INNHOLD


Add to my manuals
35 Pages

advertisement

INNHOLD | Manualzz

INNHOLD

1

INNHOLD

KORTFATTET BRUKSANVISNING ......................................................................................................2

GENERELL BESKRIVELSE.................................................................................................................... 3

Innmating av data, generelt ..........................................................................................................4

Lysdiode.......................................................................................................................................4

Sikkerhetstermostater ...................................................................................................................5

Alarm ...........................................................................................................................................5

Strømbrudd ..................................................................................................................................5

Hvilestilling..................................................................................................................................6

Skriver..........................................................................................................................................6

Vedlikehold..................................................................................................................................6

Feilretting .....................................................................................................................................6

BILDEBESKRIVELSE..............................................................................................................................7

Bilde nr 1 - Hovedbilde...............................................................................................................7

Bilde nr 2 - Børverdier .................................................................................................................8

Bilde nr 3 - Datalogging...............................................................................................................8

Bilde nr 4 - Tid .............................................................................................................................9

Bilde nr 5-8 - Programverk ..........................................................................................................9

Bilde nr 9 - Stige/Falltid...............................................................................................................11

Bilde nr 10 - Opsjoner og Kalibrering ........................................................................................ 11

Bilde nr 11 - Avriming.................................................................................................................12

KORTFATTET BRUKSANVISNING

2

KORTFATTET BRUKSANVISNING

Dekker kontinuerlig drift ved en temperatur. Ønskes en eller flere tilleggsfunksjoner, finnes dette på de påfølgende sider. Eksemplene er på norsk, se avsnitt om språkvalg, bilde 10.

1 Slå på hovedbryter. Normalt kommer følgende bilde på displayet:

Tilfeldige verdier

Hvis det ikke kommer noe tekst i displayet og lampen på « trykke en gang på «

»

.

» lyser, får man fram bildet ved å

Meldingene «BATTERY ERROR ENTER NEW DATA!

» eller «STRØMBRUDD MAT INN

TID

» kan komme hvis skapet har vært strømløst mer enn 48 timer. Disse meldingene har ingen betydning ved kontinuerlig drift og fjernes med «

»

.

Andre tegn eller meldinger kan også komme opp, se avsnitt om bildebeskrivelse, bilde 1.

2 Kontroller at tidsfunksjonen ikke er på. Lampen på « trykk på «

»

.

» skal ikke lyse, slås eventuelt av med et

3 Kontroller børverdien på 2. linje.

Hvis ønsket verdi allerede vises, betyr det at skapet skal kjøres som før og man kan hoppe over punktene 4-6.

Hvis ny børverdi ønskes, trykkes « », og følgende bilde kommer opp:

Tilfeldige verdier

Ved kontinuerlig drift er det alltid T1 som er aktiv og dette markeres med blinkende kolon.

Flytt markøren til første siffer med «

»

. Ønsket børverdi kan nå mates inn med knappene 0-9.

Markøren flytter seg automatisk til neste siffer.

Gå tilbake til hovedbildet med « » .

En pil på første linje viser at temperaturen er på vei opp eller ned mot børverdien.

4 Skru « » til 0 og « » til 10.

5 La temperaturen stabilisere på børverdi

6 Skru « » sakte nedover til lampen tenner. Skru så forsiktig opp igjen til lampen slukker.

På samme måte skrus « » sakte oppover til lampen tenner. Skru så forsiktig tilbake til den slukker igjen.

Hold øye med disse lampene den første tiden etter innstillingen. Hvis de lyser av og til, betyr det at de et innstilt litt for nær børverdien. Dette vil i så fall forstyrre temperaturreguleringen.

7 Skapet er nå ferdig innstilt for kontinuerlig drift ved en temperatur. Man kan når som helst under driften avlese max, min og gjennomsnittsverdiene. Se beskrivelse av bilde nr 3 - datalogging.

GENERELL BESKRIVELSE

GENERELL BESKRIVELSE

3

Skapet er konstruert med tanke på å oppnå jevnest mulig temperatur i hele nytterommet samt lavest mulig uttørring.

Dette er oppnådd ved at en kjølemaskin går kontinuerlig når det er behov for det. Et varmeelement som styres av en mikroprosessor-basert regulator holder temperaturen på riktig verdi.

Varmeelementet ligger inne i kjølesystemets «radiator » . Dette, sammen med en høy lufthastighet fører til en optimal overflatetemperatur på «radiatoren » med tanke på kondensering og eventuell ising.

Luften føres i kanaler rundt nytterommet, slik at luften i nytterommet står tilnærmet stille.

Regulatoren styrer også kjølemaskinen. Den starter ikke ved en fast temperaturgrense, men etter behov. I praksis betyr det at maskinen stopper ved arbeidstemperaturer høyere enn ca 10 °C over værelsetemperatur.

Maskinen går alltid når temperaturen endres mot en lavere verdi, og den kan også styres manuelt.

Ved svært lave temperaturer, er det fare for ising på «radiatoren

»

.

Det er derfor lagt inn en avrimingssyklus ved de laveste temperaturene.

Regulatoren har et LCD-display som normalt viser børverdi og virkelig temperatur i skapet.

I tillegg kan det komme en rekke meldinger, og man kan få fram en rekke «bilder » for innmating av data. Et oppladbart og vedlikeholdsfritt batteri holder alle data i minnet under stømbrudd.

Skapet er også utstyrt med elektroniske sikkerhetstermostater som sikrer prøvene i skapet mot

ødeleggende over- eller undertemperatur om regulatoren skulle svikte.

Man kan også velge mellom en rekke spesialfunksjoner som programmert stige/falltid, programverk, datalogging, språkvalg, manuell styring av kjølemaskin og digital kalibrering.

GENERELL BESKRIVELSE

4

Dataloggingen starter etter den innledende stabiliseringen. Ved forstyrrelser, f.eks. når døren

åpnes overskrides.

vil alarmgrensen

I dette eksempelet følger temperaturen 4 forskjellige sykluser. Rampefunksjonen er i bruk.

I

NNMATING AV DATA

,

GENERELT

Når markøren står på kolon, vil ikke noen data kunne endres. Man flytter markøren med til den ligger under det sifferet man ønsker å endre. Deretter mates så det nye tallet inn.

