- No category
advertisement
User's Manual
DIN EN ISO 9001
Certificate: 01 100 98505
UM91001D
ZEL-4100 / 7100 / 8100 / 9100
Auto-Tune Fuzzy / PID
Process / Temperature Controller
ZESTA ENGINEERING LTD.
Warning Symbol
The Symbol calls attention to an operating procedure, practice, or the like, which, if not correctly performed or adhered to, could result in personal injury or damage to or destruction of part or all of the product and system. Do not proceed beyond a warning symbol until the indicated conditions are fully understood and met.
Use the Manual
Installers
System Designer
Expert User
Read Chapter 1, 2
Read All Chapters
Read Page 12
NOTE:
It is strongly recommended that a process should incorporate a LIMIT CONTROL like L91 which will shut down the equipment at a preset process condition in order to preclude possible damage to products or system.
Information in this user's manual is subject to change without notice.
This manual is applicable for the products with software version 23 and later version.
Copyright February 2002, ZESTA ENGINEERING LTD, all rights reserved. No part of this publication may be reproduced, transmitted, transcribed or stored in a retrieval system, or translated into any language in any form by any means without the written permission of
ZESTA ENGINEERING LTD.
2 UM91001D
Contents
Page No
Chapter 1 Overview
1-1 General ------------------------- 5
1-2 Ordering Code --------------- 8
1-3 Programming Port ------------ 9
1-4 Keys and Displays --------- 10
1-5 Menu Overview ------------- 12
1-6 Parameter Descriptions ---- 13
Chapter 2 Installation
2-1 Unpaking ------------------------- 20
2-2 Mounting ------------------------- 20
2-3 Wiring precautions --------- 22
2-4 Power Wiring ----------------- 25
2-5 Sensor Installation Guidlines — 25
2-6 Sensor Input Wiring ------- 26
2-7 Control Output Wiring ----- 26
2-8 Alarm Wiring ----------------- 30
2-9 Data Communication ------ 31
Page No
Chapter 4 Applications
4-1 Heat Only Control with Dwell Timer ---- 51
4-2 Cool Only Control ------------------------- 52
4-3 Heat-Cool Control ------------------------- 53
Chapter 5
Calibration -------- 55
Chapter 6
Specifications ---- 60
Chapter 7
Modbus Communications ---- 66
7-1 Functions Supporte --------------------------- 66
7-2 Exception Responses ------------------------- 68
7-3 Parameter Table --------------------------- 69
7-4 Data Conversion --------------------------- 73
7-5 Communication Examples ----------------- 73
Appendix
A-1 Error Codes ------------------ 76
A-2 Warranty ---------------------- 77
Chapter 3 Programming
3-1 Lockout ------------------------ 33
3-2 Signal Input ------------------- 33
3-3 Control Outputs -------------- 34
3-4 Alarm --------------------------- 39
3-5 Configure User Menu ------- 40
3-6 Ramp --------------------------- 41
3-7 Dwell Timer ------------------- 42
3-8 PV Shift ------------------------ 43
3-9 Digital Filter ------------------- 44
3-10 Failure Transfer ------------- 45
3-11 Auto-tuning ------------------ 46
3-12 Manual tuning --------------- 47
3-13 Manual Control ------------- 48
3-14 Data Communication ---- 50
3-15 PV Retransmission ------- 50
UM91001A 3
Figures & Tables
Page No
Figure 1.1 Fuzzy Control Advantage ---------------------------------------------------------------- 6
Figure 1.2 Programming Port Overview ------------------------------------------------------------ 9
Figure 1.3 Front Panel Description ----------------------------------------------------------------- 11
Figure 1.4 Display of Initial Stage ------------------------------------------------------------------- 11
Figure 2.1 Mounting Dimensions ------------------------------------------------------------------- 21
Figure 2.2 Lead Termination for ZEL - 4100, ZEL - 8100 and ZEL - 7100 ------------- 23
Figure 2.3 Lead Termination for ZEL - 9100 ------------------------------------------------------- 23
Figure 2.4 Rear Terminal Connection for ZEL - 4100 and ZEL - 8100 --------------------- 23
Figure 2.5 Rear Terminal Connection for ZEL - 7100 -------------------------------------------- 24
Figure 2.6 Rear Terminal Connection for ZEL - 9100 -------------------------------------------- 24
Figure 2.7 Power Supply Connections ------------------------------------------------------------ 25
Figure 2.8 Sensor Input Wiring ---------------------------------------------------------------------- 26
Figure 2.9 Output 1 Relay or Triac (SSR) to Drive Load --------------------------------------- 26
Figure 2.10 Output 1 Relay or Triac (SSR) to Drive Contactor ------------------------------- 27
Figure 2.11 Output 1 Pulsed Voltage to Drive SSR --------------------------------------------- 27
Figure 2.12 Output 1 Linear Current --------------------------------------------------------------- 28
Figure 2.13 Output 1 Linear Voltage --------------------------------------------------------------- 28
Figure 2.14 Output 2 Relay or Triac (SSR) to Drive Load ------------------------------------- 28
Figure 2.15 Output 2 Relay or Triac (SSR) to Drive Contactor ------------------------------- 29
Figure 2.16 Output 2 Pulsed Voltage to Drive SSR --------------------------------------------- 29
Figure 2.17 Output 2 Linear Current --------------------------------------------------------------- 29
Figure 2.18 Output 2 Linear Voltage -------------------------------------------------------------- 30
Figure 2.19 Alarm Output to Drive Load ---------------------------------------------------------- 30
Figure 2.20 Alarm Output to Drive Contactor ---------------------------------------------------- 30
Figure 2.21 RS-485 Wiring --------------------------------------------------------------------------- 31
Figure 2.22 RS-232 Wiring --------------------------------------------------------------------------- 32
Figure 2.23 Configuration of RS-232 Cable ------------------------------------------------------ 32
Figure 3.1 Conversion Curve for Linear Type Process Value --------------------------------- 34
Figure 3.2 Heat Only ON-OFF Control ------------------------------------------------------------ 35
Figure 3.3 Output 2 Deviation High Alarm -------------------------------------------------------- 38
Figure 3.4 Output 2 Process Low Alarm ---------------------------------------------------------- 38
Figure 3.5 RAMP Function --------------------------------------------------------------------------- 41
Figure 3.6 Dwell Timer Function -------------------------------------------------------------------- 42
Figure 3.7 PV Shift Application ---------------------------------------------------------------------- 43
Figure 3.8 Filter Characteristics --------------------------------------------------------------------- 44
Figure 3.9 Effects of PID Adjustment ------------------------------------------------------------- 49
Figure 4.1 Heat Control Example ------------------------------------------------------------------- 51
Figure 4.2 Cooling Control Example --------------------------------------------------------------- 52
Figure 4.3 Heat-Cool Control Example ------------------------------------------------------------ 53
Figure 5.1 RTD Calibration --------------------------------------------------------------------------- 57
Figure 5.2 Cold Junction Calibration Setup ------------------------------------------------------ 58
Table 1.1 Display Form of Characters ------------------------------------------------------------ 11
Table 3.1 Heat-Cool Control Setup Value --------------------------------------------------------- 34
Table 3.2 PID Adjustment Guide -------------------------------------------------------------------- 48
Table A.1 Error Codes and Corrective Actions -------------------------------------------------- 66
4 UM91001A
Chapter 1 Overview
1 - 1 General
The Fuzzy Logic plus PID microprocessor-based controller series, incorporate two bright, easy to read 4-digit LED displays, indicating process value and set point value. The Fuzzy Logic technology enables a process to reach a predetermined set point in the shortest time, with the minimum of overshoot during power-up or external load disturbance.
ZEL - 9100 is a 1/16 DIN size panel mount controller. It can also be used for rail mount by adding a rail mount kit . ZEL - 7100 is a
72X72 DIN size panel mount controller. ZEL - 8100 is a 1/8 DIN size panel mount controller and ZEL - 4100 is a 1/4 DIN size panel mount controller. These units are powered by 11-26 or 90-250 VDC
/VAC supply, incorporating a 2 amp. control relay output as standard. The second output can be used as cooling control, or an alarm. Both outputs can select triac, 5V logic output, linear current or linear voltage to drive external device. There are six types of alarm plus a dwell timer can be configured for the third output.The units are fully programmable for PT100 and thermocouple types J,
K, T, E, B, R, S, N, L with no need to modify the unit. The input signal is digitized by using a 18-bit A to D converter. Its fast sampling rate allows the unit to control fast processes.
Digital communications RS-485 or RS-232 ( excluding ZEL - 7100 ) are available as an additional option. These options allow the units to be integrated with supervisory control system and software.
A programming port is available for automatic configuration, calibration and testing without the need to access the keys on front panel.
By using proprietary Fuzzy modified PID technology, the control loop will minimize the overshoot and undershoot in a shortest time. The following diagram is a comparison of results with and without Fuzzy technology.
UM91001B 5
PID control with properly tuned
PID + Fuzzy control
Temperature
Set point
Warm Up Load Disturbance
High Accuracy
The series are manufactured with custom designed ASIC(Application
Specific Integrated Circuit ) technology which contains a 18-bit A to
D converter for high resolution measurement ( true 0.1 BF resolution for thermocouple and PT100 ) and a 15-bit D to A converter for linear current or voltage control output. The ASIC technology provides improved operating performance, low cost, enhanced reliability and higher density.
Time
Fast Sampling Rate
The sampling rate of the input A to D converter reaches 5 times/second.
The fast sampling rate allows this series to control fast processes.
Fuzzy Control
The function of Fuzzy control is to adjust PID parameters from time to time in order to make manipulation output value more flexible and adaptive to various processes. The results is to enable a process to reach a predetermined set point in the shortest time, with the minimum of overshoot and undershoot during power-up or external load disturbance.
Digital Communication
The units are equipped with RS-485 or RS-232 interface card to provide digital communication. By using the twisted pair wires there are at most 247 units can be connected together via RS-485 interface to a host computer.
Figure 1.1
Fuzzy Control
Advantage
6 UM91001A
Programming Port
A programming port is used to connect the unit to a hand-held programmer or a PC for quick configuration, also can be connected to an ATE system for automatic testing & calibration.
Auto-tune
The auto-tune function allows the user to simplify initial setup for a new system. A clever algorithm is provided to obtain an optimal set of control parameters for the process, and it can be applied either as the process is warming up ( cold start ) or as the process has been in steady state ( warm start ).
Lockout Protection
According to actual security requirement, one of four lockout levels can be selected to prevent the unit from being changed abnormally.
Bumpless Transfer
Bumpless transfer allows the controller to continue to control by using its previous value as the sensor breaks. Hence, the process can be well controlled temporarily as if the sensor is normal.
Soft-start Ramp
The ramping function is performed during power up as well as any time the set point is changed. It can be ramping up or ramping down. The process value will reach the set point with a predetermined constant rate.
Digital Filter
A first order low pass filter with a programmable time constant is used to improve the stability of process value. This is particularly useful in certain application where the process value is too unstable to be read.
SEL Function
The units have the flexibility for user to select those parameters which are most significant to him and put these parameters in the front of display sequence. There are at most 8 parameters can be selected to allow the user to build his own display sequence.
