InRow® Direct Expansion Air Conditioners
ACRD100, ACRD200, ACRD600, and ACRD600P
Series
Technical Specifications
Up to 42kW
990-5801C-001
Release Date: 10/2019
www.schneider-electric.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Table of Contents
Technical Data .............................................................................................5
Model Identification.....................................................................................5
Overview ...................................................................................................6
Capacities ............................................................................................6
Room Air Distribution ............................................................................6
Compliance Approval ............................................................................7
Working Conditions and Environmental Limits.........................................8
Scalable Solution for Critical Environments...................................................9
InRow Advantages................................................................................9
Scalable for High Density ......................................................................9
Standard Features and Options .................................................................10
Standard Features ..............................................................................10
Optional Features ...............................................................................13
Microprocessor Controller .........................................................................14
ACRD100 and ACRD200 Series ..........................................................14
ACRD600 and ACRD600P Series ........................................................15
Microprocessor Controller....................................................................15
Open Architecture...............................................................................15
Control Type.......................................................................................15
Functions ...........................................................................................16
Logging..............................................................................................16
Control ...............................................................................................16
Alarms ...............................................................................................16
Component Identification ..........................................................................19
External Components..........................................................................19
Internal Components...........................................................................21
Electrical Panels .................................................................................27
Performance Specifications.......................................................................33
Net Cooling Capacity ..........................................................................33
General Data ......................................................................................41
Altitude Correction Factors ..................................................................45
Electrical Data ....................................................................................46
Sound Data ........................................................................................47
Dimensions and Weights...........................................................................48
ACRD100 and ACRD200 Series ..........................................................48
ACRD600 and ACRD600P Series ........................................................49
Piping and Electrical Access Locations .................................................51
ACRD600 and ACRD600P Series..............................................................55
Water-Cooled Bottom Piping (ACRD200 Series) .........................................56
Glycol-Cooled Bottom Piping (ACRD200 Series).........................................57
Outdoor Heat Exchanger Data ...............................................................58
Mechanical Data.......................................................................................58
Air-Cooled Condensers (ACRD100 Series)...........................................58
Air-Cooled Condensers (ACRD600 Series)...........................................59
Fluid Coolers (ACRD200 Series)..........................................................60
Electrical Data ..........................................................................................61
Air-Cooled Condensers (ACRD100 Series)...........................................61
Air-Cooled Condensers (ACRD600 Series)...........................................61
990-5801C-001
3
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Fluid Coolers (ACRD200 Series)..........................................................62
Dimensions ..............................................................................................62
4
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Model Identification
ACRD100 Series and ACRD200 Series—300 mm Units
The model number can be found on the outside of the shipping crate and on the
name plate located on the unit as shown. Use the table below to verify that the
equipment is the right type and voltage.
REAR
na4402b
NAME PLATE
Model
Range of Capacity
Heat Rejection
Voltage/Phase/
Frequency
Humidifier/Reheat
Air Pattern
ACRD100
Up to 10 kW
Air-cooled
208-240/1~/60 Hz
None
Back to front
ACRD101
Up to 10 kW
Air-cooled
220-240/1~/50 Hz
None
Back to front
ACRD200
Up to 10 kW
Fluid-cooled
208-240/1~/60 Hz
None
Back to front
ACRD201
Up to 10 kW
Fluid-cooled
220-240/1~/50 Hz
None
Back to front
ACRD600 and ACRD600P Series—600 mm Units
na5809a
NAMEPLATE
The model number can be found on the outside of the shipping crate and on the
nameplate located inside the equipment as shown. Use the table below to verify
that the equipment is the correct size and voltage.
Range of
Capacity
Heat Rejection
Voltage
Frequency
Reheat
Humidifier
Air Pattern
ACRD600
Up to 42 kW
Air-cooled
200–240
50/60 Hz
N/A
N/A
Rear to front
ACRD601
Up to 42 kW
Air-cooled
460–480
60 Hz
N/A
N/A
Rear to front
ACRD602
Up to 42 kW
Air-cooled
380–415
50/60 Hz
N/A
N/A
Rear to front
ACRD600P
Up to 42 kW
Air-cooled
200–240
50/60 Hz
Electric
Steam canister
(replaceable)
Rear to front
ACRD601P
Up to 42 kW
Air-cooled
460–480
60 Hz
Electric
Steam canister
(replaceable)
Rear to front
ACRD602P
Up to 42 kW
Air-cooled
380–415
50/60 Hz
Electric
Steam canister
(replaceable)
Rear to front
SKU
990-5801C-001
5
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Overview
This modular, row-based computer room cooling system offers efficient,
predictable, and economical cooling for a variety of spaces.
Critical environmental requirements now reach far beyond the confines of the
traditional data center or computer room to encompass a larger suite of
applications, referred to as technology rooms. Critical environment applications
include the following:
•
Computer rooms
•
Telecommunication facilities
•
Clean rooms
•
Power equipment
•
Medical equipment rooms
•
LAN/WAN environments
A worldwide network by Schneider Electric representatives is fully qualified to
provide engineering, sales, installation, and service for our products.
Capacities
InRow® Direct Expansion (DX) units are available in two sizes (300 mm and 600
mm) with nominal capacities ranging from 2–10 kW (300 mm) and 8–42 kW (600
mm).
Room Air Distribution
Row-based systems are placed in line with rack enclosures. At least one system is
used per hot aisle. Air is drawn in through the rear of the system, cooled, and
discharged into the cold aisle, thereby neutralizing the sensible heating effects of
the data processing equipment. InRow DX products deliver high volumes of
airflow to eliminate hot spots in densely populated environments.
Configuration:
6
•
Air-cooled
•
Fluid-cooled
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Compliance Approval
Agency
UL and cUL
ACRD100
ACRD101
ACRD200
ACRD201
ACRD600
X
X
X
X
X
RCM
X
X
CE
X
X
EAC
X
CMIM
Agency
X
X
ACRD600P
ACRD601
ACRD601P
ACRD602
ACRD602P
X
X
X
X
X
RCM
X
X
CE
X
X
X
X
X
X
UL and cUL
EAC
CMIM
990-5801C-001
X
X
X
7
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Working Conditions and Environmental Limits
InRow DX units have a minimum heat load to ensure proper operation. Failure to
operate the unit with at least the minimum load will result in one or more of the
following conditions:
•
Decreased operating efficiency
•
Equipment on/off cycling
•
Inadequate dehumidification
•
Increased wear and tear caused by frequent on/off cycles
•
Decreased group control effectiveness
•
Potential increase in cost of ownership
Limit Working Conditions
Models
Power Supply
Minimum
Recommended
Load
8
ACRD600
ACRD600P
ACRD601
ACRD601P
ACRD602
ACRD602P
200–240 V
3 Phase
50/60 Hz
460–480 V
3 Phase
60 Hz
380–415 V
3 Phase
50/60 Hz
8 kW (27,296 BTU/hr)
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Scalable Solution for Critical Environments
InRow Advantages
na5859a
The row-based solution improves energy efficiency and cooling ability in a number
of ways. First, the InRow DX unit draws air directly from the hot aisle, allowing the
InRow DX unit to take advantage of higher heat transfer efficiency due to higher
temperature differences. It can then discharge room-temperature air directly in
front of the servers it is cooling. Placing the unit in the row enables the unit to
operate at higher return and supply air temperatures, yielding 100% sensible
capacity. This significantly reduces the need for humidification.
HOT AISLE
Scalable for High Density
The predictable performance of the row-based architecture makes it well-suited
for high density applications. The focus on heat removal instead of cold-air
delivery is the key to making this approach scalable. The modular design of the
InRow DX unit allows it to be easily added in the row as the demand for cooling
increases.
The additional benefit of the row-based architecture is the ability to add hot-aisle
containment. Containing the hot aisle further reduces any chance of hot and cold
air streams mixing. This provides ultimate predictability and allows the cooling
capacity to be matched to the IT heat load.
990-5801C-001
9
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Standard Features and Options
Standard Features
•
•
•
•
All series
◦
Variable-speed fans
◦
Standby input
◦
Common alarm output
◦
Internal condensate pump
◦
Top or bottom piping
◦
Network Management Card (NMC)
◦
Remote temperature sensors
◦
Microprocessor controller
◦
Insulated cabinet
ACRD100 series and ACRD200 series only
◦
Washable filter
◦
Condensate management with dual floats
◦
Condensate pump
◦
Scroll compressor
◦
Hot gas bypass
◦
2-way/3-way floating point valve (ACRD200 series only)
◦
Liquid line solenoid valve (ACRD100 series only)
◦
Isolation ball valves
ACRD600 and ACRD600P series only
◦
Backward inclined impeller
◦
Pleated 100-mm (4-in.) filter
◦
Condensate management with a dual-position float
◦
Scroll compressor with VFD control
◦
Liquid line solenoid valve
◦
Pipe adapters
◦
Electric reheat (ACRD600P series only)
◦
Humidifier (ACRD600P series only)
Accessories
◦
Cable leak detector
◦
Joining kit—InRow to NetShelter® VX rack
◦
NetShelter SX 42-U to 48-U height adapters
◦
NetShelter VX 42-U height adapters
◦
Bridge trough power cable shield
◦
Data cable bridge partition
◦
Fluid cooler
◦
Condenser
◦
Aisle/rack containment
Cabinet
The frame is constructed of 16-gauge formed steel for maximum strength. The
cabinet is serviceable from the front and rear. All exterior panels and corner posts
on the frame are powder coated for durability and an attractive finish. The front
and rear exterior panels are constructed of 18 gauge perforated steel with 80%
10
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
open free area. All panels, which include a key latch for safety and security, allow
easy access and removal. Insulation (ACRD100 and ACRD200 series only) is
80.1 kg/m3 (5 lb/ft3) density and complies with ASTM E84 rating of 25/50.
Condensate Pump
•
ACRD100 and ACRD200 series: A condensate pump is factory wired and
piped internally to the condensate drain pan. The pump is capable of pumping
34 l/h (9 g/hr) against head pressures of up to 50 ft (15.2 m) of total run. Of
that run, 16 ft (4.9 m) can be vertical lift as measured from floor level. Dual
floats are included with the unit. One float is used for condensate pump
control, and the other float generates a condensate pump failure alarm. The
InRow RD unit can be set to either continue running in an alarm condition or
shut down to prevent condensate pan overflow.
•
ACRD600 and ACRD600P series: A condensate pump is factory wired and
piped internally to the condensate drain pan. Within the condensate pump,
there is a dual position float. The first position is used for condensate pump
control and the other float generates a condensate pump failure alarm to
prevent condensate pan overflow.
Counterflow Cooling Coil/Condensate Pan
Designed for high-sensible heat ratios, the coil is constructed with copper tubes,
raised-lance-type aluminum fins, and 18-gauge galvanized steel end plates. Coil
headers are equipped with anti-drip shields in the event of condensation. The
condensate pan is thermal formed non-ferrous material, and is sloped for positive
drainage to provide higher indoor air quality.
Electric Reheat (ACRD600P Series Only)
Electric reheat elements are low watt density, wired for three-phase and loaded
equally on all three phases, and electrically and thermally protected by both
automatic and manual reset thermal cut outs. Reheat elements are stainless steel,
fin tubular construction.
Filters
Filtration of conditioned air is extremely vital to maintaining the clean, particle-free
environment required by electrical equipment. Filters are easily replaceable from
the rear of the unit. The ACRD100 and 200 series systems use greater-than 20%
efficiency ASHRAE 52.1, 12.7 mm (1/2 in.) washable filters that meet HF-1
standards for electronics (MERV 1 per ASHRAE 52.2). The ACRD600 and
ACRD600P series system uses a 30% efficient, 102 mm (4 in.), deep loading,
pleated filter (MERV 8 per ASHRAE 52.2, EN779 G4).
990-5801C-001
11
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Humidifier (ACRD600P Series Only)
The humidifier is a self-contained, steam-generating type, factory piped and wired,
with a disposable cylinder and an automatic solid state control circuit. Humidifier
canisters are replaceable. The humidifier controller communicates directly to the
microprocessor controller and provides complete status and control at the
operator interface.
Joining Kit—InRow/NetShelter SX
Joining kits made of 16-gauge steel enable joining the InRow unit to NetShelter
enclosures.
Network Management Card
The Network Management Card (NMC) allows communication with the local area
network (LAN). In addition, the NMC permits multi-level access to monitoring,
control, and event notification features over the building network.
Pipe Adapters (ACRD600 and ACRD600P Series Only)
Standard pipe connections are 31.75 mm (1 1/4 in.) 12 UNF female threaded ring
seal (manufactured in accordance with ANSI B1.1). The adapter converts the
threaded ring seal to a sweat adapter.
Remote Temperature Sensors
To control the cooling unit based on rack inlet temperature, remote temperature
sensors are provided. The ACRD100 and ACRD200 series units come equipped
with one temperature sensor, and the ACRD600 and ACRD600P series units
come equipped with three. These sensors measure temperature at a point 4 m (13
ft) from the connection inside the InRow DX unit. These sensors are used for
remote placement in the field on an adjacent IT rack.
Shutdown Input/Alarm Output
The unit provides one field connection input for remote shutdown and one field
connection alarm output.
Selectable Top or Bottom Piping Connections
The cooling unit includes both top and bottom piping connections. All ACRD100,
ACRD600, and ACRD600P series connections use threaded ring seals for ease of
installation and service. The ACRD200 series uses union connectors.
Variable-Speed Fans
Each unit is equipped with variable speed fans to allow for varying heat loads. In
order to provide uniform airflow over the cooling coil, the fans provide a drawthrough air pattern. The ACRD100 and ACRD200 series units are equipped with
six direct-drive fan modules. These fans are easily replaceable while the unit is in
operation. The ACRD600 and ACRD600P series is equipped with two backward
inclined, direct drive fans.
12
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Optional Features
Aisle Containment
This containment solution isolates pods (two rows of InRow cooling units sharing a
common aisle) from the whole IT environment, increasing cooling efficiency at any
density.
Cable Water Detector
A leak detection cable is placed on the floor or sub-floor around all possible leak
sources. If water or other conductive liquids contact the cable anywhere along its
length, the microprocessor controller announces the leak visually, audibly, and
across the network. The 6.1-m (20-ft) cable may be cascaded to make custom
lengths up to 24.4 m (80 ft).
Data Partition
Overhead cable distribution between adjacent NetShelter racks allows for removal
of the InRow DX units without disrupting overhead cabling.
Filters
Electrical equipment requires clean, particle-free air, thus making air filtration
extremely important. As an optional feature, higher efficiency filters can be
purchased for the InRow DX units. The
Height Adapters
To match height of the InRow DX cooling units to various rack heights, height
adapters are available for NetShelter 42-U VX and 48-U SX racks.
Network Cable
Various lengths of network cable are available to ship with your cooling system.
The network cable is used to interconnect multiple units in a redundant group, as
well as to connect the Network Management Card to your LAN.
Power Trough
Overhead power distribution between adjacent NetShelter racks allows for
removal of the InRow DX cooling units without disrupting overhead power cabling.
Rack Air Containment
This containment solution isolates the airflow of InRow cooling units from the
whole IT environment, increasing efficiency while allowing for high density
deployment.
Seismic Latch
Users must obtain and install this latch kit for deployments that require seismic
certification (ACRD100 and ACRD200 series only).
990-5801C-001
13
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Microprocessor Controller
ACRD100 and ACRD200 Series
Display Interface
Status
ESC
Check
Log
?
Warning
na1582a
Critical
Item
14
Description
Function
Critical alarm LED
(red)
When illuminated, a critical alarm condition
exists that requires your immediate attention.
Warning alarm LED
(yellow)
When illuminated, a warning alarm condition
exists. Failure to correct this condition could
cause a critical alarm.
Check log LED
(yellow)
When illuminated, at least one new event has
been logged since the last time the log was
checked. Only events that pertain to the
operation of the cooling unit will activate this
LED.
Check log LED
(yellow)
When illuminated, the cooling unit is receiving
electrical power. When the LED is flashing, the
cooling unit is downloading firmware for the
controller. This may take a few minutes.
Liquid crystal display
(LCD)
View alarms, status data, context-sensitive
help, and modify configurable items.
Up and down arrow
keys
Select menu items and access information.
ESC key
Return to previous screen or cancel current
operation.
Enter key
Open menu items and input changes to the
cooling unit settings.
Help key
Display context-sensitive help. Press the help
key for information about each option on the
screen and for instructions on performing the
tasks.
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
ACRD600 and ACRD600P Series
Display Interface
Display
Reset
10/100
USB
Console
Item
na4820a
Micro
SD
Service
Port
Description
Function
LCD Display
4.3-inch touch-screen color display
Power LED
The cooling unit is powered when the LED is
illuminated. Unit firmware is updating when
LED is blinking.
Check Log LED
When this LED is illuminated, a new entry has
been made to the event log.
Alarm LED
Displays current alarm condition of unit.
Status LED
Displays current network management card
status.
Display Reset button
Resets the display microprocessor. This has
no effect on the air conditioner controller.
Link-RX/TX (10/100)
LED
Displays current network link status.
Micro SD card slot
Memory card expansion slot.
Service port
USB-B port used only by service personnel.
USB-A port
Supports firmware upgrades.
Serial Configuration
port
Connects the display to a local computer to
configure initial network settings or access the
command line interface (CLI).
Microprocessor Controller
The microprocessor controller is standard on each system. The easy-to-use
display allows the operator to select options from the device menu-driven interface
to control and monitor the connected air conditioning system.
Open Architecture
The InRow Direct Expansion protocol is open for integration with all building
management systems. Communication interface on the system can be MODBUS
RS485 or Ethernet.
Control Type
The controller uses proportional/integral/derivative (PID), a time-proven precision
environmental control method. This allows for custom tuning of control variables to
achieve desired system response.
990-5801C-001
15
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Functions
•
Supply and return air conditions
•
Operational mode control
•
Event logging
•
Alarms
•
Redundant group control
•
Fan speed adjustment
•
Input/Output module programming
Logging
The event log keeps a record of all alarms and events. Each event log contains a
time/date stamp. The controller also displays run time, in hours, for major
components (air filters, fans, and condensate pump, as well as humidifier, heater,
and compressor for the air-cooled unit).
Control
ACRD100/ACRD200 Series
The back-lit, four-line by twenty-character display is password configurable.
ACRD600 and ACRD600P Series
The touch-screen LCD display interface is protected by a configurable password
and provides access to information and settings for the unit.
