Allen-Bradley Compact 8-Bit Low Resolution Analog I/O Combination Module User Manual
Allen-Bradley Compact 8-Bit Low Resolution Analog I/O Combination Module is a versatile component for industrial control systems. It features 4 analog input channels, configurable for either voltage or current, along with 2 analog output channels. This makes it ideal for a wide range of applications involving monitoring and control of physical processes, such as temperature, pressure, flow rate, or level.
Advertisement
Advertisement
Compact™ 8-Bit
Low Resolution
Analog I/O
Combination
Module
(Catalog Number 1769-IF4XOF2)
User Manual
Important User Information
Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability
(to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation and Maintenance of Solid-State Control
(available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this manual we use notes to make you aware of safety considerations:
ATTENTION
!
Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss
Attention statements help you to:
• identify a hazard
• avoid a hazard
• recognize the consequences
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
MicroLogix, Compact, RSLogix and RSLinx are trademarks of Rockwell Automation.
Belden is a trademark of Belden, Inc.
DeviceNet is a trademark of Open DeviceNet Vendor Association (ODVA).
Table of Contents
i
Overview
Preface
Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . P-1
How to Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Manual Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . P-2
Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . P-3
Local Product Support . . . . . . . . . . . . . . . . . . . . . . . . . P-3
Technical Product Assistance . . . . . . . . . . . . . . . . . . . . P-3
Your Questions or Comments on the Manual . . . . . . . . P-3
Chapter 1
How to Use Analog I/O . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Hardware Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
General Diagnostic Features . . . . . . . . . . . . . . . . . . . . . 1-4
Overview of the Analog System . . . . . . . . . . . . . . . . . . . . . 1-4
System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Module Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Module Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Chapter 2
Quick Start for Experienced Users
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Required Tools and Equipment . . . . . . . . . . . . . . . . . . . . . 2-1
What You Need To Do . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Installation and Wiring
Chapter 3
Compliance to European Union Directives . . . . . . . . . . . . . 3-1
EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Low Voltage Directive . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
General Considerations to Avoid Electrostatic Damage . . . . 3-2
Hazardous Location Considerations . . . . . . . . . . . . . . . 3-3
Prevent Electrostatic Discharge . . . . . . . . . . . . . . . . . . . 3-3
Remove Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Reducing Electrical Noise Interference . . . . . . . . . . . . . 3-4
Protecting the Circuit Board from Contamination. . . . . . 3-5
System Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Mounting the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Minimum Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Panel Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
DIN Rail Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Replacing a Single Module within a System . . . . . . . . . . . . 3-9
Publication 1769-UM008A-EN-P - November 2001
Table of Contents ii
Module Diagnostics and
Troubleshooting
Field Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
System Wiring Guidelines. . . . . . . . . . . . . . . . . . . . . . . 3-10
Removing the Finger-Safe Terminal Block . . . . . . . . . . . 3-14
Wiring the Finger-Safe Terminal Block . . . . . . . . . . . . . 3-15
Analog Input Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Terminal Door Label . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Analog Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
1769-IF4XOF2 Module Data, Status, and Configuration Channels
Chapter 4
Module Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Input/Output/Configuration Data Registers . . . . . . . . . . 4-2
Input Data File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Input Image. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Input Data Words 0 through 3 . . . . . . . . . . . . . . . . . . . 4-4
Input Data Words 4 through 7 . . . . . . . . . . . . . . . . . . . 4-4
Bit Definitions for Input Data . . . . . . . . . . . . . . . . . . . . 4-4
Input Data Resolution and Format . . . . . . . . . . . . . . . . 4-6
Output Data File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Output Data Words 0 and 1 . . . . . . . . . . . . . . . . . . . . . 4-7
Output Data Resolution and Format . . . . . . . . . . . . . . . 4-8
Configuration Data File . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Bit Definitions for Configuration Data . . . . . . . . . . . . . . 4-9
Input Filter Selection . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Chapter 5
Safety Considerations When Troubleshooting . . . . . . . . . . . 5-1
Indicator Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Activating Devices When Troubleshooting . . . . . . . . . . 5-1
Stand Clear of the Machine. . . . . . . . . . . . . . . . . . . . . . 5-2
Program Alteration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Safety Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Module Operation vs. Channel Operation . . . . . . . . . . . . . 5-2
Power-up Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Channel Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Out-of-Range Detection . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Critical vs. Non-Critical Errors . . . . . . . . . . . . . . . . . . . . . . 5-4
I/O Module Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Extended Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Module Condition Errors . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Common Hardware Errors . . . . . . . . . . . . . . . . . . . . . . 5-6
Hardware Specific Errors . . . . . . . . . . . . . . . . . . . . . . . 5-6
Module Inhibit Function . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Contacting Rockwell Automation . . . . . . . . . . . . . . . . . . . . 5-7
Publication 1769-UM008A-EN-P - November 2001
Table of Contents iii
Specifications
Module Addressing and
Configuration with MicroLogix
1500
Appendix A
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Input Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Appendix B
Module Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
1769-IF4XOF2 Input Image. . . . . . . . . . . . . . . . . . . . . . B-2
1769-IF4XOF2 Configuration File . . . . . . . . . . . . . . . . . B-3
Configuring 1769-IF4XOF2 in a MicroLogix 1500 System. . . B-3
Configuring the 1769-IF4XOF2 . . . . . . . . . . . . . . . . . . . B-6
Configuration Using the
1769-IF4XOF2 Combination Analog
Module with a CompactLogix
System
Appendix C
Adding a 1769-IF4XOF2 Module to Your System . . . . . . . . C-1
Thin Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3
Generic Profile. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
Configuring the 1769-IF4XOF2 Analog
Combination Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-5
Accessing the Input and Output Tags. . . . . . . . . . . . . . . . . C-9
Thin Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-9
Generic Profile. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-9
Two’s Complement Binary
Numbers
Appendix D
Positive Decimal Values . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
Glossary
Index
Publication 1769-UM008A-EN-P - November 2001
Table of Contents iv
Publication 1769-UM008A-EN-P - November 2001
1
Preface
Read this preface to familiarize yourself with the rest of the manual.
This preface covers the following topics:
•
Who Should Use This Manual on page P-1
•
How to Use This Manual on page P-1
•
Related Documentation on page P-2
•
Conventions Used in This Manual on page P-2
•
Rockwell Automation Support on page P-3
Who Should Use This
Manual
Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use
Allen-Bradley Compact™ I/O.
How to Use This Manual
As much as possible, we organized this manual to explain, in a task-by-task manner, how to install, configure, program, operate and troubleshoot a control system using the analog I/O modules.
Manual Contents
If you want...
An overview of the analog combination module
A quick start guide for experienced users
Installation and wiring guidelines
Module addressing, configuration and status information
Information on module diagnostics and troubleshooting
Specifications for the combination module
Information on addressing and configuration using MicroLogix 1500 and RSLogix 500
Information on configuring the module using CompactLogix and
RSLogix 5000
Information on understanding two’s complement binary numbers
Definitions of terms used in this manual
See
Publication 1769-UM008A-EN-P - November 2001
P-2
Related Documentation
The table below provides a listing of publications that contain important information about MicroLogix 1500 systems.
For Read this document
A user manual containing information on how to install, use and program your MicroLogix 1500 controller.
MicroLogix™ 1500 User Manual
A user manual containing information on how to install, and use your 1769-ADN DeviceNet Adapter.
DeviceNet Adapter User Manual
A user manual containing information on how to install, use and program your CompactLogix controller.
CompactLogix User Manual
An overview of 1769 Compact Discrete I/O modules 1769 Compact Discrete Input/Output Modules Product
Data
An overview of the MicroLogix 1500 System, including
1769 Compact I/O.
MicroLogix™ 1500 System Overview
In-depth information on grounding and wiring
Allen-Bradley programmable controllers.
Allen-Bradley Programmable Controller Grounding and
Wiring Guidelines
Document number
1764-UM001A-US-P
1769-UM001A-US-P
1769-UM007C-EN-P
1769-2.1
1764-SO001B-EN-P
1770-4.1
If you would like a manual, you can:
• download a free electronic version from the internet at
www.theautomationbookstore.com
• purchase a printed manual by:
– contacting your local distributor or Rockwell Automation representative
– visiting www.theautomationbookstore.com and placing your order
– calling 1.800.963.9548 (USA/Canada) or 001.330.725.1574
(Outside USA/Canada)
Conventions Used in This
Manual
The following conventions are used throughout this manual:
•
Bulleted lists (like this one) provide information not procedural steps.
•
Numbered lists provide sequential steps or hierarchical information.
•
Italic type is used for emphasis.
•
Text in this font indicates words or phrases you should type.
Publication 1769-UM008A-EN-P - November 2001
Rockwell Automation
Support
P-3
Rockwell Automation offers support services worldwide, with over
75 Sales/Support Offices, 512 authorized distributors and 260 authorized Systems Integrators located throughout the United States alone, plus Rockwell Automation representatives in every major country in the world.
Local Product Support
Contact your local Rockwell Automation representative for:
• sales and order support
• product technical training
• warranty support
• support service agreement
Technical Product Assistance
If you need to contact Rockwell Automation for technical assistance,
please review the information in Chapter 5, Module Diagnostics and
Troubleshooting first. Then call your local Rockwell Automation representative.
Your Questions or Comments on the Manual
If you find a problem with this manual, please notify us. If you have any suggestions for how this manual could be made more useful to you, please contact us at the address below:
Rockwell Automation
Automation Control and Information Group
Technical Communication, Dept. A602V
P.O. Box 2086
Milwaukee, WI 53201-2086
Publication 1769-UM008A-EN-P - November 2001
P-4
Publication 1769-UM008A-EN-P - November 2001
1
Chapter
1
Overview
How to Use Analog I/O
This chapter explains how analog data is used and describes the
1769-IF4XOF2 combination analog I/O module. Included is information about:
•
How to Use Analog I/O on page 1-1
•
General Description of the Module’s Hardware and Diagnostic
•
Overview of the Analog System on page 1-4
Analog refers to the representation of numerical quantities by the measurement of continuous physical variables. Analog applications are present in many forms. The following application shows a typical use of analog data.
In this application, the processor controls the amount of fluid in a holding tank by adjusting the valve opening. The valve is initially open 100%. As the fluid level in the tank approaches the preset point, the processor modifies the output to close the valve 90%, 80%, and so on, continuously adjusting the valve to maintain the fluid level.
Analog output wired to valve
Valve
Level Sensor
Controller
Analog input wired to tank
Analog I/O
Module
Publication 1769-UM008A-EN-P - November 2001
1-2 Overview
General Description of the
Module’s Hardware and
Diagnostic Features
The analog input channels convert and digitally store analog data for retrieval by controllers, such as the MicroLogix™ 1500 and
CompactLogix, and from network adapters like the 1769-ADN (Series
B) DeviceNet Adapter. The module supports connections from any combination of up to four voltage or current analog sensors. The four high-impedance input channels can be wired as either single-ended or differential inputs.
The output channels provide two single-ended analog outputs, each individually configurable for voltage or current.
The module provides the following input/output types/ranges:
Table 1.1 Normal and Full Input and Output Ranges
Normal Operating Range
0 to +10V dc
0 to 20 mA
Full Module Range
(1)
0.0 to +10.5V dc
0 to 21 mA
(1) The module provides an overrange band of 0.5V for the 0 to 10V range and 1 mA for the 0 to 20 mA range.
The modules provide the data as raw/proportional data. If scaling to engineering units is required, it must be done in your control program.
Hardware Features
The module has a removable terminal block. The module’s four input channels can be wired as either single-ended or differential inputs.
The module’s two output channels are single-ended only. Module configuration is done via proper wiring of the I/O and the controller’s programming software. In addition, some controllers support configuration via the user program. In either case, the module configuration is stored in the memory of the controller. Refer to your controller’s user manual for more information.
Publication 1769-UM008A-EN-P - November 2001
1
10a
10
10b
Overview 1-3
The following illustration shows the hardware features of the Compact combination analog I/O module.
8a
2a
7a
7a
OK
Analog
DANGER
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous
V in 0 +
V in 1 +
V/I in 1-
V/I in 0-
I in 1 +
V in 3+
I in 1 +
V in 2+
V/I in 2 -
V/I in 3 -
I in 3+
ANGL
Com
V out 1+
I in 2+
ANGL
Com
V out 0+
I out 0+
I out 1+
Ensure Adjacent
Bus Lever is Unlatched/Latched
Before/After
Removing/Inserting Module
1769-IF4XOF2
3
4
5a
9
2b
8a
8b
9
10
5b
6
7a
7b
10a
10b
2b
3
4
5a
Item
1
2a
OK
Analog
7b
7b
8b
Description
bus lever (with locking function) upper panel mounting tab lower panel mounting tab green module status OK LED module door with terminal identification label movable bus connector (bus interface) with female pins stationary bus connector (bus interface) with male pins nameplate label upper tongue-and-groove slots lower tongue-and-groove slots upper DIN rail latch lower DIN rail latch write-on label for user identification tags removable terminal block (RTB) with finger-safe cover
RTB upper retaining screw
RTB lower retaining screw
6
5b
Publication 1769-UM008A-EN-P - November 2001
1-4 Overview
General Diagnostic Features
The module contains diagnostic features that can help you identify the source of problems that may occur during power-up or during normal channel operation. These power-up and channel diagnostics are
explained in Chapter 5, Module Diagnostics and Troubleshooting.
Overview of the Analog
System
The module communicates to the controller through the bus interface.
The module also receives 5 and 24V dc power through the bus interface.
You can install as many analog modules as your power supply can support. However, the 1769-IF4XOF2 module has a power supply distance rating of 8, which means that it may not be located more than
8 modules away from the system power supply. The illustration below shows how power supply distance is determined.
MicroLogix 1500 Controller with Integrated System
Power Supply
OR
1 2 3 4
Power Supply Distance
4 3 2 1 1 2 3
Power Supply Distance
Publication 1769-UM008A-EN-P - November 2001
Overview 1-5
System Operation
At power-up, the module performs a check of its internal circuits, memory, and basic functions. During this time, the module status LED remains off. If no faults are found during power-up diagnostics, the module status LED is turned on.
After power-up checks are complete, the module waits for valid channel configuration data. If an invalid configuration is detected, the module generates a configuration error. Once a channel is properly configured and enabled, it begins the analog-to-digital or digital-to-analog conversion process.
Input Channels
Each time an input channel is read by the module, that analog data value is tested by the module for an over-range condition (e.g. input voltage greater than 10V dc). If such a condition is detected, a unique bit is set in the channel status word. The channel status word is
described in Input Data File on page 4-3.
The controller reads the analog data from the module. This typically occurs at the end of the program scan or when commanded by the control program. If the controller and the module determine that the bus data transfer was made without error, the data is used in your control program.
Output Channels
The module monitors output channels for over-range conditions. If such a condition is detected, a unique bit is set in the channel status
word. The channel status word is described in Output Data File on page 4-7.
The module receives proportional binary values from the bus master
(e.g. controller). This typically occurs at the end of the program scan or when commanded by the control program. If the controller and the module determine that the bus transfer was completed without error, the module converts the data to an analog output signal.
Publication 1769-UM008A-EN-P - November 2001
1-6 Overview
Input
Vin+
CH0
Iin+
(same as CH0)
CH1 CH2 CH3
V/Iin-
A-GND
Output
CH0
Vout+
Module Operation
Module Block Diagram
The module’s input channel circuitry consists of four differential analog inputs multiplexed into a single analog-to-digital (A/D) converter. The A/D converter reads the selected input signal and converts it to a digital value which is presented to the controller. The multiplexer sequentially switches each input channel to the module’s
A/D converter. The module’s output channel uses a digital-to-analog
(D/A) converter to read the digital output data from the controller and convert it to an analog output signal. See the block diagram below.
Galvanic
Isolation
VA1 VS1
VA2
AIN+
A/D
VA3
TXD
ASIC
RXD
Vref
Channel Select
VREF
MCU
VA2
VA2
VA1
DC/DC
Power
Supply
VA2
VA3
VS1
VS2
D/A
VA3
A-GND
S-GND Iout+
A-GND
ANLG COM
CH1
(same as CH0)
A-GND
A-GND
Publication 1769-UM008A-EN-P - November 2001
Module Calibration
The module’s input/output channel calibration is guaranteed by its design. No field calibration is required.
1
Chapter
2
Quick Start for Experienced Users
Before You Begin
Required Tools and
Equipment
This chapter can help you to get started using the analog module. We base the procedures here on the assumption that you have an understanding of Allen-Bradley controllers. You should understand electronic process control and be able to interpret the ladder logic instructions required to generate the electronic signals that control your application.
Because it is a start-up guide for experienced users, this chapter does not contain detailed explanations about the procedures listed. It does, however, reference other chapters in this book where you can get more information about applying the procedures described in each step.
If you have any questions or are unfamiliar with the terms used or concepts presented in the procedural steps, always read the referenced
chapters and other recommended documentation before trying to apply the information.
Have the following tools and equipment ready:
• medium blade or cross-head screwdriver
• analog input or output device
• shielded, twisted-pair cable for wiring (Belden™ 8761 or equivalent)
• controller (for example, a MicroLogix™ 1500 controller)
• analog combination (1769-IF4XOF2) module
• programming device and software (for example, RSLogix 500™)
Publication 1769-UM008A-EN-P - November 2001
2-2 Quick Start for Experienced Users
What You Need To Do
This chapter covers:
•
Verify power supply is adequate on page 2-2
•
Attach and lock the module. on page 2-2
•
Mount the I/O bank. on page 2-3
•
•
Configure the module on page 2-5
•
•
Monitor the module status. on page 2-6
Step 1:
Verify power supply is adequate
Reference
(Installation and Wiring)
Ensure that your power supply has sufficient current output to support your system configuration. The modules maximum current draw is shown below.
Module
1769-IF4XOF2
5V dc
120 mA
24V dc
160 mA
TIP
The module cannot be located more than 8 modules away from the system power supply.
Step 2:
Attach and lock the module.
Reference
(Installation and Wiring) a. Check that the bus lever of the module to be installed is in the unlocked (fully right) position.
b. Use the upper and lower tongue-and-groove slots to secure the modules together (or to a controller).
c. Move the module back along the tongue-and-groove slots until the bus connectors line up with each other.
d. Push the bus lever back slightly to clear the positioning tab. Use your fingers or a small screwdriver.
Publication 1769-UM008A-EN-P - November 2001
Quick Start for Experienced Users 2-3
Step 3:
e. To allow communication between the controller and module, move the bus lever fully to the left until it clicks. Ensure it is locked firmly in place.
ATTENTION
!
When attaching I/O modules, it is very important that the bus connectors are securely locked together to ensure proper electrical connection.
f. Attach an end cap terminator to the last module in the system by using the tongue-and-groove slots as before. g. Lock the end cap bus terminator.
ATTENTION
!
Remove power before removing or inserting this module. When you remove or insert a module with power applied, an electrical arc may occur.
Mount the I/O bank.
Reference
(Installation and Wiring)
Be sure to observe minimum spacing guidelines on page 3-7 for
adequate ventilation.
Publication 1769-UM008A-EN-P - November 2001
2-4 Quick Start for Experienced Users
Step 4:
Wire the module.
Reference
(Installation and Wiring)
The terminal connections are shown below:
V in 1 +
V/I in 1 -
I in 1 +
V in 3 +
V/I in 3 -
I in 3 +
ANLG Com
V out 1 +
I out 1 +
V in 0 +
V/I in 0 -
I in 0 +
V in 2 +
V/I in 2 -
I in 2 +
ANLG Com
V out 0 +
I out 0 +
D A N G E R
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous.
V in 0 +
V in 1 +
V/I in 1 -
V/I in 0 -
I in 0 +
I in 1 +
V in 2 +
V in 3 +
V/I in 2 -
V/I in 3 -
I in 2+
I in 3 +
ANLG
Com
ANLG
Com
V out 0 +
V out 1 +
I out 0 +
I out 1 +
Ensure Adjacent Bus Lever is
Unlatched/Latched Before/After
Removing/Inserting Module
1769-IF4XOF2
Be sure to follow the system wiring guidelines on page 3-10. See
the 1769-IF4XOF2 Wiring Diagram Showing Differential Inputs on
page 3-18 and the Wiring Single-ended Sensor/Transmitter Input
Types on page 3-19 for examples of wiring using differential and
single-ended inputs.
Publication 1769-UM008A-EN-P - November 2001
Quick Start for Experienced Users 2-5
Step 5:
Configure the module
Reference
(Module Data, Status, and
Configuration Channel for
1769-IF4XOF2)
The 1769-IF4XOF2 module is configured for current or voltage operation by proper wiring of the analog I/O device to the module.
However, a channel is enabled using its configuration file.
Table 2.1 Configuration Data File
Bit Position
0
1
15 14 13 12
Not Used
(1)
11 10
9 8 7
EI3
6
EI2
5
EI1
EO1
4
EI0
EO0
2
3
4
5
SGN
SGN
SGN
SGN
Channel 0 Fault Value
Channel 0 Program (Idle) Value
Channel 1 Fault Value
Channel 1 Program (Idle) Value
0
0
0
0
0
0
0
0
0
0
0
0
(1) Any attempt to write a non-valid (1’s) bit configurations into any not used selection field results in a module configuration er ror.
(2) Not all controllers support these functions. Refer to your controller’s user manual for details.
0
0
0
0
3
FM0
(2)
2
PM0
PM1
0
1
Not
Not
0
0
0
0
0
0
0
0
0
0
0
0
The configuration file is typically modified using the programming software configuration screen. It can also be modified through the control program, if supported by the controller. See the configuration
For an example of module configuration using MicroLogix 1500 and
RSLogix 500, see Appendix B. For an example of module
configuration using CompactLogix and RSLogix 5000, see Appendix C.
Publication 1769-UM008A-EN-P - November 2001
2-6 Quick Start for Experienced Users
Step 6:
Step 7:
Start the system.
Reference
(Module Diagnostics and
Troubleshooting) a. Apply power.
b. Download your program, which contains the analog module configuration settings, to the controller and put the controller into
Run mode.
c. During a normal start-up, the module status LED turns on.
d. If the module status LED does not turn on, cycle power. If the condition persists, replace the module.
Monitor the module status.
Reference
Chapter 6
(Module Diagnostics and
Troubleshooting)
Module and channel configuration errors are reported to the controller. These errors are typically reported in the controller’s I/O status file. Check the controller’s I/O file.
Channel status data is also reported in the module’s input data table, so these bits can be used in your control program to flag a channel
error. See Input Data File on page 4-3.
Publication 1769-UM008A-EN-P - November 2001
1
Chapter
3
Installation and Wiring
This chapter tells you about:
•
Compliance to European Union Directives on page 3-1
•
Power Requirements on page 3-2
•
General Considerations to Avoid Electrostatic Damage on page
•
•
Mounting the Module on page 3-6
•
Field Wiring Connections on page 3-10
•
Analog Input Wiring on page 3-16
•
Analog Output Wiring on page 3-21
Compliance to European
Union Directives
This product is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive
The analog modules are tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file:
•
EN 50081-2
EMC – Generic Emission Standard, Part 2 - Industrial
Environment
•
EN 50082-2
EMC – Generic Immunity Standard, Part 2 - Industrial
Environment
This product is intended for use in an industrial environment.
Publication 1769-UM008A-EN-P - November 2001
3-2 Installation and Wiring
Power Requirements
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low
Voltage, by applying the safety requirements of EN 61131-2
Programmable Controllers, Part 2 – Equipment Requirements and
Tests.
For specific information required by EN61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications:
•
Industrial Automation, Wiring and Grounding Guidelines for
Noise Immunity, publication 1770-4.1
•
Automation Systems Catalog, publication B113
The module receives its power through the bus interface from the +5V dc/+24V dc system power supply.
The maximum current drawn by the module is shown in the table below.
Module
1769-IF4XOF2
5V dc
120 mA
24V dc
160 mA
General Considerations to
Avoid Electrostatic Damage
Compact I/O is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use in clean, dry environments (Pollution degree 2
(1)
) and to circuits not exceeding Over Voltage Category II
(2)
(IEC 60664-1).
(3)
Publication 1769-UM008A-EN-P - November 2001
(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation shall be expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
Installation and Wiring 3-3
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations.
WARNING
!
EXPLOSION HAZARD
•
Substitution of components may impair suitability for Class I, Division 2.
•
Do not replace components or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
•
Do not connect or disconnect components unless power has been switched off or the area is known to be non-hazardous.
•
This product must be installed in an enclosure.
•
All wiring must comply with N.E.C. article
501-4(b)
Prevent Electrostatic Discharge
ATTENTION
!
Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins or the terminal block. Follow these guidelines when you handle the module:
•
Touch a grounded object to discharge static potential.
•
Wear an approved wrist-strap grounding device.
•
Do not touch the bus connector or connector pins.
•
Do not touch circuit components inside the module.
•
If available, use a static-safe work station.
•
When not in use, keep the module in its static-shield box.
Publication 1769-UM008A-EN-P - November 2001
3-4 Installation and Wiring
Remove Power
ATTENTION
!
Remove power before removing or inserting this module. When you remove or insert a module with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
• sending an erroneous signal to your system’s field devices, causing unintended machine motion
• causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance.
Reducing Electrical Noise Interference
Most applications require installation in an industrial enclosure to reduce the effects of electrical interference. Analog inputs and outputs are highly susceptible to electrical noise. Electrical noise coupled to the analog inputs will reduce the performance (accuracy) of the module.
Group your modules to minimize adverse effects from radiated electrical noise and heat. Consider the following conditions when selecting a location for the analog module. Position the module:
• away from sources of electrical noise such as hard-contact switches, relays, and AC motor drives
• away from modules which generate significant radiated heat, such as the 1769-IA16. Refer to the module’s heat dissipation specification.
In addition, route shielded, twisted-pair analog input and output wiring away from any high voltage I/O wiring.
Publication 1769-UM008A-EN-P - November 2001
System Assembly
Installation and Wiring 3-5
Protecting the Circuit Board from Contamination
The printed circuit boards of the analog modules must be protected from dirt, oil, moisture, and other airborne contaminants. To protect these boards, the system must be installed in an enclosure suitable for the environment. The interior of the enclosure should be kept clean and the enclosure door should be kept closed whenever possible.
The module can be attached to the controller or an adjacent I/O module or power supply before or after mounting. For mounting
instructions, see Panel Mounting Using the Dimensional Template on
page 3-7, or DIN Rail Mounting on page 3-8. To work with a system
that is already mounted, see Replacing a Single Module within a
The following procedure shows you how to assemble the Compact
I/O system.
C
D
B
A
F
A
E
1. Disconnect power.
2. Check that the bus lever of the module to be installed is in the unlocked (fully right) position.
3. Use the upper and lower tongue-and-groove slots (A) to secure the modules together (or to a controller or power supply).
4. Move the module back along the tongue-and-groove slots until the bus connectors (B) line up with each other.
5. Push the bus lever back slightly to clear the positioning tab (C).
Use your fingers or a small screwdriver.