UM91001A 7
1 - 2 Ordering Code
ZEL - 4100 -
ZEL - 7100 -
ZEL - 8100 -
ZEL - 9100 -
Power Input
4: 90 - 250 VAC,
50/60 HZ
5: 11 - 26 VAC or
VDC
9: Special Order
Signal Input
1: Standard Input
Thermocouple:
J, K, T, E, B, R,
S, N, L
RTD: PT100 DIN,
PT100 JIS
2: 0 - 60 mV
3: 0 -1 V
4: 0 - 5 V
5: 1 - 5 V
6: 4 - 20 mA
7: 0 - 20 mA
8: 0 - 10 V
9: Special Order
Output 1
0: None
1: Relay rated 2A/240VAC
2: Pulsed voltage to drive SSR,
5V/30mA
3: Isolated 4 - 20mA / 0 - 20mA
4: Isolated 1 - 5V / 0 - 5V
5: Isolated 0 - 10V
6: Triac output 1A / 240VAC,SSR
C: Pulsed voltage to drive SSR,
14V/40mA
9: Special order
Options
0: Panel mount IP50 standard
1: Panel mount IP65 water
resistant rubber installed
2: DIN Rail mount with IP50
(for ZEL - 9100 only)
3: DIN Rail mount with IP65
(for ZEL - 9100 only)
Communications
0: None
1: RS-485 interface
2: RS-232 interface ( not
available for ZEL - 7100 )
3: Retransmit 4-20mA / 0-20mA
4: Retransmit 1-5 V / 0-5V
5: Retransmit 0-10V
9: Special order
Alarm
0: None
1: Form C relay 2A/240VAC
9: Special order
Output 2
0: None
1: Form A relay 2A/240VAC
2: Pulsed voltage to
drive SSR, 5V / 30mA
3: Isolated 4 - 20mA / 0 - 20mA
4: Isolated 1 - 5V / 0 - 5V
5: Isolated 0 - 10V
6: Triac output, 1A / 240VAC,
SSR
7: Isolated 20V/25mA
transducer power supply
8: Isolated 12V/40mA
transducer power supply
9: Isolated 5V/80mA
transducer power supply
C: Pulsed voltage to drive SSR,
14V/40mA
A: Special order
8 UM91001C
Accessories
OM94-6 = Isolated 1A / 240VAC Triac Output Module ( SSR )
OM94-7 = 14V / 40mA SSR Drive Module
OM96-3 = Isolated 4 - 20 mA / 0 - 20 mA Analog Output Module
OM96-4 = Isolated 1 - 5V / 0 - 5V Analog Output Module
OM96-5 = Isolated 0 -10V Analog Output Module
CM94-1 = Isolated RS-485 Interface Module for ZEL - 8100/4100/7100
CM94-2 = Isolated RS-232 Interface Module for ZEL - 8100/4100
CM94-3 = Isolated 4 - 20 mA / 0 - 20 mA Retrans Module for
ZEL - 8100/4100/7100
CM94-4 = Isolated 1 - 5V / 0 - 5V Retrans Module for ZEL - 8100,
ZEL - 4100 , ZEL - 7100
CM94-5 = Isolated 0-10V Retrans Module for ZEL - 8100/4100/7100
CM97-1 = Isolated RS-485 Interface Module for ZEL - 9100
CM97-2 = Isolated RS-232 Interface Module for ZEL - 9100
CM97-3 = Isolated 4-20 mA / 0-20mA Retrans Module for ZEL - 9100
CM97-4 = Isolated 1-5V / 0-5V Retrans Module for ZEL - 9100
CM97-5 = Isolated 0-10V Retrans Module for ZEL - 9100
DC94-1 = Isolated 20V/25mA DC Output Power Supply
DC94-2 = Isolated 12V/40mA DC Output Power Supply
DC94-3 = Isolated 5V/80mA DC Output Power Supply
CC94-1 = RS-232 Interface Cable ( 2M )
CC91-1 = Programming Port Cable
RK91-1 = Rail Mount kit for ZEL - 9100
Related Products
SNA10A = Smart Network Adaptor for third party software, which
converts 255 channels of RS-485 or RS-422 to RS-232
Network.
SNA10B = Smart Network Adaptor for ZE - Net software, which
converts 255 channels of RS-485 or RS-422 to RS-232
network.
SNA12A = Smart Network Adapter for programming port to RS-232
interface
ZE - Set = Configuration Software
UM91001C 8-1
1 - 3 Programming Port
Rear
Terminal
6 4 2
5 3 1
Access Hole
6 4 2
5 3 1
A special connector can be used to touch the programming port which is connected to a PC for automatic configuration, also can be connected to an ATE system for automatic calibration and testing.
The programming port is used for off-line automatic setup and testing procedures only. Don't attempt to make any connection to these pins when the unit is used for a normal control purpose.
Front
Panel
Figure 1.2
Programming Port
Overview
9 UM91001A
1 - 4 Keys and Displays
KEYPAD OPERATION
SCROLL KEY :
This key is used to select a parameter to be viewed or adjusted.
UP KEY :
This key is used to increase the value of selected parameter.
DOWN KEY :
This key is used to decrease the value of selected parameter.
RESET KEY : R
This key is used to:
1. Revert the display to display the process value.
2. Reset the latching alarm, once the alarm condition is
removed.
3. Stop the manual control mode , auto-tuning mode and calibration
mode.
4. Clear the message of communication error and auto-tuning error.
5. Restart the dwell timer when the dwell timer has been time out.
6. Enter the manual control menu during failure mode occurs.
ENTER KEY : Press for 5 seconds or longer .
Press for 5 seconds to:
1. Ener setup menu. The display shows .
2. Enter manual control mode during manual control mode
is selected.
3. Enter auto-tuning mode during auto-tuning mode is
selected.
4. Perform calibration to a selected parameter during the
calibration procedure.
Press for 6.2 seconds to select manual control mode.
Press for 7.4 seconds to select auto-tuning mode.
Press for 8.6 seconds to select calibration mode.
UM91001D 10
Alarm
Indicator
Output 2
Indicator
Output 1
Indicator
OP1 OP2 ALM
Upper Display, to display process value, menu symbol and error code etc.
Process Unit Indicator
C F
Manual
Mode
Indicator
Auto-tuning
Indicator
MAN
AT
Lower Display, to display set point value, parameter value or control output value etc.
ZESTA
R
ZEL - 9100
Figure 1.3 Front Panel Description
4 Buttons for ease of control setup and set point adjustment.
Table 1.1 Display Form of Characters
A
B
C c
D
E
F
G
H h
I
J
K
L
M
N
O
P
Q
R
: Confused Character
S
T
U
V
W
X
Y
Z
?
=
OP1 OP2 ALM
MAN
AT
C F
Display program code of the product for 2.5 seconds.
The left diagram shows program no. 6 for ZEL - 9100 with version 24.
The program no. for ZEL - 7100 is 13, for ZEL - 8100 is 11 and for ZEL - 4100 is 12.
R
ZEL - 9100
Figure 1.4
Display of Initial Stage
11
ZESTA
UM91001D
1 - 5 Menu Overview
User menu
Setup menu
Manual
Mode
Auto-tuning
Mode
Calibration
Mode
PV, SV
5 sec.
*2
SP2
SP3
INPT
UNIT
DP
PB
TI
TD
CYC1
ADDR
*1
BAUD
DATA
PARI
STOP
RELO
REHI
SEL1
SEL2
CPB
DB
ALFN
ALMD
ALHY
ALFT
COMM
ADDR
SEL3
SEL4
SEL5
SEL6
SEL7
SEL8
TD
OUT1
O1TY
O1FT
O1HY
CYC1
OFST
RAMP
RR
OUT2
O2TY
O2FT
O2HY
CYC2
LOCK
INPT
UNIT
DP
INLO
INHI
SP1L
SP1H
SHIF
FILT
PB
TI
6.2 sec.
H_ _ _
C_ _ _
7.4 sec.
Press for 5 seconds to start manual control.
Release then press for 5 seconds to start auto-tuning mode.
8.6 sec.
*3
ADLO
ADHI
RTDL
RTDH
CJLO
CJHI
9.8 sec.
Press for
5 seconds to perform calibration.
Apply these modes will break the control loop and change some of the previous setting data. Make sure that if the system is allowable to apply these modes.
*1: The flow chart shows a complete listing of all parameters. For actual application the number of available parameters depends on setup conditions, and should be less than that shown in the flow chart.
*2:
You can select at most 8 parameters put in the user menu by using SEL1~SEL8 contained at the bottom of setup menu.
*3: Release , press again for 2 seconds or longer (but not longer than 3 seconds), then release to enter the calibration menu.
The user menu shown in the flow chart is corresponding to the default setting for the SEL parameters SEL1 to SEL8. SP3 will be hidden if NONE is selected for
ALFN. SP2 will be hidden if alarm function is not selected for OUT2. The unused parameter will be hidden even if it is selected by SEL parameters.
UM91001D 12
1 - 6 Parameter Descriptions
Parameter
Notation
SP1
SP2
SP3
Parameter Description
Set point for output 1
Set point for output 2 when output 2 performs alarm function
Set point for alarm or dwell timer output
LOCK
INPT
13
Select parameters to be locked
Input sensor selection
Range
Low: SP1L High :SP1H
Low: -19999 High :45536
Low: -19999 High: 45536
4
5
6
2
3
0
1
7
8
9
0 : No parameter
is locked
1 : Setup data are
locked
2 : Setup data and
User data except Set
point are locked
3 : All data are locked
10
11
12
13
14
15
16
17
:
:
:
:
:
:
:
:
J type thermocouple
K type thermocouple
T type thermocouple
E type thermocouple
B type thermocouple
R type thermocouple
S type thermocouple
N type thermocouple
: L type thermocouple
:
:
PT 100 ohms DIN curve
PT 100 ohms JIS curve
:
:
:
:
:
4 - 20 mA linear current input
0 - 20 mA linear current input
:
: 0 - 60 mV linear millivolt input
0 - 1V linear voltage input
0 - 5V linear voltage
input
1 - 5V linear voltage
input
0 - 10V linear voltage
input
UM91001A
Default
Value
25.0 BC
(77.0BF)
10.0 BC
(18.0BF)
10.0 BC
(18.0 BF)
0
1
(0)
Parameter
Notation
UNIT
DP
INLO
INHI
SP1L
SP1H
SHIF
FILT
Parameter Description
Input unit selection
Decimal point selection
Input low sale value
Input high scale value
Low limit of set point value
High limit of set point value
PV shift (offset) value
Filter damping time constant of PV
Range
Default
Value
0
1
2
0
:
:
: Degree C unit
Degree F unit
Process unit
:
:
: No decimal point
1 decimal digit
2 decimal digits
0
(1)
1
2
1
3 : 3 decimal digits
Low:
Low:
Low:
-19999
INLO+50
-19999
High:
High:
High:
45486
45536
45536
Low: SP1L High: 45536
Low:
-200.0 LC
(-360.0 LF)
0 :
1
2
3
4
5
6
7
8
9
:
:
:
:
:
:
:
:
:
High:
200.0 LC
( 360.0 LF)
0 second time
constant
0.2 second time
constant
0.5 second time constant
1 second time constant
2 seconds time constant
5 seconds time constant
10 seconds time constant
20 seconds time constant
30 seconds time constant
60 seconds time constant
-17.8 LC
( 0 LF )
93.3 LC
(200.0 LF)
-17.8 LC
(0 LF)
537.8 LC
(1000 LF)
0.0
2
UM91001A 14
Parameter
Notation
TI
TD
CYC1
OFST
15
PB
OUT1
O1TY
O1FT
O1HY
RAMP
Parameter Description
Proportional band value
Integral time value
Derivative time value
Low: 0
Low: 0
Low: 0
Range
500.0 LC
(900.0 LF)
High: 1000 sec
High: 360.0 sec
Output 1 function
Output 1 signal type
Output 1 failure transfer mode
0
1
0
1
2
:
: Reverse (heating ) control action
Direct (cooling) control action
: Relay output
: Solid state relay
drive output
: Solid state relay
output
3 : 4-20 mA current
module
4
5
6
7
8
: 0 - 20 mA current
module
:
:
0 - 1V voltage
module
0 - 5V voltage
module
:
:
1 - 5V voltage
module
0 - 10V voltage
module
Select BPLS ( bumpless transfer ) or 0.0 ~ 100.0 % to continue output 1 control function as the unit fails, or select OFF (0) or ON (1) for ON-OFF control.
Output 1 ON-OFF control hysteresis
Low: 0.1 High: 50.0 BC(90.0BF)
Output 1 cycle time
Offset value for P control
Ramp function selection
Low: 0.1 High: 90.0 sec.
