Evolis from 7.2 to 24 kV

Evolis from 7.2 to 24 kV
Vacuum circuit breakers
Evolis from 7.2 to 24 kV
Catalogue
2005
The Guiding System, the new way to create your
electrical installations
A comprehensive offer of products with consistent design
The Guiding System is first and foremost a Merlin Gerin product
offer covering all electrical distribution needs. However, what
makes all the difference is that these products have been designed
to operate togheter: mechanical and electrical compatibility,
interoperability, modularity, communication.
Thus the electrical installation is both optimised and more efficient:
better continuity of supply, enhanced safety for people and
equipment, guaranteed upgradeability, effective monitoring and
control.
Tools to simplify design and implementation
With the Guiding System, you have a comprehensive range of tools
- the Guiding Tools - that will help you increase your product
knowledge and product utilisation. Of course this is in compliance
with current standards and procedures.
These tools include technical booklets and guides, design aid
software, training courses, etc. and are regularly updated.
For a genuine partnership with you
Because each electrical installation is unique, there is no standard
solution. With the Guiding System, the variety of combinations
allows for genuine customisation solutions. You can create and
implement electrical installations to meet your creative
requirements and design knowledge.
You and Merlin Gerin’s Guiding System form a genuine partnership.
For more details on the Guiding System,
consult www.merlin-gerin.com
0
A consistent design of offers from
Medium Voltage to Ultra terminal
All Merlin Gerin offers are designed according to
electrical, mechanical and communication
consistency rules.
The products express this consistency by their
overall design and shared ergonomics.
Electrical consistency:
Discrimination guarantees co-ordination between the operating
characteristics of serial-connected circuit-breakers. Should a
fault occurs downstream, only the circuit-breaker placed
immediately upstream from the fault will trip.
Each product complies with or enhances system performance at coordination level: breaking capacity, Isc, temperature rise, etc. for
more safety, continuity of supply (discrimination) or economic
optimisation (cascading).
The leading edge technologies employed in Merlin Gerin’s
Guiding System ensure high performance levels in discrimination
and cascading of protection devices, electrodynamic withstand of
switches and current distributors, heat loss of devices, distribution
blocks and enclosures.
Likewise, inter-product ElectroMagnetic Compatibilty (EMC) is
guaranteed.
Mechanical consistency:
Each product adopts dimensional standards simplifying and
optimising its use within the system.
It shares the same accessories and auxiliaries and complies with
global ergonomic choices (utilisation mode, operating mode, setting
and configuration devices, tools, etc.) making its installation and
operation within the system a simpler process.
Prefabricated and tested solutions, upstream and downstream
from the device complying with the IEC 60439-1 switchboard
standard.
Communication consistency:
Thanks to the use of standard Web technologies, you can offer
your customers intelligent Merlin Gerin switchboards allowing
easy access to information: follow-up of currents, voltages,
powers, consumption history, etc.
Each product complies with global choices in terms of
communication protocols (Modbus, Ethernet, etc.) for simplified
integration in the management, supervision and monitoring
systems.
Guiding Tools
for more efficient design
and implementation
of your installations.
1
0
SM6
Sepam
Masterpact
Medium voltage switchboard
system from 1 to 36 kV
Protection relays
Protection switchgear
from 100 to 6300 A
Trihal
MV/LV dry cast resin
transformer
from 160 to 5000 kVA
Evolis
MV vacuum
switchgear and
components
from 1 to 24 kV.
The Technical guide
CAD software and tools
These technical guides help you comply with
installation standards and rules i.e.:
The electrical installation guide, the
protection guide, the switchboard
implementation guide, the technical booklets
and the co-ordination tables all form genuine
reference tools for the design of highperformance electrical installations.
For example, the LV protection co-ordination
guide - discrimination and cascading optimises choice of protection and
connection devices while also increasing
markedly continuity of supply in the
installations.
The CAD software and tools enhance
productivity and safety.
They help you create your installations
by simplifying product choice through
easy browsing in the Guiding System
offers.
Last but not least, they optimise
use of our products while also complying
with standards and proper procedures.
2
0
Compact
Multi 9
Prisma Plus
Protection switchgear system
from 100 to 630 A
Modular protection switchgear
system up to 125 A
Functional system for electrical
distribution switchboards
up to 3200 A
Pragma
Enclosures for
distribution
switchboards
up to 160 A
Canalis
Prefabricated Busbar
Trunking
from 25 to 4000 A
PowerLogic
Power
management
Training
Training allows you to acquire the Merlin
Gerin expertise (installation design, work
with power on, etc.) for increased efficiency
and a guarantee of improved customer
service.
The training catalogue includes beginner’s
courses in electrical distribution, knowledge
of MV and LV switchgear, operation and
maintenance of installations, design of LV
installations to give but a few examples.
3
Evolis
Circuit breakers adapted
to your needs
Description
Evolis: a range of circuit breakers
that takes account of your electrical
installations’ requirements today
and in the future.
Evolis: a range of vacuum-type circuit breakers from 7.2 kV to 24 kV,
combining easy selection and a comprehensive offer:
b a fixed, frontal or lateral version
b a withdrawable, frontal version with a circuit breaker and cradle
b a fixed, lateral version equipped with an integrated protection chain
b separately delivered accessories.
Evolis is an integral part of
the Merlin Gerin Guiding System.
The Evolis circuit breaker is operated via a spring mechanism that gives an operating
speed that is independent of the operator and that does not require an auxiliary
power supply.
When the operating mechanism is motorized the circuit breaker can include
telecontrol functions and carry out rapid reclosing cycles.
The various circuit breaker versions are easy to integrate in a cubicle environment.
An Installation Guide details the required procedure.
Applications
Evolis is intended for use in medium voltage network applications, in new installations
or renovation, for utilities companies, infrastructures, the process industry and
the tertiary sector.
It provides protection for all types of applications: cables, overhead lines, motors,
capacitors, transformers, source busbar sections, etc.
Evolis, a fixed, frontal or lateral version
PE55692
PE40002
Here the circuit breaker is in its simplest version. In this case it can be combined
with additional accessories to meet various requirements.
For the fixed lateral version, the MV connection can be on the right
or on the left depending on the type of circuit breaker.
Evolis 24 kV fixed, lateral version
MV connection on the left hand side
4
Evolis 24 kV fixed, frontal version
PE55931
PE55930
Evolis 17.5 kV fixed, frontal version
Evolis 24 kV fixed, lateral version
MV connection on the right hand side
0
Evolis
Circuit breakers adapted
to your needs (cont.)
0
Evolis: a withdrawable, frontal version
PE55693
PE55101
In this version, the circuit breaker is equipped with arms, clusters and a rack
and cradle. The cradle and the circuit breaker can be ordered and delivered
separately.
Evolis 17.5 kV withdrawable, frontal version
Evolis 24 kV withdrawable, frontal version
EVOset: a fixed, lateral version equipped
with an integrated protection chain
PE55932
The EVOset is provided with a fully autonomous integrated protection chain (with
a VIP type control unit) operating without an auxiliary power source. The protection
unit exists in 4 models: VIP30, VIP35, VIP300P and VIP300LL. VIP protection units
are associated with functional current sensors. The circuit breaker is delivered with
its factory-tested protection chain. It therefore simplifies the panel builder’s
installation work.
EVOset 24 kV fixed, lateral version
MV connection on the right hand side
5
Evolis
The very best of vacuum technology
DE60163
As a specialist in breaking technologies,
Merlin Gerin took naturally an interest
in vacuum breaking techniques.
A major R&D investment was made to
develop and engineer Evolis, providing
customers with the very best of vacuum
technology.
Ceramic chamber
Shield
Fixed contact
Mobile contact
Make-up of a vacuum interrupter
Vacuum interrupters basically have two electrical contacts, one fixed and the other
mobile, and a sealed enclosure. The latter enables a high level of vacuum to be
maintained inside the interrupter (less than 10 -2 Pa) to provide insulation between
the open contacts.
The dielectric strength of the vacuum allows the contact-to-contact distance
to be reduced. This short distance together with the low opening speed allow
the use of a low energy control mechanism. A metal clusters provides the link
between the mobile contact and the enclosure.
In order to keep the vacuum level required for the correct operation
of the interrupter for 30 years, the enclosure must be perfectly sealed,
and the various components have to be fully degased. This is achieved by:
b choosing materials that are specifically selected for this application
(metals and ceramics)
b choosing an appropriate assembly process (vacuum, high temperature brazing)
b the use of a “getter” material to absorb the residual gas.
Current breaking in a vacuum interrupter
Metal bellows
At low values of current, these vapors very quickly condense on the shield
and contacts when the arc disappears, thus allowing:
b the vacuum to be re-established
b a contact-to-contact dielectric strength to be restored that is greater than
the recovery voltage: breaking is then complete.
Fig. 1: vacuum interrupter components
DE60164
Current
Electrode
AMF coil
Contact disk
Arc plasma
Axial magnetic field
PE60042
Fig. 2: cross-section of AMF contact
Fig. 3: diffuse vacuum arc AMF technology
6
In vacuum breaking, the electrical arc generated on separation of the contacts
is made up of a plasma of metal vapors produced by the vaporization of the contact
material.
At high currents, the electrical arc in the vacuum switches to a concentrated mode
which causes high, localized temperature rises on the contacts. The existence of
these hot spots is detrimental to the quick restoring of the dielectric strength.
Two techniques can be used in order to avoid this stagnation of the static
concentrated arc:
b the so called RMF (Radial Magnetic Field) technique, involves rotating the arc
thanks to an electromagnetic effect generated by a radial magnetic field;
this therefore limits contact erosion.
b a more recent technique called AMF (Axial Magnetic Field) involves applying
an axial magnetic field parallel to the axis of the two contacts (fig. 2) which allows
a diffuse arc to be maintained (fig. 3) even at high current values. The arc energy
is spread over the whole contact surface area, therefore causing very low levels
of erosion.
b Merlin Gerin has chosen this last technique for the Evolis range.
0
Evolis
The very best of vacuum technology
(cont.)
200110
Merlin Gerin’s choices for Evolis combined
with its industrial expertise provides
customer with a highly reliable range
of circuit breakers. These products are
suitable for the most demanding conditions
with the guarantee of full compliance with
international standards.
AMF technology
Evolis circuit breakers use AMF type vacuum interrupters.
According to technical and economic optimization considerations, the axial magnetic
field is generated:
b either by a coil outside of the interrupter (fig. 4), for rated voltages up to 17.5 kV
b or by a coil integrated in the interrupter contact structure (fig. 5), for the 24 kV
voltage level.
In both cases the AMF vacuum interrupters feature low arc voltages (Uarc of around
50 V) and maximum usage of the contact surface for very low contact erosion.
The advantages provided
The above choices provide customers with the following advantages
in MV circuit breaker applications:
b simple and compact vacuum interrupters
b high electrical endurance meaning that there is no need for contact wear
inspection in normal network protection applications including highly disturbed
overhead line feeders.
DE60162
Fig. 4: 17.5 kV external coil type interrupter
Fig. 5: 24 kV internal coil type interrupter
7
0
Evolis
The very best of vacuum technology
0
(cont.)
PE55694
Systematic advanced control
The main components of the circuit breaker, such as vacuum interrupter and
operating mechanism, are produced by Schneider Electric. The vacuum interrupters
are manufactured in an ultra-modern production unit in France.
During manufacture, each circuit breaker is subjected to systematic advanced testing.
Vacuum interrupter testing
The level of vacuum in each interrupter is tested using the “magnetron discharge
method”.
Using this sophisticated procedure, measurement is very precise and does not
require access to the inside of the interrupter, thus not affecting the airtight seal.
Circuit breaker testing
A rigorous set of tests and measurements is carried out on each circuit breaker.
The results are reported and signed off by the quality control department on each
device’s test certificate to ensure product traceability.
PE55695
Vacuum interrupter
Compliance with standards
b Evolis complies with IEC 62271-100.
b Design and production are certified to ISO 9001: 2000.
Industrial process expertise
DE55746
DE55745
b Production sites are certified to ISO 14001 (environmental standard).
Certification
The certificate of conformity provides guarantees that the circuit breaker:
b has been subject to type tests according to EN 45001 standards procedures
in accredited laboratories by independent organizations
b is in conformity with recognized international standards.
Evolis is currently being certified by external EN 45011 accredited organizations,
members of the STL (Short circuit Testing Liaison):
b EN 45001: general requirements for the competence of testing and calibration
laboratories
b EN 45011: general requirements for bodies of operating product certification
systems.
Environmental care
Product design takes account of the environmental constraints described
in a “Product Environment Profile” dossier (PEP).
An end-of-service-life manual details procedures for dismantling and processing
components.
8
General contents
0
Panorama
11
Evolis 17.5 kV fixed,
frontal version
15
Evolis 17.5 kV withdrawable,
frontal version
33
Evolis 24 kV fixed,
frontal version
53
Evolis 24 kV withdrawable,
frontal version
67
Evolis and EVOset 24 kV
fixed, lateral version
87
Evolis Pilot monitoring device
109
9
0
10
Extended products offer
0
PE55691
Panorama
LV cubicle
components
b Mcb
b protection relay
b lamp
b push button
b terminal blocks
connector
Protection and
control
b UMI
Circuit breaker
b pilot
b cradle
Metering
b VPIS
b PM500
Instrument
transformer
MV cubicle
components
b capacitor insulator
b earthing switch
b heating resistor
b voltage presence
indicator
b crank
b extraction table
11
Panorama
0
Circuit breakers
Evolis from 7.2 kV to 17.5 kV
Evolis 24 kV
DV2
Ue (V)
220/440
525
690
Icu (kA)
100
100
85
Icw 85kA/1s
cat.B
Ics =
100%
Icu
50/60Hz
947-2
IEC
EN 60947-2
BS CEI
UTE
UNE
AS NEMA
VDE
DV2
Icu
Ue
(V)
(kA)
100
100
220/440
85
525
690
Icw
85kA/1s
cat.B
Ics =
100%
Icu
50/60Hz
IEC
947-2
EN 60947-2
AS
NEMA
UNE
BS
CEI
VDE
UTE
Fixed, frontal version
Operating mechanism
on the front
Withdrawable, frontal version
Operating mechanism
on the front
Fixed, frontal version
Operating mechanism
on the front
Withdrawable, frontal version
Operating mechanism
on the front
The “Pilot” option monitors correct The “Pilot” option monitors correct
circuit breaker operation
circuit breaker operation
WEB enabled
WEB enabled
from 25 to 40 kA
from 16 to 31.5 kA
from 16 to 31.5 kA
from 630 to 2500 A
from 630 to 2500 A
from 630 to 2500 A
Rated voltage Ur (kV, 50/60 Hz)
Short circuit rated breaking capacity (Isc)
from 25 to 40 kA
Rated current (Ir)
from 630 to 2500 A
12
Panorama
0
Protection, monitoring and control
EVOset 24 kV
Protection
Protection
and control
MERLIN GERIN
Sepam
on
1 > 51
1 > >51 1o > 51 1o > >51
I1 =
I2 =
I3 =
Fixed, lateral version
Operating mechanism
on the side
Fixed, lateral version
Operating mechanism
on the side - Integrated
protection system
The “Pilot” option monitors correct
circuit breaker operation
VIP30
for phase protection
VIP35
for phase and
earthing protection
VIP300P
for phase protection
VIP300LL
for phase and
earthing protection
WEB enabled
Rated voltage Ur (kV, 50/60 Hz)
ext
0 off
Metering
I on Trip
165A RMS
166A RMS
167A RMS
Sepam series 20
for normal
applications
Sepam series 40
for demanding
applications
Sepam series 80
for full applications
PM500, PM700
for basic metering
PM800
for advanced
metering
CM3000, CM4000
for full metering
and power quality
Short circuit rated breaking capacity (Isc)
from 12.5 to 25 kA
from 12.5 to 20 kA
Rated current (Ir)
from 630 to 1250 A
from 630 to 1250 A
Separate catalogue
13
0
14
Evolis
Evolis 17.5 kV
fixed, frontal version
0
Panorama
11
Main characteristics
16
Description of functions
MV connection
LV connection
Opening circuit
Remote control
Indication
Locking/interlocking
Wiring diagram
17
17
19
20
22
23
24
25
Dimensions
26
Offer structure
27
Order form
29
Separated components
30
Services
32
Evolis 17.5 kV withdrawable, frontal version
Evolis 24 kV fixed, frontal version
Evolis 24 kV withdrawable, frontal version
Evolis and EVOset 24 kV fixed, lateral version
Evolis Pilot monitoring device
33
53
67
87
109
15
Evolis 17.5 kV
fixed, frontal version
Main characteristics
0
PE40002
Electrical characteristics according to IEC 62271-100
Ur 7.2 kV
Isc
Phase to phase distance (mm)
Ud 20 kV 50 Hz, 1 min
25 kA
Up 60 kV peak
Ir
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
Ir
31.5 kA
40 kA
Ur 12 kV
Isc
Phase to phase distance (mm)
Ud 28 kV 50 Hz, 1 min
25 kA
Up 75 kV peak
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
Ir
31.5 kA
40 kA
Ur 17.5 kV
Isc
Phase to phase distance (mm)
Ud 38 kV 50 Hz, 1 min
25 kA
Up 95 kV peak
145
b
b
b
b
b
b
b
145
b
b
185
b
b
240
b
b
b
b
b
b
b
145
40 kA
240
b
b
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
31.5 kA
185
b
b
185
b
b
240
b
b
b
b
b
b
b
Additional characteristics according to IEC 62271-100
Rated values
Voltage
Insulation voltage:
- power frequency withstand
- lightning impulse withstand
Frequency
Short time withstand current
Peak withstand current
Ur
kV rms
7.2-12-17.5
Ud
Up
fr
Ik/tk
Ip
kV rms
kV peak
Hz
kA
kA peak
20-28-38
60-75-95
50-60
Isc/3 s
2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
Short circuit making capacity
kA peak
Other characteristics
Operating sequence
Operating times
Mechanical endurance
Electrical endurance
Number of switching operations
at full Isc value
Capacitive current breaking capacity
Operating conditions
Average relative humidity
16
Opening
Breaking
Closing
Class
Number of switching
operations
Class
25 kA
31.5 kA
40 kA
Class
Over 24 h
Over 1 month
O-0.3 s-CO-15 s-CO
O-0.3 s-CO-3 min-CO
O-3 min-CO-3 min-CO
< 50 ms
< 60 ms
< 65 ms
M2
10000
E2
100
50
30
C1
–25°C to +40°C
< 95%
< 90%
Description of functions
MV connection
Evolis 17.5 kV
fixed, frontal version
0
Composition
DE56864
The basic circuit breaker is equipped with drilled copper connection terminals,
at the top and bottom of the breaking units.
The connectors are fitted to the terminals using the corresponding bolts.
Several variants are possible.