Publication 1769-UM008A-EN-P - November 2001
3-6 Installation and Wiring
6. To allow communication between the controller and module, move the bus lever fully to the left (D) until it clicks. Ensure it is locked firmly in place.
ATTENTION
!
When attaching I/O modules, it is very important that the bus connectors are securely locked together to ensure proper electrical connection.
7. Attach an end cap terminator (E) to the last module in the system by using the tongue-and-groove slots as before.
8. Lock the end cap bus terminator (F).
IMPORTANT
A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the end of the communication bus.
Mounting the Module
ATTENTION
!
During panel or DIN rail mounting of all devices, be sure that all debris (metal chips, wire strands, etc.) is kept from falling into the module. Debris that falls into the module could cause damage on power up.
Publication 1769-UM008A-EN-P - November 2001
Installation and Wiring 3-7
Minimum Spacing
Maintain spacing from enclosure walls, wireways, adjacent equipment, etc. Allow 50 mm (2 in.) of space on all sides for adequate ventilation, as shown below:
Top
Side Side
Host Controller
Bottom
Panel Mounting
Mount the module to a panel using two screws per module. Use M4 or #8 panhead screws. Mounting screws are required on every module.
Panel Mounting Using the Dimensional Template
For more than 2 modules: (number of modules-1) X 35 mm (1.38 in.).
Refer to host controller documentation for this dimension.
NOTE: All dimensions are in mm (inches).
Hole spacing tolerance: ±0.04 mm (0.016 in.).
132
(5.197)
122.6±0.2
(4.826±0.008)
35
(1.38)
28.5
(1.12)
Publication 1769-UM008A-EN-P - November 2001
3-8 Installation and Wiring
Panel Mounting Procedure Using Modules as a Template
The following procedure allows you to use the assembled modules as a template for drilling holes in the panel. Due to module mounting hole tolerance, it is important to follow these procedures:
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel, and check for proper hole alignment.
6. Attach the modules to the panel using the mounting screws.
TIP
If mounting more modules, mount only the last one of this group and put the others aside.
This reduces remounting time during drilling and tapping of the next group.
7. Repeat steps 1 to 6 for any remaining modules.
DIN Rail Mounting
The module can be mounted using the following DIN rails:
35 x 7.5 mm (EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x
15).
Before mounting the module on a DIN rail, close the DIN rail latches.
Press the DIN rail mounting area of the module against the DIN rail.
The latches will momentarily open and lock into place.
Publication 1769-UM008A-EN-P - November 2001
Installation and Wiring 3-9
Replacing a Single Module within a System
The module can be replaced while the system is mounted to a panel
(or DIN rail). Follow these steps in order:
1. Remove power. See attention note on 3-4.
2. On the module to be removed, remove the upper and lower mounting screws from the module (or open the DIN latches using a flat-blade or phillips-style screwdriver).
3. Move the bus lever to the right to disconnect (unlock) the bus.
4. On the right-side adjacent module, move its bus lever to the right (unlock) to disconnect it from the module to be removed.
5. Gently slide the disconnected module forward. If you feel excessive resistance, check that the module has been disconnected from the bus, and that both mounting screws have been removed (or DIN latches opened).
TIP
It may be necessary to rock the module slightly from front to back to remove it, or, in a panel-mounted system, to loosen the screws of adjacent modules.
6. Before installing the replacement module, be sure that the bus lever on the module to be installed and on the right-side adjacent module are in the unlocked (fully right) position.
7. Slide the replacement module into the open slot.
8. Connect the modules together by locking (fully left) the bus levers on the replacement module and the right-side adjacent module.
9. Replace the mounting screws (or snap the module onto the DIN rail).
Publication 1769-UM008A-EN-P - November 2001
3-10 Installation and Wiring
Field Wiring Connections
Grounding
This product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used) are not required unless the mounting surface cannot be grounded. Refer to Industrial
Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1, for additional information.
System Wiring Guidelines
Consider the following when wiring your system:
General
•
All module commons (ANLG COM) are connected in the analog module. The analog common (ANLG COM) is not connected to earth ground inside the module.
•
Channels are not isolated from each other.
•
Use Belden™ 8761, or equivalent, shielded wire.
•
Under normal conditions, the drain wire and shield junction must be connected to earth ground via a panel or DIN rail mounting screw at the analog I/O module end. Keep the shield connection to ground as short as possible.
(1)
•
To ensure optimum accuracy, limit overall cable impedance by keeping your cable as short as possible. Locate the I/O system as close to your sensors or actuators as your application will permit.
(2)
Inputs
•
If multiple power supplies are used with analog inputs, the power supply commons must be connected.
•
The module does not provide loop power for analog inputs. Use a power supply that matches the input transmitter specifications.
•
Differential analog inputs are more immune to noise than single-ended analog inputs.
•
Voltages on Vin+, V/Iin-, and Iin+ of the module must be within
0 to +10V dc of analog common.
Publication 1769-UM008A-EN-P - November 2001
(1) In environments where high-frequency noise may be present, it may be necessary to directly ground cable shields to earth at the module end and via a 0.1µF capacitor at the sensor end.
(2) Cable length over 50 meters may impact accuracy., For details, refer to the
Compact Combination Analog I/O Module, publication 1769-UM008A-EN-P.
Installation and Wiring 3-11
Outputs
•
Voltage outputs (Vout 0+ and Vout 1+) of the module are referenced to ANLG COM. Load resistance for a voltage output channel must be equal to or greater than 1K
Ω
.
•
Current outputs (Iout 0+ and Iout 1+) of the module source current that returns to ANLG COM. Load resistance for a current output channel must remain between 0 and 300
Ω
.
ATTENTION
Be careful when stripping wires. Wire fragments that fall into a module could cause damage at power up. Once wiring is complete, ensure the module is free of all metal fragments.
!
Effect of Transducer/Sensor and Cable Length Impedance on Voltage Input
Accuracy
For voltage inputs, the length of the cable used between the transducer/sensor and the module can affect the accuracy of the data provided by the module.
Rs Rc
Vs
+
-
V in
Ri
Rc
Where:
Rc = DC resistance of the cable (each conductor) depending on
cable length
Rs = Source impedance of analog transducer/sensor input
Ri = Impedance of the voltage input (150 K
Ω
)
Vs = Voltage source (voltage at the transducer/sensor input
device)
Vin = Measured potential at the module input
%Ai = Percent added inaccuracy in a voltage-based system due
to source and cable impedance.
Vin
=
[
Rs
+
[
(
Ri
2
×
×
Vs
Rc
)
]
+
Ri
]
Publication 1769-UM008A-EN-P - November 2001
3-12 Installation and Wiring
For example, for Belden 8761 two conductor, shielded cable:
Rc = 16
Ω
/1000 ft
Rs = 0 (ideal source)
Table 3.1 Effect of Cable Length on Input Accuracy
Length of Cable (m)
50
100
200
300
dc resistance of the
2.625
5.25
10.50
15.75
cable, Rc (
Ω
)
Accuracy impact at the input module
0.00350%
0.00700%
0.01400%
0.02100%
%
Ai = 1
–
Vin

Vs
×
100
As input source impedance (Rs) and/or resistance (dc) of the cable
(Rc) get larger, system accuracy decreases. If you determine that the inaccuracy error is significant, implementing the following equation in the control program can compensate for the added inaccuracy error due to the impedance of the source and cable.
Vs = Vin
×
[
Rs +
(
2 Rc
)
Ri
+ Ri
]
TIP
In a current loop system, source and cable impedance do not impact system accuracy.
Publication 1769-UM008A-EN-P - November 2001
Installation and Wiring 3-13
Effect of Device and Cable Output Impedance on Output Accuracy
The maximum value of the output impedance is shown in the example below, because it creates the largest deviation from an ideal voltage source.
Rs Rc
+
Vs
-
V in
Ri
Rc
Where:
Rc = DC resistance of the cable (each conductor)
depending on cable length
Rs = Source impedance of the 1769-IF4XOF2 output (10
Ω
)
Ri = Impedance of the voltage input (150 K
Ω for the voltage input channel of the 1769-IF4XOF2)
Vs = Voltage at the output
Vin = Measured potential at the module input
%Ai = Percent added inaccuracy in a voltage-based
system due to source and cable impedance.
Vin =
[
Rs +
[
(
Ri
2
×
×
Vs
Rc
)
]
+ Ri
]
For example, for Belden 8761 two conductor, shielded cable and an input channel:
Rc = 16
Ω
/1000 ft
Rs = 10
Ω
Ri = 150 K
Ω
%
Ai = 1
–
Vin

Vs
×
100
Table 3.2 Effect of Output Impedance and Cable Length on Accuracy
Length of Cable (m)
50
100
200
300
dc resistance of the cable
Rc (
Ω
2.625
5.25
10.50
15.75
)
Accuracy impact at the input module
0.01017%
0.01366%
0.02066%
0.02766%
Publication 1769-UM008A-EN-P - November 2001
3-14 Installation and Wiring
As output impedance (Rs) and/or resistance (dc) of the cable (Rc) get larger, system accuracy decreases. If you determine that the inaccuracy error is significant, implementing the following equation in the control program can compensate for the added inaccuracy error due to the impedance of the output module and cable.
Vs = Vin
×
[
Rs
+
(
2
Rc
)
Ri
+
Ri
]
TIP
In a current loop system, source and cable impedance do not impact system accuracy.
Removing the Finger-Safe Terminal Block
When wiring field devices to the module, it is not necessary to remove the terminal block. If you remove the terminal block, use the write-on label on the side of the terminal block to identify the module slot location and type.
SLOT # _____
MODULE TYPE ______
Publication 1769-UM008A-EN-P - November 2001
Installation and Wiring 3-15
To remove the terminal block, loosen the upper and lower retaining screws. The terminal block will back away from the module as you remove the screws. When replacing the terminal block, torque the retaining screws to 0.46 Nm (4.1 in-lbs).
upper retaining screw wiring the finger-safe terminal block lower retaining screw
Wiring the Finger-Safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1. Loosen the terminal screws to be wired.
2. Route the wire under the terminal pressure plate. You can use the bare wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.
TIP
The terminal screws are non-captive.
Therefore, it is possible to use a ring lug
[maximum 1/4 inch o.d. with a 0.139 inch minimum i.d. (M3.5)] with the module.
3. Tighten the terminal screw making sure the pressure plate secures the wire. Recommended torque when tightening terminal screws is 0.68 Nm (6 in-lbs).
TIP
If you need to remove the finger-safe cover, insert a screw driver into one of the square wiring holes and gently pry the cover off. If you wire the terminal block with the finger-safe cover removed, you will not be able to put it back on the terminal block because the wires will be in the way.
Publication 1769-UM008A-EN-P - November 2001
3-16 Installation and Wiring
Solid
Stranded
Wire Type
Cu-90°C (194°F)
Cu-90°C (194°F)
Analog Input Wiring
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
Wire Size
#14 to #22 AWG
#16 to #22 AWG
Terminal Screw Torque
0.68 Nm (6 in-lbs)
0.68 Nm (6 in-lbs)
Retaining Screw Torque
0.46 Nm (4.1 in-lbs)
0.46 Nm (4.1 in-lbs)
ATTENTION
!
To prevent shock hazard, care should be taken when wiring the module to analog signal sources. Before wiring any analog module, disconnect power from the system power supply and from any other source to the analog module.
After the analog module is properly installed, follow the wiring procedure below. To ensure proper operation and high immunity to electrical noise, always use Belden™ 8761 (shielded, twisted-pair) or equivalent wire.
ATTENTION
!
When wiring an analog input, take care to avoid connecting a voltage source to a channel configured for current input. Improper module operation or damage to the voltage source can occur.
Never connect a voltage or current source to an analog output channel.
Publication 1769-UM008A-EN-P - November 2001 cable
Cut foil shield and drain wire signal wire signal wire drain wire foil shield signal wire signal wire
To wire your module follow these steps.
1. At each end of the cable, strip some casing to expose the individual wires.
2. Trim the signal wires to 2-inch lengths. Strip about 3/16 inch (5 mm) of insulation away to expose the end of the wire.
Installation and Wiring 3-17
ATTENTION
Be careful when stripping wires. Wire fragments that fall into a module could cause damage at power up.
!
3. At one end of the cable, twist the drain wire and foil shield together.
Under normal conditions, this drain wire and shield junction must be connected to earth ground, via a panel or DIN rail mounting screw at the analog I/O module end. Keep the length of the drain wire as short as possible.
In environments where high frequency noise may be present, the cable shields should be grounded via a 0.1 µF capacitor at the end using the data. In other words, for analog inputs, the cable shield should be grounded via the 0.1 µF capacitor at the analog module end. For analog outputs, the cable shield should be grounded via a 0.1 µF capacitor at the load end.
4. At the other end of the cable, cut the drain wire and foil shield back to the cable.
5. Connect the signal wires to the terminal block as shown in
input or output device.
6. Repeat steps 1 through 5 for each channel on the module.
Publication 1769-UM008A-EN-P - November 2001
3-18 Installation and Wiring
Publication 1769-UM008A-EN-P - November 2001
Terminal Door Label
A removable, write-on label is provided with the module. Remove the label from the door, mark the identification of each terminal with permanent ink, and slide the label back into the door. Your markings
(ID tag) will be visible when the module door is closed.
V in 1 +
V/I in 1 -
I in 1 +
V in 3 +
V/I in 3 -
I in 3 +
ANLG Com
V out 1 +
I out 1 +
V in 0 +
V/I in 0 -
I in 0 +
V in 2 +
V/I in 2 -
I in 2 +
ANLG Com
V out 0 +
I out 0 +
D A N G E R
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous.
V in 0 +
V in 1 +
V/I in 1 -
V/I in 0 -
I in 0 +
I in 1 +
V in 2 +
V in 3 +
V/I in 2 -
V/I in 3 -
I in 2+
I in 3 +
ANLG
Com
ANLG
Com
V out 0 +
V out 1 +
I out 0 +
I out 1 +
Ensure Adjacent Bus Lever is
Unlatched/Latched Before/After
Removing/Inserting Module
1769-IF4XOF2
Wiring Diagram Showing Differential Inputs
V in 1+
V/I in 1 -
I in 1+
V in 3+
V/I in 3 -
I in 3+
ANLG Com
V out 1+
I out 1+
V in 0+
V/I in 0-
I in 0+
V in 2 +
V/I in 2-
I in 2+
ANLG Com
V out 0+
I out 0+
1769-IF4XOF2 Terminal Block
+
–
earth ground the shield locally at
the module differential voltage transmitter
Belden 8761 cable (or equivalent)
(1) All analog commons (ANLG Com) are internally connected.
(2) If multiple power supplies are used, the commons must have the same ground reference.
(3) User Belden 8761 cable (or equivalent) for wiring analog I/O.
Wiring Single-ended Sensor/Transmitter Input Types
Installation and Wiring 3-19
1769-IF4XOF2 Terminal Block
Sensor/
Transmitter
+
Power
Supply
(1)
-
+
Current
Transmitter
Signal
Voltage Transmitter
+
Ground Signal
(1) The sensor power supply must be rated Class 2.
(2) All analog commons (ANLG Com) are internally connected.
(3) If multiple power supplies are used, the commons must have the same ground reference.
(4) User Belden 8761 cable (or equivalent) for wiring analog I/O.
V/I in 2-
V in 3+
I in 3+
V/I in 3-
ANLG Com
ANLG Com
V out 0+
I out 0+
V out 1+
I out 1 +
V in 0+
I in 0+
V/I in 0 -
V in 1+
I in 1+
V/I in 1-
V in 2+
I in 2+
Publication 1769-UM008A-EN-P - November 2001
3-20 Installation and Wiring
Wiring Mixed Transmitter Input Types
Single-ended
Voltage
–
Transmitter
+
Signal
–
Differential
Voltage
Transmitter
Supply
+
+
–
Signal
+
–
Signal
–
Differential
Current
Transmitter
Supply
+
2-Wire
Current
Transmitter
+
Signal
Sensor/
Transmitter
Power Supply
(1)
+
–
1769-IF4XOF2 Terminal Block
V in 0+
I in 0+
V/I in 0 -
V in 1+
I in 1+
V/I in 1-
V in 2+
I in 2+
V/I in 2-
V in 3+
I in 3+
V/I in 3-
ANLG Com
ANLG Com
V out 0+
I out 0+
V out 1+
I out 1 +
(1) The sensor power supply must be rated Class 2.
(2) All analog commons (ANLG Com) are internally connected.
(3) If multiple power supplies are used, the commons must have the same ground reference.
(4) User Belden 8761 cable (or equivalent) for wiring analog I/O.
Publication 1769-UM008A-EN-P - November 2001
Installation and Wiring 3-21
Analog Output Wiring
ATTENTION
!
To prevent shock hazard, care should be taken when wiring the module to analog signal sources. Before wiring any analog module, disconnect power from the system power supply and from any other source to the analog module.
Voltage Load
Current Load
Earth Ground
V in 0+
I in 0+
V/I in 0 -
V in 1+
I in 1+
V/I in 1-
V in 2+
I in 2+
V/I in 2-
V in 3+
I in 3+
V/I in 3-
ANLG Com (1)
ANLG Com
(1)
V out 0+
I out 0+
V out 1+
I out 1 +
Earth Ground
(1) All analog common terminals (ANLG Com) are internally connected in the module.
Publication 1769-UM008A-EN-P - November 2001
3-22 Installation and Wiring
Publication 1769-UM008A-EN-P - November 2001
1
Chapter
4
1769-IF4XOF2 Module Data, Status, and
Configuration Channels
Module Addressing
slot e
Input Image File slot e
Configuration
File slot e
Output Image
File
This chapter examines the 1769-IF4XOF2 module’s data table, channel status, and channel configuration word:
•
•
•
•
Configuration Data File on page 4-8
The following memory map shows the input, output, and configuration image tables. Detailed information on the input image
table can be found in Input Image on page 4-3.
Input Image
8 words
Configuration File
6 words
Output Image
2 words
Memory Map
Channel 0 Input Word
Channel 1 Input Word
Channel 2 Input Word
Channel 3 Input Word
Over-range Bits - Inputs
Over-range Bits - Outputs
Channel 0 Output Loopback
Channel 1 Output Loopback
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6, bits 7 to 14
Word 7, bits 7 to 14
Configuration Word
Configuration Word
Output Channel 0 Fault Value
Output Channel 0 Program (Idle) Value
Output Channel 1 Fault Value
Output Channel 1 Program (Idle) Value
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Bit 15
Channel 0 Output Data Word
Channel 1 Output Data Word
Bit 0
Word 0
Word 1
Publication 1769-UM008A-EN-P - November 2001
4-2 1769-IF4XOF2 Module Data, Status, and Configuration Channels
Input/Output/Configuration Data Registers
Data registers are available for input, output, and configuration. There are eight input data registers, six configuration registers, and two output data registers. The module and programming software applies the following default values to the registers:
I:5
I:6
I:7
O:0
O:1
I:0
I:1
I:2
I:3
I:4
Table 4.1 Data Registers
Register
C:0
C:1
C:2
C:3
C:4
C:5
Function
Configuration Word 1
Configuration Word 2
Configuration - Channel 0
Fault Value
Configuration - Channel 0
Program Value
Configuration - Channel 1
Fault Value
Default at
Power-Up
0000h
0000h
0000h
0000h
0000h
Configuration - Channel 1
Program Value
Channel 0 Input Word
Channel 1 Input Word
Channel 2 Input Word
Channel 3 Input Word
Input Channel Over-range
0000h
Output Channel Over-range 0000h
Channel 0 Output Data Echo 0000h
Channel 1 Output Data Echo 0000h
Channel 0 Output Word
Channel 1 Output Word
0000h
0000h
0000h
0000h
0000h
0000h
0000h
Programming Software
Default Down Load
0000h
0000h
0000h
0000h
0000h
0000h
0000h
0000h
Publication 1769-UM008A-EN-P - November 2001
1769-IF4XOF2 Module Data, Status, and Configuration Channels 4-3
Input Data File
The input data file provides access to analog input data for use in the control program. Input data resolution is 8 bits with the least significant 7 bits (0 to 6) permanently set to zero (0) by the module. In addition, over-range indication for the input and output channels, and output data feedback is provided as described below.
Table 4.2 Input Data File
0
1
2
3
4
5
6
7
15
SGN
SGN
SGN
SGN
Not
SGN
SGN
14
H0
13 12 11 10 9
Analog Input Data Value Channel 0
Analog Input Data Value Channel 1
Analog Input Data Value Channel 2
Bit Position
8 7
Not
Used
Analog Input Data Value Channel 3
Not Used
(1)
H1
Not Used
Output Data Echo/Loopback for Output Channel 0
Output Data Echo/Loopback for Output Channel 1
(1) All unused bits are set to 0 by the module.
6
0
0
0
0
0
0
5
0
0
0
0
0
0
4
0
0
0
0
0
0
3
0
0
0
0
I3
E1
0
0
2
0
0
0
0
I2
E0
0
0
1
0
0
0
0
I1
O1
0
0
0
0
0
0
0
I0
O0
0
0
Input Image
The input image file represents input channel data words I/O, and I/O channel status bits. Input words 0 through 3 contain the converted analog input data from the field device. Word 4, bit 1,2 and 3 are the over-range flag bits for input channels 0 to 3. Word 5, bit 0 and 1 are the over-range flag bits for output channels 0 and 1. Words 6 and 7, bits 7 through 14 are the data echo. These words provide output channel loopback/data echo from output channels 0 and 1 through
the input array. See Input Data File on page 4-3 for more information.
TIP
You can access information in the input image file using the programming software configuration screen.
Publication 1769-UM008A-EN-P - November 2001
4-4 1769-IF4XOF2 Module Data, Status, and Configuration Channels
15
SGN
14
A7
13
A6
12
A5
11
A4
10
A3
Input Data Words 0 through 3
All bits shown as 0 (bits 0 through 6) are always set to 0. Bits 7 through 14 contain the 8 input data bits. The table below illustrates the format of the input data, words 0 to 3.
9
A2
8
A1
7
A0
6
0
5
0
4
0
3
0
2
0
1
0
0
0
Input Data Words 4 through 7
These words contain diagnostic and control information. For details
see Bit Definitions for Input Data below.
Bit Definitions for Input Data
Sign Bit (SGN)
The sign bit is always positive (equal to zero).
Over Input Range Flag Bits (I0 to I3)
Word 4, bits 0 to 3 (i0 to I3) contain over-range flag bits for input channels 0 through 3 respectively. These bits can be used in the control program for error detection. When set to 1, the bits signal that the input signal is outside the normal operating range. However, the module continues to convert analog data to the maximum full-range value. When the over-range condition is cleared, the bits automatically reset to (0).
Over Output Range Flag Bits (O0 and O1)
Word 5, bits 0 and 1 (O0 and O1) provide over-range indication for output channels 0 and 1. These bits can be used in the control program for error detection. When set to 1, the bits signal that the output signal is outside the normal operating range. However, the module continues to convert analog data to the maximum full-range value. When the over-range condition is cleared, the bits automatically reset to 0.
TIP
Under-range indication is not provided for the
1769-IF4OXF2 because zero is a valid number.
Refer to Table 4.9 Valid Input Data on page 4-14 to
view the normal operating and over-range areas.
Publication 1769-UM008A-EN-P - November 2001
1769-IF4XOF2 Module Data, Status, and Configuration Channels 4-5
Invalid Data Set (Ex)
Word 5, bits 2 and 3 provide invalid output data indication for output channels 0 and 1, respectively. When either invalid output data bit is set to 1, it indicates that invalid output data has been sent by the controller to that channel of the module. When this occurs, the module sets the appropriate (Ex) flag and continues to operate with the previously accepted data.
NOTE: Invalid data is a value outside the standard range or increment.
For example, 128, 256, etc. or by writing to bits 0 though 6 and bit 15.
Hold Last State (Hx)
Word 5, bits 12 and 14, indicates that the channel is in a hold last state condition when set to 1.
IMPORTANT
Not all controllers support Hold Last State functionality. Refer to your controller’s user manual.
Analog Output Loopback/Data Echo
Input words 6 and 7, bits 7-14, reflect the analog output data echo of the analog value being converted by the digital/analog converter, not necessarily the electrical state of the output terminals. They do not reflect shorted or open outputs.
IMPORTANT
Input words 6 and 7 contain the Output Data
Echo/Loopback information for output channels 0 and 1 respectively. Bits 0 through 6 and Bit 15 of words 6 and 7 should always be set to zero in your control program, or the module will set the Invalid
Data Set (Ex) flag.
IMPORTANT
It is only important to use the loopback function of input words 6 and 7 if the controller supports the
Program Mode or Fault Mode functions, and if it is configured to use them.
Publication 1769-UM008A-EN-P - November 2001
4-6 1769-IF4XOF2 Module Data, Status, and Configuration Channels
Input Data Resolution and Format
Table 4.3 Input Data Resolution and Format
Full Input Range
0V to 10.5V dc
0 mA to 21 mA
Significant Bits
Sign + 8 bits
Sign + 8 bits
The following table identifies the current and voltage input ranges for the 1769-IF4XOF2 module, and the number of significant bits provided by the module with its single (non-programmable) filter. The number of significant bits indicated in the table has little or no jitter due to noise. The module’s RAW/Proportional data format presents the value to the controller via a left justified 16-bit field, with the most significant bit for the sign bit (which is always zero).
Resolution per LSB
41.18mV
82.35mA
RAW/Proportional Data
Decimal Representation of Input
0 to 32640
0 to 32640
Count Value
128 (1LSB)
128 (1LSB)
Input Scaling
Example 1: Find voltage by converting raw/proportional data values
To convert a raw/proportional data value to find the voltage being measured:
Voltage = (Input Data Value X volts/significant bit) /
(counts/significant bit)
If input data value is 32,640
Voltage = (32640 X 0.04118V) / 128
= 10.50 Volts
Example 2: Find current by converting raw/proportional data values
To convert a raw/proportional data value to find the current being measured:
Current = (Input Data Value X amps/significant bit) /
(counts/significant bit)
If the input data value is 31,104
Current = (31,104 X 0.08235A) /128
= 20 mA
Publication 1769-UM008A-EN-P - November 2001
1769-IF4XOF2 Module Data, Status, and Configuration Channels 4-7
Output Data File
The output file contains the module’s analog output data information.
Word 0 and 1, bits 7 through 14 contain the output data bits for channels 0 and 1.
The output data file applies only to output data from the module as shown in the table below.
Table 4.4 Output Data File
0
1
15
SGN
SGN
14 13 12 11 10 9
Analog Output Data Channel 0
Analog Output Data Channel 1
Bit Position
8 7 6
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
0
0
0
15
SGN
14
A7
13
A6
12
A5
Output Data Words 0 and 1
11
A4
The SGN bit of Words 0 and 1 is always zero (0). The following table illustrates the format of the output data.
10
A3
9
A2
8
A1
7
A0
6
0
5
0
4
0
3
0
2
0
1
0
0
0
IMPORTANT
Bits 0 through 6 and Bit 15 of output data words 0 and 1 should always be set to zero in your control program. If they are not set to 0, the invalid data flag
(Ex) will be set for that channel. However the channel will continue to operate with the previously converted value. If a MVM (Move with Mask) instruction is used with a mask of 7F80 (hexidecimal) to move data to the output words, writing to bits 0 through 6 and bit 15 can be avoided.
Publication 1769-UM008A-EN-P - November 2001
4-8 1769-IF4XOF2 Module Data, Status, and Configuration Channels
Output Data Resolution and Format
Table 4.5 Output Resolution
Full Output Range
Significant Bits
0V to 10.5 V dc
0 mA to 21 mA
Sign + 8 bits
Sign + 8 bits
The resolution of an analog output channel depends on the output type/range and data format selected. The following table provides detailed resolution information for the module.
RAW/Proportional Data
Resolution per LSB Decimal
Representation of
Output
41.18mV
0 to 32640
82.35mA
0 to 32640
Count Value
128 (1LSB)
128 (1LSB)
Configuration Data File
The configuration file allows you to enable or disable an input or output channel. It also allows you to configure the operation of the outputs during a mode change to Program or a Fault condition.
Word 0 bits 4, 5, 6 and 7 allow the individual input channels to be enabled or disabled. Word 1 bits 4 and 5 allow the individual output channels to be enabled or disabled.
TIP
Not all controllers support program access to the configuration file. Refer to your controller’s user manual.
Publication 1769-UM008A-EN-P - November 2001
1769-IF4XOF2 Module Data, Status, and Configuration Channels 4-9
The manipulation of the bits from this file is normally done with programming software (e.g. RSLogix 500, RSLogix 5000, RSNetworx for DeviceNet, etc.) during initial configuration of the system. In that case, graphical screens are typically provided by the programmer to simplify configuration. However, some systems, like the 1769-ADN
DeviceNet Adapter, also allow the bits to be altered as part of the control program, using communication rungs. In that case, it may be beneficial to understand the bit arrangement.
Table 4.6 Configuration Data File
0
1
15 14 13 12
Not Used
(1)
11 10
9 8
Bit Position
7
EI3
6
EI2
5
EI1
EO1
4
EI0
EO0
3
FM0
(2)
2
PM0
FM1
PM1
2
3
4
5
SGN
SGN
SGN
SGN
Channel 0 Fault Value
Channel 0 Program (Idle) Value
Channel 1 Fault Value
Channel 1 Program (Idle) Value
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
(1) Any attempt to write a non-valid (1’s) bit configurations into any not used selection field results in a module configuration er ror.
(2) Not all controllers support these functions. Refer to your controller’s user manual for details.
0
0
0
0
1
Not
Used
Not
Used
0
0
0
0
0
0
0
0
0
Bit Definitions for Configuration Data
Sign Bit (SGN)
The sign bit is always positive (Bit 15 = zero).
Enable/Disable Input Channel (EIx)
Word 0 bits 4 to 7 (EI0 to EI3) are defined as the input channel enable/disable bits. These bits allow individual input channels 0 through 3 to be enabled (on) or disabled (off). When a channel is not enabled, the module provides no current or voltage input to the host controller.
Publication 1769-UM008A-EN-P - November 2001
4-10 1769-IF4XOF2 Module Data, Status, and Configuration Channels
Enable/Disable Output Channel (EOx)
Word 1 bits 4 and 5 (EO0 and EO1) are defined as the output channel enable/disable bits. EOx bits allow individual output channels 0 and 1 to be enabled or disabled. When a channel is not enabled, the module does not produce current or voltage.
TIP
To improve performance and speed, disable unused channels.
Publication 1769-UM008A-EN-P - November 2001
Program/Idle Mode Selection Channel 0 and 1 (PM0 and PM1)
These bits provide Program (Idle) Mode selection for analog output channels 0 (Word 0 Bit 2) and 1 (Word 1 Bit 2).
•
Hold Last State (0) – When reset (to 0), this bit directs the module to hold the analog output at the last converted value when the module transitions from Run to Program Mode. This is the default channel condition.
IMPORTANT
Hold last state is the default condition for the module during a control system run-to-program mode change.
TIP
MicroLogix 1500™ does not support the analog output module’s default hold last state function and resets analog outputs to zero when the system enters the program mode.
•
User-Defined Safe State (1) – When this bit is set (to 1) and the module transitions to Program mode, the module converts the user-specified integer value from the Channel x Program Value
Word (3 or 5) to the appropriate analog output.
Fault Mode Selection Channel 0 and 1 (FM0 and FM1)
FM0 and FM1 bits provide Fault Mode selection for analog output channels 0 (Word 0 Bit 3) and 1 (Word 1 Bit 3). When this selection is disabled [the bit is reset (0)] and the system transitions from Run to
Fault mode, the module holds the last output state value. This means
1769-IF4XOF2 Module Data, Status, and Configuration Channels 4-11 that the analog output remains at the last converted value prior to the condition that caused the system to enter the fault mode.
IMPORTANT
Hold last state is the default condition for the module during a control system run-to-fault mode change.
TIP
MicroLogix 1500 does not support the analog output module’s default hold last state function and resets analog outputs to zero when the system enters the fault mode.
•
Hold Last State (0) – When reset, this bit directs the module to hold the analog output at the last converted value when the module transitions to Fault Mode. This is the default condition.
•
User-Defined Safe State (1) – When this bit is set and the module transitions to Fault mode, the module converts the user-specified integer value from the Channel x Fault Value Word (2 or 4) to the appropriate analog output for the configured range as wired.
If the default value, 0000, is entered, the output converts to the minimum value for the range selected.
TIP
Not all controllers support this function. Refer to your controller’s user manual for details.
Program to Fault Enable Selection (PFE0 and PFE1)
The Program to Fault Enable bit determines which data value,
Program (PFEx = 0) or Fault (PFEx = 1), is applied to the output if the module undergoes a fault condition while in the Program Mode, resulting in a change to Fault Mode. Word 0 Bit 0 applies to channel 0, while Word 1 Bit 0 applies to channel 1.
•
Program Value (Channel 0 and 1) – Words 3 and 5 allow you to enter the integer values that output Channel 0 (Word 3) and output Channel 1 (Word 5) should assume when the system transitions to the Program mode. The value must be in increments of 128 (0, 128, 256, etc.) for proper operation. If the value entered is outside the acceptable increment or range, the module generates a configuration error for that channel. The module default value is zero.
Publication 1769-UM008A-EN-P - November 2001
4-12 1769-IF4XOF2 Module Data, Status, and Configuration Channels
•
Fault Value (Channel 0 and 1) – Words 2 and 4 allow you to enter the integer values that output Channel 0 (Word 2) and output Channel 1 (Word 4) should assume when the system transitions to the Fault mode. The value must be in increments of 128 (0, 128, 256, etc.) for proper operation. If the value entered is outside the acceptable increment or range, the module generates a configuration error for that channel. The module default value is zero.
IMPORTANT
PMx, FMx, PFEx, Channel x Program (Idle) Value, and Channel x Fault Value functions are not supported by all controllers. Refer to your controller’s user manual for details.
Input Filter Selection
The 1769-IF4XOF2 has a fixed input filter. No configuration is required.
Channel Step Response
The module’s fixed filter frequency determines the channel’s step response. The step response is the time required for the analog input signal to reach 63% or 90% of its expected final value. This means that if an input signal changes faster than the channel step response, a portion of that signal will be attenuated by the channel filter.
Table 4.7 Filter Frequency and Step Response
Fixed Filter Frequency Filter Cut-Off Frequency
2.7 kHz
2.7 kHz
2.7 kHz
2.7 kHz
Step Response
% Complete
63%
90%
Step Response
Time
59 us
136 us (Nominal)
Channel Cut-Off Frequency
The -3 dB frequency is the filter cut-off frequency. The cut-off frequency is defined as the point on the input channel frequency response curve where the frequency components of the input signal are passed with 3 dB of attenuation. All input frequency components at or below the cut-off frequency are passed by the digital filter with less than 3 dB of attenuation. All frequency components above the cut-off frequency are increasingly attenuated.
Publication 1769-UM008A-EN-P - November 2001
Input Signal
Input After Filter
A/D Conversion (4 CH)
MPU/ASIC Input Data
Communication
MPU/ASIC Output Data
Communication
Output D/A Conversion
1769-IF4XOF2 Module Data, Status, and Configuration Channels 4-13
Module Input Update Time and Scanning Process
The module input update time is defined as the time required for the module to sample and convert the input signals of all 4 enabled input channels and provide the resulting data values to the processor.
Maximum Input Response Time of Module (5 ms)
Minimum Input Response
Time of Module (5 ms)
Input Update Time (4.5 ms)
Module update time can be calculated by adding the sum of all enabled channel times. Channel times include channel scan time, channel switching time, and reconfiguration time. The module sequentially samples the channels in a continuous loop. The table below shows module update times, based on the number of input channels enabled.
Table 4.8 Module Update Time
Number of Enabled Input Channels
2
3
0
1
4
Typical Update Time
(1)
1.3 ms
2.1 ms
2.9 ms
3.7 ms
4.5 ms
(1) Each enabled output channel adds 0.02 ms to the typical module update time.
Publication 1769-UM008A-EN-P - November 2001
4-14 1769-IF4XOF2 Module Data, Status, and Configuration Channels
Analog Range Selection
The analog input range selection is accomplished by proper wiring of the input channels.
Valid Input Data Word Formats/Ranges
The analog input data received at the module is converted to
RAW/proportional data format. Unlike the 1769-IF4 and 1769OF2. on-board scaling is not provided by the module. You must do this via your control program.
The following table shows the valid input data format for the data range provided by the module.
Table 4.9 Valid Input Data
Input Range
0 to +10V dc
0 to 20 mA
Input Value
Over 10.5V dc
+10.5V dc
0.0V dc to
+10.0V dc
Over 21.0 mA
21.0 mA
0.0 mA to 20.0 mA
Example Data
+11.0V dc
+ 10.5V dc
+10.0V dc
5.0V dc
0.0V dc
+22.0 mA
+21.0 mA
+20.0 mA
+10.0 mA
0.0 mA
Input Range
Condition
Over-range
(1)
Over-range
Normal
Normal
Normal
Over-range
Over-range
Normal
Normal
Normal
Raw/Proportional Data
Decimal Range
32640
32640
31104
15488
0
32640
32640
31104
15488
0
(1) The module’s maximum range is 10.5V or 21 mA. An over-range flag is set at either value. This flag automatically resets when the input data is below the over-range value.
Publication 1769-UM008A-EN-P - November 2001
1769-IF4XOF2 Module Data, Status, and Configuration Channels 4-15
Valid Output Data Word Formats/Ranges
The analog output data received at the module is converted to
RAW/proportional data format. Unlike the 1769-IF4 and 1769OF2. on-board scaling is not provided by the module. You must do this via your control program.
The following table shows the valid output data format for the data range provided by the module.
Table 4.10 Valid Output Data
Output Range
0 to 10V dc
0 to 20mA
Output Value
Over +10.5V dc
+10.5V dc
0.0V dc to
+10.0V dc
Over 21.0 mA
21.0 mA
0.0 mA to 20.0 mA
Example Data
N/A
+ 10.5V dc
+10.0V dc
+5.0V dc
0.0V dc
N/A
21.0 mA
20.0 mA
10.0 mA
0.0 mA
Output Range
Condition
N/A
(1)
Over-range
Normal
Normal
Normal
N/A
Over-range
Normal
Normal
Normal
Raw/Proportional Data
Decimal Range
N/A
32640
31104
15488
0
N/A
32640
31104
15488
0
(1) The module’s maximum range is 10.5V or 21 mA. An over-range flag is set at either value. This flag automatically resets when the output data is below the over-range value.
Publication 1769-UM008A-EN-P - November 2001
4-16 1769-IF4XOF2 Module Data, Status, and Configuration Channels
Publication 1769-UM008A-EN-P - November 2001
Chapter
5
Module Diagnostics and Troubleshooting
1
Safety Considerations
When Troubleshooting
This chapter describes troubleshooting the analog input and output channels. This chapter contains information on:
•
Safety Considerations When Troubleshooting on page 5-1
•
Module Operation vs. Channel Operation on page 5-2
•
Module Diagnostic Features on page 5-3
•
Critical vs. Non-Critical Errors on page 5-4
•
Module Condition Errors on page 5-6
Safety considerations are an important element of proper troubleshooting procedures. Actively thinking about the safety of yourself and others, as well as the condition of your equipment, is of primary importance.
The following sections describe several safety concerns you should be aware of when troubleshooting your control system.
ATTENTION
!
Never reach into a machine to actuate a switch because unexpected motion can occur and cause injury.
Remove all electrical power at the main power disconnect switches before checking electrical connections or inputs/outputs causing machine motion.
Indicator Lights
When the green LED on the analog module is illuminated, it indicates that power is applied to the module.
Activating Devices When Troubleshooting
When troubleshooting, never reach into the machine to actuate a device. Unexpected machine motion could occur.
Publication 1769-UM008A-EN-P - November 2001
5-2 Module Diagnostics and Troubleshooting
Module Operation vs.
Channel Operation
Stand Clear of the Machine
When troubleshooting any system problem, have all personnel remain clear of the machine. The problem could be intermittent, and sudden unexpected machine motion could occur. Have someone ready to operate an emergency stop switch in case it becomes necessary to shut off power to the machine.
Program Alteration
There are several possible causes of alteration to the user program, including extreme environmental conditions, Electromagnetic
Interference (EMI), improper grounding, improper wiring connections, and unauthorized tampering. If you suspect a program has been altered, check it against a previously saved program on an
EEPROM or UVPROM memory module.
Safety Circuits
Circuits installed on the machine for safety reasons, like over-travel limit switches, stop push buttons, and interlocks, should always be hard-wired to the master control relay. These devices must be wired in series so that when any one device opens, the master control relay is de-energized, thereby removing power to the machine. Never alter these circuits to defeat their function. Serious injury or machine damage could result.
The module performs operations at two levels:
• module level
• channel level
Module-level operations include functions such as power-up, configuration, and communication with a bus master, such as a
MicroLogix 1500 or Compact Logix controller.
Channel-level operations describe channel related functions, such as data conversion and over-range detection.
Publication 1769-UM008A-EN-P - November 2001
Power-up Diagnostics
Module Diagnostics and Troubleshooting 5-3
Internal diagnostics are performed at both levels of operation. When detected, module error conditions are immediately indicated by the module status LED. Both module hardware and channel configuration error conditions are reported to the controller. Channel over-range conditions are reported in the module’s input data table. Module hardware errors are typically reported in the controller’s I/O status file. Refer to your controller manual for details.
At module power-up, a series of internal diagnostic tests are performed. These diagnostic tests must be successfully completed or the module status LED remains off and a module error results and is reported to the controller.
If module status LED is: Indicated condition: Corrective action:
On
Off
Proper Operation
Module Fault
No action required.
Cycle power. If condition persists, replace the module.
Channel Diagnostics
When an input or output channel is enabled, the module performs a diagnostic check to see that the channel has been properly configured. In addition, the module checks each channel on every scan for configuration errors and over-range conditions.
Out-of-Range Detection
For input channels, whenever the data received at the channel word is out of the defined operating range, an over-range error is indicated in input data word 4, bits 0 to 3 for input channels 0 through 3, respectively.
For output channels, whenever the controller is driving data over the defined operating range, an over-range error is indicated in the input data word 5, bits 0 and 1 for output channels 0 and 1, respectively.
Publication 1769-UM008A-EN-P - November 2001
5-4 Module Diagnostics and Troubleshooting
Critical vs. Non-Critical
Errors
Critical errors signal conditions that prevent normal or recoverable operation of the system. When these types of errors occur, the system leaves the run or program mode of operation until the error is
remedied. See Table 5.2 Extended Error Codes on page 5-5 for more
information on critical module errors.
Non-critical errors are recoverable and can be dealt with by running the Fault routine. For example, a channel over-range condition is a
non-critical error. See Table 5.2 Extended Error Codes on page 5-5 for
more information.
15
r
0
14
r
0
13
r
0
12
r
0
11
r
0
I/O Module Errors
10
r
0
The analog I/O modules notify the host of critical and non-critical module errors. Word 0 contains the error codes generated by the module. The module errors are expressed as two fields: Mod_Error
(bits 9, 10, and 11) and Extended_Error_Info (bits 0 to 8). The following table shows the error fields:
9
r
1
8
r
0
7
r
0
6
r
0
5
r
0
4
r
0
3
r
0
2
r
0
1
r
0
0
r
1
Output_State
Mod_Configured
Bus_WD_Timeout_Latch
Mod_Error r = read only
Extended_Error_Info
Mod_Error Field
The Mod_Error field classifies module errors into three groups:
•
No Errors (Mod_Error = 0): The module has no errors. There is no need to check the Extended_Error_Info field.
•
Hardware Errors (Mod_Error = 1): Check the
Extended_Error_Info field for general and specific error codes.
•
Configuration Errors (Mod_Error = 2): Check the
Extended_Error_Info field for module-specific error codes.
Publication 1769-UM008A-EN-P - November 2001
Module Diagnostics and Troubleshooting 5-5
Extended_Error_Info Field
Check the Extended_Error_Info field when a non-zero value is in the
Mod_Error field. The following are some Extended_Error_Info error codes:
Table 5.1 Extended Error Information Field
Error Type
No Error
Hardware Error
Configuration Error
Mod_Error (11:9)
0
1
2
Extended_Error_Info (8:0)
always 000
000 = no additional information
001 = Power-up Reset
002 to 0FF = general common errors
100 to 1FF = module specific errors
000 = no additional information
001 to 1FF = module specific errors
Extended Error Codes
When invalid values are entered in the configuration file, the module ignores the invalid configuration, generates a non-critical error, and keeps operating with the previous configuration. The following table explains the extended error codes for the 1769-IF4XOF2 analog combination module:
Table 5.2 Extended Error Codes
Error Type Hex
Equivalent
(1)
No Error
General Common
Hardware Error
Hardware-
Specific Error
1769-IF4XOF2 Specific
Configuration Error
X400
X401
X402
X403
X404
X000
X200
X201
X300
X301
(1) X represents the “Don’t Care” digit.
010
010
010
010
010
Module
Error
Code
Bits (11:9)
Binary
000
001
001
001
001
Extended Error
Information
Code Bits 8:0
Binary
0 0000 0000
0 0000 0000
0 0000 0001
1 0000 0000
1 0000 0001
0 0000 0000
0 0000 0001
0 0000 0010
0 0000 0011
0 0000 0100
Error Description
No Error
General Hardware Error; no additional information
Power-up reset state
General hardware error (ASIC)
Microprocessor hardware error
General configuration error; no additional information invalid Fault Value Entered for (channel 0) invalid Fault Value Entered for (channel 1) invalid Program Value Entered for (channel 0) invalid Program Value Entered for (channel 1)
Publication 1769-UM008A-EN-P - November 2001
5-6 Module Diagnostics and Troubleshooting
Module Condition Errors
Common Hardware Errors
There are several general common hardware errors. The following table lists these errors.
Table 5.3 Common Hardware Errors
Mod_Error
(11:9)
0
1
1
Extended_Error
_Info (8:0)
000
000
001
Error Description
No Errors
General hardware error; no additional information
Power-up reset state
Hardware Specific Errors
If the module detects that any of the analog to digital converters are not functioning properly, one of the following hardware errors is set:
Table 5.4 Specific Hardware Errors
Mod_Error
(11:9)
1
1
1
1
Extended_Error
_Info (8:0)
100
101
102
103
Error Description
General H/W error (ASIC)
Microprocessor H/W error
SPARE (not part of 1769-IF4XOF2 design)
SPARE (not part of 1769-IF4XOF2 design)
Module Inhibit Function
Some controllers support the module inhibit function. See your controller manual for details.
Whenever the combination module is inhibited, it enters the program mode and the output channels are changed to the state configured for the program mode. The input channels of the module continue to provide information about changes at its inputs to the 1769 Compact
Bus Master (for example, a CompactLogix controller).
Publication 1769-UM008A-EN-P - November 2001
Contacting Rockwell
Automation
Module Diagnostics and Troubleshooting 5-7
If you need to contact Rockwell Automation for assistance, please have the following information available when you call:
• a clear statement of the problem, including a description of what the system is actually doing. Note the LED state; also note input and output image words for the module.
• a list of remedies you have already tried
• processor type and firmware number (See the label on the processor.)
• hardware types in the system, including all I/O modules
• fault code if the processor is faulted
Publication 1769-UM008A-EN-P - November 2001
5-8 Module Diagnostics and Troubleshooting
Publication 1769-UM008A-EN-P - November 2001
Appendix
A
Specifications
1
General Specifications
Specification
Dimensions
Approximate Shipping
Weight (with carton)
Storage Temperature
Operating Temperature
Operating Humidity
Operating Altitude
Vibration
Shock
Bus Current Draw (max.)
Heat Dissipation
System Power Supply
Distance Rating
Recommended I/O Cable
Maximum I/O Cable
Length
Module OK LED
Agency Certification
Vendor I.D. Code
Product Type Code
Product Code
1769-IF4XOF2
118 mm (height) x 87 mm (depth) x 35 mm (width) height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 1.38 in (width) height including mounting tabs is 5.43 in.
290g (0.64 lbs.)
-40°C to +85°C (-40°F to +185°F)
0°C to +60°C (32°F to +140°F)
5% to 95% non-condensing
2000 meters (6561 feet)
Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak
Relay Operation: 2G
(1)
Operating: 30G, 11 ms panel mounted
(20G, 11 ms DIN rail mounted)
Relay Operation: 7.5G panel (5G DIN rail mounted)
Non-Operating: 40G panel mounted
(30G DIN rail mounted)
120 mA at 5V dc
160 mA at 24V dc
3.03 Total Watts (The Watts per point, plus the minimum
Watts, with all points energized.)
8 (The module may not be more than 8 modules away from a system power supply.)
Belden™ 8761 (shielded)
200m (656 feet) Exceeding cable length reduces accuracy.
For more information, see “Effect of Transducer/Sensor
Cable Length Impedance on Voltage Input Accuracy” on
page 3-11 and “Effect of Device and Cable Output
Impedance on Output Module Accuracy” on page 3-13.
1
10
33
On: module has power, has passed internal diagnostics, and is communicating over the bus.
Off: Any of the above is not true.
C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE and C-Tick compliant for all applicable directives
Publication 1769-UM008A-EN-P - November 2001
A-2 Specifications
Input Specifications
Publication 1769-UM008A-EN-P - November 2001
Specification
Hazardous Environment
Class
Radiated and Conducted
Emissions
Electrical /EMC:
ESD Immunity
(IEC61000-4-2)
Radiated Immunity
(IEC61000-4-3)
Fast Transient Burst
(IEC61000-4-4)
Surge Immunity
(IEC61000-4-5)
Conducted Immunity
(IEC61000-4-6)
1769-IF4XOF2
Class I, Division 2, Hazardous Location, Groups A, B, C, D
(UL 1604, C-UL under CSA C22.2 No. 213)
EN50081-2 Class A
The module has passed testing at the following levels:
•
4 kV contact, 8 kV air, 4 kV indirect
•
10 V/m , 80 to 1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier
•
2 kV, 5kHz
•
1kV galvanic gun
•
10V, 0.15 to 80MHz
(2)
(1) When a relay module, such as the 1769-OW8, is used.
(2) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is
30 MHz to 1000 MHz.
Specification
Number of Inputs
Analog Normal Operating
Ranges
Full Scale
(1)
Analog
Ranges
Converter Type
Resolution (max.)
Response Speed per
Channel
Rated Working Voltage
(2)
1769-IF4XOF2
4 differential or single-ended
Voltage: 0 to 10V dc
Current: 0 to 20 mA
Voltage: 0 to 10.5V dc
Current: 0 to 21 mA
Successive Approximation
8 bits plus sign (Sign is always positive)
5 ms
30V ac/30V dc
Common Mode Voltage
(3) 10V dc maximum per channel
Common Mode Rejection greater than 60 dB at 60 Hz at 1V between inputs and analog common
Normal Mode Rejection
Input Impedance
Overall Accuracy
25°C
Accuracy Drift with
Temperature
(4)
Overall Accuracy at
0 to 60°C
at none
Voltage Terminal: 150K
Ω
(nominal)
Current Terminal: 150
Ω
(nominal)
Voltage Terminal: ±0.7% full scale
Current Terminal: ±0.6% full scale
Voltage Terminal: ±0.9% full scale
Current Terminal: ±0.8% full scale
Voltage Terminal: ±0.006% per °C
Current Terminal: ±0.006% per °C
Output Specifications
Specifications A-3
Specification
Calibration
Non-linearity (in percent full scale)
Repeatability
(5)
Input Channel
Configuration
1769-IF4XOF2
Not required. Accuracy is guaranteed by components.
±0.4%
±0.4%
Channel Diagnostics
Maximum Overload at
Input Terminals
(6)
Input Group to Bus
Isolation via wiring of devices, configuration software screen, or the user program (by writing a unique bit pattern into the module’s configuration file). Refer to your controller’s user manual to determine if user program configuration is supported.
Over range by bit reporting
Voltage Terminal: 20V continuous, 0.1 mA
Current Terminal: 32 mA continuous, 5V dc
500V ac or 710V dc for 1 minute (qualification test)
30V ac/30V dc working voltage (IEC Class 2 reinforced insulation)
(1) The over-range flag will come on when the normal operating range is exceeded. The module will continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the normal operating range.
(2) Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground potential (for example, 10V dc input sig nal and 20V dc potential above ground).
(3) For proper operation, both the plus and minus input terminals must be within 0 to +10V dc of analog common.
(4) Includes offset, gain, non-linearity and repeatability error terms.
(5) Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.
(6) Damage to the input circuit may occur if this value is exceeded.
Specification
Number of Outputs
Analog Normal Operating
Ranges
(1)
1769-IF4XOF2
2 single-ended
Voltage: 0 to 10V dc
Current: 0 to 20 mA
Full Scale Analog Ranges Voltage: 0 to 10.5V dc
Current: 0 to 21 mA
Converter Type Resistor String
Resolution (max.)
Response Speed per
Channel
Current Load on Voltage
Output
8 bits plus sign (Sign is always positive, Bit 15 = 0)
0.3 ms for rated resistance and rated inductors
3.0 ms for rated capacitance
10 mA max.
