Trane VariTrane VPWF Installation, Operation And Maintenance Manual

Trane VariTrane VPWF Installation, Operation And Maintenance Manual

Add to My manuals
64 Pages

advertisement

Trane VariTrane VPWF Installation, Operation And Maintenance Manual | Manualzz
Installation, Operation, and Maintenance
VariTrane™
™ Variable Air Volume
(VAV) Terminal Air Units
Shutoff, Fan Powered, and CoolSense™
Sensible Cooling
S i n g l e - D u c t : VCCF, VCEF, VCWF
D u a l - D u c t : VDDF
F a n - P o w e r e d : VPCF, VPEF, VPWF, VSCF, VSEF, VSWF
F a n - P o w e r e d L o w H e i g h t : LPCF, LPEF, LPWF, LSCF, LSEF, LSWF
C h i l l e d W a t e r S e n s i b l e C o o l i n g T e r m i n a l U n i t s : LDCF, LDEF, LDWF
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning
equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person
could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment.
September 2021
VAV-SVX08R-EN
Introduction
Read this manual thoroughly before operating or
servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required. Your personal safety and the proper
operation of this machine depend upon the strict
observance of these precautions.
The three types of advisories are defined as follows:
WARNING
CAUTION
NOTICE
Indicates a potentially hazardous situation
which, if not avoided, could result in death or
serious injury.
Indicates a potentially hazardous situation
which, if not avoided, could result in minor or
moderate injury. It could also be used to alert
against unsafe practices.
Indicates a situation that could result in
equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are
refrigerants that contain Chlorine, Fluorine and Carbon
(CFCs) and those containing Hydrogen, Chlorine,
Fluorine and Carbon (HCFCs). Not all refrigerants
containing these compounds have the same potential
impact to the environment. Trane advocates the
responsible handling of all refrigerants-including
industry replacements for CFCs and HCFCs such as
saturated or unsaturated HFCs and HCFCs.
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or
serious injury.
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded
field wiring poses FIRE and ELECTROCUTION
hazards. To avoid these hazards, you MUST follow
requirements for field wiring installation and
grounding as described in NEC and your local/
state/national electrical codes.
WARNING
Personal Protective Equipment (PPE)
Required!
Failure to wear proper PPE for the job being
undertaken could result in death or serious injury.
Technicians, in order to protect themselves from
potential electrical, mechanical, and chemical
hazards, MUST follow precautions in this manual
and on the tags, stickers, and labels, as well as the
instructions below:
•
Before installing/servicing this unit,
technicians MUST put on all PPE required for
the work being undertaken (Examples; cut
resistant gloves/sleeves, butyl gloves, safety
glasses, hard hat/bump cap, fall protection,
electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Safety Data
Sheets (SDS) and OSHA guidelines for
proper PPE.
•
When working with or around hazardous
chemicals, ALWAYS refer to the appropriate
SDS and OSHA/GHS (Global Harmonized
System of Classification and Labelling of
Chemicals) guidelines for information on
allowable personal exposure levels, proper
respiratory protection and handling
instructions.
•
If there is a risk of energized electrical
contact, arc, or flash, technicians MUST put
on all PPE in accordance with OSHA, NFPA
70E, or other country-specific requirements
for arc flash protection, PRIOR to servicing
the unit. NEVER PERFORM ANY SWITCHING,
DISCONNECTING, OR VOLTAGE TESTING
WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE
ELECTRICAL METERS AND EQUIPMENT ARE
PROPERLY RATED FOR INTENDED
VOLTAGE.
Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices
are important to the environment, our customers, and
the air conditioning industry. All technicians who
handle refrigerants must be certified according to local
rules. For the USA, the Federal Clean Air Act (Section
608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management
of refrigerants. Know the applicable laws and follow
them.
©2021 Trane
VAV-SVX08R-EN
Introduction
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in
death or serious injury.
•
•
All Trane personnel must follow the
company’s Environmental, Health and Safety
(EHS) policies when performing work such as
hot work, electrical, fall protection, lockout/
tagout, refrigerant handling, etc. Where local
regulations are more stringent than these
policies, those regulations supersede these
policies.
Non-Trane personnel should always follow
local regulations.
WARNING
Fiberglass Wool!
Exposure to glass wool fibers without all
necessary PPE equipment could result in cancer,
respiratory, skin or eye irritation, which could
result in death or serious injury. Disturbing the
insulation in this product during installation,
maintenance or repair will expose you to airborne
particles of glass wool fibers and ceramic fibers
known to the state of California to cause cancer
through inhalation.
You MUST wear all necessary Personal Protective
Equipment (PPE) including gloves, eye protection,
a NIOSH approved dust/mist respirator, long
sleeves and pants when working with products
containing fiberglass wool.
Precautionary Measures:
•
Avoid breathing fiberglass dust.
•
Use a NIOSH approved dust/mist respirator.
•
Avoid contact with the skin or eyes. Wear
long-sleeved, loose-fitting clothing, gloves,
and eye protection.
•
Wash clothes separately from other clothing;
rinse washer thoroughly.
•
Operations such as sawing, blowing, tearout, and spraying may generate fiber
concentrations requiring additional
respiratory protection. Use the appropriate
NIOSH approved respirator.
First Aid Measures:
•
Eye Contact - Flush eyes with water to
remove dust. If symptoms persist, seek
medical attention.
•
Skin Contact - Wash affected areas gently
with soap and warm water after handling.
VAV-SVX08R-EN
About This Manual
This manual describes the installation of with
recommended wiring, piping, and mounting of singleduct, dual-duct, fan-powered, and low-height VAV
terminal units, and chilled water sensible coil terminal
units.
See also the following reference documents:
•
BAS-SVX40-EN —Wireless Comm IOM
•
BAS-SVX55-EN — Wireless Comm Network Design
Best Practices Guide
•
BAS-SVX62*-EN — Tracer® UC210 Programmable
Variable-Air-Volume (VAV) Box Controller
•
VAV-SVX07*-EN — Tracer® UC400 Programmable
BACnet® Controller for VAV Units
•
VAV-SVP01*-EN — VAV VV550 LonTalk® Controller
•
VAV-SVX01*-EN — VAV-UCM 4.2 IOM
Receiving and Handling
These units are shipped completely assembled with the
exceptions of outlet duct temperature sensors on nonVCEF products, water valves, and accessories. Upon
receiving the equipment, complete the following:
•
Locate the nameplate and refer to the model and
sales order number and check that the correct units
have been delivered.
•
Inspect the control enclosures and air valve casing
for dents or punctures.
•
Verify that all options have been included, such as
filters, controls, heating coils, water valves, etc.
Also check that the unit voltages agree with the
building parameters.
•
Manually rotate fan (if applicable) to assure that
there are no obstructions within the housing.
•
Claims for in-transit damage must be filed
immediately with the delivery carrier.
•
For hot water re-heat units, check the coil fins and
make sure that coils are not damaged.
•
Locate and verify that the correct zone sensors are
with the order. These will be marked with an orange
“Accessories Enclosed” label. Store in a secure
location until needed. Accessories lost at the job
site are NOT covered by the Trane warranty.
•
If a discrepancy occurs between what was ordered
and what is received, contact you local Trane
representative immediately.
•
Read appropriate section in this manual for
installation procedures prior to starting equipment.
Upon receiving the equipment, please inspect each unit
and components for external or internal damage. Refer
to the bill of lading to insure all equipment and
accessories have been received. Contact your local
Trane sales representative and notify the trucking
3
Introduction
company immediately of any short ship or damaged
equipment.
Read this manual thoroughly before operating or
servicing this unit.
Copyright
This document and the information in it are the
property of Trane, and may not be used or reproduced
in whole or in part without written permission. Trane
reserves the right to revise this publication at any time,
and to make changes to its content without obligation
to notify any person of such revision or change.
4
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
Revision History
•
Updated the Model Number chapter.
•
Running edits.
VAV-SVX08R-EN
Table of Contents
Model Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Single-Duct VAV Units . . . . . . . . . . . . . . . . . . . . 6
Dual-Duct VAV Units . . . . . . . . . . . . . . . . . . . . . . 9
Fan-Powered VAV Units Model Number
Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Chilled Water Sensible Cooling Terminal
Units Moisture Sensor Installation . . . . . . . . 26
Unit Accessibility . . . . . . . . . . . . . . . . . . . . . . . . 26
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Mounting Actuator . . . . . . . . . . . . . . . . . . . . . . 26
Single Duct VAV Units . . . . . . . . . . . . . . . . . . . 15
Typical Single Duct VAV Units . . . . . . . . 15
Stand-alone Units . . . . . . . . . . . . . . . . . . . . . . .
Stand-alone UCM 4.2. . . . . . . . . . . . . . . . .
Stand-alone VV550 LonTalk
Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stand-alone UC400. . . . . . . . . . . . . . . . . . .
Stand-alone UC210. . . . . . . . . . . . . . . . . . .
Dual-Duct VAV Units . . . . . . . . . . . . . . . . . . . . 16
Bottom Access . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Fan-Powered/Fan-Powered Low-Height
VAV Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Typical Fan-powered Units . . . . . . . . . . . 16
Weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Chilled Water Sensible Cooling Terminal
Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Information. . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Chilled Water Sensible Cooling Terminal
Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
26
26
27
27
27
Unit Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Fan Motor Amperage . . . . . . . . . . . . . . . . . . . . 32
Adjusting the SCR Motor Speed
Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Single-Duct VAV Units . . . . . . . . . . . . . . . . . . . 19
Electrically Commutated Motor
(ECM). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Dual-Duct VAV Units . . . . . . . . . . . . . . . . . . . . . 19
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Fan-Powered VAV Units and Chilled
Water Sensible Cooling Terminal
Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Bracket Locations — Fan
Powered . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Bracket LocationsChilled Water
Sensible Cooling Terminal
Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Wiring — Electric Heater Control
Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Duct Connections. . . . . . . . . . . . . . . . . . . . . . . . 24
Water Coil Connections . . . . . . . . . . . . . . . . . . 24
Discharge Duct Temperature Sensor
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Electronic Duct Temperature Sensor
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
VAV-SVX08R-EN
Control Box Wiring . . . . . . . . . . . . . . . . . . . . . . 52
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Fan Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Filter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Filter Change Out . . . . . . . . . . . . . . . . . . . . 60
Water Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Fan Motor Replacement . . . . . . . . . . . . . . . . . . 60
SCR Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5
Model Numbers
Single-Duct VAV Units
Digit 1, 2— Unit Type
Digit 12, 13, 14, 15 — Controls
(continued)
Digit 12, 13, 14, 15 — Controls
(continued)
VC = VariTrane™ Single—Duct
DD22 = VV550 DDC- Vent Flow control to
operate prop water valve
DD23 = VV550 DDC- Basic plus- Local
(Electric heat- PWM) Remote
DD24 = VV550 DDC- Basic plus- Local
(Water heat- Modulating)
DD25 = VV550 DDC- Basic plus- Local
(Water heat- Modulating) Remote (WaterN.O. 2-position)
DD26 = VV550 DDC- Basic plus- Local
(Water heat- N.O. 2-position) Remote
(Water- Modulating)
DD27 = VVV550 DDC- Basic plus- Local
(Water heat- N.C. 2-position) Remote
(Water- Modulating)
DD28 = VV550 DDC- Basic plus- Local
(Water heat- N.O. 2-position) Remote
(Water- N.O. 2-position)
DD29 = VV550 DDC- Basic plus- Local
(Water heat- N.C. 2-position) Remote
(Water- NC 2-position)
DD30 = VV550 DDC- Basic plus- Local
(Water heat- N.O. 2-position) Remote
(Water- N.C. 2-position)
DD31 =VV550 DDC- Basic plus- Local (Water
heat- N.C. 2-position) Remote (Water- N.O.
2-position)
DD32 = VV550 DDC- Basic plus- Local
(Electric heat- Staged) Remote (Staged EH)
DD33 = VV550 DDC- Vent Flow control to
operate N.O. On/Off water valve
DD41 = UC400 DDC- Basic (No water or
electric heat)
DD42 = UC400 DDC- Basic (Water heat- N.C.
2-position)
DD43 = UC400 DDC- Basic (Water heatModulating)
DD44 = UC400 DDC- Basic (Electric heatStaged)
DD45 = UC400 DDC- Basic (Electric heatPWM)
DD46 = UC400 DDC- Ventilation flowcooling only
DD47 = UC400 DDC- Basic (Water heat- N.O.
2-position)
DD49 = UC400 DDC- Flow Tracking (Cooling
only)
DD50 = UC400 DDC- Ventilation Flow (Water
heat- N. C. 2-position
DD51 = UC400 DDC- Ventilation Flow
(Electric heat- Staged)
DD52 = UC400 DDC- Ventilation Flow (Water
heat- Modulating)
DD53 = UC400 DDC- Basic plus- Local
(Electric heat- PWM) Remote (Staged EH)
DD54 = UC400 DDC- Basic plus- Local
(Water heat- Modulating) Remote (WaterN.C. 2-position)
DD55 =UC400 DDC- Basic plus Local (Water
heat- Modulating) Remote (Water- N.O.
2-position)
DD56 = UC400 Basic plus - Local (Water heat
- N.O. 2-position) Remote (Water Modulating)
DD57 = UC400 DDC- Basic plus- Local
(Water heat- N.C. 2-position) Remote
(Water- Modulating)
DD58 = UC400 DDC- Basic plus- Local
(Water heat- N.O. 2-position) Remote
(Water- N.O. 2-position)
DD59 = UC400 DDC- Basic plus- Local
(Water heat- N.C. 2-position) Remote
(Water- N.C. 2-position)
DD60 = UC400 DDC- Basic plus- Local
(Water heat- N.O. 2-position) Remote
(Water- N.C. 2-position)
DD61 = UC400 DDC- Basic plus- Local
(Water heat- N.C. 2-position) Remote
(Water- N.O. 2-position)
DD62 = UC400 DDC- Basic plus- Local
(Electric heat- Staged) Remote (Staged EH)
DD63 = UC400 DDC- Ventilation Flow (Water
heat- N.O. 2-position)
DD65 = UC400 Basic (Electric Heat
Modulating SCR)
DD66 = UC400 Basic plus- Local (Electric
heat-Modulating SCR) Remote (Staged EH)
DD67 = UC400 Ventilation Flow (Electric
heat- Modulating SCR)
DD71 = UC210 DDC- Basic (No water or
electric heat)
DD72 = UC210 DDC- Basic (Water heat- N.C.
2-position)
DD73 = UC210 DDC- Basic (Water heatModulating)
DD74 = UC210 DDC- Basic (Electric heatStaged)
DD75 = UC210 DDC- Basic (Electric heatPWM)
DD76 = UC210 DDC Ventilation flow- cooling
only
DD77 = UC210 DDC- Basic (Water heat- N.O.