•
Supply Temperature Setpoint: 15.0–30.2°C (59.0–86.4°F)
•
Cool Setpoint: 18.0–32.2°C (64.4–90.0°F)
•
Rack Inlet High Temperature Threshold: 10.0–65.6°C (50.0–150.1°F)
•
Supply Air High Temperature Threshold: 10.0–65.6°C (50.0–150.1°F)
•
Return Air High Temperature Threshold: 10.0–65.6°C (50.0–150.1°F)
Alarms
The microprocessor controller shall activate a visible and audible alarm in the
following occurrences:
All Series
16
•
Cool fail
•
Air filter clogged
•
Return air sensor fault
•
Supply air sensor fault
•
Rack temperature sensor fault
•
High discharge pressure
•
Low suction pressure
•
Fan fault
•
Water detected (if optional leak detector used)
•
Check condensate management system
•
Air filter run hours violation
•
Group communication fault
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
•
Supply air high temperature violation
•
Return air high temperature violation
•
Filter DP sensor failure
•
Suction pressure sensor failure
•
Discharge pressure sensor failure
•
Persistent high discharge pressure fault
•
Rack inlet temperature high violation
•
External communication fault
•
Internal communication fault
•
On standby input contact fault
•
A-link isolation relay fault
ACRD100 Series and ACRD200 Series only
•
Condensate pan full
•
Upper fan power supply fault
•
Lower fan power supply fault
•
Suction temperature sensor failure
•
Persistent low suction pressure fault
•
Factory configuration not completed
•
Liquid refrigerant sensor failure
ACRD200 Series Only
•
Condenser fluid valve actuator fault
•
Outdoor heat exchanger (OHE) fault
ACRD600 and ACRD600P Series Only
•
Compressor drive communication fault
•
Compressor drive fault
•
Compressor run hours violation
•
Condensate pump run hours violation
•
Fan run hours violation
•
Idle mode active
•
High pressure switch active
•
Compressor high pressure
•
Supply humidity sensor fault
•
High suction pressure
•
Excessive compressor cycling
•
VFD inverter overheat
•
Compressor drive locked
ACRD600P Series Only
990-5801C-001
•
Humidifier water conductivity high violation
•
Humidifier fault tolerance exceeded
•
Humidifier low water
•
Humidifier excessive output reduction
17
ACRD100, ACRD200, ACRD600, and ACRD600P Series
18
•
Humidifier drain fault
•
Humidifier cylinder full
•
Humidifier RS485 communication fault
•
Humidifier run hours violation
•
Humidity high/low violation
•
Return humidity sensor fault
•
Heater fault
•
Heater run hours exceeded
Technical Data
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Component Identification
External Components
na2625a
ACRD100 and ACRD200 Series
Item
990-5801C-001
Description
Removable rear door
Side panel latch
Removable side panel
Rear casters (non-swiveling)
Front casters (swiveling)
Adjustable leveling foot
Display interface
Removable front door
Door lock
19
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
na5807a
Front (ACRD60x and ACRD60xP)
Item
20
Description
Removable rear doors
Side panel lock
Removable side panel
Adjustable leveling foot
Caster
Door handle and lock
Display interface
Removable front door
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Internal Components
na2626a
Internal Components—Front
Item
990-5801C-001
Description
Electrical control box 1
Electrical control box 2
Temperature sensor (7 total)
Condensate pan floats (2)
Condensate pan
Compressor
Front air block panel
Evaporator fans (6)
Expansion valve
Evaporator coil
21
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
na2627a
Internal Components—Rear
Item
22
Description
Filter drier
Pressure transducer (2) (located behind air block)
Filter differential pressure port
Air filter (2)
Condensate pump (2)
Electrical control box 2
Sight glass
Hot gas bypass valve
Liquid line shutoff solenoid
Electrical control box 1
Power supply unit #2
Power supply unit #1
Service junction box (top entry shown)
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
na5823a
Front (ACRD60x)
Item
990-5801C-001
Description
Condensate drain pan
Electronic expansion valve
Compressor
Variable frequency drive for
compressor (VFD)
Supply air temperature sensor
Main circuit breaker
Item
Description
Fan (2)
Fan guard (2)
Electrical panel
Communication and external device
connectors
Ground lug
Humidity sensor
23
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
na5824a
Rear (ACRD60x)
Item
24
Description
Evaporator coil
Sight glass
Condensate drain pan
Filter drier
Oil separator
Item
Description
Condensate pump
Air filters
Pipe chase
Return air temperature sensor
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
na5821a
Front (ACRD60xP)
Item
Description
Electric heater
Condensate drain pan
Electronic expansion valve
Humidifier
Compressor
Variable frequency drive for
compressor (VFD)
Supply air temperature sensor
990-5801C-001
Item
Description
Main circuit breaker
Fan (2)
Fan guard (2)
Electrical panel
Communication and external device
connectors
Ground lug
Humidity sensor
25
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
na5822a
Rear (ACRD60xP)
Item
26
Description
Evaporator coil
Sight glass
Condensate drain pan
Filter drier
Oil separator
Condensate pump
Item
Description
Humidifier
Air filters
Pipe chase
Humidity sensor
Return air temperature sensor
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Electrical Panels
na2664a
ACRD100 and ACRD200 Series
Item
990-5801C-001
Description
Leak detector port
Remote temperature sensor port
A-Link ports
Reset button
Network port
Building management system (BMS) RS-485 port
Control RS-485 port
Form C and shutdown input
RS-232 console port
Outdoor heat exchanger (OHE) ports (optional)
27
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
ACRD600, ACRD601, ACRD602
Item
Description
Transformers
Display interface connectors
Main controller board
Relay board
Ground lug
Main circuit breaker
Compressor fuse block (ACRD600, ACRD601)
Compressor circuit breaker (ACRD602)
Fan circuit breakers
Fuse not populated
Transformer A fuse
Transformer C/MB fuse
NOTE: For a top installation, control wiring is routed through the wire channel
located at the top-left corner, just above the user interface connectors.
na2724b
For a bottom installation, the control wiring is routed to the access hole in the
bottom of the equipment through wire clamps from the interface connectors. Then,
the wiring is routed down along the electrical panel and secured with wire clamps
28
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
ACRD600P, ACRD601P, ACRD602P
Item
Description
Transformers
Display interface connectors
Main controller board
Relay board
Ground lug
Main circuit breaker
Compressor fuse block (ACRD600P, ACRD601P)
Compressor circuit breaker (ACRD602P)
Fan circuit breakers
Controller fuse
Heater circuit breaker
Humidifier circuit fuse
Heater contactors
Humidifier contactor
NOTE: For a top installation, control wiring is routed through the wire channel
located at the top-left corner, just above the user interface connectors.
na2032b
For a bottom installation, the control wiring is routed to the access hole in the
bottom of the equipment through wire clamps from the interface connectors. Then,
the wiring is routed down along the electrical panel and secured with wire clamps
990-5801C-001
29
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Customer Interface Connections—ACRD100 and ACRD200
Series
LEAK DETECT
COM
RUN
OUTPUT
NO
OHE
ALARM
INPUT
24V AC/DC
+
-
COM
RUN
OUTPUT
NO
ALARM
INPUT
24V AC/DC
+
-
RACK
TEMPERATURE
USER INTERFACE
CONNECTIONS
WIRE AS CLASS 2
CIRCUITS ONLY
RS-232
CONSOLE PORT
9600-8-N-1
DTE
SHUTDOWN INPUT
CONTACTS AND
ALARM OUTPUT
CONTACTS
NC
OUTPUT
RELAY
COM
NO
GND
VOLTAGE
OUTPUT
+12 V
+24 V
SHUTDOWN
INPUT
12-30V AC/DC
+
D1
CONTROL
RS-485
D0
GND
CONTROL
MODBUS
D1
MODBUS
RS-485
D0
GND
LINK RX/TX
10/100 BASE-T
NETWORK PORT
STATUS
10 = GREEN
100 = ORANGE
RESET
885-3432_REVE1
Item
Description
A-Link ports: Pin 1 = High; pin 2 = Low;
Pins 3,6 = Perf Power; Pins 4, 5 =
Ground
Reset button
Network port
Shield/ground
RTRX(-)
Item
na2688a
24VDC
Description
NO (normally open contact)
COM (common contact)
NC (normally closed contact)
RS-232 console port
OHE (outdoor heat exchanger) alarm
input - (not used)
OHE alarm input + (not used)
OHE COM (optional*)
OHE NO port (optional*)
Leak detector port (AP9325)
Remote temperature sensor
RTRX(+)
Shutdown –
Shutdown +
24 VDC (bias)
12 VDC (bias)
Return (bias)
*To avoid unnecessary condenser operation when the ambient temperature exceeds 43°C (110°F), connect
these leads.
30
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Customer Interface Connections—ACRD600 and ACRD600P
Series
NOTE: Wire all input and output connections as Class 2 circuits.
Depending on the configuration, additional customer interface connections may
be required for the A-Link remote communications through the Network
Management Card support or traditional equipment-monitoring software.
Description
Rack inlet temperature sensors 1, 2, 3
A-Link IN
A-Link OUT
Network port
Customer output, NC (normally closed)
Customer output, COM (common)
Customer output, NO (normally open)
Supply GND (Ground)
Supply 12 VDC (current limit: 20 mA)
Supply 24 VDC (current limit: 20 mA)
Customer input + (12–30 VAC/VDC, 24 VDC @ 11 mA)
Supply COM
RTRX(-)
RTRX(+)
Modbus GND
Supply air temperature sensor (front)
Supply air humidity sensor (front)
na2009b
Item
990-5801C-001
31
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Item
Description
Rack inlet temperature sensors 1, 2,
3
A-Link IN
A-Link OUT
Network port
Technical Data
Three temperature sensors which must be installed on
the cold aisle side of the server racks. See
In and out connections for A-Link. The terminators
supplied with the equipment must be plugged into the
first A-link port and the final A-Link port for the group.
10/100 Base-T Network port. Connects the equipment
to the network; Status and Link LEDs indicate network
traffic.
• Status LED—blinks orange and green at startup;
indicates the status of the network connection
(solid green—IP address established; blinking
green— attempting to obtain an IP address).
•
Customer output, NC (normally
closed)
Customer output, COM (common)
Customer output, NO (normally
open)
Supply GND (Ground)
Supply 12 VDC (current limit: 20 mA)
Supply 24 VDC (current limit: 20 mA)
Customer input + (12–30 VAC/VDC,
24 VDC @ 11 mA)
Supply COM
RTRX(-)
RTRX(+)
Modbus GND
Supply air temperature sensor (front)
Supply air humidity sensor (front)
32
Link LED—blinks to indicate network traffic (green
— operating at at 10 mbps; orange—operating at
100
Customer-configurable output relay which can be
activated for all types of alarms or critical alarms. The
relay can be connected to external equipment using
30 VAC/VDC, 2 A.
Can be used for customer input and output interface.
Can be used for customer input and output interface.
Current limit is 20 mA.
Can be used for customer input and output interface.
Current limit is 20 mA.
Used for remote shutdown of an InRow DX unit.
Voltage is applied from the internal power supply or by
using an external power supply.
Ground connection point for remote shutdown supply
source.
Connections for Building Management System. Wire a
150-Ohm terminator resistor (supplied) into the final
InRow DX unit, between Modbus D0 and Modbus D1.
Temperature sensor installed on the front of the
equipment.
Humidity sensor installed on the front of the
equipment.
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Performance Specifications
Net Cooling Capacity
Air-Cooled and Glycol-Cooled Units
Cooling Performance at a Fixed Compressor Speed
Return Air Temperature
22.2°C DB, 15.5°C WB (72.0°F DB,
60.0°F WB)
23.9°C DB, 16.2°C WB (75.0°F DB,
61.1°F WB)
26.7°C DB, 19.4°C WB (80.0°F DB,
67.0°F WB)
26.7°C DB, 17.1°C WB (80.0°F DB,
62.8°F WB)
29.4°C DB, 18.1°C WB (85.0°F DB,
64.6°F WB)
Model
Total Capacity – kW (BTU/
hr)
Sensible Capacity – kW
(BTU/hr)
ACRD100
8.22 (28,000)
8.04 (27,000)
ACRD101
8.01 (27,000)
7.71 (26,000)
ACRD200
8.22 (28,000)
8.04 (27,000)
ACRD201
8.01 (27,000)
7.71 (26,000)
ACRD600, ACRD600P
26.87 (92,000)
21.03 (72,000)
ACRD100
8.52 (29,000)
8.52 (29,000)
ACRD101
8.16 (28,000)
8.16 (28,000)
ACRD200
8.52 (29,000)
8.52 (29,000)
ACRD201
8.16 (28,000)
8.16 (28,000)
ACRD600, ACRD600P
27.78 (95,000)
22.99 (79,000)
ACRD100
10.02 (34,000)
9.12 (31,000)
ACRD101
9.72 (33,000)
8.85 (30,000)
ACRD200
10.02 (34,000)
9.12 (31,000)
ACRD201
9.72 (33,000)
8.85 (30,000)
ACRD600, ACRD600P
N/A
N/A
ACRD100
9.36 (32,000)
9.36 (32,000)
ACRD101
8.97 (31,000)
8.97 (31,000)
ACRD200
10.02 (34,000)
9.12 (31,000)
ACRD201
9.72 (33,000)
8.85 (30,000)
ACRD600, ACRD600P
28.94 (99,000)
26.55 (92,000)
ACRD100
9.90 (34,000)
9.90 (34,000)
ACRD101
9.69 (33,000)
9.69 (33,000)
ACRD200
9.90 (34,000)
9.90 (34,000)
ACRD201
9.69 (33,000)
9.69 (33,000)
ACRD600, ACRD600P
30.19 (103,000)
29.72 (99,000)
1Airflow
is reduced to 887 l/s (1880 SCFM) at this condition to maintain adequate evaporating temperature.
is reduced to 717 l/s (1520 SCFM) at this condition to maintain adequate evaporating temperature.
