RPL: RCS, RDT, RFS, RPS, Sizes 080-135

RPL: RCS, RDT, RFS, RPS, Sizes 080-135
Replacement Parts List No. 7000070
Revision AG 01/15
Roofpak
Applied Rooftop Units
RCS, RDT, RFS, RPS
Sizes 080 - 135 Tons
Vintage C
To find your Daikin Applied parts distributor, call 1- 800-377-2787 or visit www.DaikinApplied.com
Contents
Parts List Revision History....................................................................................................................................................... 6
Nomenclature ........................................................................................................................................................................ 7- 15
Electrical Legend ................................................................................................................................................................. 16- 20
Section A- Outdoor/Return Air Section
Notes
................................................................................................................................................................................ 21
100% Outside Air Damper with Hood- No Return Air Plenum.......................................................................................... 22
100% Outside Air Damper ................................................................................................................................................ 23
0- 30% Outside Air Section w/ ACT3................................................................................................................................ 24
0- 100% Economizer Section with Barometric Exhaust Damper- Units without Return Air Fans..................................... 25
0- 100% Economizer Section with Barometric Exhaust Damper- Units with 44” Return Air Fans.................................... 26
0- 100% Economizer Section with Prop Exhaust Fan & Damper ..................................................................................... 27
0- 100% Economizer Damper- Diagrams ......................................................................................................................... 28
0- 100% Economizer Damper w/ ACT3- Components ..................................................................................................... 29
0- 100% Economizer Exhaust Damper (Until 1/05) .................................................................................................... 30, 31
Return Air Plenum Isolation Damper w/ Actuator ACT6.................................................................................................... 32
Prop Exhaust Fan, Damper & Inverter.............................................................................................................................. 33
Prop Exhaust Fan Control Box ......................................................................................................................................... 34
Design Flow ...................................................................................................................................................................... 35
Return Air Fan Detail- Fan Mounts (Until 11/04)............................................................................................................... 36
Return Air Fan Detail- Fan Mounts (11/04 & Later) .......................................................................................................... 37
Return Air Fan: Code 21= 44B*, 44W*.............................................................................................................................. 38
Return Air Fan Motors ...................................................................................................................................................... 39
Section Mounted Controls- OAE, RAE, RAT, SD2, LT11, S11, REC11........................................................................... 40
Section B- Draw-Thru Filter/Blank Section
Notes
................................................................................................................................................................................ 41
Section Mounted Controls- PC5, SPS5- Clogged Filter Static Pressure Sensor.............................................................. 41
Filters
.......................................................................................................................................................................... 42, 43
Section C- Draw-Thru Blank Access Section OR Separate Inverter Section
Notes
................................................................................................................................................................................ 44
Unit Mounted Controls- LT17, S17, REC17...................................................................................................................... 44
Section D- Draw-Thru Cooling Section
Notes
................................................................................................................................................................................ 45
Evaporator Coils, Drain Pans, Gasketing
Small Face DX Coils: Code 03= S, Unit Sizes 080, 090.............................................................................................. 46
Small Face DX Coils: Code 03= S, Unit Sizes 105, 115........................................................................................ 47, 48
Large Face DX Evaporator Coils: Code 03= L, Unit Sizes 080- 135 ..................................................................... 49, 50
Section E- 48” Spacer Section or Draw-Thru Heat Section- RDT Units
................................................................................................................................................................................ 51
Notes
Section Mounted Controls- LT18, REC18, S18 ................................................................................................................ 51
Hot Water OR Steam Coil Heat, Mixing Valves & Actuator (VM1).............................................................................. 52, 53
Section F- Supply Air Section
Notes
................................................................................................................................................................................ 54
Forward Curved Fans- Low Pressure (FCLP) .................................................................................................................. 55
Forward Curved Fans- High Pressure (FCMP)................................................................................................................. 56
Air Foil Fan- Double Width.......................................................................................................................................... 57, 58
Air Foil- Double Width- VAV Assembly............................................................................................................................. 59
Air Foil Fan- Single Width- RDT (Draw-Thru/No Heat) Units...................................................................................... 60, 61
Air Foil- Single Width- VAV Assembly............................................................................................................................... 62
Fan Mounts- 33” Forward Curved Fan (Until 11/04)......................................................................................................... 63
Fan Mounts- 33” Forward Curved Fan (11/04 & Later)..................................................................................................... 64
Fan Mounts- 36” Forward Curved Fan (Until 11/04)......................................................................................................... 65
Fan Mounts- 36” Forward Curved Fan (11/04 & Later)..................................................................................................... 66.
Fan Mounts- 40” Forward Curved Fan (Until 11/04)......................................................................................................... 67
Fan Mounts- 40” Forward Curved Fan (11/04 & Later)..................................................................................................... 68
Fan Mounts- 33” Airfoil Double Width Fan (Until 11/04) ................................................................................................... 69
Fan Mounts- 33” Airfoil Double Width Fan (11/04 & Later)............................................................................................... 70
Fan Mounts- 36” Airfoil Double Width Fan (Until 11/04) ................................................................................................... 71
Fan Mounts- 36” Airfoil Double Width Fan (11/04 & Later)............................................................................................... 72
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 2
Contents
Continued
Section F- Supply Air Section, Continued
Fan Mounts- 40” Airfoil Double Width Fan (Until 11/04) ................................................................................................... 73
Fan Mounts- 40” Airfoil Double Width Fan (11/04 & Later)............................................................................................... 74
Fan Mounts- 44” AFSW- RDT Units (Until 11/04)............................................................................................................. 75
Fan Mounts- 44” AFSW- Draw-Thru/No Heat Units (11/04 & Later)................................................................................. 76
Fan Mounts- 49” AFSW- RDT Units (Until 11/04)............................................................................................................. 77
Fan Mounts- 49” AFSW- RDT Units (11/04 & Later)......................................................................................................... 78
Supply Air Fan Motors ...................................................................................................................................................... 79
Belt Guard......................................................................................................................................................................... 80
Inverters & Inverter Bypass Control Box (Until 3/05)
Motor HP 5- 25............................................................................................................................................................. 81
Motor HP 30- 75........................................................................................................................................................... 82.
Inverters & Inverter Bypass Control Box (3/05 thru 10/06)
Motor HP 5............................................................................................................................................................. 83, 84
Motor HP 7.5- 25.................................................................................................................................................... 85, 86
Motor HP 30- 75..................................................................................................................................................... 87, 88
Inverters & Inverter Bypass Control Box (1/07 & Later)
Motor HP 5................................................................................................................................................................... 89
Motor HP 7.5- 25.................................................................................................................................................... 90, 91
Motor HP 30- 75..................................................................................................................................................... 92, 93
Inverters...................................................................................................................................................................... 94- 97
Line Reactors.................................................................................................................................................................... 98
Section Mounted Controls- PC7, HL22, LT10, S10, REC10, UV Lights........................................................................... 99
Section Mounted Controls- MAT, EFT, SAT, DAT, OAT, SD1........................................................................................ 100
Section Mounted Controls- SCB- TB25, TB27, TB28, PB10, PB9, PB20, PB19............................................................ 101
Section G- Blow-Thru Heat Section
Notes
.............................................................................................................................................................................. 102
Option 1: Blank Section
Unit Mounted Controls- LT1, S12, REC12................................................................................................................ 102
Diffuser....................................................................................................................................................................... 102
Option 2- Hot Water, Steam Coil Heat: Code 04= W, S
Mixing Valves & Actuator (VM1) ........................................................................................................................ 103, 104
Option 3- Electric Heat: Code 04= E
Heaters, Hi Limit Cutouts, Diffusers................................................................................................................... 105, 106
Electric Heat Control Box (Until 3/05)................................................................................................................. 107- 111
Electric Heat Control Box (3/05 & Later)............................................................................................................ 112- 116
Option 4- Gas Heat: Code 04= A
Heat Exchangers & Vestibules- 500, 640, 650, 790, 800, 1000, 1100, 1400 MBH Furnaces ................................... 117
Heat Exchangers- 1500, 2000 MBH Furnaces .......................................................................................................... 118
Modulating OR Single Stage Burner.................................................................................................................. 119- 122
Hi Turn Down Burner ......................................................................................................................................... 123- 126
Single Stage OR Modulating Burner Controls
MicroTech OR No Controls (Until 6/95) ................................................................................................................ 127
MicroTech OR No Controls (7/95 thru 1/01) ......................................................................................................... 128
MicroTech II OR No Controls (1/01 & Later) ................................................................................................ 129, 130
MicroTech III Controls........................................................................................................................................... 131
Hi Turn Down Burner Controls
MicroTech II OR No Controls........................................................................................................................ 132, 133
MicroTech III Controls........................................................................................................................................... 134
Gas Train- Inlet .................................................................................................................................................. 135- 138
Gas Train- Controls: GV1, GV2, GV4, GV5, GV6, GV7, GV8, GV9, VM1......................................................... 139- 143
Gas Train- Outlet ....................................................................................................................................................... 144
Gas Train- Damper Linkage............................................................................................................................... 145- 147
Cabinet Doors, Gasketing, Hardware, & Flue Box Mounting............................................................................. 148- 151
Section H- Blow-Thru Heat Blank Access Section
Notes
.............................................................................................................................................................................. 152
Section Mounted Controls- LT19, REC19, S19 .............................................................................................................. 152
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 3
Contents
Continued
Section I- Blow-Thru Cooling Section
Notes
.............................................................................................................................................................................. 153
Section Mounted Controls- LT16, S16, REC16............................................................................................................... 153
Section J- Final Filter Section
.............................................................................................................................................................................. 154
Notes
Section Mounted Controls- HL23, PC6, SPS6................................................................................................................ 154
Filters
.............................................................................................................................................................................. 155
Section K- Discharge Plenum Section- RPS, RFS
.............................................................................................................................................................................. 156
Notes
Section Mounted Controls- DAT, OAT, SD1................................................................................................................... 156
Damper Assembly- w/ Actuator ACT5 ............................................................................................................................ 157
Section L- Out-of-Airstream Blank Access Section
.............................................................................................................................................................................. 158
Notes
Section Mounted Controls- LT20, REC20, S20 .............................................................................................................. 158
Section M- Condenser Section
.............................................................................................................................................................................. 159
Notes
Section Mounted Controls- PC22, PC12......................................................................................................................... 159
Units with Original Fan Assembly (3 blade Prop) ................................................................................................... 160, 161
Units with Later Fan Assembly (4 blade Prop) ....................................................................................................... 162, 163
Quiet Fans............................................................................................................................................................... 164, 165
Compressors & Compressor Components
Semi Hermetic Compressors: Code 44= H, K.................................................................................................... 166- 169
Scroll Compressors
R22 Compressor: Code 44= Z (Until 7/08) ........................................................................................................... 170
R22 Compressor: Code 44= Z (7/08 & Later)....................................................................................................... 171
R407C Compressor: Code 44= T (Until 7/08)..................................................................................................... 1712.
R407C Compressor: Code 44= T (7/08 & Later) ....................................................................................................... 173
Compressor Mounting........................................................................................................................................... 174
Condenser Coil Guards .................................................................................................................................................. 174
Condenser Control Box
Power Panel (Until 3/05) .................................................................................................................................... 175- 181
Control Panel- MicroTech (Until 1/01) OR No Controls (Until 3/05)................................................................... 182, 183
Control Panel- MicroTech II OR No Controls (3/05 & Later) ............................................................................. 184- 191
Control Panel (RCS Units Only)- MicroTech III Controls (9/08 & Later)............................................................. 192- 194
Speedtrol Control Box and Transformer ......................................................................................................................... 195
Factory Supplied Line Voltage Box- T6, DS6, FU6A, FU6B, FU6C................................................................................ 196
Section N- Main Control Box
Notes
.............................................................................................................................................................................. 197
Control Panel- Units with MicroTech Controls Until 1/01........................................................................................ 198- 200
Control Panel- Units with MicroTech II Controls 1/01 thru 3/05.............................................................................. 201- 203
Control Panel- Units w/o MicroTech Controls Until 3/05......................................................................................... 204, 205
Control Panel- MicroTech II Units OR Units with No Controls 3/05 & Later .......................................................... 206- 212
Control Panel- MicroTech III Units with Controller 9/08 & Later ............................................................................. 213- 215
Power Panel Until 3/05
Diagram ..................................................................................................................................................................... 216
Common Components ....................................................................................................................................... 217, 218
Fan Motor Contactors, Overloads, Fusing Components & Line Reactors ......................................................... 219- 227
Power Panel 10/04 thru 10/06
Diagrams............................................................................................................................................................ 228- 230
Common Components ....................................................................................................................................... 231- 236
Supply MMP10 & M10 Fan Contactor and Return MMP20 & M20 Fan Contactor ............................................ 236- 242
Compressor Contactors
Unit Size 080: Scroll Compressors (Code 44= Z, T)............................................................................................. 243
Unit Size 090: Scroll Compressors (Code 44= Z, T)............................................................................................. 244
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 4
Contents
Continued
Section N- Main Control Box, Continued
Power Panel 10/04 thru 10/06, Continued
Compressor Contactors, Continued
Unit Size 105: Scroll Compressors (Code 44= Z, T)............................................................................................. 245
Unit Sizes 080- 105: Semihermetic Compressors (Code 44= H, K) ............................................................ 246, 247
Unit Size 115: Semihermetic Compressors (Code 44= H, K) .............................................................................. 248
Unit Size 125: Semihermetic Compressors (Code 44= H, K) AND AL Start (Code 10= AL)................................ 249
Unit Size 125: Semihermetic Compressors (Code 44= H, K) AND PW Start (Code 10= PW)...................... 250, 251
Unit Size 135: Semihermetic Compressors (Code 44= H, K) .............................................................................. 252
Condenser Fan Contactors & Motor Protectors................................................................................................. 253, 254
Power Panel 1/07 & Later
Diagram.............................................................................................................................................................. 255, 256
Common Components ....................................................................................................................................... 257- 262
Supply MMP10 & M10 Fan Contactor and Return MMP20 & M20 Fan Contactor............................................. 263- 267
Compressor Contactors & Motor Protectors....................................................................................................... 268- 274
Condenser Fan Contactors & Motor Protectors................................................................................................. 275- 277
Refrigeration Tubing
Notes
.............................................................................................................................................................................. 278
Units with Semi-Hermetic Discus Compressors: Code 44= H, K.....................................................................................279
Units with Scroll Compressors: Code 44= Z, T............................................................................................................... 280
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 5
Parts List Revision History
Rev. Date
Description
A- AF var.
Archived Revisions A- AF.
AG 01/15 Cover, Rev. pg.: Updated to Daikin Applied logo format.
Various: Changed “Daikin McQuay Parts” to “Daikin Applied”; changed “insure” to “ensure”; 1/07 to present” to “1/07 & Later”; & changed “193414601” to “193414602”. Changed “Code 12= *M” to “Code 12= 1M, 2M, 4M, 5M)”.
Page 5 (NEW): Added page for additional TOC.
Page 6: Deleted/archived this Revision page. Repaginated form & updated TOC.
Page 7: Reorganized/updated page contents.
Page 8: Added footnote #1.
Page 9: Updated tables as needed.
Page 10- 14: Updated/corrected Nomenclature coding.
Page 21, 42, 45, 46, 54, 102, 151, 152, 153, 155, 157, 158, 196, 289 (OLD) 21, 41, 44, 45, 51, 53, 101, 150, 151, 152, 154, 156, 157, 195, 276 (NEW): Rewrote Notes.
Page 22: Updated dwg. Rewrote footnotes and updated footnote notation. Deleted Iso. dmpr. info.
Page 23: Rewrote Page Header. Added footnote #1.
Page 24: Rewrote Page header. Rewrote footnotes and updated footnote notation.
Page 25, 26, 27: Rewrote footnotes and updated footnote notation.
Page 28: Updated dwgs.
Page 29: Updated table and rewrote footnotes & footnote notation.
Page 32: Added “Until 12/08” to page header, added footnote #1 and footnote notation, & changed Ref # 16 from ”055638101” to “055638102”. Page 33: Updated VFD tables. Added footnote #5 and footnote notation.
Page 34: Deleted OL/OL Htr. p/ns. Updated dwgs. Rewrote footnotes & updated footnote notation.
Page 36, 37: Updated dwgs. Changed “Code 15 & C15=” to “Code 21 & C21”.
Page 39: Updated mtr. table. Added footnote #1.
Page 40: Updated dwgs. Updated RAT & SD2 tables. Rewrote footnotes.
Page 41: Deleted pg. w/ Ebtron info. Ebtron is considered a special. Repaginated form & updated TOC.
Page 42 (OLD) 41 (NEW): Updated fixture dwg. Rewrote footnote.
Page 45 (OLD 44 (NEW): Updated section headers, updated fixture dwg. & corrected fixture table header.
Page 52: Moved vlv. p/ns to new pg. 63. Updated/added to dwgs.
Page 53: (NEW): Added pg. for additional vlv. components. Repaginated form & updated TOC.
Page 55, 56, 58, 61 (OLD) 55, 56, 58, 61 (NEW): Changed Brg. p/ns “020648604”, “020648605”, “020648608”, “020648609”, to “020648654”, “020648655”, “020648658”, “020648659” & added footnote explaining bearing change.
Page 57: Corrected Fan Wheel orientation: Bubs 3 & 4 to match description for CW & CCW wheels.
Page 61: Changed description of p/n 049541108 from “Bearing- Ball” to “Bearing- Roller”.
Page 79: Updated mtr. table and added footnote #1.
Page 81- 93: Updated pg. headers. Corrected misc. formatting issues.
Page 94: Deleted obsolete Inverter series ACH401 table.
Page 95: Rewrote footnote #1.
Page 97: Updated table with current p/ns and footnotes.
Page 99: Corrected fixture table header and updated fixture dwg.
Page 100: Updated tables as needed. Rewrote footnotes.
Page 102: Corrected Diffuser p/ns.
Page 103: Moved p/n table to new pg. 104. Updated/added to dwgs.
Page 104 (NEW): Added pg. for additional vlv. & Actuator p/ns. Repaginated form & updated TOC.
Page 116, 117 (OLD) 117, 118 (NEW): Rewrote page header & updated TOC. Updated/added p/ns, rewrote footnotes & updated footnote notation.
Page 119, 123 (OLD) 120, 124 (NEW): Updated Ref #4 Wheel description.
Page 127 (OLD) 128 (NEW): Changed Ref # 64, 65 Relay R21, 22 description from “(C12= A*)” to “Code 20= A*”.
Page 153 (OLD) 154 (NEW): Rewrote footnote #1.
Page 155 (OLD) 165 (NEW): Updated tables & dwgs. Rewrote footnote #1.
Page 156 (OLD) 157 (NEW): Rewrote page header & footnotes. Corrected dmpr. qtys.
Page 157 (OLD) 158 (NEW): Corrected Section Size coding. Updated fixture dwg.
Page 159, 160 (OLD) 160, 161 (NEW): Rewrote page headers. Rewrote footnotes and updated footnote notation. Updated p/ns.
Page 161, 162 (OLD) 162, 163 (NEW): Rewrote page headers. Rewrote footnotes and updated footnote notation. Updated/added to p/ns. Updated Fan Detail dwg.
Page 171, 172 (OLD) 172, 173 (NEW): P/Ns for Ref # 6 were reversed. 047356121 is for MTII & 047356122 is for NC.
Page 181, 182 (OLD) 182, 183 (NEW): Rewrote Page Header & updated TOC.
Page 185 (OLD) 186 (NEW): Rewrote footnote #1.
Page 195 (OLD) 196 (NEW): Changed page header “McQuay Supplied...” to “Factory Supplied...” Updated TOC.
Page 205- 226 (OLD) 216- 228 (NEW): Moved pgs. to reorganize section for clarity.
Page 232 (OLD) 211 (NEW): Rewrote footnote #1.
Page 207 (OLD) 218 (NEW): Rewrote footnotes.
Page 201- 226 (OLD) 219- 227 (NEW): Deleted OL & OL Heater information & Code 10 PP & PS option. Rewrote/added to footnotes. Deleted 9 pgs. Repaginated form & updated TOC.
Page 240- 242 (OLD) 231- 233 (NEW): Deleted unneeded CB & Contactor, etc. blank entries. Added rewrote Header footnote.
Page 243 (OLD) 234 (NEW): Deleted duplicate CB & Contactor, etc. blank entries. Rewrote Header footnote.
Page 237- 274 (OLD) 228- 266 (NEW): Numerous updates/corrections. Rewrote Page Header & Header footnote. Updated TOC.
Paged 275 (OLD) 265 (NEW): Deleted page and reorganized and condensed section.
Page 276- 267 (OLD) 264- 277 (NEW): Numerous updates/corrections. Rewrote Page Header & Header footnote. Updated TOC.
Page 288 (OLD): Deleted pg. with unused TEAO mtr. info. Option coded but never used.
Page 290 (OLD) 279 (NEW): Rewrote footnote #4.
Daikin Applied, 13600 Industrial Park Blvd., P.O. Box 1551, Minneapolis, MN 55440 (763) 553-5330
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 6
Nomenclature
Serial Number- Until 2/1999
3 7A12345 01
Engineering Revision
Serial Number
Factory
3= Faribault, MN
Year and Month of Manufacture:
YearMonth
6= 1996
A= Jan.
G= Jul.
B= Feb.
H= Aug.
7= 1997
8= 1998
C= Mar.
J= Sep.
9= 1999
D= Apr.
K= Oct.
E= May
L= Nov.
F= Jun.
M= Dec.
Serial Number- 2/1999 & Later
FBO
U
05
10
04800
Serial Number
(Build sequence)
Plant Identification Abbreviation
FBO= Faribault, MN
Month of Manufacture
01= Jan. 04= Apr. 07= July 10= Oct.
02= Feb. 05= May 08= Aug. 11= Nov.
03= Mar. 06= Jun. 09= Sept. 12= Dec.
U= Unit
Year of Manufacture
99= 1999, 00= 2000, 01= 2001,
02= 2002, 03= 2003, 04= 2004,
05= 2005, 06= 2006, 07= 2007
etc.
Unit Model Number
R
PS
135
C
S
R = RoofPak
Unit Configuration
PS = Heating, Mechanical Cooling; Single Zone Unit
FS = Heating, Future Mechanical Cooling; Single Zone Unit
CS = Condensing Section Only; Single Zone Unit
DT = Draw Through Heating, Mechanical Cooling
Nominal Capacity (tons)
080, 090, 105, 115, 125, 135
Design Vintage
Heat Medium
A = Natural Gas
E = Electric
S = Steam
W = Hot Water
Y = None (Cooling Only)
Cooling Coil Size
S = Standard (Low Airflow)
L = Large (High Airflow)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 7
L
Nomenclature
Continued
Unit Model Number- Complete 1
RPS080C S A Y 1
EU P
27 AL P1 LD
5 5 A 1 CH R120 BB FE 44B1 JEY 1250A Y AB S CYYS 4Z104D
Code
03040506 07 08 09 10 11 12 1314151617 18
19 20
21
22
23 2425 26 27
28
YYYYYY BBBBBB 30A1 QEY 1250A 110SSB YYYY YYYYYY YYYYYY
B B BB
Y
38 39 40
41 42 43 444546474849
29
30
31
32
33
34
35
36
37
6 AG Z 2 1 1 Y D YY1AAA
50-54
An "X" located in any position in a code string indicates a special feature. Contact Daikin Applied with model and serial number information in
order to correctly identify the required part(s).
1
Unit Section Layout Examples
G, H, I=
Blow-Thru Section
F=
Supply Fan
Section
B, C, D, E=
Draw-Thru Section
A=
Return Air/Outside Air/
Heat Recovery/Prop Exhaust
Section
J=
Final
Filter
M=
Condenser Section
L=
Out-of AirStream
Blank Access
K=
Discharge
Plenum
RPS
BC D F
A
G H JK L
A
M
B C D
Prop Exhaust Draw Thru
BCD F
A
GH
K
B C
A
M
Heat Recovery Draw Thru
A
G
H
J
K
M
Return Air Fan Draw Thru
J
RFS
B C D F
G
F
F G H I
J
K
Heat Recovery Blow-Thru
H
J
RCS
M
K
Return Air Fan Draw Thru
RDT
A
B C D E
F
M
A
B C D E
With Prop Exhaust
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” F
M
With Return Air Fan
Rev. AG 01/15
RPL 7000070 / Page 8
M
Nomenclature
Continued
General Options
Section J- Final Filter Section
Section A
Outdoor/Return Air Section
Section K- Discharge Plenum Section
Unit Model Codes that Pertain: 05, 06, 07, 51- 54
Unit Model Codes that Pertain:
14, 15, 19, 20, 21, 22, 23, 24, 49
Unit Model Codes that Pertain: 39
Unit Model Codes that Pertain: 40
Section L- Blank Section- Out of Airstream
Unit Model Codes that Pertain: 41
Sections B, C, D, E
Draw-Thru Cooling Sections
Section B- Filter
Unit Model Codes that Pertain: 25
Section C- Draw-Thru Blank Access
Unit Model Codes that Pertain: 14, 15, 26
Section D- Draw-Thru Cooling Section
Section M- Condenser Section
Unit Model Codes that Pertain: 42, 43, 44, 45, 47
Section N- Main Control Panel
Unit Model Codes that Pertain: 08, 09, 10, 11, 12, 13, 14, 15, 17, 18
Refrigeration Tubing Options
Unit Model Codes that Pertain: 45, 46
Unit Model Codes that Pertain: 03, 27, 28
Section E- Draw-Thru Heating/Blank Section
Unit Model Codes that Pertain: 04, 30
Section F- Supply Fan Options
Unit Model Codes that Pertain:
12, 14, 15, 31, 32, 33, 40
Sections G, H, I
Blow-Thru Options (N/A RDT)
Section G= Blow-Thru Heat/Blank
Unit Model Codes that Pertain: 04, 34
Section H= Blow-Thru Blank Access
Unit Model Codes that Pertain: 38
Section I- Blow-Thru Coil Sections
Unit Model Codes that Pertain: 03, 35, 36
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 9
Nomenclature
Continued
Code 12= Temperature Controls (continued)
MicroTech II
LD= LonMark w/ Discharge Air Temp. Ctl.
LS= LonMark w/ Space or Zone Ctl.
BD= BACNet w/MSTP w/ Discharge Air Temp. Ctl.
BS= BACNet w/MSTP w/ Space or Zone Ctl.
ED= BACNet w/Ethernet w/ Discharge Air Temp. Ctl.
ES= BACNet w/Ethernet w/ Space or Zone Ctl.
SD= Standalone w/ Discharge Air Temp. Ctl.
SS= Standalone w/ Space or Zone Ctl.
MicroTech III
LE= LonMark w/ Discharge Air Temp. Ctl.
LF= LonMark w/ Space or Zone Ctl.
BE= BACNet w/ MSTP w/ Discharge Air Temp. Ctl.
BF= BACNet w/ MSTP w/ Space or Zone Ctl.
EE= BACNet w/Ethernet w/ Discharge Air Temp. Ctl.
EF= BACNet w/Ethernet w/ Space or Zone Ctl.
SE= Standalone w/ Discharge Air Temp. Ctl.
SF= Standalone w/ Space or Zone Ctl.
No Controls
YM= No Temperature Controls
YC= No Temperature Controls w/6 to 9 volt DC modulating Gas Heat Actuator
Code 04= Heat Section- Type of Heat
Y= No Heat
A= Natural Gas Heat
E= Electric Heat
S= Steam Heat
W= Hot Water Heat
X= Propane Heat or Fuel Oil Furnace (specials)
Code 05= Split Unit
C= Split at condenser
F= Split at Fan/Heat
Y= None
Code 06= Insulation and Liners
1= 1”, 3/4# with liners on doors
2= 1½”, 1.5# with solid liners on doors & ceilings
3= 1½”, 1.5# with perforated liners in plenums, solid elsewhere
4= 1½”, 1.5# with solid liners on doors, ceilings and floors
5= 1½”, 1.5# with perforated liners in plenums, solid elsewhere
(including floors)
6= 1½”, 1.5# with St Stl Solid Liners on Doors, Ceilings and Floors
Code 07= Approval agency listing
CY= ETL-Canada
EY= USA
YY= None
Code 13= Air Flow Controls
Y= None
1= 1 duct sensor
2= 2 duct sensors
3= 1 duct and 1 space sensor
4= 1 space sensor
5= Duct Hi Limit (DHL) sensor for no controls unit- VAV unit only
Code 08= Main Control Box Location
P= Discharge Plenum MicroTech (2 panel)
D= Discharge Plenum MicroTech II OR III (1 panel)
S= Supply Fan (2 panel)
F= Supply Fan II OR III (1 panel)
Code 14= Inverters
Y= None
X= Special (Inverter)
Separate Section
1= SA Fan only w/bypass
2= SA & RA Fans w/bypass
4= RA only w/bypass
No Separate Section
3= SA Fan only w/bypass
5= SA & RA Fans w/bypass
6= SA Fan only no bypass
7= SA & RA Fans no bypass
8= RA Fan only w/bypass
9= RA Fan only no bypass
Code 09= Unit Voltage
12= 208/60/3
27= 460/60/3
28= 380/50/3
29= 230/60/3
37= 575/60/3
Code 10= Starting Option
AL= Across-the-Line (std.)
PW= Part Winding Start
PP= Part Winding Compressor & Fan
PS= Part Winding Fans
Code 11= Field Power Connection and Disconnect
P1= Single Power Block: Complete Unit
Q1= Two Power Blocks: EH/Balance of Unit
A2= One, thru-the-door Disconnect: Complete Unit
C2= Two, thru-the-door Disconnects: SAF&RAF&CB/Balance of Unit
B2= Two, thru-the-door Disconnects: EHB/Balance of Unit
D2= Three thru-the-door Disconnects: EH/SAF&RAF&CB/Balance of
Unit
Code 12= Temperature Controls
MicroTech
1M= MicroTech, CAV, Zone Control
2M= MicroTech, VAV, Discharge Air Cooling Control, Zone/Return
Air Heating Control (Constant Volume)
4M= MicroTech, VAV, Disch. Air Cool and Heating Control
5M= MicroTech, CAV, Disch. Air Cooling or Cool & Heat Control
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Code 15= Inlet Vane/Damper Actuators or Inverter Type
Y= None
1= Supply Fan Only
2= Supply and Return Fan
4= Return Fan Only
A= ABB Inverter
G= Graham Inverter
R= Reliance Inverter
S= Daikin Applied MD2, MD3, MD6
F= Field Installed Inverter controlled by MicroTech II or III
Code 16= Smoke Detectors
1= Return Air Smoke Detector
2= Supply Air Smoke Detector
3= 1 + 2
Y= None
Rev. AG 01/15
RPL 7000070 / Page 10
Nomenclature
Continued
Code 17= Misc. Aux. Controls
C G
Y= None
F= Freezestat (Steam or HW Heat only)
P= Phase Failure
G= Ground Fault Protection
L= Line Reactors (Inverter w/ separate section only)
A= Freezestat & Phase Failure (Steam or HW Heat only)
B= Freezestat & Ground Fault (Steam or HW Heat only)
C= Phase Failure & Ground Fault
D= Freezestat, Phase Failure & Ground Fault (Steam or HW Heat only)
E= Freezestat & Line Reactors (Steam or HW Heat & Inverter w/ separate section only)
H= Phase Failure & LIne Reactors (Inverter w/ separate section only)
J= Freezestat, P.F. & Line Reactors (ST or HW Heat & Inverter w/ separate section only)
K= Ground Fault, Phase Failure & Line Reactors (Inverter w/ separate section only)
1= UV Lights
2= UV Lights & Freezestat (Steam or HW Heat only)
3= UV Lights & Phase Failure
4= UV Lights & Line Reactors (Inverter w/ separate section only)
5= UV Lights, Freezestat & Phase Failure (Steam or HW Heat only)
6= UV Lights, Freezestat & Line Reactors (ST or HW Heat & Inv. w/ sep. section only)
7= UV Lights, Phase Failure & Line Reactors
(Inverter w/ separate section only)
8= UV Lights, Freezestat, Phase Failure & Line
C= Differential Enthalpy
Y= None (includes mechanical enthalpy)
Code 18= Misc. Controls/ Unit Length
YYYY= None
MicroTech
KYYY= Unit mounted Keypad
BYYY= Unit mounted Keypad and Modem
MicroTech II or MicroTech III
W___= Wireless Modem (___= Air Handler Length [in.])
M___= Phone Modem (___= Air Handler Length [in.])
R___= Remote Keypad (___= Air Handler Length [in.])
K___= Remote Keypad (___= Air Handler Length [in.])
U___= Unit Powered Receptacle (___= Air Handler Length [in.])
V___= K + U (___= Air Handler Length [in.])
Code 20= Outdoor Air Options
YY= None
AE= 100% Outside air damper w/hood & actuator
AY= 100% Outside air damper w/hood/no actuator
BE= 0- 30% Outdoor air section w/actuator
BY= 0- 30% Outdoor air section w/o actuator
DE= 0- 100% Econ. w/barometric exhaust damper w/act.
DY= 0- 100% Econ. w/barometric exhaust damper w/o act.
EE= 0- 100% Econ. w/power closure exhaust damper w/act.
EY= 0- 100% Econ. w/power closure exhaust damper w/o act.
HE= 0- 100% Econ. w/prop exhaust damper w/act.
HY= 0- 100% Econ. w/prop exhaust damper w/o act.
FE= same as DE + Design Flow
FY= same as DY + Design Flow
GE= same as EE + Design Flow
GY= same as EY + Design Flow
JE= same as HE + Design Flow
JY= same as HY + Design Flow
KE= same as DE + Ebtron Sensor
KY= same as DY + Ebtron Sensor
LE= same as EE + Ebtron Sensor
LY= same as EY + Ebtron Sensor
ME= same as HE + Ebtron Sensor
MY= same as HY + Ebtron Sensor
Code 21= Return Air Fan
YYYY= No Return Air Fan
44B()= 44” Airfoil w/o vanes
44W()= 44” Airfoil w/vanes
()= Isolator type:
1= Rubber-In-Shear 2= Spring
3= Spring w/ Seismic Restraints
Code 22= Return Air Fan Motor
YYY= No Return Fan
J K Y
Always Y
A= Open Drip-proof motor
E= High Eff. ODP motor
F= High Eff. VAV motor
G= Totally- Enclosed motor
H= High Eff. Totally-Enclosed
J= Premium Eff. ODP
K= Premium Eff. Totally- Encl.
J= 5.0 HP
P= 25.0 HP
Code 19= Return Air Plenum
K= 7.5 HP
Q= 30.0 HP
L= 10.0 HP
R= 40.0 HP
YY= None (No return air section)
M= 15.0 HP
S= 50.0 HP
BY= Bottom Return
N= 20.0 HP
T= 60.0HP
HY= Back Return
(prop exhaust option is always J [5.0 HP])
SY= Side (opp. drive) Return
BE= Bottom Return w/ Iso. Damper & Actuator
BB= Bottom Return w/ Burglar Bars
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 11
Nomenclature
Continued
Code 23= Return Air Fan Drive Selection
YYYY= No Return Air Fan
____A
Required
RPM
Service Factor/Pitch Type
A= Std. SF/Fixed Pitch
B= 150% SF/Fixed Pitch
C= Std. SF/Variable Pitch
D= 150% SF/Variable Pitch
Code 27= Draw-Thru Drain Pan/Cooling Coil Section
RPS/RFS/RDT
YYYY= None
CYYS= Cooling coil section w/stainless steel sloped Drain Pan
CYYY= Cooling coil section w/galvanized steel sloped Drain Pan
Code 28= Draw-Thru Cooling Coil
YYYYYY= No Cooling Coil
5Z 08 3
H
Code 24= Exhaust Fans
Y= None
2= 2 Prop Exhaust Fan w/ Hood
3= 3 Prop Exhaust Fans w/ Hood
Code 25= Draw-Thru Filter Section
AA= Angular/Throwaway
AB= Angular/30% Throwaway
AC= Angular/30%/Intersept
AY= Angular/No Media
DB= Angular w/LO CFM Blender/30% Throwaway
DC= Angular w/LO CFM Blender/30%/Intersept
DY= Angular w/LO CFM Blender/No Media
EB= Angular w/HI CFM Blender/30% Throwaway
EC= Angular w/HI CFM Blender/30%/Intersept
EY= Angular w/HI CFM Blender/No Media
FA= Flat/ Throwaway
FB= Flat/ 30%/Throwaway
FC=Flat/30%/Intersept
FD= Flat/65% Cartridge
FE= Flat/95% Cartridge
FG= Flat/95% Cartridge/Intersept
FY= Flat/Rack Only
GY= Flat/Rack only w/LO CFM Blender
HB= Flat w/HI CFM Blender/30%Throwaway
HC= Flat w/HI CFM Blender/30%/Intersept
HD= Flat w/HI CFM Blender/65% Cartridge
HE= Flat w/HI CFM Blender/95% Cartridge
HG= Flat w/HI CFM Blender/95% Cartridge/ Intersept
HY= Flat w/HI CFM Blender/Rack Only
LE= Large Staggered/95% Cartridge
LG= Large Staggered/95% Cartridge/Intersept
LY= Large Staggered/Rack Only
SD= Staggered 65% Cartridge
SE= Staggered 95% Cartridge
SG= Staggered 95% Cartridge/Intersept
SY= Staggered Rack Only
VD= Staggered w/HI CFM Blender/65% Cartridge
VE= Staggered w/HI CFM Blender/95% Cartridge
VG= Staggered w/HI CFM Blender/95% Cartridge/Intersept
VY= Staggered w/HI CFM Blender/Rack Only
BY= Blank 24” Section- less Filters and Rack
CY= Blank 48” Section- less Filters and Rack
Code 26= Blank Draw-Thru Section
Y= None
S= Blank 48” Section
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” H= Aluminum Fin
D= Lanced Aluminum
C= Copper Fin
3= 3 Row
4= 4 Row
5= 5 Row
6= 6 Row
08= 8 Fins-per-inch
10= 10 Fins-per-inch
12= 12 Fins-per-inch
4Z= Type 4EZ
5Z= Type 5EZ
Code 29= Draw-Thru Heating Coil
YYYYYY= No Heating Coil (always)
Code 30= Draw-Thru Heating Section (RDT only) OR Blank Spacer
Section
YYYYYY= No Heating Section
BBBBBB= Blank 48” Section
Hydronic Heat (RDT only)
W22 J 3
E
E= Electric Actuator
Y= Less Actuator
2= 2 Way Steam Valve
3= 3 Way HW Valve
Y= No Valve
E= 1¼” Valve Pkg. H= 2½” Valve Pkg.
F= 1½” Valve Pkg. J= 3.0” Valve Pkg.
G= 2.0” Valve Pkg. Y= No Valve Pkg.
S11= 5JA0601H (6FPI, 1 Row 5J Steam Coil)
S12= 5JA1201H (12FPI, 1 Row 5J Steam Coil)
S13= 5JA0602C (6FPI, 2 Row 5J Steam Coil)
S14= 5JA1202C (12FPI, 2 Row 5J Steam Coil)
W11= 5WH0901H (9FPI, 1 Row 5WH HW Coil)
W22= 5WS0902C (9FPI, 2 Row 5 WS HW Coil)
Electric Heat (RDT only)
E120 2 Y
Always ‘Y’
1= 1 Stage
4= 4 Stages
E020= 20 KW Heater
E040= 40 KW Heater
E060= 60 KW Heater
E080= 80 KW Heater
E100= 100 KW Heater
E120= 120 KW Heater
Rev. AG 01/15
2= 2 Stages
6= 6 Stages
E160= 160 KW Heater
E200= 200 KW Heater
E240= 240 KW Heater
E280= 280 KW Heater
E320= 320 KW Heater
RPL 7000070 / Page 12
Nomenclature
Continued
Code 31= Supply Air Fan
33A()= 33” Airfoil Double Width, w/o Vanes
33V()= 33” Airfoil Double Width, w/ Vanes
33F()= 33” Forward Curved, LP
33M()= 33”Forward Curved, MP
36A()= 36” Airfoil Double Width, w/o Vanes
36V()= 36” Airfoil Double Width, w/ Vanes
36F()= 36” Forward Curved, LP
36M()= 36”Forward Curved, MP
40A()= 40” Airfoil Double Width, w/o Vanes
40V()= 40” Airfoil Double Width, w/ Vanes
44B()= 44” Airfoil Single Width, w/o Vanes (RDT only)
44W()= 44” Airfoil Single Width, w/ Vanes (RDT only)
49B()= 49” Airfoil Single Width, w/o Vanes (RDT only)
49W()= 49” Airfoil Single Width, w/ Vanes (RDT only)
()= Fan Isolators: 1= RIS; 2= Spring; 3= Spring w/ Seismic Snubbers
Code 32= Supply Air Fan Motor
E A Y
A= Open Drip-proof Motor
E= High Eff. ODP Motor
F= High Eff. VAV
G= Totally- Enclosed Motor
H= High Eff. Totally-Enclosed
J= Premium Eff. ODP Motor
K= Premium Eff. Totally-Enclosed
M= 15.0 HP
N= 20.0 HP
P= 25.0 HP
Q= 30.0 HP T= 60.0 HP
R= 40.0 HP U= 75.0 HP
S= 50.0 HP Code 33= Supply Air Fan Drive Selection
____A
Required
RPM
E= Electric Actuator
Y= Less Actuator
2= 2 Way Steam Valve
3= 3 Way HW Valve
Y= No Valve
H= 2½” Valve Pkg.
J= 3.0” Valve Pkg.
Y= No Valve Pkg.
E= 1¼” Valve Pkg.
F= 1½” Valve Pkg.
G= 2.0” Valve Pkg.
S11= 5JA0601H (6FPI, 1 Row 5J Steam Coil)
S12= 5JA1201H (12FPI, 1 Row 5J Steam Coil)
S13= 5JA0602C (6FPI, 2 Row 5J Steam Coil)
S14= 5JA1202C (12FPI, 2 Row 5J Steam Coil)
W11= 5WH0901H (9FPI, 1 Row 5WH HW Coil)
W22= 5WS0902C (9FPI, 2 Row 5 WS HW Coil)
Electric Heat Breakdown:
E020 1 Y
Always ‘Y’
J= 5.0 HP
K= 7.5 HP
L= 10.0 HP
Code 34= Blow-Thru Heat Section (continued)
Hydronic Heat Breakdown:
W22 J 3
E
Service Factor/Pitch Type
A= Std. SF/Fixed Pitch
B= 150% SF/Fixed Pitch
C= Std. SF/Variable Pitch
D= 150% SF/Variable Pitch
Code 34= Blow-Thru Heat Section
YYYYYY= No section, cooling only
BBBBBB= Blank 48” section, no heat, cooling only
Gas Heat Breakdown:
079 S S
C
Always ‘Y’
1= 1 Stage
2= 2 Stages
A= Aluminized Steel Secondary Heat Exchanger
S= Stainless Steel Heat Exchanger
MBH (in 10’s)
ex. 065= 650 MBH [050, 064, 065, 079, 080, 100, 110, 140, 150, 200]
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” E200= 200 KW Heater
E240= 240 KW Heater
E280= 280 KW Heater
E320= 320 KW Heater
E020= 20 KW Heater
E040= 40 KW Heater
E060= 60 KW Heater
E080= 80 KW Heater
E100= 100 KW Heater
E120= 120 KW Heater
E160= 160 KW Heater
Code 35= Blow-Thru Drain Pan/Cooling Coil Section
RPS/RFS
YYYY= None
CYYS= Cooling Coil section w/stainless steel Drain Pan
CYYY= Cooling Coil section w/galvanized steel Drain Pan
DYYS= Stainless Steel Drain Pan only (48” blank section)
DYYY= Galvanized Steel Drain Pan only (48” blank section)
YYYY= None
Code 36= Blow-Thru Cooling Coil
YYYYYY= No Cooling Coil
5Z 08 3
H
A= Low CFM Baffle Position
B= Medium CFM Baffle Position
C= High CFM Baffle Position
D= Extra High CFM
Y= None
A= One Stage Heat/Maximum gas pressure= 0.5 psi
P= One Stage Heat/ with H.P. Regulator Range= 2- 3 psi
Q= One Stage Heat/ with H.P. Regulator Range= 5- 10 psi
E= Modulating Burner/Maximum gas pressure= 0.5 psi
R= Modulating Burner/with H.P. Regulator Range= 2- 3 psi
S= Modulating Burner/with H.P. Regulator Range= 5- 10 psi
H= Hi Turn Down Burner 20:1
T= Hi Turn Down Burner 20:1/with H.P. Regulator Range= 2- 3 psi
U= Hi Turn Down Burner 20:1/with H.P. Regulator Range= 5- 10
psi
4= 4 Stages
6= 6 Stages
H= Aluminum Fin
D= Lanced Aluminum
C= Copper Fin
3= 3 Row
4= 4 Row
5= 5 Row
6= 6 Row
08= 8 Fins-per-inch
10= 10 Fins-per-inch
12= 12 Fins-per-inch
4Z= Type 4EZ
5Z= Type 5EZ
Code 37= Not an RPS/RDT/RFS/RCS Code
YYYYYY= None
Code 38= Blow-Thru Blank Access Section
Y= None- no section
B= Blank Section after Heat Section- 48” section
Rev. AG 01/15
RPL 7000070 / Page 13
Nomenclature
Continued
Code 39= Final Filter Section
Y= None
A= Flat Filter section, 95% cartridge, 24/24”
B= Flat Filter section, 95% cartridge, 24/48”
C= Blank- 24/24” section
D= Blank- 24/48” section
E= Flat Filter section, 95% cartridge, 24/24” with Intersept
F= Flat Filter section, 95% cartridge, 24/48” with Intersept
Code 40= Discharge Plenum
BY= Bottom Discharge
GY= Bottom Discharge (SW Supply Fan Only)
BB= Bottom Discharge w/ Burglar Bars
GB= Bottom Discharge w/ Burglar Bars (SW Supply Fan Only)
BE= Bottom Discharge w/ Discharge Damper (VAV) w/act.
FY= Front Discharge (RFS only)
SY= LH Side Discharge (SW Supply Fan only)
HY= LH Side Discharge (SW Supply Fan only)
Code 41= Blank Section- Out of Airstream
Y= None- no selection required
1= 48/24” Blank Section only- out of airstream with Light
2= 48” Blank Section only- out of airstream with Light
Code 42= Compressor Capacity Control
4= 4 steps
6= 6 steps
8= 8 steps
Code 47= Low Ambient Operation
1= Fantrol Standard Fans
2= Speedtrol Standard Fans
3= Fantrol Quiet Fans
4= Speedtrol Quiet Fans
Code 48= Seismic Construction / Power Factor Capacitors
I= Seismic Construction
P= Power Factor Capacitor(s)
Code 49= Supply and Return Fan Options
Y= None
A= SA fan belt guard
B= SA fan section light
C= A + B
D= SA & RA fan belt guard
E= SA & RA section light
F= D + E
Code 50= Misc.
Code 51= Packaging
Code 52= Parts Warranty
Code 53= Compressor Warranty
Code 54= Heat Exchanger Warranty
Code 43= Condenser Options
AY= Aluminum Fin Air Coil
AG= Aluminum Fin Air Coil w/ Coil Guards
AS= Aluminum Fin Air Coil w/ Seal Tite Conduits
AB= Alum. Fin Coil w/ Coil Guards & Seal Tite Conduits
CY= Copper Fin Air Coil
Code 44= Compressor Type
H= Semi Hermetic R22
K= Semi Hermetic R407C
Z= Scroll R22 (080- 105 only)
T= Scroll R407C (080- 105 only)
Code 45= Compressor Isolation
1= Resilient Rubber-In-Shear (RIS)
2= Spring isolation
3= Seismic
Code 46= Piping Option
1= Hot Gas Bypass, circuit #1 only
2= Hot Gas Bypass, circuits 1 & 2
3= Replaceable Filter Drier Core
4= 1 + 3
5= 2 + 3
Y= None RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 14
Nomenclature
Continued
Control Locations 1
PC7 (located in Supply Air Section) is not
shown.
RPS, RFS, RCS - MicroTech controls & optional
Inlet Vanes
RPS, RFS, RCS - MicroTech II OR III controls
RDT - MicroTech controls & optional Inlet Vanes
RDT - MicroTech II OR III controls
Supply Air Section
Prop Exhaust
(not shown)
Condenser
Section
Inverters, Line Reactors & Manual Bypass
Electric
Heat Contol
Panel
N
Main Control
Panel
1
Fuse
Box
Condenser
Control
CondenserPanel
Control
Panel
Units shown for reference only. Controls and control locations may vary depending on unit configuration, age, and options selected.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 15
Electrical Legend
Schematic Sym.
ACT1
ACT2
ACT3, 4
ACT5
ACT6
ACT7
ACT8
ACT 10, 11
ADI
AFD10
AFD20
AS
BM
C1- 5
C2, 6
C3, 7
C4, 8
C9, 10
C11
C19, 20
C21
CB10
CB20
CCB1, 2
COMPR.1- 4
CPC
CPR
CS1, 2
DAT
DB1
DFLH
DFRH
DHL
DS1
DS2
DS3
DS4
DS6
EFT
EHB1
EXPA, B, D
F1, 1A
F1C
F2
F3
F4
F11
F12
FB1- 4
FB8
FB9, 10
FB11- 18
FB19, 20
FB31- 40
Description
Actuator Motor, Supply Fan Vanes
Actuator Motor, Return Fan Vanes
Actuator Motors, Economizer Dampers
Actuator Motor, Discharge Isolation Damper
Actuator Motor, Return Air Isolation Damper
Actuator Motor, Heat Face/Bypass
Actuator Motor, Cool Face/Bypass
Actuator Motors, Exhaust Dampers
ADI Board
Adjustable Frequency Drive (Inverter), Supply Fan
Adjustable Frequency Drive (Inverter), Return Fan
Blower Air Switch
Burner Blower Motor
Power Factor Capacitors, Compressor #1
Power Factor Capacitors, Compressor #2
Power Factor Capacitors, Compressor #3
Power Factor Capacitors, Compressor #4
Power Factor Capacitors, Supply Fan
Capacitor, Speedtrol (Circuit #1)
Power Factor Capacitors, Return Fan
Capacitor, Speedtrol (Circuit #2)
Circuit Breaker, Supply Fan
Circuit Breaker, Return Fan
Compressor Control Boards
Compressors
Circuit Board, Main, MicroTech Controller
Circuit Board, expansion, Main Controller
Control Switches, Refrigerant Circuits
Discharge Air Temperature Sensor
Daughter Board
Design Flow Sensor, Left Hand
Design Flow Sensor, Right Hand
Duct High Limit
Disconnect, Total Unit or Condenser/Heat
Disconnect, SAF/RAF/Controls
Disconnect, Electric Heat
Disconnect, Condenser
Disconnect, Unit Supplied 120V Power
Entering Air Temperature Sensor
Staged Electric Heat Board
Expansion Boards
Fuses, Control Circuit, T1 Primary
Fuse, Control Circuit, T1 Secondary
Fuse, Control Circuit
Fuse, Burner Motor
Fuse, T4 Transformer
Fuse, Speedtrol Motor
Fuse, 208V Speedtrol Motor
Fuseblocks, Compressors
Fuseblock, Main Transformer
Fuseblocks, Supply Fan
Fuseblocks, Condenser Fans
Fuseblocks, Return Fan
Fuseblocks, Electric Heat (Top Bank)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Location
Supply Air Section
Return Air Section
Economizer Section
Discharge Section
Return Air Section
Coil Section, Heat
Coil Section, Cool
Return Air Section
Main Control Box
AFD or Supply Fan Sect.
AFD or Supply Fan Sect.
Furnace Section
Furnace Section
Condenser Section
Condenser Section
Condenser Section
Condenser Section
Supply Air Section
Cond. Bulkhead
Return Air Fan
Cond. Bulkhead
Main Control Box
Main Control Box
Main or Cond. Ctl. Box
Condenser Section
Main Control Box
Main Control Box
Condenser Control Box
Discharge section
Main Control Box
Return Section
Return Section
Main Control Box
Main Control Box
Main Control Box
Electric Heat Section
Cond. Control Box
Bulkhead
Supply Fan Section
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Condenser Control Box
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Condenser/Fuse Ctrl Box
Main Control Box
Main Control Box
Cond. Control Box
Main Control Box
Electric Heat Section
RPL 7000070 / Page 16
Electrical Legend
Continued
Schematic Sym.
FB41- 50
FD
FLC
FS1
FSG
GCB1
GFS1/GFR1
GFS2/GFR2
GFS4/GFR4
GRD
GV1
GV2, 3
GV4- 8
HL 1- 10
HL 11- 20
HL22
HL23
HL31- 40
HL41- 50
HP1- 4
HP5
HS1
HTR1- 4
IT
LP1, 2
LP5
LT2
LT3
LT4
LT10
LT11
LT12
LT13
LT14
LT15
LT16
LT17
LT18
LT19
LT20
LT22
M1- 8
M9, 10
M11- 18
M19, 20
M21- 28
M29
M30 M31- 39
M40
M41- 50
M51, 52, 53
Description
Fuseblocks, Electric Heat (Bottom Bank)
Flame Detector
Fan Limit Control
Freezestat
Flame Safeguard
Generic Condenser Board
Ground Fault Sensor/Relay, RPS Unit
Ground Fault Sensor/Relay, RCS Unit
Ground Fault Sensor/Relay, RCS Unit
Ground
Gas Valve, Pilot
Gas Valves, Main
Gas Valves, Hi-Turn Down
High Limits, Elec. Heaters, Power (Top Bank)
High Limits, Elec. Heaters, Power (Bottom Bank)
High Limit, Gas Heat (Prefilters)
High Limit, Gas Heat (Final Filter)
High Limits, Elec. Heaters, Control (Top Bank)
High Limits, Elec. Heaters, Control (Bottom Bank)
High Pressure Controls, Refrigerant
High Pressure Control, Gas
Heat Switch, Electric, Shutdown
Crankcase Heaters
Ignition Transformer
Low Pressure Controls, Refrigerant
Low Pressure Control, Gas
Light, Furnace On
Light, Pilot Gas Valve On
Light, Main Gas Valve On
Light, Supply Fan
Light, Return Fan
Light, Heat Section
Light, Filter Section
Light, Final Filter Section
Light, Discharge Section
Light, Blow-through Coil Section
Light, Evaporator Coil Section
Light, Preheat Section
Light, Blank Section
Light, Blank Section
Light, Condenser Section
Contactors, Compressors
Contactors, Supply Fan
Contactors, Condenser Fans, Circuit #1
Contactors, Return Fan
Contactors, Condenser Fans, Circuit #2
Contactor, Burner Motor
Contactor, Supply Fan Inverter
Contactors, Elec. Heaters (Top Bank)
Contactor, Return Fan Inverter
Contactors, Elec. Heaters (Bottom Bank)
Contactors, Prop Exhaust Fan Motor
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Location
Electric Heat Section
Furnace Section
Furnace Section
Coil Section, Heat/Cool
Furnace Section
Main Control Box
Main Control Box
Cond. Control Box
Cond. Control Box
All Control Boxes
Furnace Section
Furnace Section
Furnace Section
Electric Heat Section
Electric Heat Section
Supply Air Section
Final Filter Section
Electric Heat Section
Electric Heat Section
On Compressors
Furnace Section
Main Control Box
On Compressors
Furnace Section
On Compr.
Furnace Section
Furnace Section
Furnace Section
Furnace Section
Supply Air Section
Return Air Section
Heat Section
Filter Section
Final Filter Section
Discharge Section
Blow-Thru Coil Section
Evaporator Coil Section
Preheat Section
Blank Section
Blank Section
Condenser Section
Main/Cond. Control Box
Main Control Box
Cond. Control Box
Main Control Box
Cond. Control Box
Furnace Section
Inverter Bypass Box
Electric Heat Section
Inverter Bypass Box
Electric Heat Section
Return Air Section
RPL 7000070 / Page 17
Electrical Legend
Continued
Schematic Sym.
MAT
MCB
MCB1
MJ
MMP1- 6
MMP10
MMP11, 12
MMP20
MMP21, 22
MMP51, 52, 53
MP1- 4
NB1, 2
NB3
OAE
OAT
OBA
OBB
OBC
OL9, 10
OL 19, 20
OL 51, 52, 53
OP1- 4
PB1
PB2
PB3
PB4
PB9, 10
PB19, 20
PB31
PB41
PC5
PC6
PC7
PC8
PC12, 22
PM1
PS1, 2
PS3
PVM1
PVM2, 4
R1, 2
R3, 4
R5- 8
R9, 10
R11, 12
R12, 13, 14
R19, 20
R20
R21, 22
R23
R24
R25
Description
Mixed Air Temperature Sensor
Microprocessor Control Board
Microprocessor Control Board #1
Mechanical Jumpers
Manual Motor Protectors, Compressors
Manual Motor Protector, Supply Fan
Manual Motor Protectors, Condenser Fans Ckt. 1
Manual Motor Protector, Return fan
Manual Motor Protectors, Condenser Fans Ckt. 2
Manual Motor Protectors, Prop Exhaust Fan Motors
Motor Protectors, Compressors
Neutral Blocks
Neutral Block
Outside Air Enthalpy Control
Outside Air Temperature Sensor
Output Board A, Standard
Output Board B, Cooling
Output Board C, Heating
Overload Relays, Supply Fan
Overload Relays, Return Fan
Overload Relays, Prop Exhaust Fan
Oil Pressure Controls, Compressors
Powerblock, Total Unit or Cond./Heat
Powerblock, SAF/RAF/Controls
Powerblock, Electric Heat
Powerblock, Condenser
Powerblocks, Supply Fan
Powerblocks, Return Fan
Power Block, DS3 Power Distribution
Powerblock, Power Distribution
Pressure Control, Clogged Filter
Pressure Control, Clogged Final Filter
Pressure Control, Proof of Airflow
Pressure Control, Minimum Airflow
Pressure Controls, FanTrol
Phone Modem
Pumpdown Switches, Refrigerant Circuits
Pumpdown Switch, Unit
Phase Voltage Monitor, RPS Unit
Phase Voltage Monitors, RCS Unit
Relays, High Pressure Reset
Relays, Hi Pressure delay
Relays, Compressor, Safety/Cool Fail
Relays, Compressor Lockout
Relays, Low Ambient
Relays, Condenser Fan
Relays, Cool Failure Indicator
Relay, Gas, Steam, Hot Water Heat
Relays, Gas Heat
Relay, Gas Heat, Modulating Valve or Electric Heat
Relay, Gas Heat Alarm
Relay, Gas Heat Start, Supply Fan Inverter
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Location
Supply Air Section
Main Control Box
Main Control Box
Terminal Blocks
Main/Cond. Control Box
Main Control Box
Main/Cond. Control Box
Main Control Box
Main/Cond. Control Box
Return Air Section
On Compressors
Main Control Box
Cond. Control Box
Economizer Section
Discharge Bulkhead
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Return Air Section
Condenser Section
Main Control Box
Main Control Box
Electric Heat Section
Cond. Control Box
Unit Split Junction Box
Unit Split Junction Box
Electric Heat Control Box
RCS Control Box
Filter Section
Final Filter Section
Supply Air Filter
Evaporator Coil Section
Cond. Bulkhead
Main Control Box
Cond. Control Box
Main Control Box
Main Control Box
Cond./Fuse Ctrl Box
Main/Cond. Control Box
Main/Cond. Control Box
Main/Cond. Control Box
Main/Cond. Control Box
Main/Cond. Control Box
<Main Control Box
Main Control Box
Main Control Box
Furnace Section
Furnace Sect./Elec. Ht. CB
Main Control Box
Main Control Box
RPL 7000070 / Page 18
Electrical Legend
Continued
Schematic Sym.
R26
R27
R28
R29
R30
R45
R46, 47
R48, 49
R62, 64
R63
R66
R67
R68
R69
R81- 88
RAE
RAT
REC1
REC2
REC3
REC10- 23
S1
S2
S3
S4
S6
S7
S10- 22
S40- 45
SAT
SB1
SB2
SC11
SC21
SD1
SD2
SPS1, 2
SPS5
SPS6
SR1- 3
SV1- 4
SV5- 8
T1
T2
T3
T4
T5
T6
T7
T8
T9
T10
Description
Relay, Occupied/Unoccupied
Relay, Exhaust Dampers
Relay, Isolation Dampers
Relay, Remote Fire Alarm
Relay, Cool Valve w/ F&B
Relay, UV Lights
Relays, Supply Fan Inverter increase/decrease
Relays, Return Fan Inverter increase/decrease
Relays, Special
Relay, Duct Hi Limit
Relay, RA Smoke Detector
Relay, Supply Fan Enable
Relay, Return Fan Enable
Relay, Inverter Bypass VAV Box Interlock
Relays, Smoke
Return Air Enthalpy Sensor
Return Air Temperature Sensor
Receptacle, Main Box
Receptacle, Condenser Box
Receptacle, Field Power, 115V
Receptacles, Cabinet Section
Switch, System On/Off, RPS Unit
Switch, System On/Off, RCS Unit
Switch, Furnace On/Off
Switch, Inverter Bypass On/Off
Switch, Return Fan Vanes Adjustment
Switch, Local On/Off/Auto to Controller
Switches, Cabinet Section Lights
Switches, Door Interlock, UV Lights
Supply Air Temperature Sensor
Staging Board #1, Cooling
Staging Board #2, Heating
Speed Control, Circuit #1
Speed Control, Circuit #2
Smoke Detector, Supply Air
Smoke Detector, Return Air
Static Pressure Sensors, Duct or Building
Static Pressure Sensor, Clogged Filter
Static Pressure Sensor, Clogged Final Filter
Sequence Relays, Electric Heat
Solenoid Valves, Liquid
Solenoid Valves, Hot Gas
Transformer, Main Control
Transformer, Unit 24V
Transformer, Controller, 18V
Transformer, Exhaust Dampers
Transformer, Electric Heat
Transformer, Unit Supplied 120V Voltage
Transformer, Gas Pilot Valve
Transformer, Gas Main Valve
Transformer, 24V Refrigerant Circuit
Transformer, SpeedTrol, 24V
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Location
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Return Air Section
Return Air Section
Main Control Box
Cond. Control Box
Discharge Bulkhead
Cabinet Sections
Main Control Box
Cond. Control Box
Furnace Section
Main Control Box
Main Control Box
Main Control Box
Cabinet Sections
Cabinet Sections
Discharge Section
Main Control Box
Main Control Box
Cond. Bulkhead
Cond. Bulkhead
Discharge Section
Return Air Section
Main Control Box
“” Filter Section
Final Filter Section
Electric Heat Section
Discharge Bulkhead
Discharge Bulkhead
Main Control Box
Main Control Box
Main Control Box
Main Control Box
Electric Heat Section
Bulkhead
Furnace Section
Furnace Section
Main Control Box
Cond. Control Box
RPL 7000070 / Page 19
Electrical Legend
Continued
Schematic Sym.
T11
TB1
TB2
TB3, 4
TB5
TB6
TB7, 8
TB10
TB11
TB12, 13
TB25
TB27, 28
TC1, 2
TC12
TD1, 2
TD3, 4
TD5- 8
TD9
TD10
TD11, 12
TD19
TD20
TR1, 2
U1, 2
VM1
VM5
VV1
ZNT1
ZNT2- 5
Description
Transformer, Speedtrol, 230V
Terminal Block, 115V, Field
Terminal Block, 24V, Field
Terminal Blocks, Condenser
Terminal Block, 115V, Factory
Terminal Block, 115V/24V, Factory
Terminal Blocks, 24V, Factory
Terminal Block, Heating
Terminal Block, Heating
Terminal Blocks, Electric Heat, Power
Terminal 115V Factory
Terminals 24V Factory
Temperature Controls, FanTrol
Temperature Control, Fantrol
Time Delays, Compressor Lockout
Time Delays, High Pressure
Time Delays, Compressor Part Winding
Time Delay, Supply Fan Part Winding
Time Delay, Hi-Turn Down Burner
Time Delays, Low Ambient
Time Delays, Return Fan Part Winding
Time Delay, Return Air Fan
Transducers, Pressure
Unloaders, Compressors
Valve Motor, Heating
Valve Motor, Cooling
Vent Valve
Zone Temperature Sensor, Control
Zone Temperature Sensors, Special
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Location
Cond. Control Section
Main/Cond. Control Box
Main/Cond. Control Box
Cond. Control Box
Main/Cond. Control Box
Main Control Box
Main Control Box
Main Control Box
Electric Heat Section
Electric Heat Section
Unit Split Junction Box
Unit Split Junction Box
Cond. Control Box
Cond. Control Box
Main/Cond. Control Box
Main/Cond. Control Box
Cond. Control Box
Main Control Box
Furnace Section
Cond. Control Box
Main Control Box
Main Control Box
Main Control Box
On Compressors
Heating Section
Coil Section, Cool
Furnace Section
Field Installed
Field Installed
RPL 7000070 / Page 20
Section A- Outdoor/Return Air Section
Notes
➩
Primary Codes that pertain: 19, 20, 21, 22, 23
Additional Codes that pertain: 06, 09, 12, 14, 15, 16, 17, 49
Codes 19 and 20 determine the base section. Code 19 is the Return Air Plenum, and determines if the unit has
back/horizontal return air, bottom return air, or side return air. A Return Air Plenum is required for any outdoor air
application with an Economizer (Code 20= BE, BY, DE, DY, EE, EY, FE, FY, GE, GY, HE, HY, JE, JY). The only case
in which a Plenum is not required is when a 100% Outdoor Air Damper and Hood are ordered (Code 20= AE, AY).
Codes 21, 22, 23 determine the Return Air Fan, Motor and drives. These codes only pertain to units with a 0- 100%
Economizer (Code 20= DE, DY, EE, EY, FE, FY, GE, GY, HE, HY, JE, JY). Return Fan section parts, Fans, and
Fan Motors are listed in this section. Drive components (Fan Sheave, Motor Sheave, V-belt(s), and Sheave
Bushing(s) [if required]) are NOT listed as they are unique to the unit. If a drive component is required you
may use the number from the part and cross reference it with the Drive Components Cross Reference, form
number 571006, or contact Daikin Applied with model and serial number information for identification. Note
that units built 1/99 & Earlier will require a new drive selection. If this is the case, ALL drive components
need to be replaced at the same time to ensure correct drive operation. Return Fan Motors range from 5- 60
horsepower and the Fan Wheel is a 44” Airfoil.
Code 06 determines the panels used in final cabinet assembly (return air units only). For sheet metal components
that make up the Outdoor/Return Air Section, contact Daikin Applied to ensure that correct liners, insulation
and hardware are ordered.
Code 09, the voltage, is part of the Motor part number identification.
Code 12, the control system, comes into play when an Economizer is present. The Economizer comes with an
Actuator Motor on any MicroTech unit (Code 12 1M, 2M, 4M, 5M [MicroTech] OR *D, *S, *E, *F [MicroTech II or
MicroTech III]), but MAY OR MAY NOT come with a factory supplied Actuator if the unit has controls by others
(Code 12= YM, YC).
Code 14 determines if the Return Fan has an Inverter, or Variable/Adjustable Frequency Drive. If Code 14 equals
1- 9 (or X for units built 2001 & Earlier), then the unit has Inverters, and cannot, therefore have Fan Wheels with
Variable Inlet Vanes. Note that Variable Inlet Vanes were not offered after mid 2003.
Code 15, determines if Variable Inlet Vanes (VIV) are present OR determines what type of Inverter was ordered,
OR if the Inverter was field supplied and controlled by the Microtech Controller.
Code 16 determines the Smoke Detector which is located in the Return Air Cabinet. Code 16= 1, 3 if a Smoke
Detector (SD2) is present.
Code 17 determines the Enthalpy Control. If Code 17= Y* and the unit has an Economizer there is mechanical
enthalpy control (OAE). If Code 17= C*, there is differential enthalpy control (OAE + RAE).
Code 49 determines if the Return Air Cabinet has a Light, Switch and Receptacle (Code 49= B), Fan Belt Guards
(Code 49= D), or both (Code 49= F).
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 21
Section A1- Outdoor/Return Air Section
100% Outside Air Damper with Hood
Code 20= AE, AY AND Code 19= YY
No Return Air Plenum
9
11
Air w
Flo
4
12
Se
cti
on
B
9
10
15
14
13
15
Ref. Part No.
Description
4
Damper Assembly
Damper Only
9 Liner
10
Panel- Hood Side
11
Panel- Hood Side
12
Panel- Hood Top
13 Louver
14
Channel- Support
15
Channel- Support
Actuator
Qty.
C20= AE
C20= AY
1
2
1
098313801
039813801
1
056132701056132701 2
056132203 056132203 1
056132204 056132204 1
056131802 056131802 1
056132002056132002 5
056132403 056132403 2
056132102 056132102 2
This Damper Assy. includes the Damper, Damper Linkage, and Actuator. For Damper Assy. components see the following
page. For COMPLETE Damper Assembly p/ns contact Daikin Applied with model and serial number information so that
the correct assembly can be identified.
2
This Damper Assy. includes the Damper and Damper Linkage, but NO Actuator. For Damper Assy. components see the
following page. For COMPLETE Damper Assembly p/ns contact Daikin Applied with model and serial number information
so that the correct assembly can be identified.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 22
Section A- Outdoor/Return Air Section
100% Outside Air Damper Detail w/ ACT3
Code 20= AE, AY AND Code 19= YY AND MicroTech, MicroTech II, No Controls 1
14
22
Motorized Linkage
Detail:
Code 20= AE
27
25
22
13
20
17
4
23
21
21
4
6
Manual Linkage Detail:
Code 20= AY
17
29
10
23
20
40
5
26
16
21
Damper Assy Detail 28
7
40
24
Ref.PartActuator
Qty.
No. Description
C20= AE
C20= AY
4
Shaft- Linkage
055979701 Not Used
2
5
Shaft Assy
Not Used 056081001
1
6
Adapter Plate- CrankArm
055542001 Not Used
1
7
Shaft- Linkage
Not Used 055536609
2
10 Channel- Support
Not Used 056080601
1
13 Blade- Damper 044195103044195103 13
14 Grille 055982601055982601 2
16 Stop/Anti- Rotate- Damper
065779801 065779801
2
17 Support- Damper Motor 055982001 Not Used
1
Support- Damper
Not Used 056080701
1
20 Crank Arm- Damper
032279200 Not Used
1
Crank Arm- Adjustable
Not Used 025072600
1
21 Ball Joint- Damper
000887000 000887000
4
22 Actuator- Motorized ACT3
059999804 Not Used
1
23 Bushing- Linkage Bar, Nylon
046098300 046098300 12
24 Bushing- Damper Blade, Nylon
043730400 043730400 24
25 Gasket- Vinyl 044193116044193116 12
26 Gasket- Vinyl 045655716045655716 1
27 Plug- Damper End
041003501 041003501 12
28 Plug- Damper End
041003502 041003502
6
29 Plug- Damper End
041003503 041003503
6
40 Bearing- Sleeve
Not Used 047138504
2
1
For units with MicroTech III controls (Code 12= *E, *F), contact Daikin Applied with model and serial number information so that the the
correct part(s) can be identified.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 23
Section A- Outdoor/Return Air Section
0- 30% Outside Air Section w/ ACT3
Code 20= BE, BY AND Code 19= BE, BY, HY
14
11
30
13
9
10
8
15
33
31
13
Linkage
Detail:
Without
Actuator
Code 20= BY
34
32
Linkage
Detail:
With
Actuator
Code 20= BE
Damper Detail
26
12
35
13
15
34
36
View A-A
35
Ref.PartActuator
Qty.
No. Description
C20= BE C20= BY,HY
Damper Assembly- Complete 055608703 1055608702 21
Damper Assembly 098314001 3098314001 31
8
9
10
11
12
13
14
15
26
30
31
32
33
34
35
36
Blade- Damper
Gasket- Vinyl
Gasket- Vinyl
Seal- End
Grille
Support- Motor
Rod- Support Angle
Bar- Linkage
Shaft- Linkage
Louver
Plug- End
Plug- End
Bushing- Damper Blade
Bushing- Linkage Bar, Nylon
Ball Joint- Damper
Actuator- Motorized, 120V ACT3
Crank Arm- Damper
044193212044193212
055940203055940203
044193124044193124
055942501055942501
055942601055942601
055595701 Not Used
Not Used 055608601
055942701055942701
055536608055536608
055593202055593202
041003505041003505
041003506041003506
043730400 043730400
046098300 046098300
000887000 Not Used
059999804 Not Used
032279200 Not Used
5
1
5
2
1
1
1
2
1
6
5
5
10
10
2
1
1
This Damper Assembly includes the Damper, Damper Linkage, and Actuator.
This Damper Assembly includes the Damper and Damper Linkage, but NO Actuator.
3
Damper only, no Actuator Linkage or Actuator.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 24
Section A- Outdoor/Return Air Section
0- 100% Economizer Section with Barometric Exhaust Damper
Units w/o Return Air Fans
Code 20= DE, DY, EE, EY, FE, FY, GE, GY AND Code 21= YYYY
12
Back Return (Code 19= HY)
shown.
11
Air
Flo
w
RefPart
Part Qty.
No. Description
Number
11 Economizer Damper
1
w/Act.(Code 20= DE, EE, FE, GE)
1
1
w/o Act. (Code 20= DY, EY, FY, GY)
1
12 Exhaust Damper Assy
Until 1/05
2
Powered (Code 20= EE, EY, GE, GY)
1
2
Barometric (Code 20= DE, DY, FE, FY)
1
Exhaust Damper Assy 1/05 & Later
Powered (Code 20= EE, EY, GE, GY) 112040401 1
Barometric (Code 20= DE, DY, FE, FY) 112039601 1
Economizer parts detail two pages after next. For COMPLETE Damper assemblies contact Daikin Applied with
model and serial number information so that the correct assembly can be identified.
2
Powered Exhaust Damper (Until 2/05) detail follows the Economizer Damper detail. For COMPLETE Damper
assemblies contact Daikin Applied with model and serial number information so that the correct Assembly can be
identified.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 25
Section A- Outdoor/Return Air Section
0- 100% Economizer Section with Barometric Exhaust Damper
Units with 44” Return Air Fans
Code 20= DE, DY, EE, EY, FE, FY, GE, GY AND Code 21= 44B*, 44W*
16
12
(see Return
Fan Detail)
16
126
57
125
124
124
54
Bottom Return
(Code 19= BY, BE,
BD, BE) shown
56
55
57
54
16
(see Return Fan Detail)
11
16
Part
Number
Qty.
RefPart
No. Description
11 Economizer Damper w/Actuator
Code 20= DE, EE, FE, GE
w/o Actuator
Code 20= DY, EY, FY, GY
12 Exhaust Damper Assy 2
Until 1/05
Powered Code 20= EE, EY, GE, GY
Barometric Code 20= DE, DY, FE, FY
Exhaust Damper Assy 1/05 & Later
Powered Code 20= EE, EY, GE, GY
Barometric Code 20= DE, DY, FE, FY
112040401 1
112039601 1
16
54
55
56
57
124
125
126
055582601
055921404
055921415
055921406
055921407
055957610
055957611
055957612
Gasket
.125 x 2.00
Gasket
Gasket
Gasket
Gasket
Fan Guard
Fan Guard
Fan Guard
1
1
1
1
055929902 1
055929901 1
20
2
2
2
2
3
1
1
Economizer parts detail on page after next. For COMPLETE Damper assemblies contact Daikin Applied with
model and serial number information so that the correct assembly can be identified.
2
Powered Exhaust Damper (Until 1/05) detail follows the Economizer Damper detail.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 26
Section A- Outdoor/Return Air Section
0- 100% Economizer Section with Prop Exhaust Fan & Damper
Code 20= HE, HY, JE, JY AND Code 24= 2, 3
Section Assembly Detail
-2 Fan Arrangement Shown(Code 24= 2)
Fan Guard
20
6
41
15
6
Ref. Part
Part
Qty.
No. Description
Number
6
Fan Assembly 1
208/230/460V111056601 2
1
Fan Assembly 575V111056602 2
15 Fan Guard
111181901 1 3
20 Panel- Weather Hood
111173101 1 3
41 Hood- Prop Exhaust
111182301 1 3
Grille Only- Prop Exhaust Hood
111182101 1 3
See detail following Isolation Damper Detail.
Quantity may be two (Code 24= 2) or three (Code 24= 3).
3
Quantity is PER fan.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 27
Section A- Outdoor/Return Air Section
0- 100% Economizer Damper Detail
Code 20= DE, DY, EE, EY, FE, FY, GE, GY, HE, HY, JE, JY
Diagrams
24
25
26
13
27
23
28
18
19
16
24
29
Linkage Detail:
With Actuator
Code 20= *E AND
MT, MTII, OR
No Controls
22
21
21
7
6
7
11
31
17
6
22
Linkage Detail:
With Actuator
Code 20= *E AND
MTIII Controls
19
10
20
19
22
4
21
4
22
21
20
17
11
5
21
7
6
21
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Linkage
Detail:
Without
Actuator
Code 20= *Y
Rev. AG 01/15
RPL 7000070 / Page 28
Section A- Outdoor/Return Air Section
0- 100% Economizer Damper w/ ACT3
Code 20= DE, DY, EE, EY, FE, FY, GE, GY, HE, HY, JE, JY
Components
Ref.
No.
4
5
6
7
10
11
13
16
17
18
19
20
21
22
23
24
25
26
27
28
29
31
40
N/S
Part Actuator
Qty.
Description
C20= *E
C20= *Y
1
Damper Assy- Complete
21
Damper Assembly 098313301 3 098313301 31
Shaft Assembly 058390001 Not Used
1
Shaft Assembly
Not Used 056081001
1
Plate- Crank Arm
(Code 12= 1M, 2M, 4M, 5M, *D, *S, Y*) 055542001 Not Used
1
Plate- Crank Arm
(Code 12= *E, *F) 066302059 Not Used
1
Shaft Assembly
Not Used 058390001
1
Shaft- Linkage 058389901 058389901
1
Bracket Support- Actuator
(Code 12= *E, *F) 403630501 Not Used
1
Channel- Support
(Code 12= *E, *F) 403659701 Not Used
1
Channel- Support
Until 4/01
Not Used 056080601
1
Channel- Support
4/01 & Later
Not Used 111087501
1
Blade- Damper 044195103 044195103
12
Stop/Anti-Rotate- Damper 065779801 065779801
4
Support- Damper Motor (Code 12= 1M, 2M, 4M, 5M, *D, *S, Y*) 055546601 Not Used
1
Channel- Support
Until 4/01
Not Used 056264501
1
Channel- Support
4/01 & Later
Not Used 111087502
1
Bar- Linkage 044194800 044194800
2
Drive Tab- Linkage Bar 044194900 044194900
2
Crank Arm- Damper
(Code 12= 1M, 2M, 4M, 5M, *D, *S, Y*) 032279200 Not Used
1
Crank Arm- Adjustable
Not Used 025072600
1
Ball Joint- Damper 000887000 000887000
4
Actuator- ACT3, 120V
ALL Until 10/98 047936105 Not Used
1
Actuator- ACT3, 120V (C12= 1M, 2M, 4M, 5M, *D, *S, Y*) 10/98 & Later 059999804 Not Used
1
Actuator- ACT3, 24V
(Code 12= *E, *F) 113139501 Not Used
1
Bushing- Linkage Bar 046098300 046098300
12
Bushing- Damper Blade 043730400 043730400
24
Gasket- Vinyl 044193116 044193116
12
Gasket- Vinyl 045655716 045655716
2
End Plug- Damper 041003501 041003501
12
End Plug- Damper 041003502 041003502
6
End Plug- Damper 041003503 041003503
6
Bearing- Sleeve
(Code 12= *E, *F) 047138504 Not Used
2
Bearing- Sleeve
Until 4/01
Not Used 047138504
2
Gasket- Neoprene 4 056003501 056003501 4
N/S= Not Shown on Diagram.
1
This Damper Assembly includes the Damper, Damper Linkage, and Actuator. Contact Daikin Applied with model and serial number
information so that the correct Damper Assembly can be identified.
2
This Damper Assembly includes the Damper and Damper Linkage, but NO Actuator. Contact Daikin Applied with model and serial number
information so that the correct Damper Assembly can be identified.
3
Damper only, no Actuator Linkage or Actuator.
4
Applied from outer edge of assembly to inside edge of center support and flush with edge of the bottom channel.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 29
Section A- Outdoor/Return Air Section
0- 100% Economizer Exhaust Damper (Until 1/05)
Code 20= DE, DY, EE, EY, FE, FY, GE, GY w/ACT10, ACT11
Diagrams
17
Damper Detail
39
25
32
23
19
35
13
15
34
25
40
43
16
39
34
43
38
18
44
View A-A
ACT11
Detail
41
43
14
34
42
33
21
20
36 ACT11
44 41
View B-B
ACT10
43 34
Detail
42
36
33
Powered Closure Exhaust
Damper Actuator Detail
(ACT10, ACT11 )
Code 20= EE, EY, GE, GY
37 ACT10
21
37
20
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 30
Section A- Outdoor/Return Air Section
0- 100% Economizer Exhaust Damper Detail (Until 1/05)
Code 20= DE, DY, EE, EY, FE, FY, GE, GY
Components
Ref. Part Damper Type
No. Description
Powered Barometric Qty.
C20= E*, G* C20= D*, F*
Exhaust Damper Assy
055929902 055929901
1
13 Blade- Exhaust 055925201055925201 7
14 Louver- Exhaust 055925602055925602 6
15 Plate- Linkage 055925801055925801 3
16 Angle- Blade Support
055925301 055925301
1
17 Angle- Blade Support
055925302 055925302
1
18 Strap- Louver 055925703055925703 1
19 Support- Damper Blade
055549001 055549001 21
20 Panel- Motor Mount
Until 2/02
055928402 Not Used
2
Panel- Motor Mount
2/02 & Later
111263001 Not Used
2
21 Plate- Linkage
Until 2/02
055928501 Not Used
2
Plate- Linkage
2/02 & Later
111263101 Not Used
2
Ratchet Pin
2/02 & Later
111059301 Not Used
2
23 Grille- Exhaust Damper
055925502 055925502
1
25 Shaft- Damper Blade
055924402 055924402 14
32 Bearing- Flange, Nylon
001113500 001113500 14
33 Fastener- Stud
018619100 Not Used
2
34 Ball Joint- Damper
000887000 000887000
2
35 Bearing- Sleeve 047138507047138507 21
36 Actuator- Motorized, Opposite Drive Side ACT11
Until 2/02
049126401 Not Used
2
2/02 & Later
111059101 Not Used
2
37 Actuator- Motorized, Drive Side ACT10
Until 2/02
049126401 Not Used
2
2/02 & Later
111059101 Not Used
2
38 Gasket- Vinyl 044193124044193124 1
39 Gasket- Sponge Rubber
021768949 021768949
2
40 Gasket- Vinyl 055940201055940201 5
41 Cap- Closure
049025401 Not Used
2
42 Spring- Compression
065497401 Not Used
2
43 Bearing- Sleeve
047138510 Not Used
2
44 Rod- Linkage
056225101 Not Used
2
*= E (powered) OR Y (manual).
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 31
Section A- Outdoor/Return Air Section
Return Air Plenum Isolation Damper w/ Actuator ACT6 (Until 12/08) 1
Code 19= BE
15
21
23
20
18
Damper Detail
22
20
15
22
View A-A
ACT6 Motorized Actuator
3
16
22
24
4
19
17
Ref.
No.
3
4
15
16
17
18
19
20
21
22
23
24
1
Part
Description
Isolation Damper Assy- Motorized
Motor Mount Assembly
Blade Assembly- Return, 4”
Angle- Linkage
Angle- Blade
Shaft- Damper Blade
Shaft- Linkage
Bearing- Flange, Nylon
Actuator- Motorized, 120V ACT6
Crank Arm- Damper
Ball Joint
Bearing- Sleeve
Gasket- Vinyl
Part
Qty.
Number
055921126
1
055921201
1
055921302 15
055917902
3
055638102 45
055637801 30
055536601
1
001113500 30
059999804
1
032279200
1
000887000
2
047138507 45
030051985 16
For units built 1/09 & Later contact Daikin Applied with model and serial number information so that the correct Damper Assembly or part(s)
can be identified.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 32
Section A- Outdoor/Return Air Section
Prop Exhaust Fan, Damper, & Inverter
Code 20= HE, HY, JE, JY AND Code 24= 2, 3
Fan Assembly Components
- 2 Fan Arrangement ShownCode 24= 2
6
6C
1B
54
51
Lube Line Detail
6E 6F
1A
6G
1
6H
Control Box
53
6A
6D
6B
(see following page
6I
575V
460V
230V
208V
Voltage
Ref.
Sch.
Part
Part
No.
Sym.
Description Number
1
AFD20
Inverter
see charts below
1A
Resistor- Inverter 044690105 1 1 1 1
1B
Jumper- Inverter 1 055719731 3 33 3
6
Fan Assembly- Complete 111056601
Fan Assembly- Complete 111056602
3
6A
Damper- Backdraft
6B
Fan Prop- 36” 300044027 1414 14 14
6C
Fan Shaft 300044028 1414 14 14
6D
Bearing 300044029 24242424
6E
Fan Sheave 019291400 1414 14 14
6F
Bushing- Fan Sheave 000804000 1414 14 14
6G
Belt 049260805 24242424
6H
Motor Sheave 000607600 1414 14 14
6I
Motor 3000468871414 14
Motor 30004625114
51
Tube- Plastic 2 020954800 8’ 8’8’ 8’
53
Coupling- Tube 2 .25 x .125 FPT 021213800 2 2 2 2
54
Fitting- Grease 2 000109800 2 22 2
Quantity= 2 when Inverter model 3500 (Code 15= G) is used.
Quantity shown are for 2 fans. Quantities for 3 fan units: Ref. 51= 32’; Ref. 53= 6; Ref. 54= 6.
Contact Daikin Applied.
4
Quantity is PER fan.
1
2
3
5
575V
460V
230V
208V
575V
Voltage
Code
Inverter Model Part
15= Number
A
55010/04 & Later 5099488008 1 1
55010/04 & Later 5099488107 1
G 3500098656919 1
3500098656929 1
3500098656906 1
3500
0986569461
R VTAC9111046871 1 1
VTAC9111046857 1
S MD2193475812 1 1
MD2193475828 1
460V
Voltage
Code
Inverter Model Part
15= Number
A
55010/04 & Later 5099488007 1 1
55010/04 & Later 5099488106 1
G 3500098656918 1
3500098656928 1
3500098656905 1
R VTAC9111046870 1 1
VTAC9111046856 1
S MD2193475811 1 1
MD2193475827 1
230V
Inverter- 3 Fan Units (Code 24= 3)
208V
Inverter- 2 Fan Units (Code 24= 2)
Model ACH401 ABB brand Inverters used before 10/04 have been discontinued and are no longer available. Replace with the comparable
Model 550 p/n shown above. Note that repair parts for Model 401 Inverters are also no longer available. The Keypad Display for Model 550
Inverters is p/n 300040924.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 33
Section A- Outdoor/Return Air Section
Prop Exhaust Fan Control Box
Until 3/05
131
135 136
2 Fan Units Shown
575V
460V
120
230V
208V
Voltage
Ref.Sch. Part Part
No. Sym. Description Number
120 PB20 Power Block 030372705 1111
131 M51, 52, 53Contactor 027514101 3333
1
135 OL51, 52, 53Overload
3333
1
136
-
Heater- Overload
9999
NOTE: Quantity shown is for a 3 Fan unit (Code 24= 3).
1
Note that there have been two different series of Overloads and Overload Heaters
used during the production run.
When replacing an Overload OR the matching Overload Heater it is VITAL to obtain
vendor p/n and amperage rating from BOTH parts.
When replacing ONLY an Overload Heater, it is VERY IMPORTANT to first obtain
vendor information and amperage rating from the existing Overload, Overload
Heater, and Motor. It is important to obtain this information to ensure that the correct
Overload Heater is selected since Overload Heaters are chosen based upon Motor
amperage draw, AND Overload Heaters are NOT interchangeable between series.
Also, Overload Heaters DO NOT automatically come with Overloads. OVERLOAD
HEATERS MUST BE ORDERED SEPARATELY.
Once vendor and amperage information is obtained, contact Daikin Applied for p/ns.
3/05 & to 10/06 2
141
140
MMP51,
MMP52,
MMP53
Detail
142
575V
460V
230V
Voltage
Ref.Sch.Part
Part
No. Sym. Description
Number
140 MMP
51, 52, 53 MMP- Prop Exh. Motors 349934012 1 1
MMP- Prop Exh. Motors 349934010 1
MMP- Prop Exh. Motors 349934009 1
141
Line Shield 3499330011111
142
Short Circuit Alarm 3499339031111
208V
2 Fan Units
Shown
NOTE: All quantities listed are PER fan.
10/06 to present 2
OL51 OL52
M51
M52
220
2 Fan Units
Shown
Contactors &
Overloads
Detail
575V
460V
230V
208V
Voltage
Ref.Sch.Part Part
No. Sym. Description Number
220OL51, 52, 53Overload 349934663 1
Overload3499346621
Overload3499346601
Overload3499346591
230 M51, 52, 53Contactor 349932123 1 1
Contactor 349932121 11
NOTE: All quantities listed are PER fan.
2
Units built between 10/06 and 12/06 may have either group of components installed.
If unsure, contact Daikin Applied to verify.
230
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 34
Section A- Outdoor/Return Air Section
Design Flow
Code 20= FE, FY, GE, GY
4
LH Louvered Door Assy
Louvered Door
Assembly Detail
Section Final
Assembly
➤
3
2
RH Louvered Door Assy
1
105
127
9
➤
131
12
110
104
106
120
Design Flow Vane and
Vane Bearings Detail
109
104
Adjuster Control Assy
Detail
RefPart
No. Description
1 Louver Panel
Left Hand Door
Louver Panel
Right Hand Door
2 Grille
3 Gasket
4 Gasket
9 Potentiometer
12 O’Ring- Potentiometer
104 Panel- Vane
105 Shaft- Upper
106 Bearing- Lower
109 Crank Arm Assy
Left Hand Door
Crank Arm Assy
Right Hand Door
110 Link Arm
120 Bearing
127 Bearing
130 Spring- Main
131 Spring- Secondary
N/S Leveling Kit- Design Flow
130
Spring
Detail
Part Qty.1
Number
059595204 15
059595203 15
055541401 2
055921403 1
055921401 1
098663701 1
098663801 1
098661803 1
098662601 1
091634501 1
091658802 1
091658801 1
2
1
060014201 1
047138535 1
098664701 1
098664901 1
091659301 1
N/S= Not shown on diagram.
1
Quantity is PER door.
2
P/N is unit specific. Contact Daikin Applied with overall length and bolt hole spacing so that the correct part can
be identified.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 35
Section A- Outdoor/Return Air Section
Return Air Fan- Fan Mounts
Until 11/04
62 or 162
161 or 61
Mounting
Diagram
163 or 63
64 or 164
Rubber Mounts (Code 21= 44B1, 44W1)
91
92
93
61
62
63 64
89
90
21
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
5- 40
50, 60
62
5- 40
50, 60
63
All
64
All
89
All
90
All
91
All
92
All
93
All
Part
Description
Channel- Mount Support
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Red
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Washer- Plain, 1/2”
Part
Qty.
Number
055512101 4
021639701 1
021639704 1
021639701 1
021639704 1
021639701 1
021639701 1
048878118 8
048164812 8
032333305 12
040499501 8
040500310 8
Spring Mounts (Code 21= 44B2, 44B3, 44W2, 44W3)
188
189
121
190
122
123
160
155
161 162
156
163 164
Spring Mounts
Ref. Fan Motor
No.
HP
121
All
122
All
123
All
155
All
156
All
160
All
161
5- 30
40- 60 162
5- 30
40- 60 163
All
164
All
188
All
189
All
190
All
N/S
All
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Part
Description
Support Assembly
Screw Adjust Assembly
Channel Assembly
Plate- Gasket Retainer
Support- Spring Locator
Pad- Rubber Vibration
Mount- Spring, Red
Mount- Spring, Green
Mount- Spring, Red
Mount- Spring, Green
Mount- Spring, Red
Mount- Spring, Red
Nut- 5/8-11
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Screw- Tapping, 1/4-20
Rev. AG 01/15
Part
Qty.
Number
055606901 4
055528201 4
055606801 4
055502101 4
055502201 4
048447901 4
048448503 1
048448504 1
048448503 1
048448504 1
048448503 1
048448503 1
040500002 4
048878118 12
048164812 8
046093809 8
RPL 7000070 / Page 36
Section A- Outdoor/Return Air Section
Return Air Fan- Fan Mounts
11/04 & Later
Rubber Mounts (Code 21= 44B1, 44W1)
91
92
61
93
62
63 64
89
21
81
91
Rubber Mounts
Part
Description
Channel- Mount Support
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Red
Nut
Screw
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Washer- Plain, 1/2”
Part
Qty.
Number
055512101 4
021639701 1
021639704 1
021639701 1
021639704 1
021639701 1
021639701 1
059992201 8
112047201 8
032333305 12
040499501 8
040500310 8
Mounting
Diagram
161 OR 61
OR
Ref. Fan Motor
No.
HP
21
All
61
5- 40
50, 60
62
5- 40
50, 60
63
All
64
All
81
All
89
All
91
All
92
All
93
All
63
163
62 OR 162
64 OR 164
Spring Mounts (Code 21= 44*2) & Seismic Spring (44*3)
188
121
189
181
Seismic strap used only
when Code 21= 44*3.
161 162
163 164
Spring Mounts
Ref. Fan Motor Part
No.
HP
Description
121
All
Mount
Spring (C21= 44*2)
Seismic (C21= 44*3)
161
5- 10
Spring Mount- Brown
15- 30
Spring Mount- Red
40- 60
Spring Mount- Red/Black
162
5- 10
Spring Mount- Brown
15- 60
Spring Mount- Red
163
5- 10
Spring Mount- Brown
15- 30
Spring Mount- Red
40- 60
Spring Mount- Red/Black
164
5- 10
Spring Mount- Brown
15- 60
Spring Mount- Red
181
All
Nut
Spring (C21= 44*2)
Seismic (C21= 44*3)
188
All
Nut
189
All
Screw
Spring (C21= 44*2)
Seismic (C21= 44*3)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Part
Number
Qty.
251783201
251783301
251784801
251784901
251785001
251784801
251784901
251784801
251784901
251785001
251784801
251784901
4
4
1
1
1
1
1
1
1
1
1
1
059992201 12
111056301 20
040500002 4
112047201 12
112047201 20
RPL 7000070 / Page 37
Section A- Outdoor/Return Air Section
Return Air Fan (Code 21= 44B*, 44W*)
21 19 18 17
27 26
37 13
1
23 24
35
11
36
4
12
48 63
5
28 29
14 30
Ref. Motor
No. HP
1
4
All
5
All
11
All
All
12
All
All
13
All
14
All
17
All
18
All
All 19 All
21
All
23
All
24
All
26
All
27
All
28 5- 20
25- 60
29
All
30
All
35
All All
36
All
All
36
All
All
37
All
48
All
63
All
Part
Description
Motor
see table on following page
Mount- Motor
Channel Assembly
Clamp- Motor Channel
until 11/02
Clamp- Motor Channel
11/02 & Later
Clamp- Motor Channel
until 11/02
Clamp- Motor Channel
11/02 & Later
Shaft- Fan
2.438” dia.
Linkage- Shaft
Tubing- Plastic
Coupling
Until 12/04
Coupling
12/04 & Later
Coupling
Fitting- Grease
1/8” MPS
Bearing, Ball Flange- 2.437”
Opposite Drive End
Bearing, Roller- 2.437”
Drive End
Key- Wheel
5/8” X 6½”
Key- Fan Sheave
5/8” x 5½”
Actuator
ACT2
Actuator
ACT2
Crank Arm- Damper
Ball Joint
Wheel- SISW
until 6/00
Wheel- SISW
6/00 & Later
Control- Fan Vane
until 6/00
Control- Fan Vane
6/00 & Later
Funnel- Inlet
until 6/00
Funnel- Inlet
6/00 & Later
Lock Collar
2.437”
Lock Washer
Cap Screw
No VIV
C21= 44B*
With VIV
C21= 44W* Qty.
056234101
056234201
056230201
056230203
056230202
056230203
056255103
Not Used
021136745
021213700
027674000
021213800
000109800
020649905
049547014
023221610
023221607
Not Used
Not Used
Not Used
Not Used
093413720
111041201
Not Used
Not Used
092045214
110941810
049115912
048164814
040499501
056234101
056234201
056230201
056230203
056230202
056230203
056255103
055536608
021136745
021213700
027674000
021213800
000109800
020649905
049547014
023221610
023221607
059999801
059999802
032279200
000887000
093413720
111041201
048447007
110941910
Not Used
Not Used
049115912
048164814
040499501
1
1
1
1
1
1
1
2
2
2
2
2
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
2
* Mounting type 1= RIS, 2= Spring, 3= Spring w/ seismic snubbers.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 38
Section A- Outdoor/Return Air Section
Return Air Fan Motors 1
H.P. Motor HP
C22=**Y
5
J*Y
7.5
K*Y
10
L*Y
15
M*Y
20
N*Y
25
P*Y
30
Q*Y
40
R*Y
50
S*Y
60
T*Y
5
J*Y
7.5
K*Y
10
L*Y
15
M*Y
20
N*Y
25
P*Y
30
Q*Y
40
R*Y
50
S*Y
60
T*Y
5
J*Y
7.5
K*Y
10
L*Y
15
M*Y
20
N*Y
25
P*Y
30
Q*Y
40
R*Y
50
S*Y
60
T*Y
5
J*Y
7.5
K*Y
10
L*Y
15
M*Y
20
N*Y
25
P*Y
30
Q*Y
40
R*Y
50
S*Y
60
T*Y
Unit
Voltage
C09= 12
208/60/3
208/60/3
208/60/3
208/60/3
208/60/3
208/60/3
208/60/3
208/60/3
208/60/3
208/60/3
C09= 29
230/60/3
230/60/3
230/60/3
230/60/3
230/60/3
230/60/3
230/60/3
230/60/3
230/60/3
230/60/3
C09= 27
460/60/3
460/60/3
460/60/3
460/60/3
460/60/3
460/60/3
460/60/3
460/60/3
460/60/3
460/60/3
C09= 37
575/60/3
575/60/3
575/60/3
575/60/3
575/60/3
575/60/3
575/60/3
575/60/3
575/60/3
575/60/3
ODP HiEff ODP PrEff. TEFC HiEff
C22= *EY C22= *JY C22= *HY
TEFC PrEff
C22= *KY
039447600065817200049186800
037530300065817300047665900
038999000065817400047666100
039896200065817500049186900
039895800065817600049187000
039448900065817700049187100
041775200205066500049187200
041775300205067100049187300
041775400205067500049187400
041775800205067700049187500
065819500
065819600
065819700
065819800
065819900
065820000
205066800
205070700
205091600
039442500065818200040161200
039448700065818300049100500
039446500065818400044691100
039446600065818500038689700
039448800065818600040161300
039896100065818700040161400
040626800205066600049025300
041770000205067200048448000
039899200205067600040161600
041775500065819100046748300
065820200
065820300
065820400
065820500
065820600
065820700
205066900
205069200
205069400
205069600
039442500065818200040161200
039448700065818300049100500
039446500065818400044691100
039446600065818500038689700
039448800065818600040161300
039896100065818700040161400
040626800205066600049025300
041770000205067200048448000
039899200205067600040161600
041775500065819100046748300
065820200
065820300
065820400
065820500
065820600
065820700
205066900
205069200
205069400
205069600
046741900205168900049188400
047443300205168800049188500
047443400205168600049188600
047443500205166600049185200
049181100205166800049188700
049181200205166900049188800
049181300205066700049188900
049181400205067300049189000
049181500205091800049189100
049181600205069000049189200
046514600
046514700
065821400
065821500
065821600
065821700
205067000
205069300
205069500
205069800
2
All motors listed are Across-The-Line start (Code 10= AL, PW). There are a small number of units that have Part-Winding start motors (Code
10= PP, PS). These units have motors 15HP and greater and are 208V or 230V only. Contact Daikin Applied if a PW replacement motor is
needed. Note that Standard Efficiency Motors (Code 22= *AY, *GY) are no longer available. Use High (HiEff.) or Premium Efficency (PrEff.)
instead.
2
60 HP motors are not available in 208/230V (Code 09= 12, 29).
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 39
Section A- Outdoor/Return Air Section
Section Mounted Controls
OAE, RAE, RAT, SD2, LT11, S11, REC11
OAE- Mechanical Enthalpy (Code 17= Y*)
Economizer
40
Bottom Return
Shown
Code 19= BY, BE
41
RefPart
No. Description
40 Mount- OAE Enthalpy
41 Enthalpy Assembly
(Knob & Control)
Knob only
Control- OAE only
Part
Number
055800101
Qty.
1
055740691
026215500
030706702
1
1
1
40
41
Economizer
OAE & RAE Differential Enthalpy (Code 17= C*)
40
Mixing Box
43
RefPart
No. Description
40 Mount- OAE Enthalpy
Economizer Units
Mixing Box Units
41 Control- OAE
43 Control- RAE
Part
Number
059328901
055800301
049262201
049262202
Qty.
1
1
1
43
RAT- Return Air Temperature Sensor
RefPart
Part
No. Description Number Qty.
7 Sensor- RAT
MicroTech Controls 065829505 1
MicroTech II Controls 060004705 1
MicroTech III Controls 193414602 1
7
SD2- Return Air Smoke Detector
Code 16= 1, 3
30
30
n
tur
Re
Back Return
Code 19= HY
g
nin
pe
O
Air
Re
Op tur
en n A
in ir
g
Bottom Return
Code 19= BY, BE
84
88
85
89
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Ref Part
Part
No. Description
Number
Qty.
30 Smoke Detector SD2 098873101 11
1
The original Smoke Detector for units built 2003 & Earlier is no
longer available. When replacing any version of SD2, reuse
existing Sampling Tubes or order 1pc. 098873101 for Standard
Discharge or 2pc. of 098873501 for Side or Top Discharge.
Minor field modifications may be required for proper installation.
LT11- Return Fan Light/S11- Return Fan Light
Switch/REC11- Return Fan Light Receptacle
Code 49= E, F
RefPart
No. Description
84 Light Fixture
85 Bulb- LT11
88 Light Switch- S11
89 Receptacle- REC11
Rev. AG 01/15
Part
Number Qty.
042229500 1
065492402 1
065492201 1
030187000 1
RPL 7000070 / Page 40
Section B- Draw-Thru Filter/Blank Section
Notes
➩
Primary Codes that pertain: 25
Additional Codes that pertain: 06, 19, 20
Code 25 determines all of the section characteristics. If the first digit of Code 25= A,D, E the Filters are in an angular
rack; if the first digit= F, G, H the Filters are in a flat rack; if the first digit= S, T, V the Filters are in a staggered rack; if
the first digit is L the Filters are in a large staggered rack; and If the first digit= B, C there is a Blank/empty Section. If
the second digit= Y Filters were not factory supplied; if the second digit= A there are throwaway Filters; if the second
digit= B there are 30% eff. Filters; and if the second digit= C there are 30% eff. Filters with antimicrobial Intersept.
If the second digit= D there are 65% eff. Filters; if the second digit= E there are 95% eff. Filters; and if the second
digit= G there are 95% eff. Filters with antimicrobial Intersept.
Code 06 determines the final assembly panel part numbers. For sheet metal components that make up the
Draw-Thru Filter/Blank Access Section, contact Daikin Applied with model and serial number information
to ensure that the correct liners, insulation and hardware are ordered.
Codes 19 and 20 determine the Return Air section which has an effect on the final assembly panels.
Section B- Draw-Thru Filter/Blank Section
Section Mounted Controls
PC5- Clogged Filter Control and
SPS5- Clogged Filter Static Pressure Sensor
65
71
66
70
60
84
88
85
89
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Controls PC5 and SPS5
ef.Part
R
No. Description
60 Cover 1
65 PC5 Pressure Ctl
66 SPS5 Transducer 1
70 Plastic Tube 1
71 Grommet 1
1
Part Qty.
Number
0557325011
065493801 1
0495450051
0490951041
0049101001
MicroTech controls (Code 12= 1M, 2M, 4M, 5M) only.
LT13- Filter Section Light/S13- Filter Section
Light Switch/REC13- Filter Section Receptacle
RefPart
No. Description
84 Light Fixture
85 Bulb- LT13
88 Light Switch- S13
89 Receptacle- REC13
Rev. AG 01/15
Part
Number Qty.
055737501 1
065492402 1
065492201 1
030187000 1
RPL 7000070 / Page 41
Section B- Draw-Thru Filter/Blank Section
Filters
Angular Filter Rack- Code 25= AA, AB, AC, DB, DC, EB, EC
14
4
4
Air w
Flo
4
5
8
14
Ref. Part
Code
Part Qty.
No. Description
25= Number
4 Filter- Throwaway 1
AA 00001610033
Filter- 30% Eff. Throwaway 1 *B 03129800233
Filter- 30% Eff w/Intersept 1 *C 11104630633
5 Filter- Throwaway 2
AA 00001170011
Filter- 30% Eff. Throwaway 2 *B 03129800111
Filter- 30% Eff w/Intersept 2 *C 11104630511
8 Stop, Filter
011484101 11
14 Angle Assembly 3 05607730133
* First digit of code, may be A, D, E.
1
Filter size= 16 x 25 x 2.
2
Filter size= 16 x 20 x 2.
3
Optional- angle is mounted on leaving air side.
Flat Filter Rack- Code 25= FD, FE, FG, GD, GE, GG, HD, HE, HG
107A 107
105
105A
104A
104
106
106A
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Ref. Part
Code
Part Qty.
No. Description
25= Number
104 Filter- 65% Eff. Cartridge 4 *D 06581070412
Filter- 95% Eff Cartridge 4 *E 06581070212
104A Gasket- Filter
021768924 12
105 Filter- 65% Eff. Cartridge 5 *D 0658107034
Filter- 95% Eff Cartridge 5 *E 0658107014
105A Gasket- Filter
021768912 4
106 Pre Filter 6
*D or *E
until 3/02 031298006 12
3/02 & Later 111046101 12
106A Gasket- Pre Filter 111051900 24ft
107 Pre Filter 7
*D or *E
until 3/02 031298005 4
3/02 & Later 111046103 4
107A Gasket- Pre Filter 111051900 8 ft
* First digit of code, may be F, G, H.
4
5
Filter size= 24 x 24 x 12.
Filter size= 12 x 24 x 12.
6
7
Filter size= 24 x 24 x 2.
Filter size= 12 x 24 x 2.
Rev. AG 01/15
RPL 7000070 / Page 42
Section B- Draw-Thru Filter/Blank Section
Filters, Continued
Staggered Filter Rack- Code 25= SD, SE, SG, TD, TE, TG, VD, VE, VG
204 204A
Ref. Part
Code
Part Qty.
No. Description
25= Number
204 Filter- 65% Eff. Cartridge 1 *D 06581070416
Filter- 95% Eff Cartridge 1 *E 06581070216
204A Gasket- Filter
021768924 16
206 Pre Filter 2
*D or *E
until 3/02 031298006 16
3/02 & Later 111046101 16
206A Gasket- Pre Filter 111051900 32ft
* First digit of code, may be S, T, V.
1
Filter size= 24 x 24 x 12.
2
Filter size= 24 x 24 x 2.
206A 206
Large Staggered Filter Rack- Code 25= LD, LE, LG
204
206A
Code
Part Qty.
No. Description
25= Number
204 Filter- 65% Eff. Cartridge 3 LD 06581070416
Filter- 95% Eff Cartridge 3 LE 06581070216
204A Gasket- Filter
021768924 16
205A 205 Filter- 65% Eff. Cartridge 4 LD 0658107038
4
205 Filter- 95% Eff Cartridge LE 0658107018
205A Gasket- Filter
021768912 8
206 Pre Filter 5
LD/LE
until 3/02 031298006 16
3/02 & Later 111046101 16
206A Gasket- Pre Filter 111051900 32ft
207
6
LD/LE
207A 207 Pre Filter until
3/02
031298005 8
205
3/02 & Later 111046103 8
205A
207A Gasket- Pre Filter 111051900 16ft
204
204A
206
207
204
204A Ref. Part
204A
207A
3
5
Filter size= 24 x 24 x 12.
Filter size= 24 x 24 x 2.
4
6
Filter size= 12 x 24 x 12.
Filter size= 12 x 24 x 2.
Air Blender Section Parts
(Code 25= EE, EC, HD, HE, HG, VD, VE, VG)
68
75
Ref.Part
Part Qty.
No. Description
Number
65 Panel- Access 251802801 2
68 Air Blender 205139546 2
75 Plate- Economizer Linkage Access 059384601 1
68
65
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 43
Section C- Draw-Thru Blank Access Section
OR Separate Inverter Section
Notes
➩
Primary Codes that pertain: 26, 14, 15
Additional Codes that pertain: 06
Code 26 determines if a section is installed and if so, the size of the section. If Code 26= S there is a 48” Blank/
empty Section. If Code 26= Y, there is no section.
Codes 14 & 15 determine if the unit has inverter(s) and if so where they are installed. If Code 14= 1, 2, 4 AND Code
26= S, there is a separate Inverter Section. If Code 14= 3, 5, 6, 7, 8, 9, the inverter(s) are installed in the Supply Air
Section. If Code 14= Y, there are no inverters. Code 15 determines the Inverter vendor specified. An Inverter with
Bypass is shown below (the illustration shows the Inverter Bypass Box used until 3/05). All components pertaining
to the inverter(s) are listed in the Supply Air Section (Section F).
Code 06 determines the liners and insulation, and will affect the final assembly panels. For sheet metal components
that make up theBlank Access/Separate Inverter Section, contact Daikin Applied to ensure correct liners,
insulation and hardware are ordered.
Return Air Inverter
(AFD20)
Overload
(OL10- Supply
Air)
(OL20- Return
Air)
Supply Air Inverter
(AFD10)
Contactor
(M30A/M30B- Supply Air)
(M40A/M40B- Return Air)
Power Block
(PB10- Supply Air)
(PB20- Return Air)
Unit Mounted Controls
LT17- DT Blank Access, Separate Inverter Section Light/S17- DT Blank
Access, Separate Inverter Section Light Switch/REC17- DT Blank Access
OR Separate Inverter Section Filter Section Receptacle
84
88
85
89
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” LT17- D-T Blank Section Light/S17- D-T Blank
Section Light Switch/REC17- D-T Blank Section
Receptacle
RefPart
No. Description
84 Light Fixture
85 Bulb- LT17
88 Light Switch- S17
89 Receptacle- REC17
Rev. AG 01/15
Part
Number Qty.
042229500 1
065492402 1
065492201 1
030187000 1
RPL 7000070 / Page 44
Section D- Draw-Thru Cooling Section
Notes
➩
Primary Codes that pertain: 03, 27, 28
Additional Codes that pertain: 06
Code 03 determines the DX Cooling Coil size. If Code 03= S there is a small face area Coil (24” section for unit
sizes 080, 090 or 48” section for unit sizes 105- 115). If Code 03= L there is a large face area Coil (48” section for
unit sizes 080, 090 or 24/48” for unit sizes 105- 135).
Code 27 determines if there is a Section D. If Code 27= YYYY, then there is no section (for RPS or RFS units this
indicates that the cooling coil is in the Blow-Thru position [RDT units always have a section D]). If the code is CYYY,
CYYS then there is a unit Cooling Coil and Drain Pan (the “S” means the Drain Pan is stainless steel, a “Y” in the
fourth position indicates that the pan is galvanized). If Code 27= DYYY, DYYS, then the section contains only a
Drain Pan (not an option for RDT units).
Code 28 will apply only if Code 27= CYYY, CYYS and determines Cooling Coil characteristics.
Code 06 determines the liners and insulation, and will affect the final assembly panels. For sheet metal components
that make up the Draw-Thru Cooling Section, contact Daikin Applied to ensure that correct liners, insulation
and hardware are ordered.
NOTE: The drawings and components listed in this section also apply to Section I—
Blow-Thru Cooling Section- RPS or RFS units.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 45
Section D- Draw-Thru Cooling Section
Evaporator Coils, Drain Pans, Gasketing
Small Face DX Coils (Code 03= S, Unit Sizes 080, 090)
Small Face Area Coil
24” Section
Code 03= S
Unit Sizes 080, 090
3
39
43
13
10
Ref.Part
Part Qty.
No. Description Number
3 Coil
see below
10 Drain Pan
Sloped 1
Galvanized
C27= CYYY 056267751 1
Stainless
C27= CYYS 056267752 1
Drain Pan
Non- Sloped 1
Galvanized
C27= CYYY 055531301 1
Stainless
C27= CYYS 055531302 1
13 Pan- Auxiliary 9/93 & Later
Galvanized
C27= CYYY 055926503 1
Stainless
C27= CYYS 057356801 1
Pan- Auxiliary
Until 9/93 055524402 1
39 Gasket 049263200 8’
43 Gasket 021911422 2
1
Sloped Drain Pans are used 9/93 & Later.
DX Evaporator Coils- Small Face (Code 03= S)
Note: For units built 9/93 & Earlier, 1/07 & Later, OR built with Copper Fins contact Daikin Applied.
Coil
Description
4Z 08 3 D
Fin Stock
D= AluminumLanced
C= Copper
H= Aluminum
Rows
3, 4, 5 ,6
Fins-per-inch
08, 10 ,12
Coil Model
Ref. Coil Description No. Code 28= 3Coil
4Z083D
4Z084D
4Z085D
4Z103D
4Z104D
4Z105D
4Z123D
4Z124D
4Z125D
5Z083H
5Z084H
5Z085H
5Z103H
5Z104H
5Z105H
5Z123H
5Z124H
5Z125H
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Unit Size Qty.
080, 090
0684715671
0684714681
0684715681
0684717361
0684715291
0684714711
0684715451
0684714581
0684714591
0684710791
0684711431
0684712261
0684713471
0684711921
0684712541
0684712551
0684713581
0684711221
RPL 7000070 / Page 46
Section D- Draw-Thru Cooling Section
Evaporator Coils, Drain Pans, Gasketing
Small Face DX Coils (Code 03= S, Unit Sizes 105, 115)
Small Face Area Coil
48” Section
Code 03= S
Unit Sizes 105, 115
4
43
3
11
12
13
39
39
37
10
Ref.Part
Part Qty.
No. Description Number
3 Coil- Upper see next page
4 Coil- Lower see next page
10 Drain Pan
Sloped 1
Galvanized
C27= CYYY 056267755 1
Stainless
C27= CYYS 056267756 1
Drain Pan
Non- Sloped 1
Galvanized
C27= CYYY 055531305 1
Stainless
C27= CYYS 055531306 1
11 Drain Pan
Sloped 1
Galvanized
C27= CYYY
4/00 & Later 096235001 1
Until 4/00 055531353 1
Stainless
C27= CYYS 055531354 1
Drain Pan
Non- Sloped 1
Galvanized
C27= CYYY 055531303 1
Stainless
C27= CYYS 055531304 1
12 Pan- Liner
9/93 & Later 055531202 1
Until 9/93 055531201 1
13 Pan- Auxiliary
11/01 & Later 056271401 1
Until 11/01 055524401 1
37 Gasket 056003501144
39 Gasket 04926320010’
43 Gasket 021911422 4
1
Sloped Drain Pans are used 9/93 & Later.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 47
Section D- Draw-Thru Cooling Section
Small Face DX Evaporator Coils (Code 03= S, Unit Sizes 105, 115)
Continued
DX Evaporator Coils- Small Face (Code 03= S)
Note: For units built 9/93 & Earlier, 1/07 & Later, OR built with Copper Fins contact Daikin Applied.
Coil
Description
4Z 08 3 D
Fin Stock
D= Aluminum- Lanced
C= Copper
H= Aluminum
Rows
3, 4, 5 ,6
Fins-per-inch
08, 10 ,12
Coil Model
Ref.
No.
3
4
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Coil Description Code 28= Coil- Upper
4Z083D
4Z084D
4Z085D
4Z103D
4Z104D
4Z105D
4Z123D
4Z124D
4Z125D
5Z083H
5Z084H
5Z085H
5Z086H
5Z103H
5Z104H
5Z105H
5Z106H
5Z123H
5Z124H
5Z125H
5Z126H
Coil- Lower
4Z083D
4Z084D
4Z085D
4Z103D
4Z104D
4Z105D
4Z123D
4Z124D
4Z125D
5Z083H
5Z084H
5Z085H
5Z086H
5Z103H
5Z104H
5Z105H
5Z106H
5Z123H
5Z124H
5Z125H
5Z126H
Rev. AG 01/15
Unit Size Qty.
105,115
0684810841
0684714691
0684715101
0684714721
0684715771
0684714951
0684810351
0684714601
0684714611
0684713861
0684713731
0684710901
0684711371
0684712111
0684711361
0684710661
0684711061
-
1
0684710691
0684711651
0684710911
0684716311
0684810191
0684810331
0684810211
0684810591
0684810281
0684715191
0684810141
0684810561
0684809781
0684809681
0684808461
0684808711
0684809031
0684808701
0684808401
0684808531
0684809831
0684808411
0684808841
0684808471
RPL 7000070 / Page 48
Section D- Draw-Thru Cooling Section
Large Face DX Evaporator Coils (Code 03= L, Unit Sizes 080- 135)
4
43
3
11
Large Face Area Coil
48” Section (unit sizes 080, 090)
24/48” Section (unit sizes 105- 135)
Code 03= L
(080, 090 shown)
12
13
39
39
37
Base- 080, 090
10
39
Base- 105- 135
48” Section- 080, 090
24/48” Section- 105- 135
Ref.Part
Part Qty.
No. Description Number
3 Coil- Lower see next page
4 Coil- Upper see next page
10 Drain Pan
Sloped 1
Galvanized
C27= CYYY 056267755 1
Stainless
C27= CYYS 056267756 1
Drain Pan
Non- Sloped 1
Galvanized
C27= CYYY 055531305 1
Stainless
C27= CYYS 055531306 1
11 Drain Pan
Sloped 1
Galvanized
C27= CYYY
4/00 & Later 096235001 1
Until 4/00 055531353 1
Stainless
C27= CYYS 055531354 1
Drain Pan
Non- Sloped 1
Galvanized
C27= CYYY 055531303 1
Stainless
C27= CYYS 055531304 1
12 Pan- Liner
9/93 & Later 055531202 1
Until 9/93 055531201 1
13 Pan- Auxiliary
11/01 & Later 056271401 1
Until 11/01 055524401 1
37 Gasket 056003501144
39 Gasket 04926320010’
43 Gasket 021911422 4
Ref.Part
Part Qty.
No. Description Number
3 Coil- Lower see next page
4 Coil- Upper see next page
10 Drain Pan
Sloped 2
Galvanized
C27= CYYY 056267751 1
Stainless
C27= CYYS 056267752 1
Drain Pan
Non- Sloped 2
Galvanized
C27= CYYY 055531305 1
Stainless
C27= CYYS 055531306 1
11 Drain Pan
Sloped 2
Galvanized
C27= CYYY
4/00 & Later 096235001 1
Until 4/00 055531353 1
Stainless
C27= CYYS 055531354 1
Drain Pan
Non- Sloped 2
Galvanized
C27= CYYY 055531303 1
Stainless
C27= CYYS 055531304 1
12 Pan- Liner
9/93 & Later 055531202 1
Until 9/93 055531201 1
13 Pan- Auxiliary
11/01 & Later 056271401 1
Until 11/01 055524401 1
37 Gasket 056003501168
39 Gasket 04926320011’
43 Gasket 021911422 4
1
Sloped Drain Pans are used 9/93 & Later.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” 2
Sloped Drain Pans are used 9/93 & Later.
Rev. AG 01/15
RPL 7000070 / Page 49
Section D- Draw-Thru Cooling Section
Large Face DX Evaporator Coils (Code 03= L, Unit Sizes 080- 135)
Continued
DX Evaporator Coils- Large Face (Code 03= L)
Note: For units built 9/93 & Earlier, 1/07 & Later, OR built with Copper Fins contact Daikin Applied.
Coil
Description
4Z 08 3 D
Fin Stock
D= Aluminum- Lanced
C= Copper
H= Aluminum
Rows
3, 4, 5 ,6
Fins-per-inch
08, 10 ,12
Coil Model
Ref.
No.
3
4
Coil Description
Unit Size
Qty.
Code 28= 080, 090
105-135
Coil- Lower
4Z083D
068481084068471575 1
4Z084D
068471469068471470 1
4Z085D
068471510068471563 1
4Z103D
068471472068471570 1
4Z104D
068471577068471482 1
4Z105D
068471495068471506 1
4Z123D
068481035068471523 1
4Z124D
068471460068471462 1
4Z125D
068471461068471463 1
5Z083H
068471386068471379 1
5Z084H
068471373068471214 1
5Z085H
068471090068471228 1
5Z086H
068471137
-
1
5Z103H
068471211068471213 1
5Z104H
068471136068471274 1
5Z105H
068471066068471139 1
5Z106H
068471106
1
5Z123H
068471395 1
5Z124H
068471069068471053 1
5Z125H
068471165068471056 1
5Z126H
068471091
-
1
Coil- Upper
4Z083D
068471631068481058 1
4Z084D
068481019068481020 1
4Z085D
068481033068481053 1
4Z103D
068481021068481057 1
4Z104D
068481059068481024 1
4Z105D
068481028068481031 1
4Z123D
068471519068481036 1
4Z124D
068481014068481016 1
4Z125D
068481056068481017 1
5Z083H
068480978068480972 1
5Z084H
068480968068480906 1
5Z085H
068480846068480913 1
5Z086H
068480871
-
1
5Z103H
068480903068480905 1
5Z104H
068480870068480926 1
5Z105H
068480840068480872 1
5Z106H
068480853
-
1
5Z123H
068480983068481117 1
5Z124H
068480841068480835 1
5Z125H
068480884068480837 1
5Z126H
068480847
-
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 50
Section E- 48” Spacer Section
RPS, RDT, RFS Units
Notes
➩
Primary Codes that pertain: 30
Additional Codes that pertain: 06
Code 30 determines all of the section characteristics. If Code 30= BBBBBB there is a 48” Blank/empty Section. If
Code 30= YYYYYY, there is no section.
Code 06 determines the liners and insulation, and will affect the final assembly panels. For sheet metal components
that make up the 48” Spacer Section, contact Daikin Applied to ensure that correct liners, insulation and
hardware are ordered.
Section E- Draw-Thru Heat Section
RDT Units
Notes
➩
Primary Codes that pertain: 04, 30
Additional Codes that pertain:
Code 04 determines what type of heat is specified. Draw-Thru Heat units are normally hydronic heat with Steam
(Code 04= S) OR Hot Water (Code 04= W) Heating Coils.
Code 30 determines the coil and associated valve characteristics.
Section Mounted Controls
LT18, REC18, S18- Section Mounted Light
284 285
288 289
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” LT18- D-T Heat Section Light/S18- D-T Heat
Section Light Switch/REC18- D-T Heat
Section Light Receptacle
RefPart
No. Description
284 Light Fixture
285 Bulb- LT18
288 Light Switch- S18
289 Receptacle- REC18
Rev. AG 01/15
Part
Number Qty.
042229500 1
065492402 1
065492201 1
030187000 1
RPL 7000070 / Page 51
Section E- Draw-Thru Heat Section
RDT Units
Hot Water OR Steam Coil Heat, Mixing Valves & Actuator VM1
Code 30 first 3 digits = S11, S12, S13, S14, W11, W22
Diagrams & Components
Mixing Valve Detail- HW, Steam
12/08 & Earlier
Coil Location
63
3
64
2
Mixing Valve Detail- Hot Water
1/09 & Later
163
65
Mixing Valve Detail- Steam
1/09 & Later
249
263
RefSch. Part
No. Sym. Description
2
Steam Heat Coil- Bottom
Steam Heat Coil- Bottom
Steam Heat Coil- Bottom
Steam Heat Coil- Bottom
Hot Water Heat Coil- Bottom
Hot Water Heat Coil- Bottom
3
Steam Heat Coil- Top
Steam Heat Coil- Top
Steam Heat Coil- Top
Steam Heat Coil- Top
Hot Water Heat Coil- Top
Hot Water Heat Coil- Top
1
2
Code
30= S11***
S12***
S13***
S14***
W11***
W22***
S11***
S12***
S13***
S14***
W11***
W22***
Coil
Type
5JA0601H
5JA1201H
5JA0602C
5JA1202C
5WH0901H
5WS0902C
5JA0601H
5JA1201H
5JA0602C
5JA1202C
5WH0901H
5WS0902C
Coil
Height
42”
42”
42”
42”
42”
42”
39”
39”
39”
39”
39”
39”
Part
Number Qty.
056053061 11
056053062 11
056053063 1
056053064 1
056053065 11
056053066 1
056053041 21
056053042 21
056053043 1
056053044 1
056053045 21
056053046 1
Contact Daikin Applied for units built before 1/95.
Contact Daikin Applied for units built before 1/95.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 52
Section E- Draw-Thru Heat Section
RDT Units
Hot Water OR Steam Coil Heat, Mixing Valves AND Actuator VM1
Code 30 first 3 digits = S11, S12, S13, S14, W11, W22
Components, Continued
RefSch. Part Code
Coil
No. Sym. Description
30= Type
Valve/Actuator 12/08 & Earlier
63 VM1 Actuator- 120V
*****E
All
64
Linkage- 1.25”, 1.50”, 2.00” Valve
*****E
All
Linkage- 2.50”, 3.00” Valve
*****E
All
65
Valve, 2 Way- Steam Heat
1.25” S**E2*
5JA
1.50” S**F2*
5JA
2.00” S**G2*
5JA
2.50” S**H2*
5JA
3.00” S**J2* 5JA
Valve, 3 Way- Hot Water Heat
1.25” W**E3* 5WH, 5WS
1.50” W**F3* 5WH, 5WS
2.00” W**G3* 5WH, 5WS
2.50” W**H3* 5WH, 5WS
3.00”
W**J3* 5WH, 5WS
Valve Assy.
1/09 & Later
163 VM1 Actuator- 24V, 1.25”- 2.00” Valve 3W****E
All
Actuator- 24V, 2.50”- 3.00” Valve 3W****E
All
263
Valve, 3 Way- HW w/ Actuator
1.25” W**E3E 5WH, 5WS
1.50” W**F3E 5WH, 5WS
2.00” W**G3E 5WH, 5WS
2.50” W**H3E 5WH, 5WS
3.00” W**J3E 5WH, 5WS
249
Valve, 2 Way- Steam w/ Actuator 4
1.25” S**E2E
5JA
1.50” S**F2E
5JA
2.00” S**G2E
5JA
2.50” S**H2E
5JA
Coil
Height
Part
Number
Qty.
All
All
All
059999804
049762401
049762403
1
1
1
All
All
All
All
All
049762502 1
049762503 1
049762504 1
049762505 1
049762506 11
All
All
All
All
All
047936505 1
047936501 1
047936502 1
047936506 1
047936503 21
All
All
300046566 1
113149601 1
All
All
All
All
All
113166703
113166704
113166705
113166706
113166707
1
1
1
1
1
All
All
All
All
113147501
113147701
113147901
113148101
1
1
1
1
Steam Heat 3.00” Valve has a Flange Gasket p/n: 031315900.
Hot Water Heat 3.00” Valve has a Flange Gasket p/n: 031316000.
3
Note that the HW Valve is factory supplied WITH the Actuator. Use this p/n when replacing the HW Actuator ONLY.
4
Note that the Steam Valve is factory supplied WITH the Actuator. For Actuator ONLY p/ns contact Daikin Applied with model and
serial number information so that the correct Actuator can be identified.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 53
Section F- Supply Air Section
Notes
➩
Primary Codes that pertain: 31, 32, 33, 12, 14, 15, 40
Additional Codes that pertain: 04, 06, 26, 34, 49
Code 31 determines the Supply Fan size and type, Code 32 determines the Fan Motor horsepower and type, and
Code 33 determines the drive selection. Drive components (Fan Sheave, Motor Sheave, V-belt(s), and Sheave
Bushing(s) [if required]) are NOT listed as they are unique to the unit. If a drive component is required you
may use the number from the part and cross reference it with the Drive Components Cross Reference, form
number 571006, or contact Daikin Applied with model and serial number information for identification. Supply
Air Fan Motors range from 5- 75 horsepower.
Code 12 determines the location of the unit’s Main Control Box. RDT units with no Blow-Thru section have Main
Control Boxes in the Supply Air section.
Codes 14 and 15 determine if the unit has inverter(s) and if so where they are installed. If Code 14 equals 1- 9 (or
X for units built prior to 2000), the inverter(s) are installed in the Supply Air Section. If Code 14= 1, 2, 4 AND Code
26= S, there is a separate Inverter Section. If Code 14= Y, there are no inverters. Code 15 determines the inverter
vendor. All components pertaining to the Supply Air Fan Inverter are listed in this section.
Code 40 determines the Discharge Plenum configuration. The Discharge Plenum is located in Section F when the
section is bolted directly to the Condenser (Section M). RDT units always have the Discharge Plenum located in
Section F. If Code 40= BE, there is an Isolation Damper with Actuator ACT5. Isolation Dampers are detailed
in Section K.
Code 04 and Code 34 determine the heat type, which can affect the final assembly part numbers, the location of the
Discharge Plenum, as well as the section installed controls.
Code 06 determines the liners and insulation, and will affect the final assembly panels. For sheet metal components
that make up the Supply Air Section, contact Daikin Applied to ensure that correct liners, insulation and
hardware are ordered.
Code 49 determines if the Supply Air cabinet has a Belt Guard (Code 49= A, D), a Fan Section Light (Code 49= B,
E), or both (Code 49= C, F).
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 54
Section F- Supply Air Section
Forward Curved Fans
Low Pressure (FCLP)- Code 31= 33F*, 36F*, 40F*
1
2
15
17
17
3
21
16
12
5
22 11
23 20
Ref. Part
No. Description
1 Motor- see table after Fan Mount section
2
Housing- Blower Assy
Housing- Blower Assy
Housing- Blower Assy
3
Wheel Assembly
Wheel Assembly
Wheel Assembly
5
Screw Adjust Assy
11
Shaft- 2.188” Dia.
Shaft- 2.438” Dia.
Shaft- 2.688” Dia.
12
Plate, Cutoff
Plate, Cutoff
Plate, Cutoff
15
Mount Assy- Motor
16
Angle- Motor Mount 17Hold Down
20
Plate- Shim
21
Key- Fan, 4.75” Long
Key- Fan, 6.90” Long
22
Key- Sheave, 6.50” Long
Key- Sheave, 6.50” Long
23
Bearing- Ball- 2.188” Bearing- Ball- 2.438”
Bearing- Ball- 2.688” 1
Part Fan Size
Number 33” 36” 40”
055527716
1
055527717
1
055527719
1
012725735
1
012726239
1
012726743
1
055528202
1
1
1
055582702
1
055667502
1
055664602
1
029309800
1
029309900
1
029310001
1
056104501
1
1
1
055514201
1
1
1
0412729002 22
032422700
2
023221508
1
023221619
1
1
023221515
1
023221610
1
1
020648654 12
020648655 1 2
020648658 1 2
Note that some units may have been equipped with standard setscrew locking bearings. This locking collar style
bearing is the recommended replacement.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 55
Section F- Supply Air Section
Forward Curved Fans
High Pressure (FCMP)- Code 31= 33M*, 36M*
1
2
15
17
17
3
21
16
12
5
22 11
20 23
Ref.
No.
1
2
3
5
11
12
15
16
17
20
21
22
23
1
Part
Description
Motor- see table after Fan Mount section
Housing- Blower Assy
Housing- Blower Assy
Wheel Assembly
Wheel Assembly
Screw Adjust Assy
Shaft- 2.438” Dia.
Shaft- 2.688” Dia.
Plate, Cutoff
Plate, Cutoff
Mount Assy- Motor
Angle- Motor Mount Hold Down
Plate- Shim
Key- Fan, 9.25” Long
until 4/01
Key- Fan, 4.25” Long
4/ 01 & Later
Key- Fan, 10.00” Long
Key- Sheave, 6.50” Long
Bearing- Ball- 2.437”
Bearing- Ball- 2.688”
Part
Number
Fan Size
33” 36”
055527716
1
055527718
012727939
1
012728343
055528202
1
055515702
1
055667303
029309800
1
029309900
056104501
1
055514201
1
041272900
2
032422700
1
023221614
1
023221617
2
023221613
023221610
1
020648655 12
020648658 1
1
1
1
1
1
1
1
2
1
1
2
Note that some units may have been equipped with standard setscrew locking bearings. This locking
collar style bearing is the recommended replacement.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 56
Section F- Supply Air Section
Air Foil Fan- Double Width
Code 31= 33V*, 33A*, 36V*, 36A*, 40V*, 40A*
Detail A
14
View FACING Discharge
opening
27
21
3
4
26
19
2
17
27
13
6
18
27
1
14
17
See Detail A
to Left
15
6
26
19
VAV
11
5
25
detail on page after next
5
13
22
16
Ref. Part
No Description
1 Motor- see table after Fan Mount section
2 Housing Assy- Blower, w/Inlet Vanes
Code 31= 33V*
Inlet Vane Assembly Only
CW
Inlet Vane Assembly Only
CCW
Housing Assy- Blower, w/o Inlet Vanes
Code 31= 33A*
Inlet Funnel Only
Housing Assy- Blower, w/Inlet Vanes
Code 31= 36V*
Inlet Vane Assembly Only
CW
Inlet Vane Assembly Only
CCW
Housing Assy- Blower, w/o Inlet Vanes
Code 31= 36A*
Inlet Funnel Only
Housing Assy- Blower, w/Inlet Vanes
Code 31= 40V*
Inlet Vane Assembly Only
CW
Inlet Vane Assembly Only
CCW
Housing Assy- Blower, w/o Inlet Vanes
Code 31= 40A*
Inlet Funnel Only
3 Wheel, Fan- Single Inlet Single Width
CW
Wheel, Fan- Single Inlet Single Width
CW
Wheel, Fan- Single Inlet Single Width
CW
4 Wheel, Fan- Single Inlet Single Width
CCW
Wheel, Fan- Single Inlet Single Width
CCW
Wheel, Fan- Single Inlet Single Width
CCW
5 Screw Adjust Assembly
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Part Fan Size
Number 33” 36” 40”
055527710
1
032739500
1
032738900
1
055527704
1
031940903
2
055527711
1
032739600
1
032739000
1
055527705
1
031940904
2
055527712
032739700
032739100
055527706
031940905
066543205
1
066543207
1
066543209
066543206
1
066543208
1
066543210
055528202
2
2
1
1
1
1
2
1
1
2
RPL 7000070 / Page 57
Section F- Supply Air Section
Air Foil Fan- Double Width
Code 31= 33V*, 33A*, 36V*, 36A*, 40V*, 40A*
Continued
Ref. Part
Part Fan Size
No Description Number 33” 36” 40”
6 Crank Arm Units with Inlet Vanes only 055529403
1
Crank Arm Units with Inlet Vanes only 055529404
1
Crank Arm Units with Inlet Vanes only 055529405
1
11 Shaft- 2.438” Diameter 055515702
1
Shaft- 2.688” Diameter 055667303
1
Shaft- 2.938” Diameter 055642402
1
13 Angle- Linkage Units with Inlet Vanes only 055570901
1
Angle- Linkage Units with Inlet Vanes only 055667201
1
Angle- Linkage
Units with Inlet Vanes only 055644301
1
14 Angle- Linkage Units with Inlet Vanes only 055570902
1
Angle- Linkage Units with Inlet Vanes only 055667202
1
Angle- Linkage Units with Inlet Vanes only 055644302
1
15 Motor Mount Assembly 056104501
1
1
1
16 Angle- Motor Mount 055514201
1
1
1
17 Holddown 041272900 1
2
2
18 Angle, Clamping 055576601
1
19 Mount, Bearing
Units with Inlet Vanes only 055570801
2
2
2
21 Key- Fan 4.75” Long X 5/8” Diameter
until 4/00 023221606
2
4/00 & Later 023221617
2
Key- Fan 10.00” Long X 5/8” Diameter 023221613
1
Key- Fan 5.50” Long X 3/4” Diameter 023221702
2
22 Key- Sheave
6.50” Long X 1/2” Diameter 023221610
1
1
Key- Sheave
5.50” Long X 3/4” Diameter 023221702
1
25 Bearing- Ball
2.437” Bore 020648655 12
Bearing- Ball
2.688” Bore 020648658 1 2
Bearing- Ball
2.937” Bore 020648659 1 2
26 Bearing- Sleeve, .752“ Bore
Units with Inlet Vanes only 047138508
2
2
2
27 Bearing- Flange, .505“ Bore
Units with Inlet Vanes only 047138509
4
4
4
1
Note that some units may have been equipped with standard setscrew locking bearings. This locking collar style bearing is the
recommended replacement.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 58
Section F- Supply Air Section
Air Foil- Double Width- VAV Assembly
Code 31= 33V*, 36V*, 40V*
68
65
69
61
66
60
67
Ref.
No.
60
61
65
66
67
68
69
Motor
H.P.
All
All
5- 40
50- 75
10- 40
50- 75
4
5
6
All
10- 40
50- 75
All
All
All
Part
Part Fan Size
Description Number 33” 36”40”
Plate- Adapter 033603300
1
1
1
Shaft- Linkage 055530507
1
Shaft- Linkage 055530506
1
Shaft- Linkage 055530504
1
Shaft- Linkage 055530508
1
Shaft- Linkage 055530505
1
Actuator- 120V ACT1 059999801 11 1 1
Actuator- 120V ACT1 059999802 21 1 1
Actuator- 120V ACT1 059999803 3 11
Crank Arm 032279200
1
Crank Arm 032279200
1
1
Crank Arm 031771800
1
1
Ball Joint- Female 027671100
1
1
1
Ball Joint- Male 034256500
1
1
1
Turnbuckle032851100 1 1 1
Prior to 1/98 the Actuator was p/n 031771701.
Prior to 1/98 the Actuator was p/n 031771702.
3
Prior to 1/98 the Actuator was p/n 031771600.
4
Horsepower range— 33” Fan: 5- 15HP; 36”, 40” Fan: 10, 15 HP.
5
Horsepower range— 33” Fan: 20- 50HP; 36”, 40” Fan: 20- 40 HP.
6
Horsepower range— 36”, 40” Fan: 50- 75 HP.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 59
Section F- Supply Air Section
Air Foil Fan- Single Width- RDT (Draw-Thru/No Heat) Units
Code 31= 44B*, 44W*, 49B*, 49W*
Diagram & Components
21
24
3
25 26
4
23
27
38
1
22 11
15
16
5
17
Ref. Part
Part
Fan Size
No. Description
Number 44” 49”
1 Motor- see table after Fan Mount section
3 Wheel, Fan- Single Inlet/Single Width
Until 6/00
093413720
1
Wheel, Fan- Single Inlet/Single Width
6/00 & Later
110942010
1
Wheel, Fan- Single Inlet/Single Width
Until 6/00
093413572
1
Wheel, Fan- Single Inlet/Single Width
6/00 & Later
110942011
1
4 Fan Vane Control w/Funnel
Code 31= 44W*
Until 6/00
048447007
1
6/00 & Later
110941910
1
Until 6/00065816501 1
6/00 & Later
110941911
1
Inlet Funnel Assembly (no vanes)
Code 31= 44B*
Until 6/00
092045214
1
6/00 & Later
110941810
1
Until 6/00092042515 1
6/00 & Later
110941811
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 60
Section F- Supply Air Section
Air Foil Fan- Single Width- RDT (Draw-Thru/No Heat) Units
Code 31= 44B*, 44W*, 49B*, 49W*
Components, Continued
Ref.
No.
5
11
15
16
17
21
22
23
24
25
26
27
38
1
Part
Part
Fan Size
Description
Number 44” 49”
Screw Adjust Assembly 055528203
2
2
Shaft- 2.438” Diameter 055534702
1
Shaft- 2.188” Diameter 056079802
1
Mount Assembly-Motor 056104501
1
1
Angle -Motor Mount 055514201
1
1
Angle, Clamping 055512701
2
2
Key- Fan, 6.50” Long X 5/8” Diameter 023221610
1
Key- Fan, 6.00” Long X 1/2” Diameter 023221520
2
Key- Fan, 5.50” Long X 5/8” Diameter 023221607
1
Key- Fan, 6.00” Long X 1/2” Diameter 023221520
1
Plate
Until 1/00 055606701
1
1
Tubing- Plastic 021136795
1
Tubing- Plastic 021136798
1
Bearing- Ball, 2.437” Bore 020648655 11
Bearing- Ball, 2.188” Bore 020648654 1 1
Fitting- 1/4” OD X 1/8” MPT
Until 12/04 021213700
1
1
Fitting- 1/4” OD X 1/8” MPT
12/04 & Later 027674000
1
1
Fitting- 1/4” OD X 1/8” FPT
Until 12/04 021213800
1
1
Fitting- 1/4” OD X 1/8” MPT
12/04 & Later 027674100
1
1
Bearing- Ball, 2.437” Bore 020648655 11
Bearing- Roller, 2.188” Bore 049541108
1
Note that some units may have been equipped with standard setscrew locking bearings. This locking collar style
bearing is the recommended replacement.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 61
Section F- Supply Air Section
Air Foil- Single Width- VAV Assembly
Code 31= 44W*, 49W*
44” Fan
67
66
61
65
67
See Detail to Right
49” Fan
69 68
61
66
60
66
65
67
65
67
62
7.5- 40 HP
50- 75 HP
See Detail to Right
Ref. Motor
No. H.P.
60
7.5- 40
61
All
7.5- 40
50- 75
62
50- 75
65
3- 20
25- 60
7.5- 15
20- 40
50- 75
66
All
7.5- 40
50- 75
67
All
All
68
All
69 All
Part
Part
Fan Size
Description Number 44”49”
Mount- Ball Joint
056080101
1
Rod- Damper
028680926
1
Linkage- Shaft
055530509
1
Linkage- Shaft
055530502
1
Support- Motor
056079901
1
Actuator- 120V ACT1 059999801 11
Actuator- 120V ACT1 059999802 21
Actuator- 120V ACT1 059999801 1 1
Actuator- 120V ACT1 059999802 2 1
Actuator- 120V ACT1 059999803 3 1
Crank Arm
032279200
1
Crank Arm
032279200
1
Crank Arm
031771800
1
Ball Joint
000887000
2
Ball Joint
027671100
1
Ball Joint
034256500
1
Turnbuckle 032851100 1
Prior to 1/98 Actuator p/n was 031771701.
Prior to 1/98 Actuator p/n was 031771702.
3
Prior to 1/98 Actuator p/n was 031771600.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 62
Section F- Supply Air Section
Fan Mounts- 33” Forward Curved Fan
Code 31= 33F1, 33F2, 33F3, 33M1, 33M2, 33M3
Until 11/04
Rubber Mounts (Code 31= 33F1, 33M1)
91
92
61
62
63 64
89
90
21
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
5, 7.5
10- 50
62
5- 40
50
63
5, 7.5
10- 25, 50
30, 40
64
All
89
All
90
All
91
All
92
All
1
Part
Description
Channel- Mount Support 1
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Red
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Part
Qty.
Number
0983160014
021639704 1
021639701 1
021639704 1
021639701 1
021639704 1
021639701 1
021639703 1
021639701 1
048878118 8
048164812 8
032333305 12
040499501 8
Prior to 5/02 p/n was 055512101.
161
or
Mount Locations
61
63
or
62
163
or
or
64
162
164
Spring Mounts (Code 31= 33F2, 33F3, 33M2, 33M3)
188
189
121
190
122
123
160
155
161 162
156
163 164
Spring Mounts
Ref. Fan Motor
No.
HP
121
All
122
All
123
All
155
All
156
All
160
All
161
5- 10
15- 50
162
All
163
5
7.5- 25
30- 50
164 5-10, 40, 50
15- 30
188
All
189
All
190
All
N/S
All
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Part
Description
Support Assembly
Screw Adjust Assembly
Channel Assembly
Plate- Gasket Retainer
Support- Spring Locator
Pad- Rubber Vibration
Mount- Spring, Black
Mount- Spring, Red
Mount- Spring, Black
Mount- Spring, Black
Mount- Spring, Red
Mount- Spring, Green
Mount- Spring, Red
Mount- Spring, Black
Nut- 5/8-11
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Screw- Tapping, 1/4-20
Rev. AG 01/15
Part
Qty.
Number
055606901 4
055528201 4
055606801 4
055502101 4
055502201 4
048447901 4
048448502 1
048448503 1
048448502 1
048448502 1
048448503 1
048448504 1
048448503 1
048448502 1
040500002 4
048878118 12
048164812 8
046093809 8
RPL 7000070 / Page 63
Section F- Supply Air Section
Fan Mounts- 33” Forward Curved Fan
Code 31= 33F1, 33F2, 33F3, 33M1, 33M2, 33M3
11/04 & Later
Rubber Mounts (Code 31= 33F1, 33M1)
91
92
61
93
62
63 64
89
21
81
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
5, 7.5
10- 50
62
5- 40
50
63
5, 7.5
10- 25, 50
30, 40
64
All
81
All
89
All
91
All
92
All
93
All
Part
Description
Channel- Mount Support
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Red
Nut
Screw
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Washer- Plain, 1/2”
Part
Qty.
Number
098316001 4
021639704 1
021639701 1
021639704 1
021639701 1
021639704 1
021639701 1
021639703 1
021639701 1
059992201 8
112047201 8
032333305 12
040499501 8
048164812 8
161
or
Mount Locations
61
63
or
163
62
64
or
or
162
164
188
121
189
Seismic strap used only
when Code 31= 33*3.
181
161 162
163 164
Spring Mounts
Spring Mounts (Code 31= 33F2, 33M2) AND
Seismic Spring (Code 31= 33F3, 33M3)
Ref. Fan Motor Part
No.
HP
Description
121
All
Mount
Spring (C31= 33*2)
Seismic (C31= 33*3)
161
5, 7.5
Spring Mount- Purple
10- 30
Spring Mount- Brown
40, 50
Spring Mount- Red
162
All
Spring Mount- Brown
163
5, 7.5
Spring Mount- Brown
10- 30
Spring Mount- Red
40, 50
Spring Mount- Red/Black
164
5- 20
Spring Mount- Red
25- 50
Spring Mount- Red/Black
181
All
Nut
Spring (C31= 33*2)
Seismic (C31= 33*3)
188
All
Nut
189
All
Screw
Spring (C31= 33*2)
Seismic (C31= 33*3)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Part
Number
Qty.
251783201
251783301
251784701
251784801
251785001
251784801
251784801
251784901
251785001
251784901
251785001
4
4
1
1
1
1
1
1
1
1
1
059992201 12
111056301 20
040500002 4
112047201 12
112047201 20
RPL 7000070 / Page 64
Section F- Supply Air Section
Fan Mounts- 36” Forward Curved Fan
Code 31= 36F1, 36F2, 36F3, 36M1, 36M2, 36M3
Until 11/04
161
or
61
163
or
63
Mount Locations
62
64
or
162
164
Rubber Mounts (Code 31= 36F1, 36M1)
91
92
or
61
62
63 64
89
90
21
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
All
62
All
63
10- 25
30- 50
60, 75
64
All
89
All
90
All
91
All
92
All
1
Part
Description
Channel- Mount Support 1
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Gray
Rubber Mount- Red
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Part
Qty.
Number
0983160014
021639701 1
021639701 1
021639701 1
021639703 1
021639705 1
021639701 1
048878118 8
048164812 8
032333305 12
040499501 8
Prior to 5/02 p/n was 055512101.
Spring Mounts (Code 31= 36F2, 36F3, 36M2, 36M3)
188
189
121
190
122
123
160
155
161 162
156
163 164
Spring Mounts
Ref. Fan Motor
No.
HP
121
All
122
All
123
All
155
All
156
All
160
All
161
10
15- 75
162
10
15- 75
163
10- 20
25- 75
164
All
188
All
189
All
190
All
N/S
All
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Part
Description
Support Assembly
Screw Adjust Assembly
Channel Assembly
Plate- Gasket Retainer
Support- Spring Locator
Pad- Rubber Vibration
Mount- Spring, Black
Mount- Spring, Red
Mount- Spring, Red
Mount- Spring, Black
Mount- Spring, Red
Mount- Spring, Green
Mount- Spring, Red
Nut- 5/8-11
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Screw- Tapping, 1/4-20
Rev. AG 01/15
Part
Qty.
Number
055606901 4
055528201 4
055606801 4
055502101 4
055502201 4
048447901 4
048448502 1
048448503 1
048448503 1
048448502 1
048448503 1
048448504 1
048448503 1
040500002 4
048878118 12
048164812 8
046093809 8
RPL 7000070 / Page 65
Section F- Supply Air Section
Fan Mounts- 36” Forward Curved Fan
Code 31= 36F1, 36F2, 36F3, 36M1, 36M2, 36M3
11/04 & Later
161
or
61
163
or
63
Mount Locations
62
64
or
162
164
Rubber Mounts (Code 31= 36F1, 36M1)
91
92
61
93
62
63 64
89
21
81
or
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
All
62
All
63
10- 25
30- 50
60, 75
64
All
81
All
89
All
91
All
92
All
93
All
Part
Description
Channel- Mount Support
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Gray
Rubber Mount- Red
Nut
Screw
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Washer- Plain, 1/2”
Part
Qty.
Number
098316001 4
021639701 1
021639701 1
021639701 1
021639703 1
021639705 1
021639701 1
059992201 8
112047201 8
032333305 12
040499501 8
048164812 8
Spring Mounts (Code 31= 36F2, 36M2) AND
Seismic Spring (Code 31= 36F3, 36M3)
188
121
189
Seismic strap used only
when Code 31= 36*3.
181
161 162
163 164
Spring Mounts
Ref. Fan Motor Part
No.
HP
Description
121
All
Mount
Spring (C31= 36*2)
Seismic (C31= 36*3)
161
10- 20
Spring Mount- Brown
25- 50
Spring Mount- Red
60, 75
Spring Mount- Red
162
All
Spring Mount- Brown
163
10- 20
Spring Mount- Red
25- 50
Spring Mount- Red/Black
60, 75
Spring Mount- Red/Green
164
10
Spring Mount- Red
15- 75
Spring Mount- Red/Black
181
All
Nut
Spring (C31= 36*2)
Seismic (C31= 36*3)
188
All
Nut
189
All
Screw
Spring (C31= 36*2)
Seismic (C31= 36*3)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Part
Number
Qty.
251783201
251783301
251784801
251784901
251785001
251784801
251784901
251785001
251785001
251784901
251785001
4
4
1
1
1
1
1
1
1
1
1
059992201 12
111056301 20
040500002 4
112047201 12
112047201 20
RPL 7000070 / Page 66
Section F- Supply Air Section
Fan Mounts- 40” Forward Curved Fan
Code 31= 40F1, 40F2, 40F3, 40M1, 40M2, 40M3
Until 11/04
161
or
61
163
or
63
Mount Locations
62
64
or
162
164
Rubber Mounts (Code 31= 40F1, 40M1)
91
92
or
61
62
63 64
89
90
21
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
All
62
All
63
10- 25
30- 50
60, 75
64
All
89
All
90
All
91
All
92
All
1
Part
Description
Channel- Mount Support 1
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Gray
Rubber Mount- Red
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Part
Qty.
Number
0983160014
021639701 1
021639701 1
021639701 1
021639703 1
021639705 1
021639701 1
048878118 8
048164812 8
032333305 12
040499501 8
Prior to 5/02 p/n was 055512101.
Spring Mounts (Code 31= 40F2, 40F3, 40M2, 40M3)
188
189
121
190
122
123
160
155
161 162
156
163 164
Spring Mounts
Ref. Fan Motor
No.
HP
121
All
122
All
123
All
155
All
156
All
160
All
161
All
162
10- 25
30- 75
163
10- 20
25- 75
164
All
188
All
189
All
190
All
N/S
All
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Part
Description
Support Assembly
Screw Adjust Assembly
Channel Assembly
Plate- Gasket Retainer
Support- Spring Locator
Pad- Rubber Vibration
Mount- Spring, Red
Mount- Spring, Red
Mount- Spring, Black
Mount- Spring, Red
Mount- Spring, Green
Mount- Spring, Red
Nut- 5/8-11
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Screw- Tapping, 1/4-20
Rev. AG 01/15
Part
Qty.
Number
055606901
4
055528201
4
055606801
4
055502101
4
055502201
4
048447901
4
048448503
1
048448503
1
048448502
1
048448503
1
048448504
1
048448503
1
040500002
4
048878118 12
048164812
8
046093809
8
RPL 7000070 / Page 67
Section F- Supply Air Section
Fan Mounts- 40” Forward Curved Fan
Code 31= 40F1, 40F2, 40F3, 40M1, 40M2, 40M3
11/04 & Later
161
or
61
163
or
63
Mount Locations
62
64
or
162
164
Rubber Mounts (Code 31= 40F1, 40M1)
91
92
61
93
62
63 64
89
21
81
or
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
All
62
All
63
10- 25
30- 50
60, 75
64
All
81
All
89
All
91
All
92
All
93
All
Part
Description
Channel- Mount Support
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Gray
Rubber Mount- Red
Nut
Screw
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Washer- Plain, 1/2”
Part
Qty.
Number
098316001 4
021639701 1
021639701 1
021639701 1
021639703 1
021639705 1
021639701 1
059992201 8
112047201 8
032333305 12
040499501 8
048164812 8
Spring Mounts (Code 31= 40F2, 40M2) AND
Seismic Spring (Code 31= 40F3, 40M3)
188
121
189
Seismic strap used only
when Code 31= 40*3.
181
161 162
163 164
Spring Mounts
Ref. Fan Motor Part
No.
HP
Description
121
All
Mount
Spring (C31= 40*2)
Seismic (C31= 40*3)
161
10, 15
Spring Mount- Brown
20- 50
Spring Mount- Red
60, 75
Spring Mount- Red
162
10- 20
Spring Mount- Red
25- 75
Spring Mount- Brown
163
10, 15
Spring Mount- Red
20- 50
Spring Mount- Red/Black
60, 75
Spring Mount- Red/Green
164
All
Spring Mount- Red/Black
181
All
Nut
Spring (C31= 40*2)
Seismic (C31= 40*3)
188
All
Nut
189
All
Screw
Spring (C31= 40*2)
Seismic (C31= 40*3)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Part
Number
Qty.
251783201
251783301
251784801
251784901
251785001
251784901
251784801
251784901
251785001
251785001
251785001
4
4
1
1
1
1
1
1
1
1
1
059992201 12
111056301 20
040500002 4
112047201 12
112047201 20
RPL 7000070 / Page 68
Section F- Supply Air Section
Fan Mounts- 33” Airfoil Double Width Fan
Code 31= 33A1, 33A2, 33A3, 33V1, 33V2, 33V3
Until 11/04
161
163
or
or
61
Mount Locations
63
62
64
162
164
Rubber Mounts (Code 31= 33A1, 33V1)
91
92
or
or
61
62
63 64
89
90
21
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
5, 7.5
10- 50
62
All
63
5- 25
30- 50
64
5- 25
30- 50
89
All
90
All
91
All
92
All
1
Part
Description
Channel- Mount Support 1
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Black
Rubber Mount- Red
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Part
Qty.
Number
0983160014
021639704 1
021639701 1
021639704 1
021639701 1
021639703 1
021639704 1
021639701 1
048878118 8
048164812 8
032333305 12
040499501 8
Prior to 5/02 p/n was 055512101.
Spring Mounts (Code 31= 33A2, 33A3, 33V2, 33V3)
188
189
121
190
122
123
160
155
161 162
156
163 164
Spring Mounts
Ref. Fan Motor
No.
HP
121
All
122
All
123
All
155
All
156
All
160
All
161
5- 10
15, 20, 40, 50
25, 30
162
All
163
5
7.5- 20
25- 50
164
All
188
All
189
All
190
All
N/S
All
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Part
Description
Support Assembly
Screw Adjust Assembly
Channel Assembly
Plate- Gasket Retainer
Support- Spring Locator
Pad- Rubber Vibration
Mount- Spring, Black
Mount- Spring, Red
Mount- Spring, Green
Mount- Spring, Black
Mount- Spring, Black
Mount- Spring, Red
Mount- Spring, Green
Mount- Spring, Black
Nut- 5/8-11
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Screw- Tapping, 1/4-20
Rev. AG 01/15
Part
Qty.
Number
055606901 4
055528201 4
055606801 4
055502101 4
055502201 4
048447901 4
048448502 1
048448503 1
048448504 1
048448502 1
048448502 1
048448503 1
048448504 1
048448502 1
040500002 4
048878118 12
048164812 8
046093809 8
RPL 7000070 / Page 69
Section F- Supply Air Section
Fan Mounts- 33” Airfoil Double Width Fan
Code 31= 33A1, 33A2, 33A3, 33V1, 33V2, 33V3
11/04 & Later
161
or
61
163
or
63
Mount Locations
62
64
162
164
Rubber Mounts (Code 31= 33A1, 33V1)
91
92
61
93
62
63 64
89
21
81
or
or
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
5, 7.5
10- 50
62
All
63
5- 25
30- 50
64
5- 25
30- 50
81
All
89
All
91
All
92
All
93
All
Part
Description
Channel- Mount Support
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Black
Rubber Mount- Red
Nut
Screw
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Washer- Plain, 1/2”
Part
Qty.
Number
098316001 4
021639704 1
021639701 1
021639704 1
021639701 1
021639703 1
021639704 1
021639701 1
059992201 8
112047201 8
032333305 12
040499501 8
048164812 8
Spring Mounts (Code 31= 33A2, 33V2) AND
Seismic Spring (Code 31= 33A3, 33V3)
188
121
189
Seismic strap used only
when Code 31= 33*3.
181
161 162
163 164
Spring Mounts
Ref. Fan Motor Part
No.
HP
Description
121
All
Mount
Spring (C31= 33*2)
Seismic (C31= 33*3)
161
5 , 7.5
Spring Mount- Purple
10- 30
Spring Mount- Brown
40, 50
Spring Mount- Red
162
All
Spring Mount- Brown
163
5, 7.5
Spring Mount- Brown
10- 30
Spring Mount- Red
40, 50
Spring Mount- Red/Black
164
All
Spring Mount- Red
181
All
Nut
Spring (C31= 33*2)
Seismic (C31= 33*3)
188
All
Nut
189
All
Screw
Spring (C31= 33*2)
Seismic (C31= 33*3)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Part
Number
Qty.
251783201
251783301
251784701
251784801
251784901
251784801
251784801
251784901
251785001
251784901
4
4
1
1
1
1
1
1
1
1
059992201 12
111056301 20
040500002 4
112047201 12
112047201 20
RPL 7000070 / Page 70
Section F- Supply Air Section
Fan Mounts- 36” Airfoil Double Width Fan
Code 31= 36A1, 36A2, 36A3, 36V1, 36V2, 36V3
Until 11/04
161
163
or
or
61
Mount Locations
63
62
64
162
164
Rubber Mounts (Code 31= 36A1, 36V1)
91
92
or
or
61
62
63 64
89
90
21
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
All
62 10, 30- 50
20, 60, 75
63
10- 25
30- 50
60, 75
64
All
89
All
90
All
91
All
92
All
1
Part
Description
Channel- Mount Support 1
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Gray
Rubber Mount- Red
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Part
Qty.
Number
0983160014
021639701 1
021639701 1
021639704 1
021639701 1
021639703 1
021639705 1
021639701 1
048878118 8
048164812 8
032333305 12
040499501 8
Prior to 5/02 p/n was 055512101.
Spring Mounts (Code 31= 36A2, 36A3, 36V2, 36V3)
188
189
121
190
122
123
160
155
161 162
156
163 164
Spring Mounts
Ref. Fan Motor
No.
HP
121
All
122
All
123
All
155
All
156
All
160
All
161
10- 60
75
162
10
15- 60
75
163
10- 20
25- 75
164
All
188
All
189
All
190
All
N/S
All
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Part
Description
Support Assembly
Screw Adjust Assembly
Channel Assembly
Plate- Gasket Retainer
Support- Spring Locator
Pad- Rubber Vibration
Mount- Spring, Red
Mount- Spring, Green
Mount- Spring, Red
Mount- Spring, Black
Mount- Spring, Blue
Mount- Spring, Red
Mount- Spring, Green
Mount- Spring, Red
Nut- 5/8-11
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Screw- Tapping, 1/4-20
Rev. AG 01/15
Part
Qty.
Number
055606901 4
055528201 4
055606801 4
055502101 4
055502201 4
048447901 4
048448503 1
048448504 1
048448503 1
048448502 1
048448501 1
048448503 1
048448504 1
048448503 1
040500002 4
048878118 12
048164812 8
046093809 8
RPL 7000070 / Page 71
Section F- Supply Air Section
Fan Mounts- 36” Airfoil Double Width Fan
Code 31= 36A1, 36A2, 36A3, 36V1, 36V2, 36V3
11/04 & Later
Rubber Mounts (Code 31= 36A1, 36V1)
91
92
61
93
62
63 64
89
21
81
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
All
62 10, 30- 50
20, 60, 75
63
10- 25
30- 50
60, 75
64
All
81
All
89
All
91
All
92
All
93
All
Part
Description
Channel- Mount Support
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Gray
Rubber Mount- Red
Nut
Screw
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Washer- Plain, 1/2”
Part
Qty.
Number
098316001 4
021639701 1
021639701 1
021639704 1
021639701 1
021639703 1
021639705 1
021639701 1
059992201 8
112047201 8
032333305 12
040499501 8
048164812 8
161
or
Mount Locations
61
63
or
62
163
64
or
or
162
164
188
121
189
Seismic strap used only
when Code 31= 36*3.
181
161 162
163 164
Spring Mounts
Spring Mounts (Code 31= 36A2, 36V2) AND
Seismic Spring (Code 31= 36A3, 36V3)
Ref. Fan Motor Part
No.
HP
Description
121
All
Mount
Spring (C31= 36*2)
Seismic (C31= 36*3)
161
10, 15
Spring Mount- Brown
20- 50
Spring Mount- Red
60, 75
Spring Mount- Red/Black
162
All
Spring Mount- Brown
163
10, 15
Spring Mount- Red
20- 50
Spring Mount- Red/Black
60, 75
Spring Mount- Red/Green
164
10- 20
Spring Mount- Red
25- 75
Spring Mount- Red/Black
181
All
Nut
Spring (C31= 36*2)
Seismic (C31= 36*3)
188
All
Nut
189
All
Screw
Spring (C31= 36*2)
Seismic (C31= 36*3)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Part
Number
Qty.
251783201
251783301
251784801
251784901
251785001
251784801
251784901
251785001
251785101
251784901
251785001
4
4
1
1
1
1
1
1
1
1
1
059992201 12
111056301 20
040500002 4
112047201 12
112047201 20
RPL 7000070 / Page 72
Section F- Supply Air Section
Fan Mounts- 40” Airfoil Double Width Fan
Code 31= 40A1, 40A2, 40A3, 40V1, 40V2, 40V3
Until 11/04
161
163
or
or
61
Mount Locations
63
62
64
162
164
Rubber Mounts (Code 31= 40A1, 40V1)
91
92
or
or
61
62
63 64
89
90
21
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
10- 50
60, 75
62
10- 30
40- 75
63
10, 15
20- 50
60, 75
64
All
89
All
90
All
91
All
92
All
1
Part
Description
Channel- Mount Support 1
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Gray
Rubber Mount- Red
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Part
Qty.
Number
0983160014
021639701 1
021639703 1
021639701 1
021639704 1
021639701 1
021639703 1
021639705 1
021639701 1
048878118 8
048164812 8
032333305 12
040499501 8
Prior to 5/02 p/n was 055512101.
Spring Mounts (Code 31= 40A2, 40A3, 40V2, 40V3)
188
189
121
190
122
123
160
155
161 162
156
163 164
Spring Mounts
Ref. Fan Motor
No.
HP
121
All
122
All
123
All
155
All
156
All
160
All
161
10- 50
60, 75
162
All
163
10, 15
20- 75
164
All
188
All
189
All
190
All
N/S
All
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Part
Description
Support Assembly
Screw Adjust Assembly
Channel Assembly
Plate- Gasket Retainer
Support- Spring Locator
Pad- Rubber Vibration
Mount- Spring, Red
Mount- Spring, Green
Mount- Spring, Black
Mount- Spring, Red
Mount- Spring, Green
Mount- Spring, Red
Nut- 5/8-11
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Screw- Tapping, 1/4-20
Rev. AG 01/15
Part
Qty.
Number
055606901 4
055528201 4
055606801 4
055502101 4
055502201 4
048447901 4
048448503 1
048448504 1
048448502 1
048448503 1
048448504 1
048448503 1
040500002 4
048878118 12
048164812 8
046093809 8
RPL 7000070 / Page 73
Section F- Supply Air Section
Fan Mounts- 40” Airfoil Double Width Fan
Code 31= 40A1, 40A2, 40A3, 40V1, 40V2, 40V3
11/04 & Later
Rubber Mounts (Code 31= 40A1, 40V1)
91
92
61
93
62
63 64
89
21
81
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
10- 50
60, 75
62
10- 30
40- 75
63
10, 15
20- 50
60, 75
64
All
81
All
89
All
91
All
92
All
93
All
Part
Description
Channel- Mount Support
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Gray
Rubber Mount- Red
Nut
Screw
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Washer- Plain, 1/2”
Part
Qty.
Number
098316001 4
021639701 1
021639703 1
021639701 1
021639704 1
021639701 1
021639703 1
021639705 1
021639701 1
059992201 8
112047201 8
032333305 12
040499501 8
048164812 8
161
or
Mount Locations
61
63
or
163
62
64
or
or
162
164
188
121
189
Seismic strap used only
when Code 31= 40*3.
181
161 162
163 164
Spring Mounts
Spring Mounts (Code 31= 40A2, 40V2) AND
Seismic Spring (Code 31= 40A3, 40V3)
Ref. Fan Motor Part
No.
HP
Description
121
All
Mount
Spring (C31= 40*2)
Seismic (C31= 40*3)
161
10
Spring Mount- Brown
15- 30
Spring Mount- Red
40- 75
Spring Mount- Red/Black
162
All
Spring Mount- Brown
163
10
Spring Mount- Red
15- 30
Spring Mount- Red/Black
40- 75
Spring Mount- Red/Green
164
10- 20
Spring Mount- Red
25- 75
Spring Mount- Red/Black
181
All
Nut
Spring (C31= 40*2)
Seismic (C31= 40*3)
188
All
Nut
189
All
Screw
Spring (C31= 40*2)
Seismic (C31= 40*3)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Part
Number
Qty.
251783201
251783301
251784801
251784901
251785001
251784801
251784901
251785001
251785101
251784901
251785001
4
4
1
1
1
1
1
1
1
1
1
059992201 12
111056301 20
040500002 4
112047201 12
112047201 20
RPL 7000070 / Page 74
Section F- Supply Air Section
Fan Mounts- 44” AFSW- RDT Units
Code 31= 44B1, 44B2, 44B3, 44W1, 44W2, 44W3
Until 11/04
Mount Locations
62
161
or
61
163
or
63
162
64
or
164
Rubber Mounts (Code 31= 44B1, 44W1)
91
92
or
61
62
63 64
89
90
21
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
7.5- 25
30- 60
62
All
63
7.5, 10
15- 50
60
64
All
89
All
90
All
91
All
92
All
1
Part
Description
Channel- Mount Support 1
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Red
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Part
Qty.
Number
0983160014
021639704 1
021639701 1
021639701 1
021639704 1
021639701 1
021639703 1
021639701 1
048878118 8
048164812 8
032333305 12
040499501 8
Prior to 5/02 p/n was 055512101.
Spring Mounts (Code 31= 44B2, 44B3, 44W2, 44W3)
188
189
121
190
122
123
160
155
161 162
156
163 164
Spring Mounts
Ref. Fan Motor
No.
HP
121
All
122
All
123
All
155
All
156
All
160
All
161
7.5- 40
50, 60
162
7.5- 30
40- 60
163
7.5- 20
25- 50
60
164
All
188
All
189
All
190
All
N/S
All
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Part
Description
Support Assembly
Screw Adjust Assembly
Channel Assembly
Plate- Gasket Retainer
Support- Spring Locator
Pad- Rubber Vibration
Mount- Spring, Black
Mount- Spring, Red
Mount- Spring, Red
Mount- Spring, Black
Mount- Spring, Black
Mount- Spring, Red
Mount- Spring, Green
Mount- Spring, Red
Nut- 5/8-11
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Screw- Tapping, 1/4-20
Rev. AG 01/15
Part
Qty.
Number
055606901 4
055528201 4
055606801 4
055502101 4
055502201 4
048447901 4
048448502 1
048448503 1
048448503 1
048448502 1
048448502 1
048448503 1
048448504 1
048448503 1
040500002 4
048878118 12
048164812 8
046093809 8
RPL 7000070 / Page 75
Section F- Supply Air Section
Fan Mounts- 44” AFSW- Draw-Thru/No Heat Units
Code 31= 44B1, 44B2, 44B3, 44W1, 44W2, 44W3
11/04 & Later
Mount Locations
62
161
or
61
163
or
63
162
64
or
164
Rubber Mounts (Code 31= 44B1, 44W1)
91
92
61
93
62
63 64
89
21
81
or
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
7.5- 25
30- 60
62
All
63
7.5, 10
15- 50
60
64
All
81
All
89
All
91
All
92
All
93
All
Part
Description
Channel- Mount Support
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Black
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Red
Nut
Screw
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Washer- Plain, 1/2”
Part
Qty.
Number
098316001 4
021639704 1
021639701 1
021639701 1
021639704 1
021639701 1
021639703 1
021639701 1
059992201 8
112047201 8
032333305 12
040499501 8
048164812 8
Spring Mounts (Code 31= 44B2, 44W2) AND
Seismic Spring (Code 31= 44B3, 44W3)
188
121
189
Seismic strap used only
when Code 31= 44*3.
181
161 162
163 164
Spring Mounts
Ref. Fan Motor Part
No.
HP
Description
121
All
Mount
Spring (C31= 44*2)
Seismic (C31= 44*3)
161
7.5- 20
Spring Mount- Purple
25- 50
Spring Mount- Brown
60
Spring Mount- Red
162
All
Spring Mount- Brown
163
7.5- 25
Spring Mount- Brown
30- 50
Spring Mount- Red
60
Spring Mount- Red/Black
164
All
Spring Mount- Red
181
All
Nut
Spring (C31= 44*2)
Seismic (C31= 44*3)
188
All
Nut
189
All
Screw
Spring (C31= 44*2)
Seismic (C31= 44*3)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Part
Number
Qty.
251783201
251783301
251784701
251784801
251784901
251784801
251784801
251784901
251785001
251784901
4
4
1
1
1
1
1
1
1
1
059992201 12
111056301 20
040500002 4
112047201 12
112047201 20
RPL 7000070 / Page 76
Section F- Supply Air Section
Fan Mounts- 49” AFSW- RDT Units
Code 31= 49B1, 49B2, 49B3, 49W1, 49W2, 49W3
Until 11/04
Mount Locations
62
161
or
61
163
or
63
91
92
or
162
64
or
164
Rubber Mounts (Code 31= 49B1, 49W1)
61
62
63 64
89
90
21
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
All
62
All
63
7.5- 30
40- 75
64
7.5- 30
40- 75
89
All
90
All
91
All
92
All
1
Part
Description
Channel- Mount Support 1
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Red
Rubber Mount- Green
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Part
Qty.
Number
0983160014
021639701 1
021639701 1
021639701 1
021639703 1
021639701 1
021639703 1
048878118 8
048164812 8
032333305 12
040499501 8
Prior to 5/02 p/n was 055512101.
Spring Mounts (Code 31= 49B2, 49B3, 49W2, 49W3)
188
189
121
190
122
123
160
155
161 162
156
163 164
Spring Mounts
Ref. Fan Motor
No.
HP
121
All
122
All
123
All
155
All
156
All
160
All
161
7.5- 60
75
162
All
163
7.5- 30
40- 75
164
7.5
10- 75
188
All
189
All
190
All
N/S
All
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Part
Description
Support Assembly
Screw Adjust Assembly
Channel Assembly
Plate- Gasket Retainer
Support- Spring Locator
Pad- Rubber Vibration
Mount- Spring, Red
Mount- Spring, Green
Mount- Spring, Red
Mount- Spring, Red
Mount- Spring, Green
Mount- Spring, Red
Mount- Spring, Green
Nut- 5/8-11
Screw- Cap, 3/8-16 X 1”
Washer- Lock, 3/8”
Screw- Tapping, 1/4-20
Rev. AG 01/15
Part
Qty.
Number
055606901 4
055528201 4
055606801 4
055502101 4
055502201 4
048447901 4
048448503 1
048448504 1
048448503 1
048448503 1
048448504 1
048448503 1
048448504 1
040500002 4
048878118 12
048164812 8
046093809 8
RPL 7000070 / Page 77
Section F- Supply Air Section
Fan Mounts- 49” AFSW- RDT Units
Code 31= 49B1, 49B2, 49B3, 49W1, 49W2, 49W3
11/04 & Later
62
161
or
61
163
or
63
162
64
or
164
Rubber Mounts (Code 31= 49B1, 49W1)
91
92
61
93
62
63 64
89
21
81
or
91
Rubber Mounts
Ref. Fan Motor
No.
HP
21
All
61
All
62
All
63
7.5- 30
40- 75
64
7.5- 30
40- 75
81
All
89
All
91
All
92
All
93
All
Part
Description
Channel- Mount Support
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Red
Rubber Mount- Green
Rubber Mount- Red
Rubber Mount- Green
Nut
Screw
Nut- 1/2-13
Screw- Cap, 1/2-13 X 1”
Washer- Plain, 1/2”
Part
Qty.
Number
098316001 4
021639701 1
021639701 1
021639701 1
021639703 1
021639701 1
021639703 1
059992201 8
112047201 8
032333305 12
040499501 8
048164812 8
Spring Mounts (Code 31= 49B2, 49W2) AND
Seismic Spring (Code 31= 49B3, 49W3)
188
121
189
Seismic strap used only
when Code 31= 49*3.
181
161 162
163 164
Spring Mounts
Ref. Fan Motor Part
No.
HP
Description
121
All
Mount
Spring (C31= 49*2)
Seismic (C31= 49*3)
161
7.5- 30
Spring Mount- Red
40, 50
Spring Mount- Red/Black
60, 75
Spring Mount- Red/Green
162
All
Spring Mount- Red/Black
163
7.5- 20
Spring Mount- Red
25- 75
Spring Mount- Red/Black
164
All
Spring Mount- Red/Black
181
All
Nut
Spring (C31= 49*2)
Seismic (C31= 49*3)
188
All
Nut
189
All
Screw
Spring (C31= 49*2)
Seismic (C31= 49*3)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Part
Number
Qty.
251783201
251783301
251784901
251785001
251785101
251785001
251784901
251785001
251785001
4
4
1
1
1
1
1
1
1
059992201 12
111056301 20
040500002 4
112047201 12
112047201 20
RPL 7000070 / Page 78
Section F- Supply Air Section
Supply Air Fan Motors 1
H.P. Motor HP
C32=
5
J*Y
7.5
K*Y
10
L*Y
15
M*Y
20
N*Y
25
P*Y
30
Q*Y
40
R*Y
50
S*Y
60
T*Y
75
U*Y
5
J*Y
7.5
K*Y
10
L*Y
15
M*Y
20
N*Y
25
P*Y
30
Q*Y
40
R*Y
50
S*Y
60
T*Y
75
U*Y
5
J*Y
7.5
K*Y
10
L*Y
15
M*Y
20
N*Y
25
P*Y
30
Q*Y
40
R*Y
50
S*Y
60
T*Y
75
U*Y
5
J*Y
7.5
K*Y
10
L*Y
15
M*Y
20
N*Y
25
P*Y
30
Q*Y
40
R*Y
50
S*Y
60
T*Y
75
U*Y
Unit
Voltage
C09= 12
208/60/3
208/60/3
208/60/3
208/60/3
208/60/3
208/60/3
208/60/3
208/60/3
208/60/3
208/60/3
208/60/3
C09= 29
230/60/3
230/60/3
230/60/3
230/60/3
230/60/3
230/60/3
230/60/3
230/60/3
230/60/3
230/60/3
230/60/3
C09= 27
460/60/3
460/60/3
460/60/3
460/60/3
460/60/3
460/60/3
460/60/3
460/60/3
460/60/3
460/60/3
460/60/3
C09= 37
575/60/3
575/60/3
575/60/3
575/60/3
575/60/3
575/60/3
575/60/3
575/60/3
575/60/3
575/60/3
575/60/3
ODP HiEff ODP PrEff. TEFC HiEff
C32= *EY C32= *JY C32= *HY
TEFC PrEff
C32= *KY
039447600065817200049186800
037530300065817300047665900
038999000065817400047666100
039896200065817500049186900
039895800065817600049187000
039448900065817700049187100
041775200205066500049187200
041775300205067100049187300
041775400205067500049187400
041775800205067700049187500
041775700205069100049187600
065819500
065819600
065819700
065819800
065819900
065820000
205066800
205070700
205091600
039442500065818200040161200
039448700065818300049100500
039446500065818400044691100
039446600065818500038689700
039448800065818600040161300
039896100065818700040161400
040626800205066600049025300
041770000205067200048448000
039899200205067600040161600
041775500065819100046748300
041775600205070300049187800
065820200
065820300
065820400
065820500
065820600
065820700
205066900
205069200
205069400
039442500065818200040161200
039448700065818300049100500
039446500065818400044691100
039446600065818500038689700
039448800065818600040161300
039896100065818700040161400
040626800205066600049025300
041770000205067200048448000
039899200205067600040161600
041775500065819100046748300
041775600205070300049187800
065820200
065820300
065820400
065820500
065820600
065820700
205066900
205069200
205069400
205069600
205069900
046741900205168900049188400
047443300205168800049188500
047443400205168600049188600
047443500205166600049185200
049181100205166800049188700
049181200205166900049188800
049181300205066700049188900
049181400205067300049189000
049181500205091800049189100
049181600205069000049189200
049181800205070400049189300
046514600
046514700
065821400
065821500
065821600
065821700
205067000
205069300
205069500
205069800
205070000
2
2
2
2
All motors listed are Across-The-Line start (Code 10= AL, PW). There are a small number of units that have Part-Winding start motors (Code
10= PP, PS). These units have motors 15HP and greater and are 208V or 230V only. Contact Daikin Applied if a PW replacement motor is
needed. Note that Standard Efficiency Motors (Code 22= *AY, *GY) are no longer available. Use High (HiEff.) or Premium Efficency (PrEff.)
instead.
2
60 AND 75 HP motors are not available in 208/230V (Code 09= 12, 29).
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 79
Section F- Supply Air Section
Belt Guard
Code 49= A, C, D, F
Air Foil Double Width (AFDW) OR Forward Curved Fans (FCLP, FCMP)
Ref.
No.
40
41
40
41
Air Foil Single Width (AFSW) with
Side Discharge (Code 40= HY),
Main Control Box (Code 08= S, F)
The Main Control Box is mounted in this section on RDT
units (the supply air section is mounted directly to the
condenser section).
Part
Description
Grille Assembly
Grille Assembly
Grille Assembly
Belt Guard Assembly
Belt Guard Assembly
Belt Guard Assembly
PartFan Size
Number 33”36”40”
055606004 1
055606005 1
055606006 1
055606014 1
055606015 1
055606016 1
Air Foil Single Width (AFSW) with
Side Discharge (Code 40= SY),
No Control Box (Code 08= P, D)
RPS units (Main Control Box is mounted in the
Discharge Plenum Section K).
82
81
81
80
80
Air Foil Single Width (AFSW) with
Bottom Discharge (Code 40= G*),
Main Control Box (Code 08= S, F)
The Main Control Box is mounted in this section on RDT
units (the supply air section is mounted directly to the condenser section).
Air Foil Single Width (AFSW) with
Bottom Discharge (Code 40= B*),
No Control Box (Code 08= P, D)
RPS units (Main Control Box is mounted in the
Discharge Plenum Section K).
83
83
82
81
81
80
80
Ref. Part
No. Description
80 Grille Assy
Grille Assy
81 Grille Assy
Grille Assy
82 Grille Assy
83 Grille Assy
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Part
Fan Size
Number 44” 49”
056259211 1
056259221
1
056259212 1
056259222
1
056259213 1
1
056259214 1
1
Rev. AG 01/15
RPL 7000070 / Page 80
Section F- Supply Air Section
Inverters & Inverter Bypass Control Box
Until 3/05 (Code 08= P) 3
Motor HP 5- 25 (Code 22 OR Code 32= J*Y, K*Y L*Y, M*Y, N*Y, P*Y)
Inverters may be located in a separate section (Code 14= 1, 2, 4, only Inverters WITH bypass may be installed in a separate section), or the Supply
Air Section (Code 14= 3, 5, 6, 7, 8, 9). The inverter and bypass controls are the same regardless of the installation location, although the sheet
metal components differ. The diagrams shown below apply to either a Return Air or Supply Air Inverter (both may be installed if Code 14= 5). Even
if Code 14= 8, 9— where only a Return Air Fan Inverter is called for— The inverter and bypass controls are still installed in the Supply Air Section.
3
If the unit was built between 10/04- 3/05 Contact Daikin Applied to confirm installed components.
40
M30A/M30B (Supply)
M40A/M40B (Return)
PB10 (Supply)
PB20 (Return) OR
60
M10 (Supply)
M20 (Return)
40
62
Supply Air AND Return Air
Fan Inverter without Bypass.
(Code 14= 7)
50
OL10 (Supply)
OL20 (Return)
61A 61
40
Bypass Controls
Detail
Supply OR Return Air Fan
Inverter w/ Bypass Control Box.
(Code 14= 3, 5, 8)
Supply Air OR Return Air
Fan Inverter without Bypass.
(Code 14= 6, 7, 9)
1
2
575V
460V
230V
208V
575V
460V
230V
208V
575V
460V
230V
208V
575V
460V
230V
208V
575V
460V
230V
208V
Motor Horsepower
5
7.5, 10
15
20
25
Ref Sch. Part
Part
No.Sym. Description Number
40 AFD10, 20Inverter
see Inverter section
50
Gasket
055940207 11111 11111 1111111111
60M30ABContactor
066814301 1111 11
M40AB
066814303111
11
1
0668143041
11
1
0668143051
06681430611
066814307
1
1
61 OL10, 20Overload
1
61A
Heater- OL
62 PB10, 20Power Block 030372715 11111 11111 1111111111
2
M10, 20 Contactor
For part numbers for OL10, OL20 and associated Heater see “Section N- Main Control Box Power Panel Until 3/05”.
The Inverter Bypass Box originally had a Contactor (M10 and/or M20) installed. This was replaced with a Power Block. If a Contactor
is needed see “Section N- Main Control Box Power Panel Until 3/05” for part number(s).
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 81
Section F- Supply Air Section
Inverters & Inverter Bypass Control Box
Until 3/05 (Code 08= P) 3
Motor HP 30- 75 (Code 22= Q*Y, R*Y, S*Y, T*Y OR Code 32= Q*Y, R*Y, S*Y, T*Y, U*Y)
Inverters may be located in a separate section (Code 14= 1, 2, 4, only Inverters WITH bypass may be installed in a separate
section), or the Supply Air Section (Code 14= 3, 5, 6, 7, 8, 9). The inverter and bypass controls are the same regardless of the
installation location, although the sheet metal components differ. The diagrams shown below apply to either a Return Air or
Supply Air Inverter (both may be installed if Code 14= 5). Even if Code 14= 8, 9— where only a Return Air Fan Inverter is called
for— The inverter and bypass controls are still installed in the Supply Air Section.
3
If the unit was built between 10/04- 3/05 Contact Daikin Applied to confirm installed components.
40
M30A/M30B (Supply)
M40A/M40B (Return)
PB10 (Supply)
M10 (Supply)
PB20 (Return) OR M20 (Return)
60
40
62
Supply Air AND Return Air
Fan Inverter without Bypass.
(Code 14= 7)
50
OL10 (Supply)
OL20 (Return)
61A 61
Supply Air OR Return Air Fan
Inverter w/ Bypass Control Box.
(Code 14= 3, 5, 8)
40
Bypass Controls
Detail
Supply Air OR Return Air
Fan Inverter without Bypass.
(Code 14= 6, 7, 9)
1
2
575V
460V
575V
460V
575V
460V
230V
208V
575V
460V
230V
208V
575V
460V
230V
208V
Motor Horsepower
304050
60
75
Ref Sch. Part
Part
No.Sym.Description Number
40AFD10, 20Inverter
see Inverter section
50
Gasket
055940207 11 111 11111
60 M30AB Contactor
066814304 1 1
M40AB
066814306 11
066814307111
066814308 111
111
1
61 OL10, 20Overload
1
61A
Heater- OL
62 PB10,20 Power Block 030372715 11 111 11111 1 111
2
M10, 20 Contactor
For part numbers for OL10, OL20 and associated Heater see “Section N- Main Control Box Power Panel Until 3/05”.
The Inverter Bypass Box originally had a Contactor (M10 and/or M20) installed. This was replaced with a Power
Block. If a Contactor is needed see “Section N- Main Control Box Power Panel Until 3/05” for part number(s).
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 82
Section F- Supply Air Section
Inverters & Inverter Bypass Control Box
3/05 thru 10/06 (Code 08= D, F) 1
Motor HP 5 (Code 22 OR Code 32= J*Y) Diagrams
Inverters may be located in a separate section (Code 14= 1, 2, 4, only inverters WITH bypass may be installed in a separate
section), or the Supply Air Section (Code 14= 3, 5, 6, 7, 8, 9). The inverter and bypass controls are the same regardless of the
installation location, although the sheet metal components differ. The diagrams shown below apply to either a Return Air or
Supply Air Inverter (both may be installed if Code 14= 5). Even if Code 14= 8, 9— where only a Return Air Fan Inverter is called
for— The inverter and bypass controls are still installed in the Supply Air Section.
1
If the unit was built 10/04 thru 3/05 OR 10/06 thru 12/06 contact Daikin Applied to confirm installed components.
LR10 (Supply)
LR20 (Return)
71
MMP30 (Supply)
MMP40 (Return)
40
70
50
72
M30B/M30I (Supply)
M40B/M40I (Return)
Supply Air OR Return Air Fan Inverter
with Bypass Control Box.
(Code 14= 3, 5, 8)
Two boxes installed if Code 14= 5
Bypass Controls Detail
75
70
40
78
Supply Air AND Return Air Fan
Inverter without Bypass.
(Code 14= 7)
72
73
40
74
76
Supply Air OR Return Air Fan
Inverter without Bypass.
(Code 14= 6, 7, 9)
77
MMP & Contactor Link Detail
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 83
Section F- Supply Air Section
Inverters & Inverter Bypass Control Box
3/05 thru 10/06 (Code 08= D, F) 1
Motor HP 5 (Code 22 OR Code 32= J*Y) Components
If the unit was built 10/04 thru 3/05 OR 10/06 thru 12/06 contact Daikin Applied to confirm installed components.
575V
460V
Motor HP
5
208V
230V
1
Ref Sch.
Part
Part
No.Sym. Description
Number
40 AFD10, 20 Inverter- see Inverter section
50
Gasket
0559402071111
70 MMP30, 40
Motor Control
3499340091
349934010 1
349934012 1 1
71 LR10, 20 Line Reactor- see page after inverters
72 M30B, I Contactor
349933102 1 1
M40B, I
349933201 1
349933301 1
73
Alarm- Short Circuit3499339031111
74
Alarm/Aux. Contact3499339021111
75
Line Shield
3499330011111
76
Cover- Contactor 349932801 2 2
349932802 2
349932803 2
77
Aux. Contact Block
N/A
78
Link Module
349932902 1 1
349932903 1
349932904 1
N/A= Not Applicable.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 84
Section F- Supply Air Section
Inverters & Inverter Bypass Control Box
3/05 thru 10/06 (Code 08= D, F) 1
Motor HP 7.5- 25 (Code 22 OR Code 32= K*Y, L*Y, M*Y, N*Y, P*Y) Diagrams
1
If the unit was built 10/04 thru 3/05 OR 10/06 thru 12/06 contact Daikin Applied to confirm installed components.
71
LR10 (Supply)
LR20 (Return)
70
40
MMP30 (Supply)
MMP40 (Return)
50
72
M30B/M30I (Supply)
M40B/M40I (Return)
Bypass Controls Detail
Supply Air OR Return Air Fan
Inverter w/Bypass Control Box.
(Code 14= 3, 5, 8)
Two boxes installed if
Code 14= 5
75
70
70
78
78
72
73
72
73
74
76
77
77
72
MMP & Contactor Link Detail
MMP p/n 349934109
MMP & Contactor Link Detail
MMP p/n 3499340xx
70
70
79
79
72
72
73
78
77
72
80
77
76
MMP & Contactor Link Detail
MMP p/n 349934105,06,07,08
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” MMP & Contactor Link Detail
MMP p/n 349938606
Rev. AG 01/15
RPL 7000070 / Page 85
Section F- Supply Air Section
Inverters & Inverter Bypass Control Box
3/05 thru 10/06 (Code 08= D, F) 1
Motor HP 7.5- 25 (Code 22 OR Code 32= K*Y, L*Y, M*Y, N*Y, P*Y)
Components
1
If the unit was built 10/04 thru 3/05 OR 10/06 thru 12/06 contact Daikin Applied to confirm installed components.
575V
460V
230V
575V
208V
460V
230V
575V
208V
460V
230V
575V
208V
460V
230V
575V
208V
460V
230V
208V
Motor Horsepower
7.5 101520 25
RefSch. Part
Part
No.Sym. Description
Number
40 AFD10, 20 Inverter- see Inverter section
50
Gasket
05594020711111111111111111111
70 MMP30, 40
Motor Control
3499340101
34993401111
3499340121
3499340131
34993401411
349934105
11
3499341061
111
3499341071
3499341081
1
3499341091
11
3499386061
71 LR10, 20 Line Reactor- see page after inverters
72M30B, IContactor
349933102111
M40B, I
3499332011
34993330111
1
349933401 1
3499335011
11
11
11
1
3499336011
11
1
73
Alarm- Short Circuit3499339031111111111111111 111
74 Alarm/Aux. Contact3499339021111111
75 Line Shield
3499330011111111
76 Cover- Contactor 349932801222
3499328022
34993280322
2
349932804 2
3499328052
22
22
22
2
77 Aux. Contact Block349933804111111111111
78 Link Module
349932902111
3499329031
34993290411
1
349932906 1
3499329071
11
11
11
1
79 Aux. Contact
3499387011
80 Lug
3499388016
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 86
Section F- Supply Air Section
Inverters & Inverter Bypass Control Box
3/05 thru 10/06 (Code 08= D, F) 1
Motor HP 30- 75 (Code 22= Q*Y, R*Y, S*Y, T*Y OR Code 32= Q*Y, R*Y, S*Y, T*Y, U*Y)
Diagrams
1
If the unit was built 10/04 thru 3/05 OR 10/06 thru 12/06 contact Daikin Applied to confirm installed components.
71
LR10 (Supply)
LR20 (Return)
70
40
MMP30 (Supply)
MMP40 (Return)
50
72
M30B/M30I (Supply)
M40B/M40I (Return)
Bypass Controls Detail
Supply Air OR Return Air Fan
Inverter w/Bypass Control
Box.
(Code 14= 3, 5, 8)
Two boxes installed if
Code 14= 5
70
78
72
73
77
70
72
MMP & Contactor Link Detail
MMP p/n 349934108, 09
79
70
79
72
80
72
77
73
78
77
72
MMP & Contactor Link Detail
MMP p/n 349938606, 07
76
MMP & Contactor Link Detail
MMP p/n 349934107
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 87
Section F- Supply Air Section
Inverters & Inverter Bypass Control Box
3/05 thru 10/06 (Code 08= D, F) 2
Motor HP 30- 75 (Code 22= Q*Y, R*Y, S*Y, T*Y OR Code 32= Q*Y, R*Y, S*Y, T*Y, U*Y)
Components
2
If the unit was built 10/04 thru 3/05 OR 10/06 thru 12/06 contact Daikin Applied to confirm installed components.
50
Gasket
70MMP30Motor Control
MMP40
575V
460V
230V
575V
208V
460V
230V
208V
575V
460V
230V
575V
208V
460V
230V
208V
575V
460V
230V
Ref Sch.
Part
Part
No.Sym. Description
Number
40 AFD10, 20 Inverter- see Inverter section
208V
Motor Horsepower
30 405060 75
05594020711111111 11 11 11
349934107111
3499341081
349934109111
349938606
1
111
3499386071
1
71 LR10, 20 Line Reactor- see page after inverters
72M30B, I
Contactor
M40B, I
3499335011
34993350211
34993360111111
349933602
1111
3499337011
73
Alarm- Short Circuit
3499339031111111
76
Cover- Contactor 349932805111
77
Aux. Contact Block3499338041111111
78
Link Module
349932907111
79
Aux. Contact
349938701
1
11
111
80
Lug
349938801 6 6 313166
1
Also requires 3 ring terminals.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 88
Section F- Supply Air Section
Inverters & Inverter Bypass Control Box
1/07 & Later (Code 08= D, F) 1
Motor HP 5 (Code 22 OR Code 32= J*Y)
1
If the unit was built between 10/06- 12/06 Contact Daikin Applied to confirm installed components.
LR10 (Supply)
LR20 (Return)
71
MMP30 (Supply)
MMP40 (Return)
40
70
Bypass Controls Detail
50
72
M30B/M30I (Supply)
M40B/M40I (Return)
Supply Air OR Return Air Fan Inverter
w/ Bypass Control Box.
(Code 14= 3, 5, 8)
MMP & Auxiliary
Contact Detail
10/07 & Later
Two boxes installed if Code 14= 5
40
MMP & Auxiliary
Contact Detail
Until 10/07
Supply Air OR
Return Air Fan
Inverter without
Bypass.
(Code 14= 6, 7, 9)
Supply Air AND Return
Air Fan Inverter
without Bypass.
(Code 14= 7)
73
70
73
40
70
74
MMP & Contactor
Link Detail
72
Motor HP
5
1
2
575V
460V
230V
208V
Ref Sch.
Part
Part
No.Sym. Description
Number
40 AFD10, 20 Inverter- see Inverter section
50
Gasket
0559402071111
70 MMP30, 40
Motor Control
3499340491
349934050 1
349934052 1 1
71 LR10, 20 Line Reactor- see page following inverters
72 M30B, I Contactor
349933121 1 1
M40B, I
349933123 1 1
73
Contact- Auxiliary 13499339221111
Contact- Auxiliary 23499338211111
74
Link
3499329221111
Side Mounted, 1 NO/1 NC. Until 10/07.
Side Mounted, 1 NO or NC. 10/07 & Later.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 89
Section F- Supply Air Section
Inverters & Inverter Bypass Control Box
1/07 & Later (Code 08= D, F) 1
Motor HP 7.5- 25 (Code 22 OR Code 32= K*Y, L*Y, M*Y, N*Y, P*Y) Diagrams
1
If the unit was built between 10/06- 12/06 Contact Daikin Applied to confirm installed components.
40
Supply Air OR
Return Air Fan
Inverter without
Bypass.
(Code 14= 6, 7, 9)
71
40
50
LR10 (Supply)
LR20 (Return)
70
MMP30 (Supply)
MMP40 (Return)
72
Supply Air OR Return Air Fan
Inverter w/Bypass Control
Box.
(Code 14= 3, 5, 8)
Supply Air AND Return
Two boxes installed if
Air Fan Inverter
Code 14= 5
without Bypass.
(Code 14= 7)
M30B/M30I (Supply)
M40B/M40I (Return)
40
Bypass Controls Detail
70
MMP & Auxiliary
Contact Detail
10/07 & Later
73
77
70
73
70
73
70
76
MMP & Auxiliary
Contact Detail
Until 10/07
74
72
72
72
72
MMP & Contactor Link Detail
MMP p/n 3499340xx
MMP & Contactor Link Detail
MMP p/n 349934147, 48, 49
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
MMP & Contactor Link Detail
MMP p/n 349938606
RPL 7000070 / Page 90
Section F- Supply Air Section
Inverters & Inverter Bypass Control Box
1/07 & Later (Code 08= D, F) 4
Motor HP 7.5- 25 (Code 22 OR Code 32= K*Y, L*Y, M*Y, N*Y, P*Y)
Components
4
If the unit was built between 10/06- 12/06 Contact Daikin Applied to confirm installed components.
50
Gasket
575V
460V
230V
575V
208V
460V
230V
575V
208V
460V
230V
575V
208V
460V
230V
575V
208V
460V
230V
RefSch. Part
Part
No.Sym. Description
Number
40 AFD10, 20 Inverter- see Inverter section
208V
Motor Horsepower
7.5 101520 25
05594020711111111111111111111
70 MMP30, 40
Motor Control
3499340501
34993405111
34993405211
349934053111
349934054
11
34993405511
34993414711
3499341481
1
3499341491
11
3499386061
71 LR10, 20 Line Reactor- see page after inverters
72
M30B,
IContactor
M40B, I
3499331211
34993312211
34993312311
349933321
1
111
349933322111
34993352111
3499335221
1
3499335231
1
3499336211
1
73
Contact- Auxiliary 23499338041
11
11
1
Contact- Auxiliary 134993392211111111 11 11 1
Contact- Auxiliary 334993382111111111111111111111
74
Link
34993292211111111 11 11 1
76
Interlock- Trip
3499387011
77
Lug Kit (3 per kit) 3499388012
Side Mounted, 1 NO/1 NC. Until 10/07.
Front Mounted, NC. Until 10/07.
3
Front Mounted, 1 NO or NC. 10/07 & Later.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 91
Section F- Supply Air Section
Inverters & Inverter Bypass Control Box
1/07 & Later(Code 08= D, F) 1
Motor HP 30- 75 (Code 22= Q*Y, R*Y, S*Y, T*Y OR Code 32= Q*Y, R*Y, S*Y, T*Y, U*Y)
Diagrams
1
If the unit was built between 10/06- 12/06 OR 4/13- 5/13 Contact Daikin Applied to confirm installed components.
71
LR10 (Supply)
LR20 (Return)
70
40
MMP30 (Supply)
MMP40 (Return)
50
72
M30B/M30I (Supply)
M40B/M40I (Return)
Bypass Controls Detail
Supply Air or Return Air Fan
Inverter w/Bypass Control Box.
(Code 14= 3, 5, 8)
Two boxes installed if Code 14= 5
70
70
70
73
73
73
MMP & Auxiliary
Contact Detail
Until 10/07
74
MMP & Auxiliary
Contact Detail
10/07 & Later
72
72
MMP & Contactor Link Detail
MMP p/n 349934147, 48, 49
MMP & Contactor Link Detail
MMP p/n 349934055
77
77
70
70
76
76
72
72
72
MMP & Contactor Link Detail
MMP p/n 349938606
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” MMP & Contactor Link Detail
MMP p/n 349938607
Rev. AG 01/15
RPL 7000070 / Page 92
Section F- Supply Air Section
Inverters & Inverter Bypass Control Box
1/07 & Later (Code 08= D, F) 5
Motor HP 30- 75 (Code 22= Q*Y, R*Y, S*Y, T*Y OR Code 32= Q*Y, R*Y, S*Y, T*Y, U*Y)
Components
5
If the unit was built between 10/06- 12/06 OR 4/13- 5/13 Contact Daikin Applied to confirm installed components.
50
Gasket
575V
460V
230V
208V
575V
460V
230V
575V
208V
460V
230V
208V
575V
460V
230V
575V
208V
460V
05594020711111111 11 11 1
70MMP30Motor Control
MMP40
71 LR10, 20 Line Reactor-
230V
Ref Sch.
Part
Part
No.Sym. Description
Number
40 AFD10, 20 Inverter- see next page
208V
Motor Horsepower
3040 506075
3499340551
349934147 1
3499341481
34993414911
11
349938606
1
111
3499386071
1
see page after inverters
72M30B, IContactor
3499333221
M40B, I
349933521 1
3499335221
1
3499335231
1
34993362111
1
349933721
111
3499337221
73
Contact- Auxiliary 3349933804111111
Contact- Auxiliary 13499339221
Contact- Auxiliary 4349933821
74 Link
3499329221
76 Interlock- Trip
349938701
1
11
111
77
Lug Kit (3 per kit)
349938801 2 2 121222
Side Mounted, 1 NO/1 NC. Until 10/07.
Also requires 3 ring terminals.
3
Front Mounted, NC. Until 10/07.
4
Front Mounted, 1 NO or NC. 10/07 & Later.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 93
Section F- Supply Air Section
Inverters
Code 15= R Model VTAC9
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
460V
208/230V
460V
460V
208/230V
460V
208/230V
208/230V
460V
208/230V
460V
460V
208/230V
460V
208/230V
208/230V
460V
208/230V
460V
460V
208/230V
208/230V
Motor Horsepower
5 7.51015202530 40506075
Part
Number
0988614541
0988614551
0988614561
0988614571
0988614581
0988614591
0988614601
0988614611
0988614621
0988614631
0988614641
098861468 1
0988614691
0988614701
RPL 7000070 / Page 94
Section F- Supply Air Section
Inverters, Continued
Code 15= A Model 550 (8/04 & Later) 1
Part
Number
112046002 1
1120460031
1120460041
1120460051
1120460061
1120460071
1120460081
1120460091
1120460101
1120460111
1120460121
112046015 1
1120460161
1120460171
1120460181
1120460191
1120460201
112046021
1
1120460221
1120460231
1120460241
1120460251
112046027 1
1120460281
1120460291
1120460301
1120460311
1120460321
1120460331
1120460341
112046035
1
1120460361
1
575V
460V
208/230V
575V
460V
208/230V
575V
460V
575V
208/230V
460V
575V
208/230V
460V
575V
208/230V
460V
575V
208/230V
460V
575V
208/230V
460V
208/230V
575V
460V
208/230V
575V
460V
208/230V
575V
460V
208/230V
Motor Horsepower
57.5101520253040 506075
Model ACH401 Inverters used until 8/04 have been discontinued and are no longer available. Replace with the comparable Model ACH550
p/n shown above. Note that repair parts for Model ACH401 Inverters are also no longer available. The Keypad Display for Model ACH550
Inverters is p/n 300040924.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 95
Section F- Supply Air Section
Inverters, Continued
Code 15= G Model 3500
575V
460V
230V
575V
208V
460V
230V
575V
208V
460V
230V
575V
208V
460V
230V
575V
208V
460V
230V
208V
575V
460V
230V
208V
Motor Horsepower
5 7.51015 2025
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
460V
230V
208V
575V
460V
230V
575V
208V
460V
230V
208V
575V
460V
230V
208V
575V
460V
230V
208V
Motor Horsepower
30 405060 75
Part
Number
098656909 1
0986569101
098656911
1
0986569121
0986569131
098656922 1
0986569231
0986569401
098656932 1
0986569331
0986569531
0986569511
0986569541
575V
Part
Number
098656903 1
0986569041
098656905
1
0986569061
0986569071
0986569081
098656916 1
0986569171
0986569181
0986569191
0986569201
0986569211
0986569261
0986569271
0986569281
0986569291
0986569301
0986569311
0986569431
0986569441
0986569451
0986569461
0986569471
0986569481
RPL 7000070 / Page 96
Section F- Supply Air Section
Inverters, Continued
Code 15= S, Q (MD2, MD3, MD6)
575V
460V
575V
208/230V
460V
208/230V
575V
460V
208/230V
575V
460V
208/230V
575V
460V
575V
208/230V
460V
575V
208/230V
460V
575V
208/230V
460V
575V
208/230V
460V
575V
208/230V
460V
208/230V
575V
460V
208/230V
Motor Horsepower
57.51015202530405060 75
Part
Number
193475809 11
193475810 11
193475811 11
193475812 11
193475813 11
193475814 11
193475815 11
193475816 11
349956617 31
193475825 11
193475826 11
193475827 11
193475828 11
193475829 11
193475830 11
193475831 11
193475832 11
193475883 11
193475884 31
193475885 31
193456304 2,4 1
193456305 2,41
193456306 2,41
193456307 2,41
193456308 2,41
349956647 31
349956648 31
349956649 31
349956650 31
349956651 31
349956652 3
1
Units built late 2010 & earlier shipped with ATV21 VFDs. All ATV21 drives have been replaced with ATV212 drives as listed above. These
new drives are drop in replacements with the exception of the Remote Keypad and Communication Cards. The ATV21 Remote Keypad
is p/n 349958801. The ATV21 Lonworks communication card is p/n 349927103. The ATV212 Remote Keypad is p/n 349958805 and
the Remote Keypad Mounting kit is p/n 349958803. The ATV212 Lonworks communication card is p/n 193482601. All other ATV212
communication cards are integral to the VFD and are not available separately. Note that 60 & 75 HP motors are not available in 208/230V
(Code 09= 12, 29).
2
MD3 Remote Keypad p/n is 349958802.
3
MD6 Remote Keypad p/n is 349958805 plus Mount p/n 349958803.
4
For 575V units with an MD3 Inverter and Motor under 25 HP a Line Reactor will be installed regardless of whether one is specified in Code 17 (see nomenclature page). See the next page for Line Reactor part numbers.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 97
Section F- Supply Air Section
Line Reactors 1
575V
460V
208V/230V
575V
460V
575V
208V/230V
460V
575V
208V/230V
460V
575V
208V/230V
460V
575V
208V/230V
460V
575V
208V/230V
460V
575V
208V/230V
460V
575V
208V/230V
460V
208V/230V
575V
460V
208V/230V
575V
460V
208V/230V
Motor Horsepower
5 7.51015 202530 4050 60 75
Part
Number
0733235031
0733235041
0733235051
0733235061
0733235071
0733235081
0733235091
0733235101
0733235111
0733235121
073323518 1
0733235191
0733235201
0733235211
0733235221
0733235231
0733235341
0733235351
0733235361
0733235571
0733235581
34996492621
34996492721
3499649292 1
3499649302
1
34996493121
34996493221
34996495421
34996495521
34996495621
Line Reactors are used when Code 17= CL, CE, CH, CJ, CK, C4, C6, C7, C8, YL, YE, YH, YJ, YK, Y4, Y6, Y7, Y8; except for MD3 575V
Inverters (Code 15= S, Q ) 2- 20 HP; these will always have a Line Reactor installed regardless of Code 17.
2
These are 5% impedance Line Reactors. Some units may have 3% impedance Line Reactors installed, the 5% may be used in their
place. Due to dimensional differences, minor field modifications may be required for proper installation.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 98
Section F- Supply Air Section
Section Mounted Controls
PC7, HL22, LT10, S10, REC10, UV Lights
Until 1/00
PC7- Proof of Airflow Pressure Control
20
19
15
15
1/00 & Later
19
RefPart
No. Description
15 Bracket, Until 1/00
Bracket, 1/00 & Later 19 PC7 Pressure Control
Until 1/00
1/00 & Later 20 Pneumatic Fitting
Until 1/00
1/00 & Later 1
20
Part
Number Qty.
057233101 1
1
1
065493801 1
1
1
049763002 1
1
1
In 06/12 the design of PC7 was changed. Units built 1/00 &
Later require Retrofit Kit 910122413 for proper installation
as old and new parts are NOT interchangeable. In the Kit,
the Switch is p/n 910115489, the Pneumatic Fitting is p/n
910122414, and the Support Bracket is p/n 910122290.
HL22- Gas Heat Hi Limit Switch
Code 04= A
67
RefPart
No. Description
67 T-stat- HL22 Hi Limit
84
85
86
87
88 89
Part
Number Qty.
047938801 1
LT10- Supply Fan Light/S10- Supply Fan
Light Switch/REC10- Supply Fan Light
Receptacle
Code 49= B, E
RefPart
No. Description
84 Light Fixture
85 Bulb- LT10
86 Junction Box
87 Junction Box Cover
88 Light Switch- S10
89 Receptacle- REC10
Part
Number Qty.
042229500 1
065492402 1
065491901 1
065492001 1
065492201 1
030187000 1
UV Lights
Code 17= C1 thru C8 AND Y1 thru Y8
98
99
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” RefPart
No. Description
98 Lamp Holder- 18”
Lamp Holder- 24”
Lamp Holder- 36”
99 Lamp- 18”
Lamp- 24”
Lamp- 36”
Rev. AG 01/15
Part
Number Qty.
205484001 1
205484101 1
205484201 1
205484501 1
205484601 1
205484701 1
RPL 7000070 / Page 99
Section F- Supply Air Section
Section Mounted Controls
MAT, EFT, SAT, DAT, OAT, SD1
Mixed Air Temperature Sensor- MAT OR
Entering Fan Temperature Sensor- EFT
5
RefPart
Part
No. Description
Number Qty.
5 MAT/EFT Sensor
MicroTech Controls
059974605 1
MicroTech II Controls
060004705 1
MicroTech III Controls 193414602 1
MAT (until 2/04)
EFT (2/04 & Later)
Supply Air Temperature Sensor- SAT OR
Discharge Air Temperature Sensor- DAT
RefPart
Part
No. Description
Number Qty.
8 SAT/DAT Sensor
MicroTech Controls
059974605 1
MicroTech II Controls
060004705 1
MicroTech III Controls 193414602 1
8
SAT (until 2/04)
DAT (2/04 & Later)
Outdoor Air Temperature Sensor- OAT
7
RefPart
Part
No. Description
Number Qty.
7 OAT Sensor
MicroTech Controls
059974605 1
MicroTech II Controls
060004705 1
MicroTech III Controls 193414602 1
OAT
Smoke Detector- SD1
51
Smoke
Detector
Detail
Part
RefPart
No. Description
Number
Qty.
50 Smoke Detector- SD1 098873101 11
1
50
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” The original Smoke Detector for units built 2003 & Earlier is no
longer available. When replacing any version of SD1, reuse
existing Sampling Tubes or order 1pc. 098873101 for Standard
Discharge or 2pc. of 098873501 for Side or Top Discharge.
Minor field modifications may be required for proper installation.
Rev. AG 01/15
RPL 7000070 / Page 100
Section F- Supply Air Section
Section Mounted Controls
SCB- Split Junction Box (Code 05= F)- TB25, TB27, TB28, PB10, PB9, PB20, PB19
TB28
PB 19
PB 20
TB27
PB 9
TB25
PB 10
Across- The- Line Start (Code 10= AL, PW)
575V
460V
230V
208V
575V
460V
230V
208V
575V
460V
230V
208V
575V
460V
230V
208V
Motor HP
2 - 25
30
40, 50
60 - 75
Sch. Part
Part
Sym. Description
Number
Terminal Blocks
TB25 Terminal Block- SCB
01599812411 11 111111111111
TB27 Terminal Block- SCB
01599813011 11 111111111111
TB28 1Terminal Block- SCB
01599812411 11 111111111111
PB10 Power Block- Supply Fan
95A, 600V, 3P
03037270711 11 11111111 11
175A, 600V, 3P
0303727101
1
PB9 Power Block- Supply Fan
95A, 600V, 3P
03037270711
1
PB20 Power Block- Return Fan
95A, 600V, 3P
03037270711 11 11111111
PB19 Power Block- Return Fan
95A, 600V, 3P
030372707 1
Part Winding Start (Code 10= PP, PS) 2
1
2
575V
460V
230V
208V
575V
460V
230V
208V
575V
460V
230V
208V
575V
460V
230V
208V
Motor HP
2 - 25
30
40, 50
60 - 75
Sch. Part
Part
Sym. Description
Number
Terminal Blocks
TB25 Terminal Block- SCB
01599812411 11111111111 111
TB27 Terminal Block- SCB
01599813011 11111111111 111
TB28 1Terminal Block- SCB
01599812411 11111111111 111
PB10 Power Block- Supply Fan
95A, 600V, 3P
03037270711 1111111111 11
175A, 600V, 3P
03037271011
PB9 Power Block- Supply Fan
95A, 600V, 3P
03037270711 11111111111 111
PB20 Power Block- Return Fan
95A, 600V, 3P
03037270711 1111111111
PB19 Power Block- Return Fan
95A, 600V, 3P
03037270711 1111111111
Only used when the unit has a Supply Fan Inverter, VIV, or an Economizer with a Power Closure Exhaust Damper.
Part Winding Fans are rare.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 101
Section G- Blow-Thru Heat Section
Notes
➩
Primary Codes that pertain: 04, 34
Additional Codes that pertain: 06, 07, 08, 09, 12, 31
This section is divided into four subsections: 1. Blank Access; 2. HW/Steam Heat; 3. Electric Heat; and 4. Gas Heat.
Code 04 determines what type of heat, if any, the unit employs, and Code 34 defines the Heat Section’s characteristics.
If Code 04= Y, and Code 34= YYYYYY there is no section. If Code 04= Y and Code 34= BBBBBB, then there is a
48” Blank Access Section installed. Refer to the Unit Code Index for specific Heat Section coding and definitions.
Code 06, insulation and liners, influences the final cabinet assembly panel part numbers. For sheet metal
components that make up the Blow-Thru Heat Section, contact Daikin Applied with model and serial number
information to ensure that the correct liners, insulation and hardware are ordered.
Code 07 is the Gas Heat Burner Approval Code and affects many of the parts in the Gas Heat Section depending
on whether the unit is UL approved (USA) or CSA approved (Canada).
Code 08 and Code 12 determine the control type, control location, generation of controls installed, and the Gas
Heat Actuator Motor used.
Code 09 determines the Unit Voltage, which will have an effect on the Electric Heaters and their controls.
Code 31 is the Supply Fan size, and has an effect on the Heat Section’s bulkhead panels and Diffusers.
Section Mounted Controls
LT12- BT Heat Section Light/S12- Heat Section
Light Switch/REC12- Heat Section Receptacle
84 85
RefPart
No. Description
84 Light Fixture
85 Bulb- LT12
88 Light Switch- S12
89 Receptacle- REC12
88 89
Part
Number Qty.
042229500 1
065492402 1
065492201 1
030187000 1
Option 1: Blank Section
Code 34= BBBBBB
Diffuser AND Code 04= Y 1
12
RefPart
Part
No. Description
Number
12 Diffuser
33” Supply Fan Code 31= 33** 055988003
36” Supply Fan Code 31= 36** 055988004
40” Supply Fan
Code 31= 40** 055988005
1
Qty.
1
1
1
The drawing shows a Diffuser factory mounted on a unit shipped fully assembled
(Code 05= Y). If Code 05= F, the unit is split at the Supply Fan Section (Section
F) and the Heat Section (Section G); in this case the Diffuser is field mounted. The
part number is the same in either case.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 102
Section G- Blow-Thru Heat Section
Option 2- Hot Water, Steam Coil Heat
Code 04= W, S AND Code 34 first 3 digits = S11, S12, S13, S14, W11, W22
Coils, Valves, Diffusers & Actuator VM1 Diagrams
Diffuser
Coil Location
12
3
2
Mixing Valve Detail 12/08 & Earlier
63
64
65
Steam Coil Units 1/09 & Later
249
Hot Water Coil Units 1/09 & Later
163
263
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 103
Section G- Blow-Thru Heat Section
Option 2- Hot Water, Steam Coil Heat
Code 04= W, S AND Code 34 first 3 digits = S11, S12, S13, S14, W11, W22
Coils, Valves, Diffusers & Actuator VM1 Components
RefSch. Part Code
Coil
Coil
No. Sym. Description
34= Type
Height
2
Steam Heat Coil- Bottom
S11***
5JA0601H
42”
Steam Heat Coil- Bottom
S12***
5JA1201H
42”
Steam Heat Coil- Bottom
S13***
5JA0602C
42”
Steam Heat Coil- Bottom
S14***
5JA1202C
42”
Hot Water Heat Coil- Bottom
W11*** 5WH0901H
42”
Hot Water Heat Coil- Bottom
W22*** 5WS0902C
42”
3
Steam Heat Coil- Top
S11***
5JA0601H
39”
Steam Heat Coil- Top
S12***
5JA1201H
39”
Steam Heat Coil- Top
S13***
5JA0602C
39”
Steam Heat Coil- Top
S14***
5JA1202C
39”
Hot Water Heat Coil- Top
W11*** 5WH0901H
39”
Hot Water Heat Coil- Top
W22*** 5WS0902C
39”
12
Diffuser- 33” Supply Fan
Diffuser- 36” Supply Fan
Diffuser- 40” Supply Fan
Valve & VM1
12/08 & Earlier
63 VM1 Actuator- 120V
*****E
All
All
64
Linkage- 1.25”, 1.50”, 2.00” Valve
*****E
All
All
Linkage- 2.50”, 3.00” Valve
*****E
All
All
65
Valve, 2 Way— Steam Heat
1.25” S**E2*
5JA
All
1.50” S**F2*
5JA
All
2.00” S**G2*
5JA
All
2.50” S**H2*
5JA
All
3.00” S**J2*
5JA
All
Valve, 3 Way— Hot Water Heat
1.25” W**E3* 5WH, 5WS
All
1.50” W**F3* 5WH, 5WS
All
2.00” W**G3* 5WH, 5WS
All
2.50” W**H3* 5WH, 5WS
All
3.00”
W**J3* 5WH, 5WS
All
Valve & VM1
1/09 & Later
249
Valve, 2 Way Steam Heat w/ Act. 5
1.25” S**E2E
5JA
All
1.50” S**F2E
5JA
All
2.00” S**G2E
5JA
All
2.50” S**H2E
5JA
All
163 VM1 Actuator- 24V, 1.25- 2.00” Valve 6
W***3E
All
All
Actuator- 24V, 2.50- 3.00” Valve 6
W***3E
All
All
263
Valve, 3 Way HW w/ Actuator
1.25” W**E3E 5WH, 5WS
All
1.50” W**F3E 5WH, 5WS
All
2.00” W**G3E 5WH, 5WS
All
2.50” W**D3E 5WH, 5WS
All
3.00” W**D3E 5WH, 5WS
All
Part
Number Qty.
056053061 31
056053062 31
056053063 1
056053064 1
056053065 31
056053066 1
056053041 31
056053042 31
056053043 1
056053044 1
056053045 31
056053046 1
055988003 1
055988004 1
055988005 1
059999804
049762401
049762403
1
1
1
049762502 1
049762503 1
049762504 1
049762505 1
049762506 11
047936505 1
047936501 1
047936502 1
047936506 1
047936503 21
113147501
113147701
113147901
113148101
300046566
113149601
1
1
1
1
1
1
113166703
113166704
113166705
113166706
113166707
1
1
1
1
1
Steam Heat 3.00” Valve has a Flange Gasket p/n: 031315900.
Hot Water Heat 3.00” Valve has a Flange Gasket p/n: 031316000.
3
Prior to 12/94 1 row coils were “C” type. Top Coils are, 5JA0601C — p/n 056053001; 5JA1201C— p/n 056053002; 5WH0901C—
p/n 056053005.
4
Prior to 12/94 1 row coils were “C” type. Bottom Coils are, 5JA0601C — p/n 056053011; 5JA1201C— p/n 056053012; 5WH0901C—
p/n 056053015.
5
Note that the Steam Valve is factory supplied WITH the Actuator. For Actuator ONLY p/ns contact Daikin Applied with model and
serial number information so that the correct Actuator can be identified.
6
Note that the HW Valve is factory supplied WITH the Actuator. Use this p/n when replacing the HW Actuator ONLY.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 104
Section G- Blow-Thru Heat Section
Option 3- Electric Heat: Code 04= A AND Code 34 first digit = E
Heaters, Hi Limit Cutouts, Diffusers
5
12
Air
w
Flo
7
7A
6
575V
460V
208/230V
Hi Limit Cutout Unit
with with
Voltage
Auto and
Auto
Ref Sch. Part
Total
Code
Heater Manual
Cutout
No. Sym. Description
KW
34= KW
Cutout 1Only 2
5
Heater Assy- Top
80
E080
80 049269206 049269215 1
Heater Assy- Top
80
E080
80 049269224 049269233 1
Heater Assy- Top
80
E080
80
N/A
049269242 1
Heater Assy- Top
100
E100
100 049269205 049269214 1
Heater Assy- Top
100
E100
100 049269223 049269232 1
Heater Assy- Top
100
E100
100
N/A
049269241 1
Heater Assy- Top
120
E120
120 049269204 049269213 1
Heater Assy- Top
120
E120
120 049269222 049269231 1
Heater Assy- Top
120
E120
120
N/A
049269240 1
Heater Assy- Top
160
E160
160 049269203 049269212 1
Heater Assy- Top
160
E160
160 049269221 049269230 1
Heater Assy- Top
160
E160
160
N/A
049269239 1
Heater Assy- Top
200
E200
120 049269204 049269213 1
Heater Assy- Top
200
E200
120 049269222 049269231 1
Heater Assy- Top
200
E200
120
N/A
049269240 1
Heater Assy- Top
240
E240
120 049269204 049269213 1
Heater Assy- Top
240
E240
120 049269222 049269231 1
Heater Assy- Top
240
E240
120
N/A
049269240 1
Heater Assy- Top
280
E280
160 049269203 049269212 1
Heater Assy- Top
280
E280
160 049269221 049269230 1
Heater Assy- Top
280
E280
160
N/A
049269239 1
Heater Assy- Top
320
E320
160 049269203 049269212 1
Heater Assy- Top
320
E320
160 049269221 049269230 1
Heater Assy- Top
320
E320
160
N/A
049269239 1
N/A= Not Applicable.
1
Units ETL/MEA approval (Code 07= EY) OR no approval (Code 07= YY). Heater Assy. includes Hi Limit Auto and Manual Reset Switches.
2
Units CSA approval (Code 07= CY). Heater Assy. includes Hi Limit Auto Reset Switches.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 105
Section G- Blow-Thru Heat Section
Option 3- Electric Heat: Code 04= A AND Code 34 first digit = E
Heaters, Hi Limit Cutouts, Diffusers
Continued
575V
460V
208/230V
Hi Limit Cutout Unit
with with
Voltage
Auto and
Auto
Ref Sch. Part
Total
Code
Heater Manual
Cutout
No. Sym. Description
KW
34= KW
Cutout 1Only 2
6
Blank Assy- Bottom
80- 160 E/080- 160
055923602 055923602 1 1 1
Heater Assy- Bottom
200
E200
80 049269206 049269215 1
Heater Assy- Bottom
200
E200
80 049269224 049269233 1
Heater Assy- Bottom
200
E200
80
N/A
049269242 1
Heater Assy- Bottom
240
E240
120 049269204 049269213 1
Heater Assy- Bottom
240
E240
120 049269222 049269231 1
Heater Assy- Bottom
240
E240
120
N/A
049269240 1
Heater Assy- Bottom
280
E280
120 049269204 049269213 1
Heater Assy- Bottom
280
E280
120 049269222 049269231 1
Heater Assy- Bottom
280
E280
120
N/A
049269240 1
Heater Assy- Bottom
320
E320
160 049269203 049269212 1
Heater Assy- Bottom
320
E320
160 049269221 049269230 1
Heater Assy- Bottom
320
E320
160
N/A
049269239 1
7 HL1- 20 Hi Limit- Manual Cutout
All
All
All 065496201
N/A
1 1 1
7A HL31- 50 Hi Limit- Auto Cutout
All
All
All 065824501 065824501 1 1 1
12
Diffuser
AllAllAll
055658401
055658401
2
2
2
N/A= Not Applicable.
1
Units ETL/MEA approval (Code 07= EY) OR no approval (Code 07= YY). Heater Assy. includes Hi Limit Auto and Manual Reset Switches.
2
Units CSA approval (Code 07= CY). Heater Assy. includes Hi Limit Auto Reset Switches.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 106
Section G- Blow-Thru Heat Section
Option 3- Electric Heat: Code 04= A AND Code 34 first digit = E
Electric Heat Control Box- Until 3/05
FB FB FB FB FB
33 32 36 31 35
M
33
M
32
M
36
M
31
M
35
HS
3
TB
12
FB
33
FB
32
FB
31
FB
33
FB
32
FB
31
M
33
M
32
M
31
M
33
M
32
M
31
FB
34
FB
44
M
34
M
44
FB
43
FB
42
FB
41
M
43
M
42
M
41
HS
3
TB
12
TB
12
FB
34
M
34
FB
34
TB
11
TB
11
M
34
DS3
or
PB3
208/230V 20-160 KW
TB
11
DS3
or
PB3
DS3
or
PB3
NOTE: Diagram illustrates maximum KW
HS
3
380/460/575V 20-160 KW
NOTE: Diagram illustrates maximum KW
380/460/575V 200- 320 KW
NOTE: Diagram illustrates maximum KW
DS3— Disconnect Switch- Through the Door Style
Sch.
Symbol
DS3
DS3
DS3
DS3
DS3
DS3
DS3
DS3
DS3
DS3
DS3
DS3
Unit
Voltage
208/230
208/230
208/230
380/575
380/575
380/575
380/575
460
460
460
460
460
Total
Heater KW
20
40,60,80
100,120
20,40
60-200
240,280
320
20,40
60-160
200,240
280
320
Disconnect
Specs
60A 600V 3P
250A 600V 3P
400A 600V 3P
60A 600V 3P
250A 600V 3P
400A 600V 3P
400A 600V 3P
60A 600V 3P
250A 600V 3P
400A 600V 3P
800A 600V 3P
600A 600V 3P
Disconnect
PN
031446200
047442104
047442108
031446200
047442104
047442109
072937502
031446200
047442104
047442109
031019401
027070601
Mechanism
PN
031322400
039903100
025862500
031322400
039903100
025862500
025862500
031322400
039903100
025862500
031011600
028399200
Term. Lug
PN
FWS
FWS
FWS
FWS
FWS
FWS
FWS
FWS
FWS
FWS
031019403
FWS
FWS= Furnished with Switch.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 107
Section G- Blow-Thru Heat Section
Option 3- Electric Heat: Code 04= A AND Code 34 first digit = E
Electric Heat Control Box- Until 3/05
20- 120 KW Components
Sch.
Sym.
PB3
208V
230V
460V
380/575V
208V
230V
460V
380/575V
208V
230V
460V
380/575V
208V
230V
460V
380/575V
208V
230V
460V
380/575V
208V
230V
460V
380/575V
Heater KW=
20406080100
120
Part
Part
Description
Number
Power Block 030372707 1111
Power Block 0303727051111111 11111
Power Block 03037271711
11111
Power Block 0303727181
DS3 Disconnect Switch
2
HS3 Switch 033696300 1 11 11 11 1111 1 11 111 111 11 11
TB11 Terminal Block 0159981091 1 11 11 11 1111 1 11 111 111 11 11
TB12 Terminal Block 03037271711
TB12 Terminal Block 0303727201
1
TB12 Terminal Block 0303727051
11
11
1
M31
M32
M33
M34
M35
M36
Contactor 027514103 1111 11111 111
Contactor027514102
1
1
1
1
Contactor 027514101111111 11
Contactor 027514103111
111
11
11
Contactor027514102
1
1
1
Contactor 0275141011111 1111
Contactor 0275141031
1111
1
Contactor027514102
1
1
Contactor 0275141011
11
11
1
Contactor 0275141031
1111
1
Contactor027514102
1
1
Contactor 0275141011
11
11
1
Contactor 027514103111
1
Contactor 0275141031
1
FB31 Fuse Block 023780209 111111 1111 11
Fuse Block 023780205111111 11
Fuse Block 0237802101
11
1
FB32 Fuse Block 0237802091111 1111 11
Fuse Block 0237802051111 1111
Fuse Block 0237802101
1
FB33 Fuse Block 0237802091
11
1111
1
Fuse Block 0237802051
11
11
1
FB34 Fuse Block 0237802091
11
1111
1
Fuse Block 0237802051
11
11
1
FB35 Fuse Block 023780209111
1
FB36 Fuse Block 0237802091
1
1
2
Terminal Block listed is for 1- 6 stages of heat (standard). For units with 7- 10 stages of heat (rare specials) use p/n 015998114.
See chart on previous page.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 108
Section G- Blow-Thru Heat Section
Option 3- Electric Heat: Code 04= A AND Code 34 first digit = E
Electric Heat Control Box- Until 3/05
20- 120 KW Components, Continued
Sch.
Sym.
F31
F32
F33
F34
F35
F36
Heater KW=
60
80
100
120
208V
230V
460V
380/575V
208V
230V
460V
380/575V
208V
230V
460V
380/575V
208V
230V
460V
380/575V
208V
230V
460V
380/575V
208V
230V
460V
380/575V
20
40
Part
Part
Description
Number
Fuse- FB31 0258605143
33
3333
33
3
Fuse- FB31 0258605113
Fuse- FB31 0258605123
Fuse- FB31 025860409 3 333
Fuse- FB31 02586040833 3 3
Fuse- FB31 02586041433
Fuse- FB31 02586041333
Fuse- FB32 0258605143
3333
33
3
Fuse- FB32 0258605113
Fuse- FB32 0258605123
Fuse- FB32 0258604093333
Fuse- FB32 0258604083333
Fuse- FB32 0258604143
Fuse- FB32 0258604133
Fuse- FB33 0258605113
Fuse- FB33 0258605123
Fuse- FB33 025860514333
33
3
Fuse- FB33 025860409333
Fuse- FB33 025860408333
Fuse- FB33 0258604123
Fuse- FB33 0258604113
Fuse- FB34 0258605113
Fuse- FB34 0258605123
Fuse- FB34 025860514333
33
3
Fuse- FB34 025860409333
Fuse- FB34 025860408333
Fuse- FB35 0258605143
33
3
Fuse- FB36 0258605143
3
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 109
Section G- Blow-Thru Heat Section
Option 3- Electric Heat: Code 04= A AND Code 34 first digit = E
Electric Heat Control Box- Until 3/05
160- 320 KW Components, Continued
Sch. Part
Sym. Description
PB3Power Block
Power Block
Power Block
Power Block
DS3 Disconnect Switch
Heater KW=
160 200240280 320
460V
380/575V
460V
380/575V
460V
380/575V
460V
380/575V
460V
380/575V
Part
Number
0303727211
1
030372720 1 1 1
030372717 1 1
030372706 1 1 1
2
HS3 Switch 033696300 1111111111
TB11 Terminal Block 015998109 11111111111
TB12 Terminal Block 030372705 1
TB12 Terminal Block 030372720 11111111
TB12 Terminal Block 030372716 1
M31 Contactor
Contactor
M32 Contactor
Contactor
M33 Contactor
Contactor
Contactor
M34 Contactor
Contactor
Contactor
M41Contactor
Contactor
Contactor
M42Contactor
Contactor
Contactor
M43 Contactor
Contactor
Contactor
M44 Contactor
Contactor
Contactor
02751410311111
02751410211111
02751410311111
02751410211111
027514103111
027514102111
0275141011111
027514103111
027514102111
0275141011111
0275141031
027514102
1
027514101 111111
0275141031
027514102
1
027514101 111111
027514103111
027514102111
027514101 11
027514103111
027514102111
027514101 11
Terminal Block listed is for 1- 6 stages of heat (standard). For units with 7- 10 stages of heat (rare specials) use p/n 015998114.
2
See chart 3 pages prior.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 110
Section G- Blow-Thru Heat Section
Option 3- Electric Heat: Code 04= A AND Code 34 first digit = E
Electric Heat Control Box- Until 3/05
160- 320 KW Components, Continued
Sch. Part
Sym. Description
FB31 Fuse Block
FB32 Fuse Block
FB33 Fuse Block
Fuse Block
FB34 Fuse Block
Fuse Block
FB41Fuse Block
Fuse Block
FB42Fuse Block
Fuse Block
FB43 Fuse Block
Fuse Block
FB44 Fuse Block
Fuse Block
F31 Fuse- FB31
Fuse- FB31
F32 Fuse- FB32
Fuse- FB32
F33 Fuse- FB33
Fuse- FB33
Fuse- FB33
Fuse- FB33
F34 Fuse- FB34
Fuse- FB34
Fuse- FB34
Fuse- FB34
F41 Fuse- FB41
Fuse- FB41
Fuse- FB41
Fuse- FB41
F42 Fuse- FB42
Fuse- FB42
Fuse- FB42
Fuse- FB42
F43 Fuse- FB43
Fuse- FB43
Fuse- FB43
Fuse- FB43
F44 Fuse- FB44
Fuse- FB44
Fuse- FB44
Fuse- FB44
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Heater KW=
160200240280320
460V
380/575V
460V
380/575V
460V
380/575V
460V
380/575V
460V
380/575V
Part
Number
023780210 1111111111
023780210 1111111111
023780210 1 1 111 1
0237802051111
023780210 1 1 111 1
0237802051111
023780210
1
1
023780205111111
023780210
1
1
023780205111111
023780210 11 111 1
023780205 1 1
023780210 11 111 1
023780205 1 1
025860414 33 3 33
02586041333333
025860414 33 3 33
02586041333333
025860414 3 33
025860413 33 3
02586040933
02586040833
025860414 3 33
025860413 33 3
02586040933
02586040833
025860409333
025860408333
025860414
3
0258604133
025860409333
025860408333
025860414
3
0258604133
025860409 3
025860408 3
025860414 3 33
02586041333 3
025860409 3
025860408 3
025860414 3 33
02586041333 3
Rev. AG 01/15
RPL 7000070 / Page 111
Section G- Blow-Thru Heat Section
Option 3- Electric Heat: Code 04= A AND Code 34 first digit = E
Electric Heat Control Box- 3/05 & Later
FB33
FB32
FB31
M33
M32
M31
FB33
FB32
FB31
FB44
FB34
M33
M32
M31
M44
M34
FB43
FB42
FB41
M43
M42
M41
FB33 FB32 FB36 FB31 FB35
M33 M32 M36 M31 M35
H
S
3
H
S
3
FB34
H
S
3
FB34
M34
M34
T
B
11
208/230V
20KW- 120KW
460/575V
20KW- 160KW
PB31
DS3
or
PB3
T
B
11
460/575V
200KW- 320KW
PB31
PB31
DS3
or
PB3
T
B
11
DS3
or
PB3
DS3- Disconnect Switch 1— Until 10/06 2
Sch.
Sym.
DS3
Part
Disconnect Switch Component
Description
Amps
Switch
Handle
Lugs
Disconnect Switch 100 Amp
349935101
349935501 349935901 (6)
Disconnect Switch 150 Amp
349935102
349935501 349935901 (6)
Disconnect Switch 250 Amp
349935201
349935501 349936001 (6)
Disconnect Switch 400 Amp
349935301
349935602 349936201 (2)
Disconnect Switch 600 Amp
349935302
349935602 349936201 (2)
Disconnect Switch 800 Amp
349935403
349935701 349936401 (6)
Disconnect Switch 1200 Amp
349935403
349935701 349936501 (6)
Ground Lug
349938001
349938001
349938001
349938002
349938002
349938003
349938003
DS3- Disconnect Switch 1— 1/07 & Later 2
Sch. Part
Disconnect Switch Component
Sym. Description
Amps
Switch
Handle 3
Shaft
Ground Lug
DS3
Disconnect Switch
100 Amp349935125349935523349962211349938001
Disconnect Switch
150 Amp349935126349935533349962212349938001
Disconnect Switch
250 Amp349935226349935533349962212349938001
Disconnect Switch
400 Amp349935325349935622349962213349938002
4, 5
Disconnect Switch 600 Amp 193438205 5
349962243 5349938002
Disconnects are sized according to various unit specifications. Check installed switch to verify the correct DS3 size.
For units built between 10/1/06 and 12/31/06 contact Daikin Applied to ensure correct switch is ordered.
3
Includes mechanism (except 600A switch, see footnote 4).
4
Handle only p/n 349961102; Mechanism only p/n 193455001; Shaft p/n 349961403.
5
Note that the original Disconnect is obsolete. Due to dimensional differences minor field modifications may be required for proper
installation.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 112
Section G- Blow-Thru Heat Section
Option 3- Electric Heat: Code 04= A AND Code 34 first digit = E
Electric Heat Control Box- 3/05 & Later
20- 120KW Components
208V
230V
460V
575V
208V
230V
460V
575V
208V
230V
460V
575V
208V
230V
460V
575V
208V
230V
460V
575V
208V
230V
460V
575V
Heater KW=
20406080100
120
Sch. Part
Part
Sym. Description
Number
PB3 Power Block
until 10/06 3 030372730 1111111111 11 11 11
Power Block
until 10/06 3030372744
1
11
1
1
1
Power Block
until 10/06 3 0303727521
1
Cover- PB3
until 10/06 3 349938302 1 11 11 11 1111 1 11 1111 1 111 11
Power Block
1/07 & Later 3 030372777 1111111111 11 11 11
Power Block
1/07 & Later 3030372785
1
11
1
1
1
1
1
1/07 & Later 3
PB31 Power Block 4
used w/100A, 150A DS3 used w/250A DS3 used w/400A DS3 used w/600A DS3 DS3 Disconnect Switch
030372777 1 11 11 11 1111 1 11 1111 1 111 11
030372783 1 11 11 11 1111 1 11 1111 1 111 11
030372785 1 11 11 11 1111 1 11 1111 1 111 11
030372721 5 1 11 11 11 1111 1 11 1111 1 111 11
2
HS3 Switch 033696300 1 11 11 11 1111 1 11 1111 1 111 11
TB11 Terminal Block
Terminal Block
until 10/06 33499306031111 1 11 1111 1 11 1111 1 111 11
1/07 & Later 33499306211111 1 11 1111 1 11 1111 1 111 11
M31
M32
M33
M34
M35
M36
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
until 10/06 3 3499322011111 11
until 10/06 3 349932301 1 1 1 1 111 1 11 11 1 111 11
until 10/06 3 349932301 1 1 111 1 11 11 11 11
until 10/06 3 349932201111
111
until 10/06 3349932301
1
11
1
1
1
1
1
until 10/06 3 3499322011
1111
1
until 10/06 3349932301
1
11
1
1
1
1
1
until 10/06 3 3499322011
1111
1
until 10/06 3 3499323011
11
1
1
until 10/06 3 3499323011
M31
M32
M33
M34
M35
M36
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
1/07 & Later 3 3499323211111 11
1/07 & Later 3 349932322 1 1 1 1 111 1 11 11 1 111 11
1/07 & Later 3 349932322 1 1 111 1 11 11 11 11
1/07 & Later 3 349932321111
111
1/07 & Later 3349932322
1
11
1
1
1
1
1
1/07 & Later 3 3499323211
1111
1
1/07 & Later 3349932322
1
11
1
1
1
1
1
1/07 & Later 3 3499323211
1111
1
1/07 & Later 3 3499323221
11
1
1/07 & Later 3 3499323221
1
Part number is for one section. The number of sections used is determined by the options installed.
See charts on previous page.
3
For units built between 10/1//06 and 12/31/06 contact Daikin Applied to ensure correct part is ordered.
4
Not Used when PB3 Power Block connection is present.
5
Cover— PB31 used with 600A DS3= p/n 349938345.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 113
Section G- Blow-Thru Heat Section
Option 3- Electric Heat: Code 04= A AND Code 34 first digit = E
Electric Heat Control Box- 3/05 & Later
20- 120KW Components, Continued
208V
230V
460V
575V
208V
230V
460V
575V
208V
230V
460V
575V
208V
230V
460V
575V
208V
230V
460V
575V
208V
230V
460V
575V
Heater KW=
20
40
60
80
100
120
Sch. Part
Part
Sym. Description
Number
FB31 Fuse Block 0237802291
11
111111
11
1
Fuse Block 0237802251
11
111
Fuse Block 023780230111
11
1
FB32 Fuse Block 023780229 11111111 11
Fuse Block 0237802251
1111
1
Fuse Block 023780230111
1
FB33Fuse Block0237802291
1
1
1
1
11
1
Fuse Block 023780225111
11
1
FB34Fuse Block0237802291
1
1
1
1
11
1
Fuse Block 023780225111
11
1
FB35 Fuse Block 0237802291
11
1
FB36 Fuse Block 0237802291
1
F31Fuse- FB31 0258605143
33
3333
33
3
Fuse- FB31 0258605113
Fuse- FB31 0258605123
Fuse- FB31 025860409333
Fuse- FB31 025860408333
Fuse- FB31 0258604123
Fuse- FB31 0258604113
Fuse- FB31 02586041433
Fuse- FB31 02586041333
F32Fuse- FB32 0258605143
3333
33
3
Fuse- FB32 0258605113
Fuse- FB32 0258605123
Fuse- FB32 025860409333
Fuse- FB32 025860408333
Fuse- FB32 0258604123
Fuse- FB32 0258604113
Fuse- FB32 0258604143
Fuse- FB32 0258604133
F33Fuse- FB33 0258605113
Fuse- FB33 0258605123
Fuse- FB33 025860514333
33
3
Fuse- FB33 025860409333
Fuse- FB33 025860408333
F34Fuse- FB34 0258605113
Fuse- FB34 0258605123
Fuse- FB34 025860514333
33
3
Fuse- FB34 025860409333
Fuse- FB34 025860408333
F35Fuse- FB35 0258605143
33
3
F36Fuse- FB36 0258605143
3
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 114
Section G- Blow-Thru Heat Section
Option 3- Electric Heat: Code 04= A AND Code 34 first digit = E
Electric Heat Control Box- 3/05 & Later
160- 320KW Components
460V
575V
460V
575V
460V
575V
460V
575V
460V
575V
Heater KW=
160200240280320
Sch. Part
Part
Sym. Description
Number
PB3 Power Block
until 10/ 06 3 030372744 11
Power Block
until 10/ 06 30303727521
1
1
1
1
1
1
1
Cover- PB3
until 10/ 06 3 349938302 111 1111111
Power Block
10/ 06 & Later 3 030372785 111 1111111
4
PB31 Power Block 1/07 & Later 3
used w/100A, 150A DS3 030372777 1 1 1 1 1 1 1 1 11
used w/250A DS3 030372783 1 1 1 1 1 1 1 1 11
used w/400A DS3 030372785 1 1 1 1 1 1 1 1 11
used w/600A DS3 030372721 5111 1111111
2
DS3 Disconnect Switch
HS3 Switch 033696300 111 1111111
TB11 Terminal Block
until 10/ 06 33499306031 1 1 1 1 1 1 11 1
Terminal Block 10/ 06 & Later 33499306211 1 1 1 1 1 1 11 1
M31 Contactor
until 10/ 06 3 349932301 111 1111111
M32 Contactor
until 10/ 06 3 349932301 111 1111111
M33 Contactor
until 10/ 06 3 349932301111111
Contactor
until 10/ 06 33499322011
1
1
1
M34 Contactor
until 10/ 06 3 349932301111111
Contactor
until 10/ 06 33499322011
1
1
1
M41 Contactor
until 10/ 06 33499323011
1
Contactor
until 10/ 06 33499322011
1
1
1
1
1
M42 Contactor
until 10/ 06 33499323011
1
Contactor
until 10/ 06 33499322011
1
1
1
1
1
M43 Contactor
until 10/ 06 33499323011
1
1
1
1
1
Contactor
until 10/ 06 33499322011
1
M44 Contactor
until 10/ 06 33499323011
1
1
1
1
1
Contactor
until 10/ 06 33499322011
1
M31
M32
M33
M34
M41
M42
M43
M44
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
1/07 & Later 3 349932322 111 1111111
1/07 & Later 3 349932322 111 1111111
1/07 & Later 3 349932322111111
1/07 & Later 33499322211
1
1
1
1/07 & Later 3 349932322111111
1/07 & Later 33499322211
1
1
1
1/07 & Later 33499323221
1
1/07 & Later 33499323211
1
1
1
1
1
1/07 & Later 33499323221
1
1/07 & Later 33499323211
1
1
1
1
1
1/07 & Later 33499323221
1
1
1
1
1
1/07 & Later 33499323211
1
1/07 & Later 33499323221
1
1
1
1
1
1/07 & Later 33499323211
1
Part number is for one section. The number of sections used is determined by the options installed.
See chart 3 pages prior.
3
For units built between 10/1//06 and 12/31/06 contact Daikin Applied to ensure correct part is ordered.
4
Not Used when PB3 Power Block connection is present.
5
Cover— PB31 used with 600A DS3= p/n 349938345.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 115
Section G- Blow-Thru Heat Section
Option 3- Electric Heat: Code 04= A AND Code 34 first digit = E
Electric Heat Control Box- 3/05 & Later
160- 320KW Components, Continued
460V
575V
460V
575V
460V
575V
460V
575V
460V
575V
Heater KW=
160200 240280320
Sch. Part
Part
Sym. Description
Number
FB31 Fuse Block
023780230 1111111111
FB32 Fuse Block
023780230 1111111111
FB33 Fuse Block
023780230 1 1 11 1 1
Fuse Block
023780225 1 1 1 1
FB34 Fuse Block
023780230 1 1 11 1 1
Fuse Block
023780225 1 1 1 1
FB41Fuse Block
0237802301
1
Fuse Block
023780225 1 1 1 1 11
FB42Fuse Block
0237802301
1
Fuse Block
023780225 1 1 1 1 11
FB43Fuse Block
0237802301
1
1
1
1
1
Fuse Block
023780225 1 1
FB44Fuse Block
0237802301
1
1
1
1
1
Fuse Block
023780225 1 1
F31Fuse- FB31
02586041433333
Fuse- FB31
02586041333333
F32Fuse- FB32
02586041433333
Fuse- FB32
02586041333333
F33 Fuse- FB33
025860414 3 3 3
Fuse- FB33
025860413333
Fuse- FB33
025860409 3 3
Fuse- FB33
02586040833
F34 Fuse- FB34
025860414 3 3 3
Fuse- FB34
025860413333
Fuse- FB34
025860409 3 3
Fuse- FB34
02586040833
F41 Fuse- FB41
025860409 3 3 3
Fuse- FB41
025860408333
Fuse- FB41
0258604143
0258604133
Fuse- FB41
F42 Fuse- FB42
025860409 3 3 3
Fuse- FB42
025860408333
Fuse- FB42
0258604143
0258604133
Fuse- FB42
F43 Fuse- FB43
025860409 3
Fuse- FB43
0258604083
Fuse- FB43
025860414333
025860413333
Fuse- FB43
F44 Fuse- FB44
025860409 3
Fuse- FB44
0258604083
Fuse- FB44
025860414333
025860413333
Fuse- FB44
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 116
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Heat Exchangers & Vestibules
500, 640, 650, 790, 800, 1000, 1100, 1400 MBH Furnaces
Code 34= 050**, 064**, 065**, 079**, 080**, 100**, 110**, 140**
Heat
Exchanger
1
21
22
Burner 4
Burner
Control
Box 5
Gas Train 6
Ref Part 500/640 650/790 800/1000 1100/1400Qty.
No.
Description
MBHMBHMBHMBH
1
1
1
1
1
Heat Exch.- Aluminized Sec.C34= ***A**
1
2
2
2
Heat Exch. Kit- S.S. Sec.
C34= ***S** 098322521 098322522 098322523 098322524 21
21 Vestibule055636326055636326055636326055636326 1
22 Vestibule055636322055636323055636324055636325 1
N/S Turbulator058387201058387201058387201058387201 3
N/S= Not shown on diagram.
1
Aluminized Secondary Heat Exchangers are no longer available. Use the comparable Stainless Steel Secondary Kit p/n instead.
2
Kit includes the Heat Exchanger, Flue Front Cover, Flue Back Cover, Inspection Door, and Inspection Door Gasket.
3
Quantity varies depending upon the size of the Heat Exchanger. For 500/640 MBH order 9 pc.; for 650/790 MBH order 12 pc.; for
800/1000 MBH order 15 pc; for 1100/1400 order 22 pc. Note that the required Turbulators are NOT included in the Heat Exchanger Kits.
4
Parts detail follows this section.
5
Parts detail follows Burner section.
6
Parts detail follows Burner Control Box section.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 117
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Heat Exchangers
1500, 2000 MBH Furnaces
Code 34= 150***, 200***
Heat
Exchanger
1
Burner 4
Burner
Control
Box 5
Gas Train 6
RefPart 1500/2000Qty.
No. Description
MBH
1
1
Heat Exchanger- Aluminized Secondary
Code 34= ***A**
1
Heat Exchanger Kit- Stainless Steel Secondary
Code 34= ***S** 098322525 21
N/S Turbulator 058387201 327
N/S= Not shown on diagram.
1
Aluminized Secondary Heat Exchangers are no longer available. Use the comparable Stainless Steel Secondary Kit p/n
instead.
2
Kit includes the Heat Exchanger, Flue Front Cover, Flue Back Cover, Inspection Door, and Inspection Door Gasket.
3
Note that the required Turbulators are NOT included in the Heat Exchanger Kit.
4
Parts detail follows this section.
5
Parts detail follows Burner section.
6
Parts detail follows Burner Control Box section.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 118
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Modulating OR Single Stage Burner:
Code 34= ****A*, ****P*, ****Q*, ****E*, ****R*, ****S*
Diagrams
Burner Control
Box
113
125
102
149
115
109
500- 1000 mbh Burners
119
147
130
114 112
124
110
106
116
122
117
123
111
120
126
105
103
121
127
104
107
108
118
Housing Detail:1100- 2000 mbh
Burners
115
149
102
160
Pilot Valve/Pressure
Regulator Assy.
Detail
112
162
150
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
114
124
116
RPL 7000070 / Page 119
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Modulating OR Single Stage Burner:
Code 34= ****A*, ****P*, ****Q*, ****E*, ****R*, ****S*
Components
Burner Approval Code
Ref Part
C07= EU C07= CC, CD
No. Description
UL/ETL
CSA
102 Burner Housing
500- 1000 MBH Furnace
059362302
059362302
1100- 2000 MBH Furnace
066673702
066673702
103 Scroll
500- 1000 MBH Furnace
035740701
035740701
1100- 2000 MBH Furnace
035740901
035740901
104 Wheel- .5” bore
500- 1000 MBH Furnace
034861102
034861102
1100- 1500 MBH Furnace
034249005
034249005
2000 MBH Furnace
034249004
034249004
105 Motor
500- 1000 MBH Furnace
034249200
034249200
1100- 1500 MBH Furnace
032248600
032248600
2000 MBH Furnace
032248400
032248400
106 Gun Assembly
500 MBH Furnace
034880001
034880001
640, 650 MBH Furnace
034880002
034880002
790, 800 MBH Furnace
034880003
034880003
1000 MBH Furnace
034880004
034880004
1100 MBH Furnace
035721001
035721001
1400 MBH Furnace
035721002
035721002
1500 MBH Furnace
035721003
035721003
2000 MBH Furnace
036235700
036235700
107 Inlet Funnel
500- 1000 MBH Furnace
034743101
034743101
1100- 2000 MBH Furnace
034743102
034743102
108 Fan Guard
034742800
034742800
109 Blast Tube
500- 650 MBH Furnace
034101703
034101703
790- 1000 MBH Furnace
034101707
034101707
1100, 1400 MBH Furnace
034101706
034101706
1500, 2000 MBH Furnace
035164701
035164701
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Qty.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
RPL 7000070 / Page 120
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Modulating OR Single Stage Burner:
Code 34= ****A*, ****P*, ****Q*, ****E*, ****R*, ****S*
Components, Continued
Burner Approval Code
Ref Part
C07= EU C07= CC, CD
No. Description
UL/ETL
CSA
110 Pilot Mixer
500- 1000 MBH Furnace
036516401
036516401
1100- 2000 MBH Furnace
036516402
036516402
111 Pilot Assembly
035019600
035019600
Flame Rod
Code 34 [5th digit]= E, R, S 300032902
300032902
112 Damper Assembly
035721501
048791401
500- 1000 MBH Furnace
1100- 2000 MBH Furnace
035721502
048791402
113 Blast Tube Gasket
034102000
034102000
500- 1000 MBH Furnace
1100, 1400 MBH Furnace
034101900
034101900
1500, 2000 MBH Furnace
034101900
034101900
114 Right Side Damper
500 MBH Furnace
058594301
058594301
640 MBH Furnace
058595201
058595201
650- 1000 MBH Furnace
058594501
058594501
1100 MBH Furnace
059366301
059366301
1400 MBH Furnace
059366201
059366201
1500, 2000 MBH Furnace
059365501
059365501
115 Left Side Damper
500, 640 MBH Furnace
058595001
058595001
650- 1000 MBH Furnace
058594401
058594401
1100 MBH Furnace
059366501
059366501
1400 MBH Furnace
059366401
059366401
1500, 2000 MBH Furnace
059365101
059365101
116 Slide Damper
500 MBH Furnace
058594805
058594815
640 MBH Furnace
058594806
058594816
650 MBH Furnace
058594807
058594817
790 MBH Furnace
058594808
058594818
800 MBH Furnace
058594809
058594819
1000 MBH Furnace
058594810
058594820
1100 MBH Furnace
058594831
058594831
1400 MBH Furnace
058594837
058594837
1500 MBH Furnace
058594843
058594843
2000 MBH Furnace
058594849
058594849
117 Blower Gasket
035019500
035019500
118 Burner Cover
500- 1000 MBH Furnace
033972100
033972100
1100- 2000 MBH Furnace
033973101
033973101
119 Ignition Assembly
500- 1000 MBH Furnace
034742900
034742900
1100- 2000 MBH Furnace
036518500
036518500
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Qty.
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
RPL 7000070 / Page 121
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Modulating OR Single Stage Burner:
Code 34= ****A*, ****P*, ****Q*, ****E*, ****R*, ****S*
Components, Continued
Burner Approval Code
Ref Part
C07= EU C07= CC, CD
No. Description
UL/ETL
CSA
120 Glass Cover
036557000
036557000
121 Glass Cover Support
036009600
036009600
122 Orifice
500 MBH Furnace
058599101
058599101
640 MBH Furnace
058599102
058599102
650 MBH Furnace
058599103
058599103
790 MBH Furnace
058599104
058599104
800 MBH Furnace
058599104
058599104
1000 MBH Furnace
058599201
058599201
1100 MBH Furnace
059364601
059364601
1400 MBH Furnace
059364602
059364602
1500 MBH Furnace
059364603
059364603
123 Clip
034919400
034919400
124 Flange Bearing
034252000
034252000
125 Air Switch Tube
500- 1000 MBH Furnace
034102801
034102801
1100- 2000 MBH Furnace
034102701
034102701
126 Pilot Burner Tube
500- 1000 MBH Furnace
036236100
036236100
1100, 1400 MBH Furnace
036236200
036236200
1500, 2000 MBH Furnace
036519900
036519900
127 Compression Fitting
034097500
034097500
130 Pilot Tube
034102601
034102601
147 Torsion Spring
Not Used
037528600
149 Burner Box Baffle
500- 1000 MBH Furnace
058597902
058597902
1100- 2000 MBH Furnace
059365801
059365801
150 Damper, Slide- Top
1100 MBH Furnace
058594830
Not Used
1400 MBH Furnace
058594836
Not Used
1500 MBH Furnace
058594842
Not Used
2000 MBH Furnace
058594848
Not Used
160 Valve- Pressure Regulator
034077600
034077600
162 Valve- Solenoid
034488400
034488400
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Qty.
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
RPL 7000070 / Page 122
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Hi Turn Down Burner:
Code 34= ****H*, ****T*, ****U*
Diagrams
328
114
102
109
119
358
113
106
116
295
121
120
358
300
118
110
105
310
318
145
117
103
324
375
325
104
107
108
321
322
323
320
144
Orifice, Control Rod, Control Arm,
Linkage, Plate Detail
297
299
110
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 123
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Hi Turn Down Burner
Code 34= ****H*, ****T*, ****U*
Components
Burner Approval Code
Ref Part
C07= EU C07= CC, CD
No. Description
UL/ETL
CSA
102 Burner Housing
500- 1000 MBH Furnace
059862103
059862103
1100- 2000 MBH Furnace
059862133
059862133
103 Scroll
500 thru 800 MBH Furnace
096434806
096434806
1000- 2000 MBH Furnace
059862136
059862136
104 Wheel- .5” bore
500- 800 MBH Furnace
034861102
034861102
1000- 1500 MBH Furnace
034249005
034249005
2000 MBH Furnace
034249004
034249004
105 Motor- .25 HP, 115/60/1
500- 800 MBH Furnace
034249200
034249200
1000- 1500 MBH Furnace
032248600
032248600
2000 MBH Furnace
032248400
032248400
106 Gun Assembly
500 MBH Furnace
096414805
096414805
640, 650 MBH Furnace
096414806
096414806
790, 800 MBH Furnace
096414808
096414808
1000 MBH Furnace
096414810
096414810
1100 MBH Furnace
096414811
096414811
1400 MBH Furnace
096414812
096414812
1500 MBH Furnace
096414813
096414813
2000 MBH Furnace
096414814
096414814
107 Inlet Funnel
500- 800 MBH Furnace
034743101
034743101
1000- 2000 MBH Furnace
034743102
034743102
108 Fan Guard
034742800
034742800
109 Blast Tube
500, 640 MBH Furnace
034101703
034101707
650- 1000 MBH Furnace
034101707
034101707
1100, 4000 MBH Furnace
034101706
034101706
1500, 2000 MBH Furnace
035164701
035164701
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Qty.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
RPL 7000070 / Page 124
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Hi Turn Down Burner
Code 34= ****H*, ****T*, ****U*
Components, Continued
Burner Approval Code
Ref Part
C07= EU C07= CC, CD
No. Description
UL/ETL
CSA
110 Orifice Assembly
500 MBH Furnace
096414705
096414725
640 MBH Furnace
096414706
096414726
650 MBH Furnace
096414707
096414727
790, 800 MBH Furnace
096414708
096414728
1000 MBH Furnace
096414710
096414730
1100 MBH Furnace
096414711
096414731
1400 MBH Furnace
096414712
096414732
1500 MBH Furnace
096414712
096414733
2000 MBH Furnace
096414714
096414734
113 Gasket- Blast Tube
034102000
034102000
500- 1000 MBH Furnace
1100- 2000 MBH Furnace
034101900
034101900
114 Air Box Assy
059862112
059862112
500- 1000 MBH Furnace
1100- 2000 MBH Furnace
059862142
059862142
116 Plate- Actuator Scale
059645001
059645001
117 Gasket- Blower
035019500
035019500
118 Panel- Burner Box Cover
059388501
059388501
500- 1000 MBH Furnace
1100- 2000 MBH Furnace
059649401
059649401
119 Ignition Wire Assy
034742902
034742902
500- 1000 MBH Furnace
1100- 2000 MBH Furnace
036518500
036518500
Flame Rod
059867701
059867701
120 Glass Cover- Burner
036557000
036557000
121 Support- Glass Cover
036009600
036009600
144 Grommet- Flat
060017701
060017701
145 Box- Conduit (500- 800 MBH only)
036558800
036558800
295 Motor- Actuator
047936110
047936110
Until 3/01
3/01 & Later
111047701
111047701
297 Control Arm
059862114
059862114
500- 1000 MBH Furnace
1100- 2000 MBH Furnace
059862144
059862144
299 Control Rod
059861101
059861101
500- 1000 MBH Furnace
1100- 2000 MBH Furnace
059650501
059650501
300 Crank Arm
059645101
059645101
500- 1000 MBH Furnace
1100- 2000 MBH Furnace
023463200
023463200
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Qty.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
RPL 7000070 / Page 125
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Hi Turn Down Burner
Code 34= ****H*, ****T*, ****U*
Components, Continued
Burner Approval Code
Ref Part
C07= EU C07= CC, CD
No. Description
UL/ETL
CSA
310 Extension- Crank Arm
059862110
059862110
318 Bushing- Control Rod
059861301
059861301
320 Linkage
096414901
096414901
321 Plate- Adjustable
500 MBH Furnace
060086401
096422901
640 MBH Furnace
096417701
096417801
650 MBH Furnace
096416301
096416301
790 MBH Furnace
060097101
060097101
800 MBH Furnace
060097101
096422701
1000 MBH Furnace
060092401
060097301
1100 MBH Furnace
096422501
096422501
1400 MBH Furnace (until 7/06)
096422101
096422101
1400 MBH Furnace (7/06 & Later)
096420201
096420201
1500 MBH Furnace
096420201
096420201
2000 MBH Furnace
096420301
096420301
322 Plate- Profile
500 MBH Furnace
060086101
060086101
640 MBH Furnace
096417901
096417901
650 MBH Furnace
096415301
096418001
790 MBH Furnace
096416501
096416501
800 MBH Furnace
060096901
060097001
1000 MBH Furnace
060092601
060097201
1100 MBH Furnace
059648801
096422401
1400 MBH Furnace
096422201
096422301
1500 MBH Furnace
096419801
096419901
2000 MBH Furnace
096419701
096420001
323 Plate- Slide Damper
500 MBH Furnace
060086301
060086301
640, 650 MBH Furnace
096417601
096417601
790, 800, 1000 MBH Furnace
060092501
060092501
1100, 1400, 1500 MBH Furnace
059649201
059649201
2000 MBH Furnace
096420401
096420501
324 Box- Air
500- 1000 MBH Furnace
060092201
060092201
1100- 2000 Furnace
060092202
060092202
325 Gasket- Air Box
060092301
060092301
500- 1000 MBH Furnace
1100- 2000 Furnace
096421701
096421701
328 Grommet
000498100
000498100
358 Bearing- Sleeve
046761000
046761000
375 Grommet
500- 1000 MBH Furnace
059988700
059988700
1100- 2000 Furnace
059988800
059988800
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Qty.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
RPL 7000070 / Page 126
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Single Stage OR Modulating Burner Controls:
Code 34= ****A*, ****P*, ****Q*, ****E*, ****R*, ****S* AND
MicroTech OR No Controls (Code 12= 1M, 2M, 4M, 5M, YC, YM)
Until 6/95
26
28
32
25
FSG Detail
26
38
31
37
13
13A
25
28
33
26
35
34
29
1100- 2000
MBH only
30
Ref. Sch. Part
Furnace MBH
No. Sym. Description
500- 1000
1100- 2000 Qty.
13 GV1 Valve- Gas Solenoid
034488400 034488400
1
13A
Valve- Pressure Regulator
034077600 034077600
1
25 FSG Timer- Flame Safeguard, 90 Second
Modulating Burners/ UL Units
065824402 065824402
1
FSG Timer- Flame Safeguard, 30 Second
Modulating Burners/ CSA Units
065824401 065824401
1
All Single Stage Burners
065824401 065824401
1
26 FSG Flame Safeguard- Less Timer
065824201 065824201
1
28
Subbase- Flame Safeguard
065824301 065824301
1
29
S3
Switch- Furnace On/Off
033536700 033536700
1
30 LT2 Light- Furnace On
034251301 034251301
1
30 LT3 Light- Pilot Gas Valve On
034251301 034251301
1
30 LT4 Light- Main Gas Valve On
034251301 034251301
1
31
IT
Transformer- Ignition, 180 KVA
034482600 034482600
1
32
AS
Switch- Air Pressure, Blower
033003800 033003800
1
33 FLC Control- Fan Limit
034082100 034082100
1
34 M29 Relay- Motor 1
027400700027400700 1
35 R23 Relay- Gas Heat Modulating Valve
044465500 044465500
1
37 R21 Relay- Gas Heat, 100% Outside Air, SPST
027400700 027400700
1
38 R22 Relay- Gas Heat, 100% Outside Air, DPDT
019643000 019643000
1
1
1100- 2000 MBH units only.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 127
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Single Stage OR Modulating Burner Controls:
Code 34= ****A*, ****P*, ****Q*, ****E*, ****R*, ****S* AND
MicroTech OR No Controls (Code 12= 1M, 2M, 4M, 5M, YC, YM)
7/95 thru 1/01
FSG Detail
24
Panel Detail
30
23
64
31
39
26
62
25
R
21
65
R
22
M
29
34
32
29
63
R
23
GV1
TB 11
11
Ref Sch.
Part
Furnace MBH:
No. Sym.
Description 500- 1000
1100- 2000 Qty.
11 GV1
Pressure Reg. Assy 039742000
039742000
1
Valve Only
034077600
034077600
1
Solenoid Valve
034488400
034488400
1
23
Flame Safeguard Subbase 073300701
073300701
1
24 FSG
Flame Safeguard- FSG 073300803 1073300803 11
25
Amplifier- FSG 073300901
073300901
1
26
Flame Safeguard T.D. 90 Sec.
Modulating Burner/UL Units 073301002
073301002
1
Flame Safeguard T.D. 30 Sec.
Modulating Burner/CSA 073301001 073301001
1
All Single Stage Burners 073301001
073301001
1
29
S3
Toggle Switch- 4PST 033536700
033536700
1
30
IT
Ignition Transformer 034482600
034482600
1
31
AS
Air Switch- Gas Burner 033003800
033003800
1
32 FLC
Fan Limit Control 073337102
073337102
1
34 TB11
Terminal Block- 9 Pole 015998109
015998109
1
39
Fitting 067297701 067297701
1
62 M29
Contactor- Motor
Not Used
027400700
1
63 R23
Pilot Relay- DPDT 044465500
044465500
1
64 R21
Relay- 100% O.A. (Code 20= A*) 027400700 2027400700 21
65 R22
Relay- 100% O.A. (Code 20= A*) 019643000 2019643000 21
The original Flame Safeguard, p/n 073300801 is obsolete and no longer available. For units built 7/95 thru 1/01 use p/n 073300803.
When replacing 073300801 minor field modifications are required for proper installation and operation.
2
Used on CSA (Code 07= CC, CD) units only.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 128
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Single Stage OR Modulating Burner Controls:
Code 34= ****A*, ****P*, ****Q*, ****E*, ****R*, ****S* AND
MicroTech II OR No Controls (Code 12= *D, *S, YM, YC)
Diagram
1/01 & Later
FSG Detail
25
24
41
30
31
26
39
63
27
22
61
32
34
29
25
Gas
Control
Box
11
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 129
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Single Stage OR Modulating Burner Controls:
Code 34= ****A*, ****P*, ****Q*, ****E*, ****R*, ****S* AND
MicroTech II OR No Controls (Code 12= *D, *S, YM, YC)
Components
1/01 & Later
Ref Sch.
Part
Furnace MBH:
No. Sym.
Description 500- 1000
1100- 2000 Qty.
11 GV1
Pressure Reg. Assy 039742000
039742000
1
Valve Only 034077600
034077600
1
Solenoid Valve 034488400
034488400
1
22
Support 059388701 059388701
1
24
Flame Safeguard Subbase 073300702
073300702
1
25 FSG
Flame Safeguard 4/07 & Later 1073300803 073300803 1
26
Amplifier 073300901 073300901
1
27
Flame Safeguard T.D. 90 Sec.
UL Units 073301002
073301002
1
Flame Safeguard T.D. 30 Sec.
CSA Units 073301001
073301001
1
29
S3
Toggle Switch- 4PST: S3 033536700
033536700
1
30
IT
Ignition Transformer 034482600
034482600
1
31
Air Switch- Gas Burner 033003800
033003800
1
32 FLC
Fan Limit Control 9/08 & Later 2193423703 193423703 1
34 TB11
Terminal Block- 14 Pole 015998114
015998114
1
39
Fitting 067297701 067297701
1
41
Bushing 001242600 001242600
3
61 R20
Relay- SPDT
Code 12= *D, *S 026213000
026213000
1
61 R20
Relay (Before 1/10)
Code 12= YM, YC 061019403
061019403
1
N/S R20A
Relay (1/01 & Later)
Code 12= YM, YC 349934764
349934764
1
N/S Relay Socket 349964702
349964702
1
63 R23
Relay (Before 1/10)
Code 12= YM, YC 019643000
019643000
1
N/S R23A Pilot Relay (1/01 & Later, ETL only) C12= YM, YC 349934764
349934764
1
N/S Mounting Adapter 349964702
349964702
1
N/S R23B
Pilot Relay (1/01 & Later)
Code 12= YM, YC 193454702
193454702
1
N/S Relay Socket 193454801
193454801
1
62 M29
Contactor- Motor Not Used
027400700
1
63 R23
Pilot Relay- DPDT 019643000
019643000
1
N/S= Not shown on diagram.
1
The original part for units built 4/07 & Earlier is obsolete and no longer available. When replacing an original Flame Safeguard minor
field modifications will be required for proper installation and operation.
2
The original part for units built 9/08 & Earlier is obsolete and no longer available. When replacing an original Fan Limit Control minor
field modifications will be required for proper installation and operation.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 130
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Modulating Burner Controls: Code 34= ****E*, ****R*, ****S* AND
MicroTech III Controls (Code 12= LE, LF, BE, BF, EE, EF, SE, SF)
M29
64
R23B 63
R23A 62
R20A
61
30 IT
32
FLC
31
34
TB11
Gas
Control
Box
29 S3
25
24
26
11
25 FSG
See Detail
27
FSG Detail
Gas Valve Detail
Ref Sch.
PartFurnace MBH:
No. Sym.
Description 500- 1000 1100- 2000 Qty.
11 GV1
Pressure Reg. Assy 039742000 039742000
1
Valve Only
034077600
034077600
1
Solenoid Valve
034488400
034488400
1
24
Flame Safeguard Subbase 073300702 073300702
1
25 FSG
Flame Safeguard 073300803 073300803
1
26
Amplifier 073300901 073300901
1
27
Flame Safeguard T.D. 90 Sec.
UL Units 073301002 073301002
1
Flame Safeguard T.D. 30 Sec.
CSA Units 073301001 073301001
1
29
S3
Toggle Switch- 4PST: S3 033536700 033536700
1
30
IT
Ignition Transformer 034482600 034482600
1
31
AS
Air Switch- Gas Burner 033003800 033003800
1
32 FLC
Fan Limit Control 193423703 193423703
1
34 TB11
Terminal Block- 14 Pole 015998114 015998114
1
Jumper- Terminal Block 001354100 001354100
1
61 R20A
Relay- High Amp
DPDT/120V 349934764 349934764
1
62 R23A
Relay- High Amp
DPDT/120V 349934764 349934764
1
63 R23B
Relay- Low Amp
DPDT/120V 193424341 193424341
1
64 M29
Contactor- Motor
DPDT/120V Not Used 349934764
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 131
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Hi Turn Down Burner Controls: Code 34= ****H*, ****T*, ****U* AND
MicroTech II OR No Controls (Code 12= *D, *S, YM)
R22
TD10
TB11 34
66
65
41
30
39
FSG Detail
R20
24
61
22
25
31
R23 63
32
26
27
64
R21
23
29
33
42
62
1100- 2000 MBH
Panel Detail
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 132
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Hi Turn Down Burner Controls: Code 34= ****H*, ****T*, ****U* AND
MicroTech II OR No Controls (Code 12= *D, *S, YM)
Components
Ref Sch.
PartFurnace MBH
Qty.
No. Sym.
Description 500- 1000 1100- 2000
22
Support 059388701 059388701 1
23
Support 059388601 059649701 1
24
Subbase- Flame Safeguard 073300702 073300702
1
25 FSG
Flame Safeguard
4/07 & Later 1073300803 073300803 1
26
Amplifier 073300901 073300901 1
27
Time Delay- Flame Safeguard 073301003 073301003
1
29
S3
Switch- Toggle 033536700 033536700
1
30
IT
Transformer- Ignition 034482600 034482600
1
31
AS
Switch- Air 033003800 033003800
1
32 FLC
Control- Fan Limit
Until 9/08 073337102 073337102
1
Control- Fan Limit
9/08 & Later 193423703 193423703
1
33 LS1/LS2 Switch- Limit 059975301 059975301
2
34 TB11
Terminal Block 015998114 015998114
1
39
Fitting 067297701 067297701 1
41
Bushing 001242600 001242600 1
42
Bushing 049751901 049751901 1
61 R20
Relay
120V/DPDT- MicroTech Units Until 1/01 019643000 019643000
1
24V/DPDT- MicroTech II Units 1/01 and later 016508002 016508002
1
N/S R20A
Relay 120V 1/01 & Later 349934764 349934764
1
N/S Mounting Adapter 349964702 349964702
1
N/S R20B
Relay 120V 1/01 & Later 193454703 193454703
1
Relay Socket
193454801
193454801
1
62 M29
Contactor- Motor Not Used
027400700
1
63 R23
Relay- 120V/DPDT Until 3/10 019643000 019643000
1
N/S R23B
Relay- 120VSPST 3/10 & Later 193454703 193454703
1
Relay Socket
193454801
193454801
1
64 R21
Relay- 120V/DPDT Until 3/10 019643000 019643000
1
64 R21
Relay- 120V/DPDT 3/10 & Later 193454703 193454703
1
Relay Socket
193454801
193454801
1
65 R22
Relay- 120VSPST Until 3/10 027400700 027400700
1
65 R22
Relay- 120VSPST 3/10 & Later 349964764 349964764
1
N/S Mounting Adapter 349964702 349964702
1
66 TD10
Relay- Time Delay 20.0 Sec. 028210106 028210106
1
1
The original Flame Safeguard, p/n 073300801, used 3/07 & Earlier, is obsolete and no longer available. For units built 3/07 &
Earlier, use p/n 073300803. When replacing 073300801 minor field modifications are required for proper installation and operation.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 133
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Hi Turn Down Burner Controls: Code 34= ****H*, ****T*, ****U* AND
MicroTech III Controls (Code 12= *E, *F)
M29
30 IT
66
R23B 65
R23A 64
R21 63
32 FLC
R20B 62
R20A 61
34 TB11
LS1
LS2
AS 31
33 LS_
25
24
29 S3
26
27
FSG Detail
FSG 25
See Detail
Ref Sch.
Part Furnace MBH
Qty.
No. Sym.
Description 500- 1000 1100- 2000
24
Subbase- Flame Safeguard 073300702 073300702
1
25 FSG
Control- Flame Safeguard 073300803 073300803
1
26
Amplifier 073300901 073300901 1
27
Time Delay- Flame Safeguard 073301002 073301002
1
29
S3
Switch- Toggle 033536700 033536700
1
30
IT
Transformer- Ignition 034482600 034482600
1
31
AS
Switch- Air 033003800 033003800
1
32 FLC
Control- Fan Limit 193423703 193423703
1
33 LS1/LS2 Switch- Limit 059975301 059975301
2
34 TB11
Terminal Block 015998114 015998114
1
Jumper- Terminal Block 001354100 001354100
1
61 R20A
Relay- High Amp
DPDT/120V 349934764 349934764
1
62 R20B
Relay- Low Amp
DPDT/120V 193424341 193424341
1
63 R21
Relay- Low Amp
DPDT/120V 193424341 193424341
1
64 R23A
Relay- High Amp
DPDT/120V Not Used
349934764
1
65 R23B
Relay- Low Amp
DPDT/120V Not Used
193424341
1
66 M29
Relay- High Amp
DPDT/120V Not Used
349934764
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 134
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Single Stage OR Modulating Burner:
Code 34= ****A*, ****E*, ****P*, ****Q*, ****R*, ****S*
Gas Train- Inlet
Until 6/96
206
228
226
205
232
234
Ref.
Heat Exch.
No. Size/MBH
205
500- 2000
Part
Description
Valve- Manual, Gas
Part
Number
034077300
Qty.
1
206
500- 2000
Tube
036517130
1
226
500
640- 1000
1100- 1500
2000
Shut off Valve- 1.00” NPT
Shut off Valve- 1.25” NPT
Shut off Valve- 1.50” NPT
Shut off Valve- 2.00” NPT
034077102
034077103
034490205
034490206
1
1
1
1
228
500
640, 650
790, 800
1000, 1100
1500, 2000
Regulator Valve- 1.00” NPT
Regulator Valve- 1.25” NPT
Regulator Valve- 1.25” NPT
Regulator Valve- 1.25” NPT
Regulator Valve- 1.25 NPT
036619914
036619923
036619922
036619921
034077900
1
1
1
1
1
232
500
640- 1500
2000
Union- 1.00” NPT
Union- 1.25” NPT
Union- 2.00” NPT
027666800
030731000
031318500
1
1
1
234
500
640- 2000
Shut off Valve- 1.00” NPT
Shut off Valve- 1.25” NPT
046747803
046747804
1
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” .31 Orifice
.38 Orifice
.50 Orifice
.62 Orifice
.50 Vent
Rev. AG 01/15
RPL 7000070 / Page 135
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Single Stage OR Modulating Burner:
Code 34= ****A*, ****E*, ****P*, ****Q*, ****R*, ****S*
Gas Train- Inlet
6/96 & Later
Units without Pressure Regulator Valve:
Code 34= ****A*, ****E*
RefPart
No. Description
205 Shutoff Valve
500- 2000 MBH
234 Gas Valve
500 MBH
640- 1000 MBH
1100- 1500 MBH
2000 MBH
234 205
205 234
500- 1500 MBH
2000 MBH
Part
Number
Qty.
034077300
1
059468802
059468803
059468804
059468805
1
1
1
1
Units with Pressure Regulator Valve:
Code 34= ****P*, ****Q*, ****R*, ****S*
228
228
228
234
205
234
500, 640, 650, 800 MBH
Furnaces
205
1000 MBH
Furnaces
205
228
228
234
234 205
205 234
1100, 1400 MBH
Furnaces
1500 MBH
Furnaces
Ref PartPressure Regulator
No. Description
2- 3 PSI 5- 10 PSI
205 Shutoff Valve
034077300 034077300
228 Pressure Regulator
500 MBH
036619914 036619915
640, 650 MBH
036619923 036619925
790, 800 MBH
036619922 036619924
1000 MBH
073387201 036619923
1100 MBH
073387302 036619923
1400 MBH
073387301 073387303
1500 MBH
073387301 073387302
2000 MBH
073387306 073387301
234 Gas Valve
500 MBH
073387402 073387402
640- 1500 MBH
073387403 073387403
2000 MBH
073387404 073387403
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
2000 MBH
Furnaces
Qty.
1
1
1
1
1
1
1
1
1
1
1
1
RPL 7000070 / Page 136
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Hi Turn Down Burner:
Code 34= ****H*, ****T*, ****U*
Gas Train- Inlet
CSA Units— Code 07= CC, CD
Units without Pressure Regulator Valve: Code 34= ****H*
Back Wall of
Vestibule
RefPart
No. Description
226 Gas Valve
292
500 MBH
640- 1000 MBH
1100- 1500 MBH
2000 MBH
Combination
292 Combination Valve
Valve Detail
226
Part
Number
Qty.
059468802
059468803
059468804
059468805
073336504
1
1
1
1
1
Units with Pressure Regulator Valve: Code 34= ****T*, ****U*
Back Wall of
Vestibule
232
226
292
Combination
Valve Detail
Ref PartPressure Regulator
No. Description
2- 3 PSI 5- 10 PSI
226 Shutoff Valve
500 MBH
073387402 073387402
640- 1500 MBH
073387403 073387403
2000 MBH
073387404 073387403
232 Pressure Regulator
500 MBH
036619914 036619915
640, 650 MBH
036619923 036619925
790, 800 MBH
036619922 036619924
1000 MBH
073387201 036619923
1100 MBH
073387202 036619923
1400 MBH
073387301 073387303
1500 MBH
073387301 073387302
2000 MBH
073387306 073387301
292 Valve- Combination
073336504 073336504
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Qty.
1
1
1
1
1
1
1
1
1
1
1
1
RPL 7000070 / Page 137
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Hi Turn Down Burner: Code 34= ****H*, ****T*, ****U*
Gas Train- Inlet
UL Units— Code 07= EU
Units without Pressure Regulator Valve:
Code 34= ****H*
226
RefPart
No. Description
226 Gas Valve
400, 500 MBH
640- 1000 MBH
1100- 1500 MBH
2000 MBH
Part
Number
Qty.
059468802
059468803
059468804
059468805
1
1
1
1
Units with Pressure Regulator Valve:
Code 34= ****T*, ****U*
232
226
Ref PartPressure Regulator
No. Description
2- 3 PSI 5- 10 PSI
226 Shutoff Valve
500 MBH
073387402 073387402
640- 1500 MBH
073387403 073387403
2000 MBH
073387404 073387403
232 Pressure Regulator
500 MBH
036619914 036619915
640, 650 MBH
036619923 036619925
790, 800 MBH
036619922 036619924
1000 MBH
073387201 036619923
1100 MBH
073387202 036619923
1400 MBH
073387301 073387303
1500 MBH
073387301 073387302
2000 MBH
073387306 073387301
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Qty.
1
1
1
1
1
1
1
1
1
1
1
RPL 7000070 / Page 138
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Single Stage OR Modulating Burner:
Code 34= ****A*, ****E*, ****P*, ****Q*, ****R*, ****S*
Gas Train- Controls: GV2, VM1
Until 6/96
249
250
248
253
Ref.
No.
248
249
Heat Exch.
Size/MBH
500
500
640- 1000
640- 1000
1100- 2000
1100- 1500
2000
500- 2000
Part
Description
Gas Valve, Body- 1.00” IPS
CSA Units
Gas Valve, Diaphragm- 1.00” IPS
UL Units
Gas Valve, Body- 1.25” IPS
CSA Units
Gas Valve, Diaphragm- 1.25” IPS UL Units
Gas Valve, Body- 2.00” IPS
CSA Units
Gas Valve, Diaphragm- 1.50” IPS
UL Units
Gas Valve, Diaphragm- 2.00” IPS UL Units
Part
Number Qty.
041768902
1
034271802
1
041768903
1
034271803
1
041768905
1
034271804
1
034271805
1
Actuator 034490100
CSA Units
1
250
All
Orifice0344878001
253
500
Regulator Valve Assembly 1
500
640- 1000
640- 800
1000
1100- 1500
2000
CSA Units
Regulator Valve UL Units
Regulator Valve
CSA Units
Regulator Valve
UL Units
Regulator Valve
UL Units
Regulator Valve
Regulator Valve 042052800 11
034078100
034077804
034077801
034077804
034077802
034077803
1
1
1
1
1
1
Regulator Valve Assembly Assy.= 034078100 Valve & 041121802 Spring.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 139
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Single Stage OR Modulating Burner:
Code 34= ****A*, ****E*, ****P*, ****Q*, ****R*, ****S*
Gas Train- Controls: GV2, GV3
UL Units— Code 07= EU, YU
6/96 & Later
Gas Controls: 500- 2000 MBH Furnace
UL Approved
500- 2000 MBH
Furnaces
UL Approved
(Code 07= EU, YU)
261
256
255
253
GV2
248
GV3
248
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Ref Part
No. Description
248 Gas Valve- GV2, GV3
500 MBH
640- 1000 MBH
1100- 1500 MBH
2000 MBH
253 Pressure Regulator
500 MBH
640- 1000 MBH
1100- 1500 MBH
2000 MBH
255 Junction Box
256 Junction Box Cover
261 Gas Pipe
Modulating Burner
500 MBH
640 MBH
650, 790 MBH
800, 1000 MBH
1100, 1400 MBH
1500 MBH
2000 MBH
Single Stage Burner
500 MBH
640 MBH
650, 790 MBH
800 MBH
1000 MBH
1100, 1400 MBH
1500 MBH
2000 MBH
Rev. AG 01/15
Part
Number Qty.
073387801
073387802
073387803
073387804
2
2
2
2
034078100
034077804
034077802
034077803
020766100
000127300
1
1
1
1
1
1
055964002
055964108
055964103
055964102
031326400
056010902
056011208
1
1
1
1
1
1
1
055964003
055964104
055964117
055964107
055964108
056010902
056010903
056011002
1
1
1
1
1
1
1
1
RPL 7000070 / Page 140
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Single Stage OR Modulating Burner:
Code 34= ****A*, ****E*, ****P*, ****Q*, ****R*, ****S*
Gas Train- Controls: GV2, VM1
CSA Units— Code 07= CC, CD
6/96 & Later
Gas Controls: 500- 2000 MBH Furnace
CSA Approved
500- 2000 MBH
Furnaces
CSA Approved
(Code 07= CC, CD) 249
261
253
GV2
248
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” RefPart
No. Description
248 Gas Valve Body- GV2
500 MBH
640- 1000 MBH
1100- 2000 MBH
249 Actuator- VM1
253 Pressure Regulator
500 MBH
640- 1000 MBH
1100- 1500 MBH
2000 MBH
261 Gas Pipe
Modulating Burner
500 MBH
640 MBH
650, 790 MBH
800, 1000 MBH
1100, 1400 MBH
1500 MBH
2000 MBH
Single Stage Burner
500 MBH
640 MBH
650, 790 MBH
800, 1000 MBH
1100, 1400 MBH
1500 MBH
2000 MBH
Rev. AG 01/15
Part
Number Qty.
041768902
041768903
041768905
034490101
1
1
1
1
034078100
034077804
034077802
034077803
1
1
1
1
055964202
055964308
055964302
056011101
056011104
056011105
056011207
1
1
1
1
1
1
1
055964203
055964303
055964307
055964306
056011105
056011106
056011205
1
1
1
1
1
1
1
RPL 7000070 / Page 141
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Hi Turn Down Burner:
Code 34= ****H*, ****T*, ****U*
Gas Train- Controls: GV1, GV4, GV5, GV6, GV7, GV8
UL Units— Code 07= EU, YU
500- 650 MBH
Furnaces
UL (C07= EU, YU)
254
790- 1000 MBH
Furnaces
UL (C07= EU, YU)
1100 MBH
Furnaces
UL (C07= EU, YU)
GV4
254
GV5
GV4
GV1
254
GV1
254
254
GV6
GV4
GV5
GV1
254
1400, 1500 MBH
Furnaces
UL (C07= EU, YU)
254
254
GV7
254
GV6
GV5
254
GV4
GV1
2000 MBH
Furnaces
UL (C07= EU, YU)
254
254
GV7
GV6
254
GV5
254
254
GV4
GV8
254
GV1
254
RefPart
No. Description
254 Gas Valve- GV1, GV4
400- 650 MBH
Gas Valve- GV1, GV4, GV5
790- 1000 MBH
Gas Valve- GV1, GV4, GV5, GV6
1100 MBH
Gas Valve- GV1, GV4, GV5, GV6, GV7
1400, 1500 MBH
Gas Valve- GV1, GV4, GV5, GV6, GV7, GV8
2000 MBH
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Part
Number Qty.
073336504 2
073336504 3
073336504 4
073336504 5
073336504 6
RPL 7000070 / Page 142
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Hi Turn Down Burner:
Code 34= ****H*, ****T*, ****U*
Gas Train- Controls: GV2, GV4, GV5, GV6, GV7, GV8, GV9, VM1
CSA Units— Code 07= CC, CD
500- 650 MBH Furnaces
CSA (C07= CC, CD)
GV5 254
254
GV4 254
GV5
GV2
247
GV2
246
2000 MBH Furnaces
CSA (C07= CC, CD)
254
GV2
247
246
GV6 254
GV8
GV5
GV7
254
GV4
254
254
246
254
254
GV4
247
1400, 1500 MBH Furnaces
CSA (C07= CC, CD)
GV8
GV5
GV6
254
GV4 254
GV2
246
254
254
254 GV7
GV6
254
247
1100 MBH Furnaces
CSA (C07= CC, CD)
790- 1000 MBH Furnaces
CSA (C07= CC, CD)
247
GV9
GV2
246
254
254
GV7
GV6
254
GV5
GV4
254
RefPart
Furnace
Part
No. Description
Size Number Qty.
246 Gas Valve Body- GV2
400, 500 MBH 041768902 1
Gas Valve Body- GV2
640- 1000 MBH 041768903 1
Gas Valve Body- GV2
1100- 2000 MBH 041768905 1
247 Actuator- VM1
until 11/00 034490100 1
11/00 & Later 111047401 1
254 Gas Valve- GV4, GV5
400- 650 MBH 073336504 2
Gas Valve- GV4, GV5, GV6
790- 1000 MBH 073336504 3
Gas Valve- GV4, GV5, GV6, GV7
1100 MBH 073336504 3
Gas Valve- GV4, GV5, GV6, GV7 ,GV8
1400, 1500 MBH 073336504 3
Gas Valve- GV4, GV5, GV6, GV7, GV8, GV9
2000 MBH 073336504 3
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 143
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Gas Train- Outlet
Single Stage Burners
Code 34= ****A*, ****P*, ****Q*
275
283
275
283
800, 1000
MBH UL
500- 790 MBH
800, 1000 MBH CSA
1100- 2000 MBH
275
283
RefPart
No. Description
275 Pipe w/ Valve Mount
500 MBH
640- 1000 MBH
1100, 1400 MBH
1500, 2000 MBH
283 Shutoff Valve 1
500 MBH
640- 800 MBH
1000 MBH UL
1000 MBH CSA
1100- 1500 MBH
2000 MBH
1
Modulating Burners
500, 640 MBH
275
277
283
Actuator & LinkageSee next page
277
275
650- 2000 MBH
1
Actuator & LinkageSee next page
283
Qty.
035019800
036235500
035019900
036235600
1
1
1
1
059468802
059468803
058968804
059468803
059468804
059468805
1
1
1
1
1
1
Part
Number
Qty.
035019800
036235500
035019900
036235600
1
1
1
1
034488303
034488304
034488305
1
1
1
059468802
059468803
058968804
059468803
059468804
059468805
1
1
1
1
1
1
See note below.
RefPart
No. Description
275 Pipe w/ Valve Mount
500 MBH
640- 1000 MBH
1100, 1400 MBH
1500, 2000 MBH
277 Butterfly Valve
500 MBH
640- 1400 MBH
1500, 2000 MBH
283 Shutoff Valve 1
500 MBH
640- 800 MBH
1000 MBH UL
1000 MBH CSA
1100- 1500 MBH
2000 MBH
Code 34= ****E*, ****R*, ****S*
Part
Number
Units built prior to 1998 may use a different shut off valve— UL
Units: 500 MBH p/n 034077102; 640/650/790/800/1000 MBH
p/n 034077103; 1100/1400/1500 MBH p/n 034490205; 2000
MBH p/n 034490206— CSA Units: 500 MBH p/n 046747803;
640/650/790 MBH p/n 046747804; 800/1000/1100/1400/1500
MBH p/n 046747805; 2000 MBH p/n 046747806. Applies to both
Single Stage and Modulating Burners.
Hi Turn Down Burners
Code 34= ****H*, ****T*, ****U*
RefPart
No. Description
275 Gas Valve
500 MBH
640- 1000 MBH
1100- 1500 MBH
2000 MBH
650, 2000
MBH
275
500, 640
MBH
275
790- 1500
MBH
Part
Number
Qty.
059468802
059468803
059468804
059468805
1
1
1
1
275
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 144
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Gas Train- Damper Linkage
Single Stage Burners
Code 34= ****A*, ****P*, ****Q*
UL Units (Code 07= EU, YU)
296
297
RefPart
No. Description
296 Crank Arm Bracket
297 Crank Arm
Part
Number Qty.
036519800 1
034250600 1
RefPart
No. Description
296 Damper Stop
297 Crank Arm
298 Linkage- Ball Joint
299 Damper Rod
500 MBH
640- 1400 MBH
1500, 2000 MBH
300 Crank Arm
Part
Number Qty.
037265500 1
034250600 1
034250500 2
CSA Units (Code 07= CC, CD)
300
297
296
298
299
056040201
056040202
056040203
023680400
1
1
1
2
298
300
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 145
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Gas Train- Damper Linkage
Modulating Burners w/ VM1 Actuator
Code 34= ****E*, ****R*, ****S*
Until 4/96
(Link Rods and Clips come with Modulator Valve)
299
295
297
298
Ref.
Heat Exch.
No. Size/MBH
295
All
All
297 500-1000, 2000
1100- 1500
298
All
299 200- 320, 500
400, 640-1000
500
640- 2000
300
All
300
Part
Description
Act. w/Aux. Switch- 120V 16W
CSA Units
Actuator- 120V 16W UL Units
Crank Arm Assy
Crank Arm Assy
Ball Joint
Control Rod
Control Rod
Control Rod
Control Rod
Crank Arm
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Part
Number Qty.
047936109
1
047936110
1
034715100
1
034250600
1
034250500
2
034844500
1
036519100
1
034844500
1
036519100
1
023463200
1
RPL 7000070 / Page 146
Section G- Blow-Thru Heat Section
Option 4- Gas Heat: Code 04= A
Gas Train- Damper Linkage
Modulating Burners w/ VM1 Actuator
Code 34= ****E*, ****R*, ****S*
4/96 & Later
Burner
Box
297
295
Butterfly Valve
(see previous page)
Burner
Box
297
295
Butterfly Valve
(see previous page)
311
311
298
298
VM1
Actuator
300
300
301
299
310
UL Units
299
Transformer
Switch Kit
CSA Actuator Detail
310
CSA Units
Ref Part
Furnace MBH
No. Description 500- 650 790- 1000 1100, 1400 1500, 2000 Qty.
295 Actuator Motor
VM1
Units w/ MicroTech Controls
UL Units
Until 3/01 047936110 047936110 047936110 047936110 1
UL Units
3/01 & Later 111047701 111047701 111047701 111047701 1
CSA Units
Until 3/01 059403184 3 059403184 3 059403184 3 059403184 31
CSA Units
3/01 & Later 091688001 2091688001 2091688001 2091688001 21
Units w/ No Temp. Ctl. (Code 12= YC)
UL Units
Until 10/06 066534804 066534804 066534804 066534804 1
UL Units
10/06 & Later 063483422 1063483422 1063483422 1063483422 11
CSA Units 063483422 1063483422 1063483422 1063483422 11
297Crank Arm034250600034250600034250600 034250600 1
298Ball Joint034250500034250500034250500 034250500 2
299Linkage Arm058598401058598401059371601 059368701 1
300Crank Arm023463200023463200023463200 023463200 1
301 Extension- Arm
CSA Units Only 098735201 098735201 098735201 098735201 1
310 Air Damper Lever Arm 059365001 058598101 058598101 Not Used 1
311 Gas Valve Arm 058598601 058598601 058598601 058598601 1
Assembly part number. Motor only is p/n 113105101 (066534803 was used until 8/06), and Interface Kit only is p/n 067112501.
Assembly part number. Motor only is p/n 111047701, and Switch Kit only is p/n 060009101.
3
Assembly part number. Motor only is p/n 060009601, Transformer is p/n 067112601, and Switch Kit is p/n 060009101.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 147
Section G- Blow-Thru Heat Section
Option 4- Gas Heat w/ 320MBH thru 1000 MBH Furnace
C04= A & C34= 050***,064***,065***,079***,080***, 100***, 110***, 140***
Cabinet Doors, Gasketing, Hardware, & Flue Box Mounting
Until 8/03 1
650
652
665 664
669
663
661
668
673
667
668
RefPart
No. Description
650 Door Assembly
500, 640 MBH
650, 790 MBH
800, 1000 MBH
1100, 1400 MBH
652 Inspection Door
661 Mount- Flue Box 500, 640 MBH
650, 790 MBH
800, 1000 MBH
1100, 1400 MBH
663 Baffle
664 Sleeve Bearing
665 Door Catch
667 Gasket
668 Gasket
669 Gasket
673 Hinge
1
Part
Number
Qty.
055632637
055632638
055632639
096181431
034095801
1
1
1
1
1
055972801
055977901
055980501
055970401
096427701
047138507
055502602
055921409
055921410
031949200
034005900
1
1
1
1
1
3
3
2
2
1
2
The cabinet components shown changed when the new design Heat Exchanger was installed in August, 2003. However, if an original design
Heat Exchanger has been replaced with a current design Heat Exchanger the original Flue Box mounting hardware was also replaced.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 148
Section G- Blow-Thru Heat Section
Option 4- Gas Heat w/ 320MBH thru 1000 MBH Furnace
Code 04= A & Code 34= 050***,064***,065***,079***,080***, 100***, 110***, 140***
Cabinet Doors, Gasketing, Hardware, & Flue Box Mounting
8/03 & Later 1
652
650 669
663
661
665 664
668
667
673
668
658
RefPart
No. Description
650 Door Assembly
500, 640 MBH
650, 790 MBH
800, 1000 MBH
1100, 1400 MBH
652 Inspection Door
658 Back- Flue Box
500, 640 MBH
650, 790 MBH
800, 1000 MBH
1100, 1400 MBH
661 Angle- Flue Box 500, 640 MBH
650, 790 MBH
800, 1000 MBH
1100, 1400 MBH
663 Drip Shield
664 Sleeve Bearing
665 Door Catch
667 Gasket
668 Gasket
669 Gasket
673 Hinge
1
Part
Number
Qty.
096181451
096181442
096181453
096181444
034095801
1
1
1
1
1
403399801
403400201
403400401
403400701
1
1
1
1
403399901
403400101
403400501
403400801
033487300
047138507
055502602
055921409
055921410
031949200
034005900
1
1
1
1
1
3
3
2
2
1
2
The cabinet components shown changed when the new design Heat Exchanger was installed in August, 2003. However, if an original design
Heat Exchanger has been replaced with a current design Heat Exchanger the original Flue Box mounting hardware was also replaced.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 149
Section G- Blow-Thru Heat Section
Option 4- Gas Heat w/ 1500 MBH, 2000 MBH Furnace
Code 04= A AND Code 34= 150***, 200***
Cabinet Doors, Gasketing, Hardware, & Flue Box Mounting
Until 8/03 1
652
665 664
661
663
650
667
669
668
668
RefPart
No. Description
650 Door Assembly
652 Inspection Door
661 Angle- Flue Box 663 Baffle
664 Sleeve Bearing
665 Door Catch
667 Gasket
668 Gasket
669 Gasket
1
Part
Number Qty.
055632640
1
034095801
1
055945001
1
096427701 1
047138507
3
055502602
3
055921409 2
055921410 2
031949200 1
The cabinet components shown changed when the new design Heat Exchanger was installed in August, 2003. However, if an original design
Heat Exchanger has been replaced with a current design Heat Exchanger the original Flue Box mounting hardware was also replaced.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 150
Section G- Blow-Thru Heat Section
Option 4- Gas Heat w/ 1500 MBH, 2000 MBH Furnace
Code 04= A AND Code 34= 150***, 200***
Cabinet Doors, Gasketing, Hardware, & Flue Box Mounting
8/03 & Later 1
652
665 664
667
661
663
650
658
669
668
668
RefPart
No. Description
650 Door Assembly
652 Inspection Door
658 Back- Flue Box
661 Angle- Flue Box 663 Drip Shield
664 Sleeve Bearing
665 Door Catch
667 Gasket
668 Gasket
669 Gasket
1
Part
Number Qty.
096181445
1
034095801
1
403401001
1
055945001
1
033487300
1
047138507
3
055502602
3
055921409 2
055921410 2
031949200 1
The cabinet components shown changed when the new design Heat Exchanger was installed in August, 2003. However, if an original design
Heat Exchanger has been replaced with a current design Heat Exchanger the original Flue Box mounting hardware was also replaced.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 151
Section H- Blow-Thru Heat/Blank Access Section
Notes
➩
Primary Codes that pertain: 38
Additional Codes that pertain: 06, 34
Code 38 determines all of the section characteristics. If Code 38= B there is a 48” Blow-Thru Heat/Blank Access
Section. If Code 38= Y, there is no section.
Code 34 determines the Blow-Thru Heat Section (Section G). There has to be a Section G in order for there to be
a Section H, therefore Code 34 cannot= YYYYYY.
Code 06 determines the liners and insulation, and will affect the final assembly panels. For sheet metal components
that make up the Blow-Thru Heat Blank Access Section, contact Daikin Applied to ensure that correct liners,
insulation and hardware are ordered.
Door Hardware and Gasketing
RefPart
No. Description
N/S Sleeve Bearing
N/S Door Catch
N/S Gasket- Horizontal
N/S Gasket- Vertical
Part
Number
Qty.
047138507
8
055502602
8
055921408 14
055921411
4
N/S= Not Shown on diagram.
1
If the unit is split at the fan and heat sections (Code 05= F) use p/n 055921409.
Section Mounted Controls
LT19, REC19, S19- Section Mounted Light
284 285
288 289
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” LT19- B-T Heat Section Light/S19- B-T Heat
Section Light Switch/REC19- B-T Heat
Section Receptacle
RefPart
No. Description
284 Light Fixture
285 Bulb- LT19
288 Light Switch- S19
289 Receptacle- REC19
Rev. AG 01/15
Part
Number Qty.
042229500 1
065492402 1
065492201 1
030187000 1
RPL 7000070 / Page 152
Section I- Blow-Thru Cooling Section
Notes
➩
Primary Codes that pertain: 03, 35, 36
Additional Codes that pertain: 06
Code 03 determines the cooling coil size. If Code 03= S there is a small face area coil, and if Code 03= L there is
a large face area coil.
Code 35 determines if there is a Section I. If Code 35= YYYY, there is no section. If the first digit of the code is C
then there is a Cooling Coil, and if it is D there is a Drain Pan with no coil. The second and third digit of Code 35 is
always YY. If the fourth digit is Y the Drain Pan is made of galvanized steel, if the fourth digit is S the Drain Pan is
made from stainless steel.
Code 36 determines Cooling Coil characteristics.
Code 06 determines the liners and insulation, and will affect the final assembly panels. For sheet metal components
that make up the Blow-Thru Cooling Section, contact Daikin Applied to ensure that correct liners, insulation
and hardware are ordered.
Section I applies to the RPS or RFS, but not to the RCS or RDT units.
NOTE: See Section D for all parts used in Section I. Although the section location is
different within the unit configuration, the components are identical.
Section Mounted Controls
LT16, S16, REC16
284 285
288 289
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” LT16- B-T Cooling Section Light/S16- B-T
Cooling Section Light Switch/REC16- B-T
Cooling Section Receptacle
RefPart
No. Description
284 Light Fixture
285 Bulb- LT16
288 Light Switch- S16
289 Receptacle- REC16
Rev. AG 01/15
Part
Number Qty.
042229500 1
065492402 1
065492201 1
030187000 1
RPL 7000070 / Page 153
Section J- Final Filter Section
Notes
➩
Primary Codes that pertain: 39
Additional Codes that pertain: 04, 34
Code 39 determines all of the section characteristics. If Code 39= A, B, E, F there are filters, if it equals C, D then it
is a Blank/empty Section. If Code 39= Y, there is no section.
Codes 04 and 34 determine what type of heat the unit uses. The type of heat influences the filter media and associated
parts.
Door Hardware and Gasketing
RefPart
No. Description
N/S Sleeve Bearing
N/S Door Catch
N/S Gasket- Horizontal
N/S Gasket- Vertical
Part
Number
Qty.
047138507
8
055502602
7
055921408 14
055921410
4
N/S= Not Shown on diagram.
1
If the unit is split at the fan and heat sections (Code 05= F), use p/n 055921409.
Section Mounted Controls
HL23 Gas Hi Limit Control: Code 04= A AND Code 39= A, B, C, D, E, F
PC6/SPS6 Clogged Filter Controls: Code 39= A, B, E, F
Gas Hi Limit Control
Control HL23
it A Gas Heat Hi-Limit (Firestat)
ir
Un
387 F
low
Clogged Filter Control
Clogged Filter Pressure Switch- PC6
Clogged Filter Transducer- SPS6
345
351
386
350
346
340
Unit
Base
RefPart
Part
Qty.
No.Description Number
386 Stat Support 058379401 1
387 HL23 Firestat 047938804 1
Ref.Part
Part Qty.
No. Description
Number
340 Cover 1
0557325011
345 PC6 Pressure Ctl
065493801 1
346 SPS6 Transducer 1049545005 1
350 Plastic Tube 1
0490951041
351 Grommet 1
0049101001
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” MicroTech Controls (Code 12= 1M, 2M, 4M, 5M) only.
Rev. AG 01/15
RPL 7000070 / Page 154
Section J- Final Filter Section
Filters
5A
Flat Filter Rack- Code 39= A, E
5
4
Ref.
No.
4
4A
5
5A
Part
Description
Filter- 95% Eff- Cartridge 2
High Heat 4
2
Filter- 95% Eff- Cartridge Standard 4
Gasket- Filter
High Heat 4
Gasket- Filter
Standard 4
3
Filter- 95% Eff- Cartridge High Heat 4
3
Filter- 95% Eff- Cartridge Standard 4
Gasket- Filter
High Heat 4
Gasket- Filter
Standard 4
4A
Code Code
Part
Qty.
04= 25 1= Number
A, E
A
073381102 12
S, W
A
065810702 12
A, E
A
073337024 12
S, W
A
021768924 12
A, E
A
073381101 4
S, W
A
065810701 4
A, E
A
073337012 4
S, W
A
021768912 4
If Code 25= E (Intersept) Contact Daikin Applied.
Filter size= 24 x 24 x 12.
3
Filter size= 12 x 24 x 12.
4
High Heat Filters are used on units with Gas OR Electric heat. Standard filters are used with Steam, HW heat.
1
2
Staggered Filter Rack- Code 39= B, F
14 14A
14A 14
Ref.
No.
14
14A
Part
Description
Filter- 95% Eff- Cartridge 6
High Heat 7
6
Filter- 95% Eff- Cartridge Standard 7
Gasket- Filter
High Heat 7
Gasket- Filter
Standard 7
Code Code
Part
Qty.
04= 25 5= Number
A, E
B
073381102 16
S, W
B
065810702 16
A, E
B
073337024 16
S, W
B
021768924 16
If Code 25= F (Intersept) Contact Daikin Applied.
Filter size= 24 x 24 x 12.
7
High Heat filters are used on units with Gas OR Electric heat. Standard filters are used with Steam, HW heat.
5
6
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 155
Section K- Discharge Plenum Section- RPS, RFS
Notes
➩
Primary Codes that pertain: 40
Additional Codes that pertain: 06, 11, 16, 34, 35, 36, 38, 39, 41.
Code 40 determines the discharge direction. RPS units may have bottom discharge (Code BE, BY) or side discharge
(Code SY). RFS units may have bottom, side, or front discharge (code FY). This section does not pertain to the
RDT or the RCS.
Code 06, insulation and liners, influences the front panels part numbers. Code 11, Disconnect Switch option, influences
Access Door part numbers. For sheet metal components that make up the Discharge Plenum Section, contact
Daikin Applied to ensure that correct liners, insulation and hardware are ordered.
Code 16 determines Smoke Detectors. If Code 16= 2, 3 there is a Supply Air Smoke Detector (SD1). For RPS and
RFS units with heat the SD1 is in Section K. For RDT units, or RPS/RFS draw thru cooling only units— units with
no separate discharge plenum section— the SD1 is in the Supply Air Section (Section F).
Codes 34- 39, the Blow-Thru/Final Filter section codes, and Code 41, the special Blank Section code, pertain to
some of the final assembly part numbers. If there is no Blow-Thru/final section then the Discharge Plenum is attached
directly to the Supply Air Section and some of the final assembly part numbers are different than they are if the
Blow-Thru section is present. If Code 41=Y (no Blank Access Section), then the Discharge Plenum End Panels are
painted. If the Blank Access Section is present then the End Panels are unpainted.
Note: The RPS and RFS Main Control Box is located in this section. However, the Main Control Box
components are listed in their own section (Section N).
Section Mounted Controls
DAT, OAT, SD1
Outside Air Temperature Sensor- OAT
7A
7
8A
8
Ref Part
Part
No. Description
Number Qty.
7 OA Temp. Sensor- OAT
MicroTech Controls
059974605 1
MicroTech II Controls
060004705 1
MicroTech III Controls 193414602 1
7A Bracket
111075901 1
Discharge Air Temperature Sensor- DAT
OAT
RefPart
Part
No. Description
Number Qty.
8 DA Temp. Sensor- DAT
MicroTech Controls
059974605 1
MicroTech II Controls
060004705 1
MicroTech III Controls 193414602 1
8A Bracket
055732401 1
DAT
30
51
Smoke
Detector
Detail
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Smoke Detector- SD1
Part
RefPart
No. Description
Number
Qty.
30 Smoke Detector SD1 098873101 11
50
1
The original Smoke Detector for units built 2003 & Earlier is no
longer available. When replacing any version of SD1, reuse
existing Sampling Tubes or order 1pc. 098873101 for Standard
Discharge or 2pc. of 098873501 for Side or Top Discharge.
Minor field modifications may be required for proper installation.
Rev. AG 01/15
RPL 7000070 / Page 156
Section K- Discharge Plenum Section
Damper Assembly- w/ Actuator ACT5
Code 40= BE
8/3/92 thru 12/01/08 3
Damper Detail
15
23
18
21
20
22
3
16
24
24
4
22
15
22
View A-A ACT5 Actuator Linkage
Detail
19
17
Opening Size
Ref. Part
Part
38” 146” 2
No.
Description
Number
C03= S C03= L
Complete Assy w/Actuator
(Code 40= BE) 055921127
1
Complete Assy w/Actuator
(Code 40= BE) 055921125
1
Complete Assy w/o Actuator
(Code 40= BD) 055921117
1
Complete Assy w/o Actuator
(Code 40= BD) 055921115
1
3
Motor Mount
(Code 40= BE) 055921201
1
1
4 Blade 055921301
9 12
15
Angle- Linkage 055917702
3 Not Used
Angle- Linkage 055914202 Not Used
3
16Blade- Angle055638102 2733
17Shaft- Damper055637801 1822
18
Linkage- Shaft 055536601
1
1
19Bearing, Flange001113500 1822
20
Actuator- ACT5
(Code 40= BE) 059999804
1
1
21
Crank Arm
(Code 40= BE) 032279200
1
1
22
Ball Joint 000887000
2
2
23Bearing- Sleeve047138507 2733
24
Gasket 030051985
8 Not Used
Gasket 030051979 Not Used
12
Small Face Cooling Coil.
Large Face Cooling Coil.
3
For units built 8/2/92 & Earlier OR 12/02/08 & Later contact Daikin Applied with model and serial number information so that
the correct part(s) OR Complete Damper Assembly can be identified.
1
2
NOTE: This Isolation Damper and ACT5 Actuator may also be located in Section F
(Supply Air). The discharge air opening is in the Supply Air section on RDT units, and
RPS or RFS Draw-Thru units with no Blow-Thru heat (applications where Section F is
attached directly to the condensing unit, or is the end of the unit).
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 157
Section L- Out-of-Airstream Blank Access Section
Notes
➩
Codes that pertain: 41
Additional Codes that pertain: 06
If Code 41= Y, there is no Blank Access Section. If Code 41= 1, there is a 48/24” Blank Access Section with Access
Doors and Light (LT20). If Code 41= 2, there is a Blank Access Section, 48” with Access Doors and Light.
Code 06 determines the liners and insulation, and will affect the final assembly panels. For sheet metal components
that make up the Blank Access Section, contact Daikin Applied to ensure that correct liners, insulation and
hardware are ordered.
Doors, Gasketing and Hardware
Ref PartSection Size
No. Description
48/24” (C41= 1) Qty.
48” (C41= 2) Qty.
N/S
Door Assembly0961792052
0961792052
096179202
2
N/S
Gasket- Horizontal0559214094
0559214094
055921408
4
N/S
Gasket- Vertical0559214114
0559214118
N/S Door Sleeve Bearing
047138507
8
047138507
16
N/S Door Catch
055502602
8
055502602
16
N/S= Not Shown on diagram.
Section Mounted Controls
LT20, REC20, S20- Section Mounted Light
284 285
288 289
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” LT20- Out-of-Airstream Blank Access Section
Light/S20- Out-of-Airstream Blank Access
Section Switch/REC20- Out-of-Airstream
Blank Access Section Receptacle
RefPart
No. Description
284 Light Fixture
285 Bulb- LT20
288 Light Switch- S20
289 Receptacle- REC20
Rev. AG 01/15
Part
Number Qty.
042229500 1
065492402 1
065492201 1
030187000 1
RPL 7000070 / Page 158
Section M- Condenser Section
Notes
➩
Primary Codes that pertain: 42, 43, 44, 45, 47
Additional Codes that pertain: 09, 10
This section houses the Compressors, Condenser Coils, Condenser Control Box, and Fan Deck.
Codes 09, 10, 42 affect Compressor selection.
Codes 09 & 10 also affect the Compressor Contactors located in the Condenser Control Box.
Code 43 determines the fin material used in the Condenser Coils.
Code 44 determines the Compressor type— discus or scroll— and refrigerant.
Code 45 determines the way the Compressor is mounted.
Code 47 determines the low ambient operation and Condenser Fan Motor selection. If Code 47= 1, the unit has
standard FanTrol Condenser Fan control. If Code 47= 2 the unit has SpeedTrol controls that allow for low ambient
(lower temperature) operation. If Code 47= 3, 4 the unit uses Quiet Fans.
Note: Condenser Coil Section, and Compressor Section components are different for the RPS/RDT and the RCS
units. All other aspects of the section (Fan Deck, Compressors, etc.) are identical.
The condenser section is used on the RPS unit, but not the RFS. The condenser section is the RCS unit.
Section Mounted Controls
PC22, PC12
12
12A
Fantrol Pressure Control 1
RefPart
Part
Qty.
No. Description Number
12 Pressure Control
PC12 047356118 1
12A Pressure Control
PC22 047356118 1
1
Generally used only with Discus Compressors (Code 44= H, K) and
original MicroTech Controls (Code 08= P, S [RPS/RDT] or Y [RCS]).
View from Condenser Control Box End
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 159
Section M- Condenser Section
Units with Original Fan Assembly (3 blade Prop)
Diagrams
26
81
81
26
Fan
(see below)
Fan
7
(see below)
8
8
5
7
5
2A
or
l
ro
nt
Co Box
x
n
Co
2
Compressors
#2, #4
Compressors
#1, #3
o
l B
tro
2
1
or
or
2A
1A
1
Compressors
#2, #4
Compressors
#1, #3
080C, 090C, 105C
Condenser Section
Fan # 23
Fan # 22
Fan # 21
or
1A
115C, 125C, 135C
Condenser Section
Fan # 24
Fan # 23 Fan # 22
Fan Detail
Fan # 21
81
Fan # 24
Fan # 14
Fan # 13
Fan # 12
Fan # 11
Fan # 15
Fan # 14 Fan # 13
080C, 090C
Fan Deck Detail
26
Fan # 25
Fan # 12 Fan # 11
105C
Fan Deck Detail
38
68
37
Fan # 23
Fan # 22
Fan # 14
Fan # 25
Fan # 13
Fan # 12
Fan # 21
Fan # 24
Fan # 11
105C
Fan Deck Detail
Fan # 24
Fan # 23 Fan # 22
Fan # 21
Fan # 15 Fan # 16
Fan # 26 Fan # 25
Fan # 14 Fan # 13
Fan # 12 Fan # 11
Motor Mount
Detail
35
38
36
46 47
30
125C, 135C
Fan Deck Detail
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 160
Section M- Condenser Section
Units with Original Fan Assembly (3 blade Prop) 7
Components
575V
460/380V
208/230V
575V
460/380V
208/230V
575V
460/380V
575V
208/230V
460/380V
208/230V
575V
460/380V
Unit Size
080090105115
125, 135
208/230V
Ref Part
Part
No.Description Number
1 Compressor #1 see 4 pages after next
1A Compressor #3 see 4 pages after next
2 Compressor #2 see 4 pages after next
2A Compressor #4 see 4 pages after next
5 Horizontal Coil
Aluminum Fin 1 055560703 111
Horizontal Coil
Aluminum Fin 2055560705 111111
Horizontal Coil
Aluminum Fin 2055560707 1111 11
Horizontal Coil
Copper Fin 3 055560704 111
Horizontal Coil
Copper Fin 4055560706 111111
Horizontal Coil
Copper Fin 4055560708 1111 11
7 Vertical Coil- Circuit #1 Aluminum Fin 2 055561503 111
Vertical Coil- Circuit #1 Aluminum Fin 2055561505 111111
Vertical Coil- Circuit #1 Aluminum Fin 2055561507 1111 11
Vertical Coil- Circuit #1
Copper Fin 4 055561504 111
Vertical Coil- Circuit #1
Copper Fin 4055561506 111111
Vertical Coil- Circuit #1
Copper Fin 4055561508 1111 11
8 Vertical Coil- Circuit #2 Aluminum Fin 2 055561603 111
Vertical Coil- Circuit #2 Aluminum Fin 2055561605 111111
Vertical Coil- Circuit #2 Aluminum Fin 2055561607 1111 11
Vertical Coil- Circuit #2
Copper Fin 4 055561604 111
Vertical Coil- Circuit #2
Copper Fin 4055561606 111111
Vertical Coil- Circuit #2
Copper Fin 4055561608 1111 11
26 Fan Guard 047359201 7 8 8 8 8 8 8 9 9 9 10101012 1212
30 Channel- Motor Support 055545501 7888888999
Channel- Motor Support 055672801 7 10101012 1212
35 Motor- Condenser 111052903 588 88 9910
101212
Motor- Condenser (1/08 & Earlier)1.5HP 046744200 5 8 8 91012
Motor- Condenser (2/08 & Later) 1.0HP 046744203 5 8 8 91012
36 Rain Slinger 027471200 7 8 8 8 8 8 8 9 9 9 10101012 1212
37 Fan Propeller- 4 Blade 258981901 6 8 8 8 8 8 8 9 9 9 10101012 1212
38 Motor Mount- U Bolt 046743101 7 8 8 8 8 8 8 9 9 9 10101012 1212
46 Nut 032333304 732323232323236363640404048 4848
47 Washer- Flat 040500308 732323232323236363640404048 4848
68 Top Panel 055556001 7888888999
Top Panel 055556002 7 10101012 1212
81 Panel, Blank- Fan Deck 055547102 7111111000
Panel, Blank- Fan Deck 055672702 7 2220 00
Code 43= AY.
Code 43= AY, AG, AS, AB.
3
Code 43= CY.
4
Code 43= CY, CG, CS, CB.
5
If unit has Speedtrol (Code 45= 2) Fan Motors #11 & #21 are p/n 034914500.
6
Note that the original Fan Props (3 AND 5 blade) are obsolete. They have been replaced with this functional replacement four (4) blade Prop.
7
There were TWO DIFFERENT Condenser Fan Assemblies provided during the production run. Due to overlapping production times it is
necessary to VISUALLY confirm which style of assembly is installed BEFORE ordering parts. (The most notable differences are in the design
of the Fan Motor Mount [Ref # 38] and the Fan Guard [Ref # 26]. Refer to the Fan detail on the following page to aid in identification.) If visual
identification is not possible, contact Daikin Applied with model and serial number information so that the correct part(s) can be identified.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 161
Section M- Condenser Section
Units with Later Fan Assembly (4 blade Prop)
Standard Fans (Code 47= 1, 2)
Diagrams
26
81
Fan
26
(see below)
81
* Control Box applies to RCS only with
MicroTech II new design
(3/05 & Later [C08= D])
(see below)
Fan
7
8
8
Bo
x*
7
Qty.= 3
(scrolls)
Qty.= 1
(discus)
Qty.= 1
(discussize 105)
5
Co
nt
ro
l
5
Control
Box*
2
2
Qty.= 3
(scrolls)
Qty.= 1
(discus)
1
or
2A
or
Compressors
#2, #4, #6
1A
Compressors
#1, #3, #5
1
or
2A
Compressors
#2, #4
Fan # 21
Fan # 24
Fan # 23
1A
115C, 125C, 135C
Condenser Section
(shown with scroll compressors: Code 44= Z, T)
Fan # 22
Compressors
#1, #3
Qty.= 1
(discussize 105)
080C, 090C, 105C
Condenser Section
Fan # 23
or
Fan # 22
Fan Detail
Fan # 21
26
Fan # 14
Fan # 13
Fan # 12
Fan # 24
Fan # 15
Fan # 11
Fan # 14
080C , 090C
Fan Deck Detail
Fan # 23
Fan # 22
Fan # 21
Fan # 25
Fan # 13
Fan # 12
37
Fan # 11
115C
Fan Deck Detail
Fan # 24
Fan # 23
Fan # 22
50
Fan # 21
38
Fan # 14
Fan # 25
Fan # 24
Fan # 15
Fan # 16
Fan # 26
35
Fan # 25
46
38
Fan # 13
Fan # 12
Fan # 11
105C
Fan Deck Detail
Fan # 14
Fan # 13
Fan # 12
Fan # 11
44
47
125C, 135C
Fan Deck Detail
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 162
Section M- Condenser Section
Units with Later Fan Assembly (4 blade Prop) 5
Standard Fans (Code 47= 1, 2)
Components
575V
460/380V
208/230V
575V
460/380V
208/230V
575V
460/380V
575V
208/230V
460/380V
208/230V
575V
460/380V
208/230V
Unit Size
080 090 105 115
125,135
Ref Part
Part
No.Description Number
1,1A Compressors #1,3,5 see 2 pages after next
2,2A Compressors #2,4,6 see 2 pages after next
5 Horizontal Coil
Aluminum Fin 1 055560703 11 1
Horizontal Coil
Aluminum Fin 1055560705 111111
Horizontal Coil
Aluminum Fin 10555607071
1
1
1
1
1
Horizontal Coil
Copper Fin 2 055560704 11 1
Horizontal Coil
Copper Fin 2055560706 111111
Horizontal Coil
Copper Fin 20555607081
1
1
1
1
1
7 Vertical Coil- Circuit #1 Aluminum Fin 1
Scroll Compressors
Code 44= Z, T 251701903 1 1 1
Scroll Compressors
Code 44= Z, T 251701905 1 1 1 1 1 1
Discus Compressors Code 44= H, K 055561503 1 1 1
Discus Compressors Code 44= H, K 055561505 1 1 1 1 1 1
Discus CompressorsCode 44= H, K0555615071
1
1
1
1
1
Vertical Coil- Circuit #1
Copper Fin 2 251703004 11 1
Vertical Coil- Circuit #1
Copper Fin 2055561506 111111
Vertical Coil- Circuit #1
Copper Fin 20555615081
1
1
1
1
1
8 Vertical Coil- Circuit #2 Aluminum Fin 1
Scroll Compressors
Code 44= Z, T 251702003 1 1 1
Scroll Compressors
Code 44= Z, T 251702005 1 1 1 1 1 1
Discus Compressors Code 44= H, K 055561603 1 1 1
Discus Compressors Code 44= H, K 055561605 1 1 1 1 1 1
Discus CompressorsCode 44= H, K0555616071
1
1
1
1
1
Vertical Coil- Circuit #2
Copper Fin 2 251703204 11 1
Vertical Coil- Circuit #2
Copper Fin 2055561606 111111
Vertical Coil- Circuit #2
Copper Fin 20555616081
1
1
1
1
1
26 Fan Guard 098668302 588888899910
10
10
12
12
12
35 Motor- Condenser 111052903 388 88 9910
1012
12
Standard (1/08 & Earlier)
C47= 1, 2 046744200 38891012
Standard (2/08 & Later)
C47= 1, 2 046744203 38891012
37 Fan Propeller- 4 Blade 258981901 688888899910
10
10
12
12
12
38 Motor Mount- 2 pc. 098667802 4, 5161616161616181818202020242424
44 Screw, Cap 048878129 161616161616242424242424323232
46 Nut 040500104 323232323232484848484848646464
47 Washer- Flat 040500307 161616161616242424242424323232
50 Top Panel 110941201 5888888999
Top Panel 110941002 5
10
10
10
12
12
12
81 Panel, Blank- Fan Deck 110943201 52
2
2
Panel, Blank- Fan Deck 098666802 5111111
Code 43= AY, AG, AS, AB.
Code 43= CY, CG, CS, CB.
3
If unit has Speedtrol (Code 47= 2) Fan Motors #11 & #21 are p/n 034914500. P/N 111052903 is a replacement motor. Rain Slinger
027471200 is ONLY used with the obsolete older style Fan Motor. P/N 111052903 comes assembled with a slinger.
4
P/N 098667802 is only 1 of the two pieces that make up the Motor Mount. For a complete Motor Mount, order a qty. of TWO PER Fan.
5
There were TWO DIFFERENT Condenser Fan Assemblies provided during the production run. Due to overlapping production times it is
necessary to VISUALLY confirm which style of assembly is installed BEFORE ordering parts. (The most notable differences are in the
design of the Fan Motor Mount [Ref # 38] and the Fan Guard [Ref # 26].) If visual identification is not possible, contact Daikin Applied with
model and serial number information so that the correct part(s) can be identified.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 163
Section M- Condenser Section
Quiet Fans (Code 47= 3, 4)
Diagrams
81
Fan
81
Fan
(see below)
8
(see below)
8
7
Bo
x*
7
Qty.= 3
5
Co
nt
ro
l
5
2
2
1
Qty.= 3
Compressors
#2, #4, #6
1
or
2A
Compressors
#2, #4
Fan # 22
Fan # 21
or
Compressors
#1, #3
1A
Compressors
#1, #3, #5
080C, 090C, 105C
(090 Shown)
Fan # 23
Control
Box
Fan # 24
115C, 125C, 135C
(115 shown)
Fan # 23
Fan Detail
Fan # 21
Fan # 22
37
Fan # 14
Fan # 13
Fan # 12
Fan # 24
Fan # 15
Fan # 11
Fan # 14
080C, 090C
Fan Deck Detail
Fan # 13
Fan # 12
Fan # 11
115C
Fan Deck Detail
Fan # 23
Fan # 22
Fan # 21
Fan # 24
Fan # 14
Fan # 25
Fan # 24
Fan # 15
Fan # 13
Fan # 12
Fan # 11
Fan # 14
105C
Fan Deck Detail
Fan # 25
50
Fan # 22
Fan # 21
Fan # 16
Fan # 26
Fan # 25
Fan # 13
Fan # 12
Fan # 11
Fan # 23
38
125C, 135C
Fan Deck Detail
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 164
Section M- Condenser Section
Quiet Fans (Code 47= 3, 4)
Components
575V
460/380V
208/230V
575V
460/380V
208/230V
575V
460/380V
208/230V
575V
460/380V
575V
208/230V
460/380V
208/230V
Unit Size
080 090 105 115
125,135
Ref Part
Part
No.Description Number
1,1A Compressors #1,3,5
see next page
2,2A Compressors #2,4,6
see next page
5 Horizontal Coil
Aluminum Fin 1 055560703 11 1
Horizontal Coil
Aluminum Fin 1 055560705 111111
Horizontal Coil
Aluminum Fin 10555607071
1
11
1
1
Horizontal Coil
Copper Fin 2 055560704 11 1
Horizontal Coil
Copper Fin 2 055560706 111111
Horizontal Coil
Copper Fin 20555607081
1
11
1
1
7 Vertical Coil- Circuit #1 Aluminum Fin 1 066305219 11 1
Vertical Coil- Circuit #1 Aluminum Fin 1 104474263 111111
Vertical Coil- Circuit #1 Aluminum Fin 11044741211
1
11
1
1
Vertical Coil- Circuit #1
Copper Fin 2 251703004 11 1
Vertical Coil- Circuit #1
Copper Fin 2 104474131 111111
Vertical Coil- Circuit #1
Copper Fin 20555615081
1
11
1
1
8 Vertical Coil- Circuit #2 Aluminum Fin 1 066305319 11 1
Vertical Coil- Circuit #2 Aluminum Fin 1 104474265 111111
Vertical Coil- Circuit #2 Aluminum Fin 11044741221
1
11
1
1
Vertical Coil- Circuit #2
Copper Fin 2 251703204 11 1
Vertical Coil- Circuit #2
Copper Fin 2 104474132 111111
Vertical Coil- Circuit #2
Copper Fin 20555616081
1
11
1
1
37 Motor/Fan Assembly- Condenser 098874203 8 8 9 10 12
Motor/Fan Assembly- Condenser 098874202 8 8 9 10 12
Motor/Fan Assembly- Condenser0988742018891012
38 Housing, Bell- Fan 09887430188888899910
10
1012
12
12
50 Panel- Fan 111425201888888999
Panel- Fan113021901
10
10
10
12
12
12
81 Panel, Blank- Fan Deck 110943201 2 2 2
Panel, Blank- Fan Deck 098666802 1 1 1 1 1 1
1
2
Code 43= AY, AG, AS, AB.
Code 43= CY, CG, CS, CB.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 165
Section M- Condenser Section
Units with Semi Hermetic Compressors (Code 44= H, K)
Compressors & Compressor Components
Compressor Detail
1K 1J
1L
1H
1M
Oil Equalization Detail
208/230V
575V
460/380V
208/230V
090
575V
460/380V
080
U
nit Size 1
105
115, 125
135
575V
460/380V
2A
208/230V
or
575V
2
or
460/380V
1A
208/230V
or
208/230V
1
575V
1G
1N 1P
460/380V
Disch.
Valve
AL= Across the Line Start (Code 10= AL); PW= Part Winding Start (Code 10= PW, PP).
Code 44= H.
3
Code 44= K.
4
Unit sizes 080 & 090, Ref 1, 2 / Compressor 1, 2; Unit size 105-135, Ref 1,1A / Compressor 1, 3.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 166
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
efPart
R
Part
No.Description
Number
4Compressor
25HPR22 2
0 unloaders0492671002
2
2
1 unloader0464965002
2
2
0 unloaders0492686002
1 unloader0464966002
0 OR 1 Unloader0471311002
2
25HPR407C 3
0 unloaders2517015012
2
2
1 unloader2517015022
2
2
0 unloaders2517015032
1 unloader2517015042
0 OR 1 Unloader2517015062
2
30HPR22 2
0 OR 1 Unloader0464967002
2
2
0 OR 1 Unloader0464968002
0 OR 1 Unloader047131200
2
2
30HPR407C 3
0 OR 1 Unloader2517016012
2
2
0 OR 1 Unloader2517016032
0 OR 1 Unloader251701605
2
2
35HPR22 2
1 unloader04926720022
22
2
2
2 unloaders04649690022
22
2
2
1 unloader049267400
22
2 unloaders046497000
22
1 unloader0492676002
22
2
2 unloaders0471313002
22
2
Section M- Condenser Section
Units with Semi Hermetic Compressors (Code 44= H, K)
Compressors & Compressor Components, Continued
575V
AL
PW
460/380V
AL
PW
208/230V
AL
PW
575V
AL
PW
460/380V
AL
PW
208/230V
AL
PW
575V
AL
PW
460/380V
AL
PW
208/230V
AL
PW
575V
AL
PW
460/380V
AL
PW
208/230V
AL
PW
575V
AL
PW
460/380V
AL
PW
AL
PW
208/230V
U
nit Size 1
080
090
105
115, 125
135
RefPart
Part
No.Description
Number
9Compressor
35HPR407C 3
1 unloader
251701702
2
2
22
2
2
2 unloaders
251701703
2
2
22
2
2
1 unloader
251701705
22
2 unloaders
251701706
22
1 unloader
2517017082
22
2
2 unloaders
2517017092
22
2
40HPR22 2
1 unloader 04926810042
2
2
2 unloaders 04446280052
2
2
1 unloader
049267900
2
2 unloaders
044462900
2
1 or 2 unloaders
0471314002
2
40HPR407C 3
1 unloader 25170180542
2
2
2 unloaders 25170180652
2
2
1 unloader
251701808
2
2 unloaders
251701809
2
1 or 2 unloaders
2517018122
2
1G Crankcase Heater
Liquid Tite Conduit 7059479001222222 222222222222222222
Flex Conduit 8059443001222222 222222222222222222
All Conduit030178400 222222
1H High Pressure Control
MicroTech
047356110222222222222222222222222222222
MicroTech II047356120222222222222222222222222222222
1J
1K
1L
1M
1N
1P
Valve- Unloader046497300 666666666666666666666666666666
Gasket- Unloader046498800 666666666666666666666666666666
Gasket027017048222222222222222222222222222222
Low Pressure Control047356111222222222222222222222222222222
Valve- Oil Equalization049122702111111111111111111111111111111
Cap- Oil Equal. Valve001106100111111111111111111111111111111
AL= Across the Line Start (Code 10= AL); PW= Part Winding Start (Code 10= PW, PP).
Code 44= H.
3
Code 44= K.
4
230/460V units only. For 208V units use p/n 049267700 (R22) or 251701802 (R407C).
5
230/460V units only. For 208V units use p/n 044462700 (R22) or 251701803 (R407C).
6
Quantity of unloader valve is as required. There are 2 gaskets PER valve.
7
Code 43= AS, AB, CS, CB.
8
Code 43= AG, AY, CG, CY.
9
Unit sizes 080 & 090, Ref 1, 2 / Compressor 1, 2; Unit size 105-135, Ref 1,1A / Compressor 1, 3.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 167
Section M- Condenser Section
Units with Semi Hermetic Compressors (Code 44= H, K)
Compressors & Compressor Components, Continued
575V
460/380V
208/230V
125,135
575V
460/380V
208/230V
Unit Size 1
115
575V
460/380V
208/230V
105
AL
PW
AL
PW
PW
AL
AL
PW
AL
PW
AL
PW
PW
AL
AL
PW
AL
PW
RefPart
Part
No.Description
Number
2,2A Compressor #2,4
25HPR22 2
0 unloaders 049267100 2 2 2
1 unloader 046496500 2 2 2
0 unloaders 049268600 2
1 unloader 046496600 2
0 OR 1 Unloader 047131100 22
25HPR407C 3
0 unloaders 251701501 2 2 2
1 unloader 251701502 2 2 2
0 unloaders 251701503 2
1 unloader 251701504 2
0 OR 1 Unloader 251701506 22
30HPR22 2
0 OR 1 Unloader 046496700 2 22
0 OR 1 Unloader0464968002
0 OR 1 Unloader047131200
2
2
30HPR407C 3
0 OR 1 Unloader 251701601 2 22
0 OR 1 Unloader2517016032
0 OR 1 Unloader251701605
2
2
35HPR22 2
1 unloader0492672002
2
2
2 unloaders0464969002
2
2
1 unloader0492674002
2 unloaders0464970002
1 unloader0492676002
2
2 unloaders0471313002
2
35HPR407C 3
1 unloader2517017022
2
2
2 unloaders2517017032
2
2
1 unloader2517017052
2 unloaders2517017062
1 unloader2517017082
2
2 unloaders2517017092
2
AL= Across the Line Start (Code 10= AL); PW= Part Winding Start (Code 10= PW, PP).
Code 44= H.
3
Code 44= K.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 168
Section M- Condenser Section
Units with Semi Hermetic Compressors (Code 44= H, K)
Compressor Mounting
Resilient Mount (Code 45= 1)
22
24
Compressor
10
23
11
12
20
4
Mounting
Base
Ref. Part
No. Description
4 Channel- Rubber Mount
10 Spacer Pad- Lower
11 Spacer Pad- Upper
12 Spacer- Rubber
20 Screw- Cap, 3/8-16 X 1
21 Nut- Hex, Flanged
22 Bolt- Hex 5/8-11 X 2.75
23 Nut- Hex, 5/8-11
24 Washer- Flat, 5/8
Comp.
HP
All
All
All
All
All
All
All
All
All
Part
Number
055565501
041763300
041763400
019941000
048878118
032333304
040499525
040500002
040500312
Qty.
Comp.
HP
All
20
25, 30
35
40
All
All
Part Number
055646001
001402900
001403600
019439200
034895100
048878118
032333304
Qty.
4
4
4
4
8
8
4
8
4
21
Spring Mount (Code 45= 2)
Compressor
9
4
20
Ref. Part
No. Description
4 Channel- Spring Mount
9 Spring Isolator
Spring Isolator
Spring Isolator
Spring Isolator
20 Screw- Cap, 3/8-16 X 1
21 Nut- Hex, Flanged
1
Mounting
Base
4
11
11
11
11
8
8
includes 4 springs.
21
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 169
Section M- Condenser Section
Units with Scroll Compressors
R22 Compressor (Code 44= Z)- Until 7/08
Components
3
6
7
4
5
2
Circuit #1
or
Circuit #2
Comp. #2
Comp. #4
Comp. #6
Comp. #5
Comp. #3
Comp. #1
or
or
or
1
or
575V
460/380V
208/230V
575V
460/380V
575V
208/230V
460/380V
208/230V
Unit Size
080090105
Ref Part
Part
No.Description Number
R22
Code 44= Z
1, 2 Compressor #1, 2, 3, 4, 5, 6 Trio 3 060010321 6 31
Compressor #1, 2, 3, 4, 5, 6 Trio 3 060010323 6 31
Compressor #1, 2, 3, 4, 5, 6 Trio 3 060010324 6 31
Compressor #1, 2, 3, 4, 5, 6 Trio 3 060010421 32 6
Compressor #1, 2, 3, 4, 5, 6 Trio 3 060010423 326
Compressor #1, 2, 3, 4, 5, 6 Trio 3 060010424 32 6
3 Low Pressure Control047356111 222222222
4 Valve Stem110986801 222222222
5 Valve Core026541100 222222222
6 High Pressure Control
MicroTech OR No Controls 4047356110 222222222
MicroTech II Controls 5047356120 222222222
7 Crankcase Heater
Standard Conduit 6112056403 666666666
Liquid-Tite Conduit 7111003001 666666666
Circuit #2 (Compressors #2, 4, 6).
Circuit #1 (Compressors #1, 3, 5).
3
Part number is for one (1) Compressor.
4
Code 12= 1M, 2M, 4M, 5M, YM, YC.
5
Code 12= SS, SD, ES, ED, BS, BD, LS, LD.
6
Code 43= AG, AY, CG, CY.
7
Code 43= AS, AB, CS, CB.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 170
Section M- Condenser Section
Units with Scroll Compressors
R22 Compressor (Code 44= Z)- 7/08 & Later
Components
4
5
2
Comp. #2
Comp. #4
Comp. #6
Comp. #5
Comp. #3
Comp. #1
or
or
575V
Unit Size
090
105
208/230V
460/380V
208/230V
080
575V
or
460/380V
or
Circuit #2
1
208/230V
Circuit #1
or
575V
3
6
460/380V
7
Ref Part
Part
No.Description
Number
R22
Code 44= Z
1, 2 Compressor #1, 2, 3, 4, 5, 6 Trio 3113116801 631
Compressor #1, 2, 3, 4, 5, 6 Trio 3 113116803 631
Compressor #1, 2, 3, 4, 5, 6 Trio 3113116804631
Compressor #1, 2, 3, 4, 5, 6 Trio 311311710132 6
Compressor #1, 2, 3, 4, 5, 6 Trio 3113117103
32 6
3
Compressor #1, 2, 3, 4, 5, 6 Trio 113117104326
3 Low Pressure Control047356111 222222222
4 Valve Stem110986801 222222222
5 Valve Core026541100 222222222
6 High Pressure Control
MicroTech OR No Controls 4047356110 222222222
MicroTech II OR III Controls 5047356120 222222222
7 Crankcase Heater113108903 666666666
Circuit #2 (Compressors #2, 4, 6).
Circuit #1 (Compressors #1, 3, 5).
3
Part number is for one (1) Compressor.
4
Code 12= 1M, 2M, 4M, 5M, YM, YC
5
Code 12= *D, *S, *E, *F.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 171
Section M- Condenser Section
Units with Scroll Compressors
R407C Compressor (Code 44= T)- Until 7/08
Components
4
5
2
or
Circuit #2
Comp. #2
Comp. #4
Comp. #6
Comp. #5
Comp. #3
Comp. #1
or
or
1
or
575V
105
208/230V
460/380V
208/230V
575V
460/380V
208/230V
Unit Size
080
090
575V
Circuit #1
or
460/380V
3
6
7
Ref Part
Part
No.Description
Number
R407C
Code 44= T
1, 2 Compressor #1, 2, 3, 4, 5, 6 Trio 3098868901 631
Compressor #1, 2, 3, 4, 5, 6 Trio 3 098868903 631
Compressor #1, 2, 3, 4, 5, 6 Trio 3098868904631
Compressor #1, 2, 3, 4, 5, 6 Trio 309886880132 6
Compressor #1, 2, 3, 4, 5, 6 Trio 3098868803
32 6
Compressor #1, 2, 3, 4, 5, 6 Trio 3098868804326
3 Low Pressure Control047356111 222222222
4 Valve Stem110986801 222222222
5 Valve Core026541100 222222222
6 High Pressure Control
MicroTech II Controls 4047356121 222222222
No Controls 5047356122 222222222
7 Crankcase Heater
Standard Conduit 6112056403 666666666
Liquid-Tite Conduit 7111003001 666666666
Circuit #2 (Compressors #2, 4, 6).
Circuit #1 (Compressors #1, 3, 5).
3
Part number is for one (1) Compressor.
4
Code 12= SS, SD, ES, ED, BS, BD, LS, LD.
5
Code 12= YM, YC.
6
Code 43= AG, AY, CG, CY.
7
Code 43= AS, AB, CS, CB.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 172
Section M- Condenser Section
Units with Scroll Compressors
R407C Compressor (Code 44= T)- 7/08 & Later
Components
3
6
7
4
5
2
Circuit #1
or
Circuit #2
Comp. #2
Comp. #4
Comp. #6
Comp. #5
Comp. #3
Comp. #1
or
or
or
1
or
575V
460/380V
575V
208/230V
460/380V
208/230V
575V
460/380V
Ref Part
Part
No.Description
Number
R407C
Code 44= T
1, 2 Compressor #1, 2, 3, 4, 5, 6 Trio 3
Compressor #1, 2, 3, 4, 5, 6 Trio 3
Compressor #1, 2, 3, 4, 5, 6 Trio 3
Compressor #1, 2, 3, 4, 5, 6 Trio 3
Compressor #1, 2, 3, 4, 5, 6 Trio 3
Compressor #1, 2, 3, 4, 5, 6 Trio 3
208/230V
Unit Size
080 090105
113119101 6 31
113119103 6 31
113119104 6 31
113119301 32 6
113119203 326
113119204 32 6
3 Low Pressure Control047356111 222222222
4 Valve Stem110986801 222222222
5 Valve Core026541100 222222222
6 High Pressure Control
MicroTech II Controls 4047356121 222222222
No Controls 5047356122 222222222
7 Crankcase Heater113108903 666666666
Circuit #2 (Compressors #2, 4, 6).
Circuit #1 (Compressors #1, 3, 5).
3
Part number is for one (1) Compressor.
4
Code 12= SS, SD, ES, ED, BS, BD, LS, LD.
5
Code 12= YM, YC.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 173
Section M- Condenser Section
Units with Scroll Compressors (Code 44= Z, T)
Compressor Mounting
Trio Compressors- Unit Sizes 080C, 090C, 105C
Until 6/04
10
Rail
22
24
Ref. Part
No. Description
10 Spacer
11 Spacer
12 Sleeve
22 Screw
23 Nut
24 Washer
11
12
23
Mounting
Channel
Comp.
HP
All
All
All
All
All
All
Part
Qty.
Number
111056001 6
111056101 6
111056201 6
048878123 6
032333304 6
040500316 6
NOTE: Quantities are per circuit (for one trio)
Trio Compressors- Unit Sizes 080C, 090C, 105C
6/04 and Later
22
Rail
24
Ref. Part
No. Description
11 Grommet
12 Sleeve
22 Screw
23 Nut
24 Washer
11
12
23
Mounting
Channel
Comp.
HP
All
All
All
All
All
Part
Qty.
Number
251774401 8
111056201 8
048878123 8
032333304 8
040500316 8
NOTE: Quantities are per circuit (for one trio)
Condenser Coil Guards
28
18
28
28
080C, 090C, 105C
(080C shown)
115C, 125C, 135C
(125C shown)
18
28
28
28
Ref Part
No. Description
080
18 Channel- Grille Support
055544202
28 Grille- Coil Guard
049757701
Unit Size
090,
105
055680802
049757702
18
28
115, 125, Qty.
135
055673202 4
049757703 6
N/A= Not applicable.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 174
Section M- Condenser Section
Condenser Control Box
RPS/RDT/RCS
Power Panel Diagrams Until 3/05
GFS2
PB4
or
DS4
FB1
FB
8
FB2
M
24
M
14
M
13
M
12
M
11
M
23
M
22
M
21
FB
11
RPS Units- FB1, FB2 located in separate fuse box
T1
RPS Units- PVM2
located in separate
fuse box
FB13 FB12
M1
PVM2
M5
M2
M6
Power PanelUnit Sizes 080C, 090C
With Speedtrol (Code 47= 2)
NOTE: Italicized components are used only on
RCS units.
NOTE: RPS units have a separate fuse box which
contains FB1, FB2, PVM2.
NOTE: M5, M6 Not Used on 460V/575V AL units.
TB1
GFS2
PB4
or
DS4
FB1
FB
8
FB2
M
24
M
14
M
13
M
12
M
23
M
22
M
21
M
11
RPS Units- FB1, FB2 located in separate fuse box
FB15 FB14 FB13 FB12
T1
RPS Units- PVM2
located in separate
fuse box
PVM2
M1
M5
M2
M6
Power PanelUnit Sizes 080C, 090C
No Speedtrol (Code 47= 1)
NOTE: Italicized components are used only on
RCS units.
NOTE: RPS units have a separate fuse box which
contains FB1, FB2, PVM2.
NOTE: FB14, FB15 used only on 208/230V units.
NOTE: M5, M6 Not Used on 460V/575V AL units.
TB1
GFS2
PB4
or
DS4
RPS Units- PVM2
located in separate
fuse box
FB
8
FB1
FB3
FB2
FB4
RPS Units- FB1, FB2, FB3, FB4 located in separate fuse box
M
13
M
12
M
11
M
23
M
22
M
21
FB
11
FB15 FB14 FB13 FB12
T1
PVM2
M
24
M
14
M1
M5
M3
M4
M7
M8
M2
M6
TB1
GFS2
PB4
or
DS4
RPS Units- PVM2
located in separate
fuse box
FB
8
FB1
FB3
FB2
FB4
RPS Units- FB1, FB2, FB3, FB4 located in separate fuse box
M
13
M
12
M
23
M
22
M
21
M
11
FB15 FB14 FB13 FB12
T1
PVM2
M
24
M
14
M1
M5
M3
M7
M4
TB1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” M8
M2
M6
Power PanelUnit Sizes 105C,115C,125C,135C
With Speedtrol (Code 47= 2)
NOTE: Italicized components are used only on
RCS units.
NOTE: RPS units have a separate fuse box which
contains FB1, FB2, FB3, FB4, PVM2.
NOTE: FB14 Not Used on 105C units. FB14, FB15
Not Used on 460V or 575V units.
NOTE: M5, M6, M7, M8 Not Used on 460V/575V
AL units.
Power PanelUnit Sizes 105C,115C,125C,135C
No Speedtrol (Code 47= 1)
NOTE: Italicized components are used only on
RCS units.
NOTE: RPS units have a separate fuse box which
contains FB1, FB2, FB3, FB4, PVM2.
NOTE: FB14, FB15 Not Used on 460V or 575V
units.
NOTE: M5, M6, M7, M8 Not Used on 460V/575V
AL units.
Rev. AG 01/15
RPL 7000070 / Page 175
Section M- Condenser Section
Condenser Control Box- RPS/RDT/RCS
Power Panel Components Until 3/05
Unit Sizes
Sch Part
Part080, 090105, 115, 125, 135
Sym Description Number 208V230V 380V460V 575V 208V230V380V 460V575V
Transformer
T1
Transformer- Main
RCS only 038253913 1
1
Transformer- Main
RCS only 038253904 1 1
Transformer- Main
RCS only 038253932
1
Transformer- Main
RCS only 038253916
1
Transformer- Main
RCS only
038253907
1
Transformer- Main
RCS only
0382539151
Transformer- Main
RCS only
0382539061
Transformer- Main
RCS only
0382539291
Fuse Block- T1 Transformer
FB8 Fuse Block- T1 Transformer
RCS only 023780202 1 1
1 1
Fuse Block- T1 Transformer
RCS only 023780203
1 1 1 1 1 1
Fuse- FB8
Fuse- FB8 Fuse Block
4.0A 025860530 2
Fuse- FB8 Fuse Block
3.2A 025860532 2
Fuse- FB8 Fuse Block
3.5A 025860435
2
Fuse- FB8 Fuse Block
3.0A 025860434 2
Fuse- FB8 Fuse Block
2.5A 025860402
2
Fuse- FB8 Fuse Block
12.0A 025860534
2
Fuse- FB8 Fuse Block
10.0A 025860504 2
Fuse- FB8 Fuse Block
4.0A 025860436 2
Fuse- FB8 Fuse Block
3.5A
0258604352
Fuse- FB8 Fuse Block
5.0A
0258604332
Terminal Blocks
TB1Terminal Block- Receptacle
02243120311 11 1 111 11
Ground Fault 2
GFR2Relay- Ground Fault
06581340111 11 1 111 11
GFS2Sensor- Ground Fault Relay
06581340211 11 1 111 11
Phase Voltage 3
PVM2Phase Voltage Monitor
until 8/02
05947530611 11 111 1
Phase Voltage Monitor
8/02 & Later 098860401 1 1 1 1
1 1 1 1
Phase Voltage Monitor
05947530311
Power Block- RCS (Code 11= P1)
111 11
PB4 Power Block
335A 600V 030372706 11 11 1
11 11 1
111 11
Power Block
380A 600V 030372720
111 11
Power Block
335A 600V 030372717 11 11 1
11 11 1
111 11
Power Block
760A 600V 030372721
Disconnect Switch- RCS (Code 11= A2)
111 11
DS4 Disconnect Switch
100A 600V 047442101 11 11 1
11 11 1
111 11
Disconnect Switch
150A 600V 047442102
11 11 1
111 11
Disconnect Switch
225A 240V 047442103
11 11 1
111 11
Disconnect Switch
250A 600V 047442104
11 11 1
111 11
Disconnect Switch
600A 600V 047442106
11 11 1
111 11
Disconnect Switch
400A 240V 047442108
11 11 1
111 11
Disconnect Switch
400A 600V 047442109
The power connection (Power Block OR Disconnect Switch) is selected based on unit options. Any of these listed may be used. Check
installed part or Contact Daikin Applied to ensure proper replacement is selected.
2
Ground Fault is used when Code 17= YG, YC [RCS]; or YG, YB, YC, YD, YK, CG, CB, CC, CD, CK [RPS/RDT]. GFR2 is shown on Control
Panel Switch Bracket diagram.
3
PVM is used when Code 17= YP, YC [RCS]; or YP, YA, YC, YD, YH, YJ, YK, CP, CA, CC, CD, CH, CJ, CK [RPS/RDT].
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 176
Section M- Condenser Section
Condenser Control Box- RPS/RDT/RCS
Power Panel Components Until 3/05, Continued
575V
380V
460V
575V
125,135
208/230V
380V
460V
575V
208/230V
380V
460V
575V
Unit Size
105
115
208/230V
380V
460V
208/230V
080, 090
Sch Part
Part
SymDescription Number
Condenser Fan Fuse Blocks & Fuses
Speedtrol Units— Code 47= 2
FB11 Fuse Block- Condenser Fan 1
0237802021111
Fuse Block- Condenser Fan 1
023780203 111111111111
Fuse- FB110258605052222
Fuse- FB110258604372222
Fuse- FB110258604312222
Fuse- FB110258604332222
FB12 Fuse Block- Condenser Fan
0237802041111
Fuse Block- Condenser Fan
023780205 111111111111
Fuse- FB12 025860507 323232
Fuse- FB120258605053
Fuse- FB12025860405 333333333333
FB13 Fuse Block- Condenser Fan
0237802041111
Fuse Block- Condenser Fan
023780205 111111111111
Fuse- FB1302586050533
Fuse- FB13 025860507 3232
Fuse- FB13025860405 333333333333
FB14
Fuse Block- Condenser Fan02378020411
Fuse- FB1402586050533
FB15Fuse Block- Condenser Fan023780204111
Fuse- FB15025860505333
Condenser Fan Fuse Blocks & Fuses
Fantrol Units— Code 47= 1
FB12 Fuse Block- Condenser Fan
0237802041111
Fuse Block- Condenser Fan
023780205 111111111111
Fuse- FB12025860505
333 Fuse- FB120258605073
Fuse- FB12025860405 333333333333
FB13 Fuse Block- Condenser Fan
0237802041111
Fuse Block- Condenser Fan
023780205 111111111111
Fuse- FB13025860505
333
Fuse- FB130258605073
Fuse- FB13025860405 333333333333
FB14 Fuse Block- Condenser Fan
0237802041111
Fuse- FB14025860505
33
Fuse- FB1402586050733
FB15 Fuse Block- Condenser Fan
0237802041111
Fuse- FB15 025860505 3
Fuse- FB15025860507333
Condenser Fan Contactors
M11M24Contactor- Condenser Fan Motor 0417696018 88888 88888 88888
1
2
FB11 is used on speedtrol units only (Code 47= 2).
Units built prior to 3/00 used Fuse p/n 025860505.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 177
Section M- Condenser Section
Condenser Control Box
Condenser Control Box- RPS/RDT/RCS
Power Panel Components Until 3/05, Continued
575V
460/380V
208/230V
575V
460/380V
575V
208/230V
460/380V
575V
208/230V
460/380V
575V
208/230V
460/380V
575V
208/230V
460/380V
208/230V
Unit Size
080090105115125135
Sch Part
Part
SymDescription Number
RCS Units
Compressors # 1 & 2
Fuse Blocks & Fuses 1
FB1, 2 Fuse Block- Compressor 100A/250V 023780213 2
Fuse Block- Compressor200A/250V02378021822222
Fuse Block- Compressor 60A/600V0237802102
222
Fuse Block- Compressor100A/600V0237802122
222222
2
Fuse- FB1 OR FB2 025860518 6
Fuse- FB1 OR FB20258605216
6
Fuse- FB1 OR FB2025860522
66
Fuse- FB1 OR FB2 025860523 6
Fuse- FB1 OR FB2025860413
666
Fuse- FB1 OR FB2 025860414 6
Fuse- FB1 OR FB2025860415
6
6
Fuse- FB1 OR FB2025860416666
Fuse- FB1 OR FB202586041766
Fuse- FB1 OR FB2 025860418 6
RPS/RDT Units
Compressors # 1 & 2
Fuse Blocks & Fuses 1
FB1, 2 Fuse Block- Compressor 100A/250V 023780210 2 2
Fuse Block- Compressor100A/600V0237802122
2222222
2
Fuse Block- Compressor400A/250V023780213
2
Fuse Block- Compressor 60A/600V 023780215 2
Fuse Block- Compressor 100A/600V 023780216 2
Fuse Block- Compressor200A/600V023780218
22
22
Fuse- FB1 OR FB2 025860518 2
Fuse- FB1 OR FB2025860523
22
22
Fuse- FB1 OR FB2 025860524 2
Fuse- FB1 OR FB2025860414
2
Fuse- FB1 OR FB2025860415222
Fuse- FB1 OR FB2025860416
2
2
Fuse- FB1 OR FB2025860417222
Fuse- FB1 OR FB202586041822
Fuse- FB1 OR FB2 025860419 2
1
There is one Fuse Block PER compressor. On any given unit size the Fuse Block— FB1, FB2— is identical for each Compressor.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 178
Section M- Condenser Section
Condenser Control Box
Condenser Control Box- RPS/RDT/RCS
Power Panel Components Until 3/05, Continued
575V
460/380V
208/230V
575V
460/380V
575V
208/230V
460/380V
575V
208/230V
460/380V
208/230V
Unit Size
105115125135
Sch Part
Part
SymDescription Number
RCS Units
Compressors # 3 & 4
Fuse Blocks & Fuses 1
FB3, 4 Fuse Block- Compressor
100A/250V 023780213 2
Fuse Block- Compressor
200A/250V0237802182
22
Fuse Block- Compressor
60A/600V 0237802102
22
Fuse Block- Compressor
100A/600V 023780212 2 2 2 2 2
Fuse- FB3 OR FB4 025860518 6
Fuse- FB3 OR FB4 025860521 6
Fuse- FB3 OR FB4025860522
66
Fuse- FB3 OR FB4 025860413 6 6
Fuse- FB3 OR FB4 025860414 6
Fuse- FB3 OR FB40258604156
6
Fuse- FB3 OR FB4 025860416 6
Fuse- FB3 OR FB4 025860417 6 6
RPS/RDT Units
Compressors # 3 & 4
Fuse Blocks & Fuses 1
FB3, 4 Fuse Block- Compressor
100A/250V 023780210 2 2
Fuse Block- Compressor
100A/600V 023780212 2 2 2 2 2 2
Fuse Block- Compressor
400A/250V 023780213 2
Fuse Block- Compressor
200A/600V0237802182
22
Fuse- FB3 OR FB4 025860518 6
Fuse- FB3 OR FB4 025860523 6 6 6
Fuse- FB3 OR FB4 025860414 6
Fuse- FB3 OR FB4 025860415 6 6
Fuse- FB3 OR FB40258604166
6
Fuse- FB3 OR FB4 025860417 6
Fuse- FB3 OR FB4 025860418 6 6
1
There is one fuse block PER compressor. On any given unit size the fuse block— FB3, FB4— is identical for each compressor.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 179
Section M- Condenser Section
Condenser Control Box
Condenser Control Box- RPS/RDT/RCS
Power Panel Components Until 3/05, Continued
Compressor #1 Contactor- Semi Hermetic Compressors
460/380V
230V
208V
575V
460/380V
230V
208V
575V
460/380V
230V
208V
575V
460/380V
230V
208V
575V
460/380V
230V
575V
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
AL
M5 Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
PW
208V
Unit Size
080090105 115, 125
135
Sch. Part
Part
Sym. Desc.
Number
M1 Contactor 0275144011
Contactor 02751440211
Contactor 0275144031 1
Contactor 027514404111
1
1
11
111
1
Contactor 027514405111
1
1
111 1
Contactor 0275144061
1
1
1
11
1
11
11
11
Contactor 0275144071
1
0275144011
02751440211
0275144031 1
027514404111
1
1
111
0275144051
1
1
1
0275144061
1
1
11
11
11
1
0275144071
1
1
Compressor #2 Contactor- Semi Hermetic Compressors
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
575V
PW
460/380V
0275144011
02751440211
0275144031 1
027514404111
1
1
1
11
0275144051
1
11
0275144061
1
1
11
11
11
1
0275144071
1
AL
PW
AL
208V
230V
PW
AL
PW
AL
460/380V
575V
PW
AL
PW
AL
208V
230V
PW
AL
PW
AL
460/380V
575V
PW
AL
PW
AL
208V
230V
PW
AL
PW
AL
460/380V
575V
PW
AL
PW
AL
208V
230V
PW
AL
PW
AL
460/380V
575V
PW
AL
PW
AL
230V
PW
AL
AL
M6 Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
PW
208V
Unit Size
080090105
115, 125 135
Sch. Part
Part
Sym. Desc.
Number
M2 Contactor 0275144011
Contactor 02751440211
Contactor 0275144031 1
Contactor 027514404111
1
1
1
1
111
1
Contactor 027514405111
1
11
11 1
Contactor 0275144061
1
1
1
11
1
11
11
11
Contactor 0275144071
1
1
RPL 7000070 / Page 180
Section M- Condenser Section
Condenser Control Box
Condenser Control Box- RPS/RDT/RCS
Power Panel Components Until 3/05, Continued
Compressor #3 Contactor- Semi Hermetic Compressors
460/380V
230V
208V
575V
460/380V
230V
208V
575V
460/380V
230V
575V
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
AL
M7 Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
PW
208V
Unit Size
105115
125, 135
Sch. Part
Part
Sym. Desc.
Number
M3 Contactor 0275144011
Contactor 02751440211
Contactor 0275144031
Contactor 0275144041
1
1
1
1111
Contactor 0275144051
1
1
1111
Contactor 0275144061
1
111
0275144011
02751440211
0275144031
0275144041
1
1
111
0275144051
1
1
1
0275144061
1
11
Compressor #4 Contactor- Semi Hermetic Compressors
460/380V
230V
208V
575V
460/380V
230V
208V
575V
460/380V
230V
575V
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
PW
AL
AL
M8 Contactor
Contactor
Contactor
Contactor
Contactor
Contactor
PW
208V
Unit Size
105 115 125, 135
Sch. Part
Part
Sym. Desc.
Number
M4 Contactor 0275144011
Contactor 02751440211
Contactor 0275144031
Contactor 0275144041
1
1
1
1111
Contactor 0275144051
1
1
1
111
Contactor 0275144061
11
11
0275144011
02751440211
0275144031
0275144041
1
1
111
0275144051
1
1
1
0275144061
11
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 181
Section M- Condenser Section
Condenser Control Box- RPS/RDT/RCS
Control Panel Diagram & Components
Unit Sizes 080, 090 (2 compressor units)
MicroTech Controls (Code 12= 1M, 2M, 4M, 5M AND Code 08= P, F) Until 1/01
OR No Controls (Code 12= YM, YC AND Code 08= P) Until 3/05 1
Switch Bracket Detail
R
11
T10
T
B
4
GFR2 is detailed in
Power Panel
R1
R5
R9
TD1 TD5 TD11
S2
R2
R6
R
10
TD2 TD6 TD12
F2
R
12
GFR2 is detailed in
Power Panel
GFR2
REC2
GFR2
TB3
NB3
REC2
TC13
TC14
OP1
RCS
Units
CS1 CS2
PS1
PS2
CS1
CS2
PS1
PS2
RPS/
RDT
Units
This date is approximate. If the unit was built between 10/04 and 3/05,
check the GO to verify that Code 08= P, or a visual inspection is needed.
If the unit is an RPS and the unit has a condenser control box then the
above controls are used. RPS units built after 3/05 do not have a Condenser
Control Box (all condenser controls are integrated into the Main Control
Box).
1
OP2
T
B
2
Sch
Part
Sym Description
Switches- Controls
CS1, 2 Switch, Control
PS1, 2 Switch, Pumpdown- Circuit #2
S2
Switch- On/Off
RCS
Terminal Blocks- Control Panel
TB2
Terminal Block- 24V Field
RCS
TB3
Terminal Block- Field
RCS
Terminal Block- Field
RPS/RDT
TB4
Terminal Block- Factory
NB3 Neutral Block
7 Pole
Relays, Time Delays
R1, R2 Relay- High Pressure Reset
R5, R6 Relay- Compressor Safety/Cool Fail
R9, 10 Relay- Compressor Lockout
R11, 12 Relay- Low Ambient
TD1, 2 Time Delay- Comp. Lockout— 300 sec.
Until 12/98
Time Delay- Comp. Lockout— 300 sec.
12/98 & Later
TD5, 6 Time Delay- Part Winding (Code 10= PW)
1 sec.
TD11, 12 Time Delay- Low Ambient
2.75 min.
Transformer
T10
Transformer- Speedtrol (C47= 2)
RCS only until 5/02
Transformer- Speedtrol (C47= 2) RCS only 5/02 & Later
Temperature & Pressure Controls
TC13, 14 Fantrol Control (Code 47= 1, 2)
DPDT
OP1, 2 Oil Pressure Control
Control Fuse & Receptacle
F2
Fuse- Control Circuit
RCS
Holder- F2
RCS
REC2 Receptacle- GFI
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Part
Unit Size
Number 080090
001355000
001355000
001355000
2
2
1
2
2
1
022431209
022431224
015998130
015998124
037530800
1
1
1
1
1
1
1
1
1
1
032508101
073340001
032508101
032508101
028210108
028210138
028210101
032358500
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
046738109
060614101
1
1
1
1
065498401
047357604
2
2
2
2
025954700
018690600
039003600
1
1
1
1
1
1
RPL 7000070 / Page 182
Section M- Condenser Section
Condenser Control Box- RPS/RDT/RCS
Control Panel Diagram & Components
Unit Sizes 105, 115, 125, 135 (4 compressor units)
MicroTech Controls (Code 12= 1M, 2M, 4M, 5M AND Code 08= P, F) Until 1/01
OR No Controls (Code 12= YM, YC AND Code 08= P, F) Until 3/05 1
R3
T10
T
B
4
R1
R2
R4
TD3
Switch Bracket Detail
R
11
R7
TD7
R5
R9
TD1 TD5 TD11
S2
R6
R
10
TD2 TD6 TD12
F2
R8
TD8
TD4
GFR2 is detailed in
Power Panel
R
12
GFR2 is detailed in
Power Panel
GFR2
REC2
REC2
TC13
OP1
TC14
OP3
OP2
OP4
T
B
2
PS1
PS2
CS1
CS2
PS1
PS2
GFR2
TB3
NB3
CS1 CS2
RCS
Units
RPS/
RDT
Units
This date is approximate. If the unit was built between 10/04 and 3/05, check
the GO to verify that Code 08= P, or a visual inspection is needed. If the unit
is an RPS and the unit has a condenser control box then the above controls
are used. RPS units built after 3/05 do not have a Condenser Control Box
(all condenser controls are integrated into the Main Control Box).
1
Sch
Part
Part Unit Size
Sym Description Number 105115125135
Switches- Controls
CS1, 2Switch, Control
0013550002222
PS1, 2 Switch, Pumpdown- Circuit #2 001355000 2
2
2
2
S2 Switch- On/Off
RCS
0013550001111
Terminal Blocks- Control Panel
TB2
Terminal Block- 24V Field
RCS 022431209 1
1
1
1
TB3 Terminal Block- Field
RCS
0224312241111
Terminal Block- Field
RPS/RDT
0159981301111
TB4 Terminal Block- Factory
0159981241111
NB3 Neutral Block
7 Pole
0375308001111
Relays, Time Delays
R1, 2
Relay- High Pressure Reset 019643000 2
2
2
2
R3, 4
Relay- High Pressure Delay
1/02 & Later 032508101 2
2
2
2
R5, 6 ,7, 8 Relay- Compressor Safety/Cool Fail 047356603 4
4
4
4
R9, 10 Relay- Compressor Lockout 032508101 2
2
2
2
R11, 12 Relay- Low Ambient 032508101 2
2
2
2
TD1, 2 Time Delay- Comp. Lockout— 300 sec.
Until 12/98 028210108 2
2
2
2
Time Delay- Comp. Lockout— 300 sec. 12/98 & Later 028210138 2
2
2
2
TD3, 4 Time Delay- Hi Pressure
1/02 & Later 111056701 2
2
2
2
TD5, 6, 7, 8 Time Delay- Part Winding (Code 10= PW)
1 sec. 028210101 4
4
4
4
TD11, 12 Time Delay- Low Ambient
2.75 min. 032358500 2
2
2
2
Transformer
T10
Transformer- Speedtrol (C47= 2) RCS only Until 5/02 046738109 1
1
1
1
Transformer- Speedtrol (C47= 2) RCS only 5/02 & Later 060614101 1
1
1
1
Temperature & Pressure Controls
TC13, 14 Fantrol Control (Code 47= 1, 2)
DPDT 065498401 2
2
2
2
OP1, 2, 3, 4 Oil Pressure Control 047357604 4
4
4
4
Control Fuse & Receptacle
F2 Fuse- Control Circuit
RCS
0259547001111
Holder- F2
RCS
0186906001111
REC2Receptacle- GFI
0390036001111
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 183
Section M- Condenser Section
Condenser Control Box- RPS/RDT/RCS
Control Panel Diagram & Components
Unit Sizes 080, 090 (2 compressor units)
MicroTech II Control Panel (Code 12= *D, *S AND Code 08= P, F) 1/01 thru 3/05 1
Switch Bracket Detail
T9
TD5
R1
CCB1
R2
S2
CCB2
GFR2 is detailed in
Power Panel
TB3
NB3
OP1
F2
RES
T
B
4
GFR2 is detailed in
Power Panel
TD6
OP2
GFR2
REC2
GFR2
REC2
T
B
2
PS1
PS2
CS1
CS2
PS1
PS2
RPS/
RDT
Units
This date is approximate. If the unit was built between 10/04 and 3/05,
check the GO to verify that Code 08= P, F OR a visual inspection is needed.
If the unit is an RPS and the unit has a Condenser Control Box then the
above controls are used. RPS units built after 3/05 do not have a Condenser
Control Box (all condenser controls are integrated into the Main Control Box).
1
Sch
Part
Sym Description
Switches- Controls
CS1, 2 Switch, Control
PS1, 2 Switch, Pumpdown- Circuit #2
S2
Switch- On/Off
RCS
Terminal Blocks- Control Panel
TB2
Terminal Block- 24V Field
RCS
TB3
Terminal Block- Field
RCS
Terminal Block- Field
RPS/RDT
TB4
Terminal Block- Factory
RCS
Terminal Block- Factory
RPS/RDT
NB3 Neutral Block
7 Pole
Relays, Time Delays
R1, 2 Relay- High Pressure Reset
TD5, 6 Time Delay- Part Winding (Code 10= PW)
1 sec.
Transformer
T9
Transformer- Control Board
120- 24V
Pressure Controls
OP1, 2 Oil Pressure Control
Control Fuse & Receptacle
F2
Fuse- Control Circuit
RCS
Holder- F2
RCS
REC2 Receptacle- GFI
Control Boards
CCB1, 2 Compressor Controller
Standoff- Compressor Controller
Communication Board
Standoff- Communication Board
RES Resistor Assy- CCB1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” RCS
Units
CS1 CS2
Rev. AG 01/15
Part
Unit Size
Number 080090
018446400
001355000
001355000
2
2
1
2
2
1
022431209
022431230
015998130
015998109
015998114
037530800
1
1
1
1
1
1
1
1
1
1
1
1
032508101
028210101
2
2
2
2
060630801
1
1
047357604
2
2
025954700
018690600
039003600
1
1
1
1
1
1
112026101 2
048166705 14
060006202 2
048166707 8
060003901 1
2
14
2
8
1
RPL 7000070 / Page 184
Section M- Condenser Section
Condenser Control Box- RPS/RDT/RCS
Control Panel Diagram & Components
Unit Sizes 105, 115, 125, 135 (4 compressor units)
MicroTech II Control Panel (Code 12= *D, *S AND Code 08= P, F) 1/01 thru 3/05 1
T
B
4
R11
TD7
R12
TD8
R1
TD5
R2
TD6
CCB1
OP3
GFR2 is detailed in
Power Panel
S2
F2
TD3 R3 TD4 R4
GFR2 is detailed in
Power Panel
TB3
NB3
OP1
Switch Bracket Detail
CCB2
RES
T9
OP2
OP4
GFR2
REC2
GFR2
REC2
T
B
2
CS1
CS2
PS1
PS2
CS1 CS2
PS1
PS2
RCS
Units
RPS/
RDT
Units
This date is approximate. If the unit was built between 10/04 and 3/05,
check the GO to verify that Code 08= P, F OR a visual inspection is needed.
If the unit is an RPS and the unit has a Condenser Control Box then the
above controls are used. RPS units built after 3/05 do not have a Condenser
Control Box (all condenser controls are integrated into the Main Control Box).
1
Sch
Part
Part Unit Size
Sym Description Number 105115125135
Switches- Controls
CS1, 2Switch, Control
0184464002222
PS1, 2 Switch, Pumpdown- Circuit #2 001355000 2
2
2
2
S2 Switch- On/Off
RCS
0013550001111
Terminal Blocks- Control Panel
TB2
Terminal Block- 24V Field
RCS 022431209 1
1
1
1
TB3 Terminal Block- Field
RCS
0224312301111
Terminal Block- Field
RPS/RDT
0159981301111
TB4 Terminal Block- Factory
RCS
0159981091111
Terminal Block- Factory
RPS/RDT
0159981141111
NB3 Neutral Block
7 Pole
0375308001111
Relays, Time Delays
R1, 2
Relay- High Pressure Reset 032508101 2
2
2
2
R3, 4
Relay- High Pressure Delay
1/02 & Later 032508101 2
2
2
2
R11, 12 Relay- Low Ambient
1/02 & Later 032508101 2
2
2
2
TD3, 4 Time Delay- High Pressure 111056701 2
2
2
2
TD5, 6, 7, 8 Time Delay- Part Winding (Code 10= PW)
1 sec. 028210101 4
4
4
4
Transformer
T9
Transformer- Control Board
120- 24V 060630801 1
1
1
1
Pressure Controls
OP1, 2, 3, 4
Oil Pressure Control
0473576042222
Control Fuse & Receptacle
F2 Fuse- Control Circuit
RCS
0259547001111
Holder- F2
RCS
0186906001111
REC2Receptacle- GFI
0390036001111
Control Boards
CCB1, 2
Compressor Controller
1120261012222
Standoff- Compressor Controller04816670514141414
Communication Board
0600062022222
Standoff- Communication Board
0481667078888
RES Resistor Assy- CCB1
0600039011111
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 185
Section M- Condenser Section
Condenser Control Box (RCS Units Only)
MicroTech II OR No Controls 3/05 & Later
Diagrams
Condenser Control Box- With Factory Installed Controller:
Code 12= *D, *S (shown w/ Fantrol [Code 47=1])
Unit Size 135 Shown
GFS4
PB
41
GFR4
DS4 or
PB4
MMP1 MMP5 MMP3 MMP7 MMP2 MMP6 MMP4 MMP8
Left Side
M1
M5
M3
M7
M2
M6
M4
M8
TB8
Standoff
Expansion Board
Standoff
CCB
Controller
Detail
Comm. Card
M24 M23 M22 M21
M14 M13 M12 M11
T9
PVM4
RES
CCB1
MMP23 MMP21
CCB2
R1 R2
MMP13 MMP11
TB5
TB3
Right Side
TB6
CS1CS2 S2
PL28 PL29 PL30
PS1 PS2
REC2
OP1 1
TB1
OP3 1
OP2 1
PL25 PL26 PL27
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
OP4 1
1
Oil Pressure Controls
are only used on units
with Semi-Hermetic
Discus Compressors
(Code 44= H, K).
OP3, 4 are used only on
sizes 080, 090.
RPL 7000070 / Page 186
Section M- Condenser Section
Condenser Control Box (RCS Units Only)
MicroTech II OR No Controls 3/05 & Later
Diagrams, Continued
Condenser Control Box- With No Controller and Scroll Compressors:
Code 12= YM (208/230V shown w/ Speedtrol [Code 47=2])
Unit Size 105 Shown
GFS4
PB
41
GFR4
DS4 or
PB4
MMP1 MMP3 MMP5
MMP2 MMP4 MMP6
Left Side
M1
M3
M2
M5
M4
M6
TB8
TD1 TD2 TD11 TD12
M24 M23 M22 M14 M13 M12
M21 M11
FB12FB11
PVM4
MMP24 MMP22
MMP12
R
5.1
R
6.1
R
5.2
R
7.1
R
6.2
R
8.1
R
7.2
R
9
R
8.2
R
11
R
10
TB3
T10
PL28 PL29 PL30
R
1
R
12
TB5
R
13.1
R
2
R
14.1
R
13.2
R
14.2
TB6
Right Side
CS1 CS2 S2
PS1 PS2
TB1
REC2
PL25 PL26 PL27
TC14
TC12
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 187
Section M- Condenser Section
Condenser Control Box (RCS Units Only)
MicroTech II OR No Controls 3/05 & Later
Diagrams, Continued
Condenser Control Box- With No Controller and Discus Compressors:
Code 12= YM (shown w/ Fantrol [Code 47=1])
Unit Size 135 Shown
GFS4
PB
41
GFR4
DS4 or
PB4
MMP1 MMP5 MMP3 MMP7 MMP2 MMP6 MMP4 MMP8
Left Side
M1
M5
M7
M3
M2
M6
M4
M8
TB8
TD1 TD2 TD11 TD12 TD3 TD4 TD5 TD6 TD7 TD8
M24 M23 M22 M14 M13 M12 M21 M11
PVM4
MMP22
MMP21
MMP12
R
5.1
MMP11
R
6.1
R
5.2
R
7.1
R
6.2
R
8.1
R
7.2
R
9
R
8.2
R
11
R
10
R
1
R
12
TB3
TB5
OP3
OP2
R
3
R
2
R
4
Right Side
TB6
CS1 CS2 S2
PS1 PS2
PL28 PL29 PL30
TB1
REC2
OP1
PL25 PL26 PL27
TC
13
OP4
TC
14
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 188
Section M- Condenser Section
Condenser Control Box (RCS Units Only)
MicroTech II OR No Controls 3/05 & Later
Components
Sch.
Part
Sym. Description
Controller (Code 12= DS)
CCB1, 2 Expansion Board- Compressor Controller
Standoff- Expansion Board
Comm. Card- Bacnet
Standoff- Comm. Card
RES Resistor- CCB1
Switches- Control
PS1, 2Switch- Pumpdown
CS1, 2 Switch- Control
with factory controller (Code 12= DS)
with no controller (Code 12= YM)
S2 Switch- System
Receptacle
REC2Receptacle
Time Delays
TD1, 2 Time Delay, 300Sec.- Compressor Lockout
TD3, 4 Time Delay, 5 Sec.- High Pressure
TD5, 6, 7, 8 Time Delay, 1 Sec.- Part Winding
TD11, 12 Time Delay, 165 Sec.- Speedtrol
Temp. Controls
TC12 Temperature Control- Fantrol
TC13 Temperature Control- Fantrol
TC14Temperature Control- Fantrol
Ground Fault Protection
GFR4 Ground Fault Relay- SPDT
GFS4Ground Fault Sensor
Phase Voltage Monitor
PVM4 Phase Voltage Monitor
208/230/460V Units
575V Units
Plugs
PL25- 30 Plug- 12 Pin
Transformers
T9
Transformer, 24V- Refrigeration Circuit
T10
Transformer, 280/240-24V- Speedtrol/No Controls
Contactors
M1- 8 Contactor- Compressors
M11- 24 Contactor- Fan Motors
Manual Motor Protector
MMP1- 8 MMP- Compressors
MMP11- 24 MMP- Fan Motors
Speedtrol Fuses and Parts
FB11,12 Fuses- Speedtrol Fan
Part Unit Size
Number 080090 105115125135
112026101 2 2
2 2 2 2
048166705 1414 14141414
06000620222 2222
04816670788 8888
06000390111 1111
00135500022 2222
018446400 2 2
2 2 2 2
001355000 2 2
2 2 2 2
00135500011 1111
03900310011 1111
028210138
111056701
028210101
032358500
2 2
2 2 2 2
242424242424
242444444444
2 2
2 2 2 2
065498401 1 31 31 3
065498401 1 41 41 41 11
06549840111 1111
349937502 1 1
1 1 1 1
34993740711 1111
11202200111 1111
11202200211 1111
349930405
349937201
349931703
1/comp 1/comp 1/comp 1/comp 1/comp 1/comp
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
For units built between 10/06 & 12/06 contact Daikin Applied. For units built 1/07 & Later use p/n 349930621. PN is for one section.
These components are installed in the RCS unit Condenser Control Box, OR the RPS/RDT unit Main Control Box. The Compressor
and Condenser Fan Motor Contactors and MMP’s and associated parts are detailed in the Main Control Box Section (Section N).
3
Scroll Compressor units only (Code 44= Z, T).
4
Discus Compressor units only (Code 44= H , K).
5
P/N 349931703 was used on units built before 12/08.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 189
Section M- Condenser Section
Condenser Control Box (RCS Units Only)
MicroTech II OR No Controls 3/05 & Later
Components, Continued
Sch.
Part
Part
Unit Size
Sym. Description Number 080090105115125135
Pressure Controls
OP1, 2,3,4 Oil Pressure Controls 047357604 232343434343
Terminal Blocks
TB1
Terminal Block 349930605 1var.var.var.var.var.var.
TB3,5,6,8 Terminal Block 349930603 1var.var.var.var.var.var.
Relays, Time Delays, Temp. Controls Until 10/06 2
R1, 2Relay- Hi Pressure Reset349934704222222
R3, 4 Relay- Hi Pressure Delay 349934704
2 2 2
R5.1,5.2
Relay- Safety349934704222222
R6.1,6.2
Relay- Safety349934704222222
R7.1,7.2
Relay- Safety349934704222222
R8.1,8.2
Relay- Safety349934704222222
R9, 10Relay- Compressor Lockout349934704222222
R11, 12
Relay- Speedtrol Fan Cycling349934704222222
R13.1,13.2
Relay- Safety349934704222
R14.1,14.2
Relay- Safety349934704222
Relays, Time Delays, Temp. Controls 1/07 & Later 2
R1, 2Relay- Hi Pressure Reset349934724222222
R3, 4 Relay- Hi Pressure Reset 349934724
2 2 2
R5.1,5.2
Relay- Safety349934724222222
R6.1,6.2
Relay- Safety349934724222222
R7.1,7.2
Relay- Safety349934724222222
R8.1,8.2
Relay- Safety349934724222222
R9, 10Relay- Compressor Lockout349934724222222
R11,12Relay- Speedtrol Fan Cycling349934724222222
R13.1,13.2
Relay- Safety349934724222
R14.1,14.2
Relay- Safety349934724222
Disconnect Switch (Code 11= A2)
Until 10/06 2
DS4
Switch- Disconnect 100A 349935101 1111111
Handle- Disconnect 349935501111111
Switch- Disconnect 150A 349935102 1
111111
Handle- Disconnect 349935501111111
Switch- Disconnect 250A 349935201 1111111
Handle- Disconnect 349935501111111
Switch- Disconnect 400A 349935301 1111111
Handle- Disconnect349935602111111
Switch- Disconnect 600A 349935302 1111111
Handle- Disconnect 349935602111111
PB41 Power Block- Distribution (used with DS4)
175A 030372730 1111111
Power Block- Distribution (used with DS4)
310A 030372744 1111111
Power Block- Distribution (used with DS4)
420A 030372752 1111111
Any of the listed parts may be used, depending on unit options. Check installed part to verify, or contact Daikin Applied with unit serial and/
or GO number to ensure correct replacement is selected.
2
For units built between 10/06 & 12/06 Contact Daikin Applied.
3
Discus Compressor units only (Code 44= H, K).
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 190
Section M- Condenser Section
Condenser Control Box (RCS Units Only)
MicroTech II OR No Controls 3/05 & Later
Components, Continued
Sch.
Part
Part
Unit Size
Sym. Description Number 080090105115125135
Disconnect (Code 11= A2)
1/07 & Later 2
DS4
Switch- Disconnect 100A 349935125 1
Handle- Disconnect 349935521111111
Shaft Mod349962208111111
Lug- Ground349938001111111
Switch- Disconnect 150A 349935126 1
Handle- Disconnect 349935532111111
Shaft Mod349962209111111
Lug- Ground349938001111111
Switch- Disconnect 250A 349935226 1
Handle- Disconnect 349935532111111
Shaft Mod349962209111111
Lug- Ground349938001111111
Switch- Disconnect 400A 349935325 1
Handle- Disconnect 349935621111111
Shaft Mod349962210111111
Lug- Ground349938002111111
Switch- Disconnect 3
600A193438002 1
Handle- Disconnect 3193437901111111
Shaft Mod 3349962241111111
Lug- Ground349938002111111
PB41 Power Block- Distribution (used with DS4)
100A- 400A DS4 030372785 1111111
600A DS4 030372786 1111111
Power Block- Main (Code 11= P1)
Until 10/06 2
PB4
Power Block
175A 030372749 1
111111
Cover- Power Block349938302111111
Power Block
310A 030372749 1
111111
Cover- Power Block349938302111111
Power Block
420A 030372752 1
111111
Cover- Power Block349938302111111
Power Block
760A 030372728 1
111111
Cover- Power Block349938303111111
Power Block- Main (Code 11= P1)
1/07 & Later 2
PB4
Power Block
175A, 310A, 420A 030372785 1
111111
Power Block
760A 030372721 1
111111
Cover- Power Block
760A only349938345111111
Any of the listed parts may be used, depending on unit options. Check installed part to verify, or contact Daikin Applied with unit serial and/
or GO number to ensure correct replacement is selected. Handles include Operating Mechanism.
2
For units built between 10/06 & 12/06 Contact Daikin Applied.
3
Note that the original Disconnect is obsolete. Due to dimensional differences minor field modifications may be required for proper
installation.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 191
Section M- Condenser Section
Condenser Control Box (RCS Units Only)
MicroTech III Controls 9/08 & Later
Diagram
Condenser Control Box- Unit Size 135 Shown
GFS4
GFR4
DS4 or
PB4
MMP1 MMP5 MMP3 MMP7 MMP2 MMP6 MMP4 MMP8
Left Side
M1
M5
M7
M3
M2
M6
M4
M8
TB8
M24 M23 M22 M14 M13 M12
Speedtrol Units
(Code 47= 2)
M21 M11
FB12FB11
MMP24 MMP22
Fantrol Units (Code 47= 1, 3)
MMP12
M24 M23 M22 M21 M14 M13 M12 M11
R13
PVM
4
MMP23 MMP21
R12 R14
MMP13 MMP11
TB3
TB5
TB6
Right Side
PL28 PL29 PL30
REC2
TB1
PL25 PL26 PL27
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 192
Section M- Condenser Section
Condenser Control Box (RCS Units Only)
MicroTech III Controls 9/08 & Later
Components
Sch.
Sym.
R12
R13
R14
Part
Part Unit Size
Description Number 080 090 105115125135
Relays
Relay- Condenser Fans Fans 12 & 22 349934724 1
1 1 1 1 1
Relay- Condenser Fans Fans 13 & 23 349934724 1
1 1 1 1 1
Relay- Condenser Fans Fans 14 & 24 349934724 1
1 1 1 1 1
Receptacle
REC2 Receptacle 039003600 1 1 1 1 1 1
Ground Fault Protection
GFR4 Ground Fault Relay- SPDT 349937502
GFS4 Ground Fault Sensor 349937407
1
1
1
1
1
1
1
1
1
1
1
1
Phase Voltage Monitor
PVM4 Phase Voltage Monitor
208/230/460V Units 112022001
575V Units 112022002
1
1
1
1
1
1
1
1
1
1
1
1
Power Block- Main (Code 11= P1)
PB4
Power Block
175A, 310A, 420A 030372785 11 1 1 1 1 1
Power Block
760A 030372721 11 1 1 1 1 1
Cover- Power Block
760A only 349938345 1
1 1 1 1 1
Disconnect (Code 11= A2)
DS4
Switch- Disconnect 100A 349935125 1
Handle- Disconnect 349935521
Shaft Mod 349962208
Lug- Ground 349938001
Switch- Disconnect 150A 349935126 1
Handle- Disconnect 349935532
Shaft Mod 349962209
Lug- Ground 349938001
Switch- Disconnect 250A 349935226 1
Handle- Disconnect 349935532
Shaft Mod 349962209
Lug- Ground 349938001
Switch- Disconnect 400A 349935325 1
Handle- Disconnect 349935621
Shaft Mod 349962210
Lug- Ground 349938002
Switch- Disconnect 2
600A193438002 1, 2
2
Handle- Disconnect 193437901
Shaft Mod 2349962241
Lug- Ground 349938002
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 1 1 1 1
1 1 1 1 1
1
1 1 1 1
Any of the listed parts may be used, depending on unit options. Check installed part to verify, or contact Daikin Applied with unit
serial and/or GO number to ensure correct replacement is selected. Handles include Operating Mechanism.
2
Note that the original Disconnect is obsolete. Due to dimensional differences minor field modifications may be required for proper
installation.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 193
Section M- Condenser Section
Condenser Control Box (RCS Units Only)
MicroTech III Controls 9/08 & Later
Components, Continued
Sch.
Sym.
TB1- 8
Part
Part Unit Size
Description Number 080 090 105115125135
Terminal Blocks
Terminal Block 349930641 1 var. var. var.var.var.var.
Plugs
PL25- 30 Plug- 12 Pin 349930405
Contactors
M1- 8 Contactor- Compressors
M11- 24 Contactor- Fan Motors
2
Manual Motor Protector
MMP1- 8 MMP- Compressors
MMP11- 24 MMP- Fan Motors
2
Speedtrol Fuses and Parts
FB11, 12 Fuses- Speedtrol Fan
1
2
1/comp 1/comp 1/comp 1/comp 1/comp 1/comp
2
2
2
Part number is for one section. Quantity varies with unit options.
These components are installed in the RCS unit Condenser Control Box, or the RPS/RDT unit Main Control Box. The Compressor
and Condenser Fan Motor Contactors and MMP’s and associated parts are detailed in the Main Control Box Section (Section N).
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 194
Section M- Condenser Section
Speedtrol Control Box and Transformer
RPS/RDT/RCS
Speedtrol Box Motor #11
(see detail right)
Box Detail
Speedtrol Box Motor #21
(see detail right)
13
10
14
C11
or
C21
Condenser Control Box
(RCS Units, RPS units until 3/05)
Speedtrol Transformer- RCS Units
SC11
or
SC21
Speedtrol Transformer- RPS Units
(080- 105 shown)
7
7
T11
T11
Ref Sch
Part
Part
No Sym Description Number 208V 230V380V460V575V
7
T11
Transformer- Speedtrol 037533625
1
Transformer- Speedtrol
0375336051
Transformer- Speedtrol
0375336191
10 SC11, 21 Control, Pressure- Speedtrol
7/03 & Later 048445211 2
2
Control, Pressure- Speedtrol
Until 7/03 048445202 2
2
Control, Pressure- Speedtrol 048445203
2
2
2
2
2
13 C11, 21 Capacitor, Run- Speedtrol
30MFD/440V 037516429 2
2
2
2
2
14 Strap- Capacitor
028765100
2 2222
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 195
Section M- Condenser Section
Factory Supplied Line Voltage Box- Code 18= U***, V***
(Powers Receptacle and Lights)
T6, DS6, FU6A, FU6B, FU6C
2
9
L1 L2 L3
DS6
T6
8
3
FU6C
FU6B
FU6A
T1 T2 T3
575V
460V
230V
208V
Voltage
Ref Sch
No Sym
2 T6
Part
Description
Transformer
2KVA
Transformer
2KVA
Transformer
2KVA
Part
Number
3499870011
349987002 11
349987003 1
3
Disconnect Switch
349991901 1 1 1 1
DS6
8 FU6A,B Fuse
FU6A,BFuse
FU6A,B Fuse
9 FU6C Fuse
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” 30A/600V
20A/600V 19340371122
10A/600V 193403708 2
8A/600V 193403707 2
20A/600V 193403711 1 111
Rev. AG 01/15
RPL 7000070 / Page 196
Section N- Main Control Box
Notes
➩
➩
Primary Codes that pertain: 08, 09, 10, 11, 12, 13, 14, 15, 17, 18
Additional Codes that pertain: 04, 19, 20, 22, 27, 32, 34, 35, 40, 44, 47
The Main Control Box applies to the RPS, RFS, and RDT. The RCS has its own Controls that are detailed in Section M.
There have been five generations of Main Control Boxes offered:
1. Original MicroTech Controls (Code 08= P, S AND Code 12= 1M, 2M, 4M, 5M) were used until 12/2000. This panel had a Main
Processor (MCB) and a Keypad mounted on the Deadfront Door Assembly, an Output Board with a varying (depending upon
unit options) number of relays, and an ADI (Analog/Digital Interface) OR Daughter board mounted in the Control Panel. This two
control panel design housed the Condenser controls in a separate Condenser Control Box.
2. The MicroTech II Control Box (Code 08= P, S AND Code 12= *D, *S) was introduced January, 2001. This MicroTech II box
had the Main Processor (MCB) mounted in the Control Panel with the Keypad mounted in the Deadfront Door.
NOTE: The Power Panel components for both of the above were the same, and in the case of the RPS, units with either of these
Main Boxes still had a separate Condenser Control Panel.
3. A redesigned MicroTech II Control Box (Code 08= D, F AND Code 12= *D, *S) was offered beginning in October of 2004
and was used exclusively after March, 2005. There is a MCB as well as two Compressor Control Boards (CCB1 & CCB2) in the
Control Panel. The new panel incorporates the Condenser Section controls as well. Consequently, RPS and RDT units no longer
have a separate Condenser Control Box. This design was offered until the end of 2006.
4. Starting in 10/06, and used exclusively after 01/2007, a change was made to the MicroTech II Control Box that changed the
vendor for Contactors, Motor Protectors, Relays, etc. Note that components and component accessories such as Auxiliaries,
Links, etc. are NOT interchangeable with the previous design. MicroTech II controls were offered until the end of 2008.
5. The MicroTech III Control Box (Code 12= *E, *F) was offered beginning in 11/2008. There is an MCB as well as separate
Expansion Boards/Modules. The Power Panel components are the same as the later MicroTech II design.
Units may also have no unit controls (Code 12= YM, YC) in which case the Main Control Box has no MCB or Expansion Boards/
Modules, but instead has a set of Relays.
Code 08 determines which generation of Control Box is installed- “P, F” is the original design (where the RPS condenser section
has its own Control panel); “D, S” indicates the later single panel design Code 09 is the unit voltage and affects Transformers,
Fan Overloads/MMPs, Contactors, Fuses, etc. Code 10 indicates whether the starting option is Across-the-Line or Part-Winding.
Code 11 determines whether the main power connection is a Terminal Block or a through-the-door Disconnect Switch. Code 12
selects whether or not the unit has MicroTech controls or controls by others, the communication type, and the type of temperature
control specified. Code 13 determines the presence of Duct Sensors, and associated Relays. Codes 14 and 15 determine presence
of Supply and Return Fan Variable Inlet Vanes OR VFD/Inverter(s). Code 17 determines whether there is a PVM, GFR, and/or
Line Reactor installed. Code 18 indicates whether a unit has a Keypad Display (remote or unit mounted), and/or if a Modem is
present (original MicroTech).
Codes 19, 20, and 22 are return air codes, and impact several controls options. The presence of an OA hood, the horsepower of
the Return Air Motor, etc, have an impact on Fan Overloads/MMPs, Contactors, Fuses, and duct sensors. Code 27 determines
the draw through section, and can impact the Cooling Circuit Relays. Code 32 determines horsepower for the Supply Fan Motor
which, like the Return Air Motor, have an impact on Contactors, Overloads/MMPs, Fuses, and Sensors.
Codes 04, 34, and 35 determine the Blow-Thru section, and the heat type, which will impact Transformers, Heat Circuit Relays,
and Cooling Circuit Relays.
Code 40 determines if there is a VAV/Discharge Damper and associated Relay.
Code 44 determines whether the unit has Semi-hermetic (Discus) Compressors OR Scroll Compressors (which affect Power
Panel components).
Code 47 determines if the unit has FanTrol OR SpeedTrol fan control which affects Condenser Fan fusing (MicroTech II AND
III only).
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 197
Section N- Main Control Box
Control Panel- Units with MicroTech Controls
(Code 12= 1M, 2M, 4M, 5M)— Until 1/01
Diagram
F3
Terminal Block - T4
T5
T4
Rectifier
T2
T3
R69
R67 R68 R65 R66
R
28
MCB 1
R
24
R27
OBA
T
B
6
DHL
R29
SB1
OBB
SB2
OBC
R26
R20 TD19 TD9
N
B
1
ADI 2
Keypad
S6
S1 HS1PS3
Deadfront Door
(shown open)
F1
1
1
REC1 GFR1 GFR2
S4 S5
T
B
7
T
B
8
T
B
5
T
B
10
TB2
TB2
N
B
2
SPS SPS
1
2
TB1
Remote Monitor Panel
Part Description
Status Panel- Honeywell Model W950F
Includes:
- Switches: Fan On/Off & System Heat/Auto/Cool
- 6 Lights, with 4 and 6 light cover plate
(Does not include Economizer Minimum Position
Potentiometer)
Part Number
065491505 3
GFR1 & GFR2 are detailed with the GFS1, GFS2 in the Power Panel section.
Early units had a Daughter Board (DB1).
3
Contact Daikin Applied to confirm availability.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 198
Section N- Main Control Box
Control Panel- Units with MicroTech Controls
(Code 12= 1M, 2M, 4M, 5M)— Until 1/01
Components
Sch. Part Part
Sym.
Description
Number Qty.
Switches
S1
Toggle Switch- Control: Units with Gas Heat
(Code 04= A 018446400 1
Toggle Switch- Control: Units without Gas Heat (Code 04= E, W, S, Y, X) 001355000 1
S4, 5
Toggle Switch- Inverters (Code 14= 1-9, X) 028798400 1
Connector Bar- S4, S5 033250200 1
S6
Switch- VIV Units
(Code 15= 2) 047357306 1
HS1
Switch- Electric Heat Shutdown
(Code 04= E) 001355000 1
PS3
Toggle Switch- Unit Pumpdown 001355000 1
Fusing
F1
Fuse- Control Circuit- 15A/250V 025954700 1
Fuse Holder for F1 018690600 1
F3
Fuse- 500- 1000 MBH Gas Heat Burner Motor 025860505 1
Fuse- 1100- 2000 MBH Gas Heat Burner Motor 025860507 1
Fuse Holder for F3 023780201 1
Receptacle
REC1
Receptacle- Standard, 1P/3W/15A 025283700 1
Receptacle- Duplex Feed thru GF1, 2P/3W/15A 039003100 1
Receptacle- Duplex GF1, 2P/3W/15A 039003600 1
Receptacle- Duplex Feed thru GF1, 2P/3W/20A 066402701 1
Terminal Blocks
TB1
Terminal Block- Service Receptacle Circuit, 115V Field, 3 Pole 022431203 1
TB2
Terminal Block- Field
Code 12= 2M, 4M, 5M- units with inverter (14 pole portion) 022431214 1
Code 12= 2M, 4M, 5M- units with inverter (24 pole portion) 022431224 1
Code 12= 1M- units with inverter 022431230 1
Code 12= 2M, 4M, 5M- units with no inverters 022431230 2
Code 12= 1M- units with no inverters (14 pole portion) 022431214 1
Code 12= 1M- units with no inverters (24 pole portion) 022431224 1
TB5
Terminal Block- Control 015998130 1
TB6
Terminal Block- Control 015998120 1
TB7
Terminal Block- Factory 015998130 1
TB8
Terminal Block- Inverters 015998114 1
TB10
Terminal Block- Heating 015998109 1
NB1, 2
Neutral Block, 7 Pole 037530800 2
Transformers
T2
Transformer- Unit 060630801 1
T3
Transformer- Controller 046738114 1
T4
Transformer- Power Relief Dampers
Until 5/02 046738109 1
5/02 & Later 060614101 1
Rectifier- T4 111059401 1
Terminal Block- T4 & Rectifier 065499806 1
T5
Transformer- Specials 060630801 1
Time Delays
TD9
Time Delay- Supply Fan PW
028210101 1
TD19
Time Delay- Supply Fan PW 028210101 1
Relays
R20
Relay- Gas Heat On/Off 019643000 1
R24
Relay- Gas Heat Alarm 032508101 1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 199
Section N- Main Control Box
Control Panel- Units with MicroTech Controls
(Code 12= 1M, 2M, 4M, 5M)— Until 1/01
Components
Sch. Part Part
Sym.
Description
Number Qty.
Relays, continued
R26
Relay- Occupied/Unoccupied 019643000 1
R27
Relay- Powered Relief Dampers 019643000 1
R28
Relay- Isolation Damper 032508101 1
R29
Relay- Final Filter 026213000 1
R65
Relay- PW Fan 073340001 1
R66
Relay- PW Fan 073340001 1
R67
Relay- Supply Fan with inverter 019643000 1
R68
Relay- Return Fan with inverter 019643000 1
R69
Relay- Inverter with Bypass 032508101 1
Relay- Inverter without Bypass 019643000 1
Transducer and Pressure Controls
SPS1
Sensor- Duct Static Pressure
(Code 13= 1, 2, 3) 049545005 1
SPS2
Sensor- Duct Static Pressure (Code 13= 2) 049545005 1
Sensor- Building Static Pressure (Code 13= 3, 4) 049545006 1
DHL
Switch- Duct Hi- Limit 065493801 1
Fitting for DHL 049763002 1
Main MicroTech Controller and Associated Boards
MCB1
Microprocessor (must be programmed- requires unit GO or Serial No.) 065487306 1
Fuse- MCB1 065822001 1
Keypad
Keypad/Display Assembly 065497201 1
Ribbon Cable- MCB to Keypad 065499702 1
ADI
ADI Board 1065816005 1
OBA
Output Board- 16 position 066542201 1
Ribbon Cable- MCB to OBA 049265204 1
OBB
Output Board- 4 position- Cooling 066542203 13
OBB
Output Board- 8 position- Cooling 066542202 14
OBC
Output Board- 8 position- Heating 066542202 15
OB_ _
Output Board Relay
2
Positions OBA1- 8, OBA13- 16, OBB1- 8, OBC1- 8 049265601
2
Positions OBA9- 12 no inverters (Code 14= Y) 049265601
2
Positions OBA9- 12 units with inverters (Code 14= 1- 9, X) 049265603
SB1
Cooling Staging Board
4, 6 stages cooling and no unloaders 065499001 1
6 stages cooling and 2 unloaders per circuit 065499002 1
4- 8 stages cooling and 1 unloader per circuit 065499003 1
SB2
Heating Staging Board- 4 to 8 stages of Heat 065499001 15
Room Sensors
Sensor #1- Standard VAV 066540401 16
Sensor #2- Enhanced VAV (includes tenant override) 066540402 16
Sensor #9- Standard CAV 066540409 16
NS
Door Lock with key, Condenser Control Box 001157200 1
NS
Key only for Condenser Control Box Lock 021993200 1
Units built prior to 1995 used a Daughter Board (DB1) p/n 049545501 (the DB1 fuse is p/n 065829601 and the ribbon cable from MCB to DB1 is p/n 049265103).
2
Quantity varies depending on options.
3
Used on VAV units (Code 12= 2M, 4M) with 4 stages of cooling (Code 42= 4). CAV units (Code 12= 1M, 5M) units have all cooling control
directly from MCB to OBA. Ribbon cable connecting OBB to SB1 is p/n 065499501.
4
Used on VAV units (Code 12= 1M, 4M) with 6 or 8 stages of cooling (Code 42= 6, 8). CAV units (Code 12= 1M, 5M) units have all cooling
control directly from MCB to OBA. Ribbon cable connecting OBB to SB1 is p/n 065499501.
5
Used on CAV units (Code 12= 1M, 5M) with more than 4 stages of electrical heat. Ribbon cable connecting OBC to SB2 is p/n 065499501.
6
Prior to 1/92 use p/n 058899372 for VAV and p/n 065824701 for CAV.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 200
Section N- Main Control Box
Control Panel- Units with MicroTech II Controls
(Code 12= *D, *S)— 1/01 thru 3/05 2
Diagrams
Code 08= P, S. Between 10/04 and 3/05 either this Control Panel or the later design Control Panel (Code 08= D, F) could be installed.
Check the GO or visually inspect the unit to verify which panel is installed.
2
Terminal Block - T4
F3
T4
Rectifier
R
69
Keypad
InterfaceRemote
Keypad
R
68
R
67
T3
T2
T
B
6
R49
R48
R47
R46
T5
R
28
R27
EHB1
MCB
R26
DHL
NB1
Power
R R
R20 Supply
24 25
TB
(power supply)
S7
Deadfront Door
(shown open)
S1 HS1PS3
S6
F1
VIV Units only
(Code 15= 2)
1
1
REC1 GFR1 GFR2
T
B
5
Part Winding
Detail
TB
6
R
R27 R26
28
R
20
TD TD9
19
S4 S5
See Power
Panel
NB1
T
B
8
T
B
10
TB2 (51-70, 101-109)
SPS1
SPS2
N
B
2
TB2 (110-139)
1
GFR1 & GFR2 are detailed with the GFS1, GFS2 in the power panel section.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 201
Section N- Main Control Box
Control Panel- Units with MicroTech II Controls
(Code 12= *D, *S)— 1/01 thru 3/05 5
Components
Code 08= P, S. Between 10/04 and 3/05 either this Control Panel or the later design Control Panel (Code 08= D, F) could be installed.
Check the GO or visually inspect the unit to verify which panel is installed.
1
Sch. Part
Part
Qty.
Sym. Description Number
Switches
S1
Toggle Switch- Control: Units with Gas Heat (Code 04= A) 018446400
1
Toggle Switch- Control: Units without Gas Heat (Code 04= E, W, S, Y, X) 001355000
1
S4, S5 Toggle Switch- Inverters (Code 14= 1- 9, X) 028798400
2
Connector Bar- Inverter on Supply and Return Air Fan (C14= 1- 9, X) 033250200
2
S6
Rocker Switch- VIV Units (Code 15= 2) 072402801
1
S7
Rocker Switch- On/Off 072402801
1
HS1
Electric Heat Shutdown Switch (Code 04= E) 001355000
1
PS3
Toggle Switch- Unit Pumpdown Switch 001355000
1
Fusing
F1 Fuseholder 018690600 1
F1 Fuse- Control Circuit Fuse 025954700
1
F3
Fuse Block- Gas Heat Units 023780201
1
Fuse, Gas Heat Units: 500- 1000 MBH furnaces 025860505
1
Fuse, Gas Heat Units: 1100- 2000 MBH furnaces 025860507
1
Receptacle
REC1 Receptacle- GFI
Until 1/03 039003100
1
1/03 & Later 039003600
1
Receptacle- Std. 15A 025283700
1
Terminal Blocks
TB1
Terminal Block- Receptacle- 3 Terminals (not shown on diagram) 022431203
1
TB2
Terminal Block- 30 Terminals 022431230
2
TB5
Terminal Block, 24 Terminals- RPS, RDT Units 015998124
1
Terminal Block, 24 Terminals- RFS Units 022431224
1
TB6
Terminal Block- 24 Terminals
Until 6/01 015998120
1
6/01 & Later 015998124
1
TB8
Terminal Block, 14 Terminals- Field Installed Inverters only (Code 15= F) 022431214
1
TB10 Terminal Block- 12 Terminals- Electric or Gas Heat (Code 04= E, A) 015998112
1
Terminal Block- 12 Terminals- Hot Water, Steam, No Heat (C04= W, S,Y) 022431212
1
NB1, 2 Terminal Block- Neutral Block 037530800
2
Transformers
T2, T3 Transformer- Control Circuit 060004601
1
T4
Transformer- Power Exhaust 060614101
1
Terminal Block- T4 Transformer 065499806
1
Rectifier- T4 Transformer Terminal Block 111059401
1
T5
Transformer- Specials 060630801
1
Time Delays
TD9
Time Delay- Part Winding Supply Fan 026213000
1
TD19 Time Delay- Part Winding Return Fan 026213000
1
Relays
R20
Relay- Gas Steam, Hot Water Heat (Code 04= W, S, A) 026213000
1
R24
Relay- Gas Heat 032508101
1
R25
Relay, Gas Heat- Units With Inverters
(Code 14= 1-9, X) 032508101
1
R26
Relay- Iso Damper 073305401
1
R27
Relay- Powered Relief Damper 073305401
1
R28
Relay- Isolation Damper (Code 40= BE OR Code 19= BE) 026213000
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 202
Section N- Main Control Box
Control Panel- Units with MicroTech II Controls
(Code 12= *D, *S)— 1/01 thru 3/05 5
Components, Continued
Code 08= P, S. Between 10/04 and 3/05 either this Control Panel or the later design Control Panel (Code 08= D, F) could be installed.
Check the GO or visually inspect the unit to verify which panel is installed.
5
Sch. Part
Part
Qty.
Sym. Description Number
Relays, Continued
R46, 47 Relay- Supply Fan 072789226 11
R48, 49 Relay- Exhaust Fan Inverter 072789226 11
R67
Relay, Control- units with Inverters
(Code 14= 1- 9, X) 073305401
1
Relay, Control- units without Inverters (Code 14= Y) 026213000
1
R68
Relay- Return Fan w/ Inverter or Exhaust Fan 073305401
1
Relay- Return Fan without Inverter 026213000
1
R69
Relay- Inverters w/ bypass (Code 14= 1, 2, 3, 4, 5) 032508101
1
Main MicroTech Controller and Associated Boards
MCB Main Controller- Must be programmed (unit GO# required) 060006101
1
Com Card- Bacnet (Code 12= B*) 060006202
1
Com Card- Bacnet with Ethernet (Code 12= E*) 060006201
1
Com Card- LonMark with Space Control (Code 12= LS) 060006203
1
Com Card- LonMark with Discharge Control (Code 12= LD) 060006204
1
Standoff- Com Card 048166706
4
Kit- Connector Repair 300036605
1
Power Supply- 5 VDC 111049610
Serial Port Ribbon Cable 111047201
1
Battery049754501 1
EHB1 Electric Heat Board (Code 04= E) 112026101
1
Standoff EHB1 048166705
7
Communication Module 060006202
1
Standoff- Comm Module 048166707
4
Keypad Keypad Assy
(Code 19= R, Y) 060006301
1
Board- Remote Keypad Interface (Code 19= R) 112021601
1
Cable- Keypad 111044601
1
Transducers and Pressure Controls
SPS1 Static Pressure Transducer- Duct (Code 13= 1, 2, 3) 049545007 41
SPS2 Static Pressure Transducer- Duct (Code 13= 2) 049545007 41
Static Pressure Transducer- Building (Code 13= 3, 4) 049545006
1
DHL Duct Hi-Limit Pressure Control 065493801
1
Pressure Fitting- DHL 049763002
1
Power Supply
Power Supply- Design Flow Units 111049610
1
Terminal Block for Power Supply 065499809
1
Sensors
ZNT1 Sensor- Zone Temperature w/ Tenant Override 2111048101 1
Sensor- Zone Termp. w/ Tenant Override & Remote Setpoint Adjustment 2, 3111048102 1
DAT Sensor- Discharge Air Temperature 2060004705 1
ENT Sensor- Entering Air Temperature 2060004705 1
OAT Sensor- Outside Air Temperature 2060004705 1
RAT Sensor- Return Air Temperature 2060004705 1
Door Lock with key, Condenser Control Box 2001157200 1
Key only for Condenser Control Box Lock 2021993200 1
Relay Assembly. Consists of: Relay- p/n 060017101; Socket Only- p/n 060016901; Clip Only- p/n 060017001.
Not Shown on diagram.
3
SCC Units only- Code 12= BS, LS, ES, SS.
4
Prior to 8/02 the Duct Sensor was p/n 049545005. 049545007 is a direct replacemnt on MicroTech II units.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 203
Section N- Main Control Box
Control Panel- Units without MicroTech Controls
Code 12= YC, YM— Until 3/05
Diagram
Code 08= P, S. Between 10/04 and 3/05 either this Control Panel or the later design Control Panel (Code 08= D, F) could be installed.
Check the GO or visually inspect the unit to verify which panel is installed.
1
Deadfront Door
(shown open)
F3
T2
T
B
6
R69 R70
DHL
R67 R68
R63
R19 R18
R
24
R20 TD
19 TD9
N
B
1
S1 HS1PS3
F1
REC1 GFR11 GFR21
T
B
5
T
B
7
T
B
10
T
B
8
TB2
1
S4 S5
N
B
2
GFR1 & GFR2 are detailed with the GFS1, GFS2 in the power panel section.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 204
Section N- Main Control Box
Control Panel- Units without MicroTech Controls
Code 12= YC, YM— Until 3/05 1
Components
Code 08= P, S. Between 10/04 and 3/05 either this Control Panel or the later design Control Panel (Code 08= D, F) could be installed.
Check the GO or visually inspect the unit to verify which panel is installed.
1
Sch.Part Part Qty.
Sym. Description Number
Switches
S1
Toggle Switch- On/Off: Units with Gas Heat (Code 04= A) 018446400
1
Toggle Switch- On/Off: Units without Gas Heat (Code 04= E, W, S, Y, X) 001355000
1
S4/S5
Toggle Switch- Inverters (Code 14= 1- 9, X) 028798400
1
Connector Bar- Inverter on Supply and Return Air Fan C14= 1- 9, X) 033250200
1
PS3
Toggle Switch- Unit Pumpdown Switch 001355000
1
HS1
Electric Heat Shutdown Switch (Code 04= E) 001355000
1
Fusing
F1
Fuseholder018690600 1
Fuse- Control Circuit Fuse 025954700
1
F3
Fuse Block- Gas Heat 023780201
1
Fuse, Gas Heat: 200- 1000 MBH 025860505
1
Fuse, Gas Heat: 1100- 2000 MBH 025860507
1
Relays & Time Delays
R18, 19 Relay 016508002
2
R20
Relay- Gas Heat (Code 04= A) 019643000
1
R24
Relay- Gas Heat Alarm 032508101
1
R63
Relay- Hi Limit 073305401
1
R67
Relay- Inverters (Code14= 1- 9, X)
No Bypass (Code14= 6, 7, 9, X) 016508002
2
With Bypass (Code14= 1- 5, 8, X) 019643000
2
R68
Relay- Inverters (Code14= 1- 9, X)
No Bypass (Code14= 6, 7, 9, X) 016508002
2
With Bypass
(Code14= 1- 5, 8, X) 019643000
2
Relay- Exhaust Fan (Code 20= HY, JY 019643000
1
R69
Relay- Inverters with bypass only (Code14= 1- 5, 8, X) 032508101
1
R70
Relay- Inverters (Code14= 1- 9, X) 016508002
1
TD9, TD19 Time Delay- Part Winding Fan 026213000 1/fan
Terminal Blocks
TB1
Terminal Block- 3 Terminals used w/ REC1 (not shown on diagram)
TB2
Terminal Block- 30 Terminals 022431230
1
TB5
Terminal Block- 30 Terminals 022431230
1
TB6
Terminal Block- 20 Terminals 015998120
1
TB7
Terminal Block- 30 Terminals 022431230
1
TB8
Terminal Block- 24 Terminals 022431214
1
TB10
Terminal Block- 14 Terminals- Gas Heat Single Stage OR Modulating Burner 022431214
1
Terminal Block- 9 Terminals- Hi-Turn Down Burner 022431209
1
NB1, 2 Terminal Block- Neutral Block 037530800
2
Transformers
T2
Control Circuit Transformer 029948300
1
Receptacle
REC1 Receptacle
Until 1/03 039003100
1
1/03 & Later 039003600
1
Pressure Controls
DHL
Duct Hi-Limit Pressure Control 065493801
1
Duct Hi Limit Control Pneumatic Fitting 049763002
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 205
Section N- Main Control Box
MicroTech II OR No Controls Control Panel— 3/05 & Later 1
Units with Controller (Code 12= *D, *S)
Diagrams
Code 08= D, F. Between 10/04 & 3/05 either this control panel or the original MicroTech control panel could be installed. Check the GO
or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
R R R R R R R R R
1 2 20 24 25 26 28 30 45
R
46
R
48
R R
3 4
TD9
TD19
RES
CCB1
CCB2
R R R R R
61 66 67 68 69
T9
Left Side
DoorSee
Detail Below
SPS1
T2
EHB1
T3
T4
SPS2
TD3 TD5 TD7
TD4 TD6 TD8
MCB
TB1
Inverter
Display
SERIAL
DHL
Left Side Door- Detail
Remote Keypad
See Power
Panel
Keypad
Display
HS1 S1 CS2 CS1
Switches Detail
S4 S7 PS2 PS1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 206
Section N- Main Control Box
MicroTech II OR No Controls Control Panel— 3/05 & Later 1
080- 105 Units with No Controller (Code 12= YM, YC)
Diagram
Code 08= D, F. Between 10/04 & 3/05 either this control panel or the original MicroTech control panel could be installed. Check the GO
or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
R R R
1 2 20
R R
24 25
R R R R R R
28 30 45 18 19 63
R
5.1
TD9
R
6.1
R
7.1
R
8.1
R R
9 10
TD19
R
5.2
R
67
R
61
R
69
R
11
T2
R
66
T4
TB1
R
68
Switches Detail
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” R
12
TD
2
TD
12
R
7.2
R
8.2
R
R
13.2 14.2
R
R
13.1 14.1
TD5 TD7
TD6 TD8
HS1 S1 CS2 CS1
S4 S7 PS2 PS1
R
70
TD
1
TD
11
R
6.2
DHL
See Power
Panel
Rev. AG 01/15
RPL 7000070 / Page 207
Section N- Main Control Box
MicroTech II OR No Controls Control Panel— 3/05 & Later 1
115- 135 Units with No Controller (Code 12= YM, YC)
Diagram
Code 08= D, F. Between 10/04 & 3/05 either this control panel or the original MicroTech control panel could be installed. Check the GO
or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
R R R
1 2 20
R R
24 25
R R R R R R R R
28 30 45 18 19 63 3 4
TD9
TD19
R
61
R
67
R
69
R
11
R
R
5.1 6.1
TD TD
1 2
R
5.2
R
7.1
R
6.2
R
8.1
R R
9 10
R
R
7.2 8.2
T2
R
66
T4
TB1
R
68
R
70
R
TD TD
12
11 12
TD3 TD5 TD7
TD4 TD6 TD8
HS1 S1 CS2 CS1
DHL
S4 S7 PS2 PS1
Switches Detail
See Power
Panel
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 208
Section N- Main Control Box
MicroTech II OR No Controls Control Panel— 3/05 & Later 1
Components
Code 08= D, F. Between 10/04 & 3/05 either this control panel or the original MicroTech control panel could be installed. Check the GO
or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
Sch. Part
Sym. Description
Main Controller
MCB Main Controller- Must be programmed (unit GO# required)
Com Card- Bacnet (Code12= B*)
Com Card- Bacnet with Ethernet (Code12= E*)
Com Card- LonMark Space Control
(Code12= LS)
Com Card- LonMark Discharge Control (Code12= LD)
Standoff- Com Card
Kit- Connector Repair
Power Supply- 5 VDC
(Code 12= *D, *S)
Serial Port Ribbon Cable
Battery
Grounding Bar
Keypad
Keypad Keypad
Remote Keypad Interface Board
Cable- Interface
Compressor Controller
CCB1, 2 Expansion Board- Compressor Controller
Standoff- Expansion Board
Comm. Card- Bacnet
Standoff- Comm. Card
RES Resistor- CCB1
Electric Heat Board
EHB1 Expansion Board- Electric Heat
Standoff- Expansion Board
Comm. Card- Bacnet
Standoff- Comm. Card
Switches- Control
HS1 Switch- Electric Heat Shutdown
(Code 04= E)
PS1, 2 Switch- Pumpdown
CS1, 2 Switch- Control
with factory Controller (Code 12= *D, *S)
with no Controller (Code 12= YM, YC)
S1
Switch- System On/Off
Gas Heat Units (Code 04= A)
Elec., Steam, HW, No Heat (Code 04= E, S, W, Y)
S4
Switch- Inverter Bypass On/Off
S7
Switch- Local On/Auto/Off to Controller
Serial Cables
Serial Serial Cable
Duct Hi Limit and Duct Static Pressure Sensors
DHL Duct Hi Limit Switch
SPS1 Pressure Transducer- Duct Sensor
(Code 13= 1, 2, 3)
SPS2 Pressure Transducer- Duct Sensor
(Code 13= 2)
Pressure Transducer- Space Sensor
(Code 13= 3, 4)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
Part
Number Qty.
060006101
060006202
060006201
060006203
060006204
048166706
300036605
111049610
111047201
049754501
349936901
1
1
1
1
1
4
1
1
1
1
060006301 1
112021601 1
349938501 1
112026101
048166705
060006202
048166707
060003901
2
14
2
8
1
112026101
048166705
060006202
048166707
1
7
1
4
001355000
001355000
1
2
018446400
001355000
2
2
018446400
001355000
028798400
349931201
1
1
1
1
111047201
1
065493801
049545007
049545007
049545006
1
1
1
1
RPL 7000070 / Page 209
Section N- Main Control Box
MicroTech II OR No Controls Control Panel— 3/05 & Later 3
Components, Continued
Code 08= D, F. Between 10/04 & 3/05 either this control panel or the original MicroTech control panel could be installed. Check the GO
or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
3
Sch. Part Part
Sym. Description Number Qty.
Relays 3/05 thru 10/06 1
R1, 2 Relay- Hi Pressure Reset 349934704 2
R3, 4 Relay- Hi Pressure Delay 349934704 2
R5.1,5.2 Relay- Safety 349934704 2
R6.1,6.2 Relay- Safety 349934704 2
R7.1, 7.2 Relay- Safety 349934704 2
R8.1, 8.2 Relay- Safety 349934704 2
R9, 10 Relay- Compressor Lockout 349934704 2
R11, 12 Relay- Speedtrol Fan Cycling
(Code 47= 2) 349934704 2
R13.1,13.2 Relay- Safety 349934704 2
R14.1,14.2 Relay- Safety 349934704 2
R18, 19 Relay- Cooling Failure Indicator 349934701 2
R20
Relay- Steam, Hot Water Heat (Code 04= S, W)
Units with Controller (Code 12= *D, *S) 349934901 1
Units with No Controller (Code 12= YM) 349934704 1
Relay- Electric Heat (Code 04= E) 349934701 1
Relay- Gas Heat 2
(Code 04= A)
Units with Controller (Code 12= *D, *S)
Hi Turn Down Burner (Code 34 [5th digit]= H, T, U) 016508002 1
Modulating Burner (Code 34 [5th digit]= E, R, S) 026213000 1
Units w/No Controller & Gas Actuator (Code 12= YC
Hi Turn Down Burner
(Code 34 [5th digit]= H, T, U) 073340001 1
Modulating Burner (Code 34 [5th digit]= E, R, S) 027400700 1
Units w/No Controller & Float Control (Code 12= YM
Hi Turn Down Burner (Code 34 [5th digit]= H, T, U) 019643000 1
Modulating Burner (Code 34 [5th digit]= E, R, S) 027400700 1
R24
Relay- Gas Heat Alarm (Code 04= A 349934704 1
R25
Relay- Gas Heat, Start Supply Fan Inverter (Code 14= 1, 2,3,5,6,7) 349934704 1
R26
Relay- Iso Damper- Open/Close 349934901 1
R28
Relay- Isolation Damper Safety 349934701 1
R30
Relay- Cool Valve w/ Face Bypass 349934704 1
R45
Relay- UV Lights 349934701 1
R46
Relay- Inverter, Supply Fan increase/decrease (Code 14= 1- 3,5- 7) 112033501 1
R48
Relay- Inverter, Return Fan increase/decrease(Code 14= 2,4,5,7-9) 112033501 1
R61
Relay- Discharge Air Smoke Detector 349934701 1
R63
Relay- Specials 349934901 1
R66
Relay- Return Air Smoke Detector
(Code 16= 1, 3) 349934701 1
R67
Relay- Supply Fan Enable
No Controller
(Code 12= YM, YC) 349934704 1
With Controller
(Code 12= *D, *S) 349934701 1
R68
Relay- Return Fan Enable
No Controller
(Code 12= YM, YC) 349934704 1
With Controller
(Code 12= *D, *S) 349934701 1
R69
Relay- Inverter Bypass VAV Interlock
(Code 14= 1- 9) 349934704 1
R70
Relay- Specials 349934701 1
There was a change in many of the Main Box components at the end of 2006. The majority of the component changes
occurred in the Power Panel. The only components that changed in the Control Panel were several of the relays. See the
following page for relays used in units built 1/07 & Later. If the unit was built between 10/06 & 12/06 contact Daikin Applied to
verify which controls are installed.
2
All R20 options are detailed here but for units with gas heat, the R20 is located in the gas heat control box (see section G).
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 210
Section N- Main Control Box
MicroTech II OR No Controls Control Panel— 3/05 & Later 3
Components, Continued
Code 08= D, F. Between 10/04 & 3/05 either this control panel or the original MicroTech control panel could be installed. Check the GO
or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
3
Sch. Part Part
Sym. Description Number Qty.
Relays 1/07 & Later 1
R1, 2 Relay- Hi Pressure Reset 349934724 2
R3, 4 Relay- Hi Pressure Delay 349934724 2
R5.1,5.2 Relay- Safety 349934724 2
R6.1,6.2 Relay- Safety 349934724 2
R7.1, 7.2 Relay- Safety 349934724 2
R8.1, 8.2 Relay- Safety 349934724 2
R9, 10 Relay- Compressor Lockout 349934724 2
R11, 12 Relay- Speedtrol Fan Cycling
(Code 47= 2) 349934724 2
R13.1,13.2 Relay- Safety 349934724 2
R14.1,14.2 Relay- Safety 349934724 2
R18, 19 Relay- Cooling Failure Indicator 349934722 2
R20
Relay- Steam or Hot Water Heat (Code 04= S, W)
Units with Controller (Code 12= *D, *S) 349934921 1
Units with No Controller (Code 12= YM) 349934724 1
Relay- Electric Heat (Code 04= E) 349934722 1
Relay- Gas Heat 2
(Code 04= A)
Units with Controller (Code 12= *D, *S)
Hi Turn Down Burner (Code 34 [5th digit]= H, T, U) 016508002 1
Modulating Burner (Code 34 [5th digit]= E, R, S) 026213000 1
Units w/No Controller & Gas Actuator (Code 12= YC)
Hi Turn Down Burner
(Code 34 [5th digit]= H, T, U) 073340001 1
Modulating Burner (Code 34 [5th digit]= E, R, S) 027400700 1
Units w/No Controller & Float Control (Code 12= YM)
Hi Turn Down Burner (Code 34 [5th digit]= H, T, U) 019643000 1
Modulating Burner (Code 34 [5th digit]= E, R, S) 027400700 1
R24
Relay- Gas Heat Alarm (Code 04= A) 349934724 1
R25
Relay- Gas Heat, Start Supply Fan Inverter (Code 14= 1, 2,3,5,6,7 349934724 1
R26
Relay- Iso Damper- Open/Close 349934921 1
R28
Relay- Isolation Damper Safety 349934722 1
R30
Relay- Cool Valve w/ Face Bypass 349934724 1
R45
Relay- UV Lights 349934722 1
R46
Relay- Inverter, Supply Fan increase/decrease(Code 14= 1- 3,5- 7) 112033501 1
R48
Relay- Inverter, Return Fan increase/decrease (C14= 2,4,5,7- 9) 112033501 1
R61
Relay- Discharge Air Smoke Detector 349934722 1
R63
Relay- Specials 349934921 1
R66
Relay- Return Air Smoke Detector
(Code 16= 1, 3 349934722 1
R67
Relay- Supply Fan Enable
No Controller with Inverter bypass
(Code 12= YM), YC) 349934724 1
No Controller with no Inverter bypass
(Code 12= YM), YC) 349934722 1
With Controller
(Code 12= *D, *S) 349934722 1
R68
Relay- Return Fan Enable
No Controller
(Code 12= YM), YC) 349934724 1
With Controller
(Code 12= *D, *S) 349934722 1
R69
Relay- Inverter Bypass VAV Interlock
(Code 14= 1- 9) 349934722 1
R70
Relay- Specials 349934722 1
There was a change in many of the Main Box components at the end of 2006. The majority of the component changes
occurred in the Power Panel. The only components that changed in the Control Panel were several of the relays. See the
previous page for relays used in units built 3/05 thru 9/06. If the unit was built between 10/06 & 12/06 contact Daikin Applied
to verify which controls are installed.
2
All R20 options are detailed here but for units with gas heat, the R20 is located in the gas heat control box (see section G).
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 211
Section N- Main Control Box
MicroTech II OR No Controls Control Panel— 3/05 & Later 7
Components, Continued
Code 08= D, F. Between 10/04 & 3/05 either this control panel or the original MicroTech control panel could be installed. Check the GO
or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
7
Sch. Part
Part
Sym. Description Number Qty.
Time Delays
TD1 Time Delay- Compressor Lockout
300 Sec. 028210138 1
TD2 Time Delay- Compressor Lockout
300 Sec. 028210138 1
TD3 Time Delay- Hi Pressure
5 Sec. 111056701 1
TD4 Time Delay- Hi Pressure
5 Sec. 111056701 1
TD5 Time Delay- Part Winding 3
1 Sec. 028210101 1
TD6 Time Delay- Part Winding 3
1 Sec. 028210101 1
TD7 Time Delay- Part Winding 3
1 Sec. 028210101 1
TD8 Time Delay- Part Winding 3
1 Sec. 028210101 1
TD9 Time Delay- SA Fan PW (Special) 3
1 Sec. 028210101 1
TD11 Time Delay- Low Ambient
165 Sec. 032358500 1
TD12 Time Delay- Low Ambient
165 Sec. 032358500 1
TD19 Time Delay- RA Fan PW (Special) 3
1 Sec. 028210101 1
Transformers- Controls
T2
Transformer- Control Input
115- 24V
With Controller
Code 12= *D, *S 349937303 1
No Controller
Code 12= YM, YC 349937201 1
T3
Transformer- Control Output
115- 24V 349937303 1
T4
Transformer- Exhaust Damper Actuator
115- 12VDC 349931801 1
T9
Transformer- Refrigerant Circuit
24V 349937201 1
Terminal Blocks
TB1
Terminal Block- Internal
Units built 3/05 thru 10/06 6349930605 4
Units built 1/07 & Later 6349930641 5
Sensors
ZNT1 Sensor- Zone Temperature w/ Tenant Override 21110481011
Sensor- Zone Temp. w/ Tenant Override & Remote Setpoint Adj. 1, 2111048102 1
DAT Sensor- Discharge Air Temperature 20600047051
ENT Sensor- Entering Air Temperature 20600047051
OAT Sensor- Outside Air Temperature 20600047051
RAT Sensor- Return Air Temperature 20600047051
SCC Units only- Code 12= BS, LS, ES, SS.
Not Shown on diagram.
3
Part Winding units (Code 10= PW) applies to units with Semihermetic Compressors only.
4
Varies depending on unit options. Part number is for one individual section. Ground Block is p/n 349930606.
5
Varies depending on unit options. Part number is for one individual section. Ground Block is p/n 349930647. Jumpers are p/n
349930945 (TB1A:5), 349930943 (TB1B:14), 349930942 (TB1C:20,TB1D:25 & TB1E:30).
6
If unit was built between 10/06 & 12/06 contact Daikin Applied.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 212
Section N- Main Control Box
Control Panel 9/08 & Later 1
MicroTech III Units with Controller (Code 12= *E, *F)
Diagram
1
This is for MicroTech III units only. Components for units with No controls (Code 12= YC, YM) are listed on the previous four pages.
See Power Panel
T3
T2
TB1
R
81
R12 R13 R14 R20
COM
MCB
EXP A
R25 R26 R28
EXP B
R
82
R
83
R
84
R
85
R R
86 87
R
88
R63
EXP D
TD
20
SPS1 SPS2 SPS3
HS1 S1
DHL
S4 S7
See Power Panel
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 213
Section N- Main Control Box
Control Panel 9/08 & Later*
MicroTech III Units with Controller (Code 12= *E, *F)
Components
Sch. Part Part
Sym. Description Number Qty.
Main Controller
MCB Main Controller- Must be programmed (unit GO# required) 193407301 1
Terminal Block, MCB- 2 Pole 193410302 1
Terminal Block, MCB- 3 Pole 193410303 6
Terminal Block, MCB- 5 Pole 193410305 1
Terminal Block, MCB- 6 Pole 193410306 1
Terminal Block, MCB- 7 Pole 193410307 1
Terminal Block, MCB- 8 Pole 193410308 2
Expansion Module
EXP A Expansion Module- Condenser 193407501 1
EXP B Expansion Module- Heat 193407501 1
EXP D Expansion Module- Specials 193407501 1
Terminal Block, EXP- 2 Pole 193410302 1/board
Terminal Block, EXP- 3 Pole 193410303 1/board
Terminal Block, EXP- 7 Pole 193410307 1/board
Terminal Block, EXP- 8 Pole 193410308 2/board
Communication Card
COM Bacnet- MSTP
(Code 12= BE, BF) 090016710 1
Bacnet- IP
(Code 12= EE, EF) 090016709 1
LonWorks- Discharge
(Code 12= LE) 090016712 1
LonWorks- Constant Volume
(Code 12= LF) 090016711 1
Resistors 1
RES1 Resistor- Refrigeration Circuit #1
1500 OHM 044690151 1
RES2 Resistor- Refrigeration Circuit #2
1000 OHM 044690110 1
RES3 Resistor- Freezestat (FS1)
1000 OHM 044690110 1
RES4 Resistor- OAE
1500 OHM 044690151 1
RES6,7,8 Resistor- SPS1, SPS2, SPS3
500 OHM 044690146 1/switch
Switches- Control
HS1
Switch- Electric Heat Shutdown (Code 04= E) 001355000 1
S1
Switch- System On/Off
Gas Heat Units with no UV Lights
DPST/15A 018446400 1
Gas Heat Units with UV Lights
4PST/30A 033536700 1
Electric, Steam, HW or No Heat with no UV Lights SPST/20A 001355000 1
Electric, Steam, HW or No Heat with UV Lights
DPST/15A 018446400 1
S4
Switch- Inverter Bypass On/Off
DPST/15A 018446400 1
S7
Switch- Local On/Auto/Off to Controller
SPDT/15A 193412101 1
Transformers
T2
Transformer- Control
120- 24V 349937303 1
T3
Transformer- Control
120- 24V 349937303 1
Duct Hi Limit and Duct Static Pressure Sensors
DHL
Duct Hi Limit Switch 065493801 1
SPS1 Pressure Transducer- Duct Sensor
(Code 13= 1, 2, 3) 910124528 21
SPS2 Pressure Transducer- Duct Sensor
(Code 13= 2) 910124528 21
Pressure Transducer- Space Sensor
(Code 13= 3, 4) 910124529 21
SPS3 Pressure Transducer- Space Sensor
(Code 13= 8) 910124529 21
1
2
Not Shown on diagram.
The original Transducer is no longer available. This replacement kit requires minor field modifications for proper installation
& operation.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 214
Section N- Main Control Box
Control Panel 9/08 & Later
MicroTech III Units with Controller (Code 12= *E, *F)
Components, Continued
Sch. Part Part
Sym. Description Number Qty.
Relays
R12
Relay- Condenser Fan 349934724
1
R13
Relay- Condenser Fan 349934724
1
R14
Relay- Condenser Fan 349934724
1
R20
Relay- Heat 349934724
1
R25
Relay- Gas Heat, Start Supply Fan Inverter (Code 14= 1, 2,3,5,6,7) 349934724
1
R26
Relay- Iso Damper- Open/Close 349934722
1
R28
Relay- Isolation Damper Safety 349934722
1
R63
Relay- Duct Hi Limit
Units with Return Fan Inverter
3PDT/120V 349934923
1
Units with No Return Fan Inverter
DPDT/120V 349934724
1
R81
Relay- Smoke
4P/6A/24V 193413601
1
R82
Relay- Smoke
4P/6A/24V 193413601
1
R83
Relay- Smoke
4P/6A/24V 193413601
1
R84
Relay- Smoke
4P/6A/24V 193413601
1
R85
Relay- Smoke
4P/6A/24V 193413601
1
R86
Relay- Smoke
4P/6A/24V 193413601
1
R87
Relay- Smoke
4P/6A/24V 193413601
1
R88
Relay- Smoke
4P/6A/24V 193413601
1
Time Delays
TD20 Time Delay- Return Air Fan 028210106
1
TB1
ZNT1
DAT
EFT
OAT
RAT
EAT
LAT
Terminal Block
Terminal Block 349930641
Phase Voltage
Sensor- Zone Temperature w/ Tenant Override 3113117701
Sensor- Zone Temp. w/ Tenant Override & Remote Setpoint Adj.2, 3 113117801
Sensor- Discharge Air Temperature 3193414602
Sensor- Entering Air Temperature 3193414602
Sensor- Outside Air Temperature 3193414602
Sensor- Return Air Temperature 3193414602
Sensor- Exhaust Air Temperature 3193414602
Sensor- Leaving Air Temperature 3193414602
1
1
1
1
1
1
1
1
1
Remote Display
Remote Interface Display 3193408001 1
Varies depending on unit options. Part number is for one individual section. Ground Block is p/n 349930647.
SCC Units only- Code 12= BF, LF, EF, SF.
3
Not Shown on diagram.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 215
Section N- Main Control Box
Power Panel- Until 3/05 3
Diagram
Code 08= P, S. Between 10/04 and 3/05 either this Power Panel OR the redesigned MicroTech II Power Panel (Code 08= D, F) could
be installed. Check the GO or visually inspect the unit to verify which panel is installed.
3
See Control Panel
LR20 2
LR10 2
T1
FB
19 1
M19 1
FB
91
FB
20
M20
OL
19 1
FB
10
M9 1
OL
20
OL
91
F
B
8
GFS1
GFS2
PVM1
PVM2
M10
OL
10
PB1
or
DS1
PB2
or
DS2
Used with all Part Winding Motors (Code 10= PP, PS), all 60HP and 75HP motors, and 208/230V 40HP and 50HP Across-the-Line Motors
(Code 10= AL, PW).
2
Line Reactor part numbers are listed in Section F.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 216
Section N- Main Control Box
Power Panel- Until 3/05 2
Common Components
Code 08= P, S. Between 10/04 and 3/05 either this Power Panel OR the redesigned MicroTech II Power Panel (Code 08= D, F) could
be installed. Check the GO or visually inspect the unit to verify which panel is installed.
2
Power Panel- TB1 Terminal Block, T1 Transformer and Fusing, Ground Fault, PVM
Voltage
Sch.Part Part
SYM). Description Number 208V230V380V460V575V
Transformer- Main
T1
Transformer- Power
Electric, H)W. Steam, H)eat (C04= E), S, H) 038253916
1
1
Electric, H)W. Steam, H)eat (C04= E), S, H) 038253907
1
1
Electric, H)W. Steam, H)eat (C04= E), S, H) 038253930
1
Gas Heat (Code 04= A) 038253917
1
1
Gas Heat (Code 04= A) 038253908
1
1
Gas Heat (Code 04= A) 038253930
1
No Heat (Code 04= Y)
MicroTech Control (C12= 1- 5M, *D, *S) 038253916
1
1
MicroTech Control (C12= 1- 5M, *D, *S) 038253907
1
1
MicroTech Control (C12= 1- 5M, *D, *S) 038253930
1
No Controls
(Code 12= YM) 038253913
1
1
No Controls
(Code 12= YM) 038253904
1
1
No Controls
(Code 12= YM) 038253932
1
Fuse Block, Fuses for Main Transformer
FB8
Fuse Block- T1 Transformer 023780202
1
1
Fuse Block- T1 Transformer 023780203
1
1
1
F8
Fuse- T1 Transformer
Electric, H)W, Steam Heat (Code 04=E) 025860534
2
Electric, H)W, Steam Heat (Code 04=E) 025860504
2
Electric, H)W, Steam Heat (Code 04=E) 025860404
2
Electric, H)W, Steam Heat (Code 04=E) 025860433
2
2
Gas Heat (Code 04= A) 025860534
2
2
Gas Heat (Code 04= A) 025860431
2
Gas Heat (Code 04= A) 025860437
2
Gas Heat (Code 04= A) 025860433
2
No Heat (Code 04= Y)
MicroTech Control (C12= 1- 5M, *D, *S) 025860534
2
MicroTech Control (C12= 1- 5M, *D, *S) 025860504
2
MicroTech Control (C12= 1- 5M, *D, *S) 025860404
2
MicroTech Control (C12= 1- 5M, *D, *S) 025860433
2
2
No Controls (Code 12= YM) 025860530
2
No Controls (Code 12= YM) 025860532
2
No Controls (Code 12= YM) 025860435
2
No Controls (Code 12= YM) 025860434
2
No Controls (Code 12= YM) 025860402
2
Ground Fault Relay and Sensor
GFR1,2 1 Relay- Ground Fault 065813401 1/fan1/fan1/fan1/fan1/fan
GFS1, 2 Sensor- Ground Fault 065813402 1/fan1/fan1/fan1/fan1/fan
Phase Voltage Monitor
PVM1,2 Phase Voltage Monitor 098860401 1/fan1/fan1/fan1/fan
Phase Voltage Monitor
059475303
1/fan
1
GFR1, 2 shown on Control Panel diagram.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 217
Section N- Main Control Box
Power Panel- Until 3/05 4
Common Components, Continued
Code 08= P, S. Between 10/04 and 3/05 either this Power Panel OR the redesigned MicroTech II Power Panel (Code 08= D, F) could
be installed. Check the GO or visually inspect the unit to verify which panel is installed.
4
Power Panel- Power Blocks, Disconnects
Sch.
Sym.
PB1, 2 2
Part
PartVoltage
Description Number 208V230V380V460V575V
Power Block
(Code 11= P1, Q1)
11111
Power Block- 6 outlet holes/1inlet hole
95A 030372707
11111
Power Block- 6 outlet holes/1inlet hole
175A 030372705
11111
Power Block- 6 outlet holes/1inlet hole
335A 030372717
11111
Power Block- 6 outlet holes/1inlet
350/380A 030372718
11111
Power Block- 8 outlet holes/1inlet hole
335A 030372706
11111
Power Block- 12 outlet holes/1inlet 350/380A 030372720
11111
Power Block- 6 outlet holes/2inlet holes 760A 030372721
11111
Power Block- 12 outlet holes/1inlet hole 760A 030372728
Disconnect Switch (Code 11= A2, B2, C2, D2)
DS1, DS2 Disconnect Switch
60A/600V
Handle Mechanism- 60A Switch
Disconnect Switch
100A/600V
Handle Mechanism- 100A Switch
Disconnect Switch
250A/600V
Handle Mechanism- 250A Switch
Disconnect Switch
400A/600V- 2 inlet holes
Handle Mechanism- 400A Switch
Disconnect Switch
400A/240V- 2 inlet holes
Handle Mechanism- 400A Switch
Disconnect Switch
400A/600V- 1 inlet hole
Handle Mechanism- 400A Switch
Disconnect Switch
400A/240V- 1 inlet hole
Handle Mechanism- 400A Switch
Disconnect Switch
600A/600V
Handle Mechanism- 600A Switch
Disconnect Switch
800A/600V- 2 inlet holes
Handle Mechanism- 800A Switch
Disconnect Switch
800A/600V- 1 inlet hole
Handle Mechanism- 800A Switch
Disconnect Switch
1200A/600V
Handle Mechanism- 1200A Switch
33333
031446200
031322400
33333
025860602
025862400
33333
047442104
039903100
33333
047442111
025862500
33333
025860702
025862500
33333
047442109
025862500
33333
047442108
025862500
33333
027070601
028399200
33
031019401
031011600
333
031019411
031011611
33333
031019501
031011700
The Power Block used on a given unit is contingent upon the unit voltage, the motor(s) horsepower, and other options. Check the
part in the unit to size up the replacement, or contact Daikin Applied with the unit model/GO number to assure proper replacement.
2
PB2 is only used when Code 11= Q1.
3
The Disconnect Switch used on a given unit is contingent upon the unit voltage, the Motor(s) horsepower, and other options. Check the part in the unit to size up the replacement, or contact Daikin Applied with the unit model/GO number to assure proper replacement. DS2 is only used when Code 11= A2, C2, D2
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 218
Section N- Main Control Box
Power Panel— Until 3/05 3
Fan Motor Contactors, Overloads, Fusing Components & Line Reactors
Code 08= P, S. Between 10/04 and 3/05 either this Power Panel OR the redesigned MicroTech II Power Panel (Code 08= D, F) could
be installed. Check the GO or visually inspect the unit to verify which panel is installed.
3
5 Horsepower Motor- Code 22 OR 32= J*Y
Sch. Part
PartVoltage
Sym. Description
Number 208V230V380V460V575V
Contactors
M10, 20 Contactor- Supply (M10), Return (M20) Fan Motor
027514401 1 1
1
1
1
Fuse Block and Fuses- FB10, 20 Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780204 1 1
Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780205
1
1
1
Fuse- FB10 OR FB20
025860508 3 3
Fuse- FB10 OR FB20
025860538
3
3
Fuse- FB10 OR FB20
025860430
3
FB20 Fuse Block- Prop Exhaust (FB20)
2 Fan (Code 24= 2)
023780209 1
2 Fan (Code 24= 2)
023780204
1
2 Fan (Code 24= 2)
023780205
1
1
1
3 Fan (Code 24= 3)
023780209 1
3 Fan (Code 24= 3)
023780205
1
1
1
1
Fuse- 2 Fan (Code 24= 2)Prop Exhaust FB20
025860510 3
Fuse- 2 Fan (Code 24= 2)Prop Exhaust FB20
025860509
3
Fuse- 2 Fan (Code 24= 2)Prop Exhaust FB20
025860405
3
3
Fuse- 2 Fan (Code 24= 2)Prop Exhaust FB20
025860438
3
Fuse- 2 Fan (Code 24= 3)Prop Exhaust FB20
025860513 3
Fuse- 2 Fan (Code 24= 3)Prop Exhaust FB20
025860512
3
Fuse- 2 Fan (Code 24= 3)Prop Exhaust FB20
025860408
3
3
Fuse- 2 Fan (Code 24= 3)Prop Exhaust FB20
025860406
3
Overloads and Heaters
OL10, 20 Overload- Supply (OL10), Return (OL20) Fan Motor
1
Overload
1
Heater, Overload
2
LR10, 20 Line Reactors NOTE: Quantities Listed are PER motor.
1
Note that there have been two different series of Overloads and Overload Heaters used during the production run.
When replacing an Overload OR the matching Overload Heater it is VITAL to obtain vendor p/n and amperage rating from BOTH parts.
When replacing ONLY an Overload Heater, it is VERY IMPORTANT to first obtain vendor information and amperage rating from the
existing Overload, Overload Heater, and Motor. It is important to obtain this information to ensure that the correct Overload Heater is
selected since Overload Heaters are chosen based upon Motor amperage draw, AND Overload Heaters are NOT interchangeable
between series. Also, Overload Heaters DO NOT automatically come with Overloads. OVERLOAD HEATERS MUST BE ORDERED
SEPARATELY.
Once vendor and amperage information is obtained, contact Daikin Applied for p/ns.
2
When the unit has an Inverter with Bypass (Code 14= 2, 4, 5, 8) the Line Reactors are located in the Bypass Box. When there is no
Inverter Bypass Box the Line Reactors are located in the Main Control Power Panel. Line Reactor part numbers are listed in the
Supply Air section (Section F).
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 219
Section N- Main Control Box
Power Panel— Until 3/05 3
Fan Motor Contactors, Overloads, Fusing Components & Line Reactors,
Continued
Code 08= P, S. Between 10/04 and 3/05 either this Power Panel OR the redesigned MicroTech II Power Panel (Code 08= D, F) could
be installed. Check the GO or visually inspect the unit to verify which panel is installed.
3
7.5 Horsepower Motor- Code 22 OR 32= K*Y
Sch. Part
PartVoltage
Sym. Description
Number 208V230V380V460V575V
Contactors
M10, 20 Contactor- Supply (M10), Return (M20) Fan Motor
027514402 1
Contactor- Supply (M10), Return (M20) Fan Motor
027514401
1 1
1 1
Fuse Block and Fuses
FB10, 20 Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780209 1
1
Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780205
1
1 1
Fuse- FB10 OR FB20
025860510 3
3
Fuse- FB10 OR FB20
025860406
3
3
Fuse- FB10 OR FB20
025860405
3
Overloads and Heaters
OL10, 20 Overload- Supply (OL10), Return (OL20) Fan Motor
1
Overload
1
Heater, Overload
2
LR10, 20 Line Reactors 10 Horsepower Motor- Code 22 OR 32= L*Y
Sch.
Part
Part Voltage
Sym. Description
Number 208V 230V380V 460V575V
Contactors
M10, 20 Contactor- Supply (M10), Return (M20) Fan Motor
027514403 1
Contactor- Supply (M10), Return (M20) Fan Motor
027514402
1
Contactor- Supply (M10), Return (M20) Fan Motor
027514401
1
1 1
Fuse Block and Fuses
FB10, 20 Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780209 1
1
Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780205
1
1 1
Fuse- FB10 OR FB20
025860513 3
Fuse- FB10 OR FB20
025860511
3
Fuse- FB10 OR FB20
025860407
3
3
Fuse- FB10 OR FB20
025860406
3
Overloads and Heaters
OL10, 20 Overload- Supply (OL10), Return (OL20) Fan Motor
1
Overload
1
Heater, Overload
2
LR10, 20 Line Reactors NOTE: Quantities Listed are PER motor.
1
Note that there have been two different series of Overloads and Overload Heaters used during the production run.
When replacing an Overload OR the matching Overload Heater it is VITAL to obtain vendor p/n and amperage rating from BOTH parts.
When replacing ONLY an Overload Heater, it is VERY IMPORTANT to first obtain vendor information and amperage rating from the
existing Overload, Overload Heater, and Motor. It is important to obtain this information to ensure that the correct Overload Heater is
selected since Overload Heaters are chosen based upon Motor amperage draw, AND Overload Heaters are NOT interchangeable
between series. Also, Overload Heaters DO NOT automatically come with Overloads. OVERLOAD HEATERS MUST BE ORDERED
SEPARATELY.
Once vendor and amperage information is obtained, contact Daikin Applied for p/ns.
2
When the unit has an Inverter with Bypass (Code 14= 2, 4, 5, 8) the Line Reactors are located in the Bypass Box. When there is no
Inverter Bypass Box the Line Reactors are located in the Main Control Power Panel. Line Reactor part numbers are listed in the
Supply Air section (Section F).
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 220
Section N- Main Control Box
Power Panel— Until 3/05 4
Fan Motor Contactors, Overloads, Fusing Components & Line Reactors,
Continued
Code 08= P, S. Between 10/04 and 3/05 either this Power Panel OR the redesigned MicroTech II Power Panel (Code 08= D, F) could
be installed. Check the GO or visually inspect the unit to verify which panel is installed.
4
15 Horsepower Motor- Code 22 OR 32= M*Y AND Code 10= AL, PW 3
Sch.
Part
Part Voltage
Sym. Description
Number 208V230V380V460V575V
Contactors
M10, 20 Contactor- Supply (M10), Return (M20) Fan Motor
027514404 1
1
Contactor- Supply (M10), Return (M20) Fan Motor
027514402
1
1 1
Fuse Block and Fuses
FB10, 20 Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780213 1
Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780209
1
Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780205
1
1 1
Fuse- FB10 OR FB20
025860515 3
Fuse- FB10 OR FB20
025860514
3
Fuse- FB10 OR FB20
025860409
3
3 3
Overloads and Heaters
OL10, 20 Overload- Supply (OL10), Return (OL20) Fan Motor
1
Overload
1
Heater, Overload
2
LR10, 20 Line Reactors 20 Horsepower Motor- Code 22 OR 32= N*Y AND Code 10= AL, PW 3
Sch.
Part
Part Voltage
Sym. Description
Number 208V 230V380V 460V575V
Contactors
M10, 20 Contactor- Supply (M10), Return (M20) Fan Motor
027514406 1
Contactor- Supply (M10), Return (M20) Fan Motor
027514405
1
Contactor- Supply (M10), Return (M20) Fan Motor
027514403
1
1 1
Fuse Block and Fuses
FB10, 20 Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780213 1
1
Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780210
1
1 1
Fuse- FB10 OR FB20
025860517 3
Fuse- FB10 OR FB20
025860516
3
Fuse- FB10 OR FB20
025860411
3
3
Fuse- FB10 OR FB20
025860410
3
Overloads and Heaters
OL10, 20 Overload- Supply (OL10), Return (OL20) Fan Motor
1
Overload
1
Heater, Overload
2
LR10, 20 Line Reactors NOTE: Quantities Listed are PER motor.
1
Note that there have been two different series of Overloads and Overload Heaters used during the production run.
When replacing an Overload OR the matching Overload Heater it is VITAL to obtain vendor p/n and amperage rating from BOTH parts.
When replacing ONLY an Overload Heater, it is VERY IMPORTANT to first obtain vendor information and amperage rating from the existing
Overload, Overload Heater, and Motor. It is important to obtain this information to ensure that the correct Overload Heater is selected since
Overload Heaters are chosen based upon Motor amperage draw, AND Overload Heaters are NOT interchangeable between series. Also,
Overload Heaters DO NOT automatically come with Overloads. OVERLOAD HEATERS MUST BE ORDERED SEPARATELY.
Once vendor and amperage information is obtained, contact Daikin Applied for p/ns.
2
When the unit has an Inverter with Bypass (Code 14= 2, 4, 5, 8) the Line Reactors are located in the Bypass Box. When there is no Inverter
Bypass Box the Line Reactors are located in the Main Control Power Panel. Line Reactor part numbers are listed in the Supply Air section
(Section F).
3
If Code 10= PP, PS contact Daikin Applied with p/n information so that the correct part(s) can be identified. (Rare option.)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 221
Section N- Main Control Box
Power Panel— Until 3/05 4
Fan Motor Contactors, Overloads, Fusing Components & Line Reactors,
Continued
Code 08= P, S. Between 10/04 and 3/05 either this Power Panel OR the redesigned MicroTech II Power Panel (Code 08= D, F) could
be installed. Check the GO or visually inspect the unit to verify which panel is installed.
4
25 Horsepower Motor- Code 22 OR 32= P*Y AND Code 10= AL, PW 3
Sch.
Part
Part Voltage
Sym. Description
Number 208V 230V 380V460V575V
Contactors
M10, 20 Contactor- Supply (M10), Return (M20) Fan Motor
027514407 1
Contactor- Supply (M10), Return (M20) Fan Motor
027514406
1
Contactor- Supply (M10), Return (M20) Fan Motor
027514404
1 1 1
Fuse Block and Fuses
FB10, 20 Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780218 1
Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780213
1
Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780210
1
1 1
Fuse- FB10 OR FB20
025860519 3
Fuse- FB10 OR FB20
025860518
3
Fuse- FB10 OR FB20
025860413
3 3
Fuse- FB10 OR FB20
025860411
3
Overloads and Heaters
OL10, 20 Overload- Supply (OL10), Return (OL20) Fan Motor
1
Overload
1
Heater, Overload
2
LR10, 20 Line Reactors NOTE: Quantities Listed are PER motor.
1
Note that there have been two different series of Overloads and Overload Heaters used during the production run.
When replacing an Overload OR the matching Overload Heater it is VITAL to obtain vendor p/n and amperage rating from BOTH parts.
When replacing ONLY an Overload Heater, it is VERY IMPORTANT to first obtain vendor information and amperage rating from the existing
Overload, Overload Heater, and Motor. It is important to obtain this information to ensure that the correct Overload Heater is selected since
Overload Heaters are chosen based upon Motor amperage draw, AND Overload Heaters are NOT interchangeable between series. Also,
Overload Heaters DO NOT automatically come with Overloads. OVERLOAD HEATERS MUST BE ORDERED SEPARATELY.
Once vendor and amperage information is obtained, contact Daikin Applied for p/ns.
2
When the unit has an Inverter with Bypass (Code 14= 2, 4, 5, 8) the Line Reactors are located in the Bypass Box. When there is no Inverter
Bypass Box the Line Reactors are located in the Main Control Power Panel. Line Reactor part numbers are listed in the Supply Air section
(Section F).
3
If Code 10= PP, PS contact Daikin Applied with p/n information so that the correct part(s) can be identified. (Rare option.)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 222
Section N- Main Control Box
Power Panel— Until 3/05 5
Fan Motor Contactors, Overloads, Fusing Components & Line Reactors,
Continued
Code 08= P, S. Between 10/04 and 3/05 either this Power Panel OR the redesigned MicroTech II Power Panel (Code 08= D, F) could
be installed. Check the GO or visually inspect the unit to verify which panel is installed.
5
30 Horsepower Motor- Code 22 OR 32= Q*Y AND Code 10= AL, PW 4
Sch.
Part
Part Voltage
Sym. Description
Number 208V 230V 380V460V575V
Contactors
M10, 20 Contactor- Supply (M10), Return (M20) Fan Motor
027514405 1
Contactor- Supply (M10), Return (M20) Fan Motor
0275144071
Contactor- Supply (M10), Return (M20) Fan Motor
027514404
1
1 1
Fuse Block and Fuses
FB10, 20 Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780213 3 1
Fuse Block- Supply (FB10), Return (FB20) Fan Motor
0237802181
Fuse Block- Supply (FB10), Return (FB20) Fan Motor
023780210
1
1 1
Fuse- FB10 OR FB20
025860515 33
Fuse- FB10 OR FB20
0258605203
Fuse- FB10 OR FB20
025860414
3
3
Fuse- FB10 OR FB20
025860413
3
Overloads and Heaters
OL10, 20 Overload- Supply (OL10), Return (OL20) Fan Motor
1
Overload
1
Heater, Overload
2
LR10, 20 Line Reactors NOTE: Quantities Listed are PER motor.
1
Note that there have been two different series of Overloads and Overload Heaters used during the production run.
When replacing an Overload OR the matching Overload Heater it is VITAL to obtain vendor p/n and amperage rating from BOTH parts.
When replacing ONLY an Overload Heater, it is VERY IMPORTANT to first obtain vendor information and amperage rating from the existing
Overload, Overload Heater, and Motor. It is important to obtain this information to ensure that the correct Overload Heater is selected since
Overload Heaters are chosen based upon Motor amperage draw, AND Overload Heaters are NOT interchangeable between series. Also,
Overload Heaters DO NOT automatically come with Overloads. OVERLOAD HEATERS MUST BE ORDERED SEPARATELY.
Once vendor and amperage information is obtained, contact Daikin Applied for p/ns.
2
When the unit has an Inverter with Bypass (Code 14= 2, 4, 5, 8) the Line Reactors are located in the Bypass Box. When there is no Inverter
Bypass Box the Line Reactors are located in the Main Control Power Panel. Line Reactor part numbers are listed in the Supply Air section
(Section F).
3
This part number is used for a Motor with no Inverter. If the 208V unit has an Inverter use Fuse Block p/n 023780218 and Fuse p/n 025860520.
4
If Code 10= PP, PS contact Daikin Applied with p/n information so that the correct part(s) can be identified. (Rare option.)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 223
Section N- Main Control Box
Power Panel— Until 3/05 6
Fan Motor Contactors, Overloads, Fusing Components & Line Reactors,
Continued
Code 08= P, S. Between 10/04 and 3/05 either this Power Panel OR the redesigned MicroTech II Power Panel (Code 08= D, F) could
be installed. Check the GO or visually inspect the unit to verify which panel is installed.
6
40 Horsepower Motor- Code 22 OR 32= R*Y AND Code 10= AL, PW 5
Sch. Part
PartVoltage
Sym. Description
Number 208V 230V 380V460V 575V
Contactors
M9,10 4
M19, 20 Contactor- Supply (M9, 10), Return (M19, 20) Fan Motor 027514406 2
2
1 1
1
Fuse Block and Fuses
FB9,10 4
FB19, 20 Fuse Block- Supply (FB9, 10), Return (FB19, 20) Fan Motor 023780213 2 32
Fuse Block- Supply (FB9, 10), Return (FB19, 20) Fan Motor 023780212
1 1
1
Fuse- FB9,10, 19, 20
025860516 6 36 33
Fuse- FB9,10, 19, 20
025860415
3
Overloads and Heaters
OL9,10 4
OL19, 20 Overload- Supply (OL9,10), Return (OL19, 20) Fan Motor
1
Overload
1
Heater, Overload
LR10, 20 Line Reactors 2
NOTE: Quantities Listed are PER motor.
1
Note that there have been two different series of Overloads and Overload Heaters used during the production run.
When replacing an Overload OR the matching Overload Heater it is VITAL to obtain vendor p/n and amperage rating from BOTH parts.
When replacing ONLY an Overload Heater, it is VERY IMPORTANT to first obtain vendor information and amperage rating from the existing
Overload, Overload Heater, and Motor. It is important to obtain this information to ensure that the correct Overload Heater is selected since
Overload Heaters are chosen based upon Motor amperage draw, AND Overload Heaters are NOT interchangeable between series. Also,
Overload Heaters DO NOT automatically come with Overloads. OVERLOAD HEATERS MUST BE ORDERED SEPARATELY.
Once vendor and amperage information is obtained, contact Daikin Applied for p/ns.
2
When the unit has an Inverter with Bypass (Code 14= 2, 4, 5, 8) the Line Reactors are located in the Bypass Box. When there is no Inverter
Bypass Box the Line Reactors are located in the Main Control Power Panel. Line Reactor part numbers are listed in the Supply Air section
(Section F).
3
This part number is used for a motor with no Inverter. If the 208V unit has an Inverter use Fuse Block p/n 023780218 and Fuse p/n 025860521.
4
M9, M19, FB9, FB19, AND OL9, OL19 are only used on 208/230V motors.
5
If Code 10= PP, PS contact Daikin Applied with p/n information so that the correct part(s) can be identified. (Rare option.)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 224
Section N- Main Control Box
Power Panel— Until 3/05 6
Fan Motor Contactors, Overloads, Fusing Components & Line Reactors,
Continued
Code 08= P, S. Between 10/04 and 3/05 either this Power Panel OR the redesigned MicroTech II Power Panel (Code 08= D, F) could
be installed. Check the GO or visually inspect the unit to verify which panel is installed.
6
50 Horsepower Motor- Code 22 OR 32= S AND Code 10= AL, PW 5
Sch. Part
Sym. Description
Contactors
M9, 10 4
M19, 20 Contactor- Supply (M9, 10), Return (M19, 20) Fan Motor
Fuse Block and Fuses
FB9,10 4
FB19, 20 Fuse Block- Supply (FB9, 10), Return (FB19, 20) Fan Motor
Fuse Block- Supply Fan Motor
Fuse- FB9,10, 19, 20
Fuse- FB9,10, 19, 20
Overloads and Heaters
OL9,10 4
OL19, 20 Overload- Supply (OL9, 10), Return (OL19, 20) Fan Motor
Overload
Heater, Overload
LR10, 20 Line Reactors
PartVoltage
Number 208V230V380V 460V575V
027514407
2
2
1
1
023780213 2 32
023780212
1
1
025860518 6 36 3 3
025860416
1
1
1
3
1
2
NOTE: Quantities Listed are PER motor.
1
Note that there have been two different series of Overloads and Overload Heaters used during the production run.
When replacing an Overload OR the matching Overload Heater it is VITAL to obtain vendor p/n and amperage rating from BOTH parts.
When replacing ONLY an Overload Heater, it is VERY IMPORTANT to first obtain vendor information and amperage rating from the existing
Overload, Overload Heater, and Motor. It is important to obtain this information to ensure that the correct Overload Heater is selected since
Overload Heaters are chosen based upon Motor amperage draw, AND Overload Heaters are NOT interchangeable between series. Also,
Overload Heaters DO NOT automatically come with Overloads. OVERLOAD HEATERS MUST BE ORDERED SEPARATELY.
Once vendor and amperage information is obtained, contact Daikin Applied for p/ns.
2
When the unit has an Inverter with Bypass (Code 14= 2, 4, 5, 8) the Line Reactors are located in the Bypass Box. When there is no Inverter
Bypass Box the Line Reactors are located in the Main Control Power Panel. Line Reactor part numbers are listed in the Supply Air section
(Section F).
3
This part number is used for a Motor with no Inverter. If the 208V unit has an Inverter use Fuse Block p/n 023780218 and Fuse p/n 025860523.
4
M9, M10, FB9 FB19, OL9 and OL19 are only used on 208/230V motors.
5
If Code 10= PP, PS contact Daikin Applied with p/n information so that the correct part(s) can be identified. (Rare option.)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 225
Section N- Main Control Box
Power Panel— Until 3/05 5
Fan Motor Contactors, Overloads and Fusing
Components, Continued
Code 08= P, S. Between 10/04 and 3/05 either this Power Panel OR the redesigned MicroTech II Power Panel (Code 08= D, F) could
be installed. Check the GO or visually inspect the unit to verify which panel is installed.
5
60 Horsepower Motor- Code 22 OR 32= S AND Code 10= AL, PW 4
Sch. Part
Sym. Description
Contactors
M9, 10
M19, 20 Contactor- Supply (M10), Return (M20) Fan Motor
Contactor- Supply Fan Motor
Fuse Block and Fuses
FB9,10 FB19 ,20Fuse Block- Supply (FB9,10), Return (FB19,20) Fan Motor
Fuse Block- Supply Fan Motor
Fuse- FB9,10, 19, 20
Fuse- FB9,10, 19, 20
Fuse- FB9,10, 19, 20
Overloads and Heaters
OL9,10
OL19, 20Overload- Supply (OL9,10), Return (OL19,20) Fan Motor
Overload
Heater, Overload
LR10, 20 Line Reactors Part Voltage
Number 208V230V380V 460V575V
027514408 2
2
027514405
2
2
2
023780213 2 2
023780210
2 32 32
025860518 6
6
025860414
6 3 6 3
025860413
3
1
1
2
NOTE: Quantities Listed are PER motor.
1
Note that there have been two different series of Overloads and Overload Heaters used during the production run.
When replacing an Overload OR the matching Overload Heater it is VITAL to obtain vendor p/n and amperage rating from BOTH parts.
When replacing ONLY an Overload Heater, it is VERY IMPORTANT to first obtain vendor information and amperage rating from the existing
Overload, Overload Heater, and Motor. It is important to obtain this information to ensure that the correct Overload Heater is selected since
Overload Heaters are chosen based upon Motor amperage draw, AND Overload Heaters are NOT interchangeable between series. Also,
Overload Heaters DO NOT automatically come with Overloads. OVERLOAD HEATERS MUST BE ORDERED SEPARATELY.
Once vendor and amperage information is obtained, contact Daikin Applied for p/ns.
2
When the unit has an Inverter with Bypass (Code 14= 2, 4, 5, 8) the Line Reactors are located in the Bypass Box. When there is no Inverter
Bypass Box the Line Reactors are located in the Main Control Power Panel. Line Reactor part numbers are listed in the Supply Air section
(Section F).
3
This part number is used for a Motor with no Inverter. If a 380V or 460V unit has an Inverter use Fuse Block p/n 023780212 and Fuse p/n
025860418.
4
If Code 10= PP, PS contact Daikin Applied with p/n information so that the correct part(s) can be identified. (Rare option.)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 226
Section N- Main Control Box
Power Panel— Until 3/05 5
Fan Motor Contactors, Overloads and Fusing
Components, Continued
Code 08= P, S. Between 10/04 and 3/05 either this Power Panel OR the redesigned MicroTech II Power Panel (Code 08= D, F) could
be installed. Check the GO or visually inspect the unit to verify which panel is installed.
5
75 Horsepower Motor- Code 32= S AND Code 10= AL, PW 4
Sch. Part
Sym. Description
Contactors
M9, 10 Contactor- Supply Fan Motor
Fuse Block and Fuses
FB9, 10 Fuse Block- Supply Fan Motor
Fuse- FB9,10
Overloads and Heaters
OL9, 10 Overload- Supply Fan Motor
Overload Heater- Overload
LR10 Line Reactors Part
Voltage
Number 460V575V
027514406 2
2
023780210 2 32
025860514 6 36
1
1
2
NOTE: Quantities Listed are PER motor.
1
Note that there have been two different series of Overloads and Overload Heaters used during the production run.
When replacing an Overload OR the matching Overload Heater it is VITAL to obtain vendor p/n and amperage rating from BOTH parts.
When replacing ONLY an Overload Heater, it is VERY IMPORTANT to first obtain vendor information and amperage rating from the existing
Overload, Overload Heater, and Motor. It is important to obtain this information to ensure that the correct Overload Heater is selected since
Overload Heaters are chosen based upon Motor amperage draw, AND Overload Heaters are NOT interchangeable between series. Also,
Overload Heaters DO NOT automatically come with Overloads. OVERLOAD HEATERS MUST BE ORDERED SEPARATELY.
Once vendor and amperage information is obtained, contact Daikin Applied for p/ns.
2
When the unit has an Inverter with Bypass (Code 14= 2, 4, 5, 8) the Line Reactors are located in the Bypass Box. When there is no Inverter
Bypass Box the Line Reactors are located in the Main Control Power Panel. Line Reactor part numbers are listed in the Supply Air section
(Section F).
3
This part number is used for a Motor with no Inverter. If the 460V unit has an Inverter use Fuse Block p/n 023780215 and Fuse p/n
025860420.
4
If Code 10= PP, PS contact Daikin Applied with p/n information so that the correct part(s) can be identified. (Rare option.)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 227
Section N- Main Control Box
Power Panel 10/04 thru 12/04 1
Units with Semihermetic Compressors (Code 44= H, K)
Diagram
The single RPS control box (Code 12= D, F) was used on some units prior to the change from semihermetic to scroll compressors.
Unit size 105 shown. Components and component location may vary depending upon unit size.
1
See Control Panel
F F MMP
12 11 12
See
Control
Panel
M11 M21
MMP
22
M12 M13 M14
NOTE:
Condenser Fan MMP (12, 22, 24) & Contactors
MMP (M11- 24) are shown with the 208/230V Speedtrol
(Code 47= 2) arrangement. Components &
24
Component layout may vary depending upon
voltage and unit options selected.
M22 M23 M24
T1
PWR
F3
F1.A
F1.B
F1.C
TB3
PL1 - PL43 Plugs
CB10
CB20
or
or
MMP10 MMP20
GFR1
PB11
PVM1
M10
or
PB10
M20
or
PB20
MMP
4
MMP
8
M4
M8
Compressor MMP and Contactors
460 or 575 AL
PVM2
PB12
GFR2
REC1
GFS1
GFS2
Compressor MMP (MMP1-8)/Contactors (M1-8) show
TB3
MMP
1
MMP
2
MMP
3
MMP
4
208/230V AL or PW or 460/575 PW
(size 105 shown)
MMP MMP
1
5
TB4
M1
M2
M3
M4
M1 M5
MMP MMP MMP
3
7
2
M3
M7
M2
MMP
6
M6
DS2
or
PB2
DS1
or
PB1
TB2
TB7
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 228
Section N- Main Control Box
Unit Sizes 080- 105 Power Panel 3/05 thru 10/06 1
Units with Scroll Compressors (Code 44= Z, T)
Diagram
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
See Control Panel
MMP
11
See Control Panel
MMP
13
MMP
21
MMP
23
NOTE:
— The Condenser Fan MMP (11, 13 ,21, 23) &
Contactors (M11- 24) are shown with the 208V
Fantrol (Code 47= 1) arrangement.
M11 M12 M13 M14 M21 M22 M23 M24
T1
PWR
F3
F1.A
F1.B
F1.C
TB3
PL1 - PL43 Plugs
CB10
CB20
or
or
MMP10 MMP20
GFR1
PB11
PVM1
M10
or
PB10
PVM2
M20
or
PB20
PB12
GFR2
REC1
GFS1
GFS2
TB3
TB4
MMP MMP MMP MMP
1
3
5
2
MMP MMP
6
4
TB2
M1
M3
M5
M2
M4
DS2
or
PB2
DS1
or
PB1
M6
TB7
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 229
Section N- Main Control Box
Unit Sizes 115- 135 Power Panel 3/05 thru 10/06 1
Diagram
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
See Control Panel
F
11
MMP
12
MMP MMP MMP
24
14 22
NOTE:
— The Condenser Fan MMP (12,14,22,24)
& Contactors (M11- 24) are shown with the
460/575V Fantrol (Code 47= 1) arrangement.
See Control Panel
M11 M21 M12 M13 M14
M22 M23 M24
T1
PWR
F3
F1.A
F1.C
F1.B
TB3
PL1 - PL43 Plugs
CB10
CB20
or
or
MMP10 MMP20
Compressor MMP and Contactors
208/230V AL, PW OR
460V, 575V PW
MMP
4
MMP
8
M4
M8
GFR1
PB11
PVM1
M10
or
PB10
PVM2
M20
or
PB20
PB12
REC1
GFS1
TB3
MMP MMP
1
5
MMP MMP MMP
3
7
2
GFR2
GFS2
Compressor MMP (MMP1- 4)
Contactors (M1- 4) show
460, 575V AL
TB4
MMP MMP MMP
1
2
3
MMP
4
TB2
M1
M4
M3
M2
DS2
or
PB2
DS1
or
PB1
MMP
6
TB7
M1
M5
M3
M7 M2
M6
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 230
Section N- Main Control Box
Power Panel 3/05 thru 10/06 2
Common Components
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
2
Power Panel- Terminal Blocks, T1 Transformer & Fusing, Power Supply, Ground Fault
Sch.
Part
Part
Voltage
Sym. Description Number 208V230V460V575V
Terminal Blocks
1
1
1
1
TB2
Terminal Block- Field 349930603
1
1
1
1
TB3
Terminal Block- Factory 349930603
1
1
1
1
TB4
Terminal Block- RFS Field 349930603
1
1
1
1
TB7
Terminal Block- Field Convenience Outlet 349930603
Transformer- Main
T1
Transformer- Main Control
Electric, Hydronic, No Heat
Code 04= E, S, W, Y
Units without UV Lights 038253966
1
1
1
1
Units without UV Lights 038253991
Code 17 (2nd digit)= 1- 8 038253967
1
Units with UV Lights
Code 17 (2nd digit)= 1- 8 038253992
1
1
1
Units with UV Lights
Gas Heat Code 04= A
Units without UV Lights 038253967
1
1
1
1
Units without UV Lights 038253992
Code 17 (2nd digit)= 1- 8 038253968
1
Units with UV Lights
Code 17 (2nd digit)= 1- 8 038253959
1
Units with UV Lights
Code 17 (2nd digit)= 1- 8 038253993
1
Units with UV Lights
Fuses- T1
F1.A,B Fuse- T1 Transformer, Primary
Electric, Hydronic, No Heat
Code 04= E, S, W, Y
Units without UV Lights 349937133
2
Units without UV Lights 349937135
2
Units without UV Lights 349937129
2
Units without UV Lights 349937127
2
Code 17 (2nd digit)= 1- 8 349937136
2
2
Units with UV Lights
Code 17 (2nd digit)= 1- 8 349937132
2
Units with UV Lights
Code 17 (2nd digit)= 1- 8 349937130
2
Units with UV Lights
Gas Heat Code 04= A
Units without UV Lights 349937136
2
2
Units without UV Lights 349937132
2
Units without UV Lights 349937130
2
Units with UV Lights
Code 17 (2nd digit)= 1- 8 349937137
2
Units with UV Lights
Code 17 (2nd digit)= 1- 8 349937133
2
2
Code 17 (2nd digit)= 1- 8 349937132
2
Units with UV Lights
F1.C
Fuse- T1 Transformer, Secondary 349937035
1
1
1
1
F3
Fuse- Burner Blower Motor
Code 04= A
1
1
1
1
Fuse Block 023780223
Fuse
200- 1000 mbh furnace 349937035
1
1
1
1
Fuse
1100- 2000 mbh furnace 349937036
1
1
1
1
Fuse Cover
3499382071111
Power Supply Board
PWR Power Supply Board
5V 111049610
1
1
1
1
Ground Fault Protection
Code 17= G,B,C,D,K
GFR1, 2 Ground Fault Relay- SPDT 349937502
1
1
1
1
GFS1, 2 Ground Fault Sensor 349937407
1
1
1
1
1
Varies depending on unit options. Part number is for one individual section. Ground Block is p/n 349930604.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 231
Section N- Main Control Box
Power Panel 3/05 thru 10/06 2
Common Components, Continued
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
2
Power Panel- Phase Protection, Power Blocks
Voltage
Sch.
Part
Part
Sym. Description
Number 208V230V460V575V
Phase Voltage Monitor Code 17= P,A,C,D,H,J,K
PVM1, 2 Phase Voltage Monitor 112022001
1
1
1
Phase Voltage Monitor 112022002
1
Power Blocks
PB1, PB2 Power Block- Main
Code 11= P1, Q1
Power Block- 175A 1
0303727101111
Cover- 175A Block
3499383011111
Lug- 175A Block
3499380011111
0303727341111
Power Block- 255A 1
Cover- 255A Block
3499383021111
Lug- 255A Block
3499380011111
Power Block- 380A 1
0303727511111
Cover- 380A Block
3499383021111
Lug- 380A Block
3499380011111
Power Block- 420A 1
0303727521111
Cover- 420A Block
3499383021111
Lug- 420A Block
3499380021111
Power Block- 620A 1
0303727011111
Cover- 620A Block
3499383033333
Lug- 620A Block
3499380021111
Power Block- 760A 1
0303727601111
Cover- 760A Block
3499383033333
Lug- 760A Block
3499380031111
Power Block- 840A 1
0303727241111
Cover- 840A Block
3499383033333
Lug- 840A Block
3499380031111
PB11 Power Block- Power Distribution
Power Block- 175A 1
0303727051111
Cover- 175A Block
3499383011111
Power Block- 310A 1
0303727491111
Cover- 310A Block
3499383021111
0303727521111
Power Block- 420A 1
Cover- 420A Block
3499383021111
Power Block- 760A 1
0303727281111
Cover- 760A Block
3499383031111
PB12 Power Block- Power Distribution
Code 04= E
20, 40 KW Electric Heat 030372730
1
1
1
1
60, 80, 100 KW Electric Heat 030372744
1
1
60, 80, 100 KW Electric Heat 030372730
1
1
120 KW Electric Heat 030372752
1
1
120, 160 KW Electric Heat 030372744
1
1
200, 240, 280, 320 KW Electric Heat 030372752
1
1
PB10 Power Block- Supply Fan
Code 15= F 030372729
1
1
1
1
PB20 Power Block- Return Fan
Code 15= F 030372729
1
1
1
1
Any of the listed parts may be used, depending on unit options. Check installed part to verify, or contact Daikin Applied with unit serial
and/or GO number to ensure correct replacement is selected. PB2 is installed when code 11= Q1.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 232
Section N- Main Control Box
Power Panel 3/05 thru 10/06 5
Common Components, Continued
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
5
Power Panel- Receptacle, Disconnect Switch
Sch.
Part
Part
Voltage
Sym. Description
Number 208V230V460V575V
Receptacles
REC1
Receptacle
0390031001111
Disconnect Switch
DS1
Disconnect Switch- Main
Code 11= A2, C2, D2
DS2
Disconnect Switch- RAF/SAF
Code 11= C2, D2
Switch- 100A 1, 3
3499351011111
Lugs 349935901 3 23 23 23 2
Lug
3000414881111
Handle
3499355011111
Ground Lug
3499380011111
Switch- 150A 1
3499351021111
Lugs 349935901 6 26 26 26 2
Handle
3499355011111
Ground Lug
3499380011111
Switch- 250A 1
3499352011111
Lugs 349936001 6 26 26 26 2
Handle
3499355011111
Ground Lug
3499380011111
Switch- 400A 1
3499353011111
Lugs 349936201 2 22 22 22 2
Handle
3499356021111
Ground Lug
3499380021111
Switch- 600A 1
3499353021111
Lugs 349936201 2 22 22 22 2
Handle
3499356021111
Ground Lug
3499380021111
Switch- 800A 1
3499354011111
Lugs
3499364016666
Handle
3499357011111
Ground Lug
3499380031111
Switch- 1200A 1, 4
3499354031111
Lugs
3499365016666
Handle
3499357011111
Ground Lug
3499380031111
Any of the listed Disconnects may be used, depending on unit options. Check installed part to verify, or contact Daikin Applied with
unit serial and/or GO number to ensure correct replacement is selected.
2
The Lug quantites listed are for the DS1. DS2 use ½ the quantity plus an additional Lug: 150A Lug p/n 300041488; 250A Lug p/n 349936101; 400A Lug p/n TACL40PD3; 600A Lug p/n 349936301.
3
DS2 only.
4
DS1 only.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 233
Section N- Main Control Box
Power Panel 3/05 thru 10/06 11
Common Components, Continued
11
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
Power Panel- Plugs
Sch.
Sym.
4
5
6
7
8
9
10
Part
Description
Plugs 3
4 Pin Plug
6 Pin Plug
12 Pin Plug
3 Pin Cap Kit
6 Pin Cap Kit
9 Pin Cap Kit
15 Pin Cap Kit
Part
Voltage
Number 208V230V460V575V
349930201
349930403
349930405
349930501
349930503
349930504
349930506
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
All possible Plugs used are listed. Check actual unit to verify which Plug is required.
Used for PL1, PL, 2, PL3, PL4, PL5, PL6, PL22,PL23, PL24, PL37, PL38.
5
Used with Strain Relief (p/n 300041173) & 6 Pin Cap Kit (p/n 349930503). Used for PL20, PL21.
6
Used for PL11, PL12, PL25, PL26, PL27, PL28, PL29, PL30 (PL11 & 12 also use Strain Relief p/n 300041175 & Cap Kit p/n 349930505).
7
Used for PL16, PL17, PL31, PL32, PL33, PL34, PL39, PL40, PL41, PL42.
8
Used for PL9, PL10.
9
Used for PL18, PL19, PL35, PL36, PL43.
10
Used for PL7, PL8.
3
4
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 234
Section N- Main Control Box
Power Panel 3/05 thru 10/06 2
Common Components, Continued
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
2
1
Lug
2
Breaker
3
Rating Plug
Circuit Breakers- Motor Horsepower 2- 25 1
1
575V
460V
230V
208V
Voltage
Ref.Sch. Part Part
No. Sym. Description Number
1
Lug 3499359016 666
2 CB10 Circuit Breaker- Supply Fan
CB20 Circuit Breaker- Return Fan
Motor HP= 5, 7.5 349936601 1 1 1 1
Motor HP= 10, 15 349936602 1 1
Motor HP= 10, 15 349936601 1 1
Motor HP= 20, 25 349936603 1 1
Motor HP= 20, 25 349936602 1
Motor HP= 20 349936601 1
Motor HP= 25 349936602 1
3
Plug- Rating
Motor HP= 5 349936702 1 1
Motor HP= 5, 7.5 349936701 1 1
Motor HP= 7.5 349936704 1 1
Motor HP= 10 349936705 1 1
Motor HP= 10 349936702 1
Motor HP= 10 349936701 1
Motor HP= 15 349936707 1 1
Motor HP= 15 349936704 1
Motor HP= 15 349936702 1
Motor HP= 20 349936709 1
Motor HP= 20 349936708 1
Motor HP= 25 349936710 1
Motor HP= 25 349936709 1
Motor HP= 20, 25 349936705 1
Motor HP= 20 349936704 1
Motor HP= 25 349936705 1
Circuit Breakers are only used when a Fan Motor has an Inverter (Code 14= 1- 9, X).
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 235
Section N- Main Control Box
Power Panel 3/05 thru 10/06 2
Common Components, Continued
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
2
1
Lug
2
Breaker
3
Rating Plug
Circuit Breakers- Motor Horsepower 30- 50 1
1
575V
460V
230V
208V
Voltage
Ref.Sch. Part Part
No. Sym. Description Number
1
Lug 3499359016 666
2 CB10 Circuit Breaker- Supply Fan
CB20 Circuit Breaker- Return Fan
Motor HP= 30 349936602 1
Motor HP= 30 349936603 1
Motor HP= 30, 40 349936604 1
Motor HP= 40 349936604 1
Motor HP= 40, 50 349936603 1
Motor HP= 30, 40, 50 349936602 1
Motor HP= 60, 75 349936603 1 1
3
Plug- Rating
Motor HP= 30 349936705 1
Motor HP= 30 349936706 1
Motor HP= 30 349936711 1
Motor HP= 30 349936712 1
Motor HP= 40 349936714 1 1
Motor HP= 40 349936708 1
Motor HP= 40 349936706 1
Motor HP= 50 349936707 1
Motor HP= 50 349936709 1
Motor HP= 60 349936709 1
Motor HP= 60 349936710 1
Motor HP= 75 349936711 1 1
Circuit Breakers are only used when a Fan Motor has an Inverter (Code 14= 1- 9, X).
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 236
Section N- Main Control Box
Power Panel 3/05 thru 10/06 1
Supply MMP10 & M10 Fan Contactor & Return MMP20 & M20 Fan Contactor
Diagrams
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
MMP
3
3A
3
Line
Shield
MMP
3E
3B
Short
Circuit 3C
Alarm
Aux. Contact
Link
1
3D
NO/NC Aux.
Contact
1D
Contactor
Cover
1A
NC Front
1B Aux. Contact
3B
Link
3C
1
Contactor
1A
NO/NC Aux.
Contact
1C
NO Front Aux. Contact
Short
Circuit
Alarm
Front
Mounted
Contact
MMP10 & M10 Link Detail
MMP20 & M20 Link Detail
Cover
1B
1D
NO Front Aux.Contact
1C
NC Front
Aux. Contact
MMP10 & M10 Link Detail
MMP20 & M20 Link Detail
5 HP Motors- All Voltages
7.5 HP Motor- 230/460/575V
10, 15HP Motors- 460/575V
7.5 HP Motors- 208V
10, 15HP Motors- 208/230V
20, 25, 30 HP Motors- 460/575V
40 HP Motors- 575V
NOTE: The diagrams show all possible parts.
Not every part shown applies to every unit
size/voltage combination.
MMP
3G
3
Front
Mounted
Contact
3E
Lug
3
MMP
3F
3G
Lug
3
Trip Ind.
Interlock
Short
Circuit
Alarm
3C
Contactor
1
1
NO/NC Aux.
Contact
1B
NC Front
Aux. Contact
1D
NO Front Aux.
Contact
1C
MMP10 & M10 Link Detail
MMP20 & M20 Link Detail
20 HP Motors- 208/230V
25 HP Motors- 230V
40 HP Motors- 460V
50 HP Motors- 460/575V
60HP Motors- 575V
1D
NO/NC Aux.
Contact
1C
Contactor
NC Front
Aux. Contact
NO Front
Aux. Contact
1B
MMP10 & M10 Link Detail
MMP20 & M20 Link Detail
25 HP Motors- 208V
30 HP Motors- 208/230V
40 HP Motors- 230V
60 HP Motors- 460V
75 HP Motors- 460/575V
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
MMP
3F
Trip Ind.
Interlock
1
Contactor
MMP10 & M10 Link Detail
40 HP Motors- 208V
50 HP Motors- 208/230V
60HP- 208/230V
RPL 7000070 / Page 237
Section N- Main Control Box
Power Panel 3/05 thru 10/06 1
Supply MMP10 & M10 Fan Contactor & Return MMP20 & M20 Fan Contactor
Components
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
5 HP Motor- Code 22 OR 32= JEY, JFY, JHY, JJY, JKY
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932301 1
Contactor- Supply (M10) OR Return (M20) Fan 349932201 1
Contactor- Supply (M10) OR Return (M20) Fan 349932102 1 1
1A
Cover- Contactor 349932803 1
Cover- Contactor349932802 1
Cover- Contactor34993280111
3 MMP10, 20 MMP- Supply (MMP10) OR Return (MMP20) Fan 349934012 1 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934010 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934009 1
3A
Line Shield 3499330011 111
3B
Link 349932904 1
Link 349932902 111
3C
Short Circuit Alarm 349933903 1 1 1 1
3D
Aux. Interlock- 1 NO/1 NC 349933902 1 1 1 1
7.5 HP Motor- Code 22 OR 32= KEY, KFY, KHY, KJY, KKY
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932401 1
Contactor- Supply (M10) OR Return (M20) Fan 349932301 1
Contactor- Supply (M10) OR Return (M20) Fan 349932102 1 1
1A
Cover- Contactor 349932804 1
Cover- Contactor349932803 1
Cover- Contactor34993280111
3 MMP10, 20 MMP- Supply (MMP10) OR Return (MMP20) Fan 349934105 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934014 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934011 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934010 1
3A
Line Shield 349933001 111
3B
Link 349932906 1
Link349932904 1
Link34993290211
3C
Short Circuit Alarm 349933903 1 1 1 1
3D
Aux. Interlock- 1 NO/1 NC 349933902 1 1 1
3E
OL Circuit Alarm- Front 349933804 1
RPL 7000070 / Page 238
Section N- Main Control Box
Power Panel 3/05 thru 10/06 1
Supply MMP10 & M10 Fan Contactor & Return MMP20 & M20 Fan Contactor
Components, Continued
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
10 HP Motor- Code 22 OR 32= LEY, LFY, LHY, LJY, LKY
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932501 1 1
Contactor- Supply (M10) OR Return (M20) Fan 349932201 1
Contactor- Supply (M10) OR Return (M20) Fan 349932102 1
1A
Cover- Contactor 349932805 1 1
Cover- Contactor3499328021
Cover- Contactor3499328011
3 MMP10, 20 MMP- Supply (MMP10) OR Return (MMP20) Fan 349934106 1 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934012 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934011 1
3A
Line Shield34993300111
3B
Link 349932907 1 1
Link3499329031
Link3499329021
3C
Short Circuit Alarm 349933903 1 1 1 1
3D
Aux. Interlock- 1 NO/1 NC 349933902 1 1
3E
OL Circuit Alarm- Front 349933804 1 1
15 HP Motor- Code 22 OR 32= MEY, MFY, MHY, MJY, MKY
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932501 1 1
Contactor- Supply (M10) OR Return (M20) Fan 349932301 1 1
1A
Cover- Contactor 349932805 1 1
Cover- Contactor34993280311
3 MMP10, 20 MMP- Supply (M10) OR Return (M20) Fan 349934108 1 1
MMP- Supply (M10) OR Return (M20) Fan 349934014 1
MMP- Supply (M10) OR Return (M20) Fan 349934013 1
3A
Line Shield34993300111
3B
Link 349932907 1 1
Link34993290411
3C
Short Circuit Alarm 349933903 1 1 1 1
3D
Aux. Interlock- 1 NO/1 NC 349933902 1 1
3E
OL Circuit Alarm- Front 349933804 1 1
RPL 7000070 / Page 239
Section N- Main Control Box
Power Panel 3/05 thru 10/06 1
Supply MMP10 & M10 Fan Contactor & Return MMP20 & M20 Fan Contactor
Components, Continued
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
20 HP Motor- Code 22 OR 32= NEY, NFY, NHY, NJY, NKY
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932601 1 1
Contactor- Supply (M10) OR Return (M20) Fan 349932501 1 1
1A
Cover- Contactor34993280511
3 MMP10,20 MMP- Supply (M10) OR Return (M20) Fan 349934109 1
MMP- Supply (M10) OR Return (M20) Fan 349934108 1
MMP- Supply (M10) OR Return (M20) Fan 349934106 1
MMP- Supply (M10) OR Return (M20) Fan 349934105 1
3B
Link34993290711
3C
Short Circuit Alarm 349933903 1 1 1 1
3E
OL Circuit Alarm- Front 349933804 1 1 1 1
25 HP Motor- Code 22 OR 32= PEY, PFY, PHY, PJY, PKY
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932601 1 1
Contactor- Supply (M10) OR Return (M20) Fan 349932501 1 1
1A
Cover- Contactor34993280511
3 MMP10,20 MMP- Supply (M10) OR Return (M20) Fan 349938606 1
MMP- Supply (M10) OR Return (M20) Fan 349934109 1
MMP- Supply (M10) OR Return (M20) Fan 349934107 1
MMP- Supply (M10) OR Return (M20) Fan 349934106 1
3B
Link34993290711
3C
Short Circuit Alarm 349933903 1 1 1
3E
OL Circuit Alarm- Front 349933804 1 1 1
3F
Trip Indicator Interlock 349938701 1
3G
Lug (3 per kit) 349938801 2
RPL 7000070 / Page 240
Section N- Main Control Box
Power Panel 3/05 thru 10/06 2
Supply MMP10 & M10 Fan Contactor & Return MMP20 & M20 Fan Contactor
Components, Continued
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
2
30 HP Motor- Code 22 OR 32= QEY, QFY, QHY, QJY, QKY
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932602 1
Contactor- Supply (M10) OR Return (M20) Fan 349932601 1
Contactor- Supply (M10) OR Return (M20) Fan 349932502 1
Contactor- Supply (M10) OR Return (M20) Fan 349932501 1
1A
Cover- Contactor34993280511
3 MMP10, 20 MMP- Supply (M10) OR Return (M20) Fan 349938606 1 1
MMP- Supply (M10) OR Return (M20) Fan 349934107 1 1
3B
Link34993290711
3C
Short Circuit Alarm 349933903 1 1
3E
OL Circuit Alarm- Front 349933804 1 1
3F
Trip Indicator Interlock 349938701 1 1
3G
Lug (3 per kit) 349938801 2 2
40 HP Motor- Code 22 OR 32= REY, RFY, RHY, RJY, RKY
1
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932701 1
Contactor- Supply (M10) OR Return (M20) Fan 349932602 1
Contactor- Supply (M10) OR Return (M20) Fan 349932601 1
Contactor- Supply (M10) OR Return (M20) Fan 349932502 1
1A
Cover- Contactor3499328051
3 MMP10, 20 MMP- Supply (MMP10) OR Return (MMP20) Fan 349938607 1 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934108 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934109 1
3B
Link3499329071
3C
Short Circuit Alarm 349933903 1 1
3E
OL Circuit Alarm- Front 349933804 1 1
3F
Trip Indicator Interlock 349938701 1 1
3G
Lug (3 per kit) 349938801 1111
Also requires 3 ring terminals.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 241
Section N- Main Control Box
Power Panel 3/05 thru 10/06 3
Supply MMP10 & M10 Fan Contactor & Return MMP20 & M20 Fan Contactor
Components, Continued
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
3
50 HP Motor- Code 22 OR 32= SEY, SFY, SHY, SJY, SKY
1
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1
M10
Contactor- Supply (M10) OR Return (M20) Fan 349932701 1 1
Contactor- Supply (M10) OR Return (M20) Fan 349932601 1 1
3 MMP10, 20 MMP- Supply (MMP10) OR Return (MMP20) Fan 349938607 1 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934108 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934109 1
3C
Short Circuit Alarm 349933903 1 1
3E
OL Circuit Alarm- Front 349933804 1 1
3F
Trip Indicator Interlock 349938701 1 1
3G
Lug (3 per kit) 349938801 1111
Also requires 3 ring terminals.
60 HP Motor- Code 32 OR 32 = TEY, TFY, THY, TJY, TKY
2
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1
M10
Contactor- Supply (M10) OR Return (M20) Fan 349932702 1 1
Contactor- Supply (M10) OR Return (M20) Fan 349932601 1
Contactor- Supply (M10) OR Return (M20) Fan 349932602 1
3 MMP10, 20 MMP- Supply (MMP10) OR Return (MMP20) Fan 349938608 1 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349938606 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934109 1
3C
Short Circuit Alarm 349933903 1
3E
OL Circuit Alarm- Front 349933804 1
3F
Trip Indicator Interlock 349938701 1 1 1
3G
Lug 349938801 3 23 2 6
Also requires 3 ring terminals.
75 HP Motor- Code 32= UEY, UFY, UHY, UJY, UKY
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1
M10
Contactor- Supply Fan 349932602 1 1
3
MMP10 MMP- Supply Fan 349938606 1 1
3F
Trip Indicator Interlock 349938701 1 1
3G
Lug 349938801 6 6
RPL 7000070 / Page 242
Section N- Main Control Box
Power Panel 3/05 thru 10/06 1
Unit Size 080: Scroll Compressors (Code 44= Z, T)
Compressor MMP1- 6 and Contactor M1- 6
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
3
MMP
MMP
3E
Line
Shield
3A
Front Mounted
Contact
3B
3B
Link
3D
Short
Circuit
Alarm
3
1
Contactor
1A
Cover
MMP & Contactor Link Detail
208/230V
Short
Circuit
Alarm
1
3D
Link
Contactor
1A
3C
Aux.
Contact
Cover
1B
NC Front
Aux. Contact
MMP & Contactor Link Detail
460/575V
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Part
Number
575V
Part
Description
Compressor Contactors & Parts
Contactor- Compressor
Contactor- Compressor
Cover- Contactor
Cover- Contactor
Aux. Contact, Front- 1NC
Compressor MMP’s & Parts
Manual Motor Protector- Compr.
Manual Motor Protector- Compr.
Manual Motor Protector- Compr.
Line Shield
Link
Link
Aux. Contact- 1NO/1NC
Short Circuit Alarm
Front Mounted Contact- 1NO
460V
Ref Sch
No Sym
1 M1- 6
1A
1B
3 MMP1- 6
3A
3B
3C
3D
3E
208/230V
080
349932502 6
349932301 6 6
349932805 6
349932803 6 6
349931901 6 6
349934108 6
349934015 6
349934013
349933001 6
349932904 6
349932907 6
349933901 6
349933903 6 6
349933801 6
Rev. AG 01/15
6
6
6
6
6
RPL 7000070 / Page 243
Section N- Main Control Box
Power Panel 3/05 thru 10/06 1
Unit Size 090: Scroll Compressors (Code 44= Z, T)
Compressor MMP1- 6 and Contactor M1- 6
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
4B
Short
Circuit
Alarm
3D
Link
4D
Contactor
1
2
Short
Circuit
Alarm
Contactor
2A
3A
4D
208/230V
Ref
Sch
No Sym
1 M1, 3, 5
1A
1B
2 M2, 4, 6
2A
2B
3 MMP1, 3, 5
3A
3B
3C
3D
3E
4 MMP2 ,4, 6
4A
4B
4C
4D
4E
MMP2,4,6 &
M2,4,6 Contactor Link Detail
208/230V
3C
or
4C
Aux.
Contact
4A
Line
Shield
4B
or
1
3D
or
Link
or
2
Cont.
1A
or
2A
1B
Cover
or
NC Front
2B
Aux.
Contact
MMP & Contactor Link Detail
460/575V
Part
Description
Compressor Contactors & Parts
Contactor- Compressor
Contactor- Compressor
Cover- Contactor
Aux. Contact, Front- 1NC
Contactor- Compressor
Contactor- Compressor
Cover- Contactor
Cover- Contactor
Aux. Contact, Front- 1NC
Compressor MMP’s & Parts
Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
Manual Motor Protector- Comprressor
Line Shield
Link
Aux. Contact- 1NO/1NC
Short Circuit Alarm
Front Mounted Contact- 1NO
Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
Manual Motor Protector- Comprressor
Line Shield
Link
Link
Aux. Contact- 1NO/1NC
Short Circuit Alarm
Front Mounted Contact- 1NO
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” 3B
or
Short
Circuit
Alarm
Cover
MMP1,3,5 &
M1,3,5 Contactor Link Detail
3
Rev. AG 01/15
Part
Number
349932601 3
349932301
349932803
349931901
349932502 3
349932301
349932805 3
349932803
349931901
575V
4
3E
MMP
MMP
Front Mounted
4E Contact
460V
3
208/230V
MMP
4
or
3 3
3 3
3 3
3 3
3 3
3 3
349934109 3
349934015 3
349934014 3
349933001 3 3
349932904 3 3
349933901 3 3
349933903 3 3 3
349933801 3
349934108 3
349934015 3
349934013 3
349933001 3 3
349932907 3
349932904 33
349933901 3 3
349933903 3 3 3
349933801 3
RPL 7000070 / Page 244
Section N- Main Control Box
Power Panel 3/05 thru 10/06 1
Unit Size 105: Scroll Compressors (Code 44= Z, T)
Compressor MMP1- 6 and Contactor M1- 6
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
MMP
3
3A
3B
1
3D
Short
Circuit
Alarm
3C
Aux.
Contact
MMP
Line
Shield
3
3E
Front
Mounted
Contact
Link
Contactor
1A
Cover
Short
Circuit
Alarm
3D
Contactor
1
1B
NC Front
Aux. Contact
MMP & Contactor Link Detail
460/575V
MMP & Contactor Link
Detail
208/230V
NOTE: The diagrams show all possible parts. Not every part shown applies
to every unit size/voltage combination.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Part
Number
575V
Part
Description
Compressor Contactors & Parts
Contactor- Compressor
Contactor- Compressor
Cover- Contactor
Aux. Contact, Front- 1NC
Compressor MMP’s & Parts
Manual Motor Protector- Compr.
Manual Motor Protector- Compr.
Manual Motor Protector- Compr.
Line Shield
Link
Aux. Contact- 1NO/1NC
Short Circuit Alarm
Front Mounted Contact- 1NO
460V
Ref Sch
No Sym
1 M1- 6
1A
1B
3 MMP1- 6
3A
3B
3C
3D
3E
105
208/230V
349932601 6
349932301 6 6
349932803 6 6
349931901 3 3
349934109 6
349934015 6
349934014
349933001 6
349932904 6
349933901 6
349933903 6 6
349933801 6
Rev. AG 01/15
6
6
6
6
6
RPL 7000070 / Page 245
Section N- Main Control Box
Power Panel 3/05 thru 10/06 1
Unit Sizes 080- 105: Semihermetic Compressors (Code 44= H, K) 2
Compressor MMP1- 8 and Contactor M1- 8
Diagrams
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
2
Unit sizes 080, 090, 105 began using Scroll Compressors shortly after the newer style unit Control Box design was employed.
1
3
MMP
MMP
Front Mounted
3E Contact
3B
3
1
3B
Link
3D
1
Contactor
1A
Link
1
3D
Short
Circuit
Alarm
Line
Shield
3A
Short
Circuit
Alarm
Contactor
3C
1A
Aux.
Contact
Cover
1B
Cover
NC Front
Aux. Contact
MMP & Contactor Link Detail
Unit Size 080: 460V PW & 575V AL
Unit Size 090: 460V PW
Unit Size 105: 208/230V 460V AL
MMP & Contactor Link Detail
Unit Size 080: 575V PW
Unit Size 090: 575V PW
Unit Size 105: 460/575V PW
NOTE: The diagrams show all possible parts. Not every part shown applies
to every unit size/voltage combination.
3G
MMP
Lugs
3
3E
3
Front
Mounted
Contact
MMP
3F
Short
Circuit
Alarm
3D
Contactor
1
1
MMP & Contactor Link Detail
Unit Size 080: 208/230V
Unit Size 090: 575V AL
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Trip
Indicator
Contactor
MMP & Contactor Link Detail
Unit Size 090: 208/230V & 460V AL
Rev. AG 01/15
RPL 7000070 / Page 246
Section N- Main Control Box
Power Panel 3/05 thru 10/06 4
Unit Sizes 080- 105: Semihermetic Compressors (Code 44= H, K) 5
Compressor MMP1- 8 and Contactor M1- 8
Components
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
5
Unit sizes 080, 090, 105 began using Scroll Compressors shortly after the newer style unit Control Box design was employed.
4
575V PW
575V AL
460V AL
460V PW
575PW
208/230V
575V AL
460V AL
460V PW
208/230V
575 PW
575V AL
460V AL
460V PW
208/230V
080
090
105
Ref Sch Part
Part
No Sym Description
Number
Comp. Contactors & Parts
1 M1- 81 Contactor- Compressor
349932601 4
Contactor- Compressor
34993260242
Contactor- Compressor
3499325024
2
8
Contactor- Compressor
349932503222
Contactor- Compressor
349932501444
Contactor- Compressor
3499322018
Contactor- Compressor
349932301448
1A Cover- Contactor
349932805424844
Cover- Contactor
3499328028
Cover- Contactor
349932803448
1B
Aux. Contact, Front- 1NC
349931901 2323 4343
Comp. MMP’s & Parts
3 MMP1- 81 Manual Motor Protector- Compressor
3499341094
22
Manual Motor Protector- Compressor3499341074484
Manual Motor Protector- Compressor
3499340138
Manual Motor Protector- Compressor
34993401448
Manual Motor Protector- Compressor
3499340154
Manual Motor Protector- Compressor
34993410824
Manual Motor Protector- Compressor
3499386064
2
3A Line Shield
3499330014488
3B Link
3499329038
Link
349932904448
Link
3499329074242844
3C Aux. Contact- 1NO/1NC
3499339014488
3D
Short Circuit Alarm
349933903 42424 42484848
3E
Front Mounted Contact- 1NO
349933801 4242 4284 4
3F Trip Indicator
3499387014
2
3G
Lug Kit (3 lugs per kit)
349938801 8 4
NOTE: PW= Part Winding Start (Code 10= PW); AL= Across the Line Start (Code 10= AL).
1
MMP1, 2/M1, 2 apply to 080- 105, all voltages and starting options.
MMP3, 4/M3 ,4 apply to 105, 208/230V units and 460 and 575V Part Winding units only.
MMP5, 6/M5 ,6 apply to 080- 105, 208/230V units and 460 and 575V Part Winding units only.
MMP7, 8/M7, 8 apply to 105, 208/230V units and 460 and 575V Part Winding units only.
2
230V unit uses p/n 349932601.
3
Applies to M1, M2 (080, 090) only; M1, M2, M3, M4 (105) only.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 247
Section N- Main Control Box
Power Panel 3/05 thru 10/06 3
Unit Size 115: Semihermetic Compressors (Code 44= H, K)
Compressor MMP1- 8 and Contactor M1- 8
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
3
3D
Short
Circuit
Alarm
1
Link
Contactor
1A
Cover
MMP & Contactor Link Detail
575V AL
3B
3D
Short
Circuit
Alarm
3C
1
3E
Link
Short
Circuit
Alarm
Contactor
1A
Aux.
Contact
3D
1
MMP & Contactor Link Detail
208/230V & 460V AL
Part
Number
Front
Mtd.
Contact
Contactor
Cover
NC Front
1B Aux. Contact
MMP & Contactor Link Detail
460V PW & 575 PW
Ref Sch Part
No Sym Description
Comp. Contactors & Parts
1 M1- 81 Contactor- Compressor
Contactor- Compressor
Contactor- Compressor
1A
Cover- Contactor
Cover- Contactor
1B
Aux. Contact, Front- NC
Comp. MMP’s & Parts
3 MMP1- 81 Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
3A
Line Shield
3B
Link
Link
3C
Aux. Contact- 1NO/1NC
3D
Short Circuit Alarm
3E
Front Mounted Contact- 1NO
3
115
575 PW
3B
MMP
Line
Shield
3A
575V AL
Front Mtd.
Contact
3
460V PW
3E
MMP
460V AL
MMP
208/230V
3
349932503 8 4
379932301 8 8
349932501 4
349932805 4
349932803 8 8
349931901 4242
349934109 8 4
349934107 4
349934013
349934015 8
349933001 8
349932904 8
349932907 4
349933901 8
349933903 8 4 8 4
349933801 8 4 4
8
8
8
8
8
NOTE: PW= Part Winding Start (Code 10= PW); AL= Across the Line Start (Code 10= AL).
1
MMP1- 4/M1- 4 apply to all sizes, all voltages and starting options.
MMP5- 8/M5- 8 apply to 208/230V and 460V, 575V Part Winding units only.
2
Used on M1, M2, M3, M4 only.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 248
Section N- Main Control Box
Power Panel 3/05 thru 10/06 2
Unit Size 125: Semihermetic Compressors (Code 44= H, K) AND
Across The Line Start Compressors (Code 10= AL)
Compressor MMP1- 8 and Contactor M1- 8
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
2
3
3E
Front Mtd.
Contact
3B
3D
Short
Circuit
Alarm
MMP
MMP
1
Link
Contactor
1A
Front
Mtd.
Contact
3E
Short
Circuit
Alarm
3D
Cover
MMP & Contactor Link Detail
575V
3
1
Contactor
MMP & Contactor Link Detail
208/230V & 460V
575V
460V
208/230V
125
Ref
Sch
Part
Part
No
Sym
Description
Number
Comp. Contactors & Parts
1 M1, 2, 5, 6 1 Contactor- Compressor
349932503 4 2
M1, 2 1
Contactor- Compressor
349932501 2
M3, 4, 7, 8 1 Contactor- Compressor
349932601 4
M3, 4 1
Contactor- Compressor
349932503 2
M3, 4 1
Contactor- Compressor
349932502 2
1A
Cover- Contactor
349932805 4
Comp. MMP’s & Parts
3 MMP1- 8 1 Manual Motor Protector- Compressor
349934109 8 4
MMP1, 2 1 Manual Motor Protector- Compressor
349934107 2
MMP3, 4 1 Manual Motor Protector- Compressor
349934108 2
3B
Link
349932907 4
3D
Short Circuit Alarm
349933903 8 4 4
3E
Front Mounted Contact- 1NO
349933801 8 4 4
NOTE: PW= Part Winding Start (Code 10= PW); AL= Across the Line Start (Code 10= AL).
1
MMP1- 4/M1- 4 apply to all voltages.
MMP5- 8/M5- 8 apply to 208/230V units only.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 249
Section N- Main Control Box
Power Panel 3/05 thru 10/06 1
Unit Size 125: Semihermetic Compressors (Code 44= H, K) AND
Part Winding Start Compressors (Code 10= PW)
Compressor MMP1- 8 and Contactor M1- 8
Diagrams
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
3
or
3E
4
3
MMP
or
4E
3B
or
Front Mtd.
Contact
4B
Link
or
4
MMP
3A
Short
Circuit
Alarm
4D
3B
or
4D
or
3D
Short
Circuit
Alarm
1
3D
1
2
or
1A
or
Cover
or
or
or
4B
Link
2
Cont.
1A
Cont.
4C
2A
3C
or
Line
Shield
4A
or
2A
Cover
Aux.
Contact
1B
or
2B
NC Front
Aux. Contact
MMP & Contactor Link Detail
MMP3,4,7,8 460V
MMP & Contactor Link Detail
MMP1-8 575V, MMP1,2,5,6 460V
3
or
MMP
4
3E
Front
Mtd.
Contact
4E
or
4D
or
3D
Short
Circuit
Alarm
1
or
2
Contactor
MMP & Contactor Link Detail
MMP1-8 Unit Sizes 208/230V
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 250
Section N- Main Control Box
Power Panel 3/05 thru 10/06 3
Unit Size 125: Semihermetic Compressors (Code 44= H, K) AND
Part Winding Start Compressors (Code 10= PW)
Compressor MMP1- 8 and Contactor M1- 8
Components
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
3
1
2
575V
Part
Number
125
460V
208/230V
Ref
Sch
Part
No
Sym
Description
Compressor Contactors & Parts
1 M1, 2, 5, 6 Contactor- Compressor
Contactor- Compressor
1A
Cover- M1, 2, 5, 6 Contactor
1B
Aux. Contact, Front- 1NC
2 M3, 4, 7, 8 Contactor- Compressor
Contactor- Compressor
Contactor- Compressor
2A
Cover- M3, 4, 7, 8 Contactor
Cover- M3, 4, 7, 8 Contactor
2B
Aux. Contact, Front- 1NC
Compressor MMP’s & Parts
3 MMP1, 2, 5, 6 Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
3A
Line Shield
3B
Link
3C
Aux. Contact- 1NO/1NC
3D
Short Circuit Alarm
3E
Front Mounted Contact- 1NO
4 MMP3, 4, 7, 8 Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
4A
Line Shield
4B
Link
Link
4C
Aux. Contact- 1NO/1NC
4D
Short Circuit Alarm
4E
Front Mounted Contact- 1NO
349932503 4
349932301 4 4
349932803 4 4
349931901 2121
349932601 4
349932502 4
349932301 4
349932805 4
349932803 4
349931901 22
349934109 4
349934013
349934015 4
349933001 4
349932904 4
349933901 4
349933903 4 4
349933801 4
349934109 4
349934014
349934107 4
349933001
349932904
349932907 4
349933901
349933903 4 4
349933801 4 4
4
4
4
4
4
4
4
4
4
4
Applies to M1, M2 only.
Applies to M3, M4 only.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 251
Section N- Main Control Box
Power Panel 3/05 thru 10/06 3
Unit Size 135: Semihermetic Compressors (Code 44= H, K)
Compressor MMP1- 8 and Contactor M1- 8
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
3
3A
1A
Cover
MMP & Contactor Link Detail
575V AL
Link
1
3D
Short
Circuit
Alarm
3C
Aux.
Contact
Contactor
1A
Cover
Short
Circuit
Alarm
3D
Front
Mtd.
Contact
Contactor
1
1B
NC Front
Aux. Contact
MMP & Contactor Link Detail
Unit Sizes 460V PW & 575 PW
Ref Sch Part
No Sym Description
Comp. Contactors & Parts
1 M1- 81 Contactor- Compressor
Contactor- Compressor
Contactor- Compressor
Contactor- Compressor
1A
Cover- Contactor
Cover- Contactor
1B
Aux. Contact, Front- 1NC
Comp. MMP’s & Parts
3 MMP1- 81 Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
3A Line Shield
3B Link
Link
3C
Aux. Contact- 1NO/1NC
3D
Short Circuit Alarm
3E
Front Mounted Contact- 1NO
MMP & Contactor Link Detail
Unit Sizes 208/230V & 460V AL
Part
Number
135
575 PW
Contactor
3B
3
3E
575V AL
1
Link
Line
Shield
460V AL
Front Mtd.
Contact
3B
Short
Circuit
Alarm
MMP
3
460V PW
3E
3D
MMP
MMP
208/230V
3
349932601 8
349932503 4
349932502 8 4
3499323018
349932805 8 4
3499328038
349931901 42
349934109 8 4
349934107 8
349934108 4
349934014 8
3499330018
3499329048
34993290784
349933901 8
349933903 84848
349933801 8 4 8 4
NOTE: PW= Part Winding Start (Code 10= PW); AL= Across the Line Start (Code 10= AL).
MMP1- 4/M1- 4 apply to all sizes, all voltages and starting options.
MMP5- 8/M5- 8 apply to 208/230V and 460V, 575V Part Winding units only.
2
Applies to M1, M2, M3 and M4 only.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 252
Section N- Main Control Box
Power Panel 3/05 thru 10/06 1
Condenser Fan MMP11, 12, 13, 21, 22, 23 and Contactors M11- 24
FanTrol Units (Code 47= 1)
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
Short
Circuit
Alarm
8A
8D
Line
Shield
8
MMP13, 23 used on sizes 080, 090, 105, 115
MMP11, 21 used on sizes 080, 090, 105, 115, 125, 135
MMP
MMP12, 22 used on sizes 125, 135
8B
Link
8C
7
Bus Bar
Contactor
MMP & Contactors Detail
(applies to all sizes)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
575V
460V
208/230V
575V
460V
208/230V
575V
460V
208/230V
080- 105
115
125, 135
Ref
Schematic
Part
Part
No
Symbol
Description
Number
Fan Contactors
7 M11,12,13,14
21, 22, 23, 24 Contactor- Condenser Fan
349934201888888888
Fan MMP’s & Parts
8
MMP11, 21
Manual Motor Protector
349934009 2 2 2 2
Manual Motor Protector
3499340102222
Manual Motor Protector
3499340122
MMP13, 23
Manual Motor Protector
349934009 2 2
Manual Motor Protector
349934010 2 2 2
Manual Motor Protector
349934012 2
MMP12, 22 Manual Motor Protector
3499340102
2
Manual Motor Protector
3499340122
8A
Line Shield- MMP
349933001444444444
8B
Link- MMP
349932901444444444
8C
Bus Bar
349934301444444444
8D
Short Circuit Alarm
349933903444444444
RPL 7000070 / Page 253
Section N- Main Control Box
Power Panel 3/05 thru 10/06 1
Condenser Fan MMP12, 14, 22, 24 and Contactors M11 - 24
Speedtrol Units (Code 47= 2)
Code 08= D, F. Between 10/04 & 3/05 either this Power Panel OR the original MicroTech II Power Panel (Code 08= P, S) could be installed.
Check the GO or contact Daikin Applied to verify which panel is installed. If built between 10/06 & 12/06 contact Daikin Applied.
1
Short
Circuit
Alarm
8A
8D
Line
Shield
MMP12, 22 used on sizes 080,090,105,115,135
8
9A
MMP MMP14, 24 used on sizes 115,125,135
8B
Link
8C
Bus Bar
F11 used on All Speedtrol Fuse
Units Block
F12 used on 208/230V Units
9
9B
Contactor
Fuse
Fuse Puller
7
7
MMP & Contactors Detail
(applies to all sizes)
Contactor
Speedtrol Fusing Detail
F11, F12 & M12, M22 (with Speedtrol)
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
575V
460V
208/230V
575V
460V
208/230V
575V
460V
208/230V
080- 105
115
125, 135
Ref
Schematic
Part
Part
No
Symbol
Description
Number
Fan Contactors
7 M11,12,13,14
21, 22, 23, 24 Contactor- Condenser Fan
349934201888888888
Fan MMP’s & Parts
8
MMP12, 22
Manual Motor Protector
349934009 2 2
Manual Motor Protector
349934010 222 22
Manual Motor Protector
349934012
22
MMP14, 24
Manual Motor Protector
349934009 2 2 2 2
Manual Motor Protector
34993401022
8A
Line Shield- MMP
349933001222444444
8B
Link- MMP
349932901222444444
8C
Bus Bar (MMP12, 22 only)
349934301222222222
8D
Short Circuit Alarm
349933903222444444
9
F11
Fuse Block
023780222111111111
F12
Fuse Block
023780222111
9A
F11
Fuse
349937133222222
F11
Fuse
349937129222
F12
Fuse
349937129222
9B
Fuse Puller
349938227422422422
RPL 7000070 / Page 254
Section N- Main Control Box
Unit Sizes 080- 105 Power Panel 1/07 & Later 1
Diagram
1
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
See Control Panel
MMP
11
MMP
13
MMP
21
MMP
23
See Control Panel
M11 M12 M13 M14 M21 M22 M23 M24
NOTE:
— The Condenser Fan MMP (11, 13, 21, 23) &
Contactors (M11- 24) are shown with the Fantrol
(Code 47= 1) arrangement.
— The diagram on the following page illustrates
460/575V Speedtrol (Code 47= 2) arrangement, and
the inset to the left illustrates the 208/230V Speedtrol
arrangement.
T1
PWR
F3
F1.A
F1.B
F1.C
TB3
F5 F2
Fan MMP & Contactors- 208/230V
Speedtrol (Code 47= 2) arrangement.
M11 M21
MMP
12
M12 M13 M14
MMP
22
MMP
24
PL1 - PL43 Plugs
F F
11 12
CB10
CB20
or
or
MMP10 MMP20
M22 M23 M24
GFR1
PB11
PVM1
M10
or
PB10
PVM2
M20
or
PB20
PB12
GFR2
REC1
GFS1
GFS2
TB3
TB4
MMP MMP MMP MMP
1
3
5
2
MMP MMP
6
4
TB2
M1
M3
M5
M2
M4
DS2
or
PB2
DS1
or
PB1
M6
TB7
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 255
Section N- Main Control Box
Unit Sizes 115- 135 Power Panel 1/07 & Later 1
Diagram
1
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
See Control Panel
F
11
See Control Panel
M11 M21
MMP
12
MMP MMP MMP
24
14 22
M12 M13 M14
NOTE:
— The Condenser Fan MMP (12, 14, 22 ,24)
& Contactors (M11- 24) are shown with the
460/575V Fantrol (Code 47= 1) arrangement.
— The diagrams on the previous page illustrates
the Fantrol (Code 47= 1) arrangement, and the
208/230V Speedtrol Unit.
M22 M23 M24
T1
PWR
F3
F1.A
F1.B
F1.C
TB3
F5 F2
PL1 - PL43 Plugs
CB10
CB20
or
or
MMP10 MMP20
Compressor MMP and Contactors
208/230V AL, PW OR
460V, 575V PW
MMP
4
MMP
8
M4
M8
GFR1
PB11
PVM1
M10
or
PB10
PVM2
M20
or
PB20
PB12
REC1
GFS1
MMP MMP MMP
3
7
2
GFS2
Compressor MMP (MMP1- 4)/
Contactors (M1- 4) show
TB3
MMP MMP
1
5
GFR2
460 or 575V AL
TB4
MMP MMP MMP
1
2
3
MMP
4
TB2
M1
M4
M3
M2
DS2
or
PB2
DS1
or
PB1
MMP
6
TB7
M1
M5
M3
M7 M2
M6
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 256
Section N- Main Control Box
Power Panel 1/07 & Later 6
Common Components
6
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
Power Panel- Terminal Blocks, T1 Transformer & Fusing
Sch. Part
Sym. Description
Terminal Blocks
TB2, 7 Terminal Block
TB3, 4 Terminal Block
Transformer- Main 3
T1
Transformer- Main Control
Electric, Hydronic, No Heat
Code 04= E, S, W, Y
Units without UV Lights
Units without UV Lights
Units without UV Lights
Units with UV Lights
Code 17 (2nd digit)= 1- 8
Units with UV Lights
Code 17 (2nd digit)= 1- 8
Units with UV Lights
Code 17 (2nd digit)= 1- 8
Gas Heat Code 04= A
Units without UV Lights
Units without UV Lights
Units without UV Lights
Units with UV Lights
Code 17 (2nd digit)= 1- 8
Units with UV Lights
Code 17 (2nd digit)= 1- 8
Units with UV Lights
Code 17 (2nd digit)= 1- 8
Fuses- T1
F1.A, B Fuse- T1 Transformer, Primary
Electric, Hydronic, No Heat
Code 04= E, S, W, Y
Units without UV Lights
Units without UV Lights
Units without UV Lights
Units without UV Lights
Units with UV Lights
Code 17 (2nd digit)= 1- 8
Units with UV Lights
Code 17 (2nd digit)= 1- 8
Units with UV Lights
Code 17 (2nd digit)= 1- 8
Gas Heat Code 04= A
Units without UV Lights
Units without UV Lights
Units without UV Lights
Units with UV Lights
Code 17 (2nd digit)= 1- 8
Units with UV Lights
Code 17 (2nd digit)= 1- 8
Units with UV Lights
Code 17 (2nd digit)= 1- 8
F1.C Fuse- T1 Transformer, Secondary
Fuse- T1 Transformer, Secondary
Fuse- T1 Transformer, Secondary
Part
Voltage
Number 208V230V 460V 575V
349930641
349930641
1
1
1
1
2
2
2
2
038253975
1
038253957
1
1
038253984
1
038253976
1
038253958
1
1
038253985
1
038253976
1
038253958
1
1
038253985
349939819
1
349939809
1
1
349939829
349937134
2
349937133
2
349937129
2
349937125
349937135
2
2
349937131
2
349937129
349937135
2
2
349937131
2
349937129
349937137 2 52 5
349937133
2 5
349937132
349937038 41 1 1
349937036 41 1 1
349937035 41 1 1
1
1
2
2
2
25
1
1
1
Varies depending on unit options. Part number is for one individual section. Ground Block is p/n 349930647.
Varies depending on unit options. Part number is for one individual section. When required, Jumpers are p/n 349930922 (2 pole),
349930923 (3 pole), 349930924 (4 pole), 349930925 (5 pole).
3
T1 transformers also use Cover Kit p/n 349955901 & Fuse Puller Kit p/n 349955801 (Not Used on Transformer p/n 349939819,
349939809, 349939829.
4
Fuse depends on heat type and presence of UV lights. 349937038= Gas Heat Unit w/UV lights; 349937036= Gas Heat Unit with no
UV lights OR Non-Gas Heat Unit with UV lights; 349937035= Non- Gas Heat Units with no UV lights.
5
Fuses used on Gas Heat Unit w/UV lights also use Fuse Block p/n 023780231 & 3 Fuse Pullers p/n 349938227.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 257
Section N- Main Control Box
Power Panel 1/07 & Later 3
Common Components, Continued
3
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
Power Panel- Fuses, Phase Protection, Ground Fault, Power Blocks
Sch.
Part
Part
Voltage
Sym. Description
Number 208V230V460V575V
Fuses, continued
F2, F3, F5Fuses
Fuse Block 023780223 1/fuse 1/fuse 1/fuse 1/fuse
Fuse Cover 349938227 1/fuse 1/fuse 1/fuse 1/fuse
F2
Fuse- 2000+VA transformer
3499370351111
F3 Fuse- Blower Motor
200- 1500 mbh furnace 349937035
1
1
1
1
F3 Fuse- Blower Motor
2000 mbh furnace 349937036
1
1
1
1
F5 Fuse- UV Lights
Code 17 (2nd digit)= 1- 8 349937032
1
1
1
1
Phase Voltage Monitor Code 17= P,A,C,D,H,J,K
PVM1, 2 Phase Voltage Monitor 112022001
1
1
1
Phase Voltage Monitor 112022002
1
Ground Fault Protection
Code 17= G,B,C,D,K
GFR1, 2 Ground Fault Relay- SPDT 349937502
1
1
1
1
GFS1, 2 Ground Fault Sensor 349937407
1
1
1
1
Power Blocks
PB1, PB2 Power Block- Main 2
Code 11= P1, Q1
Power Block, Non- Electric Heat Units- 175A 1
0303727761111
Power Block, Electric Heat Units- 175A 1
0303727801111
Lug- 175A Block
3499380011111
Power Block, Non- Electric Heat Units- 255A 1
0303727781111
Lug- 255A Block
3499380011111
Power Block, Non- Electric Heat Units- 380A 1
0303727791111
Power Block, Electric Heat- 380A 1
0303727821111
Lug- 380A Block
3499380021111
Power Block, Non- Electric Heat Units- 620A 1
0303727011111
Cover- 620A Block
3499383453333
Lug- 620A Block
3499380021111
Power Block, Non- Electric Heat Units- 760A 1
0303727601111
Power Block, Electric Heat Units, 208/230V- 760A 1 030372772
1
1
Power Block, Electric Heat Units, 460/575V- 760A 1 030372760
1
1
Cover- 760A Block
3499383453333
Lug- 760A Block
3499380031111
0303727241111
Power Block, Non- Electric Heat Units- 840A 1
Cover- 840A Block
3499383453333
Lug- 840A Block
3499380031111
PB11 Power Block- Power Distribution
Power Block- 420A 1
0303727851111
Power Block- 760A 1
0303727211111
Cover- 760A Block
3499383451111
PB12 Power Block- Power Distribution
Code 04= E
20, 40 KW Electric Heat 030372777
1
1
1
1
60, 80, 100, 120 KW Electric Heat 030372785
1
1
60, 80, 100, 120 KW Electric Heat 030372777
1
1
160, 200, 240, 280, 320 KW Electric Heat 030372785
1
1
Any of the listed parts may be used, depending on unit options. Check installed part to verify, or contact Daikin Applied with unit
serial and/or GO number to ensure correct replacement is selected. PB2 is installed when Code 11= Q1.
2
These Power Blocks are used on RPS and RDT units. RFS units use the following: 175A p/n 030372777 + Lug p/n 349938302;
310A p/n 030372783 + Lug p/n 349938302; 420A p/n 030372785 + Lug 349938302; 760A p/n 030372721 + Lug p/n 349938003.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 258
Section N- Main Control Box
Power Panel 1/07 & Later 4
Common Components, Continued
4
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
Power Panel- Power Blocks, Receptacle, Power Supply Board, Disconnect Switches
Sch.
Part
Part
Voltage
Sym. Description
Number 208V 230V460V575V
Power Blocks, continued
PB10 Power Block- Supply Fan
Code 15= F 030372776 1
1
1
1
PB20 Power Block- Return Fan
Code 15= F 030372776 1
1
1
1
Receptacles
REC1
Receptacle
0390036001 111
Power Supply Board
PWR Power Supply Board, 5V
Code 12= *D, *S 111049610 1
1
1
1
Disconnect Switches
DS1
Disconnect Switch- Main
Gas, Steam, HW, No Heat Code 04= A, S, W, Y
3499351251 111
Switch- 100A 1
Handle Kit
3499355211 111
Shaft
3499622041 111
Ground Lug
3499380011 111
3499351261 111
Switch- 150A 1
Handle Kit (with operating mechanism) 349935532 1
1
1
1
Shaft
3499622051 111
Ground Lug
3499380011 111
3499352261 111
Switch- 250A 1
Handle Kit (with operating mechanism) 349935532 1
1
1
1
Shaft
3499622051 111
Ground Lug
3499380021 111
Switch- 400A 1
3499353251 111
Handle Kit (with operating mechanism) 349935621 1
1
1
1
Shaft
3499622061 111
Ground Lug
3499380021 111
Switch- 600A 1, 2, 3
1934382051 111
Handle
3499611021 111
Operating Mechanism 3
1934550011 111
Shaft
3499613011 111
Shaft- Mod 3
3499622071 111
Ground Lug
3499380021 111
Switch- 800A 1, 3
1934382011 111
Handle
3499611021 111
Operating Mechanism 3
1934550011 111
Shaft
3499613011 111
Shaft- Mod 3
3499622421 111
Ground Lug
3499380031 111
Switch- 1000A 1, 3
1934382061 111
Handle
3499611021 111
Operating Mechanism 3
1934550011 111
Shaft
3499613011 111
Shaft- Mod 3
3499622421 111
Ground Lug
3499380031 111
Any of the listed Disconnects may be used, depending on unit options. Check installed part to verify, or contact Daikin Applied with
unit serial and/or GO number to ensure correct replacement is selected.
2
The 600A switch listed is used on units with one Disconnect or two Disconnects EH/balance of unit (Code 11= A2, B2). If unit has
two Disconnects where the second Disconnect controls the Fans (Code 11= C2) OR 3 Disconnects (Code 11= D2) then use Switch
p/n 193438002, Handle Kit p/n 193437901, Shaft p/n 349962233, and Ground Lug p/n 349938002.
3
Note that the original Disconnect is obsolete. Due to dimensional differences minor field modifications may be required for proper
installation.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 259
Section N- Main Control Box
Power Panel 1/07 & Later 4
Common Components, Continued
4
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
Power Panel- Disconnect Switches
Voltage
Sch.
Part
Part
Sym. Description
Number 208V230V460V575V
Disconnect Switches, continued
DS1
Disconnect Switch- Main
Electric Heat Code 04= E
Switch- 100A 1
3499351211111
Handle Kit
3499355211111
Shaft
3499622041111
Ground Lug
3499380011111
Load Lug
3499561011111
Cover- Load Lug
3499570031111
Switch- 150A 1
3499351221111
Handle Kit
3499355321111
Shaft
3499622051111
Ground Lug
3499380011111
Load Lug
3499562021111
Cover- Load Lug
3499570011111
3499352221111
Switch- 250A 1
Handle Kit
3499355321111
Shaft
3499622051111
Ground Lug
3499380011111
Load Lug
3499563021111
Cover- Load Lug
3499570021111
Switch- 400A 1
3499353251111
Handle Kit
3499356211111
Shaft
3499622061111
Ground Lug
3499380021111
Switch- 600A 1, 2, 3
1934382051 111
Handle
3499611021 111
Operating Mechanism 3
1934550011 111
Shaft
3499613011 111
Shaft- Mod 3
3499622071 111
Ground Lug
3499380021 111
Switch- 800A 1, 3
1934382011 111
Handle
3499611021 111
Operating Mechanism 3
1934550011 111
Shaft
3499613011 111
Shaft- Mod 3
3499622421 111
Ground Lug
3499380031 111
Switch- 1000A 1, 3
1934382061 111
Handle
3499611021 111
Operating Mechanism 3
1934550011 111
Shaft
3499613011 111
Shaft- Mod 3
3499622421 111
Ground Lug
3499380031 111
Any of the listed Disconnects may be used, depending on unit options. Check installed part to verify, or contact Daikin Applied with
unit serial and/or GO number to ensure correct replacement is selected.
2
The 600A switch listed is used on units with one Disconnect or two Disconnects EH/balance of unit (Code 11= A2, B2). If unit
has two Disconnects where the second Disconnect controls the Fans (Code 11= C2) OR 3 Disconnects (Code 11= D2) then use
Switch p/n 193438002, Handle Kit p/n 193437901, Shaft p/n 349962233, and Ground Lug p/n 349938002.
3
Note that the original Disconnect is obsolete. Due to dimensional differences minor field modifications may be required for proper
installation.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 260
Section N- Main Control Box
Power Panel 1/07 & Later 2
Common Components, Continued
2
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
Power Panel- Disconnect Switches (continued), Circuit Breakers
Sch.
Part
Part
Voltage
Sym. Description
Number 208V230V460V575V
Disconnect Switches, continued
DS2
Disconnect Switch- SAF/RAF
Code 11= C2, D2
Switch- 100A 1349935121 1 1 1 1
Handle Kit 349935521 1
1
1
1
Shaft 349962204 1 1 1 1
Ground Lug 349938001 1
1
1
1
Load Lug 349956101 1
1
1
1
Cover- Load Lug 349957003 1
1
1
1
Switch- 150A 1349935122 1 1 1 1
Handle Kit 349935532 1
1
1
1
Shaft 349962205 1 1 1 1
Ground Lug 349938001 1
1
1
1
Load Lug 349956202 1
1
1
1
Cover- Load Lug 349957001 1
1
1
1
Switch- 250A 1349935222 1 1 1 1
Handle Kit 349935532 1
1
1
1
Shaft 349962205 1 1 1 1
Ground Lug 349938001 1
1
1
1
Load Lug 349956302 1
1
1
1
Cover- Load Lug 349957002 1
1
1
1
Switch- 400A 1349935321 1 1 1 1
Handle Kit 349935621 1
1
1
1
Shaft 349962206 1 1 1 1
Ground Lug 349938002 1
1
1
1
Load Lug 349956401 3
3
3
3
Cover- Load Lug 349957004 1
1
1
1
Circuit Breakers
CB10 Circuit Breaker- Supply Fan
CB20 Circuit Breaker- Return Fan
Motor HP= 5, 7.5, 10
Motor HP= 5
Motor HP= 5, 7.5
Motor HP= 7.5
Motor HP= 10
Motor HP= 10
Motor HP= 15
Motor HP= 15
Motor HP= 15, 20
Motor HP= 20
Motor HP= 20
Motor HP= 20, 25
Motor HP= 25
Motor HP= 25
Motor HP= 25, 30
1
349939601
349939622 1
1
349939621
1
349939624 1
1
349939626 1
1
349939622
1
349939629 1
1
349939624
1
349939604
349939631 1
349939630
1
349939626
1
349939632 1
349939631
1
349939606
1
1
1
Any of the listed Disconnects may be used, depending on unit options. Check installed part to verify, or contact Daikin Applied with
unit serial and/or GO number to ensure correct replacement is selected.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 261
Section N- Main Control Box
Power Panel 1/07 & Later 9
Common Components, Continued
9
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
Power Panel- Circuit Breakers (continued), Plugs
Sch.
Part
Sym. Description
Circuit Breakers, Continued
CB10 Circuit Breaker- Supply Fan
CB20 Circuit Breaker- Return Fan
Motor HP= 30
Motor HP= 30
Motor HP= 30
Motor HP= 40
Motor HP= 40
Motor HP= 40
Motor HP= 50
Motor HP= 50
Motor HP= 60 Motor HP= 60
Motor HP= 75
2
3
4
5
6
7
8
Plugs 1
4 Pin Plug
6 Pin Plug
12 Pin Plug
3 Pin Cap Kit
6 Pin Cap Kit
9 Pin Cap Kit
15 Pin Cap Kit
Part
Voltage
Number 208V230V460V575V
349939701
1
349939633
1
349939628
1
349939703
1
1
349939630
1
349939608
349939631
1
349939610
349939632
1
349939611
349939701
1
349930201
349930403
349930405
349930501
349930503
349930504
349930506
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
varies
1
1
1
varies
varies
varies
varies
varies
varies
varies
All possible Plugs used are listed. Check actual unit to verify which Plug is required.
Used for PL1, PL, 2, PL3, PL4, PL5, PL6, PL22,PL23, PL24, PL37, PL38.
3
Used with Strain Relief (p/n 300041173) & 6 Pin Cap Kit (p/n 349930503). Used for PL20, PL21.
4
Used for PL11, PL12, PL25, PL26, PL27, PL28, PL29, PL30 (PL11 & 12 also use Strain Relief p/n 300041175 & Cap Kit p/n 349930505).
5
Used for PL16, PL17, PL31, PL32, PL33, PL34, PL39, PL40, PL41, PL42.
6
Used for PL9, PL10.
7
Used for PL18, PL19, PL35, PL36, PL43.
8
Used for PL7, PL8.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 262
Section N- Main Control Box
Power Panel 1/07 & Later 1
Supply MMP10 & M10 Fan Contactor & Return MMP20 & M20 Fan Contactor
Diagrams
1
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
3G
Lug
MMP
3
3E
Front Mtd.
Contact
3
3E
Link
3
MMP
Trip
Indicator
Alarm
3F
MMP
3B
1
Front
Mounted
Contact
Contactor
1
1
Contactor
Contactor
MMP10 & M10 Link Detail
MMP20 & M20 Link Detail
5, 7.5 HP Motors- All Voltages
10 HP Motor- 230/460/575V
15, 20 HP Motor- 460/575V
25, 30 HP Motors- 575V
MMP10 & M10 Link Detail
MMP20 & M20 Link Detail
10HP Motor- 208V
15HP Motor- 208/230V
20 HP Motors- 208/230V
25 HP Motors- 230/460V
30 HP Motors- 460V
40 HP Motors- 460/575V
50 HP Motors- 460/575V
60 HP Motors- 575V
MMP10 & M10 Link Detail
MMP20 & M20 Link Detail
25 HP Motors- 208V
30 HP Motors- 230V
60 HP Motors- 460V
NOTE: The diagrams show all possible parts. Not every
part shown applies to every unit size/voltage combination.
Lug
MMP
Trip Ind.
Interlock
3G
3G
3
3
MMP
3F
3F
Contactor
Lug
Trip Ind.
Interlock
1
1
Contactor
MMP10 & M10 Link Detail
MMP20 & M20 Link Detail
30 HP Motors- 208V
40 HP Motors- 208/230V
50 HP Motors- 230V
75 HP Motors- 460/575V
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” MMP10 & M10 Link Detail
50 HP Motors- 208V
60 HP Motors- 208/230V
Rev. AG 01/15
RPL 7000070 / Page 263
Section N- Main Control Box
Power Panel 1/07 & Later 1
Supply MMP10 & M10 Fan Contactor & Return MMP20 & M20 Fan Contactor
Components
1
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
5 HP Motor- Code 22 OR 32= JEY, JHY, JJY, JKY
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932123 1 1
Contactor- Supply (M10) OR Return (M20) Fan 349932121 1 1
3 MMP10, 20 MMP- Supply (MMP10) OR Return (MMP20) Fan 349934052 1 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934050 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934049 1
3B
Link 3499329221 111
3E
Aux. Contact- 1 NO or NC 349933821 1 1 1 1
7.5 HP Motor- Code 22 OR 32= KEY, KHY, KJY, KKY
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932321 1 1
Contactor- Supply (M10) OR Return (M20) Fan 349932122 1
Contactor- Supply (M10) OR Return (M20) Fan 349932121 1
3 MMP10, 20 MMP- Supply (MMP10) OR Return (MMP20) Fan 349934054 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934053 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934051 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934050 1
3B
Link 3499329221 111
3E
Aux. Contact- 1 NO or NC 349933821 1 1 1 1
10 HP Motor- Code 22 OR 32= LEY, LHY, LJY, LKY
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932521 1
Contactor- Supply (M10) OR Return (M20) Fan 349932322 1
Contactor- Supply (M10) OR Return (M20) Fan 349932123 1
Contactor- Supply (M10) OR Return (M20) Fan 349932122 1
3 MMP10, 20 MMP- Supply (MMP10) OR Return (MMP20) Fan 349934147 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934055 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934052 1
MMP- Supply (MMP10) OR Return (MMP20) Fan 349934051 1
3B
Link 349932922 111
3E
Aux. Contact- 1 NO or NC 349933821 1 1 1 1
RPL 7000070 / Page 264
Section N- Main Control Box
Power Panel 1/07 & Later 1
Supply MMP10 & M10 Fan Contactor & Return MMP20 & M20 Fan Contactor
Components, Continued
1
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
15 HP Motor- Code 22 OR 32= MEY, MHY, MJY, MKY
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932522 1 1
Contactor- Supply (M10) OR Return (M20) Fan 349932321 1
Contactor- Supply (M10) OR Return (M20) Fan 349932123 1
3 MMP10, 20 MMP- Supply (M10) OR Return (M20) Fan 349934148 1 1
MMP- Supply (M10) OR Return (M20) Fan 349934053 1
MMP- Supply (M10) OR Return (M20) Fan 349934052 1
3B
Link34993292211
3E
Aux. Contact- 1 NO or NC 349933821 1 1 1 1
20 HP Motor- Code 22 OR 32= NEY, NHY, NJY, NKY
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932523 1 1
Contactor- Supply (M10) OR Return (M20) Fan 349932322 1
Contactor- Supply (M10) OR Return (M20) Fan 349932321 1
3 MMP10, 20 MMP- Supply (M10) OR Return (M20) Fan 349934149 1 1
MMP- Supply (M10) OR Return (M20) Fan 349934055 1
MMP- Supply (M10) OR Return (M20) Fan 349934053 1
3B
Link34993292211
3E
Aux. Contact- 1 NO or NC 349933821 1 1 1 1
25 HP Motor- Code 22 OR 32= PEY, PHY, PJY, PKY
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932621 1 1
Contactor- Supply (M10) OR Return (M20) Fan 349932521 1
Contactor- Supply (M10) OR Return (M20) Fan 349932322 1
3 MMP10, 20 MMP- Supply (M10) OR Return (M20) Fan 349938606 1
MMP- Supply (M10) OR Return (M20) Fan 349934149 1
MMP- Supply (M10) OR Return (M20) Fan 349934147 1
MMP- Supply (M10) OR Return (M20) Fan 349934054 1
3B
Link3499329221
3E
Aux. Contact- 1 NO OR NC 349933821 1 1 1
3F
Trip Indicator Interlock 349938701 1
3G
Lug (3 per kit) 349938801 2
RPL 7000070 / Page 265
Section N- Main Control Box
Power Panel 1/07 & Later 3
Supply MMP10 & M10 Fan Contactor & Return MMP20 & M20 Fan Contactor
Components
3
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
30 HP Motor- Code 22 OR 32= QEY, QHY, QJY, QKY
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932721 1
Contactor- Supply (M10) OR Return (M20) Fan 349932621 1
Contactor- Supply (M10) OR Return (M20) Fan 349932521 1
Contactor- Supply (M10) OR Return (M20) Fan 349932322 1
3 MMP10, 20 MMP- Supply (M10) OR Return (M20) Fan 349938606 1 1
MMP- Supply (M10) OR Return (M20) Fan 349934147 1
MMP- Supply (M10) OR Return (M20) Fan 349934055 1
3B
Link3499329221
3E
Aux. Contact- 1 NO OR NC 349933821 1 1
3F
Trip Indicator Interlock 349938701 1 1
3G
Lug (3 per kit) 349938801 2 2
40 HP Motor- Code 22 OR 32= REY, RHY, RJY, RKY
1
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932722 1
Contactor- Supply (M10) OR Return (M20) Fan 349932721 1
Contactor- Supply (M10) OR Return (M20) Fan 349932522 1 1
3 MMP10, 20 MMP- Supply (M10) OR Return (M20) Fan 349938607 1 1
MMP- Supply (M10) OR Return (M20) Fan 349934148 1 1
3E
Aux. Contact- 1 NO OR NC 349933821 1 1
3F
Trip Indicator Interlock 349938701 1 1
3G
Lug (3 per kit) 349938801 1111
Also requires 3 ring terminals.
50 HP Motor- Code 22 OR 32= SEY, SHY, SJY, SKY
2
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932702 1
Contactor- Supply (M10) OR Return (M20) Fan 349932722 1
Contactor- Supply (M10) OR Return (M20) Fan 349932621 1
Contactor- Supply (M10) OR Return (M20) Fan 349932523 1
3 MMP10, 20 MMP- Supply (M10) OR Return (M20) Fan 349938607 1 1
MMP- Supply (M10) OR Return (M20) Fan 349934149 1 1
3E
Aux. Contact- 1 NO OR NC 349933821 1 1
3F
Trip Indicator Interlock 349938701 1 1
3G
Lug (3 per kit) 349938801 1212
Also requires 3 ring terminals.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 266
Section N- Main Control Box
Power Panel 1/07 & Later 2
Supply MMP10 & M10 Fan Contactor & Return MMP20 & M20 Fan Contactor
Components
2
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
60 HP Motor- Code 22 OR 32= TEY, THY, TJY, TKY
1
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1 M10, 20 Contactor- Supply (M10) OR Return (M20) Fan 349932702 1 1
Contactor- Supply (M10) OR Return (M20) Fan 349932621 1 1
3 MMP10, 20 MMP- Supply (M10) OR Return (M20) Fan 349938608 1 1
MMP- Supply (M10) OR Return (M20) Fan 349938606 1
MMP- Supply (M10) OR Return (M20) Fan 349934149 1
3E
Aux. Contact- 1 NO OR NC 349933821 1
3F
Trip Indicator Interlock 349938701 1 1 1
3G
Lug (3 per kit) 349938802 1111
Lug (3 per kit) 349938801 2
Also requires 3 ring terminals.
75 HP Motor- Code 32= UEY, UHY, UJY, UKY
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
575V
460V
230V
208V
Voltage
Ref. Sch. Part Part
No. Sym. Description Number
1
M10
Contactor- Supply Fan 349932721 1 1
3
MMP10 MMP- Supply Fan 349938606 1 1
3F
Trip Indicator Interlock 349938701 1 1
3G
Lug 349938801 2 2
RPL 7000070 / Page 267
Section N- Main Control Box
Power Panel 1/07 & Later 3
Unit Size 080: Compressor MMP1- 6 and Contactor M1- 6
3
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
MMP
Front Mounted
Contact
3
3E
Contactor
3
Front Mounted
Contact
1
MMP
3E
Link
3B
1
Contactor
MMP & Contactor Link Detail
MMP & Contactor Link Detail
208/230V
460/575V
460V
575V
230V
208V
080
349934148 616
349934149 61
349934054 6
349934052
349934053
349932922 6
349933821 6 6 6
62
62
6
6
Ref Sch Part
Part
No Sym Description
Number
Compressor Contactors & Parts
1 M1- 6 Contactor- Compressor
349932523 6 6
Contactor- Compressor
349932322
6
6
3 MMP1- 6
3B
3E
Compressor MMP’s & Parts
Manual Motor Protector- Compr.
Manual Motor Protector- Compr.
Manual Motor Protector- Compr.
Manual Motor Protector- Compr.
Manual Motor Protector- Compr.
Link
Front Mounted Contact- 1NO OR 1 NC
When the Compressor changed in 7/08, the MMP for the 208V changed. -48 is used for the scroll Compressors used
until 7/08, -49 for 7/08 & Later. If an original Specter Compressor is replaced with a new Summit Compressor, the
MMP should be replaced as well.
2
When the Compressor changed in 7/08, the MMP for the 575V changed. -52 is used for the scroll Compressors used
until 7/08, -53 for 7/08 & Later. If an original Specter Compressor is replaced with a new Summit Compressor, the
MMP should be replaced as well.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 268
Section N- Main Control Box
Power Panel 1/07 & Later 3
Unit Size 090: Compressor MMP1- 6 and Contactor M1- 6
3
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
MMP
3
MMP
Front Mounted
Contact
Contactor
3E
Front
Mounted
Contact
3E
Contactor
1
3
1
MMP1,3,5 & M1,3,5 Contactor Link Detail
460/575V
MMP1,3,5 & M1,3,5 Contactor Link Detail
MMP2,4,6 & M2,4,6 Contactor Link Detail
208/230V
Front Mounted
Contact
4
MMP
4E
Link
4B
2 Contactor
MMP2,4,6 & M2,4,6 Contactor Link Detail
460/575V
575V
460V
230V
208V
090
Ref
Sch
Part
Part
No Sym
Description
Number
Compressor Contactors & Parts
1 M1, 3, 5 Contactor- Compressor
349932521 3 3
Contactor- Compressor
349932621 3 3
2 M2, 4, 6 Contactor- Compressor
349932523 3
Contactor- Compressor
349932322 3 3
Compressor MMP’s & Parts
3 MMP1, 3, 5 Manual Motor Protector- Compressor
349934149 3 3
Manual Motor Protector- Compressor
349934055 3
Manual Motor Protector- Compressor
349934054 3
3E
Front Mounted Contact- 1NO OR 1 NC
349933821 3 3 3
4 MMP2, 4, 6 Manual Motor Protector- Compressor
349934148 313
Manual Motor Protector- Compressor
349934149 31
Manual Motor Protector- Compressor
349934054 3
Manual Motor Protector- Compressor
349934052 32
Manual Motor Protector- Compressor
349934053 32
4B
Link
349932922 3 3
4E
Front Mounted Contact- 1NO
349933821 3 3 3 3
When the Compressor changed in 7/08, the MMP for the 208V changed. -48 is used for the Scroll Compressors used
until 7/08, -49 for 7/08 & Later. If an original Specter Compressor is replaced with a new Summit Compressor, the MMP
should be replaced as well.
2
When the Compressor changed in 7/08, the MMP for the 575V changed. -52 is used for the Scroll Compressors used
until 7/08, -53 for 7/08 & Later. If an original Specter Compressor is replaced with a new Summit Compressor, the MMP
should be replaced as well.
1
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 269
Section N- Main Control Box
Power Panel 1/07 & Later 1
Unit Size 105: Compressor MMP1- 6 and Contactor M1- 6
1
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
MMP
MMP
3
3E
Front
Mounted
Contact
Front
Mounted
Contact
3
3E
Contactor
1
MMP & Contactor Link Detail
208/230V
Contactor
1
MMP & Contactor Link Detail
460V, 575V
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Part
Number
575V
Part
Description
Compressor Contactors & Parts
Contactor- Compressor
Contactor- Compressor
Compressor MMP’s & Parts
Manual Motor Protector- Compr.
Manual Motor Protector- Compr.
Manual Motor Protector- Compr.
Front Mounted Contact- 1NO
460V
Ref Sch
No Sym
1 M1- 6
3 MMP1- 6
3E
208/230V
105
349932621 6
349932521 6 6
349934149 6
349934055 6
349934054 6
349933821 6 6 6
Rev. AG 01/15
RPL 7000070 / Page 270
Section N- Main Control Box
Power Panel 1/07 & Later 2
Unit Size 115: Compressor MMP1- 8 and Contactor M1- 8
2
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
MMP
3
3E
Front
Mtd.
Contact
3
Front
Mtd.
Contact
Contactor
1
3E
Link
3B
1
Contactor
MMP & Contactor Link Detail
460V PW
MMP & Contactor Link Detail
208/230V, 460V, 575V AL
MMP
Front
Mtd.
Contact
MMP
3
3E
Contactor
1
MMP & Contactor Link Detail
575V PW
575 PW
575V AL
460V AL
Part
Number
115
460V PW
208/230V
Ref Sch Part
No Sym Description
Comp. Contactors & Parts
1 M1- 81 Contactor- Compressor
Contactor- Compressor
Contactor- Compressor
Comp. MMP’s & Parts
3 MMP1- 81 Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
3B
Link
3E
Aux. Contact- 1 NO OR NC
349932523844
349932322 8
3799325218
349934149 8 4
349934147 4
349934053 8
349934055 8
349932922 8
349933821 8 4 8 4 8
NOTE: PW= Part Winding Start (Code 10= PW); AL= Across the Line Start (Code 10= AL).
1
MMP1- 4/M1- 4 apply to all sizes, all voltages and starting options.
MMP5- 8/M5- 8 apply to 208/230V and 460V, 575V Part Winding units only.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 271
Section N- Main Control Box
Power Panel 1/07 & Later 2
Unit Size 125: Compressor MMP1- 8 and Contactor M1- 8
Across The Line Start Compressors (Code 10= AL)
2
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
MMP
3
3E
1
Front
Mtd.
Contact
Contactor
3 MMP1- 8 1
MMP1, 2 1
MMP3, 4 1
3E
1
Comp. MMP’s & Parts
Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
Front Mounted Contact- 1NO
575V
460V
208/230V
125
Ref
Sch
Part
Part
No Sym Description
Number
Comp. Contactors & Parts
1
M1- 8 1 Contactor- Compressor
349932523 8 4 4
349934149 8 4
349934147 2
349934148 2
349933821 8 4 4
MMP1- 4/M1- 4 apply to all voltages.
MMP5- 8/M5- 8 apply to 208/230V units only.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 272
Section N- Main Control Box
Power Panel 1/07 & Later 1
Unit Size 125: Compressor MMP1- 8 and Contactor M1- 8
Part Winding Start Compressors (Code 10= PW)
1
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
MMP
4
or
3
3E
or
4E
Contactor
1
or
MMP
Front
Mtd.
Contact
2
4E
or
Front
Mtd.
Contact
Link
3B
3
3E
or
4B
4E
MMP
Contactor
2
Contactor
1
MMP & Contactor Link Detail
208/230V
4
or
Front
Mtd.
Contact
4
or
2
MMP & Contactor Link Detail
460V, 575V MMP 1, 2, 5, 6
MMP & Contactor Link Detail
575V MMP 3, 4, 7, 8
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
575V
460V
208/230V
125
Ref
Sch
Part
Part
No
Sym
Description
Number
Compressor Contactors & Parts
1 M1, 2, 5, 6 Contactor- Compressor
349932503 4
Contactor- Compressor
349932322 4
Contactor- Compressor
3499323214
2 M3, 4, 7, 8 Contactor- Compressor
349932601 4
Contactor- Compressor
349932322 4
Contactor- Compressor
3499325214
Compressor MMP’s & Parts
3 MMP1, 2, 5, 6 Manual Motor Protector- Compressor
349934109 4
Manual Motor Protector- Compressor
349934055 4
Manual Motor Protector- Compressor
349934053 4
3B
Link
349932922 4 4
3E
Front Mounted Contact- 1NO
349933801 4
Front Mounted Contact- 1NO or 1NC
349933821 4 4
4 MMP3, 4, 7, 8 Manual Motor Protector- Compressor
349934109 4
Manual Motor Protector- Compressor
349934055 4
Manual Motor Protector- Compressor
349934054 4
4B
Link
349932922 4
4E
Front Mounted Contact- 1NO
349933801 4
Front Mounted Contact- 1NO or 1NC
349933821 4 4
RPL 7000070 / Page 273
Section N- Main Control Box
Power Panel 1/07 & Later 2
Unit Size 135: Compressor MMP1- 8 and Contactor M1- 8
2
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
MMP
3
3E
Front
Mtd.
Contact
MMP
3
Front Mtd.
Contact
Contactor
3E
Link
1
3B
1
MMP & Contactor Link
Detail
460 PW
MMP & Contactor Link Detail
Unit Sizes 208/230V, 460V AL & 575 AL
MMP
Front Mtd.
Contact
Contactor
Contactor
3
3E
1
MMP & Contactor Link
Detail
575 PW
575 PW
575V AL
460V AL
Part
Number
460V PW
135
208/230V
Ref Sch Part
No Sym Description
Comp. Contactors & Parts
1 M1- 81 Contactor- Compressor
Contactor- Compressor
Contactor- Compressor
Comp. MMP’s & Parts
3 MMP1- 81 Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
Manual Motor Protector- Compressor
3B
Link
3E
Front Mounted Contact- 1NO or 1NC
349932523 8 44
349932322 8
349932521 8
349934149 8 4
349934055 8
3499341484
349934054 8
349932922 8
349933821 8 4 8 4 8
NOTE: PW= Part Winding Start (Code 10= PW); AL= Across the Line Start (Code 10= AL).
1
MMP1- 4/M1- 4 apply to all sizes, all voltages and starting options.
MMP5- 8/M5- 8 apply to 208/230V and 460V, 575V Part Winding units only.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 274
Section N- Main Control Box
Power Panel 1/07 & Later 2
Condenser Fan MMP11, 12, 13, 21, 22, 23 and Contactors M11 - 24
FanTrol Units (Code 47= 1)
2
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
MMP13, 23 used on sizes 080, 090, 105, 115
MMP11, 21 used on sizes 080, 090, 105, 115, 125, 135
MMP12, 22 used on sizes 125, 135
Link
8
8B
Bus Bar
8C
Contactor
7
1
575V
460V
208/230V
575V
460V
208/230V
575V
460V
208/230V
080- 105
115
125, 135
Ref
Schematic
Part
Part
No
Symbol
Description
Number
Fan Contactors
7 M11,12,13,14
21, 22, 23, 24 Contactor- Condenser Fan
349932121888888888
Fan MMP’s & Parts
8
MMP11, 21
Manual Motor Protector
349934049 2 2 2 2
Manual Motor Protector
3499340502222
Manual Motor Protector
3499340512
MMP13, 23
Manual Motor Protector
349934049 2121
Manual Motor Protector
349934050 212
2
Manual Motor Protector
349934051 2
MMP12, 22 Manual Motor Protector
3499340502
2
Manual Motor Protector
3499340512
8B
Link- MMP
349932922444444444
8C
Bus Bar
349934311444444444
The part numbers for unit size 105 MMP23 are— 208/230V p/n 349934051; 460/575V p/n 349934050.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 275
Section N- Main Control Box
Power Panel 1/07 & Later 2
Condenser Fan MMP12, 14, 22, 24 and Contactors M11 - 24
SpeedTrol Units (Code 47= 2) 3
2
3
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
For Speedtrol units with Quiet Fans (Code 47= 4) contact Daikin Applied with Unit GO/Serial Number.
208/230V
9A
Fuse
MMP12, 22 used on sizes
080,090,105,115,135
MMP14, 24 used on sizes
115,125,135
MMP
Fuse
Guard
8
9B
9
7
Link
Bus Bar
8B
8C
Contactor
Contactor
460/575V
Fuse
7
Fuse
Block
Fuse
Guard
9A
9B
9
MMP & Contactors Detail
(applies to all sizes)
7
Fuse
Block
Contactor
Speedtrol Fusing Detail
F11, F12 & M12,M22 (with Speedtrol)
1
575V
460V
208/230V
575V
460V
208/230V
575V
460V
208/230V
080- 105
115
125, 135
Ref
Schematic
Part
Part
No
Symbol
Description
Number
Fan Contactors
7 M11,12,13,14
21, 22, 23, 24 Contactor- Condenser Fan
349932121888888888
Fan MMP’s & Parts
8
MMP12, 22
Manual Motor Protector
349934049 2 2
Manual Motor Protector
349934050 21 21222
Manual Motor Protector
349934051 212
MMP14, 24
Manual Motor Protector
349934049 2 2 2 2
Manual Motor Protector
34993405022
8B
Link- MMP
349932922222444444
8C
Bus Bar (MMP12, 22 only)
349934311222222222
9
F11
Fuse Block
023780222111111111
F12
Fuse Block
023780222111
9A
F11
Fuse
349937133222222
F11
Fuse
349937129222
F12
Fuse
349937129222
9B
Fuse Puller
349938227422422422
The part numbers for MMP22, unit size 105 are— 208/230V p/n 349934050; 460/575V p/n 349934049.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 276
Section N- Main Control Box
Power Panel 1/07 & Later 4
Condenser Fan MMP11, 12, 13, 21, 22, 23 and Contactors M11- 24
Quiet Fan Fantrol Units (Code 47= 3)
4
Code 08= D, F. For units built 10/06 thru 12/06 contact Daikin Applied to ensure that the correct part(s) are identified.
MMP13, 23 used on sizes 090, 105, 115
MMP11, 21 used on sizes 090, 105, 115, 125, 135
MMP12, 22 used on sizes 125, 135
Link
8
8B
Bus Bar
8C
7
Contactor
575V
460V
230V
208V
575V
460V
230V
208V
575V
460V
230V
208V
575V
460V
230V
208V
080, 090
105
115
125, 135
Ref Schematic Part
Part
No Symbol Description
Number
Fan Contactors
7 M11,12,13,14
21, 22, 23, 24Contactor- Cond. Fan 349932121888 888 8888888888
Fan MMP’s & Parts
8 MMP11, 21 Manual Motor Protector 349934049 2 2 2 2 2 2
Manual Motor Protector34993405022 22 22 22
Manual Motor Protector
3499340512
Manual Motor Protector
3499340522
MMP13, 23 Manual Motor Protector 349934049 2 2
Manual Motor Protector 349934050 2 2 2323 22
Manual Motor Protector 349934051 21222
Manual Motor Protector
3499340522
MMP12, 22
Manual Motor Protector
3499340502
2
Manual Motor Protector
3499340512
Manual Motor Protector
3499340522
8B
Link- MMP
349932922444 444 4444444444
8C
Bus Bar
349934311444 444 4444444444
208V unit size 105 MMP23 is p/n 349934052.
230V unit size 105 MMP23 is p/n 349934051.
3
460/575V unit size 105 MMP23 is p/n 34993450.
1
2
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 277
Refrigeration Tubing
Notes
Main Codes that pertain: 45, 46
Code 45, Compressor mounting, pertains to the Suction and Discharge Tubing located in the Condenser Section. If the unit has
Spring Isolators, then there are also Vibration Eliminators on the Suction and Discharge Lines. The Suction and Discharge Lines
only pertain to RPS and RCS units. RFS units do not have an integrated Condenser Section and are designed to hook up to a
separate Condensing Unit (such as an RCS unit.)
Code 46, Hot Gas Bypass, pertains to the Liquid Line tubing on RPS and RFS units. The drawings below show the Hot Gas Bypass
option installed. RCS units come from the factory with NO Liquid Line components installed. HGBP can be field installed on RPS
and RCS units, however, it is important to note that additional piping required for field installed HGBP is ALWAYS field supplied.
Schematic— Discus Compressor (Circuit # 1 OR Circuit #2):
Discharge Line
Condenser
Coil
Hot Gas
Bypass
Solenoid
Compressor
Suction Line
Hot Gas
Bypass
Valve
id
ss
no
la
Evaporator
Coil
G
ht
Di
st
rib
ut
or
Ex
Va pa
lv ns
e i
S
ne
g
Si
e
ol
id
Li
Manual
Shutoff
valve
Filter
Drier
qu
Li
on
Schematic— Scroll Compressor (Circuit # 1 OR Circuit #2):
Discharge Line
Condenser
Coil
Hot Gas
Bypass
Solenoid
Suction Line
Compressor
id
ss
no
la
Evaporator
Coil
tG
gh
Di
st
rib
ut
or
Ex
Va pa
lv ns
e i
Si
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” ne
id
Li
e
ol
S
Filter
Drier
Manual
Shutoff
valve
qu
on
Li
Rev. AG 01/15
RPL 7000070 / Page 278
Refrigeration Tubing
Components
Units with Semi-Hermetic Discus Compressors (Code 44= H, K)
Ref. Part
Part Unit Size 1
No. Description Number 080090105115125135
Condenser Section
N/S Valve- Shut Off
049266501111111
Cap- Shut Off Valve 032943500 1 1 1 1 1 1
Discharge Line
N/S
Eliminator- Vibration 4020001710 2
Eliminator- Vibration 4
0200017111 1 222
N/S Stem- Valve
034915300222222
N/S Core- Valve
026541100222222
N/S Cap- Valve
032943500111111
N/S
Valve- Pressure Relief, 450 PSIG 039441300 1 1 1 1 1 1
N/S Muffler047664304 1 1
Muffler
047664305 1 111
N/S
N/S
N/S
N/S
N/S
N/S
N/S
Liquid Line
Shell- Replaceable Filter Drier 3
019190500111111
Core, Replaceable- Filter Drier 3
001360800222222
Filter Drier- Sealed Core 021057426 1 1 1 1 1 1
Solenoid Valve- Liquid Line 047931305 1 1
Solenoid Valve- Liquid Line 025327600
1 1 1 1
Body- Sight Glass
Until 1/00 022431100 1 1 1 1 1 1
Cap- Sight Glass
Until 1/00 022427700 1 1 1 1 1 1
Sight Glass Assy
1/00 & Later 015997806 1 1 1 1 1 1
N/S
Expansion Valve- Small Face Area Coils (C03= S)
TXV- 40 Ton 024029503 1
TXV- 55 Ton 024029504
1
TXV- 30 Ton 024029605
N/S
Expansion Valve- Large Face Area Coils (C03= L)
TXV- 20 Ton 024029601 2 2
TXV- 30 Ton 024029605
2 2 2
TXV- 40 Ton
024029501
2
N/S
Suction Line
Eliminator- Vibration 4020001712 2
Eliminator- Vibration 4
0200017131 1 222
Hot Gas Bypass Valves 2
N/S Solenoid
N/S
Pressure Regulator- Set 58 PSIG
N/S
Solenoid Valve- HGBP
2
2 N/AN/A
Until 5/02
047931304111111
Until 5/02 024684106 1 1 1 1 1 1
5/02 & Later 111011001 1 1 1 1 1 1
N/A= Not Applicable.
N/S= Not Shown on Diagram.
1
Quantity is PER circuit. Each unit has two (2) circuits. The components listed are the same for either circuit.
2
Code 46= 1, 2, 4, 5. If Code 46= 1, 4 then there is Hot Gas Bypass on Circuit #1 only.
3
Code 46= 3, 4, 5.
4
Only used when Compressors are spring mounted (Code 45= 2).
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 279
Refrigeration Tubing
Components
Units with Scroll Compressors (Code 44= Z, T)
Ref.
Part
PartUnit Size 1
No.
Description Number 080 090105
Condenser Section
N/S
Valve- Shut Off 049266502 1 1 1
Cap- Shut Off Valve 032943500 1 1 1
Discharge Tubing
Valve- Angle Shut Off
Valve- Angle Shut Off
Stem- Valve
Core- Valve
Cap- Valve
N/S
N/S
N/S
N/S
N/S
N/S
N/S
N/S
N/S
N/S
Liquid Line
Sight Glass Assy 015997806 1 1 1
Shell- Replaceable Filter Drier 3019190500 1 1 1
Core, Replaceable- Filter Drier 3001360800 2 2 2
Filter Drier- Sealed Core 021057426 1 1 1
Solenoid Valve- Liquid Line 047931305 1 1
Solenoid Valve- Liquid Line 025327600 1
N/S
Expansion Valve- Small Face Area Coils (Code 03= S)
TXV- 20 Ton 024029601 2
TXV- 30 Ton 024029605
TXV- 55 Ton 024029504
1
N/S
Expansion Valve- Large Face Area Coils (Code 03= L)
TXV- 20 Ton 024029601 2 2
TXV- 30 Ton 024029605
098805301 1
098805302
034915300 2
026541100 2
032943500 1
Hot Gas Bypass 2
N/S
Solenoid Valve- Hot Gas Bypass 111011001
1
1
2
2
1
1
1
2
2
1
2
2
1
N/S= Not Shown on Diagram.
1
Quantity is PER circuit. Each unit has two (2) circuits. The components listed are the same for either circuit.
2
Code 46= 1, 2, 4, 5. If Code 46= 1, 4 then there is Hot Gas Bypass on Circuit #1 only.
3
Code 46= 3, 4, 5.
RoofPak Singlezone; RCS,RDT,RFS,RPS 080-135 “C” Rev. AG 01/15
RPL 7000070 / Page 280