Fixed connectors
Mixed connectors
DE56868
Vertical connectors (V)
DE56867
DE56866
Horizontal connectors (H)
An adjustable connector enables the vertical distance to be increased to enable
rotation of 90°.
Adjustable gap connectors
Connection terminal
Extendable connectors
vertical (V)
DE56870
DE56869
DE56865
Extendable connectors
horizontal (H)
An adjustable connector enables the connection distance to be increased
from 0 to 25 mm.
3 connector sets
Mixed solution
DE56871
Example
Comment:
The insulation withstand values given in the performance table, do not take account
of the connectors.
With these connectors it is possible to use unplated or tin-plated copper conductors
or tin-plated aluminium conductors, without any specific precautions being required.
The shape and dimensions of these conductors must be determined by the panel builder
according to the dielectric withstand and temperature rise characteristics of the whole
connection system.
Typical examples are provided in the Installation Guide.
17
Evolis 17.5 kV
fixed, frontal version
Description of functions
MV connection (cont.)
0
Composition
DE56872
Panels builders can transform a fixed device into a withdrawable device by adding
the following assemblies:
b arms
b clusters
b fingers
b bushings
b field deflectors.
DE51945
Clusters and fingers
Cluster and finger
b The tulip type cluster has a shape which provides maximum contact surface whilst
optimising heat dissipation. Moreover, in the case of short-circuit, it offers good
compensation characteristics for electrodynamic forces.
b The finger is a component designed specifically for the cluster, regarding
its shape, tolerances and materials. Contact between the finger and the cluster
is guaranteed by type testing: 1000 racking in-out operations.
Arm and bushing
b The arms cylindrical shape optimizes dielectric strength and avoids the need
for any additional insulation.
b The bushing’s cylindrical shape gives it outstanding dielectric strength.
DE56874
Arms and bushings
b The previously described connectors can be mounted on bushing connection
terminals.
Comment:
Performance levels of the whole assembled unit must be tested by the panel builder.
Installation conditions for the two units presented above are described in the Installation Guide.
For the 17.5 kV withdrawable circuit breaker, phase to phase distance 185 mm, field deflectors
must be added to the bushings.
Field deflectors
For circuit breakers with a rated voltage of Ur = 17.5 kV with a phase to phase
distance of 185 mm, field deflectors are used to increase the dielectric strength
by 75 kV to 95 kV.
Arms, clusters, fingers and bushings, busbars
and field deflectors
18
Evolis 17.5 kV
fixed, frontal version
Description of functions
LV connection
0
Two connection solutions
DE56889
Directly on the LV terminal block
The circuit breaker’s LV wiring can be directly connected to the LV terminal block
of the operating mechanism through a cable protection duct.
DE51943
LV terminal block
With LV plug
b The fixed part (male) mounted on the circuit breaker and fully connected to
the operating mechanism
b The mobile part (female) compatible with the male part.
Two versions of the LV plug are available
18-pin version LV plug
An 18-pin version, enabling connection of:
b a shunt opening release MX1
b a remote control mechanism (electrical motor, shunt closing release XF,
anti-pumping relay)
b a “ready to close” contact PF
b a maximum number of auxiliary contacts: 1 NC - 1 NO - 2 changeover contacts.
(see “indication” page, “Open/closed position auxiliary contacts” chapter).
DE51944
A 42-pin version, enabling connection of:
b an opening release (shunt type MX1 or undervoltage type MN)
b a second opening release (shunt type MX2 or undervoltage type MN)
b a low energy release (Mitop)
b a fault trip indicator contact SDE
b a remote contact reset system SDE
b a remote control mechanism (electrical motor, shunt closing release XF)
b a “ready to close” contact PF
b a maximum number of auxiliary contacts: 4 NC - 5 NO - 2 changeover contacts.
42-pin version LV plug
(see “indication” page, “Open/closed position auxiliary contacts” chapter).
Note: see the table of the releases’ combinations “Order form” page.
LV wiring kit
A wiring kit with 21 or 42 wires (2 meters long) equipped with pins that can be
adapted to the LV plug can be supplied for connected in to the cubicle’s LV
compartment.
Flexible ducting
This 525 mm long duct with a hinged LV plug, enables protection of the LV wiring
that connects the circuit breaker to the cubicle’s LV compartment.
Interlocking kit
For circuit breakers intended for withdrawable applications, an interlocking kit can be
adapted. The kit enables the mechanical position status to be given (“connected/
disconnected”) of the LV plug. By adding a link between this mechanical data
(by the customer) and the open/closed position of the circuit breaker, interlocking
can be achieved between the LV plug and the open/closed position
of the circuit breaker (required by IEC standard 62271-200).
A detailed explanation of operation is given in the Installation Guide.
19
Evolis 17.5 kV
fixed, frontal version
Description of functions
Opening circuit
Composition
DE56877
The opening circuit is produced using the following components:
b a shunt opening release (MX1)
b a second shunt opening release (MX2)
b an undervoltage release (MN)
b time delayed undervoltage release (MNR: MN + time delay).
The time delay, placed outside the circuit breaker, can be disabled by an emergency
stop button to give instant circuit breaker opening.
b low energy release (Mitop).
Note: see the table of the releases’ combinations “Order form” page.
Shunt opening release (MX1 and MX2)
Circuit breaker equipped with
a shunt opening release MX
Energizing this release causes instant opening of the circuit breaker.
Permanent power supply to the MX unit locks the circuit breaker in the “open” position.
Characteristics
DE56879
Power supply
Threshold
Consumption (VA or W)
Shunt opening release (MX1 and MX2)
20
See “Order form” page
0.7 to 1.1 Un
Triggering
200 (for 200 ms)
Latched
4.5
0
Evolis 17.5 kV
fixed, frontal version
Description of functions
Opening circuit (cont.)
0
Undervoltage release (MN)
DE56879
This release unit causes the systematic opening of the circuit breaker when its
supply voltage drops below a value less than 35% of the rated voltage, even if this
drop is slow and gradual. It can open the circuit breaker between 35% and 70% of
its rated voltage. If the release unit is not supplied power, manual or electrical closing
of the circuit breaker is impossible. Closing of the circuit breaker is possible when
the supply voltage of the release unit reaches 85% of its rated voltage.
Undervoltage release (MN)
Characteristics
DE56881
Power supply
Threshold
Consumption (VA or W)
See “Order form” page
Opening
0.35 to 0.7 Un
Closing
0.85 Un
Triggering
200 (for 200 ms)
Latched
4.5
Time delay for MN
DE56882
Time delay for undervoltage release (MN)
To eliminate spurious tripping of the circuit breaker when there are brief voltage
drops, the MN action is controlled with a time delay.
This function is achieved by adding a time delay unit outside of the undervoltage
release (MN) circuit (adjustable time delay).
This unit is placed outside the circuit breaker and can be inhibited by an emergency
stop button to obtain instant circuit breaker opening.
Characteristics
Power supply
Threshold
Consumption (VA or W)
Time delay
See “Order form” page
Opening
0.35 to 0.7 Un
Closing
0.85 Un
Triggering
200 (for 200 ms)
Latched
4.5
0.5 s - 0.9 s - 1.5 s - 3 s
Low energy release (Mitop)
Low energy release (Mitop)
This release includes a low consumption unit and is specifically used
with the Sepam 100LA self-powered unit (“REFLEX MODULE”), or the VIP relay.
Characteristics
Power supply
Threshold
Direct current
0.6 A < I < 3 A
Any tripping due to the Mitop release unit is momentarily indicated by an SDE type
changeover contact.
This release also includes a coil (reset) enabling remote SDE contact reset.
Comment:
Use of the Mitop low energy release requires adjustment of the protection relay time delay
in order to ensure that the circuit breaker trips between 45-50 ms.
21
Evolis 17.5 kV
fixed, frontal version
Description of functions
Remote control
Function
DE56883
Remote control enables the remote opening and closing of the circuit breaker.
The opening order always takes priority over the closing order.
In the event of simultaneous opening and closing orders, the mechanism discharges
under no load, without moving the main contacts. The circuit breaker remains in the
“open” position.
In the event of latched opening and closing orders, the mechanism carries out antipumping function as standard, by blocking the circuit breaker in the “open” position.
Anti-pumping function: after opening on a fault or deliberate opening via the manual
or electrical mechanism, the closing order must be interrupted then reactivated to
enable reclosing of the circuit breaker.
Composition
DE56884
Circuit breaker equipped with remote control
The remote control comprises:
b an electrical motor (MCH) equipped with a “spring armed” limit switch
b a shunt closing release (XF)
b a shunt opening release (MX)
b an operation counter.
It can be added with:
b a “ready to close” contact PF
b a second block of 4 contacts (OC) for O/C position indication
for the circuit breaker
b a third block of 4 contacts (OC) for O/C position indication
for the circuit breaker.
Electrical motor (MCH)
DE56879
Electrical motor MCH
The electrical motor carries out the automatic rearming of the storage energy springs
as soon as the circuit breaker closes. This allows instant reclosing
of the device after opening. The arming lever is only used as a backup control
in the case of the absence of the auxiliary power supply.
An electrical motor (MCH) equipped with a “spring armed” limit switch.
This contact indicates the “armed” position of the mechanism (springs armed).
Characteristics
Shunt release XF/MX
Power supply
Threshold
Consumption (VA or W)
Motor overcurrent
Arming time
Operating rate
CH contact
See “Order form” page
0.85 to 1.1 Un
180
2 to 3 In for 0.1 s
6 s maximum
3 cycles maximum per minute
10 A/240 V
Shunt releases (XF and MX)
They can be permanently or briefly supplied power.
Shunt closing release (XF)
This release allows remote closing of the circuit breaker when the control
mechanism is armed.
Shunt opening release (MX)
This release allows remote opening of the circuit breaker.
It locks it in the “open” position is the order is latched.
XF/MX characteristics
Power supply
Threshold
Consumption (VA or W)
22
See “Order form” page
XF
0.85 to 1.1 Un
MX
0.7 to 1.1 Un
Triggering
200 (for 200 ms)
Latched
4.5
0
Evolis 17.5 kV
fixed, frontal version
Description of functions
Indication
0
DE56885
“Open/closed” auxiliary position contacts (OC)
DE56886
Rotary type contacts (OC)
These auxiliary contacts indicate the “open” or “closed” position of the circuit
breaker.
b Rotary type changeover contacts directly controlled by the circuit breaker
mechanism.
b Indicator contacts are proposed:
v for standard relaying applications
v for low level control applications with plc’s or electronic circuits.
This version is compatible with Sepam series 20-40-80 units.
Characteristics
Standard
V AC
DE56887
“Ready to close” PF contact
Standard delivery
Maximum quantity
Breaking capacity (A)
Cos ϕ: 0.3
AC12/DC12
V DC
Operation counter (CDM)
Low level
V AC
V DC
240/380
480
690
24/48
125
250
24/48
240
380
24/48
125
250
4
12
Min. load: 100 mA/24 V
10/6*
10/6*
6
10/6*
10/6*
3
Min. load: 2 mA/15 V DC
6
6
3
6
6
3
* Standard contacts: 10 A; optional contacts: 6 A (temperature derating)
“Ready to close” PF contact
The circuit breaker is “ready to close” when shown by a mechanical indicator
and a PF changeover contact.
This information simultaneously indicates that:
b the circuit breaker is open
b the storage energy springs are armed
b there is no permanent closing order
b there is no permanent opening order caused by:
v a safety opening order (2nd MX or MN)
v keylocking of the device in the open position.
Characteristics
Standard delivery
Maximum quantity
Breaking capacity (A)
Cos ϕ: 0.3
AC12/DC12
Standard
V AC
V DC
Low level
V AC
V DC
240/380
480
690
24/48
125
250
24/48
240
380
24/48
125
250
0
1
Min. load: 100 mA/24 V
5
5
3
3
0.3
0.15
Min. load: 2 mA/15 V DC
3
3
3
3
0,3
0,15
Operation counter (CDM)
The operation counter is visible on the front panel.
It totalizes the number of switching cycles (CO) that the device has carried out.
23
Description of functions
Locking/interlocking
DE56894
Evolis 17.5 kV
fixed, frontal version
Locking the circuit breaker in the open
position
Opening button
Closing button
Control mechanism status
(charged or discharged)
Push button locking
Circuit breaker position indicator
Operation counter
Push button locking
DE56895
DE56892
Push button locking
DE56896
DE56891
This transparent screen blocks access to the opening and closing push-buttons
on the circuit breaker.
The device enables the opening or closing push button to be locked independently.
It is often associated with an electrical motor (MCH).
Locking is achieved either:
b by 2 screws
b by 3 padlocks, not supplied
b by a lead seal.
Padlocking
Lead sealing
DE56893
Padlocking of the circuit breaker in the “open” position
Locking of the circuit breaker in the “open” position
RONIS
Keylocking of the circuit breaker in the “open” position
24
The circuit breaker is locked in the “open” position by blocking the opening push
button in the engaged position:
b by a padlock 1 to 3 padlocks, not supplied
b by a keylocks 1 or 2 different keylocks, not supplied
The keylocks are of captive key type, with the key free after locking, either Profalux
or Ronis (right turn), and are proposed according to the options either with:
b 1 single keylock
b 1 single keylock mounted on the circuit breaker + 1 identical delivered separately
for interlocking with another device
b 2 different keylocks for double locking.
Profalux and Ronis keylocks are inter-compatible.
0
Description of functions
Wiring diagram
Evolis 17.5 kV
fixed, frontal version
0
DE56125EN
Wiring diagram (principle)
Circuit breaker open
Operating mechanism loaded
Charged
Fault
Ready to close
MCH
OF1
OF2
OF3
OF4
OF11
OF12
OF13
OF14
OF21
OF22
OF23
OF24
XF
MX1
MX2
or
MN
Mitop
Reset
SDE
PF
Auxiliary contacts
Remote control
MCH: electrical motor
XF: shunt closing release
MX1: shunt opening release
MX2: shunt opening release
or MN: undervoltage release
Mitop: low energy release
SDE: electrical fault signal contact
Reset: remote SDE contact reset
PF: “ready to close” contact
25
Dimensions
Evolis 17.5 kV
fixed, frontal version
0
Device:
Isc
25 kA
Ir
630 A
12 kV
25 kA
1250 A
630 A
1250 A
Weight
51 kg
145 90
145
DE56111
Ur
7.2 kV
DE56110
Phase to phase distance 145 mm
535
470
Isc
25 kA
31.5 kA
12 kV
25 kA
31.5 kA
17.5 kV
25 kA
31.5 kA
Ir
630 A
Weight
55 kg
1250 A
630 A
1250 A
630 A
1250 A
630 A
1250 A
630 A
1250 A
630 A
1250 A
185
185
90
DE56111
Ur
7.2 kV
DE56112
Phase to phase distance 185 mm
535
550
12 kV
17.5 kV
Isc
25 kA
Ir
2500 A
31.5 kA
40 kA
2500 A
630 A
1250 A
2500 A
2500 A
2500 A
630 A
1250 A
2500 A
2500 A
2500 A
630 A
1250 A
2500 A
25 kA
31.5 kA
40 kA
25 kA
31.5 kA
40 kA
Weight
79 kg
Important
Detailed installation instructions are given in
the “Evolis Installation Guide”. Please consult us.
26
240
240
90
DE56111
Ur
7.2 kV
DE56113
Phase to phase distance 240 mm
535
660
Evolis 17.5 kV
fixed, frontal version
Offer structure
0
The basic fixed, frontal circuit breaker includes:
b a manual operating mechanism (spring type)
b 1 shunt opening release MX
b 1 block of 4 ON/OFF indication contacts.
The circuit breaker can receive options.
DE56940
Basic fixed, frontal circuit breaker
Phase distance (mm)
7.2 kV
25 kA
31.5 kA
40 kA
12 kV
25 kA
31.5 kA
40 kA
17.5 kV
25 kA
31.5 kA
40 kA
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
145
b
b
185
b
b
240
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
27
Offer structure (cont.)
Evolis 17.5 kV
fixed, frontal version
Circuit breaker options
Fig. 4
DE56887
Fig. 3
Fig. 1
1st opening release
Possibility of replacing MX by
undervoltage release MN (fig. 3)
Possibility of replacing MX by
low energy release Mitop (fig. 2)
2nd opening release
Shunt opening release MX (circuit breaker opening) (fig. 3)
Undervoltage release MN (circuit breaker opening) (fig. 3)
Time delay unit for MN (setting 0.5, 0.9, 1.5, 3 s) (fig. 4)
Low energy release Mitop (fig. 2)
1 AC fault signalling SDE and reset 200…250 Vac are included
Remote control including:
Electrical motor MCH and shunt closing release XF
and operation counter CDM (fig. 1, 3 & 5)
DE56881
DE56879
DE56934
DE56933
Remote control (see possible choices in combination table below)
Fig. 2
Fig. 5
Releases combinations table
2 1
MX
1
1
1
MN
1
Mitop
1
1
2
1
1
1
1
1
1
Fig. 1
Operation counter CDM (fig. 1)
Additional auxiliary contacts OF (4 AC) (fig. 2)
Ready to close contact PF (1 AC) (fig. 3)
DE56886
DE56885
DE56887
Indication
Fig. 3
Fig. 2
Standard plug 18 pins (fig. 1)
All options plug 42 pins (fig. 2)
Low voltage terminal blocks (fig. 3)
42 pins or terminal blocks are mandatory if more than one opening coil is needed
DE56889
DE51944
DE51943
LV wiring connection
Fig. 3
Fig. 1
Fig. 2
Fig. 1
28
DE56891
DE56936
DE56935
Locking/interlocking
Fig. 2
Fig. 3
Locking of the circuit breaker in the open position by padlock
(padlock supplied by customer) (fig. 1)
Locking of the circuit breaker in the
1 lock
open position by key locks (fig. 2)
2 locks
Disabling of O/C circuit breaker buttons
(padlock supplied by customer) (fig. 3)
0
Order form
Evolis 17.5 kV
fixed, frontal version
Only one of the boxes (ticked X or filled
by
the needed value) have to be considered between each
horizontal line.
Orange box X corresponds to none priced functions.
0
Basic fixed, frontal circuit breaker
Quantity
Rated voltage Ur
(kV)
Rated short-circuit breaking current Isc
(kA)
Rated normal current Ir
Phase distance (mm)
(A)
145
Colour for push buttons and indicators
185
240
IEC standard
ANSI standard
Circuit breaker options
1st opening release (see possible choices in combination table below)
Shunt opening release - MX
24 Vac
24…30 Vdc
48 Vac
48…60 Vdc
Undervoltage release - MN
24 Vac
24…30 Vdc
48 Vac
48…60 Vdc
Time delay unit for MN
48…60 Vdc/ac
100…130 Vdc/ac
Low energy release Mitop
1 AC fault signalling SDE and reset 200...250 Vac are included
100…130 Vdc/ac
200…250 Vdc/ac
100…130 Vdc/ac
200…250 Vdc/ac
200…250 Vdc/ca
2nd opening release (a low voltage plug and socket 42 pins is mandatory)
Shunt opening release - MX
24 Vac
24…30 Vdc
48 Vac
48…60 Vdc
Undervoltage release - MN
24 Vac
24…30 Vdc
48 Vac
48…60 Vdc
Time delay unit for MN
48…60 Vdc/ac
100…130 Vdc/ac
Low energy release Mitop
1 AC fault signalling SDE and reset 200...250 Vac are included
100…130 Vdc/ac
200…250 Vdc/ac
100…130 Vdc/ac
200…250 Vdc/ac
200…250 Vdc/ca
Remote control (operation counter already included)
Electrical motor - MCH
24…30 Vdc
48…60 Vdc/ac
Shunt closing release - XF
24 Vac
48 Vac
100…125 Vdc
100…130 Vac
200…250 Vdc
200…240 Vac
24…30 Vdc
48…60 Vdc
100…130 Vdc/ac
200…250 Vdc/ac
Operation counter CDM (already included if remote control supplied)
Additional auxiliary contacts OF (4 AC)
1
Ready to close contact PF (1 AC)
LV plug
18 pins LV plug
42 pins LV plug
Locking of the circuit breaker in the open position
By padlock
or by locks and keys
Profalux
If locks
1 lock
2 identical locks
Disabling of O/C circuit breaker push buttons
Releases combinations table
Shunt opening MX
1
Undervoltage MN
Mitop
2
1
1
1
1
1
1
2
1
1
1
2
LV terminal blocks
Ronis
2 different locks
1
1
1
29
Evolis 17.5 kV
fixed, frontal version
Offer structure
Separated components
0
The following components can be ordered
separately and can be adapted or replaced
by the customer.
Remote control
Ref.
DE56879
MX1, MX2, XF shunt opening/closing release
24…30 Vdc
48…60 Vdc
100…130 Vac - 50/60 Hz
200…250 Vac - 50/60 Hz
24 V 50/60 Hz
48 V 50/60 Hz
59141
59142
59143
59144
24…30 Vdc
48…60 Vdc
100…130 Vac - 50/60 Hz
200…250 Vac - 50/60 Hz
24 V 50/60 Hz
48 V 50/60 Hz
33668
33669
33670
33671
DE56879
MN undervoltage release
DE56933
MCH electrical motor
24…30 Vdc
48…60 Vdc
100…125 Vdc
200…250 Vdc
48…60 Vac - 50/60 Hz
100…130 Vac - 50/60 Hz
200…240 Vac - 50/60 Hz
47888
47889
47890
47891
47889
47893
47894
4 AC
47887
DE56885
Additional auxiliary contacts
MV and LV connection accessories
Ref.
Arm
DE56956
DE56955
DE56954
MV connection accessories
Cluster
Finger
3 clusters + 3 fingers
3 clusters + 3 fingers
3 arms
3 arms
630-1250 A
630-2500 A
630-1250 A
630-2500 A
59369
59371
59396
59397
Bushings
DE56995
1 full bushing 630-1250 A
1 full bushing 630-2500 A
(you need at least 6 bushings per cradle)
59382
59383
DE56939
Field deflectors for bushings
6 deflectors used to increase dielectric
withstand from 75 to 95 kV
59283
Standard (18 pins)
All options (42 pins)
59114
59115
1 terminal block
47074
21 marked LV wires fitted in socket type pins
59117
DE56957
LV plug
DE56958
LV terminal blocks
LV wiring
30
Offer structure
Separated components (cont.)
Evolis 17.5 kV
fixed, frontal version
Other circuit breaker accessories
0
Ref.
DE56953
DE56951
DE56952
Upstream and downstream fixed connections, Ir (to be mounted on basic circuit breaker or bushings)
Fig. 2
Fig. 1
Fig. 3
3 fixed distance H or V (fig. 1)
3 variable distance H (fig. 3)
3 variable distance V (fig. 2)
630-1250 A
630-1250 A
630-1250 A
59400
59401
59402
630-2500 A
630-2500 A
630-2500 A
59403
59404
59405
630-2500 A
630-2500 A
630-2500 A
59409
59410
59411
DE56953
DE56951
DE56952
Upstream fixed connections, Ir (to be mounted on basic circuit breaker or bushings)
or downstream fixed connections, Ir (to be mounted on bushings only)
Fig. 2
Fig. 1
Fig. 3
3 fixed distance H or V (fig. 1)
3 variable distance H (fig. 3)
3 variable distance V (fig. 2)
Fig. 1
DE56953
DE56951
DE56952
Downstream fixed connections, Ir (to be mounted on basic circuit breaker only)
Fig. 2
Fig. 3
3 fixed distance H or V (fig. 1)
3 variable distance H (fig. 3)
3 variable distance V (fig. 2)
ON
push
d
charge
OK
d
charge
OK
dis
ch
arg
Circuit breaker specific labels green, red, etc.
59100
Adaptation kit needed for circuit breaker opening (for retrofit)
59093
push OFF
DE56898
Labels kit for push button and indicator (O/C)
O OFF
ed
DE56897
Circuit breaker opening external device
Various
Ref.
DE56996
Circuit breaker support frame
Drawings and casters
59050
User manual
59069
DE56997
Technical documentation
de
an
mm
on ca
cti ôle
m
pa
ote ntr
Se +
Pr co
e 00
et
10
mmm ion
ce
Ga pa lat on rvi
Se tal ati se
Ins ilis en
Ut se
Mi
I off
O
off
SF6
ext
b>>51n
b>51n
I>51
Trip
reset
on
ir
31
Evolis 17.5 kV
fixed, frontal version
Services
The following components can only be adapted or replaced
on site by staff trained by Schneider Electric:
b remote control mechanism (comprising: electrical motor, shunt closing release,
operation counter)
b operation counter
b low energy release (Mitop)
b circuit breaker front cover.
32
0
Evolis
Evolis 17.5 kV
withdrawable, frontal version
0
Panorama
Evolis 17.5 kV fixed, frontal version
11
15
Main characteristics
34
Description of functions
Racking in
MV connection
LV connection
Opening circuit
Remote control
Indication
Locking/interlocking
Wiring diagram
Safety functions
35
35
36
37
38
40
41
42
43
44
Dimensions
45
Offer structure
46
Order form
48
Separated components
49
Services
51
Evolis 24 kV fixed, frontal version
Evolis 24 kV withdrawable, frontal version
Evolis and EVOset 24 kV fixed, lateral version
Evolis Pilot monitoring device
53
67
87
109
33
Evolis 17.5 kV
withdrawable,
frontal version
Main characteristics
0
PE55101
Electrical characteristics according to IEC 62271-100
Ur 7.2 kV
Isc
Phase to phase distance (mm)
Ud 20 kV 50 Hz, 1 min
25 kA
Up 60 kV peak
Ir
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
Ir
31.5 kA
40 kA
Ur 12 kV
Isc
Phase to phase distance (mm)
Ud 28 kV 50 Hz, 1 min
25 kA
Up 75 kV peak
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
Ir
31.5 kA
40 kA
Ur 17.5 kV
Isc
Phase to phase distance (mm)
Ud 38 kV 50 Hz, 1 min
25 kA
Up 95 kV peak
145
b
b
b
b
b
b
b
145
b
b
185
b
b
240
b
b
b
b
b
b
b
145
40 kA
240
b
b
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
31.5 kA
185
b
b
185
b
b
240
b
b
b
b
b
b
b
Additional characteristics according to IEC 62271-100
Rated values
Voltage
Insulation voltage:
- power frequency withstand
- lightning impulse withstand
Frequency
Short time withstand current
Peak withstand current
Ur
kV rms
7.2-12-17.5
Ud
Up
fr
Ik/tk
Ip
kV rms
kV peak
Hz
kA
kA peak
20-28-38
60-75-95
50-60
Isc/3 s
2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
Short circuit making capacity
kA peak
Other characteristics
Operating sequence
Operating times
Mechanical endurance
Electrical endurance
Number of switching operations
at full Isc value
Capacitive current breaking capacity
Operating conditions
Average relative humidity
34
Opening
Breaking
Closing
Class
Number of switching
operations
Class
25 kA
31.5 kA
40 kA
Class
Over 24 h
Over 1 month
O-0.3 s-CO-15 s-CO
O-0.3 s-CO-3 min-CO
O-3 min-CO-3 min-CO
< 50 ms
< 60 ms
< 65 ms
M2
10000
E2
100
50
30
C1
–25°C to +40°C
< 95%
< 90%
Description of functions
Racking in
Evolis 17.5 kV
withdrawable,
frontal version
0
Composition
DE51956
The “racking in” function is carried out by:
b the racking truck supporting the circuit breaker (mobile part)
b the cradle with bushings (fixed part)
b LV plug.
Operation
The circuit breaker can be placed in 3 stable positions:
b service position: circuit breaker racked in and locked in position;
LV plugs connected
b test position: circuit breaker racked out and locked in position;
LV plug connected
b disconnected position: the circuit breaker can be unlocked and extracted
from the cubicle.
Propulsion system
Service position
DE56858
DE56857
DE56856
DE56851
3 stable states for operating
Test position
Disconnected position
Note: the arrows show the “locked positions” for the circuit breaker and the LV plug.
DE56852
Functions
DE56855
DE51946
Shutters
DE51947
Circuit breaker Racked in/out
position
contacts
contact locked
Earthing sliding device
b A drive system combined with a threaded shaft gives easier racking in and out.
The racking in mechanism can be operated with the door closed.
An interlock stops the user from inserting the lever as long as the racking truck
has not been put in the “racked in/out” position.
b An interlock between the circuit breaker status and the truck gives secure operation:
racking in or out is only possible if the circuit breaker is open.
b An interlock also exists between the LV connector and the truck. It is only possible
to rack in if the LV connector is connected.
The cradle floor has all the fixing holes needed to correctly position the earthing
switch control mechanism and power circuit. This makes earthing switch operation
reliable and gives interlocking between the circuit breaker and the earthing switch.
b Earthing is automatic when the truck is fully racked in.
b Protective shutters stop fingers from touching the racking clusters when the device
is extracted (protection index: IP2X).
b For maintenance operations, it is possible to:
v padlock the shutters in the closed position
v unlock the shutter mechanism to access the racking clusters.
b A foolproof device enables correct matching of the cradle and circuit breaker rating.
This system is mounted on the cradle base. Part of the system must be assembled
by the panel builder on the cubicle floor.
Accessories
C
C
b One set of auxiliary contacts:
v 4 circuit breaker racked in/out position contacts
v 1 contact showing that the circuit breaker is locked in place on the cradle.
b Cradle earthing is provided by a sliding copper contact.
b A key locking system (Ronis or Profalux) for the circuit breaker in the racked out
position enables increased safety downstream of it during work.
This system is associated with an earthing switch.
b Locking of the circuit breaker compartment door.
This device enables the circuit breaker, full version, to only be operated
when the door is closed.
Door locking mechanism
35
Evolis 17.5 kV
withdrawable,
frontal version
Description of functions
MV connection
Composition
DE51942
The power circuit comprises:
b mobile contacts with disconnectable clusters and arms mounted on the circuit
breaker
b fingers attached to the cradle and insulated by bushings and metal shutters.
This assembly provides perfect control of the dielectric strength, mechanic,
the short time withstand current and the temperature rise.
All of these characteristics have been validated in tests.
Connection
Connection is easily done from outside the cradle:
b on vertical copper terminals integrated in the bushing
b by a connector set, also used on the base circuit breaker.
Note:
The dielectric strength values given in the performance table, do not take these connectors
into account.
The panel builder must check the whole cubicle connection configuration.
DE56847
Power circuit
DE56849
3 connector sets
Field deflectors
36
For circuit breakers with a rated voltage of Ur = 17.5 kV with a phase to phase
distance of 185 mm, field deflectors are used to increase the dielectric strength
by 75 kV to 95 kV.
0
Evolis 17.5 kV
withdrawable,
frontal version
Description of functions
LV connection
Main functions
DE51943
With the base circuit breaker, the LV wiring uses a LV plug which comprises:
b the fixed part (male) mounted on the circuit breaker and fully connected to
the control mechanism
b the mobile part (female) compatible with the male part.
18-pin version LV plug
Two versions of the LV plug are available
DE51944
An 18-pin version, enabling connection of:
b a shunt opening release MX1
b a remote control mechanism (electrical motor, shunt closing release XF)
b a “ready to close” contact PF
b a maximum number of auxiliary contacts: 1 NC - 1 NO - 2 changeover contacts.
(see “indication” page, “Open/closed position auxiliary contacts” chapter).
42-pin version LV plug
An 42-pin version, enabling connection of:
b a shunt opening release MX1
b a second opening release (shunt type MX2 or undervoltage type MN)
b a low energy release (Mitop)
b a fault trip indicator contact SDE
b a remote contact reset system SDE
b a remote control mechanism (electrical motor, shunt closing release XF)
b a “ready to close” contact PF
b a maximum number of auxiliary contacts: 4 NC - 5 NO - 2 changeover contacts.
(see “indication” page, “Open/closed position auxiliary contacts” chapter).
Note: see the table of the releases’ combinations “Order form” page.
Interlocking function:
In conformity with IEC standard 62271-200, an interlocking function prohibits:
b racking in when the LV plug is not connected
b disconnection of the LV plug if the circuit breaker is in the racked-in position.
LV wiring kit
A wiring kit with 21 or 42 wires (2 meters long) equipped with pins that can be
adapted to the LV plug can be supplied for connected in to the cubicle’s LV
compartment.
Flexible ducting
This 525 mm long duct with a hinged LV plug, enables protection of the LV wiring
that connects the circuit breaker to the cubicle’s LV compartment.
37
Evolis 17.5 kV
withdrawable,
frontal version
Description of functions
Opening circuit
Composition
DE56877
In its basic version, the circuit breaker includes a shunt opening release (MX1)
The opening circuit can also be produced using the following components:
b a second shunt opening release MX2
b undervoltage release (MN)
b time delayed undervoltage release (MNR: MN + time delay).
The time delay, placed outside the circuit breaker, can be disabled by an emergency
stop button to give instant circuit breaker opening.
b low energy release (Mitop).
Note: see the table of the releases’ combinations “Order form” page.
Shunt opening release (MX1 and MX2)
Circuit breaker equipped with
a shunt opening release MX
Energizing this release causes instant opening of the circuit breaker.
Permanent power supply to the MX unit locks the circuit breaker in the “open” position.
Characteristics
DE56879
Power supply
Threshold
Consumption (VA or W)
Shunt opening release (MX1 and MX2)
38
See “Order form” page
0.7 to 1.1 Un
Triggering
200 (for 200 ms)
Latched
4.5
0
Evolis 17.5 kV
withdrawable,
frontal version
Description of functions
Opening circuit (cont.)
0
Undervoltage release (MN)
DE56879
This release unit causes the systematic opening of the circuit breaker when its
supply voltage drops below a value less than 35% of the rated voltage, even if this
drop is slow and gradual. It can open the circuit breaker between 35% and 70% of
its rated voltage. If the release unit is not supplied power, manual or electrical closing
of the circuit breaker is impossible. Closing of the circuit breaker is possible when
the supply voltage of the release unit reaches 85% of its rated voltage.
Undervoltage release (MN)
Characteristics
DE56881
Power supply
Threshold
Consumption (VA or W)
See “Order form” page
Opening
0.35 to 0.7 Un
Closing
0.85 Un
Triggering
200 (for 200 ms)
Latched
4.5
Time delay for MN
DE56882
Time delay for undervoltage release (MN)
To eliminate spurious tripping of the circuit breaker when there are brief voltage
drops, the MN action is controlled with a time delay.
This function is achieved by adding a time delay unit outside of the undervoltage
release (MN) circuit (adjustable time delay).
This unit is placed outside the circuit breaker and can be inhibited by an emergency
stop button to obtain instant circuit breaker opening.
Characteristics
Power supply
Threshold
Consumption (VA or W)
Time delay
See “Order form” page
Opening
0.35 to 0.7 Un
Closing
0.85 Un
Triggering
200 (for 200 ms)
Latched
4.5
0.5 s - 0.9 s - 1.5 s - 3 s
Low energy release (Mitop)
Low energy release (Mitop)
This release includes a low consumption unit and is specifically used
with the Sepam 100LA self-powered unit (“REFLEX MODULE”), or the VIP relay.
Characteristics
Power supply
Threshold
Direct current
0.6 A < I < 3 A
Any tripping due to the Mitop release unit is momentarily indicated by an SDE type
changeover contact.
This release also includes a coil (reset) enabling remote SDE contact reset.
Comment:
Use of the Mitop low energy release requires adjustment of the protection relay time delay
in order to ensure that the circuit breaker trips between 45-50 ms.
39
Evolis 17.5 kV
withdrawable,
frontal version
Description of functions
Remote control
Function
DE56883
Remote control enables the remote opening and closing of the circuit breaker.
The opening order always takes priority over the closing order.
In the event of simultaneous opening and closing orders, the mechanism discharges
under no load, without moving the main contacts. The circuit breaker remains in the
“open” position.
In the event of latched opening and closing orders, the mechanism carries out antipumping function as standard, by blocking the circuit breaker in the “open” position.
Anti-pumping function: after opening on a fault or deliberate opening via the manual
or electrical mechanism, the closing order must be interrupted then reactivated to
enable reclosing of the circuit breaker.
Composition
DE56884
Circuit breaker equipped with remote control
The remote control comprises:
b an electrical motor (MCH) equipped with a “spring armed” CH limit switch
b a shunt closing release (XF)
b a shunt opening release (MX)
b an operation counter.
It can be added with:
b a “ready to close” contact PF
b a second block of 4 contacts (OC) for O/C position indication
for the circuit breaker
b a third block of 4 contacts (OC) for O/C position indication
for the circuit breaker.
Electrical motor (MCH)
DE56879
Electrical motor MCH
The electrical motor carries out the automatic rearming of the storage energy springs
as soon as the circuit breaker closes. This allows instant reclosing
of the device after opening. The arming lever is only used as a backup control
in the case of the absence of the auxiliary power supply.
An electrical motor (MCH) equipped with a “spring armed” CH limit switch.
This contact indicates the “armed” position of the mechanism (springs armed).
Characteristics
Shunt release XF/MX
Power supply
Threshold
Consumption (VA or W)
Motor overcurrent
Arming time
Operating rate
CH contact
See “Order form” page
0.85 to 1.1 Un
180
2 to 3 In for 0.1 s
6 s maximum
3 cycles maximum per minute
10 A/240 V
Shunt releases (XF and MX)
They can be permanently or briefly supplied power.
Shunt closing release (XF)
This release allows remote closing of the circuit breaker when the control
mechanism is armed.
Shunt opening release (MX)
This release allows remote opening of the circuit breaker.
It locks it in the “open” position if the order is latched.
XF/MX characteristics
Power supply
Threshold
Consumption (VA or W)
40
See “Order form” page
XF
0.85 to 1.1 Un
MX
0.7 to 1.1 Un
Triggering
200 (for 200 ms)
Latched
4.5
0
Evolis 17.5 kV
withdrawable,
frontal version
Description of functions
Indication
0
DE56885
“Open/closed” auxiliary position contacts (OC)
DE56886
Rotary type contacts (OC)
These auxiliary contacts indicate the “open” or “closed” position of the circuit
breaker.
b Rotary type changeover contacts directly controlled by the circuit breaker
mechanism.
b Indicator contacts are proposed:
v for standard relaying applications
v for low level control applications with plc’s or electronic circuits.
This version is compatible with Sepam series 20-40-80 units.
Characteristics
Standard
V AC
DE56887
“Ready to close” PF contact
Standard delivery
Maximum quantity
Breaking capacity (A)
Cos ϕ: 0.3
AC12/DC12
V DC
Operation counter (CDM)
Low level
V AC
V DC
240/380
480
690
24/48
125
250
24/48
240
380
24/48
125
250
4
11
Min. load: 100 mA/24 V
10/6*
10/6*
6
10/6*
10/6*
3
Min. load: 2 mA/15 V DC
6
6
3
6
6
3
* Standard contacts: 10 A; optional contacts: 6 A (temperature derating)
“Ready to close” PF contact
The circuit breaker is “ready to close” when shown by a mechanical indicator
and a PF contact.
This information simultaneously indicates that:
b the circuit breaker is open
b the storage energy springs are armed
b there is no permanent closing order
b there is no permanent opening order caused by:
v a safety opening order (2nd MX or MN)
v keylocking of the device in the open position.
Characteristics
Standard delivery
Maximum quantity
Breaking capacity (A)
Cos ϕ: 0.3
AC12/DC12
Standard
V AC
V DC
Low level
V AC
V DC
240/380
480
690
24/48
125
250
24/48
240
380
24/48
125
250
0
1
Min. load: 100 mA/24 V
5
5
3
3
0.3
0.15
Min. load: 2 mA/15 V DC
3
3
3
3
0,3
0,15
Operation counter (CDM)
The operation counter is visible on the front panel.
It totalizes the number of switching cycles (CO) that the device has carried out.
41
Description of functions
Locking/interlocking
DE56894
Evolis 17.5 kV
withdrawable,
frontal version
Locking the circuit breaker in the open
position
Opening button
Closing button
Control mechanism status
(charged or discharged)
Push button locking
Circuit breaker position indicator
Operation counter
Push button locking
DE56895
DE56892
Push button locking
DE56896
DE56891
This transparent screen blocks access to the opening and closing push-buttons
on the circuit breaker.
The device enables the opening or closing push button to be locked independently.
It is often associated with an electrical motor (MCH).
Locking is achieved either:
b by 2 screws
b by 3 padlocks, not supplied
b by a lead seal.
Padlocking
Lead sealing
DE56893
Padlocking of the circuit breaker in the “open” position
Locking of the circuit breaker in the “open” position
RONIS
DE51947
Keylocking of the circuit breaker in the “open” position
The circuit breaker is locked in the “open” position by blocking the opening push
button in the engaged position:
b by a padlock 1 to 3 padlocks, not supplied
b by a keylocks 1 or 2 different keylocks, not supplied
The keylocks are of captive key type, with the key free after locking, either Profalux
or Ronis (right turn), and are proposed according to the options either with:
b 1 single keylock
b 1 single keylock mounted on the circuit breaker + 1 identical delivered separately
for interlocking with another device
b 2 different keylocks for double locking.
Profalux and Ronis keylocks are inter-compatible.
Cubicle door interlocking mechanism
This device enables the circuit breaker to only be operated when the door
is closed, for the withdrawable version with a cradle.
C
C
Cubicle door interlocking mechanism
42
0
Description of functions
Wiring diagram
Evolis 17.5 kV
withdrawable,
frontal version
0
Circuit breaker open
Operating mechanism loaded
Fault
Ready
to
close
B2
B1
OF1
OF2
OF3
OF4
OF11
OF12
OF13
OF14
OF21
OF22
OF23
MCH
XF
For heating element
DE56135EN
Wiring diagram (principle)
MX1
MX2
or
MN
Mitop
Reset
SDE
PF
Remote control
Auxiliary contacts
MCH: electrical motor
XF: shunt closing release
MX1: shunt opening release
MX2: shunt opening release
or MN: undervoltage release
Mitop: low energy release
SDE: electrical fault signal contact
Reset: remote SDE contact reset
PF: “ready to close” contact
43
Description of functions
Safety functions
Evolis 17.5 kV
withdrawable,
frontal version
0
This table describes the safety functions available on the withdrawable version
of the Evolis 17.5 kV circuit breaker.
How to use the table
Each of the boxes describes the functional status of each circuit breaker position
and the associated parts:
Possible status
Possible status, operation impossible
Impossible status
Parts
Circuit breaker positions
Insertion
Racking-in
Extraction
Racking-out
Removed
1 - Cradle
Disconnected Test position
Service
Fool-proof
protection (1)
Anti-drop (2)
No opening shutters
Shutters padlocking possible
2 - LV plug
Disconnected
No racking-in
Connected
3 - Circuit breaker
Closed
No unplugging
No racking-in
No racking-out
Open
No closing
Open position circuit breaker locking available
4 - Switchboard door
Open
No racking-in
Closed
5 - Earthing switch
No door opening (3)
Open
Closed
No earthing switch closing
No racking-in
(1) This protection mechanism ensures that the performance levels of the circuit breaker correspond with those of the cradle.
(2) Device that prevents the circuit breaker from dropping when extracted from the cradle.
The device can be either unlocked manually or when the extraction rig is put in position.
(3) Interlocking device to be fitted to the cubicle door. If there is no interlocking, the circuit breaker device should be inhibited.
44
Dimensions
Evolis 17.5 kV
withdrawable,
frontal version
0
Device
Isc
25 kA
Ir
630 A
12 kV
25 kA
1250 A
630 A
1250 A
Weight
165 kg
DE56121
Ur
7.2 kV
DE56120
Phase to phase distance 145 mm
12 kV
25 kA
31.5 kA
17.5 kV
25 kA
31.5 kA
Weight
174 kg
DE56121
31.5 kA
Ir
630 A
Weight
272 kg
DE56124
Isc
25 kA
DE56122
Ur
7.2 kV
DE56123
Phase to phase distance 185 mm
1250 A
630 A
1250 A
630 A
1250 A
630 A
1250 A
630 A
1250 A
630 A
1250 A
Phase to phase distance 240 mm
Ur
7.2 kV
Isc
25 kA
Ir
2500 A
31.5 kA
40 kA
2500 A
630 A
1250 A
2500 A
2500 A
2500 A
630 A
1250 A
2500 A
2500 A
2500 A
630 A
1250 A
2500 A
12 kV
25 kA
31.5 kA
40 kA
17.5 kV
25 kA
31.5 kA
40 kA
Important
Detailed installation instructions are given in
the “Evolis Installation Guide”. Please consult us.
45
Evolis 17.5 kV
withdrawable,
frontal version
Offer structure
0
The basic withdrawable, frontal circuit breaker includes:
b 6 arms with clusters
b racking truck with operating crank and screw-shaft system
b a manual operating mechanism (spring type)
b LV plug 18 pins
b 1 shunt opening release MX
b 1 block of 4 ON/OFF indication contacts.
The circuit breaker can receive options.
The cradle includes:
b 6 bushings with fingers
b shutters
b shutters mechanism.
The cradle can receive accessories.
Basic withdrawable, frontal circuit breaker
DE56931
Phase distance (mm)
7.2 kV
25 kA
31.5 kA
40 kA
12 kV
25 kA
31.5 kA
40 kA
17.5 kV
25 kA
31.5 kA
40 kA
46
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
630 A
1250 A
2500 A
145
b
b
185
b
b
240
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
Offer structure (cont.)
Evolis 17.5 kV
withdrawable,
frontal version
0
Circuit breaker options
DE56881
DE56879
DE56934
DE56933
Remote control (see possible choices in combination table below)
Fig. 1
Fig. 4
DE56887
Fig. 3
Fig. 2
Fig. 5
2nd opening release
Shunt opening release MX (fig. 3)
Undervoltage release MN (fig. 3)
Time delay unit for MN (setting 0.5, 0.9, 1.5, 3 s) (fig. 4)
Low energy release Mitop (fig. 2)
1 AC fault signalling SDE and reset 200…250 Vac are included
Remote control including:
Electrical motor MCH and shunt closing release XF
and operation counter CDM (fig. 1, 3 & 5)
Releases combinations table
MX
1 2 1 1 2
1
MN
1 1
Mitop
1
1
1
Fig. 1
Operation counter CDM (fig. 1)
Additional auxiliary contacts OF (4 AC) (fig. 2)
Ready to close contact PF (1 AC) (fig. 3)
DE56886
DE56885
DE56887
Indication
Fig. 3
Fig. 2
LV wiring connection
DE51944
42-pin LV plug (instead of 18 pins)
Rack-in/rack-out operation
DE56915
Operating crank
Fig. 1
DE56891
DE56936
DE56935
Locking/interlocking
Fig. 2
Fig. 3
Locking of the circuit breaker in the open position by padlock
(padlock supplied by customer) (fig. 1)
Locking of the circuit breaker in the
1 lock
open position by key locks (fig. 2)
2 locks
Disabling of O/C circuit breaker buttons
(padlock supplied by customer) (fig. 3)
Cradle
DE56937
Cradle with 145 mm phase distance
Cradle with 185 mm phase distance
Cradle with 240 mm phase distance
Cradle accessories
DE51950
DE56938
Racked in/out position contacts (4 AC) (fig. 1)
C.B. “ready to be operated” PAF (1 AC) (fig.2)
indicates that the C.B. is locked in place in the cradle
Fig. 2
DE56939
Fig. 1
6 field deflectors for bushings
mandatory if Ur = 17.5 kV - 95 kVpeak with phase distance 185 mm
47
Order form
Evolis 17.5 kV
withdrawable,
frontal version
Only one of the boxes (ticked X or filled
by
the needed value) have to be considered between each
horizontal line.
Orange box X corresponds to none priced functions.
0
Basic withdrawable, frontal circuit breaker
Quantity
Rated voltage Ur
(kV)
Rated short-circuit breaking current Isc
(kA)
Rated normal current Ir
Phase distance (mm)
(A)
145
Colour for push buttons and indicators
185
240
IEC standard
ANSI standard
Circuit breaker options
1st opening release (see possible choices in combination table below)
Shunt opening release - MX
24 Vac
48 Vac
24…30 Vdc
48…60 Vdc
100…130 Vdc/ac
200…250 Vdc/ac
2nd opening release (a 42-pin LV plug is mandatory)
Shunt opening release - MX
24 Vac
24…30 Vdc
48 Vac
48…60 Vdc
Undervoltage release - MN
24 Vac
24…30 Vdc
48 Vac
48…60 Vdc
Time delay unit for MN
48…60 Vdc/ac
100…130 Vdc/ac
Low energy release Mitop
1 AC fault signalling SDE and reset 200...250 Vac are included
100…130 Vdc/ac
200…250 Vdc/ac
100…130 Vdc/ac
200…250 Vdc/ac
200…250 Vdc/ca
Remote control (operation counter already included)
Electrical motor - MCH
24…30 Vdc
48…60 Vdc/ac
Shunt closing release - XF
24 Vac
48 Vac
100…125 Vdc
100…130 Vac
200…250 Vdc
200…240 Vac
24…30 Vdc
48…60 Vdc
100…130 Vdc/ac
200…250 Vdc/ac
Operation counter CDM (already included if remote control supplied)
Additional auxiliary contacts OF (4 AC)
1
2
Ready to close contact PF (1 AC)
LV plug
42-pin LV plug (instead of 18)
Operating crank
Quantity (one mini per switchboard)
Locking of the circuit breaker in the open position
By padlock
or by locks and keys
Profalux
Ronis
If locks
1 lock
2 identical locks
2 different locks
Disabling of O/C circuit breaker push buttons
Cradle
Phase distance (mm)
Quantity
145
Cradle accessories
Racked in/out C.B. position signalling (4 AC)
C.B. “ready to be operated” PAF (1 AC)
Field deflectors for bushings
Releases combinations table
Shunt opening MX
Undervoltage MN
Mitop
48
1
2
1
1
1
2
1
1
1
1
1
185
240
Offer structure
Separated components
Evolis 17.5 kV
withdrawable,
frontal version
0
The following components can be ordered
separately and can be adapted or replaced
by the customer.
Remote control
Ref.
DE56879
MX1, MX2, XF shunt opening/closing release
24…30 Vdc
48…60 Vdc
100…130 Vac - 50/60 Hz
200…250 Vac - 50/60 Hz
24 V 50/60 Hz
48 V 50/60 Hz
59141
59142
59143
59144
24…30 Vdc
48…60 Vdc
100…130 Vac - 50/60 Hz
200…250 Vac - 50/60 Hz
24 V 50/60 Hz
48 V 50/60 Hz
33668
33669
33670
33671
DE56879
MN undervoltage release
DE56933
MCH electrical motor
24…30 Vdc
48…60 Vdc
100…125 Vdc
200…250 Vdc
48…60 Vac - 50/60 Hz
100…130 Vac - 50/60 Hz
200…240 Vac - 50/60 Hz
47888
47889
47890
47891
47889
47893
47894
4 AC
47887
DE56885
Additional auxiliary contacts
MV and LV connection accessories
Ref.
Arm
3 clusters + 3 fingers
3 clusters + 3 fingers
3 arms
3 arms
DE56956
DE56955
DE56954
MV connection accessories
Cluster
Finger
630-1250 A
630-2500 A
630-1250 A
630-2500 A
59369
59371
59396
59397
DE56957
LV plug
Standard (18 pins)
All options (42 pins)
59114
59115
1 terminal block
47074
21 marked LV wires fitted in socket type pins
59117
DE56958
LV terminal blocks
LV wiring
Other circuit breaker accessories
Ref.
DE56953
DE56951
DE56952
Upstream and downstream fixed connections, Ir (to be mounted on basic circuit breaker or bushings)
Fig. 2
Fig. 1
Fig. 3
3 fixed distance H or V (fig. 1)
3 variable distance H (fig. 3)
3 variable distance V (fig. 2)
630-1250 A
630-1250 A
630-1250 A
59400
59401
59402
630-2500 A
630-2500 A
630-2500 A
59403
59404
59405
630-2500 A
630-2500 A
630-2500 A
59409
59410
59411
DE56953
DE56951
DE56952
Upstream fixed connections, Ir (to be mounted on basic circuit breaker or bushings)
or downstream fixed connections, Ir (to be mounted on bushings only)
Fig. 2
Fig. 1
Fig. 3
3 fixed distance H or V (fig. 1)
3 variable distance H (fig. 3)
3 variable distance V (fig. 2)
Fig. 1
DE56953
DE56951
DE56952
Downstream fixed connections, Ir (to be mounted on basic circuit breaker only)
Fig. 2
Fig. 3
3 fixed distance H or V (fig. 1)
3 variable distance H (fig. 3)
3 variable distance V (fig. 2)
49
Evolis 17.5 kV
withdrawable,
frontal version
Offer structure
Separated components (cont.)
DE56855
Earthing device
Earthing sliding contact on C.B.
59456
Circuit breaker specific labels green, red, etc.
59100
Adaptation kit needed for circuit breaker opening (for retrofit)
59093
ON
push OFF
DE56898
Labels kit for push button and indicator (O/C)
push
d
charge
O OFF
OK
d
charge
OK
dis
ch
arg
ed
DE56897
Circuit breaker opening external device
Cradle
Ref.
DE56994
Cradle without bushings
Phase distance 145 mm
Phase distance 185 mm
Phase distance 240 mm
59316
59317
59318
1 full bushing 630-1250 A
1 full bushing 630-2500 A
(you need at least 6 bushings per cradle)
59382
59383
DE56995
Bushings
DE56939
Field deflectors for bushings
6 deflectors used to increase dielectric
withstand from 75 to 95 kV
59283
4 AC
59173
C.B. “ready to be operated” PAF (1 AC)
indicates that the C.B. is locked in place in the cradle
59174
2 rails
59299
DE51950
Racked in/out position signalling
DE56938
Ready to be operated signalling
Racking base
Various
Ref.
DE56996
Circuit breaker support frame
Drawings and casters
59050
User manual
59069
DE56997
Technical documentation
an
de
mm
on ca
cti ôle
m
pa
ote ntr
Se +
Pr co
e 00
et
10
mmm ion
ce
Ga pa lat on rvi
Se tal ati se
Ins ilis en
Ut se
Mi
I off
O
off
SF6
ext
b>>51n
b>51n
I>51
Trip
reset
on
50
ir
0
Evolis 17.5 kV
withdrawable,
frontal version
Services
0
The following components can only be adapted or replaced
on site by staff trained by Schneider Electric:
b remote control mechanism (comprising: electrical motor, shunt closing release,
operation counter)
b operation counter
b low energy release (Mitop)
b interlocking between the “open” circuit breaker position and the LV plug
b racking truck
b circuit breaker front cover.
51
0
52
Evolis
Evolis 24 kV
fixed, frontal version
0
Panorama
Evolis 17.5 kV fixed, frontal version
Evolis 17.5 kV withdrawable, frontal version
11
15
33
Main characteristics
54
Description of functions
MV connection
LV connection
Opening circuit
Remote control
Indication and locking/interlocking
Wiring diagram
55
55
56
57
58
59
60
Dimensions
61
Offer structure
62
Order form
63
Separated components
64
Services
66
Evolis 24 kV withdrawable, frontal version
Evolis and EVOset 24 kV fixed, lateral version
Evolis Pilot monitoring device
67
87
109
53
Evolis 24 kV
fixed, frontal version
Main characteristics
0
PE55692
Electrical characteristics according to IEC 62271-100
Ur 24 kV
Isc
Phase to phase distance (mm)
Ud 50 kV 50 Hz, 1 min
16 kA
Up 125 kV peak
Ir
25 kA
31.5 kA
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
230
b
b
b
b
250
b
b
b
b
b
b
b
b
b
b
b
b
Additional characteristics according to IEC 62271-100
Rated values
Voltage
Ur
Insulation voltage:
- power frequency withstand
Ud
- lightning impulse withstand (1.2/50 µs) Up
Frequency
fr
Short time withstand current
Ik/tk
Peak withstand current
Ip
Short circuit making capacity
kV rms
24
kV rms
kV peak
Hz
kA
kA peak
50
125
50-60
Isc/3 s
2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
kA peak
Other characteristics
Operating sequence
Operating times
Mechanical endurance
Electrical endurance
Number of switching operations
at full Isc value
Capacitive current breaking capacity
Operating conditions
Average relative humidity
54
Opening ms
Breaking ms
Closing
ms
Class
Number of switching
operations
Class
16 kA
25 kA
31.5 kA
Class
Over 24 h
Over 1 month
O-0.3 s-CO-15 s-CO
O-0.3 s-CO-3 min-CO
O-3 min-CO-3 min-CO
< 50
< 65
< 70
M2
10000 (30000 on request)
E2
100
100
100
C1-C2 (for certain applications)
–25°C to +40°C
< 95%
< 90%
Description of functions
MV connection
Evolis 24 kV
fixed, frontal version
0
Composition
The basic circuit breaker is equipped with nickel plated aluminium connector
terminals with drilled holes.
Connection
DE56011
The customer connection is carried out easily from outside the circuit breaker on these
vertical connection terminals.
Connection configurations that have undergone type testing are shown
in the Installation Guide.
55
Evolis 24 kV
fixed, frontal version
Description of functions
LV connection
0
DE51951
Two connection solutions
Directly on the LV terminal block
The circuit breaker’s LV wiring can be directly connected to the LV terminal block of
the operating mechanism through a cable protection duct.
With LV plug
b The fixed part (male) mounted on the circuit breaker and fully connected to
the operating mechanism
b The mobile part (female) compatible with the male part.
Two versions of the LV plug are available
LV connection without plug
An 21-pin version, enabling connection of:
b a shunt opening release YO1
b an electrical remote control mechanism (electrical motor, shunt closing release XF,
anti-pumping relay)
b the “Pilot” monitoring device
b a maximum number of auxiliary contacts: 3 NC - 3 NO - 1 changeover contact.
DE51952
(see “indication and locking/interlocking” page, “Open/closed position auxiliary contacts” chapter).
Note: see the table of the releases’ combinations “Order form” page.
An 42-pin version, enabling connection of:
b an opening release (shunt type YO1 or undervoltage type YM)
b a second opening release (shunt type YO2 or undervoltage type YM
or Mitop low energy release)
b an electrical remote control mechanism (electrical motor, shunt closing release YF,
anti-pumping relay)
b the “Pilot” monitoring device
b a maximum number of auxiliary contacts: 5 NC - 6 NO - 1 changeover contact.
(see “indication and locking/interlocking” page, “Open/closed position auxiliary contacts” chapter).
Note: see the table of the releases’ combinations “Order form” page.
LV wiring kit
LV connection with plug
A wiring kit with 21 or 42 wires (2 meters long) equipped with pins that can be
adapted to the LV plug can be supplied for connected in to the cubicle’s LV
compartment.
Flexible ducting
This 525 mm long duct with a hinged LV plug, enables protection of the LV wiring
that connects the circuit breaker to the cubicle’s LV compartment.
Interlocking kit
For circuit breakers intended for withdrawable applications, an interlocking kit can be
adapted. The kit enables the mechanical position status to be given (“connected/
disconnected”) of the LV plug. By adding a link between this mechanical data
(by the customer) and the open/closed position of the circuit breaker, interlocking
can be achieved between the LV plug and the open/closed position
of the circuit breaker (required by IEC standard 62271-200).
A detailed explanation of operation is given in the Installation Guide.
56
Evolis 24 kV
fixed, frontal version
Description of functions
Opening circuit
0
DE56114EN
Composition
The opening circuit is produced using the following components:
b shunt opening release (Y01)
b second shunt opening release (YO2)
b undervoltage release (YM)
b low energy release (Mitop).
(2)
(1) or (3)
Note: see the table of the releases’ combinations “Order form” page.
Shunt opening release (YO1 and YO2)
Energizing this release causes instant opening of the circuit breaker.
Characteristics
Power supply
Threshold
See “Order form” page
V AC
0.85 to 1.1 Un
V DC
0.7 to 1.1 Un
V AC
160 VA
V DC
50 W
Consumption
Operating mechanism
Undervoltage release (YM)
DE60094
This release unit causes the systematic opening of the circuit breaker when its
supply voltage drops below a value less than 35% of the rated voltage, even if this
drop is slow and gradual. It can open the circuit breaker between 35% and 70% of
its rated voltage. If the release unit is not supplied power, manual or electrical closing
of the circuit breaker is impossible. Closing of the circuit breaker is possible when
the supply voltage of the release unit reaches 85% of its rated voltage.
Shunt opening release (1)
Characteristics
DE60089
Power supply
Threshold
Consumption
Triggering
Latched
See “Order form” page
Opening
0.35 to 0.7 Un
Closing
0.85 Un
V AC
400 VA
V DC
100 W
V AC
100 VA
V DC
10 W
Undervoltage release (2)
DE60091
Low energy release (Mitop)
This release includes a low consumption unit and is specifically used with the Sepam
100LA self-powered relay (“REFLEX MODULE”), or the VIP relay.
Characteristics
Low energy release (3)
Power supply
Threshold
Direct current
0.6 A < I < 3 A
Any tripping due to the Mitop release unit is momentarily indicated by an SDE type
changeover contact (option).
57
Evolis 24 kV
fixed, frontal version
DE56115
(5)
Description of functions
Remote control
Function
Remote control enables the remote opening and closing of the circuit breaker.
Composition
The remote control mechanism comprises:
b an electrical motor with gearing
b a shunt closing release (YF) combined with an anti-pumping device
b an operation counter.
Electrical motor with gearing
The electrical motor carries out the automatic rearming of the stored energy unit as
soon as the circuit breaker is closed. This allows the instant reclosing of the device
after opening. The arming lever is only used as a backup operating mechanism
in the case of the absence of the auxiliary power supply.
The M3 contact indicates the end of arming operations.
Characteristics
(4)
Power supply
Threshold
Consumption
Operating mechanism
See “Order form” page
V AC/V DC
0.85 to 1.1 Un
V AC
380 VA
V DC
380 W
DE60093
Shunt closing release (YF)
This release allows the remote closing of the circuit breaker when the operating
mechanism is armed.
Characteristics
DE60151
Electrical motor and gearing (4)
Power supply
Threshold
Consumption
See “Order form” page
V AC
0.85 to 1.1 Un
V DC
0.85 to 1.1 Un
V AC
160 VA
V DC
50 W
The shunt closing release is combined with an anti-pumping relay that enables priority
to be given to opening in the case of a permanent closing order. This thus avoids
the device being caught in an uncontrolled opening-closing cycle.
Shunt closing release (5)
58
0
DE56116
Evolis 24 kV
fixed, frontal version
(6)
Description of functions
Indication and locking/interlocking
0
Operation counter
(7)
The operation counter is visible on the front panel.
It displays the number of switching cycles (CO) that the device has carried out.
“Open/closed” auxiliary contacts (OC)
These auxiliary contacts indicate the “open” or “closed” position of the circuit breaker.
The number of contacts available depends on the options chosen on the operating
mechanism.
(8)
b In the basic configuration, the circuit breaker operating mechanism comprises
a total of:
v 5 normally closed contacts (NC)
v 6 normally open contacts (NO)
v 1 changeover contact (CHG).
The usage mode for auxiliary contacts is given in the following table:
Options
DE60087
Operating mechanism
DE51953
Operation counter (6)
Auxiliary contacts (7)
NC contact
1
0
0
0
1
Remote control
Shunt opening release (each one)
Undervoltage release
Low energy release (Mitop)
Trip circuit supervision
NO contact
1
1
0
0
0
To know the final number of available contacts, you must deduct the total number
of contacts included in the circuit breaker (5 NC + 6 NO + 1 CHG) from the number
of contacts used indicated in the table below.
E.g.: a circuit breaker equipped with a remote control and a shunt release
has the following contacts available:
4 NC + 4 NO + 1 CHG.
With an undervoltage release instead of a shunt release, this circuit breaker
would have the following available contacts:
4 NC + 5 NO + 1 CHG.
b Using a 21-pin LV plug (for withdrawable applications) the maximum number of
available contacts is:
v 3 NC
v 3 NO
v 1 changeover.
(Instead of 5 NC-6 NO-1 CHG with a 42-pin socket).
DE60124
Contact characteristics
Rated current
Breaking capacity
AC
DC
220 V (cos ϕ ≥ 0.3)
110/220 V (L/R ≤ 0.02 s)
10 A
1A
0.3 A
Locking of the circuit breaker in the “open” position
This locking system enables the fitting of a Profalux or Ronis captive key type
keylock (right turn type keylock).
The keylock is not part of the kit but can be supplied as an option.
Kit to lock the circuit breaker in the “open” position (8)
59
Evolis 24 kV
fixed, frontal version
Description of functions
Wiring diagram
0
DE56117EN
Wiring diagram (principle)
Close CB
Open CB
M
M3
YF +
anti-pumping
Motor
Shunt closing
release
+ anti-pumping
system
Remote control
60
YO1
“Control
mechanism
armed”
indicator contact
YO2
Shunt
opening
release
Mitop
YM
Undervoltage
release
Low energy
release
(Mitop)
Changeover
contact
NO
NC
contacts contacts
Dimensions
Evolis 24 kV
fixed, frontal version
0
Device
Isc
16 kA
Ir
630 A
25 kA
1250 A
630 A
1250 A
Weight
97 kg
DE56127
Ur
24 kV
DE56126
Phase to phase distance 230 mm
593
Isc
16 kA
Ir
630 A
25 kA
1250 A
630 A
1250 A
Weight
97 kg
DE56127
Ur
24 kV
DE56128
Phase to phase distance 250 mm
Isc
16 kA
25 kA
31.5 kA
Ir
2000 A
Weight
135 kg
DE56130
Ur
24 kV
DE56129
593
2500 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
593
Important
Detailed installation instructions are given in
the “Evolis Installation Guide”. Please consult us.
61
Evolis 24 kV
fixed, frontal version
Offer structure
0
The basic fixed, frontal circuit breaker includes:
b a manual operating mechanism (spring type)
b 1 shunt opening release YO1
b 1 block of auxiliary contacts.
The circuit breaker can receive options.
Basic fixed, frontal circuit breaker
DE56031
Phase distance (mm)
24 kV - 125 kV peak
16 kA
25 kA
31.5 kA
230
b
b
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
b
b
Circuit breaker options
DE56038
DE56033
DE56037
Remote control (see possible choices in combination table below)
Fig. 1
Fig. 2
Fig. 3
1st opening release
Possibility of replacing YO1 by
undervoltage release - YM (fig. 2)
2nd opening releasee
Shunt opening release - YO2 (fig. 1)
Undervoltage release - YM (fig. 2)
Low energy release Mitop (fig. 3)
Remote control including:
Electrical motor, gear reducer, shunt closing release,
anti-pumping relay, operation counter
Releases combinations table
Shunt opening YO1
Shunt opening YO2
Undervoltage release YM
Mitop
No LV plug or
42-pin LV plug
1
1 1 1
1
1
1
1
21-pin
LV plug
1
1
1
Indication
DE56040
Operation counter (already included if remote control supplied)
LV wiring connection
DE51954
21-pin LV plug
42-pin LV plug
Locking, interlocking
DE56039
Open position circuit breaker locking (without lock)
Ronis lock
Profalux lock
Monitoring device
DE56035
Pilot module (with connecting kit)
Diagnosis by Schneider Electric expert
62
250
b
b
b
b
b
b
b
b
b
b
b
b
Order form
Evolis 24 kV
fixed, frontal version
Only one of the boxes (ticked X or filled
by
the needed value) have to be considered between each
horizontal line.
Orange box X corresponds to none priced functions.
0
Basic fixed, frontal circuit breaker
Quantity
Rated voltage Ur
(kV)
Rated short-circuit breaking current Isc
(kA)
Rated normal current Ir
(A)
Phase distance (mm)
Colour for push buttons and indicators
230
Operating mechanism charged/discharged:
250
IEC standard
ANSI standard
red/black
Push buttons open/closed:
Indicator open/closed:
24
black/white
green/red
white/yellow
charge/discharge
Circuit breaker options
1st opening release (see possible choices in combination table below)
Shunt opening release - YO1
24 Vdc
48 Vdc
Undervoltage release - YM
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
2nd opening release (see possible choices in combination table below)
Shunt opening release - YO2
24 Vdc
48 Vdc
Undervoltage release - YM
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
Low energy release Mitop
Remote control (operation counter already included)
Electrical motor
Shunt closing release - YF
24 Vdc
48 Vdc
24…32 Vdc
48…60 Vdc/ac
100…127 Vdc/ac
220…250 Vdc/ac
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
Operation counter (already included if remote control supplied)
LV plug
21 pins LV plug
Open position CB locking (without lock)
Lock
Ronis
Pilot module (with connecting kit)
Without LV plug
Diagnosis by Schneider Electric expert (separated order)
Releases combinations table
No LV plug or
42-pin LV plug
1
1 1 1
Shunt opening YO1
Shunt opening YO2
1
Undervoltage YM
1
1
Mitop
1
42 pins LV plug
Profalux
With LV plug
21-pin
LV plug
1
1
1
63
Evolis 24 kV
fixed, frontal version
Offer structure
Separated components
0
The following components can be ordered
separately and can be adapted or replaced
by the customer.
Remote control
Ref.
Shunt opening release YO1 or YO2
DE56037
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
50 Hz
50 Hz
60 Hz
AAA10 115
AAA10 116
AAA10 117
AAA10 118
AAA10 119
AAA10 120
AAA10 121
AAA10 122
50 Hz
50 Hz
60 Hz
AAA10 106
AAA10 107
AAA10 108
AAA10 109
AAA10 110
AAA10 111
AAA10 112
AAA10 113
50 Hz
50 Hz
60 Hz
AAA10 124
AAA10 125
AAA10 126
AAA10 127
AAA10 128
AAA10 129
AAA10 130
AAA10 131
Shunt closing release YF
DE56041
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
Undervoltage release YM
DE56033
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
Electrical motor
DE56036
DE56042
24… 32 Vdc
48… 60 Vac/dc
100… 127 Vac/dc
220… 250 Vac/dc
Gear reducer
Locking, interlocking
Ref.
DE56039
Open position CB locking device (without lock)
Ronis lock
Profalux lock
Interlocking kit fixed CB
64
AAA10 027
AAA10 028
AAA10 029
AAA10 030
AAA10 065
AAA10 092
AAA10 058
AAA10 059
AAA10 033
Evolis 24 kV
fixed, frontal version
Offer structure
Separated components (cont.)
MV and LV connection accessories
0
Ref.
Arm
Clusters set (including fingers)
DE56956
DE56955
DE51941
MV connection accessories
Cluster
Arms set
630-1250 A
2500 A
630-1250 A
AAA10 025
AAA10 026
AAA10 022
LV plug support
21-pin plug
LV plug support
42-pin plug
AAA10 035
AAA10 031
AAA10 035
AAA10 032
Finger
LV connection
DE51954
21-pin LV plug*
42-pin LV plug*
(*) 2 references are necessary
PE55698
Flexible conduct for LV wiring
LV connecting kit 24 wires
LV connecting kit 42 wires
59099
59117
AAA10 087
DE56035
Monitoring device
Pilot module (consult us)
65
Evolis 24 kV
fixed, frontal version
Services
The following components can only be adapted or replaced
on site by staff trained by Schneider Electric:
b the “Pilot” monitoring device
b remote control mechanism (comprising: electrical motor, gearing, shunt closing
release, anti-pumping relay, operation counter)
b operation counter
b low energy release (Mitop)
b circuit breaker front cover.
66
0
Evolis
Evolis 24 kV
withdrawable, frontal version
0
Panorama
Evolis 17.5 kV fixed, frontal version
Evolis 17.5 kV withdrawable, frontal version
Evolis 24 kV fixed, frontal version
11
15
33
53
Main characteristics
68
Description of functions
Racking in
LPCT sensors
MV connection
LV connection
Opening circuit
Remote control
Indication and locking/interlocking
Wiring diagram
Safety functions
69
69
71
72
73
74
75
76
77
78
Dimensions
79
Offer structure
80
Order form
82
Separated components
83
Services
85
Evolis and EVOset 24 kV fixed, lateral version
Evolis Pilot monitoring device
87
109
67
Evolis 24 kV
withdrawable,
frontal version
Main characteristics
0
PE55693
Electrical characteristics according to IEC 62271-100
Ur 24 kV
Isc
Phase to phase distance (mm)
Ud 50 kV 50 Hz, 1 min
16 kA
Up 125 kV peak
Ir
25 kA
31.5 kA
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
230
b
b
250
b
b
b
b
b
b
b
b
b
b
Additional characteristics according to IEC 62271-100
Rated values
Voltage
Ur
Insulation voltage:
- power frequency withstand
Ud
- lightning impulse withstand (1.2/50 µs) Up
Frequency
fr
Short time withstand current
Ik/tk
Peak withstand current
Ip
Short circuit making capacity
kV rms
24
kV rms
kV peak
Hz
kA
kA peak
50
125
50-60
Isc/3 s
2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
kA peak
Other characteristics
Operating sequence
Operating times
Mechanical endurance
Electrical endurance
Number of switching operations
at full Isc value
Capacitive current breaking capacity
Operating conditions
Average relative humidity
68
Opening ms
Breaking ms
Closing
ms
Class
Number of switching
operations
Class
16 kA
25 kA
31.5 kA
Class
Over 24 h
Over 1 month
O-0.3 s-CO-15 s-CO
O-0.3 s-CO-3 min-CO
O-3 min-CO-3 min-CO
< 50
< 65
< 70
M2
10000 (30000 on request)
E2
100
100
100
C1-C2 (for certain applications)
–25°C to +40°C
< 95%
< 90%
Evolis 24 kV
withdrawable,
frontal version
Description of functions
Racking in
0
DE51984
Composition
The “racking in” function is carried out by:
b the racking carriage holding the circuit breaker (mobile part)
b the cradle with bushings (fixed part)
b LV plug.
DE51977
Operating position
The circuit breaker can be placed in 3 stable positions:
b service position: circuit breaker racked in and locked in position,
LV plug connected
b test position: circuit breaker racked out and locked in position,
LV plug connected
b disconnected position: the circuit breaker can be unlocked and extracted
from the cubicle, without interlocking.
DE51978
Test position
Operation
Safety functions
A drive system using a threaded shaft gives easier racking and unracking.
DE51961
Disconnected position
Interlocking mechanisms
In conformity with IEC standards 62271-100 and 62271-200, the following interlocks
are available:
b impossibility of racking in or out is the circuit breaker is not in the “open” position
b impossible to rack in the circuit breaker when the LV plug is not connected
b impossible to disconnect the LV plug if the circuit breaker is not racked-out.
Cubicle door interlocking mechanism
The carriage is equipped with a device that enables interlocking between the racking
out of the circuit breaker and the cubicle door (the door must be specifically designed):
b possible to rack in the circuit breaker only if the door is closed
b possible to open the door only if the circuit breaker is racked out.
This device must be disabled if the interlocking function is not present.
Earthing is achieved throughout the operation via the racking carriage casters.
An addition earthing system can be supplied as an option.
Protective shutters placed on the cradle stops access to the racking fingers
when the device is extracted (protection index: IP2X).
For maintenance purpose, it is possible to:
b padlock the shutters in the closed position
b unlock the fixed contact access mechanism and insert a screen
to insulate the energized contact set. A drawing is available on request to produce
this protective screen (see Installation Guide).
Interlocking door-cubicle
A foolproof device enables the cradle to be fitted perfectly to the circuit breaker
relative to the cradle caliber.
This system is mounted on the cradle side. The combination corresponding
to the right circuit breaker rating must be produced by the panel builder.
Anti-drop function:
This function provides operator safety when extracting the circuit breaker.
Earthing switch
It can be fitted under the cradle, to give the appropriate interlocking between
the circuit breaker and the earthing switch (see detailed description
in the “Earthing switch and cubicle components” catalogue).
69
Description of functions
Racking in (cont.)
DE56025
Racked in/out position
Auto-discharge function
70
0
Optional accessories
DE56855
DE51950
Evolis 24 kV
withdrawable,
frontal version
Earthing sliding device
b 4 racked in/out position contacts.
b Additional earthing device (copper sliding device).
b LPCT tore type sensors, mounted directly on the cradle bushings.
b Auto-discharge function:
the circuit breaker operating mechanism springs are automatically discharged
when the circuit breaker is extracted from the cubicle. This function avoids all risks
of spurious closing of the circuit breaker.
b Test position contact.
This contact is activated when the circuit breaker is in the “test” or “service” position.
b Access ramp for the circuit breaker in the cradle.
Evolis 24 kV
withdrawable,
frontal version
Description of functions
LPCT sensors
LPCT sensors are the best way to increase
the effectiveness of the protection chain
and simplify the selection.
Function
0
LPCT type sensors (Low Power Current Transducers) provide accurate
measurement for protection functions when an Evolis circuit breaker is combined
with a Sepam range relay.
DE60099
They comply with IEC 60044-8 standard.
Composition
Two types of LPCT are available:
b LPCT’s for bushings, with LV insulation for cradle installation (TLP type)
b LPCT with MV insulation for cubicle installation (CLP type).
DE60097
LPCT for bushings (TLP type)
The sensor is supplied with 5 m of cable and connectors that allows
direct connection to the Sepam unit.
Mechanical characteristics (LPCT for bushings TLP type)
Mounted directly on the Evolis withdrawable circuit breaker cradle.
The sensors are simply located on the bushings and fixed using three screws.
Each sensor covers the full operating range of the corresponding circuit breaker.
Connection to the Sepam is achieved using a shielded cable which is attached to
each sensor.
LPCT for cubicle (CLP type)
Electrical characteristics:
b conformity with IEC standard 60044-8, which defines LPCT’s with an output
voltage
b usable for nominal currents of 25 A to 2500 A
b class 0.5 throughout the range
b current sensors give a voltage output at a ratio of 100 A/22.5 mV.
Common features
Rated primary current
Rated secondary output (at 100 A)
Accuracy class for measuring
Accuracy class for protection
Burden
Frequency
100 A
22.5 mV
0.5
5P
u 2 kΩ
50/60 Hz
TLP190
On the bushings
On the bushings
Rated extended primary current
Accuracy limit factor
Rated short time thermal current
Rated voltage
Rated power frequency withstand voltage
Rated lightning impulse withstand voltage
Internal diameter
1250 A
250
25 kA/3 s
24 kV
50 kV
125 kV
2500 A
315
31.5 kA/3 s
24 kV
50 kV
125 kV
DE60100
TLP160
In the cubicle
DE60099
CLP3
In the cubicle
DE60098
CLP2
Assembly
DE60097
Specific features
1250 A
250
25 kA/3 s
24 kV (1)
50 kV
125 kV
160 mm
2500 A
315
31.5 kA/3 s
24 kV (1)
50 kV
125 kV
190 mm
(1) Voltage applied to the cradle equipped with sensors
71
Description of functions
MV connection
Evolis 24 kV
withdrawable,
frontal version
Connection
DE60158
DE56026
The customer connection is carried out easily from outside the cradle on copper
vertical connection terminals integrated in the bushings.
Field deflectors
The aim of field deflectors is to improve the dielectric strength at the end of the cradle
bushings. They are necessary in the case of installation in a NEX 24 kV type cubicle.
For any other installation, the dielectric strength is the responsibility of the installation
designer.
72
0
Evolis 24 kV
withdrawable,
frontal version
Description of functions
LV connection
0
DE51958
Main functions
With the base circuit breaker, the LV wiring uses a LV plug unit which comprises:
b the fixed part (male) mounted on the circuit breaker and fully connected to
the control mechanism
b the mobile part (female) compatible with the male part.
Two versions of the LV plug are available
Push
Push
ON
OFF
An 21-pin version, enabling connection of:
b a shunt opening release YO1
b an electrical remote control mechanism (electrical motor, shunt closing release YF,
anti-pumping relay)
b the “Pilot” monitoring device
b a maximum number of auxiliary contacts: 3 NC - 3 NO - 1 changeover contact.
(see “indication and locking/interlocking” page, “Open/closed position auxiliary contacts” chapter).
Note: see the table of the releases’ combinations “Order form” page.
An 42-pin version, enabling connection of:
b an opening release (shunt type YO1 or undervoltage type YM)
b a second opening release (shunt type YO2 or undervoltage type YM
or Mitop low energy release)
b an electrical remote control mechanism (electrical motor, shunt closing release YF,
anti-pumping relay)
b the “Pilot” monitoring device
b a maximum number of auxiliary contacts: 5 NC -6 NO -1 changeover contact.
(see “indication and locking/interlocking” page, “Open/closed position auxiliary contacts” chapter).
Note: see the table of the releases’ combinations “Order form” page.
Interlocking function
In conformity with IEC standard 62271-200, an interlocking function prohibits:
b racking in when the LV plug is not connected
b disconnection of the LV plug if the circuit breaker is in the racked-in position.
LV wiring kit
A wiring kit with 21 or 42 wires (2 meters long) equipped with pins that can be
adapted to the LV plug can be supplied for connected in to the cubicle’s LV
compartment.
Flexible ducting
This 525 mm long duct with a hinged LV plug, enables protection of the LV wiring
that connects the circuit breaker to the cubicle’s LV compartment.
73
Description of functions
Opening circuit
Evolis 24 kV
withdrawable,
frontal version
0
DE56114EN
Composition
In its basic version, the circuit breaker includes a shunt opening release (YO1).
The opening circuit can be produced using the following components:
b second shunt opening release (on energizing) (YO2)
b undervoltage release (YM)
b low energy release (Mitop).
(2)
(1) or (3)
Note: see the table of the releases’ combinations “Order form” page.
Shunt opening release (YO1 and YO2)
Energizing this release causes instant opening of the circuit breaker.
Characteristics
Power supply
Threshold
See “Order form” page
V AC
0.85 to 1.1 Un
V DC
0.7 to 1.1 Un
V AC
160 VA
V DC
50 W
Consumption
Operating mechanism
Undervoltage release (YM)
DE60094
This release unit causes the systematic opening of the circuit breaker when its
supply voltage drops below a value less than 35% of the rated voltage, even if this
drop is slow and gradual. It can open the circuit breaker between 35% and 70% of
its rated voltage. If the release unit is not supplied power, manual or electrical closing
of the circuit breaker is impossible. Closing of the circuit breaker is possible when
the supply voltage of the release unit reaches 85% of its rated voltage.
Shunt opening release (1)
Characteristics
DE60089
Power supply
Threshold
Consumption
Triggering
Latched
See “Order form” page
Opening
0.35 to 0.7 Un
Closing
0.85 Un
V AC
400 VA
V DC
100 W
V AC
100 VA
V DC
10 W
Undervoltage release (2)
DE60091
Low energy release (Mitop)
This release includes a low consumption unit and is specifically used with the Sepam
100LA self-powered relay (“REFLEX MODULE”), or the VIP relay.
Characteristics
Low energy release (3)
Power supply
Threshold
Direct current
0.6 A < I < 3 A
Any tripping due to the Mitop release unit is momentarily indicated by an SDE type
changeover contact (option).
74
Evolis 24 kV
withdrawable,
frontal version
DE56115
(5)
Description of functions
Remote control
0
Function
Remote control enables the remote opening and closing of the circuit breaker.
Composition
The remote control mechanism comprises:
b an electrical motor with gearing
b a shunt closing release (YF) combined with an anti-pumping device
b an operation counter.
Electrical motor with gearing
The electrical motor carries out the automatic rearming of the stored energy unit as
soon as the circuit breaker is closed. This allows the instant reclosing of the device
after opening. The arming lever is only used as a backup operating mechanism
in the case of the absence of the auxiliary power supply.
The M3 contact indicates the end of arming operations.
Characteristics
(4)
Power supply
Threshold
Consumption
Operating mechanism
See “Order form” page
V AC/V DC
0.85 to 1.1 Un
V AC
380 VA
V DC
380 W
DE60093
Shunt closing release (YF)
This release allows the remote closing of the circuit breaker when the operating
mechanism is armed.
Characteristics
DE60151
Electrical motor and gearing (4)
Power supply
Threshold
Consumption
See “Order form” page
V AC
0.85 to 1.1 Un
V DC
0.85 to 1.1 Un
V AC
160 VA
V DC
50 W
The shunt closing release is combined with an anti-pumping relay that enables priority
to be given to opening in the case of a permanent closing order. This thus avoids
the device being caught in an uncontrolled opening-closing cycle.
Shunt closing release (5)
75
Description of functions
Indication and locking/interlocking
Evolis 24 kV
withdrawable,
frontal version
DE56116
(6)
0
Operation counter
(7)
The operation counter is visible on the front panel.
It displays the number of switching cycles (CO) that the device has carried out.
“Open/closed” auxiliary contacts (OC)
These auxiliary contacts indicate the “open” or “closed” position of the circuit breaker.
The number of contacts available depends on the options chosen on the operating
mechanism.
(8)
b In the basic configuration, the circuit breaker operating mechanism comprises
a total of:
v 5 normally closed contacts (NC)
v 6 normally open contacts (NO)
v 1 changeover contact (CHG).
The usage mode for auxiliary contacts is given in the following table:
Options
DE60087
Operating mechanism
DE51953
Operation counter (6)
Auxiliary contacts (7)
NC contact
1
0
0
0
1
Remote control
Shunt opening release (each one)
Undervoltage release
Low energy release (Mitop)
Trip circuit supervision
NO contact
1
1
0
0
0
To know the final number of available contacts, you must deduct the total number
of contacts included in the circuit breaker (5 NC + 6 NO + 1 CHG) from the number
of contacts used indicated in the table below.
E.g.: a circuit breaker equipped with a remote control and a shunt release
has the following contacts available:
4 NC + 4 NO + 1 CHG.
With an undervoltage release instead of a shunt release, this circuit breaker
would have the following available contacts:
4 NC + 5 NO + 1 CHG.
b Using a 21-pin LV plug (for withdrawable applications) the maximum number
of available contacts is:
v 3 NC
v 3 NO
v 1 changeover.
(Instead of 5 NC-6 NO-1 CHG with a 42-pin socket).
DE60124
Contact characteristics
Rated current
Breaking capacity
AC
DC
220 V (cos ϕ ≥ 0.3)
110/220 V (L/R ≤ 0.02 s)
10 A
1A
0.3 A
Locking of the circuit breaker in the “open” position
This locking system enables the fitting of a Profalux or Ronis captive key type
keylock (right turn type keylock).
The keylock is not part of the kit but can be supplied as an option.
Kit to lock the circuit breaker in the “open” position (8)
76
Description of functions
Wiring diagram
Evolis 24 kV
withdrawable,
frontal version
0
DE56117EN
Wiring diagram (principle)
Close CB
Open CB
M
M3
YF +
anti-pumping
Motor
Shunt closing
release
+ anti-pumping
system
YO1
“Control
mechanism
armed”
indicator contact
YO2
Shunt
opening
release
Mitop
YM
Undervoltage
release
Low energy
release
(Mitop)
Changeover
contact
NO
NC
contacts contacts
Remote control
77
Description of functions
Safety functions
Evolis 24 kV
withdrawable,
frontal version
0
This table describes the safety functions available on the withdrawable version
of the Evolis 24 kV circuit breaker.
How to use the table
Each of the boxes describes the functional status of each circuit breaker position
and the associated parts:
Possible status
Possible status, operation impossible
Impossible status
Parts
Circuit breaker positions
Insertion
Racking-in
Extraction
Racking-out
Removed
1 - Cradle
Disconnected Test position
Service
Fool-proof
protection (1)
Anti-drop (2)
No opening shutters
Shutters padlocking possible
2 - LV plug
Disconnected
No racking-in
Connected
3 - Circuit breaker
No unplugging
Closed
Open
Auto-discharge
function (3)
No racking-in
No racking-out
No closing
Open position circuit breaker locking available (3)
4 - Switchboard door
Open
No racking-in
Closed
5 - Earthing switch
No door opening (4)
Open
Closed
No earthing switch closing
No racking-in
(1) This protection mechanism ensures that the performance levels of the circuit breaker correspond with those of the cradle.
(2) Device that prevents the circuit breaker from dropping when extracted from the cradle.
The device can be either unlocked manually or when the extraction rig is put in position.
(3) Option.
(4) Interlocking device to be fitted to the cubicle door. If there is no interlocking, the circuit breaker device should be inhibited.
78
Dimensions
Evolis 24 kV
withdrawable,
frontal version
0
Device
Phase to phase distance 230 mm
Ir
630 A
25 kA
1250 A
630 A
1250 A
Weight *
145 +125 kg
230
163
288
DE56132
Isc
16 kA
DE56131
230
Ur
24 kV
400
1188
473.5
786
1309
1400
Phase to phase distance 250 mm
25 kA
31.5 kA
Ir
2000 A
Weight *
206 +148 kg
250
193
288
DE56132
Isc
16 kA
DE56133
250
Ur
24 kV
2500 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
400
1188
(*) Circuit breaker + cradle
473.5
886
1309
1400
Important
Detailed installation instructions are given in
the “Evolis Installation Guide”. Please consult us.
79
Offer structure
Evolis 24 kV
withdrawable,
frontal version
0
The basic withdrawable, frontal circuit breaker includes:
b 6 arms with clusters,
b racking truck with operating crank and screw-shaft system
b a manual operating mechanism (spring type)
b a 21-pin LV plug
b 1 shunt opening release YO1
b 1 block of auxiliary contacts
b an interlocking kit between the LV plug and the circuit breaker position O/C.
The circuit breaker can receive options.
The cradle includes:
b 6 bushings with fingers
b shutters
b shutters mechanism.
The cradle can receive accessories.
Basic withdrawable, frontal circuit breaker
DE56032
Phase distance (mm)
24 kV - 125 kV peak
16 kA
25 kA
31.5 kA
230
b
b
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
630 A
1250 A
2000 A
2500 A
b
b
b
b
b
b
b
b
b
b
Circuit breaker options
DE56038
DE56033
DE56037
Remote control (see possible choices in combination table below)
Fig. 1
Fig. 2
Fig. 3
1st opening release
Possibility of replacing YO1 by
undervoltage release - YM (fig. 2)
2nd opening release
Shunt opening release - YO2 (fig. 1)
Undervoltage release - YM (fig. 2)
Low energy release Mitop (fig. 3)
Remote control including:
Electrical motor, gear reducer, shunt closing release,
anti-pumping relay, operation counter
Releases combinations table
Shunt opening YO1
Shunt opening YO2
Undervoltage YM
Mitop
42-pin
LV plug
1
1
1
1
1
21-pin
LV plug
1
1
1
1
1
1
Indication
DE56040
Operation counter (already included if remote control supplied)
LV wiring connection
DE51954
LV plug: possibility of choosing a 42-pin LV plug instead of a 21-pin LV plug
Rack-in/rack-out operation
DE56915
Operating crank
80
250
Evolis 24 kV
withdrawable,
frontal version
Offer structure (cont.)
0
Locking/interlocking
DE56039
Open position circuit breaker locking device (without lock)
Ronis lock
Profalux lock
Safety device
DE56043
Operating mechanism auto discharge
230 mm phase distance circuit breaker
250 mm phase distance circuit breaker
Earthing sliding device
DE56855
Circuit breaker earthing sliding device
Monitoring device
DE56035
Pilot module (with connecting kit)
Diagnosis by Schneider Electric expert
Cradle
DE56044
Cradle with 230 mm phase distance
Cradle with 250 mm phase distance
Racked in/out position contacts (4 AC) (fig.1)
6 field deflectors for cradle bushings (fig.2)
DE56047
DDE51950
Cradle accessories
Fig. 2
DE56046
DE56045
Fig. 1
TPL 160
630-1250 A
2500 A
LPCT tore sensor
230 mm phase distance cradle (TLP 160) with insulating screen
230 mm phase distance cradle (TLP 190)
TPL 190
81
Order form
Evolis 24 kV
withdrawable,
frontal version
Only one of the boxes (ticked X or filled
by
the needed value) have to be considered between each
horizontal line.
Orange box X corresponds to none priced functions.
0
Basic withdrawable, frontal circuit breaker
Quantity
Rated voltage Ur
(kV)
Rated short-circuit breaking current Isc
(kA)
Rated normal current Ir
(A)
Phase distance (mm)
Colour for push buttons and indicators
230
Operating mechanism charged/discharged:
250
IEC standard
ANSI standard
red/black
Push buttons open/closed:
Indicator open/closed:
24
black/white
green/red
white/yellow
charge/discharge
Circuit breaker options
1st opening release (see possible choices in combination table below)
Shunt opening release - YO1
24 Vdc
48 Vdc
Undervoltage release - YM
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
2nd opening release (see possible choices in combination table below)
Shunt opening release - YO2
24 Vdc
48 Vdc
Undervoltage release - YM
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
Low energy release Mitop
Remote control (operation counter already included)
Electrical motor
24…32 Vdc
48…60 Vdc/ac
100…127 Vdc/ac
220…250 Vdc/ac
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
Operation counter (already included if remote control supplied)
LV plug 42-pin (instead of 21)
Operating crank
Open position CB locking device (without lock)
Lock
Ronis
Auto-discharge device
Earthing sliding contact
Pilot module (with connecting kit and LV plug)
Diagnosis by Schneider Electric expert (separated order)
Profalux
Shunt closing release - YF
24 Vdc
48 Vdc
Cradle
Rated current
Up to 1250 A and 25 kA
Above 1250 A or 25 kA
Cradle accessories
Releases combinations table
42-pin
LV plug
1
1
Shunt opening YO1
Shunt opening YO2
1
Undervoltage YM
1
Mitop
82
Rack in/rack out position contact (4 AC)
LPCT-TLP
Up to 1250 A and 25 kA
6 field deflectors
1
21-pin
LV plug
1
1
1
1
1
1
630-1250 A
Above 1250 A or 25 kA
2500 A
Evolis 24 kV
withdrawable,
frontal version
Offer structure
Separated components
0
The following components can be ordered
separately and can be adapted or replaced
by the customer.
Remote control
Ref.
Shunt opening release YO1 or YO2
DE56037
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
50 Hz
50 Hz
60 Hz
AAA10 115
AAA10 116
AAA10 117
AAA10 118
AAA10 119
AAA10 120
AAA10 121
AAA10 122
50 Hz
50 Hz
60 Hz
AAA10 106
AAA10 107
AAA10 108
AAA10 109
AAA10 110
AAA10 111
AAA10 112
AAA10 113
50 Hz
50 Hz
60 Hz
AAA10 124
AAA10 125
AAA10 126
AAA10 127
AAA10 128
AAA10 129
AAA10 130
AAA10 131
Shunt closing release YF
DE56041
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
Undervoltage release YM
DE56033
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
Electrical motor
DE56036
DE56042
24… 32 Vdc
48… 60 Vac/dc
100… 127 Vac/dc
220… 250 Vac/dc
Gear reducer
DE56039
Locking, interlocking
AAA10 027
AAA10 028
AAA10 029
AAA10 030
AAA10 065
Ref.
Open position CB locking device (without lock)
Ronis lock
Profalux lock
AAA10 092
AAA10 058
AAA10 059
83
Offer structure
Separated components (cont.)
Evolis 24 kV
withdrawable,
frontal version
MV and LV connection accessories
Ref.
Arm
Clusters set (including fingers)
DE56956
DE56955
DE51941
MV connection accessories
Cluster
Arms set
630-1250 A
2500 A
630-1250 A
AAA10 025
AAA10 026
AAA10 022
LV plug support
21-pin plug
LV plug support
42-pin plug
AAA10 035
AAA10 031
AAA10 035
AAA10 032
Finger
LV connection
DE51954
21-pin LV plug*
42-pin LV plug*
(*) 2 references are necessary
PE55698
Flexible conduct for LV wiring
LV connecting kit 21 wires
LV connecting kit 42 wires
59099
59117
AAA10 087
Earthing sliding device
Ref.
DE56855
Earthing sliding contact
59456
Monitoring device
DE56035
Pilot module (consult us)
Cradle
Ref.
Cradle without bushings
DE56048
Cradle with 230 mm phase distance
Cradle with 250 mm phase distance
AAA10 015
AAA10 017
Fig. 2
DE56046
DE56045
Fig. 1
TPL 160
84
Bushing kit for cradle (fig.1)
DE51950
DE56047
DE56995
Cradle accessories
TPL 190
6 field deflectors
for cradle bushings (fig.2)
Fig. 3
4 racked in/out position contacts (fig.3)
(to be installed in the cradle)
LPCT toroidal sensor
630-1250 A
2500 A
630-1250 A
2500 A
AAA10 016
AAA10 018
AAA10 020
AAA10 021
59173
TLP 160 (up to 1250 A)
TLP 190 (above)
AAA10 094
AAA10 095
0
Evolis 24 kV
withdrawable,
frontal version
Services
0
The following components can only be adapted or replaced
on site by staff trained by Schneider Electric:
b the “Pilot” monitoring device
b remote control mechanism (comprising: electrical motor, gearing, shunt closing
release, anti-pumping relay, operation counter)
b operation counter
b low energy release (Mitop)
b interlocking between the “open” circuit breaker position and the LV plug
b racking truck
b auto-discharge device
b circuit breaker front cover.
85
0
86
Evolis
Evolis and EVOset 24 kV
fixed, lateral version
0
Panorama
Evolis 17.5 kV fixed, frontal version
Evolis 17.5 kV withdrawable, frontal version
Evolis 24 kV fixed, frontal version
Evolis 24 kV withdrawable, frontal version
11
15
33
53
67
Main characteristics
Evolis 24 kV
EVOset 24 kV
88
88
89
Description of functions
MV and LV connections
Opening circuit
Remote control
Indication and locking/interlocking
Wiring diagram
90
90
91
92
93
94
Protection, monitoring and control
EVOset : integrated protection chain
VIP30 et VIP35 protection units
VIP300P et VIP300LL protection units
Current sensors and test unit for VIP relays
95
95
96
98
100
Dimensions
101
Offer structure
Evolis 24 kV
EVOset 24 kV
102
105
Order form
Evolis 24 kV
EVOset 24 kV
103
106
Separated components
Evolis 24 kV
EVOset 24 kV
104
107
Services
108
Evolis Pilot monitoring device
109
87
Evolis 24 kV
fixed, lateral version
Main characteristics
0
PE55931
Electrical characteristics according to IEC 62271-100
Ur 24 kV
Isc
Phase to phase distance (mm)
MV connection on the:
Ud 50 kV 50 Hz, 1 min
12.5 kA
Up 125 kV peak
16 kA
20 kA
25 kA
Ir
250
right
b
b
b
b
b
b
b
b
630 A
1250 A
630 A
1250 A
630 A
1250 A
630 A
1250 A
left
b
b
b
b
b
b
b
b
300
right
b
b
b
b
b
b
b
left
b
b
Additional characteristics according to IEC 62271-100
PE55930
Evolis 24 kV fixed, lateral version
MV connection on the right hand side
Rated values
Voltage
Ur
Insulation voltage:
- power frequency withstand
Ud
- lightning impulse withstand (1.2/50 µs) Up
Frequency
fr
Short time withstand current
Ik/tk
Peak withstand current
Ip
Short circuit making capacity
kV rms
24
kV rms
kV peak
Hz
kA
kA peak
50
125
50-60
Isc/3 s
2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
kA peak
Other characteristics
Operating sequence
Operating times
Mechanical endurance
Evolis 24 kV fixed, lateral version
MV connection on the left hand side
Electrical endurance
Number of switching operations
at full Isc value
Capacitive current breaking capacity
Operating conditions
Average relative humidity
88
Opening ms
Breaking ms
Closing
ms
Class
Number of switching
operations
Class
12.5 kA
16 kA
20 kA
25 kA
Class
Over 24 h
Over 1 month
O-0.3 s-CO-15 s-CO
O-0.3 s-CO-3 min-CO
O-3 min-CO-3 min-CO
< 50
< 60
< 65
M2
10000
E2
100
100
100
100
C1-C2 (for certain applications)
–25°C to +40°C
< 95%
< 90%
EVOset 24 kV
fixed, lateral version
Main characteristics
0
PE55932
Electrical characteristics according to IEC 62271-100
Ur 24 kV
Isc
Phase to phase distance (mm)
MV connection on the:
Ud 50 kV 50 Hz, 1 min
12.5 kA
Up 125 kV peak
16 kA
20 kA
Ir
250
right
b
b
b
b
b
b
630 A
1250 A
630 A
1250 A
630 A
1250 A
left
300
right
b
b
b
b
b
b
left
Additional characteristics according to IEC 62271-100
EVOset 24 kV fixed, lateral version
MV connection on the right hand side
Rated values
Voltage
Ur
Insulation voltage:
- power frequency withstand
Ud
- lightning impulse withstand (1.2/50 µs) Up
Frequency
fr
Short time withstand current
Ik/tk
Peak withstand current
Ip
Short circuit making capacity
kV rms
24
kV rms
kV peak
Hz
kA
kA peak
50
125
50-60
Isc/3 s
2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
kA peak
Other characteristics
Operating sequence
Operating times
Mechanical endurance
Electrical endurance
Number of switching operations
at full Isc value
Capacitive current breaking capacity
Operating conditions
Average relative humidity
Opening ms
Breaking ms
Closing
ms
Class
Number of switching
operations
Class
12.5 kA
16 kA
20 kA
Class
Over 24 h
Over 1 month
O-0.3 s-CO-15 s-CO
O-0.3 s-CO-3 min-CO
O-3 min-CO-3 min-CO
< 50
< 60
< 65
M2
10000
E2
100
100
100
C1-C2 (for certain applications)
–25°C to +40°C
< 95%
< 90%
89
Description of functions
MV and LV connections
Evolis and EVOset 24 kV
fixed, lateral version
MV connection
DE51979
The base circuit breaker is equipped with copper connection terminals with drilled
holes.
The customer connection is carried out easily from outside the circuit breaker on these
connection terminals.
Connection configurations that have undergone type testing are shown
in the Installation Guide.
LV connection
DE51980
The circuit breaker’s LV wiring must be directly connected to the terminal
on the control mechanism via a protection sheath.
90
0
Evolis and EVOset 24 kV
fixed, lateral version
Description of functions
Opening circuit
0
DE56114EN
Composition
(2)
(1) or (3)
Evolis circuit breaker
In its basic version, the circuit breaker includes a shunt opening release (YO1).
The opening circuit can be produced using the following components:
b second shunt opening release (on energizing) (YO2)
b undervoltage release (YM)
b low energy release (Mitop).
EVOset circuit breaker
In its basic version, the circuit breaker includes a low energy release (Mitop).
In addition, the opening circuit can be produced using the following components:
b shunt opening release (YO1)
b undervoltage release (YM).
An external power supply is necessary in this case.
Note: see the table of the releases’ combinations “Order form” page.
Shunt opening release (YO1 and YO2)
Energizing this release causes instant opening of the circuit breaker.
Operating mechanism
Characteristics
DE60094
Power supply
Threshold
See “Order form” page
V AC
0.85 to 1.1 Un
V DC
0.7 to 1.1 Un
V AC
160 VA
V DC
50 W
Consumption
Shunt opening release (1)
Undervoltage release (YM)
DE60089
This release unit causes the systematic opening of the circuit breaker when its
supply voltage drops below a value less than 35% of the rated voltage, even if this
drop is slow and gradual. It can open the circuit breaker between 35% and 70% of
its rated voltage. If the release unit is not supplied power, manual or electrical closing
of the circuit breaker is impossible. Closing of the circuit breaker is possible when
the supply voltage of the release unit reaches 85% of its rated voltage.
DE60091
Undervoltage release (2)
Characteristics
Power supply
Threshold
Consumption
Triggering
Latched
See “Order form” page
Opening
0.35 to 0.7 Un
Closing
0.85 Un
V AC
400 VA
V DC
100 W
V AC
100 VA
V DC
10 W
Low energy release (3)
Low energy release (Mitop)
This release includes a low consumption unit and is specifically used with the Sepam
100LA self-powered relay (“REFLEX MODULE”), or the VIP relay.
Characteristics
Power supply
Threshold
Direct current
0.6 A < I < 3 A
Any tripping due to the Mitop release unit is momentarily indicated by an SDE type
changeover contact (option).
91
Evolis and EVOset 24 kV
fixed, lateral version
DE56115
(5)
Description of functions
Remote control
Function
Remote control enables the remote opening and closing of the circuit breaker.
Composition
The remote control mechanism comprises:
b an electrical motor with gearing
b a shunt closing release (YF) combined with an anti-pumping device
b an operation counter.
Electrical motor with gearing
The electrical motor carries out the automatic rearming of the stored energy unit as
soon as the circuit breaker is closed. This allows the instant reclosing of the device
after opening. The arming lever is only used as a backup operating mechanism
in the case of the absence of the auxiliary power supply.
The M3 contact indicates the end of arming operations.
Characteristics
(4)
Power supply
Threshold
Consumption
Operating mechanism
See “Order form” page
V AC/V DC
0.85 to 1.1 Un
V AC
380 VA
V DC
380 W
DE60093
Shunt closing release (YF)
This release allows the remote closing of the circuit breaker when the operating
mechanism is armed.
Characteristics
DE60151
Electrical motor and gearing (4)
Power supply
Threshold
Consumption
See “Order form” page
V AC
0.85 to 1.1 Un
V DC
0.85 to 1.1 Un
V AC
160 VA
V DC
50 W
The shunt closing release is combined with an anti-pumping relay that enables priority
to be given to opening in the case of a permanent closing order. This thus avoids
the device being caught in an uncontrolled opening-closing cycle.
Shunt closing release (5)
92
0
Description of functions
Indication and locking/interlocking
DE56116
Evolis and EVOset 24 kV
fixed, lateral version
(6)
0
Operation counter
(7)
The operation counter is visible on the front panel.
It displays the number of switching cycles (CO) that the device has carried out.
“Open/closed” auxiliary contacts (OC)
These auxiliary contacts indicate the “open” or “closed” position of the circuit breaker.
The number of contacts available depends on the options chosen on the operating
mechanism.
In the basic configuration, the circuit breaker operating mechanism comprises
a total of:
b 5 normally closed contacts (NC)
b 6 normally open contacts (NO)
b 1 changeover contact (CHG).
(8)
The usage mode for auxiliary contacts is given in the following table:
Options
NC contact
1
0
0
0
1
Remote control
Shunt opening release (each one)
Undervoltage release
Low energy release (Mitop)
Trip circuit supervision
Operating mechanism
NO contact
1
1
0
0
0
DE60087
To know the final number of available contacts, you must deduct the total number
of contacts included in the circuit breaker (5 NC + 6 NO + 1 CHG) from the number
of contacts used indicated in the table below.
E.g.: a circuit breaker equipped with a remote control and a shunt release
has the following contacts available:
4 NC + 4 NO + 1 CHG.
With an undervoltage release instead of a shunt release, this circuit breaker
would have the following available contacts:
4 NC + 5 NO + 1 CHG.
DE51953
Operation counter (6)
Contact characteristics
Rated current
Breaking capacity
220 V (cos ϕ ≥ 0.3)
110/220 V (L/R ≤ 0.02 s)
AC
DC
10 A
1A
0.3 A
Auxiliary contacts (7)
DE60124
Locking of the circuit breaker in the “open” position
This locking system enables the fitting of a Profalux or Ronis captive key type
keylock (right turn type keylock).
The keylock is not part of the kit but can be supplied as an option.
Push button locking
DE56895
Kit to lock the circuit breaker in the “open” position (8)
DE56896
This transparent screen blocks access to the opening and closing push-buttons
on the circuit breaker.
The device enables the opening or closing push button to be locked independently.
It is often associated with an electrical motor.
Locking is achieved either:
b by 2 screws
b by 3 padlocks, not supplied
b by a lead seal.
Padlocking
Lead sealing
93
Evolis and EVOset 24 kV
fixed, lateral version
Description of functions
Wiring diagram
0
DE56117EN
Wiring diagram (principle)
Close CB
Open CB
M
M3
YF +
anti-pumping
Motor
Shunt closing
release
+ anti-pumping
system
Remote control
94
YO1
“Control
mechanism
armed”
indicator contact
YO2
Shunt
opening
release
Mitop
YM
Undervoltage
release
Low energy
release
(Mitop)
Changeover
contact
NO
NC
contacts contacts
Protection, monitoring and control
EVOset: integrated protection chain
by a VIP relay
EVOset 24 kV
fixed, lateral version
0
PE55932
The EVOset circuit breaker has an independent protection
chain
DE56137
The EVOset circuit breaker comprises an Evolis circuit breaker into which is integrated
a protection chain comprising:
b a set of current sensors installed on the lower current terminals of the circuit
breaker: type CEc, CEa or CEb
b a VIP protection relay mounted on the control unit: of type VIP30, VIP35, VIP300P
or VIP300LL
b a “Mitop” low energy release installed on the circuit breaker operating mechanism.
The unit is fully independent and functions without an auxiliary power supply.
Evolis
Mitop
EVOset with a VIP protection unit installed on the front panel
PE55933
CE
VIP
EVOset schematic diagram
Independent protection chain operating principle
VIP300LL protection unit
The protection chain is supplied with power by sensors which supply:
b the “current” information”, processed by the VIP protection unit
b the electrical power required for the whole protection chain to operate;
VIP relay and Mitop release.
All settings are visible and accessible from the front of the device.
To achieve the indicated performance levels, the VIP relay must be used with
the specified sensors. The combination of the unit/sensor is essential in order to
comply with the indicated characteristics and in particular with:
b operation throughout the whole range
b trip times
b precision
b short circuit thermal withstand.
The sensors on each of the phases must be of the same type.
Hardware description for the VIP relay
The VIP relay is mounted in an injected polycarbonate casing which protects it
against run off water and dusty atmospheres.
The front face is protected by a transparent cover with a seal.
This cover can be sealed to prohibit access to settings.
Settings are made with rotary switches. The phase service current and the earthing
current limit are set directly in Amps. Therefore, the graduation on the front face must
be adapted to the rating used on the sensor; this is achieved by a “graduation plate”
must be positioned on the relay when fitted.
Connection is carried out at the rear of the relay using fast-on clips.
95
Protection, monitoring and control
VIP30 and VIP35 protection units
EVOset 24 kV
fixed, lateral version
Use
Independent protection units VIP30 and VIP35 are intended for use on distribution
networks, mainly in MV/LV substations where they provide upstream protection
of the transformer.
DE56138
These are independent relays that do not require any auxiliary power supply;
they are powered by the current sensors. The relays directly actuate the “Mitop”
release.
Mitop
VIP30
VIP35
Simplified connection arrangement
The associated current sensors of type CEc give a setting range of (Is) 8 A to 200 A
for the service current.
VIP30 relay
This provides protection against phase-to-phase faults.
The protection curve is similar to a fuse curve.
Phase protection is achieved using an inverse definite time threshold from 1.2 times
the service current (Is).
VIP35 relay
This provides protection against phase-to-phase faults and against earthing faults:
b the phase protection is identical to the VIP30
b the earthing fault protection functions with the measurement of residual current
calculated from the sum of the sensor secondary currents.
This measurement is made by a CSH30 core balance CT mounted at the back
of the VIP casing.
Earthing protection is definite time; its threshold and time delay can be adjusted.
DE56139
Trip curves
t
t
to >
I
1.2 Is
VIP30/VIP35: phase protection curve
96
I
Io >
VIP35: earth protection curve
0
Protection, monitoring and control
VIP30 and VIP35 protection units (cont.)
EVOset 24 kV
fixed, lateral version
0
Phase protection trip curve:
VIP30 and VIP35
DE56100
T (s)
100
10
1
0.1
max.
typ.
min.
0.01
0
1.2 Is
5
10
15
20
25
30
I/Is
35
97
Protection, monitoring and control
VIP300P protection relay
and VIP300LL
EVOset 24 kV
fixed, lateral version
0
Use
Independent protection units VIP300P and 300LL are intended for use on distribution
networks. They can be used to protect MV/LV transformers, to protect the head
of the industrial installation, but also to protect branches.
Mitop
DE55726
DE55725
These are independent relays that do not require any auxiliary power supply;
they are powered by the current sensors. The relays directly actuate the “Mitop”
release.
t
VIP300
t>
t >>
I
1,2 Is 10 Is
Simplified connection arrangement
I >>
Phase and earthing protection curve
The associated current sensors of type CEa and CEb give a setting range
for the service current (Is) of 10 A to 1250 A.
VIP300P relay
This provides protection against phase-to-phase faults
Phase protection has two independently adjustable thresholds:
b the lower threshold can be chosen to be either definite time or inverse definite time.
It can be executed according to the RI curve.
b the upper threshold is inverse definite time.
The definite time curves are in conformity with standard IEC 60255-3.
They are either of type inverse (SI), very inverse (VI) and extremely inverse (EI).
VIP300LL relay
This provides protection against phase-to-phase faults and against earthing faults:
b the phase protection is identical to the VIP300P
b earthing fault protection functions with the measurement of residual current:
this is carried out based on the sum of secondary currents in the sensors.
As for phase protection, earthing protection has two independently adjustable
thresholds.
Indication
Two indicators show the origin of tripping (phase or earth).
They stay in position after breaking the relay power supply.
Two LED indicator lights (phase and earth) show that the lower threshold has been
exceeded and that the time delay has been started.
98
Protection, monitoring and control
VIP300P protection relay
and VIP300LL (cont.)
EVOset 24 kV
fixed, lateral version
0
DE55727
Trip curves
t>
t>
t >>
t >>
Is 1.2 Is
10 Is I >>
Is
I>
I >>
With an inverse definite time lower threshold
With a definite time lower threshold
Definite time trip curves
DE55728
t (s)
t (s)
100
100
10
10
6
4
3
2
1.5
1
1
6
1
0.6
0.4
0.3
0.2
0.15
0.1
0.07
0.05
0.1
1
10
1 1.2 Is
t (s)
DE55729
100
10
SI curve
t (s)
1000
1000
100
100
10
10
6
4
3
2
1.5
1
0.6
0.4
0.3
0.2
0.15
0.1
0.07
0.05
1
0.1
10
6
4
3
2
1.5
1
0.6
0.4
0.3
0.2
0.15
0.1
0.07
0.05
1
0.1
I/Is
0.01
1 1.2 Is
I/Is
0.01
100
RI curve
VI curve
0.6
0.4
0.3
0.2
0.15
0.1
0.07
0.05
0.1
I/Is
0.01
4
3
2
1.5
1
100
0.01
1 1.2 Is
10
I/Is
100
EI curve
99
EVOset 24 kV
fixed, lateral version
Protection, monitoring and control
Current sensors and test unit
for VIP relays
0
Current sensors for VIP relays
PE55935
In order to achieve the specified performance levels, the VIP protection relays must
be used with the specified sensors. The relay/sensor pairing is indissociable.
in order to comply with characteristics and in particular:
b operation throughout the whole range
b response time
b precision
b short circuit thermal withstand.
Sensor type
CEc
CEa
CEb
Relay
VIP30/VIP35
VIP300P/VIP300LL
VIP300P/VIP300LL
Service current (Is)
8 A to 200 A
10 A to 200 A
63 A to 1250 A
VAP6 test unit for VIP relays
VIP type protection units have a “test” socket to connect a VAP6 test unit.
This portable unit with its own power supply enables the correct functioning
of the protection relay to be checked.
PE55774
CE type current sensors
VAP6 test unit
100
Dimensions
Evolis and EVOset 24 kV
fixed, lateral version
0
Evolis
DE52023
Phase to phase distance E = 250 mm, L = 1095
Ur
Isc
Ir
Weight
24 kV
12.5 kA
630 A
90 kg
DE51971
MV connection on the right hand side
1250 A
630 A
1250 A
20 kA
630 A
1250 A
25 kA
630 A
1250 A
Phase to phase distance E = 300 mm, L = 1195
Ur
Isc
Ir
Weight
24 kV
12.5 kA
630 A
90 kg
16 kA
630 A
1250 A
20 kA
630 A
1250 A
25 kA
630 A
1250 A
16 kA
DE51975
Phase to phase distance E = 250 mm, L = 1095
Ur
Isc
Ir
Weight
24 kV
12.5 kA
630 A
90 kg
DE52024
MV connection on the left hand side
1250 A
630 A
1250 A
20 kA
630 A
1250 A
25 kA
630 A
1250 A
Phase to phase distance E = 300 mm, L = 1195
Ur
Isc
Ir
Weight
24 kV
16 kA
630 A
90 kg
20 kA
1250 A
16 kA
EVOset
DE51973
Phase to phase distance E = 250 mm, L = 1095
Ur
Isc
Ir
Weight
24 kV
12.5 kA
630 A
120 kg
DE51972
MV connection on the right hand side
1250 A
630 A
1250 A
20 kA
630 A
1250 A
Phase to phase distance E = 300 mm, L = 1195
Ur
Isc
Ir
Weight
24 kV
12.5 kA
630 A
120 kg
1250 A
16 kA
630 A
1250 A
20 kA
630 A
1250 A
16 kA
Important
Detailed installation instructions are given in
the “Evolis Installation Guide”. Please consult us.
101
Evolis 24 kV
fixed, lateral version
Offer structure
0
The basic fixed, lateral circuit breaker includes:
b a manual operating mechanism (spring type)
b 1 shunt opening release YO1
b 1 block of auxiliary contacts.
The circuit breaker can receive options.
Basic fixed, lateral circuit breaker
Phase distance (mm)
DE56118
24 kV - 125 kV peak
12.5 kA
250
Right
b
b
b
b
b
b
b
b
630 A
1250 A
630 A
1250 A
630 A
1250 A
630 A
1250 A
16 kA
20 kA
25 kA
Left
b
b
b
b
b
b
b
b
Circuit breaker options
DE56038
DE56033
DE56037
Remote control (see possible choices in combination table below)
Fig. 1
Fig. 2
Fig. 3
1st opening release
Possibility of replacing YO1 by
undervoltage release - YM (fig. 2)
2nd opening release
Shunt opening release - YO2 (fig. 1)
Undervoltage release - YM (fig. 2)
Low energy release Mitop (fig. 3)
Remote control including:
Electrical motor, gear reducer, shunt closing release,
anti-pumping relay, operation counter
Releases combinations table
1
Shunt opening YO1
Shunt opening YO2
Undervoltage YM
Mitop
1
1
1
1
1
1
1
1
1
Indication
DE56040
Operation counter (already included if remote control supplied)
Locking/Interlocking
DE56039
Open position circuit breaker locking device (without lock)
Ronis lock
Profalux lock
Push button disabling
Monitoring device
DE56035
Pilot module (with connecting kit without LV plug)
Diagnosis by Schneider Electric expert
102
300
Right
b
b
b
b
b
b
b
Left
b
b
Evolis 24 kV
fixed, lateral version
Only one of the boxes (ticked X or filled
by
the needed value) have to be considered between each
horizontal line.
Orange box X corresponds to none priced functions.
Order form
0
Basic fixed, lateral circuit breaker
Quantity
Rated voltage Ur
(kV)
Rated short-circuit breaking current Isc
(kA)
Rated normal current Ir
MV connection
(A)
On the left
On the right
250
300
Phase distance (mm)
Colour for push buttons and indicators
IEC standard
Operating mechanism charged/discharged:
ANSI standard
red/black
Push buttons open/closed:
Indicator open/closed:
24
black/white
green/red
white/yellow
charge/discharge
Circuit breaker options
1st opening release (see possible choices in combination table below)
Shunt opening release - YO1
24 Vdc
48 Vdc
Undervoltage release - YM
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
2nd opening release (see possible choices in combination table below)
Shunt opening release - YO2
24 Vdc
48 Vdc
Undervoltage release - YM
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
Low energy release Mitop
Remote control (operation counter already included)
Electrical motor
Shunt closing release - YF
24 Vdc
48 Vdc
24…32 Vdc
48…60 Vdc/ac
100…127 Vdc/ac
220…250 Vdc/ac
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
Operation counter (already included if remote control supplied)
Open position CB locking device (without lock)
Lock
Ronis
Push button disabling
Pilot module (with connecting kit without LV plug)
Diagnosis by Schneider Electric expert (separated order)
Releases combinations table
1
Shunt opening YO1
Shunt opening YO2
Undervoltage YM
1
Mitop
1
1
1
Profalux
1
1
1
1
1
103
Evolis 24 kV
fixed, lateral version
Offer structure
Separated components
0
The following components can be ordered
separately and can be adapted or replaced
by the customer.
Remote control
Ref.
Shunt opening release YO1 or YO2
DE56037
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
50 Hz
50 Hz
60 Hz
AAA10 115
AAA10 116
AAA10 117
AAA10 118
AAA10 119
AAA10 120
AAA10 121
AAA10 122
50 Hz
50 Hz
60 Hz
AAA10 106
AAA10 107
AAA10 108
AAA10 109
AAA10 110
AAA10 111
AAA10 112
AAA10 113
50 Hz
50 Hz
60 Hz
AAA10 124
AAA10 125
AAA10 126
AAA10 127
AAA10 128
AAA10 129
AAA10 130
AAA10 131
Shunt closing release YF
DE56041
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
Undervoltage release YM
DE56033
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
Electrical motor
DE56036
DE56042
24… 32 Vdc
48… 60 Vac/dc
100… 127 Vac/dc
220… 250 Vac/dc
Gear reducer
Locking, interlocking
Ref.
DE56039
Open position circuit breaker locking device (without lock)
Ronis lock
Profalux lock
Push button disabling
Monitoring device
DE56035
Pilot module (consult us)
104
AAA10 027
AAA10 028
AAA10 029
AAA10 030
AAA10 065
AAA10 092
AAA10 058
AAA10 059
48536
EVOset 24 kV
fixed, lateral version
Offer structure
0
The basic fixed, lateral circuit breaker includes:
b a manual operating mechanism (spring type)
b low energy release Mitop
b 1 block of auxiliary contacts
b phase protection relay VIP 30 and associated sensors.
The circuit breaker can receive options.
Basic fixed, lateral circuit breaker
Phase distance (mm)
DE56119
24 kV - 125 kV peak
12.5 kA
630 A
1250 A
630 A
1250 A
630 A
1250 A
16 kA
20 kA
250
Right
b
b
b
b
b
b
300
Right
b
b
b
b
b
b
Circuit breaker options
DE56033
DE56037
Remote control (see possible choices in combination table below)
Fig. 1
Fig. 2
Protection relay
Possibility of replacing VIP30 by:
VIP35 (phase protection + earth)
VIP300P (phase protection)
VIP300LL (phase protection + earth)
VAP6 test unit for VIP relay
Opening release
Shunt opening release YO1 (fig. 1)
Undervoltage release YM (fig. 2)
Remote control including:
Electrical motor, gear reducer, shunt closing release,
anti-pumping relay, operation counter
Releases combinations table
1
Mitop
Shunt opening YO1
Undervoltage YM
1
1
1
1
Indication
DE56040
Operation counter (already included if remote control supplied)
DE56039
Locking/Interlocking
Open position circuit breaker locking device (without lock)
Ronis lock
Profalux lock
Push button disabling
105
EVOset 24 kV
fixed, lateral version
Only one of the boxes (ticked X or filled
by
the needed value) have to be considered between each
horizontal line.
Orange box X corresponds to none priced functions.
Order form
0
Basic fixed, lateral circuit breaker
Quantity
Rated voltage Ur
(kV)
Rated short-circuit breaking current Isc
(kA)
Rated normal current Ir
24
(A)
Phase distance (mm)
250
300
IEC standard
Colour for push buttons and indicators
ANSI standard
red/black
Push buttons open/closed:
Indicator open/closed:
Operating mechanism charged/discharged:
black/white
green/red
white/yellow
charge/discharge
Circuit breaker options
VIP protection relay
VIP30
Service current
VIP35
8-80 A
20-200 A
VIP300P
Service current
VIP300LL
10-50 A
63-312 A
40-200 A
250-1250 A
VAP6 test unit for VIP relay
Opening release (see possible choices in combination table below)
Shunt opening release - YO1
24 Vdc
48 Vdc
Undervoltage release - YM
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
Remote control (operation counter already included)
Electrical motor
Shunt closing release - YF
24 Vdc
48 Vdc
24…32 Vdc
48…60 Vdc/ac
100…127 Vdc/ac
220…250 Vdc/ac
110 Vdc
125-127 Vdc
220 Vdc
110 Vac (50 Hz)
220-230 Vac (50 Hz)
120 Vac (60 Hz)
Operation counter (already included if remote control supplied)
Open position CB locking device (without lock)
Lock
Ronis
Push button disabling
Releases combinations table
1
Mitop
Shunt opening YO1
Undervoltage YM
106
1
1
1
1
Profalux
EVOset 24 kV
fixed, lateral version
Offer structure
Separated components
0
The following components can be ordered
separately and can be adapted or replaced
by the customer.
Remote control
Ref.
Shunt opening release YO1 or YO2
DE56037
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
50 Hz
50 Hz
60 Hz
AAA10 115
AAA10 116
AAA10 117
AAA10 118
AAA10 119
AAA10 120
AAA10 121
AAA10 122
50 Hz
50 Hz
60 Hz
AAA10 106
AAA10 107
AAA10 108
AAA10 109
AAA10 110
AAA10 111
AAA10 112
AAA10 113
50 Hz
50 Hz
60 Hz
AAA10 124
AAA10 125
AAA10 126
AAA10 127
AAA10 128
AAA10 129
AAA10 130
AAA10 131
Shunt closing release YF
DE56041
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
Undervoltage release YM
DE56033
24 Vdc
48 Vdc
110 Vdc
125-127 Vdc
220 Vdc
110 Vac
220-230 Vac
120 Vac
Electrical motor
DE56036
DE56042
24… 32 Vdc
48… 60 Vac/dc
100… 127 Vac/dc
220… 250 Vac/dc
Gear reducer
Locking, interlocking
Ref.
Open position circuit breaker locking device (without lock)
Ronis lock
Profalux lock
Push button disabling
DE56039
AAA10 027
AAA10 028
AAA10 029
AAA10 030
AAA10 065
AAA10 092
AAA10 058
AAA10 059
48536
DE56035
Monitoring device
Pilot module (consult us)
107
Evolis and EVOset 24 kV
fixed, lateral version
Services
The following components can only be adapted or replaced
on site by staff trained by Schneider Electric:
b the “Pilot” monitoring device (except on EVOset)
b remote control mechanism (comprising: electrical motor, gearing, shunt closing
release, anti-pumping relay, operation counter)
b operation counter
b low energy release (Mitop)
b circuit breaker front cover.
108
0
Evolis
Evolis Pilot monitoring device
Panorama
Evolis 17.5 kV fixed, frontal version
Evolis 17.5 kV withdrawable, frontal version
Evolis 24 kV fixed, frontal version
Evolis 24 kV withdrawable, frontal version
Evolis and EVOset 24 kV fixed, lateral version
Description of functions
0
11
15
33
53
67
87
110
109
Evolis Pilot monitoring
device
Description of functions
Fitted on the circuit breaker,
the Pilot monitors its operating conditions.
The Pilot circuit breaker monitoring device has two specific
features
0
PE55697
Monitoring operating conditions
The device monitors external conditions and provides alarms if they are out of
the specified range.
Recording circuit breaker operating data
Similarly to an aircraft black box the monitor device logs the circuit breaker’s key data
over time, allowing a diagnosis on its mechanical conditions.
Pilot main characteristics
Characteristics
Power supply
Service temperature
Consumption
Measurement inputs
Events recording capacity
Conditions record capability
Maintenance notes record capacity
DE56049EN
Energy
supply
V AC 50/60 Hz
V DC
°C
VA or W
V AC 50/60 Hz
V DC
100/250
24/250
100/250
24/250
1000
1000
256 (x 256 characters)
–15% to +10%
–30% to +10%
–25°C to +70°C
<3
–15% to +10%
–30% to +10%
Detailed features
YM
YL
M
DE56050
Communication
Pilot
ON
Reset alarm
Aux. voltage
θ °C
45°C
40°C
50°C
55°C
N > 20000
Operating
I > 360j
110
OK
Monitoring operating conditions:
b the module continuously monitors
v opening auxiliary voltage
v circuit breaker ambient temperature
v number of operations
v time between operations
and sends alarms if the set points are exceeded.
b alarms are visible on the front of the device and can also be transferred to
the LV compartment, or supervision system.
b operating conditions are recorded: minimum and maximum values of auxiliary
voltage and ambient temperature are time-tagged and stored every 24 h.
Recording circuit breaker data
All circuit breaker events are time-tagged and stored (opening, closing, motor
charging, energizing, voltage set point, temperature set point, number of operations,
time between operations).
A circuit breaker expert can analyse the stored data in order to check the correct
mechanical functioning of the circuit breaker, 1000 events are stored in the module.
Servicing note-pad
The device incorporates this useful feature to record any information related to
servicing the circuit breaker (250x250 - character note-pad).
Evolis Pilot monitoring
device
0
DE56051EN
PE60037
Local or remote data collection
5
48
ON
θ °C
OK
Reset alarm
Aux. voltage
45°C
50°C
40°C
55°C
N > 20000
Operating
I > 360j
ernet network
We
bs
er
r
ve
RS
E th
Pilot
DE56030
Description of functions (cont.)
Local use
Alarms are displayed on the device itself.
A dry contact relay collates the faults and can be wired to the low voltage
compartment.
A laptop user-machine Interface can be used to set parameters and to display
and upload data.
Remote use
The monitoring device can be connected to a supervisor or concentrator
for connection to the Web via a local RS485 Modbus network.
The supervisor can display, process and acknowledge alarms.
Data is then either processed in the supervision system or in the remote
web-enabled system.
Easy to install module
The module is mounted on all Evolis 24 kV circuit breakers apart from EVOset.
It is inserted in a special slot on the front face of the circuit breaker
This module may be added at any time during the circuit
breaker’s service life
The module may be factory-mounted within the circuit breaker: connection
and parameter setting, are done by Schneider Electric.
The module may be added after circuit breaker commissioning:
connection, parameter setting and testing, are done by a specialized service
provider (Schneider Electric or other).
The customer is provided with the product manual and the CD-Rom containing
the computerized manual and UMI PC software.
Connection to a withdrawable circuit breaker is carried out with a connection kit with
a LV plug. For a fixed circuit breaker, two types of connection are possible according
to whether or not the circuit breaker has a LV plug:
b a connection kit with LV plug
b a connection kit without LV plug.
Operation and service
The “Pilot” monitoring device can be used on two levels:
b information on operating conditions
b diagnosis of mechanical circuit breaker conditions: performed by a circuit breaker
expert (from Schneider Electric), by analyzing the recorded data.
111
Notes
112
0
89, boulevard Franklin Roosevelt
F - 92500 Rueil-Malmaison (France)
Tel.: +33 (0)1 41 29 85 00
http://www.schneider-electric.com
http://www.merlin-gerin.com
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
This document has been
printed on ecological paper
Production: Schneider Electric - Graphème
Photos: Schneider Electric
Printing: Imprimerie du Pont de Claix/JPF
AMTED305018EN
06-2005
ART807087 © 2005 - Schneider Electric - All rights reserved
Schneider Electric Industries SAS
Was this manual useful for you? yes no