Below you will find brief information for stepping/servo motor control card STEP 200. The STEP-200 card is a 2-axis command-type stepping motor control card, it also can be used in servo motor control (pulse input type). This card has an embedded CPU which perform motion commands transfered from PC to increase the system performance.
Advertisement
Advertisement
STEP-200 User Manual Version 3.0 02/2001
STEP-200
2-axis stepping/servo motor control card
User Manual
Version 3.0 02/2001 Edition
Driver update : http://www.icpdas.com
Warranty: All products manufactured by ICP DAS are warranted against defective materials for one year from the date of delivery to the original purchaser
Warning: ICP DAS assumes no liability for damage consequent to the use of this product. ICP DAS reserves the right to change this manual at any time without notice. The information furnished by ICP DAS is believed to be accurate and reliable. However, no responsibility is assumed by ICP DAS for it’s use, nor for any infringements of patents or other rights of third parties resulting from it’s use.
Copyright
Copyright 2001 by ICP DAS. All right are reserved
Trademark
The names used for identification only maybe registered trademarks of their respective companies.
http://www.icpdas.com
-1-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
STEP200
2-axis Stepping/Servo Motor Control Card
STEP200 card is a 2-axis command-type stepping motor control card, it also can be used in servo motor control (pulse input type). This card has an embedded CPU which perform motion commands transfered from PC to increase the system performance. A 2Kbytes-FIFO is introduced as command buffer. This buffer can provide 1360ms buffer time. Therefore, STEP200 card is design for windows operation system. STEP200 card provide DOS, windows 95 and windows NT driver, let you have real time motion control solution in windows system.
Features
•
2-axis independent, simultaneous stepping motor control / servo motor control(pulse input type)
•
step rate : 1pps~250Kpps
•
Max. step count : 2
32
−
1
steps
•
DOS, windows 95, windows NT driver
•
embedded CPU
•
command type interface
•
linear, circular interpolation
•
automatic trapezoidal acceleration / deceleration
•
output pulse modes : CW/CCW or pulse / direction
•
output polarity can be programmable
•
2500Vrms optical isolated signal output
•
5 optical isolated digital inputs per axis for limit switches http://www.icpdas.com
-2-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
Contents
1. Introduction
1.1 System Block Diagram
1.2 DDA technology
2. Hardware setup
2.1 Address selection
2.2 Register of STEP200 card
2.3 Hardware configuration
2.3.1 Limit switch configuration
2.3.2 Output pulse mode configuration
2.3.3 Direction configuration
2.3.4 Turn Servo ON/OFF (Hold ON/OFF)
2.3.5 Protection
2.4 Connection
3. Software
3.1 Functions
3.1.1 Loading and unloading driver commands(only for windows)
3.1.2 Setting commands
3.1.3 Stop commands
3.1.4 Simple motion commands
3.1.5 Interpolation commands
3.1.6 Others
3.1.7 New Command
3.2 Start up and end of program
4. Driver
DOS Driver(C,C++)
Windows 95 Driver
Windows NT Driver
5. Example
5.1 DOS example
5.2 Windows example http://www.icpdas.com
-3-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
1. Introduction
1.1 System Block Diagram
STEP200 Stepping motor control card is a micro-computer controlled, 2 axes pulse generation card. It includes a 2Kbytes-FIFO to receive motion command from host PC, a micro-computer for profile generation and protection, two axes DDA chip to execute DDA function when interpolation command is called, 2500Vrms optical isolation inserted for industrial application.
2K FIFO
Interface Buffer
CPU
Profile Generation
Protection
DDA Chip
X-axis
ISA
BUS
CPU Status
DDA Chip
Y-axis
Limit Switch
Input Port
Limit Switch Signal
Limit Switch
Input Port
Figure(1) block diagram of STEP200
Optical
Isolation
Connector
1.2 DDA Technology
The DDA chip is heart of STEP200 card, it will generate equal-space pulse train corresponding to specific pulse number during a DDA period.
This mechanism is very useful to execute pulse generation and interpolation function. The DDA period can be determined by DDA cycle.
Table(1) shows the relation among DDA cycle, DDA period and output pulse rate. When DDA cycle set to 1, the DDA period is equal to 8.192ms.
The output pulse number can be set to 0~2047, therefore the maximum output pulse rate will be 249.877kpps. The minimum output pulse rate is
0.96pps when set DDA cycle=254 (DDA period = 1040.384ms).
DDA period
DDA cycle
X pulse (n=4)
Y pulse (n=12)
Figure(2) DDA mechanism http://www.icpdas.com
-4-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
Table(1) The Relation among DDA cycle, DDA period and output pulse rate.
DDA cycle DDA period
1 8.192ms
Max. pulse rate(n=2047)
249877pps
Min. pulse rate (n=1)
122pps
2
3
12.288ms
16.384ms
166585pps
.
81pps
.
.
N
.
254
.
.
(N+1)*4.096ms
2047/(DDA period)
.
.
1040.384ms
1967pps
.
1/(DDA period)
.
0.96pps
The DDA cycle can be set by MSTEP2_SET_VAR(DDA_cycle, Acc_Dec,
Low_Speed, High_Speed) command which decribed in charpter 3. The selection criterion of DDA cycle describes as following.
(1) The required max. output pulse rate.
PRmax =
V
60 max
*
N
PRmax =
(
DDAcycle
2047
+
1 4 096
ms
PRmax : max. output pulse rate.
Vmax : max. speed (rpm).
N : the pulse number of stepping motor per revolution.
(pulse/rev).
2. The required speed resolution.
The maximum output pulse number is Np(0~2047), therefore the speed resolution is Vmax(max. speed)/Np. The DDA cycle can obtain as following.
PRmax =
(
DDAcycle
Np
+
1 ) * .
ms
3. Large DDA cycle (DDA period), it will occur vibration between different pulse input which generally can be observed during acceleration or deceleration. So, the small DDA cycle , the smooth acceleration/deceleration curve as long as the speed resolution can be acceptable.
Example: Stepping Motor
The specification of stepping motor is 500 pulse/rev, max. speed 500 rpm, speed resolution 2 rpm.
http://www.icpdas.com
-5-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
The required max. pulse rate
PRmax = 500 rpm/60 * 500 = 4166.67 pps
The maximum output pulse
Np = 500rpm/2rpm =250 pulse number
The DDA cycle can be calculated by follow equation
PRmax =
(
DDAcycle
Np
+
1 ) * .
ms
4166.67 =
(
DDAcycle
250
+
1 4 096
ms
DDA cycle = 14
High Speed = 256 pulse (4166.67*15*0.004096)
The above results means that maximum speed is 500rpm when send command MSTEP2_SET_VAR(14, 1, 10, 256) to STEP200 card.
Example: Pulse type input Servo Motor
The specification of servo motor is 4000 pulse/rev, max. speed 3000 rpm, speed resolution 2 rpm.
The required max. pulse rate
PRmax = 3000 rpm/60 * 4000 = 200,000 pps
The maximum output pulse
Np = 3000rpm/2rpm =1500 pulse number
The DDA cycle can be calculated by follow equation
PRmax =
(
DDAcycle
Np
+
1 ) * .
ms
200,000 =
(
DDAcycle
1500
+
1 4 096
ms
DDA cycle = 1
High Speed = 1638 pulse (200,000*2*0.004096)
The above results means that maximum speed is 3000rpm when send command MSTEP2_SET_VAR(1, 5, 20, 1638) to STEP200 card.
http://www.icpdas.com
-6-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
2 Hardware setup
2.1 Address selection
The address is determined by A3~A9, there exist a dip switch on STEP200 card for address selection. The address can be select as following examples. Relatively, this address must be set using
MSTEP2_REGISTRATION( ) command to select STEP200 card. The
MSTEP2_REGISTRATION( ) command has been described in chapter 3.
300H =
0
ON
1
1 2 3 4 5 6 7 8
A3 A4 A5 A6 A7 A8 A9
240H =
0
ON
1
1 2 3 4 5 6 7 8
A3 A4 A5 A6 A7 A8 A9
ON
0
280H =
1
1 2 3 4 5 6 7 8
A3 A4 A5 A6 A7 A8 A9
Figure(3) Address selection
2.2 Register of STEP200 card
There are 4 registers which resided in selected address (base) on
STEP200 card. It includes FIFO register, DI1 register, DI2 register, STS register.
(1) FIFO register (base + 0) (write only)
STEP200 driver will send motion command by way of this register.
Please do not use this register to write any thing, or STEP200 will not operate properly.
(2) DI1 register (base + 0) (read only)
MSB 7 6
/EMG xx
5 4 3 2 1 0 LSB xx /LS14 /LS13 /LS12 /LS11 /ORG1
/ORG1 : original point switch of X-axis, low active.
/LS11, /LS12, /LS13, /LS14 : limit switches of X-axis, low active, which must be configured as next session.
/EMG : emergency switch, low active.
http://www.icpdas.com
-7-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
(3) DI1 register (base + 1) (read only)
MSB 7 6 5 4 3 2 1 0 LSB ystop xstop xx /LS24 /LS23 /LS22 /LS21 /ORG2
/ORG2 : original point switch of Y-axis, low active.
/LS21, /LS22, /LS23, /LS24 : limit switches of Y-axis, low active, which must be configured as next session.
xstop, ystop : These signals indicate the operating situation of X, Y axis in CPU.
1 : busy, 0 : stop
The commands MSTEP2_WAIT_X( ) and MSTEP2_WAIT_Y( ) just to waiting for 'xstop' or 'ystop' signal become to '0'.
(4) STS register (base + 2) (read only)
This register is used for manufacturing and testing.
2.3 Hardware Configuration
2.3.1 Limit switch configuration
Because the profile generation and protection is executed by the CPU on STEP200 card, the limit switches must configure as following diagram.
The motion command just can work properly.
CCW/BW CW/FW
Motor ccm
LS11 ORG1 LS12
/LS11
/ORG1
/LS12
/LS13
/LS14
EXT_GND
/EMG
X axis
Emergency
Figure(4) Limit switch configuration of X axis
LS13 LS14 http://www.icpdas.com
-8-
ICPDAS
STEP-200 User Manual
CCW/BW
Version 3.0 02/2001
CW/FW
Motor ccm
LS21 ORG2 LS22 LS23 LS24
/LS21
/ORG2
/LS22
/LS23
/LS24
EXT_GND
Y axis
Figure(5) Limit switch configuration of Y axis
2.3.2 Output pulse mode configuration
STEP200 card provide two kind output method.
(a) CW/CCW mode
(b) Pulse/Direction mode
The command MSTEP2_SET_MODE( modeX, modeY) provide parameters CW_CCW (0) and PULSE_DIR (1) to define output pulse mode.
Mode = 0 (CW_CCW)
CW
CCW
Pulse
Mode = 1 (PULSE_DIR)
Direction
Figure(6) Output pulse mode
2.3.3 Direction configuration
Sometimes, the output direction of X-axis, Y-axis is undesired direction due to motor connection or gear train. In oder to unify the output direction as shown in Figure(4) and Figure(5). Where CW/FW direction is defined as toward outside from motor, CCW/BW direction is defined as toward inside from motor. MSTEP2_SET_DEFDIR(defdirX, defdirY ) command provide parameters NORMAL_DIR (0) and
REVERSE_DIR (0) to define the rotating direction of motor.
http://www.icpdas.com
-9-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
2.3.4 Turn Servo ON/OFF (Hold ON/OFF)
To turn servo motor into servo ON(OFF) state, or turn stepping motor into hold ON(OFF) state, the command
MSTEP2_SET_SERVO_ON(sonX, sonY) provide parameters ON (1) and OFF (0) to turn ON or OFF.
2.3.5 Protection
STEP200 card is a automatic protected system.
(a) If X-aixs command is executing and moving toward CW/FW direction,
X-axis will immediately stop when LS14 is touched. To release this protection as long as X-axis move toward CCW/BW direction.
(b) If X-aixs command is executing and moving toward CCW/BW direction, X-axis will immediately stop when LS11 is touched. To release this protection as long as X-axis move toward CW/FW direction.
(c) If Y-aixs command is executing and moving toward CW/FW direction,
Y-axis will immediately stop when LS24 is touched. To release this protection as long as Y-axis move toward CCW/BW direction.
(d) If Y-aixs command is executing and moving toward CCW/BW direction, Y-axis will immediately stop when LS21 is touched. To release this protection, as long as Y-axis move toward CW/FW direction.
http://www.icpdas.com
-10-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
2.4 Connection
(1) Pin Assignment of connector CN1
+5V
CW_PULSE2
CCW_DIR2
HOLD2
EXT_VCC
/ORG2
/LS21
/LS22
/LS23
/LS24
CW_PULSE1
CCW_DIR1
HOLD1
/ORG1
/LS11
/LS12
/LS13
/LS14
/EMG
CN1
DB25
DB25/FEMALE/90
19
7
20
8
21
9
22
10
23
11
24
12
25
13
1
14
2
15
3
16
4
17
5
18
6 pin name
CW_PULSE1
CCW_DIR1
HOLD1
CW_PULSE2
CCW_DIR2
HOLD2
/ORG1,
/LS11, /LS12
/LS13, /LS14
/ORG2,
/LS21, /LS22
/LS23, /LS24
/EMG
+5V pin 1 pin 14
GND pin 5 pin 18
EXT_VCC pin 6 pin 19
EXT_GND pin 13 pin 25
EXT_GND
Figure (7) CN1 connector
Table(2) which axis
X
X
X
Y
Y
Y
X can be configure as CW or PULSE pin can be configure as CCW or DIR pin servo ON/OFF or hold ON/OFF signal 1: ON, 0:
OFF can be configure as CW or PULSE pin can be configure as CCW or DIR pin servo ON/OFF or hold ON/OFF signal 1: ON, 0:
OFF orginal point ,limit switches, low active should be configure as Figure(4)
Y original point, limit switches, low active should be configure as Figure(5) emergency switch, low active internal supplied voltage, only used for output pulse. (50mA) don't use for other device internal ground, only used for output pulse.
don't use for other device external power 12V~24V, used for limit switches external ground, used for limit switches http://www.icpdas.com
-11-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
(2) The internal circuit of CW_PULSE, CCW_DIR, HOLD
When output these signal as 1, it can source 15mA(max.).
When output these signal as 0, it can sink 50mA(max.)
+5V
330
CW_PULSE1
CCW_DIR1
HOLD1
CW_PULSE2
CCW_DIR2
HOLD2
Figure(8) internal signal of pulse output connection
(3) The internal circuit of switch connection
EXT_VCC (12V~24V)
4.7K
/ORG1, /LS11, /LS12
/LS13, /LS14
/ORG2, /LS21, /LS22
/LS23, /LS24
/EMG
Figure(9) internal circuit of limit switch connection http://www.icpdas.com
-12-
ICPDAS
STEP-200 User Manual
(3) Examples for connection
Version 3.0 02/2001
1
3
1
3
1
3
+5V
6
5
4
CW_PULSE1
CW +
CW -
1
2
4
3
+5V
6
5
4
CCW_DIR1
CCW +
CCW -
1
2
4
3
+5V
6
5
4
HOLD1
HOLD +
HOLD -
1
2
4
3
GND
DGND
FAN-OUT TYPE (VEXTA) DRIVER
Figure(10) fan-out type driver (VEXTA's motor driver)
1
3
1
3
1
3
+5V
6
5
4
6
5
4
+5V
6
5
4
+5V
DGND
CW_PULSE1
CCW_DIR1
COM
CW/PULSE
CCW/DIR
1
2
1
2
1
2 HOLD1
GND
HOLD
SINK TYPE DRIVER
Figure(11) Sink type driver
4
3
4
3
4
3 http://www.icpdas.com
-13-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
PHOME2
PLS21
PLS22
PLS23
PLS24
5V
CW_PULSE1
CW_PULSE2
CCW_DIR1
CCW_DIR2
HOLD1
HOLD2
GND
EXT_24V
PHOME1
PLS11
PLS12
PLS13
PLS14
PEMG
EXT_GND
16
4
17
5
18
6
19
7
20
8
1
14
2
15
3
21
9
22
10
23
11
24
12
25
13
CN1
DB25
DB25/FEMALE/90
1A+
1A-
1B+
1B-
1C+
1C-
5V
EGND
2A+
2A-
2B+
2B-
2C+
2C-
5V
EGND
3A+
3A-
3B+
3B-
3C+
3C-
5V
EGND
EGND
CN1
DB25
DB25/FEMALE/90
16
4
17
5
18
6
19
7
20
8
1
14
2
15
3
21
9
22
10
23
11
24
12
25
13
Figure (12) The connection between ENCODER3 card and STEP200 card.(for testing) http://www.icpdas.com
-14-
ICPDAS
STEP-200 User Manual
3. Software
Directories
Version 3.0 02/2001
3.1 Functions
Constants
#define ON
#define OFF
#define CW_CCW
#define PULSE_DIR 1
#define NORMAL_DIR 0
#define REVERSE_DIR 1
#define FW 0
1
0
0
#define BW
#define CW
#define CCW
#define X_axis
#define Y_axis
1
0
1
1
2
#define READY 0
#define BUSY 1
STEP200 card is a automatic protected system.
