Top Cop TC5000 User Manual
 @Zone1 Reaty ®
© Zone 2 Amed O
CD 9 Zone 3 System ©
—_—_ @ Zone 4
J и
A
Co
NR
| [1] [2] [3]
[4] [5] [6]
| [#] [0] (#] [access
WTOP 8OP
II
|
|
|
| INTRUDER ALARMS
TC5000
| INTRUDER ALARMS
July 14 1993
29000396 R1
| OPERATING INSTRUCTIONS
T | » | | » Lone Star Alarms e C
® |
TC5000
TOP COP Operating Instructions
e
MASTER CODE
The 4 digit Master Code is used to arm and disarm the security system, to
program additional security codes and to change other system features.
The Master Code will be supplied to you by your installer. All keypad
entries are made by pressing one key at a time. (See Additional Codes
section)
ARMING THE SYSTEM
Check the following items before arming the system:
SYSTEM LIGHT
If the “System” light is ON, this indicates a memory, bypass or trouble
condition. Check condition before arming system. (To view conditions,
see the Zone Bypassing, Trouble Conditions and Alarm Memory sections).
READY LIGHT
If the “Ready” light is NOT ON, check to see that all doors and windows are
closed and that motion is stopped in areas covered by motion detectors.
The system cannot be armed unless the “Ready” light is ON indicating that
all zones are closed.
NOTE: The system may be armed with a zone bypassed or a trouble
present but your security protection may be reduced.
TO ARM
Enter your 4 digit access code. As each digit is entered, the keypad
sounder will beep. If the correct access code is entered, the keypad
sounder will beep quickly and the “Armed” light will come ON.
If the access code was entered incorrectly, the keypad buzzer will beep
steadily for 2 seconds. If this occurs, press the [#] key once and re-enter
the access code.
When the correct access code is entered and the “Armed” light comes ON,
exit the premises through the door indicated by your installer as the Exit-
Entry door.
At the end of the exit delay period, all lights, except the “Armed” light, will
go out and the system will be armed. The exit time delay can be adjusted
by your installer to suit your requirements.
ALARM MEMORY DISPLAY ZONE BYPASSING
If the “System” light is ON, an alarm has occurred during the last armed (CONTINUED)
period. The alarm memory will automatically be displayed when the system For security reasons, your installer may prevent the bypass command from
is disarmed (See Disarming the System). working on certain zones. The “System” light is ON as long as ONE or more
Press [+] then [3] to display the zone or zones which caused the alarm. zones are bypassed. Be sure that the system is not armed with zones
Press [4] to return to Ready. unintentionally bypassed.
NOTE: The alarm memory is cleared each time the panel is armed so that Zone bypasses are automatically cancelled each time the system is
any alarms showing are alarms that occurred only during the last armed disarmed.
period. | VIEWING TROUBLE CONDITIONS
IF AN ALARM SOUNDS | O Ue monitors a number о possioe rouble conditions.
a trouble condition occurs, the keypad will beep twice every 10 seconds
INTRUSION ALARM and the keypad “System” indicator will light. Pressing any key on the keypad
It an intrusion alarm sounds (continuous Bell/Siren), the alarm may be N - will silence the sounder but the “System” light will remain ON until the trouble
silenced by entering your access code. Transmission to the monitoring ( sondition is cleared. If you cannot determine the cause of the trouble
station will not be interrupted by silencing the alarm. If the alarm was - condition, contact your installer for assistance.
unintentional, cali the monitoring station or local authorities immediately to T " bl
avoid an unnecessary response. o view type of trouble:
Press [k][2] to display the type of trouble. A zone light will come on to
You can determine the source of the alarm by following the instructions in NED ; ,
y q indicate which type of trouble exists.
the Alarm Viewing section of this manual. Once the source of the alarm has
been corrected, the panel can be restored to its original armed state. Press [+] to return to Ready.
ZONE BYPASSING LIGHT TYPE OF TROUBLE
Use zone bypassing when you wish to remain in part of the protected area To, Low or disconnected standby battery
while the system is armed. Bypassed zones will not cause an alarm. Zones D Loss of AC power (Loss of AC power will turn on the
that are temporarily out of service due to damaged wiring or contacts may trouble light but keypad sounder will not sound)
be bypassed to allow system arming (partial protection) until repairs can be 3 Е vell/si
made. Zones cannot be bypassed after the systemisarmed. See use open (bell/siren)
TO BYPASS ZONES: 4... Zone return wiring trouble _
Enter [*][1][Zone number(s) to be bypassed] Ready verevrorenoa Not used to indicate trouble conditions
Enter zone number(s) as single digits (1-4). + “Armed” ............ Loss of time on the system clock
As each zone is bypassed, the zone light will come ON. If a zone is
Qypassed in error press that zone литое! again and the zone light will go PE is activated by pressing the [1] and [3] keys at the
indicating that the zone is not assed. :
9 УР | same time. The Emergency alarm sounds the bell/siren in a pulsed mode.
Press [4] to return to Ready. A transmission will be sent to the monitoring station only if it has been
TO RECALL LAST GROUP OF ZONES BYPASSED: | programmed to do so by your installer.
Enter [+][1][9]
Zone lights for the last group of zones bypassed will come ON to show
which zones were bypassed. If you wish to add or delete a zone from the ;
group, press [#] to exit then go to zone bypass as described above. C No
Press [#] to return to Ready.
“AT HOME” ARMING
Simply press the [+] button then the number [9] and then your code. This
will eliminate the entry delay from any zones programmed with a delay. An
instant alarm will be created if one of the zones are tripped during the armed
period.
ACCESS BUTTON
Unit must be armed in the “At Home” mode. To allow entry or exit, press
and hold the [4] key. Open door to allow exit or entry; close door and then
release the key. Should you release the key while the door is open, the
alarm will sound instantly.
TESTING YOUR SYSTEM
It is recommended that you test your system weekly.
NOTE: Perform system tests in the off-peak hours, such as early morning or (
late evening.
1. Perform a bell/battery test by pressing [x]{6][Master Code][0]. The signal
will sound for about 2 seconds. if a trouble occurs after the test, press
[k][2] to view the trouble condition.
2. Activate each sensor in turn (e.g. open a door/window or walk in motion
detector areas). Observe the zone light come ON when the zone is
activated. The zone light will go OFF when the system restores to normal
(i.e. door or window closed).
3. If your system is programmed for communication, test the communication
function with the monitoring station. First inform the monitoring station
that you intend to test your system. Next, ensure that the “Ready” light is
ON. Enter an access code to arm the system. Activate a zone by
opening a door or window. Enter access code to disarm the system and
silence the alarm. Ask the monitoring station to call back to verify
transmission of the alarm.
4. If the panel has a zone programmed for fire, activation will cause the
alarm signal to sound in a pulsed mode.
CAUTION: Do not use an open flame or burn materials to test a smoke
detector. Contact your alarm installer for information on safe methods
to activate a smoke detector.
5. Should the system fail to operate properly, call your alarm dealer for
service.
6. When testing is complete, call and advise the monitoring station.
‚неее
o —————]—_ LE Lao a .
MAINTENANCE
C
With normal use, the system requires minimum maintenance. The following
points should be observed. |
1. Do not wash the keypad with a wet cloth. Light dusting with a damp cloth
should remove normal accumulations of dust.
2. The battery/beli test is designed to determine battery condition.
However, it is recommended that the standby battery be replaced every
three years.
3. For other system devices such as passive infrared, ultrasonic or
microwave motion detectors or glassbreak detectors, consult the
respective manufacturer's literature for testing and maintenance.
FCC COMPLIANCE
This equipment generates and uses radio frequency energy, and if not installed and used
properly, in strict accordance with the manufacturer's instructions, may cause interference
to radio and television reception. It has been type tested and found to comply with the limits
for aclass *B" computing device in accordance with the specifications in Subpart "B" of Part
15 of FCC Rules, which are designed to provide reasonable protection against such
interference in any residential installation. However, there is no guarantee that interference
will not occur in a particular installation. 1f this equipment does cause interference to radio
or television reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one or more of the following
measures.
e Reorient the receiving antenna.
Relocate the equipment with respect to the receiver.
* Move the equipment away from the receiver.
e Plug the equipment into a different outlet so that the equipment and the receiver are
on different circuits.
If necessary, the user should consult the dealer or an experienced radio/television
technician for additional suggestions. The user may find the following booklet prepared by
the FCC useful:
“How to identify and Resolve Radio/Television Interference Problems”
This booklet is available fromthe U.S. Government Printing Office, Washington D.C. 20402,
Stock # 004-000-00345-4
IMPORTANT INFORMATION
CAUTION: Changes or modifications not expressly approved by the manufacturer
could void your authority to use this equipment.
NOTIFICATION TO TELEPHONE COMPANY
Upon request, the customer shall notify the telephone company of the particular line on which
the connection will be made, and provide the ringer equivalence of the protective circuit.
Ringer Equivalence Number: 0.0B
MALFUNCTION OF THE EQUIPMENT
In the event that the TC5000 should fail to operate properly, the customer shall disconnect
the equipment from the telephone line to determine if it is the customer's equipment which
is not working properly, or if the problem is with the telephone company network. If the
problem is with the TC5000, the customer shall discontinue use until it is repaired.
TELEPHONE CONNECTION REQUIREMENTS
Except for the telephone company provided ringers, all connections to the telephone
network shall be made through standard plugs and telephone company provided jacks”
or equivalent, in such a manner as to allow for easy, immediate disconnection of a
terminal equipment. Standard jacks shall be so arranged that, if the plug connected there
is withdrawn, no interference to the operation of the equipment at the customer's premises
which remains connected to the telephone network shall occur by reason of such
withdrawal.
NOTE: Ensure that plugs and jacks meet the dimension, tolerance and metallic plating
requirements of 47 C.F.R. Part 68, Subpart F.
INCIDENCE OF HARM
Shouldterminal equipment or protective circuitry cause harmto the telephone network, the
telephone company shall, where practicable, notify the customer that temporary
disconnection of service may be required; however, where prior notice is not practicable,
the telephone company may temporarily discontinue service if such action is deemed
reasonable in the circumstances. In the case of such temporary discontinuance, the
telephone company shall promptly notify the customer and will be given the opportunity
to correct the situation. The customer also has the right to bring a complaint to the FCC
if he feels the disconnection is not warranted.
CHANGE IN TELEPHONE COMPANY EQUIPMENT OR FACILITIES
The Telephone Company may make changes in its communications facilities, equipment,
operations or procedures, where such actions are reasonably required and proper in its
business. Shouldany suchchanges renderthe customer's terminal equipmentincompatible
with the telephone company facilities the customer shall be given adequate notice to the
effect of the modifications to maintain uninterrupted service.
GENERAL
This equipment should not be used on coin telephone lines. Connection to party line
service is subject to state tariffs.
RINGER EQUIVALENCE NUMBER (REN)
The REN is useful to determine the quantity of devices that you may connect to your
telephone line and still have all of those devices ring when your telephone number is called.
In most but not all areas, the sum of the RENs of all devices connected to one line shoul
not exceed five (5). To be certain of the number of devices that you may connect to vol
line, you may want to contact your local telephone company.
EQUIPMENT MAINTENANCE FACILITY
Digital Security Controls Ltd.
160 Washburn St.
Lockport, NY 14094
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement