Magelis Smart iPC
Industrial PCs
User Manual
eng November 2004
2
Table of Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Part I
General overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Chapter 1
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Chapter 2
Physical overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Chapter 3
Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Part II
Implementation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Chapter 4
Main Power Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Chapter 5
Getting started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Chapter 6
Hardware extensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
3
4
Chapter 7
Configuration of the Bios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Chapter 8
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Part III
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Chapter 9
Dimension/Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Chapter 10
Connections to PLCs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Part IV
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Chapter 11
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Safety Information
§
General safety information for users
General
Personnel qualifications
The present documentation is aimed at qualified technical personnel responsible for the implementation, operation and maintenance of the products described. It contains the information necessary for compliance with the proper use of the products. However, those who wish to make more "advanced" use of our products may find it necessary to consult our nearest distributor in order to obtain additional information.
The contents of this documentation are not contractual, and in no way constitutes an extension to, or restriction of, the contractual warranty clauses.
Only qualified personnel are authorized to implement, operate or maintain the products. The interference of non-qualified persons or failure to observe the security instructions contained in this manual, or attached to the devices, can endanger the personnel and/or do irreparable damage to the equipment. The following persons can be designated as " qualified personnel ": l l at application design level, engineering department personnel who are familiar with automation safety concepts (for example, a design engineer), at equipment implementation level, personnel who are familiar with the installation, connection and commissioning of automation equipment (for example, an installation assembly or cabling engineer, or a commissioning technician), l l at operation level, personnel who are experienced in the use and control of automation and computing equipment (for example, an operator), as far as preventive or corrective maintenance is concerned, persons trained and qualified in regulating or repairing automatic and computing devices (for example an operating technician, or an after-sales service technician, etc.).
5
Safety Information
Switching off
Compliance of use
Control software such as is typically used on Industrial PCs permits various users to be given different rights. A user who may not close software may also not switch the
Industrial PC off, since data can be lost from the hard disk by switching off while software is running.
If the Industrial PC is switched off as the software is writing a file to the hard disk, the file can be destroyed. Control software typically writes datas to the hard disk every few seconds, so that the probability of causing damage by switching off while the software is running is very high.
To avoid that please respect the instructions of the operation system for closing the softwares and switching off the Industrial PC.
The products described in the present documentation comply with the European
Directives* to which they are subject (EC marking). However, these can only be used correctly if in applications for which they are specifically intended, as specified in the relevant documentation, and in connection with approved third-party products.
As a general rule, correct usage of the products, with no danger to personnel or hardware, consists of complying with all handling, transport and storage recommendations, and all installation, operation and maintenance instructions.
* EMCD and LVD directives concerning Electromagnetic Compatibility and Low
Voltage.
Replacement and recycling of used batteries
Replace batteries with those of the same type, and dispose of any defective batteries in the same way as toxic waste.
Lithium or mercury batteries must not be thrown into a fire, opened, recharged or welded.
Lithium battery The terminal contains a lithium battery, which is used to save certain data such as the date and time.
This must only be replaced by a qualified technician.
WARNING
Non-compliance with this warning may lead to a risk of explosion!
Failure to follow this precaution can result in death, serious injury, or equipment damage.
6
Safety Information
Federal
Communications
Commission
Radio Frequency
Interference
Statement - For
U.S.A.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by l l l turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
l Consult the Support Service Center or an experienced radio/TV technician for help.
WARNING
To assure continued compliance, use only shielded interface cables when connecting to a computer or peripheral. Also, any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this equipment.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: l This device may not cause harmful interference received, including interference that may cause undesired operation.
l This device must accept any interference received, including interference that may cause undesired operation.
Failure to follow this precaution can result in death, serious injury, or equipment damage.
7
Safety Information
Safety Warnings
- For U.K.
WARNING
This apparatus must be earthed for your safety.
To ensure safe operation the three-pin plug must be inserted only into a standard three-pin power point, which is effectively earthed through the normal household wiring.
Extension cords used with the equipment must be three-core and be correctly wired to provide connection to earth. Wrongly wired extension cords are a major cause of fatalities.
The fact that the equipment operates satisfactorily does not imply that the power point is earthed and that the installation is completely safe.
For your safety, if you have any doubt about the effective earthing of the power point, consult a qualified electrician.
Failure to follow this precaution can result in death, serious injury, or equipment damage.
8
Safety Information
WARNING
THIS APPLIANCE MUST BE EARTHED
Important
The wires in this mains lead are coloured in accordance with the following code: l l l
Green-and-yellow: Earth
Blue: Neutral
Brown: Live
As the colours of the wires in the mains lead of this apparatus may not correspond with the coloured markings identifying the terminals in your plug, proceed as follows:
The wire which is coloured GREEN-and-YELLOW must be connected to the terminal in the plug which is marked by the letter E or by the safety earth symbols coloured GREEN or GREEN-and-YELLOW.
The wire which is coloured Blue must be connected to the terminal which is marked with the letter N or coloured BLACK.
The wire which is coloured Brown must be connected to the terminal which is marked with the letter L or coloured RED.
The mains plug on this equipment must be used to disconnect the mains power.
Please ensure that a socket outlet is available near the equipment and is easily accessible.
Failure to follow this precaution can result in death, serious injury, or equipment damage.
9
Safety Information
WARNING l l
This equipment is not designed for connection to an IT power system:
An IT system is a system having no direct connections between live parts and Earth; the exposed conductive parts of the electrical installation are earthed.
An IT system is not permitted where the computer is directly connected to public supply systems in the UK.
Disconnect the mains plug from the supply socket when the computer is not in use.
Failure to follow this precaution can result in death, serious injury, or equipment damage.
Warnung Für
Deutschland
Warnung bezüglich der Lithiumbatterie (Sicherungsbatterie)
Lithiumbatterie
Dieser Computer enthält eine Lithiumbatterie zur Sicherung von Datum und Uhrzeit der eingebauten Uhr sowie anderer Systemdaten im Speicher bei einer
Unterbrechung der Hauptstromversorgung. Diese Sicherungsbatterie darf nur von
Kundendienstpersonal ausgewechselt werden.
Warnung! Bei falschem Gebrauch besteht Explosionsgefahr!
Entsorgung gebrauchter Batterien nach Angaben des Herstellers.
10
Safety Information
Hazardous Location Installations - for USA and Canada
General Schneider Automation designed the systems with the intention of meeting the requirements of Class 1, Division 2 hazardous location applications. Division 2 locations are those locations that are normally non-hazardous, but potentially hazardous should an accident expose the area to flammable vapors, gases or combustible dusts.
These systems are non-incendiary devices. They are not intrinsically safe and should never be operated within a Division 1 (normally hazardous) location when installed as described here. Nor should any peripheral interface device attached to these systems be located within Division 1 locations unless approved and/or certified diode barriers are placed in series with each individual signal and DC power line. Any such installations are beyond the bounds of Schneider Automation design intent. Schneider Automation accepts no responsibility for installations of this equipment or any devices attached to this equipment in Division 1 locations.
It is mandatory to install the Hazardous Location.
Warning
For AC version equipment only: the power switch is in arcing device. It should be switched to the ON position and the corresponding retainer bracket for the Control Box should be attached according to the Hazardous Location Kit service instruction
Only technically qualified service personnel should perform installation and service.
These workstations are designed to require no service in the course of normal operation by an operator.
Warning
It is the user's responsibility in case of maintenance or repair of any subassembly to verify that the exchanged or repaired module is labelled as a Class I Division 2 hazardous location.
It is the responsibility of the customer to ensure that the product is properly rated for the location. If the intended location does not presently have a Class, Division and
Group rating, then users should consult the appropriate authorities having jurisdiction in order to determine the correct rating for that hazardous location.
11
Safety Information
In accordance with Federal, State/Provincial, and Local regulations, all hazardous location installations should be inspected prior to use by the appropriate authority having jurisdiction. Only technically qualified personnel should install, service, and inspect these systems.
Warning
Suitable for use in Class I, Division 2 Groups A, B, C, and D, hazardous locations or non-hazardous locations only.
Warning - Explosion Hazard
Substitution of components may impair suitability for Class I, Division 2.
Warning
For a use in hazardous locations, the PCI or ISA controller cards shall be found in category NWHP2, provided that they are suitable for Class I,
Division 2, Goups A, B, C ,and D; T-code:T4A, and suitable for an ambient temperature range of +0°C to +50°C.
Warning - Explosion Hazard
Do not connect or disconnect equipment unless the power has been switched off or the area is known to be non-hazardous.
Warning
Power wiring must be in accordance with the National Electrical Code article 501.4(B) for Class I, Division 2.
12
Definition
Safety Information
Warning - Explosion Hazard
When in hazardous locations, turn off power before replacing or wiring modules.
Warning - Explosion Hazard
Do not connect or disconnect the output ports such as PS2/USB/
Communication cable/Video connectors, when the unit is in a Hazardous
Location area
The following Class and Division explanations are derived from Article 500 (Sections
5 and 6) of the United States National Fire Protection Agency National Electric Code
(NFPA 70, 1990). They are not complete and are included here only for a general description for those not familiar with generic hazardous locations requirements.
Persons responsible for the installation of this equipment in hazardous locations are responsible for ensuring that all relevant codes and regulations related to location rating, enclosure, and wiring are met.
Class I Locations
Class I locations are those in which flammable gases or vapors are or may be present in the air in quantities sufficient to produce explosive or ignitable mixtures.
Class II Locations
Class II locations are those that are, or may become, hazardous because of the presence of combustible dust.
Division 1 Locations
A Division 1 location is one in which flammable or ignitable gases, vapors or l l combustible dusts and particles can exist due the following conditions:
Normal operating conditions.
Due to repair, maintenance conditions, leakage, or where mechanical failure or abnormal operation of machinery or equipment might release or cause explosive or ignitable mixtures to be released or produced.
l Combustible dusts of an electrically conductive nature may be present in hazardous quantities.
13
Safety Information
Note
Schneider Automation MPC••• systems are not suitable for installation within Class II Division 2 and Class 1 Division 1 locations.
Note
Electrical equipment cannot be installed in Division 1 locations unless they are intrinsically safe, installed inside approved explosion-proof enclosures, or installed inside approved purged and pressurized enclosures.
l l
Division 2 Locations l Class I volatile flammable liquids or flammable gases are handled, processed or used, but confined within closed containers or closed systems from which they can escape only in cases of accidental rupture or breakdown of such enclosures l or systems, or in case of abnormal operation of equipment.
Ignitable concentrations of Class I vapors or gases are normally prevented by positive mechanical ventilation, but may become hazardous due to mechanical failure of those ventilation systems.
Location is adjacent to a Division 1 location.
Class II combustible dust is not normally in the air in quantities sufficient to produce explosive or ignitable mixtures. Dust accumulations are normally insufficient to interfere with normal operation of electrical equipment or other apparatus. Combustible dust may be in suspension in the air as a result of the following: infrequent malfunctioning of handling or processing equipment; combustible dust accumulations on, or in the vicinity of, electrical equipment; may be ignitable by abnormal operation or failure of electrical equipment.
Groups
All electrical equipment that is approved for use in hazardous locations must include a group rating. Various flammable and combustible substances are divided into these groups as a function of their individual maximum experimental safe gap
(MESG), explosion pressure, and ignition temperature. Component temperatures and the potential for spark based upon voltage, current and circuit characteristics of electrical equipment will determine what the equipment group rating will be. A device approved for installation within Class I, Group A locations may also be used in
Groups B, C, or D.
14
Safety Information
Note
Approved Class I equipment may not be suitable for Class II installations.
Class I includes Groups A, B, C, and D. Class II includes Groups F, and G.
Power Switch
Cable connections
The amount of input power required by these systems classifies a power switch as an incendiary device because the voltage and current across the make/break device are capable of creating a spark.
Hazardous location regulations require that a power switch rated for ordinary locations may be used if it is located in an area specified as non-hazardous.
However, limits in cable length between the workstation and the power switch may apply. Otherwise the switch must be compliant with Class I, Division 1 requirements
(intrinsically safe). These switches are built in a manner that prevents the possibility of a spark when contacts are made or broken.
Use suitable UL listed and/or CSA Certified Class I, Division 1 switches in hazardous locations. These switches are available from a wide number of sources. It is the responsibility of the customer to ensure that the power switch selected for the installation has the correct hazardous locations rating for the location in which it is installed.
Division 2 hazardous location regulations require that all cable connections be provided with adequate strain relief and positive interlock. USB connections can never be used in hazardous location installations, because USB connectors do not provide adequate strain relief. Never connect or disconnect a cable while power is applied at either end of the cable. All communication cables should include a chassis ground shield. This shield should include both copper braid and aluminum foil. The
D-sub style connector housing should be a metal conductive type (e.g., molded zinc) and the ground shield braid should be well terminated directly to the connector housing. Do not use a shield drain wire.
The outer diameter of the cable must be suited to the inner diameter of the cable connector strain relief in order to ensure that a reliable degree of strain relief is maintained. Always secure the D-Sub connectors to the workstation-mating connectors via the two screws located on both sides.
Warning
Never connect or disconnect the communication cables while power is applied at either end of the cable. This may result in an incendiary spark.
Permanent damage to the workstation communication components may occur.
15
Safety Information
Operation and
Maintenance
Safety Agency
Approval
The systems have been designed for compliance with relevant spark ignition tests.
However, please note that the workstation front panel keypad switches and PS/2 connector are the only make/break components intended to be exercised by the operator in the course of normal operation.
Always observe the following rules with respect to hazardous location installations: l l l
Always install the workstations within an enclosure suitable for the specific application. General-purpose enclosures may be acceptable for Class I applications but are never acceptable for Class II applications. Type 4 (IP 65) enclosures are recommended even when not required by regulations.
If present, keep enclosure doors or openings closed at all times, to avoid the accumulation of foreign matter inside the workstation.
Never subject the unit to any installation or service procedures unless power is removed and the area is known to be non-hazardous. This includes the installation or removal of power cables, communication cables, or removal of the rear cover of the unit.
The Schneider Automation systems are designed to meet the following standards: l l l l l
Underwriters Laboratories Inc., UL 1604 Standard for Safety Electrical equipment for use in Class I Division 2 locations
Underwriters Laboratories Inc., UL 60950, Information Technology Equipment
Canadian Standard Association, Specification C22.2 No. 213-M1987
Non incendiary electrical equipment for use in Class I, Division 2 hazardous locations.
Canadian Standards Association, Specification C22.2 No. 950 Information
Technology Equipment
EN 60950, Information Technology Equipment
16
About the Book
At a Glance
Document Scope This manual describes the installation of the Magelis Smart iPC of industrial PCs.
Related
Documents
Title of Documentation
Magelis Smart and Compact iPC installation guide
Reference Number
35008589
User Comments We welcome your comments about this document. You can reach us by e-mail at [email protected]
17
About the Book
18
General overview
I
At a Glance
Subject of this part
What's in this
Part?
This part provides an overview of the Magelis Smart iPC products.
This part contains the following chapters:
Chapter
1
2
3
Chapter Name
Introduction
Physical overview
Characteristics
Page
19
General overview
20
Introduction
1
Introduction
Thank you
At a Glance
Congratulations!
Thank you for having purchased an industrial computer from the Magelis Smart iPC range.
This computer, designed to operate in an industrial environment, features the very latest technologies.
Magelis Smart iPC computers is a panel PC product working with 24VDC industrial voltage.
The Smart iPC runs Microsoft Windows® embeded operating system and is dedicated to web browsing application.
The reference of the product is : l Reference: MPC ST52 ••• •••
The characteristics are detailed in chapter 3.
21
Introduction
22
Physical overview
2
At a Glance
Subject of this chapter
What's in this
Chapter?
This chapter provides physical overviews of the products.
This chapter contains the following topics:
Topic
Package Contents
Smart iPC Unit description
Page
23
Physical overview
Package Contents
Items The following items are included in the Smart Magelis iPC package. Before using the unit, please confirm that all items listed here are present.
Designation
MPC ST52 ••• ••
Figure
Installation Fasteners (4/set x 2)
Installation Guide
CF Card
CD-ROM
OS restore and bundled softwares
24
Physical overview
Smart iPC Unit description
Features
View
Front
FIgure
Rear
1
4
2
3
Legend
1 : Display / Touch Panel
2 : Power Lamp LED (POWER)
LED
Green
Orange
Orange/Red
Status
Normal Operation
(Power On)
System Monitor Error
Touch Panel
Self Test Error
Backlight is not functionning
3 : IDE Access Lamp
LED
Green
Status
Normal Operation
4 : Fan
25
Physical overview
View FIgure
Left Side
5
6
Legend
5 : PCMCIA Interface
6 : Ethernet Interface
10 Base-T / 100 BASE-TX
Auto Changeover
Top
7
7 : Rear Cover
This cover is removed when
installing a main memory
Bottom
8
9
10
11
12
13
14 15
8 : Keyboard Connector (KEYBOARD)
Connect a PS/2-compatible
keyboard
9 : USB Interface (2 ports)
Provides a USB 1.1 compatible
connection. Connect a USB
connectable device here.
10 : Serial Interface (COM1)
11 : Serial Interface (COM2)
12 : Speaker Output Connector
(SPEAKER OUT)
13 : Printer Connector (LPT1)
14 : CF Card Interface Cover
15 : Power Input Terminal Block
26
Characteristics
At a Glance
Subject of this chapter
What's in this
Chapter?
This chapter gives the product characteristics.
This chapter contains the following topics:
Topic
Characteristics of the Smart iPC
Environment characteristics
3
Page
27
Characteristics
Characteristics of the Smart iPC
Introduction
CPU characteristics
The different characteristics of the Smart iPC model are given below.
