provides an overview of the Series 90-70 High Speed Counter
module features.
Chapter 2. Installation and Wiring: describes installation and field wiring for the High
Speed Counter module.
Chapter 3. Counter Type A: describes operation of the Type A counter.
Chapter 4. Counter Type B: describes operation of the Type B counter.
Chapter 5. Counter Type C: describes operation of the Type C counter.
Chapter 6. Counter Type D: describes operation of the Type D counter.
Chapter 7. Counter Type E: describes operation of the Type E counter.
Appendix A. Using Special CPU Communications Functions: provides descriptions
and examples of sending data commands to the High Speed Counter using the
COMMREQ function in the PLC’s ladder diagram and using the DOIO function as it
relates to the High Speed Counter.
Appendix B. Using Interrupts with the HSC: provides a description of how to use
interrupts with the High Speed Counter,
Appendix C. High Speed Counter Summary: provides a summary of return data,
output data, data commands, error codes, and wiring information for the High Speed
Counter.
Appendix D. Module Specifications: provides specifications for the High Speed
Counter.
Appendix E. Application Examples: provides a group of application examples using
the various features of the High Speed Counter.
iv
Series 90t-70 High Speed Counter User’s Manual – November 1995
GFK-1062A
Preface
Related Publications:
H
GFK-0262: Series 90t-70 Programmable Controller Installation Manual. Describes
system hardware components and system configuration, and provides installation
and field wiring information for system planning and actual installation.
H
GFK-0401: Workmasterr II PLC Programming Unit Guide to Operation. Describes
installation and operation of the Workmaster II computer, specifically when it is used
as the programming device for a Series 90 Programmable Logic Controller.
H
GFK-0263: Logicmastert 90-70 Programming Software User’s Manual. Explains use of
Logicmastert 90-70 software to configure a Series 90-70 Programmable Logic
Controller and create application programs.
H
GFK-0265: Series 90t-70 Programmable Controllers Reference Manual. Describes the
programming instructions used to create application programs for the Series 90-70
Programmable Logic Controllers.
H
GFK-1179: Installation Requirements for Conformance to Standards. Describes installation
requirements for programmable control products used in industrial environments,
specifically, in situations where compliance to standards or directives from the
Federal Communications Commission, the Canadian Department of
Communications, or the European Union is necessary.
We Welcome Your Comments and Suggestions
At GE Fanuc Automation, we strive to produce quality documentation. After you have
used this manual, please take a few moments to complete and return the Reader’s
Comment Card located on the next page.
Henry A. Konat
Senior Technical Writer
GFK-1062A
Series 90t-70 High Speed Counter User’s Manual – November 1995
v
Contents
Chapter 1
Chapter 2
vi
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
High Speed Counter Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
Configurable Counter Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description of Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2
1-2
Count Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selectable Input Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Continuous or Single-Shot Counting . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4
1-4
1-4
Counter Accumulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Counts per Timebase Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4
1-4
Strobe Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preloads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-5
1-5
Selectable On/Off Output Presets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selectable Preset Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-5
1-5
Oscillator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Velocity Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-5
1-5
1-5
Accumulator Adjust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-5
1-6
Count Rate and Input Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Continuous or Single-Shot Counting . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8
1-8
Preloads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Strobe Register Stack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Counter Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8
1-8
1-8
Output Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Oscillator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-9
1-9
Data Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-9
Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
I/OModule Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
Recommended Field Wiring Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing an I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
2-3
Field Wiring Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal Board Pin Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3
2-4
User Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical User Input Circuit Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7
2-7
Encoder Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical Encoder Connections Using External Power Supply . . . . . . . . .
User Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7
2-8
2-8
Typical Output Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Oscillator Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-8
2-9
Oscillator Output Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring for TTL Open-Collector Input Devices . . . . . . . . . . . . . . . . . . . . . .
2-9
2-9
Series 90-70 High Speed Counter User’s Manual – November 1995
GFK-1062A
Contents
Chapter 3
Counter Type A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1
Contents and Operation of a Type A Counter . . . . . . . . . . . . . . . . . . . . . . . . .
3-1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1
Count Pulse Input and Accumulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Strobe Input and Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Preloads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3
Counts per Timebase Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3
Preset Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4
Preset Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5
Output Failure Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5
Oscillator Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5
Configuring the Type A High Speed Counter . . . . . . . . . . . . . . . . . . . . . . . . .
3-6
Output Failure Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-6
Oscillator Divider . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7
Input Thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7
Input Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7
Preset Accumulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7
Output Preset ON and OFF Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-8
Data Transfer Between High Speed Counter and CPU . . . . . . . . . . . . . . . . .
3-11
%I and %AI Data Sent by a Module Configured as Type A . . . . . . . . . . .
3-11
Status Bits (%I) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
%AI Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
%Q and %AQ Data Sent from CPU to HSC Configured as Type A . . . .
3-15
%Q Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Data Commands for Counter Type A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Chapter 4
GFK-1062A
Counter Type B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
Contents and Operation of a Type B Counter . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
Count A and B Inputs and Accumulator . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2
Strobe Inputs and Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4
Strobe Linkage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4
Preload Input and Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5
Counts per Timebase Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5
Preset Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6
Preset Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7
Output Failure Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7
Oscillator Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7
Series 90-70 High Speed Counter User’s Manual – November 1995
vii
Contents
Configuring the Type B High Speed Counter . . . . . . . . . . . . . . . . . . . . . . . . .
4-8
Output Failure Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-8
Oscillator Divider . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-9
Input Thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-9
Input Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-9
Preset Accumulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-9
Output Preset ON and OFF Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-10
Count Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-11
Count Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-11
Count Signal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-12
Counter Timebase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-12
Preload Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-12
Strobe Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-12
Strobe Edge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-12
Strobe Linkage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-12
Data Transfer Between High Speed Counter and CPU . . . . . . . . . . . . . . . . .
4-13
%I and %AI Data Sent by a Module Configured as Type B . . . . . . . . . . .
4-13
Status Bits (%I) - Type B Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
%AI Data - Type B Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
%Q and %AQ Data Sent from CPU to HSC Configured as Type B . . . . .
4-17
%Q Data - Type B Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18
Data Commands for Counter Type B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
Chapter 5
viii
Counter Type C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
Contents and Operation of a Type C Counter . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
Count Inputs and Accumulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2
Strobe Inputs and Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-6
Preload Input and Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-6
Home Switch, Marker Input, and Home Value . . . . . . . . . . . . . . . . . . . . .
5-7
Counts per Timebase Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-7
Preset Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-7
Preset Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-8
Output Failure Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-8
Oscillator Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-9
Configuring the Type C High Speed Counter . . . . . . . . . . . . . . . . . . . . . . . . .
5-10
Output Failure Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-10
Oscillator Divider . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-11
Input Thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-11
Series 90-70 High Speed Counter User’s Manual – November 1995
GFK-1062A
Contents
Chapter 6
GFK-1062A
Input Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Output Preset ON and OFF Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preset Interrupt Enables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Count Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Count Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Count Signal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Counter Timebase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preload Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Home Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Strobe Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Strobe Edge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-11
5-11
5-13
5-13
5-13
5-14
5-14
5-14
5-14
5-15
5-15
Data Transfer Between High Speed Counter and CPU . . . . . . . . . . . . . . . . .
%I and %AI Data Sent by a Module Configured as Type C . . . . . . . . . . .
Status Bits (%I) - Type C Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
%AI Data - Type C Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
%Q and %AQ Data Sent from CPU to HSC Configured as Type C . . . .
%Q Data - Type C Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Commands for Counter Type C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-16
5-16
5-17
5-18
5-21
5-22
5-24
Counter Type D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1
Contents and Operation of a Type D Counter . . . . . . . . . . . . . . . . . . . . . . . . .
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Count A and B Inputs and Accumulator . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preload Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Marker Input and Home Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Counts per Timebase Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preset Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preset Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Output Failure Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Oscillator Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring the Type D High Speed Counter . . . . . . . . . . . . . . . . . . . . . . . . .
Output Failure Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Oscillator Divider . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input Thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preset Accumulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Output Preset ON and OFF Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1
6-1
6-2
6-4
6-4
6-5
6-5
6-6
6-6
6-6
6-8
6-8
6-9
6-9
6-9
6-9
6-10
Data Transfer Between High Speed Counter and CPU . . . . . . . . . . . . . . . . .
%I and %AI Data Sent by a Module Configured as Type D . . . . . . . . . . .
Status Bits (%I) - Type D Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
%AI Data - Type D Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
%Q and %AQ Data Sent from CPU to HSC Configured as Type D . . . .
%Q Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Commands for Counter Type D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-13
6-13
6-14
6-15
6-17
6-18
6-19
Series 90-70 High Speed Counter User’s Manual – November 1995
ix
Contents
Chapter 7
Counter Type E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1
Contents and Operation of a Type E Counter . . . . . . . . . . . . . . . . . . . . . . . . .
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Count A and B Inputs and Accumulator . . . . . . . . . . . . . . . . . . . . . . . . . . .
Strobe Inputs and the Strobe Event Stack . . . . . . . . . . . . . . . . . . . . . . . . .
Preload Input and Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preset Outputs (Fast Response) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preset Outputs (Standard) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preset Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Output Failure Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Oscillator Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring the Type E High Speed Counter . . . . . . . . . . . . . . . . . . . . . . . . .
Output Failure Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Oscillator Divider . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input Thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Output Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Outpulse Milliseconds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preset Accumulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standard Preset Output ON and OFF Positions . . . . . . . . . . . . . . . . . . . .
Count Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Count Signal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preload Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Strobe Edge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Transfer Between High Speed Counter and CPU . . . . . . . . . . . . . . . . .
%I and %AI Data Sent by a Module Configured as Type E . . . . . . . . . . .
Status Bits (%I) - Type E Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
%AI Data - Type E Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
%Q and %AQ Data Sent from CPU to HSC Configured as Type E . . . . .
%Q Data - Type E Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Commands for Type E Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix A Using Special CPU Communications Functions . . . . . . . . . . . . . . . . .
Sending Data Commands Using the COMMREQ Function . . . . . . . . . . . . .
COMMREQ Function Block Description . . . . . . . . . . . . . . . . . . . . . . . . . .
Communications Request Function Block Format . . . . . . . . . . . . . . . . . . .
Updating I/O Data using the DOIO Function . . . . . . . . . . . . . . . . . . . . . . . . .
DOIO Function Block Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix B Using Interrupts with the HSC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
x
7-1
7-1
7-2
7-4
7-4
7-4
7-6
7-6
7-7
7-8
7-9
7-9
7-10
7-10
7-10
7-10
7-11
7-11
7-11
7-12
7-12
7-12
7-12
7-13
7-13
7-14
7-15
7-17
7-17
7-19
A-1
A-1
A-1
A-1
A-6
A-6
B-1
High Speed Counter Interrupt Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Interrupt Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controlling Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Masking Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Suspending Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B-1
B-1
B-3
B-3
B-5
Series 90-70 High Speed Counter User’s Manual – November 1995
GFK-1062A
Contents
Appendix C High Speed Counter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C-1
High Speed Counter %I Return Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
High Speed Counter %AI Return Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-2
High Speed Counter %Q Control Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3
High Speed Counter Data Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
High Speed Counter Module Status Codes (%AI Word 1) . . . . . . . . . . . . C-5
High Speed Counter User I/O Terminal Pin Assignments . . . . . . . . . . . . C-6
Appendix D Module Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications for the High Speed Counter . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix E Application Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GFK-1062A
D-1
D-1
E-1
Counter Cascading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-2
Monitoring and Controlling Differential Speeds . . . . . . . . . . . . . . . . . . . . . . .
E-3
Direction-Dependent Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-4
RPM Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-7
Tolerance Checking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-8
Measuring or Comparing Pulse Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-9
Measuring Pulse Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-11
Measuring Total Material Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-12
Material Handling Conveyor Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-13
Timing Pulse Generation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-14
Digital Velocity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-15
Dynamic Counter Preloading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-16
Carousel Tracking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-17
Series 90-70 High Speed Counter User’s Manual – November 1995
xi
Contents
Figure 1-1. Series 90-70 High Speed Counter Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3
Figure 2-1. I/O Module Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
Figure 2-2. Removal of I/O Terminal Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2
Figure 2-3. Field Wiring for the High Speed Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4
Figure E-1. Example of Direction-Dependent Sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-5
Figure E-2. Output Timing Conditions Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-6
Figure E-3. Example of Terminal Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-6
Figure E-4. Example of Tolerance Checking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-8
Figure E-5. Terminal Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-8
Figure E-6. Example of Terminal Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-9
xii
Series 90-70 High Speed Counter User’s Manual – November 1995
GFK-1062A
Contents
Table 2-1. Pin Assignments for Each Counter Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5
Table 3-1. Type A Specific Terminal Strip Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5
Table 4-1. Type B Specific Terminal Strip Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7
Table 5-1. Type C Specific Terminal Strip Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-9
Table 6-1. Type D Specific Terminal Strip Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-7
Table 7-1. Type E Specific Terminal Strip Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-8
Table B-1. Service Request #17 Parameter Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B-3
Table E-1. Counter Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-4
Table E-2. Operating Count Directions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-4
xiv
Series 90-70 High Speed Counter User’s Manual – November 1995
GFK-1062A
Restarts for autonumbers that do not restart in
each chapter.
figure bi level 1, reset
table_big level 1, reset
chap_big level 1, reset 1
app_big level 1, reset A
figure_ap level 1, reset
table_ap level 1, reset
figure level 1, reset
table level 1, reset
Table 1.
Chapter
these restarts must be in the header frame of
chapter 1.
a:ebx, l 1 reset
A
a:obx:l 1, reset
A
a:bigbx level 1 reset
A
a:ftr level 1 reset
A
c:ebx, l 1 reset
1
c:obx:l 1, reset
1
c:bigbx level 1 reset
1
c:ftr level 1 reset
1
1 Introduction
Reminders for autonumbers that need to be
restarted manually (first instance will always be 4)
also needs to be in head:bx:1ch:
let_in level 1:
A. B. C.
letter level 1:
A.B.C.
num level 1:
1. 2. 3.
num_in level 1:
1. 2. 3.
rom_in level 1:
I. II. III.
roman level 1:
I. II. III.
steps level 1:
1. 2. 3.
section level 1
figure bi level 1
table_big level 1
1
This chapter describes:
H
H
H
H
The High Speed Counter Module
Configurable counter types
Basic module features
The module’s inputs and outputs
High Speed Counter Module
The High Speed Counter (HSC) module, catalog number IC697HSC700, for the Series
90t-70 Programmable Logic Controller (PLC) provides direct processing of rapid pulse
signals up to 200 kHz (800 kHz for Type E in A Quad B mode) for industrial control
applications such as:
H
H
H
H
H
H
H
Turbine flowmeter
Meter proving
Velocity measurement
Material handling
Motion control
Process control
Printing processes
Direct processing means that the module is able to sense inputs, process the input count
information, and control the outputs without needing to communicate with a CPU.
The High Speed Counter uses 18 words of input memory. This consists of 32 bits of
discrete input memory (%I) and 16 words of analog input memory (%AI). These inputs
are updated once per CPU sweep. The High Speed Counter also uses 32 bits of discrete
output memory (%Q) and 6 words of analog output memory (%AQ) which are
transferred once per sweep. DOIO functions can be used to update any type of the HSC
reference data more frequently.
The High Speed Counter is configured using the Logicmastert 90-70 Programming
Software Configurator function. Many features can be configured from the user’s
application program as well. Each feature is set to a factory default configuration which
is suitable for many applications. There are no jumpers or DIP switches to set on the
module. The green LEDs at the top of the module indicate the operating status of the
module and the current status of each of the preset outputs.
GFK-1062A
1-1
1
Configurable Counter Types
When the module is configured, a counter type must first be selected. The choices are:
H
H
H
H
H
Type A - selects four identical, independent simple 16-bit counters
Type B - selects two identical, independent 32-bit bidirectional counters
Type C - selects one complex counter
Type D - selects four identical, independent simple 32-bit counters
Type E - selects two identical, fast response 16-bit counters
Type A Configuration
When used in this basic configuration, Type A, the module has four identical
programmable up or down 16-bit counters. Each counter can be programmed to count
either up or down. Each has three inputs: a Preload input, a Count Pulse input, and a
Strobe input.
Type B Configuration
In its Type B configuration, the module has two identical bidirectional 32-bit counters.
The count inputs may be configured to accept Up/Down, Pulse/Direction, or A Quad B
signals. For a Type B counter configuration, each counter has two completely
independent sets of Strobe inputs and Strobe registers. A Disable input is available to
suspend counting. A Linked Strobe mode allows counter 2 counts to generate a strobe
on both counters. This allows timing of a pulse by comparison to a known pulse rate.
Type C Configuration
In the Type C configuration, the module has one 32-bit counter with three strobe
registers with strobe inputs, and two Preload values with Preload inputs. In addition,
the module has a Home Position register for preloading the Accumulator to the Home
Position value. Two sets of bi-directional counter inputs can be connected to operate in a
differential fashion. Each set of inputs can be configured for A Quad B, Up/Down, or
Pulse/Direction operation. The Type C configuration is suitable for applications requiring
motion control, differential counting, or homing capability.
Type D Configuration
The Type D counter contains four identical 32-bit bidirectional counters which can
interpret A Quad B, Up/Down, or Pulse/Direction inputs. A Home Position register
allows a marker input to preload the Accumulator to the Home Position during a Home
cycle. In A Quad B mode, the counter detects quadrature errors.
Type E Configuration
The Type E counter contains two identical 16-bit counters with Strobe and Preload inputs
capable of counting Up/Down or A Quad B signals. Each has a Count Disable and a Strobe
Disable input. The Type E counter is designed primarily as a Down counter, but can handle
up counts to account for A Quad B jitter. When a counter counts down to zero, it turns on
a dedicated preset output with a 15µs response time.
Description of Module
Module features include:
H
1-2
12 differential or single-ended (source) inputs with input voltage range selection of
either 5 VDC (TTL) or 10 to 30 VDC (NON-TTL)
Series 90t-70 High Speed Counter User’s Manual – November 1995
GFK-1062A
1
H
4 positive logic (source) outputs independently assignable to any available counter
(Types A - D)
H
H
H
H
H
H
H
External oscillator
Built-in +5 VDC output
Counts per timebase register for each counter (Types A - D)
Software configuration
Internal module diagnostics
Individual LEDs that provide a visual indication of Module OK and Output States
A removable terminal board for connection of field wiring
a45425
OK
O1
O2
O3
O4
HIGH SPEED
COUNTER
5/12/24 VDC
I1
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
O1
O2
O3
O4
01–04 1.0A @ 12/24VDC
01–04 0.02A @ 5 VDC
4.0A MODULE
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
OK
O1
O2
O3
O4
HIGH SPEED COUNTER
5/12/24 VDC
1
I1
2
3
I2
4
5
I3
6
7
I4
8
SHIELD
9
INCOM
10
11
I5
12
13
I6
14
15
16
I8
I7
17
18
SHIELD
I9
INCOM
20
21
I9
22
23
I10
24
25
I11
26
27
I12
28
SHIELD
29
INCOM
30
31
5V
32
OSC
SHIELD
33
UNUSED
34
V L+ 35
Î
Î
V
O
36
37
1 O2
O3
39
O4
38
OUTCOM 40
MODULE IC697HSC700
LABEL 44A726758–030R01
Figure 1-1. Series 90-70 High Speed Counter Module
GFK-1062A
Chapter 1 Introduction
1-3
1
Inputs can be used as count signals, direction, disable, edge-sensitive strobe, and preload
inputs depending on the counter type selected by the user. Outputs can be used to drive
indicating lights, solenoids, relays, and other devices.
For each counter, a Counts per Timebase register indicates the number of counts in a
given time interval. The Counts per Timebase data is a 16-bit signed number. The sign
indicates up counts (+) or down counts (–). The Timebase value is specified in
milliseconds and ranges from 1 to 65535 milliseconds.
All configuration parameters for the module are downloaded from the PLC to the High
Speed Counter after it passes its internal diagnostics and the MODULE OK indicator has
turned on. An initial (default) set of configuration parameters is loaded during diagnostics.
These default parameters can be used or modified through a download from the PLC.
Operation of the High Speed Counter module is monitored by a watchdog timer circuit
which, if it detects a module failure, will force all outputs off and turn off the MODULE OK
LED.
Type A, B, C, and D Operating Features
Operating features of the High Speed Counter for Types A, B, C, and D are described below.
Features that have selectable parameters are configured using the Logicmaster 90
Programming Software Configurator function that has been installed on your programming
computer. For detailed information about selectable features, refer to the applicable chapter
for each counter type in this manual.
Count Rate
Maximum count rates are 200 KHz with the high frequency filter and 30 Hz with the
low-frequency filter.
Selectable Input Filters
The Count, Count Disable, and Preload inputs for each counter can be configured for a high
frequency filter (2.5 microseconds) or a low-frequency filter (12.5 milliseconds).
Continuous or Single-Shot Counting
Each counter can be configured to operate in either continuous or single-shot mode.
Continuous Counter Mode: If either the upper or lower count limit is exceeded the counter
wraps around to the other limit and continues.
Single-shot Counter Mode: The counter counts to either the upper or lower limit and stops.
When the counter is at the limit, counts in the opposite direction back it off from the limit.
Counter Accumulator
The Accumulator contains the current count value of each counter. The CPU can read the
accumulator value or set it from the application program.
Counts per Timebase Register
Each counter stores the number of counts that have occurred in a specified period of time.
A timebase value from 1 ms to 65535 ms can be configured.
1-4
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
1
Strobe Register
Type A, B and C counters have one or more Strobe registers that capture the current
Accumulator value when a Strobe input transitions. The Strobe inputs are edge-triggered
and can be configured for positive-edge or negative-edge response. The Strobe registers
can be configured to update at any Strobe trigger or only on the first strobe trigger
Preloads
Counters A, B and C have one or more Preload inputs. The Preload inputs set the
accumulator to a configured Preload value. %Q bits sent from the PLC can also be used to
generate Preloads and set the accumulator to the configured Preload value.
Selectable On/Off Output Presets
Counter output signals can be configured to be On or Off when the count Accumulator
reaches configured On and Off Preset values. There are four On/Off Preset outputs which
can be independently assigned to any counter. An assigned output’s state indicates when
the counter Accumulator is between the defined On and Off points. Output polarity can
be configured to On only between points or Off only between points by the relative location
of the On/Off Presets.
Selectable Preset Interrupts
Each Preset output can generate PLC interrupts from On and/or Off transitions. Interrupts
can be enabled for either or both transitions of each Preset output.
Oscillator
The module provides an external oscillator output that can be wired as a count input to any
counter and used as a timing reference for measurement. The 5V square wave oscillator
output can be configured to operate at frequencies from 15 Hz to 1 MHz. This output has
a CMOS buffer with a 47 ohm output impedance.
Data Commands
The PLC can send data commands to the HSC70 through %AQ data or with a COMMREQ.
These commands allow the user to dynamically modify counter operation and
configuration parameters. Configuration parameters that can be dynamically modified
include: accumulator value, counter limits, Preload values, On and Off Preset values and
Home Position.
Velocity Command
A %AQ or COMMREQ Data Command can be used to generate an internal velocity of up
to 100,000 counts per second. The counter accumulator will increment or decrement at the
commanded velocity. Counts generated by the user count inputs will be accumulated in
addition to the Velocity Command counts.
Accumulator Adjust
A data command can be used to adjust the accumulator value from –128 to +127 counts
at any time.
GFK-1062A
Chapter 1 Introduction
1-5
1
Module Inputs and Outputs
The High Speed Counter Module accepts 12 input signals, and can provide four output
signals, plus an oscillator output and a +5 VDC output.
INPUT 1
INPUT 2
a43073
OUTPUT 1
INPUT 3
INPUT 4
INPUT 5
OUTPUT 2
INPUT 6
INPUT 7
INPUT 8
OUTPUT 3
INPUT 9
INPUT 10
INPUT 11
OUTPUT 4
INPUT 12
+5 VOLTS
OSCILLATOR
Inputs
Inputs can include count signals, Disable, edge-sensitive Strobe, and other inputs which
can be configured for the application. Input filters can be configured for high frequency
or low frequency operation.
Count Inputs:
A rising edge on a count input will increment or decrement its Count Accumulator.
The method of counting depends upon the counter type and the count mode
configured.
The Count input is positive-edge sensitive. It may be configured to have either the
high-frequency (2.5mS) or low-frequency filter (12.5mS). The default filter is
high-frequency.
Preload Inputs:
Each counter has a configurable preload register. The contents of this register
determine the value the counter resets to when the Preload input goes active. The
default value of the Preload register is zero.
The Preload input is positive-edge sensitive. It may be configured to have either the
high-frequency (2.5mS) or low-frequency filter (12.5mS). The default is
high-frequency.
If Preload occurs during counting, preload data with a resolution of Ç 1 count is
stored in the accumulator and a Preload flag is set to indicate to the CPU that a
Preload occurred.
1-6
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
1
Strobe Inputs:
Strobe inputs are edge-sensitive. They may be configured to respond to either the
positive or negative edge. Strobe inputs always have the 2.5mS high-frequency filter
enabled. On counter types with multiple strobe inputs, the strobes may occur
simultaneously without affecting the integrity of the data strobed. When the strobe
signal goes active, count data with a resolution of one count is stored in the
associated Strobe register and a Strobe flag is set to indicate to the CPU that a strobe
value was captured. This value remains in the Strobe register until the Strobe signal
goes active again, at which time it is overwritten. Each time the CPU acknowledges
receipt of the Strobe flag, the application program should clear it.
If a Strobe input and Preload input both go active in the same 0.5mS interval, both
the Accumulator and Strobe register will be set to the Preload value.
Other Inputs:
These are described under the discussion of operation for each counter type.
Outputs
The module’s four outputs can be used to drive indicating lights, solenoids, relays,
and other devices. The outputs are also capable of driving CMOS level loads. Each
output is a positive logic (source) output, with power supplied from a user supplied
power source. The outputs are protected against short circuits by a common 3 Amp
picofuse. Diodes protect outputs against transients going below output common.
The module’s outputs can be programmed to turn on or off when the accumulated
count reaches appropriate values. The count input-to-output delay is 1mS
maximum (200mS minimum) plus the configured Input Filter Time.
GFK-1062A
Chapter 1 Introduction
1-7
1
Type E Operating Features
Operating features of the High Speed Counter for Type E are described below.
Count Rate and Input Filters
The maximum count rate with the low-frequency filter (12.5 milliseconds) is 30 Hz; with the
high-frequency filter (2.5µs), the maximums are 200 KHz in Up/Down mode and 800 kHz
in A Quad B mode. The Count, Count Disable, and Preload inputs for each counter can use
either filter, but the Strobe and Strobe Disable inputs use only the high-frequency filter.
Continuous or Single-Shot Counting
Each counter can be configured to operate in either continuous or single-shot mode.
Continuous Counter Mode: When the counter decrements to zero, it turns on the fast
response output and automatically preloads itself to the preload value and continues
counting.
Single-shot Counter Mode: When the counter counts to zero, it turns on the fast response
output and ignores count pulses until a preload occurs.
Preloads
A rising edge on the Preload input, a rising edge on the %Q Preload Accumulator bit, or the
counter decrementing to zero in Continuous mode will set the accumulator to a configured
Preload value. Preloads caused by the Preload input and count decrementing to zero will
set a %I bit in the PLC to indicate a preload occurred.
Strobe Register Stack
Each counter has a Strobe Register stack which will store up to four strobe values. Strobes
can be configured to occur on rising, falling, or both edges of the Strobe input. %I bits
indicate how many strobes have occurred. A Reset Strobes %Q bit or a Preload clears the
Strobe Register stack and %I indicators. A Strobe Disable input causes all Strobe input
transitions to be ignored.
Counter Outputs
The Type E counter supports two types of output presets, Fast Response and Standard.
Fast Response: There is one dedicated fast response output for each accumulator. The fast
response output turns on within 15µs of the associated counter decrementing to zero, with
less than 2µs variation. In addition, two output modes are supported for the fast response
outputs.
Pulse Output Mode: The output turns on when the Accumulator counts down to zero and
stays on for a configured duration, from 1 to 1000 milliseconds.
Latched Output Mode: (Single Shot mode only) The output turns on when the Accumulator
counts down to zero and stays on until a Preload occurs.
Standard Output Presets: Outputs 3 and 4 can be assigned to either counter and configured
to be On or Off when the count Accumulator reaches configured On and Off values. An
assigned output’s state indicates when the counter Accumulator is between the defined On
and Off points.
1-8
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
1
Output Interrupts
Interrupts can be enabled or disabled for Off to On transitions of the fast response outputs.
Interrupts can be enabled or disabled for either transition of the standard preset outputs.
Oscillator
The module provides an external oscillator output that can be wired as a count input to any
counter and used as a timing reference for measurement. The 5V square wave oscillator
output can be configured to operate at frequencies from 15 Hz to 1 MHz. This output has
a CMOS buffer with a 47 ohm output impedance.
Data Commands
The PLC can send data commands to the HSC70 through %AQ data or with a COMMREQ.
These commands allow the user to dynamically modify counter operation and
configuration parameters. Configuration parameters that can be dynamically modified
include: Preload values, On and Off Preset values, and Fast Response output duration.
GFK-1062A
Chapter 1 Introduction
1-9
section level 1
figure bi level 1
table_big level 1
Chapter
2 Installation and Wiring
2
I/O Module Installation and Wiring
This chapter contains information on installing the High Speed Counter module and
information relevant to field wiring to and from the module.
Recommended Field Wiring Procedures
The following procedures are recommended when connecting field wiring to the detachable
terminal board on the module. Module features referenced in the following procedures that
are common to all Series 90-70 I/O modules are shown in the following figure.
a43855
JACKSCREW
HINGED
DOOR
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎ
ÎÎÎÎ
ÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
Î
ÎÎÎÎ
ÎÎ
Î
Î
TERMINAL
BOARD
CORD
TIE
CORD
TIE
CLEAT
STRAP
JACKSCREW
Î
CORD
TIE
CLEAT
CORD
TIE
STRAP
CLEAT
ÎÎ
ÎÎ
Î
Î
STRAP
Figure 2-1. I/O Module Features
GFK-1062A
2-1
2
1.
Turn off power before removing or installing terminal boards. Open the hinged
door on the module to access a jackscrew which holds the terminal board securely
in place. The detachable field wiring terminal board can now be removed from the
module by turning the jackscrew counter-clockwise until it is fully disengaged.
2.
To remove the terminal board, grasp the top of the terminal board and swing it
outward.
Caution
Do not use the hinged door to remove the terminal board. The hinged
door could be damaged if this is done.
3.
The terminal board is designed to accept wire sizes from AWG #22 (0.35 mm2)
through AWG #14 (2.1 mm2). It is important that when using AWG #14 (2.1 mm2)
wire for wiring all points, that a maximum insulation diameter of .135 inch (3.43
mm) not be exceeded. To ensure proper connection, two wires may be terminated
on any one terminal only if both wires are the same size.
4.
The terminal board is designed to accept a maximum of (40) AWG #14 (2.1
mm2)wires. If AWG #14 (2.1 mm2) wires are to be used, then wire markers should
be placed at least 8 inches (203 mm) from termination end to provide sufficient space
for the hinged door to close.
ÎÎ
ÎÎ
Î
ÎÎ
Î
ÎÎ
ÎÎ
Î
Î
ÎÎ
Î
ÎÎ
Î
ÎÎ
Î
ÎÎ
Î
ÎÎ
ÎÎÎ
Î
ÎÎ
Î
ÎÎ
Î
ÎÎ
Î
ÎÎ
Î
ÎÎ
ÎÎÎ
Î
ÎÎ
Î
ÎÎ
Î
JACKSCREW
a43747
ÎÎÎ
Î
ÎÎÎ
Î
ÎÎÎ
Î
ÎÎÎÎÎ
ÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎ
DO NOT
PULL
ON DOOR
WIRE BUNDLE CABLE TIE CLEAT
Figure 2-2. Removal of I/O Terminal Board
5.
2-2
After completing connections to all modules in a rack, the wire bundle must be secured.
To ensure that the wire bundle is secured properly, it is recommended that a cable tie be
wrapped around the wire bundle and tightly secured through the cable tie cleat located
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
2
6.
7.
8.
at the lower right corner of the terminal board. For extremely large wire bundles,
additional cable ties should be used.
A door label insert is included with each module to indicate circuit wiring information
and provide space to record user circuit wiring identification. A slot is provided on the
hinged door to allow for insertion of this label. If the label is difficult to insert, crease
the scored edge before insertion. The outside label has a color coded stripe to allow
quick identification of the module voltage type (blue: low voltage; red: high voltage).
After field wiring is completed, the terminal board should be securely fastened to the
rack by inserting the terminal board strap (attached to each module) into the small
rectangular slots in the bottom card guide grill on the rack. This strap not only secures
the terminal board to the rack, it also provides a way of identifying the wired terminal
board with its correct mating rack slot location.
For adequate module ventilation, it is recommended that at least a 6 inch (152 mm)
clearance be allowed above and below the rack grill. Wire bundles should not obstruct
the rack grill work.
Removing an I/O Module
The instructions below should be followed when removing an I/O module from its slot in
a rack.
H
Grasp the board firmly at the top and bottom of the board cover with your thumbs
on the front of the cover and your fingers on the plastic clips on the back of the
cover.
H
Squeeze the rack clips on the back of the cover with your fingers to disengage the
clip from the rack rail and pull the board firmly to remove it from the backplane
connector.
H
Slide the board along the card guide and remove it from the rack.
Field Wiring Considerations
It is recommended that the following procedures be followed when routing and
connecting field wiring from user devices to the PLC or to Output devices to be
controlled by the PLC.
H
H
All low level signal wires should be run separately from other field wiring.
AC power wiring should be run separately from DC field wiring.
Warning
You should calculate the maximum current for each wire and observe
proper wiring practices. Failure to do so may cause injury to personnel
or damage to equipment.
GFK-1062A
H
Field wiring should not be routed close to any device that could be a potential source
of electrical interference.
H
If severe noise problems are present, additional power supply filtering or an
isolation transformer may be required.
H
Ensure that proper grounding procedures, as previously described, are followed to
minimize potential safety hazards to personnel.
H
Label all wires to and from I/O devices. Record circuit identification numbers or
other pertinent data on the inserts which go in the module’s faceplate door.
Chapter 2 Installation and Wiring
2-3
2
Terminal Board Pin Assignments
The High Speed Counter Module has a removable terminal strip for connection to field
devices. High Speed Counter terminal board pin assignments for field wiring
connections are shown in the following figure.
The following figure provides wiring information for field connections to and from the
High Speed Counter.
a45426
HIGH SPEED COUNTER
5/12/24 VDC
PIN
NAME
1
1
IN1P
2
IN2P
3
IN1M
4
IN2M
5
IN3P
6
IN4P
7
IN3M
8
IN4M
9
SHIELD
10
INCOM
11
IN5P
12
IN6P
13
IN5M
14
IN6M
15
IN7P
16
IN8P
17
IN7M
18
IN8M
19
SHIELD
20
INCOM
21
IN9P
22
IN10P
23
IN9M
24
IN10M
25
IN11P
26
IN12P
27
IN11M
28
IN12M
29
SHIELD
30
INCOM
31
OSC
32
5VP
33
SHIELD
34
not used
35
OUTPWR
36
OUT1
37
OUT2
38
OUT3
39
OUT4
40
OUTCOM
I1
2
3
I2
4
5
I3
6
7
I4
8
SHIELD
9
INCOM
10
11
I5
12
13
I6
14
15
16
I7
17
I8
18
I9
SHIELD
INCOM
20
21
I9
22
23
I10
24
25
I11
26
27
I12
28
29
INCOM
30
SHIELD
OSC
31
5V
32
SHIELD
33
UNUSED
34
VL+ 35
V
O1
36
37
O3
38
39
OUT COM
O2
O4
40
MODULE IC697HSC700
LABEL 44A726758–030R01
Figure 2-3. Field Wiring for the High Speed Counter
2-4
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
2
Note
All 12 High Speed Counter inputs are positive logic (source) type.
Transducers with CMOS buffer outputs (74HC04 equivalent) can directly drive the High
Speed Counter inputs using the 5V input range.
Transducers using TTL totem pole or open collector outputs must include a 470 ohm pullup
resistor (to 5V) to guarantee compatibility with the High Speed Counter inputs.
Transducers using high voltage open collector (sink) type outputs must have a 1K pullup
resistor to +12V for compatibility with the High Speed Counter 10 to 30 volt input range.
Caution
Do not connect 10 to 30 VDC to the module inputs when the 5 VDC
input range (pins 13 to 15 jumpered) is selected. Doing so will cause
damage to the module.
Terminal Assignments for Counter Type
The following table defines which terminals to use for the type of counter selected
during module configuration.
Table 2-1. Pin Assignments for Each Counter Type
Signal
Pin
GFK-1062A
Name
Signal Name by Counter Type
Pin Definition
Type A
Type B
Type C
Type D
Type E
1
IN1P
Positive Logic Input - Positive
CH1P
CH1AP
CH1AP
CH1AP
CH1AP
2
IN2P
Positive Logic Input - Positive
CH2P
CH1BP
CH1BP
CH1BP
CH1BP
3
IN1M
Positive Logic Input - Negative
CH1M
CH1AM
CH1AM
CH1AM
CH1AM
4
IN2M
Positive Logic Input - Negative
CH2M
CH1BM
CH1BM
CH1BM
CH1BM
5
IN3P
Positive Logic Input - Positive
CH3P
CH2AP
CH2AP
CH2AP
CH2AP
6
IN4P
Positive Logic Input - Positive
CH4P
CH2BP
CH2BP
CH2BP
CH2BP
7
IN3M
Positive Logic Input - Negative
CH3M
CH2AM
CH2AM
CH2AM
CH2AM
8
IN4M
Positive Logic Input - Negative
CH4M
CH2BM
CH2BM
CH2BM
CH2BM
9
SHIELD
Cable Shield
SHIELD
SHIELD
SHIELD
SHIELD
SHIELD
10
INCOM
Common for positive logic inputs
INCOM
INCOM
INCOM
INCOM
INCOM
11
IN5P
Positive Logic Input - Positive
PRLD1P
PRLD1P
PRLD1P
CH3AP
PRLD1P
12
IN6P
Positive Logic Input - Positive
PRLD2P
DISABLE1P
DISABLE1P
CH3AP
DISABLE1P
13
IN5M
Positive Logic Input - Negative
PRLD1M
PRLD1M
PRLD1M
CH3AM
PRLD1M
14
IN6M
Positive Logic Input - Negative
PRLD2M
DISABLE1M
DISABLE1M
CH3BM
DISABLE1M
15
IN7P
Positive Logic Input - Positive
PRLD3P
PRLD2P
PRLD2P
CH4AP
PRLD2P
16
IN8P
Positive Logic Input - Positive
PRLD4P
DISABLE2P
HOMEP
CH4BP
DISABLE2P
17
IN7M
Positive Logic Input - Negative
PRLD3M
PRLD2M
PRLD2M
CH4AM
PRLD2M
18
IN8M
Positive Logic Input - Negative
PRLD4M
DISABLE2M
HOMEM
CH4BM
DISABLE2M
19
SHIELD
Positive Logic Output
SHIELD
SHIELD
SHIELD
SHIELD
SHIELD
Chapter 2 Installation and Wiring
2-5
2
Table 2-1.
