SGM LEKTRA VLW602 Technical Documentation Manual
SGM LEKTRA VLW602 is a display and configuration unit designed for use with their PTU5_ series ultrasonic level sensors. It offers a versatile interface with a clear LCD display and robust configuration options allowing you to control and monitor your level measurement system. Configure settings such as distance ranges, alarm thresholds, and output behaviour to suit your specific application. The VLW602 also features advanced diagnostics capabilities, providing insights into the sensor's functioning and aiding in troubleshooting.
PDF
Download
Document
Advertisement
Advertisement
VLW602 Display and configuration unit technical documentation EN Rev. Of 19/07/2022 VLW602 - contents CONTENTS 1-WARRANTY page 3 2-PRODUCT page 4 3-PERFORMANCE SPECIFICATIONS page 5 4-DIMENSIONS page 6 5-ELECTRICAL CONNECTIONS page 7 6-CONFIGURATION AND CALIBRATION page 9 7-QUICK SETUP page 10 8-ADVANCED SETUP page 16 9-FACTORY TEST AND QUALITY CERTIFICATE page 32 Page 2 of 32 www.sgm-lektra.com VLW602 - warranty 1-WARRANTY Products supplied by SGM LEKTRA are guaranteed for a period of 12 (twelve) months from delivery date according to the conditions specified in our sale conditions document. SGM LEKTRA can choose to repair or replace the Product. If the Product is repaired it will maintain the original term of guarantee, whereas if the Product is replaced it will have 12 (twelve) months of guarantee. The warranty will be null if the Client modifies, repair or uses the Products for other purposes than the normal conditions foreseen by instructions or Contract. In no circumstances shall SGM LEKTRA be liable for direct, indirect or consequential or other loss or damage whether caused by negligence on the part of the company or its employees or otherwise howsoever arising out of defective goods www.sgm-lektra.eu Page 3 of 32 VLW602 - product 2- PRODUCT 1 2 3 4 1. DISPLAY 2. CONFIGURATION KEYS 3. REMOVABLE CLAMPING PANEL 4. FOUR PG9 CABLE GLANDS 2.1 IDENTIFICATION Each meter has an adhesive identification plate on which are the meter main data. The following picture describes the information and data on the identification plate. VLW602A0A 24Vac 50÷60Hz PAI091800107 1. Product code 2. Power supply 3. Serial number Page 4 of 32 www.sgm-lektra.com 3-FEATURES VLW602 - features Housing material Epoxy coated aluminum Mechanical installation Wall mountig Protection degree IP66 Keyboard 4 push buttons Display LCD Electrical connection Internal connector Working temperature -25° ÷ +70°C Power supply 12÷30 Vdc 85÷265 Vdc Power consumption Max. 5W Power supply for PTU5_ 24Vdc Data comunication with PTU5_ Via MODBUS RTU www.sgm-lektra.eu Page 5 of 32 VLW602 - dimensions 4-DIMENSIONS 4.1 MECHANICAL DIMENSIONS 75 20~ 160 95 100 Page 6 of 32 www.sgm-lektra.com VLW602 - electrical connections 5-ELECTRICAL CONNECTIONS 5.1 CONNECTIONS BLUE GREEN YELLOW B(RS485) A(RS485) 4-20mA -mA BROWN 0V +mA RED 24VDC N(-) GND L(+) 1) Separate the engine control cables or power cables from the VLW602 connection cables. 2) Remove the caps from the cable glands and open the cover by unscrewing the screws. 3) Lead the cables into the transmitter through the cable glands. 4) Close the cap and tighten the cable glands 5.2 RECOMMENDATIONS FOR EXTERNAL MOUNTING To avoid the humidity infiltration inside the housing is recommended: - For electrical connections, tighten the PG9 cable gland.. - fully tighten the cap. - position the cable so that it forms a downward curve at the PG9 output; in this way the condensation and/or rain water will tend to drop from the curve bottom. - The two central cable glands are arranged for the PTU sensor connection cables. www.sgm-lektra.eu Page 7 of 32 VLW602 - electrical connections L(+) GND N(-) Page 8 of 32 BLUE GREEN YELLOW B(RS485) A(RS485) 4-20mA -mA BROWN 0V +mA RED 24VDC N(-) GND L(+) 5.3 Connection -mA +mA www.sgm-lektra.com VLW602 - configuration and calibration 6-CONFIGURATION AND CALIBRATION Via the VLW602 the operator can: access any transmitter function, change configuration parameter settings and other functions. 6.1 VLW602 FEATURES The VLW602 program module has 4 buttons which allow to perform all operational, control and programming instrument functions. In the configuration menus, is possible: 1. Submenus and parameters access; press 2. Parameter options choice: Press Press 3. to select and press to select the option and press to access. to store the option. to exit without storing. Configure the parameter values; in some parameters the configuration is done by setting a value (eg., in the SET DISTANCE 4mA parameter is possible to change the the corresponding distance value, in mm): press to select the digit to be modified (the digit is highlighted in inverse ), press to change the high lighted digits number, press Press to exit without storing. to save the set value and exit automatically. LEFT ARROW button: • Exit configuration • Back to previous menu • Echo map (from RUN mode) UP ARROW button: • Parameter values modification • Parameter scroll SCROLL button: • Cursor movement (to the right) • Parameter scroll ENTER button: • Configuration access • Options confirmation • Parameters values confirmation ! Displayed at the top alert thet the PTU sensor is not communicating with VLW602. ! Displayed at the top alerts that there is a generic error; press SCROLL to show the message that indicates the present error type. The PTU5_ returns automatically to RUN mode. www.sgm-lektra.eu Page 9 of 32 VLW602 - quick setup 7-QUICK SETUP 7.1 - Quick Setup menu structure Parameter Default Values Quick Setup Set Distance 4mA 0000 mm 1500mm (PTU50 1.5mt max) 6000mm (PTU51 6mt max) 12000mm (PTU56 12mt max) Set Distance 20mA 100mm (PTU50 1.5mt max) 400mm (PTU51 6mt max) 600mm (PTU56 12mt max) Set Distance 4mA Set Distance 20mA Medium $'/ -* Ȃ$$ )/ Blind Distance Display 0000 mm Medium >Liquids Solids Liquids Pipe $'/ -* Ȃ$$ )/ 000 Blind Distance 0000 mm Distace mm Level mm Level % Output mA Temperature °C 7.2 - QUICK SETUP MODE From “RUN” mode press ENTER to access the Quick Setup menu. Select the parameters by moving the cursor with SCROLL, and confirm with ENTER; press LEFT ARROW to exit. Page 10 of 32 Liquids 20 050mm (PTU50 1.5mt max) 300mm (PTU51 6mt max) 500mm (PTU56 12mt max) Distance mm 4321 D mm Ź DISTANCE 4mA DISTANCE 20mA MEDIUM FILTER COEFFICENT BLIND DISTANCE DISPLAY www.sgm-lektra.com VLW602 - quick setup 7.2.1 SET DISTANCE 4mA Ź DISTANCE 4mA DISTANCE 20mA MEDIUM FILTER COEFFICENT BLIND DISTANCE DISPLAY Press ENTER to display the distance value associated with 4mA output. Use SCROLL and UP ARROW to modify that value; in the example the 4mA distance is 3500mm. Press ENTER to confirm. SET DISTANCE 4mA 3500 mm DISTANCE 4mA Ź DISTANCE 20mA MEDIUM FILTER COEFFICENT BLIND DISTANCE DISPLAY 7.2.2 SET DISTANCE 20mA Press ENTER to display the distance value associated with 20mA output. Use SCROLL and UP ARROW to modify that value; in the example the 20mA distance is 500mm. Press ENTER to confirm.. SET DISTANCE 20mA 0500 mm Referent point PTU50-51-56 Distance 20mA Level measurament 100% Distance 4mA www.sgm-lektra.eu 0% Page 11 of 32 VLW602 - quick setup 7.2.3 MEDIUM DISTANCE 4mA DISTANCE 20mA Ź MEDIUM FILTER COEFFICENT BLIND DISTANCE DISPLAY Press ENTER to display the previous setting. Press SCROLL to select the medium type. Press ENTER to confirm. Ź LIQUIDS SOLIDS LIQUIDS PIPE LIQUIDS Page 12 of 32 SOLIDS LIQUIDS PIPE www.sgm-lektra.com VLW602 - quick setup 7.2.4 FILTER COEFFICIENT Press ENTER. Use SCROLL and UP ARROW to modify the value. Input a value from 1 to 99. 