Delivery programme Technical data

Delivery  programme Technical  data
Touch�panel,�24�V�DC,�5.7z,�TFTcolor,�ethernet,�RS485,�profibus,�SWDT,
PLC
Delivery�programme
Part�no. Article�no. Catalog�No. XV-102-E8-57TVRC-10
153526
XV-102-E8-57TVRC-10
Model
Insulating enclosure and front plate
Subrange
SmartWire-DT touch display with integrated controller (HMI PLC)
Function
SmartWire-DT coordinator
Product range
Visualisation solutions
SmartWire-DT Communication System
Front type
Standard front with standard membrane (fully enclosed)
Screen diagonal
Inch
5.7
Resolution
Pixel
VGA
640 x 480
built-in interfaces
1 x Ethernet 100base-TX/10base-T
1 x USB device
1 x RS485
1 x PROFIBUS/MPI
1 x USB host
1 x SmartWire-DT
Display - Type
Color display, TFT
Screen diagonal
Inch
5.7
Resolution
Pixel
VGA
640 x 480
Visible screen area
mm
115 x 86
Number of colours
64 k Colours
Contrast ratio (Normally)
Normally 300:1
Brightness
cd/m
Normally 250
Back-lighting
LED
dimmable via software
Service life of back-lighting
h
Normally 40000
Resistive touch protective screen
Touch sensor (glass with foil)
Technology
Resistive-Touch
4 Drath
Processor
RISC CPU, 32 Bit, 400 MHz
Internal memory
DRAM (OS, Program and data memory): 64 MByte
NAND-Flash (can be used for data backup): approx. 128 MByte available
NVRAM (retained data): approx. 32 KByte available
External memory
SD Memory Card Slot: SDA Specification 1.00
Back-up of real-time clock
Battery (service life)
Zero maintenance
Backup (time at zero voltage)
Normally 10 years
Operating system
Windows CE 5.0 (licence incl.)
Visualisation software
GALILEO
EPAM
XSOFT-CODESYS-2
XSOFT-CODESYS-3
PLC-Programming software
XSOFT-CODESYS-2
XSOFT-CODESYS-3
Target and web visualization
Yes
built-in interfaces
1 x Ethernet 100base-TX/10base-T
1 x USB device
1 x RS485
1 x PROFIBUS/MPI
1 x USB host
1 x SmartWire-DT
02/21/2015
153526 - HPL-ED2014 V9.0 EN
Technical�data
Display
Operation
System
Engineering
Interfaces,�communication
2
1/6
PLC-licence
PLC licence inclusive
USB Host
USB 2.0 (1.5 - 12 Mbit/s), not galvanically isolated
USB device
USB 2.0, not galvanically isolated
CAN
no
Profibus
Yes
RS485 (COM port)
Yes
Slots
for SD card: 1
SmartWire-DT master
Yes
Ethernet
100Base-TX/10Base-T
easyNet
no
MPI
Yes
Nominal voltage
24 V DC SELV (safety extra low voltage)
permissible voltage
Effective: 19.2-30.0 V DC (rated operating voltage -20%/+25%)
Absolute with ripple: 18,0-31,2 V DC
Battery powered: 18,0-31,2 V DC (rated operating voltage -25%/+30%)
35 V DC for a duration of < 100 ms
Voltage dips
ms
≤ 10 ms from rated voltage (24 V DC)
5 ms from undervoltage (20.4 V DC)
Power consumption
Pmax.
W
10
Note on power consumption
Basic device
USB Slave to USB Host: 2.5
Total: 9.5
Siemens MPI, (optional)
yes
Type of fuse
Yes (fuse not accessible)
Potential isolation
no potential isolation
Heat dissipation
W
9.5
Note on heat dissipation
Heat dissipation with power consumption for 24 V
7 W for basic device + 2.5 W for USB module
Housing material
Plastic, gray
Front type
Standard front with standard membrane (fully enclosed)
Weight
kg
0.6
Degree of protection (IEC/EN 60529, EN50178, VBG 4)
IP65 (at front), IP20 (at rear)
Approvals
Approvals
cUL (UL508)
Explosion protection (according to ATEX 94/9/EC)
II 3D Ex II T70°C IP5x: Zone 22, Category 3D
EMC
(in relation to CE)
EN 61000-6-2
EN 61000-6-4
EN 61131-2
Explosion protection (relevant for CE)
EN 60079-0
EN 61241-1
EN 13463_x
Product standards
EN 50178
EN 61131-2
Security
EN 60950
UL 60950
Mechanical shock resistance
g
according to IEC 60068-2-27
Vibration
according to IEC/EN 60068-2-6
Temperature
Operation
ϑ
°C
0 - +50
Storage / Transport
ϑ
°C
-20 - +60
%
10 - 95%, non-condensing
Rated operational voltage
UAux
V
24 V DC (-20/+25%)
Residual ripple on the input voltage
%
Protection against polarity reversal
02/21/2015
153526 - HPL-ED2014 V9.0 EN
Power�supply
General
Applied standards and directives
Environmental�conditions
Relative humidity
Relative humidity
Supply�voltage�UAux
5
Yes
2/6
Max. current
Imax
A
3
Note
If contactors with a total power consumption > 3 A are connected, a power feeder
module EU5C-SWD-PF1/2 has to be used.
Short-circuit rating
no, external fuse FAZ Z3
Potential isolation
No
Rated operating voltage of 24-V-DC slaves
V
typ. UAux - 0.2
Supply voltage
UPow
V
24 DC -20 % + 25 %
Input voltage ripple
%
Siemens MPI, (optional)
yes
Rated current
I
A
0.7
Overload proof
yes
Inrush current and duration
A
12.5 A/6 ms
Heat dissipation at 24 V DC
W
1.0
Potential isolation between UPow and 15 V SmartWire-DT supply voltage
No
Bridging voltage dips
ms
10
Repetition rate
s
1
Status indication
LED
yes
Rated operating voltage
Ue
V
14,5 ± 3 %
max. current
Imax
A
0.7
Note
If SmartWire-DT modules with a total power consumption > 0.7 A are connected, a
power feeder module EU5C-SWD-PF2 has to be used.
Short-circuit rating
Yes
Connection type
Solid
mm
Flexible with ferrule
UL/CSA solid or stranded
Supply�voltage�UPow
SmartWire-DT�supply�voltage
Connection�supply�voltages
5
Push in terminals
2
0.2 - 1.5
mm
2
0.25 - 1.5
AWG
24 - 16
Station type
SmartWire-DT master
Number of SmartWire-DT slaves
99
Baud Rates
kBd
125
250
Address allocation
automatic
Status indication
LED
SmartWire-DT master LED: green
Configurations LED: red
Connections
Plug, 8-pole
Plug connectors
Blade terminal SWD4-8MF2
SmartWire-DT�network
Data�for�design�verification�according�to�IEC/EN�61439
Technical data for design verification
Rated operational current for specified heat dissipation
In
A
0
Heat dissipation per pole, current-dependent
Pvid
W
0
Equipment heat dissipation, current-dependent
Pvid
W
0
Static heat dissipation, non-current-dependent
Pvs
W
9.5
Heat dissipation capacity
Pdiss
W
0
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
02/21/2015
153526 - HPL-ED2014 V9.0 EN
3/6
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical�data�ETIM�5.0
PLC's (EG000024) / Graphic panel (EC001412)
Electric engineering, automation, process control engineering / Control / Operate and Observe (HMI) / Graphic panel (HMI) ([email protected] [BAA722009])
Supply voltage AC 50 Hz
V
0-0
Supply voltage AC 60 Hz
V
0-0
Supply voltage DC
V
20.4 - 28.8
Voltage type of supply voltage
DC
Number of HW-interfaces industrial Ethernet
1
Number of HW-interfaces PROFINET
0
Number of HW-interfaces RS-232
0
Number of HW-interfaces RS-422
0
Number of HW-interfaces RS-485
1
Number of HW-interfaces serial TTY
0
Number of HW-interfaces USB
2
Number of HW-interfaces parallel
0
Number of HW-interfaces Wireless
0
Number of HW-interfaces other
1
With SW interfaces
Yes
Supporting protocol for TCP/IP
Yes
Supporting protocol for PROFIBUS
Yes
Supporting protocol for CAN
No
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for KNX
No
Supporting protocol for MODBUS
Yes
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
No
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for PROFINET IO
No
Supporting protocol for PROFINET CBA
No
Supporting protocol for SERCOS
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
Yes
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
02/21/2015
153526 - HPL-ED2014 V9.0 EN
4/6
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for other bus systems
Yes
Radiostandard Bluetooth
No
Radiostandard WLAN 802.11
No
Radiostandard GPRS
No
Radiostandard GSM
No
Radiostandard UMTS
No
IO link master
No
Type of display
TFT
With colour display
Yes
Number of colours of the display
65536
Number of grey-scales/blue-scales of display
0
Screen diagonal
inch
7
Number of pixels, horizontal
640
Number of pixels, vertical
480
Useful project memory/user memory
kByte
64000
With numeric keyboard
Yes
With alpha numeric keyboard
Yes
Number of function buttons, programmable
0
With system buttons
No
Buttons with LED
No
With touch screen
Yes
With message indication
Yes
With message system (incl. buffer and confirmation)
Yes
Process value representation (output) possible
Yes
Process default value (input) possible
Yes
With recipes
Yes
Number of password levels
200
Printer output available
Yes
Number of online languages
100
Additional software components, loadable
Yes
Degree of protection (IP), front side
IP65
Operation temperature
°C
0 - 50
Rail mounting possible
No
Wall mounting/direct mounting
No
Suited for safety functions
No
Width of the front
mm
170
Height of the front
mm
130
Built-in depth
mm
34
Product Standards
UL508, cULus; IEC/EN 61131-2, CE
UL File No.
E205091
UL Category Control No.
NRAQ
CSA File No.
UL report applies to US and Canada
CSA Class No.
-
North America Certification
UL listed, certified by UL for use in Canada
Degree of Protection
IEC:IP20, UL/CSA Tape: open type
02/21/2015
153526 - HPL-ED2014 V9.0 EN
Approvals
5/6
Dimensions
Additional�product�information�(links)
IL04802004Z�Instruction�leaflet
IL04802004Z Instruction leaflet
ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL04802004Z2013_03.pdf
MN04802004Z�Operator�manual�XV-102
MN04802004Z Betriebsanleitung XV-102 Deutsch
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN04802004Z_DE.pdf
MN04802004Z Operator manual XV-102 English
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN04802004Z_EN.pdf
MN04802013Z�quick-start�instructions�XV100
MN04802013Z Schnellstartanleitung XV100 Deutsch
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN04802013Z_DE.pdf
MN04802013Z quick-start instructions XV100 - ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN04802013Z_EN.pdf
English
MN04802091Z�User�manual�XSoft-CoDeSys-2,�PLC�programming�XV100
MN04802091Z User manual XSoft-CoDeSys-2,
PLC programming XV100
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN04802091Z-DE_2010-12.pdf
MN04802091Z User manual XSoft-CoDeSys-2,
PLC programming XV100
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN04802091Z-DE_2012-05.pdf
MN04802091Z User manual XSoft-CoDeSys-2,
PLC programming XV100
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN04802091Z-DE_2014-05.pdf
MN04802091Z User manual XSoft-CoDeSys-2,
PLC programming XV100
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN04802091Z-EN_2010-12.pdf
MN04802091Z User manual XSoft-CoDeSys-2,
PLC programming XV100
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN04802091Z-EN_2012-05.pdf
MN04802091Z User manual XSoft-CoDeSys-2,
PLC programming XV100
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN04802091Z-EN_2014-05.pdf
MN048008ZU�Manual�XSOFT-CODESYS-3,�PLC�programming
MN048008ZU Handbuch XSOFT-CODESYS-3,
SPS-Programmierung - Deutsch
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN048008ZU_DE.pdf
MN048008ZU Manual XSOFT-CODESYS-3, PLC ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN048008ZU_EN.pdf
programming - English
02/21/2015
Eaton Industries GmbH
http://www.eaton.eu
© 12/2014 by Eaton Industries GmbH
153526 - HPL-ED2014 V9.0 EN
6/6
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF