DESCRIPTION
Pedestal mounted emergency eyewash. Supplied with stainless steel bowl, stay-open full flow ball valve; activated stainless steel push handle, twin spray heads with individual flow restrictors, and flip-off dust covers.
SPECIFICATIONS
BOWL: 300 Series Stainless Steel.
SPRAY HEADS: (2) Aerated Yellow ABS Plastic Spray Outlet, Sprayface, and Dust Cover.
VALVE: 1/2” NPT Female Brass, Chrome-Plated. by
INLET: 1/2” NPT Female.
PIPE: 1-1/4” IPS Galvanized Steel.
FLOOR FLANGE: Brass Casting with (3) 17/32” Dia. Mounting Holes on 9” Dia. Bolt Circle, Spaced 120° Apart.
WASTE: 1-1/4” NPT Female.
FINISH: Safety Green Powder Coating.
SHIPPING WEIGHT: 21 lb.
EMERGENCY SIGN: 7-7/8” x 7-7/8” Plastic Wall Sign.
OPTIONS
◊
AL1
(Air Horn Alarm)
◊
AL2
(Electrical Alarm)
◊
AL3
(Electrical Alarm)
◊
FLW (Flow Switch)
◊
HS
(Hand-held Spray)
◊
◊
SSBV2
(1/2” Stainless Steel Valve)
◊
◊
VPL
(Vapor Proof Light)
◊
AL2-C1D2
(Electrical Alarm / Haz. Area)
◊
AL3-C1D2
(Electrical Alarm / Haz. Area)
◊
◊
SGN4
FPV
(Eye Wash Floor Sign)
(Anti-Freeze Protection Valve)
◊
SPV
(Anti-Scald Protection Valve)
◊
◊
◊
◊
ILS
(In-Line Strainer)
INSTALLATION
Review drawing (as shown on other side) to assure proper location of inlet and drain. Mount stanchion to floor using suitable anchors. Rest the eye/face wash bowl on the rubber washer and drain spud making sure to get the bowl level as possible, to ensure a proper flow pattern, and to avoid unnecessary water spillage. Once bowl is positioned correctly on spud, apply plumbers putty to drain strainer and tighten with hex tool (supplied). Connect a water supply to the unit (use pipe sealant on all joints) that is 1/2” minimum uninterrupted source of potable water. Failure to use potable water can result in emergency units producing impure of contaminated water causing possible further injury. The drain tailpiece or waste should be connected to an adequate drain in compliance with local plumbing codes.
OPERATION
The eyewash is activated by pushing the push handle back 90°. The unit will operate until the push handle is manually pulled beck up to the off position.
TESTING PROGRAM
The American National Standards Institute (ANSI) states that all safety emergency equipment shall be activated on weekly basis to flush the line and verify proper operation. Speakman Company furnishes a testing record tag
(91-0635) with each unit. On this tag the date of inspection and the inspectors initials should be noted. a
MAINTENANCE
The valve and the eyewash are the only portions of the unit that may require maintenance. Should you need parts to repair this unit, please reference the parts listing below for correct part numbers.
Reference additional technical sheet
(supplied) for information on the SE-582 eyewash. Before any maintenance is done be sure to shut the water supply off.
WARNING: Use only genuine
Speakman parts when repairing or replacing components . To order parts call 1-800-537-2107.
SE-584 REPLACEMENT/REPAIR PARTS
ITEM PART/GROUP # DESCRIPTION
1 SE-582 Eyewash
2 G74-0018-PNT Stanchion
FLOW DATA
EYEWASH:
FLOW PRESSURE PSI (BAR)
FLOW RATE GPM (LPM)
30 (2.07)
3.6 (15)
NOTE: This unit should be connected to an uninterrupted source of potable water, with a minimum flowing pressure of 30 PSI and a maximum static pressure of 125 PSI.
Note: All units meet existing
ANSI Z358.1 Standards and
OSHA Rules. Product improvements may cause specification and dimensional changes without notice.