1 maximum speed, 99 maximum slowness. The function is deactivated with 0 (immediate response). Press ENTER to confirm. DISTANCE 4mA DISTANCE 20mA MEDIUM Ź FILTER COEFFICENT BLIND DISTANCE DISPLAY FILTER COEFFICENT 20 Fast resp. 5÷10 www.sgm-lektra.eu Normal resp. 20 Slow resp. 40÷100 Page 13 of 32 VLW602 - quick setup 7.2.5 BLIND DISTANCE Press ENTER. The BLIND ZONE is used to avoid undesired measures near to the transmitter. Use SCROLL and UP ARROW to modify the value. Press ENTER to confirm. The minimum value is 50mm (PTU50), or 300mm (PTU51) or 500mm (PTU56). DISTANCE 4mA DISTANCE 20mA MEDIUM FILTER COEFFICENT Ź BLIND DISTANCE DISPLAY BLIND DISTANCE 0250 mm Referent point PTU50-51-56 BLIND ZONE BLIND DISTANCE 7.2.6 DISPLAY Press ENTER to access the settings change. With the SCROLL button is possible to select the data to display. Press ENTER to confirm. Page 14 of 32 DISTANCE 4mA DISTANCE 20mA MEDIUM FILTER COEFFICENT BLIND DISTANCE Ź DISPLAY Ź DISTANCE mm LEVEL mm LEVEL % OUTPUT mA TEMPERATURE °C www.sgm-lektra.com VLW602 - quick setup 7.3 - ECHO MAP Pressing LEFT ARROW, from RUN mode, to access directly to the echoes digital map display, which are in PTU50-51-56 receiving. This function is useful for: - properly orient the transducer pointing. - verify the echoes in acquisition correctness. - identify any false echo signals that may cause measurement errors. Measured distance from PTU50-51-56 in real time Measure status D 721mm Echo frequency G 020 57.2KHz Echo signal normalization threshold 1 2 3 4 5 m The rectangle placed at the echo line base, indicates the measurement range within which the echo signal in reception is considered always valid for the distance measurement. This interval value is variable depending on the measurement conditions: min. ± 2.5% of the measured distance. www.sgm-lektra.eu Page 15 of 32 VLW602 - advanced configuration 8-ADVANCED CONFIGURATION 8.1 - “SETUP” MENU SETUP SET DISTANCE 4mA SET DISTANCE 20mA MEDIUM FILTER COEFFICIENT BLIND DISTANCE ACTUAL LEV 4mA ACTUAL LEV 20mA 8.2 - SETUP SET DISTANCE 4mA 0000mm SET DISTANCE 20mA 0000mm LIQUIDS SOLIDS LIQUIDS PIPE FILTER COEFFICIENT 000 BLIND DISTANCE 0000mm OK to confirm DISTANCE 3321 mm LEVEL 1679 mm From “RUN” mode, holding down UP ARROW, press ENTER to the advanced configuration mode access. Ź SETUP DISPLAY DIAGNOSTIC SERVICE PROBE INFO UNIT INFO Press SCROLL to select the menu and press ENTER to access. Press LEFT ARROW to exit. Ź SET DISTANCE 4mA SET DISTANCE 20mA MEDIUM FILTER COEFFICIENT BLIND DISTANCE ACTUAL LEV 4mA ACTUAL LEV 20mA Page 16 of 32 www.sgm-lektra.com VLW602 - advanced configuration 8.2.1 - SET DISTANCE 4mA Position the cursor on DISTANCE 4mA, press ENTER to access. Use UP ARROW and SCROLL to modify the value. Press ENTER to confirm. LEFT ARROW to exit without changes Default value: 1500mm (PTU50 range 1,5mt), 6000mm (PTU51 range 6mt.) or 12000mm (PTU56 range 12mt) 8.2.2 - SET DISTANCE 20mA Position the cursor on DISTANCE 20mA, press ENTER to access. Use UP ARROW and SCROLL to modify the value. Press ENTER to confirm. LEFT ARROW to exit without changes Default value: 100mm (PTU50 range 1,5mt), 400mm (PTU51 range 6mt.) or 600mm (PTU56 range 12mt) 8.2.3 - MEDIUM Position the cursor on MEDIUM, press ENTER to access. 