Allen-Bradley ControlLogix User manual
Advertisement
Advertisement
Allen-Bradley
ControlLogix
Data Highway Plus/
Remote I/O
Communication
Interface Module
User
Manual
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. “Safety Guidelines for the
Application, Installation and Maintenance of Solid State Controls”
(Publication SGI-1.1) describes some important differences between solid state equipment and hard-wired electromechanical devices.
Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will the Allen-Bradley Company be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, the Allen-Bradley Company cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Allen-Bradley Company with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of the Allen-Bradley Company is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
!
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
Attentions help you:
• identify a hazard
• avoid the hazard
• recognize the consequences
Important: Identifies information that is especially important for successful application and understanding of the product.
Ethernet is a registered trademark of Digital Equipment Corporation, Intel and Xerox Corporation.
Microsoft is a registered trademark of Microsoft Corporation.
Windows, Windows 95 and Windows NT are trademarks of Microsoft Corporation.
ControlLogix and Data Highway Plus are trademarks of the Allen-Bradley Company, Inc.
What This Preface Contains
Who Should Use this Manual
Purpose of This Manual
Preface
About This User Manual
This preface describes how to use this manual. The following table describes what this preface contains and its location.
For information about:
Who Should Use This Manual
Purpose of This Manual
Conventions and Related Terms
Related Products and Documentation
Rockwell Automation Support
See page:
We assume you have a good understanding of the Data Highway Plus protocol and Remote I/O. This user manual contains a brief
description of Data Highway Plus in Chapter 2 and a brief description
This manual describes how to understand, configure and troubleshoot your ControlLogix Data Highway Plus/Remote I/O communication interface module.
For installation information, refer to the ControlLogix Data Highway
Plus Communication Interface Module Installation Instructions, publication 1756-5.4.
Publication 1756-6.5.14 - August 1998
P-2 About This User Manual
Conventions and Related Terms
This manual uses the following conventions:
This icon:
TIP
Calls attention to: helpful, time-saving information
Example an example
For more information . . .
additional information in the publication referenced
Publication 1756-6.5.14 - August 1998
About This User Manual P-3
Terms
This term: Means: bridge
ControlLogix Gateway
Configuration tool communication module 1756-DHRIO module connection a logical communication path
DH+ TM
Ethernet
Data Highway Plus - A-B’s proprietary token pass communications protocol for peer to peer communications a physical layer standard using Carrier Sense Multiple Access with Collision Detection (CSMA/CD) methods
Ethernet network gateway indicator link a local area network with a baseband communication rate of
10M bps designed for the high-speed exchange of information between computers and related devices a module or set of modules that allows communications between nodes on dissimilar networks
LED indicator a unique network module address an internetwork node between two similar communication subnets where protocol translation is minimal software that provides manual configuration capability for the
DH+ module
PCCC rack
RIUP transaction transfer a six-bit number used to uniquely identify any module on the local and extended ControlLogix backplane programmable controller communications commands a physical and logical collection of application modules sharing a common power supply and backplane for module to module communication remove and insert under power an exchange of request and data and response and data to send a message to the next destination
Publication 1756-6.5.14 - August 1998
P-4 About This User Manual
Related Products and
Documentation
Rockwell Automation Support
The following table lists related ControlLogix products and documentation:
Catalog number:
Document title:
1756-DHRIO Data Highway Plus Communication Interface Module
Installation Instructions
1756-GTWY ControlLogix Gateway Configuration Tool Quick Start
Publication number:
1756-5.4
1756-10.2
If you need more information on these products, contact your local
Allen-Bradley integrator or sales office for assistance. For more information on the documentation, refer to the Allen-Bradley
Publication Index, publication SD499.
Rockwell Automation offers support services worldwide, with over
75 sales/support offices, 512 authorized distributors and 260 authorized systems integrators located throughout the United States alone, plus Rockwell Automation representatives in every major country in the world.
Local Product Support
Contact your local Rockwell Automation representative for:
•sales and order support
•product technical training
•warranty support
•support service agreements
Technical Product Assistance
If you need to contact Rockwell Automation for technical assistance,
please review the troubleshooting information in Appendix A first. If
problem persists, then call your local Rockwell Automation representative.
Your Questions or Comments on this Manual
If you find a problem with this manual, please notify us of it on the enclosed Publication Problem Report.
Publication 1756-6.5.14 - August 1998
Table of Contents
ControlLogix Data Highway Plus/
Remote I/O Communication
Interface Module
Basics of Using Data
Highway Plus
DH+ Operation
Chapter 1
What the Module Does . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Routing Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
DH+ and CIP Messaging . . . . . . . . . . . . . . . . . . . . 1-2
Remote I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Module Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Setting Switches . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Alphanumeric Indicators . . . . . . . . . . . . . . . . . . . . 1-6
Compliance to European Union Directives . . . . . . . . . . 1-6
EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Low Voltage Directive . . . . . . . . . . . . . . . . . . . . . 1-7
Preventing Electrostatic Discharge . . . . . . . . . . . . . . . . 1-7
Removal and Insertion Under Power . . . . . . . . . . . . . . . 1-8
Chapter Summary and What’s Next . . . . . . . . . . . . . . . 1-8
Chapter 2
What is Data Highway Plus . . . . . . . . . . . . . . . . . . . . . . 2-1
Selecting Devices that You Can Connect . . . . . . . . . . . 2-1
Link Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Programming Terminal Port . . . . . . . . . . . . . . . . . . . . . 2-2
Application Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Chapter Summary and What’s Next . . . . . . . . . . . . . . . 2-3
Chapter 3
Two Methods of Communication Over
Data Highway Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Using DH+ Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Benefits of DH+ Messaging . . . . . . . . . . . . . . . . . . . . . 3-2
Local DH+ Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Receiving Local DH+ Messages on DH+ . . . . . . . 3-3
Sending Local DH+ Messages on DH+ . . . . . . . . 3-3
Limitations of Local DH+ Messaging . . . . . . . . . . 3-4
Routing Error in Local DH+ Messaging . . . . . . . . 3-5
Before Programming in a Controller . . . . . . . . . . . . . . . 3-5
Remote DH+ Messaging . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Limitations of Remote DH+ Messaging . . . . . . . . 3-9
Routing Errors in Remote DH+ Messaging . . . . . 3-9
Configuration Information in DH+ Messaging . . . . . . 3-10
Generating Configuration Faults . . . . . . . . . . . . . 3-10
Application Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Publication 1756-6.5.14 - August 1998
toc–ii Table of Contents
Programming Terminal
Operation Over DH+
PLC-5 or SLC-5/04 to PLC-5 or
SLC-5/04 Messaging
Example of an Application Timeout . . . . . . . . . . 3-11
Example DH+ Routing Configuration . . . . . . . . . . . . . 3-12
Using Control and Information
Protocol (CIP) Messaging . . . . . . . . . . . . . . . . . . . . 3-13
Limitations of CIP Messaging . . . . . . . . . . . . . . . 3-14
Chapter Summary and What’s Next . . . . . . . . . . . . . . 3-14
Chapter 4
Connecting Your Programming Terminal
Over DH+ Using RSLogix 5 . . . . . . . . . . . . . . . . . . . 4-1
Connecting Your Programming Terminal
Over DH+ RSLogix 500 . . . . . . . . . . . . . . . . . . . . . . 4-2
Connecting Your Programming Terminal
Over DH+ Using RSLogix 5000 . . . . . . . . . . . . . . . . 4-3
Defining Connection Paths . . . . . . . . . . . . . . . . . . . . . . 4-5
Connection path examples . . . . . . . . . . . . . . . . . . . 4-6
Chapter Summary and What’s Next . . . . . . . . . . . . . . . 4-9
Chapter 5
DH+ Messaging Between PLC-5s With
One 1756-DHRIO Module . . . . . . . . . . . . . . . . . . . . . 5-2
Set the Module Switches . . . . . . . . . . . . . . . . . . . . 5-3
Set-Up a Routing Table for the1756-DHRIO Module 5-3
Configure Message Instructions . . . . . . . . . . . . . . 5-4
DH+ Messaging Between SLC-5/04s With
Two 1756-DHRIO Modules With One
ControlLogix Chassis . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Set the Module Switches . . . . . . . . . . . . . . . . . . . . 5-6
Set-Up a Routing Table for the First
1756-DHRIO Module . . . . . . . . . . . . . . . . . . . . 5-7
Set-Up a Routing Table for the Second
1756-DHRIO Module . . . . . . . . . . . . . . . . . . . . 5-7
Configure Message Instructions . . . . . . . . . . . . . . 5-8
DH+ Messaging Between PLC-5s With
Multiple ControlLogix Chassis . . . . . . . . . . . . . . . . . 5-9
Set the Module Switches . . . . . . . . . . . . . . . . . . . 5-10
Set-Up a Routing Table for the First
1756-DHRIO Module . . . . . . . . . . . . . . . . . . . 5-11
Set-Up a Routing Table for the Second
1756-DHRIO Module . . . . . . . . . . . . . . . . . . . 5-11
Configure Message Instructions . . . . . . . . . . . . . 5-12
DH+ Messaging From PLC-5 to PLC-5/C
on ControlNet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
Set the Module Switches . . . . . . . . . . . . . . . . . . . 5-14
Set-Up a Routing Table for the
1756-DHRIO Module . . . . . . . . . . . . . . . . . . . 5-15
Configure Message Instructions . . . . . . . . . . . . . 5-16
Chapter Summary and What’s Next . . . . . . . . . . . . . . 5-16
Publication 1756-6.5.14 - August 1998
PLC-5 or SLC-5/04 to Logix5550
Messaging
Logix5550 to PLC-5 or SLC-5/04
Messaging
Table of Contents toc–iii
Chapter 6
DH+ Messaging From a PLC-5 to One Logix5550
With One ControlLogix Chassis . . . . . . . . . . . . . . . . 6-2
Set the Module Switches . . . . . . . . . . . . . . . . . . . . 6-3
Set-Up a Controller Slot for the
1756-DHRIO Module . . . . . . . . . . . . . . . . . . . . 6-4
Configure Message Instructions . . . . . . . . . . . . . . 6-5
DH+ Messaging From a PLC-5 to Multiple
Logix5550s With One ControlLogix Chassis . . . . . . 6-6
Set the Module Switches . . . . . . . . . . . . . . . . . . . . 6-7
Set-Up a Controller Slot for the
1756-DHRIO Module . . . . . . . . . . . . . . . . . . . . 6-8
Set-Up a Routing Table for the
1756-DHRIO Module . . . . . . . . . . . . . . . . . . . . 6-9
Configure Local Message Instructions . . . . . . . . 6-10
Configure Remote Message Instructions . . . . . . . 6-11
DH+ Messaging From a SLC-5/04 to a Logix5550
With Multiple ControlLogix Chassis . . . . . . . . . . . . 6-12
Set the Module Switches . . . . . . . . . . . . . . . . . . . 6-13
Set-Up a Routing Table for the
1756-DHRIO Module . . . . . . . . . . . . . . . . . . . 6-14
Configure Message Instructions . . . . . . . . . . . . . 6-15
Chapter Summary and What’s Next . . . . . . . . . . . . . . 6-16
Chapter 7
Local DH+ Messaging From a Logix5550 to
a PLC-5 With One ControlLogix Chassis . . . . . . . . . 7-2
Set the Module Switches . . . . . . . . . . . . . . . . . . . . 7-3
Configure Message Instructions . . . . . . . . . . . . . . 7-4
DH+ Messaging From a Logix5550 to a PLC-5
With Multiple ControlLogix Chassis Over DH+ . . . . 7-5
Set the Module Switches . . . . . . . . . . . . . . . . . . . . 7-6
Set-Up a Routing Table for the First
1756-DHRIO Module . . . . . . . . . . . . . . . . . . . . 7-7
Set-Up a Routing Table for the Second
1756-DHRIO Module . . . . . . . . . . . . . . . . . . . . 7-7
Configure Message Instructions . . . . . . . . . . . . . . 7-8
DH+ Messaging From a Logix5550 to a SLC-5/04
Over ControlNet and DH+ With Multiple
ControlLogix Chassis . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
Set the Module Switches . . . . . . . . . . . . . . . . . . . 7-10
Set-Up a Routing Table for the
1756-DHRIO Module . . . . . . . . . . . . . . . . . . . 7-11
Configure Message Instructions . . . . . . . . . . . . . 7-12
Chapter Summary and What’s Next . . . . . . . . . . . . . . 7-13
Publication 1756-6.5.14 - August 1998
toc–iv Table of Contents
Logix5550 to Logix5550
Messaging
Chapter 8
CIP Messaging Between a Logix5550 and
a Logix5550 Over One Link . . . . . . . . . . . . . . . . . . . 8-2
Set the Module Switches . . . . . . . . . . . . . . . . . . . . 8-3
Configure Message Instructions . . . . . . . . . . . . . . 8-4
CIP Message Routing Between a Logix5550 and
a Logix5550 Over Two Links . . . . . . . . . . . . . . . . . . 8-5
Set the Module Switches . . . . . . . . . . . . . . . . . . . . 8-6
Configure Message Instructions . . . . . . . . . . . . . . 8-7
Chapter Summary and What’s Next . . . . . . . . . . . . . . . 8-8
Basics of Using Remote I/O Chapter 9
Introduction to Remote I/O . . . . . . . . . . . . . . . . . . . . . . 9-1
Selecting Devices That You Can Connect . . . . . . . . . . . 9-2
Designing a Remote I/O Network . . . . . . . . . . . . . . . . . 9-3
Network Design Guidelines . . . . . . . . . . . . . . . . . 9-3
Cable Design Guidelines . . . . . . . . . . . . . . . . . . . . 9-3
Configuring a DHRIO Channel as a RIO Scanner . . . . 9-5
Chapter Summary and What’s Next . . . . . . . . . . . . . . . 9-6
Communicating with Remote I/O Chapter 10
DHRIO Module Operation . . . . . . . . . . . . . . . . . . . . . 10-1
Exchanging I/O Data Between Adapters on
the RIO Link and the 1756-DHRIO Module . . 10-2
Exchanging I/O Data Between the Logix5550
and the 1756-DHRIO Module . . . . . . . . . . . . . 10-2
I/O Configuration Tree in Controller Organizer
in RSLogix 5000 . . . . . . . . . . . . . . . . . . . . . . . 10-3
RIO Scanner Status . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3
Adapter Module I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3
Setting the Rate of Data Exchange Between the
Logix5550 and the 1756-DHRIO Module . . . . . . . . 10-4
Requested Packet Interval (RPI) . . . . . . . . . . . . . 10-4
RIO Scanner Status Update Rate With the
1756-DHRIO in a Local Chassis . . . . . . . . . . . 10-4
RIO Scanner Status Update Rate With the
1756-DHRIO Module in a Remote Chassis . . 10-4
Setting the Rate of I/O Data Exchange Between
the Logix5550 and the 1756-DHRIO Module . . . . . 10-5
Minimum Requested Packet Intervals (RPIs) . . . 10-6
Adapter Module I/O Update Rate with
the 1756-DHRIO Module in the Local Chassis 10-7
Adapter Module I/O Update Rate with the
1756-DHRIO Module in the Remote Chassis . 10-8
RIO Scanner Failure Notification . . . . . . . . . . . . . . . . 10-9
RIO Adapter Failure Notification . . . . . . . . . . . . . . . . 10-9
Inhibiting the DHRIO Module Connections . . . . . . . 10-10
Publication 1756-6.5.14 - August 1998
Connecting a Logix5550 to
Remote I/O
Block Transfers
Table of Contents toc–v
Inhibiting an RIO Connector Adapter . . . . . . . . . . . . 10-10
Increased Remote I/O System Throughput . . . . . . . . 10-11
Sending Block Transfer Data . . . . . . . . . . . . . . . . . . . 10-12
Block Transfer Notification . . . . . . . . . . . . . . . . . . . . 10-12
Block Transfer ‘Pass-Through’ Messages . . . . . . . . . 10-13
Troubleshooting Remote I/O
Communication Difficulties . . . . . . . . . . . . . . . . . . 10-14
Chapter Summary and What’s Next . . . . . . . . . . . . . 10-16
Chapter 11
Scanning Remote FLEX Adapter Through a
1756-DHRIO Module in a Local 1756-Chassis . . . . 11-2
Set the Module Switches . . . . . . . . . . . . . . . . . . . 11-3
Configure DHRIO Module . . . . . . . . . . . . . . . . . 11-3
Configure the FLEX Adapter . . . . . . . . . . . . . . . 11-4
Scanning Remote FLEX Adapters Through
Multiple 1756-DHRIO Modules in a Local Chassis 11-6
Set the Module Switches . . . . . . . . . . . . . . . . . . . 11-7
Configure 1st DHRIO Module . . . . . . . . . . . . . . 11-7
Configure 1st FLEX Adapter . . . . . . . . . . . . . . . 11-8
Configure 2nd DHRIO Module . . . . . . . . . . . . . 11-10
Configure 2nd FLEX Adapter . . . . . . . . . . . . . . 11-11
Scanning 1771 Remote I/O Adapters Through
a 1756-DHRIO in a Remote Chassis . . . . . . . . . . . 11-12
Set the Module Switches . . . . . . . . . . . . . . . . . . 11-13
Configure 1st CNB Module . . . . . . . . . . . . . . . 11-14
Configure 2nd CNB Module . . . . . . . . . . . . . . . 11-15
Configure DHRIO Module . . . . . . . . . . . . . . . . 11-16
Configure 1771-ASB Adapter . . . . . . . . . . . . . . 11-17
Run RSNetworx . . . . . . . . . . . . . . . . . . . . . . . . 11-18
Chapter Summary and What’s Next . . . . . . . . . . . . . 11-18
Chapter 12
Block Transfers to Remote FLEX I/O Modules
Through a 1756-DHRIO in a Local Chassis . . . . . . 12-2
Set the Module Switches . . . . . . . . . . . . . . . . . . . 12-3
Configure DHRIO Module . . . . . . . . . . . . . . . . . 12-3
Configure the FLEX Adapter . . . . . . . . . . . . . . . 12-4
Configure Block Transfer Module . . . . . . . . . . . 12-6
Configure Message Instruction. . . . . . . . . . . . . . . 12-7
Block Transfers to Remote 1771-ASB I/O Modules
Through a 1756-DHRIO in a Remote Chassis . . . . . 12-8
Set the Module Switches . . . . . . . . . . . . . . . . . . . 12-9
Configure 1st CNB Module . . . . . . . . . . . . . . . 12-10
Configure 2nd CNB Module . . . . . . . . . . . . . . . 12-11
Configure DHRIO Module . . . . . . . . . . . . . . . . 12-12
Configure 1771-ASB Adapter . . . . . . . . . . . . . . 12-13
Configure 1771-BT Module . . . . . . . . . . . . . . . 12-14
Publication 1756-6.5.14 - August 1998
toc–vi Table of Contents
Troubleshooting
PCCC Commands Supported by the Data Highway Plus Module
Specifications
Chapter Summary and What’s Next . . . . . . . . . . . . . 12-15
Chapter 13
Checking Power Supply and Module Status . . . . . . . . 13-1
Troubleshooting the Power Supply . . . . . . . . . . . . . . . 13-2
Troubleshooting the Module . . . . . . . . . . . . . . . . . . . . 13-2
Monitoring DH+ Communication Channels . . . . . . . . 13-5
Chapter Summary and What’s Next . . . . . . . . . . . . . . 13-6
Appendix A
Appendix B
Publication 1756-6.5.14 - August 1998
What This Chapter Contains
What the Module Does
Routing Limitations
Chapter
1
ControlLogix Data Highway Plus/Remote
I/O Communication Interface Module
This chapter describes the module and what you must know and do before you begin to use it. The following table describes what this chapter contains and its location.
For information about:
What the Module Does
Routing Limitations
Module Features
Compliance to European Union Directives
Preventing Electrostatic Discharge
Removal and Insertion Under Power
Chapter Summary and What’s Next
See page:
The Data Highway Plus/RIO module supports the following types of communication:
• DH+ Messaging
• Control and Information Protocol (CIP) Messaging
• Remote I/O
You can send messages between devices on Data Highway Plus networks and devices on other networks such as ControlNet,
Ethernet, or other DH+.
Using the RIO functionality, a 1756-DHRIO channel in scanner mode transfers discrete and block-transfer data with remote I/O devices.
This module allows connection to multiple remote I/O adapters.
The 1756-DHRIO module has the capability of routing a message through up to four communications networks and three chassis. This is only a limitation on the routing of a message and not on the total number of networks or chassis in a system.
Publication 1756-6.5.14 - August 1998
1-2 ControlLogix Data Highway Plus/Remote I/O Communication Interface Module
DH+ and CIP Messaging
The 1756-DHRIO module allows an information exchange between devices, such as PLCs, Logix5550 processors in ControlLogix chassis, and SLCs.