(a) If X-aixs command is executing and moving toward CW/FW direction,
X-axis will immediately stop when LS14 is touched. To release this protection as long as X-axis move toward CCW/BW direction.
(b) If X-aixs command is executing and moving toward CCW/BW direction, X-axis will immediately stop when LS11 is touched. To release this protection as long as X-axis move toward CW/FW direction.
(c) If Y-aixs command is executing and moving toward CW/FW direction,
Y-axis will immediately stop when LS24 is touched. To release this http://www.icpdas.com
-15-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001 protection as long as Y-axis move toward CCW/BW direction.
(d) If Y-aixs command is executing and moving toward CCW/BW direction, Y-axis will immediately stop when LS21 is touched. To release this protection, as long as Y-axis move toward CW/FW direction.
http://www.icpdas.com
-16-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
3.1.1 Loading and unloading driver commands (only for windows)
(1) MSTEP2_INITIAL( )
To load VxD driver.
(2) MSTEP2_END( )
To release VxD driver.
http://www.icpdas.com
-17-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
3.1.2 Setting commands
(3) unsigned char MSTEP2_REGISTRATION(unsigned char cardNo, unsigned int address);
To select the address of board and check it exist or not. 20 STEP-200 boards can be added in one system.
cardNo : board number 0~19.
address : select the address as well as hardware selected in chapter 2.
return NO : board not exist
YES : board exist
Example:
MSTEP2_REGIDTRATION(1, 0x300);
(4) MSTEP2_RESET_SYSTEM( unsigned char cardNo )
to reset STEP-200 card.
cardNo : board number 0~19.
(5) MSTEP2_SET_VAR(unsigned char cardNo, unsigned char DDA_cycle, unsigned char Acc_Dec, unsigned int Low_Speed, unsigned int High_Speed)
to set variable of DDA cycle, accelerating/decelerating speed, low speed and high speed value.
cardNo : board number 0~19.
Acc_Dec
High_Speed
Acc_Dec
Low_Speed
Restriction:
1
≤
1
≤
1
≤
≤
254
≤
200
≤
200
_
≤
_ default value
DDA_cycle = 10
Acc_Dec = 1
Low_Speed = 10
High_Speed = 100
≤
2047 http://www.icpdas.com
-18-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
Example:
MSTEP2_SET_VAR(1, 5, 2, 10, 150); where
DDA_cycle = 5 --> DDA period = (5+1)*4.096ms = 24.576ms
Acc_Dec = 2 --> Acc/Dec speed = 2/(24.576ms)^2 = 3311 p/s^2
Low_Speed = 10 --> low speed = 10/24.576ms = 407pps
High_Speed = 150 --> high speed = 150/24.576ms = 6107pps
(6) MSTEP2_SET_DEFDIR(unsigned char cardNo, unsigned char defdirX, unsigned char defdirY)
Sometimes, the output direction of X-axis, Y-axis is undesired direction due to motor connection or gear train. In oder to unify the output direction as shown in Figure(4) and Figure(5). Where CW/FW direction is defined as toward outside from motor, CCW/BW direction is defined as toward inside from motor. MSTEP2_SET_DEFDIR( ) command provide parameters to define the rotating direction of motor.
cardNo : board number 0~19.
defdirX : X axis direction definition defdirY : Y axis direction definition
0 : NORMAL_DIR
1 : REVERSE_DIR
(7) MSTEP2_SET_MODE(unsigned char cardNo, unsigned char modeX, unsigned char modeY)
STEP200 card provide two kind output method.
modeX : X axis output mode modeY : Y axis output mode
0 : CW_CCW
1 : PULSE_DIR
CW/CCW mode
Pulse/Direction mode
Mode = 0 (CW_CCW)
CW
CCW
Pulse
Mode = 1 (PULSE_DIR)
Direction
Example:
MSTEP2_SET_MODE(1,CW_CCW, PULSE_DIR);
(8) MSTEP2_SET_SERVO_ON(unsigned char cardNo, unsigned char sonX, unsigned char sonY)
To turn servo motor into servo ON(OFF) state, or turn stepping motor into http://www.icpdas.com
-19-
ICPDAS
STEP-200 User Manual hold ON(OFF) state.
sonX : X axis servo/hold on switch sonY : Y axis servo/hold on switch
1 : ON
0 : OFF
Version 3.0 02/2001 http://www.icpdas.com
-20-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
3.1.3 Stop Commands
(9) MSTEP2_STOP_X(unsigned char cardNo)
to stop X axis.
(10) MSTEP2_STOP_Y(unsigned char cardNo)
to stop Y axis.
(11) MSTEP2_STOP_ALL(unsigned char cardNo)
to stop X, Y axis immediatly.
This command will clear commands pending the FIFO, and then send stop
X, Y axis command to achieve immediately stop all axis.
http://www.icpdas.com
-21-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
3.1.4 Simple motion commands
(12) MSTEP2_LSP_ORG(unsigned char cardNo,
unsigned char DIR, unsigned char AXIS)
Low speed move , and stop when ORG1/ORG2 limit switch is touched.
ORG
Low speed
Example:
MSTEP2_LSP_ORG(1, CCW, X_axis);
MSTEP2_LSP_ORG(1, CCW, Y_axis);
(13) MSTEP2_HSP_ORG(unsigned char cardNo, unsigned char DIR,
unsigned char AXIS)
High speed move , and stop when ORG1/ORG2 limit switch is touched.
ORG high speed
Example:
MSTEP2_HSP_ORG(1, CCW, X_axis);
MSTEP2_HSP_ORG(1, CCW, Y_axis);
(14) MSTEP2_HSD_ORG(unsigned char cardNo,
unsigned char DIR, unsigned char AXIS)
High speed move , and slow down to low speed when LS12/LS22 limit switch is touched, and then stop when reach ORG1/ORG2 limit switch.
X axis high speed
LS12 low speed
ORG1 high speed
LS22
Y axis low speed
Example:
MSTEP2_HSD_ORG(1, CCW, X_axis);
ORG2 http://www.icpdas.com
-22-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
MSTEP2_HSD_ORG(1, CCW, Y_axis);
(15) MSTEP2_LSP_PULSE_MOVE(unsigned char cardNo, unsigned char AXIS, long pulseN)
Low speed move #pulseN
#pulseN
Example:
MSTEP2_LSP_PULSE_MOVE(1, X_axis, 20000);
MSTEP2_LSP_PULSE_MOVE(1, X_axis, -2000);
MSTEP2_LSP_PULSE_MOVE(1, Y_axis, 20000);
MSTEP2_LSP_PULSE_MOVE(1, Y_axis, -2000); where when pulseN>0, move toward CW/FW direction when pulseN<0, move toward CCW/BW direction
(16) MSTEP2_HSP_PULSE_MOVE(unsigned char cardNo, unsigned char AXIS, long pulseN)
High speed move #pulseN.
high speed
#pulseN
Example:
MSTEP2_HSP_PULSE_MOVE(1, X_axis, 20000);
MSTEP2_HSP_PULSE_MOVE(1, X_axis, -2000);
MSTEP2_HSP_PULSE_MOVE(1, Y_axis, 20000);
MSTEP2_HSP_PULSE_MOVE(1, Y_axis, -2000); where when pulseN>0, move toward CW/FW direction when pulseN<0, move toward CCW/BW direction
(17) MSTEP2_LSP_MOVE(unsigned char cardNo, unsigned char DIR, unsigned char AXIS)
Low speed move toward direction DIR. It can be stop by
MSTEP2_STOP_X or MSTEP2_STOP_Y or MSTEP2_STOP_ALL command.
Low speed
Example: http://www.icpdas.com
-23-
ICPDAS
STEP-200 User Manual
MSTEP2_LSP_MOVE(1, CW, X_axis);
getch( );
MSTEP2_STOP_X(1);
MSTEP2_LSP_MOVE(1, CCW, Y_axis);
getch( );
MSTEP2_STOP_Y(1);
Version 3.0 02/2001
(18) MSTEP2_HSP_MOVE(unsigned char cardNo, unsigned char DIR, unsigned char AXIS)
High speed move toward direction DIR. It can be stop by
MSTEP2_STOP_X or MSTEP2_STOP_Y or MSTEP2_STOP_ALL command.
high speed
Example:
MSTEP2_HSP_MOVE(1, CW, X_axis);
getch( );
MSTEP2_STOP_X(1);
MSTEP2_HSP_MOVE(1, CCW, Y_axis);
getch( );
MSTEP2_STOP_Y(1);
(19) MSTEP2_CSP_MOVE(unsigned char cardNo, unsigned char dir, unsigned char axis, unsigned int move_speed)
This command will accelerate/decelerate the selected axis’s motor to the
“move_speed”. This command can be continuously send to STEP-200 to dynamicly change speed. The rotating motor can be stop by the command MSTEP2_STOP() or MSTEP2_DEC_STOP().
cardNo : board number 0~9.
axis : selected axis.
1 : X axis
2 : Y axis dir : moving direction.
0 : CW
1 : CCW
0 < move_speed <= 2040 http://www.icpdas.com
-24-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001 move speed
Acc_Dec
Example:
MSTEP2_CSP_MOVE(1, CW, X_axis, 10);
delay(10000);
MSTEP2_CSP_MOVE(1, CW, X_axis, 20);
delay(10000);
MSTEP2_CSP_MOVE(1, CW, X_axis, 30);
delay(10000);
(20) MSTEP2_SLOW_DOWN(unsigned char cardNo, unsigned char AXIS)
to decelerate to slow speed until MSTEP2_STOP_X( ) or
MSTEP2_STOP_Y or MSTEP2_STOP_ALL is executed.
SLOW_DOWN
Example:
MSTEP2_HSP_MOVE(1, CW, X_axis);
getch( );
MSTEP2_SLOW_DOWN(1, X_axis);
getch( );
MSTEP2_STOP_X(1);
(21) MSTEP2_SLOW_STOP(unsigned char cardNo, unsigned char AXIS)
to decelerate to stop.
SLOW_STOP
Example:
MSTEP2_HSP_MOVE(1, CW, Y_axis);
getch( );
MSTEP2_SLOW_STOP(1, Y_axis); http://www.icpdas.com
-25-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
3.1.5 Interpolation commands
(22) MSTEP2_INTP_PULSE(unsigned char cardNo, int Xpulse, int Ypulse)
This command will move a short distance(interpolation short line) in X-Y plane. This command provide user to generate an arbitrary curve in X-Y plane.
Y
(Xpulse,Ypulse)
X
Y
1
2
3 4
5
6 7
8
9
10
X
Restriction:
−
2047
−
2047
≤
≤
# Xpulse
#Ypulse
≤
≤
2047
2047
Example:
MSTEP2_INTP_PULSE(1,20,20);
MSTEP2_INTP_PULSE(1,20,13);
MSTEP2_INTP_PULSE(1,20,7);
MSTEP2_INTP_PULSE(1,20,0);
MSTEP2_INTP_PULSE(1,15,-5);
(23) MSTEP2_INTP_LINE(unsigned char cardNo, long Xpulse, long
Ypulse)
This command will move a long distance(interpolation line) in X-Y plane.
The CPU on STEP200 card will generate a trapezoidal speed profile of Xaxis and Y-axis, and execute interpolation by way of DDA chip.
Y
(Xpulse,Ypulse)
X
(0,0) http://www.icpdas.com
-26-
ICPDAS
STEP-200 User Manual
Restriction:
−
524287
−
524287
Example:
≤
# Xpulse
≤
#Ypulse
≤
≤
524287
524287
MSTEP2_INTP_LINE(1,2000,-3000);
MSTEP2_INTP_LINE(1,-500,200);
Version 3.0 02/2001
(24) MSTEP2_INTP_LONG_LINE(unsigned char cardNo, long x, long y
, unsigned int speed)
This command will move a long interpolation line in X-Y plane. PC will automaticly generate a trapezoidal speed profile of X-axis and Y-axis, and send these profile by way of MSTEP2_INTP_PULSE( ) command.
This command only can be immediately stopped by /EMG switch.
Y
(X,Y)
X
(0,0) speed : 0~2040
Restriction:
−
2
32
+ ≤ ≤
2
32
−
1
−
2
32
+ ≤
# x
# y
≤
2
32
−
1
Example:
MSTEP2_INTP_LONG_LINE(1,20000,-30000);
(25) MSTEP2_CIRCLE(unsigned char cardNo, long x, long y, unsigned
char dir, unsigned int speed)
This command will generate a interpolation circle in X-Y plane. PC will automaticly generate a trapezoidal speed profile of X-axis and Y-axis, and send these profile by way of MSTEP2_INTP_PULSE( ) command.
This command only can be immediately stopped by /EMG switch.
x, y : center point of circle relate to present position.
dir : moving direction.
0 : CW
1 : CCW speed : 0~2040 http://www.icpdas.com
-27-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
Y
(X,Y)
CW
X
CCW where radius = sqrt(X^2 + Y^2)
Restriction:
−
2
32
+ ≤ ≤
2
32
−
1
−
2
32
+ ≤
# x
# y
≤
2
32
−
1
Example:
MSTEP2_INTP_CIRCLE(1,2000,-2000,CW,100);
(26) MSTEP2_ARC(unsigned char cardNo, long x, long y, long R,
unsigned char dir, unsigned int speed)
This command will generate a interpolation arc in X-Y plane. PC will automaticly generate a trapezoidal speed profile of X-axis and Y-axis, and send these profile by way of MSTEP2_INTP_PULSE( ) command.
This command only can be immediately stopped by /EMG switch.
x, y : end point of arc relate to present position.
R : radius of arc.
if R>0 , the arc < 180degree if R<0 , the arc > 180 degree dir : moving direction.
0 : CW
1 : CCW
R
R>0 dir
CW path of curve
'B'
R>0
R<0
R<0
CCW
CW
CCW
'C'
'A'
'D' speed : 0~2040 http://www.icpdas.com
-28-
ICPDAS
STEP-200 User Manual
'A'
CW
Y
'B'
CW
CCW
'C'
(X,Y)
'D'
CCW
Restriction:
−
2
32
+ ≤ ≤
2
32
−
1
−
2
32
+ ≤
# x
# y
≤
2
32
−
1
−
2
32
+ ≤
# R
≤
2
32
−
1
x
2
+
y
2
R
≥
2
Example:
MSTEP2_INTP_ARC(1,2000,-2000,2000,CW,100);
X
Version 3.0 02/2001 http://www.icpdas.com
-29-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
3.1.6 Others
(27) unsigned char MSTEP2_LIMIT_X(unsigned char cardNo)
to request the condition of X-axis limit switches
MSB 7 6
/EMG xx
5 4 3 2 1 0 LSB xx /LS14 /LS13 /LS12 /LS11 /ORG1
/ORG1 : original point switch of X-axis, low active.
/LS11, /LS12, /LS13, /LS14 : limit switches of X-axis, low active, which must be configured as Figure(4).
/EMG : emergency switch, low active.
Example: unsigned char limit1;
limit1 = MSTEP2_LIMIT_X(1);
(28) unsigned char MSTEP2_LIMIT_Y(unsigned char cardNo)
to request the condition of Y-axis limit switches
MSB 7 6 5 4 3 2 1 0 LSB ystop xstop xx /LS24 /LS23 /LS22 /LS21 /ORG2
/ORG2 : original point switch of Y-axis, low active.
/LS21, /LS22, /LS23, /LS24 : limit switches of Y-axis, low active, which must be configured as Figure(5).
Example:
limit2 = MSTEP2_LIMIT_Y(1);
(29) MSTEP2_WAIT_X(unsigned char cardNo)
to wait X-axis going to STOP state.
(30) MSTEP2_WAIT_Y(unsigned char cardNo)
to wait Y-axis going to STOP state.
http://www.icpdas.com
-30-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
3.1.7 New Commands
(31) MSTEP2_SET_NC(unsigned char cardNo, unsigned char sw);
To set all of the following limit switches as N.C.(normal close) or
N.O.(normal open). If set as N.O., those limit switches are active low. If set as N.C., those limit switches are active high. The auto-protection will automatically change the judgement whatever it is N.O. or N.C..
Limit switches: ORG1, LS11, LS12, LS13, LS14, ORG2, LS21, LS22,
LS23, LS24, EMG.
cardNo : card number 0~9.
sw: 0(NO) normal open (default).
1(YES) normal close.
(32) MSTEP2_EMG_STOP(unsigned char cardNo);
This function is the same as MSTEP2_STOP_ALL(), but MSTEP2_
EMG_STOP() only can be used in timer interrupt routine.
cardNo : card number 0~9.
This command will clear all of pending commands in the buffer, and immediately terminate all commands which is executing in STEP-200 board.
(33) MSTEP2_INTP_LINE02(unsigned char cardNo, long x, long y
, unsigned int speed
, unsigned char acc_mode)
(34) MSTEP2_INTP_CIRCLE02(unsigned char cardNo, long x, long y,
unsigned char dir, unsigned int speed,
unsigned char acc_mode)
(35) MSTEP2_INTP_ARC02(unsigned char cardNo, long x, long y, long R,
unsigned char dir, unsigned int speed,
unsigned char acc_mode)
acc_mode: 0: enable acceleration and deceleration profile
1: disable acceleration and deceleration profile
The new driver provide a set of state-machine-type interpolation command including:
MSTEP2_INTP_LINE02
MSTEP2_INTP_CIRCLE02
MSTEP2_INTP_ARC02
These command can be set acc_mode=1 to disable the acceleration and http://www.icpdas.com
-31-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001 deceleration profile.
(36) unsigned char MSTEP2_INTP_STOP()
This command is to compute the interpolation service. It will return
READY(0) for interpolation command completed. And retrun BUSY(1) for not yet complete.
(37) unsigned char MSTEP2_GET_CARD()
This command is used only for DOS in timer interrupt service (10ms) to compute the state-machine-type interpolation command.
These 3 state-machine-type interpolation commands must use
MSTEP2_GET_CARD() (only for windows) and MSTEP2_INTP_STOP() simultaneously. The state-machine-type interpolation commands are only set parameters into the driver. The computing entity is in MSTEP2_GET_CARD()
(only for windows) and MSTEP2_INTP_STOP().
In windows application, when The MSTEP2_GET_CARD() command is running in the timer interrupt routine by 10ms, it will help to calculate the interpolation service.
Both of DOS and windows application, User can directly call the do {} while
(MSTEP2_INTP_STOP()!=READY) to execute the computing entity. The user can monitor something or waiting for keyboard input in the do loop. Therefore,
The user has chance to do the software stop or monitor something.
DOS application example1
MSTEP2_INTP_LINE02(CARD1,1000,1000,100,1); do
{
show_panel();
if (kbhit()) chkey=bioskey(0); //F7=0x4100
} while ( (chkey!= 0x4100) && (MSTEP2_INTP_STOP()!=READY) );
if (chkey==0x4100) MSTEP2_STOP_ALL(CARD1);
DOS application example2
void TimerInterrupt(void)
{
MSTEP2_GET_CARD(CARD1);
show_panel();
if (kbhit()) chkey=bioskey(0); //F7=0x4100 http://www.icpdas.com
-32-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
}
void test_intp(void)
{
MSTEP2_INTP_LINE02(CARD1,1000,1000,100,1); do
{ } while ( (chkey!= 0x4100) && (MSTEP2_INTP_STOP()!=READY) );
if (chkey==0x4100) MSTEP2_STOP_ALL(CARD1);
}
Windows application example1
{
void __fastcall TMSERVO::Timer1Timer(TObject *Sender)
Timer1->Interval = 10; //10ms
MSTEP2_GET_CARD(CARD1);
}
show_panel();
{
void __fastcall TMSTEP::IntpCircleClick(TObject *Sender)
char str[20];
if ( (MSTEP2_IS_X_STOP(CARD1)==NO)
|| (MSTEP2_IS_Y_STOP(CARD1)==NO)
)
{
Application->MessageBox(
"Motor's rotating, can't execute this command",
"Message Box",
MB_DEFBUTTON1);
return;
};
ltoa(x, str, 10);
IntpCircleDialog->Xcenter->Text = AnsiString(str);
ltoa(y, str, 10);
IntpCircleDialog->Ycenter->Text = AnsiString(str);
IntpCircleDialog->SelectDir->ItemIndex = direction;
ltoa(speed, str, 10); http://www.icpdas.com
-33-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
IntpCircleDialog->speed->Text = AnsiString(str);
if (IntpCircleDialog->ShowModal()==mrOk)
{
x= (long)IntpCircleDialog->Xcenter->Text.ToInt();
y= (long)IntpCircleDialog->Ycenter->Text.ToInt();
direction = IntpCircleDialog->SelectDir->ItemIndex;
speed= (unsigned int)IntpCircleDialog->speed->Text.ToInt();
//MSTEP2_CIRCLE(CARD1,x, y, (unsigned char)direction, speed);
MSTEP2_INTP_CIRCLE02(CARD1,x,y,(unsigned char)direction,speed,0);
do {Application->ProcessMessages();}
while (MSTEP2_INTP_STOP()!=READY);
}
} http://www.icpdas.com
-34-
ICPDAS
STEP-200 User Manual
3.2 Start up and end of program
Version 3.0 02/2001
Start up program
When you are going to use STEP200 card, there are some commands must be used firstly.
MSTEP2_INITIAL()
to load vxd driver. DOS application don't need execute this command.
MSTEP2_REGISTRATION(CARD1,0x300)
set CARD1 address, (where CARD1=1)
MSTEP2_RESET_SYSTEM(CARD1);
reset system
MSTEP2_SET_VAR(CARD1, DDA, AD, LSP, HSP);
set DDA cycle, accelerating/decelerating speed, low speed and high speed value
MSTEP2_SET_DEFDIR(CARD1, xdir, ydir);
define direction.
MSTEP2_SET_MODE(CARD1, xmode, ymode);
define output mode.
MSTEP2_SET_SERVO_ON(CARD1, xson, yson);
set servo ON/OFF.
end of program
MSTEP2_RESET_SYSTEM(CARD1);
reset system
MSTEP2_END();
to release VxD driver. DOS application don't need execute this command.