2-position)
DD79 = UC210 DDC- Flow Tracking (Cooling
only)
DD80 = UC210 DDC- Ventilation Flow (Water
heat- N.C. 2-position)
DD81 = UC210 DDC- Ventilation Flow
(Electric heat- Staged)
DD82 = UC210 DDC- Ventilation Flow (Water
heat- Modulating)
DD83 = UC210 DDC- Basic plus- Local
(Electric heat- PWM) Remote (Staged EH)
DD84 = UC210 DDC- Basic plus- Local
(Water heat- Modulating) Remote (WaterN.C. 2-position)
DD85 = UC210 DDC- Basic plus- Local
(Water heat- Modulating) Remote (WaterN.O. 2-position)
DD86 = UC210 DDC- Basic plus- Local
(Water heat- N.O. 2-position) Remote
(Water- Modulating)
Digit 3— Reheat
C = Cooling Only
E = Electric Heat
W = Hot Water Heat
Digit 4 — Development Sequence
F = Sixth
Digit 5, 6 — Primary Air Valve
04 = 4" inlet (225 cfm)
05 = 5" inlet (350 cfm)
06 = 6" inlet (500 cfm)
08 = 8" inlet (900 cfm)
10 = 10" inlet (1400 cfm)
12 = 12" inlet (2000 cfm
14 = 14" inlet (3000 cfm)
16 = 16" inlet (4000 cfm)
24 = 24" x 16" inlet (8000 cfm)
Digit 7, 8, 9— Not Used
000 = N/A
Digit 10, 11— Design Sequence
M0 = New Hot Water Coil
Digit 12, 13, 14, 15 — Controls
DD00 = Trane Actuator Only and Enclosure
DD01 = UCM4 Cooling Only Control
DD02 = UCM4 N.C. On/Off Hot Water
DD03 = UCM4 Prop Hot Water
DD04 = UCM4 Staged On/Off Elec Heat
DD05 = UCM4 Pulse Width MOD Elec Heat
DD07 = UCM4 N.O. On/Off Hot Water
DD11 = VV550 DDC- Controller, Cool Only
DD12 = VV550 DDC- Ctrl to operate N.C. On/
Off Water Valve
DD13 =VV550 DDC- Ctrl to operate Prop
Water Valve
DD14 = VV550 DDC- Ctrl On/Off Elec Heat
DD15 = VV550 DDC- Ctrl w/Pulse Width
Modulation
DD16 = VV550 DDC- Controller Ventilation
Flow
DD17 = VV550 DDC- Ctrl to Operate N.O.
On/Off Water Valve
DD19 = VV550 DDC- Controller with Flow
Tracking
DD20 = VV550 DDC- Vent Flow Control l to
Operate N.C. Water Valve
DD21 = VV550 DDC- Vent Flow w/ On/Off
Elec Heat
6
VAV-SVX08R-EN
Model Numbers
Digit 12, 13, 14, 15 — Controls
(continued)
Digit 21— Water Coil
Digit 27, 28, 29 — Electric Heat kW
DD87 = UC210 DDC- Basic plus- Local
(Water heat- N.C. 2-position) Remote
(Water- Modulating)
DD88 = UC210 DDC- Basic plus- Local
(Water heat- N.O. 2-position) Remote
(Water- N.O. 2-position)
DD89 = UC210 DDC- Basic plus- Local
(Water heat- N.C. 2-position) Remote
(Water- N.C. 2-position)
DD90 = UC210 DDC- Basic plus- Local
(Water heat- N.O. 2-position) Remote
(Water- N.C. 2-position)
DD91 = UC210 DDC- Basic plus- Local
(Water heat- N.C. 2-position) Remote
(Water- N.O. 2-position)
DD92 = UC210 DDC- Basic plus- Local
(Electric heat- Staged) Remote (Staged EH)
DD93 = UC210 Ventilation Flow (Water heatN.O. 2-position)
DD95 = UC210 Basic (Electric Heat
Modulating SCR)
DD96 = UC210 Basic plus- Local (Electric
heat-Modulating SCR) Remote (Staged EH)
DD97 = UC210 Ventilation Flow (Electric
heat-Modulating SCR)
ENCL = Shaft Only in Enclosure
FM00 = Other Actuator and Control
FM01 = Trane Supplied Actuator, Other Ctrl
N.C. = Normally-Closed
N.O. = Normally-Open
FM = Factory Installation of Customersupplied Controllers
0 = None
1 = 1 Row
2 = 2 Row
3 = 3 Row
4 = 4 Row
A = 1 Row Premium
B = 2 Row Premium
C = 3 Row Premium
D = 4 Row Premium
000 = None
010 = 1.0 kW
015 = 1.5 kW
460 = 46.0 kW
Digit 16 — Insulation
A = 1/2” Matte-faced
B = 1” Matte-faced
D = 1” Foil-faced
F = 1” Double Wall
G = 3/8” Closed-cell
Digit 17, 18— Not Used
00 = Not Applicable
Digit 19— Outlet Plenum (Slip-andDrive Connection
0 = None
A = 1 Outlet RH
B = 1 Outlet END
C = 1 Outlets, LH
D = 2 Outlets, 1RH, 1END
E = 2 Outlets, 1LH, 1END
F = 2 Outlets, 1RH, 1LH
H = 3 Outlets, 1LH, 1RH, 1END
J = 4 Outlets, 1LH, 1RH, 2END
Note: See unit drawings for outlet sizes/
damper information.
Digit 20— Not Used
0 = Not Applicable
VAV-SVX08R-EN
Digit 22— Electrical Connections
F = Able to Flip for LH/RH Connections (VCEF
Only)
L = Left, Airflow hits in face
R = Right, Airflow hits in face
0 = Opposite side connection, coil and control
(VCWF Only)
Note: VCCF/VCWF can be flipped in field for
opposite connections.
Notes:
•
0.5 to 8.0 kW in 1/2 kW
increments
•
8.0 to 18.0 kW in 1 kW
increments
•
18.0 to 46.0 kW in 2 kW
increments
Digit 30 — Electric Heat Stages
0 = None
1 = 1 Stage
2 = 2 Stages Equal
3 = 3 Stages Equal
Digit 31 — Electric Heat Contactors
Digit 23— Transformer
0 = None
1 = 120/24V, 50 VA
2 = 208/24V, 50 VA
3 = 240/24V, 50 VA
4 = 277/24V, 50 VA
5 = 480/24V, 50 VA
6 = 347/24V, 50 VA
7 = 380/24V, 50 VA
8 = 575/24V, 50 VA
Note: For VCEF units with transformers the
VA depends on the staging, control,
and contactor type (ranges are 50 VA
or 75 VA)
Digit 24 — Disconnect Switch
0 = None
W = With
Note: VCCF/VCWF— toggle disconnect.
VCEF-door interlocking power
disconnect.
0 = None
1 = 24V Magnetic
5 = 0–10Vdc SCR Heat; UC400/UC210
6 = 0–10Vdc SCR Heat; FMTD/ENCL/DD00
7 = 24V SSR (Solid State Relay)
Digit 32, 33— Not Used
00 = Not Applicable
Digit 34 — Actuator
0 = Standard
A = Spring Return, Normally Open
B = Spring Return, Normally Closed
C = Belimo™ Actuator
G = Trane Analog Actuator (UC210 or UC400
only)
Digit 35 — Sensor Options
Digit 25 — Power Fuse
0 = Standard, Wired
3 = Trane Air-Fi® Wireless Communications
Interface
0 = None
W = With
Digit 36 — Pre-wired Factory
Solutions
Digit 26 — Electric Heat Voltage
0 = None
A = 208/60/1
B = 208/60/3
C = 240/60/1
D = 277/60/1
E = 480/60/1
F = 480/60/3
G = 347/60/1
H = 575/60/3
J = 380/50/3
K = 120/60/1
0 = None
1 = Factory-mounted DTS
2 = HW Valve Harness
3 = Both DTS/HW Valve Harness
4 = Averaging DTS Factory-installed in Unit
(Required UC210/UC400 w/SCR Heat)
5 = Analog HW Valve, field provided
6 = Factory-mounted DTS and HWV Harness
7
Model Numbers
Digit 37 — Integral Attenuator with
Cam Lock Bottom Access
0 = None
1 = Attenuator and bottom access - left side
controls
2 = Attenuator and bottom access - right side
controls
3 =Attenuator and bottom access - left side
controls, right side water coil connections
4 = Attenuator and bottom access - right side
controls, left side water coil connections
Digit 38 —Piping Package
0 = None
A = 2–Way Automatic Balancing
B = 3–Way Automatic Balancing
C = 2-Way Standard Valve Only, Floating
Point Actuator
D = 3-Way Standard Valve Only, Floating
Point Actuator
E = 2-Way Standard Valve Piping Package,
Floating Point Actuator
F = 3-Way Standard Valve Piping Package,
Floating Point Actuator
Digit 39 — Water Valve
0 = None
1 = HW Valve 0.7 Cv
2 = HW Valve 2.7 Cv
5 = Analog HW Valve, field provided (UC210
or UC400 only)
6 = HW Valve, 1.7 Cv
7 = HW Valve, 5.0 Cv
Digit 40 — Flow Rate
0 = None
A = 0.5 gpm, 0.03 l/s
B = 1.0 gpm, 0.06 l/s
C = 1.5 gpm, 0.09 l/s
D = 2.0 gpm, 0.13 l/s
E = 2.5 gpm, 0.16 l/s
F = 3.0 gpm, 019 l/s
G = 3.5 gpm, 0.22 l/s
H = 4.0 gpm, 0.25 l/s
J = 4.5 gpm, 0.28 l/s
K = 5.0 gpm, 0.31 l/s
L = 5.5 gpm, 0.35 l/s
M = 6.0 gpm, 0.38 l/s
N = 6.5 gpm, 0.41 l/s
P = 7.0 gpm, 0.44 l/s
Q = 7.5 gpm, 0.47 l/s
R = 8.0 gpm, 0.50 l/s
S = 9.0 gpm, 0.57 l/s
T = 10.0 gpm, 0.63 l/s
U = 11.0 gpm, 0.69 l/s
V = 12.0 gpm, 0.76 l/s
Digit 41 — Air Leakage Class
0 = Standard Air Leakage
1 = Certified Ultra-Low Air Leakage
8
VAV-SVX08R-EN
Model Numbers
Dual-Duct VAV Units
Digit 1, 2, 3— Unit Type
Digit 17— Not Used
Digit 26 — Not Used
VDD = VariTrane™ Dual—Duct
0 = Not Applicable
0 = Not Applicable
Digit 4 — Development Sequence
Digit 18— Not Used
Digit 27 — Not Used
0 = Not Applicable
0 = Not Applicable
Digit 5, 6 — Primary Air Valve
Digit 19 — Outlet Plenum (Slip-andDrive Connection)
Digit 28 — Not Used
05 = 5" inlet (350 cfm)
06 = 6" inlet (500 cfm)
08 = 8" inlet (900 cfm)
10 = 10" inlet (1400 cfm)
12 = 12" inlet (2000 cfm
14 = 14" inlet (3000 cfm)
16 = 16" inlet (4000 cfm)
0 = None
A = 1 Outlet RH
B = 1 Outlet END
C = 1 Outlets, LH
D = 2 Outlets, 1RH, 1END
E = 2 Outlets, 1LH, 1END
F = 2 Outlets, 1RH, 1LH
G = 2 Outlets, 2END
H = 3 Outlets, 1LH, 1RH, 1END
J = 4 Outlets, 1LH, 1RH, 2END
0 = Not Applicable
Note: See unit drawings for outlet sizes/
damper information.
Digit 31 — Not Used
F = Sixth
Digit 7, 8 — Secondary Air Valve
05 = 5" inlet (350 cfm)
06 = 6" inlet (500 cfm)
08 = 8" inlet (900 cfm)
10 = 10" inlet (1400 cfm)
12 = 12" inlet (2000 cfm
14 = 14" inlet (3000 cfm)
16 = 16" inlet (4000 cfm)
Digit 20— Not Used
0 = Not Applicable
Digit 29 — Not Used
0 = Not Applicable
Digit 30— Not Used
0 = Not Applicable
0 = Not Applicable
Digit 32 — Not Used
0 = Not Applicable
Digit 9— Not Used
Digit 21— Not Used
0 = Not applicable
0 = Not Applicable
Digit 33 — Special Options
Digit 10, 11— Design Sequence
Digit 22— Not Used
0 = None
X = Varies, Factory Assigned
** = Factory Assigned
0 = Not Applicable
Digit 34 — Actuator
Digit 12, 13, 14, 15 — Controls
Digit 23 — Transformer
DD00 = Trane Actuator Only
DD01 = Dual UCM4.2 Cooling Only Control
DD08 = Dual UCM4.2 Constant Volume
DD11 = Dual VV550 DDC, Cooling Only
DD18 = Dual VV550 DDC, Constant Volume
DD41 = UC400 DDC Basic, No Water or
Electric Heat
DD48 = UC400 DDC Basic, Constant Volume
FM00 = Other Actuator and Control
FM01 = Trane Supplied Actuator, Other Ctrl
0 = None
1 = 120/24V, 50 VA
2 = 208/24V, 50 VA
3 = 240/24V, 50 VA
4 = 277/24V, 50 VA
5 = 480/24V, 50 VA
6 = 347/24V, 50 VA
7 = 575/24V, 50 VA
0 = Standard
A = Belimo™ Actuator
B = Trane Analog Actuator (UC400 only)
Digit 24— Disconnect Switch
Digit 36 — Duct Temperature Sensor
Digit 16 — Insulation
0 = None
W = With Toggle
0 = None
1 = With Duct Temperature Sensor
A = 1/2” Matte-faced
B = 1” Matte-faced
D = 1” Foil-faced
F = 1” Double Wall
G = 3/8” Closed-cell
VAV-SVX08R-EN
Digit 35 — Wireless Sensor
0 = Sensor/Receiver Standard
3 = Trane Air-Fi® Wireless Communication
Interface
Note: All sensors selected in accessories.
Digit 25 — Power Fuse
0 = None
W = With
9
Model Numbers
Fan-Powered VAV Units Model Number Descriptions
Digit 1, 2— Unit Type
Digit 12, 13, 14, 15 — Controls
Digit 12, 13, 14, 15 — Controls
(continued)
VP = VariTrane™ Fan-Powered Parallel
VS = VariTrane™ Fan-Powered Series
LP = VariTrane™ Fan-Powered Low Height
Parallel
LS = VariTrane™ Fan-Powered Low Height
Series
DD01 = Cooling Only Control
DD02 = N.C. On/Off Hot Water
DD03 = Prop Hot Water
DD04 = Staged On/Off Elec Heat
DD05 = Pulse Width Mod of Elect Heat
DD07 = N.O. On/Off Hot Water
DD11 = VV550 DDC- Controller, Cooling Only
DD12 = VV550 DDC- Control w/N.C. On/Off
HW Valve
DD13 = VV550 DDC- Control w/Prop. Hw
Valve
DD14 = VV550 DDC- Control On/Off Electric
Heat
DD15 = VVV550 DDC- Control w/Pulse Width
Modulation
DD17 = VVV550 DDC- Control w/N.O On/Off
HW Valve
DD41 = UC400 DDC- Basic (No water or
electric heat)
DD42 = UC400 DDC- Basic (Water heat- N.C.