Low: 0 High: 100.0 %
0 : No Ramp Function
1 : Use unit/minute as
Ramp Rate
2 : Use unit/hour as
Ramp Rate
UM91001A
Default
Value
10.0 LC
(18.0 LF)
100
25.0
0
0
0
0.1LC
(0.2LF)
18.0
25.0
0
Parameter
Notation
RR
Parameter Description
Ramp rate
OUT2
O2TY
O2FT
Output 2 function
Output 2 signal type
Output 2 failure transfer mode
Low: 0
Range
High:
500.0 LC
(900.0 LF)
0 : Output 2 No Function
2 : Deviation High Alarm
3 : Deviation Low Alarm
6 : Process High Alarm
7 : Process Low Alarm
8 : Cooling PID Function
0 : Relay output
1
2
3
4
5
6
7
8
:
:
:
:
:
:
:
: Solid state relay drive output
Solid state relay output
4 - 20 mA current module
0 - 20 mA current module
0 - 1V voltage module
0 - 5V voltage module
1 - 5V voltage module
0 - 10V voltage module
Select BPLS ( bumpless transfer ) or 0.0 ~ 100.0 % to continue output 2 control function as the unit fails, or select ON (0) or
OFF (1) for alarm function.
O2HY
CYC2
CPB
Output 2 hysteresis value when output 2 performs alarm function
Output 2 cycle time
Cooling proportional band value
Low: 0.1
Low: 0.1
Low: 50
High: 90.0 sec.
High: 300 %
UM91001A
Default
Value
0.0
2
0
0
0.1 LC
(0.2 LF)
18.0
100
16
Parameter
Notation
DB
Parameter Description
Heating-cooling dead band (negative value= overlap)
ALFN
ALMD
ALHY
ALFT
COMM
Alarm function for alarm output
Alarm operation mode
Hysteresis control of alarm
Alarm failure transfer mode
Communication
function
Low: -36.0
Range
High: 36.0 %
Default
Value
0
0 :No alarm function
1 :Dwell timer action
2 :Deviation high alarm
3 :Deviation low alarm
4 :Deviation band out of
band alarm
5 :Deviation band in
band alarm
6 :Process value high
alarm
7 :Process value low
alarm
0
1
2
3
:
:
:
Normal alarm action
Latching alarm action
Hold alarm action
:
Latching & Hold action
Low: 0.1
0
1 :
: Alarm output ON as unit fails
Alarm output OFF as unit fails
0 : No communication
1 : Modbus RTU mode
protocol
2
3
4
5
6
:4-20mA retransmission
output
:0-20mA retransmission
output
:0-5V retransmission
output
:1-5V retransmission
output
:0-10V retransmission
output
2
0
0.1 LC
(0.2 LF)
0
1
17 UM91001D
Parameter
Notation
ADDR
Parameter Description
Address assignment of digital communication
BAUD
DATA
Baud rate of digital communication
Data bit count of digital communication
Range
Low: 1 High: 255
5
6
3
4
0
1
2
:
:
:
:
:
:
:
2.4 Kbits/s baud rate
4.8 Kbits/s baud rate
9.6 Kbits/s baud rate
14.4 Kbits/s baud rate
19.2 Kbits/s baud rate
28.8 Kbits/s baud rate
38.4 Kbits/s baud rate
0 : 7 data bits
1 : 8 data bits
PARI
Parity bit of digital communication
0 : Even parity
1 : Odd parity
2 : No parity bit
Default
Value
2
1
0
STOP
RELO
REHI
Stop bit count of digital communication
Retransmission low scale value
Retransmission high scale value
SEL1
Select 1'st parameter for user menu
0 : One stop bit
1 : Two stop bits
Low: -19999 High: 45536
Low: -19999 High: 45536
3
4
5
6
0
1
2
7
UM91001D
: No parameter selected
:LOCK is put ahead
:INPT is put ahead
:UNIT is put ahead
:DP is put ahead
:SHIF is put ahead
:PB is put ahead
:TI is put ahead
0
0.0 LC
(32.0 LF)
100.0 LC
(212.0 LF)
2
18
Prameter
Notation
Parameter Description
SEL1
Select 1'st parameter for user menu
8
9
10
11
17
18
14
15
16
12
13
SEL2
SEL3
SEL4
SEL5
SEL6
SEL7
SEL8
Select 2'nd parameter for user menu
Select 3'rd parameter for user menu
Select 4'th parameter for user menu
Select 5'th parameter for user menu
Select 6'th parameter for user menu
Select 7'th parameter for user menu
Select 8'th parameter for user menu
Same as SEL1
Same as SEL1
Same as SEL1
Same as SEL1
Same as SEL1
Same as SEL1
Same as SEL1
Range
:TD is put ahead
: O1HY is put ahead
: CYC1 is put ahead
: OFST is put ahead
:RR is put ahead
:O2HY is put ahead
:CYC2 is put ahead
:CPB is put ahead
:DB is put ahead
:ADDR is put ahead
:ALHY is put ahead
Default
Value
2
6
7
8
10
17
3
4
19 UM91001A
Chapter 2 Installation
Dangerous voltages capable of causing death are sometimes present in this instrument.
Before installation or beginning any cleaning or troubleshooting procedures the power to all equipment must be switched off and isolated. Units suspected of being faulty must be disconnected and removed to a properly equipped workshop for testing and repair. Component replacement and internal adjustments must be made by a qualified maintenance person only.
This instrument is protected throughout by Double Insulation . To minimize the possibility of fire or shock hazards, do not expose this instrument to rain or excessive moisture.
Do not use this instrument in areas under hazardous conditions such as excessive shock, vibration, dirt, moisture, corrosive gases or oil. The ambient temperature of the areas should not exceed the maximum rating specified in Chapter 6.
Remove stains from this instrument using a soft, dry cloth. Don't use harsh chemicals, volatile solvent such as thinner or strong detergents to clean the instrument in order to avoid deformation or discoloration.
2 - 1 Unpacking
Upon receipt of the shipment remove the unit from the carton and inspect the unit for shipping damage.
If any damage due to transit , report and claim with the carrier.
Write down the model number, serial number, and date code for future reference when corresponding with our service center. The serial number (S/N) and date code (D/C) are labeled on the box and the housing of control.
2 - 2 Mounting
Make panel cutout to dimension shown in Figure 2.1.
Take both mounting clamps away and insert the controller into panel cutout. Install the mounting clamps back. Gently tighten the screws in the clamp till the controller front panels is fitted snugly in the cutout.
UM91001B 20
Figure 2.1 Mounting Dimensions
Panel Cutout
92 mm
Panel
53 mm
ZEL-4100
Panel
Cutout
45 mm
ZEL-8100
Panel
65 mm
21
Panel Cutout
68 mm
Panel
65 mm
UM91001A
ZEL-7100
Panel
45 mm
Panel
Cutout
ZEL-9100
Panel Mount
11.5mm
104.8mm
7.5mm
48.0mm
11.5mm
104.8mm
2 - 3 Wiring Precautions
* Before wiring, verify the label for correct model number and options. Switch off the power while checking.
* Care must be taken to ensure that maximum voltage rating specified on the label are not exceeded.
* It is recommended that power of these units to be protected by fuses or circuit breakers rated at the minimum value possible.
* All units should be installed inside a suitably grounded metal enclosure to prevent live parts being accessible from human hands and metal tools.
* All wiring must conform to appropriate standards of good practice and local codes and regulations. Wiring must be suitable for voltage, current, and temperature rating of the system.
* Beware not to over-tighten the terminal screws. The torque should not exceed 1 N-m ( 8.9 Lb-in or 10.2KgF-cm ).
62.0mm
ZEL-9100
Rail Mount
6.5mm
UM91001D 22
*
Unused control terminals should not be used as jumper points as they may be internally connected, causing damage to the unit.
* Verify that the ratings of the output devices and the inputs as specified in Chapter 6 are not exceeded.
*
Except the thermocouple wiring, all wiring should use stranded copper conductor with maximum gauge 18 AWG.
3.2mm min.
7.0mm max.
Figure 2.2 Lead Termination for
ZEL-4100, ZEL-8100
and ZEL-7100
6.0mm max.
Figure 2.3 Lead Termination
for ZEL-9100
3.0mm min.
90-250VAC
47-63 Hz
12VA
OP1
OP2
ALM
CAT. I I
_
_
5
6
7
8
3
4
1
2
L
C
N
NO
C
NO
C
NO
9 NC
10
11
12
RE+ TX1 TXD 13
RE TX2 RXD 14
COM 15
PTA
TC+, V+
PTB, mA+
TC-, V-
PTB, mA-
16
17
18
19
20
RS-485
RETRANSMISSION
RS-232
50LC max. air ambient
Use copper conductors
(except on T/C input )
A
RTD
B
_ _
V _
TC V mA RTD
B
Figure 2.4 Rear Terminal Connection
for ZEL-4100 and ZEL-8100
23 UM91001D
90-250VAC
47-63 Hz
12VA
1 L 8
_
OP1
CAT. I I
2 N 9
3 RE + 10 TX1
RS-485 or
RETRANSMISSION
ALM
4 RE 11
TX2
PTA
A
OP2
_
5
6
7
TC+, V+
PTB, mA+
TC-, V-
PTB, mA-
12
13
14
_ _
V _
RTD
TC V mA RTD
50LC max. air ambient
Use copper conductors (except on T/C input )
B
B
Figure 2.5
Rear Terminal Connection for ZEL-7100
RETRANSMISSION:
RS-232:
RS-485:
RE + RE -
TXD RXD
TX1 TX2
COM
13 14 15
I
ALM
B
V
_
B
A
RTD
_
1
2
3
4
5
6
NO
NC
C
PTA
TC+, V+
PTB, mA+
TC-, V-
PTB, mA-
L
N
7
8
C 9
NO
50LC max. air ambient
Use copper conductors (except on T/C input )
Figure 2.6
Rear Terminal Connection for ZEL-9100
10
C 11
NO 12
CAT. I I
_
90-250VAC
47-63 Hz
12VA
_
OP1
OP2
UM91001B 24
2 - 4 Power Wiring
The controller is supplied to operate at 11-26 VAC / VDC or 90-250
VAC. Check that the installation voltage corresponds with the power
rating indicated on the product label before connecting power to
the controller. Near the controller a fuse and a switch rated at
2A/250VAC should be equiped as shown in the following diagram.
ZEL-4100
ZEL-7100
ZEL-8100
L
N
1
2
ZEL-9100
L
N
7
8
Fuse
2A/250VAC
~
~
Figure 2.7 Power Supply Connections
This equipment is designed for installation in an enclosure which provides adequate protection against electric shock. The enclosure must be connected to earth ground.
Local requirements regarding electrical installation should be rigidly observed. Consideration should be given to prevent from unauthorized person access to the power terminals.
2 - 5 Sensor Installation Guidelines
Proper sensor installation can eliminate many problems in a control system. The probe should be placed so that it can detect any temperature change with minimal thermal lag. In a process that requires fairly constant heat output, the probe should be placed closed to the heater. In a process where the heat demand is variable, the probe should be closed to the work area. Some experiments with probe location are often required to find this optimum position.
In a liquid process, addition of a stirrer will help to eliminate thermal lag. Since the thermocouple is basically a point measuring device, placing more than one thermocouple in parallel can provide an average temperature readout and produce better results in most air heated processes.
25 UM91001B
Proper sensor type is also a very important factor to obtain precise measurements. The sensor must have the correct temperature range to meet the process requirements. In special processes the sensor might need to have different requirements such as leak-proof, antivibration, antiseptic, etc.
Standard sensor limits of error are A4 degrees F (A 2 degrees C ) or 0.75% of sensed temperature (half that for special ) plus drift caused by improper protection or an over-temperature occurrence.
This error is far greater than controller error and cannot be corrected on the sensor except by proper selection and replacement.
2 - 6 Sensor Input Wiring
PTA
TC+, V+
PTB, mA+
TC-, V-
ZEL-4100
ZEL-8100 ZEL-7100 ZEL-9100
PTB, mA-
18
19
20
12
13
14
4
5
6
A
RTD
B
_ _
V _
TC V MA RTD
B
Figure 2.8 Sensor Input Wiring
2 - 7 Control Output Wiring
ZEL-4100
ZEL-8100 ZEL-7100 ZEL-9100
LOAD
_
3
4
8
9
9
10
120V/240VAC
Mains Supply
Figure 2.9
Output 1 Relay or Triac (SSR) to Drive Load
UM91001A 26
ZEL-4100
ZEL-8100 ZEL-7100 ZEL-9100
_
3
4
8
9
9
10
120V /240V
Mains Supply
Three
Phase
Heater
Power
Three Phase
Delta
Heater
Load
Contactor
No Fuse
Breaker
Figure 2.10
Output 1 Relay or Triac (SSR) to Drive Contactor
ZEL-4100
ZEL-8100 ZEL-7100 ZEL-9100
3
4
8
9
9
10 _
SSR
_
Load
120V /240V
Mains Supply
30mA / 5V
Pulsed
Voltage
Internal Circuit
5V
33
33
0V
+
Figure 2.11 Output 1 Pulsed Voltage to Drive SSR
27 UM91001A
ZEL-4100
ZEL-8100 ZEL-7100 ZEL-9100
3
4
8
9
9
10
0 - 20mA,
4 - 20mA
Load
_
Maximum Load
500 ohms
Figure 2.12 Output 1 Linear Current
ZEL-4100
ZEL-8100 ZEL-7100 ZEL-9100
3
4
8
9
9
10
0 - 1V, 0 - 5V
1 - 5V, 0 - 10V
Load
_
Minimum Load
10 K ohms
Figure 2.13 Output 1 Linear Voltage
ZEL-4100
ZEL-8100 ZEL-7100 ZEL-9100
_
5
6
6
7
11
12
Load
120V/240VAC
Mains Supply
Figure 2.14
Output 2 Relay or Triac (SSR) to Drive Load
UM91001A 28
ZEL-4100
ZEL-8100 ZEL-7100 ZEL-9100
_
5
6
6
7
11
12
120V /240V
Mains Supply
Three Phase
Delta
Heater
Load
Contactor
No Fuse
Breaker
Figure 2.15
Output 2 Relay or Triac (SSR) to Drive Contactor
Three
Phase
Heater
Power
ZEL-4100
ZEL-8100 ZEL-7100 ZEL-9100
5
6
6
7
11
12 _
SSR
_
Load
120V /240V
Mains Supply
30mA / 5V
Pulsed
Voltage
Internal Circuit
5V
33
33
0V
+
Figure 2.16 Output 2 Pulsed Voltage to Drive SSR
29
ZEL-4100
ZEL-8100 ZEL-7100 ZEL-9100
5
6
6
7
11
12
0 - 20mA,
4 - 20mA
Load
_
Figure 2.17 Output 2 Linear Current
Maximum Load
500 ohms
UM91001A
ZEL-4100
ZEL-8100 ZEL-7100 ZEL-9100
5
6
6
7
11
12
0 - 1V, 0 - 5V
1 - 5V, 0 - 10V
Load
_
Minimum Load
10 K ohms
Figure 2.18 Output 2 Linear Voltage
2 - 8 Alarm Wiring
ZEL-4100
ZEL-8100 ZEL-7100 ZEL-9100
7
8
9
3
4
5
3
1
2
Load
120V/240VAC
Mains Supply
Figure 2.19 Alarm Output to Drive Load
ZEL-4100
ZEL-8100 ZEL-7100 ZEL-9100
7
8
9
3
4
5
3
1
2
120V /240V
Mains Supply
Three Phase
Delta
Heater
Load
Contactor
No Fuse
Breaker
Relay Output to
Drive Contactor
Figure 2.20 Alarm Output to Drive Contactor
Three
Phase
Heater
Power
UM91001A 30
2 - 9 Data Communication
ZEL-4100
ZEL-8100
ZEL-9100
TX1
TX2
13
14
ZEL-7100
10
11
TX1
TX2
Twisted-Pair Wire
ZEL-4100
ZEL-8100
ZEL-9100 ZEL-7100
TX1
TX1 13 10
TX2 14 11
TX2
RS-485 to RS-232 network adaptor
SNA10A or
SNA10B
TX1
TX2
RS-232
PC
31
Max. 247 units can be linked
ZEL-4100
ZEL-8100
ZEL-9100
TX1
TX2
13
14
ZEL-7100
10
11
TX1
TX2
Terminator
220 ohms / 0.5W
Figure 2.21 RS-485 Wiring
UM91001A
RS-232
ZEL-4100
ZEL-8100
ZEL-9100
TXD
RXD
COM
13
14
15
PC
9-pin
RS-232 port
CC94-1
Figure 2.22
RS-232 Wiring
If you use a conventional 9-pin RS-232 cable instead of CC94-1, the cable must be modified according to the following circuit diagram.
To DTE ( PC ) RS-232 Port
ZEL-4100
ZEL-8100
ZEL-9100
TXD
RXD
13
14
COM 15
TX1
TX2
COM
RD
TD
GND
3
4
5
1
2
6
7
8
9
Female DB-9
Figure 2.23
Configuration of RS-232 Cable
1 DCD
2 RD
3 TD
4 DTR
5 GND
6 DSR
7 RTS
8 CTS
9 RI
UM91001A 32
Chapter 3 Programming
Press for 5 seconds and release to enter setup menu. Press to select the desired parameter. The upper display indicates the parameter symbol, and the lower display indicates the selected value of parameter.
3 - 1 Lockout
There are four security levels can be selected by using LOCK parameter.
If NONE is selected for LOCK, then no parameter is locked.
If SET is selected for LOCK, then all setup data are locked.
If USER is selected for LOCK, then all setup data as well as user data
(refer to section 1-5) except set point are locked to prevent from being changed.
If ALL is selected for LOCK, then all parameters are locked to prevent from being changed.
3 - 2 Signal Input
INPT: Selects the sensor type or signal type for signal input.
Range: ( thermocouple ) J_TC, K_TC, T_TC, E_TC, B_TC, R_TC
S_TC, N_TC, L_TC
( RTD ) PT.DN, PT.JS
(linear ) 4-20, 0-20, 0-60, 0-1V, 0-5V, 1-5V, 0-10
UNIT: Selects the process unit
Range: LC, LF, PU( process unit ). If the unit is neither LC nor LF,
then selects PU.
DP: Selects the resolution of process value.
Range: ( for T/C and RTD ) NO.DP, 1-DP
(for linear ) NO.DP, 1-DP, 2-DP, 3-DP
INLO: Selects the low scale value for the linear type input.
INHI : Selects the high scale value for the linear type input.
How to use INLO and INHI :
If 4 - 20 mA is selected for INPT,let SL specifies the input signal low
( ie. 4 mA ), SH specifies the input signal high ( ie. 20 mA ), S specifies the current input signal value, the conversion curve of the process value is shown as follows :
33 UM91001D
process value
INHI
PV
Figure 3.1
Conversion Curve for
Linear Type Process Value
INLO input signal
SL S SH
Formula : PV = INLO + ( INHI - INLO )
S - SL
SH - SL
Example : A 4-20 mA current loop pressure transducer with range
0 - 15 kg/cm is connected to input, then perform the
INPT = 4 - 20 INLO = 0.00
INHI = 15.00 DP = 2-DP
Of course, you may select other value for DP to alter the resolution.
3 - 3 Control Outputs
There are 4 kinds of control modes can be configured as shown in Table 3.1
Table 3.1 Heat-Cool Control Setup Value
Control
Modes
Heat only
Cool only
Heat: PID
Cool: ON-OFF
Heat: PID
Cool: PID
OUT1
REVR
DIRT
REVR
REVR
: Don't care
: Adjust to met process
requirements
OUT2
DE.HI
COOL
O1HY O2HY CPB
: Required if ON-OFF control
is configured
DB
UM91001A 34
Heat Only ON-OFF Control : Select REVR for OUT1, Set PB to 0,
O1HY is used to adjust dead band for ON-OFF control, The output 1 hysteresis ( O1HY ) is enabled in case of PB = 0 . The heat only on-off control function is shown in the following diagram :
PV
SP1
Dead band = O1HY
SP1 - O1HY
OUT1 Action
Time
ON
OFF
Time
Figure 3.2 Heat Only
ON-OFF Control
The ON-OFF control may introduce excessive process oscillation even if hysteresis is minimized to the smallest. If ON-OFF control is set ( ie.
PB = 0 ), TI, TD, CYC1, OFST, CYC2, CPB, DB will be hidden and have no function to the system. The auto-tuning mode and bumpless transfer will be disabled too.
Heat only P ( or PD ) control : Select REVR for OUT1, set TI to 0,
OFST is used to adjust the control offset ( manual reset ). O1HY is hidden if PB is not equal to 0. OFST Function : OFST is measured by
% with range 0 - 100.0 %. In the steady state ( ie. process has been stabilized ) if the process value is lower than the set point a definite value, say 5 LC, while 20 LC is used for PB, that is lower 25 %, then increase OFST 25 %, and vice versa.
35 UM91001A
After adjusting OFST value, the process value will be varied and eventually, coincide with set point. Using the P control ( TI set to 0 ), the auto-tuning is disabled. Refer to section 3-12 " manual tuning " for the adjustment of PB and TD. Manual reset ( adjust OFST ) is not practical because the load may change from time to time and often need to adjust
OFST repeatedly. The PID control can avoid this situation.
Heat only PID control : Selecting REVR for OUT1, PB and TI should not be zero. Operate auto-tuning for the new process, or set PB, TI and TD with historical values. See section 3-11 for auto-tuning operation. If the control result is still unsatisfactory, then use manual tuning to improve the control . See section 3-12 for manual tuning. The unit contains a very clever PID and Fuzzy algorithm to achieve a very small overshoot and very quick response to the process if it is properly tuned.
Cool only control:ON-OFF control, P ( PD ) control and PID control can be used for cool control. Set OUT1 to DIRT ( direct action ). The other functions for cool only ON-OFF control, cool only P ( PD ) control and cool only PID control are same as descriptions for heat only control except that the output variable
( and action ) for the cool control is inverse to the heat control.
NOTE :
The ON-OFF control may result excessive overshoot and undershoot problems in the process. The P ( or PD ) control will result in a deviation process value from the set point. It is recommended to use PID control for the Heat-Cool control to produce a stable and zero offset process value.
Other Setup Required : O1TY, CYC1, O2TY, CYC2, O1FT, O2FT
O1TY & O2TY are set in accordance with the types of OUT1 & OUT2 installed. CYC1 & CYC2 are selected according to the output 1 type
( O1TY ) & output 2 type ( O2TY ). Generally, selects 0.5 ~ 2 sec. for
CYC1, if SSRD or SSR is used for O1TY; 10 ~ 20 sec. if relay is used for O1TY, and CYC1 is ignored if linear output is used. Similar condition is applied for CYC2 selection.
UM91001A 36
You can use the auto-tuning program for the new process or directly set the appropriate values for PB, TI & TD according to the historical records for the repeated systems. If the control behavior is still inadequate, then use manual tuning to improve the control. See section 3-12 for manual tuning.
CPB Programming : The cooling proportional band is measured by % of PB with range
50~300. Initially set 100% for CPB and examine the cooling effect. If cooling action should be enhanced then decrease CPB, if cooling action is too strong then increase CPB. The value of
CPB is related to PB and its value remains unchanged throughout the auto-tuning procedures.
Adjustment of CPB is related to the cooling media used. For air is used as cooling media, adjust
CPB at 100(%).For oil is used as cooling media, adjust CPB at 125(%). For water is used as cooling media, adjust CPB at 250(%).
DB Programming: Adjustment of DB is dependent on the system requirements. If more positive value of DB ( greater dead band ) is used, an unwanted cooling action can be avoided but an excessive overshoot over the set point will occur. If more negative value of DB ( greater overlap ) is used, an excessive overshoot over the set point can be minimized but an unwanted cooling action will occur. It is adjustable in the range -36.0% to 36.0 % of PB. A negative DB value shows an overlap area over which both outputs are active. A positive DB value shows a dead band area over which neither output is active.
Output 2 ON-OFF Control ( Alarm function ): The output 2 can also be configured as alarm function. There are 4 kinds of alarm functions can be selected for output 2, these are: DE.HI (deviation high alarm ),
DE.LO (deviation low alarm ), PV.HI (process high alarm ) and PV.LO
( process low alarm ). Refer to Figure 3.3 and Figure 3.4 for the description of deviation alarm and process alarm.
37 UM91001A
SV+SP2
SV+SP2-O2HY
OUT2 Action
ON
OFF
PV OUT2=DE.HI
SP2+O2HY
SP2
OUT2 Action
ON
OFF
PV
Figure 3.3 Output 2 Deviation
High Alarm
Figure 3.4 Output 2 Process
Low Alarm
UM91001A
Time
Time
Time
Time
38
3 - 4 Alarm
The controller has one alarm output. There are 6 types of alarm functions and one dwell timer can be selected, and four kinds of alarm modes ( ALMD ) are available for each alarm function
( ALFN ). Besides the alarm output, the output 2 can also be configured as another alarm. But output 2 only provides 4 kinds of alarm functions and only normal alarm mode is avaiable for this alarm.
A process alarm sets two absolute trigger levels. When the process is higher than SP3, a process high alarm ( PV.HI ) occurs, and the alarm is off as the process is lower than SP3-ALHY. When the process is lower than SP3, a process low alarm ( PV.LO ) occurs and the alarm is off as the process is higher than SP3+ALHY. A process alarm is independent of set point.
A deviation alarm alerts the user when the process deviates too far from set point. When the process is higher than SV+SP3, a deviation high alarm (DE.HI) occurs and the alarm is off as the process is lower than SV+SP3-ALHY. When the process is lower than SV+SP3, a deviation low alarm (DE.LO) occurs and the alarm is off as the process is higher than SV+SP3+ALHY. Trigger level of deviation alarm is moving with set point.
A deviation band alarm presets two trigger levels relative to set point.
The two trigger levels are SV+SP3 and SV - SP3 for alarm. When the process is higher than ( SV+SP3 ) or lower than ( SV - SP3 ), a deviation band high alarm ( DB.HI ) occurs. When the process is within the trigger levels, a deviation band low alarm (DB.LO) occurs.
In the above descriptions SV denotes the current set point value for control which is different from SP1 as the ramp function is performed.
There are four types of alarm modes available for each alarm function, these are: Normal alarm, Latching alarm, Holding alarm and Latching/
Holding alarm. They are described as follows:
39 UM91001A
Normal Alarm : ALMD = NORM
When a normal alarm is selected, the alarm output is de-energized in the non-alarm condition and energized in an alarm condition.
Latching Alarm : ALMD = LTCH
If a latching alarm is selected, once the alarm output is energized, it will remain unchanged even if the alarm condition is cleared. The latching alarm is reset when the RESET key is pressed, once the alarm condition is removed.
Holding Alarm : ALMD = HOLD
A holding alarm prevents an alarm from power up. The alarm is enabled only when the process reaches the set point value.
Afterwards, the alarm performs same function as normal alarm.
Latching / Holding Alarm : ALMD = LT.HO
A latching / holding alarm performs both holding and latching function.
The latching alarm is reset when the RESET key is pressed, once the alarm condition is removed.
Alarm Failure Transfer is activated as the unit enters failure mode.
Alarm will go on if ON is set for ALFT and go off if OFF is set for ALFT. The unit will enter failure mode when sensor break occurs or if the A-D converter of the unit fails.
3 - 5 Configure User Menu
The conventional controllers are designed with a fixed parameters' scrolling.
If you need a more friendly operation to suit your application, the vender will say " sorry " to you. The series have the flexibility for you to select those parameters which are most significant to you and put these parameters in the
front of display sequence.
SEL1~SEL8 : Selects the parameter for view and change in the user menu.
Range : LOCK, INPT, UNIT, DP, SHIF, PB, TI, TD, O1HY, CYC1, OFST,
RR, O2HY, CYC2, CPB, DB, ADDR, ALHY
When using the up-down key to select the parameters, you may not obtain all of the above parameters. The number of visible parameters is dependent on the setup condition. The hidden parameters for the specific application are also deleted from the SEL selection.
UM91001A 40
Example :
OUT2 selects DE.LO PB= 100.0 SEL1 selects INPT
SEL2 selects UNIT SEL3 selects PB SEL4 selects TI
SEL5~SEL8 selects NONE Now, the upper display scrolling becomes :
PV
3 - 6 Ramp
The ramping function is performed during power up as well as any time the set point is changed. Choose MINR or HRR for RAMP, the unit will perform the ramping function. The ramp rate is programmed by adjusting RR. The ramping function is disabled as soon as the failure mode, the manual control mode, the auto-tuning mode or the calibration
Mode occurs.
Example without Dwell Timer
Select MINR for RAMP, selects LC for UNIT, selects 1-DP for DP,
Set RR= 10.0. SV is set to 200 LC initially, and changed to 100 LC after
30 minutes since power up. The starting temperature is 30 LC. After power
Up the process is running like the curve shown below:
PV
200
C
100
C
30
C
0 17 30 40
Time
(minutes)
Figure 3.5 RAMP Function
Note:
When the ramp function is used, the lower display will show the current ramping value. However it will revert to show the set point value as soon as the up or down key is touched for adjustment. The ramping value is initiated to process value either as power up or RR and /or set point are changed.
Setting RR to zero means no ramp function at all.
41 UM91001A
3 - 7 Dwell Timer
Alarm output can be configured as dwell timer by selecting TIMR for
ALFN . As the dwell timer is configured, the parameter SP3 is used for dwell time adjustment. The dwell time is measured in minute ranging from 0.1 to 4553.6 minutes. Once the process reaches the set point the dwell timer starts to count down until zero ( time out ). The timer relay will remain unchanged until time out. The dwell timer operation is shown as following diagram.
After time out the dwell timer will be restarted by pressing the RESET key.
The timer stops to count during the manual control mode, failure mode,
Calibration period and auto-tuning period.
PV
SP power off or touch RESET key
Time
ON
OFF
ALM
SP3
Timer starts
Figure 3.6 Dwell Timer Function
If alarm is configured as dwell timer, ALHY and ALMD are hidden.
Time
UM91001A 42
3 - 8 PV Shift
In certain applications it is desirable to shift the controller display value from its actual value.
This can be easily accomplished by using the PV shift function.
The SHIF function will alter PV only.
Here is an example. A process is equipped with a heater, a sensor and a subject to be warmed up. Due to the design and position of the components in the system, the sensor could not be placed any closer to the part. Thermal gradient ( different temperature ) is common and necessary to an extent in any thermal system for heat to be transferred from one point to another. If the difference between the sensor and the subject is 35 LC, and the desired temperature at the subject to be heated is 200 LC, the controlling value or the temperature at the sensor should be 235 LC. You should input -35 LC as to subtract 35 LC from the actual process display. This in turn will cause the controller to energize the load and bring the process display up to the set point value.
Subject
165 C
Heat
Transfer
200 C
Sensor
C
Heater
Subject
165 C
Heat
Transfer
200 C
Sensor
C
Heater
Subject
200 C
Heat
Transfer
235 C
Sensor
C
Heater
35 C temperature difference is observed
SHIF= 0
Adjust SHIF
SHIF= -35 C
Supply more heat
Figure 3.7
PV Shift Application
Display is stable
SHIF= -35 C
PV=SV
43 UM91001A
3 - 9 Digital Filter
In certain application the process value is too unstable to be read. To improve this a programmable low pass filter incorporated in the controller can be used. This is a first order filter with time constant specified by FILT parameter . The default value of FILT is 0.5 sec. before shipping. Adjust FILT to change the time constant from 0 to 60 seconds. 0 second represents no filter is applied to the input signal. The filter is characterized by the following diagram.
PV
1 sec
FILT=0
FILT=1
FILT=30
1 sec
Time
Figure 3.8
Filter Characteristics
NOTE :
The Filter is available only for PV, and is performed for the displayed value only. The controller is designed to use unfiltered signal for control even if Filter is applied. A lagged ( filtered ) signal, if used for control, may produce an unstable process.
UM91001A 44
3 - 10 Failure Transfer
The controller will enter occurs:
as one of the following conditions
1. occurs due to the input sensor break or input current below
1mA if 4-20 mA is selected or input voltage below 0.25V if 1-5 V is
selected .
2. occurs due to the A-D converter of the controller fails.
The output 1 and output 2 will perform the failure transfer function as the controller enters failure mode.
Output 1 Failure Transfer, if activated, will perform :
1. If output 1 is configured as proportional control ( PB=0 ), and BPLS
is selected for O1FT, then output 1 will perform bumpless transfer.
Thereafter the previous averaging value of MV1 will be used for
controlling output 1.
2. If output 1 is configured as proportional control ( PB=0 ), and a
value of 0 to 100.0 % is set for O1FT, then output 1 will perform
failure transfer. Thereafter the value of O1FT will be used for
controlling output 1.
3. If output 1 is configured as ON-OFF control ( PB=0 ), then output 1
will transfer to off state if OFF is set for O1FT and transfer to on
state if ON is set for O1FT.
Output 2 Failure Transfer, if activated, will perform :
1. If OUT2 is configured as COOL, and BPLS is selected for O2FT,
then output 2 will perform bumpless transfer. Thereafter the previous
averaging value of MV2 will be used for controlling output 2.
2. If OUT2 is configured as COOL, and a value of 0 to 100.0 % is set
for O2FT, then output 2 will perform failure transfer. Thereafter the
value of O2FT will be used for controlling output 2.
3. If OUT2 is configured as alarm function, and OFF is set for O2FT,
then output 2 will transfer to off state, otherwise, output 2 will transfer
to on state if ON is set for O2FT.
Alarm Failure Transfer is activated as the controller enters failure mode.
Thereafter the alarm will transfer to the ON or OFF state which is determined by the set value of ALFT.
45 UM91001A
3 - 11 Auto-tuning
The auto-tuning process is performed at set point.
The process will oscillate around the set point during tuning process.
Set a set point to a lower value if overshooting beyond the normal process value is likely to cause damage.
*
*
*
The auto-tuning is applied in cases of :
Initial setup for a new process
The set point is changed substantially from the previous auto- tuning value
The control result is unsatisfactory
Operation :
1. The system has been installed normally.
2. Set the correct values for the setup menu of the unit.
But don't use a zero value for PB and TI , otherwise, the
auto-tuning program will be disabled. The LOCK parameter
should be set at NONE.
3. Set the set point to a normal operating value or a lower value if
overshooting beyond the normal process value is likely to
cause damage.
4. Press and hold until appears on the display.
5. Press for at least 5 seconds. The AT indicator will begin to
flash and the auto-tuning procedure is beginning.
NOTE :
The ramping function, if used, will be disabled once auto-tuning is proceeding.
The auto-tuning mode is disabled as soon as either failure mode
or manual control mode occurs.
UM91001D 46
Procedures:
The auto-tuning can be applied either as the process is warming
up ( Cold Start ) or as the process has been in steady state ( Warm Start ).
After the auto-tuning procedures are completed, the AT indicator will cease to flash and the unit revert to PID control by using its new PID values. The
PID values obtained are stored in the nonvolatile memory.
Auto-Tuning Error
If auto-tuning fails an ATER message will appear on the upper display in cases of :
If PB exceeds 9000 ( 9000 PU, 900.0 LF or 500.0 LC ).
or if TI exceeds 1000 seconds.
or if set point is changed during auto-tuning procedure.
Solutions to
1. Try auto-tuning once again.
2. Don't change set point value during auto-tuning procedure.
3. Don't set zero value for PB and TI.
4. Use manual tuning instead of auto-tuning. ( See section 3-12 ).
5. Touch RESET key to reset message.
3 - 12 Manual Tuning
In certain applications ( very few ) using auto-tuning to tune a process may be inadequate for the control requirement, then you can try manual tuning.
If the control performance by using auto- tuning is still unsatisfactory, the following rules can be applied for further adjustment of PID values :
47 UM91001A
ADJUSTMENT SEQUENCE
(1) Proportional Band ( PB )
(2) Integral Time ( TI )
(3) Derivative Time ( TD )
SYMPTOM
Slow Response
High overshoot or
Oscillations
Slow Response
Instability or
Oscillations
Slow Response or
Oscillations
High Overshoot
SOLUTION
Decrease PB
Increase PB
Decrease TI
Increase TI
Decrease TD
Increase TD
Table 3.2 PID Adjustment Guide
Figure 3.9 shows the effects of PID adjustment on process response.
