[EN]
- Instructions for use
Code LSS100200
spaceLYnk
Logic controller
KNX/Modbus/BACnet/IP
Connections and operating elements
Back view
A
B
H
Front view
C
A LED indicator 1
B LED indicator 2
C Ethernet terminal RJ45 with USB 2.0 type
D RS-485 Modbus terminal
E RS-232 terminal
F Supply 24 V DC
G KNX bus terminal
H Reset push button
D E F G
For your safety
Danger
Risk of fatal injury due to electrical current.
Any work on the device should only be carried out by qualified electricians. Please observe the country specific regulations as well as the relevant KNX guidelines.
Danger
The spaceLYnk must be supplied via a SELV and low power circuit (LPS) certified power supply, according to the
IEC 60950-1.
Getting to know
The spaceLYnk is the easiest way to visualise and program complex logic in KNX and Modbus networks.
Applications:
> Logical functions
> WEB SCADA visualization for PC and touch-devices
> Cross-standard gateway between
KNX and Modbus RTU/TCP
> BACnet Server
> Integration with third party devices over RS-232 (IR, AV)
> Scheduling
> Camera streaming
> Data logger with trends
Network configuration
Default IP configuration
Login name: admin
Password: admin
IP address on LAN 192.168.0.10
Networks mask on LAN 255.255.255.0
Please read the spaceLYnk product manual carefully for advice on how to configure and program the device properly. This product manual is available at Schneider Electric front office in your country. www.schneider-electric.com
Mounting the spaceLYnk
Warning
Risk of death from electric shock.
Mishandling of the device may cause damage. Safety clearance must be adhered to in accordance with
IEC 60664-1. There must be at least
4 mm between the individual cores of the 230 V supply cable and the KNX bus cable.
230 V
4 mm
KNX
2
1
3
1 Place the device into the DIN rail
(see picture)
2 Press down the DIN rail lock
3 Wire the device of the desired application accordingly and connect the power supply at the end
Technical data
Supply voltage 24 V DC
Power 2 W consumption
LED indicator 1 Green LED (CPU load)
LED indicator 2 Green LED (Operation)
Interface or Red LED (Reset)
1x KNX
1x10BaseT/100BaseTX
1x RS-485
(incl. polarization resistors 47 kΩ, no termination)
1x RS-232
1x USB2.0
1x Reset push button
Terminal
KNX bus Bus connecting
terminal
2 x 0.8 mm
Power supply Clamp,
0.5 mm²–1.5 mm²
Serial Clamp,
0.5 mm²–1.5 mm²
Operation -5°C to +45°C
Environment Can be used at elevations up to
2000 m above sea level (MSL)
Max. humidity 93%, no condensation
Dimension (HxWxD) 90 x 52 x 58 mm
Status LED
Procedure
Operating device
Rebooting device
Temporary settings of default IP
Press RESET < 10sec
Press RESET > 10 sec
To exit temporary settings
Press RESET < 10 sec or
Select system config ->
System -> Reboot
Factory settings of default IP passwords
& project deleted
Press RESET > 10 sec
+ Release
+ Press RESET > 10 sec
LED 1 status
Blinking Green proportionally to
CPU load
LED 2 status
Green steady ON
Steady Red
Blinking Red
Flashing Red
If you have any technical questions, please contact the customer care center for your country.