Allen-Bradley PanelView Plus Compact User Manual
Below you will find brief information for PanelView Plus Compact Terminal 2711PC-K4M20D, PanelView Plus Compact Terminal 2711PC-B4C20D, PanelView Plus Compact Terminal 2711PC-T6M20D, PanelView Plus Compact Terminal 2711PC-T6C20D, PanelView Plus Compact Terminal 2711PC-T10C4D1. The PanelView Plus Compact terminals are similar to some PanelView Plus terminal configurations but with limited hardware and software functions. Major differences of the compact terminals include a fixed hardware configuration, without the addition or replacement of modular components. The terminals are intended for use with programmable logic controllers. Terminals that are AC powered must also be connected to the secondary of an isolating transformer.
Advertisement
Advertisement
PanelView Plus Compact Terminals
User Manual
Catalog Numbers
2711PC-K4M20D,
2711PC-B4C20D, 2711PC-T6M20D,
2711PC- T6C20D, 2711PC-T10C4D1
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
available from your local
Rockwell Automation sales office or online at http://literature.rockwellautomation.com
) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
SHOCK HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Allen-Bradley, PanelView Plus, PanelView Plus Compact, FactoryTalk View, FactoryTalk View ME, FactoryTalk View Studio, FactoryTalk ViewPoint, RSLinx Enterprise, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of Contents
Preface
Overview
Installing the Terminal
Connecting Power
Configuring the Terminal
3 Publication 2711PC-UM001A-EN-P - March 2009
Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Resources. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . 9
Software Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Hardware Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Chapter 2
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Hazardous Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Environment and Enclosure. . . . . . . . . . . . . . . . . . . . . . . . . 16
Required Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Cutout Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Mount the 400 or 600 Terminal in a Panel . . . . . . . . . . . . . . 18
Mount the 1000 Terminal in a Panel. . . . . . . . . . . . . . . . . . . 20
Product Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Chapter 3
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Wiring and Safety Guidelines. . . . . . . . . . . . . . . . . . . . . . . . 23
Removing and Installing the Power Terminal Block . . . . . . . 24
Connecting Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Resetting the Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Chapter 4
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Accessing Configuration Mode. . . . . . . . . . . . . . . . . . . . . . . 31
Loading an Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Running an Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Application Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Terminal Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Configuring Communication . . . . . . . . . . . . . . . . . . . . . . . . 37
Configuring Network Information . . . . . . . . . . . . . . . . . . . . 41
Configuring Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Managing Files on the Terminal . . . . . . . . . . . . . . . . . . . . . . 47
Modifying Display Settings . . . . . . . . . . . . . . . . . . . . . . . . . 50
Font Linking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Configuring the Keypad, Keyboard, or Mouse . . . . . . . . . . . 54
3
4
Table of Contents
Installing and Replacing
Components
Terminal Connections
Upgrading Firmware
Configuring the Touch Screen . . . . . . . . . . . . . . . . . . . . . . . 56
Configuring Print Options . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Configuring Startup Options . . . . . . . . . . . . . . . . . . . . . . . . 60
Configuring Startup Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Clearing the System Event Log. . . . . . . . . . . . . . . . . . . . . . . 65
Displaying Terminal Information . . . . . . . . . . . . . . . . . . . . . 66
FactoryTalk View ME Station Information. . . . . . . . . . . . . . . 68
Modifying the Date, Time, or Time Zone . . . . . . . . . . . . . . . 69
Modifying Regional Settings. . . . . . . . . . . . . . . . . . . . . . . . . 71
Chapter 5
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Required Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Replacing the Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Replacing the Backlight . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Using an External CompactFlash Card . . . . . . . . . . . . . . . . . 81
Removing the Product ID Label . . . . . . . . . . . . . . . . . . . . . . 82
Replacing the Bezel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Display Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Chapter 6
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Cables for Runtime Communication . . . . . . . . . . . . . . . . . . . 87
Communication Port Isolation . . . . . . . . . . . . . . . . . . . . . . . 88
USB Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Serial Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Ethernet Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Chapter 7
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Transferring Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Firmware Upgrade Wizard. . . . . . . . . . . . . . . . . . . . . . . . . . 95
Upgrading Firmware with a CompactFlash Card . . . . . . . . . . 96
Upgrading Firmware over a Network Connection . . . . . . . . 100
Publication 2711PC-UM001A-EN-P - March 2009
Troubleshooting
Specifications
USB Devices
Available Fonts
Index
Table of Contents
Chapter 8
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Isolating the Problem . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Startup Information Messages . . . . . . . . . . . . . . . . . . . . . . 108
Startup Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Startup Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Checking Terminal Components . . . . . . . . . . . . . . . . . . . . 111
Ethernet Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Hardware Compatibility. . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Application Does Not Load . . . . . . . . . . . . . . . . . . . . . . . . 115
Application Does Not Run . . . . . . . . . . . . . . . . . . . . . . . . . 116
Configuration Mode Access . . . . . . . . . . . . . . . . . . . . . . . . 116
Appendix A
Electrical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Agency Certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Appendix B
Compatible USB Devices . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Appendix C
Download Fonts to Terminal . . . . . . . . . . . . . . . . . . . . . . . 123
Machine Edition Fonts CD . . . . . . . . . . . . . . . . . . . . . . . . . 124
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Publication 2711PC-UM001A-EN-P - March 2009
5
Table of Contents
6
Publication 2711PC-UM001A-EN-P - March 2009
Preface
Intended Audience
Parts List
Additional Resources
Use this manual if you are responsible for installing, configuring, and operating the PanelView Plus Compact terminals.
No special knowledge is required to understand this manual or operate the terminal. However, you must understand the functions and operations of the FactoryTalk View ME applications that will run on the terminal. Consult the application designer for this information.
Equipment installers must be familiar with standard panel installation techniques.
Your terminal is shipped with these items:
•
Power terminal block
•
FactoryTalk View ME runtime software preloaded
•
Mounting levers or mounting clips (model dependent)
•
Panel cutout template
•
Installation instructions
The table lists resources available for the PanelView Plus terminals.
Resource
PanelView Plus 400 and 600 Terminals
Installation Instructions, publication
2711P-IN002
PanelView Plus 700 to 1500 Terminals and
Display Modules, and PanelView Plus
Compact 1000 Terminals, Installation
Instructions, publication 2711P-IN001
Wiring and Grounding Guidelines for
PanelView Plus Devices Technical Data, publication 2711P-TD001
Description
Provides details on how to install the terminals in a panel, and wire power.
Provides details on how to install the terminals in a panel, and wire power.
Provides grounding and wiring guidelines for PanelView Plus terminals.
You can view or download publications at http://literature.rockwellautomation.com
. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.
7 Publication 2711PC-UM001A-EN-P - March 2009
7
Preface
8
Publication 2711PC-UM001A-EN-P - March 2009
Chapter
1
Chapter Objectives
Product Overview
Catalog Number
Explanation
Cat. No.
2711PC-K4M20D
2711PC-B4C20D
2711PC-T6M20D
2711PC-T6C20D
2711PC-T10C4D1
9 Publication 2711PC-UM001A-EN-P - March 2009
Overview
This chapter covers these topics:
•
Product description
•
Catalog number explanation
•
Software support
•
Terminal configurations
•
Display modules
•
Accessories
The PanelView Plus Compact terminals are similar to some PanelView
Plus terminal configurations but with limited hardware and software functions. Major differences of the compact terminals include:
•
Fixed hardware configuration, without the addition or replacement of modular components.
•
Serial and Ethernet communication only.
•
Connection to a single logic controller using either RSLinx
Enterprise or KEPServer Enterprise software, not both.
•
Limited number of displays and alarms in the FactoryTalk View
Machine Edition (ME) application and runtime software.
•
FactoryTalk ViewPoint software is not supported.
•
Primary HMI for CompactLogix controllers.
TIP
Applications created for PanelView Plus Compact terminals are referred to as Compact Machine Edition applications. You can run compact applications on PanelView Plus and PanelView
Plus Compact terminals. You cannot run a regular Machine
Edition application created for a PanelView Plus terminal on a
PanelView Plus Compact terminal.
The table provides catalog number configurations for the PanelView
Plus Compact terminals.
Input Power Display Size
4 inch
6 inch
10 inch
Operator Input
Keypad
Keypad and Touch
Touch
Touch
Display Type
Monochrome
Color
Monochrome
Color
Color
DC
9
Chapter 1 Overview
Software Support
Each terminal is preloaded with FactoryTalk View Machine Edition runtime and configuration software that does not require activation.
Applications for the compact terminals are created using FactoryTalk
View Studio software.
Software Requirements
FactoryTalk View Studio
RSLinx Enterprise
(1)
Version
5.1 or later
5.20 or later
(1)
RSLinx Enterprise software is provided with FactoryTalk View Studio. During software installation, you are prompted to install RSLinx Enterprise software.
Compact Machine Edition applications are restricted to a subset of the functions allowed on the PanelView Plus terminals.
•
Maximum of 25 displays
•
Maximum of 200 alarm messages
•
Maximum screen resolution of 640 x 480 (VGA)
• one connection or shortcut to a single controller using either
RSLinx Enterprise 5.20 or KEPServer Enterprise.
•
Serial and Ethernet communication only.
If using RSLinx Enterprise, only serial-DF1, serial-DH485 and
Ethernet drivers are supported.
Hardware Configurations
The terminal configurations are fixed and do not support communication modules. The 1000 touch terminal has a fixed display module and logic module that cannot be replaced.
400 and 600 Configurations 1000 Configuration
5
5
1
2 3
4
1
2
Item
1
2
3
4
5
Description
USB port
(1)
RS-232 serial port
10/100BaseT Ethernet port
Power input, 24V DC
CompactFlash Type 1 card slot
(1)
The 400 and 600 models have one USB port; the 1000 model have two USB ports.
3
4
10
Publication 2711PC-UM001A-EN-P - March 2009
Displays
Overview Chapter 1
The terminal configurations provide monochrome or color displays with keypad, touch, or keypad/touch input.
Keypad Description of 400 Terminals
Keys Description
F1 through F8 Programmable keys that initiate functions on terminal display.
Numeric Keypad 0…9, ., -, Backspace, Enter, Left and Right Tab keys, Shift keys
Navigation Keys Use the arrow keys for navigation.
Use the Alt+arrow keys to activate home, end, page up, and page down functions.
ATTENTION
Use a finger or gloved finger to operate the keypad. To operate the touch screen, use your finger, gloved finger, or plastic stylus with a minimum tip radius of 1.3 mm (0.051 in.). Using other object or tool may damage the touch screen or keypad.
Accessories
Publication 2711PC-UM001A-EN-P - March 2009
The compact terminals use many of the same accessories as the
PanelView Plus terminals with the exception of the display modules, communication modules, logic modules, and memory.
IMPORTANT
The PanelView Plus Compact terminals do not support the addition or replacement of modular components.
Compact Flash Cards
Cat. No.
2711P-RC2
2711P-RC3
2711P-RC4
2711P-RCH
Description
128 MB blank CompactFlash card
256 MB blank CompactFlash card
512 MB blank CompactFlash card
CompactFlash to PCMCIA adapter
Backlight
Cat. No.
2711P-RL10C2
Description
Replacement color backlight for 1000 series B and C displays
11
Chapter 1 Overview
12
Replacement Bezels
Cat. No.
2711P-RBT10
Description
Replacement bezel for 1000 touch terminal
Protective Antiglare Overlays
Cat. No.
Description
2711P-RGK4 Antiglare overlay (3) for PanelView Plus 400 keypad terminal
2711P-RGB4 Antiglare overlay (3) for PanelView Plus 400 color keypad/touch terminal
2711P-RGT6 Antiglare overlay (3) for PanelView Plus 600 touch terminal
2711P-RGT6 Antiglare overlay (3) for PanelView Plus 600 touch terminal
2711P-RGT10 Antiglare overlay (3) for PanelView Plus 1000 touch terminal
Adapter Plates
Cat. No.
2711P-RAK4
2711P-RAT10
Description
Adapts a PanelView Plus 400 keypad terminal to a PanelView
Standard 550 keypad cutout
Adapts a PanelView Plus 1000 touch terminal to a PanelView
1000/1000E touch cutout
Cables
Cat. No.
2711-NC13
Description
RS-232 operating/programming cable (9-pin D-shell to 9-pin D-shell), 5 m (16.4 ft)
2711-NC14
2711-NC17
2711-NC21
RS-232 operating/programming cable (9-pin D-shell to 9-pin D-shell),
10 m (32.7 ft)
Remote RS-232 serial cable (9-pin D-shell to 9-pin D-shell)
RS-232 operating cable (9-pin D-shell to 8-pin mini DIN), 5 m (16.4 ft)
2711-NC22 RS-232 operating cable (9-pin D-shell to 8-pin mini DIN), 10 m (32.7 ft)
2711P-CBL-EX04 Ethernet CAT5 crossover cable, industrial grade, 4.3 m (14 ft)
Communication Adapters
Cat. No.
1761-NET-AIC
Description
AIC+ advanced interface converter
Miscellaneous
Cat. No.
2711P-RY2032
2711P-RTMC
Description
Replacement battery for 1000 terminal
Replacement mounting clips for 1000 terminals, quantity of 8
2711P-RTFC
2711-TBDC
Replacement mounting levers for 400 and 600 terminals, quantity of 8
Replacement DC power terminal block for 400 and 600 terminals
2711P-RTBDC2 Replacement two-position DC power terminal block for 1000 terminal
Publication 2711PC-UM001A-EN-P - March 2009
Chapter
2
Installing the Terminal
Chapter Objectives
This chapter provides pre-installation information and procedures on how to install the terminals.
•
Hazardous locations
•
Environment and enclosure
•
Required tools
•
Clearances
•
Panel cutout dimensions
•
Mount the 400 or 600 terminal in a panel
•
Mount the 1000 terminal in a panel
•
Product dimensions
Hazardous Locations
This equipment is suitable for these locations:
•
Class I, Division 2, Groups A, B, C, D
•
Class II, Division 2, Groups F, G
•
Class III
• ordinary, nonhazardous locations
The following statement applies to use in hazardous locations.
13 Publication 2711PC-UM001A-EN-P - March 2009
WARNING
Explosion Hazard
•
Substitution of components may impair suitability for hazardous locations.
•
Do not disconnect equipment unless power has been switched off and area is known to be nonhazardous.
•
Do not connect or disconnect components unless power has been switched off.
•
All wiring must comply with N.E.C. articles 501, 502, 503, and/or
C.E.C. section 18-1J2 as appropriate.
•
Peripheral equipment must be suitable for the location in which it is used.
The terminals have a temperature code of T4 when operating in a
55 °C (131 °F) maximum ambient temperature. Do not install the terminals in environments where atmospheric gases have ignition temperatures less than 135 °C (275 °F).
13
Chapter 2 Installing the Terminal
USB Ports
The PanelView Plus Compact terminals contain universal serial bus
(USB) ports that comply with hazardous location environments. This section details the field-wiring compliance requirements and is provided in accordance with the National Electrical Code, article 500.
PanelView Plus Compact Terminals Control Drawing
Associated Nonincendive Field Wiring Apparatus
PanelView Plus 400, 600, or 1000 Host Product
Nonincendive Field
Wiring Apparatus
Nonincendive Field Wiring
USB Port
USB
Peripheral
Device
Table 1 - PanelView Plus Compact USB Port Circuit Parameters
C a
Display Size
V oc
I sc
5.25V DC 1.68 A
Groups
A and B
10 µF
Groups
C and D
10 µF
Groups
A and B
3.5 µH 400 and 600
Series C or later
1000 5.25V DC 1.68 A 10 µF 10 µF 15 µH
L a
Groups
C and D
15 µH
15 µH
Selected nonincendive field wiring apparatus must have nonincendive circuit parameters conforming with Table 2.
Table 2 - Required Circuit Parameters for the USB Peripheral Device
V
I max max
≥
V oc
≥
I sc
C i
+ C cable
L i
+ L cable
£ C a
£ L a
14
Publication 2711PC-UM001A-EN-P - March 2009
Publication 2711PC-UM001A-EN-P - March 2009
Installing the Terminal Chapter 2
Application Information
Per the National Electrical Code the circuit parameters of nonincendive field wiring apparatus for use in hazardous locations shall be coordinated with the associated nonincendive field wiring apparatus such that their combination remains nonincendive. The
PanelView Plus terminal and the USB peripheral device shall be treated in this manner.
The circuit parameters of the PanelView Plus terminal USB port are given in Table 1. The USB peripheral device and its associated cabling shall have circuit parameters with the limits given in Table 2 for them to remain nonincendive when used with the PanelView Plus terminal
USB port. If cable capacitance and inductance are not known the following values from ANSI/ISA-RP 12.06.01-2003 may be used:
C cable
= 197 pF/m (60 pF/ft)
L cable
= 0.7 µH/m (0.20 µH/ft)
Nonincendive field wiring must be wired and separated in accordance with 501.10(B)(3) of the National Electrical Code (NEC) ANSI/NFPA 70 or other local codes as applicable.
This associated nonincendive field wiring apparatus has not been evaluated for use in combination with another associated nonincendive field wiring apparatus.
Symbol Definitions
V oc
I sc
V max
I
C
C
L
L max i i a a
Open circuit voltage of the host USB port.
Maximum output current of the host USB port.
Maximum applied voltage rating of the USB peripheral device.
V max
shall be greater than or equal to V oc
in Table 1. (V max
≥
V oc ).
Maximum current to which the USB peripheral device can be subjected.
I max
shall be greater than or equal to I sc
in Table 1. (I max
≥
I sc
).
Maximum internal capacitance of the USB peripheral device.
Maximum allowed capacitance of the USB peripheral device and its associated cable. The sum of C i
of the USB peripheral device and C cable the associated cable shall be less than or equal to C a
. (C i
+ C cable
≤
C
of a
).
Maximum internal inductance of the USB peripheral device.
Maximum allowed inductance of the USB peripheral device and its associated cable. The sum of L i
of the USB peripheral device and L cable
of the associated cable shall be less than or equal to L a
. (L i
+ L cable
≤
L a
).
15
Chapter 2 Installing the Terminal
Environment and Enclosure
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications
(as defined in IEC 60664-1), at altitudes up to 2000 m (6561 ft) without derating.
The terminals are intended for use with programmable logic controllers. Terminals that are AC powered must also be connected to the secondary of an isolating transformer.
This equipment is considered Group 1, Class A industrial equipment according to IEC CISPR 11. Without appropriate precautions, there may be difficulties ensuring electromagnetic compatibility in residential and other environments due to conducted or radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. The terminals meet specified NEMA Type and IEC ratings only when mounted in a panel or enclosure with the equivalent rating. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see:
•
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
, for additional installation requirements.
•
NEMA Standards 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
16
Publication 2711PC-UM001A-EN-P - March 2009
Required Tools
Clearances
Cutout Dimensions
Installing the Terminal Chapter 2
These tools are required for panel installation:
•
Panel cutout tools
•
Small, slotted screwdriver
•
Torque wrench (lb•in) for tightening the mounting clips on the
1000 terminal
Allow adequate clearance around the terminal, inside the enclosure, for adequate ventilation. Consider heat produced by other devices in the enclosure. The ambient temperature around the terminals must be between 0…55 °C (32…131 ºF).
Clearance Area 400 and 600 Terminals
Top 51 mm (2 in.)
Bottom
Side
(1)
Back
102 mm (4 in.)
25 mm (1 in.)
None
1000 Terminal
51 mm (2 in.)
51 mm (2 in.)
25 mm (1 in.)
25 mm (1 in.)
(1)
Minimum side clearance for insertion of memory card and cable wiring is 102 mm (4 in.).
Use the full size template shipped with your terminal to mark the cutout dimensions.
Terminal Type
400 Keypad, or Keypad and Touch
600 Touch
1000 Touch
Height mm (in.) Width mm (in.)
123 (4.86)
123 (4.86)
224 (8.8)
156 (6.15)
156 (6.15)
305 (12.00)
Publication 2711PC-UM001A-EN-P - March 2009
17
Chapter 2 Installing the Terminal
Mount the 400 or 600
Terminal in a Panel
Mounting levers secure the terminal to the panel. The number of levers you use (4 or 6) varies by terminal type.
ATTENTION
Disconnect all electrical power from the panel before making the panel cutout.
Make sure the area around the panel cutout is clear.
Take precautions so metal cuttings do not enter any components already installed in the panel.
Failure to follow these warnings may result in personal injury or damage to panel components.
Follow these steps to mount the 400 or 600 terminals in a panel.
1. Cut an opening in the panel by using the panel cutout shipped with the terminal.
2. Make sure the terminal sealing gasket is properly positioned on the terminal.
This gasket forms a compression-type seal. Do not use sealing compounds.
Sealing Gasket
3. Place the terminal in the panel cutout.
If installing the terminal in an existing 550 panel cutout, align the terminal with the center of the cutout for best gasket sealing.
4. Insert all mounting levers into the mounting slots on the terminal.
18
Publication 2711PC-UM001A-EN-P - March 2009
Installing the Terminal Chapter 2
Mounting Slots
Slide each lever until the flat side of the lever touches the surface of the panel.
Mounting Levers
Flat Side of Lever
5. When all levers are in place, slide each lever an additional notch or two until you hear a click.
6. Rotate each lever in the direction indicated until it is in the final latch position.
Follow the latching sequence for the optimum terminal fit.
6
5
4
3
2
1
Terminal Markings or Alignment
1 4
4 Levers
3
5
6 Levers
2
2
6 1
Notch
Alignment Marks
Rotate lever until notch in lever aligns with proper alignment mark on terminal.
1
4
Use this table as a guide to provide an adequate gasket seal between the terminal and the panel.
6
3
4
5
6
2
3
Lever Position Panel Thickness Range
1 1.52…2.01 mm (0.060…0.079 in.)
2.03…2.64 mm (0.08…0.104 in.)
2.67…3.15 mm (0.105…0.124 in.)
3.17…3.66 mm (0.125…0.144 in.)
3.68…4.16 mm (0.145…0.164 in.)
4.19…4.75 mm (0.165…0.187 in.)
10
8/9
7
Typical Gauge
16
14
12
ATTENTION
Follow instructions to provide a proper seal and to prevent potential damage to the product. Rockwell
Automation assumes no responsibility for water or chemical damage to the terminal or other equipment within the enclosure because of improper installation.
Publication 2711PC-UM001A-EN-P - March 2009
19
Chapter 2 Installing the Terminal
Mount the 1000 Terminal in a Panel
Mounting clips secure the terminal to the panel.
ATTENTION
Disconnect all electrical power from the panel before making the panel cutout.
Make sure the area around the panel cutout is clear.
Take precautions so metal cuttings do not enter any components already installed in the panel.
Failure to follow these warnings may result in personal injury or damage to panel components.
Follow these steps to mount the terminal in a panel.
1. Cut an opening in the panel by using the panel cutout shipped with the terminal.
2. Make sure the terminal sealing gasket is properly positioned on the terminal.
This gasket forms a compression-type seal. Do not use sealing compounds.
3. Place the terminal in the panel cutout.
Sealing Gasket
20
Publication 2711PC-UM001A-EN-P - March 2009
Installing the Terminal Chapter 2
4. Slide the ends of the mounting clips into the slots on terminal.
Mounting Clip
Mounting Clip Slot
5. Tighten the mounting clip screws by hand until the gasket seal contacts the mounting surface uniformly.
Publication 2711PC-UM001A-EN-P - March 2009
6. Tighten the mounting clips screws to a torque of 0.90…1.1 N•m
(8…10 lb•in) by using the specified sequence, making sure not to overtighten.
1
Torque Sequence
4
3 2
ATTENTION
Tighten the mounting clips to the specified torque to provide a proper seal and to prevent damage to the product. Allen-Bradley assumes no responsibility for water or chemical damage to the product or other equipment within the enclosure because of improper installation.
21
Chapter 2 Installing the Terminal
Product Dimensions
Product dimensions for each terminal are in mm (in.).
PanelView Plus 400 Keypad or Keypad/Touch Dimensions
152
(6.0)
90
(3.54)
60
(2.35)
71 (2.81)
154 (6.08)
185 (7.28)
PanelView Plus Compact 600 Touch Dimensions
185 (7.28)
152 (6.0)
98 (3.86)
71 (2.81)
154 (6.08)
PanelView Plus Compact 1000 Touch Dimensions
68 (2.68)
248
(9.7)
55 (2.18)
329
(12.97)
22
Publication 2711PC-UM001A-EN-P - March 2009
Chapter Objectives
Wiring and Safety
Guidelines
Chapter
3
Connecting Power
This chapter covers wiring and safety guidelines, and provides procedures to:
• remove and install the power terminal block.
• connect DC power.
• reset the terminal.
Use publication NFPA 70E Electrical Safety Requirements for
Employee Workplaces, IEC 60364 Electrical Installations in Buildings, or other applicable wiring safety requirements for the country of installation when wiring the devices. In addition to the NFPA guidelines:
• connect the device and other similar electronic equipment to its own branch circuit.
• protect the input power by a fuse or circuit breaker rated at no more than 15 A.
• route incoming power to the device by a separate path from the communication lines.
• cross power and communication lines at right angles if they must cross.
•
Communication lines can be installed in the same conduit as low-level DC I/O lines (less than 10V).
• shield and ground cables appropriately to avoid electromagnetic interference (EMI).
•
Grounding minimizes noise from EMI and is a safety measure in electrical installations.
For more information on grounding recommendations, refer to the
National Electrical Code published by the National Fire Protection
Association.
For more information, refer to Wiring and Grounding Guidelines for
PanelView Plus Devices, publication 2711P-TD001 . You can locate this publication in the literature library at this website http://literature.rockwellautomation.com
.
23 Publication 2711PC-UM001A-EN-P - March 2009
23
Chapter 3 Connecting Power
Removing and Installing the
Power Terminal Block
The terminals are shipped with the power terminal block installed.
You can remove the terminal block for ease of installation, wiring, and maintenance.
WARNING
Explosion Hazard
Substitution of components may impair suitability for hazardous locations.
Do not disconnect equipment unless power has been switched off and area is known to be nonhazardous.
Do not connect or disconnect components unless power has been switched off.
All wiring must comply with N.E.C. articles 501, 502, 503, and/or C.E.C. section 18-1J2 as appropriate.
Peripheral equipment must be suitable for the location in which it is used.
PanelView Plus Compact 400 and 600 Terminals
ATTENTION
Do not force terminal blocks into connectors to prevent potential damage to terminal.
Follows these steps to remove the terminal block in the PanelView
400 and 600 terminals.
1. Insert the tip of small, flat-blade, screwdriver into the terminal block access slot.
2. Gently pry the terminal block away from terminal to release the locking mechanism.
24
Publication 2711PC-UM001A-EN-P - March 2009
Publication 2711PC-UM001A-EN-P - March 2009
Connecting Power Chapter 3
Follow these steps to replace the terminal block.
1. Press the terminal block base in first with block leaning outward.
2. Gently push the top of the terminal block back to the vertical position to snap in locking tab.
PanelView Plus Compact 1000 Terminals
Follow these steps to remove the terminal block.
1. Loosen the two screws that secure the terminal block.
2. Gently pull the terminal block away from the connector.
GND
Follow these steps to install the terminal block.
1. Reattach the terminal block to the connector until seated.
2. Tighten the two screws that secure the terminal block to the connector.
25
Chapter 3 Connecting Power
Connecting Power
Terminal
400 and 600
1000
The PanelView Plus Compact terminals have an integrated, 24V DC power supply. See
Appendix A , Specifications for power ratings.
The power supply is internally protected against reverse polarity of the DC+ and DC- connections. Connecting DC+ or DC- to the earth terminal may damage the device.
The input power terminal block supports these wire sizes.
Stranded or solid
Wire Type
Wire Specifications for DC Input Power Terminal Block
Dual-wire Gauge
(1) Single-wire Gauge
Terminal Screw Torque
Cu 90 °C (194 °F) 22…16 AWG 22…14 AWG
0.45…0.56 N•m (4…5 lb•in)
0.56 N•m (5 lb•in)
(1)
Two-wire max. per terminal.
External Power Supply For Non-insolated DC Terminals
TIP
The PanelView Plus Compact terminals contain non-isolated DC power supplies.
Use a single, 24V DC power supply to power each PanelView Plus
Compact terminal, such as cat. no. 2711P-RSACDIN. Using a separate, isolated and ungrounded source to power each terminal prevents ground loop currents from damaging the terminals.
Multiple AC Power Supplies to Power Multiple DC Terminals
L2 L1
AC/DC Power Supply
(2711P-RSACDIN) dc+ dc-
L2 L1
AC/DC Power Supply
(2711P-RSACDIN) dc+ dc-
Circuitry Circuitry
PanelView Plus
PanelView Plus
The output on the power supply must be isolated from the input and not connected to earth/ground.
The non-isolated power supply does not provide galvanic isolation. A
Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply with a 24V DC nominal output voltage is required to power the terminal.
ATTENTION
Use a Class 2 or SELV supply as required by local wiring codes for your installation. The Class 2 and SELV power sources provide protection so that under normal and single-fault conditions, the voltage between the conductors, and between the conductors and functional earth or protective earth does not exceed a safe value.
26
Publication 2711PC-UM001A-EN-P - March 2009
Connecting Power Chapter 3
Earth/Ground Connection
You must connect the earth/ground terminal to a low-impedance earth/ground.
•
The 1000 terminals have the earth/ground connection on the rear of the display module.
•
The 400 and 600 terminals have the functional earth/ground connection on the power input terminal block.
IMPORTANT
The earth/ground connection to ground is mandatory. This connection is required for noise immunity, reliability, and
Electromagnetic Compliance (EMC) with the European Union
(EU) EMC directive for CE-mark conformance and is required for safety by Underwriters Laboratory.
Terminal
400 and 600
1000
The earth terminal requires a minimum wire gauge.
Symbol
GND
Earth Wire Specifications
Wire Type Wire Gauge
14…12 AWG
Stranded or solid Cu 90 °C (194 °F)
14…10 AWG
Terminal Screw Torque
0.45…0.56 N•m (4…5 lb•in)
1.13…1.36 N•m (10…12 lb•in)
On most PanelView Plus DC terminals, the earth/ground terminal is internally connected to the DC- terminal within the product.
ATTENTION
Damage or malfunction can occur when a voltage potential exists between two separate ground points. Make sure the terminal does not serve as a conductive path between ground points at different potentials.
The PanelView Plus terminals have isolated and nonisolated communication ports. Refer to
Communication Port Isolation page 88
for details.
IMPORTANT
For more information, refer to Wiring and Grounding Guidelines for PanelView Plus Devices, publication 2711P-TD001 .
Publication 2711PC-UM001A-EN-P - March 2009
27
Chapter 3 Connecting Power
Connect DC Power
WARNING
Explosion Hazard - Do not disconnect equipment unless power has been switched off and area is known to be nonhazardous.
Disconnect all power before installing or replacing components.
Failure to disconnect power may result in electrical shock or damage to the terminal.
Follow these steps to connect the terminal to DC power.
1. Verify that the terminal is not connected to a power source.
2. Secure the DC power wires to the terminal block.
Follow the markings on terminal blocks and terminal for proper connections.
3. Secure the earth/ground wire.
•
On 400 and 600 terminals, secure the earth/ground wire to the functional earth/ground terminal on the input power terminal block.
•
On the 1000 terminal, secure the earth/ground wire to the earth/ground terminal screw at the bottom of the display.
400 and 600 DC Terminals
1000 DC Terminal
GND
Earth/Ground to Ground Bus
GND
Terminal Block
–
+
DC - DC +
4. Apply 24V DC power to the terminal.
+
–
DC +
DC -
Functional Earth to Ground Bus
28
Publication 2711PC-UM001A-EN-P - March 2009
Connecting Power Chapter 3
Resetting the Terminals
Use the reset switch to restart a terminal without having to disconnect and reapply power. After a reset, the terminal performs a series of startup tests and then either:
• runs the .MER application loaded in the terminal.
• enters Configuration mode.
The action that occurs depends on the startup options configured for
your terminal. Refer to page 60 for information on startup options.
Refer to
, for a list of startup information and error messages.
Reset
Reset Switch
•
On 400 and 600 terminals, press the reset switch with your finger or a nonconductive object.
•
On 1000 terminals, insert a thin, nonconductive probe into the hole marked reset and press the switch.
ATTENTION
Use a nonconductive object to press the reset or default switch.
Do not use a conducting object such as a paper clip or you may damage the terminal. Do not use the tip of a pencil; graphite may damage the terminal.
Publication 2711PC-UM001A-EN-P - March 2009
29
Chapter 3 Connecting Power
30
Publication 2711PC-UM001A-EN-P - March 2009
Chapter
4
Configuring the Terminal
Chapter Objectives
This chapter shows how to use the Configuration mode of your terminal to:
• perform data entry and navigation.
• load an application.
• run an application.
• modify application settings.
• modify terminal settings.
Accessing Configuration
Mode
Your terminal has onboard software, FactoryTalk View ME Station, to perform and configure terminal operations. When you reset or start the terminal, you automatically enter Configuration mode, unless your
.MER application is automatically set to run on startup.