3 configurations are possible: LIQUIDS - liquids measurement SOLIDS - granular solids measurement LIQUIDS PIPE - liquids measurement in pipe reference Press SCROLL to select the product type. Press ENTER to confirm. LEFT ARROW to exit without changes Default value: LIQUIDS 8.2.4 - FILTER COEFFICIENT Position the cursor on FILTER COEFFICIENT, press ENTER to access. Enter a value from 1 to 99: 1 maximum speed, 99 maximum slowness. The function is deactivated with 0 (immediate response) Use UP ARROW and SCROLL to modify the value. Press ENTER to confirm. LEFT ARROW to exit without changes Ź SET DISTANCE 4mA SET DISTANCE 20mA MEDIUM FILTER COEFFICIENT BLIND DISTANCE ACTUAL LEV 4mA ACTUAL LEV 20mA SET DISTANCE 4mA 5000 mm SET DISTANCE 4mA Ź SET DISTANCE 20mA MEDIUM FILTER COEFFICIENT BLIND DISTANCE ACTUAL LEV 4mA ACTUAL LEV 20mA SET DISTANCE 20mA 0300 mm SET DISTANCE 4mA SET DISTANCE 20mA Ź MEDIUM FILTER COEFFICIENT BLIND DISTANCE ACTUAL LEV 4mA ACTUAL LEV 20mA Ź LIQUIDS SOLIDS LIQUIDS PIPE SET DISTANCE 4mA SET DISTANCE 20mA MEDIUM Ź FILTER COEFFICIENT BLIND DISTANCE ACTUAL LEV 4mA ACTUAL LEV 20mA FILTER COEFFICIENT 20 Default value: 10 www.sgm-lektra.eu Page 17 of 32 VLW602 - advanced configuration 8.2.5 - BLIND DISTANCE Position the cursor on DISTANCE 4mA, press ENTER to access. Represent the “BLIND ZONE” Input the desired value in order to avoid measures near the surface of the sensor (if necessary). The minimum value is 250mm (6m vers.) or 400mm (10m vers.) Use UP ARROW and SCROLL to modify the value. Press ENTER to confirm. LEFT ARROW to exit without changes Default values: 50mm (PTU50), 300mm (PTU51) or 500mm (PTU56) 8.2.6 - ACTUAL LEV. 4mA Position the cursor on ACTUAL LEV. 4mA, press ENTER to access. SET DISTANCE 4mA SET DISTANCE 20mA MEDIUM FILTER COEFFICIENT Ź BLIND DISTANCE ACTUAL LEV 4mA ACTUAL LEV 20mA BLIND DISTANCE 0600 mm SET DISTANCE 4mA SET DISTANCE 20mA MEDIUM FILTER COEFFICIENT BLIND DISTANCE Ź ACTUAL LEV 4mA ACTUAL LEV 20mA Self distance learning function that is associated with the 4mA (lower value). Make sure that the level corresponds to 0%, ENTER to associate the actual measure with 4mA output value; OK TO CONFIRM . LEFT ARROW to exit without changes. 8.2.7 - ACTUAL LEV. 20mA Position the cursor on ACTUAL LEV. 20mA, press ENTER to access. SET DISTANCE 4mA SET DISTANCE 20mA MEDIUM FILTER COEFFICIENT BLIND DISTANCE ACTUAL LEV 4mA Ź ACTUAL LEV 20mA Self distance learning function that is associated with the 20mA (upper value). Make sure that the level corresponds to 100%, ENTER to associate the actual measure with 20mA output value; OK TO CONFIRM . LEFT ARROW to exit without changes. Page 18 of 32 www.sgm-lektra.com VLW602 - advanced configuration 8.3 “DISPLAY” menu DISPLAY DISPLAY VALUES >1 VALUE 2 VALUES 1 VALUE >2 VALUES LCD CONTRAST LCD CONTRAST 00 WELCOME TEXT WELCOME TEXT SGM-LEKTRA PTU5x DISTANCE mm LEVEL mm LEVEL % OUTPUT mA TEMPERATURE °C >PRIMARY VALUE SECONDARY VALUE PRIMARY VALUE >SECONDARY VALUE 8.4 - DISPLAY From “RUN” mode, holding down UP ARROW, press ENTER to access Position the cursor on DISPLAY and press ENTER DISTANCE mm LIVEL mm LIVEL % OUTPUT mA TEMPERATURE °C SETUP Ź DISPLAY DIAGNOSTIC SERVICE PROBE INFO UNIT INFO Select the parameters by moving the cursor with SCROLL and confirm with ENTER Ź DISPLAY VALUES LCD CONTRAST WELCOME TEXT 8.4.1 - DISPLAY VALUES Position the cursor on DISPLAY VALUES, press ENTER to access. Ź DISPLAY VALUES LCD CONTRAST WELCOME TEXT Itʼs possible to select if one value with big digits or two values are shown on the display in “RUN” mode. Select the parameters by moving the cursor with SCROLL and confirm with Ź 1 VALUE ENTER. 2 VALUES LEFT ARROW to exit without changes 8.4.1.1 - 1 VALUE Position the cursor on 1 VALUE, press ENTER to access. Only one value is displayed; itʼs possible to choose from 5 parameters. With the SCROLL button you can select data to display. Press ENTER to confirm. LEFT ARROW to exit without changes Ź 1 VALUE 2 VALUES Ź DISTANCE mm LEVEL mm LEVEL % OUTPUT mA 2013 www.sgm-lektra.eu D mm Page 19 of 32 VLW602 - advanced configuration 8.4.1.2 - 2 VALUE Position the cursor on 2 VALUE, press ENTER to access. 1 VALUE Ź 2 VALUES Two values are displayed; itʼs possible to choose which one is the primary and which is the secondary, each with a choice of 5 parameters. With the SCROLL button you can select data to display. Press ENTER to confirm. LEFT ARROW to exit without changes Ź PRIMARY VALUE SECONDARY VALUE Ź DISTANCE mm LEVEL mm LEVEL % OUTPUT mA PRIMARY VALUE Ź SECONDARY VALUE DISTANCE mm Ź LEVEL mm LEVEL % OUTPUT mA TEMPERATURE °C Page 20 of 32 www.sgm-lektra.com VLW602 - advanced configuration 8.4.2 - LCD CONTRAST Position the cursor on LCD CONTRAST, press ENTER to access. itʼs possible to adjust the contrast of LCD, simply increasing or decreasing the value of a parameter from 0 to 63. Use UP ARROW and SCROLL to modify the value. Press ENTER to confirm. LEFT ARROW to exit without changes DISPLAY VALUES Ź LCD CONTRAST WELCOME TEXT LCD CONTRAST 22 Default value: 32 8.4.3 - WELCOME TEXT Position the cursor on WELCOME TEXT, press ENTER to access. Itʼs possible to edit or delete the message that is displayed by the PTU5_ during the ignition phase. Use UP ARROW (up scroll) and SCROLL (down scroll) to change the digit; ENTER to move the digit to the right. To confirm press ENTER repeatedly until leave the parameter. LEFT ARROW to exit without changes Default value: SGM-LEKTRA PTU50-51-56 www.sgm-lektra.eu DISPLAY VALUES LCD CONTRAST Ź WELCOME TEXT WELCOME TEXT SGM-LEKTRA PTU5x Page 21 of 32 VLW602 - advanced configuration 8.5 “DIAGNOSTIC” menu DIAGNOSTIC ALARM CONFIGURATION MEASURE STATUS TEMPERATURE NO ECHO FOUND MAX GAIN ECHO IN BLIND DISTANCE >120% MEASURE STATUS G : 00000 FROZEN GAIN FROZEN GAIN 000 MAX GAIN TH. MAX GAIN TH 200 PEAK VALUES >DISPLAY VALUES RESET VALUES OUTPUT SIMUL DISABLE >ENABLE PEAK VALUES Max 0000mm Min 0000mm OUTPUT SIMUL 00.0mA 8.6 - DIAGNOSTIC From “RUN” mode, holding down UP ARROW, press ENTER to access Position the cursor on DIAGNOSTIC and press ENTER SETUP DISPLAY Ź DIAGNOSTIC SERVICE PROBE INFO UNIT INFO Select the parameters by moving the cursor with SCROLL and confirm with ENTER Ź ALARM CONFIGURATION MEASURE STATUS FROZEN GAIN MAX GAIN TH. PEAK VALUES OUTPUT SIMUL. 8.6.1 - ALARM CONFIGURATION Position the cursor on ALARM CONFIGURATION, press ENTER to access To enable or disable each diagnostic alarms. - with UP ARROW or SCROLL chose the desired item and press ENTER Ź ALARM CONFIGURATION MEASURE STATUS FROZEN GAIN MAX GAIN TH. PEAK VALUES OUTPUT SIMUL. Ź TEMPERATURE NO ECHO FOUND MAX GAIN ECHO IN BLIND DISTANCE >120% - with UP ARROW or SCROLL enable or disable the alarm signal and press ENTER to confirm DISABLE Ź ENABLE Page 22 of 32 www.sgm-lektra.com VLW602 - advanced configuration 8.6.2 - MEASURE STATUS Position the cursor on MEASURE STATUS, press ENTER to access. Itʼs possible to display the gain of the system, with values from 0 to 255. LEFT ARROW to exit ALARM CONFIGURATION Ź MEASURE STATUS FROZEN GAIN MAX GAIN TH. PEAK VALUES OUTPUT SIMUL. MEASURE STATUS G: 00000 8.6.3 - FROZEN GAIN Position the cursor on MEASURE STATUS, press ENTER to access. Itʼs possible to fix a value of gain (from 1 to 255) and consequently disable the automatic gain control. Once the value is 000 the automatic gain control restarts. Use UP ARROW and SCROLL to modify the value. Press ENTER to confirm. LEFT ARROW to exit without changes ALARM CONFIGURATION MEASURE STATUS Ź FROZEN GAIN MAX GAIN TH. PEAK VALUES OUTPUT SIMUL. FROZEN GAIN 000 Default value: 000 8.6.4 - MAX GAIN TH Position the cursor on MAX GAIN TH, press ENTER to access. Itʼs possible to change the max value of gain. If the gain reaches this value, the “GAIN” error code is activated Use UP ARROW and SCROLL to modify the value. Press ENTER to confirm. LEFT ARROW to exit without changes ALARM CONFIGURATION MEASURE STATUS FROZEN GAIN Ź MAX GAIN TH. PEAK VALUES OUTPUT SIMUL. MAX GAIN TH 255 Default value: 255 8.6.5 - PEAK VALUES Position the cursor on PEAK VALUES, press ENTER to access. The system store the maximum distance and the minimum distance measured since the power is turned ON. Itʼs possible to see those values or reset the values. With the SCROLL button you can select the function. Press ENTER to confirm. www.sgm-lektra.eu ALARM CONFIGURATION MEASURE STATUS FROZEN GAIN MAX GAIN TH. Ź PEAK VALUES OUTPUT SIMUL. Ź DISPLAY VALUES RESET VALUES Page 23 of 32 VLW602 - advanced configuration 8.6.5.1 - DISPLAY VALUES Position the cursor on DISPLAY VALUES, press ENTER to access. Ź DISPLAY VALUES RESET VALUES Displays the max. and min. distance measured from power on. LEFT ARROW to exit. NB - The peak values stored are erased every time the PTU50-51-56 turns-offl PEAK VALUES MAX 0000mm MIN 0000mm 8.6.5.2 - RESET VALUES Position the cursor on RESET VALUES, press ENTER to access. DISPLAY VALUES LEFT ARROW to return to the previous menu Ź RESET VALUES 8.6.6 - OUTPUT SIMULATION ALARM CONFIGURATION MEASURE STATUS WARNING - entering in the SIMULATION function, the current output is not FROZEN GAIN MAX GAIN TH. in function of the level measurement. To restore the current as a measured level PEAK VALUES function, press the LEFT ARROW button 3 times (RUN mode) Ź OUTPUT SIMUL. Position the cursor on OUTPUT SIMULATION, press ENTER to access. Itʼs possible to force the analog output to a desired value, from 3,5 to 21mA. Use UP ARROW and SCROLL to modify the value. Press ENTER to start the simulation. The simulation will remain active for 5 minutes, by pressing the LEFT ARROW itʼs possible to stop the simulation before 5 minute LEFT ARROW to return to the previous menu. Page 24 of 32 OUTPUT SIMUL. 04.0mA www.sgm-lektra.com VLW602 - advanced configuration 8.7 “SERVICE” menu SERVICE OUTPUT SAFE MODE UID 21.5 mA 3.85 mA HOLD LAST VALUE PROBE UID SET PROBE UID SET 001 UNIT UID SET UNIT UID SET 001 UID SEARCH OK TO BEGIN LANGUAGE ENGLISH ITALIANO FRANCAIS FREQUENCY FREQUENCY 00,0kHz F_WINDOW F_WINDOW 00 RESTORE SETTING OK TO CONFIRM ENABLE LOCK DISABLE ENABLE PASSWORD SET PASSWORD SET 0001 PASSWORD LOCK 8.8 - SERVICE From “RUN” mode, holding down UP ARROW, press ENTER to access Position the cursor on SERVICE and press ENTER SETUP DISPLAY DIAGNOSTIC Ź SERVICE PROBE INFO UNIT INFO Select the parameters by moving the cursor with SCROLL and confirm with ENTER Ź OUTPUT SAFE MODE UID LANGUAGE FREQUENCY F_WINDOW RESTORE SETTING PASSWORD LOCK 8.8.1 - OUTPUT SAFE MODE Position the cursor on OUTPUT SAFE MODE, press ENTER to access. Itʼs possible to choose a analog output value during diagnostic errors. “21.5 mA” forces the current output to 21,5mA “3.85 mA” forces the current output to 3,85mA ”HOLD LAST VALUE” maintains the output at the last valid value. With the SCROLL button you can select the operation mode. Press ENTER to confirm. LEFT ARROW to exit without changes Default value: HOLD LAST VALUE www.sgm-lektra.eu Ź OUTPUT SAFE MODE UID LANGUAGE FREQUENCY F_WINDOW RESTORE SETTING PASSWORD LOCK Ź 21.5 mA 3.85 mA HOLD LAST VALUE Page 25 of 32 VLW602 - advanced configuration 8.8.2 -UID Place the cursor on UID and press ENTER to enter. In this submenu you can manage the UID address of the PTU probe and of the VLW602 8.8.2.1 -PROBE UID SET Position the cursor on PROBE UID SET and press ENTER to enter. In this parameter it is possible to assign the UID address of the probe for data communication in a MODBUS RTU network. After confirming the change, VLW602 will automatically change the setting of the UNIT UID SET parameter in order not to interrupt communication with the PTU probe Use the UP ARROW and SCROLL to change the value. To confirm press ENTER LEFT ARROW to exit without changes Default value: 001 8.8.2.2 - UNIT UID SET Place the cursor on SET UNIT UID and press ENTER to enter. In this parameter it is possible to assign the UID address of VLW602 for MODBUS RTU communication with the PTU probe having the same UID address. Use the UP ARROW and SCROLL to change the value. To confirm press ENTER LEFT ARROW to exit without changes Default value: 001 8.8.2.3 - UID SEARCH Place the cursor on UID SEARCH and press ENTER to enter. This parameter automatically scans the UID address previously set in the UID probe connected to the VLW602. To start the search, press ENTER LEFT ARROW to exit Page 26 of 32 OUTPUT SAFE MODE Ź UID LANGUAGE FREQUENCY F_WINDOW RESTORE SETTING PASSWORD LOCK Ź PROBE UID SET UNIT UID SET UID SEARCH PROBE UID SET 001 PROBE UID SET Ź UNIT UID SET UID SEARCH UNIT UID SET 001 PROBE UID SET UNIT UID SET Ź UID SEARCH OK to begin www.sgm-lektra.com VLW602 - advanced configuration 8.8.3 - LANGUAGE Position the cursor on LANGUAGE, press ENTER to access. Sets the menu language: English, Italian, French Press SCROLL to select the menu language. Press ENTER to confirm. LEFT ARROW to exit without changes 8.8.4 - FREQUENCY Position the cursor on FREQUENCY, press ENTER to access. Itʼs possible to check the computed sensor emission frequency. OUTPUT SAFE MODE UID Ź LANGUAGE FREQUENCY F_WINDOW RESTORE SETTING PASSWORD LOCK ENGLISH Ź ITALIANO FRANCAIS OUTPUT SAFE MODE UID LANGUAGE Ź FREQUENCY F_WINDOW RESTORE SETTING PASSWORD LOCK LEFT ARROW to exit FREQUENCY 00.0 kHz 8.8.5 - F_ WINDOW Position the cursor on F_WINDOW, press ENTER to access. It is the increase value (in cm), step to step, of the window width during the echo signal research phase. The “F_WINDOW” is the area where the echo reception is active. Normally it is positioned around the real echo signal and all echoes detected within the F_WINDOW are deemed valid. Example: F_WINDOW parameter set to 5. - The PTU5_ detects an echo signal which is 4 meters from the sensor. - Suddenly, the echo signal disappears and a new echo signal to 3.5 mt away from the sensor is detected. - Each time the echo signal will be emitted, the PTU5_ will enlarge “F_WINDOW” with 5cm step, until covering the new eco detected area. Now the F_WINDOW will start to tighten around the new echo signal and the new measurement of 3,5mt distance will be used to calculate the level measurement, alarm thresholds, etc.. F_WINDOW serves to filter false echo signals products, for example, by the agitator blades Range: 05÷20 Use UP ARROW and SCROLL to modify the value. Press ENTER to confirm. LEFT ARROW to exit without changes OUTPUT SAFE MODE UID LANGUAGE FREQUENCY Ź F_WINDOW RESTORE SETTING PASSWORD LOCK SET WIDTH 05 Default value: 05 www.sgm-lektra.eu Page 27 of 32 VLW602 - advanced configuration 8.8.6 - RESTORE SETTING Position the cursor on SET UID, press ENTER to access. Press ENTER to restore the PTU50-51-56 default settings LEFT ARROW to exit without restored the PTU50-51-56 default settings 8.8.7 - PASSWORD LOCK Place the cursor on PASSWORD LOCK and press ENTER to enter. In this submenu it is possible to enable and set the password to protect the VLW602 programming menus 8.8.7.1 - ENABLE LOCK Position the cursor on ENABLE LOCK and press ENTER to enter. In this parameter it is possible to disable or enable the password protection to block access to the programming menus of the VLW602. Use the UP ARROW and SCROLL to select the setting. To confirm press ENTER LEFT ARROW to exit without changes Default value: DISABLE 8.8.7.2 - PASSWORD SET Place the cursor on SET PASSWORD and press ENTER to enter. In this parameter, you can set the protection password to block access to the VLW602 programming menus. Use the UP ARROW and SCROLL to change the value. To confirm press ENTER LEFT ARROW to exit without changes Default value: 0000 Page 28 of 32 OUTPUT SAFE MODE UID LANGUAGE FREQUENCY F_WINDOW Ź RESTORE SETTING PASSWORD LOCK OK TO CONFIRM OUTPUT SAFE MODE UID LANGUAGE FREQUENCY F_WINDOW RESTORE SETTING Ź PASSWORD LOCK Ź ENABLE LOCK PASSWORD SET Ź DISABLE ENABLE ENABLE LOCK Ź PASSWORD SET PASSWORD 0000 www.sgm-lektra.com VLW602 - advanced configuration 8.9 - PROBE INFO Position the cursor on INFO, press ENTER to access. In addition to information about the manufacturer, are displayed the firmware revision and the configuration index 8.10 - UNIT INFO Position the cursor on INFO, press ENTER to access. Firmware revision and the configuration index are displayed. www.sgm-lektra.eu SETUP DISPLAY DIAGNOSTIC SERVICE Ź PROBE INFO UNIT INFO SETUP DISPLAY DIAGNOSTIC SERVICE PROBE INFO Ź UNIT INFO Page 29 of 32 VLW602 - note _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ Page 30 of 32 www.sgm-lektra.com www.sgm-lektra.eu Page 31 of 32 Documentation subject to technical change with no prior warning 9-FACTORY TEST AND QUALITY CERTIFICATE In conformity to the company and check procedures I certify that the equipment: (Display and configuration unit) is conform to the technical requirements on Technical Data and it is made in conformity to the procedure Quality Control Manager: .......................................................... Production and check date: ................................................. SGM-LEKTRA S.r.l. Via Papa Giovanni XXIII, 49 20053 Rodano (MI) - ITALY tel: ++39 02 95328257 fax: ++39 02 95328321 e-mail: [email protected] web: sgm-lektra.com ">
Advertisement
Key features
- IP66 protection
- LCD display
- MODBUS RTU communication
- Advanced configuration options
- Diagnostic capabilities
- Wall mountable
- Quick setup mode
Frequently asked questions
Quick setup allows you to adjust parameters like distance, medium type and blind distance using predefined values that are common for most applications. Advanced setup unlocks more control over specific settings that may be necessary for complex applications.
From the 'RUN' mode, press the LEFT ARROW button to access the echo map display. It shows the digital map of echoes received by the PTU sensor in real-time. Use it to verify the sensor's orientation, identify false echoes, and ensure proper echo acquisition.
This parameter controls the responsiveness of the level measurement. Higher values increase the filtering effect, slowing down the response to changes in the level, while lower values result in a faster response.