33002204 12/2010
Concept 2.6
User Manual
33002204.12
12/2010
www.schneider-electric.com
© 2010 Schneider Electric. All rights reserved.
2
33002204 12/2010
Table of Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1 General description of Concept . . . . . . . . . . . . . . . . . . .
1.1 General description of Concept. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLC hardware configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLC Hardware Package Contents in Concept S, M and XL . . . . . . . . . . .
1.2 Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Libraries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Editors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Online functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Secure Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Utility program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2 New Performance Attributes of Concept 2.6 in
Comparison with Concept 2.5 . . . . . . . . . . . . . . . . . . . . .
New Performance Attributes of Concept 2.6 Compared with Concept 2.5
New performance attributes of Concept 2.6 SR2 in comparison with
Concept 2.6 SR1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
New performance attributes of Concept 2.6 SR3 in comparison with
Concept 2.6 SR2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 3 Project structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Project Structure and Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 4 Creating a Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 1: Launching Concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 2: Configuring the PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 2.1: Required Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 2.2: Optional Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33002204 12/2010
19
21
23
24
25
27
28
29
30
31
33
37
38
39
41
45
46
52
55
57
58
64
68
73
75
76
77
78
79
81
3
Step 3: Creating the User Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 4: Save . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 5: Perform Memory Prediction. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 6: Loading and Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 7: Optimize and Separate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 8: Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
85
88
89
90
95
97
Chapter 5 PLC configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
99
5.1 General information about hardware configuration . . . . . . . . . . . . . . . . .
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Proceed in the following way with the configuration . . . . . . . . . . . . . . . .
5.2 Configuration in OFFLINE and ONLINE mode . . . . . . . . . . . . . . . . . . . .
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Available Functions in OFFLINE and ONLINE Modes. . . . . . . . . . . . . . .
5.3 Unconditional Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Precondition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLC selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CPU Selection for the PLC Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLC memory mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Loadables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Segment manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Optional configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Settings for ASCII Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Making Additional Functions Available in the Configurator . . . . . . . . . . .
Data Exchange between Nodes on the Modbus Plus Network . . . . . . . .
How many words are really used when data is received (Peer Cop) . . .
Protecting Data in the State RAM before Access . . . . . . . . . . . . . . . . . .
Parameterize interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5 Backplane Expander Config . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generals to Backplane Expander . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Edit I/O Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6 Configuration of various network systems . . . . . . . . . . . . . . . . . . . . . . . .
Configure INTERBUS system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure Profibus DP System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure Ethernet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RTU extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ethernet I/O Scanner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to use the Ethernet / I/O Scanner . . . . . . . . . . . . . . . . . . . . . . . . . .
5.7 Quantum Security Settings in the Configurator . . . . . . . . . . . . . . . . . . . .
Quantum Security Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
100
101
102
103
104
105
107
108
109
110
113
114
117
119
122
123
124
125
126
128
129
131
133
134
135
136
137
138
139
141
143
144
149
151
151
33002204 12/2010
Chapter 6 Main structure of PLC Memory and optimization of
memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 Main structure of the PLC Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General structure of the PLC Memory. . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 General Information on Memory Optimization. . . . . . . . . . . . . . . . . . . . . .
Possibilities for Memory Optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLC-Independent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 Memory Optimization for Quantum CPU X13 0X and 424 02 . . . . . . . . . .
General Information on Memory Optimization for Quantum CPU X13 0X
and 424 02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selecting Optimal EXEC File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the Extended Memory (State RAM for 6x references) . . . . . . . . . .
Harmonizing the IEC Zone and LL984 Zone. . . . . . . . . . . . . . . . . . . . . . .
Harmonizing the Zones for Global Data and IEC Program Memory . . . . .
6.4 Memory Optimization for Quantum CPU 434 12(A) and 534 14(A/B). . . .
General Information on Memory Optimization for Quantum CPU 434
12(A) and 534 14(A/B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Harmonizing IEC Zone and LL984 Zone. . . . . . . . . . . . . . . . . . . . . . . . . .
Harmonizing the Zones for Global Data and IEC Program Memory (CPU
434 12(A) / 534 14 (A/B)) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5 Memory optimization for Compact CPUs . . . . . . . . . . . . . . . . . . . . . . . . .
General Information on Memory Optimization for Compact CPUs . . . . . .
Harmonizing IEC Zone and LL984 Zone. . . . . . . . . . . . . . . . . . . . . . . . . .
Harmonizing the Zones for Global Data and IEC Program Memory
(Compact) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.6 Memory optimization for Momentum CPUs. . . . . . . . . . . . . . . . . . . . . . . .
General Information on Memory Optimization for Momentum CPUs . . . .
Selecting Optimal EXEC file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Harmonizing the Zones for Global Data and IEC Program Memory
(Momentum) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7 Memory optimization for Atrium CPUs . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information on Memory Optimization for Atrium CPUs . . . . . . . .
Use of IEC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Harmonizing the Zones for Global Data and IEC Program Memory
(Atrium) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 7 Function Block language FBD. . . . . . . . . . . . . . . . . . . . .
7.1 General information about FBD Function Block . . . . . . . . . . . . . . . . . . . .
General information on Function Block language FBD . . . . . . . . . . . . . . .
7.2 FBD Function Block objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Functions and Function Blocks (FFBs) . . . . . . . . . . . . . . . . . . . . . . . . . . .
Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Actual parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Text Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33002204 12/2010
155
156
156
157
158
159
162
163
165
169
171
173
176
177
179
184
187
188
190
194
197
198
200
201
204
205
207
209
213
214
214
215
216
220
221
223
5
6
7.3 Working with the FBD Function Block langauge . . . . . . . . . . . . . . . . . . .
Positioning Functions and Function Blocks . . . . . . . . . . . . . . . . . . . . . . .
FFB Execution Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Loops . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4 Code generation with the FBD Function Block language . . . . . . . . . . . .
Code Generation Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.5 Online functions of the FBD Function Block language. . . . . . . . . . . . . . .
Online Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.6 Creating a program with the FBD Function Block language . . . . . . . . . .
Creating a Program in the FBD Function Block Language . . . . . . . . . . .
224
225
227
230
232
232
233
233
235
235
Chapter 8 Ladder Diagram LD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
239
8.1 General information about Ladder Diagram LD . . . . . . . . . . . . . . . . . . . .
General Information about the LD Ladder Diagram Language . . . . . . . .
8.2 Objects in Ladder Diagram LD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Functions and Function Blocks (FFBs) . . . . . . . . . . . . . . . . . . . . . . . . . .
Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Actual Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Text object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.3 Working with the LD Ladder Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . .
Positioning Coils, Contacts, Functions and Function Blocks . . . . . . . . . .
Execution sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Loops . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.4 Code generation with LD Ladder Diagram. . . . . . . . . . . . . . . . . . . . . . . .
Code Generation Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.5 Online functions with the LD Ladder Diagram . . . . . . . . . . . . . . . . . . . . .
Online Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.6 Creating a program withLD Ladder Diagram . . . . . . . . . . . . . . . . . . . . . .
Creating a Program in LD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
240
240
242
243
245
248
253
254
256
257
258
260
262
264
264
265
265
267
267
Chapter 9 Sequence language SFC . . . . . . . . . . . . . . . . . . . . . . . . . .
271
9.1 General information about SFC sequence language. . . . . . . . . . . . . . . .
General information about SFC language . . . . . . . . . . . . . . . . . . . . . . . .
9.2 SFC sequence language elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transition section. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Jump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alternative Branch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alternative connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parallel branch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parallel connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Text object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
272
272
274
275
278
280
282
284
285
287
289
290
291
292
33002204 12/2010
9.3 Working with the SFC Sequence Language . . . . . . . . . . . . . . . . . . . . . . .
General information on editing objects . . . . . . . . . . . . . . . . . . . . . . . . . . .
Declaring step properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Declaring actions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Identifier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Declaring a Transition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alias Designations for Steps and Transitions . . . . . . . . . . . . . . . . . . . . . .
9.4 Online functions of the SFC sequence language . . . . . . . . . . . . . . . . . . .
Animation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controlling a Step String . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Learn monitoring times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transition diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 10 Instruction list IL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.1 General information about the IL instruction list . . . . . . . . . . . . . . . . . . . .
General Information about the IL Instruction List . . . . . . . . . . . . . . . . . . .
10.2 Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General information about instructions . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Declaration (VAR...END_VAR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.3 IL instruction list operators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Load (LD and LDN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Store (ST and STN). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Set (S) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reset (R) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Boolean AND (AND, AND (), ANDN, ANDN ()). . . . . . . . . . . . . . . . . . . . .
Boolean OR (OR, OR (), ORN, ORN ()) . . . . . . . . . . . . . . . . . . . . . . . . . .
Boolean exclusive OR (XOR, XOR (), XORN, XORN ()) . . . . . . . . . . . . .
Invert (NOT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Addition (ADD and ADD ()) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Subtraction (SUB and SUB ()). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Multiplication (MUL and MUL()). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Division (DIV and DIV ()) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compare on "Greater Than" (GT and GT ()). . . . . . . . . . . . . . . . . . . . . . .
Compare to "Greater than/Equal to" (GE and GE ()) . . . . . . . . . . . . . . . .
Compare to "EQual to"(EQ and EQ ()) . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compare to "Not Equal to" (NE and NE ()) . . . . . . . . . . . . . . . . . . . . . . . .
Compare to "Less than/Equal to" (LE and LE ()). . . . . . . . . . . . . . . . . . . .
Compare to "Less Than"(LT and LT ()) . . . . . . . . . . . . . . . . . . . . . . . . . . .
33002204 12/2010
293
294
297
299
302
305
307
310
311
313
316
319
321
322
322
324
325
327
329
331
334
336
338
339
340
341
342
344
346
348
350
352
353
354
355
357
359
360
361
362
363
364
7
Jump to label (JMP, JMPC and JMPCN). . . . . . . . . . . . . . . . . . . . . . . . .
Call Function Block/DFB (CAL, CALC and CALCN) . . . . . . . . . . . . . . . .
FUNCNAME. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Right parenthesis ")" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.4 Call up of functions, Function Blocks (EFBs) and Derived Function Blocks
(DFBs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of Function Blocks and DFBs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Invoking a Function Block/DFB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function call. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.5 Syntax check and Code generation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Syntax Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Code generation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.6 Online functions of the IL instruction list . . . . . . . . . . . . . . . . . . . . . . . . .
Animation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Monitoring field. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.7 Creating a program with the IL instruction list . . . . . . . . . . . . . . . . . . . . .
Creating a program in the IL instruction list. . . . . . . . . . . . . . . . . . . . . . .
371
372
374
379
381
382
384
385
386
389
390
390
Chapter 11 Structured text ST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
393
11.1
General information about structured Text ST. . . . . . . . . . . . . . . . . . . . .
General Information about the ST Structured Text . . . . . . . . . . . . . . . . .
11.2 Expressions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11.3 Operators of the programming language of structured ST text . . . . . . . .
Use of parentheses "()" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FUNCNAME. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exponentiation (**) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Negation (-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Complement formation (NOT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Multiplication (*) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Division (/) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modulo (MOD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Addition (+) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Subtraction (-) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comparison on "Greater Than" (>) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comparison on "Greater than/Equal to" (>=) . . . . . . . . . . . . . . . . . . . . . .
Comparison with "EQual to" (=) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comparison with "Not Equal to" (<>) . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comparison with "Less Than"(<) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comparison with "Less than or Equal to" (<=) . . . . . . . . . . . . . . . . . . . . .
Boolean AND (AND or &). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Boolean OR (OR). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Boolean Exclusive OR (XOR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
365
368
369
370
394
394
396
397
399
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
33002204 12/2010
11.4 Assign instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Declaration (VAR...END_VAR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IF...THEN...END_IF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELSIF...THEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CASE...OF...END_CASE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FOR...TO...BY...DO...END_FOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WHILE...DO...END_WHILE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REPEAT...UNTIL...END_REPEAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EXIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Empty instruction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11.5 Call up of functions, Function Blocks (EFBs) and Derived Function Blocks
(DFBs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function Block/DFB Invocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function Invocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11.6 Syntax check and code generation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Syntax Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Code generation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11.7 Online functions of the ST programming language . . . . . . . . . . . . . . . . . .
Online functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11.8 Creating a program with the structured ST text. . . . . . . . . . . . . . . . . . . . .
Creating a program in structured ST text . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 12 Ladder Logic 984 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.1 General about Ladder Logic 984. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General about Ladder Logic 984. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.2 Working with Ladder Logic 984 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Entering and Editing Logic Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Entering and Editing Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ladder and Network Editing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Zoom and DX Zoom . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Search and Replace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.3 Subroutines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Subroutines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.4 Equation Network Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Equation Editing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Syntax and Semantics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.5 LL984 Programming Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LL984 Programming Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33002204 12/2010
422
423
424
426
428
429
430
431
432
435
437
438
439
440
441
442
446
448
449
450
451
451
452
452
455
456
456
458
459
461
464
466
468
469
469
471
472
474
476
480
480
9
Chapter 13 DFBs (Derived Function Blocks) . . . . . . . . . . . . . . . . . . .
13.1
482
483
485
487
489
496
499
501
502
503
504
507
511
513
515
517
519
520
Chapter 14 Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
521
14.1
10
481
DFBs (Derived Function Blocks) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General information about DFBs (Derived Function Blocks) . . . . . . . . . .
Global / Local DFBs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of variables in DFBs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combined Input/Output Variables (VARINOUT Variables) . . . . . . . . . . .
Global Variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Creating Context Sensitive Help (Online Help) for DFBs. . . . . . . . . . . . .
13.2 Programming and calling up a DFB . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Creating the DFB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Creating the Logic in FBD Function Block Language . . . . . . . . . . . . . . .
Creating the Logic in LD Ladder Diagram . . . . . . . . . . . . . . . . . . . . . . . .
Creating the Logic in IL Instruction List . . . . . . . . . . . . . . . . . . . . . . . . . .
Creating the Logic in ST Structured Text. . . . . . . . . . . . . . . . . . . . . . . . .
Calling up a DFB in the FBD Function Block dialog. . . . . . . . . . . . . . . . .
Calling up a DFB in Ladder Diagram LD . . . . . . . . . . . . . . . . . . . . . . . . .
Calling up a DFB in the IL instruction list . . . . . . . . . . . . . . . . . . . . . . . . .
Calling up a DFB in structured text ST. . . . . . . . . . . . . . . . . . . . . . . . . . .
Macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Macros: general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Global / Local Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exchange marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Creating Context Sensitive Help (Online Help) for Macros . . . . . . . . . . .
14.2 Programming and calling up a macro . . . . . . . . . . . . . . . . . . . . . . . . . . .
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Occupying the macro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Creating the logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Calling up a macro from an SFC section . . . . . . . . . . . . . . . . . . . . . . . . .
Calling a macro from an FBD/LD section. . . . . . . . . . . . . . . . . . . . . . . . .
522
523
525
527
529
531
532
533
534
537
540
Chapter 15 Variables editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
543
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Declare variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Searching and replacing variable names and addresses . . . . . . . . . . . .
Searching and Pasting Variable Names and Addresses . . . . . . . . . . . . .
Exporting located variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
544
545
548
552
556
Chapter 16 Project Browser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
557
General information about the Project Browser . . . . . . . . . . . . . . . . . . . .
Detailed view in the project browser . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating the Project Browser. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
558
561
563
33002204 12/2010
Chapter 17 Derived data types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17.1 General information on Derived Data Types . . . . . . . . . . . . . . . . . . . . . . .
Derived Data Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Global / Local Derived Data Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Extended Data Type Definition (larger than 64 Kbytes) . . . . . . . . . . . . . .
17.2 Syntax of the data type editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Elements of the Derived Data Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Key Words. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Names of the derived datatypes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Separators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17.3 Derived data types using memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of Memory by Derived Data Types . . . . . . . . . . . . . . . . . . . . . . . . . .
17.4 Calling derived data types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Calling Derived Data Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 18 Reference data editor . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information about the Reference Data Editor . . . . . . . . . . . . . . .
Converting RDE templates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing signal states of a Located variable . . . . . . . . . . . . . . . . . . . . . .
Cyclical Setting of Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unconditional locking of a section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Animation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacing variable names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Load reference data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 19 ASCII Message Editor. . . . . . . . . . . . . . . . . . . . . . . . . . . .
19.1 ASCII Editor Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generals to ASCII editor dialog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Spaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Carriage Return. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flush (buffer) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repeat. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
19.2 User Interface of ASCII Message Editor . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Use the ASCII Message Editor . . . . . . . . . . . . . . . . . . . . . . . . . . .
Message Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Message Text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Simulation Text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
19.3 How to Continue after Getting a Warning . . . . . . . . . . . . . . . . . . . . . . . . .
How to Continue after Getting a Warning . . . . . . . . . . . . . . . . . . . . . . . . .
19.4 ASCII Editor in Offline/Combination/Direct Modes . . . . . . . . . . . . . . . . . .
ASCII Message Editor in Offline/Combination/Direct Modes . . . . . . . . . .
33002204 12/2010
565
566
567
570
572
574
575
577
582
583
585
586
586
588
588
595
596
598
600
602
605
606
608
609
611
612
613
614
615
616
617
618
619
620
621
622
624
626
627
628
628
629
629
11
Chapter 20 Online functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20.1
632
632
633
634
637
638
639
644
646
647
648
649
650
651
652
654
655
656
659
660
663
664
665
667
670
671
672
674
677
679
681
682
684
685
685
687
687
Chapter 21 Import/Export . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
691
21.1
21.2
21.3
12
631
General information about online functions . . . . . . . . . . . . . . . . . . . . . . .
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20.2 Connect to PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Presettings for ONLINE operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modbus Network Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modbus Plus Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modbus Plus Bridge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TCP/IP-Network Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting IEC Simulator (32 bit) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
State of the PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20.3 Setting up and controlling the PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Time for Constant Scans . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Single Sweeps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Deleting memory zones from the PLC . . . . . . . . . . . . . . . . . . . . . . . . . . .
Speed optimized LL984-Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Save To Flash . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reactivate flash save. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Set PLC Password. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20.4 Selecting Process information (status and memory) . . . . . . . . . . . . . . . .
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLC state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Memory Statistics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20.5 Loading a project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Download Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Uploading the PLC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Upload Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20.6 Section animation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IEC-Sections animation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LL984 Programming Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20.7 Online Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostics Viewer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20.8 Logging Write Access to the PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Logging and Encrypted Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information about Import/Export. . . . . . . . . . . . . . . . . . . . . . . . .
General Information about Import/Export. . . . . . . . . . . . . . . . . . . . . . . . .
Exporting sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exporting Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exporting variables and derived data types . . . . . . . . . . . . . . . . . . . . . . .
Exporting variables and Derived Data Types. . . . . . . . . . . . . . . . . . . . . .
692
692
694
694
697
697
33002204 12/2010
21.4 Section import . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Importing Sections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Procedure for importing sections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Importing IL and ST Programs to FBD, SFC, IL or ST Sections (with
Conversion) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Importing (insert file) IL and ST programs into IL or ST sections . . . . . . .
Procedure for "Copying" an IL section from an existing project into a new
project.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Procedure for converting FBD sections from an existing project into IL
sections of a new project. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21.5 Variables import . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Importing Variables in "Text Delimited" Format. . . . . . . . . . . . . . . . . . . . .
Importing structured variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Importing variables in Factory Link format . . . . . . . . . . . . . . . . . . . . . . . .
Multiple Address Assignment after Variable Import . . . . . . . . . . . . . . . . .
21.6 Import/Export of PLC Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Import/Export of PLC Configuration using Concept . . . . . . . . . . . . . . . . .
Import/Export of PLC Configuration using Concept Converter . . . . . . . . .
Chapter 22 Documentation and Archiving. . . . . . . . . . . . . . . . . . . . .
22.1 Documentation of projects, DFBs and macros . . . . . . . . . . . . . . . . . . . . .
Documentation contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Documentation Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defining Page Breaks for Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of keywords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22.2 Managing projects, DFBs and macros . . . . . . . . . . . . . . . . . . . . . . . . . . .
Archiving projects, used DFBs, EFBs and data type files . . . . . . . . . . . . .
Deleting projects, DFBs and macros. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 23 Simulating a PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23.1 Simulating a PLC (16-bit simulator). . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Simulating a Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23.2 Simulating a PLC (32-bit simulator). . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Concept-PLCSIM32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Simulating a PLC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Simulating a TCP/IP interface card in Windows 98. . . . . . . . . . . . . . . . . .
Simulating a TCP/IP interface card in Windows NT . . . . . . . . . . . . . . . . .
Chapter 24 Concept Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
698
699
703
709
712
713
714
716
717
720
724
725
726
727
728
729
730
731
732
735
739
740
741
743
745
746
746
748
749
751
753
754
757
General Description of Concept Security . . . . . . . . . . . . . . . . . . . . . . . . .
Access Rights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing Passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Activating Access Rights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protecting Projects/DFBs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
758
760
767
769
770
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
773
33002204 12/2010
13
Appendix A Tables of PLC-dependent Performance Attributes. . . . .
775
Performance of Quantum. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Performance Attributes of Compact. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Performance Attributes of Momentum . . . . . . . . . . . . . . . . . . . . . . . . . . .
Performance Attributes of Atrium. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
776
781
786
792
Appendix B Windows interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
799
B.1
Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Window Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Elements of a window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Menu commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Menu commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dialog boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dialog boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generating a project symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Creating a Project Symbol in a Program Group. . . . . . . . . . . . . . . . . . . .
Online help. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How the Online Help is set out. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
800
801
803
806
806
808
808
811
811
813
814
815
Appendix C List of symbols and short cut keys . . . . . . . . . . . . . . . . .
819
C.1 Icon bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General icon bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Icon bar in the FBD editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Icon bar in the SFC-Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Icon bar in the LD editor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
List of Symbols in the IL and ST Editor . . . . . . . . . . . . . . . . . . . . . . . . . .
List of Symbols in the LL984-Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Icons in PLC Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Toolbar in the RDE Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Toolbar in the Project Browser. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.2 Short cut keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Short Cut Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Short Cut Keys in the IL, ST and Data Type Editor . . . . . . . . . . . . . . . . .
Short Cut Keys in the FBD and SFC Editor . . . . . . . . . . . . . . . . . . . . . . .
Shortcut keys in the LD-Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Short Cut Keys in the LL984-Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
820
821
822
823
825
827
828
829
830
831
832
833
834
837
841
847
Appendix D IEC conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
849
D.1 What is the IEC 1131-3 standard?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General information about IEC conformity. . . . . . . . . . . . . . . . . . . . . . . .
IEC Conformity Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D.2 IEC standards tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Common elements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IL (AWL) language elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ST language elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
850
851
852
853
854
861
863
B.2
B.3
B.4
B.5
14
33002204 12/2010
Common graphic elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LD (KOP) language elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Implementation-dependent parameters . . . . . . . . . . . . . . . . . . . . . . . . . .
Error causes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D.3 Expansions of IEC 1131-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Expansions of IEC 1131-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D.4 Text language syntax . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Text Language Syntax . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix E Configuration examples. . . . . . . . . . . . . . . . . . . . . . . . . .
E.1
E.2
E.3
E.4
E.5
E.6
E.7
E.8
E.9
33002204 12/2010
Quantum Example - Remote Control with RIO . . . . . . . . . . . . . . . . . . . . .
Editing local drop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Editing Remote Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quantum Example - Remote control with RIO (series 800) . . . . . . . . . . .
Editing Local Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Editing Remote Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Editing Remote Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quantum Example - Remote Control with DIO . . . . . . . . . . . . . . . . . . . . .
Editing Local Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Editing Local Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quantum Example – INTERBUS Control . . . . . . . . . . . . . . . . . . . . . . . . .
General Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Editing Local Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quantum Example - SY/MAX Controller . . . . . . . . . . . . . . . . . . . . . . . . . .
Editing Local Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Editing Remote Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quantum Example - Profibus DP Controller . . . . . . . . . . . . . . . . . . . . . . .
General Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Profibus DP Export Settings in SyCon . . . . . . . . . . . . . . . . . . . . . . . . . . .
Editing Local Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Importing Profibus DP Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quantum-Example - Peer Cop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generals to Peer Cop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration of Peer Cop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Global data transfer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specific data transfer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compact Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Editing Local Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Atrium Example – INTERBUS Controller . . . . . . . . . . . . . . . . . . . . . . . . .
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INTERBUS export settings in CMD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Edit local I/O drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Edit remote I/O drop (import INTERBUS configuration) . . . . . . . . . . . . . .
865
866
868
871
873
873
875
875
877
878
879
884
887
888
893
897
900
901
906
910
911
912
916
917
922
925
926
927
929
934
941
942
944
946
948
950
950
955
956
957
958
962
15
E.10 Momentum Example - Remote I/O Bus . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Editing local drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 10 – Editing Remote Drops (I/O Bus) . . . . . . . . . . . . . . . . . . . .
E.11 Momentum Example - Ethernet Bus System . . . . . . . . . . . . . . . . . . . . . .
Configure Ethernet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Network Configuration in Different Operating Systems . . . . . . . . . . . . . .
Editing local drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Create online connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
965
966
967
971
974
975
976
986
990
Appendix F Convert Projects/DFBs/Macros . . . . . . . . . . . . . . . . . . . .
991
Converting projects/DFBs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
991
Appendix G Concept ModConnect . . . . . . . . . . . . . . . . . . . . . . . . . . . .
995
G.1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integration of Third Party Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrating new Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of third party module in Concept. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of Third Party Modules in Concept . . . . . . . . . . . . . . . . . . . . . . . . . .
996
996
997
998
999
1000
1000
Appendix H Convertion of Modsoft Programs. . . . . . . . . . . . . . . . . . .
1001
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Convert a Modsoft Program. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exceptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1002
1004
1005
Appendix I Modsoft and 984 References . . . . . . . . . . . . . . . . . . . . . .
1007
Modsoft Keys with Concept Equivalents . . . . . . . . . . . . . . . . . . . . . . . . .
Modsoft Function Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1008
1010
Appendix J Presettings when using Modbus Plus for startup . . . . .
1011
Installing the SA85/PCI85 with Windows 98/2000/XP . . . . . . . . . . . . . . .
Installing the SA85/PC185 in Windows NT . . . . . . . . . . . . . . . . . . . . . . .
Installing the Modbus Plus Driver in Windows 98/2000/NT . . . . . . . . . . .
Virtual MBX Driver for 16 bit application capability with Windows
98/2000/NT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MBX Driver for connection between ModConnect Host interface adapters
and 32 bit applications with Windows 98/2000/NT . . . . . . . . . . . . . . . . .
Remote MBX - Driver for Remote Operation . . . . . . . . . . . . . . . . . . . . . .
Ethernet MBX - Driver for Modbus Plus Function via TCP/IP . . . . . . . . .
Establishing the hardware connection. . . . . . . . . . . . . . . . . . . . . . . . . . .
1012
1016
1018
Appendix K Presettings when using Modbus for startup. . . . . . . . . .
1025
Interface Settings in Windows 98/2000/XP . . . . . . . . . . . . . . . . . . . . . . .
Interface Settings in Windows NT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting up the hardware connection . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transfer problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1026
1028
1029
1030
G.2
G.3
16
1019
1020
1021
1022
1024
33002204 12/2010
Appendix L Startup when using Modbus with the EXECLoader . . .
Quantum first startup with EXECLoader . . . . . . . . . . . . . . . . . . . . . . . . . .
Compact first startup with EXECLoader . . . . . . . . . . . . . . . . . . . . . . . . . .
Momentum first startup for IEC with EXECLoader . . . . . . . . . . . . . . . . . .
Momentum first startup for LL984 with EXECLoader . . . . . . . . . . . . . . . .
Appendix M Startup when using Modbus with DOS Loader . . . . . . .
1031
1032
1036
1040
1044
1049
Quantum first startup with DOS Loader . . . . . . . . . . . . . . . . . . . . . . . . . .
Compact first startup with DOS Loader. . . . . . . . . . . . . . . . . . . . . . . . . . .
Momentum first startup for IEC with DOS Loader . . . . . . . . . . . . . . . . . . .
Momentum first startup for LL984 with DOS Loader . . . . . . . . . . . . . . . . .
1050
1053
1056
1059
Appendix N Startup when using Modbus Plus with the EXECLoader
1063
Quantum first startup with EXECLoader . . . . . . . . . . . . . . . . . . . . . . . . . .
Compact first startup with EXECLoader . . . . . . . . . . . . . . . . . . . . . . . . . .
Atrium first startup with EXECLoader . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Momentum first startup for IEC with EXECLoader . . . . . . . . . . . . . . . . . .
Momentum first startup for LL984 with EXECLoader . . . . . . . . . . . . . . . .
1064
1068
1072
1076
1080
Appendix O Startup when using Modbus Plus with DOS Loader . . .
Quantum first startup with DOS Loader . . . . . . . . . . . . . . . . . . . . . . . . . .
Compact first startup with DOS Loader. . . . . . . . . . . . . . . . . . . . . . . . . . .
Atrium first startup with DOS Loader. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Momentum first startup for IEC with DOS Loader . . . . . . . . . . . . . . . . . . .
Momentum first startup for LL984 with DOS Loader . . . . . . . . . . . . . . . . .
Appendix P EXEC files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Loading Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix Q INI Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Q.1 Settings in the CONCEPT.INI File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General information on the Concept INI file . . . . . . . . . . . . . . . . . . . . . . .
INI Print Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INI Settings for Register Address Format, Variable Storage and Project
Name Definition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INI-settings for path information and global DFBs [Path] [Upload] . . . . . .
Representation of Internal Data in the INI File . . . . . . . . . . . . . . . . . . . . .
INI Settings for the LD Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INI Settings for Online Processing [Colors] . . . . . . . . . . . . . . . . . . . . . . . .
INI Settings for Warning Messages and the Address Format . . . . . . . . . .
INI Security Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INI-Settings for the RDE behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INI settings for the Options> Toolsmenu. . . . . . . . . . . . . . . . . . . . . . . . . .
Q.2 Settings in the Projectname.INI File . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information for Projectname.INI File . . . . . . . . . . . . . . . . . . . . . .
INI Settings for the Event Viewer [Online Events] . . . . . . . . . . . . . . . . . . .
INI-Settings for the Online-Backup [Backup]. . . . . . . . . . . . . . . . . . . . . . .
33002204 12/2010
1085
1086
1089
1092
1095
1098
1101
1101
1105
1106
1107
1108
1109
1110
1113
1114
1115
1116
1117
1118
1119
1120
1121
1122
1123
17
18
Appendix R Interrupt Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1125
R.1 General information about interrupt sections . . . . . . . . . . . . . . . . . . . . . .
General Information about Interrupt Processing . . . . . . . . . . . . . . . . . . .
R.2 Interrupt section: Timer event section . . . . . . . . . . . . . . . . . . . . . . . . . . .
Timer Event Sections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defining the Scan Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defining the Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Execution Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Examples for Parameterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
R.3 Interrupt section: I/O event section . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O Event Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Priority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Runtime Error. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
R.4 Modules for interrupt sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EFBs for Interrupt Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1126
1126
1128
1129
1130
1131
1134
1135
1137
1141
1142
1143
1144
1146
1146
Appendix S Automatic Connection to the PLC . . . . . . . . . . . . . . . . . .
1147
Automatic Connection with Command Line Parameters (Modbus,
Modbus +, TCP/IP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Automatic Connection with the CCLaunch Tool (Modbus Plus) . . . . . . .
1148
1151
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1157
1187
33002204 12/2010
Safety Information
§
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with
the device before trying to install, operate, or maintain it. The following special
messages may appear throughout this documentation or on the equipment to warn
of potential hazards or to call attention to information that clarifies or simplifies a
procedure.
33002204 12/2010
19
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by
qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction
and operation of electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved.
20
33002204 12/2010
About the Book
At a Glance
Document Scope
This user manual is intended to help you create a user program with Concept. It
provides authoritative information on the individual program languages and on
hardware configuration.
Validity Note
The documentation applies to Concept 2.6 for Microsoft Windows 98, Microsoft
Windows 2000, Microsoft Windows XP and Microsoft Windows NT 4.x.
NOTE: Additional up-to-date tips can be found in the Concept README file.
Related Documents
Title of Documentation
Reference Number
Concept Installation Instructions
840 USE 502 00
Concept IEC Block Library
840 USE 504 00
Concept EFB User Manual
840 USE 505 00
Concept LL984 Block Library
840 USE 506 00
You can download these technical publications and other technical information from
our website at www.schneider-electric.com.
User Comments
We welcome your comments about this document. You can reach us by e-mail at
[email protected].
33002204 12/2010
21
22
33002204 12/2010
General description of Concept
33002204 12/2010
General description of Concept
1
Overview
This chapter contains a general description of Concept. It should provide an initial
overview of Concept and its helper programs.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
1.1
General description of Concept
24
1.2
Programming
29
23
General description of Concept
1.1
General description of Concept
Overview
This section describes the performance features of Concept and provides an
overview of the hardware that may be programmed using Concept.
What's in this Section?
This section contains the following topics:
Topic
24
Page
Introduction
25
PLC hardware configuration
27
PLC Hardware Package Contents in Concept S, M and XL
28
33002204 12/2010
General description of Concept
Introduction
Operating System
Nowadays, a graphical user interface is a requirement for tasks of this kind. For this
reason, Concept has been established as an MS Windows application. Concept can
be operated in Windows 98, Windows 2000, Windows XP and Windows NT. These
operating systems have the advantage that they are used all over the world.
Therefore PC users have a basic knowledge of Windows technology and mouse
operation. In addition to this all common monitors, graphic cards and printers can be
used with MS Windows. As a user, you are not therefore tied to specific hardware
configurations.
International Standard IEC 1131-3
For effective system configuration Concept offers a unified configuration
environment in accordance with international standard regulations IEC 1131-3.
PLC Independence when Programming
The guiding principle behind the development of Concept was that all the system
configuration procedures and all the editors should have the same look and feel.
Most of the configuration steps, especially program creation, are designed
independently of the PLC to be programmed.
Graphical Interface
The entire program is divided up into sections corresponding to the logic structure.
The Concept configuration tool enables objects (such as function blocks, steps, and
transitions) to be selected, placed and moved easily in graphical form. Plausibility
tests already take place in the SFC editor (Sequential Function Chart/ sequence
language) during object placing, as most of the links between objects are generated
automatically during placing. In the FBD editor (Function Block Diagram/Function
Block language) and LD editor (Ladder Diagram), plausibility tests take place when
blocks are linked. Unauthorized links, such as those between different data types
have already been rejected during configuration. A plausibility test also takes place
in the LL984 editor (Ladder Logic 984) during placing. In the IL editor (Instruction
List) and ST editor (Structured Text) unauthorized instructions are identified via a
colored outline. After the first successful program run, the program may be
optimized in graphic terms by moving links, blocks or texts to improve the display.
33002204 12/2010
25
General description of Concept
Print
If desired the sections may be displayed with print preview information, in order to
individually control pages of documentation. Signals receive an expansive
designation with symbol names and comments. Unique notes on signal tracking are
provided at the signal breaks. The individual block processing sequences from one
section may be displayed and documented in the FBD editor.
Import/Export Functions
Sections from various projects can be combined as desired in another project using
import/export functions.
It is also possible to convert the sections of one IEC programmer language into
sections of another IEC programmer language.
Variables may be imported into and exported from the text using text delimited or
FactoryLink format.
Runtime System
The runtime system on the PLC offers quick reactions to signal state process
changes (short cycle time), Simulating signal transmitters (see page 745), Online
display (see page 631), online parameter changes and online program changes.
Open Software Architecture
Concept possesses open software architecture to enable connection to external
systems (e.g. for visualization) via standard interfaces.
Online Help
Special care was taken when developing the help function. The context sensitive
Online help function (see page 815) provides support for every configuration
situation just by clicking on the subject using the mouse or pressing the F1 key.
Menu commands and dialogs are also context sensitive, as are, function blocks and
hardware components of the individual PLC families.
26
33002204 12/2010
General description of Concept
PLC hardware configuration
Description
Concept is the unified projection tool for Quantum, Compact, Momentum and Atrium
products.
Hardware components (for example CPU, program memory, input/output units etc.)
can be specified before, during or after program creation.
This projection task can be performed both online (linked to the PLC) and locally (PC
alone). Projection is supported by Concept, and only suggests valid combinations.
Misprojection is therefore prevented. In online mode the projected hardware is
tested for plausibility immediately and input errors are rejected.
After linking the programmer device (PC) to the PLC, a plausibility test is performed
on the projected values (e.g. from the Variable Editor) using the actual hardware
resources and if necessary an error message will appear.
33002204 12/2010
27
General description of Concept
PLC Hardware Package Contents in Concept S, M and XL
Description
PLC Hardware Package Contents in Concept S, M and XL:
28
Concept version
contain Hardware
Concept Vx.x S
Momentum
Concept Vx.x M
Compact, Momentum
Concept Vx.x XL
Atrium, Compact, Momentum, Quantum
33002204 12/2010
General description of Concept
1.2
Programming
Overview
This section provides an overview of the editors which are available in Concept.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
General information
30
Libraries
31
Editors
33
Online functions
37
Communication
38
Secure Application
39
Utility program
41
29
General description of Concept
General information
At a Glance
As a solution for automatic control engineering tasks, Concept provides the following
IEC 1131-3 compatible programming languages:
z Function Block language FBD (Function Block Diagram) (see page 33),
z LD (Ladder Diagram) (see page 34),
z Sequential language SFC (Sequential Function Chart) (see page 34),
z Instruction List IL (see page 34) and
z Structured Text ST (see page 35).
The Modsoft orientated language is also available
Ladder Diagram LL984 (Ladder Logic) (see page 35).
z
The IEC programming language (FBD, LD, SFC, ST and IL) basic elements are
Functions and Function Blocks, which make up assembled logic units. Concept
contains various Block libraries (see page 31) with predefined elementary
functions/Function Blocks (EFBs). In order to locate the individual EFBs without
difficulty, they are split into different groups according to their area of use.
For the Modsoft orientated programming language LL984, there is a Block library
(see page 31) with Instructions available.
Sections
The control program is constructed from sections according to the logic structure.
Only one programming language is used within a section.
Merging these sections makes up the entire control program and the automation
device uses this to control the process. Any IEC sections (FBD, LD, SFC, IL, ST)
may be mixed within the program. The LL984 sections are always edited as a block
before the IEC sections.
Data types
A subset of Data types from the international standard IEC1131-3 is available.
In the Data type editor (see page 36) intrinsic data types can be derived from IEC
data types.
Using variables
Variables for linking basic elements (objects) within a section are not usually
necessary with the graphic programming languages FBD, LD, SFC and LL984, as
these links are usually made graphically. (An additional link using variables is only
necessary for incredibly complex sections.) Graphic links are managed by the
system and therefore no projection requirement is created. The Variable Editor
(see page 36) is used to project all other variables such as those for data transfer
between various sections.
30
33002204 12/2010
General description of Concept
Libraries
At a Glance
For program creation Concept provides various block libraries with predefined
Functions and Function Blocks.
There are 2 different types of block libraries:
IEC library
Block libraries for sections in the IEC programming languages (FBD, LD, SFC, IL
and ST)
z LL984 Library
Block library for sections in the Modsoft orientated programming language LL984
z
IEC library
The following IEC libraries are available for applications:
z AKFEFB
This library contains the AKF/ALD EFBs, which are not covered by the IEC
library.
z ANA_IO
This library is for analog value processing.
z COMM
This library is used for exchanging data between a PLC and another Modbus,
Modbus Plus or Ethernet node.
z CONT_CTL
This library is for projecting process-engineering servoloops. It contains
controller, differential, integral, and polygon graph EFBs.
z DIAGNOSTICS
This library is used to investigate the control program for misbehaviors. It
contains action diagnostics, Reaction diagnostics, locking diagnostics, process
prerequisite diagnostics, dynamic diagnostics and signal group monitoring EFBs.
z EXPERTS
This library contains EFBs, which are necessary for using expert modules.
z EXTENDED
This library contains useful supplements for different libraries. It has EFBs for
creating average values, selecting maximum values, negating, triggering,
converting, creating a polygon with 1st degree interpolation, edge recognizing,
and for specifying an insensitive zone for control variables.
z FUZZY
This library contains EFBs for fuzzy logic.
z IEC
This library contains the EFBs defined in IEC 1131-3. It has for example EFBs for
mathematical calculations, counters, timers etc.
33002204 12/2010
31
General description of Concept
z
z
LIB984
This library contains IEC 1131 compatible EFBs from the LL984 library, for
example, EFBs for register transfer.
SYSTEM
This library contains EFBs for using system functions. It has EFBs for cycle time
recognition, for various system cycle use, for SFC section control and for system
status display.
LL984 Library
The LL984 library contains the LL984 editor instructions (blocks). It contains
instructions for mathematical calculations, counters, timers, instructions for
displaying system status, controller, differential and integral instructions and
instructions for exchanging data between a PLC and another Modbus or Modbus
Plus node.
32
33002204 12/2010
General description of Concept
Editors
At a Glance
When generating a section specify which programming language you are going to
use.
The following editors are available for creating sections in the various programming
languages:
z FBD editor (Function Block Language) (see page 33)
z LD editor (Ladder Diagram) (see page 34)
z SFC editor (Sequence language) (see page 34)
z IL editor (Instruction List) (see page 34)
z ST editor (Structured Text) (see page 35)
z LL984 editor (Modsoft orientated Ladder Logic) (see page 35)
The following editors are available for declaring variables, creating data types and
displaying variables.
z the Variable Editor (for declaring variables), (see page 36)
z the reference data editor (for displaying and online changing of values)
(see page 36) and
z the data type editor (for creating user specific data types) (see page 36).
The following editors are available for creating user specific functions and Function
Blocks:
z Concept DFB (for creating Derived Function Blocks and macros) (see page 41)
z Concept EFB (for creating user specific elementary functions and Function
Blocks) (see page 42)
FBD editor
The FBD editor (see page 213) is used for graphic function plan programming
according to IEC 1131-3.
Elementary functions, Elementary Function Blocks (EFBs) and Derived Function
Blocks (DFBs) are connected with signals (variables) onto FBD sections for the
function plan. The size of a FBD section is 23 lines and 30 columns.
EFBs are equipped with a fixed or variable number of input variables and may be
placed anywhere on the section. Variables and EFBs may have comments
separately added to them, column layouts on a section may be commented on
anywhere using text boxes. All EFBs may be performed conditionally or
unconditionally.
All the EFBs are divided into function- and use-orientated libraries in various groups,
to make them easier to locate.
33002204 12/2010
33
General description of Concept
LD editor
The LD editor (see page 239) is used for graphic ladder programming according to
IEC 1131-3.
Contacts and coils are connected to the Ladder Diagram in LD sections using
signals (variables).
The size of a FBD section is 23 lines and 30 columns.
Furthermore, the elementary functions and Function Blocks (EFBs), which are
named in the FBD editor, the Derived Function Blocks (DFBs) and User Defined
Function Blocks (UDFBs) may also be bound in the ladder diagram (see FBD editor,
page 33).
The structure of a LD section corresponds to a rung for relay switching. The left
power rail is located on its left-hand side. This left power rail corresponds to the
phase (L ladder) of a rung. With LD programming, in the same way as in a rung, only
the LD objects (contacts, coils) which are linked to a power supply, that is to say
connected with the left power rail, are "processed". The right power rail, which
corresponds to the neutral ladder, is not shown optically. However, all coils and EFB
outputs are linked with it internally and this creates a power flow.
SFC editor
The SFC editor (see page 271) is used to graphically program an IEC 1131-3
compatible sequential control.
The SFC elements are connected in a SFC section to one of the sequential controls
corresponding to the task setting. The size of a SFC section is 32 lines and 200 lines.
The following sequential control programming objects are available in Concept.
Step (including actions and action sections)
z Transition (including transition section)
z Alternative branch and merge
z Parallel branch and merge
z Jump
z Connection
z
Simple diagnostics monitoring functions are already integrated in the steps.
IL editor
The IL editor (see page 321) is used for programming IEC 1131-3 compatible
instruction lists.
Existing IL instructions, elementary functions and Elementary Function Blocks
(EFBs), and Derived Function Blocks (DFBs) are written in series in text form in IL
sections from operators (commands) and operands (signals, variables).
34
33002204 12/2010
General description of Concept
When the program is entered, all the standard Windows services and some
additional commands for text-processing are available. The size of an IL section is
64 Kbyte maximum.
The following instruction list programming operators are available in Concept:
z Logic (AND, OR etc.)
z Arithmetic (ADD, SUB, MUL, DIV, …)
z Comparative (EQ, GT, LT, …)
z Jumps (JMP, … conditional/unconditional)
z EFB call (CAL , … conditional/unconditional)
IL programming is done in text form. When text is entered, all the standard Windows
services for text-processing are available. The IL editor also contains some further
commands for text-processing.
A spell check is performed immediately after text has been entered (instructions, key
words, separators), highlighting errors with a colored outline.
ST editor
The ST editor (see page 393) is used for programming IEC 1131-3 structured text.
Existing ST statements, elementary functions and Elementary Function Blocks
(EFBs), and Derived Function Blocks (DFBs) are written in text form in IL sections
by printing (operator lists) and operands (signals, variables).
When the program is entered, all the standard Windows services and some
additional commands for text-processing are available. The size of a ST section is
64 Kbyte maximum.
The following structured text programming statements and operators are available
in Concept:
z conditional/unconditional statement execution (IF, ELSIF, ELSE, …)
z conditional/unconditional loop execution (WHILE, REPEAT)
z Mathematical, comparative, and logic operators
z conditional/unconditional EFB call
ST programming is done in text form. When text is entered, all the standard
Windows services for text-processing are available. The ST editor also contains
some further commands for text-processing.
A spell check is performed immediately after text has been entered (instructions, key
words, separators), highlighting errors with a colored outline.
LL984 editor
Using the Modsoft orientated LL984-Editor (see page 455) (Ladder Diagram 984),
instructions, contacts, coils and signals (variables) are connected to a ladder
diagram. Instructions, contacts, coils and variables may be commented on.
33002204 12/2010
35
General description of Concept
The structure of a LL984 section corresponds to a rung for relay switching. The left
power rail is located on its left-hand side, but it is not visually displayed. This left
power rail corresponds to the phase (L ladder) of a rung. With LL984 programming,
in the same way as in a rung, only the LL984 objects (instructions, contacts, coils)
connected to a power supply, i.e. connected to the left power rail, are "processed".
The right power rail, which corresponds to the neutral ladder is not visually displayed
either. However, all coils and instruction outputs are linked with it internally and this
creates a power flow.
Concept has various predefined instructions for ladder programming using LL984.
These may be found in the block library LL984. Additional instructions for special
applications are available as loadables and may be loaded at a later time.
Variable Editor
The Variable Editor (see page 543) is used to declare and comment on all
necessary symbolic signal names (variables). Only declared variables may be used
in Concept programs.
A data type must be assigned to each symbolic signal name! If this variable is
assigned a reference address, a Located variable (without reference address =
Unlocated variable) is received. An initial value may also be provided for each
variable, which will be transferred into the PLC during the first load.
Data type editor (DDT editor)
The Data type editor (see page 565) may be used to define specific Derived Data
Types (Derived Data Type = DDT).
Derived Data Types combine several Elementary data types (BOOL, WORD, …) in
one data record. It is not only the same data types which may be combined as
ARRAY, but also various data types may be combined as STRUCT. In Concept, a
number of Derived Data Types are already available, which for instance may be
used for DFBs.
DDTs appear in DFBs or EFBs only as a connection, i.e. for instance in FBD a
variable input is only necessary in the block. It is thus recommended that frequently
recurring groups of elementary data types (and also DDTs) be defined as DDTs, in
order to improve accessibility of an application.
The definition appears in text form, and all the standard Windows services and some
additional commands for text-processing are available. The size of a data type file
is 64 Kbyte maximum.
Reference data editor
The Reference data editor (see page 595) may be used in online mode to display
the variable value, to force variables and to set variables. There is also the possibility
of separating variables from the process. Inputs may be saved in a data file and be
reused.
36
33002204 12/2010
General description of Concept
Online functions
Available online functions
After the programming device has been linked to the PLC, a range of online Startup
and maintenance functions become available.
z the program on the programming device is compared with the program on the
PLC
z the PLC can be started and stopped
z Object information is displayed
z Programs can be loaded, sections can be changed online and loaded
z Variable values can be entered online
z Animation mode shows the program with its current signal states
Operating and monitoring
Declaration of special operating and monitoring variables is not necessary in
Concept. The variables to be visualized can be identified as such in the Variable
Editor and then be exported into a ModLink or FactoryLink configuration data file.
This data file can be used for visualizing.
33002204 12/2010
37
General description of Concept
Communication
Description
Communication between the PLC and another Modbus-, Modbus Plus-, SY/MAXEthernet or TCIP/IP Ethernet node is projected using IEC languages (FBD, LD,
SFC, ST, IL) with the EFBs from the block library COMM. The instruction MSTR may
be used with the programming language LL984 to construct these communications.
A peer to peer transfer of register contents is possible using the peer cop,
independent of these blocks/instructions.
Communication is projected between the PLC and the decentralized I/O via the
INTERBUS by simply entering the NOA module in the component list and loading a
loadable (ULEX).
Communication is projected between the programming device and a PLC via
Ethernet by simply entering and parametering the appropriate couple module in the
component list.
38
33002204 12/2010
General description of Concept
Secure Application
At a Glance
In several areas of industry, the need for security demands regulated access to
PLCs, recording program changes and archiving those recordings. Following a
standardized procedure ensure that records may not be falsified. To enable these
requirements, new features have been implemented in Concept that ensure secure
application. To guarantee that all of these parameters are defined, the user can
activate the Secure Application check box in the Project →Project Properties
dialog. Concept will then ensure that all of these parameters are set and that their
contents remain valid. The project is then indicated as being a secure application,
and this information is included in the information that is downloaded to the PLC.
Secure Application
The secure application is defined in the Project →Project Properties dialog by
activating the Secure Application check box. These settings are then exported,
imported, read and loaded to the PLC.
NOTE: When the secure application is activated, a NOT EQUAL status is generated
and required reloading to the PLC. Unchecking the check box also creates a NOT
EQUAL status so that loading is again required as well. If Concept is connected to
a PLC that is already defined with the "Secure Application" setting, the setting is
automatically accepted in Concept in case of upload the controller.
The log file is stored in the Concept directory and has the name of the current date
(YEARMONTHDAY.ENC, e.g. 20020723.ENC). The path of the log file can be
defined in dialog Common Preferences. If no path is defined then Concept uses
the default log path (Concept directory, e.g. C:\CONCEPT).
Among other things, logging write-access to the PLC can record the following data:
z Section name
z EFB/DFB Instance name, FB Type name
z Pin Name
z [Variable name] [Literal] [Address]
z Old value
z New value
z User name (if the Concept (Login) password is activated in Concept Security)
z Data and Time (see alsoAddress format in LOG file [Logging], page 1116)
Requirements
The secure application can only be activated if the following prerequisites are met:
z can only be used with 140 CPU 434 12A or 140 CPU 534 14A/B
z at least one IEC section (if no IEC section exists then the download is aborted.)
z Offline mode (Online →Disconnect...)
z Supervisor Rights (see Concept under Help →About... →Current User:)
33002204 12/2010
39
General description of Concept
Activation Combination for Secure Application
Various Activation Combinations for Secure Application:
"Secure
Application"
activated in
Concept
"Secure
Application"
loaded to PLC
Reaction to connection with the PLC
Not activated
Not activated
Normal operation without secure application
Not activated
Activated
When uploading, the Secure Application
check box is activated in Concept and
encrypted logging is activated.
Activated
Not activated
Download required because the status is NOT
EQUAL.
Activated
Activated
Normal operation with secure application (e.g.
encrypted logging).
Reading the Encrypted Log File
To read the encrypted log file, the View tool is opened automatically in the View
Logfile dialog.
NOTE: If an encrypted log file has been improperly modified in any way, the log is
decoded as much as is possible, and the lines that have been modified will remain
unreadable. The first line will contain the message: "This log file has been modified".
40
33002204 12/2010
General description of Concept
Utility program
At a Glance
In addition to Concept the following range of utility programs are available:
z Concept DFB
z Concept EFB
z Concept SIM (16 bit)
z Concept PLCSIM32 (32 bit)
z Concept Security
z Concept WinLoader
z Concept Converter
z Concept ModConnect
Concept DFB
Concept DFB is used to create DFBs (Derived Function Blocks) (see page 481) and
Macros (see page 521).
DFBs (Derived Function Blocks)
DFBs can be used for setting both the structure and the hierarchy of a program. In
programming terms, a DFB represents a subroutine.
DFBs can be created in the programming languages FBD, LD, IL, and ST. In
Concept, DFBs can be called up in any programming language, regardless of the
programming language they were created in. One or several existing DFBs can be
called up within one DFB, with the called-up DFBs themselves able to call up one or
several DFBs.
Macros
Macros are used to duplicate frequently used sections and networks (including their
logic, variables and variable declaration).
Macros have the following properties:
z Macros can only be created in the programming language FBD.
z Macros only contain one section.
z Macros can contain a section of any complexity.
z In programming terms, there is no difference between an instanced macro, i.e. a
macro inserted into a section and a conventionally created section.
z It is possible to call up DFBs in a macro.
z It is possible to declare macro-specific variables for the macro.
z It is possible to use data structures specific to the macro
z Automatic transfer of the variables declared in the macro.
z Initial values are possible for the macro variables.
z It is possible to instance a macro many times in the entire program with different
variables.
z Section names, variable names and data structure names can contain the
character ~ as an exchange marking.
33002204 12/2010
41
General description of Concept
Concept EFB
The optional tool Concept EFB can be used to generate, in C++ programming
language, your own application specific Functions and Function Blocks (EFBs) and
to integrate them in the form of libraries with groups in your version of Concept.
The operating rules for these user-defined blocks (UDFBs) are identical to those for
standard EFBs.
It is, for instance, recommended that complex program parts with a high number of
calls and program parts, whose solution is to remain hidden from the user, e.g.
special technology objects etc. be generated using Concept EFB.
NOTE: Concept EFB is not included as part of the Concept package and may be
ordered in addition.
Concept SIM (16 bit)
The 16 bit simulator Concept SIM (see page 746) is available for simulating a PLC,
i.e. to test your user program online without hardware. Concept SIM simulates a
coupled PLC via Modbus Plus.
NOTE: The simulator is only available for the IEC languages (FBD, SFC, LD, IL and
ST).
Concept PLCSIM (32 bit)
The 32 bit simulator Concept PLCSIM32 (see page 748) is available for simulating
a PLC, i.e. to test your user program online without hardware. Concept PLCSIM32
simulates a PLC coupled via TCP/IP, where the signal states of the I/O modules can
also be simulated. Up to 5 programming devices can be coupled to the simulated
PLC at the same time.
NOTE: The simulator is only available for the IEC languages (FBD, SFC, LD, IL and
ST).
Concept Security
Concept Security (see page 757) can be used to assign access. Access signifies
that the function of Concept and its utility programs is limited depending on the user.
The access defined for one user is applicable to all Concept installation projects. A
maximum of 128 users may be defined.
Concept Converter
Projects, DFBs, macros, and data structures (Derived Data Types), created for an
earlier version of Concept, can be converted without hassle to work in the current
version of concept in the Concept Converter (see page 991).
42
33002204 12/2010
General description of Concept
Concept EXECLoader
The Concept EXECLoader can be used to load Exec data files onto the PLC.
Concept ModConnect
Concept-ModConnect (see page 995) can be used to extend the configurator for
new (specific) I/O modules.
33002204 12/2010
43
General description of Concept
44
33002204 12/2010
New Performance Attributes
33002204 12/2010
New Performance Attributes of
Concept 2.6 in Comparison with
Concept 2.5
2
Overview
This Chapter describes the new performance attributes of Concept 2.6 in
comparison with Concept 2.5.
What's in this Chapter?
This chapter contains the following topics:
Topic
33002204 12/2010
Page
New Performance Attributes of Concept 2.6 Compared with Concept 2.5
46
New performance attributes of Concept 2.6 SR2 in comparison with Concept
2.6 SR1
52
New performance attributes of Concept 2.6 SR3 in comparison with Concept
2.6 SR2
55
45
New Performance Attributes
New Performance Attributes of Concept 2.6 Compared with Concept 2.5
Highlights
New general performance attributes:
Interrupt sections
z Global variables
z Security features
z
New EFBs
New EFBs in the SYSTEM library:
New EFBs
Description
I_LOCK
Disable all interrupt sections
I_UNLOCK
Enable all interrupt sections
I_MOVE
Interrupt protected assignment
ISECT_OFF
Disable specific interrupt sections
ISECT_ON
Unlock a specific interrupt section
ISECT_STAT
Interrupt section status
PRJ_VERS
States project name and version
GET_IEC_INF
Read IEC status flags
RES_IEC_INF
Reset IEC status flags
New EFBs in the COMM library:
New EFBs
Description
PORTSTAT
States Modbus Port status
Start Concept
New features when starting Concept:
46
New performance attributes
Description
Automatic connection to every
desired PLC
Startup using the Concept Project Symbol creates
automatic connection to any desired PLC. This
connection is defined by the Command line parameter
(see page 1148).
When starting Concept using the
CCLaunch tool, a connection is
made to every desired PLC
In large networks, a topology file is created and is then
used in the CCLaunch tool. You can use this to create a
complete MB+ Routing path (see page 1151), which
then creates a connection to the PLC automatically.
33002204 12/2010
New Performance Attributes
New performance attributes
Description
Displays list of previously opened
Projects/DFBs
When starting Concept a list of previously opened
Projects/DFBs (max. 4) is displayed in the File main
menu.
Archive content display
When unpacking an archived project, all archived files
are shown first.
Animation
12 different color schemes for animation in the FBD, IL, ST, SFC and LD editors:
New performance attributes
Description
CONCEPT.INI:
[Colors]
AnimationColors= (0-12)
Defines the color scheme for online animation in all
editors.
Reference data editor
New feature in the reference data editor:
New performance attributes
Description
Address format IEC (QW0000X)
The IEC (QW0000X) address format can be displayed.
Online functions
New online features:
New performance attributes
Description
Quantum password protection
Quantum PLC is write protected by entering a
password.
Event sections
Online diagnostics are displayed for Interrupt sections.
Event viewer
Error descriptions can be defined in a project specific INI
file (see page 1122) that should appear in the event
viewer (Online →Online events...).
Message window
New performance attributes in the Windows menu:
33002204 12/2010
New performance attributes
Description
Save messages
After messages are displayed they can be saved to file
using the Save Messages... (main menu Window)
menu command.
47
New Performance Attributes
New CPU
New CPU:
PLC family
Description
Atrium
CPU 180-CCO-241-11
New Module
New Quantum module:
Module
Description
140-NOE-771-01
Ethernet module without Hot Standby features.
140-NOE-771-11
Ethernet module (Factory Cast) without Hot Standby
features.
140-CPS-114-20
Power supply module
140-CPS-124-20
Power supply module
140-NOG-111-00
1/SFB Master module
140-NWM-100 00
Ethernet module (Factory Cast HMI)
New Momentum module:
Module
Description
170-ANR-120-91
Analog/Digital Input/Output module
Project Browser
New features in the Project browser:
48
New performance attributes
Description
Display interrupt sections
When I/O event sections and Timer event sections are
used, they are displayed in the Project browser
structure.
Show detailed view
The Project browser window is split vertically, and a
second window displays the substructure (e.g. DFBs,
Transitions sections, etc.) of the selected elements in a
structure tree.
33002204 12/2010
New Performance Attributes
Analyze section
New features when analyzing sections:
New performance attributes
Description
Analyze interrupt sections
There is now an additional analysis for Interrupt
sections.
Analyzing global variables in DFBs There is an analysis for global variables in DFBs.
DFB
New features for DFB programming:
New performance attributes
Description
Located variables
Located variables are permitted in DFBs when the
option in the IEC Extensions dialog box is enabled.
Global variables can be created throughout the program
with located variables in DFBs.
Data types
New features for DFB programming:
33002204 12/2010
New performance attributes
Description
View comments for data structure
elements
Comments for data type components defined in data
type files (*.ddt, *.dty) are displayed in:
z Editors status line
z Variables editor for the definition of initial values
z Inspect Animation field
Extended Data Type Definition
(larger than 64 Kbytes), page 572
The 64 kb restriction is not imposed for local data type
definition with the introduction of unlocated Include files.
49
New Performance Attributes
Configuration
New features in the Configurator:
New performance attributes
Description
1/SFB Coupler configuration
Required to provide support for the A500/A350 I/O
module. Extended I/O range up to 160 input/output
words.
Quantum security parameter
The following parameters can be defined in the new
dialog box (submenu of the Config. Extensions):
z Secure data area
z Network write restrictions
z Enable the Auto-Logout option
Interbus configuration with Atrium
The Interbus configuration is done with Atrium CPUs
180 CCO 241 01 (= 1 INTERBUS) and 180 CCO 241 11
(= 2 INTERBUS).
Logging (*.LOG, *.ENC)
New features for DFB logging:
New performance attributes
Description
Additional contents
When logging PLC write access, modifications made to
variable and literal values are displayed in addition.
New Date/Time format
By activating the check box Universal Date Format in
dialog Common Preferences (setting also affects the
CONCEPT.INI file) the format can be changed. The
month is then stated within Concept with 3 characters
and in English. Example: 24-Dec-2002 14:46:24
Encrypting the log
By activating the check box Encrypt Logfile in dialog
Common Preferences (or indirectly using the check
box Secure Application in dialog Project Properties)
login the write access to the PLC will be encrypted. The
encrypted file contains the file extension *.ENC.
Secure Application
New features for a secured application:
50
New performance attributes
Description
Application backup
If you activate the check box in the Project →Project
Properties dialog box, program modifications are
automatically logged and encrypted in a *.ENC file.
These settings can be loaded using Export/Import and
transferred to the PLC.
33002204 12/2010
New Performance Attributes
New Tools
New Tools for Concept:
33002204 12/2010
New Tool
Description
CCLaunch
This tool is used for making an automatic connection
(see page 1151) with a PLC in a large network.
View Tool
This tool allows you to view encoded LOG files (*.ENC).
It is started automatically with menu instruction View
Logfile if log encrypting has been activated.
51
New Performance Attributes
New performance attributes of Concept 2.6 SR2 in comparison with Concept 2.6
SR1
New EFBs
New EFBs in the IEC library:
New EFBs
Description
CMPR
Compares the Bit pattern of Matrix A to that of Matrix B.
MBIT with pointer
Changes the bit position in a data matrix.
SEARCH
Searches the register in a source table for a specific bit pattern.
SENS with pointer
Checks the query value of a specific bit position in a data matrix.
XXOR
Performs a Boolean Exclusive-OR-Operation with the bit
patterns of the source and target matrix.
Search/Replacement of FFBs
New features when searching for/replacing FFBs:
New feature
Description
FFB type is replaced in all
sections (only for DFBs)
In the dialog box Replace FFB Type by activating the new
check box Replace in all sections the selected FFB type can
be replaced in all sections (only for DFBs).
Create a new project
New features when generating a new project:
52
New feature
Description
Specify project path when
generating a new project
When generating a new project (File →New Project) you can
define a new path or accept the standard path again.
33002204 12/2010
New Performance Attributes
New options in the upload and loading dialog box
New options in the upload and loading dialog box:
New features
Description
New check boxes in the
dialog box Load into the
PLC:
z State RAM + Initial
Values
z Only state RAM
By activating the check box State RAM + Initial Values at first
all initial values of the Located 4x-Variables are copied from the
Variable Editor into the state RAM mirror. Then, the initial values
and all blocked 0x and 1x-I/O-bits are loaded from the state
RAM mirror into the PLC.
By activating the check box State RAM Only the initial values
of the Located 4x-Variables and all blocked 0x and 1x I/O bits
are loaded from the state RAM mirror into the PLC.
New check boxes in the
dialog box PLC Upload:
z Upload State RAM +
Initial Values
z Only upload State
RAM
By activating the check box Upload State RAM + Initial Values
at first all Located 0x-, 1x, and 4x-values are read from the PLC
and saved in the state RAM mirror. Then, the initial values of the
4x-variables are overwritten with the value from the state RAM
mirror.
With the activation of the check box Only read state RAM all
Located 0x-, 1x- and 4x-values are read from the SPS, and
saved in the state RAM mirror.
INI files
New settings in the CONCEPT.INI:
New Settings
Description
Define overwriting of the
uploaded state RAM
values
In the line [RDE] of the CONCEPT.INI you can define that
uploaded state RAM values are not overwritten by online
operations in the RDE.
Define start of the RDEAnimation
In the line [RDE] of the CONCEPT.INI you can define that the
RDE animation is automatically started when opening a table.
Exclusion of all or global
In the line [Backup] of the CONCEPT.INI you can define that
DFBs from Online-Backup after the Online-Backup the directories "DFB" and/or
"DFB.GLB" are not present in the backup directory.
New settings in the Projectname.INI:
33002204 12/2010
New Setting
Description
Define path and backup
files
In the line [Backup] of Projectname.INI, you can output a Batchfile (EXE-file) for the Online-Backup-Operation, by which you
perform additional backups e.g. for another PC.
53
New Performance Attributes
Multiple Address Assignment
New feature for multiple address assignment:
54
New feature
Description
Cleaning up multiple
assignment of a single
address by different
variable names
In the dialog box Multiple Address Assignments variable
names that are all assigned to the same address are replaced
or renamed. In the end, only one variable name is assigned to
this address.
33002204 12/2010
New Performance Attributes
New performance attributes of Concept 2.6 SR3 in comparison with Concept 2.6
SR2
New menu command
New menu command:
33002204 12/2010
New menu command
Description
Options →Tools
Use this menu command to open a menu to execute
additional applications or help programs.
55
New Performance Attributes
56
33002204 12/2010
Project structure
33002204 12/2010
Project structure
3
Overview
This chapter describes the structure of projects in Concept.
What's in this Chapter?
This chapter contains the following topics:
Topic
33002204 12/2010
Page
Project Structure and Processing
58
Programs
64
Sections
68
Configuration data
73
57
Project structure
Project Structure and Processing
Structure of a project
The creation of a PLC program with Concept is carried out hierarchically in a project
using PLC configuration (see page 73) and Program (see page 64). The program is
divided into section groups and Sections (see page 68).
The PLC configuration and required program parts can be created in any order
within a project (top down or bottom up).
Structure of a project:
Processing an IEC/LL984 project
This table describes the processing of a LL984/IEC project (Quantum):
Step
Logic processor
I/O processor
1
Overhead, e.g. communication with
NOM, NOE etc.
-
2
Executing LL984 segment 1
Writing outputs calculated in segment n
Reading inputs required in segment 2
3
Executing LL984 segment 2
Writing outputs calculated in segment 1
Reading inputs required in segment 3
58
33002204 12/2010
Project structure
Step
Logic processor
I/O processor
4
Executing LL984 segment 3
Writing outputs calculated in segment 2
Reading inputs required in segment 4
...
...
...
n
Executing LL984 segment n (n =< 32)
Writing outputs calculated in segment
n-1
Reading inputs required in segment 1
n+1
Executing IEC section 1
-
n+2
Executing IEC section 2
-
n+3
Executing IEC section 3
-
..
-
Executing IEC section n (n =< 1600)
and back to stage 1
-
m
1 The overhead is executed in this stage (e.g. communication with the coupling
modules NOM, NOE).
2 - 4 In these stages, the logic for the LL984 sections is executed by the logic
processor in segments 1-3 (corresponding to the settings in the Segment
scheduler (see page 117)).
At the same time the I/O processor transfers the output values calculated in the
respective previous segment to the hardware and the hardware reads the input
values required for the next respective segment.
n In this step, the logic processor in segment n runs the LL984 sections logic.
At the same time the I/O processor transfers the output values calculated in the
previous segment to the hardware and the hardware reads the input values
required for segment 1.
Note: The output values calculated in this segment are only executed on next
execution of stage 2, i.e. after the IEC logic and the overhead have been
processed. Therefore no time critical logic should be executed in this segment.
n+1 - m The logic processor runs the IEC sections logic in these steps.
It then "jumps back" to stage 1.
Note: No hardware signals are read or written. The values calculated/read in
stages 2 to n are used exclusively. The outputs calculated in these stages are
transferred in stages 2 to n (corresponding to the settings in the segment
scheduler).
33002204 12/2010
59
Project structure
Processing a LL984 project
This table describes the processing of a LL984 project (Quantum):
Step
Logic processor
I/O processor
1
Overhead, e.g. communication with
NOM, NOE etc.
-
2
Executing LL984 segment 1
Writing outputs calculated in segment n
Reading inputs required in segment 2
3
Executing LL984 segment 2
Writing outputs calculated in segment 1
Reading inputs required in segment 3
4
Executing LL984 segment 3
Writing outputs calculated in segment 2
Reading inputs required in segment 4
...
...
...
n
Executing LL984 segment n (n =< 32)
and back to stage 1
Writing outputs calculated in segment
n-1
Reading inputs required in segment 1
1 The overhead is executed in this stage (e.g. communication with the coupling
modules NOM, NOE).
2 - 4 In these stages, the logic for the LL984 sections is executed by the logic
processor in segments 1-3 (corresponding to the settings in the Segment
scheduler (see page 117)).
At the same time the I/O processor transfers the output values calculated in the
respective previous segment to the hardware and the hardware reads the input
values required for the next respective segment.
n In this step, the logic processor in segment n runs the LL984 sections logic.
At the same time the I/O processor transfers the output values calculated in the
previous segment to the hardware and the hardware reads the input values
required for segment 1.
It then "jumps back" to stage 1.
Note: The output values calculated in this segment are only processed the next
time stage 2 is completed, i.e. after the overhead has been processed. Therefore
no time critical logic should be executed in this segment.
Processing an IEC project
This table describes the processing of an IEC project (Quantum):
60
Step
Logic processor
I/O processor
1
Overhead, e.g. communication with
NOM, NOE etc.
-
33002204 12/2010
Project structure
Step
Logic processor
I/O processor
2
-
Writing outputs allocated to segment 1
Reading inputs allocated to segment 1
3
-
Writing outputs allocated to segment 2
Reading inputs allocated to segment 2
4
-
Writing outputs allocated to segment 3
Reading inputs allocated to segment 3
...
...
...
n
-
Writing outputs allocated to segment n
(n =< 32)
Reading inputs allocated to segment n
(n =< 32)
n+1
Executing IEC section 1
-
n+2
Executing IEC section 2
-
n+3
Executing IEC section 3
-
..
-
Executing IEC section n (n =< 1600)
and back to stage 1
-
m
1 The overhead is executed in this stage (e.g. communication with the coupling
modules NOM, NOE).
2 - n The hardware signals from the allocated modules respective segments are
written and read by the I/O processor in these stages (corresponding to the
settings in the Segment scheduler (see page 117)).
n+1 - m The logic processor runs the IEC sections logic in these steps.
It then "Returns" to stage 1.
Note: No hardware signals are read or written. The values read in stage 2 to n
are used exclusively. The outputs calculated in these stages are transferred in
stages 2 to n (corresponding to the settings in the Segment manager).
Processing an IEC project
This table describes the processing of an IEC project (Quantum):
Step
Logic processor
I/O processor
1
Overhead, e.g. communication with
NOM, NOE etc.
-
2
-
Writing outputs allocated to segment 1
3
-
Writing outputs allocated to segment 2
Reading inputs allocated to segment 1
Reading inputs allocated to segment 2
33002204 12/2010
61
Project structure
Step
Logic processor
I/O processor
4
-
Writing outputs allocated to segment 3
Reading inputs allocated to segment 3
HE1
1. I/O event section, spontaneous
execution, when Hardware Interrupt
occurs
-
HE2
2. I/O event section, spontaneous
execution, when Hardware Interrupt
occurs
-
...
...
...
HE64
64. (last) I/O event section,
spontaneous execution, when
Hardware Interrupt occurs
-
TE1
1. Timer event section, only executed
when time interrupt occurs
-
TE2
2. Timer event section, only executed
when time interrupt occurs
-
...
...
...
TE16
16. Timer event section, only executed
when time interrupt occurs
-
...
...
...
n
-
Writing outputs allocated to segment n
(n =< 32)
Reading inputs allocated to segment n
(n =< 32)
n+1
Executing IEC section 1 (cyclically)
-
n+2
Executing IEC section 2 (cyclically)
-
n+3
m
Executing IEC section 3 (cyclically)
-
..
-
Executing IEC section n (n =< 1600)
and return to stage 1
-
1 The overhead is executed in this stage (e.g. communication with the coupling
modules NOM, NOE).
2 - n The hardware signals from the allocated modules respective segments are
written and read by the I/O processor in these stages (corresponding to the
settings in the Segment scheduler (see page 117)).
n+1 - m The logic processor processes the IEC sections logic in these steps.
It then "Returns" to stage 1.
62
33002204 12/2010
Project structure
Note: No hardware signals are read or written. The values read in stage 2 to n
are used exclusively. The outputs calculated in these stages are transferred in
stages 2 to n (corresponding to the settings in the Segment scheduler).
HE1 - HE64 If a hardware interrupt signal specially assigned to a section changes
its value according to its parameter configuration, the cyclical processing and if
necessary the processing of a Timer event section is immediately stopped and
returned to the I/O event section. Once all event sections (and Timer event
sections) are processed, the cyclical processing is continued at the point where
the interrupt occurred. (See also chapter "I/O Event Sections, page 1142")
TE1 - TE16 When a specially configured Timer interrupt signal for a section occurs,
cyclical processing is immediately stopped and jumps to the Timer event section.
Once Timer event sections are processed, the cyclical processing is continued at
the point where the interrupt occurred as long as there are no further instructions
for Timer event sections. (See also chapter "Timer Event Sections, page 1129")
33002204 12/2010
63
Project structure
Programs
Structure of a program
A program consists of one or more Sections (see page 68) or section groups.
Section groups can contain sections and other section groups. Section groups can
be created exclusively and filled using Project →Project browser. Sections
describe the entire systems mode of operating.
Moreover the variables, constants, literals and direct addresses are managed within
the program.
Variables
Variables are used to exchange data within a section, between several sections and
between the program and the PLC.
Variables are declared using the menu command Project →Variable declaration.
If the variable with this function is assigned an address, it is called a Located
variable. If the variable has no address assigned to it, it is called an Unlocated
variable. If the variable is assigned with a derived data type, it is called a Multielement variable.
There are also constants and literals.
The following table provides an overview of the various types of variables:
Variable type
Description
Located variables
Located variables are allocated a State RAM address (reference
address 0x, 1x, 3x,4x). The value of this variable is saved in the
State RAM and can be changed online using the Reference data
editor. These variables can be addressed using their symbolic
names or using their reference address.
All PLC inputs and outputs are connected to the State RAM. The
program can only access peripheral signals attached to the PLC
via located variables. Access from external pages via Modbus or
Modbus Plus interfaces of the PLC, e.g. from visualization
systems can be made using located variables.
Unlocated variables
Unlocated variables are not assigned a State RAM addresses.
They therefore do not occupy any State RAM addresses. The
value of this variable is saved internally in the system and can be
changed using the Reference data editor. These variables are
only addressed using their symbolic names.
Signals requiring no peripheral access, e.g. intermediate results,
system tags etc, should primarily be declared as unlocated
variables.
64
33002204 12/2010
Project structure
Variable type
Description
Multi element variables
A variable which is assigned a Derived data type.
A distinction is made here between Structured variables and Array
variables.
Structured variables
Variables to which a Derived data type defined using a STRUCT
(structure) is assigned.
A structure is a collection of data elements with generally different
data types (Elementary data types and/or Derived data types).
Array variables
A variable which is assigned a defined data type with the key word
ARRAY.
An array is a collection of data elements with the same data type.
Variable start behavior
In start behavior of PLCs there is a distinction between cold restarts and warm
restarts:
z Cold restart
Following a cold restart (loading the program with Online →Download) all
variables (irrespective of type) are set to "0" or their initial value if available.
z Warm restart
In a warm restart (stopping and starting the program or Online →Download
changes) different start behaviors are valid for located variables/direct
addresses and unlocated variables:
z Located variables/direct addresses
In a warm restart all 0x, 1x and 3x registers are set to "0" or their initial value
if available.
The buffered coils are an exception to this. Buffered coils retain their current
value (storage behavior).
4x registers retain their current value (storage behavior).
z Unlocated variables
In a warm restart all unlocated variables retain their current value (storing
behavior).
This varying behavior in a warm restart leads to peculiarities in the warm restart
behavior of set and reset functions.
z Set and Reset in LD and IL
Warm restart behavior is dependent on the variable type used (storage behavior
in use of unlocated variables; non storage behavior in use of located
variables/direct addresses)
z SR and RS Function Blocks in FBD, LD, IL and ST
These function blocks work with internal unlocated variables and therefore
always have a storage behavior.
33002204 12/2010
65
Project structure
Constant variables
Constants are unlocated variables assigned a value, which cannot be modified by
the logic program (read only).
Literals (values)
Literals are used to describe FFB inputs, and transition conditions etc using direct
values. These values cannot be overwritten by the program logic (read only).
The values of literals can be changed online.
There are two different types of literal; generic and standardized.
The following table provides an overview of the various types of literals:
Literal
Description
Generic literals
If the literal’s data type is not relevant, simply
specify the value for the literal. In this case,
Concept automatically assigns a suitable
data type to the literal.
Standardized literals
If you would like to manually determine a
literal’s data type, this may be done using the
following construction: "Data type
name"#"Literal value"
For example
INT#15 (Data type: Integer, value: 15),
BYTE#00001111 (Data type: Byte, value:
00001111)
REAL#23.0 (Data type: Real, value: 23.0)
To assign the data type REAL the value may
also be specified in the following manner:
23.0.
Entering a comma will automatically assign
the data type REAL.
66
33002204 12/2010
Project structure
Direct addresses
Direct addresses are memory ranges in the PLC. They are located in the State RAM
and can be assigned Input/Output modules.
Direct addresses can be entered or displayed in various formats. The display format
is specified in the dialog box Options →Preferences →Common. Setting the
display format has no impact on the entry format, i.e. direct addresses can be
entered in any format.
The following address formats are possible:
Standard format (400001)
The five character address comes directly after the first digit (the Reference).
z Separator format (4:00001)
The first digit (the Reference) is separated from the following five-character
address by a colon (:).
z Compact format (4:1)
The first digit (the Reference) is separated from the following address by a colon
(:), and the leading zeros of the address are not given.
z IEC format (QW1)
In first place, there is an IEC identifier, followed by the five-character address.
z %0x12345 = %Q12345
z %1x12345 = %I12345
z %3x12345 = %IW12345
z %4x12345 = %QW12345
z
The values of direct address can be modified online using the Reference data editor
(see page 595).
Start behavior of digital outputs
Outputs that are assigned 0x registers are deleted during PLC startup. Digital
outputs that assigned 4x registers keep their current value when the PLC is stopped
or started.
33002204 12/2010
67
Project structure
Sections
Introduction
A program consists of one or more sections. A section describes the mode of
functioning of a systems technological unit (for example a motor).
Each section has its own document window in Concept. For overview purposes it is
useful to divide a very large section into several small ones. The scroll bar is used
to move within a section.
The page break can be made visible for each section, so that the page format can
be monitored when programming. In this way, a readable printout of the section is
assured.
Section types
There are three different types of sections in Concept provided for Quantum
processing.
z Cyclical section are executed in every program cycle. The reaction time
depends on the cycle time and is a minimum of one cycle and maximum of two
cycles.
z I/O event sections are not executed cyclically, but are started and processed
spontaneously when a specially assigned Interrupt signal value changes state
(corresponding to the setting in the Configurator and Section properties).
The 140-HLI-340-00 module provides 16 Interrupt inputs. The local backplane
has space for a maximum of 4 HLI modules.
The reaction time to an I/O event generally depends on the process duration of
the EFBs to be processed in the section as well as the transition times.
z Timer event sections are started and processed in precise user defined
intervals.
The time intervals are defined in multiples of 1ms and a Phase in the Section
properties for Timer Event Sections dialog box.
The reaction time is independent of the cycle time. Reactions to outputs are also
carried out in defined time intervals.
Maximum number of sections
There can be up to a maximum of 1,600 sections per program.
Programming languages
Sections can be programmed using the IEC programming languages FBD (Function
Block Diagram), LD (Ladder Diagram), SFC (Sequential Control), IL (Instruction
List), or ST (Structured Text), or in the LL984 programming language (Ladder
Logic), which resembles Modsoft. Only one of the stated programming languages is
permitted to be used within a section.
68
33002204 12/2010
Project structure
Exchanging values
Values are exchanged within sections via links, variables, or direct addresses.
Values are exchanged between different sections via variables or direct addresses.
Section execution order
The LL984 sections are the first to be executed. The LL984 section vertical
sequence can be defined via the Project →Configurator →Configure → Segment
scheduler... dialog box. Once the entire LL984 section has been processed, the
IEC sections are then processed (FBD, SFC, LD, IL, ST). The execution order can
be determined using either the Project →Execution order... or the Project browser
(see page 557) dialog box.
Printing sections
Sections are divided into pages when printing out. The amount of information on
these pages is dependent on the settings in the menu File →Print. Page division
can be displayed using the menu option View →Page breaks.
Section variable
A Multi-element variable is automatically generated for each IEC section (FBD, SFC,
LD, IL, and ST) and has the same name as the section.
This variable is SECT_CTRL data and has two elements:
z The "disable" BOOL data type element for disabling sections.
z The "hsbyState" BYTE data type element for displaying the Hot Standby status
of sections.
If the smallest bit of this element is set, the data from this section is
transferred/received, see the Hot Standby User's manual. (This bit corresponds
to the exclamation mark in the project browser.)
Disabling sections
The component "disable" can be used to enable/disable the section variable If the
multi element address is not used or if the value 0 has been assigned to "disable",
the corresponding section is executed. If "disable" is assigned the value "1", the
corresponding section will not be executed. By using this variable, the execution of
sections can be controlled according to events.
NOTE: If a disabled section is animated, the DISABLED status is displayed in the
status bar.
33002204 12/2010
69
Project structure
CAUTION
Risk of unwanted process states.
Disabling a section does not mean that programmed outputs will be deactivated
within the section if an output has already been set in a prior cycle, this status
remains even after the section is disabled. The status of these outputs cannot be
modified.
Failure to follow these instructions can result in injury or equipment damage.
Disabling Interrupt Sections
A specific Interrupt section can be disabled using the ISECT_OFF block. It can be
enabled again using the ISECT_ON block. The section names are provided by the
SECT_CTRL control variable.
The I_LOCK block can disable all interrupt sections. They can be enabled again
using the I_UNLOCK block.
NOTE: A possible interrupt on an interrupt section has no effect.
Lock section UNCONDITIONALLY (possibility 1)
The procedure for locking a section unconditionally is as follows:
Step
1
70
Action
Using Online →Reference data editor open the Reference data editor
(see page 595).
2
By double clicking on a line number, open the Lookup variables dialog box.
3
From the area Data type first choose the option Structured and then from this
list SECT_CTRL.
Result: The names of all sections are displayed.
4
Now select the names of the section to be locked.
5
Use the command button Components... to select the ANY type components
dialog box.
6
Select the line disable: BOOL and confirm with OK.
7
If the following has not been performed yet:
Create a connection between the PLC and the programming device and load
your program onto the PLC.
33002204 12/2010
Project structure
Step
Action
8
Change the entry in the column Value to 1 (TRUE) to lock the section or 0
(FALSE) to enable the section.
9
Using Online →Animation activate the animation if it is inactive.
Result: The section is disabled or enabled according to the value.
Note: Locking a section does not mean that programmed outputs will be
deactivated within the section if an output has already been set in a prior cycle,
this status remains even after the section has been disabled. The status of these
outputs cannot be modified.
CAUTION
Risk of unwanted process states.
The entry in the column Value remains even after the reference data editor has
been closed (even if the entries are not saved), or in other words, the section
remains disabled and must be explicitly re-enabled via the reference data editor
(value = 0).
Failure to follow these instructions can result in injury or equipment damage.
Lock section UNCONDITIONALLY (possibility 2)
The procedure for locking a section unconditionally is as follows:
Step
33002204 12/2010
Action
1
Using Project →Project browser open the Project browser (see page 557).
2
From Online →Connect... create a connection between the programming
device and the PLC.
3
From Online →Download... (if the program is in NOT EQUALmode) or Online
→Download changes (if in MODIFIED mode) restore the consistency between
the programming device and the PLC.
4
Select the section to be locked from the project browser.
5
Activate the context menu for sections using the right mouse button, and activate
Animate enable state.
6
Change the enable status using the menu command Switch enable state from
the context menu (right mouse button) of the selected section.
Note: Sections may only be disabled or enabled via the Project browser, if they
have not already been disabled/enabled via another Section (see page 72) or via
the Reference data editor (see page 70).
Result: The section is locked.
Note: Locking a section does not mean that programmed outputs will be
deactivated within the section if an output has already been set in a prior cycle,
this status remains even after the section has been disabled. The status of these
outputs cannot be modified.
71
Project structure
Locking a section CONDITIONALLY
The procedure for locking a section conditionally (program dependent) is as follows:
Step
1
Create the logic according to the section to be locked, for example in an FBD
section.
When doing this, please note that the logic must carry a BOOL data "output" and
that the section to be disabled will be disabled at logic "1".
Note: The section containing a logic for disabling/enabling other sections should
not be disabled.
2
By double clicking on your logic’s "output", open the Connect FFB dialog box.
3
Use the command button Lookup... to open the Lookup Variable dialog box.
4
From the area Data type first choose the option Structured and then from this
list SECT_CTRL.
Reaction: The names of all sections are displayed.
5
By double clicking, now select the names of the section to be locked.
6
Select the line disable: BOOL and confirm with OK.
Result: The multi-element variable from the section to be locked (Section
name.disable) now creates the "output" of the logic.
7
From Project →Execution order... open the Section Execution Order dialog
box.
8
Using the command buttons, ensure that the section containing the logic for
locking is executed before the section to be locking is executed.
9
If the following has not been performed yet:
Create a connection between the PLC and the programming device.
10
72
Action
Download your program to the PLC.
Result: When logic "1" is at the "Output" the section to be locked is not edited.
Note: Locking a section does not mean that programmed outputs will be
deactivated within the section if an output has already been set in a prior cycle,
this status remains even after the section has been disabled. The status of these
outputs cannot be modified.
33002204 12/2010
Project structure
Configuration data
Description
The PLC configuration is the interface between the program and the hardware.
The configuration data consists essentially of the component list and the entry in the
address field of the program.
Loadables facilitate communication with the IEC programming language and the
loading of further LL984-Instructions.
33002204 12/2010
73
Project structure
74
33002204 12/2010
Creating a Project
33002204 12/2010
Creating a Project
4
Overview
This chapter describes the general procedure for the initial creation of a project. The
most linear sequence possible is used here, in order to show a Concept-newcomer
an easily manageable way of creating a project. Crosslinks between the Menu
Commands are of course possible. As they gain experience, users will learn
shortcuts and alternatives. For more detailed information, please see the relevant
chapters in the user manual.
What's in this Chapter?
This chapter contains the following topics:
Topic
Overview
33002204 12/2010
Page
76
Step 1: Launching Concept
77
Step 2: Configuring the PLC
78
Step 2.1: Required Configuration
79
Step 2.2: Optional Configuration
81
Step 3: Creating the User Program
85
Step 4: Save
88
Step 5: Perform Memory Prediction
89
Step 6: Loading and Testing
90
Step 7: Optimize and Separate
95
Step 8: Documentation
97
75
Creating a Project
Overview
Project Creation
The creation of a project has 8 main steps:
Step
Action
1
Launching Concept (see page 77)
Launch Concept and start a new project.
2
Configuring the PLC (see page 78)
Set the hardware configuration.
3
Creating the user program (see page 85)
Create new sections and create your program.
4
Save (see page 88)
Save your project
5
Perform Memory Prediction (see page 89)
Check the PLC memory workload.
6
Loading and testing the project (see page 90)
Create a link between the PC and the PLC. Load the project in the PLC and start
it. Test the program with the Online Test Function. Now eliminate any mistakes
in the program! Load the altered sections into the PLC.
7
Optimize and Separate (see page 95)
It is now advisable to optimize the program storage capacity and to reload the
optimized program into the PLC. After successfully loading, testing and (if
necessary) optimizing, you may disconnect the PC from the PLC. The program
will now run offline.
8
Documenting (see page 97)
Create a complete set of documentation of your project.
Notes
NOTE: The steps "Configuring the PLC" and "Creating the User Program" can be
performed in either order. This means that the PLC configuration can also be
changed after the creation of the program.
NOTE: In order to prevent loss of data, you should save your program regularly.
76
33002204 12/2010
Creating a Project
Step 1: Launching Concept
Launching Concept
The procedure for launching Concept is as follows:
Step
Action
1
Double click on the Concept icon to launch Concept.
2
Select File →New Project.
3
You can specify a new project path or accept the standard project path with the
project name namenlos.prj.
Result:The new project is opened.
Note: If you select the standard project path with the project name
namenlos.prj , you can save this project with a name at a later time Step 4:
Save, page 88. A saved project can be invoked with the Open Project..., or by
using its project icon.
Note
NOTE: For additional steps please note the settings in the submenu Options →
Preferences!
Resume
Now proceed with Step 2: Configuring the PLC (see page 78).
33002204 12/2010
77
Creating a Project
Step 2: Configuring the PLC
What should be configured?
Using Project →PLC configuration configure the entire hardware configuration for
your project.
Required Configuration
NOTE: The PLC type must first be set! All further configurations can then be
executed independently of the processing sequence.
The following configurations are necessary for the configuration:
Specifying the type of PLC (minimum configuration), page 79
z Set memory partitions, page 79
z Install loadables, page 80
z Set I/O map, page 80
z
Optional Configuration
The following configurations are to be used according to the project:
z Set head setup, page 81
z Set Modbus communication, page 81
z Set Peer Cop communication, page 82
z Set data protection, page 82
z Various PLC settings, page 83
z ASCII messages (only for 984 LL), page 83
78
33002204 12/2010
Creating a Project
Step 2.1: Required Configuration
Precondition
The PLC type must first be set! All further configurations can then be executed
independently of the processing sequence.
Specifying the type of PLC (minimum configuration)
The procedure for specifying the type of PLC (minimum configuration) is as follows:
Step
Action
1
Select Project →PLC configuration.
Response: The PLC configuration window is opened, this contains further
menu commands for hardware configuration.
2
Select the PLC Selection menu command from the list.
Response: The PLC selection dialog is opened.
3
From the PLC family list select your PLC type.
4
Select your CPU from the CPU/Executive list.
5
From the Runtime list select the Enable status.
Response: It is possible to program sections in IEC languages (FBD, LD, IL and
ST).
Note: In the Runtime list, the status Not available, Disabled or Only 984 is
displayed, then the selected CPU does not support any IEC programming
languages. If in the list the status Only IEC is displayed, then the selected CPU
exclusively supports IEC languages and these do not have to be explicitly
enabled.
6
With simple tests and programs the configuration can now be exited and the
procedure continued from Step 3: Creating the User Program, page 85 orStep
4: Save, page 88.
Set memory partitions
The procedure for setting the memory partition is as follows:
Step
33002204 12/2010
Action
1
Select Project →PLC configuration.
Response: The PLC configuration window is opened, this contains further
menu commands for hardware configuration.
2
Select the PLC memory partition menu command from the list.
Response: The PLC memory partition dialog is opened.
3
In the Discretes and Words ranges select the probable number of I/O flag bits
and I/O words, to be required by the user program
Note: The maximum address range, that must not be exceeded, can be read on
the right-hand side of the dialog.
79
Creating a Project
Install loadables
The procedure for installing the loadables is as follows:
Step
Action
1
Select Project →PLC configuration.
Response: The PLC configuration window is opened, this contains further
menu commands for hardware configuration.
2
Select the Loadables menu command from the list box.
Response: The Loadables dialog is opened.
3
Select the loadable in the Available: list.
Note: Loadables are assigned in the Loadables, page 114section.
4
Select the Install => command button.
Response: The selected loadable is moved to the Installed: field.
5
Repeat the steps 3 and 4 until all the loadables required have been installed.
Set I/O map
The procedure for setting the I/O map is as follows:
Step
Action
1
Select Project →PLC configuration.
Response: The PLC configuration window is opened, this contains further
menu commands for hardware configuration.
2
Select the I/O map menu command from the list.
Response: The I/O map dialog is opened.
3
Select the Supervision time column and enter a time, within which a
communication exchange must take place. If this time is exceeded, an error
message appears.
4
Select the Edit... command button.
Response: The dialog for entering modules is opened.
5
In the Module column, select the ... command button.
Response: The I/O Module Selection dialog is opened.
6
In the Modules column, select the module.
Response: The module is displayed in the current slot.
7
Select the Input start and/or Output start columns and enter the first address
of the occupied input and/or output reference range for the module.
8
Select the module and choose the Paramscommand button.
Response: If the module has a parameter dialog, you can define the parameter
(e.g. disconnect behavior, data format, measuring range) here.
Resume
Now proceed with Step 3: Creating the user program (see page 85).
80
33002204 12/2010
Creating a Project
Step 2.2: Optional Configuration
General Information
The following configurations do not need to be executed urgently, but they offer
extended functions.
Set head setup
The procedure for specifying the remote I/O is as follows (this procedure is optional
for minimum configuration):
Step
Action
1
Select Project →PLC configuration.
Response: The PLC configuration window is opened, this contains further
menu commands for hardware configuration.
2
Select the I/O map menu command from the list.
Response: The I/O map dialog is opened.
3
Select the Head setup... command button.
Response: The Head Setup dialog is opened.
4
Enter the slots for the RIO or NOM modules.
Response: Return to the I/O map dialog.
5
Select the head setup in the Go To list.
6
Select an empty line (last line) in the table, and select the Insertcommand
button.
Response: In the Type column another I/O station is entered.
7
Select the Drop column and enter the station number.
Note: Only as many remote I/O stations can be configured as there are
segments registered in the segment scheduler.
8
Select the head setup in the Go To list for the 2nd drop.
9
Next, carry out steps 3 to 6 of the Set I/O map, page 80 procedure.
Set Modbus communication
To set the Modbus communication (Quantum slave, terminal, printer, etc.) proceed
as follows:
Step
33002204 12/2010
Action
1
Select Project →PLC configuration.
Response: The PLC configuration window is opened, this contains further
menu commands for hardware configuration.
2
Select the Modbus Port settings menu command from the list.
Response: The Modbus port settings dialog is opened.
3
Make the corresponding settings.
81
Creating a Project
Set Peer Cop communication
If a Modbus Plus link exists, the Peer Cop functionality is able to transfer state RAM
data globally or directly between several nodes on a local network. The procedure
for setting the Peer Cop communication is as follows:
Step
Action
1
Select Project →PLC configuration.
Response: The PLC configuration window is opened, this contains further
menu commands for hardware configuration.
2
Select the Config. Extensions →Select Extensions list.
Response: The Select extensions dialog is opened.
3
Check the Peer Cop box.
Response: Return to the PLC configuration window and the Peer Cop menu
command is now available.
4
Select Config. Extensions →Peer Cop.
Response: The Peer Cop dialog is opened.
5
In the Go To range select the local bus devices, and enter the slot.
6
Select in the Global range the Receive... and Send... command buttons to
define the destination and source addresses of the transmission data and/or the
address of the other bus devices.
7
Select in the Specific range the Receive... and Send... command buttons to
define the destination and source addresses of the transmission data and/or the
address of the other bus devices.
Set data protection
Address ranges of coils and holding registers can be protected from being
overwritten by external signals. The procedure for setting the data protection is as
follows:
Step
82
Action
1
Select Project →PLC configuration.
Response: The PLC configuration window is opened, this contains further
menu commands for hardware configuration.
2
Select the Config. Extensions →Configuration extensions.
Response: The Configuration extensions dialog is opened.
3
Check the Data protection box.
Response: Return to the PLC configuration window and the Data protection
menu command is now available.
4
Select Config. Extensions →Data protection.
Response: The Data protection dialog is opened.
5
Select the range for the coils and holding registers. This range should contain
write-protection.
33002204 12/2010
Creating a Project
Various PLC settings
Diverse internal PLC data can be evaluated, a watchdog timeout for the user
program can be specified, the time windows for the communication (I/O time disk)
parameterized and the multiple assignment of outputs authorized. The procedure for
setting the PLC settings is as follows:
Step
Action
1
Select Project →PLC configuration.
Response: The PLC configuration window is opened, this contains further
menu commands for hardware configuration.
2
Select the Specials menu command from the list.
Response: The Specials dialog is opened.
3
Check the Battery coil, Timer register and Time of Day check boxes and enter
an address in the corresponding text boxes.
4
Check the Allow Duplicate Coils check box and enter the address from which
this should be allowed in the text box..
5
In the Watchdog timeout (ms*10): text box enter a numeric value between 2
and 255 (ms). This enables you to set an impulse watchdog for the user
program.
Response: As soon as the count pulses exceed the specified time, an error
message appears.
6
In the Online Editing Timeslice (ms): text box enter a numeric value between
3 and 100 (ms). This enables you to define a time for executing the multi-cycle
edit functions (paste, delete, find etc.)
ASCII messages (only for 984 LL)
To set the ASCII messages (only for 984LL), execute the following steps:
Step
33002204 12/2010
Action
1
Select Project →PLC configuration.
Response: The PLC configuration window is opened, this contains further
menu commands for hardware configuration.
2
Select from the list ASCII →ASCII Setup.
Response: The ASCII Setup dialog is opened.
3
Enter the total messages, the size of the message width and the number of
ASCII ports (from the I/O periphery) in the text boxes.
Response: In the PLC configuration →ASCII window the ASCII Port Settings
menu command is available.
4
Select from the list ASCII →ASCII port settings.
Response: The ASCII port settings dialog is opened.
5
Make the corresponding settings.
Note: ASCII messages can now be created under Project →ASCII messages...
.
83
Creating a Project
Resume
Now proceed with Step 3: Creating the user program (see page 85).
84
33002204 12/2010
Creating a Project
Step 3: Creating the User Program
General
A user program is created in sections. Each section is programmable in one of the
available languages and has a unique name in the project. Sections can be
generated at any time during the programming.
Overview
The creation of a user program consists of 9 steps:
Step
1
Action
Generating a New Section (see page 85)
2
Declaring the Variables (see page 86)
3
Programming a Section (see page 86)
4
Analyzing Program/Section (see page 86)
5
Specifying the section execution sequence (see page 87)
Generating a New Section
The procedure for generating a new section is as follows:
Step
33002204 12/2010
Action
1
In the main menu File call up the menu command New section... .
Result: The dialog box New program section is opened.
2
Click on the programming language desired for this section.
3
In the text box Section name enter the unique name for this section.
4
Generate all the required sections in this way.
85
Creating a Project
Declaring the Variables
A program consists of functions and Function Blocks (FFBs) or of instructions with
the statement of variables (e.g. signals), addresses or literals. While direct
addresses and literals can be used immediately, variables must be declared before
they can be used in programming. The procedure for declaring variables is as
follows:
Step
Action
1
In the main menu Project call the menu command Variable declaration... .
Result: The dialog box Variable declaration is opened.
2
Enter the variable name, the associated data type, and if necessary the
reference address, the initial value and a comment.
3
Confirm the entries with OK.
Note: Further editing is also possible from a FFB connection or contact etc. by
double-clicking -> Var. Declaration... . This starts the Variables editor.
Programming a Section
The procedure for programming a section is as follows:
Step
Action
1
Using File →Open section open the section to be programmed.
2
Create programs according to the rules of the individual programming
languages:
z Function Block Diagram FBD (see page 213)
z Ladder Diagram LD (IEC) (see page 239)
z SFC (Sequential Control) (see page 271)
z Instruction list (IL) (see page 321)
z Structured text (ST) (see page 393)
z LL984 (Ladder Diagram (Modsoft)) (see page 455)
Analyzing Program/Section
Check a section or the entire program for syntax violations! The procedure for
analyzing a program/section is as follows:
Step
86
Action
1
In the main menu Project call up the menu command Analyze section or
Analyze program.
2
Remove the cause of the displayed or reported error.
Note: Loading a section or program into the PLC is only possible after an errorfree check. (The removal of the cause of warnings is not absolutely necessary.
Checking the warnings is, however, sensible.)
33002204 12/2010
Creating a Project
Set execution order of sections
The sections are initially stored in the order of their creation and are executed after
the program has started. In general this sequence must be adjusted projectspecifically to suit the task setting. The procedure for specifying the section
execution sequence is as follows:
Step
1
Action
To specify the section execution sequence there are two alternatives:
z In the main menu Project call the menu command Execution order... and
using the command buttons First, Last, Next, Previous sequence the
sections as required.
z In the main menu Project call up the menu command Project browser and
sequence them as required by moving them around in the Project Browser,
page 557.
Resume
Now proceed with Step 4: Saving (see page 88).
33002204 12/2010
87
Creating a Project
Step 4: Save
General Information
General information about saving:
If you exit a project without saving, you will be automatically asked if you want to
save the project or not. If you answer yes to this question, this begins the same
procedure described below.
z In order to prevent loss of data, projects should be saved regularly during long
periods of configuration or programming sessions.
z
Saving a Project for the First Time
The procedure for saving a project for the first time is as follows:
Step
Action
1
In the File main menu invoke the Save Project As... menu command.
2
In the File name text box, enter the project name name.prj.
3
Select the desired drive and directory from the Directory list.
Alternatively, it is possible to enter the whole path specification in the File name
text box, e.g. c:\product1\reactor3.prj (max. 28 characters +
.prj). If these directories do not yet exist, they will be automatically created.
Note: According to IEC 1131, a project includes all programs, data etc which
belong to a PLC. If several projects (i.e. PLCs) belong to one system, then all
projects should be stored in a common directory named after the system.
4
Click the OK command button.
Response: The project has now been stored in the specified directory under the
given name.
Supplementary Saving
The procedure for supplementary saving is as follows:
Step
1
Action
From the File main menu simply select the Save menu command.
Resume
Now proceed with Step 5: Executing memory prediction (see page 89).
88
33002204 12/2010
Creating a Project
Step 5: Perform Memory Prediction
Check the PLC memory workload.
Perform an offline memory prediction of the configured PLC before downloading the
program to the PLC. The table displayed in the Project →Memory Prediction
dialog shows the use of individual memory ranges. An expected memory workload
is then recognized.
NOTE: In some cases the memory prediction is not very accurate. A discrepancy
between required memory in the PLC and the memory prediction under Concept
may occur. The memory prediction always indicates more available memory than is
actually available in the PLC.
This is due to the dynamic memory in the DFBs and Sections, which is difficult to
calculate. Especially ST sections cause a great difference between the prediction
and PLC. To be sure that there is sufficient memory available in the PLC, load a
project into a PLC for examination. The simulator cannot be used because many
projects have sufficient memory in the simulator but not in the PLC.
Resume
Now proceed with Step 6: Loading and testing the project (see page 90).
33002204 12/2010
89
Creating a Project
Step 6: Loading and Testing
General Information
Loading and testing programs is only possible if
either the 16-bit simulator Concept SIM is switched on or
z the Concept SIM 16-bit simulator is switched off and a PLC is attached with a
Modbus Plus, Modbus, TCP/IP cable, or
z the Concept PLCSIM32 simulator is switched on.
z
NOTE: Testing using Concept SIM (see page 746) and Concept PLCSIM32
(see page 748) simulators is only possible with IEC user programs.
Overview
Loading and testing macros is divided into 9 main steps:
Step
Action
1
Loading the EXEC file into the PLC (see Concept Installation Instructions)
2
Connecting the PC and PLC (see page 90)
3
Loading and Starting the Program (see page 91)
4
Activating the Animation (see page 91)
5
Changing the Values of Literals (see page 92)
6
Changing the Values of Variables (see page 93)
7
Locating Errors (see page 93)
8
Downloading Changes (see page 94)
9
Starting and Stopping the PLC (see page 94)
Connecting the PC and PLC
The procedure for linking the PC and the PLC is as follows:
Step
90
Action
1
From the Online main menu invoke the Connect... menu command.
Response: The Link to PLC dialog box opens.
2
Set the protocol type (Modbus, Modbus Plus, TCP/IP or Simulator) and the PLC
node (when working in a network) with which you wish to communicate.
3
Under Access right select the Change Configuration option
4
Confirm the details with OK.
33002204 12/2010
Creating a Project
Loading and Starting the Program
The procedure for loading and launching the program is as follows:
Step
Action
1
From the Online main menu invoke the Connect... menu command.
Response: The Download Controller dialog box will be opened in the PLC.
2
When loading the program for the first time, use the All command button.
3
Click the Load command button.
Response: Various dialog boxes will be displayed.
4
Answer the question Stop the program in PLC? Yes/No with Yes.
Note: This question only appears when a program is already running in the PLC.
5
Answer the question Start a program in PLC? Yes/No with Yes, if there
are no errors.
If warnings or errors are reported, these will be listed in the Messages window.
Correct the warnings or errors at the specified point.
Activating the Animation
With the animation (online status report) it is possible to monitor the status of
variables, steps, transitions etc within individual sections of the editor window. The
procedure for activating the animation is as follows:
33002204 12/2010
If…
Then…
To display binary values exclusively.
To display binary values exclusively, invoke the
Online main menu and click on the Animate
booleans menu command.
Response: The valences of all booleans (variables,
direct addresses, literals) are displayed in colour (0Signal = red, 1-Signal = green).
91
Creating a Project
If…
Then…
If you want to display the values of all To display the values of all variables invoke the
variables.
Editing main menu option and select the Select All
menu command (selects all items in the current
section).
Thereafter invoke from the Online main menu option
the Animate selection menu command.
Response: The valences of all values (variables,
direct addresses, literals) are displayed in colour (red
= 0-Signal, green = 1-Signal, yellow = either, for
variables, immediate display of the value or, for multielement-variables, displays the value by doubleclicking on the variable).
If you want to enter monitoring fields
in the text languages (IL and ST).
Use the Selected Inspect menu command to paste
the text languages IL and ST into section monitoring
fields.
Response: The current value of the allocated
variables is shown in these monitoring fields. With
multi element variables, only the value of the first
element is shown.
This can be changed by double-clicking on the
monitoring field of the Numeric Inspect Settings
dialog box, which invokes the options available.
Changing the Values of Literals
The procedure for changing literals is as follows:
Step
1
92
Action
Activate the animation, as described in Activating the Animation, page 91.
2
Double-click on the literal to be changed.
3
Enter a new value and confirm with OK.
Response: The new value will be sent to the PLC during the next logic scan.
33002204 12/2010
Creating a Project
Changing the Values of Variables
With the Reference data editor (see page 595) it is possible to show and set the
values of variables (state, control, force). The procedure for changing variables is as
follows:
Step
Action
1
From the main menu, select Online and then the Reference data editor menu
command.
2
Enter the variables to be displayed in the dialog box marked RDE Templates.
3
To set the value highlight the Disable check box, and enter the desired value.
4
The RDE template can be saved under a unique name.
To do this, invoke the RDE main menu option and select the Save template
as… menu command.
Note: Several RDE templates can be invoked at once. To do this, invoke the
RDE main menu option and select the Open template... menu command.
