SMC EX12#-SMJ1 EX120-SMJ1, EX121-SMJ1, EX122-SMJ1, EX124U-SMJ1, EX124D-SMJ1, EX126D-SMJ1 SI unit for CC-Link Operation Manual
Below you will find brief information for SI unit for CC-Link EX120-SMJ1, SI unit for CC-Link EX121-SMJ1, SI unit for CC-Link EX122-SMJ1, SI unit for CC-Link EX124U-SMJ1, SI unit for CC-Link EX124D-SMJ1, SI unit for CC-Link EX126D-SMJ1. The SI unit for CC-Link EX12#-SMJ1 series is a remote I/O for CC-Link that controls up to 16 solenoid valves. It makes it easy to connect solenoid valves to a CC-Link network and allows for easy control and monitoring of the valves.
Advertisement
Advertisement
PRODUCT NAME
SI unit for CC-Link
MODEL / Series / Product Number
EX12#-SMJ1 Series
No.EX##-OMB0014-E
Table of Contents
Model Indication and How to Order
Settings
Troubleshooting
Specifications
Dimensions
2
7
10
11
11
13
19
22
23
-1-
No.EX##-OMB0014-E
Safety Instructions
These safety instructions are intended to prevent hazardous situations and/or equipment damage.
These instructions indicate the level of potential hazard with the labels of "Caution", "Warning" or
"Danger". They are all important notes for safety and must be followed in addition to International standards (ISO/IEC)
∗1)
and other safety regulations.
∗1) ISO 4414: Pneumatic fluid power -- General rules relating to systems.
ISO 4413: Hydraulic fluid power -- General rules relating to systems.
IEC 60204-1: Safety of machinery -- Electrical equipment of machines. (Part 1: General requirements)
ISO 10218-1992: Manipulating industrial robots -Safety. etc.
Caution
:
Warning
Danger
:
:
CAUTION indicates a hazard with a low level of risk which, if not avoided, could result in minor or moderate injury.
WARNING indicates a hazard with a medium level of risk which, if not avoided, could result in death or serious injury.
DANGER indicates a hazard with a high level of risk which, if not avoided, will result in death or serious injury.
Warning
1. The compatibility of the product is the responsibility of the person who designs the equipment or decides its specifications.
Since the product specified here is used under various operating conditions, its compatibility with specific equipment must be decided by the person who designs the equipment or decides its specifications based on necessary analysis and test results. The expected performance and safety assurance of the equipment will be the responsibility of the person who has determined its compatibility with the product. This person should also continuously review all specifications of the product referring to its latest catalog information, with a view to giving due consideration to any possibility of equipment failure when configuring the equipment.
2. Only personnel with appropriate training should operate machinery and equipment.
The product specified here may become unsafe if handled incorrectly. The assembly, operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced.
3. Do not service or attempt to remove product and machinery/equipment until safety is confirmed.
1. The inspection and maintenance of machinery/equipment should only be performed after measures to prevent falling or runaway of the driven objects have been confirmed.
2. When the product is to be removed, confirm that the safety measures as mentioned above are implemented and the power from any appropriate source is cut, and read and understand the specific product precautions of all relevant products carefully.
3. Before machinery/equipment is restarted, take measures to prevent unexpected operation and malfunction.
4. Contact SMC beforehand and take special consideration of safety measures if the product is to be used in any of the following conditions.
1. Conditions and environments outside of the given specifications, or use outdoors or in a place exposed to direct sunlight.
2. Installation on equipment in conjunction with atomic energy, railways, air navigation, space, shipping, vehicles, military, medical treatment, combustion and recreation, or equipment in contact with food and beverages, emergency stop circuits, clutch and brake circuits in press applications, safety equipment or other applications unsuitable for the standard specifications described in the product catalog.
3. An application which could have negative effects on people, property, or animals requiring special safety analysis.
4. Use in an interlock circuit, which requires the provision of double interlock for possible failure by using a mechanical protective function, and periodical checks to confirm proper operation.
-2-
No.EX##-OMB0014-E
Caution
The product is provided for use in manufacturing industries.
The product herein described is basically provided for peaceful use in manufacturing industries.
If considering using the product in other industries, consult SMC beforehand and exchange specifications or a contract if necessary.