2-position)
DD43 = UC400 DDC- Basic (Water heatModulating)
DD44 = UC400 DDC- Basic (Electric heatStaged)
DD45 = UC400 DDC- Basic (Electric heatPWM)
DD47 = UC400 DDC- Basic (Water heat- N.O.
2-position)
DD53 = UC400 DDC- Basic plus- Local
(Electric heat- PWM) Remote (Staged EH)
DD58 = UC400 DDC- Basic plus- Local
(Water heat- Modulating) Remote (WaterN.O. 2-position)
DD59 =UC400 DDC- Basic plus Local (Water
heat- Modulating) Remote (Water- N.C.
2-position)
DD60 = UC400 DDC- Basic Plus Local (Water
Heat- N.O. 2-position) Remote Water- N.C.
2-position)
DD61 = UC400 DDC- Basic plus- Local
(Water heat- N.C. 2-position) Remote
(Water- N.O. 2-position)
DD62 = UC400 DDC- Basic plus- Local
(Electric heat- Staged) Remote (Staged EH)
DD65 = UC400 Basic (Electric Heat
Modulating SCR)
DD66 = UC400 Basic plus- Local (Electric
heat-Modulating SCR) Remote (Staged EH)
DD71 = UC210 DDC- Basic (No water or
electric heat)
DD72 = UC210 DDC- Basic (Water heat- N.C.
2-position)
DD73 = UC400 DDC- Basic (Water heatModulating)
DD74 = UC210 DDC- Basic (Electric heatStaged)
DD75 = UC210 DDC- Basic (Electric heatPWM)
DD77 = UC210 DDC- Basic (Water heat- N.O.
2-position)
DD83 = UC210 DDC- Basic plus- Local
(Electric heat- PWM) Remote (Staged EH)
DD84 = UC210 DDC- Basic plus- Local
(Water heat- Modulating) Remote (WaterN.C. 2-position)
DD85 = UC210 DDC- Basic plus- Local
(Water heat- Modulating) Remote (WaterN.O. 2-position)
DD86 = UC210 DDC- Basic plus- Local
(Water heat- N.O. 2-position) Remote
(Water- Modulating)
DD87 = UC210 DDC- Basic plus- Local
(Water heat- N.C. 2-position) Remote
(Water- Modulating)
DD88 = UC210 DDC- Basic plus- Local
(Water heat- N.O. 2-position) Remote
(Water- N.O. 2-position)
DD89 = UC210 DDC-Basic plus- Local (Water
heat- N.C. 2-position) Remote (Water- N.C.
2-position)
DD90 = UC210 DDC- Basic plus- Local
(Water heat- N.O. 2-position) Remote
(Water- N.C. 2-position)
DD91 = UC210 DDC- Basic plus- Local
(Water heat- N.C. 2-position) Remote
(Water- N.O. 2-position)
DD92 = UC210 DDC- Basic plus- Local
(Electric heat- Staged) Remote (Staged)
DD95 = UC210 Basic (Electric Heat
Modulating SCR)
DD96 = UC210 Basic plus- Local (Electric
heat-Modulating SCR) Remote (Staged EH)
DD00 = Trane Actuator Only
ENCL = Shaft Only in Enclosure
FM00 = Other Actuator and Control
FM01 = Trane Supplied Actuator, Other Ctrl
Digit 3— Reheat
C = Cooling Only
E = Electric Heat
W = Hot Water Heat
Digit 4 — Development Sequence
F = Sixth
Digit 5, 6 — Primary Air Valve
04 = 4" inlet (225 cfm)
05 = 5" inlet (350 cfm)
06 = 6" inlet (500 cfm)
08 = 8" inlet (900 cfm)
10 = 10" inlet (1400 cfm)
12 = 12" inlet (2000 cfm
14 = 14" inlet (3000 cfm)
16 = 16" inlet (4000 cfm)
RT = 8" x 14" inlet (1800 cfm)
Note: 10, 12, 14, and 16 not available on low
height units.
Digit 7, 8— Secondary Air Valve Used
00 = N/A
Digit 9 — Fan
A = DS02 Fan (1300 nom cfm)
B = DS03 Fan (1950 nom cfm)
C = PS02 Fan (1160 nom cfm)
P = 02SQ Fan (500 nom cfm)
Q =03SQ Fan (1100 nom cfm)
R = 04SQ Fan (1350 nom cfm)
S = 05SQ Fan (1550 nom cfm)
T =06SQ Fan (1850 nom cfm)
U = 07SQ Fan (2000 nom cfm)
Digit 10, 11— Design Sequence
** = Factory Assigned
10
VAV-SVX08R-EN
Model Numbers
Digit 16 — Insulation
Digit 23— Transformer
Digit 31 — Electric Heat Contactors
A = 1/2” Matte-faced
B = 1” Matte-faced
D = 1” Foil-faced
F = 1” Double Wall
G = 3/8” Closed-cell
0 = Not Applicable
0 = None
1 = 24V Magnetic
5 = 0-10 Vdc SCR Heat; UC400
6 = 0-10 Vdc SCR Heat; FMTD/ENCL/DD00
7 = 24V SSR (Solid State Relay)
Digit 17— Motor Type
D = PSC Motor
E = High-efficiency Electronically
Commutated Motor (ECM)
F = Variable Speed High-efficiency
Electronically Commutated Motor (ECV)
Digit 18— Motor Voltage
1 = 115/60/1
2 = 277/60/1
3 = 347/60/1
4 = 208/60/1
5 = 230/50/1
Digit 19— Outlet Connection
1 = Flanged
2 = Slip–and-Drive Connection
Digit 20— Attenuator
Digit 24 — Disconnect Switch
0 = None
W = With
Note: Electric reheat w/door interlocking
power disconnect, cooling only and
water reheat w/toggle disconnect.
Digit 25 — Power Fuse
Digit 26 — Electric Heat Voltage
0 = None
A = 208/60/1
B = 208/60/3
C = 240/60/1
D = 277/60/1
E = 480/60/1
F = 480/60/3
G = 347/60/1
H = 575/60/3
J = 380/50/3
K = 120/60/1
Note: Digit K not available wit low height.
Digit 21— Water Coil
000 = None
010 = 1.0 kW
015 = 1.5 kW
460 = 46.0 kW
Digit 22— Electrical Connections
F = Flippable Left and Right Hand
L = Left, Airflow hits in face
R = Right, Airflow hits in face
W = Narrow Corridor LH, High Voltage, Inlet
Facing
X = Narrow Corridor RH, High Voltage, Inlet
Facing
Note: Digits W and X, fan-powered series
only.
VAV-SVX08R-EN
•
kW>10,208V, 3Ph, Low Height
•
kW>22,480V, 3Ph, Low Height
•
Voltage = 575V
Digit 32— Air Switch
0 = None
W = With
0 = None
B = Suppressor
T = Thinline Suppressor
0 = None
1 = 1 Row, Plenum Inlet Installed RH
2 = 2 Row, Plenum Inlet Installed RH
3 = 1 Row, Discharge Installed LH
4 = 1 Row, Discharge Installed RH
5 = 2 Row, Discharge Installed LH
6 = 2 Row, Discharge Installed RH
A = 1 Row Premium, Water Coil Inlet
B = 2 Row Premium, Water Coil Inlet
C = 1 Row Premium, Hot Coil on Discharge LH
D = 1 Row Premium, Hot Coil on Discharge
RH
E = 2 Row Premium, Hot Coil on Discharge LH
F = 2 Row Premium, Hot Coil on Discharge RH
Notes: SCR cannot be selected with the
following:
Digit 27, 28, 29— Electric Heat kW
Notes:
•
0.5 to 8.0 kW in 1/2 kW
increments
•
8.0 to 18.0 kW in 1 kW
increments
•
18.0 to 46.0 kW in 2 kW
increments
Digit 30 — Electric Heat Stages
0 = None
1 = 1 Stage
2 = 2 Stages Equal
3 = 3 Stages Equal
Note: Digit 3 not available with low height.
0 = Not Applicable
W = With
Digit 33— Not Used
0 = Not Applicable
Digit 34 — Actuator
0 = Standard
A = Belimo™ Actuator
G = Trane Analog Actuator (UC210 or UC400
only)
Digit 35 — Wireless Sensors
0 = None
3 = Trane Air-Fi® Wireless Communications
Interface
Note: All sensors selected in accessories.
Digit 36 — Pre-wired Factory
Solutions
0 = None
1 = Factory-mounted DTS
2 = HW Valve Harness
3 = Both DTS/HW Valve Harness
Digit 37 — Bottom Access
0 = None
W = Access Left Side Terminal Unit
Digit 38 —Piping Package
0 = None
A = 2–Way Automatic Balancing
B = 3–Way Automatic Balancing
C = 2-Way Standard Valve Only, Floating
Point Actuator
D = 3-Way Standard Valve Only, Floating
Point Actuator
E = 2-Way Standard Valve Piping Package,
Floating Point Actuator
F = 3-Way Standard Valve Piping Package,
Floating Point Actuator
11
Model Numbers
Digit 39 — Water Valve
0 = None
1 = HW Valve 0.7 Cv
2 = HW Valve 2.7 Cv
5 = Analog HW Valve, Field Provided (UC210
or UC400 only)
6 = HW Valve 1.7 Cv
7 = HW Valve 5.0 Cv
Digit 40 — Flow Rate
0 = None
A = 0.5 gpm, 0.03 l/s
B = 1.0 gpm, 0.06 l/s
C = 1.5 gpm, 0.09 l/s
D = 2.0 gpm, 0.13 l/s
E = 2.5 gpm, 0.16 l/s
F = 3.0 gpm, 019 l/s
G = 3.5 gpm, 0.22 l/s
H = 4.0 gpm, 0.25 l/s
J = 4.5 gpm, 0.28 l/s
K = 5.0 gpm, 0.31 l/s
L = 5.5 gpm, 0.35 l/s
M = 6.0 gpm, 0.38 l/s
N = 6.5 gpm, 0.41 l/s
P = 7.0 gpm, 0.44 l/s
Q = 7.5 gpm, 0.47 l/s
12
VAV-SVX08R-EN
Model Numbers
Chilled Water Sensible Cooling Terminal Units
Digit 1, 2— Unit Type
Digit 16 — Insulation
Digit 26 — Electric Heat Voltage
LD = Chilled Water Sensible Cooling Terminal
Units
A = 1/2” Matte-faced
B = 1” Matte-faced
D = 1” Foil-faced
F = 1” Double Wall
G = 3/8” Closed-cell
0 = None
A = 208/60/1
B = 208/60/3
C = 240/60/1
D = 277/60/1
E = 480/60/1
F = 480/60/3
Digit 3— Heating
C = Cooling Only
E = Electric Heat
W = Hot Water Heat
Digit 4 — Development Sequence
F = Sixth
Digit 17 — Motor Type
E = High-efficiency Motor (ECM)
F = Variable Speed High-efficiency
Electronically Commutated Motor (ECV)
Digit 18 — Motor Voltage
Digit 5, 6 — Primary Air Valve
04 = 4" inlet (225 max cfm)
05 = 5" inlet (350 max cfm)
06 = 6" inlet (500 max cfm)
08 = 8" inlet (900 max cfm)
RT = 8x14” inlet (1800 max cfm)
Digit 7, 8— Secondary Air Valve
1 = 115/60/1
2 = 277/60/1
Digit 27, 28, 29 — Electric Heat kW
000 = None
005 = 0.5 kW
010 = 1.0 kW
015 = 1.5 kW
200 = 20.0 kW
Notes:
Digit 19 — Outlet Connection
•
0.5 to 8.0 kW in 1/2 kW
increments
1 = Flanged
2 = Slip–and-Drive Connection
•
8.0 to 18.0 kW in 1 kW
increments
Digit 20 — Attenuator
•
18.0 to 20.0 kW in 2 kW
increments
00 = N/A
0 = No Attenuator
Digit 9 — Fan
Digit 21 — Water Coil
B = DS02 Fan (1300 max cfm)
Digit 10, 11— Design Sequence
** = Factory Assigned
Digit 12, 13, 14, 15 — Controls
DD00 = Trane Actuator Only
ENCL = Shaft Only in Enclosure
FM00 = Other Actuator and Control
FM01 = Trane Supplied Actuator, Other
Control
SC41 = UC400 DDC- Sensible Cooling- Basic
(No water or electric heat)
SC43 = UC400 DDC- Sensible Cooling- Basic
(Water heat, Modulating)
SC44 = UC400 DDC- Sensible Cooling- Basic
(Electric heat- Staged)
SC62 = UC400 DDC- Sensible Cooling- Basic
plus Local (Electric heat- Staged), Remote
(Staged)
SC65 = UC400 DDC- Sensible Cooling- Basic
(Electric Heat Modulating SCR)
SC66 = UC400 DDC- Sensible Cooling- Basic
plus Local (Electric heat- Modulating SCR)
Remote (Staged)
0 = None
3 = 1 Row, Discharge Installed, LH
4 = 1 Row, Discharge Installed, RH
5 = 2 Row, Discharge Installed, LH
6 = 2 Row, Discharge Installed, RH
C = 1 Row Premium, Hot Coil on Discharge,
LH
D = 1 Row Premium, Hot Coil on Discharge,
RH
E = 2 Row Premium, Hot Coil on Discharge,
LH
F = 2 Row Premium, Hot Coil on Discharge,
RH
Digit 30 — Electric Heat Stages
0 = None
1 = 1 Stage
2 = 2 Stages Equal
Digit 31 — Electric Heat Contactors
0 = None
1 = 24V Magnetic
5 = SCR Heat, UC400
6 = SCR Heat, FM00/ENCL/DD00
Digit 32 — Airflow Switch
0 = None
W = With
Digit 22 — Control, Heat Connections
Digit 33 — Not Used
F = Flippable Left and Right Hand
0 = Not Applicable
Digit 23 — Unit Filter
Digit 34 — Actuator
0 = Construction Throw-away Filter
8 = MERV 8 Filter
0 = Standard
A = Belimo™ Actuator
Digit 24 — Disconnect Switch
Digit 35 — Wireless Sensors
0 = None
W = With
0 = None
3 = Air-Fi® Wireless Communications
Digit 25 — Power Fuse
Note: All sensors selected in accessories.
0 = None
W = With
VAV-SVX08R-EN
13
Model Numbers
Digit 36 — Pre-wired Factory
Solutions
Digit 43 — Chilled Water Piping
Package
0 = None
1 = Discharge Temperature Sensor (DTS)
2 = Hot Water (HW) Valve Harness
3 = DTS and HW Valve Harness
7 = Chilled Water (CW) Valve Harness
8 = CW and HW Valve Harness
B = DTS with CW Valve Harness
C = DTS with CW and HW Valve Harness
0 = None
A = 2–Way Automatic Balancing
B = 3–Way Automatic Balancing
C = 2-Way Standard Valve Only, Floating
Point Actuator
D = 3-Way Standard Valve Only, Floating
Point Actuator
E = 2-Way Standard Valve Piping Package,
Floating Point Actuator
F = 3-Way Standard Valve Piping Package,
Floating Point Actuator
Digit 37 — Not Used
0 = Not Applicable
Digit 44 — Chilled Water Valve
Digit 38 — Hot Water Piping Package
0 = None
A = 2–Way Automatic Balancing
B = 3–Way Automatic Balancing
C = 2-Way Standard Valve Only, Floating
Point Actuator
D = 3-Way Standard Valve Only, Floating
Point Actuator
E = 2-Way Standard Valve Piping Package,
Floating Point Actuator
F = 3-Way Standard Valve Piping Package,
Floating Point Actuator
Digit 39 — Hot Water Valve
0 = None
1 = HW Valve, 0.7 Cv
2 = HW Valve, 2.7 Cv
5 = Analog, HW Valve, field provided (UC210
or UC400 only)
6 = HW Valve, 1.7 Cv
7 = HW Valve, 5.0 Cv
Digit 40 — Hot Water Flow Rate
0 = None (No Flow Rate)
A = 0.5 gpm (0.03 L/s)
B = 1 gpm (0.06 L/s)
C = 1.5 gpm (0.09 L/s)
D = 2 gpm (0.13 L/s)
E = 2.5 gpm (0.16 L/s)
F = 3 gpm (0.19 L/s)
G = 3.5 gpm (0.22 L/s)
H = 4 gpm (0.25 L/s)
J = 4.5 gpm (0.28 L/s)
K = 5 gpm (0.32 L/s)
L = 5.5 gpm (0.35 L/s)
M = 6 gpm (0.38 L/s)
N = 6.5 gpm (0.41 L/s)
P = 7 gpm (0.44 L/s)
Q = 7.5 gpm (0.47 L/s)
0 = None
1 = CW Valve, 0.7 Cv
2 = CW Valve, 2.7 Cv
5 = Analog CW Valve, Field-Provided (UC400
Only)
6 = CW Valve, 1.7 Cv
7 = CW Valve, 5.0 Cv
Digit 45 — Chilled Water Flow Rate
0 = None (No Flow Rate)
A = 0.5 gpm (0.03 L/s)
B = 1 gpm (0.06 L/s)
C = 1.5 gpm (0.09 L/s)
D = 2 gpm (0.13 L/s)
E = 2.5 gpm (0.16 L/s)
F = 3 gpm (0.19 L/s)
G = 3.5 gpm (0.22 L/s)
H = 4 gpm (0.25 L/s)
J = 4.5 gpm (0.28 L/s)
K = 5 gpm (0.32 L/s)
L = 5.5 gpm (0.35 L/s)
M = 6 gpm (0.38 L/s)
N = 6.5 gpm (0.41 L/s)
P = 7 gpm (0.44 L/s)
Q = 7.5 gpm (0.47 L/s)
R = 8.0 gpm (0.50 L/s)
Digit 41 — Sensible Cooling Coil
2 = 2–Row Standard Cooling Coil
4 = 4–Row Standard Cooling Coil
6 = 6–Row Standard Cooling Coil
Digit 42 — Chilled Water Coil
Connections
D = Cooling Coil Connections at Unit
Discharge End
V = Cooling Coil Connections at Air Valve End
14
VAV-SVX08R-EN
Unit Information
Single Duct VAV Units
Typical Single Duct VAV Units
The basic unit consists of a sheet metal casing with an
air valve, which is used to modulate the air being
delivered into the occupied zone. The unit is designed
to modulate either cooling or heating air between 40°F
and 140°F (4.44°C and 60°C). Air enters the air valve
through the round or rectangular inlet and exits into
the sheet metal casing to be distributed to the zone
either through integral round outlets in the casing or
through rectangular duct attached to the discharge of
the unit.
Figure 1. Typical single duct unit; VCCF VCWF, VCEF
The basic unit can also be ordered with factorymounted electric or hot water heating coils attached to
the discharge.
These re-heat units are used primarily to reheat air-tozone temperature when the load in the occupied space
is low.
Primary air is modulated through the VariTrane™ air
valve by rotating the damper blade. All air valves have
a round/rectangular inlet for easy fit-up with incoming
duct work.
VAV-SVX08R-EN
15
Unit Information
Dual-Duct VAV Units
Dual-duct units provide two air valves: one as heating
primary air and the other as cooling primary air. Both
discharge into the common outlet, which leads to the
zone being controlled. See Figure 2, p. 16.
Units are provided with a slip and drive rectangular
duct connection or can be ordered with integral outlet
plenum.
Sequencing of hot and cold air valve is dependent on
job requirements. One typical control is valves working
in conjunction to respond to zone temperature.
Fan-Powered/Fan-Powered LowHeight VAV Units
VariTrane™ fan-powered and low-height fan-powered
units can be either parallel or series, with or without reheat. Refer to the following figures.
Typical Fan-powered Units
Figure 3. Parallel fan-powered terminal unit (top) and
series fan-powered terminal units (bottom)
When the cooling valve becomes fully closed or
reaches a specified minimum, the heating valve will
begin to modulate or vice versa. The typical result is
that air flowing to the zone varies from maximum
down to a minimum and back up to maximum as load
varies and controls would cause one air valve to close
and the other to open.
Another typical application is when the unit provides a
constant volume to the zone. When the zone sensor is
tied directly to the heating valve, it will modulate the
heating valve according to the zone temperature.
When the heating valve is fully closed or there is a call
for cooling in the zone, the cooling valve will be at
constant supply. As the space becomes too cool, the
heating valve will modulate open, decreasing the
cooling valve flow. The typical result is that the air
flowing into the zone stays at a constant flow whether
the unit is heating or cooling.
Figure 4. Low height series: LSCF (top) and low
height series: LSWF (bottom)
Factory-installed Trane unit controls available include;
•
•
•
UC400 — one required per unit
VV550 — two required per unit
UCM — two required per unit
Figure 2. Typical dual-duct unit; VDDF
16
VAV-SVX08R-EN
Unit Information
Figure 5. Low height series: LSEF (top) and low
height parallel: LPCF (bottom)
fan is turned on as the first stage of heat. The fan
delivers plenum air from above the occupied space to
the unit outlet, which is mixed with primary air and
delivered to the occupied space.
N o t e : Either the fan, the air valve, or both can deliver
airflow into the occupied space. In order to
prevent primary airflow from exiting through the
fan when the fan is not running on a parallel unit,
a back draft damper is provided. When the fan is
not running, the efficiency of this system is the
same as a standard single-duct VAV unit.
Typically, the control systems applied to parallel units
cause the air valve to close to zero or a minimum flow
before the fan is activated. After the fan is activated, the
optional heat will be activated upon further reduction
in zone temperature. Therefore, minimal primary air is
mixed with the heated air.
Figure 6. Low height parallel: LPWF (top) and low
height parallel: LPEF (bottom)
VariTrane™ fan-powered unit fan sizes 02SQ–05SQ,
DS02, PS02 and DS03 were performance tested at .12
in. w.g. and sizes 06SQ and 07SQ were tested at .15 in.
w.g. Units are not designed to operate without ducts
and below these tested static pressures.
N o t e : Fan-powered units are available with rectangular
discharge connection only. The optional heater
is mounted on the discharge of the unit. Hot
water coils are connected to either the plenum
inlet or on the discharge on parallel units, and to
the discharge of series units.
Chilled Water Sensible Cooling
Terminal Units
Chilled water sensible cooling terminal units are
available with or without re-heat. Refer to the following
figures.
Figure 7. Chilled water sensible cooling unit
The fan on a series unit runs continuously whenever
the main air handler unit is in operation. There are
three (3) methods to start the fan: 1) remotely, 2) by a
duct pressure switch, or 3) by a combination of both.
The particular fan control method may vary from unit
to unit, depending upon job needs.
Typically, heater is off while air valve modulates
primary air and responds to zone temperature. If zone
temperature decreases to the point where a decrease in
primary air will not maintain the desired temperature,
the re-heat will be activated to increase the
temperature of the discharge air.
On a parallel unit, the VariTrane™ air valve delivers
primary cooling air to the unit outlet. When the space
temperature decreases beyond air valve control, the
VAV-SVX08R-EN
17
Unit Information
Figure 8. Chilled water sensible cooling unit with hot
water coil
Figure 9. Chilled water sensible cooling unit with
electric heat
The function of the Trane chilled water sensible cooling
terminal units is a little different than traditional VAV
18
Terminal Units. These terminal units are part of a
s y s t e m that uses a dedicated outdoor-air unit to
distribute outdoor air to an air valve on each terminal
unit to meet the ventilation requirements of the zone.
Each terminal unit is also equipped with a cooling coil
mounted on the plenum inlet. Recirculated air from the
plenum (or directly from the occupied space) is drawn
in through this cooling coil by the local fan. This cooled
air is then mixed with the conditioned (cooled,
dehumidified, heated, or humidified) outdoor air from
the dedicated OA unit, and distributed through the
downstream ductwork to the zone.
In most applications, the water supplied to this local
cooling coil is controlled to a temperature above the
dew point in the zone. This avoids moisture in the air
from condensing on the coil, so it operates dry and
provides only sensible cooling. All the
dehumidification must then be provided by the
dedicated outdoor-air unit. Trane chilled water sensible
cooling terminal units are built with a drip pan located
beneath the cooling coil, with a moisture sensor
installed in it, to detect and prevent any moisture from
getting on the ceiling beneath the units or into the
occupied space below. These terminal units can be
configured with either a hot water coil or electric heater
mounted at the unit discharge.
VAV-SVX08R-EN
Unit Installation
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge
capacitors before servicing could result in death or
serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper
lockout/tagout procedures to ensure the power
cannot be inadvertently energized. For variable
frequency drives or other energy storing
components provided by Trane or others, refer to
the appropriate manufacturer’s literature for
allowable waiting periods for discharge of
capacitors. Verify with a CAT III or IV voltmeter
rated per NFPA 70E that all capacitors have
discharged.
WARNING
Proper Structural Support Required!
Failure to ensure proper structural ceiling support
could result in unit falling from its location which
could result in death or serious injury.
Ceiling structure must be strong enough to
support the weight of the unit and any
accessories. If unsure, check with a structural
engineer.
Due to their weight, the VAV terminal units should be
suspended from the uppermost ceiling, independent of
the false ceiling grid. In fact, VAV terminal units are
primarily designed for installation in the plenum space
between the upper most ceiling and the false ceiling
grid below it. See “Weights,” p. 28 for unit weights.
Suspension devices are to be supplied by the installer.
Units must be installed level and upright. Failure to
level the unit properly may prevent proper operation of
the controls and/or terminal unit. Units are not
designed to be installed vertically. Consequently, this
will also void the U.L. ratings and any warranty on the
unit.
Single-Duct VAV Units
Figure 10.
Single-duct hanging recommendations
Depending upon the size and weight of the single-duct
unit, it may be capable of being supported by the
ductwork that is connected to it. No hanger brackets
are provided on these units since the unit should be
supported by means of a hanger strap. The hanger
strap should be secured directly to the unit casing as
shown above.
•
For cooling only single-duct units or single-duct
units with hot water coil, the unit may be rotated
180° for opposite side connections.
•
For units with electric heat, the unit can be flipped
to either RH or LH connection orientation if model
number digit 22 Electrical Connections = F.
Dual-Duct VAV Units
Dual-duct units should be supported by either hanger
straps or by using a threaded rod in conjunction with
the hanger brackets that are provided on the unit.
Figure 11.
Dual-duct hanger bracket locations
B
C
AIR
VALVE
AIR
VALVE
COOLING
HEATING
A
TOP VIEW
VAV-SVX08R-EN
19
Unit Installation
Fan-Powered VAV Units and
Chilled Water Sensible Cooling
Terminal Units
Table 1. Dual duct VAV unit hanger location
dimensions
A
Inlet
Size
(in)
B
C
in
mm
in
mm
in
mm
5 thru
10
23.15
588
25.25
641
1.38
35
12 thru
16
23.15
588
37.25
946
1.38
35
Fan-powered (standard and low-height) and chilled
water sensible cooling terminal units should be
supported by either hanger straps or by using a
threaded rod in conjunction with the hanger brackets
that are provided on the unit. Care should be exercised
to insure that the hanging straps do not block the side
access panel. Refer to the following figures.
Bracket Locations — Fan Powered
Figure 12.
Parallel hanger bracket location sizes
B
Primary
Airflow
Flow Ring
tubing
B
Primary
Airflow
OPTIONAL
SUPPRESSOR
Flow Ring
tubing
OPTIONAL
SUPPRESSOR
Air
Valve
Air
Valve
C
A
A
Terminal Box
D
Airflow
Discharge Outlet
Heater
Water Coil
Airflow
Discharge Outlet
43.546
(1106 mm)
Table 2. Parallel hanger bracket location dimensions
A
B
C
D
Fan Size
in.
mm
in.
mm
in.
mm
in.
mm
02SQ
26.75
679
38.95
989
28.95
735
37.10
942
03SQ, 04SQ, 05SQ
29.75
756
38.95
989
31.45
799
39.70
1008
06SQ, 07SQ
36.75
933
38.95
989
38.95
989
47.10
1196
20
VAV-SVX08R-EN
Unit Installation
Figure 13.
Series hanger bracket locations
A
A
Flow Ring
tubing
Flow Ring
tubing
Air
Valve
Air
Valve
B
SU OP
PP TIO
RE N
SS AL
O
R
SU OP
PP TIO
RE N
SS AL
O
R
B
G
1.625”
(41 mm)
Water Coil
Electric Heater
H
1.625”
(41 mm)
F
Table 3. Series hanger bracket location dimensions
A
Fan Size
B
in.
mm
in.
mm
02SQ
18.75
476
41.2
1041
03SQ, 04SQ
20.75
527
41.2
1041
05SQ
26.75
679
41.2
1041
06SQ, 07SQ
27.25
692
41.2
1041
Table 4. Series hanger bracket location dimensions — electric heat only
F
G
H
Fan Size
in.
mm
in.
mm
in.
mm
02SQ
20.13
511
53.75
1365
19.0
483
03SQ, 04SQ
23.88
606
59.75
1517
19.0
483
05SQ
28.97
736
59.75
1517
19.0
483
06SQ, 07SQ
29.88
759
58.25
1479
17.5
445
VAV-SVX08R-EN
21
Unit Installation
Figure 14.
Low-height parallel DS02/PS02
39.1
[993]
39.1
[993]
Primary Airflow
Primary Airflow
Airflow Plenum
Inlet
Airflow Plenum
Inlet
34.3
[871]
34.3
[871]
34.3
[871]
34.3
[871]
Water Coil
Airflow Discharge
Outlet
Airflow Discharge
Outlet
39.1
[993]
39.1
[993]
39.1
[993]
0.8
[20]
Primary Airflow
Airflow Plenum
Inlet
34.3
[871]
56.3
[1430]
Optional Electric
Hetaer
Airflow Discharge
Outlet
37.9
[963]
22
VAV-SVX08R-EN
Unit Installation
Figure 15.