Locating Errors
If errors occur during the processing of the program by the PLC, these will generally
be reported on screen Messages and entered in an events list in log book form. The
procedure for locating errors is as follows:
Step
33002204 12/2010
Action
1
From the Online main menu invoke the Event Viewer menu command.
Response: A window is opened, in which all errors are listed and described.
2
Select an error line and use the command button Go to Error.
Response: This will go directly to the section in which the error occurred. The
faulty object is highlighted.
3
Correct the program.
4
If your program now has the UNEQUAL status carry out the steps in
Downloading and Starting the Program (see page 91) once again.
If the program now has the MODIFIED status perform the steps in Downloading
Changes (see page 94) once again.
93
Creating a Project
Downloading Changes
If the project has the MODIFIED status after it has been altered, these changes can
be loaded online into the PLC without stopping the program currently running. The
procedure for downloading changes is as follows:
Step
Action
1
From the Online main menu access the Download Changes... menu
command.
2
Click on OK.
Response: The changes will be downloaded to the controller.
Starting and Stopping the PLC
The procedure for starting and stopping the PLC is as follows:
Step
1
Action
If the same project is running on the PC and PLC (EQUAL), then the PLC can
be started or stopped with Online →Online Control Panel... .
Resume
Now proceed with Step 7: Optimize and Separate (see page 95).
94
33002204 12/2010
Creating a Project
Step 7: Optimize and Separate
Optimizing Projects
At the end of the installation and/or after several runs ofDownload Changes... it is
useful to perform an optimization, so that any gaps in the program data memory
management are filled. After optimization the project is UNEQUAL on the PC and
PLC and the program must be loaded into the PLC with Download... (Warning:
Program must be stopped and restarted!). The procedure for optimizing projects is
as follows:
Step
Action
1
Save the project with File →Save Project.
2
In the File main menu invoke the Close project menu command and take note
of the dialog boxes which then appear.
3
In the File main menu invoke the Optimize Project... menu command and
select the project to be optimized. Take note of the dialog boxes which
subsequently appear.
4
Check the size of the program data memory in the Online main menu with the
Memory Statistics... menu command.
5
The sizes can then be altered with PLC configuration.
6
Save the project with File →Save Project.
7
Reload the optimized program into the PLC using Online →Download... . To do
this the program currently running must be stopped.
8
Start the newly loaded program using Online →Online Control Panel.
Separating the PC and Controller
After successfully testing the program in the PLC (with a connected process) the PC
can be separated from the controller. The procedure for separating the PC and the
controller is as follows:
Step
33002204 12/2010
Action
1
Please take note of the program status in the footnote!
To maintain consistency EQUAL must be there.
z if it readsMODIFIED, modifications must be loaded first Downloading
Changes, page 94.
z If it readsUNEQUAL the program must be reloaded into the PLC Loading and
Starting the Program, page 91.
2
From the Online main menu access the Disconnect... menu command. Take
note of the information in the displayed dialog box.
3
The project can be closed after separation.
In the File main menu invoke the Close project... menu command. Take note
of the information in the dialog box, if displayed.
95
Creating a Project
Resume
Now proceed with Step 8: Documenting (see page 95).
96
33002204 12/2010
Creating a Project
Step 8: Documentation
General information
Each project should be fully documented. Changes and additions should also be
documented (partial documentation).
Among other things documentation includes:
z Comments on the project (Project →Properties),
z Comments on each separate section (File →Section properties),
z Comments on variables,
z Comments on the functions applied, function modules and DFBs (command
button Comment in the property dialog of each module),
z Comments on steps and transitions (command button Comment in the property
dialog of each element),
z Comments in the form of freely placed text elements in the graphic programming
languages (Object →Text),
z Comments on each line of commands in the textual programming languages
z Comments on user-specific data types,
z Comments on derived function modules (DFBs).
33002204 12/2010
97
Creating a Project
Printing the documentation
The procedure for printing documentation is as follows:
Step
Action
1
In the main menu call up File menu command Print... .
2
In dialog box Documentation contents select Page layout whether each page
should have a uniform header and footer as well as printing a front page. The
appearance of header, footer and front page is stored in the available ASCII
files.
3
In the areaContents and in dialog box Documentation contents, select what
is to be printed.
4
If Variable list has been selected, call up Options in order to select the
variables which are to be printed.
5
When Sections has been selected,
z call up Select and specify the sections that are to be printed and
z also call up Options. In area Graphics enlargement factor also specify
the appropriate size of the logic which is to be printed.
98
6
Activate command button OK.
Reaction: All entries are saved.
7
Make sure that the page set-up of the sections is as desired.
In the main menu call up Viewfollow this with the successive menu commands
Overview and Pabe Break.
8
Change the order of for example the FFBs in such a way, that there are as few
transitions between adjoining pages as possible.
9
In the main menu call up File the menu commandPrint...again and activate
command button Print.
The printout is made with defined settings and the dialog box is closed.
33002204 12/2010
PLC configuration
33002204 12/2010
PLC configuration
5
Overview
This section describes the single process for the hardware configuration.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
5.1
General information about hardware configuration
100
5.2
Configuration in OFFLINE and ONLINE mode
103
5.3
Unconditional Configuration
107
5.4
Optional configuration
122
5.5
Backplane Expander Config
133
5.6
Configuration of various network systems
137
5.7
Quantum Security Settings in the Configurator
151
99
PLC configuration
5.1
General information about hardware
configuration
Overview
This section contains general information about hardware configuration.
What's in this Section?
This section contains the following topics:
Topic
100
Page
General information
101
Proceed in the following way with the configuration
102
33002204 12/2010
PLC configuration
General information
At a Glance
The system configuration has far-reaching consequences as it influences the entire
control work mode. It has to define all control-specific information as well as general
information, allocate the necessary memory space and determine the input/output
area. For the first configuration the user must enter several basic details for the PLC
area, such as PLC type and memory. Only valid configurations are authorized.
A configuration always refers to a Project, i.e. the menu command PLC configurationis only available when a project has been opened.
The configuration is available offline or online.
33002204 12/2010
101
PLC configuration
Proceed in the following way with the configuration
Introduction
In this section you are given a general overview on how to proceed with the
configuration.
Use Configuration Menu
There are menu commands that absolutely must be carried out and are available in
the PLC Configuration window. Grayed out menu commands are currently
unavailable and can be enabled for extending the hardware-configuration in the
Config. Extensions directory with the menu command Select Extensions.
Read in Module Set-up
The PLC module set-up is entered manually and can be compared with the
connected hardware in ONLINE mode. After it has been read in, the modules
missing in Concept are shown in the I/O map, and can be re-edited.
The I/O addressing must then be done for each module.
When doing this, please ensure the permitted references are used:
Modules
References
Analog input modules
3x references
Analog output modules
4x references
Digital input modules
3x or 1x references
Digital output modules
4x or 0x references
Expert modules - input
3x or 1x references
Expert modules - output
4x or 0x references
Downloading the Hardware Configuration
The hardware configuration of a project is saved and can be downloaded to the
simulation program Concept-SIM, Concept-SIM32 or an automation installation. By
doing this, the EQUAL status is established between the host computer and the
PLC.
NOTE: The Concept-SIM must be deactivated for transfer of the configuration to a
real PLC.
102
33002204 12/2010
PLC configuration
5.2
Configuration in OFFLINE and ONLINE mode
Overview
This section contains information for configuration in OFFLINE and ONLINE mode.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
General information
104
Available Functions in OFFLINE and ONLINE Modes
105
103
PLC configuration
General information
At a Glance
In OFFLINE mode no link is created between programming device and PLC, and the
configuration can be performed. In ONLINE mode there is a link between
programming device and PLC, so that only one conditional configuration can take
place.
104
33002204 12/2010
PLC configuration
Available Functions in OFFLINE and ONLINE Modes
Introduction
This section contains an overview of the available functions in OFFLINE and/or
ONLINE mode. The possibilities in the ONLINE mode are different in their use of the
simulator and the real PLC.
Configuration in OFFLINE Mode
In OFFLINE mode all menu commands are available for the hardware configuration
in the PLC Configuration window. The submenus in the Config. Extensions
directory can be enabled in the Select Extensions dialog to extend the
configuration.
If the PLC is in ONLINE mode, you can switch to OFFLINE mode using the menu
command Online →Disconnect.... In the footer of the editor window, the status-bar
indicator NOT CONNECTED appears.
Configuration in ONLINE Mode and in the Active Simulator
A configuration is not possible in ONLINE mode with an active simulator or a
Modbus Plus connection, i.e. no entries can occur. The available dialogs can only
be invoked and read.
You can switch to ONLINE mode using the menu command Online →Connect...
and establishing a connection between the host computer and the PLC.
Configuration in ONLINE Mode and in the Real PLC
Using the connection to a real PLC a configuration in ONLINE mode is possible, as
long as the Change Configuration access level is activated.
It is not possible to configure or reconfigure a PLC while the PLC is in RUN mode.
If a program is already running in the PLC, it must be stopped before reconfiguration
can be implemented. Stop the PLC with Online →Online Control Panel →Stop
PLC. After editing, the changes are automatically transferred to the hardware when
the PLC is started up.
NOTE: When you delete an Expert module in ONLINE mode in the I/O map, the
allocated loadable is also automatically deleted. If you wish to place this module
back in the I/O map at a later time, it will be necessary to download again.
You can switch to ONLINE mode using the menu command Online →Connect...
and establishing a connection between the host computer and PLC.
33002204 12/2010
105
PLC configuration
Effects of ONLINE Changes
If the following conditions are satisfied, all animated windows are automatically
closed if a change is made in the I/O map (e.g. deleting or adding to a module)
Conditions:
ONLINE mode
z animated section(s)
z Status between PLC and host computer is EQUAL
z Controller stopped
z Access level Change Configuration is activated.
z
106
33002204 12/2010
PLC configuration
5.3
Unconditional Configuration
Overview
This section contains a description of the configuration to be performed
unconditionally and an overview of the presettings in the configuration menu.
What's in this Section?
This section contains the following topics:
Topic
Precondition
33002204 12/2010
Page
108
PLC selection
109
CPU Selection for the PLC Type
110
PLC memory mapping
113
Loadables
114
Segment manager
117
I/O Map
119
107
PLC configuration
Precondition
Introduction
Only when the CPU has been selected in the PLC Selection dialog will all the other
menu commands become available in the PLC Configuration window.
The following dialogs are a minimum selection and MUST be edited as part of the
hardware configuration.
z PLC Selection
z
PLC Memory Partition
z
Loadables
z
Segment Scheduler
z
I/O Map
The preferences can be adopted as long as they are compatible with the hardware
being used.
108
33002204 12/2010
PLC configuration
PLC selection
Introduction
Select the PLC family (Quantum, Compact, Momentum or Atrium) and the CPU, as
well as the memory size, according to use. All the available CPUs are listed in the
list box.
Determine logic zone
The logic zone for the desired programming language (IEC or LL984) can be
expanded to the corresponding PLC type with the PLC family selection.
The assignment and installation of the loadables is determined according to the
following settings:
Selection
Meaning
Enable
Installation of the IEC loadables. A desired memory area for the IEC
zone can be set up. The assignment and installation of the loadable
pairing to the selected CPU is performed automatically in the
Loadables dialog.
Disable
No installation of the IEC loadables. This will completely switch off
the IEC zone and the entire logic zone will be made available for the
LL984.
984 only/IEC only
Some Momentum CPUs can only be programmed in the IEC zone
or only in the LL984 zone.
Determine total IEC memory
By defining the total IEC memory size and the global data, you also automatically
determine the IEC-program memory size. On the basis of this size, the available
memory space for the LL984 user program can also be determined.
NOTE: With global data it is the memory space of the unlocated variables.
NOTE: Total IEC memory = IEC program memory + global data
33002204 12/2010
109
PLC configuration
CPU Selection for the PLC Type
Introduction
When installing hardware (Concept EXECLoader), you are required to load various
EXEC data files (*.BIN). This determines the firmware for various PLC types. The
available PLC types, which can be operated by loading the EXEC data files with the
corresponding CPUs, are shown in the following tables.
Loading Firmware for Quantum PLC Types
The following table shows the current EXEC versions, which are located on the
Service Release CD and supplied with Concept.
Quantum PLC type:
140 CPU
Q186Vxxx
(IEC+LL984)
Q486Vxxx
(IEC+LL984)
Q58Vxxxx
(IEC+LL984)
Q5RVxxxx
(IEC+LL984)
QIECVxxx
(IEC only) *
IEC memory
(kbyte)
113 02
X
(LL984 only)
-
-
-
-
113 02S
-
-
-
-
X
113 02X
X
(LL984 only)
-
-
-
-
113 03
X
-
-
-
-
max. 136
113 03S
-
-
-
-
X
max. 379
max. 150
113 03X
X
-
-
-
-
max. 136
213 04
X
-
-
-
-
max. 305
213 04S
-
-
-
-
X
max. 610
213 04X
X
-
-
-
-
max. 305
424 0x
-
X
-
-
-
max. 465
424 0xX
-
X
-
-
-
max. 465
434 12
-
-
X
-
-
max. 890
534 14
-
-
X
-
-
max. 2550
434 12A
(Redesigned
CPU)
-
-
-
X
-
max. 890
534 14A/B
(Redesigned
CPU
-
-
-
X
-
max. 2550
NOTE: * After the QIECVxxx.BIN EXEC data file has been loaded, the EMUQ.EXE
loadable must be loaded into Concept in the Loadables dialog.
110
33002204 12/2010
PLC configuration
Loading Firmware for Quantum LL984 Hot Standby Mode
The Quantum CPUs not ending in X or S can be used for the LL984 Hot Standby
mode. A special EXEC file must be downloaded onto the CPU for this. The loadable
for LL984 Hot Standby (CHS_208.DAT) is automatically installed by the system.
Loading Firmware for Quantum IEC Hot Standby Mode
The 140 CPU 434 12 and 140 CPU 534 14 CPUs can also be used for IEC Hot
Standby. A special EXEC file must be downloaded onto the CPU for this. The
loadables for IEC Hot Standby (IHSB196.EXE and CHS_208.DAT) are
automatically installed by the system.
Loading Firmware for Quantum Equation Editor
The Quantum CPUs not ending in X or S can be used for the LL984 equation editor.
A special EXEC file must be downloaded onto the CPU flash for this. This EXEC file
is not part of the Concept delivery range but can be obtained over the Internet at
www.schneiderautomation.com.
Loading Firmware for Momentum PLC Type
The following table shows the current EXEC versions, which are located on the
Service Release CD and supplied with Concept.
Momentum PLC type (CPU 171 CBB 970 30):
171 CBB
MPSV100.BIN
(LL984 only)
MPSV100e.BIN
(IEC only)
970 30-984
X
-
970 30-IEC
-
X
IEC memory
(kbyte)
236
Momentum PLC type (CPU 171 CCC 7x0 x0):
33002204 12/2010
171 CCC
M1LLVxxx
(LL984 only)
M1IVxxxE
(IEC only)
760 10-984
X
-
760 10-IEC
-
X
780 10-984
X
-
780 10-IEC
-
X
IEC memory
(kbyte)
220
220
111
PLC configuration
Momentum PLC type (CPU 171 CCC 9x0 x0):
171 CCC
M1EVxxx
(LL984 only)
M1EVxxxE
(IEC only)
960 20-984
X
-
960 30-984
X
-
960 30-IEC
-
X
980 20-984
X
-
980 30-984
X
-
980 30-IEC
-
X
IEC memory
(kbyte)
236
236
Momentum PLC type (CPU 171 CCS 7x0 x0):
171 CCS
M1LLVxxx
(LL984 only)
M1IVxxxE
(IEC only)
700 10
X
-
700/780 00
X
-
760 00-984
X
-
760 00-IEC
-
X
IEC memory
(kbyte)
160
The stripped EXEC of the M1 supports up to a maximum of 44 I/O modules.
Loading Firmware for Compact PLC Types
The CTSXxxxD.BIN EXEC file must be downloaded onto the CPU flash for all
Compact CPUs.
Loading Firmware for Atrium PLC Types
A special EXEC file (see table below) must be downloaded onto the CPU flash for
each Atrium CPU.
112
180 CCO
EXEC file
121 01
AI3Vxxxx.BIN
241 01
AI5Vxxxx.BIN
241 11
AI5Vxxxx.BIN
33002204 12/2010
PLC configuration
PLC memory mapping
At a Glance
For the creation of the program, sufficient address zones for the necessary number
of input bits, output/flag bits, input words and output/flag words are to be entered.
An overview of the state RAM value is also given:
z Max. state RAM
z
State RAM in use
z
State RAM use
An unassociated value is shown with an error message, and can be automatically
suited to the given value.
IEC Hot Standby data
After configuration of an IEC Hot Standby system, enter sufficient address zones for
the required number of input words. The higher the number of IEC Hot Standby input
words, the larger the transmit buffers for the IEC component. This means all the
bigger the IEC application in use can be.
CAUTION
System cycle time influence!
The size of the configured state RAM in an IEC Hot Standby project has a
significant effect on the system cycle time. As soon as a configured cycle ends, the
next starts after the transfer of all state RAM data to the CHS module.
Failure to follow these instructions can result in injury or equipment damage.
33002204 12/2010
113
PLC configuration
Loadables
Introduction
Loadables are loadable programs, which are only loaded into the PLC when
required.
The various uses of loadables are described in the following sections.
NOTE: When you delete an Expert module in online mode in the I/O map the
allocated loadable is also automatically deleted. If you wish to place this module
back in the I/O map at a later time, it will be necessary to download again.
Downloading Loadables for the IEC Runtime System
The following loadables for the combined execution of IEC and LL984 programs
(CPU 113 0x, CPU 213 0x or CPU 424 02) are available:
If...
Then...
you want to use CPUs with the
mathematics processor for IEC
programming,
install the loadable pairing @1S7196 and @2I7196.
you want to use CPUs without the
mathematics processor for IEC
programming,
install the loadable pairing @1SE196 and @2IE196.
Downloading Loadables for Expert Modules
The following loadables are available for Expert modules:
If...
Then...
you are configuring the 140 ESI
062 00 module with 32 bit runtime
system and the 140-NOA-611-x0
module
install the loadable ASUP196.
Note: The ULEX196 loadable is automatically installed.
The ASUP 196 loadable is only installed automatically
on 32-bit CPUs. On 16-bit CPUs with Stripped EXEC
(QIECVxxx.BIN), the ASUP196 loadable must be
installed afterwards.
you are configuring the 140 ESI
062 10 module,
install the loadable pairing NSUP + ESI.
Note: These two loadables do not come with the
Concept software package, but are supplied with the
140 ESI 062 10 module and must be unpacked at the
time of installation (Unpack...).
Downloading Loadables for LL984
These are not included in the Concept delivery range. You can order these
loadables via the "Automation Customer Service Bulletin Board (BBS)" (related
topics README).
114
33002204 12/2010
PLC configuration
Downloading Loadables for Hot Standby
The following loadables for Hot Standby mode are available:
If...
Then
you are using the LL984 Hot
Standby mode,
the loadable CHS_208 is automatically installed.
you are using the IEC Hot Standby the loadables IHSB196 and CHS_208 will be loaded
mode,
automatically.
Downloading User Loadables
Loadables that are created by the user are called user loadables (*.EXE, *.DAT).
They are located in the Concept directory DAT and using the Unpack... command
button they can be inserted into the Loadables dialog at installation.
Downloading Loadables for IEC Support Only
The following loadables for IEC support only (CPU 113 xxS without mathematics
processor) are available:
If...
Then
your application uses REAL
arithmetic,
install the loadable EMUQ196.
Note: The loadable is installed together with the EXECfile QIECVxxx (installation in Concept EXECLoader).
Downloading Loadables for INTERBUS and IEC Support Only
The following loadables for IEC support are available:
If the CPU
Then
z
z
z
z
z
install the loadable ASUP196.
Note: The ULEX196 loadable is automatically installed.
The ASUP 196 loadable is only installed automatically
on 32-bit CPUs. On 16-bit CPUs with Stripped EXEC
(QIECVxxx.BIN), the ASUP196 loadable must be
installed afterwards.
113 02S
113 03S
213 04S
534 14
434 12
is configured,
33002204 12/2010
113 03 is configured
install the loadable pairing @1SE196 + @2IE196. The
ULEX196 loadable is automatically installed.
213 04 is configured,
install the loadable pairing @1S7196 + @2I7196. The
ULEX196 loadable is automatically installed.
115
PLC configuration
Downloading Loadables for INTERBUS and LL984 Support Only
The following loadables for LL984 support are available:
If the CPU
Then
z 113 02
z 113 03
z 213 04
you can install the following loadables:
z ULEX196
z @1S7196 + @2I7196 + ULEX196
is configured,
Note: The ULEX196 loadable is automatically installed
with this.
z 534 14
z 434 12
the loadables ASUP196 and ULEX196 will be loaded
automatically.
is configured,
116
33002204 12/2010
PLC configuration
Segment manager
At a Glance
If a remote I/O st. (Drop) is configured, the sequence and method of processing the
LL984 section can be defined in the dialog box Segment manager.
When deleting (in the dialog box I/O map) a configured remote I/O st. (Drop), it is
automatically deleted in the segment manager.
Mode of Functioning
Every I/O st. (Drop) is assigned a segment. It is therefore not permitted to enter
fewer segments in the segment scheduler, than there are I/O st.s (Drops) configured
in the I/O map. In the segment scheduler, the maximum segment numbers is by
default set at 32.
The configurator checks the agreement between the two dialogs and classifies the
I/O st.s (Drops) in the segment scheduler. A window informs you which I/O stations
(Drops) have been inserted.
Altering the segment processing sequence
The sequence for segment processing can be altered manually, in that the segment
number or I/O st. number can be edited in the corresponding line. For the local I/O
st. (Drop), 1 is entered in the first line of the dialog box in the columnsIn stat. and
Out stat. automatically.1
If no sequence was defined, the segments are processed in ascending order.
Sorting criteria for additional I/O st.s
Recently added I/O st.s (Drops) are classified in the segment manager according to
the following criteria:
33002204 12/2010
If…
Then…
A new I/O st. is added,
it is automatically classified behind the last available
line.
All determined segments are
already in use,
the last segment is reused for the input of the new I/O st.
(Drop), i.e. a segment number can be repeated, as the
stations are differentiated.
117
PLC configuration
Available methods for segment processing
When setting the segment manager, the following methods of processing can be
selected:
Processing type
Meaning
Continuous
Cyclic processing
Controlled
Manually controlled processing
WDT reset
Reset watchdog timer
End of logic
End of processing
NOTE: If subprograms are to be used in LL984, the last configured segment cannot
be processed in the segment manager. The type of solution must unconditionally be
End of logic.
Advanced settings in the segment manager
With the "Controlled" type of processing, only the reference numbers 0x and 1x are
authorized, which determines when the logic for the corresponding section is
processed.
The field In. stat. and Out stat. allow the input of corresponding I/O st. numbers,
which must be configured. If a 0is entered, no input/output is served by this segment
number.
118
33002204 12/2010
PLC configuration
I/O Map
Introduction
In the I/O map, configure the I/O stations (drops) with the modules in use. Afterwards
perform the I/O addressing and the parameterization of the configured modules.
Allocating Drops
Drop numbers can be allocated optionally except for the first one (from 2 to ). The
first drop number is automatically recognized as the local drop, and cannot be
edited.
Configuring the Backplane Expander
The 140 XBE 100 00 module is necessary to expand the backplane. By doing this
you can connect a second backplane, and gain 13 extra slots. The 140 XBE 100 00
module is mounted in both backplanes and, in addition, requires an independent
power supply (power supply unit).
Expanded backplanes are configured in Concept in the first drop using slots 2-1 to
2-16.
A more detailed description about the configuration of expanded backplanes with
the 140 XBE 100 00 module is given in the chapter Backplane Expander Config,
page 133.
CAUTION
The slot assignment of the 140 XBE 100 00 is not shown in the configurator,
so a double assignment is possible.
You should take note of the hardware slots of the module and the power supply,
and should not occupy these slots with other modules in the I/O map.
Failure to follow these instructions can result in injury or equipment damage.
NOTE: The flow of data via an expanded backplane is quicker than via the remote
system.
33002204 12/2010
119
PLC configuration
Allocating the I/O Ranges
When allocating the I/O ranges the following references are allowed:
3x references for analog input modules
z
z
4x references for analog output modules
z
3x or 1x references for digital input modules
z
4x or 0x references for digital output modules
z
1x or 3x references for Expert modules (input)
z
0x or 4x references for Expert modules (output)
NOTE: The unique addressing is checked so that no addresses are occupied twice
within the configuration.
Parameterization
Configured modules can be individually parameterized to determine the variable
process conditioned settings.
Connection to other Network Systems
In addition to local and remote drops, links to other network systems can be
established with configured coupling modules:
z Ethernet
z
INTERBUS
z
Profibus DP
See also the chapter entitled Configuration of various network systems, page 137
and Configuration examples, page 877.
120
33002204 12/2010
PLC configuration
Read in Map
In the ONLINE mode of the stopped PLC, the hardware modules are listed in the I/O
map and can be transferred as follows:
Step
1
2
Open the PLC Configuration window.
3
Using the PLC Type menu command, open the PLC Type dialog and select the
PLC type.
4
Connect the host computer to the PLC (Online →Connect...).
5
Open the I/O Map dialog (PLC Configuration →I/O Map).
6
Use the Edit command button to open the Local Quantum I/O station dialog.
7
Check the Poll check box.
Response: The recognized modules are listed in the Read column in color.
8
Double click on the colored text boxes in the Read column.
Response: The listed modules are transferred to the Module column.
9
Enter the address zone in the corresponding columns (In.Ref., In End, Out Ref.,
Out End).
10
33002204 12/2010
Action
Open a project.
After the hardware matching between the host computer and the PLC, the
configuration can continue.
121
PLC configuration
5.4
Optional configuration
Overview
This section contains the description of the optional configuration.
What's in this Section?
This section contains the following topics:
Topic
122
Page
Settings for ASCII Messages
123
Making Additional Functions Available in the Configurator
124
Data Exchange between Nodes on the Modbus Plus Network
125
How many words are really used when data is received (Peer Cop)
126
Protecting Data in the State RAM before Access
128
Parameterize interfaces
129
Special Options
131
33002204 12/2010
PLC configuration
Settings for ASCII Messages
Introduction
To create the ASCII messages, you are required first of all to set a mask, which
contains the number of messages, the message area size and the ASCII ports.
Once you have done that you can create the ASCII messages, which are then
processed with the Ladder Logic programming language.
Precondition
ASCII messages are only possible in the Quantum family, and can only be
processed with the LL984 processing language.
Procedure
To create the ASCII messages, you must first set the mask:
Step
33002204 12/2010
Action
1
In the PLC Configuration →ASCII window, open the ASCII Setup dialog.
2
In the Total Messages text box specify a value from 1 to 999.
3
In the Message Area Size text box specify a value from 1 to 9999 bytes.
4
In the ASCII Ports text box specify an interface from 2 to 32.
5
Confirm your entries with the OK command button.
Response: The settings are saved and the dialog is exited.
6
In the Project main menu open the ASCII Message Editor dialog (with the
ASCII Messages... menu command).
7
Create the ASCII messages here, see also the description ASCII Message
Editor, page 611.
123
PLC configuration
Making Additional Functions Available in the Configurator
Introduction
Additional functions can be used for the configuration, if they have previously been
enabled or set in the Select Extensions dialog.
Activating Advanced functions/Dialogs
By checking the check box or setting the Ethernet modules the corresponding menu
commands are enabled and can be edited in the PLC Configuration →ASCII
window.
The following functions/dialogs can be activated:
Data protection
z Peer Cop
z Hot Standby
z Ethernet I/O-Scanner
z
NOTE: The available functions are dependent upon the configured CPU. Also see
the online help "Select Extensions".
Specify Coupling Modules
Coupling modules must be configured in order to connect to other network systems.
To do this, specify the number of modules in the corresponding list box, which are
then available in the I/O map.
The following systems can be configured:
TCP/IP Ethernet
z
z
Symax-Ethernet
z
MMS-Ethernet
z
Profibus DP
NOTE: The maximum number of coupling modules depends upon the configured
CPU. Also see the online help "Select Extensions".
124
33002204 12/2010
PLC configuration
Data Exchange between Nodes on the Modbus Plus Network
Introduction
With a Modbus Plus (MB+) connection you can configure a PLC using the Peer Cop
functionality, so that data exchange with another PLC is possible. In such a case,
the Peer Cop takes data from a reference area within a "source" PLC and places
this via the Modbus Plus (MB+) network into a determined reference range of a
"destination" PLC. This operation is performed in the same identical way for each
token rotation.
Using the Peer Processor, input data from other nodes on the local network can be
received by the user program. Likewise, output data from the user program can be
transmitted to other nodes on the local network.
The Peer Cop has two variants for data exchange:
z global data exchange
z
specific data exchange
Precondition
The Peer Cop menu command is only available if, in the Select extensions dialog
the Peer Cop check box is checked.
Global Data Exchange
With global data exchange, the data sent from the current "source" PLC is received
by all "destination" PLC devices in the Modbus Plus (MB+) network. Up to 64
destination devices can be reached in this way, which can each receive the data in
8 destination addresses of the State RAM.
See also section "How many words are really used when data is received (Peer
Cop), page 126".
Specific Data Exchange
With specific data exchange, data is sent from a selected "source" PLC to a selected
"destination" PLC in the Modbus Plus (MB+) network. To do this, enter the
respective addresses for the data exchange in a table at the corresponding source
and destination nodes (1-64).
The address must correspond to the MB+ node address on the back of the
respective module. This address setting can be altered and must be specified before
mapping. (See also hardware description)
Select the node to be read or written according to the hardware configuration.
33002204 12/2010
125
PLC configuration
How many words are really used when data is received (Peer Cop)
Introduction
The number of words used may not exceed 500. To avoid this a simple formula can
be used, how many words are used on receipt.
Formula
The formula, to find the number of words used is as follows:
Length + (index – 1) = number of words
Example
The Peer Cop dialog Global Input has the following entry:
126
33002204 12/2010
PLC configuration
The following process takes place:
Step
Action
1.
Bus node 1 sends 1 word to the subfield start reference 400001, starting at index
3.
2.
At index 3 (word 3) the receipt of the data begins. (The preceding words are also
counted.)
Word 1 - 500
3.
In total 3 words are required by subfield 1.
Formula: 1 + (3 - 1) = 3
4.
Bus node 1 sends 18 words to the subfield start reference 400002, starting at
index 5.
5.
At index 5 (word 5) the receipt of the data begins. (The preceding words are also
counted.)
Word 1 - 500
6.
In total 22 words are required by subfield 2.
Formula: 18 + (5 - 1) = 22
NOTE: Only the largest number of words used per bus node by be taken into
account. In the example 22 words from a maximum of 500 permitted words are
used.
For more bus nodes the largest number of words used per bus node must be added.
For example:
33002204 12/2010
127
PLC configuration
Protecting Data in the State RAM before Access
Introduction
Output address ranges (coils and registers) can be protected by specifying the
address from which writing is possible in the Data Protection dialog. All addresses
before this are write-protected.
Precondition
The Data Protection menu command is only available if, in the Select Extensions
dialog, the Data Protection check box is checked.
Entering Access Protection
This access protection operates in connection with "normal" data access, which
happens externally via a Modbus or Modbus Plus interface. Access from the host
computer out is in any case permitted and bypasses this protection mechanism.
128
33002204 12/2010
PLC configuration
Parameterize interfaces
At a Glance
Depending on their use in Concept, the following interfaces must be parameterized:
z ASCII interface
z
Modbus interface
Parameterize ASCII interface
For an ASCII message transmission, the serial communication parameters for the
port interfaces can be specified in the ASCII port settings dialog box.
NOTE: The ASCII port settings dialog box is only available when the number of
ASCII ports has been specified beforehand in the dialog box ASCII set up.
Parameterize Modbus interface
For a Modbus coupling, in the dialog box Modbus port settings the serial
communication parameters of the port interface can be entered on the programming
device, on a CPU and the NOM assemblies (Network Option Module).
CAUTION
Do not make any online changes since this will cause all Editors to close!
The Modbus port settings should not be altered in Online mode, or else all Editors
are automatically closed.
Failure to follow these instructions can result in injury or equipment damage.
NOTE: The settings for a Modbus coupling in Concept only have an effect if the
switch on the front of the assembly is at the lowest position (mem).
Switch position on the NOM
NOTE: If the left-hand switch is in the upper position and right-hand switch is set to
mem then, as of firmware version 2.20, bridge mode is deactivated. This means that
the network connection between Modbus and Modbus Plus is locked.
33002204 12/2010
129
PLC configuration
Interface parameterization with network connections between Modbus and Modbus Plus
A network connection between Modbus and Modbus Plus nodes can be made in the
dialog box Modbus port settings by checking the check box Bridge mode.
NOTE: The settings are only effective if the switch on the front of the assembly is in
the middle position (RTU).
130
33002204 12/2010
PLC configuration
Special Options
Introduction
In the Specials dialog you can configure special options:
z Battery coil
z
Timer register:
z
Time stamp for MMI applications (TOD)
z
Allow duplicate coils
z
Watchdog-Timeout (ms)
z
Time slice for online changes (ms)
Battery coil
You can specify an address of a coil, which shows the status of the battery. This
assignment is used for battery monitoring. In this way, the weak battery can be
replaced early to avoid a loss of data.
Timer Register:
The content of the time register is incremented every 10 ms and has a free value
between 0000 and FFFF hex.
Time for MMI applications (Date/Time)
This time stamp is only intended for a MMI application. Eight registers are reserved
for setting the clock.
The TOD input (Time of Day) is in the American format:
4xxxx
Control register
Discrete 1 (MSB)
Discrete 2
Discrete 3
Discrete 4
33002204 12/2010
4xxxx+1
Day of week (1 - 7)
4xxxx+2
Month (1 - 12)
4xxxx+3
Day (1 - 31)
4xxxx+4
Year (00 - 99)
4xxxx+5
Hours (0 - 23)
4xxxx+6
Minutes (0 - 59)
4xxxx+7
Seconds (0 - 59)
1 = set clock values
1 = read clock values
1 = preset discrete
1 = error discrete
131
PLC configuration
Allow Duplicate Coils
You can assign several outputs to a coil. To do this, check the check box, and
specify the first address to which several outputs can be allocated in the First Coil
Address: text box.
NOTE: This function is unavailable with the Momentum PLC family.
Watchdog Timeout (ms*10)
You can set a pulse supervision for the user program by entering a numerical value
of between 2 and 255 (ms). As soon as there are no count pulses within the specified
time, an error message will appear.
Time Slice for Online Changes (ms)
You can set a time supervision for the communication between the nodes by
entering a numerical value between 3 and 30 (ms). As soon as there is no
communication within the specified time, an error message will appear.
132
33002204 12/2010
PLC configuration
5.5
Backplane Expander Config
Introduction
This chapter describes the function and configuration of the backplane expander.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
Generals to Backplane Expander
134
Edit I/O Map
135
Error handling
136
133
PLC configuration
Generals to Backplane Expander
Introduction
The Quantum backplane expander provides a single backplane expansion to a local
drop or a RIO drop through the 140 XBE 100 00 module.
Function description
The module connects two Quantum backplanes (primary and secondary) through a
custom cable and support all data communication between the backplanes. Each
backplane requires a 140XBE10000 module that occupy a single slot and requires
its own power supply.
Procedure at an Error
The backplane expander is designed in the way that if it is not installed or improperly
connected, it will not effect the functionality of the primary rack. Only the backplane
expander installed and connected properly, the both racks are then able to
communicate and controlled by prime CPU or RIO drop controller.
134
33002204 12/2010
PLC configuration
Edit I/O Map
Requirements
Currently only Quantum controllers support backplane expander. Primary rack
contains the CPU or RIO drop controller and is allowed to config all type of additional
modules up to the physical slot address limitation. All I/O modules can be also added
to the secondary rack. However, option modules, such as NOMs, NOEs and CHSs
must reside in the primary rack.
To place a module in proper rack, it is necessary to add an extra attribute in the I/O
module database to specify that the module is available only for the primary or
secondary or both.
Configuration in I/O Map
Exist Quantum local drop or RIO drop only support one rack up to sixteen slots. With
backplane expander, it is extended as if the drop support two racks, and each has
sixteen slots. By clicking at the button ... on Module column, all modules available
to the rack clicked (primary or secondary) will show in the module selection dialog
that can be selected and assigned to the current slot.
Each rack requires a 140 XBE 100 00 module to make backplane expander work
properly.
NOTE: The 140 XBE 100 00 module does not have a personality code and therefore
can not be recognized by the Concept.
The module will just look like an unfilled slot in the Concept I/O map. If any module
is configured in the secondary rack, it is user’s responsibility to ensure there is one
slot in each rack that is reserved for 140 XBE 100 00 module and all hardware are
connected properly.
33002204 12/2010
135
PLC configuration
Error handling
Introduction
The validate processes for the primary rack will be applied to the secondary rack too,
such as duplicate reference, missing input or output reference, etc. Besides existing
regular validation, traffic cop will do some special check for the backplane expander.
No reserved slot for 140 XBE 1000 00
If any module is found in the secondary rack and there is no empty slot left in either
of racks when user trying to exit the rack editor dialog, an error message will be
displayed: "There must be one empty slot reserved for 140 XBE 100 00 module in
each rack to make backplane expander work." The rack editor dialog will then not
be closed.
Special module in secondary rack
To prevent any special module (such as, NOE, CHS, etc) being added to the
secondary rack, rack editor dialog do not allow to cut/copy these head modules. It
will also check module personalities before user try to do any paste operation. If
some unsupported module for the secondary rack is found, an error message will be
displayed: "The buffer contains some module that can not reside in the secondary
rack." The paste operation will be aborted.
136
33002204 12/2010
PLC configuration
5.6
Configuration of various network systems
Overview
This section contains the description of the configuration of various network
systems.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
Configure INTERBUS system
138
Configure Profibus DP System
139
Configure Ethernet
141
RTU extension
143
Ethernet I/O Scanner
144
How to use the Ethernet / I/O Scanner
149
137
PLC configuration
Configure INTERBUS system
At a Glance
The configuration of the INTERBUS system can take place within the PLC families
of Quantum and Atrium.
INTERBUS configuration with Quantum
With the Quantum family the coupling of a remote bus takes place in a Quantum I/O
station (Drop). To do this, the INTERBUS Master NOA 611 00 must be configured
and parameterized in the CMD tool (Configuration Monitoring and Diagnostic Tool).
See also Configuration example 4 (see page 910).
INTERBUS configuration with Atrium
With the Atrium family, the coupling of the remote bus takes place via the master
assembly 180 CCO 121 01, 180 CCO 241 01 or 180 CCO 241 11 in this way, the
INTERBUS Master CRP 660 0x is automatically inserted into the local I/O station
(Drop). The INTERBUS I/O station (Drop) nodes are configured in the CMD tool
(Configuration Monitoring and Diagnostic tool), saved as a *.SVC data file and
imported to Concept. After the import into the I/O map the configuration can be
changed afterwards in Concept.
See also Configuration example 9 (see page 955).
138
33002204 12/2010
PLC configuration
Configure Profibus DP System
Introduction
The configuration of the Profibus DP system can take place within the PLC families
of Quantum and Atrium.
Profibus DP Configuration with Quantum
With the Quantum family the connection to the Profibus DP system takes place in a
Quantum drop. To do this, you must first of all set the number of bus controllers
(CRP 811 00) used in the Select Extensions dialog. The modules then appear in
the list box of the I/O Module Selection dialog and can be inserted into the I/O map.
The configuration of the Profibus DP node is created in the SyCon configuration tool,
saved as a *.CNF file and transferred directly to Concept. However, the
configuration (*.CNF) can be imported to Concept at a later time.
CAUTION
PROFIBUS DP ADDRESSES MAY BE OVERWRITTEN
When working with Profibus DP configuration make sure that the addresses of two
8 bit E/A modules without gap to the following 16 bit limit is only permitted when
both 8 bit modules belong to the same Profibus DP master. If you do not adhere to
this guideline, the input bits of one module (e.g. Profibus DP Master A) may be
overwritten by the other module (e.g. Profibus DP Master B).
Failure to follow these instructions can result in injury or equipment damage.
33002204 12/2010
139
PLC configuration
Importing the Profibus DP Configuration
To import the configuration (*.CNF) to Concept, proceed as follows:
Step
Action
1
In the PLC Configuration window, open the I/O Map dialog.
2
Select the drop and use the Editdialog Local Quantum I/O Drop.
3
Double click on the in the Modulecolumn.
Reaction: The I/O Modules Selection dialog is opened.
4
In the I/O Adapter column, select the CRP-811-00 module, and press the OK
command button.
Reaction: The CRP-811-00 will be inserted in the I/O map.
5
In the Local Quantum I/O Drop dialog, select the line of the mapped bus
controller (CRP-811-00) and press the Params command button.
Reaction: The CRP-811-00 (Profibus DP) dialog will open.
6
Using the Import open the Select Import File window.
7
To import, specify the path of the CNF file, and press the OK command button.
Reaction: The Profibus DP configuration is entered in the Concept I/O map.
Note: After the Profibus DP nodes are entered into Concept, the reference
ranges for all modules and diagnostic data must be edited later.
Configuration Example
An example of configuration is given in Example 11 (see page 925).
140
33002204 12/2010
PLC configuration
Configure Ethernet
Introduction
An Ethernet bus system can be configured within the following PLC families:
z Quantum
z Atrium
z Momentum
Precondition
In order to connect to the Ethernet bus system, a PCI network card must be
available in the host computer. Afterwards the Ethernet interface needs to be
parameterized and the drivers that are provided on CD need to be installed
(Configure Ethernet, page 975).
After the Ethernet module has been slotted into the central backplane, the internet
address, subnet mask, gateway and frame type can be allocated by the network
administrator.
Configuration with Quantum
The procedure for Ethernet configuration in Concept is as follows:
Step
33002204 12/2010
Action
1
In the PLC Configuration window, open the Select Extensions dialog.
2
Enter the number of Ethernet modules (NOE) in the text boxes.
Response: The modules then appear in the list box in the I/O Module Selection
dialog and can be inserted into the I/O map.
3
In the PLC Configuration window, open the Ethernet I/O Scannerdialog, in
which you enter the information from the network administrator (Internet
address, subnet mask, gateway, frame type).
4
In the Online main menu, open the Connect to PLC dialog (menu command
Connect...).
5
In the Protocol Type list box, select the option TCP/IP, and in the IP address
or DNS Hostname text box, enter the address of the TCP/IP card.
6
After programming, in the Online main menu, open the Load into PLC dialog
(menu command Load...), and click on the Load command button.
Response: A message appears, asking whether you would like to start the PLC.
7
Before you confirm the message with the Yes command button, the display "link"
must appear on the Ethernet module.
141
PLC configuration
Error Action
After configuration, only start the PLC once the display "link" has appeared on the
Ethernet module. If this is not the case, withdraw the Ethernet module from the
central backplane and then slot it in again. If the display "link" is still not shown, there
must be a serious error.
Available Ethernet Modules
The maximum number of NOE modules is dependent upon the configured CPU
(select in the PLC Selection dialog):
CPUs
Number of NOE modules
113 02/S/X
0-2
113 03/S/X
0-2
213 04/S/X
0-2
424 0x/X
0-6
434 12
0-6
534 14
0-6
Configuration with Momentum
The configuration of the Ethernet bus system with Momentum is described in the
section Momentum Example - Ethernet Bus System, page 974.
142
33002204 12/2010
PLC configuration
RTU extension
Requirements
To make the RTU menu command available you have to choose a Compact CPU
with LL984 programming language in the PLC Selection dialog.
CTS-/RTS-Delay
In this dialog you can set time delay for CTS or RTS independently for Comm port
1 of your Compact PLC. This feature allows modem communications with radios that
require longer time frames. The delay time range is 0 ... 500 ms using 10 ms units.
Enter the time delays your require.
Secured Data Area (SDA)
This feature allows you to configure an area in RAM that is secured from being
overwritten. Secured Data Area (SDA) is a block of the Compact PLCs RAM that is
set aside as 6x data space. The SDA can only be written to by specific functions that
require secured data storage. General purpose Modbus commands, builtins, can
not write to the SDA. Modbus Read (function 20) is able to read from the SDA,
Modbus Write (function 21) is not able to write to the SDA. The SDA size range is 0
... 128 K words using only 1 K word blocks. Enter the size your require.
Refer to the applicable user manual for the specific function for the required SDA
size. For example, for Gas Flow, refer to the "Starling Associates Gas Flow
Loadable Function Block" User Guide (890 USE 137 00).
PLC Login Password Protection
For the description of password protection, refer to section Set PLC Password,
page 660.
33002204 12/2010
143
PLC configuration
Ethernet I/O Scanner
Introduction
This function is for the following Quantum modules available:
140-NOE-211-x0
z 140-NOE-251-x0
z 140-NOE-771-xx
z
This function is for the following Momentum modules available:
z 171-CBB-970-30
z 171-CCC-960-20
z 171-CCC-980-20
z 171-CCC-980-30
z 171-CCC-960-30
Ethernet address and I/O scanning parameters can be modified using the Ethernet
/ I/O Scanner dialog box. From the PLC Configuration window, select Ethernet /
I/O Scanner. This menu option will only be available if you have selected an M1
Processor Adapter with an Ethernet port or have Quantum TCP/IP Ethternet
modules (NOE) as specified above.
This section describes how to configure the Ethernet port, including IP address,
other address parameters and I/O scanning.
Ethernet Configuration Options
The Ethernet / I/O Scanner screen offers three options for configuring the Ethernet
port on an M1 Processor Adapter:
144
Configuration options
Meaning
Specify IP Address
This is the default option. It allows you to type the IP address,
gateway and subnet mask in the text boxes in the upper righthand
corner of the screen.
Use Bootp Server
Click this radio button if you want the address parameters to be
assigned by a Bootp server. If you select this option, the address
parameter text boxes in the upper righthand corner of the screen
will be grayed out. They will not display the actual address
parameters.
Disable Ethernet
Click this radio button if you want to disable the Ethernet port.
Disabling the port will reduce the scan time for the Processor
Adapter.
33002204 12/2010
PLC configuration
Setting Ethernet Address Parameters
If you choose to specify the IP address, you should complete all four text boxes in
the upper righthand corner of the dialog box:
Parameters
Meaning
Internet Address
Type a valid IP address in the Internet Address text box (for
example: 1.0.0.1).
CAUTION
Potential for duplicate addresses
Obtain a valid IP address from your system administrator to avoid duplication.
Failure to follow these instructions can result in injury or equipment damage.
Gateway
Consult your system administrator to determine the appropriate
gateway. Type it in the Gateway text box.
Subnet Mask
Consult your system administrator to obtain the appropriate
subnet mask. Type it in the Subnet Mask text box (for example:
255.255.255.0).
Frame Type
For NOE there is an additional Frame Type field. Your two
possible choices are ETHERNET II or IEEE 802.3
NOTE: Changing the subnet mask or the frame type and downloading the
application via the NOE hinder the I/O scanner to run after a PLC start.
Disconnecting Concept then leads to run the I/O scanner.
Configuring I/O
Once the Ethernet port address parameters have been set, you may assign
parameters for I/O scanning.
The text box Master Module (Slot) contains the Module type that you have
configured for Ethernet communications. In the case of the Momentum Ethernet
controller the slot will always be number 1, and the configured module type is
displayed in the variable dialog field. If you are configuring a NOE in a standard rack
the slot number assigned in the I/O Map will be displayed along with the module
type. Until the I/O Map is conmpleted this test field will indicate "Unassigned". In
instances where more than one NOE is configured the I/O Scan parameters reflect
the unit currently in the dialog box from which you can select the additional unit by
activating the Pulldown list.
33002204 12/2010
145
PLC configuration
The text field Health Block (1x/3x) is only available by using the 140-NOE-771-xx.
The health timeout is used for setting the health bit. If the response arrives before
the end of the HealthTimeout period, the health bit is set; otherwise it is cleared. If
the Health Timeout is zero, the health bit is set to true once communications are
established, and it is never cleared.
NOTE: The configuration of the health block, refer to the user guide Quantum NOE
771 xx Ethernet Modules, model no. 840 USE 116 00.
The text box Diagnostic Block (64 words, 3x or 4x registers) is only available by
using the Momentum Ethernet (M1E) and allows you to define the starting register
of a number of bits which are used for diagnostic. The block can be specified in
either 3x or 4x registers. For more information, refer to the user guide Quantum NOE
771 xx Ethernet Modules, model no. 840 USE 116 00.
The Device Control Block is only available when using NOE 771-01(11) with the
Firmware Rev. 3.5 and higher.
Enable this check box, to enable/disable the I/O scanner entry.
Each entry in the I/O scanner can be enabled or disabled by setting the related bit
in the control block.
z Bit=1, than I/O scanning stops, corresponding Health bit = 0 (socket is closed)
z Bit=0, than I/O scanning starts, corresponding Health bit = 1.
For more information, please refer to Quantum NOE 771 xx, Ethernet Modules, User
Guide in Chapter I/O-Scanner Enable/Disable.
I/O Scanner Configuration table:
146
Column
Description
Slave IP Address
Type the IP address of the slave module in this column (for example:
128.7.32.54). This address will be stored in a pulldown menu, so that
you may use it in another row by clicking on the down arrow and
selecting it.
Unit ID
If the slave module is an I/O device attached to the specified slave
module, use the Unit ID column to indicate the device number. The Unit
ID is used with the Modbus Plus to Ethernet bridge to route to Modbus
Plus networks.
Health Timeout
Use this column to specify the length of time in ms to try the transaction
before timing out. Valid values are 0 ... 50 000 ms (1 min).
To avoid timing out, specify 0.
Rep Rate
Use this column to specify how often in ms to repeat the transaction.
Valid values are 0 ... 50 000 ms (1 min).
NOTE: For legacy NOEs the repetition rate must be 0 or a multiple of 16
ms. Legacy NOEs are the NOE 771 00 versions and NOE 771 01/NOE
771 11 versions lower than rev. 4.3.
33002204 12/2010
PLC configuration
WARNING
Unpredictable operation
The repetition rate values of NOEs with firmware rev. 4.3 and higher must be 0 ms
or a multiple of a step size between 5 ms (minimum) and 200 ms (maximum). The
minimum cyclic repetition rate that is allowed is 5 ms.
If you configure more than one slave and want to use different repetition rates, then
you must ensure that the repetition rates have a common step size.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Examples: If one repetition rate in the I/O scanner is set to 6 ms, all other repetition
rates values must be a multiple of 6 (i.e. 6 ms, 12 ms, 18 ms, 24 ms, etc.)
z Repetition Rates 24 ms, 30 ms, 36 ms, 42 ms are also valid becaue the step size
is 6 ms
z Repetition Rates 0 ms, 35 ms, 42 ms, 70 ms, 14 ms are valid because the step
size is 7 ms
z Repetition Rates 24 ms, 35 ms, 19 ms are not valid because there is no common
step size
z Repetition Rates 20 ms, 100 ms, 300 ms are not valid because the max. limit has
been exceeded
z Repetition Rates 0 ms, 3 ms, 30 ms are not valid because the min. limit has been
exceeded
I/O Scanner Configuration table continued:
33002204 12/2010
Column
Description
Read Ref Master
Use the read function to read data from the slave to the master.
This column specifies the first address to be read (for example: 400001).
Read Ref Slave
Use the read function to transfer data from the slave to the master.
This column specifies the first address of up to 125 to read to (for
example: 400050).
Read Length
Use the read function to read data from the slave to the master.
This column specifies the number of registers to read (for example: 20).
Write Ref Master
Use the write function to write data from the master to the slave.
This column specifies the first address to write (for example: 400100).
Write Ref Slave
Use the write function to write data from the master to the slave.
This column specifies the first address of up to 100 to write to (for
example: 400040).
Write Length
Use the write function to write data from the master to the slave.
This column specifies the number of registers to write (for example: 40).
Description
You can type a brief description (up to 32 characters) of the transaction
in this column.
147
PLC configuration
NOTE: You may include read and write commands on the same line.
How to use
For more information about how to use the Ethernet / I/O Scanner dialog see section
How to use the Ethernet / I/O Scanner, page 149.
148
33002204 12/2010
PLC configuration
How to use the Ethernet / I/O Scanner
Introduction
This section describes how to complete your Ethernet I/O configuration using the
Copy, Cut, Paste, Delete and Fill Down buttons.
Copy and Paste
To save time when typing similar read and write commands, you may copy and
paste entire rows within your configuration:
Step
Action
1
Select the row you want to copy by clicking on the row number at the far left.
2
Click the Copy button above the I/O configuration list.
3
Select the row where you would like to paste the data (by clicking on the row
number at the far left).
4
Click the Paste button.
Cut and Paste
To move a row within the configuration list, follow the direction:
Step
Action
1
Select the row you want to move by clicking on the row number at the far left.
2
Click the Cut button above the I/O configuration list.
3
Select the row where you would like to paste the data (by clicking on the row
number at the far left).
4
Click the Paste button.
Note: Multiple rows may be cut/copy and pasted. The number of rows actually
pasted is limited by the number of rows selected. For example if you copy 10
rows to the clipboard, then select an area of 6 rows to past, only the first six rows
of clipboard data is pasted.
Delete
To delete a row within the configuration list, follow the direction:
Step
33002204 12/2010
Action
1
Select the row you want to delete by clicking on the row number at the far left.
2
Click the Delete button above the I/O configuration list.
Note: Multiple rows may be deleted.
149
PLC configuration
Fill down
To copy part of any row to the next row or to a series of adjoining rows, use the Fill
Down button, following the steps in the table
Step
Action
1
Use your mouse to select the data you would like to copy and the cells you would
like to copy it to.
Note: You must select one contiguous block of cells, with the data to be copied
in the first row. You cannot select two separate blocks.
2
Click the Fill down Button.
Result: The data from the first row is copied to the selected cells in the defined
block.
NOE Ethernet modules
In this dialog the NOE Ethernet modules 140 NOE 211 x0,140 NOE 251 x0 and 140
NOE 771 10 are parameterized (in the Ethernet Configuration area).
In this dialog the NOE Ethernet module 140 NOE 771 00 is parameterized and
addressed (in the I/O Scanner Configuration area).
For the followings modules you receive an function description:
z 140 NOE 211 x0
z 140 NOE 251 x0
z 140 NOE 771 xx
Momentum Ethernet modules
In this dialog the Momentum Ethernet modules are addressed (in the I/O Scanner
Configuration area).
For the followings modules you receive an function description:
171 CBB 970 30 IEC
z 171 CBB 970 30 984
z 171 CCC 980 30 IEC
z 171 CCC 980 30 984
z 171 CCC 980 20 984
z 171 CCC 960 30 IEC
z 171 CCC 960 30 984
z 171 CCC 960 20 984
z
150
33002204 12/2010
PLC configuration
5.7
Quantum Security Settings in the Configurator
Quantum Security Parameters
Introduction
Various security parameters can be defined in the configuration of the Quantum
CPUs 140 434 12A and 140 534 14A/B which are indicated in the log file *.LOG. This
guarantees secure process documentation which includes the logging with the
automatic logout, write access of NOEs/NOMs on the PLC as well as limited
participants (max. 12) for network write access.
The definition of the security parameters can be found in dialog Configuration →
Security Expansion.
Dialog Quantum Security Parameters:
Requirements
The security parameters are only available if the following conditions have been met:
z Supervisor Rights (see Concept under Help →Info... →Current User:)
z only with CPUs 140 CPU 434 12A and 140 CPU 534 14A/B
33002204 12/2010
151
PLC configuration
Automatic Logout
Auto. logout is only available for Quantum CPU 434 12A and 534 14 A/B.
The automatic logout procedure logs a user out as soon as a predefined time limit
(max. 90 minutes) is reached with no activity on the connection. This could be a lack
of read or write activity from the programming device to the PLC for example.
The Never setting disables this function, i.e. automatic logout cannot occur.
NOTE: Automatic logout does not function if:
z
z
the programming device (Concept) is connected to the PLC not via the local
ModbusPlus Port of the CPU, but via a NOE/NOM module
and at the same time
another device is connected to the same NOE/NOM module with read access to
the PLC.
Disable All Writes from NOEs/NOMs
By disabling all write accesses of
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
140 NBE 210 00 (ID-Code 0x0406)
140 NBE 250 00 (ID-Code 0x0407)
140 NOE 211 00 (ID-Code 0x0404)
140 NOE 251 00 (ID-Code 0x0405)
140 NOE 311 00 (ID-Code 0x0408)
140 NOE 351 00 (ID-Code 0x0409)
140 NOE 511 00 (ID-Code 0x040A)
140 NOE 551 00 (ID-Code 0x040B)
140 NOE 771 00 (ID-Code 0x040D)
140 NOE 771 01 (ID-Code 0x0422)
140 NOE 771 10 (ID-Code 0x040E)
140 NOE 771 11 (ID-Code 0x0423)
140 NOM 211 00 (ID-Code 0x010C)
140 NOM 212 00 (ID-Code 0x010C)
140 NOM 252 00 (ID-Code 0x010C)
140 NWM 100 00 (ID-Code 0x0420)
to the PLC, all write instructions are ignored by the CPU and responded to with an
error message.
NOTE: MSTR read operations are not executed if the check box Disable All Writes
from NOEs/NOMs is checked. (this also means the error state of the MSTR block
shows no error!)
Disable all Writes from CPU Modbus Ports
To disable writes from the Quantum CPU Modbus connections, check the Disable
all Writes from CPUs from Modbus Ports check box.
152
33002204 12/2010
PLC configuration
Limited Write Access on the Modbus Plus Network
A restricted number of participants that have access to the PLC can be configured
for the Modbus Plus network. A maximum of 12 participants are allowed, the
participant address of the programming device is automatically entered in the
participant list and cannot be deleted.
Dialog Add Modbus Plus Address (press Add...)
Examples of Modbus Plus paths
Modbus Plus network:
The address must be entered from the point of view of the receiving PLC to the
sender, and thus begins at the first gateway or the next PLC. This depends on
whether the sender and the receiver are located in the same Modbus Plus segment
(no bridges/gateways) or whether the sender and the receiver are located in
different segments (separated by one or more bridges/gateways).
33002204 12/2010
153
PLC configuration
Example 1:
Concept (MB+ Address 1) writes to PLC 6. There are no bridges or gateways
between the two participants. Thus, the address entered appears as follows: 1 or
1.0.0.0.0
Example 2:
PLC 2 (MB+ Address 2) writes to PLC 6. A gateway (MB+ Address 3) is located
between the two participants. Thus, the address entered appears as follows:
3.2.0.0.0
NOTE: Only the first Modbus Plus address can be recognized by the PLC. Thus, as
soon as this first address is a bridge or a gateway, all devices in the network behind
the bridge or gateway have write access to the PLC. Thus, in our example PLC 7
could also write to PLC 6 (Address: 3.7.0.0.0).
154
33002204 12/2010
PLC Memory and optimization
33002204 12/2010
Main structure of PLC Memory
and optimization of memory
6
Overview
This Chapter describes the main structure of the PLC Memory and the optimization
of the memory with the different PLC families.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
6.1
Main structure of the PLC Memory
156
6.2
General Information on Memory Optimization
157
6.3
Memory Optimization for Quantum CPU X13 0X and 424 02
162
6.4
Memory Optimization for Quantum CPU 434 12(A) and 534
14(A/B)
176
6.5
Memory optimization for Compact CPUs
187
6.6
Memory optimization for Momentum CPUs
197
6.7
Memory optimization for Atrium CPUs
204
155
PLC Memory and optimization
6.1
Main structure of the PLC Memory
General structure of the PLC Memory
At a Glance
In principle, the memory of a PLC consists of three parts:
the memory for the Exec file,
z the state RAM and
z the program memory.
z
Memory for the EXEC file
The EXEC file contains the operating system and one or two runtime systems (IEC
and/or LL984) for operating the user programs.
State RAM
The state RAM can be divided into different zones:
z the used 0x, 1x, 3x and 4x references,
z a reserve for further 0x, 1x, 3x and 4x references,
z possibly an extended memory zone for 6x references.
Program Memory
The program memory can be divided into different zones:
z the I/O map etc.,
z a reserve for extensions,
z the ASCII messages (if used), the Peer Cop configuration (if used), the Ethernet
configuration (if used) etc.,
z a reserve for extensions,
z the IEC loadables (if required),
z the Global Data, consisting of the Unlocated Variables,
z the IEC program memory with the program codes, EFB-Codes and program data
(section data and DFB instance data),
z possibly the ULEX loadable for INTERBUS or other loadables,
z the LL984 program memory.
156
33002204 12/2010
PLC Memory and optimization
6.2
General Information on Memory Optimization
Overview
This Section contains general information on memory optimization.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
Possibilities for Memory Optimization
158
PLC-Independent
159
157
PLC Memory and optimization
Possibilities for Memory Optimization
Description
The possibilities for memory optimization are partly dependent on the PLC family
and CPU used:
z PLC-Independent, page 159
z Memory Optimization for Quantum CPU X13 0X and 424 02, page 162
z Memory Optimization for Quantum CPU 434 12(A) and 534 14(A/B), page 176
z Memory optimization for Compact CPUs, page 187
z Memory optimization for Momentum CPUs, page 197
z Memory optimization for Atrium CPUs, page 204
158
33002204 12/2010
PLC Memory and optimization
PLC-Independent
Introduction
There are 3 PLC-independent possibilities for memory optimization:
z Optimize State RAM for 0x and 1x References, page 159
z Only Download Required Loadables, page 160
z Optimize Expansion Size, page 161
Optimize State RAM for 0x and 1x References
The state RAM contains the current values of the 0x, 1x, 3x and 4x references.
Even if the state RAM zone is outside the program memory zone, the size of the
state RAM for 0x and 1x references influences the size of the program memory.
Therefore, do not select a state RAM zone that is too large. In theory, the procedure
only needs as many 0x and 1x references as the hardware requires. However, you
will require a somewhat larger number of references if the I/O map is to be extended.
It is advisable to be generous with the number of references during the creation
phase of the user program when frequent changes are still being made. At the end
of the programming phase, the number of these references can be reduced in order
to create more space for the user program.
The settings for the 0x-, 1x-references can be found in Project →PLC
Configurator →PLC Memory Partition.
In this dialog box, there is an overview of the size of the occupied state RAM zone
and the percentage of the maximum state RAM that this represents.
33002204 12/2010
159
PLC Memory and optimization
Optimize state RAM for 0x, 1x, 3x and 4x references:
Only Download Required Loadables
All the installed loadables are downloaded into the program memory zone and
occupy space. Therefore, only install those loadables which you really need (related
topics Loadables, page 114).
The memory space occupied by the installed loadables is displayed in the
Loadables dialog box under Used Bytes (Project →PLC configurator). This
information is calculated from the size of the loadable files and from the memory size
assigned to the loadables.
160
33002204 12/2010
PLC Memory and optimization
Optimize Expansion Size
Each time, there is the possibility to reserve memory space for later expansion in the
mapping zone (I/O map) and in the configuration expansion zone (Peer Cop). This
memory space is necessary if e.g. the I/O map or the Peer Cop settings should be
changed online. It is advisable to overestimate the reserves during the installation
phase of the user program, that is, when modifications are often being made. At the
end of the programming phase the reserves may be reduced again, to provide more
space for the user program.
The settings for the mapping reserves are found in Project →PLC Configurator →
I/O Map →Expansion Size. The settings for the Peer Cop reserves can be found in
Project →PLC Configurator →Config. Extensions →Select Extensions →Peer
Cop →Expansion Size.
Optimize Expansion Size
33002204 12/2010
161
PLC Memory and optimization
6.3
Memory Optimization for Quantum CPU X13 0X
and 424 02
Overview
This Section describes the memory optimization for the Quantum CPUs CPU X13
0X and CPU 424 02.
What's in this Section?
This section contains the following topics:
Topic
162
Page
General Information on Memory Optimization for Quantum CPU X13 0X and
424 02
163
Selecting Optimal EXEC File
165
Using the Extended Memory (State RAM for 6x references)
169
Harmonizing the IEC Zone and LL984 Zone
171
Harmonizing the Zones for Global Data and IEC Program Memory
173
33002204 12/2010
PLC Memory and optimization
General Information on Memory Optimization for Quantum CPU X13 0X and
424 02
Logic Memory
The program memory zone, in which the user program is located, is called the logic
zone. This zone therefore determines the maximum size of your user program.
The current size of the logic zone is displayed under Project →PLC Configuration
in the configurations overview in the PLC zone. The entry for the memory size is
given in Nodes for LL984 (1 node equals 11 bytes) and in kilobytes for IEC.
Optimizing the Logic Memory
You have various possibilities for optimising the logic memory to suit your
requirements:
z Selecting Optimal EXEC File, page 165
z Using the Extended Memory (State RAM for 6x references), page 169
z Harmonizing the IEC Zone and LL984 Zone, page 171
z Harmonizing the IEC Zone and LL984 Zone, page 171
NOTE: Also note the PLC-independent possibilities for memory optimization
(see page 157).
33002204 12/2010
163
PLC Memory and optimization
Structure of the CPU X13 0X memory (simplified representation):
164
33002204 12/2010
PLC Memory and optimization
Selecting Optimal EXEC File
Introduction
The simplest and most basic option is to download the optimal EXEC file for your
requirements onto the PLC (see also Installation Instructions).
Depending on which EXEC file you select, zones will be reserved in the program
memory of the PLC for IEC and/or LL984 programs. Therefore, if you install a
'combined EXEC file' and then only use one of the two language types in the user
program, the program memory will not be used optimally.
Therefore, decide which languages you want to use:
z Exclusive Use of IEC, page 165
z Exclusive Use of LL984, page 166
z Joint Use of IEC and LL984, page 167
Exclusive Use of IEC
If you want to use IEC exclusively, download the EXEC file "QIEC_xxx.bin" (not
available for CPU 424 02). Since this EXEC file does not contain an operating
system, you have to download the IEC runtime system onto the PLC in the form of
a loadable (EMUQ.exe) (related topics Loadables, page 114). The loadable is
downloaded into the program memory zone and takes up memory space.
33002204 12/2010
165
PLC Memory and optimization
Structure of the CPU X13 0X memory with exclusive use of IEC:
Exclusive Use of LL984
If you want to use LL984 exclusively, download the EXEC file "Q186Vxxx.bin" for a
CPU X13 0X and the EXEC file "Q486Vxxx.bin" for a CPU 424 02.
166
33002204 12/2010
PLC Memory and optimization
Structure of the CPU X13 0X memory with exclusive use of LL984:
Joint Use of IEC and LL984
If joint use of IEC and LL984 is required, download the EXEC file "Q186Vxxx.bin" for
a CPU X13 0X and the EXEC file zone "Q486Vxxx.bin" for a CPU 424 02. Since
these EXEC files only contain the LL984 operating system, you have to download
the IEC operating system onto the PLC in the form of loadables (@2I7/@2IE or
@1S7/@1SE) (see also Loadables, page 114). Both loadables will be downloaded
into the program memory zone and occupy memory space.
NOTE: Joint use of IEC and LL984 is not possible with the CPU 113 02 because its
memory is too small for this application.
33002204 12/2010
167
PLC Memory and optimization
Structure of the CPU X13 0X memory with joint use of IEC and LL984:
168
33002204 12/2010
PLC Memory and optimization
Using the Extended Memory (State RAM for 6x references)
Introduction
If a CPU 213 04 or CPU 424 02 is used, you can make a zone in the state RAM
available for the 6x references.
NOTE: 6x references are registers and can only be used with LL984 user programs.
Even if the state RAM memory zone is outside the program memory zone, the size
of the state RAM influences the size of the program memory.
Using the extended memory (state RAM for 6x references):
33002204 12/2010
169
PLC Memory and optimization
If you do NOT use 6x
If you do not want to use any 6x references, you can, with a CPU 213 04, select
whether to reserve state RAM 6x references or not.
Under Project →PLC Configuration →PLC Selection select from the Memory
Partition the 48 K Logic / 32 K Memoryentry.
NOTE: With a CPU 424 02 there is no option for deactivating the 6x zone.
If you use 6x
If you want to use 6x references, select under Project →PLC Configuration →PLC
selection in the Memory Partition list box, the 32 K Logic / 64 K Memoryentry.
170
33002204 12/2010
PLC Memory and optimization
Harmonizing the IEC Zone and LL984 Zone
Introduction
With joint use of IEC and LL984 sections, the sizes of both zones should be
harmonized with each other.
Harmonizing the IEC zone and LL984 zone:
33002204 12/2010
171
PLC Memory and optimization
Size of IEC Zone
The size of the total IEC memory and also the available space for LL984 data (user
program) is determined by the memory size of the loadable @2I7 or @2IE.
You can define the memory size of the loadables in Project →PLC Configuration
→Loadables →Install @2I7 or @2IE →Edit... →Memory Size.
The total size is given in paragraphs. A paragraph equals 16 bytes.
For the @1S7 or @1SE loadables, no memory size is needed. Ensure that "0" is
specified here.
The fixed total IEC memory size is again made up of several zones. You will find the
explanation of how to harmonize these zones vertically in the chapter Harmonizing
the Zones for Global Data and IEC Program Memory, page 173.
Size of LL984 Zone
The size of the available memory for LL984 user programs is calculated using the
following formula:
LL984 zone = available LL984 nodes – memory size of loadable @2I7/@2IE – size
of loadables @2I7 or @2IE – size of loadables @1S7 or @1SE
When doing this calculation, it must be ensured that the size of the LL984 zone is
node-oriented and the remaining instructions are byte-oriented.
Error Message during Download of Program
There are three possible causes for an error message, which says that the user
program is too large for the PLC memory, appearing during download:
1. The memory is currently too small.
2. The loadable memory size is too small (see current chapter).
3. The zone for global data and the IEC program memory zone are not optimally
harmonized (see chapter Harmonizing the Zones for Global Data and IEC
Program Memory, page 173).
172
33002204 12/2010
PLC Memory and optimization
Harmonizing the Zones for Global Data and IEC Program Memory
Introduction
The total IEC memory space, determined by the loadable memory size, (see
Chapter Harmonizing the IEC Zone and LL984 Zone, page 171) is made up of two
zones:
z IEC Program Memory
z comprising the EFB codes,
z the program codes,
z the section data,
z the DFB specimen data,
z the block links,
z possibly data from online changes,
z possibly animation data etc.
z
Global Data
z comprising the Unlocated Variables
The zones for global data and IEC program memory can be harmonized with one
another.
33002204 12/2010
173
PLC Memory and optimization
Harmonizing the Zones for IEC Program Memory and Global Data:
Size of the IEC Program Memory Zone
You change the settings for the IEC program memory in Project →PLC
Configuration →PLC selection in the IECzone. Enter the size of the total IEC
memory and the global data, so that the IEC program memory size will be calculated
(IEC program memory size = total IEC memory - global data). This setting is only
possible when the PC and PLC are offline. If you do not use any or only a few
unlocated variables and have no or only a few block links, you can select the IEC
program memory as very large, because hardly any memory is needed for global
data.
174
33002204 12/2010
PLC Memory and optimization
Size of the Zone for Global Data
The zone for global data (unlocated variables) is calculated using the following
formula:
Zone for global data = memory size of the loadable - IEC program memory
The current content of the individual zones (EFBs, specimen data, user program
etc.) is displayed under Online →Memory statistics... →Memory statistics. This
display is only possible when the PC and PLC are online.
Error Message during Download of Program
There are three possible reasons for an error message, which says that the user
program is too large for the PLC memory, appearing while downloading the program
onto the PLC:
1. The memory is currently too small.
2. The loadable memory size is too small (see Chapter Harmonizing the IEC Zone
and LL984 Zone, page 171).
3. The zone for global data and the IEC program memory zone are not optimally
harmonized (see current chapter).
33002204 12/2010
175
PLC Memory and optimization
6.4
Memory Optimization for Quantum CPU 434 12(A)
and 534 14(A/B)
Overview
This section describes the memory optimization for the Quantum CPUs 434 12(A)
and 534 14(A/B).
What's in this Section?
This section contains the following topics:
Topic
General Information on Memory Optimization for Quantum CPU 434 12(A) and
534 14(A/B)
176
Page
177
Harmonizing IEC Zone and LL984 Zone
179
Harmonizing the Zones for Global Data and IEC Program Memory (CPU 434
12(A) / 534 14 (A/B))
184
33002204 12/2010
PLC Memory and optimization
General Information on Memory Optimization for Quantum CPU 434 12(A) and
534 14(A/B)
Logic Memory
The program memory zone, in which the user program is located, is called the logic
zone. This zone therefore determines the maximum size of your user program.
The current size of the logic zone is displayed under Project →PLC Configurator
in the configurations overview in the PLC zone. The memory size is given in nodes
for LL984 (1 node equals 11 bytes) and in kilobytes for IEC.
Optimizing the Logic Memory
You have various possibilities for optimising the logic memory to suit your
requirements:
z Harmonizing IEC Zone and LL984 Zone, page 179
z Harmonizing the Zones for Global Data and IEC Program Memory (CPU 434
12(A) / 534 14 (A/B)), page 184
NOTE: Also note the PLC-independent possibilities for memory optimization
(see page 157).
33002204 12/2010
177
PLC Memory and optimization
Structure of the CPU 434 12(A) / 534 14(A/B) memory (simplified representation):
178
33002204 12/2010
PLC Memory and optimization
Harmonizing IEC Zone and LL984 Zone
Introduction
The EXEC file "Q58Vxxxx.bin" is required for the CPU 434 12 and 534 14.
The EXEC file "Q5RVxxxx.bin" is required for the CPU 434 12A and 534 14A/B
(redesigned CPUs).
These EXEC files contain the runtime systems for IEC and LL984.
The sizes of the logic zones for IEC and LL984 should be harmonized with each
other. The size of both zones can be defined in Project →PLC Configurator →
PLC selection.
Depending on the size you select for the IEC zone, zones will be reserved in the
program memory of the PLC for IEC and/or LL984 programs. Therefore, if you
define a combined IEC and LL984 zone and then only use one of the two language
types in the user program, the program memory will not be used optimally.
Therefore, decide which languages you want to use:
z Exclusive Use of IEC, page 179
z Exclusive Use of LL984, page 180
z Joint Use of IEC and LL984, page 181
Exclusive Use of IEC
If you require exclusive use of the IEC, select in Project →PLC Configuration →
PLC Selection in the IEC Operating System list box, the entry Enable and drag
the total IEC memory slider to the right hand margin (highest value). This will
completely switch off the LL984 zone and the entire logic zone will be made
available for the IEC user program.
33002204 12/2010
179
PLC Memory and optimization
Structure of the CPU 434 12 (A)/ 534 14(A/B) memory with exclusive use of IEC:
Exclusive Use of LL984
If you require exclusive use of LL984, select from Project →PLC Configuration →
PLC Selection in the IEC Operating System list box, the Disable entry. This will
completely switch off the IEC zone and the entire logic zone will be made available
for the LL984 user program.
180
33002204 12/2010
PLC Memory and optimization
Structure of the CPU 434 12(A)/ 534 14(A/B) memory with exclusive use of LL984:
Joint Use of IEC and LL984
When using IEC and LL984 jointly, you should harmonize the sizes of both zones
with each other.
By setting the total IEC memory size and Global Data you can automatically
determine the size of the IEC program memory, and also the available space for
LL984-data (user program).
The size of the available memory for LL984 user programs is calculated using the
following formula:
LL984 zone = available LL984 nodes - total IEC memory
When performing this calculation, it must however be ensured that the size of the
LL984 zone is node-oriented and the remaining instructions are kilobyte-oriented.
33002204 12/2010
181
PLC Memory and optimization
To set the total IEC memory, select from Project →PLC Configuration →PLC
selection in the IEC Operating System list box, the Enable entry. The IEC zone is
now enabled and you can enter the required memory size in the Total IEC Memory
text box. The memory size is given in kilobytes.
The fixed total IEC memory size is again made up of several zones. You will find the
explanation of how to harmonize these zones vertically in the chapter Harmonizing
the Zones for Global Data and IEC Program Memory, page 173.
Structure of the CPU 434 12(A)/ 534 14(A/B) memory with exclusive use of IEC and
LL984:
182
33002204 12/2010
PLC Memory and optimization
Error Message during Download of Program
There are three possible causes for an error message, which says that the user
program is too large for the PLC memory, appearing during download:
1. The memory is currently too small.
2. The logic zone is too small (see current chapter).
3. The zone for global data and the IEC program memory zone are not optimally
harmonized (see chapter Harmonizing the Zones for Global Data and IEC
Program Memory (CPU 434 12(A) / 534 14 (A/B)), page 184).
33002204 12/2010
183
PLC Memory and optimization
Harmonizing the Zones for Global Data and IEC Program Memory (CPU 434 12(A)
/ 534 14 (A/B))
Introduction
The fixed total IEC memory (see chapter Harmonizing IEC Zone and LL984 Zone,
page 179) is made up of two zones.
The total IEC memory space, determined by the loadable memory size, (see
Chapter Harmonizing the IEC Zone and LL984 Zone, page 171) is made up of two
zones:
z IEC Program Memory
z comprising the EFB codes,
z the program codes,
z the section data,
z the DFB specimen data,
z the block links,
z possibly data from online changes,
z possibly animation data etc.
z
Global Data
z comprising the Unlocated Variables
The zones for global data and IEC program memory can be harmonized with one
another.
184
33002204 12/2010
PLC Memory and optimization
Harmonizing the Zones for Global Data and IEC Program Memory (CPU 434 12(A)
/ 534 14 (A/B))
Size of the IEC Program Memory Zone
You change the settings for the IEC program memory in Project →PLC
Configuration →PLC selection in the IECzone. Enter the size of the total IEC
memory and the global data, so that the IEC program memory size will be calculated
(IEC program memory size = total IEC memory - global data). This setting is only
possible when the PC and PLC are offline. If you do not use any or only a few
unlocated variables and have no or only a few block links, you can select the IEC
program memory as very large, because hardly any memory is needed for global
data.
33002204 12/2010
185
PLC Memory and optimization
Size of the Zone for Global Data
The zone for global data (unlocated variables) is calculated using the following
formula:
Zone for global data = memory size of the loadable - IEC program memory
The current content of the individual zones (EFBs, specimen data, user program
etc.) is displayed under Online →Memory statistics... →Memory statistics. This
display is only possible when the PC and PLC are online.
Error Message during Download of Program
There are three possible reasons for an error message, which says that the user
program is too large for the PLC memory, appearing while downloading the program
onto the PLC:
1. The memory is currently too small.
2. The total IEC memory size is too small (see Chapter Harmonizing IEC Zone and
LL984 Zone, page 179).
3. The zone for global data and the IEC program memory zone are not optimally
harmonized (see current chapter).
186
33002204 12/2010
PLC Memory and optimization
6.5
Memory optimization for Compact CPUs
Overview
This Section describes the memory optimization for Compact CPUs.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
General Information on Memory Optimization for Compact CPUs
188
Harmonizing IEC Zone and LL984 Zone
190
Harmonizing the Zones for Global Data and IEC Program Memory (Compact)
194
187
PLC Memory and optimization
General Information on Memory Optimization for Compact CPUs
Logic Memory
The program memory zone, in which the user program is located, is called the logic
zone. This zone therefore determines the maximum size of your user program.
The current size of the logic zone is displayed under Project →PLC Configuration
in the configurations overview in the PLC zone. The entry for the memory size is
given in Nodes for LL984 (1 node equals 11 bytes) and in kilobytes for IEC.
Optimizing the Logic Memory
You have various possibilities for optimising the logic memory to suit your
requirements:
z Harmonizing IEC Zone and LL984 Zone, page 190
z Harmonizing the Zones for Global Data and IEC Program Memory (Compact),
page 194
NOTE: Also note the PLC-independent possibilities for memory optimization
(see page 157).
188
33002204 12/2010
PLC Memory and optimization
Structure of a Compact CPU memory (simplified representation)
33002204 12/2010
189
PLC Memory and optimization
Harmonizing IEC Zone and LL984 Zone
Introduction
The IEC zone "CTSXxxxx.bin", required for Compact CPUs, contains the runtime
systems for IEC and LL984 (see also Installation instructions).
The sizes of the logic zones for IEC and LL984 should be harmonized with each
other. You can define the size of both zones in Project →PLC Configurator →
PLC Selection.
Depending on the size you select for the IEC zone, zones will be reserved in the
program memory of the PLC for IEC and/or LL984 programs. Therefore, if you
define a combined IEC and LL984 zone and then only use one of the two language
types in the user program, the program memory will not be used optimally.
Therefore, decide which languages you want to use:
Exclusive Use of IEC, page 190
z Exclusive Use of LL984, page 191
z Joint Use of IEC and LL984, page 192
z
Exclusive Use of IEC
If you require exclusive use of the IEC, select in Project →PLC Configuration →
PLC Selection in the IEC Operating System list box, the entry Enable and drag
the total IEC memory slider to the right hand margin (highest value). This will
completely switch off the LL984 zone and the entire logic zone will be made
available for the IEC user program.
190
33002204 12/2010
PLC Memory and optimization
Structure of the Compact CPU memory with exclusive use of IEC
Exclusive Use of LL984
If you require exclusive use of LL984, select from Project →PLC Configuration →
PLC Selection in the IEC Operating System list box, the Disable entry. This will
completely switch off the IEC zone and the entire logic zone will be made available
for the LL984 user program.
33002204 12/2010
191
PLC Memory and optimization
Structure of the Compact CPU memory with exclusive use of LL984
Joint Use of IEC and LL984
When using IEC and LL984 jointly, you should harmonize the sizes of both zones
with each other.
By setting the total IEC memory size and Global Data you can automatically
determine the size of the IEC program memory, and also the available space for
LL984-data (user program).
The size of the available memory for LL984 user programs is calculated using the
following formula:
LL984 zone = available LL984 nodes - total IEC memory
When performing this calculation, it must however be ensured that the size of the
LL984 zone is node-oriented and the remaining instructions are kilobyte-oriented.
To set the total IEC memory, select from Project →PLC Configuration →PLC
selection in the IEC Operating System list box, the Enable entry. The IEC zone is
now enabled and you can enter the required memory size in the Total IEC Memory
text box. The memory size is given in kilobytes.
192
33002204 12/2010
PLC Memory and optimization
The fixed total IEC memory size is again made up of several zones. You will find the
explanation of how to harmonize these zones vertically in the chapter Harmonizing
the Zones for Global Data and IEC Program Memory (Compact), page 194.
Structure of the Compact Memory with joint use of IEC and LL984:
Error Message during Download of Program
There are three possible causes for an error message, which says that the user
program is too large for the PLC memory, appearing during download:
1. The memory is currently too small.
2. The logic zone is too small (see current chapter).
3. The zone for global data and the IEC program memory zone are not optimally
harmonized (see chapter Harmonizing the Zones for Global Data and IEC
Program Memory (Compact), page 194).
33002204 12/2010
193
PLC Memory and optimization
Harmonizing the Zones for Global Data and IEC Program Memory (Compact)
Introduction
The fixed total IEC memory (see chapter Harmonizing IEC Zone and LL984 Zone,
page 190) is made up of two zones.
z IEC Program Memory
z comprising the EFB codes,
z the program codes,
z the section data,
z the DFB specimen data,
z the block links,
z possibly data from online changes,
z possibly animation data etc.
z
Global Data
z comprising the Unlocated Variables
The zones for global data and IEC program memory can be harmonized with one
another.
194
33002204 12/2010
PLC Memory and optimization
Harmonizing the Zones for Global Data and IEC Program Memory (Compact):
Size of the IEC Program Memory Zone
You change the settings for the IEC program memory in Project →PLC
Configuration →PLC selection in the IEC zone. Enter the size of the total IEC
memory and the global data, so that the IEC program memory size will be calculated
(IEC program memory size = total IEC memory - global data). This setting is only
possible when the PC and PLC are offline. If you do not use any or only a few
unlocated variables and have no or only a few block links, you can select the IEC
program memory as very large, because hardly any memory is needed for global
data.
33002204 12/2010
195
PLC Memory and optimization
Size of the Zone for Global Data
The zone for global data (unlocated variables) is calculated using the following
formula:
Zone for global data = memory size of the loadable - IEC program memory
The current content of the individual zones (EFBs, specimen data, user program
etc.) is displayed under Online →Memory statistics... →Memory statistics. This
display is only possible when the PC and PLC are online.
Error Message during Download of Program
There are three possible reasons for an error message, which says that the user
program is too large for the PLC memory, appearing while downloading the program
onto the PLC:
1. The memory is currently too small.
2. The total IEC memory size is too small (see Chapter Harmonizing IEC Zone and
LL984 Zone, page 190).
3. The zone for global data and the IEC program memory zone are not optimally
harmonized (see current chapter).
196
33002204 12/2010
PLC Memory and optimization
6.6
Memory optimization for Momentum CPUs
Overview
This Section describes the memory optimization for Momentum CPUs.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
General Information on Memory Optimization for Momentum CPUs
198
Selecting Optimal EXEC file
200
Harmonizing the Zones for Global Data and IEC Program Memory
(Momentum)
201
197
PLC Memory and optimization
General Information on Memory Optimization for Momentum CPUs
Logic Memory
The program memory zone, in which the user program is located, is called the logic
zone. This zone therefore determines the maximum size of your user program.
The current size of the logic zone is displayed under Project →PLC Configuration
in the configurations overview in the PLC zone. The entry for the memory size is
given in Nodes for LL984 (1 node equals 11 bytes) and in kilobytes for IEC.
Optimizing the Logic Memory
You have various possibilities for optimising the logic memory to suit your
requirements:
z Selecting Optimal EXEC file, page 200
z Harmonizing the Zones for Global Data and IEC Program Memory (Momentum),
page 201
NOTE: Also note the PLC-independent possibilities for memory optimization
(see page 157).
198
33002204 12/2010
PLC Memory and optimization
Structure of a Momentum CPU memory (simplified representation):
33002204 12/2010
199
PLC Memory and optimization
Selecting Optimal EXEC file
Introduction
It is not possible to use IEC and LL984 jointly in Momentum.
Using IEC
EXEC file assignment during IEC use:
171 CBB
M1IVxxxE
MPSV100e.BI
N
970 30
-
x
171 CCS
M1IVxxxE
M1EVxxxE
760 00
x
-
760 10
x
-
780 10
x
-
960 30
-
x
980 30
-
x
Using LL984
EXEC file assignment during LL984 use:
200
171 CBB
M1LLVxxx
M1MVxxxE
970 30
x
-
171 CCS
M1LLVxxx
M1EVxxx
700 10
x
-
700/780 00
x
-
760 00
x
-
760 10
x
-
780 10
x
-
960 20
-
x
960 30
-
x
980 20
-
x
980 30
-
x
33002204 12/2010
PLC Memory and optimization
Harmonizing the Zones for Global Data and IEC Program Memory (Momentum)
Introduction
The logic zone for the total IEC memory is made up of two zones.
z IEC Program Memory
z comprising the EFB codes,
z the program codes,
z the section data,
z the DFB specimen data,
z the block links,
z possibly data from online changes,
z possibly animation data etc.
z
Global Data
z comprising the Unlocated Variables
The zones for global data and IEC program memory can be harmonized with one
another.
33002204 12/2010
201
PLC Memory and optimization
Harmonizing the Zones for Global data and IEC Program Memory (Momentum 171
CCS 760 00-IEC):
Size of the IEC Program Memory Zone
The settings for the IEC user program zone are available in Online →Memory
statistics... →Memory statistics in the Configured text box. This setting is only
possible when the PC and PLC are offline. If you do not use any or only a few
unlocated variables and have no or only a few block links, you can select the IEC
program memory as very large, because hardly any memory is needed for global
data.
202
33002204 12/2010
PLC Memory and optimization
Size of the Zone for Global Data
The zone for global data (unlocated variables and block links) is calculated using the
following formula:
Zone for global data = memory size of the loadable - IEC program memory
The current content of the individual zones (EFBs, specimen data, user program
etc.) is displayed under Online →Memory statistics... →Memory statistics. This
display is only possible when the PC and PLC are online.
Error Message during Download of Program
There are two possible reasons for an error message, saying that the user program
is too large for the PLC memory, appearing while downloading the program onto the
PLC:
1. The memory is currently too small.
2. The zone for global data and the IEC program memory zone are not optimally
harmonized (see current chapter).
33002204 12/2010
203
PLC Memory and optimization
6.7
Memory optimization for Atrium CPUs
Overview
This Section describes the memory optimization for Atrium CPUs.
What's in this Section?
This section contains the following topics:
Topic
204
Page
General Information on Memory Optimization for Atrium CPUs
205
Use of IEC
207
Harmonizing the Zones for Global Data and IEC Program Memory (Atrium)
209
33002204 12/2010
PLC Memory and optimization
General Information on Memory Optimization for Atrium CPUs
Logic Memory
The program memory zone, in which the user program is located, is called the logic
zone. This zone therefore determines the maximum size of your user program.
The current size of the logic zone is displayed under Project →PLC Configurator
in the configurations overview in the PLC zone. The memory size is given in
kilobytes for IEC.
Optimizing the Logic Memory
You have various possibilities for optimising the logic memory to suit your
requirements:
z Use of IEC, page 207
z Harmonizing the Zones for Global Data and IEC Program Memory (Atrium),
page 209
NOTE: Also note the PLC-independent possibilities for memory optimization
(see page 157).
33002204 12/2010
205
PLC Memory and optimization
Structure of the Atrium CPU Memory (simplified representation):
206
33002204 12/2010
PLC Memory and optimization
Use of IEC
Introduction
The EXEC files required for the CPUs of the Atrium family contain the operating
systems for IEC (see also Installation Instructions).
When using the Atrium 180 CCO 121 01, load the EXEC file "AI3Vxxxx.bin".
When using the Atrium 180 CCO 241 01and 180 CCO 241 11 load the EXEC file
"AI5Vxxxx.bin".
Select in Project →PLC Configuration →PLC Selection in the IEC Operating
System list box, the entry Enable and drag the total IEC memory slider to the right
hand margin (highest value). This will completely switch off the LL984 zone and the
entire logic zone will be made available for the IEC user program.
Structure of the Atrium CPU memory with exclusive use of IEC:
33002204 12/2010
207
PLC Memory and optimization
Error Message during Download of Program
There are three possible causes for an error message, which says that the user
program is too large for the PLC memory, appearing during download:
1. The memory is currently too small.
2. The logic zone is too small (see current chapter).
3. The zone for global data and the IEC program memory zone are not optimally
harmonized (see chapter Harmonizing the Zones for Global Data and IEC
Program Memory (Atrium), page 209).
208
33002204 12/2010
PLC Memory and optimization
Harmonizing the Zones for Global Data and IEC Program Memory (Atrium)
Introduction
The fixed total IEC memory (see chapter Use of IEC, page 207) is made up of two
zones.
z IEC Program Memory
z comprising the EFB codes,
z the program codes,
z the section data,
z the DFB specimen data,
z the block links,
z possibly data from online changes,
z possibly animation data etc.
z
Global Data
z comprising the Unlocated Variables
The zones for global data and IEC program memory can be harmonized with one
another.
33002204 12/2010
209
PLC Memory and optimization
Harmonizing the Zones for Global Data and IEC Program Memory (Atrium):
Size of the IEC Program Memory Zone
You change the settings for the IEC program memory in Project →PLC
Configuration →PLC selection in the IEC zone. Enter the size of the total IEC
memory and the global data, so that the IEC program memory size will be calculated
(IEC program memory size = total IEC memory - global data). This setting is only
possible when the PC and PLC are offline. If you do not use any or only a few
unlocated variables and have no or only a few block links, you can select the IEC
program memory as very large, since hardly any memory is needed for global data.
210
33002204 12/2010
PLC Memory and optimization
Size of the Zone for Global Data
The zone for global data (unlocated variables) is calculated using the following
formula:
Zone for global data = memory size of the loadable - IEC program memory
The current content of the individual zones (EFBs, specimen data, user program
etc.) is displayed under Online →Memory statistics... →Memory statistics. This
display is only possible when the PC and PLC are online.
Error Message during Download of Program
There are three possible reasons for an error message, which says that the user
program is too large for the PLC memory, appearing while downloading the program
onto the PLC:
1. The memory is currently too small.
2. The total IEC memory size is too small (see Chapter Use of IEC, page 207).
3. The zone for global data and the IEC program memory zone are not optimally
harmonized (see current chapter).
33002204 12/2010
211
PLC Memory and optimization
212
33002204 12/2010
Function Block language FBD
33002204 12/2010
Function Block language FBD
7
Overview
This Chapter describes the Function Block language FBD which conforms to IEC
1131.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
7.1
General information about FBD Function Block
7.2
FBD Function Block objects
215
7.3
Working with the FBD Function Block langauge
224
7.4
Code generation with the FBD Function Block language
232
7.5
Online functions of the FBD Function Block language
233
7.6
Creating a program with the FBD Function Block language
235
214
213
Function Block language FBD
7.1
General information about FBD Function Block
General information on Function Block language FBD
At a Glance
The objects of the programming language FBD (Function Block Diagram) help to
divide a section into a number of:
z EFBs (Elementary Functions and Elementary Function Blocks) (see page 216),
z DFBs (Derived Function Blocks) (see page 218) and
z UDEFBs (User-defined Functions and Function Blocks) (see page 219).
These objects, combined under the name FFBs, can be linked with each other by:
z Links (see page 220) or
z Current parameters (see page 221).
Expansive logic can also be placed in the FBD section in the form of macros (see
also Macros, page 521).
Theoretically, each section can contain as many FFBs and also as many inputs and
outputs as required. However, it is advisable to subdivide a whole program in logic
units, that is to say in different sections.
Comments can be provided for the logic of the section with text objects (see Text
Object, page 223).
Processing sequence
The processing sequence of the individual FFBs in an FBD section is determined by
the data flow within the section (see also FFB Execution Order, page 227).
Editing with the keyboard
Normally editing in Concept is performed with the mouse, however it is also possible
with the keyboard (see also Short Cut Keys in the FBD and SFC Editor, page 837)
IEC conformity
For a description of the IEC conformity of the FBD programming language see IEC
conformity, page 849.
214
33002204 12/2010
Function Block language FBD
7.2
FBD Function Block objects
Overview
This section describes the FBD Function Block objects.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
Functions and Function Blocks (FFBs)
216
Link
220
Actual parameters
221
Text Object
223
215
Function Block language FBD
Functions and Function Blocks (FFBs)
Introduction
FFB is the generic term for:
EFB (Elementary Function and Elementary Function Block) (see page 216)
z DFB (Derived Function Block) (see page 218)
z UDEFB (Derived Elementary Function and Derived Elementary Function Block)
(see page 219)
z
EFB
EFB is the generic term for:
z Elementary Function (see page 216)
z Elementary Function Block (see page 217)
EFBs are functions and function blocks that are available in Concept in the form of
libraries. The logic of EFBs is built in C programming language and cannot be
changed in the FBD editor.
Elementary Function
Functions have no internal conditions. If the input values are the same, the value at
the output is the same for all executions of the function. E.g. the addition of two
values gives the same result at every execution.
An Elementary Function is represented graphically as a frame with inputs and
outputs. The inputs are always represented on the left and the outputs always on the
right of the frame. The name of the function, that is the function type, is displayed in
the center of the frame. The function counter is displayed above the frame.
The function counter cannot be changed and always has an .n.m. structure.
.n = current section number
.m = current function number
Functions are only executed in FBD if the input EN=1 or if the input EN is grayed out
(see also EN and ENO, page 219).
Elementary Function
216
33002204 12/2010
Function Block language FBD
Elementary Function Block
Function blocks have internal conditions. If the inputs have the same values, the
value at the output at every execution is another value. E.g. with a counter, the value
on the output is incremented.
A function block is represented graphically as a frame with inputs and outputs. The
inputs are always represented on the left and the outputs always on the right of the
frame. The name of the function block, that is the function block type, is displayed in
the center of the frame. The instance name is displayed above the frame. The
instance name serves as a unique identification for the function block in a project.
The instance name is produced automatically with the following structure: FBI_n_m
FBI = Function Block Instance
n = Section number (current number)
m = Number of the FFB object in the section (current number)
The instance name can be edited in the Object →Properties dialog box of the
function block. The instance name must be unique throughout the whole project and
is not case sensitive. If the name entered already exists, you will be warned and you
will have to choose another name. The instance name must correspond to the IEC
name conventions, otherwise an error message occurs.
NOTE: In compliance with IEC1131-3 only letters are permitted as the first character
of instance names. Should numbers be required as the first character however, the
menu command Options →Preferences →IEC Extensions... →Permit Leading
Figures in Identifiers will enable this.
Function blocks are only executed in FBD if the input EN=1 or if the input EN is
grayed out (related topics EN and ENO, page 219).
Elementary Function Block
33002204 12/2010
217
Function Block language FBD
DFB
Derived Function Blocks (DFBs) are function blocks that have been defined in
Concept DFB.
With DFBs, there is no distinction between functions and function blocks. They are
always treated as function blocks regardless of their internal structure.
A DFB is represented graphically as a frame with double vertical lines and with
inputs and outputs. The inputs are always represented on the left and the outputs
always on the right of the frame. The DFB name is displayed centrally within the
frame. The instance name is displayed above the frame. The instance name serves
as a unique identification for the function block in a project.
The instance name is produced automatically with the following structure: FBI_n_m
FBI = Function Block Instance
n = Section number (current number)
m = Number of the FFB object in the section (current number)
The instance name can be edited in the Object →Properties dialog box of the DFB.
The instance name must be unique throughout the whole project and is not case
sensitive. If the name entered already exists, you will be warned and you will have
to choose another name. The instance name must correspond to the IEC name
conventions, otherwise an error message occurs.
NOTE: In compliance with IEC1131-3 only letters are permitted as the first character
of instance names. Should numbers be required as the first character however, the
menu command Options →Preferences →IEC Extensions... →Permit Leading
Figures in Identifiers will enable this.
Derived function blocks are only executed in FBD if the input EN=1 or if the input EN
is grayed out (related topics EN and ENO, page 219).
Derived Function Block
218
33002204 12/2010
Function Block language FBD
UDEFB
UDEFB is the generic term for:
z User-defined Elementary Function
z User-defined Elementary Function Block
UDEFBs are functions and function blocks that have been programmed with
Concept EFB in C++ programming language and are available in Concept in the
form of libraries.
In Concept, there is no functional difference between UDEFBs and EFBs.
EN and ENO
With all FFBs, an EN input and an ENO output can be configured.
The configuration of EN and ENO is switched on or off in the FFB Properties dialog
box. The dialog box can be called up with the Objects →Properties... menu
command or by double-clicking on the FFB.
If the value of EN is equal to "0" when the FFB is invoked, the algorithms that are
defined by the FFB will not be executed and all outputs keep their previous values.
The value of ENO is automatically set to "0" in this case.
If the value of EN is equal to "1", when the FFB is called up, the algorithms which
are defined by the FFD will be executed. After successful execution of these
algorithms, the value of ENO is automatically set to "1". If an error occurs during
execution of these algorithms, ENO will be set to "0".
The output behavior of the FFBs in FBD does not depend on whether the FFBs are
called up without EN/ENO or with EN=1.
33002204 12/2010
219
Function Block language FBD
Link
Description
Links are connections between FFBs.
Several links can be connected with one FFB output. The link points are identified
by a filled-in circle.
Data Types
The data types of the inputs/outputs to be linked must be the same.
Creating Links
Links can be created using Objects →Link.
Editing Links
Links can be edited in select mode. An overlap with other objects is permitted.
Configuring Loops
No loop can be configured with links because in this case, the execution order in the
section cannot be determined uniquely. Loops must be resolved with actual
parameters (see Configuring Loops, page 230).
220
33002204 12/2010
Function Block language FBD
Actual parameters
At a Glance
In the program runtime, the values from the process or from other actual parameters
are transferred to the FFB over the actual parameters and then re-emitted after
processing.
These actual parameters can be:
direct addresses (see page 67)
z Located variables (see page 64)
z Unlocated variable (see page 64)
z Constants (see page 66)
z Literals (see page 66)
z
Direct addresses
The information on/display of direct addresses can be given in various formats. The
display format is set in the dialog box Options →Presettings →Joint. Setting the
display format has no impact on the entry format, i.e. direct addresses can be
entered in any format.
The following address formats are possible:
z Standard format (400001)
The five-character address comes directly after the first digit (the Reference).
z Separator format (4:00001)
The first digit (the Reference) is separated from the following five-character
address by a colon (:).
z Compact format (4:1)
The first digit (the Reference) is separated from the following address by a colon
(:), and the leading zeros of the address are not given.
z IEC format (QW1)
In first place, there is an IEC identifier, followed by the five-character address.
z %0x12345 = %Q12345
z %1x12345 = %I12345
z %3x12345 = %IW12345
z %4x12345 = %QW12345
Data types
The data type of the actual parameter must match the data type of the input/output.
The only exceptions are generic inputs/outputs, of which the data type is determined
by the formal parameter. If all actual parameters consist of literals, a suitable data
type is selected for the Function Block.
33002204 12/2010
221
Function Block language FBD
Initial values
FFBs, which use actual parameters on the inputs that have not yet received any
value assignment, work with the initial values of these actual parameters.
Unconnected inputs
NOTE: Unconnected FFB inputs are specified as "0" by default.
222
33002204 12/2010
Function Block language FBD
Text Object
At a Glance
Text can be positioned in the form of text objects using FBD Function Block
language. The size of these text objects depends on the length of the text. The size
of the object, depending on the size of the text, can be extended vertically and
horizontally to fill further grid units. Text objects may not overlap with FFBs; however
they can overlap with links.
Memory space
Text objects occupy no memory space on the PLC because the text is not
downloaded onto the PLC.
33002204 12/2010
223
Function Block language FBD
7.3
Working with the FBD Function Block langauge
Overview
This section describes working with the FBD Function Block object language..
What's in this Section?
This section contains the following topics:
Topic
224
Page
Positioning Functions and Function Blocks
225
FFB Execution Order
227
Configuring Loops
230
33002204 12/2010
Function Block language FBD
Positioning Functions and Function Blocks
Selecting FFBs
Using Objects →Select FFB... you can open a dialog for selecting FFBs. This
dialog is modeless, that is, it is not automatically closed once an FFB is positioned,
but remains open until you close it. If you have several FBD sections open, and
invoke the dialog, only one dialog box is opened that is available for all sections. The
dialog box is not available for any other sections (non-FBD editor). If the FBD
sections are changed into icons (minimize window), the dialog box is closed. If one
of the FBD section icons is called up again, the dialog box is automatically reopened.
The first time Concept is started the FFB is displayed oriented to the library. This
means that, when selecting an FFB, the Library command button must first of all be
used to select the corresponding library. Then you can select the corresponding
Group in the list box. Now, you can select the required FFB from the EFB type list.
If you do not know which library/group the FFB required is in, you can invoke an
FFB-oriented dialog with the Sorted by FFB command button. This contains all
FFBs of all libraries and groups in an alphabetical list.
After each subsequent project start, the view you selected appears.
Once the FFB has been selected, its position in the section must be selected. The
cursor becomes a small FFB and the cross shows the position (upper left corner of
the FFB) where the FFB is positioned. The FFB is positioned by clicking on the lefthand mouse button.
Positioning FFBs (Functions and Function Blocks)
In the FBD function block language editor, the window appears with a logic grid.
FFBs (see page 216) are aligned in this grid as they are positioned. If FFBs are
positioned outside of the section frame or if there is overlapping with another FFB,
an error warning will appear and the FFB will not be positioned. Actual parameters
may overlap another object when being positioned at an FFB input/output, but they
must not go outside the limits of the section frame. If a link to another FFB is
established, this link is checked. If this link is not permitted, a message is received,
and the link is not established. When links are created, overlaps and crossing with
other links and FFBs are permitted. If an FFB is selected, the comment relating to it
is displayed in the first column of the status line. If an actual parameter is selected,
its name and, if applicable, its direct address, its I/O map and its comment are
displayed in the first column of the status line.
33002204 12/2010
225
Function Block language FBD
Change FFB Type
With the Objects →Replace FFBs... menu command the FFBs already positioned
in the section can be replaced with FFBs of another type (e.g. an AND with an OR).
The variables given to the FFB remain if the data type and position of the
inputs/outputs are the same as the "old" and the new FFB.
NOTE: FFBs with inputs / outputs of the ANY data type (generic FFBs) cannot be
replaced.
226
33002204 12/2010
Function Block language FBD
FFB Execution Order
Introduction
The execution order is first determined by the order when positioning the FFB. If the
FFBs are then linked graphically, the execution order is determined by the data flow.
Display FFB Execution Order.
The execution order can also be displayed with the Objects →FFB Execution
Order menu command. This is represented by the execution number (number in
brackets behind the instance name or function counter).
Show execution order of the FFBs
33002204 12/2010
227
Function Block language FBD
Change FFB Execution Order
The execution order can be specifically changed afterwards with the menu
command Objects →Change FFB Execution Order, but only if the rules regarding
data flow are not broken.
Changing the execution order of two networks which are in one loop
This change can only be made when the two FFBs are linked by the feedback
variable of the loop.
Step 1: Select the two FFBs.
Step 2: Press the menu command Change FFB-execution sequence.
Result: The execution sequence has changed as follows:
228
33002204 12/2010
Function Block language FBD
Changing the execution order of FFBs which are executed according to the positioning order
The change operation permits the creation of a different, desired order (sometimes
step by step if several FFBs are involved).
Result: The execution sequence has changed as follows:
33002204 12/2010
229
Function Block language FBD
Configuring Loops
Non-permitted Loops
Configuring loops exclusively via links is not permitted, as it is not possible to
uniquely set the data flow (the output of one FFB is the input of the next FFB, and
the output of this one is the input of the first).
Non-permitted Loops via Links
Resolution using an Actual Parameter
This type of logic must be resolved using actual parameters so that the data flow can
be determined uniquely.
Resolved loop using an actual parameter: Variant 1
Resolved loop using an actual parameter: Variant 2
230
33002204 12/2010
Function Block language FBD
Resolution using Several Actual Parameters
Loops using several actual parameters are also allowed. With such loops, the
execution order can later be influenced by executing – possibly several times – the
menu command Objects →Reverse FFB Execution Order (see also FFB
Execution Order, page 227).
Loop using several actual parameters
33002204 12/2010
231
Function Block language FBD
7.4
Code generation with the FBD Function Block
language
Code Generation Options
Introduction
Using the Project →Code Generation Options menu command, you can define
options for code generation.
Include Diagnosis Information
If the Include Diagnosis information check box is checked, additional information
for the process diagnosis (e.g. Transition Diagnosis (see page 319), diagnosis
codes for diagnosis function blocks with extended diagnosis, such as e.g. XACT,
XLOCK etc. ) will be produced during code generation. This process diagnosis can
be evaluated with MonitorPro or FactoryLink, for example.
Fastest Code (Restricted Checking)
If you check the Fastest code (Restricted Checking) check box, a runtimeoptimized code is generated. This runtime optimization is achieved by realizing the
integer arithmetic (e.g. "+" or "-") using simple CPU commands instead of EFB
invocations.