If anything is unclear, contact your nearest sales branch.
Limited warranty and Disclaimer/Compliance Requirements
The product used is subject to the following "Limited warranty and Disclaimer" and "Compliance
Requirements".
Read and accept them before using the product.
Limited warranty and Disclaimer
1. The warranty period of the product is 1 year in service or 1.5 years after the product is delivered.
∗2)
Also, the product may have specified durability, running distance or replacement parts. Please consult your nearest sales branch.
2. For any failure or damage reported within the warranty period which is clearly our responsibility, a replacement product or necessary parts will be provided.
This limited warranty applies only to our product independently, and not to any other damage incurred due to the failure of the product.
3. Prior to using SMC products, please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products.
∗2) Vacuum pads are excluded from this 1 year warranty.
A vacuum pad is a consumable part, so it is warranted for a year after it is delivered.
Also, even within the warranty period, the wear of a product due to the use of the vacuum pad or failure due to the deterioration of rubber material are not covered by the limited warranty.
Compliance Requirements
1. The use of SMC products with production equipment for the manufacture of weapons of mass destruction (WMD) or any other weapon is strictly prohibited.
2. The exports of SMC products or technology from one country to another are governed by the relevant security laws and regulation of the countries involved in the transaction. Prior to the shipment of a SMC product to another country, assure that all local rules governing that export are known and followed.
-3-
No.EX##-OMB0014-E
Operator
♦This operation manual is intended for those who have knowledge of machinery using pneumatic equipment, and have sufficient knowledge of assembly, operation and maintenance of such equipment. Only those persons are allowed to perform assembly, operation and maintenance.
♦Read and understand this operation manual carefully before assembling, operating or providing maintenance to the product.
■
Safety Instructions
Warning
■
Do not disassemble, modify (including changing the printed circuit board) or repair.
An injury or failure can result.
■
Do not operate the product outside of the specifications.
Do not use for flammable or harmful fluids.
Fire, malfunction, or damage to the product can result.
Verify the specifications before use.
■
Do not operate in an atmosphere containing flammable or explosive gases.
Fire or an explosion can result.
This product is not designed to be explosion proof.
■
If using the product in an interlocking circuit:
•Provide a double interlocking system, for example a mechanical system.
•Check the product regularly for proper operation.
Otherwise malfunction can result, causing an accident.
■ The following instructions must be followed during maintenance:
•Turn off the power supply.
•Stop the air supply, exhaust the residual pressure and verify that the air is released before performing maintenance.
Otherwise an injury can result.
Caution
■
After maintenance is complete, perform appropriate functional inspections.
Stop operation if the equipment does not function properly.
Safety cannot be assured in the case of unexpected malfunction.
■
Provide grounding to assure the safety and noise resistance of the Serial System.
Individual grounding should be provided close to the product with a short cable.
-4-
No.EX##-OMB0014-E
■
NOTE
○Follow the instructions given below when designing, selecting and handling the product.
● The instructions on design and selection
(installation, wiring, environment, adjustment, operation, maintenance, etc.)
described below must also be followed.
∗Product specifications
•When conformity to UL is required, the SI unit should be used with a UL1310 Class 2 power supply.
•The SI unit is a approved product only if they have a
•Use the specified voltage.
mark on the body.
Otherwise failure or malfunction can result.
•Reserve a space for maintenance.
Allow sufficient space for maintenance when designing the system.
•Do not remove any nameplates or labels.
This can lead to incorrect maintenance, or misreading of the operation manual, which could cause damage or malfunction to the product.
It may also result in non-conformity to safety standards.
● Product handling
∗Installation
•Do not drop, hit or apply excessive shock to the fieldbus system.
Otherwise damage to the product can result, causing malfunction.
•Tighten to the specified tightening torque.
If the tightening torque is exceeded the mounting screws may be broken.
•Never mount a product in a location that will be used as a foothold.
The product may be damaged if excessive force is applied by stepping or climbing onto it.
∗Wiring
•Avoid repeatedly bending or stretching the cables, or placing heavy load on them.
Repetitive bending stress or tensile stress can cause breakage of the cable.
•Wire correctly.
Incorrect wiring can break the product.