Low-height series DS02/PS02/DS03 w/hot water or electric heat
32.3
[821]
32.3
[821]
Primary Airflow
Primary Airflow
Airflow Plenum
Inlet
Airflow Plenum
Inlet
41.2
[1047]
41.2
[1047]
61.2
[1555]
Water Coil
Airflow
Discharge Outlet
Optional Electric
Heater
2.0
[51]
VAV-SVX08R-EN
Airflow Discharge
Outlet
23
Unit Installation
Bracket Locations
Chilled Water Sensible Cooling Terminal
Units
Figure 16. Bracket locations — cooling only unit, and
unit with hot water coil
Duct Connections
All VariTrane™ units should be provided with a
minimum of 1.5-duct diameters of straight duct prior to
the inlet of the unit. It is recommended that at least 48
inches of straight duct be provided from the discharge
of the units prior to any take-offs or transitions.
Primary Airflow
I m p o r t a n t : This is a requirement for electric heat fanpowered units used in applications with
100% downward discharge.
In order to maintain good air distribution
over the elements and not create
turbulence which could cause a limit cutout
there should be four feet of ductwork,
consistent of the discharge dimensions of
the heater. downstream of the reheat coil
prior to any diffuser takeoffs for
VariTrane™ electric coils.
Airflow
Plenum Inlet
41,2 [1045]
1. After all connections are made, check that the entire
ductwork system is airtight. In some high-pressure
systems, duct sealer may be necessary.
N o t e : All inlet duct on the VAV boxes are sized
approximately 0.125 inches smaller in
diameter than the nominal size in order to
allow the incoming duct to slide over the inlet
of the VAV box.
Hot Water Coil
(not present on cooling-only units)
Airflow
Discharge
Outlet
2. Provide insulation around the entire inlet collar (all
the way to the unit casing).
27,0 [685]
Figure 17.
Bracket locations — electric heat unit
Primary Airflow
N o t e : Use caution not to damage the flow tubes
when making ductwork connections or
insulating.
3. Cut slits in the insulation for the flow tubes and
secure with duct tape.
4. If the unit is to be installed in a location with high
humidity, external insulation around the heating
coil should be installed as required.
Airflow
Plenum Inlet
Water Coil Connections
41,2
[1045]
61,2 [1553]
Airflow
Discharge
Outlet
N o t e s : The following coils have 0.375 inches OD water
coil piping connections.
•
Single Duct 1-row coils (inlet sizes 05, 05, 06,
08 or 10 only)
•
Low Height Parallel Inlet 1-row
•
Low Height Parallel Discharge 1-row
All others require a 0.875 inches OD water coil
piping connections.
1. If necessary, you can change the coil connection
from left-handed to right-handed (and vice-versa)
by disconnecting the coil from the unit and rotating
the coil like a steering wheel 180°.
N o t e : The exception is that the coil connection
cannot be changed on parallel fan powered
unit with hot water coil on plenum inlet.
2,1 [53]
24
24,9 [631]
2. Use port at the bottom for inlet and top for outlet on
VAV-SVX08R-EN
Unit Installation
single row coils. For multi-row coils, always plumb
in counter flow orientation.
damage. Return damage or defective products.
•
Water inlet is always on the airflow downstream
side of the hot water coil.
•
Cutter to release zip tie
•
Water outlet is always on the upstream side of
the hot water coil.
•
DVM (Digital Volt ohm Meter)
•
Appropriate screw driver for mounting screws
•
Appropriate drill and drill bit for mounting screws
3. Care should be taken to properly support the water
coil piping connections while connecting the
adjoining pipe.
4. It is recommended that piping to the water coil
should be done after field-mounted controls,
external insulation, and ductwork connections have
been completed.
I m p o r t a n t : Do not connect water valve or pipe
extensions to the water coil connections
unless supported.
Tools required for installation:
Notes:
•
Installer must be a qualified, experienced
technician.
•
Cut loose harness, verify location.
•
Avoid location where excessive vibration,
moisture, corrosive fumes or vapors are
present.
Discharge Duct Temperature
Sensor Installation
1. Determine the sensor mounting location on the
duct. The sensing element is located within 1 inch
(25mm) of the end of the sensing probe, and it
should be located in the air stream typical of the
temperature requiring sensing.
Note: This process is to be used for control
sequences that involve Discharge Air
Temperature (DAT) control.
2. Use the mounting plate supplied as a template (or
refer to Figure 18, p. 25 for duct mounting
dimensions) for mounting hole location.
Several Tracer® UC210/UC400 control sequences
perform direct DAT control of the VAV unit when both
modulating unit heat and modulating ECM fan are
present or when modulating unit heat is present on a
non-fan-powered VAV unit. Supported modulating unit
heat options include modulating hot-water and SCRcontrolled electric heat. In these Tracer® UC210/UC400
control sequences, the DAT is a control input to the unit
controller.
Figure 18.
Mounting dimensions
N o t e : Optional factory mounted discharge duct
temperature sensors available with modulating
unit heat control.
I m p o r t a n t : To ensure good control of the DAT and
overall level of heat being supplied to the
zone, it’s critical to locate the DAT sensor in
a location in the downstream ductwork that
is not too close to the heating water or
electric coils.
1. Locate mounting location for DAT sensor a
minimum of 1.5 equivalent duct diameters
downstream of the heating coils and midway
between top and bottom on the side of the
ductwork.
2. Mount the DAT sensor using the instructions
provided at the end of this manual.
3. If not already factory wired to unit controller, wire
DAT sensor to unit controller using unit schematic.
Electronic Duct Temperature
Sensor Installation
Visually inspect the sensor unit and harness for
VAV-SVX08R-EN
3. Mount the sensor to the duct using (2) #8–1/6 x 1/2–
in sheet metal screws.
25
Unit Installation
Chilled Water Sensible Cooling
Terminal Units Moisture Sensor
Installation
In most applications, the water supplied to this local
cooling coil is controlled to a temperature above the
dew point in the zone. This avoids moisture in the air
from condensing on the coil, so it operates dry and
provides only sensible cooling. All dehumidification
must then be provided by the dedicated outdoor-air
unit. Trane chilled water sensible cooling terminal units
are built with a drip pan located beneath and above the
cooling coil, with a moisture sensor installed, to detect
and prevent any moisture from getting on the ceiling
beneath the units or into the occupied space below.
Sensible cooling units are designed so that the unit can
be flipped 180 degrees for right and left hand
orientation. They are configured as left hand from the
factory with a moisture sensor installed to a bracket on
the bottom of the drip pan. If installed as a right hand
unit the moisture sensor will need to be moved to the
bracket provided (shown in the following figure) so that
the moisture sensor is on the bottom of the unit for
proper moisture detection.
Figure 19. Moisture sensor installation and additional
bracket shown in cooling coil drip pan
side of the water coil. All other single-duct and dualduct units are provided without access, as all
functioning components are external to the unit.
•
Fan-powered terminals are provided with a sliding
side access.
•
Low-height terminal units have a removable
bottom panel.
Clearances
For proper service, it is recommended that at least 3
inches” of side clearance be provided to service and
access single-duct and dual-duct terminals units.
•
Fan-powered VAV units have a plenum inlet that
must be clear of obstructions. Allow at least 36
inches of clearance in front of the side access and
plenum opening.
•
Low-height fan-powered terminals require the
same plenum clearance requirement that applies to
the standard fan-powered units. However the
access to the internal components is located on the
bottom of the unit.
•
Fan-powered VAV units with Suppressor attenuator
requires at least 4.5 inches (6 inches preferred)
clearance above the plenum opening.
•
Fan-powered VAV units with Thinline Suppressor
attenuator requires at least 4.5 inches (6 inches
preferred) clearance at plenum openings.
It is also recommended that 6 inches of clearance be
provided to the top and bottom of all the units.
N o t e : The minimum clearance for controls and heater
controls should be 36 inches for all models
except units with 575-volt electric heaters, which
require 48 inches of clearance. NEC™ and/or
local codes override all clearance requirements.
Mounting Actuator
I m p o r t a n t : When installing or replacing the actuator
tighten the actuator set screw per the
manufacturer’s instructions. Failure to
follow the manufacturer’s specifications
may result in unit malfunction.
Trane offers a factory-mounted actuator with a 90second drive time. The actuator drives 1° per second. A
field-installed actuator may be used if desired. The
actuator shaft has a 0.5 inch diameter and is designed
to travel clockwise to close the damper and counterclockwise to open the damper. There is an indicator on
the end of the actuator shaft that can be used to
determine the position of the damper.
Stand-alone Units
Unit Accessibility
•
26
Single-duct and dual-duct units provided with hot
water reheat have an access panel located on the
Stand-alone UCM 4.2
When there is no communication to the UCM control
and the unit is in the stand-alone mode the control
VAV-SVX08R-EN
Unit Installation
action is determined by the auxiliary temperature
sensor located on TB3-5 and TB3-6 terminals on the
UCM board. In order for the auxiliary sensor to
determine the control action (heat, cool) it must be
located in the supply duct, upstream of the VAV unit.
The auxiliary temperature is then compared to the zone
temperature. If the supply air temperature is 10
degrees above the zone temperature, then the control
action will be heat. If the supply air temperature is less
than or equal to the zone temperature, then the control
action will be cool. If the supply air temperature is
between the zone temperature and the zone
temperature + 10ºF (5.5°C) [zone temperature < supply
air temperature < zone temperature + 10ºF] (5.5°C), the
control action remains the same and the UCM controls
to the minimum flow set point. If an auxiliary sensor is
not installed the UCM will retain the last control action
in effect.
Stand-alone VV550 LonTalk Control
When there is no communication to the VV550 control
and the unit is in the stand-alone mode the control
action is determined by the auxiliary temperature
sensor located on TB3-5 and TB3-6 terminals on the
VV550 board. The control must also be configured
through the Inputs Tab of Analog Input 4 as Primary
Supply Air Sensor. In order for the auxiliary sensor to
determine the control action (heat, cool) it must be
located in the supply duct, upstream of the VAV unit.
The auxiliary temperature is then compared to the zone
temperature. If the supply air temperature is 10
degrees above the zone temperature, then the control
action will be heat. If the supply air temperature is less
than or equal to the zone temperature, then the control
action will be cool. If the supply air temperature is
between the zone temperature and the zone
temperature + 10ºF (5.5°C) [zone temperature < supply
air temperature < zone temperature + 10ºF] (5.5°C), the
control action remains the same and the UCM controls
to the minimum flow set point. If an auxiliary sensor is
not installed the UCM will retain the last control action
in effect.
Stand-alone UC400
When there is no communication to the UC400 control
and the unit is in the stand-alone mode the control
action is determined by the auxiliary temperature
sensor located on AI5 terminals on the UC400 control.
This input may have to be changed from AI4 (Discharge
Air Input) as wired from the factory. In order for the
auxiliary temperature sensor to determine the control
action (heat, cool) it must be located in the supply duct,
upstream of the VAV unit. The auxiliary temperature is
then compared to the zone temperature. If the supply
air temperature is 10°F above the zone temperature,
then the control action will be heat. If the supply air
temperature is less than or equal to the zone
temperature, then the control action will be cool. If the
supply air temperature is between the zone
VAV-SVX08R-EN
temperature and the zone temperature +10°F (5.5°C)
[zone temperature < supply air temperature < zone
temperature +10°F] (5.5°C), the control action remains
the same and the UC400 controls to the minimum flow
set point. If an auxiliary sensor is not installed the
UC400 will retain the last control action in effect.
Stand-alone UC210
When there is no communication to the UC210 control
and the unit is in the stand-alone mode the control
action is determined by the auxiliary temperature
sensor located on AI3 terminals on the UC210 control.
From the factory, this input is configured for discharge
air temperature and needs to be field reconfigured as
supply air temperature using Tracer® TU. In order for
the auxiliary temperature sensor that is configured for
supply air temperature to determine the control action
(heat, cool) it must be located in the supply duct,
upstream of the VAV unit. The supply air temperature
is then compared to the zone temperature. If the supply
air temperature is 10°F above the zone temperature,
then the control action will be heat. If the supply air
temperature is less than or equal to the zone
temperature, then the control action will be cool. If the
supply air temperature is between the zone
temperature and the zone temperature +10°F (5.5°C)
[zone temperature < supply air temperature < zone
temperature +10°F] (5.5°C), the control action remains
the same and the UC210 controls to the minimum flow
set point. If an auxiliary temperature sensor is not
installed and configured for supply air temperature, the
UC210 will retain the last control action in effect.
Bottom Access
An optional bottom access can be provided in the
casing of fan powered series or parallel terminal unit.
The 22-gauge door is lined with 1 inch, 26-gauge, dual
wall insulation and thermal lined with 1 inch – 1 lb.
density fiberglass insulation with a 3.85 R-value.
Each door includes 1 to 6 cam locks that are used to
secure the door to the casing.
The cam lock engages a metal encapsulated frame on
the unit that encloses the unit insulation to prevent air
erosion.
The cam lock engagements are interlocked using a flat
head screwdriver. Once unlocked, the entire door
assembly can be removed for access.
Figure 20.
Bottom access
27
Unit Installation
Weights
Table 5. Single-duct units— lb/kg
Single Wall
Unit Size
VCCF
VCEF
4
16/7
5
16/7
6
VCCF
VCEF
1–Row
2–Row
3–Row
4–Row
38/17
21/10
22/10
23/11
24/11
19/9
38/17
21/10
22/10
23/11
24/11
19/9
16/7
38/17
21/10
22/10
22/10
24/11
8
16/7
38/17
21/10
24/11
24/11
10
22/10
46/21
29/13
32/15
12
27/12
52/24
37/17
40/18
14
32/15
60/27
44/20
16
35/16
69/31
24
52/24
84/38
Table 6.
28
Dual Wall
VCWF
VCWF
1–Row
2–Row
3–Row
4–Row
48/22
24/11
25/11
26/12
27/12
48/22
24/11
25/11
26/12
27/12
19/9
48/22
24/11
25/11
25/11
27/12
26/12
20/9
49/22
25/11
28/13
28/13
30/14
32/15
36/16
27/12
60/27
34/15
37/17
37/17
41/19
41/19
45/20
34/15
68/31
43/20
47/21
48/22
52/24
48/22
51/23
55/25
41/19
80/36
53/24
57/26
60/27
64/29
49/22
54/24
56/25
61/28
46/21
91/41
60/27
65/29
67/30
72/33
70/32
77/35
76/35
82/37
63/29
106/48
81/37
88/40
87/40
93/42
Dual-duct units — lb/kg
Unit Size
VDDF
VDDF w/Dual Wall
505
54/24
68/31
506
54/24
68/31
606
54/24
68/31
508
55/25
68/31
608
55/25
69/31
510
56/25
69/31
808
56/25
70/32
610
56/25
70/32
810
57/26
70/32
1010
61/28
74/34
612
57/26
70/32
812
58/26
71/32
1012
59/27
72/33
1212
60/27
84/38
814
78/35
102/46
1014
79/36
103/47
1214
80/36
104/47
1414
81/37
105/48
816
79/36
103/47
1016
80/36
104/47
1216
81/37
105/48
1416
82/37
105/48
1616
83/38
106/48
VAV-SVX08R-EN
Unit Installation
Table 7.
Parallel fan-powered units — lb/kg
Single Wall
Unit Size
VPCF
VPEF
0502SQ
81/37
0602SQ
80/36
0603SQ
Dual Wall
VPWF
VPCF
VPEF
95/43
115/52
94/43
114/52
105/48
108/49
110/50
92/42
83/38
112/51
84/38
113/51
1002SQ
82/37
1003SQ
1–Row
2–Row
110/550
92/42
109/49
91/41
83/38
112/51
0802SQ
81/37
0803SQ
0804SQ
VPWF
VPxF
Suppressor
1–Row
2–Row
144/65
126/57
129/59
15.5/7.0
143/65
125/57
128/58
15.5/7.0
117/53
146/66
139/63
142/64
16.5/7.5
95/43
115/52
144/65
126/57
129/59
15.5/7.0
105/48
108/49
117/53
146/66
139/63
142/64
16.5/7.5
106/48
109/49
118/54
147/67
140/64
143/65
16.5/7.5
111/50
93/42
96/44
116/53
145/66
127/58
130/59
15.5/7.0
84/38
113/51
106/48
109/49
118/54
147/67
140/64
143/65
16.5/7.5
1004SQ
85/39
114/52
107/49
110/50
119/54
148/67
141/64
144/65
16.5/7.5
1005SQ
98/44
128/58
120/54
123/56
132/60
162/73
154/70
157/71
16.5/7.5
1006SQ
114/52
144/65
127/58
130/59
148/67
178/81
161/73
164/74
20.5/9.3
1007SQ
122/55
152/69
135/61
138/63
156/71
186/84
169/77
172/78
20.5/9.3
1203SQ
85/39
114/52
107/49
110/50
119/54
148/67
141/64
144/65
16.5/7.5
1204SQ
86/39
115/52
108/49
111/50
120/54
149/68
142/64
145/66
16.5/7.5
1205SQ
99/45
129/59
121/55
124/56
133/60
163/74
155/70
158/72
15.5/7.0
1206SQ
115/52
145/66
128/58
131/59
149/68
179/81
162/73
165/75
20.5/9.3
1207SQ
123/56
153/69
136/62
139/63
157/71
187/85
170/77
173/78
20.5/9.3
1404SQ
87/39
116/53
109/49
112/51
121/55
150/68
143/65
146/66
16.5/7.5
1405SQ
100/45
130/59
122/55
125/57
134/61
164/74
156/71
159/72
16.5/7.5
1406SQ
116/53
146/66
129/59
132/60
150/68
180/82
163/74
166/75
20.5/9.3
1407SQ
124/56
154/70
137/62
140/64
158/72
188/85
171/78
174/79
20.5/9.3
1606SQ
117/53
147/67
130/59
133/60
151/68
181/82
164/74
167/76
20.5/9.3
1607SQ
125/57
155/70
138/63
141/64
159/72
189/86
172/78
175/79
20.5/9.3
Table 8.
Series fan–powered units — lb/kg
Single Wall
Unit Size
VSCF
Dual Wall
VSWF
VSEF
VSCF
1–Row
2–Row
VSxF
Suppressor
VSWF
VSEF
1–Row
2–Row
0402SQ
78/35
104/47
85/39
87/39
93/42
119/54
100/45
102/46
11.0/5.0
0502SQ
78/35
104/47
85/39
87/39
93/42
119/54
100/45
102/46
11.0/5.0
0602SQ
77/35
103/47
84/38
86/39
92/42
118/54
99/45
101/46
11.0/5.0
0603SQ
76/34
105/48
88/40
92/42
100/45
129/59
112/51
116/53
16.5/7.5
0604SQ
87/39
116/53
99/45
103/47
111/50
140/64
123/56
127/58
16.5/7.5
0802SQ
79/36
105/48
86/39
88/40
94/43
120/54
101/46
103/47
11.0/5.0
0803SQ
77/35
106/48
89/40
93/42
101/46
130/59
113/51
117/53
16.5/7.5
0804SQ
88/40
117/53
100/45
104/47
112/51
141/64
124/56
128/58
16.5/7.5
1002SQ
81/37
107/49
88/40
90/41
96/44
122/55
103/47
105/48
11.0/5.0
1003SQ
80/36
109/49
92/42
96/44
104/47
133/60
116/53
120/54
16.5/7.5
VAV-SVX08R-EN
29
Unit Installation
Table 8.
Series fan–powered units — lb/kg (continued)
Single Wall
Unit Size
1004SQ
VSCF
Dual Wall
VSWF
VSEF
VSCF
1–Row
2–Row
VSxF
Suppressor
VSWF
VSEF
1–Row
2–Row
91/41
120/54
103/47
107/49
115/52
144/65
127/58
131/59
1005SQ
92/42
121/55
104/47
108/49
116/53
145/66
128/58
132/60
16.5/7.5
1006SQ
104/47
135/61
119/54
124/56
133/60
164/74
148/67
153/69
22.5/10.2
1007SQ
117/53
148/67
132/60
137/62
146/66
177/80
161/73
166/75
22.5/10.2
1203SQ
82/37
111/50
94/43
98/44
106/48
135/61
118/54
122/55
16.5/7.5
1204SQ
92/42
121/55
104/47
108/49
116/53
145/66
128/58
132/60
16.5/7.5
1205SQ
94/43
123/56
106/48
110/50
118/54
147/67
130/59
134/61
16.5/7.5
1206SQ
105/48
136/62
120/54
125/57
134/61
165/75
149/68
154/70
22.5/10.2
1207SQ
118/54
149/68
133/60
138/63
147/67
178/81
162/73
167/76
22.5/10.2
1404SQ
93/42
122/55
105/48
109/49
117/53
146/66
129/59
133/60
16.5/7.5
1405SQ
96/44
125/57
108/49
112/51
120/54
149/68
132/60
136/62
16.5/7.5
1406SQ
106/48
137/62
121/55
126/57
135/61
166/75
150/68
155/70
22.5/10.2
1407SQ
119/54
150/68
134/61
139/63
148/67
179/81
163/74
168/76
22.5/10.2
1606SQ
107/49
138/63
122/55
127/58
136/62
167/76
151/68
156/71
22.5/10.2
1607SQ
120/54
151/68
135/61
140/64
149/68
180/82
164/74
169/77
22.5/10.2
Table 9.
Low height parallel units — lb/kg
Single Wall
Unit Size
16.5/7.5
LPCF
Dual Wall
LPWF
LPEF
LPCF
1–Row
2–Row
LPxF
Attenuator
LPWF
LPEF
1–Row
2–Row
05DS02
90/41
109/49
97/44
99/45
114/51
132/60
120/54
122/55
14/6
05PS02
93/42
110/50
99/45
101/46
116/52
133/60
122/55
124/56
14/6
06DS02
90/41
108/49
96/43
96/43
113/51
131/59
119/54
121/55
14/6
06PS02
92/42
110/50
98/44
100/45
115/52
133/60
121/55
123/56
14/6
08DS02
91/41
109/49
97/44
99/45
114/51
132/60
120/54
122/55
14/6
08PS02
93/42
110/50
99/45
101/46
116/52
133/60
122/55
124/56
14/6
14RTDS02
109/49
121/55
109/49
111/50
132/60
144/65
132/60
134/61
14/6
14RTPS02
111/50
123/56
111/50
113/51
134/61
146/66
134/61
136/61
14/6
30
VAV-SVX08R-EN
Unit Installation
Table 10.
Low–height series units — lb/kg
Single Wall
Unit Size
LSCF
Dual Wall
LSWF
LSEF
LSCF
1–Row
2–Row
LSxF
Attenuator
LSWF
LSEF
1–Row
2–Row
04DS02
89/41
107/49
95/43
97/44
112/51
130/59
118/54
120/55
14/6
04PS02
91/42
108/49
97/44
99/45
114/52
131/60
120/55
122/55
14/6
05DS02
89/41
107/49
95/43
97/44
112/51
130/59
118/54
120/55
14/6
05PS02
91/42
108/49
97/44
99/45
114/52
131/60
120/55
122/55
14/6
06DS02
88/40
106/48
94/43
96/44
111/50
129/59
117/53
119/54
14/6
06PS02
90/41
108/49
96/44
98/45
113/51
131/60
119/54
121/55
14/6
06DS03
94/43
112/51
100/45
104/47
117/53
135/61
123/56
127/58
14/6
08DS02
89/41
107/49
95/43
97/44
112/51
130/59
118/54
120/55
14/6
08PS02
91/42
108/49
97/44
99/45
114/52
131/60
120/55
122/55
14/6
08DS03
95/43
113/51
101/46
105/48
118/54
136/62
124/56
128/58
14/6
10DS03
97/44
115/52
103/47
107/49
120/55
138/63
126/57
130/59
14/6
14RTDS02
107/49
119/54
107/49
109/50
130/59
142/65
130/59
132/60
14/6
14RTPS02
109/50
121/55
109/50
111/50
132/60
144/65
132/60
134/61
14/6
14RTDS03
100/45
118/54
106/48
110/50
122/55
140/64
128/58
132/60
14/6
Table 11.
Chilled water sensible coil terminal units — lb/kg
Single Wall
Unit Size
DS02
VAV-SVX08R-EN
Dual Wall
LDWF
LDCF
LDEF
125/57
143/65
LDWF
1–Row
2–Row
131/59
135/61
LDCF
LDEF
148/67
166/75
1–Row
2–Row
154/70
158/72
31
Unit Setup
Figure 21.
Flow sensor ΔP vs. airflow delivery
Flow Sensor Differential Pressure (inches water)
10
6”
4”
1
8"
5”
8" x 12"
10" 12" 14" 16"16" x 24"
0.1
0.01
10
100
1,000
10,000
Airflow (CFM)
Fan Motor Amperage
Reference unit submittal data and motor nameplate.
Adjusting the SCR Motor Speed
Control
In order to make units more convenient and efficient to
balance, an SCR (silicone control rectifier) is provided
as standard on all fan-powered units.
The SCR is located on the side of the fan control box.
To adjust the speed of the motor, the external knob
must be rotated either clockwise or counterclockwise
depending on the desired speed adjustment.
There is an internal potentiometer setting on the SCR
controller that can be accessed by removing the control
box cover. This internal potentiometer is set at the
factory to the specific motor voltage.
It may be necessary to adjust this in the field
depending on the building power factor.
32
VAV-SVX08R-EN
Unit Setup
Figure 22.
(bottom)
SCR (top) and internal potentiometer
N o t e : This feature only verifies airflow is set properly. It
does not indicate actual ECM speed. The ECM
must be load tested. The ECM must be
connected to the fan to properly test the ECM
and display fan speed.
The following tables provide mapping from fan
percent-on setting to fan airflow for each fan type and
size. Additional fan settings can be determined by
interpolating from the tables or using the following
equation:
•
Max
Airflow setting = Airflow min + {(Potentiometer
Setting) x [(Airflow max - Airflow min)/100]}
Figure 24. ECM control board – Modulating control
with non-Trane unit controller
120 v
208 v–
277 v
347 v
DO NOT SET THIS
POTENTIOMETER
BELOW THE VOLTAGE
OF THE FAN MOTOR.
N o t e : Do not set this potentiometer below the voltage
of the fan motor.
Electrically Commutated Motor
(ECM)
Figure 23. ECM control board – Non-modulating
control with Trane unit controller (excludes Tracer®
UC210 and UC400) or non-Trane unit controller
An alternate ECM interface (shown in Figure 24, p. 33)
is utilized on unit with Non-Trane unit controller
including factory mounted third-party unit controllers.
This ECM interface allows fan modulation and fan on/
off control from the unit controller. There are two input
signal options as well as a temporary adjustment via
manual potentiometer.
•
0-10 VDC modulation signal with separate on/off
binary signal.
•
2-10 VDC modulation signal where the ECM starts
at a rise to 2 VDC and stops at a fall to 1 VDC.
N o t e : 2-10 VDC input signal requires the shunt to be
installed on the “P” terminals as shown in Figure
25, p. 33.
Figure 25. ECM control board 2-10 VDC input signal
shunt placement
Trane offers an energy efficient ECM as a motor option.
The optional Tracer® UC210 and UC400 unit controllers
directly interface with the ECM to control fan airflow
and fan on/off control. Other Trane and non-Trane unit
controller options require an ECM control interface
(shown in Figure 23, p. 33) to set fan airflow while the
unit controller dictates fan on/off control via a binary
output. The manual potentiometer is used to set the
percent-on or speed. The ECM control interface
contains display, which can be used to view percent-on
setting and speed.
VAV-SVX08R-EN
The ECM control interface contains two diagnostic LED
indicators, motor RPM (speed) and Motor Speed
Request. Motor RPM indicates the motor is driven and
running when lit. Motor Speed Request, represents the
percentage of the requested motor speed being
33
Unit Setup
supplied to the motor. Short and long flashes are used
to indicate values from 0 to 100 percent.
•
0% is displayed as an off LED.
•
1 – 99% are represented by a series of long flashes
followed by short flashes, whereas each long flash
adds 10% and each short flash adds 1%.
•
Table 13.
ECM Control
Airflow
Trane
Board Signal(b)
(Min CFM: 220,
Controller
Max CFM: 1510) PWM Signal (a)
100% is displayed as a constantly lit LED.
The following tables provide mapping from input
signal to fan airflow for each fan type and size.
Additional fan settings can be determined by
interpolating from the tables.
Table 12.
VPxF 04SQ ECM CFM
VPxF 03SQ ECM CFM
CFM
L/s
% Setting
0-10V
2-10V
220
104
0%
0.0
2.0
285
134
5%
0.5
2.4
349
165
10%
1.0
2.8
414
195
15%
1.5
3.2
478
226
20%
2.0
3.6
543
256
25%
2.5
4.0
Trane
ECM Control Board
Airflow
Controller
Signal(b) (c)
(Min CFM: 160, Max
PWM
(a)
Signal
CFM: 1085)
607
286
30%
3.0
4.4
672
317
35%
3.5
4.8
736
347
40%
4.0
5.2
800
378
45%
4.5
5.6
(a)
(b)
(c)
34
CFM
L/s
% Setting
0-10V
2-10V
160
76
0%
0.0
2.0
865
408
50%
5.0
6.0
206
97
5%
0.5
2.4
929
439
55%
5.5
6.4
253
119
10%
1.0
2.8
994
469
60%
6.0
6.8
299
141
15%
1.5
3.2
1059
500
65%
6.5
7.2
345
163
20%
2.0
3.6
1123
530
70%
7.0
7.6
391
185
25%
2.5
4.0
1188
560
75%
7.5
8.0
438
206
30%
3.0
4.4
1252
591
80%
8.0
8.4
484
228
35%
3.5
4.8
1317
621
85%
8.5
8.8
530
250
40%
4.0
5.2
1381
652
90%
9.0
9.2
576
272
45%
4.5
5.6
1446
682
95%
9.5
9.6
623
294
50%
5.0
6.0
1510
713
100%
10.0
10.0
669
316
55%
5.5
6.4
(a)
715
337
60%
6.0
6.8
(b)
761
359
65%
6.5
7.2
(c)
808
381
70%
7.0
7.6
854
403
75%
7.5
8.0
900
425
80%
8.0
8.4
946
447
85%
8.5
8.8
993
468
90%
9.0
9.2
1039
490
95%
9.5
9.6
1085
512
100%
10.0
10.0
% setting from Trane unit controller via pulse width modulating
signal or ECM control board with manual fan speed adjust setting.
ECM control board with 0-10 VDC fan modulation input and separate
fan on/off binary input required.
ECM control board with 2-10 VDC, has combined fan on/off and
modulation input where fan comes on when signal rises to 2 VDC and
goes off when signal falls to 1 VDC.
(c)
% setting from Trane unit controller via pulse width modulating
signal or ECM control board with manual fan speed adjust setting.
ECM control board with 0-10 VDC fan modulation input and separate
fan on/off binary input required.
ECM control board with 2-10 VDC, has combined fan on/off and
modulation input where fan comes on when signal rises to 2 VDC and
goes off when signal falls to 1 VDC.
Table 14.
VPxF 05SQ ECM CFM
ECM Control Board
Trane
Airflow
Signal(b) (c)
Controller
(Min CFM: 280,
Max CFM: 1850) PWM Signal (a)
CFM
L/s
% Setting
0-10V
2-10V
280
132
0%
0.0
2.0
359
169
5%
0.5
2.4
437
206
10%
1.0
2.8
516
243
15%
1.5
3.2
594
280
20%
2.0
3.6
673
317
25%
2.5
4.0
751
354
30%
3.0
4.4
830
391
35%
3.5
4.8
VAV-SVX08R-EN
Unit Setup
Table 14.
VPxF 05SQ ECM CFM (continued)
Table 15.
ECM Control Board
Trane
Airflow
Signal(b) (c)
Controller
(Min CFM: 280,
Max CFM: 1850) PWM Signal (a)
(a)
(b)
(c)
VPxF 06SQ ECM CFM (continued)
ECM Control
Trane
Airflow
Board Signal(b)
Controller
(Min CFM: 530,
Max CFM: 2100) PWM Signal (a)
(c)
CFM
L/s
% Setting
0-10V
2-10V
CFM
L/s
% Setting
0-10V
2-10V
908
428
40%
4.0
5.2
1786
843
80%
8.0
8.4
986
466
45%
4.5
5.6
1865
880
85%
8.5
8.8
1065
503
50%
5.0
6.0
1943
917
90%
9.0
9.2
1144
540
55%
5.5
6.4
2022
954
95%
9.5
9.6
2100
991
100%
10.0
10.0
1222
577
60%
6.0
6.8
1301
614
65%
6.5
7.2
(a)
1379
651
70%
7.0
7.6
(b)
1458
688
75%
7.5
8.0
(c)
1536
725
80%
8.0
8.4
1615
762
85%
8.5
8.8
1693
799
90%
9.0
9.2
1772
836
95%
9.5
9.6
1850
873
100%
10.0
10.0
Table 16.
% setting from Trane unit controller via pulse width modulating
signal or ECM control board with manual fan speed adjust setting.
ECM control board with 0-10 VDC fan modulation input and separate
fan on/off binary input required.
ECM control board with 2-10 VDC, has combined fan on/off and
modulation input where fan comes on when signal rises to 2 VDC and
goes off when signal falls to 1 VDC.
Table 15.
Trane
Airflow
Controller
(Min CFM: 530,
Max CFM: 2100) PWM Signal (a)
VSxF 03SQ ECM CFM
ECM Control Board
Trane
Airflow
Signal(b) (c)
Controller
(Min CFM: 200,
(a)
Max CFM: 1100) PWM Signal
VPxF 06SQ ECM CFM
ECM Control
Board Signal(b)
% setting from Trane unit controller via pulse width modulating
signal or ECM control board with manual fan speed adjust setting.
ECM control board with 0-10 VDC fan modulation input and separate
fan on/off binary input required.
ECM control board with 2-10 VDC, has combined fan on/off and
modulation input where fan comes on when signal rises to 2 VDC and
goes off when signal falls to 1 VDC.
(c)
CFM
L/s
% Setting
0-10V
2-10V
200
94
0%
0.0
2.0
245
116
5%
0.5
2.4
290
137
10%
1.0
2.8
335
158
15%
1.5
3.2
380
179
20%
2.0
3.6
425
201
25%
2.5
4.0
470
222
30%
3.0
4.4
515
243
35%
3.5
4.8
CFM
L/s
% Setting
0-10V
2-10V
530
250
0%
0.0
2.0
560
264
40%
4.0
5.2
609
287
5%
0.5
2.4
605
285
45%
4.5
5.6
687
324
10%
1.0
2.8
650
307
50%
5.0
6.0
766
361
15%
1.5
3.2
695
328
55%
5.5
6.4
844
398
20%
2.0
3.6
740
349
60%
6.0
6.8
923
435
25%
2.5
4.0
785
370
65%
6.5
7.2
1001
472
30%
3.0
4.4
830
392
70%
7.0
7.6
1080
509
35%
3.5
4.8
875
413
75%
7.5
8.0
1158
546
40%
4.0
5.2
920
434
80%
8.0
8.4
1237
584
45%
4.5
5.6
965
455
85%
8.5
8.8
1315
621
50%
5.0
6.0
1010
477
90%
9.0
9.2
1394
658
55%
5.5
6.4
1055
498
95%
9.5
9.6
1472
695
60%
6.0
6.8
1100
519
100%
10.0
10.0
1551
732
65%
6.5
7.2
(a)
1629
769
70%
7.0
7.6
(b)
1708
806
75%
7.5
8.0
VAV-SVX08R-EN
% setting from Trane unit controller via pulse width modulating
signal or ECM control board with manual fan speed adjust setting.
ECM control board with 0-10 VDC fan modulation input and separate
fan on/off binary input required.
35
Unit Setup
Table 16.
(c)
VSxF 03SQ ECM CFM (continued)
ECM control board with 2-10 VDC, has combined fan on/off and
modulation input where fan comes on when signal rises to 2 VDC and
goes off when signal falls to 1 VDC.
Table 17.
VSxF 04SQ ECM CFM
Trane
Airflow
Controller
(Min CFM: 275,
Max CFM: 1500) PWM Signal (a)
Table 18.
ECM Control Board
Trane
Airflow
Signal(b) (c)
Controller
(Min CFM: 350,
Max CFM: 2050) PWM Signal (a)
ECM Control Board
Signal(b) (c)
CFM
L/s
% Setting
0-10V
2-10V
275
130
0%
0.0
2.0
336
159
5%
0.5
2.4
398
188
10%
1.0
2.8
459
216
15%
1.5
3.2
520
245
20%
2.0
3.6
581
274
25%
2.5
4.0
643
303
30%
3.0
4.4
704
332
35%
3.5
4.8
765
361
40%
4.0
5.2
826
390
45%
4.5
5.6
887
419
50%
5.0
6.0
949
448
55%
5.5
6.4
1010
477
60%
6.0
6.8
(a)
1071
506
65%
6.5
7.2
1133
534
70%
7.0
7.6
1194
563
75%
7.5
8.0
1255
592
80%
8.0
8.4
(b)
(a)
(b)
(c)
1316
621
85%
8.5
8.8
1378
650
90%
9.0
9.2
1439
679
95%
9.5
9.6
1500
708
100%
10.0
10.0
% setting from Trane unit controller via pulse width modulating
signal or ECM control board with manual fan speed adjust setting.
ECM control board with 0-10 VDC fan modulation input and separate
fan on/off binary input required.
ECM control board with 2-10 VDC, has combined fan on/off and
modulation input where fan comes on when signal rises to 2 VDC and
goes off when signal falls to 1 VDC.
Table 18.
VSxF 05SQ ECM CFM
ECM Control Board
Trane
Airflow
Signal(b) (c)
Controller
(Min CFM: 350,
Max CFM: 2050) PWM Signal (a)
CFM
L/s
% Setting
0-10V
2-10V
350
165
0%
0.0
2.0
435
205
5%
0.5
2.4
520
245
10%
1.0
2.8
605
285
15%
1.5
3.2
690
36
326
20%
2.0
3.6
VSxF 05SQ ECM CFM (continued)
(c)
CFM
L/s
% Setting
0-10V
2-10V
775
366
25%
2.5
4.0
860
406
30%
3.0
4.4
945
446
35%
3.5
4.8
1030
486
40%
4.0
5.2
1115
526
45%
4.5
5.6
1200
566
50%
5.0
6.0
1285
606
55%
5.5
6.4
1370
647
60%
6.0
6.8
1455
687
65%
6.5
7.2
1540
727
70%
7.0
7.6
1625
767
75%
7.5
8.0
1710
807
80%
8.0
8.4
1795
847
85%
8.5
8.8
1880
887
90%
9.0
9.2
1965
927
95%
9.5
9.6
2050
967
100%
10.0
10.0
% setting from Trane unit controller via pulse width modulating
signal or ECM control board with manual fan speed adjust setting.
ECM control board with 0-10 VDC fan modulation input and separate
fan on/off binary input required.
ECM control board with 2-10 VDC, has combined fan on/off and
modulation input where fan comes on when signal rises to 2 VDC and
goes off when signal falls to 1 VDC.
Table 19.
VSxF 06SQ ECM CFM
ECM Control
Airflow
Trane
Board Signal(b)
(Min CFM: 700,
Controller
Max CFM: 2500) PWM Signal (a)
(c)
CFM
L/s
% Setting
0-10V
2-10V
700
330
0%
0.0
2.0
790
373
5%
0.5
2.4
880
415
10%
1.0
2.8
970
458
15%
1.5
3.2
1060
500
20%
2.0
3.6
1150
543
25%
2.5
4.0
1240
585
30%
3.0
4.4
1330
628
35%
3.5
4.8
1420
670
40%
4.0
5.2
1510
713
45%
4.5
5.6
1600
755
50%
5.0
6.0
1690
798
55%
5.5
6.4
1780
840
60%
6.0
6.8
VAV-SVX08R-EN
Unit Setup
Table 19.
VSxF 06SQ ECM CFM (continued)
ECM Control
Trane
Airflow
Board Signal(b)
Controller
(Min CFM: 700,
Max CFM: 2500) PWM Signal (a)
(a)
(b)
(c)
Table 20.
(c)
LSxF DS03 ECM CFM (continued)
ECM Control Board
Trane
Airflow
Signal(b) (c)
Controller
(Min CFM: 100,
Max CFM: 1300) PWM Signal (a)
CFM
L/s
% Setting
0-10V
2-10V
CFM
L/s
% Setting
0-10V
1870
882
65%
6.5
7.2
1240
585
95%
9.5
9.6
1960
925
70%
7.0
7.6
1300
613
100%
10.0
10.0
2050
967
75%
7.5
8.0
(a)
2140
1010
80%
8.0
8.4
(b)
2230
1052
85%
8.5
8.8
(c)
2320
1095
90%
9.0
9.2
2410
1137
95%
9.5
9.6
2500
1180
100%
10.0
10.0
% setting from Trane unit controller via pulse width modulating
signal or ECM control board with manual fan speed adjust setting.
ECM control board with 0-10 VDC fan modulation input and separate
fan on/off binary input required.
ECM control board with 2-10 VDC, has combined fan on/off and
modulation input where fan comes on when signal rises to 2 VDC and
goes off when signal falls to 1 VDC.
Table 20.
L/s
% Setting
0-10V
2-10V
47
0%
0.0
2.0
160
76
5%
0.5
2.4
220
104
10%
1.0
2.8
280
132
15%
1.5
3.2
340
160
20%
2.0
3.6
400
189
25%
2.5
4.0
460
217
30%
3.0
4.4
520
245
35%
3.5
4.8
580
274
40%
4.0
5.2
640
302
45%
4.5
5.6
700
330
50%
5.0
6.0
760
359
55%
5.5
6.4
820
387
60%
6.0
6.8
880
415
65%
6.5
7.2
940
444
70%
7.0
7.6
1000
472
75%
7.5
8.0
1060
500
80%
8.0
8.4
1120
529
85%
8.5
8.8
1180
557
90%
9.0
9.2
VAV-SVX08R-EN
LSxF, LpxF, LDxF DS02 ECM CFM
ECM Control Board
Trane
Airflow
Signal(b) (c)
Controller
(Min CFM: 400,
Max CFM: 1800) PWM Signal (a)
ECM Control Board
Trane
Airflow
Signal(b) (c)
Controller
(Min CFM: 100,
Max CFM: 1300) PWM Signal (a)
100
% setting from Trane unit controller via pulse width modulating
signal or ECM control board with manual fan speed adjust setting.
ECM control board with 0-10 VDC fan modulation input and separate
fan on/off binary input required.
ECM control board with 2-10 VDC, has combined fan on/off and
modulation input where fan comes on when signal rises to 2 VDC and
goes off when signal falls to 1 VDC.
Table 21.
LSxF DS03 ECM CFM
CFM
2-10V
(a)
(b)
(c)
CFM
L/s
% Setting
0-10V
2-10V
400
189
0%
0.0
2.0
470
222
5%
0.5
2.4
540
255
10%
1.0
2.8
610
288
15%
1.5
3.2
680
321
20%
2.0
3.6
750
354
25%
2.5
4.0
820
387
30%
3.0
4.4
890
420
35%
3.5
4.8
960
453
40%
4.0
5.2
1030
486
45%
4.5
5.6
1100
519
50%
5.0
6.0
1170
552
55%
5.5
6.4
1240
585
60%
6.0
6.8
1310
618
65%
6.5
7.2
1380
651
70%
7.0
7.6
1450
684
75%
7.5
8.0
1520
717
80%
8.0
8.4
1590
750
85%
8.5
8.8
1660
783
90%
9.0
9.2
1730
816
95%
9.5
9.6
1800
849
100%
10.0
10.0
% setting from Trane unit controller via pulse width modulating
signal or ECM control board with manual fan speed adjust setting.
ECM control board with 0-10 VDC fan modulation input and separate
fan on/off binary input required.
ECM control board with 2-10 VDC, has combined fan on/off and
modulation input where fan comes on when signal rises to 2 VDC and
goes off when signal falls to 1 VDC.
37
Wiring Diagrams
N o t e s : See programming guides listed below for
detailed class II low voltage unit controls wiring
information on the following:
38
•
UCM 4.2: VAV-SVX01*-EN
•
UC400: VAV-SVX07*-EN
•
UC210: BAS-SVX62*-EN
•
VV550: VAV-SVP01*-EN
VAV-SVX08R-EN
Wiring Diagrams
Wiring — Electric Heater Control Box
Figure 26.
Single duct , single phase, 1 leg, 3 stages
VAV-SVX08R-EN
39
Wiring Diagrams
Figure 27.
40
Single duct, single phase, 2 legs, 3 stages
VAV-SVX08R-EN
Wiring Diagrams
Figure 28.
Single duct, three phase, delta, 3 stages
VAV-SVX08R-EN
41
Wiring Diagrams
Figure 29.