CPU commands are much quicker than EFB invocations, but they do not generate
any error messages, such as, for example, arithmetic or array overflow. This option
should only be used when you have ensured that the program is free of arithmetic
errors.
If Fastest Code (Restricted Checking) was selected, the addition IN1 + 1 is solved
with the "add" CPU command. The code is now quicker than if the ADD_INT EFB
were to be invoked. However, no runtime error is generated if "IN1" is 32767. In this
case, "OUT1" would overrun from 32767 to -32768!
232
33002204 12/2010
Function Block language FBD
7.5
Online functions of the FBD Function Block
language
Online Functions
Introduction
There are two animation modes available in the FBD editor:
z Animation of binary variables and links
z Animation of selected objects
These modes are also available on display of a DFB item (command button
Refine... in the dialog box Function block: xxx).
NOTE: If the animated section is used as a transition section for SFC and the
transition (and therefore also the transition section) is not processed, the status
DISABLED appears in the animated transition section.
Animation of binary variables and links
The animation of binary variables and links is activated with the menu command
Online →Animate Booleans.
In this mode, the current signal status of binary variables, direct addresses in the 0x
and 1x range and binary links is displayed in the Editor window.
Animation of selected objects
The animation of the selected objects is activated with the menu command Online
→Animate selected.
In this mode, the current signal status of the selected links, variables, multi-element
variables and literals are displayed in the Editor window.
NOTE: If all variables/links of the section need to be animated, the whole section
can be selected with CTRL+A and then Online →Animate selected (CTRL+W) all
variables and links of the section will be animated.
If a numerical value is selected on an input/output, the name of the variable, its direct
address and I/O assignment (if available) and its comment will be displayed in the
status bar.
NOTE: The selected objects remain selected even after "Animate selected" has
been selected again, in order to keep these for a further reading, and/or to be able
to easily modify the list of objects.
33002204 12/2010
233
Function Block language FBD
Color key
There are 12 different color schemes available for animation. An overview of the
color scheme and the meaning of each color can be found in the Online help (Tip:
Search the online help for the index reference "Colors").
234
33002204 12/2010
Function Block language FBD
7.6
Creating a program with the FBD Function Block
language
Creating a Program in the FBD Function Block Language
Introduction
The following description contains an example for creating a program in the function
block language (FBD). The creation of a program in the function block language is
divided into 2 main steps:
Step
Action
1
Creating a Section (see page 235)
2
Creating the Logic (see page 236)
Creating a Section
The procedure for creating a section is as follows:
Step
1
33002204 12/2010
Action
Using the File →New Section... menu command, create a new section and
enter a section name.
Note: The section name (max. 32 characters) is not case-sensitive and must be
unique within the whole project. If the name entered already exists, you will be
warned and you will have to choose a different name. The section name must
comply with the IEC name conventions, otherwise an error message appears.
Note:In compliance with IEC1131-3 only letters are permitted as the first
character of names. However, if you wish to use numbers as the first character,
you can enable this using the Options →Preferences →IEC Extensions... →
Allow Leading Digits in Identifiers menu command.
235
Function Block language FBD
Creating the Logic
The procedure for creating the logic is as follows:
Step
236
Action
1
To insert an FFB into the section, select the Objects →Select FFB... menu
command.
Response: The FFB dialog box from the library is opened.
2
In this dialog box you can select a library and an FFB from it by using the
Library... command button. You can, however, also display the DFBs that you
created and select one of them using the DFB command button.
3
Place the selected FFB in the section.
4
When all FFBs have been placed, close the dialog box with Close.
5
Activate the selection mode with Objects →Select Mode, click on the FFB and
move the FFBs to the desired position.
6
Activate the link mode with Objects →Link and connect the FFBs.
7
Then re-activate select mode with Objects →Select Mode and double-click on
one of the unconnected inputs/outputs.
Response: The Connect FFB dialog box opens, where an actual parameter can
be allocated to the input/output.
33002204 12/2010
Function Block language FBD
Step
8
Action
Depending on the program logic you can allocate the following to the
input/output:
z Variable
z Located variable
You can allocate a hardware input/output signal to the input/output of the
FFB using a located variable.
The name of the variable is shown at the input/output in the editor window.
z Unlocated variable
You can use the unlocated variable allocated to the input/output of the
FFB as a discrete, i.e. when resolving loops, or when transferring values
between different sections.
The name of the variable is shown at the input/output in the editor window.
z Constant
You can allocate a constant to the input of the FFB. The constant can be
transferred to other sections. You determine the value of the constant in
the variable editor.
The name of the constant is shown at the input in the editor window.
z Literal
You can allocate a literal to the input, i.e. directly allocate a value to the
input/output.
The value is shown at the input in the editor window.
z Direct address
You can allocate a hardware input/output signal to the input/output using an
address.
The address is shown at the input/output in the editor window.
Note: For an example for invocation of multi element variables see Calling
Derived Data Types, page 588.
Note: Unconnected FFB inputs are specified as "0" by default.
9
33002204 12/2010
Save the FBD section with the menu command File →Save Project .
237
Function Block language FBD
238
33002204 12/2010
Ladder Diagram LD
33002204 12/2010
Ladder Diagram LD
8
Overview
This Chapter describes the Ladder Diagram LD which conforms to IEC 1131.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
8.1
General information about Ladder Diagram LD
240
8.2
Objects in Ladder Diagram LD
242
8.3
Working with the LD Ladder Diagram
257
8.4
Code generation with LD Ladder Diagram
264
8.5
Online functions with the LD Ladder Diagram
265
8.6
Creating a program withLD Ladder Diagram
267
239
Ladder Diagram LD
8.1
General information about Ladder Diagram LD
General Information about the LD Ladder Diagram Language
Introduction
This section describes the Ladder Diagram (LD) according to IEC 1131-3.
The structure of a LD section corresponds to a rung for relay switching. The window
in the LD editor is shaded with a logic grid, on the left side of which there is the socalled left power rail. This left power rail corresponds to the phase (L ladder) of a
rung. With LD programming, in the same way as in a rung, only the LD objects
(contacts, coils) which are linked to a power supply, that is to say connected with the
left power rail, are "processed". The right power rail, which corresponds to the
neutral ladder, is not shown optically. However, all coils and FFB outputs are linked
with it internally and this creates a power flow.
Objects
The objects of the programming language LD (Ladder Diagram) help to divide a
section into a number of:
z Contacts (see page 243),
z Coils (see page 245) and
z FFBs (Functions and Function Blocks) (see page 248).
These objects can be linked with each other through:
z Links (see page 253) or
z Actual Parameters (see page 254).
Expansive logic can also be positioned in the LD section in the form of macros
(related topics Macros, page 521).
Theoretically, each section can contain as many FFBs and also as many inputs and
outputs as required. It is therefore advisable to subdivide a whole program into
logical units, that is to say into different sections.
Comments can be provided for the logic of the section with text objects (related
topics Text object, page 256).
Processing Sequence
Basically, LD sections are processed from top to bottom and from left to right.
Networks connected to the left power rail are processed from top to bottom.
The processing sequence of objects (contacts, coils, FFBs) is determined by the
data flow within a network.
A detailed description can be found under Execution sequence, page 260).
240
33002204 12/2010
Ladder Diagram LD
Editing with the Keyboard
Normally editing in Concept is performed with the mouse, however it is also possible
with the keyboard (related topics Shortcut keys in the LD-Editor, page 841).
In order to make editing with the keyboard easier, you can specify the number of
columns per section in the CONCEPT.INI (see page 1114) file, after which an
automatic carriage return should appear when you are expanding a rung. This
means that when you reach the last column, the next object is automatically placed
in the second column of the next row. Objects on different rows are automatically
linked, i.e. the objects are generated within a common rung.
IEC Conformity
For a description of the IEC conformity of the LD programming language see IEC
conformity, page 849.
33002204 12/2010
241
Ladder Diagram LD
8.2
Objects in Ladder Diagram LD
Overview
This section describes the objects in LD Ladder Diagram.
What's in this Section?
This section contains the following topics:
Topic
242
Page
Contacts
243
Coils
245
Functions and Function Blocks (FFBs)
248
Link
253
Actual Parameters
254
Text object
256
33002204 12/2010
Ladder Diagram LD
Contacts
At a Glance
A contact is an LD element that transfers a status on the horizontal link to its right
side. This status comes from the boolean AND link of the status of the horizontal link
on the left side, with the status of the relevant variable/direct address.
A contact does not change the value of the relevant variable/direct address.
The following contacts are available:
z Closer (see page 243)
z Opener (see page 243)
z Contact for detection of positive transitions (see page 243)
z Contact for detection of negative transitions (see page 244)
Closer
On closing, the status of the left link is copied onto the right link, if the status of the
relevant boolean variable is ON. Otherwise, the status of the right link is OFF.
Closer
Opener
On opening, the status of the left link is copied onto the right link, if the status of the
relevant boolean variable is OFF. Otherwise, the status of the right link is OFF.
Opener
Contact for detection of positive transitions
With contacts for detection of positive transitions, the right link for a program cycle
is ON if a transfer of the relevant boolean variable is made from OFF to ON and the
status of the left link is ON at the same time. Otherwise, the status of the right link is
OFF.
Contact for detection of positive transitions
33002204 12/2010
243
Ladder Diagram LD
Contact for detection of negative transitions
With contacts for detection of negative transitions, the right link for a program cycle
is ON if a transfer of the relevant boolean variable is made from ON to OFF and the
status of the left link is ON at the same time. Otherwise, the status of the right link is
OFF.
Contact for detection of negative transitions
244
33002204 12/2010
Ladder Diagram LD
Coils
At a Glance
A coil is an LD element which transfers the status of the horizontal link on the left
side, unchanged, to the horizontal link on the right side. The status is saved in the
relevant variable/direct address.
Start behavior of coils
In the start behavior of PLCs there is a distinction between cold starts and warm
starts:
z Cold start
Following a cold start (load the program with Load online →Load) all variables
(independent of type) are set to "0" or, if available, their initial value.
z Warm start
In a warm start (stop and start the program or Online → changes) different start
behaviors are valid for located variables/direct addresses and unlocated
variables:
z Located variables/direct addresses
In a warm start all coils (0x registers) are set to "0" or, if available, their initial
value.
z Unlocated variable
In a warm start all unlocated variables retain their current value (storing
behavior).
This different behavior in a warm start leads to particular characteristics in the warm
start behavior of LD objects "Coil – set" and "Coil – reset". Warm start behavior is
dependent on the variable type used (storing behavior in use of unlocated variables;
non storing behavior in use of located variables/direct addresses)
If a buffered coil is required with a located variable or with direct addresses, the RS
or SR Function Block from the IEC block library should be used.
Available coils
The following coils are available:
z Coil (see page 246)
z Coil - negated (see page 246)
z Coil - set (see page 247)
z Coil - reset (see page 247)
z Coil – positive edge (see page 246)
z Coil – negative edge (see page 246)
33002204 12/2010
245
Ladder Diagram LD
Coil
With coils, the status of the left link is copied onto the relevant Boolean variable and
the right link.
Normally, coils follow contacts or EFBs, but they can also be followed by contacts.
Coil
Coil - negated
With negated coils, the status of the left link is copied onto the right link. The inverted
status of the left link is copied onto the relevant Boolean variable. If the left link is
OFF, then the right link will also be OFF and the relevant variable will be ON.
Coil - negated
Coil – positive edge
With coils for detection of positive transfers, the status of the left link is copied onto
the right link. The relevant Boolean variable is ON for a program cycle, if a transfer
of the left link from OFF to ON is made.
Coil – positive edge
Coil – negative edge
With coils for detection of negative transfers, the status of the left link is copied onto
the right link. The relevant Boolean variable is ON for a program cycle, if a transfer
of the left link from ON to OFF is made.
Coil – negative edge
246
33002204 12/2010
Ladder Diagram LD
Coil - set
With "set coils", the status of the left link is copied onto the right link. The relevant
Boolean variable is set to ON status, if the left link is in ON status, otherwise it
remains unchanged. The relevant Boolean variable can only be reset through the
"reset coil".
Coil - set
Coil - reset
With "reset coils", the status of the left link is copied onto the right link. The relevant
Boolean variable is set to OFF status, if the left link is in ON status, otherwise it
remains unchanged. The relevant Boolean variable can only be set through the "set
coil".
Coil - reset
33002204 12/2010
247
Ladder Diagram LD
Functions and Function Blocks (FFBs)
Introduction
FFB is the generic term for:
EFB (Elementary Function and Elementary Function Block) (see page 248)
z DFB (Derived Function Block) (see page 250)
z UDEFB (Derived Elementary Function and Derived Elementary Function Block)
(see page 251)
z
EFB
EFB is the generic term for:
z Elementary Function (see page 248)
z Elementary Function Block (see page 249)
EFBs are functions and function blocks that are available in Concept in the form of
libraries. The logic of EFBs is built in C programming language and cannot be
changed in the FBD editor.
NOTE: The EFBs AND_BOOL, NOT_BOOL, OR_BOOL, R_TRIG and F_TRIG are
not available in LD. Their function is executed with contacts. The MOVE function
cannot be used with the data type BOOL.
Elementary Function
Functions have no internal conditions. If the input values are the same, the value at
the output is the same for all executions of the function. E.g. the addition of two
values gives the same result at every execution.
An Elementary Function is represented graphically as a frame with inputs and
outputs. The inputs are always represented on the left and the outputs always on the
right of the frame. The name of the function, that is the function type, is displayed in
the center of the frame. The function counter is displayed above the frame.
The function counter cannot be changed and always has an .n.m. structure.
.n = current section number
.m = current function number
Functions are only executed if the input EN=1 or if the input EN is grayed out (see
also EN and ENO, page 252).
248
33002204 12/2010
Ladder Diagram LD
Elementary Function
Elementary Function Block
Function Blocks have internal conditions. If the inputs have the same values, the
value at the output at every execution is another value. E.g. with a counter, the value
on the output is incremented.
A function block is represented graphically as a frame with inputs and outputs. The
inputs are always represented on the left and the outputs always on the right of the
frame. The name of the function block, that is the function block type, is displayed in
the center of the frame. The instance name is displayed above the frame. The
instance name serves as a unique identification for the function block in a project.
The instance name is produced automatically with the following structure: FBI_n_m
FBI = Function Block Instance
n = Section number (current number)
m = Number of the FFB object in the section (current number)
The instance name can be edited in the Properties dialog box of the function block.
The instance name must be unique throughout the whole project and is not case
sensitive. If the name entered already exists, you will be warned and you will have
to choose another name. The instance name must comply with the IEC name
conventions otherwise an error message appears.
NOTE: In compliance with IEC1131-3 only letters are permitted as the first character
of instance names. Should numbers be required as the first character however, the
Options →Preferences →IEC Extensions... →Permit Leading Figures in
Identifiers menu command will enable this.
Function blocks are only executed if the input EN=1 or if the input EN is grayed out
(see also EN and ENO, page 252).
33002204 12/2010
249
Ladder Diagram LD
Elementary Function Block
DFB
Derived Function Blocks are function blocks that have been defined in Concept
DFB.
With DFBs, there is no distinction between functions and function blocks. They are
always treated as function blocks regardless of their internal structure.
A DFB is represented graphically as a frame with double vertical lines and with
inputs and outputs. The inputs are always represented on the left and the outputs
always on the right of the frame. The DFB name is displayed centrally within the
frame. The instance name is displayed above the frame. The instance name serves
as a unique identification for the function block in a project.
The instance name is produced automatically with the following structure: FBI_n_m
FBI = Function Block Instance
n = Section number (current number)
m = Number of the FFB object in the section (current number)
The instance name can be edited in the Properties dialog box of the DFB. The
instance name must be unique throughout the whole project and is not case
sensitive. If the name entered already exists, you will be warned and you will have
to choose another name. The instance name must comply with the IEC name
conventions otherwise an error message appears.
NOTE: In compliance with IEC1131-3 only letters are permitted as the first character
of instance names. Should numbers be required as the first character however, the
Options →Preferences →IEC Extensions... →Permit Leading Figures in
Identifiers menu command will enable this.
Derived Function Blocks are only executed if the input EN=1 or if the input EN is
grayed out (see also EN and ENO, page 252).
250
33002204 12/2010
Ladder Diagram LD
Derived Function Block
UDEFB
UDEFB is the generic term for:
z User-defined Elementary Function
z User-defined Elementary Function Block
UDEFBs are functions and function blocks that have been programmed with
Concept EFB in C++ programming language and are available in Concept in the
form of libraries.
In Concept, there is no functional difference between UDEFBs and EFBs.
Editing FFBs
FFBs are only edited if at least one Boolean input is linked with the left power rail. If
the FFB has no Boolean input, the EN input of the FFB must be used. If the FFB is
to be conditionally executed, the Boolean input can be pre-linked through contacts
or other FFBs.
NOTE: If the EN input is not linked with the left power rail, it must be deactivated in
the Properties dialog box, otherwise the FFB will never be edited.
NOTE: Each FFB without Boolean link to the left power rail gives rise to an error
message when downloading onto the PLC.
33002204 12/2010
251
Ladder Diagram LD
Connection to an FFB with the left power rail:
EN and ENO
With all FFBs, an EN input and an ENO output can be configured.
EN and ENO configuration is switched on or off in the FFB properties dialog box.
The dialog box can be invoked with the Objects →Properties... menu command
or by double-clicking on the FFB.
If the value of EN is equal to "0" when the FFB is invoked, the algorithms that are
defined by the FFB will not be executed and all outputs keep their previous values.
The value of ENO is automatically set to "0" in this case.
If the value of EN is equal to "1", when the FFB is invoked, the algorithms which are
defined by the FFD will be executed. After successful execution of these algorithms,
the value of ENO is automatically set to "1". If an error occurs during execution of
these algorithms, ENO will be set to "0".
NOTE: If the EN input is not linked with the left power rail, it must be deactivated in
the Properties dialog box, otherwise the FFB will never be edited.
The output behavior of the FFBs does not depend on whether the FFBs are invoked
without EN/ENO or with EN=1.
252
33002204 12/2010
Ladder Diagram LD
Link
Description
Links are connections between contacts, coils and FFBs.
Several links can be connected with one contact, one coil or one FFB output. The
link points are identified with a filled circle.
NOTE: Unconnected contacts, coils and FFB inputs are specified as "0" by default.
Data Types
The data types of the inputs/outputs to be linked must be the same.
Editing Links
Links can be edited in select mode. An overlap with other objects is permitted.
Configuring Loops
No loop can be configured with links because in this case, the execution order in the
section cannot be determined uniquely. Loops must be resolved with actual
parameters (related topics Configuring Loops, page 230).
Horizontal Links
Contacts and coils are automatically connected during positioning with a
neighboring, unconnected contact/coil that has the same vertical position. A
connection to the power rail is only established if the contact is placed nearby (also
see Defining the Contact Connection, page 1114 in the Concept INI-Filechapter). If
a coil or a contact is positioned on an existing horizontal link, the link is automatically
separated and the contact/coil is inserted. When positioned, actual parameters may
overlap another object, but they must not go outside the limits of the section frame.
If a link to another object is established, this link is checked. If this link is not
permitted, you will receive a message and the link will not be generated.
Once objects are positioned, horizontal links with directly adjacent objects are
automatically created.
Vertical Links
An exceptional link is the "vertical link". The vertical link serves as a logical OR. With
this form of the OR link, 32 inputs (contacts) and 64 outputs (coils, links) are
possible.
33002204 12/2010
253
Ladder Diagram LD
Actual Parameters
Possible Actual Parameters
In the program runtime, the values from the process or from other actual parameters
are transferred to the FFB via the actual parameters and then re-emitted after
processing.
Table of possible actual parameters
Element
Actual Parameters
Contacts
z Direct addresses (see page 67)
z Located variables (see page 64)
z Unlocated variable (see page 64)
Coils
z Direct addresses (see page 67)
z Located variables (see page 64)
z Unlocated variable (see page 64)
FFB inputs
z
z
z
z
z
FFB outputs
z Direct addresses (see page 67)
z Located variables (see page 64)
z Unlocated variable (see page 64)
Direct addresses (see page 67)
Located variables (see page 64)
Unlocated variable (see page 64)
Constant (see page 66)
Literals (see page 66)
Direct Addresses
The information on/display of direct addresses can be given in various formats. The
display format is set in the Options →Preferences →Common dialog box. Setting
the display format has no impact on the entry format, i.e. direct addresses can be
entered in any format.
The following address formats are possible:
Standard Format (400001)
The five figure address comes directly after the first digit (the reference).
z Separator Format (4:00001)
The first digit (the reference) is separated from the five figure address that follows
by a colon (:).
z Compact format (4:1)
The first digit (the Reference) is separated from the address that follows by a
colon (:) where the leading zeros are not specified.
z
254
33002204 12/2010
Ladder Diagram LD
z
IEC Format (QW1)
There is an IEC type designation in initial position, followed by the five-character
address.
z %0x12345 = %Q12345
z %1x12345 = %I12345
z %3x12345 = %IW12345
z %4x12345 = %QW12345
Data Types
The data type of the actual parameter must be of BOOL type with contacts and coils.
With FFB inputs/outputs, the data type of the actual parameter must match the data
type of the inputs/outputs. The only exceptions are generic FFB inputs/outputs,
whose data type is determined by the formal parameter. If all actual parameters
consist of literals, a suitable data type is selected for the function block.
Initial Values
FFBs, which use actual parameters on the inputs and coils that have not yet
received a value assignment, work with the initial values of these actual parameters.
Unconnected Inputs
NOTE: Unconnected contacts, coils and FFB inputs/outputs are specified as "0" by
default.
33002204 12/2010
255
Ladder Diagram LD
Text object
At a Glance
Text can be positioned in the form of text objects in the Ladder Diagram (LD). The
size of these text objects depends on the length of the text. The size of the object,
depending on the size of the text, can be extended vertically and horizontally to fill
further grid units. Text objects may not overlap with other objects; however they can
overlap with links.
Memory space
Text objects occupy no memory space on the PLC because the text is not
downloaded onto the PLC.
256
33002204 12/2010
Ladder Diagram LD
8.3
Working with the LD Ladder Diagram
Overview
This section describes working with LD Ladder Diagram.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
Positioning Coils, Contacts, Functions and Function Blocks
258
Execution sequence
260
Configuring Loops
262
257
Ladder Diagram LD
Positioning Coils, Contacts, Functions and Function Blocks
Positioning Objects
In the LD contact plan editor, the window has a logic grid in the background. The
objects are aligned in the bars of this grid (52 x 230 fields) during positioning. With
the exception of vertical shorts, FFBs and text fields, all elements require exactly
one grid field. Objects can only be positioned within such a field. If an object is
positioned between two fields, the object is automatically placed in the nearest field.
When objects are positioned outside the section frame with another object, an error
message occurs and the object is not positioned.
When being positioned, contacts and coils are automatically linked with a directly
adjacent, unconnected contact/coil, if the contact/ coil has the same vertical
position. A link to the power rail is therefore created even if the contact is positioned
2 fields away. If contacts or coils are positioned on existing contacts or coils, the
existing ones are replaced by the current ones (only applies to same types, i.e. when
replacing coils with coils and contacts with contacts). If a coil or a contact is
positioned on an existing horizontal short, the link is automatically separated and the
contact/coil is inserted.
When positioned, actual parameters may overlap another object, but they must not
go outside the limits of the section frame. If a link to another object is established,
this link is checked. If this link is not permitted, you will receive a message and the
link will not be generated. When producing links, overlaps and crossings with other
links and objects are permitted.
If an FFB is selected, its comment is displayed in the first column of the status line.
If an actual parameter is selected, its name and, if applicable, its direct address and
its comment are displayed in the first column of the status line.
Automatic Carriage Return
As a keyboard user, you have the possibility of determining the number of
columns/fields in the CONCEPT.INI (see page 1114) file after which an automatic
carriage return will appear during editing as soon as the last column/field is reached.
The following object is then inserted into the second column/field and linked to the
last object of the previous row. I.e. the objects are created inside the same rung.
258
33002204 12/2010
Ladder Diagram LD
Selecting FFBs
Using Objects →Select FFB... you can open a dialog for selecting FFBs. This dialog
is modeless, which means it is not automatically closed once an FFB has been
positioned, but remains open until you close it. If you have several LD sections open
and you invoke the dialog, only one dialog box is opened and is available for all
sections. The dialog box is not available for any other sections (not LD editor). If the
LD sections are changed into symbols (Minimize window), the dialog box is closed.
If one of the LD section symbols is invoked again, the dialog box is automatically reopened.
The first time Concept is started, the FFB is displayed oriented to the library. This
means that to select an FFB, the corresponding library must first be selected using
the Library command button. Then you can select the corresponding group in the
Group list box. Now, you can select the required FFB from the EFB type list box.
If you do not know which library/group the FFB required is located in, you can invoke
an FFB-oriented dialog with the FFB sorted command button. This contains all
FFBs in all libraries and groups in an alphabetical list.
After each subsequent project start, the view that you select will appear.
Once the FFB has been selected, its position in the section must be selected. The
cursor becomes a small FFB and the cross shows the position (upper left corner of
the FFB) in which the FFB is placed. The FFB is positioned by clicking on the lefthand mouse button.
Change FFB-Type
With the Objects →Replace FFBs... menu command, the FFBs already positioned
in the section can be replaced with FFBs of another type (e.g. an AND with an OR).
The variables given to the FFB remain if the data type and position of the
inputs/outputs are the same in the "old" as the new FFB.
NOTE: FFBs with inputs/outputs of the ANY data type (generic FFBs) cannot be
replaced.
Change contact/coil
Contacts and coils which are already positioned can simply be replaced. In order to
do this, select the new element and click on the one to be replaced.
33002204 12/2010
259
Ladder Diagram LD
Execution sequence
Description
The following applies to the execution sequence in LD sections:
The execution sequence of networks which are only linked by the left power rail,
is determined by the graphic position in which the networks are connected to the
left power rail.
The networks are processed from top to bottom.
See example below, Networks I-VI).
z The execution sequences of objects (contacts, coils FFBs) are determined by the
data flow within a network. This means that the coils and FFBs whose inputs have
already received value assignments will be processed first.
z Current paths that begin at outputs (Pins) from FFBs are processed according to
the vertical, graphical position of its first object (from top to bottom).
See example below, Network III):
Processing after the FFB (FBI_11_63) begins with the current path whose first
object is located at the uppermost vertical position (13) and thus follows current
path (13)->(14).
When current path (13)->(14) has been processed, processing of the next current
path (15)->(19) begins.
z If the first objects of 2 current paths that begin at outputs (pins) of FFBs, at the
same height, the first current path to be processed is that of the object that is
farther left.
See example below, Network IV): (22)->(23) then (24)->(25).
z The position of an FFB is determined by the upper left corner of the FFB.
See example below.
Network V: Upper left corner of FFB (FBI_11_76) above contact (30). Process:
(28)->(29) then (30)->(31).
Network VI: Upper left corner of FFB (FBI_11_82) same height as contact (34).
Process: (34)->(35) then (36)->(37).
z
260
33002204 12/2010
Ladder Diagram LD
Example
LD section
33002204 12/2010
261
Ladder Diagram LD
Configuring Loops
Non-permitted Loops
Configuring loops exclusively via links is not permitted, as it is not possible to make
a unique specification of the data flow (the output of one FFB is the input of the next
FFB, and the output of this one is the input of the first).
Non-permitted Loops via Links
Resolution using an Actual Parameter
This type of logic must be resolved using actual parameters so that the data flow can
be determined uniquely.
Resolved loop using an actual parameter: Variant 1
Resolved loop using an actual parameter: Variant 2
262
33002204 12/2010
Ladder Diagram LD
Resolution using Several Actual Parameters
Loops using several actual parameters are also allowed.
Loop using several actual parameters
33002204 12/2010
263
Ladder Diagram LD
8.4
Code generation with LD Ladder Diagram
Code Generation Options
Introduction
Using the Project →Code Generation Options menu command, you can define
options for code generation.
Include Diagnosis Information
If you check the Include Diagnosis Information check box, additional information
for the process diagnosis (e.g. transition diagnosis, diagnosis codes for diagnosis
function blocks with extended diagnosis, such as XACT, XLOCK etc.) will be created
during code generation. This process diagnosis can be evaluated with MonitorPro
or FactoryLink, for example.
Fastest Code (Restricted Checking)
If you check the Fastest code (Restricted Checking) check box, a runtimeoptimized code is generated. This runtime optimization is achieved by realizing the
integer arithmetic (e.g. "+" or "-") using simple CPU commands instead of EFB
invocations.
CPU commands are much quicker than EFB invocations, but they do not generate
any error messages, such as, for example, arithmetic or array overflow. This option
should only be used when you have ensured that the program is free of arithmetic
errors.
If Fastest Code (Restricted Checking) was selected, the addition IN1 + 1 is solved
with the "add" CPU command. The code is now quicker than if the ADD_INT EFB
were to be invoked. However, no runtime error is generated if "IN1" is 32767. In this
case, "OUT1" would overrun from 32767 to -32768!
264
33002204 12/2010
Ladder Diagram LD
8.5
Online functions with the LD Ladder Diagram
Online Functions
Introduction
There are two animation modes available in the LD editor:
z Animation of binary variables and links
z Animation of selected objects
These modes are also available when a DFB instance is displayed (command
button Refine... in the Function Block: xxx dialog box).
NOTE: If the animated section is used as a transition section for SFC and the
transition (and therefore also the transition section) is not processed, the status
DISABLED appears in the animated transition section.
Animation of Binary Variables and Links
The animation of binary variables and links is activated using the Online →Animate
Booleans menu command.
In this mode, the current signal status of binary variables, direct addresses in the 0x
and 1x range and binary links is displayed in the editor window.
Meaning of Colors
Color
Meaning
Contact, coil, input/output, link red
Contact, coil, input/output, link transferring
the value 0
Left power rail, contact, coil, input/output, link
green
Left power rail, contact, coil, input/output, link
transferring the value 1
Variable highlighted in beige
Variable forced
Variable highlighted in purple
Variable cyclically set
The name of the multi-element variable (e.g.
motor) highlighted in color.
In the editor, a multi-element variable (e.g.
motor) is displayed, in which one or more
elements is forced or cyclically set.
The whole element name of the multi-element In the editor, an element of a multi-element
variable (e.g. right.motor.on) is highlighted in variable (e.g. right motor on) that is forced or
cyclically set is displayed.
color.
The name of the multi-element variable (e.g.
right.motor.on) is highlighted in color, but the
name of the element is not.
33002204 12/2010
In the editor, an element of a multi-element
variable (e.g. right motor on) that is not
forced or cyclically set is displayed, but a
different element of this multi-element
variable is cyclically set or forced.
265
Ladder Diagram LD
Animation of Selected Objects
The animation of the selected objects is activated with the Online →Animate
Selection menu command.
In this mode, the current signal status of the selected links, variables, multi-element
variables and literals is displayed in the editor window.
NOTE: If you want to animate all variables/links in the section, you can select the
whole section using CTRL+A and then animate all variables and links in the section
using Online →Animate Selection (CTRL+W).
If a numerical value is selected on an input/output, the name of the variable, its direct
address and I/O mapping (if existent) and its comment will be displayed in the status
bar.
NOTE: The selected objects remain selected even after "animate selection" has
been selected again, to retain these objects for a further reading, and/or to be able
to easily modify the list of objects.
Color key
There are 12 different color schemes available for animation. An overview of the
color scheme and the meaning of each color can be found in the Online help Tip:
Search the online hlep for the index reference "Colors").
266
33002204 12/2010
Ladder Diagram LD
8.6
Creating a program withLD Ladder Diagram
Creating a Program in LD
Introduction
The following description contains an example for creating a program in Ladder
Diagram (LD). The creation of a program in LD Ladder Diagram is divided into 2
main steps:
Step
Action
1
Creating a Section (see page 267)
2
Creating the Logic (see page 268)
Creating a Section
The procedure for creating a section is as follows:
Step
1
33002204 12/2010
Action
Using the File →New Section... menu command, create a new section and
enter a section name.
Note: The section name (max. 32 characters) is not case-sensitive and must be
unique within the whole project. If the name entered already exists, you will be
warned and you will have to choose a different name. The section name must
comply with the IEC name conventions, otherwise an error message appears.
Note:In compliance with IEC1131-3 only letters are permitted as the first
character of names. However, if you wish to use numbers as the first character,
you can enable this using the Options →Preferences →IEC Extensions... →
Allow Leading Digits in Identifiers menu command.
267
Ladder Diagram LD
Creating the Logic
The procedure for creating the logic is as follows:
Step
268
Action
1
To insert a contact or coil in the section, open the Objects main menu and select
the desired contact or coil. Contacts and coils can also be selected using the tool
bar. Place the contact or coil in the section.
2
To insert an FFB into the section, select the Objects →Select FFB... menu
command.
Response: The FFBs from Library dialog box is opened.
3
In this dialog box you can select a library and an FFB from it by using the
Library... command button. You can, however, also display the DFBs that you
created and select one of them using the DFB command button.
4
Place the selected FFB in the section.
5
When all FFBs have been placed, close the dialog box with Close.
6
Activate select mode using Objects →Select Mode, and move the contacts,
coils and FFBs to the required position.
7
Activate link mode with Objects →Link, and connect the contacts, coils and
FFBs. Connect the contacts, FFBs and the left power rail.
8
Then re-activate select mode with Objects →Select mode, and double-click on
a contact or coil.
Response: The Properties: LD objects dialog box is opened, in which you
can allocate an actual parameter to the contact/coil.
33002204 12/2010
Ladder Diagram LD
Step
9
Action
Depending on the program logic you can allocate the following to the
contact/coil:
z Variable
z Located variable
You can allocate a hardware input/output signal to the input/output using
a located variable.
The name of the variable is shown at the input/output in the editor window
z Unlocated variable
You can use the unlocated variable allocated to the input/output as a
discrete, i.e. to resolve loops, or to transfer values between different
sections.
The name of the variable is shown at the input/output in the editor
window.
z Direct address
You can allocate a hardware input/output signal to the input/output using an
address.
The address is shown at the input/output in the editor window.
Note: For an example for invocation of multi-element variables see Calling
Derived Data Types, page 588.
Note: Unconnected FFB inputs are specified as "0" by default.
10
33002204 12/2010
To connect the FFB input/outputs to the actual parameters, double-click on one
of the unconnected input/outputs.
Response: The Connect FFB dialog box is opened, in which you can allocate
an actual parameter to the input/output.
269
Ladder Diagram LD
Step
11
Action
Depending on the program logic you can allocate the following to the
input/output:
z Variable
z Located variable
You can allocate a hardware input/output signal to the input/output using
a located variable.
The name of the variable is shown at the input/output in the editor window
z Unlocated variable
You can use the unlocated variable allocated to the input/output as a
discrete, i.e. to resolve loops, or to transfer values between different
sections.
The name of the variable is shown at the input/output in the editor
window.
z Constant
You can allocate a constant to the input. The constant can be transferred
to other sections. You determine the value of the constant in the variable
editor.
The name of the constant is shown at the input in the editor window.
z Literal
You can allocate a literal to the input, i.e. directly allocate a value to the
input/output.
The value is shown at the input in the editor window.
z Direct address
You can allocate a hardware input/output signal to the input/output using an
address.
The address is shown at the input/output in the editor window.
Note: For an example for invocation of multi-element variables see Calling
Derived Data Types, page 588.
Note: Unconnected FFB inputs are specified as "0" by default.
12
270
Save the LD section using the File →Save Project menu command.
33002204 12/2010
Sequence language SFC
33002204 12/2010
Sequence language SFC
9
Overview
This Chapter describes the sequence language SFC which conforms to IEC 1131.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
9.1
General information about SFC sequence language
272
9.2
SFC sequence language elements
274
9.3
Working with the SFC Sequence Language
293
9.4
Online functions of the SFC sequence language
310
271
Sequence language SFC
9.1
General information about SFC sequence
language
General information about SFC language
At a Glance
The sequence language SFC is described in this section according to IEC 1131-3.
In the SFC (Sequential Function Chart) sequence language, a section is split into
single configured sequential steps, through steps and transitions, which alternate in
the sequence plan.
Objects
A sequential control uses the following objects when creating a program:
Step (see page 275)
z Transition (see page 280)
z Jump (see page 285)
z Connection (see page 284)
z Alternative branch (see page 287)
z Simultaneous branch (see page 290)
z Alternative connection (see page 289)
z Parallel connection (see page 291)
z Text object (see page 292)
z
Structure of an SFC section
Steps and transitions are linked with one another through directional links. Two
steps can never be directly linked, and must always be separated by a transition.
The processes of the active signal status take place along the directional links,
triggered by the connecting of a transition. The direction of the string process follows
the directional links and runs from the under side of the predecessor step to the top
side of the successive step. Branches are processed from left to right.
A jump can be put in the place of a step. Step strings are always concluded with a
jump to another step on the same step string. It is run down cyclically.
Nil or more action belong to every step. Steps without action are known as waiting
steps. A condition for transition belongs to every transition.
Editing with the keyboard
Normally editing in Concept is performed with the mouse, however it is also possible
with the keyboard (see also Short Cut Keys in the FBD and SFC Editor, page 837)
272
33002204 12/2010
Sequence language SFC
IEC conformity
For a description of the IEC conformity of the SFC programming language see IEC
conformity, page 849.
33002204 12/2010
273
Sequence language SFC
9.2
SFC sequence language elements
Overview
This section describes the SFC sequence language elements.
What's in this Section?
This section contains the following topics:
Topic
274
Page
Step
275
Action
278
Transition
280
Transition section
282
Link
284
Jump
285
Alternative Branch
287
Alternative connection
289
Parallel branch
290
Parallel connection
291
Text object
292
33002204 12/2010
Sequence language SFC
Step
Introduction
A step is represented using a block that contains a step name. Step names must be
unique within the project.
A step becomes active when the upstream transition is satisfied and is normally
inactive when the downstream transition is satisfied.
Initial Step
A special case with steps is the initial step. The initial status of a SFC section is
characterized by the initial step, which is active when initializing the project
containing the section. A step in a SFC section must always be defined as an initial
step. In Concept it is possible to define a step in the middle of a step string as initial.
The initial step is denoted by double lined borders.
Waiting Step
Zero or more actions belong to every step. Steps without action are known as
waiting steps.
Step Delay Time
A time can be entered, which is the least amount of time the step must be active for.
This is called the step delay time (step duration).
NOTE: This time is only applicable to the step, not for the actions allocated to it.
Individual times can be defined for these.
Maximum Supervision Time
The maximum supervision time specifies the maximum time in which the step should
normally be active. If the step is still active after this period of time, an error message
occurs, which you can view using the Online →Event Viewer. In animation mode,
the error is additionally identified by a colored outline around the step object.
NOTE: This time supervision applies only to the step, not to the actions allocated to
it. Individual times can be defined for these.
33002204 12/2010
275
Sequence language SFC
Minimum Supervision Time
The minimum supervision time sets the minimum time for which the step should
normally be active. If the step is still active after this period of time, an error message
occurs, which you can view in the Online →Event Viewer. In animation mode, the
error is additionally identified by a colored outline around the step object.
NOTE: This time supervision applies only to the step, not to the actions allocated to
it. Individual times can be defined for these.
Coordinating the Times
Step delay time< minimum supervision time< maximum supervision time
Setting the Times
In the properties dialog, the time values can be entered directly as time literals or
can be set as multi element variables of data type SFCSTEP_TIMES. The values
can be automatically determined in learn supervision time mode.
The time literals can be modified in animation mode.
’SFCSTEP_TIMES’ Variable
In ’SFCSTEP_TIMES’ variable usage, the learned times of these variables are
assigned as the initial values. If these initial values are to be used for a long period
of time, corresponding elements (min., max.) of these variables must not be written.
After the supervision times have been learned, the modified initial values must be
downloaded to the PLC using Online →Download Changes.
The ’SFCSTEP_TIMES’ variable can be used everywhere and has the following
structure:
’varname’: SFCSTEP_TIMES
delay: TIME
min: TIME
max: TIME
The elements have the following meaning:
’varname’.delay = delay time
z ’varname’.min = minimum supervision time
z varname’.max = maximum supervision time
z
276
33002204 12/2010
Sequence language SFC
Step Variable
Every step is implicitly allocated a (read only) variable of data type
SFCSTEP_STATE. This step variable has the name of the allocated step. The step
variable can be used everywhere and has the following structure:
’Step name’: SFCSTEP_STATE
t: TIME
x: BOOL
tminErr: BOOL
tmaxErr: BOOL
The elements have the following meaning:
’Step name’.t = current dwell time in step
z ’Step name’.x
z 1: Step active
z 0: Step inactive
z
33002204 12/2010
z
’Step name’.tminErr
z 1: Underflow of minimum supervision time
z 0: No underflow of minimum supervision time
z
’Step name’.tmaxErr
z 1: Overflow of maximum supervision time
z 0: No overflow of maximum supervision time
277
Sequence language SFC
Action
At a Glance
The actions, which are to be performed, as the step is active must be connected to
the step.
Actions are declared in the properties dialog of the triggering step, see Declaring
actions, page 300.
A step can be assigned none or several actions. A step which is assigned no action,
has a waiting function, i.e. it waits until the assigned transition is completed.
An action is a variable of BOOL data type.
The control of actions is expressed through the use of identifiers.
Signal assignment
The following signals can be assigned to an action:
Direct address
An action can be assigned a hardware output via a direct address. In this case,
the action can be used as an enabling signal for a transition, as an input signal in
another section and as an output signal for the hardware.
z Variable
The action can be used as an input signal with assistance from a variable in
another section. This variable is also called action variable.
z Unlocated variable
With Unlocated variablethe action can be used as an enabling signal for a
transition and as an input signal in an FBD section. Unlocated variables are
declared in the Variable Editor (see page 543).
z Located variable
With Located variable the action can be used as an enabling signal for a
transition, as an input signal in another section and as an output signal for the
hardware. Located variables are declared in the Variable Editor
(see page 543).
z
278
33002204 12/2010
Sequence language SFC
Direct addresses
The information on/display of direct addresses can be given in various formats. The
display format is set in the dialog box Options →Presettings →Joint. Setting the
display format has no impact on the entry format, i.e. direct addresses can be
entered in any format.
The following address formats are possible:
z Standard format (X00001)
The five-character address comes directly after the first digit (the Reference).
z Separator format (X:00001)
The first digit (the Reference) is separated from the following five-character
address by a colon (:).
z Compact format (X:1)
The first digit (the Reference) is separated from the following address by a colon
(:), and the leading zeros of the address are not given.
z IEC format (XW1)
In first place, there is an IEC identifier, followed by the five-character address.
z %0x12345 = %Q12345
z %1x12345 = %I12345
z %3x12345 = %IW12345
z %4x12345 = %QW12345
33002204 12/2010
279
Sequence language SFC
Transition
Introduction
A transition specifies the condition through which the check of one or more pretransition steps passes on to one or more consecutive steps along the
corresponding link.
Transition Condition
A transition condition is one of the variables of data type BOOL allocated to the
transition.
Transition conditions are declared in the properties dialog of the transition, see also
Declaring a Transition, page 305.
The transition condition can be:
a direct address (input or output),
z a variable (input or output) or
z a Transition Section (see page 282).
z
Variable name position:
If...
Then...
If you allocate a direct address or a variable to Then the name of the address/variable is
the transition.
displayed below the transition icon.
If you allocate a transition section to the
transition.
Then the name of the transition section is
displayed above the transition icon.
NOTE: The variable or address allocated to the transition is only read by the
transition, never written.
Enabling a Transition
A transition is enabled if the steps immediately preceding it are active. Transitions
whose immediately preceding steps are not active are not analyzed.
NOTE: If no transition condition is defined, the transition will never be active.
Transition Switch Time
The transition switch time can theoretically be as short as possible, but can never
be zero. The transition switch time lasts at least the duration of the scan.
Transition Diagnosis
Transition switching can be supervised by the Transition Diagnosis (see page 319).
280
33002204 12/2010
Sequence language SFC
Transition Trigger Sweep
Transition trigger sweep occurs when the transition is enabled and the associated
transition conditions are satisfied.
Triggering a transition leads to the disabling (resetting) of all immediately preceding
steps that are linked to the transition, followed by the activation of all immediately
following steps.
If triggering a transition leads to the activation of several steps at the same time, then
the sequence belonging to these steps is called Parallel Chain (see page 290). After
simultaneous activation, each of these chains is processed independently of each
other. To emphasize this specific type of construction, the branch and connection of
parallel chains are displayed with a double horizontal line.
33002204 12/2010
281
Sequence language SFC
Transition section
At a Glance
For every Transition (see page 280) a transition section can be created. This is a
section containing the logic of the transition condition and it is automatically linked
with the transition.
Generating a transition section
Transition sections are generated in the properties dialog of the transition, see also
Declaring a Transition, page 305.
Name of transition section
Name of transition section:
If…
Then…
If in the dialog Options →Preferences →
Graphical Editors... the option Dynamically
enumerated has been selected.
Then the alias designation of the transition is
displayed in the Transition properties
dialog automatically.
Should a name for the transition section be
entered manually.
Please ensure that the name is unique
throughout the whole project (the name is not
case-sensitive). If the section name entered
already exists, a warning is given, and
another name must be chosen. The name
must correspond to the IEC Name
conventions, otherwise an error message
appears.
NOTE: Do NOT alter the name of a transition section through Data file → Section
properties, otherwise the link to the transition is will be lost.
Occupying a transition section
When first opening the transition section (Edit... key in the Transition properties
dialog) this is automatically generated. The name of the transition section is
displayed above the transition symbol in the SFC editor.
Altering the transition conditions
Should another option be selected after the creation of the transition section as
Transition section, a query appears, whether the transition section should be
deleted. If the question is replied in the negative, the transition section remains.
A list can be displayed with the currently unused transition section with help from the
command button Look up... .
282
33002204 12/2010
Sequence language SFC
Programming languages for transition section
FBD, LD, IL and ST are possible as programming languages for transition sections.
The programming language to be used can be defined in the dialog Options →
Preferences... →Common... with the option Language for transition sections.
Should the FBD programming language be selected, the section is automatically
preallocated with a UND block with 2 inputs whose outputs is preallocated with the
name of the transition section. The proposed block can then be linked or altered. No
such provision is evident for the other programming languages.
Editing function for transition section
The editing function for transition sections is restricted as opposed to "normal"
sections in the following ways:
z The transition section only has one single output (transition variable), whose data
type is BOOL. The name of this variable must be identical to the name entered in
the Transition section field.
z The transition variable can only be used once in written form.
z Only functions can be used, Function Blocks cannot.
z There is only one network, i.e. all functions used are linked with each other either
directly or indirectly.
z Transition sections can only be reached via the menu command button Edit... in
the Transition properties dialog. They do not appear in the Open section
dialog.
z In the Delete section dialog transition sections are denoted by a "T" in front of
the section name.
Transition section animation
If the transition, and therefore the transition section, is not processed, the status
INHIBITED appears in the animated transition section.
33002204 12/2010
283
Sequence language SFC
Link
At a Glance
Links connect steps and transitions. Links are normally generated automatically
when positioning objects. If objects are positioned in cells which do not immediately
follow each other, a link must explicitly be made.
Simple sequences
The change of step and transition is consequentially repeated with simple
sequences.
A process of S_5_10 to S_5_11 only takes place, if step 5_10 is in an active state
and the condition for transition a is true.
284
33002204 12/2010
Sequence language SFC
Jump
General information
A jump enables a program to continue in another place. Jumps into a Parallel chain
(see page 290) in or out of a parallel chain are not possible.
Differences are made between chain jumps and chain loops with jumps.
Chain jump
A chain jump is a special case of alternative branch, with one or more branches
containing no steps.
A process of S_5_10 via S_5_11 and S_5_12 after S_5_13 only occurs, if S_5_10
is active and the condition for transition a is true. A process of S_5_10 directly after
S_5_13 only occurs, if S_5_10 is active and the condition for transition b is true and
a is false.
33002204 12/2010
285
Sequence language SFC
Chain loop
A chain loop is a special case of alternative branch, with which one or more
branches lead back to a previous step.
A process of S_5_11 via S_5_10 only occurs if the condition for transition c is false
and b is true.
286
33002204 12/2010
Sequence language SFC
Alternative Branch
Introduction
The alternative branch offers the possibility to program branches conditionally in the
control flow of the SFC structure.
Structure
With alternative branches, as many transitions follow a step under the horizontal line
as there are different sequences. Only one of these transitions can ever be
switched. The branch to be solved is determined by the result of the transition
conditions of the transitions, which come after the alternative branch.
Processing Sequence
Branch transitions are processed from left to right. If a transition condition is
satisfied, the remaining transitions are no longer processed The branch with the
satisfied transition is activated. This gives rise to a left to right priority for branches.
If none of the transitions is switched, the currently set step remains set.
Processing
Sequence processing:
If...
Then...
If S_5_10 is active and the transition condition Then a sequence from S_5_10 to S_5_11
a is true.
occurs.
If S_5_10 is active and the transition condition Then a sequence from S_5_10 to S_5_12
b is true and a is false.
occurs.
Sequence processing:
33002204 12/2010
287
Sequence language SFC
Alternative Branch after Parallel Joint
According to IEC 1131-3, alternative branches may not directly follow parallel joints.
The joint and the branch must be separated by a transition step sequence.
Example:
If you want to insert an alternative branch directly after a parallel joint, you can use
the Options →Preferences →Graphic Editors →Allow Alternative Branches
after Parallel Joints to do so.
Example:
Joint
All alternative branches must be rejoined to a single branch through Alternative
Joints (see page 289) or Jumps (see page 285).
288
33002204 12/2010
Sequence language SFC
Alternative connection
At a Glance
In the alternative connection, the various branches of an alternative branch are
again connected to one branch in which additional processing can be performed.
This connection can also be performed with a jump.
Processing
Sequence processing:
If…
Then…
If S_5_10 is active and the transition condition Then a process of S_5_10 to S_5_12 takes
d is true.
place.
If S_5_8 is active and the transition condition
b is true, and therefore a jump to S_5_12 is
performed.
Then a process of S_5_8 to S_5_12 takes
place.
If S_5_11 is active and the transition condition Then a process of S_5_11 to S_5_12 takes
e is true.
place.
NOTE: Only a single one of these branches is active, corresponding to the transition
condition in the alternative branch.
Sequence processing:
33002204 12/2010
289
Sequence language SFC
Parallel branch
At a Glance
With parallel branches, the edit is split into two or more strings, which will be
processed in parallel Only a joint transition immediately through the horizontal
double synchronization lines is possible.
Processing
Processing a sequence:
If…
Then…
If S_5_10 is active and the transition condition Then a process of S_5_10 to S_5_11,
S_5_12,… takes place.
a, which shares the same transition, is
likewise true.
NOTE: After the simultaneous activation of S_5_11, S_5_12 etc., the sequences
run independent of each other.
Processing a sequence:
Definition of initial steps
If a step is to become an initial step within a parallel branch, a step must be defined
as the initial step in each branch of the parallel branch.
290
33002204 12/2010
Sequence language SFC
Parallel connection
At a Glance
The parallel connection reconnects two or more parallel branches to a branch. The
transition to a parallel connection is evaluated when all previous steps of the
transition are set. Only a joint transition immediately through the double horizontal
synchronisation lines is possible.
Processing
Processing a sequence:
If…
Then…
If S_5_10, S_5_11 etc. are active at the same Then a process of S_5_10, S_5_11, …to
time and the transition condition d, sharing a S_5_13 takes place.
joint transition, is true.
Processing a sequence:
33002204 12/2010
291
Sequence language SFC
Text object
At a Glance
Text can be positioned in the form of text objects using SFC sequence language.
The size of these text objects depends on the length of the text. This text object is
at least the size of a cell and can be vertically and horizontally enlarged to other cells
according to the size of the text. Text objects can only be placed in free cells.
Memory space
Text objects occupy no memory space on the PLC because the text is not
downloaded onto the PLC.
292
33002204 12/2010
Sequence language SFC
9.3
Working with the SFC Sequence Language
Overview
This section describes working with the SFC sequence language.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
General information on editing objects
294
Declaring step properties
297
Declaring actions
299
Identifier
302
Declaring a Transition
305
Alias Designations for Steps and Transitions
307
293
Sequence language SFC
General information on editing objects
At a Glance
In the SFC editor the background consists of a logical grid. SFC objects can
theoretically be placed in every unoccupied cell. If a link with another object is
established (explicitly or by vertically placing objects in neighboring cells), this link
will be tested. If this link is not permitted, a report of this is given and the object is
not inserted.
Steps, transitions and jumps each require a cell. Parallel branches, parallel
connections, alternative branches and alternative connections do not require a
separate cell each, but are inserted into the corresponding cell of the step or
transition.
Maximum number of elements
To prevent step strings being subdivided, 99 linked steps with the transitions are
vertically shown along with a locking jump with its transition. To limit the complexity
and to enable the animation to be performed, the number of objects (Steps +
Transitions + Branches + Connections) in one section is limited to 2000.
Inserting Objects
The SFC object (Step, Transition etc.) can be inserted individually via the menu
command in the main menu Objects or in the form of a a group (Step transition
string, structured parallel string etc.) of the required size.
After selection of the object, a position in the step string can be selected, in which
the object should be inserted. If the position selected is already occupied, space is
made before insertion into the step string, if desired, and then the object placed in
it. If the object is placed on a connection, it is separated, the object is inserted and
a link to the newly placed object is generated.
Shifting objects
If the object is shifted onto a connection, it is separated, the object is inserted and a
link to the newly placed object is generated.
Copying steps
By copying and inserting it is possible to copy steps through projects. Since the
definition of actions displays a reference to a variable, which is defined by the
Variable Editor for the particular project, copying between projects can result in this
reference no longer being valid. In this instance, the action is deleted, the action list
is updated and an error message is displayed.
294
33002204 12/2010
Sequence language SFC
Deleting steps
Steps can only be deleted after an action has been saved if the action(s) were
unconnected before the step was performed.
Selecting an object
The procedure for selecting an object is as follows:
Step
Action
1
With Objects →Selection mode go to selection mode.
2
Position the cursor on the object to be selected and left-click.
Reaction: The selected object is displayed in a blue border.
Selecting several objects (by pressing Shift)
The procedure for selecting several objects (by pressing Shift) is as follows:
Step
Action
1
With Objects →Selection mode go to selection mode.
2
Position the cursor on the object to be selected first and left-click.
3
Press and hold the Shift key, select additional objects and left-click.
Reaction: The selected objects are displayed in a blue border.
Selecting several objects (by using the rubber band function)
The procedure for selecting several objects (by using the rubber band function) is as
follows:
Step
Action
1
With Objects →Selection mode go to selection mode.
2
Press and hold the left mouse button, and pull a border over the objects to be
selected.
Reaction: On releasing the mouse key, all objects touching the border will be
selected. The selected objects are displayed in a blue border.
Selecting all objects in a column/line
The procedure for selecting all objects in a column/line is as follows:
Step
33002204 12/2010
Action
1
With Objects →Selection mode go to selection mode.
2
In the column ruler/line ruler, click on the column number/line number whose
objects are to be selected.
Note: To select several columns/lines, press and hold the Shift key.
Reaction: The selected objects are displayed in a blue border.
295
Sequence language SFC
Inserting additional columns
The procedure for inserting additional columns within an existing step string is as
follows:
Step
Action
1
With Objects →Selection mode go to selection mode.
2
In the column ruler, click on the column number in front of which the insertion is
to be performed.
Note: In order to insert several columns, press the Shift key to select several
columns and insert a corresponding number of empty spaces.
3
Use the menu command Edit →Insert.
Reaction:From the selected column, the entire step string is moved one column
to the right. The links (branches) will remain intact.
Inserting additional lines
The procedure for inserting additional lines within an existing step string is as
follows:
Step
296
Action
1
With Objects →Selection mode go to selection mode.
2
In the line ruler, click on the line number in front of which the insertion is to take
place.
Note: Should the insertion of several lines be required, several lines are selected
and a corresponding number of empty spaces are inserted by pressing the Shift
key.
3
Use the menu command Edit →Insert.
Reaction: From the selected line, the entire step string is moved one line
downwards. The links (branches) therefore remain even.
33002204 12/2010
Sequence language SFC
Declaring step properties
Introduction
The step properties are declared in the properties dialog of the step.
Declaring step properties:
33002204 12/2010
297
Sequence language SFC
Declaring step properties
The following description contains an example of declaring the step properties:
Step
298
Action
1
With Objects →Selection mode go to selection mode.
2
Double-click on a step.
Result: The dialog Step properties of the step opens.
3
A name can be manually defined for the step, or the proposed name can remain.
If a name is to be assigned, please note that the step name (max. 32 characters)
must be unique for the entire project. If the step name entered already exists, a
warning is given and another name must be chosen. The step name must
correspond to the IEC name conventions, otherwise an error message is
displayed.
Note: In accordance with IEC1131-3, only letters are permitted as the first
character of step names. Should numbers be required as the first character,
however, use the menu command Options →Preferences →IEC Extensions
→Allow leading digits in identifiers.
Step names may not end in 4 digits (e.g. xxx_1234). This ending is reserved in
case in Options →Preferences →Graphical Editors... the options button
Dynamic numbered is activated.
Instead of the free names an alias designation can also be selected, see also
Alias Designations for Steps and Transitions, page 307 This is then shown in
SFC and FBD sections and with search functions, application documentation
and analysis.
4
Next, define whether or not the step is the initial step of the sequence. A initial
step must be defined for each sequence.
5
If desired, the Supervision time and delay time can be defined for the step.
The time values can be entered in the properties dialog either directly as time
duration literal (this can be automatically transmitted in the Learn Supervision
time mode, see also Learn monitoring times, page 316) or as multi-element
variable of SFCSTEP_TIMES data type, see also ’SFCSTEP_TIMES’ Variable,
page 276.
Here:
Delay time< minimum Supervision time< maximum Supervision time
6
Using the button Comment call up the dialog box Enter with comment, in
which a comment on the step may be entered. This comment is shown in the
status bar of the editor window, when the step is selected.
33002204 12/2010
Sequence language SFC
Declaring actions
At a Glance
The actions are declared in the properties dialog of the step.
Declaring actions:
33002204 12/2010
299
Sequence language SFC
Declaring actions
The following description contains an example of declaring the actions:
Step
Action
1
With Objects →Selection mode go to selection mode.
2
Double-click on a step.
Reaction: The dialog Step properties of the step is opened.
3
From the Cdet list, select an Identifier (see page 302) for the Action. In this way,
the behavior of the action is determined (e.g. saving, non saving, delayed etc.).
Note: With the identifiers L, D, and DS, in the text box Time duration: an
additional time duration of TIME data type must be defined.
4
Next define the type of action (variable or dirct address) in the zone Type: with
the option buttons.
5
z If the Variable has been selected, it is possible with the button Var.
declaration...to open the Variable Editor and define a new output variable
there.
Also with the command button Look up... a list of all the variables can be
shown and one selected through Select.
z If the Direct address has been selected, in the text box Direct address: the
output address must be entered.
6
After all the definitions for the actions have been met, confirm this with the
command button New
Note: Confirmation with the Enter key is not possible in this case and leads to
an error message
Altering an action
The procedure for altering an action declaration is as follows:
Step
Action
1
With Objects →Selection mode go to selection mode.
2
Double-click on a step.
Reaction: The dialog Step properties of the step is opened.
3
To alter an action declaration, select an action in the list.
Reaction: All definitions (identifiers, time duration, variable or address and type)
of the action are transferred into the corresponding text boxes and lists.
4
If these definitions are altered, as described in the Declaring actions, page 300
section.
5
z Should it be necessary to assign these new definitions as a new action in the
step, use the command button New.
Reaction: The action is additionally recorded in the list of actions.
z Should it be necessary to overwrite the current action with the new action, use
the command button Accept
Reaction: The old action is overwritten.
300
33002204 12/2010
Sequence language SFC
Deleting an action declaration
The procedure for deleting an action declaration is as follows:
Step
33002204 12/2010
Action
1
With Objects →Selection mode go to selection mode.
2
Double-click on a step.
Reaction: The dialog Step properties of the step is opened.
3
To delete an action declaration, select an action in the list.
Reaction: All definitions (identifiers, time duration, variable or address and type)
of the action are transferred into the corresponding text boxes and lists.
4
Use the command button Delete.
Reaction: The selected action is deleted.
301
Sequence language SFC
Identifier
At a Glance
For every connection of an action to a step, an identifier must be defined for the
action. The identifier must define the control of the action. The identifier can be
introduced as the input of an internal Function Block for the configured link of the
step with the action. If the step is active, the input of this internal Function Block is
set to 1. The Function Block is then processed according to its type. If all conditions
are satisfied, the output Q (action) is set to 1.
The following identifiers are usable in Concept:
z N / none (see page 302)
z S (see page 302)
z R (see page 303)
z L (see page 303)
z D (see page 303)
z P (see page 304)
z DS (see page 304)
For the identifiers L, D and DS, a time duration of the data type TIME must
additionally be defined.
Identifier N / none
The identifiers N and none have the same meaning and stand for "Not saved" and/or
"No identifier".
Identifier S
The identifier S stands for "set (saved)".
The set action also remains active, when the associated step is inactive. The action
first becomes inactive, when reset is used with the Identifier R (see page 303) in
another step.
NOTE: The identifier is automatically declared as unbuffered. This means that the
value is reset to "0" after stop and cold restart, e.g. when voltage is on/off. Should a
buffered output be required, please use the RS or SR Function Block from the IEC
block library.
302
33002204 12/2010
Sequence language SFC
Identifier R
The identifier R stands for "overriding reset".
The action, which is set in another step with the Identifier S (see page 302), is reset.
The activation of any action can also be prevented.
NOTE: The identifier is automatically declared as unbuffered. This means that the
value is reset to "0" after stop and cold restart, e.g. when voltage is on/off. Should a
buffered output be required, please use the RS or SR Function Block from the IEC
block library.
In the step S_5_10 the action ACT1 becomes and remains active, until the reset in
step S_5_12.
Identifier L
The identifier L stands for "Limited".
If the step is active, the action is also active. After the process of the time duration,
defined manually for the action, the action returns to 0, even if the step is still active.
The action also becomes 0 if the step is inactive.
Identifier D
The identifier D stands for "delayed".
If the step is active, the internal timer is started and the action becomes 1 after the
process of the time duration, which was defined manually for the action. If the step
becomes inactive after that, the action becomes inactive as well. If the step becomes
inactive before the process of the internal time, the action does not become active.
33002204 12/2010
303
Sequence language SFC
Identifier P
The identifier P stands for "Pulse".
If the step becomes active, the action becomes 1 and this remains for one program
cycle, independent of whether or not the step remains active.
Identifier DS
The identifier DS stands for "delayed and saved". It is a combination of the identifiers
D (see page 303) and S (see page 302).
If the step becomes active, the internal timer is started and the action becomes
active after the process of the manually defined time duration. The action first
becomes inactive once again, when reset is used with the IdentifierR
(see page 303) in another step. If the step becomes inactive before the process of
the internal time, the action does not become active.
304
33002204 12/2010
Sequence language SFC
Declaring a Transition
Introduction
Transitions are declared in the properties dialog of the transition.
Declaring a transition:
33002204 12/2010
305
Sequence language SFC
Declaring a transition:
The following example describes the procedure when declaring a transition:
Step
Action
1
With Objects → Selection mode go to selection mode.
2
Double-click on a transition.
Response: The dialog Transition properties of the transition is opened.
3
Begin by determining Kind of transition condition: determine the type
(Transition section, Variable, Literal, Direct address) of transition condition.
4
z
5
The transition condition can now be inverted with the Invert trans. cond. check
box.
Response: An inverted transition condition is displayed with a (~) symbol in front
of the name of the variable on the transition.
6
With the command button Comment click on the dialog box Enter with
comment, in which a comment about the transistion can be entered. This
comment is shown in the status bar of the editor window, if the transition is
selected.
7
After all the definitions for the transition have been met, confirm this with the
command button OK.
After selecting theTransition section has been selected, enter in the text
box Transition section the name of the transition section to be created. This
is a section containing the logic of the transition condition and it is
automatically linked with the transition. To process this section, press the
command button Process....
z After selecting theVariable has been selected, enter in the text box BOOL
variable the name of the selected unlocated variable, located variable or
constants.
Note: For an example for invocation of multi-element variables see Calling
Derived Data Types, page 588.
z If the Literal has been selected, select in the field Value the value of the
literal.
z If the Dir. address , enter in the text box Direct addressthe required
address.
Copying transition conditions
By copying and inserting it is possible to copy transitions through projects. Since the
definition of a transition displays a reference to a variable, which is defined by the
Variable Editor for the particular project, copying between projects can result in this
reference no longer being valid. In this instance, the transition condition is deleted
and an error message appears.
306
33002204 12/2010
Sequence language SFC
Alias Designations for Steps and Transitions
Introduction
Instead of free names you can also select alias designations for steps and
transitions. These are then displayed in SFC and FBD sections during search
functions, application documentation and analysis.
Import and export functions do not recognize the alias designations, since they are
dynamically generated. The visualization can retrieve the alias designations
dynamically, however they cannot be used for the configuration of fixed references,
since they can change constantly.
The languages ST, IL and LD do not support alias designations and display the free
names.
Name Definition
The alias designations are dynamically generated during editing procedures, and
the same applies when the Dynamic Numbered option is switched on.
Alias designations remain empty until numbering can take place i.e. when all objects
are linked to one chain.
The alias designations are made up of the position of the steps and transitions in the
section and the section name.
The length of the section name part displayed in the alias designation is freely
definable in the Options →Preferences →Graphical Editors Preferences dialog.
You can define how many characters from the section name (beginning with the first
character) should go into the alias designations here.
NOTE: The settings in this dialog are used in the project description (PRJ.DSK) and
in the Concept installations description (CONCEPT.DSK), i.e. they are valid for the
entire Concept installation.
If a project is opened, which was created using alternative settings (e.g. Settings
from Presentation of Steps and Transitions numbered IEC_like in the project and
Dynamic numbered in the current Concept installation), errors can occur when
opening projects.
Alias Designations for Steps
With steps, the lines and columns occupied by steps are each numbered beginning
with the top left. A four-figure step number is made from the column and line
numbers (ccll). The alias designation for steps is made from S_ string, part of the
section name (nnn), a further underscore (_) and the step number (ccll) (S_nn_ccll).
33002204 12/2010
307
Sequence language SFC
Alias Designations for Transitions
The alias designations for transitions are derived from the alias designation of the
preceding step cell, even when this is empty. The alias designation for transitions is
made from the T_ string, part of the section name (nnn), a further underscore (_)
and the number of the preceding step cell (ccll) (T_nn_ccll).
Activating the Alias Designations
The free name is entered as the default for steps and transitions. If you require alias
designations, you can activate them in the Options →Preferences →Graphical
Editors Preferences dialog using the Dynamic Numbered option.
CAUTION
Danger of loss of data.
The free names (IEC_like) are overwritten by the alias names when this option is
selected. If you want to restore the free names, close the project without saving.
Failure to follow these instructions can result in injury or equipment damage.
CAUTION
Danger of loss of data.
You must not switch between the IEC_like and Dynamic Numbered display
modes if an FBD transition section is already open. Otherwise, this could result in
section and variable names containing spaces. Therefore, close all FBD transition
sections before you change the representation mode.
Failure to follow these instructions can result in injury or equipment damage.
308
33002204 12/2010
Sequence language SFC
Example for Alias Designations
Example for alias designations:
Inserting and Deleting Objects
When inserting and deleting objects (steps and transitions) the alias designations
are renumbered.
33002204 12/2010
309
Sequence language SFC
9.4
Online functions of the SFC sequence language
Overview
This section describes the online functions of the SFC sequence language
elements.
What's in this Section?
This section contains the following topics:
Topic
310
Page
Animation
311
Controlling a Step String
313
Learn monitoring times
316
Transition diagnosis
319
33002204 12/2010
Sequence language SFC
Animation
Introduction
In the animation mode the following are displayed in different colors in the editor
window:
z the active steps,
z the time the steps are or were active for,
z time out errors of the steps and
z the status of the transitions (made, not made).
NOTE: If the transition, and therefore the transition section, is not processed, the
status DISABLED appears in the animated transition section.
Activating the Animation
The animation is activated with the menu command Online →Animation.
Color key
There are 12 different color schemes available for animation. An overview of the
color scheme and the meaning of each color can be found in Online help (Tip:
Search the online help for the index reference "Colors").
Changing Values
In this mode the following can be changed:
z With transitions:
z the transition condition, if this is a literal.
z
With steps:
z the maximum supervision time,
z the minimum supervision time,
z the delay time and
z the times of the actions.
These changes are sent online to the PLC.
33002204 12/2010
311
Sequence language SFC
Transition Animation
Normally, only the currently evaluated transitions are animated and their status
(transition condition satisfied/not satisfied) is displayed.
It is also possible to display the status of the transitions not currently being
processed. This will only show the status of the transitions. It has no influence on the
behavior of the sequence. To do this you require the XSFCCNTRL function block of
the SYSTEM block library. Additionally, in the Options →Preferences →Graphical
Editors dialog, you must check the Animate All Conditions of the Transition
Section check box.
NOTE: This function leads to a considerable burden on the logic scan. This results
from the fact that all the transitions in the affected section are solved and animated
in one logic scan, whereas this is normally solved sequentially depending on the
process status (preceding step active/inactive).
Displaying all Transition Conditions
The procedure for showing all transition conditions is as follows:
Step
312
Action
1
Create an FBD section and enter the XSFCCNTRL function block of the
SYSTEM block library.
2
Enter the names of the SFC section to be animated as the instance name (block
name) of the XSFCCNTRL function block.
3
Assign the value "1" to the ALLTRANS input of the XSFCCNTRL function block
(using a literal or, depending on the process, a variable).
Response: By doing this, the calculation of all transition conditions is activated.
Otherwise an old status of the transition condition would be displayed.
4
With the menu command Project →Execution Order... (or the project browser)
ensure that the FBD section is executed before the SFC section to be animated
5
Check the Animate All Conditions of the Transition Section check box in the
Options →Preferences →Graphical Editors dialog.
6
Download the program to the PLC and start the animation of the SFC section.
Response: All transition conditions are then displayed.
33002204 12/2010
Sequence language SFC
Controlling a Step String
Introduction
There are 3 ways of controlling a string:
z with the animation control
z with the menu commands in the main menu Online
z with the SFCCNTRL or XSFCCNTRL function block (SYSTEM block library)
If controlling a string through the different options simultaneously, these control
operations have equal priority.
The control operations triggered using the menu commands in the Online main
menu and using the animation panel can be locked by the function blocks
SFCCNTRL and XSFCCNTRL.
A control operation in one of the methods is also displayed in the other two methods.
Requirements
It is only possible to control the step string when the animation mode for the section
is active.
Animation Panel
The animation panel is activated with the menu command Online →Show
Animation Panel.
The animation panel contains all the possibilities that are also available as menu
commands.
Mode of Functioning
You can test the processing of an SFC section with the animation panel and the
menu commands. For example, steps can be relayed, the processing of the string
can be controlled (whether or not transitions and/or actions are to be processed),
time errors can be reset or the string can be reset to initialization status.
WARNING
Danger of unsafe, dangerous and destructive tool operations.
Set/Reset flag, Disable Transitions, Disable Actions, Step Unconditional,
Step/Trans. dependant and Force Selected Steps should not be used for
debugging on controllers of machine tools, processes or material maintenance
systems when they are running. This can lead to unsafe, dangerous and
destructive operation of tools or processes linked to the controller.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
33002204 12/2010
313
Sequence language SFC
Set/Reset Flag
The Set/Reset flag resets the string and starts it as standard.
Reset chain
To reset the string, activate Set/Reset Flag. This stops the chain and all actions
are reset. No operator interventions are possible.
z Starting the chain in a standardized way
For a standardized start of the string, Set/Reset Flag must first be activated and
then deactivated. With the 1 →0 slope the chain is reset i.e. the initial step is
activated.
z
Disable Time Check
If Disable Time Check is activated, there is no longer any time supervision of the
steps. The step delay time, however, still remains active.
Disable Transitions
If Disable Transitions is activated, the transition conditions are no longer utilized.
The string remains in its current state, independent of the signals on the transitions.
The string can still only be used via the control commands (Set/Reset Flag, Step
Unconditional, Step/Trans. Dependant).
Disable Actions
If Disable Actions is activated, the step actions are no longer processed.
Step Unconditional
The next step is activated independently of the transition status, but not until the step
delay time of the active step has elapsed.
With Step Unconditional, all branches are activated in parallel branches, and the
left branch is always activated in alternate branches.
Step/Trans. dependent is used for activating process-dependent branches.
WARNING
Danger of unsafe, dangerous and destructive tool operations.
Step Unconditional activates the next step, even if the transition is not satisfied.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
314
33002204 12/2010
Sequence language SFC
Step/Trans. Dependent
The next step is activated when the transition conditions are satisfied.
Step/Trans. Dependent is advisable only when Disable Transitions is active.
By freezing the transitions (Disable Transitions) it is possible, with Step/Trans.
Dependent to process the string elements manually step by step. In this way the
transitions commutate depending on the transition condition.
Reset Time Error
If Reset Time Error is activated, the error message display for time supervision in
the SFC section is reset.
Force Selected Steps
The selected step(s) are activated independent of the status of the transitions and
steps.
In alternative branches, only one single step and one single branch can be activated.
In parallel branches, steps can only be set, if the process is already located in the
parallel branch and one step in every branch is active. If one step is set in a parallel
branch, all other parallel branches remain unaffected by it.
WARNING
Danger of unsafe, dangerous and destructive tool operations.
Force Selected Steps activates the selected steps, even if the transition is not
satisfied.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
This functionality is not available via the function blocks SFCCNTRL or
XSFCCNTRL (SYSTEM block library).
Select Active Steps
The active step of the step string is searched for and selected.
33002204 12/2010
315
Sequence language SFC
Learn monitoring times
At a Glance
In this mode, the minimum and maximum times, for which the steps were active, are
determined. After mode deactivation, the determined times for the single steps are
shown in the Learn step monitoring times dialog box. From there, the minimum
(see page 276) and maximum monitoring time (see page 275) are accepted in the
step properties. During the transfer, a factor can be specified for the minimum and
maximum time.
NOTE: This functionality is not available via the Function Blocks SFCCNTRL or
XSFCCNTRL (Block library SYSTEM).
Note on determining values
Please ensure that at least 2 cycles typical for the process were gathered.
The determined values are first saved after the single step becomes inactive, i.e. if
a step was never active during the "Learn monitoring times" mode, no value is
determined for this step.
The storage of all determined step cells of a cycle can take some time. Because of
this, very long step sequence times and very short individual step durations may be
indeterminable, due to internal time overlaps.
Use of ’SFCSTEP_TIMES’ variable or constants
Should the step have been assigned a ’SFCSTEP_TIMES’ variable or constant in
the Step properties dialog, the times learned for these variables/constants are
shown as the initial value. Should these initial values be used for a long period of
time, do not allow corresponding elements (min., max.) of these variables/constants
to be written.
After learning the monitoring times, the altered initial values must be loaded into the
PLC.
z This is performed for variables with the menu command Online →Load.
z This is performed for constants with the menu command Online →Load
changes.
Calculating "learned" times
A factor can be defined for the determined values, which are multiplied when
calculating the monitoring times.
z Minimum monitoring time = minimum determined time x Minimum [%]
z Maximum monitoring time = maximum determined time x Maximum [%]
316
33002204 12/2010
Sequence language SFC
Calculating "learned" times " Example 1
Calculating "learned" times
z The determined times for one step are: 1 s, 2 s, 2 s
z Minimum [%]: 50
z Maximum [%]: 200
Following the above formula, this results in a minimum monitoring time of 500 ms
and a maximum monitoring time of 4 s.
Calculating "learned" times " Example 2
If a delay time is given for the step, this is considered when calculating the minimum
monitoring time. I.e. if the delay time is larger than the calculated value for the
minimum monitoring time, the calculated value for the minimum monitoring time is
ignored and set to 0 ms (i.e. there is no monitoring of the minimum time).
Calculating "learned" times
z The determined times for one step are: 1 s, 2 s, 2 s
z Delay time: 2 s
z Minimum [%]: 50
z Maximum [%]: 200
This results in a minimum monitoring time of 0 ms and a maximum monitoring time
of 4 s.
Calculating "learned" times " Example 3
If a delay time is given for the step, this is likewise considered when calculating the
maximum monitoring time. I.e. if the delay time is larger than the calculated value for
the maximum monitoring time, the calculated value for the maximum monitoring time
is ignored and in its place, a suitable value is calculated.
In such a case 2 cases are considered:
A value for the minimum monitoring time is available.
Then the value for the maximum monitoring time is calculated according to the
following formula: Minimum monitoring time + 20 ms
Example:
z The determined times for one step are: 2 s, 2 s, 2 s
z Delay time: 3 s
z Minimum [%]: 200
z Maximum [%]: 100
z
Following the above formula, this results in a minimum monitoring time of 4 s and
a maximum monitoring time of 4s20ms.
33002204 12/2010
317
Sequence language SFC
z
No value for the minimum monitoring time is available, see example 2.
Then the value for the maximum monitoring time is calculated according to the
following formula: Delay time + 20 ms
Example:
z The determined times for one step are: 1 s, 2 s, 2 s
z Delay time: 1 s
z Minimum [%]: 50
z Maximum [%]: 100
Following the above formula, this results in a minimum monitoring time of 0 s and
a maximum monitoring time of 1s20ms.
318
33002204 12/2010
Sequence language SFC
Transition diagnosis
Preview
The transition diagnosis monitors that the immediately preceding step was active
following the transition, commutated within a certain time in the step sequence (with
parallel branches in the step sequences). Should this not be the case, the
associated transition network (with alternative branches, the transition network of all
associated transitions) is analysed, and the error, including the analysed signal, is
entered in the signal buffer. This can now be evaluated using visualization software
(e.g. MonitorPro, Factory Link).
NOTE: The transition diagnosis only runs when the string is active.
Transition diagnosis vs. Reaction diagnosis
The performance of the transition diagnosis is about equal to that of the reaction
diagnosis (see Function Block REA_DIA from the block library DIAGNO). Contrary
to the reaction diagnosis the re-registration of all the actions started and possible
additional conditions are monitored here.
Activating the transition diagnosis
Activating the transition diagnosis:
Step
33002204 12/2010
Action
1
Activate the transition diagnosis by entering a Mon. time in the field Maximum
step properties of the immediately preceding step (see also Learn monitoring
times, page 316).
If the field remains empty or the time 0 is entered the transition monitoring is
inactive.
2
Aktivate in the dialog Project →Code generation options... →Code
generation options... the option Include diagnosis information to make
memory available in the PLC for the error buffer.
3
Load the altered configuration into the PLC.
319
Sequence language SFC
320
33002204 12/2010
Instruction list IL
33002204 12/2010
Instruction list IL
10
Overview
This Chapter describes the programming language instruction list IL which conforms
to IEC 1131.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
10.1
General information about the IL instruction list
322
10.2
Instructions
324
10.3
IL instruction list operators
339
10.4
Call up of functions, Function Blocks (EFBs) and Derived
Function Blocks (DFBs)
371
10.5
Syntax check and Code generation
381
10.6
Online functions of the IL instruction list
385
10.7
Creating a program with the IL instruction list
390
321
Instruction list IL
10.1
General information about the IL instruction list
General Information about the IL Instruction List
Introduction
With assistance from the programming language (IL) instruction list e.g. Function
Blocks and functions can be called up conditionally or unconditionally, assignments
can be performed, and jumps can be performed conditionally or unconditionally
within a section.
Spell Check
Spelling is immediately checked when key words, separators and comments are
entered. If a key word, separator or comment is recognized, it is identified with a
color surround. If unauthorized key words (instructions or operators) are entered, it
is likewise identified in color.
IEC Conventions
The IEC 1131 does not permit the input of direct addresses in the usual Concept
form. To input direct addresses see Operands, page 327.
In accordance with IEC 113-3, key words must be entered in upper case. Should the
use of lower case letters be required, they can be enabled in the dialog box Options
→Preferences →IEC Extensions... →IEC expansions with the option Allow
case insensitive keywords.
Blank spaces and tabs have no influence upon the syntax and can be used freely.
Context help
With the right mouse button an object can be selected and at the same time a
context sensitive menu called up. Therefore, for example, with FFBs the right mouse
button can call up the associated block description.
Syntax Check
A syntax check can be performed during the program/DFB creation with Project →
Analyze section, see also Syntax Check, page 382.
Codegeneration
Using the Project →Code Generation Options menu command, you can define
options for code generation, see also Code generation, page 384.
322
33002204 12/2010
Instruction list IL
Editing with the Keyboard
Normally editing in Concept is performed with the mouse, however it is also possible
with the keyboard (see also Short Cut Keys in the IL, ST and Data Type Editor,
page 834).
IEC Conformity
For a description of the IEC conformity of the IL programming language see IEC
conformity, page 849.
33002204 12/2010
323
Instruction list IL
10.2
Instructions
Overview
This section contains an overview of the instructions for the programming language
instruction list.(IL)
What's in this Section?
This section contains the following topics:
Topic
General information about instructions
324
Page
325
Operands
327
Modifier
329
Operators
331
Tag
334
Declaration (VAR...END_VAR)
336
Comment
338
33002204 12/2010
Instruction list IL
General information about instructions
At a Glance
An instruction list is composed of a series of instructions.
Each instruction begins on a new line and consists of:
z an Operator (see page 327),
z if necessary with modifier (see page 329) and
z if necessary one or more operands (see page 339).
Should several operands be used, they are separated by commas. It is possible for
a mark (see page 334)to be in front of the instruction, which is followed by a colon.
A comment (see page 338) can follow the instruction.
Example:
Structure of the programming language
IL is a so-called battery orientated language, i.e. each instruction uses or alters the
current content of the battery (a form of internal cache). The IEC 1131 refers to this
battery as the "result".
For this reason, an instruction list should always begin with the LD operand ("Load
in battery command").
Example of an addition:
33002204 12/2010
Command
Meaning
LD 10
The value "10" is loaded into the battery.
ADD 25
"25" is added to the battery content.
ST A
The result is stored in the "A" variable.
The content of the "A" variable and the battery is now "35". A
possible ensuing instruction would be worked with the battery
content "35", should it not begin with LD.
325
Instruction list IL
Comparative operations likewise always refer to the battery. The Boolean result of
the comparison is stored in the battery and is therefore the current battery content.
Example of a comparison:
326
Command
Meaning
LD B
The value "B" is loaded into the battery.
GT 10
"10" is compared with the battery content.
ST A
The result of the comparison is stored in the "A" variable.
If "B" is less than or equal to "10", the value of both the "A"
variable, and the battery content is "0" (FALSE). If "B" is
greater than or equal to "10", the value of both the "A"
variable, and the battery content is "1" (TRUE).
33002204 12/2010
Instruction list IL
Operands
At a Glance
An operand can be:
z a literal,
z a variable,
z a multi-element variable,
z an element of a multi-element variable,
z a FB/DFB output or
z a direct address.
Access to the field variables
When accessing the field variable (ARRAY), only literals and variables of ANY_INT
type are permitted in the index entry.
Example: Saving a field variable
LD var1[i]
ST var2.otto[4]
Type conversion
The operand and the current accu content must be of the same type. Should
operands of various types be processed, a type conversion must be performed
beforehand.
An exception is the data type TIME in conjunction with the arithmetic operators MUL
and DIV. With both these operators, an operand of TIME data type can be
processed together with an operand of ANY_NUM data type. The result of this
instruction has in this instance the data type TIME.
Example: Integer variable and real variable
In the example the integer variable "i1" is converted into a real variable, before being
added to the real variable "r4".
LD i1
INT_TO_REAL
ADD r4
ST r3
33002204 12/2010
327
Instruction list IL
Example: Integer variable and time variable
In the example the time variable "t2" is multiplied by the integer variable "i4" and the
result is stored in the time variable "t1".
LD t2
MUL i4
ST t1
Default data types of direct addresses
The following table shows the default data types of direct addresses:
Input
Output
Default data type
possible data type
%IX,%I
%QX,%Q
BOOL
BOOL
%IB
%QB
BYTE
BYTE
%IW
%QW
INT
INT, UINT, WORD
%ID
%QD
REAL
REAL, DINT, UDINT, TIME
Using other data types
Should other data types be assigned as default data types of a direct address, this
must be done through an explicit declaration (VAR…END_VAR (see page 336)).
VAR…END_VAR cannot be used in Concept for the declaration of variables. The
variable declaration conveniently follows the Variable Editor (see page 543).
328
33002204 12/2010
Instruction list IL
Modifier
At a Glance
Modifiers influence the implementation of the preceding operators (see Operators,
page 331).
Modifier N
The Modifier N is used to invert the value of the operands bit by bit.
The modifier can only be used on operands with the ANY_BIT data type.
Example: N
In the example C will be "1", when A is "1" and B is "0".
LD A
ANDN B
ST C
Modifier C
The modifier C is used to carry out the associated instruction, should the value of
the battery be "1" (TRUE).
The modifier can only be used on operands with the BOOL data type.
Example: C
In the example the jump after START is only performed, when A is "1" (TRUE) and
B is "1" (TRUE).
LD AAND BJMPC START
Modifier CN
If the modifiers C and N are combined, the associated instruction is only performed,
should the value of the battery be a Boolean "0" (FALSE).
Example: CN
In the example, the jump after START is only performed, when A is "0" (FALSE)
and/or B is "0" (FALSE).
LD A
AND B
JMPCN START
33002204 12/2010
329
Instruction list IL
Left bracket modifier "("
The left bracket modifier "(" is used to move back the evaluation of the operand, until
the right bracket operator appears. The number of right bracket operations must be
equal to the number of left bracket modifiers. Brackets can be nested.
Example: Left bracket "("
In the example E will be "1", if C and/or D is "1", just as A and B are "1".
LD A
AND B
AND( C
OR D
)
ST E
The example can also be programmed in the following manner:
LD A
AND B
AND(
LD C
OR D
)
ST E
330
33002204 12/2010
Instruction list IL
Operators
At a Glance
An operator is a symbol for:
z an arithmetic operation to be executed,
z a configured operation to be executed or
z the function call up.
Operators are generic, i.e. they are automatically suited to the operands data type.
NOTE: Operators can be either entered by hand or generated with assistance from
the menu Objects.
Table of operators
IL programming language operators:
33002204 12/2010
Operator
Operator key
possible
modifier
possible operand
see also
LD
Loads the operands
value into the battery
N
Literal, variable,
direct address of
ANY data type
Load (LD and
LDN), page 340
ST
Saves the battery
value in the operand
N
Store (ST and
Variable, direct
address of ANY data STN), page 341
type
S
Sets the operand to 1,
when the battery
content is 1
Variable, direct
address of BOOL
data type
Set (S),
page 342
R
Sets the operand to 0,
when the battery
content is 1
Variable, direct
address of BOOL
data type
Reset (R),
page 344
AND
Configured AND
N, N(, (
Literal, variable,
direct address of
ANY_BIT data type
Boolean AND
(AND, AND (),
ANDN, ANDN
()), page 346
OR
Configured OR
N, N(, (
Literal, variable,
direct address of
ANY_BIT data type
Boolean OR
(OR, OR (),
ORN, ORN ()),
page 348
XOR
Configured exclusive
OR
N, N(, (
Literal, variable,
direct address of
ANY_BIT data type
Boolean
exclusive OR
(XOR, XOR (),
XORN, XORN
()), page 350
331
Instruction list IL
332
Operator
Operator key
possible
modifier
possible operand
see also
ADD
Addition
(
Addition (ADD
Literal, variable,
and ADD ()),
direct address of
ANY_NUM data type page 353
or TIME data type
SUB
Subtraction
(
Subtraction
Literal, variable,
(SUB and SUB
direct address of
ANY_NUM data type ()), page 354
or TIME data type
MUL
Multiplication
(
Multiplication (*),
Literal, variable,
page 408
direct address of
ANY_NUM data type
or TIME data type
DIV
Division
(
Division (DIV
Literal, variable,
and DIV ()),
direct address of
ANY_NUM data type page 357
or TIME data type
GT
Comparison: >
(
Literal, variable,
direct address of
ANY_ELEM data
type
Compare on
"Greater Than"
(GT and GT ()),
page 359
GE
Comparison: >=
(
Literal, variable,
direct address of
ANY_ELEM data
type
Compare to
"Greater
than/Equal to"
(GE and GE ()),
page 360
EQ
Comparison: =
(
Literal, variable,
direct address of
ANY_ELEM data
type
Compare to
"EQual to"(EQ
and EQ ()),
page 361
NE
Comparison: <>
(
Literal, variable,
direct address of
ANY_ELEM data
type
Compare to "Not
Equal to" (NE
and NE ()),
page 362
LE
Comparison: <=
(
Literal, variable,
direct address of
ANY_ELEM data
type
Compare to
"Less
than/Equal to"
(LE and LE ()),
page 363
LT
Comparison: <
(
Literal, variable,
direct address of
ANY_ELEM data
type
Compare to
"Less Than"(LT
and LT ()),
page 364
33002204 12/2010
Instruction list IL
33002204 12/2010
Operator
Operator key
possible
modifier
possible operand
see also
JMP
Jump to tag
C, CN
TAG
Jump to label
(JMP, JMPC
and JMPCN),
page 365
CAL
Calling up a Function
Block or DFB
C, CN
FBNAME (item
name)
Call Function
Block/DFB
(CAL, CALC and
CALCN),
page 368
FUNCNA
ME
Performing a function
)
Editing on-hold
operations
Function call,
Literal, variable,
direct address (data page 379
type is dependent on
function)
Right
parenthesis ")",
page 370
333
Instruction list IL
Tag
At a Glance
Tags serve as destinations for Jumps (see page 365).
Properties
Tag properties:
Tags must always be the first element in a line.
z Tags must be unique throughout the project/DFB, and are not case-sensitive.
z Tags can be 32 characters long (max.).
z Tags must conform to the IEC name conventions.
z Tags are separated by a colon ":" from the following instruction.
z Tags are only permitted at the beginning of "Expressions", otherwise an
undefined value can be found in the battery.
z
Destinations
Possible destinations are:
z the first LD instruction of a FB/DFB call up with assignment of input parameters
(see start2),
z a normal LD instruction (see start1),
z a CAL instruction, which does not work with assignment of input parameters
(seestart3),
z a JMP instruction (see start4),
z the end of an instruction list (see start5).
334
33002204 12/2010
Instruction list IL
Example
start2: LD A
ST counter.CU
LD B
ST counter.R
LD C
ST counter.PV
CAL counter
JMPCN start4
start1: LD A
AND B
OR C
ST D
JMPC start3
LD A
ADD E
JMP start5
start3: CAL counter (
CU:=A
R:=B
PV:=C )
JMP start1
start4: JMPC start1
start5:
33002204 12/2010
335
Instruction list IL
Declaration (VAR...END_VAR)
At a Glance
The VAR instruction is used to declare the function blocks and DFBs used, and
direct addresses if they are not to be used with the default data type. VAR cannot
be used for declaring a variable in Concept. Declaring the variables may
conveniently be done via the Variables editor.
The END_VAR instruction marks the end of the declaration.
NOTE: The declaration of the FBs/DFBs and direct addresses applies only to the
current section. If the same FFB type or the same address are also used in another
section, the FFB type or the address must be declared again in this section.
Declaration of function blocks and DFBs
During declaration for each FB/DFB example, a unique example name is assigned.
The example name is used to mark the function block uniquely in a project. The
example name must be unique in the whole project; no distinction is made between
upper/lower case. The example name must correspond to the IEC Name
conventions, otherwise an error message will be displayed.
After specifying the example name, the function block type, e.g.CTD_DINT is
specified.
In the case of function block types no data type is specified. It is determined by the
data type of the actual parameters. If all actual parameters consist of literals, a
suitable data type will be selected.
Any number of example names may be declared for an FB/DFB.
NOTE: The dialog Objects →Insert FFB provides you with a form for creating the
FB-/DFB declaration in a simple and speedy manner.
NOTE: In contrast to grafic programming languages (FBD, LD), it is possible to call
up multiple calls in FB/DFB examples within IL.
Example
Declaration of function blocks and DFBs
336
33002204 12/2010
Instruction list IL
Declaration of direct addresses
In the case of this declaration, every direct address used whose data type does not
correspond to the default data type will be assigned the required data type (see also
Default data types of direct addresses (see page 328)).
Example
Declaration of direct addresses
VAR
AT %QW1 : WORD ;
AT %IW15 : UINT ;
AT %ID45 : DINT ;
AT %QD4 : TIME ;
END_VAR
33002204 12/2010
337
Instruction list IL
Comment
Description
Within the IL Editor, comments always start with the string (* and end in the string
*). Any comments may be entered between these two strings. Comments are shown
in colors.
NOTE: In accordance with IEC 1131-1, comments are only permissible at the end
of a line. However, if you wish to place theses elsewhere, you can do this by using
Options →Preferences →IEC Extensions →Allow comments anywhere in
text (IL).
NOTE: In accordance with IEC 1131-1, nested comments are not permissible.
However, if you wish to place theses elsewhere, you can do this by using Options
→Preferences →IEC Extensions →Allow nested comments.
338
33002204 12/2010
Instruction list IL
10.3
IL instruction list operators
Overview
This section describes the IL instruction list operators.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
Load (LD and LDN)
340
Store (ST and STN)
341
Set (S)
342
Reset (R)
344
Boolean AND (AND, AND (), ANDN, ANDN ())
346
Boolean OR (OR, OR (), ORN, ORN ())
348
Boolean exclusive OR (XOR, XOR (), XORN, XORN ())
350
Invert (NOT)
352
Addition (ADD and ADD ())
353
Subtraction (SUB and SUB ())
354
Multiplication (MUL and MUL())
355
Division (DIV and DIV ())
357
Compare on "Greater Than" (GT and GT ())
359
Compare to "Greater than/Equal to" (GE and GE ())
360
Compare to "EQual to"(EQ and EQ ())
361
Compare to "Not Equal to" (NE and NE ())
362
Compare to "Less than/Equal to" (LE and LE ())
363
Compare to "Less Than"(LT and LT ())
364
Jump to label (JMP, JMPC and JMPCN)
365
Call Function Block/DFB (CAL, CALC and CALCN)
368
FUNCNAME
369
Right parenthesis ")"
370
339
Instruction list IL
Load (LD and LDN)
LD Description
With LD the value of the Operands is downloaded into the accumulator. The data
width of the accumulator adapts itself automatically to the data type of the operand.
This also applies to derived datatypes.
Example LD
Example LD
Operation
Description
LD A
The value of "A" is downloaded onto the accu.
ADD B
The accu contents are added to the value of "B".
ST E
The result is saved in "E".
LDN Description
The downloaded operand can be negated with the Modifier N (only if the Operand
is of data type ANY_BIT).
LDN Example
LDN Example
340
Operation
Description
LDN A
The value of "A" is inverted and downloaded onto the accu.
ADD B
The accu contents are added to the value of "B".
ST E
The result is saved in "E".
33002204 12/2010
Instruction list IL
Store (ST and STN)
ST Description
With ST the current value of the accu is saved in the operand. The data type of the
operand must therefore agree with the "data type" of the accu.
Depending on whether an LD follows after ST or not, calculation proceeds with the
"old" result.
ST Example
ST Example
Operation
Description
LD A
The value of "A" is downloaded onto the accu.
ADD B
The accu contents are added to the value of "B".
ST E
The result is saved in "E".
ADD B
Afterwards the value of "E" (current accu contents) is added to the value
of "B" again
ST F
The result is saved in "F".
LD X
The value of "X" is now downloaded onto the accu.
SUB 3
3 is subtracted from the accu contents.
ST Y
The result is saved in "Y".
STN Description
The operand to be saved can be negated with the N modifier (only if the operand is
on the ANY_BIT data type).
STN Example
ST Example
33002204 12/2010
Operation
Description
LD A
The value of "A" is downloaded onto the accu.
ADD B
The accu contents are added to the value of "B".
STN E
The result is inverted and saved in "E".
341
Instruction list IL
Set (S)
Description
S sets the operand to "1" when the current content of the accu is a Boolean "1".
Example S
Example S
Command
Description
LD A
The value of "A" is loaded into the accu.
S OUT
If the content of the accu (the value of A) is "1", "OUT" is set to "1".
Use
Usually this operator is used together with the Reset operator R (flip flop) as a pair.
Example RS flip flop
The example shows an RS flip flop (Reset dominant).
342
Command
Description
LD A
The value of "A" is loaded into the accu.
S OUT
If the content of the accu (the value of "A") is "1", "OUT" is set to "1".
LD C
The value of "C" is loaded into the accu.
R OUT
If the content of the accu (the value of "C") is "1", "OUT" is set to "0".
33002204 12/2010
Instruction list IL
Start behavior
The start behavior of PLC’s is divided into cold and warm starts.
z Cold Start
Following a cold start (loading the program with Online →Download) all
variables are set (independently of their type) to "0" or, if available, to their initial
value.
z Warm Start
On a warm start (stopping and starting of the program or Online →Download
changes) different start behavior applies for located variables/direct addresses
and unlocated variables:
z Located variables/direct addresses
During a warm start the located variable/direct address, is set to "0", or to its
initial value if present, via the set instruction.
z Unlocated variables
On a warm start the unlocated variable, set via the set instruction, maintains
its present value (storing behavior).
NOTE: Should a buffered located variable/direct address be required, please use
the RS or SR function blocks from the block library IEC.
33002204 12/2010
343
Instruction list IL
Reset (R)
Description
R sets the operand to "0" when the current content of the accu is a Boolean "1".
Example R
Example R
Command
Description
LD A
The value of "A" is loaded into the accu.
R OUT
If the content of the accu (the value of "A") is "1", "OUT" is set to "0".
Use
Usually this operator is used together with the Set operator S (flip flop) as a pair.
Example SR flip flop
The example shows an SR flip flop (Set dominant).
344
Command
Description
LD A
The value of "A" is loaded into the accu.
R OUT
If the content of the accu (the value of "A") is "1", "OUT" is set to "0".
LD C
The value of "C" is loaded into the accu.
S OUT
If the content of the accu (the value of "C") is "1", "OUT" is set to "1".
33002204 12/2010
Instruction list IL
Start behavior
PLC start behavior is divided into cold and warm starts:
z Cold Start
Following a cold start (loading the program with Online →Download) all
variables are set (independently of their type) to "0" or, if available, to their initial
value.
z Warm Start
On a warm start (stopping and starting of the program or Online →Download
changes) different start behavior applies for located variables/direct addresses
and unlocated variables:
z Located variables/direct addresses
On a warm start the located variable/direct address, is set to "0", or to its initial
value if present, via the reset instruction.
z Unlocated variables
On a warm start the unlocated variable, set via the reset instruction, maintains
its present value (storing behavior).
NOTE: Should a buffered located variable/direct address be required, please use
the RS or SR function blocks from the block library IEC.
33002204 12/2010
345
Instruction list IL
Boolean AND (AND, AND (), ANDN, ANDN ())
AND Description
With AND a logical AND link occurs between the accu contents and the operand.
For the data types BYTE and WORD the link is made by bit.
AND Example
In the example D is "1", if A, B and C are "1".
Operation
Description
LD A
The contents of "A" are downloaded onto the accu.
AND B
The accu contents are AND-linked with the contents of "B".
AND C
The accu contents (result of the AND link from "A" and "B") are ANDlinked with the contents of "C".
ST D
The link result is saved in "D".
AND () Description
AND can be used with the "(" left bracket modifier.
AND () Example
In the example D is "1", if A is "1" and B or C are "1".
Operation
Description
LD A
The contents of "A" are downloaded onto the accu.
AND (
The AND link is deferred until the right bracket is reached.
LD B
The contents of "B" are downloaded onto the accu.
OR C
The contents of "C" are OR-linked with the accu contents.
)
The deferred AND link is solved. The accu contents (result of the OR
link from "B" and "C") are AND-linked with the contents of "A".
ST D
The link result is saved in "D".
ANDN Description
AND can be used with the N modifier.
346
33002204 12/2010
Instruction list IL
ANDN Example
In the example D is "1", if A is "1" and B and C are "0".
Operation
Description
LD A
The contents of "A" are downloaded onto the accu.
ANDN B
The contents of "B" are inverted and AND-linked with the accu contents.
ANDN C
The contents of "C" are inverted and AND-linked with the accu contents
(Result of the AND link from "A" and "B").
ST D
The link result is saved in "D".
ANDN () Description
AND can be used with the N modifier and the "(" left bracket modifier.
ANDN () Example
In the example D is "1", if A is "1", B is "0" and C is "1".
33002204 12/2010
Operation
Description
LD A
The contents of "A" are downloaded onto the accu.
ANDN (
The AND link is deferred until the right bracket is reached.
LD B
The contents of "B" are downloaded onto the accu.
ORN C
The contents of "C" are inverted and OR-linked with the accu contents.
)
The deferred AND link is solved. The contents of "A" are inverted and
AND-linked with the accu contents (Result of the OR link from "B" and
"C").
ST D
The link result is saved in "D".
347
Instruction list IL
Boolean OR (OR, OR (), ORN, ORN ())
OR Description
With OR a logical OR link occurs between the accu contents and the operand.
For the data types BYTE and WORD the link is made by bit.
OR Example
In the example D is "1", if A or B is "1" and C is "1".
Operation
Description
LD A
The contents of "A" are downloaded onto the accu.
OR B
The accu contents are OR-linked with the contents of "B".
AND C
The accu contents (result of the AND link from "A" and "B") are ANDlinked.
ST D
The link result is saved in "D".
OR () Description
OR can be used with the "(" left bracket modifier.
OR () Example
In the example D is "1", if A is "1" or B and C are "1".
Operation
Description
LD A
The contents of "A" are downloaded onto the accu.
OR (
The OR link is deferred until the right bracket is reached.
LD B
The contents of "B" are downloaded onto the accu.
AND C
The contents of "C" are AND-linked with the accu contents.
)
The deferred OR link is solved. The accu contents (Result of the AND
link from "B" and "C") are OR linked with the contents of "A".
ST D
The link result is saved in "D".
ORN Description
ORN can be used with the N modifier.
348
33002204 12/2010
Instruction list IL
ORN Example
In the example D is "1", if A is "1" or B is "0" and C is "1".
Operation
Description
LD A
The contents of "A" are downloaded onto the accu.
ORN B
The contents of "B" are inverted and OR linked with the accu contents.
AND C
The contents of "C" are AND linked with the accu contents (result of the
OR link from "A" and "B").
ST D
The link result is saved in "D".
ORN () Description
ORN can be used with the N modifier and the "(" left bracket modifier.
ORN () Example
In the example D is "1", if A is "1" or B or C are "0".
33002204 12/2010
Operation
Description
LD A
The contents of "A" are downloaded onto the accu.
ORN (
The OR link is deferred until the right bracket is reached.
LD B
The contents of "B" are downloaded onto the accu.
AND C
The contents of "C" are AND-linked with the accu contents.
)
The deferred OR link is solved. The accu contents (result of the AND
link from "B" and "C") are OR linked with the contents of "A".
ST D
The link result is saved in "D".
349
Instruction list IL
Boolean exclusive OR (XOR, XOR (), XORN, XORN ())
XOR description
With XOR, a logical exclusive OR link is made between the accu contents and the
operand.
If more than two operands are linked the result is "1" for an odd number of 1
conditions and "0" for an even number of 1 conditions.
For the data types BYTE and WORD the link is made by bit.
XOR example
In the example, D is "1" if A or B is "1". If A and B have the same status (both "0" or
both "1"), D is "0".
Operation
Description
LD A
The contents of "A" are downloaded onto the accu.
XOR B
The accu contents are linked with the contents of the "B" exclusive OR.
ST D
The equation result is saved in "D".
XOR () description
XOR can be used with the "(" left bracket modifier.
XOR () example
In the example, D is "1" if A or the AND link from B and C is "1". If A and the result
of the AND link have the same status (both "0" or both "1"), D is "0".
Operation
Description
LD A
The contents of "A" are downloaded onto the accu.
XOR (
The exclusive OR link is deferred until the right bracket is reached.
LD B
The contents of "B" are downloaded onto the accu.
AND C
The contents of "C" are AND-linked with the accu contents.
)
The reset exclusive OR link is performed. The accu contents (result of
the AND link from "B" and "C") are exclusive OR-linked with the
contents of "A".
ST D
The equation result is saved in "D".
XORN description
XOR can be used with the N modifier.
350
33002204 12/2010
Instruction list IL
XORN example
In the example, D is "1" if A and B have the same contents (both "1" or both "0'). If
A and B do not have the same status, D is "0".
Operation
Description
LD A
The contents of "A" are downloaded onto the accu.
XORN B
The contents of "B" are inverted and exclusive OR-linked with the accu
contents.
ST D
The equation result is saved in "D".
XORN () description
XORN can be used with the "(" left bracket and N modifiers.
XORN () example
In the example, D is "1" if A and the AND link from B and C have the same contents
(both "1" or both "0'). If A and B and the AND link from B and C do not have the same
status, D is "0".
33002204 12/2010
Operation
Description
LD A
The contents of "A" are downloaded onto the accu.
XORN (
The exclusive OR link is deferred until the right bracket is reached.
LD B
The contents of "B" are downloaded onto the accu.
AND C
The contents of "C" are AND-linked with the accu contents.
)
The reset exclusive OR link is performed. The accu contents (result of
the AND link from "B" and "C") are exclusive OR-linked with the
contents of "A".
ST D
The equation result is saved in "D".
351
Instruction list IL
Invert (NOT)
NOT Description
The accumulator content is inverted with NOT.
NOT can only be used with Boolean data types (BIT, BYTE, WORD).
NOTE: This operator does not conform to IEC 61131-1.
Example NOT
Example NOT
352
Operation
Description
LD A
The contents of "A" are downloaded onto the accumulator.
NOT
The accumulator content is inverted.
ST B
The result is saved in "B".
33002204 12/2010
Instruction list IL
Addition (ADD and ADD ())
ADD Description
With ADD the value of the operand is added to the accu contents.
ADD Example
The example corresponds to the formula D = A + B + C
Operation
Description
LD A
The value of "A" is downloaded onto the accu.
ADD B
The accu contents are added to the value of "B".
ADD C
The accu contents (sum of "A"+"B") are added to the value of "C".
ST D
The result is saved in "D".
ADD () Description
ADD can be used with the "(" left bracket modifier.
ADD () Example
The example corresponds to the formula D = A + (B - C)
33002204 12/2010
Operation
Description
LD A
The value of "A" is downloaded onto the accu.
ADD (
The addition is deferred until the right bracket is reached.
LD B
The value of "B" is downloaded onto the accu.
SUB C
The value of "C" is subtracted from the accu contents.
)
The deferred addition is solved. The accu contents (result of "B"-"C")
are added to the value of "A".
ST D
The result is saved in "D".
353
Instruction list IL
Subtraction (SUB and SUB ())
SUB Description
With SUB the value of an operand is subtracted from the accu contents.
SUB Example
The example corresponds to the formula D = A - B - C
Operation
Description
LD A
The value of "A" is downloaded onto the accu.
SUB B
The value of "B" is subtracted from the accu contents.
