Schneider Electric Sun/twilight sensor User Guide | Manualzz
Sun/twilight sensor© Schneider-Electric 2014V5806-564-0110/16
en
1
du
Technical data
2
Max. sensitivity of photoelectric diode:
Temperature range:
Type of protection:
Cable length:
Sun/twilight sensor
Operating instructions
Art. no. MTN580691
3
4
1. The sun/twilight sensor measures the brightness. The
limit value is exceeded.
2. The blind is lowered. The sensor is now in the shade,
the blind stops below the sensor.
3. The blind is raised a little.
4. The blind is lowered and stops above the sensor.
Accessory from
– Brightness sensor interface flush-mounted (Art. no.
MTN5195-0100)
The limit value can be adjusted in the advanced menu of
the display timer module. The push-button module Comfort uses fixed limit values.
|
at λ = approx. 850 nm
-30 to +70°C
IP 54
2m
Dispose of the device separately from household waste at an official collection point. Professional recycling protects people and the
environment against potential negative effects.
Schneider Electric Industries SAS
If you have technical questions, please contact the Customer Care Centre in your country.
schneider-electric.com/contact
The sun protection function is only active when
the blind is completely raised.
For your safety
¼
DANGER
Risk of serious damage to property and personal injury, e.g. from fire or electric shock,
due to incorrect electrical installation.
Safe electrical installation can only be ensured if
the person in question can prove basic knowledge in the following areas:
How to install the sensor
Connecting the sensor
|
The sensor cable conducts safety extra-low voltage (SELV). Observe the installation regulations
according to VDE 0100.
|
The sensor cables may not be extended.
• Connecting to installation networks
• Connecting several electrical devices
• Laying electric cables
These skills and experience are normally only
possessed by skilled professionals who are
trained in the field of electrical installation technology. If these minimum requirements are not met
or are disregarded in any way, you will be solely liable for any damage to property or personal injury.
Getting to know the sensor
The sun/twilight sensor (referred to below as the sensor) is an accessory for the brightness sensor interface
flush-mounted in the PlusLink system.
The sensor is connected to the brightness sensor interface flush-mounted.
1 Cut off the connection plug and remove insulation
from the cable ends.
2 Connect sensor cables to inputs for the brightness
sensor interface flush-mounted:
– White core A (reference potential) to connecting
terminal 1
– White/grey core B (signal line) to connecting terminal 4
The sensor is affixed to the inside of the window pane by
means of the sucker, from where it measures brightness.
The brightness value is evaluated by the brightness sensor interface flush-mounted.
When combined with a blind control insert connected via
PlusLink and the relevant modules (e.g. push-button
module Comfort, display timer module), the sensor
makes it possible to implement a sun protection function.
B
1 2 3 4
Affixing the sensor to window pane
|
The position of the sensor on the window pane is
a decisive factor for the sun protection function
because it determines the starting point for the
blind.
1 Clean the window pane and the sensor's sucker
with a window cleaning agent.
2 Moisten the sucker and affix it to the intended location on the window pane.
V5806-564-01 10/16
The sun protection function is activated as soon as the
brightness by the window measured by the sensor exceeds the set limit value for 2 minutes. The blind is lowered to below the sensor, is raised a little and stops
above the sensor. If the brightness falls below the limit
value for 15 minutes, the blind is raised again.
A
Sun/twilight sensor© Schneider-Electric 2014V5806-564-0110/16
en
3 Lead the cable directly through the cable duct to the
connecting terminal. The cable must lie straight in
the cable duct and there must be no loops in the
area of the 230 V connecting terminal.
Connections
Sun/twilight sensor
Operating instructions
A
C
B
4 Connect the sensor cable to the connecting terminal (included with the attachment with sensor connection): white/grey core in the centre, white core on
the right.
Surface-mounted installation (blind push-button
with sensor connection), option 2
1 Cut off the connection plug.
Art. no. MTN580691
A Bore for tube
B Line terminal
C Connection terminal
How to install the sensor
B
Accessory from
– Blind push-button with sensor connection
– Blind push-button with memory function and sensor
connection
– Blind push-button with IR receiver and sensor connection
– CONNECT radio roller shutter push-button with sensor connection
– Blind time switch with sensor connection
|
The sensor cable conducts safety extra-low voltage (SELV). Observe the installation regulations
according to VDE 0100.
Depending on the attachment, the sensor is placed directly onto the attachment or installed on the insert using
a clamp, with the attachment then placed on top.
The sensor cable can be either surface-mounted or
flush-mounted at the insert.
¼
1 Cut off the connection plug.
3 Connect the sensor cable to the connecting terminal (included with the attachment with sensor connection): white/grey core in the centre, white core on
the right.
B
DANGER
Risk of serious damage to property and personal injury, e.g. from fire or electric shock,
due to incorrect electrical installation.
2 Guide the sensor cable A through the cable duct
B in the attachment to the connecting terminal in
the insert.
Surface-mounted installation with blind time switch
with sensor connection
Flush-mounted installation
For your safety
A
A
A
Safe electrical installation can only be ensured if
the person in question can prove basic knowledge in the following areas:
• Connecting to installation networks
1 Connect the sensor directly to the attachment A
via the connection plug.
• Connecting several electrical devices
D
• Laying electric cables
Getting to know the sensor
C
2 Lead the individual cores of the sensor cable
through the insulation tube A (included with the
sensor connection).
3 Push the cable and the insulation tube through the
bore B of the insert and through the line terminal
C to the connecting terminal. The insulation tube
must cover the individual cores all the way from the
external cable insulation up to the connecting terminal D.
Sun protection function
Automatic lowering of the blinds/roller shutters when the
set brightness value has been exceeded.
Twilight function
Lowering of blinds/roller shutters at twilight.
1 Clean the window pane and the sensor sucker using a suitable cleaning agent (e.g. soap suds).
2 Dampen the sensor and push it onto the window
pane.
|
Information on setting the sun protection function
and the twilight function can be found in the instructions for the attachment concerned.
Technical data
The sun/twilight sensor (referred to below as the sensor) is used together with an attachment from the blind
control system range (blind push-button/blind time
switch with sensor connection) and the appropriate insert. It functions as a light sensor and is equipped with a
suction cup with which it can be attached to the window
pane.
Two functions are enabled by the sensor:
Fastening the sensor to the window
Max. sensitivityof the
photodiode:
Temperature range:
Type of protection:
Cable lenght:
A
at λ = approx. 850 nm
-30 to +70 °C
IP 54
2m
B
4 Connect the sensor cable to the connecting terminal (included with the attachment with sensor connection): white/grey core A in the centre, white
core B on the right.
5 Place the connecting terminal into the insert.
Surface-mounted installation (blind push-button
with sensor connection), option 1
1 Cut off the connection plug.
2 Lead the sensor cable behind the supporting plate
(between the wall and the supporting plate) through
the opening in the cable duct of the insert.
Dispose of the device separately from household waste at an official collection point. Professional recycling protects people and the
environment against potential negative effects.
Schneider Electric Industries SAS
If you have technical questions, please contact the Customer Care Centre in your country.
schneider-electric.com/contact
V5806-564-01 10/16
These skills and experience are normally only
possessed by skilled professionals who are
trained in the field of electrical installation technology. If these minimum requirements are not met
or are disregarded in any way, you will be solely liable for any damage to property or personal injury.