O1878GB
7
Fire Expert
Contents
2 Quick guide to set up EcoStruxure Fire Expert account............................8
4 How to set up your EcoStruxture Fire Expert user account.................. 12
How to group and filter the active faults and disablements ...............................43
How to add a comment for a fault or a disablement...........................................44
O1878GB7 2
How to add comments in the Event wall view....................................................46
How to change the zone of an address..............................................................50
How to share access to your fire detection system ...........................................84
How to transfer the ownership of your fire detection system ............................85
O1878GB7 3
1 Introduction to EcoStruxure Fire Expert
1
1.1
1.2
1.3
Introduction to EcoStruxure Fire Expert
EcoStruxure Fire Expert
EcoStruxure TM Fire Expert is an online application for the efficient management of Esmi
Sense FDP fire detection systems. EcoStruxure Fire Expert allows you to remotely monitor and manage multiple fire detection systems.
You do not need to install any software - access the application online at ecostruxure-fireexpert.se.app
. EcoStruxure Fire Expert supports computers, mobile phones and tablets.
The minimum supported resolution for desktop use is 1920 x 1080. For details, see Tables
1: EcoStruxure Fire Expert compatible browsers
and
2: EcoStruxure Fire Expert platform support
.
Table 1: EcoStruxure Fire Expert compatible browsers
Browser Version
Microsoft Edge 103.x and newer
Google Chrome 103.x and newer
Apple Safari *) 15.5 and newer
*) On Apple devices the Safari version is essential, even if another browser is used.
Table 2: EcoStruxure Fire Expert platform support
System Version Notes
Android 11 and newer
Apple iOS
Microsoft Windows desktop
15.x and newer
10 or newer
Configuration management,
Customer care or Orientation map views are not supported.
Configuration management,
Customer care or Orientation map views are not supported.
The minimum resolution is
1920 x 1080.
Licenses
You need a license to use EcoStruxure Fire Expert. Licenses are either user-specific or system-specific. All licenses are valid until they are revoked. The billing cycle is one (1) year.
How to start to use EcoStruxure Fire Expert
To access EcoStruxure Fire Expert, you must get an invitation from your fire detection system administrator (if EcoStruxure Fire Expert is already in use in your location), or from a Schneider Electric representative. For more information, refer to Chapter
O1878GB7 4
1 Introduction to EcoStruxure Fire Expert
1.4
User levels and user rights
EcoStruxure Fire Expert has four user roles: Firesystem User , Fire system designer ,
Account Manager and Back Office user . User rights depend on the chosen user level.
Table 3: EcoStruxure Fire Expert user rights
End-user Fire Detection Company
Account manager
Firesystem user
Account manager
Back
Office user
Fire system designer
Firesystem user
Edit personal preferences
Edit organization details
Invite new organization
Edit user account
Delete user account
Manage ccc email
Edit organization account
Complete end-user purchase
Discontinue license
Receive license expiration notifications
Buy licenses
Manage firesystem
Assign license to firesystem
Receive push notifications
Share firesystem access
Transfer firesystem ownership
List users with access to fire system
Delete fire system
Accept shared fire system
Request premium user level pin
Request normal user level pin
Issue fire system zone test commands
Edit configurations
-
-
-
-
-
-
-
-
-
X
X
-
X
X
-
X
-
-
X
-
-
-
-
X
X 1
X
X
X
X
X
-
-
-
-
-
-
-
X
X
X
X
X
X 2
X
X 6
-
-
-
-
-
-
-
-
-
-
X
X
X
X
X
X
X
-
-
X
-
-
-
-
-
-
-
-
-
-
-
-
-
X
-
-
-
-
-
-
X
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
X
-
-
-
-
-
-
-
-
-
-
-
-
-
X
X
X 2
X
-
-
-
-
-
-
-
X
X
X
X
X 3
X 4
X
X 1
X
X
X
X
O1878GB7 5
1 Introduction to EcoStruxure Fire Expert
End-user
Account manager
Firesystem user
Account manager
Change configuration status
Send/activate configuration
View configuration
Capacity Calculator in configuration
Add new fire system
Fire system monitoring
Fire system list
Export maintenance test report or other events
Export address and zone list as configured
Address and Zone disablement
Check status of disabled addresses
Address LED activation
Address-based modification
Address Output testing
Disable/enable controls
Activate/deactivate test for controls
Activate fire test/Silence and reset fire alarms, faults and maintenance warnings
View and edit Orientation map
Contamination display with export report
FDP Capacity Calculation
Tool for designers
Esmi Impresia Device
Scanner
Require QR session for configuration activation
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
X
X 5
X
X 6
-
-
-
-
-
X 6
X 6
-
-
X 7 and 6
X 7 and 6
X 7 and 6
X 7 and 6
X 5 and 8
X 6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1) Push Notifications license required (FFS00704003).