SUB C
The value of "C" is subtracted from the accu contents (result of "A"-"B").
ST D
The result is saved in "D".
Description SUB ()
SUB can be used with the "(" left bracket modifier.
Example SUB ()
The example corresponds to the formula D = A - (B - C)
354
Operation
Description
LD A
The value of "A" is downloaded onto the accu.
SUB (
The subtraction is reset until the right bracket is reached.
LD B
The value of "B" is downloaded onto the accu.
SUB C
The value of "C" is subtracted from the accu contents.
)
The reset subtraction is performed. The accu contents (result of "B""C") are subtracted from the value of "A".
ST D
The result is saved in "D".
33002204 12/2010
Instruction list IL
Multiplication (MUL and MUL())
MUL Description
With MUL the accu contents are multiplied by the value of an operand.
MUL Example
The example corresponds to the formula D = A x B x C
Operation
Description
LD A
The value of "A" is downloaded onto the accu.
MUL B
The accu contents are multiplied by the value of "B".
MUL C
The accu contents (Result of "A"x"B") are multiplied by the value of "C".
ST D
The result is saved in "D".
Multiplication of TIME values
Normally the operand and the current accu contents must be of the same data type.
The TIME data type in relation to MUL is an exception. In this case the accu content
of data type TIME can be used together with an operand of data type ANY_NUM.
After the execution of this instruction list the accu contents have, in this case, the
data type TIME.
Example MUL with TIME values
The example corresponds to the formula t1 = t2 x i4.
Operation
Description
LD t2
The value of the time variables "t2" are downloaded onto the accu.
MUL i4
The accu contents are multiplied by the value of the integer variable
"i4".
ST t1
The result is saved in the time variable "t1".
Description MUL ()
MUL can be used with the "(" left bracket modifier.
33002204 12/2010
355
Instruction list IL
Example MUL ()
The example corresponds to the formula D = A x (B - C)
356
Operation
Description
LD A
The value of "A" is downloaded onto the accu.
MUL (
The multiplication is reset until the right bracket is reached.
LD B
The value of "B" is downloaded onto the accu.
SUB C
The value of "C" is subtracted from the accu contents.
)
The reset multiplication is performed. The accu contents (result of "B""C") are multiplied by the value of "A".
ST D
The result is saved in "D".
33002204 12/2010
Instruction list IL
Division (DIV and DIV ())
DIV Description
With DIV the accu contents are divided by the value of an operand.
DIV example
The example corresponds to the formula D = A / B / C.
Operation
Description
LD A
The value of "A" is downloaded onto the accu.
DIV B
The accu contents are divided by the value of "B".
DIV C
The accu contents (result of "A"/"B") are divided by the value of "C".
ST D
The result is saved in "D".
Division of TIME values
Normally the operand and the current accu contents must be of the same data type.
One exception is the data type TIME in connection with DIV. In this case the accu
contents of data type TIME can be processed with an operand of data type
ANY_NUM. After the execution of this instruction list the accu contents have, in this
case, the data type TIME.
Example MUL with TIME values
The example corresponds to the formula t1 = t2 / i4.
Operation
Description
LD t2
The value of the time variables "t2" is downloaded onto the accu.
DIV i4
The accu contents are divided by the value of the integer variable "i4".
ST t1
The result is saved in the time variable "t1".
DIV () Description
DIV can be used with the "(" left bracket modifier.
33002204 12/2010
357
Instruction list IL
DIV () Example
The example corresponds to the formula D = A / (B - C)
358
Operation
Description
LD A
The value of "A" is downloaded onto the accu.
DIV (
The division is reset until it the right bracket is reached.
LD B
The value of "B" is downloaded onto the accu.
SUB C
The value of "C" is subtracted from the accu contents.
)
The reset division is performed. The value of "A" is divided by the accu
contents (result of "B"-"C").
ST D
The result is saved in "D".
33002204 12/2010
Instruction list IL
Compare on "Greater Than" (GT and GT ())
Description GT
With GT the accu contents is compared with the operand contents. If the accu
contents is greater than the operand contents, the result is a boolean "1". If the accu
contents is less than or equal to the operand contents, the result is a boolean "0".
Example GT
Example GT
Command
Description
LD A
The value of "A" is loaded into the accu.
GT 10
The accu content is compared with the value ‘’0’’.
ST D
If the value of ‘’A’’ was less than ‘’10’’ (or equal ‘’10’’), the value ‘’0’’ is
saved in ‘’D’’.
If the value of ‘’A’’ was greater than ‘’10’’, the value ‘’1’’ is saved in ‘’D’’.
Description GT ()
GT can be used witht the modifier left bracket "(".
Examplel GT ()
Example GT ()
33002204 12/2010
Command
Description
LD A
The value of "A" is loaded into the accu.
GT (
The comparison is deferred until the right bracket has been reached.
LD B
The value of "B" is loaded into the accu.
SUB C
The value of "C" is subtracted from the accu content.
)
The deferred comparison is now carried out. The value of "A" is
compared with the accu contents (result of "B"-"C").
ST D
If the value of "A" was less than "B"-"C" (or equal "B"-"C"), the value "0"
is saved in "D".
If the value of ‘’A’’ was greater than "B"-"C", the value ‘’1’’ is saved in
‘’D’’.
359
Instruction list IL
Compare to "Greater than/Equal to" (GE and GE ())
Description GE
With GE the accu contents is compared with the operand contents. If the accu
contents is greater than or equal to the operand contents, the result is a Boolean "1".
If the accu contents is less than the operand contents, the result is a Boolean "0".
GE example
E.g. GE
Command
Description
LD A
The value of "A" is loaded into the accu.
GE 10
The accu content is compared with the value ‘’10’’.
ST D
If the value of ‘’A’’ was less than ‘’10’’, the value ‘’0’’ is saved in ‘’D’’.
If the value of ‘’A’’ was equal to or greater than ‘’10’’, the value ‘’1’’ is
saved in ‘’D’’.
Description GT ()
GE can be used with the modifier left bracket "(".
GE () example
GE () example
360
Command
Description
LD A
The value of "A" is loaded into the accu.
GE (
The comparison is deferred until the right bracket has been reached.
LD B
The value of "B" is loaded into the accu.
SUB C
The value of "C" is subtracted from the accu content.
)
The deferred comparison is now carried out. The value of "A" is
compared with the accu contents (result of "B"-"C").
ST D
If the value of ‘’A’’ was less than "B"-"C", the value ‘’0’’ is saved in ‘’D’’.
If the value of ‘’A’’ was equal to or greater than ‘’B’’ – "C", the value ‘’1’’
is saved in ‘’D’’.
33002204 12/2010
Instruction list IL
Compare to "EQual to"(EQ and EQ ())
EQ description
With EQ the accu contents are compared with the operand contents. If the accu
contents are equal to the operand contents, the result is a Boolean "1". If the accu
contents are not equal to the operand contents, the result is a Boolean "0".
EQ example
EQ example
Command
Description
LD A
The value of "A" is loaded into the accu.
EQ 10
The accu contents are compared with the value ‘’10’’.
ST D
If the value of ‘’A’’ was not equal to ‘’10’’, the value ‘’0’’ is saved in ‘’D’’.
If the value of ‘’A’’ was equal to ‘’10’’, the value ‘’1’’ is saved in ‘’D’’.
Description EQ ()
EQ can be used with the modifier left bracket "(".
EQ () example
EQ () example
33002204 12/2010
Command
Description
LD A
The value of "A" is loaded into the accu.
EQ (
The comparison is deferred until the right bracket has been reached.
LD B
The value of "B" is loaded into the accu.
SUB C
The value of "C" is subtracted from the accu content.
)
The deferred comparison is now carried out. The value of "A" is
compared with the accu contents (result of "B"-"C").
ST D
If the value of ‘’A’’ was not equal to "B"-"C", the value ‘’0’’ is saved in
‘’D’’.
If the value of ‘’A’’ was equal to "B"-"C", the value ‘’1’’ is saved in ‘’D’’.
361
Instruction list IL
Compare to "Not Equal to" (NE and NE ())
NE description
With NE the accu contents are compared with the operand contents. If the accu
contents are not equal to the operand contents, the result is a Boolean "1". If the
accu contents are equal to the operand contents, the result is a Boolean "0".
NE example
NE example
Command
Description
LD A
The value of "A" is loaded into the accu.
NE 10
The accu contents are compared with the value ‘’10’’.
ST D
If the value of ‘’A’’ was equal to ‘’10’’, the value ‘’0’’ is saved in ‘’D’’.
If the value of ‘’A’’ was not equal to ‘’10’’, the value ‘’1’’ is saved in ‘’D’’.
Description NE ()
NE can be used with the modifier left bracket "(".
NE () example
NE () example
362
Command
Description
LD A
The value of "A" is loaded into the accu.
NE (
The comparison is deferred until the right bracket has been reached..
LD B
The value of "B" is loaded into the accu.
SUB C
The value of "C" is subtracted from the accu content.
)
The deferred comparison is now carried out. The value of "A" is
compared with the accu contents (result of "B"-"C").
ST D
If the value of ‘’A’’ was equal to "B"-"C", the value ‘’0’’ is saved in ‘’D’’.
If the value of ‘’A’’ was not equal to "B"-"C", the value ‘’1’’ is saved in
‘’D’’.
33002204 12/2010
Instruction list IL
Compare to "Less than/Equal to" (LE and LE ())
Description
With LE the accu contents are compared with the operand contents. If the accu
contents are less than or equal to the operand contents, the result is a Boolean "1".
If the accu contents are greater than the operand contents, the result is a Boolean
"0".
LE example
LE example
Command
Description
LD A
The value of "A" is loaded into the accu.
LE 10
The accu contents are compared with the value ‘’10’’.
ST D
If the value of ‘’A’’ was greater than ‘’10’’, the value ‘’0’’ is saved in ‘’D’’.
If the value of ‘’A’’ was less than or equal to ‘’10’’, the value ‘’1’’ is saved
in ‘’D’’.
Description LE ()
LE can be used with the modifier left bracket "(".
LE () example
LE () example
33002204 12/2010
Command
Description
LD A
The value of "A" is loaded into the accu.
LE (
The comparison is deferred until the right bracket has been reached.
LD B
The value of "B" is loaded into the accu.
SUB C
The value of "C" is subtracted from the accu content.
)
The deferred comparison is now carried out. The value of "A" is
compared with the accu contents (result of "B"-"C").
ST D
If the value of ‘’A’’ was greater than "B"-"C", the value ‘’0’’ is saved in
‘’D’’.
If the value of "A" was less than "B"-"C" (or equal to "B"-"C"), the value
"1" is saved in "D".
363
Instruction list IL
Compare to "Less Than"(LT and LT ())
LT description
With LT the accu contents are compared with the operand contents. If the accu
contents are less than the operand contents, the result is a Boolean "1". If the accu
contents are greater than or equal to the operand contents, the result is a Boolean
"0".
LT example
LT example
Command
Description
LD A
The value of "A" is loaded into the accu.
LT 10
The accu contents are compared with the value ‘’10’’.
ST D
If the value of ‘’A’’ was greater than ‘’10’’ (or equal to ‘’10’’), the value
‘’0’’ is saved in ‘’D’’.
If the value of ‘’A’’ was less than ‘’10’’, the value ‘’1’’ is saved in ‘’D’’.
Description LT ()
LT can be used with the modifier left bracket "(".
LT () example
LT () example
364
Command
Description
LD A
The value of "A" is loaded into the accu.
LT(
The comparison is deferred until the right bracket has been reached.
LD B
The value of "B" is loaded into the accu.
SUB C
The value of "C" is subtracted from the accu content.
)
The deferred comparison is now carried out. The value of "A" is
compared with the accu contents (result of "B"-"C").
ST D
If the value of ‘’A’’ was greater than ‘’B’’-"C" (or equal to ‘’B’’-"C"), the
value ‘’0’’ is saved in ‘’D’’.
If the value of ‘’A’’ was less than "B"-"C", the value ‘’1’’ is saved in ‘’D’’.
33002204 12/2010
Instruction list IL
Jump to label (JMP, JMPC and JMPCN)
JMP Description
With JMP a conditional or unconditional jump to a label is solved.
The label is used as an address and identifies the destination instruction. The
destination instruction can be above or below the jump instruction. A label must
always be the first element of a line. The label (max. 32 characters) must not be
duplicated anywhere else in the project and there is no case sensitivity. The labels
are separated by a colon ":" from the following instruction. Labels should only be at
the beginning of "expressions", since otherwise an undefined value can be in the
accu.
JMP Example
In the example an unconditional jump to the label "start" is solved.
Operation
start:
Description
LD A
The value of "A" is downloaded onto the accu.
AND B
Logical AND link between the accu contents and the
contents of "B".
OR C
Logical OR link between the accu contents and the contents
of "C".
ST D
The result of the links is saved in "D".
JMP start
Independent of the accu contents (value of "D") a jump to
label "start" is solved.
JMPC and JMPCN Description
JMP can be used with the modifiers C and CN (only if the operand is of data type
ANY_BIT).
33002204 12/2010
365
Instruction list IL
JMPC Example
In the example a conditional jump (with "1") to label "start" is solved.
Operation
start:
Description
LD A
The value of "A" is downloaded onto the accu.
AND B
Logical AND link between the accu contents and the
contents of "B".
OR C
Logical OR link between the accu contents and the contents
of "C".
ST D
The result of the links is saved in "D".
JMPC start
The jump is only solved if the accu contents (value of "D")
has the value "1".
JMPCN Example
In the example a conditional jump (by "0") to label "start" is solved.
Operation
start:
Description
LD A
The value of "A" is downloaded onto the accu.
AND B
Logical AND link between the accu contents and the
contents of "B".
OR C
Logical OR link between the accu contents and the contents
of "C".
ST D
JMPCN start
366
The result of the links is saved in "D".
The jump is only solved if the accu contents (value of "D")
has the value "0".
33002204 12/2010
Instruction list IL
Addresses
Possible addresses are:
z each LD instruction (see start1)
z each CAL instruction (see start2)
z the end of an instruction list (see start3)
Jumps cannot be made into other sections.
Example for possible addresses:
Operation
Description
VAR
Timer_1 : TON;
END_VAR
Declaration of the
function blocks TON.
LD IN1_BOOL
ST OT1_BOOL
JMPC start1
Jump to start1, if
OT1_BOOL = 1
LD IN1_BOOL
AND IN2_BOOL
JMPCN start2
Jump to start2, if
OT1_BOOL = 0
ST OT2_BOOL
start1: LD IN1_INT
ADD IN2_INT
ST OT1_INT
JMP start3
Unconditional jump after
start3, JMPC/JMPCN is
not allowed here as the
accu contents are not of
type BOOL.
start2: CAL Timer_1 (IN:=IN3_BOOL, PT:=t#6s)
LD Timer_1.ET
ST OT1_TIME
LD Timer_1.Q
ST OT3_BOOL
start3
33002204 12/2010
367
Instruction list IL
Call Function Block/DFB (CAL, CALC and CALCN)
CAL Description
With CAL a function block or a DFB is conditionally or unconditionally called.
CALC and CALCN Description
CAL can be used with the Modifiers C and CN (only if the operand is of data type
ANY_BIT).
Use of Function Blocks and DFBs
Use of Function Blocks and DFBs, page 372
368
33002204 12/2010
Instruction list IL
FUNCNAME
Description
A function is performed with the function name (see Function call, page 379).
33002204 12/2010
369
Instruction list IL
Right parenthesis ")"
At a Glance
With the right parenthesis ")" the editing of the reset operator is started. The number
of right parenthesis operations must be equal to the number of left bracket modifiers.
Brackets can be nested.
Example
In the example E will be "1", if C and/or D is "1", just as A and B are "1".
LD A
AND B
AND( C
OR D
)
ST E
370
33002204 12/2010
Instruction list IL
10.4
Call up of functions, Function Blocks (EFBs) and
Derived Function Blocks (DFBs)
Overview
This section describes the call up of functions, Function Blocks (EFBs) and Derived
Function Blocks (DFBs).
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
Use of Function Blocks and DFBs
372
Invoking a Function Block/DFB
374
Function call
379
371
Instruction list IL
Use of Function Blocks and DFBs
Use of Function Blocks and DFBs
Function blocks are provided by Concept in the form of libraries. The function block
logic is created in C++ programming language and cannot be altered in the IL Editor.
The names of the available function blocks can be taken from the block libraries.
DFBs are function blocks, which have been defined in Concept-DFB. There is no
difference between functions and function blocks for DFBs. They are always
handled as function blocks regardless of their internal structure.
The use of function blocks and DFBs consists of three parts in IL:
the declaration (see page 373),
z the function block/DFB invocation (see page 374),
z the use of the function block/DFB outputs (see page 373).
z
NOTE: The declaration of the function block/DFB invocation can take place
manually or you can create the block end and the assignment of the parameters
using the menu command Objects → Insert FFB.
Function Blocks with Limited Use
Use of the following EFBs from the DIAGNO block library is limited in IL (the function
blocks can be used, but the expanded diagnostic information cannot be evaluated):
z XACT, XACT_DIA,
z XDYN_DIA,
z XGRP_DIA,
z XLOCK,
z XPRE_DIA,
z XLOCK_DIA,
z XREA_DIA
Function Blocks with Limited Invocation
For EFBs which have one or more outputs with data type ANY but no inputs with
data type ANY (generic outputs/inputs), the block invocation can only take place in
compact form (see page 376). e.g. in the block library LIB984:
z GET_3X
z GET_4X
Unusable Function Blocks
Unusable Function Blocks:
z EFBs which use several registers with only the entry for the first register on the
input/output (e.g. MBP_MSTR from the COMM block library) cannot be used.
z EFBs, which contain outputs with input information (e.g. GET_BIT, R2T from the
LIB984 block library) cannot be used
372
33002204 12/2010
Instruction list IL
z
The following EFBs from the COMM block library cannot be used for the technical
reasons listed above:
z CREADREG
z CREAD_REG
z CWRITREG
z CWRITE_REG
z READREG
z READ_REG
z WRITEREG
z WRITE_REG
z MBP_MSTR
z
The following EFBs from the LIB984 block library cannot be used for the technical
reasons listed above:
z FIFO
z GET_BIT
z IEC_BMDI
z LIFO
z R2T
z SET_BIT
z SRCH
z T2T
Declaration
Before invoking the function block/DFBs, they must be declared using VAR and
END_VAR (see page 336).
Function Block/DFB Invocation
Invoking a Function Block/DFB, page 374
Use of the Function Block/DFB Outputs
The outputs of the function block/DFBs can always be used when a variable (read
only) can also be used.
33002204 12/2010
373
Instruction list IL
Invoking a Function Block/DFB
At a Glance
The invocation can be made in 4 forms:
using CAL with a list of the input parameters (see page 374),
z using CAL with a list of the input/output parameters (compact form)
(see page 376),
z using CAL and Load/Save the input parameters (see page 376),
z when using the input operators (see page 377).
z
NOTE: Even if the function block has no inputs or the input parameters are not to be
defined, the function block should be invoked (CAL EFB_XY ()) before the outputs
can be used. Otherwise the initial values for the outputs are given, i.e. "0".
NOTE: In IL, unlike the graphic programming languages (FBD, LD), FB/DFB
instances can be invoked multiple times.
CAL with a list of the input parameters
Function blocks/DFBs can be invoked using an instruction consisting of the CAL
instruction followed by the instance names for the FBs/DFBs and a list, in brackets,
of value assignments (current parameters) to formal parameters. The order of the
formal parameters in a function block invocation is not significant. The list of the
current parameters can be broken straight after a comma. It is not necessary for all
formal parameters to be assigned a value. If a formal parameter is not assigned a
value, the initial value defined in the variable editor is used when executing the
function block. If an initial value is not defined, the default value (0) is used.
NOTE: Inputs of type VARINOUT (see page 493) always have to be assigned a
value.
Using the CAL (..) instruction, setting the parameters for the function blocks/DFBs is
ended. Then no more values can be sent to the FB/DFB. Only the output values can
be read.
374
33002204 12/2010
Instruction list IL
Example
CAL with a list of the input parameters
or
Invocation of the function block in FBD.
33002204 12/2010
375
Instruction list IL
CAL with a list of the input/output parameters (compact form)
Block invocation and the assignments for the inputs/outputs are also possible in a
more compact form, which saves runtime:
VAR
CLOCK : SYSCLOCK ;
COUNT : CTU_DINT ;
END_VAR
CAL CLOCK () ;
CAL COUNT (CU:=CLOCK.CLK3, R:=%IX10, PV:=100, Q=>out)
CAL with Loading/Saving of Input Parameters
Function blocks/DFBs can be invoked using an instruction list, which consists of
loading the current parameters, followed by saving them in the formal parameters,
followed by the CAL instruction. The order in which the parameters are loaded and
saved is not significant. The list of the current parameters can be broken directly
after a comma. It is not necessary for all formal parameters to be assigned a value.
If a formal parameter is not assigned a value, the initial value defined in the variable
editor is used when executing the function block. If an initial value is not defined, the
default value (0) is used.
NOTE: Inputs of type VARINOUT (see page 493) always have to be assigned a
value.
Using the CAL FBNAME instruction, setting the parameters for the function
blocks/DFBs is ended. Then no more values can be sent to the FB/DFB. Only the
output values can be read.
Only load and save instructions for the current FB/DFBs to be configured are
allowed to be between the first load instruction for the current parameters and
invocation of the function block/DFBs. All other instructions are not allowed in this
position.
376
33002204 12/2010
Instruction list IL
Example
CAL with Loading/Saving of Input Parameters
Using the Input Operators
Function blocks can be called using an instruction list which consists of loading the
current parameters, followed by saving them in the formal parameters, followed by
an input operator. The order in which the parameters are loaded and saved is not
significant. The list of the current parameters can be broken directly after a comma.
It is not necessary for all formal parameters to be assigned a value. If a formal
parameter is not assigned a value, the initial value defined in the variable editor is
used when executing the function block. If an initial value is not defined, the default
value (0) is used.
NOTE: Inputs of type VARINOUT (see page 493) always have to be assigned a
value.
The possible input operators for the different function blocks can be taken from the
table. Other input operators are not available.
33002204 12/2010
Input operator
FB Type
S1, R
SR
S, R1
RS
CLK
R_TRIG
CLK
F_TRIG
CU, R, PV
CTU_INT, CTU_DINT, CTU_UINT, CTU_UDINT
CD, LD, PV
CTD_INT, CTD_DINT, CTD_UINT, CTD_UDINT
CU, CD, R, LD, PV
CTUD_INT, CTUD_DINT, CTUD_UINT, CTUD_UDINT
IN, PT
TP
IN, PT
TON
IN, PT
TOF
377
Instruction list IL
Using input operator invocation, setting the parameters for the function blocks is
ended. Then no more values can be sent to the FB. Only the output values can be
read.
Only load and save instructions for the current FB being configured are allowed to
be between the first load instruction for the current parameters and the input
operator for the function block. All other instructions are not allowed in this position.
Example
Using the Input Operators
378
33002204 12/2010
Instruction list IL
Function call
Use of functions
Functions are provided by Concept in the form of libraries. The logic of the functions
is created in the programming language C++ and cannot be changed in the IL editor.
You will find the names of the available functions in the block libraries.
Functions are called using an instruction list consisting of loading the first actual
parameter into the battery and the name of the function. If necessary, this will be
followed by a list of further actual parameters. The sequence in which the formal
parameters in a function call are enumerated is not significant. Immediately following
a comma, the list of the actual parameters may be wrapped. The result of the
function becomes the battery content after the function has been executed, and can
be saved using ST (see page 341) in an operand, or may directly be processed
further.
NOTE: The declaration of function calls may either be generated manually, or you
may generate the block rump and the allocation of the parameters using the menu
command Objects →Insert FFB.
The picture shows calling a function in IL.
The picture shows calling a function in FDP.
Functions which cannot be used
Functions having one or more outputs of data type ANY but no inputs of data type
ANY (generic outputs/inputs) cannot be used in IL.
33002204 12/2010
379
Instruction list IL
Calling a function with an input
If the function to be executed has only got one input, the name of the function is not
followed by a list of actual parameters.
Calling a function with multiple inputs
If the function to be executed has several inputs, there are two possibilities for
assigning the actual parameters.
z The name of the function is followed by a list of the actual parameters
z
The name of the function is followed by a list of the value assignments (actual
parameters) to the formal parameters.
Function calls including processing of the battery value
If the value to be processed is already in the battery, it is not necessary to use the
loading instruction.
LIMIT_REAL B,C
ST result
Function calls including further direct processing of the result
If the result is immediately to be processed further it is not necessary to include the
memory instruction.
LD A
LIMIT_REAL B,C
MUL E
380
33002204 12/2010
Instruction list IL
10.5
Syntax check and Code generation
Overview
This section describes the syntax check and the code generation with the IL
instruction list.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
Syntax Check
382
Code generation
384
381
Instruction list IL
Syntax Check
Introduction
A syntax check can be performed during the program/DFB creation with Project →
Analyze section.
Syntax Check Options
With the menu command Options →Preferences →IEC extensions... →IECextensions the syntax check options can be defined.
NOTE: The settings in this dialog are used in the project description (PRJ.DSK) and
in the Concept installations description (CONCEPT.DSK), i.e. they are valid for the
entire Concept installation.
If a project is opened, that was created using different settings (e.g. Allow nested
comments in the project and not in the actual Concept Installation), errors can occur
when opening the project.
Allow Case Insensitive Keywords
If the check box Allow case insensitive keywords is checked, upper and lower
case for all keywords is enabled.
Allow nested comments
If the check box Nested comments authorized is checked, nested comments can
be entered. There are no limits to the nesting depths.
Comments everywhere in the text permitted (IL)
If the check box Comments everywhere in the text permitted (IL) is checked,
comments can be placed anywhere in the IL section.
Additional Variable Names Permitted (IL)
If the check box Additional variable names permitted (IL) is checked, the use of
additional variable names (e.g. "S1" or "IN") is possible in IL. (These variables can
always be used in FBD, LD and ST.)
Allow Leading Digits in Identifiers
If the check box Allow leading digits in identifiers is checked, figures as the first
character of identifiers (i.e. variable names, step names, EFB names) are possible.
Identifiers, which consist solely of figures are, however, not authorized, they must
contain at least one letter.
382
33002204 12/2010
Instruction list IL
Unused Parameters Cause Warnings
The IEC 1131-3 permits functions and Function Blocks to be called up without
calling up the assignment of all the input parameters. These unused parameters are
implicitly assigned a 0, or they retain the value from the last call up (Function Blocks
only).
If in the menu command Options →Preferences →Analysis... →Analysis the
check box Unused parameters lead to warnings is checked, a list of these unused
parameters is displayed in the message window when generating the code.
33002204 12/2010
383
Instruction list IL
Code generation
At a Glance
The menu command Project →Options for code generation is used to define
options for code generation.
Fastest code (restricted check)
If the check box Fastest Code (restricted check) is activated, a runtime-optimized
code will be generated.
This runtime optimization is achieved with integer arithmetic (e.g. "+" or "-") with
simple process commands instead of EFB calls.
Process commands are much faster than EFB calls, but they generate no error
messages, such as e.g. Arithmetic or Array overrun. This option should only be used
if it has been ensured that the program is free of arithmetic errors.
Example: Fastest Code
LD in1
ADD 1
ST out1
If Fastest Code (restricted check) is selected, the addition "in1 + 1" is executed
with the process command "add". The code is now faster than if EFB ADD_INT had
been called up. However, no runtime error is generated if "in1" is 32767. In this case,
"out1" would overrun from 32767 to -32768!
Activate loop control
This check box activates a software watchdog for continuous loops.
If this check box is checked, with loops within IL and ST sections, it is tested whether
these loops are again exited within a certain time. The time authorized depends on
the manually defined watchdog time. The authorized time for all loops combined
constitutes 80% of the Hardware watchdog time. In this way triggering of the
hardware watchdog by endless loops is disabled. If a time consuming loop or an
endless loop is detected, processing of the affected section will stop, an entry in the
Event display will be generated and processing of the next section will begin. In the
next cycle, the segment will be re-processed until a time consuming loop or an
endless loop is detected once again, or until the segment is completed correctly.
NOTE: If the hardware watchdog stops the PLC when a time consuming loop or an
endless loop is detected, this option should not be activated. The hardware
watchdog itself is not switched off by this function.
384
33002204 12/2010
Instruction list IL
10.6
Online functions of the IL instruction list
Overview
This section describes the online functions of the IL instruction list.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
Animation
386
Monitoring field
389
385
Instruction list IL
Animation
At a Glance
There are two animation modes available in the IL and ST editor:
Animation of binary variables
z Animation of selected variables
z
Animation of binary variables
The animation of the selected objects is activated with the menu command Online
→Animate selection.
In this mode, the current signal status of binary values is shown in the editor window.
The animation of direct addresses and direct FB input/outputs is not possible.
Animation of selected variables
The dialog box for the display of the current signal status of selected variables is
activated with the menu command Online →View selected.
Furthermore, at least one variable, which can be animated, must be selected.
Variables and multi-element variables that can be selected are denoted by red,
green or yellow script.
Properties of the dialog box
The name of the selected variables or multi-element variables are shown in the
dialog box, with the data type and current value.
The dialog box is modeless, i.e. it remains open until it is closed or the animation is
terminated. If several text language sections are open and clicked on in this dialog
box, a dialog box is opened for each section. The name of the section is displayed
in the dialog box heading.
Color key
There are 12 different color schemes available for animation. An overview of the
color scheme and the meaning of each color can be found in the Online help (Tip:
Search the online help for the index reference "Colors").
Inserting several variables
The procedure for inserting several variables is as follows:
Step
386
Action
1
Select the desired variables or multi-element variables.
2
Accept this with Online →Animate selected in the dialog box.
33002204 12/2010
Instruction list IL
Inserting all variables
The procedure for inserting all the variables is as follows:
Step
Action
1
Select the whole section with CTRL+A.
2
Migrate all variables and multi-element variables of the dialog section with
Online →Animate selcted to the dialog box.
Altering column width
The procedure for altering the column width is as follows:
Step
Action
1
Position the mouse pointer on the right margin button.
Reaction: The mouse pointer changes its shape to .
2
Alter the column width by dragging with the left mouse button depressed.
Multi-element variables
With multi-element variables the display of the elements can be switched on or off.
33002204 12/2010
Action
Function
Click on symbol + or
key +
The next component level
When using the keyboard, the cursor
for the current line is shown. must remain on a + symbol.
Condition
Key x (number lock)
All component levels for the The cursor must remain on a + symbol.
current line are shown.
Click on symbol - or
key -
All component levels for the When using the keyboard, the cursor
must remain on a - symbol.
current line, which are
shown, are grayed out.
CTRL++
The display of the
components of the current
line is restored (Restoration
of display before the last
activation of -
The cursor must remain on a + symbol.
CTRL+x (number
lock)
All component levels of the
current multi-element
variables are shown.
The cursor must remain on an element
of a multi-element variable.
CTRL+-
All component levels of the
current multi-element
variables are grayed out.
The cursor must remain on an element
of a multi-element variable.
CTRL+end
to go to the end of the table
CTRL+Pos1
to go to the start of the table
387
Instruction list IL
Saving and restoring animation
With the menu command Save animation the settings (e.g. Position of monitoring
fields) of the current animation can be saved. After terminating this animation, the
animation can be restored with the same settings via the menu command Restore
animation.
NOTE: To avoid inconsistencies between the program on the PC and the PLC and
to also have the animation available in the next Concept sitting, the project must be
saved when quitting Concept
388
33002204 12/2010
Instruction list IL
Monitoring field
At a Glance
With the menu command Online →Selected in Inspect field a monitoring field can
be entered in the section. The current value of the assigned variables is shown in
this monitoring field.
Limitations
The generation of monitoring fields for direct addresses and direct FB input/outputs
(INST.Q) is not possible.
Display of multi-element variables
With multi-element variables, the value of the first element is shown.
If a view of more elements is desired, this can be defined in the dialog Settings for
monitoring field, which is called up by double clicking on the monitoring field.
Minimum and maximum values
In the dialog Settings for monitoring field, which can be called up with a double
click on the monitoring field, a minimum and maximum value can be defined for the
monitored variable. If the variable violates one of these thresholds, this will be
displayed in color in the monitoring field.
An overview of the color scheme and the meaning of each color can be found in the
Online help (Tip: Search the online help for the index reference "Colors").
Generating a monitoring field
The procedure for generating a monitoring field is as follows:
Step
33002204 12/2010
Action
1
Select a variable (e.g. double-click on variable).
2
Execute the menu command Online →Selected in Inspect field.
Reaction: The section animation is started (gray section background) and the
cursor symbol changes into box symbol.
3
Position the cursor to any position in the section and click with the left mouse
button.
Reaction: A monitoring field, consisting of variable name and value, is
generated for the selected variable on the chosen position.
389
Instruction list IL
10.7
Creating a program with the IL instruction list
Creating a program in the IL instruction list.
At a Glance
The following description contains an example of creating a program in IL instruction
list. The creation of a program in IL instruction list is organized into 2 main steps:
Step
Action
1
Generating a section (see page 390)
2
Creating the logic (see page 391)
Generating a section
The procedure for generating a section is as follows:
Step
1
390
Action
Using the menu command File →New section... and enter a section name.
Note: The section name (max. 32 characters) must be clear throughout the
project, so that there is no difference regarding case sensitivity. If the name
entered already exists, a warning is given and another name must be chosen.
The section name must correspond to the IEC name conventions, otherwise an
error message arises.
Note: In accordance with IEC1131-3, only letters are permitted as the first
character of names. Should numbers be required as the first character, however,
the menu command Options →Presettings →IEC expansions... →Enable
leading figures in identifiers .
33002204 12/2010
Instruction list IL
Creating the logic
The procedure for creating the logic is as follows:
Step
33002204 12/2010
Action
1
Declare the Function Block and DFBs, which are to be used, with assistance
from VAR…END_VAR.
Example:
VAR
RAMP_UP, RAMP_DOWN, RAMP_X : TON ;
COUNT : CTU_DINT ;
END_VAR
2
Declare the variables and their initial value in the Variable Editor.
3
Create the logic of the program.
Example:
LD A
SIN_REAL
MUL_REAL B,C
ST D
LD Y
AND X
JMPC endl
LD M
SIN_REAL
MUL_REAL N,O
ST P
JMP end2
end1: LD D
ST %QD4
end2: LD P
ST %QD5
4
save the section with the menu command Data file →Save project .
391
Instruction list IL
392
33002204 12/2010
Structured text ST
33002204 12/2010
Structured text ST
11
Overview
This Chapter describes the programming language structured text ST which
conforms to IEC 1131.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
11.1
General information about structured Text ST
11.2
Expressions
396
11.3
Operators of the programming language of structured ST text
402
11.4
Assign instructions
422
11.5
Call up of functions, Function Blocks (EFBs) and Derived
Function Blocks (DFBs)
441
11.6
Syntax check and code generation
448
11.7
Online functions of the ST programming language
451
11.8
Creating a program with the structured ST text
452
394
393
Structured text ST
11.1
General information about structured Text ST
General Information about the ST Structured Text
Introduction
With the programming language of structured text (ST), it is possible, for example,
to call up Function Blocks, perform functions and assignments, conditionally perform
instructions and repeat tasks.
Spell Check
Spelling is immediately checked when key words, separators and comments are
entered. If a key word, separator or comment is recognized, it is identified with a
color surround. If unauthorized key words (instructions or operators) are entered, it
is likewise identified in color.
IEC Conventions
The IEC 1131 does not permit the input of direct addresses in the usual Concept
form. To input direct addresses see Operands, page 397.
In accordance with IEC 113-3, key words must be entered in upper case. Should the
use of lower case letters be required, they can be enabled in the dialog box Options
→Preferences →IEC Extensions... →IEC expansions with the option Allow
case insensitive keywords.
Blank spaces and tabs have no influence upon the syntax and can be used freely.
Context help
With the right mouse button an object can be selected and at the same time a
context sensitive menu called up. Therefore, for example, with FFBs the right mouse
button can call up the associated block description.
Syntax Check
A syntax check can be performed during the program/DFB creation with Project →
Analyze section, see also Syntax Check, page 449.
Codegeneration
Using the Project →Code Generation Options menu command, you can define
options for code generation, see also Code generation, page 450.
394
33002204 12/2010
Structured text ST
Editing with the Keyboard
Normally editing in Concept is performed with the mouse, however it is also possible
with the keyboard (see also Short Cut Keys in the IL, ST and Data Type Editor,
page 834).
IEC Conformity
For a description of the IEC conformity of the ST programming language see IEC
conformity, page 849.
33002204 12/2010
395
Structured text ST
11.2
Expressions
Overview
This section contains an overview of the expressions in the programming language
of structured text ST.
expressions consists of operands and operators.
What's in this Section?
This section contains the following topics:
Topic
396
Page
Operands
397
Operators
399
33002204 12/2010
Structured text ST
Operands
At a Glance
An operand can be:
z a literal,
z a variable,
z a multi-element variable,
z an element of a multi-element variable,
z a function call up,
z a FB/DFB output or
z a direct address.
Access to the field variables
When accessing field variables (ARRAY), only literals and variables of ANY_INT
type are permitted in the index entry.
Example: Using field variables
var1[i] := 8 ;
var2.otto[4] := var3 ;
var4[1+i+j*5] := 4 ;
Type conversion
Data types, which are in an instruction of processing operands, must be identical.
Should operands of various types be processed, a type conversion must be
performed beforehand.
An exception is the data type TIME in conjunction with the arithmetic operators "*"
(multiplication) and "/" (division). With both these operators, an operand of TIME
data type can be processed together with an operand of ANY_NUM data type. The
result of this instruction has in this instance the data type TIME.
Example: Integer variable and real variable
In the example the integer variable i1 is converted into a real variable before being
added to the real variable r4.
r3 := r4 + SIN_REAL(INT_TO_REAL(i1)) ;
Example: Integer variable and time variable
In the example the time variable t2 is multiplied by the integer variable i4 and the
result is stored in the time variable t1.
t1 := t2 * i4 ;
33002204 12/2010
397
Structured text ST
Default data types of direct addresses
The following table shows the default data types of direct addresses:
Input
Output
Default data type
possible data type
%IX,%I
%QX,%Q
BOOL
BOOL
%IB
%QB
BYTE
BYTE
%IW
%QW
INT
INT, UINT, WORD
%ID
%QD
REAL
REAL, DINT, UDINT, TIME
Using other data types
Should other data types be assigned as default data types of a direct address, this
must be done through an explicit declaration (VAR…END_VAR (see page 426)).
VAR…END_VAR cannot be used in Concept for the declaration of variables. The
variable declaration is performed conveniently by using the Variable Editor
(see page 543).
398
33002204 12/2010
Structured text ST
Operators
Introduction
An operator is a symbol for:
z an arithmetic operation to be executed or
z a configured operation to be executed or
z the function call up.
Operators are generic, i.e. they are automatically matched with the operands data
type.
NOTE: Operators can be either entered manually or generated with assistance from
the menu Objects →Operators.
Expression Evaluation
The evaluation of an expression consists of applying the operators to the operands,
in the sequence, which is defined by the order of the operators rank (see table). The
operator with the highest rank in an expression is performed first, followed by the
operator with the next highest rank etc. until the evaluation is complete. Operators
with the same rank are performed from left to right, as they are written in the
expression. This sequence can be altered with the use of parentheses.
Table of Operators
ST programming language operators:
33002204 12/2010
Operator
Meaning
possible operand
Order of
rank
see also
()
Use of
parentheses:
Expression
1
(highest)
Use of
parentheses "()",
page 403
FUNCNA Function editing
(call up)
ME
(current
parameter
list)
Expression, literal, variable, 2
direct address of ANY data
type
Function
Invocation,
page 446
-
Negation
Expression, literal, variable, 3
direct address of
ANY_NUM data type
Negation (-),
page 406
NOT
Complement
Expression, literal, variable, 3
direct address of ANY_BIT
data type
Complement
formation (NOT),
page 407
399
Structured text ST
400
Operator
Meaning
possible operand
Order of
rank
see also
**
Exponentiation
Expression, literal, variable, 4
direct address of REAL data
type (basis), ANY_NUM
(exponent)
Exponentiation
(**), page 405
*
Multiplication
Expression, literal, variable, 5
direct address of
ANY_NUM data type or
TIME data type
Multiplication (*),
page 408
/
Division
Expression, literal, variable, 5
direct address of
ANY_NUM data type
Division (/),
page 409
MOD
Modulo
Expression, literal, variable, 5
direct address of ANY_INT
data type
Modulo (MOD),
page 410
+
Addition
Expression, literal, variable, 6
direct address of
ANY_NUM data type or
TIME data type
Addition (+),
page 411
-
Subtraction
Expression, literal, variable, 6
direct address of
ANY_NUM data type or
TIME data type
Subtraction (-),
page 412
<
Less-than
comparison
Expression, literal, variable, 7
direct address of
ANY_ELEM data type
Comparison with
"Less Than"(<),
page 417
>
Greater-than
comparison
Expression, literal, variable, 7
direct address of
ANY_ELEM data type
Comparison on
"Greater Than"
(>), page 413
<=
Less or equal to
comparison
Expression, literal, variable, 7
direct address of
ANY_ELEM data type
Comparison with
"Less than or
Equal to" (<=),
page 418
>=
Greater or equal
to comparison
Expression, literal, variable, 7
direct address of
ANY_ELEM data type
Comparison on
"Greater
than/Equal to"
(>=), page 414
=
Equality
Expression, literal, variable, 8
direct address of
ANY_ELEM data type
Comparison with
"EQual to" (=),
page 415
<>
Inequality
Expression, literal, variable, 8
direct address of
ANY_ELEM data type
Comparison with
"Not Equal to"
(<>), page 416
33002204 12/2010
Structured text ST
33002204 12/2010
Operator
Meaning
possible operand
Order of
rank
see also
&, AND
configured AND
Expression, literal, variable, 9
direct address of ANY_BIT
data type
Boolean AND
(AND or &),
page 419
XOR
Configured
exclusive OR
Expression, literal, variable, 10
direct address of ANY_BIT
data type
Boolean Exclusive
OR (XOR),
page 421
OR
Configured OR
Expression, literal, variable, 11
direct address of ANY_BIT (lowest)
data type
Boolean OR (OR),
page 420
401
Structured text ST
11.3
Operators of the programming language of
structured ST text
Overview
This section describes the operators of the programming language of structured ST
text.
What's in this Section?
This section contains the following topics:
Topic
402
Page
Use of parentheses "()"
403
FUNCNAME
404
Exponentiation (**)
405
Negation (-)
406
Complement formation (NOT)
407
Multiplication (*)
408
Division (/)
409
Modulo (MOD)
410
Addition (+)
411
Subtraction (-)
412
Comparison on "Greater Than" (>)
413
Comparison on "Greater than/Equal to" (>=)
414
Comparison with "EQual to" (=)
415
Comparison with "Not Equal to" (<>)
416
Comparison with "Less Than"(<)
417
Comparison with "Less than or Equal to" (<=)
418
Boolean AND (AND or &)
419
Boolean OR (OR)
420
Boolean Exclusive OR (XOR)
421
33002204 12/2010
Structured text ST
Use of parentheses "()"
Description
Brackets are used to alter the execution sequence of the operators.
Example of parentheses "()"
If the operands A, B, C, and D have the values "1", "2", "3", "and -4",
A+B-C*D
has the result 15 and
(A+B-C)*D
has the result 0.
33002204 12/2010
403
Structured text ST
FUNCNAME
Description
The function processing is used to perform functions (see Function Invocation,
page 446).
404
33002204 12/2010
Structured text ST
Exponentiation (**)
Description
For exponentiation "**" the value of the first operand (basis) is potentiated with that
of the second operand (exponent).
NOTE: Exponentiation operates in the ST programming languageand with a
resolution of 23 bits. For the graphic languages the exponentiation operates with a
resolution of 24 bits..
Example: Exponentiation "**"
In the example OUT will be"625.0", when IN1 is "5.0" and IN2 is "4.0".
OUT := IN1 ** IN2 ;
33002204 12/2010
405
Structured text ST
Negation (-)
Description
During negation "-" a sign reversal for the value of the operand takes place.
Example: Negation "-"
In the example OUT will be "-4", when IN1 is "4".
OUT := - IN1 ;
406
33002204 12/2010
Structured text ST
Complement formation (NOT)
Description
In NOT a bit by bit inversion of the operands takes place.
Example: NOT
In the example OUT will be"0011001100", when IN1 is "1100110011".
OUT := NOT IN1 ;
33002204 12/2010
407
Structured text ST
Multiplication (*)
Description
For multiplication "**" the value of the first operand is multiplied with that of the
second operand (exponent).
Example: Multiplication "*"
OUT := IN1 * IN2 ;
Multiplication of TIME values
Normally the data types of the operands to be processed must be identical to an
instruction. However, the multiplication forms an exception when combined with
data type TIME. In this case an operand with the datentype TIME combined with an
operanden of data type ANY_NUM can be processed. In this case the result of this
instruction has the data type TIME.
Example: Multiplication of TIME values
In the example the Time variable t2 is multiplied by the integer variables i4 and the
result is deposited in the t1 Time variables.
t1 := t2 * i4 ;
408
33002204 12/2010
Structured text ST
Division (/)
Description
For division "/" the value of the first operand is divided by that of the second operand
(exponent).
Example: Division "/"
OUT := IN1 / IN2 ;
Division of TIME values
Normally the data types of the operands to be processed must be identical to an
instruction. However the division forms an exception when combined with data type
TIME. In this case an operand with the data type TIME combined with an operand
of data type ANY_NUM can be processed. In this case the result of this instruction
has the data type TIME.
Example division of TIME values
In the example the Time variable t2 is divided by the integer variables i4 and the
result is deposited in the t1 Time variables.
t1 := t2 / i4 ;
33002204 12/2010
409
Structured text ST
Modulo (MOD)
Description
For MOD the value of the first operandis divided by that of the second operand and
the remainder of thedivision (Modulo) is displayed as the result.
Example: MOD
OUT := IN1 MOD IN2 ;
410
33002204 12/2010
Structured text ST
Addition (+)
Description
For the addition "+" the value of the first operand is added to that of the second
operand.
Example: Addition "+"
OUT := IN1 + IN2 ;
33002204 12/2010
411
Structured text ST
Subtraction (-)
Description
For the subtraction "-" the value of the second operand is subracted from that of the
first operand.
Example: Subtraction "-"
OUT := IN1 - IN2 ;
412
33002204 12/2010
Structured text ST
Comparison on "Greater Than" (>)
Description
With ">" the value of the first operand is compared with that of the second operand.
If the first operand is greater than the second, the result is a boolean "1". If the first
operand is less than or equal to the second, the result is a Boolean "0".
Example: Greater Than ">"
In the example "OUT" will be "1" if "IN1" is greater than "10" and "0", if "IN1" is less
than "0".
OUT := IN1 > 10 ;
33002204 12/2010
413
Structured text ST
Comparison on "Greater than/Equal to" (>=)
Description
With ">=" the value of the first operand is compared to that of the second operand.
If the first operation is greater than or equal to the second, the result is a Boolean
"1". If the first operand is less than the second, the result is a Boolean "0".
Example: Greater Than/Equal ">="
In the example "OUT"will be "1"if "IN1" is greater than/equal to "10" and otherwise
"0".
OUT := IN1 >= 10 ;
414
33002204 12/2010
Structured text ST
Comparison with "EQual to" (=)
Description
The value of the first operation is compared with the value of the second with "=". If
the first operation is equal to the second, the result is a Boolean "1". If the first
operation is not equal to the second, the result is a Boolean "0".
Example: Equal "="
In the example, "OUT" will be "1", if "IN1" is equal to "10" – otherwise it will be "0".
OUT := IN1 = 10 ;
33002204 12/2010
415
Structured text ST
Comparison with "Not Equal to" (<>)
Description
The value of the first operation is compared with the value of the second with "<>".
If the first operation is not equal to the second, the result is a Boolean "1". If the first
operation is equal to the second, the result is a Boolean "0".
Example: Not Equal "<>"
In the example, "OUT" will be "1", if "IN1" is not equal to "10" – otherwise it will be "0".
OUT := IN1 <> 10 ;
416
33002204 12/2010
Structured text ST
Comparison with "Less Than"(<)
Description
The value of the first operation is compared with the value of the second with "<". If
the first operation is smaller than the second, the result is a Boolean "1". If the first
operation is bigger than or the same size as the second, the result is a Boolean "0".
Example: Less Than "<"
In the example, "OUT" will be "1", if "IN1" is less than "10" – otherwise it will be "0".
OUT := IN1 < 10 ;
33002204 12/2010
417
Structured text ST
Comparison with "Less than or Equal to" (<=)
Description
The value of the first operation is compared with the value of the second with "<=".
If the first operation is less than or equal to the second, the result is a Boolean "1".
If the first operation is greater than the second, the result is a Boolean "0".
Example: Less Than or Equal "<="
In the example, "OUT" will be "1", if "IN1" is less than or equal to "10" – otherwise it
will be "0".
OUT := IN1 <= 10 ;
418
33002204 12/2010
Structured text ST
Boolean AND (AND or &)
Description
With "AND" or "&" a configured AND link occurs between the operations.
With the BYTE and WORD data types, the link is performed bit by bit.
Example: Boolean "AND or &"
In the examples, "OUT" will be "1" if "IN1", "IN2" and "IN3" are "1".
OUT := IN1 AND IN2 AND IN3 ;
or
OUT := IN1 AND IN2 AND IN3 ;
33002204 12/2010
419
Structured text ST
Boolean OR (OR)
Description
With OR, a configured OR link occurs between the operations.
With the BYTE and WORD data types, the link is performed bit by bit.
Example Boolean OR "OR"
In the example, "OUT" will be "1" if "IN1", "IN2" or "IN3" is "1".
OUT := IN1 OR IN2 OR IN3 ;
420
33002204 12/2010
Structured text ST
Boolean Exclusive OR (XOR)
Description
With XOR, a configured Exclusive OR link occurs between the operations.
With the BYTE and WORD data types, the link is performed bit by bit.
Example: Boolean Exclusive OR "XOR"
In the example "OUT" will be "1", if "IN1" and "IN2" are not equal. If "IN1" and "IN2"
have the same state (both "0" or "1"), "OUT" is "0".
OUT := IN1 XOR IN2 ;
Linking more than 2 operations
If more than two operations are linked, the result is "1" with an odd number of 1states and "0" with an even number of 1-states.
Example: Linking more than 2 operations
In the example, "OUT" will be "1" if 1, 3 or 5 operations are "1". "OUT" will be "0" if
0, 2 or 4 operations are "1".
OUT := IN1 XOR IN2 XOR IN3 XOR IN4 XOR IN5;
33002204 12/2010
421
Structured text ST
11.4
Assign instructions
Overview
This section describes the instructions for the programming language of structured
ST text.
What's in this Section?
This section contains the following topics:
Topic
Instructions
422
Page
423
Assignment
424
Declaration (VAR...END_VAR)
426
IF...THEN...END_IF
428
ELSE
429
ELSIF...THEN
430
CASE...OF...END_CASE
431
FOR...TO...BY...DO...END_FOR
432
WHILE...DO...END_WHILE
435
REPEAT...UNTIL...END_REPEAT
437
EXIT
438
Empty instruction
439
Comment
440
33002204 12/2010
Structured text ST
Instructions
Description
Instructions are the "commands" of the ST programming language.
Instructions must be completed by semicolons. Several instructions can be entered
in one line (separated by semicolons).
NOTE: Instructions can be either entered manually or generated using the menu
Objects.
33002204 12/2010
423
Structured text ST
Assignment
At a Glance
When an assignment is performed, the current value of a single or multi-element
variable is replaced by the result of the evaluation of the expression
An assignment consists of a variable specification on the left side, followed by the
assignment operator ":=", followed by the expression to be evaluated. Both variables
must be of the same data type.
Assigning the value of a variable to another variable
Assignments are used to assign the value of a variable to another variable.
The instruction
A := B ;
is for instance used to replace the value of the variable "A" by the current value of
the variable "B". If "A" and "B" are of an elementary data type, the individual value
"B" is passed to "A". If "A" and "B" are of a derived data type, the values of all
elements are passed from "B" to "A".
Assigning the value of a literal to a variable
Assignments are used to assign a literal to variables.
The instruction
C := 25 ;
is for instance used to assign the value "25" to the variable "C".
Assigning the value of an FFB to a variable
Assignments are used to assign a value to a variable which is returned by a function
or a function block.
The instruction
B := MOD_INT(C,A) ;
is for instance used to assign the modulo of the variables "C" and "A" to the variable
"B".
The instruction
A := TON1.Q ;
is for instance used to assign to the variable "A" the value of the output "Q" of the
function block TONI.
424
33002204 12/2010
Structured text ST
Assigning the value of an operation to a variable
Assignments are used to assign to a variable a value which is the result of an
operation.
The instruction
X := (A+B-C)*D ;
is for instance used to assign to the variable "X" the result of the operation "(A+BC)*D".
33002204 12/2010
425
Structured text ST
Declaration (VAR...END_VAR)
At a Glance
The VAR instruction is utilized for declaring the function blocks used and DFBs and
declaring direct addresses if they are not to be used with the default data type. VAR
cannot be used for declaring a variable in Concept. Declaring the variables may
conveniently be done via the Variables editor.
The END_VAR instruction marks the end of the declaration.
NOTE: The declaration of the FBs/DFBs and direct addresses applies only to the
current section. If the same FFB type or the same address are also used in another
section, the FFB type or the address must be declared again in this section.
Declaration of function blocks and DFBs
Every time a FB/DFB example is used, a unique example name is assigned when it
is declared. The example name is used to mark the function block uniquely in a
project. The example name must be unique in the whole project; no distinction is
made between upper/lower case. The example name must correspond to the IEC
Name conventions, otherwise an error message will be displayed.
After specifying the example name, the function block type, e.g.CTD_DINT is
specified.
In the case of function block types no data type is specified. It is determined by the
data type of the actual parameters. If all actual parameters consist of literals, a
suitable data type will be selected.
Any number of example names may be declared for an FB/DFB.
NOTE: The dialog Objects →Insert FFB provides you with a form for creating the
FB-/DFB declaration in a simple and speedy manner.
NOTE: In contrast to grafic programming languages (FBD, LD), it is possible to
execute multiple calls in FB/DFB examples within ST.
Example
Declaration of function blocks and DFBs
426
33002204 12/2010
Structured text ST
Declaration of direct addresses
In the case of this declaration, every direct address used whose data type does not
correspond to the default data type will be assigned the required data type (see also
Default data types of direct addresses (see page 328)).
Example
Declaration of direct addresses
VAR
AT %QW1 : WORD ;
AT %IW15 : UINT ;
AT %ID45 : DINT ;
AT %QD4 : TIME ;
END_VAR
33002204 12/2010
427
Structured text ST
IF...THEN...END_IF
Description
The IF instruction determines that an instruction or a group of instructions will only
be executed if its related Boolean expression has the value 1 (true). If the condition
is 0 (false), the instruction or the instruction group will not be executed.
The THEN-command identifies the end of the condition and the beginning of the
command(s).
The END_IF instruction marks the end of the instruction(s).
NOTE: Any number of IF…THEN…ELSE…END_IF commands may be nested to
generate complex selection commands.
Example IF...THEN...END_IF
If FLAG is 1, the instructions will be executed; if FLAG is 0, they will not be executed.
IF FLAG THEN
C:=SIN_REAL(A) * COS_REAL(B) ;
B:=C - A ;
END_IF ;
Example IF NOT...THEN...END_IF
Using NOT, the condition may be inverted (execution of both instructions at 0).
IF NOT FLAG THEN
C:=SIN_REAL(A) * COS_REAL(B) ;
B:=C - A ;
END_IF ;
Related topic(s)
ELSE (see page 429)
ELSEIF (see page 430)
428
33002204 12/2010
Structured text ST
ELSE
Description
The ELSE command always comes after an IF…THEN-, ELSIF…THEN- or CASEcommand.
If the ELSE command comes after IF or ELSIF, the command or group of commands
will only be executed if the associated Boolean expressions of the IF and ELSIF
command have the 0 value (false). If the condition of the IF or ELSIF command is 1
(true), the command or group of commands will not be executed.
If the ELSE command comes after CASE, the command or group of commands will
only be executed if no identification contains the value of the selector. If an identification contains the value of the selector, the command or group of commands will
not be executed.
NOTE: As many IF…THEN…ELSE…END_IF-commands as required can be
encapsulated to create complex selection commands.
Example ELSE
IF A>B THEN
C:=SIN_REAL(A) * COS_REAL(B) ;
B:=C - A ;
ELSE
C:=A + B ;
B:=C - A ;
END_IF ;
Related topic(s)
IF (see page 428)
ELSIF (see page 430)
CASE (see page 431)
33002204 12/2010
429
Structured text ST
ELSIF...THEN
Description
The ELSIF-command always comes after an IF…THEN-command. The ELSIFcommand establishes that a command or group of commands will only be executed
if the associated Boolean expression of the IF-command has the 0 value (false) and
the associated Boolean expression of the ELSIF command has the 1 value (true). If
the condition of the IF-command is 1 (true) or the condition of the ELSIF-command
is 0 (false), the command or group of commands will not be executed.
The THEN-command identifies the end of the ELSIF-condition(s) and the beginning
of the command(s).
NOTE: As many IF…THEN…ELSIF…THEN…END_IF-commands as required can
be encapsulated to create complex selection commands.
Example ELSIF…THEN
IF A>B THEN
C:=SIN_REAL(A) *
B:=SUB_REAL(C,A)
ELSIF A=B THEN
C:=ADD_REAL(A,B)
B:=MUL_REAL(C,A)
END_IF ;
COS_REAL(B) ;
;
;
;
Example encapsulated commands
IF A>B THEN
IF B=C THEN
C:=SIN_REAL(A) * COS_REAL(B) ;
ELSE
B:=SUB_REAL(C,A) ;
END_IF ;
ELSIF A=B THEN
C:=ADD_REAL(A,B) ;
B:=MUL_REAL(C,A) ;
ELSE
C:= DIV_REAL (A,B) ;
END_IF ;
Related topic(s)
IF (see page 428)
ELSE (see page 429)
430
33002204 12/2010
Structured text ST
CASE...OF...END_CASE
Description
The CASE instruction consists of an INT data type expression (the "selector") and a
list of instruction groups. Each group is provided with a marke which consists of one
or several whole numbers (ANY_INT) or zones of whole number values. The first
group is executed by instructions, whose marke contains the calculated value of the
selector. Otherwise none of the instructions will be executed.
The OF instruction indicates the start of the mark.
An ELSE instruction may be carried out within the CASE instruction, whose
instructions are executed if no mark contains the selector value.
The END_CASE instruction marks the end of the instruction(s).
Example CASE...OF...END_CASE
Example CASE...OF...END_CASE
Related topic(s)
ELSE (see page 429)
33002204 12/2010
431
Structured text ST
FOR...TO...BY...DO...END_FOR
Description
The FOR instruction is used when the number of occurrences can be determined in
advance. Otherwise WHILE (see page 435) or REPEAT (see page 437) are used
The FOR instruction repeats an instruction sequence until the END_FOR
instruction. The number of occurrences is determined by start value, end value and
control variable. Start value, end value and the control variable must be the same
type of data (DINT or INT) and may not be modified by one of the repeated
instructions. The FOR instruction increments the control variable value of one start
value to an end value. The increment value has the default value 1. If a different
value is to be used, it is possible to specify an explicit increment value (variable or
constant). The control variable value is checked before each renewed loop running.
If it is outside the start value and end value range, the loop will be left.
Before running the loop for the first time a check is made to determine whether
incrementation of the control variables, starting from the initial value, is moving
towards the end value. If this is not the case (e.g. initial value ≤end value and
negative increment), the loop will not be processed.
Using this ruler, continuous loops will be prevented.
NOTE: For the end value of the data type DINT the range of values -2 147 483 646
to 2 147 483 645 will apply.
The DO command identifies the end of the repeat definition and the beginning of the
instruction(s).
Repetition may be terminated early by using the EXIT instruction. The END_FOR
instruction marks the end of the instruction(s).
Example: FOR with increment "1"
FOR with increment "1"
432
33002204 12/2010
Structured text ST
FOR with increment not equal to "1"
If an increment other than "1" is to be used, this can be defined by BY. The
increment, the initial value, the end value, and the control variable must be of the
same data type (DINT or INT). The criterion for the processing direction (forward,
backward) is the sign of the BY expression. If this expression is positive, the loop will
run forward; if it is negative, the loop will run backward.
Example: Counting forward in two steps
Counting forward in two steps
Example: Counting backward
Counting backward
FOR i:= 10 TO 1 BY -1 DO (* BY < 0 : Backward loop *)
C:= C * COS_REAL(B) ; (* Application will be executed 10
x *)
END_FOR ;
Example: "Unique" loops
The loops in the example are run once precisely, as the initial value = end value. In
this context it does not matter whether the increment is positive or negarive.
FOR i:= 10 TO 10 DO (* Unique Loop *)
C:= C * COS_REAL(B) ;
END_FOR ;
or
FOR i:= 10 TO 10 BY -1 DO (* Unique Loop *)
C:= C * COS_REAL(B) ;
END_FOR ;
33002204 12/2010
433
Structured text ST
Example: Critical loops
If in the example there is the increment j > 0, the instructions will not be executed,
as the situation initial value > end value only permits an increment ≤0. A continuous
loop can only arise if the increment is 0. If this situation is identified during the section
analysis, an error message will be generated. If the error is identified during running
time, an error message will be generated in the event viewer.
FOR i:= 10 TO 1 BY j DO (* Backward loop *)
C:= C * COS_REAL(B) ;
END_FOR ;
If in the example there is the increment j < 0, the instructions will not be executed,
as the situation initial value < end value only permits an increment ≥ 0. A continuous
loop can only arise if the increment is 0. If this situation is identified during the section
analysis, an error message will be generated. If the error is identified during running
time, an error message will be generated in the event viewer.
FOR i:= 1 TO 10 BY j DO (* Forward loop *)
C:= C * COS_REAL(B) ;
END_FOR ;
Example: Illegal loops
Illegal loops
FOR i:= 1 TO 10 BY 0 DO (* Error with Section- *)
C:= C * COS_REAL(B) ; (* Analysis, as continous loop *)
END_FOR ;
or
FOR i:= 1 TO 10 BY j DO (* at j=0, Error message *)
C:= C * COS_REAL(B) ; (* in of Event indicator *)
END_FOR ;
434
33002204 12/2010
Structured text ST
WHILE...DO...END_WHILE
Description
The WHILE instruction has the effect that a sequence of instructions will be
executed repeatedly until its related Boolean expression is 0 (false). If the
expression is false right from the start, the group of instructions will not be executed
at all.
The DO command identifies the end of the repeat definition and the beginning of the
command(s).
The occurrence may be terminated early using the EXIT.
The END_WHILE instruction marks the end of the instruction(s).
WARNING
Risk of program crashing
WHILE must not be used to carry out synchronization between processes, e.g. as
a "waiting loop" with an externally determined end condition. This means that a
continous loop must not be created, unless you prevent this using the function
Project →Code generation options... →Enable Loop Control.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
WARNING
Risk of program crashing
WHILE must not be used in an algorithm for which fullfilling the loop end condition
or the execution of an EXIT instruction can not be guaranteed. This means that a
continuous loop must not be created, as this may result in crashing the program,
unless you prevent this by using the function Project →Code generation
options... →Enable Loop Control.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
33002204 12/2010
435
Structured text ST
Example WHILE...DO...END_WHILE
var := 1
WHILE var <= 100 DO
var := var + 4;
END_WHILE ;
Related topic(s)
EXIT (see page 438)
436
33002204 12/2010
Structured text ST
REPEAT...UNTIL...END_REPEAT
Description
The REPEAT instruction has the effect that a sequence of instructions is executed
repeatedly (at least once), until its related Boolean condition is 1 (true).
The UNTIL instruction marks the end condition.
The occurrence may be terminated early using the EXIT.
The END_REPEAT instruction marks the end of the instruction(s).
WARNING
Risk of program crashing
REPEAT must not be used to carry out synchronization between processes, e.g.
as a "waiting loop" with an externally determined end condition. This means that a
continous loop must not be created, unless you prevent this using the function
Project →Code generation options... →Enable Loop Control.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
WARNING
Risk of program crashing
REPEAT must not be used in an algorithm for which fullfilling the loop end
condition or the execution of an EXIT instruction can not be guaranteed. This
means that a continuous loop must not be created, as this may result in crashing
the program, unless you prevent this by using the function Project →Code
generation options... →Enable Loop Control.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Example REPEAT...UNTIL...END_REPEAT
var := -1
REPEAT
var := var + 2
UNTIL var >= 101
END_REPEAT ;
Related topic(s)
EXIT (see page 438)
33002204 12/2010
437
Structured text ST
EXIT
Description
The EXIT command is used to terminate repeat instructions (FOR, WHILE,
REPEAT) before the end condition has been met.
If the EXIT instruction is within a nested occurrence, the innermost loop (in which
EXIT is situated) is left. Next, the first instruction following the loop end (END_FOR,
END_WHILE or END_REPEAT) is executed.
Example EXIT
If FLAG has the value 0, SUM will be 15 following execution of the instructions.
If FLAG has the value 1, SUM will be 6 following execution of the instructions.
SUM : = 0 ;
FOR I := 1 TO 3 DO
FOR I := 1 TO 2 DO
IF FLAG=1 THEN EXIT;
END_IF;
SUM := SUM + J ;
END_FOR ;
SUM := SUM + I ;
END_FOR
Related topic(s)
CASE (see page 431)
WHILE (see page 435)
REPEAT (see page 437)
438
33002204 12/2010
Structured text ST
Empty instruction
Description
Empty instructions are generated by a semicolon (;).
33002204 12/2010
439
Structured text ST
Comment
Description
Within the ST editor, comments start with the string (* and end in the string *). Any
comments may be entered between these two strings. Comments may be entered
in any position in the ST editor. Comments are shown in colour.
NOTE: In accordance with IEC 1131-1, nested comments are not permissible.
However, if you wish to place theses elsewhere, you can release them by using
Options →Preferences →IEC Extensions →Allow nested comments.
440
33002204 12/2010
Structured text ST
11.5
Call up of functions, Function Blocks (EFBs) and
Derived Function Blocks (DFBs)
Overview
This section describes the call up of functions, Function Blocks (EFBs) and Derived
Function Blocks (DFBs).
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
Function Block/DFB Invocation
442
Function Invocation
446
441
Structured text ST
Function Block/DFB Invocation
Use of Function Blocks and DFBs
Function blocks are provided by Concept in the form of libraries. The logic of the
function blocks is created in C++ programming language and cannot be altered in
the ST Editor. The names of the available function blocks can be taken from the
block libraries.
DFBs are function blocks which can be defined in Concept-DFB. There is no
difference between functions and function blocks for DFBs. They are always
handled as function blocks regardless of their internal structure.
The use of function blocks and DFBs consists of three parts in ST:
the declaration (see page 443),
z the function block/DFB invocation (see page 443),
z the use of the function block/DFB outputs (see page 445).
z
NOTE: The declaration of the function block/DFB invocation can take place
manually or you can create the block end and the assignment of the parameters
using the menu command Objects → Insert FFB.
Function Blocks with Limited Use
Use of the following EFBs from the DIAGNO block library is limited in ST (function
blocks can be used, but the expanded diagnostic information cannot be evaluated):
z XACT, XACT_DIA
z XDYN_DIA
z XGRP_DIA
z XLOCK,
z XPRE_DIA
z XLOCK_DIA
z XREA_DIA
Function Blocks with Limited Invocation
For EFBs which have one or more outputs with data type ANY but no inputs with
data type ANY (generic outputs/inputs), the block invocation can only take place in
compact form (see page 445). e.g. in the block library LIB984:
z GET_3X
z GET_4X
442
33002204 12/2010
Structured text ST
Unusable Function Blocks
Unusable Function Blocks:
z EFBs which use several registers with only the entry for the first register on the
input/output (e.g. MBP_MSTR from the COMM block library) cannot be used.
z EFBs which contain outputs with input information (e.g. GET_BIT, R2T from the
LIB984 block library) cannot be used
z The following EFBs from the COMM block library cannot be used for the technical
reasons listed above:
z CREADREG
z CREAD_REG
z CWRITREG
z CWRITE_REG
z READREG
z READ_REG
z WRITEREG
z WRITE_REG
z MBP_MSTR
z
The following EFBs from the LIB984 block library cannot be used for the technical
reasons listed above:
z FIFO
z GET_BIT
z IEC_BMDI
z LIFO
z R2T
z SET_BIT
z SRCH
z T2T
Declaration
Before invoking the function block/DFBs, they must be declared using VAR and
END_VAR (see page 426).
Function Block/DFB Invocation
Function blocks/DFBs are invoked using an instruction consisting of the instance
name for the FB/DFB, which is followed by a list, in brackets, of value assignments
(current parameters) to formal parameters. The order of the formal parameters in a
function block invocation is not significant. It is not necessary for all formal
parameters to be assigned a value. If a formal parameter is not assigned a value,
the initial value defined in the variable editor is used when executing the function
block. If an initial value is not defined, the default value (0) is used.
NOTE: Inputs of type VARINOUT (see page 491) always have to be assigned a
value.
33002204 12/2010
443
Structured text ST
Function block/DFB invocation:
NOTE: In ST, unlike the graphic programming languages (FBD, LD), FB/DFB
instances can be called multiple times.
NOTE: Even if the function block has no inputs or the input parameters are not to be
defined, the function block should be invoked before the outputs can be used.
Otherwise the initial values for the outputs are given, i.e. "0".
Declaration and invocation of a function block in ST:
VAR
CLOCK : SYSCLOCK ;
COUNT : CTU_DINT ;
END_VAR
CLOCK () ;
COUNT (CU:=CLOCK.CLK3, R:=reset, PV:=100) ;
out:=COUNT.Q ;
current:=COUNT.CV ;
Invocation of the function block in FBD.
444
33002204 12/2010
Structured text ST
Function Block/DFB Invocation in Compact Form
The block invocation and the assignments for the inputs/outputs are also possible in
a more compact form, which saves runtime:
VAR
CLOCK : SYSCLOCK ;
COUNT : CTU_DINT ;
END_VAR
CLOCK () ;
COUNT (CU:=CLOCK.CLK3, R:=reset, PV:=100,
Q=>out, CV=>current) ;
Use of the Function Block/DFB Outputs
The outputs of the function block/DFBs can always be used when a variable (read
only) can also be used.
33002204 12/2010
445
Structured text ST
Function Invocation
Using Functions
Functions are provided by Concept in the form of libraries. The logic of the function
is created in C++ and cannot be edited in the ST Editor. The names of the available
function can be taken from the block libraries.
NOTE: The declaration of the function invocation can take place manually or you
can create the block end and the assignment of the parameters using the menu
command Objects → Insert FFB.
Invoking a function in ST:
out := LIMIT_INT (MN:=0, IN:=in1, MX:=5 + var) ;
Invoking the function FBD:
Unusable Functions
Functions which have one or more outputs with data type ANY but no inputs with
data type ANY (generic outputs/inputs) cannot be used in ST.
Invoking a Function: Variant 1
The function can also be invoked using an instruction consisting of a current
parameter (variable) followed by the instruction assignment ":=" followed by the
name of the function followed by a list of value assignments (current parameters) for
the formal parameters in brackets. The order of the formal parameters in a function
block invocation is not significant.
446
33002204 12/2010
Structured text ST
Invoking a Function: Variant 2
Functions are invoked using an instruction. The instruction consists of the current
parameter (variable) for the output followed by the instruction assignment ":="
followed by the name of the function followed by a list of current input parameters in
brackets. The order of the current parameters in a function invocation is significant.
33002204 12/2010
447
Structured text ST
11.6
Syntax check and code generation
Overview
This section describes the syntax check and the code generation of the structured
ST text.
What's in this Section?
This section contains the following topics:
Topic
448
Page
Syntax Check
449
Code generation
450
33002204 12/2010
Structured text ST
Syntax Check
Introduction
A syntax check can be performed during the program/DFB creation with Project →
Analyze section.
Syntax Check Options
With the menu command Options →Preferences →IEC extensions... →IECextensions the syntax check options can be defined.
NOTE: The settings in this dialog are used in the project description (PRJ.DSK) and
in the Concept installations description (CONCEPT.DSK), i.e. they are valid for the
entire Concept installation.
If a project is opened, that was created using different settings (e.g. Allow nested
comments in the project and not in the actual Concept Installation), errors can occur
when opening the project.
Allow Case Insensitive Keywords
If the check box Allow case insensitive keywords is checked, upper and lower
case for all keywords is enabled.
Allow nested comments
If the check box Nested comments authorized is checked, nested comments can
be entered. There are no limits to the nesting depths.
Allow Leading Digits in Identifiers
If the check box Allow leading digits in identifiers is checked, figures as the first
character of identifiers (i.e. variable names, step names, EFB names) are possible.
Identifiers, which consist solely of figures are, however, not authorized, they must
contain at least one letter.
Unused Parameters Cause Warnings
The IEC 1131-3 permits functions and Function Blocks to be called up without
calling up the assignment of all the input parameters. These unused parameters are
implicitly assigned a 0, or they retain the value from the last call up (Function Blocks
only).
If in the menu command Options →Preferences →Analysis... →Analysis the
check box Unused parameters lead to warnings is checked, a list of these unused
parameters is displayed in the message window when generating the code.
33002204 12/2010
449
Structured text ST
Code generation
At a Glance
The menu command Project →Options for code generation is used to define
options for code generation.
Fastest code (restricted check)
If the check box Fastest Code (restricted check) is activated, a runtime-optimized
code will be generated.
This runtime optimization is achieved with integer arithmetic (e.g. "+" or "-") with
simple process commands instead of EFB calls.
Process commands are much faster than EFB calls, but they generate no error
messages, such as e.g. Arithmetic or Array overrun. This option should only be used
if it has been ensured that the program is free of arithmetic errors.
Example: Fastest code
IF i <= max THEN
i := i +1 ;
END_IF;
(*i and max are of INT type*)
If Fastest Code (restricted check) is selected, the addition "i1 + 1" is executed with
the process command "add". The code is now faster than if EFB ADD_INT had been
called up. However, no runtime error is generated if "max" is 32767. In this case, "i"
would overrun from 32767 to -32768!
Activate loop control
This check box activates a software watchdog for continuous loops.
If this check box is checked, with loops within IL and ST sections, it is tested whether
these loops are again exited within a certain time. The time authorized depends on
the manually defined watchdog time. The authorized time for all loops combined
constitutes 80% of the Hardware watchdog time. In this way triggering of the
hardware watchdog by endless loops is disabled. If a time consuming loop or an
endless loop is detected, processing of the affected section will stop, an entry in the
Event display will be generated and processing of the next section will begin. In the
next cycle, the segment will be re-processed until a time consuming loop or an
endless loop is detected once again, or until the segment is finished correctly.
NOTE: If the hardware watchdog stops the PLC when a time consuming loop or an
endless loop is detected, this option should not be activated. The hardware
watchdog itself is not switched off by this function.
450
33002204 12/2010
Structured text ST
11.7
Online functions of the ST programming language
Online functions
Description
The online functions available in the programming language Instruction List (IL) are
available here (see Online functions of the IL instruction list, page 385).
33002204 12/2010
451
Structured text ST
11.8
Creating a program with the structured ST text
Creating a program in structured ST text
At a Glance
The following description contains an example of the creation of a program in the
programming language of structured ST text. This creation is divided into 2 main
steps:
Step
Action
1
Generating a section (see page 452)
2
Creating the logic (see page 453)
Generating a section
The procedure for generating a section is as follows:
Step
1
452
Action
Using the menu command File →New section... and enter a section name.
Note: The section name (max. 32 characters) is not case-sensitive and must be
unique throughout the project. If the name entered already exists, a warning is
given and another name must be chosen. The section name must correspond to
the IEC name conventions, otherwise an error message is displayed.
Note: In accordance with IEC1131-3, only letters are permitted as the first
character of names. Should numbers be required as the first character, however,
the menu command Options →Presettings →IEC expansions... →Enable
leading figures in identifiers .
33002204 12/2010
Structured text ST
Creating the logic
The procedure for creating the logic is as follows:
Step
33002204 12/2010
Action
1
Declare the Function Block and DFBs, which are to be used, with assistance
from VAR…END_VAR.
Example:
VAR
RAMP_UP, RAMP_DOWN, RAMP_X : TON
COUNT : CTU_DINT ;
END_VAR
2
Declare the variables and their initial value in the Variable Editor.
3
Create the logic of the program.
Example:
SUM : = 0 ;
FOR I = 1 TO 3 DO
FOR J = 1 TO 2 DO
IF FLAG = 1 THEN EXIT;
END_IF;
SUM := SUM + J ;
END_FOR ;
SUM = SUM + I ;
END_FOR
4
Save the section with the menu command Data file →Save project .
453
Structured text ST
454
33002204 12/2010
Ladder Logic 984
33002204 12/2010
Ladder Logic 984
12
Introduction
This chapter describes the programming language Ladder Logic 984.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
12.1
General about Ladder Logic 984
456
12.2
Working with Ladder Logic 984
458
12.3
Subroutines
469
12.4
Equation Network Editor
471
12.5
LL984 Programming Modes
480
455
Ladder Logic 984
12.1
General about Ladder Logic 984
General about Ladder Logic 984
Introduction
Ladder logic is displayed in a graphic window. Each window contains exactly one
ladder logic section. One or more different ladder sections can be viewed or edited
(multiple windows of the same section is not supported).
If you are adding a new section the section number is posted for your reference.
Correlation between Sections and Segments
Each ladder logic section becomes tied to a PLC ladder logic segment (e.g., one
section equals one segment) by a segment number entry in the Section Properties
dialog.
One network at a time is visible in each section.
Using the Keyboard
Editing in Concept is ordinarily done with the mouse, but it is also possible with the
keyboard (see also Short Cut Keys in the LL984-Editor, page 847).
456
33002204 12/2010
Ladder Logic 984
Project Analyzation
Ladder logic is analyzed before the program is downloaded to the controller.
The editor permits only valid Ladder Logic to be entered in the editor, e.g.:
z Only those logic elements supported by the current PLC configuration are visible
for selection. You must configure the controller before entering logic.
z The analyzer does not allow references outside the range of the current
configuration.
z The analyzer does not allow duplicate coils unless supported by the current
configuration.
z The analyzer does not allow loadables that are not in the current configuration.
z All subroutines must exist in a single section.
z The section containing subroutines cannot be scheduled.
z All jumptosubroutine instructions must reference the same section.
z Multiple variables per reference are supported. A user preference is available to
enable or disable this feature. When multiple variables are declared for a given
reference either a warning or error is generated, depending on this preference.
NOTE: Your changes to configuration may cause the program to become
incompatible with the configuration.
NOTE: Contacts or coils may be entered without references. This not allowed, but
not covered by the project analyzation.
Capacity and Limitations
Capacity and Limitations:
Editor cannot permit more sections than number of segments
z Editor cannot permit more networks than can fit in controller memory
z
33002204 12/2010
457
Ladder Logic 984
12.2
Working with Ladder Logic 984
Introduction
This section describes how to work with Ladder Logic 984.
What's in this Section?
This section contains the following topics:
Topic
458
Page
Entering and Editing Logic Objects
459
Entering and Editing Variables
461
Ladder and Network Editing
464
Reference Zoom and DX Zoom
466
Search and Replace
468
33002204 12/2010
Ladder Logic 984
Entering and Editing Logic Objects
Prerequisite Requirements
Only those logic objects supported by the current PLC configuration are visible for
your selection. You must configure the controller before entering logic.
For Loadables that require settings in Project →Configurator →Configure →
Config. extensions, provisions must be made before inclusion in a Ladder
program.
Navigation
When you are in the middle of a section, the next or previous network can be viewed
by scrolling with PgUp and PgDn keys.
When you are at the top or bottom of a section, the next or previous section can be
viewed by scrolling with PgUp and PgDn keys, if the section exists.
For instance if you are at the end of networks in the last section (and it is not section
32), you are prompted with a dialog to allow appending a new section. Each network
is compared against the database on PgUp/PgDn (in Combo-Mode).
You can go to a network within a section by using the Go to Network dialog. You
can select the first or last network within the current section, or go to a network by
entering a network name or number. A sortable list of networks (with names) is
provided.
Dialog Interaction
Your actions for entering and editing Ladder Logic follow the standards of MSWindows and conventions of major MS-Windows applications. When an element is
selected with the mouse, the mouse cursor changes to a graphical picture that
represents the logic item. The application programmer places the logic item in the
edit area by clicking or pressing the Enter key.
A keyboard cursor is shown as a high lighted cell (block) within the Ladder Logic
network. For each editing mouse action there is a corresponding keyboard action
(see also Short Cut Keys in the LL984-Editor, page 847). When the keyboard is
used to enter a logic item, there is no initial selection step the logic item is
immediately placed in the network at the keyboard cursor.
33002204 12/2010
459
Ladder Logic 984
Ladder Logic sample network:
Placing Objects
The entire range of programming objects is available from the Object main menu
and selected sub menu items.
Occupied nodes of equivalent height can be overwritten.
Instructions can be entered by typing the name in a dialog.
NOTE: When possible, Concept uses Ctrl key in place of the Modsoft Alt key (see
also Modsoft Keys with Concept Equivalents, page 1008).
Online Restriction
Online restrictions:
z Online deletes require user confirmation.
z Concept does not support drag/drop of programmed elements when online.
460
33002204 12/2010
Ladder Logic 984
Entering and Editing Variables
Introduction
References of nodes in logic items can be viewed or edited by double clicking an
item in a network or by pressing the Enter key on an item that has the focus. An
Object Properties dialog is presented when you double click on a highlighted object
or by pressing the Enter key on an item that has the focus.
You can view the already created variables by clicking on the Lookup button.
You can create new variables by clicking on the Variable declarations button.
Editing References
References of each node of the logic element (e.g., multi-node) can be edited. When
applicable, you can enter the sub-function name (from a drop-down list). If both a
constant and a reference can be entered, the # sign must be entered before a
constant beginning with 0, 1, 3, or 4. You may enter a variable name for references.
33002204 12/2010
461
Ladder Logic 984
Object properties with Lookup Variables dialog:
Entry Format of Reference Values
When entering references, the first digit is always the reference type (e.g., 0x) and
the following digits are the reference number. You may change the format of the
displayed references by setting Options →Preferences →Common.
462
33002204 12/2010
Ladder Logic 984
Status Bar
The variable name (if applicable) is shown on the display status line, for the element
in focus. When online, the value of the reference is also shown. The initial display
format of the reference value depends on the instruction in the program. You can
change the display format using the following keys in combination to define the data
precision and then format.
Table of display formats:
Precision
Format
L (32bit)
D (signed decimal)
U (unsigned)
A (ascii)
H (hex)
S (16bit)
D (signed decimal)
U (unsigned)
A (ascii)
H (hex)
Reference Offsetting
Program references can be offset using Edit →Offset References. Multiple
references can be offset in the same step (while offline). Sections/networks that are
being offset are selectable. You are asked to put in the first and last reference to be
affected and put in the number you want the offset to be.
33002204 12/2010
463
Ladder Logic 984
Ladder and Network Editing
Introduction
Ladder and network edit functions are available from the main menus Edit and
Networks.
NOTE: Menu items in diminished brightness are not selectable given the current
configuration, status, etc,.
Undo Delete
The Edit →Undo delete function, is an ofline mode function that allows up to the
most current 5 deletes to be undone. The Undo delete is provided for each ladder
logic section and includes element and network cut/delete events.
Insert, Append or Reorder network operations cause a reset of the delete-save
area therby assuring the network numbers are not contaminated.
Select/De-select All, Cut, Copy and Paste
Select all, Cut, Copy, and Paste operations on individual language elements occur
within a single network (at a time). Your can select-all or unselect-all elements in a
single network. You can also select, cut, copy, and paste language elements within
and between ladder logic networks or sections.
In an online paste operation, the item being pasted is done in increments of scans
until complete.
Selecting Elements
You cannot select multiple language elements (e.g., accumulate selections) across
networks or sections.
Setting focus to an element is done by moving the cursor (either with mouse or arrow
key) to the element.
Selection of elements is done by clicking or pressing the Spacebar key on the
element which has the focus.
Multiple elements can be selected by using mouse-rubber-band actions. Multiple
elements can also be selected by holding down the Shift key and then clicking on
the elements or pressing the Spacebar key on the elements.
An entire row or column can be selected by clicking on the rung or column header
in the network.
The mouse provides a finer level of selection than the keyboard. If two or more
elements appear in a cell (e.g., both a vertical short and a contact), pressing the
Spacebar key selects all items in that cell. Clicking the mouse selects the element
closest to the mouse pointer.
464
33002204 12/2010
Ladder Logic 984
Open Row
A new row is opened at the current cursor position. This command is executed only
if there is enough free space (i.e., the last row is empty). The rest of the network is
shifted down accordingly. Function boxes and other objects with a height of more
than one node are not split by this command.
Open Column
If the rightmost node column is free, the rest of the network is shifted right, and an
empty column is opened at the current cursor position.
Close Row
If the node row on which the cursor is positioned is empty, all node elements below
are shifted up one row, and an empty bottom row remains.
Close Column
If the node column on which the cursor is positioned is empty, all node elements to
the right are shifted left one column and an empty right column remains.
Network
By using the Networks main menu and it’s subcommands, you can insert (before)
or append (after) a single empty network or delete one or more networks.
In addition, within a single section, you can cut/copy a network then you can
copy/paste networks in any section. You are provided with a list of networks to
consider for the cut/copy operation
Reorder Networks
Network execution reordering is an offline function. You may change the execution
order of networks within a single section. Networks are solved in the order they
appear in the section.
The execution order of networks is changed by using the Network Execution Order
dialog. i.e. select Network →Reorder....
Network Comments
A section description can be included. Each network can be individually commented
using network comments and online comments.
A network name can be entered in the Network Comment dialog.
33002204 12/2010
465
Ladder Logic 984
Reference Zoom and DX Zoom
Introduction
Concept offers you two different zoom types:
the Reference Zoom
z the DX Zoom
z
Reference Zoom
Some programming elements allow parameters to be set which in effect customize
a network implementation for this specific element. Such features as ranges and
limits etc., are input using this zoom edit capability.
Information on individual references can be viewed or edited.
The Reference Zoom dialog shows the following information about a reference:
z State-ram value
z The drop/rack/slot if the reference is in I/O map
z If reference is 0x or 1x, then the disable/enable state is shown
The initial display format of 3x and 4x reference values depends on the instruction
in the program. The display format can be changed. The state ram value or
disable/enable state (if applicable) can also be changed. Constants cannot be
zoomed. You cannot zoom on variables without a reference. Reference Zoom
dialogs can be used for 4x references and for 0x references that are disabled.
DX Zoom
The DX Zoom editor allows you to edit registers for DX functions. These registers
used by the DX function also have text descriptions associated with them to aid with
DX programming. There is both keyboard and mouse access to DX zoom from the
Ladder Logic editor.
The DX Zoom dialog allows you to edit registers for given DX functions. The DX
zoom screen contains text for each register, bit, or group of bits.
The allowed data types are:
466
Data Type
Length
Unsigned Integer
16 bit
Signed Integer
16 bit
Unsigned Long Integer
32 bit
Signed Long Integer
32 bit
float
32 bit
bit (flag)
1 bit
bitfield
1-16 bits
33002204 12/2010
Ladder Logic 984
The allowed complex data types are:
Complex Data Types
Length
equation
1-16 bits
ASCII
String up to 80 characters
Absolute addressing is the only addressing method allowed. There is no support for
indirect addressing
In addition to data entry, DX zoom has the capability to display textual information
associated with a particular register. Each register entry will have an associated
descriptor as well as context sensitive help.
33002204 12/2010
467
Ladder Logic 984
Search and Replace
Trace
The Online →Trace function finds coils from 0x references in the program. You can
trace a coil by first setting focus to a 0x reference and then running the trace
function. The result of trace is to position the network with the found coil on the edit
area. After a successful trace, with Online →ReTrace you can go back to the initial
0x reference.
Online Search
A separate dialog is available for Project →Search in direct mode. The Online
Search dialog. On each find, the choice to search previous or next is provided.
Search can be canceled at any time.
There is no support for searching variable names if in Ladder Logic direct mode.
Replace References
Search and replace of references occur throughout an entire program. You can
select which sections/networks are being searched.
The Edit →Replace References dialog is modal. Request may be prompted for
each individual replace, or request to replace all with no prompting. Replaced
references are listed in the Project →Search →Search History list.
You may exclude DX functions with discrete references from the search. DX
functions require 0x and 1x references to be on a 16 bit boundary.
468
33002204 12/2010
Ladder Logic 984
12.3
Subroutines
Subroutines
Example
The example below shows a series of three user logic networks, the last of which is
used for an up-counting subroutine. Segment 32 has been removed from the orderof-solve table in the segment scheduler.
33002204 12/2010
469
Ladder Logic 984
Description of Example
Description of example:
Stage
470
Description
1
When input 10001 to the JSR block in network 2 of segment 1 transitions from
OFF to ON, the logic scan jumps to subroutine #1 in network 1 of segment 32.
Result: The subroutine will internally loop on itself ten times, counted by the
ADD block.
2
The first nine loops end with the JSR block in the subroutine (network 1 of
segment 32) sending the scan back to the LAB block.
3
Upon completion of the tenth loop, the RET block sends the logic scan back to
the scheduled logic at the JSR node in network 2 of segment 1.
33002204 12/2010
Ladder Logic 984
12.4
Equation Network Editor
Introduction
This section describes the LL984 equation network editor.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
Introduction
472
Equation Editing
474
Syntax and Semantics
476
471
Ladder Logic 984
Introduction
Overview
The equation network is a combination of both Ladder Logic and an algebraic
equation. This network type allows a control designer to incorporate an algebraic
equation into a Ladder Logic program The Equation Network Editor dialog has no
row/column numbers since they have no significance. The grid display option is not
available for the equation network because the row/column concept does not apply
to this new network type. You have the ability, using Ladder Logic notation, to
indicate when the equation will be solved.
Equation network is a special type of Ladder Logic network that allows you to specify
the value of a result register in algebraic notation. If your PLC has an floating point
processor, equation network will take advantage of this feature for faster processing.
It uses a full Ladder Logic network to compose the equation, with a contact or
horizontal short as the enabling input and up to five output coils to describe the state
of the result.
Available Menu Items
The Networks main menu includes two submenu entries to support equation
networks: Insert Equation and Append Equation. If you page through the
networks and reach the start/end of the section, you have the opportunity to
insert/append a new equation network, in addition to the other choices available
(insert/append ladder network, cancel, etc.).
Representation
The Ladder Logic network display changes to accommodate an initialized equation
network. The row and column numbers are removed and also the grid lines are
removed if they are currently being displayed.
472
33002204 12/2010
Ladder Logic 984
The initial display is replaced by the figure below when you double click on the
default equation body.
33002204 12/2010
473
Ladder Logic 984
Equation Editing
Equation Entries
In the first column of the network, row 1 column 1, the legal equation enable entries
are:
z Normally open contact ( -| |- )
When a normally open contact is entered as the first node of the network the
equation is solved when the contact’s referenced coil or input is ON.
z Normally closed contact ( -|/|- )
When a normally closed contact is entered as the first node of the network the
equation is solved when the contact’s referenced coil is OFF.
z Horizontal short ( ----- )
When a horizontal short is entered as the first node of the network the equation
to be solved on every scan.
The horizontal short is used for display purposes only and is not sent to the PLC
as part of the network; the absence of an enabling contact node in the network
sent to the PLC indicates that the network should always be solved.
z Horizontal open ( - --- )
When a horizontal open is entered as the first node of the network the execution
of the equation network is prevented.
Equation Results
Equation network can produce five possible outputs from the top five rows of the
network to describe the result of the equation. You choose the outputs you want to
use by assigning 0x reference numbers to them.
The outputs are displayed as coils in the last column of the equation network.
The row in which the output coils are placed determines their meanings:
Done without error ( -(√) )
When the equation passes power to the output from the top row, the equation has
completed successfully without an error.
z Result < 0 ( -(< 0) )
When the equation passes power to the output from the second row, the equation
has completed successfully and the result is less than zero.
z Result = 0 ( -(= 0) )
When the equation passes power to the output from the third row, the equation
has completed successfully and the result is equal to zero.
z Result > 0 ( -(> 0) )
When the equation passes power to the output from the fourth row, the equation
has completed successfully and the result is greater than zero.
z Done with error ( -(!) )
When the equation passes power to the output from the fifth row, the data in the
equation has caused a calculation error.
z
474
33002204 12/2010
Ladder Logic 984
Cut, Copy and Paste
Text may be pasted into the edit box of an Equation Network Editor dialog. These
are standard Windows text operations, and are the only cut/copy/paste operations
allowed within equation networks. No validation is performed at the time of a cut or
paste; the equation is validated when the user decides to terminate the dialog with
the OK button.
You can cut/copy/paste equation networks using Network →Cut/Copy... in which
a netwotk is manipulated in its entirety.
When a network is cut or copied it may be pasted as a new equation network. In this
case, "paste" means "insert new network". This is the same operation as is used with
ladder networks.
Validity Check
When OK is selected in the Equation Network Editor dialog, the equation is
checked for validity. If an error is detected the cursor is placed as near to the error
as possible and an error message is displayed.
33002204 12/2010
475
Ladder Logic 984
Syntax and Semantics
Operators
The operators are listed below in order of precedence highest to lowest. If required
competing operators are evaluated left to right.
Operator Group
Operators
Description
Unary
-
Negation
~
Ones complement
Exponentiation
**
Exponentiation
Multiply/divide
*
Multiply
/
Divide
+
Addition
-
Subtraction
&
And
Add/subtract
Bitwise
Relations
Conditional
476
-
Or
<<
Left shift
>>
Right shift
^
Xor
<
Less than
< =
Less than or equal
=
Equal
< >
Not equal
= >
Greater than or equal
>
Greater than
?:
Test
33002204 12/2010
Ladder Logic 984
Functions
Additionally the following functions are recognized (and predefined) in an equation:
Function
Description
ABS
Absolute value
ARCCOS
Arc Cosine
ARCSIN
Arc Sine
ARCTAN
Arc Tangent
COS
Cosine of Radians
COSD
Cosine of Degrees
EXPE
Exponential function, e** argument
FIX
Convert float to integer, presumes floating point argument
FLOAT
Convert Integer to Floating point
LN
Natural Logarithm (base e)
LOG
Common Loagarithm (base 10)
SIN
Sine of Radians
SIND
Sine of Degrees
SQRT
Square Root
TAN
Tangent of Radians
TAND
Rangent of Degrees
Equation Syntax
Equation syntax conventions:
33002204 12/2010
Command
Description
[abc]
Any one of a b c
[a-z]
Any characters in the range a trough z
expr*
Zero or more expr
expr+
One or more expr
477
Ladder Logic 984
Lexical Classes
Table of lexical classes
letter
a-z A-Z
bit
0-1
octal_digit
0-7
digit
0-9
hex_digit
0-9 a-f A-F
letter_or_digit
letter | digit
identifier
letter letter_or_digit*
assignment_op
:=
relational_op
> < >= <= = <>
bitwise_op
& | ^ >> <<
add_sub_op
+ -
Mul_div_op
* /
exp_op
**
unary_op
- ~
optional_sign
+ - /*nothing*/
Constants
Constants consist of:
binary_const 2# bit binary_const_body
z decimal_const digit decimal_const_body
z octal_const 8# octal_digit octal_const_body
z hex_const 16# hex_digit hex_const_body
z float_const mantissa exponent
z
478
33002204 12/2010
Ladder Logic 984
Register References
reg_rvalue consists of:
discrete_rvalue
0 digit+
1 digit+
int_reg_rvalue
3 digit+
4 digit+
6 digit+
uint_reg_rvalue
U3 digit+
U4 digit+
U6 digit+
long_reg_rvalue
L3 digit+
L4 digit+
L6 digit+
ulong_reg_rvalue
UL3 digit+
UL4 digit+
UL6 digit+
float_reg_rvalue
F3 digit+
F4 digit+
F6 dgit+
reg_lvalue consists of:
int_reg_lvalue
4 digit+
6 digit+
uint_reg_lvalue
U4 digit+
U6 digit+
long_reg_lvalue
L4 digit+
L6 digit+
ulong_reg_lvalue
UL4 digit+
UL6 digit+
float_reg_lvalue
F4 digit+
F6 dgit+
Note
Because of Concept IEC standards, placement of lexical identifiers differ between
Modsoft and Concept. However, an existing Modsoft Equation is properly
transformed using the Modsoft program converter.
For example a Modsoft equation
400100F := 400001UL + 400002U + 400003L + #23
becomes a Concept equation
%F400100 := %UL400001 + %U400002 + %L400003 +23
33002204 12/2010
479
Ladder Logic 984
12.5
LL984 Programming Modes
LL984 Programming Modes
Direct Programming
There are two situations that determine how direct mode ladder editing is applied:
The first is where there is no open project and you are connected to a PLC that
has a valid program in it. When you select the command Direct-mode 984LL
Editor the first program in the first segment is displayed. You can see the direct
mode status at the right side of the status bar and the network window is labled
984LL Direct.
z The second case occurs when you have a project open and you are connected
to the PLC (but not EQUAL). When you select Direct-mode 984LL Editor in this
case a dialog is displayed listing segments and the number of networks contained
in each. Click on the segment you want click on OK and the Network edit window
is displayed with a window labeled 984LL Direct. If you have an orignal edit
window it will remain on the display.
z
Combination Mode
Combination programming occurs when the programming panel is online. Valid
program changes are immediately written to both the controller and the program
database simultaneously.
480
33002204 12/2010
DFBs (Derived Function Blocks)
33002204 12/2010
DFBs (Derived Function Blocks)
13
Overview
This Chapter describes the procedure for creating DFBs (Derived Function Blocks)
with help from Concept DFB.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
13.1
DFBs (Derived Function Blocks)
482
13.2
Programming and calling up a DFB
501
481
DFBs (Derived Function Blocks)
13.1
DFBs (Derived Function Blocks)
Overview
This section provides an overview on creating and applying DFBs (Derived Function
Blocks).
What's in this Section?
This section contains the following topics:
Topic
General information about DFBs (Derived Function Blocks)
482
Page
483
Global / Local DFBs
485
Use of variables in DFBs
487
Combined Input/Output Variables (VARINOUT Variables)
489
Global Variables
496
Creating Context Sensitive Help (Online Help) for DFBs
499
33002204 12/2010
DFBs (Derived Function Blocks)
General information about DFBs (Derived Function Blocks)
At a Glance
DFBs are created with the help of the Concept DFB software.
DFBs (Derived Function Blocks) can be used for setting both the structure and the
hierarchy of a program.
In programming terms, a DFB represents a subroutine.
Meaning:
z Delivery/transfer of defined values to/from the subroutine
z Any complex program
z Nesting of one or more DFBs in a DFB
z Multiple DFB call up in the whole program, where the program code is bound only
once during the whole program
z DFB specific local variables
z Initial value for variables
z freely definable Interface
Programming languages
DFBs can be created in the Function Block language (FBD), ladder diagram (LD),
instruction list (IL) and structured text (ST) programming languages.
Structure of a DFB
A DFB firstly provides an empty space, which contains a manually defined
input/output and any manually programmed logic. The hierarchic structure of this
logic corresponds to a project in Concept which consists of one or more sections.
These sections contain the actual logic.
Internal structure of the DFB in the FBD editor:
Processing sequence
The processing sequence of the logic, the programming rules and the usable FFBs
and DFBs correspond overall to those of the FBD, LD, IL and/or ST programming.
33002204 12/2010
483
DFBs (Derived Function Blocks)
Nesting
It is possible to call up one or more already existing DFBs in a DFB, where the called
up DFBs themselves can call up one or more DFBs. A DFB cannot however contain
itself. A nesting depth of 5 should not be exceeded. The exact border depends,
among other factors, upon parameterization (e.g. the number of DFB input/output
variables) of the CPU in use and its configuration.
NOTE: If nested DFBs are used, the whole nested DFB hierarchy is not checked
consistently in the DFB editor, but only the DFB on the next level. This means that,
for example, with a DFB with 3 or 4 levels, the deep nested DFBs can be altered (i.e.
Pin assignment), without this being apparent. In Concept, an error is not reported
until project analysis.
NOTE: NEVER use diagnostic EFBs (diagnostic library) in DFBs.
Context help
Personalized context-sensitive help (online help) can be created for DFBs (see
Creating Context Sensitive Help (Online Help) for DFBs, page 499).
Calling up a DFB
DFBs are visually denoted in the FBD and LD editor window by double vertical lines
on the DFB border. Using the command button Despeckle… in the properties dialog
box of the DFB a document window can be opened, in which the programmed logic
of the DFB can be viewed (even when it was created with IL or ST). This document
window has a gray background, which denotes that the DFB in this document
window cannot be edited.
DFBs are treated as Function Blocks after they are called into Concept.
Call up of the DFB in the FBD editor:
Archiving and Documentation
The archiving and documentation of a DFB is the same as with projects (see
Documentation and Archiving, page 729).
484
33002204 12/2010
DFBs (Derived Function Blocks)
Global / Local DFBs
Description
Global and local DFBs differ in the locality of their directory hierarchy.
Depending on the directory or subdirectory in which the DFB is stored, it can be
called up globally, i.e. within all the projects created under Concept, or locally, in a
specific project.
In the Defining the Storage of Global DFBs during Upload, page 1110 you can
ensure that during the IEC upload process a GLB directory containing the global
DFBs is created in the project directory. By doing this, the existing global DFBs in
the Concept →DFB will not be overwritten and therefore it will not have any effect
on other projects.
Directory structure without uploaded project:
33002204 12/2010
485
DFBs (Derived Function Blocks)
Directory structure according to INI settings ([Upload]: PreserveGlobalDFBs=1)
for uploaded projects:
If a local and a global DFB have the same name, the local DFB is given priority.
NOTE: The length of the DOS path name in which the DFBs are stored is limited to
29 characters. Care should be taken that the DFB directory does not exceed this
limit.
486
33002204 12/2010
DFBs (Derived Function Blocks)
Use of variables in DFBs
Introduction
When programming DFBs, two forms of variables are distinguished:
z Internal variables
z Formal parameters (Input/Output variables)
Internal variables
Internal variables are variables that are only used within the logic of DFBs. These
variables can only be altered in Concept DFB itself. This alteration is therefore valid
for all instances of this DFB.
The following are permitted as types of variables:
Unlocated variables,
z Unlocated Multi-element variables,
z Constant variables
z Literals and
z Located variables.
z
NOTE: Located variables can be used if in the IEC Extentions dialog box you
activate the Allow located variables in DFBs option (see also section Global
Variables, page 496).
These variables are declared in the Variable editor (see page 485).
Formal parameters
Input and output variables are required to transfer values to or from a DFB. These
types of variables are called formal parameters. These variables are taken from the
DFB and displayed as input/output when calling up the DFB.
In the Variable editor (see page 485) define the formal parameter names (the
names of the inputs/outputs), the type of data and the position of the inputs/outputs
(for the FBD /LD editor) on the DFB.
A maximum of 32 input and 32 output variables are possible. The width of the DFB
symbol is automatically matched to the length of the name of the inputs/outputs.
Input and output variables are always Unlocated variables.
An initial value can also be defined for input variables. Input variables, i.e. inputs,
are always shown to the left of the DFB in the FBD/LD editor. Output variables, i.e.
outputs, are always shown to the right of the DFB.
A special form of input/output variables are the VARINOUT variables
(see page 489).
33002204 12/2010
487
DFBs (Derived Function Blocks)
Transfer of values during the program runtime
During program runtime, the value of the current parameters in the DFB program are
passed and redistributed via the formal parameters. The value of these formal
parameters are determined by the value of the current parameters, which have been
linked with the corresponding DFB input/output. The current parameters can be
direct addresses, located variables, unlocated variables, located multi-element
variables, unlocated multi-element variables, elements from multi-element
variables, constants or literals.
Through this, the same DFB type can be called up several times and each copy of
the DFB assigned with individual parameters.
Exchanging positions
If all 32 possible input or output variables are occupied when creating the DFB and
the exchange of the positions of 2 variables is required, a variable can be placed in
position 33 in the meantime. This enables the alteration of the variable positions.
However, saving a DFB with 33 input or output variables is not possible. Position 33
only serves as an auxiliary position when editing.
488
33002204 12/2010
DFBs (Derived Function Blocks)
Combined Input/Output Variables (VARINOUT Variables)
Introduction
Combined input/output variables are a special form of input/output variables. These
are also called VARINOUT variables.
Application Purpose
DFBs are often used to read a variable on input (input variables), to process it and
to restate the altered values of the same variable (output variables). If the variables
are structured variables and elements unaffected by the processing are also to be
output again at the output, it is necessary to copy the complete variable within the
DFB from the input to the output. This is also necessary when only a single element
of a structured variable is processed in the DFB. To save memory and shorten the
execution time, it is sensible to use VARINOUT variables in this case. This variable
type can (must) be used simultaneously at DFB inputs and the associated DFB
outputs.
Creating a VARINOUT variable in DFB
The following conditions must be noted when creating a VARINOUT variable:
z Like all input/output variables, VARINOUT variables are created in the Variable
Editor.
z VARINOUT variables are declared twice. Once as input variables and once as
output variables.
z The same formal parameter names must be used in both declarations.
z The same data types must be used in both declarations.
z The same pin positions must be used in both declarations.
z The input variable is declared first, and then the output variable.
z After confirming the declaration with OK, it is no longer possible to modify the
input variable.
Specific Features during Creation
The following special features are to be noted when creating DFBs with VARINOUT
inputs/outputs.
z If the DFB VARINOUT input has been assigned an initial value, this is not used,
as it is imperative that the input is switched on.
33002204 12/2010
489
DFBs (Derived Function Blocks)
Example
DFB logic:
Declaration of inputs:
490
33002204 12/2010
DFBs (Derived Function Blocks)
Declaration of outputs:
Use of the DFB in FBD/LD
The DFB is invoked and used in FBD/LD editor (see also Calling up a DFB in the
FBD Function Block dialog, page 515 and Calling up a DFB in Ladder Diagram LD,
page 517) just like any other DFB. The inputs/outputs of type VARINOUT are
characterized by a dotted line.
Use of the DFB in the FBD editor:
Specific features in usage
The following special features are to be noted when using DFBs with VARINOUT
inputs/outputs.
z It is essential that VARINOUT inputs/outputs are linked. Otherwise an error
message appears during the section analysis.
z The same variables/variable components must be attached at the VARINOUT
input and the VARINOUT output.
z No graphical links can be attached to VARINOUT inputs/outputs.
z No literals or constants can be attached to VARINOUT inputs/outputs.
z No Boolean variables can be attached to VARINOUT inputs/outputs, because
this leads to problems in the code generation.
z No negations can be used at VARINOUT inputs/outputs.
z If a DFB with VARINOUT inputs/outputs is used within another DFB (nested
DFBs), the VARINOUT inputs/outputs of the inner DFB can be linked to those of
the outer DFB.
33002204 12/2010
491
DFBs (Derived Function Blocks)
Use of the DFB in ST
The DFB is invoked and used in ST Editor (see also Function Block/DFB Invocation,
page 442) like any other DFB.
Use of the DFB in the ST Editor:
(* Function Block declaration *)
VAR
Instance_Name : DFBX;
END_VAR
(* Block invocation *)
Instance_Name (IN1 := V1,
IO1 := V5,
IN2 := V2);
(* Assignments *)
V4 := Instance_Name.OUT1;
V3 := Instance_Name.OUT3;
The following special features are to be noted when using DFBs with VARINOUT
inputs/outputs.
z It is essential that VARINOUT inputs be assigned a value on DFB invocation.
Otherwise an error message will appear during the section analysis i.e. the
following block invocation is not allowed, because the assignment of a value at
the VARINOUT input "V5" is missing:
Instance_Name (IN1 := V1,
IN2 := V2);
z VARINOUT outputs are not to be assigned a value. Otherwise an error message
will appear during the section analysis i.e. the following output assignment is not
allowed, because a value has been assigned at the VARINOUT output:
V5 := Instance_Name.IO1;
z No literals or constants are to be assigned to VARINOUT inputs.
z No Boolean variables can be attached to VARINOUT inputs/outputs, because
this leads to problems in the code generation.
z If a DFB with VARINOUT inputs/outputs is used within another DFB (nested
DFBs), the VARINOUT inputs/outputs of the inner DFB can be linked to those of
the outer DFB.
492
33002204 12/2010
DFBs (Derived Function Blocks)
Use of the DFB in IL
The DFB is invoked and used in IL editor (see also Use of Function Blocks and
DFBs, page 372) like any other DFB.
Use of the DFB in the IL editor:
(* Function Block declaration *)
VAR
Instance_Name : DFBX;
END_VAR
(* Block invocation *)
CAL Instance_Name (IN1 := V1, IO1 := V5, IN2 := V2)
(* Assignments *)
LD Instance_Name.OUT1
ST V4
LD Instance_Name.OUT3
ST V3
The following special features are to be noted when using DFBs with VARINOUT
inputs/outputs.
z It is essential that VARINOUT inputs be assigned a value on DFB invocation.
Otherwise an error message will appear during the section analysis i.e. the
following block invocation is not allowed, because the assignment of a value at
the VARINOUT input "V5" is missing:
CAL Instance_Name (IN1 := V1, IN2 := V2)
z VARINOUT outputs are not to be assigned a value. Otherwise an error message
will appear during the section analysis i.e. the following output assignments are
not allowed, because a value has been assigned at the VARINOUT output:
LD Instance_Name.IO1
ST V5
z No literals or constants are to be assigned to VARINOUT inputs.
z No Boolean variables can be attached to VARINOUT inputs/outputs, because
this leads to problems in the code generation.
z If a DFB with VARINOUT inputs/outputs is used within another DFB (nested
DFBs), the VARINOUT inputs/outputs of the inner DFB can be linked to those of
the outer DFB.
33002204 12/2010
493
DFBs (Derived Function Blocks)
Special features when modifying
There are 3 general possibilities for modifying VARINOUT variables:
Modify existing VARINOUT variables:
z Rename the variables
z Change the data type
z Change the pin position
z
z
z
Two existing variables can be joined in one VARINOUT variable
Split a VARINOUT variable into two variables
Change existing VARINOUT variables
To change (rename, change data type, change pin position) existing VARINOUT
variables, proceed as follows:
Step
Action
1
Open the Variable Editor (F8).
2
Select the Outputs option.
3
Implement the required changes.
Response: The changes are automatically transferred to the input variable.
4
Confirm the changes with OK.
Join variables to VARINOUT variable
To join two variables to a VARINOUT variable, perform the following steps:
Step
494
Action
1
Open the Variable Editor (F8).
2
Select the Inputs option.
3
Create a new input variable (e.g. INOUT1).
4
Select the Outputs option.
5
Create a new output variable with the same name (e.g. INOUT1), data type and
pin position as the input variable.
6
Confirm the changes with OK.
7
Replace all uses of the input and output variable with the VARINOUT variable in
your program.
8
Open the Variable Editor (F8) and delete the now redundant input and output
variable.
33002204 12/2010
DFBs (Derived Function Blocks)
Splitting VARINOUT variable
To split a VARINOUT variable into two variables, proceed as follows:
Step
33002204 12/2010
Action
1
Open the Variable Editor (F8).
2
Select the Inputs option.
3
Create a new input variable (e.g. IN1).
4
Select the Outputs option.
5
Create a new output variable (e.g. OUT1).
6
Confirm the changes with OK.
7
Replace all usages of the VARINOUT variable with the input and output
variables in your program.
8
Open the Variable Editor (F8) and delete the now redundant VARINOUT
variable.
495
DFBs (Derived Function Blocks)
Global Variables
Introduction
Global variables are located variables which are declared in Concept-DFB and
Concept.
Global variables in DFBs can only be declared if the Allow Located Variables in
DFBs check box is activated in the IEC Extensions dialog box. Then the the
Address column is available in the DFB Variable Editor, i.e. located variables can
now be declared.
Global validity of the variables is defined as soon as the DFB is used in the project
and the respective located variables are declared in the Concept Variable Editor.
When declaring the variables, make sure that the same name, address and data
type is used as in the DFB Variable Editor. All reference ranges can be used (0x, 1x,
3x and 4x).
Declaration errors are found and error messages are given when the program is
analyzed (Project →Analyze program). If global validity is recognized, the global
variables are shown with a gray background in the Concept Variable Editor and are
write protected in Concept. That means global variables canonly be changed in the
DFB Variable Editor. Then the declaration for the changed variables must be
updated in the Concept Variable Editor to restore global validity.
NOTE: If inconsistencies are found between the declaration of global variables in
the DFB and the program when analyzing the program (e.g. the address is declared
differently), the program cannot be downloaded to the PLC.
Execution in Concept-DFB
To create global variables in DFB, carry out the following steps in Concept-DFB:
Step
496
Action
1
Close Concept and Start Concept-DFB.
2
Select Options →Preferences →IEC Extensions..., and activate the check
box Allow Located Variables in DFBs.
3
Create a DFB (see section Creating the DFB, page 503).
4
Create the logic (example: see section Creating the Logic in FBD Function Block
Language, page 504).
33002204 12/2010
DFBs (Derived Function Blocks)
Step
5
Select Project →Variable declarations. To declare the located variables,
activate the Variables option button.
Note: All reference ranges can be used (0x, 1x, 3x and 4x) for addressing.
6
Now re-activate the selection mode with Objects →Select mode and doubleclick on one of the unconnected inputs.
Result: The Connect FFB dialog box is opened, where you can assign a current
parameter to the input.
7
In Connect with, activate the Variable option button.
8
Open the variable editor using he Variable declaration... command button.
Then select the unlocated variable (STOP) and click OK.
Result: The selected variable is transferred to the text box in the Connect FFB
dialog box.
9
With OK, the variable (STOP) is assigned to the selected input on the module.
10
33002204 12/2010
Action
Save the DFB using the menu command File →Save.
497
DFBs (Derived Function Blocks)
Execution in Concept
To create global variables in DFB, carry out the following steps in Concept:
Step
498
Action
1
Close the Concept DFB and Start Concept.
2
Call the DFB (example: see section Calling up a DFB in the FBD Function Block
dialog, page 515).
3
Select Project →Variable declarations.... To declare the located variables
(STOP), activate the Variables option button.
4
Transfer the variable names, data type and the address of the located variables,
exactly as they were declared in the Concept-DFB variable editor.
5
Analzye the program using Project →Analyze program.
Result: The Messages window is opened and shows that the global variable
"STOP" was found in the DFB.
The global validity of the variable is recognized, therefore it is shown with a gray
background in the Concept Variable Editor.
6
In the DFB Editor, you can open the Function Block dialog box by doubleclicking on the DFB. Using the Refine... command button, open a document
window with the inner logic of the DFB (the global variable STOP is also shown
here).
33002204 12/2010
DFBs (Derived Function Blocks)
Creating Context Sensitive Help (Online Help) for DFBs
Introduction
In Concept, help is provided for each EFB, which can be invoked according to the
context (the Help on Type command key in the EFBs properties dialog). There are
of course no corresponding help texts in Concept for the DFBs created by you.
You can, however, create your own help for each DFB, which can be invoked in
Concept with Help on Type.
File Format:
You can create your help in the following file formats:
.chm (Microsoft Windows compiled HTML help file)
z .doc (Microsoft Word format)
z .htm (Hypertext Markup Language)
z .hlp (Microsoft Windows help file (16- or 32-Bit Format))
z .pdf (Adobe Portable Document Format
z .rtf (Microsoft Rich Text Format)
z .txt (Plain ASCII Text-Format)
z
Name
The name of the help file must be exactly the same as the name of the DFB (e.g.
SKOE.ext)
The only exceptions are standardized DFB names (e.g. SKOE_BOOL,
SKOE_REAL etc.) In these cases the help file name is the DFB name without the
datatype extension (e.g. DFB name) SKOE_BOOL has the help file SKOE.ext).
Directory
The help file can be stored in the following directories:
z Concept directory
z Concept Help directory (if defined in the file Concept.ini, see readme)
z Global DFB directory
z Local DFB directory
33002204 12/2010
499
DFBs (Derived Function Blocks)
Invoking the Help File
Concept carries out the following procedure to invoke the help file:
Phase
1
Description
Search for the help file DFBName.ext in the local DFB-directory.
The help file is searched for in the following sequence:
z .hlp
z .chm
z .htm
z .rtf
z .doc
z .txt
z .pdf
Result: If the search result is positive the help file will be displayed, otherwise it
will continue with phase 2.
500
2
Search for the help file DFBName.ext in the global DFB-directory.
For the order, see phase 1.
Result: If the search result is positive the help file will be displayed, otherwise it
will continue with phase 3.
3
Search for the help file DFBName.ext in the Concept-directory or Concept-Help
directory.
For the order, see phase 1.
Result: If the search result is positive the help file will be displayed, otherwise it
will continue with phase 4.
4
Display of the comment created in Concept DFB with Project →Properties.
33002204 12/2010
DFBs (Derived Function Blocks)
13.2
Programming and calling up a DFB
Overview
This section describes programming and calling up a DFB.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
At a Glance
502
Creating the DFB
503
Creating the Logic in FBD Function Block Language
504
Creating the Logic in LD Ladder Diagram
507
Creating the Logic in IL Instruction List
511
Creating the Logic in ST Structured Text
513
Calling up a DFB in the FBD Function Block dialog
515
Calling up a DFB in Ladder Diagram LD
517
Calling up a DFB in the IL instruction list
519
Calling up a DFB in structured text ST
520
501
DFBs (Derived Function Blocks)
At a Glance
At a Glance
Programming and calling up a DFB is divided into 3 main steps:
Step
Action
1
Occupying the DFB (see page 503)
2
Creating the logic in:
z Function Block language (FBD) (see page 504)
z Ladder diagram (LD) (see page 507)
z Instruction list (IL) (see page 511)
z Structured text (ST) (see page 513)
3
Calling up the DFB in:
Function Block language (FBD) (see page 515)
Ladder diagram (LD) (see page 517)
Instruction list (IL) (see page 519)
Structured text (ST) (see page 520)
z
z
z
z
502
33002204 12/2010
DFBs (Derived Function Blocks)
Creating the DFB
Description
The procedure for creating the DFB is as follows:
Step
33002204 12/2010
Action
1
Close Concept and start Concept DFB.
2
Create a new DFB using the menu command Data file →New DFB.
Reaction: The name now appears on the title bar:[untitled].
3
Using the menu command Data file →New section... , generate a new section
and enter a section name.
The section name (max. 32 characters) must be clear throughout the DFB, and
is not case-sensitive. If the section name entered already exists, a warning is
given and another name must be chosen. The section name must correspond to
the IEC Name conventions, otherwise an error message appears.
Note: In accordance with IEC1131-3, only letters are permitted as the first
character of names. If, however numbers are required as the first character, this
can be enabled using the menu command Options →Pre-settings →IEC
Expansions... →IEC Expansions →Enable leading figures in identifiers .
4
Select a programming language for the section:
z Function Block language (FBD) (see page 504)
z Ladder diagram (LD) (see page 507)
z Instruction list (IL) (see page 511)
z Structured text (ST) (see page 513)
5
The menu command Project →Properties can be used to generate a comment
about the DFB.
Reaction: This comment can be shown in Concept in the DFB properties box
with the command button Help for type.
6
Save the DFB with the menu command Data file →Save DFB.
Reaction: The first time the Save is used, the Save as dialog box opens –
specify the DFB name and directory where it is to be saved here.
7
Select the directory to be occupied by the DFB. Attention should be paid to the
difference between global and local DFBs (see also Global / Local DFBs,
page 485).
8
Enter the DFB name (max. 8 characters, always with the .DFB extension).
The name must be clear throughout the directory, and is not case-sensitive. If
the section name entered already exists, a warning is given and another name
must be chosen.
503
DFBs (Derived Function Blocks)
Creating the Logic in FBD Function Block Language
Description
The procedure for creating the logic in FBD function block language is as follows:
Step
504
Action
1
To insert an FFB into the section, select the Objects →Select FFB... menu
command.
Result: The FFB dialog box from the library is opened.
2
In this dialog box you can select a library and an FFB from it by using the
Library... command button. You can, however, also display the DFBs that you
created and select one of them using the DFB command button.
3
Place the selected FFB in the section.
4
When all FFBs have been positioned, close the dialog box with OK
5
Activate select mode with Objects →Select Mode, click on the FFB and move
the FFBs to the desired position.
6
Activate the link mode with Objects →Link and connect the FFBs.
For example:
33002204 12/2010
DFBs (Derived Function Blocks)
Step
7
Action
Activate the Variables Editor withProject →Variable Editor to declare the DFB
variables and inputs/outputs (formal parameters).
Example (inputs):
Example (outputs):
33002204 12/2010
505
DFBs (Derived Function Blocks)
Step
506
Action
8
Then re-activate the select mode with Objects →Select Mode and double-click
on one of the unconnected inputs/outputs.
Result: The Connect FFB dialog box opens, in which you can allocate a current
parameter to the input/output.
9
Back up the DFB with the File →Save menu command.
For example:
33002204 12/2010
DFBs (Derived Function Blocks)
Creating the Logic in LD Ladder Diagram
Description
The procedure for creating the logic in LD ladder diagram is as follows:
Step
33002204 12/2010
Action
1
To insert a contact or coil in the section, open the Objects main menu and select
the desired contact or coil. Contacts and coils can also be selected using the tool
bar. Place the contact or coil in the section.
2
To insert an FFB into the section, select the Objects →Select FFB... menu
command.
Result: The FFBs from Library dialog box is opened.
3
In this dialog box you can select a library and an FFB from it by using the
Library... command button. You can, however, also display the DFBs that you
created and select one of them using the DFB command button.
4
Place the selected FFB in the section.
5
When all FFBs have been positioned, close the dialog box with OK
6
Activate select mode using Objects →Select Mode, and move the contacts,
coils and FFBs to the required position.
507
DFBs (Derived Function Blocks)
Step
7
508
Action
Activate link mode with Objects →Link, and connect the contacts, coils and
FFBs. Connect the contacts, FFBs and the left power rail.
For example:
33002204 12/2010
DFBs (Derived Function Blocks)
Step
8
Action
Activate the Variables Editor withProject →Variable Editor to declare the DFB
variables and inputs/outputs (formal parameters).
Example (inputs):
Example (outputs):
9
33002204 12/2010
Then re-activate select mode with Objects →Select mode, and double-click on
a contact or coil.
Result: The Properties: LD Objects dialog box is opened, in which you can
allocate an actual parameter to the contact/coil.
509
DFBs (Derived Function Blocks)
Step
510
Action
10
To connect the FFB input/outputs to the current parameters, double-click on one
of the unconnected input/outputs.
Result: The Connect FFB dialog box is opened, in which you can allocate a
current parameter to the input/output.
11
Back up the DFB with the File →Save menu command.
For example:
33002204 12/2010
DFBs (Derived Function Blocks)
Creating the Logic in IL Instruction List
Description
The procedure for creating the logic in Instruction List (IL) is as follows:
Step
Action
1
Declare the function block and DFBs to be used using VAREND_VAR.
Note: Functions do not have to be declared:
Example:
VAR
CLOCK : CLOCK_DINT ;
END_VAR
2
Declare the variables and their initial value in the Variable Editor.
Example (inputs):
Example (outputs):
33002204 12/2010
511
DFBs (Derived Function Blocks)
Step
512
Action
3
Create your program's logic.
For example:
LD IN1
ADD IN2
MUL (
LD IN3
SUB IN4
)
ST OUT
4
Back up the section with the File →Save Project menu command.
33002204 12/2010
DFBs (Derived Function Blocks)
Creating the Logic in ST Structured Text
Description
The procedure for creating the logic in ST structured text is as follows:
Step
Action
1
Declare the function block and DFBs to be used using VAREND_VAR.
Note: Functions do not have to be declared:
Example:
VAR
CLOCK : CLOCK_DINT ;
END_VAR
2
Declare the variables and their initial value in the Variable Editor.
Example (inputs):
Example (outputs):
33002204 12/2010
513
DFBs (Derived Function Blocks)
Step
514
Action
3
Create your program's logic.
For example:
OUT := (IN1 + IN2) * (IN3 - IN4)
4
Back up the section with the File →Save Project menu command.
33002204 12/2010
DFBs (Derived Function Blocks)
Calling up a DFB in the FBD Function Block dialog
Note
When a DFB is called up, it is not significant which program languages it was created
in. The DFB can be called up in all the IEC sections.
Description
The procedure for calling up a DFB in the FBD Function Block dialog is as follows:
Step
33002204 12/2010
Action
1
Close the Concept DFB and start Concept.
2
Open or create a project and open or create a section.
3
As with an EFB, the DFB is called up using the command button: Objects →
Select FFB....
Reaction: The dialog box FFBs from library is opened.
4
Press the DFB command button to display the global and local DFBs.
For example:
5
Now click on the desired DFB in the list, and position it in the Editor window.
For example:
515
DFBs (Derived Function Blocks)
Step
Action
6
Double-clicking on the DFB opens the Properties: Derived Function Block
dialog box, where the Refine... command button can be used to open a
document window with the internal DFB logic. The gray background indicates
that the DFB cannot be edited in this document window.
7
Now only the actual parameter needs to be defined. This is performed in a way
corresponding to the normal EFB link using the Link FFB dialog box (doubleclick on the inputs/outputs to be parametered.
For example:
Reaction: As is clear from the example, two different sets of parameters are
used in the DFB calls 1 and 2. The formal parameters are the same in both calls
because the program code of the DFB is only occupied once.
516
33002204 12/2010
DFBs (Derived Function Blocks)
Calling up a DFB in Ladder Diagram LD
Note
When a DFB is called up, it is not significant which program languages it was created
in. The DFB can be called up in all the IEC sections.
Description
To call up a DFB in Ladder Diagram LD, do the following:
Step
33002204 12/2010
Action
1
Close the Concept DFB and start Concept.
2
Open or create a project and open or create a section.
3
As with an EFB, the DFB is called up using the command button: Objects →
Select FFB....
Reaction: The dialog box FFBs from library is opened.
4
Press the DFB command button to display the global and local DFBs.
For example:
5
Now click on the DFB required in the list, and position it in the Editor window.
For example:
517
DFBs (Derived Function Blocks)
Step
Action
6
Double-clicking on the DFB opens the Properties: Derived Function Block
dialog box, where the Refine... command button can be used to open a
document window with the internal DFB logic. The gray background indicates
that the DFB cannot be edited in this document window.
7
Use the left power rail to link the EN input.
8
Now only the actual parameter needs to be defined. This is performed in a way
corresponding to the normal EFB link using the Link FFB dialog box (doubleclick on the inputs/outputs to be parametered.
For example:
Reaction: As is clear from the example, two different sets of parameters are
used in the DFB call 1 and 2. The formal parameters are the same in both calls
because the program code of the DFB is only occupied once.
518
33002204 12/2010
DFBs (Derived Function Blocks)
Calling up a DFB in the IL instruction list
Note
When a DFB is called up, it is not significant which program languages it was created
in. The DFB can be called up in all the IEC sections.
Description
To call up a DFB in the IL instruction list, do the following:
Step
33002204 12/2010
Action
1
Close the Concept DFB and start Concept.
2
Open or create a project and open or create a section.
3
Calling up a DFB in the IL is performed like Calling up a Function Block
(see page 372).
For example:
VAR
SKOE1, SKOE2 : SKOE;
(* Instancing the DFBs *)
END_VAR
CAL SKOE1(IN1:=VALUE1,IN2:=VALUE2,IN3:=VALUE3,IN4:=VALUE4)
LD SKOE1.out
(* DFB Call 1 *)
ST RESULT1
CAL SKOE2(IN1:=VALUE5,IN2:=VALUE6,IN3:=VALUE7,IN8:=VALUE4)
LD SKOE2.out
(* DFB Call 2 *)
ST RESULT2
Reaction: As is clear from the example, two different sets of parameters are used
in the DFB calls 1 and 2. The formal parameters are the same in both calls because
the program code of the DFB is only occupied once.
519
DFBs (Derived Function Blocks)
Calling up a DFB in structured text ST
Note
When a DFB is called up, it is not significant which program languages it was created
in. The DFB can be called up in all the IEC sections.
Description
The procedure for calling up a DFB in structured text ST is as follows:
Step
520
Action
1
Close the Concept DFB and start Concept.
2
Open or create a project and open or create a section.
3
Calling up a DFB in the ST is performed like Calling up a Function Block
(see page 442).
For example:
VAR
SKOE1, SKOE2 : SKOE;
(* Instancing the DFBs *)
END_VAR
SKOE1(IN1:=VALUE1, IN2:=VALUE2, IN3:=VALUE3, IN4:=VALUE4);
RESULT1:=SKOE1.OUT ;
(* DFB Call 1 *)
SKOE2(IN1:=VALUE5, IN2:=VALUE6, IN3:=VALUE7, IN4:=VALUE8);
RESULT2:=SKOE2.OUT ;
(* DFB Call 2 *)
Reaction: As is clear from the example, two different sets of parameters are used
in the DFB calls 1 and 2. The formal parameters are the same in both calls because
the program code of the DFB is only occupied once.
33002204 12/2010
Macros
33002204 12/2010
Macros
14
Overview
This Chapter describes the procedure for creating macros with help from Concept
DFB.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
14.1
Macro
522
14.2
Programming and calling up a macro
531
521
Macros
14.1
Macro
Overview
This section provides an overview on creating and applying macros.
What's in this Section?
This section contains the following topics:
Topic
522
Page
Macros: general
523
Global / Local Macros
525
Exchange marking
527
Creating Context Sensitive Help (Online Help) for Macros
529
33002204 12/2010
Macros
Macros: general
At a Glance
Macros are used to duplicate frequently used sections and networks (including their
logic, variables and variable declaration).
Creating macros
Macros are created with the help of the Concept DFB software.
Programming languages
Macros can only be created in the FBD and LD programming languages.
Properties
Macros have the following properties:
z Macros only contain one section.
z Macros can contain a section of any complexity.
z From the point of view of program technology, there is no difference between an
instanced macro, i.e. a macro inserted into a section and a conventionally created
section.
z It is possible to call up DFBs in a macro.
z It is possible to declare macro-specific variables for the macro.
z It is possible to use data structures specific to the macro
z Automatic transfer of the variables declared in the macro.
z Initial values are possible for the macro variables.
z It is possible to instance a macro many times in the entire program with different
variables.
z The name of the section, variable names and data structure names can contain
up to 10 different exchange marks (@0 to @9).
Hierarchic structure
The hierarchic structure of a macro corresponds to a project in Concept which
consists of only one section. This section contains the actual logic.
Context help
Personalised context-sensitive help (online help) can be generated for macros (see
Creating Context Sensitive Help (Online Help) for Macros, page 529).
Processing sequence
The processing sequence of the logic, the programming rules and the usable FFBs
and DFBs correspond overall to those of the FBD or LD programming.
33002204 12/2010
523
Macros
Calling up a macro
A macro can be called up from SFC, FBD and LD sections.
There is a fundamental difference here:
Call from an SFC Section
When a macro is called up (instanced) from an SFC section (e.g. as a network
for the action variable), a new FBD/LD section containing only the macro’s logic
is automatically created
z Calling up an FBD/LD section
When a macro is called up from an FBD or LD section, the macro’s logic is
inserted into the current FBD or LD section. In this case a new section is not
created.
z
Archiving and Documentation
The process for archiving a macro is the same as for archiving and documenting a
project (see Documentation and Archiving, page 729).
524
33002204 12/2010
Macros
Global / Local Macros
Description
Global and local macros differ in the locality of their directory hierarchy.
Depending on the directory or subdirectory in which the macro is stored, it can be
called up globally, i.e. within all the projects created under Concept, or locally, in a
specific project.
In the Defining the Storage of Global DFBs during Upload, page 1110 you can
ensure that during the IEC upload process a GLB directory containing the global
macros is produced in the project directory. By doing this, the existing global macros
in the Concept →DFB will not be overwritten and therefore it will not have an effect
on other projects.
Directory structure without uploaded project:
33002204 12/2010
525
Macros
Directory structure according to INI settings ([Upload]: PreserveGlobalDFBs=1)
for uploaded projects:
If a local and a global macro have the same name, the name of the local macro is
displayed in lower case letters and that of the global macro in upper case letters
when they are inserted.
NOTE: The length of the DOS path name in which the macros is stored is limited to
29 characters. Care should be taken that the macro directory does not exceed this
limit.
526
33002204 12/2010
Macros
Exchange marking
At a Glance
The exchange markings (@0 to @9) in macros are used to insert the macro in a
Concept section. When inserting a macro into a section, you will input a character
string that will replace the character strings. It is therefore possible to use a logically
identical macro with different variables, data structures and comments, because
different series of character strings can be pre-set during each insertion.
The exchange flags can be used in the following elements:
z Section names
z Variable names
z Comments
Comment on exchange markings
A comment on the macro’s exchange marking can be written usingFile →Section
Properties. This comment will be displayed when the macro is called up in Concept
the in the exchange marking’s replacement dialog.
Exchange marking in the section name
When a macro is instanced, i.e. when it is called up from an SFC section, a new
section is automatically occupied with the name of the macro section, as well as
other procedures. The section name must be changed with each instancing so that
the macro can be instanced several times in one project. The exchange marking in
the section name is used for this. Therefore an exchange marking (@0 to @9)
should always be entered when a section is created in the macro. Otherwise the
macro can only be called up once from an SFC section and used in the project.
When a macro is called up from an FBD/LD section, the section name of the macro
is not significant because no new section is created in this case.
Exchange marking in variable names
Input and output variables are required to transfer values to or from a network.
These variables are already declared in the macro and are connected to the macro’s
EFBs.
To declare these variables, the variable name (with exchange markings), the data
type and possibly a comment (possibly with exchange markings) should be declared
in the variables editor. An initial value can also be defined for input variables.
When a macro is instanced in Concept, the exchange markings in all the variable
names are replaced with the pre-set character strings. This ensures that the
variables required for each use of the macro are clearly declared. If a variable is
used in all cases of macro instancing, it should be given a name without the
exchange marking.
33002204 12/2010
527
Macros
The same applies to variables with Derived Data Types (data structures). This
means that the type of one data structure can be used in as many macros as
required as often as required.
Exchange markings in the Variables Editor
NOTE: If the macro is to be connected as an action to a step in a sequence, it is
advisable to denote the variable designated as an action variable only with the @0
exchange marking. In this case, the designated action variable will automatically be
connected to the step when the macro is instanced. Care should be taken that the
action variables are always of the BOOL type. If the macro contains several action
variables (e.g. for the forward and backward running of a motor), it is advisable to
define these action variables in a Derived Data Type (data structure) and to denote
the variable which this data type is assigned to with the @0 exchange marking only.
Since a clear variable is assigned to each input/output during the instancing of the
macro, only unlocated variables can be assigned to the macro when it is created. It
is not possible to use direct addresses and located variables in the macro. If located
variables are to be used, the corresponding variables can be assigned a direct
address in the variables editor after the macro is instanced. If direct addresses are
to be used, no variables should be assigned to the corresponding inputs/outputs in
the macro and the inputs/outputs should be linked to the address desired after the
macro is instanced. If variables have already been declared, they are used
(references and initial values are retained).
Exchange marking in comments
When a macro is instanced in Concept, the exchange markings in all the comments
are replaced with the pre-set character strings. The same applies to text objects in
the section and to variable comments in the variables editor.
528
33002204 12/2010
Macros
Creating Context Sensitive Help (Online Help) for Macros
Introduction
In Concept, help is provided for each EFB, which can be invoked according to the
context (the Help on Type command button in the EFB properties dialog). There is
of course no corresponding help text in Concept for the macros that you created.
You can, however, create your own help for each macro, that can be invoked in
Concept with Help on Type.
File Format:
You can create your help in the following file formats:
.CHM (Microsoft Windows compiled HTML help file)
z .DOC (Microsoft Word format)
z .HTM (Hypertext Markup Language)
z .HLP (Microsoft Windows help file (16- or 32-Bit Format))
z .PDF (Adobe Portable Document Format
z .RTF (Microsoft Rich Text Format)
z .TXT (Plain ASCII Text-Format)
z
Name
The name of the help file must be exactly the same as the name of the macro (e.g.
SKOE.EXT)
The only exceptions are standardized macro names (e.g. SKOE_BOOL,
SKOE_REAL etc.). In these cases the help file name is the macro name without the
datatype extension (e.g. macro name) SKOE_BOOL has the help file SKOE.EXT).
Directory
The help file can be stored in the following directories:
z Concept directory
z Concept Help directory (if defined in the file CONCEPT.INI, see readme)
z Global macro directory
z Local macro directory
33002204 12/2010
529
Macros
Invoking the Help File
Concept carries out the following procedure to invoke the help file:
Phase
1
Description
Search for the help file MacroName.EXT in the local macro-directory.
The help file is searched for in the following sequence:
z .HLP
z .CHM
z .HTM
z .RTF
z .DOC
z .TXT
z .PDF
Result: If the search result is positive the help file will be displayed, otherwise it
will continue with phase 2.
530
2
Search for the help file MacroName.EXT in the global macro-directory.
For the order, see phase 1.
Result: If the search result is positive the help file will be displayed, otherwise it
will continue with phase 3.
3
Search for the help file MacroName.EXT in the Concept-directory or ConceptHelp directory.
For the order, see phase 1.
Result: If the search result is positive the help file will be displayed, otherwise it
will continue with phase 4.
4
Display of the comment created in Concept DFB with Project →Properties.
33002204 12/2010
Macros
14.2
Programming and calling up a macro
Overview
This section describes programming and calling up a macro.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
At a Glance
532
Occupying the macro
533
Creating the logic
534
Calling up a macro from an SFC section
537
Calling a macro from an FBD/LD section.
540
531
Macros
At a Glance
At a Glance
Programming and calling up a macro is divided into 3 main steps:
Step
532
Action
1
Occupying the macro (see page 533)
2
Creating the logic (see page 534)
3
Calling up the macro in:
z Sequence language (SFC) (see page 537)
z Function Block language (FBD) (see page 540)
z Ladder Diagram language (LD) (see page 540)
33002204 12/2010
Macros
Occupying the macro
Description
The procedure for occupying the macro is as follows:
Step
33002204 12/2010
Action
1
Close Concept and start Concept DFB.
2
Create a new macro usingFile →New macro... menu command.
Reaction: The name now appears on the title bar: [untitled].
3
Using the menu command File →New section... generate a new section and
enter a section name (with an exchange marking such as @0).
The section name (max. 32 characters) must be clear throughout the macro, and
it is not case-sensitive. If the section name entered already exists, a warning is
given and another name must be chosen. The section name must correspond to
the IEC Name conventions, otherwise an error message appears.
Note: In accordance with IEC1131-3, only letters are permitted as the first
character of names. If, however numbers are required as the first character, this
can be enabled using the menu commandPresettings →Presettings →IEC
Expansions... →IEC Expansions →Enable leading figures in identifiers .
4
Select a programming language for the section:
z Function Block language (FBD)
z Ladder Diagram (LD)
5
The menu command Project →Properties can be used to generate a comment
on the macro.
Reaction: The comment can then be displayed in Concept using the Help for
type command key in the selection dialog for macros.
6
The menu command File →Section properties can be used to generate a
comment on the exchange markings.
Reaction: This comment then appears automatically in the Replace dialog for
the exchange markings.
7
Save the macro with the menu command File →Save macro.
Reaction: The first time the Save is used, the Save as dialog box opens –
specify the macro name and directory where it is to be saved here.
8
Select the directory to be occupied by the macro. Attention should be paid to the
difference between global and local macros (see also Global / Local Macros,
page 525).
9
Enter the macro name (max. 8 characters, always with the Extension Mac).
The name must be clear throughout the directory, and it is not case-sensitive. If
the section name entered already exists, a warning is given and another name
must be chosen.
533
Macros
Creating the logic
Description
The procedure for creating the logic is as follows:
Step
534
Action
1
To insert an FFB into the section, select the menu command Objects →Select
FFB....
Reaction: The FFBs in IEC library dialog box opens.
2
In this dialog box a library can be selected and an FFB selected from it by using
the Library... command button. Also with the command button DFB the
manually generated DFBs can be shown and one selected from them.
3
Place the selected FFB in the section.
4
When all FFBs have been positioned, close the dialog box with Close
5
Activate the selection mode with Objects →Selection mode, click on the FFB
and move the FFBs to the position required.
6
Activate the link mode with Objects →Link and connect the FFBs.
33002204 12/2010
Macros
Step
7
Action
Activate the Variables Editor withProject →Variables Editor to declare the
variables.
For unlocated variables, declare a name here (with exchange markings), a data
type, an initial value and a comment if necessary (possibly with exchange
markings).
For constants, declare a name here (with exchange markings), a data type, a
value and a comment if necessary (possibly with exchange markings).
For example:
Note: If located variables are to be used, the corresponding unlocated variables
can be assigned a direct address in the variables editor after the macro is
instanced.
If direct addresses are to be used, no variables should be assigned to the
corresponding inputs/outputs in the macro and the inputs/outputs should be
linked to the address required after the macro is instanced.
Note: If a variable or constant is to be used in all cases of macro instancing, this
variable or constant should be given a name without any exchange marking.
33002204 12/2010
535
Macros
Step
536
Action
8
Then re-activate the selection mode with Objects →Select and double-click on
one of the unconnected inputs/outputs.
Reaction: The Link FFB dialog box opens, where an actual parameter can be
assigned to the input/output.
9
Save the macro with the menu command File →Save.
For example:
33002204 12/2010
Macros
Calling up a macro from an SFC section
Description of the action
The procedure for calling up a macro from an SFC section is as follows:
Step
Action
1
Close Concept DFB.
2
Start Concept, open or create a project and open or create an SFC section.
3
Double-click to open the step properties of the step which the macro is to be
connected to.
4
Use the command button Instance section... to call up the dialog for instancing
the macros.
5
Select the desired macro from the list.
If section groups have been created in the Project Browser, the section group
where the section is to be inserted can be selected in the Insert into section
group text field.
Confirm with OK.
Example:
Reaction: The dialog Replace is opened to replace the exchange markings.
33002204 12/2010
537
Macros
Step
6
538
Action
Pre-set for the text fields @0 to @9 the character strings which the exchange
markings are to be replaced with in the macro.
Example:
33002204 12/2010
Macros
Step
33002204 12/2010
Action
7
Confirm the inputs with OK.
Reaction:
The following occurs after the procedure described above has been performed:
z A section is now automatically created whose name consists of the macro
section name and of the pre-set character strings in place of the exchange
marking.
Note: This section is not automatically opened. To perform any editing, open
by clicking on the variable name in the step properties dialog.
z All the variables declared in the macro are transferred into the variables
declaration of the current project and the exchange marking is also replaced
with the current character string. If variables have already been declared,
they are used (references and initial values are retained). The same applies
to any comments containing the exchange flags.
z If the macro contains a single Boolean input variable, it is automatically
transferred as an action variable.
z If the macro contains several Boolean input variables, the Select one of
these variables dialog opens, where the variable desired can be selected as
an action variable.
z If a data structure has been marked individually with the exchange flag, the
Select Bool type elements dialog is called up and the Boolean variable
desired for the action can be selected there.
8
This action can be used to call the macro as often as required without any name
collisions occurring. The instanced macro and its variables are completely
identical to the sections and variables generated beforehand.
Example of an instanced macro:
539
Macros
Calling a macro from an FBD/LD section.
Description of the action
The procedure for calling up a macro from an FBD/LD section is as follows:
Step
540
Action
1
Close Concept DFB.
2
Start Concept, open or create a project and open or create an FBD/LD section.
3
With the menu command Objects →Macro insert the dialog Select macro to
insert macros into FBD/LD sections.
4
Select the desired macro from the list and confirm with OK.
Reaction: The dialog Replace is opened to replace the exchange markings.
5
Pre-set for the text fields @0 to @9 the character strings which the exchange
markings are to be replaced with in the macro.
Example:
33002204 12/2010
Macros
Step
33002204 12/2010
Action
6
Confirm the inputs with OK.
Reaction:
The following occurs after the procedure described above has been performed:
z There is now an automatic shift to Insert mode and the macro’s logic can be
inserted in any position in the FBD or LD section.
z Moreover, all the variables declared in the macro are transferred into the
variable declaration of the current project and the exchange marking is also
replaced with the current character string. The same applies to any
comments containing the exchange markings.
7
This action can be used to call the macro as often as required without any name
collisions occurring. The inserted macro and its variables are completely
identical to the sections and variables generated conventionally.
Example of an instanced macro:
541
Macros
542
33002204 12/2010
Variables editor
33002204 12/2010
Variables editor
15
Overview
This Section contains information about declaring variables in the variables editor.
What's in this Chapter?
This chapter contains the following topics:
Topic
33002204 12/2010
Page
General
544
Declare variables
545
Searching and replacing variable names and addresses
548
Searching and Pasting Variable Names and Addresses
552
Exporting located variables
556
543
Variables editor
General
At a Glance
The Variables-Declaration serves as data exchange in user program. Hence you
can address Variables (Located and Unlocated Variables) and/or assign a value to
constants
Variables or direct addresses will be assigned via the addressing of the I/O-Map and
can be used with symbolic names (variable) or with the direct addresses in the
programming. In so doing, values will be exchanged between different Sections via
the variables or the direct addresses.
NOTE: In accordance with IEC1131-3, only letters are permitted as the first
character of variable names. If, however numbers are required as the first character,
this can be enabled using the menu commandOptions →Presettings →IEC
Expansions... →IEC Expansions →Enable leading figures in identifiers
enable.
NOTE: Undeclared variables will be denied during programming.
544
33002204 12/2010
Variables editor
Declare variables
At a Glance
At variable declaration the Data type, address and symbolic name are determined.
Via the addressing define the inputs (1x/3x) and outputs (0x/4x), assigned in the
user program with the selection of the data type of the respective function, or the
respective Function Blocks.
An initial value may also be provided for each variable; this will be transferred into
the PLC during the first load.
A comment may be written for each Variable or direct address, to aid recognition of
the assignment of a function.
If Declarations are changed, deleted or added, this alteration will be identified
through certain symbols in the first column.
Changes in ONLINE mode
Variable names and addresses can be changed online. Apart from that, an
unlocated variable can be changed into a located variable (i.e. it will be assigned its
own address or the address will be deleted). Clicking on the command button OK
transfers the changes to the affected sections i.e. the sections in which the changed
variables will be used.
This has the following effects:
If…
Then…
the variables are modified, the status of all affected sections will be set to MODIFIED and
the affected sections must be loaded into the PLC using Online
→Load modifications.
a transition section is
affected by the
modifications,
the SFC section assigned to it is also set to the status
MODIFIED.
an affected section is
animated,
the animation is aborted.
a modified variable is used no more variables can be inserted into the editor window, and
the animation of the reference data editor is stopped. This is
in the reference data
valid until the modifications are loaded into the PLC using
editor,
Online →Load modifications and the status EQUAL is
restored.
NOTE: The assignment of direct addresses and comments can also occur outside
Concept on completion of the programming.
33002204 12/2010
545
Variables editor
Variable declaration outside the variable editor
Procedure for completing variable declaration outside the variable editor:
Step
Action
1
Export the variable declaration using File →Export →Variables: Text
delimited.
2
Open the exported file.
3
Enter the addresses and comments.
4
Import the edited variable declaration using File →Import →Variables: Text
delimited.
Copying rows in the variable editor
It is possible to copy individual rows and whole blocks of rows and to paste them into
another position in the variable editor, before editing them. This operation is
performed using shortcut keys.
Copying and pasting can only take place inside the open variable editor; pasted
rows are marked red. These rows must subsequently be changed or they will
disappear on exiting the dialog. Identical settings are not permitted in the variable
editor.
NOTE: A maximum of 500 rows can be copied.
Procedure for copying and pasting
To copy and paste entire rows proceed as follows:
Step
546
Action
1
Select the relevant row in the first column in the table.
Reaction: The entire row is displayed in a different color.
Note: When copying a block of rows, select the first row in the block, and press
Shift, while simultaneously selecting the last row in the block.
2
To copy use the shortcut Ctrl+Insert or Ctrl+Alt+c.
Reaction: The selected rows are copied into the cache.
3
Select the row off which is to be pasted.
Reaction: The entire row is displayed in a different color.
4
To paste use the shortcut Shift+Insert or Ctrl+Alt+v.
Reaction: The copied rows are pasted off the selected row in the table, and are
marked red.
Note: When pasting between two existing rows, the selected row is moved down
according to the number of copied rows.
33002204 12/2010
Variables editor
Printing the variable list
Printing the variable list is done in the main menu File. Using the menu command
Print... open the dialog Document contents, in which the print undertaking is set
by checking the box Variable list.
NOTE: It should be noted that all 32 characters (maximum) of the symbol name do
not always appear on the paper when printing.
33002204 12/2010
547
Variables editor
Searching and replacing variable names and addresses
At a Glance
Use command button Search/Replace to call up a dialog box to search and replace
variable names and addresses. Therefore, unlike Search/Insert the existing
variable names/addresses are changed.
Use option button Name and Address to choose whether to search for variable
names or addresses.
If Search and Replace are to be restricted to a certain area of variables or
addresses, this area can be selected. In this case, searching and replacing is only
carried out in the selected area. If nothing is selected, search and replace are
applicable to all variables and addresses in the variable editor.
On activating check box Extend address the addresses specified in text box
Address are automatically extended to Standard format.
Use of wildcards
The following wildcards can be used for searching and replacing:
* This character is used to represent any number of characters. * can only be used
at the beginning or the end of a line.
? This character is used to represent exactly one character. If several characters are
to be ignored, a certain number of ? have to be used.
The wildcards can be combined. The combinations *? and ?* are, however, not
permitted.
NOTE: When searching and replacing, the number of wildcards in the Search
character sequence and the Replace character sequence have to be equal. See
also the following examples in the table.
548
33002204 12/2010
Variables editor
Examples of Search/Replace
The example shows different search methods and the respective results when
replacing:
Search:
Replace with:
available names
Result
Name1
Name2
Name1
Name1A
Name A
Name B
Name2
Name1A
NameA
NameB
???123
???456
abc123
cde123
abcd123
abc1234
abc456
cde456
abcd123
abc1234
Name1*
Name2*
Name1A
Name1B
NameAB
Name2A
Name2B
NameAB
*123
*456
abc123
cde123
abc1234
abcde123
abc456
cde456
abc4564
abcde456
*123*
*456*
abc123abc
cde123defghi
abcde123def
abc456abc
cde456defghi
abcde456def
???123*
???456*
abc123abc
cde123defghi
abcde123def
abc456abc
cde456defghi
abcde123def
Search and replace name
Select this option button to search and replace variable names. However, the search
for the occurrence of the character sequence to be found is exclusively carried out
in column Variable name of the variable editor.
Search and replace address
Select this option button, to search and replace addresses. However the search for
the occurrence of the address to be found is exclusively carried out in column
Address of the variable editor.
33002204 12/2010
549
Variables editor
Search for:
Enter a character sequence, according to which the variables or addresses are to
be searched.
Without entering a character sequence that leads to a successful search result,
none of the possible functions of the dialog are executed.
NOTE: Entries in the field Search remain intact for future use, even after closing the
dialog box.
Replace with:
Enter a character sequence, which replaces the character sequence to be searched
for in the new variables or addresses
NOTE: Entries in the field Replace with remain intact for future use even after
closing the dialog box.
Find Next
Description of function Find Next:
Stage
550
Description
1
The command button Find Next starts the search process at the beginning of
the variable editor table or the selected area and marks the found variable.
2
A query appears, asking whether a search for further occurrences of the
character sequence is required.
3
By activating command button Yes, the next location of the searched character
sequence is selected.
By activating command button No, the search is terminated.
4
When the search process has reached the end of the variable editor table, the
system asks whether or not the search process should be restarted at the
beginning of the variable editor table or the selected area.
5
By activating command button Yes, the next location of the searched character
sequence is selected.
By activating command button No, the search is terminated.
6
If no further occurrences of the character sequence are found, a message
appears, indicating that the search is terminated.
33002204 12/2010
Variables editor
Replace
Description of function Replace:
Stage
Description
1
The command button Replace starts the search process at the beginning of the
variable editor table or the selected area and marks the found variable.
Note: This function cannot be undone.
2
The system asks whether the found character sequence is to be replaced.
3
By activating command button Yes, the variable/address is replaced by the
character sequence in the text box Replace with:
By activating command button No, the search is terminated.
4
If there are several uses of the searched character sequence, the next site where
it is found is selected and a new query appears.
5
When the search process has reached the end of the variable editor table, the
system asks whether or not the search process should be restarted at the
beginning of the variable editor table or the selected area.
6
By activating command button Yes, the next location of the searched character
sequence is selected.
By activating command button No, the search is terminated.
7
If no further occurrences of the character sequence are found, a message
appears, indicating that the search is terminated.
Replace all
Searches for all occurrences of the character sequence and replaces these (without
first querying) with the inputs in the text box Replace with:. When the search
process has reached the end of the variable editor table, the system asks whether
or not the search process should be restarted at the beginning of the variable editor
table or the selected area.
NOTE: This function cannot be undone.
33002204 12/2010
551
Variables editor
Searching and Pasting Variable Names and Addresses
Introduction
The Search/Paste command button can be used to invoke a dialog for creating new
variables based on existing ones. Unlike with Search/Replace, a copy of the
existing variables with a new name/address is generated.
If, for example, you have already declared the variables for a motor and you want to
declare the same variables but with different names and addresses for another
motor, this is easily achieved with this dialog.
If you simply want to generate further variables from a specific range of variables,
this area can be selected. In this case, a search will only be carried out in the
selected range. If nothing is selected, search and paste applies to all variables in the
variable editor.
If you check the Extend Address check box, the addresses entered in the Address
text box are automatically extended to Standard format.
Using Wildcards
The following wildcards can be used for searching and pasting:
* This character is used to represent any number of characters. * can only be used
at the beginning or the end of a line.
? This character is used to represent exactly one character. If several characters are
to be ignored, the corresponding number of ? have to be used.
The wild cards can be combined. The combinations *? and ?* are, however, not
permitted.
NOTE: When searching and pasting, the number of wildcards in the Search string
and the Replace string has to be equal.
Find Name
If you select this option button, you can search for variable names. Occurrences of
the string to be found are searched for exclusively in the Variable Name column of
the variable editor.
Find Address
This field is only unavailable for constants.
If you select this option button you can search for addresses. Occurrences of the
address to be found are searched for exclusively in the Address column of the
variable editor.
552
33002204 12/2010
Variables editor
Find What:
Enter a string to be searched for in variables or addresses.
The search is only carried out in the Variable Name and Address columns in the
variable editor table. A search in other areas (e.g. Data type) is not possible.
If you do not enter a string that leads to a successful search result, none of the
possible functions of the dialog are executed.
NOTE: Entries in the Search field are retained for future use, even after the dialog
box is closed.
Replace With:
Enter a string to be replaced in the new variable or address with the string being
searched for.
If the name entered already exists, no new variable is created.
NOTE: Entries in the Replace With field are retained for future use even after the
dialog box is closed.
Offset Address By:
This field is only unavailable for constants.
Enter a value by which the addresses of the existing variables are to be increased.
NOTE: If you do not enter an offset value, the new variable will be placed in the
same address as the one already present.
With unlocated variables, it is not necessary to enter a value.
Entries in this field are retained for future use even after the dialog has been closed.
Example of Offset Address By
SKOE1 has the address 000012
Find What: SKOE1
Replace With: SKOE2
Offset Address By: 1
This results in the creation of the following new variable:
SKOE2 on address 000013
33002204 12/2010
553
Variables editor
Find Next
Description of Find Next function:
Stage
Description
1
The Find Next command button starts the search process at the beginning of
the variable editor table or the selected area and marks the found variable.
2
A query appears, asking whether a search for further occurrences of the string
is required.
3
If the Yes command button is pressed, the next location of the string being
searched for is marked.
If the No command button is pressed, the search is finished.
4
When the search process has reached the end of the variable editor table, a
query appears asking whether or not the search process should be restarted at
the beginning of the variable editor table or the selected area.
5
If the Yes command button is pressed, the next location of the string being
searched for is marked.
If the No command button is pressed, the search is finished.
6
If no further occurrence of the string is found, a message appears to inform you
that the search is done.
Start Paste
Description of Start Paste function:
Stage
554
Description
1
The Start Paste command button is used to start the search process at the
beginning of the variable editor table or the selected area and the found variable
is marked.
Note: This function cannot be undone.
2
A query appears asking whether a new variable with the displayed name and
address should be created.
3
If the Yes command button is pressed, the variable is created and the process
continued until all occurrences of the string being searched for have been
"exhausted".
If the No command button is pressed, the search is finished.
4
When the search process has reached the end of the variable editor table, the
system asks whether the search process should be restarted at the beginning of
the variable editor table or the selected area.
5
If the Yes command button is pressed, the next location of the string being
searched for is marked.
If the No command button is pressed, the search is finished.
6
If no further occurrence of the string are found, a message appears to inform you
that the search is finished.
33002204 12/2010
Variables editor
Paste All
Searches for all occurrences of the string to be found and replaces them (without
asking first) with the new variables given in the Replace With: text box. This process
is carried out until all occurrences of the string being searched for have been
exhausted, or until an error appears.
If an error appears, the function is immediately cancelled. However, all the
previously created variables are retained.
NOTE: This function cannot be undone.
33002204 12/2010
555
Variables editor
Exporting located variables
At a Glance
For data exchange with MMI units, all Located variables in the column Exp can be
selected and transferred using the Export function in the main menu File.
Located variables can be exported via ModLink, Factory Link and via export format
"text delimited".
Removing the selection
After export, the selection (in the column Exp) of the exported variables using the
shortcut Ctrl+Alt+F3 can be removed at once.
NOTE: This removal cannot be undone, not even with the command button Cancel.
556
33002204 12/2010
Project Browser
33002204 12/2010
Project Browser
16
Overview
This chapter describes the Project Browser.
What's in this Chapter?
This chapter contains the following topics:
Topic
33002204 12/2010
Page
General information about the Project Browser
558
Detailed view in the project browser
561
Operating the Project Browser
563
557
Project Browser
General information about the Project Browser
Introduction
The Project browser can be used to create groups of sections to make the layout
clearer and to facilitate operations. These groups have unique names and can
contain sections and further section groups. The display and operations are
performed graphically by means of Structure tree. The Project browser functions
represent a convenient, more extensive way of operating as an alternative to the
Concept functions present.
You can open an additional window in the Project browser for viewing existing DFBs,
sections with control blocks and transition sections.
Project browser:
558
33002204 12/2010
Project Browser
Functions
The Project browser provides the following functions:
z Create new section
z Open section (override the editor)
z Changing section properties (names, comments)
z Changing the execution order
z Delete section
z Creating section groups
z Opening section groups (showing the substructure)
z Closing section groups (hiding the substructure)
z Renaming section groups
z Finding section groups or sections in the Project browser
z Moving sections groups or sections (modification of the execution sequence
results!)
z Start up offline memory prognosis
z Deleting section groups
z Opening the Configurator
z Minimize open windows
z Open minimized windows
z Close all windows
z Set maximizing window size
z Show exact view
z Excluding individual sections from the alignment between the primary CPU and
standby CPU with Hot Standby systems.
z Animate enable states (animation of the structure tree)
z Switch enable state
Restrictions
Attention should be paid to the following restrictions:
Section groups can only be created with the Project browser.
z Transition sections are not displayed in the Project browser.
z It is only possible to modify the execution sequence via Project →Execution
order if no section groups exist in the Project browser. After the first section group
has been created, no further modifications can be performed via Project →
Execution order change.
z It is only possible to change the enable status of a section if the variable
belonging to the section (.disable) has not been used.
z
Special features for LL984
Attention should be paid to the following special features when using LL984:
If one or several LL984 sections exist, the Project browser automatically
generates an LL984 section group.
z LL984 sections cannot be moved.
z No IEC sections can be put into or before the LL984 section groups.
z
33002204 12/2010
559
Project Browser
Special features of I/O Events and Timer Events
Please take note of the following special features when using interrupt sections:
z If one or several LL984 sections exist, the Project browser automatically
generates an I/O Event or Timer Event section group.
z Interrupt sections cannot be moved.
z No IEC sections can be put into or before the interrupt section group.
560
33002204 12/2010
Project Browser
Detailed view in the project browser
Introduction
In the shortcut menu for the project, you can divide the project browser window
vertically using the menu command Show detailed view. The right side of the
window contains the detailed information concerning the selected element in the
project structure tree.
The type of information depends on the selected element:
Element
Information
Project
Call hierarchy for all DFBs used in the project.
Group
No display
LL984 section
No display
FBD/LD
Call hierarchy for all DFBs used in the section. If no DFBs are used, a
message is given (!).
ST/IL
Call hierarchy for all DFBs used in the section. If no DFBs are used,
or if the analysis fails, a message is given (!).
SFC
The SFC info module can contain the following information:
z Section which contains the control module (e.g. SFC_CTRL) for
this SFC section.
z Message with red exclamation point(!): The SFC section is in the
execution order before the section with the control module.
z Message with a black exclamation point(!): No transition sections
are used.
z All transition sections used.
33002204 12/2010
561
Project Browser
Detailed view in the right window of the project browser:
562
33002204 12/2010
Project Browser
Operating the Project Browser
Introduction
The browser allows keyboard and mouse operation.
Mouse operation
Operating the project browser with the mouse:
Function
Key
Selecting a group or section
(during selection, a section which is already
open is put before all other open sections)
left mouse button
Switching off the context menu
right mouse button
Using the first menu entry of the context menu Double-click with the left mouse button
Moving a group or section
left-click on the corresponding symbol and
hold the mouse button, select the target
position by moving the mouse and release
the mouse button
or
Call context menu (right mouse button) →
Select Move →Find target position by
cursor up/down →Confirm position with
Enter
Opening or closing a section group
click on the corresponding +/- symbol with
the left mouse button
NOTE: Context menus do not only appear when symbols are clicked on. The
following way to insert a new group or section is available: If the cursor is positioned
to the right of the connecting line between two symbols, it changes to show that a
context menu can be called in this location by clicking with the right mouse button.
This means that a new group or section can be inserted in the line selected.
33002204 12/2010
563
Project Browser
Keyboard operation
Operating the project browser with the keyboard:
564
Function
Key
selecting the next/previous group/section
(during selection, a section which is already
open is put before all other open sections)
Cursor up/Cursor down
Selecting a group/section on the next or
previous page
Scroll up/Scroll down
Selecting a project symbol
Pos1
selecting the last group or section
End
Scrolling with the keyboard
CTRL + Cursor up/Cursor down
or
CTRL + Scroll up/Scroll down
Switching off the context menu
SWITCH + F10
or List
Carrying out the first menu entry
Entry
Moving a group/section
Call context menu (SWITCH + F10) →
Select Move →Find target position by
cursor up/down →Confirm position with
Enter
or
CTRL + SWITCH →Cursor up/down /
Scroll up/down →Confirm position with
Enter
Opening or closing a section group
+ or where: + restores the status before the last -
Opening a section group and all sub-groups
*
Deleting a group or section
Delete
Selecting the group above
Cursor left or backspace delete
If the element actually selected is a group
when cursor left is used, the group is closed
before the higher group is selected.
Selecting the first section/group in a group
Cursor right
If the group is closed and contains a section
or groups, it is opened.
Canceling the move
ESC
33002204 12/2010
Derived data types
33002204 12/2010
Derived data types
17
Overview
This Chapter describes the data type editor and the procedure for creating derived
data types.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
17.1
General information on Derived Data Types
17.2
Syntax of the data type editor
574
17.3
Derived data types using memory
586
17.4
Calling derived data types
588
566
565
Derived data types
17.1
General information on Derived Data Types
Overview
This section contains general information about Derived Data Types.
What's in this Section?
This section contains the following topics:
Topic
566
Page
Derived Data Types
567
Global / Local Derived Data Types
570
Extended Data Type Definition (larger than 64 Kbytes)
572
33002204 12/2010
Derived data types
Derived Data Types
Introduction
Derived data types are defined using the data type editor. All the elementary data
types that already exist in a project and the Derived Data Types can be used to
define new data types.
NOTE: Open the Data Type Editor in Concept/Concept-DFB using File →Open →
File Format Data Type Files (*.DTY).
NOTE: Note that the File →Save and File →Save as menu commands are not
available in this editor. To save the Derived Data Types, select the menu command
File →Exit.
Using Derived Data Types
Various block parameters can be transferred as one set through Derived Data
Types. This set is then divided into individual parameters again in the DFBs and
EFBs; these are processed and then output again as a set or as individual
parameters.
33002204 12/2010
567
Derived data types
Using Derived Data Types in a DFB:
NOTE: For a definition of the Derived Data Types IN and OUT, see Example of a
Derived Data Type, page 576.
Definition of Derived Data Types
The definition of Derived Data Types appears in textual form.
When text is entered, all the standard Windows services for word processing are
available. The data type editor also contains some further commands for text
processing.
Spelling is immediately checked when key words, separators and comments are
entered. If a key word, separator or comment is recognized, it is identified with a
color surround.
568
33002204 12/2010
Derived data types
Name Conventions
The following name conventions apply to derived data types:
z Multi-element variable
If a Derived Data Type is assigned to a variable (field or structure), it is designated
as a multi-element variable.
z Structured variable
If a derived data type is assigned to a variable consisting of several elements, it
is designated as a structured variable. If this is the case, the declaration contains
the keyword STRUCT (see page 577). This also applies if the derived data type
only contains ARRAY declarations.
e.g.
TYPE
EXP:
STRUCT
PAR1: ARRAY [0..1] OF INT;
PAR2: REAL;
PAR3: TEST;
END_STRUCT;
END_TYPE
z Field variable
If a derived data type is assigned to a variable which consists of several ARRAY
Declarations (see page 578), it is designated as a field variable. The key word
STRUCT is not used in this case.
e.g.
TYPE
TEST: ARRAY [0..1] OF UINT;
END_TYPE
33002204 12/2010
569
Derived data types
Global / Local Derived Data Types
Description
Concept differentiates between global Derived Data Types and local Derived Data
Types. Global Derived Data Types can be used in any project (Concept) or in any
DFB (Concept DFB). Global Derived Data Types must be placed in the DFB
subdirectory of the Concept Directory. Local Derived Data Types are only
recognized in the context of a project or its local DFBs and can only be used there.
Local Derived Data Types must be located in the DFB subdirectory of the project
directory.
In the General information on the Concept INI file, page 1107 you can specify that a
GLB directory containing the global Derived Data Types is generated in the project
directory during the IEC upload process. This means existing global Derived Data
Types in Concept →DFB are not overwritten, and there is no effect on other
projects.
NOTE: This file structure should be noted at the creation stage of the Derived Data
Types, because the menu command File →Save as is not available for these. For
this reason it is imperative to ensure that the correct path has been selected prior to
pressing OK.
Directory structure without uploaded project:
570
33002204 12/2010
Derived data types
Directory structure after setting up INI file ([Upload]: PreserveGlobalDFBs=1) for
uploaded projects:
Number of data type files
Concept only supports one single local data type file for each project and only one
single global data type file. To ensure consistency between the host computer and
the PLC, the project containing one of the Derived Data Types must be reloaded into
the PLC after either of these files is edited.
If a local and a global Derived Data Type have the same name, the local Derived
Data Type is given priority.
Maximum File Size
NOTE: The maximum file size (.DTY) for global and local Derived Data Types (i.e.
the definitions and including all comments) is 64 kbytes. If this maximum file size is
too small, the data type definitions can be shared between the global and local data
type file. T
33002204 12/2010
571
Derived data types
Extended Data Type Definition (larger than 64 Kbytes)
At a Glance
The maximum file size (*.dty) for global and local derived data types is 64 KBytes
(this includes the definitions and all comments). To extend this limitation for local
derived data types, you can create an Include file (*.inc), without increasing the size
of the database. This file contains a list of any data type files with the extension *.ddt.
However, the file cannot contain any DTY data type files.
A DDT data type file is structured just like a DTY data type file. Unlike DTY data type
files, a backup copy is not made in the database for DDT data type files. Therefore
it is impossible to determine exactly which data type was recently changed. Each
data type in the DDT data type file looks as if it was changed if the DDT data type
file was changed in any location. All initial values for variables with data types
defined in this DDT data type file are set to 0. The program status will be NOT
EQUAL as well.
The Include file is only allowed to be in the local DFB directory and contains the
name of the project, e.g. TESTPRJ.INC. Changing an Include file is monitored with
check digits.
The Include file has priority over the DTY data type file.
NOTE: Only one Include file can be in the local DFB directory.
The definition of global derived data types has not changed.
Create INC file
An Include file can only contain existing data type files (*.ddt), i.e. the data type files
must exist in the project before creating an Include file.
The DDT data type files can be compared to DTY data type files, they are created
in the same way (see page 575) and can therefore have the same contents.
The Include file is created in the Include file editor.
Carry out the following steps to open the Include file editor:
572
Step
Action
1
Select File →Open and then go to the List files of type list box and select the
option Datatype file (*.dty...).
Reaction: The file types *.dty,*.ddt,*.inc are shown in the File name text box.
2
In the Folder text box, you must select the local DFB directory for your project.
3
In the File name text box, delete all data types except for *.inc.
4
Enter the name of the project as file name, e.g. TESTPRJ.INC.
5
Select OK and another window is opened. Confirm the question of if this file should
be created with Yes.
Reaction: The Include file editor is opened.
33002204 12/2010
Derived data types
With this editor, the Include file created is automatically opened and now contains
all data type files (*.ddt) in the project. The data type files can then be added to the
contents of the Include file to define the Include file.
Only file names are allowed for data type file list, no path entries.
Example of the contents of an Include file:
The check digits are automatically generated by Concept when opening the project.
Limitations
Changes in a DDT data type file or in the Include file do not cause this data type
check. Concept automatically carries out a data type check. The check consists of
many general tests which require a large amount of time.
This smallest change causes the program status to go to NOT EQUAL.
33002204 12/2010
573
Derived data types
17.2
Syntax of the data type editor
Overview
This section describes the syntax to be noted when generating Derived Data Types.
What's in this Section?
This section contains the following topics:
Topic
574
Page
Elements of the Derived Data Types
575
Key Words
577
Names of the derived datatypes
582
Separators
583
Comments
585
33002204 12/2010
Derived data types
Elements of the Derived Data Types
At a Glance
The following elements can be used to generate the Derived Data Types:
z Key words (see page 577)
z Names (see page 582)
z Separators (see page 583)
z Comments (see page 585)
Indents
Indents and line breaks can be inserted at any position where a blank character is
also allowed to make the layout clearer. This does not affect the syntax.
33002204 12/2010
575
Derived data types
Example of a Derived Data Type
Defining Derived Data Types:
576
33002204 12/2010
Derived data types
Key Words
Introduction
The following key words can be used to define the Derived Data Types:
z TYPE ... END_TYPE (see page 577)
z STRUCT ... END_STRUCT (see page 577)
z ARRAY (see page 578)
z "Data types" (see page 581)
In accordance with IEC 113-3, key words must be entered in upper case. If lower
case is also to be used, however, this can be enabled in the dialog box IEC
Extensions using the option Allow case insensitive keywords.
If a key word is recognized, it is identified in colour.
TYPE ... END_TYPE
The key word TYPE denotes the beginning of the data type definitions. The key word
TYPE is only entered once at the beginning of the data type definitions and is then
valid for all subsequent data type definitions.
The key word END_TYPE denotes the end of the data type definitions. The key word
END_TYPE is only entered once at the end of the data type definitions.
STRUCT ... END_STRUCT
The key word STRUCT denotes the beginning of the elements of a Derived Data
Type. Structures are collections of various Elementary and Derived Data Types.
Variables, to which a Derived Data Type like this is assigned, are designated as
structured variables.
The key word END_STRUCT denotes the end of the elements of a Derived Data
Type.
Syntax for STRUCT
STRUCT
NAME1: Data type;
NAME2: Data type;
NAMES: Data type;
END_STRUCT;
33002204 12/2010
577
Derived data types
Example: STRUCT ... END_STRUCT
TYPE
Example1:
STRUCT
Name1: BOOL; (* Comment *)
Name2: INT; (* Comment *)
Name3: ARRAY [0..5] OF BOOL; (* Comment *)
END_STRUCT;
END_TYPE
ARRAY
If several consecutive elements with the same data type are in use, they can be
defined as a field with the key word ARRAY.
After the key word ARRAY, the zone is given, i.e. the number of elements and the
number of the elements’ sub-elements if need be. Finally, the data type common to
all the elements is given. Elementary or Derived Data Types can also be used.
If a Derived Data Type is assigned to a variable in the variable editor consisting of
an ARRAY declaration, it is designated as a field variable.
Syntax for ARRAY
NAME: ARRAY [No. 1.Element .. No. last element, no. 1st element .. no. last
element etc. ] OF data type;
Encapsulation Depth
The encapsulation depth is practically unlimited but should be restricted to a few
stages, e.g. to 2 or 3 dimensions to ensure clarity. The maximum size of a data type
file should not exceed 64KB.
Restrictions
ARRAY indices can not be used in generic functions/function blocks (i.e. SEL and
MUX).
The following operations would generate an error:
k := Arr[a,b,MUX(i,in1=2)];
Arr30[0,1,MUX_INT( K := K, IN0 := 0, IN1 := 1, IN2 := 0)];
ARRAY indices can be used in all other functions/function blocks.
The following operation is possible:
B[8] :=
578
Arr3[REAL_TO_INT(TAN_REAL(ie.real1[2]),j,2]);
33002204 12/2010
Derived data types
Example: One-dimensional ARRAYs
In the following example, a Derived Data Type is defined with the name par. This
Derived Data Type contains 6 elements (par[0] to par [5]) of the BOOL data type.
par: ARRAY [0..5] OF BOOL;
It is not absolutely necessary to begin the range with "0". Any range can be defined.
In this example the Derived Data Type contains 14 elements (par[51] to par [64]) of
the BOOL data type.
par: ARRAY [51..64] OF BOOL;
Example: A one-dimensional ARRAY in a structured variable
ARRAYs can also be used as elements in structured variables (definition with the
key word STRUCT):
Par3: STRUCT
Name1: ARRAY [0..5] OF INT);
Name2: BOOL;
Name3: REAL;
END_STRUCT;
Variables of the Par3 data type contain 3 elements:
z Name1 with 6 sub-elements (Par3.Name1[0] to Par3.Name1[5] of the INT data
type
z Name2 with 1 element of the BOOL data type
z Name3 with 1 element of the REAL data type
Multi-dimensional ARRAYs
In multi-dimensional ARRAYs the statements in [ ] are expanded by the number of
sub-elements of each element. i.e. the element given in the ARRAY contains in turn
a specific number of elements of the same data type.
Example: Two-dimensional ARRAY
The following example shows a two-dimensional ARRAY.
Par4: ARRAY [0..5, 1..3] OF BOOL;
Variables of the Par4 data type contain 6 elements of the BOOL data type each with
3 sub-elements of the BOOL data type:
z Par4 [0,1] to Par4 [0,3]
z Par4 [1,1] to Par4 [1,3]
and so on up to
z Par4 [5,1] to Par4 [5,3]
33002204 12/2010
579
Derived data types
Example: Three-dimensional ARRAY
The following example shows a three-dimensional ARRAY.
Par5: ARRAY [0..5, 1..4, 11..14] OF REAL;
Variables of the Par5 data type contain 6 elements of the REAL data type each with
4 sub-elements of the REAL data type: Each sub-element contains 4 further subelements of the REAL data type:
z Par5 [0,1,11] to Par5 [0,1,14]
z Par5 [0,2,11] to Par5 [0,2,14]
and so on up to
z Par5 [0,4,11] to Par5 [0,4,14]
z Par5 [1,1,11] to Par5 [1,1,14]
and so on up to
z Par5 [5,4,11] to Par5 [5,4,14]
Example: A multi-dimensional ARRAY in a structured variable
As for one-dimensional ARRAYs, multi-dimensional ARRAYs can also be used as
elements in structured variables (definition with the key word STRUCT).
Par6: STRUCT
Name1: ARRAY [0..5, 1..3] OF INT;
Name2: BOOL;
Name3: REAL;
END_STRUCT;
Variables of the Par6 data type contain 3 elements:
z Name1 with 18 sub-elements:
z Par6.Name1[0,1]
to
z Par6.Name1[5,3] of the INT data type
z
z
Name2 with 1 element of the BOOL data type
Name3 with 1 element of the REAL data type
Example: Step by step definition of multi-dimensional ARRAYs
Multi-dimensional ARRAYs can also be defined step-by-step.
Par71: ARRAY [1..100] OF WORD;
Par72: ARRAY [1..3] OF Par71;
Par73: ARRAY [1..33] OF Par6;
580
33002204 12/2010
Derived data types
"Data types"
The names of the elementary data types and the names of already defined Derived
Data Types are recognized as a key word (in contrast with the names of elementary
data types, the names of derived data types are not displayed in color). Data types
must be closed with the separator ";".
If a different Derived Data Type is in use while defining a Derived Data Type, it must
be defined before it can be invoked.
33002204 12/2010
581
Derived data types
Names of the derived datatypes
Description
Names are given to the derived data types and the elements in the data type editor.
Names should not be longer than 24 characters and must be ended with the
separator ":"
Names are displayed in black
NOTE: Names should not begin with figures even if the option Options →
Preferences →IEC expansions... →Enable leading figures in identifiers is
activated.
NOTE: Within the data type editor it is possible to use special symbols (umlauts,
accents etc.). These symbols are also permitted in Concept EFBs created with
Concept-EFB can NOT be used however. The above is based on the internal
processes of Borland products. It is therefore strongly recommended that NO
special symbols are used in names.
582
33002204 12/2010
Derived data types
Separators
Introduction
The following separators can be used to define the derived data types:
z : (colon) (see page 583)
z ; (semi-colon) (see page 583)
z [ ] (square brackets) (see page 583)
z .. (full stops) (see page 584)
Separator ":" (colon)
Marks the end of a name (name of the derived data type, name of the element).
Example:
TYPE
Example1:
STRUCT
Name1: BOOL; (* Comment *)
Name2: INT; (* Comment *)
Name3: ARRAY [0..5] OF BOOL; (* Comment *)
END_STRUCT;
END_TYPE
Separator ";" (semi colon)
Indicates the end of an instruction.
Example:
TYPE
Example1:
STRUCT
Name1: BOOL; (* Comment *)
Name2: INT; (* Comment *)
Name3: ARRAY [0..5] OF BOOL; (* Comment *)
END_STRUCT;
END_TYPE
Separator "[ ]" (square brackets)
Encloses the range specification of the keyword ARRAY.
33002204 12/2010
583
Derived data types
Example:
TYPE
Example1:
STRUCT
Name1: BOOL; (* Comment *)
Name2: INT; (* Comment *)
Name3: ARRAY [0..5] OF BOOL; (* Comment *)
END_STRUCT;
END_TYPE
Separator ".." (full stops)
Separates the beginning and end of range for the keyword ARRAY.
Example:
TYPE
Example1:
STRUCT
Name1: BOOL; (* Comment *)
Name2: INT; (* Comment *)
Name3: ARRAY [0..5] OF BOOL; (*Comment *)
END_STRUCT;
END_TYPE
584
33002204 12/2010
Derived data types
Comments
Description
In the data type editor begin comments with the character sequence (* and end with
the character sequence *). Between these character sequences any comments can
be entered.
Comments can be entered at any position in the data type editor
Comments are displayed in color.
Using the menu command Options →Preferences →IEC Extensions →Nested
comments authorized you can enable nested comments to be authorized. There
are then no limits to the nesting depths.
Example: Comments
TYPE
Example1:
STRUCT
Name1: BOOL; (* Comment *)
Name2: INT; (* Comment *)
Name3: ARRAY [0..5] OF BOOL; (* Comment *)
END_STRUCT;
END_TYPE
33002204 12/2010
585
Derived data types
17.3
Derived data types using memory
Use of Memory by Derived Data Types
Boolean Elements
Boolean elements are conveyed as bytes, the bit information is in the first bit.
Storage of Boolean elements:
WORD Elements
There are no gaps when Derived Data Types are stored in memory.
Example of a Derived Data Type:
TYPE
SKOE:
STRUCT
PAR1: BOOL;
PAR2: WORD;
PAR3: BOOL;
PAR4: WORD;
END_STRUCT;
END_TYPE
586
33002204 12/2010
Derived data types
Storage of the Derived Data Type in memory:
It should be ensured that WORD elements begin with word addresses (a dummy bit
could be inserted).
NOTE: If the structured variable is associated with a direct address and is further
processed externally (e.g. is read by a visualisation system from the PLC), the
WORD elements (including ANY_NUM elements) absolutely must begin with a word
address.
Located Derived Data Types
If derived data types are passed to the hardware (located Derived Data Types) they
may only be stored in the 3x or 4x registers. Storage in the 0x or 1x registers is not
possible.
33002204 12/2010
587
Derived data types
17.4
Calling derived data types
Calling Derived Data Types
Introduction
When a derived data type is defined in the data type editor, the name of the derived
data type appears automatically in the variables editor (Column Data type). The
assignment of a variable to a derived data type occurs in the same way as for
elementary data types.
Multi-element variables can be called as a text input of the individual elements or
using a dialog box Lookup variables. In such a case, the corresponding elements
are chosen according to the selection of a multi-element variable in the Select
Component of Type dialog box.
Addressing a structure element
To address a structure element the variable names are first assigned and then
separated from the element name by a dot
(e.g.VARIABLE_NAME.ELEMENT_NAME). If this element also consists of a
Derived data type as well, it is again separated from the next element name by a full
stop (e.g. VARIABLE_NAME.ELEMENT_NAME.SUB_ELEMENT_NAME) etc.
Example: Addressing a structure element
Addressing a structure element:
Step
588
Action
1
Define a derived data type.
For example:
TYPE
Example1:
STRUCT
Par1: BOOL;
Par2: INT;
END_STRUCT;
END_TYPE
2
Declare a new variable in the variable editor (e.g. with the name TEST).
3
Assign these variables the data type of the derived data type created (e.g.
Example1).
33002204 12/2010
Derived data types
Step
Action
4
Close the variable editor with OK.
Reaction: A new multi-element variable called "TEST" of data type "Example1"
is now created.
5
To address this multi-element variable in its "entirety", simply enter the name of
the variable (TEST) into the program as usual.
To address only a single element of this multi-element variable (e.g. the element
"Par1"), enter the variable name and (separated by a dot) the name of the
element (e.g. TEST.Par1) into the program.
Addressing an ARRAY element
To address an ARRAY element the variable name comes first followed by the
element number in square brackets (e.g. VARIABLE_NAME[4]).
Example: Addressing an ARRAY element
Addressing an ARRAY element
Step
Action
1
Define a derived data type.
For example:
TYPE
Example2: ARRAY [0..5] OF BOOL;
END_TYPE
2
Declare a new variable in the variable editor (e.g. with the name MY_VAR).
3
Assign these variables the data type of the derived data type created (e.g.
Example2).
4
Close the variable editor with OK.
Reaction: A new multi-element variable called "MY_VAR" of data type
"Example2" was created.
5
To address this "entire" multi-element variable, simply enter the name of the
variable (MY_VAR) into the program as usual.
To address only a single element of this Multi-element variable (e.g. the 4th
element of the ARRAY), enter into the program the variable name and in square
brackets the number of the element (e.g. MY_VAR[4]).
Addressing an ARRAY element in a structure
To address an ARRAY element which is part of a structure the variable name is
entered first, followed by a dot and the element name, followed by the element
number in square brackets (e.g. VARIABLE_NAME.ELEMENT[4])
33002204 12/2010
589
Derived data types
Example: Addressing an ARRAY element in a structure
Addressing an ARRAY element in a structure:
Step
Action
1
Define two derived data types (in which the second derived data type uses the
first as an element).
For example:
TYPE
Example3:
STRUCT
Par1: BOOL;
Par2: ARRAY [0..5] OF BOOL;
Par3; BOOL;
END_STRUCT;
Example4:
STRUCT
Elem1: Example3:
Elem2: INT;
END_STRUCT;
END_TYPE
2
Declare a new variable in the variable editor (e.g. with the name
COMPLEX_VAR).
3
Assign these variables the data type of the derived data type created (e.g.
Example4).
4
Close the variable editor with OK.
Reaction: A new multi-element variable called "COMPLEX_VAR" of data type
"Example4" is now created.
5
To address this "entire" multi-element variable, simply enter the name of the
variable (COMPLEX_VAR) into the program as usual.
For example, if you only want to address one individual element of this multielement variable (e.g. you want to call the 5th element of the ARRAY from
element "Par2" (derived data type "Example3") as an element of "Elem1"), enter
the variable names in your program and the element name separated by a dot,
(in your "current" derived data type, here "Example4"), and the name of the
elements of the derived data type called by the "current" derived data type
separated by a dot (here "Example3") and followed by the element number in
square brackets (e.g. COMPLEX_VAR.Elem1.Par2[5]).
Range Monitoring for Indexed Access
Indexed access to Arrays in ST are monitored for over range violations. If the index
is a constant, monitoring is carried out on the compile level in the programming
device. If the index is a variable, monitoring is carried out during runtime in the PLC
during every cycle.
590
33002204 12/2010
Derived data types
In order to optimize program run time, the index for multi-dimensional arrays or
arrays that are embedded in structures are only checked for the starting and end
address of the memory area reserved for the variable. This means that an invalid
component is overwritten even though it is always located inside the structure. An
error message is only generated in the event display dialog box when the index for
the memory area allocated for this structure is exited: "ARRAY Index exceeds range
(..)". Data access is diverted to the memory starting address of the structure.
CAUTION
Data can be overwritten!
The index ARRAY does not serve as the range boundary, but always the entire
memory range allocated to the variable.
With multi-dimensional Arrays or Arrays within a structure, an error message is first
returned when the index is displayed on a memory address outside of the memory
area allocated for the entire array or entire structure.
Failure to follow these instructions can result in injury or equipment damage.
Example 1 one dimensional structure
Defining a derived data type in the data type editor:
Variable definition:
Sequence in text language:
If the Index (indx) is too large (>7) or too small (<4), and data access is made
outside the range(Otto), the first element is automatically accessed in the PLC
runtime system (Otto[4]) and an error message is generated.
33002204 12/2010
591
Derived data types
Example 2 Array embedded in a structure
Defining a derived data type in the data type editor:
Variable definition:
Sequence in text language:
In this case the range boundary is determined by the total amount of memory
occupied by the Otto variables. The range monitoring is first activated when indx <2
or indx >9 occurs. An over range then accesses the address Otto.F1!
Access with indx = 2-3 or indx = 8-9 is not recognized as faulty, but the elements
F1 (indx = 2-3)or F3 (indx = 8-9) are overwritten!
Example 3 multi-dimensional array
Defining a derived data type in the data type editor:
592
33002204 12/2010
Derived data types
Variable definition:
Sequence in text language:
In this case when the first index indx_x of the range boundary is exceeded it directly
results in a error message. For the second index indx_y, the range monitoring
becomes active when the address created from the two indexes are outside the
memory area for the entire array (4*4 words).
Examples:
for indx_x = 1, it can become indx_y = 16 before the range monitoring is put into
effect.
for indx_x = 4, range monitoring becomes active when indx_y = 5.
33002204 12/2010
593
Derived data types
594
33002204 12/2010
Reference data editor
33002204 12/2010
Reference data editor
18
Overview
This Chapter describes the reference data editor (RDE) and its use with activated
animation.
What's in this Chapter?
This chapter contains the following topics:
Topic
33002204 12/2010
Page
General Information about the Reference Data Editor
596
Converting RDE templates
598
Changing signal states of a Located variable
600
Cyclical Setting of Variables
602
Unconditional locking of a section
605
Animation
606
Replacing variable names
608
Load reference data
609
595
Reference data editor
General Information about the Reference Data Editor
At a Glance
Variables can be displayed in animation mode, 0x and 1x references can be blocked
(forced) and unlocated element variables or elements of structures can be set
cyclically using the Reference Data Editor (RDE). The behavior of the variables can
be followed and modified online through directly accessing the variables and direct
addresses used in the IEC program. Variable states are displayed in animation
mode with different colors (disabled, cyclically set).
Maximum 250 entries are possible in the Reference Data Editor. If this limit is
exceeded a warning message is generated when saving.
Creating RDE Templates
To create an RDE template, use the variables declared in the variable editor. There
are various possibilities here:
If ...
Then
You make a double click on the
corresponding numerical field in the first
column,
you open the dialog Lookup variables, for
selecting a declared variable or component of
a structure.
You enter the variable names of a declared
variable in the column Variable name,
the declared parameters are entered into the
RDE template.
You enter the direct address in the column
Address,
then the value, the format and in some cases
the defined name of the corresponding signal
are entered in the RDE template.
You use menu command Insert
Addresses... to insert entire reference
blocks into the column Address,
the values and the formats of the
corresponding signals are entered into the
RDE template.
Display Signal States
Stored signal states are always overwritten by the current values in the PLC with an
activated animation (Online →Animation) when opening an RDE template.
The signal states in the PLC can be displayed in online mode using menu instruction
Controller status... . When starting the PLC, you can view signal states
corresponding with the program progress in animation mode.
596
33002204 12/2010
Reference data editor
Printing RDE Templates
To print an open RDE template, click in the RDE main menu on the menu instruction
Print. An exact copy of the screen image of the RDE template will be created on
paper.
NOTE: We recommend that you modify the printer properties to landscape paper
format in the operating system (Windows). This will give you the complete image of
the RDE template on a single page.
Using RDE Templates
Using an RDE template in more than one project is not recommended. This can
cause doubled variable names to appear as well as variable names that did not exist
in the original RDE template. The variables in the RDE templates are always
displayed with the current reference addresses.
Converting RDE Templates
This procedure can be found in the description Converting RDE Templates
(see page 598).
33002204 12/2010
597
Reference data editor
Converting RDE templates
Introduction
RDE templates from an earlier version of Concept are automatically converted into
the template format of the new Concept version. To differentiate between the
converted RDE templates and the other RDE templates, they are saved with the file
extension *.RDF.
CAUTION
Incomplete RDE templates are created!
Before the conversion make sure that the variables in the RDE template are
declared in the opened project in the new version of Concept. New variables are
listed in an error message and cannot be displayed in the RDE template (*.RDF)
created from it.
Failure to follow these instructions can result in injury or equipment damage.
598
33002204 12/2010
Reference data editor
Automatic Conversion
Automatic Conversion is performed when the RDE template of a previous version of
Concept is opened:
Step
33002204 12/2010
Action
1
Start the new version of Concept and open the project.
2
In the Online main menu click on the Reference data editor menu command.
Result: The RDE main menu appears in the men bar.
3
In the Online main menu click on the Reference data editor menu command.
4
Select the directory, in which the RDE template (*.RDE) is saved (e.g.
D:\CONCEPT_OLD).
Result: All existing RDE templates (*.RDE or *.RDF) are displayed.
Note: The files with the *.RDF extension come from the conversion of generated
RDE templates (*.RDE).
5
Select the *RDE RDE template to be converted.
6
Click on the command button OK.
Result: The RDE AutoConvert message appears. This informs you that the
*RDE template was created in a previous version of Concept and is now being
saved in a new format, so that it can be used in this version of Concept. The
converted template is saved in a file with the *.RDF extension.
7
Click on the command button OK.
Result: The converted RDE template (*.RDF) is displayed.
Warning: All RDE template variables must be declared beforehand in the
project. For new variables, the RDE Template Errors error message appears
now, in which all faulty variables are listed. After closing the window, the
converted RDE template opens, but only containing the declared variables.
8
Using the Save reference data table under... menu command, it is possible to
save the converted RDE template in the directory in the new version of Concept
(C:\CONCEPT_NEW).
Result: The converted RDE template is stored in the Concept directory with the
*.RDF file extension.
599
Reference data editor
Changing signal states of a Located variable
Introduction
Located variables can be changed by checking the corresponding signal box in the
columnDisable and editing the value. Upon locking, the variable is separated from
the hardware and is only used in the logic again if the disablement is undone. In this
way, the changed signal states of all editors (FBD, SFC, LD, ST, LL984) are taken
into account.
Unintended setting of values
Confirm values that were entered in an RDE table with the Input key. However,
authorized values are also transferred if you switch to another input field using the
cursor key or the mouse or if you leave the RDE table.
You can cancel an entry using the ESC key.
WARNING
UNINTENDED SETTING OF VALUES
Do not leave the RDE table (for example by clicking on another window) if you have
already entered an authorized value in an input field, since otherwise the value will
be transferred and unintended setting of values can occur.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Forcing inputs and outputs
When inputs are forced, signal states are transferred until the value in the RDE table
is changed again. When outputs are forced, the new value appears at the beginning
of each program cycle. When a subsequent change is made using the program
logic, this value is not saved in the state RAM until the locking of the output has been
removed.
CAUTION
All changed signal states are loaded directly onto the PLC.
Though not in the case of forced located variables.
Failure to follow these instructions can result in injury or equipment damage.
600
33002204 12/2010
Reference data editor
Display of disabled variables
Variables that have been disabled by checking the check mark are shaded in color
in the editor display. By removing the check symbol, the colored background of the
corresponding variable is also no longer visible.
Loading reference data
Cyclically set values and disabled variables can be loaded onto the PLC using the
menu command Load reference data.
These settings then remain the same until the user makes a change in the RDE
Template, or the PLC loses the loaded data (e.g. by loading a different project).
NOTE: In an open RDE Template, the changed date is then automatically saved
using the menu command Load reference data. The menu command Save table
then no longer needs to be used.
33002204 12/2010
601
Reference data editor
Cyclical Setting of Variables
Introduction
Variables and structure elements can be changed by entering a set value
corresponding to the data type of the variable in theSet Value column. This value
will be written uniquely, if the corresponding signal's box in the Cyclic Set column
is subsequently checked. The new signal state is loaded directly onto the PLC and
is transferred to the cyclically set variables administrator. The signal state of the
variable, attained after logic editing at the end of the cycle, is specified in the Value
column. In animation mode, the cyclical setting of variables in IEC sections is
displayed.
Unintended setting of values
Confirm values that were entered in an RDE table with the Input key. However,
authorized values are also transferred if you switch to another input field using the
cursor key or the mouse or if you leave the RDE table.
You can cancel an entry using the ESC key.
WARNING
UNINTENDED SETTING OF VALUES
Do not leave the RDE table (for example by clicking on another window) if you have
already entered an authorized value in an input field, since otherwise the value will
be transferred and unintended setting of values can occur.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
602
33002204 12/2010
Reference data editor
Cyclic Set
NOTE: Cyclical setting of variables can only be performed ONLINE and in EQUAL
mode, not in animation mode. Depending on logic, the displayed value may deviate
from the cyclically set value.
When the cyclical setting check box is checked, the set value in the Set Value
column can still be changed.
If the box in the column Cyclic Set is unchecked, the signal state in the column
Value is loaded onto the PLC and is used in the logic.
A maximum of 300 variables can be cyclically set. For cyclical setting, the length of
the entry is limited to 150 characters in the column Variable Name, because this
name is sent to control. If a variable is used several times in the reference data
editor, the most recently entered value will always be the one taken into account for
cyclical setting.
NOTE: All changed signal states are loaded directly onto the PLC.
CAUTION
Modified variable names are not recognized by replacements.
When a variable is cyclically set, the spelling of the variable name should not be
changed in the variables editor.
Failure to follow these instructions can result in injury or equipment damage.
Cyclical setting and locking of signal states in the operating modes:
33002204 12/2010
Mode
Option
Meaning
LOCAL
Disable
The variables declared in the Variable Editor can be
written in the RDE Template in local mode. The signal
states specified in online mode are displayed in local
mode but cannot be changed and have no effect.
ONLINE
Disable
The changed signal states of located variables are
transferred directly from the program logic.
LOCAL
Cyclic Set
Cyclical setting of variables cannot be executed in local
mode.
ONLINE
Cyclic Set
The signal state in the column Set Value is used in logic
editing by checking the box (check mark visible), and
supplies a value at the end of the cycle, which is
displayed in the column Value.
603
Reference data editor
Getting/deleting cyclical set list
The cyclical values set in animation mode can be inserted into the RDE Template in
disabled animation using the menu command Get CSL.
Cyclically set values are recognized in the RDE Template by the check mark in the
column Cyclic Set, and are automatically recognized row by row. It is therefore
referred to as a cyclical set list. Using the menu command Online →Get CSL this
recognized list will be inserted dependently from the selected row in the RDE table.
Getting and inserting the cyclical set list can be done as often as required. The most
recent cyclical set list is always located on the clipboard and can only be deleted
using the menu command Delete CSL. Thereafter, getting and inserting is no longer
possible until values are cyclically set at the next animation.
NOTE: Each time, the system getsall cyclically set values .
Loading reference data
Cyclically set values and disabled variables can be loaded onto the PLC using the
menu command Load reference data.
These settings then remain the same until the user makes a change in the RDE
Template, or the PLC loses the loaded data (e.g. by loading a different project).
NOTE: In an open RDE Template, the changed date is then automatically saved
using the menu command Load reference data. The menu command Save table
then no longer needs to be used.
604
33002204 12/2010
Reference data editor
Unconditional locking of a section
At a Glance
At the section to be inhibited, the logic must carry a BOOL data type "output" and it
should be noted that the section is disabled at configured "1".
CAUTION
Risk of unwanted process states.
Locking a section does not mean that programmed outputs within the section are
deactivated. If an output was already set during a previous cycle, this state also
remains after the section has been inhibited. It only ceases to be possible to
change the state of these outputs once the section has been inhibited.
Failure to follow these instructions can result in injury or equipment damage.
NOTE: A section that contains a logic to lock/release other sections should not be
disabled, if possible. Output state disabled sections cannot be changed.
Procedure for unconditional locking of a section.
The following procedure is performed to disable a section unconditionally in the RDE
table:
Step
33002204 12/2010
Action
1
By double-clicking in a text box in the first column in the table (1 … 100) open
the dialog box Look up variables.
2
In the zone Data type select the option button Structured and from the list select
SECT_CTRL.
Reaction: The names of all sections are displayed.
3
Select the name of the file to be disabled and using the command button
Elements... open the dialog box Select elements by type.
4
Select the line disable : BOOL and confirm with OK.
Reaction:The structured variable (Sectionname.disable) to which the section to
be disabled is assigned, is entered in the RDE table.
5
Link the PLC and the programming device (Online →Link...), and load the user
program onto the PLC (Online →Load...).
Reaction: The PLC is in ONLINE and ANIMATIONS mode.
6
In the column Value enter a configured "1".
Reaction: The section is disabled and will not be processed.
605
Reference data editor
Animation
At a Glance
Animation can only take place in ONLINE mode. By activating Animation in the
Reference data editor it is possible to display the signal states of the variables, and
to observe the behavior of the output signals while the program is running.
During animation, signal states can be changed online also. The new values are
automatically loaded onto the PLC and are taken into account during the next cycle.
NOTE: When changing a value it should be ensured that the locking of the variable
is subsequently removed. It is impossible to animate disabled variables correctly.
Animation status
The column Animation status specifies the status of entered unlocated Variables
during animation.
This table provides an overview of the animation status possibilities:
606
Display
Mode
Cause
Not used
Note: In LOCAL
mode, this display
changes to "Unequal
program"
ONLINE,
ANIMATED
A variable not used in the user program, which is
declared in the Variable Editor, was entered in the
RDE table.
Inhibited I/O flag bits
ONLINE
An unlocated variable was cyclically set during the
ANIMATIONS mode.
Unequal program
ONLINE
A variable that is used in the user program, which is
declared in the Variable Editor, was entered in the
RDE table. The program is in MODIFIED mode.
Unequal program
Note: In ONLINE
mode, this display
changes to "Not
used".
LOCAL
A variable not used in the user program, which is
declared in the Variable Editor, was entered in the
RDE table.
33002204 12/2010
Reference data editor
Display of forced and cyclically set signals in ANIMATIONS mode
The variables that are forced or cyclically set in the reference editor are labelled with
a colored background in the individual editors.
Forced variables are displayed in the following way:
Editor
Display
IEC editors (FBD, LD, SFC, IL, ST)
When forcing occurs, variable names are shaded in
ochre (brown-yellow).
LL984 editor
When forcing contacts, variable names are
underlined.
When forcing spools, an opened contact ("inhibited")
is displayed before the spool.
Monitoring fields and Display dialog
When forcing occurs, variable names are shaded in
ochre (brown-yellow).
Cyclically set variables are displayed in the following way:
Editor
Display
IEC editors (FBD, LD, SFC, IL, ST)
When cyclical setting occurs, the variable name is
shaded in violet.
Monitoring fields and Display dialog
When cyclical setting occurs, the variable name is
shaded in magenta.
NOTE: In LD (Ladder Diagram) spools and contacts are displayed in color.
However, due to forcing and cyclical setting, it is possible that the colors of the
variable names will be different from the color display of spools and contacts.
Display of forced and cyclically set element structured variables in ANIMATIONS mode
If a structured variable element is forced or cyclically set, there are different display
possibilities.
33002204 12/2010
Display
Cause
The name of the structured variable
(e.g. motor) is shaded in color.
In the editor, a multi-element variable (e.g. motor) is
displayed, in which one or more elements is forced
or cyclically set.
The name of the structured variable
element (e.g. right motor on) is
shaded in color.
In the editor, a forced or cyclically set element of a
multi-element variable (e.g. right motor on) is
displayed.
The name of the structured variable
element (e.g. right motor on) is
shaded in color, but the name of the
element is not.
In the editor, an element of a multi-element variable
that is not forced or cyclically set is displayed, but a
different element of this multi-element variable is
cyclically set or forced.
607
Reference data editor
Replacing variable names
At a Glance
When using an open RDE table it is possible to simultaneously edit the Variable
Editor. If variable names are changed in the Variable Editor using the Find/replace
function, these changes are automatically adopted in the open RDE table. In this
case the RDE animation is initially terminated and the RDE table must be reloaded.
Procedure and reaction
For the automatic adoption of replaced variable names in the simultaneously open
RDE table, the following steps are to be performed:
Step
608
Action
1
Open a section and create an online link.
Note: The state between PLC and programming device must be EQUAL. If not,
load the program into the PLC.
2
Start the animation (Online →Animate binary values).
Reaction: The signal states of the section are displayed in color.
3
Open an existing RDE table (RDE →Open table...).
Reaction: The RDE animation is started.
4
Open the Variable Editor (Project →Variable declaration...).
5
Using the command button Find/replace open the dialog Find/replace.
6
Replace an existing variable name with a new name (Command button
Replace).
Reaction: The variable name was changed in the Variable Editor.
7
Exit the Variable Editor using OK.
Reaction: The section is automatically updated, and the RDE animation is
terminated.
8
Close the RDE table and save the changes (Command button Yes).
9
Reopen the saved RDE table (RDE →Open table...).
Reaction: The RDE animation with the changed variable name is recovered.
33002204 12/2010
Reference data editor
Load reference data
At a Glance
In the same cycle, the variables changed in the reference data editor are sent to the
PLC, using the menu command Online →Load reference data.
NOTE: To perform the loading, the animation must be disabled.
33002204 12/2010
609
Reference data editor
610
33002204 12/2010
ASCII Message Editor
33002204 12/2010
ASCII Message Editor
19
Introduction
This chapter describes the ASCII message editor.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
19.1
ASCII Editor Dialog
612
19.2
User Interface of ASCII Message Editor
621
19.3
How to Continue after Getting a Warning
628
19.4
ASCII Editor in Offline/Combination/Direct Modes
629
611
ASCII Message Editor
19.1
ASCII Editor Dialog
Introduction
This section describes the ASCII editor dialog.
What's in this Section?
This section contains the following topics:
Topic
612
Page
Generals to ASCII editor dialog
613
Text
614
Variables
615
Control code
616
Spaces
617
Carriage Return
618
Flush (buffer)
619
Repeat
620
33002204 12/2010
ASCII Message Editor
Generals to ASCII editor dialog
Introduction
Use the ASCII message editor to create, edit, and simulate ASCII messages. The
ASCII message text/control that is created in the editor can be transferred to the
selected PLC. Conversely, the ASCII messages internal to the controller can be
uploaded to the editor.
An ASCII message set consists only of a list of messages that satisfy certain rules.
The number of messages allowed and the maximum length of the ASCII message
set is defined as part of the PLC configuration. Each message consists of a list of
ASCII message fields separated by commas.
The following fields are currently supported:
z Text, page 614
z Variables, page 615
z Control code, page 616
z Spaces, page 617
z Carriage Return, page 618
z Flush (buffer), page 619
z Repeat, page 620
Preconditions
This function is only available when using:
Concept for Quantum
z The modules J892 or P892
z Programming language LL984
z
33002204 12/2010
613
ASCII Message Editor
Text
Introduction
The text messages defined by text fields take the format ’Hello World’ whereby
Hello World becomes the text to be forwarded. The single quotation marks are
the delimiters. The ASCII message editor development dialog provides a
development area and a simulator area where the composed message is interpreted
and displayed for you to make any necessary edits before leaving the editor dialog.
Message Length
An ASCII message can be as long as 134 words. Three words are for overhead plus
the actual message maximum of 131 words (2 characters per word).
Message words are used up as follows:
614
Field type
Field length (in words)
ASCII text
1 + length of text / 2 rounded up
Return
1
Flush 0, 1
1
Flush 2, 3
2
Control
1
Variable
1
Repeat
2
Space
1
33002204 12/2010
ASCII Message Editor
Variables
Introduction
A variable will be given the format NTF.
The meaning of this is:
z N representing the decimal number (1...99) of the data fields of the data type
defined by T.
z T is the data type of the variable.
z F the decimal field width for the variable.
Data Types
The data types supported are:
Type
Repetition factor
A = ASCII character
1
B = binary number
1 to 16
H = hexadecimal
1 to 4
I = integer
1 to 8
L = integer with leading 0s
1 to 8
O = octal
1 to 6
Example
For example: 2H2 means:
2 registers (N)
z in hexadecimal (T)
z containing 2 hexadecimal numbers (F)
z
N can fit into the number of data registers needed, but it is not an absolute
requirement.
The relationship is:
33002204 12/2010
Type
Relationship
A
Number of registers = N/2 (next upper integer value)
B
Number of registers = N
H
for 1 ≤F ≤4... Number of registers = N
for 5 ≤F ≤8... Number of registers = 2 x N
I and L
The same as H
O
Number of registers = N
615
ASCII Message Editor
Control code
Meaning of Control Code
A control code is given the format "Null", with Null being a three characters OOO,
and the double quotation marks are delimiters.
For example: "017"
616
33002204 12/2010
ASCII Message Editor
Spaces
Meaning of Spaces
A space field is given the format ddx, with dd being a decimal number (1..99) used
to determine how many spaces are to be added to the message.
Representation of Dialog
Many spaces between text:
33002204 12/2010
617
ASCII Message Editor
Carriage Return
Meaning of Carriage Return
A carriage return field will add a carriage return to the output information, and it has
the format, /.
Representation of Dialog
Carriage return:
618
33002204 12/2010
ASCII Message Editor
Flush (buffer)
Meaning of Flush
This will expressly specify for the P892 only how the input message buffer is to be
cleared. This field has the format <*>/.
The * can be any of the following:
33002204 12/2010
*
Meaning
0
Remove all characters in the buffer. An example is: <0> clears all.
1;bbb
Removing the number of characters specified by bbb, whereby bbb is a number
(1...255). For example, <1;100> flushes the first 100 characters in a buffer.
2;hhhh
Scanning the message for the 2 characters that are specified by the
hexadecimal numbers hhhh. If a match is found, delete all characters up to but
not including the match.
An example is: <2;5445> causes the buffer ‘12TEST’ to become "TEST".
3;rrr;hhhh
Scanning the message for the 2 characters that are specified by the
hexadecimal numbers hhhh. If a match is found, delete all characters up to and
including the match. The search is to be performed as often as specified by rrr,
whereby rrr is representing a decimal number 1...255.
Example: <3;2;5445> causes the buffer ‘12TEST3456TEST789TEST’ to
become ST789TEST.
619
ASCII Message Editor
Repeat
Meaning of Repeat
Use this message field to specify that a number of message fields will be repeated
several times. This field has the format dd(*), with dd being a decimal repetition
factor (1....99), ( ) are delimiters, and * is a series of message fields.
Representation of Dialog
Repeated text:
620
33002204 12/2010
ASCII Message Editor
19.2
User Interface of ASCII Message Editor
Introduction
This section describes the user interface of the ASCII message editor.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
How to Use the ASCII Message Editor
622
Message Number
624
Message Text
626
Simulation Text
627
621
ASCII Message Editor
How to Use the ASCII Message Editor
Invocation of ASCII Message Editor
The ASCII message editor is invoked from the ASCII messages... menu item in the
Project menu. This editor allows you to add/modify/delete messages in a temporary
work space, then save or cancel the changes.
Add New Messages
To add a new message, type the new message number into the Message text box
and type a syntactically correct message into the message text box. As you enter a
message into the message text box, its corresponding simulation is displayed in the
Simulation text box. When the message is syntactically incorrect, it is displayed in
red.
Modify Existing Messages
To modify an existing message, select a message from the Message number list
and change the text.
Delete Messages
To delete a message, select a message from the Message number list and click on
Delete.
Clicking on the button Delete All will remove all messages in the temporary
workspace. The button is active if there is at least one ASCII message in the
message set. Selecting this option results in the display of a confirmation dialog.
View
Clicking at the button View will produce a view of the displayed ASCII message
dialog. The view message format is message number followed by message text.
You can select from the choices available. To download the editor from the view list,
click on the message and on OK.
Save Changes
Use the button OK to save processes performed while working with the ASCII editor
and to close the dialog. Each message that has been created or changed is checked
for syntactic correctness at this point. The checking begins at the current message
and wraps around until all messages are checked. If a syntax error is detected, a
definition of the error is displayed first, and as soon as the error dialog is cleared, the
message itself appears with the cursor on the faulty character. Every attempt to add
ASCII characters which will cause the size of the entire message area set in the
configuration to be exceeded will generate an error.
622
33002204 12/2010
ASCII Message Editor
Length, Used and Free
These fields display the length of the current message (in words), the number of
words used and the number of words remaining.
33002204 12/2010
623
ASCII Message Editor
Message Number
Introduction
The combo box Message number is a dialog that contains a message selection list
with a check mark next to the currently selected message.
Use this dialog to select existing message numbers and/or to add new message
numbers. As long as there are no messages, text box and list are empty. If there are
messages, the editor is initially displayed with the text box containing the first
message number and a list of message numbers for existing messages. The
message number that relates to the currently displayed message is posted above
the list box.
Action
For the selection of an existing message, click at the list button and mark a number
in the list or type the number into the text field. A new message number can be
inserted by typing the number into the text field.
Effects
If the message number assigned to an existing message is changed (either text or
list entry), the text box Message will display the message text for the message
number and the box Simulation shows the simulation of the message. If a new
message number has been entered, the text boxes Message and Simulation will
be cleared.
624
33002204 12/2010
ASCII Message Editor
Error handling
The following errors can be appearing:
If...
Then ...
an unauthoried character is entered a message field dialog will show: "Message number
in the number field of the message. contains illegal characters".
After acknowledging the error, the message number is
reset and the process will continue in the text box
Message.
the text box Message is not filled
out.
a message field dialog will show: "There must be a
message number before text can be
entered".
After acknowledging the error, the message number is
reset and the process will continue in the text box
Message.
a message field dialog will show: " Message number
the number is greater than the
maximum number set in Configure exceeds maximum set in configuration".
After acknowledging the error, the message number is
→ASCII Setup....
reset and the process will continue in the text box
Message.
33002204 12/2010
625
ASCII Message Editor
Message Text
Introduction
The text box Message is a text editor with free format for the entry of ASCII
messages. This editor allows one arbitrarily long line of free-format text. Although
the text should follow the ASCII message syntax, it does not necessarily have to be
syntactically correct prior to activating the OK button, even though a view note
regarding validity will appear already during entry of the messages.
Actions
A currently selected message is made available for editing, otherwise a new
message can be entered. The standard Windows edit operations (Cut, Paste,
Copy, ...) are allowed.
Effects
If the message is syntactically correct, its text will be displayed in normal textual
color, if not, the display will be in red. Text wraps so there is never a case where
horizontal scrolling is required.
626
33002204 12/2010
ASCII Message Editor
Simulation Text
Introduction
The text box Simulation is a read-only multi-line field. The simulated output of the
current message is displayed in this window. As messages are added or changed,
the simulated output is displayed in the simulation window.
Special Considerations
The simulation of control codes is shown as the ASCII character that corresponds
to the controller, except those control codes that are not authorized in Windows text
control and are written as an ’l’.
NOTE: Any simulation greater than 32 k characters is truncated to this maximum.
33002204 12/2010
627
ASCII Message Editor
19.3
How to Continue after Getting a Warning
How to Continue after Getting a Warning
Introduction
A few conditions will allow continuing work with the ASCII editor although with
possibly restricted functionality.
NOTE: To match a configuration, messages may be deleted.
Exceeding the Total Messages
Message numbers that are above the maximum limit set in Configure →ASCII
Setup... will only be available for display or delete. These messages appear grayed
out.
The accompanying warning reads: "Warning: Some message numbers
exceed the highest message number xx, defined in Configure.
All messages beyond xx can only be displayed or deleted."
Exceeding the Message Area Size
If the size of the message in the data base is greater than the size defined in
Configure →ASCII Setup..., a warning will appear. You can continue to view,
change, or delete but changes cannot be saved unless the size falls below the
configuration setting.
This warning reads: "Warning: The size of the ASCII message area,
xx, exceeds the maximum size, xx, defined in Configure."
Tips
NOTE: To match a configuration, messages may be deleted.
NOTE: Information about the ASCII character set can be found in the PLC User’s
Guide.
628
33002204 12/2010
ASCII Message Editor
19.4
ASCII Editor in Offline/Combination/Direct Modes
ASCII Message Editor in Offline/Combination/Direct Modes
Offline
When using Concept to program in offline mode, the ASCII message editor is
displayed with the set of messages saved in the data base. By activating the OK
button, these messages will be saved in the database.
Direct
When using Concept to program in direct mode, the ASCII message editor will be
displayed with the set of messages saved in the controller. By clicking on the OK
button, the changes made to the ASCII messages will be downloaded to the
controller.
Combination Mode
When entering the Combination mode, Concept checks whether the information in
the controller matches the information in the data base. If a match is found, the
controller is considered EQUAL to the database. A mismatch is marked as NOT
EQUAL. If the status is EQUAL, the ASCII message editor will be displayed with the
ASCII message set taken from the data base. If a displayed editor message is
changed, these changes will be saved to the database and the controller after
clicking the OK button.
33002204 12/2010
629
ASCII Message Editor
630
33002204 12/2010
Online functions
33002204 12/2010
Online functions
20
Overview
This chapter describes the various online functions.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
20.1
General information about online functions
632
20.2
Connect to PLC
633
20.3
Setting up and controlling the PLC
649
20.4
Selecting Process information (status and memory)
663
20.5
Loading a project
670
20.6
Section animation
681
20.7
Online Diagnosis
685
20.8
Logging Write Access to the PLC
687
631
Online functions
20.1
General information about online functions
General information
At a Glance
After setting up a link via Modbus, Modbus Plus or TCP/IP between the
programming device and the PLC the project can be loaded onto the PLC. Now
special online functions for displaying and changing the current value in the PLC
state RAM are available in the separate editors. The PLC can be controlled.
CAUTION
A communication timeout or a general memory protection failure could occur if the system clock of the programming device is changed while it is online.
If the running program cannot be terminated, all animated program sections should
be closed , or the animation should be turned off in order to reduce the possibility
of getting into a time critical operation.
Failure to follow these instructions can result in injury or equipment damage.
632
33002204 12/2010
Online functions
20.2
Connect to PLC
Overview
This section contains information about connecting the PLC.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
General
634
Presettings for ONLINE operation
637
Modbus Network Link
638
Modbus Plus Network
639
Modbus Plus Bridge
644
TCP/IP-Network Link
646
Connecting IEC Simulator (32 bit)
647
State of the PLC
648
633
Online functions
General
Introduction
A connection can be created between a programming device and the PLC.
In monitor operation (it is not supported by M1E PLCs), it is possible to make
alterations to the IEC sections, but these cannot be downloaded to the PLC. When
exiting Concept a warning will be displayed.
NOTE: Only one programming device may be connected to the PLC.
Limited PLC Login
When logging into the PLC, the following restrictions are imposed for Quantum
CPUs 140 434 12 A and 534 14 A/B:
z If a programming device is already connected with the PLC in programming
mode, then no other programming devices can be connected with the PLC.
z If a programming device is already connected with the PLC in Monitor mode then
other programming devices can be only connected with the PLC in Monitor mode.
An attempt to connect with the PLC in another operating mode is not possible for
the other programming devices.
Consistency check
If a project is open and a connection between the programming device and the PLC
is to be created, a consistency check is automatically carried out between the
program, EFBs and DFBs on the programming device, and the PLC. The result of
this check (EQUAL, MODIFIED or NOT EQUAL) is displayed in the status bar and
written in a file. This file is located in the project directory of Concept and has the
name PROJEKTNAME.RMK. It functions for internal usage and automatically
changes its contents. The meaning of the individual entries can be found in the
following diagram.
634
33002204 12/2010
Online functions
Status descriptions
Status descriptions:
z EQUAL
The program on the programming device and the PLC is consistent.
z NOT EQUAL
The program on the programming device and the PLC is not consistent. To
establish consistency use the menu command Online →Download... .
z MODIFIED
The program on the programming device was modified. The modifications can be
made online in the PLC with the menu command Online →Download changes.
Note: Even when changes that are not relevant to the code (e.g.
creating/changing comments in IL/ST, moving objects (without affecting logic)
exist in FDB/LD/SFC), the MODIFIED status is displayed temporarily. When the
section is next analyzed (Project →Analyze project, Project →Analyze section
or Online →Download changes), the program automatically reverts to the
EQUAL status (if no changes have been carried out that are relevant to the code).
Even if changes that are relevant to the code have been carried out, only these
sections appear in the Download changes dialog box.
33002204 12/2010
635
Online functions
Relationships between states
The diagram shows the relationships between the different program states:
Unk UNKNOWN
Dis DISCONNECTED
!Eq NOT EQUAL
Mod MODIFIED
E!S EQUAL but not saved
EqS EQUAL and saved
636
33002204 12/2010
Online functions
Presettings for ONLINE operation
At a Glance
The dialog box Link PLC to can be used to specify settings for both the PLC link
and ONLINE mode resulting from it.
Access
It is possible to specify which functions will be executed in the ONLINE operation,
i.e. which menu commands are available in the Online main menu.
Protocol types
To link the programming device and PLC, it is important to know which network the
communicating nodes are in so that the correct protocol type is selected.
Use the table to decide which protocol type fits the network link used:
Linking the network nodes
Protocol type
Serial Interface
Modbus
SA85-/PCI85-Adapter
Modbus Plus
NOE-module (on Ethernet-Bus SINEC H1)
TCP/IP
TCP/IP Interface map (32-Bit Simulation)
IEC Simulator (32-Bit)
NOTE: The programming device can always only be linked to one PLC. This means
that before a link is made to another PLC, any existing link must be terminated with
the Terminate Link menu command.
33002204 12/2010
637
Online functions
Modbus Network Link
Introduction
For a Modbus network link, the settings of the modbus interface must correspond
with the settings on the PLC.
The interface is edited in the Modbus Port Settings dialog (PLC Configuration →
Modbus Port Settings...).
Protocol Settings for Modbus
When the Modbus protocol type is selected, specify further data in the Protocol
Settings: Modbus range. Specify the Node Address (Node No.) on the PLC and
enter this in the corresponding text box. You can determine the transfer mode for
communication between the PLC and the host computer.
The following modes are available according to the application:
Application
Mode
Communication with various host devices. The ASCII mode
works with 7 data bits.
ASCII
Communication with an IBM compatible personal computer. The
RTU mode works with 8 data bits.
RTU
After the serial interface for the Modbus network link has been specified, using the
Settings... command button, open the Settings for COMx dialog. Enter the settings
for the interface here, as in the Modbus port settings dialog.
Use the OK command button to create the ONLINE link.
638
33002204 12/2010
Online functions
Modbus Plus Network
Introduction
For a Modbus Plus network connection, enter in the Protocol settings: Modbus
Plus range whether the 16-Bit IEC-Simulator (Port 0) or the Modbus Plus interface
(Port 1) is being used.
All nodes on the local network are displayed in the list. Additionally, the routing path
of the token rotation sequence in the network, which can contain up to 5 Node
addresses is displayed. Up to 64 nodes can be addressed on one network, i.e. a
routing path address can be between 1 and 64. Several networks can be linked via
a bridge.
NOTE: The node list of a different network can be displayed by double-clicking on a
listed bridge.
To pass the program execution to the Modbus Plus device driver, Concept triggers
a MS DOS Software Interrupt. The preset Interrupt number for this is 5C (hex).
NOTE: If no virtual Modbus Plus driver is installed, the virtual MS DOS environment
in Windows NT has problems when reacting to the software interrupt. If a share
violation (Exception) occurs under certain conditions, change the Interrupt number
to 5D (hex) in the MODICON.INI file:
[PORTS]
mbp0=5d
If the Interrupt 5D from the NTVDM.EXE is activated the share violation should no
longer occur.
IEC Simulator (16 Bit)
The simulator simulates a coupled PLC via Modbus Plus. The address of the
programming device is displayed in the list in the routing path.
The simulator is active if in the Protocol settings: Modbus Plus: area, the option
Port 0 is selected.
NOTE: When the simulator is active, no further nodes can be displayed.
The simulator is only available for the IEC languages (FBD, SFC, LD, IL and ST).
PLC as Modbus Plus Node
When the PLC is a Modbus Plus node, the address which the PLC has in the routing
path is displayed in the list. This address corresponds to the node address which is
set with a rotary switch on the back of the CPU.
33002204 12/2010
639
Online functions
SA85/PCI85 as Modbus Plus Node
The SA85 module is a Modbus Plus adapter for an IBM-AT or compatible computer.
The port address is displayed in the list. The address shows in which network the
SA85/PCI85 is installed.
Displaying a routing path with SA85/PCI85:
Bridge Plus as Modbus Plus Node
A Bridge Plus (BP85) links nodes within two Modbus Plus networks. The Bridge is
displayed in the list box, and the next Modbus Plus network can be accessed by
double-clicking on the Bridge.
640
33002204 12/2010
Online functions
Displaying a routing path with a Bridge Plus BP85:
Example:
The example shows a routing path across 3 Modbus Plus networks. The task is to
send a message from node 5 in network A to node 12 in network C.
The routing path here is 22.20.12.00.00 and it is made up as follows:
33002204 12/2010
Path
Meaning
22
The first address contains the network A Bridge Plus address from Network A
from output node 5. This means the message is sent from output node 5 across
this Bridge to the next network, B.
20
The second address contains the Bridge Plus address of the next network, B.
Here, the message is sent from network B to the third network, C.
12
The third address contains the address of node 12, the destination segment.
00.00
Addresses four and five are set to 0 because there are no further forwarding
addresses.
641
Online functions
Bridge as Modbus Plus Node
A link between the Ethernet and the Modbus Plus network or between two Modbus
Plus networks is created via the Modbus Plus Bridge.
The Modbus Plus Bridge should be regarded as a host computer and must be
configured in the Protocol settings: TCP/IP area. Enter the IP address or the host
name of the Bridge, and finally in the text box Protocol type: change to Modbus
Plus network setting.
The Modbus Plus Bridge is only listed in the list of nodes in the Modbus Plus network
as a host name which was previously entered in the Protocol Settings: TCP/IP
area. A double-click on the corresponding host name opens the Modbus Plus
Bridge dialog box for 5 byte routing path configuration.
Further action in the dialog box can be found in the chapter"Modbus Plus Bridge,
page 644".
Example:
In the dialog box Modbus Plus Bridge, create the routing path 25.8.17.33.0, which
defines the following link (from A to D):
A
642
The message sent from the host computer contains the 5 byte Modbus Plus Routing Path.
The first byte with the node address of the host computer refers to the Modbus Plus Bridge
linked to it. The Modbus Plus Bridge 1 receives the message on internal path 8, as
specified in byte 2.
33002204 12/2010
Online functions
B
C
D
The TCP Index No. 17 (byte 3) administered in the Modbus Plus Bridge passes the
message on to the configured node with the IP address 205.167.8.10. In this case the node
with this IP address is another Modbus Plus Bridge.
Modbus Plus Bridge 2 receives the message. The MBP Index No. 3 given in 4 byte and
administered by the bridge passes the message on to the configured Modbus Plus node.
In this case the node 12.0.0.0.0.
The message has reached its destination, Modbus Plus node 12.
Bridge Multiplexer as Modbus Plus Node
The BM85 Bridge Multiplexer links up to four Modbus devices or Modbus networks
to a Modbus Plus network.
See also "User’s Guide BM85 Modbus Plus Bridge/Multiplexer."
Displaying a routing path with a Bridge Multiplexer BM85:
33002204 12/2010
643
Online functions
Modbus Plus Bridge
At a Glance
Enter the 5 byte routing path which defines the link from the host computer to the
Ethernet node in this dialog box.
Making settings
The following table describes how to define the routing path:
644
Setting zone
Routing path byte
Meaning
Bridge Path
2. Byte
A maximum of 8 links can go out from the
Bridge to the other network, and one of these
should be selected.
IP routing byte
3. Byte
Enter an index no. which is assigned to an IP
address. This IP address should correspond to
an Ethernet node address where the message
is then sent. If this IP address is being sent to
another Modbus Plus Bridge in the
Ethernet,another node address (MB+ routing
byte) must be given for it to be transferred
further into the Modbus Plus network.
MB+ routing byte
4. Byte
If a link is displayed between two Modbus Plus
networks via two Modbus Plus bridges, the
index no. of the Modbus Plus node must be
entered here. This index no. is also assigned to
a node address. If there is no link across a
different bridge, the value "0" is entered.
Complete address
5. Byte
The whole 5 byte routing path is displayed
according to the setting. The first byte is then
automatically adjusted to the node address of
the host computer.
33002204 12/2010
Online functions
Modbus Plus index no.
The assignments of the Modbus Plus index no. are pre-set and can be selected
between 0 and 255. Note that index no. 255 is reserved for specific operations.
When this index no. is selected, data selection or loading is permitted between a
TCP/IP node and the Modbus Plus Bridge via an internal command. Index nos. 250
– 253 are reserved and cannot be used.
The index in the Modbus Plus routing path is shown in the following table:
Index
Modbus Plus routing path
1 ... 64
1.0.0.0.0 ... 64.0.0.0.0
65 ... 128
2.1.0.0.0 ... 2.64.0.0.0
129 ... 192
3.1.0.0.0 ... 3.64.0.0.0
193 ... 249
3.2.1.0.0 ... 3.2.57.0.0
TCP/IP Index No.
The assignments of the TCP index no. follow automatically after the IP address of
the Modbus Plus Bridge has been specified in the Link →Protocol Settings:
TCP/IP dialog box. Each index is assigned to an IP address where the first 3 bytes
are assigned to the first 3 bytes of the Modbus Plus Bridge IP address. The 4th byte
is counted upwards from 1 to 255 at the most.
Example:
For a Modbus Plus Bridge IP address of 205.167.4.65, the TCP/IP addresses are
automatically pre-set, as in the following table:
Index
IP address
1
205.167.4.1
2
205.167.4.2
...
...
255
205.167.4.255
NOTE: Refer to the "174 CEV 200 30 TSX Momentum Modbus Plus to Ethernet
Bridge User Guide" for a detailed description of the Ethernet Bridge.
33002204 12/2010
645
Online functions
TCP/IP-Network Link
Introduction
For an Ethernet link, select the protocol type TCP/IP in the Connect to PLC dialog
box.
Protocol Settings for TCP/IP
To connect to other Ethernet nodes, specify the IP address or the host name of the
Ethernet node in the Protocol Settings: TCP/IP range.
To connect to the Ethernet via Modbus Plus node, specify the IP address or the host
name of the Modbus Plus Bridge in the Protocol Settings: TCP/IP range (see also
"Bridge as Modbus Plus Node (see page 642)").
Connecting Quantum to the Ethernet
You can connect the Quantum to the Ethernet Bus by configuring the NOE module.
By doing this, it is possible to communicate with other automation components in the
Ethernet Bus system via the host computer.
646
33002204 12/2010
Online functions
Connecting IEC Simulator (32 bit)
Introduction
The simulator simulates a PLC connected via TCP/IP, where the signal status of the
I/O modules can also be simulated. Up to 5 host computers are connected to the
simulated PLC at the same time.
To activate the simulator, select the protocol type IEC simulator (32 bit) in the
Connect to PLC dialog box.
Protocol Settings for IEC Simulator (32 bit)
The simulator is active, if you specify the address of your TCP/IP interface board in
the Protocol Settings: IEC Simulator (32 bit) range.
The TCP/IP address can be obtained on the title bar of the Concept simulator
program PLCSIM32.
NOTE: At the present time the simulator is only available for IEC languages (FBD,
SFC, LD, IL and ST).
33002204 12/2010
647
Online functions
State of the PLC
At a Glance
With a network link, the state of the PLC is displayed in the list of nodes in the
Modbus Plus network in the Link to PLC dialog box.
States of the PLC
All the states which can arise are listed in the following table:
648
State
Meaning
Running
Identifies a PLC with a program running.
Stopped
Identifies a PLC with a program which has stopped.
Unknown
Identifies an unknown PLC.
Not configured
Identifies a PLC without a hardware configuration, i.e. no online
functions are possible.
33002204 12/2010
Online functions
20.3
Setting up and controlling the PLC
Overview
This chapter contains information about setting up and controlling the PLC.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
General Information
650
Setting the Time for Constant Scans
651
Single Sweeps
652
Deleting memory zones from the PLC
654
Speed optimized LL984-Processing
655
Save To Flash
656
Reactivate flash save
659
Set PLC Password
660
649
Online functions
General Information
Introduction
The PLC and CPU functions can be controlled in ONLINE mode. The PLC must be
connected to the host computer to establish ONLINE mode.
You can control the PLC directly with the following commands:
Set Scan Time
z Single Scan Function
z Clear Controller
z Set Clock
z Run Optimized Solve
z Save in Flash
z Set Password for PLC
z
The commands for setting up and controlling the PLC can be found in Online →
Online Control Panel.
650
33002204 12/2010
Online functions
Setting the Time for Constant Scans
Introduction
A constant cycle time for processing the user program can be specified in the Online
→Online control panel →Invoke constant sweep →Constant Sweep Settings
dialog box.
However, if the actual cycle time is longer than the constant cycle time specified the
system ignores the user settings and uses the normal cycle running time (Cycle
time in free running mode).
If a constant cycle time is selected which is longer than the actual cycle time, the
control will wait during each cycle until the set cycle time has been reached.
NOTE: Inputs/outputs connected via communication experts may not be used for
updating constant I/O requests, as there can be highly variable I/O response times.
NOTE: This function cannot be performed when there is a link with the simulator.
Selection condition
This dialog box is only available if the link has been established between the PLC
and the programming device (ONLINE mode).
Settings for constant cycle
A tab (4x) must be specified first to determine the constant cycle. You also need to
enter the scan time (10-200m) that is allocated to the register.
NOTE: The scan time increases if several windows are open in Concept, e.g.
several sections are displayed in animation mode. Therefore if you are using several
windows you should reduce the scan time.
Exiting Constant Scan
After starting the constant scan with the Invoke constant sweep... changes the
designation of the command button in Cancel constant sweep.... Clicking on this
command button exits the function.
33002204 12/2010
651
Online functions
Single Sweeps
Introduction
You can specify single sweeps times for processing the user program in theOnline
→Online Control Panel →Single Sweep On… →Settings for Single Sweeps
dialog box.
After the specified number of scans has been performed the logic editing stops. This
function is helpful for diagnostic purposes. It allows the checking of edited logic,
modified data and calculations that have been carried out.
WARNING
It can lead to unsafe, dangerous and destructive operations of the tools or
processes that are attached to the controller.
Single sweeps should not be used for searching for errors in controlling machine
tools, processes or material maintenance systems if these are running. When the
number of scan times given has been processed, all the outputs will be retained in
their last state. Since no more logic editing is taking place, the controller ignores
all input information. Therefore the single sweeps function should only be used for
searching for errors during start up.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Selection Condition
This dialog box is only available if the link has been established between the PLC
and the host computer (ONLINE mode). Single sweeps are only performed in PLC
RUN mode.
Settings for Single Sweeps
To determine the single sweeps, the scan time (10 – 200ms) and the number of
scans being performed must be specified. A maximum of 15 single sweeps is
possible.
Execution of Single Sweeps
After the scan time and number have been specified you can perform the single
sweeps with the Trigger Sweep command button.
NOTE: The Trigger Sweep command button is only available in PLC RUN mode.
652
33002204 12/2010
Online functions
Exiting Single Sweeps Function
After the single sweeps function has been started with the Single Sweep On
command button, the designation of the command button changes to Single
Sweeps Off. Clicking on this command button terminates the function again, and
the Settings... and Trigger Sweep command buttons no longer appear in the dialog
box.
33002204 12/2010
653
Online functions
Deleting memory zones from the PLC
At a Glance
Specific memory zones can be deleted from the PLC by activating the
corresponding options key in theOnline →Online Control →Delete PLC... →Delete
PLC contents dialog box.
The menu command Load... can be used to load the deleted memory areas back
onto the PLC.
Condition for dial-in
This dialog box is only available if the link has been established between the PLC
and the programming device (ONLINE mode) and the PLC is in STOP mode.
Deleting a configuration
If the hardware function of a PLC is deleted, no further online functions can be
performed. The NOT CONFIGURED and NOT EQUAL TO modes are displayed in
the status bar.
Deleting a program
If the user program is deleted in the PLC, the PLC cannot be started. The NOT
EQUAL TO state is displayed in the status bar.
Deleting state RAM
If the state RAM is deleted, the initial values of the located variables in the PLC are
set to 0.
654
33002204 12/2010
Online functions
Speed optimized LL984-Processing
At a Glance
A speed optimized LL984 Processing can be optimized in the dialog boxOnline →
Online Control with the Opt. processing in command button.
After the command button is activated its designation changes in Opt. Processing
out. This means that a click on this command button will deactivate the speed
optimization which is running again.
NOTE: This function only influences the LL984- program.
Condition for dial-in
This dialog box is only available if the link has been established between the PLC
and the programming device (ONLINE mode) and the PLC is in STOP mode.
33002204 12/2010
655
Online functions
Save To Flash
Introduction
For data protection purposes, you can save parts of the RAM in the PLC's FlashEPROM. After a power failure, the contents of the Flash-EPROM is loaded back
onto the CPU RAM for the restart.
WARNING
Modified process status after next start!
It is important to choose the right time for saving to Flash, as there could be signal
values in the Flash memory which are downloaded later following a power failure,
and which do not correspond to the process status for the next start.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Selection condition
This function is available when using all 140 CPU 434 12 and 140 CPU 534 14 TSX
Compact, Momentum and Quantum modules.
This function is not available with IEC Hot Standby operation with Quantum.
The Flash memory function is not available when using the simulator.
Procedure
Carry out the following steps to Save To Flash:
Step
656
Action
1
In the Flash Type area, select the Internal or PC Card option button depending
on the hardware used.
Note: Applications that require more than 480 kBytes must be saved in the PC
Card Flash.
2
In the Controller State area, select the operating mode (RUNNING or
STOPPED) the PLC should be in after a restart.
3
Check the Allow Editing After Power Up check box if you want to edit the
uploaded Flash program when the voltage supply returns.
Caution: Since these later modifications were not downloaded onto the FlashEPROM, this data is lost if there is a power failure.
4
Check the Save State Ram check box if you want to save all 4x registers to
Flash-EPROM.
Note: This selection is not available with the Momentum family, i.e. all
applications are always downloaded to Flash-EPROM.
33002204 12/2010
Online functions
Step
Action
5
If you have checked the Save State Ram check box, you must enter the number
of registers to save in the Number of registers to save text box. The
corresponding register area, which is downloaded onto Flash-EPROM, is then
set from the 400001 address.
6
Select the Save To Flash command button to load the user program, the
configuration, the IEC programming initial values from the RAM to the Flash
EPROM.
Edit Flash program
As soon as the Allow Editing After Power Up check box is checked, on saving to
Flash, information is loaded to the Flash-EPROM, which after uploading the
contents of Flash (e.g. in the case of the return of the power supply) allows the
program to be edited. Since these later modifications were not downloaded onto the
Flash-EPROM, this data is lost if there is a power failure. To prevent this, changes
should be downloaded to Flash-EPROM by using the Save To Flash command
button.
Modification of the Flash program is not allowed.
As soon as the Allow Editing After Power Up check box is unchecked, the
program can be modified after reading the Flash contents (e.g. in the case of the
return of the power supply), but cannot be loaded to the Flash EPROM.
Modifying the program leads to the following reactions when uploading:
Procedure:
Changes protected
with Download
changes...
Changes protected
with Save project
The following status
is established after
connection:
a)
Yes
No
EQUAL
b)
Yes
Yes
NOT EQUAL
If the EQUAL status is established in the above case a), the contents of the host
computer are different from the contents of the Flash-EPROM. After a power failure
the Flash-EPROM is uploaded, resulting in the loss of all changes.
If the NOT EQUAL status is established in the above case b), the contents of the
Flash-EPROM are different from the contents of the host computer. After a power
failure the Flash-EPROM is uploaded, resulting in the loss of all changes.
NOTE: To download a program change to Flash EPROM again, the Save To Flash
command button must be available again. Specific steps must be carried out to do
this, as described in the Reactivate flash save, page 659 section.
33002204 12/2010
657
Online functions
M1 Ethernet CPU
The password protected application is automatically downloaded on each switching
on/off cycle. This procedure cannot be undone if you forget the password. The PLC
must be sent for repair.
658
33002204 12/2010
Online functions
Reactivate flash save
Introduction
If you have not checked the check box in Flash Save Allow Editing after Power Up
the program saved in Flash EPROM can no longer be changed. After a power failure
the Flash-EPROM will finish on restarting the PLC. However, the command buttons
Save to Flash and Clear Flash are not available.
Reactivate Flash Save
In order to enable the Flash Save again, the following steps are necessary:
Step
33002204 12/2010
Action
1
Turn off the controller.
2
Compact CPUs: Set the "Memory Protect" switch (Memory Protect) to ON.
Quantum CPUs: Set the switch to the "stop" position.
3
Turn the controller on again.
4
Compact CPUs: Set the "Memory Protect" switch (Memory Protect) to OFF.
Quantum CPUs: Set the switch to the "start" position.
5
Make the link between the host computer and the controller (Online →
Connect...).
6
Open the dialog box Save to Flash (Online →Online control panel →Flash
Program...).
Result: The command buttons Save to Flash and Clear Flash are now
available again.
659
Online functions
Set PLC Password
Introduction
You can use a password to prevent the PLC being written to without permission.
Before you can set a new password, however, you must first download the
configuration to the PLC. Then enter the password that is to loaded to the PLC. The
password is now saved so that password protection operates when a connection is
made between the host computer and the PLC (password required).
NOTE: When setting a Quantum password, a specific time can also be set for the
automatic cancel function in the Quantum Security Parameter dialog box. This
function is found in the preference setting Never. This function means that the user
is logged out after the time specified as soon as no read or write access occurs from
the programming device to the PLC through this connection within the predefined
amount of time.
Valid characters for the PLC password and user name
The following characters are permitted within the character length of 616 characters:
z a ... z
z A ... Z
z 0 ... 9
z _
NOTE: Spaces, umlauts (e.g.: ä, ö, ü) and special characters are not allowed!
Selection conditions
This function is available when using all TSX Compact CPUs, a Quantum CPU 434
12 A/534 14 A/B or a Momentum Ethernet CPU.
Note
The following passwords can be assigned in Concept:
PLC password
z Concept Password (see page 767) (in Concept Security)
z
660
33002204 12/2010
Online functions
Set new PLC password
To set a new PLC password, proceed as follows:
Step
Action
1
Using Online →Download load the configuration onto the PLC
2
Using Online →Online Control Panel... →Set PLC password... open the
dialog Change PLC Password.
3
Enter your new password in the Enter New Password: text box.
4
Enter the new password in the Confirm New Password: text box again.
5
Enter the user name in the User name text box, e.g. "anyname".
6
Press the OK command button.
Reaction: The dialog box is closed and the password is automatically
downloaded to the PLC
Change Old PLC Password
To change an old PLC password, proceed as follows:
Step
33002204 12/2010
Action
1
Using Online →Online Control Panel →Set PLC password... open the dialog
Change PLC Password.
2
Enter your old password in the Enter Old Password: text box.
3
Enter your new password in the Enter New Password: text box.
4
Enter the new password in the Confirm Password: text box again.
5
Enter the user name in the User name text box.
6
Press the OK command button.
Reaction: The dialog box is closed.
7
Using Online →Download load the configuration onto the PLC
Reaction: The password was loaded onto the PLC, and will be requested the
next time the PLC and the host computer are connected.
661
Online functions
If You Forget Your Password
If the PLC password has been forgotten the procedure depends on the PLC platform
used.
Quantum and Compact:
Step
Action
1
Switch off the power supply to the PLC.
2
Move the Memory Protect switch on your hardware module to the MEM_PROT
position.
3
Remove the lithium battery from the PLC.
4
Wait 5 minutes and then switch on the power supply to the PLC again.
Reaction: By doing this, the battery backup RAM is deleted without
downloading the PLC program from Flash-EPROM. In this way, the start status
of the PLC (configuration-free and without log on password) is re-established.
5
Continue with the step table Set new PLC password, page 661.
Momentum without Flash:
Step
Action
1
Switch off the power supply to the PLC.
2
Remove the battery from the interface adapter.
3
Wait 5 minutes and then switch on the power supply to the PLC again.
4
Continue with the step table Set new PLC password, page 661.
Momentum with Flash:
Step
662
Action
1
Switch off the power supply to the PLC.
2
Send the module back to the product manufacturer (Schneider Automation
GmbH).
33002204 12/2010
Online functions
20.4
Selecting Process information (status and
memory)
Overview
This chapter contains information about selecting the process information.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
General information
664
PLC state
665
Memory Statistics
667
663
Online functions
General information
At a Glance
Certain processes and their storage occupancy can be controlled during operation
of the automation equipment.
NOTE: Errors can occur when selecting a configuration that has been generated by
another configuration tool (e.g. SyCon, CMD). The selection is based on removing
the memory, whereby this is not always compatible with the other software
programs. Therefore please use the Modsoft Converter to transfer the Modsoft
application according to Concept.
Read status bits.
Status bits provide information about the hardware communication with other
modules as well as existing errors in the running of the program. The user specifies
the status register already during configuration. In this register , status bits that
change their state as soon as a faulty signal is set in the process or a timeout word
is not observed are saved. The user can recognize via defined status states (0 or 1)
whether the process is faulty.
Read storage occupancy
The user can control the storage occupancy for the current project in the memory
statistics. In an overview the total memory, free memory space and used memory
for the user program, as well as the user files and FFB libraries are displayed.
664
33002204 12/2010
Online functions
PLC state
At a Glance
All the PLC states are displayed in the multi-page dialog box.
There are 67 pages altogether, containing various state information
Condition for dial-in
This function is only available if a link has been established between the PLC and
the programming device. When the simulator is active the PLC states cannot be
retrieved.
Programming states
The following status information is obtained through the programming:
z Number of segments
z
End of logic pointer address
z
Run/Download/Debug Status
Hardware states
The following state information is given about the hardware:
CPU state
z
z
S911 Hot Standby State
z
Machine State
z
State of the I/O processor
z
Quantum I/O state
z
DIO-State
Error codes
The following state information is given about errors arising:
Machine stop code
z
z
Quantum start error code S908
Transfer and communication states
The following state information is given about transfer and communication
executions:
z Data transfer state
33002204 12/2010
z
Message transfer state
z
Communication state
665
Online functions
Cable A + B states
The following state information is given about the A + B cable:
Cable A + B error counter
z
666
z
A + B global state
z
Cable A + B communication error counter
33002204 12/2010
Online functions
Memory Statistics
At a glance
An overview of the IEC memory data for the open project is provided in the Memory
Statistics dialog box. The current scan time will be displayed if a real PLC is used
(i.e. not the simulator). This dialog box does not show information concerning LL984
memory. Information for IEC HSBY memory, which is part of the state RAM (number
of input registers), is not shown either.
Total IEC memory
The value shown for the total memory is the value specified in the PLC Selection
dialog box.
Modifying the total IEC memory size
The total IEC memory consists of the IEC program memory, the global data, and the
EFB memory. Additional space is required in the total IEC memory for program
expansions and for the administration of program changes. The general recommendation is to set the value in such a way that 20-30% of the value entered in the Used
text box will remain free.
NOTE: Changes can only be made offline and are only applied once the program
has been loaded onto the PLC.
33002204 12/2010
667
Online functions
IEC Program Memory
The program memory includes the program code, the EFB code, program data
(section data and DFB instance data), upload information, diagnosis information,
and administration information.
Memory information
Meaning
Configured
Once you have defined the size of the total IEC memory, the
global data, and the size of the EFB memory, you will obtain
information regarding the size of the IEC program memory
(IEC program memory = total IEC memory - global data - EFB
memory).
Free
Shows the available IEC program memory.
The values displayed correspond to the memory space used for:
Program code
z
z
EFB code
z
Program data (section and DFB instance data)
z
Upload information
z
Diagnostic information
z
Administration information
Defragmentation
The value displayed corresponds to the current Defragmentation status.
Defragmentation is enabled in the PLC Selection dialog box. Defragmentation is a
continuous process that ends with a value of 0 after a certain period. "0" in this case
means that there are no more gaps in the PLC's memory.
Since this continuous process affects the scan time, it can be disabled in the PLC
Selection dialog box.
Global Data
The memory statistics cover the following information:
668
Memory information
Meaning
Configured
The value shown corresponds to the memory space set for
unlocated variables in the PLC Selection dialog box.
Free
The available memory for unlocated variables is shown here.
33002204 12/2010
Online functions
Changing the memory space used for global data
You can change the memory space used for global data. It should be noted that
increasing the memory space for global data will decrease the IEC program memory
size. Each object, e.g. FFB instance, variable, step etc., takes up several bytes in
the IEC program memory.
Since deleting unlocated variables does not free up more memory space
automatically, we recommend making plans so as to have sufficient memory space.
The general recommendation is to set the value in such a way that 20-30% of the
value entered in the Used text box will remain free.
NOTE: Changes can only be made offline and are only applied once the program
has been loaded onto the PLC.
EFB Memory
The EFB memory is used by the user program that contains the EFB code. The latter
must not be moved during the memory defragmentation process:
Memory information
Meaning
Configured
The EFB memory size configured in the PLC Selection dialog
box for PLC memory defragmentation is shown here.
Free
Shows the available EFB memory.
Scan Time
The value displayed corresponds to the current scan time. With the first call, the I/O
station is standardized so that a scan time of 0 ms/scan is shown. After initialization,
the scan time is calculated as an average value.
NOTE: If you are using the simulator, the scan time is not shown. na means “not
available”.
33002204 12/2010
669
Online functions
20.5
Loading a project
Overview
This chapter contains information about loading a project.
What's in this Section?
This section contains the following topics:
Topic
670
Page
General information
671
Loading
672
Download Changes
674
Uploading the PLC
677
Upload Procedure
679
33002204 12/2010
Online functions
General information
At a Glance
To carry out an online command a transfer has to be made to the PLC after setting
up or changing sections. Otherwise a complete project can be transferred from the
PLC to the programming device. As soon as the user program is consistent on the
programming device and the PLC, the EQUALS status is displayed in the status bar.
The status display MODIFIED identifies the program in which at least one section
has been changed or where changes to the variable editor were performed. With
command button Load changes... the consistency between the programming
device and the PLC is restored. Status display NOT EQUALS identifies a program
in which critical changes were performed. Critical changes are for example changes
to EFBs, DFBs or derived data types. With command button Load... the consistency
between the programming device and the PLC is restored.
Loading, loading changes and selecting are not possible in the animation mode.
With command button Select... the following project areas can be selected from the
PLC:
z Configuration
z IEC sections
z 984 Ladder Logic sections
z ASCII messages
z State RAM
z Initial values
z Extended memory
Process for loading
Loading the PLC can take place in two parts:
1. The exportable code (machine code) is always loaded onto the PLC.
2. The complete compressed user program is loaded onto the PLC
NOTE: The user program, consisting of user defined EFBs, DFBs, derived data
types and the program (variables, sections, etc.), is only loaded onto the PLC if in
dialog Options for generating codes (Project →Options for generating
codes...) check box contain IEC selection information was activated beforehand.
The option to also load the comments contained in the check box onto the PLC,
thereby making them available as selection information, is available, as well.
During selection the entire user program can be transferred from the empty project
to the programming device.
33002204 12/2010
671
Online functions
Loading
Introduction
With menu command Load...the configuration, the entire user program (IEC or
LL984 sections) ASCII messages (only with Concept for Quantum) and the state
RAM with the initial values of a project can be sent to the PLC. This establishes
consistency between the user program on the programming device and the PLC so
the online functions are executable.
Loading single parts onto the PLC
Single parts to be loaded onto the PLC can be selected.
The following table contains the available options and their meaning:
672
Option to be loaded
Meaning
Configuration
This option sends the hardware configuration to the PLC.
Note: The Hardware Configuration can only be sent to the PLC
when a corresponding access privilegehas been authorized. This
option is not available with a Modbus Plus connection.
IEC Sections
This option sends the code from all the sections created with an
IEC programming language (FBD, SFC, LD, IL, ST) to the PLC.
984 Ladder Logic
This option sends the code from all the sections created with an
LL984 programming language to the PLC.
ASCII messages
This option sends ASCII messages for Ladder Logic to the PLC.
Note: This function is only available when using Concept for
Quantum.
State RAM + Initial
Values
With this option, at first all initial values of the Located 4xVariables are copied from the Variable Editor into the state RAM
mirror (image). Then, the initial values and all blocked 0x- and 1xI/O bits from the state RAM mirror (Image) are loaded into the
PLC.
Note: While the PLC is running, all non-blocked 0x-variables are
reset by the firmware in the PLC. Thus, values of 0x- and 1xvariables are only loaded if the variables are in blocked status.
Only state RAM
With this option, the initial values of the Located 4x-variables and
all blocked 0x and 1x I/O bits are loaded from the state RAM
mirror (Image) into the PLC.
Only initial values
With this option, exclusively initial values of the Located 4xVariables are loaded from the Variable Editor into the state RAM.
Expanded memory
This option assigns the PLC an extended memory allocation (6xreferences).
Note: This function is only available when using Concept for
Quantum.
33002204 12/2010
Online functions
Loading IEC selection information
To obtain a complete project when uploading from the PLC Options for code
generation the check box Include IEC Upload Information must be activated in
the dialog box before loading. If this check box is not activated only the executable
code (machine code) is loaded onto the PLC.
If loading is not possible
There are several possibilities why loading is not possible:
z An active screen saver can lead to loading errors. It is therefore recommended to
deactivate the screen saver.
z If loading the program is not possible due to insufficient program data memory,
the memory size can be optimized.Main structure of PLC Memory and
optimization of memory, page 155.
NOTE: If, while loading the program, a warning appears due to inconsistent DFB
versions, use the menu command Project →Synchronize nested DFB versions.
33002204 12/2010
673
Online functions
Download Changes
Introduction
Download changes is always used if sections have been changed, added or
deleted, whether online or offline, and the program is in MODIFIED state. In this way
the changes are indicated and can be transferred to the PLC.
The changes are loaded into the PLC and the consistency between the user
program on the programming device and the PLC is restored.
With changes that do not influence the logic of the program (e.g. renaming a step
name, renaming a section, renaming a variable, graphic moving of a component,
etc.), the state of the program between PLC and host computer will remain EQUAL
and cannot be downloaded to the PLC using the Download changes function.
However, the changes will not be lost. They can be updated with the Download
changes function during the change, which will result in the state of CHANGED. Or
the entire project is downloaded to the PLC using the Online →Download function.
NOTE: However, if you wish to update your changes immediately, simulate a Modify
code (e.g. delete and restore), so that the state of the program changes to
MODIFIED. Then carry out the Download changes function.
If the changes cannot be downloaded because there is too little memory in the PLC,
there are 2 possibilities for proceeding:
z Sequential loading of modified sections
z Optimize Project
NOTE: If, while loading the program, a warning appears due to inconsistent DFB
versions, use the menu command Project →Synchronize nested DFB versions.
ID for specific sections
The following sections contain additional ID information as they are different from
cyclically set sections:
z E for "Event Section" (I/O Event and Timer Event Section = Interrupt-Section)
z T for "Transition Section"
674
33002204 12/2010
Online functions
Sequential loading of modified/new sections
The user can download changed/new segments onto the PLC one after the other.
When segments are downloaded sequentially, the following points must be noted:
z If the constants value has been changed, it is not possible to download the
changed segments sequentially.
z All deleted IEC segments will be automatically deleted the first time the user
downloads sequentially onto the PLC.
z All initial values of new variables, all modified values of literals are automatically
loaded onto the PLC on the first sequential loading.
z If new sections already contain used variables, the value of these variables
remains.
z When closing a project ensure that it is saved before loading changes onto the
PLC. Otherwise it might not be possible to continue the project after it is reopened
with the remaining changes loaded, or there will be "newer" sections (previously
loaded changes) on the PLC than on the programming device.
CAUTION
Risk of unwanted and dangerous process states
Loading sections sequentially on a running PLC can lead to unwanted and
dangerous process states. It is therefore recommended to stop the PLC during
sequential loading.
Failure to follow these instructions can result in injury or equipment damage.
Modified Initial values
Modified initial values are no longer loaded onto the PLC. The initial value during the
first download (Download.../Download changes...) that was downloaded to the
PLC cannot be overwritten with the menu command Download changes.... The
initial values can however be changed in the Reference data editor.
Procedure for sequential loading
The procedure for downloading changes sequentially is as follows:
Step
33002204 12/2010
Action
1
Stop the PLC with Online →Online control →Stop controller.
2
Select the segment(s) which must be downloaded from the list.
3
Confirm using OK.
4
Call the dialog box again and repeat the process until all modified/new sections
are loaded onto the PLC and EQUAL mode is reached.
5
Start the PLC with Online →Online PLC →Start PLC.
675
Online functions
Loading IEC upload information
If, in the Code generation options dialog, the check box Include IEC upload
information is checked, IEC upload information is loaded onto the PLC with the
Download changes...menu command.
Optimize the Project
It may be possible to eliminate existing gaps in the program data memory
management of the PLC with the menu command Optimize projectand enable
loading again in this way. However, the PLC must be stopped and the complete
program must be downloaded again. Furthermore, it may be necessary to adjust the
size of program data memory, see Memory statistics (see page 667).
It is still possible to optimize use of the program data memory with the menu
command Online →Memory statistics.
CAUTION
Modifications are only transferred when the program is loaded onto the PLC.
After optimizing the project or modifying the program data memory size the PLC
must be stopped and the program loaded onto the PLC.
Failure to follow these instructions can result in injury or equipment damage.
676
33002204 12/2010
Online functions
Uploading the PLC
Introduction
With menu command Upload...the configuration, the entire user program (IEC
and/or LL984 sections), the ASCII messages and the state RAM with a project’s
initial values can be transferred from the PLC to the host computer.
NOTE: Upload information (PLC configuration), which was generated by the
Software programs as Concept, is possibly erroneous. The upload is based on
removing the memory, so that it is not always compatible with other software
programs. Please use the Modsoft converter for transferring your Modsoft
application to Concept.
Reading Individual Parts from the PLC
Individual parts to be loaded from the PLC to the host computer can be selected.
The following table contains the available options and their meaning:
33002204 12/2010
Option to be loaded
Meaning
Configuration
This option sends the hardware configuration to the host
computer.
Note: The hardware configuration can only be sent from the PLC
when a relevant authorization is granted in the Access Rights.
This option is not available with a Modbus Plus connection.
IEC sections
This option transfers the revertive presentation information of all
the sections created with an IEC programming language (FBD,
SFC, LD, IL, ST) to the host computer. In this process, however,
no current signal values from variables and registers are loaded.
984 Ladder Logic
This option sends the revertive information from all the sections
created with an LL984 programming language to the host
computer.
ASCII messages
This option transfers ASCII messages for Ladder Logic to the
host computer.
Note: This function is only available when using Concept for
Quantum.
Upload state RAM +
update initial values
With this option, first all Located 0x-, 1x- and 4x-values are read
from the SPS, and saved in the state RAM mirror (Image). Then,
the initial values of the 4x-variables are overwritten with the value
from the state RAM mirror (Image). With the upload process, the
dialog box Upload initial values is then opened. With the
command button Yes you confirm the overwriting of the initial
value displayed with the new value.
Note: Uploaded state RAM values can be overwritten in the RDE
by Online Operations. This behavior can be changed, however,
in the CONCEPT.INI-file (see page 1118).
677
Online functions
Option to be loaded
Meaning
Only update initial values With this option, the initial values of the Located 4x-Variables are
overwritten by the Variable Editor with values from the state
RAM.
678
Only upload State RAM
With this option, all Located 0x-, 1x- and 4x-values are read from
the SPS, and saved in the state RAM mirror (Image). The initial
values in the Variable Editor are not overwritten.
Expanded memory
This option transfers the PLC’s available extended memory (6x
references) into the configuration.
Note: This function is only available when using Concept for
Quantum.
33002204 12/2010
Online functions
Upload Procedure
Introduction
If the IEC upload information was being taken into account during loading into the
PLC (Project →Code Generation Options →Include IEC upload information), a
new project containing the IEC upload information is generated in Concept during
upload. In this way, the entire user program and user EFB libraries are always
downloaded, i.e. individual sections, EFBs etc, cannot be selected for transfer.
NOTE: During loading (Online →Download Controller) of the IEC upload
information, additional memory is required so that this function should only be used,
when you want to upload the project loaded into the PLC again.
Requirements
In order to carry out a PLC upload, an empty project must first be created.
There are several ways of doing this.
33002204 12/2010
Selectio
n
Action
1
You can create an empty project using the File →New project menu command.
Then execute the Online →Upload... menu command.
Result: The Upload to project dialog is opened. Here you can determine (e.g.
D:\NEW\TESTPRJ.PRJ) where the project will be uploaded to.
Note: You can select a different directory or even create a new directory so as
not to come into conflict with existing projects. The preset project name
corresponds to the project name downloaded in the PLC and does not
necessarily have to be changed.
2
Using the File →Open... menu command you can create a new project (e.g.
D:\NEW\TESTPRJ.PRJ) Then execute the Online →Upload... menu command.
Result: The Upload Controller dialog is opened.
3
There is no project open and you have established a connection with the PLC
using the Online →Connect... menu command. Then execute the Online →
Upload... menu command.
Result: The Upload to project dialog is opened. Here you can determine (e.g.
D:\NEW\TESTPRJ.PRJ) where the project will be uploaded to.
Note: You can select a different directory or even create a new directory so as
not to come into conflict with existing projects. The preset project name
corresponds to the project name downloaded in the PLC and does not
necessarily have to be changed.
679
Online functions
Procedure
To upload loaded IEC information, proceed as follows:
Step
Action
1
Open a new project.
Note:If, during upload, there is a second project still open, it must be closed. In
this case a query appears asking whether the project should be saved before it
is closed and all changes are lost.
2
Establish a connection between the PLC and the programming unit ( Online →
Connect...).
3
Start the upload procedure (Online →Upload Controller...).
Result: A window appears in which you can determine the path for the project
that is to be uploaded.
Double Designation
Conflicts with existing names can occur during the upload procedure.
Double designation is prevented for each program sequence as follows:
680
Program
sequence
process
User EFB library
A query appears, which can interrupt uploading. If not, a query appears,
asking whether the user EFB library should be overwritten, and whether
a backup of the old EFB library should therefore be created.
DTY File (derived
data types)
A query appears, which can interrupt uploading. If not, the DTY file of the
same name is automatically overwritten. No backup is made of the old
file.
DFB library
A query appears, which can interrupt uploading. If not, the DFB file of the
same name is automatically overwritten. No backup is made of the old
file.
33002204 12/2010
Online functions
20.6
Section animation
Overview
This chapter describes the basic principles for animating sections. The details can
be found in the chapters on individual programming languages.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
IEC-Sections animation
682
LL984 Programming Modes
684
681
Online functions
IEC-Sections animation
At a Glance
IEC sections can be animated, i.e. the program’s current states in the PLC /simulator
will be displayed.
Animation is possible with both a running and a stationary PLC. Display data is
automatically refreshed when the PLC is running. The static state of the program on
the PLC is displayed when the PLC is stationary.
Load and Load changes is not possible in animations mode. Should these
commands be executed, animation will be stopped automatically.
Requirements for animation
Requirements for animation
The section to be animated in the programming device and the section loaded
onto the PLC must be consitent. Otherwise, establish consistency using Online
→Load... (if mode UNEQUAL) or Online →Load changes... (if mode
MODIFIED).
Note: Even when the program mode is MODIFIED, the sections that have not
been changed can be animated. The mode displayed in the footer refers to the
program and not to the currently displayed program.
z To animate, the programming device and the PLC must be online. Otherwise,
establish the link using Online →Link... .
z
Active animation display
The active animations mode is indicated:
by a check mark before the menu command, in the ANIMATEDbox on the status
bar,
z by a depressed animations button on the symbol bar and
z by the gray window background.
z
Animating more than one section
If several sections are animated, an animated section is updated in each cycle. This
means that the more animations are active, the "older" the values of the individual
animations. Additionally, the animation increases the load on the PLC cycle. For this
reason, animations that are no longer necessary should be terminated. This also
applies to the animation of many variables or very large derived data types.
NOTE: When coupling using Modbus Plus, it is recommended that no more than 10
sections should be animated at one time.
NOTE: When coupling using Modbus, it is recommended that no more than 5
sections should be animated at one time.
682
33002204 12/2010
Online functions
Animating a disabled section
If a disabled section is animated, the state INHIBITED is displayed in the status bar.
Animation of a transition section
If the animated section is used as a transition section for the sequential control
(SFC), and the transition (and therefore also the transition section) is not processed,
the status INHIBITEDappears in the transition section.
Changing a animated section into a symbol
If an animated section is changed into a symbol, the animation with the most current
values stops, and then restarts automatically once the section is called.
33002204 12/2010
683
Online functions
LL984 Programming Modes
Direct Programming
There are two situations that determine how direct mode ladder editing is applied.
The first is where there is no open project and you are connected to a PLC that has
a valid program in it. When you select the command Direct Mode LL Editor the first
program in the first segment is displayed. You can see the direct mode status at the
right side of the status bar and the network window is labled 984 LL Direct.
The second case occurs when you have a project open and you are connected to
the PLC (but not EQUAL ). When you select Direct Mode LL Editor in this case a
dialog is displayed listing segments and the number of networks contained in each.
Click on the segment you want click on OK and the network edit window is displayed
with a window labeled 984 LL Direct. If you have an orignal edit window it will remain
on the display.
Combination Mode
Combination programming occurs when the programming panel is online. Valid
program changes are immediately written to both the controller and the program
database simultaneously.
684
33002204 12/2010
Online functions
20.7
Online Diagnosis
Diagnostics Viewer
Introduction
Using the diagnostics viewer in Concept (Online →Online Diagnostics...) it is
possible to view the content of the PLC diagnostics error buffer.
Selection Condition
The diagnostics viewer is only available if the PLC is in online mode and the EQUAL
status has been created between the PLC and host computer.
The diagnostics viewer only works with the SFC, FBD and LD programming
languages and with the diagnostics blocks of the EXTENDED group.
Conditions of the Diagnostics Viewer
To activate diagnostics, a supervision time must first be set for the step (Transition
diagnostics) or the diagnostics block (Reaction diagnostics). In addition, in the Code
generation options dialog (Project →Code generation options...), the Include
diagnosis information check box must be checked. As a result memory space is
prepared on the PLC (max. 64 diagnostics entries) for the diagnostics error buffer.
Behavior of the error buffer
A maximum of 64 events (errors) and a maximum 20 signals per event are read. If
the diagnostics error buffer overflows all further signals (21 onwards) are lost. The
next event (error) coming is only entered once an event (error) which has gone has
been acknowledged in the error buffer.
A diagnostics error buffer overflow is displayed in the dialog status line.
NOTE: A maximum of 16 events (errors) can be scheduled within one SFC section.
All further errors (17 onwards) are lost. The next event (error) is only entered once
a past event (error) has been acknowledged in the error buffer.
Transition Diagnosis
Information on this can be found in the Transition diagnosis, page 319section.
Reaction diagnosis
Information on this can be found in the "Diagnostics Block Library" handbook.
33002204 12/2010
685
Online functions
Diagnostics viewer
After analysis, the events (errors) and the analyzed signals are written in the buffer
and displayed in the diagnostics viewer in Concept.
The following specific information is contained in transition diagnostics:
Denotes the transition preventing the active step from being executed to the next
step.
z Denotes the TRANS type for transition in a PLC section
z Denotes the active step, which is not executed.
z If this is a transition section in the named transition, the analyzed signals are also
listed.
z
The following specific information is contained in reaction diagnostics:
z Denotes the diagnostics block preventing a reaction from being triggered due to
incorrect signals.
z Denotes type ACT, PRE, GRP, LOCK, REA for diagnostics blocks
z Diagnostics block drop number
z The analyzed signals are listed.
686
33002204 12/2010
Online functions
20.8
Logging Write Access to the PLC
Logging and Encrypted Logging
Introduction
Logging the write access to the PLC can record the following data among others:
z Section name
z EFB/DFB Instance name, FB type name
z Pin-Name
z [variable name] [literal] [address]
z Old value
z New value
z User name (if the Concept (Login) password is activated in Concept Security)
z Date and Time (see alsoAddress format in LOG file [Logging], page 1116)
The following logging can be carried out during log-on:
z Modification of the user rights
z Deleted user
z Aborted log-on
Besides the log which can be read in the *.LOG file, an encrypted log can be created
in an *.ENC file. The file name is made up of the current date, e.g. 20020723.LOG
or 20020723.ENC.
Encrypting the protocol file is done to protect the file contents from being changed.
The view tool is only provided so that the user can read the log file. Saving the file
in another readable format is not possible. Editing the file so that it is not
recognizable is impossible since the ASCII file only displays unrecognizable
characters.
NOTE: Log files are not archived by Concept and no backup files are created.
Log *.LOG
Logging is activated in Concept using the Options →Preferences →Common... →
Common preferences with the File option dialog box. Use the text box Directory
for Log-File: to define a new path for the log file (e.g. 20020723.LOG).
33002204 12/2010
687
Online functions
Dialog Common Preferences:
The current logfile can be viewed in Concept with menu command File →View
Logfile.
Encrypted Logfiles *.ENC
In addition, any repetitive strings are displayed in separate encrypted strings in the
logfile.
In Concept, the encryption can be activated with two different settings:
With menu command Options →Preferences →Common →Common
Preferences and the activation of the check box Encypt Logfile.
Note: The check box is only available if no project is open.
z Indirectly with the menu command Project →Project Properties and the
activation of the check box Secure Application.
Note: This dialog box is only available in offline mode.
z
688
33002204 12/2010
Online functions
Dialog Project Properties:
If the encryption is activated after an unencrypted logfile (*.LOG) has been created,
then a second encrypted logfile (*.ENC) is created. The storage location for the
*.ENC file is defined in the Common Preferences (Directory for Log-File:) dialog
box.
NOTE: Supervisor rights are required for activating the encrypted logging
procedure.
View Tool
The View tool can be used for reading encrypted logfiles. Editing and saving so that
the file can be read normally is not possible but the logfile can be printed. Supervisor
rights are required in this case as well. With menu command File →View Protocol
the View tool is opened automatically if encryption has been activated for the current
log.
The logfile is stamped with an electronic signature and the following tests are
performed:
z The logfile is created by Concept.
z The logfile is not a counterfeit.
33002204 12/2010
689
Online functions
690
33002204 12/2010
Import/Export
33002204 12/2010
Import/Export
21
Overview
This chapter describes the various import and export options for sections, variables
and PLC configurations.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
21.1
General Information about Import/Export
692
21.2
Exporting sections
694
21.3
Exporting variables and derived data types
697
21.4
Section import
698
21.5
Variables import
716
21.6
Import/Export of PLC Configuration
726
691
Import/Export
21.1
General Information about Import/Export
General Information about Import/Export
Export functions
The following export options are available:
Program
Path
Export files
Concept
Concept DFB
File →Export
z Sections from a source project and import
into a target project
z Sections from a source DFB and import into
a target DFB
z Sections from a source DFB and import into
a target project
z Sections from a source project and import
into a target DFB
z FBD, SFC and LD sections into IL or ST
files
z Variable declarations into an ASCII file
(Concept only)
z PLC configuration (Concept only)
Concept
Edit →Save as text file...
z Contents of IL or ST sections into an ASCII
file
z Definitions of Derived data types from the
Data type editor
692
Concept
File →Archiving...
Relevant project files (compressed)
Concept
Converter
File →Export →
Configuration
PLC Configuration
33002204 12/2010
Import/Export
Import functions
The following import options are available:
Program
Path
Import files
Concept
Concept DFB
File →Import
z Exported sections from a source project or
source DFB
z Exported or externally created IL/ST files
into IL/ST sections
z Exported or externally created IL/ST files
into FBD/SFC sections (with conversion)
z Variable declarations from an ASCII file
(Concept only)
z PLC configuration exported with Concept
(Concept only)
Concept
Edit →Insert text file...
z Contents of ASCII files IL or ST sections
z Definitions of Derived data types into the
Concept
File →Archiving...
Relevant project files (decompressed)
Concept
Converter
File →Import
PLC Configuration
Data type editor
33002204 12/2010
693
Import/Export
21.2
Exporting sections
Exporting Sections
Introduction
In Concept it is possible to export projects or DFBs selectively from a source
project/source DFB, and if desired, to then import them immediately into the current
target project.
Requirements
The project from which the export is to take place must be stable (check using
Project →Analyze Program).
NOTE: When exporting IL and ST sections, ensure that the settings for nested
comments (Options →Preferences →IEC Extensions →Allow nested
comments) are identical in the source and target projects.
Export range
The following are exported:
the selected sections with their accompanying variables, DFBs, EFBs and data
types.
z In the case of SFC, the accompanying transition sections are also exported.
z The PLC configuration is not exported.
z
Exporting more than one section
When more than one section is exported, a "pseudo SFC" is generated to maintain
the execution order. To do this, the following code is generated:
INITIAL_STEP
SECTION_SCHEDULER:
Section1 (N);
Section2 (N);
:
SectionN (N);
END_STEP
Exporting FBD, SFC and LD Sections
Using File →Export →Program: IEC Text FBD, SFC and LD sections can be
exported to IL and ST. The text languages of both export files follow the grammar of
IEC text languages, shown in IEC 1131-3 and in the process tables 52 - 56 of IEC
1131-3.
694
33002204 12/2010
Import/Export
The exported code is displayed in a PROGRAM … END_PROGRAM or
FUNCTION_BLOCK ... END_FUNCTION_BLOCK frame and contains all project or
DFB variables in a VAR ... END_VAR frame at the start of the file.
If more than one section is being exported, the code separation is expressed as an
artificial PLC frame, which is not a component of the original program. It only has
one INITIAL_STEP for all sections linked to it as actions (with the identifier N). These
actions (sections) are executed every time the step is active, which is always the
case. The actions follow as sections, which do not have variable declarations.
The artificial INITIAL_STEP has the name SECTION_SCHEDULER. It displays the
execution order as it was specified in the section execution order dialog box. The
artificial SFC frame is left out when re-importing in Concept. The criterion for this
omission is the specific name SECTION_SCHEDULER.
The ASCII file can be re-imported into a FBD or SFC section using the IEC text
import. Using exports and imports it is possible, for example, to convert a LD section
into a FBD section. Importing into a LD section is not possible.
If the EN and ENO optional imports/exports have been used in the FBD/LD sections,
they are ignored when exporting to IL/ST.
FBD section logic before export:
FBD section logic after import:
The LD elements "N.C. contact" and "N.O. contact" are converted to AND and
ANDNOT.
The ASCII file can, however, also be imported into an IL or ST section using the
Insert Text File function. In this case, however, manual correction of the files is
necessary, since the extensions described above must be removed again from the
file.
33002204 12/2010
695
Import/Export
SFC Export Limitations
The following limitations should be noted when using SFC import:
Only variables are permitted as actions. Direct addresses cannot be exported.
z Only literals are allowed as time variables for identifiers. Variables are converted
to literals with the value 0.
z Transition section names are changed to standard names.
z Step monitoring times and step delay times are lost when exporting.
z
Exporting IL and ST Sections
Using Process →Save as Text File... it is possible to export the contents of IL or ST
sections into an ASCII file.
This export function is a simple text export function, which can also be performed via
the clipboard (cut/copy/paste). Data conversion does not take place. For this
reason, the required variable declarations, for example, are not exported with the
section contents. If the ASCII files are to be converted to an FBD or SFC section
using File →Import →Program: IEC Text, all information necessary for the project
(e.g. program frame, section name (see also Importing (insert file) IL and ST
programs into IL or ST sections, page 712 and Procedure for "Copying" an IL
section from an existing project into a new project., page 713)) must be entered
manually.
696
33002204 12/2010
Import/Export
21.3
Exporting variables and derived data types
Exporting variables and Derived Data Types
Exporting variables in "Text delimited" format
Using File →Export →Variables: Text delimited a project’s variables can be
exported into a ASCII file in text delimited format (refer to Importing Variables in
"Text Delimited" Format, page 717 and Importing structured variables, page 720).
The ASCII file can be re-imported into a Concept project with the help of the
importing text delimited (refer to Importing Variables in "Text Delimited" Format,
page 717).
Exporting variables for Factory Link
Using File →Export →Variables: Factory Link a project’s variable declarations
can be exported into a ASCII file in "Factory Link" format.
If your Factory Link version of Concept is not supported, please call our hotline.
The ASCII file can be re-imported into a Concept project with the help of Factory Link
import (see page 724).
Exporting variables for Modlink
Using File →Export →Variables: Modlink a Modlink configuration file can be
generated, which can be used directly in Modlink.
The Modlink configuration file contains all those Located variables, which are
selected to be exported in the Variable Editor.
If no Located variables are selected to be exported, an error message appears and
a configuration file will not be generated.
Related information about Modlink is found in Modicon ModLink, User Guide.
Exporting Derived Data Types
In the data type editor, using Process →Save as text file... definitions of Derived
Data Types can be exported to a ASCII file.
33002204 12/2010
697
Import/Export
21.4
Section import
Overview
This section describes the import of sections.
What's in this Section?
This section contains the following topics:
Topic
698
Page
Importing Sections
699
Procedure for importing sections
703
Importing IL and ST Programs to FBD, SFC, IL or ST Sections (with
Conversion)
709
Importing (insert file) IL and ST programs into IL or ST sections
712
Procedure for "Copying" an IL section from an existing project into a new
project.
713
Procedure for converting FBD sections from an existing project into IL sections
of a new project.
714
33002204 12/2010
Import/Export
Importing Sections
Introduction
In Concept, the possibility exists to export individual sections selectively from a
source project or source DFB, and if desired, to then import them immediately into
the current target project or DFB:
z Section export from source project, followed by section import into the target
project
This transfers section information, including transition sections at SFC, all used
global and local DFBs used, as well as all the variable declarations used.
Data types defined in data type files are not transferred, (refer to notes).
z Section export from source DFB, followed by section import into the target DFB
This transfers section information, all global and local DFBs used as well as all
declarations of variables, inputs and outputs used.
Data types defined in data type files are not transferred, (refer to notes).
z Section export from source project, followed by section import into the target DFB
This transfers section information, all global and local DFBs used as well as all
used declarations of unlocated variables.
Direct address and Located variable declarations must be deleted before export,
since they are not authorized in a DFB. Data types defined in data type files are
not transferred, (refer to notes).
z Section export from source DFB, followed by section import into the target project
This transfers section information, all global and local DFBs used as well as all
declarations of variables used.
Declarations of inputs/outputs in this DFB must be deleted before export, since
they are not authorized in a Concept project. Data types defined in data type files
are not transferred, (refer to notes).
Notes
Attention should be paid to the following notes:
The imported sections will be inserted at the end of existing sections.
z The PLC configuration is not automatically imported. Instead, it must be imported
explicitly (refer to Import/Export of PLC Configuration using Concept, page 727.
z If projects with different local data structures are being imported (different DTY
files in the local DFB directories), they must be brought together in an individual
DTY file before import. This common file must then be saved in the local DFB
directories for source and target projects. Afterwards, open these files to make
them known to the individual projects.
z Ensure during import of IL and ST sections that the settings for nested comments
(Options →Preferences →IEC extensions →Nested comments
authorised) are identical in the source and target projects.
z
33002204 12/2010
699
Import/Export
Checking the Sections to be Imported
Before the import actually takes place, a check of the following takes place:
identical project environment (DFBs, EFBs, definition of Derived Data Types)
z existing sections
z existing SFC sections (not authorized in Concept DFB)
z existing step names
z Declarations of inputs/outputs (not authorized in Concept projects)
z Declarations of direct addresses (not authorized in Concept DFB)
z
If an error is identified, the import is canceled.
Errors that occur subsequently are "irreparable" and will cause the project to close
(i.e. all changes made since the last save are lost). Possible errors are:
z Name collisions between variables with different data types
z Name collisions between item names
z other errors
Name collisions between variables with different initial values or direct addresses
(located variable) cause a warning. The value of the target project is retained.
Automatic adjustment of standard preset names
An automatic adjustment of standard preset names occurs in the case of:
Standard generated names, such as SFC step names (S_x_y) and transition
section names (TransSection_x_y)
z Standard generated item names (FBI_x_y)
z Position of new DFB inputs/outputs (only with import into Concept DFB)
z
Specific Changes
During import there are also the following possibilities for performing specific
changes, in order to adjust the sections that are to be imported specifically to the
target project / target DFB.
z Replacing names (variable names, section names, item names, names in text
languages, comments, etc)
z Address offset for located variables and direct addresses in graphic languages
(e.g. %3:10 -> %3:20) and text languages (%QW10 -> %QW20)
The following points are excluded from the replace function:
z DFB names
z Index of ARRAYs (e.g. a[1])
z Elements from multi-element variables (e.g. a.dummy)
z In the case of EFBs, the replace function is only used for non-automatically
generated names (i.e. Instance names)
700
33002204 12/2010
Import/Export
Syntax for replacing names and address offset (address shift)
The following syntax applies when replacing names:
z Only entire names will be searched. If parts of names are to be replaced,
wildcards must be used.
z The "?" character is permitted as a wildcard. It is used to represent one character
exactly. If more than one character is to be ignored, a corresponding number of
"?" must be used. The "?" character is only permitted at the start of the name.
z The "*" character is permitted as a wildcard. It is used to represent any number
of characters. The "*"character is only permitted in the character string that is to
be searched for.
z Wildcards are only permitted in the search character string.
z There are no case distinctions.
z The section name, which is to be used as a replacement, must conform to IEC
name conventions, otherwise an error message occurs.
z In accordance with IEC1131-3, only letters are permitted as the first character of
item names. Should figures be required as the first character, however, the menu
command Options →Preferences →IEC extensions... →Allow leading digits
in identifiers.
z The specified value for the address offset is added to the corresponding address
zone for located variables and direct addresses.
z The offset value is given in decimal format by default. If it is given in hexadecimal
format, this can be marked as such with the prefix "16#" in front of the actual
offset value (e.g. 16#100).
NOTE: Replacing names has an effect on all variables, instance names and
comments. Using wildcards runs the risk of replacing names that also happen
incidentally to contain the same character string that is being searched. This would
normally lead to a cancellation.
Examples of search and replace:
33002204 12/2010
Replaces:
By:
available names
Result
Name1
Name2
Name1
Name1A
NameA
NameB
Name2
Name1A
NameA
NameB
???123
456
abc123
cde123
abcd123
abc1234
abc456
cde456
abcd123
abc1234
Name1*
Name2
Name1A
XName1B
NameAB
Name2A
XName1B
NameAB
701
Import/Export
Replaces:
By:
available names
Result
*123
456
abc123
cde123
abcde123
abd123a
abc456
cde456
abcde456
abd123a
*123*
456
abc123abc
cde123defghi
abcde123def
abc456abc
cde456defghi
abcde456def
???123*
456
abc123abc
cde123defghi
abcde123def
abc456abc
cde456defghi
abcde123def
Syntax for Creating the Replace List with an External Editor
When creating the replace list using an external editor, the following syntax should
also be noted:
z The replace-by string (previous name-new name) must be separated by a
comma (e.g. name1,name2).
z The replace list is processed line by line. Individual replace instructions must be
separated by a line break.
z The instructions for the address offset have the following structure:
z to add an address offset:
<reg0>,www
<reg1>,xxx
<reg3>,yyy
<reg4>,zzz
z to subtract an address offset:
<reg0>,-www
<reg1>,-xxx
<reg3>,-yyy
<reg4>,-zzz
z Likewise, the value can be given in hexadecimal form, e.g.:
<reg1>,16#xxx
702
33002204 12/2010
Import/Export
Procedure for importing sections
At a Glance
In principle, sections must firstly be exported from the source project /DFB into an
export file (*.sec) and then be imported by the target project/DFB. Exporting and
importing from project to project or from DFB to DFB can take place in shared or in
separate sessions. Exporting and importing from projects into DFBs or from DFBs
into projects must take place in separate sessions.
Section export and section import
To section export a source project and then section import into a target project, the
following procedure should be performed:
Step
33002204 12/2010
Action
1
Open the target project in Concept.
2
Call File →Export →Program: section(s).
3
In the window Open file select the source project, e.g.
C:\SOURCE_DIR\SOURCE.PRJ
4
Select the sections to be exported from the source project.
5
In Save section export under , specify the name of the export file (*.SEC), e.g.
C:\TARGET_DIR\TARGET.SEC
Reaction: The sections are exported and saved in the *.SEC file, e.g. in
TARGET.SEC.
The question Import section into project now ? follows
6
If the question as to whether the sections should be imported is answered with
OK , the import will be performed now.
Answer Cancel, if you want to start the mport later, see also procedure
Resuming following canceled import (see page 708).
7
Answer the question as to whether the project should be saved first with OK.
Note: The query Save project first ? should be answered with OK , because,
in the event of an import error, the current project is closed and all changes since
the last save are rejected.
8
If it is required or necessary, it is possible in the table Replace , to make
replacements for item names of variables, sections etc., as well as to define
address offsets for located variables and direct addresses (refer to Specific
Changes, page 700).
703
Import/Export
Step
Action
9
Select OK to continue (the whole import process is canceled if Cancel is
selected).
Reaction: Sections, used DFBs, used derived data types and the declarations
for used variables, including comments, are imported into the target project.
The import is canceled and the current project closed, if
z the sections to be imported contain DFBs that are not available in the target
project.
z the sections to be imported contain DFBs whose versions differ from already
available DFBs. (The imported DFB version can be accepted or rejected.)
z other errors arise during import.
10
If the import had been canceled, eliminate the cause of the cancelation and carry
out the Resuming after import cancelation (see page 708)procedure.
Errors are displayed in the messages window and have to be acknowledged.
DFB export and DFB import
To section export a source DFB and to then section import into a target DFB, carry
out the following procedure:
Step
704
Action
1
Open the target DFB in Concept DFB.
2
Call File →Export →Program: section(s).
3
In the window Open file select the source DFB, e.g.
C:\SOURCE_DIR\SOURCE.DFB
4
Select the sections to export from the source DFB.
5
In Save section export under specify the name of the export file (*.SEC), e.g.
C:\TARGET_DIR\DFB\TARGET.SEC
Reaction: The sections are exported and saved in the *.SEC file, e.g. in
TARGET.SEC.
The question Import section into project now? is now displayed.
6
If this question is answered with OK, the import is performed now.
If the answer given is Cancel, the import is started later, refer to Resuming after
import break (see page 708)procedure.
7
Respond to the question as to whether the project should first be saved with OK.
Note: The query Save project first ? should be answered with OK , because,
in the event of an import error, the current project is closed and all changes since
the last save are rejected.
8
If required or necessary, it is possible in the table Replace, to replace item
names of variables, sections etc., as well as to define address offsets for located
variables and direct addresses (refer to Specific Changes, page 700).
33002204 12/2010
Import/Export
Step
Action
9
Select OK to continue (the whole import process is canceled if Cancel is
selected).
Reaction: Sections, used DFBs, used derived data types and the declarations
for used variables, outputs and inputs are imported into the target project.
The import is canceled and the current DFB closed, if
z the sections to be imported contain DFBs that are not available in the target
DFB.
z the sections to be imported contain DFBs whose versions differ from already
available DFBs. (The imported DFB version can be transferred or rejected.)
z other errors arise during import.
10
If the import had been canceled, eliminate the cause of the cancel and carry out
the Resuming after import cancelation (see page 708)procedure.
Errors are displayed in the messages window and have to be acknowledged.
Section export and DFB import
To section export a source project and to then section import into a target DFB, carry
out the following procedure:
Step
33002204 12/2010
Action
1
In Concept, delete all declarations of direct addresses and located variables in
the sections to be exported. (They are not authorized in a DFB.)
2
Open the source project in Concept.
3
Call File →Export →Program: section(s).
4
In the window Open file select the source project, e.g.
C:\SOURCE_DIR\SOURCE.DFB
5
Select the sections to be exported from the source project.
6
In Save section export under specify the name of the export file (*.SEC), e.g.
C:\TARGET_DIR\TARGET.SEC
Reaction: The sections are exported and saved in the file *.SEC, e.g. in
TARGET.SEC.
The question Import section into project now? is now displayed.
7
Answer the question as to whether the sections should be imported with Cancel.
8
Close Concept.
9
Open Concept DFB and the target DFB.
10
Execute the menu command File →Import →Program: section(s).
11
Select the export file (e.g. TARGET.SEC)
12
Respond to the question as to whether the project should firstly be saved with
OK.
Note: The question Save project first ? should be answered with OK, because
in the event of an import error, the current project is closed and all changes made
since the last save are rejected.
705
Import/Export
Step
Action
13
If required or necessary, in the table Replace, it is possible to replace item
names of variables, sections etc., as well as to define address offsets for located
variables and direct addresses (refer to Specific Changes, page 700).
14
Select OK to continue (the whole import process is canceled if Cancel is
selected).
Reaction: Sections, DFBs used, derived data types used and the declarations
of used variables, inputs and outputs are imported into the target DFB.
The import is canceled and the current DFB closed, if
z the sections to be imported contain DFBs that are not available in the target
DFB.
z the sections to be imported contain DFBs whose versions differ from those of
DFBs already available. (The imported DFB version can be transferred or
rejected).
z other errors arise during import.
Errors are displayed in the messages window and have to be acknowledged.
15
If the import had been canceled, eliminate the cause of the cancel and carry out
the Resuming after import cancelation (see page 708)procedure.
DFB export and section import
To section export a source DFB and to then section import into a target project, carry
out the following procedure:
Step
706
Action
1
Delete the input/output declarations in the DFB to be exported before exporting
into Concept DFB, as these are not authorized in Concept projects.)
2
Open the source DFB in Concept DFB.
3
Call File →Export →Program: section(s).
4
In the window Open file select the source DFB, e.g.
C:\SOURCE_DIR\DFB\SOURCE.DFB
5
Select the sections to export from the source DFB.
6
In Save section export under specify the name of the export file (*.SEC), e.g.
C:\TARGET_DIR\TARGET.SEC
Reaction: The sections are exported and saved in the file *.SEC, e.g. in
TARGET.SEC.
The question Import section into project now? is now displayed.
7
Respond to the question as to whether the sections should be imported with
Cancel.
8
Close Concept DFB.
9
Open Concept and the target project.
10
Execute the menu command File →Import →Program: section(s).
11
Select the export file (e.g. TARGET.SEC).
33002204 12/2010
Import/Export
Step
Action
12
Respond to the question as to whether the project should firstly be saved with
OK.
Note: The question Save project first ? should be answered with OK, because
in the event of an import error, the current project is closed and all changes made
since the last save are rejected.
13
If required or necessary, it is possible in the table Replace, to replace item
names of variables, sections etc., as well as to define address offsets for located
variables and direct addresses (refer to Specific Changes, page 700).
14
Select OK to continue (the entire import process is canceled if Cancel is
selected).
Reaction: Sections, DFBs used, derived data types used and the declarations
of variables used, incl. comments, are imported into the target project.
The import is canceled and the current project closed, if
z the sections to be imported contain DFBs that are not available in the target
project.
z the sections to be imported contain DFBs whose versions differ from those of
DFBs already available. (The imported DFB version can be transferred or
rejected.)
z other errors arise during import.
Errors are displayed in the messages window and have to be acknowledged.
15
33002204 12/2010
If the import had been canceled, eliminate the cause of the cancel and carry out
the Resuming after import cancelation (see page 708)procedure.
707
Import/Export
Resuming after import cancelation
To resume after an import cancelation, carry out the following procedure:
Step
Action
1
Open the target project/target DFB again.
2
Execute the menu command File →Import →Program: section(s).
3
Select the export file (e.g. TARGET.SEC).
4
Answer the question Back up project?: with Yes.
Note: The question Back up project? should be answered with Yes, because
in the event of an import error, the current project is closed and all changes made
since the last save are rejected.
5
If required or necessary, it is possible in the table Replace, to replace item
names of variables, sections etc., as well as to define address offsets for located
variables and direct addresses (refer to Specific Changes, page 700).
6
Select OK to continue (the whole import process is canceled if Cancel is
selected).
Reaction: Sections, DFBs used, derived data types used and the declarations
of variables used, incl. comments, are imported into the target project.
The import is canceled and the current project closed, if
z the sections to be imported contain DFBs that are not available in the target
project/target DFB.
z the sections to be imported contain DFBs whose versions differ from those of
DFBs already available. (The imported DFB version can be transferred or
rejected.)
z other errors arise during import.
Errors are displayed in the messages window and have to be acknowledged.
708
33002204 12/2010
Import/Export
Importing IL and ST Programs to FBD, SFC, IL or ST Sections (with Conversion)
Introduction
Using File →Import →Program: IEC text ASCII files with IL or ST programs can
be imported to FBD, SFC, IL or ST sections. ST and IL are able to have SFC
elements (when imported into SFC section). Both text languages must adhere to the
grammar of IEC text languages, shown in IEC 1131-3 and in the process tables 52
56 of IEC 1131-3.
Import units
The minimum import unit is a program organization unit (POU) to IEC (PROGRAM
END_PROGRAM; FUNCTION_BLOCK ... END_FUNCTION_BLOCK).
The ASCII file can contain several POUs in Concept. From one POU, one or more
sections bearing the same name as the POU arise, which is provided with a current
number. A new section will be begun if too little graphic space is available to store
the logic. FUNCTION_BLOCK ... END_FUNCTION_BLOCK-POUs are imported as
DFBs.
In Concept DFB, the ASCII file can only contain a single POU. From this POU
(FUNCTION_BLOCK END_FUNCTION_BLOCK) one section arises.
Inserting POUs:
Type of POU
Import into open project
Import into open DFB
PROGRAM ... END_PROGRAM
as a section into the current not possible
project.
FUNCTION_BLOCK
...END_FUNCTION_BLOCK
as a section into the
as project DFB.
More than one POU can be current DFB. Only one
imported at the same time. POU can be imported.
FUNCTION ... END_FUNCTION
is changed as DFB. The
function name becomes
the DFB output
is changed as DFB. The
function name becomes
the DFB output.
Behavior in the Event of Error
In this case, sections are only stored if the ST/IL text is syntactically perfect. POUs
that cannot be reproduced are ignored completely, and an error message is
displayed in the message window.
NOTE: If the file to be imported contains more than 200 declarations (declarations
of variables and FFBs, a program error is caused. If this is the case, the declarations
should be divided amongst several VAR...END_VAR blocks.
33002204 12/2010
709
Import/Export
Variables
The variables declared in POUs appear after the import in the Variable Editor
(exceptions: SFCSTEP_STATE and SECT_CTRL type variables).
EFBs with extended parameter set
EFBs with extended parameter set (PRE_DIA, GRP_DIA, LOOKUP_TABLE, ..) are
only supported up to the predefined number of inputs/outputs.
"Bracket function" with extended number of inputs
If calls from a "bracket function" with extended number of inputs, such as
MUX_INT() are imported then all instances of this function work with the maximum
number of inputs that occur.
Changing from IL/ST to FBD
The following restrictions occur when changing to FBD:
The following restrictions occur when changing to FBD:
z Block items can only be called once
z only assignments and block calls
but none:
z RET (table 52, property 20)
z ELSIF (table 56, property 4)
z ELSIF (table 56, property 4)
z CASE (table 56, property 5)
z FOR (table 56, property 6)
z REPEAT (table 56, property 8)
z EXIT (table 56, property 9)
z
z
IF not nesting (IEC 1131-3 table 56, property 4)
Changing from IL/ST to SFC
The following limitations should be noted when making a SFC import from a text file:
Only variables are permitted as actions. Direct addresses cannot be imported.
z Only literals are allowed as time variables for identifiers.
z Transition section names are changed to standard names.
z Step monitoring times and step delay times are lost when importing.
z
The following additional restrictions occur when changing to SFC (table = IEC 11313-table):
z Transitions conditions are stored in special FBD sections (TC_secname) (table
41, property 7a ,7c, 7d). The textual import of transition conditions is not possible.
z Actions are converted into FBD sections and not linked to steps.
z no identifier SD and SL (table 45, property 8, 10), they are imported as MOVE.
710
33002204 12/2010
Import/Export
z
z
Structure components and directly addressed variables are allowed as SFC
actions. This can be seen as an extension of the IEC 1131-3 standard. ST and IL
exports support neither.
Using step variables ’step.X’ , ’step.T’ cannot be imported or exported and must
be generated again.
Changing from IL/ST to ST or IL
The following restrictions apply when changing to ST or IL, that were not created in
Concept.
z FB, DFB and direct address declarations occur at the start of the section
(VAREND_VAR)
z the source formatting (indents, comments etc) applied only to the "logic part" of
the sections, i.e. no comments for declarations (VAREND_VAR), for example
z Function Block counters must be made consistent, e.g. CTU must be changed to
CTU_INT
z no Keywords
z TYPE_...END_TYP
z VAR_INPUT...END_VAR
z VAR_OUTPUT...END_VAR
z VAR_IN_OUT...END_VAR
z VAR_EXTERNAL...END_VAR
z FUNCTION...END_FUNCTION
z FUNCTION_BLOCK...END_FUNCTIONBLOCK
z PROGRAM...END_PROGRAM
z STEP...END_STEP
z TRANSITION...END_TRANSITION
z ACTION...END_ACTION
z
z
no RETURN instruction (ST Editor)
no RET instruction (IL Editor)
Changing to Variable Declarations
When importing variable declarations the following restrictions occur:
No comments are imported.
z VAR_CONSTANT is imported as located variable.
(VAR_CONSTANT
i : INT := 10;
END_VAR
becomes located variable "I" with the initial value of "10")
z VAR_INPUT and VAR_OUTPUT definitions are imported into the programs as
located variables (VAR).
z VAR_INPUT and VAR_OUTPUT definitions are imported into DFBs as
input/output variables (VAR_INPUT, VAR_OUTPUT).
z
33002204 12/2010
711
Import/Export
Importing (insert file) IL and ST programs into IL or ST sections
At a Glance
Using Edit →Insert text file... it is possible to import ASCII files with IL or ST
programs to IL or ST sections.
This import function is a pure text import function, which can also be performed via
the clipboard (cut/copy/paste). Data conversion does not take place. For this
reason, the necessary variable declarations for example (also if these are contained
in the ASCII file) are not automatically integrated into the Variable Editor. The
necessary variable declarations must be imported explicitly via File →Import from
a "variables file", or be newly created. If variable declarations are contained in the
section, they must be deleted, since they generate errors in the code generation of
the section. Apart from this, all information for the POU must be deleted from the
program (e.g. from the export of a graphic section using File →Export →Program:
IEC text).
Restrictions
When importing IL and ST programs the following restrictions occur:
no keywords
z TYPE_...END_TYP
z VAR_INPUT...END_VAR
z VAR_OUTPUT...END_VAR
z VAR_IN_OUT...END_VAR
z VAR_EXTERNAL...END_VAR
z FUNCTION...END_FUNCTION
z FUNCTION_BLOCK...END_FUNCTIONBLOCK
z PROGRAM...END_PROGRAM
z STEP...END_STEP
z TRANSITION...END_TRANSITION
z ACTION...END_ACTION
z
z
VAR...END_VAR
z only for Function Block declarations and DFBs
z only at the start of the section for all Function Blocks and DFBs in the section
z not for variable declarations
z apart from this, for making direct addresses consistent: VAR %Q10:INT;
END_VAR
z
no RETURN instruction (ST Editor)
no RET instruction (IL Editor)
z
712
33002204 12/2010
Import/Export
Procedure for "Copying" an IL section from an existing project into a new
project.
Procedure
To "copy" an IL section from an existing project into an IL section of a new project,
perform the following steps:
Step
33002204 12/2010
Action
1
Open the IL section to be exported.
2
Using Edit →Save as text file... from the menu.
3
Select a directory for the export file and give it a name. Confirm with OK.
Reaction: The IL section contents are copied into a new ASCII file.
4
Execute the menu command File →Export →Variables: Text delimited.
5
Select the filter settings Export variables and Export constants. Select comma
as the text delimiter. Confirm with OK.
6
Select a directory for the export file and give it a name. Confirm with OK.
Reaction: The variable declarations of your project are exported to an ASCII file.
7
Using File →New project generate a new project.
8
Using Project →Configuration open the configurator.
9
Using Configure →PLC type select a PLC. Confirm with OK.
10
Using File →New section generate an IL section.
11
Using Edit →Insert text file... import the IL file.
12
Using File →Import →Variables: Text delimited(Warning: Text delimiter
must again be comma), import the variables file into the project’s Variable Editor.
13
Check the import process using Project →Analyze section.
Reaction: The import process is now completed and the new project can be
edited in the normal way (Create further sections, complete the configuration
etc.)
713
Import/Export
Procedure for converting FBD sections from an existing project into IL sections
of a new project.
Procedure
The process of converting FBD sections from an existing project into IL sections in
a new project consists of three main steps:
Step
Action
1
Exporting FBD section (see page 714).
2
Importing FBD section into an IL section (see page 714).
3
Correcting the syntax (see page 715).
Exporting FBD section.
The procedure for exporting the FBD section is as follows:
Step
Action
1
Open the existing project.
2
Export the desired FBD section using File →Export... →Program: IEC text.
3
Select a directory for the export file and give it a name. Confirm with OK.
Reaction: The FBD section is exported into an ASCII file.
4
Execute the menu command File →Export →Variables: Text delimited.
5
Select the filter settings Export variables and Export constants. Select comma
as the text delimiter. Confirm with OK.
6
Select a directory for the export file and give it a name. Confirm with OK.
Reaction: The variable declarations are exported to an ASCII file.
Importing FBD section into an IL section
The procedure for importing the FBD section into an IL section is as follows:
Step
714
Action
1
Using File →New project generate a new project.
2
Using Project →Configuration open the configurator.
3
Using Configure →PLC type select a PLC. Confirm with OK.
4
Using File →New section generate an IL section.
5
Using Edit →Insert text file... import the IL file.
6
Using File →Import →Variables: Text delimited(Warning: Text delimiter
must again be comma), import the variables file into the project’s Variable Editor.
Reaction: The FBD section (in IL format) and the variable declarations were
imported.
33002204 12/2010
Import/Export
Correcting the syntax
The procedure for correcting the syntax is as follows:
Step
33002204 12/2010
Action
1
Delete the line PROGRAM. (It contains the name of the old project.)
2
Delete any lines between VAR and END_VAR which do not contain Function
Block or DFB declarations (e.g. variable declarations).
3
Delete all lines from INITIAL_STEP to END_STEP. (They contain the sections
processing sequence of the old project.)
4
Change the ACTION lines to comment lines, e.g. (* ACTION xxx *). (They
contain the names of the FBD sections.)
5
Delete the END_ACTION line.
6
Delete the END_PROGRAM line.
7
Verify the import process using Project →Analyze section and correct any
errors.
Reaction: The import process is now completed and the new project can be
edited in the normal way (Create further sections, complete the configuration
etc.)
715
Import/Export
21.5
Variables import
Overview
This section describes the importing of variables.
What's in this Section?
This section contains the following topics:
Topic
716
Page
Importing Variables in "Text Delimited" Format
717
Importing structured variables
720
Importing variables in Factory Link format
724
Multiple Address Assignment after Variable Import
725
33002204 12/2010
Import/Export
Importing Variables in "Text Delimited" Format
Introduction
Using File →Import →Variables: Text Delimited, the variable declarations can
be imported from an ASCII file into the variable editor in text delimited format.
Importing Initial Values
Initial values of variables in derived data types cannot be imported with this import
format. If you wish to import initial values of variables in derived data types, select
the IEC text import export/import format.
General Format Description
An ASCII file in "text delimited" format must conform to the following conditions:
z The character set used conforms to ANSI (Windows).
z The parameters of a variable are executed within one line.
z The individual parameters are separated from one another by a user-defined
character.
z Leading and following spaces are allowed in any field (Exception: if a space has
been used as a separator), the import function deletes the latter (with the
exception of the comment field).
z The selected separator must not be contained in the individual parameters.
z Concept is not case-sensitive, in accordance with IEC name conventions. This
should be adhered to for variable names.
z Overlapping between pre-existing addresses and addresses to be imported can
be prevented in the following way: in the Options →Preferences →Analysis...
→Analysis Preferences dialog, activate the Treat Overlap of Addresses as
an Error option.
Order of Parameters within a Line
Order of Parameters within a Line:
Variable flag
z Variable name (symbolic name)
z Data type
z Hardware address
z Initial value
z Comment
z
33002204 12/2010
717
Import/Export
Meaning of Variable Flags
Possible values for the variable flags are:
0 or N= the symbolic name refers to a non-exportable variable
z 1 or E= the symbolic name refers to an exportable variable
z 2 or C= the symbolic name refers to a constant
z 3 or I = the symbolic name refers to an Input (see page 487) (Concept DFB only)
z 4 or O = the symbolic name refers to an Output (see page 487) (Concept DFB
only)
z 5 or M = the symbolic name refers to a VARINOUT variable (see page 489)
(Concept DFB only)
z S = Structured variable, see Importing structured variables, page 720.
z
Only variables with the 0/N or 1/E variable flag value are imported as located
variables. All others are imported as unlocated variables.
If the variable flag is set at 2/C, the hardware address is ignored.
The values 3/I and 4/O are only permitted in Concept DFB. In this case, the values
of the address fields are used for the position of the corresponding inputs and
outputs. The variable flag value 1/E is imported into Concept DFB as variable flag
value 0/N.
Structure of the Hardware Address Field
Structure of the Hardware Address Field (Example: %4:100):
Characters for direct addresses "%" (may be missing)
z Address type
z 0 = output, discrete
z 1 = input
z 3 = input word
z 4 = output word, discrete word
z
z
z
Separator ":" or ".".
If no separator is used, the address must be 6 characters long.
Address
Examples of an Address Description
Output register 123 :
z %400123 or
z %4.123 or
z %4:123 or
z 400123 or
z 4.123 or
z 4:123
718
33002204 12/2010
Import/Export
IEC Address Conventions
The IEC address conventions can also be used (e.g. %QX100 corresponds to
000100):
Address Type
Concept Designation
IEC Designation
Output, discrete
0x
%QX,%Q
Input
1x
%IX,%I
Input register
2x
%IW
Output register, discrete
register
3x
%QW
Empty Fields
Empty fields are represented by two consecutive separators.
The following fields are allowed to be empty:
z Hardware address
z Initial value
z Comment
Missing Fields
The following fields are allowed to be missing:
Comment
z Comment and initial value
z Comment and initial value and hardware address
z
33002204 12/2010
719
Import/Export
Importing structured variables
At a Glance
The basic structure of the file corresponds to that of the variables in text delimited
(see page 717) format.
Additional usage designations
In addition, the following points should be taken into account:
Multiple rows are necessary to describe a variable.
z Each of these rows must correspond to the format of variables in delimited text
format.
z A structured variable with initial values is described by an introducing row with the
following structure:
a. Variable flag
b. Variable name (symbolic name)
c. Name of derived data type
d. Hardware address
e. Empty field
f. Comment
z
z
This introductory line is followed by at least one component description. This
component description results from the description of the element components (
element data type) in the form of a row with the following structure (a component
does not have to be described if its initial value is the same as the standard
value). The sequence in which the individual components are executed is
insignificant.
a. Character "S" (S stands for structured)
b. Path of components (the variable name does not have to be included)
c. Field for IEC data type (this field can remain empty)
d. Empty field
e. Initial value
f. Empty field
Component description error trapping
Component description error trapping
z If a variable component is described more than once, the last description is used.
z If the specified component is not contained in the currently described variable, the
component description is ignored and a warning is given.
z If the field for the components path is empty, the component description is
ignored and a warning is given.
z If the field for the IEC data type is not empty, the specified data type is checked.
If the specified data type and the data type of the component are not the same,
the component description is ignored and a warning is given.
720
33002204 12/2010
Import/Export
z
z
Entries in the address field are ignored.
Entries in the address field are ignored.
Example: Structured variables in "Text delimited" format
Structured data type definition ESI_IN:
ESI_In:
(* ESI
STRUCT
in:
esi:
dummy:
slot:
END_STRUCT;
- input data *)
ESI_InOut;
ESI_Status;
BYTE;
Exp_Status;
(* ESI input data *)
(* supplement to modulo 16 *)
ESI_InOut: (* ESI input / output data structure *)
STRUCT
tstat:
BYTE;
(* transfer status, handshake *)
blocks:
BYTE;
(* number of used blocks *)
res:
BYTE;
(* reserved *)
block:
ESI_BlockArr14;
(* data block *)
END_STRUCT;
ESI_BlockArr14: ARRAY[1..14] OF ESI_Block;
ESI_Block: (* datas of ESI *)
STRUCT
func:
BYTE;
(* function *)
mux:
WORD;
(* distribution *)
attr:
BYTE;
(* attribute *)
cause:
BYTE;
(* reason *)
station:
WORD;
(* station number *)
object:
WORD;
(* objekt number *)
data:
ByteArr9; (* data bytes *)
END_STRUCT;
ByteArr9:
33002204 12/2010
ARRAY [1..9] OF BYTE;
(* 9 bytes *)
721
Import/Export
ESI_Status: (* Status of ESI
STRUCT
wdog:
BYTE;
(*
stat1:
BYTE;
(*
stat2:
BYTE;
(*
stat3:
BYTE;
(*
slot:
WORD;
(*
user:
WORD;
(*
esitime:
DPM_Time; (*
END_STRUCT;
DPM_Time:
STRUCT
sync:
ms:
min:
hour:
*)
expert watchdog-counter *)
error status 1 *)
error status 2 *)
error status 3 *)
slot number *)
virtual slot number *)
time stamp *)
(* time stamp *)
day:
mon:
year:
END_STRUCT;
BOOL;
WORD;
BYTE;
BYTE;
BYTE;
BYTE;
BYTE;
(*
(*
(*
(*
(*
(*
(*
(*
sync clock *)
milli-seconds *)
minutes *)
hours; (hour AND 16#80) *)
= day light saving time *)
days of week *)
month *)
year *)
STRUCT
Exp_Status:
ErrFlag1:
ErrFlag2:
(* error status of transfer *)
BOOL;
(* TRUE: epxert not pluged *)
BOOL;
(* TRUE: Bit 7 of DPM *)
(* Identcode is set; *)
(* logical DMP-access-error *)
UserStatus: WORD;
(* status of expert *)
ErrNo:
WORD;
(* errornumber *)
END_STRUCT;
722
33002204 12/2010
Import/Export
Representation of variables "demo" of ESP_IN data type in delimited text
format:
1;demo;ESI_In;400002;;structured data type
S;in.tstat;BYTE;;16#0F;
S;in.blocks;BYTE;;16#0F;
S;in.res;BYTE;;16#0F;
S;in.block[1].func;BYTE;;16#0F;
S;in.block[1].mux;WORD;;16#000F;
S;in.block[1].attr;BYTE;;16#0F;
S;in.block[1].cause;BYTE;;16#0F;
S;in.block[1].station;WORD;;16#000F;
S;in.block[1].object;WORD;;16#000F;
S;in.block[1].data[1];BYTE;;16#0F;
S;in.block[1].data[5];BYTE;;16#0F;
S;in.block[3].func;BYTE;;16#0F;
S;in.block[3].mux;WORD;;16#000F;
S;in.block[3].func;BYTE;;16#0F;
S;in.block[3].cause;BYTE;;16#0F
S;in.block[3].station;WORD;;16#000F
S;in.block[3].object;WORD;;16#000F
S;in.block[3].data[1];BYTE;;16#0F
S;in.block[3].data[2];BYTE;;16#0F
S;esi.wdog;BYTE;;16#0F
S;esi.stat1;BYTE;;16#0F
S;esi.stat2;BYTE;;16#0F
S;esi.stat3;BYTE;;16#0F
S;esi.slot;WORD;;16#000F
S;esi.user;WORD;;16#000F
S;esi.esitime.sync;BOOL;;TRUE
S;esi.esitime.ms;WORD;;16#000F
S;esi.esitime.min;BYTE;;16#0F
S;esi.esitime.hour;BYTE;;16#0F
S;esi.esitime.day;BYTE;;16#0F
S;esi.esitime.mon;BYTE;;16#0F;
S;esi.esitime.year;BYTE;;16#0F;
S;dummy;BYTE;;16#0F;
S;slot.ErrFlag1;BOOL;;FALSE;
S;slot.ErrFlag2;BOOL;;FALSE;
S;slot.UserStatus;WORD;;16#000F;
S;slot.ErrNo;WORD;;16#000F;
33002204 12/2010
723
Import/Export
Importing variables in Factory Link format
Description
Using File →Import →Variables: Factory Link variable declarations in Factory Link
format can be imported. In addition, carry out a Factory Link export and specify the
Factory Link version when importing into Concept.
If your Factory Link version of Concept is not supported, please call our hotline.
NOTE: Factory Link is case-sensitive with variable names. Concept does not
differentiate in accordance with IEC naming conventions. This should be adhered to
during import
724
33002204 12/2010
Import/Export
Multiple Address Assignment after Variable Import
Description
Via a Variables Import the multiple assignment of a single address by different
variable names is possible. This situation occurs if prior to the import, a variable that
has already been used in Concept is renamed in the list to be imported. In order to
not have to also manually perform this renaming in Concept, after the import you can
open the dialog box Multiple Address Assignment and perform the renaming or
replacement of the variable names automatically in the entire project (e.g. in
Variable Editor, Sections).
NOTE: In large projects and a corresponding number of multiple assignments, the
updating of the variable names can take some time.
33002204 12/2010
725
Import/Export
21.6
Import/Export of PLC Configuration
Overview
This Section describes the import and export of the PLC configuration with Concept
or Concept Converter.
What's in this Section?
This section contains the following topics:
Topic
726
Page
Import/Export of PLC Configuration using Concept
727
Import/Export of PLC Configuration using Concept Converter
728
33002204 12/2010
Import/Export
Import/Export of PLC Configuration using Concept
Introduction
Using the Import/Export function a PLC configuration can be exported out of a
current (open) project and subsequently re-imported.
Config. Export and Config. Import
To export and subsequently import SPS configurations, proceed as follows:
Step
33002204 12/2010
Action
1
To export the PLC configuration from the current project, start Concept, open the
desired project and select File →Export →Configuration.
2
In the Folder field, select the target directory for the PLC configuration to be
exported.
3
In the File name field, enter a name for the Export file (NAME.CCF) and press
OK.
Response: The PLC configuration is stored in the selected directory as an ASCII
file.
4
To import a PLC configuration into a project, open the desired project.
5
In Concept select the File →Import →Configurationmenu command.
6
From the File type list select the Concept Configuration entry. (*.CCF).
7
In the Folder field, select the desired directory.
8
From the File name list select the PLC configuration to be imported
(NAME.CCF) and click on OK.
9
Warning: The current PLC configuration of the chosen project will be
overwritten.
Answer the question with OK.
Response: The PLC configuration is imported.
727
Import/Export
Import/Export of PLC Configuration using Concept Converter
Introduction
The Concept Converter’s import/export function enables you to export the
configuration from one project (Project A) and import it into another project (Project
B).
Config Export and Config Import
In order to export and then import a PLC configuration, carry out the following steps:
Step
728
Action
1
To export the PLC Configuration from project A, start the Concept Converter and
select File →Export →Configuration.
2
From the Folder field, select the Project A system directory.
3
Select the PLC configuration to be exported (PROJECTNAME.C1) and click on
OK.
Response: The PLC configuration is filed in the system directory in the form of
an ASCII file (PROJECTNAME.CON).
4
To import the PLC configuration into Project B, copy the exported file into the
system directory of Project B.
5
In Concept Converter select the File →Import menu command.
6
From the File Type list box select the Configuration (*.CON) entry.
7
From the Folder field, select the Project B system directory.
8
From the File Name list box, select the PLC configuration
(PROJEKTNAME.CON) to be imported and click on OK.
9
Caution: The current PLC configuration of the selected project will be
overwritten.
Answer the question with OK.
Response: The PLC configuration will be imported.
33002204 12/2010
Documentation and Archiving
33002204 12/2010
Documentation and Archiving
22
Overview
This chapter describes the documentation, the archiving and deleting of projects,
DFBs and macros.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
22.1
Documentation of projects, DFBs and macros
730
22.2
Managing projects, DFBs and macros
740
729
Documentation and Archiving
22.1
Documentation of projects, DFBs and macros
Overview
This section describes the documentation of projects, DFBs and macros.
What's in this Section?
This section contains the following topics:
Topic
730
Page
Documentation contents
731
Documentation Layout
732
Defining Page Breaks for Sections
735
Use of keywords
739
33002204 12/2010
Documentation and Archiving
Documentation contents
At a Glance
The contents of the documentation can range in length from one on-screen page to
the entire documentation of a project. The order in the first chapter is given as in the
dialog box File →Print →Documentation contents and cannot be changed.
Project documentation
The following chapter can be printed for project documentation using the menu
command File →Print:
z Project description
z Derived data types
z Using state RAM
z State RAM values
z Using the DFBs
z Using the EFBs
z PLC configuration
z I/O Map
z Execution sequence of the sections
z Project structure
z Messages
z ASCII messages only with Concept for Quantum
z Variable lists
z Use of variables
z Contents of sections
z Contents directory for the printed documentation
DFB/macro documentation
The following chapter can be printed for DFB/macro documentation using the menu
command File →Print :
z DFB/macro description
z Derived data types
z Using the DFBs
z Using the EFBs
z Execution sequence of the sections
z Messages
z Variable lists
z Use of variables
z Contents of the sections
z Contents directory for the printed documentation
33002204 12/2010
731
Documentation and Archiving
Documentation Layout
Print Format
The printout can be in either portrait or landscape mode. This is set up in the dialog
box File →Printer Setup →Select Printer.
Page Numbering
The pages are numbered linearly. The starting page number can be selected by the
user.
Page Size
The left margin is 12 characters wide. The area for text and graphics is
approximately 132 characters wide, the height depends on the header and footer
files. If the header and footer files are not activated or the keyword "%PAGENO" is
not contained in them, the page number will be printed automatically in the bottom
right corner of the page.
Page Breaks
If a graphics section does not fit on a printed page, the section will be divided - like
a map - in the printout. In this case page references are printed in all four corners of
the graphics area to show which page the graphics are continued on. The View →
Page Break menu option displays the page break corresponding to the printer set
in File →Printer Setup and to the enlargement factor in the editor window.
Also see the Defining Page Breaks for Sections, page 735 description.
Size and Fonts
In text sections the font size in the printout cannot be altered. Emphasis of keywords
is represented in the printout using bold and italic typefaces.
732
33002204 12/2010
Documentation and Archiving
Standard Layout
Standard Layout:
Header
It is possible to give your documentation a header. The header is stored as an ASCII
file and can be created using any ASCII editor. The maximum file size is 15 lines or
approx. 2 Kbytes.
A sample file called "HEADER.TXT" is available in the Concept directory. This file
can be modified as required. Keywords (see page 739) can also be used with it.
Footer
It is possible to give your documentation a footer. The footer is stored as an ASCII
file and can be created using any ASCII editor. The maximum file size is 15 lines or
approx. 2 Kbytes.
An sample file called "FOOTER.TXT" is available in the Concept directory. This file
can be modified as required. Keywords (see page 739) can also be used with it.
33002204 12/2010
733
Documentation and Archiving
Front Page
It is possible to give your documentation a front page. The front page is stored as an
ASCII file and can be created using any ASCII editor. The size of the file is unlimited.
An sample file called "FRONTPG.TXT" is available in the Concept directory. This file
can be modified as required. Keywords (see page 739) can also be used with it.
The printout of the front page also contains the header and footer if these are
switched on.
734
33002204 12/2010
Documentation and Archiving
Defining Page Breaks for Sections
Introduction
For printing graphics in FBD, LD and SFC sections, you can define the values for
the page break and paper orientation of the graphics. The higher the value you
select, the smaller the graphics will be displayed. But in return more space is
available on a page.
Settings
You can set the values for the page break for portrait and landscape. When
changing the paper format, the settings for the other format stay saved. Using the
Download standard values command button, the standard values from the
CONCEPT.INI file can be loaded.
When defining values for the width and height of the paper, you should make sure
that the different editors show different grid units.
The min. and max. values are:
Section
33002204 12/2010
1 grid unit equals the value
Paper Width
Paper Height
FBD
10
30 - 300
30 - 230
LD
8
30 - 400
10 - 230
SFC
1
4 - 32
4 - 60
735
Documentation and Archiving
Example for FBD section
Dialog setting
736
33002204 12/2010
Documentation and Archiving
Representation in the FBD editor window
1
2
3a
3b
33002204 12/2010
FBD section
Grid view (View -> Grid)
Page break, width: 75 (View -> Page break)
Page break, height: 100 (View -> Page break)
737
Documentation and Archiving
Print-out
738
33002204 12/2010
Documentation and Archiving
Use of keywords
At a Glance
Keywords allow project or object specific information to be inserted into the header,
footer and title page files.
Usable keywords
Table of usable keywords:
%PROJNAME
Project name
%SECTNAME
Section name
%VERSION
Program/DFB version
%CREDATE
Creation date
%MODDATE
Date of last project/DFB modification
%DATE_D
Current date (European format, DD.MM.YY)
%DATE_US
Current date (US format, DD.MM.YY)
%PAGENO
Current page numbers
%RECT(Column,Width,Height)
Draws a rectangle with its top left-hand
corner in the current line
%HLINE(Column,Length)
Draws a horizontal line in the current line
%VLINE(Column,Length)
Draws a vertical line starting in the current
line
NOTE: The total number of lines in the header, footer or title page file must agree
with the number of lines needed to print rectangles and vertical lines.
Example: Header with keywords
Contents of the ASCII file:
%RECT (1,132,4)
S A
CONCEPT
¶
%VLINE (24,4)
%VLINE (110,4)
Project comment
Name
%DATE_D
NOTE: The symbol ¶ is not entered, it should only show that the file ends with a
blank line.
Expression:
S A
CONCEPT
33002204 12/2010
Project comment
Name
01.04.99
739
Documentation and Archiving
22.2
Managing projects, DFBs and macros
Overview
This section describes the archiving and deletion of projects, DFBs and macros.
What's in this Section?
This section contains the following topics:
Topic
740
Page
Archiving projects, used DFBs, EFBs and data type files
741
Deleting projects, DFBs and macros
743
33002204 12/2010
Documentation and Archiving
Archiving projects, used DFBs, EFBs and data type files
Introduction
When archiving projects, used DFBs, EFBs and data type files, all data of the project
is collected and compressed. The *.PRZ file is created and put into the same
directory as the project itself. The file can be decompressed at any time thereafter.
NOTE: When archiving DFBs, their help files (*.DOC, *.PDF, *.TXT), which are
located in the Concept directory or the defined path (see CONCEPT.INI
(see page 1110)) are not considered. However, if you want to archive these help
files, you must copy these files into the local/global DFB-directory.
Archiving Projects
The procedure for archiving projects is as follows:
Step
Action
1
Start Concept.
Note: No project may be open during the archiving procedure, otherwise the
Archive...command cannot be selected.
2
To archive, select File →Archive....
Response: A window showing the Concept projects appears.
3
Select the project to be archived from the window and press OK.
Reaction 1: A check for whether a compressed *.PRZ file has the same name
is performed. If there is a file with the same name, you are requested to confirm
whether the existing file should be replaced by the new file.
Reaction 2: The project data is compressed and saved in the *.PRZ file and is
then found in the same directory as the project.
Unpacking Archived Projects
The procedure for unpacking archiving projects is as follows:
Step
33002204 12/2010
Action
1
Select File →Open.
Result: A window showing all Concept projects appears.
2
Go to the list field File Type and select option Archived Projects (*.prz).
Result: The archived Concept projects are displayed.
3
Select the project that you want to open and press OK.
Reaction 1: A check for whether a *.PRJ file has the same name is performed.
If there is a file with the same name, you are requested to confirm whether the
existing file should be replaced by the new file.
Reaction 2: A check for whether DFBs, EFB libraries and data type files with the
same name exist, is performed. If there is a file with the same name, you are
requested to confirm whether the existing file should be replaced by the new file.
Reaction 3: The Archive content dialog is opened.
741
Documentation and Archiving
Step
Action
4
Select Decompress.
Reaction 1: The project data is decompressed and stored as a normal Concept
project. The project is then found in the same directory as the archived file.
Reaction 2: The project is automatically opened in Concept.
5
Establish a connection between the PC and the PLC with Online →
Connection.
Result: The PC and PLC have the same status as before the archive procedure.
Archiving/unpacking global DFBs
When archiving or unpacking the used global DFBs, the following sequence should
be used:
Step
Action
1
The project directory is searched for an existing GLB directory.
2
The relevant settings are checked in the CONCEPT.INI file.
For example:
[Path]: GlobalDFBPath=x:\DFB
[Upload]: PreserveGlobalDFBs=0
In this example, the DFB directory of the path defined is searched for global
DFBs.
3
The DFB directory in x:\CONCEPT\DFB is searched.
The global DFBs from only one directory are used and/or are saved in only one
directory. i.e. if step 1 is unsuccessful, then step 2 follows, step 3 is only performed
if neither of the first two are successful.
Diagnostic Information
When downloading the project, diagnostic information is created and put into the
corresponding directory. Then, the status between PC and PLC becomes EQUAL.
When archiving the project, this diagnostic information is compressed with the other
project data and stored in a file.
To use the diagnostic information after it is decompressed, make sure that the status
between the PC and the PLC is EQUAL when archiving. Downloading is no longer
required and diagnostics can be run immediately.
If the status is anything else between the PC and the PLC, e.g. NOT EQUAL, then
this status will be displayed while decompressing and after the connection (Online
→Connect...). Downloading is therefore required to put the system into operation.
Downloading also creates new diagnostic information while the old information is
lost however.
742
33002204 12/2010
Documentation and Archiving
Deleting projects, DFBs and macros
Deleting projects, DFBs and macros
The procedure for deleting projects, DFBs and macros is as follows:
Step
33002204 12/2010
Action
1
Delete the project/DFB/macro directory (including the subdirectory "dfb").
If only certain DFBs/macros need to be deleted from this directory, open the
subdirectory and delete all files with the required DFB/macro name (name *).
2
Use global DFBs, and global macros in the project/DFB and if these also need
to be deleted, they must be deleted separately.
Open the subdirectory "dfb" of the Concept directory and delete all files carrying
the name DFBs/macros (name *).
743
Documentation and Archiving
744
33002204 12/2010
Simulating a PLC
33002204 12/2010
Simulating a PLC
23
Overview
This chapter describes how to simulate a PLC. By using a simulator the functions of
a program may be tested without the actual required hardware.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
23.1
Simulating a PLC (16-bit simulator)
746
23.2
Simulating a PLC (32-bit simulator)
748
745
Simulating a PLC
23.1
Simulating a PLC (16-bit simulator)
Simulating a Controller
Introduction
This section describes the 16-bit simulator Concept SIM.
Area of Application
Concept SIM may be used to simulate any PLC (Quantum, Compact, Momentum,
Atrium) in order to test the user program "online" without hardware.
The simulator is only available for the IEC languages (FBD, SFC, LD, IL and ST).
The 16-bit simulator Concept SIM is used for testing programs containing Concept
EFB generated 16-bit EFB.
NOTE: If your program does not contain 16-bit EFBs created with Concept EFB, you
should use the 32-bit simulator (PLCSIM) to simulate a PLC.
Max. Number of Variables
When using the 16 bit simulator Concept SIM, a specific number of state RAM
references (Project →PLC configuration →Configuring →Memory Partitions)
may not be exceeded.
The table below shows the maximum number of these state RAM references:
Reference type
max. number
0x
60000
1x
5008
3x
4000
4x
24000
Concept vs. Concept SIM
Concept SIM and Concept may only be opened independently, i.e. when starting
Concept SIM, Concept cannot be open. It is therefore advisable to decide before
starting Concept, whether the simulator or the controller should perform the test. In
each case, make sure that the simulator is turned on or off as required.
746
33002204 12/2010
Simulating a PLC
Activating Concept SIM
The procedure for activating Concept SIM is as follows:
Step
Action
1
Close Concept if it is open.
2
Open Concept-SIM by double-clicking on the Concept-SIM icon.
3
Click on the File main menu and activate the Simulation on menu command.
Response: The simulator is on.
4
Exit Concept SIM via the File main menu using the Exit menu command.
5
Start Concept.
6
From Online →Connect... open the Connect to PLC dialog window.
7
For Protocol type: always select Modbus Plus, even if your real PLC will be
coupled via a different bus at a later stage.
Response: The simulator will now be displayed as a PLC in the node list of the
Modbus Plus network.
8
Now create a link to the simulated PLC by double clicking on the list entry or via
OK.
Response: You may now test the behavior of your IEC user program.
Note
NOTE: Please note that the simulator remains active even after rebooting the PC.
To build a link to a PLC the simulator must be explicitly terminated.
Disabling Concept SIM
The procedure for disabling Concept SIM is as follows:
Step
33002204 12/2010
Action
1
Close Concept if it is open.
2
Open Concept-SIM by double-clicking on the Concept-SIM icon.
3
Click on the File main menu and select the Simulation Off menu command.
Response: The simulator is on.
4
Exit Concept SIM via the File main menu using the Exit menu command.
747
Simulating a PLC
23.2
Simulating a PLC (32-bit simulator)
Overview
This Section describes how to simulate a PLC with the 32-bit simulator Concept
PLCSIM32.
What's in this Section?
This section contains the following topics:
Topic
Concept-PLCSIM32
748
Page
749
Simulating a PLC
751
Simulating a TCP/IP interface card in Windows 98
753
Simulating a TCP/IP interface card in Windows NT
754
33002204 12/2010
Simulating a PLC
Concept-PLCSIM32
Introduction
The Concept-PLCSIM32 program simulates any PLC unit (Quantum, Compact,
Momentum, Atrium) and its signal states.
Area of Use
The simulator is presently only available for IEC languages (FBD, SFC, LD, IL and
ST).
NOTE: Not supported:
z
z
z
z
z
z
LL984 language
Loadables, e.g. ULEX
6x-Register (extended memory)
RIO
DIO
Backplane Expander
Note for Windows 98 and Windows NT
Since the simulator is connected to Concept via a TCP/IP link, you need a card in
your computer to handle the TCP/IP interface (when using Windows 98 or Windows
NT). If your computer is not equipped with such a card, it can be simulated. Follow
the procedure described in Simulation of a TCP/IP interface card in Windows 98
(see page 753) or Simulation of a TCP/IP interface card in Windows NT
(see page 754).
When using Windows 2000, simulating a TCP/IP interface card is not necessary
because all drivers needed for Concept PLCSIM32 are installed automatically.
33002204 12/2010
749
Simulating a PLC
Structure of the dialog box
The title bar shows the name of the application (PLC Sim32) and the address of your
PC-interface card.
The first text box in the simulator window shows the status of the simulated PLC.
This field is read-only. The displayed status is determined by Concept, as with a real
PLC.
The status may be shown as the following:
DIM (Dim Awareness)
The simulator is in an undefined state.
z STOPPED
The simulator (the simulated PLC) is stopped.
z RUNNING
The simulator (the simulated PLC) is running.
z
The type of PLC to be simulated can be selected from the first list box.
The following registers are available:
z State RAM
Provides an overview of the signal memory.
z I/O Modules
Shows the configuration currently loaded or the signal memory of a selected
group of components.
z Connections
Displays connections between the simulator and programming device(s).
750
33002204 12/2010
Simulating a PLC
Simulating a PLC
Overview
A controller is simulated with the PLCSIM32 simulator using 4 main steps:
Step
Action
1
Program creation and controller configuration.
2
Activating the simulator.
3
Construction of the connection between Concept and simulator.
4
Downloading the program.
Program creation and controller configuration
The following steps describe how to create programs and configure the controller.
Step
Action
1
Create your program and your controller configuration in Concept.
2
Save your project with File →Save.
Activating the simulator
The following steps describe how to activate the simulator:
Step
Action
1
Run PLCSIM32 simulator in the Concept program group.
2
Select the controller type appropriate to your project in the simulator.
Construction of the connection
The following steps describe how to construct the connection between Concept and
the simulator.
Step
33002204 12/2010
Action
1
Using Online →Connect... open the Connect to PLC dialog in Concept.
2
Select the IEC Simulator (32-Bit) entry in the Protocol Type list box.
3
In the Access range, activate the Change configuration option button.
4
Confirm with OK.
Response: A connection has been made between the programming unit and the
simulator. A note then appears, saying that the configurations of the
programming unit and the simulator are different.
751
Simulating a PLC
Downloading the program
The following steps describe how to download the program:
Step
752
Action
1
Using Online →Download open the Download Controller dialog.
2
Confirm with Download.
Response: Your program and your configuration are loaded into the simulator.
You will be asked if you wish to start the controller.
3
Confirm with Yes.
Response: You may now test the behavior of your IEC user program.
33002204 12/2010
Simulating a PLC
Simulating a TCP/IP interface card in Windows 98
Introduction
As the coupling between Concept and the simulator PLCSIM32 is made via a
TCP/IP coupling, a TCP/IP interface card is needed in the PC. If your PC does not
have one of these cards, it may be simulated.
CAUTION
Risk of PC problems
Do NOT complete this procedure if your PC already has a TCP/IP connection. The
software installation of the TCP/IP connection would be destroyed by this
procedure. Only carry out this procedure once, otherwise PC problems may arise.
Failure to follow these instructions can result in injury or equipment damage.
Simulating a TCP/IP Interface Card
Carry out the following steps to simulate a TCP/IP interface card in Windows 98:
Step
1
33002204 12/2010
Action
In Windows 98 invoke Start →Settings →Control Panel.
2
From Software open software settings.
3
From the Windows Setup register select the Links entry and click on the
Details... command button.
4
Check the DFU network entry here and confirm with OK. (To do this, you may
require the Windows system CD.)
Response: The computer reboots.
The DFU network and the TCP/IP protocol are available to the system after the
reboot. (Concept can only connect to the simulator.)
753
Simulating a PLC
Simulating a TCP/IP interface card in Windows NT
Introduction
As the coupling between Concept and the simulator PLCSIM32 is made via a
TCP/IP coupling, a TCP/IP interface card is needed in the PC. If your PC does not
have one of these cards, it may be simulated.
CAUTION
Risk of PC problems
Do NOT complete this procedure if your PC already has a TCP/IP connection. The
software installation of the TCP/IP connection would be destroyed by this
procedure. Only carry out this procedure once, otherwise PC problems may arise.
Failure to follow these instructions can result in injury or equipment damage.
Simulating a TCP/IP Interface Card
The main steps for simulating a TCP/IP interface card in Windows NT are as follows:
Step
1
Action
Setting the basic settings.
2
Installing a new modem.
3
Setting the workgroup.
Setting the Basic Settings
The procedure for setting the basic settings is as follows:
Step
754
Action
1
In Windows NT, invoke Start →Settings →Control Panel →Network and
answer Yes to the question.
Response: The Network Setup Wizard dialog is opened.
2
Deactivate the Wired to the network option.
3
Select the Remote access to the network option.
Response: The network card installation dialog will be opened.
4
Click on Next (without installing a network card).
Response: The dialog for selecting a network protocol will be opened.
5
Select the TCP/IP-Protocol option.
6
Deactivate all the other options and click on Next.
Response: The dialog for selecting services will be opened.
33002204 12/2010
Simulating a PLC
Step
Action
7
Click on Next (without making any changes in the dialog).
8
Answer the question with Next.
Response: The Windows NT Setup dialog is opened.
Installing a New Modem
The procedure for installing a new modem is as follows:
Step
33002204 12/2010
Action
1
Insert the Windows NT CD and specify the path for the installation data files (for
example D:\i386). Click on Resume.
Response: The TCP/IP Setup dialog is opened.
2
Click on No.
Response: The Remote Access Setup dialog is opened.
3
Click on Yes.
Response: The Install New Modem dialog is opened.
4
Select the Don’t detect my modem; I will select it from a list. option and press
Next.
Response: The dialog for selecting a modem is opened.
5
Select a standard modem (for example Standard 28800 bps modem) and press
Next.
Response: The dialog for selecting the connection is opened.
6
Select the Selected ports option and the COM interface. Click on Next.
Response: The Standard information dialog is opened.
7
Select your country.
8
Enter the code for your town (your area code) and click on Next.
Response: The Install New Modem dialog is opened.
9
Click on Finish.
Response: The Add Remote Access Setup device dialog is opened.
10
Click on OK.
Response: The Remote Access Setup dialog is opened.
11
Click on Next.
Response: The Network installation assistant dialog is opened.
12
Click on Next twice.
Response: The dialog for setting the workgroup is opened.
755
Simulating a PLC
Setting the Workgroup
The procedure for setting the workgroup is as follows:
Step
756
Action
1
Select the Workgroup option and enter the WORKGROUP name. Click on Next.
2
Click on Finish.
Response: The Network Settings Changes dialog is opened.
3
Click on Yes to restart.
Response: Your PC now simulates a TCP/IP network and the 32-bit simulator
PLCSIM may be used.
33002204 12/2010
Concept Security
33002204 12/2010
Concept Security
24
Overview
This chapter describes Concept Security.
What's in this Chapter?
This chapter contains the following topics:
Topic
33002204 12/2010
Page
General Description of Concept Security
758
Access Rights
760
Changing Passwords
767
Activating Access Rights
769
Protecting Projects/DFBs
770
757
Concept Security
General Description of Concept Security
At a Glance
You can define access rights (see page 760) (user definitions) using Concept
Security. The access rights limit the functionality of Concept and its utilities for
certain users.
NOTE: The Editor LL984 cannot be protected with Concept Security.
Projects/DFBs can be protected (see page 770) from being edited using Concept
Security.
Scope
The access rights defined for a user are valid for all projects within the Concept
installation. If a user edits projects in different Concept installations, he has to be
defined as a user in each Concept installation.
Max. number of users
A maximum of 128 users can be defined.
Activating Concept Security
After Concept is installed, Concept Security is inactive and must be activated by the
system administrator (Supervisor).
The system administrator
Access rights are defined and Concept Security is switched on/off by the system
administrator (user name: Supervisor).
When Concept is installed, a password file is automatically created for the
"Supervisor" (system administrator) with an empty password. This user has
"Supervisor" access rights.
Changing the access rights online
Concept Security and Concept/Concept-DFB can be started at the same time, i.e.
the access rights can be changed while Concept/Concept-DFB is running and
become active immediately.
758
33002204 12/2010
Concept Security
Creating a log
In Concept, if you go into the Options →Preferences →Common... →Common
Preferences dialog box in the Logging area and activate the File option (and enter
a path name), the log function is activated. A file with the name
YEARMONTHDAY.LOG (e.g. 19980926.LOG) is created in the folder you selected,
which contains a log of all system critical (runtime relevant) changes.
The following data (and other data) is logged in the ASCII file:
z Section name
z EFB/DFB instance name, FB type name
z Pin name
z [variable name] [literal] [address]
z Old value
z New value
z User name (if password protection is activated in Concept Security)
z Date and time (also see Options →Preferences →Common...)
The following logging can be carried out during log-on:
z Modification of the user rights
z Deleted user
z Aborted log-on
In Concept, you can view the current log using the menu command File →View
Logfile.
Encrypt Logfile
Logging write access on the PLC can be stored in an encrypted
YEARMONTHDAY.ENC file (e.g. 20021025.ENC). To do this, go to the Project
Properties (main menu Project) dialog box and activate the control box Secure
Application. In Concept, you can view the current log using the menu command
File →View Logfile. If the current log is encrypted, the content of the ENC file is
automatically opened in a view tool and can viewed or printed there. Supervisor
rights are required to do this.
33002204 12/2010
759
Concept Security
Access Rights
At a glance
The access rights are set up in a hierarchy; if the user has the rights for a certain
level, he also has the rights to all lower levels.
Access Right Levels
The following levels are defined (from lowest to highest):
760
Level
Access rights
Assigned Functionality
1
Read only
The user can view projects offline and online, but cannot
change them. The user can establish a connection
between the programming device and PLC and casn
view variables online.
2
Reset SFC
The same functionality as above and also: Animation
panel can be use for control (e.g. disable steps, disable
transitions, force steps, etc.).
3
Change data
The same functionality as above and also: The user can
change literals online.
4
Force data
The same functionality as above and also: Forcing
variables.
5
Download
The same functionality as above and also: The user can
download the program to the PLC.
Note: To download the configuration, you at least need
the access rights Change configuration.
6
Change program
The same functionality as above and also: The user can
make any changes to the program, but not to DFBs or
EFBs.
7
Change configuration
The same functionality as above and also: The user can
change the PLC configuration.
8
Tools
The same functionality as above and also: The user can
use Concept DFB, Concept EFB and Concept
Converter.
9
Supervisor
The same functionality as above and also: The user can
use Concept Security in Supervisor mode (set up users,
activate/deactivate Concept Security).
33002204 12/2010
Concept Security
Access Rights for the Main Menu File
The following table shows the minimum access rights required in Concept for the
menu commands in the main menu File:
33002204 12/2010
Menu commands in the main menu File
Minimum access rights needed
New Project
Change program
Open / Close
Read only
Open / Close
(replacing/deleting EFBs/DFBs; error
messages: FFB does not exist; FFB formula
parameter was changed, DFB was changed
internally)
Change program
Save project
Change data
Save project as....
Change data
Optimize project...
Change program
New section...
Change program
Open section...
Read only
Delete section...
Change program
Section properties... (read)
Read only
Section properties... (write)
Change program
Section Memory
Read only
Import...
Change program
Export...
Read only
Print...
Read only
Printer setup...
Read only
Exit
Read only
761
Concept Security
Access Rights for the Main Menu Edit
The following table shows the minimum access rights required in Concept for the
menu commands in the main menu Edit:
762
Menu commands in the main menu Edit
Minimum access rights needed
Undo: Delete
Change program
Cut
Change program
Copy
Read only
Insert
Change program
Delete
Change program
Select all
Read only
Deselect all
Read only
Goto line... (text languages)
Read only
Goto counterpart (text languages)
Read only
Expand statement (text languages)
Change program
Lookup variables (text languages)
Change program
Search... (text languages)
Read only
Find Next (text languages)
Read only
Replace... (text languages)
Change program
Insert text file... (text languages)
Change program
Save as text file... (text languages)
Read only
Open Column (LL984 Editor)
Read only
Open Row (LL984 Editor)
Read only
Close Column (LL984 Editor)
Read only
Close Row (LL984 Editor)
Read only
DX Zoom... (LL984 Editor)
Read only
Reference Zoom (LL984 Editor)
Read only
Offset References... (LL984 Editor)
Read only
Replace References (LL984 Editor)
Read only
33002204 12/2010
Concept Security
Access Rights for the Main Menu View
The following table shows the minimum access rights required in Concept for the
menu commands in the main menu View (only for FBD, LD and SFC):
Menu commands in the main menu View
Minimum access rights needed
Overview
Read only
Normal
Read only
Expanded
Read only
Zoom in
Read only
Zoom out
Read only
Grid
Read only
Page breaks
Read only
Access Rights for the Main Menu Objects
The following table shows the minimum access rights required in Concept for the
menu commands in the main menu Objects:
Menu commands in the main menu
Objects
Minimum access rights needed
Properties (read) (only for FBD, LD and SFC) Read only
Properties (write) (only for FBD, LD and SFC) Change program
33002204 12/2010
Select
Read only
Text
Change program
Replace variables...
Change program
Link
Change program
Vertical Link (LD Editor)
Change program
FFB: Last Type (FBD, LD Editor)
Change program
Invert input/output (FBD, LD Editor)
Change program
Insert Macro... (FBD Editor)
Change program
FFB selection... (FBD, LD Editor)
Change program
Replace FFBs... (FBD, LD Editor)
Change program
FFB Show execution order (FBD Editor)
Read only
Reverse FFB execution order (FBD Editor)
Change program
Insert contacts, coils (LD Editor)
Change program
Select column structure (SFC Editor)
Change program
Select row structure (SFC Editor)
Change program
Insert steps, transitions (SFC Editor)
Change program
763
Concept Security
Menu commands in the main menu
Objects
Minimum access rights needed
Insert FFB, Download, Save etc. (IL Editor)
Change program
Insert FFB, Assignment, Operators,
Declaration etc. (ST Editor)
Change program
Coils, Insert contacts (LL984 Editor)
Change program
Access Rights for the Main Menu Project
The following table shows the minimum access rights required in Concept for the
menu commands in the main menu Project:
Menu commands in the main menu Project Minimum access rights needed
764
Properties (write)
Change program
Memory Prediction
Read only
PLC configuration
Change configuration
Project Browser (write)
Change program
Execution order... (write)
Change program
Variable declarations... (write)
Change program
ASCII Messages
Read only
Search...
Read only
Trace
Read only
Find Next
Read only
Search Results
Read only
Used references...
Read only
Analyze section
Read only
Analyze program
Read only
Synchronize versions of nested DFBs
Read only
Code generation options...
Supervisor
33002204 12/2010
Concept Security
Access Rights for the Main Menu Online
The following table shows the minimum access rights required in Concept for the
menu commands in the main menu Online:
Menu commands in the main menu Online Minimum access rights needed
33002204 12/2010
Connect... (view only)
Read only
Connect... (change data)
Reset SFC
Connect... (change program)
Download
Connect... (change configuration)
Download
Disconnect...
Read only
Online control panel... (all commands)
Download
Single sweep trigger
Download
Controller status......
Read only
Online events...
Read only
Online diagnostics (read)
Read only
Online diagnostics (acknowledge entries)
Change data
Record changes
Change program
Object information...
Read only
Memory statistics...
Read only
Download... (IEC Program, 984 Ladder
Logic, ASCII Messages, Status-RAM,
Extended Memory)
Download
Download... (configuration)
Change configuration
Download changes...
Change program
Upload... (Status-RAM, Extended Memory)
Change data
Upload... (IEC Program, 984 Ladder Logic,
ASCII Messages, Status-RAM)
Change program
Upload... (configuration)
Change configuration
Reference Data Editor (read only)
Read only
Reference Data Editor (write)
Change data
Reference Data Editor (force)
Force data
Disabled discretes...
Change data
Activate animation
Read only
Change literals during animation
Change data
Animation Panel (SFC Editor)
SFC Animation Panel
Animation Panel (forcing SFC steps)
SFC Animation Panel
Animation Panel (Resetting an SFC string)
SFC Animation Panel
765
Concept Security
Menu commands in the main menu Online Minimum access rights needed
Save animation (IL, ST Editor)
Read only
Restore animation (IL, ST Editor)
Read only
Direct-mode 984LL Editor... (LL984 Editor)
Read only
power flow (LL984 Editor)
Read only
Power flow with contact state (LL984
Editor)
Read only
Trace (LL984 Editor)
Read only
ReTrace (LL984 Editor)
Read only
Access Rights for the Main Menu Options
The following table shows the minimum access rights required in Concept for the
menu commands in the main menu Options:
Menu commands in the main menu
Options
Minimum access rights needed
Confirmations...
Change program
Preferences →Common...
Change program
Preferences →Graphical Editor...
Change program
Preferences →Analysis...
Change program
Preferences →IEC Extensions...
Change program
Save settings
Change program
Save settings on close
Change program
Access Rights for the Main Menu Window
The following table shows the minimum access rights required in Concept for the
menu commands in the main menu Window:
766
Menu commands in the main menu
Window
Minimum access rights needed
Cascade
Read only
Slit window
Read only
Tile
Read only
Arrange icons
Read only
Close all
Read only
Messages
Read only
Name of Open Sections
Read only
33002204 12/2010
Concept Security
Changing Passwords
Introduction
This section describes the steps necessary to change the system administrator's
password and enter new users.
Changing the System Administrator's password
The following steps are only necessary when you start Concept Security for the first
time after installing Concept. They describe the procedure for changing the system
administrator's password:
Step
33002204 12/2010
Action
1
Start access management by double clicking on the Concept Security icon.
2
Enter the user name for the supervisor and confirm with OK. Entering a
password is not necessary in this case.
3
Press the Change Password command button.
4
Enter a password in the Password text box.
Note: The password is context sensitive.
5
To confirm the password, enter the same password in the Confirm New
Password text box.
Reaction: If the two entries are identical, the command button OK is enabled.
6
Confirm the change by pressing the OK button
7
Exit access management with the command button Exit.
767
Concept Security
Entry for a user and the access rights
To enter users, assign access rights and activate Concept Security, follow these
steps:
Step
768
Action
1
Start access management by double clicking on the Concept Security icon.
2
Enter a user name with supervisor access rights, enter the password and confirm
with OK.
3
Select the User tab.
4
Press the Add command button.
5
Enter the user name (at least 2, maximum 16 characters) and confirm with OK.
6
In the Access Rights: list box, select the desired access rights and confirm with
the command button OK.
7
Exit access management with the command button Exit.
8
To change the password for the new user, follow the procedure Changing the
System Administrator's password. Enter the user name for the user that was just
defined.
33002204 12/2010
Concept Security
Activating Access Rights
Activating access rights
To activate access rights, follow these steps:
Step
33002204 12/2010
Action
1
Start access management by double clicking on the Concept Security symbol.
2
Enter a user name with supervisor access rights, enter the password and
acknowledge with OK.
3
Select the register Options.
4
Activate the check box Password Required.
5
Exit access management with the command button Exit.
Reaction: Concept, Concept DFB, Concept EFB, etc. can only be started by
authorized users and with the access rights defined for them.
769
Concept Security
Protecting Projects/DFBs
Introduction
With Concept Security, you can protect projects/DFBs from being changed.
Protected projects can only be loaded on the PLC but cannot be changed. Protected
DFBs can only be used and cannot be changed.
Protecting projects/DFBs
To protect projects/DFBs, follow these steps:
Step
770
Action
1
Start access management by double clicking on the Concept Security symbol.
2
Enter a user name with supervisor access rights, enter the password and confirm
with OK.
3
Select the Protect register.
4
Press the command button Select and select the project/DFB to be protected.
Confirm with OK.
Reaction: The selected project/DFB will appear in a list box.
5
Select the project/DFB in the list box and press Protect.
Reaction: The dialog box Enter Password is opened.
6
Enter a password for Password and acknowledge it by entering the same
password for Confirm Password. Press OK.
Reaction: The project/DFB is now protected. This is identified by a (c) in the list
box.
7
In order to locate protected projects/DFBs quickly, it is advisable to save the list
in the Program/DFB list box using Save list... .
33002204 12/2010
Concept Security
Deactivate protection for projects/DFBs
To deactivate protection for projects/DFBs, follow these steps:
Step
33002204 12/2010
Action
1
Start access management by double clicking on the Concept Security symbol.
2
Enter a user name with supervisor access rights, enter the password and confirm
with OK.
3
Select the Protect register.
4
Press the command button Select and select the protected project/DFB that
should have protection deactivated. Confirm with OK.
Reaction: The selected project/DFB will appear in a list box.
or
Use Load list... to load a previously saved list.
Reaction: All projects/DFBs in the loaded list will appear in the list box.
5
Select the project/DFB from the list box (identified by (c)) and press Unprotect.
Reaction: The Enter Password dialog box is opened.
6
Enter the password for Password and press OK.
Reaction: The project/DFB is no longer protected. This is identified by the (c)
not being shown in the list box.
771
Concept Security
772
33002204 12/2010
33002204 12/2010
Appendices
Overview
Additional information that is not necessarily required for an understanding of the
documentation.
What's in this Appendix?
The appendix contains the following chapters:
Chapter
33002204 12/2010
Chapter Name
Page
A
Tables of PLC-dependent Performance Attributes
775
B
Windows interface
799
C
List of symbols and short cut keys
819
D
IEC conformity
849
E
Configuration examples
877
F
Convert Projects/DFBs/Macros
991
G
Concept ModConnect
995
H
Convertion of Modsoft Programs
1001
I
Modsoft and 984 References
1007
J
Presettings when using Modbus Plus for startup
1011
K
Presettings when using Modbus for startup
1025
L
Startup when using Modbus with the EXECLoader
1031
M
Startup when using Modbus with DOS Loader
1049
N
Startup when using Modbus Plus with the EXECLoader
1063
O
Startup when using Modbus Plus with DOS Loader
1085
P
EXEC files
1101
Q
INI Files
1105
R
Interrupt Processing
1125
S
Automatic Connection to the PLC
1147
773
774
33002204 12/2010
Performance
33002204 12/2010
Tables of PLC-dependent
Performance Attributes
A
Overview
The performance attributes of the different hardware platforms (Quantum, Compact,
Momentum and Atrium) can be found in the following tables.
What's in this Chapter?
This chapter contains the following topics:
Topic
Performance of Quantum
33002204 12/2010
Page
776
Performance Attributes of Compact
781
Performance Attributes of Momentum
786
Performance Attributes of Atrium
792
775
Performance
Performance of Quantum
IEC and LL984 Support
Availability of IEC and LL984 support:
CPU type
Performance
113 02
113 03
213 04
424 0x
434 12
534 14
LL984 only
x
-
-
-
-
-
IEC only (Stripped Exec)
x
x
x
-
-
-
IEC and LL984
-
x
x
x
x
x
213 04
424 0x
434 12
534 14
x = available
- = not available
Special Performance Attributes
Availability of special performance attributes:
CPU type
Performance
776
113 02
113 03
LL984 Hot Standby
x
x
x
x
x
x
IEC Hot Standby
-
-
-
-
x
x
Interrupt processing with
HLI (LL984 only)
x
x
x
x
x
x
Split memory (LL984 only with separate software
-
-
-
-
-
Support for XMIT
loadable (LL984 only)
x
x
x
x
x
x
Support for XMIT EFB
(IEC only)
-
-
-
-
-
-
Support for XXMIT EFB
(IEC only)
x
x
x
x
x
x
Upload of the user
program
x
x
x
x
x
x
Support of the Modbus
function codes 42 (IEC
only)
x
x
x
x
x
x
Password protection of
connection structure with
PLC
-
-
-
-
-
-
PCMCIA support
-
-
-
-
-
-
33002204 12/2010
Performance
CPU type
Performance
113 02
113 03
213 04
424 0x
434 12
534 14
Flash memory for
program and
configuration
-
-
-
-
x
x
Remote Terminal Unit
(RTU) configuration
extension
-
-
-
-
-
-
Profibus DP configuration x
extension
x
x
x
x
x
x
x
x
x
x
x
Code generation options: x
Include diagnosis
information
x
x
x
x
x
Code generation options: Fastest code
-
x
x
x
x
MMS Ethernet
configuration extension
x
x
x
x
x
x
ASCII Messages
x
x
x
x
x
x
Peer Cop
x
x
x
x
x
x
RIO (Remote I/O)
x
x
x
x
x
x
Cyclical data exchange
for configuration
extension
DIO (Distributed I/O)
x
x
x
x
x
x
SYMAX I/O
x
x
x
x
x
x
800 I/O
x
x
x
x
x
x
LonWorks
x
x
x
x
x
x
A120 I/O
-
-
-
-
-
-
x = available
- = not available
33002204 12/2010
777
Performance
Buses
Availability of the buses:
CPU type
Performance
113 02
113 03
213 04
424 0x
434 12
534 14
Modbus
x
x
x
x
x
x
Modbus Plus
x
x
x
x
x
x
Ethernet (TCP/IP)
x
x
x
x
x
x
Ethernet (SY/MAX)
x
x
x
x
x
x
Interbus
x
x
x
x
x
x
Interbus: PCP loadable
(LL984 only)
x
x
x
x
x
x
Interbus: PCP-EFB (IEC
only)
x
x
x
x
-
-
INTERBUS G4
(Generic Bus)
-
x
x
-
x
x
LonWorks (Echelon)
using
NOL 911
xx and
LL984
using
NOL 911
xx and
LL984
using
NOL 911
xx and
LL984
using
NOL 911
xx and
LL984
using
NOL 911
xx and
LL984
using
NOL 911
xx and
LL984
MVB (MultiVehicleBus)
-
-
-
-
-
-
x = available
- = not available
778
33002204 12/2010
Performance
Block Libraries
Availability of the block libraries:
CPU type
Performance
113 02
113 03
213 04
424 0x
434 12
534 14
AKFEFB (IEC only)
x
x
x
x
x
x
ANA_IO (IEC only)
x
x
x
x
x
x
COMM (IEC only)
x
x
x
x
x
x
CONT_CTL (IEC only)
x
x
x
x
x
x
DIAGNO (IEC only)
x
x
x
x
x
x
EXPERTS (IEC only)
x
x
x
x
x
x
EXTENDED (IEC only)
x
x
x
x
x
x
FUZZY (IEC only)
x
x
x
x
x
x
HANDTABLEAU (IEC
only)
x
x
x
x
x
x
IEC (IEC only
x
x
x
x
x
x
LIB984 (IEC only)
x
x
x
x
x
x
SYSTEM (IEC only)
x
x
x
x
x
x
LL984 (LL984 only)
x
x
x
x
x
x
x = available
- = not available
Utilities
Availability of utilities:
CPU type
Performance
113 02
113 03
213 04
424 0x
434 12
534 14
Concept DFB
x
x
x
x
x
x
Concept EFB
x
x
x
x
x
x
Concept SIM
x
x
x
x
x
x
Concept PLCSIM32
x
x
x
x
x
x
Concept security
x
x
x
x
x
x
Concept EXECLoader
x
x
x
x
x
x
Concept-Converter
x
x
x
x
x
x
Modsoft converter
x
x
x
x
x
x
ModConnect tool
x
x
x
x
x
x
x = available
- = not available
33002204 12/2010
779
Performance
Runtime System
Runtime System
CPU type
Performance
113 02
113 03
213 04
424 0x
434 12
534 14
16 bit CPU
x
x
x
x
-
-
32 bit CPU
-
-
-
-
x
x
x = available
- = not available
Available Memory for User Program
Available memory for user program
CPU type
Performance
113 02
113 03
213 04
424 0x
434 12
534 14
IEC only runtime system
125k
375k
612k
-
-
-
IEC and LL984 runtime
system
-
160k
330k
460k
800k
2500k
LL984 only runtime
system
-
-
-
-
-
-
x = available
- = not available
Different Performance Attributes
Availability of different performance attributes:
CPU type
Performance
113 02
113 03
213 04
424 0x
534 14
534 14
Battery adapter required
for backing up IEC
programs
-
-
-
-
-
-
Floating point processor
-
-
x
x
x
x
Floating point emulation
(IEC)
x
x
-
-
-
-
x = available
- = not available
780
33002204 12/2010
Performance
Performance Attributes of Compact
IEC and LL984 Support
Availability of IEC and LL984 support:
CPU type
Performance
258 (512k)
265 (512k)
275 (512k)
285 (1M)
LL984 only
-
-
-
-
IEC only (Stripped Exec)
-
-
-
-
IEC and LL984
x
x
x
x
275 (512k)
285 (1M)
x = available
- = not available
Special Performance Attributes
Availability of special performance attributes:
CPU type
Performance
33002204 12/2010
258 (512k)
265 (512k)
LL984 Hot Standby
-
-
-
-
IEC Hot Standby
-
-
-
-
Interrupt processing with HLI
(LL984 only)
-
-
-
-
Split memory (LL984 only with
separate software
x
x
x
x
Support for XMIT loadable
(LL984 only)
x
x
x
x
Support for XMIT EFB (IEC
only)
-
-
-
-
Support for XXMIT EFB (IEC
only)
x
x
x
x
Upload of the user program
x
x
x
x
Support of Modbus function
code 42 (IEC only)
x
x
x
x
Password protection of
connection structure with PLC
x
x
x
x
PCMCIA support
-
-
x
x
Flash memory for program and x
configuration
x
x
x
781
Performance
CPU type
Performance
258 (512k)
265 (512k)
275 (512k)
285 (1M)
Remote Terminal Unit (RTU)
configuration extension
x
x
x
x
Profibus DP configuration
extension
-
-
-
-
Cyclical data exchange for
configuration extension
-
-
-
-
Code generation options:
Include diagnosis information
x
x
x
x
Code generation options:
Fastest code
x
x
x
x
MMS Ethernet configuration
extension
-
-
-
-
ASCII Messages
-
-
-
-
Peer Cop
-
x
x
x
RIO (Remote I/O)
-
-
-
-
DIO (Distributed I/O)
-
-
-
-
SYMAX I/O
-
-
-
-
800 I/O
-
-
-
-
LonWorks
-
-
-
-
A120 I/O
x
x
x
x
x = available
- = not available
782
33002204 12/2010
Performance
Buses
Availability of the buses:
CPU type
Performance
258 (512k)
265 (512k)
275 (512k)
285 (1M)
Modbus
x
x
x
x
Modbus Plus
using
BridgeModul
e
x
x
x
Ethernet (TCP/IP)
using
BridgeModul
e
using
BridgeModul
e
using
BridgeMod
ule
using
BridgeModul
e
Ethernet (SY/MAX)
-
-
-
-
Interbus
using BKF
xxx
using BKF
xxx
using BKF
xxx
using BKF
xxx
Interbus: PCP loadable (LL984 only)
-
-
-
Interbus: PCP-EFB (IEC only)
-
-
-
-
LonWorks (Echelon)
-
-
-
-
MVB (MultiVehicleBus)
x
x
x
x
x = available
- = not available
33002204 12/2010
783
Performance
Block Libraries
Availability of block libraries:
CPU type
Performance
258 (512k)
265 (512k)
275 (512k)
285 (1M)
AKFEFB (IEC only)
x
x
x
x
ANA_IO (IEC only)
x
x
x
x
COMM (IEC only)
-
x
x
x
CONT_CTL (IEC only)
x
x
x
x
DIAGNO (IEC only)
x
x
x
x
EXPERTS (IEC only)
x
x
x
x
EXTENDED (IEC only)
x
x
x
x
FUZZY (IEC only)
x
x
x
x
HANDTABLEAU (IEC only)
x
x
x
x
IEC (IEC only)
x
x
x
x
LIB984 (IEC only)
x
x
x
x
SYSTEM (IEC only)
x
x
x
x
LL984 (LL984 only)
x
x
x
x
x = available
- = not available
Utilities
Availability of utilities:
CPU type
Performance
258 (512k)
265 (512k)
275 (512k)
285 (1M)
Concept DFB
x
x
x
x
Concept EFB
x
x
x
x
Concept SIM
x
x
x
x
Concept PLCSIM32
x
x
x
x
Concept Security
x
x
x
x
Concept EXECLoader
x
x
x
x
Concept-Converter
x
x
x
x
Modsoft converter
x
x
x
x
Concept-ModConnect
-
-
-
-
x = available
- = not available
784
33002204 12/2010
Performance
Runtime System
Runtime system
CPU type
Performance
258 (512k)
265 (512k)
275 (512k)
285 (1M)
16 bit CPU
-
-
-
-
32 bit CPU
x
x
x
x
x = available
- = not available
Different Performance Attributes
Availability of different performance attributes:
CPU type
Performance
258 (512k)
265 (512k)
275 (512k)
285 (1M)
Battery adapter required for
backing up IEC programs
-
-
-
-
Floating point processing
-
-
-
-
Floating point emulation
x
x
x
x
x = available
- = not available
33002204 12/2010
785
Performance
Performance Attributes of Momentum
IEC and LL984 Support
Availability of IEC and LL984 support:
CPU type
Performance
700 00
700 10
780 00
760 00
760 10
780 10
960 20
980 20
960 30
980 30
970 30
LL984 only
x
x
x
x
x
x
IEC only
-
x
x
-
x
x
IEC and LL984
-
-
-
-
-
-
x = available
- = not available
Special Performance Attributes
Availability of special performance attributes:
CPU type
Performance
700 00
700 10
780 00
760 00
760 10
780 10
960 20
980 20
960 30
980 30
970 30
LL984 Hot Standby
-
-
-
-
-
-
IEC Hot Standby
-
-
-
-
-
-
Interrupt processing with HLI (LL984 only)
-
-
-
-
-
-
Split memory (LL984 only with separate
software
-
-
-
-
-
-
Support for the XMIT blocks (LL984 only)
x
x
x
x
x
x
Support for XMIT EFB (IEC only)
-
-
-
-
-
-
Support for XXMIT EFB (IEC only)
x
x
x
x
x
x
Uploading the user program
x
x
x
x
x
x
Support of Modbus function code 42 (IEC only) -
x
x
-
x
x
Password protection of connection structure
with PLC
-
-
-
x
x
x
PCMCIA support
-
-
-
-
-
-
Flash memory for program and configuration
(LL984)
x
x
x
x
x
x
Flash memory for program and configuration
(IEC)
-
-
x
-
x
x
786
33002204 12/2010
Performance
CPU type
Performance
700 00
700 10
780 00
760 00
760 10
780 10
960 20
980 20
960 30
980 30
970 30
Remote Terminal Unit (RTU) configuration
extension
-
-
-
-
-
-
Profibus DP configuration extension
-
-
-
-
-
-
Cyclical data exchange for configuration
extension
-
-
-
-
-
-
Code generation options: Include diagnostics
information
-
-
-
-
-
-
Code generation options: Fastest code
-
-
-
-
-
-
MMS Ethernet configuration extension
-
-
-
-
-
-
ASCII messages
-
-
-
-
-
-
Peer Cop
x
x
x
x
x
-
RIO (Remote I/O)
-
-
-
-
-
-
DIO (Distributed I/O)
-
-
-
-
-
-
TIO (Terminal I/O
x
x
x
x
x
-
SY/MAX I/O
-
-
-
-
-
-
800 I/O
-
-
-
-
-
-
LonWorks
-
-
-
-
-
-
A120 I/O
-
-
-
-
-
-
x = available
- = not available
33002204 12/2010
787
Performance
Buses
Availability of the buses:
CPU type
Performance
700 00
700 10
780 00
760 00
760 10
780 10
960 20
980 20
960 30
980 30
970 30
Modbus (with ring card)
x
x
x
x
x
-
Modbus Plus (with ring card)
x
x
x
x
x
-
Ethernet (TCP/IP)
-
-
-
x (LL984 x
only)
x
Ethernet (SY/MAX)
-
-
-
-
-
-
INTERBUS
x
x
x
x
x
-
INTERBUS: PCP loadable (LL984 only)
-
-
-
-
-
-
INTERBUS: PCP-EFB (IEC only)
-
-
-
-
-
-
LonWorks (Echelon)
-
-
-
-
-
-
MVB (MultiVehicleBus)
-
-
-
-
-
-
x = available
- = not available
788
33002204 12/2010
Performance
Block Libraries
Availability of the block libraries:
CPU type
Performance
700 00
700 10
780 00
760 00
760 10
780 10
960 20
980 20
960 30
980 30
970 30
AKFEFB (IEC only)
-
x
x
-
x
x
ANA_IO (IEC only)
-
x
x
-
x
x
COMM (IEC only)
-
-
-
-
x
x
CONT_CTL (IEC only)
-
x
x
-
x
x
DIAGNO (IEC only)
-
x
x
-
x
x
EXPERTS (IEC only)
-
-
-
-
x
x
EXTENDED (IEC only)
-
x
x
-
x
x
FUZZY (IEC only)
-
x
x
-
x
x
HANDTABLEAU (IEC only)
-
-
-
-
x
x
IEC (IEC only)
-
x
x
-
x
x
LIB984 (IEC only)
-
x
x
-
x
x
SYSTEM (IEC only)
-
x
x
-
x
x
LL984 (LL984 only)
x
x
x
x
x
x
x = available
- = not available
33002204 12/2010
789
Performance
Utilities
Availability of utilities:
CPU type
Performance
700 00
700 10
780 00
760 00
760 10
780 10
960 20
980 20
960 30
980 30
970 30
Concept DFB
-
x
x
-
x
x
Concept EFB
-
x
x
-
x
x
Concept SIM
-
x
x
-
x
x
Concept PLCSIM32
-
x
x
-
x
x
Concept security
-
x
x
-
x
x
Concept EXECLoader
x
x
x
x
x
x
Concept-Converter
x
x
x
x
x
x
Modsoft converter
x
x
x
x
x
x
Concept-ModConnect
x
x
x
x
x
x
x = available
- = not available
Runtime System
Runtime system
CPU type
Performance
700 00
700 10
780 00
760 00
760 10
780 10
960 20
980 20
960 30
980 30
970 30
16 bit CPU
x
x
x
x
x
x
32 bit CPU
-
-
-
-
-
-
x = available
- = not available
790
33002204 12/2010
Performance
Different Performance Attributes
Availability of different performance attributes:
CPU type
Performance
700 00
700 10
780 00
760 00
760 10
780 10
960 20
980 20
960 30
980 30
970 30
Battery adapter required for backing up IEC
programs
-
x
-
-
-
-
Floating point processor
-
-
-
-
-
-
Floating point emulation (IEC)
-
x
x
-
x
x
x = available
- = not available
33002204 12/2010
791
Performance
Performance Attributes of Atrium
IEC and LL984 Support
Availability of IEC and LL984 support:
CPU type
Performance
121 01 (2M)
241 01 (4M)
241 11 (4M)
LL984 only
-
IEC only (Stripped Exec)
x
IEC and LL984
-
x = available
- = not available
Special Performance Attributes
Availability of special performance attributes:
CPU type
Performance
792
121 01 (2M)
241 01 (4M)
241 11 (4M)
LL984 Hot Standby
-
IEC Hot Standby
-
Interrupt processing with HLI
(LL984 only)
-
Split memory (LL984 only with
separate software
-
Support for XMIT loadable
(LL984 only)
-
Support for XMIT EFB (IEC
only)
-
Support for XXMIT EFB (IEC
only)
-
Upload of the user program
x
Support of Modbus function
code 42 (IEC only)
x
Password protection of
connection structure with PLC
-
PCMCIA support
33002204 12/2010
Performance
CPU type
Performance
121 01 (2M)
241 01 (4M)
241 11 (4M)
Flash memory for program and configuration
Remote Terminal Unit (RTU)
configuration extension
-
Profibus DP configuration
extension
-
Cyclical data exchange for
configuration extension
-
Code generation options:
Include diagnosis information
-
Code generation options:
Fastest code
-
MMS Ethernet configuration
extension
-
ASCII Messages
-
Peer Cop
x
RIO (Remote I/O)
-
DIO (Distributed I/O)
-
SYMAX I/O
-
800 I/O
-
LonWorks
-
A120 I/O
-
x = available
- = not available
33002204 12/2010
793
Performance
Buses
Availability of the buses:
CPU type
Performance
121 01 (2M)
241 01 (2M)
241 11 (4M)
Modbus
-
Modbus Plus
x
Ethernet (TCP/IP)
-
Ethernet (SY/MAX)
-
Interbus
x
x
x
Interbus: PCP loadable (LL984 only)
-
Interbus: PCP-EFB (IEC only)
-
Profibus
-
LonWorks (Echelon)
-
MVB (MultiVehicleBus)
-
x = available
- = not available
794
33002204 12/2010
Performance
Block Libraries
Availability of block libraries:
CPU type
Performance
121 01 (2M)
241 01 (2M)
241 11 (4M)
AKFEFB (IEC only)
x
ANA_IO (IEC only)
x
COMM (IEC only)
x
CONT_CTL (IEC only)
x
DIAGNO (IEC only)
x
EXPERTS (IEC only)
x
EXTENDED (IEC only)
x
FUZZY (IEC only)
x
HANDTABLEAU (IEC only)
x
IEC (IEC only)
x
LIB984 (IEC only)
x
SYSTEM (IEC only)
x
LL984 (LL984 only)
-
x = available
- = not available
33002204 12/2010
795
Performance
Utilities
Availability of utilities:
CPU type
Performance
121 01 (2M)
241 01 (2M)
241 11 (4M)
Concept DFB
x
Concept EFB
x
Concept SIM
x
Concept PLCSIM32
x
Concept Security
x
Concept EXECLoader
x
Concept-Converter
x
Modsoft converter
x
Concept-ModConnect
-
x = available
- = not available
Runtime System
Runtime system
CPU type
Performance
121 01 (2M)
241 01 (2M)
241 11 (4M)
16 bit CPU
-
32 bit CPU
x
x = available
- = not available
796
33002204 12/2010
Performance
Different Performance Attributes
Availability of different performance attributes:
CPU type
Performance
121 01 (2M)
241 01 (2M)
241 11 (4M)
Battery adapter required for backing up
IEC programs
-
Floating point processor
x
x
Floating point emulation
x
-
x = available
- = not available
33002204 12/2010
797
Performance
798
33002204 12/2010
Windows interface
33002204 12/2010
Windows interface
B
Overview
The chapter describes the most important properties of Concept’s Windows
interface. Further information can be found in the Microsoft Windows manuals.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
B.1
Window
800
B.2
Menu commands
806
B.3
Dialog boxes
808
B.4
Generating a project symbol
811
B.5
Online help
813
799
Windows interface
B.1
Window
Overview
This section describes the types of windows and window elements in Windows.
What's in this Section?
This section contains the following topics:
Topic
800
Page
Window Types
801
Elements of a window
803
33002204 12/2010
Windows interface
Window Types
Introduction
In Windows there are two types of windows:
z Application Window
z Document Window
Types of window:
Application Window
When Concept is started the application window is opened on your desktop. The
application window can be moved to any position on the desktop. Alternatively it can
be minimized to a button on the task bar.
A project can be opened or created in this application window. The name of the
project then appears in the title bar of the application window.
33002204 12/2010
801
Windows interface
Document Window
After opening or creating a project you can open different document windows.
Document windows are, for example, sections in which a user program is created or
the document window of the PLC configuration.
Several document windows can be open simultaneously, but only one of these can
be active. An active document window can be recognized by the color of the title bar.
Depending on the active document window the menu commands change in the pull
down menus and the tool bar of the application window.
802
33002204 12/2010
Windows interface
Elements of a window
At a Glance
This section describes the Concept specific elements of a window.
Elements of a window:
Title bar
A project’s title bar shows the name of the active application (i.e. Concept) and the
name of the project. When coupled with a PLC the node address of the PLC is
indicated in angled brackets (<>). If this PLC is on another network the routing path
is also indicated.
If a document window (e.g. a section) is enlarged to full screen, i.e. the section takes
up the entire application window, the name of the document window (e.g. the section
name) appears in the title bar.
Document windows which are not enlarged to full screen have their own title bar in
which the name of the document window is indicated.
33002204 12/2010
803
Windows interface
Menu Bar
The menu bar of the application window contains various main menus. The contents
of the menu bar depend on the active document window.
Toolbar
The toolbar consists of buttons which correspond to a menu command on the pulldown menus. The range and content of the toolbar depend on which window is
active.
There are three different ways a button can be represented:
grayed
The command is currently unavailable. One or more other commands must be
executed before the desired button can be used.
z unpressed
The command can be selected.
z pressed
The command is active.
z
Status bar
The appearance of the status bar depends on whether the project is open and the
programming language used in the section.
In the first part of the status bar various information is displayed depending on the
selected object.
z If a dialog box is open or a menu command or button has been selected some
help will be given about it. To display the help select a menu command or a button
with the left mouse button and hold it down. A short description of the menu
command or button appears in the status bar. To execute the menu
command/button release the mouse button. If execution of the menu
command/button is not required, move the pointer away from the active area (the
description in the status bar disappears) and then release the mouse button.
z If an FFB, a parameter to an input/output, a step or a transition has been selected,
a comment about the selected object is displayed. With parameters and
transitions the assigned direct address (only in case of located variables) is also
displayed.
The second part of the status bar (status of the active section) indicates whether the
section is in animation mode or the section is disabled.
z ANIMATED
The section is animated.
z INHIBITED
The section is inhibited and will not be processed.
The third part of the status bar indicates the status of the PLC.
z NOT CONNECTED.
The programming device is not coupled with a PLC.
804
33002204 12/2010
Windows interface
z
z
STOPPED
The program on the PLC is suspended.
RUNNING: CHANGE CONFIG
The program on the PLC is running and was connected with the access Change
Configuration.
In the fourth part of the status bar the program status between the PLC and
programming device is displayed. This display only appears if a project is open and
the programming device with PLC is online.
z EQUAL
The program on the programming device and the PLC is consistent.
z UNEQUAL
The program on the programming device and the PLC is not consistent. To
establish consistency use the menu command Online →Load... .
z MODIFIED
The program on the programming device was modified. The modifications can be
made online in the PLC with the menu command Online →Load changes.
Status bar:
33002204 12/2010
805
Windows interface
B.2
Menu commands
Menu commands
At a Glance
The titles of the individual menus are displayed in the menu bar. The menu
commands are listed in the pull-down menus. As in Windows, each Concept window
and dialog box has a system menu. This menu is opened using the small box in the
top left-hand corner of the window.
A pull-down menu is opened by left-clicking on the title of the menu. To go directly
to a menu command, drag the mouse pointer down the menu and then release the
mouse button.
The menu can be closed by clicking on the title of the menu or anywhere outside of
the menu.
Typical pull-down menu:
Underlined letter
A main menu (menu title) and subsequently a menu command can be selected by
holding down Alt and simultaneously entering the underlined letter in the menu title
and then that of the menu command. If, for instance, from the menu Project you
want to execute the menu command Search... press Alt+P to open the menu and
then Alt+S to execute the menu command.
806
33002204 12/2010
Windows interface
Grayed out menu command
The command is currently unavailable. One or more other commands must be
executed before the desired menu command can be executed.
Suspension points (…) after the menu command
On execution of this menu command a dialog box appears with options, which must
be selected before execution.
Check mark (√) before the menu command
The menu command is active. If the menu command is selected the check mark
disappears and the menu command is inactive. The check mark is mostly used to
identify active modes (e.g. normal display, dial in mode etc.).
Shortcut keys
The key combinations (e.g. F8, Alt+F9, Ctrl+R) after the menu command are
shortcut keys for executing this menu command. Using this key or key combination
the menu command can be selected, without having to open the menu.
33002204 12/2010
807
Windows interface
B.3
Dialog boxes
Dialog boxes
At a Glance
In Concept dialog boxes are displayed if additional information is required from you
in order to perform a particular task. Potentially necessary information is also
communicated in this way.
Most dialog boxes contain options which can be selected, textboxes, in which text
can be entered, and buttons which can be pressed.
Grayed out options are currently not available. One or more other commands must
be executed, or options selected or deselected, before the desired option can be
activated.
Concept specific basics of a window:
808
33002204 12/2010
Windows interface
Command buttons
Command buttons are used to initiate actions immediately, e.g. executing or
aborting a command. Command buttons include e.g. OK, Abort and Help.
Command buttons followed by suspension points (…), open a further dialog box. A
command button with a "greater than" sign (>>) extends the active dialog box.
The standard setting is identified by a dark margin. This command button can be
selected by pressing Enter.
To close a dialog box without executing a command select the command button
Cancel.
Text boxes
Information (text) is entered into a text box.
If you enter an empty text box an insertion point appears in the far left of the box.
The entered text begins at this insertion point. If text is already present within the
respective box, it will be selected and replaced by the new text automatically. The
text can, however, also be deleted by pressing Delete or Backspace.
Lists
In a list the available selection possibilities are listed. If more possibilities are
available than fit into the list, the scrollbar or the arrow keys can be used to move
within the list.
As a rule only a single entry can be chosen form the list. There are, however, some
cases in which several entries can be chosen, e.g. when opening sections.
One line lists
A single line list box initially appears as a rectangular box, in which the current
selection (the default value) is selected. If the arrow in the right of the box is selected,
a list of the available selection possibilities opens. If more possibilities are available
than fit into the list, then the scrollbar or arrow keys can be used to move around the
list.
Option buttons
Option buttons represent mutually exclusive options. In each case only one option
can be chosen.
The selected option button is identified by a black dot.
If the option name contains an underlined letter, the option button can be activated
from any position in the dialog box by holding down Alt and entering the underlined
letter.
33002204 12/2010
809
Windows interface
Check box
A check box next to an option means that the option can be activated or deactivated.
Any number of check box options can be activated.
Activated options are identified by an X or a check mark (√).
If the option name contains an underlined letter, the check box can be activated or
deactivated from any position in the dialog box by holding down Alt and entering the
underlined letter.
810
33002204 12/2010
Windows interface
B.4
Generating a project symbol
Creating a Project Symbol in a Program Group
Introduction
Creating a project symbol allows you to immediately load a certain project and/or
connect to a PLC when opening Concept. In this way, one or more program groups
can be created, which e.g. contain all the projects in a system.
NOTE: A symbol can only be created for an existing project. Otherwise an error
message appears when starting.
Creating a symbol for projects
Follow these steps to create a project symbol:
Step
33002204 12/2010
Action
1
Under Start →Settings →Taskbar..., you can open the Taskbar Properties
dialog box.
2
In the register Start Menu Programs/Expanded (Win2000), select the Add...
command button.
3
In the Create Shortcut dialog box, select the Browse... command button.
4
In the Browse dialog box, go to the Concept installation path and double-click
on the file CONCEPT.EXE.
Result: The Browse dialog box is closed and the file CONCEPT.EXE is entered,
including the path, in the Command line: text box, e.g.
C:\CONCEPT\CONCEPT.EXE.
5
Now add the project path and project name to the command line, e.g.
C:\CONCEPT\CONCEPT.EXE PLANT1.PRJ and confirm the entry using Next>
command button.
Note: To create a connection to any PLC, add additional Parameters
(see page 1148) to the command line.
6
In the Select program group dialog box, select an existing program group for
the symbol or create a new one using New folder....
Confirm the entry using the Next> command button.
7
In the Select program designation dialog box, select the project name and
confirm using the Finish command button.
8
Close the Taskbar Properties dialog box with OK.
Result: The properties dialog box is closed and the project symbol is available
in the start menu of the folder you selected.
9
Open the folder with the project symbol in the Start Menu.
Select the project symbol and click the right mouse button.
Result: A menu window is opened.
811
Windows interface
Step
Action
10
Select the Properties command button.
Result: The "Project Symbol Name" Properties dialog box is opened.
11
Go to the Connection register and complete the command line Working
directory/Target (Win2000) with the name of the project directory, e.g.
C:\CONCEPT\PROJECTS.
Confirm the entry using the Set command button.
12
Then exit the dialog box by selecting OK.
13
Open the project by clicking on the project symbol.
Creating a symbol for DFBs
In this way, symbols can also be created for DFBs. To do this, select the file
CCEPTDFB.EXE in step 4 and add the DFB name and path instead of the project
name and path in step 5.
812
33002204 12/2010
Windows interface
B.5
Online help
Overview
This section describes use of online help.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
At a Glance
814
How the Online Help is set out
815
813
Windows interface
At a Glance
General information
The online help is used to quickly and easily obtain information about the task being
performed, the use of an unfamiliar command or the functions, Function Blocks and
modules.
The online help is available throughout Concept.
NOTE: The option Use polygon acceleration may not be used if the graphics card
has hardware acceleration functions. Use of these may still lead to the graphics in
the online help being incomplete. A detailed description of how to switch off the
acceleration function will be found in the graphics card’s user manual.
Starting the online help
There are several methods of calling up the online help:
Invoking the contents)
There are two methods of invoking the online help contents:
z To invoke the online help contents, select the menu command Help →
Contents.
z In the program group Concept open the help symbol.
z
z
Help with the execution of a menu command
There are two methods of invoking help with a menu command:
z using the mouse)
To obtain an explanation select the menu command with the left mouse
button, hold down the mouse button, press F1, and then release the mouse
button.
z using the keyboard)
To obtain an explanation of a menu command, select it and then press F1.
z
Help with a dialog
There are two methods of invoking help with a dialog:
z To obtain an explanation of a dialog, click on the command button Helpin the
dialog itself.
z To obtain an explanation of a dialog, press F1in the dialog itself.
z
Help with operating an EFB
To obtain an explanation of the operation of the EFB, click on the command
button Help with type within the dialog with the EFB properties.
Help with the operation of a module
In the dialog I/O module selection click on the command button Help with
module, to obtain an explanation of the operation of a module.
z
814
33002204 12/2010
Windows interface
How the Online Help is set out
Introduction
If you start the online help, the Windows Help system opens, containing either
z a table of contents (if you started with Help →Contents or the icon),
z or containing a description of the dialog (if you started with the Help command
button),
z or containing a description of an EFB (if you started with the Help on Type
command button),
z or containing a description of a module (if you started with the Module Help
command button),
This section describes the Concept specific basics of the online help window.
Online help window:
Title Bar
The title bar contains the active help file names, or in other words the help project.
33002204 12/2010
815
Windows interface
Menu Bar
A description of the standard menu bar can be found in the respective Microsoft
Windows manual.
Toolbar
The following buttons are available in Concept:
Contents
This button is used to invoke the online help contents directory.
Details about this function can be found in the corresponding Windows Manual.
Note: If you jump (see page 817) between different help projects and click the
Contents button, the contents of the invoked help project (rather than the current
one) is displayed. This is a Microsoft error. The Navigator is available to allow you
to navigate within the current help project (related topics Navigator, page 816).
z Index
This button is used to invoke an index for finding help texts.
Details about this function can be found in the corresponding Windows Manual.
Note: If you want to carry out a search of the whole text, press the Index
command button, select the Search index card, choose the desired search
function and type in the term you're looking for.
z Back
This button is used to invoke the previously read help text.
z Print
This button is used to print out the current topic (the current help topic).
z <<
This button is used to "browse" the previous help text. This button is used to read
the online help like a book. When you have reached the first "page" of the online
help (contents directory), the button is hidden.
z >>
This button is used to "browse" to the next help text. This button is used to read
the online help like a book. When you have reached the last "page" of the online
help, the button is hidden.
z History
When you use this button a window opens which displays all of the help topics
that are already open.
z
Title of Topic
The topic title refers to the title of a chapter from paper documentation. This topic
title always remains visible, even if, in the case of long documents, the text is moved
in the window.
Navigator
The Navigator is in the topic title. It serves as a navigator inside the help projects.
816
33002204 12/2010
Windows interface
Jump
A jump can be recognized by the fact it is written in green and is underlined. When
you click on a jump, the help text corresponding to this key word/ topic appears.
Jumps correspond to "related topics" entries in paper documents, the pages are
however removed for your convenience. The invoked help text is then replaced by
a new help text.
Popup
A popup can be recognized by the fact it is written in green and has a dotted line
under it. When you click on a popup, the help text corresponding to this key word
appears. Popups correspond to glossary entries in paper documents, however, the
pages here are removed for your convenience. To display the text, a popup window
is opened. This popup window may contain further popups. The popup window is
cleared by re-clicking on it or pressing any key. This does not replace the present
help text.
33002204 12/2010
817
Windows interface
818
33002204 12/2010
List of symbols and short cut keys
33002204 12/2010
List of symbols and short cut keys
C
Description
Each editor and the PLC configuration have their own list of symbols available. This
facilitates access to frequently used functions. It is also possible to call up many
functions with short cut keys instead of menu commands.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
C.1
Icon bar
820
C.2
Short cut keys
832
819
List of symbols and short cut keys
C.1
Icon bar
Description
This section describes the icon bar icons. In the icon bars there are editor
independent and editor dependent icons.
What's in this Section?
This section contains the following topics:
Topic
General icon bar
820
Page
821
Icon bar in the FBD editor
822
Icon bar in the SFC-Editor
823
Icon bar in the LD editor
825
List of Symbols in the IL and ST Editor
827
List of Symbols in the LL984-Editor
828
Icons in PLC Configuration
829
Toolbar in the RDE Editor
830
Toolbar in the Project Browser
831
33002204 12/2010
List of symbols and short cut keys
General icon bar
Symbols
The table below shows the available symbols and their corresponding menu entry
commands:
Symbol
Menu entry command executed
File →Open...
File →New section... / New DFB section...
File →Open section...
File →Save
Project →Variable declaration...
Project →Search…
Online →Online control panel...
Online →Download changes...
Edit →Undo: Delete
Edit →Cut
Edit →Copy
Edit →Paste
33002204 12/2010
821
List of symbols and short cut keys
Icon bar in the FBD editor
Symbols
The table shows the additional icons available in the FBD editor and the
corresponding menu entry commands (see also General icon bar, page 821):
Symbol
Menu entry command executed
View →Zoom in
View →Zoom out
Objects →Select
Objects →Link
Objects →FFB: Last Type
Objects →Invert Input/Output
Objects →Text
Objects →FFB selection...
Online →Animate selected
Online →Animate booleans
822
33002204 12/2010
List of symbols and short cut keys
Icon bar in the SFC-Editor
Symbols
The table shows the additional icons available in the SFC editor and the
corresponding menu entry commands (see also General icon bar, page 821):
Symbol
Menu entry command executed
View →Zoom in
View →Zoom out
Objects →Select
Objects →Select column structure
Objects →Select row structure
Objects →Step
Objects →Transition
Objects →Parallel branch
Objects →Parallel joint
Objects →Alternative branch
Objects →Alternative joint
Objects →Jump
Objects →Link
Objects →Step - Transition sequence
Objects →Structured Parallel sequence
Objects →Structured Alternative sequence
33002204 12/2010
823
List of symbols and short cut keys
Symbol
Menu entry command executed
Objects →Transition - Step sequence
Objects →Text
Online →Animate
Online →Animation Panel functions
824
33002204 12/2010
List of symbols and short cut keys
Icon bar in the LD editor
Symbols
The table shows the additional symbols available in the LD editor and the
corresponding menu entry commands (please also refer to the General icon bar,
page 821):
Symbol
Menu entry command executed
View →Zoom in
View →Zoom out
Objects →Select
Objects →Link
Objects →Direct Link
Objects →Vertical Link
Objects →FFB: Last Type
Objects →Invert Input/Output
Objects →Text
Objects →FFB selection...
Objects →Coil
Objects →Coil - Negated
Objects →Contact - Normally Open
Objects →Contact – Normally Closed
33002204 12/2010
825
List of symbols and short cut keys
Symbol
Menu entry command executed
Online →Animate selected
Online →Animate booleans
826
33002204 12/2010
List of symbols and short cut keys
List of Symbols in the IL and ST Editor
Symbols
The table shows the additional symbols available in the IL and ST editor and the
corresponding menu entry commands (see also General icon bar, page 821):
Symbol
Menu Entry Command Executed
Objects →Insert FFB
Online →Watch Selected
Online →Animate booleans
33002204 12/2010
827
List of symbols and short cut keys
List of Symbols in the LL984-Editor
Symbols
The table shows the additional symbols available in the LL984 editor and the
corresponding menu entry commands (see also General icon bar, page 821):
Symbol
Menu Entry Command Executed
Objects →Select
Objects →Coil
Objects →Coil - Retentive
Objects →Horiz Short
Objects →Vertical Short
Objects →Contact – Normally Open
Objects →Contact – Normally Closed
Objects →Contact – Pos Trans
Objects →Contact – Neg Trans
Objects →Instruction: Last Type
Objects →List Instructions...
828
33002204 12/2010
List of symbols and short cut keys
Icons in PLC Configuration
Icons
The table shows the icons also available in PLC configuration and their allocated
menu commands (related topics: General icon bar, page 821):
Icon
Executed menu command
PLC configuration →PLC Selection...
PLC configuration →Memory Partitions...
PLC configuration →ASCII Setup...
PLC configuration →Loadables...
PLC configuration →Config. Extension...
PLC configuration →Segment scheduler...
PLC configuration →I/O Map...
PLC configuration →Data Protection...
PLC configuration →Peer Cop...
PLC configuration →Ethernet / I/O Scanner...
PLC configuration →Hot Standby...
PLC configuration →ASCII Port Settings...
PLC configuration →Modbus Port Settings...
PLC configuration →Specials...
33002204 12/2010
829
List of symbols and short cut keys
Toolbar in the RDE Editor
Icons
The table shows the icons also available in the RDE Editor and their allocated menu
commands (see also General icon bar, page 821):
Icon
Executed menu command
Template →New Template...
Template →Open Template...
Template →Save Template
Online →Animate
Online →Download Reference Data
Online →Get CSL
Online →Delete CSL
830
33002204 12/2010
List of symbols and short cut keys
Toolbar in the Project Browser
Icons
The table shows the additional symbols available in the project browser and the
corresponding menu commands (also see General icon bar, page 821):
Icon
Menu command executed
Project Shortcut Menu →Animate Enable States
Project Shortcut Menu →Show Detailed View
33002204 12/2010
831
List of symbols and short cut keys
C.2
Short cut keys
Description
This section describes the available short cut keys. There are editor independent
and editor dependent short cut keys.
What's in this Section?
This section contains the following topics:
Topic
832
Page
General Short Cut Keys
833
Short Cut Keys in the IL, ST and Data Type Editor
834
Short Cut Keys in the FBD and SFC Editor
837
Shortcut keys in the LD-Editor
841
Short Cut Keys in the LL984-Editor
847
33002204 12/2010
List of symbols and short cut keys
General Short Cut Keys
Short Cut Keys
The table shows the short cut keys available and the corresponding menu entry
command:
33002204 12/2010
Short Cut Keys
Menu Entry Command Executed
F1
Calls the context-sensitive online help. Use this key to call up an
explanation of the menu entry command or dialog chosen. In
dialogs, this key corresponds to the menu entry command Help.
Ctrl+F4
System menu (for the document window) →Close document
window
Ctrl+F6
System menu (for the document window) →Next
Ctrl+S
File →Save project/save DFB
Alt+F4
File →Quit the application window (Concept-Application)
F8
Project →Variable declarations...
F3
Project →Search
Shift+F3
Project →Trace
F5
Project →Search history...
F6
Project →Search next
Alt+F9
Project →Analyze section
Ctrl+P
Online →Online control panel...
F9
Online →Single sweep trigger
Ctrl+R
Online →Reference Data Editor
Shift+F5
Window →Cascade
Shift+F4
Window →Tile Vertically
833
List of symbols and short cut keys
Short Cut Keys in the IL, ST and Data Type Editor
Calling up menu command entries
The table shows the short cut keys available in the IL, ST and Data Type Editor and
the corresponding menu entry commands (see also General Short Cut Keys,
page 833):
834
Key
Menu Entry Command Executed
Ctrl+Z
Edit →Undo delete
Ctrl+X
Edit →Cut
Ctrl+C
Edit →Copy
Ctrl+V
Edit →Paste
Del
Edit →Delete
Ctrl+G
Edit →Goto line...
Ctrl+J
Edit →Goto counterpart
Ctrl+E
Edit →Expand statement
Alt+F8
Edit →Lookup variables
Ctrl+F
Edit →Find next
Ctrl+H
Edit →Replace...
Ctrl+Y
Online →Animate Booleans
Ctrl+I
Online →Inspect Selected
Ctrl+W
Online →Watch Selected
33002204 12/2010
List of symbols and short cut keys
Moving insertion marks in the text
Moving insertion marks in the text:
Key
Moving
Down
Onto the next line
Up
Onto the previous line
Ctrl+G
Onto a specific line
End
To the end of the line
Home
To the beginning of the line
Picture up
Into the next window
Picture up
Into the previous window
Ctrl+Right
To the next word
Ctrl+Left
To the previous word
Ctrl+End
To the end of the document
Ctrl+Home
To the beginning of the document
Deleting text
Deleting text:
33002204 12/2010
Key
Function
Backspace Key (Delete backwards)
Deleting a mark (or deleting marked text) to
the left of the insertion mark.
Del
Deleting a character (or deleting marked
text) to the right of the insertion mark.
Ctrl+Backspace key (Delete backwards)
Deleting a line
835
List of symbols and short cut keys
Marking text
Marking text:
Key
Extending the marking
Shift+Right
to the next character
Shift+Left
to the previous character
Ctrl+Shift+Right
to the next word
Ctrl+Shift+Left
to the previous word
Shift+Down
to the next line
Shift+Up
to the previous line
Shift+End
to the end of the line
Shift+Home
to the beginning of the line
Shift+Picture down
to a window underneath
Shift+Picture up
to a window above
Ctrl+Shift+Picture down
to the end of the current window
Ctrl+Shift+Picture up
to the beginning of the current window
Ctrl+Shift+End
to the end of the document
Ctrl+Shift+Home
to the beginning of the document
Editing text
Editing text:
836
Key
Function
Ctrl+X
Deleting marked text and saving in the
clipboard
Ctrl+C
Copying marked text and saving in the
clipboard
Entering the new text
Replacing marked text
Del
Deleting marked text without saving in the
clipboard
Ctrl+V
Replacing marked text with text from the
clipboard.
Ctrl+F
Searching for text
Ctrl+R
Replacing text
33002204 12/2010
List of symbols and short cut keys
Short Cut Keys in the FBD and SFC Editor
At a Glance
Concept supports the work with the keyboard in the graphic editors. Although the
mouse is a more appropriate input tool, it is nevertheless possible to operate
Concept with the keyboard alone – especially in machine environments. The editors
behave in the same way regardless of whether they are operated with the mouse or
with the keyboard.
Rules
The following general rules need to be observed:
z The space bar corresponds to the left mouse button, i.e. the space bar is used for
selecting and moving.
z The enter key corresponds to the double click with the left mouse button – for
example, the input key is used to call up the properties dialog of objects.
z The shift key is used in conjunction with the keyboard exactly as it is with the
mouse – for example, the shift key is used to extend an object selection or to
reselect a few objects from a number which have already been selected.
Calling up menu command entries
The table shows the short cut keys available in the FBD and SFC editor and the
corresponding menu entry commands (see also General Short Cut Keys,
page 833):
33002204 12/2010
Key
Menu Entry Command Executed
Ctrl+A
Edit →Select All
Ctrl+Z
Edit →Undo delete
Ctrl+X
Edit →Cut
Ctrl+C
Edit →Copy
Ctrl+V
Edit →Paste
Del
Edit →Delete
Ctrl+O
View →Overview
Ctrl+N
View →Normal
Ctrl+E
View →Expanded (only in SFC)
Ctrl++
View →Zoom in
Ctrl+-
View →Zoom out
Ctrl+Y
In the FBD Editor: Online →Animate booleans
In SFC-Editor: Online →Animate
Ctrl+W
Online →Animate selected (in FBD)
837
List of symbols and short cut keys
Moving the cursor
Moving the cursor:
Key
Function
Cursor keys
The cursor keys move the cursor inside the document window. The
cursor is moved further around a Pixel. If the cursor is at the edge of
the document window, pressing the cursor keys again will page the
document window in the corresponding direction.
Ctrl+Cursor Keys
When the Strg key is pressed, the cursor keys move the cursor
inside the document window. The cursor is moved further around a
logical unit (depending on the active editor). If the cursor is at the
edge of the document window, pressing the cursor keys again will
page the document window in the corresponding direction
Home
The Pos1 key moves the cursor to the left-hand edge of the document
window.
End
The End key moves the cursor to the right-hand edge of the
document window.
Scrolling
Scrolling:
838
Key
Function
Ctrl+Home
When the Ctrl key is pressed, the Pos1 key moves the document
window to the upper left-hand corner of the section.
Ctrl+End
When the Ctrl key is pressed, the End key moves the document
window to the lower right-hand corner of the section.
Picture up
The picture up key scrolls the document window one screen page
upwards, while the cursor remains in the same position in the
document window.
Picture down
The picture down key scrolls the document window one screen page
downwards, while the cursor remains in the same position in the
document window.
Ctrl+Picture up
When the Ctrl key is pressed, the Picture up key scrolls the
document window one page to the left while the cursor remains in the
same place in the document window.
Ctrl+Picture down
When the Ctrl key is pressed, the Picture down key scrolls the
document window one page to the right while the cursor remains in
the same place in the document window.
33002204 12/2010
List of symbols and short cut keys
Edit
Edit
Key
Function
Space bar
In select mode, the object at the cursor position is selected and all
other objects are deselected.
In placing mode the corresponding object is placed where the cursor
is.
Shift key+Space
bar
In selection mode, when the Shift key is pressed, objects which have
not previously been selected in the cursor position are selected, or
vice versa. The selection of all other objects is not affected.
In placing mode the corresponding object is placed where the cursor
is.
Space bar+Cursor
Keys
In selection mode – if there is no selected object where the cursor is
– the cursor moves and a selection rectangle is displayed. If a
selected object is in the cursor position, all objects will be shifted
according to how the cursor is moved.
The number of inputs of an FFB with a variable input number can be
changed in the FB Editor’s Selection Mode by placing the cursor on
the rectangle in the middle of the lower edge of the selection frame,
which holds down the Space bar and presses the Up or Down keys.
The width of the branches or connections can be changed in the SFC
Editor’s Selection Mode by placing the cursor on the rectangle of the
selection frame, which holds down the Space bar and presses the
Right or Left keys.
In Link Mode, a link is produced by dragging the mouse.
Shift key+Space
bar+Cursor keys
In Selection Mode, this key combination creates a selection frame as
described above, and the selection of all other objects is retained.
Allocating variables onto an FFB
To allocate variables onto an FFB, do the following:
Step
33002204 12/2010
Action
1
Use the cursor keys or Shift+cursor keys to move the cursor to the
input/output of the FFB.
2
Press Enter.
Reaction: The Connect FFB dialog for the selected input/output opens.
839
List of symbols and short cut keys
Changing variables onto an FFB
To change variables onto an FFB, do the following:
Step
Action
1
Use the cursor keys or Shift+cursor keys to move the cursor to the FFB
variables to be changed.
2
Press Enter.
Reaction: The Connect FFB dialog for the selected input/output opens.
Changing the number of inputs/outputs
To change the number of inputs/outputs with extendable FFBs, do the following:
Step
840
Action
1
Use the cursor keys or Shift+cursor keys to move the cursor to the centre of
the lower edge of the FFB’s block frame.
2
Press Space bar+Down cursor key to generate further inputs/outputs.
Press Space bar+Up cursor key to hide further inputs/outputs.
Reaction: The number of inputs/outputs is changed.
33002204 12/2010
List of symbols and short cut keys
Shortcut keys in the LD-Editor
At a Glance
Concept supports the work with the keyboard in the graphic editors. Although the
mouse is a more appropriate input tool, it is nevertheless possible to operate
Concept with the keyboard alone – especially in machine environments. The Editors
behave in the same way regardless of whether they are operated with the mouse or
with the keyboard.
Rules
The following general rules need to be observed:
z The space bar corresponds to the left mouse button, i.e. the space bar is used for
selecting and moving.
z The Enter key corresponds to the double click with the left mouse button – for
example, the input key is used to call up the properties dialog of objects.
z The Shift key is used in conjunction with the keyboard exactly as it is with the
mouse – for example, the Shift key is used to extend an object selection or to
reselect a few objects from a number which have already been selected.
z Pressing a key only once only affects the element in the center of the current cell.
z Pressing a key together with Ctrl affects the right side of the current cell..
z Striking a key together with Shift afects the left side of the current cell
Calling up menu command
The table shows the additional shortcut keys and their corresponding menu
commands avialable in LD Editor (see also General Short Cut Keys, page 833):
33002204 12/2010
Key
Menu Entry Command Executed
Ctrl+A
Edit →Select All
Ctrl+Z
Edit →Undo delete
Ctrl+X
Edit →Cut
Ctrl+C
Edit →Copy
Ctrl+V
Edit →Paste
Del
Edit →Delete
Ctrl+O
View →Overview
Ctrl+N
View →Normal
Ctrl++
View →Zoom in
Ctrl+-
View →Zoom out
Esc
Objects →Select
Shift+H
Objekts →Link
H
Objects →Direct Link
841
List of symbols and short cut keys
Key
Menu Entry Command Executed
V
Objects →Vertical Link
F
Objects →FFB: Last Type
I
Objects →Invert Input/Output
T
Objects →Text
Shift+F
Objects →FFB selection...
C
Objects →Contact Normally Open
L
Objects →Contact – Normally Closed
P
Objects →Contact - Rising Edge (Positive)
N
Objects →Contact - Falling Edge (Negative)
Shift+C
Objects →Coil
Shift+L
Objects →Coil - Negated
Shift+S
Objects →Coil - Set
Shift+R
Objects →Coil - Reset
Shift+P
Objects →Coil - Rising Edge (Positive)
Shift+N
Objects →Coil - Falling Edge (Negative)
Ctrl+Y
Online →Animate booleans
Ctrl+W
Online →Animate selected
Placing objects
In order to place objects in the LD Editor by using the keyboard, please carry out the
following steps:
Step
842
Action
1
Move the field with a gray background onto the field where the object is to be
placed (move gray field (selecting a field)).
2
Strike the key assigned to the object (see Creating objects, page 845).
Reaction: Adjoining boolean objects are automatically connected.
3
Links between non-adjoining objects and non-boolean in/outputs have to be
made with the mouse pointer (see Moving the mouse pointer, page 845).
4
The mouse pointer must also be used to invert in/outputs (see Moving the mouse
pointer, page 845).
33002204 12/2010
List of symbols and short cut keys
Moving the gray field (selecting a field)
Moving the gray field (selecting a field)
Key
Function
Up
Moves the gray field up by one field
Down
Moves the gray field down by one field
To the right
Movesthe gray fields to the right by one field
To the left
Moves the gray fields to the left by one field
Home
Moves the gray field to the left margin
Shift+Home
Moves the gray field to the left margin
End
Moves the gray field to the right margin
Shift+End
Moves the gray field to the right margin
Ctrl+Home
Moves the gray field to the top left-hand
corner
Ctrl+End
Moves the gray field to the top right-hand
corner
Selecting objects
Selecting objects
33002204 12/2010
Key
Function
Space character
Selects object in the middle of the gray field
Ctrl+Space character
Selects object on the right-hand side of the
gray field
Shift+Space character
Selects object on the left-hand side of the
gray field
Enter
In select mode: Selects object in the middle
of the gray field and opens its Select dialog (if
available)
Ctrl+Enter
In select mode: Selects object from the righthand side of the gray field and opens its
Select dialog (if available)
Shift+Enter
In select mode: Selects object from the lefthand side of the gray field and opens its
Select dialog (if available)
843
List of symbols and short cut keys
Moving a selected object
Moving a selected object
Key
Function
Shift+Up
Moves the selected object up by one field
Shift+Down
Moves the selected object down by one field
Shift+Right
Moves the selected object to the right by one
field
Shift+Left
Moves the selected object to the left by one
field
Allocating variables onto an FFB
To allocate variables onto an FFB, do the following:
Step
Action
1
Move the gray field onto the cell containing the in/output.
2
To allocate variables to inputs, press Ctrl+Enter.
To allocate variables to outputs press Ctrl+Enter.
Reaction: The dialog Connect FFB of the selected in/output is opened.
Changing variables onto an FFB
To change variables onto an FFB, do the following:
Step
Action
1
Move the gray field onto the cell containing the variable to be changed.
2
To select the variable press Shift+Enter.
Reaction: The dialog Connect FFB of the selected in/output is opened.
Deleting vertical links
To delete vertical variables, carry out the following step:
Step
844
Action
1
Move the gray field onto the cell running through the vertical link.
2
Press Ctrl+Delete.
Reaction: The vertical link is deleted.
33002204 12/2010
List of symbols and short cut keys
Moving the mouse pointer
Moving the mouse pointer
Key
Function
Ctrl+Up
Moving the mouse pointer up by one step
Ctrl+Down
Moving the mouse pointer down by one step
Ctrl+Right
Moving the mouse pointer to the right by one
step
Ctrl+Left
Moving the mouse pointer to the left by one
step
Scrolling
Scrolling:
Key
Function
Picture up
Scrolls the display sector one page up
Shift+Picture up
Scrolls the display sector one page up
Picture down
Scrolls the display sector one page down
Shift+Picture down
Scrolls the display sector one page down
Ctrl+Picture up
Scrolls the display sector one page to the
right
Ctrl+Picture down
Scrolls the display sector one page to the
right
Creating objects
Creating objects
33002204 12/2010
Key
Function
C
Creates a N.O. in the gray field
L
Creates an opener in the gray field
P
Creates a contract for the recognition of
positive flanks in the gray field
N
Creates a contract for the recognition of
negative flanks in the gray field
Shift+C
Creates a coil in the gray field
Shift+L
Creates a negated coil in the gray field
Shift+S
Creates a coil set in the gray field
Shift+R
Creates a reset coil in the gray field
845
List of symbols and short cut keys
Key
Function
Shift+P
Creates a coil for the recognition of positive
flanks in the gray field
Shift+N
Creates a coil for the recognition of negative
flanks in the gray field
Shift+F
Opens FFB selection dialog
F
Creates current FFB in the gray field
Creating links
Creating links
Key
Function
H
Activates the link mode
V
Creates a vertical link in the right-hand
bottom corner of the gray field (and then
moves the gray field to the right by one field)
Shift+V
Creates a vertical link in the bottom left-hand
corner of the gray field.
Activating the different modes
Activating the different modes
846
Key
Function
Space character
Activates the selection mode
Esc
Activates the selection mode
H
Activates the link mode
I
Activates the mode for inverting in/outputs
T
Activates the text mode
33002204 12/2010
List of symbols and short cut keys
Short Cut Keys in the LL984-Editor
Short Cut Keys
The table shows the additional short cut keys available in the LL984 editor and the
corresponding menu entry commands (see also General Short Cut Keys,
page 833):
33002204 12/2010
Short Cut Keys
Menu Entry Command Executed
Ctrl+Z
Edit →Undo delete
Ctrl+X
Edit →Cut
Ctrl+C
Edit →Copy
Ctrl+V
Edit →Paste
Del
Edit →Delete
Ctrl+D
Edit →DX Zoom...
Ctrl+H
Edit →Offset References...
Ctrl+O
View →Overview
Ctrl+N
View →Normal
Ctrl+E
View →Expanded
Ctrl++
View →Zoom in
Ctrl+-
View →Zoom out
(
Objects →Coil
Ctrl+L
Objects →Coil - Retentive
"
Objects →Contact – Normally Open
/
Objects →Contact – Normally Closed
P
Objects →Contact – Pos Trans
N
Objects →Contact – Neg Trans
=
Objects →Horiz Short
I
Objects →Vertical Short
Ctrl+F
Objects →Instruction by name...
Ctrl+G
Network →Goto...
Ctrl+I
Networks →Insert
Ctrl+Q
Networks →Insert Equation
Ctrl+A
Networks →Append
Ctrl+U
Networks →Attach formula
Ctrl+K
Networks →Delete
Picture up
Networks →Next
847
List of symbols and short cut keys
Short Cut Keys
848
Menu Entry Command Executed
Picture up
Networks →Previous
Ctrl+M
Networks →Comment...
Ctrl+T
Online →Trace
Ctrl+B
Online →ReTrace
33002204 12/2010
IEC conformity
33002204 12/2010
IEC conformity
D
Overview
This Chapter contains the standards tables required by IEC 1131-1.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
D.1
What is the IEC 1131-3 standard?
850
D.2
IEC standards tables
853
D.3
Expansions of IEC 1131-3
873
D.4
Text language syntax
875
849
IEC conformity
D.1
What is the IEC 1131-3 standard?
Overview
This section contains general information about IEC 1131-3 and the implemented
IEC conformity test.
What's in this Section?
This section contains the following topics:
Topic
850
Page
General information about IEC conformity
851
IEC Conformity Test
852
33002204 12/2010
IEC conformity
General information about IEC conformity
At a Glance
The IEC standard 1131-3 (compare chapter 1.4) specifies the syntax and semantics
of a standardized series of programming languages for Programmable Logic
Controls (PLC). These include the two text languages IL (Instruction List) and ST
(Structured Text) and the two graphical languages LD (Ladder Diagram) and FBD
(Function Block Diagram).
It also defines the elements of the sequential function chart (SFC) language for
structuring the internal organization of PLC programs and Function Blocks.
Configuration elements, used for installing PLC programs onto PLC systems, are
also defined.
NOTE: Concept uses the English acronyms for the programming languages.
Furthermore, it defines methods to enable communication between the PLC and
other automated system components.
Concept standard accordance
In accordance with the standard, the present version of the programming system
Concept supports a subset of language elements, which are defined in the standard.
In this context, accordance with the standard means the following:
z The standard allows the individual implementing an IEC program system to select
or deselect certain language properties or even complete languages from the
selection tables, which represent an integrated part of the standard
specifications. A system, which itself accords with the standard, may only
implement the selected properties exactly as they are given in the standard.
z In addition, the standard enables the individual implementing to introduce defined
language elements into an interactive programming environment. As the
standard expressly emphasizes that the specification of such environments lies
outside of its area of application, the person implementing has a certain degree
of freedom to offer optimized forms of display and implementation mechanisms
for the benefit of the user.
z Concept uses these degrees of freedom e.g. when introducing the term "Project"
to implement the IEC language elements "Configuration", "Resource" and
"Program" all together (Concept only supports one single cyclically running
program within a single resource within the configuration). Apart from this, it uses
them, for example, with implementation mechanisms made available for
declaring variables and authorizing Function Blocks.
IEC standards tables
Information on which properties are supported and other implementation specific
details can be found in the following statements on standard fulfilment and the
associated standards tables.
33002204 12/2010
851
IEC conformity
IEC Conformity Test
Testing the Import/Export Interface
An interface for importing standard IEC programs and DFBs from ASCII files (menu
File →Import) and exporting these programs into graphical languages in ASCII
format (menu File →Export) is available in Concept. The conformity of this
interface can be tested using files which can be obtained from IFAK (Institut für
Automation und Kommunikation e.V. Magdeburg).
IEC conformity test scripts:
(c) 1994, IFAK Institut für Automation und Kommunikation e.V.
Magdeburg
Steinfeldstraße 3
D-39179 Barleben
Notes
The following points must be considered with regard to the conformity of the import
interface:
z In Concept, IL operators are permitted as identifiers.
R, S, LD, S1 and R1 are possible parameter names. Therefore, there will be no
changes made to the standard functions/function blocks. Concept requires no
change in the IEC table 54 with S to SET, R to RESET, S1 to SET1, R1 to
RESET1.
z All IL operators not in conflict with functions are permitted as variable names in
Concept (N, S, R, S1, R1, CLK, CU, CD, PV, IN, PT) – contrary to IEC table 54.
z Counter EFBs must be typified in Concept, e.g. CTU must become CTU_INT.
z Function block instances cannot be called up more than once; a restriction that is
self-evident if IEC table 53, property 3 is required.
z An overflow of time span variables (e.g. t#100s) is not detected. The system
calculates the time correctly, so that detection of an overflow is not necessary.
z IEC IL comments are only permitted as the last element in a line. Concept allows
comments to be made everywhere.
852
33002204 12/2010
IEC conformity
D.2
IEC standards tables
Overview
This system fulfils the requirements of the IEC 1131-3 in the following properties of
the language.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
Common elements
854
IL (AWL) language elements
861
ST language elements
863
Common graphic elements
865
LD (KOP) language elements
866
Implementation-dependent parameters
868
Error causes
871
853
IEC conformity
Common elements
IEC standards table
IEC standards table for common elements:
854
Table
number
Property
number
Property description
1
1
For required character set – see Chapter 2.1.1 of 1131-3
1
2
Lower case characters
1
3a
Hash key (#)
1
4a
Dollar sign ($)
1
5a
Vertical line (|)
1
6a
Left and right square brackets "[ ]"
2
1
Upper case character and numbers
2
2
Upper and lower case characters, numbers, embedded
underscore
2
3
Upper and lower case characters, numbers, leading and
embedded underscore
3
1
Comments
4
1
Integer (whole number) literals
4
2
Real literals
4
3
Real literals with exponents
4
4
Base 2 literals
4
5
Base 8 literals
4
6
Base 16 literals
4
7
Boolean zero and one
4
8
Boolean FALSE and TRUE
7
1a
Time span without underscores: short prefix
7
1b
Time span without underscores: long prefix
7
2a
Time span with underscores short prefix
7
2b
Time span with underscores long prefix
10
1
BOOL: Boolean
10
3
INT: Integer
10
4
DINT: Double integer
10
7
UINT: Signed integer
10
8
UDINT: Signed double integer
10
10
REAL: Floating point number
33002204 12/2010
IEC conformity
33002204 12/2010
Table
number
Property
number
Property description
10
12
TIME: Time span
10
17
BYTE: Bit sequence 8
10
18
WORD: Bit sequence 16
12
4
Data types for fields
12
5
Data types for structures
15
1
I: Input (Note 1, page 859)
15
2
Q: Output (Note 2, page 859)
15
4
X: Bit size (Note 2, page 859, Note 1, page 859)
15
5
no prefix: Bit size (Note 2, page 859, Note 1, page 859)
15
6
B: Byte size (Note 2, page 859, Note 1, page 859)
15
7
W: Word size (Note 2, page 859, Note 1, page 859)
15
8
D: Double word size (Note 2, page 859, Note 1, page 859)
17
2
Declaration of directly displayed buffered variables (Note 5,
page 860, Note 9, page 860)
17
3
Declaration of storage locations with symbolic variables (Note
5, page 860)
17
4
Assignment of storage locations with fields (Note 5, page 860,
Note 11, page 860)
17
5
Automatic storage allocation for symbolic variables (Note 5,
page 860)
17
7
Declaration for buffered fields (Note 5, page 860, Note 11,
page 860)
17
8
Declaration for structured variables (Note 5, page 860)
18
2
Initialization of directly displayed buffered variables (Note 5,
page 860, Note 9, page 860, Note 10, page 860)
18
3
Assignment of storage locations and start values for
fields(Note 5, page 860)
18
4
Assignment of storage locations and start values for fields
(Note 5, page 860, Note 11, page 860)
18
5
Initialization of symbolic variables (Note 5, page 860)
18
7
Declaration and initialization of buffered variables (Note 5,
page 860, Note 11, page 860)
18
8
Initialization of structured variables (Note 5, page 860)
18
9
Initialization of constants
19
1
Negated input
19
2
Negated output
855
IEC conformity
856
Table
number
Property
number
Property description
20
1
Use of "EN" and "ENO" - REQUIRED for LD (Note 6,
page 860)
20
2
Use of "EN" and "ENO" – OPTIONAL for FBD
20
3
FBD without "EN" and "ENO"
21
2
Standardized functions (Note 3, page 859)
22
1
(*-TO-**) Type conversion functions (Note 4, page 859
22
2
Truncation towards zero: TRUNC (Note 3, page 859))
23
1
ABS: Absolute value
23
2
SQRT: Square root
23
3
LN: Natural logarithm
23
4
LOG: Base 10 logarithm
23
5
EXP: Exponential function
23
6
SIN: Sine, input in radians
23
7
COS: Cosine, input in radians
23
8
TAN: Tangent, input in radians
23
9
ASIN: Arc sine, principal value
23
10
ACOS: Arc cosine, principal value
23
11
ATAN: Arc tangent, principal value
24
12
ADD: Add
24
13
MUL: Multiply
24
14
SUB: Subtract
24
15
DIV: Divide
24
16
MOD: Modulo
24
17
EXPT: Exponentiation
24
18
MOVE: Assignment
25
1
SHL: move to the left
25
2
SHR: Move to the right
25
3
ROR: Rotate to the right
25
4
ROL: Rotate to the left
26
5
AND: LLogical And
26
6
OR: Logical Or
26
7
XOR Logical exclusive Or
26
8
NOT: Negation
27
1
SEL: Binary selection
33002204 12/2010
IEC conformity
Table
number
33002204 12/2010
Property
number
Property description
27
2a
MAX: Extendable maximum
27
2b
MIN: Extendable minimum
27
3
LIMIT: Limit
27
4
MUX: Extendable multiplexer
28
5
GT: Falling sequence
28
6
GE: Monotonic sequence (decreasing)
28
7
EQ: Equality
28
8
LE: Monotonic sequence (increasing)
28
9
LT: Rising seqence
28
10
NE: Inequality
30
1
ADD: Adding TIME to TIME
30
4
SUB: Subtracting TIME from TIME
30
10
MUL: Multiplying TIME by ANY_NUM
30
11
DIV: Dividing TIME by ANY_NUM
33
1
RETAIN identifier for internal variables (Note 5, page 860)
33
2
RETAIN identifier for output variables (Note 5, page 860)
33
3
RETAIN identifier for internal Function Blocks (Note 5,
page 860)
34
1
Bistable Function Block (set priority)
34
2
Bistable Function Block (reset priority)
35
1
Detecting the rising edge
35
2
Detecting the falling edge
36
1
Up counter
36
2
Down counter
36
3
Up/Down counter
37
1
TP: Pulse (timer)
37
2a
TON: Switch-on delay
37
3a
TOF: Switch-off delay
39
1
RETAIN identifier for internal variables (Note 5, page 860)
39
2
RETAIN identifier for output variables (Note 5, page 860)
39
3
RETAIN identifier for internal Function Blocks (Note 5,
page 860)
39
14
Assignment of storage locations with fields (Note 5, page 860)
857
IEC conformity
858
Table
number
Property
number
Property description
39
18
Assignment of storage locations and start values for
fields(Note 5, page 860)
39
19
Use of directly displayed variables (Note 2, page 859, Note 1,
page 859)
40
1
Step/Start step – graphical form with directional links
40
2
Step/Start step – text form without directional links (Note 8)
40
3a
Step marker – general form
40
4
Step time elapsed – general form
41
1
Transition condition in ST language within the graphic (Note
8, page 860)
41
5
Transition condition in ST language – textual reference (Note
9, page 860)
41
6
Transition condition in IL language – textual reference (Note
9, page 860)
41
7
Use of the transition name
41
7b
Transition condition in FBD language
41
7c
Transition condition in IL language
41
7d
Transition condition in ST language
42
1
Each Boolean variable can be an action
43
1
Action block
43
2
Concatenated action blocks
43
3
Step body in text form (Note 8, page 860)
44
1
Identifier
44
2
Action name
45
1
Not saved (no identifier)
45
2
N: not saved
45
3
R: Overriding reset
45
4
S: Set (saved)
45
5
L: Time limited
45
6
D: Delayed
45
7
P: Pulse
45
9
DS: Delayed and saved
46
1
Simple string
46
2a
Branching in string selection (priority from left to right)
46
3
Merging a string selection
33002204 12/2010
IEC conformity
Table
number
Property
number
Property description
46
4
Parallel strings - branch and merge
46
5a
String jump (priority from left to right)
46
6a
String loop (priority from left to right)
Note 1
Modicon TSX Quantum Präfix 3 is used in the prefix IB, ID position in all graphical
languages.
Note 2
Modicon TSX Quantum Präfix 4 is used in the prefix QB, QD position in all graphical
languages.
Note 3
The following functions are overloaded with reference to the data which is selected,
multiplexed or assigned; the type statement refers to the selection parameters.
List of overloaded functions:
z SEL
z MUX
z MOVE
All other functions are standardized, e.g. REAL_TRUNC_INT.
Note 4
List of type conversion functions:
BOOL_TO_BYTE, BOOL_TO_DINT, BOOL_TO_INT, BOOL_TO_REAL,
BOOL_TO_TIME, BOOL_TO_UDINT, BOOL_TO_UINT, BOOL_TO_WORD,
z BYTE_TO_BOOL, BYTE_TO_DINT, BYTE_TO_INT, BYTE_TO_REAL,
BYTE_TO_TIME, BYTE_TO_UDINT, BYTE_TO_UINT, BYTE_TO_WORD,
z DINT_TO_BOOL, DINT_TO_BYTE, DINT_TO_INT, DINT_TO_REAL,
DINT_TO_TIME, DINT_TO_UDINT, DINT_TO_UINT, DINT_TO_WORD,
z INT_TO_BOOL, INT_TO_BYTE, INT_TO_DINT, INT_TO_REAL,
INT_TO_TIME, INT_TO_UDINT, INT_TO_UINT, INT_TO_WORD,
z REAL_TO_BOOL, REAL_TO_BYTE, REAL_TO_DINT, REAL_TO_INT,
REAL_TO_TIME, REAL_TO_UDINT, REAL_TO_UINT, REAL_TO_WORD,
z TIME_TO_BOOL, TIME_TO_BYTE, TIME_TO_DINT, TIME_TO_INT,
TIME_TO_REAL, TIME_TO_UDINT, TIME_TO_UINT, TIME_TO_WORD,
z UDINT_TO_BOOL, UDINT_TO_BYTE, UDINT_TO_DINT, UDINT_TO_INT,
UDINT_TO_REAL, UDINT_TO_TIME, UDINT_TO_UINT, UDINT_TO_WORD,
z
33002204 12/2010
859
IEC conformity
z
z
UINT_TO_BOOL, UINT_TO_BYTE, UINT_TO_DINT, UINT_TO_INT,
UINT_TO_REAL, UINT_TO_TIME, UINT_TO_UDINT, UINT_TO_WORD,
WORD_TO_BOOL, WORD_TO_BYTE, WORD_TO_DINT, WORD_TO_INT,
WORD_TO_REAL, WORD_TO_TIME, WORD_TO_UDINT, WORD_TO_UINT
The consequences of each conversion are described in the block library and the
help texts, which are available for the library of IEC standard functions.
Note 5
The RETAIN identifier is implicitly required; no language elements displayed in nonbuffered memory areas are supported.
Note 6
"EN" and "ENO" are offered as standard; they can, however, be hidden and any
other input or output of data type BOOL can be used for links.
Note 7
Expressions are restricted to individual simple Boolean variables.
Note 8
Only available on import of IEC text form in graphical SFC representation.
Note 9
Only available in textual declaration in IL or ST sections.
Note 10
Initialization only possible for non Boolean outputs.
Note 11
Declaration of field variables only possible when using previously defined field data
type names.
860
33002204 12/2010
IEC conformity
IL (AWL) language elements
IEC standards table
IEC standards table for IL (AWL) language elements:
Table
number
Property
number
Property description
52
1
LD operator: sets the current result to that of the operand
52
2
ST operator: saves the current result to the operand address
52
3
S operator: sets Boolean operands to "1"
R operator: sets Boolean operands to "0"
52
4
AND operator
52
6
OR operator
52
7
XOR operator
52
8
ADD operator
52
9
SUB operator
52
10
MUL operator
52
11
DIV operator
52
12
GT operator: Comparison >
52
13
GE operator: Comparison >=
52
14
EQ operator: Comparison =
52
15
NE operator: Comparison <>
52
16
LE operator: Comparison <=
52
17
LT operator: Comparison <
52
18
JMP operator: Jump to tag (Note 1, page 861)
52
19
CAL operator: Calls Function Block
52
21
Closing bracket ")": Editing deferred operations
53
1
CAL operator with list of input parameters
53
2
CAL operator with loading/saving of input parameters
Note 1
Jumps are only allowed within sections, not across section boundaries.
33002204 12/2010
861
IEC conformity
Note 2
The following keywords are not available:
TYPE...END_TYP
z VAR_INPUT...END_VAR
z VAR_OUTPUT...END_VAR
z VAR_IN_OUT...END_VAR
z VAR_EXTERNAL...END_VAR
z FUNCTION...END_FUNCTION
z FUNCTION_BLOCK...END_FUNCTION_BLOCK
z PROGRAM...END_PROGRAM
z STEP...END_STEP
z TRANSITION...END_TRANSITION
z ACTION...END_ACTION
z SEGMENT_SCHEDULER
z RET
z &
z
862
33002204 12/2010
IEC conformity
ST language elements
IEC standards table
IEC standards table for ST language elements:
33002204 12/2010
Table
number
Property
number
Property description
55
1
Placing in brackets: ( Expression )
55
2
Function calls: Function name ( list of arguments )
55
3
Exponentiation: **
55
4
Negation: -
55
5
Complement: NOT
55
6
Multiplication: *
55
7
Division: /
55
8
Modulo: MOD
55
9
Addition: +
55
10
Subtraction: -
55
11
Comparison: <, >, <=, >=
55
12
Equality: =
55
13
Inequality: <>
55
14
Boolean AND: &
55
15
Boolean AND: AND
55
16
Boolean exclusive OR: XOR
55
17
Boolean OR: OR
56
1
Assignment
56
2
Function Block calls and use of FB outputs
56
4
IF instruction
56
5
CASE instruction
56
6
FOR instruction
56
7
WHILE instruction
56
8
REPEAT instruction
56
9
EXIT instruction
56
10
Empty instruction
863
IEC conformity
Note 1
The following keywords are not available:
TYPE...END_TYP
z VAR_INPUT...END_VAR
z VAR_OUTPUT...END_VAR
z VAR_IN_OUT...END_VAR
z VAR_EXTERNAL...END_VAR
z FUNCTION...END_FUNCTION
z FUNCTION_BLOCK...END_FUNCTION_BLOCK
z PROGRAM...END_PROGRAM
z STEP...END_STEP
z TRANSITION...END_TRANSITION
z ACTION...END_ACTION
z SEGMENT_SCHEDULER
z RETURN
z
864
33002204 12/2010
IEC conformity
Common graphic elements
IEC standards table
IEC standards table for common graphic elements:
33002204 12/2010
Table
number
Property
number
Property description
57
2
Horizontal lines: Graphic or semi-graphic
57
4
Vertical lines: Graphic or semi-graphic
57
6
Horizontal/vertical connection: Graphic or semi-graphic
57
8
Line intersection without connection: Graphic or semi-graphic
57
10
Connected and unconnected corners: Graphic or semigraphic
57
12
Blocks with connecting lines: Graphic or semi-graphic
865
IEC conformity
LD (KOP) language elements
IEC standards table
IEC standards table for LD (KOP) language elements:
Table
number
Property
number
Property description
59
1
Left power rail (with linked horizontal connection)
60
1
Horizontal connection
60
2
Vertical connection (with linked horizontal connections)
61
1
Closer
61
3
Opener
61
5
Contact for detection of positive transition
61
7
Contact for detection of negative transition
62
1
Coil (Note 1, page 866)
62
2
Negative coil (Note 1, page 866)-{}-
62
3
SET coil (Note 1, page 866)
62
4
RESET coil (Note 1, page 866)
62
8
Coil for detection of positive transition
62
9
Coil for detection of negative transition
Note 1
In start behavior of PLCs there is a distinction between cold starts and warm starts:
Cold start
Following a cold start (loading the program with Online →Load) all variables
(irrespective of type) are set to "0" or, if available, their initial value.
z Warm start
In a warm start (stopping and starting the program or Online →Load changes)
different start behaviors are valid for located variables/direct addresses and
unlocated variables:
z Located variables/direct addresses
In a warm start all 0x, 1x and 3x registers are set to "0" or, if available, their
initial value.
4x registers retain their current value (storage behavior).
z Unlocated variables
In a warm start all unlocated variables retain their current value (storing
behavior).
z
866
33002204 12/2010
IEC conformity
This varying behavior in a warm start leads to peculiarities in the warm start behavior
of set and reset functions.
z Set and Reset in LD and IL
Warm start behavior is dependent on the variable type used (storage behavior in
use of unlocated variables; non storage behavior in use of located
variables/direct addresses)
z SR and RS Function Blocks in FBD, LD, IL and ST
These Function Blocks work with internal unlocated variables and therefore
always have a storage behavior.
33002204 12/2010
867
IEC conformity
Implementation-dependent parameters
IEC standards table
IEC standards table for implementation-dependent parameters:
Parameters
Threshold values/behavior
Error-handling procedure
See Error causes, page 871 & EFB
help
National characters used
All characters in the Windows ANSI
character set are supported.
Maximum length of identifiers
Program name: 8
Formal parameter names: 8
DFB type names: 8
EFB type names: 17
Data type names: 24
all others: 32
Maximum comment length:
Limited only by Windows resources
Range of values for time span literals
0s to 49d_17h_2m_47.295s
Range of values for variables of type TIME
0s to 49d_17h_2m_47.295s
868
Accuracy of the seconds display with types
TIME_OF_DAY and DATE_AND_TIME
not applicable
Maximum number of field indices
Practically no limit
Maximum field size
64 kB
Maximum number of structure elements
Only limited by Windows or PLC
resources
Maximum structure size
64 kB
Maximum number of variables per declaration
Only limited by Windows or PLC
resources
Maximum number of enumerated values
not applicable
Default maximum length of STRING variables
not applicable
Maximum authorized length of STRING variables
not applicable
Maximum number of hierarchy tiers
1
Configured or physical illustration
Configured illustration, physical
illustration through separate I/O
projection
Parameters
Threshold values/behavior
Maximum number of indices
Practically no limit
Maximum range of index values
Range of data type INT
33002204 12/2010
IEC conformity
33002204 12/2010
Parameters
Threshold values/behavior
Maximum number of structure levels
Only limited by Windows or PLC
resources
Initialization of system inputs
System zero; no user-definable start
values
Maximum number of variables per declaration
Only limited by Windows or PLC
resources
Information for the determination of execution times
of program organization units
In preparation
Methods of function display (names or symbols)
Names
Maximum number of function specifications
not applicable
Maximum number of inputs for extendable functions
32
Type conversion accuracy
See EFB help
Accuracy of functions of a variable
INTEL floating point processor or
emulator
Arithmetic function implementation
INTEL floating point processor or
emulator
Maximum number of Function Block specifications
Only limited by Windows or PLC
resources
Maximum number of Function Block authorizations
512 per section; number of sections
per program organization unit is only
limited by Windows or PLC resources
Pvmin, Pvmax of counters
Limited by rangess of the INT or
DINT data types
Effect of a change in the value of a PT input during a
time measurement operation
Directly affects the timer’s default
time
Program size limits
Only limited by available PLC
memory
Time behavior and porting effects of the execution
control elements
The execution of SFC networks in
different sections occurs
sequentially, in the order given in
these sections.
Accuracy of elapsed step time
10 ms
Maximum number of steps per SFC
Limited by the available area for
entering characters within the
section; number of sections per
program organization unit only
limited by Windows or PLC
resources; the upper limit for the total
number of objects per SFC is 2000
Parameters
Threshold values/behavior
869
IEC conformity
Parameters
Threshold values/behavior
Maximum number of transitions per SFC and per step Limited by the available area for
entering characters within the
section; number of sections per
program organization unit only
limited by Windows or PLC
resources; the upper limit for the total
number of objects per SFC is 2000
Action control mechanism
Functionally equivalent to the
specification in the standard
Maximum number of actions per step
Only limited by Windows or PLC
resources
Graphical display of the step situation
Green = active
Red = inactive
Transition switch time
Of the magnitude of 10 ms
Maximum width of branches/connections
Limited by the available area for
entering characters 32
Contents of the RESOURCE libraries
See EFB libraries & help
Maximum number of tasks
1
Task interval resolution
not applicable
Pre-justified and non pre-justified schedules
not applicable
Maximum length of expressions
Practically no limit
Partial evaluation of Boolean expressions
no partial evaluation
Maximum length of instructions
Practically no limit
Maximum number of CASE selections
Practically no limit
Value of the control variables on completion of FOR
loops
undefined
Graphic/semi-graphic display
Graphic
Network topology restrictions
no restrictions
Evaluation sequence of feedback loops
Within a network, the starting point of
the FFB execution sequence is
determined by the "single" available
feedback variable
Means of specifying the network execution sequence 1: Execution sequence of program
organization unit sections
2: The network execution sequence
can be changed within sections; this
is done by using a menu command to
switch between the execution
sequences of two selected FFB
items
870
33002204 12/2010
IEC conformity
Error causes
IEC standards table
IEC standards table for error causes:
Error cause
Handling (see Note 1, page 872)
Variable value exceeds the specified range
not applicable
Initialization list length and number of field
elements do not agree
2) Error message during programming
Incorrect use of directly displayed or external
variables in functions
not applicable
Type conversion error
4) Error message during execution
Numerical result exceeds the range for data
type
4) Error message during execution
Division by zero
4) Error message during execution
Mixed input data types in a selection function 2) Error message during programming
33002204 12/2010
Selector (K) outside MUX function range
4) Error message during execution
Invalid character position
not applicable
Result exceeds maximum sequence length
not applicable
Numerical result exceeds the range for data
type
4) Error message during execution
Zero or more than one starting step in SFC
network
3) Error message during
analysis/loading/connection
User program attempting to change step
situation or step time
2) Error message during programming
Simultaneously completed transitions without
priority in a selection branch
not applicable
Side effects of evaluation of a transition
condition
3) Error message during
analysis/loading/connection
Action control error
1) Error not reported
Unsafe or unreachable SFCs
3) Error message during
analysis/loading/connection
Data type conflict in VAR_ACCESS
not applicable
Tasks demanding too many processor
resources
3) Error message during
analysis/loading/connect
Scan time overrun
4) Error message during execution
Error cause
Handling (see note 1)
Further task schedule conflicts
not applicable
871
IEC conformity
Error cause
Handling (see Note 1, page 872)
Numerical result exceeds the range for data
type
4) Error message during execution
Division by zero
4) Error message during execution
Invalid data type for operation
3) Error message during
analysis/loading/binding
Return from function without assigned value
not applicable
Occurrence arrives at no outcome
4) Error message during execution
The same identifier as connector tag and
element name use
not applicable
Non-initialized feedback variable (initialized
with system zero)
1) Error not reported
Note 1
Identification for the handling of error causes according to IEC 1131-3, chapter
1.5.1, d):
z 1) Error not reported
z 2) Error message during programming
z 3) Error message during analysis/loading/binding
z 4) Error message during execution
872
33002204 12/2010
IEC conformity
D.3
Expansions of IEC 1131-3
Expansions of IEC 1131-3
At a Glance
The Concept programming environment makes the construct of the so-called
section available in all programming languages permitting the subdivision of a
program organization unit. This construct provides the opportunity to mix several
languages in the body of a POU (e.g. FBD sections, SFC sections), a property,
which, if used for this purpose, represents an expansion of the IEC syntax. Sections
do not generate their own name space; the name space for all language elements
is the POU.
Sections appearing in the body of a POU written only in the FBD language are not
to be viewed as an expansion, rather as a permitted means of specifying the
execution sequences of several FBD networks furnished with tags, as specified in
the corrigendum to 1131-3.
Purpose of sections
Sections serve various purposes
z Sections permit the functional division of an expansive POU body: The body of a
POU can be divided into sensible functional parts. The section list represents a
kind of functional table of contents for a large, otherwise unstructured POU body.
z Sections permit the graphical division of an expansive POU body: in accordance
with an intentionally graphic form of representation, sub-structures of an
expansive body can be established. Smaller or larger partial structures may be
chosen.
z The division of an expansive POU body enables faster online changes: the
section serves as the unit for online changes in Concept. If the POU body is
changed in various places during the program runtime, all sections affected by
the changes are taken into account if explicitly initiated reloading occurs.
33002204 12/2010
873
IEC conformity
z
z
874
Sections permit the execution sequence to influence particular marked parts of
the POU body: the section name serves as a marking for the part of the body
contained in the section, and the execution sequence of the sections can be
changed by ranking the sections (see also the last part of the "implementationdependent parameters" table for information on the execution sequence of
networks in the FBD language).
Sections permit the parallel use of different languages in the same POU: this
property is a considerable expansion of the syntax of the IEC 1131-3 standard,
which only permits the use of a single IEC language for a POU body. Only the
SFC language also provides the opportunity to formulate parts of the body in
different languages, because transitions and actions can be expressed in any
language, in as far as the corresponding properties are supported by the
programming system.
33002204 12/2010
IEC conformity
D.4
Text language syntax
Text Language Syntax
Description
The programming system Concept supports the complete language syntax, as
specified in appendix B of the IEC language standard 1131-3, with the following
exceptions:
z Syntax productions in appendix B of 1131-3, belonging to properties, which
according to the IEC standards tables in IEC standards tables, page 853 in this
document are not supported by Concept, are not implemented.
z The use of some Concept supported properties is, according to the associated
remarks in the IEC standards table, only possible in a restricted or modified form.
The associated syntax productions are therefore only occasionally or somewhat
differently implemented.
z Concept supports the NOT Operator for inverting Boolean battery content in IL.
z The implementation of some faulty syntax productions in appendix B of 1131-3,
improved upon either in the corrigendum to 1131-3 or in the planned amendment
to 1131-3, uses the suggestions in these documents for orientation.
The improved productions are implemented in Concept as follows (chapter
numbers refer to appendix B of 1131-3):
z B.1.3.3:
array_initialization ::= ’[’ array_initial_elements {’,’
array_initial_elements} ’]’
z
z
33002204 12/2010
initialized_structure ::= structure_type_name [’:=’
structure_initialization]
B.2.1:
il_operand_list ::= il_operand [’,’ [EOL] il_operand]
il_fb_call ::= (’CAL’ | ’CALC’ | ’CALCN’) fb_name ’(’
il_operand_list ’)’
B.2.2:
il_operator ::= ’LD’ | ’LDN’ | ’ST’ | ’STN’ | ’S’ | ’R’
| (’AND’ | ’ANDN’ | ’OR’ | ’ORN’ | ’XOR’ | ’XORN’) [’(’]
| (’ADD’ | ’SUB’ | ’MUL’ | ’DIV’) [’(’]
| (’GT’ | ’GE’ | ’EQ’ | ’NE’ | ’LT’ | ’LE’) [’(’]
| ’JMP’ | ’JMPC’ | ’JMPCN’ | ’)’ | function_name
875
IEC conformity
876
33002204 12/2010
Configuration examples
33002204 12/2010
Configuration examples
E
Overview
This section contains various configuration examples, given as step-by-step
instructions.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
Page
E.1
Quantum Example - Remote Control with RIO
E.2
Quantum Example - Remote control with RIO (series 800)
887
E.3
Quantum Example - Remote Control with DIO
900
E.4
Quantum Example – INTERBUS Control
910
E.5
Quantum Example - SY/MAX Controller
916
E.6
Quantum Example - Profibus DP Controller
925
E.7
Quantum-Example - Peer Cop
941
E.8
Compact Example
950
E.9
Atrium Example – INTERBUS Controller
955
E.10
Momentum Example - Remote I/O Bus
965
E.11
Momentum Example - Ethernet Bus System
974
878
877
Configuration examples
E.1
Quantum Example - Remote Control with RIO
Overview
This Chapter contains the step-by-step process for the configuration of remote
control with RIO (Remote I/O).
What's in this Section?
This section contains the following topics:
Topic
878
Page
Editing local drop
879
Editing Remote Drop
884
33002204 12/2010
Configuration examples
Editing local drop
Introduction
This section describes the configuration of the first (local) drop. The processing
sequence begins first of all with the definition of all drops.
When editing the first (local) drop the modules must be set with their I/O references
before the individual modules can be parameterized.
Quantum – remote controller with RIO
1
2
3
4
33002204 12/2010
Local Quantum drop 1
RIO master module
RIO slave module
RIO drop 2
879
Configuration examples
Defining Drops
To define drops proceed as follows in the PLC Configuration window:
Step
880
Action
1
Select PLC Selection.
Response: The PLC selection dialog is opened.
2
Select the Quantum PLC family and a CPU x113 xx. Using OK return to the
PLC Configuration window.
3
Select I/O Map.
Response: The I/O Map dialog is opened and the first drop is automatically
entered in the table.
4
Select the Head Setup command button.
Response: The Head Setup dialog is opened.
5
Enter a 7 in RIO Slot and quit the dialog using OK.
Response: The CRP-93x-00 module is automatically inserted in the component
list (in slot 7) of the selected drop. In the Go To list box, the Local/RIO (Slot 7)
network link is displayed.
6
Select the last line in the table.
Select the Insert command button.
Response: The second drop is entered in the Type column.
Note: The number of drops to be inserted is defined in the segment scheduler
dialog. The default predetermines a maximum number of 32.
Dialog display
7
Select the drop from the Drop column.
Select the Edit... command button.
Response: You reach the module map.
33002204 12/2010
Configuration examples
Mapping Modules and Specifying I/O References
To map the modules and specify the address ranges proceed as follows in the Local
Quantum Drop dialog:
Step
33002204 12/2010
Action
1
Select the Module →... column.
Response: The I/O Module Selection dialog is opened.
2
From the Category column, select the <all> option.
Response: All modules are listed in the Modules column.
3
In the Modules column, select the CPS-214-00 module.
Exit the dialog with OK.
Response: The module is inserted in the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example (see Local Quantum
Drop dialog representation).
5
In the In Ref and Out Ref columns, set the start references for the input and
output modules.
Note: Discrete Input References have the prefix 1 (e.g. 100001), Coil
References have the prefix 0 (e.g. 000001), Input Register References have the
prefix 3 (e.g. 300001) and Output Register References have the prefix 4 (e.g.
400001).
Response: The end reference (column In.End. or Out.End) of the available
address range is automatically entered.
881
Configuration examples
Dialog display
Following module mapping and I/O reference specification the dialog looks like this:
Set module parameters
To set parameters for the individual modules, proceed as follows in the Local
Quantum Drop dialog:
Step
882
Action
1
From the Rack Slot column select the 1-3 line.
Response: The 1-3 text box has a dark background, i.e. the DDI-353-00 module
has been selected for editing.
Note: Parameters are not set for the CPS-214-00 and CPU-x13-0x modules.
2
Select the Params command button.
Response: The 140-DDI-353-00 dialog is opened.
3
Select the Discrete option button.
Response: You return to the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example.
Note: The modules are sometimes set with different parameters. Help with this
can be obtained from the corresponding help texts in the parameter dialog.
33002204 12/2010
Configuration examples
Editing Remote Drop
Editing of the I/O st. (Drop) defined second takes place in the dialog RIO (Slot 7) quantum I/O-St. 2.
This dialog can be reached in two ways:
z In the I/O Map dialog, using the Edit.... command button, or
z
33002204 12/2010
in the Local Quantum Drop dialog, using the Next command button.
883
Configuration examples
Editing Remote Drop
Introduction
This section describes the configuration of the second (remote) drop. The drop has
already been defined in Editing the First (local) Drop (see page 879).
To edit the second (remote) drop, the modules must be specified with their I/O
references before parameters for the individual modules can be set.
Quantum – remote controller with RIO
1
2
3
4
884
Local Quantum drop 1
RIO master module
RIO slave module
RIO drop 2
33002204 12/2010
Configuration examples
Mapping Modules and Specifying I/O References
To allocate the modules and specify the address ranges use the dialog RIO (slot 7)
- quantum I/O-St. 2 and proceed as follows:
Step
33002204 12/2010
Action
1
Select the Module →... column.
Response: The I/O Module Selection dialog is opened.
2
From the Category column, select the <all> option.
Response: All modules are listed in the Modules column.
3
In the Modules column select the CRA-93x-00 module.
Exit the dialog with OK.
Response: The module is inserted in the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example (see dialog representation
RIO (Slot 7) Quantum Drop 2).
5
In the In Ref and Out Ref columns, set the start references for the input and
output modules.
Note: Discrete Input References have the prefix 1 (e.g. 100001), Coil
References have the prefix 0 (e.g. 000001), Input Register References have the
prefix 3 (e.g. 300001) and Output Register References have the prefix 4 (e.g.
400001).
Response: The end reference (column In.End. or Out.End) of the available
address range is automatically entered.
885
Configuration examples
Dialog display
Following module mapping and I/O reference specification the dialog looks like this:
Set module parameters
To set parameters for individual modules use the dialog RIO (slot 7) - Quantum I/OSt. 2 and proceed as follows:
Step
886
Action
1
From the Rack Slot column select the 1-2 line.
Response: The 1-2 text box has a dark background, i.e. the DDI-353-00 module
has been selected for editing.
2
Select the Params command button.
Response: The 140-DDI-353-00 dialog is opened.
3
Select the Discrete option button.
Response: You return to the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example.
Note: The modules are sometimes set with different parameters. Help with this
can be obtained from the corresponding help texts in the parameter dialog.
33002204 12/2010
Configuration examples
E.2
Quantum Example - Remote control with RIO
(series 800)
Overview
This Chapter contains the step-by-step process for the configuration of remote
control with RIO (Remote I/O) and series 800 modules.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
Editing Local Drop
888
Editing Remote Drop
893
Editing Remote Drop
897
887
Configuration examples
Editing Local Drop
Introduction
This section describes the configuration of the first (local) drop. The processing
sequence begins first of all with the definition of all drops.
When editing the first (local) drop the modules must be set with their I/O references
before parameters can be set forindividual modules.
Quantum – remote controller with RIO (Series 800)
1
2
3
4
5
6
Local Quantum drop 1
RIO master module
RIO slave module
RIO drop 2
Adapter module
RIO drop 3 with series 800 modules
Defining Drops
To define drops proceed as follows in the PLC Configuration window:
Step
888
Action
1
Select PLC Selection.
Response: The PLC selection dialog is opened.
2
Select the Quantum PLC family and a CPU x113 xx. Using OK return to the
PLC Configuration window.
3
Select I/O Map.
Response: The I/O Map dialog is opened and the first drop is automatically
entered in the table.
4
Select the Head Setup command button.
Response: The Head Setup dialog is opened.
5
Enter a 7 in RIO Slot and quit the dialog using OK.
Response: The CRP-93x-00 module is automatically inserted in the I/O map (in
slot 7) of the selected drop. In the Go To list box, the Local/RIO (Slot 7) network
link is displayed.
33002204 12/2010
Configuration examples
Step
33002204 12/2010
Action
6
Select the last free row in the table, and insert the second drop with the
command button Insert.
Response: The second drop is entered in the Type column of the table.
Note: The number of drops to be inserted is defined in the segment scheduler
dialog. The default predetermines the maximum number of 32, so that settings
are not necessary.
7
Select the last free row in the table again, and insert the third drop with the Insert
command button.
Response: The second drop is entered in the Type column of the table.
8
Select the third drop and open the list box in the Type column.
Select the 800 I/O option.
Dialog display
9
Select the first drop from the Drop column.
Select the Edit... command button.
Response: You reach the module map.
889
Configuration examples
Mapping Modules and Specifying I/O References
To map the modules and specify the address ranges proceed as follows in the Local
Quantum Drop dialog:
Step
890
Action
1
Select the Module →... column.
Response: The I/O Module Selection dialog is opened.
2
From the Category column, select the <all> option.
Response: All modules are listed in the Modules column.
3
In the Modules column, select the CPS-214-00 module.
Exit the dialog with OK.
Response: The module is inserted in the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example (see Local Quantum
Drop dialog representation).
5
In the In Ref and Out Ref columns, set the start references for the input and
output modules.
Note: Discrete Input References have the prefix 1 (e.g. 100001), Coil
References have the prefix 0 (e.g. 000001), Input Register References have the
prefix 3 (e.g. 300001) and Output Register References have the prefix 4 (e.g.
400001).
Response: The end reference (column In.End. or Out.End) of the available
address range is automatically entered.
33002204 12/2010
Configuration examples
Dialog display
Following module mapping and I/O reference specification the dialog looks like this:
Set module parameters
To set parameters for the individual modules, proceed as follows in the Local
Quantum Drop dialog:
Step
33002204 12/2010
Action
1
From the Rack Slot column select the 1-3 line.
Response: The 1-3 text box has a dark background, i.e. the DDI-353-00 module
has been selected for editing.
Note: Parameters are not set for the CPS-214-00 and CPU-x13-0x modules.
2
Select the Params command button.
Response: The 140-DDI-353-00 dialog is opened.
3
Select the Discrete option button.
Response: You return to the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example.
Note: The modules are sometimes set with different parameters. Help with this
can be obtained from the corresponding help texts in the parameter dialog.
891
Configuration examples
Editing Remote Drop
Editing of the I/O st. (Drop) defined second takes place in the dialog RIO (Slot 7) quantum I/O-St. 2.
This dialog can be reached in two ways:
In the I/O Map dialog, using the Edit.... command button, or
z
z
892
in the Local Quantum Drop dialog, using the Next command button.
33002204 12/2010
Configuration examples
Editing Remote Drop
Introduction
This section describes the configuration of the second (remote) drop. The drop has
already been defined in Editing the First (local) Drop (see page 888).
To edit the second (remote) drop, the modules must be specified with their I/O
references before parameters for the individual modules can be set.
Quantum – remote controller with RIO (Series 800)
1
2
3
4
5
6
33002204 12/2010
Local Quantum drop 1
RIO master module
RIO slave module
RIO drop 2
Adapter module
RIO drop 3 with series 800 modules
893
Configuration examples
Mapping Modules and Specifying I/O References
To allocate the modules and specify the address ranges use the dialog RIO (slot 7)
- quantum I/O-St. 2 and proceed as follows:
Step
894
Action
1
Select the Module →... column.
Response: The I/O Module Selection dialog is opened.
2
From the Category column, select the <all> option.
Response: All modules are listed in the Modules column.
3
In the Modules column select the CRA-93x-00 module.
Exit the dialog with OK.
Response: The module is inserted in the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example (see dialog representation
RIO (Slot 7) Quantum Drop 2).
5
In the In Ref and Out Ref columns, set the start references for the input and
output modules.
Note: Discrete Input References have the prefix 1 (e.g. 100001), Coil
References have the prefix 0 (e.g. 000001), Input Register References have the
prefix 3 (e.g. 300001) and Output Register References have the prefix 4 (e.g.
400001).
Response: The end reference (column In.End. or Out.End) of the available
address range is automatically entered.
33002204 12/2010
Configuration examples
Dialog display
Following module mapping and I/O reference specification the dialog looks like this:
Set module parameters
To set parameters for individual modules use the dialog RIO (slot 7) - Quantum I/OSt. 2 and proceed as follows:
Step
33002204 12/2010
Action
1
From the Rack Slot column select the 1-2 line.
Response: The 1-2 text box has a dark background, i.e. the DDI-353-00 module
has been selected for editing.
2
Select the Params command button.
Response: The 140-DDI-353-00 dialog is opened.
3
Select the Discrete option button.
Response: You return to the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example.
Note: The modules are sometimes set with different parameters. Help with this
can be obtained from the corresponding help texts in the parameter dialog.
895
Configuration examples
Editing Remote 800 Drops
The third defined drop is edited in the RIO (Slot 7) - 800 Drop 3 dialog.
This dialog can be reached in two ways:
In the I/O Map dialog, using the Edit.... command button, or
z
z
896
in the RIO (Slot 7) - Quantum Drop 2 dialog using the Next command button.
33002204 12/2010
Configuration examples
Editing Remote Drop
Introduction
This Section describes the configuration of the third (remote) drop. The drop has
already been defined in Editing the First (local) Drop (see page 888).
To edit the third (remote) drop, the modules must be specified with their I/O
references before the individual modules can be parameterized.
NOTE: The J890 adapter module must be mounted in the rack of the third drop.
However, this module is not visible either in the software or in the dialogs.
Quantum – remote controller with RIO (Series 800)
1
2
3
4
5
6
33002204 12/2010
Local Quantum drop 1
RIO master module
RIO slave module
RIO drop 2
Adapter module
RIO drop 3 with series 800 modules
897
Configuration examples
Mapping Modules and Specifying I/O References
To map the modules and specify the address ranges go to the RIO (slot 7) - 800
drop 3 dialog and proceed as follows:
Step
898
Action
1
Select the Module →... column.
Response: The I/O Module Selection dialog is opened.
2
From the Category column, select the <all> option.
Response: All modules are listed in the Modules column.
3
In the Modules column select the B810 module.
Exit the dialog with OK.
Response: The module is inserted in the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example (see dialog representation
RIO (slot 7) 800 drop 3).
5
In the Out Ref. column, enter the start references for the output modules.
Note: Discrete Input References have the prefix 1 (e.g. 100001), Coil
References have the prefix 0 (e.g. 000001), Input Register References have the
prefix 3 (e.g. 300001) and Output Register References have the prefix 4 (e.g.
400001).
Response: The end reference of the available address range (Out End column)
is entered automatically.
33002204 12/2010
Configuration examples
Dialog display
Following module mapping and I/O reference specification the dialog looks like this:
Set module parameters
To set parameters for individual modules go to the RIO (slot 7) - 800 drop 3 dialog
and proceed as follows:
Step
33002204 12/2010
Action
1
From the Rack Slot column select the 1-1 line.
Response: The 1-1 text box has a dark background, i.e. the B810 module has
been selected for editing.
2
Select the Params command button.
Response: The B810 dialog is opened.
3
Select the option button Discrete
Response: You return to the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example.
Note: The modules are sometimes set with different parameters. Help with this
can be obtained from the corresponding help texts in the parameter dialog.
899
Configuration examples
E.3
Quantum Example - Remote Control with DIO
Overview
This Chapter contains the step-by-step process for the configuration of remote
control with DIO (Distributed I/O).
What's in this Section?
This section contains the following topics:
Topic
900
Page
Editing Local Drop
901
Editing Local Drop
906
33002204 12/2010
Configuration examples
Editing Local Drop
Introduction
This section describes the configuration of the first (local) drop. The processing
sequence begins first of all with the definition of the drop.
When editing the first (local) drop the modules must be set with their I/O references
before parameters can be set forindividual modules.
Quantum – remote controller with DIO
1
2
3
4
33002204 12/2010
Local Quantum drop 1
DIO master module
DIO slave module
DIO drop 2
901
Configuration examples
Defining the Drop
To define the drop use Configure from the main menu and proceed as follows:
Step
902
Action
1
Select PLC Selection.
Response: The PLC selection dialog is opened.
2
Select the Quantum PLC family and a CPU x113 xx. Using OK return to the
PLC Configuration window.
3
Select I/O Map.
Response: The I/O Map dialog is opened and the first drop is automatically
entered in the table.
4
Select the Head Setup command button.
Response: The Head Setup dialog is opened.
5
Enter a 7 in NOM Slot 1 and quit the dialog using OK.
Response: The NOM module NOM-2xx-00 is automatically inserted in the I/O
map (in slot 7) of the selected drop. In the Go to list box, the network link
Local/RIO (Slot ?) is displayed.
Dialog display
6
Select the drop from the Drop column.
Select the Edit... command button.
Response: You reach the module map.
33002204 12/2010
Configuration examples
Mapping Modules and Specifying I/O References
To map the modules and specify the address ranges proceed as follows in the Local
Quantum Drop dialog:
Step
33002204 12/2010
Action
1
Select the Module →... column.
Response: The I/O Module Selection dialog is opened.
2
From the Category column, select the <all> option.
Response: All modules are listed in the Modules column.
3
In the Modules column, select the CPS-214-00 module.
Exit the dialog with OK.
Response: The module is inserted in the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example (see Local Quantum
Drop dialog representation).
5
In the In Ref and Out Ref columns, set the start references for the input and
output modules.
Note: Discrete Input References have the prefix 1 (e.g. 100001), Coil
References have the prefix 0 (e.g. 000001), Input Register References have the
prefix 3 (e.g. 300001) and Output Register References have the prefix 4 (e.g.
400001).
Response: The end reference (column In.End. or Out.End) of the available
address range is automatically entered.
903
Configuration examples
Dialog display
Following module mapping and I/O reference specification the dialog looks like this:
Set module parameters
To set parameters for the individual modules, proceed as follows in the Local
Quantum Drop dialog:
Step
904
Action
1
From the Rack Slot column select the 1-3 line.
Response: The 1-3 text box has a dark background, i.e. the DDI-353-00 module
has been selected for editing.
Note: Parameters are not set for the CPS-214-00 and CPU-x13-0x modules.
2
Select the Params command button.
Response: The 140-DDI-353-00 dialog is opened.
3
Select the Discrete option button.
Response: You return to the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example.
Note: The modules are sometimes set with different parameters. Help with this
can be obtained from the corresponding help texts in the parameter dialog.
33002204 12/2010
Configuration examples
Editing Remote Drop
To edit the remote drop with DIO, you must return to the I/O Map dialog and define
the drop.
33002204 12/2010
905
Configuration examples
Editing Local Drop
Introduction
This section describes the configuration of the second (remote) drop. The
processing sequence begins first of all with the definition of the drop.
To edit the second (remote) drop, the modules must be specified with their I/O
references before parameters for the individual modules can be set.
NOTE: To link to the remote network, the coupling module CRA-21x-x0 must be
entered during module mapping.
Quantum – remote controller with DIO
1
2
3
4
906
Local Quantum drop 1
DIO master module
DIO slave module
DIO drop 2
33002204 12/2010
Configuration examples
Defining the Drop
To define the drop go to the I/O map dialog and proceed as follows:
Step
33002204 12/2010
Action
1
From the Go to list box, select the DIO 1 (Slot 7) network link.
Response: The drop entered in the table is no longer displayed.
2
Select the Insert command button.
Response: In the Type column, the Read/Write type is entered.
Dialog display
3
Select the drop from the Drop column.
Select the Edit... command button.
Response: You reach the module map.
907
Configuration examples
Mapping Modules and Specifying I/O References
To map the modules and specify the address ranges use the DIO 1 (slot 7) - drop
1 dialog and proceed as follows:
Step
908
Action
1
Select the Module →... column.
Response: The I/O Module Selection dialog is opened.
2
From the Category column, select the <all> option.
Response: All modules are listed in the Modules column.
3
In the Modules column select the CRA-21x-x0 module.
Exit the dialog with OK.
Response: The module is inserted in the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example (see dialog representation
DIO (slot 7) Quantum drop 1).
5
In the In Ref and Out Ref columns, set the start references for the input and
output modules.
Note: Discrete Input References have the prefix 1 (e.g. 100001), Coil
References have the prefix 0 (e.g. 000001), Input Register References have the
prefix 3 (e.g. 300001) and Output Register References have the prefix 4 (e.g.
400001).
Response: The end reference (column In.End. or Out.End) of the available
address range is automatically entered.
33002204 12/2010
Configuration examples
Dialog display
Following module mapping and I/O reference specification the dialog looks like this:
Set module parameters
To set parameters for individual modules use the DIO 1 (slot 7) - Drop 1 dialog and
proceed as follows:
Step
33002204 12/2010
Action
1
From the Rack Slot column select the 1-2 line.
Response: The 1-2 text box has a dark background, i.e. the DDI-353-00 module
has been selected for editing.
2
Select the Params command button.
Response: The 140-DDI-353-00 dialog is opened.
3
Select the Discrete option button.
Response: You return to the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example.
Note: The modules are sometimes set with different parameters. Help with this
can be obtained from the corresponding help texts in the parameter dialog.
909
Configuration examples
E.4
Quantum Example – INTERBUS Control
Overview
This Chapter contains the step-by-step process for the configuration of INTERBUS
control with the Quantum.
What's in this Section?
This section contains the following topics:
Topic
910
Page
General Information
911
Editing Local Drop
912
33002204 12/2010
Configuration examples
General Information
Introduction
INTERBUS control using Quantum occurs via module NOA-611-10. During this
process the module collects the words of all remote bus nodes and creates a
telegram with status information and I/O words. The telegram is then transferred to
the CPU, so that the NOA behaves like an I/O module.
NOTE: Using branch interfaces in the remote bus, remote bus branches with further
remote bus nodes (TIOs) can be constructed. However, the branch interfaces can
only be inserted in the remote bus, not in the remote bus branch.
Parameterization
Command sequence parameterization (restart procedure) occurs in the CMD Tool,
produced by the PHÖNIX firm (see also " NOA 611 1 restart procedure" with an
example for parameterizing the command sequence in CMD Tool).
33002204 12/2010
911
Configuration examples
Editing Local Drop
Introduction
This section describes the configuration of the first (local) drop. The processing
sequence begins first of all with the definition of the drop.
When editing the first (local) drop the modules must be set with their I/O references
before parameters can be set for individual modules.
NOTE: When the NOA-611-00 module is entered in the I/O map, the loadable ULEX
is automatically installed.
Quantum - INTERBUS controller
1
2
3
Local Quantum Drop
INTERBUS master module
Remote bus without branch interface
NOTE: The configuration of remote bus nodes does not take place in Concept and
is therefore not apparent in the I/O map. To edit the remote bus nodes, you must use
the CMD tool produced by the PHÖNIX firm (Configuration Monitoring and
Diagnostic Software).
912
33002204 12/2010
Configuration examples
Defining Drops
To define drops proceed as follows in the PLC Configuration window:
Step
33002204 12/2010
Action
1
Select PLC Selection.
Response: The PLC selection dialog is opened.
2
Select the Quantum PLC family and a CPU x113 xx. Use OK return to the PLC
Configuration window.
3
Select I/O Map.
Response: The I/O Map dialog is opened and the first drop is automatically
entered in the table.
Dialog display
4
Select the drop from the Drop column.
Select the Edit... command button.
Response: You reach the module map.
913
Configuration examples
Mapping Modules and Specifying I/O References
To map the modules and specify the address ranges proceed as follows in the Local
Quantum Drop dialog:
Step
914
Action
1
Select the Module →... column.
Response: The I/O Module Selection dialog is opened.
2
From the Category column, select the <all> option.
Response: All modules are listed in the Modules column.
3
In the Modules column, select the CPS-214-00 module.
Exit the dialog with OK.
Response: The module is inserted in the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example (see Local Quantum
Drop dialog representation).
5
In the In Ref and Out Ref columns, set the start references for the input and
output modules.
Note: Discrete Input References have the prefix 1 (e.g. 100001), Coil
References have the prefix 0 (e.g. 000001), Input Register References have the
prefix 3 (e.g. 300001) and Output Register References have the prefix 4 (e.g.
400001).
Response: The end reference (column In.End. or Out.End) of the available
address range is automatically entered.
33002204 12/2010
Configuration examples
Dialog display
Following module mapping and I/O reference specification the dialog looks like this:
Set module parameters
To set parameters for the individual modules, proceed as follows in the Local
Quantum Drop dialog:
Step
33002204 12/2010
Action
1
From the Rack Slot column select the 1-3 line.
Response: The 1-3 text box has a dark background, i.e. the DDI-353-00 module
has been selected for editing.
Note: Parameters are not set for the CPS-214-00 and CPU-x13-0x modules.
2
Select the Params command button.
Response: The 140-DDI-353-00 dialog is opened.
3
Select the Discrete option button.
Response: You return to the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example.
Note: The modules are sometimes set with different parameters. Help with this
can be obtained from the corresponding help texts in the parameter dialog.
915
Configuration examples
E.5
Quantum Example - SY/MAX Controller
Overview
This Chapter contains the step-by-step process for the configuration of a SY/MAX
controller.
What's in this Section?
This section contains the following topics:
Topic
916
Page
Editing Local Drop
917
Editing Remote Drop
922
33002204 12/2010
Configuration examples
Editing Local Drop
Introduction
This section describes the configuration of the first (local) drop. The processing
sequence begins first of all with the definition of all drops.
When editing the first (local) drop the modules must be set with their I/O references
before parameters can be set forindividual modules.
Quantum – SY/MAX controller
1
2
3
33002204 12/2010
Local Quantum drop 1
RIO master module
SY/MAX drop 2
917
Configuration examples
Defining Drops
To define drops proceed as follows in the PLC Configuration window:
Step
918
Action
1
Select PLC Selection.
Response: The PLC selection dialog is opened.
2
Select the Quantum PLC family and a CPU x113 xx. Using OK return to the
PLC Configuration window.
3
Select I/O Map.
Response: The I/O Map dialog is opened and the first drop is automatically
entered in the table.
4
Select the Head Setup command button.
Response: The Head Setup dialog is opened.
5
Enter a 7 in RIO Slot and quit the dialog using OK.
Response: The CRP-93x-00 module is automatically inserted in the I/O map (in
slot 7) of the selected drop. In the Go To list box, the Local/RIO (Slot 7) network
link is displayed.
6
Select the last line in the table.
Select the Insert command button.
Response: The second drop is entered in the Type column.
Note: The number of drops to be inserted is defined in the segment scheduler
dialog. The default defines a maximum number of 32.
7
Select the second drop and in the Type column, open the list box.
Select the SY/MAXoption.
Dialog display
8
Select the first drop from the Drop column.
Select the Edit... command button.
Response: You reach the module map.
33002204 12/2010
Configuration examples
Mapping Modules and Specifying I/O References
To map the modules and specify the address ranges proceed as follows in the Local
Quantum Drop dialog:
Step
33002204 12/2010
Action
1
Select the Module →... column.
Response: The I/O Module Selection dialog is opened.
2
From the Category column, select the <all> option.
Response: All modules are listed in the Modules column.
3
In the Modules column, select the CPS-214-00 module.
Exit the dialog with OK.
Response: The module is inserted in the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example (see Local Quantum
Drop dialog representation).
5
In the In Ref and Out Ref columns, set the start references for the input and
output modules.
Note: Discrete Input References have the prefix 1 (e.g. 100001), Coil
References have the prefix 0 (e.g. 000001), Input Register References have the
prefix 3 (e.g. 300001) and Output Register References have the prefix 4 (e.g.
400001).
Response: The end reference (column In.End. or Out.End) of the available
address range is automatically entered.
919
Configuration examples
Dialog display
Following module mapping and I/O reference specification the dialog looks like this:
Set module parameters
To set parameters for the individual modules, proceed as follows in the Local
Quantum Drop dialog:
Step
920
Action
1
From the Rack Slot column select the 1-3 line.
Response: The 1-3 text box has a dark background, i.e. the DDI-353-00 module
has been selected for editing.
Note: Parameters are not set for the CPS-214-00 and CPU-x13-0x modules.
2
Select the Params command button.
Response: The 140-DDI-353-00 dialog is opened.
3
Select the Discrete option button.
Response: You return to the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example.
Note: The modules are sometimes set with different parameters. Help with this
can be obtained from the corresponding help texts in the parameter dialog.
33002204 12/2010
Configuration examples
Editing Remote Drop
Editing the drop defined second takes place in the dialog RIO (slot 7) – SY/MAX
I/O-St. 2.
This dialog can be reached in two ways:
z In the I/O Map dialog, using the Edit.... command button, or
z
33002204 12/2010
in the Local Quantum Drop dialog, using the Next command button.
921
Configuration examples
Editing Remote Drop
Introduction
This section describes the configuration of the second (remote) drop. The drop has
already been defined in Editing the First (local) Drop (see page 917).
To edit the second (remote) drop, the modules must be specified with their I/O
references before parameters for the individual modules can be set.
NOTE: To link to the remote network, the coupling module CRM-931-RG must be
entered during module mapping.
Quantum – SY/MAX controller
1
2
3
922
Local Quantum drop 1
RIO master module
SY/MAX drop 2
33002204 12/2010
Configuration examples
Mapping Modules and Specifying I/O References
To map the modules and specify the address ranges proceed as follows in the RIO
(slot 7) – SY/MAX I/O-St. 2 dialog:
Step
33002204 12/2010
Action
1
Select the Module →... column.
Response: The I/O Module Selection dialog is opened.
2
From the Category column, select the <all> option.
Response: All modules are listed in the Modules column.
3
In the Modules column select the CRM-931-RG module.
Exit the dialog with OK.
Response: The module is inserted in the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example (see dialog representation
RIO (Slot 7) SY/MAX drop 2).
5
In the In Ref and Out Ref columns, set the start references for the input and
output modules.
Note: Discrete Input References have the prefix 1 (e.g. 100001), Coil
References have the prefix 0 (e.g. 000001), Input Register References have the
prefix 3 (e.g. 300001) and Output Register References have the prefix 4 (e.g.
400001).
Response: The end reference (column In.End. or Out.End) of the available
address range is automatically entered.
923
Configuration examples
Dialog display
Following module mapping and I/O reference specification the dialog looks like this:
Set module parameters
To parameter the individual modules use the dialog RIO (slot 7) – SY/MAX I/O-St.
2 and proceed as follows:
Step
924
Action
1
In the Slot column, select line 2.
Response: The 2 text box has a dark background, i.e. the RIM-101/361 module
has been selected for editing.
2
Select the Params command button.
Response: The 8030-RIM-101/361 dialog is opened.
3
Select the Discrete option button.
Response: You return to the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example.
Note: The modules are sometimes set with different parameters. Help with this
can be obtained from the corresponding help texts in the parameter dialog.
33002204 12/2010
Configuration examples
E.6
Quantum Example - Profibus DP Controller
Overview
This Chapter contains the step-by-step process for the configuration of a Profibus
DP controller with the Quantum.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
General Information
926
Profibus DP Export Settings in SyCon
927
Editing Local Drop
929
Importing Profibus DP Configuration
934
925
Configuration examples
General Information
Introduction
Configuring Profibus DP is done using the SyCon (System Configurator) software
produced by Hilscher GmbH. It is initially stored there as a file (*.CNF). This
generated file is loaded into Concept and is visible in the I/O map of the configurator.
Before the Profibus DP nodes (max. 32) can be imported, a bus controller (CRP 811
00) must be mapped in the drop (Quantum I/O). Depending on the CPU selection in
the Select Extensions dialog box, a maximum of two to six bus controllers can be
inserted.
926
33002204 12/2010
Configuration examples
Profibus DP Export Settings in SyCon
Introduction
SyCon is used to configure Profibus DP. The procedure for this is to be found in the
user manual provided by the manufacturer. The settings for the export of the *.CNF
file are explained in the following step-by-step instructions.
Preconditions
For CRP-811-00 diagnostics the serial interface of the host computer and the
diagnostic interface of the bus controller must be linked with a V24 cable.
To display this diagnostic data, terminal emulation software must be started (e.g.
PROCOMM using the settings: 19.2 kBd, 8 data bits, 1 stop bit, no parity).
Defining the Destination Directory
Firstly, specify the destination directory in which all files are to be saved:
Step
Action
1
Select in the main menu Settings →Search Path....
Response: The Search Path dialog is opened and is pre-set with the SyCon
directory path as the project directory (e.g. C:\HILSCHER
GMBH\SYCON\FIELDBUS\PROFIBUS).
2
Enter the path of the Concept directory (e.g. C:\CONCEPT\PROFIBUS) in the
Project Directory text box.
Note: You can also accept the default.
Response: Execution of the Save and Export menu commands (in the File
main menu) saves all files in the entered Concept directory.
Generating an Export File
To generate an export file (*.CNF) proceed as follows:
Step
33002204 12/2010
Action
1
Select in the main menu File →Save →*.PB.
Response: The configuration is stored as a database file *.PB in the specified
directory.
2
Select in the main menu File →Export →ASCII.
Response: The configuration is stored as an ASCII file *.CNF in the specified
directory.
3
Exit SyCon and start Concept.
927
Configuration examples
Note about Saving
The configuration must always be saved as a database file *.PB first, only then can
an ASCII file be generated from the saved *.PB file. Every change must therefore
also be saved as a *.PB file first, before an ASCII file can be generated for export.
The files *.PB and *.CNF should always be saved in the same project directory.
Profibus DP Configuration in Concept
After the Profibus DP nodes have been configured in SyCon, the Profibus DP
configuration is imported into the Concept I/O map.
An example of configuration and import is described in the chapter "Editing a Local
Drop (see page 929)".
928
33002204 12/2010
Configuration examples
Editing Local Drop
Introduction
This section describes the configuration of the first (local) drop.
For Profibus DP configuration the CRP-811-00 coupling module must be registered
in the I/O map. The configuration defined in SyCon is loaded into Concept as the
generated *.CNF file is imported into the parameter dialog of the CRP-811-00
coupling module.
NOTE: For an error free transfer of the Profibus DP configuration, it should be
ensured that sufficient memory is available. To optimize storage occupancy open
the dialog PLC Memory Partition (PLC Configuration →PLC Memory Partition).
When editing the first (local) drop the modules must be set with their I/O references
before the individual modules can be parameterized.
Quantum – Profibus DP controller
1
2
3
4
5
6
33002204 12/2010
Device data base for CRP-811-00 (load onto SyCon)
Host computer for Concept and SyCon
V24 cable
Local Quantum drop 1
RIO master module
Profibus DP configuration (External modules)
929
Configuration examples
Defining Drops
To define drops proceed as follows in the PLC Configuration window:
Step
930
Action
1
Select PLC Selection.
Response: The PLC Selection dialog is opened.
2
Select the Quantum PLC family and a CPU x113 xx. Using OK return to the
PLC Configuration window.
3
Select Config. Extensions →Select Extensions list.
Response: The Select Extensions dialog is opened.
4
In the Profibus DP list box select the 1 option.
Response: The coupling module then appears in the I/O Module Selection
dialog and can be used in the I/O map.
5
Select I/O Map.
Response: The I/O Map dialog is opened and the first drop is automatically
entered in the table.
Dialog Representation
6
Select the drop from the Drop column.
Select the Edit... command button.
Response: You reach the module map.
33002204 12/2010
Configuration examples
Mapping Modules and Specifying I/O References
To map the modules and specify the address ranges proceed as follows in the Local
Quantum Drop dialog:
Step
33002204 12/2010
Action
1
Select the Module →... column.
Response: The I/O Module Selection dialog is opened.
2
From the Category column, select the <all> option.
Response: All modules are listed in the Modules column.
3
In the Modules column, select the CPS-214-00 module.
Exit the dialog with OK.
Response: The module is inserted in the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example (see Local Quantum
Drop dialog representation).
5
In the In Ref and Out Ref columns, set the start references for the input and
output modules.
Note: Discrete Input References have the prefix 1 (e.g. 100001), Coil
References have the prefix 0 (e.g. 000001), Input Register References have the
prefix 3 (e.g. 300001) and Output Register References have the prefix 4 (e.g.
400001).
Response: The end reference of the available address range (In End or Out
End column) is entered automatically.
931
Configuration examples
Dialog Representation
Following module mapping and I/O reference specification, the dialog looks like this:
Parameterization of Modules
To parameterize the individual modules, proceed as follows in the Local Quantum
Drop dialog:
Step
932
Action
1
From the Rack Slot column, select line 1-3.
Response: The 1-3 text box has a dark background, i.e. the DDI-353-00 module
has been selected for editing.
Note: The CPS-214-00 and CPU-x13-0x modules are not parameterized.
2
Select the Params command button.
Response: The 140-DDI-353-00 dialog is opened.
3
Select the Discrete option button.
Response: You return to the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example.
Note: The modules are sometimes parameterized differently. Help with this can
be obtained from the corresponding help texts in the parameter dialog.
33002204 12/2010
Configuration examples
Importing a Profibus DP Configuration
Importing configured Profibus DP nodes occurs in the parameter dialog of the CRP811-00 coupling module. This dialog opens when you select the CRP-811-00 row
from the I/O map and press the Params command button.
33002204 12/2010
933
Configuration examples
Importing Profibus DP Configuration
Introduction
This section describes the import of the Profibus DP configuration. After that, further
parameter settings for the master take place and the I/O map can be established.
Downloading a Profibus DP Configuration to Concept
To import, proceed as follows:
Step
934
Action
1
Select the Import... command button.
Response: The Select Import File standard window is opened.
2
Enter the path of the previously generated *.CNF file and exit the dialog with OK.
Response: The transfer of the *.CNF file is displayed in the Import Status
dialog.
3
Close the dialog after the transfer (100%).
Response: The imported configuration is displayed in the CRP-811-00
(Profibus DP) dialog.
33002204 12/2010
Configuration examples
Dialog Representation
Following the import of the configuration, the dialog looks like this (view scrolled all
the way to the left):
33002204 12/2010
935
Configuration examples
Following the import of the configuration, the dialog looks like this (view scrolled all
the way to the right):
NOTE: In the Slave range, the Parameter... command button is used for displaying
slave parameters. The slave modules are, however, parameterized in SyCon (see
SyCon software user manual).
936
33002204 12/2010
Configuration examples
Parameterizing the Master
To parameterize the master, proceed as follows:
Step
33002204 12/2010
Action
1
In the Master range, select the Parameters... command button.
Response: The DP Master Parameters dialog is opened.
Dialog Representation
2
Accept the defaults, as shown in the figure above, or redefine them.
3
Close the dialog using OK.
Response: You return to the CRP-811-00 (Profibus DP) dialog.
937
Configuration examples
Setting I/O References
To set the I/O references proceed as follows:
Step
938
Action
1
Select the command button Preset. ....
The Preset dialog is opened.
Dialog Representation
2
Accept the defaults, as shown in the figure above, or redefine them.
3
Close the dialog using OK.
Response: You return to the CRP-811-00 (Profibus DP) dialog, in which the
defined reference ranges have automatically been entered.
33002204 12/2010
Configuration examples
Dialog Representation
After the I/O references have been set the dialog looks like this (view scrolled all the
way to the left):
33002204 12/2010
939
Configuration examples
After the I/O references have been set the dialog looks like this (view scrolled all the
way to the right):
940
33002204 12/2010
Configuration examples
E.7
Quantum-Example - Peer Cop
Introduction
In this chapter the configuration of Peer Cop is described step by step.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
Generals to Peer Cop
942
Configuration of Peer Cop
944
Global data transfer
946
Specific data transfer
948
941
Configuration examples
Generals to Peer Cop
Introduction
Peer Cop is a data exchange service provided by the Modbus Plus network. As an
overview, imagine that every Modbus Plus network segment (max. 64 nodes) has a
global memory, i.e. a certain number of global variables can be read by every node
connected to the same segment. The total amount of global variables depends on
the number. of connected (and active) nodes, every node can provide up to 32
words (16 bit) to the global memory. Only the 32 words provided by a node can be
written by the same node, all other nodes have read only access to these variables.
So by definition, there is a maximum of 64 * 32 words of global memory available to
a Modbus Plus network segment. Nodes connected to different (through bridges or
gateways) segment cannot share global memory.
When a PLC provides 32 words of global memory it does so by assigning holding
registers for broadcast, and when the PLC wants to read global variables provided
by another Peer Cop node, assigning holding registers to receive them. These
registers are called Global Input (from other nodes) and Global Output (what this
node provides) get updated cyclically (in case of a PLC after every scan).
To pass Routing Paths
Actually every Modbus Plus node has its own communication processor (the so
called Peer processor), in addition to the processor that controls the node specific
work (in case of a PLC: solving user logic).
This leads to some routing paths the global data has to pass to traverse from one
node to the other:
z From the data provider (e.g. user logic) to the local (most times embedded peer
processor).
z From the local peer processor to the other peer processors (this takes the token
cycle time of the Modbus Plus network segment, that depends directly on the
number of connected nodes).
z From the peer processor of the data receiver to the data receiver itself, (that is
usually the user logic in the receiver PLC).
The actual update time depends on the speed of the Modbus Plus network segment
and (that’s the big time consumer) the scan times of the data provider and the data
receiver.
942
33002204 12/2010
Configuration examples
Send directly
But the sharing of global memory is just the first part of the full Peer Cop service.
Since the gobal memory architecture requires a setup (or configuration) for both
communication partners, there is another subservice to communicate directly with
rather than Configure nodes. This service is somewhat like a master to slave
communication, where the master knows what data to send and the slave expects
data in a fixed layout and uses this data in a fixed manner (like Terminal I/O). The
limit of data that can be sent from the master to the slave is also 32 words. This
mode is not global data, since it is sent from one node directly and explicitly to one
other node. The sender specifies this as specific output and the receiver as specific
input (this specification is hardwired on nonintelligent modules like Terminal I/O).
The specific output and input words are also assigned to holding registers when a
PLC makes use of this Peer Cop service.
Since both, global and specific data transfer, depend on scan time of the PLC’s
which provide and use this data in their logic, there is no big performance difference
with the transfer from one holding register to the other registers.
33002204 12/2010
943
Configuration examples
Configuration of Peer Cop
Define Peer Cop functionality
Before configure a Peer Cop you must activate the check box Peer Cop in the dialog
box Select Extensions.
NOTE: Since every PLC can be connected to up to 3 different Modbus Plus network
segments, you can setup Peer Cop for every connection separately (remember Peer
Cop is reduced to one segment, it doesn’t work through bridges).
944
33002204 12/2010
Configuration examples
Peer Cop settings
To configure a Peer Cop, proceed with the following steps:
Step
33002204 12/2010
Action
1
In the window PLC Configuration with the menu command Config. Extensions
→Peer Cop open the dialog box Peer Cop.
2
Assume the default value 100 in the text field Expansion Size:.
Note: This text field is just a space of memory (in words) that gets reserved for
future changes (in offline mode) that shall not cause the necessity for a complete
download (this is especially importent for direct application setup at a plant).
3
Select the option button Link 0 (CPU) in the area Go To.
4
Assume the default value 500 in the text field Health timeout (msec.):.
Note: The Health timeout value has the same meaning as it has in the I/O map
for local and remote I/O.
5
Select the option button Hold on timeout in the area Last value.
Representation of the dialog:
945
Configuration examples
Global data transfer
Global Input
For Global Input proceed as follows:
Step
Action
1
For global data transfer open the dialog box Gobal Input by clicking the
command button Input... in the area Global.
2
Select node 10 in the list box of the left side of the dialog box.
3
Enter the Destination register, the index, the length and the Bin/BCD Code in the
text field of the dialog box, as shown in the figure.
Representation of the dialog box:
Result: The holding register 400040 gets the first word of global output data of
node 10, therefore this is global input data for this PLC. If the length value is
higher, lets say 2, register 400041 would get the second word of global output
data of node 10. The index value declares with what word the assignment shall
start, in this case with the first word. The BIN/BCD column gives you the choice
of getting the global data formatted either into the usual binary format or into
binary coded decimals.
The index value may not be higher than 32, since every node can provide a
maximum of 32 word only for global output data. The lenght value may also not
be higher than 32 for the same reason.
4
946
Close the dialog box Global Input with the command button OK.
33002204 12/2010
Configuration examples
Global Output
For Global Output proceed as follows:
Step
33002204 12/2010
Action
1
Open the dialog box Gobal Output by clicking the command button Output... in
the area Global.
2
Enter the Source register, the length and the Bin/BCD Code in the text field of
the dialog box, as shown in the figure.
Representation of the dialog box:
3
Close the dialog box Global Output with the command button OK.
947
Configuration examples
Specific data transfer
Specific Input
For Specific Input proceed as follows:
Step
Action
1
For specific data transfer open the dialog box Specific Input by clicking the
command button Input... in the area Specific.
2
Enter the Destination register, the length and the Bin/BCD Code in the text field
of the dialog box, as shown in the figure.
Representation of the dialog box:
Result: If node 10 has declared some specific output, which gets delivered with
every token cycle on the Modbus Plus network segment (which is usually faster
than the updating by the controller’s user logic), that gets sent to holding register
400040. And if it is more than one word, it gets stored in the following holding
register, up to 400019 in this example. The formatting can also be either binary
or binary coded decimals.
3
948
Close the dialog box with the command button OK.
33002204 12/2010
Configuration examples
Specific Output
For Specific Output proceed as follows:
Step
Action
1
Open the dialog box Specific Output by clicking the command button Output...
in the area Specific.
2
Enter the Destination Reference register, the length and the Bin/BCD Code
option in the text field of the dialog box, as shown in the figure.
Representation of the dialog box:
Result: The values or registers 300030 to 300032 will be sent to node 20 (Target
Source) in binary format.
3
33002204 12/2010
Close the dialog box with the command button OK.
949
Configuration examples
E.8
Compact Example
Editing Local Drop
Introduction
This section describes the configuration of the first (local) drop.
When editing the first (local) drop the modules must be set with their I/O references
before the individual modules can be parameterized.
NOTE: The communication module MVB258A is parameterized in the TCN tool
(Train Communication Network). A parameterization file (binary file) is generated
and imported into the Concept parameter dialog.
Compact controller
950
33002204 12/2010
Configuration examples
Defining Drops
To define drops proceed as follows in the PLC Configuration window:
Step
33002204 12/2010
Action
1
Select PLC Selection.
Response: The PLC Selection dialog is opened.
2
Select the Compact PLC family and a PC-E984-258. Using OK return to the
PLC Configuration window.
3
Select I/O Map.
Response: The I/O Map dialog is opened and the first drop is automatically
entered in the table.
Dialog Representation
4
Select the drop from the Drop column.
Select the Edit... command button.
Response: You reach the module map.
951
Configuration examples
Mapping Modules and Specifying I/O References
To map the modules and specify the address ranges proceed as follows in the Local
TSX Compact Drop dialog:
Step
952
Action
1
Select the Module →... column.
Response: The I/O Module Selection dialog is opened.
2
From the Category column, select the <all> option.
Response: All modules are listed in the Modules column.
3
In the Modules column, select the MVB258A module.
Exit the dialog with OK.
Response: The module is inserted in the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example (see Dialog
Representation Local TSX Compact Drop).
5
In the In Ref and Out Ref columns, set the start references for the input and
output modules.
Note: Discrete Input References have the prefix 1 (e.g. 100001), Coil
References have the prefix 0 (e.g. 000001), Input Register References have the
prefix 3 (e.g. 300001) and Output Register References have the prefix 4 (e.g.
400001).
Response: The end reference of the available address range (In End or Out
End column) is entered automatically.
33002204 12/2010
Configuration examples
Dialog Representation
Following module mapping and I/O reference specification, the dialog looks like this:
33002204 12/2010
953
Configuration examples
Parameterization of Modules
To parameterize the individual modules proceed as follows in the Local TSX
Compact Drop dialog:
Step
954
Action
1
From the Rack Slot column, select line 1-3.
Response: The 1-3 text box has a dark background, i.e. the MVB258A module
has been selected for editing.
Note: The CPU module is not parameterized.
2
Select the Params command button.
Response: The AS-BMVB258A dialog is opened.
3
Select the Select command button.
Response: The Select MVB Import File dialog is opened.
4
Set the path of the parameterization file generated in the TCN tool, and exit the
dialog using OK.
Response: The selected parameterization file is displayed in the text box in the
AS-BMVB258A dialog.
5
Select the Do Import command button.
Response: The project data of the parameterization file is transferred to
Concept and displayed in the lower list box.
Dialog Representation
6
Exit the dialog using OK.
7
Repeat steps 1 to 2 for all the modules in the example.
Note: The modules are sometimes parameterized differently. Help with this can
be obtained from the corresponding help texts in the parameter dialog.
33002204 12/2010
Configuration examples
E.9
Atrium Example – INTERBUS Controller
Overview
This Chapter contains the step-by-step process for the configuration of an
INTERBUS controller with Atrium (PC based).
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
General
956
INTERBUS export settings in CMD
957
Edit local I/O drop
958
Edit remote I/O drop (import INTERBUS configuration)
962
955
Configuration examples
General
Introduction
The configuration of the INTERBUS is done using the PHOENIX software CMD. It
is initially stored as a file (*.SVC). This generated file is imported into Concept and
is visible in the I/O map of the Configurator.
Before the INTERBUS nodes are imported, set up the first drop (Atrium I/O) with the
CPU board (180-CCO-121-01, 180-CCO-241-01 and 180 CCO 241 11) and the
INTERBUS master (CRP-660-00/01). A maximum of two INTERBUS masters may
be inserted. The diagnostics of the field bus can take place with the CRP-660-0x
register in Concept.
956
33002204 12/2010
Configuration examples
INTERBUS export settings in CMD
Introduction
The CMD tool (Configuration Monitoring and Diagnostic tool) is used to configure the
INTERBUS. For information about this, refer to the corresponding chapter in the
PHOENIX user manual
Preconditions
The serial interface of the host computer and the diagnostic interface of a PC104
board (RS232, to connect to the CMD tool) must be linked with a V24 cable.
Implementing Export Settings
Before you import the configuration into Concept, carry out the following settings in
the CMD tool:
Step
1
Select Configuration →Controller Board →Type....
2
Select IBS PC104 SC-T.
3
Deactivate the control button Automatic Recognition, select version≤4.40
firmware from the list and confirm your selection with OK.
4
Select File →Operating Mode...
Response: The Operating Mode dialog is opened.
5
Activate the Configuration (Online) option button and exit the dialog using OK.
6
Select from Configuration →Controller Board →Control the command
Activate Configuration Frame.
Confirm with Yes.
Result: A configuration frame is generated.
7
Select Configuration →Configuration Frame →Read Again (from Memory).
Result: The configuration is read into the frame.
8
Under Configuration →Parameterization Memory →Write ASCII File select
the command INTERBUS Data (*.SVC)....
Response: The INTERBUS data is stored in a file.
9
Enter the directory and the file name in the open dialog and confirm the entry
using OK.
10
33002204 12/2010
Action
Select File →Save As....
Response: The INTERBUS project is saved.
957
Configuration examples
Edit local I/O drop
Introduction
In this section the configuration of the first (local) I/O station (drop) is described. The
processing sequence begins first with the definition of all I/O drops.
NOTE: To guarantee an error free transfer of the INTERBUS configuration, make
sure that sufficient memory is available. To optimise the storage allocation open the
PLC Memory Partition dialog (PLC Configuration →PLC Memory Partition).
When editing the first (local) drop the modules must be set with their I/O references
before parameters can be set for individual modules.
Atrium INTERBUS Controller
1
2
3
4
958
Programming device for Concept and CMD
V24 cable
PC104 board on a standard AT platine
INTERBUS configuration with the INTERBUS nodes
33002204 12/2010
Configuration examples
Define I/O drops
To define the I/O drops, in the PLC Configuration window carry out the following
steps :
Step
33002204 12/2010
Action
1
Select PLC Selection.
Result: The PLC Selection dialog is opened.
2
Select the PLC family Atrium and under CPU 180-CCO-241-01. Clicking OK will
return you to the PLC Configuration window.
3
Select I/O Map.
Result: The I/O Map dialog is opened and the first entry in the table is the I/O
drop which is automatically entered as Atrium I/O.
4
Select the last row in the table.
Select the command button Insert.
Result: In the Type column the second I/O drop Interbus S is entered.
Dialog display
5
Under Type you can still select the following for Interbus S:
z Interbus S
z Interbus S (PCP)
6
Select the line 1 (Atrium I/O).
Select the command button Edit.
Result: The module mapping appears.
959
Configuration examples
Setting I/O references
In the dialog field Local Atrium I/O Drop the INTERBUS Master CRP-660-00 is
automatically entered in the I/O map.
To specify the I/O references, in columns In Ref and Out Ref enter the start
references. After the start references have been entered, the end reference for the
available address area of the component is shown.
NOTE: Input register references have the prefix 3 (e.g. 300001) and output register
references have the prefix 4 (e.g. 400001).
Dialog display
960
33002204 12/2010
Configuration examples
Set Module Parameters
To set parameters for the INTERBUS master in the Local Atrium I/O Dropdialog
proceed in the following way:
Step
Action
1
In column Slot select the line 2.
Result: The text field 2 will then have a dark background, i.e.. the module CRP660-00 is selected for editing.
Note: Parameters are not set for CCO-24000 module.
2
Select the Params... command button.
Result: The CRP-660-00 dialog is opened.
3
Press the options button, as shown in the following picture, and exit the dialog
by clicking on OK.
Note: Help with setting parameters is obtained via the dialog box’s help text.
Dialog display
4
Leave the Local Atrium I/O Drop dialog by clicking on OK.
Edit remote I/O drop
To edit the remote I/O drop open the dialog box INTERBUS Drop 2. This dialog box
will take you to the I/O Map dialog box, when you click on the command button
Edit... of the second I/O drop (INTERBUS).
33002204 12/2010
961
Configuration examples
Edit remote I/O drop (import INTERBUS configuration)
Introduction
The INTERBUS configuration import process is described in this section. The map
for the I/O reference is in the import dialog, before the transfer of the configuration
file is run.
NOTE: The module parameters are set in the CMD tool (see CMD tool user
manual), because the imported modules are not recognized in Concept.
Atrium INTERBUS Controller
1
2
3
4
962
Programming device for Concept and CMD
V24 cable
PC104 board on a standard AT platine
INTERBUS configuration with the INTERBUS nodes
33002204 12/2010
Configuration examples
Setting I/O references
To set the address area follow the following steps in the INTERBUS Drop 2 dialog :
Step
33002204 12/2010
Action
1
Select the command button Import....
Result: The Import IBS Configuation is opened.
2
Activate the checkbox Overwrite IBS drop.
Result: The checkbox Do I/O mapping is made available.
3
Activate the Do I/O mapping checkbox.
Result: The Map Discretes to 3x/4x area checkbox and the text fields Input 3x
and Output 4x are made available.
4
Deactivate the checkbox Map Discretes to 3x/4x.
Result: The textfields Input 1x and Output 0x are made available.
5
In the textfields Input 3x and Output 4x enter the value 100.
Result: The 3x and 4x address areas of the imported components start with the
references 300100 and 400100.
Note: The 1x- and 0x address areas contain the predefined value 1, i.e. these
address area begin with 100001 and 000001.
Dialog display
6
You can exit the dialog with OK.
Result: The dialog Select Import File is opened.
7
Enter the path in the *.SVC configuration file.
Select OK.
Result: The dialog Import Status is opened, the file transfer starts and the
import status is shown.
8
After the transfer (100%) close the dialog.
Result: The imported INTERBUS configuration is shown in the INTERBUS
Drop 2 in the I/O map.
963
Configuration examples
Dialog display
After the INTERBUS configuration the dialog looks, for example, as follows:
964
33002204 12/2010
Configuration examples
E.10
Momentum Example - Remote I/O Bus
Overview
This Chapter contains the step-by-step process for the configuration of a remote I/O
bus (Momentum).
What's in this Section?
This section contains the following topics:
Topic
General Information
33002204 12/2010
Page
966
Editing local drop
967
Example 10 – Editing Remote Drops (I/O Bus)
971
965
Configuration examples
General Information
Introduction
TSX Momentum is a modular system. Bus adapters (e.g. 170 INT 110 00) and CPU
adapters (e.g. 171-CCC-760-10-IEC) work in conjunction with an I/O unit as
independent modules. In order to function properly, each I/O unit must be equipped
with an adapter.
966
33002204 12/2010
Configuration examples
Editing local drop
Introduction
This section describes the configuration of the first (local) drop. The processing
sequence begins first of all with the definition of all drops.
When editing the first (local) drop the modules must be set with their I/O references
before parameters can be set forindividual modules.
Momentum – remote controller with I/O bus
1
2
3
4
5
6
7
33002204 12/2010
Host Computer
I/O unit e.g. 170-AAI-030-00
Interface adapter
CPU adapter e.g. 171-CCC-760-10-IEC
I/O bus interface e.g. 172-PNN-210-22
Bus adapter e.g. 170-INT-110-00
I/O unit e.g. 170-AMM-090-00
967
Configuration examples
Defining Drops
To define drops proceed as follows in the PLC Configuration window:
Step
968
Action
1
Select PLC Selection.
Response: The PLC selection dialog is opened.
2
Select the PLC family Momentum and CPU 171-CCC-760-10-IEC. Use OK
return to the PLC Configuration window.
3
Select I/O Map.
Response: The I/O Map dialog is opened and the first drop is automatically
entered in the table.
4
Select the last line in the table.
Select the Insert command button.
Response: The second drop is entered in the Type column.
Note: Only one I/O bus can be configured.
Dialog display
5
Select the drop from the Drop column.
Select the Edit... command button.
Response: You reach the module map.
33002204 12/2010
Configuration examples
Mapping Modules and Specifying I/O References
To map the modules and specify the address ranges proceed as follows in the Local
Quantum Drop dialog:
Step
Action
1
Select the Module →... column.
Response: The I/O Module Selection dialog is opened.
2
From the Category column, select the <all> option.
Response: All modules are listed in the Modules column.
3
Select from the column Modules, the moduleAAI-030-00.
Exit the dialog with OK.
Response: The module is inserted in the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example (see Local Momentum
drop).
5
In the In Ref and Out Ref columns, set the start references for the input and
output modules.
Note: Discrete Input References have the prefix 1 (e.g. 100001), Coil
References have the prefix 0 (e.g. 000001), Input Register References have the
prefix 3 (e.g. 300001) and Output Register References have the prefix 4 (e.g.
400001).
Response: The end reference (column In.End. or Out.End) of the available
address range is automatically entered.
Dialog display
Following module mapping and I/O reference specification the dialog looks like this:
NOTE: With this addressing the 8 measurements of the AAI-030-00 are to be found
in the words 300001-300008. The parameters are in the words 400001 and 400002.
33002204 12/2010
969
Configuration examples
Set Module Parameters
To set parameters for the module proceed as follows in the Local Momentum Drop
dialog:
Step
Action
1
Select the Params command button.
Response: The 170-DDI-353-00 dialog is opened.
2
Select the signal conditions for the input and output channels from the list boxes
and exit the dialog using OK.
Note: Help with this can be obtained from the corresponding help text in the
parameter dialog.
Response: The parameter settings are automatically allocated to the addresses
400001 and 400002.
Dialog display
3
Exit the dialog using OK.
Response: You return automatically to the I/O Map dialog.
Editing Remote Drops (I/O bus)
To edit the remote drop open the RIO I/O Bus Drop dialog. This dialog is reached
via the I/O Map dialog by pressing the Edit... command button in the second drop
(I/O bus).
970
33002204 12/2010
Configuration examples
Example 10 – Editing Remote Drops (I/O Bus)
Introduction
This section describes the configuration of the Momentum I/O bus. The drop has
already been defined in Editing the First (local) Drop (see page 967).
When editing the I/O bus the modules must be specified with their I/O references
before the individuals modules can be parameterized.
Momentum – remote controller with I/O bus
1
2
3
4
5
6
7
33002204 12/2010
Host Computer
I/O unit e.g. 170-AAI-030-00
Interface adapter e.g. 172-PNN-210-22
CPU adapter e.g. 171-CCC-760-10-984
I/O bus interface
Bus adapter e.g. 170-INT-110-00
I/O unit e.g. 170-AMM-090-00
971
Configuration examples
Mapping Modules and Specifying I/O References
To map the modules and specify the address ranges proceed as follows in the Local
TSX Compact Drop dialog:
Step
Action
1
Select the Module →... column.
Response: The I/O Module Selection dialog is opened.
2
From the Category column, select the <all> option.
Response: All modules are listed in the Modules column.
3
Select from the column Modules, the moduleAMM-090-00.
Exit the dialog with OK.
Response: The module is inserted in the I/O map.
4
Repeat steps 1 to 3 for all the modules in the example (see Local Quantum
Drop dialog representation).
5
In the In Ref and Out Ref columns, set the start references for the input and
output modules.
Note: Discrete Input References have the prefix 1 (e.g. 100001), Coil
References have the prefix 0 (e.g. 000001), Input Register References have the
prefix 3 (e.g. 300001) and Output Register References have the prefix 4 (e.g.
400001).
Response: The end reference (column In.End. or Out.End) of the available
address range is automatically entered.
Dialog display
Following module mapping and I/O reference specification the dialog looks like this:
NOTE: With this addressing, the 4 measurements of the AMM-090-00 are to be
found in the words 300009-300013. The parameters are in the words 400009400013.
972
33002204 12/2010
Configuration examples
Set Module Parameters
To set parameters for the module proceed as follows in the RIO I/O bus drop dialog:
Step
33002204 12/2010
Action
1
Select column No. line 1.
Response: The 1 text box has a dark background, i.e. the AMM-090-00 module
has been selected for editing.
2
Select the Params command button.
Response: The 170-AMM-090-00 dialog is opened.
3
Select the signal states for the input and output channels from the list boxes and
exit the dialog using OK.
Note: Help with this can be obtained from the help text in the parameter dialog.
Response: The parameter settings are automatically allocated to the addresses
400009-400013.
Dialog display
973
Configuration examples
E.11
Momentum Example - Ethernet Bus System
Overview
This chapter contains step-by-step instructions for the configuration of an Ethernet
bus system with Momentum.
What's in this Section?
This section contains the following topics:
Topic
Configure Ethernet
974
Page
975
Network Configuration in Different Operating Systems
976
Editing local drop
986
Create online connection
990
33002204 12/2010
Configuration examples
Configure Ethernet
Preconditions
To configure an Ethernet bus system, the following preconditions must be fulfilled:
z PCI network cards in the host computer
z Installation of the network card driver
z Setting Ethernet interface parameters
z Addressing the M1 Ethernet CPU
Installing the PCI network card
For a link to an Ethernet bus system an Ethernet interface located on a PCI network
card must be available in the host computer. This card can be upgraded in PCs, as
long as a PCI slot is available. Information about this can be found in the computer
manufacturer’s user manual.
Network configuration
Network configurations for different operating systems are given in section Network
Configuration in Different Operating Systems, page 976.
Installing Drivers
Following the installation of the PCI network card the drivers, which come with the
network card, must be installed.
To proceed further, the IP address of the network card is required (it may be
necessary to contact network administrator).
Addressing the M1 Ethernet CPU
The M1 Ethernet CPU does not have an IP address when supplied, and must
therefore be determined in the Ethernet / I/O Scanner dialog. The address for the
gateway and Subnet Mask is also determined in this dialog.
The IP address can be assigned via the system administrator or the BOOTP server.
NOTE: It is important to ensure that the IP address has not already been assigned
to another device. Double addressing causes an unforeseeable function in the
network.
After addressing, saving to Flash is recommended (Online Control Panel →Flash
Program...), so that the settings are not lost in case of a power outage.
33002204 12/2010
975
Configuration examples
Network Configuration in Different Operating Systems
Network configuration in Win 98
Declare this IP address in the operating system as follows:
Step
976
Action
1
Select Start →Settings →Control Panel →Network.
Response: The Network dialog box is opened.
Dialog display
2
Select the register Configuration.
Select the network connection TCP/IP.
33002204 12/2010
Configuration examples
Step
33002204 12/2010
Action
3
Select the Properties command button.
Response: The TCP/IP Properties dialog is opened.
Dialog display
4
Select the register IP Address and make the following settings.
Response: The programming device is then registered for network operation
with the IP address.
977
Configuration examples
Computer Identification in Win 98/NT
The information is used to identify the computer in the network:
Step
978
Action
1
Select Start →Settings →Control Panel →Network.
Response: The Network dialog box is opened.
2
Select the register Identification.
Enter the computer name, the name of the workgroup and a short description of
the computer.
Dialog display
3
Exit the dialog using OK.
33002204 12/2010
Configuration examples
Network configuration in Win NT
Declare this IP address in the operating system as follows:
Step
1
33002204 12/2010
Action
Select Start →Settings →Control Panel →Network.
Response: The Network dialog box is opened.
Dialog display
979
Configuration examples
Step
2
Action
Select the register Protocols.
Dialog display
Select the network connection TCP/IP Protocol.
980
33002204 12/2010
Configuration examples
Step
33002204 12/2010
Action
3
Select the Properties command button.
Response: The Microsoft TCP/IP Properties dialog box is opened.
Dialog display
4
Select the register IP Address and make the following settings.
Response: The programming device is then registered for network operation
with the IP address.
981
Configuration examples
Network configuration in Win 2000
Declare this IP address in the operating system as follows:
Step
982
Action
1
Select Start →Settings →Network and Dial-Up Connections.
Response: The Network and Dial-Up Connections window is opened.
2
Select the LAN Connection icon.
Response: The LAN Connection status dialog box is opened.
Dialog display
33002204 12/2010
Configuration examples
Step
33002204 12/2010
Action
3
Select the Properties command button.
Response: The LAN Connection Properties dialog box is opened.
Dialog display
4
Select the network connection Internet Protocol (TCP/IP).
983
Configuration examples
Step
984
Action
5
Select the Properties command button.
Response: The Internet Protocol (TCP/IP) Properties dialog box is opened.
Dialog display
6
Make the settings there.
Response: The programming device is then registered for network operation
with the IP address.
33002204 12/2010
Configuration examples
Computer Identification in Win 2000
The information is used to identify the computer in the network:
Step
33002204 12/2010
Action
1
Select Start →Settings →Control Panel →System.
Response: The System Properties window is opened.
2
Select the register Network Identification.
Dialog display
3
Select the Network ID command button.
Response: The assistant for creating a user on the network is started.
Or select the Properties command button.
Response: The Identification Changes dialog box is opened.
4
Exit the dialog using OK.
985
Configuration examples
Editing local drop
Introduction
This section describes the configuration of the local I/O station (Drop). The
processing sequence begins first of all with the definition of the drop.
When editing the local I/O station (Drop) the I/O unit must be specified with its I/O
references before parametering of the individual assemblies can take place.
NOTE: Only particular CPUs can be used for the Ethernet bus configuration.
The following CPUs are available:
171 CCC 980 30
z 171 CCC 960 30
z 171 CCC 980 20
z 171 CCC 960 20
z
Momentum - Ethernet Bus System
1
2
3
4
5
986
Host Computer
Ethernet network card
I/O unit e.g. 170-AMM-090-00
CPU adapter e.g. 171-CCC-960-20-IEC
Hub or Switch
33002204 12/2010
Configuration examples
Defining Drops
To define drops proceed as follows in the PLC Configuration window:
Step
Action
1
Select PLC Selection.
Response: The PLC selection dialog is opened.
2
Select the PLC family Momentum and CPU 171-CCC-960-20-IEC. Use OK
return to the PLC Configuration window.
3
Select I/O Map.
Response: The I/O Map dialog is opened and the first drop is automatically
entered in the table.
4
Select the drop from the Drop column.
Select the Edit... command button.
Response: You reach the module map.
Mapping Modules and Specifying I/O References
To map the modules and specify the address ranges proceed as follows in the Local
Quantum Drop dialog:
Step
33002204 12/2010
Action
1
Select the Module →... column.
Response: The I/O Module Selection dialog is opened.
2
From the Category column, select the <all> option.
Response: All modules are listed in the Modules column.
3
Select from the column Modules, the moduleAMM-090-00.
Exit the dialog with OK.
Response: The module is inserted in the I/O map.
4
In the In Ref and Out Ref columns, set the start references for the input and
output modules.
Note: Discrete Input References have the prefix 1 (e.g. 100001), Coil
References have the prefix 0 (e.g. 000001), Input Register References have the
prefix 3 (e.g. 300001) and Output Register References have the prefix 4 (e.g.
400001).
Response: The end reference (column In.End. or Out.End) of the available
address range is automatically entered.
987
Configuration examples
Dialog display
Following module mapping and I/O reference specification the dialog looks like this:
988
33002204 12/2010
Configuration examples
Set module parameters
To set parameters for the individual modules, proceed as follows in the Local
Momentum Drop dialog:
Step
33002204 12/2010
Action
1
Select the Params command button.
Response: The 170-AMM-090-00 dialog is opened.
2
Select the signal states for the input and output channels from the list boxes and
exit the dialog using OK.
Note: Help with this can be obtained from the corresponding help text in the
parameter dialog.
Dialog display
989
Configuration examples
Create online connection
Introduction
This chapter describes how a link is created between the programming device and
the Ethernet bus system.
Creating a link
For the link between the programming device and the Ethernet bus system use the
Concept main menu Online and proceed as follows.
Step
990
Action
1
Select menu commandLink....
Response: The Link to PLC dialog box opens.
2
From the list Protocol type select the link TCP/IP.
Response: The zone Protocol settings alters for the TCP/IP settings.
3
In the text box IP address or DNS hostname enter the IP address of the Ethernet
network card (PCI card).
Note: Make sure that the address in Concept matches the address in Network
settings of the operating system (see page 976).
Response: An online link exists between the programming device and the
Ethernet bus system, and all bus nodes are displayed in the list.
Dialog display
4
Exit the dialog using OK.
33002204 12/2010
Convert Projects/DFBs/Macros
33002204 12/2010
Convert Projects/DFBs/Macros
F
Converting projects/DFBs
At a Glance
The four main steps for converting projects/DFBs are as follows:
Step
Action
1
Exporting projects/DFBs/macros within the earlier version of Concept, see
Exporting project/DFB/macro (earlier version of Concept), page 992.
2
For information on installing the new version of Concept, see Installing new
versions of Concepts, page 993.
3
For information on importing projects/DFBs/macros, see Importing
project/DFB/macro, page 993.
4
For information on editing projects/DFBs/macros, see Editing the
project/DFB/macro, page 993.
Converting EFBs
CAUTION
Risk of losing data
If user-defined EFBs are being used in the project (EFBs which have been created
manually), the current version of the EFB toolkit must be used to convert them (File
→Concept library…). The Concept converter is not able to convert user-defined
EFBs.
Failure to follow these instructions can result in injury or equipment damage.
33002204 12/2010
991
Convert Projects/DFBs/Macros
Exporting project/DFB/macro (earlier version of Concept)
The procedure for exporting projects/DFBs/macros is as follows:
CAUTION
Risk of losing data
The following steps must be performed in the EARLIER version of Concept. The
new version of Concept may only be installed once all existing projects have been
exported.
Failure to follow these instructions can result in injury or equipment damage.
Step
Action
1
Start the Concept converter.
2
From File →Export... open the menu to select the export range.
3
Select the required export range:
z Project with used DFBs: All project information including the DFBs and data
structures used within the project (derived data types) will be exported.
z Project with all DFBs + macros: All project information including all the
DFBs and data structures (derived data types) will be exported.
z Project without DFBs: All project information including all data structures
(derived data types), but excluding DFBs and macros will be exported.
z Single DFB with used DFBs/single macro: Only the selected DFB/macro
will be exported.
Reaction: The select export data dialog box will be opened.
992
4
Different file extensions must be selected depending on the element to be
exported:
z Exporting projects: From the Format list select the extension .prj.
z Exporting DFBs: From the Format list select the extension .dfb.
z Exporting macros: From the Format list select the extension .mac.
5
Select the project / DFB / macro and confirm with OK.
Reaction: The project/DFBs/macros/data structures (derived data types) will be
contained in the current directory as an ASCII data file (.asc).
6
Quit the Concept converter with File →Quit.
33002204 12/2010
Convert Projects/DFBs/Macros
Installing new versions of Concepts
CAUTION
Risk of losing data
Only install the NEW version of Concept if you have performed the previous steps.
Failure to follow these instructions can result in injury or equipment damage.
Follow the procedure described in the "Installation" chapter of the installation
instructions.
Importing project/DFB/macro
The procedure for importing projects/DFBs/macros is as follows:
Step
Action
1
Start the Concept converter.
2
From File →Import... open the select import projects/DFBs/macros dialog box.
3
Select the project/DFB/macro (data file format .asc) and confirm with OK.
Reaction: The project/DFBs/macros/data structures will be contained in the
current directory as Concept data files.
4
Quit the Concept converter with File →Quit.
Editing the project/DFB/macro
Start the Concept/Concept DFB and edit the project/DFBs/macros/data structures
in the usual way.
33002204 12/2010
993
Convert Projects/DFBs/Macros
994
33002204 12/2010
Concept ModConnect
33002204 12/2010
Concept ModConnect
G
Introduction
This chapter describes how to integrate third party modules into the Concept I/O
map and how to remove it.
What's in this Chapter?
This chapter contains the following sections:
Section
33002204 12/2010
Topic
G.1
Introduction
G.2
Integration of Third Party Modules
G.3
Use of third party module in Concept
Page
996
997
1000
995
Concept ModConnect
G.1
Introduction
Introduction
Overview
Information on hardware and I/O modules is stored in the Concept System
Information Database (SysInfDb). This database is maintained and updated by
Schneider and included with every Concept release.Nevertheless, Concept is able
to support new I/O modules without having to wait for a new release. That's where
the ModConnect Tool comes in - it takes a textual module description (MDC) and
adds this information into the SysInfDb. This means that supplier of a new I/O
module, who wants this module to be available in Concept, must also deliver an
MDC file which describes the characteristics of this module.
Once installed, the I/O modules have the same functionality as existing Schneider
Automation modules. This includes the ability to set module parameters and to
display an online help.
For the installation of new modules, the third party module manufacturer has to
supply a disk which contains a specific MDC file and the help information.
NOTE: The MDC file is dependent on the version of Concept so if you upgrade your
Concept version, make sure you get also an upgraded version of your previously
used MDC files. You will have to reinstall them.
996
33002204 12/2010
Concept ModConnect
G.2
Integration of Third Party Modules
Introduction
This chapter describes the procedures which have to be used in Concept
ModConnect in order to integrate third party modules into Concept or to remove it.
What's in this Section?
This section contains the following topics:
Topic
33002204 12/2010
Page
Integrating new Modules
998
Removing Modules
999
997
Concept ModConnect
Integrating new Modules
Precondition
The specific MDC file for the new module has to be available.
Integrating new Modules
For integrating new modules, proceed the following steps:
Step
Action
1
For starting the application select ModConnect Tool in the Concept programm
group.
Reaction: Concept ModConnect displays its main window. If any Modules have
been installed, a lis of installed modules is shown.
2
Copy the MDC file and the help file supplied with module to the Concept
installation path.
3
Select File →Open Installation File...
Reaction: A dialog for selection the specific MDC file is opened.
4
Set the correct path to the MDC file and select it (e.g. SAMPLE.MDC). Confirm
with OK.
Reaction: The path including the name of the MDC file is now displayed in the
Select Module dialog along with the defined modules.
5
Select the module you want to add and click Add Module or in the case of
multiple entries click on the Add All button. You may additionally click the
Browse button to return to the Open file dialog where you can select another
.MDC for evaluation.
6
Click on the Close button to return to the main window.
Reaction: The main window will now be displayed with the module information
appearing in the Imported Modules in Concept Database window. By clicking
on the added module (to select it) the module details are shown. With Help →
Help on Module the help of the selected module can be displayed.
7
Select File →Save Changes to save the changes data base.
8
Select File →Exit for terminating Concept ModConnect.
Reaction: The installed modules are now avaiable in the Concept I/O map
(see page 1000).
Upgrate of Concept
NOTE: The MDC-File is dependent on the version of Concept so if you upgrade your
Concept version, make sure you get also an upgraded version of your previously
used MDC files. You will have to reinstall them.
998
33002204 12/2010
Concept ModConnect
Removing Modules
Removing Modules
For removing modules, proceed the following steps:
Step
33002204 12/2010
Action
1
For starting the application select ModConnect Tool in the Concept programm
group.
Reaction: Concept ModConnect displays its main window with a lis of the
installed modules.
2
Select the module you want to remove and select File →Remove selected
Module.
Reaction: The Confirm IOModule Removal dialog is displayed.
3
Selecting OK, causes the removal of the module from Concept.
Reaction: The module is no longer listed in the main window of Concept
ModConnect or in the I/O Module Selection list box of Concept.
Note: When removing modules. If the module has been used in existing Concept
projects, the integrity of these projects will be compromised.
4
Select File →Save Changes to save the changes data base.
5
Select File →Exit for terminating Concept ModConnect.
Reaction: The installed modules are now avaiable in the Concept I/O map
(see page 1000).
999
Concept ModConnect
G.3
Use of third party module in Concept
Use of Third Party Modules in Concept
Precondition
The modules have to be installed according to the procedure Integrating new
Modules, page 998.
Insert module to I/O Map
To insert a module to the I/O map, proceed the following steps:
Step
1
Start Concept.
2
Open the configurator with Project →Configurator.
3
Open the I/O map with I/O map... →Edit....
4
Open the I/O Module Selection dialog by clicking on ... at the Module column.
Reaction: The third party modules appear in the Other column.
5
Select the module by clicking.
Reaction: A short description appear at the top of the dialog. You may press the
Help on Module button to display the module’s help file supplied by the vendor.
6
Click on OK (or doubleclick on the module) to insert the module the the I/O map.
Reaction: The I/O Module Selection dialog is cloes and the selected module is
inserted in the I/O map.
7
For entering the module’s parameters (if available), select the Rack-Slot column
of the module and click on the Params button.
Reaction: The parameter screen for the selected dialog is opened.
8
Set the parameters for the module and confirm with OK.
9
Enter the input and output references for the module.
10
1000
Action
Confirm the I/O map with OK and save the project with File →Save project.
33002204 12/2010
Convertion of Modsoft Programs
33002204 12/2010
Convertion of Modsoft Programs
H
Introduction
This information provides you with the necessary process required to change
previously generated Modsoft derived Ladder Logic programs into the Concept
environment.
What's in this Chapter?
This chapter contains the following topics:
Topic
Introduction
33002204 12/2010
Page
1002
How to Convert a Modsoft Program
1004
Exceptions
1005
1001
Convertion of Modsoft Programs
Introduction
Overview
For the convertion of an existing Modsoft program to a valid Concept 984 Ladder
Logic project the Mosdsoft Converter is used. The Modsoft Converter provides
current Modsoft users with a migration path to the 984 Ladder Logic for Windows
environment. The Modsoft Converter requires no previous knowledge of the
Concept programming environment. The term project is synonymous with a Modsoft
program.
Starting the Modsoft Converter
Windows 98, Windows 2000 or Windows NT allows you to run the program from the
Start menu, by selecting Modsoft Converter in the Concept programm group.
The Modsoft .ENV File
For the convertion the Modsoft .ENV file is needed. The .ENV file contains all the file
information pertaining to the Modsoft program.
The Modsoft .ENV file contains the following files:
z .CFG Configuration file
z .PRG Ladder Logic file
z .PCM Network comments
z .PCT Network comments
z .ASC ASCII file
z .USL User Loadables
z .RFD Reference presets set by the user in the Modsoft Reference Data Editor
z .REF Reference contents contained in the PLC, from an upload
z .RSF Reference symbols
The convert process requires the .CFG file to be present in the .ENV file. If it does
not exist, an dialog is displayed indicating that the .ENV file does not reference a
.CFG file. All other files are optional.
By forcing you to enter the Modsoft *.ENV filename, some of the validation is
avoided that would otherwise be required if you were allowed to enter a *.PRG and
*.CFG name separately, i.e. Loadables (DX, User and EXE), state ram and builtin
functions.
The first 5 lines of the .ENV file contain the path to the .ENV file. Be sure that the
location of the .ENV file is as it is described; otherwise the conversion seems to be
OK, but does not create a valid Concept application.
1002
33002204 12/2010
Convertion of Modsoft Programs
Incompatibilities
Due to differences in "address calculations in the configuration table" between
Modsoft 2.6 and Concept 2.2 or later, the same Modsoft program loaded in a PLC
and converted using the Modsoft Converter will cause a configuration miscompare
in certain page zero locations. This will not affect the validity of the converted
program.
Invalid PLC Types
If the Modsoft PLC type is not legal for Concept, a PLC Selection dialog box occurs
and you have to select a compatible PLC. Please note that in this case the I/O map
and other configuration elements will be defaulted or cleared.
Handling of SY/MAX
SY/MAX programs converted to Modsoft file format will migrate to the Quantum PLC
type. The Modsoft Convert utility can then bring the SY/MAX program into Concept.
Modsoft Version
The Convert utility handles Modsoft file format supported in revision 2.2 or greater.
Handling of SFC and Macros
Modsoft does allow the user to save a Ladder Logic program that consists of
undefined elements, and Concept needs to resolve those elements. The Modsoft
Ladder Logic program is converted without performing any validity checks against
the Configuration. When the Modsoft *.prg file contains either SFC or Macros the
convert process is aborted and an dialog is displayed informing you to return to
Modsoft and use Segment Status →Commands →Convert to File. This process
expands the Macros and translates the SFC elements.
Handling of I/O Map
Modsoft sets a default I/O map size of 512. Concept does not, but calculates the size
as required. Uploading a Controller that has been downloaded with Modsoft will
cause a miscompare. You are allowed to continue.
Handling of References
Modsoft can have two types of reference data or none at all. There exists online
reference data information (RAM) if you have uploaded from the PLC. There are
also references defined using the offline Reference Data Editor. When both types of
data exist in the .env file, the convert utility first imports the online references then
overlays the offline reference data.
33002204 12/2010
1003
Convertion of Modsoft Programs
How to Convert a Modsoft Program
Precondition
For converting a Modsoft program the Modsoft .ENV file (see page 1002) is
necessary. The .ENV file contains all the file information pertaining to the Modsoft
program. Once selected the conversion takes place and you are prompted to a Save
as dialog.
How to Convert a Mosdsoft Programm
For converting a Modsoft programm, proceed the following steps:
Step
1
1004
Action
Open the Modsoft Converter.
2
Select File → Convert....
3
Select the drive and the directory, where to find the Modsoft .ENV file. (The file
will be found in the Modsoft program directory, e.g. C:\Modsoft\Programs.)
4
Pick the file from the list.
5
Start the convertion with Convert.
Reaction:
The convertion is started.
z A convert progress dialog is displayed after the validity checks on the *.ENV
file are performed. The first line of the dialog indicates the section currently
being converted and the second line indicates progress as it pertains to the
whole convert process.
z f any errors, such as Out of memory, Out of disk space or File access
errors, occur during the convert process, an error dialog is displayed.
z An operation completed error free results in the automatic display of the Save
as Concept project dialog. The default name of the project, displayed in the
Save project dialog, is the *.ENV filename prompt.
6
You can then change the project name and the directory in which Concept
project will be saved.
Reaction: If the project name selected already exists a confirmation dialog is
displayed.
Note: Saving the Modsoft converted program as a Concept project does not
have to be done at this time, you can still save using the File →Save project as
menu item.
33002204 12/2010
Convertion of Modsoft Programs
Exceptions
Description
0x and 1x references in a Modsoft program are converted to a Located Variable with
data type BOOL in Concept. This data type is compatible with the use of these
references.
However, 3x and 4x are converted to integer.
NOTE: This straight conversion precludes both Modsoft bit defination and floating
point types.
Example
If you have the following defined in Modsoft:
REF
SYMBOL
DESCRIPTOR
000001
located_0x_boolean
located 0x boolean descriptor
100001
located_1x_boolean
located 1x boolean descriptor
300001
BIT
/16
400100
400200
400300
/1
bit_16_of_3000001
16th bit of 300001 descriptor
incoming_integer
incoming integer descriptor
outgoing_interger
outgoing flt32 descriptor
bit_1_of_400300
bit 1 of 400300 descriptor
A conversion of the above to Concept using the Convert program yields:
33002204 12/2010
Variable Name
Data Type
Address
Comment
located_0x_boolean
BOOL
000001
located 0x boolean descriptor
located_1x_boolean
BOOL
100001
located 1x boolean descriptor
bit_16_of_3000001
INT
300001
16th bit of 300001 descriptor
incoming_integer
INT
400100
incoming integer descriptor
outgoing_interger
INT
400200
outgoing flt32 descriptor
bit_1_of_400300
INT
400300
bit 1 of 400300 descriptor
1005
Convertion of Modsoft Programs
1006
33002204 12/2010
Modsoft and 984 References
33002204 12/2010
Modsoft and 984 References
I
Introduction
This chapter contains the Modsoft and 984 References.
What's in this Chapter?
This chapter contains the following topics:
Topic
33002204 12/2010
Page
Modsoft Keys with Concept Equivalents
1008
Modsoft Function Compatibility
1010
1007
Modsoft and 984 References
Modsoft Keys with Concept Equivalents
Keys
NOTE: When possible, the Ctrl key is used in place of the Modsoft Alt key.
Table of keys:
1008
Funtion
Modsoft 2.x Key
Concept Key
Normally open contact
’ or "
same
Coil
( or [
same
Normally closed contacts
/ or \
same
Horizontal short
=
same
Vertical short
|
same
Negative transitional contact
Alt+N
N
Positive transitional contact
Alt+P
P
Inserting a function block by name
Alt+F
Ctrl+F
Copy element(s)
Alt+F3
Ctrl+C
Delete element(s)
Alt+F4 or Del
Ctrl+X or Del
Paste
Alt+F5
Ctrl+V
Offset references
Alt+F6
Ctrl+H
Search
Alt+F7
F3
Search next
Alt+F8
F6
When online in direct mode,
Concept uses a nonmodal
dialog with accelerators for
search previous and search
next.
Network comments
Alt+C
Ctrl+M
Goto network
Alt+G
Ctrl+G
Insert network
Alt+I
Ctrl+I
Append network
Alt+A
Ctrl+A
Trace
Alt+T
Ctrl+T
Retrace
Alt+B
Ctrl+B or Ctrl+T
Dx zoom
Alt+Z
Ctrl+D
Goto node (1,1) of active network
Home
same
Goto node (7,11) of active network
End
same
Goto first network in current segment Ctrl+Home
same
Goto last network in current segment Ctrl+End
same
33002204 12/2010
Modsoft and 984 References
Funtion
Modsoft 2.x Key
Concept Key
Insert equation
Ins
Ctrl+Q
Append
-
Ctrl+A
Append equation
-
Ctrl+U
Delete current network
-
Ctrl+K
Copy to the clipboard
-
Ctrl+C
Undo
-
Ctrl+Z
Closing an mdi child window
-
Ctrl+F4
Switching to the next open mdi child
window
-
Ctrl+F6
Status Line Values
These Concept keys change the status line display value of the currently selected
reference:
A ASCII
H Hexidecimal
D Decimal (signed)
U Decimal (unsigned)
R Real
L Long (32 bit)
S Short (16 bit)
33002204 12/2010
1009
Modsoft and 984 References
Modsoft Function Compatibility
Not Supported Features
The following Modsoft functions are not supported in Concept:
Macros/macro programming
z SFC (use IEC SFC instead)
z Search of comments
z
User Interface Difference
Concept is an MS-Windows based application. Modsoft is a DOS based application.
Concept uses MS-Windows user interface standards and practices. Functions of
Concept with 984 Ladder editor are based on the pre-existing functions of Concept.
There are no exact similarities of specific user actions required to perform Concept
tasks as compared to Modsoft tasks.
Constant Sweep
Concept has no off line selection to set the constant sweep mode. This mode is
available from the Online Control Panel.
Once constant sweep has been set in the controller, you can upload the controller
and save the project. The constant sweep settings will be retained in the project. If
this project is downloaded, the constant sweep settings will be set.
NOTE: Any changes to the controller configuration cause the constant sweep
settings to be reset, i.e, constant sweep is disabled whenever the controller
configuration changes. Follow the steps above to reenable constant sweep.
How to Start the Constant Sweep
To set constant sweep before starting the controller, follow these steps:
Step
1010
Action
1
Create your configuration and program logic, offline.
2
Download your program to the controller. When the dialog appears asking Do
you want to start the controller?"click on the No button.
3
From the Online menu, choose Online Control Panel.
4
Set the constant sweep mode and sweep time.
5
Start the controller.
33002204 12/2010
Presettings for Modbus Plus
33002204 12/2010
Presettings when using Modbus
Plus for startup
J
Overview
This chapter provides a brief description of the presettings when using Modbus Plus
for first startup.
What's in this Chapter?
This chapter contains the following topics:
Topic
Installing the SA85/PCI85 with Windows 98/2000/XP
33002204 12/2010
Page
1012
Installing the SA85/PC185 in Windows NT
1016
Installing the Modbus Plus Driver in Windows 98/2000/NT
1018
Virtual MBX Driver for 16 bit application capability with Windows 98/2000/NT
1019
MBX Driver for connection between ModConnect Host interface adapters and
32 bit applications with Windows 98/2000/NT
1020
Remote MBX - Driver for Remote Operation
1021
Ethernet MBX - Driver for Modbus Plus Function via TCP/IP
1022
Establishing the hardware connection.
1024
1011
Presettings for Modbus Plus
Installing the SA85/PCI85 with Windows 98/2000/XP
Introduction
A Modbus Plus connection can be made using the SA85 or PCI85 adapters.
The difference between the adapters is in the bus used:
SA85 for ISA Bus
z PCI85 for PCI Bus
z
While the Modbus Node Address and Memory Based Address for the SA85 is set
directly on the card with the DIP switches, the address for the PCI85 is made during
the configuration in Windows.
SA85 Hardware settings
Carry out the following steps to configure the Hardware settings for the SA85:
Step
Action
1
Enter the Modbus node location (Modbus Plus Port Location) and the memory
based address in SA85 (see documentation "IBM Host Based Devices").
2
Install the SA85 as described in the "IBM Host Based Devices" documentation.
PCI85 Installation
Install the PCI85 (416 NHM 300 30 or 416 NHM 300 32) as described in the
"Modbus Plus PCI-85 Interface Adapter" 890 USE 162 00 documentation.
Driver installation
Install the Virtual MBX driver and then the MBX or Remote MBX driver.
See also:
Virtual MBX Driver for 16 bit application capability with Windows 98/2000/NT,
page 1019
z MBX Driver for connection between ModConnect Host interface adapters and 32
bit applications with Windows 98/2000/NT, page 1020
z Remote MBX - Driver for Remote Operation, page 1021
z
1012
33002204 12/2010
Presettings for Modbus Plus
Configuration
Carry out the following steps to configure the adapter after installing the driver:
Step
33002204 12/2010
Action
1
Open the Control Panel (Start →Settings →Control Panel).
2
Windows XP: Select the Printer and other Hardware icon.
3
Windows XP: Select the System icon.
4
Select the Hardware icon.
Result: The hardware wizard is called.
5
Select the Next command button.
6
Windows 98: Select the option Yes (Recommended).
Windows 2000/XP: Select the option Add/Troubleshoot a device.
Select the Next command button.
Result: Hardware detection is started.
7
Only for Windows 98: Select the Next command button.
Result: The hardware detection status is displayed.
8
Only for Windows 98: Select the Next command button.
Result: All hardware types are displayed in a list.
9
Select the hardware type MBX Devices for Modicon Networks, and press the
Next command button.
Result: The database with driver information is created.
10
Select the SA85-000 adapter or PCI85-000 and press the Next command
button.
Result: A memory range is automatically defined.
11
Select the Next command button.
Result: The automatically assigned device number and request mode (20 ms)
is displayed.
12
Select the Next command button.
Result: The software for the new hardware components is installed.
13
Select the Next command button.
Result: You are asked to shutdown the computer.
14
Press the No command button.
Result: The adapter is configured with the default settings.
1013
Presettings for Modbus Plus
Win 98: Edit configuration
Carry out the following steps to edit the configuration using Windows 98 after the first
configuration:
Step
Action
1
Open the Control Panel (Start →Settings →Control Panel).
2
Select the System icon.
Result: The System Properties window is opened.
3
Select the Device Manager tab.
4
Select the SA85-000 adapter or PCI85-000 and press the Properties command
button.
Result: The SA85-000/PCI85-000 Adapter Properties window is opened.
5
Select the Device Settings tab.
6
Make the changes as required. (See also the Help file LMBX9X on the driver
CD.)
7
Select the Resources tab to change the memory area.
8
Use the OK command button to exit the window.
Result: The changes are accepted by the system.
Win 2000/XP: Edit configuration
Carry out the following steps to edit the configuration using Windows 2000/XP after
the first configuration:
Step
1
1014
Action
Open the Control Panel (Start →Settings →Control Panel).
2
Windows XP: Select the Printer and other Hardware icon.
3
Select the System icon.
Result: The System Properties window is opened.
4
Select the Hardware tab.
5
Select the Device Manager... command button.
Result: The Device Manager window is opened.
6
Select the Network adapter →SA85-000 or PCI85-000.
7
Select the Properties command button.
Result: The SA85-000PCI85-000 Adapter Properties window is opened.
8
Select the Device Settings tab.
9
Make the changes as required. (See also the Help file LMBX9X on the driver
CD.)
10
Select the Resources tab to change the memory area.
11
Use the OK command button to exit the window.
Result: The changes are accepted by the system.
33002204 12/2010
Presettings for Modbus Plus
Peer Cop functions
Several parameter settings must be made to enable Peer Cop communication via
the adapter. The Peer Cop function is disabled by default, and should only be
enabled if your applications require Peer Cop communication.
To enable and set parameters for Peer Cop communication, start with the first steps
as with "Edit Configuration". In the SA85-000/PCI85-000 Adapter Properties
window, select the Peer Cop tab and make your settings as desired.
33002204 12/2010
1015
Presettings for Modbus Plus
Installing the SA85/PC185 in Windows NT
Introduction
A Modbus Plus connection can be made using the SA85 or PCI85 adapters.
The difference between the adapters is in the bus used:
SA85 for ISA Bus
z PCI85 for PCI Bus
z
While the Modbus Node Address and Memory Based Address for the SA85 is set
directly on the card with the DIP switches, the address for the PCI85 is made during
the configuration in Windows.
SA85 Hardware Settings
Carry out the following steps to set the SA85 hardware settings:
Step
Action
1
Set the Modbus node address (Modbus Plus Port Address) and the memory
based address on the SA85 (see documentation "IBM Host Based Devices").
2
Install the SA85 as described in the "IBM Host Based Devices" documentation.
PCI85 Installation
Install the PCI85 (416 NHM 300 30 or 416 NHM 300 32) as described in the
"Modbus Plus PCI-85 Interface Adapter" 890 USE 162 00 documentation.
Installing drivers
Install the Virtual MBX driver and then the MBX or Remote MBX driver.
Also see:
Virtual MBX Driver for 16 bit application capability with Windows 98/2000/NT,
page 1019
z MBX Driver for connection between ModConnect Host interface adapters and 32
bit applications with Windows 98/2000/NT, page 1020
z Remote MBX - Driver for Remote Operation, page 1021
z
1016
33002204 12/2010
Presettings for Modbus Plus
Configuration
Carry out the following steps to configure the adapter after installing the driver:
Step
Action
1
In the start menu, open the folder WinConX/MBXDriver (Start →Program →
WinConX).
2
Double-click on the MBX Driver Configuration icon.
Result: The dialog box MBX Driver configuration is opened.
3
In the Device Configuration register, click on the command button New.
Result: A list box will appear in the Device type column.
4
Select the option SA85 or PCI85 from the list.
Result: The dialog box SA85 configuration is opened.
5
Make the following settings. (also see Help file LMBX9X on the driver CD.)
Note: With the PCI85 you enter the Modbus Node address in the Node list box.
6
Exit the dialog box by clicking Close.
Result: The settings are accepted by the system.
Edit configuration
Carry out the following steps to edit the configuration after the first configuration:
Step
Action
1
In the start menu, open the folder WinConX/MBXDriver (Start →Program →
WinConX).
2
Double-click on the MBX Driver configuration icon.
Result: The dialog box MBX Driver configuration is opened.
3
Select SA85 from the Device configuration register.
4
Click on the command button Edit.
Result: The SA85 configuration dialog box is opened.
5
Make the following changes. (also see Help file LMBX9X on the driver CD.)
6
Exit the dialog box by clicking Close.
Result: The settings are accepted by the system.
Peer Cop functionality
Several parameter settings must be made to enable Peer Cop communication via
the adapter. The Peer Cop function is deactivated as standard, and should only be
enabled if your application requires Peer Cop communication.
To enable and set parameters for Peer Cop communication, start with the first steps
as with "Edit SA85 Configuration". In the dialog box SA85 configuration, select the
Peer Cop register and make your settings.
33002204 12/2010
1017
Presettings for Modbus Plus
Installing the Modbus Plus Driver in