355AAV - HVACpartners
DELUXE 4-WAY MULTIPOISE
VARIABLE-SPEED
DELUXE CONDENSING GAS FURNACE
355AAV
Sizes 040 thru 120
Series H
will create a fully communicating system, requiring only 4 thermostat wires between system components, and troubleshooting can
even be done from the outdoor unit without entering the home.
Optional remote access through telephone or Internet is also
available when combined with a remote connectivity kit.
FEATURES
Perfect Heat/Perfect Humidity™ Control—This intelligent heating
control constantly monitors operating conditions to adjust for
greater efficiency and comfort. The control operates 90% of the
time in low-heat and reserves the high-firing rate for times when
the heating demand is high. The Perfect Heat/Perfect Humidity
control has these additional features:
A05085
™
Building on our industry-leading condensing furnace technology,
the model 355AAV is our greatest innovation in comfort control
and operating efficiency.
Modern technology provides the Plus 90i™ design with great reliability, high efficiency, and ultra-quiet operation. Efficiencies
are up to 96.6 percent Annual Fuel Utilization Efficiency (AFUE).
The model 355AAV Plus 90i Condensing Gas Furnace incorporates our patented Perfect Heat™ Control. This control
interacts with a 2-stage gas valve, a variable-speed inducer
motor, and a variable-speed blower motor, allowing the Plus 90i
to adjust combustion air, firing rate, and airflow to maintain peak
efficiency throughout the operating cycle.
The Perfect Heat™ system provides the ultimate in heating comfort while minimizing electrical and gas consumption. The Plus
90i also features Perfect Humidity control when combined with a
Bryant Thermidistat™ Control and air conditioner or heat pump
system.
Bryant Evolution® System—When this Plus 90i gas furnace is
matched with the Evolution Control and an air conditioner or heat
pump, you will experience the ultimate in Perfect Heat™ and
Perfect Humidity™ through unmatched control of temperature,
humidity, indoor air quality, and zoning. The Bryant Evolution
System also allows for worry-free operation through on-screen,
text-based service reminders and equipment malfunction alerts.
For even greater comfort and convenience, match the Plus 90i
furnace with a two-speed Puron air conditioner or heat pump. This
• dedicated terminals for electrical connection of electronic air
cleaner and humidifier
• adjustable blower off time
• LED fault code display to aid in servicing
• selectable airflow to match cooling unit
• emergency heat setting
• setting to increase airflow for bypass-type humidifier
• selectable constant fan airflow
• a multizone setting for use with zoned air distribution systems
• a special dehumidification function increases cooling comfort
by providing greater humidity removal in summer months
• controls humidity even when there is no heating or cooling
demand
Three-Pass Primary Heat Exchangers—This design accelerates
heat transfer and extracts heat that conventional heat exchangers waste up the flue. The primary heat exchanger is made of
aluminized steel for corrosion resistance.
Flow-Through Secondary Heat Exchangers—Each cell is laminated with our patented Everlastic™ polypropylene for greater
resistance to corrosion and is epoxy coated externally to prevent
oxidation. This breakthrough in heating technology (Patent No.
4,738,307) helps extend the life of the furnace for years of reliable performance. The heat exchangers are positioned in the
furnace to extract additional heat from the combustion products
regardless of furnace orientation.
Perfect Light™ Igniter —Bryant’s unique SiN igniter is not
only physically robust but it is also electrically robust. It is capable of running at line voltage and does not require complex
voltage regulators as do other brands. This unique feature further enhances the reliability of Bryant‘s 355AAV gas furnace
and continues Bryant’s tradition of technology leadership and
innovation in providing a reliable and durable product.
Fan On Plus™ —Improves comfort all year long by allowing
you to select the continuous fan speed right at the thermostat.
SmartEvap™ —Allows your system to reduce summertime humidity levels by nearly 10% over standard systems.
Media Filter Cabinet—Enhanced indoor air quality in your
home is made easier with our media filter cabinet—a standard
accessory on all Deluxe furnaces. When installed as a part of
your system, this cabinet allows for easy and convenient addition of a Bryant high-efficiency air filter.
Catalog No. PDS 355A.40.1
Warranty—Limited lifetime warranty on the heat exchangers for
the lifetime of the original owner in single family residence; 20
years in other residential and commercial applications. Contact
your dealer for details. The rest of the unit is backed by a 5-year
limited warranty.
4-Way Multipoise Design—Allows the model 355AAV to be installed in an upflow, downflow, or horizontal orientation. Factory
configured for upflow applications with only simple drain connection changes required for conversion to downflow or horizontal.
The model 355AAV is available in 6 heat/airflow combinations.
When combined with the 4-way design, the 355AAV allows for
24 different applications.
Direct or Non-Direct Venting—This furnace can be installed as a
1-pipe/Non-direct vent or 2-pipe/Direct vent furnace. This provides added flexibility to meet diverse installation needs.
2-Stage Gas Valve—The 355AAV has a 2-stage gas valve to
vary the amount of gas being used from low-heat to high-heat
stage.
Fully-Insulated Casing—Foil-faced insulation in the heat exchanger section cuts the heat loss; double-density insulation in
the blower section reduces noise levels. The casing also has
the required openings for left- or right-side connection of gas,
electric, drain, and vent connections.
Variable-Speed Motors—Variable-speed operation improves the
comfort levels in the home. Variable-Speed motors are also
more economical to operate than standard motors. They have
the ability to adapt to changing conditions and provide consistent, comfortable, and quiet heating. Motors and electronic controls are covered by a 5-year limited warranty.
Sealed Combustion System—This furnace brings in combustionair from outside the furnace, which results in especially quiet
operation.
Monoport Inshot Burners—Produce precise air-to-gas mixture
for clean burning. The large monoport on the inshot or injectiontype burners seldom, if ever, needs cleaning.
Quality Registration—The 355AAV is engineered and manufactured under an ISO 9001 registered quality system.
Certifications—The 355AAV units are CSA (A.G.A. and C.G.A.)
design certified for use with natural and propane gases, as well
as GAMA efficiency rating certified. The furnace is factoryshipped for use with natural gas. An CSA (A.G.A. and C.G.A.)
certified gas conversion kit is required to convert furnace for use
with propane gas. The model 355AAV meets California Air Quality Management District emission requirements.
CONDENSATE TRAP
FURNACE
DOOR
BLOWER SHELF
CONDENSATE
TRAP
CONDENSATE
TRAP (INSIDE)
FURNACE
DOOR
FURNACE
SIDE
4 78
FURNACE
SIDE
4
534
534
4
FIELD
DRAIN
CONN
ALTERNATE DRAIN
TUBE LOCATION
26 1 4
26 1 4
11 2
SIDE VIEW
CONDENSATE TRAP
DRAIN TUBE LOCATION
FIELD
DRAIN
CONN
FRONT VIEW
END VIEW
SLOT FOR SCREW
HORIZONTAL
APPLICATION
(OPTIONAL)
FRONT VIEW
HORIZONTAL
APPLICATIONS
DOWNFLOW AND ALTERNATE
EXTERNAL UPFLOW APPLICATIONS
UPFLOW APPLICATIONS
34
1 ⁄4
OD
COLLECTOR BOX TO
TRAP RELIEF PORT
11 2
1 ⁄2
OD
INDUCER HOUSING
DRAIN CONNECTION
34
5 ⁄8
OD
COLLECTOR BOX
DRAIN CONNECTION
71 8
SCREW HOLE FOR
UPFLOW OR DOWNFLOW APPLICATIONS
(OPTIONAL)
13 4
WIRE TIE
GUIDES
(WHEN USED)
FRONT VIEW
78
21 4
1⁄2-IN.
