R4
séries 74-84
Cartouche option mouvement vertical
Vertical movement option cartridge
VW2-RLD221 g u i d e d’ e x p l o i t a t i o n u s e r' s m a n u a l
Sommaire / Contents
Français page
Présentation - Montage
Fonctionnement
2 - 3
Double configuration 4
Logique de frein
Autres extensions
Schéma de séquence
5 - 6 - 7
7
8
English
Presentation - Mounting
Operation
Double configuration
Brake logic
Other extensions
Sequence circuit diagram
9 - 10
11
12 - 13 - 14
15 - 16
17
1
Presentation - Mounting
Function
Mounting
Designed as an option for the RECTIVAR 4 series 84 digital variable speed controllers, the vertical movement option board is intended to extend the basic RTV
84 software while assuring a second possible motor configuration and/or the logic control for a mechanical brake for vertical movements (or, by extension, any movement where the load provides a torque which is always in the same direction, whatever the direction of motor rotation). This option cannot be combined with the other special application cartridges. It requires version V3.1 of the RTV 84 software, minimum. It can be combined with the VW1-RZD101 option board…
The cartridge, supplied separately, should be plugged into the connector reserved for this purpose on the VX4-RZD103 display board, with the speed controller switched off. The fitting (or removal) of this cartridge is monitored by the speed controller's microprocessors : change to "Option factory setting" and to configuration occurs, therefore, when the speed controller is switched back on.
EEPROM cartridge
VW2RLD221
Display
Note : the optional configuration record form provided in the Rectivar series 74/84 user's manual, enables the presence of the cartridge in question to be noted, together with the corresponding additional configurations.
This manual is purely an addition to the user's manual n
°
42085 mentioned above, and the latter publication should also be referred to.
10
Presentation - Mounting
Incompatibility
Optional factory setting
Extended configuration
Double configuratio n
The fitting of the option cartridge with a speed controller software of an earlier date than the V2.1 has no effect : the cartridge is totally ignored; no fault is displayed.
If a later version than software V3.1 is installed in the speed controller and it is incompatible with the software contained in the cartridge and in the case of a software V2.1, the procedures described below will not occur. Instead, an initial fault will appear on the display, requiring the matching of the software references :
Proms / option
Consult your local Telemecanique office to have the softwares matched.
From speed controller software V3.1 onwards, the cartridge software forces, on the first occasion that the speed controller is switched on after the board has been fitted, changeover to an restricted Factory settings procedure, which occurs when the following appears on the display :
Option fact. sett.
< ENTER >
Enter is the only answer possible.
This initialisation only concerns the data specifically related to the option cartridge.
The speed controller changes over to the configuration procedure, extended as follows.
Via the cartridge, it becomes possible to configure new parameters relating to a second motor (or group of motors) which must also be switched by contactors and relays, paying special attention to the different input/output assignments.
The two configurations, once defined, are put into effect by the exclusive selection of A or B, carried out either using the LI4 input, or by bit W24,9 of the serial link logic control word (see later). The first configuration, known as A, always has priority in the absence of a selection command.
One of the two basic setting and option values corresponds to one of the configurations A and B.This is transparent for the user. Once one of these configurations is in use, only the corresponding setting values are available via the keyboard
"Adjustment" procedure, or in read/write with serial link. Any change in configuration from A to B or B to A is taken into account only if the speed controller is locked
(RUN = 0) and if the speed controller is not in stop fault (so that the fault can be analysed in the configuration in which it occurred).
CAUTION
:
A change in configuration leads to changes in : settings, inputs and outputs, functions, fault processing.
The fitting of the cartridge does not make double configuration obligatory, but does make the choice available. If double configuration is validated, input LI4 is assigned to "configuration B" function. If this input is supplied (in local mode, if using serial link), configuration B is activated, with all its effects : settings, inputs and outputs, faults, functions. In logic line mode (serial link), bit
W24,9 activates configuration B.
NB : • "Past faults" does not distinguish between the two configurations. This distinction should be made via a serial link reading in the "current faults" zone.
• The configuration extensions resulting from the presence of the
VW1-RZD101 board (when present), are doubled, including those concerning the serial link protocol.
11
Operation
Double configuration
Enter
Standard configuration access and start according to manual 42085
Dialogue
English
Rectivar ...
... amps
Enter
Option VW1RZD1..
Ind …
Recognition of the option board, where appropriate, and its update index
Enter
Enter
Option VW2RLD221
V1.1
Recognition of the option cartridge, and its software version
Yes or No decision for the taking into account of the Double configuration function.
2 configurations
No
No and
Enter Yes and Enter
Configuration
A (then B)
Enter
F=50/60 Hz.Voltage ?
400V
Enter
Enter
Enter
EC : load weigh ?
No
Fault reassign ?
No
Latching ?
Yes
(end B or 1 config. only) Enter
Config accepted ?
<CLEAR> <ENTER>
}
}
If the answer is Yes, input LI4 and bit W24,9 are assigned to configuration B control. The assignment menu for LI4 is therefore no longer available.
Configuration described in user's manual 41248, modified by the specific brake logic function and, where appropriate, by the option board
VW1-RZD101.
(end A) Enter
Validation of the complete configuration or configurations
12
Enter
Change to working state
Clear
Revert to start
NOTE: • Carry out the adjustments for each configuration, and validate the configuration either via LI4, or via W24,9.
• In the adjustment procedure, configuration A or B is shown at the beginning of the second line of the display (DATA) for each parameter.
Example Acceleration
B 9,9 seconds
CAUTION: It is not possible to configurate two armature voltages which are not in the same limits as forced by the insulating board VW2-
RZD207 link position; ie: 0 to 260V, 261V to 460V, 461V to 570 volts.
