drives-ap005 - Rockwell Automation

160 SSC Variable Speed Drive to PowerFlex 4/4M/40 Drives
Conversion Guide
Table of Contents
TABLE OF CONTENTS.................................................................................................................. 2
REFERENCE INFORMATION ........................................................................................................ 3
INTRODUCTION ............................................................................................................................. 3
DRIVE SELECTION CONSIDERATIONS ...................................................................................... 4
C
ONVERSION
G
UIDE
...................................................................................................................... 5
Specifications and Features ................................................................................................... 5
Dimensions ........................................................................................................................... 10
Terminal Comparison............................................................................................................ 11
Communications ................................................................................................................... 13
Software................................................................................................................................ 14
D
RIVE
C
ATALOG
N
UMBERS
.......................................................................................................... 15
DRIVE CONFIGURATION ............................................................................................................ 19
G
ENERAL
N
OTES
......................................................................................................................... 19
ANALOG SPEED FOLLOWER .................................................................................................... 20
3 W
IRE
C
ONTROL
, P
OT
S
PEED
R
EFERENCE
................................................................................. 21
Wiring Examples ................................................................................................................... 21
Parameter Comparison......................................................................................................... 22
2 W
IRE
C
ONTROL
, A
NALOG
I
NPUT
S
PEED
R
EFERENCE
.................................................................. 23
Wiring Examples ................................................................................................................... 23
Parameter Comparison......................................................................................................... 24
PRESET SPEED ........................................................................................................................... 25
Wiring Examples ................................................................................................................... 25
Parameter Comparison......................................................................................................... 26
DEVICENET .................................................................................................................................. 27
G
ENERAL
.................................................................................................................................... 27
S
OFTWARE
V
ERSIONS
................................................................................................................. 27
H
ARDWIRED
D
RIVE
E
NABLE
......................................................................................................... 28
S
AVE
E
XISTING
N
ETWORK
........................................................................................................... 28
C
ONFIGURE
P
OWER
F
LEX
D
RIVE
................................................................................................... 35
C
ONFIGURE
D
EVICE
N
ET
S
CANNER
............................................................................................... 44
E
XAMPLE
L
ADDER
L
OGIC
............................................................................................................. 54
ControlLogix I/O Messaging Examples................................................................................. 57
ControlLogix Explicit Messaging Examples .......................................................................... 67
SLC 500 I/O Messaging Examples....................................................................................... 72
SLC 500 Explicit Messaging Examples ................................................................................ 84
PARAMETER CROSS REFERENCE........................................................................................... 93
2
Reference Information
22A-UM001
22B-UM001
22F-UM001
22COMM-UM003
22COMM-IN001
160-UM002
160-UM009
DNET-UM004P
PowerFlex 4 User Manual
PowerFlex 40 User Manual
PowerFlex 4M User Manual
22-COMM-D DeviceNet Adapter User Manual
22-XCOMM External Comms Installation Manual
160-DN2 Device Net Comms Module User Manual
160-SSC Variable Speed Drive User Manual
DeviceNet Modules in Logix5000 User Manual
Introduction
The purpose of this document is to assist in the retrofit of existing 160 SSC drives to PowerFlex
4-Class drives. The document is broken into four major sections:
Drive Selection
The features of the PowerFlex 4M, 4, and 40 are compared to the 160 SSC. Major differences and in-depth comparison table listed.
Analog Speed Follower
An example of a 160 SSC analog speed follower model is show. Control wiring and parameter comparisons are show for the PowerFlex 4-Class used in this configuration.
Preset
An example of a 160 SSC preset speed model is show. Control wiring and parameter comparisons are show for the PowerFlex 4-Class used in this configuration
DeviceNet
Included in this section are:
- Examples of 160 SSC and PowerFlex 4-Class DeviceNet configurations.
- Procedures to configure the PowerFlex 4-Class drive.
- Procedures configure the DeviceNet scanner are described.
- Examples of ControlLogix and SLC PLC logic.
- Examples of Explicit Messaging in ControlLogix and SLC.
3
Drive Selection Considerations
Selecting a PowerFlex to use as a replacement in a 160 SSC application needs to take into account some of the differences and features between the PowerFlex 4M, 4, and 40. Listed here are some of the major differences in the PowerFlex 4-Class compared to the 160 SSC. The next section has an in-depth comparison of the PowerFlex 4-Class.
Feed through wiring
The 160 SSC has feed through wiring. The line is connected to the top of the drive and motor is connected to the bottom of the drive. The PowerFlex 4M has feed through wiring. The PowerFlex
4 and 40 terminate the line and motor to the bottom of the drive.
DeviceNet
The 160 SSC could have an optional 160-DNx DeviceNet communication module. This enables the 160 SSC to be controlled and monitored on DeviceNet. The PowerFlex 40 accepts an optional 22COMM-D DeviceNet communication module mounted directly in the drive. For the
PowerFlex 4 and 4M to communicate on DeviceNet, a 22COMM-D module is mounted in an external 22XCOMM module and connected to the drives DSI port.
The 160 SSC has configurable Input and Output Assemblies for DeviceNet control of drive. The
PowerFlex has fixed Input and Output Assemblies. Logic changes may have to be made to control the PowerFlex in the same manner.
Speed Presets
The 160 SSC Preset Speed model has eight preset speeds set by three digital inputs. The
PowerFlex 40 has eight preset speeds and the PowerFlex 4 and 4M have four preset speeds.
Sensorless Vector Control
The 160 SSC is a Volts per Hertz drive with adjustments for Boost and Slip Compensation. The
PowerFlex 4 and 4M are Volts per Hertz drives as well. The PowerFlex 40 by default is in
Sensorless Vector control, which achieves a higher level of torque response and speed accuracy.
The PowerFlex 40 can be changed to Volts per Hertz control if need be.
Bipolar Speed Reference
The 160 SSC can accept a Bipolar (+/-10VDC) speed reference. The direction is set by the polarity of the speed reference. This feature is available on the PowerFlex 40 but not the
PowerFlex 4 and 4M.
Circuit Protection
When selecting a PowerFlex replacement for a 160 SSC, pay attention to the recommendations for fusing and circuit breakers. Protective device sizing may be different between equivalent 160
SSC and PowerFlex drives.
More information on the PowerFlex fuse and circuit breaker recommended sizes in the following publications at:
http://literature.rockwellautomation.com
22A-UM001
22B-UM001
PowerFlex 4 User Manual
PowerFlex 40 User Manual
22F-UM001
PowerFlex 4M User Manual
4
Conversion Guide
Specifications and Features
Drive Model 160 SSC
Catalog Number
160-AAxxxx
120V N/A
240V, 1-Phase
240V, 3-Phase
480V
0.5…2 HP
(0.37…1.5 kW)
0.5…5 HP
(0.37…4.0 kW)
0.5…5 HP
(0.37…4.0 kW)
PowerFlex 4M
22F-xxxxxxxx
(0.2…1.1 kW)
0.25…3 HP
(0.2…2.2 kW)
0.25…10 HP
(0.2…7.5 kW)
0.5…15 HP
(0.4…11 kW)
PowerFlex 4
22A-xxxxxxxx
(0.2…1.1 kW)
0.25…3 HP
(0.2…2.2 kW)
0.25…5 HP
(0.2…3.7 kW)
0.5…5 HP
(0.4…3.7 kW)
PowerFlex 40
22B-xxxxxxx
0.5…1.5 HP
(0.4…1.1 kW)
0.5…3 HP
(0.4…2.2 kW)
0.5…10 HP
(0.4…7.5 kW)
0.5…15 HP
(0.4…11 kW)
(0.75…11 kW)
Normal Duty Overload
1 N/A N/A N/A N/A
3 N/A N/A N/A N/A
Heavy Duty Overload
3 Seconds
Power Wiring
200% for 30 Sec.
Feed through
200% for 3 Sec.
Feed through
200% for 3 Sec.
Bottom Fed
200%
Bottom Fed
5
Specifications and Features
(continued)
Drive Model
Catalog Number
160 SSC
160-AAxxxx
PowerFlex 4M
22F-xxxxxxxx
Frequency Control 240 Hz Max.
PWM Frequency 2…8 kHz
Enclosures Types
400 Hz Max
2…10 kHz
Open, Type IP20, Type
12/4/4X IP40/54/65 all
Frames Heatsink Out the Back
Open, Type IP20
PowerFlex 4
22A-xxxxxxxx
240 Hz Max.
2…16 kHz
PowerFlex 40
22B-xxxxxxx
400 Hz Max.
2…16 kHz
Open, Type IP20, Type
1 IP30 (with kit), Type
1/12/4/4X IP40/54/65 all
Frames Heatsink Out the Back
Open, Type IP20, Type
1 IP30 (with kit), Type
1/12/4/4X IP40/54/65 C
Frame Heatsink Out the
Back
Ambient Temp 0
…
50
°
C Open
0
…
40
°
C IP66 (NEMA
12/4/4X)
Torque Control
Open Loop Accuracy N/A
Closed Loop
Accuracy
N/A
Speed Control
Open Loop Accuracy 1% - 40:1
–10
…
50
°
C –10
…
50
°
C –10
…
50
°
C
±2% across 40:1 Speed
Range, with Slip Comp.
±2% across 40:1 Speed
Range, with Slip Comp.
1% across 80:1 Speed
Range, with Slip Comp.