PVC OR CPVC
SIDE VIEW
A93026
—2—
—3—
11⁄4"
1"
14 1⁄2"
TYP
24 1⁄2"
5⁄16"
1⁄2-IN.
26 15⁄16" TYP
23 1⁄4" TYP
SIDE INLET
SIDE INLET
DIA THERMOSTAT
ENTRY
22 11⁄16"
2-IN. VENT CONN
DIA
GAS CONN
1⁄2-IN.
2-IN. COMBUSTIONAIR CONN
22
26 15⁄16"
26 1⁄4"
A
24-1/2*
17-1/2
21
21
21
24-1/2
E
INLET
D
22-7/8*
15-7/8
19-3/8
19-3/8
19-3/8
22-7/8
DIMENSIONS (IN.)
* These dimensions reflect the wider casing for the 96.6% AFUE furnace.
UNIT SIZE
042040*
042060
042080
060080
060100
060120
11/16"
D
OUTLET
11/16"
18 1⁄4"
TYP
9⁄16"
DIMPLE LOCATORS
FOR HORIZONTAL
HANGING
CONDENSATE
DRAIN LOCATION
(UPFLOW)
30 1⁄2"
CONDENSATE DRAIN
TRAP LOCATION
(DOWNFLOW &
HORIZONTAL RIGHT)
OR ALTERNATE
1
⁄2-IN. DIA GAS CONN
13/16"
E
23*
16
19-1/2
19-1/2
19-1/2
23
NOTES: 1. Minimum return-air openings at furnace, based on metal duct. If flex duct is used,
see flex duct manufacturerí s recommendations for equivalent diameters.
2. Minimum return-air opening at furnace:
a. For 800 CFM–16-in. round or 14 1/ 2 x 12-in. rectangle.
b. For 1200 CFM–20-in. round or 14 1/ 2 x 19 1/ 2-in. rectangle.
c. For 1600 CFM–22-in. round or 14 1/ 2 x 23 1/ 4-in. rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data
literature for specific use of single side inlets. The use of both side inlets, a
combination of 1 side and the bottom, or the bottom only will ensure adequate
return air openings for airflow requirements above 1800 CFM at 0.5” W.C. ESP.
CONDENSATE
DRAIN LOCATION
(UPFLOW)
9 7⁄16"
TYP
33 1⁄4"
TYP
32 5⁄8"
TYP
13⁄16"
30
29 11⁄16"
TYP
27 5⁄8"
27 9⁄16"
TYP
24 1⁄2"
17 5⁄16"
CONDENSATE
DRAIN TRAP
LOCATION
(ALTERNATE
UPFLOW)
DIA
ACCESSORY
POWER ENTRY
7⁄8-IN.
DIA
POWER CONN
7⁄8-IN.
CONDENSATE DRAIN
TRAP LOCATION
(DOWNFLOW &
HORIZONTAL LEFT)
13/16"
A
AIRFLOW
SHIP. WEIGHT (Lb)
205
170
182
204
203
234
24 3⁄16"
BOTTOM INLET
22 1⁄4" TYP
SIDE INLET
22 11⁄16"
A05070
2-IN. VENT CONN
1⁄2-IN. DIA
THERMOSTAT ENTRY
7⁄8-IN. DIA
POWER CONN
DIA
GAS CONN
1⁄2-IN.
2-IN. COMBUSTIONAIR CONN
OUTLET
19"
22 5⁄16"
26 1⁄4"
28 1⁄2"
26 15⁄16"
11⁄ "
16
7⁄16"
1"
39 7⁄8"
5⁄16"
5⁄8"
13⁄16"
INSTALLATION
This forced air furnace is equipped for use with natural gas at altitudes 0 - 10,000 ft (0 - 3,050m), except 140 size furnaces are only approved for altitudes 0 - 7,000 ft.
(0 - 2,135m).
An accessory kit, supplied by the manufacturer, shall be used to convert to propane gas use or may be required for some natural gas applications.
This furnace is for indoor installation in a building constructed on site. This furnace may be installed in a manufactured (mobile) home when stated on rating plate and
using factory authorized kit.
This furnace may be installed on combustible flooring in alcove or closet at Minimum Inches Clearance To Combustible Construction as described below.
This furnace requires a special venting system. Refer to the installation instructions for parts list and method of installation. This furnace is for use with schedule-40 PVC,
PVC-DWV, CPVC, or ABS-DWV pipe, and must not be vented in common with other gas-fired appliances. Construction through which vent/air intake pipes may be
installed is maximum 24 inches (600 mm), minimum 3/4 inches (19 mm) thickness (including roofing materials).
For upflow and downflow applications, furnace must be installed level, or pitched within 1/2" of level. For a
horizontal application, the furnace must be pitched minimum 1/4" to maximum of 1/2" forward for proper
drainage. See Installation Manual for IMPORTANT unit support details on horizontal applications.
LEVEL (0") TO
1/2" MAX
MIN 1/4" TO 1/2" MAX
FRONT
UPFLOW OR
DOWNFLOW
FRONT
HORIZONTAL
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
This furnace is approved for UPFLOW, DOWNFLOW and
HORIZONTAL installations.
ALL POSITIONS:
*
Mimimum front clearance for service 30 inches (762mm).
DOWNFLOW POSITIONS:
M
† For installation on combustible floors only when installed on special base No.
TOP/PLENU
Ø
Line contact is permissible only between lines formed by intersections of top and two sides
of furnace jacket, and building joists, studs, or framing.
Clearance shown is for air inlet and air outlet ends.
120 size furnace requires 1 inch bottom clearance to combustible materials.
0"
BA
C
SI
K
FU
RN
AC
FR
SI
§
328068-201 REV. A
LIT - TOP
FR
ON
0"
0"
†Ø
Clearance in inches.
A02250
ama
CERTIFIED
®
MEETS DOE RESIDENTIAL CONSERVATION
SERVICES PROGRAM STANDARDS.
Before purchasing this appliance, read important
energy cost and efficiency information available
from your retailer.
ISO 9001:2000
REGISTERED
As an ENERGY STAR® Partner,
Bryant Heating & Cooling Systems
determined that this product meets
the ENERGY STAR® guidelines for
energy efficiency.
—4—
O
0" §
E
T
S
DE
DE
N
T
3"
E
RV
IC
E
*
30
MIN
BOTTOM
§
1"
Clearance arrows
do not change with
furnace orientation.
KGASB0201ALL, Coil Assembly, Part No. CD5 or CK5, or Coil Casing, Part No. KCAKC.
HORIZONTAL POSITIONS:
REGISTERED QUALITY SYSTEM
These products are engineered
and manufactured under an ISO
9001 registered quality system.
Vent clearance to
combustibles 0".
SPECIFICATIONS
UNIT SIZE
RATINGS AND PERFORMANCE
Input Btuh*
Output Capacity
Btuh* (ICS)
(Shaded capacities
are specified on rating plate)
Direct Vent (2-Pipe)
Non-Direct Vent (1-Pipe)
AFUE%*
Nonweatherized ICS
Direct Vent (2-Pipe)
Non-Direct Vent (1-Pipe)
Certified Temperature Rise Range (°F)
Certified External Static Pressure (ESP)
(In. wc)
Airflow CFM‡
ELECTRICAL
Unit Volts—Hertz—Phase
Operating Voltage Range Min—Max††
Maximum Unit Amps
Unit Ampacity‡‡
Minimum Wire Size, AWG
Maximum Wire Length (Ft)***
Maximum Fuse or Ckt Bkr Amps†††
Transformer (24v)
External Control
Power Available
Accessory Relay
CONTROLS
Limit Control
Heating Blower Control (Off Delay)
Burners (Monoport)
Gas Connection Size
GAS CONTROLS
Gas Valve (Redundant 2-Stage)
Low
High
Low
Upflow
Downflow
Horizontal
High
Upflow
Downflow
Horizontal
Low
Upflow
Downflow
Horizontal
High
Upflow
Downflow
Horizontal
Upflow
Downflow
Horizontal
Upflow
Downflow
Horizontal
Low
High
Heating
Cooling
Heating Low
Heating High
Cooling (Max)
042040
042060
042080
060080
26,000
40,000
25,000
25,000
25,000
38,000
38,000
37,000
25,000
25,000
25,000
38,000
37,000
37,000
96.6
95
96.1
96.6
95
96.1
25—55
30—60
0.10
0.50
585 (690**)
800
1400
39,000
60,000
37,000
36,000
36,000
57,000
56,000
56,000
37,000
36,000
36,000
57,000
56,000
56,000
94.1
92.7
93.7
94.1
92.7
93.7
50—80
35—65
0.12
0.50
500 (590**)
1065
1400
52,000
80,000
49,000
49,000
49,000
75,000
75,000
75,000
49,000
49,000
49,000
75,000
75,000
75,000
94.1
92.7
93.7
94.1
92.7
93.7
50—80
35—65
0.15
0.50
720 (850**)
1500
1395
52,000
80,000
49,000
49,000
49,000
75,000
75,000
75,000
49,000
49,000
49,000
75,000
75,000
75,000
94.1
92.7
93.7
94.1
92.7
93.7
50—80
35—65
0.15
0.50
705 (830**)
1500
1990
8.9
12.0
14
31
15
8.9
12.0
14
31
15
Heating
Cooling
2
Manufacturer
Minimum Inlet Pressure (In. wc)
Maximum Inlet Pressure (In. wc)
060120
65,000
78,000
100,000
120,000
61,000
73,000
61,000
73,000
61,000
73,000
94,000
113,000
94,000
113,000
93,000
112,000
61,000
73,000
61,000
73,000
61,000
73,000
94,000
113,000
94,000
113,000
93,000
112,000
94.1
94.1
92.7
92.7
93.7
93.7
94.1
94.1
92.7
92.7
93.7
93.7
50—80
50—80
45—75
45—75
0.20
0.20
0.50
0.50
920 (1085**) 1160 (1370**)
1525
1880
2000
2100
13.8
18.1
12
32
20
SPST
Selectable 90, 120, 150, or 180 Sec Intervals
3
4
4
5
1/2-in. NPT
11.6
15.3
12
37
20
6
White-Rodgers
4.5 (Natural Gas)
13.6 (Natural Gas)
Hot Surface
Ignition Device
BLOWER DATA
Direct-Drive Motor HP (ICM)
Motor Full Load Amps
RPM (Nominal)—Speeds
Blower Wheel Diameter X Width (In.)
Filter Size (In.)—Permanent Washable
115—60—1
104—127
8.9
13.8
12.0
17.9
14
12
31
32
15
20
40va
25va
34va
Standard
060100
1/2
7.7
1/2
7.7
1/2
1
1
1
7.7
12.8
12.8
12.8
Variable 250—1300
11 X 10
10 X 7
11 X 10
11 X 10
11 X 10
11 X 10
(1) 24 X 25 X 1(1) 16 X 25 X 1(1) 20 X 25 X 1(1) 20 X 25 X 1(1) 20 X 25 X 1(1) 24 X 25 X 1
* Gas input ratings are certified for elevations to 2000 ft. For elevations above 2000 ft, reduce ratings 2% for each 1000 ft above sea level. In Canada, from 2000 to
4500 ft above sea level, derate the unit 5%.
† Capacity and AFUE in accordance with U.S. Government DOE test procedures.
‡ Airflow shown is for bottom only return-air supply. For air delivery above 1800 CFM, see Air Delivery curve for other options. A filter is required for each return-air
supply.
** Low heat CFM when low-heat rise adjustment switch (SWI-3) on furnace control is used.
†† Permissible voltage limits for proper furnace operation.
‡‡ Unit ampacity = 125% of largest component’s full load amps plus 100% of all other potential operating components (EAC, humidifier, etc.)
*** Length shown is measured 1 way along wire path between unit and service panel for maximum 2% voltage drop.
††† Time-delay type is recommended.
†††† High-pressure switch must be used when operating a dual fuel system. Outdoor Temperature Sensor is packaged with the Thermidistat Control and dual fuel
thermostat to gain the full benefit and features.