Element
Processor
RAM
Video processor
Ethernet TCP/IP link
PS/2 ports
USB ports
COM 1 serial port
COM 2 serial port
Parallel port
Extension card slot
PCMCIA slot
Audio port
Dimensions (WxHxD)
Weight
Characteristics
VIA 667 MHz, secondary memory cache 512 KB
DIMM Socket 1: 256 MB / 512 MB (max 512 MB)
VIA Twister-T with 32 Mb ram UMA type
1 x 10/100base TX (RJ45 interface)
1 keyboard interface
2 x USB 1.1
RS232C
RS232C
1 bi-directional link
1 PCI 2.2 interface slot
2 ports Type 2 on side
Speaker out in standard jack interface)
395 mm x 294 mm x 60 mm
6.0 Kg
Display characteristics
Element
Graphics
Nb of colors
Brightness
Characteristics
XGA active matrix (1024x768 dots), VESA max. 64 K colors
260 K colors
250 cd/m (typical value, adjust through Windows® 4 steps)
View angle Vertical 140°, horizontal 160° maximum
Touch sensitive screen Analog resistive film, resolution 1024x1024, USB interface
Backlight's life span >50 000h at ambiant temperature 25 °C
28
Power supply
Operating systems
Characteristics
Element
Supply voltage
Consumption
Short dips
Characteristics
24 V DC (range 18...36 V DC)
90 W
1 ms
The products are delivered with a Compact Flash card pre-installed operating system according the reference ordered.
The products work with the operating system Microsoft Windows XP embeded.
Reference Characteristics
MPC ST52 NDJ 00T Smart iPC with display 15" XGA Touch Screen, 24 V DC supply,
Compact Flash with Windows Embedded XP pre-installed
29
Characteristics
Environment characteristics
General The environment characteristics given below are applicable to the products.
Characteristics
Characteristics
Degree of Protection
The environment characteristics are as follows:
Operating temperature
Storage temperature
Value l l
IP 65/NEMA4 for the front panel.
IP 20 for the rest of the product
0 °C to 50 °C
-20 °C to 60 °C
Standards
-
Operating altitude
Storage altitude
Vibration
(in operation)
Shock Resistance
(in operation)
Hygrometry
Immunity to interference
0 to 3000 m maximum
0 to 12000 m maximum
3,5mm amplitude from 5 to 9 Hz,
1 g amplitude from 9 to 150 Hz
15 g over 11 ms
10 - 90%
High frequency interference
Electromagnetic waves
Safety of personnel and property
EN 61131-2, UL compliant
IEC 68-2-2 tests Bb and Ab,
IEC 68-2-14 tests Na and EN 61131-2 compliant
-
-
IEC 68-2-6 Fc test and EN 61131-2 compliant
IEC 68-2-27 Ea test and EN 61131-2 compliant
-
EN 61131, IEC 1000-4-3/6 level 3
Class A/EN 55022/55011
EN 61131-2, UL/CSA and IEC 529/IEC 950
Certification The products have been developed to comply with the following standards: l l l l l l
UL 508
IEC/EN 60950
EN 55022
IEC/EN 61131-2
CUL
Classification in hazardous areas CLASS 1 - Division 2 - UL1604
30
Implementation
II
At a Glance
Subject of this part
What's in this
Part?
This part concerns the implementation of products.
This part contains the following chapters:
Chapter
4
5
6
7
8
Chapter Name
Main Power Connection
Getting started
Hardware extensions
Configuration of the Bios
Maintenance
Page
31
Implementation
32
Main Power Connection
4
At a Glance
Subject of this chapter
What's in this
Chapter?
This chapter concerns the connection of the products to the main power.
This chapter contains the following topics:
Topic
Connecting the Power Wires
Grounding Cautions
Connecting I/O Signal Lines
Page
33
Main Power Connection
Connecting the Power Wires
Precautions
WARNING
To avoid the dangers of fire, electric hazards and equipment damage, be sure to use only the specified voltage when operating the Smart iPC.
Since the unit has no power ON/OFF switch, be sure to attach a breaker-type switch to its power cord.
Failure to follow this precaution can result in death, serious injury, or equipment damage.
Important :
• When the FG terminal is connected, be sure the wire is grounded. Not grounding the Magelis Smart iPC unit will result in excess noise.
Note :
• Whenever possible, use thick wire (max. 2mm
2
) length limited to 30 metres (60 meters round trip) or length limited to 20 meters (40 meters round trip with 1,5mm section copper wires), for Magelis Smart iPC power wires. Also, to reduce noise be sure to twist the wire ends.
34
Terminal Block
Description
The figure below presents how to wire the Terminal Block
Terminal
Screw
Main Power Connection
Wire
Opening
Bottom of
Power Input
Terminal Block
+ : Positive electrode
- : Negative electrode
Ground Terminal connected to the
Smart iPC chassis
Power Cord
Note :
• The torque required to tighten these screw is 0.5 to 0.6N•m.
• Do not solder the wire itself.
• If the central wire’s end strands are not twisted correctly, the end strands may either short against each other, or against an electrode.
• Protection fuse : The 24 VDC mains supply modules for the Smart iPC are fitted with a protection fuse as standard. This fuse, fitted in series with the 24 V DC input, is located inside the module but cannot be accessed.
How to Wire the
Terminal Block
When connecting the wires, be sure to follow the procedures given below.
Step
1
2
3
4
Action
Confirm that the power cable is disconnected from the power supply.
Loosen the screws from the middle three (3) terminals.
Remove the wire’s external covering and insert the wire center stand into the opening.
Re-attach the screws.
35
Main Power Connection
Possible connections
Connection of a Smart iPC supplied by a non-grounded safety DC network :
The 0V and mechanical ground are connected internally.
Specific connection measures are to be taken for specific applications that use a floating network installation. These depending on the chosen mode of installation.
For this, the 24V DC input of the Smart iPC supply is isolated from the outputs and mechanical ground : l l
Primary/Secondary dielectric strength: 1000V AC
Primary/Ground dielectric strength: 1000V AC
Connection of a 24V DC Smart iPC using a floating direct current network :
Circuit diagram
Low voltage
AC network
Smart iPC
Battery charger
+
-
+
-
Battery
Isolation controller
+
-
Floating 24 V DC network
+24 V
-0 V
36
Main Power Connection
Connection of a 24V DC Smart iPC using a ground referenced network :
100-240 V AC network
KM
+24
V DC
Smart iPC
Q : General isolator
KM : Line contactor or circuit breaker
(1) : Isolation strip for detecting grounding faults
(2) : Possiblity of using a TSX SUP 1101 process supply (see Schneider automation product catalog).
37
Main Power Connection
Grounding Cautions
Overview
Dedicated
Ground
Note : Use a grounding resistance of 100 Ω or less, and a 2 mm
2
or thicker wire, or your country’s applicable standard. For details, contact your local distributor.
l Set up a dedicated ground when using the rear panel’s FG terminal.
Smart iPC
Other
Device
Shared Ground allowed l l
If a dedicated ground is not possible, use a shared ground, as shown in figure.
Inside the Smart iPC unit, the SG (Signal Ground) and FG (Frame Ground) terminals are connected to each other.
Smart iPC
Other
Device
Shared Ground not allowed l l
When connecting an external device to Smart iPC with the SG terminal, ensure that no short-circuit loop is created when you set up the system.
The grounding point must be as close to the Smart iPC as possible, and the grounding wires must be as short as possible. If the wires must be long, use thick, insulated wires and run them through conduits.
Smart iPC
Other
Device
38
Main Power Connection
Connecting I/O Signal Lines
Precautions l I/O signal lines must be wired separately from the power circuit cable. If the power circuit cable needs to be wired together with the input/output (I/O) signal lines for any reason, use shielded cables and ground one end of the shield to the
Smart iPC’s FG terminal.
39
Main Power Connection
40
Getting started
5
First power-up
Warning
Note: Before the first power-up, please read the "LIMITED USE LICENSE
AGREEMENT" carefully, then remove the seal.
Preparation On first power-up, it is necessary, depending on the software configuration of your
MPC••, to perform the following operations: l l
You need to enter the licence number of the operating system. For this action, you need to connect a PS/2 or USB keyboard to the unit.
You need to customize and parameter your system or see Installation Guide for
Magelis iPC industrial PC.
41
Getting started
Some useful tools
You can notice in the taskbar some useful shortcuts.
Start l This is the virtual keyboard. Just click on it, and a graphical keyboard appears. It is useful when you don’t want or can’t connect a keyboard to the unit.
l This is the virtual mouse button selector. It allows the user to associate the next
"click" to a "right click". For instance, this tool permits the use of contextual menus.
Backlight
Brightness l Configuration Panel / Brightness : This link allows the user to change the brightness of the screen (useful for dark areas).
42
Getting started
EWF manager
(Enhanced Write
Filter)
Description :
The Magelis iPC operating system, Windows Xpe, is installed on a memory cartridge. This cartridge is a rewritable "Compactflash" card and this media offers a relatively restricted number of writing.
To resolve this limtation, , the operating system must store its temporary data in dynamic memory (RAM).
All those operations are managed by EWF. The EWF manager can be temporarily inhibited.
l l l l l
The data which are concerned by this behaviour are all configuration files like : registry, softwares and users manager.
When EWF is enabled, all operating system modifications will be lost after Magelis iPC restarting :
New applications installation
New peripheral installation
New users creation
Network configuartion : IP address, operating mode...
OS custom : background picture, screen saver...
Validation / Inhibition of EWF manager :
In Magelis iPC, an utility program allows to enable or disable EWF manager.This tool is located in the follow directory : C:\Program files\Change EWF
State\ChangeEWFstate.exe
CD restore l l l l l
Any changes will be taken account after restarting of the terminal.
ENABLED : EWF activated. Normal behaviour.
DISABLED : EWF inhibited. The operator can, after restarting, do different actions and changes settings that he doesn’t want to lose :
New applications installation
New peripheral installation
New users creation
Network configuartion : IP address, operating mode...
OS custom : background picture, screen saver...
Warning :
After any context modifications, EWF manager must be reenabled.
See Installation Guide for Magelis iPC industrial PC.
43
Getting started
44
Hardware extensions
6
At a Glance
Subject of this chapter
What's in this
Chapter?
This chapter concerns the hardware extensions for the Smart iPC.
A wide variety of optional units, Main Memory, CF cards, PCMCIA (PC cards) manufactured by Schneider Electrics and commercial PCMCIA (PC Cards) can be used with the Smart iPC. Unscrew the five (5) cover attachment screws, and remove the cover.
This chapter contains the following topics:
Topic
Before installation
Removing the Smart iPC Unit’s Cover
Smart iPC internal view
Main Memory Installation
PCMCIA Unit Installation
CF Card Installation and Removal
Page
45
Hardware extensions
Before installation
Overview Install the desired products as shown in the "Smart iPC Internal View" drawing.For the detailed optional unit installation procedures, refer to that unit’s "Installation
Guide".
WARNING
Be sure to disconnect the main power from the power supply and confirm that power is not supplied to the Smart iPC unit before installing any optional units, Main Memory, CF cards. Failure to do so can result in an electric shock.
Important l Use a screwdriver to loosen and tighten the screws. Be sure not to tighten the screws too tightly. Excessive force can damage the equipment.
l When removing or replacing screws, be careful that they do not fall inside the unit's chassis.
Failure to follow this precaution can result in death, serious injury, or equipment damage.
46
Hardware extensions
Removing the Smart iPC Unit’s Cover
Description
Step
1
Action
Lay the Smart iPC unit on its front face and remove the eight (8) cover attachment screws.
2 Slide the rear cover up to remove it in the direction shown. (When reattaching the screws, use a torque of 0.5 to 0.6N•m.).
47
Hardware extensions
Smart iPC internal view
Illustration
CF Card
Slot
PCMCIA Slot
Main Memory Installation Area
48
Hardware extensions
Main Memory Installation
Illustration
Main Memory
Connector
Stopper
How to Install the
Main Memory
The table below presents the operating mode to install the Main Memory module
Step
1
2
3
Action
Remove the Smart iPC unit’s rear cover
Angle the main memory module down slightly, and push it in until the connector pins mate with the module's pins. Then, lower the module until it is horizontal and insert it completely into the connector. This connector is shown in Smart iPC Internal View.
Push in the main memory module until the stopper snaps into place.
49
Hardware extensions
PCMCIA Unit Installation
How to install the
PCMCIA Unit
The table below presents the operating mode to install the PCMCIA Unit.
