35015036 07/2010
Magelis Smart 15"
User Manual
07/2010 www.schneider-electric.com
2
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of
Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2010 Schneider Electric. All rights reserved.
35015036 07/2010
Table of Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Part I General Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1 Important Information . . . . . . . . . . . . . . . . . . . . . . . . . . .
Federal Communications Commission Radio Frequency Interference
Statement - For U.S.A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Qualified Personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Information for the UK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Certifications and Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
European (CE) Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hazardous Location Installations - For USA and Canada. . . . . . . . . . . . .
Chapter 2 Physical Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Package Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Smart 15" Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Interface Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 3 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Characteristics of the Smart 15" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flash Disk Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Environmental Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 4 Dimensions/Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Panel Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preparing to Install the 15" Smart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Part II Implementation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 5 Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
First Power-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 6 Main Power Connection . . . . . . . . . . . . . . . . . . . . . . . . . .
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the Power Switch Cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the DC Power Cord . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the AC Power Cord . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Drawing of the USB outlet on the Magelis iPC . . . . . . . . . . . . . . .
35015036 07/2010
63
67
49
43
29
15
5
7
3
4
Chapter 7 Configuration of the BIOS . . . . . . . . . . . . . . . . . . . . . . . . .
Accessing the BIOS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 8 Hardware Modifications . . . . . . . . . . . . . . . . . . . . . . . . . .
Before Modifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing the Smart Unit’s Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Smart 15" Internal View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
USB Front Face . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PCMCIA Card Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compact Flash (CF) Card Installation and Removal . . . . . . . . . . . . . . . .
USB Cable Clamp Attachment/Removal . . . . . . . . . . . . . . . . . . . . . . . . .
Part III Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 9 Connections to PLCs. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
105
81
85
Connection to PLCs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 10 System Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Monitor Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Monitor Property . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Monitor Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 11 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reinstallation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Regular Cleaning and Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
109
129
Chapter 12 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
139
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Part IV Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 13 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessories for the Smart 15" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
145
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
35015036 07/2010
Safety Information
§
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
35015036 07/2010
5
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved.
6
35015036 07/2010
About the Book
At a Glance
Document Scope
This manual describes the configuration and usage of the Smart 15" from the
Magelis industrial PC range.
This computer is designed to operate in an industrial environment and features the very latest technologies.
The Magelis Smart 15’’ computer is a standalone product.
The product references are: z HMIPSC7DE03 - Smart 15” DC z z z z z z z
24 Vdc
15’’ XGA Touch screen
1 GHz processor
1024 MB RAM
2 GB Compact Flash card
Windows® XPe
Client application pre-installed z z z z z z z z
HMIPSC7AE03 - Smart 15” AC
100...240 Vac
15’’ XGA Touch screen
1 GHz processor
1024 MB RAM
2 GB Compact Flash card
Windows® XPe
Client application pre-installed z z z z z z
HMIGTW7353 - Graphic Terminal
24 Vdc
15’’ XGA Touch screen
1 GHz processor
1024 MB RAM
2 GB Compact Flash card
35015036 07/2010
7
8 z z
Windows® XPe
Client application and Run-Time Vijeo Designer pre-installed z z z z z z z
HMIPSF7DP03 - Smart+ 15” DC
24 Vdc
15’’ XGA Touch screen
1 GHz processor
1024 MB RAM
15 GB Flash disk
Windows® XPpro z z z z z z z
HMIPSF7AP*3 - Smart+ 15” AC
*The different letters indicate the different software bundles.
100...240 Vac
15’’ XGA Touch screen
1 GHz processor
1024 MB RAM
15 GB Flash disk
Windows® XPpro
The characteristics of the Smart 15” are detailed in Characteristics
Part Number Description
Your product may have a Part Number not included in the enclosed User Manual.
The commercial Part Number mentioned in the User Manual are those at the introduction of the product range. New part Numbers may be added during the life cycle of the product range. The new products are similar to products described in the User Manual but with changes, such as storage device size or type, memory size or bundled application software. The differences from the initial part numbers are indicated below:
Reference
HMI
1
PS
2
F
3
•
4
A
5
•
6
•
7
•
8
2
3
Reference
Number
1
Character Name
Part number radical
Product Type
Storage
Possible Value
HMI
NOTE: No change over product range
PS = Smart
NOTE: No change over product range
C = Compact Flash
F = Flash Disk
H = HDD
35015036 07/2010
Validity Note
35015036 07/2010
Reference
Number
4
Character Name Possible Value
5
6
7
8
Screen size
Power Supply
Operating System
Bundled Software
Hardware iteration
4 = 8.4”
6 = 12”
7 = 15”
9 = 19”
A = AC
D = DC
E = XP Embeded
P = XP Pro
7 = Seven
• = Other Operating System
0 = None
F = Vijeo Citect Run Time 500 I/O Full
L = Vijeo Citect Run Time 1200 I/O Lite
• = Other application software
0 = Initial
1 = First
2 = Second etc.
NOTE: All instructions applicable to the enclosed product and all safety precautions must be observed.
This documentation is valid for Magelis Smart 15’’.
The technical characteristics of the device(s) described in this manual also appear online. To access this information online:
Step
1
2
3
4
Action
Go to www.schneider-electric.com
In the Search box on the home page, type a model number. Do not type any blank spaces in the model number. To get information on a grouping similar modules, you can use the characters ** ; do not use dots or xx 's.
Under All , click Products → and select the model number that interests you.
To save or print a data sheet as a .pdf file, click Export to PDF .
The characteristics presented in this manual should be the same as those that appear online. In line with our policy of constant improvement we may revise content over time to improve clarity and accuracy. In the event that you see a difference between the manual and online information, use the online information as your reference.
9
Registered Trademarks
PL7, Vijeo Designer, Vijeo Citect and Unity are registered trademarks of Schneider
Electric.
Microsoft® and Windows® are registered trademarks of Microsoft Corporation.
Intel®, Celeron®, and Pentium® are registered trademarks of Intel Corporation.
IBM® is a registered trademark of International Business Machines Corporation.
Related Documents
Title of Documentation
Installation Guide for Magelis Industrial PC and Terminals
Vijeo Designer Tutorial
NEMA ICS 1.1
Magelis Industrial PC and Terminals - Readme
Reference Number
35012221
35007035
–
35012220
You can download these technical publications and other technical information from our website at www.schneider-electric.com.
Product Related Information
Some Smart 15" units are certified for use in Class I, Division 2 hazardous locations as defined in UL 1604, ANSI/ISA 12.12.01 or CSA C22.2 N ° 213. Observe the following:
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH z z z z z
Remove all power from the device before removing any covers or elements of the system, and prior to installing or removing any accessories, hardware, or cables.
Unplug the power cable from both the Smart unit and the power supply.
Always use a properly rated voltage sensing device to confirm power is off.
Replace and secure all covers or elements of the system before applying power to the unit.
Use only the specified voltage when operating the Smart 15". The AC unit is designed to use 100...240 Vac input. The DC unit is designed to use
23...25 Vdc. Always check whether your device is AC or DC powered before applying power.
Failure to follow these instructions will result in death or serious injury.
10
35015036 07/2010
35015036 07/2010
WARNING
LOSS OF CONTROL z z z z
The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop and overtravel stop.
Separate or redundant control paths must be provided for critical control functions.
System control paths may include communication links. Consideration must be given to the implications of unanticipated transmission delays or failures of the link.(1)
Each implementation of a Magelis Smart 15" must be individually and thoroughly tested for proper operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
(1) For additional information, refer to NEMA ICS 1.1
(latest edition) , "Safety
Guidelines for the Application, Installation, and Maintenance of Solid State Control" and to NEMA ICS 7.1 (latest edition),”Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive Systems” or their equipment governing your particular location.
NOTE: The Smart 15" is a highly configurable device and is not based on a real-time operating system. Changes to the software and settings of the following must be considered new implementations as discussed in the message above. Examples of such changes include: z z z z z
System BIOS
System Monitor
Operating system
Installed hardware
Installed software
WARNING
UNINTENDED EQUIPMENT OPERATION
Use only Schneider Electric software with the devices described in this manual.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
11
User Comments
We welcome your comments about this document. You can reach us by e-mail at [email protected].
12
35015036 07/2010
General Overview
35015036 07/2010
General Overview
I
Subject of this Part
This part provides an overview of the Magelis Smart 15" product.
What's in this Part?
This part contains the following chapters:
Chapter
1
2
3
4
Important Information
Physical Overview
Characteristics
Dimensions/Assembly
Chapter Name Page
35015036 07/2010
13
General Overview
14
35015036 07/2010
Important Information
35015036 07/2010
Important Information
1
General
This chapter describes the safety aspects which are specific to the operation of the
Smart 15".
What's in this Chapter?
This chapter contains the following topics:
Topic
Federal Communications Commission Radio Frequency Interference
Statement - For U.S.A.
Qualified Personnel
Safety Information for the UK
Certifications and Standards
European (CE) Compliance
Hazardous Location Installations - For USA and Canada
Page
15
35015036 07/2010
Important Information
Federal Communications Commission Radio Frequency Interference Statement
- For U.S.A.
FCC Radio Interference Information
This equipment has been tested and found to comply with the Federal
Communications Commission (FCC) limits for a Class A digital device, pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause or be subject to interference with radio communications. To minimize the possibility of electromagnetic interference in your application, observe the following two rules: z z
Install and operate the Smart 15’’ in such a manner that it does not radiate sufficient electromagnetic energy to cause interference in nearby devices.
Install and test the Smart 15’’ to ensure that the electromagnetic energy generated by nearby devices does not interfere with the Smart's operation.
WARNING
ELECTROMAGNETIC / RADIO INTERFERENCE
Electromagnetic radiation may disrupt the Smart's operations, leading to unintended equipment operation. If electromagnetic interference is detected: z z z z z
Increase the distance between the Smart 15’’ and the interfering equipment.
Reorient the Smart 15’’ and the interfering equipment.
Reroute power and communication lines to the Smart 15’’ and the interfering equipment.
Connect the Smart 15’’ and the interfering equipment to different power supplies.
Always use shielded cables when connecting the Smart 15’’ to a peripheral device or another computer.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
16
35015036 07/2010
Important Information
Qualified Personnel
General
You must only permit qualified personnel to install, operate, and maintain these products. A qualified person is one who has skills and knowledge related to the constructions and operation of this electrical equipment and the installations, and has received safety training to recognize and avoid the hazards involved. Refer to the most current release of NFPA 70E®, Standard for Electrical Safety in the
Workplace, for electrical safety training requirements. Examples of qualified personnel may include: z at the application design level, engineering department personnel who are z familiar with automation safety concepts (for example, a design engineer) at the equipment implementation level, personnel who are familiar with the installation, connection and commissioning of automation equipment (for example, an installation assembly or cabling engineer or a commissioning z z technician) at the operation level, personnel who are experienced in the use and control of automation and computing equipment (for example, an operator) as far as preventive or corrective maintenance is concerned, personnel trained and qualified in regulating or repairing automatic and computing devices (for example, an operating technician or an after-sales service technician, etc.)
35015036 07/2010
17
Important Information
Safety Information for the UK
Earthing and Wiring
WARNING
UNGROUNDED EQUIPMENT z z z
This apparatus must be earthed.
Use a three-pin plug with a standard three-pin power point.
Use only three-core extension cords.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
IMPROPER WIRING
Wire the equipment as described below: z z z z z z
Green and Yellow: Earth.
Blue: Neutral.
Brown: Live.
The Green and Yellow wire must be connected to the terminal in the plug marked by the letter E or by the safety earth symbols colored Green, or Green and Yellow.
The blue wire must be connected to the terminal which is marked by the letter
N or colored Black.
The brown wire must be connected to the terminal which is marked with the letter L or colored Red.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: The fact that the equipment operates satisfactorily does not imply that the power point is earthed. If you have any doubt about the effective earthing or wiring of the power point, consult a qualified electrician. Incorrectly wired power cords are a major cause of fatalities.
18
35015036 07/2010
Important Information
WARNING
INCOMPATIBLE POWER SYSTEM
Do not connect this equipment to an isolation transformer power system: z z
An isolation transformer system is a system having no reference between live parts and Earth; the exposed conductive parts of the device frame and enclosure are earthed.
An isolation transformer system is not permitted where the computer is directly connected to public supply systems in the UK.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
35015036 07/2010
19
Important Information
Certifications and Standards
Agency Certifications
Schneider Electric submitted this product for independent testing and qualification by third-party listing agencies. These agencies have certified this product as meeting the following standards.
z z z z z
Underwriters Laboratories Inc., UL 508 or CSA C22.2 N ° 142, Industrial Control
Equipment
Underwriters Laboratories Inc., UL 1604, ANSI/ISA 12.12.01 or CSA C22.2
N ° 213, Electrical Equipment for Use in Class I, Division 2 Hazardous (Classified)
Locations
These products were submitted for GOST certification. Please refer to marking on the products.
ATEX certification for DC products by INERIS is ongoing, please refer to product label.
DC products are designed to comply with Merchant Navy rules (refer to
Schneider Electric web site for installation guidelines).
For detailed information contact your local distributor and see the catalog and marking on the product.
Compliance Standards
Schneider Electric tested this product for compliance with the following compulsory standards.
United States: z z
Federal Communications Commission, FCC Part 15
Underwriters Laboratories Inc., UL 60950, Information Technology Equipment
Canada: z Canadian Standards Association, specification C22.2, No.142, Process Control
Equipment
Europe: CE z Directive 2006/95/EC (Low Voltage)
Directive 2004/108/EC (EMC) z z z z
Programmable Controllers: EN/IEC 61131-2 (Ed 3)
EMI: EN55011 (Group 1, Class A) / IEC/EN 61000-3-2, IEC/EN 61000-6-4
EMS: EN 61000-6-2
IEC/EN 60950, Information Technology Equipment
Australia: z Standard AS/NZS CISPR11 (C-Tick N998)
20
35015036 07/2010
Important Information
Qualification Standards
Schneider Electric voluntarily tested this product to additional standards. The additional tests performed, and the standards under which the tests were conducted, are specifically identified in Environmental Characteristics
.
Hazardous Substances
This product is compliant with: z z z
WEEE, Directive 2002/96/EC
RoHS, Directive 2002/95/EC
RoHS China, Standard SJ/T 11363-2006
35015036 07/2010
21
Important Information
European (CE) Compliance
CE Compliance Note
The products described in this manual comply with the European Directives concerning Electromagnetic Compatibility and Low Voltage (CE marking) when used as specified in the relevant documentation, in applications for which they are specifically intended, and in connection with approved third-party products.
22
35015036 07/2010
Important Information
Hazardous Location Installations - For USA and Canada
General
Schneider Automation designed the Smart 15’’ with the intention of meeting the requirements of Class I, Division 2 hazardous location applications. Division 2 locations are those locations where ignitable concentrations of flammable substances are normally confined, prevented by ventilation, or present in an adjacent Class I, Division 1 location, but where an abnormal situation might result in intermittent exposure to such ignitable concentrations.
While the Smart 15" is a non-incendiary device under UL 1604, ANSI/ISA 12.12.01 or CSA C22.2 N ° 213, it is not designed for, and should never be used within a
Division 1 (normally hazardous) location.
All HMIPSC7***3, HMIGTW7353 and HMIPSF7***3 devices with appropriate labeling are suitable for use in Class I, Division 2, Groups A, B, C, and D hazardous locations or in non-hazardous locations. Before installing or using your Smart 15", confirm that the UL 1604, ANSI/ISA 12.12.01 or CSA C22.2
N ° 213 certification appears on the product labeling.
NOTE: Some Smart 15" devices are not yet rated as suitable for use in hazardous locations. Always use your product in conformance with the product labeling and this manual.
DANGER
EXPLOSION HAZARD z z z z z
Do not use your Smart 15" device in hazardous environments or locations other than Class I, Division 2, Groups A, B, C, and D.
Always confirm that your Smart 15" device is suitable for use in hazardous locations by checking that the UL 1604, ANSI/ISA 12.12.01 or CSA C22.2
N
°
213 certification appears on the product labeling.
Do not install any Schneider Electric or OEM components, equipment, or accessories unless these have also been qualified as suitable for use in Class I,
Division 2, Groups A, B, C, and D locations.
In addition, confirm that any PCI controller cards have a temperature code (Tcode) of T4, and are suitable for an ambient temperature range of +0 ° C to
+50
°
C (32
°
F to 122
°
F).
Do not attempt to install, operate, modify, maintain, service, or otherwise alter the Smart 15" except as permitted in this manual. Unpermitted actions may impair the unit's suitability for Class I, Division 2 operation.
Failure to follow these instructions will result in death or serious injury.
35015036 07/2010
23
Important Information
24
DANGER
EXPLOSION HAZARD z z
Always confirm the UL 1604, ANSI/ISA 12.12.01 or CSA C22.2 N ° 213 hazardous location rating of your device before installing or using it in a hazardous location.
To apply or remove the supply power from a Smart 15" device installed in a
Class I, Division 2 hazardous location, you must either: z Use a switch located outside the hazardous environment, or; z Use a switch certified for Class I, Division 1 operation inside the hazardous area.
z z z z
Do not connect or disconnect any cables or wires while the circuit is live unless the area is known to be free of ignitable concentrations of vapors, gases, and other flammable or combustible materials. This applies to all connections including power, ground, serial, parallel, and network connections.
Never use unshielded / ungrounded cables in hazardous locations.
Use only non-incendiary USB devices
.
When enclosed, keep enclosure doors and openings closed at all times to avoid the accumulation of foreign matter inside the workstation.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH z z z z z
Remove all power from the device before removing any covers or elements of the system, and prior to installing or removing any accessories, hardware, or cables.
Always use a properly rated voltage sensing device to confirm power is off.
Unplug the power cable from both the Smart unit and the power supply.
Replace and secure all covers or elements of the system before applying power to the unit.
Use only the specified voltage when operating the Smart 15’’. The AC unit is designed to use 100...240 Vac input. The DC unit is designed to use 23...25
Vdc. Always check whether your device is AC or DC powered before applying power.
Failure to follow these instructions will result in death or serious injury.
Ensure that the product is properly rated for the location. If the intended location does not presently have a Class, Division and Group rating, then users should consult the appropriate authorities having jurisdiction in order to determine the correct rating for that hazardous location.
35015036 07/2010
Power Switch
Important Information
In accordance with Federal, State/Provincial, and Local regulations, all hazardous location installations should be inspected prior to use by the appropriate authority having jurisdiction. Only technically qualified personnel should install, service, and inspect these systems.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH z z z z z
Remove all power from the device before removing any covers or elements of the system, and prior to installing or removing any accessories, hardware, or cables.
Always use a properly rated voltage sensing device to confirm power is off.
Unplug the power cable from both the Smart unit and the power supply.
Replace and secure all covers or elements of the system before applying power to the unit.
Use only the specified voltage when operating the Smart 15’’. The AC unit is designed to use 100...240 Vac input. The DC unit is designed to use 23...25
Vdc. Always check whether your device is AC or DC powered before applying power.
Failure to follow these instructions will result in death or serious injury.
The amount of input power required by systems including a Smart 15’’ unit classifies a power switch as an incendiary device because the voltage and current across the make/break device are capable of creating a spark.
Hazardous location regulations require that a power switch rated for ordinary locations may be used if it is located in an area specified as non-hazardous.
However, limits in cable length between the workstation and the power switch may apply. Otherwise the switch must be compliant with Class I, Division 1 requirements
(intrinsically safe). These switches are built in a manner that prevents the possibility of a spark when contacts are made or broken.
Use suitable UL listed and/or CSA Certified Class I, Division 1 switches in hazardous locations. These switches are available from a wide number of sources. It is the responsibility of the customer to ensure that the power switch selected for the installation has the correct hazardous locations rating for the location in which it is installed.
35015036 07/2010
25
Important Information
Cable Connections
DANGER
EXPLOSION HAZARD z z
Always confirm the UL 1604, ANSI/ISA 12.12.01 or CSA C22.2 N
°
213 hazardous location rating of your device before installing or using it in a hazardous location.
To apply or remove the supply power from a Smart 15’’ device installed in a
Class I, Division 2 hazardous location, you must either: z Use a switch located outside the hazardous environment, or; z Use a switch certified for Class I, Division 1 operation inside the hazardous area.
z z z z
Do not connect or disconnect any cables or wires while the circuit is live unless the area is known to be free of ignitable concentrations of vapors, gases, and other flammable or combustible materials. This applies to all connections including power, ground, serial, parallel, and network connections.
Never use unshielded / ungrounded cables in hazardous locations.
Use only non-incendiary USB devices
.
When enclosed, keep enclosure doors and openings closed at all times to avoid the accumulation of foreign matter inside the workstation.
Failure to follow these instructions will result in death or serious injury.
Division 2 hazardous location regulations require that all cable connections be provided with adequate strain relief and positive interlock. Use only non-incendiary
USB devices as USB connections do not provide adequate strain relief to allow the use of incendiary peripherals
. Never connect or disconnect a cable while power is applied at either end of the cable. All communication cables should include a chassis ground shield. This shield should include both copper braid and aluminum foil. The D-sub style connector housing should be a metal conductive type
(e.g., molded zinc) and the ground shield braid should be well terminated directly to the connector housing. Do not use a shield drain wire.
The outer diameter of the cable must be suited to the inner diameter of the cable connector strain relief in order to ensure that a reliable degree of strain relief is maintained. Always secure the D-Sub connectors to the workstation-mating connectors via the two screws located on both sides.
26
35015036 07/2010
Important Information
Operation and Maintenance
The systems have been designed for compliance with relevant spark ignition tests.
However, please note that the workstation front panel keypad switches and PS/2 connector are the only make/break components intended to be exercised by the operator in the course of operations in a hazardous location.
DANGER
EXPLOSION HAZARD
In addition to the other instructions in this manual, observe the following rules when installing the Smart 15" unit in a hazardous location: z z
Wire the equipment in accordance with the National Electrical Code article
501.4 (B) for Class I, Division 2 hazardous locations.
Install your Smart 15’’ unit in an enclosure suitable for the specific application.
NEMA Type 4 (IP 65) enclosures are recommended even when not required by regulations.
Failure to follow these instructions will result in death or serious injury.
35015036 07/2010
27
Important Information
28
35015036 07/2010
Physical Overview
35015036 07/2010
Physical Overview
2
Subject of this Chapter
This chapter provides a physical overview of the product.
What's in this Chapter?
This chapter contains the following topics:
Topic
Package Contents
Smart 15" Unit Description
Interface Specification
Page
35015036 07/2010
29
Physical Overview
Package Contents
Items
The following items are included in the Magelis Smart 15’’ package. Before using the unit, please confirm that all items listed here are present.
HMIPSC7***3, HMIGTW7353 and
HMIPSF7***3
Installation Fasteners (8 per set)
CD-ROM containing the software required to reinstall the Operating System, the MS
Windows EULA and the Installation Guides and User Manuals for the HMIPSC7***3,
HMIGTW7353 and HMIPSF7***3.
Installation Gasket (Installed on the main unit)
USB Cable Clamp x 2
DC Connector
(For the Smart 15‘’ DC only, references HMIPSC7D**3, HMIGTW7353 and HMIPSF7D**3
30
35015036 07/2010
35015036 07/2010
Physical Overview
CF Card for HMIPSC7***3 and
HMIGTW7353
AC Power Cord with Terminal Block (US plug)
(For the Smart 15‘’ AC only, references HMIPSC7A**3 and
HMIPSF7A**3
AC Power Cord with Terminal Block (EU plug)
(For the Smart 15‘’ AC only, references HMIPSC7A**3 and
HMIPSF7A**3)
AC Power switch cover
(For the Smart 15‘’ AC only, references HMIPSC7A**3 and
HMIPSF7A**3)
This unit has been carefully packed, with special attention to quality. However, should you find anything damaged or missing, please contact your local distributor immediately.
31
Physical Overview
Smart 15" Unit Description
Front View
32
A Display
B Touch Panel
C Power LED/RAS Status Lamp
Green Lit: Normal z z z z z
Green Blinking: System is not running (Soft OFF state (see Note below))
Orange Lit: System Monitor Error/Touch Panel Error
Orange/Red Blinking: Backlight Error
Not Illuminated: Power is Off
D HDD/IDE Access Lamp z Green Lit: Access to HDD or IDE z Not Illuminated: No Access to HDD or IDE
E Front USB Cover
NOTE: Soft OFF: OS is shut down but the power line is still live. This is also called
"S5 state". One of the merits of this state is that you can also use the "Wake on LAN" feature.
35015036 07/2010
Rear View of the DC Units
F Unit’s Cover
G CF Card Interface Cover
H Power Connector
Physical Overview
35015036 07/2010
33
Physical Overview
Rear View of the AC Units
F Unit’s Cover
G CF Card Interface Cover
H Power Connector
34
35015036 07/2010
Sides View
I PCMCIA
J Ethernet LAN1 10/100Base-T (RJ45)
K Ethernet LAN2 10/100/1000Base-T (RJ45)
L PS/2 (Keyboard)
M Front USB Cover
Physical Overview
35015036 07/2010
35
Physical Overview
Bottom View the DC Units
N USB (4 ports) (See detail N)
O COM 1 and COM 2 (See detail O)
P Speaker Out
Q RAS (25 pins)
R CF Card Interface Cover
S Power Connector
36
35015036 07/2010
Bottom View the AC Units
N USB (4 ports) (See detail N)
O COM 1 and COM 2 (See detail O)
P Speaker Out
Q RAS (25 pins)
R CF Card Interface Cover
S Power Connector
Physical Overview
35015036 07/2010
37
Physical Overview
Interface Specification
Communication Connections
DANGER
EXPLOSION HAZARD z z
Always confirm the UL 1604, ANSI/ISA 12.12.01 or CSA C22.2 N ° 213 hazardous location rating of your device before installing or using it in a hazardous location.
z z
To apply or remove the supply power from a Smart 15’’ device installed in a
Class I, Division 2 hazardous location, you must either:
Use a switch located outside the hazardous environment, or;
Use a switch certified for Class I, Division 1 operation inside the hazardous area.
z z z z
Do not connect or disconnect any cables or wires while the circuit is live unless the area is known to be free of ignitable concentrations of vapors, gases, and other flammable or combustible materials. This applies to all connections including power, ground, serial, parallel, and network connections.
Never use unshielded / ungrounded cables in hazardous locations.
Use only non-incendiary USB devices
.
When enclosed, keep enclosure doors and openings closed at all times to avoid the accumulation of foreign matter inside the workstation.
Failure to follow these instructions will result in death or serious injury.
WARNING
EQUIPMENT DISCONNECTION OR UNINTENDED EQUIPMENT OPERATION z z z
Ensure that power, communication, and accessory connections do not place excessive stress on the ports. Consider the vibration environment when making this determination.
Securely attach power, communication, and external accessory cables to the panel or cabinet.
Use only commercially available USB cables.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
38
35015036 07/2010
Physical Overview
Serial Interfaces
COM 1 and COM 2 : These interfaces are used to connect an RS-232C (serial) cable. A D-SUB 9 pin plug connector is used.
Pin Arrangement
7
8
5
6
3
4
1
2
9
Shell
Pin No.
RS-232C
Signal
Name
CD
RXD
TXD
DTR
SG
DSR
RTS
CTS
RI
FG
Direction Meaning
Input
Input
Output
Output
–
Input
Output
Input
Input
–
Carrier Detect
Receive Data
Send Data
Data Terminal Ready
Signal Ground
Data Set Ready
Request to Send
Send Possible
Called status display (+ 5Vdc)
Frame Ground (Common with SG)
35015036 07/2010
39
Physical Overview
RAS Interface
The types of sockets for D-SUB 25 pins are listed in the table below:
Pin arrangement
20
21
22
23
16
17
18
19
24
25
13
14
15
9
10
11
12
6
7
4
5
Pin No.
Signal Name Meaning
1 GND Ground
2 +5Vdc
3 +12Vdc
Output current: 100 mA or less (with a total of 2 pin and 15 pin)
Output voltage: 5Vdc +/- 5%
Output current: 100 mA or less
Output voltage: 12Vdc +/- 5%
NC
RST(+)
DIN0(+)
DOUT2(-)
UPS
Shutdown(-)
-
Reset in(+)
Data in 0(+)
Data out 2(-) (UPS Shutdown(-))
8 Data out 2(+) (UPS Shutdown(+)) DOUT2(+)
UPS
Shutdown(+)
DOUT0(-)
DOUT0(+)
RST(-)
DIN0(-)
DIN1(+)
GND
+5 Vdc
Data out 0(-)
Data out 0(+)
Reset in(-)
Data in 0(-)
Data in 1(+)
Ground
Output current: 100 mA or less (with a total of 2 pin and 15 pin)
Output voltage: 5Vdc +/- 5%
DIN2(+)
DIN2(-)
DIN3(+)
DOUT1(-)
DOUT1(+)
DOUT3(-)
DOUT3(+)
DIN3(-)
DIN1(-)
NC
Data in 2(+)
Data in 2(-)
Data in 3(+)
Data out 1(-)
Data out 1(+)
Data out 3(-)
Data out 3(+)
Data in 3(-)
Data in 1(-)
-
40
35015036 07/2010
35015036 07/2010
INPUT VOLTAGE RANGE
INPUT CURRENT
INNER RESISTOR
INSULATION VOLTAGE
INSULATION
Output (DOUT 0,1, 2, 3)
Physical Overview
Recommended connector: XM2A-0901 Manufactured by Omron Co.
Recommended cover: XM2S-0913 Manufactured by Omron Co.
Jack Screw: XM2Z-0073 Manufactured by Omron Co.
Input (DIN 0, 1, 2, 3)
12...24 Vdc
Below 10 mA
3.6 K Ω
Below 500 Vac
Photocoupler
OUTPUT VOLTAGE RANGE
OUTPUT CURRENT
INSULATION VOLTAGE
INSULATION
24 Vdc
Below 120 mA
Below 500 Vac
Photocoupler
41
Physical Overview
42
35015036 07/2010
Characteristics
35015036 07/2010
Characteristics
Subject of this Chapter
This chapter lists the product characteristics.
What's in this Chapter?
This chapter contains the following topics:
Topic
Characteristics of the Smart 15"
Flash Disk Characteristics
Environmental Characteristics
3
Page
35015036 07/2010
43
Characteristics
Characteristics of the Smart 15"
Introduction
The characteristics of the Smart 15" models are given below:
Product Characteristics
Element
Processor
RAM
Flash Disk
Characteristics
ULV Celeron M 1 GHz, secondary memory cache 512 KB
1 GB RAM
Capacity greater or equal to 15 GB (Refer to Flash Disk
Characteristics
)
Video processor
Ethernet TCP/IP link
USB ports
Keyboard
RAS Interface
COM 1 and COM 2 serial ports
Integrated Intel 855 GME video, sharing main memory. 8/16/32 bit color resolution at 1024x768.
LAN1: 10/100Base-T
LAN2: 10/100/1000Base-T
4 x USB 2.0 (bottom side), 1 x USB 2.0 (front face)
PS/2 interface (mini Din 6 pin, female)
D-SUB 25 Pin x1 (male)
RS232C
Memory flash card slot Compact Flash type
PCMCIA slot 2 ports on side (Type II)
Audio port
Dimensions (WxHxD)
Weight
Speaker out (mini-jack interface)
395 x 294 x 60 mm (15.55 x 11.57 x 2.36 in.)
6.0 kg (13.23 lb)
NOTE: If a USB high speed device such as a webcam or a memory key isn't recognized by the Smart, or doesn't operate as expected, plug it into USB port #2 and leave USB port #1 empty.
Display Characteristics
Element
Graphics
Number of colors
Brightness
Brightness Control
Characteristics
XGA TFT active matrix (1024x768 pixels)
262144
250 cd/m2
4 levels of adjustment
44
35015036 07/2010
Characteristics
Power Supply
Element
Backlight
Characteristics
View angle Vertical 100
°
, horizontal 160
°
Typ.
Touch sensitive screen Analog resistive film, resolution 1024x1024
CFL - Life span > 50,000 h at 25 ° C (77 ° F)
For the Smart 15‘’ DC (References HMIPSC7D**3, HMIGTW7353 and
HMIPSF7D**3):
Element
Supply voltage
Consumption
Short dips
PCI extension slot capability
Characteristics
24 Vdc (19.2 Vdc to 28.8 Vdc)
90 W (max.)
5 ms (max.)
Board size 240 x 106.68 mm (9.45 x 4.2 in.) z z z z
5 Vdc, 1.5 A
12 Vdc, 0.5 A
12 Vdc, 0.1 A
3.3 Vdc, 0.5 A
For the Smart 15‘’ AC (References HMIPSC7A**3 and HMIPSF7A**3):
Element
Supply voltage
Consumption
Short dips
PCI extension slot capability
Characteristics
100...240 Vac (Range 85 ... 265 Vac)
70 VA (max.)
10 ms (20 ms max.)
Board size 240 x 106.68 mm (9.45 x 4.2 in.) z z z z
5 Vdc, 1.5 A
12 Vdc, 0.5 A
12 Vdc, 0.1 A
3.3 Vdc, 0.5 A
35015036 07/2010
45
Characteristics
Operating Systems
The products are delivered with a preinstalled operating system according to the reference ordered: Microsoft Windows® XPe.
Reference Characteristics
HMIPSC7DE03 Smart with 15" XGA Display, Touch screen, Celeron M 1 GHz, 2 GB
Compact Flash with Windows® XPe preinstalled, DC supply power.
(Client Edition)
HMIPSC7AE03 Smart with 15" XGA Display, Touch screen, Celeron M 1 GHz, 2 GB
Compact Flash with Windows® XPe preinstalled, AC supply power.
(Client Edition)
HMIGTW7353
HMIPSF7DP03
HMIPSF7AP*3
Smart with 15" XGA Display, Touch screen, Celeron M 1 GHz, 2 GB
Compact Flash with Windows® XPe and Vijeo Designer Run Time preinstalled, DC supply power. (Graphical Terminal)
Smart+ with 15" XGA Display, Touch screen, Celeron M 1 GHz, 15 GB
Flash disk with Windows® XPpro preinstalled, DC supply power.
Smart+ with 15" XGA Display, Touch screen, Celeron M 1 GHz, 15 GB
Flash disk with Windows® XPpro preinstalled, AC supply power
46
35015036 07/2010
Characteristics
Flash Disk Characteristics
Introduction
The Smart 15’’ products offer Flash Disk hard drives (also known as Solid-State
Drives or SSDs). Flash Disk hard drives are available only on HMIPSF7*** models.
All Flash Disk references are ATA-3 compliant and have no moving parts.
Characteristics
A Flash Disk (SSD) is a storage device based on semiconductors rather than rotating magnetic platters. The use of semiconductors allows a Flash Disk to perform normal storage functions while providing enhanced levels of performance and reliability. Flash Disk drives use the same industry-standard dimensions and data interfaces as conventional hard disk drives and may be used interchangeably in Smart 15’’ systems.
The references with Flash Disks share the same characteristics as other Smart 15’’ devices except as noted in the following table:
Characteristics
Capacity
MTBF
Data Reliability
Values
15 GB or higher
> 4,000,000 Hours at 25
°
C (77
°
F)
< 1 unrecoverable error in 10
14
bits read
Standards
—
—
—
Endurance
Shock resistance (in operation)
> 2,000,000 write/erase cycles
15 g over 11 ms, 3 shocks per axis
—
IEC 68-2-27 Ea test
EN/IEC 61131-2 compliant
Shock component value
Vibration resistance (in operation)
1000 g, half-sine, 0.5 ms duration, 50 g peak MIL-STD-810F, Method 516.5,
Procedure I
3.5 mm amplitude from 3 to 9 Hz
1 g amplitude from 9 to 150 Hz
EN/IEC 61131-2 compliant
Vibration component value 16.3 g RMS MIL-STD-810F, Method 514.5,
Procedure I, Category 24
35015036 07/2010
47
Characteristics
Environmental Characteristics
Characteristics
The environmental characteristics of the Smart 15" are as follows:
Characteristics
Additional Standards
Value Standards
Degree of Protection
Pollution Degree
Surrounding air temperature during operation
Storage temperature
IP 65/NEMA4x/12 for the front panel when installed.
IP 20 for the rest of the product.
For use in Pollution Degree 2 environment
0 ... 50 ° C (32 ... 122 ° F)
Operating altitude
Vibration
(in operation)
Shock Resistance
(in operation)
Surrounding air humidity during operation
Storage humidity
Immunity to interference
IEC 60529, NEMA 250, UL50, EN/IEC
61131-2
EN/IEC 61131-2
EN/IEC 61131-2, UL
– 20 ... 60 ° C (– 4 ... 140 ° F)
2000 m (6560 ft) max
3.5 mm amplitude from 5 to 9 Hz,
1 g amplitude from 9 to 150 Hz
15 g over 11 ms
IEC 60068-2-2 tests Bb and Ab,
IEC 60068-2-14 tests Na and EN/IEC
61131-2 compliant
EN/IEC 61131-2
EN/IEC 61231-2
IEC 60068-2-27 Ea test and EN/IEC 61131-
2 compliant
10 ... 85% RH (Wet bulb temperature:
29 ° C (84.2
° F) max. - no condensation)
10 ... 85% RH (Wet bulb temperature:
29 ° C (84.2
° F) max. - no condensation)
High frequency interference
–
EN 61231-2
EN/IEC 61131-2, IEC 61000-4-3/6 level 3
Electromagnetic waves
Information Technology Equipment
Information Control Equipment
Class A/EN 55022/55011
IEC 60950
UL 508, CSA 22.2 No142
48
35015036 07/2010
Dimensions/Assembly
35015036 07/2010
Dimensions/Assembly
4
Subject of this Chapter
This chapter concerns the dimensions and the panel mounting of products.
What's in this Chapter?
This chapter contains the following topics:
Topic
Dimensions
Panel Mounting
Preparing to Install the 15" Smart
Page
35015036 07/2010
49
Dimensions/Assembly
Dimensions
Dimensions of the Smart Unit
50
35015036 07/2010
Dimensions/Assembly
InstallationFastener Dimensions
The products are designed to be mounted in a cabinet with the attachments described below:
35015036 07/2010
51
Dimensions/Assembly
Dimensions with Installation Fasteners
52
35015036 07/2010
Dimensions/Assembly
Panel Mounting
Installation Location
WARNING
UNINTENDED EQUIPMENT OPERATION
Overheating can cause incorrect software behavior, therefore: z z z z z
Avoid placing the Smart unit next to other devices that might cause overheating.
Keep the Smart unit away from arc-generating devices such as magnetic switches and non-fused breakers.
Avoid using the Smart unit in environments where corrosive gases are present.
Install the Smart in a location providing a minimum clearance of 50 mm (2 in.) or more from all adjacent structures and equipment.
Install the Smart with sufficient clearance to provide for cable routing and cable connector dimensions.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Creating a Panel Cut-out for Cabinet Installation
For cabinet installation, it is necessary for the correct sized opening to be cut in the installation panel. The installation gasket and installation fasteners are required when installing the Smart.
35015036 07/2010
53
Dimensions/Assembly
Dimensions
The dimensions of the opening required to install the Smart unit are shown below:
NOTE: z z z z
Ensure the thickness of the installation panel is from 1.6 to 10 mm (0.06 to
0.39 in.)
All panel surfaces used should be strengthened. Due consideration should be given to the product’s weight, especially if high levels of vibration are expected and the product’s installation surface can move. Metal reinforcing strips can be attached to the inside of the panel near the panel cut-out, to increase the strength of the panel.
Ensure all installation tolerances are maintained.
The Smart 15" is designed for use in a NEMA Type 4X or 12 enclosure.
54
35015036 07/2010
Dimensions/Assembly
Preparing to Install the 15" Smart
Vibration and Shocks
Extra care should be taken with respect to the specification concerning vibration levels when installing or moving the Smart. If the Smart is moved, for example, while it is installed in a rack equipped with caster wheels, the unit can receive excessive shock and vibration.
CAUTION
EXCESSIVE VIBRATION z z z z
Plan your installation activities so that device shock and vibration tolerances are not exceeded.
Ensure that the panel opening and thickness are within the specified tolerances.
Before mounting the Smart unit into a cabinet or panel, ensure that the installation gasket is attached to the unit. The installation gasket provides additional protection from vibration.
The recommended torque for mounting the Smart 15" device is 0.5 N•m
(4.5 lb-in).
Failure to follow these instructions can result in injury or equipment damage.
Installation Gasket
Use of the installation gasket may help extend the operating life of your Smart The gasket is required to meet the protection ratings (IP65, IP20, NEMA4) of the unit and provides additional protection from vibration. Even if moisture protection is not required, install the gasket delivered with your Magelis product.
35015036 07/2010
CAUTION
LOSS OF SEAL z z z z z z
Inspect the installation gasket prior to installation or reinstallation, and periodically as required by your operating environment.
Replace the gasket if visible scratches, tears, dirt, or excessive wear are noted during inspection.
Do not stretch the gasket unnecessarily or allow the gasket to contact the corners or edges of the frame.
Ensure that the gasket is fully seated in the installation groove.
Install the Smart into a panel that is flat and free of scratches or dents.
Tighten the installation fasteners using a torque of 0.5 N•m (4.5 lb-in).
Failure to follow these instructions can result in injury or equipment damage.
55
Dimensions/Assembly
The corresponding gasket is provided in the maintenance kit ref:
MPC YK 50 MNT KIT.
Installation Fasteners
CAUTION
OVERTORQUE AND LOOSE HARDWARE z z
Do not exert more than 0.6 N•m (5.3 lb-in) of torque when tightening the installation fastener, enclosure, accessory, or terminal block screws. Tightening the screws with excessive force can damage the plastic casing of the Smart15"
When installing or removing screws, ensure that they do not fall inside the
Smart 15" unit's chassis.
Failure to follow these instructions can result in injury or equipment damage.
NOTE: The screw installation fasteners are required for NEMA4 protection.
56
35015036 07/2010
Dimensions/Assembly
Installing the Smart Unit
Follow the steps given below when installing the Smart.
Step
1
Action
Place the unit face down on a dry, soft surface and attach the gasket to the rear side, in the installation groove (see picture below):
2 Check that the gasket is correctly attached to the unit. The upper surface of the gasket should protrude evenly approximately 2 mm (0.08 in.) out of the groove.
Note:
When installing the Smart unit's installation gasket, avoid contact with the sharp edges of the Smart's frame, and press the gasket completely into its groove.
35015036 07/2010
57
Dimensions/Assembly
Step
3
Action
Insert each installation fastener securely into the slot’s recess at the top and bottom of the unit:
58
4 Attach and Secure the Rear Installation Attachments:
5
Note: z z
Excessive torque may damage the Smart unit.
To ensure a high degree of moisture resistance, the torque should be 0.5 N•m z
(4.5 lb-in).
Insert each of the fasteners as shown below. Be sure to pull the fasteners back until it is flush with the rear of the attachment hole.
Insert each of the fasteners. Pull the fastener back until it is flush with the rear of the attachment hole.
Note:
The corresponding installation attachments can be purchased as spare parts with the maintenance kit ref.: MPC YK 50 MNT KIT.
35015036 07/2010
35015036 07/2010
Dimensions/Assembly
Step
6
Action
Use a screw driver to tighten to 0.5 N•m (4.5 lb-in) each of the fastener screws and secure the Smart in place:
7 Smart Viewing Angle (See Display Characteristics
).
Ensure that the panel’s viewing angle is tilted no more than 30 degrees from parallel to the operator (i.e. operator is directly in front).
59
Dimensions/Assembly
60
35015036 07/2010
Implementation
35015036 07/2010
Implementation
II
Subject of this Part
This part describes the implementation of the product.
What's in this Part?
This part contains the following chapters:
Chapter
5
6
7
8
Chapter Name
Getting Started
Main Power Connection
Configuration of the BIOS
Hardware Modifications
Page
35015036 07/2010
61
Implementation
62
35015036 07/2010
Getting Started
35015036 07/2010
Getting Started
5
First Power-up
License Agreement
NOTE: Limitations on your usage of the Windows XPe or Windows XPpro Operating
System are noted in Microsoft's End User License Agreement (EULA). This EULA is included on the CD-ROM. Please read this document before first power-up.
On first power-up of your HMIPS****, it is necessary to customize and set the parameters for your system. Refer to the Magelis Installation Guide.
Install, customize and parameterize the Schneider Electric applications (Unity pro,
PL7 Junior or PL7 Pro, Vijeo Designer, Vijeo Designer Lite, OFS, MMI 17, XBTL
1000, PL7-07).
Some Useful Tools
A selection of program icons are displayed on the task bar which can be used to launch some useful programs:
Icon Usage
This is the virtual keyboard. Once you click on it, a graphical keyboard is displayed. It is useful when you do not want to connect, or cannot connect a keyboard to the unit.
This is the virtual mouse button selector. It allows the user to associate the next "click" to a "right click". For instance, this tool permits the use of context sensitive menus.
63
35015036 07/2010
Getting Started
Icon Usage
Configuration Panel / Brightness: this link allows the user to change the brightness of the screen (useful for dark areas).
These icons indicate the status of the Enhanced Write Filter (EWF)
Manager. They are located in the system tray on the Windows taskbar.
Only available for Smart with Windows® XPe pre-installed
EWF Manager Enhanced Write Filter
The Magelis Smart HMIPSC7**** and HMIGTW7353 operating system, Windows®
XPe, is installed on a memory cartridge. This cartridge is a re-writable "Compact
Flash" card and it allows approximately 100,000 write operations before it should be replaced.
The Enhanced Write Filter (EWF) Manager minimizes the number of write operations to help extend the life of the CF Card. It loads temporary data (for example, system updates and software operations) into RAM, and does not at any point write this information to the CF Card.
Therefore, if the EWF is enabled, a restart of the Smart 15" will cause any changes the user made to the system to be overwritten. The following types of modifications may be overwritten if the EWF Manager is active and the system is restarted: z z z z z
Newly installed applications
Newly installed peripherals
Newly created or modified user accounts
Network configuration changes (e.g., IP address, default gateway, etc.)
Operating System customizations (background pictures, etc.)
CAUTION
DATA AND CONFIGURATION LOSS z z z
Disable the EWF Manager before making any permanent changes to the hardware, software, or Operating System of the Smart 15" device. Confirm that the EWF icon in the Windows system tray has a red "X".
Re-enable the EWF Manager after making permanent changes and confirm that the EWF icon in the Windows system tray does not have a red "X". This can help extend the operating life of the CF Card.
Back up all CF Card data regularly to another storage media.
Failure to follow these instructions can result in equipment damage.
64
35015036 07/2010
Getting Started
Enabling/Disabling of EWF Manager
The status of the EWF Manager may be changed by running the
ChangeEWFstate.exe
program located in the C:\Program files\Schneider
Electric\EWF directory. After running this program, a system restart is required for the change to take effect. Administrator privileges are required to enable and disable the EWF Manager.
35015036 07/2010
65
Getting Started
66
35015036 07/2010
Main Power Connection
35015036 07/2010
Main Power Connection
6
Subject of this Chapter
This chapter describes the connection of the Smart 15" to the main power supply.
What's in this Chapter?
This chapter contains the following topics:
Topic
Grounding
Installing the Power Switch Cover
Connecting the DC Power Cord
Connecting the AC Power Cord
Control Drawing of the USB outlet on the Magelis iPC
Page
67
35015036 07/2010
Main Power Connection
Grounding
Overview
The grounding resistance between the Smart’s Frame Ground (FG) and Ground must be 100 Ω or less. When using a long grounding wire, check the resistance and if required replace a thin wire with a thicker wire and place it in a duct. In addition, please refer to the table below for maximum line lengths for the thickness of wire.
Ground Wire Dimensions
Wire Thickness
2 mm
2
(14 AWG)
1.5 mm
2
(16 AWG)
Maximum Line Length
30 m (98 ft.)
60 m (196 ft.) round trip.
20 m (65 ft.)
40 m (131 ft.) round trip.
Precaution
WARNING
UNINTENDED EQUIPMENT OPERATION z z z
Use only the authorized grounding configurations shown below.
Confirm that the grounding resistance is 100 Ω or less.
Test the quality of your ground connection before applying power to the device.
Excess noise on the ground line can disrupt the Smart's operations.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Dedicated Ground
Connect the Frame Ground (FG) to a dedicated ground.
68
35015036 07/2010
Main Power Connection
Shared Ground Allowed
If a dedicated ground is not possible, use a shared ground, as shown below.
Shared Ground not Allowed
Do not connect the Smart 15’’ unit to ground through other devices using the SG terminals.
Shared Ground - Avoid Ground Loop
When connecting an external device to a Smart with the Shield Ground (SG), ensure that no ground loop is created. The Smart’s FG and SG are connected internally.
Grounding Procedure
When grounding, follow the procedures given below:
35015036 07/2010
Step Action
1 Check that the grounding resistance is 100
Ω
or less.
2 When connecting the SG line to another device, ensure that the design of the system/connection does not produce a ground loop.
Note: the SG and FG terminals are connected internally in the Smart 15".
3
Wherever possible, use 2 mm
2
(14 AWG) wire to make the ground connection. If this isn't possible, ensure that the grounding wire gauge and length conform to the table in Ground Wire Dimensions
. Create the connection point as close to the iCP as possible and make the wire as short as possible.
69
Main Power Connection
Grounding I/O Signal Lines
DANGER
EXPLOSION HAZARD z z
Always confirm the UL 1604, ANSI/ISA 12.12.01 or CSA C22.2 N
°
213, hazardous location rating of your device before installing or using it in a hazardous location.
To apply or remove the supply power from a Smart 15’’ device installed in a
Class I, Division 2 hazardous location, you must either: z Use a switch located outside the hazardous environment, or; z Use a switch certified for Class I, Division 1 operation inside the hazardous area.
z z z z
Do not connect or disconnect any cables or wires while the circuit is live unless the area is known to be free of ignitable concentrations of vapors, gases, and other flammable or combustible materials. This applies to all connections including power, ground, serial, parallel, and network connections.
Never use unshielded / ungrounded cables in hazardous locations.
Use only non-incendiary USB devices
.
When enclosed, keep enclosure doors and openings closed at all times to avoid the accumulation of foreign matter inside the workstation.
Failure to follow these instructions will result in death or serious injury.
WARNING
UNINTENDED EQUIPMENT OPERATION z z
Do not wire I/O lines in proximity to power cables, radio devices, or other equipment that may cause electromagnetic interference.
If wiring of I/O lines near power lines or radio equipment is unavoidable, use shielded cables and ground one end of the shield to the Smart's Frame Ground
(FG).
Electromagnetic radiation may interfere with the Smart's control communications.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
70
35015036 07/2010
Main Power Connection
Installing the Power Switch Cover
Introduction
In hazardous locations, AC powered devices must be equipped with a power switch
compliant with Class I, Division 2 requirements (see Hazardous Location
Installations - For USA and Canada, page 23
).
To make the power switching compliant with Class I, Division 1 requirements, you z z must: install a power switch cover on your Smart unit power switch use only a remote main power switch located outside the Smart unit location to switch power on or off.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH z z z z z
Remove all power from the device before removing any covers or elements of the system and prior to installing or removing any accessories, hardware, or cables.
Always use a properly rated voltage sensing device to confirm power is off.
Unplug the power cable from both the Smart unit and the power supply.
Replace and secure all covers or elements of the system before applying power to the unit.
Use only the specified voltage when operating the Smart 15''. The AC unit is designed to use 100 ... 240 Vac input. The DC unit is designed to use
23 ... 25 Vdc. Always check whether your device is AC or DC powered before applying power.
Failure to follow these instructions will result in death or serious injury.
35015036 07/2010
71
Main Power Connection
Installing the Power Switch Cover
The procedure below describes how to install a power switch cover:
Step
1
2
3
4
Action
Shut down Windows® in an orderly fashion and remove all power from the device.
Remove the Smart unit from its mounting and place it on a clean level surface with the front panel facing downwards.
Switch ON the power switch.
Attach the power switch cover with the screw. Use a torque of 0.5 to 0.6 N•m (4.5 to 5.3 lb-in):
5 First ensure that the power cord is disconnected from the main power supply, then
connect the power cord to the Smart unit (see Connecting the AC Power Cord, page 77
).
Remote Main Power Switch
NOTE: After installing the Smart unit power switch cover, this power switch should not be used anymore.
To power on or off, you must either: z use the main power switch located outside the Smart unit location, or: z connect or disconnect the AC power cord connector, located outside the Smart unit location, from the main power supply connector.
72
35015036 07/2010
Main Power Connection
Connecting the DC Power Cord
Precaution
When connecting the Smart unit’s power cable to the power connector on the unit, first ensure that the power cord is disconnected from the main DC power supply.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH z z z z z
Remove all power from the device before removing any covers or elements of the system, and prior to installing or removing any accessories, hardware, or cables.
Always use a properly rated voltage sensing device to confirm power is off.
Unplug the power cable from both the Smart unit and the power supply.
Replace and secure all covers or elements of the system before applying power to the unit.
Use only the specified voltage when operating the Smart 15". The AC unit is designed to use 100...240 Vac input. The DC unit is designed to use
23 ... 25 Vdc. Always check whether your device is AC or DC powered before applying power.
Failure to follow these instructions will result in death or serious injury.
WARNING
EQUIPMENT DISCONNECTION OR UNINTENDED EQUIPMENT OPERATION z z z
Ensure that power, communication, and accessory connections do not place excessive stress on the ports. Consider the vibration environment when making this determination.
Securely attach power, communication, and external accessory cables to the panel or cabinet.
Use only commercially available USB cables.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
35015036 07/2010
73
Main Power Connection
Wiring and Connecting the Terminal Block (DC Smart Version)
When wiring and connecting the Smart power cables, be sure to follow the procedures given below:
Step Action
1 Remove all power from the Smart 15" and confirm that the DC power supply has been disconnected from its power source.
2 Connect the power cord
to the terminal block as shown below.
3
Use wire with cross-section 0.75 mm² to 2.5 mm² (AWG18 to AWG12)
Place the terminal block in the power connector and tighten the screws. The recommended torque to tighten these screws is 0.5 N•m (4.5 lb-in):
74
NOTE: The 24 Vdc power supply inside the DC-powered Smart unit is protected by an 8A fuse. This fuse is located inside the power supply and cannot be accessed or replaced by the user.
35015036 07/2010
Main Power Connection
Possible Connections
Connection to a Floating (Ungrounded) DC Power System:
Some specific applications require the use of a floating (ungrounded) power system.
The characteristics of such as system, as it might apply when a DC-powered Smart z z
15’’ is installed, are as follows:
The 0 Vdc power line and Frame Ground (FG) are connected internally.
The 24 Vdc power line is isolated from the FG and from the outputs. The dielectric strengths for these are: z z
Primary/Secondary: 1000 Vac
Primary/Ground: 1000 Vac
35015036 07/2010
75
Main Power Connection
Connection to a Ground-Referenced DC Power System:
Q : Mains Power Contactor
KM : Line contactor
(1) : Residual Current Detector for detecting grounding faults
(2) : Terminal block
NOTE: Schneider suggests the use of the TSX SUP 1101 DC Power Supply to provide the Smart unit's 24 Vdc power.
76
35015036 07/2010
Main Power Connection
Connecting the AC Power Cord
Precaution
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH z z z z z
Remove all power from the device before removing any covers or elements of the system and prior to installing or removing any accessories, hardware, or cables.
Always use a properly rated voltage sensing device to confirm power is off.
Unplug the power cable from both the Smart unit and the power supply.
Replace and secure all covers or elements of the system before applying power to the unit.
Use only the specified voltage when operating the Smart 15’’. The AC unit is designed to use 100...240 Vac input. The DC unit is designed to use 23 ... 25
Vdc. Always check whether your device is AC or DC powered before applying power.
Failure to follow these instructions will result in death or serious injury.
WARNING
EQUIPMENT DISCONNECTION OR UNINTENDED EQUIPMENT OPERATION z z z
Ensure that power, communication, and accessory connections do not place excessive stress on the ports. Consider the vibration environment when making this determination.
Securely attach power, communication, and external accessory cables to the panel or cabinet.
Use only commercially available USB cables.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
35015036 07/2010
77
Main Power Connection
Power Cord Connection (AC Smart Version)
The table below describes how to connect the power cord to the Smart unit:
Step
1
Action
Connect the power cord to the terminal block as shown below:
2 Place and screw the terminal block on the Smart unit’s power connector. Tighten the screws using a torque of 0.5 to 0.6 N·m (4.5 to 5.3 lb-in)
78
35015036 07/2010
Main Power Connection
Control Drawing of the USB outlet on the Magelis iPC
Introduction
The information below concerns the use of the USB outlet located on the front panels of the Magelis iPC used in Class I, Division 2 Groups A, B, C, and D hazardous locations.
DANGER
EXPLOSION HAZARD z z
Always confirm the UL 1604, ANSI/ISA 12.12.01 or CSA C22.2 N
°
213 hazardous location rating of your device before installing or using it in a hazardous location.
To apply or remove the supply power from a Smart 15’’ device installed in a
Class I, Division 2 hazardous location, you must either: z Use a switch located outside the hazardous environment, or; z Use a switch certified for Class I, Division 1 operation inside the hazardous area.
z z z z
Do not connect or disconnect any cables or wires while the circuit is live unless the area is known to be free of ignitable concentrations of vapors, gases, and other flammable or combustible materials. This applies to all connections including power, ground, serial, parallel, and network connections.
Never use unshielded / ungrounded cables in hazardous locations.
Use only non-incendiary USB devices.
When enclosed, keep enclosure doors and openings closed at all times to avoid the accumulation of foreign matter inside the workstation.
Failure to follow these instructions will result in death or serious injury.
35015036 07/2010
79
Main Power Connection
Description
Non-incendiary equipment (keyboards, mouse) are permitted for use on the Smart
15’’ unit’s Front USB port. In addition to being non-incendiary, any equipment connected to the Front USB port must satisfy the following criteria (information taken from Schneider Electric document S1A2983400):
80
Notes:
1. Non-incendiary Circuit Parameters:
Front USB Port:
Open-circuit voltage
Short-circuit current
Associated capacitance
Associated inductance
Voc = 5.0 V
Isc = 1.25 A
Ca = 10
μ
F
La = 16
μ
H
2. Associated Non-incendiary Field Wiring Apparatus shall satisfy the following:
Associated Non-incendiary Field Wiring
Apparatus (Mouse, Keyboard)
-
Voc
Isc
Ca
La
≥
≥
≤
≤
Magelis iPC
Vmax
Imax
Ci + C cable
Li + L cable
3. If the electrical parameters of the cable are unknown, the following values may be used: Capacitance = 60pF/ft and Inductive = 0.20 μ H/ft.
4. Non-incendiary Field Wiring must be installed in accordance with article
501.4(B)(3) of the National Electrical Code ANSI/NFPA 70.
5. Associated Non-incendiary Field wiring Apparatus shall not contain or be connected to another source of power.
35015036 07/2010
Configuration of the BIOS
35015036 07/2010
Configuration of the BIOS
7
Accessing the BIOS
Overview
NOTE: Normally, factory (defaults) settings should be used.
Connect a USB or PS/2 keyboard to the Smart unit.
Switch on the Smart unit power and when prompted to do so, press the F2 key to enter the BIOS.
Main Menu
Selecting the Main menu item displays the following screen:
35015036 07/2010
NOTE: When you have finished entering the parameters, press the Esc key to reach the Exit menu. Here you will be prompted either to exit saving the changes, or to exit without saving the changes as described below.
81
Configuration of the BIOS
System Time
Time (hh:mm:ss)
This field shows the present Smart unit time from the internal clock. The hh/mm/ss
(00:00:00) format is factory set prior to shipping.
Hours: 00 to 23
Minutes: 00 to 59
Seconds: 00 to 59
The correct time can be set by using the [+] and [-] keys.
System Date
Date (yy:mm:dd)
This field shows the Smart unit’s internal calendar. The correct date can be set by using the [+] and [-] keys.
Year: 1999 to 2099
Month: Jan/Feb/Mar/Apr/May/Jun/Jul/Aug/Sep/Oct/Nov/Dec
Day: 1 to 31
Primary Master
Displays the name of the devices connected to the primary bus of the Smart.
Pressing the Enter key will call up the Parameter Settings menu.
Primary Slave
Displays the name of the devices connected to the secondary bus of the Smart.
Pressing the Enter key will call up the Parameter Settings menu.
System Memory
Displays the capacity of the System Memory.
Extended Memory
Displays the capacity of the Extended Memory.
82
35015036 07/2010
Configuration of the BIOS
Password Security
From the Main menu use the Tab key to reach the Security menu. This menu is used for setting Supervisor and User Passwords.
Supervisor Password
This password is used to change system information settings. It is designed to prevent unapproved users from changing these settings. Entering up to 8 characters here will overwrite the current password.
When you wish to have no password, click on the Enter key. Next, the words
"PASSWORD DISABLE" will be displayed, providing confirmation that the
Password is no longer set.
35015036 07/2010
83
Configuration of the BIOS
User Password
This password is used to view system information settings. It is designed to prevent unapproved users from viewing the system information settings. Entering up to 8 characters here will overwrite the current password.
When you wish to have no password, click on the Enter key. Next, the words
"PASSWORD DISABLE" will be displayed, providing confirmation that the
Password is no longer set.
NOTE: z z z
Without having defined a Supervisor Password, it is not possible to define a User
Password.
When using Set Supervisor Password , you can easily view and change the system settings.
When using only Set User Password , you will be allowed to view the system data only, not change it.
Exit BIOS saving the Modifications
This feature saves the settings entered in the Setup Utility and restarts the
Smart unit.
Exit BIOS Without Saving Modifications
This feature quits the Setup Utility program without saving any settings entered.
84
35015036 07/2010
Hardware Modifications
35015036 07/2010
Hardware Modifications
8
Subject of this Chapter
This chapter concerns the hardware modifications for the Magelis Smart 15".
A wide variety of optional units, CF cards manufactured by Schneider Electric and commercial PCMCIA (PC Cards) can be used with this product.
What's in this Chapter?
This chapter contains the following topics:
Topic
Before Modifications
Removing the Smart Unit’s Cover
Smart 15" Internal View
USB Front Face
PCMCIA Card Installation
Compact Flash (CF) Card Installation and Removal
USB Cable Clamp Attachment/Removal
Page
85
35015036 07/2010
Hardware Modifications
Before Modifications
Overview
For the detailed installation procedures for the optional units, refer to the OEM
(Original Equipment Manufacturer) Installation Guide included with the optional unit.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH z z z z z
Remove all power from the device before removing any covers or elements of the system, and prior to installing or removing any accessories, hardware, or cables.
Always use a properly rated voltage sensing device to confirm power is off.
Unplug the power cable from both the Smart unit and the power supply.
Replace and secure all covers or elements of the system before applying power to the unit.
Use only the specified voltage when operating the Smart 15". The AC unit is designed to use 100...240 Vac input. The DC unit is designed to use
23 ... 25 Vdc. Always check whether your device is AC or DC powered before applying power.
Failure to follow these instructions will result in death or serious injury.
DANGER
CHEMICAL BURNS TO EYES OR SKIN z z z
Do not use tools to operate the touch panel or in the vicinity of the display.
When placing the display face-down, select a clean, level, non-abrasive surface. Place a soft, non-abrasive pad on the surface before lowering the unit upon it.
If a leak in the LCD panel is discovered, and you come in contact with the liquid crystal material, follow these procedures: z In the case of contact with eyes or mouth, flush with running water for 15 minutes minimum.
z z
In the case of contact with skin or clothing, wipe off the liquid crystal material and wash with soap and running water for 15 minutes.
If liquid crystal is ingested, induce vomiting, rinse mouth, and then drink a large quantity of water.
z Follow any other hazardous substances safety procedures required by your facility.
Failure to follow these instructions will result in death or serious injury.
86
35015036 07/2010
35015036 07/2010
Hardware Modifications
DANGER
EXPLOSION HAZARD z z
Always confirm the UL 1604, ANSI/ISA 12.12.01 or CSA C22.2 N ° 213 hazardous location rating of your device before installing or using it in a hazardous location.
To apply or remove the supply power from a Smart 15’’ device installed in a
Class I, Division 2 hazardous location, you must either: z Use a switch located outside the hazardous environment, or; z Use a switch certified for Class I, Division 1 operation inside the hazardous area.
z z z z
Do not connect or disconnect any cables or wires while the circuit is live unless the area is known to be free of ignitable concentrations of vapors, gases, and other flammable or combustible materials. This applies to all connections including power, ground, serial, parallel, and network connections.
Never use unshielded/ungrounded cables in hazardous locations.
Use only non-incendiary USB devices
.
When enclosed, keep enclosure doors and openings closed at all times to avoid the accumulation of foreign matter inside the workstation.
Failure to follow these instructions will result in death or serious injury.
CAUTION
OVERTORQUE AND LOOSE HARDWARE z z
Do not exert more than 0.6 N•m (5.3 lb-in) of torque when tightening the installation fastener, enclosure, accessory, or terminal block screws. Tightening the screws with excessive force can damage the plastic casing of the Smart 15".
When installing or removing screws, ensure that they do not fall inside the
Smart 15" unit's chassis.
Failure to follow these instructions can result in injury or equipment damage.
CAUTION
STATIC SENSITIVE COMPONENTS
Smart 15" internal components, including accessories such as RAM modules and expansion boards, can be damaged by static electricity. Observe the electrostatic precautions below when handling such components.
Failure to follow these instructions can result in injury or equipment damage.
87
Hardware Modifications
Precautions to be taken: z z z z
Keep static-producing materials (plastic, upholstery, carpeting) out of the immediate work area.
Do not remove ESD-sensitive components from their anti-static bags until you are ready to install them.
When handling static-sensitive components, wear a properly grounded wrist strap (or equivalent).
Avoid unnecessary contact with exposed conductors and component leads with skin or clothing.
88
35015036 07/2010
Hardware Modifications
Removing the Smart Unit’s Cover
How to Remove the Smart Unit’s Cover
Step Action
1 Shut down Windows® in an orderly fashion and remove all power from the device.
2
3
Place the unit on a clean, level surface with the display facing downwards. Place a soft, non-abrasive pad on the surface before placing the unit upon it.
Loosen the screws attaching the cover as shown below:
4 Remove the cover as shown below:
35015036 07/2010
89
Hardware Modifications
Smart 15" Internal View
Illustration
Description
2
3
Number
1
4
Description
Main Memory Installation Area
PCMCIA Slot (2 ports)
Battery
USB Front Face Setting Location (Activation/Deactivation)
90
35015036 07/2010
Hardware Modifications
USB Front Face
Enabled/Disabled State
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Read and understand the safety information in the sections Before modifications
and Removing the Smart’s unit cover
before attempting this procedure.
Failure to follow these instructions will result in death or serious injury.
35015036 07/2010
91
Hardware Modifications
In order to enable/disable the USB front face port, follow the procedure given below:
3
4
Step Action
1 Shut down Windows® in an orderly fashion and remove all power from the device
2 Place the unit on a clean, level surface with the display facing downwards. Place a soft, non-abrasive pad on the surface before placing the unit upon it.
Remove the Smart’s rear cover
The figure below shows the switch (B6) on the mother board which enables/disables the state of the USB front face port:
92
5 When you have completed your adjustments to switch B6, confirm all switches are in their proper positions and replace the Smart unit’s cover.
WARNING
UNINTENDED EQUIPMENT OPERATION
Before replacing the Smart's cover, confirm that all switches other than B6 are still in their default positions as indicated in the preceding figure.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
35015036 07/2010
Hardware Modifications
PCMCIA Card Installation
Overview
Before installing or removing a PCMCIA card, shut down Windows® in an orderly fashion and remove all power from the device.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Read and understand the safety information in the section Before modifications
before attempting this procedure.
Failure to follow these instructions will result in death or serious injury.
PCMCIA Cards with Cables
When using a PCMCIA card with an external cable attached, install a clamp or other type of device to secure the cable.
WARNING
EQUIPMENT DISCONNECTION OR UNINTENDED EQUIPMENT OPERATION z z z
Ensure that power, communication, and accessory connections do not place excessive stress on the ports. Consider the vibration environment when making this determination.
Securely attach power, communication, and external accessory cables to the panel or cabinet.
Use only commercially available USB cables.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: PCMCIA types are differentiated by their thickness: z z z
Type I: 3.3 mm (0.13 in)
Type II: 5 mm (0.20 in)
Type III: 10.5 mm (0.41 in)
35015036 07/2010
93
Hardware Modifications
Installing a Type I or Type II PCMCIA Card
The table below describes how to install a Type I or Type II PCMCIA Card:
Step Action
1 To install a Type I or Type II PCMCIA card, loosen the screws on the side of the
PCMCIA slot and move the cover to one side.
2 Press the eject button twice. Insert the PCMCIA card into the lower slot and push it in until the PCMCIA pins mate with the slot connector pins.
94
35015036 07/2010
Hardware Modifications
Installing a Type III PCMCIA Card
The table below describes how to install a Type III PCMCIA Card:
Step Action
1 To install a Type III PC card, unscrew the PCMCIA slot cover and remove the cover as shown below:
2
3 Press both eject buttons twice. Insert the PCMCIA card into the slots and push it in until the PCMCIA pins mate with the slots connector pins.
Removing a PCMCIA Card
The table below describes how to remove a PCMCIA Card:
Step Action
1 To remove the PCMCIA card: Press both eject buttons twice (Pressing the eject buttons once causes the tip of the card to be exposed. Pressing the eject buttons a second time ejects the PCMCIA card from the slot). Withdraw the PCMCIA card.
2 Reposition the PCMCIA slot cover and tighten the screw.
35015036 07/2010
95
Hardware Modifications
Compact Flash (CF) Card Installation and Removal
Preparing to use a CF Card
The Smart's operating system views the CF Card as a hard disk. Proper handling and care of the CF Card helps extend the life of the Card. Familiarize yourself with the Card prior to attempting insertion or removal of the Card.
CAUTION
COMPACT FLASH CARD DAMAGE AND DATA LOSS z z z z z z z
Remove all power before making any contact with an installed CF card.
Use only CF cards manufactured by Schneider Electric. The performance of the
Smart 15" has not been tested using CF cards from other manufacturers
Confirm that the CF Card is correctly oriented before insertion.
Do not bend, drop, or strike the CF card.
Do not touch the CF card connectors.
Do not disassemble or modify the CF card.
Keep the CF card dry.
Failure to follow these instructions can result in injury or equipment damage.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Read and understand the safety information in the section Before modifications
before attempting this procedure.
Failure to follow these instructions will result in death or serious injury.
96
35015036 07/2010
Hardware Modifications
Inserting the CF Card
The table below describes how to insert the CF Card.
Step Action
1 Shut down Windows in an orderly fashion and remove all power from the device.
2 Unscrew the CF Card cover's attachment screw, and remove the CF Card cover.
3 Insert the CF Card firmly into the CF card slot, and check that the eject button pops out.
4 Replace the CF Card cover and attach it in place with the screw.
Note: The necessary torque is 0.5 to 0.6 N•m (4.5 to 5.3 lb-in).
35015036 07/2010
97
Hardware Modifications
Removing the CF Card
The table below describes how to remove the CF Card.
Step Action
1 Shut down Windows® in an orderly fashion and remove all power from the device, then remove the CF card cover as described above.
2 Press the eject button in fully to remove the CF Card from the CF Card slot.
3 After inserting/removing the CF card, be sure to replace the CF Card cover and secure it in place using the attachment screw.
Note: The necessary torque is 0.5 to 0.6 N•m (4.5 to 5.3 lb-in).
Data Writing Limitation
The CF Card is limited to approximately 100,000 write operations. Back up all CF
Card data regularly to another storage media.
Backup of the CF Card Data
Refer to the relevant procedure in the Software Installation Guide for Magelis
Industrial PC and Terminals.
98
35015036 07/2010
Hardware Modifications
USB Cable Clamp Attachment/Removal
Introduction
When using a USB device, attaching the USB cable with a clamp to the Smart unit’s bridge (located on the side of the USB ports) prevents the USB device from becoming disconnected.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Read and understand the safety information on Before modifications
and Removing the Smart’s unit cover
before attempting this procedure.
Failure to follow these instructions will result in death or serious injury.
WARNING
EQUIPMENT DISCONNECTION OR UNINTENDED EQUIPMENT OPERATION z z z
Ensure that power, communication, and accessory connections do not place excessive stress on the ports. Consider the vibration environment when making this determination.
Securely attach power, communication, and external accessory cables to the panel or cabinet.
Use only commercially available USB cables.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
35015036 07/2010
99
Hardware Modifications
USB Cable Clamp Attachment
The table below describes how to attach the USB holder.
Step Action
1 Shut down Windows® in an orderly fashion and remove all power from the device.
2 Place the unit on a clean, level surface with the display facing downwards. Place a soft, non-abrasive pad on the surface before placing the unit upon it.
3 Insert the USB cable clamp’s band through the bridge. Pass the USB cables through the cable clamp’s band and securely tighten the clamp band around the cables.
Notes: z When using two or more USB ports, be sure to first connect one USB cable to the lower USB connector, and then connect the second USB cable to the upper USB connector.
z When using only one of the USB ports, be sure to use the lower USB connector.
This allows you to securely clamp the USB cable in the cable clamp.
z z
Be sure the clamp is securely holding the USB cable’s plug and collar.
Be sure the clamp is positioned pointing upwards - not to the side. This is to keep the clamp from interfering with nearby connectors and their cables.
o
100
35015036 07/2010
Hardware Modifications
USB Cable Clamp Removal
The table below describes how to remove the USB cable clamp.
Step Action
1 To remove the clamp from the USB cables, push down on the clamp strap’s clip to release it while pulling up on the clamp.
2 Remove the USB cables.
3 Remove the clamp’s band from the bridge.
35015036 07/2010
101
Hardware Modifications
102
35015036 07/2010
Installation
35015036 07/2010
Installation
Subject of this Part
This part describes the product installation.
What's in this Part?
This part contains the following chapters:
Chapter
9
10
11
12
Connections to PLCs
System Monitoring
Maintenance
Troubleshooting
Chapter Name
III
Page
103
35015036 07/2010
Installation
104
35015036 07/2010
Connections to PLCs
35015036 07/2010
Connections to PLCs
Connection to PLCs
Introduction z z
Two different kinds of architectures are possible:
Transparent Ready Architecture
Traditional Architecture
Connections to Transparent Ready Architectures
9
35015036 07/2010
With its built-in Ethernet 10/100 Mbps ports, the Smart 15" can be integrated into full
Ethernet architectures, such as Transparent Ready. Transparent Ready devices with this type of architecture enable transparent communication on the Ethernet
TCP/IP network. Communication services and Web services permit the sharing and distribution of data between levels 1, 2 and 3 of the Transparent Ready architecture.
105
Connections to PLCs
Used as a Client station, the Smart 15" makes it easier to implement Web Client solutions for: z Basic servers embedded in field devices (Advantys STB/Momentum distributed z
I/O, ATV 71/38/58 starters, OsiSense identification systems, etc.).
FactoryCast Web servers embedded in Modicon PLCs (TSX Micro, Premium and
Quantum) or the FactoryCast gateway. The following services are available as standard (without the need for additional programming): alarm management, z comprehensive view management and Web home pages created by users.
FactoryCast HMI Web servers embedded in Modicon Premium and Quantum
PLCs also provide basic data management services, automatic e-mail sending triggered by specific process events and arithmetic and logic calculations for data preprocessing.
HMI Applications in Traditional Architectures
106
The Smart 15" terminal with Vijeo Designer control or automation software can be used in fieldbus architectures such as Uni-Telway/Modbus or Fipway/Modbus Plus.
The Smart 15"terminal can connect to Uni-Telway, Modbus, and Fipway networks, but different connection devices are required depending on the network and on the communication port used. These devices are specified below: z For PCMCIA slot: z z
Fipway network with the PCMCIA card TSX FPP 20 (1).
Modbus Plus network with the PCMCIA card TSX MBP 100 or the PCI bus z z card 416 NHM 300 30.
Uni-Telway, with an RS 485 TSX SCP 114 card (1).
For a Modbus link, one of the built-in RS 232C COM ports is used.
35015036 07/2010
Connections to PLCs z For USB slot: z Modbus and Uni-Telway with the TSXCUSB485 converter. It allows an iPC to be connected to remote devices using an RS 485 interface.
This device, compatible with Modbus and Uni-Telway, requires the standard
Schneider drivers provided with software such as UNITY, PL7-Pro or part of the CD driver TLXCDDRV20M. An example is provided in the drawing below: z Modbus Plus network with the TSXCUSBMBP converter. This converter is compatible with PCs equipped with CONCEPT, ProWORX or UNITY.
Example on drawing below:
(1) Requires the X-Way drivers CD-ROM, TLX CD DRV20M.
Cables and Converters
For using the different types of PLCs, the following cables and converters are required: z TSX PCX 1031 connection cable for Nano, Micro and Premium.
z
This cable is supplied with Unity Pro, PL7 Pro and PL7 Junior software.
FT20CBCL30 connection cable for the Series 7 family (included TSX 27 PLCs, and TSX/PMX 47/67/87/107 PLCs).
This cable is supplied with the XTEL Pack software.
z TSX17ACCPC converter for TSX 17 LCs.
35015036 07/2010
107
Connections to PLCs z TSXCUSB232 converter for connecting an iPC, via an USB port, to remote devices using an RS 232 interface.
This device, compatible with Modbus and Uni-Telway, requires the standard
Schneider drivers provided with software such as UNITY, PL7-Pro or part of the
CD driver TLXCDDRV20M. An example is provided in the drawing below:
Q ua nt u m
High End with s eri a l
RJ45
Q ua nt u m
S ep a m
20/40/ 8 0
110XCA20 3 00
+ 110XCA2 8 202
S UBD 9
99 0NAA26 3 20
MiniDin 6
S UBD 9
CCA7 83
This device can be used as a PCMCIA port.
U S B-A
108
35015036 07/2010
System Monitoring
35015036 07/2010
System Monitoring
10
Subject of this Chapter
This chapter describes the system monitoring and the RAS (reliability, availability and serciceability) features of the Smart.
What's in this Chapter?
This chapter contains the following topics:
Topic
System Monitor Overview
System Monitor Property
System Monitor Interface
Page
109
35015036 07/2010
System Monitoring
System Monitor Overview
Presentation
The System Monitor software enables you to monitor several system parameters
(CPU temperature, normal operation of the miscellaneous voltages, normal operation of the backlight, normal operation of the hard disk...) as well as controlling the RAS I/O port.
The RAS I/O port is an interface that enables you to direct a remote reset of the
Smart, operate a buzzer or perform other actions as noted in the section.
The System Monitor software alerts you if thresholds are exceeded via a popup message or a Windows alarm (in the Event Viewer). You can also configure actions to be undertaken: shutdown the Smart, restart the Smart, I/O activation...).
The software enables both system configuration (See System Monitor Property
) and system operation (See System Monitor Interface
).
110
35015036 07/2010
System Monitor Architecture
The following figure shows the architecture of System Monitor:
System Monitoring
35015036 07/2010
1 Bios Setup: Voltage, Temperature alarm, Detection Level Setting, Enable/Disable Settings
2 System Properties: Power alarm, Touch Panel Alarm, Output Settings, Watchdog Timer
Value Settings, Watchdog Reset, Enable/Disable Settings
3 Popup Message
4 OS Shutdown
5 User Application
6 Bios
7 System Alarm Data
111
System Monitoring
RAS Features
8 System Monitor Application
9 Driver or API-DLL
10 Buzzer
11 LED Green: Power On - LED Orange: RAS Error/Touch Panel Self Test Error -
LED Orange/Red blinking: Backlight Error - LED Green Blinking: Soft OFF Status.
12 Watchdog Timer Reset, Mask settings
13 Reset Control
14 Watchdog Timer
15 Hardware Reset
16 RAS Connector: DIN (4 Ports), DOUT (4 Ports), RESET IN.
*
1
Be sure to adjust these settings according to your system’s specification.
*
2
The RAS Software may be configured to provide these output alarms/signals.
RAS stands for Reliability, Availability and Serviceability. It is a device-level monitoring function that provides a variety of features to improve the reliability of the
Smart 15" system.
Although the standard set of RAS features will vary depending on the devices used, the following features provide alarm monitoring and external input signal support.
Feature
Alarm Monitoring
External Input Signal
Functions Supervised
Power Voltage Alarm
Internal Temperature Alarm
Watchdog Timer (System uptime)
SMART Alarm
Backlight Alarm
General Purpose Signal Input *1 (DIN (4 ports))
Remote Reset Input *2 (1 lamp)
*1: An error message or other signal received on DIN1 (that is, a change of state on this input from 0 to 1 or 1 to 0) is stored in memory, and cannot be cleared by clicking on the Alarm dialog box generated by the System Monitor. The System Monitor software periodically checks the state of DIN1, and will display the Alarm dialog until the actual state of the DIN1 input reverts to the normal state. The other input alarms may be cleared by clicking on the Alarm dialog box.
*2: If the Remote Reset Input is disabled, DOUT cannot be configured to force a system reset.
112
35015036 07/2010
System Monitoring
The Smart's RAS software may be programmed to provide the following outputs when one of the alarms mentioned above occurs, or when an external input signal is received.
Feature
External Output Signal
Various Processing Functions
Functions Supervised
General Purpose Signal Output (DOUT (4 ports))
LED Indicator (3 colors, 1 lamp)
Popup Message Output
Buzzer Output
System Shutdown
System Reset
External Input Signals
The RAS interface connector of the Smart unit accepts the following input signals:
Feature
General Purpose Signal
Input (DIN (4 ports))
Remote Reset Input
Functions Supervised
This standard digital input is used for alarm detection in external devices. The input signal uses four bits. The System
Monitor Property of the control panel or an API-DLL can be used to enable or disable this feature, as well as to designate what type of processing is to be performed once a signal is received. (Only the "ON" state of the DIN circuit is detected.
