- KNX- Switch Actuator REG-K/x230/10
- Operating instructions
Schneider Electric KNX- Switch Actuator REG-K/x230/10 Operating instructions
Add to My manuals2 Pages
Schneider Electric KNX- Switch Actuator REG-K/x230/10 is a powerful and versatile device that allows you to control your home or office lighting, heating, and other electrical devices with ease. With its sleek design and intuitive interface, the REG-K/x230/10 is a perfect addition to any smart home or building automation system.
advertisement
GB
Switch actuator REG-K/x230/10 with manual mode
Operating instructions
Switch actuator REG-K/4x230/10 with manual mode
Art. no. MTN649204
Switch actuator REG-K/8x230/10 with manual mode
Art. no. MTN649208
For your safety
¼
DANGER
Risk of fatal injury from electrical current.
All work on the device should only be carried out by trained and skilled electricians. Observe the country-specific regulations as well as the valid
KNX guidelines.
½
CAUTION
The device could be damaged.
- Only operate the device according to the specifications stated in the Technical data.
- All devices that are installed next to the actuator must be equipped with at least basic insulation.
Getting to know the switch actuator
The switch actuator REG-K/x230/10 with manual mode
(hereinafter referred to as actuator ) can switch
– four loads (art. no. MTN649204) or
– eight loads (art. no. MTN649208) via separate, floating make contacts.
You can switch the actuator to manual operation and check that it works even without ETS programming, and you can control the connected loads directly at the actuator in the event of a bus failure.
The actuator has a bus coupler. It is installed on a DIN rail, with the bus connection made via a bus connecting terminal. It is supplied with power from the bus voltage.
A data rail is not required.
Connections, displays and operating elements
A
J
I
B
C
D
E
F
G
H
A Bus connecting terminal
B Cable cover
C Programming button
D Programming LED (red)
E Operating LED "RUN" (green)
F Manual operation LED "Manual" (red)
G Manual operation key "Manual"
H Channel terminals for load voltage
I Channel keys for manual control of the corresponding channel, only respond when manual operation is switched on
J Channel status LEDs (yellow) for the corresponding channel
Mounting the actuator
1 Set the actuator onto the DIN rail.
1
2
2 Connect KNX.
1 2
3
3 4
5 mm
¼
DANGER
Risk of fatal injury from electrical current.
Voltage may be present at the outputs when the mains voltage is connected to the system.
If subjected to strong vibrations during transportation, the switch contacts might change to the enabled state.
After connecting the bus voltage, wait 30 seconds. The relays of the channels will be switched off. Set the relays of the channels to the position desired simply by switching "On/Off".
3 Connect the bus voltage.
4 Wait at least 30 seconds.
5 Set the relays of the channels to the position desired simply by switching "On/Off".
½
CAUTION
The actuator can be damaged.
Protect:
- Connections with a 10-A circuit breaker connected upstream. If you use separate fuses for the connections of two related switching channels, these must be on the same phase.
KNX
1 2
L L
L
L
10A
10A
10A
N
6 Connect the load
7
Connect the load voltage.
Now you can check the functionality of the actuator and the connected loads without having to load the application from the ETS. (See the "Operating the actuator" section.)
Putting the actuator into operation
1
Press the programming button.
The programming LED lights up.
2
Load the physical address and application into the device from the ETS.
The programming LED goes out.
The operating LED lights up: The application was loaded successfully, the device is ready for operation.
¼
WARNING
Risk of fatal injury from electrical current. The device could become damaged.
Safety clearance must be guaranteed in accordance with IEC 60664-1. There must be at least 4 mm between the individual cores of the
230 V supply cable and the KNX line.
230 V
4 mm
KNX
Operating the actuator
Normally, you control connected devices using pushbuttons or by remote control. However, you can also switch the actuator to manual operation and then switch each channel on and off manually using its channel keys. In order to be able to do this, the ETS parameter "Manual operation enabled" must be set to
"enabled" and mains or bus voltage must be present.
Manual operation before downloading the application for the first time
Immediately after the initial installation, you can switch the actuator to manual operation, e.g. in order to test the operation of the connected devices.
Manual operation with the ETS setting "Bus and manual operation"
In manual operation, the actuator also responds to KNX telegrams. The command last received is given priority.
Exception: Safety and security alarms always have priority with this setting.
Manual operation with the ETS setting "Manual operation only"
In manual operation, the actuator does not respond to
KNX telegrams, nor to safety alarms. This setting can be useful when carrying out maintenance, for example.
½
CAUTION
Loads could be damaged.
When operating loads in "Manual operation only" using the channel keys, prioritised safety functions (e.g. priority control) no longer work. To prevent damage, you should therefore be very careful when operating manually.
| Make sure that the ETS parameter "Manual operating mode" is set to "Bus and manual operation" ( not "Manual operation only"), when you hand over the system to the operator.
Time-limited manual operation is another function that can be set in the ETS. With this function, you can set a time period after which manual operation (including
"Manual operation only") is cancelled automatically. The actuator then responds to KNX telegrams again.
How to set the actuator to manual operation
1 Press the manual operation key.
The red manual operation LED lights up. The actuator is in manual operation.
– The green operation LED "RUN" goes out when
"Manual operation only" is set in the ETS.
– The green operation LED remains lit when "Bus and manual operation" is set in the ETS.
How to control the channels in manual operation
1 To switch channels on and off: Press the corresponding channel key.
The corresponding channel status LED lights up when the relay is closed.
How to end manual operation
1 Press the manual operation key again.
The red manual operation LED goes out. The green operation LED lights up. The actuator now only responds to KNX telegrams.
What should I do if there is a problem?
The red manual operation LED and the green operation LED are not lit. Manual operation cannot
.
be activated.
Cause Solution
Bus voltage has failed Check bus voltage
The green operation LED is not lit.
Cause Solution
Check bus voltage The bus voltage has failed.
Application was not loaded properly.
Load it again
The green operating LED does not light up, the red manual operation LED lights up.
Cause Solution
Manual operation is active and "Manual operation only" is set in the ETS. Only manual operation is possible.
There is no fault.
Switch off manual operation
Actuator does not react to the manual operation key, the red manual operation LED does not light up, manual mode is not possible.
Cause Solution
ETS parameter "Manual operation enabled" is set to "blocked". There is no fault.
"Manual operation enabled" is blocked by an object (value=0), there is no fault.
Set the "Manual operation enabled" parameter to
"enabled/enable"
Enable manual operation via object
In manual operation, the actuator does not react to the activation of the channel keys, the red manual operation LED lights up, manual mode is not possible.
Cause Solution
The green operating LED is still lit:
The ETS parameter
"Manual operating mode" is set to "Bus and manual operation", a prioritised function (e.g. block) is activated, there is no fault.
Wait until the higher-level function has been completed, or switch the
ETS parameter "Manual operation type" to
"Manual operation only".
Please refer to the safety note in the "Operating the actuator" section.
In manual operation, the actuator controls connected loads without a channel key being pressed.
Cause Solution
The ETS parameter
"Manual operating mode" is set to "Bus and manual operation". The control command for the actuator came via a KNX telegram. There is no fault.
Switch the ETS parameter
"Manual operating mode" to "Manual operation only". Please refer to the safety note in the
"Operating the actuator" section.
When and how the LEDs light up
RUN
(gree n)
On
-
Manu al
(red)
-
On
On On
Channel status
(yellow)
-
-
-
Normal operation
Manual operation
(ETS: manual operation only)
Manual operation
(ETS: bus and manual operation)
Technical data
Supply from KNX:
Nominal voltage:
Per channel
Nominal current:
DC 24 V, max. 17.5 mA
AC 230 V
10 A, ohmic cos ϕ
= 1
10 A, inductive cos ϕ
= 0.6
Capacitive load: 10 A, max. 105 µF
Incandescent lamps: AC 230 V, max. 2000 W
Halogen lamps:
LV halogen lamps with wound transformer:
AC 230 V, max. 1700 W
AC 230 V, 250 VA
Fluorescent lamps: AC 230 V, max. 1800 W uncompensated,
AC 230 V, max. 1000 W parallelcompensated
Motor load: AC 230 V, max. 1000 W
Switching frequency: max. 15 times per minute at nominal load
Fuse: per channel one 10 A circuit breaker connected upstream; only one live conductor may be used per connecting terminal
Ambient temperature
Operation:
Storage:
Transport:
-5 °C to +45 °C
-25 °C to +55 °C
Environment:
-25 °C to +70 °C can be used at up to 2000 m above sea level (MSL)
Max. humidity:
Operating elements: 1 programming button,
1 "Manual" manual operation key,
1 channel key per channel
Display elements:
93 %, no moisture condensation
1 red LED: Programming check,
1 green LED: ready for operation, "RUN",
1 red LED: manual operation status,
1 yellow status LED per channel
KNX connection:
Load connection:
Device width: two 1 mm pins for bus connecting terminal per 2 channels one plug-in 4gang screw terminal for max.
2.5 mm²
4 depth units = approx. 72 mm
Schneider Electric Industries SAS
If you have technical questions, please contact the Customer Care Center in your country. www.schneider-electric.com
This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations. As standards, specifications and designs develop from time to time, always ask for confirmation of the information given in this publication.
advertisement
Key Features
- Control up to eight loads (10 A each) via separate, floating make contacts
- Manual operation mode for easy control without ETS programming
- Priority control for loads (e.g. priority control for lighting)
- Time-limited manual operation for added flexibility
- KNX bus coupler for easy integration into KNX systems
- Compact design (4 DIN rail units) for space-saving installation