42
Single duct, single phase, SCR, 1 leg, 1 stage
VAV-SVX08R-EN
Wiring Diagrams
Figure 30.
Single duct, single phase, SCR, 2 legs, 1 stage
STAGES
1
LINE VOLTAGE
(SEE NAMEPLATE)
L1
LEGEND
DEVICE
DESIGNATION
NOTES:
L2
1.
2.
SINGLE PHASE
LINE VOLTAGES
208
3.
240
UNLESS OTHERWISE NOTED, ALL SWITCHES ARE SHOWN AT 25° C
(77° F), AT ATMOSPHERIC PRESSURE, AT 50% RELATIVE HUMIDITY,
WITH ALL UTILITIES TURNED OFF, AND AFTER A NORMAL SHUTDOWN
HAS OCCURRED.
2F1,2F2,2F3
DESCRIPTION
FUSE
2HR*
2K1,2K2,2K3,2K4
HEATER ELEMENT
HEATER CONTACTOR
DASHED LINES INDICATE RECOMMENDED FIELD WIRING BY OTHERS.
DASHED LINE ENCLOSURES AND/OR DASHED DEVICE OUTLINES
INDICATE COMPONENTS THAT ARE OPTIONAL OR GROUPED
TOGETHER. SOLID LINES INDICATE WIRING BY TRANE.
2S1
DISCONNECT SWITCH
2S2
HIGH TEMPERATURE CUTOUT (MANUAL RESET)
2S3
HIGH TEMPERATURE CUTOUT (AUTO RESET)
2S4
SUPPLY AIR PROVING SWITCH
ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE
NATIONAL ELECTRIC CODE (NEC), STATE AND LOCAL REQUIREMENTS.
2T1
CONTROL POWER TRANSFORMER
2J*-*
JACK/SOCKET CONNECTOR
2P*-*
SSR1, SSR2
480
PLUG/PIN CONNECTOR
SOLID STATE CONTACTORS
POWER SUPPLY
PW1
2S1
OPTIONAL
POWER SUPPLY
2F2
2F1
OPTIONAL
FUSES
PW1
BLU
+24
VDC
BLU
BRN
YEL
24
VAC
BLU
2T1
BLU
YEL
24V
2K4
YEL
YEL
2J2-5
2S2
24VAC Ret - GND
YEL
2K4
2K4
BLU
2P2-5
2J1-5
2P1-5
BLU
BLU
2J2-6
2P2-6
2J1-6
2P1-6
2J1-4
2P1-4
24Vdc
BRN
BRN
2S4
YEL 2S3
GRY
GRY
BLU
2J1-2
TO
LOW VOLTAGE SECTION
24VAC (HOT) BLU
24VAC 50/60HZ
NEC CLASS-2
CONTROL CIRCUIT
GND
2P1-2
2J1-2
2P1-2
2J1-1
HEAT 1(0-10Vdc)
2P1-1
P
ORG
ORG
2J1-1
LOCATED IN
LOW VOLTAGE
SECTION
2P1-1
OUTPUT
1/L1
2/T1
P4
P3
OUTPUT
STATUS
P2
P1
SSR1
YEL
BK
2P1-2
BL
2J2-1
BL
2P2-1
2HR1
BK
2J1-2
VAV-SVX08R-EN
43
Wiring Diagrams
Figure 31.
44
Single duct, three phase, delta, SCR, 1 stage
VAV-SVX08R-EN
Wiring Diagrams
Figure 32.
Single duct, single phase, 1 leg
VAV-SVX08R-EN
45
Wiring Diagrams
Figure 33.
46
Fan powered, single phase, 1 leg, 2 stages
VAV-SVX08R-EN
Wiring Diagrams
Figure 34.
Fan powered, single phase, 2 legs, 2 stages
VAV-SVX08R-EN
47
Wiring Diagrams
Figure 35.
48
Fan powered, three phase, wye, 2 stages
VAV-SVX08R-EN
Wiring Diagrams
Figure 36.
Fan powered, single phase, 1 leg, 2 stages
VAV-SVX08R-EN
49
Wiring Diagrams
Figure 37.
50
Fan powered, single phase, 2 legs, 2 stages
VAV-SVX08R-EN
Wiring Diagrams
Figure 38.
Fan powered, three phase, wye, 2 stages
VAV-SVX08R-EN
51
Wiring Diagrams
Control Box Wiring
Figure 39.
52
Single duct control box
VAV-SVX08R-EN
Wiring Diagrams
Figure 40.
Fan-powered units with PSC motors
VAV-SVX08R-EN
53
Wiring Diagrams
Figure 41.
54
Fan-powered units with ECM motor
VAV-SVX08R-EN
Wiring Diagrams
Figure 42.
Fan-powered units with ECV motor
VAV-SVX08R-EN
55
Wiring Diagrams
Figure 43.
56
Fan-powered, old style
VAV-SVX08R-EN
Wiring Diagrams
Figure 44.
Fan-powered, ECM, old style
VAV-SVX08R-EN
57
Wiring Diagrams
Figure 45.
Fan-powered, low-height incl 10SQ, old style
Fan-Powered Low-Height Control Box
Fan-Powered Low-Height Control Box
FAN
MOTOR 2
(SIZE 10 ONLY)
Duct Pressure Switch Option
FAN
MOTOR
CAPACITOR
3.
FAN
FAN
MOTOR 2
(SIZE 10 ONLY)
5.
LINE VOLTAGE
OR FROM HEATER TERMINAL
3.
CAPACITOR
BR
BR
BR
L1
LINE VOLTAGE
OR FROM HEATER TERMINAL
}
MOTOR
W
N
W
L1
3.
BR
BR
5.
BK
BK
2.
BK
GROUND
MOTOR
SCREW
MOTOR
SPEED
CONTROL
SCREW
SPEED
W
CONTROL
2.
W
W
2.
BK
TERMINAL
BLOCK
DISCONNECT
W
W
W
CAPACITOR
GREEN
GREEN
GROUND
BK
CAPACITOR
BR
N
BK
BR
BK
3.
SWITCH
W
W
W
TERMINAL
BLOCK
BR
2.
W
W
DISCONNECT
W
BK
W
BR
SWITCH
4.
W
BK
4.
BK
FUSE
BK
FUSE
6.
2
BK
NO
4
24V
C
TRANSFORMER
NC
BK
BK
BL
BL
BL
Y
1 24V 3
NO
DUCT
BK
MOTOR
PRESSURE
C
RELAY
SWITCH
NC
FAN CONTROL BOX
P.E. SWITCH
FAN CONTROL BOX
NOTES:
1.
FACTORY INSTALLED
BY OTHERS
OPTIONAL OR ALTERNATE CIRCUITRY
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.
2.
DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
EXTERNAL TO CONTROL BOX.
3.
CAPACITOR IS INSTALLED ON FAN HOUSING.
DISCHARGE MOTOR START/RUN
CAPACITORS BEFORE SERVICING.
FUSE IS OPTIONAL.
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
DUCT PRESSURE MAIN CONTROL
6.
BK NO
NO
C
NC
4.
5.
DETERMINED BY MOTOR VOLTAGE ON ORDER.
VOLTAGE FOUND ON UNIT NAMEPLATE.
6.
FOR SERIES FAN POWERED TERMINAL UNITS ONLY.
P.E. SWITCH-1
C
BK
NC
P.E. SWITCH-2
BK
CAUTION
USE COPPER CONDUCTORS ONLY!
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT OTHER TYPES OF
CONDUCTORS.
FAILURE TO DO SO MAY CAUSE
DAMAGE TO THE EQUIPMENT.
58
VAV-SVX08R-EN
Wiring Diagrams
Fan-powered, low-height incl 10SQ, ECM, old style
Fan-Powered Low-Height Control Box
w/ ECM with Electronic or DDC Controls
Fan-Powered Low-Height Control Box
w/ ECM
(Depending on the size of the unit, the ECM board
may or may not be located in the fan control box.)
Duct Pressure Switch Option
LINE VOLTAGE
OR FROM HEATER TERMINAL
}
FAN
MOTOR
4.
FAN
MOTOR 2
(SIZE 10 ONLY)
FAN
MOTOR 2
(SIZE 10 ONLY)
TERMINAL
BLOCK
GREEN
GROUND
SCREW
RED
BK
TERMINAL
BLOCK
RED
2.
DISCONNECT
SWITCH W
3.
2
BK
24V
DISCONNECT
SWITCH
2.
W
W
W
Y
BK
BK
W
BK
FAN
MOTOR
GR
W
NEUT.
3.
4.
BK
GR
GREEN
GROUND
SCREW
BK
}
LINE VOLTAGE
OR FROM HEATER TERMINAL
W
Figure 46.
4
FUSE
BL
BK
W
1
G
R
ECM
BOARD
3
24V
W
BK
Y
FUSE
5.
NO BL
MOTOR
RELAY
NEUT.
24V
BL
RED
RED
C
24V
BL
BK
G
R
ECM
BOARD
BL
W
BK
Y
SWITCH
24V
}
Y
BK
NC
DUCT
PRESSURE
TO VAV
CONTROLLER
TRANSFORMER
TRANSFORMER
FAN CONTROL BOX
FAN CONTROL BOX
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.
DISCHARGE MOTOR START/RUN
CAPACITORS BEFORE SERVICING.
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
CAUTION
Fan-Powered Low-Height Control Box w/ ECM
USE COPPER CONDUCTORS ONLY!
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT OTHER TYPES OF
CONDUCTORS.
LINE VOLTAGE
4.
OR FROM HEATER TERMINAL
FAN
MOTOR 2
(SIZE 10 ONLY)
FAN
MOTOR
}
FAILURE TO DO SO MAY CAUSE
DAMAGE TO THE EQUIPMENT.
DUCT PRESSURE MAIN CONTROL
W
BK
BK
W
W
BK
GR
GREEN
GROUND
SCREW
TERMINAL
BLOCK
5.
DISCONNECT
SWITCH
2.
BK NO
3.
NO
BL
BL
W
Y
FUSE
C
C
BK
NC
NC
NEUT.
BK
BK
RED
RED
BL
NO
ECM
BOARD
G
R
FACTORY INSTALLED
BY OTHERS
OPTIONAL OR ALTERNATE CIRCUITRY
W
BK
TRANSFORMER
NOTES:
1.
24V
Y
P.E. SWITCH-2
24V
P.E. SWITCH-1
C
2.
DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
EXTERNAL TO CONTROL BOX.
NC
P.E. SWITCH
3.
FUSE IS OPTIONAL.
4.
DETERMINED BY MOTOR VOLTAGE ON ORDER.
VOLTAGE FOUND ON UNIT NAMEPLATE.
5.
FOR SERIES FAN POWERED TERMINAL UNITS ONLY.
FAN CONTROL BOX
VAV-SVX08R-EN
59
Maintenance
Periodic maintenance of the VariTrane™ product is
minimal, but necessary for efficient operation. Routine
maintenance consists of inspecting/replacing the air
filters of the fan-powered terminals.
Fan Motor Replacement
Motors
Failure to disconnect power and discharge
capacitors before servicing could result in death or
serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper
lockout/tagout procedures to ensure the power
cannot be inadvertently energized. For variable
frequency drives or other energy storing
components provided by Trane or others, refer to
the appropriate manufacturer’s literature for
allowable waiting periods for discharge of
capacitors. Verify with a CAT III or IV voltmeter
rated per NFPA 70E that all capacitors have
discharged.
Both the Permanent Split Capacitor( PSC) and the
Electrically Commutated Motor (ECM) require no
lubrication during its normal life of operation.
Fan Wheel
Routinely inspect the fan wheel for dirt or debris and
cleaned as necessary.
Filter
Routinely inspect and/or replace the filter on fanpowered terminals depending on the environmental
conditions of the plenum.
Filter Change Out
•
To remove the filter, turn each of the filter retaining
clips 90° (CW or CCW)
•
Remove the filter and replace with new filter of the
same frame size.
•
Return the filter clips to their retaining position by
turning them 90° (CW or CCW) back to their original
position.
WARNING
Hazardous Voltage w/Capacitors!
Figure 47.
Standard motor removal
Water Coil
•
Periodically inspect water coils and clean fins.
•
Water coils are provided with an access panel as
standard to assist with inspection and cleaning.
Standard height fan-powered series and parallel fan
motors are replaceable through the filter opening and
the standard sliding side access panel. To access the
fan motor, the fan housing must be detached by
removing the mounting bolts that hold the housing to
the fan board. Removing the entire housing allows the
fan motor, fan housing, and fan wheel to be re-aligned
on a workbench or floor and prevent any possible fan
wheel rubbing that may occur. Removing the housing
will provide access to the motor shaft set screw that
holds the fan wheel to the motor shaft.
The low height fan assembly has been designed to be
removed and replaced as a complete unit.
60
VAV-SVX08R-EN
Maintenance
SCR Assembly
SCR solid state relays are used to switch a single heater
stage on and off. An intelligent (Master) relay is used
for all single phase applications. For three phase
applications, a Master-Slave configuration is used to
switch two legs of three phase power to the heater
stage. The Master Relay controls one leg
independently, and provides a control signal to the
Slave Relay, which controls the second leg.
Figure 48.
Typical heat sink fin orientation
Bottom View
Every Master or Master/Slave relay combination is
mounted on a heat sink to prevent the relays from
VAV-SVX08R-EN
overheating during normal operation. The SCR
assembly must always be mounted with the heat sink
fins oriented vertically (see above) with a minimum
clearance of 0.5 inches on all sides of the heat sink for
cooling. Where additional cooling slots are provided in
the heater, the VAV unit must be mounted with a
minimum of 1 inch clearance in front of the slots.
When the 0-10 VDC control voltage is present at the
Master relay in both single and three phase
applications, an ON indicating LED light on the Master
relay will blink continually (approximately 0.5 seconds
on, 1.0 seconds off). If the load side voltage is also
present at the relay(s), the Master relay LED and the
Slave relay LED blink rate will increase as the control
signal increases. When the control signal reaches a
maximum of 10 VDC, all LEDs will be lit continuously,
indicating that the relays are full-open and
continuously conducting. If the control signal is present
in three phase applications while the load side voltage
is not, only the Master relay LED will light and the blink
rate will be constant.
If the SCR assembly does not appear to be functioning
properly, verify that all required voltages are present
and all that all wiring is properly connected. If all these
conditions are verified, and the SCR LED does not light
and/or the SCR relay does not conduct, the entire SCR
heat sink assembly should be changed out. Individual
Master or Slave relays should not be replaced.
61
Notes
62
VAV-SVX08R-EN
Notes
VAV-SVX08R-EN
63
Trane - by Trane Technologies (NYSE: TT), a global innovator - creates comfortable, energy efficient
indoor environments for commercial and residential applications. For more information, please visit
trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without
notice. We are committed to using environmentally conscious print practices.
VAV-SVX08R-EN
10 Sep 2021
Supersedes VAV-SVX08Q-EN
(April 2021)
©2021 Trane

advertisement

Related manuals

Download PDF

advertisement