The "OFF" state cannot be monitored).
This is the reset signal sent from an external device to the
Smart 15". When this signal is enabled, a forced reset of the
Smart 15" is performed.
z z z z z
Input Voltage: 12...24 Vdc
Input Current: 10 mA
Operating ON Voltage: 10 Vdc (min.)
Operating OFF Voltage: 3 Vdc (max.)
Isolation Method: Via Photocoupler
The RAS input circuits must be powered by an external DC power supply.
CAUTION
OVERCURRENT DAMAGE TO INPUTS
Use a protective impedance or other reasonable measures to limit the current to each input to 10 mA or less.
Failure to follow these instructions can result in injury or equipment damage.
35015036 07/2010
113
System Monitoring
The Interface Circuit Diagram is shown below:
See RAS interface
for details about cabling.
External Output Signals
The RAS interface connector on the Smart unit is prepared for the following output signals:
Feature Functions Supervised
General Purpose Signal
Output (DOUT (4 ports))
External Output Signal
(DOUT, common use with
Alarm Output) z z z
This general purpose digital output signal provides system condition information to external devices. The System Monitor
Property of the control panel or the API-DLL is used by applications to control this signal. The system Monitor Property can be used to enable or disable any of these output signals. z
Rated Load Voltage: 12....24 Vdc
Maximum Load Current: 120 mA/point
Maximum Voltage Drop between Terminals: 1.5Vdc (at 100 mA load current)
Isolation Method: Via Photocoupler
The RAS output circuits must be powered by an external DC power supply.
CAUTION
OVERCURRENT DAMAGE TO OUTPUTS
Use a protective impedance or other reasonable measures to limit the current to each output to 120 mA or less.
Failure to follow these instructions can result in injury or equipment damage.
114
35015036 07/2010
The Interface Circuit Diagram is shown below:
System Monitoring
*1 When connecting an inductive load, be sure to use a flyback diode.
See RAS interface
for details about cabling.
DLL Feature of System Monitor
System Monitor also includes a dynamic link library (API-DLL) feature that gives other applications access to the RAS features.
35015036 07/2010
115
System Monitoring
Accessing the System Monitor
You can monitor the system status at any time using the System Monitor interface.
The procedure below shows how to access the System Monitor interface screen:
Step
1
2
Action
Start the Smart 15" operating system
In the task bar, double-click the icon.
Result : The System Monitor GUI screen appears.
NOTE: If you cannot see the icon in the task bar, launch the System Monitor software by double-clicking the systemmonitor.exe
file located in the following path: C:\schneider\sysmon\gui .
116
35015036 07/2010
System Monitoring
System Monitor Property
Presentation
The System Monitor Property screen enables you to specify which system parameters you want to monitor and how you want to be alerted.
Accessing the System Monitor Property
The System Monitor Property screen enables you to configure the Smart system parameters you want to monitor and select how you want to be alerted. The procedure below shows how to access the System Monitor Property screen:
Step
1
2
3
Action
Start your Smart 15" operating system
Click Start
→
.
Result : The Control Panel window appears.
Double-click System Monitor Property .
Result : The System Monitor Property window appears.
35015036 07/2010
117
System Monitoring
Setting up the System Monitor Properties
The following figure gives an overview of the System Monitor Property setting screen.
118
Click the tabs on the top of the screen to access the configuration page of each system parameter.
The table below describes the system parameters available for monitoring:
Feature
Voltage
Temperature
Functions Supervised
Monitors the status of the Smart’s built-in power supply and internal
CPU power supply.
Provides an alert when a dysfunction of the System, or the CPU, could appear (due to high temperature).
35015036 07/2010
35015036 07/2010
System Monitoring
Feature
Backlight
Watchdog Timer
SMART
Functions Supervised
Detects backlight alarms. When the backlight burns out, the power
LED will flash orange/red (See Smart 15" Unit Description
).
This feature monitors the performance of the CPU by writing the uptime count value for the CPU to the built-in programmable timer of the RAS and by periodically clearing the count value from the CPU.
Errors are detected when the clearing of the count values from the
CPU stops. This causes a timer overflow.
Monitors the status of the hard drive.
Detects degradation in hard disk performance and detects hard disk errors that may result in data loss or operating system corruption.
Only available on Smart + Units and not available on Smart Units
NOTE: SMART monitoring:
A CF card does not support SMART and therefore the status of the CF card cannot be monitored on Smart units.
Once you know the system parameters you want to monitor, you can specify actions that will be undertaken when an event (timeout, value out of range...) occurs. Set the action to be performed when a System Monitor/RAS event occurs, by selecting the relevant check box.
The following table gives a description of the operations that can be performed:
Item
Enable
Buzzer
Popup Message
Operating System Shutdown
Operating System Restart
Power LED
DOUT 0 to 3
Action
Select or deselect this option to enable/disable monitoring feature.
Sound an electronic beep ("This option is automatically disabled" when a check is placed in the "OS shutdown" checkbox).
Display error messages as popup messages. (The monitoring item and description of the error are displayed).
Shutdown the operating system. (The shutdown confirmation message is not displayed).
Resets the hardware.
The Power LED lights orange for an RAS alarm.
Output from the RAS port.
119
System Monitoring
Power LED Indicator
The three colors Power LED (See Smart 15" Unit Description
) indicates the Smart system conditions. It is also a power ON/OFF indicator. The
Power LED is located on the front face of the unit.
The Smart unit can send the following system status information to an external device:
Power LED Color System Status
Green (Lit) Normal operation (Power is ON)
Green (Blinking)
Orange (Lit)
Output Condition
None
System is NOT running (Soft OFF).
See Smart 15" Unit Description
.
An RAS alarm has occurred
None
Power LED is enabled via
System Monitor Property
Touch Panel Self-Test Error
Backlight is not functioning
None
None Orange/Red
(Blinking)
Not Lit Power is OFF –
NOTE: If the orange Power LED of the Smart is illuminated immediately after the power is turned on, a Touch Panel Self-test Error may have occurred.
Features Availability
The following table lists the operating settings available for each feature:
O: Setting available - X: Setting not available
Feature Operation
Buzzer Popup Message OS Shutdown Reset LED DOUT0 to 3
O O O O O O Watchdog
Timer
Voltage
Temperature
Backlight
DIN0 to 3
O
O
O
O
O
O
O
O
X
O
O
O
X
X
X
X
O
O
O
O
O
O
O
O
120
35015036 07/2010
System Monitoring
System Monitor Interface
Presentation
You can monitor the system status at any time using the System Monitor interface.
Description of the Interface
The following screen gives an overview of the System Monitor interface. Selecting each of the tabs displays the status of each item. When an error occurs, the color of the tab changes.
35015036 07/2010
The System Monitor interface displays the status of the system parameters. The following table describes the messages provided by the System Monitor interface:
Display
Pass
Fail
Disabled
Not Supported
Meaning
Normal
Abnormal (exceeds programmed limits)
Monitoring disabled
Not supported
121
System Monitoring
System Monitoring Operation
When an error is detected, the operations specified in the System Monitor Properties settings are performed (buzzer, popup message etc.) and an "X" is displayed on the icon in the system tray indicating an error status.
When the icon in the system tray changes as shown below, double-clicking the icon gives an explanation of the error condition.
The system performs the Error Action set in the System Monitor Properties when an error condition is detected with each monitoring item. The Error Action is performed only once when an error is detected for any of the items being monitored.
For example, look at the "+3.3 V" and "+5.0 V" options in the Voltage field. When the popup message feature for monitoring the voltage status is enabled, the popup message +3.3 V Power Supply Error is shown on the screen if a +3.3 V power supply error occurs. Press the OK button on the dialog box to hide the message.
Example of +3.3 V Power Supply error:
122
If a +5.0 V power supply error occurs, the popup message +5.0 V Power Supply
Error is shown on the screen. The popup message displays the monitored item and an error description. When the buzzer feature is enabled, press the Buzzer Off button on the popup message to stop the buzzer sound. Press the OK button to close the popup message.
35015036 07/2010
System Monitoring
When OS Shutdown is enabled, the system automatically enters the shutdown operation without prompting the user for confirmation. To display the System
Monitor screen for reviewing the present condition and the Smart’s system date and time, double click on the icon in the System Tray.
When the buzzer sounds as an error action, the System Monitor screen displays the
Buzzer Off button that is hidden during normal operation. When a popup message window is displayed, the Buzzer Off button is displayed in the window.
NOTE: Once an error is detected, the System monitor stores the error status
(displays the icon indicating an error status). To resolve the error, press the Reset button on the System Monitor screen or switch off the Smart 15", perform the actions necessary to remove the cause of the error and power up the Smart 15" once more.
System Monitor Error Messages
This section describes the error messages and closing messages displayed on the
System Monitor and System Monitor Property screens.
When an error occurs while the popup message option is enabled for Error Action, the following messages appear on the popup message output screen under the factory settings.
List of the error messages:
Error Generating Item
VcoreA
VcoreB
Voltage +3.3 V
Voltage +5.0 V
Voltage +12 V
System Temperature
CPU Temperature
DIN0
DIN1
DIN2
DIN3
Watchdog Timer
Backlight
Message
VOLT VcoreA Power Supply Error
VOLT VcoreB Power Supply Error
VOLT +3.3 V Power Supply Error
VOLT +5.0 V Power Supply Error
VOLT +12 V Power Supply Error
TEMP System Temperature Error
TEMP CPU Temperature Error
DIN0
DIN1
DIN2
DIN3
Watchdog Timer Error
Backlight Error
35015036 07/2010
123
System Monitoring
Example of displayed screen:
NOTE: You can modify the messages displayed on the popup message from the
System Monitor Property screen.
Error Displays when Using the Event Viewer
The System Log records error type/location and error actions as error events. You can check the error event information using the Event Viewer.
Step
1
2
Action
Start your Smart terminal
Click Start
→ → →
Event Viewer
NOTE: This feature is supported by Windows® XPe.
124
35015036 07/2010
System Monitoring
Error Type/Location and Error Action
The error type/locations shown by the Event Viewer are shown in the table below:
Error type/Location
VcoreA
VcoreB
Voltage +3.3 V
Voltage +5.0 V
Voltage +12 V
Voltage –12 V
System Temperature
CPU Temperature
DIN0
DIN1
DIN2
DIN3
Watchdog Timer
Backlight
Error Message Description
VOLT VcoreA Error has occurred
VOLT VcoreB Error has occurred
VOLT +3.3 V Error has occurred
VOLT +5.0 V Error has occurred
VOLT +12 V Error has occurred
VOLT –12 V Error has occurred
TEMP System Error has occurred
TEMP CPU Error has occurred
DIN0 Error has occurred
DIN1 Error has occurred
DIN2 Error has occurred
DIN3 Error has occurred
Watchdog Timer Error has occurred
Backlight Error has occurred
The actions taken when an error occurs and which are shown by the Event Viewer, are shown in the table below.
Type of Alert
Buzzer
Popup Message
OS Shutdown
DOUT0
DOUT1
DOUT2
DOUT3
Error Message
Buzzer has sounded because of an "xx" error.
Popup message has been shown because of an "xx" error.
Windows® has been shutdown due to an "xx" error.
DOUT0 has output because of "xx" error.
DOUT1 has output because of "xx" error.
DOUT2 has output because of "xx" error.
DOUT3 has output because of "xx" error.
NOTE: z z z
The data shown in the table uses "xx" to indicate the error type/location
The actions taken by the system after an error occurs are set via the System
Monitor Property screen.
When a +3.3 V error occurs and the buzzer sounds, two errors will be displayed by the Event Viewer: +3.3 V Error has occurred and Buzzer has sounded because of a +3.3 V error .
35015036 07/2010
125
System Monitoring
Smart tab interface
The following figure shows an overview of the Smart monitoring screen:
126
The following table gives a description of the operations that can be performed.
Item
Device No.
Model
Status
Operation
Displays the number assigned to the hard disk/SSD/CF card to be monitored
Displays the model of the hard disk/SSD/CF card.
Specifies the item to be monitored. The status of each monitoring item is displayed.
[Pass]: Normal
[Error]: Abnormal
[Disable]: Not monitored
[Not Supported]: Not supported
NOTE: [Not Supported] is displayed when a drive that does not support
SMART monitoring is detected.
35015036 07/2010
35015036 07/2010
Item
SSD/CF
Status
System Monitoring
Operation
Selecting [SSD/CF Status] displays the [SSD/CF Status] dialog box, which allows confirmation of remaining product life.
Remaining product life is calculated according to the number of write operations made to the SSD, and is displayed as a percentage value with one decimal place.
Buzzer Off
Reset
Minimize
NOTE: When remaining life becomes 0.0%, the error set in [Error Action] under [System Monitor Property] is generated.
When the remaining life reaches 0.0%, order from Schneider service the replacement of the SSD unit with a new one.
When [Buzzer] is selected for the error notification method, you can stop the buzzer by clicking [Buzzer Off].
When an error is detected, clicking [Reset] recovers the System Monitor from the “error” status.
NOTE: Ater an error is resolved, make sure to reset. If reset is not performed, the error history remains, which causes the error to be detected again even if it was resolved.
Stores the System Monitor screen in the task tray.
127
System Monitoring
128
35015036 07/2010
Maintenance
35015036 07/2010
Maintenance
11
Subject of this Chapter
This chapter covers maintenance of the Smart 15".
What's in this Chapter?
This chapter contains the following topics:
Reinstallation Procedure
Regular Cleaning and Maintenance
Topic Page
35015036 07/2010
129
Maintenance
Reinstallation Procedure
Introduction
In certain cases, it may be necessary to reinstall the operating system.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH z z z z z
Remove all power from the device before removing any covers or elements of the system, and prior to installing or removing any accessories, hardware, or cables.
Always use a properly rated voltage sensing device to confirm power is off.
Unplug the power cable from both the Smart unit and the power supply.
Replace and secure all covers or elements of the system before applying power to the unit.
Use only the specified voltage when operating the Smart 15". The AC unit is designed to use 100...240 Vac input. The DC unit is designed to use
23 ... 25 Vdc. Always check whether your device is AC or DC powered before applying power
Failure to follow these instructions will result in death or serious injury.
DANGER
CHEMICAL BURNS TO EYES OR SKIN z z z
Do not use tools to operate the touch panel or in the vicinity of the display.
When placing the display face-down, select a clean, level, non-abrasive surface. Place a soft, non-abrasive pad on the surface before lowering the unit upon it.
If a leak in the LCD panel is discovered, and you come in contact with the liquid crystal material, follow these procedures: z In the case of contact with eyes or mouth, flush with running water for 15 z minutes minimum.
In the case of contact with skin or clothing, wipe off the liquid crystal material z and wash soap and running water for 15 minutes
If liquid crystal is ingested, induce vomiting, rinse mouth, and then drink a z large quantity of water.
Follow any other hazardous substances safety procedures required by your facility.
Failure to follow these instructions will result in death or serious injury.
130
35015036 07/2010
35015036 07/2010
Maintenance
DANGER
EXPLOSION HAZARD z z
Always confirm the UL 1604, ANSI/ISA 12.12.01 or CSA C22.2 N ° 213 hazardous location rating of your device before installing or using it in a hazardous location.
To apply or remove the supply power from a Smart 15’’ device installed in a
Class I, Division 2 hazardous location, you must either: z Use a switch located outside the hazardous environment, or; z Use a switch certified for Class I, Division 1 operation inside the hazardous area.
z z z z
Do not connect or disconnect any cables or wires while the circuit is live unless the area is known to be free of ignitable concentrations of vapors, gases, and other flammable or combustible materials. This applies to all connections including power, ground, serial, parallel, and network connections.
Never use unshielded/ungrounded cables in hazardous locations.
Use only non-incendiary USB devices
.
When enclosed, keep enclosure doors and openings closed at all times to avoid the accumulation of foreign matter inside the workstation.
Failure to follow these instructions will result in death or serious injury.
CAUTION
OVERTORQUE AND LOOSE HARDWARE z z
Do not exert more than 0.6 N•m (5.3 lb-in) of torque when tightening the installation fastener, enclosure, accessory, or terminal block screws. Tightening the screws with excessive force can damage the plastic casing of the Smart 15".
When installing or removing screws, ensure that they do not fall inside the
Smart 15" unit's chassis.
Failure to follow these instructions can result in injury or equipment damage.
CAUTION
STATIC SENSITIVE COMPONENTS
Smart 15" internal components, including accessories such as RAM modules and expansion boards, can be damaged by static electricity. Observe the electrostatic precautions below when handling such components.
Failure to follow these instructions can result in injury or equipment damage.
131
Maintenance
Before Reinstallation
Hardware required: z z
Reinstallation CD-ROM
A computer running Windows 2000/XP able to read "Compact Flash Memory" and having a CD-ROM drive.
Optimal configuration: Standard computer with PCMCIA slot (Notebook for example) and "Compact Flash" to PCMCIA adaptor.
Possible configuration: Computer and "Compact Flash reader" on USB port.
Setting up the hardware: z z z
Shut down Windows® in an orderly fashion and remove all power from the device. Then, follow the applicable instructions in Removing the Smart’s unit covert
.
Remove all PCMCIA extension boards.
Disconnect all external peripherals.
NOTE: Save all important data on the hard drive or Compact Flash card (the reinstallation process erases all data on them). The reinstallation process will return the computer to its factory settings.
Reinstallation
Precautions to be taken: z z z z
Keep static-producing materials (plastic, upholstery, carpeting) out of the immediate work area.
Do not remove ESD-sensitive components from their anti-static bags until you are ready to install them.
When handling static-sensitive components, wear a properly grounded wrist strap (or equivalent).
Avoid unnecessary contact with exposed conductors and component leads with skin or clothing.
Refer to the relevant procedure in the Installation Guide.
132
35015036 07/2010
Maintenance
Regular Cleaning and Maintenance
Cleaning Solutions
CAUTION
HARMFUL CLEANING SOLUTIONS z z
Do not clean the unit or any component of the unit with paint thinner, organic solvents, or strong acids.
Use only a mild soap or detergent that will not harm the polycarbonate material of the screen.
Failure to follow these instructions can result in injury or equipment damage.
Installing a Replacement Gasket
Installation Gasket
Use of the installation gasket may help extend the operating life of your Smart. The gasket is required to meet the protection ratings (IP65, NEMA4, IP20) of the unit and provides additional protection from vibration. Even if moisture protection is not required, install the gasket delivered with your Magelis product.
CAUTION
LOSS OF SEAL z z z z z z
Inspect the installation gasket prior to installation or reinstallation, and periodically as required by your operating environment.
Replace the gasket if visible scratches, tears, dirt, or excessive wear are noted during inspection.
Do not stretch the gasket unnecessarily or allow the gasket to contact the corners or edges of the frame.
Ensure that the gasket is fully seated in the installation groove.
Install the Smart into a panel that is flat and free of scratches or dents.
Tighten the installation fasteners using a torque of 0.5 N•m (4.5 lb-in).
Failure to follow these instructions can result in injury or equipment damage.
The corresponding gasket is provided in the maintenance kit ref: MPC YK 50 MNT
KIT.
35015036 07/2010
133
Maintenance
Installation Fasteners
CAUTION
OVERTORQUE AND LOOSE HARDWARE z z
Do not exert more than 0.6 N•m (5.3 lb-in) of torque when tightening the installation fastener, enclosure, accessory, or terminal block screws. Tightening the screws with excessive force can damage the plastic casing of the Smart 15".
When installing or removing screws, ensure that they do not fall inside the
Smart 15" unit's chassis.
Failure to follow these instructions can result in injury or equipment damage.
NOTE: The screw installation fasteners are required for NEMA4 protection.
The following procedure describes how to replace the installation gasket.
Step
1
2
3
4
Action
Shut down Windows® in an orderly fashion, remove all power from the device.
Place the unit on a clean, level surface with the display facing downwards. Place a soft, non-abrasive pad on the surface before placing the unit upon it.
Remove the gasket from the unit.
Attach the new gasket ensuring that the gasket’s grooved sides are vertical.
Ensure that the gasket’s seam is not inserted into any of the corners of the unit as this may lead to tearing of the gasket.
134
35015036 07/2010
Maintenance
Step
5
Action
Check that the gasket is correctly attached to the unit. The upper surface of the gasket should evenly protrude approximately 2 mm (0.08 in) out of the groove.
6 Replace the Smart unit on its mounting and reconnect the power.
Lithium Battery
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read and understand the safety information in the Reinstallation procedure
before attempting this procedure.
Failure to follow these instructions will result in death or serious injury.
DANGER
EXPLOSION, FIRE, OR CHEMICAL HAZARD z z z z
Follow these instructions for the Lithium batteries:
Do not recharge, disassemble, heat above 100 ° C (212 ° F), or incinerate.
Recycle or properly dispose of used batteries.
Replace with identical type.
Follow all battery manufacturer’s instructions
Failure to follow these instructions will result in death or serious injury.
The terminal contains one battery, which is used to save certain system data such as the date and time.
35015036 07/2010
135
Maintenance
Battery Replacement
The following tables gives the Battery replacement procedure:
Step
1
2
3
Action
Shut down Windows in an orderly fashion, remove all power from the device.
Remove the Smart unit from its mounting, place it on a flat level surface with the display facing downwards, and follow the procedure to remove the Smart’s unit cover Removing the Smart’s Unit cover
.
Remove the battery which is in the location shown below:
136
4 Push the clip of the battery holder and the battery is pushed up and removed.
5 Insert the battery in the side of the clip of the battery holder first with the plus (+) pole facing upward.
6
7
Push the battery from above until you hear the click to fit it in the battery holder.
Replace the Smart’s unit cover.
Replace the Smart unit on its mounting and reconnect the power.
35015036 07/2010
Maintenance
Periodic Inspection
Be sure to inspect the Smart periodically to determine its general condition. For example: z z z z
Are all power cords and cables connected properly? Have any become loose?
Are all mounting brackets holding the unit securely?
Is the ambient temperature within the specified range?
Are there any scratches or traces of dirt on the installation gasket?
35015036 07/2010
137
Maintenance
138
35015036 07/2010
Troubleshooting
35015036 07/2010
Troubleshooting
12
Troubleshooting
Troubleshooting Checklist
This section explains how to find and resolve troubleshooting items with the Smart unit.
The Smart can be connected to a wide range of devices, including a host (PLC), however, this manual will not discuss every possible device or condition. For problems not directly related to the Smart unit, refer to that device’s manual.
The most likely items for troubleshooting that can occur during usage of the Smart are: z z z
The Touch Panel display is blank
The Touch Panel does not respond
Connected devices cannot be used.
When one occurs, be sure to first read each checklist item and follow the instructions given. If this does not solve the problem, please contact your local Smart distributor.
When a hardware or software issue occurs that you cannot resolve, please contact the distributor where you purchased the Smart unit.
139
35015036 07/2010
Troubleshooting
No Display
Step Check Item or Operation Check Result
1 Switch OFF the Smart power supply.
2
3
4
Is the power cord connected correctly?
Is the power supply voltage within specification?
Switch ON the power supply.
5 Does the ON LED illuminate in green?
6
–
Does the Windows® operating system work normally?
Has the issue been resolved?
Action Required
Connect the power cord correctly.
Please refer to Power supply
Power indicator does not light up or is orange/red blinking and you have no screen operation, contact the distributor where the Smart was purchased.
If a white screen is displayed and
Windows® does not work at all, please contact the distributor where the Smart was purchased.
If not, please contact the distributor where the Smart was purchased.
Touch Panel does not Respond
Step Check Item or Operation Check
Result
1 Has the Touch Panel been calibrated?
– Has the issue been resolved?
Action Required
Calibrate the Touch Panel (See the procedure "Touch Panel Calibration" given below). If the Touch Panel cannot be calibrated, please contact the distributor where the Smart was purchased.
If not, please contact the distributor where the Smart was purchased.
140
35015036 07/2010
Troubleshooting
Touch Panel Calibration
You have two possible procedures to calibrate the Touch Panel.
First procedure:
Step
1
Actions for procedure 1
Click on the Touch Panel icon. Select ‘Calibration’, then ‘Device 1’.
35015036 07/2010
2 An arrow appears in the upper left corner of the Touch Panel: touch the red point with your finger. Do the same for the four corners.
3 In order to validate the calibration, click on OK in the following window:
141
Troubleshooting
Second procedure:
Step
1
2
Actions for procedure 2
Open the ‘Control panel’ window.
Click on the ‘Pointer Devices’ icon.
3 In the following window, click on ‘Calibrate’ (bottom left):
Connected Devices cannot be Used
4
5
Step Check Item or Operation Check Result Action Required
1 Switch OFF the Smart power supply.
2 Connect the power cord correctly.
3
Is the power cord connected correctly?
Are the peripheral devices connected correctly?
Switch ON the Smart power supply.
Follow the instructions described in the respective manual.
–
Does this device require driver setup?
Has the issue been resolved?
Refer to the device’s manual and setup the driver.
If not, please contact the distributor where the Smart was purchased.
Recovery
4 Then follow steps 2 and 3 of the previous table.
Please refer to the Reinstallation Procedure
142
35015036 07/2010
Appendices
35015036 07/2010
Appendices
IV
35015036 07/2010
143
Appendices
144
35015036 07/2010
Accessories
35015036 07/2010
Accessories
13
Accessories for the Smart 15"
List
Accessories are available as options. The list of accessories available for the Smart
15" is shown below:
Description
Maintenance Kit including installation fasteners, installation screws and gasket
Reference
MPC YK50 MNT KIT
35015036 07/2010
145
Accessories
146
35015036 07/2010
Index
35015036 07/2010
Index
A
Accessing the BIOS,
Accessories for the Smart 15",
B
Backup of the CF Card Data, 98
Before Modifications,
C
Characteristics,
Characteristics of the Smart 15",
Cleaning and Maintenance,
Compact Flash (CF) Card Installation and
Removal,
Connecting the AC Power Cord,
Connecting the DC Power Cord, 73
Connection to PLCs,
Cables and Converters,
Traditional Architectures, 106
Transparent Ready Architectures,
Control Drawing of the USB outlet on the
Magelis iPC,
D
Dimensions of the Smart Unit,
Dimensions with Installation Fasteners,
35015036 07/2010
A C
E
Environmental Characteristics,
Exit BIOS saving the Modifications,
Exit BIOS Without Saving Modifications, 84
F
First Power-up,
Flash Disk Characteristics,
G
Grounding,
H
Hazardous Location Installations - For USA
147
Index
I
Installation Location,
Installing a Replacement Gasket,
Installing a Type I or Type II PCMCIA Card,
Installing a Type III PCMCIA Card,
Installing the Smart Unit,
L
M
O
P
Package Contents,
Panel Cut Dimensions,
Power Supply,
Preparing to Install the 15" Smart,
Preparing to use a CF Card, 96
Primary Master,
Product Characteristics,
R
148
S
Shared Ground - Avoid Ground Loop, 69
Shared Ground Allowed,
Shared Ground not Allowed , 69
Smart 15" Unit Description, 32
System Date,
System Monitor
access,
configuration,
access,
interface,
System Monitor Property,
U
USB Cable Clamp Attachment,
USB Cable Clamp Attachment/Removal,
V
35015036 07/2010