•Do not perform wiring while the power is on.
Otherwise damage to the fieldbus system and/or I/O device can result, causing malfunction.
•Do not route wires and cables together with power or high voltage cables.
Otherwise the fieldbus system and/or I/O device can malfunction due to interference of noise and surge voltage from power and high voltage cables to the signal line.
Route the wires (piping) of the fieldbus system and/or I/O device separately from power or high voltage cables.
•Confirm proper insulation of wiring.
Poor insulation (interference from another circuit, poor insulation between terminals, etc.) can lead to excess voltage or current being applied to the product, causing damage.
•Take appropriate measures against noise, such as using a noise filter, when the fieldbus system is incorporated into equipment.
Otherwise noise can cause malfunction.
-5-
No.EX##-OMB0014-E
∗Environment
•Select the proper type of protection according to the environment of operation.
In case of IP20, avoid use in the place where water and oil scatter.
•Do not use the product in an environment where corrosive gases or fluids could be splashed.
Otherwise damage to the product and malfunction can result.
•Do not use in an area where surges are generated.
If there is equipment which generates a large amount of surge (solenoid type lifter, high frequency induction furnace, motor, etc.) close to the fieldbus system, this may cause deterioration or breakage of the internal circuit of the fieldbus system. Avoid sources of surge generation and crossed lines.
•When a surge-generating load such as a relay or solenoid is driven directly, use an fieldbus system with a built-in surge absorbing element.
Direct drive of a load generating surge voltage can damage the fieldbus system.
•The product is CE marked, but not immune to lightning strikes. Take measures against lightning strikes in the system.
•Prevent foreign matter such as remnant of wires from entering the fieldbus system to avoid failure and malfunction.
•Mount the product in a place that is not exposed to vibration or impact.
Otherwise failure or malfunction can result.
•Do not use the product in an environment that is exposed to temperature cycle.
Heat cycles other than ordinary changes in temperature can adversely affect the inside of the product.
•Do not expose the product to direct sunlight.
If using in a location directly exposed to sunlight, shade the product from the sunlight.
Otherwise failure or malfunction can result.
•Keep within the specified ambient temperature range.
Otherwise malfunction can result.
•Do not operate close to a heat source, or in a location exposed to radiant heat.
Otherwise malfunction can result.
∗Adjustment and Operation
•Set the switches by using a sharp-pointed screwdriver etc.
It may damage set switches.
•Perform settings suitable for the operating conditions.
Incorrect setting can cause operation failure.
For details of each setting, refer to page 13 of this manual.
•Please refer to the PLC manufacturer's manual etc. for details of programming and addresses.
For the PLC protocol and programming refer to the relevant manufacturer's documentation.
∗Maintenance
•Turn off the power supply, stop the supplied air, exhaust the residual pressure and verify the release of air before performing maintenance.
There is a risk of unexpected malfunction.
•Perform regular maintenance and inspections.
There is a risk of unexpected malfunction.
•After maintenance is complete, perform appropriate functional inspections.
Stop operation if the equipment does not function properly.
Otherwise safety is not assured due to an unexpected malfunction or incorrect operation.
•Do not use solvents such as benzene, thinner etc. to clean the each unit.
They could damage the surface of the body and erase the markings on the body.
Use a soft cloth to remove stains.
For heavy stains, use a cloth soaked with diluted neutral detergent and fully squeezed, then wipe up the stains again with a dry cloth.
-6-
No.EX##-OMB0014-E
Model Indication and How to Order
EX120-SMJ 1
Output type
1 16 outputs, NPN (positive common) / sink
Fieldbus
MJ CC-Link
Valve interface
EX120 Direct mounting - Plug in
EX121 DIN rail mounting - Flat ribbon cable
EX122 DIN rail mounting - Plug in
EX124U Direct mounting - Plug in (IP65) U side
EX124D Direct mounting - Plug in (IP65) D side
EX126D Direct mounting - Plug in (IP67) D side
-7-
No.EX##-OMB0014-E
Summary of Product elements
•EX120-SMJ1
•EX121-SMJ1
•EX122-SMJ1
-8-
No.EX##-OMB0014-E
•EX124D/U-SMJ1
•EX126D-SMJ1
-9-
No.EX##-OMB0014-E
○Terminal block (with switch cover open)
No. Element
1 Output connector
Description
To connect to the valve manifold
2 LED and Switch cover
LED display to indicate the status of the SI unit.
Switches for setting the station number and transmission speed.
3 Communication terminals (DA, DB, DG) To connect the CC-Link line with a CC-Link-dedicated cable.
4 Power supply terminals (24 V, 0 V) To supply power to solenoid valves.
5 Power supply terminals (+24 V, 24 G) To supply power for communication.
terminal
7 DIN rail mounting bracket
To connect to functional ground and to connect the CC-Link cable shield wire.
For mounting to a DIN rail.
For the CC-Link and power supply wiring to the SI unit.
A waterproof plug assembly (P/N: AXT100-B04A) must be used for unused conduit ports.
■
Definition and terminology
No. Term
1 Number of stations
Definition
Total number of stations occupied by all slaves connected to the CC-Link network.
3 Slave station
4 Number of occupied slaves
Numbers assigned to the slave stations, from 1 to 64, with No. 0 assigned to the
CC-Link master. Slave stations must be assigned numbers according to the number of occupied stations so they are not duplicated.
General term for any station other than the master station.
Number of networked stations in use by a slave. Depending on the data, one to four stations can be set. The remote I/O only occupies one station.
A station which can only use digital data. Occupies only one station.
(Example: digital units, solenoid valves, sensors, etc)
-10-
No.EX##-OMB0014-E
Mounting and Installation
■
Communication wiring
The connection between a CC-Link-dedicated cable and an SI unit communication terminal for CC-Link is shown below.
(1) Be sure to connect each signal line to its dedicated terminal. (Refer to Fig. 1)
Tighten the screws securely with a torque of 0.5 to 0.6 Nm.
The terminal screw is an M3 cross head screw.
Fig. 1
(2) Be sure to connect a terminating resistor between “DA” and “DB” at both ends of the CC-Link system.
(Refer to Fig. 2)
(3) The appropriate terminating resistor varies depending on the CC-Link cable used.
(Refer to the table and Fig. 3 below.)
Cable type
CC-Link dedicated cable
Terminating resistor
110
Ω 1/2 W (Brown, Brown, Brown)
CC-Link dedicated cable compatible to Ver.1.10
CC-Link dedicated high performance cable 130
Ω 1/2 W (Brown, Orange, Brown)
Fig. 2
Fig. 3
Use the correct terminating resistor, available from the manufacturer of the CC-Link master.
Use a CC-Link-dedicated cable, or a cable with the same specifications.
If a cable with any other specifications is used, normal data transmission cannot be guaranteed.
-11-
No.EX##-OMB0014-E
(4) The CC-Link-dedicated cable’s shield wire (SLD) should be connected to the “FG” terminal of the SI unit.
For the EX12#-SMJ1, the "SLD terminal" and "FG terminal" are common.
Therefore, connect 3 wires to the "FG Terminal" as shown in Fig. 4.
Fig. 4: Wiring to the FG terminal on the SI unit
When connecting 3 wires to the “FG terminal”, crimp 2 wires together into one crimped terminal as shown in Fig. 5. Use another crimped terminal for other wires.
After crimping, connect wires so that the back of the two crimped terminals face each other.
Fig. 5: How to crimp the terminal
-12-
No.EX##-OMB0014-E
■
Power supply wiring
Connect the power supply wiring to the solenoid valve power supply terminals and to the SI unit control power supply terminals.
Although the power supply consists of two separate systems, it is possible to use either a single power supply or separate power supplies.
Be sure to connect the power supply to the correct terminals (Refer to Fig. 6).
Tighten the screws securely with a torque of 0.5 to 0.6 Nm.
The terminal screw is an M3 cross head screw.
Note: Connect the ground terminal to ground. Resistance to ground should be 100 ohms or less.
A. Single power supply used B. Dual power supplies used
Fig. 6
Settings
○Display setting
Display
PW LED is ON when the communication power is ON
Meaning
L RUN
Indicates whether the SI unit is communicating with the master station correctly.
LED is ON when the SI unit is receiving normal data from the master station.
LED is OFF during time-out.