31 Publication 2711PC-UM001A-EN-P - March 2009
To access Configuration mode from a running application, press the
Goto Configuration Mode button. The application stops running but is still loaded.
IMPORTANT
To access Configuration mode from a running application, you must add a Goto Configuration Mode button to an application screen in FactoryTalk View Studio software.
31
Chapter 4 Configuring the Terminal
Name of application that is currently loaded.
Only appears if application is loaded.
Configuration Mode
Terminal Operation
Load Application (F1)
Run Application (F2)
Application Settings (F3)
Terminal Settings (F4)
Delete Log Files Before
Running (F5)
Reset (F7)
Exit (F8)
Description
Opens another screen where you can select an application to load. Once loaded, the application name will appear under Current Application.
Runs the .mer application displayed under Current
Application. An application must be loaded before you can run it.
Opens a menu of application-specific configuration settings.
Opens a menu of options to configure non-application, specific terminal settings.
Toggles between Yes and No. If you select Yes, all data log files, alarm history and alarm status file will be deleted before the application is run. If you select No, log files are not deleted first.
Resets the terminal. The action on startup depends on how you configure the startup option.
Exits Configuration mode.
32
Publication 2711PC-UM001A-EN-P - March 2009
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
Navigation Buttons
Screen buttons are used for data entry and navigation.
•
On touch-screen terminals, tap the button with your finger or stylus.
•
On keypad terminals, select the function key listed on the button, or in some cases, the corresponding key on the keypad.
•
If a mouse is attached, click a button.
In addition to operation specific buttons, most screens have a combination of these buttons.
Navigation Buttons
Close
[F8]
Description
Returns to the previous screen.
OK
[F7]
Cancel
[F8]
Accepts modified values and returns to previous screen.
Cancels the current operation without saving any changes.
Moves highlight up or down a list.
Selects a highlighted screen or item from a list.
33
Chapter 4 Configuring the Terminal
Display Area
Enter or Edit Data
Many screens have buttons that access fields where you must enter or edit data. When you press the button or function key, the input panel opens ready for you to enter data. If a field is restricted to a numeric value, only the 0…9 keys will be enabled. If the value is an IP address, the 0…9 and decimal point keys will be enabled.
PanelView Plus
Character Keyboard
Controls
34
Input Panel Controls
SHF
CAPS
SPACE
Backspace
Select
Right, Left, Up, Down Arrow
Keys
Enter
ESC
Function
Switches keys between their shifted and unshifted state. The initial default is shifted.
Switches keys between lowercase and uppercase characters. The initial default is lowercase.
Enters a space between characters in the Display Area.
Deletes the previous character (to the left of the cursor) in the Display Area.
Selects a character and enters it in the Display Area.
Selects the character to the right, left, above or below the currently selected character.
Accepts the entered characters and returns to the previous screen
Cancels the current operation and returns to the previous screen.
Follow these steps to enter characters in the display area.
1. Select a character on the character keyboard.
•
On a touch-screen terminal, tap or press a key.
•
On a keypad terminal, use the arrow keys on the keypad to select a key.
•
If a mouse is attached, click a key.
2. Press the Select button to copy the character to the display area.
3. Press Enter when done to exit the input panel.
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
Loading an Application
You can load a FactoryTalk View ME .MER application from internal
CompactFlash in the terminal or an external CompactFlash card.
List of .MER applications stored in the CompactFlash of the terminal.
Moves highlight up
Moves highlight down
Publication 2711PC-UM001A-EN-P - March 2009
Follows these steps to load an application:
1. Select Load Application from the main screen.
2. Press the Source button to select the storage location of the application file you want to load.
•
Internal Storage - internal CompactFlash in the terminal.
•
External Storage 1 - external CompactFlash card loaded in the card slot of the terminal.
•
External Storage 2 - reserved for future use.
TIP
FactoryTalk View ME software only recognizes files in the \Rockwell Software\RSViewME\Runtime\ folder.
3. Select an .MER file from the list by using the up and down cursor keys.
4. Press the Load button to load the selected application.
You are asked if you want to replace the terminal’s communication configuration with the communication settings in the application.
5. Select Yes or No.
If you select Yes, any changes to the device addresses or driver properties in the RSLinx Communication screen will be lost.
The name of the currently loaded application will appear at the top of the main configuration screen.
If you try to load a regular Machine Edition application created for a
PanelView Plus application on a PanelView Compact terminal, an error is generated.
Error: Unable to load non-Compact Machine Edition application. Please load a compact Machine Edition application.
IMPORTANT
You can only load a Compact Machine Edition application on a
PanelView Plus Compact terminal.
35
Chapter 4 Configuring the Terminal
Running an Application
After loading an .MER application, you can run the application. To load an application, select the Run Application button on the main screen.
Log files are generated by the application. To delete the log files before running an application, select the Delete Log Files Before
Running button on the main screen.
Application Settings
You can show device shortcuts defined for the loaded .MER application. For example, your .MER application might have SLC defined as a device shortcut name for the SLC 5/05 controller. Device shortcuts are read-only and cannot be edited. To view device shortcuts, select the Application Settings button from the main screen.
Terminal Settings
36
You can modify settings on the terminal that are not specific to the application.
Terminal Settings
Diagnostic
Display
File Management
Font Linking
Description
Forwards diagnostic messages form a remote log destination to a computer running diagnostics.
Shows the temperature of the display, sets the intensity of the backlight, and enables/disables the screen saver.
Copies or deletes application files or font files from a storage location.
Links a font file to a base font loaded on the terminal.
Input Devices Configures settings for the keypad, touch screen, or attached keyboard and mouse.
Networks and Communications Configures network connections and communication settings specific to the application.
Print Setup Configures settings for printing displays, alarm messages, and diagnostics messages generated by the application.
Startup Options
System Event Log
System Information
Time/Date/Regional Settings
Specifies whether the terminal starts up in configure or run mode. Also lets you enable/disable tests to run on the terminal at startup.
Displays a list of system events currently logged by the terminal.
Displays power, temperature, battery and memory details for the terminal. Also shows the firmware number for FactoryTalk View ME software and technical support information.
Sets the date, time, language, and numeric format used by the terminal and applications.
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
Follow these steps to access terminal settings and select a function.
1. Select Terminal Settings from the main screen.
Diagnostics Setup
Display
File Management
Font Linking
Input Devices
Networks and Communications
Print Setup
Startup Options
System Event Log
System Information
Time/Date/Regional Settings
Moves highlight up.
Moves highlight down.
Selects highlighted item and opens screen.
Returns to previous screen.
2. Highlight an option by using the up and down cursor buttons.
•
On touch screen terminals, press the buttons.
•
On keypad terminals, press a key on the keypad or the corresponding function key.
3. Press the Enter key to access the highlighted function.
Configuring Communication
You configure communication for your application and controller by using RSLinx Enterprise software.
•
Access KEPServer Serial Port ID’s.
•
Edit or view the driver settings for the communication protocol used by your .MER application.
•
Edit the device address of the controller on the network.
Publication 2711PC-UM001A-EN-P - March 2009
KEPServer Serial Port ID’s
To access the KEPServer Serial Port ID’s screen, you must have
KEPServer Enterprise installed on your terminal. Otherwise, you will get an error message when accessing this screen. If you plan on using
KEPServer Enterprise and serial communication, you must specify which COM port to use.
To access the KEPServer Serial Port ID screen, select Terminal
Settings>Networks and Communications>KEPServer Serial Port ID’s.
37
Chapter 4 Configuring the Terminal
Configure Communication Properties
Follow these steps to configure driver settings for the communication protocol used by your application.
1. Select Terminal Settings>Networks and Communications>RSLinx
Enterprise Communications.
You see a tree view of installed communication cards and network configurations.
Ethernet Driver
Has no properties to edit.
Communication Driver
AB_ETH-1
<No Devices>
Serial-DF1
<No Devices>
2. Select the communication card installed on your terminal.
3. Press the Edit Driver button to view the current properties for the communication driver.
38
4. Select the property you want to modify, then press the Edit button.
5. Modify the setting and then press the Enter button.
You return to the previous screen with the newly entered data.
Publication 2711PC-UM001A-EN-P - March 2009
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
Serial Properties
Field
Device
Error Check
Parity
Stop Bits
Ack Timeout
Max Retries
Station
Baud Rate
Use Auto Config
Com Port
Description
The serial device your terminal is connected to.
Type of error checking used. Error checking is automatically configured if Use Auto Config is set to Yes.
Valid Values
PLC_CH0
KF2
SLC_CH0
KF3
KFC
KFC15
AC_CH0
BCC, CRC
Type of parity used. The parity is automatically configured if Use Auto Config is set to Yes.
Number of stop bits used.
Ack/Poll timeout value in ms.
None, Odd, Even
1 or 2
20…60,000 ms
Maximum number of retries before the serial driver fails.
Data rate at which serial driver communicates. The baud rate is automatically configured if Use Auto Config is set to Yes.
0…255
Station number based on a specific device.
PLC_CH0 0…77 (octal)
KF2 0…77 (octal)
SLC_CH0 0…31
KF3
KFC
0…31
1…99
KFC15 1…99
AC_CH0 0…255
110
300
600
1200
4800
9600
19,200
38,400
115,200
Automatically or manually configures the baud rate, parity, and error checking parameters.
Communication port used on the terminal.
Yes (auto configure)
No (manual configure)
1 (COM1)
2 (COM2)
39
Chapter 4 Configuring the Terminal
Configure the Controller Address
Follow these steps to edit the device address of the logic controller.
1. From the RSLinx Configuration screen, select a device node.
2. Press the Edit Device button to view the device name and current address of the logic controller.
40
3. Press the Device Address button to modify the address.
The input panel opens with the current address.
4. Use the Input Panel to modify the address and then press the
Enter button.
You return to the previous screen with the new address.
5. Press OK.
IMPORTANT
Modified settings do not take effect until the terminal is restarted.
Publication 2711PC-UM001A-EN-P - March 2009
Configuring Network
Information
Configuring the Terminal Chapter 4
You can configure network information for your terminal.
•
Device name to identify terminal on network
•
IP address of terminal on network
•
Username and password to access network resources
Define a Device Name for the Terminal
You can configure a device name and description to identify your your terminal on the network.
Follow these steps to enter a device name and description for your terminal.
1. Select Terminal Settings>Networks and
Communications>Network Connections>Device Name.
Publication 2711PC-UM001A-EN-P - March 2009
2. Press the Device Name button to enter or edit the device name.
3. Press the Device Description button to enter or edit the description for the device.
Field
Device Name
(1)
Description
Name that identifies the terminal to other computers on the network.
Device Description Provides a description of the terminal.
Valid Values
1…15 characters
A leading character in the range of a through z or
A through Z.
Remaining characters in the range of a through z,
A through Z, 0…9, or - (hyphen)
50 characters max
(1)
Check with your network administrator to determine a valid device name.
4. Press OK.
41
Chapter 4 Configuring the Terminal
Define an Ethernet IP Address
Some networks automatically assign IP addresses to Ethernet devices if DHCP is enabled. If DHCP is not enabled, you can manually enter an IP address for the terminal.
Follow these steps to view or enter an IP address for your terminal.
1. Select Terminal Settings>Networks and
Communications>Network Connections>Network Adapters.
E100CE1:Built-in Ethernet Controller
2. Press the IP Address button to view or modify the IP address.
42
3. Press the DHCP button to enable or disable DHCP assignment of addresses.
4. Press the IP address, Subnet Mask, and Gateway buttons, then enter the appropriate information.
5. Press OK when done.
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
Field
Use DHCP
IP Address
Subnet Mask
Gateway
Mac ID
Description
Enables or disables Dynamic Host
Configuration Protocol (DHCP) settings. DHCP automatically allocates network devices and configurations to newly attached devices on the network.
Valid Values
Yes (default)
No
If DHCP is set to Yes, the terminal is automatically assigned an IP address, Subnet
Mask, and Gateway. The fields are disabled.
If DHCP is set to No, you can enter the IP address, Subnet Mask, and Gateway address.
A unique address identifying the terminal on the Ethernet network.
xxx.xxx.xxx.xxx
000.000.000.000 (default)
Range of values for the first set of decimal numbers is
1…255 unless all fields are set to 000. The range of values for the last three sets of decimal numbers is 0…255.
xxx.xxx.xxx.xxx
Address must be identical to the server subnet mask.
Optional Gateway address.
Read-only field.
xxx.xxx.xxx.xxx
Publication 2711PC-UM001A-EN-P - March 2009
43
Chapter 4 Configuring the Terminal
Define Name Server Addresses
You can define name server addresses for the EtherNet/IP network adapter. These addresses are automatically assigned if DHCP is enabled for the network adapter.
Follow these steps to define name server address.
1. Select Terminal Settings>Networks and
Communications>Network Connections>Network Adapters.
2. Press a button to enter a name server address.
Field
Primary DNS
Secondary DNS
Primary WINS
Secondary WINS
Description
The address of the primary DNS resolver.
Valid Values
xxx.xxx.xxx.xxx
The address of the secondary DNS resolver.
xxx.xxx.xxx.xxx
The address of the primary WINS resolver.
xxx.xxx.xxx.xxx
The address of the secondary WINS resolver.
xxx.xxx.xxx.xxx
3. Press OK when done.
44
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
Authorize Terminal to Access Network Resources
The terminal can access network resources with proper identification.
A user name, password, and domain must be provided by your network administrator.
1. Select Terminal Settings>Networks and
Communications>Network Connections>Network Identification.
2. Press the user name, password and domain buttons and enter the information provided by your network administrator.
Field
User Name
Password
Domain Name
Description
Identifies the user to the network.
Characters that gain access to network along with the user name.
Provided by network administrator.
Valid Values
70 characters max
No character limitation
15 characters max
3. Press OK when done.
Configuring Diagnostics
You can configure diagnostics for the current computer. To access the diagnostic screen, select Terminal Settings>Diagnostic Setup from the main screen. The screen shows a tree view of diagnostic nodes.
To access the Remote
Log Setup or Message
Routing, select the node and then the Edit button.
Publication 2711PC-UM001A-EN-P - March 2009
45
Chapter 4 Configuring the Terminal
Remote Log Destination
The Remote Log Destination forwards messages that it receives to a
Windows 2000/XP computer running diagnostics. The location is determined by the IP address and port number.
Field
Address
Port
Description
Address of the remote Windows
2000/XP computer.
The port used to communicate with the remote Windows 2000/XP computer.
Valid Values
xxx.xxx.xxx.xxx
4445 (default)
Message Routing
The Message Routing screen lets you access these screens:
•
Remote Log
•
FactoryTalk View Diagnostics List
Each of the above screens shows a list of messages that can be sent to that destination. The list shows the On/Off status of each message type. Use the On/Off button to turn a message type on or off. A message type is enabled if it has a checked box.
46
Publication 2711PC-UM001A-EN-P - March 2009
Managing Files on the
Terminal
Configuring the Terminal Chapter 4
The terminal provides operations for managing files that are stored on the terminal.
•
Delete application .MER files, font files, or log files that reside in a storage location on the terminal.
•
Copy application .MER files or font files from one storage location to another.
Delete an Application File or a Font File
The procedure for deleting an application file or a font file from the terminal is the same except for the type of file you are deleting.
1. Select Terminal Settings>File Management>Delete Files>Delete
Applications or Delete Fonts.
2. Press the Source button to choose the storage location of the application or font file you want to delete.
•
Internal Storage - the internal CompactFlash in the terminal.
•
External Storage 1 - the external CompactFlash card loaded in the card slot of the terminal.
•
External Storage 2 - for future use.
Publication 2711PC-UM001A-EN-P - March 2009
3. Select a file from the list.
4. Press the Delete button.
5. Select Yes or No when asked if you want to delete the selected application or font file from the storage location.
47
Chapter 4 Configuring the Terminal
Delete Log Files from Terminal
You can delete log files, alarm history files, and alarm status files from the System Default location on the terminal.
1. Select Terminal Settings>File Management>Delete Files>Delete
Log Files.
You are asked to confirm the deletion of the files.
2. Select Yes or No.
Only log files in the System Default location are deleted.
Copy an Application File or Font File
The procedure for copying an application .MER file or a font file from one storage location on the terminal to another is the same.
1. Select Terminal Settings>File Management>Copy Files>Copy
Applications or Copy Fonts.
List of files stored in CompactFlash of terminal.
48
2. Press the Source button to choose the location of the application or font file you want to copy.
•
Internal Storage - the internal CompactFlash in the terminal.
•
External Storage 1 - the external CompactFlash card loaded in the card slot of the terminal.
•
External Storage 2 - for future use.
3. Select a file from the storage location.
4. Press the Destination button on the same screen.
Publication 2711PC-UM001A-EN-P - March 2009
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
5. Press the Destination button to choose the storage location where you want to copy the application or font file.
The destination must be different than the source location.