3 - 13 Manual Control
Operation:
To enable manual control the LOCK parameter should be set with
NONE, then press for 6.2 seconds ( Hand
Control ) will appear on the display. Press for 5 seconds then the
MAN indicator will begin to flash and the lower display will show
. The controller now enters the manual control mode
. indicates output control variable for output 1, and indicates control variable for output 2. Now you can use up-down key to adjust the percentage values for the heating or cooling output.
The controller performs open loop control as long as it stays in manual control mode.
Exit Manual Control
UM91001D 48
49
PV
Set point
PV
Set point
PV
Set point
Perfect
PB too low
P action
PB too high
Time
TI too high
TI too low
Perfect
Time
TD too low
Perfect
I action
TD too high
Time
Figure 3.9 Effects of PID Adjustment
D action
UM91001A
3 - 14 Data Communication
The controllers support RTU mode of Modbus protocol for the data communication. Other protocols are not available for the series.
Two types of interface are available for Data Communication. These are RS-485 and RS-232 interface. Since RS-485 uses a differential architecture to drive and sense signal instead of a single ended architecture which is used for RS-232, RS-485 is less sensitive to the noise and suitable for a longer distance communication. RS-485 can communicate without error over 1 km distance while RS-232 is not recommended for a distance over 20 meters.
Using a PC for data communication is the most economic way. The signal is transmitted and received through the PC communication Port ( generally RS-232 ). Since a standard PC can't support RS-485 port, a network adaptor ( such as SNA10A, SNA10B ) has to be used to convert
RS-485 to RS-232 for a PC if RS-485 is required for the data communication. But there is no need to be sad. Many RS-485 units ( up to 247 units ) can be connected to one RS-232 port, therefore a PC with 4 comm ports can communicate with 988 units. It is quite economic.
Setup
Enters the setup menu.
Select RTU for COMM . Set individual address as for those units which are connected to the same port.
Set the Baud Rate ( BAUD ), Data Bit ( DATA ), Parity Bit ( PARI ) and Stop Bit ( STOP ) such that these values are accordant with PC setup conditions.
If you use a conventional 9-pin RS-232 cable instead of CC94-1, the cable should be modified for proper operation of RS-232 communication according to Section 2-9.
3 - 15 PV Retransmission
The controller can output (retransmit) process value via its retransmission terminals RE+ and RE- provided that the retransmission option is ordered. A correct signal type should be selected for COMM parameter to meet the retransmission option installed. RELO and REHI are adjusted to specify the low scale and high scale values of retransmission.
UM91001A 50
Chapter 4 Applications
4 - 1 Heat Only Control with Dwell Timer
An oven is designed to dry the products at 150 ZEL for 30 minutes and then stay unpowered for another batch. A ZEL-8100 equipped with dwell timer is used for this purpose. The system diagram is shown as follows :
Set
SP1=150.0
SP3 =30.0
19 20
C
Oven
T/C
Heater
Figure 4.1
Heat Control
Example
R
9
ZESTA
7
ZEL - 8100
4 3
OUT1
ON
Mains
Supply
Timer ( ALM ) OFF
To achieve this function set the following parameters in the setup menu.
INPT=K_TC UNIT= LC DP=1_DP
OUT1=REVR O1TY=RELY CYC1=18.0
O1FT=BPLS ALFN=TIMR ALFT=ON
Auto-Tuning is performed at 150 LC for a new oven.
51 UM91001A
4 - 2 Cool Only Control
A ZEL-8100 is used to control a refrigerator at temperature below 0 ZE. The temperature is lower than the ambient, a cooling action is required. Hence select DIRT for OUT1. Since output 1 is used to drive a magnetic contactor, O1TY selects RELY. A small temperature oscillation is tolerable, hence use ON-OFF control to reduce the over-all cost. To achieve ON-
OFF control, PB is set with zero and O1HY is set at 0.1 ZE.
Setup Summary:
INPT=PT.DN
UNIT= LC
DP=1-DP
OUT1=DIRT
O1TY=RELY
Refrigerator
RTD
Mains
Supply
User Menu:
PB = 0 ( LC )
O1HY=0.1 ( LC )
18
19 20 3
4
R
ZESTA ZEL - 8100
Figure 4.2
Cooling Control Example
UM91001A 52
4 - 3 Heat-Cool Control
An injection mold required to be controlled at 120 LC to ensure a consistent quality for the parts. An oil pipe is buried in the mold. Since plastics is injected at higher temperature ( e.g.
250 LC ), the circulation oil needs to be cooled as its temperature rises. Here is an example:
Plastics
Injection Mold
120 C
Freezer
Oil Tank
Oil
Pump
RTD
4-20 mA
OUT2
5,6
OUT1
3 4
20
19
18
INPT
Heater
Supply
R
ZESTA ZEL - 8100
Figure 4.3
Heat-Cool Control Example
53 UM91001A
The PID Heat-Cool is used for the above example. To achieve this set the following parameters in the Setup Menu:
INPT=PT.DN
UNIT= LC
DP= 1-DP
OUT1=REVR
O1TY=RELY
CYC1=18.0 (sec.)
O1FT=BPLS
OUT2=COOL
O2TY=4-20
O2FT=BPLS
Adjust SV at 120.0 LC , CPB at 125 ( % ) and DB at -4.0 (%).
Apply Auto-tuning at 120 LC for a new system to get an optimal PID values. See Section 3-11.
Adjustment of CPB is related to the cooling media used. If water is used as cooling media instead of oil, the CPB is set at 250 (%). If air is used as cooling media instead of oil, the CPB is set at 100 (%). Adjustment of DB is dependent on the system requirements. More positive value of DB will prevent unwanted cooling action, but will increase the temperature overshoot, while more negative value of DB will achieve less temperature overshoot, but will increase unwanted cooling action.
UM91001A 54
Chapter 5 Calibration
Do not proceed through this section unless there is a definite need to re-calibrate the controller. Otherwise, all previous calibration data will be lost. Do not attempt recalibration unless you have appropriate calibration equipment. If calibration data is lost, you will need to return the controller to your supplier who may charge you a service fee to re-calibrate the controller.
Entering calibration mode will break the control loop. Make sure
that if the system is allowable to apply calibration mode.
Equipments needed before calibration:
(1) A high accuracy calibrator ( Fluke 5520A Calibrator
recommended ) with following functions:
0 - 100 mV millivolt source with A0.005 % accuracy
0 - 10 V voltage source with A0.005 % accuracy
0 - 20 mA current source with A0.005 % accuracy
0 - 300 ohm resistant source with A0.005 % accuracy
(2) A test chamber providing 25 ZE - 50 ZE temperature range
(3) A switching network ( SWU16K, optional for automatic
calibration )
(4) A calibration fixture equipped with programming units ( optional
for automatic calibration )
(5) A PC installed with calibration software ZE-Net and Smart
Network Adaptor SNA10B ( optional for automatic calibration )
The calibration procedures described in the following section are a step by step manual procedures.
Since it needs 30 minutes to warm up an unit before calibration, calibrating the unit one by one is quite inefficient. An automatic calibration system for small quantity as well as for unlimited quantity is available upon request.
55 UM91001A
Manual Calibration Procedures
Step 1.
* Perform step 1 to enter calibration mode.
Set the Lock parameter to the unlocked condition
( LOCK=NONE).
Press and hold the scroll key until appears on the display, then release the scroll key.
Press the scroll key for 2 seconds then release,the display will show and the unit enters calibration mode .
* Perform step 2 to calibrate Zero of A to D converter and step 3 to calibrate gain of A to D converter.
Step 2.
Short the thermocouple inpt terminals , then press scroll key for at least 5 seconds. The display will blink a moment and a new value is obtained. Otherwise, if the display didn't blink or if the obtained value is equal to -199.9 or 199.9, then the calibration fails.
Step 3.
Press scroll key until the display shows . Send a 60mV signal to the thermocouple input terminals in correct polarity.
Press scroll key for at least 5 seconds. The display will blink a moment and a new value is obtained. Otherwise, if the display didn't blink or if the obtained value is equal to -199.9 or 199.9, then the calibration fails.
* Perform both steps 4 and 5 to calibrate RTD function ( if required ) for input .
UM91001D 56
Step 4.
Press scroll key until the display shows . Send a 100 ohms signal to the RTD input terminals according to the connection shown below:
100 ohms
ZEL-4100
ZEL-8100
18
19
20
ZEL-7100
12
13
14
ZEL-9100
4
5
6
Figure 5.1 RTD Calibration
Press scroll key for at least 5 seconds . The display will blink a moment, otherwise the calibration fails.
Step 5.
Press scroll key and the display will show . Change the ohm's value to 300 ohms. Press scroll key for at least 5 seconds. The display will blink a moment and two values are obtained for RTDH and RTDL ( step 4 ). Otherwise, if the display didn't blink or if any value obtained for RTDH and
RTDL is equal to -199.9 or 199.9 , then the calibration fails.
* Perform step 6 to calibrate offset of cold junction compensation, if required.
Step 6.
Setup the equipments according to the following diagram for calibrating the cold junction compensation. Note that a
K type thermocouple must be used.
57 UM91001D
5520A
Calibrator
K-TC
ZEL-4100
ZEL-8100
ZEL-7100
K+
19
20
13
14
K -
Stay at least 20 minutes in still-air room room temperature 25 A 3 LC
ZEL-9100
5
6
Figure 5.2
Cold Junction Calibration Setup
The 5520A calibrator is configured as K type thermocouple output with internal compensation.
Send a 0.00 LC signal to the unit under calibration.
The unit under calibration is powered in a still-air room with temperature 25A3 ZE. Stay at least 20 minutes for warming up. Perform step 1 stated above, then press scroll key until the display shows . Press up/down key to obtain40.00.
Press scroll key for at least 5 seconds. The display will blink a moment and a new value is obtained. Otherwise, if the display didn't blink or if the obtained value is equal to -5.00 or
40.00, then the calibration fails.
Step 7.
* Perform step 7 to calibrate gain of cold junction compensation if required.
Setup the equipments same as step 6. The unit under calibration is powered in a still-air room with temperature 50A3 ZE. Stay at least 20 minutes for warming up. The calibrator source is set at
0.00 ZE with internal compensation mode.
UM91001D 58
Perform step 1 stated above, then press scroll key until the display shows . Press scroll key for at least 5 seconds.
The display will blink a moment and a new value is obtained.
Otherwise, if the display didn't blink or if the obtained value is equal to -199.9 or 199.9, then the calibration fails.
This setup is performed in a high temperature chamber, hence
it is recommended to use a computer to perform the procedures.
* Input modification and recalibration procedures for a linear voltage or a linear current input:
1. Remove R60(3.3K) and install two 1/4 W resistors RA and RB
on the control board with the recommended values specified
in the following table.
The low temperature coefficient resistors should be used for
RA and RB.
Input Function
T/C, RTD, 0~60mV
0 ~ 1 V
0 ~ 5V, 1 ~ 5V
0 ~ 10 V
0~20mA, 4~20mA
RA
X
61.9K
324K
649K
39W
RB
X
3.92K
3.92K
3.92K
3.01W
R60
3.3K
X
X
X
X
2. Perform Step 1 and Step 2 to calibrate the linear input zero.
3. Perform Step 3 but send a span signal to the input terminals
instead of 60mV. The span signal is 1V for 0~1V input, 5V for
0~5V or 1~5V input, 10V for 0~10V input and 20mA for
0~20mA or 4~20mA input.
* Final step
Step 8.
Set the LOCK value to your desired function.
59 UM91001D
Chapter 6 Specifications
Power
90 - 250 VAC, 47 - 63 Hz, 12VA, 5W maximum
11 - 26 VAC / VDC, 12VA, 5W maximum
Input
Resolution : 18 bits
Sampling Rate : 5 times / second
Maximum Rating : -2 VDC minimum, 12 VDC maximum
( 1 minute for mA input )
Temperature Effect : A1.5uV/ ZE for all inputs except
mA input
A3.0uV/ ZE for mA input
Sensor Lead Resistance Effect :
T/C: 0.2uV/ohm
3-wire RTD: 2.6 LC/ohm of resistance difference of two
leads
2-wire RTD: 2.6 LC/ohm of resistance sum of two leads
Burn-out Current :
200 nA
Common Mode Rejection Ratio ( CMRR ): 120dB
Normal Mode Rejection Ratio ( NMRR ): 55dB
Sensor Break Detection :
Sensor open for TC, RTD and mV inputs,
Sensor short for RTD input below 1 mA for 4-20 mA input, below 0.25V for 1 - 5 V input, unavailable for other inputs.