—5—
BRYANT ACCESSORIES*
DESCRIPTION
EZ Flex Media Filter with end
caps – 16 in. (9 pack)
EZ Flex Media Filter with end
caps – 20 in. (9 pack)
EZ Flex Media Filter with end
caps – 24 in. (6 pack)
Replacement EZ Flex Filter – 16 in. (10 pack)
Replacement EZ Flex Filter – 20 in. (10 pack)
Replacement EZ Flex Filter – 24 in. (10 pack)
Unframed filter, one inch – 16x25
Unframed filter, one inch – 20x25
Unframed filter, one inch – 24x25
Combustible Floor Base (not required when evaporator
coil case is used)
Natural-to-Propane Gas Conversion Kit (Single Kit)*
Propane-to-Natural Gas Conversion Kit (Single Kit)
ECM Motor Simulator (replaces the ECM motor to aid trouble shooting)
Door Gasket Kit
Advanced Product Monitor (software and hearware to link
PC laptop to control board)
ECM Control Replacement Module - 1/2 HP
ECM Control Replacement Module - 1 HP
Downflow Base ‡‡‡
Vent Termination Kit (Bracket Only for 2 Pipes)
Concentric Vent Termination Kit (Single Pipe)
Condensate Freeze Protection Kit
Condensate Neutralizer Kit (Obtained thru RCD)
Electronic or Mechanical Air Cleaner****
Humidifier
Heat/Energy Recovery Ventilator
Gas Orifice Kit (Qty 50) Size 42
Gas Orifice Kit (Qty 50) Size 43
Gas Orifice Kit (Oty 50) Size 44
Gas Orifice Kit (Oty 50) Size 45
Gas Orifice Kit (Oty 50) Size 46
Gas Orifice Kit (Oty 50) Size 47
Gas Orifice Kit (Oty 50) Size 48
Gas Orifice Kit (Oty 50) Size 54
Gas Orifice Kit (Oty 50) Size 55
Gas Orifice Kit (Oty 50) Size 56
Gas Orifice Kit (Oty 50)1.25 mm
Gas Orifice Kit (Oty 50)1.30mw
UV Lights
NON-PROGRAMMABLE
TSTATBBNAC01-C
TSTATBBNHP01-C
TSTATBBN2S01-C
TSTATBBPRH01-B**
PROGRAMMABLE THERMOSTAT SELECTION
TSTATBBPAC01-B
TSTATBBPHP01-B*
TSTATBBP2S01-B*
TSTATBBSAC01
TSTATBBPDF01-B**
TSTATBBPRH01-B***
ZONING CONTROL SELECTION
ZONEBB3Z(AC/HP)01
ZONEBB2KIT01-B
ZONEBB4KIT01-B
ZONEBB8KIT01-B
PART NO.
042040
EXPXXLMC0016
042060 04080
06080
060100
X
X
06120
X
EXPXXLMC0020
X
EXPXXLMC0024
X
X
EXPXXFIL0016
EXPXXFIL0020
EXPXXFIL0024
KGAWF1301UFR
KGAWF1306UFR (6-pack)
KGAWF1401UFR
KGAWF1406UFR (6 pack)
KGAWF1501UFR
KGAWF1506UFR (6 pack)
X
KGASB0201ALL
X
X
X
X
X
KGANP4001ALL
KGAPN3301ALL
KGASD0201FMS
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
HK44EA120
HK52EA120
X
X
X
KGASB0201ALL
2-in.—KGAVT0101BRA 3-in.—KGAVT0201BRA
2-in.—KGAVT0501CVT 3-in.—KGAVT0601CVT
KGAHT0101CFP
P908-0001
Model EACB, EZXCAB, or FILCAB
Model HUM
Models HRV or ERV
KGAHA0150N42
KGAHA0250N43
KGAHA0350N44
KGAHA0450N45
KGAHA0550N46
KGAHA1550N47
KGAHA1850N48
KGAHA0850P54
KGAHA0750P55
KGAHA0850P56
KGAHA5750125
KGAHA5750130
Model UVL
CONTROLS—THERMOSTAT AND ZONING
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
KGBAC0110DGK
KGAFP0201APM
X
X
X
X
X
S
X
X
S
S
S
X
X
X
X
See Installation Instructions
for model, altitude, and
heat value usages.
For use with 1-spd. Air Conditioner - deg. F/C, Auto Changeover
For use with 1-spd. Air Conditioner - deg. F/C, Auto Changeover
For use with 2-spd. Air Conditioner - deg. F/C, Auto Changeover
For multi-use / stage configurations - deg. F/C, Auto Changeover
For use with 1-spd. Air Conditioner - deg. F/C, Auto Changeover, 7-Day Programmable
For use with 1-spd. Air Conditioner - deg. F/C, Auto Changeover, 7-Day Programmable
For use with 2-spd. Air Conditioner - deg. F/C, Auto Changeover, 7-Day Programmable
For use with 1-spd. Air Conditioner - deg. F/C, Auto Changeover, 5-2 Day Programmable
For use with multi-stage applications - deg. F/C, Auto Changeover, 7-Day Programmable
For multi-use / stage configurations - deg. F/C, Auto Changeover, 7-Day Programmable
Zone Perfect Two-Zone kit
Zone Perfect Plus 2-Zone kit
Zone Perfect Plus 4-Zone kit
Zone Perfect Plus 8-Zone kit
*
S
*
**
***
Factory-authorized and field installed. Gas conversion kits are CSA (A.G.A. and C.G.A.) recognized.
16 x 25 filters suitable for side return on all furnace sizes.
Model HP and 2S thermostat must be field converted to air conditioner operation.
Dual Fuel thermostat is used with furnace and heat pump application.
Thermidistat can be configured for multiple use and staging, it must be configured for each specific application.
‡‡‡ Required for installation on combustible floors when no coil box is used, or when any coil box other than a Bryant CD5, CK5 or KCAKC cased
coil is used.
ECM—Electronically Commutated Motor.
**** An external filter is required for right-side return-air installations.
—6—
COMBUSTION-AIR AND VENT PIPING FOR DIRECT VENT/2-PIPE (ALL SIZES) AND
NON-DIRECT VENT/1-PIPE (SIZES 040 THROUGH 120 ONLY) APPLICATIONS
MAXIMUM ALLOWABLE PIPE LENGTH (FT)
DIRECT VENT (2-PIPE) ONLY
ALTITUDE
0 to 2000
UNIT SIZE
(BTUH)
Termination
Type
40,000
2 Pipe or 2-In.
Concentric
60,000
2 Pipe or 2-In.
Concentric
80,000
2 Pipe or 2-In.
Concentric
100,000
2 Pipe or 2-In.
Concentric
120,000
2 Pipe or 3-In.
Concentric
Pipe Dia
(IN.)*
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
2-1/2
3
3†
DIRECT VENT (2-PIPE) ONLY
ALTITUDE
UNIT SIZE
(BTUH)
40,000
60,000
2001 to 3000
80,000
100,000
120,000
ALTITUDE
3001 to 4000
UNIT SIZE
(BTUH)
Termination
Type
Pipe Dia
(IN.)*
1-1/2
2
1-1/2
2 Pipe or 2-In.
Concentric
2
1-1/2
2 Pipe or 2-In.
Concentric
2
2
2 Pipe or 2-In.
Concentric
2-1/2
3
2 Pipe or 3-In.
Concentric
3†
DIRECT VENT (2-PIPE) ONLY
2 Pipe or 2-In.
Concentric
Termination
Type
40,000
2 Pipe or 2-In.
Concentric
60,000
2 Pipe or 2-In.
Concentric
80,000
2 Pipe or 2-In.
Concentric
100,000
2 Pipe or 2-In.
Concentric
120,000
2 Pipe or 3-In.
Concentric
Pipe Dia
(IN.)*
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
3
3†
DIRECT VENT (2-PIPE) ONLY
ALTITUDE
4001 to 5000‡
UNIT SIZE
(BTUH)
Termination
Type
40,000
2 Pipe or 2-In.
Concentric
60,000
2 Pipe or 2-In.
Concentric
80,000
2 Pipe or 2-In.
Concentric
100,000
2 Pipe or 2-In.
Concentric
120,000
2 Pipe or 3-In.
Concentric
Pipe Dia
(IN.)*
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
NON-DIRECT VENT
(1-PIPE) ONLY
Pipe Dia
(IN.)*
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
2-1/2
3
3
NON-DIRECT VENT
(1-PIPE) ONLY
Pipe Dia
(IN.)*
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
3
3
NON-DIRECT VENT
(1-PIPE) ONLY
Pipe Dia
(IN.)*
1-1/2
70
1-1/2
2
1-1/2
2
2
2-1/2
3
3
NON-DIRECT VENT
(1-PIPE) ONLY
Pipe Dia
(IN.)*
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
3†
3
See notes on page 9.
—7—
NUMBER OF 90° ELBOWS
1
2
3
4
5
6
50
70
50
70
30
70
45
70
10
35
70
45
70
45
70
25
70
40
70
NA
30
70
40
70
40
70
20
70
35
70
NA
15
70
35
70
35
70
15
70
30
70
NA
NA
70
30
70
30
70
10
70
25
70
NA
NA
70
25
70
25
70
5
70
20
70
NA
NA
70
NUMBER OF 90° ELBOWS
1
2
3
4
5
6
45
70
45
70
26
70
40
70
31
63
40
70
40
70
21
70
35
70
26
62
35
70
35
70
16
70
30
70
12
62
30
70
30
70
11
70
25
70
NA
61
25
70
25
70
6
70
20
70
NA
61
20
70
20
70
NA
70
15
70
NA
61
NUMBER OF 90° ELBOWS
1
2
3
4
5
6
42
70
42
70
25
70
38
70
29
59
37
70
37
70
20
70
33
70
24
59
32
70
32
70
15
70
28
70
10
58
27
70
27
70
10
70
23
70
NA
57
22
70
22
70
5
70
18
70
NA
57
17
17
70
NA
70
13
70
NA
56
NUMBER OF 90° ELBOWS
1
2
3
4
5
6
40
70
40
70
23
70
36
70
35
70
35
70
18
70
31
70
30
70
30
70
13
70
26
70
25
70
25
70
8
70
21
70
20
70
20
70
NA
70
16
70
15
70
15
70
NA
68
11
70
56
55
54
53
52
52
COMBUSTION-AIR AND VENT PIPING FOR DIRECT VENT/2-PIPE (ALL SIZES) AND
NON-DIRECT VENT/1-PIPE (SIZES 040 THROUGH 120 ONLY) APPLICATIONS
MAXIMUM ALLOWABLE PIPE LENGTH (FT)
DIRECT VENT (2-PIPE) ONLY
ALTITUDE
5001 to 6000‡
UNIT SIZE
(BTUH)
40,000
2 Pipe or 2-In.
Concentric
60,000
2 Pipe or 2-In.
Concentric
80,000
2 Pipe or 2-In.
Concentric
100,000
2 Pipe or 2-In.
Concentric
120,000
ALTITUDE
6001 to 7000‡
Termination
Type
UNIT SIZE
(BTUH)
Pipe Dia
(IN.)*
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
2 Pipe or 3-In.
3†
Concentric
DIRECT VENT (2-PIPE) ONLY
Termination
Type
40,000
2 Pipe or 2-In.
Concentric
60,000
2 Pipe or 2-In.
Concentric
80,000
2 Pipe or 2-In.
Concentric
100,000
2 Pipe or 2-In.
Concentric
120,000
2 Pipe or 3-In.
Concentric
ALTITUDE
7001 to 8000‡
Termination
Type
40,000
2 Pipe or 2-In.
Concentric
60,000
2 Pipe or 2-In.
Concentric
80,000
2 Pipe or 2-In.
Concentric
100,000
2 Pipe or 2-In.
Concentric
120,000
2 Pipe or 3-In.
Concentric
NON-DIRECT VENT
(1-PIPE) ONLY
Pipe Dia
(IN.)*
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
3
Pipe Dia
(IN.)*
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
NON-DIRECT VENT
(1-PIPE) ONLY
Pipe Dia
(IN.)*
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
3†
3
DIRECT VENT (2-PIPE) ONLY
UNIT SIZE
(BTUH)
Pipe Dia
(IN.)*
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
Continued
NON-DIRECT VENT
(1-PIPE) ONLY
Pipe Dia
(IN.)*
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
3†
3
See notes on page 9.
—8—
NUMBER OF 90° ELBOWS
1
2
3
4
5
6
37
70
37
70
22
70
33
70
32
70
32
70
17
70
28
70
27
70
27
70
12
70
23
70
22
70
22
70
7
70
18
70
17
70
17
70
NA
68
13
70
12
70
12
70
NA
63
8
70
53
52
50
49
48
47
NUMBER OF 90° ELBOWS
1
2
3
4
5
6
35
70
35
70
20
70
31
70
30
70
30
70
15
70
26
70
25
68
25
68
10
68
21
68
20
67
20
67
5
67
16
67
15
66
15
66
NA
62
11
66
10
64
10
64
NA
57
6
64
49
48
47
45
44
43
NUMBER OF 90° ELBOWS
1
2
3
4
5
6
32
66
32
66
18
66
29
66
27
65
27
65
13
65
24
65
22
63
22
63
8
63
19
63
17
62
17
62
NA
62
14
62
12
60
12
60
NA
57
9
60
7
59
7
59
NA
52
NA
59
46
44
43
41
40
38
COMBUSTION-AIR AND VENT PIPING FOR DIRECT VENT/2-PIPE (ALL SIZES) AND
NON-DIRECT VENT/1-PIPE (SIZES 040 THROUGH 120 ONLY) APPLICATIONS
MAXIMUM ALLOWABLE PIPE LENGTH (FT)
Termination
Type
Pipe Dia
(IN.)*
40,000
2 Pipe or 2-In.
Concentric
60,000
2 Pipe or 2-In.
Concentric
80,000
2 Pipe or 2-In.
Concentric
100,000
2 Pipe or 2-In.
Concentric
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
NON-DIRECT VENT
(1-PIPE) ONLY
Pipe Dia
(IN.)*
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
120,000
2 Pipe or 3-In.
Concentric
3†
3
DIRECT VENT (2-PIPE) ONLY
ALTITUDE
8001 to 9000‡
UNIT SIZE
(BTUH)
Termination
Type
Pipe Dia
(IN.)*
40,000
2 Pipe or 2-In.
Concentric
60,000
2 Pipe or 2-In.
Concentric
80,000
2 Pipe or 2-In.
Concentric
100,000
2 Pipe or 2-In.
Concentric
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
NON-DIRECT VENT
(1-PIPE) ONLY
Pipe Dia
(IN.)*
1-1/2
2
1-1/2
2
1-1/2
2
2
2-1/2
120,000
2 Pipe or 3-In.
Concentric
3†
3
DIRECT VENT (2-PIPE) ONLY
ALTITUDE
9001 to 10000‡
UNIT SIZE
(BTUH)
Continued
NUMBER OF 90° ELBOWS
1
2
3
4
5
6
30
62
30
62
17
62
27
62
25
60
25
60
12
60
22
60
20
58
20
58
7
58
17
58
15
56
15
56
NA
56
12
56
10
55
10
55
NA
51
7
55
5
53
5
53
NA
46
NA
53
43
41
39
37
35
34
NUMBER OF 90° ELBOWS
1
2
3
4
5
6
27
57
27
57
15
57
24
57
22
55
22
55
10
55
19
55
17
53
17
53
5
53
14
53
12
51
12
51
NA
51
9
51
7
49
7
49
NA
46
NA
49
NA
47
NA
47
NA
41
NA
47
39
37
35
33
31
29
* Disk usage—Unless otherwise stated, use perforated disk assembly (factory-supplied in loose parts bag).
† Wide radius elbow.
‡ Vent sizing for Canadian installations over 4500 ft (1370m) above sea level are subject to acceptance by the local authorities having jurisdiction.
NA—Not Allowed; pressure switch will not make.
NOTES:
1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
2. Size both the combustion-air and vent pipe independently, determine the smallest diameter allowed by the table for each pipe, then use the larger diameter for both pipes.
3. Assume two 45° elbows equal one 90° elbow. Long radius elbows are desirable and may be required in some cases.
4. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
5. The minimum pipe length is 5 ft for all applications.
—9—
MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT)
WITH INSULATION IN WINTER DESIGN TEMPERATURE AMBIENT*
INSULATION THICKNESS (IN.)†
WINTER DESIGN MAXIMUM PIPE
TEMP °F
DIA
UNIT SIZE
042040
042060
042080
060080
060100
060120
0
3/8
1/2
3/4
1
20
2
21
37
42
50
57
0
2
10
22
25
30
35
–20
2
5
14
17
21
25
20
2
30
55
61
70
70
53
0
2
16
33
38
46
–20
2
9
23
26
33
38
20
2
37
65
70
70
70
0
2
20
39
45
55
63
–20
2
11
27
31
39
45
20
2-1/2
41
70
70
70
70
0
2-1/2
21
42
48
59
68
–20
2-1/2
11
28
33
41
49
20
3
49
70
70
70
70
0
3
26
51
58
70
70
–20
3
15
35
40
50
59
* Pipe length (ft) specified for maximum vent pipe lengths located in unconditioned spaces. Vent pipes located in unconditioned space cannot exceed total
allowable pipe length as specified in maximum allowable pipe length table.
† Insulation thickness based on R value of 3.5 per in.
ACCESSORIES
COMBUSTION-AIR PIPE FOR NON-DIRECT (1-PIPE) VENT
APPLICATION (SIZES 040 THROUGH 120 ONLY)
FIELD-SUPPLIED
2-IN. DIAMETER
PVC 90° ELBOW
FIELD-SUPPLIED
2-IN. DIAMETER
PVC PIPE
LENGTH OF STRAIGHT
PIPE PORTION OF COMBUSTION
AIR INLET PIPE ASSEMBLY (IN.)
CASING WIDTH
A
17-1/2
8-1/2 ± 1/2
21
10-1/2 ± 1/2
24-1/2
12 ± 1/2
A
COMBUSTION-AIR DISC
(FACTORY-SUPPLIED IN
LOOSE PARTS BAG)
A96211
A96211
CONCENTRIC VENT FOR DIRECT VENT (2-PIPE) APPLICATION (ALL MODEL SIZES)
B IN. DIA PVC
VENT/EXHAUST
F
E
C IN. DIA
13/16
11/2
D
A
B IN. DIA PVC
INTAKE/COMBUSTION AIR
A97110
DIMENSIONS (IN.)
KIT PART NO.
A*
B
C
D†
E
F
KGAVT0501CVT
33-3/8
2
3-1/2
16-5/8
6-1/4
5-3/4
KGAVT0601CVT
38-7/8
3
4-1/2
21-1/8
7-3/8
6-1/2
* Dimension A will change accordingly as dimension D is lengthened or shortened.
† Dimension D may be lengthened to 60 in. maximum. Dimension D may also be shortened by cutting the pipes provided in the kit to 12 in. minimum.
—10—
ACCESSORY DOWNFLOW SUBBASE
;;;;
;;;;
LOCATING
TAB
1 1/4″ TYP
PLENUM
OPENING
B
D
A
1
2
3
4
LOCATING
TAB
4
3
2
A88207
A97427
Disassembled
FURNACE
CASING
WIDTH
C
FACTORY-SUPPLIED
FIELD-INSTALLED
INSULATION
1
Assembled
PLENUM OPENING*
FLOOR OPENING
FURNACE IN DOWNFLOW APPLICATION
A
B
C
D
HOLE NO.
FOR WIDTH
ADJUSTMENT
17-1/2
Furnace with or without Cased Coil
Assembly or Coil Box
15-1/8
19
16-3/4
20-3/8
3
21
Furnace with or with Cased Coil
Assembly or Coil Box
18-5/8
19
20-1/4
20-3/8
2
24-1/2
Furnace with or without Cased Coil
Assembly or Coil Box
22-1/8
19
23-3/4
20-3/8
1
* The plenum should be constructed 1/4-in. smaller in width and depth than the plenum dimensions shown above.
MEDIA FILTER CABINET
25 5/8"
23 5/8"
24 3/8"
Opening with Flanges Bent
3/8
23 "
23 1/8"
Opening
B Opening
A
Duct Side
Furnace Side
23 3/4"
Centerline Screw Slots
5 3/4"
Media
Filter Cabinet
A
B
16"
17"
16"
060-12, 080-12, 080-16
20"
21"
20"
100-16, 100-20
24"
25"
24"
120-20
Shipped with sizes
A05186
—11—
AIR DELIVERY - CFM (Bottom Return With Filter)*
Unit
Size
Operating Mode
CFM Airflow
Setting
External Static
Pressure Range*
0.1
0.2
External Static Pressure (ESP)
0.3 0.4 0.5 0.6 0.7 0.8
AAIRFLOW (CFM)
0.9
042040
†† Low Heat
585†
0-0.60
585 580 585 585 585 580
High Heat
800
0-1.0
800 800 800 800 800 790 780 760 750
†† 1-1/2-Ton Cooling
525
0-0.50‡
525 525 505 505 505
†† 2-Ton A/C Cooling
700
0-0.90‡
675 685 695 695 700 700 700 700 700
2-1/2-Ton A/C Cooling
875
0-1.0
875 875 875 875 865 855 835 820 795
3-Ton A/C Cooling
1050
0-1.0
1050 1050 1050 1050 1045 1020 1010 995 980
1225
0-1.0
1225 1225 1225 1225 1225 1225 1220 1210 1195
3-1/2-Ton A/C Cooling
Maximum
1400
0-1.0
1390 1400 1400 1400 1400 1375 1330 1285 1235
042060
†† Low Heat
500†
0-0.50
500 495 485 460 430
High Heat
1065
0-1.0
1055 1065 1065 1065 1065 1065 1065 1065 1060
†† 1-1/2-Ton A/C Cooling
525
0-0.50‡
525 525 510 495 465
†† 2-Ton A/C Cooling
700
0-0.50‡
700 700 695 680 680
2-1/2-Ton A/C Cooling
875
0-1.0‡
850 870 875 875 870 860 845 825 810
3-Ton A/C Cooling
1050
0-1.0
1050 1050 1050 1050 1050 1050 1050 1050 1050
3-1/2-Ton A/C Cooling
1225
0-1.0
1210 1220 1225 1225 1225 1225 1225 1225 1215
1400
0-1.0
1400 1400 1400 1400 1400 1400 1400 1400 1385
Maximum
042080***
†† Low Heat
720†
0-0.50
720 715 715 720 720
High Heat
1500
0-1.0
1500 1500 1470 1420 1375 1330 1290 1250 1210
†† 1-1/2-To A/C Cooling
525
0-0.50‡
525 525 515 505 485
†† 2-Ton A/C Cooling
700
0-0.50‡
700 700 695 695 700
2-1/2-Ton A/C Cooling
875
0-1.0‡
840 855 875 875 875 875 870 855 850
3-Ton A/C Cooling
1050
0-1.0‡
1050 1050 1050 1050 1050 1050 1045 1045 1040
3-1/2-Ton A/C Cooling
1225
0-1.0‡
1225 1225 1225 1225 1225 1225 1225 1225 1225
Maximum
1400
0-1.0‡
1400 1400 1400 1400 1395 1355 1315 1275 1230
060080***
†† Low Heat
705†
0-0.50
705 680 680 675 675
High Heat
1500
0-1.0
1500 1500 1500 1500 1500 1500 1500 1495 1485
†† 2-Ton A/C Cooling
700
0-0.50‡
700 670 665 665 655
†† 2-1/2-Ton A/C Cooling
875
0-0.50‡
875 875 875 875 875
3-Ton A/C Cooling
1050
0-1.0‡
1050 1050 1050 1045 1050 1050 1045 1045 1045
3-1/2-Ton A/C Cooling
1225
0-1.0‡
1215 1220 1220 1220 1225 1225 1225 1225 1225
4-Ton A/C Cooling
1400
0-1.0‡
1370 1385 1385 1395 1395 1395 1395 1400 1395
5-Ton A/C Cooling
1750
0-1.0
1750 1750 1750 1750 1750 1750 1745 1740 1735
Maximum
2000
0-1.0
2000 2000 2000 2000 1990 1975 1950 1925 1900
060100***
Low Heat
920†
0-1.0
920 915 915 920 920 920 915 900 895
High Heat
1525
0-1.0
1525 1525 1525 1525 1520 1515 1515 1515 1515
†† 2-Ton A/C Cooling
700
0-0.50‡
700 700 700 690 685
†† 2-1/2-Ton A/C Cooling
875
0-0.50‡
865 875 870 870 875
3-Ton A/C Cooling
1050
0-1.0‡
1035 1045 1050 1045 1050 1050 1050 1050 1050
3-1/2-Ton A/C Cooling
1225
0-1.0‡
1180 1195 1215 1225 1225 1225 1225 1225 1225
4-Ton A/C Cooling
1400
0-1.0‡
1400 1400 1400 1400 1400 1400 1400 1395 1375
5-Ton A/C Cooling
1750
0-1.0
1740 1745 1750 1750 1750 1750 1750 1750 1750
Maximum
2000
0-1.0
2000 2000 2000 2000 2000 2000 1985 1965 1940
060120
Low Heat
1180†
0-1.0
1160 1175 1180 1180 1180 1180 1180 1180 1180
High Heat
1885
0-1.0
1875 1880 1885 1885 1885 1885 1885 1885 1880
†† 2-Ton A/C Cooling
700
0-0.50‡
700 700 700 700 695
†† 2-1/2-Ton A/C Cooling
875
0-0.50‡
875 875 875 870 870
3-Ton A/C Cooling
1050
0-1.0‡
1035 1040 1050 1050 1050 1050 1050 1025 1005
3-1/2-Ton A/C Cooling
1225
0-1.0‡
1205 1210 1225 1225 1225 1225 1225 1225 1220
4-Ton A/C Cooling
1400
0-1.0‡
1390 1400 1400 1400 1400 1400 1395 1385 1370
5-Ton A/C Cooling
1750
0-1.0‡
1745 1740 1745 1745 1745 1745 1745 1740 1730
6-Ton A/C Cooling
2100
0-1.0
2100 2100 2100 2100 2100 2095 2075 2040 1975
Maximum
2100
0-1.0
2100 2100 2100 2100 2100 2095 2075 2040 1975
Actual external static pressure (ESP) can be determined by using the fan laws (CFM 2 proportional to ESP); such as,
*
a system with 1750 CFM at 0.5 ESP would operate at high-heating airflow of 1500 CFM at 0.37 ESP and low-heating airflow
of 705 CFM at 0.08 ESP.
†
Low heat CFM when low-heat rise adjustment switch (SW1-3) and comfort/efficiency adjustment switch (SW1-4) on
control center are OFF.
‡
Ductwork must be sized for high-heating CFM within the operational range of ESP.
**
Wattage data provided is for the circulating blower with bottom return and does not include draft inducer, accessories,
or gas controls.
††
Operation within the blank areas of the chart is not recommended because high-heat operation will be above 1.0 ESP.
***
All airflows on 21" casing size furnaces are 5% less on side return only installations.
—12—
1.0
735
700
720
965
1175
1185
1050
805
1050
1195
1345
1170
850
1030
1195
1190
1480
1035
1220
1390
1725
1865
890
1515
1045
1225
1365
1740
1910
1180
1870
1000
1215
1360
1715
1910
1910
AIR DELIVERY - POWER DRAW (WATTS)**
Unit
Operating Mode
CFM Airflow
External Static
External Static Pressure (ESP)
Size
Setting
Pressure Range*
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
042040
POWER DRAW (WATTS)* *
†† Low Heat
585†
0-0.60
55
71
91 108 129 147
High Heat
800
0-1.0
97 119 141 165 187 209 230 252 274
†† 1-1/2-Ton Cooling
525
0-0.50‡
49
63
75
94 107
†† 2-Ton A/C Cooling
700
0-0.90‡
67
92 117 134 159 186 216 239 267
2-1/2-Ton A/C Cooling
875
0-1.0
112 138 164 188 210 236 256 275 295
3-Ton A/C Cooling
1050
0-1.0
167 202 233 263 288 307 334 364 388
1225
0-1.0
232 266 308 341 380 413 448 491 524
3-1/2-Ton A/C Cooling
Maximum
1400
0-1.0
317 379 425 475 527 535 542 546 551
042060
†† Low Heat
500†
0-0.50
43
55
70
83
97
High Heat
1065
0-1.0
150 175 200 234 264 292 321 352 378
†† 1-1/2-Ton A/C Cooling
525
0-0.50‡
46
62
74
91 104
†† 2-Ton A/C Cooling
700
0-0.50‡
69
86 105 124 138
101 126 154 179 202 226 248 267 287
2-1/2-Ton A/C Cooling
875
0-1.0‡
3-Ton A/C Cooling
1050
0-1.0
149 174 199 233 263 291 320 351 377
3-1/2-Ton A/C Cooling
1225
0-1.0
210 248 278 312 344 384 418 449 476
1400
0-1.0
311 341 384 420 455 495 529 568 602
Maximum
042080***
†† Low Heat
720†
0-0.50
80
95 118 142 168
High Heat
1500
0-1.0
442 507 519 527 535 543 550 557 564
†† 1-1/2-Ton A/C Cooling
525
0-0.50‡
50
63
80
96 111
†† 2-Ton A/C Cooling
700
0-0.50‡
73
94 113 133 156
102 133 161 191 218 241 268 291 320
2-1/2-Ton A/C Cooling
875
0-1.0‡
168 206 240 273 299 324 356 385 418
3-Ton A/C Cooling
1050
0-1.0‡
245 277 317 355 394 431 481 522 558
3-1/2-Ton A/C Cooling
1225
0-1.0‡
Maximum
1400
0-1.0‡
376 422 478 520 527 537 544 553 560
060080***
†† Low Heat
705†
0-0.50
76
90 112 129 149
High Heat
1500
0-1.0
381 432 478 511 564 610 650 688 732
†† 2-Ton A/C Cooling
700
0-0.50‡
76
89 109 127 148
†† 2-1/2-Ton A/C Cooling
875
0-0.50‡
113 136 157 178 208
158 191 213 239 266 300 326 351 392
3-Ton A/C Cooling
1050
0-1.0‡
227 262 294 322 360 390 432 459 501
3-1/2-Ton A/C Cooling
1225
0-1.0‡
298 340 384 417 458 493 534 574 607
4-Ton A/C Cooling
1400
0-1.0‡
5-Ton A/C Cooling
1750
0-1.0
587 631 664 724 772 815 861 907 943
Maximum
2000
0-1.0
839 911 973 1029 1066 1104 1134 1149 1170
060100***
Low Heat
920Ü
0-1.0
113 136 159 186 221 243 263 285 316
High Heat
1525
0-1.0
378 419 448 486 518 561 606 650 696
†† 2-Ton A/C Cooling
700
0-0.50‡
74
89 109 126 146
†† 2-1/2-Ton A/C Cooling
875
0-0.50‡
99 124 147 168 200
144 177 207 229 258 288 319 350 385
3-Ton A/C Cooling
1050
0-1.0‡
3-1/2-Ton A/C Cooling
1225
0-1.0‡
189 223 268 306 346 377 399 447 488
283 328 360 400 439 474 510 541 575
4-Ton A/C Cooling
1400
0-1.0‡
5-Ton A/C Cooling
1750
0-1.0
502 558 602 657 715 754 797 847 889
Maximum
2000
0-1.0
766 819 887 947 991 1030 1065 1101 1129
060120
0-1.0
162 194 228 265 297 325 363 392 432
Low Heat
1180†
High Heat
1885
0-1.0
547 607 652 715 756 816 870 912 958
†† 2-Ton A/C Cooling
700
0-0.50‡
72
89 113 128 146
†† 2-1/2-Ton A/C Cooling
875
0-0.50‡
98 119 140 163 187
126 156 194 221 249 279 307 327 351
3-Ton A/C Cooling
1050
0-1.0‡
178 211 253 284 314 352 382 424 455
3-1/2-Ton A/C Cooling
1225
0-1.0‡
4-Ton A/C Cooling
1400
0-1.0‡
257 310 348 388 421 458 488 528 557
461 498 552 618 665 711 760 800 847
5-Ton A/C Cooling
1750
0-1.0‡
6-Ton A/C Cooling
2100
0-1.0
794 867 931 996 1042 1092 1135 1152 1124
Maximum
2100
0-1.0
592 673 746 811 885 935 994 1026 1102
2
* Actual external static pressure (ESP) can be determined by using the fan laws (CFM proportional to ESP); such as,
a system with 1750 CFM at 0.5 ESP would operate at high-heating airflow of 1500 CFM at 0.37 ESP and low-heating airflow
of 705 CFM at 0.08 ESP.
† Low heat CFM when low-heat rise adjustment switch (SW1-3) and comfort/efficiency adjustment switch (SW1-4) on
control center are OFF.
‡ Ductwork must be sized for high-heating CFM within the operational range of ESP.
** Wattage data provided is for the circulating blower with bottom return and does not include draft inducer, accessories,
or gas controls.
†† Operation within the blank areas of the chart is not recommended because high-heat operation will be above 1.0 ESP.
*** All airflows on 21" casing size furnaces are 5% less on side return only installations.
—13—
1.0
292
296
317
417
561
563
408
313
407
503
612
572
348
460
568
568
761
425
538
647
988
1182
340
730
415
517
598
930
1152
459
1000
381
494
591
888
1098
1129
COMBUSTION AIR PIPE
(DIRECT VENT/2-PIPE APPLICATION)
OUTDOOR UNIT
VENT PIPE
A/C COIL
HUMIDIFIER
COMBUSTION
AIR INLET
(NON-DIRECT
1-PIPE APPLICATION)
GAS-FIRED
WATER HEATER
ELECTRONIC
AIR CLEANER
FRONT OF
FURNACE
AIRFLOW
A05064
ELECTRONIC
AIR CLEANER
VENT
COMBUSTION AIR
INLET (NON-DIRECT
VENT/ 1-PIPE APPLICATION
COMBUSTION
AIR (DIRECT VENT/
2 PIPE APPLICATION
HUMIDIFIER
OUTDOOR
UNIT
A/C COIL
AIRFLOW
FRONT OF
FURNACE
A05065
—14—
COMBUSTION-AIR INLET
(NON-DIRECT VENT/1-PIPE APPLICATION)
COMBUSTION–AIR PIPE
DIRECT VENT/2-PIPE APPLICATION)
VENT PIPE
ELECTRONIC
AIR CLEANER
FRONT OF FURNACE
FURNACE
CONDENSATE
DRAIN
REFRIGERATION
PIPING
AIR CONDITIONING
COIL
AIRFLOW
A05066
COMBUSTION– AIR PIPE
(DIRECT VENT/2-PIPE
APPLICATION)
COMBUSTION - AIR INLET
(NON-DIRECT VENT/
1-PIPE APPLICATION)
VENT
PIPE
REFRIGERATION
PIPING
AIR CONDITIONING
COIL
ELECTRONIC
AIR CLEANER
AIRFLOW
FURNACE CONDENSATE
DRAIN
—15—
FRONT OF
FURNACE
A05067
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
UNIT MUST BE INSTALLED IN ACCORDANCE
WITH INSTALLATION INSTRUCTIONS
Cancels: PDS 355M.40.11
® 2005 Bryant Heating & Cooling Systems, 7310 W. Morris St.
Indpls, IN 46206
—16—
PRINTED IN U.S.A.
Catalog No. PDS 355A.40.1
9-05