Schneider Electric AL-161-4 Three-Way Air Switching Valve is a device used for central supply air changeover in dual pressures systems. It is designed to provide reliable and efficient control of airflow in HVAC systems. The AL-161-4 features a durable die-cast aluminum actuator with a replaceable neoprene diaphragm, ensuring long-lasting performance. With a flow capacity of 25,920 scim at 15 psig supply with 1 psig drop, it can handle a wide range of airflow requirements. The valve body is rated for 250 psig, making it suitable for various applications. The AL-161-4 is easy to install and maintain, with clear instructions and a compact design. Its versatility and reliability make it an ideal choice for controlling airflow in commercial and industrial HVAC systems.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Schneider Electric AL-161-4 Three-Way Air Switching Valve User Guide | Manualzz

Application

The AL-161-4 is a three-way air switching valve used for central supply air changeover in dual pressures systems.

Features

• Die cast aluminum actuator with replaceable neoprene diaphragm

Applicable Literature

• Cross-Reference Guide, F-23638

• Reference Manual, F-21683

• Application Manual, F-21335

• Valve Products Catalog, F-27384

• EN-123 Air Quality Requirements for Pneumatic

HVAC Control Systems, F-22516

AL-161-4

Three-way Air Switching Valve

General Instructions

Printed in U.S.A. 11/09

©

Copyright 2009 Schneider Electric All Rights Reserved.

F-21286-5

SPECIFICATIONS

Valve Body Rating: 250 psig (1724 kPa).

Actuator Maximum Air Pressure: 30 psig (207 kPa).

Spring Range 8-13 psig (55-90 kPa).

Flow Capacity: 25,920 scim (7,080 ml/s) at 15 psig (103 kPa) supply with 1 psig (6.9 kPa) drop.

Connections:

Actuator, 1/8" FNPT.

Valve Body, 1/2" FNPT.

Port Code and Flow Pattern:

See Table-1.

Ambient Temperature Limits:

Shipping & Storage, -40 to 220 ° F (-40 to 104° C).

Operating, 35 to 140° F (2 to 60° C).

Humidity: 5 to 95% RH, non-condensing.

Location: NEMA Type 1.

Table-1 Flow Pattern.

Stem Up

(No Air to Actuator)

Flow

B to AB*

* AB Common.

Closed Port

A

Stem Down

20 psig (138 kPa) Air to Actuator

Flow

A to AB*

Closed Port

B

2

©

Copyright 2009 Schneider Electric All Rights Reserved.

F-21286-5

TYPICAL APPLICATIONS

L1

L2

Electric Time

Switch

1

AL-1XX

Solenoid Air Valve

(E/P Relay)

M N.C.

N.O.

C

AL-161-4

15 psi

(103 kPa)

1 Contacts Open: 20 psig to Thermostats

Contacts Closed: 15 psig to Thermostats

A AB

B

20 psi

(138 kPa)

Pressure

Gauge

0-30 psig

Supply Main to

Thermostats

Figure-1 Typical Piping Diagram.

INSTALLATION

Inspection

Requirements

Warning

Inspect the package for damage. If damaged, notify the appropriate carrier immediately.

If undamaged, open the package and inspect the device for obvious damage. Return damaged products.

Job piping diagrams

Tools (not provided):

– Appropriate drill and drill bit for mounting screws

– Appropriate screw drivers and wrenches

Mounting screws (not provided)

Training: Installer must be a qualified, experienced technician

Disconnect the power supply (line power) before installation to prevent equipment damage.

Make all connections in accordance with the piping diagram.

Caution

Do not exceed the ratings of the device(s).

Avoid locations where excessive moisture, corrosive fumes, or vibration is present.

Do not install insulation on any part of the actuator.

F-21286-5

©

Copyright 2009 Schneider Electric All Rights Reserved.

3

Mounting

The AL-161-4 is not position sensitive.

1. Mount the AL-161-4 to the wall or the subpanel of a control cabinet at any angle, using the attached mounting bracket.

2. Use three (3) 1/4" (6 mm) mounting screws (not provided) to secure the AL-161-4 to the mounting surface.

3. See Figure-2 for mounting dimensions.

Piping

Refer to the typical piping application in Figure-1.

CHECKOUT

With no air to the actuator the flow will be from ports B to AB. Apply 20 psig (38 kPa) to the actuator; the flow will be from ports A to AB.

MAINTENANCE

Regular maintenance of the total system is recommended for sustained optimum performance. For information on air quality requirements consult EN-123, Air Quality

Requirements for Pneumatic HVAC Control Systems, F-22516 .

FIELD REPAIR

Use part number PNV-102-1 when the replacement of the actuator diaphragm is necessary.

DIMENSIONAL DATA

See Figure-2 for dimensional data.

4-5/8

(117)

1

1-1/4

(32)

2-13/16

(71)

1-11/16

(43)

2-1/4

(57)

3-1/2

(89)

4-13/16

(122)

2-1/2

(64)

1-1/8

(29)

Mounting

Slots

9/32 (7) dia.

7/8 (22)

3-5/8

(92)

1-5/8

(41)

6-1/16

(154)

Mounting Slot

9/32 (7) dia.

1-1/4

(32)

3

(76)

1-15/32

(37)

1 Allow 3" (76 mm) clearance above assembly for actuator removal.

Dimensions in inches. ( ) mm.

Figure-2 AL-161-4 Air Switching Valve Dimensions.

On October 1st, 2009, TAC became the Buildings business of its parent company Schneider Electric. This document reflects the visual identity of Schneider

Electric, however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes.

Copyright 2009, Schneider Electric

All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.

Schneider Electric

1354 Clifford Avenue

P.O. Box 2940

Loves Park, IL 61132-2940 www.schneider-electric.com/buildings

F-21286-5

advertisement

Key Features

  • Die cast aluminum actuator with replaceable neoprene diaphragm
  • Flow capacity of 25,920 scim at 15 psig supply with 1 psig drop
  • Valve body rating of 250 psig
  • Easy to install and maintain
  • Applicable for various HVAC systems

Frequently Answers and Questions

What is the maximum air pressure that can be applied to the actuator?
The maximum air pressure that can be applied to the actuator is 30 psig (207 kPa).
What is the spring range of the valve?
The spring range of the valve is 8-13 psig (55-90 kPa).
What is the ambient temperature range in which the valve can operate?
The ambient temperature range in which the valve can operate is 35 to 140° F (2 to 60° C).
What is the location rating of the valve?
The location rating of the valve is NEMA Type 1.
What is the recommended maintenance procedure for the valve?
Regular maintenance of the total system is recommended for sustained optimum performance. For information on air quality requirements consult EN-123, Air Quality Requirements for Pneumatic HVAC Control Systems, F-22516.