Sensor Break Responding Time :
Within 4 seconds for TC, RTD and mV inputs,
0.1 second for 4-20 mA and 1 - 5 V inputs.
UM91001B 60
Characteristics:
Type
J
K
T
E
Range
-120 C - 1000 C
( -184 F - 1832 F )
-200 C 1370 C
( -328 F - 2498 F )
-250 C - 400 C
( -418 F - 752 F )
-100 C - 900 C
( -148 F - 1652 F )
B
0 C - 1800 C
( 32 BF - 3272 BF )
R
S
N
L
PT100
( DIN )
PT100
( JIS ) mV mA
V
0 C - 1767.8 C
( 32 BF - 3214 BF )
0 C - 1767.8 C
( 32 BF - 3214 BF )
-250 C - 1300 C
( -418 F - 2372 F )
-200 C - 900 C
( -328 F - 1652 F )
-210 C - 700 C
( -346 F - 1292 F )
-200 C - 600 C
( -328 F - 1112 F )
-8mV - 70mV
-3mA - 27mA
-1.3V - 11.5V
A2 LC
A2 LC
A2 LC
A2 LC
A0.4 LC
A0.4 LC
A0.05 %
A0.05 %
A0.05 %
Accuracy
@ 25 C
A2 LC
A2 LC
A2 LC
A2 LC
A2 LC
( 200 C -
1800 C )
Input
Impedance
2.2 M
2.2 M
2.2 M
2.2 M
2.2 M
2.2 M
2.2 M
2.2 M
2.2 M
1.3 K
1.3 K
2.2 M
70.5
650 K
61 UM91001A
Output 1 / Output 2
Relay Rating : 2A/240 VAC, life cycles 200,000 for
resistive load
Pulsed Voltage : Source Voltage 5V,
current limiting resistance 66 .
Linear Output Characteristics
Type
4~20 mA
Zero
Tolerance
3.6~4 mA
0~20 mA
0 ~ 5 V
1 ~ 5 V
0 ~ 10 V
0 mA
0 V
0.9 ~ 1 V
0 V
Span
Tolerance
20~21 mA
20~21 mA
5 ~ 5.25 V
5 ~ 5.25 V
10 ~10.5 V
Linear Output
Resolution : 15 bits
Output Regulation : 0.02 % for full load change
Output Settling Time : 0.1 sec. ( stable to 99.9 % )
Isolation Breakdown Voltage : 1000 VAC
Temperature Effect : A0.01 % of SPAN / LC
Triac ( SSR ) Output
Rating : 1A / 240 VAC
Inrush Current : 20A for 1 cycle
Min. Load Current : 50 mA rms
Max. Off-state Leakage : 3 mA rms
Max. On-state Voltage : 1.5 V rms
Insulation Resistance : 1000 Mohms min. at 500 VDC
Dielectric Strength : 2500 VAC for 1 minute
Load
Capacity
500W max.
500W max.
10 K
W
min.
10 KW min.
10 KW min.
UM91001B 62
DC Voltage Supply Characteristics ( Installed at Output 2 )
Type Tolerance Max. Output Current Ripple Voltage Isolation Barrier
20 V A1 V 25 mA 0.2 Vp-p 500 VAC
12 V A0.6 V 40 mA 0.1 Vp-p 500 VAC
5 V A0.25 V 80 mA 0.05 Vp-p 500 VAC
Alarm
Alarm Relay : Form C Rating
2A/240VAC, life cycles 200,000 for resistive load.
Alarm Functions : Dwell timer, Deviation High / Low Alarm,
Deviation Band High / Low Alarm,
PV High / Low Alarm,
Alarm Mode : Normal, Latching, Hold, Latching / Hold.
Dwell Timer : 0.1 - 4553.6 minutes
Data Communication
Interface : RS-232 ( 1 unit ), RS-485 ( up to 247 units )
Protocol : Modbus Protocol RTU mode
Address : 1 - 247
Baud Rate : 2.4 ~ 38.4 Kbits/sec
Data Bits : 7 or 8 bits
Parity Bit : None, Even or Odd
Stop Bit : 1 or 2 bits
Communication Buffer : 160 bytes
Analog Retransmission
Output Signal : 4-20 mA, 0-20 mA, 0 - 5V,
1 - 5V, 0 - 10V
Resolution : 15 bits
Accuracy : A0.05 % of span A0.0025 %/ LC
Load Resistance :
0 - 500 ohms ( for current output )
10 K ohms minimum ( for voltage output )
Output Regulation : 0.01 % for full load change
63 UM91001D
Output Settling Time : 0.1 sec. (stable to 99.9 % )
Isolation Breakdown Voltage : 1000 VAC min.
Integral Linearity Error : A0.005 % of span
Temperature Effect : A0.0025 % of span/ LC
Saturation Low : 0 mA ( or 0V )
Saturation High : 22.2 mA ( or 5.55V, 11.1V min. )
Linear Output Range :0-22.2mA(0-20mA or 4-20mA)
0-5.55V ( 0 - 5V, 1 - 5V )
0 - 11.1 V ( 0 - 10V )
User Interface
Dual 4-digit LED Displays
Keypad : 4 keys
Programming Port : For automatic setup, calibration and testing
Communication Port : Connection to PC for supervisory control
Control Mode
Output 1 : Reverse ( heating ) or direct ( cooling ) action
Output 2 : PID cooling control, cooling P band 50~300%
of PB, dead band -36.0 ~ 36.0 % of PB
ON-OFF : 0.1 - 90.0 ( LF ) hysteresis control ( P band = 0 )
P or PD : 0 - 100.0 % offset adjustment
PID : Fuzzy logic modified
Proportional band 0.1 ~ 900.0 LF.
Integral time 0 - 1000 seconds
Derivative time 0 - 360.0 seconds
Cycle Time : 0.1 - 90.0 seconds
Manual Control : Heat (MV1) and Cool (MV2)
Auto-tuning : Cold start and warm start
Failure Mode : Auto-transfer to manual mode while
sensor break or A-D converter damage
Ramping Control : 0 - 900.0 LF/minute or
0 - 900.0 LF/hour ramp rate
Digital Filter
Function : First order
Time Constant : 0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60
seconds programmable
UM91001A 64
Environmental & Physical
Operating Temperature : -10 ZE to 50 ZE
Storage Temperature : -40 ZE to 60 ZE
Humidity : 0 to 90 % RH ( non-condensing )
Altitude: 2000m maximum
Pollution: Degree 2
Insulation Resistance : 20 Mohms min. ( at 500 VDC )
Dielectric Strength : 2000 VAC, 50/60 Hz for 1 minute
Vibration Resistance : 10 - 55 Hz, 10 m/s for 2 hours
2
2
Shock Resistance : 200 m/s ( 20 g )
Moldings : Flame retardant polycarbonate
Dimensions :
ZEL-4100 ----- 96mm(W) X 96mm(H) X 65mm(D),
53 mm depth behind panel
ZEL-7100 ----- 72mm(W) X 72mm(H) X 78.2mm(D),
65 mm depth behind panel
ZEL-8100 ----- 48mm(W) X 96mm(H) X 80mm(D),
65 mm depth behind panel
ZEL-9100 ----- 48mm(W) X 48mm(H) X 116mm(D),
105 mm depth behind panel
Weight : ZEL-4100 ----- 250 grams
ZEL-7100 ----- 200 grams
ZEL-8100 ----- 210 grams
ZEL-9100 ----- 150 grams
Approval Standards
Safety : UL61010C-1
CSA C22.2 No.24-93
EN61010-1 ( IEC1010-1 )
Protective Class :
IP65 for panel with additional option
IP50 for panel without additional option
IP20 for terminals and housing with protective cover.
All indoor use.
EMC: EN61326
65 UM91001D
Chapter 7 Modbus Communications
This chapter specifies the Modbus Communications protocol as
RS-232 or RS-485 interface module is installed. Only RTU mode is supported. Data is transmitted as eight-bit binary bytes with 1 start bit,
1 stop bit and optional parity checking (None, Even or Odd). Baud rate may be set to 2400, 4800, 9600, 14400, 19200, 28800 and 38400.
7 - 1 Functions Supported
Only function 03, 06 and 16 are available for this series of controllers.
The message formats for each function are described as follows:
Function 03: Read Holding Registers
Query ( from master )
Slave address (0-255)
Function code (3)
Starting address of register Hi (0)
Starting address of register Lo (0-79,
128-131)
No. of words Hi (0)
No. of words Lo (1-79)
CRC16 Hi
CRC16 Lo
Response ( from slave )
Byte count
Data 1 Hi
Data 1 Lo
Data 2 Hi
Data 2 Lo
CRC16 Hi
CRC16 Lo
Function 06: Preset single Register
Query ( from master )
Slave address (0-255)
Function code (6)
Register address Hi (0)
Register address Lo (0-79, 128-131)
Data Hi
Data Lo
CRC16 Hi
CRC16 Lo
Response ( from slave )
UM91001B 66
Function 16: Preset Multiple Registers
Query ( from master )
Slave address (0-255)
Function code (16)
Starting address of register Hi (0)
Starting address of register Lo (0-79,
128-131)
No. of words Hi (0)
No. of words Lo (1-79)
Byte count (2-158)
Data 1 Hi
Data 1 Lo
Data 2 Hi
Data 2 Lo
CRC16 Hi
CRC16 Lo
Response ( from slave )
CRC16 Hi
CRC16 Lo
67 UM91001B
7 - 2 Exception Responses
If the controller receives a message which contains a corrupted character (parity check error, framing error etc.), or if the CRC16 check fails, the controller ignores the message.
However, if the controller receives a syntactically correct message which contains an illegal value, it will send an exception response, consisting of five bytes as follows: slave address +offset function code + exception code + CRC16 Hi + CRC16 Lo
Where the offset function code is obtained by adding the function code with 128 (ie. function 3 becomes H'83), and the exception code is equal to the value contained in the following table:
Exception Code
1
2
3
Name
Bad function code
Illegal data address
Illegal data value
Cause
Function code is not supported by the controller
Register address out of range
Data value out of range or attempt to write a read-only or protected data
UM91001A 68
7 - 3 Parameter Table
17
18
19
20
21
13
14
15
16
22
23
24
25
26
27
28
29
9
10
11
12
7
8
5
6
Register
Address
0
1
2
3
4
Parameter
Notation
Parameter
SP1
SP2
Set point 1
Set point 2
SP3
LOCK
INPT
Set point 3
Lock code
Input sensor selection
UNIT
DP
Measuring unit
Decimal point position
INLO
INHI
Low scale value for linear input
High scale value for linear input
SP1L
SP1H
Low limit of SP1
High limit of SP1
SHIF
FILT
PV shift value
Filter time constant
DISP
PB
Display form ( for C21 )
P ( proportional ) band
Integral time TI
TD
OUT1
O1TY
O1FT
O1HY
CYC1
OFST
RAMP
RR
OUT2
Derivative time
Output 1 function
Output 1 signal type
Output 1 failure transfer
Output 1 ON-OFF hysteresis
Output 1 cycle time
Offset value for P control
Ramp function
Ramp rate
Output 2 function
RELO Retransmission low scale value
O2TY
O2FT
Output 2 signal type
Output 2 failure transfer
O2HY Output 2 ON-OFF hysteresis
69 UM91001D
65535
65535
*4
*4
*4
*4
*4
65535
65535
*5
Scale
High
*4
*7
*6
65535
65535
65535
6553.5
65535
65535
4553.6
*5
6553.5
6553.5
65535
*5
65535
*4
65535
4553.6
*5
0
0.0
0
0
*4
*4
*4
0
0
*5
*4
*4
0
0
Scale
Low
*4
*7
*6
0
0
-1999.9
*5
0.0
0.0
*4
0
0
*5
0
-1999.9
*5
Notes
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
51
52
53
54
46
47
48
49
50
43
44
45
39
40
41
42
55
56
57
58
59
60
Register
Address
30
31
32
33
34
35
36
37
38
Parameter
Notation
CYC2
CPB
DB
ALFN
REHI
ALMD
STOP
SEL1
SEL2
SEL3
SEL4
SEL5
SEL6
SEL7
ALHY
ALFT
COMM
ADDR
BAUD
DATA
PARI
SEL8
ADLO
ADHI
RTDL
RTDH
CJLO
CJHI
DATE
SRNO
HOUR
Output 2 cycle time
Cooling P band
Heating-cooling dead band
Alarm function
Retransmission high scale value
Alarm opertion mode
Alarm hysteresis
Alarm failure transfer
Communication function
Address
Baud rate
Data bit count
Parity bit
Stop bit count
Selection 1
Selection 2
Selection 3
Selection 4
Selection 5
Selection 6
Selection 7
Selection 8
Parameter mV calibration low coefficient mV calibration high coefficient
RTD calibration low coefficient
RTD calibration high coefficient
Cold junction calibration low coefficient
Cold junction calibration high coefficient
Date Code
Serial Number
Working hours of the controller
65535
65535
65535
65535
65535
65535
65535
4553.6
65535
65535
65535
65535
65535
65535
65535
Scale
High
6553.5
65535
4553.6
65535
*4
65535
*5
65535
4553.6
4553.6
4553.6
455.36
4553.6
65535
65535
65535
0
0
0
0
0
0
0
-1999.9
0
0
0
0
0
0
0
0
*4
0
*5
0
Scale
Low
0.0
0
-1999.9
-1999.9
-1999.9
-1999.9
-199.99
-1999.9
0
0
0
Notes
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
UM91001D 70
Register
Address
61
62
63
64, 128
65, 129
Parameter
Notation
BPL1
BPL2
CJCL
PV
SV
Parameter
Bumpless transfer of OP1
Bumpless transfer of OP2
Cold junction signal low
Process value
Current set point value
66
130
67
131
MV1
MV2
OP1 control output value
OP2 control output value
77
78
79
73
74
75
76
68
69
70
71, 140
72
TIMER
EROR
MODE
PROG
CMND
JOB1
JOB2
JOB3
CJCT
Remaining time of dwell timer
Error code *1
Operation mode & alarm status *2
Program code *3
Command code
Job code
Job code
Job code
Cold Junction Temperature
Reserved
Reserved
Reserved
*1: The error code is show in the first column of Table A.1.
*2: Definition for the value of MODE register
H'000X = Normal mode
H'010X = Calibration mode
H'020X = Auto-tuning mode
H'030X = Manual control mode
H'040X = Failure mode
H'0X00 = Alarm status is off
H'0x01 = Alarm status is on
The alarm status is shown in
MV2 instead of MODE for models C21 and C91.
Scale
Low
0.00
0.00
0.000
*4
*4
0.00
0.00
-1999.9
0
0
0.00
0
0
0
0
-199.99
0
0
0
4553.6
65535
65535
655.35
65535
65535
65535
65535
455.36
65535
65535
65535
Scale
High
655.35
655.35
65.535
*4
*4
Notes
655.35
R
R
R
R
R
Read only, unless in manual control
655.35
Read only, unless in manual control
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
71 UM91001D
*3: The PROG Code is defined in the following table:
Model No.
Conditions
ZEL-9100 ZEL-8100 ZEL-4100 ZEL-7100 C21 C91
PROG Code 6.XX
11.XX
12.XX
13.XX
33.XX
34.XX
Where XX denotes the software version number. For example:
PROG=34.18 means that the controller is C91 with software version 18.
*4: The scale high/low values are defined in the following table for SP1,
INLO, INHI, SP1L, SP1H, SHIF, PV, SV, RELO and REHI:
Non-linear
input
Linear input
DP = 0
Linear input
DP = 1
Linear input
DP = 2
Linear input
DP = 3
Scale low
Scale high
-1999.9
4553.6
-19999
45536
-1999.9
4553.6
-199.99
455.36
-19.999
45.536
*5: The scale high/low values are defined in the following table for PB,
O1HY, RR, O2HY and ALHY:
Conditions
Non-linear
input
Linear input
DP = 0
Linear input
DP = 1
Linear input
DP = 2
Linear input
DP = 3
Scale low
Scale high
0.0
6553.5
0
65535
0.0
6553.5
0.00
655.35
0.000
65.535
*6: The scale high/low values are defined in the following table for SP3:
Conditions
ALFN=1
(TIMR)
Non-linear
input
Linear input
DP = 0
Linear input
DP = 1
Linear input
DP = 2
Linear input
DP = 3
Scale low
Scale high
-1999.9
4553.6
-1999.9
4553.6
-19999
45536
-1999.9
4553.6
-199.99
455.36
-19.999
45.536
*7: The scale high/low values are defined in the following table for Sp2:
For C21 and C91.
Conditions
OUT2=1
(TIMR)
Non-linear
input
Linear input
DP = 0
Linear input
DP = 1
Linear input
DP = 2
Linear input
DP = 3
Scale low
Scale high
-1999.9
4553.6
-1999.9
4553.6
-19999
45536
-1999.9
4553.6
-199.99
455.36
-19.999
45.536
UM91001D 72
For ZEL-9100, ZEL-8100, ZEL-7100 and ZEL-4100
Conditions
Non-linear
input
Linear input
DP = 0
Linear input
DP = 1
Scale low
Scale high
-1999.9
4553.6
-19999
45536
-1999.9
4553.6
Linear input
DP = 2
-199.99
455.36
Linear input
DP = 3
-19.999
45.536
7 - 4 Data Conversion
The word data are regarded as unsigned ( positive ) data in the
Modbus message. However, the actual value of the parameter may be negative value with decimal point. The high/low scale values for each parameter are used for the purpose of such conversion.
Let M = Value of Modbus message
A = Actual value of the parameter
SL = Scale low value of the parameter
SH = Scale high value of the parameter
The conversion formulas are as follows:
M =
65535
SH-SL
( A - SL )
A =
SH-SL
65535
M + SL
7 - 5 Communication Examples :
Example 1: Down load the default values via the programming port
The programming port can perform Modbus communications regardless of the incorrect setup values of address, baud, parity, stop bit etc. It is especially useful during the first time configuration for the controller. The host must be set with 9600 baud rate, 8 data bits, even parity and 1 stop bit.
The Modbus message frame with hexadecimal values is shown as follows:
73 UM91001A
01 10 00 00
Addr. Func. Starting Addr.
00 34
No. of words
68 4F
Bytes SP1=25.0
19 4E
SP2=10.0
83 4E
SP3=10.0
83
00
LOCK=0
00 00
INPT=1
01 00
UNIT=0
00 00
DP=1
01 4D
INLO=-17.8
6D 51 C4
INHI=93.3
4D
SP1L=-17.8
6D 63
SP1H=537.8
21 4E
SHIF=0.0
1F 00 02 00
FILT=2 DISP=0
00 00
PB=10.0
64
00
TI=100
64 00 FA
TD=25.0
00
OUT1=0
00 00
O1TY=0
00 4E
O1FT=0
1F 00 01
O1HY=0.1
00 B4
CYC1=18.0
00 FA
OFST=25.0
00
RAMP=0
00 00
RR=0.0
00 00 02
OUT2=2
4E 1F
RELO=0.0
00
O2TY=0
00 4E 1F
O2FT=0
00 01
O2HY=0.1
00 B4
CYC2=18.0
00 64
CPB=100
4E
DB=0
1F
00
ALFN=2
02 52 07
REHI=100.0
00
ALMD=0
00 00 01
ALHY=0.1
00
ADDR=1
01 00 02
BAUD=2
00
DATA=1
01 00
PARI=0
00
00
ALFT=0
00 00 01
COMM=1
00
STOP=0
00 00
SEL1=2
02
00
SEL2=3
03 00 04
SEL3=4
00
SEL4=6
06 00
SEL5=7
07 00
SEL6=8
08 00
SEL7=10
0A
00
SEL8=17
11 Hi Lo
CRC16
UM91001D 74
Example 2: Read PV, SV, MV1 and MV2.
Send the following message to the controller via the COMM port or programming port:
03 00
H'40
H'80
00 04 Hi Lo
Addr.
Func.
Starting Addr.
No. of words CRC16
Query
06 00 H'48 H'68 H'25
Addr.
Func.
Register Addr.
Example 4: Enter Auto-tuning Mode
Query
06 00 H'48
Data Hi/Lo
H'68 H'28
Addr.
Func.
Register Addr.
Example 5: Enter Manual Control Mode
Query
06 00 H'48
Data Hi/Lo
H'68 H'27
Hi
CRC16
Lo
Hi
CRC16
Lo
Hi Lo
Addr.
Func.
Register Addr.
Example 6: Read All Parameters
Query
03 00 00
Data Hi/Lo
00 H'50 Hi
CRC16
Lo
Addr.
Func.
Starting Addr.
No. of words CRC16
Example 7: Modify the Calibration Coefficient
Preset the CMND register with 26669 before attempting to change the calibration coefficient.
06 00 H'48 H'68 H'2D Hi Lo
Addr.
Func.
Register Addr.
Data Hi / Lo CRC16
75 UM91001D
Table A.1 Error Codes and Corrective Actions
Error
Code
Display
Symbol
Error Description
4
Illegal setup values been used:
Before COOL is used for OUT2,
DIRT ( cooling action ) has already been used for OUT1, or PID mode is not used for OUT1 ( that is PB
= 0, and / or TI = 0 )
10
11
14
15
Communication error: bad function code
Communication error: register address out of range
Communication error: attempt to write a read-only data or a protected data
Communication error: write a value which is out of range to a register
Corrective Action
Check and correct setup values of
OUT2, PB, TI and OUT1. IF OUT2 is required for cooling control, the control should use PID mode ( PB
= 0, TI = 0 ) and OUT1 should use reverse mode (heating action)
, otherwise, don't use OUT2 for cooling control.
Correct the communication software to meet the protocol requirements.
Don't issue an over-range register address to the slave.
Don't write a read-only data or a protected data to the slave.
Don't write an over-range data to the slave register.
26
Fail to perform auto-tuning function
1.The PID values obtained after
auto-tuning procedure are out
of range. Retry auto-tuning.
2.Don't change set point value
during auto-tuning procedure.
3.Use manual tuning instead of
auto-tuning.
4. Don't set a zero value for PB.
5. Don't set a zero value for TI.
6. Touch RESET key
Return to factory for repair.
29
30
39
40
EEPROM can't be written correctly
Cold junction compensation for thermocouple malfunction
Input sensor break, or input current below 1 mA if 4-20 mA is selected, or input voltage below
0.25V if 1 - 5V is selected
A to D converter or related component(s) malfunction
Return to factory for repair.
Replace input sensor.
Return to factory for repair.
UM91001A 76
WARRANTY
ZESTA ENGINEERING LTD, is pleased to offer suggestions on the use of its various products.
However, ZESTA makes no warranties or representations of any sort regarding the fitness for use, or the application of its products by the Purchaser. The selection, application or use of
ZESTA products is the Purchaser's responsibility. No claims will be allowed for any damages or losses, whether direct, indirect, incidental, special or consequential. Specifications are subject to change without notice. In addition, ZESTA reserves the right to make changes-without notification to Purchaser-to materials or processing that do not affect compliance with any applicable specification. ZESTA products are warranted to be free from defects in material and workmanship for two years after delivery to the first purchaser for use. An extended period is available with extra cost upon request. ZESTA’S sole responsibility under this warranty, at
ZESTA’S option, is limited to replacement or repair, free of charge, or refund of purchase price within the warranty period specified. This warranty does not apply to damage resulting from transportation, alteration, misuse or abuse.
RETURNS
No products return can be accepted without a completed Return Material Authorization
( RMA ) form.
77 UM91001A
ZESTA ENGINEERING LTD.
212 Watline Avenue
Mississauga, Ontario, Canada
L4Z 1P4
Voice: (905) 568 - 3100
Fax: (905) 568 - 3131
Website: www.zesta.com
Email: [email protected]
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement