Rockwell Automation Allen-Bradley 1606-XLE120E Original Instructions Manual
Rockwell Automation Allen-Bradley 1606-XLE120E is a high-performance, 120W power supply with a wide input voltage range of 100-240V AC. It features a compact size, high efficiency, electronic inrush current limitation, active power factor correction, and a wide operational temperature range. This power supply offers 20% output power reserves and can deliver three times the nominal output current for 12 ms, making it suitable for various applications.
PDF
Download
Document
Advertisement
Advertisement
Power Supply - 24V, 5 A, 120 W, Single-phase Input Catalog Numbers 1606-XLE120E, 1606-XLE120EC, 1606-XLE120EL, 1606-XLE120EH, 1606-XLE120ED Reference Manual Original Instructions Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. IMPORTANT Identifies information that is critical for successful application and understanding of the product. Labels may also be on or inside the equipment to provide specific precautions. SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE). 2 Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 Table of Contents Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Catalog Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Terminology and Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 AC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 DC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Input Inrush Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Hold-up Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 DC OK Relay Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Efficiency and Power Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Functional Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Front Side and User Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Connection Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Lifetime Expectancy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Mean Time Between Failure (MTBF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 EMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Safety and Protection Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Dielectric Strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Approvals and Fulfilled Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Regulatory Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Physical Dimensions and Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Application Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 3 Notes: 4 Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Product Overview The 1606-XLE units are high-end power supplies in a medium price range without compromising quality, reliability, and performance. The XLE Series is part of the Bulletin 1606 power supply family. The 1606-XLE120E power supplies come with three connection terminal options: screw, spring-clamp, or push-in terminals, which are optimized for automated wiring. The 1606-XLE120EC is equipped with conformal coated printed circuit boards that are preferred for the use in harsh environments and the 1606-XLE120ED features an enhanced DC input voltage range. These units feature a small size, high efficiency, electronic inrush current limitation, active power factor correction, and a wide operational temperature range. The devices have a power reserve of 20% included, which can even be used continuously at temperatures up to +45 °C (113 °F). Additionally, they can deliver three times the nominal output current for 12 ms that helps to trip fuses on faulty output branches. High immunity to transients and power surges and low electromagnetic emission, a DC OK signal contact for remote monitoring, and a large international approval package for various applications. • • • • • • • • • • • AC 100…240V Wide-range Input Width only 32 mm(1.26 in.) Efficiency up to 94.3% Excellent Partial Load Efficiency 20% Output Power Reserves Easy Fuse Breaking—three times nominal current for 12 ms Safe HiccupPLUS Overload Mode Active Power Factor Correction (PFC) Minimal Inrush Current Surge Full Power -25…+60 °C (-13 °F…+140 °F) DC OK Relay Contact Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 5 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Specifications Attribute Output voltage Adjustment range Output current Input voltage AC Mains frequency Input current AC Power factor Input voltage DC Input current DC AC Inrush current Efficiency Losses Hold-up time Temperature range Size (WxHxD) Weight Value 24V DC 24…28V 6.0…5.1 A 5.0…4.3 A 3.8…3.2 A Derate linearly 45…70 °C (113…158 °F) AC 100…240V 50…60 Hz 1.09/0.6 A 0.98/0.91 Notes Nominal Factory setting 24.1V Below 45 °C (113 °F) ambient At 60 °C (140 °F) ambient — -15%/+10% ±6% At 120/230V AC At 120/230V AC For 1606-XLE120E, 1606-XLE120EC, 1606-XLE120EL, 1606-XLE120EH DC 110…150V ±20% DC 110…300V ±20% 1.21/0.43 A 4/4 A 93.6/94.3% 8.2/7.3 W 35/ 35 ms -25…+70 °C (-13…+158 °F) 32x124x102 mm (1.26x4.88x4.02 in.) 440 g (0.97 lb) For 1606-XLE120ED At 110/300V DC At 120/230V AC At 120/230V AC At 120/230V AC At 120/230V AC — Without DIN rail — Catalog Numbers Power Supply 1606-XLE120E 1606-XLE120EC 1606-XLE120EL 1606-XLE120EH 1606-XLE120ED Terminology and Abbreviations Term PE and symbol Earth, Ground AC 230V 230V AC 50 Hz vs. 60 Hz 6 Connection Screw terminals Screw terminals and conformal coated pc-boards Spring-damp terminals Push-in terminals Screw terminals and enhanced DC input Definition PE is the abbreviation for Protective Earth and has the same meaning as the symbol. This document uses the term ‘earth’ which is the same as the U.S. term ‘ground.’ A figure that is displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%) included. For example: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V). A figure with the unit (V AC) at the end is a momentary figure without any additional tolerances included. As long as not otherwise stated, AC 230V parameters are valid at 50 Hz mains frequency. Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual AC Input The device is suitable to be supplied from TN, TT, or IT mains networks with AC voltage. For suitable DC supply voltages, See DC Input on page 8. Attribute AC input Value Notes Nom AC 100-240V — Min 85-264V AC Continuous operation AC input range Min 264-300V AC Occasionally for maximal 500 ms Allowed voltage L or N to earth Max 300V AC Continuous, according to IEC 60664-1 Input frequency Nom 50…60 Hz ±6% Turn-on voltage Typ 80V AC Steady-state value, see Figure 1 Shut-down voltage Typ 74V AC Steady-state value, see Figure 1 External input protection See Installation Instructions on page 6. Input current Power factor Typ Typ AC 100V 1.30 A 0.99 AC 120V 1.09 A 0.98 Crest factor Typ 1.7 1.8 Startup delay Typ Typ Typ Max 420 ms 80 ms 100 ms 200 mV 380 ms 80 ms 100 ms 200 mV Rise time AC 230V 0.60 A At 24V, 5 A, see Figure 3 0.91 At 24V, 5 A, see Figure 4 At 24V, 5 A, The crest factor is the mathematical ratio of the peak value to RMS value of the input current 2.2 waveform. 385 ms See Figure 2 80 ms At 24V, 5 A constant current load, 0 mF load capacitance, see Figure 2 110 ms At 24V, 5 A constant current load, 5 mF load capacitance, see Figure 2 200 mV See Figure 2 Figure 1 - Input Voltage Range Figure 2 - Turn-on Behavior, Definitions Figure 3 - Input Current Versus Output Current at 24V Output Voltage Figure 4 - Power Factor Versus Output Current at 24V Output Voltage Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 7 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual DC Input The device is suitable to be supplied from a DC input voltage. Use a battery or a similar DC source. A supply from the intermediate DC-bus of a frequency converter is not recommended and can cause a malfunction or damage the unit. Connect the +pole to the L, the –pole to N, and the PE terminal to an earth wire or to the machine ground. Attribute DC input Nom DC input range Min DC input current Allowed Voltage (+) or (-) input to Earth Turn-on voltage Shut-down voltage Typ Typ Max Typ Typ Value DC 110…150V DC 110…1300V 88…180V DC 88…360V DC 1.21 A 0.43 A 360V DC 74V DC 67V DC Notes ±20% For 1606-XLE120E, 1606-XLE120EC, 1606-XLE120EL, 1606-XLE120EH ±20% For 1606-XLE120ED Continuous operation for 1606-XLE120E, 1606-XLE120EC, 1606-XLE120EL, 1606-XLE120EH Continuous operation for 1606-XLE120ED At 110V DC, at 24V, 5 A At 300V DC, at 24V, 5 A Continuous according to IEC 60664-1 Steady state value Steady state value Figure 5 - Wiring for DC Input Battery + Power Supply AC L N + Load PE DC Input Inrush Current An active inrush limitation circuit (NTCs, are bypassed by a relay contact) limits the input inrush current after turn-on of the input voltage. The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. Attribute Inrush current Inrush energy AC 100V 8 Apeak 5 Apeak 5 Apeak 0.4 A²s Max Typ Typ Max Figure 6 - Typical Turn-on Behavior at Nominal Load, 120V AC Input, and 25 °C (77 °F) Ambient Battery + Power Supply AC AC 230V 7 Apeak 4 Apeak 6 Apeak 1 A²s 4A Input voltage 200V/DIV + Load PE - Output voltage DC 8 Notes At 40 °C (104 °F), cold start At 25 °C (77 °F), cold start At 40 °C (104 °F), cold start At 40 °C (104 °F), cold start Figure 7 - Typical Turn-on Behavior at Nominal Load, 230V AC Input, and 25 °C (77 °F) Ambient Input current 2A/DIV L N AC 120V 7 Apeak 4 Apeak 5 Apeak 0.5 A²s Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 50ms/DIV Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Output The output provides a SELV/PELV rated voltage, which is galvanically isolated from the input voltage. The output is designed to supply any kind of loads, including capacitive and inductive loads. If extreme large capacitors, such as EDLCs (electric double layer capacitors or ‘Ultra Caps’) with a capacitance > 0.3 F are connected to the output, the unit can charge the capacitor in an intermittent mode. The output is electronically protected against overload, no-load, and short-circuits. If there is a protection event, audible noise can occur. Attribute Output voltage Adjustment range Factory settings Line regulation Load regulation Ripple and noise voltage Nom Min Value 24V 24…28V Max 30.0V Typ Max Max Max Max 24.1V 10 mV 50 mV 50 mVpp 200 mVpp Notes — Guaranteed value This is the maximum output voltage that can occur at the clockwise end position of the potentiometer due to tolerances. It is not a guaranteed value that can be achieved ±0.2%, at full load and cold unit Between 85V and 300V AC Between 0 A and 6 A, static value, see Figure 8 Load > 0.2 A, Bandwidth 20 Hz to 20 MHz, 50 Ohms Load < 0.2 A, Bandwidth 20 Hz to 20 MHz, 50 Ohms — 6 A(1) Nom 5A — Nom 3.8 A — Nom 5.1 A — Nom 4.3 A — Nom 3.2 A — Derate linearly 45…70 °C (113…158 °F) Up to 12 ms once every 5 seconds, see Figure 9. The fuse braking current is an enhanced transient current that helps to trip fuses on faulty output branches. The output voltage stays Typ 15 A above 20V. Continuous current For output voltage above 13V DC, see Figure 8 Nom Output current Fuse breaking current Overload behavior Intermittent current(2) Max 7.2 A Overload/short-circuit current Output capacitance Typ 9A Max Typ 3.5 A 1800 μF Max 35V For output voltage below 13V DC, see Figure 8 Continuous current, see Figure 8 Intermitter current peak value for Typ 1 s. Load impedance 50 mΩ, see Figure 10 Discharge current of output capacitors is not included Intermitter current average value (R.M.S.) Load impedance 50 mΩ, see Figure 10 Included inside the power supply The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is on or off. The absorbing energy can be calculated according to the built-in large sized output capacitor. (1) This current is also available for temperatures up to +70°C (+158 °F) with a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes. (2) At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 1s. After this, the output is switched off for approx. 9s before a new start attempt is automatically performed. This cycle is repeated as long as the overload exists. If the overload has been cleared, the device will operate normally. See Figure 10 Figure 8 - Output Voltage Versus Output Current, Typ Output Voltage 28V Adjustment Range Figure 9 - Dynamic Output Current Capability, Typ Output Voltage (dynamic behavior, < 12ms) 28V 24 24 A 20 20 16 Adjustment Range 16 12 12 A: continuous current B: intermittent current 8 4 0 B 8 4 0 Output Current 0 1 2 3 4 5 6 7 8 9 10A Output Current 0 2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 A Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 9 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Figure 10 - Short-circuit on Output, HiccupPLUS Mode, Typ Output Current Normal Operation Normal Operation Short-circuit 9A t 0 Hold-up Time 1s 9s 1s 9s 1s 9s The hold-up time is the time during which a power supply’s output voltage remains within specification following the loss of input power. The hold-up time is output load dependent. At no load, the hold-up time can be up to several seconds. The green DC OK lamp is also on during this time. AC 100V 70 ms 55 ms 35 ms 27 ms Typ Min Typ Min Hold-up Time Figure 11 - Hold-up Time Versus Input Voltage AC 120V 70 ms 55 ms 35 ms 27 ms AC 230V 70 ms 55 ms 35 ms 27 ms At 24V, 2.5 A, see Figure 11 At 24V, 2.5 A, see Figure 11 At 24V, 5 A, see Figure 11 At 24V, 5 A, see Figure 11 Figure 12 - Shutdown Behavior, Definitions Zero Transition Hold-up Time 90 ms a) 24V 2.5 A typ. c) 24V 5 A typ. b) 24V 2.5 A min. d) 24V 5 A min. a 75 60 Input Voltage b 45 c d 30 - 5% Output Voltage 15 Input Voltage 0 90 120 155 190 DC OK Relay Contact Hold-up Time 230V AC This feature monitors the output voltage on the output terminals of a running power supply. Contact closes As soon as the output voltage reaches Typ 90% of the adjusted output voltage level. As soon as the output voltage dips more than 10% below the adjusted output voltage. Contact opens Short dips will be extended to a signal length of 100 ms. Dips shorter than 1 ms will be ignored. Switching hysteresis Typically 0.7V Maximal 60V DC 0.3 A, 30V DC 1 A, 30V AC 0.5 A, resistive load Contact ratings Minimal permissible load: 1 mA at 5V DC Isolation voltage See Dielectric Strength on page 17 Figure 13 - DC OK Relay Contact Behavior VOUT = VADJ 10% < 1ms open 10 > 1...4ms closed 0.9* VADJ 100ms open closed Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Efficiency and Power Losses Attribute Efficiency Typ Typ AC 100V 92.9% 92.7% AC 120V 93.6% 93.5% AC 230V 94.3% 94.5% Average efficiency(1)) Typ 91.3% 91.7% 92.0% Power losses Typ Typ Typ Typ 1.3 W 4.6 W 9.2 W 11.3 W 1.3 W 4.4 W 8.2 W 9.8 W 1.4 W 4.1 W 7.3 W 8.4 W Notes At 24V, 5 A At 24V, 6 A (Power Boost) 25% at 1.25 A, 25% at 2.5 A 25% at 3.75 A. 25% at 5 A At 24V, 0 A At 24V, 2.5 A At 24V, 5 A At 24V, 6 A (Power Boost) (1) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25% of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100% of the nominal load for the rest of the time. Figure 14 - Efficiency Versus Output Current at 24V, Typ Efficiency 95% 94 93 92 91 90 89 88 87 1 Figure 15 - Losses Versus Output Current at 24V, Typ Power Losses 12W (c) (b) (a) (a) (b) (c) (a) 100V AC (b) 120V AC (c) 230V AC 10 8 6 (a) 100V AC (b) 120V AC (c) 230V AC 4 2 Output Current 2 3 4 5 Output Current 0 1 6A Figure 16 - Efficiency Versus Output Current at 24V, 5 A, Typ 4 5 Figure 17 - Losses Versus Output Current at 24V, 5 A, Typ Power Losses Efficiency 95% 11W 94 10 93 9 92 8 91 7 6 90 Input Voltage 89 100 120 180 Input Voltage 5 230 100 120 264VAC 180 230 264VAC Functional Diagram L N Input Fuse Input Filter Input Rectifier Inrush Current Limiter PFC Converter Power Converter Output Filter Output Voltage Regulator Temperature Shut-down Output Power Manager Output Over-voltage Protection Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 Output Voltage Monitor DC-ok Relay VOUT DC OK LED DC OK Contact 11 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Front Side and User Elements Figure 18 - 1606-XLE120E, -XLE120EC Figure 19 - 1606-XLE120EL User Elements Input Terminals 2 2 1 3 N, L N, L Line Input 3 PE (Protective Earth) Input 4 4 5 Output Terminals Two identical + poles and two identical - poles 5 2 + Positive Output - Negative (return) Output 3 Output Voltage Potentiometer 4 DC OK light-emitting diode (LED) (green) On, when the output voltage is >90% of the adjusted output voltage 5 DC OK Relay Contact The DC OK relay contact is synchronized with teh DC OK lightemitting diode (LED). See DC OK Relay Contact on page 10. 1 1 Figure 20 - 1606-XLE120EH Figure 21 - 1606-XLE120ED User Elements Input Terminals 2 1 2 N, L N, L Line Input 3 3 PE (Protective Earth) Input 4 4 5 Output Terminals Two identical + poles and two identical - poles 5 2 + Positive Output - Negative (return) Output 3 Output Voltage Potentiometer 4 DC OK light-emitting diode (LED) (green) On, when the output voltage is >90% of the adjusted output voltage 5 DC OK Relay Contact The DC OK relay contact is synchronized with teh DC OK lightemitting diode (LED). See DC OK Relay Contact on page 10. 1 1 Connection Terminals 12 The terminals are IP20 fingersafe constructed and suitable for field and factory wiring. Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual 1606-XLE120E, 1606-XLE120EC, 1606-XLE120ED Type Solid wire Stranded wire American Wire Gauge Wire diameter max (including ferrules) Recommended tightening torque Wire stripping length Type Screwdriver Input Output DC OK-Signal Screw termination Max 6 mm2 Screw termination Max 6 mm2 Push-in termination Max 1.5 mm2 Max 4 mm2 AWG 20…10 2.8 mm (0.11 in.) Max 1 N•m, 9 lb•in 7 mm (0.28 in.) Screw termination Slotted or Cross- head No 2 Max 4 mm2 AWG 20…10 2.8 mm (0.11 in.) Max 1 N•m, 9 lb•in 7 mm (0.28 in.) Screw termination Slotted or Cross- head No 2 Max 1.5 mm2 AWG 24…16 1.6 mm (0.06 in.) 7 mm (0.28 in.) Push-in termination 3.0 mm (0.12 in.) slotted to open the spring Output Quick-connect spring-clamp termination Max 6 mm2 DC OK-Signal Solid wire Input Quick-connect spring-clamp termination Max 6 mm2 Stranded wire American Wire Gauge Wire diameter max (including ferrules) Wire stripping length Screwdriver Max 4 mm2 AWG 20…10 2.8 mm (0.11in.) 10 mm (0.4 in.) - Max 4 mm2 AWG 20…10 2.8 mm (0.11 in.) 10 mm (0.4 in.) - Max 1.5 mm2 AWG 24…16 1.6 mm (0.06 in.) 7 mm (0.28 in.) 3.0 mm (0.12 in.) slotted to open the spring 1606-XLE120EH Type Solid wire Input Push-in termination Output Push-in termination DC OK-Signal Push-in termination Max 2.5 mm2 Max 2.5 mm Max 2.5 mm2 Max 2.5 mm2 Max 1.5 mm2 Max 1.5 mm2 Max 1.5 mm2 AWG 24…12 2.3 mm (0.09 in.) 10 mm (0.4 in.) 3.0 mm (0.12 in.) slotted to open spring Max 1.5 mm2 AWG 24…12 2.3 mm (0.09 in.) 10 mm (0.4 in.) 3.0 mm (0.12 in.) slotted to open spring Max 1.5 mm2 AWG 24…16 1.6 mm (0.06 in.) 10 mm (0.4 in.) 3.0 mm (0.12 in.) slotted to open the spring 1606-XLE120EL Type Stranded wire American Wire Gauge Wire diameter max (including ferrules) Recommended tightening torque Wire stripping length Screwdriver 2 Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 Push-in termination Max 1.5 mm2 13 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Daisy Chaining Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current through one terminal pin does not exceed 25 A or 15 A for the 1606-XLE120EH. If the current is higher, use a separate distribution terminal block as shown in Figure 23. Figure 22 - Daisy Chain of Outputs Power Supply + +- Output Figure 23 - Distribution Terminals Use Distribution Terminals Power Supply Power Supply Load + +- Output + - + + Power Supply - - + + Output - - Output Load + - Maximal 15 A continuous for 1606-XLE120EH Maximal 25 A continuous for all other units Lifetime Expectancy The Lifetime expectancy that is shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131,400 hr). Any number exceeding this value is a calculated theoretical lifetime that can be used to compare devices. Lifetime Expectancy Mean Time Between Failure (MTBF) AC 100V 265,000 hr 748,000 hr 128,000 hr 363,000 hr AC 120V 270,000 hr 764,000 hr 143,000 hr 405,000 hr AC 230V 274,000 hr 775,000 hr 166,000 hr 469,000 hr At 24V, 2.5 A and 40 °C (104 °F) At 24V, 2.5 A and 25 °C (77 °F) At 24V, 5 A and 40 °C (104 °F) At 24V, 5 A and 25 °C (77 °F) MTBF is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. The MTBF figure is a statistical representation of the likelihood of a device to fail. An MTBF figure of, for example, 1,000,000 hr means that statistically one unit will fail every 100 hours if 10,000 units are installed in the field. However, it cannot be determined if the failed unit has been running for 50,000hr or only for 100 hr. For these types of units, the MTTF (Mean Time To Failure) value is the same value as the MTBF value. AC 100V MTBF SN 29500, IEC 800,000 hr 61709 1,402,000 hr 339,000 hr 490,000 hr MTBF MIL HDBK 217F 81,000 hr 800,000 hr 14 AC 120V 807,000 hr 1,414,000 hr 343,000 hr 496,000 hr 83,000 hr 807,000 hr AC 230V 867,000 hr 1,510,000 hr 368,000 hr 529,000 hr 89,000 hr 867,000 hr Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 At 24V, 5 A and 40 °C (104 °F) At 24V, 5 A and 25 °C (77 °F) At 24V, 5 A and 40 °C (104 °F); Ground Benign GB40 At 24V, 5 A and 25 °C (77 °F); Ground Benign GB25 At 24V, 5 A and 40 °C (104 °F); Ground Fixed GF40 At 24V, 5 A and 40 °C (104 °F) Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual EMC The electromagnetic capability (EMC) behavior of the device is designed for applications in the industrial environment and residential, commercial, and light industry environments.The device is investigated according to EN 610006-1, EN 61000-6-2, EN 61000-6-3, and EN 61000-6-4. EMC Immunity Electrostatic discharge EN 61000-4-2 Electromagnetic RF field EN 61000-4-3 Fast transients (Burst) Surge voltage on input EN 61000-4-4 EN 61000-4-5 Surge voltage on output EN 61000-4-5 Surge voltage on DC OK EN 61000-4-5 Conducted disturbance EN 61000-4-6 Voltage interruptions Powerful transients EN 61000-4-11 VDE 0160 Contact discharge 8 kV Air discharge 80 MHz…2.7 GHz Input lines Output lines Output lines DC OK signal (coupling clamp) L to N, L to PE, N to PE + to +/- to PE DC Okay Signal to PE 0.15…80 MHz 0% of 100V AC 40% of 100V AC 70% of 100V AC 0% of 100V AC 40% of 100V AC 40% of 100V AC 70% of 100V AC 0% of 200V AC (=0V) Over entire load range 15 kV 20V/m 4 kV 2 kV Criterion A(1) Criterion A Criterion A Criterion A Criterion A 2 kV Criterion A 2 kV 4 kV 1 kV 2 kV 1 kV 20V 0V AC, 20 ms 40V AC, 200 ms 70V AC, 500 ms 0V AC, 20 ms 80V AC, 200 ms, < 4 A 80V AC,500 ms, > 4 A 140V AC, 20 ms 5000 ms 750V, 0.3 ms Criterion A Criterion A Criterion A Criterion A Criterion A Criterion A Criterion A Criterion C Criterion A Criterion A Criterion A Criterion C Criterion A Criterion C Criterion A (1) A: The device shows normal operation behavior within the defined limits. C: Temporary loss of function is possible. The device can shut down and restarts by itself. No damage or hazards for the device will occur. EMC Emission Conducted emission input lines Conducted emission output lines Radiated emission Harmonic input current (PFC) Class B Limits for local DC power networks fulfilled Class B Fulfilled for Class A equipment Fulfilled, tested with constant current loads, nonVoltage fluctuations, flicker EN 61000-3-3 pulsing This device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device cannot cause harmful interference, and (2) this device must accept any interference received, including interference that can cause undesired operation. Switching Frequency PFC converter Main converter Auxiliary converter EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 EN 55011, EN 55022 EN 61000-3-2 110 kHz 84 kHz …140 kHz 60 kHz Fixed frequency Output load dependent Fixed frequency Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 15 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Environment Operational temperature Storage temperature Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 20 mm (0.79 in.) below the unit - 40 °C…+85 °C (-40 °F…185 °F) For storage and transportation .6 W/1 °C (1.6 W/1.8 °F) 45 °C…60 °C (113 °F…140 °F) 3 W/1 °C (3 W/1.8 °F) 60 °C…70 °C (140 °F…158 °F) Output de-rating 0.33A/1000 m or 5 °C/1000 m For altitudes >2000 m (6560 ft), see Figure 25 The de-rating is not hardware that is controlled. The user has to take this into consideration to stay below the de-rated current limits in order not to overload the unit. Humidity 5...95% r.h. According to IEC 60068-2-30 Atmospheric pressure 110…54 kPa See Figure 25 for details Altitude Up to 5000 m (16,400 ft) See Figure 25 for details III According to IEC 60664-1 for altitudes up to 2000 m (6560 ft) Overvoltage category II According to IEC 60664-1 for altitudes above 2000 m (6560 ft) Degree of pollution 2 According to IEC 62477-1, not conductive Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2 g 2 hours/axis According to IEC 60068-2-6 30 g 6 ms, 20 g 11 ms 3 bumps per direction, 18 bumps in total According to IEC 60068-2-27 Shock Shock and vibration are tested in combination with DIN rails according to EN 60715 with a height of 15 mm (0.59 in.) and a thickness of 1.3 mm (0.05 in.) and standard orientation. LABS compatibility As a rule, only non-silicon precipitating materials are used. The unit conforms to the LABS criteria and is suitable for use in paint shops. Tested according to ISA-71.04-1985, Severity Level G3 and IEC 60068-2-60 Test Ke Method 4 for a service life of minimum 10 years in these Corrosive gases environments. Audible noise Some audible noise can be emitted from the power supply during no load, overload, or short circuit. -25 …+70 °C (-13…158 °F) Figure 24 - Output Current Versus Ambient Temperature Figure 25 - Output Current Versus Altitude Allowed Output Current at 24V 6A Allowed Output Current at 24V B 6A 5A 5A A 3.8 A 0 -25 0 60 70°C 45 Ambient Temperature A 4A A... Tamb < 60°C B... Tamb < 45°C C... Short term A... 85 to 264V AC, continuous B... short term 16 C B Altitude 0m AP* 110 kPa * Atmospheric pressure Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 2000 m 80 kPa 5000 m 54 kPa Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Safety and Protection Features Min 500 M Ohm At delivered condition between input and output, which is measured with 500V DC Min 500 M Ohm At delivered condition between input and PE, measured with 500V DC Isolation resistance Min 500 M Ohm At delivered condition between output and PE, measured with 500V DC Min 500 M Ohm At delivered condition between output and DC OK contacts, which are measured with 500V DC PE resistance Max 0.1 Ohm Resistance between PE terminal and the housing in the area of the DIN rail mounting bracket Typ 30.5V DC Max 32.0V DC Output overvoltage protection In case of an internal anomaly, a redundant circuit limits the maximum output voltage. The output shuts down and performs three restart attempts. If the failure continues, the output shuts down. Cycle input power to reset. Class of protection I According to IEC 61140 — A PE (Protective Earth) connection is required Degree of protection IP 20 According to EN/IEC 60529 Output shutdown with automatic restart. Temperature sensors are installed on critical components inside the unit and turn off the unit in safety Over-temperature protection critical situations, which can happen, for example, when ambient temperature is too high, ventilation is Included obstructed or the derating requirements are not followed. There is no correlation between the operating temperature and turn-off temperature since this is dependent on input voltage, load, and installation methods. Metal Oxide Input transient protection For protection values See EMC on page 15. Varistor (MOV) Internal input fuse Included Not user replaceable slow-blow high-braking capacity fuse. Type. 0.10 mA/0.27 mA At 100V AC, 50 Hz, TN-,TT-mains/IT-mains Type. 0.13 mA/ 0.38 mA At 120V AC, 60 Hz, TN-,TT-mains/IT-mains Type. 0.20 mA/ 0.60 mA At 230V AC, 50 Hz, TN-,TT-mains/IT-mains Touch current (leakage current) Max 0.13 mA/ 0.35 mA At 110V AC, 50 Hz, TN-,TT-mains/IT-mains Max 0.17 mA/ 0.51 mA At 132V AC, 60 Hz, TN-,TT-mains/IT-mains Max 0.27 mA/ 0.81 mA At 264V AC, 50 Hz, TN-,TT-mains/IT-mains Dielectric Strength The output voltage is floating and has no ohmic connection to the ground. The output is insulated to the input by a double or reinforced insulation. Type and routine tests are conducted by the manufacturer. Field tests can be conducted in the field using the appropriate test equipment that applies the voltage with a slow ramp (2 s up and 2 s down). Connect all input-terminals together and all output poles before conducting the test. When testing, set the cutoff current settings to the value in the table below. We recommend that either the + pole or the – pole is to be connected to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or cannot be switched off when unnoticed earth faults occur. Type test 60 s Routine test 5 s Field test 5s Field test cut off current settings A 2500V AC 2500V AC 2000V AC > 10 mA Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 B 3000V AC 2500V AC 2000V AC > 10 mA C 1000V AC 500V AC 500V AC > 20 mA D 500V AC 500V AC 500V AC > 1 mA 17 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Figure 26 - Dielectric Strength Input DC-ok 1 B L N B A D Output Earth, PE C + (1) When testing inputs to DC OK confirm that the maximal voltage between DC OK and the output is not exceeded (column D). We recommend connecting DC OK pins and the output pins together when performing the test. 18 Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Approvals and Fulfilled Standards IEC 61010 CB Scheme Certificate IEC 61010-2-201 Electrical Equipment for Measurement, Control, and Laboratory Use— Particular requirements for control equipment IEC 62368 CB Scheme Certificate IEC 62368-1 Audio/video, information, and communication technology equipment—Safety requirements Output safety level: ES1 UL 61010-2-201 (former UL 508) UL Certificate Listed equipment for category NMTR - UL 61010-2201 Electrical Equipment for Measurement, Control, and Laboratory Use - Particular requirements for control equipment Applicable for US and Canada NMTR(7).E56639 IND. CONT. EQ. Regulatory Compliance CE EU Declaration of Conformity Trade conformity assessment for Europe The CE marking indicates conformance with the European RoHS directive, EMC Directive and the Low-voltage directive (LVD REACH Directive Manufacturer's Statement EU-Regulation regarding the Registration, Evaluation, Authorization, and Restriction of Chemicals WEEE Directive At the end of its life, this equipment should be collected separately from any unsorted municipal waste. RoHS (China RoHS 2) Manufacturer's Statement Administrative Measures for the Restriction of the Use of Hazardous Substances in Electrical and Electronic Products 25 years EAC EAC Certificate EAC Eurasian Conformity—Registration Russia, Kazakhstan, and Belarus Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 19 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Physical Dimensions and Weight Attribute Width Height Depth Weight DIN rail Body Installation clearances Penetration protection Figure 27 - Front View Approximate Dimensions (in millimeters) 1606 -XLE120E, -XLE120EC, -XLE120ED 20 1606-XLE120EL Value 32 mm (1.26 in.) 124 mm (4.88 in.) 102 mm (4.02 in.) The DIN rail height must be added to the unit depth to calculate the total required installation depth. 440 g (0.97 lb) Use 35 mm (1.38 in.) DIN rails according to EN 60715 or EN 50022 with a height of 7.5 mm or 15 mm (0.3 in. or 0.6 in.) Housing material Aluminum alloy Cover: Zinc-plated steel See Installation Instructions on page 6 Small parts like screws, nuts, etc. with a diameter larger than 3.5 mm (0.14 in.) Figure 28 - Side View Approximate Dimensions (in millimeters) 1606-XLE120EH Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Accessories 1606-XLA-XLE -Wall/Panel Mount Bracket This bracket is used to mount the devices on a wall/panel without utilizing a DIN rail. The bracket can be mounted without detaching the DIN rail brackets. Figure 29 - Isometric Right View Figure 30 - Isometric Rear View Figure 31 - Isometric Left View Figure 32 - Wall Mounting—Front View Figure 33 - Wall Mounting—Hole Pattern Figure 34 - Wall Mounting—Side View 1606-XLSRED—Redundancy Module The 1606-XLSRED is a dual redundancy module, which can be used to build 1+1 or N+1 redundant systems. The device is equipped with two 10 A nominal input channels, which are individually decoupled by utilizing diode technology. The output can be loaded with a nominal 20 A continuous current. The device does not require an additional auxiliary voltage and is self-powered even if there is a short circuit across the output. For a safe and vibration resistant wiring, the device is equipped with time saving quick connect spring clamp terminals. The unit is narrow and only requires 32 mm (1.26 in.) width on the DIN rail. Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 21 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual 1606-XLERED20 —Redundancy Module The 1606-XLERED20 is a dual redundancy module, which can be used to build 1+1 or N+1 redundant systems. The device is equipped with two input channels, each rated for 20 A for ambient temperatures up to 70 °C (158 °F) and are individually decoupled by utilizing MOSFET technology. The inputs can also be operated up to 24 A when the ambient temperature does not exceed 45 °C (113 °F). The output can be loaded with nominal 20 A at 70 °C (158 °F) or 24 A at 45 °C (113 °F) continuous current. Using MOSFETSs instead of diodes reduces heat generation, losses and voltage drop between input and output. Due to these advantages, the unit is narrow and only requires 32 mm (1.26 in.) width on the DIN rail. The device does not require an additional auxiliary voltage and is self-powered even if there is a short circuit across the output. 1606-XLERED20Y—Redundancy Module with Automated Load The 1606-XLERED20Y is a dual redundancy module, which can be used to build 1+1 redundant systems. The device is equipped with two input channels, each rated for 10 A for ambient temperatures up to 70 °C (158 °F) and are individually decoupled by utilizing MOSFET technology. The inputs can also be operated up to 12 A when the ambient temperature does not exceed 45 °C (113 °F). The output can be loaded with nominal 20 A at 70 °C (158 °F) or 24 A at 45 °C (113 °F) continuous current. Using MOSFETSs instead of diodes reduces heat generation, losses and voltage drop between input and output. Due to these advantages, the unit is narrow and only requires 32 mm (1.26 in.) width on the DIN rail. The device does not require an additional auxiliary voltage and is self-powered even if there is a short circuit across the output. The device is equipped with an automated load sharing feature, which balances the load current between the two input channels. It also monitors the function of the redundancy circuitry and provides a signal if the output current is too high, which could prevent redundancy if one power supply fails. The signal also reports too low or too high input voltages. 1606-XLSBUFFER24—Buffer Module The 1606-XLSBUFFER24 buffer module is a supplementary device for DC 24V power supplies. It delivers power to bridge typical mains failures or extends the hold-up time after the AC power is turned off. 22 Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual When the power supply provides a sufficient voltage, the buffer module stores energy in the integrated electrolytic capacitors. When the mains voltage is lost, the stored energy is released to the DC-bus in a regulated process. The buffer module can be added in parallel to the load circuit at any given point and does not require any control wiring. One buffer module can deliver 20 A additional current and can be added in parallel to increase the output ampacity or the hold-up time. Application Notes All parameters are typical values that are specified at 230V AC, 50 Hz input voltage, 24V, 5 A output load, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Peak Current Capability The unit can deliver peak currents (up to several milliseconds) which are higher than the specified short-term currents. This helps to start loads that demand a high current. Solenoids, contactors, and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal output current. The same situation applies when starting a capacitive load. The peak current capability also delivers the safe operation of subsequent circuit breakers of load circuits. The load branches are often individually protected with circuit breakers or fuses. If there is a short or an overload in one branch circuit, the fuse or circuit breaker need a certain amount of overcurrent to open in a timely manner. This avoids voltage loss in adjacent circuits. The extra current (peak current) is supplied by the power converter and the built-in large sized output capacitors of the power supply. The capacitors get discharged during such an event, which causes a voltage dip on the output. The following three examples show typical voltage dips for resistive loads: Figure 35 - 10 A Peak Current for 50 ms, Typ (2x the Nominal Current) Figure 36 - 25 A Peak Current for 5 ms, Typ (5x the Nominal Current) Figure 37 - 15 A Peak Current for 12 ms, Typ (3x the Nominal Current) Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 23 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual IMPORTANT The CD-OK relay triggers when the voltage dips more than 10 percent for longer than 1 ms. Peak Current Voltage Dips Typically from 24V to 16V Typically from 24V to 16.5V Typically from 24V to 14V At 10 A for 50 ms and resistive load At 25 A for 2 ms and resistive load At 25 A for 5 ms and resistive load Charging Batteries The power supply can be used to charge lead-acid or maintenance free batteries. Two 12V SLA or VRLA batteries are needed in series connection. Instructions for charging batteries: a. Use only matched batteries when putting 12V types in series. b. Ensure that the ambient temperature of the power supply stays below 40 °C (104 °F). c. Use a 10 A circuit breaker or a blocking diode between the power supply and the battery. d. Ensure that the output current of the power supply is below the allowed charging current of the battery. e. The return current to the power supply is typically 8 mA. This return current can discharge the battery when the power supply is switched off except in case a blocking diode is utilized. f. Set the output voltage, which is measured at no load and at the battery endof-charge voltage. The voltage should be set to the following at these ambient temperatures: • • • • 27.8V at 10 °C (50 °F) 27.5V at 20 °C (68 °F) 27.15V at 30 °C (86 °F) 26.8V at 40 °C (104 °F) Series Operation Devices of the same type can be connected in series for higher output voltages. It is possible to connect as many units in series as needed, providing the sum of the output voltage does not exceed 150V DC. Voltages with a potential above Output 60V DC must be installed with a protection against touching. Avoid return voltage (load, and example, from a decelerating motor or battery) which is applied to the output terminals. Keep an installation clearance of 15 mm (0.59 in.) (left/right) between two power supplies and avoid installing the power supplies on top of each other. Do not use power supplies in series in mounting orientations other than the standard mounting orientation. 24 Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Leakage current, EMI, inrush current, and harmonics will increase when using multiple devices. Parallel Use to Increase Output Power Devices can be paralleled to increase the output power. The output voltage shall be adjusted to the same value (±100 mV) with the same load conditions on all devices, or the devices can be left with the factory settings. The ambient temperature is not allowed to exceed 40 °C (104 °F). If more than three devices are connected in parallel, a fuse or circuit breaker with a rating of 10 A is required on each output. Alternatively, a diode or redundancy module can also be utilized. Energize all devices simultaneously. It can be necessary to cycle the input power (turn-off for at least 5 seconds), if the output was in overload or short circuits and the required output current is higher than the current of one unit. Keep an installation clearance of 15 mm (0.59 in.) (left/right) between two devices and avoid installing devices on top of each other. Do not use devices in parallel in mounting orientations other than the standard mounting orientation or in any other condition where a reduction of the output current is required (for example, altitude). Pay attention that leakage current, EMI, inrush current will increase when using multiple devices. Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 25 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Parallel Use for Redundancy Please note that there are variants with built-in redundancy available in the XLE Series. Check XLE Series -Rx units. 1+1 Redundancy: Devices can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one device fails. The simplest way is to put two devices in parallel. This is called a 1+1 redundancy. In case one device fails, the other one is automatically able to support the load current without any interruption. It is essential to use a redundancy module to decouple devices from each other. This helps prevent the defective unit from becoming a load for the other device, which helps to ensure that the output voltage can be maintained. 1+1 redundancy allows ambient temperatures up to 70 °C (158 °F). Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple devices. Recommendations for building redundant power systems: • • • • Use separate input fuses for each device. Use separate mains systems for each device whenever it is possible. Monitor the individual devices. Therefore, use the DC OK signal of the device. It is desirable to set the output voltages of all devices to the same value (± 100 mV) or leave it at the factory setting. N+1 Redundancy: Redundant systems for a higher power demand are built in a N+1 method. For example four devices, each rated for 5 A, are paralleled to build a 15 A redundant system. Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple devices. Keep an installation clearance of 15 mm (0.6 in.) (left/right) between two devices and avoid installing the devices on top of each other. Do not use devices in parallel in mounting orientations other than the standard mounting orientation or in any other condition, where a reduction of the output current is required. For N+1 redundancy the ambient temperature is not allowed to exceed 40 °C (104 °F). 26 Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Figure 38 - 1+1 Redundant Configuration for 5 A Load Current with a Dual Redundancy Module Figure 39 - 1+1 Redundant Configuration with Active Load Share for 5 A Load Current With a Dual Redundancy Module Figure 40 - N+1 Redundant Configuration for 15 A Load Current with Multiple Power Supplies and Redundancy Modules Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 27 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Operation on Two Phases The power supply can also be used on two-phases of a three-phase-system. Such a phase-to-phase connection is allowed as long as the supplying voltage is below 240V+10%. Ensure the wire, which is connected to the N-terminal, is appropriately fused. Maximum allowed voltage between a phase and PE must be below 300V AC. Power Supply +10% max. L1 240V L3 AC L N PE DC L2 Use in a Tightly Sealed Enclosure When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher than outside. In such situations, the inside temperature defines the ambient temperature for the power supply. The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. The power supply is placed in the middle of the box, no other heat producing items are inside the box The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of 10 mm (0.39 in.). The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. Attribute Enclosure size Input voltage Load Temperature inside the box Temperature outside the box Temperature rise 28 Case A 10x180x165mm (0.39x7.09x6.5 in.) Rittal Typ IP66 Box PK 9516 100 Plastic 230V AC 24V, 4 A; (=80%) 38.3 °C (101 °F) 26.1 °C (79 °F) 12.2K (22 °F) Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 Case B 10x180x165mm (0.39x7.09x6.5 in.) Rittal Typ IP66 Box PK 9516 100 Plastic 230V AC 24V, 5 A; (=100%) 39.6 °C (103.3 °F) 25.5 °C (78 °F) 14.1K (25.3 °F) Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Mounting Orientations Mounting orientations other than input terminals on the bottom and output on the top require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature. The listed lifetime and MTBF values from this datasheet apply only for the standard mounting orientation. The following curves give an indication for allowed output currents for altitudes up to 2000 m (6560 ft). Figure 41 - Mounting Orientation A (Standard Orientation) Figure 42 - Mounting Orientation B (Upside Down) Figure 43 - Mounting Orientation C (Table-top Mounting) Figure 44 - Mounting Orientation D (Horizontal CW) Figure 45 - Mounting Orientation E (Horizontal CCW) Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 29 Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual Notes: 30 Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 Power Supply - 24V, 5 A, 120 W, Single-phase Reference Manual Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Power Supply Technical Data, publication 1606-TD002. Industrial Components Preventive Maintenance, Enclosures, and Contact Ratings Specifications, publication IC-TD002 Description Provides product selection, specifications, and dimensions information. Provides a quick reference tool for Allen-Bradley industrial automation controls and assemblies. Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides general guidelines for the application, installation, and maintenance of solid-state control in Safety Guidelines for the Application, Installation, and Maintenance of the form of individual devices or packaged assemblies incorporating solid-state Solid-state Control, publication SGI-1.1 components. Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details. Product Certifications website, rok.auto/certifications. You can view or download publications at rok.auto/literature. Rockwell Automation Publication 1606-RM100A-EN-P - July 2020 31 Rockwell Automation Support Use these resources to access support information. Technical Support Center Knowledgebase Local Technical Support Phone Numbers Literature Library Product Compatibility and Download Center (PCDC) Find help with how-to videos, FAQs, chat, user forums, and product notification updates. Access Knowledgebase articles. Locate the telephone number for your country. Find installation instructions, manuals, brochures, and technical data publications. Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes. rok.auto/support rok.auto/knowledgebase rok.auto/phonesupport rok.auto/literature rok.auto/pcdc Documentation Feedback Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback. Waste Electrical and Electronic Equipment (WEEE) At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental information on its website at rok.auto/pec. Allen-Bradley, expanding human possibility, FactoryTalk, and Rockwell Automation are trademarks of Rockwell Automation, Inc. EtherNet/IP is a trademark of ODVA, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur Publication 1606-RM100A-EN-P - July 2020 Copyright © 2020 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A. ">

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- Wide input voltage range (100-240V AC)
- High efficiency (up to 94.3%)
- Compact size
- Active PFC
- 20% output power reserves
- HiccupPLUS overload mode
- DC OK relay contact
- Conformal coated pc-boards (EC model)
- Enhanced DC input voltage range (ED model)
Frequently asked questions
The output voltage is 24V DC, with an adjustment range of 24V to 28V.
The output current is 5A, with a maximum intermittent current of 15A for 12 ms.
The efficiency can reach up to 94.3%.
The 1606-XLE120E power supply comes with screw, spring-clamp, or push-in terminals.