Pin Assignments for Each Counter Type (continued)
Signal
Pin
2-6
Signal Name by Counter Type
Name
Pin Definition
Type A
Type B
Type C
Type D
Type E
20
INCOM
Common for positive logic inputs
INCOM
INCOM
INCOM
INCOM
INCOM
21
IN9P
Positive Logic Input - Positive
STRB1P
STRB11P
STRB11P
MRKR1P
STRB1P
22
IN10P
Positive Logic Input - Positive
STRB2P
STRB12P
STRB12P
MRKR2P
STRB2P
23
IN9M
Positive Logic Input - Negative
STRB1M
STRB11M
STRB11M
MRKR1M
STRB1M
24
IN10M
Positive Logic Input - Negative
STRB2M
STRB12M
STRB12M
MRKR2M
STRB2M
25
IN11P
Positive Logic Input - Positive
STRB3P
STRB21P
STRB21P
MRKR3P
STRBDIS1P
26
IN12P
Positive Logic Input - Positive
STRB4P
STRB22P
MRKR1P
MRKR4P
STRBDIS2P
27
IN11M
Positive Logic Input - Negative
STRB3M
STRB21M
STRB21M
MRKR3M
STRBDIS1M
28
IN12M
Positive Logic Input - Negative
STRB4M
STRB22M
MARK1M
MRKR4M
STRBDIS2M
29
SHIELD
Cable Shield
SHIELD
SHIELD
SHIELD
SHIELD
SHIELD
30
INCOM
Common for positive logic inputs
INCOM
INCOM
INCOM
INCOM
INCOM
31
OSC
Oscillator Input
OSC
OSC
OSC
OSC
OSC
32
5VP
5 VDC Power Source
5VP
5VP
5VP
5VP
5VP
33
SHIELD
Cable Shield
SHIELD
SHIELD
SHIELD
SHIELD
SHIELD
34
SPARE
not used
SPARE
SPARE
SPARE
SPARE
SPARE
35
OUTPWR
Common for outputs
OUTPWR
OUTPWR
OUTPWR
OUTPWR
OUTPWR
36
OUT1
Output 1, Positive Logic
HSCOUT1
HSCOUT1
HSCOUT1
HSCOUT1
HSCOUT1
37
OUT2
Output 2, Positive Logic
HSCOUT2
HSCOUT2
HSCOUT2
HSCOUT2
HSCOUT2
38
OUT3
Output 3, Positive Logic
HSCOUT3
HSCOUT3
HSCOUT3
HSCOUT3
HSCOUT3
39
OUT4
Output 4, Positive Logic
HSCOUT4
HSCOUT4
HSCOUT4
HSCOUT4
HSCOUT4
40
OUTCOM
Common for outputs
OUTCOM
OUTCOM
OUTCOM
OUTCOM
OUTCOM
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
2
User Inputs
H
H
H
H
H
H
Input Type:
Differential or single-ended, optically isolated
Input Range:
TTL, Non-TTL, or Magnetic Pickup
Input Impedance:
6000 W
Input Filtering:
10 ms to 2 ms selectable
Input Hysteresis:
250 mV, typical
Input Cable:
Shielded cable is recommended with maximum length of 30
meters (100 Feet)
Typical User Input Circuit Diagram
a47070
3K
–
I1+
OPTO
COUPLER
+
I1–
IN
3K
INCOM
3K
3K
SHIELD
VREF1
Encoder Installation
H
Encoder Power:
Optically isolated current limited +5 Volt supply is
available at the High Speed Counter I/O connector.
Maximum load should be 500 mA at 40°C (104°F) or 300
mA at 60°C (140°F).
H
H
H
H
Encoder Common:
INCOM (same as User Inputs)
Quadrature Tolerance:
90 degrees Ç 45 degrees
Z (Marker) Channel:
Positive edge triggered. Minimum pulse width 4 ms.
Encoder Direction of Travel: Channel A leading Channel B indicates positive direction.
Encoder Power Circuit Diagram
a47071
5V
IN
OUT
5V
REGULATOR
INCOM
GFK-1062A
Chapter 2 Installation and Wiring
2-7
2
Typical Encoder Connections Using External Power Supply
a43721
5/12/24 V
POWER SUPPLY
+
HSC
HSC
ENCODER
ENCODER
+5V
+ 5/12/24V
0V
0V
A–CHANNEL
OUTPUT
I1
a43723
5V
POWER SUPPLY
+
I1
A–CHANNEL
OUTPUT
I1
I1
B–CHANNEL
OUTPUT
I2
I2
I2
B–CHANNEL
OUTPUT
I2
MARKER
CHANNEL
OUTPUT
C8
C8
MARKER
CHANNEL
OUTPUT
C8
C8
(25) SHD
(25) SHD
INCOM
INCOM
Connections for Differential Inputs
Power: Positive Loop
Connections for Single-Ended Inputs
Power: Positive Loop
User Outputs
H
H
H
H
H
H
H
H
Output Type:
Positive logic, optically isolated
Output Supply Voltage:
30.0 VDC
Maximum Load Current:
1.0 A for each output using 10 to 30 VDC supply
Typical 5 VDC Output Current:
20 mA
Inductive Load Clamp Voltage:
–8.0 V typical
Off State Leakage Current:
10 mA per output
Typical Output Response Time:
500 ms
Output protection:
Single 5.0 A, 5x20mm fuse
Typical Output Circuit
a47072
OUTPWR
(VL+)
>
5.0A FUSE
Î
Î
30V
MOV
OUT1
>
30V
OPTO
COUPLER
<
4.7KW
5V
OUTCOM
2-8
t
>
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
2
Oscillator Output
H
H
H
Output Type:
CMOS, optically isolated
Maximum Load Current:
50 mA
H
Minimum Low Level Output
Voltage VOL at 20 mA:
0.2 V
Oscillator Common:
INCOM (shared with User Inputs)
H
Minimum High Level Output
Voltage VOH at 20 mA:
3.7 V
Oscillator Output Circuit
a47073
OSC
>
51 W
OPTO
COUPLER
<
CMOS
BUFFER
Wiring for TTL Open-Collector Input Devices
For TTL open-collector inputs, an external resistor must be provided. Be sure the input
device is capable of handling the load current represented by the suggested resistor
value.
Open-collector Input Device with +5 Volt Power Provided by the High Speed Counter
When using +5 volt power provided by the High Speed Counter, use a nominal pullup
resistor of 1K ohm, 1/4 Watt, 5%.
a43718
TYPICAL
OPEN–COLLECTOR
INPUT DEVICE
HSC
+ 5V
Î
1K
1/4W 5%
INPUT
DC
GFK-1062A
Chapter 2 Installation and Wiring
2-9
2
Open-collector Input Device with External Power Supply
For an external power supply, suggested nominal resistors are:
H
H
H
1K ohm, 1/4 Watt, 5% for a +5 volt supply.
1.5K ohm, 1/4 Watt, 5% for a +12 volt supply.
4.7K ohm, 1/4 Watt, 5% for a +24 volt supply.
5V
POWER SUPPLY
+
HSC
a43719
TYPICAL
OPEN–COLLECTOR
INPUT DEVICE
Î
Î
1K
1/4W 5%
INPUT
DC
2-10
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
Chapter
3 Counter Type A
section level 1
figure bi level 1
table_big level 1
3
Counter Type A is described in this chapter. The description includes counter operation,
configuration of the counter, and the interface between the counter and CPU.
Contents and Operation of a Type A Counter
Overview
The Series 90-70 High Speed Counter, when configured as Type A contains four 16-bit
unidirectional counters. Each counter is controlled by 3 of the 12 single ended or
differential voltage inputs: Count Pulse, Strobe, and Preload. Each counter can be
individually configured to count either up or down. Counter Type A elements are
shown in the figure below. Each counter has the following:
H
H
accumulator register which counts the pulses on the Count Pulse input
H
H
a preload value which is inserted into the accumulator when a preload occurs
a strobe register which stores the accumulator value when the Strobe input
transitions
a counts per timebase register which indicates the count rate of the Count Pulse
input pulses.
Each of the four 5 to 30 V preset outputs can be independently assigned to any of the
four counters, and can be used to generate PLC interrupts.
a47056
UP OR DOWN COUNTER (16-BIT)
PRELOAD
COUNT
PULSE
PRELOAD VALUE
(16-BIT)
PRESET
OUTPUT
#1
ACCUMULATOR
(16-BIT)
#2
COUNTS PER
TIME BASE
(16-BIT)
STROBE
GFK-1062A
STROBE REGISTER
(16-BIT)
ACCUMULATOR
ADJUST
(8-BIT)
#3
#4
3-1
3
Count Pulse Input and Accumulator
Positive transitions on the Count Pulse input will increment or decrement the 16-bit
Accumulator value by one count depending on the counter direction. The counter direction
is initially set in the configuration, and may be changed by using a data command.
The Accumulator is bounded by configurable High and Low Limits. The interaction
between the Accumulator and the limits depends on the configured count mode. In
Continuous mode, the Accumulator will increment or decrement to the current High or
Low Limit, roll over to the other limit, and continue counting. In Single Shot mode, the
Accumulator will count to the current High or Low Limit and stop. If the counter
direction is changed, the Accumulator will count away from the limit until it reaches the
other limit.
The High and Low Limits can be changed to any valid 16-bit value at any time using a data
command from the PLC. To be a valid 16-bit value, the following conditions must be met:
H
H
H
the High Limit must be greater than the Low Limit
the Preload value must be within the High and Low Limit bounds
any presets assigned to the counter must have ON and OFF values within the High
and Low Limit bounds.
If the limits are changed so the Accumulator is outside the limit boundaries, the
Accumulator is set to the Low Limit.
The Accumulator can be set to any 16-bit value within the bounds of the High and Low
limits at any time using a data command. Another data command allows the
Accumulator to be adjusted by a byte increment value, from –128 to +127 counts.
Finally, a velocity can be commanded which causes the Accumulator to increment or
decrement at a fixed rate. The following figure illustrates the counting operation and
timing of a counter counting up.
a42971
COUNT PULSE
INPUT
ACCUMULATOR
VALUE
N +2
N +1
N
Strobe Input and Register
The Strobe input is an edge sensitive input which can be configured to respond to either
a positive edge or a negative edge. When the configured Strobe input transition occurs,
(referred to as a Strobe Pulse) the value in the Accumulator is stored in the Strobe
register and a strobe flag is set and returned in %I data to indicate the event to the CPU.
The application program in the CPU acknowledges receipt of the strobe by toggling the
corresponding Strobe Status %Q bit.
Two strobe modes are available to select which Strobe value is most important. In Last
Strobe mode (the default) a Strobe Pulse will always update the Strobe register with
3-2
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
3
the latest Accumulator value regardless of the strobe status flags. In First Strobe mode,
the first strobe is captured and all subsequent Strobe Pulses are ignored until the strobe
flag is cleared by toggling the corresponding Reset Strobe %Q bit.
The Strobe then Preload configuration option allows a Strobe Pulse to, in addition to
capturing the Accumulator value in the Strobe register, automatically perform a preload
by placing the configured preload value into the Accumulator and setting the preload
flag in the %I data.
Preloads
Preloads are normally used to perform a reset function for the counter. The value to
which the Accumulator is set when a preload occurs can be configured to any 16-bit
value within the range of the High and Low Limits and has a default value of zero. The
Preload value can also be changed using a data command from the PLC. There are two
types of Preloads, hardware and software.
A hardware preload uses the Preload input and is positive edge sensitive only. On the
positive transition, the configured Preload value is inserted into the Accumulator and the
Preload flag is set and returned in %I data to indicate the event to the CPU. If an
application program uses this status flag, it may use the corresponding %Q bit to clear
the Preload flag before the next preload occurs. A rising edge on the Preload input
always preloads the Accumulator regardless of the state of the Preload flag.
Note that when a pulse occurs on the Preload inputs at the same time that a Strobe pulse
occurs, or if the inputs are tied together, the Preload has precedence. The Accumulator
will be set to the Preload value and then the Strobe register will be set to the
Accumulator. Thus the Strobe register will obtain a copy of the Preload value. The
counter will automatically perform a Preload after every Strobe pulse when the Strobe
Effect configuration option is set to Strobe then Preload.
A software preload can be performed by setting a Preload Accumulator %Q bit. On the
positive transition of this %Q bit, the current preload value is placed into the
Accumulator. A software preload does NOT set the Preload flag.
Counts per Timebase Register
The Counts per Timebase register is a 16-bit register which contains the number of
counts received on the Count Pulse input in the last completed timebase interval. It is
used to measure the rate of counting. If more counts are received than can be stored in a
16-bit register, the register will overflow. The timebase interval is a configurable value
from 1 to 65535 milliseconds.
Changes to the timebase will not take effect until after the previous timebase and one
new timebase have elapsed. A Preload will interrupt counting and cause the Counts per
Timebase register to be inaccurate for up to two timebase intervals. The timebase is
initially configured as 1 second, but may be changed using the Logicmaster 90-70
Configurator function or a data command.
As an unsigned number, the Counts per Timebase register will correctly indicate from 0
to 65536 positive counts received per timebase. As a signed number, it will properly
indicate from –32768 to 32767 counts per timebase. The timebase should be selected to
not allow more counts in a timebase than the 16-bit register can hold or it will overflow.
GFK-1062A
Chapter 3 Counter Type A
3-3
3
Preset Outputs
The module has four preset outputs, each of which can be assigned to any counter. Each
preset output has a preset ON and preset OFF value, or position, which must be within
the count limits of the counter to which the preset is assigned. The preset ON and OFF
positions determine when the output will be ON or OFF, as shown below.
Preset closest to low limit
Output ON
Output OFF
ON
> = ON Preset
< = OFF Preset
> OFF Preset
< ON Preset
OFF
< OFF Preset
> ON Preset
< = ON Preset
> = OFF Preset
The output may be either on or off when the accumulator value lies between the Preset
points.
OFF
PRESET
ON
PRESET
a42970
ON CONDITION INCLUDES PRESET POINTS
OFF
PRESET
ON
PRESET
OFF CONDITION INCLUDES PRESET POINTS
For example:
COUNTS
OFF PRESET
VALUE
ON PRESET
VALUE
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎÎÎÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ACCUMULATOR
VALUE
a43003
TIME
ON
CORRESPONDING
OUTPUT
OFF
Separation of Preset Points
The count accumulators are compared to the Presets at 0.5 msec intervals. Therefore, to
guarantee that the outputs will always switch, the Preset points must be separated by at
least the number of counts received in a 0.5 msec time period. For example:
If maximum count rate = 10kHz;
then minimum count separation = (10,000 Hz x .0005 sec) = 5 counts.
3-4
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
3
Preset Interrupts
Interrupts can be enabled or disabled for each preset output’s ON and OFF transition.
At the same time a preset output changes state, the CPU is interrupted. %I and %AI
data is transferred so that the interrupt routine will see the most current data from the
High Speed Counter. Simultaneous preset changes generate only one interrupt to the
CPU, so the updated %I data must be used by an interrupt routine to determine which
presets changed state and which edge(s) generated the interrupt. Once configured,
interrupts can be independently enabled or disabled using data commands. See
Appendix B for information on using the interrupt capability.
Output Failure Mode
When the CPU is stopped or lost, counter operation continues normally without
interfacing to the CPU. Preset output operations during this stopped state can be
configured for one of three modes. In Normal mode, the outputs continue to operate as
if the CPU were present, changing state to reflect the counter Accumulators. In Force
Off mode, all preset outputs are turned off and remain off until the CPU returns. In
Holdlast mode, the preset outputs retain current levels and do not reflect the counter
Accumulators. If the CPU resumes operation, the outputs will immediately begin
reflecting the counter Accumulators.
Oscillator Output
The High Speed Counter module generates a 5V square wave oscillator signal. The
oscillator output frequency is determined by the current oscillator divider (set in
configuration or by data command) as indicated below:
Oscillator Frequency (Hz) = 1,000,000 Ï oscillator divider
The output frequency ranges from approximately 15 Hz (oscillator divider of 65535) to 1
MHz (oscillator divider of 1).
Table 3-1. Type A Specific Terminal Strip Assignments
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
GFK-1062A
Pin
Signal
Name
Type A
Pin Name
1,3
IN1
COUNT PULSE 1
Counter 1 count input
2,4
IN2
COUNT PULSE 2
Counter 2 count input
5,7
IN3
COUNT PULSE 3
Counter 3 count input
6,8
IN4
COUNT PULSE 4
Counter 4 count input
11,13
IN5
PRELOAD 1
Counter 1 preload input
12,14
IN6
PRELOAD 2
Counter 2 preload input
15,17
IN7
PRELOAD 3
Counter 3 preload input
16,18
IN8
PRELOAD 4
Counter 4 preload input
21,23
IN9
STROBE 1
Counter 1 strobe input
22,24
IN10
STROBE 2
Counter 2 strobe input
25,27
IN11
STROBE 3
Counter 3 strobe input
26,28
IN12
STROBE 4
Counter 4 strobe input
Chapter 3 Counter Type A
Type A
Pin Description
3-5
3
Configuring the Type A High Speed Counter
The following table summarizes all configuration features and default configuration
values for the Type A counter.
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
Output Failure Mode
Configuration
Parameter
Description
Values
Default
Failure Mde
Output Failure Mode
NORMAL, OFF, HOLD
NORMAL
Osc Divider
OscillatorDivider
1 ... 65535
1000
Count Thrshlds
Count Input Thresholds
NON-TTL, TTL, MAG-PKUP
NON-TTL
ControlThrshlds
Control Input Thresholds
NON-TTL, TTL
NON-TTL
Count Filtr
Count Input Filter
HIFREQ, LOWFREQ
HIFREQ
Preld Filtr
Preload Input Filter
HIFREQ, LOWFREQ
HIFREQ
Preset CTR#
Preset Accumulator
CTR1 ... CTR4
Preset #
Preset ON
Preset ON setpoint
Low Limit ... High Limit
32767
Preset OFF
Preset OFF setpoint
Low Limit ... High Limit
0
ON Interrupt
Preset on transition interrupt
DISABLED,ENABLED
DISABLED
OFF Interrupt
Preset off transition interrupt
DISABLED,ENABLED
DISABLED
Hi Limit
High Count Limit
–32768 ... 32767
32767
Lo Limit
Low Count Limit
–32768 ... 32767
0
Count Mode
Count Mode
CONTINU, SINGSHOT
CONTINU
Count Dir
Count Direction
UP, DOWN
UP
Timebase (ms)
Timebase
1 ... 65535 ms
1000 ms
Preld Value
Preload Value
Low Limit ... High Limit
0
Strobe Mode
Strobe Mode
LAST, FIRST
LAST
Strobe Edge
Strobe Edge
POS, NEG
POS
Strobe Efct
Strobe Effect
STRB/PRELOAD, STRB ONLY
STRB ONLY
When the CPU is stopped or lost, counter operation continues normally; however, the
operation of the Preset outputs can be configured until the CPU returns or power is
cycled. In all modes, the Accumulators are updated and the Strobes and Preloads are
processed normally.
H
In Normal mode (NORMAL), the outputs continue to operate as if the CPU were
present. Outputs will change state to reflect the counter Accumulators.
H
In Force Off mode (OFF), all preset outputs are turned off and remain off until the
CPU returns.
H
In Holdlast mode (HOLD), the preset outputs retain current levels and do not reflect
the counter Accumulators.
If the CPU returns to operation or the module is power-cycled, the outputs will
immediately begin reflecting the counter Accumulators again.
3-6
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
3
Oscillator Divider
The oscillator divider is used to generate a 5V oscillator output. The output frequency is
1 million divided by the oscillator divider; the formula is shown below.
Oscillator Frequency (Hz) = 1,000,000 / oscillator divider
The output frequency ranges from approximately 15 Hz (oscillator divider of 65535) to 1
MHz (oscillator divider of 1).
Input Thresholds
All inputs can be used as differential or single-ended inputs. The following table
specifies the input thresholds for single-ended and differential use based on threshold
selection and input type. The configuration parameters will set input thresholds
according to the following table:
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
Configuration Parameter
Inputs Controlled
Input Definitions
Count 1, 2 Threshold
IN1, IN2
Count Pulse 1, 2
Count 3, 4 Threshold
IN3, IN4
Count Pulse 3, 4
Control 1, 2 Threshold
IN5, IN6, IN9, IN10
Preload and Strobe 1, 2
Control 3, 4 Threshold
IN7, IN8, IN11, IN12
Preload and Strobe 3, 4
Note that all the inputs controlled will have the same voltage threshold.
The voltage thresholds which can be selected for each input are described in the
following table.
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
Input Type
Single-Ended
Differential
Non-TTL
TTL
Mag-Pickup
Non-TTL
TTL
Mag-Pickup
Counter 1, 2 Threshold
8V
1.4 V
0.1 V
4.8 V
0.8 V
0.1 V
Counter 3, 4 Threshold
8V
1.4 V
0.1V
4.8 V
0.8 V
0.1V
Control 1, 2 Threshold
8V
1.4 V
X
4.8 V
0.8 V
X
Control 3, 4 Threshold
8V
1.4 V
X
4.8 V
0.8 V
X
Input Filters
All inputs default to using a 2.5 microsecond high-frequency filter. Each Count Pulse and
Preload input can be configured to use a 12.5 millisecond low-frequency filter instead.
The low-frequency filter reduces the effects of signal noise. The Strobe inputs always
use the high-frequency filter.
Preset Accumulator
The Preset Accumulator field determines which counter a preset output will reflect.
Each of the four preset outputs can be assigned to any of the accumulators. The Preset
ON and Preset OFF values must be within the range of the High and Low Limits of the
counter the Preset Accumulator is assigned to. The default for each Preset is to reflect
the counter of the same number. Thus Preset 1 points to counter 1, Preset 2 points to
counter 2, etc.
GFK-1062A
Chapter 3 Counter Type A
3-7
3
Output Preset ON and OFF Positions
Each preset output has a preset ON and OFF position. The output state reflects the
counter accumulator value in relation to the ON and OFF points.
Preset closest to low limit
Output ON
Output OFF
ON
> = ON Preset
< = OFF Preset
> OFF Preset
< ON Preset
OFF
< OFF Preset
> ON Preset
< = ON Preset
> = OFF Preset
The output may be either on or off when the accumulator value lies between the Preset
points.
OFF
PRESET
ON
PRESET
a42970
ON CONDITION INCLUDES PRESET POINTS
OFF
PRESET
ON
PRESET
OFF CONDITION INCLUDES PRESET POINTS
Location of Preset Points
The Preset points may be located anywhere within the counter range. When the
accumulator value is between the Preset points, the output ON/OFF state will always be
that of the lowest (most negative) Preset point. When the accumulator value is not
between the Preset points, the output ON/OFF state will be that of the most positive
preset. This is true regardless of the counter direction.
The following example compares the output state and accumulator value of a 16-bit
counter when the OFF Preset value is closer to the Low Limit than the ON Preset value,
OUTPUT
COUNTER RANGE
ON
OFF
8000H
COUNTER
MINIMUM
LOW
LOW LIMIT
LIMIT
3-8
t
OFF
PRESET
ACCUMULATOR
VALUE
ON
COUNTER
PRESET
HIGH
LIMIT
Series 90 -70 High Speed Counter User’s Manual – November 1995
7FFFH
MAXIMUM
HIGH LIMIT
GFK-1062A
3
Preset Interrupt Enables
Each preset can generate an interrupt to the CPU. If the Interrupt ON selection is
enabled, then an ON transition of the preset output will generate an interrupt to the
CPU. Similarly, if the Interrupt OFF selection is enabled, an OFF transition of the preset
output will generate an interrupt to the CPU. Thus no edge, either edge, or both edges
of a preset output transition can generate an interrupt. The default is for all interrupts to
be disabled.
Count Limits
Each counter is assigned upper and lower count limits. The upper (high) limit must be
the most positive, and the lower limit must be the most negative. Both limits can be
positive or negative, but the high limit must always be greater than the low limit. A
counter ’s Accumulator, Preload value, and any Preset outputs assigned to the counter
must lie within the high and low limits.
If the Accumulator value is outside the new limits when the limits are changed, it is
automatically adjusted to the low limit value. If the new limits are incompatible, that is,
(high < low or low > high), then they will be rejected and the old limits retained. In
addition, a counter limit error code will be returned. To avoid this situation when the
limits are changed one at a time, a good rule to follow is: always move the high limit first
when shifting the limits up and always move the low limit first when shifting them
down.
As a 16-bit counter, the limit range is –32,768 to 32,767.
Count Mode
A counter can be configured to count continuously within the count limits, or to count to
a limit and stop.
Continuous Counting
In the continuous counting mode, if either the upper or lower limit is exceeded, the
counter wraps around to the other limit and continues counting. Continuous counting is
the default mode.
Single-Shot Counting
If single-shot is selected, the counter will count to its upper or lower limit, then stop.
When the counter is at the limit, the direction can be reversed and the counter will back
away from the limit. The Accumulator can also be changed by loading a new value from
the CPU or by applying a Preload Input.
Count Direction
Each of the four counters in the Type A configuration has only one Count Pulse input.
The counter can be configured to increment or decrement its Accumulator on the rising
edge of a Count Pulse input transition. The default is to count up.
Counter Timebase
For each counter, the Timebase represents a span of time which can be used to measure
the rate of counting. For example, a program required to monitor the number of count
pulses which occur every 30 seconds could use a Timebase of 30,000.
GFK-1062A
Chapter 3 Counter Type A
3-9
3
A timebase from 1 millisecond to 65535 milliseconds can be selected for each counter.
The counter timebase is set to 1 second (1000 milliseconds) by default. The module
stores the number of counts that occurred during the last-completed timebase interval in
the Counts per Timebase register.
The timebase counter updates once each timebase period. After power-up, or any
disruption in counting, allow at least one timebase period for the counter to stabilize.
Preload Value
For each counter, a starting, or Preload, value can be specified which will be used when
the Preload input is activated. This Preload value is used for both hardware and
software preloads. If the counter should be reset to zero, enter 0 as the Preload value;
this is the default value. The Preload value range is –32,768 to +32,767, but it must be
within the counter limits.
Strobe Mode
The Strobe Mode determines which Strobe input pulse the Strobe register will report. In
Last mode, the Strobe register is always updated with the Accumulator value when the
configured Strobe input transition occurs. Thus two rapid Strobe pulses could result in
the first Strobe register value being missed. In First mode, the Strobe register is updated
only if the Strobe flag set by a previous Strobe pulse has been acknowledged by setting
the corresponding Reset Strobe %Q bit. In this mode, any subsequent Strobe pulses will
be ignored and lost, but the first will always be retained. The default mode is Last.
Strobe Edge
Strobe inputs are edge sensitive. Each Strobe input on the module can be individually
configured to have either the positive or the negative edge active. By default, they are
positive-edge sensitive.
Strobe Effect
In the default mode, Strobe Only, a Strobe pulse only causes the Accumulator value to be
copied into the Strobe register and the Strobe flag is set. In Strobe then Preload mode, a
Strobe pulse will, in addition to copying the Accumulator into the Strobe Register,
simultaneously perform a preload and set the Accumulator to the Preload value.
The Strobe then Preload mode should be used instead of tying the Strobe and Preload
inputs together if every Strobe Pulse is to generate a Preload. When a Preload pulse
occurs on the inputs at the same time as a Strobe pulse, or if the inputs are tied together,
the Preload has precedence. The Accumulator will be set to the Preload value and then
the Strobe register will be set to the Accumulator. Thus the Strobe register will obtain a
copy of the Preload value.
3-10
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
3
Data Transfer Between High Speed Counter and CPU
The Series 90-70 High Speed Counter updates the %I and %AI data every 0.5
milliseconds. The Series 90-70 CPU reads this data immediately preceding every pass
through the ladder logic, before triggering a ladder interrupt, and when a DOIO
specifically requesting this data is performed in the ladder logic. To support the unique
data coherency requirements of the High Speed Counter, the CPU reads both the %I and
%AI data when performing DOIOs requesting only %I data.
The format of this input data depends on the counter configuration type. In return,
during each I/O scan, the CPU sends 32 bits (%Q) of control data and 6 words (%AQ) of
output data commands to the module. COMMREQ function blocks in the user program
can also be used to send additional data commands to the module.
See Appendix A for more information about the COMMREQ and DOIO functions.
%I and %AI Data Sent by a Module Configured as Type A
The 32 status bits (%I) represent:
H
H
H
H
H
Strobe status flag
D
Interrupt status
Preload status flag
Preset Output status
Module ready status
Error status
These status bits are sent to the CPU as inputs, and can influence outputs sent from the
CPU to the module.
The 16 register data words (%AI) represent:
H
H
H
H
GFK-1062A
Module Status Codes
Counts per Timebase value
Accumulators
Strobe Registers
Chapter 3 Counter Type A
3-11
3
Status Bits (%I)
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
strobe 1 status
strobe 2 status
strobe 3 status
strobe 4 status
preload 1 status
preload 2 status
preload 3 status
preload 4 status
output 1 status
output 2 status
output 3 status
output 4 status
module ready
reserved
error
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
reserved
reserved
preset 1 interrupt status
preset 2 interrupt status
preset 3 interrupt status
preset 4 interrupt status
reserved
Strobe Status
Each bit indicates when a Strobe Pulse occurs on the counter. If an application program
uses this bit, it should be cleared by setting the corresponding Reset Strobe %Q bit. In
First Strobe mode, additional strobes will be ignored until the Reset Strobe %Q bit is set.
Preload Status
Each bit indicates a rising edge of the Preload input on the counter. If an application
program uses this bit, it should be cleared by setting the corresponding Reset Preload
%Q bit.
Output Status
These bits indicate the ON or OFF state of the four preset outputs.
Module Ready
This bit is set after the module completes its power-up tests.
3-12
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
3
Error Status
This bit is set when an error occurs. If it is set, a module status code has been returned in
the first %AI location and the board OK LED flashes at 4 Hz. The Error Status bit is
cleared by setting the Clear Error %Q bit.
Preset Interrupt Status
These bits are set by the High Speed Counter when the corresponding preset output has
changed state and generated an interrupt. These flags can be used by an interrupt
routine to determine which outputs have generated interrupts. The Output Status bits
can be used in conjunction with the Preset Interrupt Status bits to determine which
transition caused the interrupt. The Preset Interrupt Status bits should only be tested in
a ladder logic interrupt handler.
%AI Data
Word
01
02
03
04
05
06
07
Description
Word
Module Status code
Counts per timebase for counter 1
Counts per timebase for counter 2
Counts per timebase for counter 3
Counts per timebase for counter 4
Accumulator for counter 1
Strobe register for counter 1
08
09
10
11
12
13
14 - 16
Description
Accumulator for counter 2
Strobe register for counter 2
Accumulator for counter 3
Strobe register for counter 3
Accumulator for counter 4
Strobe register for counter 4
Not used (set to 0)
Module Status Codes
The Module Status Code in the %AI Input Data contains the error code returned to the
PLC. The HSC sets this code to indicate a data command or configuration error. Once
an error code has been returned, no more errors will be generated until the error is
cleared. To clear a module status code, eliminate the condition that caused the error, and
toggle the Clear Error %Q bit.
Note that fatal errors (RAM, EPROM) have no codes associated with them because these
errors cause the watchdog timer to time out and the board to go into constant reset.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
The error code format and a list of error codes are given below.
High Byte
Error Source
GFK-1062A
Chapter 3 Counter Type A
Counter or Preset #
Low Byte
Error Code
3-13
3
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
Error Codes for Type A
Error Code
Error Type
00
No Error
Definition
No Error Present
11
Unknown Command
21
Invalid Counter or Preset
31
Invalid COMMREQ Task ID
41
Command
81
Errors
Velocity Increment Out of Range
Accumulator Out of Range
91
Preload Value Out of Range
C1
Preset ON Out of Range
D1
Preset Off Out of Range
12
High Limit < Low Limit
22
Limit
Range Excludes Preload
52
Errors
Range Excludes Preset ON
62
Range Excludes Preset OFF
18
High Limit < Low Limit
28
Range Excludes Preload
58
Range Excludes Preset ON
68
Configuration
Range Excludes Preset OFF
A8
Errors
Unsupported Feature Error
B8
Unknown Counter Type
C8
PLC Version Error
D8
Logicmaster 90 Version Error
Configuration Errors are not returned in %AI data since the module does not configure,
but the error code is returned in the IO Fault data.
Counter or Preset Number
For a valid command (recognized value in byte 0), the counter or preset number, from 1
to 4, which generated the error will be reported in this nibble. A preset number only
appears in error codes C1 and D1.
Error Source
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
Command and Limit errors return the source of the error.
Value
Example:
Error Source
1
%AQ Command 1 (%AQ Offset 0-2)
2
%AQ Command 2 (%AQ Offset 3-5)
4
COMMREQ Function
If the hexadecimal data 0002 0000 0107 (set Counter 1 Velocity Increment +131,072) was
placed into the %AQ offsets 3 through 5, the error 2141h would be reported, since the
maximum Velocity Increment is 100,000. The Module Status Code represents:
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
Value
2
Error in %AQ Command 2
1
Error generated by counter 1
41
3-14
t
Representation
Velocity Increment Out of Range
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
3
%Q and %AQ Data Sent from CPU to HSC Configured as Type A
Once each I/O scan, the CPU sends 8 words of data (32 bits of %Q and 6 words of %AQ)
to the High Speed Counter Module. The application program can use these outputs to
control the module.
The 32 output bits (%Q) represent:
H
H
H
H
H
Reset Strobe flag
Reset Preload flag
Clear error flag
Output enable
Preload Accumulator
Six Words (%AQ) of Command Data
The 6 words of command data, which can also be sent using a COMMREQ Function
Block, can perform the following operations:
H
H
H
H
H
H
H
H
H
Load Accumulator
Load count limits
Load Accumulator increment
Load output preset ON and OFF values
Load Preload value
Load time base
Load Oscillator divider
Set Count Direction
Enable/Disableinterrupts
All of this data is transferred from the High Speed Counter to the CPU once per I/O
scan. The I/O scan is active while the CPU is in the RUN mode or STOP ENABLED
mode.
GFK-1062A
Chapter 3 Counter Type A
3-15
3
%Q Data
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
reset strobe 1
reset strobe 2
reset strobe 3
reset strobe 4
reset preload 1
reset preload 2
reset preload 3
reset preload 4
enable output 1
enable output 2
enable output 3
enable output 4
reserved
reserved
reserved
clear error
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
preload accumulator 1
preload accumulator 2
preload accumulator 3
preload accumulator 4
reserved
reserved
reserved
Reset Strobe
Setting this bit clears the corresponding Strobe Status %I bit. In First Strobe mode,
subsequent strobe pulses are ignored until this bit is used to clear the Strobe Status bit.
Reset Preload
This bit is used to clear the corresponding Preload Status %I bit. For example, if a
Preload occurred for counter 3, the Preload 3 Status %I bit would be set. To clear this bit
so future Preloads can be detected, the Reset Preload 3 %Q bit must transition ON.
Enable Output
These bits enable the corresponding preset output. If cleared, the output will always be
OFF and not reflect the accumulator’s value in relation to the Preset ON and OFF values.
3-16
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
3
Clear Error
This bit should be set by the CPU to clear the Error Status %I bit after the error has been
acknowledged. This bit is rising edge active, so new errors may appear while set.
Preload Accumulator
These bits tell the counter to perform a software preload and set the corresponding
Accumulator to the Preload value. They do NOT, however, cause the corresponding
Preload Status bit to be set.
GFK-1062A
Chapter 3 Counter Type A
3-17
3
Data Commands for Counter Type A
At the end of every CPU sweep, six words of %AQ data are automatically transferred
from the CPU to the High Speed Counter. These six words are used to send data
commands from the PLC to the HSC. The first three words, offsets 0 through 2, make up
%AQ command 1, and the second three words, offsets 3 through 5, make up a
completely separate %AQ command 2. Thus two commands can be sent to the HSC at
the end of each sweep. Note that %AQ command 1 is executed first, so that if identical
commands with different values are sent to the HSC simultaneously, %AQ command 2
data will overwrite %AQ command 1 data.
Even though the %AQ data is sent each sweep, commands are acted on ONLY if the
command has changed since the last sweep. When any of the 6 bytes in a command
changes, the HSC will accept the data as a new command and respond accordingly.
The DOIO function is supported, so that data can be transferred between the CPU and
HSC mid-sweep. Note that to ensure that the High Speed Counter has time to process
DOIO data sent to it, the application should not change the data more frequently than
every 0.5 millisecond. Because data sent to the HSC is updated at the end of the CPU
sweep, half a millisecond should elapse between the beginning of the sweep and a
DOIO function block, between two DOIO function blocks, and between a DOIO
function block and the end of the sweep.
The COMMREQ function block can also be used to send data commands to the HSC
mid-sweep. COMMREQs must be separated only from each other, and by at least 0.5
milliseconds. A description and example of the use of COMMREQs and DOIOs is given in
Appendix A.
%Q data is processed by the HSC before the %AQ data. Therefore commands that can be
affected by %Q bit operations should be sent at least one sweep before the %Q bit
operation. For example, the Load Preload Value command should be sent one sweep before
setting the Preload Accumulator %Q bit to preload that value.
The High Speed Counter will check each command that is sent for validity. If the
command syntax is incorrect, the counter will ignore the command and respond by
flashing the Board Okay LED at 4 Hz, setting the Error Status %I bit, and returning a
status code describing the error in the Module Status %AI word. The Error can be
cleared by toggling the Clear Error %Q bit.
In describing data commands, word offsets are shown in reverse order and in
hexadecimal to simplify data entry. The following example sends a Load Accumulator
Counts command with value 0001 to counter 2 using offsets 0 through 2.
The first word, or command word, which goes into word offset 0 would be 0201h. The
value 01 in byte 0 represents the command Load Accumulator Value. The value 02 in
byte 1 is the counter number, in this case counter 2. For the Load Accumulator Value
command, word 1 is the sixteen bit value to be loaded into the accumulator and word 2
is ignored.
In this example, word 1 would have the value 0001h because that is the value to be
placed in the accumulator. Word 2 will be ignored and can be anything, but it is usually
best to use the value 0. If word offset 0 corresponded to %AQ1, the complete command
to load the counter 2 accumulator with value 0001 would be:
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
3-18
%AQ3 (word 2)
%AQ2 (word 1)
%AQ1 (word 0)
0000
0001
0201
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
3
The following table is a list of data commands for counter Type A.
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
Data
Command Definition
Word 2
Byte 5
Byte 4
Word 1
Byte 3
Byte 2
Null
xx
xx
xx
xx
Load Accumulator Value
xx
xx
Load High Limit
xx
xx
Load Low Limit
xx
xx
Load Accumulator Increment
xx
xx
xx
data (8)
Set Counter Direction
xx
xx
xx
data (8)
Load Timebase
xx
xx
Load Velocity
xx
Load Preset ON Value
xx
xx
Enable/Disable Preset ON Interrupt
xx
xx
Load Preset OFF Value
xx
xx
Enable/Disable Preset OFF Interrupt
xx
xx
Load Preload Value
xx
xx
Load Oscillator Divider
xx
xx
Command Word
Word 0
Byte 1
Byte 0
xx
00h
data (16)
n
01h
data (16)
n
02h
data (16)
n
03h
n
04h
n
05h
n
06h
n
07h
m
0Bh
m
0Fh
m
15h
data (16)
data (24)
data (16)
xx
data (8)
data (16)
xx
data (8)
m
19h
data (16)
n
1Fh
data (16)
0
32h
m = Preset Number (1 to 4); n = Counter Number (1 to 4);
xx = Do not care (ignored); data (8, 16, 24) = 8, 16, or 24 bit data
Descriptions of each command are given below. The valid range of values is given in
parenthesis.
Null
This is the default %AQ data command. Since the %AQ data is transferred each PLC
sweep, it is a good idea to have the Null command present when not executing a specific
data command to avoid inadvertent execution. All data is ignored with a Null command.
Load AccumulatorValue (Low Limit to High Limit)
This command places a 16-bit value into a counter accumulator. The value must be
within the Count Limits, or an error will be returned and the command ignored.
Load High Limit (–32768 to 32767)
This command sets the highest value to which a counter will count. Counts that would
cause the counter to go higher are ignored or cause the accumulator to roll over to the
Low Limit depending on whether the counter is configured for Single-shot or
Continuous count mode. The High Limit can be any 16-bit value with the following
restrictions: it must be greater than the Low Limit, the counter’s Preload value must lie
between it and the Low Limit, and all preset outputs which are assigned to the counter
must have preset ON and OFF values which lie between it and the Low Limit.
If a restriction is not met, an error will be generated and the command ignored. If the
range between the Low Limit and the new High Limit excludes the Accumulator, the
Accumulator will be set to the Low Limit and no error is generated.
GFK-1062A
Chapter 3 Counter Type A
3-19
3
Load Low Limit (–32768 to 32767)
This command sets the lowest value to which a counter will count. Counts that would
cause the counter to go lower are ignored or cause the accumulator to roll over to the
High Limit depending on whether the counter is configured for Single-shot or
Continuous count mode. The Low Limit can be any 16-bit value with the following
restrictions: it must be less than the High Limit, the counter’s Preload value must lie
between it and the High Limit, and all preset outputs which are assigned to the counter
must have preset ON and OFF values which lie between it and the High Limit.