•
Internal Storage - the internal CompactFlash in the terminal.
•
External Storage 1 - the external CompactFlash card loaded in the card slot of the terminal.
•
External Storage 2 - for future use.
6. Press the Copy button to copy the selected application or font file to the selected destination.
If the file exists, you will receive a warning and will be asked if you want to overwrite the existing application.
7. Select Yes or No.
TIP
FactoryTalk View ME software looks for .MER files in the
\Rockwell Software\RSViewME\Runtime folder and font files in the \Rockwell Software\RSViewME\Fonts\ folder.
49
Chapter 4 Configuring the Terminal
Modifying Display Settings
You can access and modify these display settings for your terminal:
•
View display temperature
•
Adjust display contrast
•
Adjust display intensity
•
Configure the screen saver
•
Enable or disable the screen cursor
View the Display Temperature
To view the current temperature of the display, select Terminal
Settings>Display>Display Temperature.
50
The 600 and 1000 terminals have a cold-cathode fluorescent lamp
(CCFL) backlight. This backlight requires temperature control when the internal temperature of the product is below 10 °C (50 °F) or above 60 °C (140 °F). The terminal monitors low and high temperature conditions.
•
If the internal temperature of the product is below 10 °C (50 °F), the backlight is set to overdrive or the full-rated current setting for at least five minutes.
•
If the internal temperature is at or above 60 °C (50 °F), the backlight is set to underdrive; 40% or less of full brightness. This reduces heat generation from the backlight.
Temperature monitoring begins when the terminal powers on, or when the backlight turns on, for example, exiting Screen Saver mode.
The temperature control affects only display intensity; it does not restrict the use or operation of the terminal.
When a low or high temperature condition is detected, an error is sent to the system event log. If the temperature control is not functioning, a noncritical error is sent to the system event log but the terminal continues to operate normally.
TIP
The CCFL backlight temperature control takes precedence over the application Backlight Settings.
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
Adjust the Display Contrast
You can view or modify the display contrast for 400 and 600 grayscale terminals. Displays are shipped with the contrast level set at 50%, which is the optimum setting.
1. Select Terminal Settings>Display>Display Contrast.
2. Press the up an down cursor buttons to adjust the contrast.
The current contrast level is shown as a percentage. The change is not permanent until you press OK.
3. Press OK when done.
Adjust the Display Intensity
You can view or modify the intensity of the terminal backlight. You can use the default intensity of 100% or you can set the intensity for runtime operations.
1. Select Terminal Settings>Display>Display Intensity.
Publication 2711PC-UM001A-EN-P - March 2009
2. Press the Startup Intensity button to switch between the Default intensity and the Runtime intensity.
•
If you choose Runtime, the startup screens will use the runtime intensity.
•
If you choose Default, the startup screens will use the default setting of 100%
3. Increase or decrease the intensity for runtime operations, by pressing the up or down arrow keys.
Intensity changes are not permanent until you press OK.
4. Press OK when done.
51
Chapter 4 Configuring the Terminal
Configure the Screen Saver
The terminal screen saver activates after an idle period using a specific intensity. You can adjust the idle timeout and intensity, disable the screen saver, and enable or disable the screen saver bitmap.
1. Select Terminal Settings>Display>Screen Saver.
52
2. Press the Screen Saver button to select an idle timeout for activating the screen saver.
To disable the screen saver, select the Disabled option.
3. Increase or decrease the brightness intensity of the screen saver by pressing the up and down cursor buttons.
4. Press the Advanced Settings button to access the bitmap option.
•
Select the Screen Saver Image button to enable or disable the screen saver bitmap.
•
Press OK to return to the previous.
5. Press OK to exit and return to the terminal settings.
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
Enable or Disable the Screen Cursor
The terminal has a screen cursor that you can enable or disable.
1. Select Terminal Settings>Display>Cursor.
2. Press the Enable Cursor button to enable or disable the cursor.
3. Press OK to exit and return to Terminal Settings.
Font Linking
List of fonts loaded on the terminal.
Font linking lets you run a translated application on the terminal by linking a font file to the base font, for example, linking a Chinese font file to the base font Arial.
For more details on pre-installed terminal fonts and additional fonts available for downloading, see
.
To link a font file to the base font on the terminal, select Terminal
Settings>Font Linking.
Select Base Font
Arial
Courier New
Tahoma
Times New Roman
Show Links
[F1]
Close
[F8]
Shows the location and name of the font that is linked to the base font used by the terminal. If a file is not linked, box will be empty.
Shows all fonts loaded on the terminal except the base font. Select the name of the font you are linking to the base font. Select the Add Fonts button to link the font file for the selected font to the base font. You will return to the Linked Fonts screen.
Add Linked Font
Courier New
MS Mincho
Tahoma
Times New Roman
Add Fonts
[F1]
Linked Font
Base font = Arial
Link:
MS Mincho
External storage 1\MSMINCHO.TTC
Close
[F8]
Delete Link
[F1]
Edit Link
[F2]
Close
[F8]
Deletes linked font file (if any).
Edits the link by letting you add the linked file to a font loaded on the terminal.
Publication 2711PC-UM001A-EN-P - March 2009
53
Chapter 4 Configuring the Terminal
Configuring the Keypad,
Keyboard, or Mouse
You can configure input devices used with your terminal, including the keyboard, keypad, mouse, and attached keyboard.
Configure Keyboard Settings
You can adjust settings for the keys on the terminal keypad or for keys on an attached keyboard.
1. Select Terminal Settings>Input Devices>Keyboard.
2. Press the Repeat Rate button to specify the number of times a key is repeated per second when you hold a key down.
Valid values for the keypad are 0 and 2…30. The keyboard is device dependent but typical values are the same.
3. Press the Repeat Delay button to select the amount of time that elapses per second before a key is repeated.
Values are device dependent. Unsupported values are dimmed.
4. Press OK when done.
54
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
Configure Keypad Settings for the Terminal
You can restrict multiple or simultaneous key presses on the keypad of your terminal.
1. Select Terminal Settings>Input Devices>Keypad.
Publication 2711PC-UM001A-EN-P - March 2009
2. Press the Single Key Mode button to select a key option.
•
If Enabled, any programmable key that is pressed inhibits all keys until the programmable key is pressed again. This includes the Alt, Ctrl, Shift keys.
•
If Enabled with Abort, any secondary key press will terminate the initial key press immediately.
•
If Disabled, there are no restrictions on key presses. This is the default.
IMPORTANT
The keypad cannot produce Home, End, Page Up or Page
Down when Single Key mode is enabled.
3. Press the Hold Off Time button to enter the length of time, in seconds, to ignore multiple presses of the same key.
4. Press OK when done.
Configure the Sensitivity of the Mouse
You can set and test the sensitivity for both the speed and physical distance between mouse clicks. The process is identical to setting the double-tap sensitivity for the touch screen.
To set the mouse sensitivity, select Terminal Settings>Input
Devices>Mouse.
55
Chapter 4 Configuring the Terminal
Configuring the Touch
Screen
You can configure these operations for terminals with a touch screen:
•
Calibrate the touch screen
•
Enable or disable Cursor
•
Set the double-tap sensitivity
Calibrate the Touch-screen
IMPORTANT
Use a plastic stylus device with a minimum tip radius of 1.3 mm
(0.051 in.) to prevent damage to the touch screen.
Follow these steps to calibrate the touch screen.
1. Select Terminal Settings>Input Devices>Touch
Screen>Calibration.
The screen for calibrating the touch screen appears.
Carefully press and briefly hold stylus on the center of the target.
Repeat at as the target moves around the screen.
2. Touch the center of the target (+) each of the four times it appears on the screen.
When the calibration is complete, you will see this message.
Tap the screen to register saved data. Wait for 30 seconds to cancel saved data and keep the current settings.
3. Tap the screen to save the data or wait 30 seconds to cancel the saved data, retaining the current settings.
56
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
Enable or Disable the Cursor on Touch Screens
You can enable or disable the cursor on terminals with a touch screen. Disabling the cursor will not disable the mouse.
1. Select Terminal Settings>Input Devices>Touch Screen>Cursor.
2. Press the Enable Cursor button to enable or disable the cursor.
3. Press OK.
Set the Double-tap Sensitivity
You can set and test the sensitivity for both the speed and physical distance between touch-screen presses. The process is identical to setting the double-tap sensitivity for the mouse.
1. Select Terminal Settings>Input Devices>Touch
Screen>Double-tap Sensitivity.
Publication 2711PC-UM001A-EN-P - March 2009
2. Double-tap the Set button to set the sensitivity of touch-screen presses.
3. Double-tap the Test button to test the sensitivity of touch-screen presses.
If you double-tap the test button with the time set using the Set button, the Test button will reverse its foreground and background colors.
4. Press OK when done.
57
Chapter 4 Configuring the Terminal
Configuring Print Options
You can configure settings for printing displays, alarm messages, or diagnostic messages from FactoryTalk View ME .MER applications.
The general setup for printing displays and messages is the same, however, the advanced settings are different.
1. Select a Terminal Settings>Networks and Communications>Print
Setup> option.
•
Displays
•
Alarms
•
Diagnostic Messages
58
2. Update properties by selecting the appropriate button and changing the value, if necessary.
Field
PCL Printer
Description
Type of printer to use.
Port
Network Path
Port to use for printing displays, alarm messages, and diagnostic messages.
Network path of printer to use if the Port selection is Network.
Advanced Settings Accesses additional settings.
Valid Values
Laser (default)
Inkjet
Network (default)
USB
519 characters max
3. Press the Advanced button to access additional settings.
The advanced settings for printing displays are:
• print orientation (portrait or landscape).
• draft mode (enable or disable).
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
•
The advanced settings for printing diagnostic and alarm messages determines when to print messages that are sent to the network or USB port.
Print Messages After
Specified number of messages
500 messages or timeout period, whichever is first
Specified number of messages or timeout period, whichever is first.
Default Value Example
60 messages When the queue has 60 messages, the messages are printed regardless of how long they have been in the queue.
You can change the number of messages.
168 hours (7 days) If the queue has 350 messages after 168 hours, the 350 messages are printed.
You can change the timeout period.
60 messages
168 hours (7 days)
If the queue has 60 messages after 24 hours, then the 60 messages are printed.
You can change the number of messages and the timeout period.
For example, the number of messages is set to 75 and the timeout period is set to 48 hours.
•
If the queue has 75 messages after 24 hours, then the 75 messages are printed before the set timeout of 48 hours.
•
If the queue has 15 messages after 48 hours, the 15 messages are printed after the set timeout period.
4. Press OK when done.
5. Press OK to return to Terminal Settings.
Publication 2711PC-UM001A-EN-P - March 2009
59
Chapter 4 Configuring the Terminal
Configuring Startup Options
The action the terminal takes on startup depends on how you configure the startup options. You can:
• disable FactoryTalk View ME Station software.
• go to FactoryTalk View Configure mode.
• run the current application.
Disable FactoryTalk View ME Station Software on Startup
Follow these steps to disable FactoryTalk View Station software on startup.
1. Select Terminal Settings>Startup Options>FactoryTalk View ME
Station Startup.
2. Press the On Startup button until Do not start FactoryTalk View
ME is selected.
3. Press OK.
60
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
Enter Configuration Mode on Startup
Follow these steps to enter Configuration mode on startup.
1. Select Terminal Settings>Startup Options>FactoryTalk View ME
Station Startup.
2. Press the On Startup button to select Go to Configuration Mode.
3. Press the Configuration Mode Options button.
Publication 2711PC-UM001A-EN-P - March 2009
4. Press the Load Current Application button to specify whether you want to load the current application on startup.
5. Press the Replace RSLinx Communications button to specify whether to use the communication configuration of the current application or the terminal on startup.
•
Select No to use the RSLinx configuration of the terminal.
•
Select Yes to use the configuration of the application. The terminal configuration is replaced with the application settings. Any changes to device addresses or driver properties in RSLinx communication will be lost.
6. Press OK to return to the previous screen.
7. Press OK to return to Terminal Settings.
61
Chapter 4 Configuring the Terminal
Run the Loaded Application on Startup
Follow these steps to run the loaded application on startup.
1. Select Terminal Settings>Startup Options>FactoryTalk View ME
Station Startup.
2. Press the On Startup button to select Run Current Application.
62
If an application is not loaded, the options are disabled.
3. Press the Replace RSLinx Communications button to specify what configuration settings to use when running the application.
•
Select No to use the RSLinx configuration of the terminal.
•
Select Yes to use the configuration of the application. The terminal configuration is replaced with the application settings. Any changes to device addresses or driver properties in RSLinx communication will be lost.
4. Press the Delete Log Files to specify what action to take with the log files on startup.
•
Select Yes to delete all log files (data, alarm history, alarm status) generated by the terminal before running application.
The files are deleted from the system default location.
•
Select No to retain all log files.
5. Press OK twice to return to Terminal Settings.
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
Configuring Startup Tests
The terminal can run extended tests on startup. You can select which test to run and also specify test settings on startup.
Select Tests to Run on Startup
Follows these steps to select tests to run on startup.
1. Select Terminal Settings>Startup Options>Startup Tests.
Publication 2711PC-UM001A-EN-P - March 2009
The screen shows a list of each test that can be performed on the terminal at startup and its current On/Off status. You can turn any test in the list on or off by selecting the On/Off button.
The terminal will run tests only with a checked box.
2. Select the tests you want to run on startup.
•
Use the up and down cursor buttons to highlight a test.
•
Press the On/Off button to select a test. A checked box means the test is selected to run. Press the button again to clear the check box.
3. Press OK.
63
Chapter 4 Configuring the Terminal
Configure Startup Test Settings
Follow these steps to specify how many times to run the selected tests on startup and to enable extended diagnostics.
IMPORTANT
Enabling extended diagnostics and setting a high repeat count will increase the time it takes the terminal to reboot.
The tests will run each time you reset or cycle power to the terminal until you disable extended diagnostics. Setting a low repeat count will also decrease the startup time.
1. Select Terminal Settings>Startup Options>Startup Test Settings.
64
2. Press the Repeat Count button to specify the number of times,
0… 128, to run the selected tests on startup.
3. Press the Enable Extended Diagnostics button to enable or disable extended diagnostics on startup.
•
Select Yes to enable extended diagnostics.
•
Select No to disable extended diagnostics.
4. Press OK.
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
Clearing the System Event
Log
The System Event Log screen displays a list of system events logged by the terminal.
Follow these steps to clear all or some of the events from the system event log.
1. Select Terminal Settings>System Event Log.
2. Select an event and then press the More Details button to display system event log details for that event.
3. Press the Clear All button to clear all system event logs.
4. Press OK.
Publication 2711PC-UM001A-EN-P - March 2009
65
Chapter 4 Configuring the Terminal
Displaying Terminal
Information
You can view these details for your terminal:
•
Total power on time
•
Processor temperature
•
Battery voltage and battery state
•
Amount of memory on terminal
Follow these steps to display terminal information.
1. Select Terminal Settings>System>Information>Terminal
Information.
66
All fields are read-only except for memory allocation.
Battery State
Good
Failing
Bad
400 and 600 Terminals
Good battery condition.
Does not have a replaceable battery.
Replace the terminal.
Does not apply.
1000 Terminals
Good battery condition.
Low battery. Replace the battery.
Battery is missing or bad. Replace the battery.
IMPORTANT
For the 400 and 600 terminals, the Battery Voltage indicates the battery state only and the Processor Temperature shows the temperature of the display.
Publication 2711PC-UM001A-EN-P - March 2009
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
2. Press the Memory Allocation button to view or adjust the:
• amount of allocated storage or program memory.
• amount of storage or program memory in use.
3. Press the Up or Down button to increase or decrease the allocation of storage or program memory.
Each button press changes the allocation by a value of four. If you change the allocation for one type of memory, the other is updated accordingly.
IMPORTANT
These settings are not retained after a power cycle. The settings return to the defaults.
4. Press OK to return to previous screen.
5. Press OK to return to terminal settings.
67
Chapter 4 Configuring the Terminal
Displaying
FactoryTalk View ME
Station Information
You can display the firmware number of FactoryTalk View ME Station software and the Rockwell Automation technical support number.
1. Select Terminal Settings>System>Information>About FactoryTalk
View ME Station.
x.xx.xx.x
2. Press the Technical Support button, if desired.
3. Press Close.
68
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
Modifying the Date, Time, or Time Zone
You can adjust the date and time for terminal operations, or change the time zone.
Change the Date
Follow these steps to change the date on the terminal.
1. Select Terminal Settings>Time/Date/Regional Settings>Date.
The current date appears in the Year, Month, and Day fields.
2. Press the Year, Month, and Day buttons to change values.
Field
Year
Month
Description
The current year in a four-digit format.
The current month.
Valid Values
1980…2099
1…12
Day The current day. The day of the month is validated based on the month.
0…31
3. Press OK when done.
Change the Time
Follow these steps to change the time on the terminal.
1. Select Terminal Settings>Time/Date/Regional Settings>Time.
The current time appears in 24-hour format in separate Hour,
Minute, and Second fields.
Publication 2711PC-UM001A-EN-P - March 2009
2. Press the Hour, Minute, and Seconds buttons to change values.
Field
Hour
Minute
Seconds
Description
The current hour in 24-hour format.
The current minute in 24-hour format.
The current second in 24-hour format.
3. Press OK when done.
Valid Values
0…23
0…59
0…59
69
Chapter 4 Configuring the Terminal
Change the Time Zone
You can modify the current time zone on the terminal. Time zones are installed as a part of the operating system. When changing the time zone, the current time and date are adjusted to match the time zone.
Follow these steps to change the time zone.
1. Select Terminal Settings>Time/Date/Regional Settings>Time
Zone.
70
2. Press the up and down cursor buttons to select a time zone.
Language
English
French
German
Japanese
Default Time Zone
(GMT -05:00) Eastern Time (US and Canada)
(GMT +01:00) Brussels, Copenhagen, Madrid, Paris
(GMT +01:00) Amsterdam, Berlin, Bern, Rome, Stockholm, Vienna
(GMT +09:00) Osaka, Sapporo, Tokyo
If the selected time zone supports Daylight Savings, the Daylight
Savings button is available.
3. Press the Daylight Savings button to enable or disable daylight savings for the selected time zone.
Daylight Savings is set to Yes for all time zones except Japanese, which does not support daylight savings. Changes are permanently applied when you close the Time Zone screen.
4. Press the Use Daylight Savings Button to select Yes or No.
5. Click OK when done.
6. Click OK to return to Terminal Settings.
Publication 2711PC-UM001A-EN-P - March 2009
Modifying Regional
Settings
Configuring the Terminal Chapter 4
You can adjust regional settings for a specific language installed on the terminal, including the date, time and numeric formats.
To access regional settings for a language, select Terminal
Settings>Time/Date/Regional Settings>Regional Settings. The current language appears at the bottom of the Regional Settings screen.
Select a Language
You can select a language that is installed on the terminal. Languages are installed as a part of the operating system.
1. Select Terminal Settings>Time/Date/Regional Settings>Regional
Settings>Language.
2. Select a language by pressing the up and down cursor keys.
3. Press OK.
The selected language appears at the bottom of the Regional
Settings screen.
Change the Decimal Separator for Numeric Formats
You can change the decimal separator used in numerics for the current language. The default decimal separator is a period.
1. Select Terminal Settings>Time/Date/Regional Settings>Regional
Settings>Numeric Format.
Publication 2711PC-UM001A-EN-P - March 2009
The field shows the default decimal separator. The field accepts three characters.
2. Enter up to three characters for the new separator.
3. Click OK.
71
Chapter 4 Configuring the Terminal
Change the Time Format
You can change the time format for the selected language.
1. Select Terminal Settings>Time/Date/Regional Settings>Regional
Settings>Time Format.
72
The current time is shown in the currently selected format.
2. Press the appropriate buttons to adjust the formats.
Field
Time Format
Description
h:mm:ss tt (default) h = hour, no leading zero tt = AM or PM symbol hh:mm:ss tt hh = hour with leading zero tt = AM or PM symbol
H:mm:ss
H = hour in 24-hour format, no leading zero
Example
7:23:02 AM or 1:13:31 PM
11:43:59 AM
07:23:02 AM or 01:13:31 PM
11:43:59 PM
7:03:42 or 1:13:32
23:43:59
HH:mm:ss
HH = hour in 24-hour format with leading zero
07:03:42 or 01:13:22
23:43:59
AM Symbol Characters to indicate AM. If the time format is set to h:mm:ss tt or hh:mm:ss tt, you can modify the AM symbol.
PM Symbol Characters to indicate PM. If the time format is set to h:mm:ss tt or hh:mm:ss tt, you can modify the PM symbol.
Separator
AM (default)
12 character max
PM (default)
12 character max
Characters that separate fields in time format.
: (default)
3 character max
3. Click OK.
Publication 2711PC-UM001A-EN-P - March 2009
Configuring the Terminal Chapter 4
Change the Short Date Format
You can change the short date format for the selected language.
1. Select Terminal Settings>Time/Date/Regional Settings>Regional
Settings>Short Date Format.
Publication 2711PC-UM001A-EN-P - March 2009
The current date is shown in the selected, short date format.
Field
Format
Separator
Short Date Formats
M/d/yyyy (default)
M/d/yy
MM/dd/yy
MM/dd/yyyy yy/MM/dd yyyy-MM-dd dd-MMM-yy
Character separator for fields in time format.
The default separator is either - or / depending on short date format.
Example
1/2/2003
1/2/03
01/02/03
01/02/2003
03/01/02
2003-01-02
02-Jan-03
- or / (default)
3 character max
2. Press the Format button to select an available format.
3. Press the Separator button to change the field separator for the date elements.
4. Click OK when done.
73
Chapter 4 Configuring the Terminal
Change the Long Date Format
You can change the long date format used by the selected language.
1. Select Terminal Settings>Time/Date/Regional Settings>Regional
Settings>Long Date Format.
74
The current date is shown in the selected long date format.
2. Press the Long Date Format button to select a date format.
Long Date Formats
dddd, MMMM, dd, yyyy (default) dddd is name of week day
MMMM is name of month dd is two-digit day of month with leading zero yyyy is four-digit year
MMMM dd, yyyy
MMMM is name of month dd is two-digit day of month with leading zero yyyy is four-digit year dddd, dd MMMM, yyyy dddd is name of week day dd is two-digit day of month with leading zero
MMMM is name of month yyyy is four-digit year dd MMMM, yyyy dd is two-digit day of month with leading zero
MMMM is name of month yyyy is four-digit year
Example
Monday, January 01, 2003
January 01, 2003
Monday, 01 January, 2003
01 January, 2003
3. Click OK when done.
Publication 2711PC-UM001A-EN-P - March 2009
Chapter Objectives
Required Tools
Precautions
Installing and Replacing Components
Chapter
5
This chapter shows how to install or replace specific components of the terminals.
•
Battery
•
Backlight
•
External CompactFlash card
•
Product ID label
•
Display module bezel
These tools are required to install and replace components:
•
#00, #1, and #2 Phillips screwdriver
•
Electrostatic Discharge (ESD) wristband
Before installing or replacing any components, disconnect power from the terminal. During installation, take care not to touch any of the exposed electronic components.
WARNING
Disconnect all power from the terminal before installing or replacing any components. Failure to disconnect power may result in electrical shock or damage to the terminal.
ATTENTION
Be careful when touching any of the exposed electronic components to prevent damage from electrostatic discharge
(ESD).
Work in a static free environment and wear a properly grounded ESD wristband.
75 Publication 2711PC-UM001A-EN-P - March 2009
75
Chapter 5 Installing and Replacing Components
Replacing the Battery
The lithium battery in the terminals is used by the real-time clock and static RAM; it is not used for application backup or retention. The clock module has a life expectancy of two years without power.
The replacement battery is catalog number 2711P-RY2032.
WARNING
When you connect or disconnect the battery an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Replace the battery only with the indicated catalog number.
For safety information on the handling of lithium batteries, including handling and disposal of leaking batteries, see
Guidelines for Handling Lithium Batteries, publication AG 5-4 .
Battery Replacement for the 1000 Terminals
This product contains a hermetically sealed lithium battery which may need to be replaced during the life of the product.
At the end of its life, the battery contained in this product should be collected separately from any unsorted municipal waste.
The collection and recycling of batteries helps protect the environment and contributes to the conservation of natural resources as valuable materials are recovered.
Follow these steps to replace the battery in the 1000 terminal.
1. Disconnect power from the terminal.
2. Place the terminal, display side down, on a flat stable surface.
3. Loosen the six captive screws that attach the logic module to the display module.
76
Logic Module
Captive screws on top and bottom.
Publication 2711PC-UM001A-EN-P - March 2009
Installing and Replacing Components Chapter 5
4. Carefully lift the logic module away from the terminal and flip over to expose the circuit board.
ATTENTION
Wear a properly grounded ESD wristband before touching any of the electronic components in the logic module.
5. Locate the battery on the circuit board.
Remove battery by lifting up the edge indicated by arrow.
6. Remove the battery by lifting up the side of the battery.
7. Insert the new battery.
IMPORTANT
Use only catalog number 2711P-RY2032 to replace the battery.
8. Attach the logic module by aligning the two connectors on the bottom of the module with the connectors on the terminal.
Publication 2711PC-UM001A-EN-P - March 2009
9. Push down on the logic module until firmly seated.
10. Tighten the six captive screws that secure the logic module to a torque of 0.58 N•m (5…7 lb•in).
77
Chapter 5 Installing and Replacing Components
Battery Removal for the 400 and 600 Terminals
The lithium battery in the 400 and 600 is non-replaceable and should be removed only at the end of product life.
This product contains a hermetically sealed lithium battery which is permanently connected and should be removed only by trained professionals.
At the end of its life, the battery contained in this product should be collected separately from any unsorted municipal waste.
The collection and recycling of batteries helps protect the environment and contributes to the conservation of natural resources as valuable materials are recovered.
Follow these steps to remove the battery in the 400 and 600 terminals.
1. Disconnect power from the terminal.
2. Place the terminal, display side down, on a flat stable surface.
3. Unlatch the eight retaining tabs (two on each side) on the back cover and remove cover.
4. Locate the yellow battery on the logic board.
5. Remove the battery.
Retaining Tabs
Battery
78
Publication 2711PC-UM001A-EN-P - March 2009
Installing and Replacing Components Chapter 5
Replacing the Backlight
This section shows how to replace the backlight in the 1000 terminal.
The replacement backlight is catalog number 2711P-RL10C2.
IMPORTANT
The backlight contains mercury. At the end of its life, the backlight should be collected separately from unsorted municipal waste.
Follow these steps to replace the backlight.
1. Disconnect power from the terminal.
2. Remove the display module bezel.
3. Remove the four screws that secure the LCD display.
Publication 2711PC-UM001A-EN-P - March 2009
4. Lift the LCD display and detach the display connector from the circuit board.
The circuit board layout may vary for each terminal model.
The location of the connector varies by model.
Display
Connector
5. Detach the backlight connector from the circuit board.
79
Chapter 5 Installing and Replacing Components
6. Press the retaining tab that secures the backlight and then pull out the backlight.
Backlight
Retaining Tab
7. Insert the new backlight.
Backlight
8. Attach the LCD display connector to the circuit board.
Refer to step 4.
9. Attach the backlight connector to the circuit board.
Refer to step 5.
10. Secure the LCD display with the four screws and tighten the screws to a torque of 0.58 N•m (5…7 lb•in).
11. Replace the display module bezel.
80
Publication 2711PC-UM001A-EN-P - March 2009
Using an External
CompactFlash Card
Installing and Replacing Components Chapter 5
All of the terminals have a CompactFlash card slot that supports
Type 1 CompactFlash cards. These cards are available in different memory sizes.
CompactFlash Card Slot
Insert a CompactFlash Card
Insert the card in the CompactFlash card slot of the terminal until firmly seated.
400 and 600 Terminals 1000 Terminals
Publication 2711PC-UM001A-EN-P - March 2009
81
Chapter 5 Installing and Replacing Components
Remove a CompactFlash Card
Press the Eject button on the logic module. When the button pops out, press it again to release the card. The location of the button varies depending on the series of the logic module.
The 400 and 600 terminals do not have an eject button. Simply secure edge of card with fingers and pull card away from slot.
Removing the Product ID
Label
You can replace the label on the terminal with another label.
1. Remove the Allen-Bradley label using your fingers or a tweezers.
82
2. Clean area with damp cloth and isopropyl alcohol.
3. Remove adhesive backing of OEM label and affix over area where label was located.
Publication 2711PC-UM001A-EN-P - March 2009
Replacing the Bezel
Installing and Replacing Components Chapter 5
The 1000 terminal has a touch screen that can only be replaced with the same touch screen. You do not have to remove the logic module before removing the display module bezel.
Follow these steps to remove the display module bezel on the 1000 terminal.
1. Disconnect power from the terminal.
2. Set the terminal, display side down, on a flat stable surface.
ATTENTION
Wear a properly grounded ESD wristband before touching any of the electronic components in the logic module.
3. On touch-screen-only terminals, remove the two screws that secure the small metal plate to the back of the display module.
4. Disconnect the touch screen connector.
Plate
Touch Screen Connector
5. Remove the screws from the back of the display module.
The number of screws varies for each terminal type.
Publication 2711PC-UM001A-EN-P - March 2009
Display Module Bezel
83
Chapter 5 Installing and Replacing Components
6. Remove the sealing gasket.
7. Lift the back of the display module away from the bezel.
Work on a clean, flat, stable surface to protect the display from debris, scratches and damage.
8. Detach the touch screen connector.
9. Set the bezel aside.
Display Module Bezel
84
Publication 2711PC-UM001A-EN-P - March 2009
Cleaning the
Display Window
Installing and Replacing Components Chapter 5
Follow these steps to replace the display module bezel.
1. Make sure the bezel is free of lint and marks.
2. Attach the touch screen connector.
3. Place the back of the display module over the bezel.
Be careful not to pinch any of the cables. Allow the touch screen connector to extend out of the access opening.
4. Connect the touch screen connector.
5. Replace the sealing gasket.
6. Attach the screws that secure the display module to the bezel and tighten to a torque of 1.35…1.58 N•m (12…14 lb•in).
7. Re-attach the small metal plate to the back of the display module using two screws and torque to 0.58 N•m (5…7 lb•in).
Use a protective antiglare overlay for easier cleaning of the display window.
ATTENTION
Use of abrasive cleaners or solvents may damage the display.
Do not scrub or use brushes.
Follow these steps to clean the display window.
1. Disconnect power from the terminal at the power source.
2. Use a clean sponge or soft cloth with a mild soap or detergent to clean the display.
3. Dry the display with a chamois or moist cellulose sponge to avoid water spots.
Remove fresh paint splashes and grease before drying by rubbing lightly with isopropyl alcohol (70% concentration). Afterward, wash using a mild soap or detergent. Rinse with clean water.
Publication 2711PC-UM001A-EN-P - March 2009
85
Chapter 5 Installing and Replacing Components
86
Publication 2711PC-UM001A-EN-P - March 2009
Chapter
6
Terminal Connections
Chapter Objectives
This chapter provides network and device connections for the terminals.
•
Runtime communication cables
•
Communication port isolation
•
USB ports
•
Serial connections on base unit
•
Ethernet (onboard communication)
Cables for Runtime
Communication
The tables provide a summary of terminal connections to controllers and network interface modules for runtime communication.
PanelView Plus Compact Terminals to SLC Controllers
Protocol
DF1
DH-485
EtherNet/IP
PanelView Plus Compact
400, 600, 1000 Comm Port
RS-232 (DF1) Comm port (9-pin)
RS-232 (DH-485) Comm port (9-pin)
EtherNet/IP Comm port
SLC-500, 5/01, 5/02
CH1 RJ45
(DH-485)
N/A
Use AIC+ module
(1761-NET-AIC)
Connect to port 1 or 2
Cables: PanelView Plus Compact Terminals to SLC Controllers
SLC-5/03, 5/04, 5/05
CH0 (9-pin RS-232)
(DF1 or DH-485)
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
SLC 5/03
CH1 (RJ45)
(DH-485)
N/A
Use AIC+ module
(1761-NET-AIC)
Connect to port 1 or 2
SLC 5/04
CH1 (DH+)
N/A
N/A
N/A
Use 1761-NET-ENI module with Ethernet cable
N/A N/A
SLC 5/05
CH1 (ENET)
N/A
N/A
2711P- CBL-EX04 Ethernet crossover cable
(1)
(1)
An EtherNet/IP direction connection between a PanelView Plus Compact terminal and an SLC 5/05 requires hub or crossover cable listed.
Protocol
DF1
DH-485
PanelView Plus Compact Terminals to MicroLogix Controllers
Cables: PanelView Plus Compact to MicroLogix Controllers
PanelView Plus Compact
400, 600, 1000 Comm Port
RS-232 (DF1) Comm port (9-pin)
RS-232 (DH-485) Comm port (9-pin)
EtherNet/IP EtherNet/IP Comm port
MicroLogix 1500LRP
CH1 (9-pin RS-232)
(DF1 or DH-485)
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
MicroLogix 1000, 1200, 1500LSP
CH0 (8-pin Mini DIN)
(DF1 or DH-485)
2711-NC21 (5 m/16 ft)
2711-NC22 (15 m/49 ft)
(null modem not required)
(1)
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
2711-NC21 (5 m/16 ft)
2711-NC22 (15 m/49 ft)
Use 1761-NET-ENI module with Ethernet cable
MicroLogix 1100, 1400
Ethernet Port
N/A
N/A
Ethernet cable
(1)
AIC+ Module recommended for isolation when PanelView and controller are not using same power supply.
87 Publication 2711PC-UM001A-EN-P - March 2009
87
Chapter 6 Terminal Connections
Communication Port
Isolation
PanelView Plus Compact to Logix Controllers
Cables: PanelView Plus Compact to Logix Controllers
Protocol
DF1
DH-485
PanelView Plus Compact
400, 600, 1000 Comm Port
RS-232 (DF1) Comm port (9-pin)
RS-232 (DH-485) Comm port (9-pin)
EtherNet/IP EtherNet/IP Comm port
ControlLogix
CH0 (9-pin RS-232)
(DF1)
N/A
CompactLogix
CH0 (9-pin RS-232)
(DF1 or DH-485)
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
Use 1756-ENET or 1756-ENBT module with Ethernet cable
To 1769-L35E with Ethernet cable
Protocol
DF1
PanelView Plus Compact to Logix Communication Adapters
Cables: PanelView Plus Compact to Communication
Adapters
PanelView Plus Compact
400, 600, 1000 Comm Port
RS-232 Comm port (9-pin)
Port 1 (9-pin)
1761-NET-AIC
Port 2
8-pin Mini DIN
2711-NC21 (5 m/16 ft)
2711-NC22 (15 m/49 ft)
Port 3
(DH-485)
N/A
DH-485 RS-232 Comm port (9-pin)
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
2711-NC21 (5 m/16 ft)
2711-NC22 (15 m/49 ft) N/A
The table summarizes electrical isolation for the communication ports on the PanelView Plus Compact terminals.
Communication Port
RS-232
USB
Ethernet
400 and 600 Terminal
Nonisolated
Nonisolated
Isolated
1000 Terminal
Isolated
Nonisolated
Isolated
88
Publication 2711PC-UM001A-EN-P - March 2009
Terminal Connections Chapter 6
USB Ports
400 and 600 USB Port
4
3
2
1
1000 USB Ports
4
3
2
1
4
3
2
1
The 1000 terminals have two USB ports. The 400 and 600 terminals have one USB port. The terminals support standard USB keyboard and mouse devices (HID devices) with native device drivers. They also support some USB printers that have Printer Control Language
(PCL) capabilities. A vendor specific Windows CE driver is required for all other USB devices.
for a list of compatible USB devices.
Plug the USB device into either one of the two USB ports on the
1000 terminals.
USB Connector Pinout
Pin Signal
1
2
USBVCC
USBD-
3
4
USBD+
USB-GND
WARNING
Do not connect or disconnect the communication cable with power applied to the terminal, or the serial device on the other end of the cable. An electrical arc could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING
USB devices not powered by the USB port must be within the same enclosure and connected to a ground system common with the terminal, or the USB devices must be used with a USB hub that provides galvanic isolation.
If a USB hub is connected to the terminal, an externally powered USB hub is recommended. Before attaching devices to a USB hub, check that the power adapter is connected and powered on.
Publication 2711PC-UM001A-EN-P - March 2009
89
Chapter 6 Terminal Connections
Serial Connections
All compact terminals have a serial RS-232 port that supports:
•
DH-485 communication through a serial connection.
•
DF1 full duplex communication with controllers using direct connections or modem connections.
• third-party point-to-point communication.
• application uploads/downloads.
• printing.
The serial port on the terminals is a 9-pin, male, RS-232 connector.
The table shows the pinout descriptions for this port and how these pins map to the serial ports on the controllers.
PanelView Plus Compact 400 and 600 Terminals
PanelView Plus Compact 1000 Terminal
Serial RS-232 Port
5
9
6
1
Serial RS-232 Port
Serial Port Connector Pinout
PanelView RS-232 Port
9-pin DCE
1
2
3
4
5
6
7
8
9
Connector Shell
RXD
TXD
DTR
COM
DSR
RTS
CTS
Chassis Gnd
SLC
9-pin
PLC
25-pin
2
3
4
5
6
7
8
3
2
20
7
6
4
5
Insert plastic tie wrap in the hole and use as strain relief for all attached cables.
MicroLogix/
DNI 8-pin DIN
4
7
2
The maximum cable length for serial communication is
15.24 m (50 ft).
WARNING
Do not connect or disconnect the communication cable with power applied to the terminal, or the serial device on the other end of the cable. An electrical arc could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
90
Publication 2711PC-UM001A-EN-P - March 2009
Publication 2711PC-UM001A-EN-P - March 2009
Terminal Connections Chapter 6
Modem Connection
Wire or radio modem communication is possible between the terminal and controller. Each modem must support full duplex communication. Refer to your modem user manual for details on settings and configuration.
PanelView Plus Compact Terminal
Optical Isolator
Controller
DF1 Port
Modem
Modem
Construct a Null Modem Cable
To construct a null modem cable, refer to this pinout.
Null Modem Pinout
FG (Frame Ground)
TD (Transmit Data)
RD (Receive Data)
RTS (Request to Send)
CTS (Clear to Send)
SG (Signal Ground)
DSR (Data Set Ready)
DTR (Data Terminal Ready)
PanelView 9-pin
9-pin Modem
-
7
8
3
2
2
3
8
7
5
6
4
5
4
6
PanelView
9-pin
-
25-pin
Modem
1
5
6
4
7
8
3
2
7
20
6
5
4
3
2
FG
RD
TD
CTS
RTS
SG
DTR
DSR
91
Chapter 6 Terminal Connections
Computer Connections
The RS-232 serial port on the base-configured unit of the terminals supports:
• application uploads/downloads using a direct connection.
• printing.
PanelView Plus Compact Terminals
Computer
RS-232 Port
Available Cables
Cat. No. 2711-NC13, 5 m (16.4 ft)
Cat. No. 2711-NC14, 10 m (32.7 ft)
Cat. No. 2706-NC13, 3 m (10 ft)
25-pin to 9-pin
Adapter (if required)
PanelView Port (DCE)
9-pin male
1 NC
2
3
4 NC
5
6 (pulled high to +12V)
7
8
9 NC
RXD
TXD
COM
DSR
RTS
CTS
Computer Port (DTE) with Handshaking
9-pin male
1 DCD
2 RXD (Data Receive)
3 TXD (Data Transmit)
4
5
COM
6 DSR
7 RTS
8 CTS
9 NC
Upload/Download Cable without Hardware Handshaking
PanelView Printer Port
(DCE)
9-pin male
2
RXD
3
TXD
5
COM
Computer Port
(DTE)
9-pin 25-pin
2 3
3
5
2
7
92
Publication 2711PC-UM001A-EN-P - March 2009
Ethernet Connections
Terminal Connections Chapter 6
The Ethernet port on the PanelView terminals supports:
•
EtherNet/IP communication.
• third-party Ethernet communication.
• network connections.
• application uploads/downloads.
• printing.
Ethernet Connector
The terminals have an RJ45, 10/100 Base-T connector for EtherNet/IP or Ethernet TCP/IP network communication.
Ethernet Port
Insert plastic tie wrap in hole and use as strain relief for all attached cables.
The table shows the connector pinouts.
Ethernet Connector Pinout
Pin
Looking into RJ45
Connector
1
8
Pin
1
2
3
4
5
6
7
8
Pin Name
TD+
TD-
RD+
NC
NC
RD-
NC
NC
Shield Connection No Direct Connection
(AC coupled to Chassis GND)
Use point-to-point, 10/100 Base-T cables with cross over pin-outs, such as catalog number 2711P-CBL-EX04, when connecting the
Ethernet port on the terminal directly to:
•
Ethernet port on the controller.
•
10/100 Base-T port on a computer without a switch.
Publication 2711PC-UM001A-EN-P - March 2009
93
Chapter 6 Terminal Connections
Ethernet Cable
For PanelView Plus Compact 1000 terminals use Belden 7921A shielded Ethernet Category 5e cable according to TIA 568-B.1 and
RJ45 connector according to IEC 60603-7 for compliance with the
European Union 89/336/EEC EMC Directive.
The maximum cable length between the terminal’s Ethernet port and a
10/100 Base-T port on an Ethernet hub (without repeaters or fiber) is
100 m (328 ft).
WARNING
Do not connect or disconnect any communication cable with power applied to this device or any device on the network. An electrical arc could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Security Considerations
IGMP (Internet Group Management Protocol) is used for IPv4 multicast. A multicast is communication between a single sender and multiple receivers on a network. IGMP is used to exchange membership status data between IPv4 routers that support multicasting and members of multicast groups. A router is an intermediary device on a communication network that expedites message delivery by finding the most efficient route for a message packet within a network, or by routing packets from one subnetwork to another. A sub-network is a separate part of an organization’s network identified through IP addressing.
PanelView Plus terminals provide level 2 (full) support for IPv4 multicasting (IGMP version 2) as described in RFC 1112 and RFC 2236.
SNMP (Simple Network Management Protocol) is used for internal network management and is not supported.
Ports 137 and 138 are normally open to support the NetBIOS protocol used by Windows CE.NET similar to other Microsoft and IBM network operating systems.
94
Publication 2711PC-UM001A-EN-P - March 2009
Chapter
7
Upgrading Firmware
Chapter Objectives
This chapter shows how to upgrade firmware in a PanelView Plus
Compact terminal using the Firmware Upgrade Wizard.
Transferring Applications
You can transfer applications using a CompactFlash card or a computer.
•
To copy or load applications on the terminal from terminal configuration mode using a CompactFlash card, refer to
on page
.
•
To transfer .MER applications from a computer to the terminals, refer to FactoryTalk View Studio help or documentation.
Firmware Upgrade Wizard
The Firmware Upgrade Wizard (FUW) provides two options for upgrading firmware in a PanelView Plus Compact terminal.
•
Create a firmware upgrade card that you can then load in the
CompactFlash card slot of the terminal to upgrade firmware.
•
Upgrade firmware in a terminal connected to a computer over a direct serial or network connection. The network connection requires a computer running RSLinx Enterprise software.
Preparing Terminal for Upgrade
Before starting the FUW, you need to prepare the terminal for a successful upgrade.
1. Back up all .MER files on the terminal to an external storage card or network.
2. Delete all applications on the terminal.
3. Record Ethernet communication settings, such as IP address, subnet masks, and gateways by selecting Terminal
Settings>Networks and Communications>Network
Connections>Network Adapters>IP Address.
4. Disable the Autostart feature on the terminal by selecting
Terminal Settings>Startup Options>FactoryTalk View ME Station
Startup and select Go to Configuration Mode.
5. Reset the terminal.
95 Publication 2711PC-UM001A-EN-P - March 2009
95
Chapter 7 Upgrading Firmware
Upgrading Firmware with a
CompactFlash Card
Upgrading terminal firmware using a CompactFlash card is a two-step process. First, you create a firmware upgrade card with the necessary firmware files. Second, you load the card in the target terminal to upgrade the firmware.
Create a Firmware Upgrade Card
Follow these steps to create a firmware upgrade card.
1. Launch the Firmware Upgrade Wizard.
•
Select Start>Programs>Rockwell Software>FactoryTalk
View>Tools>ME Firmware Upgrade Wizard.
•
Select Tools>Firmware Upgrade Wizard in FactoryTalk View
Studio software.
2. Select Create firmware upgrade card.
•
In the Firmware card location box, select the destination for the
CompactFlash files, the physical location of the CompactFlash card, for example, E:\ or a folder on the hard drive.
•
From the Existing terminal type pull-down list, select the type of terminal you want to upgrade, then press Next.
96
Publication 2711PC-UM001A-EN-P - March 2009
Upgrading Firmware Chapter 7
Publication 2711PC-UM001A-EN-P - March 2009
3. From the Firmware source folder list, browse to the location of the firmware files.
The default location is shown.
4. From the Upgrade firmware version list, select the firmware version for the upgrade, then press Next.
5. Select the appropriate KEPServer drivers, then click Next.
If no KEPServer drivers are needed, just click Next.
A dialog box shows the target terminal type, upgrade firmware version, and KEPServer drivers that the CompactFlash card firmware will set.
97
Chapter 7 Upgrading Firmware
6. Click Finish to copy the firmware source files to the location specified in step 2.
TIP
If the files were created in a folder on a local hard drive, copy the files to the root directory of the CompactFlash card.
Upgrade Firmware in Terminal with Firmware Upgrade Card
Follow these steps to upgrade the terminal firmware from a
CompactFlash card.
1. Insert the CompactFlash card into the card slot of a powered terminal.
A dialog box indicates the firmware upgrade is about to occur.
98
2. Press Upgrade to begin the firmware upgrade.
IMPORTANT
Do not remove the CompactFlash card while the upgrade is in process.
A dialog box reminds you to back up all .mer and user files before upgrading the terminal.
3. Click Yes if you want to continue with the upgrade.
Publication 2711PC-UM001A-EN-P - March 2009
Upgrading Firmware Chapter 7
A dialog box shows the progress of the upgrade.
Publication 2711PC-UM001A-EN-P - March 2009
4. After the terminal resets twice, the new firmware is installed.
•
On touch-screen terminals, you must calibrate the touch screen after the first terminal reset by selecting pointers in all four corners of the screen and pressing the middle of the screen when prompted.
•
Communication settings are cleared when the terminal is upgraded. If Ethernet communication is used, reconfigure the
Ethernet settings using the values recorded when preparing the terminal for the upgrade. Refer to
IMPORTANT
Ignore this message if it appears during the upgrade.
Machine Edition may be corrupted. Do you want to download firmware?
It means FactoryTalk View Machine Edition has been removed from the terminal to install the upgrade. Do
NOT touch the two buttons that appear with the message. Doing so could render the terminal inoperable.
5. Replace the .MER files that you backed up before starting the upgrade or download a new .MER file to the terminal.
6. Load the .MER file and run the project.
TIP
You can configure your application to start automatically on power cycle by accessing Terminal Settings>Startup
Options in Configuration mode.
99
Chapter 7 Upgrading Firmware
Upgrading Firmware over a
Network Connection
You can upgrade firmware in a terminal that is connected to a computer using a direct serial connection or network connection.
•
Serial connection requires a RAS connection to be set up on computer. During the RAS setup, you select the serial COM port.
This option is used if the computer does not have RSLinx
Enterprise installed or running. The serial connection is not supported on computers running the Windows Vista operating system.
•
Ethernet connection requires that you enter the terminal’s IP
Address.
•
Network connection requires RSLinx Enterprise software running on the computer and the terminal so you can select the terminal on an existing network.
Both the serial and Ethernet connection requires the File Transfer
Utility running on the terminal.
Follow these steps to upgrade terminal firmware over a network using
RSLinx Enterprise software and Ethernet communication.
1. Launch the Firmware Upgrade Wizard.
•
Select Start>Programs>Rockwell Software>FactoryTalk
View>Tools>ME Firmware Upgrade Wizard.
•
Select Tools>Firmware Upgrade Wizard in FactoryTalk View
Studio software.
100
2. Select Upgrade firmware on terminal and click Next.
Publication 2711PC-UM001A-EN-P - March 2009
Upgrading Firmware Chapter 7
A dialog box reminds you to back up all .mer and user files before upgrading the terminal.
3. Click Yes if you want to continue with the upgrade.
4. Select Network connection and click Next.
Use the Ethernet and Serial connections only if the firmware upgrade is unsuccessful.
Publication 2711PC-UM001A-EN-P - March 2009
5. Select the terminal to be upgraded then click Next.
101
Chapter 7 Upgrading Firmware
6. From the Firmware source folder text box, select the location of the firmware files.
The default location is C:\Program Files\Rockwell
Software\RSView Enterprise\FUPs.
7. From the Upgrade firmware version list, select the firmware for the upgrade, then click Next.
102
8. Select the appropriate KEPServer drivers, then click Next.
If no KEPServer drivers are needed, just click Next.
TIP
If the selected FUP file does not support the KEPServer drivers, this dialog box will not appear.
Publication 2711PC-UM001A-EN-P - March 2009
Upgrading Firmware Chapter 7
Publication 2711PC-UM001A-EN-P - March 2009
9. Click Finish to start the upgrade.
10. Click Yes to continue the upgrade process.
If the terminal was properly prepared for the upgrade, no applications should be running.
Firmware files are downloaded to the terminal. This may take several minutes to 15 minutes.
