A-A000 SIC
 <<
GENIUS
DROW ENTERPRISE CO., LTD.
No.100, Alley 371, Lane 942, Ta Wan Road, Yung Kang City,
Tainan County 710-70, Taiwan, R.O.C.
TEL : +886-6-2724236.2728555.2055155 FAX: +886-6-2716310.2727160
E-mail:[email protected] http://www.genius.com.tw
UPS for Homes and Offices
Pure Sine Wave Inverter
WELCOME TO USE
HOME UPS
ve HARING NORA.
зе
SYSTEM TEST/MUTE
USER'S MANUAL
Model SIC-5KC SIC-6KC SIC-8KC
Capacity VA / Watt 5KVA / 4000W!| 6KVA / 6000W | 8KVA / 8000W
Battery Voltage 24Vdc 48Vdc
Backup Time (at full load) long time available
Battery
Max. Chargi
ax. Charging Current > 50A > BOA
(5 steps selectable)
UPS status, 1/P80/P Voltage Frequency,
Load?
LCD Battery Volt 2% o t
attery Voltage , arge current,
Display LCD y een 9
Temperature, Model
LED Normal (Green), Warning (Yellow), Fault (Red)
Battery Mode Beeping every 4 seconds
Low Battery Beeping every second
Audible Alarm
UPS Fault Beeping Continuously
Overload Beeping twice per second
Environment
Operation Temperature
0-40 degree C; 32-104 degree F
Relative Humidity
0-95% non-dondensing
Physical
Audible Noise Less than 55dBA (at 1M)
Net Weight (Kgs) 49.2Kg 51.4Kg 53.6Kg
(WxHxD)mm Wall Mounted 415*600*260 | 415*600*260 | 415*600*260
e Specifications are subjected to change without prior notice.
CONTENTS
Model SIC-5KC SIC-6KC SIC-8KC
Capacity VA / Watt 5KVA / 4000W | 6KVA / 6000W | 8KVA / 8000W
Nominal Voltage 220Vac; 110Vac 220Vac only
Acceptable Voltage
P 9 120-275Vac ; 60-135Vac 120-275Vac
Range
50Hz / 60Hz
Frequency 50Hz / 60Hz (45Hz - 70Hz)
(45Hz - 70Hz)
Input
pu Voltage | Line Low Transfer | 120VAC + 2% ; 60VAC +2% | 120VAC 2%
Range
Line Low Return 130VAC + 2% ; 65VAC + 2% 130VAC 2%
Line High Transfer | 275VAC + 2% ; 135VAC + 2% | 275VAC 2%
Line High Return 260VAC + 2% ; 130VAC + 2% | 260VAC 2%
220Vac (230V or 240VAC re-settable via LCD
panel);
Voltage .
110Vac (115V or 120VAC re-settable via LCD
panel)
Voltage Regulation .
< 3% RMS for entire battery voltage range
(Batt. Mode) ° ry vollage rang
Frequency 50Hz or 60Hz
F Regulati
requency Regulation +0.1Hz
Output (Batt. Mode)
Power Factor 0.8 1.0
Waveform Pure Sinewave
Effiecincy > 80%
Line Mode Circuit Breaker
Overload
Protection | Battery Mode | 110% - 150% for 30 sec. , >150% for 200ms
Transfer Time Typical <8 ms.
19
Multifunctional power inverter
1. INTRODUCTION emmm
TP 1
2. SAFTY INSTRUCTION er ere 2
3. CABLE CONNECTIÓN..............eeeen2nnneneneeeeeereneneee anne. 3
4. SYSTEM DESCRIPTION... ee... eeeenieeieneneeeaee. 4
5. UPS OPERATION .....o errr 9
6. TROUBLE SHOOTING GUIDE..................m meme 14
7. OPERATION MODES OF THE UPS ...........000.. 22... 16
8. SPECIFICATION OF HOME UPS... 17
1. INTRODUCTION
1.1 General Description
The Home UPS, a powerful all-in-one solution, delivers unsurpassed clean
true sine wave output power and combines this with a selectable multistage
battery charging current. Applicable for any kind of loads such as air
conditioner, home appliances, consumer electronic and office equipments.
This series features a durable&continuous 24 operation.
The built-in 5-stage intelligent charger automatically charges any type of
batteries without the risk of overcharge. The compact&modular design
makes utility interactive installations easier and more cost effective. It is a
high quality product that offers the best price/performance ratio in the
industry.
1.2 Key features
. Multiple microprocessor design base.
. Compatible with both linear&non-linear load.
. Stronger charger to support batteries of 500AH up.
. 24 hours operation on the inverter.
. DC start and automatic self-diagnostic function.
. THD less than 3%.
. High efficiency design to save electricity.
. Low heat dissipation in long time operation
© © “NX O Or SS WON =
. Design to operate under harsh environment
1.3 Important Notices
1. Read instructions carefully before operating the UPS.
2. UPS power connect instruction should be followed.
3. Please dont open the case to prevent danger.
5. Retain the load within the rating of UPS to prevent faults.
6. Keep the UPS clean and dry.
Model SIC-1.2KC SIC-2.4KC SIC-3.6KC
Capacit VA | Watt 1.2KVA/ 2.4KVA / 3.6KVA /
расту 800W 1600W 2400W
Battery Voltage 12Vdc 24Vdc 24Vdc
Backup Time (at full load) long time available
Battery
Max. Chargi t
ax. Charging Curren > 40A > BOA
(5 steps selectable)
UPS status, I/P&O/P Voltage Frequency,
Load%,
LCD Battery Volt & % “ch t
attery Voltage arge current,
Display LCD ry voltage & 7% 9
Temperature, Model
LED Normal (Green), Warning (Yellow), Fault (Red)
Battery Mode Beeping every 4 seconds
Low Battery Beeping every second
Audible Alarm
UPS Fault Beeping Continuously
Overload Beeping twice per second
Environment
Operation Temperature
0-40 degree C; 32-104 degree F
Relative Humidity
0-95% non-dondensing
Audible Noise
Less than 55dBA (at 1M)
Physical
Net Weight (Kgs)
14Kg 21Kg 23Kg
(WxHxD)mm Wall Mounted
298*400*150 | 298*450*190 | 298*450*190
e Specifications are subjected to change without prior notice.
8. SPECIFICATION OF HOME UPS
Model SIC-1.2KC SIC-2.4KC SIC-3.6KC
Capacit VA / Watt 1.2KVA/ 2.4KVA / 3.6KVA /
pac y 800W 1600W 2400W
Nominal Voltage 220Vac; 110Vac
Acceptable Voltage
Р 9 120-275Vac ; 60-135Vac
Range
Frequency 50Hz/60Hz (45Hz - 70HZ)
Input Voltage | Line Low Transfer 120VAC +2% ; 60VAC + 2%
Range
Line Low Return 130VAC + 2% ; 65VAC + 2%
Line High Transfer 275VAC + 2% ; 135VAC + 2%
Line High Return 260VAC + 2% ; 130VAC + 2%
220Vac (230V or 240VAC re-settable via LCD
Voltage panel)
9 110Vac (115V or 120VAC re-settable via LCD
panel)
Voltage Regulation
9 9 < 3% RMS for entire battery voltage range
(Batt. Mode)
Frequency 50Hz or 60Hz
F Regulati
requency Regulation +0 1Hz
Output (Batt. Mode)
Power Factor 0.8
Waveform Pure Sinewave
Effiecincy > 75% > 80%
Line Mode Circuit Breaker
Overload
Protection Battery Mode | 110% ~ 150% for 30 sec. , >150% for 200ms
Transfer Time Typical < 8 ms.
17
2. SAFTY INSTRUCTION
2.1 Transporting
1. Disconnect all power cables if necessary.
2. Be careful not to damage the UPS while transporting.
3. Don't move the UPS upside down.
4. Please transport the UPS system only in the original packaging (to protect
against shock and impact).
2.2 Positioning
1. Do not put the UPS on rugged or declined surface.
2. Do not install the UPS system near water or in damp environments.
3. Do not install the UPS system where it would be exposed to direct sunlight
or near heat.
4. Do not block off ventilation openings in the UPS systems housing and don
leave objects on the top of the UPS.
5. Keep the UPS far away from heat emitting sources.
6. Do not expose it to corrosive gas.
7. Ambient temperature : 0°C - 40°C
2.3 Installation
1. Connect the UPS system only to an earthed shockproof socket outlet.
2. Place cables in such a way that no one can step on or trip over them.
2.4 Operation
1. Do not disconnect the mains cable on the UPS system or the building wiring
socket outlet during operations since this would cancel the protective
earth of the UPS system and of all connected loads.
2. The UPS has its own internal power source (batteries). The output terminals
may be live even when the UPS is not connected to the AC supply.
3. Ensure that no fluids or other foreign objects can enter the UPS system.
2.5 Maintenance and Service
1. Caution - risk of electric shock.
Even after the unit is disconnected from the mains power supply (building
wiring socket outlet), components inside the UPS system are still connected
to the battery and are still electrically live and dangerous. Before carrying out
any kind of servicing and/or maintenance, disconnect the batteries and verify
that no current is present.
2. Batteries may cause electric shock and have a high short-circuit current.
Please take the precautionary measures specified below and any other
measures necessary when working with batteries:
- remove wristwatches, rings and other metal objects
- use only tools with insulated grips and handles.
3. CABLE CONNECTION
3.1 Inspection
1. The system may be installed and wired only by qualified electricians in
accordance with applicable safety regulations.
2. When installing the electrical wiring, please note the nominal amperage of
your incoming feeder.
3. Inspect the packaging carton and its contents for damage. Please inform
the transport agency immediately should you find signs of damage.
Please keep the packaging in a safe place for future use.
4. Please ensure that the incoming feeder is isolated and secured to prevent
it from being switched back on again.
3
7. OPERATION MODES OF THE UPS
7.1 UPS System Block Diagram
AC OUTPUT
| =
AC INPUT == A I i." |
р — — |
] meme] I >= ==
STATIC
N.F AC/DC DC/AC SWITCH
CHARGER INVERTER
1
BATTERY
7.2 Normal Operation
There are two main loops when AC utility is normal: the AC loop and the
battery charging loop. The AC output power comes from AC utility input and
passes through static switch to support power to load. The battery charging
voltage comes from AC utility input and converted by AC/DC charger to
support battery-charging power.
name L AC OUTPUT
ÁC INPUT | ==>] | ^, — —— —
[ — — ——
Il Е — = —
— — STATIC
N.F AC/DC DC/AC SWITCH
CHARGER INVERTER
BATTERY
7.3 AC Utility Failure (Battery Mode)
The AC output comes from battery, passing through DC/AC inverter and
| AC OUTPUT
static switch within the battery backup time.
AC INPUT [===
ee) ONES
Il = K
STATIC
N.F AC/DC DC/AC SWITCH
CHARGER INVERTER
BATTERY
16
No. UPS STATUS POSSIBLE CAUSE ACTION
AC utility power 1. AC utility power 1. Reduce the less
fails .The load is failure. critical load in
> supplied by battery 2. AC input order to extend
power. Buzzer alarm connection may backup time.
sounds every 4 be not correct. 2. Please check
seconds. the rated input or
connected line.
AC utility fails. UPS is Battery power is UPS will shut
in battery backup approaching low down
mode. Buzzer alarm level. automatically.
6 beeps every second. Please save data
or turn off the
loads soon.
AC utility power fails. Battery runs out UPS will restart up
7 UPS has shut down when AC utility
automatically.
power is restored.
15
3.2 Connection
1. UPS Input Connection
If the UPS is connected via the power cord, please use a proper socket
with protection against electric current, and pay attention to the capacity of
the socket.
2. UPS Output Connection
Simply plug the load power cord to the output to complete connection.
4. SYSTEM DESCRIPTION
4.1 Front Panel Description for LCD Model
ELLI zz ———
© ©
FAULT WARNING NORMAL
(5) » O © О <
— OFF —7— ON —
SYSTEM TEST/MUTE —A
{
Or
. LCD Display: This indicates the UPS operation information, including UPS
status, input/output voltage, input/output frequency, battery voltage,
battery capacity left, output load, inside temperature, and the times of
history events.
2. Up-key: Use to select upward the UPS status on LCD Display.
3. Down-key: Use to select downward the UPS status on LCD Display.
Beside, press it simultaneously with the Up-key to switch off the UPS.
. Enter-Key: It is pressed with the Down-key to turn on the UPS. In battery
operation mode, press it with Up-key at the same time to disable the
buzzer. Beside, it is pressed to confirm and enter the item selected.
. Fault LED (red): To indicate the UPS is in fault condition because of
inverter shutdown or over-temperature.
. Warning LED (yellow): To indicate the UPS is in the status of overload,
bypass and battery back-up.
7. Normal LED (green): To indicate the UPS is operating normally.
8. ON/TEST/MUTE key: It should be pressed with the control key
simultaneously to switch on UPS, do UPS auto-test in normal AC mode
and turn off the buzzer in battery operation.
6. TROUBLE SHOOTING GUIDE
6.1 For LCD Model
The following guideline may be helpful for basic problem solving.
No.
UPS STATUS
POSSIBLE CAUSE
ACTION
AC utility power is
normal. UPS is running
normally, but fault LED
lits up. Buzzer beeps
continuously.
1.Charger PCB is
damaged.
2.Fan is damaged.
3. Unknown
1. Replace the
charger PCB.
2. Replace the fan.
3. Restart UPS
AC utility power is
normal but UPS is
Overload
100%< load< 125%
Please reduce the
critical load to
lights up and buzzer
beeps continuously.
2 | overloaded. Warning <100%.
LED lights up and buzzer
beeps per second.
AC utility power is Overload Please reduce the
normal. Warning LED 125%< load<150% critical load to
3 | does not fade out and <100%.
buzzer beeps per 0.5
second.
AC utility power is Overload Please reduce the
a normal. Warning LED load> 150% critical load to
<100%.
14
Charging Current Adjust
A. In this screen, press Enter-key to
enter the following steps for
general battery AH adjustment.
B. The cursor (—) will pop up to
indicate the battery AH newly
selected.
C. Use Up or Down-key to select
the battery AH ( 100AH, 200AH,
300AH, 400AH, and 600AH
selectable). Press Enter-key to
confirm your battery AH.
D. Once the correct battery AH is
selected, press Enter-key again
to save the selection.
13
CHG. CURRENT SET
600AH
FAULT WARNING NORMAL
© © ©
— OFF — ON >
— SYSTEM TEST/MUTE —
CHG. CURRENT SET |
—600AH
FAULT WARNING NORMAL
— OF —— ON —
SYSTEM TEST/MUTE —
CHG. CURRENT SET
SAVE?YES
FAULT ~~ WARNING NORMAL
© © ©
— OF —— ON —
SYSTEM TEST/MUTE —
4.2 Outline
1.2KVA
Description
Wall Mounted Type
[-— (W>293mm—
+
TTT ER |
CAO @ >
150mm
Г] |
o 50 |
о <> ©
Г село
0 <> 0
(H)400mm
| o> 0
»
BATTERY(*) BATTERY() INTELLIGET SOLT
| Е (JI Bo
ШО ево
| L
SCLAR TERM
6
a ная
*
ОО ООО To
ООО ООО OU
=
|
| f
NI * косо
ef
le
2.4KVA / 3.6KVA Wall Mounted Type
—— (W) 228mm —
Ш
Ш
OA
|
o
190mm
OC 30
||
. +
2 o
o o |
©
Do
De
о <> ©
| о <= ©
. a
о == © |
—
.
о = 0
(H)450mm
[ о == ©
= VC
ШИЛО ОО
mo
Е.
A SOUL.
(LM
pare) + e ME
ER
BATTERY(-) —
-— REMOTE CONTROL
— BREAKER
Pu
SCLAR TERM
of
le
Output Voltage & Frequency Adjust
A. In this screen, press Enter-key to
enter the following steps for
output voltage and frequency
adjustment.
B. The cursor (—) will pop up to
indicate the output voltage and
frequency newly selected.
C. Use Up or Down-key to adjust
the output voltage (if 220V
configure, 220V, 230V, and 240V
is selectable; if 110V configure,
110V, 115V, and 120V is
selectable). Press Enter-key to
confirm voltage and then the
cursor will move to frequency
selection. The output frequency
(50Hz or 60Hz) can be adjusted
by the same key operation.
D. Once the correct voltage is
selected, press Enter-key again
to save the selection.
12
VOLT /FREQ SET
220Vac 50HZ
FAULT WARNING NORMAL
© © ©
— OFF —— ÓN >
SYSTEM TEST/MUTE —
VOLT / FREQ SET
—>220Vac 50HZ
FAULT WARNING NORMAL
© © ©
— OF —T ON—
— SYSTEM TEST/MUTE —
VOLT / FREQ SET
220Vac — 50HZ
FAULT ~~ WARNING NORMAL
© © ©
— OFF N—
|— SYSTEM TEST/MUTE —
Battery Status
BATTERY VOLTAGE
24 Vac
or Te ING a e
9 6 e
— О © 9 © —
Output Power
OUTPUT POWER
0%
or ve ING Not
30 a
— 9 © ) © —
History Record
NEW AC FAIL:0
REC OVERLOAD:0
"о "o ING No
9 6 a
— © © J) © —
11
BATTERY CAPACITY
100%
or “о ING AP e
30 ©
— О © ) © —
Temperature
INSIDE TEMP
33°C 91°F
or “о, ING AP e
30 ©
— О © ) © —
OLD AC FAIL:0
REC OVERLOAD:0
o "o ING a
30 a
— © © ) © —
SKVA / 6KVA / 8KVA Wall Mounted Type
!
>]
mi (E) mi (S)m| ©
=m |
q SUR DD NO ON ©
MI — mm |
. . C1
Го | à o]
0 еее 0
o O
Е
O O o
©
jé
=
O O
8 8
| © | Bad
е . —
nn
BATTERY(+) BATTERY()
a or
— ll — 0
BREAKER TERM
SJ
Ш
BE = © @- | J weer son
a
— REMOTE CONTROL
E
5. UPS OPERATION
5.1 Check Prior to Start Up
1. Ensure the UPS is in a suitable positioning.
2. Check input cord is secured.
3. Make sure the load is disconnected or in the "OFF" position.
4. Check if input voltage meets the UPS rating required.
5.2 Storage Instruction
Disconnect input power in rear panel if you will not use it for long period. If the
UPS is stored over 3 months, please keep supplying power to the UPS for at
least 24 hours to ensure battery fully recharged.
5.3 Operation Procedure for LCD Model
Please follow the instructions below for UPS operation.
1. Once the AC source is connected, the
LCD Display shall light up immediately
to display first the main menu of | | WELCOME TO USE | |
HOME UPS
greeting context and the Normal LED is
blinking to indicate ready to switch on "о "e “о”
606
© © TESTMUTE —
the inverter.
2. By pressing the Enter-key and the Down-key simultaneously for 3 seconds,
the UPS will start up after two beeps and Normal LED lights up to indicate
the power is from its inverter to the load.
3. When the Down-key and the Up-key are pressed simultaneously for 3
seconds, the inverter will be turned off after two beeps and the UPS is on
the standby status (LCD display illuminates and Normal LED is blinking)
until AC source is disconnected.
4. LCD Display Menu
Use Up/Down key to select menu-displays of the LCD described below. This
screen will refresh once the system power is enabled.
Rated Spec
INPUT:220v 50HZ
OUTPUT:220V 50HZ
o “5 ING Ne
© © TESTMUTE —
Voltage
INPUT VOLTAGE
220 Vac
"о “5 ING No
606
9 © 9 © —
Frequency
INPUT FREQUENCY
50HZ
o “5 ING бо
6006
© © TESTMUTE —
Status
AC:FAIL BAT:OK
LINE MODE
o о ING Ne
© © 9 © —
OUTPUT VOLTAGE
220 Vac
"о “о ING un
606
9 © 9 © —
OUTPUT FREQUENCY
50 HZ
"о “о ING No
606
9 © 9 © —