If a restriction is not met, an error will be generated and the command ignored. If the
range between the new Low Limit and the High Limit excludes the Accumulator, the
Accumulator will be set to the Low Limit and no error is generated.
Load Accumulator Increment (–128 to 127 counts)
The Accumulator Increment performs a one-shot adjustment to the accumulator. Only
byte 2 is used for data, all other data bytes are ignored. The one-shot increment may be
performed at any time, even when counting at maximum rate. If the offset cause the
counter to exceed its limits, the excess is treated just like any other overflow, i.e., in
Continuous mode the Accumulator rolls over to the other limit and in Single-shot mode
the Accumulator does not pass the limit.
Set Counter Direction (0=up, 1=down)
This command determines whether a counter’s accumulator increments or decrements
when there is a rising edge on its Count Pulse input. The direction may be set at any
time.
Load Timebase (1 to 65535 milliseconds)
This command sets the timebase. The timebase is the number of milliseconds for which
the counter counts input pulses and then returns in the Counts per Timebase register. If
the timebase is 1000, or 1 second, the Counts per Timebase register returns the number
of counts detected in each 1 second period. Any non-zero 16-bit value may be used as
the timebase.
Load Velocity (–100,000 to 100,000 counts per second)
A velocity increment is an internal count generator, or a continuous accumulator
increment. Each millisecond, 0.1% of the increment value is added to the accumulator.
A value of 0 will stop the velocity increment. Counts from the velocity increment are
cumulative with counts coming in from the Count Pulse input. Note that counts
generated by the velocity increment are not reflected in the Counts per Timebase
register.
Load ON and OFF Preset Value (Count Limits of the assigned counter)
This command sets the preset output turn on and turn off points within a counters
range. Preset values can be any value between the high and low limits, inclusive.
Enable/Disable Preset ON and OFF Interrupts (0= Disable, 1= Enable)
This command enables or disables interrupts resulting from Preset output transitions.
For example, if Preset ON interrupts are enabled, then a low to high transition of the
3-20
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
3
Preset ON output will generate an interrupt to the CPU. This command allows the
interrupts to be enabled or disabled within a ladder.
Load Preload Value (Low Limit to High Limit)
The Load Preload command sets the value to which the Accumulator will be set when a
positive edge occurs on the Preload input. The value must be between the High and
Low Limits inclusive, or an error will be returned and the command ignored.
Load Oscillator Divider (1 to 65535)
This command changes the frequency of the square wave oscillator signal. The
frequency generated is 1 megahertz (1 MHz) divided by the oscillator divider. Thus to
get 50 Hz, the oscillator divider should be 20000.
GFK-1062A
Chapter 3 Counter Type A
3-21
Chapter
4 Counter Type B
section level 1
figure bi level 1
table_big level 1
4
Counter Type B is described in this chapter. The counter description includes counter
operation, configuration of the counter, and the interface between the counter and the CPU.
Contents and Operation of a Type B Counter
Overview
The Type B counter contains two 32-bit bidirectional counters. Each counter is controlled
by 6 of the 12 single ended or differential voltage inputs: Count A, Count B, Strobe 1,
Strobe 2, Disable, and Preload. Each counter may be independently configured to count
in one of three modes: Up and Down, Pulse with Direction, and A Quad B. Counter
Type B elements are shown in the figure below. Each counter has the following:
H
a 32-bit Accumulator register which counts the pulses from the Count A and Count B
inputs
H
a Disable input which can make the Accumulator ignore the count pulses when
asserted.
H
two Strobe registers which store the Accumulator value when a Strobe input
transitions
H
H
a preload value which is inserted into the accumulator when a preload occurs
a counts per timebase register which indicates the count rate of the input pulses.
Each of the four 5 to 30 V preset outputs can be independently assigned to either of the
counters, and can be used to generate PLC interrupts.
a47058
UP OR DOWN COUNTER (32-BIT)
PRELOAD
PRELOAD VALUE
(32-BIT)
PRESET
OUTPUT
A INPUT
B INPUT
#1
ACCUMULATOR
(32-BIT)
DISABLE
#2
COUNTS PER
TIME BASE
(16-BIT)
GFK-1062A
STROBE 1
STROBE REGISTER 1
(32-BIT)
STROBE 2
STROBE REGISTER 2
(32-BIT)
ACCUMULATOR
ADJUST
(8-BIT)
#3
#4
4-1
4
Count A and B Inputs and Accumulator
The 32-bit Accumulator is incremented or decremented based on a configured
interpretation of its two count inputs. The interpretation can be set to Up/Down,
Pulse/Direction, or A Quad B. Each is described below.
Operating in UP/DOWN Mode
Up-counting occurs on the low-to-high transition of the Up input. Down counting
occurs on the low-to-high transition of the Down input. The accumulator automatically
tracks the difference between the number of counts received by the Up channel and the
Down channel. Simultaneous inputs on the up channel and down channel will cause a
net accumulator change of zero.
a42973
IN-A UP
IN-B DOWN
COUNT
COUNT UP
ACC
VALUE
COUNT DOWN
N +2
N +1
N
Operating in Pulse/Direction Mode
Counting always occurs on the low-to-high transition of the Pulse input. Count
direction is up for a low level on the Direction input and down for a high level on the
Direction input. Avoid changing the Direction signal coincidentally with the rising edge
of the Pulse input.
a42975
IN-A PULSE
IN-B DIRECTION
COUNT
COUNT UP
COUNT DOWN
ACC N +2
VALUE N +1
N
Operating in A Quad B Mode
In A Quad B mode, there are four counts for each A Quad B cycle. A count occurs for
each transition of either A or B. The counts will be evenly spaced with respect to the
input waveforms when the phase relationship between A and B is shifted by 1/4 cycle.
4-2
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
4
The phase relationship between A and B determines count direction, as shown in the
following timing diagrams.
The count direction is up if A leads B.
a42977
A
B
COUNT
N+6
ACC
VALUE N
The count direction is down if A lags B.
a42978
A
B
COUNT
ACC
VALUE
N
N –6
The Accumulator is bounded by configurable High and Low Limits. The interaction
between the Accumulator and the limits depends on the configured count mode. In
Continuous mode, the Accumulator will increment or decrement to the current High or
Low Limit, roll over to the other limit, and continue counting. In Single Shot mode, the
Accumulator will count to the current High or Low Limit and stop. If the counter
direction is changed, the Accumulator will count away from the limit until it reaches the
other limit.
The High and Low Limits can be changed to any valid 32-bit value at any time using a
data command from the PLC. To be a valid 32-bit value, the following conditions must
be met:
H
H
H
the High Limit must be greater than the Low Limit
the Preload value must be within the High and Low Limit bounds
any presets assigned to the counter must have ON and OFF values within the High
and Low Limit bounds.
If the limits are changed so the Accumulator is outside the limit boundaries, the
Accumulator is set to the Low Limit.
The Accumulator may be set to any 32-bit value within the bounds of the High and Low
limits at any time using a data command. Another data command allows the
Accumulator to be adjusted by a byte increment value, from –128 to +127 counts.
Finally, a velocity can be commanded which causes the Accumulator to increment or
decrement at a fixed rate.
GFK-1062A
Chapter 4 Counter Type B
4-3
4
Strobe Inputs and Register
Each Strobe input is an edge sensitive input which can be configured to respond to
either a positive edge or a negative edge. When the configured Strobe input transition
occurs (referred to as a Strobe Pulse) the value in the Accumulator is stored in the
corresponding Strobe register and a strobe flag is set and returned in %I data to indicate
the event to the CPU. The application program in the CPU acknowledges receipt of the
strobe by toggling the corresponding Strobe Status %Q bit.
Two strobe modes are available to select which Strobe value is most important. In Last
Strobe mode, the default, a Strobe Pulse will always update the Strobe register with
the latest Accumulator value regardless of the Strobe Status flag. In First Strobe mode,
the first Strobe is captured and all subsequent Strobe input transitions are ignored until
the strobe flag is cleared by toggling the corresponding Reset Strobe %Q bits.
Strobe Linkage
Normal strobe operation is achieved by setting the Strobe Linkage parameter to
Independent. In Independent Mode, Strobes 1.1 and 1.2 strobe the Accumulator 1 value
when a Strobe Pulse occurs, and Strobes 2.1 and 2.2 strobe the Accumulator 2 value
when a Strobe Pulse occurs. Counter Type B has the capability of linking Strobes 1.1 and
2.1 to a change in Accumulator 2 instead of their respective Strobe pulses. In Coupled to
Accumulator 2 mode, any count pulses which change Accumulator 2 will cause Strobe
1.1 to strobe the Accumulator 1 value and Strobe 2.1 to strobe the Accumulator 2 value.
Pulses on Strobes 1.1 and 2.1 while in this mode are ignored. Strobes 1.2 and 2.2 operate
normally.
This feature can be used to accurately measure a pulse rate against a reference pulse, or
to compare two different pulse rates. The reference pulse is connected to Counter 1
inputs and the slower pulse that is to be measured is connected to Counter 2 inputs.
The following illustration represents two pulses. Counter 1 pulses twelve times faster
than Counter 2. Each time Counter 2 pulses, its Strobe Register 1 and Counter 1’s Strobe
Register 1 are loaded with their Accumulator values.
Counter 2
Counter 1
Pulses
Accumulator
→
1
→
2
→
3
→
4
Strobe Register
Strobe Register
Accumulator
Pulses
1
←
D
D
→
12
→
12
1
←
Input terminal connections for Strobe Input 1 for Counter 1 and Strobe input 1 for
Counter 2 are not used with this feature.
4-4
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
4
Preload Input and Value
The Preload input is normally used to perform a reset function for the counter. The
value to which the Accumulator is set when a preload occurs can be configured to any
32-bit value within the range of the high and low limits and has a default value of zero.
The Preload value can also be changed using a data command from the PLC. There are
two types of Preloads, hardware and software.
A hardware preload uses the the Preload input and is positive edge sensitive only. On
the positive transition, the configured preload value is inserted into the accumulator and
a preload flag is set and returned in %I data to indicate the event to the CPU. If an
application program uses this flag indication, it can use the corresponding %Q bit to
clear the preload flag before the next preload occurs. A rising edge on the Preload input
always preloads the Accumulator regardless of the state of the Preload flag.
Note that when a pulse occurs on the Preload inputs at the same time as a Strobe pulse,
or if the inputs are tied together, the Preload has precedence. The Accumulator will be
set to the Preload value and then the Strobe register will be set to the Accumulator. This
means that he Strobe register will have a copy of the Preload value.
A software preload can be performed by setting a Preload Accumulator %Q bit. On the
positive transition of this %Q bit, the current preload value is placed into the
Accumulator. A software preload does NOT set the Preload flag.
Counts per Timebase Register
The Counts per Timebase register is a 16-bit register which contains the number of
counts received on the Count Pulse input in the last completed timebase interval. It is
used to measure the rate of counting. If more counts are received than can be stored in a
16-bit register, the register will overflow. The timebase interval is a configurable value
from 1 to 65535 milliseconds.
Changes to the timebase will not take effect until after the previous timebase and one
new timebase have elapsed. A Preload will interrupt counting and cause the Counts per
Timebase register to be inaccurate for up to two timebase intervals. The timebase is
initially configured as 1 second, but may be changed using the Logicmaster 90-70
Configurator function or a data command.
As an unsigned number, the Counts per Timebase register will correctly indicate from 0
to 65536 positive counts received per timebase. As a signed number, it will properly
indicate from –32768 to 32767 counts per timebase. The timebase should be selected to
not allow more counts in a timebase than the 16-bit register can hold or it will overflow.
GFK-1062A
Chapter 4 Counter Type B
4-5
4
Preset Outputs
The module has four preset outputs, each of which can be assigned to any counter. Each
preset output has a preset ON and preset OFF value, or position, which must be within
the count limits of the counter to which the preset is assigned. The preset ON and OFF
positions determine when the output will be ON or OFF as shown below.
Preset closest to low limit
Output ON
Output OFF
ON
> = ON Preset
< = OFF Preset
> OFF Preset
< ON Preset
OFF
< OFF Preset
> ON Preset
< = ON Preset
> = OFF Preset
The output may be either on or off when the accumulator value lies between the Preset
points.
OFF
PRESET
ON
PRESET
a42970
ON CONDITION INCLUDES PRESET POINTS
OFF
PRESET
ON
PRESET
OFF CONDITION INCLUDES PRESET POINTS
For example:
COUNTS
OFF PRESET
VALUE
ON PRESET
VALUE
ON
CORRESPONDING
OUTPUT
OFF
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎÎÎÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ACCUMULATOR
VALUE
a43003
TIME
Separation of Preset Points
The count accumulators are compared to the Presets at 0.5 msec intervals. Therefore, to
guarantee that the outputs will always switch, the Preset points must be separated by at
least the number of counts received in a 0.5 msec time period. For example:
If maximum count rate = 10kHz;
then minimum count separation = (10,000 Hz x .0005 sec) = 5 counts.
4-6
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
4
Preset Interrupts
Interrupts can be enabled or disabled for each preset output’s ON and OFF transition.
At the same time a preset output changes state, the CPU is interrupted. %I and %AI
data is transferred so that the interrupt routine will see the most current data from the
High Speed Counter. Simultaneous preset changes generate only one interrupt to the
CPU, so the updated %I data must be used by an interrupt routine to determine which
presets changed state and which edge(s) generated the interrupt. Once configured,
interrupts can be independently enabled or disabled using data commands. See
Appendix B for information on using the interrupt capability.
Output Failure Mode
When the CPU is stopped or lost, counter operation continues normally without
interfacing to the CPU. Preset output operation during this stopped state can be
configured for one of three modes. In Normal mode, the outputs continue to operate as
if the CPU were present. Outputs will change state to reflect the counter Accumulators.
In Force Off mode, all preset outputs are turned off and remain off until the CPU
returns. In Holdlast mode, the preset outputs retain current levels and do not reflect the
counter Accumulators. If the CPU returns to operation, the outputs will immediately
begin reflecting the counter Accumulators.
Oscillator Output
The High Speed Counter module generates a 5V square wave oscillator signal. The
oscillator output frequency is determined by the current oscillator divider (set in
configuration or by data command) as indicated below:
Oscillator Frequency (Hz) = 1,000,000 / oscillator divider
The output frequency ranges from approximately 15 Hz (oscillator divider of 65535) to 1
MHz (oscillator divider of 1).
Table 4-1. Type B Specific Terminal Strip Assignments
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
Á
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
GFK-1062A
Pin
Signal
Name
Type B
Pin Name
1,3
IN1
COUNT INPUT 1A
Counter 1 count A input
2,4
IN2
COUNT INPUT 1B
Counter 1 count B input
5,7
IN3
COUNT INPUT 2A
Counter 2 count A input
6,8
IN4
COUNT INPUT 2B
Counter 2 count B input
11,13
IN5
PRELOAD1
Counter 1 preload input
12,14
IN6
DISABLE 1
Counter 1 disable input
15,17
IN7
PRELOAD2
Counter 2 preload input
16,18
IN8
DISABLE 2
Counter 2 disable input
21,23
IN9
STROBE 1.1
Counter 1 strobe 1 input
22,24
IN10
STROBE 1.2
Counter 1 strobe 2 input
25,27
IN11
STROBE 2.1
Counter 2 strobe 1 input
26,28
IN12
STROBE 2.2
Counter 2 strobe 2 input
Chapter 4 Counter Type B
Type B
Pin Description
4-7
4
Configuring the Type B High Speed Counter
The following table summarizes all configuration features and default configuration
values for the Type B counter.
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
Configuration
Parameter
Description
Values
Default
Failure Mde
Output Failure Mode
NORMAL, OFF, HOLD
NORMAL
Osc Divider
OscillatorDivider
1 ... 65535
1000
Count Thrshlds
Count Input Thresholds
NON-TTL, TTL, MAG-PKUP
NON-TTL
ControlThrshlds
Control Input Thresholds
NON-TTL, TTL
NON-TTL
Count Filtr
Count Input Filter
HIFREQ, LOWFREQ
HIFREQ
Preld Filtr
Preload Input Filter
HIFREQ, LOWFREQ
HIFREQ
Disbl Filtr
Disable Input Filter
HIFREQ, LOWFREQ
HIFREQ
Preset CTR#
Preset Accumulator
CTR1 ... CTR4
Preset #
On
Preset ON setpoint
Low Limit ... High Limit
8,388,607
Off
Preset OFF setpoint
Low Limit ... High Limit
0
ON Interrupt
Preset on transition interrupt
DISABLED,ENABLED
DISABLED
OFF Interrupt
Preset off transition interrupt
DISABLED,ENABLED
DISABLED
Hi Limit
High Count Limit
–2,147,483,648 ... 2,147,483,647
8,388,607
Lo Limit
Low Count Limit
–2,147,483,648 ... 2,147,483,647
0
Count Mode
Count Mode
CONTINU, SINGSHOT
CONTINU
Count Sig
Count Signals
PULSE/DIR,UP, DOWN, A QUAD B PULSE/DIR
Timebase (ms)
Timebase
1 ... 65535 ms
1000 ms
Preld Value
Preload Value
Low Limit ... High Limit
0
Strobe Mode
Strobe Mode
LAST, FIRST
LAST
Strobe 1 Edge
Strobe 1 Edge
POS, NEG
POS
Strobe 2 Edge
Strobe 2 Edge
POS, NEG
POS
Strb Lnk
Strobe Linkage
IND, ACC2
IND
Output Failure Mode
When the CPU is stopped or lost, counter operation continues normally; however, the
operation of the Preset outputs can be configured until the CPU returns or power is
cycled. In all modes, the Accumulators are updated and the Strobes and Preloads are
processed normally.
H
In Normal mode (NORMAL), the outputs continue to operate as if the CPU were
present. Outputs will change state to reflect the counter Accumulators.
H
In Force Off mode (OFF), all preset outputs are turned off and remain off until the
CPU returns.
H
In Holdlast mode (HOLD), the preset outputs retain current levels and do not reflect
the counter Accumulators.
If the CPU returns to operation or the module is power-cycled, the outputs will
immediately begin reflecting the counter Accumulators again.
4-8
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
4
Oscillator Divider
The oscillator divider is used to generate a 5V oscillator output. The output frequency is
1 million divided by the oscillator divider; the formula is shown below.
Oscillator Frequency (Hz) = 1,000,000 / oscillator divider
The output frequency ranges from approximately 15 Hz (oscillator divider of 65535) to 1
MHz (oscillator divider of 1).
Input Thresholds
All inputs can be used as differential or single-ended inputs. The following table
specifies the input thresholds for single-ended and differential use based on threshold
selection and input type. The configuration parameters will set input thresholds
according to the following table:
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
Configuration Parameter
Inputs Controlled
Input Definitions
Counter 1 Threshold
IN1, IN2
Counter 1, Inputs A, B
Counter 2 Threshold
IN3, IN4
Counter 2, Inputs A, B
Control 1 Threshold
IN5, IN6, IN9, IN10
Preload, Disable, Strobe 1.1, 1.2
Control 2 Threshold
IN7, IN8, IN11, IN12
Preload, Disable, Strobe 2.1, 2.2
Note that all the inputs controlled will have the same voltage threshold.
The voltage thresholds which can be selected for each input are described in the
following table.
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
Input Type
Single-Ended
Differential
Non-TTL
TTL
Mag-Pickup
Non-TTL
TTL
Mag-Pickup
Counter 1 Threshold
8V
1.4 V
0.1 V
4.8 V
0.8 V
0.1 V
Counter 2 Threshold
8V
1.4 V
0.1V
4.8 V
0.8 V
0.1V
Control 1 Threshold
8V
1.4 V
X
4.8 V
0.8 V
X
Control 2 Threshold
8V
1.4 V
X
4.8 V
0.8 V
X
Input Filters
All inputs default to using a 2.5 microsecond high-frequency filter. Each Count, Preload,
and Disable input can be configured to use a 12.5 millisecond low-frequency filter
instead. The low-frequency filter reduces the effects of signal noise. The Strobe inputs
always use the high-frequency filter.
Preset Accumulator
The Preset Accumulator field determines which counter a preset output will reflect.
Each of the four preset outputs can be assigned to any of the accumulators. The Preset
ON and Preset OFF values must be within the range of the High and Low Limits of the
counter the Preset Accumulator is assigned to. The default configuration sets Presets 1
and 2 to counter 1, and Presets 3 and 4 to counter 2.
GFK-1062A
Chapter 4 Counter Type B
4-9
4
Output Preset ON and OFF Positions
Each preset output has a preset ON and OFF position. The output state reflects the
counter accumulator value in relation to the ON and OFF points.
Preset closest to low limit
Output ON
Output OFF
ON
> = ON Preset
< = OFF Preset
> OFF Preset
< ON Preset
OFF
< OFF Preset
> ON Preset
< = ON Preset
> = OFF Preset
The output may be either on or off when the accumulator value lies between the Preset
points.
OFF
PRESET
ON
PRESET
a42970
ON CONDITION INCLUDES PRESET POINTS
OFF
PRESET
ON
PRESET
OFF CONDITION INCLUDES PRESET POINTS
Location of Preset Points
The Preset points may be located anywhere within the counter range. When the
accumulator value is between the Preset points, the output ON/OFF state will always be
that of the lowest (most negative) Preset point. When the accumulator value is not
between the Preset points, the output ON/OFF state will be that of the most positive
preset. This is true regardless of the counter direction.
The following diagram illustrates the Preset Output state when the OFF Preset is closer
to the low limit than the ON Preset.
a43717
OUTPUT
COUNTER RANGE
ON
OFF
80000000H
MINIMUM
LOW LIMIT
4-10
t
COUNTER
LOW
LIMIT
OFF
PRESET
ACCUMULATOR
VALUE
ON
COUNTER 7FFFFFFFH
PRESET
MAXIMUM
HIGH
HIGH LIMIT
LIMIT
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
4
Preset Interrupt Enables
Each preset can generate an interrupt to the CPU. If the Interrupt ON selection is
enabled, then an ON transition of the preset output will generate an interrupt to the
CPU. Similarly, if the Interrupt OFF selection is enabled, an OFF transition of the preset
output will generate an interrupt to the CPU. Thus no edge, either edge, or both edges
of a preset output transition can generate an interrupt. The default is for all interrupts to
be disabled.
Count Limits
Each counter is assigned upper and lower count limits. The upper (high) limit must the
most positive, and the lower limit must be the most negative. Both limits can be positive
or negative, but the high limit must always be greater than the low limit. A counter’s
Accumulator, Preload value, and any Preset outputs assigned to the counter must lie
within the high and low limits.
If the Accumulator value is outside the new limits when the limits are changed it is
automatically adjusted to the low limit value. If the new limits are incompatible, that is,
(high < low or low > high), then they will be rejected and the old limits retained. In this
case a counter limit error code will be returned. To avoid this situation when the limits are
changed one at a time, a good rule to follow is: always move the high limit first when
shifting the limits up and always move the low limit first when shifting them down.
As a 32-bit counter, the limit range is –2,147,483,648 to 2,147,483,647.
Count Mode
A counter can be configured to count continuously within the count limits, or to count to
a limit and stop.
Continuous Counting
In the continuous counting mode, if either the upper or lower limit is exceeded, the
counter wraps around to the other limit and continues counting. Continuous counting is
the default mode.
Single-Shot Counting
If single-shot is selected, the counter will count to its upper or lower limit, then stop.
When the counter is at the limit, counts in the opposite direction will count it back off
the limit. The Accumulator can also be changed by loading a new value from the CPU or
by applying a Preset Input.
GFK-1062A
Chapter 4 Counter Type B
4-11
4
Count Signal Mode
Each counter can be configured to interpret its Count inputs in one of three ways:
H
Up/Down mode - rising edges on the A, or up, input increment the Accumulator
while positive transitions on the B, or down, input decrement the Accumulator.
H
Pulse/Direction mode - rising edges on the A, or pulse, input are counted. If the B, or
direction, input is low then the Accumulator is incremented but if the Second input
is high then the Accumulator is decremented.
H
A Quad B mode - if the A input leads the B input, the Accumulator is incremented
and if the B input leads the A input the Accumulator is decremented.
Counter Timebase
For each counter, the Timebase represents a span of time which can be used to measure
the rate of counting. For example, a program required to monitor the number of count
pulses that occur every 30 seconds could use a Timebase of 30,000.
A Timebase from 1 millisecond to 65535 milliseconds can be selected for each counter.
The counter timebase is set to 1 second (1000 milliseconds) by default. The module
stores the number of counts that occurred during the last-completed timebase interval in
theCounts/Timebase register. The timebase value selected should not allow the
Counts/Timebase register to overflow at the maximum count frequency.
The timebase counter updates once each timebase period. After power-up, or any
disruption in counting, allow at least one timebase period for the counter to stabilize.
Preload Value
For each counter, a starting, or Preload, value can be specified which will be used when
the Preload input is activated. This Preload value is used for both hardware and
software preloads. If the counter should be reset to zero, enter 0 as the Preload value;
this is the default value. The preload range is –2,147,483,648 to +2,147,483,647.
Strobe Mode
The Strobe Mode determines which Strobe input pulse the Strobe register will report. In
Last mode, the Strobe register is always updated with the Accumulator value when the
configured Strobe input transition occurs. Therefore, two rapid Strobe pulses could
result in the first Strobe register value being missed. In First mode, the Strobe register is
updated only if the Strobe flag set by a previous Strobe pulse has been acknowledged by
setting the corresponding reset Strobe %Q bit. In this mode, any subsequent Strobe
pulses will be ignored and lost, but the first will always be retained. The default mode is
Last.
Strobe Edge
Strobe inputs are edge sensitive. Each Strobe input on the module can be individually
configured to have either the positive or the negative edge active. By default, they are
positive-edge sensitive.
Strobe Linkage
The Strobe Linkage selects whether strobes for each counter operate independently or
are linked to Accumulator 2. In Independent mode, Strobe Pulses strobe their respective
Accumulators. In Accumulator 2 mode, normal Strobe 1.1 and 2.1 operations are
disabled. Strobe 1.1 and 1.2 are triggered whenever the Counter 2 Accumulator changes.
4-12
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
4
Data Transfer Between High Speed Counter and CPU
The Series 90-70 High Speed Counter updates the %I and %AI data every 0.5
milliseconds. The Series 90-70 CPU reads this data immediately preceding every pass
through the ladder logic, before triggering a ladder interrupt, and when a DOIO
specifically requesting this data is performed in the ladder logic. To support the unique
data coherency requirements of the High Speed Counter, the CPU reads both the %I and
%AI data when performing DOIOs requesting only %I data.
The format of this input data depends on the counter configuration type. In return,
during each I/O scan, the CPU sends 32 bits (%Q) of control data and 6 words (%AQ) of
output data commands to the module. COMMREQ function blocks in the user program
can be used to send additional data commands to the module.
See Appendix A for more information about the COMMREQ and DOIO functions.
%I and %AI Data Sent by a Module Configured as Type B
The 32 status bits (%I) represent:
H
H
H
H
H
H
H
Strobe status flag
Preload status flag
Disable status
Preset Output status
Module ready status
Error status
Interrupt status
These status bits are sent to the CPU as inputs, and can influence outputs sent from the
CPU to the module.
The 16 register data words (%AI) represent:
H
H
H
H
GFK-1062A
Counts per Timebase value
Accumulators
Strobe Registers
module status code
Chapter 4 Counter Type B
4-13
4
Status Bits (%I) - Type B Counter
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
strobe 1.1 status
strobe 1.2 status
strobe 2.1 status
strobe 2.2 status
preload 1 status
preload 2 status
disable 1 status
disable 2 status
output 1 status
output 2 status
output 3 status
output 4 status
module ready
reserved
error
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
reserved
reserved
preset 1 interrupt status
preset 2 interrupt status
preset 3 interrupt status
preset 4 interrupt status
reserved
Strobe Status
Each bit indicates when a Strobe Pulse occurs on the counter. If an application program
uses this bit, it should be cleared by setting the corresponding Reset Strobe %Q bit. In
First Strobe mode, additional strobes will be ignored until the Reset Strobe %Q bit is set.
Preload Status
Each bit indicate a rising edge of the corresponding Preload input on the counter. If an
application program uses these bits, it should clear them by setting the corresponding
Reset Preload %Q bit.
Disable Status
These bits indicate the level of the Disable inputs and whether counting is disabled.
When set, the Disable input is ON and count inputs are ignored.
Output Status
These bits indicate the ON or OFF state of the four preset outputs.
Module Ready
This bit is set after the module completes its power-up tests.
Error Status
This bit is set when an error occurs. If it is set, a module status code has been returned in
the first %AI location and the board OK LED flashes at 4 Hz. The Error Status bit is
cleared by setting the Clear Error %Q bit.
4-14
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
4
Preset Interrupt Status
These bits are set by the High Speed Counter when the corresponding preset output has
changed state and generated an interrupt. These flags can be used by an interrupt
routine to determine which outputs have generated interrupts. The Output Status bits
can be used in conjunction with the Preset Interrupt Status bits to determine which
transition caused the interrupt. The Preset Interrupt Status bits should only be tested in
a ladder logic interrupt handler.
%AI Data - Type B Counter
Word
Description
01
Module Status code
02
Counts per timebase for counter 1
03
Counts per timebase for counter 2
04-05
Accumulator for counter 1
06-07
Strobe register 1 for counter 1
08-09
Strobe register 2 for counter 1
10-11
Accumulator for counter 2
12-13
Strobe register 1 for counter 2
14-15
Strobe register 2 for counter 2
16
Unused
Module Status Codes
The Module Status Code in the %AI Input Data contains the error code returned to the
PLC. The HSC sets this code to indicate a data command or configuration error. Once
an error code has been returned, no more errors will be generated until the error is
cleared. To clear a module status code, eliminate the condition that caused the error, and
toggle the Clear Error %Q bit.
Note that fatal errors (RAM, EPROM) have no codes associated with them because these
errors cause the watchdog timer to time out and the board to go into constant reset.
The error code format and a list of error codes are given below.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
High Byte
Error Source
GFK-1062A
Chapter 4 Counter Type B
Counter or Preset #
Low Byte
Error Code
4-15
4
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
Error Codes for Type B Counter
Error Code
Error Type
00
No Error
Definition
No Error Present
11
Unknown Command
21
Invalid Counter or Preset
31
Invalid COMMREQ Task ID
41
Command
81
Errors
Velocity Increment Out of Range
Accumulator Out of Range
91
Preload Value Out of Range
C1
Preset ON Out of Range
D1
Preset Off Out of Range
12
High Limit < Low Limit
22
Limit
Range Excludes Preload
52
Errors
Range Excludes Preset ON
62
Range Excludes Preset OFF
18
High Limit < Low Limit
28
Range Excludes Preload
58
Range Excludes Preset ON
68
Configuration
Range Excludes Preset OFF
A8
Errors
Unsupported Feature Error
B8
Unknown Counter Type
C8
PLC Version Error
D8
Logicmaster 90 Version Error
Configuration Errors are not returned in %AI data since the module does not configure,
but the error code is returned in the IO Fault Table additional fault information, which is
accessed by pressing Ctrl-F.
Counter or Preset Number
For a valid command (recognized value in byte 0), the counter (1 or 2) or preset number,
1 to 4, which generated the error will be reported in this nibble. A preset number only
appears in error codes C1 and D1.
Error Source
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
Command and Limit errors return the source of the error.
Value
Example:
Error Source
1
%AQ Command 1 (%AQ Offset 0-2)
2
%AQ Command 2 (%AQ Offset 3-5)
4
COMMREQ Function
If the hexadecimal data 0002 0000 0107 was placed into the %AQ offsets 3 through 5, the
error 2141h would be reported. The Module Status Code represents:
Value
4-16
t
Representation
2
Error in %AQ Command 2
1
Error generated by counter 1
41
Velocity Increment Out of Range
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
4
%Q and %AQ Data Sent from CPU to HSC Configured as Type B
Once each I/O scan, the CPU sends eight words of data (32 bits of %Q and six words of
%AQ) to the High Speed Counter Module. The application program can use these
outputs to send commands to the module.
The 32 output bits (%Q) represent:
H
H
H
H
H
Reset Strobe flag
Reset Preload flag
Clear error flag
Output enable
Accumulator preload
Six words (%AQ) of Command Data
The 6 words of command data, which can also be sent using a COMMREQ Function
Block, can perform the following operations:
H
H
H
H
H
H
H
H
Load Accumulator
Load count limits
Load Accumulator increment
Load output preset on and off values
Load Preload values
Load time base
Load Oscillator divider
Enable/Disableinterrupts
All of this data is transferred from the High Speed Counter to the CPU once per I/O
scan. The I/O scan is active while the CPU is in the RUN mode or STOP ENABLED
mode.
GFK-1062A
Chapter 4 Counter Type B
4-17
4
%Q Data - Type B Counter
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
reset strobe 1.1
reset strobe 1.2
reset strobe 2.1
reset strobe 2.2
reset preload 1
reset preload 2
reserved
enable output 1.1
enable output 1.2
enable output 2.1
enable output 2.2
reserved
clear error
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
preload accumulator 1
preload accumulator 2
reserved
reserved
reserved
reserved
Reset Strobe
Setting this bit clears the corresponding Strobe Status %I bit. In First Strobe mode,
subsequent strobe pulses are ignored until this bit is used to clear the Strobe Status bit.
Reset Preload
This bit is used to clear the corresponding Preload Status %I bit. For example, if a
Preload occurred, the Preload Status %I bit would be set. To clear this bit so future
Preloads can be detected, the Reset Preload %Q bit must transition ON.
Enable Output
These bits enable the corresponding preset output. If cleared, the output will always be
OFF and not reflect the accumulator’s value in relation to the Preset ON and OFF values.
Clear Error
This bit should be set by the CPU to clear the Error Status %I bit after the error has been
acknowledged. This bit is rising edge active, so new errors may appear while set.
Preload Accumulator
These bits tell the counter to perform a software preload and set the corresponding
Accumulator to the Preload value. They do NOT, however, cause the corresponding
Preload Status bit to be set.
4-18
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
4
Data Commands for Counter Type B
At the end of every CPU sweep, six words of %AQ data are automatically transferred
from the CPU to the High Speed Counter. These six words are used to send data
commands from the PLC to the HSC. The first three words, offsets 0 through 2, make up
%AQ command 1, and the second three words, offsets 3 through 5, make up a
completely separate %AQ command 2. Thus two commands can be sent to the HSC at
the end of each sweep. Note that %AQ command 1 is executed first, so that if identical
commands with different values are sent to the HSC simultaneously, %AQ command 2
data will overwrite %AQ command 1 data.
Even though the %AQ data is sent each sweep, commands are acted on ONLY if the
command has changed since the last sweep. When any of the 6 bytes in a command
changes, the HSC will accept the data as a new command and respond accordingly.
The DOIO function is supported, so that data can be transferred between the CPU and
HSC mid-sweep. Note that to ensure that the High Speed Counter has time to process
DOIO data sent to it, the application should not change the data more frequently than
every 0.5 millisecond. Because data sent to the HSC is updated at the end of the CPU
sweep, half a millisecond should elapse between the beginning of the sweep and a
DOIO function block, between two DOIO function blocks, and between a DOIO
function block and the end of the sweep.
The COMMREQ function block can also be used to send data commands to the HSC
mid-sweep. COMMREQs must be separated only from each other, and by at least 0.5
milliseconds. A description and example of the use of COMMREQs and DOIOs is given in
Appendix A.
%Q data is processed by the HSC before the %AQ data. Therefore commands that can be
affected by %Q bit operations should be sent at least one sweep before the %Q bit
operation. For example, the Load Preload Value command should be sent one sweep before
setting the Preload Accumulator %Q bit to preload that value.
In describing data commands, word offsets are shown in reverse order and in
hexadecimal to simplify data entry. The following example sends a Load Accumulator
Counts command with value 0001 to counter 2 using offsets 0 through 2.
The first word, or command word, which goes into word offset 0 is 0201h. The value 01
in byte 0 represents the command Load Accumulator Value. The value 02 in byte 1 is the
counter number, in this case counter 2. For the Load Accumulator Value command,
word 1 is the 16-bit value to be loaded into the accumulator and word 2 is ignored. In
this example, word 1 would have the value 0001h because that is the value to be placed
in the accumulator. Word 2 will be ignored and can be anything, but it is usually best to
use the value 0. If word offset 0 corresponded to %AQ1, the complete command to load
the counter 2 accumulator with value 0001 would be:
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
GFK-1062A
%AQ3 (word 2)
%AQ2 (word 1)
%AQ1 (word 0)
0000
0001
0201
Chapter 4 Counter Type B
4-19
4
The following table is a list of data commands for counter Type B. Byte 0 data is in
hexadecimal.
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
Data
Command Definition
Null
Word 2
Byte 5
Byte 4
xx
Word 1
Byte 3
Byte 2
xx
xx
xx
Command Word
Word 0
Byte 1
Byte 0
xx
00h
Load Accumulator Value
data (32)
n
01h
Load High Limit
data (32)
n
02h
n
03h
n
04h
n
06h
Load Low Limit
data (32)
Load Accumulator Increment
xx
xx
Load Timebase
xx
xx
Load Velocity
xx
Load Preset ON Value
data (8)
data (16)
data (24)
data (32)
Enable/Disable Preset ON Interrupt
xx
Load Preset OFF Value
xx
xx
data (8)
data (32)
Enable/Disable Preset OFF Interrupt
xx
Load Preload Value
Load Oscillator Divider
xx
xx
xx
data (8)
data (32)
xx
xx
data (16)
n
07h
m
0Bh
m
0Fh
m
15h
m
19h
n
1Fh
0
32h
m = Preset Number (1 to 4); n = Counter Number (1 or 2);
xx = Do not care (ignored); data (8, 16, 24, 32) = 8, 16, 24, or 32 bit data
Descriptions of each command are given below. The valid range of values is given in
parenthesis.
Null
This is the default %AQ data command. Since the %AQ data is transferred each PLC
sweep, it is a good idea to have the Null command present when not executing a specific
data command to avoid inadvertent execution. All data is ignored with a Null
command.
Load Accumulator Value (Low Limit to High Limit)
This command places a 32-bit value into a counter accumulator. The value must be
within the Count Limits, or an error will be returned and the command ignored.
Load High Limit
(–2,147,483,648 to 2,147,483,647)
This command sets the highest value to which a counter will count. Counts that would
cause the counter to go higher are ignored or cause the accumulator to roll over to the
Low Limit depending on whether the counter is configured for Single-shot or
Continuous count mode. The High Limit can be any 32-bit value with the following
restrictions: it must be greater than the Low Limit, the counter’s Preload value must lie
between it and the Low Limit, and all preset outputs which are assigned to the counter
must have preset ON and OFF values which lie between it and the Low Limit. If a
restriction is not met, an error will be generated and the command ignored. If the range
between the Low Limit and the new High Limit excludes the Accumulator, the
Accumulator will be set to the Low Limit and no error is generated.
4-20
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
4
Load Low Limit
(–2,147,483,648 to 2,147,483,6477)
This command sets the lowest value to which a counter will count. Counts that would
cause the counter to go lower are ignored or cause the accumulator to roll over to the
High Limit depending on whether the counter is configured for Single-shot or
Continuous count mode. The Low Limit can be any 32-bit value with the following
restrictions: it must be less than the High Limit, the counter’s Preload value must lie
between it and the High Limit, and all preset outputs which are assigned to the counter
must have preset ON and OFF values which lie between it and the High Limit. If a
restriction is not met, an error will be generated and the command ignored. If the range
between the new Low Limit and the High Limit excludes the Accumulator, the
Accumulator will be set to the Low Limit and no error is generated.
Load Accumulator Increment (–128 to 127)
The Accumulator Increment performs a one-shot adjustment to the accumulator. Only
byte 2 is used for data, all other data bytes are ignored. The one-shot increment can be
performed at any time, even when counting at maximum rate. If the offset causes the
counter to exceed its limits, the excess is treated just like any other overflow, that is., in
Continuous mode the Accumulator rolls over to the other limit and in Single-shot mode
the Accumulator does not pass the limit.