11. When the download is complete, click OK to reset the terminal.
103
Chapter 7 Upgrading Firmware
12. After the terminal resets twice, the new firmware is installed.
•
On touch-screen terminals, you must calibrate the touch screen after the first terminal reset by selecting pointers in all four corners of the screen and pressing the middle of the screen when prompted.
•
Communication settings are cleared when the terminal is upgraded. If Ethernet communication is used, reconfigure the
Ethernet settings using the values recorded when preparing the terminal for the upgrade. Refer to
on page
.
IMPORTANT
Ignore this message if it appears during the upgrade.
Machine Edition may be corrupted. Do you want to download firmware?
It means FactoryTalk View Machine Edition has been removed from the terminal to install the upgrade. Do
NOT touch the two buttons that appear with the message. Doing so could render the terminal inoperable.
13. Replace the .MER files that you backed up before starting the upgrade or download the new .MER files to the terminal.
14. Load the .MER file and run the project.
TIP
You can configure your application to start automatically on power cycle by accessing Terminal Settings>Startup
Options in Configuration mode.
104
Publication 2711PC-UM001A-EN-P - March 2009
Chapter Objectives
Status Indicators
Chapter
8
Troubleshooting
This chapter provides information on how to isolate and correct common operating problems with system components.
•
Status indicators
•
Isolate the problem
•
Startup error messages
•
Startup information messages
•
Startup sequence
•
Check terminal components
•
Ethernet connection
•
Hardware compatibility errors
•
Application does not run
•
Configuration mode access
•
The terminals have two status indicators to isolate operating problems.
•
COMM indicator (green) for communication
•
FAULT indicator (red) for hardware faults
COMM and FAULT Indicators
105 Publication 2711PC-UM001A-EN-P - March 2009
105
Chapter 8 Troubleshooting
Isolating the Problem
106
This section provides general troubleshooting information to assist you when trying to isolate problems.
Check for Adequate Power
A terminal that does not receive adequate power could result in unpredictable behavior. Refer to
Appendix A , Specifications, for
power requirements.
Check Indicators at Startup
After a successful startup, both status indicators on the terminal are off and controlled by the application running on the terminal.
When the terminal starts, the fault (red) indicator should be off except for a few brief flashes, and the comm (green) indicator on.
•
If the indicators on the 1000 terminal remain off, the power supply or logic module has failed. Check the power cable. If the power is not within range, replace the power supply. If the power is within range, replace the logic module.
•
If the indicators on the 400 and 600 terminals remain off, check the power cable.
Indicator States If Terminal Stops During Startup
Fault (Red)
Indicator
Comm
(Green)
Indicator
Off
Description
Blinking
On
(2)
(1)
Blinking
On
Off
Blinking
Last firmware download failed.
Reload firmware using Firmware Upgrade Wizard (FUW) utility.
EBC boot loader firmware failed or is missing.
Reload firmware using Firmware Upgrade Wizard (FUW) utility.
Windows CE OS firmware failed or is missing.
Reload firmware using Firmware Upgrade Wizard (FUW) utility.
Fatal hardware error occurred.
For the 1000 terminals, replace the logic module. For the 400 or
600 terminals, replace the terminal.
Fatal hardware error in display.
For the 1000 terminals, replace the display module. For the 400 or 600 terminals, replace the terminal.
(1)
Blinking red indicates a recoverable error.
(2)
Solid red indicates a nonrecoverable or fatal error.
Check the Startup Messages for Errors
Record any error message that displays during startup. Refer to
Publication 2711PC-UM001A-EN-P - March 2009
Publication 2711PC-UM001A-EN-P - March 2009
Troubleshooting Chapter 8
Check Voltages and Temperatures
To check the battery voltage and processor temperature, enter
Configuration mode and select Terminal Settings>System
Information>Terminal Information.
•
The battery voltage must be at least 2.75V DC. Replace the battery if the voltage is less than 2.75V DC.
•
The CPU temperature should be less than 95 °C.
To check the display temperature, select Terminal Settings>
Display>Display Temperature.
•
The display temperature should be less than 55 °C (131 °F).
If the CPU and display temperatures are higher, check for obstructed airflow in the chassis and attempt to moderate the ambient temperatures within the enclosure and surroundings.
Check the System Event Log
To check the system event log for errors or unexpected reboots, enter
Configuration mode and select Terminal Settings>System Event Log.
Perform Extended Diagnostics
To perform more extensive hardware testing on the 1000 terminal at startup, enter Configuration mode and select Terminal Settings>Startup
Tests>Select Tests.
Select one or more tests to run. Enable extended diagnostics and set the iteration or repeat count. Restart the terminal. The serial port test requires a loopback connector with these connections.
7
8
5
6
9
3
4
1
2
DB9 Connector (female)
N/C
RX
TX
DTR
N/C
DSR
RTS
CTS
N/C
Extended diagnostics are performed at every startup until disabled. A failure will momentarily halt startup and display an error message.
107
Chapter 8 Troubleshooting
Startup Information
Messages
Startup messages display in a specific sequence on the terminal during startup and typically display for a few seconds. These messages indicate the startup sequence of the terminal, but do not require that you perform any action.
Message #
37
(1)
30
1
31.5
2
11
20
(2)
(2)
Displayed Message
Video Initialized
Watchdog Test
RAM Test
Stuck Key
Stuck Touch
Battery Test
Registry Search
Image Search
Downloading Image
External CF
Transfer Image
Internal CF
Description
Configures and initializes the graphics video system.
Tests the watchdog circuitry to verify system integrity.
Tests the RAM memory.
Checks the integrity of the function key hardware.
Checks the integrity of the touch screen hardware.
Checks the integrity of the battery hardware.
Locates and loads the most recent, valid registry. Multiple copies of the registry are maintained. If power is lost during a registry update, a valid registry is available the next time power is applied to the terminal.
Checks for new OS firmware upgrade on the external CompactFlash card and the serial port.
Downloads a new OS firmware upgrade to internal RAM. Message may remain on screen for several minutes.
Transfers a new OS firmware upgrade from the external CompactFlash card to the terminal.
Message may display for several minutes.
Programs the OS firmware just downloaded into RAM. Message may remain on screen for several minutes.
Programs the OS firmware just downloaded into the internal flash memory. Message may display for several minutes.
Checks the integrity of the OS firmware.
Decompresses the compressed OS firmware into RAM.
24
27
(2)
28
29
29.1
CRC Check
Decompress System
Starting System
System Check ###
System Check
Launches the operating system (OS).
Checks internal file system integrity (### is percent progress indicator).
Disables internal file system integrity check. Contact technical support.
(1)
The status number and message displays only on the 100 terminals.
(2)
The status number and message displays only on the 400 and 600 terminals.
108
Publication 2711PC-UM001A-EN-P - March 2009
Troubleshooting Chapter 8
Startup Sequence
This flow chart provides a sequence of startup operations for the terminal and shows system information messages that are displayed on the terminal.
No
Power On
Display copyright message, bootcode versions and Testing... message
Initialize Video - Display 37 Video Initialized (1000 only)
Perform Power On Self Test
Display 30 Watchdog Test
Display 1 RAM Test
Display 31 Stuck Key (1000 only)
Display 31.5 Stuck Touch (1000 only)
Display 32 Battery Test (1000 only)
Display 2.5 Registry Search (1000 only)
Any POST failures?
No
Check for new OS
Display 2 Image Search
Yes
Do serial or external CF card download?
Yes
Serial or CF card Download of OS
Display 11 Download to RAM (400 and 600 only)
Display 50 External CF (1000 only)
Program OS into flash
Display 20 Transfer Image (400 and 600 only)
Display 23 Internal CF (1000 only)
Display Error...
message and HALT
Check OS integrity
Display 24 CRC Check
Decompress OS to RAM
Display 27 Decompress System (400 and 600 only)
Jump to OS
Display 28 Starting System
Perform final system check (1000 only)
Display 29 System Check or
Display 29.1 System Check (if skipping check)
Publication 2711PC-UM001A-EN-P - March 2009
109
Chapter 8 Troubleshooting
Startup Error Messages
When an error occurs, the terminal displays the error number with a text message. The word ERROR! appears under this line in different languages.
# Displayed Message
ERROR! FEHLER! ERREUR! ERRORE!
Error #
1
14
23
24
30
31
31.5
32
(1)
(2)
33.5
40
50
(2)
(2)
(2)
Displayed Message
RAM Test
RAM Header Check
Transfer Image
Download Task
Internal CF
CRC Check
Battery Test
NVRAM Access
Stuck Touch
(2)
Invalid Prod Family
Decompress System
Watchdog Test
Stuck Key
Stuck Touch
EXE Check
External CF
Description
RAM Test failure
OS firmware that is downloading is not compatible with hardware.
Programming the downloaded OS firmware into flash failed.
OS firmware that is downloading to the terminal is too large.
Error programming the new OS firmware to internal CompactFlash.
Checksum of the OS firmware failed.
OS firmware that is downloading is not compatible with terminal.
Recommended Corrective Action
Reset the terminal.
400 and 600: If error persists, replace the terminal.
1000: If error persists, reseat the SO-DIMM RAM module. If error still persists, replace the logic module.
Check that you are using the correct version and type of firmware upgrade. Reset the terminal and upgrade with the correct firmware version.
Reset the terminal and attempt the firmware upgrade again. If error persists, replace the terminal.
Check that you are using the correct version and type of firmware upgrade. Reset the terminal and upgrade with the correct firmware version.
Reload the firmware. If error persists, replace the internal
CompactFlash. If error still persists, replace the logic module.
Reload the firmware.
400 and 600: If error persists, replace the terminal.
1000: If error persists, replace the internal CompactFlash card. If error still persists, replace the logic module.
Check that you are using the correct version and type of firmware upgrade. Reset the terminal and upgrade with the correct firmware version.
Reload the firmware. If error persists, replace the terminal. Error decompressing the OS firmware from flash to RAM.
Watchdog test failure
Function key failure
Touch screen failure
Reload the firmware.
400 and 600: If error persists, replace the terminal.
1000: If error persists, replace the logic module.
Check that nothing is pressed against a key. Reset the terminal without key presses. If error persists, replace display module.
Check that nothing is pressed against the touch screen. Reset the terminal without touch screen presses. If error persists, replace the display module.
Replace the battery. If error persists, replace the logic module.
Battery failure
Nonvolatile memory failure Upgrade the system firmware to revision 3.10.03 or later.
Touch screen failure Check that nothing is pressed against the touch screen. Reset the terminal without touch screen presses. If error persists, replace the terminal.
System OS firmware is missing or corrupt. Reload the firmware.
400 and 600: If error persists, replace the terminal.
1000: If error persists, replace the internal CompactFlash card. If error still persists, replace the logic module.
Error loading the OS firmware from the external CompactFlash card.
Reload the firmware. If error persists, replace the external
CompactFlash card and attempt the firmware upgrade again.
(1)
The error number and message displays only on the 400 and 600 terminals.
(2)
The error number and message displays only on the 1000 terminals.
110
Publication 2711PC-UM001A-EN-P - March 2009
Troubleshooting Chapter 8
Checking Terminal
Components
This section provides tips on how to isolate problems with the terminal display, touch screen, keypad, attached keyboard, or mouse.
Resolve Problems with Display
Symptom
The display is dim or unreadable.
The backlight is turning off or dimming the display unexpectedly.
A startup error appears during startup.
Recommended Action
Check the brightness setting on color displays. Enter Configuration mode and select Terminal Settings>Display>Display Intensity.
Page
Check the contrast setting on grayscale terminals. Enter Configuration mode and select Terminal Settings>Display>Display Contrast.
Check the screen saver settings. Enter Configuration mode and select Terminal
Settings>Display>Screen Saver.
Record the message and check the startup error messages table.
Resolve Problems with Touch Screen
Problem Recommended Action
The touch screen is not operating correctly.
Calibrate the touch screen. Enter Configuration mode and select Terminal
Settings>Input Devices>Touch Screen>Calibration.
The calibration requires four user screen touches. When the touches do not converge to a satisfactory calibration, you are asked repeatedly for additional screen touches; the calibration does not terminate.
Page
The display may not have a touch screen.
The screen cursor is not visible.
The touch screen does not accept touch input.
Touch input and dragging is inaccurate. The touch screen is present and working but requires calibration.
A touch screen that does not calibrate is not present or not functioning properly.
Replace the 1000 display module or the 400 to 600 terminal.
Check the catalog number of the unit. Verify that your terminal has a touch screen by looking at the label on the terminal.
Verify that the cursor is enabled. Enter Configuration mode and select Terminal
Settings>Input Devices>Touch Screen>Cursor.
Attach a USB mouse to check whether the problem is with the touch screen or the application.
•
If the mouse works, but the touch screen does not, the touch driver or touch screen is not functioning properly.
•
If the mouse and touch screen are not working, then the problem is with the application.
Calibrate the touch screen. Enter Configuration mode and select Terminal
Settings>Input Devices>Touch Screen>Calibration.
Publication 2711PC-UM001A-EN-P - March 2009
111
Chapter 8 Troubleshooting
Resolve Problems with Keypad
Problem
The hold-off delay may be longer than expected or multiple key presses might be inhibited by multi-key lockout.
Recommended Action
Check keypad settings. Enter Configuration mode and select Terminal
Settings>Input Devices>Keypad.
Home, End, Page Up or Page Down are not supported when single key or multi-key lockout is enabled.
The keypad is not accepting key input.
Check the key input by attaching a USB keyboard.
•
If the keyboard works but the keypad does not, then the keypad driver or keypad is not working.
•
If both the keypad and keyboard are not working, then the problem may be the application.
Page
Resolve Problems with Mouse
Problem
The mouse is not operating correctly.
The screen cursor may not be visible or the mouse settings may need adjusting.
Recommended Action
Check the USB cable and connection. Detach and reattach the mouse. Cycle power to the terminal.
Check if the screen cursor is disabled. Enter Configuration mode and select
Terminal Settings>Input Devices>Touch Screen>Cursor.
The mouse is a keyboard/mouse USB composite device.
The USB mouse may not be working or noncompliant.
Page
Check the mouse settings. Enter Configuration mode and select Terminal
Settings>Input Devices>Mouse.
Attach a standalone USB mouse.
Replace the USB mouse. Try a different model or manufacturer. If attaching a new mouse resolves the problem, then the old mouse was not working or noncompliant.
Refer to Appendix B for a list of valid USB devices that are compatible with the
terminal.
You can also check the Knowledgebase at the http://support.rockwellautomation.com
site for a list of USB devices that are compatible with the terminal.
112
Publication 2711PC-UM001A-EN-P - March 2009
Troubleshooting Chapter 8
Resolve Problems With Keyboard
Problem
The keyboard does not work.
Keyboard keys may not be enabled as expected.
The keyboard is not accepting key input.
Recommended Action
Check the USB cable and connector. Detach and reattach the keyboard. Verify a good connection. Cycle power to the terminal.
Check for enabled Alt-Ctrl keys. Enter Configuration mode and select Terminal
Settings>Input Devices>Keyboard.
Check the key input using the keypad.
•
If the keypad works but the keyboard does not, the keyboard driver or keyboard is not working.
•
If both the keypad and keyboard are not working, the problem is probably with the application.
Attach a standalone USB keyboard.
Page
The keyboard is a keyboard/mouse USB composite device.
The USB keyboard may not be a compliant device.
Replace the USB keyboard. Try a different model or manufacturer. If a new keyboard resolves the problem, then the old keyboard was probably noncompliant.
Refer to
for a list of valid USB devices that are compatible with the terminal.
You can also check the Knowledgebase at the http://support.rockwellautomation.com
site for a list of USB devices that are compatible with the terminal.
Publication 2711PC-UM001A-EN-P - March 2009
113
Chapter 8 Troubleshooting
Ethernet Connection
This section provides tips on how to isolate Ethernet problems.
•
Check the status indicators at the Ethernet connector.
Green indicates a communication link and should be ON.
Amber indicates data activity and should be flashing. Verify that there is a connection to the hub.
•
Check the cable connections and quality of cable. Check for good connections and things such as quality, crimping, hub connection, and uplink ports.
•
Check the IP Address of the Built-in Ethernet Controller.
Enter Configuration mode and select Terminal
Settings>Networks and Communications>Network
Connections>Network Adapters.
If DHCP is enabled, the device expects a valid IP address to be acquired within a several seconds after startup. The TCP/IP protocol automatically assigns 169.254.nnn.nnn when it fails to acquire an IP address from the server. In general, an IP address that begins with 169 will not support a network connection.
A bad Ethernet connection and the absence of a valid IP address are typically reported in a Communication error message box with the Winsock critical error 10065 - No route to host.
•
Check for conflicting IP addresses. If DHCP is not enabled, make sure the IP address you specify is not in conflict with the address of another device on the network.