With the 1756-DHRIO module, you may exchange information in any of the following scenarios:
• between PLCs/SLCs on different networks
• between the Logix5550 and a PLC/SLC
• between Logix5550s
The following illustration shows an example system. Two
ControlLogix Gateways link existing Data Highway Plus networks.
Communication between PLC-5 programmable controllers on different networks is accomplished in the same manner used for communication within a network.
Data Collection and
Recipe Management
Programming
Terminal
ControlLogix
Chassis
Data Highway Plus
PLC-5 SLC 500 RSView
ControlLogix
Chassis
Data Highway Plus
PLC-5 SLC 500 RSView
41275
Publication 1756-6.5.14 - August 1998
ControlLogix chassis
Logix5550
ControlLogix Data Highway Plus/Remote I/O Communication Interface Module
Remote I/O
1-3
When a channel on the module is configured for Remote I/O, the module will act as a scanner for the RIO network. The Logix5550 controller (1756-L1) communicates to the module’s RIO scanner to send and receive the I/O on the RIO network.
The following illustration shows an example system.
DHRIO module
1771-ASB
1746-ASB
Remote I/O PLC-5/20 in Adapter mode
1794-FLEX I/O
41276
Publication 1756-6.5.14 - August 1998
1-4 ControlLogix Data Highway Plus/Remote I/O Communication Interface Module
Module Features
Use the following illustration to identify the external features of the
Data Highway Plus/RIO module.
Side view
Network Type switches
(behind cover)
1
0
7
2
6
3
4
5
Switch 1
Channel A
Network Type
0
1
7
2
6
3
4
5
Switch 6
Channel B
Network Type
Channel
A
Specify Network Type Set Switch
DH+
RIO Scanner
Illegal
0
1
2-7
Channel
B
DH+
RIO Scanner
Illegal
0
1
2-7 h 5
4
5
3 2
6
(1s)
24 ss tion ddre
7
0
1
Switc osi in P nel B A
4 ch
6
4
5
3 2
7
0
1
(10s)
Swit
Chan own Sh
3
6 ch
4
5
3
(1s)
2
10 ss tion dre
7
0
1
Swit
Ad
Posi h 2
4
5
3 2
6
(10s)
in nel A wn
7
0
1
Switc
Chan
Sho
Backplane connector
(CIP=Port 1)
Alphanumeric status indicator
Channel and module status indicators
8-pin mini-DIN
Programming
Terminal
Channel A
(CIP=Port 2)
Channel B
(CIP=Port 3)
Wiring label
Front view
Network Address switches
(behind cover)
41277
Other module features are:
Door
41278
• uses routing table that allows DH+ only devices to use the
1756-DHRIO module and ControlLogix chassis to access other networks
• supports routing communications to and from other modules
• has no limit on number of modules per chassis, up to the number of available slots and the capabilities of the power supply
• can be removed and inserted under power without disrupting power to other modules in the chassis
Publication 1756-6.5.14 - August 1998
Network type switches
(behind cover)
ControlLogix Data Highway Plus/Remote I/O Communication Interface Module
Setting Switches
1-5
Before installing the module, you must set the network type switches for DH+ or RIO, depending on your application. For a channel configured as DH+, you must also select a node address within the range of 00-77. Node addresses are set and displayed in octal.
Important: If you require a channel to be configured for DH+, use
Channel A. By doing so, you can connect your programming terminal to the connector on the front of the module and communicate to devices on the network.
If only one channel is needed for RIO, use Channel B.
Set the network type and node address switches as shown below.
1
0
7
2
6
3
5
4
1
0
7
2
6
3
4
5
This example shows channel A set for DH+ and channel B set RIO
0
1
7
2
6
3
4
5
Switch 1
Channel A
Network Type
0
1
7
2
6
3
4
5
Switch 6
Channel B
Network Type
Channel
A
Channel
B
Specify Network Type Set Switch
DH+
RIO Scanner
Illegal
DH+
RIO Scanner
Illegal
0
1
2-7
0
1
2-7
4 s
4
3
5 h 5
2
6
(1s) ion 2 ddres sit
A
Switc
1
0
7
in Po el B own
4
3
5 h 4
2
6
1
0
7
Switc
(10s)
Chann
Sh
4
3
5 h 3 n 10 ss
(1s)
2
6 tio
1
0
7
Switc
Addre
Posi l A
4
3
5 h 2
2
6 n in ow anne
Sh
Ch
(10s)
Switc
1
0
7
Channel
A
Channel
B
Specify Network Type Set Switch
DH+
RIO Scanner
0
1
Illegal
DH+
RIO Scanner
Illegal
2-7
0
1
2-7
Node type switches
(behind cover)
4
3
5
2
6
1
0
7
4
3
5
2
6
1
0
7
4
3
5
2
6
1
0
7
4
3
5
2
6
1
0
7
20810
This example shows A node address at 010 and channel B at 024
Important: These node switches are not used with RIO.
Publication 1756-6.5.14 - August 1998
1-6 ControlLogix Data Highway Plus/Remote I/O Communication Interface Module
Alphanumeric Indicators
At module power-up, the alphanumeric indicator illuminates and cycles through a sequence of power-up messages.
Included in the sequence is a scrolling display of the series letter, two digits of the firmware major revision, a dot, and two digits of the firmware minor revision. For example, the display will scroll B02.14 for a series B module with firmware revision 2.14.
After the power-up sequence, a sequence of information and status messages are displayed on a continuous cycle. The following table shows the sequence of messages for a module that has channel A set for DH+ and channel B set for RIO.
Table 1.1
Data Highway Plus/Remote I/O
Sequence of display:
A DH
A#XX
XXXX
B IO
SCAN
XXXX
Where:
A is the channel (A or B) and DH indicates network type is DH+
XX is the channel’s node address
XXXX is the channel’s status message
B is the channel (A or B) and IO is network type
SCAN indicates scanner
XXXX is the channel’s status message
Compliance to
European Union Directives
The module’s alphanumeric indicators will stop cycling and display an error message or error code if it detects an error that is severe. See
chapter 13 for a detailed list of the error messages and the cyclic
status messages that my display across the alphanumeric indicator and for troubleshooting information.
This product has the CE mark and is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file:
• EN 50081-2EMC - Generic Emission Standard, Part 2 -
Industrial Environment
• EN 50082-2EMC - Generic Immunity Standard, Part 2 -
Industrial Environment
This product is intended for use in an industrial environment.
Publication 1756-6.5.14 - August 1998
ControlLogix Data Highway Plus/Remote I/O Communication Interface Module
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low
Voltage, by applying the safety requirements of EN 61131-2
Programmable Controllers, Part 2 - Equipment Requirements and Tests.
1-7
For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications:
• Industrial Automation Wiring and Grounding Guidelines
For Noise Immunity, publication 1770-4.1
• Guidelines for Handling Lithium Batteries, publication AG-5.4
• Automation Systems Catalog, publication B111
Preventing Electrostatic Discharge
The Data Highway Plus module is sensitive to electrostatic discharge.
!
ATTENTION: Electrostatic discharge can damage integrated circuits or semiconductors if you touch backplane connector pins. Follow these guidelines when you handle the module:
• Touch a grounded object to discharge static potential
• Wear an approved wrist-strap grounding device
• Do not touch the backplane connector or connector pins
• Do not touch circuit components inside the module
• If available, use a static-safe work station
• When not in use, keep the module in its static-shield bag
Publication 1756-6.5.14 - August 1998
1-8 ControlLogix Data Highway Plus/Remote I/O Communication Interface Module
Removal and Insertion Under
Power
This module is designed to be installed or removed while chassis power is applied.
!
ATTENTION: When you insert or remove a module while backplane power is on, an electrical arc may occur.
An electrical arc can cause personal injury or property damage by:
• sending an erroneous signal to your system’s field devices causing unintended machine motion or loss of process control.
• causing an explosion in a hazardous environment.
Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector.
Worn contacts may create electrical resistance that can affect module operation.
Chapter Summary and What’s Next
In this chapter you learned about:
• what the module does
• module features
• compliance to European Union Directives
• electrostatic discharge
• removal and insertion under power
Move on to Chapter 2 to learn about Using Data Highway Plus.
Publication 1756-6.5.14 - August 1998
Chapter
2
Basics of Using Data Highway Plus
What This Chapter Contains
This chapter describes the basics of Data Highway Plus. The following table describes what this chapter contains:
For information about using:
What is Data Highway Plus
Selecting Devices that You Can Connect
Link Design
Programming Terminal Port
Application Guidelines
Chapter Summary and What’s Next
See page:
What is Data Highway Plus
On the most basic level, Data Highway Plus is a wire or cable and a protocol that connects computers and peripheral devices so that they can communicate. The actual wire used for a network is called the network medium.
A DH+ link transfers data between PLC-5s, SLCs, and other devices that use the DH+ network. These devices are called stations. You can connect a maximum of 32 stations to a single DH+ link.
Selecting Devices that You
Can Connect
The following table lists the devices you can connect to a DH+ link.
Table 2.1
Selecting Devices You Can Connect
To:
Connect PLC-3 family processors to DH+
You can use:
Scanner Communication Adapter Module
Connect PLC-5 family processors to DH+
Connect PI systems to DH+
Connect IBM XT or AT compatible computers to DH+
Perform data transmission, management, and local network diagnostics over DH+ network
Perform data transmission, management, and local network diagnostics over DH+ network
Add memory, storage, and I/O capabilities to computers through DH+
Connect other SLCs to DH+
Connect AutoMax to DH+
Classic and Enhanced PLC-5 processors using on-board DH+ ports
ControlNet and EtherNet PLC-5 processors using on-board DH+ ports
Resource Manager Module
Resource Manager Module
Data Highway/Data Highway Plus
Communication Interface Module
Data Highway Plus XT/AT Interface Module
KTX Communication Interface Card
KTXD Communication Interface Card
PCMK Communication Card
SLC-5/04 Processor
AutoMax DH+ Interface
Catalog
Number:
1775-S5
1775-SR5
1785-Series
Required
Cables:
1770-CD
1770-CD
5130-RM1
5130-RM2
5130-KA
1784-KT
1784-KTX
1784-KTXD
1784-PCMK
1747-Series
57C-442
1770-CD
1770-CD
1770-CD
1770-CD
PCM6/B cable assembly
1770-CD
1770-CD
Publication 1756-6.5.14 - August 1998
2-2
Link Design
Basics of Using Data Highway Plus
Use 1770-CD (Belden 9463) cable to connect your module to DH+.
Connect a DH+ network using a daisy chain or trunk line/drop line configuration.
Trunk line/drop line considerations:
When using a trunk line/drop line configuration, use 1770-SC station connectors and follow these cable-length guidelines:
• trunk line-cable length—depends on the communication rate of the link
• drop-cable length—30.4 m (100 cable-ft.)
For more information about designing trunk line/ drop line configurations, see the Data Highway/
Data Highway Plus/Data Highway II/
Data Highway-485 Cable Installation Manual, publication 1770-6.2.2.
Verify that your system’s design plans specify cable lengths within allowable measurements.
Important: The maximum cable length for DH+ depends on the transmission rate. Configure all devices on a DH+ link to communicate at the same transmission rate.
Also note that the 1756-DHRIO module only supports
DH+ communication at the 57.6kbps rate. Be sure to use the correct cable.
For daisy chain configurations, use this table to determine the total cable length you can use.
Table 2.2
Choosing the Correct Cable Length
A DH+ link using this communication rate:
57.6 kbps
Cannot exceed this cable length:
3,048 m (10,000 ft)
For proper operation, terminate both ends of a DH+ link by using the external resistors shipped with the 1756-DHRIO.
Table 2.3
Choosing the Correct Resistor Rating
If your DH+ I/O link operates at:
57.6 kbps
Use this resistor rating:
150
Ω
Programming Terminal Port
The programming terminal connector is the same physical link as
Channel A. See the diagram below.
Programming terminal connector
Channel A
41279
Important: When configuring the module switches, remember the programming terminal connector can only be used if
Channel A is set for DH+.
Publication 1756-6.5.14 - August 1998
Application Guidelines
Basics of Using Data Highway Plus 2-3
Consider the following application guidelines when configuring a
DH+ link for your system.
• Minimize the number of DH+ nodes to achieve acceptable response times. Keep in mind the size and frequency of messages exchanged between devices.
• Limit the number of stations on your network when you are trying to achieve fastest control response time. Establish separate DH+ networks to bring-on additional stations.
• Do not add or remove stations from the network during machine or process operation. If the network token resides with a device that is removed, the token may be lost to the rest of the network. The network is automatically reestablished, but it could take several seconds. Control would be unreliable or interrupted during this time.
• When possible, do not program processors online during machine or process operation. This could result in long bursts of DH+ activity that could increase response time.
• When possible, add a separate DH+ link for programming processors to keep effects of the programming terminal from the process DH+ link.
Chapter Summary and What’s Next
In this chapter, you learned about:
• selecting devices that you can connect
• link design
• application guidelines
Move on to Chapter 3 to learn about DH+ operation.
Publication 1756-6.5.14 - August 1998
What This Chapter Contains
Two Methods of
Communication Over Data
Highway Plus
Chapter
3
DH+ Operation
This chapter describes the operation of Data Highway Plus. The following table describes what this chapter contains:
For information about using:
Two Methods of Communication
Over Data Highway Plus
Using DH+ Messaging
Benefits of DH+ Messaging
Local DH+ Messaging
Before Programming in a Controller
Remote DH+ Messaging
Application Timeout
Example DH+ Routing Configuration
Using Control and Information Protocol
Chapter Summary and What’s Next
See page:
The 1756-DHRIO module will act as a gateway/bridge for two methods of communication. These methods are:
• DH+ Messaging
• Control and Information Protocol (CIP) Messaging
The following table shows what devices support each method of communication:
Table 3.1
Types of Communication on the 1756-DHRIO module
Type of communication:
DH+ messaging
Control and Information Protocol
(CIP) messaging
Devices supporting this type:
PLC-3
PLC-5
PLC-5/250
SLC-500
Logix5550
RSLinx 1.7
Interchange
RSLogix
Logix5550
This chapter provides a detailed explanation of each method. The following chapters provide examples of how these methods might be used.
Publication 1756-6.5.14 - August 1998
3-2 DH+ Operation
Using DH+ Messaging
Benefits of DH+ Messaging
Local DH+ Messaging
Most devices with a DH+ channel support this type of
communication. These devices are listed in Table 2.1 Selecting
Devices that You Can Connect on page 2-1.
DH+ messaging is further divided into two types:
• Local DH+ Messaging
• Remote DH+ Messaging
Before you can design a control system to meet your application needs, be aware of the difference between Local DH+ Messaging and
Remote DH+ Messaging.
DH+ Messaging provides the following benefits:
• it allows you to send messages between devices on the same link
• it allows you to send messages between devices on different links
• it is compatible with many existing Allen-Bradley modules
Devices use local DH+ messaging to communicate between devices on the same physical link.
A device that uses local DH+ messaging must be able to:
• generate local DH+ packets
• support local DH+ protocol
• send and receive messages
A local DH+ message sent on a DH+ network has only enough address information to get the message to a target node on the same
DH+ network. This limits the use of local DH+ messaging in a system.
The 1756-DHRIO module has added functionality to allow the use of local DH+ messaging in limited cases.
Publication 1756-6.5.14 - August 1998
DH+ Operation
Receiving Local DH+ Messages on DH+
3-3
Because a local DH+ message only has enough address information to get the message to a target node on the same DH+ network, the
1756-DHRIO module that receives this message cannot identify where to send the message to. In this case, the 1756-DHRIO module uses the configuration parameter Controller Slot.
The 1756-DHRIO module sends any local DH+ message it receives to the single Controller Slot (default=0) configured for the receiving
DH+ channel on the 1756-DHRIO module. You must use the
ControlLogix Gateway Configuration Tool (1756-GTWY) to configure the Controller Slot.
There are some messages that, when received by the 1756-DHRIO module, are not sent to the controller slot. In this case, the
1756-DHRIO module generates a response to the message. For a
complete listing of these messages, see Appendix A.
Local DH+ messaging does not require a populated routing table.
Local DH+ messaging does require a default (a properly emptied) or an applied (a properly populated and saved) routing table, and a default or applied controller slot for each channel configured for
DH+.
Important: Local DH+ Messaging can only target one Logix5550 controller per DH+ channel. Also, the Logix5550 must reside in the same chassis as the 1756-DHRIO module receiving the message.
Sending Local DH+ Messages on DH+
If a 1756-DHRIO channel receives a DH+ message with a destination link ID=0 from a Logix5550 processor in the same chassis, the module will send the message as a local DH+ message.
Important: The target of the DH+ message must be on the same DH+ link as the 1756-DHRIO module sending the message.
Also, the Logix5550 must reside in the same chassis as the 1756-DHRIO module sending the message on DH+.
Publication 1756-6.5.14 - August 1998
3-4 DH+ Operation
Limitations of Local DH+ Messaging
When using Local DH+ Messaging, you must remember the following:
• The DH+ message contains only a node ID for a node on the
DH+ network
• A local DH+ message sent to the node ID of a port on the1756-DHRIO module will be forwarded to a single user-configured controller slot
• Messages on one DH+ network cannot be routed to other networks
The following example shows a PLC-5 sending a message to port A on the 1756-DHRIO module. Because the controller slot for port A is configured to “0”, the message is forwarded to the Logix5550 in slot 0.
Logix5550 DHRIO module
0 1 2 3
Channel A node number: 010 controller slot=0
PLC-5 processor B node number: 025
41458
Publication 1756-6.5.14 - August 1998
Before Programming in a Controller
For more information . . .
DH+ Operation
Routing Error in Local DH+ Messaging
3-5
If the 1756-DHRIO has a problem with routing a DH+ message, it may return a response with an error status of D0 hex. A PLC-5 will display this error as D000 hex when monitoring the message instruction. If you receive this error message:
• check your message instruction to make sure a valid destination node was entered
• check your default slot configuration to make sure that it matches the location of the Logix5550 in the chassis
• make sure the 1756-DHRIO module is powered-up
Before programming your message block instructions in your
PLC-5/SLC, you must:
• determine which links will send and receive DH+ Local messages
• draw a network - make sure you meet the design requirements for Local DH+ messages
• assign DH+ node numbers
• use the ControlLogix Gateway Configuration software to enter the controller slot or execute the default for the controller slot for each channel configured for DH+
Important: These configuration steps must be done for each
1756-DHRIO in the your system.
For more information on the ControlLogix Gateway Configuration
Software, see the ControlLogix Gateway Configuration software user manual, publication 1756-6.5.7.
Publication 1756-6.5.14 - August 1998
3-6 DH+ Operation
Remote DH+ Messaging
Link ID 1
Devices use remote DH+ messaging to communicate between devices on physically separate networks.
When using remote DH+ messaging, you must include the following in the message instruction:
• destination link ID - a user-configured number representing a network in your system
• remote node or slot - node or slot on the remote network you want to communicate with
If the message originates on DH+, you must also include:
• local DH+ node - node on your local DH+ network capable of routing the message
If the message originates on Ethernet, ControlNet or ControlLogix, you must also include:
• a CIP path to the first 1756-DHRIO module
The following example of remote DH+ messaging shows a PLC processor A sending a message to PLC processor B:
DHRIO module
ControlLogix chassis
Channel A node: 020
Channel B node: 025
Link ID 2
41363
PLC-5/25 processor A node:010
PLC-5 processor B node: 030
In the example above, the following information must be included in the remote DH+ message routing message instruction:
• local DH+ node = 020
• destination link ID = 2
• remote DH+ node = 030
Publication 1756-6.5.14 - August 1998
DH+ Operation
A device that uses remote DH+ messaging must be able to:
3-7
• generate Remote DH+ packets
• support Remote DH+ protocol
• send and receive messages
Remote DH+ messaging should be used when:
• the message originating device or the message target device
is one of the devices listed in Table 2.1 Selecting Devices
that You Can Connect on page 2-1
• there is a DH+ link in the message’s path from originator to target
• the message originating device and the message target device are on separate networks or the message target is in a
ControlLogix chassis and there is more than one Logix5550 target in the chassis
To use remote DH+ messaging, each network that is an originating network or target network must have a unique link ID. The
1756-DHRIO module requires these link IDs to be decimal values between 1-199. Each DH+ channel on a 1756-DHRIO must have its own unique link ID.
A source network is the network the message originates on. The destination network is the network the message is targeted for. This applies to all source and destination networks, whether they are DH+,
ControlNet, Ethernet or a ControlLogix chassis.
Important: For remote DH+ messaging, the ControlLogix chassis should be considered a separate, independent network.
Therefore, a system of 1 DH+ network and one
ControlLogix chassis is a two link system.
The ControlLogix chassis is required to be a separate, independent link for DH+ messaging if there is more than one message target Logix5550 controller in a
ControlLogix chassis.
Publication 1756-6.5.14 - August 1998
3-8 DH+ Operation
For more information . . .
The 1756-DHRIO module contains a routing table that you define for your application. You must use the ControlLogix Gateway
Configuration Tool (1756-GTWY) to configure your routing table.
For more information on the ControlLogix Gateway Configuration
Software, see the ControlLogix Gateway Configuration software user manual, publication 1756-6.5.7.
By using the routing table, the 1756-DHRIO allows existing devices, such as PLC-5s, to use ‘DH+ Remote Addressing’ for messaging.
The routing table used in your 1756-DHRIO module contains information used to steer Remote DH+ Messages through the system to ‘remote’ nodes located on separate networks.
Before programming your message block instructions in your controller, you must:
• determine which links will send and receive remote
DH+ messaging
• draw a network - make sure you meet the design requirements for remote DH+ messaging
If you are using remote DH+ messaging, you must also:
• assign link numbers - numbers must be a decimal value between 1-199. ControlLogix chassis may also be assigned link IDs. Remember that the programming terminal and channel A are the same physical link
• assign DH+ node numbers
• use the ControlLogix Gateway Configuration software to enter routing tables into each 1756-DHRIO module.
Publication 1756-6.5.14 - August 1998
DH+ Operation
Limitations of Remote DH+ Messaging
3-9
Remote DH+ Messages are actually encapsulated in Control and
Information Protocol (CIP) messages and sent on Control and
Information Protocol connections when they are sent across
ControlNet, Ethernet, and the ControlLogix chassis. Although this is transparent to the user, there are resource limits associated with
Control and Information Protocol on the 1756-DHRIO.
The 1756-DHRIO will support 32 CIP connections per DH+ channel.
These connections are made when devices want to send a DH+ message out of a 1756-DHRIO’s DH+ channel and are made by the
1756-DHRIO when it receives DH+ message traffic. The
1756-DHRIO will recover connections if they are not being used.
Because of the various paths involved, the 1756-DHRIO will respond to ‘out of connections’ in one of the following ways:
• The 1756-DHRIO may generate a Routing Error (see page
4-9) on DH+ for DH+ message requests if there are no
connections available.
• The Message Originator may generate an Application
Timeout (see page 3-11) if a remote 1756-DHRIO has no
connections available for a DH+ Message response.
• The Message Originator may receive an ‘out of connections’ error if the path from the Originator to the
1756-DHRIO is ControlLogix chassis, ControlNet or
Ethernet.
Routing Errors in Remote DH+ Messaging
If the 1756-DHRIO has a problem with routing a Remote DH+
Message, it may return a response with an error status of D0 hex. A
PLC-5 will display this error as D000 hex when monitoring the message instruction. If you receive this error message:
• check your message instruction to make sure a valid gateway node, link ID and destination node were entered
• check your routing table in each DH+ module that the message passes through
• make sure all 1756-DHRIO modules are connected and powered-up
Publication 1756-6.5.14 - August 1998
3-10 DH+ Operation
Configuration Information in DH+ Messaging
When you are using DH+ messaging, you must use either default configuration or write specific configuration for your application.
The following configuration information is stored in the non-volatile memory on your 1756-DHRIO module when you apply configuration using the Gateway Configuration Tool (1756-GTWY):
• Any routing table that may be needed to send DH+ messages through the module - must be applied to the module’s configuration separately from other information
• Controller slot for each DH+ channel - must be applied to the module’s configuration separately from other information
• Slot number of the module
• Chassis serial number
Important: If you restore default defaults using the Gateway
Configuration Tool (1756-GTWY), the slot number and chassis serial number are stored in the 1756-DHRIO module’s non-volatile memory but no routing table is used and the controller slot for both DH+ channels is set to 0.
Generating Configuration Faults
When you insert a 1756-DHRIO module in a ControlLogix chassis, the configuration information stored in the module’s non-volatile memory is compared to the slot and serial number of the chassis it is entering. If any information does not match, the 1756-DHRIO module will generate a configuration fault.
For a complete listing of the configuration faults that may be
displayed on your 1756-DHRIO module, see chapter 13.
Publication 1756-6.5.14 - August 1998
Application Timeout
DH+ Operation 3-11
When an error occurs while sending a message to a remote link, it will appear to the sending station as an application timeout because error messages are not routed back. When an error occurs during routing, it may be dropped.
For example, if a PLC 5/40 processor sends a message to a PLC processor, and the PLC-5/25 processor’s buffers are full, three things happen:
• the PLC-5/25 processor refuses the message because the buffers are full
• when no reply is received, the originator detects an application timeout
• the originator increments its error count
The PLC-5/40 processor can retry to send the message later.
ControlLogix chassis
Example of an Application Timeout
DHRIO module DHRIO module
DH+ link 1
Routed messages over the backplane
PLC-5/40 processor
PLC-5/40 detects an application timeout and increments the error count
DH+ link 2
PLC-5/25’s buffers are full
PLC-5/25 processor 19770
Publication 1756-6.5.14 - August 1998
3-12 DH+ Operation
Example DH+ Routing
Configuration
PLC-5/25 processor node: 030
1756-DHRIO module
Ch. A node: 015
Ch. B node:016
1756-L1 controller slot 0
ControlLogix chassis link ID 6
The figure below shows an example DH+ routing configuration.
Node numbers on DH+ are given in octal. Node numbers on
ControlNet and slot numbers in ControlLogix chassis are given in decimal. Links IDs for all networks are given in decimal.
Important: Some devices in the figure have the same node number because they are on different networks. Devices on the same network must have unique node numbers. You must assign the node numbers.
1756-CNB module node: 20
1756-DHRIO module node: 030 node:031
1756-L1M1 controller slot 5
DH+ link ID 1
DH+ link ID 4
DH+ link ID 5
PLC-5/15 processor node: 020
DH+ link ID 2
PLC-5/25 processor node: 020
PLC-5/40 processor node: 020
ControlNet link ID 3
PLC-5C processor node: 35
PLC-5/60 processor node:020
PLC-5C processor node: 45
41285
Publication 1756-6.5.14 - August 1998
Using Control and Information
Protocol (CIP) Messaging
ControlLogix system #1
Logix5550 Controller module
DH+ Operation 3-13
Control and Information Protocol (CIP) is the new protocol that serves as the communications mechanism on ControlLogix chassis,
ControlNet network and Ethernet with the EPIC protocol.
Like DH+ messaging, CIP supports communication between devices on the same link and physically separate links. However, CIP
Messaging uses a different method to route messages than
DH+ Messaging.
CIP uses a ‘relative path’ concept for routing messaging. Because the message itself, or the connection the message is sent on, contains all the information required to route the message, CIP messages do not require any routing table or link IDs. For more information on paths,
Devices such as ControlLogix devices, devices that use the
ControlNet network, and devices that use EPIC protocol on Ethernet support this new type of communication.
Important: Your 1756-DHRIO module supports bridging CIP messaging over a DH+ link. Your 1756-DHRIO module does not support bridging CIP I/O data from a
Logix5550 controller to an 1756-I/O module.
The message originator, target, and all modules and links between them must support CIP to send a message using CIP protocol.
DH+ module
ControlLogix system #2
Logix5550
Controller module
DH+ module
Node:0 01
Node: 002
41289
Publication 1756-6.5.14 - August 1998
3-14 DH+ Operation
Limitations of CIP Messaging
The 1756-DHRIO module will support bridging a total of 5 CIP connections. These 5 count against the 32 connections per DH+ channel. So if a 1756-DHRIO module has used 30 connections for
DH+ Message Routing, it can only use 2 connections to bridge a CIP message through the module.
Chapter Summary and What’s Next
In this chapter, you learned about:
• methods of communication
• local DH+ message routing
• remote DH+ message routing
• CIP message routing
Move on to Chapter 4 to learn about programming terminal operation
over DH+.
Publication 1756-6.5.14 - August 1998
Chapter
4
Programming Terminal Operation
Over DH+
What This Chapter Contains
Connecting Your Programming
Terminal Over DH+ Using
RSLogix 5
This chapter describes how to connect your programming terminal over DH+. The following table describes what this chapter contains:
For information about using:
Connecting Your Programming Terminal Over
DH+ Using RSLogix 5
Connecting Your Programming Terminal Over
DH+ Using RSLogix 500
Connecting Your Programming Terminal Over
DH+ Using RSLogix 5000
Defining Connection Paths
Chapter Summary and What’s Next
See page:
You must use programming software specific to your application to connect your programming terminal on the 1756-DHRIO module over DH+.
For applications connecting RSLogix 5 to a PLC-5:
1. Start the RSLogix 5 software.
2. From the Comms menu, select Who Active Go Online, as shown below:
This selection starts the Who application in RSLinx, which lets you use RSLinx to view modules in the selected ControlLogix system.
Publication 1756-6.5.14 - August 1998
4-2 Programming Terminal Operation Over DH+
3. To navigate through the control system, including over DH+, select the module and double-click on it.
For more information . . .
For a detailed instructions on using the Who applications, refer to the
RSLinx User Guide, publication 9399-WAB32LUG, or the RSLinx online help.
Connecting Your Programming
Terminal Over DH+ RSLogix 500
For applications connecting RLogix 500 to a SLC-5/04, you must:
1. Start the RSLogix 500 software.
2. From the Comms menu, select Who Active Go Online, as shown below:
For more information . . .
This selection starts the Who application in RSLinx, which lets you use RSLinx to view modules in the selected ControlLogix system.
3. To navigate through the control system, including over DH+, select the module and double-click on it.
For a detailed instructions on using the Who applications, refer to the
RSLinx User Guide, publication 9399-WAB32LUG, or the RSLinx online help.
Publication 1756-6.5.14 - August 1998
Connecting Your Programming
Terminal Over DH+ Using
RSLogix 5000
Programming Terminal Operation Over DH+ 4-3
For applications connecting RSLogix 5000 to a Logix5550, you must configure the appropriate communication driver for the network that links the workstation using RSLogix 5000 and the Logix5550.
The communication driver enables the controller to communicate over the network. You must configure communication drivers in
RSLinx software and then select the appropriate driver in the programming software.
To configure the available communication drivers for the Logix5550 controller through the programming software:
1. Start the RSLogix 5000 software.
2. From the Communications menu, select Configure, as shown below.
3. Select the Communications tab on the Workstation options screen and fill in the following information.
In this field:
Driver
Path
Recent
Enter:
This is a display-only field that describes the communications protocol of the selected driver.
Use the drop-down menu to select the driver:
• ControlNet (AB_KTC)
• DF1 (AB_DF1)
• DH+ (AB_KT)
• Ethernet (TCP)
This is the connection path to the controller you wish to communicate with from the communications card you are connected to. The path consists of a sequence of decimal numbers separated by commas.
The field displays up to three lines for a long path, and a scroll-bar appears if the entire field cannot be displayed.
This button navigates to the Recent Configurations dialog where you can choose from the recent configurations stored on the workstation.
Any driver configured through the programming software must first have been configured using RSLinx software.
Publication 1756-6.5.14 - August 1998
4-4 Programming Terminal Operation Over DH+
After configuring your communication driver, you must:
4. Select the Communications menu and select Go Online, as shown below:
For more information . . .
This selection starts the Who application in RSLinx, which lets you use RSLinx to view modules in the selected ControlLogix system.
5. To navigate through the control system, including over DH+, select the module and double-click on it.
For a detailed instructions on using the Who applications, refer to the
RSLinx User Guide, publication 9399-WAB32LUG, or the RSLinx online help.
Publication 1756-6.5.14 - August 1998
Defining Connection Paths
Programming Terminal Operation Over DH+ 4-5
You may have to configure a connection path when configuring controller to controller communication or when configuring communication from a workstation to a controller. The connection path starts with the controller or the communications card in the workstation.
The following steps construct a communication path:
1. Separate the number or address entered in each step with a comma. All numbers are in decimal by default. You can enter any number, other than an Ethernet IP address, in another base by using the IEC-1131 prefix (8# for octal, 16# for hexadecimal).
Ethernet IP addresses are always decimal numbers separated by periods.
2. To construct the path, you enter one or more path segments that lead to the controller. Each path segment takes you from one module to another module over the ControlBus backplane or over a DH+, ControlNet, or Ethernet networks.
You can only have 8 paths lead to the controller.
Each path segment contains two numbers: x,y
Where:
, y
This x
Is: number of the type of port you use to exit from the module you are at:
0 DH+ port from a KT card
1 backplane from any 1756 module
2 RS232 port from a 1756-L1 controller
2 ControlNet port from a KTC card or a 1756-CNB module
2 Ethernet port from a 1756-ENET module
2 DH+ port over channel A from a 1756-DHRIO module
3 DH+ port over channel B from a 1756-DHRIO module separates the first number and second number of the path segment address of the module you are going to
For Address means:
ControlBus backplane slot number (0-16 decimal)
DF1 network
ControlNet network station address (0-254) node number (1-99 decimal)
DH+ network
Ethernet network node number (0-77 octal)
IP address (four decimal numbers
separated by periods)
If you have multiple path segments, you must also separate each path segment with a comma (,).
Publication 1756-6.5.14 - August 1998
4-6 Programming Terminal Operation Over DH+
Connection path examples
The following examples are based on this system: programming terminal
ControlNet = port 2
DH+ = port 0 serial
DH+
Ethernet
ControlNet
Ethernet IP address = 21.21.21.21
local chassis
A B
ControlNet = node 49
Ethernet IP address = 34.34.34.34
DH+ = node 037
A B remote chassis
ControlNet = node 42 port 1 = backplane port 2 = ControlNet
Ethernet IP address = 127.127.127.12
port 1 = backplane port 2 = Ethernet
DH+ = node 24 port 1 = backplane port 2 = channel A = node 025 port 3 = channel B = node 026
41027
Publication 1756-6.5.14 - August 1998
Programming Terminal Operation Over DH+
Network: serial
ControlNet
Ethernet
Example:
Programming terminal to controller module in logical rack.
Use DF1
Upload logic from local controller.
(controller is directly connected to the programming terminal)
Programming terminal to controller module in remote rack.
Use DF1 (connected to controller in local rack)
Use ControlNet to bridge to remote chassis
Configure DF1 driver.
Leave connection path blank.
Description:
Configure the DF1 driver.
Enter connection path: 1,0,2,42,1,9
1 = backplane port of the Logix5550 controller in slot 6 of the local chassis
0 = slot number of the 1756-CNB module in the local chassis
2 = ControlNet port of the 1756-CNB module in slot 0 of the local chassis
42 = ControlNet node of the 1756-CNB module in slot 0 of the remote chassis
1 = backplane port of the 1756-CNB module in slot 0 of the remote chassis
9 = slot number of the controller in the remote chassis
Configure the ControlNet driver.
Programming terminal to controller module in remote chassis.
Use ControlNet throughout the system.
Enter connection path: 2, 49, 1, 0, 2, 42, 1, 9
2 = ControlNet port of the KTC communications card in the workstation
49 = ControlNet node of the 1756-CNB module in slot 7 of the local chassis
1 = backplane port of the 1756-CNB module in slot 7 of the local chassis
0 = slot number of the 1756-CNB module in the local chassis
2 = ControlNet port of the 1756-CNB module in slot 0 of the local chassis
42 = ControlNet node of the 1756-CNB module in slot 0 of the remote chassis
1 = backplane port of the 1756-CNB module in slot 0 of the remote chassis
Programming terminal to controller module in remote rack.
9 = slot number of the controller in the remote chassis
Configure the Ethernet driver.
Enter connection path: 1, 1, 2, 127.127.127.12, 1, 9
IMPORTANT: Connection path does not include path segment from Ethernet card in programming terminal to Ethernet module in local chassis because Ethernet driver is configured for the Ethernet module already in the local chassis
1 = backplane port of the 1756-ENET module in slot 8 of the local chassis
1 = slot number of the other 1756-ENET module in the local chassis
2 = Ethernet port of the 1756-ENET module in slot 1 of the local chassis
127.127.127.12 = IP address of the 1756-ENET module in the remote chassis
Bridge across Ethernet
1 = backplane port of the 1756-ENET module in slot 1 of the remote chassis
9 = slot number of the controller in the remote chassis
4-7
Publication 1756-6.5.14 - August 1998
4-8 Programming Terminal Operation Over DH+
Network:
DH+
ControlNet
Ethernet
DH+
Example:
Program the controller in slot 9 of the remote chassis.
Go from DH+ to the local chassis.
Bridge to the remote chassis over ControlNet.
Program the controller in slot 9 of the remote chassis.
Go from DH+ to the local chassis.
Bridge across DH+ to the remote controller.
Use several network connections across different network bridges:
• DF1 (connected to controller module in local rack)
• ControlNet to the remote chassis
• Ethernet back to the local chassis
• DH+ back to the remote chassis
Description:
Configure the DH+ driver.
Enter connection path: 0, 8#37, 1, 0, 2, 42, 1, 9
0 = DH+ port of the KT communications card in the workstation
8#37 = octal DH+ node of the 1756-DHRIO module in slot 9 of the local chassis
1 = backplane port of the 1756-DHRIO module in slot 9 of the local chassis
0 = slot number of the 1756-CNB module in the local chassis
2 = ControlNet port of the 1756-CNB module in slot 0 of the local chassis
42 = ControlNet node of the 1756-CNB module in slot 0 of the remote chassis
1 = backplane port of the 1756-CNB module in slot 0 of the remote chassis
9 = slot number of the controller in the remote chassis
Configure the DH+ driver.
Enter connection path: 0, 8#37, 1, 2, 3, 8#24, 1, 9
0 = DH+ port of the KT communications card in the workstation
8#37 = octal DH+ node of the 1756-DHRIO module in slot 9 of the local chassis
1 = backplane port of the 1756-DHRIO module in slot 9 of the local chassis
2 = slot number of the other 1756-DHRIO module in the local chassis
3 = Channel B of the 1756-DHRIO module in slot 2 of the local chassis, configured for DH+
8#24 = DH+ node of the 1756-DHRIO module in slot 2 of the remote chassis
1 = backplane port of the 1756-DHRIO module in slot 2 of the remote chassis
9 = slot number of the controller in the remote chassis
Configure the DF1 driver (to handle worst case performance)
Enter connection path: 1, 0, 2, 42, 1, 1, 2, 21.21.21.21, 1, 2, 2, 8#25, 1, 9
1 = backplane port of the Logix5550 controller in slot 6 of the local chassis
0 = slot number of the 1756-CNB module in the local chassis
2 = ControlNet port of the 1756-CNB module in slot 0 of the local chassis
42 = ControlNet node of the 1756-CNB module in slot 0 of the remote chassis
1 = backplane port of the 1756-CNB module in slot 0 of the remote chassis
1 = slot number of the 1756-ENET module in the remote chassis
2 = Ethernet port of the 1756-ENET module in slot 1 of the remote chassis
21.21.21.21 = IP address of the 1756-ENET module in slot 1 of the local chassis
1 = backplane port of the 1756-ENET module in slot 1 of the local chassis
2 = slot number of the 1756-DHRIO module in the local chassis
2 = Channel A of the 1756-DHRIO module in slot 2 of the local chassis, configured for DH+
8#25 = DH+ node of the 1756-DHRIO module in slot 2 of the remote chassis
1 = backplane port of the 1756DHRIO in slot 2 of the remote chassis
9 = slot number of the controller in the remote chassis
Publication 1756-6.5.14 - August 1998
Programming Terminal Operation Over DH+ 4-9
Chapter Summary and What’s Next
In this chapter, you learned about programming terminal operation over DH+.
Move on to Chapter 5 to see examples of PLC to PLC Messaging.
Publication 1756-6.5.14 - August 1998
What This Chapter Contains
Chapter
5
PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging
This chapter describes how to use DH+ messaging between PLC-5s and between SLC-5/04s. The following table describes what this chapter contains and its location:
For information about using:
DH+ Messaging Between PLC-5s
With One 1756-DHRIO Module
DH+ Messaging Between SLC-5/04s with Two 1756-DHRIO Modules with
One ControlLogix Chassis
DH+ Messaging Between PLC-5s with
Multiple ControlLogix Chassis
DH+ Messaging From PLC-5 to PLC-5C on ControlNet
Chapter Summary and What’s Next
See page:
This chapter contains four example applications using DH+ messaging between programmable controllers. Each example explains what steps must be taken to perform these operations.