Load Timebase (1 to 65535 milliseconds)
This command sets the timebase. The timebase is the number of milliseconds for which
the counter counts input pulses and then returns in the Counts per Timebase register. If
the timebase is 1000, or 1 second, the Counts per Timebase register returns the number
of counts detected in each 1 second period. Any non-zero 16-bit value may be used as
the timebase.
Load Velocity (–100,000 to 100,000 counts per second)
A velocity increment is an internal count generator, or a continuous accumulator
increment. Each millisecond, 0.1% of the increment value is added to the accumulator.
A value of 0 will stop the velocity increment. Counts from the velocity increment are
cumulative with counts coming in from the Count Pulse input. Note that counts
generated by the velocity increment are not reflected in the Counts per Timebase
register.
Load ON and OFF Preset Value (Count limits of the assigned counter)
This command sets the preset output turn on and turn off points within a counters
range. Preset values can be any value between the high and low limits, inclusive.
Enable/Disable Preset ON and OFF Interrupts
(0=Disable, 1=Enable)
This command enables or disables interrupts resulting from Preset output transitions.
For example, if Preset ON interrupts are enabled, then a low to high transition of the
Preset ON output will generate an interrupt to the CPU. This command allows the
interrupts to be enabled or disabled within the ladder program.
Load Preload Value (Low Limit to High Limit)
The Load Preload command sets the value to which the Accumulator will be set when a
positive edge occurs on the Preload input. The value must be between the High and
Low Limits or an error will be returned and the command ignored.
GFK-1062A
Chapter 4 Counter Type B
4-21
4
Load Oscillator Divider (1 to 65535)
This command changes the frequency of the square wave oscillator signal. The
frequency generated is 1 megahertz (1 MHz) divided by the oscillator divider. Therefore
to get 50 Hz, the oscillator divider is 20000.
4-22
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
Chapter
5 Counter Type C
section level 1
figure bi level 1
table_big level 1
5
Counter type C is described in this chapter. The counter description includes counter
operation, configuration of the counter, and the interface between the counter and the
CPU.
Contents and Operation of a Type C Counter
Overview
The Type C counter contains a single, complex 32-bit bidirectional counter. The counter
uses 12 single ended or differential voltage inputs: two pairs of count inputs (Count A1,
Count B1, Count A2, and Count B2), three independent strobe inputs (Strobe 1, Strobe 2,
and Strobe 3), two preload inputs (Preload 1 and Preload 2), Disable, Home Switch, and
Marker. The counter may be configured to count in one of three modes: Up and Down,
Pulse with Direction, and A Quad B. Counter type C elements are shown in the figure
below.
The counter has a 32-bit accumulator register which sums the pulses from a positive
input loop and a negative input loop, a Disable input which causes the accumulator to
ignore pulses on the input loops, three strobe registers which store the Accumulator
value when a corresponding Strobe input transitions, two preload values of which one is
inserted into the accumulator the corresponding preload occurs, a Home value which is
inserted into the accumulator when a Home Cycle occurs, and a counts per timebase
register which indicates the count rate of the input pulses.
The positive input loop is made up of Count A1 and Count B1, and the negative input
loop is made up of Count A2 and Count B2.
Each of four Presets is tied to one of the four 5 to 30 V outputs and can be used to
generate PLC interrupts.
GFK-1062A
5-1
5
Î
Î
Î
Î
Î
a43078
MARKER
HOME SWITCH
PRELOAD 1
PRELOAD 2
TYPE C COUNTER (32-BIT)
HOME POSITION
(32-BIT)
PRELOAD #1 POSITION
(32-BIT)
PRELOAD #2 POSITION
(32-BIT)
ÎÎÎÎÎÎÎÎ
Î
ÎÎÎÎÎÎÎÎ
Î
ÎÎÎÎÎÎÎÎ
Î
ÎÎÎÎÎÎÎÎ
Î
ÎÎÎÎÎÎÎÎÎ
ÎÎÎÎÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎÎ
Î
ÎÎÎÎÎÎÎÎ
Î
ÎÎÎÎÎÎÎÎ
ÎÎÎÎÎÎÎÎÎ
ÎÎÎÎÎÎÎÎ
Î
ÎÎÎÎÎÎÎÎÎ
ÎÎÎÎÎÎÎÎ
Î
ÎÎ
ÎÎÎÎÎÎÎÎ
ÎÎ
Î
ÎÎÎÎÎÎÎÎ
ÎÎÎÎÎÎÎÎ
ÎÎ
ÎÎÎÎÎÎÎÎ
ÎÎÎÎÎÎÎÎ
Î
ÎÎ
ÎÎÎÎÎÎÎÎ
ÎÎ
ÎÎÎÎÎÎÎÎ
Î
ÎÎ
ÎÎÎÎÎÎÎÎ
ÎÎÎÎÎÎÎÎ
A1 INPUT
(+) LOOP
B1 INPUT
DISABLE
A2 INPUT
ACCUMULATOR
(32-BIT)
(–) LOOP
B2 INPUT
COUNTS PER
TIME BASE
(16-BIT)
STROBE 1
STROBE REGISTER 1
(32-BIT)
STROBE 2
STROBE REGISTER 2
(32-BIT)
STROBE 3
STROBE REGISTER 3
(32-BIT)
ACCUMULATOR
ADJUST
(8-BIT)
ON/OFF PRESETS 1
(32-BIT)
OUTPUT 1
ON/OFF PRESETS 2
(32-BIT)
OUTPUT 2
ON/OFF PRESETS 3
(32-BIT)
OUTPUT 3
ON/OFF PRESETS 4
(32-BIT)
OUTPUT 4
Count Inputs and Accumulator
The 32-bit Accumulator is incremented or decremented based on a configured
interpretation of the two pairs of count inputs that can be connected to operate in a
differential fashion. The accumulator sums the inputs from the positive and negative
input loops.
5-2
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
5
Type C Counter Positive and Negative Loops
In the Type C counter configuration, pulses on the positive loop are counted normally,
while pulses on the negative loop are inverted. The following table describes the
accumulator function for the different input loop combinations.
Count Direction
(positive) Loop (negative) Loop
A1, B1
A2, B2
ACCUMULATOR FUNCTION
x = counts on (positive) loop
y = counts on (negative) loop
Up
Up
Differential (x–y)
Up
Down
Additive (x+y)
Down
Up
Additive –(x+y)
Down
Down
Differential (y–x)
Up
no connection
Counts Up (x)
Down
no connection
Counts Down (–x)
no connection
Up
Counts Down (–y)
no connection
Down
Counts Up (y)
The interpretation for each input loop can be set to Up/Down, Pulse/Direction,orA
Quad B. Note that the direction is reversed for the negative loop. Each is described
below.
Operating in UP/DOWN Mode
Up-counting occurs on the low-to-high transition of the Up input. Down counting
occurs on the low-to-high transition of the Down input.
a42973
IN–A UP
IN–B DOWN
COUNT
COUNT UP
ACC
VALUE
GFK-1062A
Chapter 5 Counter Type C
COUNT DOWN
N +2
N +1
N
5-3
5
Operating in Pulse/Direction Mode
Counting always occurs on the low-to-high transition of the Pulse input. Count direction is
up for a low level on the Direction input and down for a high level on the Direction input.
Avoid changing the DIR signal coincidentally with the rising edge of the Pulse input.
a42975
IN–A PULSE
IN–B DIR
COUNT
COUNT UP
COUNT DOWN
ACC N+2
VALUE N+1
N
Operating in A Quad B Mode
In A Quad B mode, there are four counts for each A Quad B cycle. A count occurs for
each transition of either A or B. The counts will be evenly spaced with respect to the
input waveforms when the phase relationship between A and B is shifted by 1/4 cycle.
The phase relationship between A and B determines count direction, as shown in the
following timing diagrams.
The count direction is up if A leads B.
a42977
A
B
COUNT
ACC
VALUE N
N+6
The count direction is down if A lags B.
a42978
A
B
COUNT
ACC
VALUE
5-4
t
N
N –6
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
5
Differential Counting
Operation of the Accumulator in a typical differential application is illustrated below.
a43716
+
LOOP
MODE:
A–QUAD–B
A
B
COUNTS
(INTERNAL)
LOOP
MODE:
A–QUAD–B
A
B
COUNTS
(INTERNAL)
COUNTS
12
11
10
9
8
7
6
5
4
3
2
1
TIME
The Accumulator is bounded by configurable High and Low Limits. The interaction
between the Accumulator and the limits depends on the configured count mode. In
Continuous mode, the Accumulator will increment or decrement to the current High or
Low Limit, roll over to the other limit, and continue counting. In Single Shot mode, the
Accumulator will count to the current High or Low Limit and stop. If the counter direction
is changed, the Accumulator will count away from the limit until it reaches the other limit.
The High and Low Limits can be changed to any valid 32-bit value at any time using a data
command from the PLC. To be a valid 32-bit value, the following conditions must be met:
H
H
H
H
GFK-1062A
the High Limit must be greater than the Low Limit
both Preload values must be within the High and Low Limit bounds
the Home value must be within the High and Low Limit bounds
all presets must be within the High and Low Limit bounds
Chapter 5 Counter Type C
5-5
5
If the limits are changed so the Accumulator is outside the limit boundaries, the
Accumulator is set to the Low Limit.
The Accumulator may be set to any 32-bit value within the bounds of the High and Low
limits at any time using a data command. Another data command allows the
Accumulator to be adjusted by a byte value, from –128 to +127. Finally, a velocity
increment can be commanded which causes the Accumulator to increment or decrement
at a fixed rate.
Strobe Inputs and Register
Each Strobe input is an edge sensitive input which can be configured to respond to
either a positive edge or a negative edge. When the configured Strobe input transition
occurs, (referred to as a Strobe Pulse) the value in the Accumulator is stored in the
corresponding Strobe register and a strobe flag is set and returned in %I data to indicate
the event to the CPU. The application program in the CPU acknowledges receipt of the
strobe by toggling the corresponding Reset Strobe %Q bit.
Two strobe modes are available to select which Strobe value is most important. In Last
Strobe mode, the default, a Strobe Pulse will always update the Strobe register with
the latest Accumulator value regardless of the strobe flag state. In First Strobe mode,
the first strobe value is captured and all subsequent Strobe Pulses are ignored until the
strobe flag is cleared by toggling the corresponding %Q bit.
Preload Input and Value
The Preload input is normally used to perform a reset function for the counter. The
value to which the Accumulator is set when a preload occurs can be configured to any
32-bit value within the range of the high and low limits and has a default value of zero.
The Preload value can also be changed using a data command from the PLC. There are
two types of preloads, hardware and software.
The Preload input is positive edge sensitive only. On the positive transition, the
configured preload value is inserted into the accumulator and a preload flag is set and
returned in %I data to indicate the event to the CPU. If an application program uses this
flag indication, it may use the corresponding %Q bit to clear the preload flag before the
next preload occurs. A rising edge on the Preload input always preloads the
Accumulator regardless of the state of the Preload flag. Preload 1 has precedence over
Preload 2 when both occur simultaneously.
Note that when a Preload pulse occurs on the inputs at the same time as a Strobe pulse,
or if the inputs are tied together, the Preload has precedence. The Accumulator will be
set to the Preload value and then the Strobe register will be set to the Accumulator. Thus
the Strobe register will obtain a copy of the Preload value.
A software preload can be performed by setting a Preload Accumulator %Q bit. On the
positive transition of this %Q bit, the preload value is placed into the Accumulator. A
software preload does NOT set the Preload Status flag. Note that there are two Preload
Accumulator %Q bits in a Type C counter, each with its own Preload value.
5-6
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
5
Home Switch, Marker Input, and Home Value
The Marker input is used in conjunction with the Home Switch to perform a homing
function for the counter. The value to which the Accumulator is set when a Home Cycle
completes can be configured to any 32-bit value within the range of the high and low
limits and has a default value of zero. The Home value can also be changed using a data
command from the PLC.
A Home Cycle is started by setting the Home Command %Q bit. Once the Home Cycle
starts, a rising edge on the Marker input while the Home Switch is level high will
complete the Home Cycle and place the Home value into the Accumulator. A Home
Found flag is set and returned in %I data to indicate the event to the CPU. The Home
Found flag will remain set until the next rising edge of the Home Command %Q bit.
The Home Cycle has precedence over the two preloads and the Accumulator value will
contain the Home value if a Home Cycle completes simultaneously with any Preload
input rising edge.
Counts per Timebase Register
The Counts per Timebase register is a 16-bit register which contains the number of
counts received in the last completed timebase interval. It is used to measure the rate of
counting. If more counts are received than can be stored in a 16-bit register, the register
will overflow. The timebase interval is a configurable value from 1 to 65535 milliseconds.
Changes to the timebase will not take effect until after the previous timebase and one
new timebase have elapsed. A Preload will interrupt counting and will cause the Counts
per Timebase register to be inaccurate for up to two timebase intervals. The timebase is
initially configured as 1 second, but may be changed using the Logicmaster 90-70
Configurator function or a data command.
As an unsigned number, the Counts per Timebase register will correctly indicate from 0
to 65536 positive counts received per timebase. As a signed number, it will properly
indicate from –32768 to 32767 counts per timebase. The timebase should be selected to
not allow more counts in a timebase than the 16-bit register can hold or it will overflow.
Preset Outputs
The module has four preset outputs. Each preset output has a preset ON and preset
OFF value, or position, which must be within the count limits. The preset ON and OFF
positions determine when the output will be ON or OFF.
Preset closest to low limit
GFK-1062A
Output ON
Output OFF
ON
> = ON Preset
< = OFF Preset
> OFF Preset
< ON Preset
OFF
< OFF Preset
> ON Preset
< = ON Preset
> = OFF Preset
Chapter 5 Counter Type C
5-7
5
The output may be either on or off when the accumulator value lies between the Preset
points.
OFF
PRESET
ON
PRESET
a42970
ON CONDITION INCLUDES PRESET POINTS
OFF
PRESET
ON
PRESET
OFF CONDITION INCLUDES PRESET POINTS
For example:
COUNTS
OFF PRESET
VALUE
ON PRESET
VALUE
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎÎÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ACCUMULATOR
VALUE
a43003
TIME
CORRESPONDING ON
OUTPUT
OFF
Separation of Preset Points
The count accumulators are compared to the Presets at 0.5 msec intervals. Therefore, to
guarantee that the outputs will always switch, the Preset points must be separated by at
least the number of counts received in a 0.5 msec time period. For example:
If maximum count rate = 10kHz;
then minimum count separation = (10,000 Hz x .0005 sec) = 5 counts.
Preset Interrupts
Interrupts can be enabled or disabled for each preset output’s ON and OFF transition.
At the same time a preset output changes state, the CPU is interrupted. %I and %AI
input data are updated so that an interrupt routine will see the most current data from
the High Speed Counter. From the %I data, an interrupt routine can determine which
presets changed state and which edge(s) generated the interrupt. Simultaneous preset
changes generate only 1 interrupt to the CPU. Once configured, interrupts can be
independently enabled or disabled using data commands. See Appendix B for
information on using the interrupt capability.
Output Failure Mode
When the CPU is stopped or lost, counter operation continues normally without
interfacing to the CPU. Until the CPU returns or power is cycled, the operation of the
Preset outputs can be configured. In Normal mode, the outputs continue to operate as if
the CPU were present. Outputs will change state to reflect the counter Accumulator. In
Force Off mode, all preset outputs are turned off and remain off until the CPU returns.
5-8
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
5
In Holdlast mode, the preset outputs retain current levels and do not reflect the counter
Accumulator. If the CPU returns to operation, the outputs will immediately begin
reflecting the counter Accumulator.
Oscillator Output
The High Speed Counter module generates a 5V square wave oscillator signal. The
oscillator output frequency is determined by the current oscillator divider (set in
configuration or by data command) as indicated below:
Oscillator Frequency (Hz) = 1,000,000 Ï oscillator divider
The output frequency ranges from approximately 15 Hz (oscillator divider of 65535) to
1 MHz (oscillator divider of 1).
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
Table 5-1. Type C Specific Terminal Strip Assignments
GFK-1062A
Pin
Signal
Name
Type C
Pin Name
Type C
Pin Description
1,3
IN1
COUNT INPUT A+
Count positive loop A input
2,4
IN2
COUNT INPUT B+
Count positive loop B input
5,7
IN3
COUNT INPUT A–
Count negative loop A input
6,8
IN4
COUNT INPUT B–
Count negative loop B input
11,13
IN5
PRELOAD1
Counter preload 1 input
12,14
IN6
DISABLE 1
Counter disable input
15,17
IN7
PRELOAD2
Counter preload 2 input
16,18
IN8
HOME
Home switch input
21,23
IN9
STROBE 1
Counter strobe 1 input
22,24
IN10
STROBE 2
Counter strobe 2 input
25,27
IN11
STROBE 3
Counter strobe 3 input
26,28
IN12
MARKER
Encoder marker input
Chapter 5 Counter Type C
5-9
5
Configuring the Type C High Speed Counter
The following table summarizes all configuration features and default configuration values
for the Type C counter.
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
Á
ÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
Output Failure Mode
Configuration
Parameter
Description
Values
Default
Failure Mde
Output Failure Mode
NORMAL, OFF, HOLD
NORMAL
Osc Divider
OscillatorDivider
1 ... 65535
1000
Count Thrshlds
Count Input Thresholds
NON-TTL, TTL, MAG-PKUP
NON-TTL
ControlThrshlds
Control Input Thresholds
NON-TTL, TTL
NON-TTL
Count Filtr
Count Input Filter
HIFREQ, LOWFREQ
HIFREQ
Preld Filtr
Preload Input Filter
HIFREQ, LOWFREQ
HIFREQ
Disbl Filtr
Disable Input Filter
HIFREQ, LOWFREQ
HIFREQ
ON
Preset ON Setpoint
Low Limit ... High Limit
8,388,607
OFF
Preset OFF Setpoint
Low Limit ... High Limit
0
ON Interrupt
Preset on transition interrupt
DISABLED,ENABLED
DISABLED
OFF Interrupt
Preset off transition interrupt
DISABLED,ENABLED
DISABLED
Hi Limit
High Count Limit
–2,147,483,648 ... 2,147,483,647
8,388,607
Lo Limit
Low Count Limit
–2,147,483,648 ... 2,147,483,647
0
Count Mode
Count Mode
CONTINU, SINGSHOT
CONTINU
Count Sig
Count Signals
PULSE/DIR,UP/DOWN, A QUAD B PULSE/DIR
Timebase (ms)
Timebase
1 ... 65535 ms
1000 ms
Preld 1 Value
Preload 1 Value
Low Limit ... High Limit
0
Preld 2 Value
Preload 2 Value
Low Limit ... High Limit
0
Home Value
Home Value
Low Limit ... High Limit
0
Strobe Mode
Strobe Mode
LAST, FIRST
LAST
Strobe 1 Edge
Strobe 1 Edge
POS, NEG
POS
Strobe 2 Edge
Strobe 2 Edge
POS, NEG
POS
Strobe 3 Edge
Strobe 3 Edge
POS, NEG
POS
When the CPU is stopped or lost, counter operation continues normally, however, the
operation of the Preset outputs until the CPU returns or power is cycled can be
configured. In all modes, the Accumulator is updated and the Strobes, Preloads, and
Home Cycle are processed normally.
In Normal mode (NORMAL), the outputs continue to operate as if the CPU were
present. Outputs will change state to reflect the counter Accumulator.
5-10
H
In Force Off mode (OFF), all preset outputs are turned off and remain off until the
CPU returns.
H
In Holdlast mode (HOLD), the preset outputs retain current levels and do not reflect
the counter Accumulator.
H
If the CPU returns to operation or the module is power-cycled, the outputs will
immediately begin reflecting the counter Accumulator again.
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
5
Oscillator Divider
The oscillator divider is used to generate a 5V oscillator output. The output frequency is
1 million divided by the oscillator divider; the formula is shown below.
Oscillator Frequency (Hz) = 1,000,000 / oscillator divider
The output frequency ranges from approximately 15 Hz (oscillator divider of 65535) to 1
MHz (oscillator divider of 1).
Input Thresholds
All inputs can be used as differential or single-ended inputs. The following table
specifies the input thresholds for single-ended and differential use based on threshold
selection and input type. The configuration parameters will set input thresholds
according to the following table:
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
Configuration Parameter
Inputs Controlled
Input Definitions
Counter Threshold
IN1, IN2, IN3, IN4
Count Pulse 1A, 1B, 2A, 2B
ControlThreshold
IN5, IN6, 1N7, 1N8,
IN9, IN10, 1N11, 1N12
Preload 1, Preload 2, Disable,
Strobe 1, Strobe 2, Strobe 3,
Marker, Home Switch
Note that all the inputs controlled will have the same voltage threshold.
The voltage thresholds which can be selected for each input are described in the
following table.
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
Input Type
Single-Ended
Differential
Non-TTL
TTL
Mag-Pickup
Non-TTL
TTL
Mag-Pickup
Counter Threshold
8V
1.4 V
0.1 V
4.8 V
0.8 V
0.1 V
ControlThreshold
8V
1.4 V
X
4.8 V
0.8 V
X
Input Filters
All inputs default to using a 2.5 microsecond high-frequency filter. Each Preload,
Disable, and pair of Count inputs can be configured to use a 12.5 millisecond
low-frequency filter instead. The low-frequency filter reduces the effects of signal noise.
The Strobe, Marker, and Home Switch inputs always use the high-frequency filter.
Output Preset ON and OFF Positions
Each counter output has a preset ON and OFF position. The output state indicates
when the counter accumulator value is between the ON and OFF points.
Preset closest to low limit
GFK-1062A
Output ON
Output OFF
ON
> = ON Preset
< = OFF Preset
> OFF Preset
< ON Preset
OFF
< OFF Preset
> ON Preset
< = ON Preset
> = OFF Preset
Chapter 5 Counter Type C
5-11
5
The output may be either on or off when the accumulator value lies between the Preset
points.
OFF
PRESET
ON
PRESET
a42970
ON CONDITION INCLUDES PRESET POINTS
OFF
PRESET
ON
PRESET
OFF CONDITION INCLUDES PRESET POINTS
For example:
COUNTS
OFF PRESET
VALUE
ON PRESET
VALUE
ON
CORRESPONDING
OUTPUT
OFF
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎÎÎÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ACCUMULATOR
VALUE
a43003
TIME
Location of Preset Points
The Preset points may be located anywhere within the counter range. When the
accumulator value is between the Preset points, the output ON/OFF state will always be
that of the lowest (most negative) Preset point. When the accumulator value is not
between the Preset points, the output ON/OFF state will be that of the most positive
preset. This is true regardless of the counter direction.
The following example compares the output state and accumulator value of a 32-bit
counter.
OUTPUT
COUNTER RANGE
ON
0
OFF
80000000H COUNTER
MINIMUM
LOW
LOW LIMIT
LIMIT
OFF
PRESET
ACCUMULATOR
VALUE
ON
COUNTER 7FFFFFFFH
PRESET
MAXIMUM
HIGH
HIGH LIMIT
LIMIT
If both preset points are within the counter range, the output always switches at the
Preset points. If only one of the Preset points is programmed within the counter range,
then the counter limits will function as the other Preset point. In the continuous mode,
the output will switch when wraparound occurs.
If neither of the Preset points is in the counter range then the output state will not
change; it will always be the state of the most positive Preset. If both Preset points are
equal and out of range, the output will always be OFF. If both Preset points are equal
5-12
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
5
and within the counter range, then the output will only be on for one count value - as
defined by the Preset points.
Preset Interrupt Enables
Each preset can generate an interrupt to the CPU. If the Interrupt ON selection is
enabled, then an ON transition of the preset output will generate an interrupt to the
CPU. Similarly, if the Interrupt OFF selection is enabled, an OFF transition of the preset
output will generate an interrupt to the CPU. Thus no edge, either edge, or both edges
of a preset output transition can generate an interrupt. The default is for all interrupts to
be disabled.
Count Limits
Each counter is assigned upper and lower count limits. The upper (high) limit must the
most positive, and the lower limit must be the most negative. Both limits can be positive
or negative, but the high limit must always be greater than the low limit. The
Accumulator, Preload values, Home Value, and all Preset outputs must lie within the
high and low limits.
If the Accumulator value is outside the new limits when the limits are changed it is
automatically adjusted to the low limit value. If the new limits are incompatible, that is,
(high < low or Low > high), then they will be rejected and the old limits retained. In
this case a counter limit error code will be returned. To avoid this situation when the
limits are changed one at a time, a good rule to follow is: always move the high limit first
when shifting the limits up and always move the low limit first when shifting them
down.
As a 32-bit counter, the limit range is –2,147,483,648 to 2,147,483,647.
Count Mode
A counter can be configured to count continuously within the count limits, or to count to
a limit and stop.
Continuous Counting
In the continuous counting mode, if either the upper or lower limit is exceeded, the
counter wraps around to the other limit and continues counting. Continuous counting is
the default mode.
Single-Shot Counting
If single-shot is selected, the counter will count to its upper or lower limit, then stop.
When the counter is at the limit, counts in the opposite direction will count it back off
the limit. The Accumulator can also be changed by loading a new value from the CPU or
by applying a Preset Input.
GFK-1062A
Chapter 5 Counter Type C
5-13
5
Count Signal Mode
Each pair of count inputs can be configured to interpret signals in one of three ways:
H
Up/Down mode mode - rising edges on the A, or up, input increment the
Accumulator while positive transitions on the B, or down, input decrement the
Accumulator.
H
Pulse/Direction mode - rising edges on the A, or pulse, input are counted. If the B, or
direction, input is low then the Accumulator is incremented but if the Second input
is high then the Accumulator is decremented.
H
A Quad B mode - if the A input leads the B input, the Accumulator is incremented
and if the B input leads the A input the Accumulator is decremented.
Counter Timebase
For each counter, the timebase represents a span of time which can be used to measure
the rate of counting. For example, a program required to monitor the number of count
pulses which occur every 30 seconds could use a timebase of 30,000.
A timebase from 1 millisecond to 65535 milliseconds can be selected for each counter.
The counter timebase is set to 1 second (1000 milliseconds) by default. The module
stores the number of counts that occurred during the last-completed timebase interval in
theCounts/Timebase register.
The timebase counter updates once each timebase period. After power-up, or any
disruption in counting, allow at least one timebase period for the counter to stabilize.
Preload Value
For each counter, a starting, or Preload, value can be specified which will be used when
the Preload input is activated. This Preload value is used for both hardware and
software preloads. If the counter should be reset to zero, enter 0 as the Preload value;
this is the default value. The Preload value range is –2,147,483,648 to +2,147,483,647,
but it must be within the counter limits.
Home Value
If the module has been set up to operate as a Type C counter, a Home Value can be
selected. The default for the Home Value is 0. The counter will be set to this value when
all three of the following events occur:
1.
Find Home command is given by the CPU;
2.
Home Switch input is present;
3.
next Marker input pulse occurs.
Additional markers will be ineffective until the Home Command is removed and the
Home Command sequence is repeated. If the Home Command is removed before the
Home marker is found, a Home Error will be returned.
5-14
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
5
Strobe Mode
The Strobe Mode determines which Strobe input pulse the Strobe register will report. In
Last mode, the Strobe register is always updated with the Accumulator value when the
configured Strobe input transition occurs. Thus two rapid Strobe pulses could result in
the first Strobe register value being missed. In First mode, the Strobe register is updated
only if the Strobe flag set by a previous Strobe pulse has been acknowledged by setting
the corresponding Reset Strobe %Q bit. In this mode, any subsequent Strobe pulses will
be ignored and lost, but the first will always be retained. The default mode is Last.
Strobe Edge
Strobe inputs are edge sensitive. Each Strobe input on the module can be individually
configured to have either the positive or the negative edge active. By default, they are
positive-edge sensitive.
GFK-1062A
Chapter 5 Counter Type C
5-15
5
Data Transfer Between High Speed Counter and CPU
The Series 90-70 High Speed Counter updates the %I and %AI data every 0.5
milliseconds. The Series 90-70 CPU reads this data immediately preceding every pass
through the ladder logic, before triggering a ladder interrupt, and when a DOIO
specifically requesting this data is performed in the ladder logic. To support the unique
data coherency requirements of the High Speed Counter, the CPU reads both the %I and
%AI data when performing DOIOs requesting only %I data.
The format of this input data depends on the counter configuration type. In return,
during each I/O scan, the CPU sends 32 bits (%Q) of control data and 6 words (%AQ) of
output data commands to the module. COMMREQ function blocks in the user program
can be used to send additional data commands to the module.
See Appendix A for more information about the COMMREQ and DOIO functions.
%I and %AI Data Sent by a Module Configured as Type C
The 32 status bits (%I) represent:
H
H
H
H
H
H
H
Strobe status flag
Preload status flag
Disable status
Preset Output status
Module ready status
Home Switch status
Error status
These status bits are sent to the CPU as inputs, and can influence outputs sent from the
CPU to the module.
The 16 register data words (%AI) represent:
H
H
H
H
5-16
Counts per Timebase value
Accumulators
Strobe Registers
Module Status Code
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
5
Status Bits (%I) - Type C Counter
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
strobe 1 status
strobe 2 status
strobe 3 status
home found
preload 1 status
preload 2 status
disable status
home switch status
output 1 status
output 2 status
output 3 status
output 4 status
module ready
reserved
error
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
reserved
reserved
preset 1 interrupt status
preset 2 interrupt status
preset 3 interrupt status
preset 4 interrupt status
reserved
Strobe Status
Each bit indicates when a Strobe Pulse occurs on the counter. If an application program
uses this bit, it should be cleared by setting the corresponding Reset Strobe %Q bit. In
First Strobe mode, additional strobes will be ignored until the Reset Strobe %Q bit is set.
Home Found
This bit indicates the completion of the Home Cycle. It is set on the rising edge of the
Marker input when the Home Switch is ON and the Find Home %Q bit is set. When the
Find Home %Q bit is cleared and then set again, the Home Found bit is cleared.
Preload Status
Each bit indicates a rising edge of the corresponding Preload input on the counter. If an
application program uses these bits, it should clear them by setting the corresponding
Reset Preload %Q bit.
Disable Status
This bit indicates the level of the Disable input and whether counting is disabled. When
set, the Disable input is ON and count inputs are ignored.
Home Switch Status
This bit indicates the level of the Home Switch input. When set, the Home Switch input
is ON. The Home Switch is often used in positioning applications to indicate which side,
in reference to a Home Position, or a range close to a Home Position.
GFK-1062A
Chapter 5 Counter Type C
5-17
5
Output Status
These bits indicate the ON or OFF state of the four preset outputs.
Module Ready
This bit is set after the module completes its power-up tests.
Error Status
This bit is set when an error occurs. If it is set, a module status code has been returned in
the first %AI location and the board OK light is flashing. The Error Status bit is cleared
by setting the Clear Error %Q bit.
Preset Interrupt Status
These bits are set by the HSC when the corresponding preset output has changed state,
generating an interrupt. These flags may be used by an interrupt routine to indicate
which counters have generated interrupts. The Output Status bits can be used in
conjunction to determine which transition caused the interrupt. The Preset Interrupt
Status bits should only be tested in a ladder interrupt handler.
%AI Data - Type C Counter
Word
Description
01
Module Status code
02
Counts per timebase for counter 1
03
Not used (set to 0)
04-05
Accumulator for counter 1
06-07
Strobe register 1
08-09
Strobe register 2
10-11
Strobe register 3
12-16
Not used (set to 0)
Module Status Codes
The Module Status Code in the %AI Input Data contains the error code returned to the
PLC. The HSC sets this code to indicate a data command or configuration error. Once
an error code has been returned, no more errors will be generated until the error is
cleared. To clear a module status code, eliminate the condition that caused the error (for
example, clear the %AQ command data, or clear the Home Command %Q bit), and
toggle the Clear Error %Q bit.
Note that fatal errors (RAM, EPROM) have no codes associated with them because these
errors cause the watchdog timer to time out and the board to go into constant reset.
5-18
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
5
The error code format and a list of error codes are given below.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
High Byte
Error Source
Low Byte
Counter or Preset #
Error Code
Error Codes for Type C
Error Code
Error Type
00
No Error
Definition
No Error Present
04
Home Error
11
Unknown Command
21
Invalid Counter or Preset
31
Invalid COMMREQ Task ID
41
Command
81
Errors
Velocity Increment Out of Range
Accumulator Out of Range
91
Preload 1 Value Out of Range
A1
Preload 2 Value Out of Range
A1
Preload 2 Value Out of Range
B1
Home Value Out of Range
C1
Preset On Out of Range
D1
Preset Off Out of Range
12
High Limit < Low Limit
22
Range Excludes Preload 1 Value
32
Limit
Range Excludes Preload 2 Value
42
Errors
Range Excludes Home Value
52
Range Excludes Preset ON
62
Range Excludes Preset OFF
18
High Limit < Low Limit
28
Range Excludes Preload 1 Value
38
Range Excludes Preload 2 Value
48
Range Excludes Home Value
58
Range Excludes Preset ON
68
Configuration
Range Excludes Preset OFF
A8
Errors
Unsupported Feature Error
B8
Unknown Counter Type
C8
PLC Version Error
D8
Logicmaster 90 Version Error
Configuration Errors are not returned in %AI data since the module does not configure,
but the error code is returned in the IO Fault data.
Counter or Preset Number
For a valid command (recognized value in byte 0), the counter or preset number which
generated the error will be reported in this nibble. In counter Type C, the counter
number is always 1. A preset number only appears in error codes C1 and D1.
GFK-1062A
Chapter 5 Counter Type C
5-19
5
Error Source
Command and Limit errors return the source of the error.
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
Value
Example:
Error Source
1
%AQ Command 1 (%AQ Offset 0-2)
2
%AQ Command 2 (%AQ Offset 3-5)
4
COMMREQ Function
If the hexadecimal data 0002 0000 0107 was placed into the %AQ offsets 3 through 5, the
error 2141h would be reported. The Module Status Code represents:
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
Value
2
Error in %AQ Command 2
1
Error generated by counter 1
41
5-20
t
Representation
Velocity Increment Out of Range
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
5
%Q and %AQ Data Sent from CPU to HSC Configured as Type C
Once each I/O scan, the CPU sends eight words of data (32 bits of %Q and six words of
%AQ) to the High Speed Counter Module. The application program can use these
outputs to send commands to the module.
The 32 output bits (%Q) represent:
H
H
H
H
H
H
Reset Strobe flag
Reset Preload flag
Clear error flag
Output enable
Home command
Preload Accumulator
All of this data is transferred from the High Speed Counter to the CPU once per I/O
scan. The I/O scan is active while the CPU is in the RUN mode or STOP ENABLED
mode.
Six Words (%AQ) of Command Data
The 6 words of command data, which can also be sent using a COMMREQ Function
Block, can perform the following operations:
H
H
H
H
H
H
H
H
H
GFK-1062A
Load Accumulator
Load count limits
Load Accumulator increment
Load output preset ON and OFF values
Load Preload
Load time base
Load Oscillator divider
Count Direction
Enable/Disableinterrupts
Chapter 5 Counter Type C
5-21
5
%Q Data - Type C Counter
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
reset strobe 1.1
reset strobe 1.2
reset strobe 1.3
unused
reset preload 1.1
reset preload 1.2
not used
not used
enable output 1.1
enable output 1.2
enable output 1.3
enable output 1.4
not used
home command
clear error
not used
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
accumulator preload 1
accumulator preload 2
reserved
Reset Strobe
Setting this bit clears the corresponding Strobe Status %I bit. In First Strobe mode,
subsequent strobe pulses are ignored until this bit is used to clear the Strobe Status bit.
Reset Preload
This bit is used to clear the corresponding Preload Status %I bit. For example, if a
Preload 2 occurred, the Preload 2 Status %I bit would be set. To clear this bit so future
Preloads can be detected, the Reset Preload 2 %Q bit must transition ON.
Enable Output
These bits enable the corresponding preset output. If cleared, the output will always be
OFF and not reflect the accumulator’s value in relation to the Preset ON and OFF
values.
Home Command
This bit is used to start a Home Cycle. When this bit transitions ON, the Home Switch
and Marker inputs are monitored. When the Home Switch is set and a rising edge
occurs on the Marker input, the Accumulator is set to the Home value and the Home
Found %I bit is set. If the Home Command bit is cleared before the Home Found bit is
set, a Home Error occurs.
Clear Error
This bit should be set by the CPU to clear the Error Status %I bit after the error has been
acknowledged. This bit is rising edge active, so new errors may appear while set.
5-22
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
5
Preload Accumulator
These bits cause the counter to perform a software preload and set the corresponding
Accumulator to the Preload value. The Preload Status bit is not set when a software
preload is performed.
GFK-1062A
Chapter 5 Counter Type C
5-23
5
Data Commands for Counter Type C
The High Speed Counter provides six %AQ words to send data commands from the PLC
to the HSC. The first three words, offsets 0 through 2, make up %AQ command 1, and
the second three words, offsets 3 through 5, make up a completely separate %AQ
command 2. Thus two commands can be sent to the HSC at the end of each sweep.
Note that %AQ command 1 is executed first, so that if identical commands with different
values are sent to the HSC simultaneously, %AQ command 2 data will overwrite %AQ
command 1 data.
Even though the %AQ data is sent each sweep, commands are acted on ONLY if the
command has changed since the last sweep. When any of the 6 bytes in a command
changes, the HSC will accept the data as a new command and respond accordingly.
The DOIO function is supported, so that data can be transferred between the CPU and
HSC mid-sweep. Note that to ensure that the High Speed Counter has time to process
DOIO data sent to it, the application should not change the data more frequently than
every 0.5 millisecond. Because data sent to the HSC is updated at the end of the CPU
sweep, half a millisecond should elapse between the beginning of the sweep and a
DOIO function block, between two DOIO function blocks, and between a DOIO
function block and the end of the sweep.
The COMMREQ function block can also be used to send data commands to the HSC
mid-sweep. COMMREQs must be separated only from each other, and by at least 0.5
milliseconds. A description and example of the use of COMMREQs is given in Appendix A.
%Q data is processed by the HSC before the %AQ data. Therefore commands that can be
affected by %Q bit operations should be sent at least one sweep before the %Q bit
operation. For example, the Load Preload Value command should be sent one sweep before
setting the Preload Accumulator %Q bit to preload that value.
The High Speed Counter will check each command that is sent for validity. If the
command syntax is incorrect, the counter will ignore the command and respond by
flashing the Board Okay LED at 4 Hz, setting the Error Status %I bit, and returning a
status code describing the error in the Module Status %AI word. The Error can be
cleared by toggling the Clear Error %Q bit.
In describing data commands, word offsets are shown in reverse order and in
hexadecimal to simplify data entry. The following example sends a Load Accumulator
Counts command with value 0001 to counter 2 using offsets 0 through 2.
The first word, or command word, which goes into word offset 0 would be 0201h. The
value 01 in byte 0 represents the command Load Accumulator Value. The value 02 in
byte 1 is the counter number, in this case counter 2. For the Load Accumulator Value
command, word 1 is the sixteen bit value to be loaded into the accumulator and word 2
is ignored. In this example, word 1 would have the value 0001h because that is the value
to be placed in the accumulator. Word 2 will be ignored and can be anything, but it is
usually best to use the value 0. If word offset 0 corresponded to %AQ1, the complete
command to load the counter 2 accumulator with value 0001 would be:
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
5-24
%AQ3 (word 2)
%AQ2 (word 1)
%AQ1 (word 0)
0000
0001
0201
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
5
The following table is a list of data commands for counter Type C. Byte 0 data is in
hexadecimal. Note that since there is only one counter, byte 1 always contains value 1
for the counter number.
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
Data
Command Definition
Null
Word 2
Byte 5
Byte 4
xx
Word 1
Byte 3
Byte 2
xx
xx
00h
Load Accumulator Value
data (32)
1
01h
Load High Limit
data (32)
1
02h
1
03h
1
04h
1
06h
1
07h
Load Low Limit
xx
xx
Command Word
Word 0
Byte 1
Byte 0
data (32)
Load AccumulatorIncrement
xx
xx
Load Timebase
xx
xx
Load Velocity
xx
xx
data (8)
data (16)
data (24)
Load Home Value
data (32)
1
08h
Load Preset ON Value
data (32)
m
0Bh
m
0Fh
m
15h
m
19h
Enable/DisablePreset ON Interrupt
xx
xx
xx
xx
Load Preset OFF Value
xx
data (8)
xx
data (8)
data (32)
Enable/DisablePreset OFF Interrupt
Load Preload 1 Value
data (32)
1
1Fh
Load Preload 2 Value
data (32)
1
20h
0
32h
Load Oscillator Divider
xx
xx
data (16)
m = Preset Number (1 to 4);
xx = Do not care (ignored); data (8, 16, 24, 32) = 8, 16, 24, or 32 bit data
Descriptions of each command are given below. The valid range of values is given in
parenthesis.