Closed Loop
Accuracy
N/A N/A N/A N/A
HP w/DC Link Choke N/A
HP w/AC line Choke N/A
Volt Tolerance ±10%
Frequency Tolerance 47…63 Hz
N/A
N/A
N/A
N/A
15 Hp
N/A
Compliance Marks CE, UL, cUL, C-Tick
Maximum Altitude 1000 m
6
Specifications and Features
(continued)
Drive Model
Catalog Number
EMC Filtering
Heatsink Out the
Back
160 SSC
160-AAxxxx
External - 1ø,
External - 3ø
Yes, All Frames
PowerFlex 4M
22F-xxxxxxxx
Internal - 1ø & 3ø,
External - 3ø
No
PowerFlex 4
22A-xxxxxxxx
Internal - 1ø,
External - 3ø
Yes, All Frames
PowerFlex 40
22B-xxxxxxx
Internal - 1ø 230V only,
External - 3ø
Yes, All Frames
Internal DB
Transistor
Internal DB Resistor
Option
Encoder Input
Standard
Yes, all Frames C frame only (7.5 HP and higher)
0.5…5 Hp 0.5-15 HP
No N/A N/A N/A
N/A N/A N/A N/A
Additional Feedback
Options
Number of Comms.
Supported
Simultaneously in
Drive
Removable MOV to
Ground
N/A N/A N/A No
1 0 0 1
No Yes Yes Yes
Max. Short Circuit
Rating
Standard Discrete
Inputs
Analog Inputs
Discrete Outputs
Analog Outputs
100,000A 100,000A 100,000A 100,000A
12V Internal Supply only. (Start/Stop function set by Input
Mode)
1 - (Bipolar 0-10 V or
Unipolar 4-20 mA)
1 - Form C Relay
No
5…24V Sink/Source
(3 - Start/Stop/Reverse,
2 - Fully Prog.)
5…24V Sink/Source
(3 - Start/Stop/Reverse,
2 - Fully Prog.)
7…24V Sink/Source
(3 - Start/Stop/Reverse,
4 - Fully Prog.)
1 Unipolar (0-10 V or
4-20 mA)
1 - Form C Relay
No
1 Unipolar (0-10V or
4-20 mA)
1 - Form C Relay
No
1 Bipolar, ±10V or
4-20 mA, 1 Unipolar
4-20mA
1 - Form C Relay,
2-optos
1 - (0-10V or 4-20 mA)
Optional I/O Voltage 115V N/A N/A N/A
Input Timer / Counter
Functions
No No No Yes
Output Timer /
Counter Functions
No No No No
7
Specifications and Features
(continued)
Drive Model
Catalog Number
Digital Input Scan
Time (Not Through
Put Time)
Analog Input
Resolution
160 SSC
160-AAxxxx
10 ms
10 Bit
PowerFlex 4M
22F-xxxxxxxx
2 ms
10 Bit
12 ms Analog Input Scan
Time (Not Through
Put Time)
Analog Output
Resolution
Analog Output Scan
Time (Not Through
Put Time)
8 ms
HIM - Local LCD No
HIM - Remote LCD Yes
HIM - Hand-held
HIM - CopyCat function
HIM - Languages
HIM - Local LED
Yes
Yes
(1) Remote HIM
Yes, including pot and control keys
HIM - Auto/ Manual function
No
PowerFlex 4
22A-xxxxxxxx
2 ms
10 Bit
12 ms
PowerFlex 40
22B-xxxxxxx
1 ms
10 Bit
10 ms
(7) Remote HIM
Yes, including pot and control keys
(7) Remote HIM
Yes, including pot and control keys
(7) Remote HIM
Yes, including pot and control keys
No (Yes - Remote HIM) No (Yes - Remote HIM) No (Yes - Remote HIM)
8
Specifications and Features
(continued)
Drive Model
Catalog Number
160 SSC
160-AAxxxx
PowerFlex 4M
22F-xxxxxxxx
Motor Control Type V/Hz V/Hz
PowerFlex 4
22A-xxxxxxxx
V/Hz
PowerFlex 40
22B-xxxxxxx
V/Hz and Sensorless
Vector
Drive Overload
Protection
Advanced
Diagnostics
Input Phase Loss
User Sets
Yes Yes Yes Yes
No
No
No
Process Control
Loop
Fast Flux Up
Feedback Loss
Switchover
Battery Back-up
Yes No No PID
No
Fast Brake to Stop No
Flux Braking No
No
No
Multi-Motor
Parameters
No
Drive Model
Catalog Number
160 SSC
160-AAxxxx
SynchLink No
Motion Controller No
Inertia Adaptation No
Power Up Time 0.8 Sec.
PowerFlex 4M
22F-xxxxxxxx
1.5…2.5 Sec.
PowerFlex 4
22A-xxxxxxxx
1.5…2.5 Sec.
PowerFlex 40
22B-xxxxxxx
1.5…2.5 Sec.
P-jump (traverse function)
No
Lifting Application No
Winder Application No
Electronic
Gearing/Line Shaft
No
9
Dimensions
160 SSC PowerFlex 4M
Frame/Hp
Height
mm
Width
mm
Depth
mm
Frame/Hp
Height
mm
Width
mm
Depth
mm
A/0.5…3 152 80 165.4 A/0.5…2 174 72 136
B/5 192.5 92 193.3 B/3…5 174 100 136
C/7.5…10 130
PowerFlex 4
Frame/HP
Height
mm
Width
mm
Depth
mm
PowerFlex 40
Frame/HP
Height
mm
Width
mm
Depth
mm
10
Terminal Comparison
Terminal Designation
Description
Input AC Line – R/L1
Input AC Line – S/L2
Input AC Line – T/L3
Motor – U/T1
Motor – V/T2
Motor – W/T3
Brake Resistor
Brake Resistor
160 SSC
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
BR+
BR–
DC Bus –
DC Bus +
DC Bus Inductor Connection
DC Bus Inductor Connection
DC–
DC+
PowerFlex 4M
R/L1
S/L2
T/L3
U/T1
PowerFlex 4
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
V/T2
W/T3
BR+ (C Frame only) BR+
BR– (C Frame Only) BR–
DC–
DC+
P2 (C Frame Only
P1 (C Frame Only
PowerFlex 40
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
BR+
BR–
DC–
DC+
P2 (C Frame Only)
P1 (C Frame Only)
Analog Input 1 Comm.
Analog Input 1 (+/–)
3
2 - (0…10V)
14
13
14
13
14
13
Shield 19
Analog Input 2 Comm. 3
Analog Input 2 (+/-)
Analog Input 3 (NTC-) Com.
4 - (4…20 mA)
Analog Input 3 (NTC+)
Shield
Analog Output 1 (–)
Analog Output 1 (+)
Analog Output 2 (–)
Analog Output 2 (+)
Encoder A (Not)
Encoder B (Not)
Encoder Z (Not)
11
Terminal Comparison
(continued)
Terminal Designation
Description
160 SSC PowerFlex 4M PowerFlex 4 PowerFlex 40
24V DC Common (–)
24V DC Source (+)
7
Digital/Relay Output 1(N.O) 11
Digital/Relay Output 1Com. 10
Digital/Relay Output 1(N.C) 9
Digital/Relay Output 2 (N.O)
Digital/Relay Output 2 Com.
Digital/Relay Output 2 (N.C)
Digital/Relay Output 3 (NC)
Digital/Relay Output 3 Com.
Digital/Relay Output 3 (NO)
Digital/Relay Output 4 (NC)
Digital/Relay Output 4 Com.
Digital/Relay Output 4 (NO)
R3
11
R1
R2
R3
11
R1
R2
18
R3
17
11
R1
R2
Digital Input 4-6 Comm.
Digital Input 4
Digital Input 5
4
5
6
4
5
6
4
5
6
48V Control Power Supply
Drive Enable (Secure
Disable Function)
Enabled could be terminal #8 terminal #1
12
Communications
Product Model Number
DF1
AS-i
160 SSC
Yes
PowerFlex 4M
Yes (with SCM adapter)
PowerFlex 4
Yes (with SCM adapter)
PowerFlex 40
Yes (with SCM adapter)
No No No No
BACnet No Yes (with X-Comm) Yes
CANopen No No No No
CC-Link No No No No
ControlNet No Yes (with X-Comm) Yes (with X-Comm) Yes
DeviceNet Yes Yes (with X-Comm) Yes (with X-Comm) Yes
Ethernet No No No No
EtherNet/IP No Yes (with X-Comm) Yes (with X-Comm) Yes
FIP No No No No
Interbus Yes No No No
LonWorks No Yes (with X-Comm) Yes (with X-Comm) Yes
Modbus RTU No Yes (Standard) Yes (Standard) Yes (Standard)
PROFIBUS DP Yes Yes (with X-Comm) Yes (with X-Comm) Yes
PROFINET No No No No
SERCOS No No No No
Uni-Telway No No No No converter)
Yes (with USB converter)
Yes (with USB converter)
13
Software
Software Versions
Connectivity
Select Features
Used With …
Full version
'Lite' version
Pocket PC version
Palm version
Serial Point-to-Point
Serial Multi-drop
Ethernet Direct
ControlNet
DeviceNet
Profibus DP
Bluetooth
WiFi
Other / Proprietary
Offline capability
Setup Wizards
Diagram Views
User-created Views
I/O Terminal Configuration
Control
Oscilloscope / Graph
Project Management
Flash
File Conversion Tool
On-line Help
Multi-language
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes (freeware)
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
Yes
Yes
Yes
English only
PowerFlex 7-Class, PowerFlex 4-
Class, 160(with DF1 160-RS1 adapter)
14
Drive Catalog Numbers
Following are part number explanations for the 160 SSC, PowerFlex 4M, PowerFlex 4, and
PowerFlex 40.
160 SSC Catalog Number
More information on the 160 SSC in the following publication at:
http://literature.rockwellautomation.com
160-UM009 160-SSC Variable Speed Drive User Manual
15
PowerFlex 4 Catalog Number
More information on the PowerFlex 4 in the following publication at:
http://literature.rockwellautomation.com
22A-UM001 PowerFlex 4 User Manual
16
PowerFlex 4M Catalog Number
More information on the PowerFlex 4M in the following publication at:
http://literature.rockwellautomation.com
22F-UM001 PowerFlex 4M User Manual
17
PowerFlex 40 Catalog Number
More information on the PowerFlex 40 in the following publication at:
http://literature.rockwellautomation.com
22B-UM001 PowerFlex 40 User Manual
18
Drive Configuration
The 160 SSC drive will be an Analog Speed Follower or a Preset Speed module and possibly have a DN2 DeviceNet option module. Because of this, the following examples put the 160 SSC to PowerFlex conversions into three broad categories:
Analog Speed Follower
Preset Speed
DeviceNet
The remainder of this document is broken into these three sections.
General Notes
The points apply to the PowerFlex drive whether it’s being used as an Analog Speed Follower,
Preset Speed, or DeviceNet
SNK/SRC DIP Switch
The PowerFlex digital inputs can operate in Sink or Source. To replicate 160 SSC functionality, the SNK/SRC DIP Switch is set to SRC so digital devices are applying a
+24VDC to inputs.
PowerFlex +24VDC power
The PowerFlex drive digital I/O has the ability to use internal or external +24VDC supply.
To replicate the wiring of the 160 SSC, the wiring diagrams will show the PowerFlex drive using internal +24VDC supply.
Motor Rotation
The output phasing of a 160 SSC series A and B drive is different than the output phasing of a 160 SSC series C and PowerFlex. Replacing a 160 SSC series A or B with a PowerFlex using the same U, V, and W (T1, T2, and T3) connections will reverse the motor rotation. To keep the same direction of rotation, switch any 2 of the output wires connected to U, V, or W (T1, T2, or T3) to the motor.
19
Analog Speed Follower
The 160 SSC Analog Speed Follower model accepts a speed reference from a potentiometer, +/-
10VDC source, 0-10VDC source, or 4-20 mA source. The 160 SSC can be configured to accept various methods of Start/Stop/Direction control.
Three examples show the 160 SSC configured to use different speed reference inputs and
Start/Stop/Direction control and equivalent PowerFlex configurations.
20
3 Wire Control, Pot Speed Reference
The control method is 3 Wire Start/Stop/Direction (Factory Default). The speed reference for the
160 SSC Analog Speed Follower comes from a 10K Ohm 2W potentiometer wired to the drive’s
10VDC power supply.
Wiring Examples
21
Parameter Comparison
The following parameters are the minimum required to configure the PowerFlex for the motor attributes and to control it with a 3 Wire Start/Stop/Direction method. The table shows a cross reference to the 160 SSC parameters.
NOTE: This example uses a 5HP, 460VAC, 6.0FLA, 60Hz motor. PowerFlex Parameters 31, 32,
33, 34, and 35, are dependant on your motor and application. PowerFlex Parameters 37, 39, and
40 are dependant on your applications stop mode and Accel/decel rates.
No.
160 SSC analog
Parameter Value
PowerFlex 40
No. Parameter Value
36
35
42
32
33
46
34
59
74
Base Voltage
Base Frequency
Motor OL Current
Minimum Frequency
Maximum Frequency
Input Mode
Stop Mode Select
Frequency Select
Analog Select
460 V
60 Hz
6.0 A
0 Hz
60 Hz
0 – 3 Wire Control
0 - Ramp to Stop
0 – TB3 Freq Input
0 - Unipolar
31
32
33
34
35
36
Motor NP Volts
Motor NP Hertz
Motor OL Current
Minimum Frequency
Maximum Frequency
Start Source
37
38
Stop Mode
Speed Reference
123 Analog Select
460 V
60 Hz
6.0 A
0 Hz
60 Hz
1 – 3 Wire
0 – Ramp CF
2 – 0-10V Input
0 - Unipolar
30 Accel Time 1 10.0 Sec 39 Accel Time 1 10.0 Sec
31 Decel Time 1 10.0 Sec 40 Decel Time 1 10.0 Sec
160 SSC Notes:
- Changing the Input Mode requires a power cycle or an entry of “2” Reset Input Mode on
Parameter 56.
PowerFlex Notes:
- By default the PowerFlex 40 is in Sensorless Vector control mode. It can be changed to
Volts/Hertz with Parameter 125.
- The ENBL jumper on the PowerFlex 40 determines the Stop Mode. If the jumper is installed the Stop Mode is as programmed in Parameter 37. If the jumper is removed the stop is always a Coast Stop.
- Parameter 123 Analog Select is available on the PowerFlex 40 only. PowerFlex 4M and 4 are Unipolar only.
22
2 Wire Control, Analog Input Speed Reference
The control method is 2 Wire Run Fwd/Run Rev. The speed reference for the 160 SSC Analog
Speed Follower comes from a 4-20mA, 0-10VDC or +/-10VDC(PowerFlex 40 only) input. The
Stop Pushbutton shown in the examples is not required. The drives run while a Run Fwd or Run
Rev input is on. To eliminate the Stop Pushbutton connect terminal 7 and 8 on the 160 SSC and terminal 1 and 11 on the PowerFlex.
Wiring Examples
23
Parameter Comparison
The following parameters are the minimum required to configure the PowerFlex for the motor attributes and to control it with a 2 Wire Run Fwd/Run Rev method. The table shows a cross reference to the 160 SSC parameters.
NOTE: This example uses a 5HP, 460VAC, 6.0FLA, 60Hz motor. PowerFlex Parameters 31, 32,
33, 34, and 35, are dependant on your motor and application. PowerFlex Parameters 37, 39, and
40 are dependant on your applications stop mode and Accel/decel rates.
160 SSC analog PowerFlex 40
No. Parameter Value No. Parameter Value
36 Base Voltage 460 V 31 Motor NP Volts 460 V
35 Base Frequency 60 Hz 32 Motor NP Hertz 60 Hz
42 Motor OL Current 6.0 A 33 Motor OL Current 6.0 A
32 Minimum Frequency 0 Hz 34 Minimum Frequency 0 Hz
33 Maximum Frequency 60 Hz 35 Maximum Frequency 60 Hz
46 Input Mode 1 – 2 Wire Control 36 Start Source 2 – 2 Wire
34 Stop Mode Select 0 - Ramp to Stop 37 Stop Mode 0 – Ramp CF
59 Frequency Select 0 – TB3 Freq Input 38 Speed Reference 2 – 0-10V Input
74 Analog Select 0 - Unipolar 123 Analog Select 0 - Unipolar
30 Accel Time 1 10.0 Sec 39 Accel Time 1 10.0 Sec
31 Decel Time 1 10.0 Sec 40 Decel Time 1 10.0 Sec
160 SSC Notes:
- Changing the Input Mode requires a power cycle or an entry of “2” Reset Input Mode on
Parameter 56
- If Parameter 46 set to “1” 2 Wire Control the drive will ramp to stop if terminal 8 is open. If
Parameter 46 set to “5” 2 Wire Control With Enable the drive will coast stop if terminal 8 is open
PowerFlex Notes:
- By default the PowerFlex 40 is in Sensorless Vector control mode. It can be changed to
Volts/Hertz with Parameter 125.
- The ENBL jumper on the PowerFlex 40 determines the Stop Mode. If the jumper is installed the Stop Mode is as programmed in Parameter 37. If the jumper is removed the stop is always a Coast Stop if terminal 8 is open.
- Parameter 123 Analog Select is available on the PowerFlex 40 only. PowerFlex 4M and 4 are Unipolar only.
- In this mode of operation, Parameter 37 controls the stop mode when the Run Fwd or
Run Rev switch is opened
- Parameter 38 should be set to “3” 4-20 mA Input if using 4-20mA speed reference.
24
Preset Speed
The control method is 2 Wire Run Fwd/Run Rev. The speed reference for the 160 SSC Preset
Speed model is selected with 3 digital inputs. The 160 SSC and PowerFlex 40 are capable of eight preset speeds and the PowerFlex 4M and 4 are capable of four preset speeds.
Wiring Examples
25
Parameter Comparison
The following parameters are the minimum required to configure the PowerFlex for the motor attributes and to control it with a 2 Wire Run Fwd/Run Rev method. The table shows a cross reference to the 160 SSC parameters.
NOTE: This example uses a 5HP, 460VAC, 6.0FLA, 60Hz motor. PowerFlex Parameters 31, 32,
33, 34, and 35, are dependant on your motor and application. PowerFlex Parameters 37, 39, and
40 are dependant on your applications stop mode and Accel/decel rates.
160 SSC preset PowerFlex 40
31
61
62
63
64
65
66
32
33
46
34
59
30
No. Parameter
36 Base Voltage
35
42
Base Frequency
Motor OL Current
Minimum Frequency
Maximum Frequency
Input Mode
Stop Mode Select
Frequency Select
Accel Time 1
Value
460 V
60 Hz
6.0 A
0 Hz
60 Hz
1 – 2 Wire Control
0 - Ramp to Stop
1 – Internal
10.0 Sec
Decel Time 1
Preset Freq 0
Preset Freq 1
Preset Freq 2
Preset Freq 3
Preset Freq 4
Preset Freq 5
10.0 Sec
3.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
30.0 Hz
40.0 Hz
40
70
71
72
73
74
75
34
35
36
37
38
39
No. Parameter
31 Motor NP Volts
32
33
Motor NP Hertz
Motor OL Current
Minimum Frequency
Maximum Frequency
Start Source
Stop Mode
Speed Reference
Accel Time 1
Value
460 V
60 Hz
6.0 A
0 Hz
60 Hz
2 – 2 Wire
0 – Ramp CF
4 – Preset Freq
10.0 Sec
Decel Time 1
Preset Freq 0
Preset Freq 1
Preset Freq 2
Preset Freq 3
Preset Freq 4
Preset Freq 5
10.0 Sec
0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
30.0 Hz
40.0 Hz
67
68
Preset Freq 6
Preset Freq 7
50.0 Hz
60.0 Hz
76
77
51
52
Preset Freq 6
Preset Freq 7
Digital In 1 Sel
Digital In 2 Sel
50.0 Hz
60.0 Hz
4 – 2 Preset Freq
4 – 2 Preset Freq
53 Digital In 3 Sel 4 – 2 Preset Freq
160 SSC Notes:
- Changing the Input Mode requires a power cycle or an entry of “2” Reset Input Mode on
Parameter 56
- If Parameter 46 set to “1” 2 Wire Control the drive will ramp to stop if terminal 8 is open. If
Parameter 46 set to “5” 2 Wire Control With Enable the drive will coast stop if terminal 8 is open
PowerFlex Notes:
- By default the PowerFlex 40 is in Sensorless Vector control mode. It can be changed to
Volts/Hertz with Parameter 125.
- The ENBL jumper on the PowerFlex 40 determines the Stop Mode. If the jumper is installed the Stop Mode is as programmed in Parameter 37. If the jumper is removed the stop is always a Coast Stop if terminal 8 is open.
- In this mode of operation, Parameter 37 controls the stop mode when the Run Fwd or
Run Rev switch is opened.
- The PowerFlex 40 has eight speed presets and the PowerFlex 4M and 4 have four speed presets. Parameters 74-77 and 53 are not on PowerFlex 4M or 4.
26
DeviceNet
General
A 160 SSC with a DN2 DeviceNet option can be replaced with a PowerFlex 4/4M or PowerFlex
40 Drive. The PowerFlex 4/4M drive requires a 22-XCOMM base and a 22-COMM-D communication adapter to connect the DSI port to DeviceNet. The PowerFlex 40 drive requires a
22-COMM-D communication adapter and adapter cover (22B-CCB or 22B-CCC) to communicate on DeviceNet.
The intent of the following procedure is to “Replace” the 160 SSC with a new PowerFlex drive.
The new PowerFlex drive will occupy the 160 SSC’s address on DeviceNet, Input/Output space in the DeviceNet scanner, and use the control logic in the PLC.
The following are the steps to replace a 160 SSC with a PowerFlex.
• Save existing network configuration. Save the network prior to replacing the 160 SSC.
Print a report for reference. The network configuration containing the 160 SSC needs to be referenced for PowerFlex drive and Scanner configuration.
• Install and configure new PowerFlex drive. Edit the PowerFlex drive parameters for motor size and control over DeviceNet.
• Configure DeviceNet Scanner. Use existing 160 SSC Input/Output mapping in Scanner for PowerFlex Input/Output.
• Edit PLC logic. Control logic for the 160 SSC needs to be edited because the Command and Status for the PowerFlex may be different. Examples for ControlLogix, and SLC are given.
Software Versions
RSNetworx for DeviceNet is used to configure the DeviceNet and the PowerFlex drive.
RSNetworx v7.00 or higher is recommended. RSNetworx v 9.00 was used for this document.
27
Hardwired Drive Enable
When the 160 SSC is being controlled over DeviceNet, hardwired devices wired to the Start,
Direction, or Stop are not required. However, when Parameter 46 (Input Mode) is set to 2
(Network Control), Terminal TB3-8 is configured as an Enable. Terminal TB3-8 has to be high to start or run. Terminal TB3-8 may be jumped to TB3-7 Common or connected through a hardware enable circuit such as a guard or safety circuit.
This function can be replicated with the PowerFlex 4/4M and the PowerFlex 40. By default,
Terminal 1 is configured as Coast to Stop and shipped with a jumper between Terminal 1 and
Terminal 11 (+24VDC). If the 160 SSC has a hardware enable circuit wired between TB3-7 and
TB3-8, the same circuit can be wired between Terminal 1 and Terminal 11 on the PowerFlex 4M,
4, and 40
The type of stop the 160 SSC performs when terminal 7 and 8 are opened up is determined by
Parameter 34. The type of stop the PowerFlex performs when terminal 1 and 11 when configured for network control is always a Coast Stop.
ENBL Jumper
NOTE: The PowerFlex 40 has an enable (ENBL) jumper. If the enable jumper is removed
Terminal 1 will always act as a hardware enable regardless of software configuration.
Save Existing Network
The existing network and drive configuration containing the 160 SSC needs to be referenced for
PowerFlex drive and Scanner configuration. Save the Network prior to replacing the 160 SSC.
28
NOTE: Be sure to have the EDS file for the 160 SSC installed on PC. EDS file for 160 SSC can be downloaded at:
http://www.rockwellautomation.com/resources/eds/
An EDS file can be created for the 160 SSC or PowerFlex. See the procedures in the following publications at:
http://literature.rockwellautomation.com
160-UM002 160-DN2 Device Net Comm Module User Manual
22COMM-UM003
22-COMM-D DeviceNet Adapter User Manual
Go online with DeviceNet.
Start RSNetworx for DeviceNet
Set Online Path to Network.
Select
Set Online Path
Browse the RSLinx path to the DeviceNet Network
Select the DeviceNet Network
Ok
Go online with DeviceNet Network.
Select Network>Online
29
When online, RSNetworx will browse and display the devices on the network.
Upload entire Network.
Select Network>Upload from Network
Click Ok
The scanner and device parameters will be uploaded.
Save the DeviceNet project.
Select File>Save As
Enter a unique project name.
Click Save.
This saves the existing DeviceNet project and allows us to generate a report.
30
Go offline.
RSNetworx will go offline
Generate Network Report.
Select File>Generate Report
Select Generate report for entire network
Click Ok
RSNetworx will generate a report in html format for the entire network. It will contain the configuration for the Scanner and the 160 SSC drive. The file has an .html extension and is saved in the same folder as the DeviceNet project (.dnt) file. It can be viewed and printed.
The current Scanner and the 160 SSC configuration will be needed in later steps. The DeviceNet project file (.dnt) saved in this step can be opened up offline or the .html report generated in this step can be viewed offline.
31
Following is a sample of the information contained in the report:
Scanlist Summary
Node Active Key Input Size Input Mapped Output Size Output Mapped
01, 'Slave Mode' No
22, 160 SSC Analog 3....
Input Memory
Assembly Data
Memory Offset
Yes
Bit Length
1:I.Data[10].0 32
Output Memory
Assembly Data
Memory Offset Bit Length
No 0
Yes 4
Node
22, 160 SSC Analog 3....
Node
No
Yes
0
4
Message Type
Polled
Message Type
No
Yes
1:O.Data[10].0 32 22, 160 SSC Analog 3.... Polled
The Scanner configuration in the report shows that the 160 SSC drive is address 22. Four bytes are mapped to input word 10 and four bytes are mapped to output word 10.
The report for the 160 SSC (address 22) configuration shows all the parameters of the drive. The parameters needed to configure the new PowerFlex are highlighted.
Parameters
ID Name Value
1
2
Output Frequency
Output Voltage
0.0 Hz
0 Volt
4
5
6
7
8
9
Output Power
Bus Voltage
Cmd Frequency
Present Fault
Heatsink Temp
Drive Status
12
13
15
Input Status
Power Factor Ang
Preset Status
17 Fault Buffer 0
18
19
Fault Buffer 1
Fault Buffer 2
20 Reserved
21 Reserved
22 Reserved
23 Reserved
24 Reserved
25 Reserved
26 Reserved
27 Reserved
28 Reserved
0.00 kW
669 Volt
0.0 Hz
No Fault
69 Deg
XXXXXXXX 10000010
38
7.06
XXXXXXXX XXXX0010
0.0 Deg
40960
XXXXXXXX XXXXXX00
0.0
Under Volt Fault
Motor OL Fault
Under Volt Fault
0
0
0
0
0
0
0
0
0
32
39
40
41
42
43
44
45
46
29 Reserved
30 Accel Time 1
31 Decel Time 1
32
33
34
35
36
37
Minimum Freq
Maximum Freq
Stop Mode Select
Base Frequency
Base Voltage
Maximum Voltage
Skip Frequency
Skip Freq Band
Overload Select
Motor Overload
Current Limit
DC Hold Time
DC Hold Voltage
Input Mode
49 PWM Frequency
51 Restart Time
53 S-Curve
56 Reset Functions
59
60
Freq Select
Zero Offset
61
62
Preset Freq 0
Preset Freq 1
63 Reserved
64 Reserved
65 Preset Freq 4
66 Preset Freq 5
67 Reserved
68 Reserved
69 Accel Time 2
70 Decel Time 2
71
72
73
IR Compensation
Slip Comp
Reverse Disable
75 Analog Minimum
76 Analog Maximum
77 Reserved
78 Compensation
79 Current Trip
24574
No Action
Unlocked
Internal Freq
0.0 %
3.0 Hz
20.0 Hz
0
0
45.0 Hz
50.0 Hz
0
0
20.0 Sec
20.0 Sec
50 %
2.0 Hz
Not Disabled
Unipolar
0.0 %
100.0 %
0
0
10.0 Sec
10.0 Sec
0 Hz
60 Hz
Ramp to Stop
60 Hz
460 Volt
460 Volt
5.0%
240 Hz
0 Hz
No Derating
6.00 Amps
150 %
0.0 Sec
0 Volt
Network Control
Ready/Faulted
0
4.0 kHz
0
10.0 Sec
0
0%
0 %
33
81
82
Proc Kp Gain
Proc Ki Gain
83
84
Proc Reference
Proc Invert
85 Reserved
86 Reserved
87 Reserved
88 Reserved
89 Reserved
90 Reserved
91 Reserved
92 Reserved
93 Reserved
94 Reserved
95 Reserved
96 Reserved
102
103
104
105
106
97 Reserved
98 Reserved
99 Reserved
100 Reserved
101 Switches MAC ID
Switches Baud
NV MAC ID
NV Baud Rate
Bus Off Error
Bus Off Count
107
108
113
114
Output Assembly
Input Assembly
DN Fault Mode
Motor Base RPM
0.01
0.01
0.0 %
0.0 %
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
22
125K Baud
63
125K Baud
Hold Error State
0
103
104
Fault and Stop
1778 RPM
115
116
117
DN Idle Mode
DN SW Version
COS Mask
Stop Drive
3.002
11111111 11111111
118 Local Return Md 3 Wire Control
DeviceNet Parameters on Report.
Parameter 101 MAC ID is the DeviceNet address and Parameter 102 is the DeviceNet baud.
These values will be use later in the PowerFlex DeviceNet configuration.
Parameter 107 Output Assembly and 108 Input Assembly are the I/O Assemblies used to control the drive over DeviceNet. They are needed later to configure the data size in the DeviceNet
Scanner and the method of control for the ladder logic.
34
Configure PowerFlex Drive
Determine Address and Baud from 160 SSC
The new PowerFlex will replace the 160 SSC at the same address on the DeviceNet.
The address and baud rate can be determined by viewing the 160 SSC parameters. These can be viewed by opening up the saved DeviceNet project with the 160 SSC or the report generated from this project.
Parameter 101 – Switches MAC ID
Parameter 102 – Switches Baud
The address and the baud rate of the 160 SSC can also be determined from the DIP switches on the back of the 160-DN2 DeviceNet Communication module.
35
36
DIP switches 6 through 1 set the module’s address. Factory default setting is 63. Note that when switches 7 and 8 are ON, the address is set to the value in Parameter 103 – NV MAC ID.
DIP switches 7 and 8 set the module’s baud rate. Factory default setting is 125 kbps. Note that when switches 7 and 8 are ON, the baud rate is set to the value in Parameter 104 – NV Baud
Rate.
For more on address and baud rate DIP settings reference the following publications at:
http://literature.rockwellautomation.com
160-UM002 160-DN2 Device Net Comm Module User Manual
37
.
38
Install DeviceNet Comms Adapter in PowerFlex Drive
Install 22-COMM-D adapter in PowerFlex 40 or 22-XCOMM for PowerFlex 4/4M per the following publications at:
http://literature.rockwellautomation.com
22COMM-UM003
22COMM-IN001
22-COMM-D DeviceNet Adapter User Manual
22-XCOMM External Comms Installation Manual
Set DIP switches on Communication Adapter
Set address and baud rate on the PowerFlex communication adapter the same as the
160 SSC.
Set Single/Multi Drive Operation jumper (J2) to Single Drive Operation.
DIP switches 1 through 6 set the address and switches 7 and 8 set the baud rate. Note that when all switches are CLOSED (0), the address is set to the value in Parameter 2 – DN Addr Cfg and the Baud is set to the value in Parameter 4 – DN Rate Cfg
39
Install and Configure PowerFlex drive.
NOTE: It’s recommended that the PLC be in program mode for this step. The new PowerFlex drive is taking the place of the 160 SSC on the DeviceNet network. The existing PLC logic for the
160 SSC could inadvertently start the PowerFlex drive. It is also recommended that the hardware enable to the PowerFlex drive (terminals 1 and 11) be open.
Install the PowerFlex 4/4M/40 per the recommendations in the following publications at:
http://literature.rockwellautomation.com
22A-UM001
22B-UM001
22F-UM001
PowerFlex 4 User Manual
PowerFlex 40 User Manual
PowerFlex 4M User Manual
Configure PowerFlex Drive.
It is possible to configure the PowerFlex many ways.
Explorer
Drive
HIM
DeviceNet
The following description uses RSNetworx to set parameters in the PowerFlex drive and configure the scanner online.
NOTE: Be sure to have the EDS file for the PowerFlex drive installed on PC. EDS file for
PowerFlex can be downloaded at:
http://www.rockwellautomation.com/resources/eds/
An EDS file can be created for the PowerFlex. See the procedures in the following publications at:
http://literature.rockwellautomation.com
22COMM-UM003
22-COMM-D DeviceNet Adapter User Manual
The PowerFlex drive and DeviceNet need to be powered up.
Go online with DeviceNet.
Start RSNetworx for DeviceNet
Set Online Path to Network.
Network>Properties
Set Online Path
Browse the RSLinx path to the DeviceNet Network
Select the DeviceNet Network
Click
Go online with DeviceNet Network.
Select Network>Online
40
RSNetworx will do a single pass browse and the new PowerFlex drive should show up on the network at the address of the 160 SSC.
Set PowerFlex drive parameters.
Double click on PowerFlex Drive.
The PowerFlex Properties is displayed.
Select the Parameters tab
Click on Upload parameters.
41
PowerFlex parameters are displayed.
Edit Parameters
The following parameters are the minimum required to configure the PowerFlex for the motor attributes and to accept commands over DeviceNet. The table shows a cross reference to the
160 SSC parameters that can be seen in the Offline DeviceNet file or the report generated in the previous step.
NOTE: This example uses a 5HP, 460VAC, 6.0FLA, 60Hz motor. PowerFlex Parameters 31, 32,
33, 34, and 35, are dependant on your motor and application. PowerFlex Parameters 37, 39, and
40 are dependant on your applications stop mode and Accel/Decel rates.
160 SSC analog PowerFlex 40
No. Parameter Value No. Parameter Value
36
35
42
32
33
46
34
59
30
Base Voltage 460 V
Base Frequency 60 Hz
Motor OL Current 6.0 A
Minimum Frequency 0 Hz
Maximum Frequency 60 Hz
Input Mode 2 - Network Control
Stop Mode Select 0 - Ramp to Stop
Frequency Select 1 – Internal
Accel Time 1 10.0 Sec
31
32
33
34
35
36
37
38
39
Motor NP Volts
Motor NP Hertz
Motor OL Current
Minimum Frequency
460 V
60 Hz
6.0 A
0 Hz
Maximum Frequency 60 Hz
Start Source
Stop Mode
Speed Reference
Accel Time 1
5 – Comm Port
0 – Ramp CF
5 – Comm Port
10.0 Sec
31 Decel Time 1 10.0 Sec 40 Decel Time 1 10.0 Sec
NOTE: PowerFlex 40 on DeviceNet. Parameter 164 may need to be edited if doing explicit messaging over DeviceNet. See the information on this parameter in the sections for
ControlLogix Explicit Messaging and SLC Explicit Messaging.
42
Click Apply.
Click Ok to close the properties.
43
Configure DeviceNet Scanner
Before configuring the DeviceNet scanner for the new PowerFlex drive, we need to know how the
160 SSC is mapped into the Input/Output of the scanner. The 160 SSC is mapped in the Scanlist with Output Assemblies of one to four bytes, and Input Assemblies from one to eight bytes.
The size in bytes of the data mapped to the 160 SSC is dependant on the configurable
Input/Output Assemblies used for DeviceNet. The size in bytes of the data mapped to the
PowerFlex is dependant on the fixed Input/Output Assemblies used for DeviceNet.
The Input/Output Assemblies used by the 160 SSC are determined by values in Parameter 107
Output Assembly and 108 Input Assembly. These can be viewed by opening up the saved
DeviceNet project with the 160 SSC or the report generated from this project. A typical example of Output Assembly 20 and Input Assembly 70 would be mapped in the scanner as four bytes out and four bytes in.
44
160 SSC Output Assembly 20 and Input Assembly 70 example.
For an explanation of the Input/Output Assemblies for 160 SSC, reference the following manual at:
http://literature.rockwellautomation.com
160-UM002
160-DN2 Device Net Communication Module User Manual
The PowerFlex drive Input and Output Assemblies are fixed at four bytes in and four bytes out.
For an explanation of the Input/Output Assemblies for PowerFlex 4, reference the following manual at:
http://literature.rockwellautomation.com
22COMM-UM003
22-COMM-D DeviceNet Adapter User Manual
If the 160 SSC used one byte Output Assemblies 1…5 or Input Assemblies 50…54 then we need to verify that the space in the scanner that the 160 SSC occupied is large enough for the four bytes of the PowerFlex.
45
Go online with DeviceNet.
Start RSNetworx for DeviceNet
Set Online Path to Network.
Network>Properties
Click
Browse the RSLinx path to the DeviceNet Network
Select the DeviceNet Network
Click
Go online with DeviceNet Network.
Select Network>Online
When online, RSNetworx will browse and display the devices on the network.
46
Edit Scanlist.
In the following example, the 1756-DNB scanner is shown. Editing other scanners is similar.
Double-Click on DeviceNet Scanner.
Select Scanlist tab and Upload.
The Scanlist will upload.
Scanlist will show an error because of the key mismatch between the 160 SSC drive in the configuration and the new PowerFlex Drive connected to the network at the same address.
Click Update Key.
This will replace the 160 SSC with the PowerFlex in the Scanlist. It is possible the I/O sizes are different. We need to verify the mapping and sizes.
47
The Scanlist will be displayed including the new PowerFlex.
Select the PowerFlex drive in the Scanlist
Click Edit I/O Parameters
This will allow us to change the Input and Output size to 4 bytes.
The I/O Parameters will be displayed.
48
Check the Polled check box.
Set Input size to 4 bytes.
Set Output size to 4 bytes.
Select Poll rate as Every Scan
Click OK and (Yes to Unmap and Yes to Automap if the size changed)
View Input/Output Mapping.
This procedure replaced the 160 SSC Input/Output mapping with the PowerFlex map. As stated earlier the PowerFlex Input/Output Assemblies are fixed at 4 bytes in and 4 bytes out. The 160
SSC Input/Output Assemblies are configurable depending on the values in drive parameters 107 and 108. If Input or Output Assemblies for the 160 SSC were less than 4 bytes, the new
PowerFlex mapping may overlap and existing device. Follow the next steps to verify the mapping and possibly move the PowerFlex.
Click on Input tab
Select the PowerFlex
The display will show the location in the Scanner’s Input table that the 4 bytes from the PowerFlex are mapped to. In this example, word 10. Also, this example uses a 1756-DNB. If a 1747-SDN or a 1771-1771-SDN is used the mapping will display in 16 bit words. Notice in this example another device has 1 byte located at word 11.
If it needs to be moved or is overlapping with another device complete the
following steps. Click on Advanced…
If the mapping is correct and does not overlap another device then click on Output tab
49
The Advanced Input mapping will be displayed
NOTE: Complete this step if it needs to be moved or is overlapping with another device.
Select Memory:
Select memory location from the pull down depending on the type of DeviceNet scanner being used.
Type of Scanner Memory Locations
1747-SDN Discrete of M-File
1771-SDN Block Xfer 62-57
Enter Word or DWord to map Input assembly to.
In this example, a 1756-DNB is used so 32 bits (4 bytes) are mapped to Dword
10. If you are using a 17xx-SDN, it will show 32 bits (4 bytes) mapped to Word
10, and 11
Click Apply Mapping
Close
The inputs should be mapped to the proper location on the Input tab.
50
Click on Output tab.
Select the PowerFlex
The display will show the location in the Scanner’s Output table that the four bytes to the PowerFlex are mapped to. In this example, word 10. Also, this example uses a 1756-DNB. If a 1747-SDN or a 1771-1771-SDN is used the mapping will display in 16 bit words. Notice in this example another device has one byte located at word 11.
NOTE: If it needs to be moved or is overlapping with another device go to the
Advanced mapping as described for inputs in the previous step. Otherwise go on to next step.
If it needs to be moved or is overlapping with another device complete the
following steps. Click on Advanced…
If the mapping is correct and does not overlap another device then go on to the next step to download to the scanner.
51
Download to Scanner.
NOTE: The PLC needs to be in program mode for this step. The new PowerFlex drive is taking the place of the 160 SSC on the DeviceNet network. It is also recommended that the hardware enable to the PowerFlex drive (terminals 1 and 11) be open.
Select the Scanlist Tab
Select the PowerFlex drive in the Scanlist
Click Download to Sanner
52
Select the Selected Scanlist Records radio button.
Click Download
This will download the changes for the PowerFlex replacement of the 160 SSC to the
Scanner.
When the download is complete, click OK to close the Scanner dialog.
Save the DeviceNet project.
Select File>Save As
Enter a unique project name.
Click Save.
This saves the new DeviceNet project which includes the PowerFlex drive.
53
Example Ladder Logic
The DeviceNet configuration has been aimed at placing the new PowerFlex in the same
Input/Output space as the 160 SSC. The logic examples provided are to replace the 160 SSC with a new PowerFlex with minimal changes to the control logic.
The ladder logic of the 160 SSC is dependant on the data mapping of the configurable
Input/Output Assemblies used for DeviceNet. The ladder logic for the PowerFlex is dependant on the fixed Input/Output Assemblies used for DeviceNet.
The Input/Output Assemblies used 160 SSC are determined by values in Parameter 107 Output
Assembly and 108 Input Assembly. These can be viewed by opening up the saved DeviceNet project of the 160 SSC or the report generated from this project.
The following tables show the data mapping for two of the most common 160 SSC Input/Output
Assemblies and the PowerFlex Input/Output Assemblies.
160 SSC Output Assembly 20 and Input Assembly 70
160 SSC Output Assembly 103 and Input Assembly 104
PowerFlex Output Assembly and Input Assembly
Logic examples for ControlLogix, and SLC500 are shown for the two common 160 SSC assemblies and equivalent logic to control a PowerFlex in the same manner. The 160 SSC logic can vary depending on Input/Output Assemblies. The logic for the PowerFlex attempts to use the same bits and method of control by minor edits to the commands to the drive and status from the drive while keeping the original command and status logic intact.
If the 160 SSC used Customizable Input Assemblies 102 or 105, the configurable parameters being read from the drive will have to be cross-referenced to the PowerFlex and possibly be transferred using an explicit message.
NOTE: Preset Speed Model.
The example logic sends a speed reference to the drives and assumes it is configured as a speed follower. The 160 SSC could be a Preset model and use Output Assembly 103 to select
Preset speed. This can also be accomplished with the PowerFlex fixed output assembly.
54
160 SSC Output Assembly 20 and Input Assembly 70
Default and common configuration.
160 SSC Output Assembly 103 and Input Assembly 104
55
PowerFlex 40 Output and Input Assembly
For Input/Output Assemblies not shown in these examples or for a more in-depth discussion reference the following publications at:
http://literature.rockwellautomation.com
160-UM002 160-DN2 Device Net Comm Module User Manual
22COMM-UM003 22-COMM-D DeviceNet Adapter User Manual
56
ControlLogix I/O Messaging Examples
In this example, DeviceNet is configured for the drive Outputs to start at Slot 1 Output Word 10
(Local:1:O.Data[10]) and drive Inputs to start at Slot 1 Input Word 10 (Local:1:I.Data[10]) in the
1756-DNB Scanner.
Tags for Example Program
Description Tag Name
Local:1:I.Data[10]
Type
Dint[]
Local:1:O.Data[10] Dint[]
DriveInputImage Int[2]
Local I/O Slot 1 Input
Local I/O Slot 1 Output
Drive Input Dint to Int conversion
Drive Output Int to Dint conversion DriveOutputImage
DriveSpdFbk
DriveSpdRef
DriveStaReady
Int[2]
Int
Int
Bool
Speed Feedback from drive +/- 0-32767
Speed Reference to drive 0-32767
Drive Status to user logic – Ready
Drive Status to user logic – Running DriveStaRunning
DriveStaFwd
DriveStaFault
DriveStaAtRef
DriveCmdStop
DriveCmdStart
Bool
Bool
Bool
Bool
Bool
Bool
Drive Status to user logic – Forward Direction
Drive Status to user logic – Faulted
Drive Status to user logic – Running at speed reference
Drive Command from user logic – Stop
Drive Command from user logic – Start
DriveCmdJog
DriveCmdClrFault
DriveCmdFwd
Bool
Bool
Bool
Drive Command from user logic – Jog
Drive Command from user logic – Clear Fault (reset)
Drive Command from user logic – Fwd/Rev Direction
57
58
ControlLogix
160 SSC Control with Output Assembly 103 and Input Assembly 104
Using the Output Assembly 103, the 160 SSC is started with a momentary DriveCmdStart bit and stopped with a momentary DriveCmdStop bit.
Speed Reference is 0-32767 (32767 = Maximum frequency).
59
ControlLogix
Equivalent PowerFlex Control for Output Assembly 103 and Input Assembly 104
The PowerFlex is started with a momentary DriveCmdStart bit and stopped with a momentary
DriveCmdStop bit.
The 160 SSC Speed Reference was 0-32767 (32767 = Maximum frequency). The PowerFlex
Speed Reference is 0-600 (0.0Hz *10). The speed reference from the user logic has to be scaled for the PowerFlex 0-600.
60
61
62
ControlLogix
160 SSC Control with Output Assembly 20 and Input Assembly 70
Using the Output Assembly 70, the 160 SSC is started with DriveCmdRunFwd bit being held high and stopped when DriveCmdRunFwd goes low.
Speed Reference is 0-1750 RPM.
63
64
ControlLogix
Equivalent PowerFlex Control for Output Assembly 20 and Input Assembly 70
The 160 SSC is started with DriveCmdRunFwd bit being held high and stopped when
DriveCmdRunFwd goes low. The PowerFlex is started with a momentary start bit and stopped with a momentary stop bit. Logic has to be added to start the Powerflex when the
DriveCmdRunFwd bit goes high and stop the PowerFlex when the DriveCmdRunFwd bit goes low.
The 160 SSC Speed Reference was 0-1750RPM. The PowerFlex Speed Reference is 0-600
(0.0Hz *10). The speed reference from the user logic has to be scaled for the PowerFlex 0-600.
65
66
ControlLogix Explicit Messaging Examples
Explicit Messaging is used to transfer data that does not require continuous updates. It can also be configured to read or write parameters not included in the fixed Input and Output Assemblies.
Two examples are shown for 160 SSC and equivalent for PowerFlex. One example reads the
Output current from the drive and the other writes Accel Rate to the drive.
NOTE: PowerFlex 40 Explicit Messaging. Writing parameter data to the PowerFlex 40 over the communications port can be stored to RAM only or Non-Volatile Storage (NVS) depending on
Parameter A164 (Comm Write Mode). If stored in RAM, the values will be lost at power down.
However, if they are stored in NVS, and the controller is programmed to write parameter data frequently, the NVS will quickly exceed its life cycle and cause the drive to malfunction.
Parameter A164 (Comm Write Mode)
0 – Save (default)
1 – RAM Only
67
68
Read Output Current, ParamReadMsg Rungs.
The following rung triggers the message to read the Output Current from the drive when bit
ParamRead goes from OFF to ON. Bit ParamRead is the result of user’s logic.
Read Output Current, ParamReadMsg Configuration.
The message control rungs for reading a value from the 160 SSC and the PowerFlex could be same, but the message configuration is different. The DeviceNet objects differ between the 160
SSC and Powerflex. Following shows the message configuration differences to read the Output
Current from a PowerFlex compared to a 160 SSC.
For a complete list of DeviceNet objects reference the following publications at:
http://literature.rockwellautomation.com
160-UM002 160-DN2 Device Net Comm Module User Manual
22COMM-UM003 22-COMM-D DeviceNet Adapter User Manual
For a cross reference of 160 SSC parameters to PowerFlex parameters see the Parameter Cross
Reference section at the end.
Message Configuration
The message type must be CIP Generic.
160 SSC – CIP Generic
PowerFlex – CIP Generic
Service Type
The service type is the requested DeviceNet service. Available services depend on the class and instance that you are using.
160 SSC – Get Attribute Single (Service Code – e)
PowerFlex – Get Attribute Single (Service Code – e)
Class
The object type is a DeviceNet class.
160 SSC – b3 (Parameter Table Object)
PowerFlex – f (Parameter Object)
Instance
The object ID is an instance of a DeviceNet class.
160 SSC – 1 (Parameter Value)
PowerFlex – 3 (Parameter #)
Attribute
The attribute is a class or instance attribute.
160 SSC – 3 (Parameter #3 Output Current)
PowerFlex – 1 (Parameter Value)
Source Element
The Source Element is the name of the tag for any data to be sent from the scanner to the drive. A tag must be specified even if it is not used.
160 SSC – blank
PowerFlex – blank
Source Length
The number of bytes of service data to be sent of received in the message.
160 SSC – 0
PowerFlex – 0
Destination
The Destination is the name of the tag that will receive service response data from the drive. A tag must be specified even if it is not used.
160 SSC – DriveOutCurr (Int Tag)
PowerFlex – DriveOutCurr (Int Tag)
Path
The path includes the following:
Name of DeviceNet scanner - DNET01
Communication port on the front of the 1756-DNB scanner. - Always 2.
Node address of the DeviceNet adapter on drive – 22
69
70
Write Accel Rate, ParamWriteMsg1 Rungs.
The following rung triggers the message to write the Accel Rate to the drive when bit ParamWrite goes from OFF to ON. Bit ParamWrite is the result of user’s logic.
Write Accel Rate, ParamWriteMsg1 Configuration.
The message control rungs for writing a value to the 160 SSC and the PowerFlex could be same, but the message configuration is different. The DeviceNet objects differ between the 160 SSC and Powerflex. Following shows the message configuration differences to write an Accel Rate to a PowerFlex compared to a 160 SSC.
For a complete list of DeviceNet objects reference the following publications at:
http://literature.rockwellautomation.com
160-UM002 160-DN2 Device Net Comm Module User Manual
22COMM-UM003 22-COMM-D DeviceNet Adapter User Manual
For a cross reference of 160 SSC parameters to PowerFlex parameters see the Parameter Cross
Reference section at the end.
Message Configuration
The message type must be CIP Generic.
160 SSC – CIP Generic
PowerFlex – CIP Generic
Service Type
The service type is the requested DeviceNet service. Available services depend on the class and instance that you are using.
160 SSC – Set Single Attribute (Service Code – 10)
PowerFlex – Set Single Attribute (Service Code – 10)
Class
The object type is a DeviceNet class.
160 SSC – b3 (Parameter Table Object)
PowerFlex – f (Parameter Object)
Instance
The object ID is an instance of a DeviceNet class.
160 SSC – 1 (Parameter Value)
PowerFlex – 39 (Parameter #)
Attribute
The attribute is a class or instance attribute.
160 SSC – 1e (30 decimal) (Parameter #30 Accel Rate)
PowerFlex – 1 (Parameter Value)
Source Element
The Source Element is the name of the tag for any data to be sent from the scanner to the drive. A tag must be specified even if it is not used.
160 SSC – DriveAccelRate (Int Tag)
PowerFlex – DriveAccelRate (Int Tag)
Source Length
The number of bytes of service data to be sent of received in the message.
160 SSC – 2
PowerFlex – 2
Destination
The Destination is the name of the tag that will receive service response data from the drive. A tag must be specified even if it is not used.
160 SSC – blank
PowerFlex – blank
Path
The path includes the following:
Name of DeviceNet scanner - DNET01
Communication port on the front of the 1756-DNB scanner. - Always 2.
Node address of the DeviceNet adapter on drive – 22
71
SLC 500 I/O Messaging Examples
I:2.10/3
I:2.10/7
I:2.10/8
B21:10/0
B21:10/1
B21:10/2
B21:10/3
B21:10/4
B21:10/5
O:2.10/0
O:2.10/1
O:2.10/2
O:2.10/3
O:2.10/4
O:2.10/5
In this example, the DeviceNet is configured for the drive Outputs to start at Slot 2 Output Word
10 (O:2.10) and drive Inputs to start at Slot 2 Input Word 10 (I:2.10) in the 1747-SDN Scanner.
Data Table Elements for Example Program
Address
N23:10
N22:10
I:2.11
Description
Speed Feedback from drive +/- 0-32767
Speed Reference to drive 0-32767
160 SSC Speed Feedback from DeviceNet
O:2.11
B20:10/0
B20:10/1
B20:10/3
B20:10/7
B20:10/8
I:2.10/0
I:2.10/1
160 SSC Speed Reference to DeviceNet
Drive Status to user logic – Ready
Drive Status to user logic – Running
Drive Status to user logic – Forward Direction
Drive Status to user logic – Faulted
Drive Status to user logic – Running at speed reference
160 SSC Status from DeviceNet – Ready
160 SSC Status from DeviceNet – Running
160 SSC Status from DeviceNet – Forward Direction
160 SSC Status from DeviceNet – Faulted
160 SSC Status from DeviceNet – Running at speed reference
Drive Command from user logic – Stop
Drive Command from user logic – Start
Drive Command from user logic – Jog
Drive Command from user logic – Clear Fault (reset)
Drive Command from user logic – Run Forward
Drive Command from user logic – Fwd/Rev Direction
160 SSC Command to DeviceNet – Stop
160 SSC Command to DeviceNet – Start
160 SSC Command to DeviceNet – Jog
160 SSC Command to DeviceNet – Clear Fault (reset)
160 SSC Command to DeviceNet – Run Forward
160 SSC Command to DeviceNet – Fwd/Rev Direction
72
SLC500
160 SSC Control with Output Assembly 103 and Input Assembly 104
Using the Output Assembly 103, the 160 SSC is started with a momentary Start (O:2.10/1) bit and stopped with a momentary Stop (O:2.10/0) bit.
Speed Reference is 0-32767 (32767 = Maximum frequency).
73
74
75
SLC500
Equivalent PowerFlex Control for Output Assembly 103 and Input Assembly 104
The PowerFlex is started with a momentary Start (O:2.10/1) bit and stopped with a momentary
Stop (O:2.10/0) bit.
The 160 SSC Speed Reference was 0-32767 (32767 = Maximum frequency). The PowerFlex
Speed Reference is 0-600 (0.0Hz *10). The speed reference from the user logic has to be scaled for the PowerFlex 0-600.
76
77
78
SLC500
160 SSC Control with Output Assembly 20 and Input Assembly 70
Using the Output Assembly 70, the 160 SSC is started with RunFwd (O:2.10/0) bit being held high and stopped when RunFwd (O:2.10/0) bit goes low.
Speed Reference is 0-1750 RPM.
79
80
SLC500
Equivalent Control for Output Assembly 20 and Input Assembly 70
Using the Output Assembly 70, the 160 SSC is started with RunFwd (O:2.10/0) bit being held high and stopped when RunFwd (O:2.10/0) bit goes low. The PowerFlex is started with a momentary start bit and stopped with a momentary stop bit. Logic has to be added to start the
Powerflex when the RunFwd (O:2.10/0) bit goes high and stop the PowerFlex when the RunFwd
(O:2.10/0) bit goes low.
The 160 SSC Speed Reference was 0-1750RPM. The PowerFlex Speed Reference is 0-600
(0.0Hz *10). The speed reference from the user logic has to be scaled for the PowerFlex 0-600.
81
82
83
SLC 500 Explicit Messaging Examples
Explicit Messaging is used to transfer data that does not require continuous updates. It can also be configured to read or write parameters not included in the fixed Input and Output Assemblies.
There are two methods of explicit messaging in the SLC 500. One method uses the DEM instruction and the other uses the Module files (M0 and M1) of the DeviceNet scanner. The DEM instruction simplifies programming and configuration. However it requires RSLogix 500 ver 7.10 or later, and a SLC 503,504, or 505 firmware level Series C, FRN 10 or later. The examples are given with the Module file method because it is more difficult but also more common.
Two examples are shown for 160 SSC and equivalent for PowerFlex. One example reads the
Output current from the drive and the other writes Accel Rate to the drive.
NOTE: PowerFlex 40 Explicit Messaging. Writing parameter data to the PowerFlex 40 over the communications port can be stored to RAM only or Non-Volatile Storage (NVS) depending on
Parameter A164 (Comm Write Mode). If they are stored in RAM, the values will be lost at power down. However, if they are stored in NVS, and the controller is programmed to write parameter data frequently, the NVS will quickly exceed its life cycle and cause the drive to malfunction.
Parameter A164 (Comm Write Mode)
0 – Save (default)
1 – RAM Only
SLC Message Format
The example uses N10:0 as the message request file and N11:0 as the message response file.
The request file and the response file need to be formatted as shown:
The N10 and N11 files are sent to and received from the M0 and M1 files of the 1747-SDN
DeviceNet scanner to control the explicit messaging. The M0 and M1 files are data files that reside in the module. M0 file is a module output file and the M1 is a module input file.
The addressing format for the M0 and M1 files
Mf : S . w / b
M = module
f = file (0 or 1)
S = slot (1 - 30)
w = word (0 – Max of the module)
b = bit (0 - 15)
In this example the 1747-SDN DeviceNet scanner resides in slot 2 so S = 2.