571 to 750 volts
Operation
Brake logic
Special aspects of configuration
The purpose of the brake logic is to ensure that the machine exerts a torque in the raising direction, by convention "forward", capable of holding the load during the transient brake release phase, whatever the direction commanded. In addition, it checks that the speed controller and the mechanical brake are operating before validating each movement.
During the transient brake actuation phase, the setting is again maintained after dynamic braking, at zero speed reference for a fixed time of 1 second.
The fitting of the option cartridge modifies configurations A and B as follows :
- Special assignment of relay K1:
The assignment menu is not available : relay K1 is assigned systematically to control of the mechanical brake contactor. It is de-energized with priority when the speed controller locks due to a stop fault or RUN = 0
- Special assignment of input LI2 :
The faster/slower function cannot be used. The LI2 assignment menu is not available : logic input LI2 is systematically assigned to the mechanical brake data feedback : auxiliary contact of the contactor or brake release control contact.
- Special assignment of input Ec :
an additional question (see previous page) is asked for each configuration
After LI3 or LI4
Ec : Load weight ?
No
Scroll down and/or Enter
Answer No or Yes or Not assigned
- if the answer is No, input Ec remains a summing speed reference
- if the answer is Yes, input Ec is assigned to load weighing, which must be equalled when the initial current impulse occurs. Ec remains assignable at 0-20 mA or 4-20 mA as usual, but 20 mA is considered equivalent to the maximum armature current configuration value : the weighing output must be scaled accordingly.
- when the answer is Not assigned, input Ec is not taken into account. This can be used, particularly with configuration B.
Caution : Do not use the speed variator in speed write by armature curent, the imprecision of this kind of regulation is incompabible with the brake command.
13
14
Operation
Brake logic
Extension of the settings
One or two settings are added at the end of the list of usual settings :
Arm.curr.impulse
amps
Impulse time
1,00 seconds
{ - If the above answer is Yes, this setting is not displayed. The current value sufficient to hold the load at the moment the brake is released is indicated.
From 0 to 100 %, by default 75 %, of the maximum armature current configuration.
{ Indication of time T1 on the timing diagram.
From 0,00 to 2,50 seconds, so that the start of the speed increase is synchronised with the effective mechanical brake release. By default, 1,00 second.
In the event of the brake control at LI2 being carried out by a normally closed contact on the brake, this time delay must be adjusted to a very low value, or to 0.
NOTE : • In the event of configuration for a horizontal movement, adjust "Arm.
curr. impulse" to zero.
Operation
Brake logic
Timing diagram • Operation is shown on the following timing diagram, which represents a normal start and stop in the "raise" direction.
• RUN signal
• FORWARD or
REVERSE input
• Internal run command
• Unlocking of the speed controller
(firing gates)
• Polarisation of the speed amplifier
• Peak limiting of the current limitation according to configuration
• Armature current signal
• Detection of current level reached = weighing or adjustment
• Relay K1 control assigned to brake contactor control
• Brake contactor feedback or brake release detection contact (LI2)
• Real state of the brake pads
• Speed amplifier integration inhibition
• Ramp reset to zero
T3 = 3s
T1 réglage
T2 = 1s
• Speed signal
T2
• Late feedback from contactor (LI2)
• Speed controller lock
• Mechanical brake feedback fault
T3 fault on energization fault on de-energization
15
Operation
Other extensions
Additional fault
Serial link
Adjustment words accessible in read and write
"
Mechanical brake"
This fault is generated in accordance with the timing diagram on the previous page : if after the run command the brake response time is longer than 3 seconds or if after the stop command the brake response time is longer than 1 second. The fault is a latching stop external dynamic type. By serial link, it is available on bits W34,B as a stop fault and W64,B as an actual fault.
In addition to the bits already given above :
- W24,9 : second configuration command
- W34,B :
- W64,B :
}
mechanical brake fault other word addresses become accessible via serial link :
Writing possible if PLI = 1
Number Name Description Definition
WO
W1
IMP.I
Armature 0,1 A for cal < 72A
I impulse value 1A for cal > 72A
T.IMP Impulse time 0,01 s
Condition
According to configuration
* IMPORTANT REMINDER
In read and write modes, access is only possible to the values corresponding to whichever of the configurations, A or B, is operational.
Configuration of the inputs/outputs • K1 relay
The relay override configuration can be read on bits W57,0 to W57,3 at the decimal value 2 = Brake control.
• LI2 input
The override configuration of logic input LI2 can be read on bits W58,4 to W58,7 at the decimal value 13 = Brake feedback.
* Testing of these decimal values can comprise an option cartridge presence check, which gives the same overrides in both configurations.
16
Sequence circuit diagram
Example of sequence diagram with hoisting option : additions to standard diagrams with minimum use of the inputs and outputs.
Note : Fit protection circuits on the brake control coils and the relay and contactor coils.
T3
Q1
Q2
F1 - F6
F5
A
TTA
TTB
OFF
)
Q4
Q1
KA1
)
ON KA1
Q3 x x x
Q10 x x
KM10
RC1
RC2
RC3
Y1
KM10
PL
LI2
PL
LI3
P10
K1A E1
K1B N10
OE1
K2A
K2B RUN
PL
KM1
KA1
Validation of the reference by
LI3 = FORWARD
Voltage control
KA1
KA1 KM1 KM10
Special assignments corresponding to this diagram:
- K1 and LI2 : automatic assignment
- LI3
- K2
: FORWARD
: Variable speed controller ready
The operating direction is controlled by the polarity of the reference; however, logic inputs (FORWARD and REVERSE) can also be used with a single reference polarity.
17
18
99344 AOUT 93