Markøren hopper automatisk fram til neste siffer. Hvis man ikke ønsker å endre det, kan man bare gå videre til neste siffer.

Skulle man komme til å gå forbi det sifferet man skulle endre, er det bare å fortsette hele runden med markøren til den kommer tilbake til det aktuelle sifferet. Det samme gjelder om man har matet inn feil verdi.

Det er satt grenser på mange av siffrene. Hvis man for eksempel forsøker å mate inn en ukedag høyere enn 7, vil «FEIL VERDI » vises en liten stund. Deretter kommer bildet tilbake med den opprinnelige verdien.

De nye verdiene lagres ikke i mikroprosessoren før det aktuelle bildet forlates. Dette skjer ved å trykke på «

» eller «

»

.

Skulle man glemme det, vil det likevel skje etter 30 sek når hovedbildet automatisk kommer opp.

Det er også mulig å nullstille alle data i minnet, se beskrivelse av bilde nr 10.

L

YSDIODE

Like under tekstvinduet finnes en lysdiode. Denne blinker når temperaturen ligger på børverdien eller like i nærheten.

Det settes spenning på varmeelemntet når det lyser.

S

IKKERHETSTERMOSTATER

Skapet er forsynt med sikkerhetstermostater for over- og undertemperatur for å sikre skapets innhold mot ødeleggende temperaturer om noe i regulatoren skulle svikte.

GENERELL BESKRIVELSE

5

Det er derfor viktig at disse blir innstilt riktig.Ved kjøring uten programverk, innstilles sikkerhetstermostatene som beskrevet i avsnitt «Kortfattet bruksanvisning

»

.

Ved kjøring med programverk, må sikkerhetstermostatene innstilles hver for seg ved den øvre og nedre børverdien i programmet.

Hvis man under normal drift skulle se at noen av lysene ved sikkerhetstermostatene lyser eller blinker, betyr det enten at grensen er satt for nær ønsket temperatur eller at det er oppstått en feil i regulatoren.

« » stopper kjølemaskinen, mens varmeelementet utkobles av « » .

A

LARM

Hvis temperaturen ved en feil fjerner seg for mye fra børverdien, vil «HØY

» eller «LAV

» blinke i tekstvinduet sammen med «TEMP

»

. Dette indikerer om temperaturen er for høy eller lav. Samtidig begynner lyset ved «

»

å blinke.

Varer alarmtilstanden mer en 1-2 minutter, får man også et akustisk signal.

Etter en temperaturendring er forsinkelsen 40 minutter.

Man kan kvittere for alarmen ved å trykke på « » .

Lyden forsvinner og lyset ved knappen går over til å lyse kontinuerlig inntil alarmtilstanden opphører.

Det samme gjelder vekslingen i tekstvinduet.

Det gis ikke noe alarmsignal når temperaturen er i endring, dvs når opp eller ned pilene vises.

S

TRØMBRUDD

Ved strømbrudd holdes alle data i minnet og klokken går i 48 timer. Deretter holdes dataene i minnet mens klokken står. Dataene vil da normalt holde seg i minnet i flere måneder, avhengig av batteriets oppladning når strømmen ble borte.

Ved normale, kortvarige strømbrudd vil altså alt gå tilbake til det normale når strømmen kommer på igjen.

Klokkens gangtid er avhengig av batteriets ladetid. For å få full gangreserve må ladetiden være minst

24 timer.

Hvis klokkens gangreserve har gått ut, kommer meldingen «STRØMBRUDD MAT INN TID » .

Hvis programmet eller stoppfunksjonen skal benyttes, må i så fall «TID NAA:

» mates inn på nytt. Hvis meldingen «BATTERY ERROR ENTER NEW DATA!

» kommer, betyr det at batteriet har vært helt utladet og alle data må legges inn på nytt.

GENERELL BESKRIVELSE

6

H

VILESTILLING

Hvis skapet slås av med hovedbryteren, oppfattes dette av regulatoren som et strømbrudd. Batteriet tappes og klokken stopper etter 48 timer.

Det anbefales derfor at man lar hovedbryteren stå på, men at man setter skapet i hvilestilling med « » når skapet ikke benyttes. Skapet er da i praksis helt avslått, men batteriet holdes fulladet og klokken går.

Lyset ved « » indikerer at skapet er i hvilestilling.

Skapet startes igjen ved et nytt trykk på «

»

.

S

KRIVER

En eventuell skriver i skapet er helt uavhengig av regulatoren og må slås på eller av med egen bryter i skriveren.

Det henvises forøvrig til egen bruksanvisning.

V

EDLIKEHOLD

For å oppnå god regulering og lang levetid må kjølemaskinens utvendige «radiatorer » holdes ren. Dette gjøres ved å trekke skapet fram og rengjøre med en støvsuger fra baksiden.

F

EILRETTING

Hvis det mot formodning skulle oppstå uregelmessigheter ved regulatoren som for eksempel ufullstendige bilder eller døde knapper, kan man forsøke å slå skapet av og på med hovedbryteren.

Mikroprosessoren går da gjennom en spesiell rydde- og oppstartsrutine før hovedprogrammet startes.

Om dette ikke løser problemet, er det nødvendig å foreta en såkalt master reset, se beskrivelse av bilde

10.

BILDEBESKRIVELSE

7

BILDEBESKRIVELSE

Tekstvinduet kan vise 9 forskjellige «bilder

» som velges med «

»

.

Et trykk på «

Et trykk på «

» gir neste bildenummer.

» fører direkte til hovedbildet.

I tillegg kan man få fram 2 spesialbilder ved å trykke på 2 knapper samtidig.

Bilde nr 1 - Hovedbilde

Velges normalt med «

»

. Kommer også automatisk opp 30 sek. etter siste trykk på en knapp selv om et annet bilde er valgt.

Dette bildet viser aktuell temperatur på øverste linje, mens innstilt temperatur vises på den nedre.

Når dette bildet er oppe, er alle knappene fra 0 til 9 uvirksomme, slik at de innmatede data ikke kan bli endret ved en tilfeldig berøring av knappene.

Følgende meldinger kan komme opp på dette bildet:

HØY

LAV

BØR 1:

V eksler med TEMP på øverste linje og indikerer at temperaturen er kommet over sin alarmgrense

Se også avsnitt om alarm.

Veksler med TEMP på øverste linje og indikerer at temperaturen er kommet under sin alarmgrense

Se også avsnitt om alarm.

Etter «BØR

» på andre linje vises 1,2,3,4 eller R.

Tallene 1 - 4 indikerer hvilken av de 4 mulige innstillingsverdiene som er aktiv. Se bilde 2.

Bokstaven R (Ramping) indikerer at temperaturen er i forandring opp eller ned etter en definert endringshastighet. Se bilde 9.

Et ter °C på øverste linje kan det vises piler som peker opp eller ned. Dette indikerer at temperaturen er på vei opp eller ned.

Dette kan skje ved oppstart eller etter en børverdiendring

Vises nederst til høyre, og indikerer at stopptidspunkt er innmatet. Se bilde 4.

s

SYKLUSVises på nedre linje og indikerer at skapet har stoppet ved full tid. Se bilde nr 4.

SLUTT

*

Vises etter °C på andre linje, og indikerer at avriming pågår eller nylig er avsluttet.

Temperaturen kan da kortvarig forstyrres noe. Se bilde 11.

BILDEBESKRIVELSE

8

Bilde nr 2 - Børverdier

Velges med «

»

.

På dette bildet kan inntil 4 børverdier for temperatur mates inn.

Markøren blinker på kolonet for den børverdien som regulatoren i øyeblikket regulerer etter. T1 er den verdien det reguleres etter når programverket er avslått, dette må man huske på når nye verdier mates inn. T2-4 benyttes altså bare når programverket er i bruk, ellers er verdiene her uten betydning.

Tallene i T1 - 4 er det samme som de kodetallene det refereres til senere under beskrivelsen av bildene

5-8 om programverket.

Temperaturområdet er 0 - 70 °C. Hvis en høyere verdi forsøkes matet inn, vil meldingen «FEIL

VERDI

» vises en liten stund og bildet kommer deretter tilbake med den opprinnelige verdien.

Bilde nr 3 - Datalogging

Velges med «

»

På dette bildet vises minimum, maksimum og gjennomsnittlig temperatur som har vært i skapet siden siste endring av innstillingsverdi.

Dataloggingen starter ikke før ca 45 minutter etter at innstilt temperatur er oppnådd. Før den tid vises bare 00.0.

Dette medfører at oppvarmingstiden ikke tas med i beregningene.

Det logges heller ikke data så lenge kontrollert stige- eller falltid er i funksjon.

Dataene vurderes slik at hvis gjennomsnittsverdien (SNITT) ligger kloss opp til eller er lik børverdien, må temperaturen stort sett ha vært riktig under hele perioden. Et stort avvik på max eller min må da bety at avviket har vært av kort og ubetydelig varighet, f.eks en kortvarig døråpning eller avrimning.

Ved kontinuerlig kjøring over lang tid, kan selvfølgelig avviket ha hatt en viss varighet uten at det gjør særlig utslag på gjennomsnittet.

Dataloggingen nullstilles i følgende tilfeller:

Oppstart av skapet

Endring av børverdi (Fra knapper eller programverk)

Omstart etter «SYKLUS SLUTT

»

Etter strømbrudd, unntatt hvis bruddet kommer i «SYKLUS SLUTT

»

- perioden.

BILDEBESKRIVELSE

9

Bilde nr 4 - Tid

Velges med «

»

.

På dette bildet vises aktuelt tidspunkt og det tidspunktet skapet eventuelt skal stoppe.

TID NAA: 1 0 0 0 0

MINUTT:

TIME:

DAG:

00 - 59 Her legges minutt fra 00 til 59 inn

00 - 23 Her legges time fra 00 til 23 inn

1 - 7 Her legges dag fra 1 til 7 inn

Dagene løper fra 1 til 7, slik at et helt omløp er akkurat en uke.

Man kan her mate inn nye verdier slik at man kan starte hvor som helst i en syklus når programverket benyttes.

STOPPTID: 0 0 0 0 0

MINUTT:

TIME:

DAG:

00 - 59 Her legges minutt fra 00 til 59 inn

00 - 23 Her legges time fra 00 til 23 inn

1 - 7 Her legges dag fra 1 til 7 inn

Her kan man mate inn det tidspunktet man eventuelt vil at skapet skal stoppe (max 1 uke), det vil si slå av varme, kjøling og vifter.

Verdien 0 00 00 betyr at skapet skal gå kontinuerlig

Når virkelig tid på øverste linje er lik innstilt stopptid, stopper kjølemaskinen, varmereguleringen opphører og viften(e) stopper.

Samtidig kommer teksten «SYKLUS SLUTT

» på nederste linje på bilde 1 og lampen på «

» tenner.

Temperaturen i skapet vises fortsatt på øverste linje, mens dataloggingen opphører. Loggdata som eventuelt ligger i systemet når skapet stopper, holdes i minnet inntil skapet startes igjen.

Stopptid blir automatisk satt til 0 00 00 når skapet stopper. Dette betyr at skapet går kontinuerlig når det igjen startes, hvis ikke en ny stopptid mates inn.

Skapet starter igjen etter et trykk på «

»

.

Bilde nr 5-8 - Programverk

Velges med «

»

.

Programverket kan programmeres på 4 like bilder: TA, TB, TC og TD.

På hvert av bildene kan det legges inn 4 forskjellige tidspunkter som temperaturen skal endres og hva den skal endres til. Tiden refererer seg til «TID NAA » som vises på bilde nr 4.

BILDEBESKRIVELSE

10

Dataene legges inn etter følgende mønster:

0 0 0 0 0 1

KODE Her legges koden, 1-4, for den børverdien som skal aktiviseres inn.

Det refereres til kodetallene på bilde 2.

MINUTT Her legges minutt fra 00 til 59 inn.

TIME Her legges time fra 00 til 23 inn.

DAG Her kan legges inn ukedag fra 1 til 7, endringen skjer da bare på den angitte ukedag.

Legges 0 inn her, vil endringen skje DAGLIG.