84
85
86
Read Output Current, Message Rungs.
The following rung triggers the message to read the Output Current from the drive when bit
B3:0/0 goes from OFF to ON. The message request configuration in N10:0 is copied to M0:2.224 to start the message. The scanner notifies the processor that it has a response from the drive by setting I:2.0/15 ON and the ladder the copies the response data from M1:2.224 to N11:0. The
Output Current is in word 3 of the response data and is divided by 100.
87
88
Read Output Current, Message Configuration.
The message control rungs for reading a value from the 160 SSC and the PowerFlex could be same, but the message configuration is different. The DeviceNet objects differ between the 160
SSC and PowerFlex. Following shows the message configuration differences to read the Output
Current from a PowerFlex compared to a 160 SSC.
For a complete list of DeviceNet objects reference the following publications at:
http://literature.rockwellautomation.com
160-UM002 160-DN2 Device Net Comm Module User Manual
22COMM-UM003 22-COMM-D DeviceNet Adapter User Manual
For a cross reference of 160 SSC parameters to PowerFlex parameters see the Parameter Cross
Reference section at the end.
N10:0 (Least Significant Byte) Command
160 SSC – 01h (Execute)
PowerFlex – 01h (Execute)
N10:0 (Most Significant Byte) TXID
160 SSC – 01h (ID = 1)
PowerFlex – 01h (ID = 1)
N10:1 (Least Significant Byte) Size
160 SSC – 06h (6 bytes)
PowerFlex – 06h (6 bytes)
N10:1 (Most Significant Byte) Port
160 SSC – 00h (Scanner port 0)
PowerFlex – 00h (Scanner port 0)
N10:2 (Least Significant Byte) Address
160 SSC – 16h (DeviceNet address 22d)
PowerFlex – 16h (DeviceNet address 22d)
N10:2 (Most Significant Byte) Service
The service type is the requested DeviceNet service. Available services depend on the class and instance that you are using
160 SSC – 0Eh (Get Single Attribute)
PowerFlex – 0Eh (Get Single Attribute)
N10:3 Class
The object type is a DeviceNet class.
160 SSC – B3h (Parameter Table Object)
PowerFlex – 0Fh (Parameter Object)
N10:4 Instance
The object ID is an instance of a DeviceNet class.
160 SSC – 01h (Parameter Value)
PowerFlex – 03h (Parameter #3 Output Current)
N10:5 Attribute
The attribute is a class or instance attribute.
160 SSC – 03h (30 decimal) (Parameter #3 Output Current)
PowerFlex – 01h (Parameter Value)
89
Write Accel Rate, Message Rungs.
The following rung triggers the message to write Accel Rate to the drive when bit B3:1/0 goes from OFF to ON. The Accel Rate is in Floating Point F8:1. It is multiplied by 10 and put in word 6
(N10:56) of the request configuration. The message request configuration in N10:50 is copied to
M0:2.224 to start the message. The scanner notifies the processor that it has a response from the drive by setting I:2.0/15 ON and the ladder the copies the response data from M1:2.224 to
N11:50.
90
Write Accel Rate, Message Configuration.
The message control rungs for writing a value to the 160 SSC and the PowerFlex could be same, but the message configuration is different. The DeviceNet objects differ between the 160 SSC and PowerFlex. Following shows the message configuration differences to write the Accel Rate to a PowerFlex compared to a 160 SSC.
For a complete list of DeviceNet objects reference the following publications at:
http://literature.rockwellautomation.com
160-UM002 160-DN2 Device Net Comms Module User Manual
22COMM-UM003 22-COMM-D DeviceNet Adapter User Manual
For a cross reference of 160 SSC parameters to PowerFlex parameters see the Parameter Cross
Reference section at the end.
N10:50 (Least Significant Byte) Command
160 SSC – 01h (Execute)
PowerFlex – 01h (Execute)
N10:50 (Most Significant Byte) TXID
160 SSC – 02h (ID = 1)
PowerFlex – 02h (ID = 1)
N10:51 (Least Significant Byte) Size
160 SSC – 08h (6 bytes)
PowerFlex – 08h (6 bytes)
N10:51 (Most Significant Byte) Port
160 SSC – 00h (Scanner port 0)
PowerFlex – 00h (Scanner port 0)
N10:52 (Least Significant Byte) Address
160 SSC – 16h (DeviceNet address 22d)
PowerFlex – 16h (DeviceNet address 22d)
N10:52 (Most Significant Byte) Service
The service type is the requested DeviceNet service. Available services depend on the class and instance that you are using
160 SSC – 10h (Get Single Attribute)
PowerFlex – 10h (Get Single Attribute)
N10:53 Class
The object type is a DeviceNet class.
160 SSC – B3h (Parameter Table Object)
PowerFlex – 0Fh (Parameter Object)
N10:54 Instance
The object ID is an instance of a DeviceNet class.
160 SSC – 01h (Parameter Value)
PowerFlex – 27h (Parameter #39 Accel Rate)
91
N10:55 Attribute
The attribute is a class or instance attribute.
160 SSC – 1Eh (30 decimal) (Parameter #30 Accel Rate)
PowerFlex – 01h (Parameter Value)
N10:56 Value
Value to be written to drive.
160 SSC – 60h (96 decimal) (Value)
PowerFlex – 5Bh (91 decimal) (Value)
92
Parameter Cross Reference
The following table cross references 160 SSC parameters to equivalent PowerFlex 40 parameters.
160 SSC PowerFlex 40
Firmware 7.03 and higher Firmware 5.x and higher Comments
No. Parameter
07
08
09
10
01
02
03
04
05
06
11
12
13
14
15
Output Frequency
Output Voltage
Output Current
Output Power
Bus Voltage
Frequency Command
Active Fault
Heatsink Temperature
Drive Status
Drive Type
Firmware Version
Input Status
Power Factor Angle
Memory Probe Display
Preset Status
16 Analog Input
41
42
43
44
45
46
47
37
38
39
40
31
32
33
34
35
36
17
18
19
30
Fault Buffer 0
Fault Buffer 1
Fault Buffer 2
Accel Time 1
Decel Time 1
Minimum Frequency
Maximum Frequency
Stop Mode Select
Base Frequency
Base Voltage
Maximum Voltage
Boost Select
Skip Frequency
Skip Frequency Band
Motor Overload Select
Motor Overload Current
Current Limit
DC Hold Time
DC Hold Voltage
Input Mode
Output Configure
No. Parameter
16
13
23
19
14
20
21
07
24
06
17
01
04
03
22
05
02
Output Frequency
Output Voltage
Output Current
Output Power
DC Bus Voltage
Commanded Freq
Fault Code 1
Drive Temp
Drive Status
Drive Type
Control SW Ver
Contrl In Status
Output Pwr Fctr
Testpoint Sata
Dig In Status
Analog In 0-10V
Analog In 4-20mA
40
34
35
37
32
31
07
08
09
39
Fault Code 1
Fault Code 2
Fault Code 3
Accel Time 1
Decel Time 1
Minimum Frequency
Maximum Frequency
Stop Mode
Motor NP Hertz
Motor NP Volts
90
33
89
80
81
36
55
88
84
Maximum Voltage
Boost Select
119 Skip Frequency
120 Skip Freq Band
Motor OL Select
Motor OL Current
Current Limit 1
DC Brake Time
DC Brake Level
Start Source
Relay Out sel
Depending on input used
Additional OPTO Out 1/2 available
93
Output Threshold
PWM Frequency
Restart Tries
Restart Time
DB Enable
S-Curve
Clear Fault
Memory Probe Address
Reset Functions
Program Lock
Internal Frequency
Frequency Select
Zero Offset
Preset Frequency 0
Preset Frequency 1
Preset Frequency 2
Preset Frequency 3
Preset Frequency 4
Preset Frequency 5
Preset Frequency 6
Preset Frequency 7
Accel Time 2
Decel Time 2
IR Compensation
Slip Compensation
Reverse Disable
Analog Select
75 Analog Input Minimum
63
64
65
66
67
68
59
60
61
62
52
53
54
55
48
49
50
51
56
57
58
69
70
71
72
73
74
76 Analog Input Maximum
78
79
80
81
82
83
84
Compensation
Software Current Trip
Stall Fault Time
PI Proportional Gain
PI Integral Gain
PI Process Reference
PI Deadband
94
72
73
74
75
76
77
38
70
71
56
91
92
93
Relay Our level
PWM Frequency
Auto Rstrt Tries
Auto Rstrt Delay
82
83
DB Resistor Sel
S Curve %
100 Fault Clear
19 Testpoint Data
41 Reset to Defaults
101 Program Lock
69 Internal Freq
Speed Reference
Preset Frequency 0
Preset Frequency 1
Preset Frequency 2
Preset Frequency 3
Preset Frequency 4
Preset Frequency 5
Preset Frequency 6
Preset Frequency 7
67
68
Accel Time 2
Decel Time 2
128 IR Voltage Drop
114 Slip Hertz @ FLA
95 Reverse Disable
132 10V Bipolar Enbl
110 Analog In 0-10V Lo
112 Analog In 4-20mA Lo
111 Analog In 0-10V Hi
113 Analog In 4-20mA Hi
97
98
Compensation
SW Current Trip
121 Stall Fault Time
134 PID Prop Gain
135 PID Integ Time
137 PID Setpoint
138 PID Deadband
Not applicable
Depending on input used
Depending on input used
Notes:
95
Drive Explorer, DriveExecutive, SSC, PowerFlex and Rockwell Automation are trademarks of Rockwell Automation, Inc Trademarks not belonging to Rockwell
Automation are property of their respective companies.
Publication DRIVES-AP005A-EN-E – April 2009
Copyright©2009 Rockwell Automation, Inc. All rights Reserved. Printed in USA.
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project