Important: The examples use PLC-5s and SLC-5/04s to send DH+ messages. In each case, the use of these devices is strictly for example purposes and not an indication of restrictions on the 1756-DHRIO module. Examples using PLC-5s could, in fact, use SLC-5/04s and examples using SLC-5/04s could use PLC-5s.
Publication 1756-6.5.14 - August 1998
5-2 PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging
DH+ Messaging Between PLC-5s
With One 1756-DHRIO Module
This application sends a DH+ message from PLC-5 processor A through a 1756-DHRIO module to PLC-5 processor B. Remote DH+ messaging is required to send the message.
The following diagram illustrates the steps you follow to use such an application:
DHRIO module
ControlLogix chassis
1 Set Module
Switches
DH+ link
Link ID 1
Channel A node number: 010
Channel B node number: 020
DH+ link
Link ID 2
2 Set-Up
Routing Table
PLC-5/25 processor A node number: 015
PLC-5 processor B node number: 025
41363
3 Configure Msg
Instructions
Publication 1756-6.5.14 - August 1998
1 Set Module
Switches
PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging
Set the Module Switches
In this application, both Channel A and Channel B on the
1756-DHRIO module must be set for DH+. Set the switches as shown below.
Channel A Channel B
1
0
7
2
6
3
5
4
1
0
7
2
6
3
5
4
Both channels are set for DH+.
5-3
2 Set -Up
Routing Table
Channel B switches Channel A switches
6 6 6 6
4
5
3 1
0
7
4
5
3
7
4
5
3
7
4
5
3
7
2 2
0
1
2
0
1
2
0
1
Channel A shows a node address at 10 and channel B at 20.
41414
Set-Up a Routing Table for the 1756-DHRIO Module
1. Use the ControlLogix Gateway Configuration Tool (1756-
GTWY) to set-up a routing table for the 1756-DHRIO module.
Your table should look like this:
2. Apply the routing table to your application.
Important: Controller slot values for channels configured for DH+ should be applied or restored to default value, using the appropriate software tabs.
In this example, controller values do not matter, but failure to enter a value, specific or default, will generate a configuration fault for that channel.
For more information on how to set-up a routing table using the
ControlLogix Gateway Configuration Tool (1756-GTWY), see publication 1756-6.5.7.
Publication 1756-6.5.14 - August 1998
5-4
3
PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging
Configure Message Instructions
Configure Msg
Instructions
You must use RSLogix5 to configure the PLC-5 message instructions.
Your message instructions should look like this:
Ladder rung
See PLC-5 Instruction set reference, publication 1785-6.1
Setup screen
Important: When choosing a Remote Link Type in RSLogix 5, you can choose either Data Highway or Data Highway II.
The User field only appears in Data Highway II.
User is not required for your application and typically is set to 0.
For more information on how to configure message instructions using the RSLogix5 software, see the online help for that software.
Publication 1756-6.5.14 - August 1998
DH+ Messaging Between
SLC-5/04s With Two 1756-DHRIO
Modules With One ControlLogix
Chassis
PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging 5-5
This application sends a DH+ message from SLC-504 processor A through two 1756-DHRIO modules in the same chassis to SLC-5/04 processor B. Remote DH+ messaging is required to send the message.
The following diagram illustrates the steps you follow to use such an application:
DHRIO module DHRIO module
1
Set Module
Switches
ControlLogix chassis
Channel B node number: 030
DH+ link
Link ID 1
Channel B node number: 020
2
Set -Up 1st
Routing Table
DH+ link
Link ID 2
3
Set -Up 2nd
Routing Table
SLC-504 processor A node number: 015
SLC-504 processor B node number: 025
19765
4
Configure Msg
Instructions
Publication 1756-6.5.14 - August 1998
5-6
1
PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging
Set the Module Switches
Set Module
Switches
In this application, Channel B on both 1756-DHRIO modules must be set for DH+.
Set the switches as shown below./
DHRIO module - Slot 0
Both channels are set for DH+.
Channel A Channel B
0
1
7
2
6
3
5
4 0
1
7
2
6
3
5
4
Channel A
DHRIO module - Slot 2
Both channels are set for DH+.
0
1
7
2
6
3
5
4
Channel B
0
1
7
2
6
3
5
4
Channel B switches Channel A switches
6
5 7 5
6
7 5
6
7 5
6
7
4 0 4 0 4 0 4 0
3 1 3 1 3 1 3 1
2 2 2 2
Channel A shows a node address at 10 and channel B at 20.
Channel B switches Channel A switches
6 6 6 6
5 7 5 7 5 7 5 7
4 0 4 0 4 0 4 0
3 1 3 1 3 1 3 1
2 2 2 2
Channel A shows a node address at 40 and channel B at 30.
Publication 1756-6.5.14 - August 1998
2 Set -Up 1st
Routing Table
PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging
Set-Up a Routing Table for the First 1756-DHRIO Module
1. Use the ControlLogix Gateway Configuration Tool
(1756-GTWY) to set-up a routing table for the first
1756-DHRIO module. Your table should look like this:
5-7
3 Set -Up 2nd
Routing Table
2. Apply the routing table to your application.
Set-Up a Routing Table for the Second 1756-DHRIO Module
3. Use the ControlLogix Gateway Configuration Tool
(1756-GTWY) to set-up a routing table for the second
1756-DHRIO module. Your table should look like this:
TIP
4. Apply the routing table to your application.
Important: Controller slot values for channels configured for DH+ should be applied or restored to default value, using the appropriate software tabs.
In this example, controller values do not matter, but failure to enter a value, specific or default, will generate a configuration fault for that channel.
Because both 1756-DHRIO modules are in the same chassis, you only need to set-up one of the two routing tables and apply it to both modules.
For more information on how to set-up a routing table using the
ControlLogix Gateway Configuration Tool (1756-GTWY), see publication 1756-6.5.7.
Publication 1756-6.5.14 - August 1998
5-8
4
PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging
Configure Message Instructions
Configure Msg
Instructions
You must use RSLogix500 to configure the SLC-504 message instructions. Your message instructions should look like this:
Ladder rung
See SLC-500 Instruction Set
Reference, publication 1747-6.15
Setup screen
Important: RSLogix 500 displays nodes and link IDs in decimal.
Also, in this application, a remote bridge address is not required.
For more information on how to configure message instructions using the RSLogix500 software, see the online help for that software.
Publication 1756-6.5.14 - August 1998
DH+ Messaging Between PLC-5s
With Multiple ControlLogix Chassis
PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging 5-9
This application sends a DH+ message from PLC-5 processor A through 1756-DHRIO modules in separate chassis over ControlNet to
PLC-5 processor B. Remote DH+ messaging is required to send the message.
The following diagram illustrates the steps you follow to use such an application:
ControlLogix system #1
DHRIO module
ControlLogix system #2
CNB module node number: 22
DHRIO module CNB module node number:23
DH+ link
Link ID 1
Channel A node number: 010
Channel B node number: 030
ControlNet link
This can be Ethernet,
ControlNet or DH+
DH+ link
Link ID 3
PLC-5/25 processor A node number: 015
1
Set Module
Switches
2
Set -Up 1st
Routing Table
3
Set -Up 2nd
Routing Table
4
PLC-5/25 processor B node number: 035
19769
Configure Msg
Instructions
Publication 1756-6.5.14 - August 1998
5-10
1
PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging
Set the Module Switches
Set Module
Switches
In this application, you must set switches on the 1756-DHRIO modules for DH+ and the switches on the 1756-CNB modules to the correct node addresses.
Important: The switches on the 1756-CNB modules must match the information in the 1756-DHRIO routing tables.
Set the channels as shown.
DHRIO module -Chassis 1
Slot 0
Both channels are set for DH+.
Channel A Channel B
1
0
7
2
6
3
5
4
1
0
7
2
6
3
5
4
DHRIO module -Chassis 2
Slot 0
Both channels are set for DH+.
Channel A Channel B
1
0
7
2
6
3
5
4
1
0
7
2
6
3
5
4
Channel B switches Channel A switches
6
5 7 5
6
7 5
6
7 5
6
7
4 0 4 0 4 0 4 0
3 1 3 1 3 1 3 1
2 2 2 2
Channel A shows a node address at 010 and channel B at 020.
CNB module - Chassis 1
Slot 3
Channel B switches Channel A switches
6 6 6 6
5 7 5 7 5 7 5 7
4 0 4 0 4 0 4 0
3 1 3 1 3 1 3 1
2 2 2 2
Channel A shows a node address at 040 and channel B at 030.
CNB module - Chassis 2
Slot 3
The module’s network address is 22.
Publication 1756-6.5.14 - August 1998
The module’s network address is 23.
41434
2 Set -Up 1st
Routing Table
PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging
Set-Up a Routing Table for the First 1756-DHRIO Module
1. Use the ControlLogix Gateway Configuration Tool
(1756-GTWY) to set-up a routing table for the first
1756-DHRIO module. Your table should look like this:
5-11
3 Set -Up 2nd
Routing Table
2. Apply the routing table to your application.
Set-Up a Routing Table for the Second 1756-DHRIO Module
3. Use the ControlLogix Gateway Configuration Tool
(1756-GTWY) to set-up a routing table for the first
1756-DHRIO module. Your table should look like this:
4. Apply the routing table to your application.
Important: Controller slot values for channels configured for DH+ should be applied or restored to default value, using the appropriate software tabs.
In this example, controller values do not matter, but failure to enter a value, specific or default, will generate a configuration fault for that channel.
For more information on how to set-up a routing table using the
ControlLogix Gateway Configuration Tool (1756-GTWY), see publication 1756-6.5.7.
Publication 1756-6.5.14 - August 1998
5-12
4
PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging
Configure Message Instructions
Configure Msg
Instructions
You must use RSLogix5 to configure the PLC-5 message instructions.
Your message instructions should look like this:
Ladder rung
See PLC-5 Instruction set reference, publication 1785-6.1
Setup screen
Important: When choosing a Remote Link Type in RSLogix 5, you can choose either Data Highway or Data Highway II.
The User field only appears in Data Highway II.
User is not required for your application and typically is set to 0.
For more information on how to configure message instructions using the RSLogix5 software, see the online help for that software.
Publication 1756-6.5.14 - August 1998
DH+ Messaging From PLC-5 to
PLC-5/C on ControlNet
PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging 5-13
This application sends a DH+ message from PLC-5 processor A through 1756-DHRIO and 1756-CNB modules to PLC-5C processor B on ControlNet. Remote DH+ messaging is required to send the message.
The following diagram illustrates the steps you follow to use such an application:
DHRIO module CNB module node number:22
1 Set Module
Switches
Channel A node number: 010
DH+ link
Link ID 1
ControlNet link
Link ID 2
2 Set-Up
Routing Table
PLC-5/25 processor A node number: 015
PLC-5C processor B node number: 45
41288
3 Configure Msg
Instructions
Publication 1756-6.5.14 - August 1998
5-14
1
PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging
Set the Module Switches
Set Module
Switches
In this application, you must set switches on the 1756-DHRIO module for DH+ and the switches on the 1756-CNB module to the correct node addresses
Set the channels as shown.
Channel A
1
0
7
2
6
3
5
4
Channel B
1
0
7
2
6
3
5
4
Both channels are set for DH+.
Channel B switches Channel A switches
6 6 6 6
5 7 5 7 5 7 5 7
4 0 4 0 4 0 4 0
3 1 3 1 3 1 3 1
2 2 2 2
Channel A shows a node address at 10 and channel B at 20.
CNB module - Chassis 1
Slot 3
The module’s network address is 22.
Publication 1756-6.5.14 - August 1998
2 Set -Up
Routing Table
PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging
Set-Up a Routing Table for the 1756-DHRIO Module
1. Use the ControlLogix Gateway Configuration Tool
(1756-GTWY) to set-up a routing table for the
1756-DHRIO module. Your table should look like this:
5-15
For more information . . .
2. Apply the routing table to your application.
Important: Controller slot values for channels configured for DH+ should be applied or restored to default value, using the appropriate software tabs.
In this example, controller values do not matter, but failure to enter a value, specific or default, will generate a configuration fault for that channel.
For more information on how to set-up a routing table using the
ControlLogix Gateway Configuration Tool (1756-GTWY), see publication 1756-6.5.7.
Publication 1756-6.5.14 - August 1998
5-16
3
PLC-5 or SLC-5/04 to PLC-5 or SLC-5/04 Messaging
Configure Message Instructions
Configure Msg
Instructions
You must use RSLogix5 to configure the PLC-5 message instructions.
Your message instructions should look like this:
Ladder rung
See PLC-5 Instruction set reference, publication 1785-6.1
Setup screen
Chapter Summary and
What’s Next
For more information on how to configure message instructions using the RSLogix5 software, see the online help for that software.
Important: When choosing a Remote Link Type in RSLogix 5, you can choose either Data Highway or Data Highway II.
The User field only appears in Data Highway II.
User is not required for your application and typically is set to 0.
In this chapter, you learned about using messaging.
Move to Chapter 6 to learn about PLC to Logix5550 messaging.
Publication 1756-6.5.14 - August 1998
What This Chapter Contains
Chapter
6
PLC-5 or SLC-5/04 to Logix5550
Messaging
This chapter describes how to use DH+ messaging between PLC-5s or SLC-5/04s and a Logix5550. The following table describes what this chapter contains and its location:
For information about using:
DH+ Messaging From a PLC-5 to One
Logix5550 with One ControlLogix Chassis
DH+ Messaging From a PLC-5 to Multiple
Logix5550s with One ControlLogix Chassis
DH+ Messaging From an SLC-5/04 to a
Logix5550 with Multiple ControlLogix Chassis
Chapter Summary and What’s Next
See page:
This chapter contains three example applications. Each example explains what steps must be taken to perform these operations.
Important: The examples use PLC-5s and SLC-5/04s to send DH+ messages. In each case, the use of these devices is strictly for example purposes and not an indication of restrictions on the 1756-DHRIO module.
Examples using PLC-5s could, in fact, use SLC-5/04s and examples using SLC-5/04s could use PLC-5s.
Publication 1756-6.5.14 - August 1998
6-2 PLC-5 or SLC-5/04 to Logix5550 Messaging
DH+ Messaging From a PLC-5 to One Logix5550 With One
ControlLogix Chassis
This application sends a DH+ message from PLC-5/60 processor A through a 1756-DHRIO module to Logix5550 B. Local DH+ messaging may be used to send the message.
Important: Local DH+ messaging can only send DH+ messages to one
Logix5550 per DH+ channel. See the next application if you want to send DH+ messages to multiple Logix5550s in the chassis.
The following diagram illustrates the steps you must use in this application:
Logix5550 B slot number:0
DH+ module slot number:3
DH+ link
Link ID 1
Channel A node number: 010
PLC-5/60 processor A node number:005
ControlLogix chassis
41283
1 Set Module
Switches
2 Set-Up
Controller Slot
Important: For this application, the 1756-DHRIO module only needs a controller slot programmed if the
Logix5550 is not located in the default slot (0) of the ControlLogix chassis.
3 Configure Msg
Instructions
Publication 1756-6.5.14 - August 1998
1 Set Module
Switches
PLC-5 or SLC-5/04 to Logix5550 Messaging
Set the Module Switches
6-3
In this application, channel A on the 1756-DHRIO module must be set for DH+.
Set the channels as shown.
Channel A Channel B
1
0
7
2
6
3
5
4
1
0
7
2
6
3
5
4
Both channels are set for DH+.
Channel B switches Channel A switches
6 6 6 6
4
5
3 1
0
7
4
5
3
7
4
5
3
7
4
5
3
7
2 2
0
1
2
0
1
2
0
1
Channel A shows a node address at 10.
41414
Publication 1756-6.5.14 - August 1998
6-4
2
PLC-5 or SLC-5/04 to Logix5550 Messaging
Set-Up a Controller Slot for the 1756-DHRIO Module
Set -Up a
Controller Slot
If the Logix5550 is located in slot 0 of the ControlLogix chassis, you do not need to modify the controller slot.
If the Logix5550 is not located in the default slot (slot 0) of the
ControlLogix chassis, you must use the ControlLogix Gateway
Configuration Tool (1756-GTWY) to set-up a controller slot for the
1756-DHRIO module.
1. In this example, you must enter the controller slot number on the channel A configuration page because the Logix5550 is not located in the default configuration slot.
2. Apply the controller slot number to your application.
Important: Controller slot values for the other channel, if it is configured for DH+, should be applied or restored to default value, using the appropriate software tabs.
In this example, controller values applied to the channel not used for DH+ messaging do not matter, but failure to enter a value will generate a configuration fault for that channel.
A routing table is not required for local DH+ messaging. However, if a routing table is programmed, verify it is programmed correctly and applied or set to default. Failure to do so may generate a configuration fault.
For more information . . .
For more information on how to set-up a controller slot using the
ControlLogix Gateway Configuration Tool (1756-GTWY), see publication 1756-6.5.7.
Publication 1756-6.5.14 - August 1998
3 Configure Msg
Instructions
See PLC-5 Instruction Set
Reference, publication 1785-6.1
PLC-5 or SLC-5/04 to Logix5550 Messaging
Configure Message Instructions
6-5
You must use RSLogix5 to configure the PLC-5 message instructions.
Your message instructions should look like this:
Ladder rung
Setup screen
For more information on how to configure message instructions using the
RSLogix5 software, see the online help for that software.
Publication 1756-6.5.14 - August 1998
6-6 PLC-5 or SLC-5/04 to Logix5550 Messaging
DH+ Messaging From a PLC-5 to Multiple Logix5550s With
One ControlLogix Chassis
This application sends a DH+ message from PLC-5/60 processor A through a 1756-DHRIO module to more than one Logix5550 in the chassis.
Important: In this example, we use both local and remote DH+ messaging to send DH+ messages. Local DH+ messaging is used to send a message to Logix5550 A. (This processor must be configured as the controller slot, see Step 2.)
Remote DH+ messaging is used to send a message to
Logix5550 B. Separate message instructions must be configured in RSLogix 5 for each Logix5550.
The following diagram illustrates the steps you follow to use such an application:
Logix5550 A slot number:1
Logix5550 B slot number:2
DH+ module
Channel A node number: 010
DH+ link
Link ID 1
41459
1 Set Module
Switches
PLC-5/60 processor A node number:005
2 Set-Up
Controller Slot
ControlLogix chassis
Link ID 2
3 Set-Up
Routing Table
4 Configure Local
Msg Instructions
5 Configure Remote
Msg Instructions
Publication 1756-6.5.14 - August 1998
1 Set Module
Switches
PLC-5 or SLC-5/04 to Logix5550 Messaging
Set the Module Switches
6-7
In this application, channel A on the 1756-DHRIO module must be set for DH+.
Set the channels as shown.
Channel A Channel B
1
0
7
2
6
3
5
4
1
0
7
2
6
3
5
4
Both channels are set for DH+.
Channel B switches Channel A switches
6 6 6 6
4
5
3 1
0
7
4
5
3
7
4
5
3
7
4
5
3
7
2 2
0
1
2
0
1
2
0
1
Channel A shows a node address at 10.
41414
Publication 1756-6.5.14 - August 1998
6-8
2
PLC-5 or SLC-5/04 to Logix5550 Messaging
Set-Up a Controller Slot for the 1756-DHRIO Module
Set -Up a
Controller Slot
If the Logix5550 is located in slot 0 of the ControlLogix chassis, you do not need to modify the controller slot.
If the Logix5550 is not located in the default slot (slot 0) of the
ControlLogix chassis, you must use the ControlLogix Gateway
Configuration Tool (1756-GTWY) to set-up a controller slot for the
1756-DHRIO module.
1. In this example, you must enter the controller slot number on the channel A configuration page because the Logix5550 is not located in the default configuration slot.
2. Apply the controller slot number to your application.
Important: Controller slot values for the other channel, if it is configured for DH+, should be applied or restored to default value, using the appropriate software tabs.
In this example, controller values applied to the channel not used for DH+ messaging do not matter, but failure to enter a value will generate a configuration fault for that channel.
For more information . . .
For more information on how to set-up a controller slot using the
ControlLogix Gateway Configuration Tool (1756-GTWY), see publication 1756-6.5.7.
Publication 1756-6.5.14 - August 1998
3 Set -Up
Routing Table
PLC-5 or SLC-5/04 to Logix5550 Messaging
Set-Up a Routing Table for the 1756-DHRIO Module
6-9
1. Use the ControlLogix Gateway Configuration Tool (1756-GTWY) to set-up a routing table for the 1756-DHRIO module. Your table should look like this:
For more information . . .
2. Apply the routing table to your application.
For more information on how to set-up a routing table using the
ControlLogix Gateway Configuration Tool (1756-GTWY), see publication 1756-6.5.7.
Publication 1756-6.5.14 - August 1998
6-10
4
PLC-5 or SLC-5/04 to Logix5550 Messaging
Configure Local Message Instructions
Configure Local
Msg Instructions
You must use RSLogix5 to configure the PLC-5 message instructions.
First configure your local message instructions for the message being sent to Logix5550A in the controller slot.
See PLC-5 Instruction Set
Reference, publication 1785-6.1
Important: Because this message instruction is sending a message to a
Logix5550 in the configured controller slot, you can use a local message instruction.
Your message instructions should look like this:
Ladder rung
Setup screen
For more information on how to configure message instructions using the
RSLogix5 software, see the online help for that software.
Publication 1756-6.5.14 - August 1998
5 Configure Remote
Msg Instructions
See PLC-5 Instruction Set
Reference, publication 1785-6.1
PLC-5 or SLC-5/04 to Logix5550 Messaging
Configure Remote Message Instructions
6-11
You must use RSLogix5 to configure the PLC-5 message instructions. In this step, configure your remote message instructions for the message being sent to Logix5550 B.
Important: Because this message instruction is sending a message to a
Logix5550 not located in the configured controller slot, you must use a remote message instruction.
Your message instructions should look like this:
Ladder rung
Setup screen
Important: When choosing a Remote Link Type in RSLogix 5, you can choose either Data Highway or Data Highway II. The User field only appears in Data Highway II.
User is not required for your application and typically is set to 0.
For more information on how to configure message instructions using the
RSLogix5 software, see the online help for that software.
Publication 1756-6.5.14 - August 1998
6-12 PLC-5 or SLC-5/04 to Logix5550 Messaging
DH+ Messaging From a
SLC-5/04 to a Logix5550 With
Multiple ControlLogix Chassis
This application sends a DH+ message from SLC-5/04 processor A through a 1756-DHRIO module in ControlLogix system #1 to a
1756-DHRIO module in ControlLogix system #2 to Logix5550 B.
Remote DH+ messaging is required to send the message.
The following diagram illustrates the steps you follow to use such an application:
ControlLogix system #1
DH+ module CNB module node number:22
Logix5550 B slot number:0
ControlLogix system #2
CNB module node number:23
DH+ link
Link ID 1
Channel A node number: 010
System #2
Backplane link ID 3
ControlNet link
This can be Ethernet,
ControlNet or DH+
SLC-504 processor A node number:050
1
Set Module
Switches
2
Set -Up
Routing Table
3
Configure Msg
Instructions
41286
Publication 1756-6.5.14 - August 1998
1 Set Module
Switches
See ControlLogix ControlNet
Bridge Installation Instructions, publication 1756-5.32
PLC-5 or SLC-5/04 to Logix5550 Messaging
Set the Module Switches
6-13
In this application, you must set switches on the 1756-DHRIO modules for DH+ and the switches on the 1756-CNB modules to the correct network addresses.
Important: The switches on the 1756-CNB modules must match the information in the 1756-DHRIO routing tables.
Set the channels as shown.
Both channels are set for DH+.
Channel A Channel B
1
0
7
2
6
3
5
4
1
0
7
2
6
3
5
4
DHRIO module -Chassis 1
Slot 0
Channel B switches Channel A switches
6
5 7 5
6
7 5
6
7 5
6
7
4 0 4 0 4 0 4 0
3 1 3 1 3 1 3 1
2 2 2 2
Channel A shows a node address at 10 and channel B at 20.
CNB module - Chassis 1
Slot 3
The module’s network address is 22.
CNB module - Chassis 2
Slot 3
The module’s network address is 23.
41417
Publication 1756-6.5.14 - August 1998
6-14
2
PLC-5 or SLC-5/04 to Logix5550 Messaging
Set-Up a Routing Table for the 1756-DHRIO Module
Set -Up
Routing Table
1. Use the ControlLogix Gateway Configuration Tool (1756-GTWY) to set-up a routing table for the 1756-DHRIO module. The table should look like this:
2. Apply the routing table to your application.
Important: Controller slot values for channels configured for DH+ should be applied or restored to default value, using the appropriate software tabs.
In this example, controller values do not matter, but failure to enter a value, specific or default, will generate a configuration fault for that channel.
For more information . . .
For more information on how to set-up a routing table using the
ControlLogix Gateway Configuration Tool (1756-GTWY), see publication 1756-6.5.7.
Publication 1756-6.5.14 - August 1998
3 Configure Msg
Instructions
See SLC-500 Instruction Set
Reference, publication 1747-6.15
PLC-5 or SLC-5/04 to Logix5550 Messaging
Configure Message Instructions
You must use RSLogix500 to configure the SLC-500 message instructions.Your message instructions should look like this:
Ladder rung
6-15
Setup screen
For more information on how to configure message instructions using the
RSLogix500 software, see the online help for that software.
Important: RSLogix500 displays nodes and link IDs in decimal. Also, in this application, a remote bridge address is not required.
Publication 1756-6.5.14 - August 1998
6-16 PLC-5 or SLC-5/04 to Logix5550 Messaging
Chapter Summary and
What’s Next
In this chapter, you learned about PLC-5 or SLC5/04 to Logix5550 messaging.
Move on to Chapter 7 to learn about Logix5550 to PLC-5 or SLC-5/04
messaging.
Publication 1756-6.5.14 - August 1998
What This Chapter Contains
Chapter
7
Logix5550 to PLC-5 or SLC-5/04
Messaging
This chapter describes how to use DH+ messaging between a
Logix5550 and PLC-5s or SLC-5/04s. The following table describes what this chapter contains and its location.
For information about using:
DH+ Messaging From a Logix5550 to a PLC-5
With One ControlLogix Chassis
DH+ Messaging From a Logix5550 to a PLC-5
With Multiple ControlLogix Chassis Over DH+
DH+ Messaging From a Logix5550 to a SLC-5/
04 With Multiple ControlLogix Chassis Over
ControlNet and DH+
Chapter Summary and What’s Next
See page:
This chapter contains three example applications. Each example explains what steps must be taken to perform these operations.
Important: The examples use PLC-5s and SLC-5/04s to send DH+ messages. In each case, the use of these devices is strictly for example purposes and not an indication of restrictions on the 1756-DHRIO module.
Examples using PLC-5s could, in fact, use SLC-504s and examples using SLC-5/04s could use PLC-5s.
Publication 1756-6.5.14 - August 1998
7-2 Logix5550 to PLC-5 or SLC-5/04 Messaging
Local DH+ Messaging From a
Logix5550 to a PLC-5 With One
ControlLogix Chassis
This application sends a DH+ message from a Logix5550 A through a
1756-DHRIO module to a PLC-5 processor B on a DH+ link. Local DH+ messaging may be used to send the message. In this case, local DH+ messaging is used.
The following diagram illustrates the steps you follow to use such an application:
ControlLogix chassis
Logix5550 A slot number:0
DHRO module
DH+ link
Channel A node number: 010
1 Set Module
Switches
PLC-5/60 processor B node number:015
2 Configure Msg
Instructions
41284
Important: When you are using local DH+ messaging between a
Logix5550 and a PLC processor, you do not need a routing table. (The default setting on the module out of the box is to have no routing table set-up.)
A routing table is not required for local DH+ messaging.
However, if a routing table is programmed, verify it is programmed correctly or a configuration fault may occur.
Also, controller slot values for channels configured for DH+ should be applied or restored to default value, using the appropriate software tabs. Failure to enter the correct value will generate a configuration fault for that channel.
For more information . . .
For more information on how to clear a routing table using the
ControlLogix Gateway Configuration Tool (1756-GTWY), see publication 1756-6.5.7.
Publication 1756-6.5.14 - August 1998
1 Set Module
Switches
Logix5550 to PLC-5 or SLC-5/04 Messaging
Set the Module Switches
In this application, channel A on the 1756-DHRIO module must be set for DH+.
Set the channels as shown.
7-3
Channel A Channel B
1
0
7
2
6
3
5
4
1
0
7
2
6
3
5
4
Both channels are set for DH+.
Channel B switches Channel A switches
6 6 6 6
4
5
3 1
0
7
4
5
3
7
4
5
3
7
4
5
3
7
2 2
0
1
2
0
1
2
0
1
Channel A shows a node address at 10.
41414
Publication 1756-6.5.14 - August 1998
7-4
2
Logix5550 to PLC-5 or SLC-5/04 Messaging
Configure Message Instructions
Configure Msg
Instructions
You must use RSLogix5000 to configure the Logix5550 message instructions.Your message instructions should look like this:
Ladder rung
See Logix5550 Instruction Set
Reference, publication 1756-6.4.1
Configuration page
Communication page
Publication 1756-6.5.14 - August 1998
Important: Setting the destination link = 0 causes the 1756-DHRIO module to send the message as a local DH+ message. Also, remember that there are limits to local DH+ messaging. For
more information on local DH+ messaging, see chapter 3.
When using DH+ messaging from a Logix5550, the path is the connection path from the Logix5550 to the first 1756-DHRIO module.
For more information on connection paths, see chapter 4.
For more information on how to configure message instructions using the
RSLogix5000 software, see the online help for that software.
DH+ Messaging From a
Logix5550 to a PLC-5 With
Multiple ControlLogix Chassis
Over DH+
Logix5550 A slot number:0
Logix5550 to PLC-5 or SLC-5/04 Messaging 7-5
This application sends a DH+ message from a Logix5550 A in one
ControlLogix chassis through 1756-DHRIO modules to a PLC-5 processor B on a DH+ link in another ControlLogix chassis. Remote DH+ messaging is required to send the message in this application.
The following diagram illustrates the steps you follow to use such an application:
ControlLogix system #1
Link ID 1
DHRIO module slot number:3
ControlLogix system #2
Link ID 2
DHRIO module slot number:0
Channel A node number: 010
DH+ link
Link ID 3
Channel A node number: 040
Channel B node number: 030
DH+ link
Link ID 4
PLC-5/25 processor B node number:045
41418
1 Set Module
Switches
2 Set-Up 1st
Routing Table
3 Set-Up 2nd
Routing Table
4
Configure Msg
Instructions
Publication 1756-6.5.14 - August 1998
7-6
1
Logix5550 to PLC-5 or SLC-5/04 Messaging
Set the Module Switches
Set Module
Switches
In this application, Channel A on the first 1756-DHRIO module and
Channel B on both 1756-DHRIO modules must be set for DH+.
Set the switches as shown below.
DHRIO module
System #1
Slot 3
Channel A Channel B
1
0
7
2
6
3
5
4
1
0
7
2
6
3
5
4
DHRIO module
System #2
Slot 2
Channel A Channel B
1
0
7
2
6
3
5
4
1
0
7
2
6
3
5
4
Both channels are set for DH+.
Both channels are set for DH+.
Channel B switches Channel A switches
4
5
3
2
6
1
0
7
4
3
5
2
6
1
0
7
4
5
3
2
6
1
0
7
4
5
3
2
6
1
0
7
Channel A shows a node address at 10 and channel B at 20.
Channel B switches Channel A switches
6 6 6 6
4
3
5
2
1
0
7
4
5
3
2
0
1
7
4
3
5
2
1
0
7
4
3
5
2
1
0
7
Channel A shows a node address at 40 and channel B at 30.
41429
Publication 1756-6.5.14 - August 1998
2 Set -Up 1st
Routing Table
Logix5550 to PLC-5 or SLC-5/04 Messaging
Set-Up a Routing Table for the First 1756-DHRIO Module
7-7
1. Use the ControlLogix Gateway Configuration Tool (1756-GTWY) to set-up a routing table for the 1756-DHRIO module in ControlLogix system #1. Your table should look like this:
3 Set -Up 2nd
Routing Table
2. Apply the routing table to your application.
Set-Up a Routing Table for the Second 1756-DHRIO Module
3. Use the ControlLogix Gateway Configuration Tool (1756-GTWY) to set-up a routing table for the 1756-DHRIO module in ControlLogix system #2. Your table should look like this:
4. Apply the routing table to your application.
Important: Controller slot values for channels configured for DH+ should be applied or restored to default value, using the appropriate software tabs.
In this example, controller values do not matter, but failure to enter a value, specific or default, will generate a configuration fault for that channel.
For more information . . .
For more information on how to set-up a routing table using the
ControlLogix Gateway Configuration Tool (1756-GTWY), see publication 1756-6.5.7.
Publication 1756-6.5.14 - August 1998
7-8
4
Logix5550 to PLC-5 or SLC-5/04 Messaging
Configure Message Instructions
Configure Msg
Instructions
See Logix5550 Instruction Set
Reference, publication 1756-6.4.1
You must use RSLogix5000 to configure the Logix5550 message instructions.You must use RSLogix5000 to configure the Logix5550 message instructions.Your message instructions should look like this:
Ladder rung
Configuration page
Communication page
Publication 1756-6.5.14 - August 1998
When using DH+ messaging from a Logix5550, the path is the connection path from the Logix5550 to the first 1756-DHRIO module.
For more information on connection paths, see chapter 4.
For more information on how to configure message instructions using the
RSLogix5000 software, see the online help for that software.
DH+ Messaging From a
Logix5550 to a SLC-5/04 Over
ControlNet and DH+ With
Multiple ControlLogix Chassis
Logix5550 A slot number:0
ControlLogix system #1
Link ID 1
CNB module node number:22 slot number:3
Logix5550 to PLC-5 or SLC-5/04 Messaging 7-9
This application sends a DH+ message from Logix5550 A to SLC-5/04 processor B over ControlNet and DH+. Remote DH+ messaging is used to send the message in this application.
The following diagram illustrates the steps you follow to use such an application:
ControlLogix system #2
DHRIO module slot number:0
CNB module node number:23 slot number:3
ControlNet link
Channel B node number: 020
1 Set Module
Switches
2 Set-Up
Routing Table
DH+ link
Link ID 4
SLC-500 processor B node number:025
41287
3 Configure Msg
Instructions
Publication 1756-6.5.14 - August 1998
7-10
1
Logix5550 to PLC-5 or SLC-5/04 Messaging
Set the Module Switches
Set Module
Switches
In this application, you must set switches on the 1756-DHRIO modules for DH+ and the switches on the 1756-CNB modules to the correct network addresses.
See ControlLogix ControlNet
Bridge Installation Instructions, publication 1756-5.32
Important: The switches on the 1756-CNB modules must match the information in the 1756-DHRIO routing tables.
Set the channels as shown.
Both channels are set for DH+.
Channel A Channel B
1
0
7
2
6
3
5
4
1
0
7
2
6
3
5
4
DHRIO module -Chassis 2
Slot 0
Channel B switches Channel A switches
6
5 7 5
6
7 5
6
7 5
6
7
4 0 4 0 4 0 4 0
3 1 3 1 3 1 3 1
2 2 2 2
Channel A shows a node address at 10 and channel B at 20.
CNB module - Chassis 1
Slot 3
The module’s network address is 22.
CNB module - Chassis 2
Slot 3
The module’s network address is 23.
41417
Publication 1756-6.5.14 - August 1998
2 Set -Up
Routing Table
Logix5550 to PLC-5 or SLC-5/04 Messaging
Set-Up a Routing Table for the 1756-DHRIO Module
7-11
1. Use the ControlLogix Gateway Configuration Tool (1756-GTWY) to set-up a routing table for the 1756-DHRIO module in ControlLogix system #2. Your table should look like this:
2. Apply the routing table to your application.
Important: Controller slot values for channels configured for DH+ should be applied or restored to default value, using the appropriate software tabs.
In this example, controller values do not matter, but failure to enter a value, specific or default, will generate a configuration fault for that channel.
For more information . . .
For more information on how to set-up a routing table using the
ControlLogix Gateway Configuration Tool (1756-GTWY), see publication 1756-6.5.7.
Publication 1756-6.5.14 - August 1998
7-12
3
Logix5550 to PLC-5 or SLC-5/04 Messaging
Configure Message Instructions
Configure Msg
Instructions
You must use RSLogix5000 to configure the Logix5550 message instructions.
Ladder rung
See Logix5550 Instruction Set
Reference, publication 1756-6.4.1
Configuration page
Communication page
Publication 1756-6.5.14 - August 1998
When using DH+ messaging from a Logix5550, the path is the connection path from the Logix5550 to the first 1756-DHRIO module.
For more information on connection paths, see chapter 4.
For more information on how to configure message instructions using the
RSLogix5000 software, see the online help for that software.
Chapter Summary and
What’s Next
Logix5550 to PLC-5 or SLC-5/04 Messaging
In this chapter, you learned about Logix5550 to PLC-5 or SLC-5/04 messaging.
7-13
Move on to Chapter 8 to learn about Logix5550 to Logix5550 messaging.
Publication 1756-6.5.14 - August 1998
What This Chapter Contains
Chapter
8
Logix5550 to Logix5550
Messaging
This chapter describes how to use Control and Information
Protocol (CIP) messaging between Logix5550s with the
1756-DHRIO module. The following table describes what this chapter contains and its location.
For information about using:
CIP Messaging Between a Logix5550 and a
Logix5550 Over One Link
CIP Messaging Between a Logix5550 and a
Logix5550 Over Two Links
Chapter Summary and What’s Next
See page:
This chapter contains two example applications. Each example explains what steps must be taken to perform these operations.
Publication 1756-6.5.14 - August 1998
8-2 Logix5550 to Logix5550 Messaging
CIP Messaging Between a
Logix5550 and a Logix5550 Over
One Link
This application sends a CIP message from Logix5550 A through a
1756-DHRIO module to Logix5550 B processor B on a DH+ link.
The following diagram illustrates the steps you follow to use such an application:
ControlLogix system #1
Logix5550 A slot number:0
DHRIO module
ControlLogix system #2
Logix5550 B slot number:0
DHRIO module
Channel B node number:020
1 Set Module
Switches
Channel B node number:030
2 Configure Msg
Instructions
41419
Publication 1756-6.5.14 - August 1998
1
Logix5550 to Logix5550 Messaging
Set the Module Switches
8-3
In this application, Channel B on both 1756-DHRIO modules must be set for DH+.
Set Module
Switches
Set the switches as shown below.
DHRIO module - Slot 0
Both channels are set for DH+.
Channel A Channel B
0
1
7
2
6
3
5
4 0
1
7
2
6
3
5
4
DHRIO module - Slot 2
Both channels are set for DH+.
Channel A Channel B
0
1
7
2
6
3
5
4 0
1
7
2
6
3
5
4
Channel B switches Channel A switches
4
5
3
2
6
1
0
7
4
3
5
2
6
1
0
7
4
5
3
2
6
1
0
7
4
5
3
2
6
1
0
7
Channel A shows a node address at 10 and channel B at 20.
Channel B switches Channel A switches
6 6 6 6
4
3
5
2
1
0
7
4
5
3
2
0
1
7
4
3
5
2
1
0
7
4
3
5
2
1
0
7
Channel A shows a node address at 40 and channel B at 30.
41429
Publication 1756-6.5.14 - August 1998
8-4
2
Logix5550 to Logix5550 Messaging
Configure Msg
Instructions
Configure Message Instructions
You must use RSLogix5000 to configure the Logix5550 message instructions.
Ladder rung
See Logix5550 Instruction Set
Reference, publication 1756-6.4.1
Configuration page
Communication page
Publication 1756-6.5.14 - August 1998
When using CIP messaging from a Logix5550, the path is the connection path from the Logix5550 to the final target of the
message. For more information on connection paths, see chapter 4.
For more information on how to configure message instructions using the RSLogix5000 software, see the online help for that software.
CIP Message Routing Between a
Logix5550 and a Logix5550 Over
Two Links
Logix5550 to Logix5550 Messaging 8-5
This application sends a CIP message from Logix5550 A through a
1756-DHRIO module to Logix5550 B processor B over two links.
The following diagram illustrates the steps you follow to use such an application:
ControlLogix system #1 ControlLogix system #2
Logix5550 A slot number:0
DHRIO module slot number:3
Ch A node:010
Ch B node:020
DHRIO module slot number:3
Ch A node:040
Ch B node:030
1 Set Module
Switches
ControlLogix system #3
Logix5550 A slot number:0
DHRIO module slot number:3
Ch A node:060
Ch B node:050
2 Configure Msg
Instructions
41420
Publication 1756-6.5.14 - August 1998
8-6
1
Logix5550 to Logix5550 Messaging
Set Module
Switches
Set the Module Switches
In this application, Channel A on the first and last 1756-DHRIO modules must be set for DH+. Channel A and B on the second
1756-DHRIO module must both be set for DH+.
Set the switches as shown below.
DHRIO module -Chassis 1
Slot 3
Both channels are set for DH+.
Channel A Channel B
1
0
7
2
6
3
5
4
1
0
7
2
6
3
5
4
DHRIO module -Chassis 2
Slot 3
Both channels are set for DH+.
Channel A Channel B
1
0
7
2
6
3
5
4
1
0
7
2
6
3
5
4
Channel B switches Channel A switches
6 6 6 6
4
5
3 1
0
7
4
5
3
7
0
1
4
5
3
7
0
1
4
5
3
7
0
1
2 2 2 2
Channel A shows a node address at 10 and channel B at 20.
DHRIO module -Chassis 3
Slot 3
Both channels are set for DH+.
Channel A
1
0
7
2
6
3
5
4
Channel B
1
0
7
2
6
3
5
4
Channel B switches Channel A switches
6
4
5
3 1
0
7
4
5
3
6
7
0
1
4
5
3
6
7
0
1
4
5
3
6
7
0
1
2 2 2 2
Channel A shows a node address at 40 and channel B at 30.
Publication 1756-6.5.14 - August 1998
Channel B switches Channel A switches
4
5
3
2
6
1
0
7
4
5
3
2
6
0
1
7
4
5
3
2
6
0
1
7
4
3
5
2
6
1
0
7
Channel A shows a node address at 60 and channel B at 50.
41427
2 Configure Msg
Instructions
See Logix5550 Instruction Set
Reference, publication 1756-6.4.1
Logix5550 to Logix5550 Messaging
Configure Message Instructions
You must use RSLogix5000 to configure the Logix5550 message instructions.
Ladder rung
8-7
Configuration page
Communication page
When using CIP messaging from a Logix5550, the path is the connection path from the Logix5550 to the final target of the
message. For more information on connection paths, see chapter 4.
For more information on how to configure message instructions using the RSLogix5000 software, see the online help for that software.
Publication 1756-6.5.14 - August 1998
8-8 Logix5550 to Logix5550 Messaging
Chapter Summary and
What’s Next
In this chapter, you learned about Logix5550 to Logix5550 messaging.
Move on to Chapter 9 to learn about the basics of remote I/O.
Publication 1756-6.5.14 - August 1998
What This Chapter Contains
Introduction to Remote I/O
Logix5550
Chapter
9
Basics of Using Remote I/O
This chapter describes the basic procedures of using the
1756-DHRIO module in RIO scanner mode and configuring a remote
I/O network. The following table describes what this chapter contains and its location.
For information about using:
Introduction to Remote I/O
Selecting Devices That You Can Connect
Designing a Remote I/O Network
Configuring a DHRIO Channel as a RIO Scanner
Chapter Summary and What’s Next
See page:
The remote I/O system lets you control I/O that is not within the controller’s chassis. A 1756-DHRIO channel, configured as an RIO scanner, transfers discrete and block-transfer data between a
Logix5550 controller and remote I/O devices.
An example remote I/O system looks like this:
DHRIO module
The scanner channel maintains a list of all the full and partial racks connected to that channel.
ControlLogix chassis
Remote I/O link cable: Belden 9463
Remote I/O node adapters like the 1771-ASB modules or PanelView operator interfaces addressed as remote I/O racks
PLC-5 channel or a processor operating as a remote I/O adapter
41290
Publication 1756-6.5.14 - August 1998
9-2 Basics of Using Remote I/O
Selecting Devices That
You Can Connect
The remote I/O scanner channel keeps a list of all the adapters on the
RIO network it transfers data with.
Follow these steps for setting up a remote I/O system:
Table 9.1
Setting Up a Remote I/O System
Step: See:
1. configure the remote I/O adapter device the device’s user manual
2. layout and connect the remote I/O link cable
3. configure the scanner channel
The following table lists some of the devices you can use on a remote I/O network as an adapter:
Table 9.2
Devices You Can Connect to a Remote I/O Link
Category: Product:
Other Processors
(in adapter mode)
To Remote I/O enhanced PLC-5 processors
Ethernet PLC-5 processors
ControlNet PLC-5 processor
VMEbus PLC-5 processors extended-local PLC-5 processors classic PLC-5 processors
SLC 500 Remote I/O Adapter Module
1791 Block I/O
Remote I/O Adapter Module
1-Slot I/O Chassis with Integral Power
Supply and Adapter
2-Slot I/O Chassis with Integral Power
Supply and Adapter
Direct Communication Module
Operator Interfaces DL40 Dataliner
RediPANEL
Drives
PanelView Terminal
Remote I/O Adapter for 1336 AC
Industrial Drives
Remote I/O Adapter for 1395 AC
Industrial Drives
Catalog number:
1785-LxxB
1785-LxxE
1785-LxxC
1785-VxxB
1785-LxxL
1785-LTx
1747-ASB
1791 series
1771-ASB
1771-AM1
1771-AM2
1771-DCM
2706-xxxx
2705-xxx
2711-xxx
1336-RIO
1395-NA
Publication 1756-6.5.14 - August 1998
Designing a Remote I/O Network
Trunk line/drop line considerations:
When using a trunk line/drop line configuration, use 1770-SC station connectors and follow these cable-length guidelines:
• trunk line-cable length—depends on the communication rate of the link
• drop-cable length—30.4 m (100 cable-ft.)
For more information about designing trunk line/ drop line configurations, see the Data Highway/
Data Highway Plus/Data Highway II/
Data Highway-485 Cable Installation Manual, publication 1770-6.2.2.
Basics of Using Remote I/O
Designing a remote I/O network requires applying:
• remote I/O network design guidelines
• cable design guidelines
Network Design Guidelines
Keep these rules in mind as you design remote I/O network:
9-3
• All devices connected to a remote I/O network must communicate using the same communication rate, 57.6,
115.2, or 230.4kbps.
• One or both channels of the 1756-DHRIO module in scanner mode cannot scan the same partial or full rack address. Assign unique partial and full racks to each channel used in remote I/O scanner mode.
• A channel can have a maximum of 32 rack numbers and a maximum of 32 physical devices connected to it.
Important: When both channels on the 1756-DHRIO module are configured for RIO, each channel must be connected to adapters with unique rack numbers. For example, channel A communicates to 00-37 octal and channel B communicates to 40-77 octal)
Cable Design Guidelines
Specify 1770-CD (Belden 9463) cable. Connect a remote I/O network using a daisy chain or trunk line/drop line configuration.
Verify that your system’s design plans specify cable lengths within allowable measurements.
Important: The maximum cable length for remote I/O depends on the transmission rate. Configure all devices on a remote I/O network to communicate at the same transmission rate.
Publication 1756-6.5.14 - August 1998
9-4 Basics of Using Remote I/O
For daisy chain configurations, use this table to determine the total cable length you can use.
Table 9.3
Determining Cable Length
A remote I/O network using this communication rate:
57.6 kbps
115.2 kbps
230.4 kbps
Cannot exceed this cable length:
3,048m (10,000 ft)
1,524m (5,000 ft)
762m (2,500 ft)
For proper operation, terminate both ends of a remote I/O network by using the external resistors shipped with the 1756-DHRIO module.
Selecting either a 150
Ω
or a 82
Ω
terminator determines how many devices you can connect on a single remote I/O network.
If your remote I/O network: operates at 230.4 kbps operates at 57.6 kbps or 115.2 kpbs and no devices listed in the table below are on the network contains any device listed in the table below operates at 57.6 kbps or 115.2 kbps, and you do not require the network to support more than 16 physical devices
Table 9.4
Determining Resistor Rating and the Number of Devices
Connected on Your Network
Use this resistor rating:
82
Ω
The maximum number of physical devices you can connect on the network:
32
The maximum number of racks you can scan on the network:
32
150
Ω
16 16
Table 9.5
I/O Adapter Devices that Require 150
Ω
Termination Resistors
Device Type:
Adapters
Miscellaneous
Catalog Number:
1771-AS
1771-ASB
1771-DCM
1771-AF
Series:
All
Publication 1756-6.5.14 - August 1998
Configuring a DHRIO
Channel as a RIO Scanner
Set the switch of the channel you are using as a scanner to 1
Basics of Using Remote I/O 9-5
When you are using a DHRIO channel as a scanner, you must set the rotary switch on the module to identify RIO functionality. Use the diagram below to determine how to set the switches.
0
1
7
2 3
4
6 5
Switch 1
Channel A
Network Type
0
1
7
2
6
3
4
5
Switch 6
Channel B
Network Type
Channel
A
Channel
B
Specify Network Type Set Switch
DH+
RIO Scanner
Illegal
DH+
RIO Scanner
Illegal
0
1
2-7
0
1
2-7 ess
(1s)
4
3
5
2
6 7
1
0
Switch 5 ition 24 Pos n in
4
3
5
2
6 7
1
0
Switch 4
(10s)
Channel B Addr
Show s res
4
3
5
2
6 7
1
0
Switch 3
(1s) ition 10 n in Pos
4
3
5
2
6 7
1
0
Switch 2
(10s)
Channel A Add
Show
41277
Important: If you require a channel to be configured for DH+, use
Channel A. By doing so, you can connect your programming terminal to the connector on the front of the module and communicate to devices on the network.
If only one channel is needed for RIO, use Channel B.
Publication 1756-6.5.14 - August 1998
9-6 Basics of Using Remote I/O
Chapter Summary and
What’s Next
In this chapter, you learned about the basics of using remote I/O
Move on to Chapter 10 to learn about remote I/O operation.
Publication 1756-6.5.14 - August 1998
What This Chapter Contains
DHRIO Module Operation
Chapter
10
Remote I/O Operation
This chapter describes how to communicate with remote I/O. The following table describes what this chapter contains and its location.
For information about using:
DHRIO Module Operation
RIO Scanner Status
Setting the Rate of Data Exchange Between the
Logix5550 and the 1756-DHRIO Module
RIO Scanner Status Update Rate With the
1756-DHRIO Module in a Local Chassis
RIO Scanner Status Update Rate With the
1756-DHRIO Module in a Remote Chassis
DHRIO System Failure Notification and Update Rate
RIO Scanner Failure Notification and Update Rates
Inhibiting the DHRIO and RIO Rack Connections
Inhibiting an RIO Connector Adapter
Increased Remote I/O System Throughput
Sending Block Transfer Data
Block Transfer Notification
Block Transfer ‘Pass-Through’ Messages
Troubleshooting Remote I/O
Communication Difficulties
Chapter Summary and What’s Next
See page:
The 1756-DHRIO module provides two configurable channels that can either send and receive messages over DH+ or scan remote I/O devices. When a channel is configured for remote I/O, the
1756-DHRIO module is designed to function as an RIO scanner for a
Logix5550 controller.
When a 1756-DHRIO module is functioning as an RIO scanner, the following occurs:
• I/O data is exchanged between the 1756-DHRIO module and remote I/O adapters on the RIO link
• I/O data is exchanged between the 1756-DHRIO module and the Logix5550 controller
Publication 1756-6.5.14 - August 1998
10-2 Remote I/O Operation
Exchanging I/O Data Between Adapters on the RIO Link and the
1756-DHRIO Module
I/O data is exchanged between adapters on the RIO link and the
1756-DHRIO module based on a list of adapters generated in the I/O configuration tree in the Controller Organizer of RSLogix 5000.
The Logix5550 controller, known as the owner-controller, downloads this list, along with the RIO baud rate, to the 1756-DHRIO module.
This completes the configuration of the remote I/O on the
1756-DHRIO module.
The remote I/O network pre-dates the producer/consumer model used for ControlLogix. Therefore, the 1756-DHRIO does not use producer/ consumer on the remote I/O network. Instead, the 1756-DHRIO module scans each adapter (exchange I/O data) in the list as quickly as possible.
Exchanging I/O Data Between the Logix5550 and the 1756-DHRIO Module
I/O data and status are exchanged between the Logix5550 and the
1756-DHRIO module through the producer/consumer model used by the ControlLogix system.
Multiple connections are established between the Logix5550 and the
1756-DHRIO module. These connections can be classified in two categories. In the first category, connections are established between the Logix5550 and the 1756-DHRIO module for each adapter on the remote I/O link. I/O data is exchanged on these connections.
In the second category, a connection is established between the
Logix5550 and the supervisor of the remote I/O on the 1756-DHRIO module. (The supervisor is the RIO scanner located internally on the module.) RIO scanner status is exchanged on this connection. In this case, the data exchange is bidirectional. The 1756-DHRIO module reports status on the RIO scanner, and the Logix5550 maintains ownership of the 1756-DHRIO module.
Important: Only 1 Logix5550 controller can communicate and own the RIO channels on a 1756-DHRIO module.
Publication 1756-6.5.14 - August 1998
RIO Scanner Status
Adapter Module I/O
TIP
Remote I/O Operation 10-3
I/O Configuration Tree in Controller Organizer in RSLogix 5000
The I/O configuration tree in the Controller Organizer in
RSLogix 5000 specifies the connections to the 1756-DHRIO module, in addition to generating the adapter list of the 1756-DHRIO module to scan.
The entry of a 1756-DHRIO module in the I/O configuration tree of the Controller Organizer specifies the status connection between the
Logix5550 and the scanner function on the 1756-DHRIO module.
The entries of adapters under the 1756-DHRIO module in the I/O configuration tree of the Controller Organizer specifies the connections between the Logix5550 and the 1756-DHRIO module for each adapter’s data.
Only enter a 1756-DHRIO module into the I/O configuration tree of the Controller Organizer if at least one of the module’s channels is configured for remote I/O.
A connection is used to exchange remote I/O scanner status as described above. The data from the 1756-DHRIO module contains the current state of the channels (A/B) that are configured for remote
I/O. The data from the Logix5550 represents an update used by the
1756-DHRIO module to maintain ownership.
This data exchange is continually updated and is responsible for maintaining module awareness in the system.
The 1756-DHRIO module scans the remote I/O devices as they appear in the Logix5550’s controller organizer. The entries in the organizer represent logical adapters. The physical adapter modules on RIO may act as several racks. This depends on the addressing mode of the physical adapter and chassis.
The RSLogix 5000 software allows 4 choices for the adapter modules:
• 1747 Remote I/O adapter
• 1771 Remote I/O adapter
• 1794 Remote I/O adapter
• Generic Remote I/O adapter
Each entry includes the following:
• rack address - values are 00-77 octal
• starting group - can start in slot 0, 2, 4, or 6
• rack size - can be 1/4, 1/2, 3/4 or full rack
Publication 1756-6.5.14 - August 1998
10-4 Remote I/O Operation
Setting the Rate of Data Exchange
Between the Logix5550 and the
1756-DHRIO Module
Important: Each choice provides a way of determining what type of adapter is present on the RIO network. They all behave the same in the ControlLogix system. When online, the
1756-DHRIO module cannot tell which specific adapter is connected to the RIO network.
The adapter output data sent by the Logix5550 is consumed by the
1756-DHRIO module on the connection created when you add remote I/O devices in RSLogix 5000.
The output data is produced by the owner-controller at the RPI and is not tied to the scan time of the controller’s program. How often the output data is sent by the RIO scanner to the RIO adapters depends upon the number of adapters on the channel and the baud rate used.
The rack input data received in the adapter response is produced by the 1756-DHRIO module immediately after the RIO adapter response is received. The owner-controller receives the data directly into the data buffer created by the software. The frequency at which the input data is produced depends upon the number of adapters on the channel and the baud rate used.
The following sections describe the process of setting the Requested
Packet Interval (RPI) for data exchanges between the Logix5550 and the 1756-DHRIO module. An RPI must be set for both the remote I/O scanner status connection and each adapter connection.
Requested Packet Interval (RPI)
This interval specifies the rate at which the 1756-DHRIO module and the Logix5550 produce data. The time ranges from 3mS to 750mS and is sent to the module with all other configuration parameters.
When the specified timeframe elapses, the 1756-DHRIO module and the Logix5550 will produce data for each other.
RIO Scanner Status Update Rate With the 1756-DHRIO in a
Local Chassis
When a module resides in the same chassis as the owner controller, the RPI affects how and when the module produces link status and consumes the controller status.
The rate the status is exchanged at is equal to the RPI.
RIO Scanner Status Update Rate With the 1756-DHRIO Module in a Remote Chassis
If a module physically resides in a chassis other than where its ownercontroller is (i.e. a remote chassis connected via ControlNet), the rate the status is exchanged at is equal to the RPI + 2 x [Network Update
Time (NUT)].
Publication 1756-6.5.14 - August 1998
TIP
Setting the Rate of I/O Data
Exchange Between the Logix5550 and the 1756-DHRIO Module
Remote I/O Operation 10-5
To maximize notification of the module status, we recommend setting the 1756-DHRIO module’s RPI value equal to the RPI used in the adapter connections.
The rate of I/O data exchange is directly related to the configured
RIO scanner baud rate. Your 1756-DHRIO module allows the following baud rates:
• 57.6Kbaud
• 115.2Kbaud
• 230.4Kbaud
The RIO scanner scan each RIO adapter at the following rates:
• 8ms/adapter @ 57.6Kbaud
• 5ms/adapter @ 115.2Kbaud
• 3ms/adapter @ 230.4Kbaud
To determine the RPI for all Controller Organizer entries use graphs on the following page.
Publication 1756-6.5.14 - August 1998
10-6 Remote I/O Operation
Number of Controller
Organizer Entries Under a 1756-DHRIO Module
Minimum Requested Packet Intervals (RPIs)
The tables below provide the minimum RPI for the different baud rates. Rates faster than those specified do not provide greater data throughput.
Adapter Update Rates for RIO at 230.4Kbaud Rate
4
3
2
6
5
1
3ms/adapter
Number of Controller
Organizer Entries Under a 1756-DHRIO Module
3 6 9 12 15 18 Valid operating RPI rate
Adapter Update Rates for RIO at 115.2Kbaud Rate
4
3
2
1
6
5
5ms/adapter
5 10 15 20 25 30 Valid operating RPI rate
Number of Controller
Organizer Entries Under a 1756-DHRIO Module
Adapter Update Rates for RIO at 57.6Kbaud Rate
4
3
2
6
5
1
8ms/adapter
8 16 24 32 40 48 Valid operating RPI rate
41463
Publication 1756-6.5.14 - August 1998
Remote I/O Operation 10-7
Adapter Module I/O Update Rate with the 1756-DHRIO Module in the Local Chassis
When the 1756-DHRIO module resides in the same chassis as the owner-controller, updated output data (refreshed to new values via the control program) is delivered to the adapter module at:
RPI + scan rate per adapter * number of adapters
Where the RPI is equal to the value determined from the graphs on
page 10-6, and scan rate per adapter=3ms @ 230.4K, 5ms @115.2K,
or 8ms @57.6K.
The updated input data is delivered to the Logix5550 at:
Scan rate per adapter * number of adapters
The update rate for an adapter module (i.e. the rate at which I/O data is produced/consumed between the owner-controller and the
1756-DHRIO module) is:
RPI + 2[Scan rate per adapter * number of adapters]
This is a turnaround calculation for an output to input in the same rack.
When you include block transfers, the update rate for an adapter module is:
RPI + 2(Scan rate per adapter * number of adapters) + (Scan rate per adapter * total number of adapters with BT modules in them)
Publication 1756-6.5.14 - August 1998
10-8 Remote I/O Operation
Adapter Module I/O Update Rate with the 1756-DHRIO Module in the Remote Chassis
When the 1756-DHRIO module resides in the remote chassis from the owner-controller, updated output data (refreshed to new values via the control program) is delivered to the adapter module at:
RPI + (scan rate per adapter * number of adapters) + 2(NUT)
The updated input data is delivered to the Logix5550 at:
(scan rate per adapter * number of adapters) + 2(NUT)
The update rate for an adapter module (i.e. the rate at which I/O data is produced/consumed between the owner-controller and the
1756-DHRIO module) is:
RPI + 2(scan rate per adapter * number of adapters) + 4(NUT)
This is a turnaround calculation for an output to input in the same rack.
When you include block transfers, the update rate for an adapter module is:
RPI + 2(scan rate per adapter * number of adapters) + (Scan rate per adapter * total number of adapters with BT modules in them) + 4(NUT)
Publication 1756-6.5.14 - August 1998
RIO Scanner Failure Notification
TIP
RIO Adapter Failure Notification
Remote I/O Operation 10-9
A 1756-DHRIO module using one of its channels for remote I/O has a connection open between the module and its owner-controller. The
RIO scanner status is continually being exchanged over this connection. This continuous data exchange is responsible for maintaining module awareness in the system.
If at any time this continuous data exchange is interrupted for a time that is 4 times the RPI, the Logix5550 drops the current RIO scanner configuration and terminates communication with the adapters on the
RIO network. The channel configured for RIO scanner goes offline and waits for new configuration data before beginning communication with the RIO network.
The Logix5550 also performs one of the following scenarios:
• Logix5550 will fault, if the 1756-DHRIO module has been configured for a major fault to occur on the controller if communication fails.
• Logix5550 will not fault, if the 1756-DHRIO module has not been configured for a major fault to occur if communication fails. In this case, the Logix5550 will repeatedly attempt to reestablish communications with the
1756-DHRIO module.
The update rate for the data exchange should be set to go at the minimum RPI set for the data flow between the Logix5550 and the
RIO adapters. This guarantees the scanner will quickly terminate remote I/O network communications if the 1756-DHRIO module loses data flow from the Logix5550.
The speed at which the Logix5550 is notified that a remote I/O adapter has faulted is directly related to the RPI. The fault, known as a connection timeout, will occur at 4 times the RPI. For example, if the RPI is set at 25ms and a fault occurs, the Logix5550 will not be notified for 100ms. For more information on connection timeouts, see
An RIO adapter fault notification occurs whenever the communication between the RIO scanner (Channel A or B) and a remote I/O adapter is interrupted or the communication between the
1756-DHRIO module and the Logix5550 is interrupted.
RSLogix 5000 alerts you to a rack fault in at least one of the following ways:
• nonzero condition appears in the tag editor
• fault icon appears in the controller organizer
• connections page displays the fault type
Publication 1756-6.5.14 - August 1998
10-10 Remote I/O Operation
Inhibiting the 1756-DHRIO
Module Connections
When the inhibit bit is set for the 1756-DHRIO module, the connection between the Logix5550 and the 1756-DHRIO module is terminated.
Although the 1756-DHRIO module connection is inhibited, the
DHRIO scanner (Channel A or B) changes to program mode and continues to scan the RIO adapters on the RIO network. When inhibited, a 1756-DHRIO module will accept configuration from any
Logix5550 in the control system.
The 1756-DHRIO connection can be inhibited on the module properties connection tab of RSLogix5000, as shown below.
Inhibiting an RIO
Connector Adapter
Inhibit the connection to the module here
When the inhibit bit is set for a RIO adapter connection, the connection between the Logix5550 and the RIO adapter is terminated.
In this case, the DHRIO scanner (Channel A or B) continues to scan the RIO rack on the RIO network and switches the affected chassis of
I/O into program mode. Only the Logix5550 that initiated the configuration of the 1756-DHRIO module can reestablish communications with the inhibited RIO adapter.
RIO rack connections can be inhibited on the module properties connection screen of RSLogix 5000, as shown below.
Inhibit the connection to the adapter here
Publication 1756-6.5.14 - August 1998
Increased Remote I/O System
Throughput
Remote I/O Operation 10-11
Because of the unique design of the 1756-DHRIO module system, performance is greatly enhanced by splitting the RIO adapters across both channels. An example of a simple system has the following devices:
• Rack 1 - Starting Quarter 0 - Size Full
• Rack 2 - Starting Quarter 0 - Size Full
If both racks are placed on the same channel at a baud rate of
230.4Kbaud, the minimum RPI between the 1756-DHRIO module and the RIO adapters would be 6mS. If the racks are split between channel A and channel B, the update rate can be decreased to 4.5mS.
The following algorithms are used to calculate various update rates:
• @ 230.4Kbaud
Update Rate = 3mS*(number of racks [channel A or B])
+ 1/2*3mS*(number of racks [channel A or B])
• @ 115.2Kbaud
Update Rate = 5mS*(number of racks [channel A or B])
+ 1/2*5mS*(number of racks [channel A or B])
• @ 57.6Kbaud
Update Rate = 8mS*(number of racks [channel A or B])
+ 1/2*8mS*(number of racks [channel A or B])
Publication 1756-6.5.14 - August 1998
10-12 Remote I/O Operation
Sending Block Transfer Data
In addition to discrete I/O, the 1756-DHRIO module supports the sending block transfer (BT) data to the Logix5550 controller. This data exchange transfers up to 64 words of data to/from a selected I/O module.
The BT data exchange is message based. This means that a message instruction in the Ladder Logic program of the Logix5550 must be used to initiate the BT request. In the case of discrete I/O modules, simply by entering the adapter in the Logix5550 organizer, data is transferred without specific instructions required.
The process for completing block transfers on remote I/O remains consistent with all adapters products. All the remote I/O network characteristics defined for the PLC-5 remote I/O scanner are the same for the 1756-DHRIO remote I/O scanner.
Block Transfer Failure Notification
The message timeout for the BT message is fixed at 4.5 seconds. This timeout is a ControlLogix network response timeout associated with the connection established between the 1756-DHRIO module and the
Logix5550 controller. There is a primary timeout for the BT response that is remote I/O network based. This timeout occurs in 4 seconds if the I/O module fails to respond to the BT message.
Publication 1756-6.5.14 - August 1998
Block Transfer ‘Pass-Through’
Messages
Remote I/O Operation 10-13
DH+ ‘Block Transfer (BT) Pass-Through’ messages are specific DH+
(PCCC) messages sent to an RIO channel, where it causes an RIO
Block Transfer.
To target a DH+ ‘BT Pass-Through’ message to an RIO channel on a
1756-DHRIO module, the final destination of the DH+ message must be the 1756-DHRIO module with the RIO channel.
In the case of Local DH+ Messaging, the bridging 1756-DHRIO module must have its default slot configured to match the location
(slot) of the final destination 1756-DHRIO module (module with the
RIO channel).
In the case of Remote DH+ Messaging, the destination link ID and destination node of the DH+ message must be set to the final destination 1756-DHRIO module (module with the RIO channel).
For example, if the target is an RIO channel on a 1756-DHRIO module in slot 5 of a ControlLogix chassis and remote DH+ messaging is used, the destination link ID is set to the ControlLogix chassis link ID and the remote destination node is set to 5.
Important: To send DH+ ‘Pass-Through’ messages to a
1756-DHRIO module, the module must be configured
with a valid routing table, as described in chapter 3, even
if both channels are configured for RIO.
Publication 1756-6.5.14 - August 1998
10-14 Remote I/O Operation
Troubleshooting Remote I/O
Communication Difficulties
The 1756-DHRIO module provides status information for both the module as a whole and each of the module’s channels. This information can be accessed through RSLogix 5000.
1756-DHRIO Module Status Information
Follow these steps:
1. Right-mouse click the 1756-DHRIO module in the I/O configuration tree of the Logix5550’s Controller Organizer and choose Properties from the pop-up menu, as shown below.
Click on the tab Connection tab or either Channel Protocol Errors tab to determine what fault/error may have occurred.
Use the on line help of RSLogix 5000 to correct the fault/error.
2. The module properties page appears in the software.
Publication 1756-6.5.14 - August 1998
Remote I/O Operation
Remote I/O Adapter Status Information
Follow these steps:
10-15
1. Right-mouse click the RIO adapter in the I/O configuration tree of the Logix5550’s Controller Organizer and choose Properties from the pop-up menu, as shown below.
Click on the tab Connection tab or either Channel Protocol Errors tab to determine what fault/error may have occurred.
Use the on line help of RSLogix 5000 to correct the fault/error.
2. The module properties page appears in the software.
Publication 1756-6.5.14 - August 1998
10-16 Remote I/O Operation
Chapter Summary and
What’s Next
In this chapter, you learned about remote I/O operation.
Move on to Chapter 11 to learn about Logix5550 and RIO Scanner
System Performance Considerations.
Publication 1756-6.5.14 - August 1998
What This Chapter Contains
Chapter
11
Connecting a Logix5550 to Remote I/O
This chapter describes how to use the 1756-DHRIO module in RIO scanner mode to connect a Logix5550 to Remote I/O. The following table describes what this chapter contains and its location.
For information about using:
Scanning Remote FLEX Adapters Through a
1756-DHRIO Module in a Local 1756-Chassis
Scanning Remote FLEX Adapters
Through Multiple 1756-DHRIO Modules in a Local Chassis
Scanning 1771 Remote I/O Adapters Through a 1756-DHRIO in a Remote Chassis
Chapter Summary and What’s Next
See page:
This chapter contains three example applications. Each example explains what steps must be taken to perform these operations.
Important: In these examples, only channel B is configured as a remote I/O scanner. You can configure both channels as remote I/O scanners simultaneously if necessary.
If only one channel is configured as a remote I/O scanner, we recommend you use channel B. If you configure channel A as a remote I/O scanner, you cannot use the programming terminal on the front of the
1756-DHRIO module for DH+ access.
Publication 1756-6.5.14 - August 1998
11-2 Connecting a Logix5550 to Remote I/O
Scanning Remote FLEX Adapter
Through a 1756-DHRIO Module in a Local 1756-Chassis
In this application, a Logix5550 controls remote I/O modules through a 1756-DHRIO module in the local chassis.
The following diagram illustrates the steps you follow to use this application:
ControlLogix chassis
Logix5550 DHRIO module
1 Set Module
Switches
1794-FLEX I/O rack number:025
2 Configure
DHRIO Module
41415
3 Configure
FLEX Adapter
Publication 1756-6.5.14 - August 1998
1 Set Module
Switches
Connecting a Logix5550 to Remote I/O
Set the Module Switches
11-3
In this application, channel B on the 1756-DHRIO module must be set for RIO. Channel A can be used for RIO or DH+, regardless of the usage assigned to channel B.
Set the channels as shown.
1
0
7
2
6
3
5
4
Channel B
1
0
7
2
6
3
5
4
Channel B is set for RIO.
2 Configure
DHRIO Module
41428
Configure DHRIO Module
Use RSLogix5000 to configure your application. Follow these steps to configure your 1756-DHRIO module:
1. Add a 1756-DHRIO module to the Controller Organizer.
Add the 1756-DHRIO module here
For more information about how to add modules to the Controller
Organizer, see the Logix5550 User Manual, publication 1756-6.5.12.
Publication 1756-6.5.14 - August 1998
11-4 Connecting a Logix5550 to Remote I/O
2. Configure the 1756-DHRIO module. The following screen shows a sample configuration:
3 Configure
FLEX Adapter
Configure the FLEX Adapter
Follow these steps to configure your 1794-ASB adapter:
1. Add a 1794-ASB adapter under the 1756-DHRIO module entry in the Controller Organizer.
Add the 1794-FLEX adapter here
Publication 1756-6.5.14 - August 1998
Connecting a Logix5550 to Remote I/O 11-5
2. Configure the 1794-ASB adapter. You must fill in the following:
• Parent channel - select which DHRIO channel is being used to scan the FLEX I/O
• Rack # (octal) - indicates the RIO rack number (in octal from 0-76)
• Size - indicates how many words of data are available for the given rack, for example:
1/4 rack = 2 words of input and 2 words of output
1/2 rack = 4 words of input and 4 words of output
3/4 rack = 6 words of input and 6 words of output
Full rack = 8 words of input and 8 words of output
• Starting group - indicates that the first word of input/output from a given rack begins at either group 0, 2, 4, or 6, for example, a system of 2 racks and 4 words of I/O may be as follows:
Rack 12, st grp 2, size 1/4
Rack 12, st grp 6, size 1/4
Important: When you choose a starting group, remember that there is a 1 to 1 ratio of words available and words transmitted.
For example, if you configure the 1794-ASB adapter for a 1/2 rack, you must specify a size equal to 1/2 rack.
The following screen shows a sample configuration:
Publication 1756-6.5.14 - August 1998
11-6 Connecting a Logix5550 to Remote I/O
Scanning Remote FLEX Adapters
Through Multiple 1756-DHRIO
Modules in a Local Chassis
In this application, a Logix5550 scans multiple FLEX remote I/O adapters through multiple 1756-DHRIO modules in the local chassis.
The following diagram illustrates the steps you follow to use this application:
ControlLogix chassis
Logix5550 DHRIO modules
1794-FLEX I/O rack number:025, St group 0, 1/2 rack
1 Set Module
Switches
1794-FLEX I/O rack number:035, St group 4, 1/4 rack
2 Configure 1st
DHRIO Module
3 Configure 1st
FLEX Adapter
41416
4 Configure 2nd
DHRIO Module
5 Configure 2nd
FLEX Adapter
Publication 1756-6.5.14 - August 1998
1 Set Module
Switches
Channel B is set for RIO on both modules
Connecting a Logix5550 to Remote I/O
Set the Module Switches
11-7
In this application, channel B on the 1756-DHRIO module must be set for RIO. Channel A can be used for RIO or DH+, regardless of the usage assigned to channel B.
Set the channels as shown.
0
1
7
2
6
3
5
4
Channel B
0
1
7
2
6
3
5
4 0
1
7
2
6
3
5
4
Channel B
0
1
7
2
6
3
5
4
2 Configure 1st
DHRIO Module
49428
Configure 1st DHRIO Module
Use RSLogix5000 to configure your application. Follow these steps to configure the first 1756-DHRIO module:
1. Add a 1756-DHRIO module to the Controller Organizer.
Add the 1756-DHRIO module here
For more information about how to add modules to the Controller
Organizer, see the Logix5550 User Manual, publication 1756-6.5.12.
Publication 1756-6.5.14 - August 1998
11-8 Connecting a Logix5550 to Remote I/O
2. Configure the 1756-DHRIO module.The following screen shows a sample configuration:
3 Configure 1st
FLEX Adapter
Configure 1st FLEX Adapter
Follow these steps to configure the first 1794-ASB adapter:
1. Add a 1794-ASB adapter under the 1756-DHRIO module entry in the Controller Organizer.
Add the 1794-FLEX adapter here
Publication 1756-6.5.14 - August 1998
Connecting a Logix5550 to Remote I/O 11-9
2. Configure the 1756-ASB adapter. You must fill in the following:
• Parent channel - select which DHRIO channel is being used to scan the FLEX I/O
• Rack # (octal) - indicates the RIO rack number (in octal from 0-76)
• Size - indicates how many words of data are available for the given rack, for example:
1/4 rack = 2 words of input and 2 words of output
1/2 rack = 4 words of input and 4 words of output
3/4 rack = 6 words of input and 6 words of output
Full rack = 8 words of input and 8 words of output
• Starting group - indicates that the first word of input/output from a given rack begins at either group 0, 2, 4, or 6, for example, a system of 2 racks and 4 words of I/O may be as follows:
Rack 12, st grp 2, size 1/4
Rack 12, st grp 6, size 1/4
Important: When you choose a starting group, remember that there is a 1 to 1 ratio of words available and words transmitted.
For example, if you configure the 1756-FLEX adapter for a 1/2 rack, you must specify a size equal to 1/2 rack.
The following screen shows a sample configuration:
Publication 1756-6.5.14 - August 1998
11-10
4
Connecting a Logix5550 to Remote I/O
Configure 2nd
DHRIO Module
Configure 2nd DHRIO Module
Use RSLogix5000 to configure your application. Follow these steps to configure the second 1756-DHRIO module:
1. Add a 1756-DHRIO module to the Controller Organizer.
Add the 1756-DHRIO module here
For more information about how to add modules to the Controller
Organizer, see the Logix5550 User Manual, publication 1756-6.5.12.
2. Configure the 1756-DHRIO module. The following screen shows a sample configuration:
Publication 1756-6.5.14 - August 1998
5 Configure 2nd
FLEX Adapter
Connecting a Logix5550 to Remote I/O
Configure 2nd FLEX Adapter
11-11
Follow these steps to configure the second 1794-ASB adapter:
1. Add a 1794-ASB adapter under the 1756-DHRIO module entry in the Controller Organizer.
Add the 1794-FLEX adapter here
2. Configure the 1794-ASB adapter. You must fill in the following:
• Parent channel
• Rack # (octal)
• Size
• Starting group
The following screen shows a sample configuration:
Publication 1756-6.5.14 - August 1998
11-12 Connecting a Logix5550 to Remote I/O
Scanning 1771 Remote I/O
Adapters Through a 1756-DHRIO in a Remote Chassis
In this application, a Logix5550 scans remote FLEX I/O modules through a 1756-DHRIO module in a remote chassis over a
ControlNet network.
The following diagram illustrates the steps you follow to use this application:
ControlLogix chassis #1
Logix5550
CNB module
Network address:01
ControlLogix chassis #2
DHRIO module
CNB module
Network address:23
1771 I/O rack number:025
1 Set Module
Switch
2 Configure
1st CNB Module
3 Configure
2nd CNB Module
41421
4 Configure
DHRIO Module
5 Configure
1771 Adapter
6 Run
RSNetworx
Publication 1756-6.5.14 - August 1998
1 Set Module
Switches
Connecting a Logix5550 to Remote I/O
Set the Module Switches
11-13
In this application, channel B on the 1756-DHRIO module must be set for RIO. Channel A can be used for RIO or DH+, regardless of the usage assigned to channel B.
Set the channels as shown.
Both channels are set for RIO.
Channel A Channel B
0
1
7
2
6
3
5
4 0
1
7
2
6
3
5
4
DHRIO module -Chassis 2
Slot 0
Channel B switches Channel A switches
6
5 7 5
6
7 5
6
7 5
6
7
4 0 4 0 4 0 4 0
3 1 3 1 3 1 3 1
2 2 2 2
Channel A shows a node address at 10 and channel B at 20.
CNB module - Chassis 1
Slot 3
The module’s network address is 1.
0
1
CNB module - Chassis 2
Slot 3
The module’s network address is 23.
41417
Publication 1756-6.5.14 - August 1998
11-14
2
Connecting a Logix5550 to Remote I/O
Configure 1st
CNB Module
Configure 1st CNB Module
Use RSLogix5000 to configure your application. Follow these steps to configure the first 1756-CNB module:
1. Add the first 1756-CNB modules to the Controller Organizer.
Add the 1756-CNB module here
For more information about how to add modules to the Controller
Organizer, see the Logix5550 User Manual, publication 1756-6.5.12.
2. Configure the 1756-CNB module. The following screen shows a sample configuration:
Publication 1756-6.5.14 - August 1998
3 Configure 2 nd
CNB Module
Connecting a Logix5550 to Remote I/O
Configure 2nd CNB Module
11-15
Use RSLogix5000 to configure your application. Follow these steps to configure the first 1756-CNB module:
1. Add the second 1756-CNB modules to the Controller Organizer.
Add the 1756-CNB module here
For more information about how to add modules to the Controller
Organizer, see the Logix5550 User Manual, publication 1756-6.5.12.
2. Configure the 1756-CNB module. The following screen shows a sample configuration:
Publication 1756-6.5.14 - August 1998
11-16
4
Connecting a Logix5550 to Remote I/O
Configure
DHRIO Module
Configure DHRIO Module
Use RSLogix5000 to configure your application. Follow these steps to configure your 1756-DHRIO module:
1. Add the 1756-DHRIO module to the Controller Organizer.
Add the 1756-DHRIO module here
For more information about how to add modules to the Controller
Organizer, see the Logix5550 User Manual, publication 1756-6.5.12.
2. Configure the 1756-DHRIO module. The following screen shows a sample configuration:
Publication 1756-6.5.14 - August 1998
5 Configure
1771 Adapter
Connecting a Logix5550 to Remote I/O
Configure 1771-ASB Adapter
Follow these steps to configure the first 1771-ASB adapter:
1. Add a 1771-ASB adapter to the 1756-DHRIO module in the
Controller Organizer.
11-17
Add the 1771-ASB adapter here
2. Configure the 1771-ASB adapter. You must fill in the following:
• Parent channel - first screen
• Rack # (octal) - first screen
• Size - first screen
• Starting group - first screen
• Requested packet interval (RPI) - second screen
The following screens show a sample configuration:
Important: Although the Inhibit and Major Fault if Connection Fails options appear on the second screen, and can be accessed there during normal operation, they are not required fields for initial configuration.
Publication 1756-6.5.14 - August 1998
11-18
6
Connecting a Logix5550 to Remote I/O
Run
RSNetworx
Run RSNetworx
You must run RSNetworx for this application to begin operation. For more information on how to run RSNetworx software, see the online help for that software.
Chapter Summary and What’s Next
In this chapter, you learned about connecting a Logix5550 to remote I/O.
Move on to Chapter 12 to see block-transfers applications.
Publication 1756-6.5.14 - August 1998
What This Chapter Contains
Chapter
12
Block Transfers
This chapter describes how to use the 1756-DHRIO module to connect a Logix5550 to a remote I/O Block Transfer (BT) module.
The following table describes what this chapter contains and its location:
For information about using:
Block Transfers to Remote FLEX I/O Modules
Through a 1756-DHRIO in a Local 1756-Chassis
Block Transfers to Remote 1771-ASB I/O
Modules Through a 1756-DHRIO in a Remote
1756-Chassis
Chapter Summary and What’s Next
See page:
This chapter contains two example BT applications. Each example explains what steps must be taken to perform these operations.
Important: In these examples, only channel B is connected to remote
I/O. You can connect both channels to remote I/O simultaneously if necessary.
If only one channel is connected to remote I/O, it is recommended that you use channel B. If you connect channel A to remote I/O, you cannot use the programming terminal on the front of the 1756-DHRIO module.
Publication 1756-6.5.14 - August 1998
12-2 Block Transfers
Block Transfers to Remote
FLEX I/O Modules Through a
1756-DHRIO in a Local Chassis
This application allows a Logix5550 to initiate block transfers to remote FLEX I/O modules through a 1756-DHRIO module in the local chassis.
The following diagram illustrates the steps you follow to use this application:
ControlLogix chassis
Logix5550 DHRIO module
1 Set Module
Switches
1794-FLEX I/O rack number:025
2 Configure
DHRIO Module
41415
3 Configure
FLEX Module
4 Configure
BT Module
5 Configure
Msg Instruction
Publication 1756-6.5.14 - August 1998
1 Set Module
Switches
Block Transfers 12-3
Set the Module Switches
In this application, channel B on the 1756-DHRIO module must be set for RIO. Channel A can be used for RIO or DH+, regardless of the usage assigned to channel B.
Set the channels as shown.
1
0
7
2
6
3
5
4
Channel B
1
0
7
2
6
3
5
4
Channel B is set for RIO.
2 Configure
DHRIO Module
41428
Configure DHRIO Module
Use RSLogix5000 to configure your application. Follow these steps to configure your 1756-DHRIO module:
1. Add a 1756-DHRIO module to the Controller Organizer.
Add the 1756-DHRIO module here
For more information about how to add modules to the Controller
Organizer, see the Logix5550 User Manual, publication 1756-6.5.12.
Publication 1756-6.5.14 - August 1998
12-4 Block Transfers
2. Configure the 1756-DHRIO module. The following screen shows a sample configuration:
3 Configure
FLEX Adapter
Configure the FLEX Adapter
Follow these steps to configure your 1794-FLEX adapter:
1. Add a 1794-FLEX adapter to the 1756-DHRIO module in the
Controller Organizer.
Add the 1794-FLEX adapter here
Publication 1756-6.5.14 - August 1998
Block Transfers 12-5
2. Configure the 1794-FLEX adapter. You must fill in the following:
• Parent channel - select which DHRIO channel is being used to scan the FLEX I/O
• Rack # (octal) - represents a link to a logical rack number
(in octal from 1-77), for example: 1-7, 10-17, 20-27
• Size - indicates how many words of data is available for the given rack, for example:
Rack 1, size 1/4 = 2 words of input and 2 words of output
Rack 5, size 1/2 = 4 words of input and 4 words of output
Rack 10, size 3/4 = 6 words of input and 6 words of output
Rack 20, size Full = 8 words of input and 8 words of output
• Starting group - represents the first word of input/output from a given rack and beginning at either group 0, 2, 4, or 6, for example: a system of 2 racks and 4 words of I/O
Rack 12, st grp 2, size 1/4
Rack 12, st grp 6, size 1/4
Important: When you choose a starting group, remember that there is a 1 to 1 ratio of words available and words transmitted.
For example, if you configure the 1756-FLEX adapter for a 1/2 rack, you must specify a size equal to 1/2 rack.
The following screen shows a sample configuration:
You can change the configuration of a FLEX adapter after it has been entered in the Controller Organizer.
For more information on changing configuration in RSLogix 5000, see the software’s online help.
Publication 1756-6.5.14 - August 1998
12-6 Block Transfers
4 Configure
BT Module
Configure Block Transfer Module
Follow these steps to configure your block transfer module.
1. Add a block transfer module to the 1794-FLEX module in the
Controller Organizer.
Add the 1794-FLEX BT module here
2. Configure the block transfer module. The following screen shows a sample configuration when adding the module to the 1794-FLEX module:
You can change the configuration of a BT module after it has been entered in the Controller Organizer.
For more information on changing configuration in RSLogix 5000, see the software’s online help.
Publication 1756-6.5.14 - August 1998
5 Configure Msg
Instructions
Block Transfers 12-7
Configure Message Instruction
You must use RSLogix 5000 to configure the Logix5550 message instructions. Your message instructions should look like this:
Ladder rung
Configuration page
Communication page
Publication 1756-6.5.14 - August 1998
12-8 Block Transfers
Block Transfers to Remote 1771-
ASB I/O Modules Through a
1756-DHRIO in a Remote Chassis
ControlLogix chassis #1
Logix5550
This application allows a Logix5550 to write block transfers to remote 1771-ASB I/O modules through a 1756-DHRIO module in a remote chassis over a ControlNet link. The following diagram illustrates the steps you follow to use this application:
CNB module
Network Address:01
ControlLogix chassis #2
DHRIO module
CNB module
Network Address:23
1771-ASB rack number:025
1 Set Module
Switches
2 Configure
1st CNB Module
4 Configure
DHRIO Module
5 Configure
1771 Adapter
7 Configure
Msg Instruction
Publication 1756-6.5.14 - August 1998
3 Configure
2nd CNB Module
41430
6 Configure
BT Module
1 Set Module
Switches
Block Transfers 12-9
Important: This example shows one 1756-DHRIO module in the local chassis. You can also connect multiple
1756-DHRIO modules in the remote chassis to additional I/O modules.
If you connect multiple 1756-DHRIO modules to remote I/O modules, follow the steps for each
1756-DHRIO module.
Set the Module Switches
In this application, channel B on the 1756-DHRIO module must be set for RIO. Channel A can be used for RIO or DH+, regardless of the usage assigned to channel B.
Set the channels as shown.
Both channels are set for RIO.
Channel A Channel B
1
0
7
2
6
3
5
4
1
0
7
2
6
3
5
4
DHRIO module -Chassis 2
Slot 0
Channel B switches Channel A switches
6
5 7 5
6
7 5
6
7 5
6
7
4 0 4 0 4 0 4 0
3 1 3 1 3 1 3 1
2 2 2 2
Channel A shows a node address at 10 and channel B at 20.
CNB module - Chassis 1
Slot 3
The module’s network address is 1.
0
1
CNB module - Chassis 2
Slot 3
The module’s network address is 23.
41417
Publication 1756-6.5.14 - August 1998
12-10 Block Transfers
2 Configure 1st
CNB Module
Configure 1st CNB Module
Use RSLogix5000 to configure your application. Follow these steps to configure the first 1756-CNB module:
1. Add the first 1756-CNB modules to the Controller Organizer.
Add the 1756-CNB module here
For more information about how to add modules to the Controller
Organizer, see the Logix5550 User Manual, publication 1756-6.5.12.
2. Configure the 1756-CNB module. The following screen shows a sample configuration when adding the module to the 1756-CNB module:
You can change the configuration of a 1756-CNB module after it has been entered in the Controller Organizer.
For more information on changing configuration in RSLogix 5000, see the software’s online help.
Publication 1756-6.5.14 - August 1998
3 Configure 2 nd
CNB Module
Block Transfers 12-11
Configure 2nd CNB Module
Use RSLogix5000 to configure your application. Follow these steps to configure the first 1756-CNB module:
1. Add the second 1756-CNB modules to the Controller Organizer.
Add the 1756-CNB module here
For more information about how to add modules to the Controller
Organizer, see the Logix5550 User Manual, publication 1756-6.5.12.
2. Configure the 1756-CNB module. The following screen shows a sample configuration:
You can change the configuration of a 1756-CNB module after it has been entered in the Controller Organizer.
For more information on changing configuration in RSLogix 5000, see the software’s online help.
Publication 1756-6.5.14 - August 1998
12-12 Block Transfers
4 Configure
DHRIO Module
Configure DHRIO Module
Use RSLogix5000 to configure your application. Follow these steps to configure your 1756-DHRIO module:
1. Add the 1756-CNB and 1756-DHRIO modules to the Controller
Organizer.
Add the 1756-DHRIO module here
For more information about how to add modules to the Controller
Organizer, see the Logix5550 User Manual, publication 1756-6.5.12.
2. Configure the 1756-DHRIO module. The following screen shows a sample configuration:
You can change the configuration of a 1756-DHRIO after it has been entered in the Controller Organizer.
For more information on changing configuration in RSLogix 5000, see the software’s online help.
Publication 1756-6.5.14 - August 1998
5 Configure
1771 Adapter
Block Transfers
Configure 1771-ASB Adapter
Follow these steps to configure the first 1771-ASB adapter:
1. Add a 1771-ASB adapter to the 1756-DHRIO module in the
Controller Organizer.
12-13
Add the 1771-ASB adapter here
2. Configure the 1771-ASB adapter. You must fill in the following:
• Parent channel - first screen
• Rack # (octal) - first screen
• Size - first screen
• Starting group - first screen
• Requested packet interval (RPI) - second screen
The following screens show a sample configuration:
Important: Although the Inhibit and Major Fault if Connection Fails options appear on the second screen, and can be accessed there during normal operation, they are not required fields for initial configuration.
You can change the configuration of a 1771-ASB adapter after it has been entered in the Controller Organizer.
For more information on changing configuration in RSLogix 5000, see the software’s online help.
Publication 1756-6.5.14 - August 1998
12-14 Block Transfers
6 Configure
1771 BT Module
Configure 1771-BT Module
Follow these steps to configure the 1771-BT module.
1. Add a 1771-BT module to the 1771-ASB adapter in the
Controller Organizer.
Add the 1771-BT module here
2. Configure the 1771-ASB adapter. The following screen shows a sample configuration.
You can change the configuration of a 1771-BT module after it has been entered in the Controller Organizer.
For more information on changing configuration in RSLogix 5000, see the software’s online help.
Publication 1756-6.5.14 - August 1998
5 Configure Msg
Instructions
Block Transfers 12-15
Configure Message Instruction
You must use RSLogix 5000 to configure the Logix5550 message instructions. Your message instructions should look like this:
Ladder rung
Configuration page
Communication page
Publication 1756-6.5.14 - August 1998
12-16 Block Transfers
Chapter Summary and What’s Next
In this chapter, you learned about block transfer applications.
Move on to Chapter 13 to learn about troubleshooting your Data
Highway Plus module.
Publication 1756-6.5.14 - August 1998
Chapter
13
Troubleshooting
What This Chapter Contains
This chapter describes your module’s diagnositcs and methods of troubleshooting your module. The following tables describes what this chapter contains and its location:
For information about:
Checking Power Supply and Module Status
Troubleshooting the Power Supply
Troubleshooting the Module
Monitoring DH+ Communication Channels
Chapter Summary and What’s Next
See page:
Checking Power Supply and
Module Status
On power-up, three events take place simultaneously:
• Alphanumeric status indicator on the module illuminates and cycles through a sequence of messages
• Module OK status indicator shows solid red, then flashes green
• Power supply indicator shows solid green
The following table describes the sequence of messages displayed on the alphanumeric status indicator:
Sequence of display: Where:
For DH+ applications
A DH
A#XX
XXXX
For RIO applications
B IO
A is channel (A or B) and DH indicates network type is DH+
XX is the channel’s node address
XXXX is the channel’s status message
SCAN
XXXX
B is the channel (A or B) and IO indicates network type is remote IO
SCAN indicates scanner
XXXX is the channel’s status message
Alphanumeric status indicator
Power supply indicator
Module OK status indicator
Publication 1756-6.5.14 - August 1998
13-2 Troubleshooting
Troubleshooting the
Power Supply
Troubleshooting the Module
Use the following table to troubleshoot the power supply:
If the POWER indicator is:
Off
On
The power supply is:
Not operating
Operating
Take this action:
Turn power switch ON
Check power wiring connections
Check fuse
None, normal operation
Use the alphanumeric indicator status message and the module status OK indicator to troubleshoot your 1756-DHRIO module.
The following table describes the messages that may appear on your module’s alphanumeric indicator status message:
If the indicator is:
For all applications:
FLSH
The network status is:
Checksum in memory did not match
Take this action:
SRAM
TERM
BPIC
ASIC
VRTX
STOP
XMIT
FALT
NO
MEM
FPWR
WTDG
Bad RAM memory
Backplane termination resistor problem
Backplane ASIC detected error
Backplane ASIC detected error
Operting system error
Module is in redundant system
Transmitter Underrun
Unrecoverable Out of Memory
DC power failure detected
Internal watchdog triggered
Record the display
Remove and reinsert or power down the module
Record the display
Remove and reinsert or power down the module
Record the display
Remove and reinsert or power down the module
Record the display
Remove and reinsert or power down the module
Record the display
Remove and reinsert or power down the module
Record the display
Remove and reinsert or power down the module
Remove the module
1756-DHRIO module does not support redundancy
Record the display
Remove and reinsert or power down the module
Record the display
Remove and reinsert or power down the module
Record the display
Remove and reinsert or power down the module
Record the display
Remove and reinsert or power down the module
Publication 1756-6.5.14 - August 1998
Troubleshooting 13-3
If the indicator is:
BOOT
The network status is:
Module is running Boot code
Take this action:
Normal when updating module firmware
If not updating firmware or after updating firmwarre:
Record the display
Remove and reinsert or power down the module
BERR, FAIL, ADDR,
ILLI, DVDZ, CHKI,
TRPV, PRIV, TRAC,
EM10, EM11,
EUNS, EUSR,
EERR, SPUR, UNIN
Fatal internal error
Record the display
Remove and reinsert or power down the module
Four digits that are frozen
Fatal internal error
Record the code
Remove and reinsert or power down the module
For DH+ applications
OFF
LINE
DUPL
NODE
ONLY
NODE
Data Highway Plus is in STOP state
Duplicate node address
Only node on Data Highway
Plus link
Correct configuration
Choose another node address and reset switches
Check cables
MUTE
LINK
RACK
OVER
DUPL
SCAN
MAX_
DEV_
CHAT
LINK
OK
CNFG
FALT
Incorrect routing table configuration
Incorrect DH+ channel configuration
No adapters found on remote I/O
Verify the module is inserted into the correct slot and chassis
Verify the routing table and DH+ channel configuration, then Apply
(or Default, if appropriate) routing table and DH+ channel configuration
OK
For RIO applications
Normal operation for that channel None, normal operation
Add an adapter to the remote
I/O network
Rack overlap on remote I/O
Duplicate scanner on remote I/O
Maximum devices exceeded on remote I/O
Reconfigure remote I/O racks
Check remote I/O scanner configuration
Remove devices to meet limitations on remote I/O network
Babble detected on remote I/O
Check remote I/O device and network connections
Normal operation for that channel None
Publication 1756-6.5.14 - August 1998
13-4 Troubleshooting
The following table describes the messages that may appear on your module’s status OK indicator:
If the OK indicator is:
The module status is: Take this action:
Off
Green flashing
Red, then Off
Green
Red
Red flashing
Not operating
Operating but not routing messages
Performing self-test
Operating and routing messages
In major fault
In major fault or configuration fault
Apply chassis power
Verify module is completely inserted into chassis and backplane
None, if no messages are actively being routed through the module
To route messages, use module default configuration or configure module
None, normal operation
Verify module configuration
Reboot module if red reoccurs, replace module
Check alphanumeric indicator and take action described in alphanumeric indicator status message table.
The following table describes the messages that may appear on your module’s channel status indicators for channel A or channel B:
If the OK indicator is:
Off
Green
Green flashing
Red
Red flashing
The channel status is: Take this action:
Not online
Operating
One or more nodes faulted or failed
No other node on the network
Hardware fault
Duplicate node detected
Place channel online
None, normal operation
Check power at other chassis
Check cables
Reboot module
If red reoccurs, replace the module
Check node address
Publication 1756-6.5.14 - August 1998
Monitoring DH+
Communication Channels
Troubleshooting
You can use the ControlLogix Gateway Configuration software
(1756-GTWY) to monitor the status of a 1756-DHRIO module.
13-5
1. Start the configuration software and select the 1756-DHRIO module.
2. Select a Port Diagnostics tab.
Diagnostic data is stored in the 1756-DHRIO module. These counters can be reset in the 1756-DHRIO module. You see a list of counter values similar to the one below:
Publication 1756-6.5.14 - August 1998
13-6 Troubleshooting
Chapter Summary and
What’s Next
In this chapter, you learned about troubleshooting your
1756-DHRIO module.
Move to Appendix A to learn about PCCC commands supported by the
1756-DHRIO module.
Publication 1756-6.5.14 - August 1998
Appendix
A
What This Appendix Contains
PCCC Commands Supported by the Data
Highway Plus Module
This appendix describes PCCC commands that your module will execute.
Echo
Any data sent in the echo command is returned in the echo reply.
CMD=06h, FNC=00
ID Host and Status
This command allows you to check the location and status of the controlling intelligent device, such as a PLC-5, that is connected to the DHRIO network.
CMD=06h, FNC=03
Read DH+ Diagnostic Counters
Diagnostic counters are bytes of information stored in RAM in you
1756-DHRIO module. The counters occupy a block of the module’s internal scratch RAM. Your module’s counters wrap around to zero when they overflow.
Counters are used to record events that can be used in debugging and long-term reliability analysis. You must issue a diagnostic read to check the information in your module’s counters.
CMD=06h, FNC=01
Reset DH+ Diagnostic Counters
After reading your 1756-DHRIO module’s diagnostic counters, you may want to reset them back to zero to clear that block of your module’s internal scratch RAM.
CMD=06h, FNC=07
Publication 1756-6.5.14 - August 1998
Appendix
B
Specifications
Description:
Module Location
Maximum Backplane Current Load
Value
ControlLogix chassis
850mA @ +5.1V dc and 1.7mA @ 24 V dc from I/O chassis backplane
4.5W maximum
15.4 BTU/hr maximum
Power Dissipation
Thermal Dissipation
Environmental Conditions:
Operational Temperature
Storage Temperature
Relative Humidity
Shock Unpackaged
Vibration Unpackaged
Connections
Conductors Wiring
Category
Agency Certification
(when product or packaging is marked)
0-60°C (32-140°F)
–40 to 85°C (–40 to 185°F)
5-95% without condensation
30g operational
50g non-operational
2g from 10-150Hz
32 CIP connections available/DH+ channel
Belden 9463 twinaxial
2
1
Class I Div 2 Hazardous
2
Class I Div 2 Hazardous
2 marked for all applicable directives
1 Use this conductor category information for planning conductor routing as described in system level installation manual. Also refer to 1770-4.1, “Programmable Controller Wiring and Grounding
Guidelines.”
2 CSA certification–Class I, Division 2, Group A, B, C, D or nonhazardous locations
FM approved–Class I, Division 2, Group A, B, C, D or nonhazardous locations
ControlLogix and Data Highway Plus are trademarks of the Allen-Bradley Company, Inc.
Publication 1756-6.5.14 - August 1998
Index
A
B
Baud rate
C
Compliance to European Union Directives, 1-6
Controller Slot
default, 3-3 choosing new, 3-3
D
DH+ packets
DH+ protocol
E
European Union Directives, 1-6
I
Inhibiting
L
Limitations
Link Design
DH+ messaging
choosing cable type, 2-2 choosing cable length, 2-2 choosing resistor, 2-2
Publication xxxx-xx.x - Month 19xx
Trunk Line/Drop Line
remote I/O
choosing cable length, 9-4 choosing resistor, 9-4
Trunk Line/Drop Line
P
R
Relative Path
for routing DH+ messages, 3-13
Removal and Insertion Under Power
Routing Error
S
T
termination resistors, 2-2, 9-4
I–1
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world’s leading technology companies.
Worldwide representation.
Argentina
•
Australia
•
Austria
•
Bahrain
•
Belgium
•
Brazil
•
Bulgaria
•
Canada
•
Chile
•
China, PRC
•
Colombia
•
Costa Rica
•
Croatia
•
Cyprus
•
Czech Republic
•
Denmark
•
Ecuador
•
Egypt
•
El Salvador
•
Finland
•
France
•
Germany
•
Greece
•
Guatemala
•
Honduras
•
Hong Kong
•
Hungary
•
Iceland
•
India
•
Indonesia
•
Ireland
•
Israel
•
Italy
•
Jamaica
•
Japan
•
Jordan
•
Korea
•
Kuwait
•
Lebanon
•
Malaysia
•
Mexico
•
Netherlands
•
New Zealand
•
Norway
•
Pakistan
•
Peru
•
Philippines
•
Poland
•
Portugal
•
Puerto Rico
•
Qatar
•
Romania
•
Russia-CIS
•
Saudi Arabia
•
Singapore
•
Slovakia
•
Slovenia
•
South Africa, Republic
•
Spain
•
Sweden
•
Switzerland
•
Taiwan
•
Thailand
•
Turkey
•
United Arab Emirates
•
United Kingdom
•
United States
•
Uruguay
•
Venezuela
•
Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 1756-6.5.14 – August 1998 PN 955132-61
Copyright 1998 Allen-Bradley Company, Inc.
Printed in USA