De forskjellige tidspunktene kan settes inn hvor som helst på disse bildene, de behøver ikke komme i noen bestemt rekkefølge og man kan blande ukentlige og daglige tidspunkt som man vil. Man må bare passe på å legge inn tidspunktene fra TA og utover. Alle tidspunkter som er lagt inn etter en posisjon med 000001, vil ikke komme med i programmet.

Man bør mate inn et nytt program med programverket avslått.

Hvis man likevel gjør endringer med programverket på, må systemet søke etter de riktige børverdiene hver gang et bilde forlates. Dette kan ta litt tid og meldingen «VENT » vises i tekstvinduet.

Systemet reagerer ikke på noen av knappene i denne perioden.

Ved innmating av et nytt program, må man se etter på alle bildene at det ikke finnes glemte tidspunkter fra et gammelt program.

Det skal stå 000001 i alle ubenyttede posisjoner.

Programverket startes med «

» og er på når det lyser.

Man kan starte hvor som helst i programmet.

Systemet leter bakover i tiden til det finner de børverdiene som hadde vært aktuelle om programverket hadde vært startet tidligere i programmet.

Denne operasjonen kan ta litt tid. Meldingen «VENT » vises da i tekstvinduet.

Systemet oppfatter ikke trykk på noen knapper i denne perioden.

Når programmet er startet, vil det gå kontinuerlig i en syklus på en uke. Hvis ingen dager er spesifisert i programmet, vil det framstå som en døgnsyklus.

BILDEBESKRIVELSE

11

Bilde nr 9 - Stige/Falltid

Velges med «

»

.

På dette bildet kan man mate inn den hastigheten temperaturen skal stige eller falle mot den endelige børverdien.

Man kan mate inn forskjellig hastighet for økende eller fallende temperatur under «OPP » eller «NED » .

Hastigheten mates inn med opp til 999 minutter pr tienedels grad.

Tidsenheten kan eventuelt endres til sekunder.

Se beskrivelse av bilde nr 10 - Opsjonsvalg og kalibrering.

Ved svært raske endringer i temperatur, vil skapets varme-eller kjølekapasitet være begrensningen.

Dette vil variere noe mellom skaptypene.

Med bare nuller innmatet under både «OPP » eller «NED » , vil skapet gå med fri hastighet til ny børverdi.

Mates en verdi inn på en eller begge steder, vil det alltid bestemme endringshastigheten, enten skapet går med eller uten programverk.

Når ny børverdi aktiveres, enten fra programverk eller manuelt, velges aktuell måleverdi som ny børverdi.

Denne vises da på hovedbildet og trappes så opp eller ned til endelig børverdi.

Så lenge denne styrte endringen pågår, vises en R etter «Bør » på hovedbildet.

Bilde nr 10 - Opsjoner og Kalibrering

Velges med «

»

+ «0

»

. Tallene er tilfeldig valgt

På første linje kan språk og tidsenhet for stige/falltid velges, man kan foreta en nullstilling av hele det endringsbare minnet i mikroprosessoren (reset), og man kan styre kjølemaskinen manuelt.

Andre linje er kalibrering og programversjon.

Språk

Meldingene i tekstvinduet kan vises på fire forskjellige språk.

Bare meldingen etter batterifeil vil alltid være på engelsk.

Ny språkkode velges etter tabellen under og mates inn etter L:

0 - ENGELSK (standard)

1 - NORSK

2 - TYSK

3 - FRANSK

BILDEBESKRIVELSE

12

Tidsenhet Stige/Falltid

Tidseneheten kan velges etter «T

»

:

0 - minutter

1 - sekunder

Hvis sekunder velges, skifter teksten på bilde 9 automatisk til SEK.

Reset

Ved å mate inn «1

» etter «R

»

:, vil alle endringsbare data i minnet nullstilles og mikroprosessoren går gjennom en rydderutine. Dette er aktuelt hvis man vil fjerne gamle data og starte fra bunnen av, eller hvis regulatoren skulle oppføre seg unormalt på noe vis.

Kjølemaskin Manuell/Auto

Man kan om ønskelig overstyre kjølemaskinens automatikk.

Ønsket funksjon velges etter tabellen under og mates inn etter C:

0 - Automatisk (standard)

1 - Alltid kjøl

2 - Uten kjøl

Kalibrering

Etter Z: kan den konstanten som står der endres for å bringe temperaturmålingene i samsvar med en eventuell kontrollmåling.

Eksempel: Måleverdi i display: 37,0 °C

Virkelig temperatur: 37,5 °C

Gammel konstant: Z:168

Ny konstant = 168 + (37,0-37,5) · 1 0 = 163

Ved å mate inn den nye konstanten vil alle målinger i dette eksempelet øke med 0,5 °C over hele temperaturområdet.

Tallet etter «A

»

: er en forsterkningsfaktor og er normalt ikke tilgjengelige for brukerne.

Programversjon

Tallet bak «P » er kun informasjon om hvilken programversjon mikroprosessoren inneholder og er ikke endringsbar.

Bilde nr 11 - Avriming

Velges med «

»

+ «

».

Standardverdier

Bilde for avrimings intervall og varighet samt øvre temperaturgrense for avriming.

LIM:

Av riming foretas bare ved arbeidstemperaturer under denne grensen. Max grense er 19,9 °C.

Eks 080 = 8,0 °C.

HRS: Timer mellom hver avriming. Max 199 timer.

SEC: Avrimingens varighet. Max er 999 og min er 50 sekunder.

BILDEBESKRIVELSE

13

Tilising kan føre til at temperaturen i skapet ikke kommer så langt ned som ønsket, eller det kan resultere i ujevn regulering.

Fastsettelse av disse verdiene er sterkt avhengig av skapets bruksområde og hvilke forhold det arbeider under.

Generelt kan man si at tilisingsfaren er størst ved temperaturer nær null, med mye fuktighet i skapet og ved høy værelsetemperatur.

Ved høy risiko for tilising, velges hyppige avriminger og/eller lange avrimingsperioder.

Under avrimingen stopper kjølemaskinen og man vil kunne registrere en mindre forstyrrelse i temperaturen. En stjerne på hovedbildet indikerer at avriming pågår eller nettopp er avsluttet.

Ved Reset (bilde 10) og ved batterifeil kommer standardverdier opp på dette bildet.

Egne notater

Egne notater

14

INDEX

15

INDEX

USERS MANUAL, Short form.................................................................................................................. 16

GENERAL DESCRIPTION. .....................................................................................................................17

How to enter data .........................................................................................................................18

Light Emitting Diode (LED) ........................................................................................................18

Safety thermostats ........................................................................................................................ 18

Alarm ...........................................................................................................................................19

Power failure ................................................................................................................................19

Standby ........................................................................................................................................19

Recorder .......................................................................................................................................20

Maintenance .................................................................................................................................20

Troubleshooting ...........................................................................................................................20

FRAME DESCRIPTIONS .........................................................................................................................21

FRAME 1, Main frame ................................................................................................................ 21

FRAME 2, setpoints.....................................................................................................................22

FRAME 3, Datalogging ...............................................................................................................22

FRAME 4, Time .......................................................................................................................... 23

FRAME 5-8, Timer breakpoints ..................................................................................................23

FRAME 9, Ramping .................................................................................................................... 24

FRAME 10, Options and calibration............................................................................................ 25

FRAME 11, Deicing .................................................................................................................... 26

USERS MANUAL, Short form

USERS MANUAL, Short form

Covers continuous run at one temperature. Additional functions are described on the following pages.

16

1 Turn on the main switch. Normally, a frame like this is displayed:

Random values

If the display remains blank, and the LED at "

" is lit, the display is turned on by hitting the "

".

The messages "BATTERY ERROR ENTER NEW DATA!" or "POWER FAIL ENTER TIME" may appear in the display if the main switch has been turned off for more than 48 hours. Those messages have no relevance during continuous run and are removed by hitting the "

"

Other messages or symbols may appear, see the section of frame descriptions, frame 1.

.

2 Confirm that the timer is off. The LED at " the "

"

.

" shall be dark and is may be turned off by hitting

3 Check the set value on line two. If correct value is displayed, the cabinet is to be used at the same temperature as last time. Therefore, the steps 4-6 may be skipped. Press "

" if a new set value is necessary. Following frame will appear in the display:

Random values

At continuous run T1 is always active and this is indicated by a flashing colon. Move the cursor to the first digit with " " . Correct value can now be entered by the buttons 0-9. The cursor moves automatically to the next digit. Return to the main frame by hitting " ".

An arrow at the first line indicates whether the temperature is changing up or down towards the setpoint.

4 Turn " " to 0 and " " to 10.

5 Let the temperature stabilise at set temperature.

6 Turn the " " slowly counter clockwise until the corresponding LED is lit. Thereafter, turn it a little bit upwards again until the LED is turned of. At the same way, turn the " " slowly clockwise until the corresponding LED is lit. Thereafter, turn it a little bit downwards again until the LED is turned of. Keep an eye on those lamps for some hours after this adjustment. If they are lighting from time to time, it means that they are adjusted too close to the setpoint. This will have a negative effect on the control accuracy.

7 The cabinet is now ready for a continuous run at one temperature. The logged values, max, min and average can be displayed at any time. See description of frame 3.

GENERAL DESCRIPTION.

GENERAL DESCRIPTION.

17

The cabinet is designed for accurate temperature control and very low dehumidification.

This is obtained by using a very accurate microprocessor-based temperature controller. The heatingand cooling elements are integrated and there is a high air speed through them and this results in a optimum surface temperature by means of condensation.

The air is blown through ducts and does not affect the air inside the cabinet.

The cooling machine is also controlled by the microprocessor. It is not started at a fixed temperature limit, but only when required. Normally, the cooling machine will stop at working temperatures higher than about 10°C above the ambient temperature.

The machine will always run when changing temperature towards a lower value.

It can also be turned on or off manually.

At very low temperatures, there is a danger of icing on the cooling element. Therefore, there is an automatic deicing cycle at the lowest temperatures.

The controller contains a LCD-display which normally displays the set- and measured values. In addition, it can display a number of messages and frames for entering of data. A chargeable backup battery keeps the data in the memory during a power failure.

The cabinet is also equipped with safety thermostats for protection of the samples in the case of a controller breakdown.

A number of special functions is also available, such as temperature ramping, cycling, datalogging, different languages, manual cooling machine control and digital calibration.

The datalogging starts after the initial stabilisation.

With disturbances such as a door opening, the alarm limit will exceeded.

GENERAL DESCRIPTION.

18

In this example the temperature is cycling between 4 diffrent temperatures and the ramping function is in use.

H

OW TO ENTER DATA

When a new frame is displayed, the cursor is always located under a colon. Frame 1 and 3 has no cursor since there are no changeable data on them.

The cursor is moved right by "

" towards the digit to be changed. A new value can be entered with the buttons 0-9 and the cursor moves automatically to the next digit. If that digit is not to be changed, the cursor can be moved right again with the " " and so on.

In the case of entering a wrong value, you have to step all the way around until the cursor is back in that position again.

There are limits on some of the digits. If, for example, a number higher than 7 is entered as day number in a week, the message "BAD VALUE" will be displayed for a moment. Thereafter, the frame is redisplayed with the original value.

The new data is stored in the memory at the moment of leaving the actual frame. This happens when hitting "

" or "

"

.

If you should happen to forget that, it will still happen after 30 sec. when frame 1 is displayed automatically.

It is also possible to clear all data in the memory. Se description of frame 10.

L

IGHT

E

MITTING

D

IODE

(LED)

A LED is located just below the display and is flashing when the temperature is on or close to the setpoint. Lights in heatup periods.

S

AFETY THERMOSTATS

The cabinet is equipped with safety thermostats for over- and under temperature to protect your samples if the electronic controller should brake down.

It is therefore very important to adjust those correct:

When running with timer off, adjust the thermostats as described in the section "User manual, short form".

GENERAL DESCRIPTION.

19

When running with timer on, you have to adjust the safety thermostats separately at the upper and lower temperature in the program.

If you, under normal operation, observe that any of those lights are lit or flashes, it means that they are adjusted too close to the setpoint, or there is a breakdown in the controller.

The " " stops the cooling machine while the " " cuts the heater.

A

LARM

If the temperature of some reason should drift away from the setpoint, the message HIGH or LOW will start to flash in frame 1 together with TEMP. This indicates that the temperature is too high or low. At the same time the LED at " " starts to flash.

If the alarm condition lasts for more than about 1-2 minutes, an acoustic signal will be heard.

This delay is 40 minutes after a temperature change.

The acoustic signal may be turned off by a hit on " " .

The LED stop flashing and will be lit until the alarm condition is ended.

No alarm signal will be given when the temperature is in change. That means no alarm when up or down arrows are displayed.

P

OWER FAILURE

In the case of a power failure, all data are kept in the memory and there is a 48 hours backup on the clock. The data will thereafter remain in the memory while the clock stops. The data will normally be kept in memory for months, depending on the condition of the battery.

After normal, short power failures everything will return to normal when the power is back.

To get full 48 hour backup time on the clock, the battery charge time must be at least 24 hours.

If the backup time has ended, the message POWER FAILURE ENTER TIME will appear. If the timer function shall be used, actual time must be entered at TIME NOW on frame 4.

The message BATTERY ERROR ENTER NEW DATA! means that the battery has been completely discharged and all data is lost.

S

TANDBY

If the cabinet is turned off with the main power switch, the controller will act the same way as in a power failure, the battery is discharging, and the clock will stop 48 hours later.

Therefore, it is better to put the controller in standby mode with the " the battery is not discharged and the clock do not stop.

"

. This turns the cabinet off but

The light at " " indicates standby mode.

The cabinet may be restarted by a hit on " " .

GENERAL DESCRIPTION.

R

ECORDER

If your cabinet has a recorder, it must be turned on/off by its internal power switch.

Read the recorder manual to operate the recorder.

20

M

AINTENANCE

To obtain accurate temperature control and a long life for the cooling machine it is important to keep it cleaned.

This can be done by pulling the cabinet out and clean it from the back with a vacuum cleaner.

T

ROUBLESHOOTING

If any abnormal conditions should appear on any frame, such as bad frame layout or dead buttons, this may be solved by turning the main switch off and on again.

The microprocessor will then go through a initial routine that should solve most of the problems.

If the problem is still there, a master reset is necessary.

See description of frame 10.

FRAME DESCRIPTIONS

FRAME DESCRIPTIONS

9 different frames can be displayed.

Next frame is displayed by a hit on "

"

.

Frame 1, the main frame, is displayed by a hit on "

"

.

In addition, two special frames can be displayed by hitting two buttons at the same time.

FRAME 1, Main frame

21

Random values. Normally displayed with a hit on "

30 sec after last button hit.

"

. Will allso appear

On this frame the measured temperature is shown on the upper line while the set value is shown on the lower line.

When this frame is displayed, all buttons from 0 to 9 are disabled.

This protect against unwanted data entering due to a random touch of these buttons.

Following messages may appear on this frame:

HIGH Alternates with TEMP on upper line and indicates that the temperature is outside the upper alarm limit.

LOW

SET 1

Alternates with TEMP on upper line and indicates that the temperature is outside the lower alarm limit.

1,2,3,4 or R may be displayed after SET on the second line.

The numbers 1-4 means which of the four possible setpoints that is active at the moment.

The letter R (Ramping) means that the temperature is changing towards a new setpoint according to a defined ramping rate. See description of frame 9.

s

This indicates that the temperature is in change from one level to an other. This happens after a restart or a setpoint change.

May appear on the lower line to the right, and indicates that the cabinet will stop at a defined time. Se description of frame 4.

END OF May be displayed on the lower line and indicates that the cabinet has stopped at

CYCLE full time. See description of frame 4.

*

Appears on the lower line to the right, and indicates that the cooling machine has stopped, or just have been stopped for deicing.

This may cause a short term disturbance on the temperature control.

FRAME DESCRIPTIONS

22

FRAME 2, setpoints

Chosen by "

"

On this frame four different temperature setpoints may be entered.

The cursor flashes on the colon of the setpoint that is active at the moment.

T1 is always the active setpoint when the timer is off.

Remember that when loading new setpoints!

T2-4 are therefore active only when the timer is on.

The numbers in T1 - 4 are the same numbers as refered to in the description of frames 5-8, timer.

The temperature range is 0 - 70 °C. If a higher value is entered, the message "BAD VALUE" will appear in the display for a moment and the frame will return with the original value after a while.

FRAME 3, Datalogging

Chosen by "

"

.

On this frame max, min and average temperature recorded since last change of the setpoint is displayed. This can be an useful aid in evaluation of the temperature cycle.

The recording is delayed for about 45 minutes after the setpoint is reached. Therefore, the stabilisation period is not recorded. In the delay period zeros are displayed only.

There is no recording while the ramping is in process.

An average value very close to the temperature setpoint indicates that the temperature must have been correct during most of the cycle.

A large deviation of the max or min values, indicates a temporary disturbance, for example a short door opening or a deicing.

Obviously, in very long cycles, a more serious deviation will still have very little influence on the average value.

The data is cleared in the following cases:

Initial start

Change of setpoint (from buttons or timer)

Restart after "End of cycle"

After a power failure, except if the power fails in the "End of cycle" period.

FRAME DESCRIPTIONS

23

FRAME 4, Time

Chosen by"

"

Actual time is displayed on the upper line while the time the cabinet shall stop is displayed on the lower line.

TIME NOW: 1 0 0 0 0

MINUTE: Minutes from 00 to 59

HOUR:Hours from 00 to 23

DAY: Days from 1 to 7

The day numbers runs from 1 to 7 so one cycle is exactly one week. It is important to enter correct time when the timer function is used. See description of frames 5-8, timer breakpoints.

STOPTIME: 0 0 0 0 0

MINUTE: Minutes from 00 to 59

HOUR:Hours from 00 to 23

DAY: Days from 1 to 7

With zeros only, as in this example, the cabinet will run continuously. If day, hour and minute is defined, the cabinet will stop when upper and lower line are equal.

At the same time the message "END OF CYCLE" appears on the lower line at frame 1 and the LED at

" " lits.

The temperature will still be displayed, while the data recording stops. All logged data are kept in the memory and will be cleared when the cabinet is restarted.

When the cycle is completed, the stop time is cleared.

Therefore, the cabinet will run continuously after the restart if not a new stop time is defined.

The cabinet is restarted by a hit on " " .

FRAME 5-8, Timer breakpoints

Chosen by "

"

The timer can be programmed at 4 equal frames: TA,TB,TC and TD.

Each of the frames contains 4 breakpoints.

The breakpoints refer to TIME NOW on frame 4.

FRAME DESCRIPTIONS

24

The breakpoints are to be entered in the following pattern:

0 0 0 0 0 1

CODE Code number for the setpoint to be activated.

The numbers refers to the code numbers on frame 2.

MINUTE

HOUR

Minutes from 00 to 59.

Hours from 00 to 23

DAY Day of week from 1 to 7. The breakpoint will be active at the defined day only. 0 means that the breakpoint is active

EVERY day.

The program shall start in the first position on frame TA.

The different breakpoints need not be entered in time order, and weekly and daily breakpoints may be mixed.

000001 must be entered in all unused positions.

A new program should be entered with the timer in the off mode.

If you enter a new program in the on mode, the system has to seek for correct setpoints each time a frame is left. This take some time and the message "WAIT" appear in the display.

All buttons are dead in this period of time.

The timer is turned on/off by the "

" and is on when lit.

The timer can be turned on at any time in the program. The system will look back in the passed time to find the correct setpoint.

This operation may take some time and the message "WAIT" will appear on the frame for a moment.

All buttons are dead in this period of time.

When the timer is on, the system will run through a one week cycle.

If no days are defined in the program, one cycle will be one day and night.

FRAME 9, Ramping

Chosen by "

"

The temperature may be ramped towards a new setpoint. The ramping rate upwards and downwards may be different and can be entered on this frame.

The temperature ramps in steps of .1°C and the entered values means minutes between each step.

Optionally the time basis may be changed to seconds. See description of frame 10.

At very fast ramping, the heat- or cooling capacity will limit the speed of the temperature change.

This limitation will be different on the different types of cabinets.

If 000 is entered, it means no ramping, and the temperature will change as fast as possible.

FRAME DESCRIPTIONS

25

If any ramping is defined, it will be active any time the temperature is changing from one level to an other.

When a new setpoint is made active, manually or by the timer, the actual temperature is used as the first setpoint in the ramping routine. This value is displayed on frame 1 and will be ramped up or down towards the final setpoint.

As long as the temperature is changing in ramping mode, the letter R is displayed just after SET on frame 1.

FRAME 10, Options and calibration

Chosen by "

Random values

"

+ " 0 "

On this frame it is possible to choose language, make a master reset of the microprocessor, change to sec. as timebase for the ramping, manually control the cooling machine, do calibration and finally, the software release is displayed.

Languages

All the messages may be displayed in four different languages.

Only the battery error message will always be displayed in English.

Choose language in the following table and enter the new code after L:

0 - ENGLISH (default)

1 - NORWEGIAN

2 - GERMAN

3 - FRENCH

Master reset

By entering a "1" after R:, all data in the memory are cleared and the microprocessor runs through a tidy up routine. This may be done if you want to remove all old data and start from scratch or in the case of abnormal behaviour by the controller.

Timebase, ramping

By entering a "1" after T:, the timebase for the ramptng is altered to seconds. "0" means minutes

(default).

Cooling machine, on/off

The automatic control of the cooling machine may be ignored by choosing a number from the table below and enter it after C:

0 - Automatic (default)

Calibration

1 - Cooler on 2 - Cooler off

The constant after Z: may be changed to bring the temperature measurement equal to the true value according to a control device.

Example: Displayed temperature 37,0 °C

True temperature

Old constant

37,5 °C

168

FRAME DESCRIPTIONS

26

New constant = 168 + (37,0-37,5)

·

10 = 163

By entering this new constant, all displayed values in this example will be increased by .5 °C over the entire temperature range.

The constant after A: is an amplifying factor and is normally not changeable for the user.

Program release

The number after P is a program release number only, and is not changeable.

FRAME 11, Deicing

Chosen by "

"

+ "

".

Default values

LIM: Deicing at temperatures below this limit only.

Example: 080 means 8.0°C.

Maximum limit is 19.9°C.

HRS: Hours between each deicing, maximum 199.

SEC: Deicing time, maximum 999 seconds, minimum 50 seconds.

Those values are strongly dependent on the working conditions.

Generally, working temperatures near zero, much water inside the cabinet and high ambient temperature increases the risk of ice build-up.

Ice build-up has a negative effect on the control accuracy.

At high risk of ice build-up, the time between each deicing can be reduced and/or the length of each deicing period may be increased.

The cooling machine stops during the deicing cycle and a small disturbance in the temperature may be seen.

A star on frame 1, lower line to the right, indicates that the deicing is, or just has been in process.

At master reset (frame 10) and after a battery error the default values will appear on this frame.

SPECIFICATIONS

SPECIFICATIONS

Temperature control

Temperature fluctuation/time

Temperature variation/interior

Readability/setability

Temperature range

Sensor

Controller

Display

Timer

Number of setpoints

Number of changes per cycle

Stop time, max number of hours

Ramping

Step per interval

Interval setable either or

Heating/cooling

Heating up time 0 -70°C

Cooling down time 70 - 0°C

Alarm

Display and acoustic

Alarm limit

Safety thermostats

Temperature fluctuation/time

Sensor

Setpoint

Shelves

Standard/max

Dimensions in mm

Load per shelf

Permitted total load

KBP 6087

+/÷ 0.1ºC

+/÷ 0.2ºC

0.1ºC

0 - 70ºC

Silicone

P + I

LCD

4

16

168

0.1ºC

0 - 999 min

0 - 999 sec

31 min

63 min

Yes

Setpoint +/÷ 2ºC

+/÷ 3ºC

Silicone

Analog

KBP 6151

+/÷ 0.1ºC

+/÷ 0.2ºC

0.1ºC

0 - 70ºC

Silicone

P + I

LCD

4

16

168

0.1ºC

0 - 999 min

0 - 999 sec

34 min

66 min

Yes

Setpoint +/÷ 2ºC

+/÷ 3ºC

Silicone

Analog

2/7

430 X 430

20 kg

80 kg

4/14

430 X 430

20 kg

80 kg

Feet

Feet adjustable

Movable an casters, 2 lockable

Power consumtion

Nominal power

Nominal voltage

Dimensions

Exterior mm

Interior mm

Volum litres

W, D, H w, d, h

Yes

1000W

230V, 50Hz, 1~

845, 615, 690

450, 450, 425

87

Yes

1000W

230V, 50Hz, 1~

845, 615, 1280

450, 450, 745

151

Weights

Net

Shipping

85 kg

100 kg, 612 dm3

110 kg

130 kg, 790 dm3

These technical data are specified for an empty cabinet and ambient temperature of 23