Step
1
2
Action
Remove the Smart iPC unit’s rear cover see Removing the Smart iPC Unit’s Cover
Remove the PCMCIA slot cover’s screws.
3
PCMCIA Slot Cover
Inserting a commercial-type PC Card
Insert the commercial-type PC Card into the PCMCIA connector.
Note :
• The PCMCIA slot has 2 connectors. When inserting the PCMCIA Card, check carefully that it is connected to the correct connector..
50
Eject Button PC Card (commercial)
Removing the PC Card
Press the eject button twice to remove the PC Card from the PCMCIA connector.
Pressing the eject button once causes its tip to come out.
Pressing the eject button the second ejects the PC Card from the PCMCIA slot.
Step
4
Hardware extensions
Action
Replace the PCMCIA slot cover removed in (1) and secure it in place using the two PCMCIA slot screws. The necessary torque is 0.5N•m to 0.6N•m.
Note :
• When using a PC Card with a cable attached, Schneider recommends you use a clamp or other type of device to prevent vibration from possibly dislodging the cable.
• Be sure to stop the Smart iPC unit PC Card’s driver prior to removing the PC
Card. A failure to stop this driver may result in damage to either the PC Card, the PC Card's data, or may cause Windows. to hang up. For information on the procedure for stopping the PC Card’s driver, please refer to your OS' User
Manual.
51
Hardware extensions
CF Card Installation and Removal
When using the
Smart iPC Unit and a CF Card
CAUTION
Follow the precautions below
Be sure to use only CF Cards manufactured by Schneider. Smart iPC unit performance cannot be guaranteed when using another manufacturer's CF Card.
Be sure to follow the instructions given below to prevent the CF Card's internal data from being destroyed or a CF Card malfunction from occurring:
• DO NOT bend the CF Card.
• DO NOT drop or strike the CF Card against another object.
• Keep the CF Card dry.
• DO NOT touch the CF Card connectors.
• DO NOT disassemble or modify the CF Card.
Failure to follow this precaution can result in injury or equipment damage.
52
Hardware extensions
When using the
CF Card Unit and the CF Card
CAUTION
Follow the precautions below
Prior to inserting the CF Card, be sure to confirm that the rear and the front of the CF Card are correctly oriented, and that the CF Card connector position is correct. If the CF Card is inserted incorrectly, the
CF Card, its internal data, and the CF card unit may be damaged.
Since the Smart iPC unit's OS views the CF Card as a hard disk, do not remove or insert the CF Card when the unit's power is switched ON.
Doing so may damage data and stop OS operation. Be sure to shut down the OS and switch power OFF prior to removing or inserting aCF
Card.
Never turn OFF or reset the Smart iPC while accessing the CF Card to prevent damaging file data. Also, be sure to shut down the Smart iPC unit's OS before turning OFF the main power.
Failure to follow this precaution can result in injury or equipment damage.
Limitation of the number of writings of data
The CF Card has a limitation of the number of writings of data of approximately
100,000 times. Therefore, be sure to back up all CF Card data regularly to another storage media.
CF Card
Insertion and
Removal
Familiarize yourself with the differences between the top and bottom surfaces of the
CF Card. Also, be sure that the Card is properly oriented when it is inserted (i.e. whether the top of the card is up or down etc.).
53
Hardware extensions
How to Insert the
CF Card
The table below presents the operating mode to insert the CF Card.
Step Action
1 Slide the CF Card coverin the direction shown and open the CF Card cover.
CF Card Cover
2 Insert the CF Card firmly into the CF card slot, and check that the eject button pops out.
CF Card Eject Button
How to Remove the CF Card
The table below presents the operating mode to remove the CF Card.
Step
1
2
Action
Press the eject button in fully to remove the CF Card from the CF Card slot.
After inserting/removing the CF card, be sure to replace the CF Card cover.
54
Configuration of the Bios
7
At a Glance
Subject of this chapter
What's in this
Chapter?
This chapter describes how to access certain paramters of the Bios (operating system of the computer) that need to be modified depending on its existing configuration.
This chapter contains the following topics:
Topic
Accessing the Bios configuration
Configuration Screens
Page
55
Configuration of the Bios
Accessing the Bios configuration
Precautions Important :
• Normally, use only the factory (default) settings.
Note :
• The following settings are those pre-set at the factory.
How to access the Bios
Configuration
The table below presents the operating mode to access the Bios Configuration.
Step Action
1 Connect a keyboard to the Smart iPC Unit.
2 Turn the main power ON.
3 After the message "Press <DEL> to Enter SETUP" appears, press the [DEL] key until the following screen appears.
Phoenix FirstBIOS(tm) Desktop CMOS Setup Utility
4 Standard CMOS Features 4 Frequency/Voltage Control
4
Advanced BIOS Features Load Fail-Safe Defaults
4 Advanced Chipset Features
4
Integrated Peripherals
Load Optimized Defaults
Set Supervisor Password
4 Power Management Setup Set User Password
4
PnP/PCI Configurations Save & Exit Setup
4 System Monitor Setup Exit Without Saving
ESC : Quit F9 : Menu in BIOS up down right left : Select Item
F10 : Save & Exit Setup
Time, Date, Hard Disk Type...
KEYBOARD ACTION KEYS
Provides a summary of the keyboard keys used to carry out the set up .
SYSTEM SETTING SELECTION AREA
Each of the titles (areas) listed here contains system setting items.
4 Use the arrow keys to move the cursor to the desired selection.
56
Configuration of the Bios
Configuration Screens
Precaution Important :
• Normally, use only the factory (default) settings.
Standard CMOS
Features
Selecting the STANDARD CMOS FEATURES menu item produces the following screen.
Date (mm:dd:yy):
Time (hh:mm:ss):
Phoenix FirstBIOS(tm) Desktop CMOS Setup Utility
Standard CMOS Features
Wed,Jun 25 2003
14 : 50 : 3
Item Help
4
IDE Primary Master
4 IDE Primary Slave
4
IDE Secondary Master
4
IDE Secondary Slave
[None]
[None]
[None]
[None]
Menu Level
4
Change the day, month, year
and century
Drive A
[1.44M, 3.5 in.]