3Airflow is reduced to 599 l/s (1270 SCFM) at this condition to maintain adequate evaporating temperature.
4Airflow is reduced to 510 l/s (1080 SCFM) at this condition to maintain adequate evaporating temperature.
5Airflow is reduced to 448 l/s (950 SCFM) at this condition to maintain adequate evaporating temperature.
*Airflow reduced to 3300 SCFM at this condition to maintain adequate return gas temperature.
** Airflow is reduced to 1353 l/s (2900 SCFM) at this condition to maintain adequate evaporating temperature. Airflow at full evaporating fan
speed: ACRD100/200 series—1081 l/s (2290 SCFM); ACRD600 and ACRD600P series—1900 l/s (4000 SCFM)
Minimum recommended loads: ACRD100/200 series—2 kW (6831 BTU); ACRD600 and ACRD600P series—8 kW (34,152 BTU)
2Airflow
NOTE: For ACRD100, ACRD600, and ACRD600P series, the outdoor air temperature is 35°C (95°F).
NOTE: For ACRD200 series, a 40% at 0.64 l/s (10 gpm) entering glycol mixture temperature is 40.6°C (105°F).
990-5801C-001
33
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Cooling Performance at a Fixed Compressor Speed
Return Air Temperature
32.2°C DB, 19.0°C WB (90.0°F DB,
66.2°F WB)
35.0°C DB, 19.9°C WB (95.0°F DB,
67.8°F WB)
37.8°C DB, 20.7°C WB (100.0°F DB,
69.3°F WB)
40.6°C DB, 21.6°C WB) (105.0°F DB,
70.8°F WB
43.3°C DB, 22.2°C WB) (110.0°F DB,
72.0°F WB
Model
Total Capacity – kW (BTU/
hr)
Sensible Capacity – kW
(BTU/hr)
ACRD1001
10.44 (36,000)
10.44 (36,000)
ACRD1011
10.29 (35,000)
10.29 (35,000)
ACRD2001
10.44 (36,000)
10.44 (36,000)
ACRD2011
10.29 (35,000)
10.29 (35,000)
ACRD600, ACRD600P
31.96 (109,000)
31.96 (109,000)
ACRD1002
10.62 (36,000)
10.62 (36,000)
ACRD1012
10.50 (36,000)
10.50 (36,000)
ACRD2002
10.62 (36,000)
10.62 (36,000)
ACRD2012
10.50 (36,000)
10.50 (36,000)
ACRD600, ACRD600P
33.97 (116,000)
33.97 (116,000)
ACRD1003
10.62 (36,000)
10.62 (36,000)
ACRD1013
10.50 (36,000)
10.50 (36,000)
ACRD2003
10.62 (36,000)
10.62 (36,000)
ACRD2013
10.50 (36,000)
10.50 (36,000)
ACRD600, ACRD600P
35.91 (123,000)
35.91 (123,000)
ACRD1004
10.56 (36,000)
10.56 (36,000)
ACRD1014
10.5 (36,000)
10.5 (36,000)
ACRD2004
10.56 (36,000)
10.56 (36,000)
ACRD2014
10.5 (36,000)
10.5 (36,000)
ACRD600, ACRD600P*
35.55 (121,000)
35.55 (121,000)
ACRD1005
10.6 (36,000)
10.6 (36,000)
ACRD1015
10.5 (36,000)
10.5 (36,000)
ACRD2005
10.6 (36,000)
10.6 (36,000)
ACRD2015
10.5 (36,000)
10.5 (36,000)
ACRD600, ACRD600P**
35.57 (121,000)
35.57 (121,000)
1Airflow
is reduced to 887 l/s (1880 SCFM) at this condition to maintain adequate evaporating temperature.
is reduced to 717 l/s (1520 SCFM) at this condition to maintain adequate evaporating temperature.
3Airflow is reduced to 599 l/s (1270 SCFM) at this condition to maintain adequate evaporating temperature.
4Airflow is reduced to 510 l/s (1080 SCFM) at this condition to maintain adequate evaporating temperature.
5Airflow is reduced to 448 l/s (950 SCFM) at this condition to maintain adequate evaporating temperature.
*Airflow reduced to 3300 SCFM at this condition to maintain adequate return gas temperature.
** Airflow is reduced to 1353 l/s (2900 SCFM) at this condition to maintain adequate evaporating temperature. Airflow at full evaporating fan
speed: ACRD100/200 series—1081 l/s (2290 SCFM); ACRD600 and ACRD600P series—1900 l/s (4000 SCFM)
Minimum recommended loads: ACRD100/200 series—2 kW (6831 BTU); ACRD600 and ACRD600P series—8 kW (34,152 BTU)
2Airflow
NOTE: For ACRD100, ACRD600, and ACRD600P series, the outdoor air temperature is 35°C (95°F).
NOTE: For ACRD200 series, a 40% at 0.64 l/s (10 gpm) entering glycol mixture temperature is 40.6°C (105°F).
34
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Water-Cooled Units
Cooling Performance at a Fixed Compressor Speed
Return Air Temperature
22.2°C DB, 15.5°C WB (72.0°F DB,
60.0°F WB)
23.9°C DB, 16.2°C WB (75.0°F DB,
61.1°F WB)
26.7°C DB, 19.4°C WB (80.0°F DB,
67.0°F WB)
26.7°C DB, 17.1°C WB (80.0°F DB,
62.8°F WB)
29.4°C DB, 18.1°C WB (85.0°F DB,
64.6°F WB)
Model
Total Capacity – kW (BTU/
hr)
Sensible Capacity – kW
(BTU/hr)
ACRD200
9.72 (33,000)
8.94 (31000)
ACRD201
9.57 (33,000)
8.79 (30,000)
ACRD200
8.43 (32,000)
8.43 (32,000)
ACRD201
9.30 (32,000)
9.30 (32,000)
ACRD200
11.52 (39,000)
9.90 (34,000)
ACRD201
11.64 (40,000)
9.99 (34,000)
ACRD200
10.38 (35,000)
10.38 (35,000)
ACRD201
10.11 (35,000)
10.11 (35,000)
ACRD200
10.92 (37,000)
10.92 (37,000)
ACRD201
10.98 (38,000)
10.98 (38,000)
Airflow is reduced to 887 l/s (1880 SCFM) at the condition below to maintain adequate evaporating temperature.
32.2°C DB, 19.0°C WB (90.0°F DB,
66.2°F WB)
ACRD200
11.64 (40,000)
11.64 (40,000)
ACRD201
11.76 (40,000)
11.76 (40,000)
Airflow is reduced to 717 l/s (1520 SCFM) at the condition below to maintain adequate evaporating temperature.
35.0°C DB, 19.9°C WB (95.0°F DB,
67.8°F WB)
ACRD200
12.00 (41,000)
12.00 (41,000)
ACRD201
12.00 (41,000)
12.00 (41,000)
Airflow is reduced to 599 l/s (1270 SCFM) at the condition below to maintain adequate evaporating temperature.
37.8°C DB, 20.7°C WB (100.0°F DB,
69.3°F WB)
ACRD200
12.06 (41,000)
12.06 (41,000)
ACRD201
12.00 (41,000)
12.00 (41,000)
Airflow is reduced to 510 l/s (1080 SCFM) at the condition below to maintain adequate evaporating temperature.
40.6°C DB, 21.6°C WB) (105.0°F DB,
70.8°F WB
ACRD200
12.06 (41,000)
12.00 (41,000)
ACRD201
12.00 (41,000)
12.00 (41,000)
Airflow is reduced to 448 l/s (950 SCFM) at the condition below to maintain adequate evaporating temperature.
43.3°C DB, 22.2°C WB) (110.0°F DB,
72.0°F WB
ACRD200
12.06 (41,000)
12.06 (41,000)
ACRD201
12.06 (41,000)
12.06 (41,000)
Airflow for the ACRD200 series is 1081 l/s (2290 SCFM) at full evaporating fan speed.
NOTE: Minimum recommended loads: ACRD200 series—2 kW (6831 BTU)
NOTE: For ACRD200 series, a 0.64 l/s (10 gpm) entering water temperature is 29.4°C (85°F).
990-5801C-001
35
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Performance at Percentage of Fan Speed
ACRD100 Series
Cooling Performance at a Target Supply Air Temperature of 20.8°C (69.5°F) when Possible
Fan Speed – %
Voltage/Ph/Hz
Air Flow – L/S
(SCFM)
Unit Power –
kW
Condenser Fan
Power – kW
Net Sensible
Capacity – kW
(BTU/h)
Supply Air
Temp – ° C (°F)
2.57
0.13
4.60 (15,710)
20.8 (69.5)
2.58
0.13
4.60 (15,710)
20.8 (69.5)
2.67
0.18
5.75 (19,637)
20.8 (69.5)
2.70
0.20
5.75 (19,637)
20.8 (69.5)
2.76
0.23
6.65 (22,711)
20.8 (69.5)
2.80
0.25
6.65 (22,711)
20.8 (69.5)
2.86
0.28
7.35 (25,102)
20.8 (69.5)
2.90
0.29
7.35 (25,102)
20.8 (69.5)
2.92
0.32
8.00 (27,321)
20.8 (69.5)
2.98
0.35
8.00 (27,321)
20.8 (69.5)
3.04
0.38
8.70 (29,712)
20.8 (69.5)
3.08
0.40
8.70 (29,712)
20.8 (69.5)
3.19
0.47
9.70 (33,127)
20.8 (69.5)
3.22
0.49
9.70 (33,127)
20.8 (69.5)
3.46
0.50
9.90 (33,810)
21.7 (71.1)
3.50
0.51
9.90 (33,810)
21.9 (71.5)
2.68
0.28
7.55 (25,785)
20.8 (69.5)
2.70
0.30
7.55 (25,785)
20.8 (69.5)
2.80
0.42
9.50 (32,444)
20.8 (69.5)
2.81
0.44
9.50 (32,444)
20.8 (69.5)
2.89
0.48
10.20 (34,835)
21.8 (71.2)
2.91
0.48
9.90 (33,810)
22.2 (71.9)
3.00
0.52
10.62 (36,269)
22.6 (72.6)
3.01
0.50
10.29 (35,142)
23.1 (73.5)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Return Air Temperature—29.4°C (85°F)
200-240/1/60
448 (950)
30
200-240/1/50
200-240/1/60
562 (1190)
40
200-240/1/50
200-240/1/60
947 (1370)
50
200-240/1/50
200-240/1/60
717 (1520)
60
200-240/1/50
200-240/1/60
779 (1650)
70
200-240/1/50
200-240/1/60
850 (1800)
80
200-240/1/50
200-240/1/60
944 (2000)
90
200-240/1/50
200-240/1/60
1081 (2290)
100
200-240/1/50
Return Air Temperature—35°C (95°F)
200-240/1/60
448 (950)
30
200-240/1/50
200-240/1/60
562 (1190)
40
200-240/1/50
200-240/1/60
947 (1370)
50
200-240/1/50
200-240/1/60
717 (1520)
60
200-240/1/50
200-240/1/60
70
N/A
200-240/1/50
200-240/1/60
80
N/A
200-240/1/50
200-240/1/60
90
N/A
200-240/1/50
200-240/1/60
100
N/A
200-240/1/50
36
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Cooling Performance at a Target Supply Air Temperature of 20.8°C (69.5°F) when Possible
Fan Speed – %
Voltage/Ph/Hz
Air Flow – L/S
(SCFM)
Unit Power –
kW
Condenser Fan
Power – kW
Net Sensible
Capacity – kW
(BTU/h)
Supply Air
Temp – ° C (°F)
2.78
0.47
10.20 (34,835)
21.3 (70.4)
2.78
0.48
10.00 (34,152)
21.6 (70.9)
2.85
0.51
10.56 (36,064)
24.8 (76.6)
2.87
0.53
10.55 (36,030)
24.8 (76.6)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Return Air Temperature—40.6°C (105°F)
200-240/1/60
448 (950)
30
200-240/1/50
200-240/1/60
562 (1190)
40
200-240/1/50
200-240/1/60
50
N/A
200-240/1/50
200-240/1/60
60
N/A
200-240/1/50
200-240/1/60
70
N/A
200-240/1/50
200-240/1/60
80
N/A
200-240/1/50
200-240/1/60
90
N/A
200-240/1/50
200-240/1/60
100
N/A
200-240/1/50
990-5801C-001
37
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
ACRD200 Series
Cooling Performance at a Target Supply Air Temperature of 20.8°C (69.5°F) when Possible
Fan Speed – %
Voltage/Ph/Hz
Air Flow – L/S
(SCFM)
Unit Power – kW
Net Sensible
Capacity – kW
(BTU/h)
Supply Air Temp –
°C (°F)
2.35
4.60 (15,710)
20.8 (69.5)
2.25
4.60 (15,710)
20.8 (69.5)
2.41
5.76 (19,671)
20.8 (69.5)
2.31
5.76 (19,671)
20.8 (69.5)
2.47
6.63 (22,643)
20.8 (69.5)
2.37
6.63 (22,643)
20.8 (69.5)
2.55
7.36 (25,136)
20.8 (69.5)
2.45
7.36 (25,136)
20.8 (69.5)
2.60
8.00 (27,321)
20.8 (69.5)
2.50
8.00 (27,321)
20.8 (69.5)
2.68
8.70 (29,712)
20.8 (69.5)
2.58
8.70 (29,712)
20.8 (69.5)
2.80
9.70 (33,127)
20.8 (69.5)
2.70
9.70 (33,127)
20.8 (69.5)
3.06
10.90 (37,225)
21.0 (69.8)
3.00
10.98 (37,499)
20.9 (69.7)
2.25
7.50 (25,614)
20.8 (69.5)
2.25
7.50 (25,614)
20.8 (69.5)
2.31
9.50 (32.444)
20.8 (69.5)
2.31
9.50 (32.444)
20.8 (69.5)
2.37
10.50 (35,859)
21.2 (70.2)
2.37
10.50 (35,859)
21.2 (70.2)
2.50
11.35 (38,762)
21.8 (71.3)
2.45
11.35 (38,762)
21.8 (71.3)
2.61
11.75 (40,128)
22.4 (72.4)
2.50
11.75 (40,128)
22.4 (72.4)
2.71
12.00 (40,982)
23.2 (73.7)
2.58
12.00 (40,982)
23.2 (73.7)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Return Air Temperature—29.4°C (85°F)
200-240/1/60
448 (950)
30
200-240/1/50
200-240/1/60
562 (1190)
40
200-240/1/50
200-240/1/60
947 (1370)
50
200-240/1/50
200-240/1/60
717 (1520)
60
200-240/1/50
200-240/1/60
779 (1650)
70
200-240/1/50
200-240/1/60
850 (1800)
80
200-240/1/50
200-240/1/60
944 (2000)
90
200-240/1/50
200-240/1/60
1081 (2290)
100
200-240/1/50
Return Air Temperature—35°C (95°F)
200-240/1/60
448 (950)
30
200-240/1/50
200-240/1/60
562 (1190)
40
200-240/1/50
200-240/1/60
947 (1370)
50
200-240/1/50
200-240/1/60
717 (1520)
60
200-240/1/50
200-240/1/60
779 (1650)
70
200-240/1/50
200-240/1/60
850 (1800)
80
200-240/1/50
200-240/1/60
90
N/A
200-240/1/50
200-240/1/60
100
N/A
200-240/1/50
38
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Cooling Performance at a Target Supply Air Temperature of 20.8°C (69.5°F) when Possible
Fan Speed – %
Voltage/Ph/Hz
Air Flow – L/S
(SCFM)
Unit Power – kW
Net Sensible
Capacity – kW
(BTU/h)
Supply Air Temp –
°C (°F)
448 (950)
2.35
10.55 36,030)
20.8 (69.5)
2.25
10.55 36,030)
20.8 (69.5)
2.40
11.70 (39,958)
22.8 (73.0)
2.31
11.70 (39,958)
22.8 (73.0)
2.46
12.00 (40,982)
24.8 (76.7)
2.37
12.00 (40,982)
24.8 (76.7)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Return Air Temperature—40.6°C (105°F)
30
200-240/1/60
200-240/1/50
40
200-240/1/60
562 (1190)
200-240/1/50
50
200-240/1/60
947 (1370)
200-240/1/50
60
200-240/1/60
N/A
200-240/1/50
70
200-240/1/60
N/A
200-240/1/50
80
200-240/1/60
N/A
200-240/1/50
90
200-240/1/60
N/A
200-240/1/50
100
200-240/1/60
200-240/1/50
990-5801C-001
N/A
39
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
ACRD600 Series (No Humidification/No Reheat)
Cooling Performance at a Target Supply Air Temperature of 20.8°C (69.5°F) when Possible
Fan Speed – %
Air Flow – L/S
(SCFM)
Unit Power – kW
Condenser Fan
Power – kW
Net Sensible
Capacity – kW
(BTU/h)
Supply Air Temp –
°C (°F)
Return Air Temperature—29.4°C (85°F)
30
600 (1200)
2.89
0.96
11.3 (38,583)
12.9 (55.2)*
40
800 (1600)
2.93
0.98
13.1 (44,729)
15.0 (59.0)*
50
900 (2000)
2.98
1.00
13.9 (47,461)
17.2 (63.0)*
60
1100 (2400)
3.12
1.02
14.5 (49,509)
18.8 (65.8)*
70
1300 (2800)
3.86
1.05
17.1 (58,387)
18.7 (65.7)
80
1500 (3200)
4.11
1.05
17.4 (59,411)
19.9 (67.8)
90
1700 (3600)
5.01
1.05
19.72 (67,332)
19.8 (67.6)
100
1900 (4000)
5.78
1.05
19.9 (67,947)
20.8 (69.4)
Return Air Temperature—35°C (95°F)
30
600 (1200)
2.88
0.99
13.4 (45,753)
15.4 (59.7)*
40
800 (1600)
2.91
1.02
14.87 (50,773)
18.7 (65.7)*
50
900 (2000)
3.54
1.05
17.9 (61,118)
19.3 (66.7)
60
1100 (2400)
4.29
1.05
20.9 (71,361)
19.8 (67.6)
70
1300 (2800)
5.14
1.05
23.6 (80,580)
20.3 (68.5)
80
1500 (3200)
6.07
1.05
26.0 (88,775)
20.8 (69.4)
90
1700 (3600)
7.09
1.05
29.2 (99,701)
20.8 (69.4)
100
1900 (4000)
9.50
1.05
32.9 (112,260)
20.8 (69.4)
Return Air Temperature—40.6°C (105°F)
30
600 (1200)
2.86
1.02
14.9 (50,875)
18.8 (65.8)*
40
800 (1600)
4.08
1.05
20.4 (69,654)
18.3 (64.9)
50
900 (2000)
4.80
1.05
23.9 (81,605)
19.7 (67.5)
60
1100 (2400)
6.36
1.05
28.7 (97,994)
19.6 (67.3)
70
1300 (2800)
7.33
1.05
31.7 (108,165)
20.8 (69.4)
80
1500 (3200)
9.19
1.05
36.1 (123,178)
20.8 (69.4)
90
1700 (3600)
11.57
1.05
40.7 (138,874)
20.8 (69.4)
100
1900 (4000)
12.47
1.05
41.9 (142,969)
22.5 (72.5)
*In this case, the compressor will cycle because its speed is down to the minimum of 25 Hz.
The minimum fan speed for the InRow mode is 30%; the minimum fan speed for HACS and RACS mode is 40%.
NOTE: Outdoor temperature is 35°C (95°F).
40
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
General Data
General Specifications—ACRD200 Series
Water Cooled
Glycol Mixture Cooled
Nominal flow rate entering the unit – l/s
(GPM)
0.64 (10.0)
0.64 (10.0)
Design entering temperature – °C (°F)
29.4 (85.0)
40.6 (105.0)
Maximum heat rejection – kW (BTU/hr)
15.2 (52,000)
15.2 (52,000)
0
40
12.8–43.3 (55.0–110.0)
12.8–43.3 (55.0–110.0)
33.1 (4.8)
43.4 (6.3)
Data
Maximum glycol percentage – %
Temperature range of fluid entering the
unit at a flow rate of 0.64 l/s (10 GPM) – °C
(°F)
Unit pressure drop at 0.64 l/s (10 GPM) –
kPa (psi)
990-5801C-001
41
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Fluid-Cooled Unit Specifications
Model
ACRD200 Series
Air System—Fan (Standard Filter Installed)
Size – mm (in.)
Air Volume – l/s (SCFM)
Fan Motor – W (HP) each
Number of Fans
200 (7.9)
1080 (2290)
115 (0.15)
6
Cooling Coil—Copper Tube/Aluminum Fin
Face Area – m2 (ft2)
Rows Deep
0.37 (3.97)
2
Filters—Washable (Standard)
Quantity
Size – mm (in.)
Depth – mm (in.)
Efficiency (%)
2
238 X 933 (9.375 X 36.75)
13 (1/2)
<20% MERV 1
Filters—Pleated (Optional)
Quantity
Size – mm (in.)
Depth – mm (in.)
Efficiency (%)
2
238 X 933 (9.375 X 36.75)
51 (2)
30% MERV 8
Physical Data
Weight – kg (lb)
199.09 (438)
Height – mm (in.)
1991 (78.39)
Width – mm (in.)
300 (11.8)
Depth – mm (in.)
1070 (42.13)
Connection Sizes
Liquid
In
7/8-in. ODF brazed
Return
7/8-in. ODF brazed
Condensate Drain
Drain Line
3/16-in. ID, 5/16-in. OD
Refrigerant
42
Type
R410A
Charge – kg (oz)
2.2 (78)
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Air-Cooled Unit Specifications
Data
Model
Value
ACRD100 series
200 (7.9)
ACRD600, ACRD600P series
400 (15.8)
ACRD100 series
1080 (2290)
ACRD600, ACRD600P series
1900 (4000)
ACRD100 series
115 (0.15)
ACRD600, ACRD600P series
1100 (1.5)
ACRD100 series
6
ACRD600, ACRD600P series
2
ACRD100 series
0.37 (3.97)
ACRD600, ACRD600P series
0.56 (6.0)
ACRD100 series
2
ACRD600, ACRD600P series
4
Air System—Fan (Standard Filter Installed)
Size – mm (in.)
Air Volume – l/s (SCFM)
Fan Motor – W (HP) each
Number of Fans
Cooling Coil—Copper Tube/Aluminum Fin
Face Area – m2 (ft2)
Rows Deep
Filters—Washable (Standard)
Quantity
2
Size – mm (in.)
238 X 933 (9.375 X 36.75)
ACRD100 series
Depth – mm (in.)
13 (1/2)
Efficiency (%)
<20% MERV 1
Filters—Pleated (Standard)
Quantity
3
Size – mm (in.)
418 x 470 (16.45 x 18.5)
ACRD600, ACRD600P series
Depth – mm (in.)
101.6 (4)
Efficiency (%)
30
Filters—Pleated (Optional)
Quantity
2
Size – mm (in.)
238 X 933 (9.375 X 36.75)
ACRD100 series
Depth – mm (in.)
51 (2)
Efficiency (%)
30% MERV 8
Filters—Pleated (Optional)
Quantity
3
Size – mm (in)
418 x 470 (16.45 x 18.5)
ACRD600, ACRD600P series
Depth – mm (in.)
Efficiency (%)
990-5801C-001
101.6 (4)
85
43
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Data
Technical Data
Model
Value
ACRD100 series
183 (404)
ACRD600
402 (886)
ACRD601/ACRD602
391 (862)
ACRD600P
413 (911)
ACRD601P/ACRD602P
402 (886)
ACRD100 series
1991 (78.39)
ACRD600, ACRD600P series
1991 (78.39)
ACRD100 series
300 (11.8)
ACRD600, ACRD600P series
600 (23.62)
ACRD100 series
1070 (42.13)
ACRD600, ACRD600P series
1070 (42.13)
ACRD100 series
1/2-in. ODF brazed
ACRD600, ACRD600P series
3/4-in. ODF brazed
ACRD100 series
1/2-in. ODF brazed
ACRD600, ACRD600P series
3/4-in. ODF brazed
ACRD100 series
3/16-in. ID, 5/16-in. OD
ACRD600, ACRD600P series
1/2
ACRD600, ACRD600P series
6.35 (1/4)
ACRD100 series
R410A (amount determined
at installation)
ACRD600, ACRD600P series
R410A (amount determined
at installation)
Flush Cycle
ACRD600P series
Automatic
Capacity – kg/hr (lb/hr)
ACRD600P series
3.0 (6.6)
kW
ACRD600P series
2.25
Physical Data
Weight – kg (lb)
Height – mm (in.)
Width – mm (in.)
Depth – mm (in.)
Connection Sizes
Refrigerant
Discharge
Liquid
Condensate Drain
Drain Line – in.
Humidifier
Supply Line – mm (in.)
Refrigerant
Type
Humidification—Solid State Electrode Canister
Reheat—Electric (Equally Loaded Three Stage, Finned Tubular, Low-watt Density)
44
Capacity – kW (BTU/hr)
ACRD600P series
6.0 (20,491)
Stages
ACRD600P series
2
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Altitude Correction Factors
Room Conditions: 22°C (72°F) DB/50%RH
Altitude – m (ft)
Specific Volume – cm3/
kg (ft3/lb)
Density –g/m3 (lb/ft3)
Density Ratio*
Capacity Correction**
0 (0)
847.77 (13.58)
1185.37 (0.074)
1.000
1.000
305 (1000)
879.61 (14.09)
1137.31 (0.071)
0.964
0.981
610 (2000)
912.70 (14.62)
1089.26 (0.068)
0.929
0.962
915 (3000)
947.66 (15.18)
1057.22 (0.066)
0.895
0.933
1219 (4000)
983.86 (15.76)
1009.16 (0.063)
0.862
0.913
1524 (5000)
1021.32 (16.36)
977.13 (0.061)
0.830
0.884
1829 (6000)
1061.28 (17.00)
945.10 (0.059)
0.799
0.865
2134 (7000)
1103.10 (17.67)
913.05 (0.057)
0.769
0.846
2438 (8000)
1146.80 (18.37)
865.00 (0.054)
0.739
0.826
2743 (9000)
1193.00 (19.11)
832.97 (0.052)
0.711
0.807
3048 (10,000)
1241.69 (19.89)
80.92 (0.050)
0.683
0.787
*Density ratio is used for air flow correction factor.
**Capacity correction is used to de-rate performance.
990-5801C-001
45
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Electrical Data
Compressor
Model
MCA**
MOP**
FLA**
LRA
RLA
Power
ACRD100—208-240 V, 1 Ph, 60 Hz
25.0
40
N/A
87.5
16.0
4.6
ACRD101—220-240 V, 1 Ph, 50 Hz
N/A
N/A
21
97.0
16.3
4.4
ACRD200—208-240 V, 1 Ph, 60 Hz
25.0
40
N/A
87.5
16.0
4.6
ACRD201—220-240 V, 1 Ph, 50 Hz
N/A
N/A
21
97.0
16.3
4.4
ACRD600—200-240 V, 3 Ph, 50/60 Hz
52.6
80
N/A
29.7*
36.6
14.6
ACRD601—460-480 V, 3 Ph, 60 Hz
24.4
40
N/A
28.1*
16.6
14.6
ACRD602—380-415 V, 3 Ph, 50/60 Hz
31.1
50
25.2
28.1*
16.6
14.6
ACRD600P—200-240 V, 3 Ph, 50/60 Hz
78.6
110
N/A
29.7*
36.6
23.5
ACRD601P—460-480 V, 3 Ph, 60 Hz
36.9
50
N/A
28.1*
16.6
23.5
ACRD602P—380-415 V, 3 Ph, 50/60 Hz
45.8
60
34.2
28.1*
16.6
23.5
NOTE: Above data is based on maximum operating condition. Evaluated at maximum allowable operating
conditions of: 39°C (102°F) DB, 11.1°C (52.0°F) DP, 46.0°C (115.0°F) ambient, 100% fan speed, 78 Hz
compressor.
NOTE: Installation must comply with national and/or local electrical codes.
NOTE: All models are hard-wired.
NOTE: Use LRA for estimation of inrush current.
* The compressor is powered by the VFD.
**Cells marked N/A indicate that this information is not required because of regional differences in electrical
codes.
46
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Sound Data
ACRD100 and ACRD200 Series Tested Sound Data
Fan Speed –
%
Fan –
RPM
Lp Sound
Pressure –dB
re: 20 µPa*
Sound Power dB at Frequency – Hz re: 10-12W
Airflow – m3/
s (SCFM)
125
250
500
1000
2000
4000
8000
dBA**
dBA
60
2300
0.66 (1400)
62.3
68.3
69.8
74.8
67.8
59.3
53.3
76.5
70.5
70
3000
0.78 (1650)
65.3
76.3
74.8
77.8
73.8
67.8
61.3
80.8
74.7
80
3450
0.85 (1800)
67.3
80.3
77.3
78.2
76.3
71.8
66.3
82.7
76.6
90
3800
0.92 (1950)
68.3
81.8
78.8
80.8
77.3
74.3
68.3
84.5
78.4
100
4300
1.08 (2290)
70.3
80.8
83.3
85.3
80.3
77.8
72.3
88.3
82.2
m3 (1000
*Weighted sound pressure dBA in a 28.3
**Based on compressor operating at full speed.
ft3)
room at 1.5 m (5-ft) distance.
ACRD600 and ACRD600P Series Air-Cooled Tested Sound Data
Fan Speed –
%
Lp Sound
Pressure –dB
re: 20 µPa*
Sound Power dB at Frequency – Hz re: 10-12W
Airflow – m3/s
(SCFM)
125
250
500
1000
2000
4000
8000
dBA**
dBA
50
0.95 (2000)
85.1
83.0
78.1
80.4
74.6
75.5
66.1
84.1
71.1
75
1.43 (3000)
89.4
84.7
86.1
83.5
78.8
76.8
68.0
88.1
75.0
100
1.89 (4000)
100.1
100.4
92.2
90.7
85.6
80.2
73.6
96.3
83.3
m3 (1000
*Weighted sound pressure dBA in a 28.3
**Based on compressor operating at full speed.
990-5801C-001
ft3)
room at 1.5 m (5-ft) distance.
47
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Dimensions and Weights
ACRD100 and ACRD200 Series
Cooling Units
)
1070 (42
1991 (78
na2231a
)
300 (12)
NOTE: Dimensions are shown in mm (in.).
Model
Packaged Weight – kg
(lb)
Unpackaged Weight –
kg (lb)
ACRD100, ACRD101
221.0 (488.0)
183.0 (404.0)
ACRD200, ACRD201
237.1 (522.7)
199.1 (438.0)
na2784a
NetShelter SX to VX Height Adapter
74.8 (
2.94)
300 (11
.8)
NOTE: Dimensions are shown in mm (in.).
48
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
265.3
na2788a
NetShelter SX to 48-U SX Height Adapter
(10.44
)
300 (1
1.8)
NOTE: Dimensions are shown in mm (in.).
ACRD600 and ACRD600P Series
Cooling Units
)
1070 (42.1
600 (23.6)
1991
(78.4)
na5811a
2156
(84.9)
879 (34.6
)
Model
990-5801C-001
)
.8
1137 (44
Net Weight – kg (lb)
Shipping Weight – kg
(lb)
ACRD600
402 (886)
447 (986)
ACRD601
391 (862)
436 (961)
ACRD602
391 (862)
436 (961)
ACRD600P
413 (911)
458 (1,010)
ACRD601P
402 (886)
447 (986)
ACRD602P
402 (886)
447 (986)
49
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
na2445a
NetShelter SX to VX Height Adapter
74.8 (
2.94)
600 (2
3.6)
NOTE: Dimensions are shown in mm (in.).
NetShelter SX to 48-U SX Height Adapter
na2446a
265.3
(10.44
)
600 (2
3.6)
NOTE: Dimensions are shown in mm (in.).
50
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Piping and Electrical Access Locations
Top Piping and Power Access Locations—Top View, Looking
Down (ACRD100 and ACRD200 Series)
REAR—HOT AISLE
88.9 (3.5)
55.1 (2.2)
85.6 (3.4)
154.6
(6.1)
109.7
(4.3)
38.2 (1.5)
na2813a
87.6
(3.4)
143.4
(5.6)
42.6 (1.7)
47.8 (1.9)
FRONT—COLD AISLE
NOTE: Dimensions are shown in mm (in.).
Item
990-5801C-001
Description
Low voltage wiring input
Electrical input
Hot gas discharge line (ACRD100 series)
Water/glycol out (ACRD200 series)
Liquid line (ACRD100 series)
Water/glycol in (ACRD200 series)
Condensate pump outlet
51
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Bottom Piping and Power Access Locations—Bottom View,
Looking Up (ACRD100 and ACRD200 Series)
REAR—HOT AISLE
102 (4.0)
88.9 (3.5)
168.8
(6.6)
122.1
(4.8)
113
(4.4)
na2814a
102.1
(4.0)
133.6
(5.3)
55.1 (2.2)
FRONT—COLD AISLE
NOTE: Dimensions are shown in mm (in.).
Item
52
Description
Electrical input
Low voltage wiring input
Liquid line (ACRD100 series)
Water/glycol in (ACRD200 series)
Condensate pump outlet
Hot gas discharge line (ACRD100 series)
Water/glycol out (ACRD200 series)
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Top Piping and Power Access Locations—Top View, Looking
Down (ACRD600, ACRD600P Series)
REAR—HOT AISLE
547 (21.54)
75 (2.95)
73 (2.86)
105 (4.12)
325 (12.78)
380 (14.94)
738 (29.04)
123 (4.84)
558 (21.97)
40 (1.58)
na2071a
47 (1.85)
FRONT—COLD AISLE
NOTE: Dimensions are shown in mm (in.).
Item
990-5801C-001
Description
Refrigerant discharge line
Refrigerant liquid line
Trough for communication cables
Power connections
Humidifier water supply (ACRD600P series only)
Condensate drain line outlet
53
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
Bottom Piping and Power Access Locations—Bottom View,
Looking Up (ACRD600, ACRD600P Series)
REAR—HOT AISLE
480 (18.90)
345 (13.58)
404 (15.91)
893 (35.16)
796 (31.34)
420 (16.54)
199 (7.84)
184 (7.24)
115 (4.53)
na5837a
57 (2.25)
140 (5.51)
178 (7.00)
FRONT—COLD AISLE
NOTE: Dimensions are shown in mm (in.).
Item
54
Description
Humidifier water supply (ACRD600P series only)
Condensate drain line outlet
Power connections
Communication connections—27.80 mm (1.09 in.)
Condensate overflow—50.00 mm (1.97 in.)
Refrigerant discharge line
Refrigerant liquid line
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
ACRD600 and ACRD600P Series
BOTTOM PIPING
TOP PIPING
na2543a
LIQUID
HOT GAS
DX
UNIT
Item
CONDENSER
LIQUID
HOT GAS
CONDENSER
RECEIVER
RECEIVER
DX
UNIT
Description
Pitch in direction of refrigerant flow; 4 mm
per m (1/2-in. per 10 ft)
Reduction of piping diameter for vertical
piping run (if necessary)
Shut-off valve
Item
Description
Check valve
P-trap
S-trap
Head pressure control valve
Inverted P-trap
Pressure relief valve
NOTE: All lines are Type L ACR copper tubing.
NOTE: Shutoff valves shown nearest to the condenser are provided in
receiver kit.
NOTE: Route piping through the top or bottom of the InRow DX.
NOTE: Trap the vertical discharge line every 6 m (20 ft) to ensure proper oil
return.
NOTE: The maximum piping run is 91 m (300 ft) equivalent length. Size the
piping pursuant to accepted refrigeration practice.
NOTE: The condenser can be placed up to 4.5 m (15 ft) below the indoor
cooling unit for equivalent line lengths of 8 m (25 ft) or less.
For Condensers Mounted Below the Level of the Indoor Unit
Piping Equivalent Length – m (ft)
Allowable Distance From Bottom of
Condenser to Bottom of Indoor Unit*
– m (ft)
91 (300)
76 (250)
61 (200)
46 (150)
30 (100)
15 (50)
8 (25)
0.3 (1)
1.5 (5)
2.1 (7)
2.7 (9)
3.3 (11)
3.9 (13)
4.5 (15)
*When condenser is installed below unit level, use 7/8 in. pipe for liquid line.
NOTE: The condenser can be placed higher than indoor cooling unit but height shall be no more than 27 m (90 ft), regardless of piping
length.
990-5801C-001
55
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Technical Data
na2765a
Water-Cooled Bottom Piping (ACRD200 Series)
Item
Description
InRow DX
Balancing valve*
Strainer, 20 mesh*
Gate valve*
Hose bib*
*Field supplied and field installed
56
990-5801C-001
Technical Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
na2766a
Glycol-Cooled Bottom Piping (ACRD200 Series)
Item
Description
Expansion tank*
Tank fill*
Fluid-cooler
Airtrol fitting*
Temperature and pressure gauges*
Air vent*
Hose bibs*
Gate valve*
Balancing valve*
Check valve
Pump package*
Flow switch
Strainer, 20 mesh*
InRow DX
*Field supplied and field installed
990-5801C-001
57
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Outdoor Heat Exchanger Data
Outdoor Heat Exchanger Data
Mechanical Data
Air-Cooled Condensers (ACRD100 Series)
Connection Size
Ambient Temp
– °C (°F)
Sound
Pressure*
Air
Quantity –
l/s (CFM)
Fan –
Qty.
Unit –
kW
ACCD75214
35.0–40.6
(95.0–105.1)
65
2380
(5,050)
1
ACCD75215
46.0
(114.8)
66
3040
(6,450)
ACCD75216
35.0–40.6
(95.0–105.1)
59
ACCD75217
46.0
(114.8)
ACCD75218
Model
Hot
Gas
Liquid
1.1
1 1/8 in.
7/8 in.
1
1.1
1 1/8 in.
2140
(4,530)
1
0.8
62
4280
(9,060)
2
35.0–40.6
(95.0–105.1)
59
2140
(4,530)
ACCD75219
46.0
(114.8)
62
ACCD75220
35.0–40.6
(95.0–105.1)
59
Capacity
Weight –
kg (lb)
MBH/1°F
TD
kW/1°C
TD
82
(180.0)
2.43
1.28
7/8 in.
118
(260.0)
4.00
2.11
22 mm
18 mm
48
(105.8)
2.35
1.24
1.6
28 mm
22 mm
89
(196.2)
4.30
2.27
1
0.6
22 mm
18 mm
48
(105.8)
2.35
1.24
4280
(9,060)
2
1.3
28 mm
22 mm
89
(196.2)
4.30
2.27
2140
(4,530)
1
0.6
22 mm
18 mm
48
(105.8)
2.35
1.24
*(dbA) at 10 ft and 100% fan speed
NOTE: ACCD75220 is CCC certified for use in China.
NOTE: ACCD75216, ACCD75217, and ACCD75218 are CMIM compliant.
58
990-5801C-001
Outdoor Heat Exchanger Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Air-Cooled Condensers (ACRD600 Series)
Model
Ambient
Temperature – °
C (°F)
Sound Pressure – (dbA)
Horizontal
Airflow
Vertical Airflow
Air Quantity – l/
s (CFM)
Fan – Qty.
Unit – kW
ACCD75228
35.0–40.6
(95.0–105.1)
67.2**
65.0**
7780 (16,672)
3
3.13
ACCD75229
46.0
(114.8)
67.2**
64.5**
7488 (16,045)
3
3.19
ACCD75230
35.0–40.6
(95.0–105.1)
67.8**
65.0**
7780 (16,672)
3
3.13
ACCD75231
46.0
(114.8)
67.8**
64.5**
7488 (16,045)
3
3.19
ACCD75232
35.0–46.0
(95.0–114.8)
60.7
56.6
5133 (11,000)
2
1.20
ACCD75232-C
35.0–46.0
(95.0–114.8)
60.7
56.6
5133 (11,000)
2
1.32
ACCD75232-40C***
–40.0–46.0
(–40.0–114.8)
60.7
56.6
5133 (11,000)
2
1.32
ACCD75233-C
35.0–46.0
(95.0–114.8)
60.7
56.6
5133 (11,000)
2
1.44
ACCD75234*
35.0–40.6
(95.0–105.1)
64
59
5400 (11,500)
1
1.45
ACCD75235*
35.0–40.6
(95.0–105.1)
64
59
5400 (11,500)
1
1.45
* Make-to-order. Additional lead times may apply.
** (dbA) is at 3 m. Note: (dbA) is at 5 m unless otherwise noted.
*** Minimum working temperature is –40°C (–40°F).
NOTE: ACCD75232-C is CMIM compliant.
Capacity
Connection Size
Weight – kg (lb)
Model
Hot Gas
Liquid
ACCD75228
7/8 in.
5/8 in.
ACCD75229
7/8 in.
ACCD75230
MBH/1°F TD
kW/1°C TD
218 (480)
5.7
3.0
5/8 in.
230 (509)
7.8
4.1
7/8 in.
5/8 in.
218 (480)
5.7
3.0
ACCD75231
7/8 in.
5/8 in.
230 (509)
7.8
4.1
ACCD75232
22 mm
16 mm
144 (318)
8.3
4.4
ACCD75232-C
22 mm
16 mm
135 (298)
8.3
4.4
ACCD75232-40C
22 mm
16 mm
135 (298)
8.3
4.4
ACCD75233-C
22 mm
16 mm
136 (300)
8.3
4.4
ACCD75234*
1 3/8 in.
1 1/8 in.
250 (550)
10.0
5.3
ACCD75235*
1 3/8 in.
1 1/8 in.
250 (550)
10.0
5.3
* Make-to-order. Additional lead times may apply.
** (dbA) is at 3 m. Note: (dbA) is at 5 m unless otherwise noted.
NOTE: ACCD75232-C is CMIM compliant.
990-5801C-001
59
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Outdoor Heat Exchanger Data
Fluid Coolers (ACRD200 Series)
Capacity
Ambient Temp
– °C (°F)
Sound
Pressure*
Air
Quantity –
l/s (CFM)
Fan –
Qty.
Unit –
kW
Connection
Size
Weight –
kg (lb)
ACFC75210
40.0 (104.0)
68
4760
(10,100)
2
2.0
1 3/8 in.
ACFC75255
35.0 (95.0)
65
2380 (5050)
1
1.0
ACFC75256
35.0 (95.0)
62
4220 (8950)
2
ACFC75257
40.0 (104.0)
56
5500
(11,650)
2
Model
MBH/1°F
TD
kW/1°C
TD
205 (450)
3.20
1.69
1 1/8 in.
150 (330)
2.36
1.24
1.6
1 1/2 in.
90 (198)
2.50
1.32
1.4
2 in.
151 (333)
3.30
1.74
*(dbA) at 10 ft and 100% fan speed
NOTE: ACFC75257 is CMIM compliant.
60
990-5801C-001
Outdoor Heat Exchanger Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Electrical Data
Air-Cooled Condensers (ACRD100 Series)
Model
Voltage, Phase,
Frequency
Receiver Model
Receiver Qty.
FLA*
MCA*
MOP*
ACCD75214
208-240V, 1 ph,
60 Hz
ACAC75009
1
4.8
15
15
ACCD75215
208-240V, 1 ph,
60 Hz
ACAC75009
2
4.8
15
15
ACCD75216
380-415V, 3 ph,
50 Hz
ACAC75009
1
1.35
N/A
N/A
ACCD75217
380-415V, 3 ph,
50 Hz
ACAC75009
1
2.7
N/A
N/A
ACCD75218
220-240V, 1 ph,
50 Hz
ACAC75009
1
3.0
N/A
N/A
ACCD75219
220-240V, 1 ph,
50 Hz
ACAC75009
1
6.0
N/A
N/A
ACCD75220
220-240V, 1 ph,
50 Hz
ACAC75009
1
3.0
N/A
N/A
* Cells marked N/A indicate that this information is not required because of regional differences in electrical codes.
NOTE: ACCD75220 is CCC certified for use in China.
NOTE: ACCD75216, ACCD75217, and ACCD75218 are CMIM compliant.
Air-Cooled Condensers (ACRD600 Series)
Model
Voltage, Phase,
Frequency
Receiver Model
Receiver Qty.
FLA*
MCA*
MOP*
ACCD75228
208-240 V, 3 ph,
60 Hz
ACAC75014
1
N/A
10.7
15
ACCD75229
208-240 V, 3 ph,
60 Hz
ACAC75014
1
N/A
10.7
15
ACCD75230
460-480 V, 3 ph,
60 Hz
ACAC75014
1
N/A
6.5
15
ACCD75231
460-480 V, 3 ph,
60 Hz
ACAC75014
1
N/A
6.5
15
ACCD75232
230 V, 1 ph, 50
Hz
ACAC75013
1
6.0
N/A
N/A
ACCD75232-C
230 V, 1 ph, 50
Hz
ACAC75015
1
6.0
N/A
N/A
ACCD7523240C
230 V, 1 ph, 50
Hz
ACAC75015
1
7.0
N/A
N/A
ACCD75233-C
230 V, 1 ph, 60
Hz
ACAC75015
1
6.0
N/A
N/A
ACCD75234*
208-240 V, 3 ph,
60 Hz
ACAC75014
1
6.4
8.8
15
ACCD75235*
460-480 V, 3 ph,
60 Hz
ACAC75014
1
2.9
4.0
15
* Make-to-order. Additional lead times may apply.
**Cells marked N/A indicate that this information is not required because of regional differences in electrical codes.
NOTE: ACCD75232-C is CMIM compliant.
990-5801C-001
61
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Outdoor Heat Exchanger Data
Fluid Coolers (ACRD200 Series)
Voltage, Phase,
Frequency
FLA*
MCA*
MOP*
ACFC75210
460 V, 3 ph, 60 Hz
2.6
15
15
ACFC75255
480 V, 3 ph, 60 Hz
1.3
15
15
ACFC75256
380-415 V, 3 ph, 50 Hz
2.7
N/A
N/A
ACFC75257
380-415 V, 3 ph, 50 Hz
2.7
N/A
N/A
Model
* Cells marked N/A indicate that this information is not required because of regional differences in electrical codes.
NOTE: ACFC75257 is CMIM compliant.
Dimensions
ACCD75234, ACCD75235
NOTE: Dimensions are shown in mm (in.).
NOTE: Make-to-order. Additional lead times may apply.
2055
(80.90
)
na6253a
1387
)
(54.62
1175
)
(46.24
1472
(57.94
)
1243
)
(48.92
ACCD75228, ACCD75229, ACCD75230, ACCD75231
NOTE: Dimensions are shown in mm (in.).
NOTE: Condensers shown have eight 22-mm (0.875 in.) mounting holes on
their lower rails.
na5853a
3151
(124.0
6)
1318
(51.88
)
1317
(51.87
)
824
)
(32.45
973
(38.3)
1003
)
3
( 9.48
62
990-5801C-001
Outdoor Heat Exchanger Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
ACCD75232
NOTE: Dimensions are shown in mm (in.).
NOTE: Condensers shown have eight 22-mm (0.875 in.) mounting holes on
their lower rails.
2167
(85.31
)
1248.5
)
(49.15
na5854a
700
)
(27.56
1000
(39.37
)
1025
(40.35
)
1050
)
4
( 1.34
1110
(43.7)
ACCD75232-C, ACCD75232-40C, ACCD75233-C
NOTE: Dimensions are shown in mm (in.).
NOTE: Condensers shown have eight 22-mm (0.875 in.) mounting holes on
their lower rails.
2090
(82.28
)
1344
)
(52.91
na5855a
700
)
2
( 7.56
1000
(39.37
)
990-5801C-001
1030
(40.55
)
1050
)
(41.34
1110
(43.7)
63
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Outdoor Heat Exchanger Data
ACCD75214
NOTE: Dimensions are shown in mm (in.).
na2891a
958
(37.71)
762
(30.00)
1085
(42.72)
ACCD75215
NOTE: Dimensions are shown in mm (in.).
na2895a
958
(37.71)
1085
(42.72)
1016
(40.00)
ACCD75216, ACCD75218, ACCD75220
NOTE: Dimensions are shown in mm (in.).
1442
(56.77)
na2893a
890
(35.04)
900
(35.43)
64
900
(35.43
990-5801C-001
Outdoor Heat Exchanger Data
ACRD100, ACRD200, ACRD600, and ACRD600P Series
ACCD75217, ACCD75219
NOTE: Dimensions are shown in mm (in.).
2222
(87.48
)
na2896a
890
)
(35.04
1680
(66.14
)
900
)
(35.43
ACFC75210
NOTE: Dimensions are shown in mm (in.).
na2890a
958
)
(37.72
1524
(60.00
)
1079
)
(42.50
ACFC75255
NOTE: Dimensions are shown in mm (in.).
na2899a
958
)
(37.72
762
(30.00
990-5801C-001
)
1079
)
(42.50
65
ACRD100, ACRD200, ACRD600, and ACRD600P Series
Outdoor Heat Exchanger Data
ACFC75256
NOTE: Dimensions are shown in mm (in.).
2222
(87.48)
na2894a
890
3
( 5.04)
1680
(66.14)
900
(35.43)
ACFC75257
NOTE: Dimensions are shown in mm (in.).
2942
(115.8
3)
na2898a
890
)
(35.04
2400
(94.50
66
)
1260
)
(49.60
990-5801C-001
Worldwide Customer Support
Customer support for this or any other product is available at no charge in any of the
following ways:
•
Visit the Schneider Electric Web site to access documents in the Schneider
Electric Knowledge Base and to submit customer support requests.
- www.schneider-electric.com (Corporate Headquarters)
Connect to localized Schneider Electric Web sites for specific countries, each of
which provides customer support information.
- www.schneider-electric.com/support/
Global support searching Schneider Electric Knowledge Base and using
esupport.
•
Contact the Schneider Electric Customer Support Center by telephone or e-mail.
Local, country-specific centers: go to www.schneider-electric.com/support/
contactwww.schneider-electric.com > Support > Operations around the
world for contact information.
For information on how to obtain local customer support, contact the representative
or other distributors from whom you purchased your product.
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.schneider-electric.com
As standards, specifications, and design change from time to time,
please ask for confirmation of the information given in this publication.
© 2016 – 2019 Schneider Electric. All rights reserved.
990-5801C-001
Was this manual useful for you? Yes No
Thank you for your participation!