Null
This is the default %AQ data command. Since the %AQ data is transferred each PLC
sweep, it is a good idea to have the Null command present when not executing a specific
data command to avoid inadvertent execution. All data is ignored with a Null
command.
Load Accumulator Value. (Low Limit to High Limit)
This command places a 32-bit value into a counter accumulator. The value must be
within the Count Limits, or an error will be returned and the command ignored.
Load High Limit.
(–2,147,483,648 to 2,147,483,647)
This command sets the highest value to which a counter will count. Counts that would
cause the counter to go higher are ignored or cause the accumulator to roll over to the
Low Limit depending on whether the counter is configured for Single-shot or
Continuous count mode. The High Limit can be any 32-bit value with the following
restrictions: it must be greater than the Low Limit, the counter’s Preload value must lie
between it and the Low Limit, and all preset outputs which are assigned to the counter
must have preset ON and OFF values which lie between it and the Low Limit. If a
restriction is not met, an error will be generated and the command ignored. If the range
GFK-1062A
Chapter 5 Counter Type C
5-25
5
between the Low Limit and the new High Limit excludes the Accumulator, the
Accumulator will be set to the Low Limit and no error is generated.
Load Low Limit.
(–2,147,483,648 to 2,147,483,6477)
This command sets the lowest value to which a counter will count. Counts that would
cause the counter to go lower are ignored or cause the accumulator to roll over to the
High Limit depending on whether the counter is configured for Single-shot or
Continuous count mode. The Low Limit can be any 32-bit value with the following
restrictions: it must be less than the High Limit, the counter’s Preload value must lie
between it and the High Limit, and all preset outputs which are assigned to the counter
must have preset ON and OFF values which lie between it and the High Limit. If a
restriction is not met, an error will be generated and the command ignored. If the range
between the new Low Limit and the High Limit excludes the Accumulator, the
Accumulator will be set to the Low Limit and no error is generated.
Load Accumulator Increment. (–128 to 127)
The Accumulator Increment performs a one-shot adjustment to the accumulator. Only
byte 2 is used for data, all other data bytes are ignored. The one-shot increment can be
performed at any time, even when counting at maximum rate. If the offset cause the
counter to exceed its limits, the excess is treated just like any other overflow, that is, in
Continuous mode the Accumulator rolls over to the other limit and in Single-shot mode
the Accumulator does not pass the limit.
Load Timebase. (1 to 65535)
This command sets the timebase. The timebase is the number of milliseconds for which
the counter counts input pulses and then returns in the Counts per Timebase register. If
the timebase is 1000, or 1 second, the Counts per Timebase register returns the number
of counts detected in each 1 second period. Any non-zero 16-bit value can be used as the
timebase.
Load Velocity.
(–100,000 to 100,000)
A velocity increment is an internal count generator, or a continuous accumulator
increment. Each millisecond, 0.1% of the increment value is added to the accumulator.
A value of 0 will stop the velocity increment. Counts from the velocity increment are
cumulative with counts coming in from the Count Pulse input. Note that counts
generated by the velocity increment are not reflected in the Counts per Timebase
register.
Load Home Value. (Low Limit to High Limit)
The Load Home command sets the value to which the Accumulator will be set when a
Home Cycle occurs. The value must be between the High and Low Limits or an error
will be returned and the command ignored.
Load ON and OFF Preset Value. (Low Limit to High Limit)
This command sets the preset output turn on and turn off points within a counters
range. Preset values can be any value between the high and low limits.
Enable/Disable Preset ON and OFF Interrupts.
(0=Disable, 1=Enable)
This command enables or disables interrupts resulting from Preset output transitions.
For example, if Preset ON interrupts are enabled, then a low to high transition of the
5-26
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
5
Preset ON output will generate an interrupt to the CPU. This command allows the
interrupts to be enabled or disabled within a ladder.
Load Preload 1 and 2 Value. (Low Limit to High Limit)
The Load Preload command sets the value to which the Accumulator will be set when a
positive edge occurs on the corresponding Preload input. The value must be between
the High and Low Limits or an error will be returned and the command ignored.
Load Oscillator Divider. (1 to 65535)
This command changes the frequency of the square wave oscillator signal. The
frequency generated is 1 megahertz (1 MHz) divided by the oscillator divider. Thus to
get 50 Hz, the oscillator divider should be 20000.
GFK-1062A
Chapter 5 Counter Type C
5-27
Chapter
6 Counter Type D
section level 1
figure bi level 1
table_big level 1
6
Counter Type D is described in this chapter. The description includes counter operation,
configuration of the counter, and the interface between the counter and CPU.
Contents and Operation of a Type D Counter
Overview
The Type D counter contains four 32-bit bidirectional counters. Each counter is
controlled by 3 of the 12 single ended or differential voltage inputs: Count A, Count B,
and Marker. Each counter may be independently configured to count in one of three
modes: Up and Down, Pulse with Direction, and A Quad B. Counter Type D elements
are shown in the figure below.
Each counter has:
H
a 32-bit Accumulator register which counts the pulses from the Count A and Count B
inputs
H
H
a Marker input which is used for setting Home Position
a counts per timebase register which indicates the count rate of the input pulses.
Each of the four 5 to 30 V Preset outputs can be independently assigned to any of the
counters, and can be used to generate PLC interrupts.
a47056
UP OR DOWN COUNTER (32-BIT)
MARKER
HOME VALUE
(32-BIT)
PRESET
OUTPUT
COUNT A
COUNT B
#1
ACCUMULATOR
(32-BIT)
#2
COUNTS PER
TIME BASE
(16-BIT)
ACCUMULATOR
ADJUST
(8-BIT)
#3
#4
GFK-1062A
6-1
6
Count A and B Inputs and Accumulator
The 32-bit Accumulator is incremented or decremented based on a configured
interpretation of its two count inputs. The interpretation can be set to Up/Down,
Pulse/Direction, or A Quad B. Each is Described below.
Operating in UP/DOWN Mode
Up-counting occurs on the low-to-high transition of the Up input. Down counting
occurs on the low-to-high transition of the Down input. The accumulator automatically
tracks the difference between the number of counts received by the Up channel and the
Down channel. Simultaneous inputs on the up channel and down channel will cause a
net accumulator change of zero.
a42973
IN-A UP
IN-B DOWN
COUNT
COUNT UP
ACC
VALUE
COUNT DOWN
N +2
N +1
N
Operating in Pulse/Direction Mode
Counting always occurs on the low-to-high transition of the Pulse input. Count
direction is up for a low level on the Direction input and down for a high level on the
Direction input. Avoid changing the DIR signal coincidentally with the rising edge of the
Pulse input.
a42975
IN-A PULSE
IN-B DIR
COUNT
COUNT UP
COUNT DOWN
ACC N +2
VALUE N +1
N
6-2
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
6
Operating in A Quad B Mode
In A Quad B mode, there are four possible counts for each A Quad B cycle. There are
three A Quad B modes which each return a different number of counts per A Quad B
cycle. The number of counts per cycle and the count direction is given in the table
below:
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
A Quad B x4
A Quad B x2
A Quad B x1
4
2
1
Counts per Cycle
Up Counts generated when:
A leads B,
all edges
A leads B,
A edges
A leads B,
rising A edge
Down Counts generated when:
B leads A,
all edges
B leads A,
A edges
B leads A,
falling A edge
The counts will be evenly spaced with respect to the input waveforms when the phase
relationship between A and B is shifted by 1/4 cycle. The phase relationship between A
and B determines count direction. An example of A Quad B x4 counting is shown in the
following timing diagrams.
The count direction is up if A leads B.
a42977
A
B
COUNT
N+6
ACC
VALUE N
The count direction is down if A lags B.
a42978
A
B
COUNT
ACC
VALUE
N
N –6
Quadrature Error
In any of the A Quad B modes, simultaneous input transitions will generate a
quadrature error. When the quadrature error occurs, the counter continues
accumulating counts normally until the error is cleared. However, preset outputs
assigned to the counter generating the error are set to the configured Output Fail Mode.
When the error is cleared, the outputs resume normal operation. The error code
indicates which Preset(s) have defaulted due to a quadrature error.
GFK-1062A
Chapter 6 Counter Type D
6-3
6
Count Limits
The Accumulator is bounded by a High Limit and a Low Limit. The interaction between
the Accumulator and the limits depends on the configured count mode. In Continuous
mode, the Accumulator will increment or decrement to the current High or Low Limit,
roll over to the other limit, and continue counting. In Single Shot mode, the
Accumulator will count to the current High or Low Limit and stop. If the counter
direction is changed, the Accumulator will count away from the limit until it reaches the
other limit.
The High Limit and Low Limit can be set to any valid 32-bit value at any time using a
data command from the PLC. To be a valid 32-bit value, the following conditions must
be met: the High Limit must be greater than the Low Limit, the Preload value must be
within the High and Low Limit bounds, and any presets pointing to the counter must be
within the High and Low Limit bounds. If the limits are changed so the Accumulator is
outside the limit boundaries, the Accumulator is set to the Low Limit.
Accumulator
The Accumulator may be set to any 32-bit value within the bounds of the High and Low
limits at any time using a data command. Another data command allows the
Accumulator to be adjusted by a byte value, from –128 to +127. Finally, a velocity
increment can be commanded which causes the Accumulator to increment at a fixed
rate.
H
H
H
H
the High Limit must be greater than the Low Limit
the Preload value must be within the High and Low Limit bounds
the Home value must be within the High and Low Limit bounds
any presets assigned to the counter must be within the High and Low Limit bounds.
If the limits are changed so the Accumulator is outside the limit boundaries, the
Accumulator is set to the Low Limit.
The Accumulator can be set to any 32-bit value within the bounds of the High and Low
limits at any time using a data command. Another data command allows the Accumulator
to be adjusted by a byte value, from –128 to +127. Finally, a velocity increment can be
commanded which causes the Accumulator to increment or decrement at a fixed rate.
Preload Value
On the Type D counter, there is no Preload input. A %Q bit can be sent by the PLC to
perform a software preload which sets the accumulator to the Preload Value. The value
to which the Accumulator is set when a preload occurs can be configured to any 32-bit
value within the range of the high and low limits and has a default value of zero. The
Preload value can also be changed using a data command from the PLC.
Marker Input and Home Cycle
The marker input is used to initialize, or home, the counter Accumulator in positioning
applications. It can be thought of as an enabled preload. In order to perform a Home
Cycle, first the Find Home %Q bit must be set. When the Find Home bit is set, the
counter enters the Home Cycle and begins observing the Marker input. On the next
6-4
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
6
positive Marker transition, the Accumulator is set to the Home Value and a Home Found
%I bit is set and returned to the CPU. If the Find Home bit is cleared before a Marker
transition is encountered, a Home error is generated and the Home Cycle is aborted.
When a Home Cycle is not in progress, the Marker input is ignored.
Counts per Timebase Register
The Counts per Timebase register is a 16-bit register which contains the number of
counts received on the Count Pulse input in the last completed timebase interval. It is
used to measure the rate of counting. If more counts are received than can be stored in a
16-bit register, the register will overflow. The timebase interval is a configurable value
from 1 to 65535 milliseconds.
Changes to the timebase will not take effect until after the previous timebase and one
new timebase have elapsed. A Preload will interrupt counting and cause the Counts per
Timebase register to be inaccurate for up to two timebase intervals. The timebase is
initially configured as 1 second, but may be changed using the Logicmaster 90-70
Configurator function or a data command.
As an unsigned number, the Counts per Timebase register will correctly indicate from 0
to 65536 positive counts received per timebase. As a signed number, it will properly
indicate from –32768 to 32767 counts per timebase. The timebase should be selected to
not allow more counts in a timebase than the 16-bit register can hold or it will overflow.
Preset Outputs
The module has four preset outputs, each of which can be assigned to any counter. Each
preset output has a preset ON and preset OFF value, or position, which must be within
the count limits of the counter to which the preset is assigned. The preset ON and OFF
positions determine when the output will be ON or OFF.
Preset closest to low limit
Output ON
Output OFF
ON
> = ON Preset
< = OFF Preset
> OFF Preset
< ON Preset
OFF
< OFF Preset
> ON Preset
< = ON Preset
> = OFF Preset
The output may be either on or off when the accumulator value lies between the Preset
points.
ON
PRESET
OFF
PRESET
a42970
ON CONDITION INCLUDES PRESET POINTS
OFF
PRESET
ON
PRESET
OFF CONDITION INCLUDES PRESET POINTS
GFK-1062A
Chapter 6 Counter Type D
6-5
6
For example:
COUNTS
OFF PRESET
VALUE
ON PRESET
VALUE
CORRESPONDING ON
OUTPUT
OFF
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎÎÎÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ACCUMULATOR
VALUE
a43003
TIME
Separation of Preset Points
The count accumulators are compared to the Presets at 0.5 msec intervals. Therefore, to
guarantee that the outputs will always switch, the Preset points must be separated by at
least the number of counts received in a 0.5 msec time period. For example:
If maximum count rate = 10kHz;
then minimum count separation = (10,000 Hz x .0005 sec) = 5 counts.
Preset Interrupts
Interrupts can be enabled or disabled for each preset output’s ON and OFF transition.
At the same time a preset output changes state, the CPU is interrupted. %I and %AI
data is transferred so that the interrupt routine will see the most current data from the
High Speed Counter. Simultaneous preset changes generate only one interrupt to the
CPU, so the updated %I data must be used by an interrupt routine to determine which
presets changed state and which edge(s) generated the interrupt. Once configured,
interrupts can be independently enabled or disabled using data commands. See
Appendix B for information on using the interrupt capability.
Output Failure Mode
When the CPU is stopped or lost, counter operation continues normally without
interfacing to the CPU. Until the CPU returns or power is cycled, the operation of the
Preset outputs can be configured. In Normal mode, the outputs continue to operate as if
the CPU were present. Outputs will change state to reflect the counter Accumulators.
In Force Off mode, all preset outputs are turned off and remain off until the CPU
returns. In Holdlast mode, the preset outputs retain current levels and do not reflect the
counter Accumulators. If the CPU returns to operation, the outputs will immediately
begin reflecting the counter Accumulators.
The Output Failure mode is applied to preset outputs assigned to an accumulator which
experiences a quadrature error. Normal output operation resumes when the quadrature
error is cleared by toggling the %Q Clear Error bit.
Oscillator Output
The High Speed Counter module generates a 5V square wave oscillator signal. The
oscillator output frequency is determined by the current oscillator divider (set in
configuration or by data command) as indicated below:
Oscillator Frequency (Hz) = 1,000,000 Ï oscillator divider
The output frequency ranges from approximately 15 Hz (oscillator divider of 65535) to 1
MHz (oscillator divider of 1).
6-6
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
6
Table 6-1. Type D Specific Terminal Strip Assignments
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
GFK-1062A
Pin
Signal
Name
Type D
Pin Name
1,3
IN1
COUNT INPUT 1A
Counter 1 count A input
2,4
IN2
COUNT INPUT 1B
Counter 1 count B input
5,7
IN3
COUNT INPUT 2A
Counter 2 count A input
6,8
IN4
COUNT INPUT 2B
Counter 2 count B input
11,13
IN5
COUNTER3A
Counter 3 A input
12,14
IN6
COUNTER 3B
Counter 3 B input
15,17
IN7
COUNTER4A
Counter 4 A input
16,18
IN8
COUNTER 4B
Counter 4 B input
21,23
IN9
MARKER1
Counter 1 marker input
22,24
IN10
MARKER2
Counter 2 marker input
25,27
IN11
MARKER3
Counter 3 marker input
26,28
IN12
MARKER4
Counter 4 marker input
Chapter 6 Counter Type D
Type D
Pin Description
6-7
6
Configuring the Type D High Speed Counter
The following table summarizes all configuration features and default configuration
values for the Type D counter.
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
Configuration
Parameter
Description
Values
Defaults
Failure Mde
Output Failure Mode
NORMAL, OFF, HOLD
NORMAL
Osc Divider
OscillatorDivider
1 ... 65535
1000
Count Thrshlds
Count Input Thresholds
NON-TTL, TTL, MAG-PKUP
NON-TTL
ControlThrshlds
Control Input Thresholds
NON-TTL, TTL
NON-TTL
Count Filtr
Count Input Filter
HIFREQ, LOWFREQ
HIFREQ
Preset CTR#
Preset Accumulator
CTR1 ... CTR4
Preset #
Preset ON
Preset ON setpoint
Low Limit ... High Limit
8,388,607
Preset OFF
Preset OFF setpoint
Low Limit ... High Limit
0
ON Interrupt
Preset on transition interrupt
DISABLED,ENABLED
DISABLED
OFF Interrupt
Preset off transition interrupt DISABLED,ENABLED
DISABLED
Hi Limit
High Count Limit
–2,147,483,648 ... 2,147,483,647
8,388,607
Lo Limit
Low Count Limit
–2,147,483,648 ... 2,147,483,647
0
Count Mode
Count Mode
CONTINU, SINGSHOT
CONTINU
Count Sig
Count Signals
PULSE/DIR,UP/DOWN, A QUAD B X1, PULSE/DIR
A QUAD B X2, A QUAD B X4
Timebase (ms)
Timebase
1 ... 65535 ms
1000 ms
Preld Value
Preload Value
Low Limit ... High Limit
0
Home Value
Home Value
Low Limit ... High Limit
0
Output Failure Mode
When the CPU is stopped or lost, counter operation continues normally; however, the
operation of the Preset outputs can be configured until the CPU returns or power is
cycled. In all modes, the Accumulators are updated and the Strobes and Preloads are
processed normally.
H
In Normal mode (NORMAL), the outputs continue to operate as if the CPU were
present. Outputs will change state to reflect the counter Accumulators.
H
In Force Off mode (OFF), all preset outputs are turned off and remain off until the
CPU returns.
H
In Holdlast mode (HOLD), the preset outputs retain current levels and do not reflect
the counter Accumulators.
If the CPU returns to operation or the module is power-cycled, the outputs will
immediately begin reflecting the counter Accumulators again.
The Output Failure mode is applied to preset outputs assigned to an accumulator which
experiences a quadrature error. Normal output operation resumes when the quadrature
error is cleared by toggling the %Q Clear Error bit.
6-8
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
6
Oscillator Divider
The oscillator divider is used to generate a 5V oscillator output. The output frequency is
1 million divided by the oscillator divider; the formula is shown below.
Oscillator Frequency (Hz) = 1,000,000 / oscillator divider
The output frequency ranges from approximately 15 Hz (oscillator divider of 65535) to 1
MHz (oscillator divider of 1).
Input Thresholds
All inputs can be used as differential or single-ended inputs. The following table
specifies the input thresholds for single-ended and differential use based on threshold
selection and input type. The configuration parameters will set input thresholds
according to the following table:
ÁÁÁÁÁÁÁÁÁ
Á
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
Configuration Parameter
Inputs Controlled
Input Definitions
Counter 1 Threshold
IN1, IN2, 1N9, 1N10
Counter 1 Inputs A, B; Marker 1, 2 Inputs
Counter 2 Threshold
IN3, IN4
Counter 2 Inputs A, B
Controller 3 Threshold
IN5, IN6, IN11, IN12
Counter 3 Inputs A, B; Marker 3, 4 Inputs
Controller 4 Threshold
IN7, IN8
Counter 4 Inputs A, B
All of the inputs controlled by a single selection will have the same voltage threshold.
The only exception is Marker inputs 1 and 2. If the Counter 1 Threshold is set to
Magnetic Pickup, the Marker inputs are set to TTL.
The voltage thresholds which can be selected for each input are described in the
following table.
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
Input Filters
Input Type
Single-Ended
Differential
Non-TTL
TTL
Mag-Pickup
Non-TTL
TTL
Mag-Pickup
Counter 1 Threshold
8V
1.4 V
0.1 V
4.8 V
0.8 V
0.1 V
Counter 2 Threshold
8V
1.4 V
0.1V
4.8 V
0.8 V
0.1V
Controller 3 Threshold
8V
1.4 V
X
4.8 V
0.8 V
X
Controller 4 Threshold
8V
1.4 V
X
4.8 V
0.8 V
X
All inputs default to using a 2.5 microsecond high-frequency filter. The Count inputs for
each counter can be configured to use a 12.5 millisecond low-frequency filter instead.
The low-frequency filter reduces the effects of signal noise. The Marker inputs always
use the high-frequency filter.
Preset Accumulator
The Preset Accumulator field determines which counter a preset output will reflect.
Each of the four preset outputs can be assigned to any of the accumulators. The Preset
ON and Preset OFF values must be within the range of the High and Low Limits of the
counter the Preset Accumulator is assigned to. The default for each Preset is to reflect
the counter of the same number. Thus Preset 1 points to counter 1, Preset 2 points to
counter 2, etc.
GFK-1062A
Chapter 6 Counter Type D
6-9
6
Output Preset ON and OFF Positions
Each counter output has a preset ON and OFF position. The output state indicates
when the counter accumulator value is between the ON and OFF points.
Preset closest to low limit
Output ON
Output OFF
ON
> = ON Preset
< = OFF Preset
> OFF Preset
< ON Preset
OFF
< OFF Preset
> ON Preset
< = ON Preset
> = OFF Preset
The output may be either on or off when the accumulator value lies between the Preset
points.
OFF
PRESET
ON
PRESET
a42970
ON CONDITION INCLUDES PRESET POINTS
OFF
PRESET
ON
PRESET
OFF CONDITION INCLUDES PRESET POINTS
For example:
Location of Preset Points
The Preset points may be located anywhere within the counter range. When the
accumulator value is between the Preset points, the output ON/OFF state will always be
that of the lowest (most negative) Preset point. When the accumulator value is not
between the Preset points, the output ON/OFF state will be that of the most positive
preset. This is true regardless of the counter direction.
The following example compares the output state and accumulator value of a 32-bit
counter when the OFF Preset value is closer to the Low Limit then the ON Preset value.
OUTPUT
COUNTER RANGE
ON
0
OFF
80000000H COUNTER
MINIMUM
LOW
LOW LIMIT
LIMIT
6-10
t
OFF
PRESET
ACCUMULATOR
VALUE
ON
COUNTER
PRESET
HIGH
LIMIT
Series 90 -70 High Speed Counter User’s Manual – November 1995
7FFFFFFFH
MAXIMUM
HIGH LIMIT
GFK-1062A
6
Preset Interrupt Enables
Each preset can generate an interrupt to the CPU. If the Interrupt ON selection is
enabled, then an ON transition of the preset output will generate an interrupt to the
CPU. Similarly, if the Interrupt OFF selection is enabled, an OFF transition of the preset
output will generate an interrupt to the CPU. Thus no edge, either edge, or both edges
of a preset output transition can generate an interrupt. The default is for all interrupts to
be disabled.
Count Limits
Each counter is assigned upper and lower count limits. The upper (high) limit must the
most positive, and the lower limit must be the most negative. Both limits can be positive
or negative, but the high limit must always be greater than the low limit. A counter’s
Accumulator, Preload value, Home value, and any Preset outputs assigned to the
counter must lie within the high and low limits.
If the Accumulator value is outside the new limits when the limits are changed it is
automatically adjusted to the low limit value. If the new limits are incompatible, that is,
(high < low or low > high), then they will be rejected and the old limits retained. In this
case a counter limit error code will be returned. To avoid this situation when the limits
are changed one at a time, a good rule to follow is: always move the high limit first when
shifting the limits up and always move the low limit first when shifting them down.
As a 32-bit counter, the limit range is –2,147,483,648 to 2,147,483,647.
Count Mode
A counter can be configured to count continuously within the count limits, or to count to
a limit and stop.
Continuous Counting
In the continuous counting mode, if either the upper or lower limit is exceeded, the
counter wraps around to the other limit and continues counting. Continuous counting is
the default mode.
Single-Shot Counting
If single-shot is selected, the counter will count to its upper or lower limit, then stop.
When the counter is at the limit, counts in the opposite direction will count it back off
the limit. The Accumulator can also be changed by loading a new value from the CPU or
by applying a Preset Input.
GFK-1062A
Chapter 6 Counter Type D
6-11
6
Count Signal Mode
Each counter can be configured to interpret its Count inputs in one of three ways:
H
Up/Down mode mode - rising edges on the A, or up, input increment the
Accumulator while positive transitions on the B, or down, input decrement the
Accumulator.
H
Pulse/Direction mode - rising edges on the A, or pulse, input are counted. If the B, or
direction, input is low then the Accumulator is incremented but if the Second input
is high then the Accumulator is decremented.
H
A Quad B mode - if the A input leads the B input, the Accumulator is incremented
and if the B input leads the A input the Accumulator is decremented.
Counter Timebase
For each counter, the timebase represents a span of time which can be used to measure
the rate of counting. For example, the program may be required to monitor the number
of count pulses which are occurring every 30 seconds.
A timebase from 1 msec to 65535 msec can be selected for each counter. The counter
timebase is set to 1 second (1000 msec) by default. The module stores the number of
counts that occurred during the last-completed timebase interval in the
Counts/Timebase register. The timebase value selected should not allow the
Counts/Timebase register to overflow at the maximum count frequency.
The timebase counter updates once each timebase period. After power-up, or any
disruption in counting, allow at least one timebase period for the counter to stabilize.
Preload Value
For each counter, a starting, or Preload, value can be specified which will be used when
the Preload input is activated. This Preload value is used for both hardware and
software preloads. If the counter should be reset to zero, enter 0 as the Preload value;
this is the default value. The preload range is –2,147,483,648 to +2,147,483,647, but it
must be within the counter limits.
6-12
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
6
Data Transfer Between High Speed Counter and CPU
The Series 90-70 High Speed Counter updates the %I and %AI data every 0.5
milliseconds. The Series 90-70 CPU reads this data immediately preceding every pass
through the ladder logic, before triggering a ladder interrupt, and when a DOIO
specifically requesting this data is performed in the ladder logic. To support the unique
data coherency requirements of the High Speed Counter, the CPU reads both the %I and
%AI data when performing DOIOs requesting only %I data.
The format of this input data depends on whether the counter is configured as Type A,
Type B, Type C, or Type D. In return, during each I/O scan, the CPU sends 32 bits (%Q)
of control data and 6 words (%AQ) of output data commands to the module.
COMMREQ function blocks in the user program can also be used to send additional
data commands to the module.
See Appendix A for more information about the COMMREQ and DOIO functions.
%I and %AI Data Sent by a Module Configured as Type D
The 32 status bits (%I) represent:
H
H
H
H
H
Home Found flag
Output status
Module ready status
Error status
Interrupt status
These status bits are sent to the CPU as inputs, and can influence outputs sent from the
CPU to the module.
The 16 register data words (%AI) represent:
H
H
H
GFK-1062A
Module Status Code
Counts per Timebase value
Accumulators
Chapter 6 Counter Type D
6-13
6
Status Bits (%I) - Type D Counter
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
home found 1 status
home found 2 status
home found 3 status
home found 4 status
reserved
output 1 status
output 2 status
output 3 status
output 4 status
module ready
not used (always 0)
error
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
reserved
preset interrupt 1 status
preset interrupt 2 status
preset interrupt 3 status
preset interrupt 4 status
reserved
Home Found
This bit indicates the completion of the Home Cycle. It is set on the rising edge of the
Marker input when the Find Home %Q bit is set. When the Find Home %Q bit is
cleared and then set again, the Home Found bit is cleared.
Output Status
These bits indicate the ON or OFF state of the four preset outputs.
Module Ready
This bit is set after the module completes its power-up tests.
Error Status
This bit is set when an error occurs. If it is set, a module status code has been returned in
the first %AI location and the board OK LED flashes at 4 Hz. The Error Status bit is
cleared by setting the Clear Error %Q bit.
Preset Interrupt Status
These bits are set by the High Speed Counter when the corresponding preset output has
changed state and generated an interrupt. These flags can be used by an interrupt
routine to determine which outputs have generated interrupts. The Output Status bits
can be used in conjunction with the Preset Interrupt Status bits to determine which
transition caused the interrupt. The Preset Interrupt Status bits should only be tested in
a ladder logic interrupt handler.
6-14
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
6
%AI Data - Type D Counter
Word
Description
Word
Description
01
Module Status code
06 - 07
Accumulator for counter 1
02
Counts per timebase for counter 1
08 - 09
Accumulator for counter 2
03
Counts per timebase for counter 2
10 - 11
Accumulator for counter 3
04
Counts per timebase for counter 3
12 - 13
Accumulator for counter 4
05
Counts per timebase for counter 4
14 - 16
Not used (set to 0)
Module Status Codes
The Module Status Code in the %AI Input Data contains the error code returned to the
PLC. The HSC sets this code to indicate a data command or configuration error. For all
error codes except quadrature errors, once an error code has been returned, no more
errors will be generated until the error is cleared. Quadrature errors are unlike other
errors in that they are cumulative and the Counter Number will be updated to indicate
additional quadrature errors. To clear a module status code, eliminate the condition that
caused the error, and toggle the Clear Error %Q bit.
Note that fatal errors (RAM, EPROM) have no codes associated with them because these
errors cause the watchdog timer to time out and the board to go into constant reset.
The error code format is given below, followed by a list of error codes on the following
page.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
High Byte
Error Source
Low Byte
Counter or Preset #
Error Code
Error Codes for Type D
Error Code
Error Type
00
No Error
03
04
11
Command
21
Errors
No Error Present
Home Error
Quadrature Error
Unknown Command
Invalid Counter or Preset
31
Invalid COMMREQ task ID
41
Velocity Increment Out of Range
81
Accumulator Out of Range
91
Preload Value Out of Range
B1
Home Value Out of range
C1
Preset ON Out of Range
D1
Preset OFF Out of Range
12
High Limit < Low Limit
22
Limit
Range Excludes Preload
52
Errors
Range Excludes Preset ON
62
GFK-1062A
Definition
Chapter 6 Counter Type D
Range Excludes Preset OFF
6-15
6
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
Error Codes for Type D (continued)
18
High Limit < Low Limit
28
48
Range Excludes Preload Value
Range Excludes Home Value
58
Configuration
Range Excludes Preset ON
68
Errors
Range Excludes Preset OFF
A8
Unsupported Feature Error
B8
Unknown Counter Type
C8
PLC Version Error
D8
Logicmaster 90 Version Error
Configuration Errors are not returned in %AI data since the module does not configure,
but the error code is returned in the IO Fault data.
Counter or Preset Number
For a valid command (recognized value in byte 0), the counter or preset number, from 1
to 4, that generated the error will be reported. A preset number only appears in error
codes C1 and D1.
In the case of the Home and Quadrature Errors, multiple errors could occur at the same
time. Thus each bit represents a counter and the value is the logical OR of these bits.
The following table shows the value for each counter.
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
Value
Counter #
1
1
2
2
4
3
8
4
Thus, a value of 9h (hexadecimal), with the error code 04 would mean both counter 1
and counter 4 had Home Errors occur at the same time.
Error Source
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
Command and Limit errors return the source of the error.
Value
Example:
Error Source
1
%AQ Command 1 (%AQ Offset 0-2)
2
%AQ Command 2 (%AQ Offset 3-5)
4
COMMREQ Function
If the hexadecimal data 0002 0000 0107 was placed into the %AQ offsets 3 through 5, the
error 2141h (hexadecimal) would be reported. The module status code represents:
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
Value
2
Error in %AQ Command 2
1
Error generated by counter 1
41
6-16
t
Representation
Velocity Increment Out of Range
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
6
%Q and %AQ Data Sent from CPU to HSC Configured as Type D
Once each I/O scan, the CPU sends eight words of data (32 bits of %Q and six words of
%AQ) to the High Speed Counter Module. The application program can use these
outputs to control the module.
The 32 output bits (%Q) represent:
H
H
H
H
Home Command
Clear error flag
Output enable
Preload Accumulator
Six Words (%AQ) of Command Data
The 6 words of command data, which can also be sent using a COMMREQ Function
Block, can perform the following operations:
H
H
H
H
H
H
H
H
H
H
Load Accumulator
Load count limits
Load Accumulator increment
Load output preset values
Load Preload value
Load time base
Load Oscillator divider
Set Count Direction
Enable/Disableinterrupts
Load Home value
All of this data is transferred from the High Speed Counter to the CPU once per I/O
scan. The I/O scan is active while the CPU is in the RUN mode or STOP ENABLED
mode.
GFK-1062A
Chapter 6 Counter Type D
6-17
6
%Q Data
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
home command 1
home command 2
home command 3
home command 4
reserved
enable output 1
enable output 2
enable output 3
enable output 4
not used
clear error
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
accumulator preload 1
accumulator preload 2
accumulator preload 3
accumulator preload 4
reserved
Home Command
This bit is used to start a Home Cycle. When this bit transitions ON, the Marker input is
monitored. When a rising edge occurs on the Marker input, the Accumulator is set to the
Home value and the Home Found %I bit is set. If the Home Command bit is cleared
before a Marker transition is encountered, a Home Error occurs.
Enable Output
These bits enable the corresponding preset output. If cleared, the output will always be
OFF and not reflect the accumulator’s value in relation to the Preset ON and OFF
values.
Clear Error
This bit should be set by the CPU to clear the Error Status %I bit after the error has been
acknowledged. This bit is rising edge active, so new errors may appear while set.
Preload Accumulator
These bits tell the counter to perform a software preload and set the corresponding
Accumulator to the Preload value. They do NOT, however, cause the corresponding
Preload Status bit to be set.
6-18
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
6
Data Commands for Counter Type D
At the end of every CPU sweep, six words of %AQ data are automatically transferred
from the CPU to the High Speed Counter. These six words are used to send data
commands from the PLC to the HSC. The first three words, offsets 0 through 2, make up
%AQ command 1, and the second three words, offsets 3 through 5, make up a
completely separate %AQ command 2. Thus two commands can be sent to the HSC at
the end of each sweep. Note that %AQ command 1 is executed first, so that if identical
commands with different values are sent to the HSC simultaneously, %AQ command 2
data will overwrite %AQ command 1 data.
Even though the %AQ data is sent each sweep, commands are acted on ONLY if the
command has changed since the last sweep. When any of the 6 bytes in a command
changes, the HSC will accept the data as a new command and respond accordingly.
The DOIO function is supported, so that data can be transferred between the CPU and
HSC mid-sweep. Note that to ensure that the High Speed Counter has time to process
DOIO data sent to it, the application should not change the data more frequently than
every 0.5 millisecond. Because data sent to the HSC is updated at the end of the CPU
sweep, half a millisecond should elapse between the beginning of the sweep and a
DOIO function block, between two DOIO function blocks, and between a DOIO
function block and the end of the sweep.
The COMMREQ function block can also be used to send data commands to the HSC
mid-sweep. COMMREQs must be separated only from each other, and by at least 0.5
milliseconds. A description and example of the use of COMMREQs and DOIOs is given in
Appendix A.
%Q data is processed by the HSC before the %AQ data. Therefore commands that can be
affected by %Q bit operations should be sent at least one sweep before the %Q bit
operation. For example, the Load Preload Value command should be sent one sweep before
setting the Preload Accumulator %Q bit to preload that value.
In describing data commands, word offsets are shown in reverse order and in
hexadecimal to simplify data entry. The following example sends a Load Accumulator
Counts command with value 0001 to counter 2 using offsets 0 through 2.
The first word, or command word, which goes into word offset 0 would be 0201h. The
value 01 in byte 0 represents the command Load Accumulator Value. The value 02 in
byte 1 is the counter number, in this case counter 2. For the Load Accumulator Value
command, word 1 is the sixteen bit value to be loaded into the accumulator and word 2
is ignored. In this example, word 1 would have the value 0001h because that is the value
to be placed in the accumulator. Word 2 will be ignored and can be anything, but it is
usually best to use the value 0. If word offset 0 corresponded to %AQ1, the complete
command to load the counter 2 accumulator with value 0001 would be:
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
GFK-1062A
%AQ3 (word 2)
%AQ2 (word 1)
%AQ1 (word 0)
0000
0001
0201
Chapter 6 Counter Type D
6-19
6
The following table is a list of data commands for counter Type D. Byte 0 data is given in
hexadecimal.
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
Command Definition
Null
Data
Word 2
Word 1
Byte 5
Byte 4
Byte 3
Byte 2
xx
xx
xx
xx
Command Word
Word 0
Byte 1
Byte 0
xx
00h
Load Accumulator Value
data (32)
n
01h
Load High Limit
data (32)
n
02h
Load Low Limit
data (32)
n
03h
n
04h
n
06h
Load Accumulator Increment
xx
xx
Load Timebase
xx
xx
Load Velocity
xx
xx
data (8)
data (16)
n
07h
Load Home Value
data (32)
m
0Bh
Load Preset ON Value
data (32)
m
0Bh
m
0Fh
m
15h
Enable/Disable Preset ON Interrupt
xx
Load Preset OFF Value
xx
xx
data (8)
data (32)
Enable/Disable Preset OFF Interrupt
xx
Load Preload Value
Load Oscillator Divider
data (24)
xx
xx
data (8)
data (32)
xx
xx
data (16)
m
19h
n
1Fh
0
32h
m = Preset Number (1 to 4); n = Counter Number (1 or 2);
xx = Do not care (ignored); data (8, 16, 24, 32) = 8, 16, 24, or 32 bit data
Descriptions of each command are given below. The valid range of values is given in
parenthesis.
Null
This is the default %AQ data command. Since the %AQ data is transferred each PLC
sweep, it is a good idea to have the Null command present when not executing a specific
data command to avoid inadvertent execution. All data is ignored with a Null
command.
Load Accumulator Value (Low Limit to High Limit)
This command places a 32-bit value into a counter accumulator. The value must be
within the Count Limits, or an error will be returned and the command ignored.
Load High Limit
(–2,147,483,648 to 2,147,483,647)
This command sets the highest value to which a counter will count. Counts that would
cause the counter to go higher are ignored or cause the accumulator to roll over to the
Low Limit depending on whether the counter is configured for Single-shot or
Continuous count mode. The High Limit can be any 32-bit value with the following
restrictions: it must be greater than the Low Limit, the counter’s Preload value must lie
between it and the Low Limit, and all preset outputs which are assigned to the counter
must have preset ON and OFF values which lie between it and the Low Limit. If a
restriction is not met, an error will be generated and the command ignored. If the range
between the Low Limit and the new High Limit excludes the Accumulator, the
Accumulator will be set to the Low Limit and no error is generated.
6-20
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
6
Load Low Limit
(–2,147,483,648 to 2,147,483,6477)
This command sets the lowest value to which a counter will count. Counts that would
cause the counter to go lower are ignored or cause the accumulator to roll over to the
High Limit depending on whether the counter is configured for Single-shot or
Continuous count mode. The Low Limit can be any 32-bit value with the following
restrictions: it must be less than the High Limit, the counter’s Preload value must lie
between it and the High Limit, and all preset outputs which are assigned to the counter
must have preset ON and OFF values which lie between it and the High Limit. If a
restriction is not met, an error will be generated and the command ignored. If the range
between the new Low Limit and the High Limit excludes the Accumulator, the
Accumulator will be set to the Low Limit and no error is generated.
Load Accumulator Increment (–128 to 127 counts)
The Accumulator Increment performs a one-shot adjustment to the accumulator. Only
byte 2 is used for data, all other data bytes are ignored. The one-shot increment may be
performed at any time, even when counting at maximum rate. If the offset cause the
counter to exceed its limits, the excess is treated just like any other overflow, i.e., in
Continuous mode the Accumulator rolls over to the other limit and in Single-shot mode
the Accumulator does not pass the limit.
Load Timebase (1 to 65535 milliseconds)
This command sets the timebase. The timebase is the number of milliseconds for which
the counter counts input pulses and then returns in the Counts per Timebase register. If
the timebase is 1000, or 1 second, the Counts per Timebase register returns the number
of counts detected in each 1 second period. Any non-zero 16-bit value may be used as
the timebase.
Load Velocity (–100,000 to 100,000 counts per second)
A velocity increment is an internal count generator, or a continuous accumulator
increment. Each millisecond, 0.1% of the increment value is added to the accumulator.
A value of 0 will stop the velocity increment. Counts from the velocity increment are
cumulative with counts coming in from the Count Pulse input. Note that counts
generated by the velocity increment are not reflected in the Counts per Timebase
register.
Load Home Value (Low Limit to High Limit)
The Load Home command sets the value to which the Accumulator will be set when a
positive edge occurs on the Marker input while in a Home Cycle. The value must be
between the High and Low Limits or an error will be returned and the command
ignored.
Load ON and OFF Preset Value (Count Limits of the assigned counter)
This command sets the preset output turn on and turn off points within a counters
range. Preset values can be any value between the high and low limits.
GFK-1062A
Chapter 6 Counter Type D
6-21
6
Enable/Disable Preset ON and OFF Interrupts (0=Disable, 1=Enable)
This command enables or disables interrupts resulting from Preset output transitions.
For example, if Preset ON interrupts are enabled, then a low to high transition of the
Preset ON output will generate an interrupt to the CPU. This command allows the
interrupts to be enabled or disabled within a ladder.
Load Preload Value (Low Limit to High Limit)
The Load Preload command sets the value to which the Accumulator will be set when a
positive edge occurs on the Preload input. The value must be between the High and
Low Limits or an error will be returned and the command ignored.
Load Oscillator Divider (1 to 65535)
This command changes the frequency of the square wave oscillator signal. The
frequency generated is 1 megahertz (1 MHz) divided by the oscillator divider. Thus to
get 50 Hz, the oscillator divider should be 20000.
6-22
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
Chapter
7 Counter Type E
section level 1
figure bi level 1
table_big level 1
7
Counter Type E is described in this chapter. The description includes counter operation,
configuration of the counter, and the interface between the counter and CPU.
Contents and Operation of a Type E Counter
Overview
The Type E counter contains two 16-bit bidirectional counters, each of which has a single,
dedicated fast response preset output. Each counter is controlled by 6 of the 12 single
ended or differential voltage inputs: Count A, Count B, Strobe, Strobe Disable, Count
Disable, and Preload. Each counter can be independently configured to count in one of
two modes: Up and Down or A Quad B. The Type E counter supports a maximum
count rate of 200 KHz in Up/Down mode, and 800 KHz in A Quad B mode. Counter
Type E elements are shown in the illustration on the following page.
Each counter has:
H
a 16-bit Accumulator register which counts the pulses from the Count A and Count B
inputs
H
a Fast Preset Output, which will turn on within 10 µS of the Accumulator counting
down to zero
H
H
a Disable input which causes the Accumulator to ignore count pulses.
H
H
a Strobe Disable that causes the counter to ignore strobe pulses
Four Strobe registers which store the Accumulator value when a Strobe input
transitions
a preload value which is inserted into the Accumulator when a preload occurs
In addition to the two Fast Preset Outputs, there are two standard preset outputs that
can be assigned to either accumulator, and have configurable on and off limits.
GFK-1062A
7-1
7
IMPLEMENTED IN HARDWARE
PRELOAD
16 BIT PRELOAD
PRELOAD VALUE
PLC
COUNT PULSE A
CLOCK
COUNT PULSE B
16 BIT
COUNTER
COUNT DISABLE
FAST RESPONSE OUTPUT
PRESET OUTPUT
COUNT = 0
PRESET
ON/OFF
ACCUMULATOR
STROBE
STROBE DISABLE
STROBE REGISTER
STROBE 1 STORAGE
STROBE 2 STORAGE
STROBE VALUES
STROBE 3 STORAGE
STROBE 4 STORAGE
Count A and B Inputs and Accumulator
The 16-bit Accumulator is incremented or decremented based on a configured
interpretation of its two count inputs. The interpretation can be set to Up/Down or A
Quad B. Each is described below.
Operating in UP/DOWN Mode
Up-counting occurs on the low-to-high transition of the Up input. Down counting
occurs on the low-to-high transition of the Down input. The accumulator automatically
tracks the difference between the number of counts received by the Up channel and the
Down channel. Simultaneous inputs on the up channel and down channel will cause a
net accumulator change of zero.
7-2
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
7
a42973
IN-A UP
IN-B DOWN
COUNT
COUNT UP
ACC
VALUE
COUNT DOWN
N +2
N +1
N
Operating in A Quad B Mode
In A Quad B mode, there are four counts for each A Quad B cycle. A count occurs for
each transition of either A or B. The counts will be evenly spaced with respect to the
input waveforms when the phase relationship between A and B is shifted by 1/4 cycle.
The phase relationship between A and B determines count direction, as shown in the
following timing diagrams.
The count direction is up if A leads B.
a42977
A
B
COUNT
N+6
ACC
VALUE N
The count direction is down if A lags B.
a42978
A
B
COUNT
ACC
VALUE
N
N –6
The Type E is designed primarily as a down counter, operating between the configured
Preload value and zero. When the Accumulator counts down to zero, the associated Fast
Preset Output will turn on. If configured for Continuous counting, the Accumulator will
automatically Preload itself when the Accumulator decrements to 0 and continue
GFK-1062A
Chapter 7 Counter Type E
7-3
7
counting. If configured for Single Shot operation, the Accumulator will count down to
zero and stay there until it receives a Preload. Although primarily designed for
down-counting, up counting is supported to accommodate momentary up counts (such
as jitter on an A Quad B input). The preset output is not energized if the counter counts
up from 65,535 and rolls over to 0.
In the Type E counter, the count limits are effectively defined by the Preload value and
zero. The Preload value can be set to any unsigned 16-bit value at any time using a data
command from the PLC. The new Preload value will not affect counting until the
counter is preloaded or decrements to zero in continuous mode.
At power-up the accumulators are initialized to the configured preload value.
Strobe Inputs and the Strobe Event Stack
Each Strobe input is an edge sensitive input which can be configured to respond to a
positive edge, negative edge, or both positive and negative edges. Each counter has a
four register Strobe Event Stack. When the configured Strobe input transition occurs,
called a Strobe Pulse, the value in the Accumulator is stored in the first available register
in the Strobe Stack, and the corresponding strobe flag is set and returned in %I data to
indicate the event to the CPU. Subsequent strobes are captured and reported in a
similar manner until the stack is full. The CPU acknowledges strobes by toggling the
Reset Strobes %Q bit, which resets all the strobe bits and enables four more strobes. The
minimum interval between successive strobes is .5 milliseconds.
Preloading the accumulator will automatically reset the Strobe Stack. If the counter is
configured for Continuous counting, the strobe stack will automatically be reset and all four
strobe flags cleared when the counter decrements to 0 and performs the automatic preload.
If a Strobe occurs within .5 milliseconds of a preload, the strobed value will be stored in
the first available Strobe Stack entry, however it is possible that the strobe status will be
reset before the strobe status %Q bit has been transferred to the CPU.
Preload Input and Value
Each counter has a 16-bit preload register which is used to initialize the counter when a
preload input is detected, when the PLC %Q preload bit has been set, or when the
counter decrements to zero in continuous mode. The value to which the Accumulator is
set when a preload occurs can be configured to any non-zero unsigned 16-bit value, and
has a default value of 1000. The Preload value can also be changed using a data
command from the PLC. The Preload input is positive edge sensitive only. Likewise, the
%Q preload bit will only cause a preload when the bit transitions from an off to an on
state. The preload flag is set and returned in %I data any time that the counter
decrements to zero in continuous mode or a positive transition occurs on the Preload
input. If an application program uses this flag indication, it should use the
corresponding %Q bit to clear the preload flag before the next preload occurs. A rising
edge on the Preload input or a %Q off-to-on transition always preloads the
Accumulator regardless of the state of the Preload flag.
Preset Outputs (Fast Response)
Each counter has one fast response output that turns on within 15 microseconds of the
counter decrementing to 0. A PLC interrupt can be enabled to occur for each On
transition. In addition, each counter module supports two standard response (0.5
millisecond) outputs which can be assigned to either counter.
7-4
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
7
Output operation in Single Shot Counter Mode
The output will have two configuration modes, Latched and Pulse.
In the Latched mode, the preset output turns on when the counter counts to 0 and
remains on until a Preload occurs. A Preload will turn the output off and it will remain
off until the counter counts to 0 as illustrated below:
Counter Mode = Single Shot
Output Mode
= Latched
Preload Value = 5
COUNTS
COUNTER VALUE
^
4
^
3
^
2
^
1
^
0
^
^ ^ ^ ^ ^
^ ^ ^ ^ ^ ^
0/5 4 3 2 1 0 0 0 0/5 4 3
0
FAST OUTPUT
PRELOAD INPUT
In the Pulse mode the preset output turns on when the counter counts to 0, and remains
on for a duration configured by the user. The configured pulse duration can be 1
millisecond to 1 second with 1 millisecond resolution. Operation in this mode is
illustrated below:
Counter Mode = Single Shot
Preload Value = 5
Output Mode
= Pulsed
Pulse Length = 10 ms
COUNTS
COUNTER VALUE
^
4
^
3
^
2
^
1
^
0
^
0
^
^ ^ ^ ^
^ ^ ^ ^ ^ ^
0 0 0 0 0 0 0/5 4 3 2 1
10 ms
FAST OUTPUT
PRELOAD INPUT
Output operation in Continuous Counter Mode
In Continuous Mode, only the output pulse mode is applicable . When the counter
counts down to 0, the output will pulse on for the configured pulse length time.
Operation in the Continuous Mode is illustrated below:
Counter Mode = Continuous
Preload Value = 5
Output Mode
Pulse Length = 10 ms
= Pulsed
COUNTS
COUNTER VALUE
^
4
^
^
^ ^ ^
^ ^ ^ ^ ^
^ ^ ^ ^ ^ ^
3 2/5 4 3 2 1 0/5 4 3 2 1 0/5 4 3 2 1
10 ms
FAST OUTPUT
10 ms
PRELOAD INPUT
Note
When configured for continuous counting with pulsed outputs, the
configured pulse duration must be at least .75 milliseconds less than the
time required to count from the preload down to zero. This is to ensure
that the pulse has had time to turn off before it is set again.
GFK-1062A
Chapter 7 Counter Type E
7-5
7
Preset Outputs (Standard)
The module has two standard preset outputs, each of which can be assigned to either
counter or disabled. When enabled, each preset output has a 16-bit preset ON and
preset OFF value. The preset ON and OFF positions determine when the output will be
ON or OFF as shown below.
Preset closest to Zero
Output ON
Output OFF
ON
> = ON Preset
< = OFF Preset
> OFF Preset
< ON Preset
OFF
< OFF Preset
> ON Preset
< = ON Preset
> = OFF Preset
The output may be either on or off when the accumulator value lies between the Preset
points.
OFF
PRESET
ON
PRESET
a42970
ON CONDITION INCLUDES PRESET POINTS
OFF
PRESET
ON
PRESET
OFF CONDITION INCLUDES PRESET POINTS
For example:
COUNTS
OFF PRESET
VALUE
ON PRESET
VALUE
CORRESPONDING ON
OUTPUT
OFF
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎÎÎÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ACCUMULATOR
VALUE
a43003
TIME
Separation of Preset Points
The count accumulators are compared to the Presets at 0.5 millisecond intervals.
Therefore, to guarantee that the outputs will always switch, the Preset points must be
separated by at least the number of counts received in a 0.5 millisecond time period. For
example:
If maximum count rate = 10KHz;
then minimum count separation = (10,000 Hz x .0005 sec) = 5 counts.
Preset Interrupts
The Fast Preset Outputs support preset ON transition interrupts only. The Standard
Preset Outputs interrupts can be enabled or disabled for each preset output’s ON and
7-6
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
7
OFF transition. At the same time a preset output changes state the CPU is interrupted
and the corresponding %I and %AI data is automatically transferred so that an interrupt
routine will see the current data from the High Speed Counter. The interrupt handler
routine can determine which preset transition occurred and which edge generated the
interrupt by examining the %I data. Simultaneous transitions on multiple presets will
generate a single interrupt to the CPU. Interrupt enables are configurable, with the
default being disabled, and can be changed via data commands. See Appendix B for
information on using the interrupt capability.
Output Failure Mode
When the CPU is stopped or lost, counter operation continues normally without
interfacing to the CPU. The operation of the Preset outputs until the CPU returns to run
mode or power is cycled can be configured. In Normal mode, the outputs continue to
operate as if the CPU were present. Outputs will change state to reflect the count
Accumulators. In Force Off mode, all preset outputs are turned off and remain off until
the CPU returns. In Holdlast mode, the preset outputs retain current levels and do not
reflect the counter Accumulators. If the CPU returns to operation, the outputs will
immediately resume reflecting the counter Accumulators.
GFK-1062A
Chapter 7 Counter Type E
7-7
7
Oscillator Output
The High Speed Counter module generates a 5V square wave oscillator signal. The
oscillator output frequency is determined by the current oscillator divider (set in
configuration or by data command) as indicated below:
Oscillator Frequency (Hz) = 1,000,000 Ï oscillator divider
The output frequency ranges from approximately 15 Hz (oscillator divider of 65535) to 1
MHz (oscillator divider of 1).
Table 7-1. Type E Specific Terminal Strip Assignments
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁ
Pin
7-8
Signal
Name
Type E
Pin Name
Type E
Pin Description
1,3
IN1
COUNT INPUT 1A
Counter 1 count A input
2,4
IN2
COUNT INPUT 1B
Counter 1 count B input
5,7
IN3
COUNT INPUT 2A
Counter 2 count A input
6,8
IN4
COUNT INPUT 2B
Counter 2 count B input
11,13
IN5
CTR 1 PRELOAD
Counter 1 preload input
12,14
IN6
CTR 1 DISABLE
Counter 1 disable input
15,17
IN7
CTR 2 PRELOAD
Counter 2 preload input
16,18
IN8
CTR 2 DISABLE
Counter 2 disable input
21,23
IN9
CTR 1 STROBE
Counter 1 strobe 1 input
22,24
IN10
CTR 1 STROBE DISABLE
Counter 1 strobe disable input
25,27
IN11
CTR 2 STROBE
Counter 2 strobe input
26,28
IN12
CTR 2 STROBE DISABLE
Counter 2 strobe disable input
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
7
Configuring the Type E High Speed Counter
The following table summarizes all configuration features and default configuration
values for the Type E counter.
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
Configuration
Parameter
Description
Values
Default
Failure Mde
Output Failure Mode
NORMAL, OFF, HOLD
NORMAL
Osc Divider
OscillatorDivider
1 ... 65535
1000
Count Thrshlds
Count Input Thresholds
NON-TTL, TTL, MAG-PKUP
NON-TTL
ControlThrshlds
Control Input Thresholds
NON-TTL, TTL
NON-TTL
Count Filtr
Count Input Filter
HIFREQ, LOWFREQ
HIFREQ
Preld Filtr
Preload Input Filter
HIFREQ, LOWFREQ
HIFREQ
Cnt Disbl Filtr
Disable Input Filter
HIFREQ, LOWFREQ
HIFREQ
Output Mode
Fast Preset Outpurt Mode
LATCHED, PULSE
PULSE
Outpulse ms
Fast Preset Output Pulse
Duration (Pulse Mode Only)
1 ... 1000
10
* Preset CTR#
Preset Accumulator
CTR1, CTR2, DISABLE
** St. Preset #
* On
Preset ON setpoint
Low Limit ... High Limit
65535
* Off
Preset OFF setpoint
Low Limit ... High Limit
0
Interrupt ON
Preset on transition interrupt
DISABLED,ENABLED
DISABLED
* Interrupt OFF
Preset off transition interrupt DISABLED,ENABLED
DISABLED
Count Mode
Count Mode
CONTINU, SINGSHOT
CONTINU
Count Sig
Count Signals
UP, DOWN, A QUAD B
UP/DOWN
Preld Value
Preload Value
0 ... 65535
1000
Strobe Edge
Strobe Edge
POS, NEG, BOTH
POS
* These items apply to the standard preset outputs (outputs 3 and 4) only.
** Counter 1 is the default counter for output 3, counter 2 is the default counter for output 4.
Output Failure Mode
When the CPU is stopped or lost, counter operation continues normally without
interfacing to the CPU. Until the CPU returns or power is cycled, the operation of the
Preset outputs can be configured. In all modes, the Accumulators are updated and the
Strobes and Preloads are processed.
H
In Normal mode (NORMAL), the outputs continue to operate as if the CPU were
present. Outputs will change state to reflect the counter Accumulators.
H
In Force Off mode (OFF), all preset outputs are turned off and remain off until the
CPU returns.
H
In Holdlast mode (HOLD), the preset outputs retain current levels and do not reflect
the counter Accumulators.
If the CPU returns to operation or the module is power-cycled, the outputs will
immediately begin reflecting the counter Accumulators again.
GFK-1062A
Chapter 7 Counter Type E
7-9
7
Oscillator Divider
The oscillator divider is used to generate a 5V oscillator output. The output frequency is
1 million divided by the oscillator divider; the formula is shown below.
Oscillator Frequency (Hz) = 1,000,000 Ï oscillator divider
The output frequency ranges from approximately 15 Hz (oscillator divider of 65535) to 1
MHz (oscillator divider of 1).
Input Thresholds
All inputs can be used as differential or single-ended inputs. The following table
specifies the input thresholds for single-ended and differential use based on threshold
selection and input type. Non-TTL is the default for all inputs.
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
Configuration Parameter
Inputs Controlled
Input Definitions
Count Threshold 1
IN1, IN2
Counter 1, Inputs A, B
Count Threshold 2
IN3, IN4
Counter 2, Inputs A, B
Control Threshold 1
IN5, IN6, IN9, IN10
Ctr 1 Preload, Count Disable,
Strobe, Strobe Disable
Control Threshold 2
IN7, IN8, IN11, IN12
Ctr 2 Preload, Count Disable,
Strobe, Strobe Disable
Note that all the inputs controlled will have the same voltage threshold.
The voltage thresholds which can be selected for each input are described in the
following table.
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
Input Type
Single-Ended
Differential
Non-TTL
TTL
Mag-Pickup
Non-TTL
TTL
Mag-Pickup
Count Threshold 1
8V
1.4 V
0.1 V
4.8 V
0.8 V
0.1 V
Count Threshold 2
8V
1.4 V
0.1V
4.8 V
0.8 V
0.1V
Control Threshold 1
8V
1.4 V
X
4.8 V
0.8 V
X
Control Threshold 2
8V
1.4 V
X
4.8 V
0.8 V
X
Only the Count inputs can be configured for Magnetic Pickup thresholds.
Input Filters
All inputs default to using a 2.5 microsecond high-frequency filter. Each Count, Preload,
and Disable input can be configured to use a 12.5 millisecond low-frequency filter
instead. The low-frequency filter reduces the effects of signal noise. The Strobe inputs
always use the high-frequency filter.
Output Mode
The Fast Preset Outputs can be configured for two modes of operation. In Pulse mode,
the presets will turn on when the counter decrements to zero, and stay on for the
duration configured by the Outpulse mS parameter. In Latched mode, the preset will
remain on until the counter is preloaded using either a software or terminal strip
preload.
7-10
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
7
Outpulse Milliseconds
When a Fast Preset Output mode is configured in pulse mode, this parameter is used to
program the duration that the output will remain on.
Note
When configured for continuous counting with pulsed outputs, the
configured pulse duration must be at least .75 milliseconds less than the
time required to count from the preload down to zero. This is to ensure
that the output has had time to turn off before being set again.
Preset Accumulator
The Preset Accumulator field determines which counter a preset output will reflect. The
two standard preset outputs can be configured to reference to either . The default
configuration references Preset 3 to counter 1, and Preset 4 to counter 2.
Standard Preset Output ON and OFF Positions
Each of the standard preset outputs has an ON and OFF preset value.
OFF
PRESET
ON
PRESET
a42970
ON CONDITION INCLUDES PRESET POINTS
OFF
PRESET
ON
PRESET
OFF CONDITION INCLUDES PRESET POINTS
Location of Preset Points
Preset points may be located anywhere within the overall 0 to 65535 counting range.
When the accumulator value is between the Preset points, the output ON/OFF state will
always be that of the lowest Preset point. When the accumulator value is not between
the Preset points, the output ON/OFF state will be that of the most positive preset. This
is true regardless of the counter direction.
OUTPUT
COUNTER RANGE
ON
OFF
0
GFK-1062A
OFF
PRESET
Chapter 7 Counter Type E
ACCUMULATOR
VALUE
ON
PRESET
PRELOAD
VALUE
FFFFH
7-11
7
Interrupt on Preset ON and OFF Transitions
Each of the Preset Outputs has the capability to generate a ladder interrupt if this
function is enabled in the configuration. For the Fast Preset Outputs interrupts may be
enabled for the ON transition only. The Standard Preset Outputs interrupts can be
enabled for either transition. Interrupts are disabled by default.
Count Mode
A counter can be configured to count continuously, automatically preloading when it
reaches zero, or to count down to zero and stop.
Continuous counting
In continuous counting mode, the counter will automatically reload itself with the
configured preload value when it reaches zero, and continue counting down.
Single-Shot counting
In Single-Shot mode, the counter will stop when it decrements to zero. Counting is
enabled again when the counter is preloaded either by a %Q Preload Accumulator pulse
or a pulse on the preload input.
Count Signal Mode
Each counter can be configured to interpret its Count inputs in one of two ways:
H
Up/Down mode - rising edges on the A, or up, input increment the Accumulator
while positive transitions on the B, or down, input decrement the Accumulator.
H
A Quad B mode - if the A input leads the B input, the Accumulator is incremented
and if the B input leads the A input the Accumulator is decremented.
Preload Value
For each counter, a starting, or Preload, value can be specified which will be used when
the Preload input is activated. This Preload value is used for both hardware and
software preloads. If the counter should be reset to 1000, use 1000 as the Preload value;
this is the default value. The preload range is 1 to 65535.
Strobe Edge
Strobe inputs are edge sensitive. Each Strobe input on the module can be individually
configured to have either the positive, negative, or both edges active. By default, they
are positive edge sensitive.
7-12
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
7
Data Transfer Between High Speed Counter and CPU
The Series 90-70 High Speed Counter updates the %I and %AI data every 0.5
milliseconds. The Series 90-70 CPU reads this data immediately preceding each pass
through the ladder logic, before triggering a ladder interrupt, and when a DOIO
specifically requesting this data is performed in the ladder. To support the unique data
coherency requirements of the High Speed Counter, the CPU reads both the %I and %AI
data when performing a DOIO requesting only %I data.
The format of this input data depends on the counter configuration type. In return,
during each I/O scan, the CPU sends 32 bits (%Q) of control data and 6 words (%AQ) of
output data commands to the module. COMMREQ function blocks in the user program
can be used to send additional data commands to the module.
See Appendix A for more information about COMMREQ and DOIO function blocks.
%I and %AI Data Sent by a Module Configured as Type E
The 32 status bits (%I) represent:
H
H
H
H
H
H
H
Strobe status flags
Strobe disable input status
Count Disable input status
Preload status
Module ready status
Error status
Interrupt status
These status bits are sent to the CPU as inputs, and can influence outputs sent from the
CPU to the module.
The 16 register data words (%AI) represent:
H
H
H
GFK-1062A
Accumulators
Strobes
Module status code
Chapter 7 Counter Type E
7-13
7
Status Bits (%I) - Type E Counter
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
strobe 1.1 flag
strobe 1.2 flag
strobe 1.3 flag
strobe 1.4 flag
strobe 1 disable
disable 1 status
always off
preload 1 status
output 1 status
output 2 status
output 3 status
output 4 status
module ready
always off
error
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
strobe 2.1 flag
strobe 2.2 flag
strobe 2.3 flag
strobe 2.4 flag
strobe 2 disable
disable 2 status
always off
preload 2 status
preset 1 interrupt status
preset 2 interrupt status
preset 3 interrupt status
preset 4 interrupt status
always off
Strobe Status
Each bit indicates when a Strobe Pulse occurs on the counter. Each successive strobe
causes the accumulator to be strobed into successive strobe registers, setting the
corresponding strobe bit. If an application program uses these bits, it may clear them by
setting the corresponding Reset Strobe %Q bit. The strobe status bits are reset
automatically when the counter is preloaded by either a %Q or user input preload, or if
the accumulator decrements to zero in continuous counting mode.
Strobe Disable Status
This bit indicates the level of the Strobe Disable input and whether strobing is disabled.
When set, the Strobe Disable input is ON and strobe inputs are ignored.
Disable Status
This bit indicates the level of the Disable input and whether counting is disabled. When
set, the Disable input is ON and count inputs are ignored.
Preload Status
This bit indicates that the counter has been preloaded by the terminal strip input, or that
it has rolled-under in continuous mode. It is not set after a user has performed a %Q
7-14
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
7
preload. If an application program uses these bits, it may clear them by setting the
corresponding Reset Preload %Q bit.
Output Status
These bits indicate the ON or OFF state of the four preset outputs.
Module Ready
This bit is set after the module completes its power-up tests.
Error Status
This bit is set when an error occurs. If it is set, a module status code has been returned in
the first %AI location and the board OK LED flashes at 4 Hz. The Error Status bit is
cleared by setting the Clear Error %Q bit.
Preset Interrupt Status
These bits are set by the HSC when the corresponding preset output has changed state,
generating an interrupt. These flags may be used by an interrupt routine to indicate
which counters have generated interrupts. The Output Status bits can be used in
conjunction to determine which transition caused the interrupt. The Preset Interrupt
Status bits should only be tested in a ladder interrupt handler.
%AI Data - Type E Counter
Word
Description
1
Module Status code
2
Accumulator for counter 1
3
Strobe 1 for counter 1
4
Strobe 2 for counter 1
5
Strobe 3 for counter 1
6
Strobe 4 for counter 1
7
Accumulator for counter 2
8
Strobe 1 for counter 2
9
Strobe 2 for counter 2
10
Strobe 3 for counter 2
11
Strobe 4 for counter 2
12 - 16
Unused
Module Status Codes
The Module Status Code in the %AI Input Data contains the error code returned to the
PLC. The HSC sets this code to indicate a data command or configuration error. Once
an error code has been returned, no more errors will be generated until the error is
cleared. To clear a module status code, eliminate the condition that caused the error, and
toggle the Clear Error %Q bit.
GFK-1062A
Chapter 7 Counter Type E
7-15
7
The Error code format and a list of error codes are given below.
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
High Byte
Error Source
Low Byte
Counter or Preset #
Error Code
Error Codes for Type E Counter
Error Code
Error Type
00
No error
11
Definition
No Error Present
Unknown Command
21
Command
31
Errors
51
Invalid Counter or Preset
Invalid COMMREQ task ID
Outpulse ms out of range
98
Outpulse ms out of range
A8
Configuration
B8
Errors
Unsupported Feature Error
Unknown Counter Type
C8
PLC Version Error
D8
Logicmaster 90 Version Error
Configuration Errors are not returned in %AI data since the module does not configure,
but the error code is returned in the IO Fault data. The error data may be accessed by
highlighting the fault in the I/O Fault Table and pressing the Control and F keys
simultaneously.
Counter or Preset Number
For a valid command (recognized value in byte 0), the counter (1 or 2) or preset number,
1 to 4, which generated the error will be reported in this nibble. The Set Preset
Accumulator command requires a valid preset and counter number or this value will be
zero.
Error Source
Command errors return the source of the error.
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
Value
Example:
Error Source
1
%AQ Command 1 (%AQ Offset 0-2)
2
%AQ Command 2 (%AQ Offset 3-5)
4
COMMREQ Function
If the hexadecimal data 030A 0003 0000 was placed into the %AQ offsets 3 through 5 to
try and set preset 3 to Counter 3, the error 2021h would be reported. The Module Status
Code represents:
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
Value
7-16
t
Representation
2
Error in %AQ Command 2
0
Unknown Counter
21
Invalid Counter or Preset
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
7
%Q and %AQ Data Sent from CPU to HSC Configured as Type E
Once each I/O scan, the CPU sends eight words of data (32 bits of %Q and six words of
%AQ) to the High Speed Counter Module. The application program can use these
outputs to send commands to the module.
The 32 output bits (%Q) represent:
H
H
H
H
H
Reset Strobes flag
Accumulator Preload
Reset Preload flag
Output Enable
Clear error
Six words (%AQ) of Command Data
The 6 words of command data, which can also be sent using a COMMREQ Function
Block, can perform the following operations:
H
H
H
H
H
H
Load Outpulse duration
Set Preset Accumulators
Load output preset on and off values
Enable/Disable preset interrupts
Load Preload values
Load Oscillator divider
%Q Data - Type E Counter
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
reset strobe 1
reserved
preload accumulator 1
reset preload 1
enable output 1
enable output 2
enable output 3
enable output 4
reserved
clear error
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
reset strobe 2
reserved
preload accumulator 2
reset preload 2
reserved
Reset Strobe flag
This flag resets all the Strobe Status %I flags and allows up to four more strobes to be
captured in the Strobe Stack. In the Type E, this bit is rising edge active, so new strobes
can be captured while it is set.
GFK-1062A
Chapter 7 Counter Type E
7-17
7
Preload Accumulator
These bits tell the counter to perform a software preload and set the corresponding
Accumulator to the Preload value. They do NOT, however, cause the corresponding
Preload Status bit to be set.
Note
If a Strobe occurs between the time that a %Q Software Preload bit is set
and when it is actually serviced by the counter, the Strobe value will be
stored in the first available Strobe register, however the counter will
reset the %I Strobe Status flags when it services the %Q Preload.
Reset Preload
This bit is used to clear the corresponding Preload Status %I bit. For example, if a
Preload occurred, the Preload Status %I bit would be set. To clear this bit so future
Preloads can be detected, the Reset Preload %Q bit must transition ON.
Clear Error
This bit should be set by the CPU to clear the Error Status %I bit after the error has been
acknowledged. This bit is rising edge active, so new errors may appear while set.
Enable Output
These bits enable the corresponding preset output. If cleared, the output will always be
OFF and not reflect the accumulator’s value in relation to the Preset ON and OFF
values.
7-18
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
7
Data Commands for Type E Counter
At the end of every CPU sweep, six words of %AQ data are automatically transferred
from the CPU to the High Speed Counter. These six words are used to send data
commands from the PLC to the HSC. The first three words, offsets 0 through 2, make up
%AQ command 1, and the second three words, offsets 3 through 5, make up a
completely separate %AQ command 2. Thus two commands can be sent to the HSC at
the end of each sweep. Note that %AQ command 1 is executed first, so that if identical
commands with different values are sent to the HSC simultaneously, %AQ command 2
data will overwrite %AQ command 1 data.
Even though the %AQ data is sent each sweep, commands are acted on ONLY if the
command has changed since the last sweep. When any of the 6 bytes in a command
changes, the HSC will accept the data as a new command and respond accordingly.
The DOIO function is supported, so that %AQ commands can be sent to the HSC
mid-sweep. However, there must be 0.5 ms between a DOIO and the beginning or end
of the sweep and between two DOIOs. This is to guarantee that the HSC has time to
process each command before the data is overwritten by a subsequent command.
The COMMREQ function block can also be used to send data commands to the HSC
mid-sweep. COMMREQs must be separated only from each other, and by at least 0.5
milliseconds. A description and example of the use of COMMREQs and DOIOs is given
in Appendix A.
%Q data is processed by the HSC before the %AQ data. Therefore commands that can be
affected by %Q bit operations should be sent at least one sweep before the %Q bit
operation. For example, the Load Preload Value command should be sent one sweep before
setting the Preload Accumulator %Q bit to preload that value.
In describing data commands, word offsets are shown in reverse order and in
hexadecimal to simplify data entry. The following example sends Load Outpulse ms
command with value 500 to counter 2 using offsets 0 through 2.
The first word, or command word, which goes into word offset 0 would be 0209h. The
value 09 in byte 0 represents the command Load Outpulse ms command. The value 02
in byte 1 is the counter number, in this case counter 2. For the Load Outpulse ms
command, word 1 is the value to be configured and word 2 is ignored. In this example,
word 1 would have the value 500 (1F4h) because that is the value to be configured.
Word 2 will be ignored but should be set to 0. If word offset 0 corresponded to %AQ1,
the complete command to load the counter 2 accumulator with value 0001 would be:
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
GFK-1062A
%AQ3 (word 2)
%AQ2 (word 1)
%AQ1 (word 0)
0000
01F4
0209
Chapter 7 Counter Type E
7-19
7
The following table is a list of data commands for counter Type E. Byte 0 data is in
hexadecimal format.
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
Data
Command Definition
Word 2
Byte 5
Byte 4
Null
xx
xx
Load Outpulse ms
xx
xx
Set Preset Accumulator
xx
xx
Load Preset ON Value
xx
xx
Enable/Disable Preset ON Interrupt
xx
xx
Load Preset OFF Value
xx
xx
Enable/Disable Preset OFF Interrupt
xx
xx
Load Preload Value
xx
xx
Load Oscillator Divider
xx
xx
Word 1
Byte 3
Byte 2
xx
Command Word
Word 0
Byte 1
Byte 0
xx
xx
00h
n
09h
k
0Ah
k
0Bh
m
0Fh
k
15h
k
19h
data (16)
n
1Fh
data (16)
0
32h
data (16)
xx
data (8)
data (16)
xx
data (8)
data (16)
xx
data (8)
k = Preset Number (3, 4); m = Preset Number (1 to 4); n = Counter Number (1, 2);
xx = Do not care (ignored); data (8, 16, 24) = 8, 16, or 24 bit data
Descriptions of each command are given below. The valid range of values is given in
parenthesis.
Null
This is the default %AQ data command. Since the %AQ data is transferred each PLC
sweep, it is a good idea to have the Null command present when not executing a specific
data command to avoid inadvertent execution. All data is ignored with a Null
command.
Load Outpulse ms (1 to 1000)
This command sets the fast preset output pulse duration when configured for pulse
mode operation. The value must be in the range of 1 to 1000, or an error will be returned
and the command ignored.
Note
When configured for continuous counting with pulsed outputs, the
configured pulse duration must be at least .75 milliseconds less than the
time required to count from the preload down to zero. This is to ensure
that the output has had time to turn off before being set again.
Preset Accumulator (0, 1 or 2, presets 3 and 4 only)
This command sets the accumulator referenced by the standard preset outputs. A data
value of 0 disables the corresponding output.
Load ON and OFF Preset Value (0 to 65535, presets 3 and 4 only)
This command sets the preset output turn on and turn off points. Preset values can be
any value in the range of 0 to 65535.
7-20
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
7
Enable/Disable Preset ON and OFF Interrupts.
(0=Disable, 1=Enable)
This command enables or disables interrupts resulting from Preset output transitions.
For example, if Preset ON interrupts are enabled, then a low to high transition of the
Preset ON output will generate an interrupt to the CPU. This command allows the
interrupts to be enabled or disabled within a ladder. The OFF interrupt is only
supported by the standard preset outputs (3 and 4).
Load Preload Value (1 to 65535)
The Load Preload command sets the value to which the Accumulator will be set when a positive edge occurs on the Preload input, the %Q Preload bit is set, or the counter rolls-under in
continuous mode.
Load Oscillator Divider (1 to 65535)
This command changes the frequency of the square wave oscillator signal. The frequency generated is 1 megahertz (1 MHz) divided by the oscillator divider. Thus to get 50 Hz, the oscillator divider should be 20000.
GFK-1062A
Chapter 7 Counter Type E
7-21
Appendix A Using Special CPU Communications
section level 1
Functions
figure_ap level 1
A
table_ap level 1
The Series 90-70 High Speed Counter has some operational requirements that are
unique among the Series 90-70 I/O products. To better support these requirements, the
Series 90-70 COMMREQ and DOIO Function blocks have some special characteristics
which are described here.
Sending Data Commands Using the COMMREQ Function
Data commands sent using %AQ data are not processed by the HSC until the %AQ data
is transmitted, either at the end of the ladder sweep or when a DO I/O command forces
a mid-sweep update of the %AQ HSC data. For large ladders, the COMMREQ function
provides a mechanism for sending Data Commands mid-sweep which will be processed
immediately by the HSC.
The PLC ladder program sends a Data Command using the COMMREQ (Communications
Request) function. The COMMREQ requires that all its command data be placed in the
correct order in the CPU memory before it is executed. It should then be executed by a
one-shot to prevent sending the data to the High Speed Counter multiple times. Successive
COMMREQs must be separated by at least 0.5 milliseconds to guarantee correct processing
by the HSC. A description of the COMMREQ function and its command block data follows
along with a ladder example which uses registers %R0001 to %R0009 for the COMMREQ
command block. Refer to GFK-0265, the Series 90-70 Programmable Controller Reference
Manual, for additional specific information on COMMREQs.
COMMREQ Function Block Description
The Communications Request (COMMREQ) function is a conditionally executed
function that communicates a particular request, through the ladder logic program, to
the High Speed Counter.
Communications Request Function Block Format
The ladder logic representation of the COMMREQ is as follows:
%Q0200
+——————+
—] [———(enable)+ COMM_+—(ok)—
| REQ |
%Q0201
%R0001——+IN FT+————————————————————————————————————( )——
|
|
CONST ——+ SYSID|
0107
|
|
|
|
CONST ——+ TASK |
00001
|
|
+——————+
GFK-1062A
A-1
A
The Communications Request function block has four inputs and two outputs. The first
input is an enable input. Generally a one-shot coil is used to enable the COMMREQ
function. This prevents multiple messages from being sent. The second input (IN) is the
starting location of the COMMREQ command block. The SYSID input is used to
indicate which rack and slot to send the message to (physical location of High Speed
Counter module). In the above example, the SYSID 0107 (in Hexadecimal) points to rack
1, slot 7 and the COMMREQ command block starts at Register 0001. The last input
(TASK) must be set to a 1.
Power is always passed to the ok output. The fault output (FT) is enabled if the
COMMREQ fails.
Command Block
The command block for data Commands is composed of 9 words of information
arranged in the following fashion: (all values in hexadecimal unless otherwise
indicated). Use the block move command to move these values to the Register tables
(refer to the Series 90-70 Programmable Controllers Reference Manual, GFK-0265, for
information on using the block move function).
A-2
Location
Data
%R0001
0003
Length of data is three words
%R0002
0000
Not used (Always zero)
%R0003
0000
Not used
%R0004
0000
Not used
%R0005
0000
Not used
%R0006
0000
Not used
%R0007
nnnn
Data Command - Command Word - Word 0
%R0008
nnnn
Data Command - Command Word - Word 1
%R0009
nnnn
Data Command - Command Word - Word 2
t
Description
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
A
Example - Sending Data Commands
An example of ladder logic for sending a data command to a Type B High Speed Counter
using COMMREQ function blocks is shown below. In this example, the COMMREQ
command block is located in registers %R0001 through %R0009. The command to send
the data is initiated by the conditional input %I0289 which sets output %Q0200 for one
sweep. The High Speed Counter is located in Rack 1, slot 7 (first expansion rack). This
command will load Accumulator 1 with the value 44332211h.
If the COMMREQ command data is formatted incorrectly, or has an invalid command,
the HSC will set the Error Status %I bit, and return an error code in Module Status Code
%AI word.
Note that the comments within /* . . . . */ have been included for information purposes only. They
are not generated by the Logicmaster 90 software.
|
|%I0289
%Q0200
+–—] [————————————————————————————————————————————————————————————(P)——
|
|%I0290
%Q0201
+——] [————————————————————————————————————————————————————————————(P)——
|
|%Q0200 +—————+
+——] [———+BLKMV+—
/* Move Command block into Registers 1—7 */
|
| WORD|
|
|
|
| CONST —+IN1 Q+—%R0001 /* Command block data starts at %R0001
*/
| 0003 |
|
/* Command data is 3 words
*/
|
|
|
/*
| CONST —+IN2 |
| 0000 |
|
/* Not used (always 0000)
*/
|
|
|
| CONST —+IN3 |
| 0000 |
|
/* Not used (always 0000)
*/
|
|
|
| CONST —+IN4 |
| 0000 |
|
/* Not used (always 0000)
*/
|
|
|
| CONST —+IN5 |
| 0000 |
|
/* Not used (always 0000)
*/
|
|
|
| CONST —+IN6 |
| 0000 |
|
/* Not used (always 0000)
*/
|
|
|
| CONST —+IN7 |
| 0101 +—————+
/* First word (Command Word)
*/
|
/* In this case, load Accumulator 1
*/
|
GFK-1062A
Appendix A Using Special CPU Communications Functions
A-3
A
|
|
|%Q0200 +—————+
+——] [———+BLKMV+—
/* Move data into registers 8 through 14 */
|
| WORD|
|
|
|
| CONST —+IN1 Q+—%R0008
| 2211 |
|
/* LSW of data. This and next word will */
|
|
|
/* load the Accumulator with 44332211H
*/
| CONST —+IN2 |
| 4433 |
|
/* MSW of data.
*/
|
|
|
| CONST —+IN3 |
| 0000 |
|
/*
*/
|
|
|
/*
*/
| CONST —+IN4 |
| 0000 |
|
/*
*/
|
|
|
/*
*/
| CONST —+IN5 |
| 0000 |
|
/*
*/
|
|
|
/*
*/
| CONST —+IN6 |
| 0000 |
|
/*
*/
|
|
|
| CONST —+IN7 |
| 0000 +—————+
/*
*/
|
/*
*/
|
|
|
|
|
/* Now call the COMMREQ to send the message */
|
|%Q0200
+—————+
+——] [————————+COMM_+
|
| REQ |
/* COMMREQ will set output %T0051 if failure */
|
|
|
/* detected when sending message.
%T0051 */
|
%R0001 —+IN FT+———————————————————————————————————————————( )——
|
|
|
/* Command block data starts in R0001
*/
|
|
|
|
CONST —+SYSID|
/* High Speed Counter is in rack 1, slot 7
*/
|
0107 |
|
|
|
|
|
CONST —+TASK |
/* (always 1)
*/
|
00000001 +—————+
|
|
A-4
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
A
|
|
/* The same data may be loaded into Counter 2 Accumulator by
*/
|
/* simply changing the command word in R0007 and adding another */
|
/* COMMREQ call as follows:
*/
|
|%Q0201 +—————+
+——] [———+MOVE_+—
|
| WORD|
|
|
|
| CONST —+IN Q+—%R0007
/* Move command to load Accumulator 2 into */
| 0201 | LEN |
/* R0007
*/
|
| 001 |
|
+—————+
|
|
|%Q0201
+—————+
+——] [———————————+COMM_+—
|
| REQ |
|
|
|
%T0052
|
%R0001 —+IN FT+——————————————————————————————————————————( )——
|
|
|
/* COMMREQ command block starts at R0001 */
|
|
|
|
CONST —+SYSID|
/* High Speed Counter is in rack 1,
*/
|
0107 |
|
/* slot 7
*/
|
|
|
|
CONST —+TASK |
|
00000001 +—————+
|
|
GFK-1062A
Appendix A Using Special CPU Communications Functions
A-5
A
Updating I/O Data using the DOIO Function
The DO I/O function is used to update selected inputs or outputs for one scan, in
addition to the normal I/O scan, while the program is running.
In the High Speed Counter there is a close relationship between the Status (%I) data and
the Counter (%AI) data. Status bits reflect events that change the Counter Data, such as
Preloads, Strobes, and Disables. In addition, changes in the Counter Data can cause
Status Data to change, such as when an Accumulator reaches a Preset position. To
support this close correlation between the Status and Counter data, the DOIO function
provides a means for updating both Discrete and Analog tables coherently, using a single
DOIO function block.
DOIO Function Block Format
The ladder logic representation of the DOIO is as follows:
|
|%T00200 +—————+
%T00201
+——] [——+DO_IO+————————————————————————————————————————(S)——
|
|
|
|%I00001-+ST
|
|
|
|
|%I00032-+END |
|
|
|
|
-+ALT |
|
+—————+
|
The DOIO function has four input parameters and one output parameter. When the
function receives power flow and input references are specified, the input points starting
at the reference ST and ending at END are scanned. If a discrete (%I) reference is
specified, with no alternate destination, both the Status (%I) and Counter (%AI) data for
the referenced counter(s) are updated. Because this operation involves the transfer of
two tables, it is only supported when no alternate location is specified. If a reference is
specified for ALT, a copy of the new input values is placed in memory beginning at the
alternate reference, and the real input points are not updated; however only the
specified table is copied. The DOIO function block represented in the figure above will
update both the %I and %AI data for a HSC with a %I starting reference of %I00001.
A-6
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
A
|
|%T00200 +—————+
%T00201
+——] [——+DO_IO+————————————————————————————————————————(S)——
|
|
|
|%Q00001-+ST
|
|
|
|
|%Q00032-+END |
|
|
|
|%T00001-+ALT |
|
+—————+
|
When the DOIO function receives power flow and output references are specified, the
output points starting at the reference ST and ending at END are written to the
referenced counter module(s). If outputs should be written to the output modules from
internal memory other than %Q or %AQ, the beginning reference can be specified using
the ALT input. If a discrete (%Q) reference is specified with no alternate source both the
Control (%Q) and Command (%AQ) data are updated using the referenced High Speed
Counter ’s %Q and %AQ data. Thus the DOIO function block represented in the figure
above will transfer 32 bits of discrete data from the alternate source location starting at
%T1 to the HSC configured with %Q starting reference of %Q00001.
Refer to GFK-0265, the Series 90-70 Programmable Controller Reference Manual, for
additional specific information on the DOIO Function Block.
GFK-1062A
Appendix A Using Special CPU Communications Functions
A-7
Appendix B Using Interrupts with the HSC
section level 1
figure_ap level 1
table_ap level 1
B
This appendix provides a description of how to use interrupts with the High Speed
Counter.
Caution
An I/O interrupt can interrupt the execution of a function block in any
program block, including the _MAIN block. Therefore, unexpected
results may occur if the interrupt block and a program block access the
same data. When it is necessary for an interrupt block and a program
block to access the same data, a SVCREQ #17 or SVCREQ #32 can be
used to temporarily block the interrupt from executing when the
shared data is being accessed.
High Speed Counter Interrupt Capability
The High Speed Counter can be configured to generate a ladder interrupt to the Series
90-70 CPU when any of the Preset Outputs change state. This capability provides a
means to minimize the latency for any special service to be performed when an Output
transitions. Correct use of the interrupt capability requires care, and a good
understanding of the HSC and CPU operation and interaction.
The High Speed Counter has four Preset Outputs, each tied to a hardware output with
an LED indicator. When configured for Type A, B, C, or D operation interrupts can be
enabled or disabled for either or both edges of each of the Preset Outputs. When
configured for Type E operation the High Speed Counter has two High Speed Outputs
and two Standard Preset Outputs. Interrupts can be enabled for the off-to-on transition
of the High Speed Outputs. Interrupts for the Standard Outputs are identical to the
other counter types.
Interrupt Operation
When a Preset Output changes state, and the corresponding interrupt is enabled, the
High Speed Counter will transmit the current %I and %AI data to the CPU. Upon
receipt of the data, the CPU will suspend its current activity, update the %I and %AI
data for the HSC, and then execute the interrupt logic. The execution of a block
triggered from an interrupt supersedes the execution of the main program sequence.
Execution of the main sequence is resumed after the interrupt block completes.
GFK-1062A
B-1
B
Any transition of an output for which the interrupt is configured as enabled will cause
an interrupt to be generated. For example, if an output has its On Preset set to 5, Off
Preset set to 10, the On Interrupt enabled, and the associated Output Enable %Q bit is
on, the counter will generate an interrupt when the accumulator increments to 5. If the
output is then pulsed off and back on by toggling the Output Enable %Q bit, the on
transition of the output will generate an interrupt.
Count Limits:
0 - 10
Preset On Interrupt:
Enabled
On Preset:
5
Preset Off Interrupt:
Disable
Off Preset:
10
COUNTS
COUNTER VALUE
^
0
^
1
^
2
^
3
^
4
^
^
6
5
7
!
INTERRUPTS
^ ^ ^ ^
^
8 9 10 0 1
!
PRESET OUTPUT
OUTPUT ENABLE %Q
Likewise, if the Output Enable %Q bit is off, and the counter is incremented into the
preset on range, the output will not turn on and no interrupt will be generated until the
Output Enable %Q bit is set. For example, if the counter is configured as in the example
above, except the %Q Output Enable bit is not set until the counter reaches 7. In this
case, the output won’t turn on, and no interrupt will be generated until the %Q bit has
turned on.
COUNTS
COUNTER VALUE
^
0
^
1
INTERRUPTS
^
2
^
3
^
4
^
5
^
6
^ ^ ^ ^
^
7 8 9 10 0 1
!
PRESET OUTPUT
OUTPUT ENABLE %Q
CPU Interrupt Routine
If a High Speed Counter has interrupts enabled for any output, a Ladder interrupt logic
block must be defined for that module. If an interrupt logic block is not defined, the
Series 90-70 CPU will report a fault. The CPU supports one interrupt logic block for each
HSC module. When defining the interrupt logic block, the first %I reference of the HSC
must be specified as the trigger reference. Four %I bits (%I25 - %I28) contain the HSC
interrupt status. Each bit corresponds to one of the Preset Outputs and is set when the
corresponding Output generated the interrupt.
The Preset Output status bits (%I9 - %I12) indicate the current Preset Output state so the
interrupt logic can determine which edge(s) occurred. If multiple outputs transition within
a single .5 mS counter service cycle, all the corresponding interrupt status bits will be set and
only one interrupt will be generated. The interrupt status bits are only set when an HSC
interrupt is generated, and should not be tested outside the counter interrupt logic block.
B-2
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
B
Controlling Interrupts
Interrupts can occur at any time with respect to the CPU sweep. Because of this
asynchronous nature and the automatic update of %I and %AI data, it is necessary to
temporarily suspend or disable the interrupts surrounding function blocks that operate
on the %I or %AI data. An example is a _MAIN ladder block performing comparisons
against %AI data from a counter which is generating interrupts. If an interrupt occurs
while the Compare function block is executing, the data can be changed in the midst of
the compare rendering the results invalid. To prevent this, interrupts need to be
disabled or suspended surrounding the compare function. The Series 90-70 CPU
provides two mechanisms for controlling interrupts.
Masking Interrupts
In PLC ladder, a Service Request #17 function block may be used to mask and unmask
interrupts from the High Speed Counter. When this service request is active the CPU
will ignore any interrupts from the specified counter and I/O will update normally, as if
no interrupts had been configured for the module. The Service Request #17 status is
maintained in the retentive CPU memory, and will remain active even if the CPU is
power-cycled. Service Request #17 has a three word parameter block that specifies
whether interrupts are to be enabled or disabled, and identifies the device for which
interrupts are to be disabled.
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Table B-1. Service Request #17 Parameter Block
Offset
Description
Address
0 = Interrupts Unmasked
1 = Interrupts Masked
Address + 1
70
Address + 2
First %I reference of selected HSC
Example of Ladder Logic
The following pages contain an example of Ladder logic that initializes two parameter
blocks, and masks interrupts for a High Speed Counter whose %I data starts at %I33.
Interrupts are then unmasked after the compare and move function.
Note that the comments within /* . . . . */ have been included for information purposes only. They
are not generated by the Logicmaster 90 software.
GFK-1062A
Appendix B Using Interrupts with the HSC
B-3
B
| (************************************************************************)
| (* This is an example of Ladder Logic to disable interrupts surrounding *)
| (* operations on a High Speed Counter’s %AI data. In this example the *)
| (* Counter uses input references %I33 and %AI1. The parameter block
*)
| (* starting at %R1 is used to mask interrupts. The parameter block
*)
| (* starting at %R4 is used to unmask interrupts. SVCREQ #17 and SVCREQ *)
| (* #32 use identical parameter blocks.
*)
| (*
*)
| (* The following BLKMOV initializes the two parameter blocks.
*)
| (************************************************************************)
|
|
|
|FST_SCN
|%S00001 +—————+
+——] [———+BLKMV+—
|
| INT |
|
|
|
|
|
| MASK
| CONST —+IN1 Q+—%R00001
|+00001 |
|
/* 1 = Mask Interrupt
*/
|
|
|
| CONST —+IN2| |
/* Always 70
*/
| +00070 |
|
|
|
|
| CONST —+IN3 |
/* First %I reference for HSC
*/
| +00033 |
|
|
|
|
| CONST —+IN4 |
/* 0 = Unmask Interrupt
*/
| +00000 |
|
|
|
|
| CONST —+IN5 |
/* Always 70
*/
| +00070 |
|
|
|
|
| CONST —+IN6 |
/* First %I reference for HSC
*/
| +00033 |
|
|
|
|
| CONST —+IN7 |
| +00000 +—————+
|
| (*************************************************************************)
| (*
### Mask Interrupts ###
*)
| (*************************************************************************)
|
|
+—————+
+————————+ SVC_+—
|
| REQ |
|
|
|
| CONST —+FNC |
/* Service Request #17
*/
| 00017 |
|
|
|
|
| MASK
|
|
|%R00001—+PARM |
/* Mask Interrupt parameter block */
|
+—————+
B-4
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
B
| (*************************************************************************)
| (*If counter 1 accumulator equals 25, copy all counter %AI data to %R10 *)
| (* and set %T1.
*)
| (*************************************************************************)
|
|
+—————+
+————————+ EQ_ +—
|
| INT |
|
|
|
|
|
|
+—————+
%T00001
| CONST —+I1 Q+—————————+MOVE_+—————————————————————————————————(S)——
| +00025 |
|
| INT |
|
|
|
|
|
|ACCUM1 |
| CTRDATA |
|
|%AI0006—+I2
| %AI0001—+IN Q+—%R00010
|
+—————+
| LEN |
|
|00016|
|
|
|
|
+—————+
|
| (*************************************************************************)
| (*
### Unmask Interrupts ###
*)
| (*************************************************************************)
|
|
+—————+
+————————+ SVC_+—
|
| REQ |
|
|
|
| CONST —+FNC |
/* Service Request #17
*/
| 00017 |
|
|
|
|
|UNMASK |
|
|%R00004—+PARM |
/* Unmask Interrupt parameter block */
|
+—————+
Suspending Interrupts
The Service Request #32 function block may be used to temporarily suspend interrupts
from the High Speed Counter. It differs from Service Request #17 in that interrupts
occurring while a Suspend is active will be stored, and transmitted to the CPU as soon as
the Suspend is disabled. A maximum of 15 interrupts are stored by the HSC in a circular
queue. If more than one interrupt occurs during a Suspend, each interrupt is queued by
the HSC. When the Suspend is deactivated, each queued interrupt is sent to the CPU
one at a time, in the order of occurrence, as fast as the CPU can service them. If more
than 15 interrupts occur during suspension, the oldest interrupts are removed from the
head of the queue, and new interrupts are added to the tail. Thus, only the 15 newest
interrupts are reported to the CPU when the suspend is disabled.
The Suspend/Unsuspend Interrupts service requests are designed to be placed around
locations in the ladder logic which reference HSC %I and %AI data. If interrupts are
suspended before operations using the HSC data begins, the HSC data will not be
changed during the operations. If the interrupts are not suspended, comparisons and
calculations can start using one set of data, an interrupt could occur which updates and
changes the data, and the calculations would use altered data when the interrupt
routine completed.
Interrupts should NEVER be suspended from the end of a ladder sweep to the
beginning of the next sweep. %I and %AI data updates are disabled when interrupts
are suspended to ensure that all data is reported to the CPU in the same sequence it
occurred at the HSC.
GFK-1062A
Appendix B Using Interrupts with the HSC
B-5
B
Note
Service Request #32 status is not retained through a power-cycle. If the
rack containing the CPU or the HSC are power-cycled, the SVCREQ #32
is deactivated, and interrupts will be generated normally.
Example of Ladder Logic
Following is an example of Ladder logic that suspends interrupts for a High Speed
Counter whose %I data starts at %I33. The Interrupts suspend is disabled after the
compare and move functions. The parameter blocks for SVCREQ #32 are identical to
those used for SVCREQ #17.
For this example, assume that the parameter blocks have been uninitialized as in the
previous example.
Note that the comments within /* . . . . */ have been included for information purposes only. They
are not generated by the Logicmaster 90 software.
|(**************************************************************************)
| (* This is an example of Ladder Logic to suspend interrupts surrounding *)
| (* operations on a High Speed Counter’s %AI data. In this example the
*)
| (* Counter uses input references %I33 and %AI1. The parameter blocks are *)
| (* identical to those used for SVCREQ #17. The parameter block starting *)
| (* at %R1 is used to suspend interrupts. The parameter block starting
*)
| (* at %R4 is used to disable the suspend interrupts.
*)
| (*************************************************************************)
|
|
| (*************************************************************************)
| (*
### Suspend Interrupts ###
*)
| (*************************************************************************)
|
|
+—————+
+————————+ SVC_+—
|
| REQ |
|
|
|
| CONST —+FNC |
/* Service Request #32
*/
| 00032 |
|
|
|
|
| MASK
|
|
|%R00001—+PARM |
/* Suspend Interrupt parameter block */
|
+—————+
|
| (*************************************************************************)
| (* If counter 1 accumulator equals 25, copy all counter %AI data to %R10 *)
| (* and set %T1.
*)
| (*************************************************************************)
|
|
+—————+
+————————+ EQ_ +—
|
| INT |
|
|
|
|
|
|
+—————+
%T00001
| CONST —+I1 Q+—————————+MOVE_+———————————————————————————————————————————(S)——
| +00025 |
|
| INT |
|
|
|
|
|
|ACCUM1 |
| CTRDATA |
|
|%AI0006—+I2
| %AI0001—+IN Q+—%R00010
|
+—————+
| LEN |
|
|00016|
|
|
|
|
+—————+
|
B-6
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
B
| (****************************************************************************)
| (*
### Unsuspend Interrupts ###
*)
| (****************************************************************************)
|
|
|
+—————+
+————————+ SVC_+—
|
| REQ |
|
|
|
| CONST —+FNC |
/* Service Request #32
*/
| 00032 |
|
|
|
|
|UNMASK |
|
|%R00004—+PARM |
/* Unsuspend interrupt parameter block* /
|
+—————+
|
Suggestions for Using Interrupts
The following is a list of suggestions for using the Series 90-70 High Speed Counter
interrupt capability.
GFK-1062A
H
Place Suspend/Unsuspend Interrupt service requests before and after any rungs
which access the HSC %I and %AI locations.
H
Minimize the time during which interrupts are masked or suspended. If interrupts
are almost always suspended or masked, they serve no purpose.
H
If there are numerous or lengthy ladder operations using the %I or %AI data,
suspend interrupts around a rung which copies the %I and %AI data to alternate
locations. The ladder then can use the alternate locations without data coherency
problems and the interrupt routine can use the real %I and %AI locations. This
procedure can be repeated as necessary throughout the ladder.
H
Always disable an interrupt suspend (#SVCREQ 32) before the end of the ladder
sweep.
Appendix B Using Interrupts with the HSC
B-7
Appendix C High Speed Counter Summary
section level 1
figure_ap level 1
table_ap level 1
C
This appendix provides a summary of the Series 90-70 High Speed Counter. Applicable
data is listed for each counter type.
High Speed Counter %I Return Data
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Bit
Counter Type B Counter Type C Counter Type D
Counter Type E
1
Strobe 1 Flag
Strobe 1.1 Flag
Strobe 1 Flag
Home 1 Found
Strobe 1.1 Flag
2
Strobe 2 Flag
Strobe 1.2 Flag
Strobe 2 Flag
Home 2 Found
Strobe 1.2 Flag
3
Strobe 3 Flag
Strobe 2.1 Flag
Strobe 3 Flag
Home 3 Found
Strobe 1.3 Flag
4
Strobe 4 Flag
Strobe 2.2 Flag
Home Found
Home 4 Found
Strobe 1.4 Flag
5
Preload 1 Flag
Preload 1 Flag
Preload 1 Flag
Alwaysoff
Strobe 1 Disable
6
Preload 2 Flag
Preload 2 Flag
Preload 2 Flag
Alwaysoff
Disable 1 Status
7
Preload 3 Flag
Disable 1 Status
Disable Status
Alwaysoff
Alwaysoff
8
Preload 4 Flag
Disable 2 Status
Home Status
Alwaysoff
Preload 1 Status
9 - 12
Output 1 - 4 Status
13
Module Ready
14 - 15
Alwaysoff
16
Error Flag
17
Alwaysoff
Strobe 2.1 Flag
18
Alwaysoff
Strobe 2.2 Flag
19
Alwaysoff
Strobe 2.3 Flag
20
Alwaysoff
Strobe 2.4 Flag
21
Alwaysoff
Strobe 2 Disable
22
Alwaysoff
Disable 2 Status
23
Alwaysoff
24
Alwaysoff
25 - 28
29 - 32
GFK-1062A
Counter Type A
Preload 2 Status
Preset 1 - 4 Interrupt Status
Alwaysoff
C-1
C
High Speed Counter %AI Return Data
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Word Counter Type A
Counter Type B Counter Type C Counter Type D
1
Module Status Code
2
Cts/Timebase 1
Cts/Timebase 1
Cts/Timebase 1
Cts/Timebase 1
Accumulator 1
3
Cts/Timebase 2
Cts/Timebase 2
Always0000
Cts/Timebase 2
Strobe 1.1
4
Cts/Timebase 3
Accumulator 1
Accumulator
Cts/Timebase 3
Strobe 1.2
5
Cts/Timebase 4
Cts/Timebase 4
Strobe 1.3
6
Accumulator 1
Accumulator 1
Strobe 1.4
7
Strobe Reg 1
8
Accumulator 2
9
Strobe Reg 2
10
Accumulator 3
11
Strobe Reg 3
12
Accumulator 4
13
Strobe Reg 4
14
Always0000
15
Always0000
16
C-2
Counter Type E
Strobe Reg 11
Strobe Reg 1
Accumulator 2
Strobe Reg 12
Strobe Reg 2
Accumulator 2
Strobe 2.1
Strobe 2.2
Accumulator 2
Strobe Reg 3
Accumulator 3
Strobe Reg 21
Always0000
Accumulator 4
Strobe 2.3
Strobe 2.4
Always0000
Strobe Reg 22
Always0000
Always0000
Always0000
Always0000
Always0000
Always0000
Always0000
Always0000
Always0000
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
C
High Speed Counter %Q Control Data
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Bit
Counter Type
A
Counter Type
B
Counter Type
C
Counter Type
D
Counter Type
E
1
Reset Strobe 1
Reset Strobe 1.1
Reset Strobe 1
Home Command 1
Reset Strobes (1)
2
Reset Strobe 2
Reset Strobe 1.2
Reset Strobe 2
Home Command 2
Reserved
3
Reset Strobe 3
Reset Strobe 2.1
Reset Strobe 3
Home Command 3
Reserved
4
Reset Strobe 4
Reset Strobe 2.2
Reserved
Home Command 4
Reserved
5
Reset Preload 1
Reset Preload 1
Reset Preload 1
Reserved
Reserved
6
Reset Preload 2
Reset Preload 2
Reset Preload 2
Reserved
Reserved
7
Reset Preload 3
Reserved
Reserved
Reserved
Preload Acc 1
8
Reset Preload 4
Reserved
Reserved
Reserved
Reset Preload 1
Reserved
Reserved
9
Enable Output Preset 1
10
Enable Output Preset 2
11
Enable Output Preset 3
12
Enable Output Preset 4
13
14
Reserved
Reserved
Reserved
Home Command
15
Reserved
16
Clear Error
17
Preload Acc 1
Preload Acc 1
Acc Preload 1
Preload Acc 1
Reset Strobes (2)
18
Preload Acc 2
Preload Acc 2
Acc Preload 2
Preload Acc 2
Reserved
19
Preload Acc 3
Reserved
Reserved
Preload Acc 3
Reserved
20
Preload Acc 4
Reserved
Reserved
Preload Acc 4
Reserved
21 - 22
Reserved
23
Reserved
Reserved
Reserved
Reserved
Preload Acc 2
24
Reserved
Reserved
Reserved
Reserved
Reset Preload 2
25 - 32
GFK-1062A
Appendix C High Speed Counter Summary
Reserved
C-3
C
High Speed Counter Data Commands
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁ
ÁÁÁÁ
Command
Data
Command Definition
Word 2
Byte
5
Null
xx
Word 1
Command
Word
Applicable
Word 0
Counters
Byte
4
Byte
3
Byte
2
Byte
1
Byte
0
xx
xx
xx
xx
00h
A- E
Load Accumulator Value
data (16 or 32)
n
01h
A-D
Load High Limit
data (16 or 32)
n
02h
A-D
Load Low Limit
n
03h
A-D
Load AccumulatorIncrement
xx
data (16 or 32)
xx
xx
data (8)
n
04h
A-D
Load Counter Direction
xx
xx
xx
data (8)
n
05h
A
Load Timebase
xx
xx
n
06h
A-D
Load Velocity Increment
xx
n
07h
A-D
n
08h
C, D
n
09h
E
Load Home Value
xx
Set Preset Accumulator
xx
Load Preset ON Value
xx
xx
data (16)
xx
data (8)
k
0Ah
E
m
0Bh
All
m
0Fh
All
m
15h
All
m
19h
All
data (16 or 32)
n
1Fh
All
data (32)
n
20h
C
0
32h
All
xx
xx
data (8)
data (16 or 32)
xx
Load Preload Value
Load Preload 2 Value
Load Oscillator Divider
xx
data (16 or 32)
Load Preset OFF Value
Enable/DisablePreset OFF Interrupt
data (24)
data (32)
Load Outpulse ms
Enable/DisablePreset ON Interrupt
data (16)
xx
xx
xx
xx
data (8)
data (16)
k = Preset Number (3 to 4); m = Preset Number (1 to 4); n = Counter Number (1, 2);
xx = Do not care (ignored); data (8, 16, 24) = 8, 16, or 24 bit data
C-4
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
C
High Speed Counter Module Status Codes (%AI Word 1)
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
Nibble 3
Nibble 2
Nibble 1
Error Source
Counter/Preset #
ErrorDescriptor
0
0
0
0
Nibble 0
Main Error Code
0 = No Error
1 = Unknown Command
2 = Invalid Counter/Preset
3 = Invalid COMMREQ Task ID
1 = Counter 1
4 = Velocity Increment Out of Range
2 = Counter 2
5 = Outpulse ms Out of Range
3 = Counter 3
8 = Accumulator Out of Range
4 = Counter 4
9 = Preload Value Out of Range
1 = %AQ1 - 3
A = Preload 2 Value Out of Range
2 = %AQ4 - 6
4 = COMMREQ
8 = Configuration
1 = Command Error
B = Home Value Out of Range
Preset
C = Preset ON Out of Range
Number
D = Preset Off Out of Range
1 = High Limit < Low Limit
1 = Counter 1
2 = Range Excludes Preload
2 = Counter 2
3 = Range Excludes Preload 2
3 = Counter 3
4 = Range Excludes Home
4 = Counter 4
5 = Range Excludes Preset ON
2 = Command Limit
Error
6 = Range Excludes Preset OFF
1 = Counter 1
0
4 = Home Error
2 = Counter 2
0
4 = Counter 3
5 = Quadrature Error
8 = Counter 4
1 = High Limit < Low Limit
2 = Range Excludes Preload
0 = Non Counter
Specific
0
3 = Range Excludes Preload 2
4 = Range Excludes Home
1 = Counter 1
5 = Range Excludes Preset ON
2 = Counter 2
6 = Range Excludes Preset OFF
3 = Counter 3
9 = Outpulse ms Out of Range
4 = Counter 4
A = Unsupported Feature Error
8 = Configuration
Error
B = Unknown Counter Type Error
C = PLC Version Error
D = Logicmaster 90 Version Error
GFK-1062A
Appendix C High Speed Counter Summary
C-5
C
High Speed Counter User I/O Terminal Pin Assignments
The following table defines which terminals to use for the type of counter selected
during module configuration.
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
Á
ÁÁÁ
Á
ÁÁÁÁ
Á
ÁÁÁÁ
Á
ÁÁÁÁÁ
Á
ÁÁÁÁ
Á
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
C-6
Connector
Signal
Pin Number
Name
Use in Counter Type
1
IN1P
CH1P
CH1AP
CH1AP
CH1AP
CH1AP
2
IN2P
CH2P
CH1BP
CH1BP
CH1BP
CH1BP
3
IN1M
CH1M
CH1AM
CH1AM
CH1AM
CH1AM
4
IN2M
CH2M
CH1BM
CH1BM
CH1BM
CH1BM
5
IN3P
CH3P
CH2AP
CH2AP
CH2AP
CH2AP
6
IN4P
CH4P
CH2BP
CH2BP
CH2BP
CH2BP
7
IN3M
CH3M
CH2AM
CH2AM
CH2AM
CH2AM
8
IN4M
CH4M
CH2BM
CH2BM
CH2BM
CH2BM
11
IN5P
PRLD1P
PRLD1P
PRLD1P
CH3AP
PRLD1P
12
IN6P
PRLD2P
DISABLE1P
DISABLE1P
CH3BP
DISABLE1P
13
IN5M
PRLD1M
PRLD1M
PRLD1M
CH3AM
PRLD1M
14
IN6M
PRLD2M
DISABLE1M
DISABLE1M
CH3BM
DISABLE1M
15
IN7P
PRLD3P
PRLD2P
PRLD2P
CH4AP
PRLD2P
16
IN8P
PRLD4P
DISABLE2P
HOMEP
CH4BP
DISABLE2P
17
IN7M
PRLD3M
PRLD2M
PRLD2M
CH4AM
PRLD2M
18
IN8M
PRLD4M
DISABLE2M
HOMEM
CH4BM
DISABLE2M
21
IN9P
STRB1P
STRB11P
STRB11P
MRKR1P
STRB1P
22
IN10P
STRB2P
STRB12P
STRB12P
MRKR2P
STRBDIS1P
23
IN9M
STRB1M
STRB11M
STRB11M
MRKR1M
STRB1M
24
IN10M
STRB2M
STRB12M
STRB12M
MRKR2M
STRBDIS1M
25
IN11P
STRB3P
STRB21P
STRB21P
MRKR3P
STRB2P
26
IN12P
STRB4P
STRB22P
MRKR1P
MRKR4P
STRBDIS2P
27
IN11M
STRB3M
STRB21M
STRB21M
MRKR3M
STRB2M
28
IN12M
STRB4M
STRB22M
MRKR1M
MRKR4M
STRBDIS2M
Type A
Type B
Type C
Type D
Type E
9
SHIELD
SHIELD
SHIELD
SHIELD
SHIELD
SHIELD
10
INCOM
INCOM
INCOM
INCOM
INCOM
INCOM
19
SHIELD
SHIELD
SHIELD
SHIELD
SHIELD
SHIELD
20
INCOM
INCOM
INCOM
INCOM
INCOM
INCOM
29
SHIELD
SHIELD
SHIELD
SHIELD
SHIELD
SHIELD
30
INCOM
INCOM
INCOM
INCOM
INCOM
INCOM
32
5VP
5VP
5VP
5VP
5VP
5VP
33
SHIELD
SHIELD
SHIELD
SHIELD
SHIELD
SHIELD
31
OSC
OSC
OSC
OSC
OSC
OSC
34
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
35
OUTPWR
OUTPWR
OUTPWR
OUTPWR
OUTPWR
OUTPWR
36
OUT1
HSCOUT1
HSCOUT1
HSCOUT1
HSCOUT1
HSCOUT1
37
OUT2
HSCOUT2
HSCOUT2
HSCOUT2
HSCOUT2
HSCOUT2
38
OUT3
HSCOUT3
HSCOUT3
HSCOUT3
HSCOUT3
HSCOUT3
39
OUT4
HSCOUT4
HSCOUT4
HSCOUT4
HSCOUT4
HSCOUT4
40
OUTCOM
OUTCOM
OUTCOM
OUTCOM
OUTCOM
OUTCOM
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
Appendix D Module Specifications
section level 1
figure_ap level 1
table_ap level 1
D
This appendix provides specifications for the Series 90-70 High Speed Counter.
Specifications for the High Speed Counter
General:
ModuleOperating Voltage
5 VDC (from backplane)
ModuleCurrent Drain
1A + (10 mA x number of ON outputs) + (1.6 x
encoder current)
Maximum Count Rate
Types A - D, and Type E in Up/Down mode
Type E in A Quad B mode
200 KHz
800 KHz
Output Points
Powered by user supplied 5V, or 10 to 30 VDC
LEDs
MODULE OK and O1 - O4 (Output circuit. status)
Input and Output Isolation
Peak (1 second)
SteadyStatus
1500 volts
30 V AC/DC
Inputs
VoltageRange
TTL
5 VDC
Non-TTL
10 to 30 VDC
Magnetic Pickup (I1 to I4 only)
400 mV
TTL
Non-TTL
Von
1.4V
8.0V
400 mV
Voff
0.8V
5.0V
200 mV
Input Thresholds (I1 to I12)
Encoder Power
Magnetic Pickup
5 VDC, 500 mA @40°C (104°F), 300 mA @60°C
(140°F)
Input Filter Delay
GFK-1062A
IN1 to IN8
10 ms or 2µs selectable
IN9 to IN12
2µs
Input Impedance
6000 ohms
Input Hysteresis
250 mV typical
Input Cable
Shielded cable recommended
Maximum length: 30 meters (100 feet)
D-1
D
Outputs
Output Type
Positive Logic, optically isolated
Maximum Supply Voltage
30.0 VDC
Maximum Output Current at 60°C (140°F)
1.0 A for each output using 10 to 30 VDC supply
Output Current using 5 VDC supply
20 mA typical
Inductive Load Clamp Voltage
–8.0 V typical
OFF State Leakage Current
10 µA for each output
Output Response Time
Type A - D, Type E Slow Response
Type E Fast Response
300µs typical
650µs worst case
24 Volts:
On:
Off:
5 Volts
On:
Off:
Output Response Variation
Slow Response
Fast Response
Output Protection
7µs typical
10µs worst case
56µs typical
10µs typical
15µs worst case
63µs typical
650µs worst case
1 µs worst case
5.0 A fuse (5x20mm replaceable) common to all
outputs
System designed to support the VME standard C.1
VME
[ Refer to GFK-0867B, or later for product standards and general specifications.
D-2
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
Appendix E Application Examples
section level 1
figure_ap level 1
table_ap level 1
E
This appendix contains descriptions of several typical applications using the Series 90-30
High Speed Counter. These application examples are:
H
H
H
H
H
H
H
H
H
H
H
H
H
GFK-1062A
Counter Cascading
Monitoring and Controlling Differential Speeds
Direction-Dependent Positioning
RPM Indicator
Tolerance Checking
Measuring or Comparing Pulse Rates
Measuring Pulse Time
Measuring Total Material Length
Material Handling Conveyor Control
Timing Pulse Generation
Digital Velocity Control
Dynamic Counter Preloading
Carousel Tracking
E-1
E
Counter Cascading
Type A counters can be cascaded to accumulate greater count values than are possible
with a single 2-byte counter. This can be accomplished by using the preset output of one
counter for the count input of the next as shown below.
a43028
COUNTER
PULSES
COUNTER 1
COUNTER 2
For example, if a 4-byte Up Counter is required, use two counters configured for the UP
direction and:
1.
Set the Count Limits for both counters at their maximum values:
LOW = –32768 and HIGH = +32767
2.
Set the output preset for counter 1 at:
a44217
ON = 0
UP
ON
0
OFF
150
OFF = 150
3.
Connect counter 1 output to the counter 2 input.
4.
Connect the count pulse stream to the counter 1 input.
Similarly, Down Counters can be cascaded by configuring all counters for the Down
direction, setting the limits at the maximum values and reversing the output presets. For
example:
a44218
OFF = 0
ON = 150
E-2
t
OFF
0
ON
150
DOWN
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
E
Monitoring and Controlling Differential Speeds
Many industrial applications require machines such as cutters, conveyors, or nip rolls to
operate at precise differential speeds. The Type C counter, which could be used with a
minimum of controller support is most suited for this application. Type A or Type B
counters could also be used with the aid of a controller.
The pulses representing the speed of each machine can be separately fed into the plus
and minus loops of the Type C counter. The accumulator will automatically track and
indicate the difference in speed of the two machines. The sign of the accumulator value
will indicate which pulse stream count is greater and the accumulator will indicate the
total accumulated count difference. The Counts/Timebase register (CTB) will indicate
the present rate difference and its sign indicates which is greater.
Depending on the count signal types, each channel of the counter can be independently
programmed to operate in any of its three modes:
1.
Pulse/Direction
2.
Up/Down
3.
A quad B
The sign (+ or –) and magnitude of the deviation from the desired difference can be
used as feedback to provide automatic control for the speed regulation of the machines.
GFK-1062A
Appendix E Application Examples
E-3
E
Direction-Dependent Positioning
Features Used :
––––––––––––––––
Single–Shot Mode
Preload Inputs
Preset Outputs
Counter Type:
–––––––––––––
B
Some applications require direction-dependent positioning. An example is an operation
where a crane on tracks has to perform certain maneuvers while traveling 100 feet in
one direction and different ones while traveling 100 feet in the reverse direction.
This example uses the Type B configuration with two counters configured to operate in
the A Quad B mode. Both counters should be driven by the same A Quad B signals and
connected so they count in opposite directions when the crane is moving, as shown in
Figure B-3 (Example of Terminal Connections).
The counter operating mode, limits and preload value can be set so that the preset
outputs are direction sensitive. In this example, this is done by using the single-shot
mode and preloading Counter 2 so that it only counts when the crane is moving in the
reverse direction (right-to-left).
The counters are both preloaded at the start point and Counter 1 will count up from 0 to
100 for the left-to-right direction, and count down for travel in the right-to-left direction.
Counter 2 will count up from (–100 to 0) only when the crane travels from right-to-left.
Table E-1. Counter Configurations
Parameter
Configuration
Counter Type
Type B (two counters)
Counter Operating Mode
A Quad B
Count Mode
one-shot (both counters),
(non-continuous)
Counter 1 Preload
0
Counter 2 Preload
–100
Counter 1 Limits
0 to 100
Counter 2 Limits
–100 to 0
Table E-2. Operating Count Directions
Counter Number
Crane Direction
Count Direction
Counter 1
→
UP
Counter 2
→
Not counting
Counter 1
←
DOWN
Counter 2
←
UP
In this example, Counter 1 is configured with a preload value of 0. An ON condition for
Preset 1 is selected which will turn on a loading device when the crane has traveled 75
feet to the right. Preset 2 (also for Counter 1) is selected to come on when the crane has
traveled 100 feet to the right.
E-4
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
E
The direction of travel is reversed at the Stop point, and as the crane travels back from
right-to-left, the ON Preset 1 of Counter 2 activates an unloading device when the crane
has traveled 40 feet to the left (ON Preset is –60).
Finally, Preset 2 of Counter 2 turns its output on when the crane has traveled 75 feet to
the left (ON Preset is –25).
The desired operation of the crane in this example is shown in the following figure.
(COUNTER # 2)
ON PRESET 2 = – 25
NEGATIVE DIRECTION
START
SENSOR
a44219
(COUNTER # 2)
ON PRESET 1 = – 60
Î
ÎÎÎÎ
ÎÎÎÎÎ
(COUNTER #1)
ON PRESET 1 = 75
(COUNTER #1)
ON PRESET 2 = 100
POSITIVE DIRECTION
CRANE
STOP
(100)
START
(0)
Figure E-1. Example of Direction-Dependent Sensing
OutputConditions
Counter 1:
Output 1
ON for Counter 1 y 75
OFF for Counter 1 t 75
Output 2
ON for Counter 1 y 100
OFF for Counter 1 <100
Counter 2:
Output 3
ON for Counter 2 v –60
OFF for Counter 2 >–60
Output 4
ON for Counter 2 v –25
OFF for Counter 2 >–25
GFK-1062A
Appendix E Application Examples
E-5
E
a43030
REVERSE
DIRECTION
START
COUNTER 1
START
75
75
75’
OUTPUT # 1
100
100’
OUTPUT # 2
60
COUNTER 2
60’
OUTPUT # 3
25
25’
OUTPUT # 4
Figure E-2. Output Timing Conditions Example
a47074
EXAMPLE
TERMINAL
CONNECTIONS:
INPUT
COUNT
PULSES
A+
B+
A–
B–
1
2
3
4
5
6
7
8
9
10
11
PRELOAD +
12
13
PRELOAD –
14
Figure E-3. Example of Terminal Connections
E-6
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
E
RPM Indicator
Feature Used:
––––––––––––––––––––––––
Counts/Timebase Register
Counter Types:
––––––––––––––
A, B, C, D
The High Speed Counter can be used as a position/motion indicator when connected to
a feedback device (such as an encoder) that is coupled to a rotary motion. RPM
indication can be obtained directly from the counter’sCounts/Timebase register (CTB) or
derived from it by a simple calculation.
The RPM is given by:
CTB
1
RPM = ––––– x –––
PPR
T
where: CTB = counts/timebase reading from the counter
PPR = pulses/revolution produced by the feedback device
T = timebase expressed in minutes
Note that if 1/T divided by PPR is some integer power of 10, then the CTB register gives
a direct reading of RPM with an assumed decimal placement. Longer timebase settings
will give better RPM resolution. This is illustrated in the following examples.
Example 1
If feedback produces 1000 pulses/revolution, CTB reading = 5212, and the timebase is
configured for 600 ms:
then T = 600 ms Ï 60000 ms/min = .01 and 1/T = 100
RPM = 5212 Ï 1000 x 100 = 521.2
CTB reading is RPM with .1 RPM resolution.
Example 2
Assume the same conditions as example 1, except the timebase is now set to 60 ms,
which gives
T = 60
Ï 60000 = .0001 and 1/T = 1000.
Since the motion is turning at the same speed as in example 1, the CTB reading now
equals 521,
and RPM = 521/1000 x 1000 = 521.
CTB reading is now RPM with 1 RPM resolution.
GFK-1062A
Appendix E Application Examples
E-7
E
Tolerance Checking
Features Used:
Counter Type:
––––––––––––––––
–––––––––––––
Strobe Inputs with
B
Positive/Negative Strobe
Edge Configuration
Parts can be measured by a counter for tolerance checking. This can be accomplished by
coupling a pulse feedback device to the transport conveyor to provide count inputs
representing increments of movement to the measuring counter.
For this example, a Type B counter is used and the same part sensing signal is connected
to both strobe inputs. The first strobe input is configured to be active on the leading
edge and the second on the falling edge. Then as each part passes through the sensor, its
length is indicated by the difference between the two strobe register readings.
Multiplying the difference by the known distance represented by each pulse gives the
length in measurement units for comparison against the allowable tolerance. Parts out
of tolerance may be marked or diverted into a separate reject storage area.
An illustration of this application is shown below along with an example of field
connections to the High Speed Counter’s terminal board.
a44220
SENSOR
Figure E-4. Example of Tolerance Checking
a47075
EXAMPLE
TERMINAL
CONNECTIONS:
FEEDBACK
COUNT
PULSES
A
B
1
2
3
4
PART
SENSE
STROBE
INPUT
22
21
Figure E-5. Terminal Connections
E-8
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
E
Measuring or Comparing Pulse Rates
The High Speed Counter can accurately measure a pulse rate or compare the rates of two
pulses. If the measured pulse rate will be less than 1 KHz, one Type A counter can be used,
as described in example 1, below. If the measured pulse rate may exceed 1 KHz, the High
Speed Counter should be configured for Type B counter operation, and set up as described
in example 2.
Using a Reference Pulse
To accurately measure a pulse rate, a pulse stream with a known frequency of up to 200
KHz is used as a reference. The reference frequency should be at least 10x the pulse rate
to be measured.
The reference pulse can come from an external source, or from the counters own
oscillator output (OSC). If the OSC output is used, it can be configured for a frequency
up to 200 KHz (oscillator divider = 5). To use the OSC output, the counter must be
configured for TTL-level Counter Input Threshold voltage (page 3-7). The OSC output
can be jumpered directly to the counter input terminal.
Example 1: Measuring a Pulse Rate Less Than 1 KHz
For this application, configure the High Speed Counter for Type A counter operation.
Configure the Strobe Effect feature for Strobe Then Preload. Configure a Preload value of
0, and configure the Count Direction to be UP.
Connect the reference pulse to the Count Input. Connect the pulse to be measured to
the Strobe input.
As each measured pulse is received, the number of reference pulses received is captured
in the Strobe Register, and the Accumulator is preloaded back to 0. The Strobe Register
always indicates the number of known-frequency pulses between each measured pulse,
and its instantaneous rate can easily be calculated.
Example 2: Measuring a Pulse Rate Over 1 KHz
For this application, the High Speed Counter
should be configured for Type B counter
operation. The Strobe Linkage feature should
be configured to ACC2 (linked) (page 4-12).
Apply the pulse rate to be measured to the
input of Counter 2, as illustrated.
EXAMPLE
TERMINAL
CONNECTIONS:
a47082
1
PULSE
RATE
TO BE
MEASURED
2
3
4
30
31
32
Figure E-6. Example of Terminal Connections
GFK-1062A
Appendix E Application Examples
E-9
E
At the rising edge of each measured pulse, the counter will:
1.
Count the #2 Counter up (or down).
2.
Transfer the contents of Counter 1 into Strobe Register 1.1.
3.
Transfer the contents of Counter 2 into Strobe Register 2.1.
Steps 2 and 3 occur simultaneously, so Strobe Register 2.1 always contains the number of
measured pulses and Strobe Register 1.1 always contains the corresponding number of
measuring pulses to within Ç 1 count.
Pulses
Counter 1
Accumulator
→
1
→
2
→
3
→
4
Counter 2
Strobe Register
Strobe Register
Accumulator
Pulses
D
D
→
12
→
13
→
14
→
15
→
12
1
←
1
←
→
24
2
←
2
←
D
D
→
24
The counter automatically transmits this Strobe Register data to the CPU. The
application program should:
1.
E-10
Find the difference between two successive sets of Strobe Register values. In the
illustration above,
A. for Strobe Register 1.1:
24 –12=12
B. for Strobe Register 2.1:
2 –1= 1
2.
Divide the number of pulses from Strobe Register 1.1 by the number of pulses from
Strobe Register 2.1. This will give the ratio between the pulse rates. In the example,
the ratio is 12 to 1.
3.
To find a measured pulse rate, the program should divide the reference pulse rate by
the number found in step 2. If the reference from the OSC output were 200 KHz,
the measured pulse rate for the example would be 16.7 KHz (200 Ï 12).
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
E
Measuring Pulse Time
Features Used:
–––––––––––––
Ref Osc Input
Strobe Inputs
Counter Type:
–––––––––––––
B
ON/OFF time of input pulses can be accurately measured using the High Speed
Counter. This can be done by configuring the Ref Osc input into Counter 1 and using
the two Strobe inputs to capture the counter value on each of the input pulse edges.
For example, assume that an input pulse needs to be measured to the nearest 0.1
milliseconds; configure the High Speed Counter as follows:
Counter: Type B
Osc Freq Div = 66 (10 kHz)
Osc IN 1 = ON (1)
For Counter 1:
Mode = Continuous
Strobe 1 Edge = Pos
Strobe 2 Edge = Neg
Connect the pulse signal to both Strobe inputs. When the signal occurs, its duration (in
tenths of ms) is now given by [Strobe Reg 2 – Strobe Reg 1] for positive going pulses or
[Strobe Reg 1 – Strobe Reg 2] for negative going pulses.
Note that if the pulse spans the counter rollover point, the calculation becomes more
complex, therefore it may be desirable to preload the counter to 0 shortly before the
pulse is measured.
If only a positive-going pulse is measured, it could also be connected to the preload
input. The Strobe Reg 2 reading would now give the pulse length directly.
GFK-1062A
Appendix E Application Examples
E-11
E
Measuring Total Material Length
Features Used:
–––––––––––––
Disable Input
Counter Type:
–––––––––––––
B
The total length of multiple pieces of material, such as plate glass, plastic strips, or
lumber, can be measured with the High Speed Counter.
This application uses an encoder geared to a transport conveyor to provide the count
input increments, and a sensor to detect material as it passes.
SENSOR
a44610
COUNTING
COUNTING
DISABLE
COUNTING
DISABLE
The High Speed Counter should be configured for Type B counter operation.
Connect the encoder to the counter’s Count Input. Connect the sensor to the Disable
Input.
Count inputs from the encoder will increment the Accumulator only while a piece of
material is passing through the sensor. The total length of all pieces will be accumulated
until the counter is reset (Preloaded) for the start of a new batch. The application
program can convert the count units from the accumulator to the actual units of length
being measured.
E-12
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
E
Material Handling Conveyor Control
Features Used:
––––––––––––––
Preset Outputs
Counter Type:
–––––––––––––
B
When transported material must be stopped momentarily for inspection or
modifications, the High Speed Counter’s Preset outputs can control conveyor slowdown
and stop points.
Use an encoder geared to the transport conveyor to provide the count input increments.
Use a sensor to detect material as it passes on the conveyor.
Determine where the material should begin to slow down, and where the material
should stop. Find out how many encoder counts are equivalent to each of these two
distances.
The High Speed Counter should be configured for Type B counter operation.
Configure Preset Output 1 to turn on at the slowdown point, by entering the number of
counts from the sensor to the point where slowdown should begin.
Configure Preset Output 2 to turn on at the stop point, by entering the number of counts
from the sensor to the inspection station.
Connect the sensor to the Preload Input of the counter to restart the counter at 0 for
each piece of material that passes (only one piece can be between the sensor and the
stop point in this configuration).
a44611
SENSOR
ALTER/CHECK
STATION
OUTPUT 1 SLOWDOWN
OUTPUT 2 STOP
GFK-1062A
Appendix E Application Examples
E-13
E
Timing Pulse Generation
Features Used:
–––––––––––––
Ref Osc Input
Preset Output
Counter Type:
–––––––––––––
A
Applications requiring an accurate timing pulse can use the High Speed Counter to
generate the pulse at the required frequency. The specified pulse width will be accurate
to 0.5 msec of resolution.
Assume that a pulse of 50 msec duration is needed every 1/2 second. The High Speed
Counter could be configured as follows to give the desired pulse output.
Counter type A
Oscillator Frequency Divider (N) = 100 (10kHz)
Oscillator Frequency Input 1 = ON (1)
For counter 1:
mode = continuous
high limit = 4999
low limit = 0
On Preset = 4499
Off Preset = 0
a44612
1/2 SECOND
0
4999
COUNTER 1
4499
OUTPUT 1
0
50mS
The counter’s upper limit of 4999 represents 5000 counts, the number of counts in 1/2
second at 10kHz. (For this example, the Oscillator Frequency could also have been set to
1kHz. If that had been done, the upper limit would have been 499.)
Setting the lower limit to 0 establishes the counter start point for each output pulse
period. The On Preset, 4499, determines that 4500 counts will pass before the beginning
of the output pulse. Setting the Off Preset to 0 turns off the output pulse when the
Accumulator reaches 5000 counts.
E-14
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
E
Digital Velocity Control
Features Used:
–––––––––––––
Ref Osc Input
Up/Down Mode
Counter Type:
–––––––––––––
B
The High Speed Counter, together with an Analog Output module and a drive amplifier,
can be used to provide accurate motor velocity control. The commanded velocity is
generated by connecting the internal oscillator to the up count input of Counter 1.
The OSC input (or an external oscillator) provides a steady counting pulse to the up
count input. The output of the counter provides the accumulator count value to the
CPU. This data can be transferred by the CPU to an analog output module. An output
from this module, in turn, controls the amplifier driving the motor.
During system operation, the motor’s velocity can be changed by changing the
frequency of the OSC output.
OSC
OUTPUT
HIGH SPEED
COUNTER
UP
COUNTER 1
ACCUMULATOR
a44577
ANALOG
OUTPUT
MODULE
D
A
AMP
MOTOR
DOWN
PULSE
TACH
A pulse tachometer is connected to the block’s down count input. This tachometer
provides count pulses that are fed into the down count input of the same counter. As a
result, the counter Accumulator reaches a stable value when the motor is turning at the
commanded velocity.
GFK-1062A
Appendix E Application Examples
E-15
E
Dynamic Counter Preloading
Feature Used:
––––––––––––
Home
Counter Type:
–––––––––––––
C
Applications using a High Speed Counter to track the position of a material conveyor or
machine slide may need to be preloaded accurately at a given reference point while in
motion. Simply connecting a limit switch to the counter’s Preload Input does not give
repeatable, accurate results because errors are introduced by:
1.
Variations in the actuation point of the limit switch and
2.
Preload Input Filter delay when actuated at different speeds.
For accurate repeatability, the Home feature of the Type C counter configuration should
be used. This application requires a marker pulse (usually 1 per revolution) from the
position feedback device (encoder). The limit switch should be placed so that it will be
encountered approximately halfway between marker pulses. When the limit switch is
reached, the next marker pulse causes the High Speed Counter to preload the
Accumulator with the desired value. The limit switch should be connected to the High
Speed Counter’s Enable Home input.
The operation is as follows:
1.
As the conveyor or slide moves toward the reference position, the CPU issues the
Home Command (by setting output bit 14 to the High Speed Counter).
2.
The Enable Home limit switch is actuated. This informs the High Speed Counter
that the next marker pulse will be the reference marker.
3.
When the next (reference) marker is reached, the High Speed Counter automatically
transfers the Home value to the counter Accumulator.
4.
The High Speed Counter informs the CPU that Home position has been found by
setting input status bit 4.
5.
The CPU may then clear the Home Command (output bit 14), causing the block to
remove the Home Found indication.
Encoder Marker Pulses
Home
Reference
↓
(1 per
revolution)
|
|
|
|
|
|
|
CPU Home Command
Enable Home LS Input
Counter Preloaded to
Home Value
Home Found Input to CPU
E-16
t
Series 90 -70 High Speed Counter User’s Manual – November 1995
GFK-1062A
E
Carousel Tracking
Features Used:
–––––––––––––
Home Inputs
Strobe Inputs
Continuous Mode
Counter Type:
–––––––––––––
C
Items stored in a rotating carousel can be tracked and retrieved using a High Speed
Counter. A feedback device coupled to the carousel rotation can be used to provide
up/down count inputs. The counter limits are configured so that the increments
produced by one complete revolution of the carousel cause one full cycle of the counter.
Type C counter configuration is best for this application, since it provides a homing
capability. The homing capability makes it possible to synchronize the counter with the
carousel position at a defined home location after powerup. From then on, any rotation
of the carousel is tracked by the counter. Since the relative location of all entrance and
exit points to the home position is known, the CPU can record the pocket location of
each item entering the carousel. It can command any pocket to any exit for item
retrieval.
If there are up to 3 entrance points, a different Strobe Input can be used to indicate
when a pocket is loaded from each entrance. When the CPU detects the Strobe Set flag,
it can record the pocket position into a memory table and mark it full. (The CPU records
the pocket position by reading the value from the Strobe Register, then adding or
subtracting the entrance offset from the home location.)
To retrieve an item from a particular exit, the CPU can locate the nearest full pocket to
that exit, and generate the required rotation command to the carousel.
a44578
EXIT 1
ÎÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎ
GFK-1062A
ENTRANCE 1
EXIT 2
ENTRANCE 2
EXIT 3
ENTRANCE 3
EXIT ( N )
Appendix E Application Examples
E-17
Index
A
A quad B mode operation, 4-2 , 5-4 , 6-3 ,
7-3
Accumulator, 3-2 , 3-11 , 4-13 , 5-16 , 6-13 ,
7-1 , 7-2
Accumulator adjust, 1-5
Accumulator, increment or decrement, 7-2
Accumulator, preset, 3-7 , 4-9 , 5-6 , 6-9 ,
7-11
Application examples
carousel tracking, E-17
counter cascading, E-2
digital velocity control, E-15
direction-dependent positioning, E-4
dynamic counter preloading, E-16
material handling conveyor control,
E-13
measuring or comparing pulse rates, E-9
measuring pulse time, E-11
measuring total material length, E-12
monitoring/controllingdifferential
speeds, E-3
rpm indicator, E-7
timing pulse generation, E-14
tolerance checking, E-8
Applications, typical, 1-1
Assignments, pin, 2-4
B
Block, command, A-2
C
Carousel tracking, E-17
Catalog number, 1-1
Clear error bit, 3-17 , 4-18 , 5-22 , 6-18 ,
7-18
Command block for data commands, A-2
Command block words, A-2
COMMREQ function block
data to HSC, 3-15 , 4-17 , 5-24 , 6-17 ,
7-17
description of, A-1
format, A-1
Configurable counter types, 1-2
Type A, 1-2
Type B, 1-2
Type C, 1-2
GFK-1062A
Type D, 1-2
Type E, 1-2
Configurable features, 3-6 , 4-8 , 5-10 , 6-8 ,
7-9
Configuration features
accumulator, 6-4
continuous, 3-9 , 6-11
continuous counting, 3-9 , 4-11 , 5-13 ,
6-11
count direction, 3-9
count limits, 3-9 , 4-11 , 5-13 , 6-4
count mode, 3-9 , 4-11 , 5-13 , 7-12
count signal mode, 4-12 , 5-14 , 7-12
counter timebase, 3-9 , 4-12 , 5-14 , 6-12
counts per timebase register, 6-5
home value, 5-14
input filters, 3-7 , 4-9 , 5-11 , 7-10
input thresholds, 3-7 , 4-9 , 5-11 , 7-10
location of preset points, 4-10 , 5-12
marker input and home cycle, 6-4
oscillator, 5-11
oscillator divider, 3-7 , 4-9 , 5-11 , 7-10
oscillator frequency divider and input,
5-11
oscillator output, 6-6
outpulse milliseconds, 7-11
output failure mode, 3-6 , 4-8 , 5-10 ,
6-6 , 7-9
output mode, 7-10
output preset on and off points, 3-8
output preset on and off positions, 4-10
output preset positions, 3-8 , 4-6 , 5-11 ,
6-5 , 6-10 , 7-6
preload configuration, 4-12 , 6-12 , 7-12
preload value, 3-10 , 4-12 , 5-14 , 6-4 ,
6-12 , 7-12
preset accumulator, 4-9 , 7-11
preset interrupt enables, 3-9 , 4-11 , 5-13
preset interrupts, 6-6
single-shot, 3-9 , 6-11
standard preset output on/off positions,
7-11
strobe edge, 3-10 , 4-12 , 5-15 , 7-12
strobe effect, 3-10
strobe linkage, 4-12
strobe mode, 3-10 , 4-12 , 5-15
Configuration features, table of
Type A, 3-6
Type B, 4-8
Type C, 5-10
Type D, 6-8
Type E, 7-9
Configuring the high speed counter, 3-6 ,
4-8 , 5-10 , 6-8 , 7-9
Series 90-70 High Speed Counter User’s Manual – November 1995
Index-1
Index
Contents and operation
Type A counter, 3-1
Type B counter, 4-1
Type C counter, 5-1
Type D counter, 6-1
Type E counter, 7-1
Counts per timebase data, 1-4
Continuous counting, 3-9 , 4-11 , 5-13 ,
6-11 , 7-12
Counter accumulator, 1-4
Data
%AI sent by Type A counter, 3-13
%AI sent by Type B counter, 4-13
%AI sent by Type C counter, 5-16
%AI sent by Type D counter, 6-15
%AI sent by Type E counter, 7-13
%AQ, CPU to HSC (Type A), 3-18
%AQ, CPU to HSC (Type B), 4-19
%AQ, CPU to HSC (Type C), 5-24
%AQ, CPU to HSC (Type D), 6-19
%AQ, CPU to HSC (Type E), 7-19
%I status bits sent by Type A counter,
3-12
%I status bits sent by Type B counter,
4-14
%I status bits sent by Type C counter,
5-17
%I status bits sent by Type D counter,
6-14
%I status bits sent by Type E counter,
7-14
%Q, CPU to HSC (Type A), 3-15 , 5-21
%Q, CPU to HSC (Type B), 4-17
%Q, CPU to HSC (Type C), 5-22
%Q, CPU to HSC (Type D), 6-17
%Q, CPU to HSC (Type E), 7-17
commands, Type A counter, 3-18
commands, Type B counter, 4-19
commands, Type C counter, 5-24
commands, Type D counter, 6-19
commands, Type E counter, 7-19
sent with COMMREQ function, A-1
updating I/O data with DOIO function,
A-6
Counter or preset number, 4-16, 5-19, 7-16
Data commands, 1-5 , 1-9
Counter outputs, 1-8
data commands, C-4
Counter types, 1-2
Data commands, example of sending, A-3
Counting
continuous, 3-9 , 4-11 , 5-13 , 6-11 , 7-12
single-shot, 3-9 , 4-11 , 5-13 , 6-11 , 7-12
Data commands, table of
Type A, 3-19
Type B, 4-20
Type C, 5-25
Type D, 6-20
Type E, 7-20
Continuous or single-shot counting, 1-4 ,
1-8
%Q control data, C-3
Count A and B inputs, 7-2
Count direction, 3-9
Count disable input status, 7-13
Count inputs, default filter, 1-6
Count limits, 3-9 , 4-11 , 5-13 , 6-4 , 6-11
Count mode, 3-9 , 4-11 , 5-13 , 6-11 , 7-12
continuous counting, 3-9 , 4-11 , 5-13 ,
6-11 , 7-12
single-shot counting, 3-9 , 4-11 , 5-13 ,
6-11 , 7-12
Count pulse input, 3-2
Count rate, 1-4
Count rate and input filters, 1-8
Count signal mode, 5-14 , 6-12
A quad B mode, 4-12 , 7-12
pulse direction mode, 4-12
up/down mode, 4-12 , 7-12
Counter
cascading, E-2
pin assignments, 2-5
timebase, 3-9 , 4-12 , 5-14 , 6-12
Type B, 4-1
Type E, 7-1
Counting, continuous, 3-9 , 4-11 , 5-13 ,
6-11 , 7-12
Counting, differential, 5-5
Counting, single-shot, 3-9, 4-11, 5-13, 6-11
Counting, single-shot, 7-12
Index-2
Counts per timebase register, 1-4 , 3-3 ,
3-11 , 4-5 , 4-13 , 5-7 , 5-16 , 6-5 , 6-13
D
Data commands, Type A counter, 3-18
enable/disable preset on and off interrupts, 3-20
Series 90E-70 High Speed Counter User’s Manual – November 1995
GFK-1062A
Index
load accumulator increment, 3-20
load accumulator value, 3-19
load high limit, 3-19
load low limit, 3-20
load on and off preset value, 3-20
load oscillator divider, 3-21
load preload value, 3-21
load timebase, 3-20
load velocity, 3-20
null, 3-19
set counter direction, 3-20
Data commands, Type B counter, 4-19
enable/disable preset on and off interrupts, 4-21
load accumulator increment, 4-21
load accumulator value, 4-20
load high limit, 4-20
load low limit, 4-21
load on and off preset value, 4-21
load oscillator divider, 4-22
load preload value, 4-21
load timebase, 4-21
load velocity increment, 4-21
null, 4-20
Data commands, Type C counter, 5-24
enable/disable preset on and off interrupt, 5-26
load accumulator increment, 5-26
load accumulator value, 5-25
load high value, 5-25
load home value, 5-26
load low limit, 5-26
load on and off preset value, 5-26
load oscillator divider, 5-27
load preload 1 and 2 value, 5-27
load timebase, 5-26
load velocity, 5-26
null, 5-25
Data commands, Type D counter, 6-19
enable/disable preset on and off interrupts, 6-22
load accumulator increment, 6-21
load accumulator value, 6-20
load high limit, 6-20
load home value, 6-21
load low limit, 6-21
load on and off preset value, 6-21
load oscillator divider, 6-22
load preload value, 6-22
load timebase, 6-21
load velocity, 6-21
null, 6-20
GFK-1062A
Data commands, Type E counter, 7-19
enable/disable preset on and off interrupts, 7-21
load on and off preset value, 7-20
load oscillator divider, 7-21
load outputs millisecond, 7-20
load preload value, 7-21
null, 7-20
set preset accumulator, 7-20
Data configuration with ladder logic, A-1
Data transfer, HSC/CPU, 3-11 , 4-13 , 5-16 ,
6-13 , 7-13
Data, %AI for Type A counter, 3-13
Data, %AI for Type B counter, 4-15
Data, %AI for Type C counter, 5-18
Data, %AI for Type D counter, 6-15
Data, %AI for Type E counter, 7-13 , 7-15
Data, %AQ for Type A counter, 3-18
Data, %AQ for Type B counter, 4-19
Data, %AQ for Type C counter, 5-24
Data, %AQ for Type D counter, 6-19
Data, %AQ for Type E counter, 7-19
Data, %I for Type A counter
error status, 3-13
module ready, 3-12
output status, 3-12
preload status, 3-12
preset interrupt, 3-13
strobe status, 3-12
Data, %I for Type B counter
disable status, 4-14
error status, 4-14
module ready, 4-14
output status, 4-14
preload status, 4-14 , 4-15
strobe status, 4-14
Data, %I for Type C counter
disable status, 5-17
error status, 5-18
home found, 5-17
home switch status, 5-17
module ready, 5-18
output status, 5-18
preload interrupt status, 5-18
preload status, 5-17
strobe status, 5-17
Data, %I for Type D counter
error status, 6-14
Series 90-70 High Speed Counter User’s Manual – November 1995
Index-3
Index
home found, 6-14
module ready, 6-14
output status, 6-14
preset interrupt status, 6-14
Data, %I for Type E counter
disable status, 7-14
error status, 7-15
module ready, 7-15
output status, 7-15
preload status, 7-14 , 7-15
strobe disable status, 7-14
strobe status, 7-14
Data, %Q for Type A counter
clear error bit, 3-17
enable output bits, 3-16
preload accumulator bits, 3-17
reset preload bit, 3-16
reset strobe bit, 3-16
Data, %Q for Type B counter
clear error bit, 4-18
enable output bits, 4-18
preload accumulator bits, 4-18
reset preload bit, 4-18
reset strobe bit, 4-18
Data, %Q for Type C counter
clear error bit, 5-22
enable output bits, 5-22
home command bit, 5-22
preload accumulator bits, 5-23
reset preload bit, 5-22
reset strobe bit, 5-22
Data, %Q for Type D counter
clear error bit, 6-18
enable output bits, 6-18
home command bit, 6-18
preload accumulator bits, 6-18
Direct processing, definition of, 1-1
Direction, count, 3-9
Disable status, 4-13 , 5-16
Divider, oscillator, 4-9 , 7-10
DOIO function
description of, A-6
example of, A-6 , A-7
function block format, A-6
Dynamic counter preloading, E-16
E
Edge, strobe, 3-10
edge,strobe, 7-12
Effect, strobe, 3-10
Elements
Type A counter, 3-1
Type B counter, 4-1
Type C counter, 5-2
Type D counter, 6-1
Type E counter, 7-2
Enable output bits, 3-16 , 4-18 , 5-22 , 6-18 ,
7-18
Enables, preset interrupt, 3-9 , 4-11 , 5-13 ,
6-11 , 7-7 , 7-12
Encoder connections, 2-8
Error codes
Type A counter, 3-14
Type B counter, 4-16
Type C counter, 5-19
Type D counter, 6-15
Type E counter, 7-16
Error source, 4-16 , 5-20 , 7-16
Data, %Q for Type E counter
clear error bit, 7-18
enable output bits, 7-18
preload accumulator bits, 7-18
reset preload bit, 7-18
reset strobe flag, 7-17
Error status, 3-11 , 3-13 , 4-13 , 5-16 , 6-13 ,
7-13 , 7-15
Data, to HSC via COMMREQ, 3-15 , 4-17 ,
5-21 , 6-17 , 7-17
Example, sending data commands, A-3
Error, home position, 5-14
Error, quadrature, 6-3
Event stack, strobe, 7-4
DC output, +5V, using to power open–
collector input device, 2-9
Description, module, 1-1
Differential counting, 5-5
Digital velocity control, E-15
Index-4
F
Failure mode, output, 7-7 , 7-9
Features, configurable, 3-6 , 4-8 , 5-10 ,
6-8 , 7-9
Series 90E-70 High Speed Counter User’s Manual – November 1995
GFK-1062A
Index
Field wiring, illustration of, 2-4
Inputs, strobe, 7-4
Filter, default frequency, 1-6
Installation, 2-1
Filters, input, 4-9 , 5-11 , 7-10
Interrupt enables, preset, 3-9 , 4-11 , 5-13 ,
7-6
H
High frequency filter, 1-6
High speed counter
count inputs, 1-6
illustration of, 1-3
inputs, 1-6
inputs, use of, 1-4
installation, 2-1
outputs, 1-7
outputs, use of, 1-4
preload inputs, 1-6
specifications, D-1
specifications, list of, D-1
Type A description, 3-1
Type B description, 4-1
Type C description, 5-1
Type D description, 6-1
Type E description, 7-1
Home command bit, 5-22 , 6-18
Home found marker, E-16
Home input, 3-11 , 4-13 , 5-16 , 6-13
Home position error, 5-14
Home switch, 5-7
Home switch status, 5-16
Home value, 5-7 , 5-14
HSC, description of, 1-1
I
IC697HSC700, catalog number, 1-1
Input circuit diagrams, 2-7
Input filters, 3-7 , 4-9 , 5-11 , 7-10
Input filters, selectable, 6-9
GFK-1062A
Interrupt status, 3-11
interrupt status, 7-13
Interrupts on preset on and off transitions, 7-12
Interrupts, preset, 3-5 , 4-7 , 5-8 , 6-6 , 7-6
L
Ladder logic, A-1
Latched output, 7-5
LEDs, status, MODULE OK, 1-4
Limits, count, 3-9 , 5-13 , 6-4
Location of preset points, 3-8 , 4-10 , 5-12 ,
6-10 , 7-11
Low frequency filter, 1-6
M
Magnetic pickup, 3-7 , 4-9 , 5-11 , 6-9 , 7-10
Marker input, 5-7
Marker input and home cycle, 6-4
Material handling conveyor control, E-13
Measuring or comparing pulse rates
pulse rate less than 1 KHz, E-9
pulse rate over than 1 KHz, E-9
using a reference pulse, E-9
measuring or comparing pulse rates, example of, E-9
Measuring pulse time, example of, E-11
Measuring total material length, E-12
Milliseconds, outpulse, 7-11
Mode, count, 5-13 , 7-12
Mode, count signal, 5-14 , 7-12
Input thresholds, 3-7 , 4-9 , 5-11 , 6-9 , 7-10
Mode, output, 7-10
Inputs, 1-6
count, 1-6
other, 1-7
preload, 1-6
strobe, 1-7
Mode, output failure, 3-5 , 3-6 , 4-7 , 4-8 ,
5-8 , 5-10 , 6-6 , 6-8
Inputs and outputs, module, 1-6
Module inputs and outputs, 1-6
Mode, strobe, 3-10 , 5-15
Module description, 1-1 , 1-2
Series 90-70 High Speed Counter User’s Manual – November 1995
Index-5
Index
MODULE OK led, 1-4
Module ready, 3-11 , 4-13 , 5-16 , 6-13 ,
7-15
Module ready status, 7-13
Module specifications, D-1
Module status code, 4-13 , 5-16
Outpulse, milliseconds, 7-11
Output
preset positions, 3-8 , 4-6 , 5-11 , 6-5 ,
6-10 , 7-6
status, 3-11 , 4-13 , 5-16 , 6-13 , 7-15
Module status codes, 3-11 , 3-13 , 4-15 ,
5-18 , 6-15 , 7-15
Output bits, representation, 4-17 , 7-17
Monitoring and controlling differential
speeds, E-3
Output circuit, typical, 2-8
N
Non-TTL, 3-7 , 4-9 , 5-11 , 6-9 , 7-10
O
On and off output preset positions, 4-10
Open–collector input devices, power for,
2-9
Operating features
accumulator adjust, 1-5
continuous or single-shot counting, 1-4 ,
1-8
count rate, 1-4
count rate and input filters, 1-8
counter accumulator, 1-4
counter outputs, 1-8
counts per timebase register, 1-4
data commands, 1-5 , 1-9
oscillator, 1-5 , 1-9
output interrupts, 1-9
preloads, 1-5 , 1-8
selectable input filters, 1-4
selectable on/off output presets, 1-5
selectable preset interrupts, 1-5
strobe register, 1-5
strobe register stack, 1-8
Type A, B, C, D counters, 1-4
Type E counter, 1-8
velocity command, 1-5
Index-6
Oscillator output frequency, calculation of,
3-5 , 4-7 , 5-9 , 6-6 , 7-8
Output circuit, oscillator, 2-9
Output failure mode, 3-5 , 3-6 , 4-7 , 4-8 ,
5-8 , 5-10 , 6-6 , 6-8 , 7-7 , 7-9
Output interrupts, 1-9
Output mode, 7-10
Output oscillator, 6-6
Output preset on and off positions, 3-8 ,
4-10 , 6-10
Output status, 7-15
Output, oscillator, 3-5 , 4-7 , 5-9 , 7-8
Output, standard preset, 7-11
Outputs, 1-7
preset, 5-7
Overview, Type A counter, 3-1
Overview, Type B counter, 4-1
Overview, Type C counter, 5-1
Overview, Type D counter, 6-1
Overview, Type E counter, 7-1
P
Pin assignments, for counter types, 2-5 ,
C-6
Pin assignments, terminal board, 2-4
Points, preset location, 3-8 , 4-10 , 5-12 ,
6-10
Points, preset separation, 3-4 , 4-6 , 5-8 ,
6-6 , 7-6
OSC output used as reference, E-15
Position error, home, 5-14
Oscillator, 1-5 , 1-9
Positioning, direction-dependent, E-4
Oscillator divider, 3-7 , 4-9 , 5-11 , 6-9 , 7-8 ,
7-10
Positions, output preset, 3-8 , 4-6 , 5-11 ,
6-5 , 6-10 , 7-6
Oscillator output, 3-5 , 4-7 , 5-9 , 6-6 , 7-8
used as a reference, E-9
Preload accumulator bits, 3-17 , 4-18 ,
5-23 , 6-18 , 7-18
Oscillator output circuit, 2-9
Preload input and value, 4-5 , 5-6 , 7-4
Series 90E-70 High Speed Counter User’s Manual – November 1995
GFK-1062A
Index
Preload inputs, 1-6
Preload inputs, default filter, 1-6
Preload status, 7-13 , 7-14
Preload value, 3-10 , 4-12 , 5-14 , 6-12 ,
7-12
Preloads, 1-5 , 1-8
Selectable input filters, 1-4
Selectable on/off presets, 1-5
Selectable preset interrupts, 1-5
Sending data commands, example of, A-3
Preloads, description of, 3-3
Separation of preset points, 3-4 , 4-6 , 5-8 ,
6-6 , 7-6
Preset accumulator, 3-7 , 4-9 , 6-9 , 7-11
Signals, input and output, 1-6
Preset interrupt enables, 3-9 , 4-11 , 5-13 ,
6-11
Single-shot counting, 3-9 , 4-11 , 5-13, 6-11
Preset interrupt status, 3-13 , 7-15
Single-shot counting configuration, 3-9 ,
4-11 , 5-13 , 6-11
Preset interrupts, 3-5 , 4-7 , 5-8 , 6-6 , 7-6
Single-shot counting, 7-12
Preset outputs, 3-4 , 4-6 , 5-7 , 7-6
fast response, 7-4
Source, error, 4-16 , 5-20 , 7-16
Preset points
location of, 3-8 , 4-10 , 5-12 , 6-10 , 7-11
separation of, 3-4 , 4-6 , 5-8 , 6-6 , 7-6
Specifications, table of, D-1
Pulse output, 7-5
Status bits, 3-11 , 4-13 , 5-16 , 6-13 , 7-14
Pulse rate measurement, E-9
Pulse/direction mode operation, 4-2 , 5-4 ,
6-2
Q
Quadrature error, 6-3
R
Recommended field wiring procedures,
2-1
Register data words, %AI
accumulators, 7-13
module status code, 7-13
strobes, 7-13
Removing an I/O module, 2-3
Reset preload bit, 3-16 , 4-18 , 5-22 , 7-18
Reset preload flag, 3-11 , 4-13 , 5-16
Reset strobe bit, 3-16 , 4-18 , 5-22
Reset strobe flag, 3-11 , 4-13 , 5-16 , 7-17
%AI return data, C-2
%I return data, C-1
RPM indicator, example of, E-7
GFK-1062A
S
Specifications for HSC, D-1
Standard preset output, 7-11
Status bits, %I for Type A counter
error status, 3-13
module ready, 3-12
output, 3-12
preload, 3-12
preset interrupt, 3-13
strobe, 3-12
Status bits, %I for Type B counter
disable, 4-14
error status, 4-14
module ready, 4-14
output status, 4-14
preload, 4-14
preset interrupt, 4-15
strobe, 4-14
Status bits, %I for Type C counter
disable, 5-17
error, 5-18
home found, 5-17
home switch, 5-17
module ready, 5-18
output, 5-18
preload, 5-17
preset interrupt, 5-18
strobe, 5-17
Status bits, %I for Type D counter
error, 6-14
home found, 6-14
module ready, 6-14
output, 6-14
Series 90-70 High Speed Counter User’s Manual – November 1995
Index-7
Index
preset interrupt, 6-14
Status bits, %I for Type E counter
count disable input status, 7-13
disable status, 7-14
error status, 7-13 , 7-15
interrupt status, 7-13
module ready, 7-15
module ready status, 7-13
output status, 7-15
preload, 7-14
preload status, 7-13
preset interrupt, 7-15
strobe, 7-14
strobe disable input status, 7-13
strobe disable status, 7-14
strobe status flags, 7-13
status codes (%AI word 1), C-5
Status codes, module, 3-13 , 4-15 , 5-18 ,
7-15
Strobe disable input status, 7-13
Strobe disable status, 7-14
Strobe edge, 3-10 , 4-12 , 5-15 , 7-12
Strobe effect, 3-10
Strobe event stack, 7-4
Strobe input
first strobe mode, 3-3
last strobe mode, 3-2
Strobe inputs, 1-7 , 7-4
Strobe inputs and register, 4-4 , 5-6
Strobe linkage, 4-4 , 4-12
Strobe mode, 3-10 , 5-15
strobe mode, 4-12
Strobe register, 1-5 , 3-11 , 4-13
Thresholds, input, 4-9 , 5-11 , 7-10
Timebase register, counts per, 4-5
Timebase, counter, 5-14
Timebase, timer, 3-9 , 6-12
Timing pulse generation, E-14
Tolerance checking, example of, E-8
TTL, 3-7 , 4-9 , 5-11 , 6-9 , 7-10
Type A configuration description, 1-2
Type A counter
configuration, 3-6
data transfer, HSC and CPU, 3-11
overview, 3-1
Type B configuration description, 1-2
Type B counter
configuration, 4-8
data commands, 4-19
data transfer, HSC and CPU, 4-13
overview, 4-1
Type C configuration description, 1-2
Type C counter
configuration, 5-10
data commands, 5-24
data transfer, HSC and CPU, 5-16
overview, 5-1
Type D configuration description, 1-2
Type D counter
configuration, 6-8
data transfer, HSC and CPU, 6-13
overview, 6-1
Type E configuration description, 1-2
Type E counter
configuration, 7-9
data commands, 7-19
overview, 7-1
Typical applications, 1-1
Strobe register stack, 1-8
Typical encoder connections, 2-8
Strobe registers, 5-16
Typical input circuit diagrams, 2-7
Strobe status, 7-14
Typical output circuit, 2-8
Strobe status flags, 7-13
T
Terminal assignments, for counter types,
2-5 , C-6
U
Up/down mode, 4-2 , 5-3 , 6-2 , 7-2
user I/O terminal pin assignments, C-6
Terminal board, field wiring recommendations, 2-3
Terminal board pin assignments, 2-4
Index-8
V
Value, home, 5-14
Series 90E-70 High Speed Counter User’s Manual – November 1995
GFK-1062A
Index
Value, preload, 3-10 , 4-12 , 5-14 , 6-12 ,
7-4 , 7-12
Velocity command, 1-5
W
wiring for TTL open–collector inputs, 2-9
Wiring, field, 2-3
GFK-1062A
Series 90-70 High Speed Counter User’s Manual – November 1995
Index-9
Was this manual useful for you? yes no
Thank you for your participation!