•
Check the device name of the terminal. Do not allow devices on the network with same host name. Enter Configuration mode and select Terminal Settings>Networks and Communications>
Network Connections>Device Name.
•
Contact your Network Administrator to check peer or
server settings. The other side of the Ethernet connection may also be a problem.
114
Publication 2711PC-UM001A-EN-P - March 2009
Troubleshooting Chapter 8
Hardware Compatibility
The PanelView Plus Compact 1000 terminal enforces a consistent hardware identity between the logic module and the internal
CompactFlash (CF) card.
If the product identity of the logic module is PanelView Plus Compact
1000 but the CF card is not, this error is generated:
Fatal Error. The internal CF card is not compatible with the PVPlus Compact Logic
Module. The CF card must be replaced to make the terminal usable.
If the product identify of the CF card is PanelView Plus Compact 1000 but the logic module is not, this error is generated:
Fatal Error. The internal PVPlus Compact CF card is not compatible with the Logic
Module. The CF card must be replaced to make the terminal usable.
If either message occurs, power off the terminal and replace the internal CF card with one that has a product identity that matches the product identity of the logic module.
Application Does Not Load
You cannot load a regular Machine Edition application created for a
PanelView Plus terminal on a PanelView Plus Compact terminal. If you do, this dialog box appears:
Publication 2711PC-UM001A-EN-P - March 2009
TIP
You can load a Compact Machine Edition application created for a PanelView Plus Compact terminal on a PanelView Plus terminal.
115
Chapter 8 Troubleshooting
Application Does Not Run
If a compact application does not run on the terminal, there may be a problem with the FactoryTalk View ME application. Verify that a startup screen was configured and that the runtime file is a compatible version.
Configuration Mode Access
To access Configuration mode while an application is running, your
FactoryTalk View ME application must contain a screen with a Goto
Configure Mode button. When the application is running, you can press this button to access Configuration mode.
If a running application does not contain a Goto Configure Mode button, you can access configuration mode during startup.
1. Restart the terminal.
The terminal goes through its startup sequence and will display a white box in the lower left corner of the display.
2. On touch screen terminals, press the white box.
On keypad terminals, press the F1 key.
The terminal enters Configuration Mode.
TIP
If the terminal is configured to enter Configuration mode at startup and does not, then reload the firmware.
116
Publication 2711PC-UM001A-EN-P - March 2009
Electrical
Environmental
Appendix
A
Specifications
Attribute
400 and 600
Input voltage, DC
Power consumption, DC
1000
Input voltage, DC
Power consumption, DC
Attribute
Temperature, operating
Temperature, non-operating
Heat dissipation
400 and 600
1000
Relative humidity
Altitude, operating
Shock, operating
Shock, nonoperating
Vibration
Enclosure Ratings
Value
24V DC nom (18…30V DC)
25 W max (1.0 A at 24V DC)
24V DC nom (18…32V DC)
70 W max (2.9 A at 24V DC),
39 W typical (1.6A @ 24V DC)
Value
0…55 °C (32…131 °F)
-25…70 °C (-13…158 °F)
85 BTU/hr
240 BTU/hr
5…95% without condensation
2000 m (6561 ft)
15 g at 11 ms
30 g at 11 ms
10…57 Hz, 0.012 pk-pk displacement
57…500 Hz, 2 g pk acceleration
NEMA Type 12, 13, 4X (Indoor use only),
IP54, IP65
Publication 2711PC-UM001A-EN-P - March 2009
117
Appendix A Specifications
Display
Mechanical
118
Attribute
Display type
400 and 600 grayscale
400, 600, 1000 color
Value
Grayscale passive matrix, film compensated super-twist nematic (FSTN)
Color active matrix, thin-film transistor (TFT) liquid crystal display (LCD)
Display size, diagonal
400 grayscale
400 color
600
1000
Display area (WxH)
400 grayscale
400 color
600 grayscale and color
1000
Resolution
400 grayscale and 400 color
600
1000
Luminance (typical)
400 grayscale
400 color
600 and 1000 color
Backlight
400
600 and 1000
Touch screen
Actuation rating
Operating force
Keypad function keys
(1)
Actuation rating
Operating force
(1)
Number of function keys varies by terminal size.
3.8 in.
3.5 in.
5.5 in.
10.4 in.
77 x 58 mm (3.0 x 2.3 in.)
71 x 53 mm (2.8 x 2.1 in.)
112 x 84 mm (4.4 x 3.3 in.)
211 x 158 mm (8.3 x 6.2 in.)
320 x 240
320 x 240
640 x 480
120 cd/m
2
Nits
200 cd/m
2
Nits
300 cd/m
2
Nits
LED
CCFL 50,000 hours life, min.
Analog resistive
1 million presses
10…110 g
Function keys, numeric and navigation
1 million presses
340 g
Attribute
Weight, approx.
400 keypad or keypad and touch
600 touch
1000 touch
Dimensions, approx. HxWxD
400 keypad or keypad and touch
600 touch
1000 touch
Value
562 g (1.24 lb)
789 g (1.74 lb)
2.9 kg (6.3 lb)
152 x 185 x 90 mm (6.0 x 7.28 x 3.54 in.)
152 x 185 x 98 mm (6.0 x 7.28 x 3.86 in.)
248 x 329 x 55 mm (9.77 x 12.97 x 2.18 in.)
Publication 2711PC-UM001A-EN-P - March 2009
Specifications Appendix A
General
Attribute
Battery life
400 and 600
1000
Clock
LED indicators
Application flash memory
400 and 600, series B or later
1000
External CompactFlash storage
Value
5 years min. at 25 °C (77 °F)
4 years min. at 25 °C (77 °F)
Battery-backed, +/-2 minutes per month
COMM (Green), Fault (Red)
20 MB
25 MB
512 MB max
Agency Certifications
Certifications
c-UL-us
(1)
Value
UL Listed Industrial Control Equipment, certified for use in
US and Canada. See File E10314.
UL Listed Industrial Control Equipment for use in:
•
Class I, Div 2, Groups A, B, C, D
•
Class II, Div 2 Groups F, G
•
Class III Hazardous Locations
CE (EMC)
CE (LVD)
C-Tick
European Union 2004/108/EC Directive, compliant with:
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
European Union 2006/95/EC Low Voltage Directive, compliant with:
EN 61131-2; Programmable Controllers
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
(1)
See the Product Certification link on http://ab.com for declarations of conformity, certificates, and other certification details.
Publication 2711PC-UM001A-EN-P - March 2009
119
Appendix A Specifications
120
Publication 2711PC-UM001A-EN-P - March 2009
Appendix
B
USB Devices
Compatible USB Devices
The table provides a list of compatible USB devices that can be used on the USB ports of the terminals.
Device
USB Keyboard
Vendor
Rockwell Automation
Ortek
Dell
Rockwell Automation USB
Keyboard/Mouse
USB Mouse
USB Hub
Logitec
Microsoft
Atek
VersaView (Rockwell
Automation)
Belkin
Model
Cat. No. 6189-KBDEPU1U
MCK-600USB
RT7D10
Cat. No. 6189-KBDEPC1U
Optical Mouse - M-BJ58
Intellimouse D58-00026
USB Mouse
USB Mouse
USB 4-Port Hub - ESU021
PanelView Plus
Compact 1000
Yes
Yes
Yes
Yes
PanelView Plus
Compact 400/ 600
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Publication 2711PC-UM001A-EN-P - March 2009
121
Appendix B USB Devices
122
Publication 2711PC-UM001A-EN-P - March 2009
Appendix
C
Available Fonts
The following fonts are pre-installed on the PanelView Plus terminals:
•
True Type fonts (scalable)
– Tahoma.ttf (proportional)
– Courier.ttf (fixed width)
– Arial.ttf (proportional)
•
23 fonts of various sizes migrated from PanelView Standard and
PanelView e terminals (various sizes)
To simplify the creation and downloading of .mer application files on these devices, use the above list of fonts when developing screens in
FactoryTalk View Studio software.
Additional fonts are available in FactoryTalk View Studio software when developing application screens.
•
If the font used to develop screens is not available on the target device, the closest font is selected.
•
If bold or italics is used, and a separate bold or italics font is unavailable, then the target operating system will use an algorithm to produce these affects.
In either case, the device screens will look different than they do in
FactoryTalk View Studio software.
Download Fonts to Terminal
To use additional fonts on a PanelView Plus device, copy any of the font files on the Machine Edition Fonts CD to this directory on the computer where FactoryTalk View Studio software is installed: c:\Documents and Settings\All Users\Documents\RSView Enterprise\ME\Runtime
You can now use the File Transfer Utility in FactoryTalk View Studio software to download the font files to the target device.
1. Select Tools>Transfer Utility.
2. Select Source File>True Type Fonts.
3. Select a font file to download to the device and press the
Download button.
Publication 2711PC-UM001A-EN-P - March 2009
123
Appendix C Available Fonts
Machine Edition Fonts CD
Additional fonts are available on the Machine Edition Fonts CD. This
CD is available from your local distributor by requesting View-SP006.
For more information, refer to the Rockwell Automation
Knowledgebase at http://support.rockwellautomation.com
.
Available Fonts
Arial
Arial (Subset 1_30)
Arial Black
Arial Bold
Arial Bold Italic
Arial Italic
Comic Sans MS
Comic Sans MS
Comic Sans MS Bold
Courier New
Courier New (Subset 1_30)
Courier New Bold
Courier New Bold Italic
Courier New Italic
Georgia
Georgia
Georgia Bold
Georgia Bold Italic
Georgia Italic
Impact
Kino
MSLogo
Symbol
Tahoma
Tahoma (Subset 1_07)
Tahoma Bold
Times New Roman
Times New Roman (Subset 1_30)
Times New Roman Bold
Times New Roman Bold Italic
Times New Roman Italic
Trebuchet MS
Trebuchet MS
Trebuchet MS Bold
Trebuchet MS Bold Italic
Trebuchet MS Italic
File Name
arial_1_30.ttf
arialk.ttf
arialbd.ttf
arialbi.ttf
ariali.ttf
comic.ttf
comicbd.ttf
cour_1_30.ttf
courbd.ttf
courbi.ttf
couri.ttf
georgia.ttf
georgiab.ttf
georgiaz.ttf
georgiai.ttf
impact.ttf
kino.ttf
mslogo.ttf
symbol.ttf
tahoma_1_07.ttf
tahomabd.ttf
times_1_30.ttf
timesbd.ttf
timesbi.ttf
timesi.ttf
trebuc.ttf
trebucbd.ttf
trebucbi.ttf
trebucit.ttf
Size (Bytes)
153,720
117,028
288,496
226,748
207,808
126,364
111,476
162,460
312,920
236,148
245,032
149,628
141,032
159,736
157,388
136,076
28,872
2,500
69,464
123,980
295,432
184,976
334,944
239,692
248,368
69,688
66,444
66,348
72,560
124
Publication 2711PC-UM001A-EN-P - March 2009
Available Fonts Appendix C
Available Fonts
Verdana
Verdana
Verdana Bold
Verdana Bold Italic
Verdana Italic
Webdings
Wingding
Chinese (Simplified) Locale Specific Support
Simsun & NSimSun
Simsun & NSimSun
Simsun & NSimSun (Subset 2_50)
Simsun & NSimSun (Subset 2_60)
Simsun & NSimSun (Subset 2_70)
Simsun & NSimSun (Subset 2_80)
Simsun & NSimSun (Subset 2_90)
SC_Song
Chinese (Traditional) Locale Specific Support
MingLiU & PMingLiU (Choose 1)
MingLiU & PMingLiU
MingLiU & PMingLiU (Subset 2_70)
MingLiU & PMingLiU (Subset 2_80)
MingLiU & PMingLiU (Subset 2_90)
MSMing
Japanese Locale Specific Support
MS Gothic
MS Gothic & P Gothic & UI Gothic
MS Gothic & P Gothic & UI Gothic (Subset 1_50)
MS Gothic & P Gothic & UI Gothic (Subset 1_60)
MS Gothic & P Gothic & UI Gothic (Subset 1_70)
MS Gothic & P Gothic & UI Gothic (Subset 1_80)
MS Gothic & P Gothic & UI Gothic (Subset 1_90)
MS Gothic & P Gothic (Subset 30)
MS Gothic & P Gothic (Subset 30_1_19)
Korean Locale Specific Support
GL_CE
Gulim & GulimChe (Choose 1)
Gulim & GulimChe (Subset 1_30)
Gulim & GulimChe (Subset 1_40)
Gulim & GulimChe (Subset 1_50)
Gulim & GulimChe (Subset 1_60)
File Name
verdana.ttf
verdanab.ttf
verdanaz.ttf
verdanai.ttf
webdings.ttf
wingding.ttf
Size (Bytes)
149,752
137,616
154,800
155,076
118,752
81,000 simsun.ttc
simsun_2_50.ttc
simsun_2_60.ttc
simsun_2_70.ttc
simsun_2_80.ttc
simsun_2_90.ttc
sunfon.ttf
10,500,400
3,051,024
3,578,692
6,975,948
8,116,188
9,066,640
4,686,044 mingliu.ttc
mingliu_2_70.ttc
mingliu_2_80.ttc
mingliu_2_90.ttc
msming.ttf
8,822,400
4,786,488
5,772,700
7,354,808
3,172,552 msgothic.ttc
msgothic_1_50.ttc
msgothic_1_60.ttc
msgothic_1_70.ttc
msgothic_1_80.ttc
msgothic_1_90.ttc
msgothic30.ttc
msgothic30_1_19.ttc
8,272,028
4,456,536
6,057,400
3,795,500
5,438,776
6,408,352
4,197,524
3,304,056 gl_ce.ttf
gulim_1_30.ttc
gulim_1_40.ttc
gulim_1_50.ttc
gulim_1_60.ttc
4,130,084
3,010,268
4,683,896
7,128,756
9,360,100
Publication 2711PC-UM001A-EN-P - March 2009
125
Appendix C Available Fonts
126
Publication 2711PC-UM001A-EN-P - March 2009
A
accessories
antiglare overlays
application
loading .MER
running
B
backlight
brightness
control
replacement
battery replacement
bezel replacement
C
cables
runtime communication cables
catalog numbers
cleaning display
communication
cables
Ethernet
serial
USB ports
configuration mode
accessing
loading application
running application
terminal settings
copying files
applications
font files
D
date
DC power
connecting
ratings
deleting files
applications
font files
log files
DF1
cables
diagnostics
display
troubleshooting
Publication 2711PC-UM001A-EN-P - March 2009
Index
display settings
configuration mode
E
enclosures
Ethernet
cables
connector pinout
port
troubleshooting
external compact flash cards
F
FactoryTalk View ME
firmware upgrade fonts
creating a firmware upgrade card
using a firmware upgrade card
linking
pre-installed
H
hardware
hardware compatibility
hazardous locations
USB port
I
IGMP Protocol
input devices
input panel
installation
ambient temperature
clearances
cutout dimensions
hazardous locations
panel installation 1000 terminal
panel installation 400-600
IP address
K
keyboard
compatibility
mouse compatibility
troubleshooting
keypad
troubleshooting
127
Index
128
L
languages
loading application
M
messages
startup information
mouse
,
compatible
troubleshooting
N
network adapters
network connections
P
power supply, external
power terminal block
print setup
for alarms
for diagnostic messages
for displays
product dimensions
product label
R
resetting terminal
S
serial communication
computer connection
connections
DF1
null modem cable
ports
printing
transferring applications
using a modem
SNMP Protocol
software supported
specifications
agency certifications
display
electrical
environmental
mechanical
startup
error messages
information messages
problem entering configuration mode
sequence
status indicators
support
system
event log
T
terminal information
terminal settings
date
diagnostics
long date format
short date format
system event log
terminal info
time
time format
time zone
time
touch screen
cursor enable
double-tap sensitivity
transferring files
troubleshooting
accessing configuration mode
display module
Ethernet connection
general
hardware compatibility
keyboard
keypad
mouse
startup error messages
startup information messages
status indicators
U
USB devices
USB ports
compatible
connector pinouts
W
wiring and safety guidelines
Publication 2711PC-UM001A-EN-P - March 2009
Rockwell Automation
Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com
, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs.
For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
United States
Outside United
States
1.440.646.3434
Monday – Friday, 8am – 5pm EST
Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States
Outside United
States
Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor in order to complete the return process.
Please contact your local Rockwell Automation representative for the return procedure.
Publication 2711PC-UM001A-EN-P - March 2009
132
Copyright © 2009 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Advertisement
Key Features
- Fixed hardware configuration
- Serial and Ethernet communication only
- Connection to a single logic controller
- Limited number of displays and alarms
- FactoryTalk ViewPoint software is not supported
- Primary HMI for CompactLogix controllers