Video
Halt On
[EGA/VGA]
[All,But Keyboard]
Base Memory
Extended Memory
Total Memory
640K
11366K
114688K up/down/right/left:Move Enter:Select +/-/PU/PD:Value F10:Save ESC:Exit F1: General Help
F5:Previous Values F6:Fail-Safe Defaults F7:Optimized Defaults
How to Modify the Date
Date (mm:dd:yy)
The Smart iPC unit’s internal calendar and clock allow you to set the date. The day of the week is automatically set.
Month: Jan/Feb/Mar/Apr/May/Jun/Jul/Aug/Sep/Oct/Nov/Dec
Day:1 to 31
Year: 1999 to 2099
57
Configuration of the Bios
How to Modify the Time
Time (hh:mm:ss)
The Smart iPC unit’s internal clock can be set.The hh/mm/ss (0:0:0) format is factory set prior to shipping.
Hours: 0 to 23
Minutes: 0 to 59
Seconds: 0 to 59
How to Set
Supervisor
Password
This password is used to change system information settings. It is designed to prevent unapproved users from changing the system information settings. Entering up to 8 characters here will overwrite the current password.
When you wish to have no password, click on the [Enter] key. Next, the words
"PASSWORD DISABLE" will appear, providing confirmation that the Password is no longer set.
When password input is required, use the [Advanced BIOS Features] area’s
[Security Option] feature to enter the password.
See : Advanced BIOS Features
How to Set User
Password
This password is used to view system information settings. It is designed to prevent unapproved users from viewing the system information settings. Entering up to 8 characters here will overwrite the current password.
When you wish to have no password, click on the [Enter] key. Next, the words
"PASSWORD DISABLE" will appear, providing confirmation that the Password is no longer set.
When password input is required, use the [Advanced BIOS Features] area's
[Security Option] feature to enter the password.
See : Advanced BIOS Features
Important :
• When using either [Set Supervisor Password] or [Set User Password], you can easily view and change system settings.
• When using BOTH the [Set Supervisor Password] and [Set User Password] features, [Set User Password] will allow you to only view system data, not change it.
How to Save and
Exit Setup
This feature saves the settings entered in the Setup Utility and restarts the Smart iPC unit.
How to Exit
Without Saving
This feature quits the Setup Utility program without saving any settings entered.
58
Maintenance
8
Regular Cleaning
Precaution
CAUTION
Do not clean the unit with thinner, organic solvents, or strong acids.
Failure to follow this precaution can result in injury or equipment damage.
How to Clean the
Display
Action Figure
When the display surface or frame become dirty, use a soft cloth moistened with neutral detergent to wipe away any dust or stains.
Neutral detergent
Display
59
Maintenance
Action Figure
Do not use sharp or hard objects, such as a mechanical pencil or screwdriver, to push on the display. This could damage the unit.
Use the screen protection sheet when using the Smart iPC in extremely dirty or dusty areas.
Protection sheet
How to Install
Gasket
Replacement
The moisture resistant gasket protects the Smart iPC. See Installation Procedures and improves its water resistance for instructions on installing the Smart iPC’s gasket.
Important :
• A gasket which has been used for a long period of time may have scratches or dirt on it, and could have lost much of its water resistance. Be sure to change the gasket periodically (or when scratches or dirt become visible).
How to Clean the
Fan Fiter
Since excessive dirt and dust in the filter of the Compact iPC’s electric fan can potentially affect the performance of the unit, regular inspection and cleaning of the filter is strongly recommended.
60
Maintenance
Illustration
Filter
The table below presents the operating mode to clean the Fan Filter.
Step
1
2
3
4
Action
Remove the fan cover after having unscrewed the 4 screws.
Remove the filter.
Clean the filter completely. If stubborn dirt or stains are present, wash the filter with a neutral detergent.
Important :
• Do not wring the filter to dry it.
• When drying the filter, dry it without exposing it to direct sunlight.
• Allow it to air dry completely before reattaching to the Compact iPC.
After having posed the filter on the grid, reattach the cover with its cover attachment screws.
61
Maintenance
62
Installation
At a Glance
Subject of this part
What's in this
Part?
This part concerns product installation.
This part contains the following chapters:
Chapter
9
10
Chapter Name
Dimension/Assembly
Connections to PLCs
III
Page
63
Installation
64
Dimension/Assembly
9
At a Glance
Subject of this chapter
What's in this
Chapter?
This chapter concerns the dimensions and the panel mouting of products.
This chapter contains the following topics:
Topic
Dimensions
Cropping for Cabinet Installation
Panel Mounting
Installing the Smart iPC
Page
65
Dimension/Asembly
Dimensions
Dimensions of the Smart iPC
Unit
Top
Unit : mm[in]
Front Side
66
Other
Dimensions
(with Installation
Fasteners installed)
Dimension/Asembly
Unit : mm[in]
67
Dimension/Asembly
Cropping for Cabinet Installation
Overview For cabinet installation, it is necessary for products to be cropped.
Dimensions The dimensions of the crop are given below. unit : mm[in]
Precautions Important :
• Be sure the thickness of the installation panel is from 1.6 mm [0.06 in] to 10 mm
[0.39 in] .
• All panel surfaces used should be strengthened. Especially, if high levels of vibration are expected and the products installation surface (i.e. an operation panel’s door, etc.) can move (i.e.open or close) due consideration should be given to the products weight.
• To insure that the products water resistance is maintained, be sure to install it into a panel that is flat and free of scratches or dents.
• Be sure all installation tolerances are maintained to prevent the unit from falling out of its installation panel.
68
Dimension/Asembly
Panel Mounting
Overview The products are designed to be attached to the door of a cabinet with the attachments described below
Dimensions
16[0.63]
M6
16.6[0.65]
31[1.22] unit : mm[in] unit : mm[in]
69
Dimension/Asembly
Installing the Smart iPC
Installation
Location
Illustration
• Avoid placing the Smart iPC next to other devices that might cause overheating.
• Keep the Smart iPC away from arc-generating devices such as magnetic switches and non-fuse breakers.
• Avoid using the Smart iPC in environments where corrosive gases are present.
• To ensure the reliability, operability and ventilation of the Smart iPC, be sure to install it in locations that are more than 50mm away from adjacent structures or equipment. Also, consider the need for installing or removing PCMCIA modules, or connectors when designing and installing your product.
Side View Rear View
Vibration and
Shocks
If the Smart iPC is moved when its enclosure doors are open, or while it is installed in a rack equipped with caster wheels, the unit can receive excessive vibration or jolting. Be especially careful at this time.
70
Dimension/Asembly
How to Install the
Smart iPC Unit
Follow the steps given below when installing the Smart iPC.
Step Action
1 Attaching the Installation Gasket
Even if the your Smart iPC’s Installation Gasket is not needed to prevent water from entering the unit, the gasket also acts as a vibration absorber and should always be attached. To install it, place the unit face down on a soft surface and attach the gasket to the rear side of the display face, in the plastic bezel’s groove (see picture below).
Important :
• Before mounting the Smart iPC into a cabinet or panel, check that the installation gasket is attached to the unit.
• A gasket which has been used for a long period of time may be scratched or dirty, and may have lost much of its water resistance. Be sure to change the gasket at least once a year, or when scratches or dirt become visible.
• The corresponding gasket is provided into the maintenance kit ref:
MPC YK 50 MNT KIT.
• Since the gasket is flexible but not elastic, be careful not to stretch it unnecessarily, as doing so could tear the gasket.
• Be sure, when pushing the gasket into the installation groove and around the corners of the unit, that the gasket’s seam is not placed in a corner. Placing the seam here could eventually cause the gasket to tear.
• Be sure to place the gasket’s flat, non-grooved side facing down.
Smart iPC
Rear Face
Gasket
Installation
Groove
Gasket seam
Note :
• The Smart iPC’s bezel has a part attached to it. To prevent the installation gasket from contacting this part, be sure to press the installation gasket completly into its groove.
Important :
• If the installation gasket is not properly inserted into the groove, the gasket’s moisture resistance may not be equivalent to IP 65.
• When the installation gasket is properly inserted, approximately 2.0 mm of it will extend outside the groove. Before installing a Smart iPC into a panel, be sure to confirm that the gasket is correctly in place.
71
Dimension/Asembly
Step Action
2 Create a Panel Cut
Create a panel cut for the Smart iPC, like that pictured here. Two additional items, the installation gasket and the installation fasteners are required when installing the unit.
See Panel Cut Dimensions
Panel
Panel Cut
Note :
• To obtain the maximum degree of moisture resistance, be sure to install the Smart iPC on a smooth, flat surface.
• The panel itself can be from 1.6 mm [0.06 in] to 10.0 mm [0.39 in] thick
Important :
• Strengthening may be required for the panel. Be sure to consider the weight of the
Unit when designing the panel.
72
Dimension/Asembly
Step Action
3 Smart iPC Viewing Angle
• Be sure that the panel’s viewing angle is tilted no more than 30 degrees from parallel to the operator (i.e. operator is directly in front).
4
Must be 30 degrees or less
• Avoid placing the Smart iPC next to other devices that might cause overheating.
• Avoid using the Smart iPC where the ambient temperature will be higher than the allowed specification.
• Keep the Smart iPC away from arc-generating devices such as magnetic switches and non-fuse breakers.
• Avoid using the Smart iPC in environments where corrosive gases are present.
Insert the Smart IPC installation slot
Mounting Panel
Smart IPC
Important :
• Be sure the panel cut’s actual measurements are the same as those given here, otherwise the Smart iPC may slip or fall out of the panel.
73
Dimension/Asembly
Step Action
5 Attach and Secure the Rear Installation Attachments
Locate the Smart iPC’s attachment holes, located on the top, bottom, and sides of the Unit.
Top
74
Attachment
Right Left
Panel
Bottom
Attachment Screw
Smart iPC
Important :
• Excessive torque may damage the Smart iPC unit.
• To ensure a high degree of moisture resistance, the torque should be 0.5N•m.
Note :
• Depending on the installation panel's thickness, etc., the number of installation fasteners used may need to be increased to provide the desired level of moisture resistance.
• The corresponding installation attachments can be purchased as spare parts with the maintenance kit ref:MPC YK 50 MNT KIT.
Connections to PLCs
10
Connection to PLCs
Nano, Micro,
Premium
This connection requires the use of connection cable TSX PCX 1031 supplied with
PL7 Pro and PL7 Junior software.
This 2 meter-long cable is equipped with the following: l l
A 9-contact SUB-D-type female connector for connection to the Smart iPC.
A 5-contact microDin-type male connector for connection to the PLC.
Series 7 This concerns TSX 27 PLCs, and TSX/PMX 47/67/87/107 PLCs.
This connection requires the use of connection cable FT20CBCL30 supplied with
XTEL Pack software.
l l
This 2.5 meter-long cable is equipped with the following:
A 9-contact SUB-D- type female connector for connection to the Smart iPC.
A 9-contact SUB-D-type male connector for connection to the PLC.
TSX 17 TSX 17 PLCs are connected via an accessory for converting the COM1 link (RS
232) into a RS 485 link (to be ordered separately).
Accessory reference number: TSX 17 ACC PC
April 2000/30000 This connection requires the use of connection cable TSX PKIT 2040 (to be ordered separately).
This 2 meter-long cable is equipped with the following: l l
A 9-contact SUB-D- type female connector for connection to the Smart iPC.
A 9-contact SUB-D-type male connector for connection to the PLC.
75
Connections to PLCs
76
IV
Appendices
At a Glance
Subject of this part
What's in this
Part?
This part contains the appendices relating to the products.
This part contains the following chapters:
Chapter
11
Chapter Name
Accessories
Page
77
Appendices
78
Accessories
11
Accessories
List Accessories are available as options. The list of accessories is shown below:
Description
RAM 512Mb 1,7G
RAM 512Mb 667M
Empty Compact Flash 512Mb
Protection sheet
Industrial external PS/2 keyboard
Reference
MPC YK05 RAM 512
MPC YK02 RAM 512
MPC YN00 CFE 00N
MPC YK50 SPS KIT
MPC YN00 KBD 00N
79
Accessories