Example
//------------------------------------------------------------------------------
#define CARD1 1 unsigned char DDA,AD; unsigned int LSP,HSP; unsigned char xmode,ymode; unsigned char xdir,ydir; unsigned char xson,yson;
{ void main ()
DDA = 5;
AD = 5;
LSP = 10;
HSP = 120;
xmode = CW_CCW;
ymode = CW_CCW; http://www.icpdas.com
-35-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
xdir = NORMAL_DIR;
ydir = NORMAL_DIR;
xson = ON;
yson = ON;
//--- start up program ---------------------
MSTEP2_INITIAL(); //-- only uesd for windows application
MSTEP2_REGISTRATION(CARD1, 0x300);
MSTEP2_RESET_SYSTEM(CARD1);
MSTEP2_SET_VAR(CARD1, DDA, AD, LSP, HSP);
MSTEP2_SET_DEFDIR(CARD1, xdir, ydir);
MSTEP2_SET_MODE(CARD1, xmode, ymode);
MSTEP2_SET_SERVO_ON(CARD1, xson, yson);
.
.
.
//--- end of program ----------------------------
MSTEP2_RESET_SYSTEM(CARD1);
}
MSTEP2_END(); //-- only uesd for windows application http://www.icpdas.com
-36-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
4. Driver
DOS Driver (C, C++)
Item
Header file
Library file
Example file mstep2.h
mstep2.lib
mtest.prj
File
Windows 95 Driver
Item
Header file
ImportLibrary file
File step32.h
step32.lib
bcstep32.lib (only for Borland C++ series)
Dynamic Link Library step32.dll(copy to c:\windows)
VxD file vportd.vxd(copy to c:\windows)
Example file project1.bpr(Borland C++ Builder) project1.cpp
bbsetp.cpp
Windows NT Driver
Item
Header file
Import Library file
File step32.h
step32.lib
bcstep32.lib (only for Borland C++ series)
Dynamic Link Library step32.dll(copy to c:\winnt)
Driver regdrv.bat
napwnt.ini
napwnt.sys
regini.exe
Example file project1.bpr(Borland C++ Builder) project1.cpp
bbsetp.cpp
The procedure of install NT drivers, to execute regdrv.bat and then re-start computer. The detail of installation, please refer regdrv.bat
http://www.icpdas.com
-37-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
5. Example
5.1 DOS example
The execution file MTEST.EXE is a command testing program, let you can fully understand the action of every command. The source files include
MTEST.PRJ, MAIN.CPP, MSTEP2.h and MSTEP2.LIB. The file MAIN.CPP
provide examples of MSTEP2 command. If you have any question of
MSTEP2 command , you could trace the source file MAIN.CPP.
The pannel of MTEST.EXE has three area :
(1) Limit switch condition area : it indicate the limit switch condition.
(2) Motion parameter area : it shows every variable of motion parameter.
(3) Command area : you can select any command in this area and to execute it.
You can press any key to stop X-axis and Y-axis.
There are three command MSTEP2_INTP_LONG_LINE( ),
MSTEP2_INTP_CIRCLE( ) and MSTEP2_INTP_ARC( ) that only can be immediately stopped by /EMG switch.
2 Axes Stepping Motor Control Card version 0.9 C.C.M.3/15/9
Limit Switch
TPEF
LS11 LS21 TP12 MSTEP2_SET_MODE MSTEP2_CSP_MOVE
LS12 LS22 TP13
LS13 LS23 TP14 /TPG MSTEP2_SET_DIRDEF MSTEP2_SLOW_DOWN
LS14 LS24 TP21 TPG1
FFEF
FFFF XSTP TP23
/EMG YSTP TP24 MSTEP2_STOP_X MSTEP2_LSP_PULSE_MOV
Motion Parameter
DDA cycle = 5 MSTEP2_STOP_Y MSTEP2_HSP_PULSE_MOV
ACC/DEC = 5
Low Speed = 10 MSTEP2_STOP_ALL MSTEP2_INTP_PULSE
High Speed = 120
X output mode= CW/CCW MSTEP2_RESET_SYSTEM MSTEP2_INTP_LINE
Y output mode= CW/CCW
X direction = NORMAL MSTEP2_LSP_ORG MSTEP2_INTP_LONG_LIN
Y direction = NORMAL
X servo on = ON MSTEP2_HSP_ORG MSTEP2_INTP_CIRCL
Y servo on = ON
MSTEP2_HSD_ORG MSTEP2_INTP_ARC
MSTEP2_LSP_MOVE ------ testing -----
Press any key, /EMG, to stop !!
http://www.icpdas.com
-38-
ICPDAS
STEP-200 User Manual Version 3.0 02/2001
5.2 Windows example
The project1.exe (source file included) is a example for ENCODER3 card and STEP200 card. It has windows95 and NT edition.
The pannel of project1.exe has four area :
(1) Limit switch condition area : it indicate the limit switch condition.
(2) Motion parameter area : it shows every variable of motion parameter.
The parameters can be modify directly, then choose the correponding command to send command into STEP200 card.
(3) Command area : you can select any command in this area and to execute it.
(4) The lower-right encoder sub-window shows the address(decimal), counter value and index value. When click the Update Parameters button, it will shows a dialog for selecting the counting mode and times mode.
http://www.icpdas.com
-39-
ICPDAS

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- 2-axis independent, simultaneous stepping motor control / servo motor control
- step rate: 1pps~250Kpps
- Max. step count: 2^32-1 steps
- DOS, windows 95, windows NT driver
- embedded CPU
- command type interface
- linear, circular interpolation
- automatic trapezoidal acceleration / deceleration
- output pulse modes: CW/CCW or pulse / direction
- output polarity can be programmable