0 to 300
Ω
(includes wire resistance) Resistive Load on Current
Output
Load Range on Voltage
Output
Max. Inductive Load
(Current Outputs)
>1 k
Ω
0.1 mH at 10V dc
Publication 1769-UM008A-EN-P - November 2001
A-4 Specifications
Specification
Max. Capacitive Load
(Voltage Outputs)
Overall Accuracy
(2)
at
25°C
Overall Accuracy at 0 to
60°C
Accuracy Drift with
Temperature
Output Ripple;
(3) range 0 - 50 kHz
(referred to output range)
Non-linearity
(in percent full scale)
Repeatability
(4)
(in percent full scale)
Output Impedance
Open and Short-Circuit
Protection
Maximum Short-Circuit
Maximum Open Circuit
Output Response at
System Power Up and
Power Down
Rated Working Voltage
Channel Diagnostics
Output Group to
Backplane Isolation
1769-IF4XOF2
1 µF
Voltage Terminal: ±0.5% full scale
Current Terminal: ±0.5% full scale
Voltage Terminal: ±0.6% full scale
Current Terminal: ±1.0% full scale
Voltage Terminal: ±0.01% full scale per °C
Current Terminal: ±0.01% full scale per °C
±0.05%
±0.4%
±0.05%
10
Yes
Ω
(nominal)
Current: 40 mA
Voltage: 15V
+2.0V dc to -1.0V dc spike for less than 6 ms
30V ac/30V dc
Over range by bit reporting
500V ac or 710V dc for 1 minute (qualification test)
30V ac/30V dc working voltage (IEC Class 2 reinforced insulation)
(1) The over-range flag will come on when the normal operating range is exceeded. The module will continue to convert the analog output up to the maximum full scale range. The flag automatically resets when within the normal operating range.
(2) Includes offset, gain, drift, non-linearity and repeatability error terms.
(3) Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.
(4) Repeatability is the ability of the output module to reproduce output readings when the same controller value is applied to it consecutively, under the same conditions and in the same direction.
Publication 1769-UM008A-EN-P - November 2001
1
Appendix
B
Module Addressing and Configuration with
MicroLogix 1500
Module Addressing
slot e
Input Image File slot e
Configuration
File slot e
Output Image
File
This chapter examines the analog module’s addressing scheme and describes module configuration using RSLogix 500 and MicroLogix
1500.
The following memory map shows the input, output, and configuration image tables for the 1769-IF4XOF2. Detailed information
for these image tables can be found on page 4-3.
Input Image
8 words
Configuration File
6 words
Output Image
2 words
Memory Map
Channel 0 Input Word
Channel 1 Input Word
Channel 2 Input Word
Channel 3 Input Word
Over-range Bits - Inputs
Over-range Bits - Outputs
Channel 0 Output Loopback
Channel 1 Output Loopback
Word 0
Word 1
Word 2
Word 3
Word 5
Word 6, bits 7 to 14
Word 7, bits 7 to 14
Address
I:e.0
I:e.1
I:e.2
I:e.3
I:e.4
I:e.5
I:e.6/7 to I:e.6/14
I:e.7/7 to I:e.7/14
Configuration Word
Configuration Word
Output Channel 0 Fault Value
Output Channel 0 Program (Idle) Value
Output Channel 1 Fault Value
Output Channel 1 Program (Idle) Value
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Refer to your controller’s user manual for addresses.
Bit 15
Channel 0 Output Data Word
Channel 1 Output Data Word
Bit 0
Word 0
Word 1
O:e.0
O:e.1
Publication 1769-UM008A-EN-P - November 2001
B-2 Module Addressing and Configuration with MicroLogix 1500
1769-IF4XOF2 Input Image
The input image file represents input channel data words I/O, channel status bits. Input words 0 through 3 contain the converted analog input data from the field device. Word 4, bits 0 to 3 are the over-range flag bits for input channels 0 to 3. Word 5, bit 0 and 1 are the over-range flag bits for channels 0 and 1. Words 6 and 7, bits 7 through 14 are the data echo. These words provide output loopback/data echo through the input array. The Input Data File is
explained in more detail on page 4-3. To receive valid status
information, the channel must be enabled.
TIP
You can access information in the input image file using the programming software configuration screen.
For example, to obtain the over-range status of input channel 2 of the
1769-IF4XOF2 analog module located in slot 3, use address I:3.4/2.
Slot
Word
Bit
Input File Type
I:3.4/2
Element Delimiter Word Delimiter Bit Delimiter
TIP
0 1 2
Slot Number
3
The end cap does not use a slot address.
Publication 1769-UM008A-EN-P - November 2001
Module Addressing and Configuration with MicroLogix 1500 B-3
1769-IF4XOF2 Configuration File
The configuration file allows you to enable or disable the modules input and/or output channels. It also allows you to select how the
Program or Fault mode condition and what the output value will be if the User-defined Safe State is selected. The configuration file is
explained in more detail in Configuration Data File on page 4-8.
The configuration file is modified using the programming software configuration screen. For an example of module configuration using
RSLogix 500.
TIP
The RSLogix 500 configuration default is to enable each analog input channel. For improved analog input module performance, disable any unused channels.
Table B.1 Software Configuration Channel Defaults
1769-IF4XOF2
Parameter
Enable/Disable Input/Output Channel
Program Mode (Outputs)
Fault Mode (Outputs)
Default Setting
Disabled
Hold Last State
Hold Last State
Configuring 1769-IF4XOF2 in a MicroLogix 1500 System
This example takes you through configuring your 1769-IF4XOF2 analog module with RSLogix 500 programming software. This application example assumes your module is installed as expansion
I/O in a MicroLogix 1500 system, and that RSLinx™ is properly configured and a communications link has been established between the MicroLogix processor and RSLogix 500.
Publication 1769-UM008A-EN-P - November 2001
B-4 Module Addressing and Configuration with MicroLogix 1500
Start RSLogix and create a MicroLogix 1500 application. The following screen appears:
While offline, double-click on the IO Configuration icon under the controller folder and the following IO Configuration screen appears.
Publication 1769-UM008A-EN-P - November 2001
This screen allows you to manually enter expansion modules into expansion slots, or to automatically read the configuration of the controller. To read the existing controller configuration, click on the
Read IO Config button.
Module Addressing and Configuration with MicroLogix 1500 B-5
A communications dialog appears, identifying the current communications configuration so that you can verify the target controller. If the communication settings are correct, click on Read IO
Config.
The actual I/O configuration is displayed. In this example, the
1769-IF4XOF2 is attached to the MicroLogix 1500 processor.
Publication 1769-UM008A-EN-P - November 2001
B-6 Module Addressing and Configuration with MicroLogix 1500
Configuring the 1769-IF4XOF2
The 1769-IF4XOF2 analog module is installed in slot 1. To configure the module, double-click on the module/slot. The 1769-IF4XOF2 general configuration screen appears.
Publication 1769-UM008A-EN-P - November 2001
Module Addressing and Configuration with MicroLogix 1500 B-7
Analog Input/Output Configuration
Each of the four analog input words (channels) and two output words
(channels) are disabled by default. To enable a channel, click its
Enable box so that a check mark appears in it. For optimum module performance, disable any channel that is not hardwired to a real input.
Generic Extra Data Configuration
This tab redisplays the configuration information entered on the
Analog Input Configuration screen in a raw data format. You have the option of entering the configuration using this tab instead of the
Analog Input Configuration tab. You do not have to enter data in both places.
Publication 1769-UM008A-EN-P - November 2001
B-8 Module Addressing and Configuration with MicroLogix 1500
Publication 1769-UM008A-EN-P - November 2001
1
Appendix
C
Configuration Using the 1769-IF4XOF2
Combination Analog Module with a
CompactLogix System
The following is used to generate a Generic or Thin Profile and configure the 1769-IF4XOF2 analog combination module in
RSLogix5000.
Version 8.02 of RSLogix5000 and the CompactLogix controllers support only the Generic 1769 Module Profile for 1769-IF4XOF2.
Version 10 of RSLogix 5000 and the CompactLogix controllers provides a “Thin” Profile for the 1769-IF4XOF2 module.
TIP
A Thin profile for an I/O module provides an extra layer of support when entering and configuring an
I/O module in your project. You do not enter I/O and Configuration file lengths for a Thin profile as you must when using the Generic profile. In addition, the I/O and Configuration tags that are created for each I/O module contain descriptive tag elements, making it easier to identify each I/O and
Configuration parameter.
Adding a 1769-IF4XOF2
Module to Your System
Refer to Chapter 3 of this manual for detailed information on wiring
your 1769-IF4XOF2 analog combination module.
Start RSLogix 5000 programming software by double-clicking its icon on your desktop. The following screen displays:
Publication 1769-UM008A-EN-P - November 2001
C-2 Configuration Using the 1769-IF4XOF2 Combination Analog Module with a CompactLogix System
Click the File pull down menu and select New or click the New icon.
Choose your controller type, name your project, then click OK. A new project screen displays.
The area on the left of this screen is called the Controller Organizer.
This is where controller properties, tasks, tags and I/O are found.
The last entry is called “[0] CompactBus Local”. This is where the local
I/O is entered into your project. Right click on it and select “New
Module.” One of the following screens displays, depending upon your version of RSLogix 5000:
RSLogix 5000 Version 8 - Generic Profile RSLogix 5000 Version 10 - Thin Profile
Publication 1769-UM008A-EN-P - November 2001
Configuration Using the 1769-IF4XOF2 Combination Analog Module with a CompactLogix System C-3
Select either the generic 1769-MODULE or the 1769-IF4XOF2/A and click OK.
For RSLogix 5000 version 10, see Thin Profile below.
For RSLogix 5000 version 8, see Generic Profile on page C-4.
Thin Profile
Once you have selected the 1769-IF4XOF2 module and clicked OK, the following screen appears:
Enter a name for your module and a description, if desired. You may
Click Finish. The appropriate I/O and Configuration tags are created, and the module appears in the Controller Organize below the
“[0] CompactBus Local”.
See Configuring the 1769-IF4XOF2 Analog Combination Module on page C-5 to continue.
Publication 1769-UM008A-EN-P - November 2001
C-4 Configuration Using the 1769-IF4XOF2 Combination Analog Module with a CompactLogix System
Generic Profile
Once you have selected the Generic 1769 Module and clicked OK, the following screen appears:
Publication 1769-UM008A-EN-P - November 2001
IMPORTANT
Do not modify the “Assembly Instance” values.
Enter a name and choose “Data-INT” for the “Comm Format”. Enter the Input, Output and Configuration data lengths for the following:
•
Input Size:
•
Output Size:
8
2
•
Configuration Size: 6
When you have entered all necessary parameters, click Finish. The module with the name you entered appears below “[0] CompactBus
Local” in the Controller Organizer.
See Configuring the 1769-IF4XOF2 Analog Combination Module on page C-5 to continue.
Configuring the
1769-IF4XOF2 Analog
Combination Module
Configuration Using the 1769-IF4XOF2 Combination Analog Module with a CompactLogix System C-5
When you add an I/O module into a CompactLogix system, the Input,
Output and Configuration tags are automatically created in the
Controller Tag base for that module.
TIP
When a Thin Profile is used, each of these tags and their sub elements contain descriptive names, which match the documentation for that module.
For the case of the 1769-IF4XOF2, the following tags are created:
Local:s:I Input tag
Local:s:O Output tag
Local:s:C Configuration tag where “s” is the slot number of the I/O module
The screen below shows the 1769-IF4XOF2 in slot 1.
Each of these tags is expanded by clicking on the plus sign to its left.
Click the plus sign to the left of the Configuration tag, then also click the plus sign to the left of “Local:1:C.Data.”
Publication 1769-UM008A-EN-P - November 2001
C-6 Configuration Using the 1769-IF4XOF2 Combination Analog Module with a CompactLogix System
One of the following screens displays, depending upon whether you are using a Generic or Thin Profile:
RSLogix 5000 Version 8 - Generic Profile
RSLogix 5000 Version 10 - Thin Profile
Publication 1769-UM008A-EN-P - November 2001
Configuration Using the 1769-IF4XOF2 Combination Analog Module with a CompactLogix System C-7
This Configuration tag is 198 words long. Only the first 6 are needed to configure this module. The remainder of the words in this tag should be a value of 0 decimal.
The 6 words of configuration data are entered in the following tags, assuming the module was configured in slot 1:
Tags in RSLogix 5000
Version 8
Generic Profile
Local:1:C.Data[0] Configuration Data for
Analog Input Channels
Configuration Data for
Analog Output Channels
Channel 0 Fault Value
Local:1:C.Data[1]
Local:1:C.Data[2]
Channel 0 Program Value Local:1:C.Data[3]
Channel 1 Fault Value Local:1:C.Data[4]
Channel 1 Program Value Local:1:C.Data[5]
in RSLogix 5000
Version 10
Thin Profile
Local:1.C.Config0
Local:1.C.Config1
Local:1.C.Ch0FaultValue
Local:1.C.Ch1FaultValue
Local:1.C.Ch0ProgValue
Local:1.C.Ch1ProgValue
The four input channels for this module are not configurable. Each input channel supports either 4 to 20mA current or 0 to 10V dc voltage. This choice is determined by the module terminal to which you are wired. There is a current and a voltage terminal for each analog channel.
TIP
CompactLogix controllers do not yet support Hold
Last State (HLS) or User Defined Safe State (UDSS) for Fault and Program modes for outputs. Analog modules, by default, hold outputs in their last state if the connection is lost to the controller (Fault State) or if the controller is placed into the Program mode or
Faults (Program State).
Publication 1769-UM008A-EN-P - November 2001
C-8 Configuration Using the 1769-IF4XOF2 Combination Analog Module with a CompactLogix System
You can only modify the configuration file to enable the input and output channels being used.
To enable channels:
Using RSLogix 5000 version 8
Generic Profile
Enter a 1 in bits Local:1:C.Data[0]/4 though
Local:1:C.Data[0]/7 for input channels 0 through 3.
Using RSLogix 5000 version 10
Thin Profile
Set Local:1:C.Ch0InputEn through
Local:1:C.Ch3InputEn equal to 1.
Enter a 1 in bits Local:1:C.Data[1]/4 and
Local:1:C.Data[0]/5 for input channels 0 and
1.
Set Local:1:C.Ch0OutputEn through
Local:1:C.Ch3OutputEn equal to 1.
TIP
All other selections in the 6 word configuration file for the analog combination module concern HLS and
UDSS, which is not yet supported by the
CompactLogix controllers. Leave these settings at their default values.
Once the configuration is complete for the 1769-IF4XOF2 module, and any other modules in your system have been entered and configured, you can write your program, and save and download your project to the controller. The configuration files are downloaded to the controller at the same time the project is downloaded to the controller. They are also sent to the module at power up and when an inhibited module is uninhibited.
Publication 1769-UM008A-EN-P - November 2001
Configuration Using the 1769-IF4XOF2 Combination Analog Module with a CompactLogix System C-9
Accessing the Input and
Output Tags
Thin Profile
The analog input data file may be accessed by clicking the plus sign to the left of the input tag, Local:1:I. Fault and status information for the module can be found in this input tag. Refer to Chapter 5
concerning the 32-bit Fault value (Local:1:I.Fault). 4, pages 4-3
through 4-6 describe each value in the input file for the 1769-IF4XOF2
module.
The actual analog input data for this module can be found in the following tags under Local:1:I.
•
Local:1:I.Ch0Data Data for input Channel 0
•
Local:1:I.Ch1Data Data for input Channel 1
•
Local:1:I.Ch2Data Data for input Channel 2
•
Local:1:I.Ch3Data Data for input Channel 3
The analog output data for the two analog output channels must be written to the following tags under Local:1:O :
•
Local:1:O.Ch0Data Data for output Channel 0
•
Local:1:O.Ch1DataData for output Channel 1
Generic Profile
Wire the module to your analog devices, or for test purposes, wire an output on the module to an input on the module. The analog input and output data can be found at the following tag locations:
•
Local:1:I.Data[0]
•
Local:1:I.Data[1]
•
Local:1:I.Data[2]
•
Local:1:I.Data[3]
•
Local:1:I.Data[4]
•
Local:1:I.Data[5]
•
Local:1:I.Data[6]
•
Local:1:I.Data[7]
Input Channel 0 Data
Input Channel 1 Data
Input Channel 2 Data
Input Channel 3 Data
Input Channels Status Flags
Output Channels Status Flags
Output Data Echo [0]
Output Data Echo [1]
•
Local:1:O.Data[0] Output Channel 0 Data
•
Local:1:O.Data[1] Output Channel 1 Data
Publication 1769-UM008A-EN-P - November 2001
C-10 Configuration Using the 1769-IF4XOF2 Combination Analog Module with a CompactLogix System
When the Input and Output tags for the 1769-IF4XOF2 module are expanded in the CompactLogix Controller Tags screen, they look like the following:
Publication 1769-UM008A-EN-P - November 2001
The analog data is presented to the controller in Raw/Proportional format. This means the data for the two possible analog types is:
0 to 20mA Raw/Proportional data range 0 to 31104 decimal
0 to 10V dc Raw/proportional data range 0 to 31104 decimal
TIP
This module only uses bits 7 through 14 to represent the analog data.
1
Two’s Complement Binary Numbers
Appendix
D
The processor memory stores 16-bit binary numbers. Two’s complement binary is used when performing mathematical calculations internal to the processor. Analog input values from the analog modules are returned to the processor in 16-bit two’s complement binary format. For positive numbers, the binary notation and two’s complement binary notation are identical.
As indicated in the figure on the next page, each position in the number has a decimal value, beginning at the right with 2
0 and ending at the left with 2
15
. Each position can be 0 or 1 in the processor memory. A 0 indicates a value of 0; a 1 indicates the decimal value of the position. The equivalent decimal value of the binary number is the sum of the position values.
Positive Decimal Values
The far left position is always 0 for positive values. As indicated in the figure below, this limits the maximum positive decimal value to 32640
(all positions are 1 except the far left position).
1 x 2
14
= 16384
1 x 2
13
= 8192
1 x 2
12
= 4096
1 x 2
11
= 2048
1 x 2
10
= 1024
1 x 2
9
= 512
1 x 2
8
= 256
1 x 2
7
= 128
0 x 2
6
= 64
0 x 2
5
= 0
0 x 2
4
= 0
0 x 2
3
= 0
0 x 2
2
= 0
0 x 2
1
= 0
0 x 2
0
= 0
0 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0
16384
8192
4096
2048
1024
512
256
128
64
0
0
0
0
0
0
________
32640
0 x 2
15
= 0 This position is always 0 for positive numbers.
Publication 1769-UM008A-EN-P - November 2001
D-2 Two’s Complement Binary Numbers
Publication 1769-UM008A-EN-P - November 2001
1
Glossary
The following terms and abbreviations are used throughout this manual. For definitions of terms not listed here refer to Allen-Bradley’s
Industrial Automation Glossary, Publication AG-7.1.
A/D Converter – Refers to the analog to digital converter inherent to the module. The converter produces a digital value whose magnitude is proportional to the magnitude of an analog input signal.
alternate last state – A configuration selection that instructs the module to convert a user-specified value from the channel fault or program/idle word to the output value when the module enters the fault or program mode.
analog input module – A module that contains circuits that convert analog voltage or current input signals to digital values that can be manipulated by the processor.
attenuation – The reduction in the magnitude of a signal as it passes through a system.
bus connector – A 16-pin male and female connector that provides electrical interconnection between the modules.
channel – Refers to analog input or output interfaces available on the module’s terminal block. Each channel is configured for connection to a variable voltage or current input or output device, and has its own data and diagnostic status words.
channel update time – The time required for the module to sample and convert the input signals of one enabled input channel and update the channel data word.
common mode rejection – For analog inputs, the maximum level to which a common mode input voltage appears in the numerical value read by the processor, expressed in dB.
common mode rejection ratio – The ratio of a device’s differential voltage gain to common mode voltage gain. Expressed in dB, CMRR is a comparative measure of a device’s ability to reject interference caused by a voltage common to its input terminals relative to ground.
CMRR=20 Log
10 (V1/V2)
common mode voltage – For analog inputs, the voltage difference between the negative terminal and analog common during normal differential operation.
common mode voltage range – For analog inputs, the largest voltage difference allowed between either the positive or negative terminal and analog common during normal differential operation.
Publication 1769-UM008A-EN-P - November 2001
2
Publication 1769-UM008A-EN-P - November 2001
configuration word – Contains the channel configuration information needed by the module to configure and operate each channel.
D/A Converter– Refers to the digital to analog converter inherent to the output module. The converter produces an analog dc voltage or current signal whose instantaneous magnitude is proportional to the magnitude of a digital value.
dB – (decibel) A logarithmic measure of the ratio of two signal levels.
data echo – The analog value currently being converted by the D/A converter and shown in words 2 and 3 of the output module’s input data file. Under normal operating conditions, the data echo value is the same value that is being sent from the bus master to the output module.
data word – A 16-bit integer that represents the value of the analog input or output channel. The channel data word is valid only when the channel is enabled and there are no channel errors. When the channel is disabled the channel data word is cleared (0).
differential operation – The difference in voltage between a channel’s positive terminal and negative terminal.
digital filter – A low-pass filter incorporated into the A/D converter.
The digital filter provides very steep roll-off above it’s cut-off frequency, which provides high frequency noise rejection.
filter – A device that passes a signal or range of signals and eliminates all others.
filter frequency – (-3 dB frequency) The user-selectable frequency.
full scale – The magnitude of voltage or current over which normal operation is permitted.
full scale error – (gain error) The difference in slope between the actual and ideal analog transfer functions.
full scale range – (FSR) The difference between the maximum and minimum specified analog input values.
hold last state – A configuration selection that instructs the module to keep the outputs at the last converted value prior to the condition that caused the control system to enter the fault or program mode.
input image – The input from the module to the controller. The input image contains the module data words and status bits.
3
LSB – (Least Significant Bit) The bit that represents the smallest value within a string of bits. For analog combo modules, 8-bit, binary codes are used in the I/O image in the card.
For analog combo inputs, the LSB is defined as the bit 7, of the 16-bit field. For analog outputs, the seven rightmost bits are not significant, and the LSB is defined as the eighth bit from the right, bit 7, of the
16-bit field.
linearity error – An analog input or output is composed of a series of voltage or current values corresponding to digital codes. For an ideal analog input or output, the values lie in a straight line spaced by a voltage or current corresponding to 1 LSB. Any deviation of the converted input or actual output from this line is the linearity error of the input or output. The linearity is expressed in percent of full scale input or output. See the variation from the straight line due to linearity error (exaggerated) in the example below.
Actual Transfer
Function
Ideal Transfer
number of significant bits – The power of two that represents the total number of completely different digital codes an analog signal can be converted into or generated from.
module scan time – same as module update time
module update time – For input modules, the time required for the module to sample and convert the input signals of all enabled input channels and make the resulting data values available to the processor. For output modules, the time required for the module to receive the digital code from the processor, convert it to the analog output signal, and send it to the output channel.
multiplexer – An switching system that allows several signals to share a common A/D or D/A converter.
normal mode rejection – (differential mode rejection) A logarithmic measure, in dB, of a device’s ability to reject noise signals between or among circuit signal conductors.
normal operating range – Input or output signals are within the
configured range. See page 1-2 for a list of input and output
types/ranges.
Publication 1769-UM008A-EN-P - November 2001
4
Publication 1769-UM008A-EN-P - November 2001
overall accuracy – The worst-case deviation of the output voltage or current from the ideal over the full output range is the overall accuracy. For inputs, the worst-case deviation of the digital representation of the input signal from the ideal over the full input range is the overall accuracy. this is expressed in percent of full scale.
Gain error, offset error, and linearity error all contribute to input and output channel accuracy.
output accuracy – The difference between the actual analog output value and what is expected, when a given digital code is applied to the d/a converter. Expressed as a ± percent of full scale. The error will include gain, offset and drift elements, and is defined at 25°C, and also over the full operating temperature range (0 to 60°C).
output image – The output from the controller to the output module.
The output image contains the analog output data.
analog output module – An I/O module that contains circuits that output an analog dc voltage or current signal proportional to a digital value transferred to the module from the processor.
repeatability – The closeness of agreement among repeated measurements of the same variable under the same conditions.
resolution – The smallest detectable change in a measurement, typically expressed in engineering units (e.g. 1 mV) or as a number of bits. For example a 8-bit system has 256 possible output states. It can therefore measure 1 part in 256.
status word – Contains status information about the channel’s current configuration and operational state. You can use this information in your ladder program to determine whether the channel data word is valid.
step response time – For inputs, this is the time required for the channel data word signal to reach a specified percentage of its expected final value, given a large step change in the input signal.
update time – see “module update time”
A
A/D
converter
definition
abbreviations
analog input module
definition
overview
attenuation
definition
B
before you begin
bus connector
definition
bus interface
C
calibration
channel
definition
channel diagnostics
channel reconfiguration time
channel scan time
channel status LED
channel step response
channel switching time
channel update time
definition
CMRR. See common mode rejection ratio
common mode rejection
definition
common mode rejection ratio
definition
common mode voltage
definition
common mode voltage range
definition
specification
configuration word
definition
contacting Rockwell Automation
current draw
D
D/A converter
definition
Index data echo
definition
data word
definition
dB
definition
definition of terms
DeviceNet adapter
user manual publication number
differential mode rejection. See normal mode rejection.
differential operation
definition
digital filter
definition
DIN rail mounting
E
electrical noise
EMC Directive
end cap terminator
equipment required for installation
error codes
European Union Directives
extended error codes
F
fault condition
at power-up
filter
definition
filter frequency
and channel step response
definition
full scale
definition
full scale error
definition
full scale range
definition
input specifications
output specifications
G
gain error. See full scale error.
grounding
Publication 1769-UM008A-EN-P - November 2001
2 Index
H
heat considerations
hold last state
definition
fault mode
I
inhibit function
input data formats
valid formats/ranges
input filter selection
input image
definition
installation
getting started
grounding
heat and noise considerations
L
least significant bit. See LSB.
LED
linearity error
definition
LSB
definition
M
module inhibit function
module operation diagram
module scan time
definition
module update time
definition
mounting
multiplexer
definition
multiplexing
N
normal mode rejection
definition
ratio
number of significant bits
definition
Publication 1769-UM008A-EN-P - November 2001
O
operation
module
system
out-of-range detection
over-range flag bits
output image
definition
output module
enable channel
output module status
over-range flag bits
overall accuracy
definition
over-range flag bits
P
panel mounting
positive decimal values
power-up diagnostics
power-up sequence
program alteration
R
reconfiguration time
replacing a module
resolution
definition
RSLogix 500
configuration example
S
safety circuits
scan time
,
spacing
specifications
start-up instructions
status word
definition
step response
step response time
definition
switching time
system operation
T
terminal door label
terminal screw torque
tools required for installation
troubleshooting
safety considerations
two’s complement binary numbers
U
update time. See channel update time.
update time. See module update time.
W
wire size
wiring
differential inputs
input module
mixed transmitter type
module
output module
routing considerations
Index 3
Publication 1769-UM008A-EN-P - November 2001
4 Index
Publication 1769-UM008A-EN-P - November 2001
Publication 1769-UM008A-EN-P - November 2001
4
© 2001 Rockwell International Corporation. Printed in the U.S.A.
Advertisement
Key features
- 4 analog input channels
- Voltage or current input configurable
- 2 analog output channels
- Compact design
- Low resolution
- Removable finger-safe terminal block
- Diagnostic LEDs
- Supports MicroLogix 1500 and CompactLogix controllers