°C

27

KBP 6395

+/÷ 0.1ºC

+/÷ 0.3ºC

0.1ºC

0 - 70ºC

Silicone

P + I

LCD

4

16

168

0.1ºC

0 - 999 min

0 - 999 sec

64 min

128 min

Yes

Setpoint +/÷ 2ºC

+/÷ 3ºC

Silicone

Analog

4/22

577 X 577

30 kg

120 kg

Yes

1200W

230V, 50Hz, 1~

1025, 765, 1780

586, 600, 1123

395

190 kg

220 kg, 1870 dm3

COOLING SYSTEM

COOLING SYSTEM

28

KBP 6087/KBP 6151

1 Compressor type AZ 44124

2 Condensor type ZZ 0005

3 Condenser fan Olmo W 40/7

4 Filter-drier KMP

5 Cap. tube 0.8mm X 2000mm

6 Air cooler type 220008

7 Check valve 1/4'' flare

Charge: 160g R-134A

KBP 6395

1 Compressor type AZ 44194

2 Condensor type ZZ 0006

3 Condenser fan Olmo W 40/7

4 Filter-drier KMP

5 Cap. tube 0.8mm X 1800mm

6 Air cooler type ZZ 00009

7 Check valve 1/4'' flare

Charge: 220g R134A

LAYOUT AND COMPONENT LIST, DIGITAL PCB

LAYOUT AND COMPONENT LIST, DIGITAL PCB

29

R1

- 270

R2

- 5.6 K

R3

- 4.7 K

R4

68 K

R5

10 K

R6

1 K

R7

- 100 K

R8

10 K

R9

-

R10 -

R11 -

10 K

10 K

10 K

R12 - 110 K

R13 -

10 K

R14 -

51 K

R15 - 270

R16 - 270

R17 - 270

R18 -

10 K

R19 -

10 K

R20 - 4.7 M

R21 -

10 K

R22 - 9.1 K

R23 - 100 K

R24 - 1.2 K

R25 - *

R26 -

R27 -

R28 -

R29 - 200 K

R30 -

R31 -

51 K

27 K

3 K

1 K

22 K

**

* Op.amplifier offset compensation, normally open.

R32 - *

R33 - *

R34 -

22 K

R35 -

1 M

R36 -

10 K

R37 -

27 K

R38 - *

R39 -

3 K

R40 - *

R41 - 3.6 K

** Op.amplifier offset compensation, may also be open.

C1

- 4.7 µF, 63 V

C2

- 4.7 µF, 63 V

D1

- 1N6263

D2-3 - 1N4148

C3

- 0.1 µF, ceramic

D4-6 - MV5074C

C4

- 4.7 µF, 63 V

D7-9 - GL5PR8

C5

33 pF, ceramic

C6

33 pF, ceramic

Q1 - 2N4400

C7

1 µF, 63 V

Q2 - 2N4400

C8

- 0.1 µF, ceramic

Q3 - 2N4400

C9

1 µF, 63 V

Q4 - 2N4400

C10 - 0.1 µF, ceramic Q5 - 2N4400

C11 - 0.1 µF, ceramic Q6 - 2N4403

C12 - 4.7 µF, 63 V

A1

- KPE 242

C13 - 0.1 µF, ceramic S1-16 - JTP 1230B

IC1 - MC68HC705C8P - MICROCONTROLLER

IC2 - MC14443P

- A/D CONVERTER

IC3 - 93C46N

IC4 - MC3317P

- EEPROM

- OP. AMPLIFIER

IC5 - MC78L05ACP

IC6 - MC78L05ACP

IC7 - MC3317P

IC8 - MC3317P

- +5V REG.

- +5V REG.

- OP. AMPLIFIER

- OP. AMPLIFIER

P1

- CPT10.10K

P2

- 378.1K

P3

- 378.1K

Y1

- 4.194304 Mhz

TEMP CONTROL & SAFETY SCHEMATIC

TEMP CONTROL & SAFETY SCHEMATIC

30

LAYOUT AND COMPONENT LIST, POWER & I/O PCB

LAYOUT AND COMPONENT LIST, POWER & I/O PCB

31

R1

15

R2

15

R3

- 120

R4

- 120

R5

- 120

R6

- 820

R7

- 820

R8

- 820

R9

39

R10 -

51

R11 - 200

F1

- 500 mA

F2

- R110

C1 - 0.1 µF, PME271

C2 - 4.7 µF, 63 V

C3 - 470 µF, 16 V

C4 - 470 µF, 16 V

C5 - .01 µF, PME261

IC1 - DF04, RECTIFIER

IC2 - DF04, RECTIFIER

IC3 - MC7805CT,+5V REG.

IC4 - MOC 3041,TRIAC DR.

IC5 - MOC 3041,TRIAC DR.

IC6 - MOC 3041,TRIAC DR.

T1

- 230/12VAC

B1 - 3.6V 65MAH

K1 - RE030012

K2 - RE030012

V1 - SIOVS10K300

TC1- MAC 97A6

TC2- BTA 08 600A

TC3- BTA 08 600A

D1 - 1N6263

SENSORS - MTS 103

POWER & I/O SCEMATIC AND AC INTERCONNECTION

POWER & I/O SCEMATIC AND AC INTERCONNECTION

32

Notes

Notes

33

Notes

Notes

34

Dette blir baksiden på brosjyren!!!

Notes

35

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project