-
-
-
-
-
Fire Detection Company
Back
Office user
Fire system designer
Firesystem user
-
-
-
-
-
-
-
-
X
X
X
X
4
4
4
4
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
X
-
-
X
X 5
X
X 3 or 6
X 4 and 5
X 3 or 6
X 3 or 6
X 3
X 3 and 4
X 7 and 3 or 6
X 7 and 3 or 6
X 7 and 3 or 6
X 7 and 3 or 6
X 5 and 8
X 3 or 6
-
X 4
X 4
O1878GB7 6
1 Introduction to EcoStruxure Fire Expert
2) Premium User personal license required.
3) Commissioning and testing package license required (FFS00704004).
4) Certified Fire Detection company user status required for configuration rights. Front office account manager gives the Certified user permission.
5) System View (FDP) (FFS00704002) license required.
6) Maintenance package license required (FFS00704005).
7) Requires session level 3 or 4 in FDP simultaneously.
8) Orientation Map license required (FFS00704006).
Licenses 5) System view (FFS00704002) and 8) Orientation Map (FFS00704006) will be inherited by the Fire Detection Company, Firesystem user, if the end-user of Fire Detection
Company has bought these licenses already for the system being managed.
O1878GB7 7
2
2.1
2 Quick guide to set up EcoStruxure Fire Expert account
Quick guide to set up EcoStruxure Fire Expert account
Set up a company account
1.
Get an invitation to EcoStruxure Fire Expert.
2.
Go to the online application via the link in the invitation email and register.
3.
Invite other users and add your fire detection systems.
2.2
Add an FDP fire detection panel
1.
Connect an Ethernet cable to your fire detection panel.
2.
Enter your fire detection panel’s identification UUID code into EcoStruxure Fire
Expert.
3.
Your system is now connected.
O1878GB7 8
3
3.1
Fire Expert user interface
Systems view
To open the Systems view, select Systems in EcoStruxure Fire Expert.
3.2
Figure 1: Systems view
In the Systems view, you can:
•
•
•
•
•
• view all your fire detection systems and their status (online/offline) view possible faults and disablements in your fire detection systems add new fire detection systems manage your fire detection systems (only firesystem users) create site plans (orientation map) view the contamination percentage of the detectors in your fire detection systems
My company view
NOTE: Only Account Manager level users can access the My company view.
To open the My company view, select My company in EcoStruxure Fire Expert.
O1878GB7 9
3.3
Figure 2: My company view
In the My company view, you can:
•
•
•
•
•
•
• see all other users in your company edit your company’s information invite new users and companies see and edit the profile of other users change the role of users delete users from your company edit your end-user company’s information
Licensing view
NOTE: Only Account Manager level users can access the Licensing view.
To open the Licensing view, select Licenses in EcoStruxure Fire Expert.
O1878GB7
Figure 3: Licensing view
In the Licensing view, you can:
•
• add subscriptions edit subscription information
10
3.4
•
• add licenses to subscriptions see the licenses for the systems that you see, own or that are shared to you
Customer Care view
NOTE: Only Back Office user level users can access the Customer Care view.
To open the Customer Care view, select Customer Care in EcoStruxure Fire Expert.
Figure 4: Customer Care view
In the Customer Care view, you can:
•
•
• see and complete license requests from partner companies see when auto-renewal is due see the already processed/purchased licenses
O1878GB7 11
4
4.1
4 How to set up your EcoStruxture Fire Expert user account
4.2
How to set up your EcoStruxture Fire Expert user account
Set up the user account
To access EcoStruxure Fire Expert, ask for an invitation from your fire detection system administrator (if EcoStruxure Fire Expert is already in use in your location) or from a
Schneider Electric representative. You will then receive an invitation email from [email protected].
Activate your user account
1.
Follow the link in the invitation email to activate your account.
2.
EcoStruxure Fire Expert opens.
3.
Fill in your personal information.
O1878GB7 12
4 How to set up your EcoStruxture Fire Expert user account
4.
Select the language to be used in FDP configuration and other functions (English as default).
5.
Create a password.
6.
Agree to accept the privacy policy and license terms and conditions of EcoStruxure
Fire Expert.
O1878GB7
7.
When you are ready, select Save .
NOTE: If you are the first admin user in your company, Fire Expert asks you to also complete your company information when you activate your user account.
13
4 How to set up your EcoStruxture Fire Expert user account
4.3
View and edit user information
1.
Go to the My account view.
2.
In the My account view, under General , you can:
•
•
• edit your personal information change the language to be used in FDP configuration change your password
O1878GB7
3.
Select Notifications to:
•
•
• select to send e-mail notifications select to send push notifications (separately for each device) select the notifications to be sent
14
4 How to set up your EcoStruxture Fire Expert user account
4.
Select Subscribe to get push notifications to your device.
NOTE:
You must have the Push notification license to receive push notifications.
Push notifications are device-specific. Select Subscribe in the device where you want to get the notifications.
Only mobile devices with an Android operating system are supported.
5.
If you selected push notifications, select Allow in the pop-up window to allow
EcoStruxure Fire Expert to send notifications to your device.
6.
Select Receive notifications to email to receive email notifications.
7.
Select the notification filters.
O1878GB7
NOTE: You can select filters separately for all of your fire detection systems.
15
4 How to set up your EcoStruxture Fire Expert user account
8.
If you are a certified user, you can purchase a personal Premium user license under
Licenses .
To purchase the license, select the license and then select Purchase .
9.
When you are ready, select Save .
4.4
View and complete company information
NOTE: Only Account Manager level users can view and complete company information.
View your company details from time to time to make sure that they are up to date.
1.
Go to the My company view.
O1878GB7 16
4 How to set up your EcoStruxture Fire Expert user account
2.
Select Manage company information
O1878GB7 17
4 How to set up your EcoStruxture Fire Expert user account
3.
Fill in the details of your company.
O1878GB7
The fields marked with an asterisk (*) are mandatory.
18
4 How to set up your EcoStruxture Fire Expert user account
4.
Fill in the billing information of your company.
O1878GB7
5.
When you are ready, select Save .
19
5
5.1
How to manage users
How to invite a new user to your company
NOTE: Only Account Manager level users can invite new users.
1.
Go to the My company view.
2.
Open the company information.
3.
Select Add new user .
O1878GB7 20
4.
Fill in the information for the new user. The fields that are marked with an asterisk (*) are mandatory.
NOTE: An email address can only be associated with one EcoStruxure Fire Expert account at a time.
5.
Select the user role for the new user: Account Manager , Firesystem user , Back Office user , or Fire system designer .
FO administrator can give configuration rights.
6.
Select Add .
5.2
O1878GB7
EcoStruxure Fire Expert sends an invitation email to the new user. If you have already invited a user but need to resend the invitation email, select Resend invite .
How to assign user roles to existing users
NOTE: Only Account Manager level users can assign user roles.
21
1.
Go to the My company view.
2.
Open the company information.
3.
Select the Manage icon for the user.
4.
Select the user role for the user: Account Manager , Firesystem user , or Back Office user .
5.
Select Save .
5.3
How to delete a user
1.
Go to the My company view.
O1878GB7 22
O1878GB7
2.
Open the company information.
3.
Select the Manage icon for the user.
4.
Select Delete user .
23
6 How to add a fire detection system
6 How to add a fire detection system
1.
To add an FDP fire detection panel, connect an Ethernet cable to your fire detection panel.
2.
Enter your fire detection panel’s identification UUID code into ExoStruxure Fire
Expert.
3.
Go to the Systems view.
4.
Select Add new system .
NOTE: The reference number for EcoStruxure Fire Expert FDP built in 3/4G modem is FFS00702579 with a SIM card and FFS00702580 without a SIM card.
O1878GB7 24
5.
The Add system page opens.
6 How to add a fire detection system
O1878GB7
6.
Fill in the system name.
25
6 How to add a fire detection system
7.
Fill in a group name, if you want.
You can use the group name to group the systems in the Systems view.
Example:
Here the system has “My FDP system” as the group name.
O1878GB7
NOTE: The group names are case sensitive.
NOTE: The Ungrouped/Grouped selection is inactive if there are no group names.
8.
Leave the 'Connected fire panel identifier' field empty to create a temporary identification UUID code.
Use the temporary identification UUID code to register an FDP system whose UUID is not yet known. Change the UUID later to the actual UUID.
9.
Fill in the location information for the fire detection system.
10. Select Add .
NOTE: To find out the identification UUID code of your fire detection panel, go to Main menu > Settings > System status . Select Export identity to export the identity to a memory stick.
NOTE: When a system is added, it takes a couple of minutes before it is online.
26
7
7.1
7.2
How to buy a license
License information
Accounts that have a license assigned to a system can access all features of EcoStruxure
Fire Expert available to that system. Accounts without a license can only see the overview of a system but not the possible faults and disablements. Configuration is possible without a license.
To buy a license, you need to have a subscription. If your account does not have a subscription, you need to add a subscription first.
The license activates immediately and can be used after purchase. The license will be invoiced later.
How to add a subscription
1.
Select Licenses . A list of subscriptions and licenses of your company opens.
2.
In the Subscriptions list, select Add subscription .
O1878GB7 27
3.
Fill in the information for a new subscription.
7.3
4.
Select Save .
When you have saved the new subscription, select Back to go back to the Subscriptions .
How to add a license
NOTE: To add a license, you need a subscription. If you do not have a subscription yet, refer to Section
for instructions.
1.
In the Subscriptions list, select the correct subscription under the name of your company.
O1878GB7 28
2.
In the Licensing view, select Add licenses .
3.
Use the + and buttons to select the license(s) to be added:
•
•
•
•
•
System view (FDP)
Push Notifications
Maintenance package
Commissioning and testing package
Orientation map
O1878GB7 29
4.
When you have added as many licenses as you need, fill in the Purchase reference .
O1878GB7
5.
Select Buy and confirm to buy the licenses.
License(s) added appears on the display.
6.
When you have saved the new licenses, select Back to go back to the Licensing view.
30
7.
Added licenses re-new automatically every year. If you want to disable the autorenew function, select Disable auto-renew . If auto-renew is disabled, the license is still valid until the end of the one-year period.
7.4
Assign the license to a system to use it.
How to assign a license to a system
1.
Go to the Systems view.
2.
Select Licenses of the system you want to license.
O1878GB7 31
3.
Select the license(s) that you want to activate.
The licenses that you can select have a green Select button.
4.
Select the subscription for which you want to assign the license.
O1878GB7 32
5.
Select Activate .
6.
The license is now assigned to the fire detection system.
O1878GB7 33
8 How to manage end-user companies
8
8.1
8.2
How to manage end-user companies
Fire Detection Company managing their end users
The fire detection company Account Manager can invite and accept end-user organizations to EcoStruxure Fire Expert. The invited company will be of end-user type by default and linked to your company.
The end-user company can buy licenses for their own use. The fire detection company
Back Office user can see in the Customer Care view the licenses and approve them for billing.
The fire detection company Account Manager can see in the Licensing view the end-user company subscription and the licenses assigned to it.
How to invite a new company
NOTE: Only fire detection company Account Manager level users can invite new companies.
1.
Go to the My company view.
2.
Select Invite new company .
O1878GB7 34
8 How to manage end-user companies
3.
Fill in the information for the company and the first admin user.
The fields that are marked with an asterisk (*) are mandatory.
NOTE: An email address can only be associated with one EcoStruxure Fire Expert account at a time.
4.
Select Save & Invite . EcoStruxure Fire Expert sends an invitation email to the admin user of the invited company.
8.3
O1878GB7
The invited company is instantly confirmed. The invited admin user can now access the
EcoStruxure Fire Expert.
End-user purchase approval process
When an end user purchases licenses for a system, a two week approval period starts during which the licenses are fully functional.
If you accept the purchase during this period, the licenses will go to the normal status and continue to function normally. You will be invoiced for the licenses.
35
8 How to manage end-user companies
8.4
If you do not accept the purchase within two weeks, the licenses become inactive and will no longer work.
Accepting the purchase after two weeks activates the licenses again.
If you reject the purchase, the licenses will be detached from the system.
How to manage the purchases of your end-users
NOTE: Only Back Office user level users can access the Customer Care view.
1.
Go to the Customer Care view.
The purchases are under the Waiting and Done headings.
2.
In the Waiting list, select the green arrow to open the purchase details.
3.
If you accept the purchase, fill in your own reference number.
O1878GB7 36
8.5
8 How to manage end-user companies
4.
Select Complete .
The purchase moves to the Done list.
5.
If you do not accept the purchase, write the reason for the rejection.
6.
Select Reject to reject the purchase.
The license is detached from the system.
NOTE: You cannot buy licenses on behalf of the end user. You can buy licenses only for your own company.
How to view the status of end-user licenses
NOTE: Only Account Manager level users can view the licenses.
A status icon shows the status of the subscription.
Table 4: Status icons
Symbol Meaning
The purchase has been approved, the license is active.
The purchase is waiting for approval. The license is active, but it will be deactivated if the purchase is not approved by the given date, or if it is rejected.
The purchase was not approved by the given date. The license is deactive until the purchase is approved.
End-user subscriptions are visible in the Licensing view as Default subscription for the end-user company.
O1878GB7 37
8 How to manage end-user companies
1.
In the Licensing view, select the subscription of the end-user company.
The subscription information and the list of licenses opens.
O1878GB7
If the license waits for approval, the deadline shows on the right.
If the license is approved by the Front Office, a green Disable auto-renew button shows on the right.
2.
If you want to disable the auto-renew function, select Disable auto-renew .
38
9
9.1
9 How to view your fire detection systems
How to view your fire detection systems
Introduction
In the Systems view, you can see all your fire detection systems and their status. You can use the search tool or the tabs ( all, online, and offline ) to filter your fire detection panels:
Figure 5: Access to fire detection systems
If a fire detection system is offline, you see a grey crossed circle indicating offline status, and information on when the system was last updated:
Figure 6: An offline fire detection system
NOTE: If your fire detection system is offline, make sure that you followed the installation instructions in Chapter
6 How to add a fire detection system
correctly.
If you use group names for your systems, the systems that have a group name are listed first.
O1878GB7
You can view your fire detection system also with a mobile device.
39
9 How to view your fire detection systems
9.2
Figure 7: Systems view on a mobile device
How to view the system status
In the Systems view, select the fire detection system you want to view:
Figure 8: Select system
The System monitor view of that fire detection system opens:
O1878GB7 40
O1878GB7
9 How to view your fire detection systems
Figure 9: Detailed view of a fire detection panel (System monitor view)
In the System monitor view, EcoStruxure Fire Expert shows the system status, and the number of active alarms, faults, disablements, and test alarms in the fire detection panels.
You can group the results by Loop or Zone. You can filter the results by panels, faults or disablements.
If there is an active session, the user and access levels show on the display:
Figure 10: Active panel session
You can view the status of your fire detection system also with a mobile device.
41
9 How to view your fire detection systems
9.3
Figure 11: System monitor view on a mobile device
How to view possible faults and disablements
You can view the active faults and disablements in the System monitor view. The icons in the panels show the number of active faults and disablements.
O1878GB7
Figure 12: Active disablements icon
42
9.3.1
9 How to view your fire detection systems
If your fire detection system does not have any active faults or disablements, no fire detection panels are listed.
All connected fire detection panels send updates to EcoStruxure Fire Expert once every 60 seconds. EcoStruxure Fire Expert automatically refreshes the data on the screen.
•
How to group and filter the active faults and disablements
Group the findings by addressable detection loop ( Loop ) or detection zone ( Zone ).
• To filter the results, select which fire detection panel(s) you want to see.
You can filter the faults and disablements by type. The selected filters are listed in the view.
O1878GB7
Figure 13: Filter by disablement, disabled from menu filter option selected
If there is no data to be shown with the selected filter(s), no fire detection panels are listed.
43
9 How to view your fire detection systems
9.3.2
Figure 14: Filter by faults, no active faults in the system
How to add a comment for a fault or a disablement
1.
Go to the fire detection panel that you want to see.
2.
Select Comments in the fault/disablement you want to add a comment to.
3.
Write your comment in the comment field.
4.
Select Add comment .
9.4
O1878GB7
How to view the event history
Information on old events is in the Event Wall view.
44
9 How to view your fire detection systems
Select the Event Wall tab. A list of the past events in that fire detection system opens:
9.4.1
Figure 15: Event Wall
How to download an event report
1.
In the Event wall view, select the calendar icon.
2.
Select the start date from the calendar.
3.
Select the end date from the calendar.
O1878GB7
Select the start date again to de-select the selection. Select the end date again to select another end date.
45
9 How to view your fire detection systems
4.
Select the start and end time (in 1 h steps) with the sliders.
5.
Select Test alarms or All events .
6.
Select Export CSV to create the report.
The report is created in Microsoft Excel.
9.4.2
Figure 16: Event report example
7.
Save the report, if necessary.
How to add comments in the Event wall view
1.
Select the Event wall tab.
2.
To add a new site comment, write your comment in the comment field.
O1878GB7 46
O1878GB7
9 How to view your fire detection systems
3.
Select Add comment .
4.
Your comment appears as a new event.
5.
To add a comment to an event, select Comments in the event you want to add a comment to.
6.
Write your comment in the comment field.
7.
Select Add comment .
8.
Your comment appears as a comment.
47
10 How to use system monitor functions
10
10.1
How to use system monitor functions
Introduction to system monitor functions
NOTE: Only Firesystem User level users can access the system monitor functions.
To access the system monitor functions, go to the Systems view and select the fire detection system you want to view:
10.2
Figure 17: Select system
The System monitor view of that fire detection system opens.
How to disable addresses and zones
NOTE: To do this action, you must have a relevant license.
There are two options to disable an address:
•
•
You can disable the address until you enable it again.
You can use a timer to disable the address for a certain time period.
When disabled, no alarms will be generated from that address.
1.
Go to the System monitor view of the system where the address is.
2.
Go to the address you want to disable.
O1878GB7 48
3.
To disable an address, select Disable address .
10 How to use system monitor functions
4.
To enable the address, select Enable address .
5.
Optionally, select + Add timer to disable the address for a maximum of 12 hours.
O1878GB7
6.
Use the + and – buttons to set the timer in steps of 30 minutes.
7.
Select Clear timer to cancel the action.
8.
Select Disable with timer to start the timer.
The timer starts immediately.
9.
To stop the timer before the set time, select Enable address .
49
10 How to use system monitor functions
10. To disable a zone, go to the zone view.
11.
Select Disable zone for the zone that you want to disable.
12. To enable the zone, select Enable zone .
10.3
10.3.1
O1878GB7
How to do address-based modifications
NOTE: You must have configuration rights to do these actions.
Commissioning and testing package license required (FFS00704004).
How to change the zone of an address
NOTE: To do this action, you must have a relevant license.
NOTE: The configuration in EcoStruxure Fire Expert and in the fire detection panel must be the same.
50
O1878GB7
10 How to use system monitor functions
You can change the zone of an address without opening the configuration. The configuration is updated and the new version is sent to the fire detection panel on the fly.
1.
In the Systems view, select the fire detection system that you want to update.
2.
Select the address that you want to update.
3.
Select Edit address .
51
10 How to use system monitor functions
4.
Change the zone number.
NOTE: The zone that you select must exist. To create a new zone, you must edit the whole configuration. For instructions, refer to the EcoStruxure Fire Expert
Configuration manual.
5.
Select Save to save the changes.
10.3.2
How to change the customer text
NOTE: To do this action, you must have a relevant license.
NOTE: The configuration in EcoStruxure Fire Expert and in the fire detection panel must be the same.
You can change the customer text of an address without opening the configuration. The configuration is updated and the new version is sent to the fire detection panel on the fly.
1.
In the Systems view, select the fire detection system that you want to update.
O1878GB7 52
2.
Select the address that you want to update.
10 How to use system monitor functions
O1878GB7
3.
Select Edit address .
4.
Change the customer text.
5.
Select Save to save the changes.
53
10 How to use system monitor functions
10.4
How to activate the zone test mode
1.
Go to the System Monitor view.
2.
Group the results by Zone .
3.
Select the detection zone that you want to set to the test mode.
4.
Select Activate test mode .
5.
The detection zone is now in the test mode.
6.
To deactivate the test mode, select the zone and then select Deactivate test mode .
10.5
How to create test alarms
1.
When the zone is in the test mode, select the detector you want to test.
NOTE: You can create test alarms for detectors only.
O1878GB7 54
O1878GB7
2.
Select Activate alarm .
10 How to use system monitor functions
3.
Wait until the test alarm is generated.
NOTE: Do not deactivate the test mode while the test alarm is generated.
4.
Repeat steps 1-3 to all the detectors that you want to test.
5.
Test Alarms are shown in the System Monitor view.
6.
To see the details, select the zone (or loop, depending on the grouping of results) and address where the active alarm is.
55
10 How to use system monitor functions
7.
Select Reset alarms to deactivate the test alarms.
Wait until the system resets the test alarms.
8.
When you have finished the test, go to the System Monitor view and select
Deactivate test mode .
10.6
How to activate an alarm
NOTE: To do this action, you must have a relevant license, an active session, and be logged in as a Normal or Premium user, access level 3 or 4.
NOTE: You can activate alarms only for detectors.
This action will set an actual fire alarm. For instructions on how to set a test alarm, refer to
Section
10.5 How to create test alarms .
1.
Go to the System monitor view of the system where the address is.
2.
Open the address.
O1878GB7 56
3.
Select Activate alarm .
10 How to use system monitor functions
O1878GB7
4.
Confirm in the pop-up that you want to activate an alarm.
A fire alarm is activated in the detector.
The system shows an active fire alarm.
5.
Select Silence alarms to silence all alarms in the system.
57
10 How to use system monitor functions
6.
Select Re-sound alarms to re-sound the silenced alarms.
7.
Select Reset alarms to reset all alarms in the system.
10.7
How to activate the LED in an address
NOTE: The commissioning and testing package license is required for this action.
1.
Go to the System monitor view.
2.
Go to the address you want to test.
3.
Select Activate led .
The LED in the selected address is lit.
4.
Select Deactivate led to end the test.
This action can also be done with a mobile device.
O1878GB7 58
10.8
10 How to use system monitor functions
How to activate an output test
NOTE: To do this action, you must have a relevant license, an active session, and be logged in as a Normal or Premium user, access level 3 or 4.
NOTE: The address must have a configured output function.
1.
Go to the System monitor view of the system where the address is.
2.
Open the address.
3.
To test the outputs, select Activate output test .
If the device in the selected address has an output LED, the LED is lit.
4.
Select Deactivate output test to end the test.
10.9
How to manage system controls
In the Systems view, select Controls from the tabs at the top.
O1878GB7 59
10 How to use system monitor functions
10.9.1
Figure 18: Controls view
In the Controls view, you can:
•
• disable the controls of devices in a system activate a test for the devices in a system
How to disable controls
NOTE: To do this action, you must have a relevant license and an active session, and be logged in as a Normal or Premium user, access level 3 or 4.
NOTE: This action affects all the selected devices in the panel, not a single address.
1.
Go to the Controls view of your system.
2.
Open the panel view.
3.
Go to the devices for which you want to disable the controls.
O1878GB7 60
10 How to use system monitor functions
4.
Select Disable control .
The number of disablements shows for the panel.
5.
To enable the control of the selected devices, select Enable control .
10.9.2
NOTE: Also Default users can select the Enable control function.
How to activate a system test
NOTE: To do this action, you must have a relevant license and an active session, and be logged in as a Normal or Premium user, access level 3 or 4.
NOTE: This action affects all the selected devices in the panel, not a single address.
1.
Go to the Controls view of your system.
2.
Go to the devices for which you want to activate the test.
O1878GB7 61
10 How to use system monitor functions
3.
Select Activate test .
The number of active tests shows for the panel.
4.
Select Deactivate test to end the test.
10.10
NOTE: Also Default users can select the Deactivate test function.
How to check the status of disabled addresses
NOTE: To do this action, you must have a relevant license and be logged in as a Normal or
Premium user, access level 3 or 4.
1.
Go to the System monitor view of the system where the address is.
2.
Go to the address that you want to check.
3.
Disable the address.
O1878GB7 62
O1878GB7
4.
Select Check alarm status .
The system checks the status of the address:
10 How to use system monitor functions
5.
Enable the address after the check.
63
11 How to use the fire orientation map feature
11
11.1
How to use the fire orientation map feature
Introduction to the fire orientation map feature
NOTE: You need the Fire orientation map license (FFS00704006) to use the fire orientation map feature.
With the orientation map, you can see the layout of the site as a map. The map shows the addresses as icons. Possible faults and disablements show on the map as icons with different colors.
To access the orientation map, go to the Systems view and select the fire detection system you want to view:
Figure 19: Select system
Select Map to open the Map view.
O1878GB7
Figure 20: Map view
64
11 How to use the fire orientation map feature
NOTE: You must have a license to use the fire orientation map feature. If you do not have a license, the Map tab is not active.
11.2
How to add an orientation map
1.
Go to the Map view.
2.
Select the + icon
3.
Give a name for the site plan.
O1878GB7 65
11 How to use the fire orientation map feature
4.
Click anywhere outside the name field to save the name.
The site plan is added.
11.3
5.
Add sub-site plans to the site plan, as necessary.
NOTE: You can only add and delete site plans and sub-site plans, you cannot change the site map structure later. Therefore, make sure that you add the structure correctly.
How to add sub-site plans
1.
Go to the Map view.
2.
Move the cursor over the site plan for which you want to add a sub-site plan.
The Settings icon appears.
3.
Select the Settings icon.
O1878GB7 66
O1878GB7
11 How to use the fire orientation map feature
4.
Select Add site plan .
5.
Give a name for the sub-site plan.
6.
Click anywhere outside the name field to save the name.
The sub-site plan is added.
NOTE: The site map structure cannot be changed later so make sure that you add the structure correctly. You can only add and delete site plans and sub-site plans.
67
11 How to use the fire orientation map feature
11.4
How to edit the orientation map
1.
To edit the site plan or sub-site plan, move the cursor over the name of the site plan or sub-site plan.
The Settings icon appears.
2.
Select the Settings icon.
3.
Select Edit name to change the name of the site plan or sub-site plan.
4.
Select Upload image to add a picture to the site plan or sub-site plan.
The maximum allowed size for the picture is 5 MB. The preferred format for the picture is SVG, but also JPEG and PNG graphics are allowed.
5.
Select Add site plan to add a sub-site plan to the site plan or sub-site plan.
O1878GB7 68
11 How to use the fire orientation map feature
6.
To edit the content of the orientation map, select the site plan or sub-site plan from the left.
The orientation map opens. If you already added a picture, it shows in the middle.
Use the mouse to scroll the image larger or smaller, if necessary. The available addresses are listed on the right.
O1878GB7 69
11 How to use the fire orientation map feature
7.
Select the Edit map button.
The map opens in edit mode.
O1878GB7
NOTE: When you select the Edit map button, all of the existing site plans and subsite plans go into the edit mode. The user interface asks you to save the current edited floor plan before you can start to edit the next one.
70
O1878GB7
11 How to use the fire orientation map feature
8.
To add addresses to the map, select the + icon next to the address you want to add.
The address is added to the top-left corner of the map.
9.
Drag and drop the address to the correct place in the map.
10. Drag and drop all the necessary addresses to the map.
71
11 How to use the fire orientation map feature
11.
To delete an address from the map, select the – icon next to the address you want to delete.
12. When you are ready, select Done .
O1878GB7 72
11 How to use the fire orientation map feature
13. Edit the sub-site plans similarly.
NOTE: The addresses that are already in use in other site plans are marked with a lock icon:
11.5
NOTE: The structure of the site plan cannot be edited.
How to view the orientation map
1.
Go to the Map view.
2.
Select the site plan you want to view.
O1878GB7
Use the mouse to scroll the image larger or smaller, or to move the picture in the view, if necessary.
73
11 How to use the fire orientation map feature
3.
The map shows the addresses as icons. Possible faults and disablements show on the map as icons with different colors. For example, the disablements show as blue icons.
4.
For details on possible faults and disablements, select the address on the map.
5.
You can enable or disable addresses from the map.
O1878GB7 74
11 How to use the fire orientation map feature
6.
Select Zones to view the descriptions of the zones.
O1878GB7 75
11 How to use the fire orientation map feature
7.
Select the settings icon to see the active configuration.
The settings view opens.
O1878GB7 76
11 How to use the fire orientation map feature
8.
Select the arrow to view the list of available configurations.
O1878GB7
9.
To change the configuration, select the configuration and select Save .
77
11 How to use the fire orientation map feature
11.6
How to delete an orientation map
1.
Go to the Map view.
2.
Move the cursor over the site plan or sub-site plan that you want to delete.
3.
Select the Settings icon.
4.
Select Delete .
NOTE: The selected orientation map and all the components in it, including the subsite plans, are deleted immediately. The system does not ask for confirmation.
O1878GB7 78
12
12.1
12 How to view the contamination of the detectors in your fire detection system
How to view the contamination of the detectors in your fire detection system
Introduction to the contamination feature
NOTE: You need a license to use the contamination feature.
Dirt collects in the detectors over time. In a dirty (dusty) environment, dirt collects faster than in a cleaner environment. With the contamination feature, you can see the contamination percentage of the detectors in one view. When the contamination percentage rises, change the dirty detectors.
To access the contamination feature, go to the Systems view and select the fire detection system you want to view.
Figure 21: Select system
Select Contamination to open the Contamination view.
O1878GB7
Figure 22: Contamination view
79
12 How to view the contamination of the detectors in your fire detection system
NOTE: You must have a license to use the contamination feature. If you do not have a license, the Contamination tab is not active.
12.2
How to view the contamination status
1.
Go to the Contamination view.
2.
Select the panels to be included.
3.
Select the loops to be included.
4.
Select the zones to be included.
O1878GB7 80
12 How to view the contamination of the detectors in your fire detection system
5.
Use the slider to change the contamination percentage to be used in the status report.
The view changes according to the selections. The single addresses show at the bottom of the columns.
NOTE: If there are too many addresses included in the selection, the data becomes difficult to read. In that case, use more filters to reduce the data.
The data is available in different charts, export the report in CSV format to Microsoft
Excel.
NOTE: If there is no data that meets the criteria, the view is empty.
6.
Select Export CSV to export the report to Microsoft Excel.
7.
Select the arrow next to the address at the bottom of the Contamination view to access the contamination graph of a single address.
The data for the selected address opens.
O1878GB7
8.
You can select Month or Year to filter the results.
81
12 How to view the contamination of the detectors in your fire detection system
9.
Select Reset data to clear the contamination data of an address.
O1878GB7 82
13
13.1
13 How to make administrative changes to your fire detection system
How to make administrative changes to your fire detection system
To make administrative changes
NOTE: Only Firesystem user level users have full access to these functions.
You can make various administrative changes to your fire detection system:
•
•
•
Edit the details or location information of your fire detection system
Share access with or transfer ownership to someone outside your organization
View the latest administrative events of your system
1.
Go to the Systems view.
2.
Find the fire detection system you want to manage and select Manage .
The Manage system view opens. Now you can view or edit the administrative details of your fire detection system.
O1878GB7
For instructions on how to configure the FDP system, refer to the EcoStruxure Fire Expert
Configuration manual .
83
13 How to make administrative changes to your fire detection system
13.2
How to share access with or transfer ownership to someone outside your organization
NOTE: You can only share access with or transfer ownership to a firesystem level user of another Fire Expert account.
If you share access to your fire detection system with another organization, you still have full control and ownership of your fire detection system
Figure 23: Shared EcoStruxure Fire Expert access
If you transfer the ownership of your fire detection system to another organization, you no longer have access to it, unless the new owner shares access with you.
13.2.1
Figure 24: Transferred EcoStruxure Fire Expert ownership
How to share access to your fire detection system
1.
Go to the Manage system view.
2.
Select Share system access .
3.
Complete the field for the e-mail address of the target organization’s admin user.
4.
Select Share rights .
When you share access with someone outside your organization, they receive an email notification. The change comes into effect after they log on to EcoStruxure Fire Expert and accept the shared access. You can remove the shared access anytime in the Manage system view.
O1878GB7 84
13 How to make administrative changes to your fire detection system
13.2.2
Figure 25: Users section in the Manage system view (access shared to a maintenance company)
How to transfer the ownership of your fire detection system
1.
Go to the Manage system view.
2.
Select Transfer system ownership .
3.
Complete the field for the email address of the target organization’s admin user.
4.
Select Change ownership .
When you transfer ownership to someone outside your organization, they receive an email notification. The change comes into effect after they log on to EcoStruxure Fire Expert and accept the ownership transfer. You can cancel the ownership transfer change only if the new owner has not yet accepted the ownership transfer.
O1878GB7 85
Schneider Electric www.se.com/buildings
© 2022 Schneider Electric. All rights reserved.