SD LED is ON when data is being sent.
RD LED is ON when data is being received.
L ERR.
LED is ON during communication errors (CRC errors).
LED is OFF during time-out (L RUN LED is also OFF).
LED is ON during station number setting and communication speed setting errors
(the LED will turn off when the setting has been corrected and power has been restored).
LED flashes when the station number or communication speed settings have changed during communication
(the L RUN LED will turn on and the SI unit will operate according to the new settings once power is restored).
If the data link is normal, “PW”, “L RUN”, “SD”, and “RD” LED's will be ON.
-13-
No.EX##-OMB0014-E
○Switch setting
The setting for the station number and communication speed can be carried out using the rotary switches under the LED and switch cover.
The settings must be carried out with the power supply for the SI unit turned off.
•Station number setting
•Communication speed setting
Setting x10
Setting range
0 to 6 x1 0 to 9
∗: The station number should be set within the range of 01 to 64.
If the number is set to 00, or to 65 or above, the “L ERR” LED will turn on.
∗: The station number must not be duplicated, this will cause an error.
∗: The default setting is 00.
Setting Communication speed
∗: The communication speed should be set within the range of 0 to 4.
If the setting is out of range, the “L ERR” LED will turn on.
Turn the power off, and correct the setting.
∗: Set the same communication speed as the master station.
∗: The default setting is 0 (156 kbps).
-14-
No.EX##-OMB0014-E
○Output and error information
(1) I/O mapping table for master station Buffer Memory.
Example when SI unit station is assigned to “01”.
Buffer area of master station
Example: QJ61BT11N
For station 1
For station 2
For station 3
For station 4
For station 5
For station 6
Address Remote output (RY)
160
161
162
163
RY0F to RY00
RY1F to RY10
RY2F to RY20
RY3F to RY30
164
165
166
167
168
169
16A
16B
:
:
RY4F to RY40
RY5F to RY50
RY6F to RY60
RY7F to RY70
RY8F to RY80
RY9F to RY90
RYAF to RYA0
RYBF to RYB0
:
:
∗: RY10 to RY1F is unused.
0: Valve OFF
1: Valve N
(2) Output number assignment
The output number refers to the D side solenoid position on the manifold and starts at zero.
∗: Standard wiring of the manifold is for double-solenoid valves and the output number starts at the A side and then B side in that order as shown in the figure a.
If a single-solenoid valve is mounted on the standard wiring manifold, the output number for the B side valve is skipped.
∗: Custom wiring for mixed mounting single-solenoid valves and double-solenoid valves can be specified with a Wiring
Specification Sheet. Example wiring is shown in the figure b.
∗: Bit status “0” and ”1” in the data corresponds to solenoid valve status OFF and ON (0: OFF, 1: ON), and the output number starts at zero from LSB (least significant bit).
-15-
No.EX##-OMB0014-E
(3) Fuse disconnection details
The power supply fuse disconnection for the SI unit solenoid valves can be monitored by the link special register of the master station.
0: Normal
1: Fuse disconnected
Buffer area of master station
Example: QJ61BT11N b15 b14 b13 b12
… b3 b2 b1 b0
(688
H
(689
H
(68A
(68B
)SW0088 16 15 14 13
)SW0089 32 31 30 29
H
)SW008A 48 47 46 45
H
)SW008B 64 63 62 61
…
…
…
…
4 3 2 1
20
36
52
19
35
51
18
34
50
17
33
49
1 to 64 represents the station number. The bits of occupied stations will turn on.
-16-
No.EX##-OMB0014-E
Maintenance
•Mounting and wiring
Item to inspect
Are SI unit terminals
(for communication and power supply) securely connected?
Are the terminating resistors securely connected to both ends of the network (when the SI unit is at the end of the network)
Criteria
No looseness
Terminating resistors must be connected.
Countermeasure
Tighten the connector.
(Refer to “Mounting/ Installation”)
Connect suitable terminating resistors to cables.
(Refer to “Mounting /Installation”)
Is the connecting cable broken.
•Replacement parts
Item to inspect
No apparent breaks
If any visible breaks are found, replace the cable.
CC-Link dedicated cable
Criteria
No visible error and the correct cable must be used
SI unit
•Power supply
Item to inspect
Check that the communication power supply voltage is within the specified range.
Check that the solenoid valve power supply voltage is within the specified range.
No error in operation and display
Criteria
15 to 30 VDC
24 VDC +10%/-5%
Countermeasure
If any visible breaks are found, replace the cable.
If it does not operate as intended, or the display indicates errors, replace the unit.
Countermeasure
Investigate the cause of the voltage fluctuation, and take countermeasures against it.
Investigate the cause of the voltage fluctuation, and take countermeasures against it.
-17-
No.EX##-OMB0014-E
○Fuse replacement (Only EX126D-SMJ1)
If an over current occurs in the power supply for communication or the power supply for solenoid valves, due to a short circuit etc, the fuse will disconnect the supply.
In this case, remove the cause of the over current and replace the fuse.
The fuse replacement should only be performed with the SI unit disconnected from the valve manifold.
The fuses are positioned either side of the connector on the bottom face of SI unit.
Fuse part number: EX9-FU20
Bottom view of Housing
-18-
No.EX##-OMB0014-E
Troubleshooting
○Troubleshooting
Applicable model: EX12#-SMJ1
If an operation failure of the product occurs, please confirm the cause of the failure from the following table.
If a cause applicable to the failure cannot be identified and normal operation can be recovered by replacement with a new product, this indicates that the product itself was faulty.
Problems with the product may be due to the operating environment (network construction etc). Please consult SMC.
If the cause of the problem cannot be found and the SI unit is not faulty, then inconsistencies with parameter settings or the network construction at the master station is possible.
In this case, please refer to the troubleshooting section of the CC-Link master user’s manual (by Mitsubishi
Electric Corporation).
Solenoid valve malfunction
Yes
No
Only the solenoid valve LED is ON
SI unit PW
LED is OFF
SI unit RD
LED is OFF
SI unit L RUN
LED is OFF
SI unit SD
LED is OFF
SI unit L ERR.
LED is flashing
Solenoid valve malfunction
SI unit has no error.
SI unit L ERR.
LED is OFF
Solenoid valve failure
Refer to Fault
No.1
Refer to Fault
No.2
Refer to Fault
No.3
Refer to Fault
No.4
Refer to Fault
No.5
Refer to Fault
No.6
Refer to Fault
No.7
-19-
No.EX##-OMB0014-E
○Faults and countermeasures
Trouble
No.
Problem Possible cause
1
SI unit PW
LED is OFF
Investigation method Countermeasure
Power supply for communication wiring failure.
Power supply for communication failure.
Check the power supply for communication cable for breaks, and check that the terminals are not loose.
Avoid repetitive bending and stress on the cables, which may cause damage
Check the power supply for communication wiring for any errors.
Connect the power supply cable correctly.
Correct the wiring.
Check the power supply for communication voltage.
Supply 15 to 30 VDC to the power supply for communication.
2
3
SI unit PW
LED is ON and
RD LED is OFF
SI unit L RUN
LED is OFF and
L ERR.LED is
OFF
Communication wiring failure
Master station power supply failure
Communication failure.
Station number setting error
Check the communication cables for breaks, and check that the terminals are not loose
Avoid repetitive bending and stress on the cables, which may cause damage
Check the communication wiring for any errors.
Connect the communication cable correctly
Correct the wiring.
Check the power supply to the master station
Connect the power supply to the master station correctly
Check that there are no high voltage cables or equipment that generates noise around the communication and power supply cables
Separate the communication and power supply cables from the noise sources.
Check that the SI unit station number setting and the setting in the master station are the same
Correct the setting.
Check that the SI unit communication speed setting and the setting in the master station are the same
4
Communication speed setting error
Station number setting error or
SI unit L RUN duplicate station
LED is OFF number error and
L ERR.LED is ON
Communication speed setting error.
Check that the station number settings contain no errors and no duplications
Check that the communication speed is set correctly
Correct the setting.
To review the setting method, see “Settings”.
-20-
No.EX##-OMB0014-E
Trouble
No.
5
6
7
Problem
SI unit L RUN
LED is ON and
SD LED is OFF
SI unit L RUN
LED is ON and
L ERR.LED is flashing
Solenoid valve malfunction.
Possible cause Investigation method Countermeasure
Communication speed setting error
Station number setting error or duplicate station number error
Check that the SI unit communication speed setting and the setting in the master station are the same
Check that the station number settings contain no errors and no duplications
Correct the setting.
Communication speed change error
Station number setting change error
Communication failure.
Solenoid valve failure.
Check that the communication speed setting has not changed while the power supply for communication is supplied.
Check that the station number setting has not changed while the power supply for communication is supplied.
Correct the settings with the power supply turned off, and then supply the power again
Check that there are no high voltage cables or equipment that generates noise around the communication and power supply cables
Separate the communication and power supply cables from the noise sources.
Replace the solenoid valve with another and check the operation, or check the troubleshooting section in the solenoid valve manual
Check the troubleshooting section of the solenoid valve manual, or contact
SMC
Connection failure between
SI unit and solenoid valve manifold
Check the connector between the SI unit and solenoid valve manifold for a connection failure, such as a bent pin
Correct the connection between the SI unit and solenoid valve manifold.
Too many solenoid valves
(more than 16 outputs)
Check that the total number of outputs for the connected solenoid valves is 16 or less
Correct the total number of outputs connected to the EX12#-SMJ1 unit to
16 outputs or less
-21-
No.EX##-OMB0014-E
Specifications
■
Specifications
Model No.
Applicable system
Occupied station
Station number setting range
Communication specification
Station type
Communication speed
Cable length between stations
Max. cable length
Communication supply voltage
Solenoid valve supply voltage
Output channels
Output type
EX12#-SMJ1
CC-Link Ver.1.10
1 station
1 to 64 (Set with a rotary switch)
Remote I/O
156 k/625 k/2.5 M/5 M/10 Mbps
20 cm or more
Connected load
Output when communication error occurs
Internal current consumption (Unit)
Environment
Enclosure
Withstand voltage
Insulation resistance
Ambient temperature
Ambient humidity
Pollution degree
Operating environment
1200/900/400/160/100 m
15 to 30 VDC
24 VDC +10%/-5%
16 outputs
Sink/NPN (positive common)
Solenoid valve with surge voltage suppressor of 24 VDC and 2.1 W or less
(manufactured by SMC)
Clear
0.1 A or less
EX120/121/122: IP20
EX124U/D: IP65
EX126D: IP67
1500 VAC 1min. (Between FG and external terminal)
2 MΩ or more (500 VDC between FG and external terminal)
Operating temperature: 0 to +55 o
C (when 8 outputs are used)
0 to +50
o
C (when 16 outputs are used)
Storage: -10 to 60 o
C
35 to 85%RH (no condensate)
Pollution degree 3
∗
No corrosive gas
Weight
EX120: 110 g or less
EX121: 140 g or less
EX122: 130 g or less
EX124U/D: 240 g or less
EX126D : 360 g or less
∗: EX120/EX121/EX122 are IP20 rated.
When operating this product in a pollution degree 3 environment, mount it onto an IP54 rate or higher controller board etc.
•Applicable solenoid valve series
Number Valve series Enclosure Mounting Valve interface
EX120-SMJ1
SV1000/2000/3000/4000
VQ1000/2000
SY3000/5000
EX121-SMJ1 SY3000/5000
EX122-SMJ1 SY3000/5000
EX124U/D-SMJ1 VQ2000/4000/5000
EX126D-SMJ1
SY3000/5000
SV1000/2000/3000
VQC1000/2000/4000
IP20
IP65
IP67
Direct Plug-in
DIN rail
Direct
Flat ribbon cable
Plug-in
-22-
No.EX##-OMB0014-E
■
Dimensions
•EX120-SMJ1
•EX121-SMJ1
-23-
No.EX##-OMB0014-E
•EX122-SMJ1
•EX124D/U-SMJ1
-24-
No.EX##-OMB0014-E
•EX126D-SMJ1
-25-
No.EX##-OMB0014-E
Revision history
C: Complete revision
D: Terminal screw change
Switch cover change (EX124U/D, EX126D)
E: Modified errors in text. (Page 13)
Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.
© 2010-2012 SMC Corporation All Rights Reserved
No.EX##-OMB0014-E