Memory Backup/Battery Backup
6
Backup Battery for RAM Memory (All Supplies)
The long-life Lithium battery (IC693ACC301) used to maintain the contents of the CMOS RAM
memory in the CPU is accessed by removing the cover plate located at the bottom of the power
supply faceplate. This battery is mounted on a plastic clip attached to the inside of this cover.
The battery is wired to a small Berg female connector that connects to either of the two Berg male
connectors mounted on the Power Supply printed circuit board. This battery can be replaced with
power applied to the PLC.
PWR
OK
Low Battery
Warning LED
RUN
BATT
BATTERY
CONNECTORS
B
A
T
T
E
R
Y
LITHIUM
BACK-UP
BATTERY
Battery
Cavity
Battery Cover Removal Notch
Figure 6-1. Backup Battery for RAM Memory
Caution
If a Low Battery Warning (BATT LED turns ON) occurs, replace the
battery located in the power supply before removing power from the rack.
Otherwise, there is a possibility that data will be corrupted or the
application program will be cleared from memory.
GFK-0356Q
6-1
6
Battery Replacement Instructions
Warning
To avoid the chance of losing the contents of RAM memory, you can
carefully perform the following steps with PLC power ON. This procedure
should only be performed by qualified electrical personnel who are trained
in applicable electrical safety rules and procedures. Failure to follow
standard electrical safety practice can result in injury or death to personnel,
damage to equipment, or both.
6-2
Ŷ
Carefully insert the tip a small pocket-size screwdriver approximately 1/4 inch (6 mm) into the
battery cover removal slot, located beneath the battery cover (see previous figure).
Ŷ
Gently rotate the screwdriver about 45 degrees to loosen the cover.
Ŷ
Remove cover with fingers. The battery is mounted in a clip on the back of the cover. It has a
pair of leads with a connector that is plugged-in to a connector on a circuit board inside the
power supply.
Ŷ
Carefully reach into battery cavity with your fingers (do not use a metal object to do this) and
unplug the battery connector.
Ŷ
Remove the old battery from the clip on the battery cover and set it aside. Be careful not to
mix it up with the new battery.
Ŷ
Carefully reach into battery cavity with your fingers (do not use a metal object to do this) and
plug in new battery connector.
Ŷ
Clip new battery into clip on battery cover.
Ŷ
Snap battery cover back onto power supply.
Series 90-30 PLC Installation and Hardware Manual – August 2002
GFK-0356Q
6
Battery Replacement/Memory Protection Factors
Since there are differences in each PLC application, each user will have to determine on an
individual basis what strategy to use. There are several factors to consider when planning a battery
replacement/memory protection strategy:
Ŷ
How critical is the application? Will considerable loss be sustained if the PLC goes down? If
so, frequent replacement of the battery would be a wise choice. For critical applications, the
cost of a battery would be quite low in comparison to the cost of a PLC shut-down.
Ŷ
How readily can a backup program be loaded? Are there technicians on-site who know how to
load a backup program? Is the backup program accessible at all times to those responsible for
maintaining the equipment? Is a personal computer or equivalent equipped with GE
programming software available at all times for use in loading the backup program?
Ŷ
Do you have a preventive maintenance program? A formal program would help ensure that
the battery is replaced on time. Some users replace the backup battery each year during their
annual shut-down period.
Ŷ
How accessible is the PLC? In some applications, the PLC may be mounted in a remote
location that is not easily accessed.
Ŷ
Safety codes. Some users may have safety rules that would not allow replacing the battery
with power applied.
Ŷ
How is the PLC used? Is power left on all the time, or is it shut down every day? See the
heading “Factors Affecting Battery Life.”
Ŷ
Some users run without a backup battery by using one of the PROM options. See the section
below called “Operating Without a Memory Backup Battery” to determine if this strategy is
suitable for your application.
The Importance of Backing up Your Program
Regardless of what strategy you use to maintain PLC memory, you should always keep an up-todate backup copy of your application program. Other suggestions to help minimize down time:
GFK-0356Q
Ŷ
Make sure the backup copy is readily accessible to those who may need to use it.
Ŷ
Train more than one person to load the backup program in case that one person is not available
when needed. Information on creating a backup can be found in GE’s software user’s
manuals. This procedure is also covered in applicable GE programming software
training courses.
Ŷ
Ensure that a suitable computer is equipped with GE PLC programming software and
will be readily available to load the backup program to the PLC.
Ŷ
Create a written backup procedure. Fortunately, restoring your program from the backup copy
is probably not something you will do very often. As a result, however, some of the steps
could easily be forgotten.
Chapter 6 Memory Backup/Battery Backup
6-3
6
Factors Affecting Battery Life
Replacing your battery once per year is a good rule of thumb. However, no one can predict
precisely how long a backup battery will last because this depends upon what CPU is used, what
temperature it is subjected to, and how it used. Considering the following list of factors that affect
battery life will help you decide how frequently to replace the battery in your application:
Ŷ
A battery that is not in use has an estimated life (called its ”shelf life”) of 5 years at ”room
temperature” (25 degrees C, or 77 degrees F).
Ŷ
A battery that is used continuously (supplying current to memory circuits with PLC power off)
if used at room temperature has an estimated average life as follows:
Estimated Average Life
at Room Temperature
Model
CPU models 311, 313 and 323
2 years
CPU models 331—364
1 year
CPU374
1.2 months
Ŷ
As long as a PLC is powered up, its battery is not being used; so how often you power down
your PLC has a direct affect on battery life. Some users keep their PLC powered up all of the
time while others turn theirs off every night.
Ŷ
Temperature has a relatively large affect on battery life. Temperatures considerably above
room temperature (25 degrees C, or 77 degrees F), or below freezing (0 degrees C, or 32
degrees F) will appreciably shorten battery life.
Ŷ
The type of CPU has a small affect on battery life. Some CPUs have more memory than
others. Some memory types require more power. Also, some CPUs have a clock and some do
not. More memory requires more battery current to maintain its contents; and a clock requires
battery current to maintain its operation.
Low Battery Warning Methods
There are three basic ways that the PLC warns of a low battery:
Ŷ
The red ”BATT” LED on the Power Supply module lights when the battery is low. The
disadvantage of this method is that the PLC is often mounted in an enclosure, so this LED
might not be easily seen.
Ŷ
The PLC Fault Table is updated with a battery low message. Viewing the PLC Fault Table
requires that a programmer be connected to the PLC.
Ŷ
Certain System Reference bits are set to logic 1 when the battery is low. These are %SA011
(LOW_BAT), %SC009 (ANY_FLT), %S010 (SY_FLT), and %SC012 (SY_PRES). The most
specific is %SA011 (LOW_BAT). This bit could be used as a contact in your ladder logic
program to turn on an output that controls a warning light on an operator panel (as in the
example rung below), or to send a warning to an operator interface terminal.
%SA011
6-4
Series 90-30 PLC Installation and Hardware Manual – August 2002
%Qxxx
GFK-0356Q
6
In the rung shown above, the %SA011 contact will close when a low battery is detected by the
PLC. This will turn on the %Q output coil, which addresses an output module’s output that will
turn on a warning light. An alternate method would be to communicate the status of the coil
(which, in that case, would probably be a %M coil) to a Human to Machine Interface (HMI)
terminal such as a GE CIMPLICITY HMI unit. The HMI could be programmed to display a
warning message when that particular bit goes to a logic 1. For more information about System
Reference bits and ladder logic programming, see the Series 90-30/20/Micro PLC CPU Instruction
Set Reference Manual, GFK-0467.
GFK-0356Q
Chapter 6 Memory Backup/Battery Backup
6-5
6
Operating Without a Memory Backup Battery
Whether it would be to your advantage to use a battery-less scheme depends on your application.
There are various advantages and disadvantages to consider in making your decision.
Possible Advantage
The obvious advantage of operating without a memory backup battery is that you are freed from
the need to maintain the battery. To be able to run without a battery, you need to have a PROM
device - either an EPROM, EEPROM, or Flash PROM - installed in your system. These devices
can store program logic, configuration, and register values without the need for a backup battery,
and you can configure your CPU to read the contents of PROM into RAM memory each time the
PLC is powered up.
Possible Disadvantages
Information is not stored to your PROM device automatically. To store information, you must stop
the PLC, then use a programming device to tell the CPU to write the current PLC (RAM) memory
contents to the PROM device. This requirement may make battery-less operation undesirable for
many users. For example, in many applications, important data is gathered and stored in RAM
register memory, data such as the current level of material in a tank that is being filled, or a running
count of parts produced, etc. This constantly changing data is not being copied automatically to
the PROM device. It only exists in RAM memory. Therefore, if power is lost and there is no
RAM memory backup battery, this data will be lost.
However, one way to preserve data in a battery-less system is to send it over a network to a
computer that can store the data on its hard drive. Also, static data (data that doesn’t change)
contained in RAM memory, such as mathematical constants or look-up table type information, can
be stored initially in PROM and automatically written back to RAM each time the PLC powers up.
Another consideration is that if you change your program (or configuration), someone will have to
remember to write the changed information to the PROM device. If that step is forgotten, the
change only exists in RAM memory, and in a battery-less system, it will be lost the next time
power is removed from the PLC.
6-6
Series 90-30 PLC Installation and Hardware Manual – August 2002
GFK-0356Q
6
Configuring a Battery-Less System
Here are the basic steps to configure a system to run battery-less. When configured this way, the
contents of PROM memory will be written into RAM memory each time the PLC powers up.
Ŷ
Equip your CPU with a PROM device. On some CPUs a PROM device is purchased as an
option; on others, it is a standard feature. For a table that identifies the standard PROM
configuration for each CPU, see “CPU Firmware and PROM Configurations” in chapter 5.
Ŷ
There are three CPU configuration parameters involved. Configure them as follows: Pwr Up
Mode: RUN; Logic/Cfg: PROM; Registers: PROM.
Ŷ
Store your folder (include Program Logic, Configuration, and Register Data) to the PLC. This
places your entire folder into RAM (working) memory.
Ŷ
Write PLC (RAM) memory to the PROM device. Make sure you write all data (Program
Logic, Configuration, and Register Data) to the PROM. Note that the type of PROM device
depends on what model CPU you have and how it is equipped.
Ŷ
If you are using a 340 or higher CPU (such as a CPU350, CPU351, etc.), read the next section
for an additional requirement.
Operation Without a Memory Backup Battery Using a 340 or Higher CPU
This information is applicable only to CPU model numbers 340 and higher (such as CPU350,
CPU351, etc.). In systems that do not use a memory backup battery, a standard 0.1” Berg jumper
should be installed across either of the two power supply battery connectors to ensure reliable
restarting of the CPU after a power cycle. This jumper should not be installed if a battery is
plugged into either the power supply or CPU battery connector.
Determining Battery Age Using Battery Date Code
Battery age can be determined from the date code stamped on the battery.
The battery, manufactured by Panasonic, will have a four-digit date code. It will be something like
5615 or 7Y34. Use the following information to determine the date of manufacture.
Ŷ
First digit shows the year in a rotating 10-year cycle. For example, 0=1990, 1=1991, 2=1992
... 9=1999, 0=2000, 1=2001, 2=2002, etc. This seeming duplication should not be a problem
because the shelf life of these batteries is 5 years. Batteries in inventory that are older than 4
years old should be discarded according to the manufacturer’s instructions (since they have
less than one year of life remaining we would not recommend using them in a PLC). This will
ensure that outdated batteries are not mistaken for newer batteries.
Ŷ
Second digit shows the month. 1=January, 2=February, 3=March, 4=April, 5=May, 6=June,
7=July, 8=August, 9=September, O=October, Y=November, Z=December.
Ŷ
Third digit shows the week of the month.
Ŷ
Fourth digit shows the day of the week. 1=Monday, 2=Tuesday, 3=Wednesday, 4=Thursday,
5=Friday, 6=Saturday, 7=Sunday.
For example, the code 7612 is interpreted as:
Manufactured on June 3, 1997
GFK-0356Q
Chapter 6 Memory Backup/Battery Backup
6-7
6
RAM Memory Battery Backup Connection Path
CMOS RAM and DRAM memory is a volatile type of memory, which means that it can lose its
contents (ladder program, configuration, etc.) if power is removed. To retain RAM memory
contents under no-power conditions, a long-life lithium battery is provided. This battery is
normally mounted in the rack’s Power Supply module. To avoid accidental disconnection of the
memory backup battery, it is beneficial to know the connection path between the battery and the
memory circuits:
For embedded CPUs: The battery connection path to RAM memory is through the Power
Supply’s baseplate connector and across the backplane board to the RAM circuits.
For modular CPUs: The battery connection path to RAM memory is through the Power Supply’s
baseplate connector, across the backplane board, and through the CPUs baseplate connector to the
RAM circuits inside the CPU module.
Obviously, removing the Power Supply module from the PLC breaks the connection between the
backup battery and the RAM memory circuits for both embedded and modular CPUs. Also, in a
modular CPU system, removing the CPU module would disconnect the backup battery from the
memory circuits. In addition, to avoid the possible problems associated with losing the contents
of RAM memory, we recommend that you maintain an up-to-date backup copy of your program
folder. Instructions for creating program folder backups can be found in the Logicmaster 90,
Series 90-30 Programming Software User’s Manual, GFK-0466, and the online help and user’s
guides for the Windows-based programming software products.
Super Capacitor Memory Backup
Besides the backup battery, the RAM memory circuits in both Embedded and Modular CPUs are
further protected by a ”super capacitor,” which can store enough charge to maintain memory for a
short time if the battery is disconnected. The amount of protection time provided by the super
capacitor depends on the following:
6-8
Ŷ
The PLC power supply supplies 5 VDC to the memory circuits, including the super capacitor.
Therefore, when PLC power is turned off, the super capacitor has an initial 5 VDC charge. If
the battery is also disconnected shortly after PLC power is turned off, the super capacitor will
begin discharging from the 5 VDC level until its charge reaches 2 VDC, at which time
memory contents will be lost. When used this way, the super capacitor can maintain memory
contents for a minimum of 1 hour.
Ŷ
The memory backup battery supplies 3 VDC to the memory circuits, including the super
capacitor. Therefore, if PLC power has been turned off for an hour or more and only the
battery is powering the memory circuits, the super capacitor has a 3 VDC charge. Then, if the
battery is disconnected, the super capacitor will begin discharging from the 3VDC level until
its charge reaches 2 VDC, at which time memory contents will be lost. When used this way,
the super capacitor can maintain memory contents for a minimum of 20 minutes.
Series 90-30 PLC Installation and Hardware Manual – August 2002
GFK-0356Q
6
Maintaining RAM Memory During Storage or Shipment of a CPU
Modular CPUs
Modular CPUs have an internal connector for a backup battery so that RAM memory contents can
be retained while the CPU is being stored or shipped. This arrangement should not to be used
when the CPU module is installed in the baseplate and the backup battery is installed in the power
supply. To use a backup battery in the CPU module, it is necessary to remove the front cover of
the CPU module. This can be accomplished by following these steps:
Ŷ
To avoid losing memory contents once the CPU is removed from the PLC, we recommend you
install the backup battery into the CPU within 20 minutes. First, make sure PLC power is off,
then remove the CPU module.
Ŷ
Gently squeeze the front cover of the CPU module and pull it forward, away from the module
case, while gently pressing in on the 4 front cover tabs sequentially with a small screwdriver.
The front cover tabs latch into holes on each side of the module case (refer to Figure 2-1 for
location of front cover holding tabs).
Ŷ
After removing the front cover, plug the memory backup battery into the two-prong battery
connector on the front of the CPU module’s printed circuit board.
Ŷ
While the battery is connected to the CPU, you will have to leave the CPU’s front cover off.
Also, the battery should be temporarily secured to the module with cable ties or tape to keep it
from being accidentally damaged or disconnected.
The Battery Accessory Kit, described below, may also be used on a Modular CPU baseplate if the
power supply has to be removed. This would require leaving the CPU module mounted in the
baseplate.
Long-term battery backup can be provided with the use of the External Battery Module, described
on page 6-10.
Embedded CPUs
Embedded CPU Models 311, 313, and 323 can be stored or shipped with a power supply installed
and the power supply battery connected in order to maintain the contents of RAM memory.
However, another option (that doesn’t require the use of a power supply) is to use the Battery
Accessory Kit, described next.
Battery Accessory Kit (IC693ACC315)
The Battery Accessory Kit (IC693ACC315) lets you maintain RAM memory contents without
using a power supply. It is useful for maintaining memory contents while a baseplate is being
stored or shipped. The Battery Accessory Kit consists of a battery with an attached connector
mounted on a circuit board. The circuit board has a connector that plugs into the power supply
backplane connector (see the figure below). The Battery Accessory Kit can be used on either
Embedded or Modular Series 90-30 CPU baseplates.
GFK-0356Q
Chapter 6 Memory Backup/Battery Backup
6-9
6
POWER
SUPPLY
CONNECTOR
BATTERY
PLUG
Figure 6-2. Installing the Battery Accessory Kit
Battery Accessory Kit Installation
1. Insert the plug on the end of the battery cable into the 2-pin connector on the Battery Accessory
board. The battery plug is normally not plugged into the accessory connector. This prevents
accidental discharge of the battery during storage and handling.
2. Align the backplane connector on the Battery Accessory board with the power supply
connector on the baseplate backplane. Push the Battery Accessory board toward the baseplate
until it is fully seated. See the figure above.
3. If the baseplate is to be shipped with the Battery Accessory board installed, ensure that the
board is held in place by packing material or cable ties. The cable ties can be installed in holes
provided on both ends of the accessory board and secured to the baseplate.
Caution
To avoid losing CPU data, the Battery Accessory must be installed within 1
hour after turning off PLC power, or 20 minutes after removing the memory
backup battery. See “Super Capacitor Memory Backup” for details.
When the Battery Accessory is removed, a power supply module with a good
battery must be installed and/or input power applied within 20 minutes to
avoid losing CPU data. See “Super Capacitor Memory Backup” for details.
External Battery Module (IC693ACC302)
This module provides long-term battery backup for all modular Series 90-30 CPUs. Its two-foot
cable plugs into the power supply battery connector. The External Battery Module maintains RAM
contents on a CPU374 for 15 months. CPU models 331—364 maintain RAM contents for
approximately 75 months. For details, see the Datasheet for the External Battery Module,
GFK-2124.
6-10
Series 90-30 PLC Installation and Hardware Manual – August 2002
GFK-0356Q
6
Batteries in Power Supplies on Expansion or Remote Racks
Batteries in power supplies on Expansion or Remote racks, are not in use. Only the battery in a
CPU rack supplies backup power to RAM memory. Batteries in non-CPU racks may be removed
and used as spares, if they meet the age requirements stated previously in this chapter.
GFK-0356Q