Allen-Bradley 1769-IQ32 is a Compact 32-point 24V dc Sink/Source Input Module designed for industrial applications. This module allows you to monitor and control up to 32 field devices, making it ideal for automation systems that require a large number of inputs. The module is compatible with a range of Allen-Bradley controllers and can be mounted on a panel or DIN rail. It is also suitable for use in hazardous locations.
Advertisement
Advertisement
Installation Instructions
Compact 32-point 24V dc Sink/Source
Input Module
Catalog Number 1769-IQ32
Use this document as a guide when installing a Compact™ 32-point 24V dc sink/source input module.
Topic
Important User Information
Replacing a Single Module within a System
Spare/Replacement Module Parts
Hazardous Location Considerations
Page
2
Publication 1769-IN032A-EN-P - April 2003
2 Compact 32-point 24V dc Sink/Source Input Module
Important User Information
Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Rockwell Automation be responsible or liable for indirect or consequential damage resulting from the use or application of these products.
Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of
Solid-State Control (available from your local Rockwell Automation office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of
Rockwell Automation, is prohibited.
Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a potential hazard:
WARNING
!
ATTENTION
!
IMPORTANT
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Publication 1769-IN032A-EN-P - April 2003
Compact 32-point 24V dc Sink/Source Input Module 3
Module Description
5a
9
7a
7b
8a
1
10a
10b
10
8b
7b
7a
2a
WARNING -Do Not
Remove RTB Unless
Area is Non-Hazardous
IN 1
IN 0
IN 17
IN 2
IN 3 IN 19
IN 4
IN 5 IN 21
IN 6
IN 7
IN 9
IN 11
IN 13
IN 15
DC COM
IN 23
DC COM
IN 25
IN 8
IN 27
IN 10
IN 29
IN 12
IN 31
IN 14
DC COM
IN 16
IN 18
IN 20
IN 22
DC COM
IN 24
IN 26
IN 28
IN 30
1769-IQ32
3
4
2b
6
5b
30538-M
3
4
Item Description
1 bus lever
(with locking function)
2a
2b upper panel mounting tab lower panel mounting tab
5a
5b
I/O diagnostic LEDs module door with terminal identification label movable bus connector with female pins stationary bus connector with male pins
6
7a
7b nameplate label upper tongue-and-groove slots lower tongue-and-groove slots upper DIN rail latch lower DIN rail latch
8a
8b
9
10 write-on label (user ID tag) removable terminal block (RTB) with finger-safe cover
10a RTB upper retaining screw
10b RTB lower retaining screw
Publication 1769-IN032A-EN-P - April 2003
4 Compact 32-point 24V dc Sink/Source Input Module
Module Installation
Compact I/O is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use in clean, dry environments (Pollution degree 2
(1)
) and to circuits not exceeding
Over Voltage Category II
(2)
(IEC 60664-1).
(3)
Prevent Electrostatic Discharge
ATTENTION
!
Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins. Follow these guidelines when you handle the module:
–
Touch a grounded object to discharge static potential.
–
Wear an approved wrist-strap grounding device.
–
Do not touch the bus connector or connector pins.
–
Do not touch circuit components inside the module.
–
If available, use a static-safe work station.
–
When not in use, keep the module in its static-shield box.
Remove Power
ATTENTION
!
Remove power before removing or inserting this module.
When you remove or insert a module with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
–
sending an erroneous signal to your system’s field devices, causing unintended machine motion
–
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance.
(1)
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation shall be expected.
(2)
Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3)
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
Publication 1769-IN032A-EN-P - April 2003
Compact 32-point 24V dc Sink/Source Input Module 5
System Assembly
The module can be attached to the controller or an adjacent I/O module before or
after mounting. For mounting instructions, see
Panel Mounting on page 6, or DIN
Rail Mounting on page 8. To work with a system that is already mounted, see
Replacing a Single Module within a System on page 8.
The following procedure shows you how to assemble the Compact I/O system.
3
4
2
1
6
1
5
30536-M
1. Disconnect power.
2. Check that the bus lever of the module to be installed is in the unlocked
(fully right) position.
3. Use the upper and lower tongue-and-groove slots (1) to secure the modules together (or to a controller).
4. Move the module back along the tongue-and-groove slots until the bus connectors (2) line up with each other.
5. Push the bus lever back slightly to clear the positioning tab (3). Use your fingers or a small screw driver.
6. To allow communication between the controller and module, move the bus lever fully to the left (4) until it clicks. Ensure it is locked firmly in place.
ATTENTION
!
When attaching I/O modules, it is very important that the bus connectors are securely locked together to ensure proper electrical connection.
Publication 1769-IN032A-EN-P - April 2003
6 Compact 32-point 24V dc Sink/Source Input Module
7. Attach an end cap terminator (5) to the last module in the system by using the tongue-and-groove slots as before.
8. Lock the end cap bus terminator (6).
IMPORTANT
A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the end of the serial communication bus.
Mounting Expansion I/O
ATTENTION
!
During panel or DIN rail mounting of all devices, be sure that all debris (metal chips, wire strands, etc.) is kept from falling into the module. Debris that falls into the module could cause damage on power up.
Minimum Spacing
Maintain spacing from enclosure walls, wireways, adjacent equipment, etc. Allow 50 mm (2 in.) of space on all sides for adequate ventilation, as shown:
Side
Controller
Top
Bottom
Side
Panel Mounting
Mount the module to a panel using two screws per module. Use M4 or #8 panhead screws. Mounting screws are required on every module.
Publication 1769-IN032A-EN-P - April 2003
Compact 32-point 24V dc Sink/Source Input Module 7
Panel Mounting Using the Dimensional Template
Spacing for single-wide modules 35mm (1.378 in.)
Spacing for one-and-a half-wide modules 52.5mm (2.067 in.)
Refer to host controller documentation for this dimension.
Note: Overall hole spacing tolerance:
±0.4mm (0.016 in.).
Locate holes every 17.5 mm (0.689 in.) to allow for a mix of single-wide and one-and-a-half-wide modules (e.g., 1769-OA16).
Panel Mounting Procedure Using Modules as a Template
30535-M
This procedure lets you use the assembled modules as a template for drilling holes in the panel. If you have sophisticated panel mounting equipment, you can use the dimensional template provided on page 7. Due to module mounting hole tolerance, it is important to follow these procedures:
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel, and check for proper hole alignment.
6. Attach the modules to the panel using the mounting screws.
Publication 1769-IN032A-EN-P - April 2003
8 Compact 32-point 24V dc Sink/Source Input Module
NOTE: If mounting more modules, mount only the last one of this group and put the others aside. This reduces remounting time during drilling and tapping of the next group.
7. Repeat steps 1 to 6 for any remaining modules.
DIN Rail Mounting
The module can be mounted using these DIN rails:
35 x 7.5 mm (EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latches. Press the DIN rail mounting area of the module against the DIN rail. The latches will momentarily open and lock into place.
Replacing a Single Module within a System
The module can be replaced while the system is mounted to a panel (or DIN rail).
1. Remove power. See important note on page 4.
2. On the module to be removed, remove the upper and lower mounting screws from the module (or open the DIN latches using a flat-blade or phillips style screw driver).
3. Move the bus lever to the right to disconnect (unlock) the bus.
4. On the right-side adjacent module, move its bus lever to the right (unlock) to disconnect it from the module to be removed.
5. Gently slide the disconnected module forward. If you feel excessive resistance, check that the module has been disconnected from the bus, and that both mounting screws have been removed (or DIN latches opened).
NOTE: It may be necessary to rock the module slightly from front to back to remove it, or, in a panel-mounted system, to loosen the screws of adjacent modules.
6. Before installing the replacement module, be sure that the bus lever on the module to be installed, and on the right-side adjacent module are in the unlocked (fully right) position.
7. Slide the replacement module into the open slot.
Publication 1769-IN032A-EN-P - April 2003
Compact 32-point 24V dc Sink/Source Input Module 9
8. Connect the modules together by locking (fully left) the bus levers on the replacement module and the right-side adjacent module.
9. Replace the mounting screws (or snap the module onto the DIN rail).
Field Wiring Connections
Grounding the Module
This product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used), are not required unless the mounting surface cannot be grounded. Refer to Industrial Automation Wiring and Grounding Guidelines,
Allen-Bradley publication 1770-4.1, for additional information.
Input Wiring
Basic wiring of input devices
(1)
to the 1769-IQ32 is shown below.
ATTENTION
!
–
Miswiring of the module to an AC power source will damage the module.
–
Be careful when stripping wires. Wire fragments that fall into a module could cause damage at power up. Once wiring is complete, ensure the module is free of all metal fragments.
(1)
Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the field device.
Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are driven by a current sourcing field device. Field devices connected to the negative side (DC Common) of the field power supply are sinking field devices.
Field devices connected to the positive side (+V) of the field supply are sourcing field devices. Europe: DC sinking input and sourcing output module circuits are the commonly used options.
Publication 1769-IN032A-EN-P - April 2003
10 Compact 32-point 24V dc Sink/Source Input Module
1769-IQ32
+DC (Sinking)
– DC (Sourcing)
+ DC (Sinking)
– DC (Sourcing)
IN 1
IN 3
IN 5
IN 7
IN 0
IN 2
IN 4
IN 6
DC
COM 1
24Vdc
IN 9
IN 11
IN 13
IN 15
DC
COM 2
IN 8
IN 10
IN 12
IN 14
– DC (Sinking)
+ DC (Sourcing)
24Vdc
– DC (Sinking)
+ DC (Sourcing)
+DC (Sinking)
– DC (Sourcing)
+ DC (Sinking)
– DC (Sourcing)
IN 17
IN 19
IN 21
IN 23
IN 16
IN 18
IN 20
IN 22
DC
COM 3
24Vdc
– DC (Sinking)
+ DC (Sourcing)
IN 25
24Vdc
IN 27
IN 29
IN 24
IN 26
IN 28
IN 31
DC
COM 4
IN 30
– DC (Sinking)
+ DC (Sourcing)
30530-M
A removable write-on label is included with the module. Remove the label from the door, mark the identification of each terminal with permanent ink, and slide the label back into the door. Your markings (ID tag) will be visible when the module door is closed.
R SLOT# L
MODULE TYPE
Publication 1769-IN032A-EN-P - April 2003
30517-M
Compact 32-point 24V dc Sink/Source Input Module 11
Removing the Finger-safe Terminal Block
When wiring field devices to the module, it is not necessary to remove the terminal block. If you remove the terminal block, use the write-on label on the side of the terminal block to identify the module slot lcation and type. RTB position can be indicated by circling either the ‘R’ for right side or ‘L’ for left side.
To remove the terminal block, loosen the upper and lower retaining screws. The terminal block will back away from the module as you remove the screws. When replacing the terminal block, torque the retaining screws to 0.46 Nm (4.1 in-lbs).
Wiring the Finger-safe Terminal Block
upper retaining wiring the finger-safe terminal lower retaining
When wiring the terminal block, keep the finger-safe cover in place.
1. Loosen the terminal screws to be wired.
2. Route the wire under the terminal pressure plate. You can use the bare wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.
NOTE: The terminal screws are non-captive. Therefore, it is possible to use a ring lug [max. 1/4” o.d. with a 0.139” minimum i.d. (M3.5)] with the module.
3. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.68 Nm (6 in-lbs).
NOTE: If you need to remove the finger-safe cover, insert a screw driver into one of the square, wiring holes and gently pry the cover off. If you wire the terminal block with the finger-safe cover removed, you will not be able to put it back on the terminal block because the wires will be in the way.
Publication 1769-IN032A-EN-P - April 2003
12 Compact 32-point 24V dc Sink/Source Input Module
Wire Size and Terminal Screw Torque
Each terminal accepts as many as two wires with these restrictions:
Wire Type
Solid Cu-90°C (194°F)
Stranded Cu-90°C (194°F)
Wire Size
#14 to #22 AWG
#16 to #22 AWG
Terminal Screw
Torque
0.68 Nm (6 in-lbs)
0.68 Nm (6 in-lbs)
Retaining Screw
Torque
0.46 Nm (4.1 in-lbs)
0.46 Nm (4.1 in-lbs)
I/O Memory Mapping
Input Data File
For each input module, slot x, word 0 in the input data file contains the current state of the field input points.
0
1 r=read
15 14 13 12 11 10 9
r r r r r r r r r r r r r r
Bit Position
8 7
r r r r
6
r r
5
r r
4
r r
3
r r
2
r r
1
r r
0
r r
Spare/Replacement Module Parts
• Terminal Block: 1769-RTBN18 (1 per kit)
Publication 1769-IN032A-EN-P - April 2003
Compact 32-point 24V dc Sink/Source Input Module 13
Specifications
General Specifications
Dimensions
Specification Value
118 mm (height) x 87 mm (depth) x 52.5 mm (width) height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 2.07 in (width) height including mounting tabs is 5.43 in.
440g (0.97 lbs.) Approximate Shipping Weight
(with carton)
Storage Temperature
Operating Temperature
Operating Humidity
Operating Altitude
Vibration
Shock
Agency Certification
Hazardous Environment Class
Radiated and Conducted Emissions
Electrical /EMC:
ESD Immunity (IEC1000-4-2)
Radiated Immunity (IEC1000-4-3)
Fast Transient Burst (IEC1000-4-4)
Surge Immunity (IEC1000-4-5)
Conducted Immunity (IEC1000-4-6)
-40°C to +85°C (-40°F to +185°F)
0°C to +60°C (32°F to +140°F)
5% to 95% non-condensing
2000 meters (6561 feet)
Operating: 10 to 500 Hz, 5G, 0.030 inches maximum peak-to-peak
Relay Operation: 2G
Operating: 30G panel mounted (20G DIN rail mounted)
Relay Operation: 7.5G panel mounted (5G DIN rail mounted)
Non-Operating: 40G panel mounted (30G DIN rail mounted)
• C-UL certified (under CSA C22.2 No. 142)
• UL 508 listed
• CE compliant for all applicable directives
Class I, Division 2, Hazardous Location, Groups A, B, C, D
(UL 1604, C-UL under CSA C22.2 No. 213)
EN50081-2 Class A
The module has passed testing at the following levels:
4kV contact, 8 kV air, 4 kV indirect
10 V/m, 80 to 1000 MHz, 80% amplitude modulation, +900
MHz keyed carrier
2 kV, 5 kHz
2 kV common mode, 1 kV differential mode
10V, 0.15 to 80 MHz
(1)
(1)
Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to
1000 MHz.
Publication 1769-IN032A-EN-P - April 2003
14 Compact 32-point 24V dc Sink/Source Input Module
Input Specifications
Specification 1769-IQ32
Voltage Category
Operating Voltage Range
Number of Inputs
Bus Current Draw (max.)
Heat Dissipation
Signal Delay (max.)
24V dc (sink/source
(1)
)
10 to 30V dc at 30°C (86°F)
10 to 26.4V dc at 60°C (140°F)
32
170 mA at 5V dc (0.85W)
4.6 Total Watts (The Watts per point, plus the minimum Watts, with all
points energized.)
On Delay: 8.0 ms
Off Delay: 8.0 ms
5V dc
1.5 mA
10V dc
2.0 mA
Off-State Voltage (max.)
Off-State Current (max.)
On-State Voltage (min.)
On-State Current (min.)
Inrush Current (max.)
Nominal Impedance
IEC Input Compatibility
Power Supply Distance Rating
250 mA
5.2kohm at 24V dc, 6.1kohm at 30V dc
Type 1+
8 (The module may not be more than 8 modules away from the power supply or controller.)
Input Point to Bus (Compact Bus)
Isolation
Isolated Groups
Verified by one of the following dielectric tests: 1200V ac for 1 sec. or
1697V dc for 1 sec.
75V dc working voltage (IEC Class 2 reinforced insulation)
Group 1: inputs 0 to 7
Group 2: inputs 8 to 15
Group 3: inputs 16 to 23
Group 4: inputs 24 to 31
Isolated groups operate in either sink or source configurations.
Input Group to Input Group Isolation Verified by one of the following dielectric tests: 1200V ac for 1 sec. or
1697V dc for 1 sec.
75V dc working voltage (IEC Class 2 reinforced insulation)
Vendor I.D. Code
Product Type Code
Product Code
1
7
68
(1)
Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the field device.
Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are driven by a current sourcing field device. Field devices connected to the negative side (DC Common) of the field power supply are sinking field devices. Field devices connected to the positive side (+V) of the field supply are sourcing field devices. Europe: DC sinking input and sourcing output module circuits are the commonly used options.
Publication 1769-IN032A-EN-P - April 2003
Compact 32-point 24V dc Sink/Source Input Module 15
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations.
WARNING
!
EXPLOSION HAZARD
• Substitution of components may impair suitability for
Class I, Division 2.
• Do not replace components or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
• Do not connect or disconnect components unless power has been switched off or the area is known to be non-hazardous.
• This product must be installed in an enclosure.
• All wiring must comply with N.E.C. article 501-4(b).
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements de Classe 1,
Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante s’applique à une utilisation dans des environnements dangereux.
AVERTISSEMENT
!
DANGER D’EXPLOSION
• La substitution de composants peut rendre cet équipement impropre à une utilisation en environnement de Classe 1,
Division 2.
• Ne pas remplacer de composants ou déconnecter l'équipement sans s'être assuré que l'alimentation est coupée et que l'environnement est classé non dangereux.
• Ne pas connecter ou déconnecter des composants sans s'être assuré que l'alimentation est coupée ou que l'environnement est classé non dangereux.
• Ce produit doit être installé dans une armoire.
Publication 1769-IN032A-EN-P - April 2003
For More Information
For Refer to this Document Pub. No.
A more detailed description of how to install and use your Compact I/O with MicroLogix
1200 & 1500 programmable controller.
MicroLogix 1200 and MicroLogix
1500 Programmable Controllers User
Manual
1764-RM001B-US-P
A more detailed description of how to install and use your Compact I/O with the
1769-ADN DeviceNet Adapter.
1769-ADN DeviceNet Adapter User
Manual
1769-UM001A-US-P
A more detailed description of how to install and use your Compact I/O with the
CompactLogix™ System.
CompactLogix System User Manual 1769-UM007C-EN-P
More information on proper wiring and grounding techniques.
Industrial Automation Wiring and
Grounding Guidelines
1770-4.1
If you would like a manual, you can:
• download a free electronic version from the internet: www.ab.com/micrologix or www.theautomationbookstore.com
• purchase a printed manual by:
– contacting your local distributor or Rockwell Automation representative
– visiting www.theautomationbookstore.com and placing your order
– calling 1.800.9NEWLIT(800.963.9548) (USA/Canada) or 001.330.725.1574 (Outside USA/Canada)
Compact and MicroLogix are trademarks of Rockwell Automation.
Publication 1769-IN032A-EN-P - April 2003 PN 40071-154-01(1)
Copyright © 2003 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
´H'+V!¶1®¨

Download
Advertisement
Key features
- 32 input points
- 24V dc sink/source
- Compact size
- Panel & DIN rail mounting
- Hazardous location certification
- Isolated input groups
- Finger-safe terminal block
- Write-on label for identification